Novus N1200 Instruction manual


Add to my manuals
13 Pages

advertisement

Novus N1200 Instruction manual | Manualzz

Controller N1200

UNIVERSAL CONTROLLER - INSTRUCTIONS MANUAL – V2.0x C

SAFETY ALERTS

The symbols below are used on the equipment and throughout this document to draw the user’s attention to important operational and safety information.

CAUTION:

Read the manual thoroughly before installing and operating the equipment.

CAUTION OR DANGER:

Electrical Shock Hazard

All safety related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner

not specified by the manufacturer, the protection provided by the equipment may be impaired.

INTRODUCTION

The N1200 is an extraordinarily versatile process controller. It holds in one single instrument all the main features needed for the vast majority of industrial processes. It accepts in a single model virtually all the sensors and signals used in the industry and provides the main output types required for the operation of diverse processes.

The configuration can be performed directly on the controller or through the USB interface. The NConfig software (free) is the configuration management tool. Connected to the USB of a Windows computer, the controller is recognized as a serial communications port (COM) running with a Modbus RTU protocol.

Through the USB interface, even if disconnected from the power supply, the configuration performed in a piece of equipment can be can be saved in a file and repeated in other pieces of equipment that require the same configuration.

It is important that the users read carefully this manual before using the controller. Verify if the release of this manual matches the instrument version (the firmware version is shown when the controller is energized). The N1200 main characteristics are:

Multi-sensor universal input;

Protection for open sensor in any condition;

Relay, 4-20 mA and logic pulse control outputs all available in the standard model;

Self-tuning of PID parameters;

Automatic / Manual function with “bumpless” transfer;

Four modes of independents alarms, with functions of minimum,

maximum, differential (deviation), open sensor and event;

Timer functions that can be associated to the alarms;

Retransmission of PV or SP in 0-20 mA or 4-20 mA;

Input for remote setpoint;

Digital input with 5 functions;

Programmable soft-start;

20 setpoint profile programs with 9 segments each, with the ability to be linked together for a total of 180 segments;

Password for parameters protection;

Universal power supply.

NOVUS AUTOMATION

CONFIGURATION / FEATURES

INPUT TYPE SELECTION

Select the input type (in parameter “tYPE”) from Table 1 below.

B

E

Pt100

0-20 mA

4-20 mA

0–50 mV

0-5 Vdc

0-10 Vdc

K

T

N

R

S

TYPE CODE

J

Tc j

RANGE OF MEASUREMENT

Range: -110 to 950 ºC (-166 to 1742 ºF)

Tc k

Range: -150 to 1370 ºC (-238 to 2498 ºF)

Tc t

Range: -160 to 400 ºC (-256 to 752 ºF)

Tc n

Tc r

Tc s

Range: -270 to 1300 ºC (-454 to 2372 ºF)

Range: -50 to 1760 ºC (-58 to 3200 ºF)

Range: -50 to 1760 ºC (-58 to 3200 ºF)

Tc b

Range: 400 to 1800 ºC (752 to 3272 ºF)

Tc e

Range: -90 to 730 ºC (-130 to 1346 ºF)

Pt

Range: -200 to 850 ºC (-328 to 1562 ºF)

L0.20

L4.20

L0.50

L0.5

L0.10

Linear Signals

Programmable indication from -1999 to 9999. ln j

4-20 mA

NON

LINEAR

Ln k ln t ln n ln r

Non Linear Analog Signals

Indication range depends on the selected sensor ln s ln b ln E

Ln.Pt

Table 1 - Input types

Note: All input types are factory calibrated.

CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS

The controller input and output channels (I / O) can assume multiple functions: control output, digital input, digital output, alarm output, retransmission of PV and SP. These channels are identified as I / O

1, I / O 2, I / O 3, I / O 4 and I / O 5.

The basic controller model comes loaded with the following features:

I / O 1- output to Relay SPST-NA;

I / O 2- output to Relay SPST-NA;

I / O 5- current output, digital output, digital input;

Optionally, other features can be added, as shown under the item

“Identification” in this manual:

- 3R: I / O3 with output to SPDT relay;

- DIO: I / O3 and I / O4 as digital input and output channels;

- HBD: Heater break detect;

- 485: Serial Communication;

The function to be used in each channel of I/O is defined by the user in accordance with the options shown in the Table 2.

1 / 13

FUNCTION OF I/O

Without Function

Output of Alarm 1

Output of Alarm 2

Output of Alarm 3

Output of Alarm 4

LBD - Loop break detection

Control Output (Relay or Digital Pulse)

Automatic / Manual mode selection

Run / Stop mode selection

Remote SP selection

Setpoint profile program HOLD (Freezes program execution)

Setpoint Profile Program 1 selection

0 to 20 mA control output selection

4 to 20 mA control output selection

Retransmission of PV in 0 to 20 mA

Retransmission of PV in 4 to 20 mA

Retransmission of Sp in 0 to 20 mA

Retransmission of SP in 4 to 20 mA

CODE

OFF

A1

A2

A3

A4

Lbd

CTRL mAN

RVN

RSP

KPRG

PR 1

TYPE OF I/O

Output

Output

Output

Output

Output

Output

Output

Digital Input

Digital Input

Digital Input

Digital Input

Digital Input

(.0.20

Analogical Output

(.4.20

Analogical Output

P.0.20

Analogical Output

P.4.20

Analogical Output

S.0.20

Analogical Output

S.4.20

Analogical Output

Table 2 - Types of functions for the I/O channels

During the configuration of the I/O channels, only the valid options for each channel will be shown on the display. These functions are described below:

off

- Without function

The I/O channel programmed with code off will not be used by the controller. Although without function, this channel is available through the serial communication as digital I/O (command 5 MODBUS).

a1

, a2, a3, a4 – Alarm Outputs

The selected channel can be used as output to Alarms 1 to 4.

Defines that the programmed I/O channel acts as alarm outputs.

Available for all the I/O channels.

Lbd

–Loop Break Detector function.

Assigns the output of the Loop Break Detector alarm to an I/O channel. Available to all I/O channels.

(trL

– PWM Control Output

Defines the I/O channel to be used as the PWM control output (relay or digital pulse). Available for all the I/O channels. The digital pulse is available on I/O5 (standard) or on I/O3 and I/O4 (when the DIO optional is installed). Check the specifications of each channel.

 mAn - Digital Input with Auto/Manual function

Defines the I/O channel as Digital Input with the function of switching the control mode between Automatic and Manual. Available on I/O5

(standard) or on I/O3 and I/O4 (when the DIO optional is installed).

Closed = Manual control;

Open = Automatic control

rvn

- Digital Input with RUN function

Defines channel as Digital Input with the function of enabling/disabling the control and alarm outputs (“RvN”: YES / no).

Available for I/O5 or I/O3 and I/O4, when installed.

Closed = outputs enabled

Open = control and alarms output shut off

rsp

- Digital Input with Remote SP function

Defines channel as Digital Input with the function of selecting the remote SP as the control setpoint. Available for I/O5 or I/O3 and

I/O4, when available.

Closed = remote SP

Open = uses main SP

kprg

- Digital Input with Hold Program function

Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program. Available for I/O5 or I/O3 and I/O4, when available.

Closed = Enables execution of the program

Open = Interrupts (freezes) execution of the program

NOVUS AUTOMATION

Controller N1200

Note: Even when the execution of the program is interrupted, the control output remains active and controlling the process at the point

(Setpoint) of interruption. The program will resume its normal execution starting from this same point when the digital input is closed.

Pr 1

- Digital Input with function to Execute Program 1

Defines the IO channel as Digital Input with the function of commanding the execution of the setpoing profile program 1.

Available for I/O5 or I/O3 and I/O4, when available.

Useful function for switching between the main setpoint and a secondary one defined by the program 1.

Closed = selects program 1;

Open = selects main setpoint

(.0.20

–0-20 mA Control Output

Available for I/O 5 only, defines the channel as a 0-20 mA control output.

(.4.20 -

4-20 mA Control Output

Defines the channel as a 4-20 mA control output.

P.0.20

– 0-20 mA PV retransmission

Available for I/O 5 only, configures the channel to retransmit the values of PV in 0-20 mA.

P.4.20

- 4-20 mA PV retransmission

Available for I/O 5 only, configures the channel to retransmit the values of PV in 4-20 mA.

s.0.20 –

0-20 mA SP (Setpoint) retransmission

Available for I/O 5 only, configures the channel to retransmit the values of SP in 0-20 mA.

 s.4.20 –

4-20 mA SP (Setpoint) retransmission

Available for I/O 5 only, configures the channel to retransmit the values of SP in 0-20 mA.

CONFIGURATION OF ALARMS

The controller has 4 independent alarms. These alarms can be configured to operate with nine different functions, as shown in Table 3.

off

– Alarms turned off.

ierr

– Open Sensor alarms - (Loop Break)

The open sensor alarm acts whenever the input sensor is broken or badly connected.

rs

– Program Event Alarm

Configures the alarm to act in (a) specific segment(s) of the programs of ramps and baselines to be created by the user.

Rfai1 – Burnt-out Resistance Alarm - (Heat Break)

Signals that the heating element has broken up. This alarm function requires the accessory Current transformer CT1. Details for use of the option “burnt-out resistance” are found in the specific documentation that accompanies the product whenever this option is requested.

lo

– Alarm of Absolute Minimum Value

Triggers when the value of measured PV is below the value defined for alarm Setpoint.

ki

– alarm of Absolute Maximum Value

Triggers when the value of measured PV is above the value defined for alarm Setpoint.

dif

– Alarm of Differential Value

In this function the parameters “SPA1”, “SPA2”,” SPA3” and “SPA4” represent the Deviation of PV in relation to the SP.

Using the Alarm 1 as example: for Positive SPA1 values, the

Differential alarm triggers when the value of PV is out of the range defined for:

(SP – SPA1) to (SP + SPA1)

For a negative SPA1 value, the Differential alarm triggers when the value of PV is within the range defined above:

difl

– Alarm of Minimum Differential Value

It triggers when the value of PV is below the defined point by:

(SP – SPA1)

2 / 13

Using the Alarm 1 as example.

difk

– Alarm of Maximum Differential Value

Triggers when the value of PV is above the defined point by:

(SP + SPA1)

Using the Alarm 1 as example.

SCREEN TYPE ACTUATION

Off

Inoperative Output is not used as alarm.

Ierr

Open sensor

(input Error)

Activated when the input signal of PV is interrupted, out of the range limits or Pt100 in short-circuit.

Activated in a specific segment of program.

Rs

Event (ramp and

Soak) rfail

Resist. burnt out

(resistance fail)

Signals a failure in the heating element.

Lo

Minimum value

(Low)

PV

SPAn

Ki

Maximum value

(High)

Dif

Differential

(diFerential)

Difl

Minimum

Differential

(diFerential

Low)

Difk

Maximum differential

(diFerential

High)

PV

SV - SPAn SV

SPAn

SV

PV

PV

SV - SPAn SV SV + SPAn alarme alarme

Positive SPAn

SV + SPAn alarme

SV SV - SPAn alarme

Negative SPAn

Positive SPAn Negative SPAn

PV

PV

SV - SPAn

SV SV + SPAn

Positive SPAn

PV

SV + SPAn SV

PV

Negative SPAn

Table 3 – Alarm Functions

Where SPAn refers to Setpoints of Alarm “SPA1”, “SPA2”,

SPA3” and “SPA4”.

ALARM TIMER MODES

The controller alarms can be configured to perform 3 timer modes:

One pulse with defined duration;

Delayed activation;

Repetitive pulses;

The illustrations in Table 4 show the behavior of the alarm output for various combinations of times t1 and t2. The timer functions can be configured in parameters A1t1, A1t2, A2t1, A2t2, A3t1, A3t2,

A4t1

and A4t2.

OPERATION T 1 T 2 ACTION

Normal

Operation

0 0

Alarm

Output

Alarm Event

Activation for a defined time 1 to 6500 s

0

Alarm

Output

T1

Alarm Event

Activation with delay

0 1 to 6500 s

Alarm

Output

T2

Alarm Event

Intermittent

Activation 1 to 6500 s 1 to 6500 s

Alarm

Output alarme

T1

Alarm Event

T2

T1

Table 4 – Temporization Functions for the Alarms

The LEDs associated to the alarms will light when the alarm condition is recognized, not following the actual state of the output, which may be temporarily OFF because of the temporization.

NOVUS AUTOMATION

Controller N1200

INITIAL BLOCKING OF ALARM

The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is first energized (or after a transition from run YES NO). The alarm will be enabled only after the occurrence of a non-alarm condition followed by a new occurrence for the alarm.

The initial blocking is useful, for instance, when one of the alarms is configured as a minimum value alarm, causing the activation of the alarm soon upon the process start-up, an occurrence that may be undesirable.

The initial blocking is disabled for the sensor break alarm function.

EXTRACTION OF THE SQUARE ROOT

With this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal.

Available only for the inputs belonging to the group of linear analogic signals: 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V.

ANALOG RETRANSMISSION OF PV AND SP

The analog output, when not used for control purposes, is available for retransmitting the PV and SP values in 0-20 or 4-20 mA. This analog output is electrically isolated from other inputs and outputs.

The analog output signal is scalable, with the output range defined by the values programmed in the parameters “rtLL” and “rtkL”.

To obtain a voltage output, the user must install a resistor shunt (550

 max.) to the current output terminals (terminals 7 and 8). The actual resistor value depends on the desired output voltage span.

There is no electrical isolation between serial communication

(RS485) and channel I/O5.

SOFT-START

The soft-start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand. .

This is accomplished by defining a limiting ramp for the control output.

The output is allowed to reach maximum value (100 %) only after the time programmed in the soft-start parameter has elapsed. The Softstart function is generally used in processes that require slow start-up, where the instantaneous application of 100 % of the available power to the load may cause damages to parts of the system.

In order to disable this function, the soft-start parameter must be configured with 0 (zero).

REMOTE SETPOINT

The controller can have its Setpoint value defined by an analog, remotely generated signal. This feature is enabled through the channels I/O3, I/O4 or I/O5 when configured as digital inputs and configured with the function rsp (Remote SP selection) or through the parameter E.rsp. The remote setpoint input accepts the signals

0-20 mA, 4-20 mA, 0-5 V and 0-10 V.

For the signals of 0-20 and 4-20 mA, a shunt resistor of 100

is required between terminals 9 and 10, as shown in Figure 4c.

CONTROL MODE

The controller can operate in two different manners: Automatic mode or Manual mode. In automatic mode the controller defines the amount of power to be applied on the process, based on defined parameters

(SP, PID, etc.).

In the manual mode the user himself defines this amount of power.

The parameter

(trl

” defines the control mode to be adopted.

PID AUTOMATIC MODE

For the Automatic mode, there are two different strategies of control:

PID control and ON/OFF control.

PID control has its action based on a control algorithm that takes into account the deviation of PV with respect to SP, the rate of change of

PV and the steady state error.

On the other hand, the ON/OFF control (obtained when Pb=0) operates with 0 % or 100 % of power, when PV deviates from SP.

3 / 13

The determination of the PID parameters (Pb, Ir and Dt) is described in the item DETERMINATION OF PID PARAMETERS of this manual.

LBD - LOOP BREAK DETECTION ALARM

The parameter defines a time interval, in minutes, within which the

PV is expect to react to a control output signal. If the PV does not react properly within the time interval configured in lbd.t, the controller interprets this as a control loop break and signals this occurrence in the display.

A LBD event may be sent to any I/O channel. Simply configure the

LDB function to the desired I/O channel: the selected output will be activated when a LDB condition is detected. When the lbd.t parameter is programmed with 0 (zero), the LDB function is disabled.

The LDB is useful in system supervision and troubleshooting, allowing early detection of problems in the actuator, power source or load.

HBD - HEATER BREAK DETECTION

Available in the products identified with the suffix HBD. Visit our web site for further information www.novusautomation.com

.

SAFE OUTPUT VALUE WITH SENSOR FAILURE

This function defines an output value (user defined) to be assigned to the control output in the event of a sensor failure.

When the input sensor is identified as broken, the controller forcing

MV to assume the user configured value in the 1E.ov parameter.

When the parameter 1E.ov is configured with 0.0 (zero) value, this function is disabled and the control output is simply turned off upon input sensor error.

USB INTERFACE

The USB interface is used for CONFIGURING or MONITORING the controller. The NConfig software must be used for the configuration.

It makes it possible to create, view, save and open configurations from the equipment or files in your computer. The tool for saving and opening configurations in files makes it possible to transfer configurations between pieces of equipment and to make backup copies. For specific models, the NConfig software also makes it possible to update the firmware (internal software) of the controller through the USB.

For MONITORING purposes you can use any supervisory software

(SCADA) or laboratory software that supports the MODBUS RTU communication on a serial communications port. When connected to the USB of a computer, the controller is recognized as a conventional serial port (COM x). Use the NConfig software or consult the

DEVICE MANAGER in the Windows CONTROL PANEL to identify the COM port that was assigned to the controller. Consult the mapping of the MODBUS memory in the controller’s communications manual and the documentation of your supervisory software to conduct the MONITORING process.

Follow the procedure below to use the USB communication of the equipment:

Download the NConfig software from our website and install it on your computer. The USB drivers necessary for operating the communication will be installed together with the software.

Connect the USB cable between the equipment and the computer. The controller does not have to be connected to a power supply. The USB will provide enough power to operate the communication (other equipment functions cannot operate).

Open the NConfig software, configure the communication and start recognition of the device.

Controller N1200

The USB interface IS NOT SEPARATE from the signal input (PV) or the controller’s/indicator’s digital inputs and outputs. It is intended for temporary use during CONFIGURATION and MONITORING periods. For the safety of people and equipment, it must only be used when the piece of equipment is completely disconnected from the input/output signals. Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it. When

MONITORING for long periods of time and with connected inputs and outputs, we recommend using the RS485 interface, which is available or optional in most of our products.

INSTALLATION / CONNECTIONS

The controller must be fastened on a panel, following the sequence of steps described below:

Prepare a panel cut-out of 45.5 x 45.5 mm;

Remove the mounting clamps from the controller;

Insert the controller into the panel cut-out;

Slide the mounting clamp from the rear to a firm grip at the panel.

RECOMMENDATIONS FOR THE INSTALLATION

All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes from 0.5 to 1.5 mm

2

(16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in)

To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power conductors. If this is impractical, use shielded cables. In general, keep cable lengths to a minimum.

All electronic instruments must be powered by a clean mains supply, proper for instrumentation.

 It is strongly recommended to apply RC'S FILTERS (noise suppressor) to contactor coils, solenoids, etc.

In any application it is essential to consider what can happen when any part of the system fails. The controller features by themselves can not assure total protection.

ELECTRICAL CONNECTIONS

The controller's internal circuits can be removed without undoing the connections on the back panel.

The controller complete set of features is drawn in Figure 1. The features loaded in a particular unit are shown on its label

Figure 1 - Connections of the back panel

NOVUS AUTOMATION 4 / 13

Power Supply Connections

Controller N1200

Digital Input Connections

Figures 5a and 5b show switches driving I/O 3 and I/O 5. The same scheme applies to I/O 4

Observe the power requirement for the unit. of required power supply

Figure 2 – Power supply connections

Input Connections

Thermocouple (T/C) and 0-50 mV

The Figure 3a indicates the wiring for the thermocouple and 0-50mV signals. If the thermocouple wires needs to be extended, use appropriate compensation cables.

RTD (Pt100):

Figure 3b shows the Pt100 wiring, for 3 conductors. For proper cable length compensation, use conductors of same gauge and length).

For 4-wires Pt100, leave one conductor disconnected at the controller. For 2-wire Pt100, short-circuit terminals 11 and 12.

