eta SH Touch Operation Manual

Add to My manuals
64 Pages

advertisement

eta SH Touch Operation Manual | Manualzz

2012-11-14

EN_Englisch

Log Boiler

20-60 kW

Operation

Contents

Contents

2

Conditions for warranty, guarantee, liability ........4

Emission measurement ...................................6

Chimney renovation .......................................7

Boiler functionality ........................................8

Start-up ..................................................... 10

Checking water pressure, suitable fuel ................ 10

Correct quantity of wood ................................ 11

Water pressure, heating lines, cleaning lever ........ 12

Charging status of buffer storage tank ................ 13

Adding wood .............................................. 14

Ignition, closing doors ................................... 15

Closing ignition and insulation doors ................. 16

Adding fuel ................................................. 17

Safety ........................................................ 18

Safety devices to prevent overheating ................ 18

Maintenance ............................................... 20

Overview of activities .................................... 20

Each time the boiler is filled ............................ 21

Every 1 - 2 weeks ........................................ 22

Annually .................................................... 24

Every 3 years ............................................... 28

Approval, antifreeze, pressure equalisation, venting

32

Softened water, safety valve .......................... 33

Return riser and safety devices ....................... 34

Minimum heat consumption, buffer storage tank 35

Split wood will dry out in just one summer ......... 36

Heating value of wood .................................. 37

User interface .............................................. 38

Adjusting the date and time ............................ 38

Changing the language .................................. 39

Changing function block names ........................40

Alarm, error, warning, message ........................ 41

Opening the text menu .................................. 42

Buffer [Buffer] ............................................. 46

Overview, buttons, functions ...........................46

Buffer with solar .......................................... 47

Combination tank with solar ...........................48

"Buffer bottom max." for solar heating systems .... 49

Heating circuit [HC1] ..................................... 50

Overview, buttons and functions ...................... 50

Operating states ........................................... 52

Setting heating time slots ............................... 54

The heating curve ......................................... 56

"Day Heating threshold" and "Night Heating threshold" .................................................. 57

Adjusting the heating curve ............................ 58

Setting the "enable temperature" .....................60

Adjusting the "Set-back" ................................ 61

Service and maintenance records ..................... 62

Meanings of symbols

Important NOTICES for operation.

CAUTION: Failure to observe these notices can

result in property damage.

STOP: Failure to observe these notices can result in

personal injury.

www.eta.co.at

Preface

Preface

Dear Customer,

We are delighted to count you among our customers.

To ensure satisfactory operation of your new boiler, you need to know how to operate, clean and maintain it. This manual contains information and advice on much more than just the boiler itself.

Warranty and guarantee

You should also read the "Conditions for warranty, guarantee, liability" ( page 4 ) carefully. As a rule, these conditions will be satisfied by a professional heating technician. Nevertheless, inform the technician of our warranty conditions. All of the requirements we impose are intended to prevent damage that neither you nor we wish to occur.

Information worth knowing in this regard can also be found starting on page 32 .

Optimum use of the control systems installed in our boilers

There are two different access levels for the control system:

At the CUSTOMER level, you can adjust the control system to your wishes and needs without any risk of altering the system configuration set by the heating system expert.

Only your technician or a customer service employee should change settings at the SERVICE level. Before making any adjustments to these settings yourself, it is essential that you consult an expert.

Read this manual

carefully before starting up the system. This is the only way to ensure that you can operate your new boiler efficiently and with minimum environmental impact.

Take advantage of the knowledge and skills of an expert.

Only allow an expert to assemble, install and commission the equipment and make the basic boiler settings. Insist on receiving an explanation and training on how your new boiler functions and how to operate and maintain it.

Extended warranty for commissioning performed by an authorised partner company

If your newly installed boiler is commissioned by an authorised partner company or one of our customer service employees, we offer an extended warranty. Refer to our warranty conditions in effect at the time of purchase.

Service agreement

You can ensure the best care for your heating system by taking out a service agreement with one of our certified heating system contractors or our own customer service.

SH Operation

2012-11

3

Conditions for warranty, guarantee, liability

Conditions for warranty, guarantee, liability

We can only guarantee and accept liability for the function of our boiler if it is properly installed and operated.

Requirement for warranty, guarantee and liability is that this boiler be used in accordance with its intended purpose,

only for heating and hot water supply with no more than 2,000 full-

load hours annually, and, in particular, that the following general conditions be observed during installation and operation:

For set-up, a

dry room is required. In particular, only condensation dryers may be used as clothes dryers in the same room.

Local building and fire protection regulations must be observed.

The log wood boiler is suitable for use with air-dried

split logs with no more than 20%

water content and wood briquettes. Use with unsuitable fuels, especially refuse, coal and coke, and also wet wood, is not permitted.

The

combustion air must be free of aggressive

substances such as chlorine and fluorine from solvents, cleaning agents, adhesives and propellants, or ammonia from cleaning agents, to prevent corrosion of the boiler and chimney.

Water is the intended heat-transfer medium. For special anti-frost requirements, up to 30% glycol may be added.

Softened water is required for the initial fill-up of the heating system and for

refilling after repairs. For the initial fill-up, the value of 20,000 lt°dH for the system volume in litres multiplied by the hardness (in degrees of

German hardness) may not be exceeded. The

pH value should be set between 8 and 9.

Addition of hard water should be minimised to limit limescale build-up in the boiler. Set enough shut-off valves to avoid bleeding large amounts of water during repairs. Any leaks in the system must be repaired at once.

Ensure a

minimum return temperature of 60°C to the boiler.

A

safety valve (3 bar) as protection against excess pressure and a

thermal relief valve (95°C) to protect against overheating must be installed by the contractor.

To protect against air suction if the system cools off, an expert must provide a

sufficiently large

expansion tank or a pressure maintenance system. Sufficient air venting must also be ensured.

Open expansion tanks or underfloor

heating with permeable piping also have a high air intake, resulting in above-average boiler corrosion. Corrosion damage to the boiler due to improper air venting or high air intake is excluded from warranty, guarantee and liability.

Operation at lower power than the lowest power specified on the type plate is not permitted.

Only components provided by us may be used for expansion of the control system, except for commonly used units such as thermostats.

Cleaning and maintenance are required as specified in the user manual.

Repairs are only

permitted with spare parts

provided by us. The only exceptions are common standardised parts such as electrical fuses or fastening materials, as long as they possess the required features and do not restrict the functionality of the system.

4 www.eta.co.at

The

installing contractor is liable for proper installation according to the boiler's installation instructions and the relevant rules and safety regulations. If you as customer have installed the heating system partly or entirely without relevant training and in particular without up-to-date practical experience, without

having the installation checked by a trained and

responsible expert, we exclude defects in our delivery and consequential damages resulting from this cause from our warranty, guarantee and liability.

For

repair of defects carried out by the

customer or by third parties, ETA only bears the costs or remains obligated by warranty if this work was approved in advance by the customer service of ETA Heiztechnik GmbH.

Conditions for warranty, guarantee, liability

Subject to technical alterations

We reserve the right to make technical modifications without notice. Printing and typesetting errors or changes of any kind made in the interim are not cause for claims. Individual configurations depicted or described here are only optionally available. In the event of contradictions between individual documents regarding delivery scope, the information in our current price list applies.

SH Operation

2012-11

5

Emission measurement

Emission measurement

Why measure emissions?

It is a requirement for the carbon monoxide (CO) emissions of every boiler to be measured periodically. In Germany, this periodical measurement must also include a dust measurement.

There are several aspects of this that could go wrong, resulting in incorrect measurements even though the boiler fully and consistently complies with these limits when operating in accordance with the relevant standards.

Boiler and flue tube must be cleaned thoroughly

3 days before measurement

The chimney sweep will contact the owner of the boiler when the measurement is due to take place. The boiler and the flue tube must be cleaned thoroughly 3 days before the measurement takes place. The remaining charcoal stays in the fuel chamber.

Heat up the boiler after cleaning

After cleaning, the boiler must be heated up again.

This allows dust that was stirred up during cleaning to settle.

Under no circumstances clean the boiler and flue tube on the day of the measurement!

Cleaning on the day of measurement should be avoided as the chimney sweep's measuring probe would measure the unsettled dust, resulting in a falsely high dust reading.

The buffer must be empty at the start of the measurement

The boiler and the buffer should be shut down before the measurement. This is best done the night before to prevent the boiler from switching to partial load during the emission measurement.

Use half-metre logs for the emission measurement

For the emission measurement,

split half-metre

logs are to be used, stacked as tightly as possible in the boiler (no round logs). The fuel chamber should be filled as full as possible and the burnthrough openings on the grate must remain free.

Heat up boiler 1-2 hours before measurement

Heat up the boiler 1-2 hours before the chimney sweep's arrival.

Ensure sufficient heat consumption

Open all the radiator valves and turn the radiator thermostats to maximum.

Close doors at 100°C exhaust gas temperature

At 100°C exhaust gas temperature, close the ignition door and the insulation door. Do not open any doors before and during the emission measurement. Also, do not stoke the fire.

Switch boiler to emission measuring mode

In the boiler overview screen, tap . This switches the boiler into

emission measurement

mode and operates it for 30 minutes at full load.

The control system ensures that sufficient heat is channelled to the buffer, the heating circuits and the hot water tank. The button shines green and a countdown for the emission measurement mode is displayed.

Wait 10 minutes, then perform emission measurement

Once emission measuring mode has been activated

( ), wait for 10 minutes until the boiler has reached the required operating temperature and stable combustion is ensured. Then carry out the

emission measurement.

After the measurement

After the measurement, emission measurement mode can be deactivated by pressing again. If this button is not pressed, the boiler will automatically switch back to normal mode after 30 minutes.

6 www.eta.co.at

Chimney renovation

With its controlled induced-draught fan and adjustable minimum exhaust gas temperature, your new boiler will largely adjust to existing flues without the need for any special measures. Nevertheless, you should have the suitability of your flue checked by a chimney sweep or chimney builder.

If the draught exceeds 30 Pa in very tall flues, a draught-regulating damper is required.

Modern heating boilers are more efficient than older ones and thus produce smaller amounts of exhaust gas at considerably lower exhaust gas temperatures.

Flues with "too large a cross-section" in particular are no longer heated adequately. The moisture contained in the exhaust gases condenses in the flue and leads to very slow but inexorable destruction of old masonry chimneys.

Furthermore, if the diameter of the flue is too large, the exit velocity and temperature are too low. The exhaust gas does not have enough energy to rise and, in extreme cases, the smoke can flow down the roof.

If your flue does not have a water-resistant liner or its diameter is too large, it will need to be renovated with the addition of a moisture-insensitive inner lining. If the existing flue cross-section is adequate, a ceramic liner that is also resistant to chimney fires is preferable to a stainless steel liner when burning wood.

In the case of short flues that are not resistant to moisture, it may suffice to raise the lower limit for the exhaust gas temperature to 180°C in the boiler's control system. In addition an auxiliary air damper will help to keep the flue dry. If these measures are deemed satisfactory, the flue should be inspected to check whether it actually remains dry. This is best discussed with the chimney sweep.

Also keep in mind that chimneys have a limited service life. Timely renovation before the chimney wall has been destroyed can be performed quickly and easily by inserting a tube. But if the flue gas condensates have penetrated the mortar joints, then the entire flue must be dismantled and rebuilt.

SH Operation

Chimney renovation

Chimney renovation

2012-11

7

Boiler functionality

Boiler functionality

8

Wood gasification

Before wood can burn, it must first be converted into gas by application of heat. From 100°C, the moisture contained in the wood is driven off. From

200°C, the process of decomposition into 20% charcoal and 80% wood gas, a mixture of carbon dioxide, carbon monoxide, hydrogen, methane, methanol, various phenols, acetone and acetic acid begins. Gas is released from a temperature of

400°C. However, a temperature of at least 900°C is required to fully break down phenols (wood tar) into combustible carbon, carbon monoxide and hydrogen; 1100°C is better. In addition to a high temperature, breaking down complex compounds into wood gas also requires time; this explains why the gas flame of a wood fire lasts so long.

Large wood supply in the fuel chamber

At the base of the stack of wood in the fuel chamber, a small gasification fire is maintained through a controlled flow of air (primary air) (1).

The boiler's control system regulates the output of the gasification fire via the flow of primary air

(2). The wood gas is drawn downwards into a hot combustion chamber. This prevents the stack of wood in the fuel chamber from undergoing uncontrolled gasification and starting to burn and makes it possible to have a boiler with a large supply of wood that burns slowly for a long time.

Mixing nozzle and complete turbulence

A mixing nozzle (3) is located between the fuel chamber and the combustion chamber. Here preheated combustion air (secondary air) is mixed with the wood gas. The flame exiting the mixing nozzle hits the hot bottom of the combustion chamber with high velocity and experiences further turbulence (4), ensuring that every bit of combustible gas finds sufficient oxygen for complete burnout.

Complete burnout in the glow zone

To achieve uncooled combustion at high temperatures, the patented glow-zone combustion chamber is made from refractory brick and is also thermally insulated (5). In this glow zone, the flame has enough time at temperatures between

900°C and 1100°C to break down and burn the very last of the resistant carbon rings (phenols) from the lignin in the wood. This enables the log boiler to go below the limit of 100 mg of carbon monoxide in the exhaust gas per MJ of output.

4

3

1

7

www.eta.co.at

2

5

6

Optimum fuel efficiency with lambda control

Gasification of the wood (output) can be controlled via the flow of primary air. Through use of the lambda-controlled secondary air (6), combustion is kept clean and highly efficient. A lack of air means there is not enough oxygen for complete combustion. On the other hand, too much air also results in incomplete combustion as it cools the fire. Below 700°C, not all of the wood gas is burned. Too much air also pulls unused heat out of the boiler. The lambda probe ensures optimum combustion and maximum fuel utilisation not only with selected wood on the test stand, but also in everyday operation.

Turbulent heat exchanger with simple cleaning

The hot gas only enters the cold section of the boiler following complete combustion. Once in the cold section, it transfers its heat to the boiler water, first while smoothly flowing through a long ash collection duct (7) and then turbulently through heat exchanger tubes equipped with turbulators.

The more turbulent the flow, the more the gas comes into contact with the tube walls, thus ensuring maximum transfer of heat to the boiler water. This ensures low exhaust gas temperatures and high efficiency. Pulling the cleaning lever about 10 times prior to opening the boiler to refill with fuel moves the turbulators up and down in the heat exchanger tubes. The resulting fly ash drops into the ash collecting duct, leaving the heat exchanger clean.

Induced-draught adjusts to the flue

Thanks to the induced draught concept, the entire interior of the boiler is under a negative pressure.

This means that no smoke or low-temperature carbonisation gases can escape from the boiler regardless of the phase of operation. The induceddraught fan accommodates every flue, even those with small cross-sections. Speed control and continuously adjustable dampers for combustion air make draught limiters in the flue virtually unnecessary. Setting a minimum exhaust gas temperature prevents condensate formation in masonry flues and allows the low-temperature capability of modern flues to be fully utilised.

SH Operation

Boiler functionality

2012-11

9

Start-up

Checking water pressure, suitable fuel

Checking water pressure, suitable fuel Start-up

Check water pressure

With a log boiler, it is no trouble to glance at the pressure gauge daily or at least regularly. In houses with up to three storeys, the water pressure in a cold system should be between 1 and 2 bar, for a warm system between 1.5 and 2.5 bar.

Suitable fuel

The firewood must be air-dry, i.e. it must have dried for at least one year and have a

water

content under 20%. We recommend using halfmetre split logs with an average diameter of 10 cm.

8 - 10 cm

7 - 9 cm

The most common defects in a heating system, i.e. leaks and boiling over, result in a low water alert.

In the event of insufficient volume compensation, water is released via the safety release valve. Either the expansion tank is too small, the diaphragm in the expansion tank is torn or a tap or valve between the heating system and the expansion tank was shut unintentionally. In this case, open the valve or tap, remove the lever or hand wheel and attach it to the valve with a wire.

Water will generally need to be added after the radiators have been bled.

Minimum pressure

To establish the minimum pressure for a cold heating system (especially when the buffer is also cold from top to bottom), determine the height of the space requiring heating above the heating system's pressure gauge and add three metres. The result is the minimum pressure in metres. Dividing the metre value by ten gives you the minimum pressure in bar, as shown on most pressure gauges.

Return temperature at least 60°C

The boiler return temperature should be at least

60°C to prevent corrosive condensation of flue gases in the heat exchanger. The control system monitors the return temperature. If the boiler return temperature is too low, a warning appears on the display.

12 - 15 cm

13 - 16 cm

Boards may only be added between the logs and in no case should they be included in the first layer as they would block the burn-through opening in the grate.

Small pieces of firewood may only be used for heating if added as a minor component to the primary fuel. The smaller the pieces of firewood, the less of them should be added.

Wood briquettes measuring 6 cm to 10 cm in diameter in compliance with ÖNORM M 7135;

Germany: 1.BimSchV 15 July 1988 Fuel Class 4.

Only one oversized log per boiler filling

Only 1 oversized split log or 1 stump can be placed in the top layer, but no more. Complete burning may require 2 combustion phases.

Unsuitable fuel

Wet fuel with a moisture content in excess of 20% may not be burned as it results in condensation which can lead to corrosion of the boiler's fuel chamber walls. The following may not be burned: rubbish, paper and cardboard (only for start-up), wood dust from sanding, sawdust, wood chips smaller than thumb-sized, coal and coke, and fuels generally prohibited by local air quality regulations, such as railway sleepers, plastic-coated plywood, impregnated wood etc.

10 www.eta.co.at

Correct quantity of wood

Start-up

Correct quantity of wood

When not much heating is needed only place a small amount of wood in the boiler

Absorbing all the heat from a boiler fully loaded with wood would require buffer storage tanks larger than needed for winter operation and also larger than those normally installed. When less heat is required, i.e. for hot water in the summer, or during the evening shortly before the night set-back, only load the boiler with the amount of wood actually needed.

The table below displays the amount of wood needed for summer operation for different boiler sizes (= fuel chamber capacity), wood type, buffer volume and buffer charging status. Bear in mind that an "buffer top" temperature sensor that is installed too low reduces the usable volume.

If the living space already needs some heating, start with the amount of wood in indicated in the table below. To establish the correct amount, approach the fully charged buffer state slowly, adding one or two more logs every heating

Correct quantity of wood

cycle. If too much wood is loaded, an emergency shutdown of the boiler will occur. If the boiler overheats, the flow of air is stopped. The fire will go out, but the hot wood will continue to smoulder for a while and the unburned wood gas resulting from the lack of air will create tar deposits in the boiler and flue. This happening once or twice in an emergency is not a problem. However, if this situation occurs every day, the boiler's heat exchanger will become clogged with tar.

Note the energy density of the fuel

The energy content of 50 litres of wood briquettes corresponds to 100 litres of beech wood or 150 litres of spruce.

Current buffer charging status is shown in overview

The current buffer charging status in percent is shown in the boiler [Boiler] and buffer [Buffer] overviews. The buffer charging status is the average of the three buffer temperatures (top, middle, bottom) between 30°C (=0%) and 80°C

(=100%).

SH20, SH30

Maximum fuel load

Briquettes Beech Spruce

1/4

1/2

1/4

1/2

3/4

Full

1/4

1/2

3/4

Full

Buffer charging status

25%

20%

15%

10%

5%

0%

65%

60%

55%

50%

45%

40%

35%

30%

Buffer size

3,300 l 2,200 l

90% 85%

1,650 l

80%

1,100 l

70%

85%

80%

75%

70%

78%

70%

63%

55%

70%

60%

50%

40%

55%

40%

25%

10%

48%

40%

33%

25%

18%

10%

0%

30%

20%

10%

0%

0%

SH40, SH50, SH60

Spruce

Maximum fuel load

Beech Briquettes

1/4

1/2

3/4

Full

1/4

1/2

1/8

1/4

SH Operation

2012-11

11

Water pressure, heating lines, cleaning lever

Water pressure, heating lines, cleaning lever Start-up

Boiler start-up

Check water pressure

Before starting up, check the heating system's water pressure (see also page 10 ). In houses with up to three storeys, the water pressure in a cold heating system should be between 1 and 2 bar, for a warm system between 1.5 and 2.5 bar.

Open heating lines

If the system is new or has been out of operation for some time, verify whether the

return riser

mixing valve is in "AUTO" position and all

shut-off valves in the heating lines are open.

Keep ball valves completely open to avoid ruining the seals. Open valves by turning anti-clockwise, and then turn back 1/4 turn from the fully open position to relieve pressure on the valve stem.

Operate cleaning lever

With the insulation door still closed, clean the heat exchanger by

operating (10x) the cleaning lever

on the side.

Open insulation door, draught fan starts automatically

When the insulating door is opened, the draught fan starts automatically and the on/off button in the boiler overview shines green. The operating mode changes to "Insulation door open".

10x

12

Afterwards, leave the lever pointing towards the rear of the boiler. Then the turbulators remain in position in the water-cooled heat exchanger.

www.eta.co.at

Buffer charging status

Start-up Buffer charging status

Check fuel chamber

Use the poker to distribute ashes and charcoal evenly throughout the fuel chamber. In the panels,

the two upper openings for primary air must

be free. Also, the 3 burn-through openings in

the grate must stay open so that the fire reaches the combustion chamber during ignition.

Primary air openings

If the draught fan does not start, it has been deactivated by the safety temperature limiter due to boiler overheating and a corresponding warning appears on the display. The safety temperature limiter can be manually released as soon as the boiler temperature has fallen below 70°C.

Open fuel chamber door

The draught fan must be running before the fuel chamber door is opened so that any combustion gas can be extracted from the fuel

chamber. If the boiler has not safely cooled, no boiler doors may be opened without an operating draught fan. A sudden inflow of air in the presence of smouldering wood may result in an explosion.

Fuel chamber door

Burn-through openings

Check buffer charging status

Before starting the boiler, check the current

buffer charging status to avoid adding too much

wood. The table on page 11 shows how much wood should be added. The buffer charging status is shown in percent values in the boiler overview.

Combustion chamber door

The fuel chamber door is always closed during both start-up and heating operation. It is opened only when ash is removed from the boiler.

Pay particular attention to the

different energy

densities of the fuels.

SH Operation

2012-11

13

Adding wood

Adding wood Start-up

Place logs close together in fuel chamber

Add the required amount

of closely spaced logs

to the fuel chamber. Stack the logs instead of throwing them in at random. Always place the first layer of logs lengthwise.

Place only 1 oversized log on top

Only 1 oversized split log or 1 stump can be placed in the top layer, but no more. Two combustion phases may be needed for complete burning.

Adjust log over burn-through opening

Lift the bottom log above the burn-through

opening with the poker and place pieces of charcoal (from the fuel chamber) or small pieces of wood under it so that

the burn-through

openings in the grate remain clear. To make ignition easier, next to the log

on the left and right there should be a small gap separating it

from the neighbouring logs.

Brushwood, coarse wood chips or carpentry waste should be added only as a secondary fuel among the split logs

First place half of the required amount of logs in the fuel chamber (at least 3 layers). Then alternately add the secondary fuel (brushwood, coarse wood chips or carpentry waste) and additional logs.

The smaller the pieces of secondary fuel are,

the more logs must be added between them.

14 www.eta.co.at

Start-up

Ignition, closing doors

Ignition, closing doors

Ignite the fire with cardboard and newspaper

Place crumpled paper or a few pieces of cardboard in front of the first layer of wood and ignite it.

The draught fan sucks the flame over the tightly stacked logs, causing them to ignite more quickly.

For heavy, smooth hardwood, larger pieces of kindling may be needed for ignition.

Never use petrol, turpentine or similar

materials as an "ignition aid": risk of explosion!

Under no circumstances should brushwood, coarse wood chips or carpentry waste be used

for the bottom layer. Such fine material burns too quickly, resulting in incomplete combustion in the combustion chamber, which is still cold during start-up. As a result, soot builds up in the heat exchanger.

Close fuel chamber door, open ignition door

Close the fuel chamber door and then open the ignition door.

The

ignition door should be kept open after

ignition to monitor the progress of the fire. It should only be closed once the boiler's exhaust gas temperature has reached 100°C. How long it takes the fire to start depends on the type of wood used; rough spruce may need only 2 minutes, smooth beech may require 5 minutes until the required exhaust gas temperature of 100°C is reached.

If the boiler is not to be started up yet, close both doors and in the boiler overview,

press the on/off button

so that it shines red.

SH Operation

2012-11

15

Closing ignition and insulation doors

Closing ignition and insulation doors Start-up

At 100°C exhaust gas temperature, close ignition door and insulating door.

Once a few logs are burning well and the

exhaust gas temperature is over 100°C, close

the ignition door and the insulating door. The exhaust gas temperature is displayed in the boiler overview. At over 100°C, an arrow appears to indicate that the ignition door should be closed.

Avoid opening boiler doors unnecessarily

Avoid opening the insulating door and the fuel

chamber door unnecessarily in heating mode.

That disrupts the boiler control and increases fuel consumption. Also keep the ignition door and the combustion chamber door closed.

Never open the insulating door and the fuel

chamber door when the boiler is in "Calibrating

lambda probe" or overtemperature mode.

Completion of heating mode with ember burnout

Once the wood in the boiler has been burned

(residual oxygen content below 15% for more than

5 minutes) or the exhaust gas temperature falls below 80°C, the boiler automatically starts burnout

("Ember burnout" mode). If the

de-ash button

was not pressed, the boiler frees the secondary air ducts of ash with fresh air.

Charcoal and

embers remain in the boiler by design so that newly added wood can be ignited more easily.

Complete ember burnout for cleaning

For cleaning after the last heating operation, in the overview

press the de-ash

button (which then shines green).

When the insulating door is closed, the boiler automatically switches to ignite mode and, once the residual oxygen content is below 15%, to heating mode. The boiler is now in heating mode and regulates the combustion of the wood independently.

Ember retention is then deactivated and the boiler performs a complete ember burnout (duration

~1 hour), burning most of the charcoal in the fuel chamber to make subsequent cleaning of the boiler easier.

16 www.eta.co.at

Start-up

Adding fuel

You should

only add fuel when the buffer

charging status is below 30% and the fuel

chamber has burned to empty.

If wood has been added and there are still embers in the boiler, it automatically tries to ignite the wood again. If the wood is hard to ignite and there are only a few remaining embers, it may help to push the charcoal together in the middle before refilling. If the remaining embers do not ignite the wood, light it with paper and cardboard through the ignition door.

Adding fuel

Adding fuel

SH Operation

2012-11

17

Safety

Safety devices to prevent overheating

Safety devices to prevent overheating Safety

Safety devices to prevent overheating

The following safety chain takes effect if the boiler exceeds the operating temperature for any reason:

• over 87°C -> pump safety run

• over 90°C -> draught fan switched off

• over 95°C -> thermal emergency cooling valve

• over 105℃ -> safety temperature limiter

• over 3 bar water pressure -> safety valve

Pump safety run

If the boiler temperature exceeds 87°C (=factory setting [Pump safety run]), the pump safety run starts.

All heating pumps and boiler pumps that are connected to the boiler control are

switched on to dissipate heat from the boiler.

This action prevents the boiler temperature from rising further and triggering further safety devices such as the safety temperature limiter and thermal emergency cooling valve. This emergency cooling is indicated on the display by "heat dissipation".

The heat dissipation is limited with the

maximum flow temperature set in the

heating circuits and the hot water setpoint

temperature.

Boiler overheating

If 90°C boiler temperature (factory setting [Boiler max.]) is reached,

the control system switches

the draught fan off and a warning message appears on the display. Reasons for a boiler temperature increase include:

• too much wood added (see page 11 )

• heating circuits unexpectedly switched off

• heating pump failed

• heating line inadvertently shut off

Once the boiler temperature has fallen below 86°C, heating resumes automatically.

During such emergency shutdowns

the wood

continues to emit gas and the unburned wood

gas causes tar deposits in the boiler and

chimney.

Thermally actuated drain valve (to be supplied by technician)

Independent of the other safety devices, the thermal emergency cooling valve

is non-electrically triggered at boiler temperatures between

92°C and 97°C. The thermal emergency cooling valve is opened by means of a sensor system containing a liquid that expands when heated (no electricity required). It causes the

boiler's safety heat exchanger to be flooded with drinking

water, dissipating the excess heat out of the boiler into the sewer.

If the thermal emergency cooling valve activates frequently, check whether it activates at a temperature below 92°C and replace it if necessary.

Safety temperature limiter

For additional safety against boiler overheating, a

safety temperature limiter is built into the boiler.

When a boiler temperature of 105°C (tolerance

100°C to 106°C) is reached, the

power supply to

the draught fan is switched off.

If the boiler temperature falls below 70°C, the safety temperature limiter can be manually reset.

The reset button is recessed into the door frame above the fuel chamber door. To reset, press it deeply into the recess.

Safety temperature limiter

Safety valve against excess pressure (to be supplied by technician)

The most common cause of safety valve activation is either an undersized expansion tank or heating lines that have been shut off. The safety valve also serves as a backup safety device to prevent boiler overheating in the event that all other devices in the safety chain fail.

18 www.eta.co.at

Safety

The

safety valve must be installed in the flow

line right where it leaves the boiler, as it cannot dissipate any heat if installed in the return line.

In rare cases when neither the thermal emergency cooling valve nor the safety temperature limiter trips, the pressure and temperature will increase until the safety valve opens. If this occurs, it is crucial to check that the thermal emergency cooling valve and the safety temperature limiter are working properly. If cold water is drawn from an on-premises well with its own pump, a power failure may be the reason for failure of the thermal emergency cooling valve. If this occurs frequently, a larger air chamber in the building's water supply or a separate air chamber for the thermal emergency cooling valve is required.

Safety devices to prevent overheating

SH Operation

2012-11

19

Maintenance

Overview of activities

Overview of activities Maintenance

Regular cleaning and servicing

To ensure that the boiler operates optimally and reliably, it must be cleaned and serviced at regular intervals.

Maintenance and cleaning of the boiler must be performed within the specified periods (see table).

Cleaning and maintenance overview

The table provides an overview of the required cleaning and maintenance.

The "To be done by" column indicates which activities you as customer can deal with and which must be performed by an expert.

Activity

Operate cleaning lever

Check water pressure

De-ash boiler

Check walls of ash collection duct

Check safety valves and thermal emergency cooling valve

Clean casing and display

Remove ash behind panels

Clean primary and secondary air duct

Check and clean flue tube

Clean heat exchanger box

Check turbulators for tar deposits

Clean draught fan

Check safety valves

Check door seals

Check safety devices

Clean the lambda probe

Inspect seal on heat exchanger cover

Perform emission measurement

Calibrate lambda probe

Perform heating test

Reset maintenance counter

Every 1 - 2 weeks

X

X

X

X

X

X

Frequency

Annual maintenance

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Every

3 years

X

X

X

X

X

X

X

X

X

X

X

X

To be done by

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Customer

Expert

Expert

Expert

Expert

Expert

Expert

Expert

20 www.eta.co.at

Each time the boiler is filled

Maintenance

Operate cleaning lever

The heat exchanger's cleaning lever must be operated 10x before every boiler start-up.

10x

Each time the boiler is filled

Check water pressure

In houses with up to three storeys, the pressure in a cold system should be between 1 and 2 bar, for a warm system between 1.5 and 2.5 bar.

If the boiler pressure is too low, fill the cold heating system to approx. 2.0 bar. This will keep the pressure below the activation pressure of the safety valve (3.0 bar) even though it rises when the water expands with increasing temperature while heating up to operating temperature.

Afterwards, leave the lever pointing towards the rear of the boiler. Then the turbulators remain in position in the water-cooled heat exchanger.

SH Operation

2012-11

21

Every 1 - 2 weeks

Every 1 - 2 weeks Maintenance

De-ash boiler

Perform complete ember burnout

During final heating operation, in the overview

press the de-ash

button (which then shines green).

Scrape ash and charcoal from fuel chamber into combustion chamber

The insulating layer of ash in the fuel chamber is necessary for ember retention, so there should be

approximately 5 cm of ash left in the fuel

chamber. Scrape the remaining ash from the fuel chamber into the combustion chamber. Some pieces of charcoal will drop into the combustion chamber during this process; these are best left there. The charcoal will burn during the next combustion cycle and the ash will protect the bottom of the combustion chamber against premature wear.

Ember retention is then deactivated and the boiler performs a complete burnout (duration ~1 hour), burning most of the charcoal in the fuel chamber.

Clean combustion chamber and ash collection duct

Once the boiler has cooled off, rake the ash out of the fire box and the ash collection duct into the ash collection pan. The rear end of the ash collection duct must also be cleared out so that there is no ash in front of the lambda probe head. If the draught fan is running while you are removing the ash, remove it from the boiler slowly and gently to avoid stirring it up too much and having it blown out through the flue.

Combustion chamber

No embers in the rubbish bin

If there are still embers in the ash, leave the ash in a closed, non-flammable container for at least 2 days. Only put it in the rubbish bin when there are really no more embers present.

Do not slide the ash collection pan into the boiler

Although the ash collection pan can be pushed into the ash duct of 40 - 60 kW boilers, it is not intended for this purpose and would be destroyed by the high temperatures there.

Ash collection duct

22 www.eta.co.at

Maintenance

Check walls of ash collection duct

The walls of the ash collection duct

may be white

to brown in appearance. If they are black with soot, either too much wood was burned at too low a heat consumption ( page 11 ), the fire was not lit correctly at start-up or, in very infrequent cases, the lambda measurement gave incorrect values.

Every 1 - 2 weeks

Clean casing and display

Clean the boiler casing with a damp cloth and

(if necessary) a commonly available household cleaner (no scouring agents). Clean the display only with a damp cloth (no cleansing or scouring agents).

Check safety valves and thermal emergency cooling valve

The safety valve and the thermal emergency cooling valve

may not drip. Dirt may be stuck in the seal seat.

Safety valve

Thermal emergency cooling valve

Only perform further steps on weekdays, never check on weekends in a cold winter as there will probably be no heating technician available if the seal is defective. If the valve drips, open the safety valve with a quarter turn of the red cap and rinse it out (danger of scalding). If the valve still cannot be closed tightly after being rinsed several times, it must be cleaned by a plumber or replaced.

If a solar heating system is to be connected to the buffer storage tank, the safety valve installed there must also be inspected.

SH Operation

2012-11

23

Annually

Annually Maintenance

Annual maintenance

In preparation, perform weekly maintenance

Before annual maintenance, all steps of the weekly maintenance must be performed.

Before starting work, let the boiler cool off and switch it off with the mains switch.

Remove ash behind panels

The panels are hung from a bolt at the top. Lift the panels slightly, pivot them out and remove them from the fuel chamber. Remove the ash behind them.

After removing the front panels, remove the guard plate between the fuel chamber and ignition doors so it cannot fall down.

Clean secondary air openings

Remove both parts of the grate and remove the ash beneath them. Then

remove the ash from

both secondary air openings at the sides.

When inserting the grate, take care that the seal

(above the secondary air opening)

is in the semi-

circular groove on the grate.

Panels

Guard plate

Clean primary air openings

The openings for primary air are behind the panels around 10 cm above the floor of the fuel chamber. Clean these openings with a vacuum cleaner.

Check and clean flue tube

Check that the flue tube from the boiler to the chimney is

air-tight. The points at which dust or flue gas escape can be identified by discolouration.

The exhaust gas pipe can be sealed with heatresistant silicone (400°C) and aluminium sealing tape. Since there are many different alternatives for connecting the exhaust gas pipe to the chimney, it is best to consult the chimney sweep regarding leaks in the connection.

Flue pipes with a horizontal run longer than 1 metre must be brushed out.

24 www.eta.co.at

Maintenance Annually

Clean heat exchanger box

Open the heat exchanger cover (at the top of the boiler in front of the exhaust gas pipe) and

remove

the ash from the heat exchanger box with a vacuum cleaner. Do not close the chamber again until the draught fan has also been cleaned.

Clean draught fan

Disconnect the power supply, remove the 3 wing screws and pull out the fan. Clean the fan wheel with a soft brush, toothbrush (no wire brush) or compressed air so that the motor shaft does not get bent.

If there

are tar deposits on the draught fan's

wheel, that is a sign that too much wood is always being added (see table on page 11 ), or the lambda probe is defective and providing false measurements.

Check turbulators for tar deposits

Check the turbulators in the heat exchanger for

tar deposits.

The turbulators must be removed as soon as

the cleaning lever becomes difficult to move.

If the turbulators and their supporting brackets have tar deposits, the cause is often the addition of more wood than is needed to meet the actual heating requirements (see page 11 ).

SH Operation

Check seal

Before installing the draught fan,

check the

seal. Make sure that the plug connection on the installed draught fan is pointing to the right (as seen from the back of the boiler).

2012-11

25

Annually Maintenance

Check door seals

Check the seals on the 3 boiler doors (fuel chamber door, ignition door, combustion chamber door). The door handles must close firmly (with force), and the sealing edges of the door frames must leave a clear impression on the sealing cord.

In particular, check the seal between the carbonisation gas extraction duct and the fuel chamber door.

0.5 - 1 mm

The boiler door hinges are adjusted in the same manner. Loosen the two hexagonal nuts next to the hinges and move the mount by 0.5 - 1 mm towards the rear of the boiler.

Leaks can be identified by variations in the colouring on the seal or by using a cigarette lighter while the draught fan is running. The flame will be drawn toward the leak. If leaks are found, it is usually sufficient to

adjust the hinges and the

closing roller mount. It is not always necessary to replace the sealing cords.

To adjust, open the door and lift it from its hinges.

Loosen the two hexagonal nuts next to the closing roller mount and move the mount by 0.5 - 1 mm towards the rear of the boiler.

0.5 - 1 mm

Then tighten the hexagonal nuts, reattach the boiler door and check that it closes tightly.

26 www.eta.co.at

Maintenance Annually

SH Operation

2012-11

27

Every 3 years

Every 3 years Maintenance

Maintenance by expert, every 3 years or after alert by control system

In preparation, perform weekly and annual maintenance

Before this maintenance, all steps of the weekly and annual maintenance must be performed.

Before starting work, let the boiler cool off and switch it off with the mains switch.

Check safety devices

Check safety valves, thermal emergency cooling valve and safety temperature limiter

See page 23 .

Clean the lambda probe

Use a pipe wrench to unscrew the lambda probe's retaining tube.

Clean the

lambda probe's seal seat in the boiler.

It must be absolutely clean. Inspect it with a torch and clean out the coupling with a vacuum cleaner.

Clean

The copper washer for sealing the lambda probe's metal flange and the seat in the boiler must be replaced when installing the probe.

Tighten the lambda probe securely (with 20 kg and

20 cm lever arm).

28

Let the lambda probe cool off and clean it with a vacuum cleaner. Take special care to clean the openings in the head of the lambda probe.

Excessive wear on the combustion chamber is often due to leaky installation of the lambda probe. Leak air penetrates the boiler and the control system reduces the air intake too much and the temperatures in the combustion chamber reach forbidden levels.

Inspect seals on heat exchanger cover

Check the heat exchanger cover's seals and replace as needed.

www.eta.co.at

Maintenance Every 3 years

Calibrate lambda probe

After every 500 hours of full-load operation, the boiler performs an automatic calibration of the lambda probe. This always occurs after an ember burnout and only at night between 23:00 and 04:00. This calibration can also be initiated manually by opening the primary and secondary air valves and flushing the boiler with fresh air using the draught fan.

If the boiler has not been in use for over 48 hours, this calibration takes only 30 minutes. If the boiler was in operation until recently, the calibration can take up to 3 hours. If the boiler is started up during calibration, the calibration is aborted and started again 9 days later.

Using the Service access level, open the text menu by pressing [Boiler] and . Tap the [Inputs] line.

In the submenu, tap the [Residual O2] line.

In the submenu, scroll down and double-tap the

[Additional calibration] line.

2 x

In the selection window that appears, select

[On] button and confirm with [Accept]. The control system will now automatically calibrate the lambda probe. The boiler is now in

Calibrating lambda probe mode. When calibration is complete, the boiler returns to "Ready" status.

After 100 hours at full load, the control system will automatically perform a re-calibration.

SH Operation

2012-11

29

Every 3 years Maintenance

Perform emission measurement

Perform the emission measurement with a measuring device on the boiler; see page 6 .

Perform heating test

Place logs in the fuel chamber, ignite them and wait 15 minutes. Then switch the boiler to emission measurement mode by pressing .

The control system ensures that sufficient heat is channelled to the buffer, the heating circuits and the hot water tank.

After around 10 minutes, a

residual oxygen value

of 4.5 to 7% should be reached. The current residual oxygen content is displayed in the boiler's text menu under [Boiler] at [Residual O2].

If the value

does not drop below 12% residual

oxygen, the boiler is receiving leak air. The reason (leaky boiler doors, heat exchanger cover, lambda probe installation etc.) must be identified and corrected.

Reset maintenance counter

After expert maintenance, the maintenance counter must be reset to zero. "Service" level access is required to do this.

30 www.eta.co.at

SH Operation

2012-11

31

Approval, antifreeze, pressure equalisation, venting

Approval, antifreeze, pressure equalisation, venting

Approval

Every heating system must be approved.

Inquire at you building authority and ask your chimney sweep.

Operation only by trained personnel

The system may be operated only by trained personnel. Instruction can be given by the heating installer or our customer service. Please read this user manual to be assured of avoiding errors in operation and maintenance of the boiler.

Fire extinguisher

In Austria at least a powder extinguisher ABC 6 kg is required. Better is a foam extinguisher AB 9 litre, which causes less damage when extinguishing.

The fire extinguisher should be kept outside the boiler room, easily visible and easily accessible.

In Germany and Switzerland, no fire extinguishers are required for heating systems in private residences. In spite of this, we recommend having one in the house.

Children must be kept away from the boiler room and pellet store.

Antifreeze

If a house with average insulation is unoccupied in winter at low temperatures for more than five days, check once a week (twice a week for very low temperatures) to make certain that the boiler is operating properly.

If the building is unoccupied in winter for longer intervals, up to 30% antifreeze can be added to the heating water. To compensate for the disadvantage of reduced heat capacity and increased flow resistance, only slightly higher flow temperatures are needed.

Insulate contact sensors

If the pipe in the vicinity of a contact temperature sensor is not insulated (e.g. in externally installed heating circuit groups), lower than actual temperatures will be measured. For this reason, pipe insulation may not be recessed or weakened for heating circuit flow sensors. For uninsulated piping systems, the measurement area must be insulated with mineral wool at least 20 mm thick over a length of at least 20 cm of pipe.

Pressure equalisation

For pressure equalisation in the system, a diaphragm expansion tank with a gross capacity of around 10% of the system volume is needed (see conditions for guarantee and warranty).

All shut-off valves along the path from the expansion tank to the boiler and to the buffer storage tank must be capped valves, or the hand wheels or levers must be removed from the valves

(hang on the valve with a wire) to ensure that they cannot be closed by accident.

If the pressure difference between cold and warm heating system (buffer fully loaded if installed) is greater than 1.0 bar for a single-floor system or 0.5 bar for a three-storey system, then the expansion tank is too small and absolutely must be replaced with a larger one. If the installed expansion tank is not large enough, the system sucks in air when cooling and the air is absorbed by the cold water and transported to the boiler.

At the point of highest temperature, the air separates from the water again. This is the usual situation in the boiler, and the inevitable result is that the boiler wall will rust through at these places.

Venting

Automatic venting valves in the boiler outlet, at the highest point in the distribution network and at the top of the buffer significantly reduce the danger of rust and also the frequency of radiator venting.

32 www.eta.co.at

Softened water, safety valve

Initial fill-up with softened water and enough shut-off valves

All relevant standards demand softened water for heating systems with larger water volumes.

For the boiler a value of 20,000 lt°dH for system volume in litres multiplied by the hardness

(in degrees of German hardness) may not be exceeded.

A system volume of 300 litres (boiler and heating elements) and very hard water with 30°dH yields a value of 9,000 lt°dH. In this case, the system can still be filled with unsoftened water.

For a heating system with a 1000-litre buffer, for example, the total volume is 1300 litres. Even with water that is not very hard, such as 20°dH, a value of 26,000 lt°dH results; that is too high. For a volume of 1300 litres, the water must be softened to less than 15°dH (20,000 divided by 1,300).

Around 0.25 kg of limescale will precipitate from a cubic metre of water with 15°dH, resulting in a limescale layer 0.2 mm thick on a quarter of a square metre of the boiler's heat exchanger surface; this small area in the boiler is where the lime build-up is concentrated. This may not seem serious, but with 2 m³ of buffer storage and a system volume of 0.5 m³, a thickness of 0.5 mm is reached. Thicker layers hinder the heat flow through the boiler wall to the extent that it is no longer cooled sufficiently and heat stress cracks can form.

In practice, that means the boiler can tolerate a buffer filled with unsoftened water as long as no repairs and no leaks in the system (defective air valves or safety valves that fail to close) force water to be refilled during the further course of the system's service life.

To have a sufficient safety reserve for additions, the new system must be filled with softened water, meaning that the empty system must really be filled exclusively with softened water before starting the boiler for the first time. Changing the water after the boiler has already been in operation is too late since the limescale from the unsoftened water has already precipitated in the boiler.

To reduce the amount of water replacement for later repairs, it must be possible to shut off all large volumes such as buffers, boiler and heating circuits to keep the lime content to a minimum during water additions.

SH Operation

Softened water, safety valve

Protection against corrosion

To limit corrosion with softened water, the pH value should be adjusted to between 8 and 9 using suitable inhibitors (trisodium phosphate).

Safety valve against overpressure

Install a safety valve with 3 bar opening pressure on the boiler (is already installed for PU and

PC boilers). No shut-off valve may be installed between the boiler and the safety valve. If solar or other heat sources provide energy to the buffer storage tank via a heat exchanger, a safety valve

(3 bar maximum) is also required on the buffer storage tank. Normally an expansion tank that is too small or defective, or blocked heating lines, are the cause for activation of the safety valve.

The safety valve must be on top of the boiler in the flow in order to also discharge heat in an emergency. Only this way can it discharge heat when it blows out hot water and also steam.

The discharge must be directed to the sewer via an easily visible, open flow path (siphon funnel) so malfunctions and, above all, a non-closing valve can be recognised. If no sewer is available, the discharge must be directed into the ground in a pipe so nobody is endangered by hot water or steam.

2012-11

33

Return riser and safety devices

Return riser and safety devices

Return riser

Wood contains water. If the temperature in the boiler is too low, steam condenses from the flue gas onto the heat exchanger surfaces. Corrosion and a leaky heat exchanger are the result. To prevent this, the water temperature at the boiler inlet must be at least 60°C. Since the return temperatures are usually lower, a return riser is needed - preferably with a mixer that provides controlled, heated flow to the boiler return.

The return riser mixing valve controls the buffer charging output. To reduce the output, the return temperature is raised over 60°C to reduce the spread compared to the boiler's setpoint temperature. With the spread the output that can be consumed from the boiler is limited.

Thermal emergency cooling valve against overheating

The safety heat exchanger built into the boiler must be connected by the heating technician to the house's cold water supply via a thermal outlet valve (opening temperature 95 °C) to protect the boiler against overheating if the pump fails. The minimum pressure in the cold water line must be

2 bar.

Connect the supply line to the lower connector of the safety heat exchanger; the upper connector is for outlet to the sewer. To prevent the supply line from being shut off accidently, remove the levers from shut-off valves or the hand wheels from valves and hang them there with a piece of wire.

The discharge must be have an easily visible, open flow path so malfunctions can be recognised.

Direct the discharged water to the sewer via a siphon funnel or at least with a pipe into the ground so that nobody can be scalded if the valve is activated.

Even for cold water coming from a domestic well with its own pump, a thermal emergency cooling valve must be installed on the boiler. With a generously dimensioned air vessel, enough water for cooling will come even if there is a power failure. If the electricity supply is very uncertain, a dedicated air vessel for the thermal emergency cooling valve is required.

34 www.eta.co.at

Minimum heat consumption, buffer storage tank

Minimum heat consumption, buffer storage tank

A minimum power level is necessary to achieve clean and complete combustion

The smaller the fire in the boiler, the lower the temperature will be in the combustion chamber.

At about a third to a quarter of the full load, the combustion temperature drops below 700°C and the tar components in the wood gas no longer burn completely. This drastically reduces the efficiency (it can drop to below 50%), causes tar build-up in the boiler's heat exchanger and in the chimney and also results in unacceptable pollution due to unburned hydrocarbons.

To maintain a clean-burning wood fire with maximum fuel efficiency, a minimum power level must be maintained and the best way to achieve this is to use a buffer storage tank.

Why a buffer storage tank?

Many old log boilers that do not have buffer storage tanks are still in use, so why do we need them with today's wood-burning systems? The answer to this frequently asked question is as follows: In the days before heating control systems, the boiler used the thermal mass of the entire house as a buffer. If the boiler is replaced, and the radiators are fitted with new thermostat valves and/or a weather-dependent mixing system, the log boiler is forced to operate at too low an output level in autumn and spring when the heating requirements are minimal. At low output levels, the temperature in the combustion chamber drops, but production of wood gas doesn't. Hard-to-burn components of the wood gas, such as tar or acetic acid no longer combust; instead, they condense

(create tar deposits) either in the boiler's heat exchanger or in the flue. The materials that are not deposited pollute the environment.

A buffer storage tank is necessary to control this low-load operation, which inevitably occurs with a modern, energy-saving heating system. Heat produced by the boiler for which there is no immediate use within the building is offloaded into a buffer storage tank and retrieved by the heating system as needed, for example, when the boiler is not operating.

As a log wood boiler cannot simply be switched off once it has been started up and while there is still wood burning in it, it must be possible to store in the buffer the energy content of the wood that is still in the combustion chamber. to hot water tank

Flow from boiler

" Buffer top" temperature sensor just under the connection

The boiler controls its output based on the reading from the "Buffer middle" temperature sensor.

Enough to provide sufficient heat to start a consumer. Not too much to ensure that the buffer is still able to store heat after the heating circuits have been switched off.

" Buffer bottom" temperature sensor just above connection

Return to boiler

No external timer thermostats

The factory-standard controls include weekly timers for two heating circuits.

If the heating pumps are controlled by the boiler control, heat can be drawn from the boiler during periods when the temperature setting has been lowered as long as there is wood in the boiler.

This is especially important if you accidentally put too much wood on in the evening, or if you intentionally heat up the boiler to its full extent in anticipation of a cold night.

Timer thermostats will switch off the heating pumps punctually at the preset time, even if wood is still burning in the boiler, and even if the

(undersized) buffer is incapable of storing more heat. The only solution for the boiler is to stop its air intake. Although this puts the fire out without the boiler overheating, the wood will continue to emit gas and the unburned wood gas resulting from the lack of air will create tar deposits in the boiler and flue.

SH Operation

2012-11

35

Split wood will dry out in just one summer

Split wood will dry out in just one summer

Why use dry split logs?

The moisture content of split logs intended for a log boiler should be below 20% (air dry).

Damp wood with a moisture content of above 20% creates a moist climate in the fuel chamber. Wood that is not sufficiently dry can cause the boiler's fuel chamber to rust through.

One summer is sufficient to dry out split firewood

Unsplit logs stacked as metre-long pieces in the forest will generally take two summers to dry.

However, it can be done faster. If the timber is felled in winter (before the end of January) and split immediately, a moisture content of 15% can be reached by September through air drying. Split logs also burn far better than unsplit logs.

Unsplit logs take two months longer, and thus a second summer, to dry.

The best approach is to split the wood in lengths of 1 m immediately after felling: split in half for a log diameter of up to 15 cm; into quarters for a diameter up to 20 cm, into sixths for a diameter up to 25 cm, and into eighths for a diameter up to 30 cm.

Store the split wood in a windy place on a dry surface; ideally stack crosswise on two logs or concrete pipes and cover only the top. Of course a sunny location is preferable, but it is more important to find a dry, windy place. Leave a gap between stacks as well. If you stack wood along the wall of a house, leave an air gap of at least 10 cm between the wall and the stack of wood.

Wood stored outside in winter will absorb moisture from precipitation. For this reason either move the wood to a covered location in September or, as a minimum, temporarily store it in a warm room for a week before burning.

During storage the heating value is reduced by processes similar to decay; depending on how dry storage conditions are, the loss can be between

1% and 3% per year. For this reason, only store firewood for longer than 3 years in exceptional circumstances.

Split the wood and store it in a dry, windy place, one percent moisture more or less will not make a big difference

To sum up: the heating value changes by only 2% between 20% and 10% moisture content. It is easy to achieve less than 20%—even if you cut the wood in summer—if you split the wood and store it outdoors with protection against the rain for a year.

36

60

%

50

40

30

Buche

Fichte

20

Buche

Fichte

10

0

De z0

2

Feb

03

Ap r03

Jun

03

Au g0

3

Ok t03

De z0

3

Feb

04

Ap r04

Jun

04

Au g0

4

Ok t04

Quelle: “Rationelle Scheitholzbereitstellungsverfahren” Bericht 11 TFZ Straubing, von ETA mit Heizwertangabe ergänzt

82,4

%

89,0

93,5

96,6

97,7

99,0

100,0

100,9

101,7

102,4

www.eta.co.at

Heating value of wood

Heating value of wood

Heating value of wood

Split wood is typically sold in stacks by the cubic meter. The energy content depends not only on the type of wood. The amount of heat a cubic metre contains also depends on whether the wood is unsplit round logs, metre-long split logs, or readyto-burn split logs, and on whether it is fresh from the forest or dried for firewood.

The wood volume stays constant from when it is freshly cut with a moisture content of 60% to the fibre saturation point at 25%. The wood starts to contract if dried below this point. It reduces in size, and this is why air-dried wood (moisture content of 15%) has more wood substance than freshly cut wood per cubic metre. The difference is typically 5% to 6% for softwood, and 6% to 9% for hardwood.

Logs are not straight. The longer the logs are, the less wood and the more air is present per cubic metre. There is typically more air in "crooked" hardwood than in "straight" softwood.

There is one further difference: round logs can typically be stacked in a far more compact way than metre-long split logs. If you split the wood yourself, buying round logs will give you up to

15% more wood per cubic metre.

In practice, deviations on the order of +/-10% compared with theoretical values are to be expected. Up to 20% is possible in extreme cases: not only if the wood is particularly straight or crooked, but also because the density of the wood mass itself can vary.

Incidentally, if you order a cubic metre of ready-toburn beech firewood as 50 cm split logs from your wood dealer, the dealer is entitled under current law to supply 0.85 m³ of half-metre split logs cut from 1 m³ of 1 metre long split logs. To avoid any unpleasant surprises, when ordering ask how your dealer measures a cubic metre (if the price is good, you may find 0.85 m³ acceptable).

Estimating your wood requirements

Each kilowatt of heat output requires 0.9 cubic metres of half-metre split beech logs, or 1.3 m³ of split spruce per year.

In other words, 8 m³ of half-metre split spruce logs or 5.5 m³ of beech will replace 1000 litres of heating oil.

Energy content of one cubic metre of wood in kilowatt hours

The table assumes that the firewood used is split and air-dry (after one year's storage) with a moisture content of around

15% when burned even if it was moist when bought.

Softwood

Fir

Spruce

Douglas fir

Pine

Larch

Hardwood

Poplar

Willow

Alder

Maple

Birch

Ash

Oak

Beech

Hornbeam

Black locust

Round logs 1 m freshly cut w=30-60%

1 stere contains 0.65 m³

1,205

1,299

1,402

1,542

1,573

Round logs 1 m dry w=15%

1,269

1,373

1,478

1,625

1,656

1 stere contains 0.59 m³

958

1,107

1,191

1,472

1,475

1,658

1,664

1,655

1,743

1,743

1,020

1,200

1,270

1,550

1,570

1,760

1,760

1,800

1,920

1,920

Logs 1 m freshly cut w=30-60%

1,038

1,119

1,208

1,329

1,355

1 stere contains 0.50 m³

812

938

1,009

1,247

1,250

1,405

1,410

1,403

1,477

1,477

Logs 1 m dry w=15%

1 stere contains 0.56 m³

1,093

1,183

1,274

1,400

1,427

864

1,017

1,076

1,314

1,331

1,492

1,492

1,525

1,627

1,627

Logs 50 cm freshly cut w=30-60%

Logs

50 cm dry w=15%

1 stere contains 0.62 m³

1,149

1,239

1,337

1,471

1,501

1,210

1,310

1,410

1,550

1,580

1 stere contains 0.59 m³

958

1,107

1,191

1,472

1,475

1,658

1,664

1,655

1,743

1,743

1,020

1,200

1,270

1,550

1,570

1,760

1,760

1,800

1,920

1,920

Logs 33 cm freshly cut w=30-60%

Logs 33 cm dry w=15%

1 stere contains 0.64 m³

1,186

1,279

1,380

1,519

1,549

1 stere contains 0.62 m³

1,007

1,163

1,252

1,547

1,550

1,742

1,749

1,739

1,832

1,832

1,249

1,352

1,455

1,600

1,631

1,072

1,261

1,335

1,629

1,650

1,849

1,849

1,892

2,018

2,018

SH Operation

2012-11

37

User interface

Adjusting the date and time

Adjusting the date and time

Getting to know the control system

Instead of buttons, the touchscreen is operated using icons directly on the screen.

In order to familiarise yourself with how to operate the system, tap once on the icon on the left of the screen.

The touchscreen only displays those function blocks that are required and configured to work with your heating system.

You can use the horizontal buttons [Boiler],

[Buffer], [HC], [HWT] ... to flick between the individual function blocks (FUBs).

These instructions contain descriptions of all the function blocks of the ETAtouch software.

User interface

Adjusting the date and time

Tap on the date or time at the bottom right-hand corner of the touchscreen.

A screen appears for adjusting the date and time:

Moving on the touchscreen

Use the horizontal buttons to select the individual

function blocks (FUBs) of the heating system.

Overview

of the selected function block.

Text menu

for adjusting the parameters of the selected function block

I/O list

allowing experts to assign inputs and outputs

Error messages

for the selected function block

Toolbox

for experts

INFO

Help

Tap on the [Day], [Month], [Year] or [Time] fields to alter the settings.

Once a field has been filled in by entering numbers, the cursor automatically moves to the next field.

[DEL] deletes the number to the left of the cursor.

[Cancel] closes the screen without saving the changes.

[Accept] saves changes and closes the screen.

38 www.eta.co.at

Changing the language

User interface

Changing the language

It is possible to change the language on the screen.

Changing the language

Switching to the toolbox

Press the button to switch to the toolbox.

Selecting a language

Select the language you require and confirm by pressing the [Accept] button.

Tapping the button with the flag symbols

Tap the button with the flag symbols to go to the language selection screen.

Back to overview

Press to return to the boiler overview screen.

SH Operation

2012-11

39

Changing function block names

Changing function block names

Changing the names of the function blocks

The names of the function blocks can be changed at any time in order to make them clearer to you.

For example, the names of the heating circuits HC,

HC2 etc. can be changed to ground floor, upper floor, parents, living room or similar.

Example: Renaming HC1 "Ground floor"

Even though this example uses a long name, it is best to choose short names so that you can reach all the function blocks without having to use the arrow buttons.

Selecting heating circuit 1

Double-tap [HC] to rename this function block.

2 x

Changing the name using the keyboard cancel

User interface

save

Use the keyboard to enter the new name for heating circuit 1, in this example: FLOOR.

Then press the [ENTER] button to save the new name.

The [ESC] button cancels the renaming process and changes back to the previous name.

HC has now been renamed "FLOOR".

The names of all the function blocks can be changed at any time.

A small screen appears for this function block.

40

Tap the [Change Name] button. An on-screen keyboard appears.

www.eta.co.at

Alarm, error, warning, message

User interface Alarm, error, warning, message

Message

This icon in the function block buttons indicates a message. Messages do not interrupt operation of the boiler, nor must they be acknowledged.

For example, they may indicate that the cleaning lever should be operated or inform the user of events outside normal operation, e.g. in summer, the pump anti-blocking protection begins every Saturday at noon.

Warning

This icon indicates a warning. Warnings are issued when a function that is not essential to active operation fails. A warning can be acknowledged before the error is resolved. However, it will continue to be displayed until the cause of the error has actually been dealt with.

Error, alarm

This icon indicates errors or alarms. Alarms are issued for errors that halt operation. Some can be acknowledged before the error is resolved. However, they continue to be displayed until their cause has actually been dealt with.

Some errors and alarms cannot be acknowledged until they have been successfully resolved. These messages can be deleted with the [Confirm later] button.

Displaying errors

Press to view the list of errors for the currently selected function block.

If an error, alarm or warning occurs in any

function block, the icon on the button changes to (alarm) or (warning).

By selecting a line, you can view a help text at the bottom of the screen.

Acknowledging errors

Select the line and

double-tap it or press [Conf.].

A confirmation window appears.

Press "OK" to acknowledge the message and delete it from the list. Press [Cancel] to close the window without acknowledging the error.

or

2 x

Acknowledging all errors

Double-tap a function block to display a menu where you can acknowledge all errors by tapping

[Confirm error].

!!! Restart after an alarm !!!

Once the errors have been resolved and the errors and alarms have been acknowledged, the boiler or the affected heating circuit must be switched back on using the on/off button .

Once they are switched on, the button lights up green.

2 x

SH Operation

2012-11

41

Opening the text menu

Opening the text menu

Function block text menus

There is a "text menu" for each function block. This view shows the current parameter settings. It also allows the user to make changes.

Opening the text menu

Select the desired function block, e.g. by tapping

[Boiler]. Next, change the view to "text menu" by pressing the button.

The text menu for the selected function block appears. The individual parameters for the selected function block are displayed.

Lines preceded by  have a submenu, which can be opened by tapping the line. The submenu can be closed again by tapping the upper-level line that is marked with .

Modifying parameters

It is possible to modify certain parameters in order to adapt the heating to your needs. Tap these parameters to select them. The [Value] field changes and the [Change value] button appears.

Change the parameters by double-tapping on the line, or

select the line and press the [Change value] button.

User interface

Example: Displaying the boiler counters

Tap the [Boiler] button to open the "Boiler" function block.

From the overview screen, press the button to go to the text menu.

The boiler text menu appears.

Tap the [Counters] line. The submenu opens and the boiler counters are displayed.

or

2x

In case of doubt, consult an expert before making any changes.

Only modify parameters if you know what their function is. Read through the corresponding section of the user manual before making changes.

If the explanation of the relevant function given in the manual is not sufficient for your purposes, confer with an expert.

Press the button to return to the overview.

42 www.eta.co.at

SH Operation

2012-11

43

Log boiler [Boiler]

Overview, buttons, functions

Overview, buttons, functions

Boiler overview

Press and [Boiler] to open the Boiler overview screen. The overview screen shows you the boiler mode and buffer charging status at a glance.

Log boiler [Boiler]

Exhaust gas temperature

Boiler flow temperature

Boiler return temperature

44

On/off button

The on/off button

serves only to switch off the

boiler. The boiler is switched on by opening the insulating door.

Green = On

Red = Off

De-ash button

If this button is pressed during boiler operation, the boiler will perform a complete ember burnout

(duration ~1 hour). All embers and ash are burned to make subsequent cleaning easier. Pressing this button again during operation ends the burnout.

Emission measurement

The boiler must already have started up in order to operate this button. This switches the boiler into

emission measurement mode and operates it

for 30 minutes at full load. The control system ensures that sufficient heat is channelled to the buffer, the heating circuits and the hot water tank.

In emission measurement mode, the button shines green and a countdown for the emission measurement mode is displayed. After 30 minutes, all pumps and valves are automatically switched back to automatic mode.

Buffer storage tank and charging status

The buffer storage tank and the pump icon are displayed as soon as the boiler pump is switched on and heat is being supplied to the buffer storage tank. The percent display shows the current buffer charging status.

Outside temperature

The current outside temperature is measured by the installed outside temperature sensor.

Operating mode

This line shows the boiler's current operating mode. The possible modes are listed below.

Ready

The boiler is switched off. The on/off button shines red. The boiler can be started up at any time.

Ignite

See "Start-up" chapter. In ignite mode, the boiler can also be switched off with the on/off button.

Heating

The boiler is switched on and the insulating door is closed. The boiler is supplying heat to the buffer storage tank.

Ember burnout

The fuel in the boiler is almost consumed and the exhaust gas temperature is below 80°C. If the ash button was pressed during boiler operation, the boiler will perform a complete ember burnout for subsequent cleaning.

www.eta.co.at

Log boiler [Boiler]

Malfunction

There is a malfunction in the draught fan, the exhaust gas temperature sensor or the boiler temperature sensor.

The boiler may not be started up in this mode.

Calibrating lambda probe

After every 500 hours of full-load operation, the boiler performs an automatic calibration of the lambda probe. This always occurs after an ember burnout and only at night between 23:00 and 04:00. This calibration can also be initiated manually by opening the primary and secondary air valves and flushing the boiler with fresh air using the draught fan. If the boiler has not been started up for over 48 hours, this calibration takes only 30 minutes. If the boiler was in operation until recently, the calibration can take up to 3 hours. If the boiler is started up during calibration, the calibration is aborted and started again 9 days later.

Insulation door open

The insulation door is open. If the boiler was previously in heating mode, it switches back to heating mode after the insulation door is closed. For all other modes, the boiler switches to ignite mode after "Insulation door open". If the insulation door stays open for more than 30 minutes, an error message is displayed and (depending on setting) an audible signal emitted.

Overtemperature

The boiler temperature is over the temperature of 90°C set for [Boiler max]. The draught fan is switched off and an error message indicates that less fuel should be added in future. Once the boiler has cooled below 86°C, the draught fan switches on again and heating resumes.

TWIN in operation

This is only displayed if a TWIN burner (pellets) is installed on the log boiler.

"TWIN in operation" mode displayed as soon as the buffer needs heat and the log boiler is unable to provide it. Then the control system starts the TWIN burner to supply heat to the buffer. The current status of the TWIN burner is shown in the [TWIN]

FUB.

If the log boiler's insulation door is open for more than 1 minute, the TWIN burner is automatically

SH Operation

Overview, buttons, functions

switched off because the control system assumes that the log boiler is to be started up. A corresponding message is displayed.

2012-11

45

Buffer [Buffer]

Overview, buttons, functions

Overview, buttons, functions Buffer

Buffer overview

Press and [Buffer] to open the Buffer overview screen. The overview shows the current temperatures, the operating mode and charging status of the buffer.

If the buffer is a combination tank (buffer with built-in hot water tank), the hot water temperature is also displayed. The display also shows the charge from a solar heating system.

How the buffer works

The current charging status is calculated using the

3 temperature sensors on the buffer. It is needed to determine the correct amount of firewood to add. The table on page 11 shows how much wood should be added.

Buffer charging status

Operating mode Buffer top

Buffer middle

Buffer bottom

[Buffer top] temperature

[Buffer middle] temperature

[Buffer bottom] temperature

Buffer charging status

Charging by boiler

This icon is displayed when the buffer is being charged by the log boiler.

With a

"combination tank", the icon is shown at the top of the buffer when hot water rapid charge is active. If the buffer is only being charged below the hot water section, this icon appears in the middle of the buffer.

Charging by solar heating system

This icon for solar charging indicates that the buffer is being charged by the solar heating system. The current solar panel temperature is shown above the icon.

Current operating mode

This line shows the current operating mode of the buffer. Below is a list of the possible modes:

Demanding

The buffer is demanding heat from the boiler. If the boiler is switched on, this causes it to start up.

Charging

The boiler is supplying heat to the buffer.

Charged

The buffer switches to charged mode when the log boiler is supplying heat and 80°C has been reached at the top of the buffer (= [Target temperature] factory setting).

If the log boiler is not supplying heat, the buffer can also reach the charged state if the [Buffer target 1] temperature is exceeded in the buffer.

Heat dissipation

After a combustion phase, residual heat from the boiler is channelled to the buffer or, if the boiler overheats, heat from the boiler is transferred to the buffer so the boiler can be cooled.

Freeze protection

A temperature sensor in the buffer has fallen below the freezing protection temperature (factory setting: 10°C).

Sensor failure

A temperature sensor in the buffer is defective.

View the list of error messages to find out which sensor is affected.

46 www.eta.co.at

Buffer with solar

Buffer

Different overviews depending on configuration

The way the buffer and the temperatures are displayed on the screen differs depending on the configuration of the heating system.

Buffer with a solar heating system

If the current solar panel temperature is 5°C

(factory setting) higher than the Buffer bottom

solar temperature, the solar heating system begins to charge the buffer. The icon for solar charging

appears together with the current solar panel temperature.

If the

solar panel temperature falls below the

Buffer bottom solar temperature, the solar coll-

ector pump is switched off.

Buffer top Solar panel temperature

Buffer with solar

Buffer with solar heating system and stratified charging valve

The stratified charging valve

toggles solar charging between the top and bottom sections

of the buffer. With this function, the temperatures

"Buffer top solar" and "Buffer bottom solar" are continually compared with the current solar panel temperature.

First the

top is always charged as soon as the solar

panel temperature is higher than the Buffer top

solar temperature.

After reaching the Buffer target temperature, charging switches to

Bottom until the Buffer

target temperature has also been exceeded at the

bottom.

The icon for solar charging is shown at the top or in the middle of the buffer, depending on the position of the stratified charging valve.

Buffer top Buffer top solar Solar panel

Buffer bottom Buffer bottom solar

Solar panel is charging buffer

Buffer bottom Buffer bottom solar

Solar panel is charging top section of buffer.

The stratified charging valve is in the top

position.

Icon in the middle: buffer is being charged in

bottom section. The stratified charging valve is in the

bottom position.

SH Operation

2012-11

47

Combination tank with solar

Combination tank with solar Buffer

Combination tank with a solar heating system

There are different types of combination tank. A hot water tank can be installed in the top section of the buffer, an internal water heat exchanger may be integrated throughout the entire height of the buffer, or a third-party fresh water module may be installed.

For all these variants, the overview always shows

an internal water heat exchanger and the hot

water temperature at the top of the buffer is displayed.

Buffer bottom

Buffer top

Temperature of hot water tank

Switching times for circulation pump for combination tanks only adjustable in text menu

With combination tanks, there is also the option of controlling a circulation pump. No timer for the circulation pump is displayed in the overview.

Switching times for the circulation pump must be adjusted in the text menu.

In the Buffer overview, press to open the text menu. Tap the [Hot water tank] line and, in the submenu, tap the [Circulation] line.

Tap the [Circulation times] line. Time slots for the circulation pump can only be set on an individual basis for each day of the week.

2 x

Double-tap the desired time slot. A screen appears for setting the time slot:

Buffer bottom solar

48

Time slots for the circulation pump can now be changed.

Press [Accept] to save the new settings. Use the same method to adjust the time slots for all other days of the week.

www.eta.co.at

"Buffer bottom max." for solar heating systems

Buffer "Buffer bottom max." for solar heating systems

"Buffer bottom max." switch-off temperature

(solar heating systems only)

The "Buffer bottom max." switch-off temperature can only be set when the

solar heating system is

charging the buffer. This adjustable temperature sets a

threshold for how much the buffer can

be charged by the solar heating system in order to prevent the buffer from overheating.

If the

Buffer bottom solar sensor reaches the adjustable Buffer top max. temperature, the solar

collector pump on the solar heating system is

switched off.

The factory setting for the "Buffer bottom max." temperature is 90°C.

Changing the "Buffer bottom max." temperature

Press the buttons [Buffer] and to open the text menu. Tap the [Buffer] line and then, in the submenu, tap [Buffer bottom solar].

Double-tap the [Buffer bottom max.] line.

2 x

A settings screen opens:

Enter the new temperature and press [Accept]. The text menu display appears again.

SH Operation

2012-11

49

Heating circuit [HC1]

Overview, buttons and functions

Overview, buttons and functions

"Heating circuit" overview

Press and [HC] to open the "Heating circuit 1" overview screen.

Each heating circuit has its own function block

(HC2, HC3...).

In the overview of the selected heating circuit, the on/off button can be used to switch the heating circuit on and off.

The timer can be used to set 3 different time slots for each day of the week. If there is a room sensor installed, you can also adjust the desired room temperature.

If not, a slider on the overview screen allows you to adjust the room temperature.

"Day" and "Night" mode

During the time slots, the heating circuit is in

"Day" mode.

Outside the time slots, the heating circuit is in

"Night" mode.

Heating circuit on/off

This button is used to switch the heating circuit on and off.

The boiler has a separate on/off button.

Green = Heating circuit on

Red = Heating circuit off

Heating circuit

Slider

The slider is

only shown if there is no room

temperature sensor installed. The slider can be used to change the room temperature by approx.

+/- 5°C.

Please bear in mind that this substitute function cannot replace the precision of a room sensor.

Timer

The timer shows the set

heating time slots for

the current day of the week. Tapping this timer brings up a screen where it is possible to set

3 time

slots for each day of the week.

If a

room sensor is installed, the desired room

temperature can be set for each time slot.

Likewise, the reduced room temperature (set-back temperature) between the heating time slots can also be adjusted.

Within a set time slot, the heating circuit will be in

"Day" mode. Outside of the time slots, it will be in

"Night" mode.

If the heating circuit is operated in

"Auto"

mode ( button),

this button changes

the icon depending on whether the heating circuit is running at

"Day"

or

"Night"

temperature.

Current room temperature

(room sensor only)

Only displayed if a room sensor is installed

for this heating circuit. This displays the current room temperature as measured by the room sensor.

Current flow temperature

The current target flow temperature for the heating circuit is only displayed if the heating circuit is switched on and in operation.

50 www.eta.co.at

Heating circuit Overview, buttons and functions

Outdoor -13°C

Current outside temperature

The current outside temperature is measured by the built-in outside temperature sensor.

Constant "Day" mode

This button can be used to switch the heating circuit to constant "Day" mode (button lights up ).

If a room sensor is installed, the temperature will be regulated to the highest room temperature set for that day in the timer. If there is no room sensor, the heating circuit runs using the

heating

curve "Day".

0 3 6 9 12 15 18 21 24 pressing the button.

Das Drücken von „Gehen“ in einer Heiz-Pause überspringt das nächste Heiz-Zeitfenster.

Constant "Night" mode

Come

This function is only available in "Auto" mode.

Regardless of the current time slot, pressing the

button (when you come home)

switches the

heating circuit to "Day" mode (button lights up

) until the next set time slot.

If the unit has a built-in room sensor, the heating circuit is regulated to the set room temperature. If there is no room sensor, the heating circuit runs using the heating curve "Day".

Das Drücken von „Kommen“ in einer Heiz-Pause heizt bis zu Ende des folgenden Heiz-Zeitfensters.

0 3 6 9 12 15 18 21 24

Das Drücken von „Kommen“ während eines Heiz-Zeitfensters überspringt die folgende Absenkphase (heizt durch).

0 3 6 9 12 15 18 21 24 temperature (button lights up ).

If there is a built-in room sensor, the temperature is regulated to the set-back temperature that is set in the timer. If the unit does not have a room sensor, the heating circuit runs using the

heating

curve "Night".

"Auto" and "Day" modes can be ended by pressing the button.

"Auto" mode

"Auto" mode automatically switches between

"Day" and "Night" mode.

Within a set time slot, the heating circuit will be in

"Day" mode. Outside of the time slots, it will be in

"Night" mode.

The

"Auto" display changes the icon depending on whether the heating circuit is currently in "Day" or "Night" mode.

"Day" mode

"Night" mode

Go

This function is

only available in "Auto" mode.

Regardless of the current time slot, pressing the button (when you go out) switches the heating circuit to "Night" mode (button lights up ) until the next set time slot.

If the unit has a built-in room sensor, the heating circuit is regulated to the stored set-back temperature. If there is no room sensor, the heating circuit runs using the heating curve "Night".

Das Drücken von „Gehen“ während eines Heiz-Zeitfenster senkt ab bis zum Beginn des nächsten Zeitfensters.

0 3 6 9 12 15 18 21 24

Das Drücken von „Gehen“ in einer Heiz-Pause überspringt das nächste Heiz-Zeitfenster.

0 3 6 9 12 15 18 21 24

Das Drücken von „Kommen“ in einer Heiz-Pause heizt bis zu Ende des folgenden Heiz-Zeitfensters.

0 3 6 9 12 15 18 21 24

Das Drücken von „Kommen“ während eines Heiz-Zeitfensters überspringt die folgende Absenkphase (heizt durch).

0 3 6 9 12 15 18 21 24

SH Operation

2012-11

51

Operating modes

Operating modes

Holiday mode

The "Holiday" button is used to set a period for which the selected heating circuit will run in

"Night" mode.

Any adjustments made to the room temperature also influence the "Day" temperature, and thus the temperature for heating up at the end of the holiday. As such, it is best not to adjust the room sensor for holiday set-back.

If you wish to reduce the room temperature, you can set an individual "set-back temperature" in the timer. During

"Holiday" mode, the lowest of all the "set-back temperatures" in the timer is the

one that applies.

On Day

Current operating mode

This line shows the current operating mode of the heating circuit. Below is a list of the possible modes:

On Day

The heating circuit is

within one of the timer’s

time slots and in “Day” mode.

The flow temperature of the heating circuit is regulated using the “Heating curve day”.

If the unit has a built-in room sensor, the temperature is regulated to the highest room temperature set for the time slot. The switch can be in either the “Auto” or the “Day” position.

Heating circuit

On Night

The heating circuit is

outside of the timer's time

slots and in "Night" mode.

The flow temperature of the heating circuit is regulated using the "Heating curve night".

If the unit has a built-in room sensor, the temperature is regulated to the stored "set-back temperature". The switch can be in either the "Auto" or the "Night" position.

Holiday On

The heating circuit is switched on and in holiday mode (= constant "Night" mode). It remains in this state until the "End of holiday" date.

On Delay

The heating circuit is no longer demanding any heat and is in delay mode. The boiler pump is still running for a short time in order to channel the heat out of the boiler.

On Freezing room

The heating circuit is in operation because the current room temperature is below the freezing protection temperature (10°C).

On Freezing flow

The heating circuit is in operation because the current flow temperature is below the freezing protection temperature (10°C).

On Heat dissipation

The heating circuit is in operation in order to cool the boiler by dissipating excess heat. Also displayed during emission measurement.

On Overtemperature

The heating circuit is in operation because the boiler is running at overtemperature. The heating circuit is running at the highest set flow temperature in order to dissipate the heat from the boiler

(overheating protection).

52 www.eta.co.at

Heating circuit

On Screed

The heating circuit is in operation; the screed drying program is being run.

Off Enable temp.

The heating circuit is still switched off because the boiler is not yet able to supply sufficient heat. The enable temperature for the heating circuit has not yet been exceeded.

Off Target day

The heating circuit is switched off. The target flow temperature calculated from the heating curve

"Day" is below the room temperature as measured by the room sensor.

If the unit does not have a room sensor, the calculated target flow temperature is below 18°C.

Off Target night

The heating circuit is switched off. The target flow temperature calculated from the heating curve "Night" is below the room temperature as measured by the room sensor.

If the unit does not have a room sensor, the calculated target flow temperature is below 18°C.

Off Target holiday

The heating circuit is within the set holiday time, and thus switched off.

The target flow temperature calculated from the heating curve "Night" is below the room temperature as measured by the room sensor.

If the unit does not have a room sensor, the calculated target flow temperature is below 18°C.

Off Room day

The heating circuit is within a time slot, but switched off. The current room temperature is higher than the set "Room target" temperature by at least the "RoomOffDiff" temperature.

Off Hot water

The heating circuit is switched off because the hot water is currently being heated.

Operating modes

Off Room night

The heating circuit is switched off and outside the set time slots. The current room temperature is higher than the stored set-back temperature by at least the "RoomOffDiff" temperature.

Off Room holiday

The heating circuit is within the set holiday time, and thus switched off. The current room temperature is higher than the stored set-back temperature by at least the "RoomOffDiff" temperature.

Off Outside day

The heating circuit is switched off. The current outside temperature is higher than the set temperature for "Day Heating threshold".

Off Outside night

The heating circuit is switched off. The current outside temperature is higher than the set temperature for "Night Heating threshold".

Off Outside holiday

The heating circuit is within the set holiday time, and thus switched off. The current outside temperature is higher than the stored set-back temperature.

Off Summer

The heating circuit is switched off. The only active functions are the freezing protection and the boiler pump's "anti-blocking protection", which runs at midday every Saturday.

Off Sensor failure

The heating circuit is switched off due to a defect in the flow temperature sensor.

SH Operation

2012-11

53

Setting the heating time slots

Setting the heating time slots

Setting the heating time slots

The heating circuit timer can be used to set 3 different time slots for the heating for each day of the week.

If the unit has a room sensor, a target room temperature can also be set for each time slot.

Likewise, the reduced room temperature (set-back temperature) between the heating time slots can also be adjusted for each day of the week.

"Day" mode

During a set time slot, the heating circuit is in

"Day" mode.

If a room sensor is installed, this regulates the heating circuit to the set target room temperature for the time slot.

If there is no room sensor, the flow temperature of the heating circuit is calculated using the heating curve.

"Night" mode

Outside the time slots, the heating circuit is in

"Night" mode.

If a room sensor is installed, this regulates the heating circuit to the stored "set-back temperature" for the time slot.

If there is no room sensor, the flow temperature of the heating circuit is calculated using the heating curve.

Adjusting the timer (with room sensor)

In the overview for the selected heating circuit, tap the timer. The screen for setting the timer opens.

Heating circuit

Overview of current time slots

The current day of the week is selected automatically. The set time slots for the current day of the week are shown on the screen.

Days of the week

Room temperature only

Set-back temperature between time slots

3 adjustable time slots for each day of the week

Target room temperature

room sensor only

Selecting a time slot

Tap the [Time slot 1] line. The time slot setting screen opens.

The times for “Day” mode can now be altered.

If the unit has a built-in room sensor, the target room temperature can also be set.

Room sensor only

Press [Accept] to save the new settings. Use the same method to adjust the other time slots.

54 www.eta.co.at

Heating circuit

Copying time slots to other days of the week

Once the time slots have been adjusted, they can also be adopted for other days of the week.

In the time slot overview screen, tap the [Copy] button. A screen appears for selecting a day of the week:

Tap to select the desired day of the week or [All] and then press [Accept]. The time slots are adopted for the selected days.

The new time slots are displayed.

Setting the heating time slots

"Holiday" function

With this function, the button can be used to switch the heating circuit

to constant "Night"

mode for an adjustable time period. This setting only ever applies for the selected heating circuit.

The hot water supply from the hot water tank or the fresh water module is

not affected by the

"Holiday" function.

For "Holiday" mode, the heating circuit is regulated to the lowest set-back temperature set in the timer.

If you wish to reduce the temperature for the

"Holiday" time period, you can set an individual set-back temperature in the timer.

Adjusting the room sensor also affects the "Day" temperature when heating up at the end of the holiday. As such, it is best not to adjust the room sensor for holiday set-back.

Setting a "Holiday" time period

In the "Heating circuit" overview screen, tap the

button. A screen opens:

Finally, press [Close].

The heating circuit overview reappears.

Enter the time for the beginning of your holiday.

The button can be used to switch between the

"Start" and "End" of the holiday.

Enter both times and press [Accept].

The heating circuit overview reappears.

SH Operation

2012-11

55

The heating curve

The heating curve

The heating curve

The heating curve controls the flow temperature for the "Day" and "Night" modes of the heating circuit in question. During a set time slot, the heating circuit is in "Day" mode. Outside the time slots, the heating circuit is in

"Night" mode.

Each heating circuit has its own heating curve, as underfloor heating requires different settings to radiator heating.

The

diagram shows a heating curve for radiator heating. If the control settings have been adapted to your system, lower heating curves may be set for underfloor heating and higher heating

curves for radiator heating.

80

70

Maximum flow temperature

(adjustable with SERVICE permission)

60

Day

50

40

44°C Day

Nigh t

30

29°C Night

20

10

Freezing protection

0

-20 -15 -10 -5 0 +5 +10

Outside temperature (°C)

+15 +20

Maximum flow temperature

This limit protects your heating system.

Underfloor heating is usually limited to 45°C, while radiators with metal pipes can take temperatures up to 85°C.

Heating circuit

Heating curve "Day"

During a set time slot, the heating circuit is in "Day" mode. The heating curve for "Day" mode can be adjusted using the parameters "Flow at -10°C" and

"Flow at +10°C". The control system uses these parameters to plot a line: the heating curve "Day".

The heating curve "Day" and the current outside temperature are used to calculate the required flow temperature for the heating circuit. Example:

at +3°C outside temperature => 44°C flow

at -5°C outside temperature => 54°C flow

If the unit has a room sensor, the calculated flow temperature is corrected. The actual flow temperature may be higher or lower.

Heating curve "Night"

Outside the set time slots, the heating circuit is in

"Night" mode.

The heating curve "Night" is set back from the heating curve "Day" by the adjustable value "Setback". The heating curve "Night" and the current outside temperature are used to calculate the required flow temperature.

Factory settings for the heating circuit

With software versions 1.20.0 and higher, the system configuration for the heating circuit offers the user a choice between

underfloor and

radiator heating.

This choice pre-sets some of the parameters in the heating circuit. For information on these parameters and their factory settings, see page <?> .

.

56 www.eta.co.at

"Day Heating threshold" and "Night Heating threshold"

Heating circuit "Day Heating threshold" and "Night Heating threshold"

The parameter "Day Heating threshold"

With the "Day Heating threshold" parameter, an outside temperature is set which, when exceeded, will result in the heating circuit being switched to

"Day" mode.

The factory setting for this parameter is 18°C.

The "Day Heating threshold" can be set

differently for each heating circuit.

Changing the parameter "Day Heating threshold"

Press to open the text menu for the selected heating circuit.

Tap the [Heating circuit] line to open the submenu.

Double-tap on the [Day Heating threshold] line

(or select the line and press the [Change value] button).

The parameter "Night Heating threshold"

If the heating circuit is in "Night" mode, an outside temperature is set which, when exceeded, will result in the heating circuit being switched off.

The factory setting for this value is 2°C.

The "Night Heating threshold" can be set

differently for each heating circuit.

Changing the parameter "Night Heating threshold"

Press to open the text menu for the selected heating circuit.

Tap the [Heating circuit] line to open the submenu.

Double-tap on the [Night Heating threshold] line

(or select the line and press the [Change value] button).

A settings screen opens:

2 x

A settings screen opens:

2 x

Enter the new heating threshold for "Day" mode.

Press [Accept] to save the new value.

Press to open the "Heating circuit" overview.

SH Operation

Enter the new heating threshold for "Night" mode.

Press [Accept] to save the new value.

Press to open the "Heating circuit" overview.

2012-11

57

Adjusting the heating curve

Adjusting the heating curve

Adjusting the heating curve

If the heating circuit is always too warm or too cold, the flow temperature must be adjusted. This can be done using two parameters:

"Flow at -10°C" and "Flow at +10°C".

No large jumps in temperature

Do not set any large jumps in temperature when adjusting "Flow at +10°C" and "Flow at -10°C":

You may need to alter the flow temperatures again after one or two days, but working in small steps will help you to set the heating circuits more precisely, thus saving energy.

During the transition period -> "Flow at +10°C"

If the heating circuit is always too warm or too cold during the

transition period (spring and autumn),

only the flow temperature for "Flow at +10°C" is

reduced or increased.

80

50

40

30

20

70

60

Nigh t

Day

10

0

-20 -15 -10 -5 0 +5 +10

Outside temperature (°C)

+15 +20

Do not change the flow temperature "Flow at

-10°C" during the transition period.

Heating circuit

Factory settings for the heating circuit

With software versions 1.20.0 and higher, the system configuration for the heating circuit offers the user a choice between

underfloor and

radiator heating.

This choice pre-sets some of the parameters in the heating circuit. These parameters and their factory settings can be seen in the table below:

Preset

Max flow

Flow at -10°C

Flow at +10°C

Set-back

Enable temperature

Room effect

Underfloor Radiator

45°C

33°C

25°C

3°C

25°C

1°C

65°C

55°C

35°C

15°C

40°C

4°C

In winter -> "Flow at -10°C"

If the heating circuit is always too cold or too warm

in winter, only the flow temperature

"Flow at -10°" is increased or reduced.

80

50

40

30

70

60

Nigh

Day t

20

10

0

-20 -15 -10 -5 0 +5 +10

Outside temperature (°C)

+15 +20

Do not change the flow temperature "Flow at

+10°C" in winter.

58 www.eta.co.at

Heating circuit

Adjusting the heating curve for outside temperatures above 0°C -> Changing

"Flow at +10°C"

If the heating circuit is always too cold or too warm in the

transition period, the flow temperature

"Flow at +10°C" is increased or reduced.

No large jumps in temperature

For underfloor heating, never more than 2°C

For radiators, never more than 4°C

Press to open the text menu for the selected heating circuit.

Tap the [Heating circuit] line and, in the submenu, tap the [Heating curve] line.

Double-tap on the [Flow at +10°C] line (or select the line and press the [Change value] button).

Adjusting the heating curve

Adjusting the heating curve for outside temperatures below 0°C -> Changing

"Flow at -10°C"

If the heating circuit is always too cold or too warm

in winter, the flow temperature "Flow at -10°C" is

increased or reduced.

No large jumps in temperature

For underfloor heating, never more than 2°C

For radiators, never more than 4°C

Press to open the text menu for the selected heating circuit.

Tap the [Heating circuit] line and, in the submenu, tap the [Heating curve] line.

Double-tap on the [Flow at -10°C] line.

A settings screen opens:

2 x

A settings screen opens:

2 x

Enter the new flow temperature for this heating circuit. Press [Accept] to save the new value.

The text menu for the selected heating circuit is displayed. Press to open the "Heating circuit" overview.

SH Operation

Enter the new flow temperature for this heating circuit. Press [Accept] to save the new value.

The text menu for the selected heating circuit is displayed. Press to open the "Heating circuit" overview.

2012-11

59

Setting the "enable temperature"

Setting the "enable temperature"

Setting the parameter "enable temperature"

The heating circuit pump does not start until the energy source (buffer or boiler) has exceeded the

"enable temperature". You can give a heating circuit priority by setting the "enable temperature" lower than that for all the other heating circuits in the system.

Opening the heating circuit text menu

Press to open the text menu for the selected heating circuit.

Tap the line [Heating circuit] and, in the submenu, double-tap the line [Enable temperature].

2 x

A settings screen opens:

60

Enter the new enable temperature for this heating circuit. Press [Accept] to save the new value.

The text menu for the selected heating circuit is displayed. Press to return to the heating circuit overview.

www.eta.co.at

Heating circuit

Adjusting the "Set-back"

Heating circuit

The parameter "Set-back"

If the unit does not have a room sensor, the parameter "Set-back" is used to adjust the night mode. The control system subtracts the "Set-back" parameter from the heating curve "Day" to get the heating curve "Night".

Outside the time slots set in the timer, the heating circuit is in "Night" mode, and runs using the heating curve "Night".

The factory setting for this "Set-back" is 15°C.

The

"Set-back" can be adjusted for each

heating circuit. The following steps are the same for all heating circuits.

Adjusting the "Set-back"

Changing the parameter "Set-back"

Press to open the text menu for the selected heating circuit.

Tap the [Heating circuit] line and, in the submenu, tap the [Heating curve] line.

Double-tap on the [Set-back] line.

2 x

Do not use large set-backs

Do not overuse "set-back", as much higher air temperatures will be required to ensure comfort in the morning if the walls have cooled down too much overnight. In addition to reducing comfort, this also wastes the energy saved overnight.

Depending on the "Flow at -10°C" temperature and the type of heating circuit used (radiator or underfloor heating), the following guidelines apply for the set-back:

Temperature

Radiator Underfloor

Flow at -10°C

40°C 60°C 80°C

Set-back 5-8°C 10-15°C 15-22°C

30-40°C

3-5°C

A settings screen opens:

Enter the new temperature difference for the "Setback". Subtracting the "Set-back" from the heating curve "Day" gives you the heating curve "Night".

Press [Accept] to save the new value. The text menu for the selected heating circuit is displayed once more.

Press to return to the heating circuit overview.

SH Operation

2012-11

61

Service and maintenance records

Service and maintenance records

Keep records for service, maintenance or repairs

We recommend that you keep records about all service and maintenance work, as well as malfunctions. These records can be entered in the following pages.

Then you and our customer service will always have an overview of the work performed on the system.

Date

Performed by

Service / maintenance / cleaning

Worked performed / parts replaced

62 www.eta.co.at

Date

Performed by

Service and maintenance records

Service / maintenance / cleaning

Worked performed / parts replaced

SH Operation

2012-11

63

Artikel Nr. der Anleitung SH_Bedienung_Touch_EN

advertisement

Key Features

  • Automatic adjustment of operation to user needs
  • Control via app or display
  • External heat source control module

Related manuals

Frequently Answers and Questions

What is the required environment for a boiler setup?
A dry room is required. In particular, only condensation dryers may be used as clothes dryers in the same room.