39214-048/2009/Rev 6
Note
1. All circuits are power limited except for relay contacts. If the relay contacts are connected to a non power limited source, remove the lower portion of the power limited label along the kiss cut. Use only limited energy cable types FPL, FPLR or FPLP on power limited circuits.
Specifi cations
Part no
Compatibility Identifi er 55000-820
Type
Style
Dimensions
Temperature range
Humidity
Wiring size
10 to 93% RH Non-condensing
24AWG - 14AWG
Signal Line Circuit (SLC) Supervised power limited
Working voltage
Operating current
Functional States Analog Level (Normal)
Analog Level (Alarm)
Analog Level (Trouble)
Initiating Device Circuit (IDC)
Wiring styles
End-of-Line Resistors
Switch Monitor Input/Output Module
Fascia plate with wiring terminals
4½” x 4½” x 1”
32ºF to 120ºF (0ºC to 49ºC)
17-28VDC
Modulation Voltage
Supervisory Current
Surge
5-9V (peak to peak)
2.5mA
Current 7.5mA
Maximum alarm Current 6.0mA (LED on)
16
64
4 can be ordered under part number 44251-146).
Open collector input Not
Relay output
Supervised power limited Class A and Class B
Voltage
Current
Line
VDC max
100Ω max
47KΩ (A UL listed end-of-line resistor is available from Apollo and supervised
Logic 1 is > 4 VDC
Logic 0 is < 1 VDC
Non supervised, programmable, dry contact
24 VDC, 1A:30 VAC, 0.5A (resistive)
Functional Test Data
Output Bit
2
1
Function
Alarm LED
1 = On
0 = Off
Not Used
0 Relay Control
1 = On
0 = Off
Input Bit
2
1
0
Function
Alarm LED Confi rmation
1 = On
0 = Off
Indicates Class Wiring
1 = Class B*
0 = Class A
Opto-isolated Input Status
1 = Input low
0 = Input high
* Note: Toggles to ‘0’ in alarm.
©Apollo Fire Detectors Ltd 1994–2009
Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, UK
Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754
Email: techsales@apollo-fi re.co.uk Website: www.apollo-fi re.co.uk
In the USA: Apollo America, 821 Ulrich Ave, Louisville, KY 40219 USA
Tel: (502) 964-6565 Fax: (502) 964-6229
Email: infoUSA@apollo-fi re.com Website: www.apollo-fi re.com
4
XP95A Switch Monitor Input/Output Module
Installation Instructions
General
The XP95A Switch Monitor Input/Output Module, part no 55000-820, is a loop-powered device which incorporates a monitored input circuit for connection to remote switches. It also has an unmonitored opto-coupled input and volt-free relay output. It is mounted on a plastic fascia plate for use with a 4" square or 2 gang electrical backbox (minimum depth 2⅛”).
A red LED flashes in synchronization with the current pulse reply from the device. If output bit 2 is set, the LED is illuminated continuously.
Note: the XP95A Switch Monitor Input/Output Module is designed for indoor use only.
Control Panel Compatibility
The module has been listed by Underwriters Laboratories Inc. For details of compatible control panels contact Apollo Fire Detectors Limited. Please check fi re control panel literature for compatible Apollo devices.
Installation
These products must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report an alarm condition. Apollo Fire Detectors Limited is not responsible for devices which are improperly installed, maintained and tested.
Before installing these products, check the continuity, polarity and insulation resistance of all wiring. Check that siting is in accordance with the fi re system drawings and conforms to all applicable local codes such as NFPA 72.
1. Mount the electrical box as required and install all cables for termination. Where applicable ensure that cable shield/earth continuity is maintained.
2. Drill holes in the fascia plate corresponding to the holes on the mounting box selected (Fig 1).
3. Terminate all cables in compliance with local codes and regulations.
4. Set the address of the module as shown on page 3.
5. Gently push the completed assembly towards the mounting box and align the fi xing holes.
Secure the unit with the screws provided. Do not overtighten the screws.
6. Commission the module.
1
Relay Functionality
The relay is operated by setting output bit 0. If the supply voltage is removed, the relay will not change state. When the Switch Monitor Input/Output Module is powered up, the relay will be in the same state as it was prior to the module being switched off but the module will respond to output bit 0 four seconds after power has been applied. If the module has not been interrogated, a relay reset will automatically be applied.
0
WIRING CLASS
ON
1 2 3 4 5 6 7 8
A
1 2 4 8 16 32 64
1 B
ADDRESS
© Apollo Fire Detectors Limited 2004/JDR
Fig 3. DIL Switch
Address Setting
Segments 1-7 of the DIL Swtich are used to select the address of the module. Each of the seven segments must be set to ‘0’ (ON) or ‘1’ (OFF) using a small screwdriver or similar tool. A complete list of address settings is shown below (The eighth segment of the switch is used to select
Class A or B wiring).
DIL switch DIL switch DIL switch DIL switch DIL switch addr setting addr setting addr setting addr setting addr setting
1234567 1234567 1234567 1234567 1234567
© Apollo Fire Detectors Limited 2004/JDR/JLC
Fig 1. Mounting the XP95A Switch Monitor Input/Output Module
30VDC max
Logic 1 is > 4VDC
Logic 0 is < 1VDC
NON-POLARIZED
OPTO-ISOLATED
INPUT
OPTO
INPUT
L2
+
L1
–
All circuits are power limited. Use only limited energy cable types FPL, FPLR or FPLP on power limited circuits.
Any number of UL contact devices may be used.
Do not mix fire alarm, supervisory or security devices on the same monitor module.
N/C
COM
N/O
A/B +
A +
A –
A/B –
1 Amp 30VDC
Class B wiring method
47K,
½W,
5% EOL
Initiating devices
Class A wiring method
60 0011110 70 0110001 80 0000101 90 0101101 100 0010011
© Apollo Fire Detectors Limited 2007-8/TP
Incoming communications loop
Outgoing communications loop
Fig 2. Wiring Diagram for XP95A Swtich Monitor Input/Output Module
2
107 1101011 117 1010111
108 0011011 118 0110111
109 1011011 119 1110111
110 0111011 120 0001111
3