Operation Manual

Smart-UPS

®

X-Series

UPS

750 VA

1000 VA

1500 VA

120V

230V

Overview........................................................................... 1

About the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

Front panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Rear panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Network Management Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

External Battery Pack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Operation.......................................................................... 3

Connect Equipment to the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Basic Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Using the display interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Standard Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Advanced Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Configuration ................................................................... 6

UPS Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Start-up Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

General Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Controllable Outlet Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Model-specific Controllable Outlet Groups . . . . . . . . . . . . . . . . . . . . 9

Using the Controllable Outlet Groups and UPS outlets . . . . . . . . . 10

Customize the Controllable Outlet Groups and the UPS outlets . 10

Network Management Card Settings . . . . . . . . . . . . . . . . . . . . . . . . 11

i Smart-UPS X-Series Operation

Emergency Power Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

EPO Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Normally open contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Normally closed contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Troubleshooting ............................................................ 13

Service and Support...................................................... 15

Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Transport the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

APC Worldwide Customer Support . . . . . . . . . . . . . . . . . . . . . . . . . 16

Smart-UPS Factory Warranty ....................................... 17

LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 ii Smart-UPS X-Series Operation

Overview

About the UPS

The APC

®

by Schneider Electric Smart-UPS

®

X-Series is a high performance uninterruptible power supply (UPS). It provides protection for electronic equipment from utility power blackouts, brownouts, sags, and surges; small utility fluctuations and large disturbances. The UPS also provides battery backup power until utility power returns to safe levels or the batteries are fully discharged.

Safety

Read the Safety Guide included in the package before installing the UPS.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.

Recycle the packaging.

Heavy: The UPS is heavy. If you are installing any external battery packs (XLBPs) with the

UPS, install the XLBPs first, at the bottom of the rack, and install the UPS last, above the

XLBPs.

Product Overview

Front panel

Battery

Battery connector

Display interface

Bezel

Rear panel

Smart slot

External battery pack connector

Outlets

EPO connector

USB port

Serial port

TVSS ground screw

UPS input

Circuit breaker

120 V

Smart-UPS X-Series Operation 1

230 V

2 Smart-UPS X-Series Operation

Specifications

Operating Conditions

This unit is intended for indoor use only. Select a location sturdy enough to support the weight of the

UPS and External Battery Packs (XLBP)..

Do not operate the unit where there is excessive dust, or the temperature or humidity are outside the specified limits.

This unit has front and rear air vents. Allow adequate space for proper ventilation.

Environmental Specifications

Environmental factors impact battery life. High temperatures, poor utility power, and frequent, short duration discharges will shorten battery life.

Temperature

Maximum

Elevation

Humidity

For additional specifications, see the APC Web site at www.apc.com.

Operating

Storage

0° to 40° C (32° to 104° F)

-15° to 45° C (5° to 113° F) charge UPS battery every six months

Operating

Storage

3,000 m (10,000 ft)

15,000 m (50,000 ft)

0% to 95% relative humidity, non-condensing

Installation

UPS

For UPS installation information, see the Smart-UPS X-Series Quick-Start guide that is included with the UPS. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Network Management Card

For installation information, see the user manual provided with the Network Management

Card (NMC). The user manual is also available on the APC Web site at www.apc.com.

External Battery Pack

For installation information, see the Smart-UPS X-Series External Battery Pack Installation guide that is included with the external battery pack. The guide is also available on the enclosed CD and the APC Web site at www.apc.com.

Smart-UPS X-Series Operation 3

Operation

Connect Equipment to the UPS

Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.

1. Connect equipment to the outlets on the rear panel of the UPS.

2. Connect the UPS to the building utility power. Connect the UPS to a two-pole, three-wire, grounded source only.

3. Press the O N /O FF

button on the front panel of the UPS to power the unit and all connected equipment.

4. To use the UPS as a master on/off switch, turn on all the equipment that is connected to the UPS.

See “Controllable Outlet Groups” on page 10 for information on how to use the Controllable

Outlet Groups.

