HyQuest Solutions iCE3 FX cellular network devices Basic User Guide
Below you will find brief information for iCE3 FX. This device enables wireless communication with equipment over a 3G network. It's ideal for interfacing with dataloggers, PLCs, and migrating legacy dial-up telemetry to cost-effective wireless IP communications. The iCE3 FX allows for data logging, alarm processing, and supports both static and dynamic IP addressing, SMS, and FTP. It's a self-contained, low-power solution for various telemetry applications.
Advertisement
Advertisement
iCE
3
FX
Basic User Guide
For Software
Version: 1.30
(Requires Firmware
Version: Vy/1.50)
Amendments
Revision History
Issue 1 Version 1.00 2 nd
Dec 2013 Preliminary release of Basic User Guide.
Adapted from the iCE
3
3G Reference Guide V2.80.
Issue 2 Version 1.20 25 th
June 2014 Added iLink 2012 configuration menu options.
Issue 3 Version 1.30 3 rd
Dec 2014
Disclaimer
Under no circumstances will HyQuest Solutions (NZ) Ltd be liable or responsible for any consequential damage or loss that may arise from the use of this product.
All examples and diagrams shown in this manual and any supplied configuration examples are intended as a guide to understanding this product, not to guarantee operation. HyQuest Solutions (NZ) Ltd accepts no responsibility for use of this product based on this information or these examples. Owing to the wide variety of possible applications of this product, you must satisfy yourself as to its suitability to your specific application.
© 2007-2014, HyQuest Solutions (NZ) Ltd. All rights reserved.
This publication, or any part of it, and any software accompanying it may not be copied, photocopied, reproduced, translated or communicated to any third party, or reduced to electronic medium without prior written permission from HyQuest Solutions (NZ) Ltd.
Contents
12.2 Campbell Scientific Array Based Datalogger (Cable label
– “CSIU”) ........................................ 40
– In NIWA enclosure (Cable label – “UNI2”) .................................................... 41
12.5 NIWA Datalogger (with Unidata engine) (Cable label
– “UNI3”) ................................................ 42
Tables & Figures
Figure 3 - RS232 Connector Pin View ............................................................................................................... 8
iCE
3
FX User Guide
1 Declaration of Conformity
We,
HyQuest Solutions (NZ) Ltd
of Waikato Innovation Park
Ruakura Road, Hamilton 3214
New Zealand
Ph: +64 7 8570810
in accordance with the following Directives:
2004/108/EC The Electromagnetic Compatibility Directive
Standards met:
BS EN 55022:2010: Incorporating Corrigendum No. 1 and Amendments Nos. 1 & 2
Information Technology Equipment
–
Radio Disturbance Characteristics
–
Limits and Methods of Measurement
BS EN 55024:2010: Incorporating Amendments Nos. 1 & 2
Information Technology Equipment
–
Immunity Characteristics
–
Limits and Methods of Measurement
FCC Code of Federal Regulations 47: Telecommunication
Part 15 – Radio Frequency Devices
Subpart A – General
Subpart B – Unintentional Radiators
I hereby declare that the equipment named above has been designed to comply with the relevant sections of the above referenced standards and all products supplied under this Declaration will be identical to the sample tested.
Signed:
Name: David Richards
Position: Managing Director
Place: Hamilton
Date: 20/09/2012
1
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
2 Introduction
2.1 About this Manual
This manual is intended as a detailed guide for the iCE
3
FX installation, configuration and operation.
This manual is also available online in PDF format at www.hyquestsolutions.co.nz
Throughout this document, small icons are used to identify additional information. These are as follows:
NOTE: Indicates extra detail to expand the current discussion.
WARNING: Describes something that may cause problems if not heeded.
2.2 Support
Additional technical support for the iCE 3 FX is available by contacting:
HyQuest Solutions (NZ) Ltd
PO Box 9466
Dinsdale
Hamilton 3240
NEW ZEALAND
Tel: +64 7 857-0810
Email: [email protected]
For latest information and software updates, visit the HyQuest Solutions (NZ) Ltd web site at www.hyquestsolutions.co.nz
.
Access to the client area on the website requires a log-in which is can also be used to access the HyQuest Solutions forum. Self-registration is available by visiting the website home page.
2
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
3
iCE
3
FX User Guide
3 Overview
3.1 General Characteristics
The iCE
3
FX (iQuest Circuit Extender) has been designed as a cost effective, low power, self-contained circuit extender to enable communication with equipment over a wireless (3G) network connection. Typical devices that the iCE
3
FX can be used to interface with include dataloggers, PLCs etc.
The iCE
3
FX unit comes standard with a d.c power lead. A host device (RS232) cable pre-wired for one of
connector allows the use of a small stubby antenna (optional accessory) or alternatively, a coaxial cable to a higher gain external antenna for use in areas where signal strength is low.
3.2 Typical Applications
The iCE
3
FX can be used in a number of applications, including:
Wireless IP telemetry and circuit extension to third party devices
Wireless IP / RS232 serial gateway to multi-drop networks
The iCE
3
FX provides an effective means for the migration of legacy dialup telemetry networks to more costeffective wireless IP communications over 3G. By simply replacing existing dialup modems with an iCE
3
FX, you can have virtually any logger type telemetered over the 3G network. If you are using a HydroTel telemetry system, the iCE
3
FX can be configured to call-in and be downloaded using a dynamic IP address
which further simplifies the deployment. See Section 3.4.4 for more details.
3.3 Technical Specifications
Dimensions:
Mass:
Digital I/O:
Environmental:
82mm x 63mm x 30mm (WxHxD),
184g
Analog I/O:
1 x Digital Input
- 30Vdc maximum input, switch to 0Vdc to activate.
- May require external debounce components for some applications.
1 x 12 bit uni-polar Analog input. Range 0-5000mV. Input impedance 103 kΩ.
Referenced to 0V common. Internal measurements available for monitoring are:
Supply Voltage
Received Signal Strength (RSSI) in dBm
iCE 3 FX internal temperature.
Power Supply:
Comms Interfaces:
External 5-32Vdc supply.
Power Consumption: Average 5 mA @ 13.8V.
“Full Save” power mode with active RS232 terminal.
Average 12 mA @ 13.8V. Idle in “Partial Save” power mode, 3-wire RS232.
Average 50 mA @ 13.8V. Active on-line with an active TCP or CSD session.
Actual current is dependent on the modem state; data traffic quantity and relative signal strength (i.e. transmit power required).
1x RS232 high density DB15, variable speed, DCE configuration.
1x Integral 3G wireless modem.
Operating Temperature: -10
C to +70
C.
Humidity: Maximum 95%, non-condensing.
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
3.4 Key Features
3.4.1 Terminal Configuration
A small number of diagnostic and initialisation options are available via a standard ASCII terminal connected to the RS232 serial interface. In previous model (iCE
3
3G) nearly all the configuration was also done using the terminal. This has been removed because of the increased features of the FX and data unloading is done using the HyQuest Solutions logger support application, iLink 2012.
Refer to Section 7 for details on the configuration options.
3.4.2 Wireless Internet (IP) Connectivity
Wireless Internet connectivity is provided via the on-board modem. Through this interface, data packets can be transferred to and from the host (RS232) port. To facilitate IP connectivity, a suitably activated SIM card must be installed in the device. It is also necessary to program the unit with appropriate settings via a terminal connected to the host (RS232) serial interface.
The iCE
3
FX communicates over the wireless network using TCP/IP or UDP protocol via a single data port.
The device supports ASCII and binary communication to a wide range of HyQuest Solutions and third party equipment. It also supports consecutive connection to two separate base servers.
3.4.3 Alternative Wireless Connectivity (SMS or FTP)
Another wireless connection mode other than IP is also possible on all hardware variants. This is SMS (Short
Message Service). As with the IP mode described above, using the SMS service requires a SIM card with the SMS service enabled by the service provider.
The SMS option works by sending a pre-set text message to up to ten destination cell phones or SMS receivers. This message contains the site identification and the current values of all enabled sensors. See
Section 8 SMS (Text) Commands for more information on using the SMS feature.
Finally, FTP file transfer is provided for installations requiring a stand-alone data uploads.
3.4.4 Static and Dynamic IP addressing
The iCE
3
FX supports both static (fixed) and dynamic IP address modes. Whether the mode is static or dynamic is set by the service provider and the SIM card supplied by them.
Static IP addressing allows the iCE 3 FX to work with any mix of software or device, as each end of the 3G link knows the IP address of the other end. However, this mode usually requires a dedicated APN or else an additional ongoing cost for a static IP on a wide area network.
Dynamic IP addressing requires that
HydroTel™ is installed at the remote (base) location. In this mode, the iCE
3
FX initiates the connection, typically via the Internet and sends a special call-in packet to the base.
HydroTel
™ then captures the IP address that was allocated to the iCE
3
FX for that session and uses it for all ongoing communication with the host device attached to the iCE 3 FX.
The advantage of dynamic IP addressing is the ability to have low cost IP connectivity to any device supported by HydroTel™. This can be achieved by a simple Internet connection via a local service provider.
The embedded microcontroller in the iCE 3 FX manages the IP session establishment and maintenance, meaning that the host device does not need any special intelligence of its own.
3.4.5 Power Management
The iCE
3
FX supports four distinct power management modes which are listed below. The power save function also has a scheduler which allows the unit to automatically switch from the lowest power state (full power save) to higher level with an active state where it can receive SMS messages and/or remote IP connections.
4
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
No Save
With power management disabled, the internal wireless modem is maintained in a powered on state even when an IP or CSD session is not currently active. While in this state, regular signal strength measurements are made and it is possible to interrogate the internal modem using the AT command set via a terminal connected to the serial interface. The unit is also able to receive and respond to SMS messages when in an idle state.
Partial Save
This mode requires that a three-wire RS232 connection be used (Rx/Tx and Gnd only). If a full
RS232 connection with handshaking lines (specifically DTR) is used, the unit will operate at a similar power level to the
“No Save” mode.
In partial power management mode, the internal wireless modem is maintained in a powered on state even when an IP or CSD session is not currently active just like “No Save”. However, in this mode, no signal strength measurements are made except just prior to a connection being made. This minimises the modem’s power requirements by making use of its automatic UART shutdown function.
It is possible to interrogate the internal modem using the AT command set via a terminal connected to the serial interface. The unit is also able to receive and respond to SMS messages when idle in this mode.
Full Power Save
When power management is set to
“Full Save” power mode, the internal wireless modem remains in a powered off state until the power level is raised by the power scheduler or an IP session is activated via the comms scheduler.
While the modem is in this full-save state, it is not possible to obtain signal strength measurements or interrogate the modem via the AT command set using the Modem Terminal mode. It will also not answer CSD calls, respond to SMS or accept incoming IP connections.
RS232 Only
This mode is provided for applications where the internal modem is not used and telemetry is achieved by a data radio or modem connected to the RS232 port. When in this mode, the RS232 port is used for all callback communication.
3.4.6 Data Logging
The iCE 3 FX supports the logging of data from six virtual sensors, plus a further three internal data sources
(supply voltage, RSSI and internal temperature).
Please refer to Section 10 for a detailed description of the datalogging capabilities of the iCE
3
FX.
3.4.7 Alarm Processing
Each virtual sensor can be checked for up to six separate alarm conditions. Each alarm has separate trigger and reset levels, as well as an activation delay or accumulation period depending upon the data type. If an alarm is triggered it will initiate an IP connection in the same way as the Comms Scheduler or a manual request via the RS232 port (AT^IGOL command) or an SMS message (GOL) initiates a connection.
3.4.8 GPS
As an optional add-on (hardware and software) the modem can be configured to log GPS position (longitude, latitude and altitude) and synchronise the device clock from GPS time.
5
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
4 iCE
3
3G and iCE
3
FX Comparison
The iCE
3
FX is a new model based on the iCE3 3G hardware but with a new Sierra Wireless modem module, expanded logged data storage and an enhanced firmware/software set which allows the fundamental datalogging format as floating-point built around a new IEEE-745 2008 compliant library.
NOTE: The legacy iCE3 3G cannot be converted to an iCE3 FX as it lacks some key hardware components.
Key differences between iCE
3
3G and iCE
3
FX
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Datalogging memory expanded from 32KB to 8MB
Standard IEEE-754-2008 compliant Floating Point library.
Datalogging sample values are floating-point. Logging multiplier removed.
All time stamping is in UTC to enhance use internationally.
Configuration via text terminal removed and only basic terminal diagnostics supported.
Default RS232 port speed increased from 9600 to 38400bps.
Logging sensor channels increased from four to six.
Sensor logging rate can be different when alarm(s) on that sensor are active.
All schedules have separate on/off/alarm intervals.
Totalisers: YTD (Year To Date) and Last Year. Settable roll-over time (daily) or date (yearly).
Capable of native FTP file transfer (CSV format) to one or two destinations.
Analogue input range now settable.
Sensor display format is settable (number of decimal places).
Multi-language support for internal date/times etc. Five supported (EN, DE, FR, ES, PT)
Secure and reliable OTA (Over The Air) firmware and software upgrades now possible.
Optional GPS Logging and Clock Sync.
6
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
5 Installation
5.1 Removing / fitting the SIM card
Important! Ensure the iCE
3
FX is depowered before attempting to fit or remove the SIM card.
Also, if the SIM card lock is not engaged (moved fully to the right), the iCE
3
FX will not operate correctly.
Figure 1 - SIM Card Lock
To fit the SIM card, check that the SIM card lock is fully to the left (unlocked). Insert the card with the gold contacts facing upwards and the edge with the chamfered corner facing the unit. Push the card fully into the slot until it clicks into place. Slide the lock fully to the right to engage it.
To remove the SIM card, slide the SIM card lock to the left (unlocked). Then press the SIM card inwards slightly. This will release the latch and allow the card to be extracted from the SIM card carrier.
5.2 External Power Supply
The iCE
3
FX does not have an internal battery and therefore requires an external power supply. It will accept any external dc power source ranging from 5 to 32Vdc. In the later model, this can be logged on a regular
the power supply connection which is part of the I/O connector.
Although the average current consumption is reasonably low, it is important that the power supply is capable of delivering the high current peaks that wireless modems are capable of drawing. To this end, HyQuest
Solutions recommends that a gel-cell type battery be used to power the unit, with appropriate trickle charging from a suitable source. In normal operation, the host device is likely to have a suitable power supply available.
5.3 Power Supply + I/O Connector
On the later hardware revision, the digital and analogue I/O share the power supply connector. The connections are via two flying leads. On earlier hardware units, the two I/O pins are unused. The pin designations of the power supply and I/O connector are shown in the diagram below.
+Vin Gnd
Analog In Digital In
Vin (Red)
Gnd (Black)
Ain (Blue)
Din (White)
4-core circular 7/0.2 cable
Figure 2 - Power Supply I/O Connector and Cable
7
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
5.4 RS232 Connector
8
9
10
11
4
5
6
7
The iCE 3 FX has a high-density DB15 male RS232 connector. The pin designation are shown in the table below.
Pin
1
2
3
Function
DCD (Data Carrier Detect)
TXD (Transmit Data In)
Not used
Type
OUT
IN
12
13
14
15
Not used
Not used
RXD (Receive Data Out)
DSR (Data Set Ready Out)
DTR (Data Terminal Ready In)
GND (Signal Ground)
Not used
CTS (Clear To Send Out)
RTS (Request To Send In)
RI (Ring Indicator Out)
Not used
Not used
OUT
OUT
IN
OUT
IN
OUT
10
5
15
1
11
6
Figure 3 - RS232 Connector Pin View
Table 1
– RS232 Connector Pin Functions
5.5 Antenna Connection
The iCE
3
FX has a standard SMA antenna connector. For installations with a good signal level, a small rightangle ground plane independent stubby antenna will provide good results. Such antennae are available from HyQuest Solutions or other suppliers. This attaches directly to the SMA connector on the front of the unit. In areas of marginal coverage, HyQuest Solutions recommend using an external higher gain antenna.
5.6 Setting the Real Time Clock
If the iCE 3 FX will be used in scheduled connection mode (by using the communication scheduler), the internal clock will need to be checked and if necessary, set correctly after installation on site and all other configuration has been completed. In normal operation, the clock will automatically synchronise to the wireless network time shortly after power up, however a facility to manually set the clock is also provided.
This step is required because the clock is reset to a default time when the iCE
3
FX has been depowered for any reason. The iCE
3
FX makes an attempt to get the best time reference in this case.
If there is no logged data available, the clock will be set to (1 st
January 2012 @ 00:00:00). If logger data is available, the iCE
3
FX will set its clock to a time/date one second past the time stamp of the last record. It does this as it has no idea of how long it has been since the record was logged.
This at least keeps logged data records in chronological order. Note that the schedulers (power and/or comms connections) will still work if the clock has not been synchronised, they will just not
be synchronised to the correct time of day. Please refer to Section 7.3.2 for more details on using
the Scheduled Power Mode.
8
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
5.7 Recommended Deployment Procedure
Obtain and install the SIM card from your preferred service provider. Ensure that the SIM card lock
is fully engaged. See Section 5.1 for details on fitting the SIM card.
Connect an antenna and power supply to the iCE
3
FX.
Using a standard cable connect a computer with a suitable terminal program such as iLink or
HyperTerminal®.
Configure the iCE
3 FX completely before taking it into the field for installation. Use the typical configuration at the end of this document as a guide.
If using the datalogging function, configure and check the operation of the real-world inputs if possible.
If used in conjunction with HydroTel™, configure the logger and site in HydroTel™ for the installation, including the chosen communication address. This must match the address in the
iCE
3
FX when used in scheduled (call-in) mode. Note that the iCE
3
FX can be configured to automatically set its address based on its serial number with an optional offset.
Test it on-line. If necessary use the manual connection initiation command ( ”AT^IGOL”) to force a
connection if waiting for the scheduler is not an option. See Section 9.1.
Take the iCE
3
FX to site and install it. Take a suitable computer (laptop) and standard cable to allow testing and further configuration on-site if needed.
As the iCE
3
FX will usually be used in scheduled connection mode, the final step is to check the internal clock. Normally, this will be synchronised to the network time after acquiring the network.
Use the standard cable and terminal program on the computer to check and if necessary, set this.
See Sections 5.6 for information on the clock.
Finally, make sure the correct cable is securely connected to the host device.
If possible check that the system works properly end to end, including communication with the host device.
9
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
6 Operation
6.1 Status LED Indicator
The iCE
3
FX has a single blue LED mounted on the front panel. This indicates the current device status and is useful for diagnostic purposes. The various LED indicator states are as follows:
Condition
Idle in full power save mode. Modem off.
Status LED Indication
Single 100ms flash every 5 seconds
Modem is being initialised.
Not connected, but has good signal strength
IP connection is being established.
Waiting for a RS232 host device to respond. Only
Constantly on.
Single 100ms flash every 2 seconds.
Three 100ms flashes every 2 seconds.
Flashes rapidly every 100ms. Very fast 50/50. applies to host types CSI Array or Unidata..
Connected to the Primary base.
Connected to the Secondary base.
Acting as a listening TCP server.
No or very low signal strength.
Custom RS232 communications.
Short 100ms flash followed by a longer 500ms flash.
500ms flash followed by a short 100ms flash
Flashes every 500ms consistently. Fast 50/50
1.5 seconds on every 2 seconds. 75/25
1 second on every 2 seconds. Slowest 50/50.
State One Second One Second
Idle in Full Power Save mode. Modem off.
Initialising modem.
Idle with adequate signal.
Connecting.
Waiting for RS232 host device response.
Connected to Primary Base.
Connected to Secondary Base.
Listening TCP server active
(This mode has a five second duration)
Idle with insufficient or no signal.
Custom RS232 comms mode active.
Table 2 - Status LED Indication Modes
6.1.1 Host Port Speed Display
To assist with determining the correct terminal setting required to connect to the iCE
3
FX, the status LED is used to display the currently programmed host port speed. This happens when the iCE 3 is first powered up and the LED will show a series of flashes indicating the host port speed setting. This sequence is repeated three times before the normal status LED mode commences. The numbers of flashes shown are:
Number of Status LED Flashes
1
2
3
Host Port Speed
1200 bps
2400 bps
4800 bps
4
5
6
9600 bps
19200 bps
38400 bps
Table 3 - RS232 Host Port Speed Indication
6.2 Digital Input LED Indicator
iCE
3
FX units have a red LED that illuminates when the digital input is active.
10
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
6.3 Host Device Type settings and operation
The following are the 4 different Host Device Types.
6.3.1 Normal (Type=0)
Typical Settings DFC=0
DTO=20
Forwarding on character disabled.
Forwarding after 200ms of no more characters from host.
Host Port Communication and Handshaking
On receipt of a data packet, the iCE
3
FX will immediately forward it to the host via the RS232 port. The handshaking lines are completely ignored. Conversely, characters that are received from the host are stored until either a matching character is detected (if the forwarding character is not zero) or else no more characters have been received for the forwarding timeout period. The packet is then sent to the remote IP address.
6.3.2 Campbell Scientific Array Based Logger (Type=1)
This mode is used for the older CSI array based loggers such as the CR10/CR10X.
Typical Settings DFC=0
DTO=20
Forwarding on a particular character is disabled.
Forwarding after 200ms if no further characters from host.
Host Port Communication and Handshaking
On receipt of a data packet, the iCE
3 will assert its CTS line (which is connected to the logger’s RING line). If the logger’s ME line is not active, the iCE
3 then waits until the logger responds (by raising its ME line). The iCE 3 FX will then output a series of carriage return characters until the logger detects the selected host port speed and returns a prompt (*).
When the iCE 3 FX determines that the logger is active and at the correct communication speed it will send the received data packet on to the logger. In reply mode, characters that are received from the datalogger are stored until no more characters are received for the forwarding timeout period. The reply packet is then sent back to the remote IP address.
6.3.3 Unidata (Type=2)
Typical Settings DFC=13 Forwarding on character is enabled on carriage return (13)
DTO=0 Forwarding on time is disabled.
Host Port Communication and Handshaking
On receipt of a data packet, the iCE 3 will assert its CTS line (which is connected to the logger’s RTS line).
The iCE
3
FX then waits until the logger scans and returns a * prompt. The iCE
3
FX then sends the received data packet to the logger. In reply, characters that are received from the datalogger are stored until a forwarding character (normally a carriage return) is received. The reply packet is then sent back to the remote IP address.
6.3.4 Standalone (Type=3)
Typical Settings DFC=0
DTO=20
Forwarding on a particular character is disabled.
Forwarding after 200ms if no further characters from host.
Host Port Communication and Handshaking
In this mode, the iCE
3
FX does not link the wireless connection to its RS232 port at all. All data packets are deemed to be for the iCE
3
FX itself and it behaves through the wireless connection just as if it were being communicated to via its RS232 port.
11
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7 Configuration
A small number of diagnostic and initialisation options are available via a standard ASCII terminal connected to the RS232 serial interface. In previous model (iCE
3
3G) nearly all the configuration was also done using the terminal. This has been removed because of the increased features of the FX and data unloading is done using the HyQuest Solutions logger support application, iLink 2012.
The iCE
3
FX will not automatically output the main menu when terminal mode is entered. This is to prevent unwanted data being sent into the attached host device’s RS232 port. To access the terminal, it must be enabled by entering the unlock command AT^ITRM. At any point, the terminal menus can be refreshed by entering the refresh command (“R” or “r”) followed by
Enter. The terminal mode will time out after 2 minutes of inactivity.
The following sections describe how to set up a terminal connection and the menu options that are available whilst connected.
This description assumes a computer running a version of the Microsoft ® Windows ® operating system is being used and the descriptions below relate to the standard Windows
®
terminal emulator application,
HyperTerminal™. Other types of computer and terminal emulators may also be used, but details on the setup required are outside the scope of this document.
A suitable cable to connect the iCE
3
host (RS232) port to the computer is required. This
should be wired as shown in Section 12.1 (Standard Devices).
The iCE3 RS232 port is a DTE (Data Terminal Equipment) configured port and is identical in pin-out and signal alloca tion to that of an IBM compatible PC’s RS232 port. Therefore the cable required is the same as that for computer-to-computer communication and is termed a null-modem cable. These are available from most electronics retailers if required.
To access the iCE 3 FX diagnostic terminal a full null-modem cable between a communication port (e.g.
COM1) on your computer and the RS232 port of the iCE
3
FX. The null modem cable configuration has the three main signal pairs crossed over. These pairs are TXD/RXD, RTS/CTS and DTR/DSR. The signal ground (SG) line is connected straight through. The CD and RI lines are unused.
The iCE 3 FX RS232 serial port is set by default to a speed of 38400bps, 8 data bits, 1 stop bit and no parity.
Flow control is not required.
12
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.1 Terminal Security Code
The iCE
3
FX supports the use of a text-based security code (of up to 10 characters) that may be used to prevent unauthorised access to the terminal menus.
If used, the code is set using iLink 2012 that is registered to “Administrator” level. If it is empty, the terminal is immediately available as soon as the RS232 connection is made. If the code has been set, then a prompt message is shown and the code must be entered before the terminal becomes available.
The security code is case-sensitive. The code cannot be viewed or changed except by an authorised user using iLink which is registered to Administrator level.
> Enter Security Code (max 10)=
7.2 Terminal Menus
Throughout all the terminal menus, there are two common entry codes.
Menu option 0 (zero) always returns you to the level above your current position.
Entering “r” or “R” when in a menu being prompted for an option will refresh the menu without selecting anything.
When a terminal session has been established with the iCE
3
FX through the RS232 port you will be presented with the main menu. To make a menu selection, type a number followed by <Enter>. Invalid menu selections will result in the display of an error message on the terminal. The current value of each settable item is enclosed in square braces e.g. [1234].
7.2.1 Main Menu (Level 1)
The first menu displayed is the Main Menu. From here, you can make the following choices: iCE3 FX (Sierra Wireless)
AE1-3301, FW: 1.10, SW: 1.30, OAT: 1.30
Site Name: My Site Name
1 Totals
2 Modem Diagnostics
3 Modem Terminal
4 Initialise
>
Option 1
– Totals
This menu option provides access to the totaliser. A sub menu displays the current totals and also provides a means of either resetting all totals for the channel or setting the running total to match a flow meter.
* Totaliser 0 Cfg
Last Year: 3457765.0
Year To Date: 96339.0
Yesterday: 1337.2
Today: 149.7
Running: 158823.0
0 Exit
1 Reset All Totals
2 Edit Running Total
13
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
>
Reset ALL Totals
> Reset ALL Totals for Totaliser 0? (0:No 1:Yes)
This option resets all totals for this channel. Enter ‘0’ to cancel resetting the totals or ‘1’ to confirm resetting all the totals.
Edit Running Total
> Totaliser Running Total=
Enter the Running Total value here and press <Enter>.
This is only possible if the totals have been cleared and is intended only as an initialization task when the logger is first commissioned.
Option 2 - Modem Diagnostics
Select this option to display the current modem identification parameters, status and signal strength. After listing the status information, this option then provides a running diagnostic log of communication with the wireless modem.
Example Status Information:
Modem Diagnostics. Enter 0 to exit
Modem: Sierra Wireless
Version: R7.53.0.201404011204.Q2698 1787208 040114 12:04
IMEI: 013166000064695
IMSI: 530011100763226
LIP: 10.236.0.1
RSSI: -69 dBm BER: 0
Status: Ready
>
12:43:55 STATE: Sig Strength PM0 CS1 LC0 LS0 PB CT30 CW230 SC0 SM0 GPS0 GPT0
12:43:55 > AT+CSQ
12:43:55 < +CSQ: 22,0 [-69 dBm]
12:43:55 STATE: Ready PM0 CS1 LC0 LS0 PB CT30 CW230 SC0 SM0 GPS0 GPT0
IMEI:
International Mobile Equipment Identifier. This is stored in the wireless module at the factory and uniquely identifies the hardware by manufacturer and serial number.
IMSI:
International Mobile Subscriber Information. This is obtained from the SIM card
LIP: The last local IP address that was allocated to the iCE
3
FX when it was last online.
RSSI: This displays the Received Signal Strength Indication in units of dBm. This is useful for determining the strength of the signal. A value of 0 indicates that the RSSI value is not available.
The iCE
3
FX will not attempt to connect to the network if the RSSI is 0 or less than -113dBm.
Example diagnostic information.
The < character indicates data received from the modem and the > character indicates data sent to the modem.
The current communication state is shown with a preceding STATE: message that includes several additional diagnostic e.g. PM0 CS1 LC0 LS0 PB CT30 CW230 SC0 SM0 GPS0 GPT0.
These are:
-
PM Actual Power Management level being used. 0=No Save, 1=Partial Save, 2 = Full Save.
-
LC Link Control. Requested link control (to the modem module).
14
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
-
LS Link State. Actual link state (from modem module).
-
PB Current base (host) that is (or will be) connected. PB=Primary, SB=Secondary.
-
CT Connection Timer. Connection time remaining. Set to duration when not connected.
-
CW Connection Watchdog. Time before a hard reset of the modem is done. Is 3 times the comms schedule interval. E.g. interval = 60 mins invokes reset if no connection in 3 hrs.
Option 3 - Modem Terminal
By using this terminal mode, it is possible to perform two distinct functions depending on the state of the internal modem. If the terminal is available, this message is displayed.
> Modem Terminal active. Press <ESC Enter> to exit.
If the internal modem is powered down, the terminal mode is unavailable and this message will appear:
> Wireless module inactive. Terminal unavailable.
Assuming the modem is active, the two scenarios are as follows:
If the internal modem is powered up, but an IP session is not in progress, then it is possible to interact with the modem using the standard AT command set.
If the internal modem is powered up and an IP session is currently in progress, then it is possible to interact with a terminal at the remote end of the connection.
When using transparent terminal mode you must press the <Enter> key after each command or message you wish to send. Press <ESC Enter> to exit the modem terminal session and return to the communication menu.
Option 4
– Initialise
This option is used to initialise the unit. This is generally done just after installation as part of the commissioning process to eliminate any test or residual data or totals. It resets the memory pointers to zero and also resets all totalisers. To ensure this task is not accidentally invoked, a specific string must be typed in order to execute the initialisation process.
=
> WARNING! This will completely clear logged data and totals.
Type 'init' to initialise the unit. Or just Enter to exit.
15
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.3 iLink 2012 Configuration Menus
All the configuration can be done by connecting the device using iLink 2012. Once the iCE 3 FX is connected to your computer, open up iLink 2012 and click on the ‘Quick Connect’ button. Select the COM port from the drop down menu and set the baud rate as 38400. When the device is connected successfully, click on the
General option under the Configuration tab to see the configuration settings for the device.
7.3.1 General
Site Name
Enter a name for the site in this field. This is not used except as part of a SMS reply string when requested by the RQ command. This function can be useful to determine the site, time/date and RSSI at a given 3G
network phone number. See section 8.1
for details on the “RQ” SMS command.
UTC Offset
Enter the offset of the iCE 3
’s local time with respect to UTC(GMT). This is used for international time correction if the data is forwarded to the HyQuest Solutions Global Data Network. For example, enter 12 for
NZST.
Date Format
Select the date format from the list as used by the iCE
3
.
Day Totals Start
This option allows you to enter the hour of the day to start calculating the day totals.
YTD Totals Start
Enter the month of the year to start calculating the year to date totals.
Language
16
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide iCE
3
FX provide multi-language support for internal date/times etc. Five languages are being supported at the moment (EN, DE, FR, ES, PT).
Security String
The Security String (up to 10 characters) is used to prevent unauthorised access to the terminal menus. If used, the code is set using iLink 2012 that is registered to "Administrator" level. If it is empty, the terminal is immediately available as soon as the RS232 connection is made. If the code has been set, then a prompt message is shown and the code must be entered before the terminal becomes available.
Sync clock from network
Enable this option to synchronise the device clock from GPS time.
7.3.2 Power
The power configuration menu allows the configuration of the iCE
3
power management settings.
Power Mode
This option is used to set the power management save level for the unit. The available options are No Save,
Partial Save, Full Save and RS232 only.
Start Time
This is the time at which the iCE 3 will switch from a forced “Full Save” power mode to the selected power mode as defined in the above Power Mode option.
End Time
This is the time at which the iCE 3 will cease switching out of “Full Save” power mode.
In the example below, the modem is enabled to go to the “No Save” level once per hour (on interval = 60 minutes), for a time of 5 minutes (duration = 300 seconds) starting at 6.00 am and ceasing after 6pm. Set the start time to 00:00 (0000) and end time to 23:59 (2359) for the on/off cycle to apply regularly throughout the complete day.
17
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
NOTE: In this example, the “on” time is from 6am to 6pm. The “off” time is from midnight to 6am and then from 6pm to midnight. Activation during these two times may be configured differently using the on interval and off interval settings described below.
Figure 5 - Scheduled Modem Power Mode Example
Duration
Enter the length of time in seconds that you want the iCE
3
to maintain the modem in the selected power mode. The minimum value for this setting is 60 seconds.
On Interval
This is the length of time in minutes between each successive power mode change when the time is in the
“on” period. i.e. between the start and end times.
Off Interval
This is the length of time in minutes between each successive modem power mode change when the time is in “off” period. i.e. before the start time or after the end time. This setting will normally be 0 (no activity in the off period), but this option does allow a different activation rate to be configured if required.
Alarm Interval
This is the length of time in minutes between each successive modem power mode change when there are one or more active alarms in the iCE 3 .
18
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.3.3 Comms Configuration
Addressing
Serial Number as Address
Tick this option if you want the iQuest protocol communication address to be automatically obtained from the device’s serial number.
Base Address
This is the address of the base station to use when calling back using the RS232 telemetry mode. The base address is normally set to zero.
Address Offset
If the “Serial Number as Address” option is enabled, then an additional offset can be entered. Using offsets can be used to categorise units into regions for example.
The serial number plus the offset must still result in an address within the allowable range of 1-
32767.
Gateway Offset
Use 0 to disable gateway communication. If this is not zero, then a gateway block of 100 locations is set up starting from the offset.
Comms Address
When using a manual address, enter a value between 1 and 32767 (the factory default is 1). This address is used to identify the unit in all iQuest protocol communication and must be unique on a HydroTel™ communications interface.
An address of 0 is reserved for the base station (e.g. HydroTel™) and must not be programmed into the iCE
3
. The iCE
3
will always respond to an address of -3 (which is a special
universal address) no matter what its own address is.
19
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Modem
APN
Enter the Access Point Name allocated by your network provider (eg. telstra.internet).
Username
Enter the user name required by your wireless network provider.
Password
Enter the password required by your wireless network provider.
Note: Many providers do not require any login credentials, in which case the username and password should be set to empty.
Use DNS for IP Address
Enable this option to use the DNS Server address for the IP address.
Primary Base IP Address
Enter the primary IP address that you will connect to. This is the primary destination IP address used for unsolicited binary calls and also host data traffic once the link is established.
Primary Base Port
Enter the port number to use for the primary connection.
Secondary Base IP Address
Enter an optional IP address to use for secondary communication if dual-base mode is enabled. If this is not required, you can set the IP address to 0.0.0.0.
Secondary Base Port
Enter the port number to use for the secondary communication. If this mode is not to be used, set the port number to zero.
20
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Connection Mode
Choose the mode that is used when a connection is initiated by scheduler, manual terminal mode command
(AT^IGOL) or an alarm trigger. The options are IP or SMS.
IP Mode
If the connection mode is set to IP, you have two different options
– TCP or UDP.
TCP Server Up Time
This allows control over the amount of time the iCE 3 will remain active as a listening TCP server after any client connections (primary and optionally, secondary) have been completed. Setting this to 0 will disable the
TCP server mode and in this scenario emulates the older iCE
3
3G software. Otherwise, the unit will remain active and able to accept an incoming TCP client connection from an accepted IP address.
TCP Server Mode Only
If the IP mode is set to TCP, this option enables to keep the iRIS remain in a listening TCP server mode.
Inhibit UDP Announcement
This allows control over whether the iCE
3
will send a call-in (announcement packet) when as scheduled connection is made. In installations where very lengthy connection times are required, where the host device is
“polled”, then a call-in packet on connection is generally not required.
Any UDP connection initiated by an alarm activation, received SMS “GOL” command, RS232
AT^IGOL command or digital input trigger will always send a call-in packet.
UDP ‘Permanent’ Connection
This option is used to enable a permanent UDP connection regardless of the schedule settings.
Dual Base Mode
If this mode is enabled and the secondary IP settings are configured, the iCE
3
will make a connection to both bases in sequence for each connection event (scheduler or manually triggered).
Connect on Startup
If this option is enabled, the device attempts to connect on startup.
Log Modem Comms Diagnostics
If this option is enabled, all the modem communication events are automatically logged along with the RSSI
(signal strength) value that was available at the time of the event occurring.
SIM PIN
When the SIM card used has a PIN code enabled for security purposes, use this option to set it. If a PIN code is not required, enter zero (0) for this setting.
If a SIM PIN is required and an incorrect PIN is entered, the unit will not operate correctly. Also, if a SIM PIN is not required and a PIN is configured, it may lock the SIM card out due to multiple attempts to use an invalid PIN number.
Allow changes to unsafe values
The APN, Username and Password are marked as unsafe values, which may cause loss of comms if set incorrectly remotely. If you want to edit these columns, the option "Allow changes to unsafe values" should be enabled.
21
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Schedule
Start Time
Enter the time at which the iCE
3
is allowed to start establishing client IP sessions.
End Time
Enter the time at which the iCE
3
must stop establishing wireless IP sessions.
In this example, the wireless IP link is established once per hour (frequency = 60 minutes), for a time of 5 minutes (duration = 300 seconds) starting at 6:00am and ceasing after 6pm. Set the start time to 00:00
(0000) and end time to 23:59 (2359) for the on/off cycle to apply regularly throughout the complete day.
NOTE: In this example, the “on” time is from 6am to 6pm. The “off” time is from midnight to 6am and from
6pm to midnight. These two times may be configured differently using the on interval and off interval settings described below.
Figure 6 - Scheduled Comms Connection Example
Duration
Enter the length of time in seconds that you want the iCE
3
to keep each wireless IP session active. The minimum value for this setting is 60 seconds.
22
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
On Interval
Enter the length of time in minutes between each successive IP session being established when the time is in the “on” period. i.e. between the start and end times.
Off Interval
Enter the length of time in minutes between each successive wireless IP session being established when the time is in the “off” period. i.e. before the start time or after the end time. This setting will normally be 0 (no activity), but this option allows a different connection rate to be configured if required.
Alarm Interval
Enter the length of time in minutes between each successive wireless IP session being established when there are one or more active alarms in the iCE
3
.
Miscellaneous
IP Address
The IP acceptance set-up menu is the place to configure the IP address acceptance list for the UDP mode.
Connect on DIN request
This option enables the device to get connected when it receives a Digital Input request.
23
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
FTP
The FTP configuration menu lets you to configure the primary and secondary FTP server settings.
File Type
Choose the File Type from the list or use the option ‘0’ if you are not using the FTP option.
Base File Name
Enter the file name in this column.
Use Serial Number in File Name
Enable this option if you wish to use the serial number in the file name.
Use Site Name in File Name
Enable this option if you wish to use the Site Name in the file name.
Include Date/Time in File Name
Tick this check box if you want to include date and time in the File name.
Include Header Line in CSV/TXT Files
Enable this option if you wish to include a header line in the file. This option is available only for CSV/TXT file types.
Apply UTC Offset to Sample Timestamps
This option is used to apply UTC offset to sample timestamps.
Host Name
Enter the name of the host device.
Username
Enter the username required to login to the FTP server.
24
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Password
Enter the password required to login to the FTP server.
Path
This is the path to the FTP subdirectory folder.
RS232
RS232 Port Speed (bps)
This option configures the RS232 port speed to use when the device is not in terminal mode and is connected to the host device. The default is 38400. To determine the programmed host port speed if this is
for information on the host port speed indication.
Host Type
The Host Type option defines the type of device connected to the RS232 host port. The options are Normal,
CSI Array, Unidata and Standalone.
Data Forward Character
The Data Forward Character defines the ASCII character, that if received will initiate the forwarding of the data packet. Setting this parameter to zero will disable the forwarding on character mode. In this situation, use the forwarding after data timeout function.
Data Forward Time
This is the data gap time (in milliseconds x 10) after which the iCE
3
FX will forward the data packet to the remote destination. This mode should be used for binary data packets as used by HyQuest Solutions products and Campbell Scientific dataloggers. If this parameter is set to zero, then data will not be forwarded unless a forwarding character is defined.
25
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Terminal Echo
This option enables or disables the echoing of characters received from the RS232 port when the unit is in terminal mode.
Inhibit User Prompts
This option inhibits any human input to the device via Terminal.
Forward SMS Messages
If this option is enabled, any incoming SMS message received by the iCE 3 are forwarded to the RS232 port.
This will allow a capable host device to process and use the SMS. The iCE
3
will still examine all messages and action them if required.
Slave Log Data Check Rate
This is the rate at which the iCE3 FX reads data from the slave device (iRIS 150FX).
7.3.4 Sensor Configuration
General
Name
This is the sensor name as displayed in the logger (maximum length 10 characters).
Units
This area displays the unit of the sensor.
Format
This option is used to choose the display format to use for the selected sensor.
Source
Enter the source from which the virtual sensor should acquire its data. A list of valid data sources is shown in the following table.
26
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Source Description
0
1
Unused / disabled
Analogue Input
2
3
4
5
6
Pulse Counter on Digital Input
Auto Pulse Counter on Digital Input
Frequency Counter on Digital Input
Database Location
Floating-Point Database Location
Raw Range
N/A
0 to 5000
0 to 1
0 to 1
0 to 5000Hz
-32768 to 32767
Multiplier Offset Log Multiplier
N/A N/A N/A
Table 4 - Sensor Sources
Multiplier
This is the scale factor to convert the raw input into actual engineering units.
Offset
Enter the scaling offset to add to the scaled engineering value.
Calibration (User) Offset
The calibration (user) offset shows the offset to shift the scaled value’s datum.
Include in SMS Responses
Enable this option to include this sensor in SMS responses.
Logging
Sample Rate
This is the rate (in seconds) at which the source is sampled.
Process Mode
Choose the processing mode from the list. The valid modes are:
27
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Mode Name
0
1
2
Instant
Full Period Average
Event
3
4
Scalar Average
(for Wind Direction)
One Minute Average
Description
Logs only the most recent sample
Logs the average of all samples taken over logging period
(Only valid for pulse input sources) Logs non-zero samples.
If the logging rate is 0, then any pulse is logged immediately.
If the logging rate is > 0, then the total accumulated in the period is logged only if it is not zero. In this mode, if there was no sample logged at the last log time, a zero sample is also logged, time stamped with last log time/date. This is required for time series management purposes.
Logs the average of all samples taken over the logging period, but uses scalar calculations to calculate the average.
Logs the average of all samples taken over last minute prior to logging
Table 5 - Sensor Modes
Normal Log Rate
Enter the logging rate (in minutes) for the sensor - when there are no active alarms in the sensor. If you wish to log digital data on change of state you can enter a value of 0. If this parameter is left at 0 for analogue sources, they will not be logged.
Alarm Log Rate
This is the logging rate (in minutes) for the sensor
– when there are one or more active alarms in the sensor.
Reject Below (Low)
This option is used to enter a simple rejection value. Any value equal to or below this will be ignored and the last “good” value retained.
Reject Above (High)
This option is used to enter a rejection value. Any value equal to or above this will be ignored and the last
“good” value retained.
Log if delta exceeds
This indicates the amount the latest processed value (in actual engineering units of the sensor) must differ from the last logged value in order to be logged.
Note: The delta logging (if enabled by having a non-zero delta set-point) is done at the time the logging would normally occur for the sensor as configured. All the delta decision does look at the last value that was actually logged and compare it to the newly processed sample value. If the difference is greater than the configured delta value, then the sample is actually logged.
The Normal Log Rate must be equal to or faster than the Routine Log Rate if that is also enabled.
First Routine Log (hour)
This is the hour in the day when the first routine log hour will occur.
Routine Log Rate
This is the interval at which a routine log is taken after the first hour is reached.
Auxiliary Logging Control
You can also configure the extended datalogging options using the logging flags. The list of the available flags are given below.
1. Log Minimum value sampled in the log period.
2. Log Maximum value sampled in the log period.
3. Log Standard Deviation of samples in log period.
28
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
4. Log Calculated Flow Rate (in l/s) over log period or Log Accumulated Volume for sensors with an analogue or frequency source.
5. Log Check Count.
Miscellaneous Settings
Supply Log Rate
Enter the logging rate for the supply voltage. Choose a value between 1 and 1440. Set this parameter to zero to disable logging.
RSSI Log Rate
Enter the logging rate for RSSI. Choose a value between 1 and 1440. Set this parameter to zero to disable logging.
Temp Log Rate
Enter the logging rate for the temperature. Choose a value between 1 and 1440. Set this parameter to zero to disable logging.
29
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.3.5 Alarms Configuration
Use the alarms configuration menu to decide which of the six alarms you want to configure.
Enable:
Tick the box in the Enable column to enable an alarm.
Sensor:
Choose the sensor which you want to activate the alarm for from the list.
Trigger:
Enter a value in engineering units that you want to use as the trigger point for the alarm. When the scaled value crosses this limit the alarm will become active. The trigger direction is determined by the reset level.
Reset:
Enter a value in engineering units that you want to use as the reset point for the alarm. When the scaled value falls below this limit the alarm will be deactivated. If the reset level is set to a value greater than the trigger level then the alarm is reverse acting. This mode is normally used for low voltage or low water level type alarms.
Duration:
This is the time in seconds to delay alarm activation. This can be used to implement alarm hysteresis for analogue data sources that vary. If the data source is one of the internal counters, then this time is used to totalise individual sample values. If the total over the given alarm duration is above the trigger level then an alarm is generated. Typically this feature is used for rainfall alarms.
30
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.3.6 SMS Numbers
This is the place to configure the phone numbers for SMS text messaging initiated by the iCE3. These numbers are only applicable when the connection mode is set to SMS.
7.3.7 User Configuration
This section enables to set different user configurations (maximum 20).
31
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
7.3.8 GPS Configuration
This is the place to configure the GPS settings if the GPS functionality is enabled. The GPS functionality is disabled when the schedule output is inactive. When the schedule generates a timed event, the GPS is powered up and the position is regularly sampled for the duration. If the GPS schedule is configured and valid values have been obtained, these are included in any call-in packet. They are also logged at the rate defined if it is non-zero.
GPS Log Rate (mins)
This is the rate (in minutes) at which the GPS values are logged.
Start Time
Enter the time at which the GPS starts logging the values.
End Time
Enter the time at which the GPS scheduler must stop.
Duration
Enter the duration in seconds that you want to keep each GPS session active.
Interval
This is the length of time in minutes between each successful GPS logging sessions.
Alarm Interval
This is the length of time in minutes between each successive GPS sessions when there are one or more active alarms in the iCE
3
.
32
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
8 SMS (Text) Commands
The iCE
3
FX is capable of responding to text commands received as SMS messages. This feature allows, for example the unit to be sent a text message to ascertain its status, change a setting or to be put in on-line.
The commands are not case sensitive. If an invalid command is sent to the iCE
3
FX it will reply with an invalid command message.
If the iCE
3
FX is already on-line with an IP session, the processing of the SMS message will be delayed until it disconnects from the IP session.
The three SMS commands supported are:
8.1 Request iCE
3
Information (RQ)
If the message “RQ” is received, the iCE
3 FX will reply to the sender with a message showing basic iCE 3 FX information. The parameters returned are:
iCE
3 date/time,
Site name
Serial number
Last logged value of any “sensor” that is enabled.
Supply Volts
iCE
3 internal temperature
RSSI. Last measured signal strength in dBm.
An example SMS response message to this command is:
12:13:26 > 11 Jun 2010 12:13:26,Site=My Site Name,S/No=AE1-1752, Rainfall=0.0,tot=12.5, Water Lvl= 1.657,Volts= 13.62,Temp=
19.9,RSSI=-71dBm
The sensor value is the last logged value, not the current value. If a particular sensor has not logged (log rate set to zero), then the last logged value returned in the SMS message will be 0.
8.2 Go On-Line (GOL)
If the SMS command
“GOL” is received the iCE
3 FX will immediately initiate a client IP connection sequence as if it was triggered by the scheduler or a manual command through the RS232 port terminal. It will remain on-line for the duration configured in the scheduler.
The iCE
3
FX will not send a reply to this SMS command. This allows an automated connection request to be sent by SMS and the initiation of the client IP connection is deemed to be an acknowledgement of the command.
8.3 Set the Scheduler On Interval (INT)
If the SMS command “INT=x” is received the iCE
3
FX will extract the parameter (x). If this is valid, the value will be used to update the On Interval in the Comms Scheduler.
This gives an external user or service the ability to change the call-in interval (cadence or frequency). The interval parameter must be between 2 and 1440 minutes.
If SMS message forwarding is enabled, the sender’s number and the actual message is sent out the RS232 port in this format. SMS: “Senders Number”,”Message”
E.g. SMS: “+64211234567”,”This is a test message”
33
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
9 Host Commands
To allow an intelligent host device to directly perform a small number of actions, there are four special AT commands that the iCE
3
FX will execute immediately without having to invoke the terminal menu.
These commands are only accepted by the iCE
3
FX when it is idle (not on an IP or CSD connection). If it is on-line, any data received on the RS232 port is transparently forwarded to the remote base.
9.1 Go On-Line (AT^IGOL)
If the command “AT^IGOL” is received the iCE
3
FX will immediately initiate an IP connection sequence as if it was triggered by the scheduler or by a “GOL” SMS command. It will remain on-line for the duration configured in the scheduler settings.
9.2 Request iCE
3
Real-Time Clock (AT^ICLK)
If the command AT^ICLK? is received, the iCE
3
FX will respond with its current date and time in a format that will allow simple parsing of the elements by the host.
E.g. for a clock date/time of 16 th
November 2009 at 12:34:56
AT^ICLK?
^ICLK: 2009,11,16,12,34,54
OK
Using this command to synchronise the clock in the host device should be done with care and validity checks. The time may be out by an hour from what is expected depending on the network time sync and the local daylight saving zone status. It is recommended only the minutes and seconds values be used.
9.3 Send manual SMS message (AT^ISMS)
This command allow the ad hoc sending of SMS messages by the host device which can be useful for site initiated alarms direct to personnel. It can be used in conjunction with the SMS message forwarding option where incoming messages are made available to the host device.
When the command “AT^ISMS” is received the iCE
3
FX will then check for and use two parameter strings.
The first string is the destination phone number to send the message to and the second string is the message text. Both strings must be encapsulated in quotes (“).
If the message is sent successfully, the iCE
3
FX will respond with an OK otherwise it will return an ERROR response. E.g.
AT^ISMS=”+6421763953”,”This is a test message from an iCE3”
OK
9.4 Request iCE
3
Received Signal Indication (AT^IRSI)
If the command AT^IRSI? is received, the iCE
3
FX will respond with the current RSSI value (in dBM).
AT^IRSI?
^IRSI: -73
OK
34
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
9.5 Set the Scheduler Call-In Interval (AT^IINT)
This command can be used to check update the On Interval setting in the Comms Scheduler. This gives the host the ability to dynamically change the call-in interval (cadence or frequency) based on certain criteria. If setting the interval, the value parameter must be between 2 and 1440 minutes.
E.g.
Set interval
AT^IINT=180
OK
Read interval AT^IINT?
AT^IINT: 60
OK
9.6 Set a Sensor Source Value for Logging (AT^IVAL)
This command can be used by an intelligent host device to set the value that can be used for a logging source. The command has two parameters. The first is the sensor number to set the value for (1-6). The second is the actual value to set.
E.g. This will set the floating point source value for sensor 1 to 123.45
AT^IVAL=1,123.45
OK
The command will result in an ERROR response if the sensor number is invalid or the input value can’t be decoded.
35
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
10 Data Logging
10.1.1 Overview
The iCE 3 FX has an internal data store capable of holding over a million time-stamped samples. This data is stored in a circular buffer in which the oldest records are overwritten when the buffer is full.
To enable this, the iCE
3
FX has six virtual “sensors” that may be configured to use a range of sources.
These sources may be from the real hardware I/O or alternatively from virtual database locations (registers) for future applications that may for example update these via a special program.
Each of the six virtual sensors can obtain information from one of the following seven data sources:
Analogue Input
Pulse Counter attached to the Digital Input
Simulated Pulse Counter enabled by the Digital Input
Frequency Counter attached to the Digital Input
Change of State on the Digital Input.
Internal Integer Database Location (for values obtained via user script or communications link)
Internal F.P Location (for values obtained via AT^IVAL command).
Each sensor can be set up to scale the raw data source into engineering units through the application of a multiplier and offset (slope and constant). The scaled value can be logged to non-volatile memory at rates between once per minute to once per hour or immediately in true event mode for pulse inputs.
It is also possible to configure a sensor to also log derived values such as minimum, maximum, standard deviation (all source types) or a calculated flow rate or volume (pulse type sources only). See the next section for further details on configuring these extended logging features as part of the Sensor Cfg menus.
The data logging time stamps will not be accurate until the iCE
3
FX real-time clock is valid (i.e. has been synchronised manually or from the network). However, all events will be in the correct chronological order as the clock is first initialised to a time one second after the timestamp latest logged sample in the event of a restart.
10.1.2 Logging Internal Parameters
There are three internal parameters that may be logged aside from the four
“free-format” sensors described above. These are supply voltage, RSSI and internal temperature. These may be logged at a rate between 1 and 1440 minutes (24 hours) if required by enabling them in the miscellaneous settings under the Sensor
Configuration menu.
10.1.3 Diagnostic Logging
There is also a “Modem comms diagnostics” logging function. If this function is enabled, several system events are automatically logged along with the RSSI (signal strength) value that was available at the time of the event occurring. The logging of RSSI in this case works in conjunction with any periodic logging of this parameter.
See the next section for the identifiers that are applied to the diagnostic events.
36
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
10.1.4 Logged Data Array Identification
The parameters that are able to be logged and their associated array ID codes are as follows:
Sensor sources selected that require hardware support (analogue, digital or supply volts) are only valid in later hardware (serial numbers from AE1-1581). In earlier units the value logged for these will be zero.
The diagnostic logging events are shaded. These only occur if diagnostic logging is enabled.
Array ID
0
Function
Cold or warm start. Note. The time stamp will not be exact, but will be in the correct chronological order with respect to the other logged data records.
Sensor 1 1
2
3
4
Sensor 2
Sensor 3
Sensor 4
Sensor 5 5
6
7
8
Sensor 6
Supply voltage. This is the voltage measured on the dc input to the iCE
Received Signal Strength Indication (RSSI). This is in dBm. iCE
3
FX internal temperature. This is in degC.
3
FX
9
61
62
Initial clock sync obtained from wireless network or user (following a cold or warm start).
IP connection was successfully established. This includes PPP and PCP socket.
IP connection failed at the PPP stage (connecting to the wireless network). 63
64
65
66
67
IP connection failed at the socket stage (connecting to the TCP server at the base).
CSD (dial-up) connection was successfully established. NOTE: CSD only possible on earlier units (serial number up to AE1-1580).
SMS text message was received.
Terminal session was invoked with AT^ITRM command via RS232 port.
Table 6 - Logged Data Array ID Definitions
Each virtual sensor’s logged data is identified by an array ID number. For the primary logged data, the ID is the sensor number itself. For the optional supplementary data (min, max, deviation, flow/vol), the array ID has an offset added to the sensor number that it is derived from. These ID offsets are as follows:
Minimum:
Maximum:
Diagnostic logging
Flow/Vol
+20
+40
(60-69)
+80
For example, Sensor 4 has been configured to log the average value, plus the maximumThree data arrays will be logged for this sensor at each logging interval with IDs of 4, 44 respectively.
Array 0 (zero) is a special array identifier and is used a system event log. Currently this is
only used to log a restart (either at the initial connection of power, on a watchdog reset or a user program start after an upgrade). The logged value in this case is always zero. In
HydroTel the identifier for this item is 0.
37
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
10.2 Unloading Logged Data
1. Connect to the iCE 3 FX using iLink 2012.
2.
Choose Manual, Automatic or “Unload all Data” option from the ‘Unload’ options on the main tool bar.
The Automatic unload option unloads the logged data automatically since the last unload process while the
Manual option enables you to enter the new start of data pointer and unloads the data manually. The
“Unload All data” option will cause all logged data to be unloaded from the logger.
Once unload has finished, a dialog will be displayed indicating the number of samples unloaded and processed. Click on OK to close the dialog box.
38
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
11 Troubleshooting
This section offers some possible answers to common installation and/or configuration issues.
11.1 iCE
3
will not respond in RS232 terminal (configuration) mode
Prompt: When the iCE
3 is in terminal mode through the either the RS232 port or via a CSD link, the current menu can be refreshed by using “R” or “r” command. Try entering an R, then Enter to attempt to refresh the menu.
Port Speed:
In the case of RS232, the computer port speed setting must match the speed configured in the iCE 3 . If you are unsure of the port speed, de-power and re-power the iCE 3 and check the
status LED for port speed indication. See Section 6.1.1.
Connection: If the iCE
3
is connected on an IP session, the RS232 terminal mode is unavailable. To disconnect from the IP session and return the unit to idle, thereby activating terminal mode, use the standard modem AT escape sequence (+++).
11.2 Unable to connect to the remote TCP or UDP server
SIM Card:
SIM PIN:
Check the SIM card is active and the account is in credit (if prepay).
Check the PIN code for the SIM card is correctly configured in the Modem section in Comms
APN: configuration menu.
The unit must be configured for a valid APN that must also match the SIM account APN.
The iCE
3
will not attempt to connect if the RSSI is 0 or less than -113dBm. Use a higher gain Signal: antenna if the signal strength is marginal.
IP Settings: The iCE 3 will not attempt to connect unless the primary IP and port are defined. I.e. the IP address is valid and the port is non-zero.
TCP Server:
The remote server is not available. Check that the TCP server is operational and configured correctly and also that the necessary firewall access is enabled for the TCP port and the complete dynamic IP address range that the iCE 3 could be allocated by the network.
11.3 iCE
3
will not respond to SMS requests
SIM Card:
SIM PIN:
Check the SIM card is active and the account is in credit (if prepay).
Check the PIN code for the SIM card is correctly configured in the Modem section in the
Comms configuration menu.
Power Mode: If Full Power Save is selected, the wireless modem is disabled and will not respond.
Connection: If the iCE
3 is connected on an IP (3G) session, the SMS feature is unavailable at that time; however the message will be replied to when unit returns to idle. Configure the scheduled IP
Signal: connection to minimise the time that SMS is unavailable.
The iCE
3
may not respond if the signal strength (RSSI) is very low. Use a higher gain antenna if the signal strength is marginal.
39
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
12 Host (RS232) Port - Cable Connections
12.1 Standard (Non-handshake) Device (No cable label)
This cable is for devices that do not require any special handshaking or prompt character recognition and are fitted with a DTE configured DB9 female connector. Such devices include the HyQuest Solutions iCE3 FX
type.
A cable of this type is required when configuring the unit from a PC using HyperTerminal® or other terminal
program. See Section 3.4.1 for more details on using the terminal mode for configuring the device.
iCE 3
DB15 (M)
Std Device
DB9 (F)
SCREEN
FRAME GND
TXD (IN) 2
3 TXD (OUT)
RXD (OUT) 6
0V (SIGNAL) 9
2 RXD (IN)
5 OV (SIGNAL)
CTS (OUT) 11
8 CTS (IN)
RTS (IN) 12
7 RTS (OUT)
Figure 4 - Standard Device Cable
12.2 Campbell Scientific Array Based Datalogger (Cable label
– “CSIU”)
This cable is used for Campbell Scientific array based dataloggers such as the CR10x, CR500 etc. The cable includes the necessary components to match the differing voltage levels between the iCE
3
RS232 port and the CSI datalogger’s serial port. It also handles both IP and CSD (dial-up) connections. See Section
6.3.2 for typical settings for this host type.
iCE
3
DB15 (M)
FRAME GND
SCREEN
CSI Datalogger
DB9 (M)
TXD (IN) 2
RXD (OUT) 6
0V (SIGNAL) 9
1N4148
2K2
9 TXD (OUT)
4 RXD (IN)
2 OV (SIGNAL)
1N4148
2K2
CTS (OUT) 11
DCD (OUT) 1
RTS (IN) 12
1N4148
3 RING (IN)
5 ME (OUT)
Figure 5 - CSI Array Based Datalogger Cable
40
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
12.3 Unidata Logger
– Standard (Cable label – “UNI1”)
This cable connects directly from the iCE 3 to a standard Unidata Star logger fitted with a DB25 female computer connector. This diagram assumes the DTE speed is set to 9600 baud as none of the baud rate setting links on the
Unidata’s DB25 are connected. See Section 6.3.3 for typical settings for this host type.
iCE 3
DB15 (M)
Unidata
DB25 (M)
SCREEN
FRAME GND
TXD (IN) 2
3 RXD (OUT)
RXD (OUT) 6
0V (SIGNAL) 9
2 TXD (IN)
7 OV (SIGNAL)
CTS (OUT) 11
4 RTS (IN)
RTS (IN) 12
6 DSR (OUT)
Figure 6 - Unidata Standard Datalogger Cable
12.4 Unidata Logger
– In NIWA enclosure (Cable label – “UNI2”)
This cable is used for Unidata dataloggers that have been installed in a NIWA pre-wired plastic enclosure and fitted with a DB9 female connector. Note that these enclosures have pins 2 and 3 of the DB9 reversed
when compared to a NIWA Unidata engine based datalogger such as the HydroLogger. See Section 6.3.3
for typical settings for this host type.
iCE
3
DB15 (M)
Unidata
(NIWA Variant)
DB9 (M)
SCREEN
FRAME GND
3 RXD (OUT)
TXD (IN) 2
RXD (OUT) 6
0V (SIGNAL) 9
2 TXD (IN)
5 OV (SIGNAL)
CTS (OUT) 11
RTS (IN) 12
7 RTS (IN)
6 DSR (OUT)
Figure 7 - Unidata (NIWA Variant) Datalogger Cable
41
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
12.5 NIWA Datalogger (with Unidata engine) (Cable label
– “UNI3”)
This cable variant is required to connect to the NIWA range of dataloggers such as the “HydroLogger”.
These devices are equipped with the Unidata logging engine and connection is via a DB9 female connector.
See Section 6.3.3 for typical settings for this host type.
iCE 3
DB15 (M)
NIWA Datalogger
(Unidata engine)
DB9 (M)
SCREEN
FRAME GND
TXD (IN) 2
2 RXD (OUT)
RXD (OUT) 6
0V (SIGNAL) 9
3 TXD (IN)
5 OV (SIGNAL)
CTS (OUT) 11
RTS (IN) 12
7 RTS (IN)
6 DSR (OUT)
Figure 8 - NIWA Logger Family Datalogger Cable
42
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
13 Firmware/Software Upgrade Procedure
13.1 Overview
This section describes the procedure to use when upgrading the firmware/software components in an iCE
3
.
The upgrade procedure has been carried out many times without issue. However, because the process does involve erasing and reprogramming of flash memory, it is important that a good, securely connected power supply is provided to the iCE
3
throughout the upgrade process.
13.2 File Naming Conventions
13.2.1 iCE
3
FX Executive Firmware.
The “Firmware” in the iCE
3 FX is analogous to the operating system in a PC. It is the Firmware that contains all the low level functions and library routines used by the Application Software.
The iCE
3
FX firmware is available as a zip file for downloading and flash upgrading using iLink 2012. The upgrade file is in the format:
iCE3FX_Firmware_xxx.bin where xxx is the firmware version e.g. iCE3FX_Firmware_150.bin iCE 3 FX Firmware, Version Vi/1.50
13.2.2 iCE
3
FX Application Software.
The “Application Software” in the iCE
3
FX is analogous to an application such as Word® on a PC. It is the software that contains the general functionality of the iCE
3
FX. This comes in three sections or “banks” (due to the memory configuration of the iCE 3 ) but runs as it were one single program.
The software upgrade files for Banks 1, 2 and 3 are in the format:
iCE3FX_Std_xxx_y.ice3fx where:
Std is the program variant xxx is the software version y is the program bank that this file should be loaded into iCE
3
FX Software, Version 1.30, Bank 3 e.g. iCE3FX_Std_130_3.ice3fx
13.2.3 Sierra Wireless Module OpenAT® Application
The HyQuest Solutions OpenAT® application runs in the Sierra Wireless modem module and manages the
IP connectivity. This application is available as a single file for downloading using iLink 2012. The upgrade file is in the format:
iQOatEmbedded_Q2698_Vy_xx.dwl where y_xx is the OpenAT® application version e.g. iQOatEmbedded_Q2698_V1_40.dwl Open AT® Application, Version 1.40
43
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
13.3 iCE
3
FX Automated Upgrade Procedure
iLink 2012 has an automated firmware/software upgrade tool. This tool includes several checks to confirm the validity of the components being installed. It can also be used to upgrade the embedded
OpenAT® application in this device.
For clarity, the example given in the following pages shows a full, automatic firmware, software and
OpenAT® application upgrade.
Make sure the required upgrade files are available on the computer. Ideally these should be located in C:\Program Data\iQuest\iLink2\Programs.
Connect to the iCE 3 FX using iLink 2012.
Go to the Program screen via the [Configuration][Program] menu option on the toolbar.
Click the Auto Upgrade button on the toolbar. The iLink 2012 will automatically detect the variant and type of the device and these fields will be populated with the appropriate configuration. If required, please select a different configuration from the drop down list and click OK. Click Yes to the warning messages in order to confirm the software and firmware upgrade. The progress of the upgrade can be seen on the status bar.
44
Once the process is completed, you can see a message saying "Upgrade completed successfully" on the status bar and the iLink 2012 window will show the current software status of the device.
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
If the process is cancelled or fails for any reason, the following dialog will appear. The whole process should be repeated to ensure that the iCE
3
FX is completely upgraded before deployment.
13.4 iCE
3
FX Manual Upgrade Procedure
iLink 2012 also allows you to upgrade the software and firmware manually. Please go through the below steps to do a manual upgrade of software and firmware for the iCE 3 FX.
Make sure the required upgrade files are available on the computer. Ideally these should be located
in the default deployment folders listed above in Section 13.2.
Connect to the iCE
3
FX using iLink 2012.
Click on the Manual Upgrade button under the Configuration tab.
If upgrading the firmware, first enable the “Upgrade Firmware” checkbox and select the new firmware file using the firmware browse button.
45
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
iCE
3
FX User Guide
Select the appropriate software files for Bank1, Bank2 and Bank3 using the browse buttons.
Enable “Upgrade OpenAT” checkbox if you wish to upgrade Open AT and choose the Open AT file using the browse button.
Click OK to load the selected programs to the device.
Once the process is completed, you can see a message saying "Upgrade completed successfully" on the status bar and the iLink 2012 window will show the current software status of the device.
14 User Notes
46
HyQuest Solutions (NZ) Ltd - PO Box 9466, Hamilton, New Zealand Tel: +64 7 857 0810 Email: [email protected]
Download
Advertisement
Key features
Wireless IP telemetry
Wireless IP / RS232 serial gateway
Supports static and dynamic IP addressing
Four power management modes
Data logging up to 6 virtual sensors
Alarm processing with multiple conditions
Optional GPS logging and clock sync
Frequently asked questions
The iCE3 FX is a wireless circuit extender that enables communication with remote equipment over a 3G network. It acts as a bridge between your local devices (like dataloggers) and a remote server, allowing you to monitor and control data from a distance.
The iCE3 FX offers several communication options: wireless Internet (IP) for data transfer over the internet, SMS (Short Message Service) for text-based updates, and FTP file transfer for uploading data to a remote server. You can choose the mode that best suits your needs.
The iCE3 FX offers four power management modes to optimize energy consumption. The 'No Save' mode keeps the modem constantly active, while 'Partial Save' and 'Full Power Save' modes conserve power when the device is idle. The 'RS232 Only' mode is for applications where the internal modem is not used.