Figure 5a – I/ O3 a Digital Input Figure 5b – I/O5 a Digital Input

Connection of Alarms and Outputs

The I/O channels, when configured as outputs, must have their load limit capacities observed, according to the product specifications.

T/C, 0-50mV

Figure 3a - Connection of T/C,

0-50mV

Pt100

Figure 3b - Connection of three wire Pt100-3

4-20 mA:

The connections for current signals 4-20 mA must be carried-out according to Figure 4a.

Figure 6a – I/ O3 or I/O4 with output pulse for SSR.

Figure 6b – I/O5 with output pulse for SSR.

I/O3, I/O4 and I/O5 can also be configured as digital outputs (I/O3 and

I/O4 provide a 5 Vdc output signal whereas I/O5 a 12 Vdc signal). An example of usage is shown in Figure 6a for the I/O3 and in Figure 6b for the I/O5. I/O5 is electrically isolated from the sensor input

OPERATION

The controller's front panel, with its parts, can be seen in the Figure 7:

4-20mA

Figure 4a - Current connection

4-20 mA

Figure 4b - Connection for 5V

and 10V

5 V and 10 V

Refer to Figure 4b for connecting voltage signals.

Remote Setpoint

Feature available in the controller's terminals 9 and 10. When the

Remote SP input signal is 0-20 mA or 4-20 mA, an external

100

 shunt resistor of must be connected to terminals 9 and 10 as indicated in Figure 4c.

NOVUS AUTOMATION

Figure 4c - Connection for remote SP

Figure 7 - Identification of the parts referring to the front panel

Display of PV/Programming: Displays the current value of PV

(Process Variable). When in configuration mode, it shows the parameters names.

Display of SP/Parameters: Displays the value of SP (Setpoint).

When in configuration mode, it shows the parameters values.

COM indicator: Flashes to indicate communication activity in the

RS485 interface.

TUNE indicator: Stays ON while the controller is in tuning process.

MAN indicator: Signals that the controller is in the manual control mode.

RUN indicator: Indicates that the controller is active, with the control output and alarms enabled.

OUT indicator: For relay or pulse control output; it reflects the actual state of the output. If an analog output is assigned for control, the

OUT indicator lights continuously.

A1, A2, A3 and A4 indicators: signalize the occurrence of alarm situation.

P

P Key (Program key): used to walk through the menu parameters.

Back Key: used to retrocede parameters.

Increment key and values of the parameters.

- Decrement key: allow altering the

When the controller is powered on, its firmware version is presented for 3 seconds, after which the controller starts normal operation. The values of PV and SP are displayed and the outputs are enabled.

5 / 13

In order to operate appropriately, the controller needs a configuration that is the definition of each one of the several parameters presented by the controller. The user must be aware of the importance of each parameter and for each one determine a valid condition or a valid value.

Note: Since many parameters depend on the input type chosen, it is recommended that the parameter TYPE be the first one to be configured.

The parameters are grouped in levels according to their functionality and operation easiness. The 7 levels of parameters are:

1 - Operation

2 - Tuning

3- R&S Programs

4- Alarms

5- Scale

6- I/Os

7- Calibration

LEVEL ACCESS

Free access

Reserved access

Table 5 – Cycles of Parameters

The parameters in the operation level have easy access through the key

P

. The access deeper levels use the combination of keys:

(BACK) and

P

(PROG) pressed simultaneously

Press

P

to advance or to retrocede parameters within a level. At the end of each level, the controller returns to the operation level.

Keep pressing the

P

key to move fast forward in the level.

Alternatively, the controller returns to the operation level after pressing the

key for 3 seconds

All configuration parameters are stored in protected memory. The values are saved when the keys

P

or are pressed after changing a parameter value. The value of SP is saved upon pressing the

P

key or every 25 seconds.

DESCRIPTION OF THE PARAMETERS

OPERATION CYCLE

To access the operation level parameters, press

P

until the desired parameter is displays.

PV Indication

(Red Screen)

SP Indication

(Green Screen)

PV and SP indication – The upper display shows the current value of PV. The lower display shows the control SP value.

(trl

Control

Control Mode:

avto

- Means automatic control mode.

Man – Means manual control mode.

(bumpless transfer between automatic and manual control modes).

PV Indication

(Red Screen)

MV Indication

(Green Screen)

MANIPULATED VARIABLE VALUE (MV): The upper display shows PV value and the lower display shows the percentage of MV applied to the control output. When in manual control, the MV value can be manually changed by the

and

keys. When in auto mode the MV value can only be viewed.

To distinguish the MV display from the SP display, the MV is shown flashing intermittently.

E pr

Enable

Program

Execution of Program - Selects the ramp and soak profile program to be executed.

0 - does not execute program

1 to 20 number of the program to be executed

With enabled outputs (RUN = YES), the program starts right after the program is selected.

Controller N1200 p.seg

Screen for indication only. When a ramp and soak program is active, this parameter shows the number of the segment under execution, from 1 to 9. t.seg

Screen for indication only. When a ramp and soak program is in execution, it shows the remaining time to the end of the current segment, in units of time configured in the Pr.tb parameter. rvn

Enables control outputs and alarms.

YES

- Outputs enables.

NO

- Outputs not enabled.

CYCLE OF TUNING

Atvn

Auto-tune

pb

Proportional

Band

ir

Integral Rate

Defines the control strategy to be taken: off

– Turned off. (no PID tuning)

Fast

– Fast automatic tuning.

Full

–More accurate automatic tuning. self

– Precise + auto - adaptative tuning rslf

–Forces one new precise automatic precise + auto - adaptative tuning.

T9kt

- Forces one new precise automatic + auto

- adaptative tuning when Run = YES or controller is turned on.

PROPORTIONAL BAND - Value of the term P of the control mode PID, in percentage of the maximum span of the input type. Adjust of between 0 and 500.0 %. Select zero for ON/OFF control.

INTEGRAL RATE - Value of the term I of the PID algorithm, in repetitions per minute (Reset).

Adjustable between 0 and 99.99.

Displayed only if proportional band

0. dt

Derivative Time

DERIVATIVE TIME - Value of the term D of the control mode PID, in seconds. Adjustable between

0 and 300.0 seconds.

Displayed only if proportional band

0.

(t

Cycle Time

kyst

Hysteresis

ACt

Action

Lbd.t

Loop break detection time.

bias ovll

Output Low

Limit

Pulse Width Modulation (PWM) period in seconds.

Adjustable between 0.5 and 100.0 seconds.

Displayed only if proportional band

0.

CONTROL HYSTERESIS (in engineering. units):

This parameter is only shown for ON / OFF control

(Pb=0).

Adjustable between 0 and the measurement input type span.