Basic Connections

Serial port: Connect to a computer to use power management software.

USB port: Connect to a computer to use power management software.

External Battery Pack connector: Connect external battery packs to provide extended runtime during power outages. The UPS can support up to five external battery packs.

4 Smart-UPS X-Series Operation

TVSS Ground Screw: The UPS features a Transient Voltage Surge-Suppression

(TVSS) screw for connecting the ground lead on surge suppression devices such as a telephone and network line protectors. When connecting a grounding cable, disconnect the UPS from utility power.

Smart-UPS X-Series Operation 5

6

Display Panel

Overview

Online indicator

UPS Output On/Off button

On Battery indicator

Fault indicator

Replace Battery indicator

Display screen

U P and DOWN buttons

E NTER button

E SCAPE button

APC By Schneider

Electric

Using the display interface

Use the U P

and D OWN

buttons to scroll through the main menu options. Press E NTER to view the submenus under each main menu option. Press E SCAPE

to exit a sub-menu and return to a main menu.

Standard menus

The Standard menus are the most commonly used menus for the UPS.

Menu General Functions

Status View basic information about the UPS:

• Operating mode

• Switched Outlet status, On or Off

• Efficiency of the UPS

• Information about the load

• Battery capacity

• Estimated runtime

• Input and output voltage and frequency

• Information about the last transfer to battery power

• Self-test results

• SmartSlot Card information

Configuration Configure the settings for the UPS:

• Language

• Local power quality: Good, Fair, Poor

• Choose Standard or Advanced menus

• UPS Test settings

• Reset to Factory Defaults

Test & Diags Use the Test & Diags menu to have the UPS perform a self-test.

Smart-UPS X-Series Operation

Menu

About

General Functions

Display information about this unit:

• Unit model number

• Serial number

• Battery information

•Model number

•Installation date

•Suggested battery replacement date

•UPS firmware version

Advanced menus

The Advanced menus provide additional options for the UPS and are available only if the display interface is configured to use the Advanced menus.

Menu General Functions

Status

Configuration Configure advanced settings for the UPS:

• MAIN AND SWITCHED OUTLET GROUPS—delays and settings

• High and lower transfer points

• Sensitivity settings

• Date of last battery replacement

• Output voltage

• Battery settings

• Number of battery packs (not available on all models)

• Reset energy meter

• UPS test settings

Control Control the MAIN AND SWITCHED OUTLET GROUPS to turn on, turn off, shutdown, or reboot.

Test & Diags

View detailed information about the UPS:

• Energy meter

• Load current

• Status of the SWITCHED OUTLET GROUP(S)

• Battery voltage

• Efficiency

Log

About

Perform UPS test and diagnostic functions such as user interface testing, battery tests, and battery calibration.

View the event and error logs for information about any changes to the UPS and any faults.

View information about the unit:

• Hardware version

• Software version

• NMC information (if applicable)

• SmartSlot Card information (if applicable)

Smart-UPS X-Series Operation 7

Configuration

UPS Settings

Start-up Settings

Configure these settings at initial start-up, using the display interface or APC PowerChute

®

software.

Note: During start-up, use the display interface to configure these settings. If nothing is selected, the unit will use the default settings.

Function Factory Default Options

Language English

Local Power

Quality

Good

• English

• French*

• German*

• Spanish*

• Italian*

• Portuguese*

• Good

• Fair

• Poor

Menu Type Standard Standard or

Advanced

Description

The language for the display interface.

*Language options will vary by model.

Select the quality of input utility power.

• If Good is selected, the unit will go on battery power more often to provide the cleanest power supply to the connected equipment.

• If Poor is selected, the UPS will tolerate more fluctuations in power and will go on battery power less often.

If unsure of the local power quality, select Good.

The Standard menus display a limited set of menus and options. The Advanced menus include all parameters.

General Settings

Configure these settings at any time, using the display interface or APC PowerChute ® software.

