installation and maintenance instructions


Add to my manuals
22 Pages

advertisement

installation and maintenance instructions | Manualzz

DC INVERTER

16kw

MODEL SERIES

Intelligent i16

User Manual

Page 1

Version 15 – 07/04/2016

Version 15 – 07/04/2016

Page 2

Safety notice

1. General ---------------------------------------------------------------- 3

2. System description ----------------------------------------------------- 3

3. Installation -------------------------------------------------------------- 3-12

4. Controller manual-----------------------------------------------------

5. Specification -----------------------------------------------------------

12-23

24-31

6. Maintenance------------------------------------------------------------- 31

7. How to get the most out of your heat pump--------------------- 32

8. Disposal------------------------------------------------------------- 32

Safety Notice

Never perform any cleaning operations before switching off the external isolator

Do not modify safety or control devices without consultation with the manufacturer

Do not pull, detach or twist the electrical cables coming from the unit

Do not introduce pointed objects through the grill and into the fan.

Version 15 – 07/04/2016

Page 3

1. GENERAL

The Husky Intelligent I16is an air source heat pump for space heating and domestic hot water heater for houses, apartment blocks and small industrial premises. Outdoor air is used as a heat source creating free energy to heat your home.

2. SYSTEM DESCRIPTION

The Intelligent I16is a monoblock (single unit) air/water heat pump, specially designed for the colder climate.

There is no need for bore holes and usually the system can be installed within 2 days.

The Intelligent I16can both heat hot water effectively at high outdoor temperatures and give a high output to the heating system at low outdoor temperatures. If the outdoor temperature drops to a level lower than minus 20c

(factory setting), the auxiliary heater switches on to ensure the heat pump unit works normally. The heat pump controller is an intelligent wired system.

The Husky Intelligent I16is rated as 16KW.The Material/components are chosen to provide a long service life and to fully withstand harsh outdoor conditions.

Intelligent I16has two different installation options:

1). Space heating + DHW (Domestic hot water)

2). Space heating or DHW

3.INSTALLATION

3.1: General points for installation engineer

3.1-1: Transport and storage

The unit should be transported and stored vertically.

Version 15 – 07/04/2016

Page 4

3.1-2: Inspection of the installation

Current regulations require the heating installation to be inspected before it is commissioned.

The inspection must be carried out by a suitably qualified person and should be documented. If the heat pump is replaced, the installation must be inspected again. In the event of installation with unvented (closed) heating systems, G3 unvented guidelines must be followed during the installation. It should be noted that the heat pump provides the first measure of defense against high pressure temperatures. A further 2 must be installed to comply with the G3 unvented procedures.

3.1-3: Siting the heat pump

The unit is placed (securely fixed) outdoors on a firm base, preferably a concrete foundation. It should not be positioned next to sensitive walls, for example, next to a bedroom. Also ensure that the placement does not inconvenience any neighbors. Local planning permission in all cases applies.

Large amounts of condensation water as well as de-icing water from defrosting can be produced. You must provide good drainage at the installation area and make sure the water cannot run out onto paths or the like during periods that ice can form. Ideally, condensation water is led off to a water drain or a suitable soak away. The unit can be sited against the wall.

3.1-4: Controller:

The Intelligent I16is equipped with an external electronic controller that handles all functions necessary for heat pump operations. Defrosting, stop at max/min temperature, connection of the compressor heater as well as enabling the auxiliary electrical heater, monitoring of motor protection and pressure switches are all controlled.

The controller is set during installation and can be used during a service.

Under normal operating conditions the home owner does not need to have access to the controller. The Intelligent

I16 has an integrated electronic outlet water temperature sensor that limits the outlet temperature to 60℃.

3.2 Installation design

The Intelligent I16can be installed in several different ways.

The heat pump is not to be used without a buffer tank or without a suitable hot water tank (designed for heat pumps).

There are not extra controls or safety devices required with each Husky heat pump unit.

Any safety equipment installed (e.g. cylinder g3 unvented) must be installed in accordance with current regulations for all installation options.

When connecting with the Intelligent I16, the total water volume in the heat pump pipe system and buffer tank must be at least 5litres per KW of output.

Version 15 – 07/04/2016

Page 5

A) Space Heating + DHW

B). Space Heating Mode Only

Version 15 – 07/04/2016

Page 6

C)

DHW

2x Intelligent I16Installation. Space Heating/Cooling +

3.3Pipe Connection

28mm pipe is recommended.

The pipe work must be flushed before the heat pump is connected, so that any contaminants do not damage the components parts.

The heating water inlet and outlet direction must be connected according to the marked areas on the heat pump.

All outdoor pipes must be thermally insulated with at least 19 mm thick pipe insulation. The insulation must also be vapor and UV resistant.

The water circulation pump must at all times be operational (even if Intelligent I6is not running) to prevent any possible damage due to freezing. Even when in standby mode, the circulation pump is controlled directly from the

Intelligent I16, which takes the outdoor temperature and temperature in the pipe into consideration to decide whether to circulate water within the system.

Shut-off valves and drain valves are fitted so that Intelligent I16can be emptied in the event of prolonged power failures.

The supplied flexible hoses act as vibration dampeners. The flexible hoses are fitted so a slight bend is created, thus acting as vibration dampening.

Important: Even though the Intelligent I16has anti-freeze protection, if the circulation pump fails or there is a problem with the power supply, there is still a risk of damage due to freezing. During the installation Anti- freeze is recommended and can affect your warranty.

Version 15 – 07/04/2016

Page 7

3.4 Electrical Connection

Electrical installation and service must be carried out under the supervision of a qualified electrician. Electrical installation and wiring must be carried out in accordance with local regulations.

3.4-1: Electric Diagram Intelligent I16

3.4-2: Circulation Pump

The integral circulation pump is controlled by the Intelligent I16. Pump activity depends on the status of heating/hot water requirements and outdoor temperature (anti-freeze function). The circulation pump can also be removed and fitted inside the building.

3.4-3:Anti-freeze Function

The heat pump protects itself, and the cylinder by maintaining a minimum temperature of 20 degrees in the cylinders and a minimum of 5 degrees in the Heat pump itself.

Version 15 – 07/04/2016

Page 8

3.4-4: Compressor Heater

The Intelligent I16is equipped with a compressor heater that heats the compressor before start-up and when the compressor is cold. The compressor heater must have been connected for 10 minutes before the FIRST start up.

The compressor heater will start automatically after turning on the heat pump and the ambient air temperature is lower than 20C.

3.5 COMMISSIONING

3.5-1: Preparations

Before commissioning, make sure the compressor heater has already pre-heated for 10 minutes.

1) Compressor Heater

As mentioned above, if the temperature is lower than 20C, it is important that the compressor heater can heat the compressor before the first start up. In order to ensure this happens, please follow the instructions below: a. Disconnect the power connection of compressor, aux electric heater, circulation pump. (Due to anti-freeze protection, the compressor, auxiliary electric heater and circulation pump could start in stand-by status. b. Switch on the outside Isolator and power connection of the unit. c. After 10 minutes, switch off the outside Isolator and re-connect the power connection of compressor, auxiliary electric heater and circulation pump.

2) Filling and Venting

Fill the system slowly ensuring bleed valves are open.

3.5-2: Inspection before Start up

1) Mechanical Inspection: a. Check the cabinet and inside pipe system for possible damage during transportation. b. Check that the heating water circuit is filled and well vented. Check the pipe system for leaks. c. Check the Fan making sure it can move freely.

2) Electric System Inspection a. Check the power supply (voltage/frequency) matches the rating label and specification. b. Check all the electrical connections for loose or damaged wires due to transportation.

3) Pipe Inspection a. Check all the valves, and water flow directions. b. Check for any possible leaks inside or outside of unit. c. Check the insulation of all the pipes.

Version 15 – 07/04/2016

Page 9

3.5-3: Start up and commissioning (only to be performed by a Husky engineer). a. After the system inspection is finished, startup can begin. b. Connect the power supply; switch on the isolator to turn on the heat pump. c. When the heat pump switches on, the water circulation pump and the fan will start 60 seconds before compressor. d. Air is initially released from the hot water and venting may be necessary. If bubbling sounds can be heard from the heat pump, the circulation pump or radiators the entire system will require further venting. When the system is stable

(correct pressure and all air eliminated) the automatic heating control system can be set as required. e. Check heating water inlet/outlet temperature difference after the system is stable(in accordance with your commission sheets). f. Check the compressor exhaust and suction temperature (in accordance with you commissioning sheet). g. Adjust the parameters according to the selected data sheet.

4. CONTROLLER MANUAL

4.1: Operating Mode Principle

1) Space Heating Mode

Temperature setting range is 10-55 ° C, the factory setting is 45℃;

2) Hot Water Mode

Temperature setting range is 10-60 ° C(50~60c is increased by electric heater), the factory setting is 50℃;

3) Defrost Cycle

Auto Defrost mode (normal defrosting)

All Husky Heat pumps are fitted with intelligent defrost controls. A number of parameters are taken into account before defrost begins and ends. The parameters should be set as per factory settings or otherwise set out by a Husky engineer. The defrost time will vary depending upon the conditions the heat pump is working in. The length between defrosts will either extend or contract depending upon the parameters set.

Version 15 – 07/04/2016

Page 10

4.1.1 The Controller

There are 6 keys for operation.

4.1.2 Buttons Definition

(1)Clock: Change the clock and timer(3)Down Key (4) Up Key:increase

(6)Confirm Key:confirm the setting(8) Mode Key:change the mode

(10) Standby Key:Turn on or off heat pump

4.1.3 Icon Definition

17

20

23

26

Item Icon meaning

5 Pending

11

14 timer period

Sterilization

29

32

Cooling (if applicable)

Temperature

Defrost

E-Heater

Week Display

Timer Off

Item Icon meaning

7

12

15

18

21

24

30

Pending

Fan

Auto Mode

Service

Buffer/Hot Water Indicator

Anti-freeze

27 Reserve

Time Display

19

22

25

28

Item Icon meaning

9 Pending

13

16

DHW

Buffer

31

Lock

Temperature (C/F)

Circulation Pump

Compressor

Timer On

Version 15 – 07/04/2016

Page 11

4.2 Changing Modes( 7 modes )

Press the M repeatedly to choose the mode, icons will flash according to the mode you are about to select the following modes are applicable; a) Heating Only – Icon 16 only b) Domestic hot water only – icon 13 only c) Heating and hot water – icons 16 and 13 d) Auto – Icon 15

Please note: when choosing you mode, press return (press button 6 to set)

4.3 Changing the Parameters

By pressing M (Key 8) and the UP arrow (Key 4) together, you will enter into the parameter modes. By using the UP and DOWN arrow, scroll to the parameter number you want to change, press the return key (Key 6) change the setting using the UP and DOWN arrows and to set press the return the key (Key 6) once more. Continue choosing other parameters when necessary.

IMPORTANT – Please note any changes can only by advised by a Husky engineer. This could invalidate your warranty.

4.4 Antibacterial Settings

Antibacterial settings will be performed daily taking the water in the DHW tank to 65 degrees. I.e. separate sterilizations can be performed by adding a separate controller to an added emersion heater.

4.5 Clock Setting

Press Key 1 and firstly the day icon flashes, using UP and DOWN arrow to set the day, press the clock to confirm. The hour then flashes, again using the UP and DOWN arrow to set, press Key 1 to confirm.

press key, week icon flash, press▲ ▼ to set the date,press for confirmation。Then the hour digit flash. As below:

Version 15 – 07/04/2016

Page 12

press▲ ▼ to set the date,press for confirmation。Then the minute digit flash. As below: press▲ ▼ to set the date,press for confirmation。Then exit.

4.6 Night Mode

Night mode can be used to “set back” your room temperature by 2 degrees. During this setting the fan speed slows down.

To switch the night mode on, change parameter 47 to “1” (0 is off). The time of night mode is set using parameter 48 (start time) and 49 (end time.

Please note – With night mode the DHW function will run as normal.

4.7 Weather Compensation and Home Optimization

The Intelligent I16 is equipped with 3 heating modes – Fixed Temperature, Weather Compensation and Intelligent Home

Optimization (IHO). IHO is the default function and your target room temperature is set within your parameters (parameter

29). This means your heat pump will produce enough temperature in the water to achieve your required room temperature.

Weather Compensation is programmable using parameters 45 and 46. If this function is used, it should only be set by a Husky engineer. Please see below the Weather Compensation graph.

Weather Compensation Graph

Version 15 – 07/04/2016

Page 13

4.8 System Protection and Error Codes

Code Fault

E1 compressor overheat or discharge

E2

E3 pipe or return air temperature sensor error

LED2 remark

Decided by outdoor unit high temperature protection red and flashes

Outdoor air temperature sensor error Flashes 3 times Sensor fault

Flashes 6 times Sensor fault

E4

E5

E6

AC return water temp sensor error

AC leaving water temp sensor error

DHW temp sensor error red and flashes red and flashes red and flashes

Sensor fault

Sensor fault

Sensor fault

E7

E8

E9 solar water temp sensor error fan coil high temp protection system anti-freeze

As normal Sensor fault red and flashes Check and test fan coil red and flashes Check return sensor and water flow

EA DHW anti-freeze

EB indoor refrigerant pipe sensor error red and flashes Check return sensor and water flow

No flash Sensor fault

EC water source inlet water sensor error No flash

ED water source leaving temp sensor No flash

Sensor fault

Sensor fault

P4

P5

P6

P7

P8

P9

EE

EF water source anti-freeze protection No flash water source water flow not enough No flash

EG Indoor ambient sensor error

F1 Aaa voltage protection

No flash

Flash 1 time

F2

F3

F4

F5

F6

N/A

N/A

Sensor fault

Voltage is too high or too low, heat pump will recover when power module PFC error compressor abnormal stop

Red and flashes

Red and flashes voltage is normal. Check Voltage (165~265VAC)

Check wiring between controller and PCB

Check compressor. Reasons for stop could be power cut. outdoor module radiator sensor error Flashes 5 time Sensor fault outdoor current sensor error Flash 8 time Sensor fault or test current.

Communication error, check wiring

F7

IPM error or Module control board error

Compressor Non Start

Red and flashes

Red and flashes

Check compressor

F8

F9

FA

Over current

Discharge sensor error

Outdoor module overheat, over current outdoor coil over heat

Red and flash Check compressor, compressor too high

Flash 7 time Sensor fault

Flash 5 time Check compressor and PCB boards

FB

/E8

P1

P2 high pressure protection low pressure protection

Flash 15 time Check defrost function and 4 way valve

Flashes 2 time Check EEV, refrigerant and high pressure switch

Flash 9 time Check refrigerant for leaks EEV and low pressure switch

P3 compressor discharge air over heat protection over current protection

Flash 10 time Check sensor, refrigerant and EEV

Flash 11 time Check refrigerant, EEV and current sensor indoor unit water flow error No flash N/A outdoor water flow error ( For GH) Flash 17 time N/A miss phase Red and flash Check power supply wrong phase communication error

Red and flash Phase problem, check power supply

Red and flash Check PCB, controller and wiring

Please note, to reset the system after a fault. Please cut the power for 60 seconds (using isolator provided) and reboot.

Version 15 – 07/04/2016

Page 14

4.9. System Adjustable Parameter Table

Press M+▲key on wire controller for 3 seconds, it will show PXX to check and set the data

Code name

P00 Auto restart

P01 DHW hot water temp differential

Range

0:off;1:on default Remark

1

P02 AC temp differential

2~15℃

2~15C

7℃

7℃

P03

P04

P06

Coil copper pipe temperature to activate defrost water source side anti-freeze temp

Defrost Exit Temperature

(for Geo heat pump)

P07 Maximum defrost time

P08 defrost interval time (minimum time between defrosts)

P09 ambient temp to activate hot water e-heater

P10 ambient temp to activate AC e-heater

P12 compressor discharge air protection temp

-20~20℃

P11 DHW frequency limitation percentage on max frequency. (Controls 2~10, (equal to the highest he power output for DHW)

(If heat pump max is 90HZ, p11=9, DHW only run 81hz) frequency 20~100%)

100~127℃

P13 defrost interval multiple times control (Multiplies the setting in parameter 8 by the number set)

P14 functional parameter

-20~5℃

N/A

10~35℃

15~99 minutes

15~99 minutes

-20~20℃

0:no defrost;1~4;defrost interval time multiple rate

0:G3 is seasonal switching valve;

-7℃

N/A

10

15

55

-20℃

-20℃

10

125

1

0

P19 fixed frequency

P20 Fixed frequency setting

P21 EEV manually initial open degree (heating) /2

P22 EEV manually initial open degree (cooling)/2

P23 EEV control mode

P24 EEV Temp differential to stop the valve (heating)

P25 EEV temp differential to stop the valve (cooling)

P26 water pump working mode

P27 second heat source validation

P28 starting air temp for second heat source

P29 room target setting temp

P30 buffer tank highest temp

P31 buffer tank lowest temp

P32 water temp adjust range

P33 water temp adjust interval

P34 longest counting period

P35 target water temp modification value

P36 ambient temp correction factor X100

P37 starting ambient temp for calculation

P38 temp differential to reduce frequency

P39 target of low frequency

P40 monitoring interval (to adjust frequency)

P41 temp interval

P42 increase frequency adjustmentX100

P43 decrease frequency adjustment X100

P44 target temp tolerance

P45 weather compensation curve offset value

P46 Weather compensation curve maximum temperature value

P47 night mode

P48 night mode starting point

P49 night mode ending point

1:G3is solar valve ;

10~100 HZ

0:manual frequency;

1:auto running frequency

50~240 (Only valid when P23=3)

50~240(Only valid when P23=3)

0—no;1—checking;2—manual;

3—auto

50HZ

1

180

150

3

-5~10℃

-5~10℃

2℃

4℃

0

(running 1 minute every 15minutes)

0

-30~15℃(On when lower than this) -15℃

10-28℃ 21℃ (H)

35-55℃

15-30℃

45℃ (G)

27℃ (L)

1-5℃

20-255min

6-48H

-2℃-5℃

10-200

4℃ (F)

20 min (I)

24H

2℃

(J)

(E)

-7-15℃

4-15℃

15-90

1-15min

1-4℃

2-50(%)

2-50 (%)

1-3℃

-15~15℃

30~50℃

75

7℃

(C)

(B)

5℃

T

40 (U

5 min (V

1℃

W

20

40

2℃

7℃

S

Y

Z

45℃

0

0-23(time)

0-23(time)

22

22

Remarks:

Version 15 – 07/04/2016

Page 15

1. Forced anti-bacterial, press M key for 5 seconds until hearing a beep, the anti-bacterial mode will now function

2. Parameter reset:Press the retune key until hearing a beep. This will reset al parameters to default

4.9.1 Function DIP switchSW1Changes will be valid after powering up the unit

SW1-1 OFF:water source ; ON:air source

SW1-2

SW1-3

SW1-4

SW1-5

SW1-6

OFF AC heating control mode 1 ON AC heating control mode 2 reserved

OFF: inverter outdoor; ON: fix speed outdoor

Reserved

OFF: DHW valid; ON: DHW not valid

SW1-7 OFF: heating valid ; ON: heating not valid

SW1-8 OFF: cooling valid; ON: cooling not valid

5

. Parameter Visuals

Press M + ▼ keys for 3 seconds it will take you into the Parameter Visuals.

No name

00 Outdoor Coil Temperature

01 Compressor Discharge temp

02 Ambient Temperature

Range / meaning

-30~97 ℃

-30~128 ℃

-30~97 ℃

03 Water Flow Temperature

04 Hot Water

05 Solar

06 DIP switch input state

07 DIP switch input state

08 DIP switch input state

09 DIP switch input state

-30~97 ℃

-30~97 ℃

-30~97 ℃ remark

Calculation parameter D

10 High Pressure Switch State

11 Over Current Protection Switch

12 Low Pressure Switch State

13 Inner Water Flow Switch (for AH, GH)

14 External Water Flow Switch (for GH)

15 Second High Pressure Switch State

19 Compressor Running Hz

20 Outdoor Fan Motor

21 Bent Axle Heater

22 Four Way Valve

23 Bypass Valve

24 1 Electrical Valve

25 2 Electrical Valve

26 3 Electrical Valve

27 1 Electrical Heater 1

28 2 Electrical Heater 2

29 C4 Water Pump

30 C5 Water Pump

31 C6 Water Pump

32 Accumulation days since last antibacterial

33 Cooling Setting Temperature

34 Heating Setting Temperature

35 Hot Water Setting Temperature

36 Anti-bacterial Setting Temperature

37 Outdoor Modular Temperature

38 Outdoor Back Temperature

Displays frequency

1:running;0:stop

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

1:on;0:off

0-99

Real setting temp

Real setting temp

Real setting temp

Real setting temp

-30~97 ℃

-30~97 ℃

Version 15 – 07/04/2016

Page 16

39 Inner Pipe Temperature

40 Expansion Valve Open Degree

41 Water Source Side Inlet Water Temperature

42 Water Side Leaving Temperature

43 Solar Water Tank Temperature

44 Refrigerant leaving heat exchanger

45 Room Temperature Display

46 Home Optimization Target Temperature

-30~97 ℃

N/A

N/A

-30~97 ℃

Displays plate heat exchanger temperature

Calculation parameter A

Version 15 – 07/04/2016

Page 17

6.TECHNICAL SPECIFICATION

6.1 Expanding View of Intelligent I16

6.2 System Drawing Intelligent I16

6.3 Dimensions:

Version 15 – 07/04/2016

Page 18

Intelligent I16 (mm)

Version 15 – 07/04/2016

Page 19

6.4 SPECIFICATIONS

Model:

Rated Heating Capacity

Rated cooling Capacity

Rated Heating Input

Rated cooling Input

Rated Heating Input Current

Rated cooling Input Current

Start Current

COP ( STC AIR 7°C、WATER 35°C)

Rated voltage / frequency

Maximum input power ( Include electric heating )

Maximum input current ( Include electric heating )

High pressure value cut-off pressure

Low pressure valve cut-off pressure

Compressor

Compressor oil type

Compressor oil amount

Refrigerant

Air flow

Fan output

Defrost

Waterproof grade

Noise (sound power)

Max water outlet temperature

Diameter of water connection

Rating water flow

Internal pressure drop at rating water flow

Min/Max heating water pressure

Fuse ( except power supply of compressor, aux heater)

Lowest Operational point, outdoor air/flow line (heating mode )

Highest Operational point, outdoor air/flow line (heating mode )

Lowest Operational point, outdoor air/flow line (cooling mode )

Highest Operational point, outdoor air/flow line (cooling mode )

Color

Net Dimensions ( L/W/H )

Intelligent I16

Intelligent I16

15.50 kw

15.70 kw

3.44 kw

4.40kw

15.6A

20.0A

1.5 A

4.50 W/W

230V/50Hz

5.75 KW

25.0A

4.20 MPa

0.03 Mpa

Mitsubishi Rotary compressor

FV50S

1400 ML

R410A ( 3.90 Kg)

5600m3/h

80 W

Auto defrost with 4 way valve

IPX4

57.8dB(A)

60 °C

DN 25

2.80m³/Hour

2.0 kpa

0.5/3.0 ( bar )

5A

-15°C/58°C

43°C/60°C

10 C/5°C

43°C/5°C

White

1115/425/1270

Net Weight 150 KGS

Rating condition: Heating: Air dry bulb 7 degree, wet bulb 6 degree, water inlet 30 degree, outlet 35 degree

Cooling: Air dry bulb 35 degree, water inlet 23 degree, outlet 18 degree

The above characteristics apply to a new unit with clean heat exchangers

Remark: The above data doesn’t include the circulation pump. If circulation pump is included, the data will be different.

Version 15 – 07/04/2016

Page 20

7. Maintenance

7.1 Maintenance and Cleaning for User

It is good practice to inspect your heat pump regularly. Maintenance should be carried out at least annually to maintain a good lifespan of your heat pump.

1. Regularly clean the filters every 6 months to ensure that the system is clean and to avoid blockage to the system.

2. Units should be kept clean (no leaves or dirt) and no obstructions should be placed in front of or behind the unit.

Good ventilation and regular cleaning (3-6 months) of the evaporator will help maintain efficiency.

3. Ensure the unit has power in the winter whether the unit is used or not.

7.2 Maintenance for Specialist

1. Check the power unit and electrical system.

2. Check the water system, safety valves and exhaust devices are working properly so as not to pump air into the system causing reduced circulation.

3. Check water pump is functioning properly. Make sure the water pipeline and pipe fittings are not leaking.

4. Clear evaporator of any debris.

5. Check the various components of the unit work properly. Inspect the pipe joints and valves branch have inflated oil, to ensure no leakage of the refrigerant unit.

6. Chemically flush the plate heat exchanger after every 3 years.

7. Check refrigerant gas content if necessary.

8. Check delta (water in/out) making it meets the guidelines of delta 3 to 7.

8. How to Get the Most Out Of Your Heat Pump

It is important to understand that you should operate heat pumps differently to conventional heating systems such as gas boilers. Below are some points you should be aware of:

 Since heat pumps produce water at a lower temperature (than gas boilers), it is important to remember the heat up time of your property is slower.

 The lower temperature the heat pump produces, the more efficient it is.

 The higher the ambient temperature (outside temperature), the more efficient the heat pump is.

 The heat pump has a simple job, and that is to maintain the water tanks at the set temperature.

 It’s a good idea to let your heat pump maintain your water tank temperatures 24 hours a day during the winter.

This will enable your central heating controller to call for heat in the home at any time. During the summer you can set the timer on the heat pump controller for your hot water requirements.

With the above in mind, you could decide between the following:

Option 1. You could decide to operate your heat pump during the day time (when temperatures are higher). At the same time you could set the water temperature lower. This will basically charge your home during the day so in the evening the home is warm and the heat pump simply maintains the heat. This is not controlled by the heat pump controller, it is controlled by your central heating controller.

Option 2. You could operate your central heating controller in a similar way to a conventional boiler. You must set the programme at least 1 hour before you need your property to be warm. The downside to this is that you may need to set the water that the heat pump produces to a higher temperature.

Version 15 – 07/04/2016

Page 21

Option 3. You could decide to operate your home with back ground heat. This means you are always (24 hours a day) putting a trickle heat in your home

In all cases it is recommended to maintain a minimum temperature in your home (e.g. 14c to16C) during the evening. This is controlled by your central heating controller.

There is no right and wrong way to operate your heat pump. We cannot tell you which is the most efficient way to operate it since every home is different. What we can say is that you should look for the best way to heat your home that suits your lifestyle. Nowadays with low cost energy monitors, you can easily find the most cost effective way to heat your home. We hope you enjoy your Husky Heat Pump.

8.1Disposal

The unit must be disposed of according to legislation in force in the country concerned.

Waiver and Liability

This publication is the sole property of Husky Heat Pumps. Any reproduction or disclosure is strictly prohibited.

This document has been prepared with maximum care and attention paid to the content shown. Nonetheless, Husky

Heat Pumps waives all liability deriving from the use of such document.

Version 15 – 07/04/2016

Page 22

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement