Tripp Lite SmartOnline 100kVA Modular 3-Phase UPS System, On-line Double-Conversion International UPS Datasheet
Add to My manuals5 Pages
Tripp Lite SU100KX2 is a modular 3-phase UPS system that provides continuous power and protection for critical equipment. With its scalable design, you can add power modules as your needs grow. It offers N+1 redundancy, ensuring 100% availability. Its compatibility with various battery packs and extended runtime options ensures reliable backup power. The SU100KX2 also features a user-friendly interface with a real-time event log and dynamic battery management screen.
advertisement
SmartOnline 100kVA Modular 3-Phase UPS System,
On-line Double-Conversion International UPS
MODEL NUMBER: SU100KX2
Highlights
100kVA / 100,000VA / 80,000W on-line double-conversion 3 phase UPS
3 phase 220/380V, 230/400V,
240/415V 4-wire + ground wye input & output
Scalable design grows as your datacenter grows
Modular N+1 redundant architecture helps assure 100% availability
Parallel up to 4 UPS systems for redundancy or increased capacity
IGBT & DSP technology produce
<4% input harmonic distiortion
(THDi)
Hot swappable power modules,
Description
Tripp Lite SU100KX2 100kVA SmartOnline Modular 3-Phase Intelligent, True On-Line Double-Conversion UPS
Expandable runtime
System provides 100% system availability with N+1 modular architecture and parallel capability. In N+1 configurations, SU100KX2 provides 5 self-contained, redundant 20kVA power modules that support hot-swappable maintenance as connected equipment remains powered. One open slot for up to one additional
20kVA power module offers increased capacity upgrades to 120kVA. In parallel applications, configured and
Package Includes
SU100KX2 UPS System
PowerAlert Software
Parallel communication cable installed by a Tripp Lite authorized technician, up to 4 SU100KX2 models can be connected to provide fail-safe redundancy (two 100kVA models supporting up to 100kVA total load) or increased capacity (two 100kVA models
Instruction manual
Warranty information supporting up to 200kVA total load). Large capacity 100,000VA / 80,000W UPS continually converts incoming
AC power into filtered DC and resynthesizes output into perfectly regulated continuous sine wave AC output with less than 3% THD. Zero transfer time assures compatibility with all equipment types. High input power factor, advanced IGBT inverter and Digital Signal Processor (DSP) technology produce less than 4% input total harmonic distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs by installing a generator with a capacity equal to the equipment load (1:1 ratio). Up to 97% efficiency in optional economy mode reduces operating costs and BTU output.
Hardwire input and output connections support a variety of permanent or PDU power connections. Frequency is 50 or 60 Hz (auto-selectable). SU100KX2 power modules are housed in a single small-footprint tower compartment. Compatible battery pack models BP480V55, BP480V78, BP480V103 and
BP480V140 (sold separately) are housed in a separate stand-alone hardwired external battery compartment. Battery runtime can be extended with additional stand-alone hardwired external battery modules. A manual bypass breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power if the UPS requires maintenance.
Features
True On-Line Double-Conversion 100kVA / 100,000VA / 80kW / 80,000 watt SmartOnline Modular 3-Phase Intelligent UPS provides 100% system availability
Scalable, modular N+1 configurations support hot-swap replacement of any of the six self-contained 20kVA power modules while connected equipment remains powered
One open slot accommodates up to one additional 20kVA power module for increased capacity up to 120kVA
Parallel applications enable the connection of 2, 3 or 4 SU100KX2 models in parallel to enable advanced configurations for fail-safe redundancy, increased capacity and combinations of the two (all parallel installations must be performed by a Tripp Lite authorized technician)
1 / 5
increased capacity and combinations of the two (all parallel installations must be performed by a Tripp Lite authorized technician)
Full-time sine wave output with less than 3% output THD
High input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce low input THD (THDi)
Less than 4% input THD (THDi) reduces installation costs by allowing 1:1 generator sizing
Extremely efficient operation (up to 97%) saves energy and reduces BTU output
Maintains continuous operation with zero transfer time through blackouts, voltage fluctuations and surges
Removes harmonic distortion, electrical impulses, frequency variations and other hard-to-solve power problems
Wide input voltage correction range: 173-300V / 276-477V AC
Precision +/-1% output voltage regulation
4 available battery modules (BP480V55, BP480V78, BP480V103 and BP480V140) are housed in a separate, stand-alone hardwired external battery compartment (Battery modules sold separately)
Front panel combination LCD/LED display includes a real-time event log screen with up to 500 events listed
Dynamic battery management screen optimizes battery function to lengthen service life and allow cold restart of the UPS
Built-in RS-232 communication port works with included PowerAlert Software to provide shutdown commands and reporting on a single server
Accessory slot accepts an optional internal SNMPWEBCARD and MODBUSCARD accessory options
Emergency Power Off button turns UPS output OFF and disables Bypass output
Built-in Emergency Power Off (EPO) dry-contact interface supports remote emergency shutdown in large facilities
Specifications
General Info
RoHS y
OUTPUT
Output Capacity Details
Output Volt Amp Capacity (VA)
Output kVA Capacity (kVA)
Output Watt Capacity (Watts)
Output kW Capacity (kW)
Power Factor
Crest Factor
Nominal Output Voltage(s)
Supported
Nominal Voltage Details
Frequency Compatibility
Output Voltage Regulation (Line
Mode)
Output Voltage Regulation (Battery
Mode)
Output Receptacles
+/- 1%
Hardwire
One open power module slot enables installation of up to one additional 20kVA power module for increased capacity to 120kVA (authorized technician required)
100000
100
80000
80
0.8
3:1
220/380V; 230/400V; 240/415V; 3-Phase Wye
Less than 3% output THD
50 / 60 Hz
+/- 1%
2 / 5
Output AC Waveform (AC Mode) Pure Sine wave
Output AC Waveform (Battery Mode) Pure Sine wave
INPUT
Rated input current (Maximum Load) 129A (220/380), 123A (230/400), 116A (240/415)
Nominal Input Voltage(s) Supported 220/380V (3ph wye); 230/400V (3ph wye); 240/415V (3ph wye)
Nominal Input Voltage Description 3-Phase Wye, 4 wire (L1, L2, L3, N, G); Less than 4% input harmonic distortion (THDi)
UPS Input Connection Type
Input Phase
Hardwire
3-Phase
BATTERY
Expandable Battery Runtime
External Battery Pack Compatibility
Expandable Runtime Description
DC System Voltage (VDC)
Battery Replacement Description
Battery set sold separate
BP480V103 ; BP480V140 ; BP480V55 ; BP480V78 ; BP480V200 ; BP480V300 ; BP480V400 ; BP480V500
External battery pack wiring is contractor supplied
+/- 240VDC
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage Regulation Description
Overvoltage Correction
Undervoltage Correction
Online, double-conversion power conditioning
Maintains continuous operation without using battery power during overvoltages to 276-477 (3-phase, 4-wire, wye), reducing output within 1% of nominal
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300
(3-phase, 4-wire, wye)
USER INTERFACE, ALERTS & CONTROLS
Switches
ON button turns UPS inverter on. OFF button turns UPS inverter off. LCD Display Control Buttons browse through and select items displayed on LCD screen. EPO (Emergency Power Off) button turns UPS output off and disables
Bypass output
Alarm Cancel Operation
Audible Alarm
LED Indicators
Power-fail alarm can be silenced using alarm-cancel switch
Alarms signal a variety of operational conditions: low-battery, overload, shutdown, bypass and more
4-LED Display: Displays normal AC input, on battery power, bypass input and fault conditions
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
UPS AC Suppression Response
Time
EMI / RFI AC Noise Suppression
5960
Instantaneous
Yes
PHYSICAL
3 / 5
Installation Form Factors Supported with Included Accessories
Primary Form Factor
UPS Power Module Dimensions
(hwd, in.)
UPS Power Module Dimensions
(hwd, cm)
UPS Power Module Weight (lbs.)
UPS Power Module Weight (kg)
Tower
Tower
66.8 x 20.5 x 38.4
169.7 x 52.1 x 97.5
766.4
347.5
UPS Shipping Dimensions (hwd / in.) 76.1 x 28.5 x 48.2
UPS Shipping Dimensions (hwd / cm)
193.3 x 193.3 x 122.4
Shipping Weight (lbs.)
Shipping Weight (kg)
Cooling Method
UPS Housing Material
766.4
347.5
Fans
Steel
ENVIRONMENTAL
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC Mode BTU / Hr. (Full Load)
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
17400
COMMUNICATIONS
Communications Interface
PowerAlert Software
Communications Cable
LINE / BATTERY TRANSFER
Transfer Time
Low Voltage Transfer to Battery
Power (Setpoint)
High Voltage Transfer to Battery
Power (Setpoint)
DB9 Serial; Slot for SNMP/Web interface
Included
DB9 cabling included
No transfer time (0 ms.) in online, double-conversion mode
Maintains continuous operation without using battery power during brownout/undervoltage conditions to 173-300V
AC (3-phase, 4-wire, wye). Below this point, output is maintained utilizing reserve battery power
Maintains continuous operation without using battery power during overvoltages to 276-477V AC (3-phase, 4-wire, wye), reducing output within 1% of nominal. Above this point, output is maintained utilizing reserve battery power
SPECIAL FEATURES
Cold Start (Startup in Battery Mode
During a Power Failure)
High Availability UPS Features
Green Energy-Saving Features
Cold-start operation supported
Automatic inverter bypass; Hot swappable batteries
High efficiency economy mode operation; Schedulable daily hours of economy mode operation
4 / 5
CERTIFICATIONS
UPS Certifications CE; ROHS (Restriction of Hazardous Substances)
WARRANTY
Product Warranty Period
(International)
Product Warranty Period (Mexico)
Product Warranty Period (Puerto
Rico)
2-year limited warranty
2-year limited warranty
2-year limited warranty
© 2015 Tripp Lite. All rights reserved. All trademarks are the sole property of their respective owners. Tripp Lite has a policy of continuous improvement.
Specifications are subject to change without notice. Photos may differ slightly from final products.
5 / 5
advertisement
Key Features
- 100 kVA 80000 W
- Waveform: Sine
- Tower Black
Related manuals
Frequently Answers and Questions
What is the capacity of the Tripp Lite SU100KX2 UPS system?
What is the output voltage of the SU100KX2?
How many power modules does the SU100KX2 have?
What is the input voltage range of the SU100KX2?
What type of batteries are compatible with the SU100KX2?
What is the warranty period for the SU100KX2?
advertisement