Function

High transfer point

Low Transfer

Point

Factory Default Options Description

120 V: 140 VAC 120 V: 140-150 VAC To avoid unnecessary battery usage, set the

230 V: 280 VAC 230 V: 280-300 VAC transfer point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition. The

P OWER Q UALITY setting will automatically change this setting.

Note: Use the Advanced Menus to configure this setting.

120 V: 85 VAC

230 V: 170 VAC

120 V: 75-85 VAC Set the transfer point lower if the utility

230 V: 150-170 VAC voltage is chronically low and the connected equipment can tolerate this condition.This setting may also be adjusted using the power quality setting.

Note: Use the Advanced Menus to configure this setting.

8 Smart-UPS X-Series Operation

Function Factory Default Options

Nominal Output 230 V: 230 VAC

Voltage

120 V: 120 VAC

Transfer

Sensitivity

High

Description

230 V: 220, 230, 240

VAC

120 V: N/A

Set the nominal output voltage of the UPS on battery. This is available on 230 V models only.

High, Low, Medium Select the level of sensitivity to power events that the UPS will tolerate.

• High: The UPS will go on battery power more often to provide the cleanest power supply to the connected equipment.

• Low: The UPS will tolerate more fluctuations in power and will go on battery power less often.

Low Battery

Warning

Date of Last

Battery

Replacement

Audible Alarm On

If the connected load is sensitive to power disturbances, set the sensitivity to High.

150 sec Set the value in seconds

The UPS will emit an audible alarm when the remaining runtime has reached this level.

Date set at factory Reset this date when the battery module is replaced.

On/Off The UPS will mute all audible alarms if this is set to Off or when the display buttons are pressed.

The interval at which the UPS will execute a self-test.

Battery Self-

Test Interval

Setting

Reset to Factory

Default

On start-up and • Never every 14 days since • Start-up only the last test • Frequency of test

(days)

No Yes/No Restore the UPS factory default settings.

Smart-UPS X-Series Operation 9

Controllable Outlet Groups

Overview

The rear panel of the UPS has multiple outlets, some are grouped into Controllable Outlet Groups, all of the other outlets are the UPS outlets, which function as an outlet group. All of these groups can independently turn off, turn on, shut down, and reboot connected equipment.

The Controllable Outlet Groups can be commanded to do the following:

• Turn off: Disconnect from power immediately and restart only with a manual command

• Turn on: Connect to power immediately

• Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available

• Reboot: Shut down and restart

In addition, the Controllable Outlet Groups and the UPS outlets can be configured to do the following:

• Turn on or off in a specified sequence

• Automatically turn off or shut down when various conditions occur

Note: If the Controllable Outlet Groups are not configured, all of the outlets on the unit will still provide battery back-up power.

Model-specific Controllable Outlet Groups

Controllable Outlet Group(s)  UPS outlets

750VA, 120 V and 230 V.

1000 VA, 120 V and 230 V.

Using the Controllable Outlet Groups and UPS outlets

The UPS outlets function as a master switch. They turn on first when power is applied, shut off last when there is a power outage and battery run-time has been exhausted.

The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.

1. Connect critical equipment to the UPS outlets (The 1500 VA units do not have UPS outlets.

10 Smart-UPS X-Series Operation

1500 VA, 120 V and 230 V.

Smart-UPS X-Series Operation 11

Connect all critical equipment to the same outlet group.)

2. Connect peripheral equipment to the Controllable Outlet Groups.

– Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short power-off delay

– If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups

– Equipment that needs to reboot independently from other equipment should be added to a separate group

3. Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.

Customize the Controllable Outlet Groups and the UPS outlets

Use the Control menus to change the Controllable Outlet Groups and the UPS outlet settings.

Function Factory Default Options

Name String

Outlet Group

Outlet Group 1

UPS Name String UPS Outlets

Turn On Delay 0 sec Set the value in seconds

Description

Edit these names using an external interface, such as the Network

Management Card Web interface.

Turn Off Delay 0 sec

Reboot Duration 4 sec

Minimum Return 0 sec

Time

Load Shed On

Battery

Disabled

Set the value in seconds

Set the value in seconds

Set the value in seconds

The amount of time the UPS or Controllable

Outlet Group will wait between receiving the command to turn on and the actual startup.

The amount of time that the UPS or

Controllable Outlet Group will wait between receiving the command to turn off and the actual shut down.

The amount of time that the UPS or

Controllable Outlet Group must remain off before it will restart.

The amount of battery runtime that must be available before the UPS or Controllable

Outlet Group will turn on.

When the unit switches to battery power, the

UPS can disconnect power to the Controllable

Outlet Groups to save runtime.

Load Shed Time when On Battery

Disabled

• Shutdown with

Delay

• Shutdown immediately

• Turn off immediately

• Turn off with delay

• Disabled

Set the value in seconds

Configure this delay time, use the L OAD S HED

T IME WHEN O N B ATTERY setting.

The amount of time the outlets will function on battery power before they will turn off.

12 Smart-UPS X-Series Operation

Function

Load Shed On

Runtime

Factory Default Options

Disabled

Disabled

• Shutdown with delay

• Shutdown immediately

• Turn off immediately

• Turn off with delay

• Disabled

Set the value in seconds

Description

When the battery runtime falls below the specified value, the Controllable Outlet Group will turn off.

Configure this time using the L OAD S HED

R UNTIME R EMAINING setting.

When the remaining runtime reaches this level, the Controllable Outlet Group will turn off.

Load Shed On

Runtime

Remaining

Load Shed on

Overload

Disabled • Disabled

• Enabled

In the event of an overload (greater than 100% output), the Controllable Outlet Group will immediately turn off to conserve power for critical loads. The Controllable Outlet Group will only turn on again with a manual command.

Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in the factory. These settings can only be modified using an external interface, like the NMC web interface.

• NMC IP Address Mode

• NMC IP Address

• NMC Subnet Mask

• NMC Default Gateway

Smart-UPS X-Series Operation 13

Emergency Power Off

Overview

The Emergency Power Off (EPO) option is a safety feature that will immediately disconnect all connected equipment from utility power. The UPS will immediately shut down and will not switch to battery power.

Connect each UPS to the EPO switch, even if the UPS units are used in parallel.

The UPS must be restarted for power to return to connected equipment. Press the O N /O FF button on the front panel of the UPS.

Normally open contacts

1. If the EPO switch or relay contacts are normally open, insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block.

Use 16-28 AWG wire.

2. Secure the wires by tightening the screws.

If the contacts are closed, the UPS will turn OFF and power will be removed from the load.

Normally closed contacts

1. If the EPO switch or relay contacts are normally closed, insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block.

Use 16-28 AWG wire.

2. Insert a wire jumper between pins 1 and 2. Secure the wires by tightening the three screws at positions 1, 2, and 3.

If the contacts are opened, the UPS will turn OFF and power will be removed from the load.

Note: Pin 1 is the power source for the EPO circuit, it provides a few milliampere of 24 V power.

If the normally closed (NC) EPO configuration is used, the EPO switch or relay should be rated for “dry” circuit applications, the rating should be for low voltage and low current applications. This normally implies the contacts are gold-plated.

Adhere to all national and local electrical codes when wiring the EPO. Wiring must be performed by a qualified electrician.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the EPO interface only to other SELV circuits. The EPO interface monitors circuits that have no determined voltage potential.

SELV circuits are controlled by a switch or relay properly isolated from utility power. To avoid damage to the UPS, do not connect the EPO interface to any circuit other than a SELV circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

• CL2: Class 2 cable for general use.

• CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

• CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

• CLEX: Limited use cable for use in dwellings and for use in raceways.

• Installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

• Installation in countries other than Canada and the USA: Use standard low-voltage cable in

14 Smart-UPS X-Series Operation

accordance with national and local regulations.

Troubleshooting

Problem and Possible Cause Solution

The UPS will not turn on or there is no output

The unit has not been turned on.

The UPS is not connected to utility power.

The input circuit breaker has tripped.

The unit shows very low or no input utility voltage.

The battery connector plug is not securely connected.

There is an internal UPS fault.

Press the ON button once to turn on the UPS.

Be sure that the power cable is securely connected to the unit and to the utility power supply.

Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.

Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.

Be sure that all battery connections are secure.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

The UPS is operating on battery, while connected to input utility power

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.

There is very high, very low, or distorted input line voltage.

Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.

UPS is emitting an audible beeping sound

The UPS is in normal operation.

None. The UPS is protecting the connected equipment.

UPS does not provide expected backup time

The UPS battery is weak due to a recent outage or is near the end of its service life.

Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.

Check the UPS load display. Unplug unnecessary equipment, such as printers.

The UPS is overloaded.

Display interface indicators flash sequentially

The UPS has been shut down remotely through software or an optional accessory card.

None. The UPS will restart automatically when utility power is restored.

The Fault indicator is lit and the UPS displays a fault message and emits a constant beeping sound

Internal UPS fault.

Do not attempt to use the UPS. Turn the UPS off and have it serviced immediately.

Smart-UPS X-Series Operation 15

Problem and Possible Cause Solution

All indicators are illuminated and the UPS is plugged into a wall outlet

The UPS has shut down and the battery has discharged from an extended outage.

None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.

The replace battery indicator is illuminated

The battery has a weak charge.

Allow the battery to recharge for at least four hours. Then, perform a self-test.

If the problem persists after recharging, replace the battery.

Be sure that the battery connector is securely connected.

The replacement battery is not properly connected.

The display interface has a Site Wiring Fault message

Wiring faults detected include missing ground, hot-neutral, polarity reversal, and overloaded neutral circuit.

If the UPS indicates a site wiring fault, have a qualified electrician inspect the building wiring. (Applicable for 120 V units only.)

Service and Support

Service

If the unit requires service, do not return it to the dealer. Follow these steps:

1. Review the Troubleshooting section of the manual to eliminate common problems.

2. If the problem persists, contact APC Customer Support through the APC Web site,

www.apc.com.

a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.

b. Call APC Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).

c. If the unit is under warranty, the repairs are free. d. Service procedures and returns may vary internationally. Refer to the APC Web site for country specific instructions.

3. Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.

a. For the UPS, always DISCONNECT THE BATTERY before shipping in compliance with U.S.

Department of Transportation (DOT) and IATA regulations. The battery may remain in the unit.

b. Internal batteries may remain connected in the XLBP during shipment, (if applicable, not all units have

XLBPs).

4. Write the RMA# provided by Customer Support on the outside of the package.

5. Return the unit by insured, pre-paid carrier to the address provided by Customer Support.

Transport the unit

1. Shut down and disconnect all connected equipment.

2. Disconnect the unit from utility power.

3. Disconnect all internal and external batteries (if applicable).

4. Follow the shipping instructions outlined in the Service section of this manual.

Smart-UPS X-Series Operation 17

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:

• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests.

www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

www.apc.com/support/

Global support searching APC Knowledge Base and using e-support.

• Contact the APC Customer Support Center by telephone or e-mail.

– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product.

18 Smart-UPS X-Series Operation

Smart-UPS Factory Warranty

LIMITED WARRANTY

American Power Conversion (APC) warrants its Smart-UPS (Products) to be free from defects in materials and workmanship for a period of three (3) years, excluding the batteries, which are warranted for two (2) years from date of purchase. APC's obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. Repair or replacement of a defective Product or part thereof does not extend the original warranty period.

This warranty applies only to the original purchaser who must have properly registered the Product within 10 days of purchase.

Products may be registered online at warranty.apc.com.

APC shall not be liable under this warranty if its testing and examination disclose that the alleged defect in the Product does not exist or that it was caused by end user's or any third person's misuse, negligence, improper installation, testing, operation or use of the Product contrary to APC's recommendations or specifications. Further, APC shall not be liable for defects resulting from:

1) unauthorized attempts to repair or modify the Product, 2) incorrect or inadequate electrical voltage or connection, 3) inappropriate on-site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall APC have any liability under this warranty for any Product where the serial number has been altered, defaced, or removed.

EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF LAW

OR OTHERWISE, APPLCIABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS AGREEMENT OR

IN CONNECTION HEREWITH.

APC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS FOR A

PARTICULAR PURPOSE.

APC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO OBLIGATION

OR LIABILITY WILL ARISE OUT OF, APC's RENDERING OF TECHNICAL OR OTHER ADVICE OR SERVICE IN

CONNECTION WITH THE PRODUCTS.

THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES

AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE APC'S SOLE LIABILITY AND

PURCHASER'S EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. APC'S WARRANTIES RUN

ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD PARTIES.

IN NO EVENT SHALL APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY

FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE USE,

SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN CONTRACT OR TORT,

IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER APC HAS BEEN ADVISED IN

ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, APC IS NOT LIABLE FOR ANY COSTS,

SUCH AS LOST PROFITS OR REVENUE (WHETHER DIRECT OR INDIRECT), LOSS OF EQUIPMENT, LOSS OF USE

OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES,

OR OTHERWISE.

NO SALESMAN, EMPLOYEE OR AGENT OF APC IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS

WARRANTY.

NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT APC'S LIABILITY FOR DEATH

OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT MISREPRESENTATION OR

TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY APPLICABLE LAW.

To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support.

Customers with warranty claims issues may access the APC worldwide customer support network through the APC Web site: support.apc.com. Select your country from the country selection pull-down menu. Open the Support tab at the top of the web page to obtain contact information for customer support in your region. Products must be returned with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase.

Smart-UPS X-Series Operation 19

20 Smart-UPS X-Series Operation

EC Declaration of Conformity

2009

Date of product declaration

Harmonized Standards

Applicable Council

Directives

Type of Equipment

Model Numbers

Manufacturers

American Power Conversion

132 Fairgrounds Rd

West Kingston, RI 02892

USA

American Power Conversion

Ballybritt Business Park

Galway

Ireland

American Power Conversion

Breaffy Rd, Castlebar

Co Mayo

Ireland

EN60950-1; IEC60950-1; EN62040-1-1; EN55022; EN55024;

IEC61000-3-2, 3-3, 4-2, 4-3, 4-4, 4-5, 4-6, 4-11

2006/95/EC; 2004/108/EC

Uninterruptible Power Supply

SMX750I, SMX1000I, SMX1500RMI2U, SMX1500RMI2UNC

American Power Conversion

2nd Street, PEZA

Cavite Economic Zone

Rosario, Cavite

Philippines

American Power Conversion

Lot 10, Block 16, Phase 4

PEZA, Rosario, Cavite

Philippines

American Power Conversion

Lot 3, Block 14, Phase 3

PEZA, Rosario, Cavite

Philippines

APC (Suzhou) UPS Co., Ltd

339 Suhong Zhong Lu

Suzhou Industrial Park

Suzhou Jiangsu 215021

P.R. China

APC Power Infrastructure Co., Ltd

1678 Ji Xian Road, Tong An

Xiamen 361100

P.R. China

APC India Pvt Ltd

187/3, Jigani Industrial Area

Bangalore, Karnataka 562106

India

APC Brazil LTDA

AI. Xingu, 850, Barueri

Alphaville/Sao Paulo 06455-030

Brazil

Importer American Power Conversion (APC) Ballybritt Business Park Galway, Ireland

Place Galway, Ireland Gerry Daly, Managing Director, Europe

01/February/2009

© 2011 APC by Schneider Electric. APC, the APC logo are owned by Schneider Electric Industries S.A.S.,

American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.

990-3458A-001 09/2011

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Key Features

  • Line-Interactive
  • 2.2 kVA 1980 W
  • Waveform: Sine
  • 8 AC outlet(s)
  • Sealed Lead Acid (VRLA)
  • Tower Black

Related manuals