Schneider Electric TSXMAP1074 Mapway module User Guide
Реклама
Реклама
Section
1 Introduction
Contents
1.1 Documentation Presentation
1.2 Module Description
1.3 Hardware Presentation
1.4 Hardware Installation
2 Software Installation
Contents
2.1 General
2.2 COM Word Service
2.3 Text Block Reminders
2.4 UNI-TE Services
2.5 Application-to-Application Communication
2.6 Priority Communication - Telegram
2.7 PLC Scan Cycle
2.8 Multiple Network Configurations
3 Maintenance
Contents
3.1 Troubleshooting
3.2 Self-Tests and Specific Tests
3.3 Data-Rate Control
Dialogue
5
General Contents
13
15
16
26
32
39
43
49
50
53
54
59
62
Page
5
7
9
3
4
1
Section
4 Technical Specifications
Contents
4.1 Performance
5 Appendix
Contents
5.1 Module Design
5.2 TSX Series 7 V3 PLC Special Points
5.3 Uni-TE Read Requests
5.4 Uni-TE Write Requests
General Contents
Page
63
64
73
74
78
80
98
2
Introduction
Sub-section
1.1 Documentation Presentation
1.2 Module Description
1.2-1 General
1.2-2 Module Features
1.3 Hardware Presentation
1.3-1 TSX MAP 1074 Module
1.3-2 TSX MAP ACC1 Terminal Block
1.4 Hardware Installation
1.4-1 Installing the Module in the Rack
1.4-2 Coding the Address in the Terminal Block
1.4-3 Connection to the Network
Introduction
1
Section 1
Page
4
7
7
8
5
5
6
9
9
10
11
3
1.1
Documentation Presentation
The TSX MAP 1074 Mapway Module User’s Manual is designed for users installing a TSX MAP 1074 Module in a TSX Series 7 PLC and connecting to a Mapway network.
The complete documentation set and the points covered are described below:
The Mapway Reference Manual (TSX DR MAP V4E) covers Mapway network:
• Operating principles,
• Installation and testing principles,
• Implementation of Control, Adjust and Diagnostic functions,
• Technical characteristics.
Specialized User’s Manuals (including this manual) are available for each device or family of devices that can be connected to a Mapway network. The main points covered by these manuals include:
• Device description,
• Mapway network implementation or connection of each device,
• Mapway network performance,
• Mapway network operation with Telemecanique terminals or programs,
• Remote diagnostics functions via the network.
This manual (TSX DM MAP 107 V4E) and the Mapway Network Reference Manual
(TSX DR MAP V4E) are supplied with the TSX MAP 1074 module. These A5 format manuals can be inserted in an A5 format binder with dividers. The TSX DAC 1 binder must be ordered separately.
†
MAPWAY
†
TSX MAP VAX 7
†
_ _ _ _ _ _ _
†
†
Mapway Network
Reference Manual
_ _ _ _ _ _ _
†
TSX MAP 207
†
TSX MAP 107
Mapway Module
User's Manual
†
4
Introduction
1
1.2
Module Description
1.2-1 General
The TSX MAP 1074 module is an intelligent module for use with TSX Series 7 modular PLCs. It can be installed in TSX Series 7 Model 40 PLCs (TSX 47-40,
TSX 67-40, TSX 87-40 and TSX 107-40 PLCs) with the following processor modules:
• TSX P47-420,
• TSX P67-410/420,
• TSX P87-410/420,
• TSX P107-410/420, and in TSX Series 7 V3 PLCs:
• TSX 47-31,
• TSX 67-21,
• TSX 87-31.
The module can be used for communication between the PLC and other devices in an X-WAY automation system.
These devices include:
• Telemecanique modular PLCs described above,
• Telemecanique TSX T607 or TSX T407 programming terminals connected to the programming port of a PLC on the network,
• Telemecanique FTX 507 workstations directly connected to the network or connected to the programming port of a PLC on the network,
• IBM PC or compatible microcomputers equipped with a PC-AT (ISA) bus,
• Telemecanique Monitor 77 supervision systems,
• Digital Equipment Corporation (DEC) MicroVAX and IVAX minicomputers,
• NUM robot or machine tool numerical controllers.
The network interfaces required depend on the device to connect to Mapway:
• TSX MAP 1074 module for PLCs,
• TSX MAP PC74 interface board for FTX 507, Monitor 77 and all IBM PC and compatible microcomputers,
• TSX MAP VAX74 or TSX VAX174 interface boards for DEC MicroVAX and IVAX minicomputers.
This manual describes the TSX MAP 1074 module for use with Telemecanique
PLCs.
5
1.2-2 Module Features
The TSX MAP 1074 module supports Mapway network connection. The module is connected to the Mapway network through a TSX MAP ACC1 terminal block. The terminal block connects to the module via a Sub-D type connector and to the
Mapway network drop cable via a type F connector. The address of the connected device on the network (station and network numbers) is set in the terminal block.
The Mapway network uses 75 Ohm coax. cable to interconnect the various devices.
The transmission data-rate is 5 Megabits/second (Mb/s). The network access method is a Token bus in a logical ring.
The application services use standard Telemecanique protocols: COM word services and Uni-TE requests.
The Mapway network supports:
• A virtual extension of the memory bus to PLCs connected to the network and using the COM (common) word service,
• The exchange of messages (text blocks) between two network stations in pointto-point or broadcast modes to all network stations,
• Remote access for all FTX 507 workstation functions when connected to the network or to the programming port of a PLC.
Ease of Use
The TSX MAP 1074 module can operate immediately on power-up in the PLC rack, without the need for downloading a configuration.
Operational Safety
The TSX MAP 1074 module is electrically isolated from the network. In addition, the terminal block that connects the module to the network can be inserted and removed under power.
Self-Tests
Each time the module is powered-up, it runs a series of self-tests of its internal logic.
These self-tests include a test of the entire network as seen by the module. Any signs of incorrect operation are displayed on the front panel of the module by a set of LED indicators and 7 segment displays. Any faults detected are also sent to the
PLC.
Watchdog
Each TSX MAP 1074 module has a built-in watchdog. If the module fails, its exchanges with the network are disabled in order to protect the network.
6
Introduction
1
1.3
Hardware Presentation
1.3-1 TSX MAP 1074 Module
The TSX MAP 1074 module is a single height module that can be installed in any slot of the basic PLC rack in a PLC configuration.
The module comprises:
1
A metal case that protects the electronics of the module and ensures shielding from interference.
2
A green "RUN" LED that lights when the module is poweredup and operating normally.
3
A red "DEF" (fail) LED that lights when a module fault is detected.
4
Three yellow LEDs that indicate the status of the module in relation to the Mapway network:
• INR: Station in the logical ring,
• RX: Station receiving data,
• TX: Station transmitting data.
5
Two 7 segment LED displays for displaying module operating data.
6
A female Sub-D 11-point connector.
7
Two mounting screws that retain the module in the rack.
MAP 107
RUN
DEF
INR
RX
TX
NET
3
4
5
6
7
The rear panel of the module is equipped with factory-coded locating devices which prevent any risk of error when modules are installed.
7
1
2
7
1.3-2 TSX MAP ACC1 Terminal Block
The terminal block is used to connect TSX MAP 1074 modules and their TSX Series 7 PLCs to the
Mapway network. It performs the following functions:
• Connection of TSX MAP 1074 modules to the Mapway network via a male Sub-D connector between the terminal block and the module and a type F connector between the terminal block and Mapway,
• Module addressing on the
Mapway network. The station and network numbers are set in hexadecimal in the terminal block, on four thumbwheel switches.
The terminal block is fitted with a plastic tab that attaches the terminal block to the PLC rack at the location of the TSX MAP 1074 module. Attaching the terminal block makes it possible to replace a module without disconnecting the terminal block from the network cabling ensuring that will not be incorrectly reconnected.
Module and terminal block dimensions
262
235
2
Minimum curve radius: 100 mm
(*) 18 with TSX MAP ACC9 90
°
angle connector adaptor.
8
Introduction
1
1.4
Hardware Installation
1.4-1 Installing the Module in the Rack
TSX Series 7 Model 40 PLCs:
TSX 47-40
TSX 67-40
TSX 87-40
TSX 107-40
Slots 0 to 7
Slots 0 to 7
Slots 0 to 7
Slots 0 to 7
1 module max.
2 modules max.
4 modules max.
4 modules max.
TSX Series 7 V3 PLCs:
TSX 47-31
TSX 67-21
TSX 87-31
Slots 0 to 7
Slots 0 to 7
Slots 0 to 7
1 module max.
1 module max.
1 module max.
Note: Regardless of the type of PLC used, TSX MAP 1074 modules can only be installed in the main configuration rack.
Hardware and software codes
Hardware code
A two figure decimal code that is set on the locating devices on the rear of the module.
Software code
A decimal code entered from the programming terminal with the I/O configuration of the PLC.
13
Model 40: 13
V3 PLCs: 12
Network installation
The network cables, tap junctions and other components should be installed according to the procedures described in the Mapway Network Reference Manual
(TSX DR MAP V4E).
9
1.4-2 Coding the Address in the Terminal Block
The thumbwheel switches are accessed by removing the side cover of the terminal block.
Once this is done, it is possible to remove the circuit board that supports the four thumbwheel switches and the type F connector.
Each station in a network layout is assigned a double identification number:
• STAT: The station number on the network. It can take a value from 0 to 3F (for a total of 64 stations),
• NET: The network number. It can take a value from 0 to 7F.
This double number is coded in Hexadecimal by the four thumbwheel switches in the terminal block, as shown in the example below. A
Mapway network can comprise up to 64 stations per network segment.
Example
The coding shown on the thumbwheel switches illustrated above corresponds to the address of station 27 (H’1B’) on network 3 (H'03').
Reminder: The addressing principles and the operation of the Mapway network are described in section 3 of the Mapway Network Reference Manual
(TSX DR MAP V4E). Network number 0 is reserved for single network layouts. In multiple network layouts, network numbers 1 to H'7F' should be used.
10
Introduction
1
1.4-3 Connection to the Network
Once the module is installed in the PLC rack and the terminal block with the address coding is connected to it and the network, then the module is connected to the
Mapway network.
When the PLC is powered-up, all of the LEDs on the module light momentarily and the self-tests start. The “RUN” LED blinks while the self-tests are in progress and remains lit once they are completed correctly. This LED shows that the module is operating correctly.
The “RUN” LED is extinguished if the module watchdog is triggered and the module becomes idle.
The “INR” (IN Ring) LED shows that the TSX MAP 1074 module is connected to the
Mapway network and is active in passing the token on the bus. This means that the module is ready to send and receive messages.
The “INR” LED remains off during the self-test phase and it only lights once these are completed successfully. Until this LED lights, the module can only receive messages, it cannot transmit on the network.
The “RX” and “TX” LEDs show that the TSX MAP 1074 module has detected data reception (RX) or transmission (TX) activity on the network.
The 7 segment LED displays are used to display different types of information. While the module is operating normally, they display two types of information at two second intervals:
• The network number with a decimal point at the lower right of the display, e.g. network 2,
• The station number without a decimal point, e.g. station 1A.
If a fault occurs during the self-test phase or during normal operation, the displays will show an error code. Refer to section 3, Maintenance, for further information.
11
12
Software Installation
Software Installation
2
Section 2
Sub-section
2.1 General
2.1-1 Functions
2.1-2 Module Configuration
2.2 COM Word Service
2.2-1 General
2.2-2 Common Memory Organization
2.2-3 COM Words in Multiple Network Layouts
2.2-4 COM Word Configuration
2.2-5 System Bits and Words
2.2-6 Application Examples
2.3 Text Block Reminders
2.3-1 Description
2.3-2 Communication by TXT Text Block
2.3-3 Communication by SYS Text Block
2.3-4 Table Layout
2.4 UNI-TE Services
2.4-1 General
2.4-2 Server PLC
2.4-3 Client PLC
2.5 Application-to-Application Communication
2.5-1 Point-to-Point Messages
2.5-2 Broadcast Messages
2.5-3 Point-to-Point Message Example
Page
15
15
15
16
16
17
18
20
22
24
26
26
26
30
31
39
39
40
41
32
32
33
35
13
Software Installation
Sub-section
2.6 Priority Communication - Telegram
2.6-1 General
2.6-2 Telegram Programming
2.6-3 Telegram Example
2.7 PLC Scan Cycle
2.8 Multiple Network Configurations
2.8-1 Module Configuration
2.8-2 PLC Cycle Time
Section 2
Page
43
43
45
46
49
50
50
51
14
Software Installation
2
2.1
General
2.1-1 Functions
The TSX MAP 1074 module supports the functions defined for the Mapway network.
These functions include:
• Carrying UNI-TE messages from the PLC processor to the network and vice versa. This message system supports access to variables (all PL7 objects) for reading and writing, program transfer and PLC operating mode control,
• Application program to application program communication in point-to-point mode from any station in the network layout to any other station, or broadcast messages on the network,
• High priority fast communication between application programs (short 16 byte exchanges) between two PLCs on the same network, in the form of telegrams
(TLG),
• Cyclic broadcasting of the distributed COM word data base between PLCs on the same network,
• Overall network management, especially message routing between networks.
During each PLC cycle, 2 messages can be sent on the network in normal operation, up to four messages per cycle can be sent at peak load. In the same way, at the start of each PLC cycle, the PLC can receive two messages in normal operation (four during peaks) from the PLC.
The TSX MAP 1074 module can handle approx. 200 messages per second. A message is a COM field sent or received or a TXT, SYS or TLG text block sent or received.
2.1-2 Module Configuration
The TSX MAP 1074 module is automatically configured on power-up. The network number (0 to H’7F’) and the station number (0 to H’3F’) assigned, are those set in the TSX MAP ACC1 terminal block.
The PLC will only recognize the TSX MAP 1074 module if it has been declared in the I/O configuration. If the module is not declared, it can still send messages to the
PLC system, e.g. for program downloading.
15
2.2
COM Word Service
2.2-1 General
Note: The COM word service described below applies to TSX Series 7 Model 40 PLCs
(TSX 47-40, TSX 67-40 TSX 87-40 and TSX 107-40). The COM word service available with V3 level PLCs (TSX 47-31, TSX 67-21 and TSX 87-31) is described in the Appendix, sub-section 5.2.
The complete set of COM words form a data base that is distributed among the various network stations.
Depending on their configuration, the various network stations can access a common memory field of 256 words of 16 bits. This memory field is dedicated to exchanges between PLCs.
Depending on its configuration, each station that supports this service is assigned from 4 to 64 COM words that can be written. The other words, assigned to other stations can only be read.
The COM words are updated automatically as they change, without requiring any intervention from the application program, at the same rate as the normal sequential
(Master task) activity.
At the start of each Master task cycle, when the station inputs are acquired, the PLC processor reads all of the COM words that have changed in other network stations, from the network interface in the module.
Master task sequence at station "n"
Read the
COM words from the interface.
Specific system bits and words ensure that the COM word update and refresh mechanism is operating correctly.
Sequential processing
Write the COM words assigned to station "n", to the interface.
The user program simply uses
PL7-3 bit or word instructions to read or write the COM words.
At the end of the Master task cycle, when the outputs are updated, the PLC processor writes the assigned COM words that have changed, to the network interface in the module.
The newly updated COM words are then sent on the network during two consecutive cycles.
Every 10 cycles, all of the COM words assigned to a station are sent on the network during two consecutive cycles.
16
Software Installation
2
2.2-2 Common Memory Organization
Each TSX MAP 1074 module has a memory field of 256 words of 16 bits dedicated to communication between PLCs. This memory field is split into sub-blocks of words. The number of stations that send COM words on the network and their address determines the number of COM words available, as shown in the table below:
Number of stations
2 to 4
5 to 8
9 to 16
17 to 32
33 to 64
Example with 64 stations:
Number of
COM words
64 max.
32 max.
16 max.
8 max.
4
Station addresses
0 to 3
0 to 7
0 to H'0F'
0 to H'1F'
0 to H'3F'
Station 0
Station 1
F 0
COM 0,0
COM 0,1
COM 0,2
COM 0,3
COM 1,0
COM 1,1
COM 1,2
COM 1,3
Station 3F
COM 3F,0
COM 3F,1
COM 3F,2
COM 3F,3
17
Each word in the memory can be accessed by the syntax COMi,j: where i = station number (0 to H’3F’), j = word position (0 to H’3F’).
The internal program of TSX Series 7 PLCs enables access to the individual bits of
COM words. In this case the syntax is COMi,j,k: where i = station number (0 to H’3F’), j = word position (0 to H’3F’), k = bit position (0 to H’0F’).
The PLC user program:
• Writes data to be sent on the network to its own COM word field COMi,j,
• Reads the data from a network station by reading from the COM word field COMi,j assigned to each station.
2.2-3 COM Words in Multiple Network Layouts
In a multiple network layout, some PLCs are connected to two or more different networks or network segments.
The common network field can therefore only be accessed by PLCs connected to the same network segment. These PLCs therefore have access to two or more memory fields.
To distinguish between COM words from different networks the following syntax is used COMxi,j: where x = logical network identifier, i = station number, j = word position.
The network logical identifier takes the value B, C or D depending on the number of interface modules in the Bridge station. The identifier letter is dynamically assigned by the PLC processor, depending on the geographical location of the interface module. Each identifier letter corresponds to a dedicated memory field that is assigned to the designated network.
18
Software Installation
2
Example
Network connected to the module in slot 1: no identifier,
Network connected to the module in slot 4: identifier B,
Network connected to the module in slot 5: identifier C.
0
M
P
W
1 2 3
M
P
W
4
M
P
W
5 6 7
Memory field that is common to the three networks connected to the
PLC.
V
COM0,0
COM0,1
. . . . .
COM1,0
. . . . .
COM8,0
. . . . .
Network 1
V
COMB0,0
COMB0,1
. . . . .
COMB1,0
. . . . .
COMB8,0
. . . . .
Network 2
V
COMC0,0
COMC0,1
. . . . .
COMC1,0
. . . . .
COMC8,0
. . . . .
Network 3
The network logical identifier does not correspond to a network number but to a geographical location. The PLC application program is independent of the network number. The user must ensure that in the application program, the logical identifier assigned by the PLC corresponds to the network that is actually connected to the module.
19
2.2-4 COM Word Configuration
When a TSX MAP 1074 module is configured, it is possible to:
• Inhibit it from accessing COM words,
• Validate COM word read-only access,
• Validate COM word read and write access,
• Declare the number of COM words (from 4 to 64) controlled by the station.
The number of COM words declared must be identical for all stations on the same network. If the value configured for a station is incorrect, it will be ignored by the others.
A station that reads and writes COM words sends its COM words on the network and receives the COM words sent by other network stations.
An inactive station neither sends nor receives COM words. This function reduces network traffic and the workload of each station.
A station that is active in read-only mode cannot send COM words on the network but can read those sent by other stations.
It is possible to configure a number of COM words that is less than the maximum allowed for each station. This feature must always be used when only limited amounts of information need to be sent on the network. This considerably improves
COM word processing time by the PLC.
Configuration procedure
The selection is made when the application is configured by an FTX 507 workstation
(with PL7-3 language in Configuration mode).
After selecting the Configure Network Service action, a screen is displayed that shows the following information for each module:
• Its type,
• Its location in the PLC,
Allowing the user to change:
• The number of COM words assigned by the module (0 by default),
• Whether or not COM words are active (inactive by default).
20
Software Installation
2
Note: When the TSX MAP 1074 module is not declared in the Input/Output configuration of the PLC, COM word exchange is not supported.
For more information on entering and configuring COM words using the programming terminals, refer to the PL7-3 Operating Modes manual (TXT DM PL7-3 V4E).
Configuring PLCs for Multiple Network Operation
Configuration of the COM words of multiple network PLCs, i.e. PLCs that have more than one TSX MAP 1074 module is performed with the PL7-NET program. This program is part of the X-TEL Software Workshop.
Among other functions, this program enables:
• Selection of stations that form a network and assignment of station addresses,
• Assignment for each Bridge station, of the modules connected to the various networks.
For more information on how to use this program, refer to the PL7-NET Program documentation (TXT DM PL7 NET V4E).
21
2.2-5 System Bits and Words
Some system bits and words can be used by the user program for testing the correct operation of the network and application coherence, with the PLC running and the
Mapway network interface operating. The following bits and words are used by the test:
System Bit
SY11
SY12
SY13
Description
COM word refresh
Network A operating
Function
Normally at 0, this bit is set to 1 when a local station has received COM words from at least one remote station.
It is reset to 0 by program or by the terminal, so that it can check other transmissions of COM words.
This bit is set to 1 once the network interface of the station has exchanged COM words with at least one other station on the network.
It is reset to 0 by program or by the terminal, so that it can check other transmissions of COM words.
as SY12
SY14
SY15
Network B operating
Network C operating
Network D operating as SY12 as SY12
22
Software Installation
2
Module
A
System Words
Module
B
Module
C
Module
D
SW64
SW65
SW66
SW67
SW68
SW69
SW70
SW71
SW72
SW73
SW74
SW75
SW76
SW77
SW78
SW79
SW80
SW81
SW82
SW83
SW84
SW85
SW86
SW87
SW88
SW89
SW90
SW91
SW92
SW93
SW94
SW95
SW96
SW97
SW98
SW99
Refresh Indicators
(1 bit per station)
Stations H'00' to H'0F',
Stations H'10' to H'1F',
Stations H'20' to H'2F',
Stations H'30' to H'3F'.
Reserved words,
Reserved words,
Reserved words,
Reserved words.
Module network address
Refresh indicators
The 16 bits of each word represent the 16 network stations. A bit at 1 indicates that the corresponding station has sent its COM words.
It is reset to 0 by program only, so that it can check other transmissions of COM words.
Module network address
This word indicates the network number (0 to 127) and the station number (0 to 63) corresponding to each module, in the form of:
F 8 7 0
Network Nbr.
Station Nbr.
23
2.2-6 Application Examples
Transmission and reception of COM words
Station 0 sends status information from a door position contact
(door open: B0 = 1, door closed: B0 = 0).
On receiving this information, station 1 controls a motion module by activating or deactivating its output O1,0:
• If the door is open: move the moving part forward,
• If the door is closed: stop the moving part.
0
0
1
Station 0 program
"
S T A T I O N 0 "
B0 COM 0,0,0
The value of bit B0 is transfered to bit 0 of
COM0,0 in station 0.
Station 1 program
0
0
1
COM 0,0,0
"
STATI O N 1
0,1,0
The value of bit B0 of
COM0,0 is transferred to output O1,0.
Using system bits and words
Use of system bits and words is not required in all applications. However, when a station has to check the correct operation of other stations connected to the network, the following tests can be performed:
24
of rred
Software Installation
2
SY12: Performs an overall check that the network is operating:
0
0
1
SY12
"
O0,0
/
Controls a "network fault" indicator
0
1
1
SW64: The user can check that within a set period of time that corresponds to the
to
maximum time-out required for transferring all COM words, the bits of all
SW99 the connected stations that use the COM word service have gone from 0 to 1. A branch to a network fault handling program can be used when one or more of these bits remains at 0.
The use of these system bits means that the state of COM words can be processed only after a network refresh. The user sets all remote station bits to 0 and monitors their change to 1.
Example
Stations 0, 1 and 2 are connected to the same network. Correct operation of stations
1 and 2 can be performed from station 0 as shown below:
"
STATI O
B0 B2
N 0
OPER
B0
T0
E D
TB=10ms
C R
PR=50
B2
500 ms time-out.
The time-out is greater than the maximum transfer time.
0
1
2
B0
"
SW64<>6
<
B1
S
B1=1
If station 1 or 2 has failed.
6 = binary values of
2 and 4 at 1
25
2.3
Text Block Reminders
2.3-1 Description
A text block is a programming object that can be used by the user program for exchanging data (word tables) with various entities. There are five types of text block that characterize the type of exchange that can be performed. The type is defined when the text block is defined and is set at that time. The various types of text block and the exchanges they can perform are listed below:
TXT Type User program
↔
Another user program,
TLG Type User program
↔
Another user program,
(short high priority messages)
CPL Type User program
↔
Intelligent module or Uni-Telway bus,
TER Type User program
↔
PLC programming port,
SYS Type User program
↔
Connected device system.
Dialog between a PLC and other devices connected to the Mapway network uses TXT type text blocks for application-to-application exchanges (word table transfers), TLG type for high priority communication between user programs and SYS type text blocks for Uni-TE services.
2.3-2 Communication by TXT Text Block
TXT text block functions comprise:
• A text block number
• An exchange type
• A communication type
• A start of table address
• A reception table length
• A transmission table length
• Input bits:
Start transmission
Start reception
Start transmission and reception
Cancel exchange
• Output bits:
Exchange complete
Exchange error
• Status word
• Report word
(usable when TXTi,S = 12)
• Destination text block number
• Destination address
TXTi,D,
TXTi,E,
TXTi,S,
TXTi,V,
TXTi,T,
TXTi,A.
TXTi,
TXT,
Network (NET), e.g. W10, e.g. 12 bytes,
TXTi,L (in bytes),
Literal Language
OUTPUT TXTi
INPUT TXTi
EXCHG TXTi
RESET TXTi
Ladder Language
S, O = 1,
S, I = 1,
S, I, O = 1,
R = 1,
26
Software Installation
2
The TXT text block function exchanges data as word tables that are organized as shown below:
• A transmission table comprising internal words (Wi) or constant words (CWi),
• A reception table comprising internal words (Wi) that allow the destination station to store the data received.
TXTi,D: This bit goes to 1 when the text block completes its exchange (refer to subsection 3.3),
TXTi,E: This bit goes to 1 if an exchange error occurs (refer to sub-section 3.3),
TXTi,S: This word comprises the number of bytes received in the reception table of the text block if the exchange is correct. If an exchange error occurs,
TXTi,S takes the following values:
1: Exchange cancelled by Reset,
2: Transmission table length error,
3: Mains failure (refer to sub-section 3.3),
4: Module failure,
5: Parameter error or too many active TXTs,
6: Message received is too long,
10: Incorrect addressing of the indirect text block,
12: Message refused (refer to TXTi,V),
13: Routing error,
14: Resource error,
20: Other error.
TXTi,V: If parameter TXTi,S is set to 12 (message refused), word TXTi,V indicates the type of refusal:
1: Inadequate bus resources,
2: Inadequate line resources,
3: Cannot access destination,
4: Line error,
5: Length error,
6: Network failure,
7: Address error,
8: Unknown request code,
9: Inadequate PLC resources,
10: Time-out exceeded,
255: Other error.
TXTi,A: Comprises the destination address (network, station), in the form:
TXTi,A = H’ Network Nbr.
Station Nbr.
1 byte 1 byte
If the messages are broadcast to all stations on the same network segment
(broadcast messages), the station number is set to H’FF’. Transmission of broadcast messages to the entire network layout is not possible.
27
The reception table length is set when the text block is configured. It cannot be changed by the user program.
The address of the word table to send and of the reception table where the words received are stored can be specified in two ways:
• By direct addressing: the address is the first word of the table,
• By indirect addressing: the address is stored in a table,
Direct addressing
The text block reception table is stacked on top of the transmission table as shown below. The start address (Addr. Buffer) and the length (Reception length) of the table that is formed, are defined when the text block is configured.
Start of table address: Addr. Buffer (Wi) Wi
Reception table length (in bytes):
Reception Lengh
Reception
Table
Transmission
Table
The transmission table length is defined by the user program, in variable TXTi,L of the text block. It can be changed during program execution.
Example
Text block number TXT0,
Start of table address: W10,
Reception table length: 12 bytes,
Transmission table length: TXT0,L = 8 bytes.
I
R
TXT0
S
O
TXT
TM
T C O
T,V O
W10
12 D
T,L,8
T,S ?
D
E
W10
W11
W12
W13
W14
W15
Reception
W16
W17
W18
W19
Transmission
Special cases
When the text block is only used to send data:
• The reception table length can be null,
• The start of table address (Addr. Buffer) is also the transmission table address,
• The table can be located in the internal words (Wi) or in the constant words (CWi).
28
Software Installation
2
Indirect addressing
The text block transmission and reception tables are defined by a six word addressing table that must be loaded with the information listed below:
Wi or CWi
Type of word in the transmission table
(0 = internal word, 1 = constant word)
Transmission table start address
Transmission table length in bytes
Type of word in the reception table
(must be 0: internal word)
Reception table start address
Reception table length in bytes
Only the start address (Wi or CWi) of the addressing table must be defined when the text block is defined.
Example
Text block TXT1, Indirect addressing, Addr. Buffer = W20.
I
R
S
O
TXT1
TXT
TM0000H
LOCAL
T C O
T,V O
W20
I
T,L,0
T,S ?
D
E
W20
W21
W22
W23
W24
W25
1
40
12
0
80
18
Adressing table
CW40
CW41
CW42
CW43
CW44
CW45
Transmission
W80
W81
W82
W83
W84
W85
W86
W87
W88
Reception
The addressing table defines the transmission and reception tables. It is composed of internal words W20 to W25 which contain the following information:
W20: Indicates the type of words in the transmission table: 1 = Constant words,
W21: Indicates the address of the transmission table: 40
→
CW40,
W22: Indicates the transmission table length: 12 bytes or 6 words. The last word in the transmission table is therefore constant word CW45,
W23: Indicates the type of words in the reception table: 0 = Internal words,
W24: Indicates the address of the reception table: 80
→
CW80,
W25: Indicates the reception table length: 18 bytes or 9 words. The last word in the reception table is therefore internal word W88.
29
2.3-3 Communication by SYS Text Block
The system (SYS) text block is used to communicate with certain system functions of a device connected to Mapway (PLCs or other vendor’s device). This type of communication uses Uni-TE requests.
SYS text blocks comprise:
• A text block number
• An exchange type
• A communication type
• A start of table address
• A reception table length
• A transmission table length
• Uni-TE request code
• An exchange report
• A destination address
• A status word
• Input bits:
Start transmission
Start reception
Start transmission and reception
Cancel exchange
• Output bits:
Exchange complete
Exchange error
TXTi,
SYS,
Network (NET), e.g. W10, e.g. 4 bytes,
TXTi,L (in bytes),
TXT,C,
TXTi,V,
TXTi,A.
TXTi,S,
Literal Language
OUTPUT TXTi
INPUT TXTi
EXCHG TXTi
RESET TXTi
TXTi,D
TXTi,E
Ladder Language
S, O = 1,
S, I = 1,
S, I, O = 1,
R = 1,
Parameters TXTi,D; TXTi,E; TXTi,A; TXTi,S and TXTi,V have the same meanings as those in TXT type text blocks.
TXTi,C: Comprises the code of the request to execute, in the form:
TXTi,C = H’ Category Code Request Code
1 byte 1 byte
The category is that of the source. It takes the value 07. The other codes are reserved.
The request code is that of the request used (refer to the list of Uni-TE requests in the Appendix).
The request data is located in the text block transmission table. The report is located in the reception table if the text block was programmed in EXCHG.
TXTi,V:
This word comprises the code written by the system, indicating exchange validity.
All other programming is performed in the same way as a TXT text block. The other bits and words have the same meaning.
30
Software Installation
2
Example
TXTi,A = H’0105' corresponds to a destination station at address 5 on network 1,
TXTi,C = H’0706' corresponds to a PLC sending the “read system word” request
(request code H’06').
2.3-4 Table Layout
The relations that exist between the structure of a report request and the parameters of a text block are:
Transmission
Request
Code
Category
Code
Byte Byte Word
Transmission Table
1st. word
2nd. word
TxTi, C = H' 07 '
Reception
Confirm Byte Byte Word
Reception Table
1st. word
2nd. word
TxTi, V = H' 00 '
31
2.4
Uni-TE Services
2.4-1 General
Reminders
This service uses a question and answer dialog called Request/Confirm.
A device that supports the Uni-TE protocol can be a:
CLIENT:
This device initiates communication. It asks a question (reads), sends an answer (writes) or an order (Run, Stop, etc.),
SERVER: This device executes the order sent by the client and sends a confirm after execution.
The services supported depend on the type of device, e.g. PLC, numerical controller, programming terminal, supervision system. Depending on its function, each device can be a Client and/or a Server on the Mapway network. Server functions include supporting Programming, Adjust and Debug functions while Client functions include the user program sending commands or reading the state of a device.
The rate at which Uni-TE requests can be handled by a PLC depends on the Master task cycle.
Regardless of where in the program a text block is activated, the
PLC processor sends the appropriate request at the end of the
PLC cycle.
Master task cycle of station "n"
Read
Uni-TE message
A check is made at the start of each cycle to determine if a confirm was received for the request.
Sequential
Processing
While the Master task is running, the PLC can send and receive two
TXT, SYS or TLG messages over
Mapway in normal operation and up to four messages in peaks.
Write
Uni-TE message
32
Software Installation
2
2.4-2 Server PLC
A PLC is a server when it responds to requests sent by a client device, e.g. another
PLC, a Monitor 77 supervisor, an FTX 507 workstation or a computer. The request is generated by the source and sent to the system gate of the destination PLC.
In this case, the exchange can comprise up to 128 characters and is fully transparent to the application program of the server PLC.
The requests that are supported PLCs are listed in the table below.
The detailed coding of these requests is given in the Appendix.
Family
Data
(Read)
Service
Read a Bit
Read a Word
Read Objects
Read a System Bit
Read the Memory
Image of an I/O Bit
Request Confirm
Hex. Dec. Hex. Dec.
00 00 30
Description
48 Reads a bit (B).
04
36
01
02
Read a Constant Word 05
04
54
01
02
05
34
66 102 Reads objects (bits,
31
32
35
52
49
Reads a word (W).
words, word strings, etc.).
Reads a system bit
(SY).
50 Reads the memory image of an I/O bit.
Read a System Word
Read a Common Word
06
07
06
07
36
37
53 Reads a constant word
(CW).
54 Reads a system word
(SW).
55 Reads a common word
(COM).
Read a Timer
Read a Monostable
Read a Counter
Read a Register
Read a Grafcet Step
Read a Double Word
Read a Constant
Double Word
Read a Grafcet Step
09 09 39 57 Reads the parameters of a timer (T).
0A 10 3A 58 Reads the parameters of a monostable (M).
0B 11 3B 59 Reads the parameters of a counter (C).
0E 14 3E 62 Reads the parameters of a register (R).
2A 42 5A 90 Reads a Grafcet step
(Xi).
40 64 70 112 Reads a double word
(DW).
41 65 71 113 Reads a constant double word (CDW).
4B 75 7B 123 Reads a Grafcet step.
33
Family
Data
(Write)
Service
Write a Bit
Write a Word
Write Objects
Write a System Bit
Write the Memory
Image of an I/O bit
Write a System Word
Write a Common Word
Write a Timer Preset
Request Confirm
Hex. Dec. Hex. Dec.
10
14
37
16
20
FE
FE
254
254
Description
Writes a bit (B).
Writes a word (W).
11
12
55 FE 254 Writes objects (bits, words, bit or word strings, etc.).
17 FE 254 Writes a system bit (SY).
18 FE 254 Writes the memory image of an I/O bit.
15
16
17
21 FE 254 Writes a system word
(SW).
22 FE 254 Writes a common word
(COM).
23 FE 254 Writes the preset of a timer (T).
Write a Monostable
Preset
18
Write a Counter Preset 19
Write a Register Input
Write a Double Word
24 FE 254 Writes the preset of a monostable (M).
25 FE 254 Writes the preset of a counter (C).
1A 26 FE 254 Writes the input of a register (R).
46 70 FE 254 Writes a double word
(DW).
Operating
Run
Modes
Stop
24
25
36 FE 254 Sets a device to Run.
37 FE 254 Sets a device to Stop.
Note: Other requests are supported by PLCs. These requests are used for specific applications and are not covered in this manual.
34
Software Installation
2
2.4-3 Client PLC
A Client PLC sends data, an order or a question using Uni-TE requests.
The request is sent to the target station by a SYS type Network text block with a maximum length of 128 bytes.
The requests that can be sent by the PLC are:
• The requests described previously (for dialog between PLCs),
• The requests supported by a destination station that is not a PLC, e.g. CNC,
MicroVAX computer. For further information refer to the documentation for the individual devices giving their coding.
Example
In the network shown below (network 1), the PLC at address 4 reads the parameters of timer T10 of the PLC at address H'0F'. The PLC at address H'0F' does not require a specific application program to allow the station access to its system.
Network 1
SYS
Station 4 Station 0F
TSX 87-40 TSX 87-40
Data
• Read timer request:
• Request code = H’09' (see list of requests),
• Parameter = Number of the timer to read.
• Text Block:
• The request is sent by text block TXT5 of the application program in station 4,
• Start of transmission table = W264. The transmission table comprises the number of the timer (10),
• Start of reception table = W200.
35
Transmission
• Station 4 Text block:
• TXT5 is a SYS type Network text block,
• TXT5,A = H’010F’ Network 1, Target station H’0F’,
• TXT5,C = H’0709' Category code = H’07', Request code = H’09',
• TXT5,L = 2 (Length of the transmission table in bytes),
• Transmission table:
Timer number
W264 10
Reception
• Station 4 Text block:
• TXT5,V = H’39' Correct exchange confirm,
• TXT5,D = 1,
• TXT5,E = 0,
• TXT5,S = 8 8 bytes received,
• Reception table:
W200
W201
W202
W203
00
01
3600
1712
02
01
• Confirm analysis:
W200 = H’0002'
Least significant byte = 02
→
1 second time-base,
Most significant byte = 00
→ time-base not timed out.
W201 = H’0101'
Least significant byte = 01
→ timer running,
Most significant byte = 01
→ preset can be changed.
W202 = 3600
The configuration preset value is 3600.
W203 = 1712
The current value when processing took place was 1712.
36
Software Installation
2
Read objects request
This request allows the reading of simple objects (words, word strings, etc.). It is described in detail in the Appendix.
When this request is sent, the user must specify the parameters of the source text block (TXTi,C; TXTi,L, etc.) and its transmission table. The transmission table includes the following parameters:
• Segment that the request is addressed to,
• Type of object to read,
• Address of the first object to read,
• Number of objects to read.
Once the request is processed by the destination device, it sends the type of object read and the requested information back to the start of the source text block.
The source text block reception table (when set to read words for example) has the following layout:
Wi
Wi+1
Wi+2
Wi+3
1st. word LSB
2nd. word LSB
3rd. word LSB etc.
Type of object
1st. word MSB
2nd. word MSB
3rd. word MSB
Data received is shifted by one byte and is stored in two consecutive words. The application program must therefore take into account the shift when processing the data received. This is done:
• By the SLCWORD (Source;Length) instruction in TSX Series 7 Model 40 PLCs,
• By program in TSX Series 7 V3 PLCs.
Example
The PLC at address 4 reads a table of 20 words (starting at address W50) from a
PLC at address H’0F’.
Network 1
SYS
Station 4 Station 0F
TSX 87-40 TSX 87-40
37
Page 37 - Recouvrement Noir
Data
• Read objects request
• Parameter: Segment nbr.
Type of object
Start address
Nbr. of objects to read
= H’36' refer to list of requests,
= H’68' (internal words),
= H’07' (16-bit integers),
= 50,
= 20.
• Text block:
• The request is sent by text block TXT2 of the application program in station 4,
• Start of transmission table : W364,
• Start of reception table : W300.
Transmission
• Station 4 text block
• TXT2 is a SYS type Network text block,
• TXT2,A = H’010F’ network 1, destination address H’0F’
• TXT2,C = H’0736' category code = H’07', request code = H’36'
• TXT2,L = 6 (transmission table length in bytes),
• Transmission table:
Type (H’07') / segment (H’68')
Address of the first word to read
Number of words to read
W364
W365
W366
07
50
20
68
Reception
• TXT2,V = H’66' (correct exchange confirm),
• TXT2,D = 1
• TXT2,E = 0,
• TXT2,S = 41 (receive 41 bytes).
As the data is shifted by one byte, the application program uses the SLCWORD
(W300;W400) instruction to shift the data again. W400 represents the length (in bytes) of the processing. In this example, W400 must contain the value 41. Once the operation has been performed, the reception table is laid out as follows:
W300
W301
W50 MSB
W51 MSB
W50 LSB
W51 LSB
W321 W69 MSB W69 LSB
38
Page 38 - Recouvrement Noir
Software Installation
2
2.5
Application-to-Application Communication
2.5-1 Point-to-Point Messages
The TSX MAP 1074 module supports point-to-point message exchange on Mapway.
A PLC connected to Mapway can:
• Send a message to another PLC when requested to do so by its application program,
• Receive a message from another PLC.
These messages are sent to their destination by a TXT type Network text block with a maximum size of 256 bytes. They are received by the destination PLC using a TXT type Network text block.
The messages are contained in the transmission and reception tables of the text blocks.
Logical connection between the two stations requires simultaneous:
• Transmission activation (OUTPUT TXTi) of a text block by the application program of the source station, and
• Reception activation (INPUT TXTi) of a TXT type Network text block by the application program of the destination station.
The text block parameters are:
TXTi,A: TXTi,A of the source station text block comprises the network and station numbers of the destination station.
TXTi,A of the destination station text block comprises the network and station numbers of the source station.
TXTi,T: TXTi,T of the source station text block comprises the number of the destination station text block.
TXTi,T of the destination station text block comprises the number of the message source text block.
Master task cycle of station "n"
Regardless of where in the program a text block is activated, the
PLC processor sends the appropriate request at the end of the
PLC cycle.
While the Master task is running, the PLC can send and receive two messages via Mapway in normal operation and up to four messages during peaks.
Sequential
Processing
Read TXT message
Write TXT message
39
Page 39 - Recouvrement Noir
Parameter programming example
H'0207'
12
Network 0, Station 3
TXT1
R D
TXT
TXT1,A
TXT1,T
S
T,T : 12
T,A : 0207H
E
I
O
Wi u
T,L : x
T,S : ,
Network 2, Station 7
TXT12
R D
TXT
S
T,T : 0
T,A : 0003H
I
O
Wj v
T,L : y
T,S : ,
E
3
0
TXT12,A
TXT12,T
2.5-2 Broadcast Messages
A broadcast message is a point-to-point message that is sent to all stations on the same network.
A broadcast message is read by all other stations on the same network as the source station, on condition that they have a text block configured to receive these messages.
TXTi,A: Comprises the network and station numbers of the destination stations.
The station number takes the value H’FF’.
E.g. H’01FF’ for all stations on network 1.
TXTi,T: Gives the number of the destination station text block. All text blocks configured to receive broadcast messages must have the same number.
The other parameters must be initialized in the same way as a point-to-point text block.
Remember to ensure that each destination station has a text block configured for reception (INPUT TXTi) with the number of the message source text block in its
TXTi,T parameter.
All of the rules that apply to text block programming apply to broadcast messages.
40
Page 40 - Recouvrement Noir
Software Installation
2
2.5-3 Point-to-Point Message Example
In the example shown below the TSX 87-40 PLC at address H'0204' (Network 2,
Station 4) sends the message “HIGHER THRES REACHED” to the TSX 47-40 PLC at address H'010C' (Network 1, Station H'0C').
Network 1
Station H' OC'
Station 6
TSX 47-40
TXT
TSX 87-40
Network 2
TXT5 Station 4
TXT
TXT8
TSX 87-40
Data
• Source PLC (Network 2, Address 4):
• The message is sent by text block TXT8 of the application program,
• Start of transmission table = W100. The transmission table comprises the message to send,
• There is no reception table.
• Target PLC (Network 1, Address H'0C'):
• The message is received by text block TXT5 of the application program,
• Start of reception table = W10,
• There is no transmission table.
Message transmission
• Text block:
• TXT8 is a TXT type Network text block set for OUTPUT TXTi,
• TXT8,A = H’010C’ Network 1, Target address H’0C’,
• TXT8,T = 5: Text block TXT5 is the destination,
• TXT8,L = 20: Send 10 words (20 bytes),
• W100 = Reception table address W100 corresponds in this case to the address of the transmission table as the reception table length is zero.
41
Page 41 - Recouvrement Noir
• Transmission table:
W100
W101
W102
W103
W104
W105
W106
W107
W108
W109
49 (I)
48 (H)
52 (R)
54 (T)
52 (R)
53 (S)
52 (R)
41 (A)
48 (H)
44 (D)
Message reception
• Text block:
• TXT5 is a TXT type Network text block set for INPUT TXTi,
• TXT5,A = H’0204' Network 2, Source station H’04',
• TXT5,T = 8: Text block TXT8 is the source,
• TXT5,L = 0: Transmission table length is zero,
• W10 = Reception table address,
• Reception table:
W10
W11
49 (I)
48 (H)
48 (H)
47 (G)
45 (E)
20 (Space)
48 (H)
45 (E)
20 (Space)
45 (E)
43 (C)
45 (E)
48 (H)
47 (G)
W18
W19
• TXT5,S = 20: Receive 20 bytes (10 words).
48 (H)
44 (D)
43 (C)
45 (E)
42
Page 42 - Recouvrement Noir
Software Installation
2
2.6
Priority Communication - Telegram
2.6-1 General
Note: The telegram service is only supported by TSX Series 7 Model 40 PLCs.
A telegram is a specific type of text block used for priority transmission of short messages (up to 16 bytes max.) between two stations. It can be used by any task in the sender PLC (Master task, fast task or interrupt task) and can be sent to any station on the same network.
When a telegram is sent, the PLC processor immediately sends the message to the network interface module, without waiting for the end of the Master task cycle.
In reception, as soon as the message is received by the network interface module, an interrupt is generated and sent to the PLC processor. The destination application interrupt task (IT task) then reads the telegram and performs any required actions.
This process usually ensures application program-to-application program communication in less than 30ms.
A telegram is sent by a TLG type Network function block. An application program can only send one telegram in each cycle to each network interface. A PLC that comprises a number of network interfaces (e.g. in Bridge or data concentrator applications) can simultaneously send a telegram from each network interface.
IT Task Read TLG
I
IT
CYT P
O
IT Task Fast or Mast
Write TLG
TLG text block parameters
The "TLG" text block function comprises the following parameters. They must be defined on configuration:
• Text block number
• Type of exchange
• Type of communication
• Start of table address
• Reception table length
• Transmission table length
• Type of addressing
TXTi
TLG
NET e.g.: W10
16 bytes max.
TXTi,L (16 bytes max.)
Direct or Indirect
43
Page 43 - Recouvrement Noir
The TLG text block also comprises:
• Input bits:
Start "Transmission"
Start "Reception"
Start "Transmission-Reception"
Cancel exchange
• Output bits:
"Exchange complete"
"Exchange error"
• Status word
• Target address
• Target text block number
Literal
OUTPUT TXTi
INPUT TXTi
EXCHG TXTi
RESET TXTi
TXTi,D
TXTi,E
TXTi,S
TXTi,A
TXTi,T
Ladder
S,O = 1
S,I = 1
S,I,O = 1
R = 1
TXTi,S
The status word (TXTi,S) comprises the number of bytes sent or received (1 to 16) by the text block by its transmission or reception table when the exchange is correct.
If an exchange error occurs, (bit TXTi,E at 1), TXTi,S takes one of the values listed below:
1 : Exchange in progress cancelled by Reset,
2 : Message longer than 16 bytes (in transmission),
3 : Power failure,
4 : Module failure,
6 : Telegram too long for the text block reception buffer,
10 : Incorrect text block parameters for indirect addressing,
13 : Routing error (cannot access network),
14 : System reconfiguring, module self-testing, etc.,
15 : Telegram channel busy (in transmission).
This variable can only be read and is significant only when the exchange is completed.
TXTi,A
The destination address (TXTi,A) must be coded as:
F 8 7 0
Network Number
0 to H' 7F'
Note:
Station Number
0 to H' 3F'
Parameters TXTi,L; TXTi,A and TXTi,T can be modified by program.
44
Page 44 - Recouvrement Noir
Software Installation
2
2.6-2 Telegram Programming
Transmission
The transmission of a telegram (TLG) type text block is programmed in the same way as a TXT type text block.
Transmission is started when input "O" is set to 1 in Ladder language or with the
OUTPUT TXTi instruction in Literal. The TLG text block can be started from the application program interrupt task, fast task or master task.
If transmission is unsuccessful, e.g. the destination PLC is powered-down, no TLG text block is configured in Input, the telegram that was sent is returned to the sender
Mapway interface. This interface will then generated an interrupt. If an IT task is running and enabled (DMASKINT), it is executed. The IT task must be acknowledged
(ACKINT) or the PLC will generate a MEM error condition and stop the application.
The use of TXTi,E and TXTi,D bits is described in sub-section 3.3, Data-Rate
Control.
Reception
A telegram is received by a TLG type text block.
The telegram destination network interface must know which text block is ready to receive the message. To ensure this, the text block must be set-up as INPUT TXTi.
On reception of a telegram from the network, the network interface gives it priority, reads it and generates an interrupt that is sent to the PLC processor. The interrupt starts the application program interrupt task that must:
• Determine which network interface generated the interrupt,
• Read the telegram with the "READTLG" instruction.
The network interface that generated the interrupt is determined by the instruction:
READINT (Ixy;Bi) x = Rack number (0), y = Module position in the rack (0 to 7),
Bi= Copies the interrupt from the module to an internal bit. This bit goes to 1 when an interrupt is detected.
45
Page 45 - Recouvrement Noir
The telegram is read by the instruction:
READTLG (Ixy;Wi) x = Rack number (0), y = Module position in the rack (0 to 7),
Wi = Read confirm that takes one of the following values:
0 : Reception successful,
4 : Message longer than 16 bytes (in reception),
5 : Incorrect destination address,
6 : Reception network interface error,
7 : Communication system reconfiguring,
8 : Telegram reception already in progress,
9 : No telegram waiting,
10 : No TSX MAP 1074 module,
11 : TSX MAP 1074 but not supported,
12 : Telegram reception refused,
13 : No TLG text block configured in Input,
14 : Telegram received with an bad check character (BCC),
15 : Telegram channel busy.
Execution of this instruction copies the message to the reception buffer of the TLG text block, sets the text block "D" bit to 1 and updates word Wi. The telegram is then available for reading and all related actions.
Transmission - Reception
A TLG text block can be programmed for transmission/reception by the EXCHG
TXTi instruction (or by setting bits S, I, O to 1). Responding to the text block is up to the application program of the destination PLC. This response must be sent by a TLG text block program for OUTPUT. Data reception is performed as described above (interrupt detection and telegram reading). The data received is stored in the reception table of the text block.
2.6-3 Telegram Example
Transmission from the TSX 67-40 PLC at address H’0204' (Network 2, Station 4) of the message "ALARM 8" to the PLC at address H’020C’ (Network 2, Station
H’0C’):
Network 2
Station H' 0C' Station 4
TSX 67-40
46
Page 46 - Recouvrement Noir
TXT3
TLG
TXT6
TLG
TSX 87-40
Software Installation
2
Data
• Source PLC (Station 4):
• The telegram is sent by application program text block TXT3,
• Start of transmission table = W100. The transmission table comprises the message to send,
• There is no reception table.
• Target PLC (station H’0C’):
• The message is received by application program text block TXT6,
• Start of reception table = W50,
• Reception table length: 16 bytes,
• There is no transmission table.
Message transmission
• Text block:
• TXT3 is a TLG type Network text block programmed for OUTPUT,
• TXT3,A = H’020C’ destination address (Network 2, Station H’0C’),
• TXT3,T = 6 : TXT6 is the destination text block,
• TXT3,L = 8 : Send 8 bytes,
• W100 = Reception table address. As there is no reception table (nul length),
W100 corresponds to the transmission table address.
• Transmission table.
W100
W101
W102
W103
4C (L)
52 (R)
20 (space)
20 (space)
41 (A)
41 (A)
4D (M)
38 (8)
• Telegram transmission
The telegram is sent from the master task:
< Transfer data to the transmission table
! W152[4]
→
W100[4]
< Send telegram
! OUTPUT TXT3
47
Page 47 - Recouvrement Noir
Message reception
• Text block:
• TXT6 is TLG type Network text block programmed in INPUT,
• TXT6,A
• TXT6,T
= H’0204' source address (Network 2, Station 4),
= 3: Text block 3 is the source,
• Recept. length = 16: receive 16 bytes max.,
• W50 = Reception table address,
• There is no transmission table, TXT6,L = 0.
The telegram destination module is located in Rack 0, Slot 2. The message is received in two steps:
• Master task:
< Activate IT task
! Start CTRL 1
< Validate interrupts
! DMASKINT (I 02)
< Set text block TXT6 to receive
! INPUT TXT6
• Interrupt task:
< Read the module interrupt
! READINT (I02;B14)
< If interrupt bit (B14) is present, read the telegram
! IF B14 THEN JUMP L10
< Continue program
! ......
< Read telegram
! L10: READTLG (I02;W45); RESET B14
< Analyze correct read confirm
! IF [W45 = 0] then jump L20
< Process errors (analyze W45)
! [IF W45 = ...] THEN ................................
....................................................................
< Number of bytes received and stored in word W30
! L20: TXT6,S
→
W30
< Process data received
! W50[W2].......
............................................................
48
Page 48 - Recouvrement Noir
Software Installation
2
2.7
PLC Scan Cycle
The diagram opposite shows the
Master task cycle of the PLC where the TSX MAP 1074 module is located.
The only information indicated is that which is absolutely necessary to understand the operation of the TSX MAP 1074 module.
1
Process system bits and words and update them when they are set by the system.
2
Monitor various parameters including the presence of the
TSX MAP 1074 module and if necessary act on the fault bits
Ixy,S; SY10, etc.
3
Write data to memory for the
COM words that have changed in other stations and up to four messages.
4
Execute the user program.
5
Send the COM words assigned to this station that have been changed and up to four messages, to the TSX MAP 1074 module.
1
2
3
4
5
System Management
• Update system bits and
words
• Monitor PLC operation
• Process terminal requests
• Route messages
Input Acquisition
Storage in data memory of data from:
• Intelligent module messages
• Messages and/or COMi,j
• IWi,j
• Input bits I
Program
Processing
Update Outputs
• Write output bits O
• Write OWi,j
• Send Telway messages
and/or COMi,j
• Send messages to intelligent
modules
Important
Each master task cycle can process in transmission and reception:
• COM words (up to 64 max.),
• Up to four messages at peak network load.
The sum total of all input and output messages (COM + TXT, SYS or TLG type text blocks) cannot exceed 200 messages per second.
To avoid overloading the PLC in normal operation, no more than two messages per cycle should be exchanged.
49
Page 49 - Recouvrement Noir
2.8
Multiple Network Configurations
2.8-1 Module Configuration
In a multiple network configuration (Mapway and/or Telway), there are three possible cases:
• The network interface is in a station that is at the end of a network drop (stations
1.a, 1.b, 1.c, 2.b, 2.c, 3.b),
• The network interface is in a station that comprises more than one network interface connected to different networks without being a network bridge (station
1.e/3.a),
• The network interface is in a station that is a network bridge (station 1.d/2.a).
Station
1.a
Station
1.b
Station
1.c
Network 1
N1/N2 Bridge
Station
Network 2
Station
1.d/2.a
Station
1.e/3.a
Network 3
Station
2.b
Station
2.c
Station
3.b
In the first two cases there is no need to configure the network interface modules.
All of the routing information is held by the bridge station on the network to which they are connected.
In the last case (bridge PLC), the network interfaces must be configured.
A network bridge station is configured with PL7-NET software. PL7-NET is an
X-TEL Software Workshop option.
50
Page 50 - Recouvrement Noir
Software Installation
2
The following operations must be performed:
• Description of the entire network layout and entry of the name and number (0 to
H’7F) assigned to each network,
• Selection of the stations that form a network and assignment of station addresses
(0 to H’3F’),
• Network interconnection by selection of bridge PLC stations,
• Assignment in each bridge of modules to the different networks,
• Storage of network layout information on disk. For each bridge, this file contains a complete list of the networks it serves,
• Transfer of this file to all of the bridge stations in the network layout.
For more information on the use of this program, refer to the PL7-NET User's
Manual, TXT DM PL7 NET V4E.
2.8-2 PLC Cycle Time
The master task cycle time of a bridge PLC depends on the type of networks connected (Mapway to Mapway or Mapway to Telway bridge).
Reminders on PLC scan cycles
Input
Acquisition
Cycle
Time
Processing
Output
Updating
Time available for asynchronous messages
(module to module)
51
Page 51 - Recouvrement Noir
Mapway to Mapway bridge PLC
Data routing is performed in the field reserved for the asynchronous message system.
The time reserved for message system processing (message transfer between segments) corresponds to the cycle time less the application program processing time.
To improve performance of a Mapway to Mapway bridge PLC, it must have the following characteristics:
• A long cycle time,
• No sequential processing,
• No COM word management.
Example: A bridge PLC with a 200 ms cycle time and no sequential processing will make approx. 195 ms, or 97% of its cycle time available to message system processing.
Mapway to Telway bridge PLC
Data routing is performed when outputs are updated (synchronous message system) at the rate of one message per cycle.
The time reserved for updating outputs is defined by the PLC system and cannot be modified by the user.
To improve performance of a Mapway to Telway bridge PLC, it must have the following characteristics:
• A short cycle time,
• No sequential processing,
• No COM word management.
Example: A bridge PLC with a 10 ms cycle time and no sequential processing will be able to route a message every 10 ms.
52
Page 52 - Recouvrement Noir
Maintenance
Maintenance
3
Section 3
Sub-section
3.1 Troubleshooting
3.1-1 General
3.1-2 LED Indicators
3.1-3 LED Displays
3.1-4 Troubleshooting Using the LED Indicators and Displays
3.2 Self-Tests and Specific Tests
3.2-1 Starting the Self-Tests
3.2-2 Starting the Specific Tests
3.3 Data-Rate Control
Page
54
54
54
56
57
59
59
60
62
Page 53 - Recouvrement Noir
53
3.1
Troubleshooting
3.1-1 General
The front panel of TSX MAP 1074 modules comprises five indicator LEDs and two seven segment LED displays.
These indicators and displays are used to display important information on the operation of the module and its connection to the Mapway network.
MAP 107
RUN
DEF
INR
RX
TX
3.1-2 LED Indicators
The “RUN” LED
This green LED indicates the general condition of the module. It is lit when the module is operational and active. It is extinguished when the module is not operational.
When the module connects to the network and while the self-tests are in progress, this LED blinks. It remains lit when the self-tests have been successfully completed and during normal module operation. If a fault is detected it is extinguished and inhibits the module from becoming active.
This LED is hardware controlled. It is extinguished by the watchdog, triggered by a module failure.
The “DEF” LED
This red LED lights when a TSX MAP 1074 module fault occurs.
This LED lights briefly when the module is powered-up, it is extinguished when the self-test phase starts. It will only light again if:
• One of the tests performed during the self-test phase detects an error. The error code will be displayed by the seven segment LED displays (refer to sub-section
3.2-1),
• A permanent error is detected during normal operation,
• The TSX MAP ACC1 terminal block is disconnected from the module.
54
Page 54 - Recouvrement Noir
Maintenance
3
This LED is software controlled. When the internal software that controls the module, detects an operating fault that affects proper module operation, it lights the
“DEF” LED. This LED does not automatically light when the “RUN” LED is extinguished.
The “INR” (IN Ring) LED
This yellow LED lights to indicate that the TSX MAP 1074 module is connected to the Mapway network and that it is active in passing the token on the bus.
It lights briefly when the module is powered-up and is extinguished when the selftest phase starts.
The last self-test checks the network, if at least one other station is connected. Once it has done this, it sends an “add station” request so that the newly powered-up module can obtain the token. If it is successful in adding the module to the network, the “INR” LED lights.
If for any reason, the module cannot connect to the network and gain access to the token, the “INR” LED will be extinguished.
This LED is software controlled. As long as it is extinguished, the station cannot send messages, it can only receive them.
Note: If the network number of a station is different than that of the other stations, its “INR”
LED will remain lit (token passing is detected) but it will never be able to send on the network as the token is not addressed to it.
The “RX” and “TX” LEDs
These two yellow LEDs indicate that the TSX MAP 1074 module has detected data reception (RX) or transmission (TX) activity. These LEDs do not indicate token passing or control frames, only data transmission and reception to and from the individual station.
On initialization, these two LEDs light briefly, only to be extinguished by the start of the self-test procedure. They are software controlled.
55
Page 55 - Recouvrement Noir
3.1-3 LED Displays
The TSX MAP 1074 module comprises two seven segment plus decimal point LED displays.
When the module is powered-up a random value will be displayed and immediately cleared.
During the self-test phase, the displays show the number of the test in progress. If a fault is detected, the corresponding error code is displayed by the LEDs and the
“DEF” LED is lit.
Once the self-tests have been completed successfully, the LEDs alternately display the network and station number of the module. The number of the network that the module is connected to is displayed first, with a decimal point in the lower right of the display. The station number assigned to the module is also displayed, without the decimal point.
In normal operation, the LEDs display the network address of the station as network number followed by the station number.
The station address display alternates cyclically over a period of approx. two seconds. This sequence allows network diagnostics in Local mode. A check can be performed to ensure that the network and station numbers are set correctly in the
TSX MAP ACC1 terminal block.
As soon as a fault is detected during normal module operation, the “DEF” LED lights and the LEDs display the appropriate error code.
56
Page 56 - Recouvrement Noir
Maintenance
3
3.1-4 Troubleshooting Using the LED Indicators and Displays
The combined use of the indicator and display LEDs will identify a number of operating faults and their causes.
The table below lists the main faults that can be detected and the remedial action that should be taken.
Before taking any action, the module should first be disconnected, reconnected and reinitialized to ensure that the fault persists.
Indicators
RUN
Probable Causes
• LED failure
• Power supply failure
Remedial Action
• Check supply to the station
• Change the power supply module
DEF
INR
• Self-test fault ( * ) • Refer to the error code displayed
RUN
DEF
• Permanent fault
(
*
)
INR
RUN
DEF
INR
• Terminal block absent ( ** )
• Fault identified by an error code displayed
• Fit the terminal block
• Refer to the error code displayed
RUN
DEF
INR
• Terminal block address error • Check the coding in the terminal code block
• Station excluded from the logical ring
• Check network status
• Network failure
• PLC not connected • Check the PLC
RUN
DEF
INR
RUN
DEF
• Normal display during normal module operation
INR
(
*
)
Error code displayed;
(
**
)
“Eb” displayed
Note: The “TX” and “RX” LEDs are not shown in the above table as they are not used for troubleshooting the module.
57
Page 57 - Recouvrement Noir
List of error codes (other than self-test error codes)
If a fault is detected during normal operation or when a specific test is run (refer to sub-section 3.2), one of the values shown in the list below will be displayed.
Error code
20
21
22
23
31
41
42
51
Eb
Fault Remedial Action
LCC initialization error
(resource allocation, self-tests).
Reset the PLC (SY0 = 1).
Problem detected in normal operation Reset the PLC (SY0 = 1).
(e.g. invalid data).
Address duplicated on the same network.
Modem problem
Change the station code set in the terminal block.
Check that the module is correctly installed and its mounting screws tight.
Reset the PLC (SY0 = 1) or cold restart.
Change the module.
Initialization problem during initialization phase.
Initialization problem in the COM protocol.
COM word reconfiguration problem
Change the module.
Change the module.
Change the module.
Initialization problem in the
TSX Series 7 protocol.
Terminal block absent.
Fit the terminal block.
58
Page 58 - Recouvrement Noir
Maintenance
3
3.2
Self-Tests and Specific Tests
3.2-1 Starting the Self-Tests
Each time it is powered-up, the TSX MAP 1074 module runs a self-test sequence that comprises:
• Module micro-program checksum,
• Checking the RAM memory assigned to the microprocessor,
• Checking the logic of the shared memory used to exchange data with the PLC,
• Inserting the station into the network logical ring and token passing. Sending test frames to the previous and next stations on the network.
The self-tests are triggered after the coded value (network and station numbers) is acquired by the TSX MAP ACC1 terminal block.
While the self-tests are in progress, the numbers of the individual tests in progress are displayed on the seven segment LED displays.
If the self-tests are completed successfully, the module becomes active and the
“RUN” and “INR” LEDs are lit.
Any fault that is detected is indicated by the “DEF” LED. The fault code is displayed on the seven segment LED indicators.
List of self-tests
There are eight classes of self-tests shown as “X_.” on the LED displays (X takes a value from 1 to 8).
Normally, the number of each class of test will be displayed as the tests are performed. If a fault is detected, the complete two figure error code will be displayed.
The table below shows the complete list of errors with the values displayed during a normal test sequence.
Value displayed
1_.
2_.
3_.
4_.
5_.
6_.
7_.
8_.
Self-tests
Minimal self-test.
PLC bus interface (SMU) test.
PLC bus shared RAM test.
System ROM checksum test.
I/O Test.
Token Bus Controller (TBC) test.
Interrupt test.
Network test.
59
Page 59 - Recouvrement Noir
3.2-2 Starting the Specific Tests
The TSX MAP 1074 module comprises a system that supports the running of specific tests for maintenance purposes. The tests can be selected from the four thumbwheel switches in the TSX MAP ACC1 terminal block.
On power-up, the value coded in the terminal block is read. If the value corresponds to a network and station number, the module runs the self-test sequence and if it is successful, starts normal operation. If the value corresponds to a specific self-test, as listed overleaf, the module will run the corresponding test.
If the specific test runs correctly, the module loops back to the start of the test and runs it again. If the test is stopped before completion, the “DEF” LED will light and the LED displays will display a test number. The tests are listed overleaf.
Specific test coding
The tests are run after the “STAT” thumbwheel switches have been set to a value listed overleaf. The “NET” thumbwheel switches must be set to H’FF’.
60
Page 60 - Recouvrement Noir
Maintenance
3
“STAT” Setting
FF
FE
FD
FC
F7
F6
F5
F4
FB
FA
F9
F8
F3
F2
F1
F0
EF
EE
ED
EC - E1
E0
DF - 80
7F - 40
3F - 00
Test Selected
Continuous self-tests
80186 register test
512 KB RAM test
Reserved
PLC bus register test
32 KB PLC bus interface RAM test
256 KB checksum ROM test
ROM type test
Indicator LED test
7 segment LED display test
Status test
Timer interrupt test
Direct memory access interrupt test
PLC bus interrupt test
Reserved
Token Bus Controller interrupt test
Token Bus Controller reset init test
CPU Token Bus Controller interface test
Token Bus Controller loopback mode test
Reserved
Permanent network test
Reserved
Reserved
Station Number
Error codes
If a fault is detected by a specific test, an error code is displayed by the module. The list of error codes is the same as that given in sub-section 3.2-1.
61
Page 61 - Recouvrement Noir
3.3
Data-Rate Control
Sending a text block changes the state of bits TXTi,D and TXTi,E. The possible values that these bits can take are:
Bit TXTi,D
0
1
1
0
Bit TXTi,E
0
0
1
1
Description
Exchange in progress
Exchange ended without error or no exchange
Exchange ended on error
Exchange not ended, exchange initially started on error
Power break or target disconnection
When a text block wired for EXCHG (or with inputs S, I and O at 1) sends a request, it is set to await a response and waits until it receives one. If a power failure occurs, or if the target station is disconnected, the source text block remains inhibited.
There are two possible cases:
Power break or target station disconnected during the exchange
Bits TXTi,D and TXTi,E remain at 0,
The application program of the source must take this case into account by including a “time-out” in the use of the source text block.
If no response is received before the time-out, then the text block should be reset to zero (Reset TXTi).
Power supply fault or disconnection of the target station before the exchange is started
The text block is set to error, bits TXTi,D and TXTi,E are set to 1 and the status word
TXTi,S takes the value 3.
62
Page 62 - Recouvrement Noir
Technical Specifications
4
Technical Specifications
Section 4
Sub-section
4.1 Performance
4.1-1 Application-to-Application Transfer Time
4.1-2 Telegram Transfer Time
4.1-3 Request Transaction Time
4.1-4 Uploading Application Programs
4.1-5 Mapway-Mapway Bridge Processing Time
4.1-6 Mapway-Telway Bridge Processing Time
Page
64
64
66
68
70
72
72
Page 63 - Recouvrement Noir
63
4.1
Performance
4.1-1 Application-to-Application Transfer Time
AAT: is the Application-to-Application Transfer time. This is the elapsed time from the moment a message is sent by the source station (START TXTi) till the moment it is received by the destination station (DONE bit processed by the application program).
Example
TXT
"Start TXTi"
Start TXTi
TC1 TC1
CPL S
TXT
TXTj,D = 1
MPW
CPL D
TC2 TC2
DONE is accepted
AAT
TC1 Source PLC cycle time,
TC2 Destination PLC cycle time,
CPL S Source PLC TSX MAP 107 module transmission processing time,
MPW Mapway network transit time,
CPL D Destination PLC TSX MAP 107 module transmission processing time.
64
Page 64 - Recouvrement Noir
Technical Specifications
4
The diagram below shows the application-to-application transfer time depending on the cycle time of the source PLC and the network load factor:
AAT
(Typical)
(ms)
300
A
B
200
100
25 50 100 150 (ms)
PLC
Cycle time
(TC1 = TC2)
A Heavily loaded network (network cycle time = 30 ms),
B Lightly loaded network (network cycle time = 2 ms),
The application-to-application transfer time varies only slightly due to the network load factor. It depends essentially on the cycle time of the two PLCs connected. If their cycle times are the same, the average application-toapplication transfer time is 1.5 times the cycle time.
65
Page 65 - Recouvrement Noir
4.1-2 Telegram Transfer Time
TTT: The Telegram Transfer Time is the time that elapses between telegram transmission by the source station (OUTPUT TXTi) and telegram reception by the interrupt task of the destination station (DONE bit accepted by the application program).
Example
TXT
Output TXTi
TC1
"Output TXTi"
CPL S
TC1
MPW
TXT
TXTj,D = 1
CPL D
TTT
TC2
IT
TC2
Process "DONE" bit
TC1
Source PLC cycle time,
TC2
Destination PLC cycle time,
CPL S Source PLC TSX MAP 1074 module transmission processing time,
MPW
Mapway network transit time,
CPL D Destination TSX MAP 1074 module transmission processing time,
IT
Interrupt task processing time.
66
Page 66 - Recouvrement Noir
Technical Specifications
4
The diagram below shows telegram transfer time depending on network cycle time:
TTT
(Typical)
(ms)
30
20
10
2 10 20
Network cycle time
30
(ms)
Page 67 - Recouvrement Noir
67
4.1-3 Request Transaction Time
RTT: The Uni-TE Request Transaction Time is the time that elapses between transmission of a request and processing, by the source, of the confirm that is sent back.
Example
TXT
Start TXTi
Confirm
System
TC1
"Start TXTi"
TC1
CPL S
MPW
CPL D
TC2 TC2
CPL D
MPW
CPL S
TC1 TC1
Confirm processing
RTT
TC1
TC2
Source PLC cycle time,
Destination PLC cycle time,
CPL S Source PLC TSX MAP 1074 module transmission processing time,
MPW Mapway network transit time,
CPL D Destination PLC TSX MAP 1074 module transmission processing time.
68
Page 68 - Recouvrement Noir
Technical Specifications
4
The diagram below shows the request transaction time depending on the cycle time of the source PLC and the network load factor:
RTT
(Typical)
(ms)
A
B
500
400
300
200
100
25
50 100
150 (ms)
PLC
Cycle time
(TC1 = TC2)
A
B
Heavily loaded network (network cycle time = 30 ms),
Lightly loaded network (network cycle time = 2 ms),
The request transaction time varies only slightly due to the network load factor.
It depends essentially on the cycle time of the two PLCs connected. If their cycle times are the same, the average request transaction time is 3 times the cycle time.
69
Page 69 - Recouvrement Noir
4.1-4 Uploading Application Programs
PLT: Program Load Time is the time required to upload (or download) an application program via Mapway (upload and receive confirm). It depends on the size of the program to be transferred. The transfer time will therefore be almost entirely unaffected by the network load factor.
Example
Once logical connection is established, the cycle shown below applies to each program segment of 128 bytes.
IBM PC
Upload
Confirm
CPL S
MPW
CPL D
PLC
CPL D
MPW
CPL S
PLT
CPL S Source PLC TSX MAP 1074 module transmission processing time,
MPW Mapway network transit time,
CPL D Destination PLC TSX MAP 1074 module transmission processing time,
PLC The transfer time to the PLC of the destination station, with PLC stopped.
Note: If the FTX 507 is connected to the terminal port of a PLC, the following times must be added to the times shown above:
• Transfer time between workstation and PLC (typically one second per K byte),
• The PLC processing time (typically 2.5 times the cycle time).
70
Page 70 - Recouvrement Noir
50
40
30
20
10
Technical Specifications
4
The diagram below shows the time required to upload an application program over a heavily loaded Mapway network (network cycle time = 20 ms) depending on the size of the program:
PLT
(Typical)
(sec)
60
10 50 100
Program size
(K bytes)
The application program upload (or download) transfer time is increased considerably when the terminal is not directly connected via an interface to the
Mapway network.
This time only varies slightly depending on the network load.
71
Page 71 - Recouvrement Noir
4.1-5 Mapway-Mapway Bridge Transit Time
MMB: Is the time taken by a message to move from one network to another. It depends on the
TSX MAP 1074 module processing time and on the time required by the bridge PLC processor to route the message.
Network 1
TSX MAP 1074
PLC
TSX MAP 1074
Network 2
The Mapway-Mapway bridge transit time is approx. 20 ms for 128 characters.
4.1-6 Mapway-Mapway Bridge Transit Time
MTB: Is the time taken by a message to move from a Mapway network to a Telway network or vice versa. It depends on the TSX MAP 1074 module processing time and on the time required by the bridge PLC processor to route the message.
Network 1
TSX MAP 1074
PLC
TSX MPT 10
Network 2
The Mapway-Telway bridge transit time is usually 1,5 times the PLC cycle time for each message.
72
Page 72 - Recouvrement Noir
Appendix
Sub-section
5.1 Module Design
5.1-1 Software Design
5.1-2 Hardware Design
5.2 TSX Series 7 V3 PLC Special Points
5.3 Uni-TE Read Requests
5.3-1 Read a Bit
5.3-2 Read a Word
5.3-3 Read Objects
5.3-4 Read a System Bit
5.3-5 Read the Memory Image of an I/O Bit
5.3-6 Read a Constant Word
5.3-7 Read a System Word
5.3-8 Read a COM Word
5.3-9 Read a Timer
5.3-10 Read a Monostable
5.3-11 Read a Counter
5.3-12 Read a Register
5.3-13 Read Grafcet Steps
5.3-14 Read a Double Word
5.3-15 Read a Constant Double Word
5.3-16 Read a Grafcet Step
5.4 Uni-TE Write Requests
5.4-1 Write a Bit
5.4-2 Write a Word
5.4-3 Write Objects
5.4-4 Write a System Bit
5.4-5 Write the Memory Image of an I/O Bit
5.4-6 Write a System Word
5.4-7 Write a COM Word
5.4-8 Write a Timer Preset
5.4-9 Write a Monostable Preset
5.4-10 Write a Counter Preset
5.4-11 Write a Register Input Word
5.4-12 Write a Double Word
5.4-13 Run
5.4-14 Stop
Appendix
5
Section 5
Page
74
74
77
78
80
90
91
92
93
94
95
96
85
87
88
89
80
81
82
84
97
98
98
99
100
102
103
104
105
106
107
108
109
110
111
112
73
5.1
Module Design
5.1-1 Software Design
The diagram below shows the software design layout and the various functions of a Mapway network module.
SMU Driver
VTOS
TSX
Series 7
Uni-TE
COM
Init
Tests
VTOS
Loader
Bridge
SMAP
NMA
LLC Class 3 Interface
TBC Driver
Definition of the Main Functions
Virtual Time Operating System (VTOS)
This is the real-time core that is used for:
• Executing the tasks in a multi-task environment,
• Communication between tasks using mailboxes and ports,
• Allocating and releasing the memory and the interrupts.
BUS Driver
This function ensures the control of communication between the PLC and the device. When a Telemecanique PLC is used, this function is designed as a driver for the PLC bus interface (SMU) and a SMU access interface that can be accessed by application services. This function controls three simultaneous communication channels: A synchronous COM channel, a synchronous and an asynchronous message channel (synchronization is ensured by the PLC cycle).
74
Appendix
5
COM
This function controls the service that exchanges COM words over the network. It ensures the periodical transmission of a list of words initiated by the PLC processor.
It provides a copy of the entire COM word field on each PLC cycle. An important part of this function is delegated to the SMU driver: control of a COM word communication memory channel between the network module and the PLC processor. The
COM word function also interfaces with the LLC service (described below).
TSX Series 7
This is the specific Telemecanique network service. This function sends TSX Series 7 datagrams (text blocks, Uni-TE requests, program, adjust and debug requests, etc.) to the destination station on the network. It also receives datagrams from the network and transmits them to the PLC processor via the SMU driver. In addition, this function receives configuration or control requests that are redirected to the
SMAP function that handles them (described below).
The TSX Series 7 service comprises a specific LOC-DIAG function that provides an overview of network control via the Uni-TE service and application protocol. Only some data objects are accessible by the LOC-DIAG service. This service converts some Uni-TE requests from the SMU into SMAP requests or responds instantly to other requests. In the other direction, SMAP responses are converted back using the Uni-TE protocol and sent back to the SMU.
System Management Access Protocol (SMAP)
This function controls all of the network functions that are distributed to the module.
SMAP also communicates with a network control server called Network Management Agent (NMA). In order to respond to requests from the NMA, SMAP interfaces directly with each function in the module.
Logical Link Control (LLC)
This function implements the interface with the IEEE 802.2 Class 3 LLC and the
IEEE 802.4 MAC sub-layer driver.
Init and Tests
This function performs two functions:
• Starting VTOS and any other Mapway program in order to end the self-tests,
• Synchronizing the changeover of the program from idle to running once the selftests have been completed successfully. It is also used to share common resources such as structures and common addresses.
This service also controls the LED indicators and the seven segment LED displays on the front panel of the TSX MAP 1074 module.
75
VTOS Loader
This module function is used to load a process into the RAM of the network interface.
This process can be performed in addition to, or in place of an existing interface process.
The VTOS Loader process normally interfaces directly with the SMU. In MAP network interfaces, an additional interface is built-in and this is accessed by the LLC for loading by the network.
Note: Mapway network interfaces are designed for future software extensions, and in particular MAP 3.0.
76
Appendix
5
5.2-2 Hardware Design
The design of the TSX MAP 1074 module is shown in the diagram below:
20 MHz.
Clock
80186
CMOS
M-Proc.
Local M-Proc. bus
I/F
Bus
(SMU)
PLC
Bus
256 K x 4
DRAM
DRAM
32 K Backed-up RAM
M-Proc.
TBC
I/F
128 K x 8
EPROM
EPROM
TBC
(68824)
I/O
Displays
LEDs
Addresses
Standard 802.4/G interface
Modem
Transformer
0 Type F connector
5 V Power consumption: 1.3 A Typical
1.6 A Maximum
77
5.2
TSX Series 7 V3 PLC Special Points
TSX Series 7 V3 PLCs (TSX 47-31, TSX 67-21 and TSX 87-31) have certain slight functional differences compared to TSX Series 7 Model 40 PLCs. A brief summary of these differences is given below.
Number of modules
• Only one Mapway or Telway module is allowed in each rack.
TSX Series 7 V3 PLC cannot therefore be used as bridge stations between networks but can be connected to a multiple network layout.
COM word service
• The COM word service (in transmission and reception) is restricted to stations with addresses from H’00' to H’0F’.
• COM size is restricted to four words per station. (A TSX Series 7 V3 station therefore imposes a four COM word size on all stations connected to the same network as itself).
• The update and transfer of all COM words is performed at the end of each master task cycle.
• When a module is configured, its activity (in read and write) in relation to COM words can be inhibited or enabled.
• Only system bits SY11 and SY12 are used (with the same functions as TSX Series 7
Model 40 PLCs).
• System words SW65 to SW99 do not apply. Two new system words are used however:
System word
SW0
SW2
Function Description
Update COM words
Each bit in this word (0 to F) represents a station on the network (0 to 15). A bit at 1 shows that the corresponding station has sent its COM words.
It is up to the user to reset this word to zero (by program).
Mapway station This word gives the decimal station number number coded in the TSX MAP ACC1 Mapway module terminal block.
78
Appendix
5
Uni-TE Service
• The Uni-TE service is identical to the one supported by TSX Series 7 Model 40
PLCs.
• The circular byte shift left instruction:
SLCWORD(Source;Length) is not supported. When the "read objects" request
(H’36') is used, shifting of data received can only be performed by program.
Application-to-application communication
• This service is identical to the one supported by TSX Series 7 Model 40 PLCs.
Priority communication - Telegram
• TSX Series 7 V3 PLC do not support this service.
79
5.3
Uni-TE Read Requests
5.3-1 Read a Bit
This request reads the value of a bit (0 or 1) and whether it is forced or not.
Request format
Request
Code
Hex.
Category
Code
Bit
Number
00/00
Confirm format
Positive confirm
Confirm
Code
Hex.
Value Forcing
30/48
Value:
Forcing:
An 8-bit string where the address of the first bit is the highest multiple of 8 contained in the bit number to be read (modulo 8).
An 8-bit value used as a forcing indicator for the 8 “value” bits:
• 1 if the bit is forced, the forced value is in the value bit,
• 0 if the bit is not forced.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Address out of range.
80
5.3-2 Read a Word
This request reads a word (W).
Request format
Request
Code
Hex.
Category
Code
Word
Number
04/04
Confirm format
Positive confirm
Confirm
Code
Hex.
Value
34/52
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Address out of range.
Appendix
5
81
5.3-3 Read Objects
This request reads of simple objects (words or bit strings etc.).
Request format
Request
Code
Hex.
Category
Code
Segment
Type of
Object
Object
Address
Number of
Objects to Read
36/54
Segment:
Type of object:
Object address:
Specifies the addressing mode used for the objects to be read and the position where they are located (in hexadecimal notation).
The segments accessible by TSX Series 7 PLCs are (in hexadecimal):
10: Common object space segment,
68: Internal word space segment,
69: Constant word space segment,
6C: Ctrl. user task space segment,
80: TSX Series 7 system object space segment.
Specifies the type of object to read:
7: 16-bit signed integer,
8: 32-bit signed integer,
64: Task period.
• The physical or logical address in the segment,
• The sequence number of the object in the segment:
• 0: Current date and time, in the common segment,
• 1: Stored time and date, in the common segment,
• 0: Programming port configuration in the system segment.
Confirm format
Positive confirm
Confirm
Code
Hex.
Type of
Object
66/102
Type of object:
Data
Returns the type of object selected when the request is sent.
82
Appendix
5
Read objects (contd)
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Unknown segment or object,
• Address out of range,
• Too many objects for the reception buffer.
Request Examples
Read words or double words
Segment: 68,
Type of object: 7
→
Wi, or 8
→
DWi,
Object address: index of the first Wi or DWi to read.
Read constant words or constant double words
Segment: 69,
Type of object: 7
→
CWi, or 8
→
CDWi,
Object address: index of the first CWi or CDWi to read.
Read Date and Time
Segment: 10 (common),
Type of object: 0 by default,
Object address: 0
→ current time and date,
1
→ saved time and date,
Quantity: 0 by default.
Read programming port configuration
Segment: 80 (TSX Series 7 system),
Type of object: 0 by default,
Object address: 0
→ programming port configuration,
Quantity: 0 by default.
Read task period
Segment: 6C (Ctrl),
Type of object: 64 (task period),
Object address: 2
→
Fast task,
3
→
Master task,
4
→
Auxiliary task 0,
5
→
Auxiliary task 1,
6
→
Auxiliary task 2,
7
→
Auxiliary task 3,
Quantity: 0 by default.
83
5.3-4 Read a System Bit
This request reads a system bit SY.
Request format
Request
Code
Hex.
Category
Code
System
Bit
Number
01/01
Confirm format
Positive confirm
Confirm
Code
Hex.
Value
31/49
Value: An 8-bit string, where the address of the first bit is the highest multiple of 8 contained in the system bit number to be read
(modulo 8).
Only the bit corresponding to the bit to be found is significant.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Bit number out of range.
84
Appendix
5
5.3-5 Read the Memory Image of an I/O Bit
This request reads the memory image generated by an I/O module.
Request format
Request
Code
Hex.
Category
Code
I/O Module
Location
02/02
Module location: bit 0
→
2: Module number, bit 3
→
6: Rack number, bits 7
→
15: Reserved (0).
Confirm format
Positive confirm
Confirm
Code
Hex.
Fault
Code
Configuration
32/50
Fault Code:
Configuration:
Value:
Value Forcing
Bit 7 = Fault: (0 = no, 1 = yes),
Bits 6 to 4 = 0,
Bits 0 to 3 = Type of fault:
0000: OK,
0001: Terminal block or process fault,
0010: Module absent,
0011: Module failure,
0100: Not an I/O module,
0101: Incompatible with configuration,
0110: Not configured,
0111: Self-test error.
bit 7: Configuration exists (0 = no, 1 = yes), bit 6: Defined type (0 = no, 1 = yes), bits 0 to 5: if type = 1
→ catalog type number, if type = 0
→ default type number.
The value of the module I/O bits. If an 8-bit module is used, the MSB contains null values that are not significant. “Value” is only significant if the fault bit = 0 (bit 7) and the configuration bit = 1 (bit 7).
85
Read the Memory Image of an I/O Bit (contd)
Forcing: Status of forcing:
• 0: The bit is not forced,
• 1: The bit is forced, its forcing state is displayed in the
“value” parameter.
Negative confirm
Confirm
Code
Hex.
FD/253
Reasons for rejection:
• Unknown request,
• Inadequate access rights,
• Module number out of range.
86
5.3-6 Read a Constant Word
This request reads constant words (CW).
Request format
Request
Code
Hex.
Category code
Word
Number
05/05
Confirm format
Positive confirm
Confirm
Code
Hex.
Value
35/53
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range.
Appendix
5
87
5.3-7 Read a System Word
This request reads system words (CW).
Request format
Request
Code
Hex.
Category
Code
Word
Number
06/06
Confirm format
Positive confirm
Confirm
Code
Hex.
Value
36/54
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range.
88
5.3-8 Read a COM Word
This request reads a COM (common) word.
Request format
Request
Code
Hex.
Category
Code
Station
Number
07/07
Word
Number
Confirm format
Positive confirm
Confirm
Code
Hex.
Station
Size
37/55
Value
Station size:
Negative confirm
Confirm
Code
Hex.
The number of COM words generated.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range,
• RAM cannot be executed,
• Station number out of range.
Appendix
5
89
5.3-9 Read a Timer
This request reads all of the parameters of a timer.
Request format
Request
Code
Hex.
Category
Code
Time
Number
09/09
Confirm format
Positive confirm
Confirm
Code
Hex.
Time
Base
Timer
Timed-out
Timer
Running
Type of
Preset
39/57
Time base:
Timer timed-out:
Timer running:
Type of preset:
Preset
Value
Current
Value
0
→
10 ms
1
→
100 ms
2
→
1 sec.
3
→
1 min.
0
→ no
1
→ yes
0
→ no
1
→ yes
0
→ preset cannot be modified,
1
→ preset can be modified.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Timer number out of range,
• RAM cannot be executed.
90
5.3-10 Read a Monostable
This request reads all of the parameters of a monostable.
Request format
Request
Code
Hex.
Category
Code
Monostable
Number
0A/10
Confirm format
Positive confirm
Confirm
Code
Hex.
Time
Base
Monostable
Running
Type of
Preset
Preset
Value
Current
Value
3A/58
Time base: 0
→
10 ms
1
→
100 ms
2
→
1 sec.
3
→
1 min.
Monostable running: 0
→ no
1
→ yes
Type of preset: 0
→ preset cannot be modified
1
→ preset can be modified
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Monostable number out of range,
• RAM cannot be executed.
Appendix
5
91
5.3-11 Read a Counter
This request reads all of the parameters of a counter.
Request format
Request
Code
Hex.
Category
Code
Counter
Number
0B/11
Confirm format
Positive confirm
Confirm
Code
Hex.
Downcount
Overflow
Upcount
Overflow
Counter
Running
Type of
Preset
Preset
Value
Current
Value
3B/59
Downcount overflow: 1 if the current counter value has gone from 0 to 9999,
Upcount overflow: 1 if the current counter value has gone from 9999 to 0,
Counter running:
Type of preset:
0
→ no,
1
→ yes,
0
→ preset cannot be modified,
1
→ preset can be modified.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Counter number out of range,
• RAM cannot be executed.
92
5.3-12 Read a Register
This request reads all of the parameters of a register.
Request format
Request
Code
Hex.
Category
Code
Register
Number
0E/14
Confirm format
Positive confirm
Confirm
Code
Hex.
Register
Type
Register
Empty
Register
Full
3E/62
Register
Length
Input
Word
Register type:
Register empty:
Register full:
0 = FIFO register,
1 = LIFO register,
0
→ no,
1
→ yes,
0
→ no,
1
→ yes.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Register number out of range,
• RAM cannot be executed.
Output
Word
Appendix
5
93
5.3-13 Read Grafcet Steps
This request reads the Grafcet step activity bits (Xi).
Request format
Request
Code
Hex.
Category
Code
Portion
Number
2A/42
Portion number: 0 = portion [X0•••••X127],
1 = portion [X128•••••X255],
2 = portion [X256•••••X383],
3 = portion [X384•••••X511].
Confirm format
Positive confirm
Confirm
Code
Hex.
5A/90
Register type:
Data
A succession of 128 bits corresponding to the step number in the selected portion: bit i = 0: step Xi inactive, bit i = 1: step Xi active.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Portion number out of range,
• No reservation.
94
5.3-14 Read a Double Word
This request reads a double word (DW).
Request format
Request
Code
Hex.
Category
Code
Double Word
Number
40/64
Confirm format
Positive confirm
Confirm
Code
Hex.
Double Word
Value
70/112
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range,
• Odd word number.
Appendix
5
95
5.3-15 Read a Constant Double Word
This request reads a constant double word (CDW).
Request format
Request
Code
Hex.
Category
Code
Constant Double
Word Value
41/65
Confirm format
Positive confirm
Confirm
Code
Hex.
Constant Double
Word Value
71/113
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range,
• Odd word number.
96
Appendix
5
5.3-16 Read a Grafcet Step
This request reads the state of a Grafcet step.
Request format
Request
Code
Hex.
Category
Code
Type of
Number
Reserved
Macro-
Step
Number
Step
Number
4B/75 00
Type of step:
Macro step nbr.:
Step nbr.:
0: Grafcet step,
1: Macro-step,
2: Macro-step entry step,
3: Macro-step exit step,
4: Macro-step step.
Comprises the number of the required macro-step or 0 if the step type is 0.
Comprises the number of the required step or 0 if the step type is 1, 2 or 3.
Confirm format
Positive confirm
Confirm
Code
Hex.
Active
Step
Not Used Not Used Inhibited
7B/123
Active step:
Inhibited step:
00 00 00
0
→ no,
1
→ yes,
0
→ no,
1
→ yes.
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Step number out of range.
97
5.4
Uni-TE Write Requests
5.4-1 Write a Bit
This request sets a bit to 1 or to 0.
Request format
Request
Code
Hex.
Category
Code
System Bit
Number
Bit
Value
10/16
Bit value: 0
→ state 0,
1
→ state 1.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Bit number out of range.
98
5.4-2 Write a Word
This request writes the content of a word.
Request format
Request
Code
Hex.
Category
Code
Word
Number
Word
Value
14/20
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range.
Appendix
5
99
5.4-3 Write Objects
This request writes simple objects (words, word strings, etc.).
Request format
Request
Code
Hex.
Category code
Segment
Type of
Object
Object
Address
Number of
Objects to Write
37/55
Segment:
Type of object:
Object address:
Data
Specifies the addressing mode and the addressing field (in hexadecimal):
10: Common object space segment,
68: Internal word space segment,
69: Constant word space segment,
6C: Ctrl user task space segment,
80: TSX Series 7 system object space segment.
Specifies the object to write:
7: 16-bit signed integer,
8: 32-bit signed integer,
64: Task period.
• The physical or logical address in the segment,
• The sequence number of the object in the segment:
• 0: Current date and time, in the common segment,
• 1: Programming port configuration in the system segment.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
100
Appendix
5
Write Objects (contd)
Negative confirm (contd)
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Unknown object,
• Address of the last object out of range.
Request Examples
Write words or double words
Segment: 68,
Type of object: 7
→
Wi or 8
→
DWi,
Object address: Index of the first Wi or DWi to write,
Quantity: Number,
Data: Table of n objects,
Write constant words or constant double words
Segment: 69,
Type of object: 7
→
CWi or 8
→
CDWi,
Object address: Index of the first CWi or CDWi to write,
Quantity:
Data:
Number,
Table of n objects,
Write Date and Time
Segment: 10 (common),
Type of object: 0 by default,
Object address: 0
→ current time and date,
Quantity: 0 by default,
Data: 17 ASCII characters that contain the time and date information:
YYYYMMDDHHMMSS.TZ
(T: tenths of a second, Z: trailer).
Write programming port configuration
Segment: 80 (TSX Series 7 system),
Type of object: 0 by default,
Object address: 0
→ programming port configuration,
Quantity:
Data:
0 by default,
1 byte that describes the new configuration.
Write task period
Segment: 6C (Ctrl),
Type of object: 64 (task period),
Object address: 2
→
Fast task,
3
→
Master task,
4
→
Auxiliary task 0,
5
→
Auxiliary task 1,
6
→
Auxiliary task 2,
7
→
Auxiliary task 3,
Quantity: 0 by default,
Data: New task period within the time base allowed for each task.
101
5.4-4 Write a System Bit
This request writes a system bit SY...
Request format
Request
Code
Hex.
Category
Code
System Bit
Number
Value
11/17
Value: 0 or 1.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Bit number out of range.
102
Appendix
5
5.4-5 Write the Memory Image of an I/O Bit
This request writes the memory image of an I/O module. As memory image processing is used, no check is made to ensure that the module exists or is operating correctly.
Request format
Request
Code
Hex.
Category
Code
I/O Module
Location
I/O
Bit
Number
Value
12/18
Module location:
I/O Bit number:
Value:
Bit 0 to 2: Module number,
Bit 3 to 6: Rack number,
Bits 7 to 15: Reserved (0).
0 to 7: For an 8-bit module,
0 to F: For a 16-bit module.
0 or 1.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• I/O module number out of range,
• I/O bit number out of range.
103
5.4-6 Write a System Word
This request writes a system word (SW..).
Request format
Request
Code
Hex.
Category
Code
System Word
Number
Value
15/21
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• System word number out of range.
104
5.4-7 Write a COM Word
This request writes a COM (common) word.
Request format
Request
Code
Hex.
Category
Code
Station
Number
COM Word
Number
Value
16/22
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range,
• RAM cannot be executed.
Appendix
5
105
5.4-8 Write a Timer Preset
This request writes the preset value of a timer (T) if it can be modified.
Request format
Request
Code
Hex.
Category
Code
Timer
Number
Preset
Value
17/23
Preset value: Between 0 and 9999 (H’00' to H’270F’ inclusive).
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Timer number out of range,
• Preset cannot be modified,
• Preset value out of range,
• Cannot execute RAM.
106
Appendix
5
5.4-9 Write a Monostable Preset
This request writes the preset value of a monostable (M), if it can be changed.
Request format
Request
Code
Hex.
Category
Code
Monostable
Number
Preset
Value
18/24
Preset Value: Between 0 and 9999 (H’00' to H’270F’) inclusive.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Monostable number out of range,
• Preset cannot be changed,
• Preset value out of range,
• Cannot execute RAM.
107
5.4-10 Write a Counter Preset
This request writes the preset value of a counter (C).
Request format
Request
Code
Hex.
Category
Code
Counter
Number
Preset
Value
19/25
Preset Value: Between 0 and 9999 (H’00' to H’270F’) inclusive.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Counter number out of range,
• Preset cannot be modified,
• Preset value out of range,
• Cannot execute RAM.
108
5.4-11 Write a Register Input Word
This request writes a register input word (R).
Request format
Request
Code
Hex.
Category
Code
Number
Register
Input Word
Value
1A/26
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Register number out of range.
Appendix
5
109
5.4-12 Write a Double Word
This request writes a double word (DW).
Request format
Request
Code
Hex.
Category
Code
Double Word
Value
Double Word
Value
46/70
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• Word number out of range,
• Odd word number.
110
Appendix
5
5.4-13 Run
This request sets a device to Run.
Request format
Request
Code
Hex.
Category
Code
24/36
Attention:
Depending on the type of device, prior reservation may be required.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• No reservation.
111
5.4-14 Stop
This request stops a device.
Request format
Request
Code
Hex.
Category
Code
25/37
Attention:
Depending on the type of device, prior reservation may be required.
Confirm format
Positive confirm
Confirm
Code
Hex.
FE/254
Negative confirm
Confirm
Code
Hex.
FD/253
Causes for rejection: • Unknown request,
• Inadequate access rights,
• No reservation.
112