Pelican Z8 Z8 Wireless Zone Controller Professional Installation Guide
Below you will find brief information for Z8 Wireless Zone Controller Z8. The Z8 Wireless Zone Controller is a wireless device that allows you to control your HVAC system from multiple locations in your home. You can use this device to control the temperature, fan speed, and other settings for your HVAC system. The Z8 is compatible with a variety of HVAC systems, including conventional and heat pump systems. It also has a built-in static pressure sensor, which allows you to control the pressure of the air in your HVAC system.
Advertisement
Advertisement
Pelican
Wireless Systems
Pelican
Wireless Systems
Z8 Wireless Zone Controller
Professional Installation Guide
Pelican Wireless Systems, 2655 Collier Canyon Rd. Livermore, CA 94551
Phone: 888.512.0490
Email: [email protected] Website: www.pelicanwireless.com
Table of Contents
Specifications & Equipment
Terminal Designations
Component Installation Locations
Mounting Locations
Installing the Z8
Z8 to Wireless Module
Z8 Wiring Guide
Conventional Unit Wiring Guide
Heat Pump Unit Wiring Guide
Constant Speed Fan
Bypass 0-10VDC Output
Variable Speed Fan 0-10VDC Output
Turn On/Off Variable Speed Fan
Economizer 0-10VDC Output
Bypass and Economizer 0-10VDC Output
Variable Speed Fan and Economizer 0-10VDC Output
10K Type II Analog Input
System Setup
Sequence of Operations
Troubleshoot Wireless Signal
Troubleshoot Z8 Control Outputs
CAUTION AND WARNING
Failure to follow these instructions or a result of improper installation, service, adjustments, maintenance, and/or use can result in personal injury, damage to personal property, and/or cause a hazardous and dangerous situation. Consult a qualified installer, distributor, or Pelican Wireless Systems for assistance or support. Follow all safety codes and regulations and all local and state building codes. Read instructions thoroughly and follow any warnings or notes.
Disconnect power during the installation of this product. All wiring must conform to local and state codes and ordinances. The Z8 is designed to wirelessly communicate with Pelican products only. This guide is designed to assist Pelican Certified Contractors on installing the Z8. For Certification assistance or other support questions contact Pelican Support at 888.512.0490.
PRE-INSTALLATION CONSIDERATIONS
Before installing any zoning system forethought and planning should take place to identify which type of
HVAC unit a Zone Controller will be controlling, how many stages the HVAC has, and how many zoned areas will be communicating with the Zone Controller. Because the Z8 uses wireless communication, plan installation locations appropriately for each product. Contact Pelican Support at 888.512.0490 for further assistance.
2
15
15
16
16
8
11
13
7
8
6
7
3
4
5
23
26
27
17
18
18
20
Specifications
Electrical
Power
Relay Current
Variable Output
Thermistor Input
Pressure Range
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Provided Equipment
Z8
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A 1 C A 2
Pressure
High Low
Wireless Module
24 VAC
1 AMP @ 24V
0-10 VDC
10K Type II
0 – 9" WC
20 Feet 1/8” Plastic Tubing 1 - Static Pressure Sensor 2 - 0.25” diameter 10K Type II Duct Probes
4 - 3/16” Machine Screws
(Wireless Module Mounting)
1 - Electical Box Gasket 1 - 10K Type II Outdoor Temp. Probe
2 - 3/16” Sheet Metal Screws
(Z8 Mounting)
3
TERMINAL DESIGNATIONS
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
A
B
C
D
T
1
T
2
T
3
E
A
HVAC UNIT CONTROL (24VAC Digital Outputs)
Y
Conventional
Compressor Stage 1
W
G
Heat Stage 1
Low/Single Speed Fan
W2
Heat Stage 2
Y2
Compressor Stage 2
G2
High Speed Fan
W3
Heat Stage 3
Y3
Compressor Stage 3
Heat Pump
Y
Compressor Stage 1
W
G
(O/B) Reversing Valve
Low/Single Speed Fan
W2
(AUX) Electric Heat
Y2
G2
Compressor Stage 2
High Speed Fan
W3
(Not Used)
Y3
Compressor Stage 3
Reference Pages:
Pages 8 - 10: Wiring Guide for Conventional HVAC units from 1-3 stages.
Pages 11 - 13: Wiring Guide for Heat Pump HVAC units from 1-3 stages and Aux Heat.
