Legrand MM6 Cable Management Racks, 10.5 channel depth, 8', OR-MM6810 Instruction Sheet
Legrand MM6 Cable Management Racks, 10.5 channel depth, 8', OR-MM6810, can be used for both 19” and 23” panels, features EIA rack unit numerals every 5 units, and can be assembled with rack unit #1 at the bottom or at the top. It has bend limiters in slots on the front waterfall and rear ladder rail, and a separator plate on the inside of the top waterfall. Multiple rack configurations are possible, and the rack(s) can be secured to the floor using the provided 7/8 diameter holes in the base of the rack.
ಪಿಡಿಎಫ್
ದಾಖಲೆ
ಜಾಹಿರಾತು
ಜಾಹಿರಾತು
©,
Sa
7
TITLE
| MIGHTY MO 6
ORTRONICS 2:27 | CABLE MANAGEMENT RACK
FAX: 860—405—2990
MIGHTY MO 6 CABLE MANAGEMENT SYSTEM
ASSEMBLY INSTRUCTIONS
NOTE: Instruction for both 19” and 23” panels. Rack for
19” panel is shown; rack for 23” panel uses the
inside mounting holes as shown on sheet 3.
STEPS:
1.
716014051
Before assembling MIGHTY MO rack, please inventory
material contents per sheet 2 and schematic inside
hardware kit cover.
The MIGHTY MO uprights have EIA rack unit numerals every
5 units and can be assembled with rack unit #1 at the
bottom or at the top. Insure both uprights start the same.
Attach the two upright side rails to the base angles using
3/8 x 17 hex head bolts, lock washers, and speed nuts.
(MAX ASSY TORQUE: 12.5 FT—LB)
Attach top front waterfall and rear ladder rail to top of
upright rails using 3/8 x 1” hex head bolts, lock washers
and speed nuts. (MAX ASSY TORQUE: 12.5 FT—LB.)
Install bend limiters in slots on front waterfall and rear
ladder rail. Hole in bracket installs on rear rail. Secure
bracket using two #10 X 1/2” hex washer—head screws.
The screws should be installed from outside of rear rail.
Install separator plate on inside of top waterfall using two
#10 X 1/2” hex washer—head screws. The screws should
be installed from the outside of the waterfall.
Install Hook—Loop wire management straps in vertical slots
on inside uprights as required.
See sheet 4 for multiple rack configuration(s) and layout
of floor mounting.
To secure rack(s) to floor, use 7/8 diameter holes
provided in base of rack. The installation vendor should
provide mounting hardware to secure rack to floor following
local and state codes.
Part of the Ortronics
Layer Zero” Solution
ZERO” em ©
INSTRUCTION SHEET $
OR-71601405
REV. | ECN # SHEET DWN.BY: DATE CHK.BY: DATE APP.BY: DATE
03 |04009 | 1 of 4 | LEVESQUE | 11/10/09 | CAC 11/30/09 |W. DIETZ | 12/01/09
©2)
& ORTRONICS
125 EUGENE O'NEILL DRIVE
NEW LONDON, CT 06320
TEL: 860—445—3800
FAX: 860—405—2990
TITLE
MIGHTY MO 6
CABLE MANAGEMENT RACK
<
RACK FOR 19” PANEL (AS SHOWN) TYPICAL
ASSEMBLED VIEW
LADDER RAIL, REAR TOP (QTY.1)
BEND LIMITER AND
BRACKET (QTY.2)
NOTE:
TO ASSEMBLE RACK FOR 23" PANELS USE THE
INSIDE MOUNTING HOLES ON THE UPRIGHTS.
| UPRIGHTS (QTY.2)
BASE ANGLE, (QTY.2)
SEPARATOR PLATE (QTY.1)
1 WATERFALL, FRONT TOP (QTY.1)
716014052
INSTRUCTION SHEET # | REV. | ECN # | SHEET DWN.BY: DATE CHK-BY: DATE APP.BY: DATE
OR-71601405 | 03 |04009 | 2 of 4 | LEVESQUE | 11/10/09 | CAC 11/30/09 |W. DIETZ | 12/01/09
Mad e 125 EUGENE O'NEILL DRIVE
E ORTRONICS 2"
Z De TEL: 860—445—3800
QD FAX: 860-405-2990
TITLE
MIGHTY MO 6
CABLE MANAGEMENT RACK
RACK FOR: 19” PANEL
BEND LIMITER
QTY 2
SCREW #10 x 1/2”
HEX WASHER HEAD
QTY 4
LADDER RAIL,
REAR TOP
NOTCH MARKS AT 5
EVERY RACK UNIT
duo
“VA
UPRIGHTS ARE NUMBERED EVERY
5 RACK UNITS, ASSEMBLY CAN
BE EITHER WITH NUMBER 11°
STARTING AT THE BOTTOM OR
THE TOP OF THE RACK.
(VIEW ENLARGED FOR CLARITY) X
ASSEMBLY HARDWARE: '
16—3/8 x 1” HEX HEAD BOLTS
16—3/8 SPRING LOCKWASHERS
8—MIGHTY MO SPEED NUTS
(MAX ASSY TORQUE: 12.5 FT—LB)
т № 3 \
Og ( , + |
NOTE:
RACK FOR 23” PANEL (NOT SHOWN)
IS ASSEMBLED BY USING INSIDE
MOUNTING HOLES ON THE UPRIGHTS
INSIDE MOUNTING HOLES USED FOR 23” VERSION
7160014053
D
©, vr
op =
м” Фа
‘es
©, vr
op =
> ©
©
©, A
©
м” Фо
©
©, A
*s
> 0e
‘о \
©, A
% a
0,
” ve"
©, A
©.
l и Oy
e
, \
м” Фи
D
(SHOWN) ASSSEMBLY FIGURES.
SEPARATOR
WATERFALL, TOP FRONT
UPRIGHT
QTY. 2
ALSO INCLUDED WITH KIT:
12-24 x 5/8" PATCH PANEL
BINDER HEAD SCREWS.
18" HOOK—LOOP STRAPS.
18" HOOK—LOOP STRAP
FEED 18" STRAPS |
THROUGH SLOTS INSIDE
RAILS FOR VERTICAL WIRE
MANAGEMENT OF CABLES.
INSTRUCTION SHEET NUMBER
OR— /1601405
REV
03
ECN
04009
SHEET
3 Or 4
DWN.BY:
LEVESQUE
DATE
11/10/09
CHK.BY:
CAC
DATE
11/30/09
APP.BY:
W. DIETZ
DATE
12/01/09
ZU Dv €
& ORTRONICS
TITLE
125 EUGENE O'NEILL DRIVE MIGHTY MO 6
NEW LONDON, CT 06320
TEL: 860—445—-3800
FAX: 860—405—2990
CABLE MANAGEMENT RACK
FLOOR MOUNTING OPTIONS
O O
© o o o o о о оо 0)
16.00 L— L—
rr °
| O O
20.50 | Ё о о оо о о оо à
18.00 |! #
10.50
UPRIGHT F
DEPTH
Ç _ 16.25” RACK BASE
' == 2 2 == — = + CAN BE TURNED
INWARDS (AS SHOWN)
© О О © TO FIT ONTO A
24” FLOOR TILE
675 / - 160 - 16.00
MOUNTING 23.75
HOLES 23.75 a
SINGLE RACK LAYOUT
MULTIPLE RACK SPACER, USE UNMARKED END FOR STARTS \ USES RACK ASSEMBLY HARDWARE, LOCATE AT BOTTOM AND
3 PROVIDED. - - TOP OF RACK BEFORE SECURING RACK TO THE FLOOR
«— 12.25 — | 8.25 | — 6.50 — 2.50 — ~~
O O O O O O O O O O
Ю о о оо о о о 0 0 Ю о о 060 о о ое © Ю о о оо о о о 0 0 fo о ооо о о оо 0) Ю о о оо о о оо ©
— —_ — —_ — —_ — —_ j— DL
a {+ {+ {+ {+ {+ {+ + + {+ {+ =
о O
20.00 - 16.00 —- 16.00 REF. == 14.255 =
RACK LAYOUT FOR RACK LAYOUT FOR RACK LAYOUT FOR RACK LAYOUT FOR
16” "Y” SHAPE CAGE 12” "Y" SHAPE CAGE 10” ”Y” SHAPE CAGE 6” CAGE
716014054
INSTRUCTION SHEET NUMBER | REV ECN SHEET DWN.BY: DATE CHK.BY: DATE APP.BY: DATE
OR-71601405 | 03 |04009! 4 OF 4 | LEVESQUE |11/10/09|CAC 11/30/09 |W. DIETZ [12/01/09
">
/
ಡೌನ್ಲೋಡ್ ಮಾಡಿ
ಕೇವಲ ಸೌಹಾರ್ದ ಜ್ಞಾಪನೆ. ನೀವು ಡಾಕ್ಯುಮೆಂಟ್ ಅನ್ನು ಇಲ್ಲಿಯೇ ವೀಕ್ಷಿಸಬಹುದು. ಆದರೆ ಮುಖ್ಯವಾಗಿ, ನಮ್ಮ AI ಈಗಾಗಲೇ ಅದನ್ನು ಓದಿದೆ. ಇದು ಸಂಕೀರ್ಣ ವಿಷಯಗಳನ್ನು ಸರಳ ಪದಗಳಲ್ಲಿ ವಿವರಿಸಬಹುದು, ನಿಮ್ಮ ಪ್ರಶ್ನೆಗಳಿಗೆ ಯಾವುದೇ ಭಾಷೆಯಲ್ಲಿ ಉತ್ತರಿಸಬಹುದು ಮತ್ತು ದೀರ್ಘವಾದ ಅಥವಾ ಹೆಚ್ಚು ಸಂಕೀರ್ಣವಾದ ಡಾಕ್ಯುಮೆಂಟ್ಗಳನ್ನು ಸಹ ತ್ವರಿತವಾಗಿ ನ್ಯಾವಿಗೇಟ್ ಮಾಡಲು ನಿಮಗೆ ಸಹಾಯ ಮಾಡುತ್ತದೆ.