XP95A Switch Monitor Input/Output Module

Add to My manuals
2 Pages

advertisement

Apollo XP95A Switch Monitor Input/Output Module Installation Instructions | Manualzz

39214-048/2009/Rev 6

Note

1. All circuits are power limited except for relay contacts. If the relay contacts are connected to a non power limited source, remove the lower portion of the power limited label along the kiss cut. Use only limited energy cable types FPL, FPLR or FPLP on power limited circuits.

Specifi cations

Part no

Compatibility Identifi er 55000-820

Type

Style

Dimensions

Temperature range

Humidity

Wiring size

10 to 93% RH Non-condensing

24AWG - 14AWG

Signal Line Circuit (SLC) Supervised power limited

Working voltage

Operating current

Functional States Analog Level (Normal)

Analog Level (Alarm)

Analog Level (Trouble)

Initiating Device Circuit (IDC)

Wiring styles

End-of-Line Resistors

Switch Monitor Input/Output Module

Fascia plate with wiring terminals

4½” x 4½” x 1”

32ºF to 120ºF (0ºC to 49ºC)

17-28VDC

Modulation Voltage

Supervisory Current

Surge

5-9V (peak to peak)

2.5mA

Current 7.5mA

Maximum alarm Current 6.0mA (LED on)

16

64

4 can be ordered under part number 44251-146).

Open collector input Not

Relay output

Supervised power limited Class A and Class B

Voltage

Current

Line

VDC max

100Ω max

47KΩ (A UL listed end-of-line resistor is available from Apollo and supervised

Logic 1 is > 4 VDC

Logic 0 is < 1 VDC

Non supervised, programmable, dry contact

24 VDC, 1A:30 VAC, 0.5A (resistive)

Functional Test Data

Output Bit

2

1

Function

Alarm LED

1 = On

0 = Off

Not Used

0 Relay Control

1 = On

0 = Off

Input Bit

2

1

0

Function

Alarm LED Confi rmation

1 = On

0 = Off

Indicates Class Wiring

1 = Class B*

0 = Class A

Opto-isolated Input Status

1 = Input low

0 = Input high

* Note: Toggles to ‘0’ in alarm.

©Apollo Fire Detectors Ltd 1994–2009

Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hants, PO9 1JR, UK

Tel +44 (0)23 9249 2412 Fax +44 (0)23 9249 2754

Email: techsales@apollo-fi re.co.uk Website: www.apollo-fi re.co.uk

In the USA: Apollo America, 821 Ulrich Ave, Louisville, KY 40219 USA

Tel: (502) 964-6565 Fax: (502) 964-6229

Email: infoUSA@apollo-fi re.com Website: www.apollo-fi re.com

4

XP95A Switch Monitor Input/Output Module

Installation Instructions

General

The XP95A Switch Monitor Input/Output Module, part no 55000-820, is a loop-powered device which incorporates a monitored input circuit for connection to remote switches. It also has an unmonitored opto-coupled input and volt-free relay output. It is mounted on a plastic fascia plate for use with a 4" square or 2 gang electrical backbox (minimum depth 2⅛”).

A red LED flashes in synchronization with the current pulse reply from the device. If output bit 2 is set, the LED is illuminated continuously.

Note: the XP95A Switch Monitor Input/Output Module is designed for indoor use only.

Control Panel Compatibility

The module has been listed by Underwriters Laboratories Inc. For details of compatible control panels contact Apollo Fire Detectors Limited. Please check fi re control panel literature for compatible Apollo devices.

Installation

These products must be installed in accordance with the applicable NFPA standards, local codes and jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report an alarm condition. Apollo Fire Detectors Limited is not responsible for devices which are improperly installed, maintained and tested.

Before installing these products, check the continuity, polarity and insulation resistance of all wiring. Check that siting is in accordance with the fi re system drawings and conforms to all applicable local codes such as NFPA 72.

1. Mount the electrical box as required and install all cables for termination. Where applicable ensure that cable shield/earth continuity is maintained.

2. Drill holes in the fascia plate corresponding to the holes on the mounting box selected (Fig 1).

3. Terminate all cables in compliance with local codes and regulations.

4. Set the address of the module as shown on page 3.

5. Gently push the completed assembly towards the mounting box and align the fi xing holes.

Secure the unit with the screws provided. Do not overtighten the screws.

6. Commission the module.

1

Relay Functionality

The relay is operated by setting output bit 0. If the supply voltage is removed, the relay will not change state. When the Switch Monitor Input/Output Module is powered up, the relay will be in the same state as it was prior to the module being switched off but the module will respond to output bit 0 four seconds after power has been applied. If the module has not been interrogated, a relay reset will automatically be applied.

0

WIRING CLASS

ON

1 2 3 4 5 6 7 8

A

1 2 4 8 16 32 64

1 B

ADDRESS

© Apollo Fire Detectors Limited 2004/JDR

Fig 3. DIL Switch

Address Setting

Segments 1-7 of the DIL Swtich are used to select the address of the module. Each of the seven segments must be set to ‘0’ (ON) or ‘1’ (OFF) using a small screwdriver or similar tool. A complete list of address settings is shown below (The eighth segment of the switch is used to select

Class A or B wiring).

DIL switch DIL switch DIL switch DIL switch DIL switch addr setting addr setting addr setting addr setting addr setting

1234567 1234567 1234567 1234567 1234567

© Apollo Fire Detectors Limited 2004/JDR/JLC

Fig 1. Mounting the XP95A Switch Monitor Input/Output Module

30VDC max

Logic 1 is > 4VDC

Logic 0 is < 1VDC

NON-POLARIZED

OPTO-ISOLATED

INPUT

OPTO

INPUT

L2

+

L1

All circuits are power limited. Use only limited energy cable types FPL, FPLR or FPLP on power limited circuits.

Any number of UL contact devices may be used.

Do not mix fire alarm, supervisory or security devices on the same monitor module.

N/C

COM

N/O

A/B +

A +

A –

A/B –

1 Amp 30VDC

Class B wiring method

47K,

½W,

5% EOL

Initiating devices

Class A wiring method

60 0011110 70 0110001 80 0000101 90 0101101 100 0010011

© Apollo Fire Detectors Limited 2007-8/TP

Incoming communications loop

Outgoing communications loop

Fig 2. Wiring Diagram for XP95A Swtich Monitor Input/Output Module

2

107 1101011 117 1010111

108 0011011 118 0110111

109 1011011 119 1110111

110 0111011 120 0001111

3

advertisement

Key Features

  • Monitored input circuit
  • Unmonitored opto-coupled input
  • Volt-free relay output
  • Loop-powered
  • Indoor use only
  • LED indication

Related manuals

Frequently Answers and Questions

What is the XP95A Switch Monitor Input/Output Module?
The XP95A Switch Monitor Input/Output Module is a loop-powered device that incorporates a monitored input circuit for connection to remote switches. It also has an unmonitored opto-coupled input and volt-free relay output.
How is the XP95A Switch Monitor Input/Output Module mounted?
The XP95A Switch Monitor Input/Output Module is mounted on a plastic fascia plate for use with a 4" square or 2 gang electrical backbox (minimum depth 2⅛”).
What is the purpose of the red LED on the XP95A Switch Monitor Input/Output Module?
The red LED flashes in synchronization with the current pulse reply from the device. If output bit 2 is set, the LED is illuminated continuously.
Where can I find information about compatible control panels for the XP95A Switch Monitor Input/Output Module?
For details of compatible control panels contact Apollo Fire Detectors Limited. Please check fire control panel literature for compatible Apollo devices.
Download PDF