Pages 13 - 14: Wiring Guide for Constant Speed and High/Low Speed Fan applications.
Page 15 - 10: Wiring Guide for Bypass, Variable Speed Fan, and Economizer control.
4
B
ELECTRICAL CONNECTIONS
C
R
Rc
D
Common 24 VAC
24 VAC Power
Two Transformer 24 VAC
Data
D
STATIC PRESSURE SENSOR
High
Duct Pressure
Low
Outside/Ambient Pressure
C
0-10VDC OUTPUTS
A
1
C
A
2
0-10 VDC
Common
0-10 VDC
E
10K ANALOG INPUTS
T
1
Input Terminal
T
2
Input Terminal
T
3
Input Terminal
Note:
“T” Terminals can accept either Type 2 10K temperature probe or a Dry Contact Sensor input to send an alarm notification through your Pelican Site
Manager (pages 18-19).
COMPONENT INSTALLATION LOCATIONS
The Z8 is not waterproof, but is designed to operate in environments from -20
˚
F to 140
˚
F. If installed outside, the Z8 must be installed inside of the HVAC unit or in a plastic waterproof case outside of the HVAC unit.
The Z8 comes with a wireless communicator (Wireless Module) which it uses to communicate with Pelican’s wireless network. Wireless signals will not communicate through metal, so if the Z8 is installed inside of an enclosed metal HVAC unit or box, you will need to remove the Wireless Module and install it outside of the metal enclosure. (NOTE: If the Z8 is installed inside of a building and/or is not enclosed in metal, you do not need to remove the Wireless Module).
The Wireless Module is water and weather proof. Install the Wireless Module onto a PLASTIC electrical box with the provided gasket placed in between to keep water out. Using three wires, connect the Wireless
Module’s D, C, and R terminals to the Z8’s D, C, R terminals (illustrated on page 7). The Wireless Module can be wired up to 500 feet away from the Z8 with non-shielded wire.
If the roof has a metal decking, install the Wireless Module below the metal roof line so that the wireless can reach into the building.
The illustration on the next page shows where to mount the Z8 and the Wireless Module if installing inside a rooftop HVAC unit.
5
Mounting Locations
Z8
Wireless Module
Static Pressure
Sensor
Return Air
Temperature
Probe
Modulating
By-Pass Damper
Z8
Supply Air
Temperature
Probe
Wireless Module
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Wire Channels
Mounting on a Flat Surface - use provided 3/16” sheet metal screws for mounting Z8.
Note: The Z8 is NOT waterproof and it should be installed inside of the HVAC unit or a waterproof box. If the Z8 is installed in a metal enclosure, remove the
Wireless Module and install it outside of the HVAC unit or metal enclosure on a PLASTIC electrical box.
Installing Wireless Module Outside: Install the wireless module onto a horizontally mounted PLASTIC electrical box and use the provided gasket placed in between the lip of the wireless module and the lip of the plastic electrical box to keep water out. The Wireless
Module is weather and water proof.
6
Installing the Z8
1. Remove the Z8’s front cover by placing two fingers into the indents found on both sides of the Z8 and pulling the front cover away from the back panel. This will expose the terminals and mounting holes.
Side Indents
2. Place the Z8’s back plate onto the flat mounting surface. Mark the two mounting holes. Drill two 3/16” holes into the surface you will be mounting the Z8 on. Note: There are two different wiring channels, one located on the side and the other for wires coming from behind the Z8. There are also two channels for running the static pressure tubes.
Mounting Hole
Mounting Hole
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Wire Channels
Pressure Tube Channels
3. Follow the wiring instructions found in this installation guide for wiring the correct terminals to the specific HVAC unit the Z8 is going to control.
4. If the Z8 is installed inside of an HVAC unit or enclosed in a metal waterproof box, you will need to separate the Wireless
Communicator from the Z8 by simply pulling it straight out. The Wireless Communicator is water and weather proof and can be installed onto a plastic electrical box outside of the metal enclosure. Below you will find wiring instructions for connecting the Z8 to the Wireless Communicator
5. Once all components are wired correctly, simply snap the front cover back onto the Z8.
Wiring Guide: Z8 to Wireless Module
The Wireless Module should only be removed from the Z8 if the Z8 is installed in an enclosed metal box or is to far away from
Pelican’s wireless network. The Wireless Module can be installed up to 500 feet away from the Z8.
With the Wireless Module remove: connect the R, C, and D terminals from the Wireless Communicator to matching terminals on the Z8.
Z8
Wireless Module
C R D
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Wire Channels
7
Note: Troubleshoot instructions are found on Page 26.
Z8 WIRING GUIDE
The Z8 is wired directly to the HVAC unit it will be controlling. The Z8 communicates using wireless to all zones and does not require any hardwired connection with zoned dampers or thermostats.
The following guide illustrates how to wire the Z8 to Conventional HVAC units from 1 to 3 stages of Heat and/or Cool and Heat
Pump units from 1 to 3 stages of Heat and/or Cool. If your installation does not fall into one of the following categories or you have further questions contact Pelican Support at 888.512.0490.
For additional wiring instructions (Analog Output and 10K Type II thermistor inputs) proceed to pages 15 - 19.
CONVENTIONAL UNIT WIRING GUIDE
1 Stage Heat & 1 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y W G
HVAC Unit
C R
24VAC
Supply Voltage
1 Stage Heat & 1 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1 V1
Compressor Heat
(Gas or Electric)
24VAC Supply Voltage
V1
— Incoming Line Voltage
8
2 Stage Heat & 2 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y W G W
2
Y
2
C
HVAC Unit
R
24VAC
Supply Voltage
2 Stage Heat & 2 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1
V1 V1 V1
Compressor
Stage 1
Heat Stage 1
(Gas or Electric)
Heat Stage 2
(Gas or Electric)
Compressor
Stage 2
24VAC Supply Voltage
V1
— Incoming Line Voltage
3 Stage Heat & 3 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y W G W
2
Y
2
W
3
Y
3
C
HVAC Unit
R
24VAC
Supply Voltage
9
3 Stage Heat & 3 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1
V1 V1
V1
V1
V1
Compressor
Stage 1
Heat Stage 1
(Gas or Electric)
Heat Stage 2
(Gas or Electric)
Compressor
Stage 2
Heat Stage 3
(Gas or Electric)
Compressor
Stage 3
V1
— Incoming Line Voltage
24VAC
Supply Voltage
10
HEAT PUMP UNIT WIRING GUIDE
1 Stage Heat & 1 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y O/B G
HVAC Unit
C R
24VAC Supply Voltage
1 Stage Heat & 1 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1
Compressor
Reversing Valve
24VAC
Supply Voltage
V1
— Incoming Line Voltage
2 Stage Heat & 2 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y O/B
Y
2
G
HVAC Unit
C R
24VAC
11
Supply Voltage
2 Stage Heat/ 2 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1 V1
Compressor
Stage 1
Reversing Valve
Compressor
Stage 2
24VAC Supply Voltage
V1
— Incoming Line Voltage
3 Stage Heat/3 Stage Cool (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y O/B Y
2
Y
3
HVAC Unit
G C R
24VAC
Supply Voltage
3 Stage Heat/3 Stage Cool (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1 V1 V1
V1
Compressor
Stage 1
Reversing Valve
Compressor
Stage 2
Compressor
Stage 3
12
24VAC
Supply Voltage
V1
— Incoming Line Voltage
Aux Heat (Direct Interface Wiring)
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
Pressure
High Low
V1
Aux Heat
(Gas or Electric)
24VAC
Supply Voltage
V1
— Incoming Line Voltage
CONSTANT SPEED FAN WIRING GUIDE
Single Speed Fan (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y W G
HVAC Unit
C R
24VAC Supply Voltage
13
Single Speed Fan (Direct Interface Wiring)
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
Pressure
Low
V1
Fan Motor
24VAC Supply Voltage
V1
— Incoming Line Voltage
High/Low Speed Fan (Conventional Thermostat Terminals)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Y W G G
2
HVAC Unit
C R
24VAC Supply Voltage
High/Low Speed Fan (Direct Interface Wiring)
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
V1 V1
High Speed
Fan Motor
Low Speed
Fan Motor
14
24VAC
Supply Voltage
V1
— Incoming Line Voltage
BYPASS 0-10VDC OUTPUT WIRING GUIDE
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
Pressure
High Low
Supply Voltage 24VAC
C 24VAC 0-10V input
Ambient Air
(mandatory)
Supply Air
Static Pressure
Probe
(mandatory)
Bypass Modulating
Damper Actuator
VARIABLE SPEED FAN 0-10VDC OUTPUT WIRING GUIDE
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
Pressure
High Low
Supply Voltage
24VAC
C 24VAC 0-10V input
Ambient Air
(mandatory)
Supply Air
Static Pressure
Probe
(mandatory)
Variable Speed Fan
15
ON/OFF OUTPUT FOR VARIABLE SPEED FAN
THAT MANAGES ITS OWN STATIC PRESSURE
Z8
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Supply Voltage
24VAC
C 24VAC
Optional Uage: for monitoring and recording duct static pressure
Supply Air
Static Pressure
Probe (mandatory)
Ambient Air
(mandatory)
Variable Speed Fan
ECONOMIZER 0-10VDC OUTPUT
Note: Connect economizer actuator to terminal A1.
IF YOU ARE CONTROLLING A BYPASS AND ECONOMIZER GO
TO PAGE 17.
IF YOU ARE CONTROLLING A VARIABLE SPEED FAN AND
ECONOMIZER GO TO PAGE 18.
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
T
1
T
2
T
3
Pressure
High Low
C 24VAC 0-10V input
24VAC
Econoimzer Modulating
Damper Actuator
16
10K Outside Air
Temperature Probe
(mandatory)
Supply Voltage
ECONOMIZER OPEN/CLOSE ACTUATOR OR ON/OFF OUTPUT
Note: Connect economizer actuator to terminal G2.
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
10K Outside Air
Temperature Probe
(mandatory)
Pressure
High Low
24VAC C
24VAC
Supply Voltage
Econoimzer Damper
Actuator
COMBINED BYPASS AND ECONOMIZER 0-10VDC OUTPUTS
Note: Connect economizer actuator to terminal A1 and Bypass to terminal A2.
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
10K Outside Air
Temperature Probe
(mandatory)
Pressure
High Low
Supply Voltage
24VAC
C 24VAC 0-10V input C 24VAC 0-10V input
Ambient Air
(mandatory)
Supply Air
Static Pressure
Probe
(mandatory)
Econoimzer Modulating
Damper Actuator
Bypass Modulating
Damper Actuator
17
COMBINED VARIABLE SPEED FAN AND ECONOMIZER 0-10VDC OUTPUTS
Note: Connect economizer actuator to terminal A2 and Variable
Speed Fan to terminal A1.
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
10K Outside Air
Temperature Probe
(mandatory)
Pressure
High Low
Supply Voltage 24VAC
C 24VAC 0-10V input C 24VAC 0-10V input
Ambient Air
(mandatory)
Supply Air
Static Pressure
Probe
(mandatory)
Variable Speed Fan
Economizer Modulating
Damper Actuator
10K TYPE II ANALOG INPUTS
This section covers the wiring options for the Analog ‘T terminals. These terminals can be used for either temperature monitoring or for a dry contact interface to generate an alarm notification through your Pelican Site Manager.
Default Options:
T
1
Supply Air Temperature
T
2
Return Air Temperature
T
3
Outside Air Temperature
T
1
T
2
T
3
Z8
10K Type 2 Temperature Probe(s)
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
18
DRY CONTACT INTERFACE FOR ALARM NOTIFICATIONS
Y W G W2 Y2 G2 W3 Y3
Z8
C R Rc D A
1
C A
2
Pressure
High Low
T
1
T
2
T
3
Note: Dry contact relay can be wired to any of the ‘T’ termainls.
19
SYSTEM ONLINE SETUP
All configuration is done Online using the Pelican Site Manager. A Pelican Gateway must be installed, connected to the Internet, and able to wirelessly communicate with a Z8 OR Z24 to access the zone controller’s configuration options. Power must be provided to each product to configure.
Step 1: Install a Pelican Wireless Gateway, setup a Pelican Site Manager, and log onto your Pelican Site
Manager using a Web browser on any Smartphone, Tablet, or PC.
Step 2: Install the Z8 or a Z24 following their proper installation guides.
Step 3: Follow the Damper Install guide and install all TS200, TCM1, and/or RT1-DC/AC. All devices will automatically connect with the Pelican Gateway. You will recieve a new notification on your Pelican Site
Manager identifing that new product have been installed. Select Configure on the far right of the product you want to setup.
Step 3: Name the Device.
Step 4: Follow the configuration guides below to properly configure the Z8.
Step 5: Once everything is installed, setup, and configured, proceed to page 26 for start-up process.
SYSTEM OPERATION CONFIGURATION
System Type: Set to Conventional or Heat Pump
AUXILIARY HEAT: Set to Disable to not use or if there is no auxiliary heat. Set to Auxiliary to utilize auxiliary heat, if needed. Set to Emergency to recieve a notification if the auxiliary heat is used.
Heat Stages: Set to the number of available heat stages.
Cool Stages: Set to the number of available cool stages.
Fan Stages: Set to the number of available fan stages.
IMPORTANT:
If the Variable Speed Fan is self regulating or it is being controlled by another controller, and you want the
Z8 to tell the other controller when to turn the Variable Speed Fan On and Off - set Fan Stages to ‘1’.
If the Z8 is controlling a 0-10VDC Variable Speed Fan - set Fan Stages to “Variable”.
Heat Needs Fan: Set to YES if the Z8 needs to call for FAN when it calls for HEAT.
20
VARIABLE SPEED FAN CONFIGURATION OPTIONS
SET VARIABLE SPEED FAN TO ON TO CONTROL A 0-10VDC VARIABLE SPEED FAN.
Minimum Operating Speed: Set the minimum required operating fan speed for when Heat or Cool is being called. This is set as a percentage of maximum available speed.
Configuring STATIC PRESSURE identifies how the Z8 should manage the bypass damper.
IMPORTANT: If the Variable Speed Fan is self regulating or it is being controlled by another controller, and you want the Z8 to tell the other controller when to turn the Variable Speed Fan On and Off - set Variable
Speed Fan to OFF and instead, set Fan Stages, under System Operations, to ‘1’.
BYPASS CONTROL CONFIGURATION OPTIONS
SET BYPASS CONTROLLER TO ON TO CONTROL A 0-10VDC MODULATING BYPASS DAMPER
ACTUATOR.
Damper Voltages: Set the output voltage range for opening and closing the bypass damper. This is most commonly either 0-10VDC or 2-10VDC:
Open: Set to the voltage output for fully open.
Closed: Set to the voltage output for fully closed.
Configuring STATIC PRESSURE identifies how the Z8 should manage the bypass damper.
STATIC PRESSURE CONFIGURATION OPTIONS
CONFIGURE STATIC PRESSURE BASED ON THE REQUIREMENTS OF YOUR SYSTEM DESIGN.
Target Operating Static: Set to the targeted static pressure for running Heat or Cool. The Z8 will modulate either a bypass damper or a variable speed fan with the goal of maintaining this target static.
Target Circulation Static: Set to the targeted static pressure for running FAN. The Z8 will modulate either a bypass damper or a variable speed fan with the goal of maintaining this target static. Setting the
Circulation Static lower than the Operating Static allows for a quiter operation when only FAN is requested by the zones.
Minimum Static: Set the minimum static pressure for when Heat or Cool is being called. The Z8 use this setting to protect the HVAC unit. If Minimum Static is detected, during a call for heat or cool, the Z8 will immediatly turn off the compressor, preventing the coils from freezing over. The Z8 will also generate a
Notification.
Maximum Static: Set the maximum static pressure for when Heat or Cool is being called. The Z8 use this setting to protect the ducts. If Maximum Static is ever detected, the Z8 will immediatly turn off the entire system, preventing the ducts from being damaged; it will then go into a 10 minute reset cycle. The Z8 will also generate a Notification.
21
ECONOMIZER CONFIGURATION OPTIONS
SETTING ECONOIMZER TO ON PROVIDES TWO OPTIONS:
1) If the Economizer is controlled by the HVAC unit or a seperate controller, but you
to ON and set a High Limit Temperature.
want the Z8 to notify the seperate controller if the zones needs or can use outside air: turn
2) If the Z8 is directly controlling a 0-10VDC Economizer damper actuator, turn
VARIABLE DAMPER to ON.
High Limit Temperature: Set to maximum outside air temperature. Above this temperature the Economizer will be disabled.
Variable Damper: Set to ON if the Z8 is directly controlling a 0-10VDC Economizer damper actuator.
Damper Voltages: Set the output voltage range for opening and closing the economizer damper actuator.
This is most commonly either 0-10VDC or 2-10VDC:
Open: Set to the voltage output for fully open.
Closed: Set to the voltage output for fully closed.
Minimum Damper Position: Set the minimum damper position for fresh air ventilation.This is set as a percentage of the maximum open position.
TEMPERATURE SENSER CONFIGURATION OPTIONS
THE Z8 USES THESE TEMPERATURE INPUTS TO PROPERLY CONTROL AND MONITOR THE ENTIRE
HVAC SYSTEM.
Input Sensor T1: Defaulted as Supply Air, but can be configured for various temperature inputs.
Input Sensor T2: Defaulted as Return Air, but can be configured for various temperature inputs.
Input Sensor T3: Defaulted as Outside Air, but can be configured for various temperature inputs.
INPUT POWER CONSUMPTION
To be able to record actual HVAC consumption, fill in each Stages energy consumption in either KW, BTU,
TON, or WATT.
If you set to TON, Pelican will calculate KW consumption based on a 13 EER rated HVAC unit.
22
SEQUENCE OF OPERATIONS
COOLING OPERATION
Outputs
Terminal
Y
Y2
Y3
W
Description
Compressor Control
Compressor Control
Compressor Control
O/B Control for Heat Pump System
Inputs
Terminal
T1
T2
Description
Supply Temperature
Return Temperature
Operation
1. Thermostats request cooling using the wireless network.
2. The Zone Controller energizes compressor stages when cooling demand is present.
3. In single duct systems, compressor stages are automatically held off if heating is active. This will continue until heating demand is satisfied.
4. Compressor stage outputs (Y, Y2, Y3) are energized based on system configured cooling stages and differential temperature between supply and return air. Target supply and differential temperature are adjusted automatically based on feedback from zoned thermostats and active settings in each zone.
5. Damper controllers are notified using wireless signals when they can open or close based on the availability of cool air in the system.
Safeties
Built-in system safeties such as coil temperature and internal pressure should be left in place since the Zone
Controller does not have provisions for monitoring or acting on these items. The Zone Controller does augment the built-in safeties in the following way:
1. Compressors will be shut down if the duct static pressure falls below acceptable levels.
2. A 4 minute short cycle timer is enforced for each compressor.
3. If all zone dampers are closed the compressors will be shut down.
23
HEATING OPERATION
Outputs
Terminal
W
W2
W3
Description
Heating Control
Heating Control
Heating Control
Inputs
Terminal
T1
T2
Description
Supply Temperature
Return Temperature
Operation
1. Thermostats request heating using the wireless network.
2. The Zone Controller energizes heating stages when demand is present.
3. In single duct systems, heating stages are automatically held off if cooling is active. This will continue until cooling demand is satisfied.
4. Heat stage outputs (W, W2, W3) are energized based on system configured heat stages and differential temperature between supply and return air. Target supply and differential temperature are adjusted automatically based on feedback from zoned thermostats and active settings in each zone.
5. Damper controllers are notified using wireless signals when they can open or close based on the availability of warm air in the system.
Safeties
Built-in system safeties should be left in place since the Zone Controller does not have provisions for monitoring or acting on these items. The Zone Controller does augment the built-in safeties in the following way:
1. Heat stages will be shut down if the duct static pressure falls below acceptable levels.
2. Heat stages will be shut down if supply temperatures exceed the maximum allowed setting.
3. If all zone dampers are closed the heat will be shut down.
VARIABLE SPEED FAN OPERATION
Outputs
Terminal
G
G2
A1
Description
Fan Stage 1 Control
Fan Stage 2 Control
Variable Speed Control
Inputs
Terminal
High
Low
Description
Duct Static Pressure
Outside Pressure
24
Operation
1. Thermostats request heating, cooling, or fan using the wireless network.
2. The Zone Controller energizes fan stages when demand is present.
3. If variable speed fan control is enabled the Zone Controller will maintain target static pressure based on measured static pressure from it's integrated pressure sensor.
4. Target static pressure can be configured for different levels depending on whether simple air circulation is active or heating/cooling is active.
5. Damper controllers are notified using wireless signals when they can open or close based on the availability of air in the system.
Safeties
Built-in system safeties should be left in place since the Zone Controller does not have provisions for monitoring or acting on these items. The Zone Controller does augment the built-in safeties in the following way:
1. The fan will be shut down if the duct static pressure exceeds acceptable levels.
2. If all zone dampers are closed the fan will be shut down.
ECONOMIZER OPERATION
Outputs
Terminal
G2
A1, A2
Description
Economizer On/Off Control
Variable Damper Control
Inputs
Terminal
T1
T2
T3
Description
Supply Temperature
Return Temperature
Outside Temperature
Operation
1. The economizer is operational during cooling cycles and ventilation cycles.
2. During operational mode, the economizer will always open to at least the minimum open position to provide outside air for ventilation.
3. When the fan is off, the economizer will be fully closed.
4. The economizer will compare supply, return and outside air temperatures to automatically regulate the mix of outside and return air entering the system.
5. The Variable damper control output will modulate the economizer damper to adjust the air mixture.
Note
1. The economizer controller does not monitor building static pressure. A separate system should be implemented to manage proper building static pressure.
2. The Economizer controller can be optionally used to signal a built-in economizer to open or close using only the G2 output signal of the Zone Controller.
3. The economizer will hold off cooling compressor stages if outside air temperature is sufficiently low to allow building cooling to be satisfied.
25
BYPASS OPERATION
Outputs
Terminal
A1, A2
Description
Variable Damper Control
Inputs
Terminal Description
High
Low
Duct Static Pressure
Outside Pressure
Operation
1. The bypass is operational during heating, cooling and ventilation cycles.
2. When the system is not active the bypass controller will position the damper in the fully open position.
3. When the system is fully operational, the bypass damper will be gradually closed until the target static pressure is achieved.
4. As the static pressure varies due to changes in active zones the bypass damper will be automatically modulated to maintain the target static pressure.
Operation with Variable Speed Fan
1. The bypass will start in the half-open position.
2. The bypass will close if the variable speed fan is able to maintain proper static pressure.
3. If the variable speed fan is running at it's minimum setting and the static pressure exceeds the target static pressure, the bypass controller will open the bypass damper to maintain target static pressure.
TROUBLESHOOT WIRELESS SIGNAL
Z8
Wireless Status:
Off - Initializing
1 Second Blink - Establishing Wireless Connection
Solid - Communicating Over Wireless
Internal Status:
Off - No Power
1 Second Blink - Initializing
Solid - Operational
T
1
T
2
T
3
Y W G W2 Y2 G2 W3 Y3 C R Rc D A
1
C A
2
Pressure
High Low
Wireless Module
C R D
Wireless Connection Identifier:
Off - No Power
1 Second Blink - Establishing Wireless Connection
Blink Every 15 sec - Communicating Over Wireless
26
TROUBLESHOOT Z8 CONTROL OUTPUTS
ON YOUR PELICAN SITE MANAGER YOU CAN TEST THE SIGNAL OUTPUTS OF THE Z8 TO
PROVIDE IMMEDIATE FEEDBACK THAT EACH OF THE Z8’s OUTPUTS ARE CONTROLLING THE
CORRECT PART OF THE SYSTEM.
THESE OPTIONS LET YOU TURN ON AND OFF THE CONTROL SIGNALS. IT ALSO ALLOWS YOU TO
DYNAMICALLY ADJUST THE O-10VDC OUTPUTS FOR TESTING A VARIABLE SPEED FAN,
MODULATING BYPASS DAMPER ACTUATOR, AND MODULATING ECONOMIZER DAMPER.
IMPORTANT: THE SIGNAL OUTPUT CONTROL IS A MASTER OVERIDE FEATURE. ALWAYS SET
SIGNAL OUTPUTS BACK TO ORIGINAL SETTING!!
27
Pelican Wireless Systems, 2655 Collier Canyon Rd. Livermore, CA 94551
Phone: 888.512.0490
Email: [email protected] Website: www.pelicanwireless.com
37-0002
Download
Advertisement
Key features
Wireless control of HVAC systems
Control temperature, fan speed, and other settings
Compatible with conventional and heat pump systems
Built-in static pressure sensor
Multiple zone control
Easy to install
Automatic system operation
Advanced safety features
Frequently asked questions
The Z8 Wireless Zone Controller is a device that allows you to control your HVAC system from multiple locations in your home. The Z8 communicates wirelessly with your HVAC system, which makes it easy to control the temperature and other settings for your HVAC system without having to run any wires to the controller.
The Z8 Wireless Zone Controller is compatible with both conventional and heat pump HVAC systems. It also has a built-in static pressure sensor, which allows you to control the pressure of the air in your HVAC system.
The Z8 Wireless Zone Controller is easy to install. The instructions in this manual will guide you through the installation process.
The Z8 Wireless Zone Controller has a number of key features, including wireless control, compatibility with conventional and heat pump systems, a built-in static pressure sensor, multiple zone control, easy installation, automatic system operation, and advanced safety features.