Nedap AP4801, AP4001 Proximity Reader Installation sheet
Publicitate
Publicitate
AP4801 / AP4001
4 in 1 Nedap Proximity Reader Installation sheet
GENERAL
Nedap 4 in 1 Proximity Reader suitable for connecting 4 Nedap antenna’s thus controlling 4 doors.
Capable of interfacing with most locks, turnstiles and speed gates on the market. Parameters are remotely monitored
4 relays using floating contacts for lock control (with status indication). 8 functionality selectable and supervised digital inputs. So for each reader one relay and 2 inputs can be available.
The firmware in the AEpack combined with the behaviour components determines the functionality.
The AP4801 is an AP4001 with additional microprocessor board (so acts like AP8001 + AP4001)
PCB LAYOUT and INDICATIONS
BE: BUS ERR (red)
AE: ADDR ERR(red)
ON No AEpu connection (AEpack passive)
Flashing 5 Hz No valid AEpack address (or already in use)
Flashing 20 Hz AEpack address being modified
ON
CE: CB ERR(red)
AEpu not active
Slow blinking
Very fast blinking ALT mode active
Fast blinking
1 short flash
2 short flashes
3 short flashes
STS: STATUS (blue)
AEpack assigned to AEpu (operating)
Downloading or error during loading
AEpack not coupled
Firmware present but not active
No firmware present
POW: POWER (green) ADDRESS SWITCHES
OFF AEpu operational, Status led gives correct state
AP4801 Processor board
AP4001 / AP4801
RY2
AEbus
RY1
~ - ~ +
ON
Tamper switch
BE
AE
CE
RY4
POW
STS
AEbus Termination
ID1
ID2
RY3
Turn for correct address
ID3
(99 for AP48xx)
ID4
Network
Battery
1
Service port Peripheral connections (4*)
3
LINK (green)
Rx/Tx (yellow)
2
Blink Communication on Ethernet
RY2, 1, 4, 3 (green)
4
ALT mode button
ID1..4 (green)
Flashing 0,5 Hz Card detected
PERIPHERAL CONNECTIONS (4*, each connector identical)
1
+5V
2
NC
3
COM
4
NO
5 6 7
IN1 GND IN2
8 9 10 11 12
Blanked connectors are not used do not connect
13 14 15 16
ANT GND UL GND NA GND
Power +5VDC
Output
Floating contact Free definable
Cable shield to GND and metal case
Relay output inputs
Remark: For each connector the numbering is increased
(for connector nr 3: IN5 and IN6 and RY3)
UL GND NA
Antenna: E.g. RefleXS 130
Date : 7 January 2005 Version: 1 Part.no.: 5266440
This information is furnished for guidance, and with no guarantee as to its accuracy or completeness; its publication conveys no licence under any patent or other right, nor does the publisher assume liability for any consequence of its use; specifications and availability of goods mentioned in it are subject to change without notice; it is not to be reproduced in any way, in whole or in part, without the written consent of the publisher.
© Nedap N.V., IDEAS P.O. Box 103 NL-7140 AC GROENLO The Netherlands Page 1 of 4
®
AP4801 / AP4001
Relay contacts are dry contacts. If supply voltage is needed, make interconnections between Power Supply and relay
All inputs are supervised (software selectable). See diagram for connections.
INx
R=4K7
GND
Contact
NA and UL led: UL – NA: 5V, R=220 included, LED cathode to GND.
CONNECTIONS
Power
GND
5V
COM
NO
NC
+
-
UL/NA
Door lock
Connect protection diode as near as possible to electrical terminals of lock
GND
R=220
AP4xxx series are NOT hot-swappable, so changing or adding these AEpacks or connections may only be done when Power is switched OFF.
Cables outside housing: Use always shielded cables and connect shield to AP4XXX connector metal case. top view
POWER CONNECTIONS
AP4xxx can get the power from the AEbus (check maximum power) or from separate Power Supply. Power for Lock must be connected external to Relay
(see above). Connections: + ~ and - ~ (both AC and DC). rear view
NETWORK CONNECTION (AP48xx only)
Network is connected using the RJ-45 network connector. (No indication 10/100 Mbit)
SERVICE CONNECTOR (AP48xx only)
For configuration the serial port on 9 pin SUB-D connector is used. Configuration is done by using hyperterminal. See
AEOS installation manual for more information.
SYSTEM CONFIGURATIONS (how to connect AP4xxx and AEpacks)
AP4xxx only
Total bus length: max 1000m. (BitRate: 1)
AP4xxx with single AEpacks AX2002
2 (Tx) Rx (Receive data)
5 (GND) GND
3 (Rx) Tx (Transmit data)
7 (CTS) Clear to send (Output)
8 (RTS) Request to send (Input)
AP4xxx with single AEpacks
Total bus length: max 5m. (BitRate: 0)
Single AEpacks with AP4xxx
Total bus length: max 300m. (BitRate: 0) Total bus length: max 5m. (BitRate: 0)
Remark: If AP4xxx is only connected and total cable length >300 m, then BitRate of AP48xx must be set to 1.(AEmon: View – Hardware – AEbusConfiguration - BitRate).
If single AEpacks are connected then BitRate must be 0. (Default setting is 0.)
AEBUS CONNECTIONS
AEbus connections must always be to the identical point of the other AEpack or AX2002. The
AP4xxx has a single AEbus connector, so two cables must be mounted on one connector. (For detailed connections see next page.)
© Nedap N.V.
AP4801 Page 2 of 4
AP4801 / AP4001
1 AP4xxx to AP4xxx
AEbus connectors
rear view
2 AP4xxx to AEpacks
AEbus connectors
rear view
3 AP4xxx to AX2002
AEbus connectors
rear view
AP4xxx n AP4xxx
+1
AP4xxx n AEpack n+1 AP4xxx n AX2002
Remark: If Power is locally supplied on the next AP4xxx connect only CH, CL and CGND.
Going outside AEpacks housing: shielded cable must be used; CH and CL must be one twisted pair.
From other pair one conductor is used for CGND. Shield must be connected to metal housing, (to which also the metal mounting rail of the AEpacks is connected). (CH Æ CH and CL Æ CL)
Attention: The communication line must be terminated correctly, see chapter Termination Switch.
TERMINATION SWITCH
The AEbus must be terminated correctly at the first and the last
AEpack. For this purpose the switch beside the AEbus connector is used. See text at switch for correct ON and OFF position. See figure below, also for combination with AX2002.
Resistor ON for
first and last Cable shield to earth on both sides
AP4xxx first
Resistor OFF for all between
AP4xxx between
ON OFF OFF
AEbus connector top view
AX2002
OFF
AEbus termination switch
ON
Resistor ON for
first and last
AX2002 last
OFF ON
AEbus (extender) connectors
rear view
ADDRESS SETTING
AP48xx: address must be 99 (AP48xx only).
The Address switch gives address of AEpack. Left: units of 10, right: units of 1.
BUS ERR and ADDR ERR LED’s indicates address status. Address valid: both LED’s must be off.
New installation: select free address; Replacing AEpack: use the same address.
The address is used for configuring the AEpack (software settings) so write it down.
Address 00 is used to set the AEpack off-line (isolation of AEpack).
© Nedap N.V.
AP4801 Page 3 of 4
AP4801 / AP4001
BATTERY (AP48xx only)
Battery must be enabled by removing plastic isolator that is put between its contacts. (Battery is used for real time clock on AP48xx)
TAMPER SWITCH
Tamper switch can be read by the software and thus generating an alarm if enclosure is opened.
AEPACK LOCAL TEST (ALT MODE)
ALT mode allows a simple test of the basic functions of AEpack. Switching on/off ALT mode is logged on server!
Start ALT mode: Press ALT button more than 3 seconds. Status LED blinks fast.
Back to normal operation: No action in ALT mode during 15 minutes or ALT switch pressing again for 3 seconds. After returning to operation mode the situation from before starting the ALT mode is restored.
ALT mode for AP4x07: Short activating button will cause a new test situation, tests will loop around:
1 Reads card: ID led blinks, UL led acts like ID led, activates relay 1
2 Relay 1 ON NA and UL led ON, UL led flashes during reading card
3 Relay 1 OFF
Steps 1,2,3 are repeated for all four outputs.
FIRMWARE
Pay attention that the firmware loaded in AEpack and AEpu determines functionality and protocols.
SPECIFICATIONS AP4801 (Product nr. 9842640) AP4001 (Product nr. 9842500)
Dimensions: 230 x 345 x 70 mm Weight: ± 900 gr
Power input: 10 – 35VDC 10 – 25VAC AP4801: Min. AEpack power consumption: 300mA@24VDC / 600mA@12VDC
Environment: Temperature: Operating: 0 – 55 °C, Storage: -30 – 65 °C Relative humidity: 10 – 93% non condensing
Inputs: 8: Intended for dry contact or open collector, optional supervised (software selectable)
Outputs: 4: Dry contact (normally open, common, normally closed).
(Suitable switching inductive loads, clean relay contacts)
Continuous current and switching current: 6A (AC and DC)
Indications: 4* UL and NA led for antenna: max 20 mA
AP48xx: UTP 100/10 Mbps (auto detection)
Service port RS232 (Rx, Tx, GND, RTS, CTS)
Battery: CR2032 (lifetime 2 years if no power present)
Antennas: Only antenna’s with adjustment included can be used, otherwise add adjustment box
UL and NA led for antenna: max 20 mA, (5VDC; R=220E)
Detection distance: RefleXS260 and UniXS card: max 30 cm, RefleXS260 and XM card: 40 cm
CABLE SPECIFICATIONS
Inputs: 2 x 0,25mm², max cable length: 100 meter, cable capacity <= 100pF/meter
Antenna: 5 x 0,25mm² shielded, max cable length: 50 meter, cable capacity <= 100pF/meter
Communication AEbus: only AP4xxx (including power): 3 x 2 x 0,5mm² shielded, max cable length: 1000 meter only AP4xxx (CL,CH,CGND): 2 x 2 x 0,5mm² shielded, max cable length: 1000 meter
AP4xxx + AEpacks: 5 x 0,5mm² shielded, max cable length 5 meter
AP4xxx + AEpacks + AX2002: 2 x 2 x 0,5mm² shielded, max cable length 300 meter
Cable shield to metal case
MORE INFORMATION: For more detailed information contact your local Nedap supplier or check the internet site.
© Nedap N.V.
AP4801 Page 4 of 4