CONTROL ACTION: For Auto Mode only. re

Control with reverse Action. Appropriate for

heating. Turns control output on when PV is below SP. dir

Control with direct Action. Appropriate for

cooling. Turns control output on when PV is above SP.

Time interval for the LBD function. Defines the maximum interval of time for the PV to react to a control command. In minutes

BIAS: Offset for MV (manual reset). Range: -100

% to +100 %.

Allows adding a percentage value between -100 % and +100 %. to the MV control output

The value 0 (zero) disables the function.

Lower limit for the control output - Minimum percentage value assumed by the control output when in automatic mode and in PID.

Typically configured with 0 %. Default value: 0 %

NOVUS AUTOMATION 6 / 13

ovkl

Output High

Limit

sfst

Softstart

Sp.a1

Sp.a2

Sp.a3

Sp.a4

Upper limit for the control output - Maximum percentage for the control output when in automatic mode and in PID. Typically configured with 100 %. Default value: 100 %

SoftStart Function –

:

Time in seconds during which the controller limits the MV value progressively from 0 to 100 %. It is enabled at power up or when the control output is activated. If in doubt set zero

(zero value disables the Soft start function).

ALARM SETPOINT: Tripping point for alarm 1, 2, 3 and 4. Value that defines the point of activation for the programmed alarms with the functions “Lo” or

“ki”.

For the alarms configured with Differential type functions, this parameter defines deviation (band).

Not used for the other alarm functions.

CYCLE OF PROGRAMS

Pr.tb

Program time base

Pr n

Program

number

Ptol

Program

Tolerance

Psp0

Psp9

Defines the time base that will be used by all Ramp

& Soak programs.

Se( - Time basis in seconds;

Min - Time basis in minutes;

Selects the ramp and soak profile program to be edited/viewed. The sequence of parameters that follows refer to this selected program. Total of 20 programs possible.

Maximum admitted deviation of PV with respect to

SP. If exceeded, the program execution is suspended

(the internal timer freezes) until the deviation be returns back within the defined tolerance.

The value 0 (zero) disables the function (the program progresses regardless of the difference between PV and SP).

Program SP’s, 0 to 9: Group of 10 values of SP that define the Ramp and Soak profile segments.

Pt1

Pt9

Segments durations, 1 to 9: Defines the time of duration, in second or minutes, of the segments of the program being edited.

Pe1

Pe9

Program event

Alarms of Event, 1 to 9: Parameters that define which alarms are to be activated during the execution of a certain program segment. The alarms chosen must have its function configured as “rS.”

(See Table 3)

Lp

Link Program

Link Programs: Number of the next profile program to be linked following the current program. Profiles can be linked together to produce larger programs of up to 180 segments

.

0 – do not link to any other program.

CYCLE OF ALARMS:

Fva1

Fva2

Fva3

Fva4

FUNCTIONS OF ALARMS 1 to 4. Defines the functions for the alarms among the options of the

Table 3. bla1 bla2 bla3 bla4

BLOCK ALARM 1 TO 4: This function blocks the alarms when the controller is energized.

YES

- enables initial blocking

NO - inhibits initial blocking

When enabled, the alarm will not be active at power-up, waiting for PV (Process Variable) to reach a non-alarm situation. From this point on the alarm will be free to actuate should a new alarm situation occur. xya1

ALARM HYSTERESIS

:

Defines the difference between the value of PV at which the alarm is

NOVUS AUTOMATION

Controller N1200 xya2 xya3 xya4 triggered and the value at which it is turned off (in engineering units).

A1t1

A2t1

A3t1

A4t1

Alarm Time t1

Defines the temporization time t1, in seconds, for the alarms. Defines the temporization time t1, in seconds, for the alarms time functions. The value 0

(zero) disables the function.

Refer to Table 4 for configuring this parameter timed functions. The value 0 (zero) disables the function.

Refer to Table 4 for configuring this parameter.

A1t2

A2t2

A3t2

A4t2

Alarm Time t2. Defines the temporization time t2, in seconds, for the alarms time functions. The value 0 (zero) disables the function. Refer to Table

4 for configuring this parameter flsh

Flash

Allows visual signalization of an alarm occurrence by flashing the indication of PV in the operation level. The user chooses which alarms are to be associated with this feature.

CYCLE OF SCALE

Type

Type

fltr

Filter

INPUT TYPE: Selects the input signal type to be connected to the process variable input. Refer to

Table 1 for the available options.

Digital Input Filter - Used to improve the stability of the measured signal (PV). Adjustable between 0 and 20. In 0 (zero) it means filter turned off and 20 means maximum filter. The higher the filter value, the slower is the response of the measured value.

Dppo

Decimal Point

Selects the decimal point position to be viewed in both PV and SP

.

vnI t

Unit.

Temperature indication in ºC or ºF: root

Square Root

Square Root Function. Applies the quadratic function on the input signal, within the limits programmed in “SPLl” and “spkL.”

YES

Enables the Function no

Does not enable the Function

The indication assumes the lower limit value when the input signal is below 1 % of programmed span.

Parameter available for lineal inputs only.

0ffs

Offset

SENSOR OFFSET: Offset value to be added to the PV reading to compensate sensor error.

Default value: zero. e.rsp

Enables remote SP.

Enable Remote

SP

YES

Enables the Function no

Does not enable the Function

This parameter is not displayed when the remote

SP selection is defined by a Digital Input. rsp

Remote SP type

rsll

Remote SP

Low Limit

Defines the signal type for the remote SP.

0-20

current of 0-20 mA

4-20

current of 4-20 mA

0-5 voltage of 0-5 V

0-10

voltage of 0-10 V

Parameter displayed when remote SP is enabled.

REMOTE SETPOINT LOW LIMIT: used in conjunction with the rSxL

, scales the remote SP input defining the initial value in the remote SP indication range.

Parameter displayed when remote SP is enabled.

7 / 13

Controller N1200 rskl

Remote SP

High Limit

REMOTE SETPOINT HIGH LIMIT: defines the full scale indication of the Remote Setpoint

.

Parameter displayed when remote SP is enabled.

Spll

Setpoint Low

Limit

Defines the SP lower limit of SP.

For the linear analog input types available (0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the minimum PV indication range, besides limiting the SP adjustment.

Spxl

Setpoint High

Limit

Defines the upper limit for adjustment of SP.

For the linear analog input types available (0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the maximum PV indication range, besides limiting the SP adjustment. rtll

Retransmission

Low Limit

In association with the rtxl

parameter, it defines the analog retransmission scale for PV or SP. The rtll

represents the. minimum scale value for the analog output

This parameter is displayed only if the analog retransmission is selected in the I/O 5 parameter

(I/O level). rtkl

Retransmission

High Limit

Defines the full scale value for the analog retransmission of PV or SP.

This parameter is displayed only when the analog retransmission is selected in the I/O 5 parameter

(I/O level).

1eov bavd

Baud Rate prty

Parity

Addr

Address

Percentage output value that will be transfer to MV when the SAFE output function is enabled. If

1eov

= 0, the SAFE output function is disabled and the outputs are turned off in the occurrence of a sensor fail.

Digital communication Baud Rate selection, in kbps: 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2

Parity of the serial communication. none

Without parity

Ewem Even parity

0dd

Odd parity

SLAVE ADDRESS SELECTION: Identifies the controller in the network. The possible address numbers are from 1 to 247.

CYCLE OF I/OS (INPUTS AND OUTPUTS)

Io 1

Function of the channel I/O 1: Selection of the function used in the channel I/O 1, according to the

Table 2.

Io 2

Function of the channel I/O 2: Selection of the function used in the channel I/O 2, according to the

Table 2.

Io 3

Function of the channel I/O 3: Selection of the function used in the channel I/O 3, according to the

Table 2.

Io 4

Function of the channel I/O 4: Selection of the function used in the channel I/O 4, according to the

Table 2.

NOVUS AUTOMATION

Io 5

Function of the channel I/O 5: Selection of the function used in the channel I/O 5, according to the

Table 2.

CALIBRATION CYCLE

All of the input and output types are calibrated in the factory. If a recalibration is required, this should be carried out by a experienced personnel. If this cycle is accidentally accessed, pass through all the parameters without pressing the or keys

pass

Password

Input of the Access Password.

This parameter is presented before the protected cycles. See item Protection of Configuration. inL(

Input Low

Calibration

See section MAINTENANCE / Input Calibration.

Enter the value corresponding to the low scale signal applied to the analog input. ink(

Input High

Calibration

See section MAINTENANCE / Input Calibration.

Enter the value corresponding to the full scale signal applied to the analog input. rsL(

Remote SP Low

Calibration

See section: MAINTENANCE / Input Calibration

Enter the value corresponding to the low scale signal applied to the remote SP input. rsk(

Remote SP

High Calibration

See section: MAINTENANCE / Input Calibration.

Enter the value corresponding to the full scale signal applied to the remote SP input.

0vL(

Output Low

Calibration

See section MAINTENANCE / Analog output

Calibration. Enter the analog low value as measured at the analog output.

0vk(

Output High

Calibration

See section MAINTENANCE / Analog output

Calibration. Enter the analog high value as measured at the analog output. rstr

Restore

(j

Restores the factory calibration for all inputs and outputs, disregarding modifications carried out by the user.

Adjusts the of cold junction temperature value. ktyp

Hardware Type

Parameter that informs the controller about the hardware optionals installed. It should not be altered by the user, except when an accessory is introduced or removed.

0 – Basic model. Without optional items

1 – 485

2 – 3R

3 – 3R + 485

4 – DIO

5 – DIO + 485

8 – HBD

9 – HDB + 485

Note: The options 6 and 7 not are used.

Pas.(

Allows defining a new access password, always different from zero.

Prot

Sets up the Level of Protection. See Table 7.

Freq

Mains frequency. This parameter is important for proper noise filtering.

8 / 13

OPERATION CYCLE TUNING CYCLE

PV and SP

(trl

PV and MV

Epr p.seg t.seg

Rvn atvn pb ir dt

(t

Kyst a(t

Lbd.t bias ovll ovkl sfst

Spa1

- spa4

PROTECTION OF CONFIGURATION

The controller provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation.

The parameter Protection (PROt), in the Calibration level, determines the protection strategy, limiting the access to particular levels, as shown by the table below.

Protection level

1

2

3

4

5

6

7

8

Protected cycles

Only the Calibration level is protected.

I/Os and Calibration levels.

Tuning, I/Os and Calibration levels.

Alarm, Tuning, I/Os and Calibration levels.

Programs, Alarm, Tuning, I/Os and Calibration levels.

Tuning, Programs, Alarm, Input, I/Os and

Calibration levels.

Operation (except SP), Tuning, Programs, Alarm, input, I/Os and Calibration levels.

Operation, Tuning, Programs, Alarm, Input, I/Os and Calibration levels.

Table 7 – Levels of Protection for the Configuration

Access Password:

The protected levels, when accessed, request the user to provide the

Access Password for granting permission to change the configuration of the parameters on these cycles.

The prompt PASS precedes the parameters on the protected levels.

If no password is entered, the parameters of the protected cycles can only be visualized.

The Access Code is defined by the user in the parameter Password

Change (PAS.(), present in the Calibration level. The factory default for the password code is 1111.

PROGRAM CYCLE ALARM CYCLE CONFIGURATION CYCLE I/O CYCLE

PR.tb pr n

Ptol psp0

psp9 pt1

pt9 pe1

pe9

Lp

Table 6 – All the Controller's Parameters fva1

- fva4 bla1

- bla4 kya1

- kya4 a1t1 a1t2 a2t1 a2t2 flsh type fltr dppo vnit

Root

Offs e.rsp

Rsp

Rsll

Rskl

Spll

Spkl

Ieov

Rtll rtkl

Bavd

Prty addr io1 io2 io3

Io4

Io5

Master Password

The Master Password is intended for allowing the user to define a new password in the event of it being forgotten. The Master

Password doesn’t grant access to all parameters, only to the

Password Change parameter (PAS(). After defining the new password, the protected parameters may be accessed (and modified) using this new password.

The master password is made up by the last three digits of the serial number of the controller added to the number 9000.

As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1.

CALIBRATION

CYCLE

pass

Inl(

Ink(

Rsl(

Rsk(

0vl(

0vk( rstr

(j ktyp

Pas.( prot freq.

PROGRAMS OF RAMP AND SOAK

This feature allows the creation of Ramp and Soak Setpoint Profiles

(Programs). Up to 20 different profiles with 9 segments each can be programmed. Longer profiles of up to 180 segments can be created by linking 2 or more profiles together.

The figure below displays a profile model:

Figure 8 - Example of a Ramp and Roak.

Once a profile is defined and selected for execution (parameter EPr in the operating level), the controller starts to generate the SP profile automatically in accordance with the elaborated program.

To execute a profile with fewer segments just program 0 (zero) for the time intervals that follow the last segment to be executed.

Protection of the access code

The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password.

NOVUS AUTOMATION

SV

SP2

SP1

SP3

SP0

T1 T2 T3

T4=0

Time

Figure 9 - Program example with few segments

9 / 13

Controller N1200

The program tolerance defines the maximum deviation between PV and SP for the execution of the profile. If this deviation is exceeded, the program will be halted until the deviation falls to within the tolerance band.

Programming 0 (zero) in the “Ptol” parameter disables the program tolerance and the profile execution will continue regardless of the PV value (time priority as opposed to SP priority).

LINK OF PROGRAMS

It is possible to create a more complex program, with up to 180 segments, joining the 20 programs. This way, at the end of a program execution the controller immediately starts to run the next one, as indicated in the “LP".

To force the controller to run a given program or many programs continuously, it is only necessary to link a program to itself or the last program to the first.

SV

Program 1

SP5 / SP0

Program 2

SP3

SP4

SP2

SP3

SP1

SP1 SP2

SP4

SP0

T1 T2 T3 T4 T5 T1 T2 T3 T4

Time

Figure 10 - Example of interlinked programs

EVENT ALARM

The Event Alarm function associates the alarms to specific segments of a program. The information of which alarms are to be activated or deactivated is given in parameters “ PE1“ to “ PE9. Press the

and

keys until the desired alarm numbers are displayed.

The Event Alarm requires that the Alarm function be configured as

“rS “.

Notes:

1. If PtoL is different than zero, the controller will wait for the PV to reach the first program set point SP0 in order to start the program execution. Otherwise, it will start promptly.

2. Should any power failure occur, the controller resumes the program execution at the beginning of the segment that was interrupted.

DETERMINATION OF PID PARAMETERS

The determination (or tuning) of the PID control parameters in the controller can be carried out in an automatic way and auto-adaptative mode. The automatic tuning is always initiated under request of the operator, while the auto-adaptive tuning is initiated by the controller itself whenever the control performance becomes poor.

Automatic tuning: In the beginning of the automatic tuning the controller has the same behavior of an ON/OFF controller, applying minimum and maximum performance to the process. Along the tuning process the controller's performance is refined until its conclusion, already under optimized PID control. It begins immediately after the selection of the options FAST, FULL, RSLF or

TGHT, defined by the operator in the parameter ATUN.

Auto-adaptive tuning: Is initiated by the controller whenever the control performance is worse than the one found after the previous tuning. In order to activate the performance supervision and auto-

adaptative tuning, the parameter ATUN must be adjusted for SELF,

RSLF or TGHT. The controller's behavior during the auto-adaptative

tuning will depend on the worsening of the present performance. If the maladjustment is small, the tuning is practically imperceptible for the user. If the maladjustment is big, the auto-adaptive tuning is similar to the method of automatic tuning, applying minimum and maximum performance to the process in ON/OFF control.

Figure 11 – Example of auto tuning

Figure 12 - Example of auto-adaptative tuning

The operator may select, through the ATUN parameter, the desired tuning type among the following options:

OFF: The controller does not carry through automatic tuning or

auto-adaptative tuning. The PID parameters will not be automatically determined nor optimized by the controller.

FAST: The controller will accomplish the process of automatic

tuning one single time, returning to the OFF mode after finishing. The tuning in this mode is completed in less time, but not as precise as in the FULL mode.

FULL: The same as the FAST mode, but the tuning is more precise and slower, resulting in better performance of the P.I.D. control.

 SELF: The performance of the process is monitored and the

auto-adaptative tuning is automatically initiated by the controller whenever the performance becomes poorer.

After a tuning cycle, the controller starts collecting data from the process for determining the performance benchmark that will allow evaluate the need for future tunings. This phase is proportional to the process response time and is signaled by the flashing TUNE indication on the display. It is recommended not to turn the controller off neither change the SP during this learning period.

 rSLF: Accomplishes the automatic tuning and returns into the

SELF mode. Typically used to force an immediate automatic

tuning of a controller that was operating in the SELF mode, returning to this mode at the end.

TGHT: Similar to the SELF mode, but in addition to the auto-

adaptative tuning it also executes the automatic tuning whenever the controller is set in RUN=YES or when the controller is turned on.

Whenever the parameter ATUN is altered by the operator into a value different from OFF, an automatic tuning is immediately initiated by the controller (if the controller is not in RUN=YES, the tuning will begin when it passes into this condition). The accomplishment of this automatic tuning is essential for the correct operation of the autoadaptative tuning.

NOVUS AUTOMATION 10 / 13

The methods of automatic tuning and auto-adaptative tuning are appropriate for most of the industrial processes. However, there may be processes or even specific situations where the methods are not capable to determine the controller's parameters in a satisfactory way, resulting in undesired oscillations or even taking the process to extreme conditions. The oscillations themselves imposed by the tuning methods may be intolerable for certain processes. These possible undesirable effects must be considered before beginning the controller's use, and preventive measures must be adopted in order to assure the integrity of the process and users.

The “TUNE” signaling device will stay on during the tuning process.

In the case of PWM or pulse output, the quality of tuning will also depend on the cycle time adjusted previously by the user.

If the tuning does not result in a satisfactory control, refer to Table 8 for guidelines on how to correct the behavior of the process.

PARAMETER

Proportional Band

Rate of Integration

Derivative Time

VERIFIED PROBLEM

Slow answer

Great oscillation

Slow answer

Great oscillation

Slow answer or instability

Great oscillation

Table 8 - Guidance for manual adjustment of the PID parameters

SOLUTION

Decrease

Increase

Increase

Decrease

Decrease

Increase

MAINTENANCE

PROBLEMS WITH THE CONTROLLER

Connection errors and inadequate programming are the most common errors found during the controller operation. A final revision may avoid loss of time and damages.

The controller displays some messages to help the user identify problems.

MESSAGE

----

Err1

Err6

DESCRIPTION OF THE PROBLEM

Open input. No sensor or signal.

Connection and/or configuration errors. Check the wiring and the configuration.

Other error messages may indicate hardware problems requiring maintenance service. When contacting the manufacturer, inform the instrument serial number, obtained by pressing the key

for more than 3 seconds.

CALIBRATION OF THE INPUT

All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you are not familiar with these procedures do not attempt to calibrate this instrument.

The calibration steps are:

a) Configure the type of input to be calibrated.

b) Configure the lower and upper limits of indication for the maximum span of the selected input type.

c) At the input terminals inject a signal corresponding to a known indication value a little above the lower display limit.

d) Access the parameter “inLC”. With the keys and adjust the display reading such as to match the applied signal. Then press the

P

key.

e) Inject a signal that corresponds to a value a little lower than the upper limit of indication.

f) Access the parameter “inLC”. With the keys and adjust the display reading such as to match the applied signal. Then press the

P

key.

Note: When checking the controller calibration with a Pt100 simulator, pay attention to the simulator minimum excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by the controller.

NOVUS AUTOMATION

Controller N1200

ANALOG OUTPUT CALIBRATION

Configure I/O 5 for the current output to be calibrated, be it

control or retransmission.

In the screen “Ctrl”, program manual mode ( man

).

Connect a current meter to the analog output.

Enter the calibration cycle with the correct password.

Select the screen “ovLC”. Press the keys and for the

controller to recognize the calibration process of the current

output.

Read the current indicated on the current meter and adjust the

parameter “ovLC” to indicate this current value (use the keys

and

)

Select the screen “ovxC”. Press the keys and for the

controller to recognize the calibration process of the current

output.

Read the current indicated on the current meter and adjust the

parameter “ ovkC

” to indicate this current value

 Press the key

P

in order to confirm the calibration procedure

and return to the operating level.

SERIAL COMMUNICATION

The controller can be supplied with an asynchronous RS-485 digital communication interface for master-slave connection to a host computer (master).

The controller works as a slave only and all commands are started by the computer which sends a request to the slave address. The addressed unit sends back the requested reply.

Broadcast commands (addressed to all indicator units in a multidrop network) are accepted but no reply is sent back in this case.

CHARACTERISTICS

Signals compatible with RS-485 standard. MODBUS (RTU)

Protocol. Two wire connection between 1 master and up to 31

(addressing up to 247 possible) instruments in bus topology. The communication signals are electrically insulated from the rest of the device;

Maximum connection distance: 1000 meters.

Time of disconnection for the controller: Maximum 2 ms after last

byte.

 Selectable speed; 8 data bits; 1 stop bit; selectable parity (no parity, pair or odd);

Time at the beginning of response transmission: maximum 100 ms after receiving the command.

There is no electrical isolation between serial communication

(RS485) and channel I/O5.

The RS-485 signals are:

D1 D D + B Bi-directional data line.

D0

D:

D - A Bi-directional inverted data line.

C

GND

Optional connection that improves the performance of the communication.

Terminal 16

Terminal 17

Terminal 18

CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION

Two parameters must be configured for using the serial type: bavd:

Communication speed. prty:

Parity of the communication. addr:

Communication address for the controller.

11 / 13

REDUCED REGISTERS TABLE

FOR SERIAL COMMUNICATION

Communication Protocol

The MOSBUS RTU slave is implemented. All configurable parameters can be accessed for reading or writing through the communication port. Broadcast commands are supported as well

(address 0).

The available Modbus commands are:

03 - Read Holding Register

05 - Force Single Coil

06 - Preset Single Register

16 - Preset Multiple Register

Holding Registers Table

Follows a description of the usual communication registers. For full documentation download the Registers Table for Serial

Communication in the N1200 section of our web site – www.novusautomation.com

.

All registers are 16 bit signed integers.

Address Parameter Register Description

0000 Active SP Read: Active control SP (main SP, from ramp and soak or from remote SP).

Write: to main SP.

Range: from spll to spkl.

0001 PV Read: Process Variable.

Write: Not allowed.

Range: Minimum value is the one configured in spll and the maximum value is the one configured in spkl. Decimal point position depends on dppo value.

In case of temperature reading, the value read is always multiplied by 10, independently of dppo value.

0002 MV Read: Output Power in automatic or manual mode.

Write: Not allowed. See address 28.

Range: 0 to 1000 (0.0 to 100.0 %).

NOVUS AUTOMATION

Controller N1200

SPECIFICATIONS

DIMENSIONS: ...................................... 48 x 48 x 110 mm (1 / 16 DIN)

............................................................ Approximate Weight: 150 g

CUTOUT IN THE PANEL: ................. 45.5 x 45.5 mm (+0.5 -0.0 mm)

POWER SUPPLY.................... 100 to 240 Vac/dc (±10 %), 50 / 60 Hz

Optionally 24V: .................. 12 to 24 Vdc / 24 Vac (-10 % / +20 %)

Maximum consumption: ........................................................ 9 VA

ENVIRONMENTAL CONDITIONS:

Operation Temperature: ............................................... 5 to 50

C

Relative Humidity: .......................................... 80 % max. @ 30 ºC

For temperatures above 30 ºC, reduce 3 % for each ºC

Internal Use; Category of installation II, Degree of pollution 2; altitude < 2000 m

INPUT ............. T/C, Pt100, voltage and current (according to Table 1)

Internal Resolution: .................................. 32767 levels (15 bits)

Resolution of Display: .... 12000 levels (from - 1999 up to 9999)

Rate of input reading: ................................. up to 55 per second

Precision: . Thermocouples J, K, T, E: 0.25 % of the span

1 ºC

................... Thermocouples N, R, S, B: 0.25 % of the span

3 ºC

................................................................ Pt100: 0.2 % of the span

.............................. 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of the span

Input Impedance: 0-50 mV, Pt100 and Thermocouples: >10 M

................................................................................. 0-5 V: >1 M

................................................. 4-20 mA: 15

(+2 Vdc @ 20 mA)

Measurement of Pt100: ............... Three wire type, (

=0.00385) with compensation for cable length, excitation current of 0.170 mA.

All input and output types are factory-calibrated. Thermocouples according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;

ANALOGICAL OUTPUT (I/O5): ..... 0-20 mA or 4-20 mA, 550

max.

31000 levels, insulated, for control or retransmission of PV and SP

CONTROL OUTPUT:

2 Relays SPST-NA (I/O1 and I/O2): 1.5 A / 240 Vac, general use

.......................... 1 Relay SPDT (I/O3): 3 A / 250 Vac, general use

.......................... Voltage pulse for SSR (I/O5): 10 V max. / 20 mA

............. Voltage pulse for SSR (I/O3 and I/O4): 5 V max. / 20 mA

ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997 and EN 61326-1 / A1:1998

SAFETY: ........................ EN61010-1:1993 and EN61010-1 / A2:1995

USB INTERFACE 2.0, CDC CLASS (VIRTUAL

COMMUNICATIONS PORT), MODBUS RTU PROTOCOL.

SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3

MM;

FRONT PANEL: IP65, polycarbonate - UL94 V-2;

CASE: IP30, ABS+PC UL94 V-0;

STARTS UP OPERATION: after 3 seconds connected to the power supply;

CERTIFICATIONS: ........................................ CE / UL (FILE: 300526)

12 / 13

IDENTIFICATION

N1200 -

A

3R -

B

485 -

C

A: Controller Model:

N1200;

B: Optional I/Os:

Blank (basic version, without I/O3 nor I/O4);

3R (SPDT Relay in I/O3);

DIO (Digital I/Os in I/O3 and I/O4);

HBD (Burnt-Out Resistance detection);

C: Digital Communication:

Blank (basic version, without serial communication);

485 (RS485, Modbus protocol)

D: Power Supply:

Blank (basic version, 100 to 240 Vac/dc input);

24V (12 to 24 Vdc / 24 Vac input voltage);

24V

D

WARRANTY

Warranty conditions are available on our web site www.novusautomation.com/warranty .

Controller N1200

NOVUS AUTOMATION 13 / 13

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement