Conventional Fire Control Panel Operation and Maintenance Manual


Add to my manuals
22 Pages

advertisement

Conventional Fire Control Panel Operation and Maintenance Manual | Manualzz

Sigma CP

(K and T Series)

Conventional Fire Control Panel

(K11020M2, K11040M2, K11080M2)

(T11020M2, T11040M2, T11080M2)

Operation and Maintenance

Manual

Man-1078 Issue 20 March 2014

Index Page

0B1. Introduction ......................................................................................................................... 3 

1B2. Safety and mounting ............................................................................................................. 3 

2B3. Technical specification ........................................................................................................... 4 

3B4. Using intrinsically safe barriers ............................................................................................... 7 

4B5. Control panel fascia............................................................................................................... 8 

5B6. Connecting to the circuit board .............................................................................................. 9 

6B7. Software revision number ...................................................................................................... 9 

7B8. Detection zone wiring .......................................................................................................... 10 

8B9. Sounder circuit wiring .......................................................................................................... 11 

9B10. Connection to remote control terminals .............................................................................. 11 

10B11. Aux 24V DC supply ............................................................................................................ 12 

11B12. Connection to relay contacts .............................................................................................. 12 

12B13. Connection to Repeater panels ........................................................................................... 12 

13B14. Connection to Ancillary boards ........................................................................................... 13 

14B15. Connection to 8 way Sounder boards ................................................................................. 13 

15B16. Panel operation ................................................................................................................. 14 

16B17. Configuration options ........................................................................................................ 15 

17B18. Watchdog reset switch ...................................................................................................... 18 

1819. Processor reset switch ....................................................................................................... 18 

19B20. Internal indications – troubleshooting ................................................................................. 18 

39B20.1 Mains fail ................................................................................................................................ 18

 

40B20.2 Batt fail ................................................................................................................................... 18

 

41B20.3 CPU fault ................................................................................................................................ 18

 

42B20.4 Aux 24V fault .......................................................................................................................... 18

 

43B20.5 Batt low .................................................................................................................................. 18

 

44B20.6 Earth fault ............................................................................................................................... 18

 

45B20.7 Sys fuse fault .......................................................................................................................... 19

 

46B20.8 S1 fault and S2 fault ................................................................................................................ 19

 

47B20.9 Comms fault ............................................................................................................................ 19

 

20B21. Power supply .................................................................................................................... 19 

1B22. Maintenance ..................................................................................................................... 20 

22B23. Zone designation label ....................................................................................................... 20 

23B24. Record of Configuration ..................................................................................................... 21 

Man-1078_Sigma_CP_20

Page 2 of 22

1. Introduction

The SIGMA CP range consists of a series of conventional fire alarm control panels designed in accordance with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating

Equipment.

The range consists of 2, 4 and 8 zone control panels. All control panels are available in two versions:

Sigma K11 range in which detectors and call points are wired on separate circuits to sounders (two sounder circuits are provided).

Sigma T11 range in which detectors, call points and sounders are wired to the same pair of cables. This is what is commonly referred to as a two-wire system.

Wiring sounders to the detection circuits eliminates the need to install sounder circuit cables and also offers the ability to provide zoned or two stage sounder operation.

All control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of EN54-4.

In addition to the requirements of EN54-2 the control panel has the following facilities:

………….

Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2

Section 10 option with requirements.

………….

Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated. EN54-2 Section 7.11 option with requirements.

………….

Fire alarm devices to enable an audible warning to be sounded throughout a premises upon the detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with requirements.

In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire which operate upon fire condition. These are to be used for local control and signalling.

2. Safety and mounting

Suppliers of articles for use at work are required under section 6 of the Health and Safety at Work act 1974 to ensure as reasonably as is practical that the article will be safe and without risk to health when properly used.

An article is not regarded as properly used if it is used ‘without regard to any relevant information or advice’ relating to its use made available by the supplier.

This product should be installed, commissioned and maintained by trained service personnel in accordance with the following:

(i) IEE regulations for electrical equipment in buildings

(iii)

Statutory requirements

(iv)

Any instructions specifically advised by the manufacturer

According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that you make any appropriate information about this product available to anyone concerned with its use.

This equipment is designed to be operated from 230V 50Hz mains supplies and is of class 1 construction. As such it must be connected to a protective earthing conductor in the fixed wiring of the installation and a readily accessible double pole disconnect device meeting the requirements of EN60950/IEC950 which disconnects live and neutral simultaneously shall be incorporated in the fixed wiring.

Switch disconnect devices such as MK Sentry 63A or similar are suitable for this.

Failure to ensure that all conductive accessible parts of this equipment are adequately bonded to the protective earth will render the equipment unsafe.

This control panel is designed for indoor use only and at temperatures between -5

0

2) and with a maximum relative humidity of 95%.

C (+/- 3) and +40

0

C (+/-

The IP rating for the enclosure is IP30.

Operation outside of these limits may render the equipment unsafe.

Man-1078_Sigma_CP_20

Page 3 of 22

Mounting

The control panel should be mounted on a dry, flat surface, at eye height to the display and in a level position such that the enclosure is not distorted.

Screws or bolts of a minimum of 5mm diameter must be used to mount the enclosure in all three mounting positions.

It should be positioned in an accessible position as agreed with the end user.

Suitable fixings should be used at all fixing points such that the control panel is securely mounted and is not liable to move once fixed.

The control panel should not be mounted in another enclosure or near sources of excessive heat.

Cables should be connected using suitable cable glands fitted to the knockouts provided. If additional cable entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel.

3. Technical specification

Table 1 - Electrical specifications

Mains supply

Mains supply fuse

Power supply rating

Maximum ripple current

Output voltage

230V AC +10% - 15% (100 Watts maximum)

1.6Amp (F1.6A L250V)

3 Amps total including battery charge 28V +/ 2V

1.5 Volts

18.5 to 29V DC +/- 2%

Imax a

Imax b

400 milliamps

2.3 Amps

Imin 0.065A

Battery type (Yuasa NP)

Battery charge voltage

Battery charge current

Battery lead fuse

Battery high impedance warning

(Rimax)

Low battery voltage indication

Two 12 Volt sealed lead acid (7Ah maximum)

27.6VDC nominal (temperature compensated)

0.7A maximum

20mm, 3.15A glass

1.35 ohms max

Low battery shut off voltage

Maximum current draw from batteries

R0V output

Dedicated sounder outputs

Zonal sounder outputs

Fault relay contact rating

Fire relay contact rating

Local fire relay contact rating

21V +/- 2%

18.5V +/- 2%

3 Amps

Fused at with electronic fuse

24V Fused at 500mA with electronic fuse

24V Fused at 500mA with electronic fuse

30VDC 1A Amp maximum for each

30VDC 1A Amp maximum for each

30VDC 1A Amp maximum for each

1.6mA maximum

0.5mm

2

to 2.5mm

2 solid or stranded wire

Zone quiescent current

Terminal capacity

Number of detectors per zone

Number of sounders per circuit

Detection circuit end of line

Sounder circuit end of line

No. of detection circuits

No. of sounder outputs

SIL, AL, FLT, RST inputs

Zone normal threshold

> 20

Dependent on type and current consumption

6K8 5% ½ Watt resistor

10K 5% ¼ Watt resistor

(see table 2 for number of zones for each model)

2 (plus one per zone on T models)

Switched -ve, max resistance 100 Ohms

8K ohm TO 1K ohm

Detector alarm threshold

Call point alarm threshold

Short circuit threshold

Head removal condition

Cabling

999 ohms to 400 ohms

399 ohms to 100 ohms

99 ohms to 0 ohms

15.5 to 17.5 volts

FP200 or equivalent (maximum capacitance 1uF maximum inductance 1 millihenry)

Table 2 - Standby battery capacity required for fully loaded system

Panel model 24 hours standby

K11020 (2 Zones) 3Ah

48 hours standby 72 hours standby

4.6Ah 6.2Ah

K11040 (4 Zones) 3.3Ah

K11080 (8 Zones) 3.75Ah

T11020 (2 Zones) 3Ah

T11040 (4 Zones) 3.3Ah

T11080 (8 Zones) 3.75Ah

4.6Ah

5.1Ah

6.2Ah

6.9Ah

Standby current Max panel alarm current

0.065 0.10A

0.065

0.075

Replace only with similar type

See table 2 for capacities

See table 3

Replace only with the same type

With main power source disconnected

1.6 Amp total load over all circuits

1.6 Amp total load over all circuits

Maximum ratings not to be exceeded

Maximum ratings not to be exceeded

Maximum ratings not to be exceeded

See table 4 for detector types

Dependent on type

See table 6 for sounder types

Supplied in terminals

Supplied in terminals

Dependent on model

Zener clamp detector base to be used

Metal cable glands must be used

0.15A

0.30A

Man-1078_Sigma_CP_20

Page 4 of 22

10

20

30

40

Table 3 - Battery charge voltage versus temperature

Temperature

0

C

0

Battery charge voltage

29.2

28.56

27.99

27.55

27.13

Table 4 - Compatible detectors

Model Type Manufacturer Maximum Number per zone

55000-200/210 - SERIES 60

55000-300 - SERIES 60

55000-100 - SERIES 60

55000-101 - SERIES 60

55000-102 - SERIES 60

55000-103 - SERIES 60

55000-104 - SERIES 60

55000-215 –

SERIES 65

55000-216 -

SERIES 65

55000-217 SERIES 65

55000-218 -

SERIES 65

55000-219 -

SERIES 65

55000-220 -

SERIES 65

55000-315 -

SERIES 65

55000-316 SERIES 65

55000-317 -

SERIES 65

55000-120 -

SERIES 65

55000-121 SERIES 65

55000-122 -

SERIES 65

53541-151 – SERIES 30

53541-152 – SERIES 30

53551-101 – SERIES 30

53531-221 – SERIES 30

53531-211 - SERIES 30

53531-212 - SERIES 30

53531-213 - SERIES 30

53531-214 - SERIES 30

IONISATION

OPTICAL

HEAT

Apollo

Apollo

Apollo

HEAT

HEAT

HEAT

HEAT

Apollo

Apollo

Apollo

Apollo

IONISATION Apollo

IONISATION Apollo

IONISATION Apollo

IONISATION Apollo

IONISATION Apollo

IONISATION Apollo

OPTICAL Apollo

OPTICAL

OPTICAL

Apollo

Apollo

HEAT

HEAT

IONISATION

IONISATION

OPTICAL

HEAT

HEAT

HEAT

HEAT

HEAT

Apollo

Apollo

Apollo

Apollo

Apollo

Apollo

Apollo

Apollo

Apollo

Apollo

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

32

8

5

32

32

32

32

32

28

28

28

28

28

AS200 OPT/HEAT 22

AS300 HIGH TEMP HEAT Argus Vega 26

AS400 RATE OF RISE HEAT Argus Vega 26

NID-48F IONISATION 32

ECO1002 HEAT/PHOTO 21

Although the current consumption of many detection devices would allow more than 32 to be connected to a zone, this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and/or call points as required by

European standard EN54-2.

No more than 32 detectors and call points should be fitted to any one zone.

Man-1078_Sigma_CP_20

Page 5 of 22

Table 5 - Compatible detector bases and call points

Model Type

YBN-R/4 STANDARD

YBO-R/5 STANDARD WITH REMOTE LED

YBO-R/5SK DIODE BASE WITH REMOTE LED

YBO-R/5PA SAVWIRE

ECO1000R STANDARD

ECO1000BRSD DIODE BASE

Hochiki

Hochiki

Hochiki

Hochiki

Hochiki

Must be used with LCMU*

Must be used with LCMU*

Only with T series panels

AUBDR100-470

AUBSR100-470

MCP1BR

WR2012

470R RESISTOR + DIODE

470R RESISTOR

470R RESISTOR + DIODE

470 + 680 OHM CALL POINT

MCP1AR 470R

CX 470 OHM CALL POINT

ELECTRONICS FREE BASES

System Sensor

Apollo

Apollo

Apollo

Argus Vega

Argus Vega

Must be used with LCMU*

Must be used with LCMU*

Only with T Series Panels

Must be used with LCMU*

KAC

KAC

KC

Fulleon

For 2-wire systems

Use with both resistors intact for call point discrimination

For standard, 4-wire systems

Nittan

ALL

Note: LCMU (Line Continuity Monitoring Device) part number K1406 allows call points mounted downline of detectors that have been removed from diode bases to continue to operate.

*LCMU units are not compatible with 2 wire “T” series Sigma CP Panels.

Table 6 - Compatible sounders

Model Type

BANSHEE ELECTRONIC

WAFER ELECTRONIC

FIRECRYER RANGE ELECTRONIC VOICE

KOBELL MOTORISED

ASKARI ELECTRONIC

ROSHNI ELECTRONIC

SQUASHNI ELECTRONIC

SYMPHONI ELECTRONIC

ELECTRONIC BELL ELECTRONIC

CFB BELLS

B6 AND B8 BELLS

MOTORISED

SOLENOID

VIMPEX

VIMPEX

VIMPEX

VIMPEX

FULLEON

FULLEON

FULLEON

Standard polarised type only

Standard polarised type only

Standard polarised type only

Table 7 - Compatible I.S. barriers

Model Type

MTL5561

MTL7778ac

DETECTION ZONE GALVANIC ISOLATOR

SOUNDER CIRCUITS SI AND S2 ONLY

Note: Use galvanic isolator with Hochiki or Apollo detectors only.

Manufac turer

MTL

MTL

Man-1078_Sigma_CP_20

Page 6 of 22

4. Using intrinsically safe barriers

SIGMA CP control panels support the use of I.S. barriers for connecting to equipment in hazardous areas.

Only certified detectors, call points and sounders may be used in hazardous areas and these must be connected to the control panel via a compatible I.S. barrier as listed in table 7.

Connection of the I.S. barrier changes the characteristics of the detection circuit so zones that have I.S. barriers connected must be adjusted to work with them.

Programmable options C61 to C68 allow each zone to operate with I.S. barriers.

The amount of detectors and call points that can be connected to a zone is limited by the I.S. approval system diagram which should be supplied by the detector manufacturer. The power rating of the end of line resistor will be dependent upon the Zone classification rating (Gas class) this will be specified on the system diagram.

Figure 1. Detection zone wiring through an

MTL5561

I.S .barrier

Figure 2. Sounder circuit wiring through an MTL7778ac I.S. barrier

Man-1078_Sigma_CP_20

Page 7 of 22

5. Control panel fascia

In addition to the mandatory controls and indications required by the EN54-2 standard, two, seven segment,

LED displays and MODE, SELECT and ENTER buttons are provided to allow easy entry and storage of codes to configure the control panel to suit the requirements of the installation.

Removing the fascia

Before the fascia can be removed it will be necessary to unplug the three way terminal block on the left hand side of the PCB.

The fascia of the control panel is held in place by countersunk screws. Undo the two screws and lift the fascia gently away from the box towards you.

With the fascia removed there is much more room inside the panel for making off and dressing cables.

When cabling work is complete the fascia can be re-fitted with the two countersunk screws and the red, green/yellow and black wires re-connected to the three way terminal block.

It is most important that the polarity of the red and black wires is observed as wrong connection of these will damage the control panel.

Man-1078_Sigma_CP_20

Page 8 of 22

6. Connecting to the circuit board

All connections for field wiring are to a single row of terminals along the top of the circuit board.

The connections for the power cables are to a pluggable terminal block which may be pulled off of the board to remove the plate/PCB assembly. Remove this pluggable terminal only with mains power off.

Shielded fire alarm cable such as FP200 and metal cable glands must be used for all connections to the panel.

The resistance of any core of any cable must not exceed 25 ohms. The shield of the cable must be bonded securely to the enclosure via a metal gland.

Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving only enough wire to ensure that there is no strain on the PCB.

Terminals are capable of accepting wires of up to 2.5mm

2

.

Terminal designations

Wiring must not go across the front of the circuit board plate or between the plate and the circuit board.

If cable entries need to be in positions other than at the knockouts provided, wiring must be fed behind and well away from the surface of the circuit board.

The space at the bottom of the enclosure is largely occupied by the standby batteries so this must be borne in mind when considering cable entries.

CORRECT

INCORRECT INCORRECT

7. Software revision number

X1

C 7 C6 C 5 C 4 C 3 C 2 C 1 C 23 C 22

VDR4

VDR3

F 2

C 97 C 93

C127 C128 C 35 C 36 C 33

C 34

C 60 C 61

VDR1

F 10

X2

C 106 C 107

FB21 FB20

RL 3

RL 2

TR 23

C 51

TR 19

Z 11

D 4

D 35

C 68

+

D 3

C 75

R 13

D 34

+

C 67

D 2

D 33

C 74

R 7

+

C 66

D 1

C 73

R 1

D 32

C 65

+

D 12

IC 2

TR9 D 11

F 11

TR47

+

REG1

IC 10

C 27

J 1

Sig27. hex

IC 6

Jason

C 41

T 3

SW4

LED 17 LED 35

R 87

D 16

R 104

R 85

D 15

R 86

D 14

R 130 D 13

R 131

R 132

D 23

R 133

D 22

R 78

R 135

R 134

D 30

IC 1

+

C 82

C 24

D 9

+

D 10

TR 25 TR 28

R 126

IC 4

IC 5

C 25

Z 14

+

VR 1

D 41

L 1

C 56

SW2 SW1

SERIAL NUMBER

+

TH 1

R 75

D 1008 ISSUE 06

R 76

LED4 LED7

R 70

New features may be added to Sigma CP fire control panels from time to time and when this is done the operating software of the unit is updated. The software revision can be located on the main processor by removing the plate holding the PCB from the enclosure and turning it over. The software version will have a number such as “Sig27.hex” and it is this number which will determine which features the panel has installed and its compatibility with Sigma CP ancillary board, sounders boards, repeaters etc.

SOFTWARE VERSION LABEL

Man-1078_Sigma_CP_20

Page 9 of 22

8. Detection zone wiring

The detection zones provide a nominal 24V DC to power conventional detectors and call points as listed in the compatibility tables on pages 6 and 7.

The wiring is monitored for open and short circuit fault conditions by removing the 6K8 end of line monitoring resistors that are supplied fitted to the control panels’ terminals and placing them across the last device that is wired to the zone circuit.

Detection zone circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly.

On T series panels, polarised sounders must also be wired across the detection zone but in reverse polarity to that shown by the zone terminals (see figure 5 below). At least one sounder should be fitted to each detection zone. Each zone can be configured individually as a 2-wire type zone or a non 2-wire type zone using configuration options C1 to C8.

For non 2-wire systems that are required to comply with BS5839 Part 1: 2002 detector removal requirements, detector bases fitted with a Schottky diode should be used and the end of line resistor replaced with an LCMU active end of line monitoring device.

DETECTOR

+

IN

+

OUT

CALL POINT

6K8 END OF

LINE RESISTOR

-

IN

-

OUT

Figure 4. – K Series detection zone wiring

DETECTOR

POLARISED

SOUNDER

+

IN

+

OUT

_ _

IN OUT

CALL POINT

6K8 END OF

LINE RESISTOR

IN

-

OUT

IN

+ +

OUT

NOTE: SOUNDER WIRED IN

REVERSE POLARITY

USE ONLY SA-WIRE BASES

ON “T” SERIES PANELS

Figure 5. - T series detection zone wiring

Man-1078_Sigma_CP_20

Page 10 of 22

9. Sounder circuit wiring

Whether using standard or T series control panels, all sounders must be of the polarised type. If nonpolarised sounders are used the control panel will permanently show a fault condition. See table 6 on page 7 for a list of compatible sounder types.

Sounder circuits are monitored for open and short circuit faults by placing a 10K end of line monitoring resistor across the last device on the circuit.

Sounder circuits must be wired as a single, radial circuit with no spurs or T junctions to enable the monitoring circuit to work correctly.

A maximum of 1.6 Amps is available for powering sounders with a maximum load of 0.41 Amps on any one circuit.

POLARISED

SOUNDER

POLARISED

SOUNDER

+

IN

+

OUT

_ _

IN OUT

+

IN

+

OUT

_ _

IN OUT

10K end of line resistor

Figure 6 . - Sounder circuit wiring

10. Connection to remote control terminals

Some functions of the control panel can be controlled externally from the panel if required. Operation of these inputs must be restricted by an access level 2 control as defined in EN54-2 These are abbreviated at the terminals block as follows: a) Remote 0 V supply - ROV b) Silence Alarm – SIL c) Sound Alarm – AL d) Fault – FLT e) Reset – RST

To activate these inputs, the remote 0 Volt (R0V) supply must be connected to the input via a normally open switch or contact and via a resistance of no greater than 100 ohms.

All of the remote control inputs are non-latching.

Man-1078_Sigma_CP_20

Page 11 of 22

11. Aux 24V DC supply

An auxiliary 24V DC supply is provided to enable local signalling or control of ancillary systems such as door release controllers.

The terminals for the Aux 24V supply are labelled Aux 24V and ROV. The ROV terminal is the negative terminal and is the same terminal that should be used to switch the remote control terminals.

It is possible to make the ROV terminal pulsing so that by connecting it to the AL terminal via a remote, volt free contact, it can be used to pulse the dedicated sounder circuits in response to a signal from another system for example to give an alert. See programming code 24.

The supply is fitted with an electronic self resetting fuse to protect the control panel’s 24V supply in the event of a wiring fault.

Any standing load on the Aux 24V supply must be taken into account when calculating battery standby times as standby time will be significantly affected by even modest standing loads. It is recommended that the

Aux24V output is not used to power standing loads and not used to supply loads of greater than 300 milliamps

Where the Aux 24V supply is used to power electromechanical devices such as relays or door retainers it is imperative that a suppression diode is fitted across the coil of the electromechanical device to prevent the generation of high voltage transients back to the control panels power supply.

The Aux 24V DC Supply is not suitable for powering Sigma CP sounder boards, a separate power supply should be used for these.

12. Connection to relay contacts

Volt free changeover relay contacts are provided for local control and signalling if required. These contacts are rated for switching signalling circuits only and the maximum ratings listed in table 1 on page 5 should not be exceeded under any circumstances.

Fault relay

The fault relay is normally energised and will de-energise upon any fault condition including total loss of power.

Local fire relay

The local fire relay will energise upon activation of a fire condition on any of the zones or pressing of the sound alarm button on the front panel. The relay will remain activated until the alarm is silenced or the panel is reset. This relay will not operate upon activation of the remote AL input or when a fire condition is triggered on a zone that is in test mode.

Fire relay

The fire relay will energise upon activation of a fire condition on any of the zones. The relay will remain activated until the control panel is reset. This relay will

NOT operate upon activation of the remote AL input.

Individual zones can be configured not to operate the Fire relay by setting configuration options E1 to E8.

13. Connection to Repeater panels

Repeater panels connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel PCB. Up to 7 repeaters may be connected and each repeater has terminals for the incoming cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.

Set the repeater address using the DIP switch (SW7); ensure no two repeaters share the same address.

Apply power to main panel first and then all repeater panels. Turn on the Enable Control keyswitch and set the Write Enable switch to on then briefly press the PROCESSOR RESET button on the main panel. Wait for a few seconds and the main panel will show the addresses of the repeaters that were found on the display for instance r1 indicates that a repeater at address 1 has been found.

Turn the write enable switch of, then on again and then press the ENTER button to accept each repeater that has been found. When all repeaters have been added, set the main panel Write Enable switch to off.

Press the Watchdog reset switch on the main panel.

All repeaters are now configured and the main control panel will report a fault if any repeaters that have been accepted become faulty or go off line.

For full details of commissioning procedures for repeaters see the Sigma CP Repeater Operation and maintenance manual.

Please note that repeaters can only be fitted to panels containing boards labeled

S4XXA or above. They will not work with panels containing boards without an alpha suffix.

Man-1078_Sigma_CP_20

Page 12 of 22

For panels with software version Sigma242.hex or below, the Enable controls keyswitch and Write Enable switch must both be set to off.

14. Connection to Ancillary boards

Ancillary boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel PCB. Up to 7 Ancillary boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last ancillary board, sounder board or repeater panel connected to the cable must have the jumper links J2 removed.

Set the ancillary board address using the DIP switch (SW2); ensure no two ancillary boards share the same address.

Apply power to main panel and all ancillary boards then turn on the enable keyswitch and set the write enable slide switch to on, briefly press the PROCESSOR RESET button on the main panel, wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance o1 indicates that an ancillary board at address 1 has been found.

Press the ENTER button to accept each ancillary board that has been found.

The control panel will report a fault if any ancillary boards that have been accepted become faulty or go off line.

For full details of commissioning procedures for ancillary boards see the Sigma CP Ancillary board Operation and maintenance manual.

Please note that Ancillary boards can only be fitted to panels containing boards labelled S4XXA or above. They will not work with panels containing boards without an alpha suffix.

15. Connection to 8 way Sounder boards

Sounder boards connect via a 2 core cable to the terminals marked RS485 + and – on the Sigma CP main control panel PCB. Up to 7 Sounder boards may be connected and each board has terminals for the incoming cables and outgoing cables. All except the last Ancillary board, Sounder board or Repeater connected to the cable must have the jumper links J2 removed. Sounder boards must be powered from a separate power supply which is suitably rated to supply the full sounder load that is connected. This can be up to 4 Amps if all circuits are fully loaded.

Set the Sounder board address using the DIP switch (SW2); ensure no two Sounder boards share the same address.

Apply power to main panel and all Sounder boards then turn on the enable keyswitch and set the write enable slide switch to on, briefly press the PROCESSOR RESET button on the main panel, wait for a few seconds and the main panel will show the addresses of the sounder boards that were found on the display for instance b1 indicates that a sounder board at address 1 has been found.

Press the ENTER button to accept each Sounder board that has been found.

The control panel will report a sounder fault if any Sounder boards that have been accepted become faulty, have cable faults on their outputs or go off line.

For full details of commissioning procedures for Sounder boards see the Sigma CP Sounder board Operation and maintenance manual.

Please note that Sounder boards can only be fitted to panels containing software

SIGMA242.HEX or later.

Man-1078_Sigma_CP_20

Page 13 of 22

16. Panel operation

16.1 Normal condition

Under normal conditions, control panels will have only the green,

Power On LED lit.

16.2 Fire condition

Upon receipt of a fire condition by activation of a detector or call point, the

Common Fire indicator will light and the zonal

Fire indicators will flash at around 2Hz.

The fire and local fire relays will also operate and signal any systems to which they are connected.

Any sounders connected to the sounder circuits will operate in common, zonal or 2-stage mode as selected by configuration options 10 to 12 (see table 8).

16.3 Silence/sound alarms

The

Silence/Sound alarm button can only be operated at access level two which means that the Enable

Control key must be inserted.

To silence the sounders, insert the Enable Control key and press the Silence/Sound alarm button.

When the sounders have been silenced, the Zone Fire LEDs will change from flashing to a steady state.

Pressing the Silence/Sound alarm whilst the control panel is in this silenced condition, will cause the sounders to operate again.

The sounders can be toggled on and off with the

Silence/Sound alarm button as required.

16.4 Reset

To reset the panel, insert the Enable key then press the Reset button.

16.5 Zone fault

Removal of a detector from its base or a fault on any of the zone wiring will cause the

Fault LED and Zone

Fault LEDs to light indicating the zone in which the fault has occurred.

16.6 Sounder fault

A fault on the wiring to sounder circuits will cause the

Fault and Sounder Fault LEDs to light indicating a fault on the wiring to the sounder circuits.

16.7 Power fault

Failure of the mains power, disconnection of the standby battery or high impedance in the charging circuit will cause the

Fault and Power Fault LEDs to light indicating an abnormality in the power supply to the control panel.

16.8 System fault

The System Fault LED will light if the configuration memory has not been set or has become corrupt.

16.9 Lamp test

All LED indicators can be tested at any time by pressing the

Lamp Test button. The Enable Control key does not need to be inserted to test the indicators.

The buzzer can be silenced at any time by pressing the

Buzzer Silence button. The enable key does not need to be inserted to silence the buzzer.

16.10 Disablements

It is possible to disable parts of the system. This may be required if there are works going on in a building which may cause the fire alarm system to operate in error.

16.10.1 Disable zones

To disable zones, the

Enable Control key should be inserted and the mode button pressed until “d” appears in the first of the two seven segment LED displays. The

Select button should then be pressed to select the number of the zone which is to be disabled in the second of the two seven segment displays. Once the desired zone is displayed, the enter button should be pressed to confirm the disablement.

The

Disable LED will light and the Zone Fault LED will light for each disabled zone.

A disabled zone is shown on the seven segment display as ‘dx.’ (where x is the zone number from 1-8).

If the ‘x’ is flashing, it means that there are activated devices in that zone and re-enabling it will put the control panel into the fire condition.

The panel should be Reset before enabling any zone with a flashing “dx.” Indication

Man-1078_Sigma_CP_20

Page 14 of 22

Note: The flashing “dx” indicator will only appear on panels with software version sigma_CP 214.hex and higher produced after July 2012.

16.10.2 Disable sounders

To disable sounder outputs, press the mode button to select “db” on the seven segment display. Pressing enter will disable all sounders and cause the

Disable and Sounder Fault LEDs to light.

16.10.3 Activate delays

To activate delays on zones as set in configuration options 31 to 48, press the mode button until Ad appears on the seven segment LED display. When the enter button is pressed any zones that are set as delayed will have their alarm outputs delayed by the time set in configuration options 00 to 09.

16.10.4 Disable fault contact

The fault relay can be disabled by selecting configuration option 22.

16.11 Test mode

Fire alarm systems must be tested regularly to ensure that they are functioning correctly. The Sigma CP range of panels enable the system to be tested single handed by using a test mode. When in test mode, activation of a fire alarm will be automatically reset after a few seconds to eliminate the need to return to the control panel to reset after every activation.

Test mode is entered in a similar way to disablements. With the Enable Control key inserted, press the Mode button until “t” appears in the first of the seven segment displays. Then press the

Select button until the required zone number appears. Pressing the

Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode.

Disablements and zone tests are cleared by repeating the sequence that is used to select them, i.e. the "db" function (for example) toggles between sounders disabled and sounders enabled.

17. Configuration options

The Sigma CP range of control panels has many configuration options which can be set at the time of commissioning to suit the requirements of the installation. These options are normally set once and will rarely need to change. The configuration options are only available at access level 3. To access level 3,

CAREFULLY slide the Write Enable switch (located behind the aperture in the panel plate) to the right position using a small screwdriver or similar. When the panel is at access level 3, the buzzer will “pip” three times every few seconds as an indication that it is at this access level.

Figure 8 – Access level 3 (Write enable) enable switch location

Configuration options are simple to enter using the codes in table 8 below. When the control panel is at access level 3, the sub-text of the

Mode and Select buttons is used to enter a number using tens (+10) and units (+1).

When the required code number is displayed, pressing the enter button will cause the dot on the units, seven segment display to flash. This indicates that a configuration option has been set.

To review which configuration options have been set previously, simply scroll through numbers 1 to 99, A1 to A8, C1 to C8 and E1 to E8 and those with a flashing dot indicate which options have been set.

Man-1078_Sigma_CP_20

Page 15 of 22

05

06

07

08

01

02

03

04

09

10

11

Figure 9 – Example display showing option set and not set.

Table 8 – Configuration codes

CODE

00

FUNCTION

SOUNDER DELAY TIME = 30 SECONDS

SOUNDER DELAY TIME = 1 MINUTE

SOUNDER DELAY TIME = 2 MINUTES

SOUNDER DELAY TIME = 3 MINUTES

SOUNDER DELAY TIME = 4 MINUTES

SOUNDER DELAY TIME = 5 MINUTES

SOUNDER DELAY TIME = 6 MINUTES

SOUNDER DELAY TIME = 7 MINUTES

SOUNDER DELAY TIME = 8 MINUTES

SOUNDER DELAY TIME = 9 MINUTES

COMMON ALARM MODE (default)

TWO-STAGE ALARM MODE

COMMENTS

Sets the time delay before sounders operate in combination with configuration codes 31 to 48 and access level 2 function AD.

All sounders operate upon any fire condition

Continuous sounders in activated zone, pulsing elsewhere

21* DISABLE FIRE BUZZER

22* DISABLE FAULT OUTPUT

23

24

DISABLE EARTH FAULT MONITORING

PULSED REMOTE CONTROL OUTPUT

25 ENABLE SOUNDERS ON DETECTION CIRCUITS

26 DISABLE FIRE OUTPUT

27 REMOVE AUX 24 UPON PANEL RESET

28 INDICATE CALL POINT ACTIVATION

29

2A

DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE

TREAT CALL POINT ALARM AS DETECTOR ALARM

52

53

54

55

47

48

51

56

57

58

42

43

44

45

46

37

38

41

31

32

33

34

35

36

Man-1078_Sigma_CP_20

ZONE 1 ALARM FROM DETECTOR DELAYED

ZONE 2 ALARM FROM DETECTOR DELAYED

ZONE 3 ALARM FROM DETECTOR DELAYED

ZONE 4 ALARM FROM DETECTOR DELAYED

ZONE 5 ALARM FROM DETECTOR DELAYED

ZONE 6 ALARM FROM DETECTOR DELAYED

ZONE 7 ALARM FROM DETECTOR DELAYED

ZONE 8 ALARM FROM DETECTOR DELAYED

ZONE 1 ALARM FROM CALL POINT DELAYED

ZONE 2 ALARM FROM CALL POINT DELAYED

ZONE 3 ALARM FROM CALL POINT DELAYED

ZONE 4 ALARM FROM CALL POINT DELAYED

ZONE 5 ALARM FROM CALL POINT DELAYED

ZONE 6 ALARM FROM CALL POINT DELAYED

ZONE 7 ALARM FROM CALL POINT DELAYED

ZONE 8 ALARM FROM CALL POINT DELAYED

COINCIDENCE ZONE 1

COINCIDENCE ZONE 2

COINCIDENCE ZONE 3

COINCIDENCE ZONE 4

COINCIDENCE ZONE 5

COINCIDENCE ZONE 6

COINCIDENCE ZONE 7

COINCIDENCE ZONE 8

Page 16 of 22

Buzzer will not operate on fire condition

Fault relay will not operate except upon total power failure

Connection of fire alarm wiring will not announce a fault

Aux 24V supply pulses 1 sec on/1 sec off

Set as default if panel is two wire “T” series (detectors and call points on same cables)

Fire relay will not operate upon any alarm

24V supply switches off for about 5 seconds when panel is reset

Activation of a call point with a 270R resistance fitted is indicated by a flashing zone indicator and “Pu” on the 7 segment display. Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display.

Silenced sounders will not re-sound upon further zone activations

When this option is active, the panel does not distinguish between detector alarms and call point alarms (v215 onward)

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by detector only.

Note: Access level 2 function Ad must be set for this to take effect.

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by call point only.

Note access level 2 function Ad must be set for this to take effect.

Zone contributes to ancillary board coincidence O/P. Any number of zones can be selected to contribute.

65

66

67

68

61

62

63

64

CONFIGURE Z1 FOR I.S BARRIER

CONFIGURE Z2 FOR I.S BARRIER

CONFIGURE Z3 FOR I.S BARRIER

CONFIGURE Z4 FOR I.S BARRIER

CONFIGURE Z5 FOR I.S BARRIER

CONFIGURE Z6 FOR I.S BARRIER

CONFIGURE Z7 FOR I.S BARRIER

CONFIGURE Z8 FOR I.S BARRIER

CODE FUNCTION

71* ZONE 1 SHORT CIRCUIT INDICATES ALARM

72* ZONE 2 SHORT CIRCUIT INDICATES ALARM

73* ZONE 3 SHORT CIRCUIT INDICATES ALARM

74* ZONE 4 SHORT CIRCUIT INDICATES ALARM

75* ZONE 5 SHORT CIRCUIT INDICATES ALARM

76* ZONE 6 SHORT CIRCUIT INDICATES ALARM

77* ZONE 7 SHORT CIRCUIT INDICATES ALARM

78* ZONE 8 SHORT CIRCUIT INDICATES ALARM

81* ZONE 1 NON-LATCHING

82* ZONE 2 NON-LATCHING

83* ZONE 3 NON-LATCHING

84* ZONE 4 NON-LATCHING

85* ZONE 5 NON-LATCHING

86* ZONE 6 NON-LATCHING

87* ZONE 7 NON-LATCHING

88* ZONE 8 NON-LATCHING

Detection threshold changed for use with IS barrier

COMMENTS

Changes the trigger threshold of the zone so that the control panel can be used on older systems that had no short circuit monitoring.

Renders the zone self-resetting so that it can be used to receive signals from other systems and will reset when the input is removed.

Note: It can take up to 20 seconds for zone to reset itself when sounders are operating

91 ZONE 1 DOES NOT SOUND ALARMS

92 ZONE 2 DOES NOT SOUND ALARMS

93

94

95

96

97

98

ZONE 3 DOES NOT SOUND ALARMS

ZONE 4 DOES NOT SOUND ALARMS

ZONE 5 DOES NOT SOUND ALARMS

ZONE 6 DOES NOT SOUND ALARMS

ZONE 7 DOES NOT SOUND ALARMS

ZONE 8 DOES NOT SOUND ALARMS

A1* ZONE 1 ANY ALARM DELAYED

A2* ZONE 2 ANY ALARM DELAYED

Prevents the zone from operating the two common sounder outputs.

Zone needs to be triggered for 30 seconds continuously before an alarm is generated.

A3* ZONE 3 ANY ALARM DELAYED

A4* ZONE 4 ANY ALARM DELAYED

A5* ZONE 5 ANY ALARM DELAYED

A6* ZONE 6 ANY ALARM DELAYED

A7* ZONE 7 ANY ALARM DELAYED

A8* ZONE 8 ANY ALARM DELAYED

C1

C2

C3

C4

C5

C6

C7

C8

ZONE 1 SOUNDERS INHIBITED

ZONE 2 SOUNDERS INHIBITED

ZONE 3 SOUNDERS INHIBITED

ZONE 4 SOUNDERS INHIBITED

ZONE 5 SOUNDERS INHIBITED

ZONE 6 SOUNDERS INHIBITED

ZONE 7 SOUNDERS INHIBITED

ZONE 8 SOUNDERS INHIBITED

Enables individual zones to be configured not to operate zonal sounders.

On 2 wire “T” series panels this enables individual zones to be configured for use with conventional (non 2-wire) detector bases.

SOFTWARE VERSIONS SIGMA242.HEX and above only

E1* ZONE 1 WILL NOT OPERTATE FIRE RELAY

E2* ZONE 2 WILL NOT OPERTATE FIRE RELAY

E3* ZONE 3 WILL NOT OPERTATE FIRE RELAY

E4* ZONE 4 WILL NOT OPERTATE FIRE RELAY

E5* ZONE 5 WILL NOT OPERTATE FIRE RELAY

E6* ZONE 6 WILL NOT OPERTATE FIRE RELAY

E7* ZONE 7 WILL NOT OPERTATE FIRE RELAY

E8* ZONE 8 WILL NOT OPERTATE FIRE RELAY

Enables individual zones to be selected to not operate the fire relay. This is sometimes combined with the non-latching function to prevent ring around on interconnected panels.

SOFTWARE VERSIONS SIGMA242.HEX and above only

NOTE: Setting the options marked with asterisks does not comply with EN54-2

Man-1078_Sigma_CP_20

Page 17 of 22

Once the required configuration options have been set, the Write enable switch must be returned to its normal position to the right. The General fault indicator will remain lit if the Write enable switch is not turned off.

18. Watchdog reset switch

If for any reason the microprocessor in the control panel fails to carry out its operation correctly it will attempt to restart itself. This process is called a “watchdog” and the control panel must record and indicate these events.

If a watchdog event occurs, the control panel will show the FAULT and SYSTEM FAULT LEDs on the front panel, the CPU fault LED inside the panel.

This fault can only be cleared by pressing the WATCHDOG RESET button on the PCB inside the control panel. The control panel buzzer can not be silenced and will continue to sound until the watchdog activation is reset.

19. Processor reset switch

Once started, the microprocessor controlling the panel should continue to run continuously without interruption. If the microprocessor fails to run correctly it can be reset by pressing the PROCESSOR RESET button on the PCB inside the control panel.

This should not normally be necessary but should be done as a matter of course if the system is behaving abnormally. The system should resume normal operation within a couple of seconds of pressing the processor reset button.

20. Internal indications – troubleshooting

To assist in identifying fault conditions which are not detailed on the front of the control panel, a number of internal indicators are visible with the front cover removed as follows:

20.1 Mains fail

Indicates that the 230V AC supply is not present and the system is running on standby batteries.

If there is not a power cut, check the panels mains fuse.

20.2 Batt fail

Indicates that the standby battery has become disconnected or that the charging circuit of the control panel has a high resistance or has failed. Check that both batteries are connected and linked together. Test battery. Disconnect battery and ensure that 28 Volts can be measured on battery charger leads.

20.3 CPU fault

Indicates that the central processor unit has failed to correctly execute code and has been re-started by the system watchdog. The watchdog reset switch must be pressed to clear the CPU fault condition.

Press watchdog reset. If system does not return to normal then the panel is probably damaged and needs the circuit board replacing. (See maintenance section).

20.4 Aux 24V fault

The Aux 24V and R0V terminals provide a 500 milliamp, 24V DC power supply for power fire alarm ancillary equipment. This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded. The fuse is a self resetting type and the supply will resume when the fault condition is removed.

20.5 Batt low

Illuminates when the system is running on batteries and the battery voltage is lower than 21V +/-2% (the minimum battery voltage).

20.6 Earth fault

Indicates that part of the system wiring is connected to earth. Remove all system wiring and re-connect cables one at a time until the earth fault returns. This will indicate which cable the earth fault is present on.

Man-1078_Sigma_CP_20

Page 18 of 22

20.7 Sys fuse fault

Indicates that the total power rating of the power supply has been exceeded and that the system fuse has come into operation. Remove and review all loads and re-connect one at a time until over rated circuit trips fuse to identify troublesome circuit.

20.8 S1 fault and S2 fault

Indicates a short or open circuit on sounder outputs. Remove wiring and refit end of line resistors. Check sounder circuit wiring.

20.9 Comms fault

Indicates that communication has been lost with a repeater panel or Ancillary board. Check for comms fault at all repeaters and ancillary boards to identify the source of the problem.

21. Power supply

The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the fused terminal block labelled “230V”.

The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar type.

The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum

0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse rated at 4 Amps.

The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at least 50mm.

Mains wiring should include an earth conductor which is securely bonded to the building earth and should enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short inside the enclosure and secured together close to the mains terminal block with a cable tie.

The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see table 2 for battery size required for each model).

The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps.

Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit which must only be replaced with one of the same type.

It is most important that the polarity of the batteries is carefully observed when connecting.

When the batteries are discharged to a level at which a low battery indication is given, the BATT FAIL indicator will also be lit.

Wrongly connected batteries could cause damage to the control panel.

MAINS

Figure 9

TERMINAL

KEEP MAINS WIRES AS SHORT AS POSSIBLE

AND SECURE ALL THREE WIRES CLOSE TO

THE TERMINAL BLOCK WITH A CABLE TIE

– Mains and battery connections

L

N

E

N

L

+

Man-1078_Sigma_CP_20

+ -

BLACK BATTERY

LEAD TO -

TERMINAL RED BATTERY

LEAD TO +

TERMINAL

Page 19 of 22

GREY LINK

22. Maintenance

Sigma CP control panels do not require any specific maintenance but should the control panel become dirty it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Detergents or solvents should not be used to clean the panel and care must be taken that water does not enter the enclosure.

The control panel contains sealed lead acid batteries to provide standby power in the event of a mains failure.

These batteries have a life expectancy of around 4 years. It is recommended that these batteries be tested in accordance with the battery manufacturer’s recommendations annually to determine their suitability for continued standby applications.

Routine testing of the fire alarm system in accordance with BS5839: Part 1: 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately.

Should the control panel become faulty the complete electronic assembly can be replaced.

To do this, any configured options should be noted then both mains and battery power should be removed before the work is started.

The field wiring should be carefully labelled and removed from the terminals.

The PCB can now be taken out of the panel by removing the 2 holding the plate in position.

Fitting the new PCB is the reverse of the procedure for removing the board.

23. Zone designation label

All Sigma CP control panels are supplied with a zone designation label onto which zone designations can be written.

This enables each zone to be given a text description allowing easier identification of any zones showing an abnormal condition.

Man-1078_Sigma_CP_20

Page 20 of 22

24. Record of Configuration

26

27

28

29 DO NOT RE-SOUND ALARMS FROM ANOTHER

ZONE

2A TREAT CALL POINT ALARM AS DETECTOR ALARM

62

63

64

65

66

67

68

56

57

58

61

52

53

54

55

46

47

48

51

41

42

43

44

45

35

36

37

38

31

32

33

34

Use the table below to record the configuration codes that have been set on the control panel for future reference. Place a tick in the grey band for any configuration options that are set.

It is recommended that a copy of this table is left with the control panel under the supervision of the person responsible for the fire detection system.

CODE

00

01

02

03

04

05

FUNCTION

SOUNDER DELAY TIME = 30 SECONDS

SOUNDER DELAY TIME = 1 MINUTE

SOUNDER DELAY TIME = 2 MINUTES

SOUNDER DELAY TIME = 3 MINUTES

SOUNDER DELAY TIME = 4 MINUTES

SOUNDER DELAY TIME = 5 MINUTES

COMMENTS

Sets the time delay before sounders operate in combination with configuration codes 31 to 48 and access level 2 function AD.

SET

06

07

08

09

10

11

SOUNDER DELAY TIME = 6 MINUTES

SOUNDER DELAY TIME = 7 MINUTES

SOUNDER DELAY TIME = 8 MINUTES

SOUNDER DELAY TIME = 9 MINUTES

COMMON ALARM MODE

TWO-STAGE ALARM MODE

21* DISABLE FIRE BUZZER

22* DISABLE FAULT OUTPUT

23 DISABLE EARTH FAULT MONITORING

24

25

PULSED REMOTE CONTROL OUTPUT

ENABLE SOUNDERS ON DETECTION CIRCUITS

DISABLE FIRE OUTPUT

REMOVE AUX 24 UPON PANEL RESET

INDICATE CALL POINT ACTIVATION

ZONE 1 ALARM FROM DETECTOR DELAYED

ZONE 2 ALARM FROM DETECTOR DELAYED

ZONE 3 ALARM FROM DETECTOR DELAYED

ZONE 4 ALARM FROM DETECTOR DELAYED

ZONE 5 ALARM FROM DETECTOR DELAYED

ZONE 6 ALARM FROM DETECTOR DELAYED

ZONE 7 ALARM FROM DETECTOR DELAYED

ZONE 8 ALARM FROM DETECTOR DELAYED

ZONE 1 ALARM FROM CALL POINT DELAYED

ZONE 2 ALARM FROM CALL POINT DELAYED

ZONE 3 ALARM FROM CALL POINT DELAYED

ZONE 4 ALARM FROM CALL POINT DELAYED

ZONE 5 ALARM FROM CALL POINT DELAYED

ZONE 6 ALARM FROM CALL POINT DELAYED

ZONE 7 ALARM FROM CALL POINT DELAYED

ZONE 8 ALARM FROM CALL POINT DELAYED

COINCIDENCE ZONE 1

COINCIDENCE ZONE 2

COINCIDENCE ZONE 3

COINCIDENCE ZONE 4

COINCIDENCE ZONE 5

COINCIDENCE ZONE 6

COINCIDENCE ZONE 7

COINCIDENCE ZONE 8

CONFIGURE Z1 FOR I.S BARRIER

CONFIGURE Z2 FOR I.S BARRIER

CONFIGURE Z3 FOR I.S BARRIER

CONFIGURE Z4 FOR I.S BARRIER

CONFIGURE Z5 FOR I.S BARRIER

CONFIGURE Z6 FOR I.S BARRIER

CONFIGURE Z7 FOR I.S BARRIER

CONFIGURE Z8 FOR I.S BARRIER

All sounders operate upon any fire condition

Continuous sounders in activated zone, pulsing elsewhere

Buzzer will not operate on fire condition

Fault relay will not operate except upon total power failure

Connection of fire alarm wiring will not announce a fault

Aux 24V supply pulses 1 sec on/1 sec off

Set as default if panel is two wire “T” series (detectors and call points on same cables)

Fire relay will not operate upon any alarm

24V supply switches off for about 5 seconds when panel is reset

Activation of a call point with a 270R resistance fitted is indicated by a flashing zone indicator and “Pu” on the 7 segment display.

Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display

Silenced sounders will not re-sound upon further zone activations

When this option is active, the panel does not distinguish between detector alarms and call point alarms (v215 onward)

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by detector only.

Note access level 2 function Ad must be set for this to take effect.

Sounder outputs will be delayed by time set at options

0-9 when selected zone(s) triggered by call point only.

Note access level 2 function Ad must be set for this to take effect.

Zone contributes to ancillary board coincidence O/P. Any number of zones can be selected to contribute.

Detection threshold changed for use with IS barrier

Man-1078_Sigma_CP_20

Page 21 of 22

CODE FUNCTION

71* ZONE 1 SHORT CIRCUIT INDICATES ALARM

72* ZONE 2 SHORT CIRCUIT INDICATES ALARM

73* ZONE 3 SHORT CIRCUIT INDICATES ALARM

74* ZONE 4 SHORT CIRCUIT INDICATES ALARM

75* ZONE 5 SHORT CIRCUIT INDICATES ALARM

76* ZONE 6 SHORT CIRCUIT INDICATES ALARM

77* ZONE 7 SHORT CIRCUIT INDICATES ALARM

78* ZONE 8 SHORT CIRCUIT INDICATES ALARM

81* ZONE 1 NON-LATCHING

82* ZONE 2 NON-LATCHING

83* ZONE 3 NON-LATCHING

84* ZONE 4 NON-LATCHING

85* ZONE 5 NON-LATCHING

86* ZONE 6 NON-LATCHING

COMMENTS

Changes the trigger threshold of the zone so that the control panel can be used on older systems that had no short circuit monitoring.

Renders the zone self-resetting so that it can be used to receive signals from other systems and will reset when the input is removed.

Note: It can take up to 20 seconds for zone to reset itself when sounders are operating

87* ZONE 7 NON-LATCHING

88* ZONE 8 NON-LATCHING

91 ZONE 1 DOES NOT SOUND ALARMS

92 ZONE 2 DOES NOT SOUND ALARMS

93

94

95

ZONE 3 DOES NOT SOUND ALARMS

ZONE 4 DOES NOT SOUND ALARMS

ZONE 5 DOES NOT SOUND ALARMS

ZONE 6 DOES NOT SOUND ALARMS 96

97

98

ZONE 7 DOES NOT SOUND ALARMS

ZONE 8 DOES NOT SOUND ALARMS

99

A1* ZONE 1 ANY ALARM DELAYED

Prevents the zone from operating the two common sounder outputs

Zone needs to be triggered for 30 seconds continuously before an alarm is generated.

A2* ZONE 2 ANY ALARM DELAYED

A3* ZONE 3 ANY ALARM DELAYED

A4* ZONE 4 ANY ALARM DELAYED

A5* ZONE 5 ANY ALARM DELAYED

A6* ZONE 6 ANY ALARM DELAYED

A7* ZONE 7 ANY ALARM DELAYED

A8* ZONE 8 ANY ALARM DELAYED

C1

C2

C3

C4

C5

C6

C7

C8

ZONE 1 SOUNDERS INHIBITED

ZONE 2 SOUNDERS INHIBITED

ZONE 3 SOUNDERS INHIBITED

ZONE 4 SOUNDERS INHIBITED

ZONE 5 SOUNDERS INHIBITED

ZONE 6 SOUNDERS INHIBITED

ZONE 7 SOUNDERS INHIBITED

ZONE 8 SOUNDERS INHIBITED

Enables individual zones to be configured not to operate zonal sounders.

On 2 wire “T” series panels this enables individual zones to be configured for use with conventional (non-savwire) detector bases.

SOFTWARE VERSIONS SIGMA242.HEX hex and above only

E1* ZONE 1 WILL NOT OPERATE FIRE RELAY

E2* ZONE 2 WILL NOT OPERATE FIRE RELAY

E3* ZONE 3 WILL NOT OPERATE FIRE RELAY

E4* ZONE 4 WILL NOT OPERATE FIRE RELAY

E5* ZONE 5 WILL NOT OPERATE FIRE RELAY

E6* ZONE 6 WILL NOT OPERATE FIRE RELAY

E7* ZONE 7 WILL NOT OPERATE FIRE RELAY

E8* ZONE 8 WILL NOT OPERATE FIRE RELAY

Enables individual zones to be selected to not operate the fire relay. This is sometimes combined with the non-latching function to prevent ring around on interconnected panels.

SOFTWARE VERSIONS SIGMA242.HEX hex and above only

NOTE: Setting the options marked with asterisks does not comply with EN54-2

SET

Man-1078_Sigma_CP_20

Page 22 of 22

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement