Baxi Potterton Gold HE A Range User's Manual

Add to my manuals
60 Pages

advertisement

Baxi Potterton Gold HE A Range User's Manual | Manualzz
You can rely on
Installation & Service Instructions
Gold HE
Range
A
Condensing
Combination Boiler
These instructions include the Benchmark Commissioning
Checklist and should be left with the user for safe keeping.
© Baxi Heating UK Ltd 2008
Natural Gas
Building Regulations and the Benchmark Commissioning
Checklist
Potterton Gold Combi 24 HE A
G.C.No 47 393 18
Potterton Gold Combi 28 HE A
G.C.No 47 393 19
Potterton Gold Combi 33 HE A
G.C.No 47 393 20
Building Regulations (England & Wales) require notification of
the installation of a heating appliance to the relevant Local
Authority Building Control Department. From 1 April 2005 this
can be achieved via a Competent Persons Self Certification
Scheme as an option to notifying the Local Authority directly.
Similar arrangements will follow for Scotland and will apply in
Northern Ireland from 1 January 2006.
CORGI operate a Self Certification Scheme for gas heating
appliances.
These arrangements represent a change from the situation
whereby compliance with Building Regulations was accepted as
being demonstrated by completion of the Benchmark Logbook
(which was then left on site with the customer).
With the introduction of Self Certification Schemes, the
Benchmark Logbook is being withdrawn. However, a similar
document in the form of a commissioning checklist and service
interval record is incorporated at the back of these instructions.
This company is a member of the Benchmark initiative and fully
supports the aims of the programme. Its aim is to improve the
standards of installation and commissioning of central heating
systems in the UK and to encourage the regular servicing of all
central heating systems to ensure safety and efficiency.
Building Regulations require that installations should comply
with manufacturer's instructions. It is therefore important that
the commissioning checklist is completed by the installer. The
relevant section of Building Regulations only relates to
dwellings. Therefore the checklist only applies if the appliance is
being installed in a dwelling or some related structure.
© Baxi Heating UK Ltd 2008 All rights reserved. No part of this publication may
be reproduced or transmitted in any form or by any means, or stored in any
retrieval system of any nature (including in any database), in each case whether
electronic, mechanical, recording or otherwise, without the prior written
permission of the copyright owner, except for permitted fair dealing under
Copyrights, Designs and Patents Act 1988.
The flowchart opposite gives guidance for installers on the
process necessary to ensure compliance with Building
Regulations.
Applications for the copyright owner’s permission to reproduce or make other
use of any part of this publication should be made, giving details of the proposed
use, to the following address:
The Company Secretary, Baxi Heating UK Ltd, The Wyvern Business Park,
Stanier Way, Derby, DE21 6BF.
Full acknowledgement of author and source must be given.
WARNING: Any person who does any unauthorised act in relation to a
copyright work may be liable to criminal prosecution and civil claims for damages.
“Potterton” supports
Baxi Heating UK Ltd is a
BS-EN ISO 9001 Accredited Company
This product has an energy rating (A) on a scale of A to G.
For more information see www.boilers.org.uk. This is a certification mark.
2
© Baxi Heating UK Ltd 2008
The code of practice for the installation,
commissioning & servicing of central
heating systems.
Installer Notification Guidelines
Choose Building
Regulations Notification
Route
Competent Person's
Self Certification Scheme
Building Control
Install and Commission this
appliance to manufacturer's
instructions
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact
a government approved
inspector
Complete the
Benchmark Checklist
If you notify via CORGI Scheme,
CORGI will then notify the
relevant Local Authority
Building Control Scheme
on member's behalf
Install and Commission this
appliance to manufacturer's
instructions
Scheme Members only
Call CORGI on: 0800 408 1007
or log onto:
www.corgi-notify.com
within 10 days
Complete the
Benchmark Checklist
You must ensure that the
notification number issued by
CORGI is written onto the
Benchmark Checklist
CORGI will record the data and
will send a certificate of
compliance to the property
© Baxi Heating UK Ltd 2008
LABC will record the data
and will issue a
certificate of compliance
3
Legislation
IMPORTANT - Installation, Commissioning, Service & Repair
This appliance must be installed in accordance with the manufacturer’s instructions and
the regulations in force. Read the instructions fully before installing or using the
appliance.
In GB, this must be carried out by a competent person as stated in the Gas Safety
(Installation & Use) Regulations.
Definition of competence: A person who works for a CORGI registered company and
holding current certificates in the relevant ACS modules, is deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813 “Domestic
Gas Installations”.
The addition of anything that may interfere with the normal operation of the appliance
without express written permission from the manufacturer or his agent could invalidate
the appliance warranty. In GB this could also infringe the Gas Safety (Installation and
Use) Regulations.
Warning - Check the information on the data plate is compatible with local supply
conditions.
All CORGI registered installers carry a CORGI identification card and have a
registration number. You can check your installer is registered by telephoning
0800 915 0485 or writing to:1 Elmwood,
Chineham Park,
Crockford Lane,
Basingstoke. RG24 8WG
or check online at www.trustcorgi.com
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency)
Regulations 1993 No 3083” and is deemed to meet the requirements of Directive
92/42/EEC on the energy efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels:Type test for purpose of Regulation 5 certified by:
Notified Body 0085.
Product/Production certified by:
Notified Body 0085 & 0086.
For GB/IE only.
4
© Baxi Heating UK Ltd 2008
This company declare that no substances harmful to health
are contained in the appliance or used during appliance
manufacture.
The appliance is suitable only for installation in GB and IE and
should be installed in accordance with the rules in force, and
only used in a suitably ventilated location.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in accordance with
the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The Building
Regulations, The Building Regulations (Scotland), Building
Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
• The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
Person and installed in accordance with the current edition of
I.S. 813 ‘Domestic Gas Installations’, the current Building
Regulations and reference should be made to the current ETCI
rules for electrical installation.
All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
Codes of Practice - refer to the most recent version
In GB the following Codes of Practice apply:
Standard
Scope
BS 6891
Gas Installation.
BS 5546
Installation of hot water supplies for domestic
purposes.
BS 5449
Forced circulation hot water systems.
BS 6798
Installation of gas fired hot water boilers.
BS 5440 Part 1
Flues.
BS 5440 Part 2
Ventilation.
BS 7074
Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593
Treatment of water in domestic hot water
central heating systems.
In IE the following Codes of Practice apply:
Standard
Scope
I.S. 813
Domestic Gas Installations.
The following standards give valuable additional information;
BS 5546
Installation of hot water supplies for domestic
purposes.
BS 5449
Forced circulation hot water systems.
BS 7074
Expansion vessels and ancillary equipment for
sealed water systems.
BS 7593
Treatment of water in domestic hot water
central heating systems.
Safe Manual Handling
General
The following advice should be adhered to, from when first handling the boiler to the final stages of installation, and also during maintenance.
Most injuries as a result of inappropriate handling and lifting are to the back, but all other parts of the body are vulnerable, particularly shoulders, arms and hands.
Health & Safety is the responsibility of EVERYONE.
There is no ‘safe’ limit for one man - each person has different capabilities. The boiler should be handled and lifted by TWO PEOPLE.
Do not handle or lift unless you feel physically able.
Wear appropriate Personal Protection Equipment e.g. protective gloves, safety footwear etc.
Preparation
Co-ordinate movements - know where, and when, you are both going.
Minimise the number of times needed to move the boiler - plan ahead.
Always ensure when handling or lifting the route is clear and unobstructed. If possible avoid steps, wet or slippery surfaces, unlit areas etc. and take special care
on ladders/into lofts.
Technique
When handling or lifting always use safe techniques - keep your back straight, bend your knees. Don’t twist - move your feet, avoid bending forwards and
sideways and keep the load as close to your body as possible.
Where possible transport the boiler using a sack truck or other suitable trolley.
Always grip the boiler firmly, and before lifting feel where the weight is concentrated to establish the centre of gravity, repositioning yourself as necessary. See the
‘Installation’ section of these instructions for recommended lift points.
Remember
The circumstances of each installation are different. Always asses the risks associated with handling and lifting according to the individual conditions.
If at any time when installing the boiler you feel that you may have injured yourself STOP !!
DO NOT ‘work through’ the pain - you may cause further injury.
IF IN ANY DOUBT DO NOT HANDLE OR LIFT THE BOILER - OBTAIN ADVICE OR ASSISTANCE BEFORE PROCEEDING !!
© Baxi Heating UK Ltd 2008
5
CONTENTS
Section
6
© Baxi Heating UK Ltd 2008
Page
1.0
Introduction
7
2.0
General Layout
8
3.0
Appliance Operation
9
4.0
Technical Data
10
5.0
Dimensions and Fixings
11
6.0
System Details
12
7.0
Site Requirements
15
8.0
Flue Options
19
9.0
Plume Displacement
24
10.0
Installation
28
11.0
Commissioning
34
12.0
Completion
37
13.0
Servicing
38
14.0
Changing Components
40
15.0
Combustion Check
49
16.0
Electrical
50
17.0
Short Parts List
51
18.0
Fault Finding
52
Benchmark Checklist
58
1.0 Introduction
1.1
Description
1. The Potterton Gold Combi HE A is a fully automatic gas
fired wall mounted condensing combination boiler. It is room
sealed and fan assisted, and will serve central heating and
mains fed domestic hot water.
Case Front Panel
2. The boiler is set to give a maximum output of :24 models - 24 kW DHW
21 kW CH (Condensing)
28 models - 28 kW DHW
25.9 kW CH (Condensing)
33 models - 33 kW DHW
30.3 kW CH (Condensing)
3. It is designed for use on Natural Gas (G20).
4. The boiler is suitable for use only on fully pumped sealed
heating systems. Priority is given to domestic hot water.
5. The boiler is supplied with a filling loop and integral timer.
6. The boiler data badge gives details of the model, serial
number and Gas Council number and is situated on the inner
door panel. It is visible when the case front panel is removed
(Fig. 1).
Lower Door
Panel
Fig. 1
7. The boiler model name and serial number are also shown
on the information label on the rear or the lower door panel.
This is for user reference.
8. The boiler is intended to be installed in residential /
commercial / light industrial E.M.C. environments on a
governed meter supply only.
Data Badge
Information Label
9. The boiler must be installed with one of the purpose
designed flues such as the standard horizontal flue kit, part no.
5118489.
9. All systems must be thoroughly flushed and treated with
inhibitor (see section 6.2).
1.2
Contents of Pack
1. Boiler Unit
2. Wall Plate (inc. taps)
3. Set of Pipe (inc. nuts)
4. Template
5. Quick Fit Guide
6. Literature Pack
7. Filling Loop
© Baxi Heating UK Ltd 2008
7
2.0 General Layout
2.1
Layout
23
1
15
22
14
13
21
16
20
10
9
1.
Expansion Vessel
2.
Automatic Air Vent
3.
DHW Plate Heat Exchanger
4.
Circulation Pump
5.
Drain Off Point
6.
Pressure Relief Valve
7.
Optional Integral Timer Position
8.
Central Heating System Pressure Gauge
9.
PCB
10.
Control Box
11.
3-Way Valve Assembly
12.
Condensate Trap
13.
Flame Sensing Electrode
14.
Spark Electrode
15.
Primary Heat Exchanger
16.
Fan Assembly
17.
On/Off/Reset Selector Switch
18.
Central Heating Temperature Control
19.
Hot Water Temperature Control
20.
Venturi
21.
Air/Gas Collector
22.
Combustion Box Cover & Burner
23.
Igniter
24.
Burner On Light
25.
Central Heating Mode Light
26.
Domestic Hot Water Mode Light
27.
Display
28.
Integral Timer
8
7
12
2
11
3
5
4
6
25
26
2
1
12
11
3
5
7
10
9
0
4
11
18
19
8
12
© Baxi Heating UK Ltd 2008
24
1
8
27
2
17
3
bar
5
4
0
AM
8
3
7
1
8
PM
9
Reset
10
4
2
28
3.0 Appliance Operation
1
3.1
Central Heating Circuit
27
1. With a demand for heating, the pump circulates water
through the primary circuit.
2
3
4
7
26
20
5
6
25
24
18
Central Heating Mode (Fig. 2)
2. Once main burner ignites the fan speed controls the gas
rate to maintain the heating temperature measured by the
temperature sensor.
3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the burner
relights automatically (anti-cycling). The pump continues to
run during this period.
8
4. When the demand is satisfied the burner is extinguished
and the pump continues to run for a period of 3 minutes
(Pump Overrun).
22
9
11
23
21
3.2
10
17
16
19
15
14
13
12
Fig. 2
Key
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Primary Heat Exchanger
Burner
Ignition Electrodes
Flame Sensing Electrode
Gas Valve
Pump
Automatic Air Vent
Plate Heat Exchanger
Flow Sensor with Filter & Regulator
Pressure Relief Valve
Boiler Drain Point
Heating Return
Cold Water Inlet On/Off Valve and Filter
Gas Inlet
15
16
17
18
19
20
21
22
23
24
25
26
27
Domestic Hot Water Outlet
Heating Flow
Pressure Gauge
Water Pressure Sensor
Automatic By-Pass
Fan
Diverter Valve Assembly
Diverter Valve Motor
Domestic Hot Water Flow Temperature Sensor
Safety Thermostat
Central Heating Temperature Sensor
Expansion Vessel
Heat Exchanger Air Vent
Domestic Hot Water Mode (Fig. 3)
1. Priority is given to the domestic hot water supply. A
demand at a tap or shower will override any central heating
requirement.
2. The flow of water will operate the Hall Effect Sensor
which requests the 3 way valve to change position. This will
allow the pump to circulate the primary water through the
DHW plate heat exchanger.
3. The burner will light automatically and the temperature of
the domestic hot water is controlled by the temperature
sensor.
4. When the domestic hot water demand ceases the burner
will extinguish and the diverter valve will remain in the
domestic hot water mode, unless there is a demand for
central heating.
IMPORTANT: When the selector switch is in the ‘0’
(Off) position the electrical supply to the boiler is isolated.
The boiler will not operate and the integral timer will
require resetting once the selector switch is set to either
Position (i) or Position (ii).
1
Domestic Hot Water Circuit
27
3.3
2
3
4
7
26
20
5
6
18
1. The frost protection mode is integral to the appliance and
functions only with the selector switch (see Section 2.1) in
the domestic hot water and central heating position. If the
system temperature falls below 5° C then the boiler will fire
on its minimum setting until a flow temperature of 30° C is
reached.
3.4
25
24
Frost Protection Mode
Pump Protection
8
22
9
11
23
21
1. With the selector switch (see Section 2.1) in either the
central heating or central heating and domestic hot water
position, the pump will automatically operate for 1 minute in
every 24 hours to prevent sticking.
10
17
16
19
15
14
13
12
Fig. 3
© Baxi Heating UK Ltd 2008
9
4.0 Technical Data
4.1
Appliance Type
C13
Appliance Category
C33
C53
CAT I 2H
Gold Combi 24, 28 & 33 HE A
NOx Class
Inlet Pressure (Natural Gas - G20)
mbar
20
Central Heating Primary Circuit
Pressures
Injector (Natural Gas - G20)
7.5mm (24&28 model) 12mm(33 model)
Heat Input CH (Net)
Max
Min
24 model
kW
20.5
7
28 model
kW
24.7
9
33 model
kW
28.9
9.7
Heat Input CH (Gross)
Max
Min
24 model
kW
22.7
7.8
Power Consumption
155W (24 & 28 model) 160W (33 model)
28 model
kW
27.4
10
Electrical Protection
33 model
kW
32.1
10.8
5
Safety Discharge
Max Operating
Min Operating
Recommended Operating Range
Electrical Supply
230V~ 50Hz
(Appliance must be connected to an
earthed supply)
DHW Circuit
Pressures
Max Operating
Min Operating
IPX0D
Flow Rates
Heat Output CH (Non-Condensing)
Max
Min
24 model
kW
20
8.7
28
9.4
Heat Output CH (Condensing)
Max
Min
24 model
7.4
28 model
kW
25.9
9.5
33 model
kW
30.3
10.2
Heat Input DHW (Net)
Max
24 model
kW
24.7
28 model
kW
28.9
33 model
kW
34
Heat Input DHW (Gross)
Max
24 model
kW
27.4
28 model
kW
32.1
33 model
kW
37.7
Heat Output DHW
Max
24 model
kW
24
28 model
kW
28
33 model
kW
33
Max Gas Rate
(Natural Gas - G20)
(After 10 mins)
24 model
m3/h
28 model
3
m /h
3.1
33 model
m3/h
3.6
11.43
13.3
15.7
Condensate Drain
To accept 21.5mm (3/4 in) plastic waste pipe
DHW Flow Rate
@ 35o C Rise
9.8
11.5
13.5
Flue Terminal
Dimensions
100mm
125mm
Min Working
DHW Flow Rate
2
2
2
copper tails
22mm
22mm
22mm
15mm
15mm
15mm
Pump
Available Head
See graph below
F2L
24
21
DHW Flow Rate
@ 30o C Rise
Internal Fuse Rating
kW
kW
(33)
l/min
6.8
kW
8
0.15
(28)
l/min
3A
33 model
bar
(24)
l/min
External Fuse Rating
28 model
bar
3
2.5
0.5
1-2
Diameter
Projection
Connections
Gas Supply
Central Heating Flow
Central Heating Return
Cold Water Mains Inlet
DHW Flow
Pressure Relief Discharge
Outercase Dimensions
Casing Height
Overall Height Inc Flue Elbow
Casing Width
Casing Depth
Clearances
Above Casing
Below Casing
Front
Front
L.H. Side
R.H. Side
-
-
Expansion Vessel
- (For Central Heating
only. Integral with appliance)
bar
Min Pre-charge Pressure
0.5
780mm
965mm
450mm
345mm
Max Capacity of
CH System
(24,28)
litre
125
(33)
litre
155
Primary Water Content
of Boiler (unpressurised)
2.5
2.8
Temperatures
C.H. Flow Temp (adjustable)
25°C to 80°C max (± 5°C)
200 mm Min
200 mm Min
450 mm Min (For Servicing)
5 mm Min (In Operation)
5 mm Min
5 mm Min (In Operation)
D.H.W. Flow Temp (adjustable)
35°C to 60°C max (± 5°C)
dependent upon flow rate
Weights (kg)
2.61
(24)
Packaged Boiler Carton 48.6
Installation Lift Weight 43.6
(28)
49.2
44.2
(33)
51
46
Pump - Available Head
5.5
5
4.5
SEDBUK Declaration
4
The efficiency is 91.1% (all models)
3.5
This value is used in the UK Government’s Standard
3
dwellings. The test data from which it has been
calculated has been certified by 0087.
Metre (wg)
Assessment Procedure (SAP) for energy rating of
2.5
2
1.5
1
0.5
0
0
10
© Baxi Heating UK Ltd 2008
200
400
600
Flow Rate (l/h)
800
1000
1200
5.0 Dimensions and Fixings
Dimensions
A 780mm
At least 1.5°
E
G
B 345mm
C 450mm
D 116mm Ø Min.
A
E 185mm
(207mm for 80/125mm
flue systems)
F 145mm
G 131mm
B
H 180mm
360° Orientation
J
270mm
H
D
C
J
Flue Ø 100mm
F
Tap Rail
32.5 mm
Condensate
Drain
65 mm
Heating
Flow
(22mm)
© Baxi Heating UK Ltd 2008
65 mm
Domestic Hot
Water Outlet
(15mm)
65 mm
Gas
Inlet
(22mm)
65 mm
Cold Water
Inlet
(15mm)
65 mm
Heating
Return
(22mm)
Pressure Relief
Valve
(15mm)
11
6.0 System Details
6.1
Information
1. The Potterton Gold Combi HE A Condensing Combination
Boiler is a ‘Water Byelaws Scheme - Approved Product’.
To comply with the Water Byelaws your attention is drawn to
the following installation requirements and notes (IRN).
a) IRN 001 See text of entry for installation
requirements and notes.
b) IRN 302 Byelaw 14.
2. Reference to the WRc publications, ‘Water fittings and
materials directory’ and ‘Water supply byelaws guide’ give full
details of byelaws and the IRNs.
6.2
Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED SYSTEMS
ONLY.
Treatment of Water Circulating Systems
• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system will
deteriorate as corrosion sludge accumulates within the system,
risking damage to pump and valves, boiler noise and circulation
problems.
• When fitting new systems flux will be evident within the system,
which can lead to damage of system components.
• All systems must be thoroughly drained and flushed out. Using,
for example Betz-Dearborn Sentinel X300 or X400 or Fernox
Superfloc Universal Cleanser. They should be used following the
flushing agent manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should comply to BS7593 requirements, e.g.
Betz-Dearborn Sentinel X100 and Fernox-Copal which should be
used following the inhibitor manufacturer’s instructions.
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
• It is important to check the inhibitor concentration after
installation, system modification and at every service in
accordance with the manufacturer’s instructions. (Test kits are
available from inhibitor stockists.)
• For information or advice regarding any of the above contact
Technical Enquiries.
6.3
Bypass
1. The boiler is fitted with an automatic integral bypass.
6.4
System Control
1. A 24 hour electro - mechanical timer is supplied fitted to
the boiler.
2. Further external controls (e.g. room thermostat) should be
fitted to optimise the economical operation of the boiler.
12
© Baxi Heating UK Ltd 2008
6.0 System Details
6.5
Stop
Valve
Double
Check
Valve
System Filling and Pressurising (Fig. 4)
1. A filling point connection on the central heating return
pipework must be provided to facilitate initial filling and
pressurising and also any subsequent water loss
replacement/refilling.
Stop
Valve
A filling loop & instructions are provided with the boiler
DHW
Mains
Inlet
Temporary
Hose
CH
Return
2. The filling method adopted must be in accordance with all
relevant water supply regulations and use approved
equipment.
Fig. 4
3. Your attention is drawn to:
for GB: Guidance G24.2 and recommendation R24.2 of the
Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
4. The sealed primary circuits may be filled or replenished by
means of a temporary connection between the circuit and a
supply pipe, provided a ‘Listed’ double check valve or some
other no less effective backflow prevention device is
permanently connected at the inlet to the circuit and the
temporary connection is removed after use.
6.6
Filling Loop
Fig. 5
Expansion Vessel (Central Heating only)
1. The appliance expansion vessel is pre-charged to 0.5 bar.
Therefore, the minimum cold fill pressure is 0.5 bar. The
vessel is suitable for correct operation for system capacities up
to 125 litres (24, 28 models) 155 litres (33 models). For
greater system capacities an additional expansion vessel must
be fitted. For GB refer to BS 7074 Pt 1. For IE, the current
edition of I.S. 813 “Domestic Gas Installations”.
6.7
Pressure Relief Valve (Fig. 6)
1. The pressure relief valve is set at 3 bar, therefore all
pipework, fittings, etc. should be suitable for pressures in
excess of 3 bar and temperature in excess of 100°C.
2. The pressure relief discharge pipe should be not less than
15mm dia, run continuously downward, and discharge outside
the building, preferably over a drain. It should be routed in
such a manner that no hazard occurs to occupants or causes
damage to wiring or electrical components. The end of the
pipe should terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or
other public access. Consideration must be given to the
possibility that boiling water/steam could discharge from the
pipe.
Fig. 6
4. A remote relief valve kit is available to enable the boiler to
be installed in cellars or similar locations below outside
ground level (kit no. 5121379).
Pressure Relief Valve
Discharge Pipe
© Baxi Heating UK Ltd 2008
13
6.0 System Details
6.8
Domestic Hot Water Circuit (Fig. 7)
1. All DHW circuits, connections, fittings, etc. should be fully
in accordance with relevant standards and water supply
regulations.
Other Tap
Outlets
Expansion
Vessel
Boiler
3. A single check valve must be fitted as shown in Fig. 7 to
prevent backflow to the supply pipe and to ensure the
efficient operation of the expansion vessel which is required
to accommodate the thermal expansion of the water.
Check
Valve
Pressure Reducer
Valve
Stop Tap
2. Your attention is drawn to:
for GB: Guidance G17 to G24 and recommendation R17 to
R24 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
To Hot
Taps
4. When the domestic water system includes any device
which prevents water expanding back towards the supply
(check valve, loose jumpered stopcock, water meter, water
treatment device) then an expansion vessel must be fitted
(eg. Zilmet 160ml, R1/2 15bar).
5. If the hot water expansion is not provided for, then high
pressures can develop which may result in damage to fittings
and devices on the system.
Fig. 7
6. The boiler’s maximum working mains pressure is 8 bar,
therefore all pipework, connections, fittings, etc. should be
suitable for pressures in excess of 8 bar. A pressure reducing
valve must be fitted for pressures in excess of 8 bar. The
manufacturer of any outlet fittings, such as a shower valve,
may require a lower maximum pressure. The pressure
reduction must take account of all fittings connected to the
DHW system.
6.9
Showers
1. If a shower control is supplied from the appliance it
should be of the thermostatic or pressure balanced type.
Thermostatic type shower valves provide the best comfort
and guard against water at too high a temperature. Existing
controls may not be suitable - refer to the shower valve
manufacturer.
6.10
Hard Water Areas
1. If the area of the installation is recognised as a HARD
WATER AREA then a suitable device should be fitted to
treat the mains water supply to the boiler. Contact your
Water Distribution Company for advice on suitable devices.
14
© Baxi Heating UK Ltd 2008
7.0 Site Requirements
450mm
5mm Min
5mm Min
7.1
200mm Min
(300mm Min if
using 80/125mm
flueing system)
Location
1. The boiler may be fitted to any suitable wall with the flue
passing through an outside wall or roof and discharging to
atmosphere in a position permitting satisfactory removal of
combustion products and providing an adequate air supply.
The boiler should be fitted within the building unless
otherwise protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard-see
Section 7.3).
2. If the boiler is sited in an unheated enclosure then it is
recommended to leave the ON/OFF Selector Switch in the
domestic hot water and central heating position to give frost
protection.
780mm
3. If the boiler is fitted in a room containing a bath or shower
reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and Building
Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI rules.
200mm Min
Fig. 8
4. If the boiler is to be fitted into a building of timber frame
construction then reference must be made to the current
edition of Institute of Gas Engineers Publication IGE/UP/7
(Gas Installations in Timber Framed Housing).
7.2
Clearances (Figs. 8 & 9)
1. A flat vertical area is required for the installation of the
At least 1.5° boiler.
2. These dimensions include the necessary clearances around
the boiler for case removal, spanner access and air
movement. Additional clearances may be required for the
passage of pipes around local obstructions such as joists
running parallel to the front face of the boiler.
450mm Min
For Servicing
Purposes
5mm Min
In Operation
Fig. 9
© Baxi Heating UK Ltd 2008
15
7.0 Site Requirement
Gas Service Cock
7.3
Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances
installed in compartments. The appliance will run sufficiently
cool without ventilation.
7.4
Gas Supply
1. The gas installation should be in accordance with the
relevant standards. In GB this is BS 6891. In IE this is the
current edition of I.S. 813 “Domestic Gas Installations”.
Fig. 10
2. The connection to the appliance is a 22mm copper tail
located at the rear of the gas service cock (Fig. 10).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a smaller
diameter than the boiler gas connection (22mm).
Zone 2
Window
Recess
7.5
Zone 1
Zone 2
1. External wiring must be correctly earthed, polarised and
in accordance with relevant regulations/rules. In GB this is
the current I.E.E. Wiring Regulations. In IE reference should
be made to the current edition of ETCI rules.
Zone 3
Zone 0
0.6 m
2.4 m
Window
Recess
2. The mains supply is 230V ~ 50Hz fused at 3A.
Zone 2
NOTE: The method of connection to the electricity
supply must facilitate complete electrical isolation of the
appliance.
Zone 3
Fig. 11
Connection may be via a fused double-pole isolator
with a contact separation of at least 3mm in all poles
and servicing the boiler and system controls only.
In GB Only
Ceiling
Outside Zones
Zone 2
Zone 3
Window
Recess
Zone 2
3.0 m
Outside
Zones
Zone 3
Zone 1
Zone 2
Zone 0
0.6 m
Fig. 12
16
In GB Only
© Baxi Heating UK Ltd 2008
Electrical Supply
2.4 m
2.25 m
7.6
Bath & Shower Rooms
1. As the boiler is fitted with an integral timer when
installed in a room containing a bath or shower it cannot
be fitted in zones 1 or 2. (Figs. 11 & 12 shows zone
dimensions for a bathtub. For other examples refer to
Section 601 of the Current I.E.E. Wiring Regulations).
Reference must be made to the relevant requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
In IE reference should be made to the current edition of I.S.
813 “Domestic Gas Installations” and the current ETCI
rules.
7.0 Site Requirements
Termination to an internal soil and
vent pipe
Boiler
50mm
per me
tre of
2.5° M
inimum
Condensate Drain
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER
The condensate discharge pipe MUST NOT RISE at any point
along its length. There MUST be a fall of AT LEAST 2.5°
(50mm per metre) along the entire run.
pipe ru
n
fall
1. The condensate outlet will accept 21.5mm (3/4in) plastic
overflow pipe which should generally discharge internally into
the household drainage system. If this is not possible, discharge
into an outside drain is acceptable.
450mm min
Fig. 13
7.7
External termination via internal discharge
branch
e.g sink waste - downstream
Boiler
2. Ensure the discharge of condensate complies with any
national or local regulations in force.
BS 6798:2000 & Part H1 of the Building Regulations give
further guidance.
3. The discharge pipe should be run in a proprietary drain pipe
material e.g. PVC, PVC-U, ABS, PVC-C or PP.
50mm
Sink
per me
tre of
2.5° M
inimum
pipe ru
n
Pipe must terminate
above water level but
below surrounding
surface
fall
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
5. The pipe should be a minimum of 21.5mm diameter and
must be supported using suitably spaced clips to prevent
sagging.
6. It is advisable to keep the condensate pipe internal.
Fig. 14
7. External runs greater than 3 metres or runs in cold areas
should use 32mm waste pipe.
Termination to a drain or gully
Boiler
Pipe must terminate above
water level but below
surrounding surface
50mm
per me
tre of
2.5° M
n
fall
Fig. 15
Termination to a purpose made soakaway
Boiler
500mm min
50mm
per me
tre of
2.5° M
inimum
pipe ru
n
9. In all cases discharge pipe must be installed to aid disposal
of the condensate. To reduce the risk of condensate being
trapped, as few bends and fittings as possible should be used.
10. When discharging condensate into a soil stack or waste
pipe the effects of existing plumbing must be considered. If soil
pipes or waste pipes are subjected to internal pressure
fluctuations when WC's are flushed or sinks emptied then
back-pressure may force water out of the boiler trap and
cause appliance lockout.
pipe ru
inimum
8. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an external
run.
Examples are shown of the following methods of termination:i) to an internal soil & vent pipe - Fig. 13
ii) via an internal discharge branch (e.g. sink waste) - Fig. 14
iii) to a drain or gully - Fig. 15
iv) to a purpose made soakaway - Fig. 16
Holes in the soak-away must
face away from the building
fall
Fig. 16
© Baxi Heating UK Ltd 2008
17
Terminal Position with Minimum Distance (Fig. 18)
(mm)
7.0 Site Requirements
Aa Directly below an opening, air brick, opening
windows, etc.
Ba Above an opening, air brick, opening window etc.
Ca Horizontally to an opening, air brick, opening window etc.
D Below gutters, soil pipes or drain pipes.
E Below eaves.
F Below balconies or car port roof.
G From a vertical drain pipe or soil pipe.
H From an internal or external corner.
I
Above ground, roof or balcony level.
J
From a surface or boundary line facing a terminal.
K From a terminal facing a terminal (Horizontal flue).
From a terminal facing a terminal (Vertical flue).
L From an opening in carport (e.g. door, window)
into the dwelling.
M Vertically from a terminal on the same wall.
N Horizontally from a terminal on the same wall.
R From adjacent wall to flue (vertical only).
S From an adjacent opening window (vertical only).
T Adjacent to windows or openings on pitched and flat roofs
U Below windows or openings on pitched roofs
300
300
300
25
25
25
25
25
300
600
1200
600
7.8
NOTE: Due to the nature of the boiler a plume of water
vapour will be discharged from the flue. This should be
taken into account when siting the flue terminal.
1. The following guidelines indicate the general requirements
for siting balanced flue terminals. For GB recommendations
are given in BS 5440 Pt 1. For IE recommendations are given
in the current edition of I.S. 813 “Domestic Gas
Installations”.
1200
1500
300
300
1000
600
2000
2. If the terminal discharges onto a pathway or passageway,
check that combustion products will not cause a nuisance
and that the terminal will not obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony, above
ground or above a flat roof to which people have access,
then a suitable terminal guard must be provided.
a In addition, the terminal should be no nearer than 150 mm to an
opening in the building fabric formed for the purpose of accommodating
a built-in element such as a window frame. See BS 5440 Pt. 1.
IMPORTANT:
• Only ONE 25mm clearance is allowed per installation.
• Under car ports we recommend the use of the plume
displacement kit.
• The terminal position must ensure the safe and
nuisance - free dispersal of combustion products.
NOTE: The distance from a fanned draught appliance terminal
installed parallel to a boundary may not be less than 300mm in
accordance with the diagram below
300 min
Terminal
Assembly
Flue
*
Plume
Displacement Kit
IMPORTANT: If fitting a Plume
Displacement Flue Kit, the air inlet
must be a minimum of 100mm from
any opening windows or doors (see
Section 9.0).
Top View Rear Flue
Fig. 17
Property Boundary Line
J,K
Air Inlet
T
U
Opening Window
or Door
100mm
MIN.
N
R
I
M
C
I
I
F
D
E
A
S
I
F
J,K
B
L
G
A
A
H
H
I
Likely flue positions requiring
a flue terminal guard
18
© Baxi Heating UK Ltd 2008
Fig. 18
Fig. 18a
8.0 Flue Options
8.1
Horizontal Flue Systems
1. The standard flue is suitable only for horizontal termination
applications.
Y
X
2. All fittings should be fully engaged. The approximate
engagement is 40mm. Apply soap solution to the seal on
each fitting to aid assembly.
3. Maximum permissible equivalent flue lengths are:(60/100)
(80/125)
Horizontal Concentric 10 metres
20 metres
4. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:Concentric Pipes:
135° bend
0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
135° bend
0.25 metres
91.5° bend
0.50 metres
Horizontal
Flues
4. The elbow connected to the boiler adaptor is not included
in any equivalent length calculations.
Plume Displacement Kit 60 /100 Ø
5. The illustrations opposite show examples of permissible
flue systems.
1M Extensions, 45° & 93° bends are
also available - see Section 9.0
NOTE: Flue length is measured from point X to Y as
shown.
NOTE: Horizontal flue pipes should always be installed with a fall of at least 1.5°
from the terminal to allow condensate to run back to the boiler.
This bend is equivalent to
1 metre
C
A
Y
B
X
This bend is equivalent to
1 metre
Total equivalent length =
A+B+C+2x90°Bends
© Baxi Heating UK Ltd 2008
19
8.0 Flue Options
Vertical
Flues
(Twin Pipe)
8.2
Twin & Vertical Flue Systems
1. Maximum permissible equivalent flue lengths are:-
Vertical Concentric
Vertical Twin Pipe
Y
(60/100)
10 metres
15 metres
(80/125)
20 metres
2. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:Concentric Pipes:
135° bend
0.5 metres
93° bend
1.0 metres
Twin Flue Pipe
135° bend
0.25 metres
91.5° bend
0.50 metres
X
Vertical
Flues
The elbow supplied with the standard horizontal telescopic
flue kit is not included in any equivalent length calculations
NOTE: Flue length is measured from point X to Y as
shown.
Y
X
Total Equivalent Length =
A+B+C+1x90°Bend
Roof
Terminal
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 91.5°
bend or two 135° bends can be included without
reduction of the flue length.
If further elbows are required the flue length must
be reduced by the following amounts:-
The total equivalent length for this example is
= 6.5 metres.
Y
1 metre for each 91.5° bend
0.5 metre for each 135° bend
C
B
Equivalent
Length Value
1m extension
135°bend
91.5°bend
This bend is equivalent to
1 metre
1m
0.25m
0.5m
AIR DUCT
No of
fittings/pipes
5
2
2
Sub total
5.0m
0.5m
1.0m
Equivalent Length Air Duct = 6.5m
A
Equivalent
Length Value
X
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
FLUE DUCT
No of
fittings/pipes
5
2
2
Sub total
5.0m
0.5m
1.0m
Equivalent Length Flue Duct = 6.5m
20
© Baxi Heating UK Ltd 2008
8.0 Flue Options
8.3
Flue Accessories
A4
A2
Key Accessory
Size
Code No
FLUE GROUP A
Concentric Flue System 100mm diameter
A3
Telescopic Internal Flue Kit
315-500mm 5119654
A2
Telescopic Flue (inc. elbow) 315-500mm 5118069
A
Horizontal Flue Terminal (inc. elbow)
5118489
B
Flue Extension
1000mm 5111074
C
Flue Bend
93°
5111075
D
Flue Bend
135°
5111076
D
Flue Bend (pair)
135°
5111085
U
Pipe Support (painted)
100Ømm 5111080
R
Vertical Flue Adaptor
5111070
P
Wall Liner
5111067
S
Flue Terminal Deflector
5111068
A
B
A3
E
FLUE GROUP N
Twin Flue System 80mm diameter
E
Flue Extension (pair)
1000mm
F
Flue Bend (pair)
90°
G
Flue Bend (2 pair)
135°
J
Vertical Flue Boiler Adaptor Kit
H
Vertical Flue Adaptor
W
Pipe Support (pair)
80mm
Y
Flue Termination Kit
(horizontal termination)
80mm
P
K,K1
R
D
C
G
F
M
H
U,W
5111087
5111072
5111086
5111079
5111084
5111081
5120172
FLUE GROUP G
Concentric Flue System 80/125mm diameter
A4
Horizontal Flue Kit
B
Straight Extension Kit
1000mm
D
Bend Kit (pair)
135°
C
Bend
91.5°
U
Pipe support
125mm
5118580
5118584
5118597
5118588
5118610
FLUE GROUP A, N, G
Vertical Flue Kits
K
Vertical Flue Terminal (use with 5111070)
K1
Vertical Flue Terminal
L
Pitched Roof Flashing
25°/50°
M
Roof cover plate
N
Flat roof flashing
5111078
5118576
5122151
246143
246144
Y
L
N
S
© Baxi Heating UK Ltd 2008
J
21
8.0 Flue Options
For Twin Flue Systems fit the adaptors as follows:-
8.4
Flue Duct Adaptor
Blanking Plate
Boiler Adaptor
Flue Duct Adaptor
1. Engage the flue duct adaptor on the boiler adaptor,
making sure that it is pushed down as far as possible.
8.5
Air duct adaptor
1. Undo the screws securing the blanking plate to the boiler
top panel. Discard the plate.
2. There are three restrictor plates supplied in the kit. One
marked ‘23’ and one marked ‘27’, these can be discarded
The third restrictor MUST be positioned as shown in the
diagrams below.
3. Take one of the gaskets supplied in the kit and place on
the boiler top panel.
4. Align the appropriate restrictor as shown. Position the
second gasket over the restrictor.
5. Using the screws previously removed secure the inlet
adaptor to the top panel.
6. Continue to fit the twin flue system.
Air Duct Adaptor
Position of Restrictor
Gasket
Restrictor
Gasket
24 kW models
28/33 kW models
22
© Baxi Heating UK Ltd 2008
8.0 Flue Options
8.6
1. In the case of a pitched roof 25 - 50 degrees, position the lead
tile to replace/flash over existing roof tiling. Make an aperture in
the roof suitable for the lower tube of the roof terminal and
ensure the integrity of the roof cover is maintained. The
adjustable plastic collar can either be positioned on the lead tile
or the lower tube of the roof terminal prior to the final
positioning of the vertical flue through the tile. Check the collar is
correctly located to suit required roof pitch (either 25° to 38° or
37° to 50°). From inside the roof adjust the flue to a vertical
position and secure to the roof structure with the clamp supplied.
Approx
1425mm
Cut the same
amount off the
Air Duct &
Flue Duct
For Roof Terminals
2. For flat roof installations the aluminium flashing must be
incorporated into the roof covering and the appropriate aperture
made in the roof decking. The vertical flue is lowered onto the
flashing making sure the collar of the flue locates securely with the
flashing. (A mastic seal may be necessary). From inside the roof,
adjust the flue to a vertical position and secure to the roof
structure with the clamp supplied.
Air Duct
Flue Duct
IMPORTANT: If the boiler is not fitted immediately after the flue
system, temporary precautions must be taken to prevent rain
entry into the room of installation. Any precautionary measures
must be removed prior to commissioning the boiler.
Push Fit Adaptor
8.7
Flue Dimensions
The standard horizontal telescopic flue kit allows for lengths
between 100mm and 685mm from elbow to terminal (Fig. 19).
m
5m
68
The maximum permissible equivalent flue length is:
10 metres (60/100 system)
20 metres (80/125 system)
m
0m
10
Flue Deflector
8.8
Fig. 19
Flue Trim
1. The rubber flue trim supplied may be fitted to either the
outside wall or on the inner wall of installation.
Fig. 20
8.9
Terminal Guard (Fig. 21)
1. When codes of practice dictate the use of terminal guards, they
can be obtained from most Plumbers’ and Builders’ Merchants.
2. There must be a clearance of at least 50mm between any part
of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance name
and model number.
4. The flue terminal guard should be positioned centrally over the
terminal and fixed as illustrated.
8.10
Fig. 21
© Baxi Heating UK Ltd 2008
Flue Deflector (Fig. 20)
1. If required, push the flue deflector over the terminal end and
rotate to the optimum angle for deflecting plume. Secure the
deflector to the terminal with screws provided.
23
93° Elbow/Plume
Outlet Assembly
60Ø Support
Bracket
O Ring
0.9 metres
60Ø Exhaust
Flue Pipe
60Ø Support
Bracket
O Ring
Fig. 22
Flexible Flue
Trim
Adaptor
‘Jubilee’ Clip
O Ring
9.0 Plume Displacement
9.1
Plume Displacement Kit (Fig. 23)
Kit No 5118638
Content of kit
1 0.9m 60/100 Concentric Flue
1 1m 60 Dia Exhaust Flue Pipe
1 Adaptor
2 60 Dia Support Brackets
1 93° Elbow/Plume Outlet Assembly
1 Flexible Flue Trim
3 “O” Rings
1 ‘Jubilee Clip
1 Boiler Elbow
1. This kit is recommended for installations where the
condensate plume emitted from the flue may cause a nuisance
or affect the surroundings.
2. The terminal must be positioned outside the building with
the air inlet facing downward and outlet connection upwards.
60/100Ø
Concentric Flue
45°
45°
Outlet must be at
least 45° from
wall face
3. The plume outlet must always be at least 45° to the wall,
with the ‘peak’ uppermost to prevent rain entry (Figs. 24 &
25), and be at least 2 metres above ground level. It must be
secured as shown in Fig. 19. The plume outlet must also be at
least 500mm from the air inlet in any direction (Fig. 25).
Fig. 23
‘Peak’ Uppermost
NOTE: The outlet must be positioned so that any
condensate plume is directed away from adjacent surfaces.
There must be a constant fall along the entire length of the
flue system from the outlet back to the boiler.
4. It is possible to reduce or increase (with the addition of
extensions) the length of either or both the 60/100 concentric
and 60Ø exhaust.
5. Standard concentric flue extension kits may be added
between the boiler elbow and the terminal assembly.
6. The minimum length of the concentric flue is 100mm when
measured from the edge of the flue elbow.
500mm Min.
IMPORTANT: The maximum equivalent length of
concentric flue is:- 8 metres
Additional bends may be fitted in the concentric flue, but
the equivalent length must be reduced by 1 metre (93°
bend) or 0.5 metres (45° bend).
Fig. 24
Air Inlet at Bottom
Fig. 25
7. 60Ø 1 metre extensions (including support bracket), and
additional 93° & 45° elbows are available. Any additional 93°
& 45° elbows must be accounted for when calculating flue
lengths.
NOTE: Permitted positions of the plume outlet relative to
doors, windows etc. are the same as for conventional
concentric flues as detailed in the main Installation &
Servicing Instructions and BS5440 Pt. 1. It is NOT
necessary to fit a terminal guard over the air inlet or the
plume outlet.
24
© Baxi Heating UK Ltd 2008
16
14
14
12
60 Ø Exhaust (metres) X
16
24
10
8
28/
33
6
2
0
0
2
3
4
5
6
7
8
28/
33
6
9
0
1
Concentric 60/100 Flue (metres) Y
2
3
4
5
6
7
8
9
Concentric 60/100 Flue (metres) Y
Example 1
Flue Lengths - Not Permissible
Example 2
Flue Lengths - OK
14
24
10
8
28/
33
6
Example 3 - Flue Lengths OK
In the example shown in Fig. 4 assume that the concentric
part of the flue needs to be 2.3 metres long. Find the
position of ‘2.3’ on the horizontal axis of the graph and then
project upwards to the solid diagonal line. This is represented
by the vertical thick dotted line. Where this dotted line
intersects with the solid diagonal line on the graph, project
across to the vertical axis. As can be seen this corresponds
with 6 metres. Therefore, the total equivalent length of the
60Ø exhaust can be up to 6 metres. Any bend equivalencies
must be accounted for i.e. 93° bends are equal to 1 metre,
each 45° bend to 0.5 metres.
4
2
0
0
1
2
3
4
Example 1 - Not Permissible
If, for instance, a concentric length of 5 metres was required
and the 60Ø exhaust needed to be 6 metres the graph
shows that this combination would NOT be permissible as
the intersection point would be above the solid diagonal line.
Example 2 - Flue Lengths OK
Where both lengths have been determined they can be
applied to the graph to check that the installation is
permissible. For example, if it was known that 2 metres of
concentric flue and 4 metres of 60Ø exhaust were required,
the values could be applied to the graph as shown in
Example 2.. As the point of intersection of the dotted lines is
below the solid diagonal line, the combination of lengths is
shown to be acceptable.
16
12
Determining Permissible Lengths
In the graph the solid line diagonal represents the
relationship between the concentric flue assembly (and any
extensions) and the 60Ø exhaust (and any extensions or
additional bends).
8
4
1
24
10
2
0
9.2
12
4
60 Ø Exhaust (metres) X
60 Ø Exhaust (metres) X
9.0 Plume Displacement
5
6
7
8
9
Concentric 60/100 Flue (metres) Y
Example 3
Flue Lengths - OK
Support
Bracket
60Ø Exhaust
X
45° Elbow
Y
Flue Length - Worked Example
Potterton Gold Combi 33HE A
93° Elbow
1 metre Extension
Concentric 60/100 Flue
1 metre supplied in kit
Fig. 26
Concentric Flue
Additional Accessories
A - 93° Elbow
B - 45° Elbow (Pair)
C - 1 metre 60Ø Extension
© Baxi Heating UK Ltd 2008
5121369
5121370
5121368
Fig. 27
In Fig. 27 opposite an additional 93° bend and pair of 45°
elbows have been included in the 60Ø exhaust.
Also 3 straight extension pieces have been used.
To calculate total length:Length of 60Ø supplied in kit =
3 x 1 metre Extensions =
1 x 93° Elbow =
2 x 45° Elbow =
1 metre
3 metres
1 metre
1 metre (0.5 metres each)
Total 60Ø =
6 metres
After consulting the table in Example 3 it can be determined
that the concentric flue could be up to approximately 2.3
metres long.
25
9.0 Plume Displacement
9.3
General Fitting Notes
1. Cut a hole in the external wall which the concentric flue
assembly will pass through. The hole should allow the flue
to fall back to the boiler at an angle of at least 1.5°.
2. When completed the terminal must be at least 2 metres
above ground level (Fig. 19).
3. Measure and cut to size the concentric assembly and any
extensions that are being used.
Min. 2 metres
4. Insert the concentric assembly through the hole from
outside the building.
5. If required, the flexible flue trim should be fitted prior to
this as it cannot be fitted after. Use the large ‘Jubilee’ clip to
secure the trim to the flue (See Fig. 20, trim shown
dotted), with the screw part of the clip at the bottom.
6. Connect any extensions or elbows that are being used
to the concentric assembly. Engage the extension, elbow
or concentric assembly in the boiler flue elbow. Fit the
boiler flue elbow to the boiler adaptor.
Fig. 28
Flue Trim
7. Ensure that the concentric assembly and any extensions
fall back to the boiler at an angle of at least 1.5° and that
the external air inlet is to the bottom.
8. Use suitable brackets to support the concentric
assembly and any extensions, and make good inside and
outside.
Spigot
9. The 60Ø exhaust can now be fitted. Slide the adaptor
over the plain end of the 60Ø exhaust (Fig. 22) and engage
the exhaust in the terminal. Slide the adaptor down over
the spigot. Mark and drill the adaptor, using a 2mm bit, as
shown in Fig. 21. Secure the adaptor to the spigot using
one of the screws supplied.
Position of ‘Jubilee’ Clip
screw
Fig. 29
50mm
10. If it is necessary to shorten the 60Ø exhaust or any of
the extensions, the excess material must be cut from the
plain end of the pipe.
Adaptor
11. Determine the position of the 60Ø exhaust and mark
on the wall a suitable position for the support bracket. If
extensions are being used, a support bracket is supplied in
each kit.
Fig. 31
12. Drill the wall, and fit the bracket(s) using the plug and
screw provided.
30mm
Fig. 30
30mm
14. Fit the 93° elbow/plume outlet and secure with the
two remaining screws supplied. Ensure the plume outlet is
at least 45° to the wall and that the ‘peak’ is uppermost
(Fig. 24).
Fig. 32
26
© Baxi Heating UK Ltd 2008
13. Mark and drill the 60Ø exhaust, using a 2mm bit, as
shown in Fig. 23. Complete the installation of the 60Ø
exhaust, securing in the brackets.
Fig. 33
9.0 Plume Displacement
Plume Outlet
Elbow
9.3
General Fitting Notes (cont.)
15. For aesthetic purposes it is permissible to route the
60Ø exhaust in an enclosed box, but the air inlet and
plume outlet MUST remain in free air.
16. It is also possible to separate the plume outlet from the
93° elbow to allow the flue to be installed as shown in
Fig. 34.
50
0m
m
Mi
n.
17. To do this, first slacken the two screws retaining the
plume outlet to the elbow, and remove the outlet (Fig. 35).
The elbow can now be used to connect the vertical to
horizontal 60Ø exhaust (Fig. 34). Retighten the screws in
the elbow.
Fig. 34
18. The outlet can now be fitted into the female end of an
60Ø extension piece. It must be secured using two of the
screws supplied in the bag with the ‘Jubilee’ clip.
19. Mark the female end of the extension at 30mm as
shown in two positions, directly opposite each other
(Fig. 36).
Fig. 35
30mm
20. Using a suitable bit (e.g. 2mm), drill through the
extension and outlet. Secure using two of the screws
supplied.
21. The remaining screw must be used to secure the
adaptor to the concentric terminal.
Fig. 36
22. When the plume outlet is positioned under a balcony
or other projection (Fig. 37) it must protrude at least
200mm (it is not necessary to extend it further than this).
200mm Min.
23. When under balconies or projections it is permissible to
rotate the concentric flue length up to 70°, clockwise or
anti-clockwise (Fig. 38), if there is insufficient space to
connect vertically.
24.This will allow the connection of the exhaust to the
outlet spigot.
25. All other minimum & maximum dimensions must be
adhered to, and the air inlet positioned such that it will not
be subject to rain entry.
Fig. 37
70°
Concentric Flue Length
(shown end-on)
Outlet Spigot
Fig. 38
© Baxi Heating UK Ltd 2008
27
10.0 Installation
10.1
Unpacking & Initial Preparation
The gas supply, gas type and pressure must be checked for
suitability before connection (see Section 7.4).
NOTE: a small amount of water may drain from the
boiler in the upright position.
1. Remove staples, open flaps and remove the cardboard
sheet. Remove the polystyrene side pieces and literature.
Two people can then lift out the boiler (Figs. 39 & 40).
Fig. 39
2. After considering the site requirements
(see Section 7.0) position the fixing template on the wall
ensuring it is level both horizontally and vertically.
3. Mark the position of the two most suitable fixing slots for
the wall plate and boiler lower fixing holes. It is preferable to
use the vertical fixing slots.
Fig. 40
4. Mark the position of the centre of the flue hole (rear
exit). For side flue exit, mark as shown (Fig. 41).
5. If required, mark the position of the gas and water pipes.
Remove the template.
145mm
6. Cut the hole for the flue (minimum diameter 116mm).
7. Drill the wall as previously marked to accept the wall
plugs supplied. Secure the wall plate using the fixing screws.
8. Using a spirit level ensure that the plate is level before
finally tightening the screws.
For Side Flue Exit
Fig. 41
9. Connect the gas and water pipes to the valves on the
wall plate using the copper tails supplied. Ensure that the
sealing washers are fitted between the connections.
Flushing Tube
10. Fit the filling loop as described in the instructions
supplied with it.
Wall Plate
10.2
Flushing
1. Connect a tube to the central heating flow or return pipe
(Fig. 42 & 43).
Central Heating Return
Fig. 42
28
© Baxi Heating UK Ltd 2008
2. Flush thoroughly (see System Details, Section 6.2).
Fig. 43
10.0 Installation
10.3
Fitting the Filling Loop
1. The filling loop supplied with the boiler can be
connected to the taps on the wall plate at this point.
2. The filling loop is to be connected between the mains
cold water inlet and central heating return isolation taps.
Cold Inlet
3. The loop and valves must be connected as shown in
the diagram (Fig. 44a).
4. Note the orientation of the flow direction arrows on
the stop valve and double check/stop valves.
Double Check Valve
& Stop Valve
Fig. 44a
Temporary Filling
Loop
CH Return
Stop Valve
5. Remove the end caps from the isolation taps and put
to one side. Connect the valves to the taps. Ensure that
the fibre washers supplied are used on these joints.
6. Connect the temporary loop, ensuring that the seals
are fitted.
To fill, test and flush if required (Fig. 44c)
7. Take the blanking plugs from the kit, and using washers
supplied with the boiler, connect them to the central
heating flow and return taps, and the cold inlet tap. The
system can now be filled by opening the cold inlet supply
and stop valves.
Fitting the Valves
to the Taps
Temporary Loop and
Flanged Washers
8. If desired a suitable gauge can be connected to one of
the taps so that the system may be accurately
pressurised.
9. All joints, fittings and system components can now be
examined for soundness at operating pressure.
10. The system can be flushed by turning off the central
heating tap and connecting a suitable fitting to the loose
nut. From the fitting a hose pipe can be run to the
nearest convenient drain. When the tap is reopened the
system will flush.
Fig. 44b
11. Remove the blanking plug(s), pressure gauge and
flushing equipment from the appliance if used.
12. Continue with the installation and commissioning.
13. The filling loop must be disconnected and completely
removed after the system is pressurised.
Pressure
Gauge
14. Hand tighten the two previously removed end caps
to the stop valve and double check valve.
Blanking
Plugs
Hose and
Fitting
Fig. 44c
© Baxi Heating UK Ltd 2008
29
Wall Plate
10.0 Installation
10.4
Fitting The Boiler
1. Lift the boiler using the Lifting Points as shown by the
shaded areas (Fig. 45). The boiler should be lifted by TWO
PEOPLE. Engage the slots at the top rear of the boiler on the
wall plate (Fig. 46) (see Safe Manual Handling page 5).
2. Ease the boiler forwards and remove the sealing caps from
the boiler connections.
NOTE: A small amount of water may drain from the boiler
once the caps are removed.
Fig. 46
Fig. 45
Suggested Lifting Points
shown as shaded area
3. Insert the sealing washers between the valves and pipes on
the wall plate and the boiler connections. THE RUBBER
WASHERS MUST BE USED ON THE GAS CONNECTION.
4. Tighten all the connections.
10.5
Fitting the Pressure Relief Discharge Pipe
(Fig. 47)
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the vicinity of
the boiler. Make up as much of the pipework as is practical,
including the discharge pipe supplied.
3. The pipework must be at least 15mm diameter and run
continuously downwards to a discharge point outside the
building. See section 6.7 for further details.
4. Utilising one of the sealing washers, connect the discharge
pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to the
outside discharge point.
Pressure Relief Valve
IMPORTANT: Make all soldered joints before connecting
to the pressure relief valve.
10.6
Fig. 47
Discharge Pipe
Condensate Drain (see section 7.7)
1. Connect the condensate drain to the trap outlet pipe.
Ensure the discharge of condensate complies with any
national or local regulations in force (see British Gas
“Guidance Notes for the Installation of Domestic Gas
Condensing Boilers”.
2. The connection will accept 21.5mm (3/4in) plastic overflow
pipe which should generally discharge internally into the
household drainage system. If this is not possible, discharge into
an outside drain is acceptable.
30
© Baxi Heating UK Ltd 2008
10.0 Installation
m
5m
68
10.7
m
0m
10
Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between 100mm
minimum and 685mm maximum, as measured from the
edge of the flue elbow outlet to the joint between the
terminal and air duct (Fig. 48).
Fig. 48
2. Locate the flue elbow on the adaptor at the top of the
boiler. Set the elbow to the required orientation (Fig. 50).
The elbow is fully engaged when there is a distance of
20mm from the adaptor to the indicator line (Fig. 49).
20mm
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
Wall Thickness
Indicator line
Fig. 49
Flue Elbow
3. Measure the distance from the outside wall face to the
elbow. This dimension will be known as ‘X’ (Fig. 51).
4. To dimension ‘X’ add 50mm. This dimension to be
known as ‘Y’.
(X)
Apply Lubricant for
ease of assembly.
IMPORTANT: Check all dimensions before cutting.
Ensure Elbow is fully
engaged into Boiler
Adaptor
Adaptor
5. Mark dimension ‘Y’ on the flue as shown (Fig. 52).
Carefully cut the waste material from the flue, ensuring that
the ducts are square and free from burrs.
Fig. 50
Wall Thickness
(X)
Fig. 51
Waste
Y
Flue
Fig. 52
© Baxi Heating UK Ltd 2008
31
10.0 Installation
Inner Flue Support Bracket
10.7
Fitting the Flue (Cont)
6. The inner flue duct support bracket may be in the waste
portion of the flue. In this case retrieve the bracket before
discarding the waste.
7. Take the inner flue support bracket (if not already fitted)
and engage it over the flue duct. This will centralise the flue
and air ducts, and ease assembly (Fig. 53).
Fig. 53
8. Insert the flue through the hole in the wall. Fit the elbow
to the boiler adaptor, ensuring that it is pushed fully in.
Apply Lubricant for
ease of assembly.
Ensure Flue is fully
engaged into Flue
Elbow
9. Draw the flue back through the wall and engage it in the
elbow. It may be necessary to use soap solution or similar
to ease assembly of the elbow adaptor and flue (Fig. 54).
10. Ensure that the terminal is positioned with the slots to
the bottom (Fig. 55).
IMPORTANT: It is essential that the flue terminal is fitted
as shown to ensure correct boiler operation and prevent
water entering the flue.
11. Make good between the wall and air duct outside the
building.
12. Fit the flue trim if required, and if necessary fit a terminal
guard (see Section 8.8 & 8.9).
Slots at bottom
Fig. 55
CONCENTRIC VERTICAL FLUE
13. Once the length of the vertical concentric extension has
been determined mark and carefully cut off the excess
material. The cut end MUST be square and free of burrs to
ensure correct insertion into the boiler adaptor.
Fig. 54
25mm
14. Measure 25mm from the end of the flue extension and
apply a length of tape around the outer duct (Fig. 56).
15. Engage the extension into the adaptor up to this
position (Fig. 57). Once the installation of the flue is
complete and all support brackets are securely in place
remove the tape.
Extension
Fig. 56
Tape
Cut End
Adaptor
Apply Lubricant for
ease of assembly.
Ensure Extension is
fully engaged into
Boiler Adaptor
Fig. 57
32
© Baxi Heating UK Ltd 2008
10.0 Installation
10.8
Making The Electrical Connections
The boiler is fitted with a 1.3m length of 3 core cable. This
can be connected to the fused 3A 230V 50HZ supply.
NOTE: Both the Live and Neutral connections are fused.
To connect an external control proceed as follows:Terminal Block Cover
1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.
2. Completely undo the screws securing the facia panel and
hinge it down (Fig. 58).
3. Undo the terminal block cover securing screw and
remove the cover (Fig. 58).
Fig. 58
Fig. 59
4. Slacken the unused cable clamp on the LH side of the
boiler chassis (Fig. 59). Insert the external control wiring
through the clamp and route it to the terminal block.
Facia Panel
Cable Clamp
5. Refer to the instructions supplied with the control.
IMPORTANT: The room thermostat MUST be suitable
for 230V switching.
Fused Spur
L
N
Room ‘Stat
NOTE: An external frost thermostat cannot be used
with the optional integral timer.
N
bk 1
bk 2
230V
g/y
b
N
7. Ensure that the external control input cable(s) have
sufficient slack to allow the control box to drop down.
Tighten the cable clamp on the boiler chassis.
br
L
Fig. 60
8. Replace the terminal block cover, routing the external
control input cable(s) through the second cut-out.
Frost Thermostat
Fused Spur
L
6. Remove the link between terminals 1 & 2. The 230V
supply at terminal 2 must be connected to the thermostat.
The switched output from the thermostat must be
connected to terminal 1 (Figs. 60 & 61). If the room
thermostat being used incorporates an anticipator it MUST
be wired as shown in Figs. 60 & 61.
N
Room ‘Stat
10.9
230V
N
bk 1
230V
bk 2
g/y
External Clock
N
L
Fig. 61
Preliminary Electrical Checks
1. Prior to commissioning the boiler preliminary electrical
system checks should be carried out.
2. These should be performed using a suitable meter, and
include checks for Earth Continuity,
Resistance to Earth, Short Circuit and Polarity.
b
br
NOTE: The 230V switched signal for external controls
(Frost Stat - Room Stat - Timer) must always be taken
from terminal 2 at the boiler. Live, Neutral and Earth to
power these controls must be taken from the Fused Spur.
© Baxi Heating UK Ltd 2008
33
Heat Exchanger
Automatic Air Vent
11.0 Commissioning
Fig. 62
11.1
Commissioning the Boiler
1. Reference should be made to BS 5449 Section 5 when
commissioning the boiler.
2. Open the mains water supply to the boiler.
IMPORTANT: The heat exchanger air vent on top of the
boiler (Fig. 62) MUST be opened before filling the
primary system.
Screw
3. Open all hot water taps to purge the DHW system.
Pump
Automatic Air
Vent
4. Ensure that the filling loop is connected and open, then
open the heating flow and return valves on the boiler.
5. Open the screw on the automatic air vent on the pump
body (Fig. 63).
6. The system must be flushed in accordance with BS 7593
(see Section 6.2) and the flushing agent manufacturers
instructions.
7. Pressurise the system to 1.5 bar (Fig. 64) then close and
disconnect the filling loop.
2
Pump
Fig. 63
1
3
8. Turn the gas supply on and purge according to in GB BS
6891 and in IE I.S. 813 “Domestic Gas Installations”.
4
0
bar
Selector Switch
Display
Pressure Gauge
Fig. 64
9. Test for gas soundness.
10. Hinge the facia panel upwards and refit the case front
panel. Tighten the securing screws.
2
1
12
11
3
7
10
9
0
4
11
© Baxi Heating UK Ltd 2008
12
34
1
Fig. 65
Domestic Hot Water
Temperature Control
2
Central Heating
Temperature Control
3
bar
5
4
0
AM
8
3
7
1
8
PM
9
5
10
4
2
Reset
11. Turning either of the temperature control knobs will set
the relevant temperature. When the knob is turned the
display will alter and show the selected temperature. After a
few seconds the display reverts to show the current boiler
temperature (Fig. 65).
11.0 Commissioning
11.2
x2
Checking
1. The gas valve is factory set and the burner pressure cannot
be measured as it is altered by suction of the fan and
modulates as demand on the boiler alters. The gas supply
pressure should be 20mb.
2. If necessary the gas rate may be checked after running the
boiler for 10 minutes with any other appliances and pilot
lights turned off.
Central Heating
Temperature Control
Fig. 66
3. Ensure that the integral timer and any external controls are
calling for heat, and the selector switch is in the central
heating and hot water position (
). The current boiler
temperature is shown on the display.
Domestic Hot Water
Temperature Control
4. To check the gas rate it is necessary to set the boiler to
‘Calibration Mode’.
Selector Switch
Display
5. Turn both temperature control knobs fully anticlockwise,
then quickly turn the DHW temperature knob 1/4 clockwise
twice and back fully anticlockwise (Fig. 66).
2
1
12
11
3
7
3
10
9
0
4
1
12
11
Domestic Hot Water
Temperature Control
2
Central Heating
Temperature Control
3
bar
5
4
0
AM
8
7
1
8
PM
9
5
10
4
2
Reset
6. The display will now alternate between ‘SF’ and the
current boiler temperature and both green LEDs will flash
(Figs. 67 & 68).
7. Turn CH temperature control knob fully clockwise. As the
knob is turned the display will change from ‘0’ to ‘00’ (Fig. 69)
indicating maximum rate, then revert to ‘P’ alternating with
the current boiler temperature (Figs 70 & 71).
8. A gas rate measurement may now be made. Approximate
values are:-
Fig. 67
Fig. 68
24 model
2.6m3/h
28 model
3.1m3/h
33 model
3.6 m3/h
9. The ‘Calibration Function’ is active for 20 minutes unless
the maximum CH temperature is exceeded.
10. The function can be disabled at any time by turning the
DHW temperature knob.
Fig. 69
Fig. 70
© Baxi Heating UK Ltd 2008
Fig. 71
35
11.0 Commissioning
11.3
Setting the Timer
10
The Electro-Mechanical Timer allows the central heating
system to be set every 15 minutes.
9
Time Pointer
Using the three position switch the timer will allow either
constant operation, timed operation or central heating off.
8
Constant
Move the switch button by sliding to the desired position.
7
Timed
Three position switch (Fig. 71a)
AM
Off
5
0
Constant (Top position): The heating will be on
constantly irrespective of the position of the tappets.The
heating will be controlled by the main thermostat on the
appliance and/or any external controls.
4
IN
3
Fig. 71a
Timed (Central position): The heating will operate
according to the position of the tappets and be controlled as
above.
2
Rotate to adjust time
4
0
Off (Bottom position): No central heating.
Domestic hot water will operate on demand.
2
3
1
12
To set the time of day
Turn the timer outer bezel clockwise, to align the pointer
with the correct time to the nearest 15 minutes
ensuring that A.M./P.M. is considered. Do not at any time
attempt to turn the bezel anti-clockwise.
11
To set the timed heating program
Decide which times of the day the central heating is required.
AM
8
7
7
8
PM
9
5
10
4
4
9
10
5
0
GRASSLIN
The heating will operate when the white tappets are set to
the outer edge of the bezel.
3
2
1
12
11
To ensure the heating stays OFF set the required tappets
inwards towards the centre of the bezel.
Each tappet represents 15 minutes.
For example: If the heating is not required between
10 A.M. and 11 A.M. the four tappets anticlockwise from the
10 A.M. will be set inwards (Fig. 71b).
On Position
12
Off Position
11
10
9
Time Pointer
36
© Baxi Heating UK Ltd 2008
Fig. 71b
12.0 Completion
12.1
Case Front Panel
Completion
1. Instruct the user in the operation of the boiler and
system explaining the operational sequence.
2. Set the central heating and hot water temperature
control knobs to the requirements of the user.
3. Carefully read and complete all sections of the
Benchmark Commissioning Checklist at the rear of this
publication that are relevant to the appliance and
installation. These details will be required in the event of
any warranty work. The publication must be handed to the
user for safe keeping and each subsequent regular service
visit recorded.
4. For IE, it is necessary to complete a “Declaration of
Conformity” to indicate compliance with I.S. 813. An
example of this is given in I.S. 813 “Domestic Gas
Installations”. This is in addition to the Benchmark
Commissioning Checklist.
5. Hand over the Users Operating, Installation and
Servicing Instructions giving advice on the necessity of
regular servicing.
Facia Panel
Fig. 72
© Baxi Heating UK Ltd 2008
37
13.0 Servicing
13 .1
Case Front Panel
Annual Servicing
1. For reasons of safety and economy, it is recommended that
the boiler is serviced annually. Servicing must be performed by
a competent person in accordance with B.S. 7967-4:2007.
If a suitably calibrated combustion analyser is available it
may not be necessary to perform a full strip down of the
appliance. Proceed as follows.
Check for/inspect:Evidence of leakage of products of combustion
Water leaks
Heat stress
Deterioration such as corrosion
Visible condition of seals and joints
Flue system and ventilation
Condensate drain system
Operation at designed maximum heat input
Fig. 73
If the above are satisfactory perform a combustion check
The CO/CO2 ratio must be less than 0.004 and the CO2
should be 8.7% ± 0.2 (max. rate) and 8.4% ± 0.2 (min.
rate). This can be adjusted - see Section 15.0 - if the
readings are incorrect. When correct combustion
readings cannot be achieved by adjustment a full strip
down must be performed - see below. Carefully check
items such as the burner, injector and heat exchanger
for blockage or damage, rectifying as necessary. Recheck the combustion. Once satisfactory readings have
been achieved and any other defects corrected complete
the relevant Service Interval Record section of the
Benchmark Commissioning Checklist at the rear of this
publication.
Facia Panel Securing
Screws
Where no suitable analyser is available a strip down
service must be performed as described below.
2. After servicing, complete the relevant Service Interval
Record section of the Benchmark Commissioning Checklist at
the rear of this publication.
If a full strip-down is to be performed proceed as follows:3. Ensure that the boiler is cool.
Inner Door
Panel
4. Ensure that both the gas and electrical supplies to the
boiler are isolated.
Fig. 74
5. Slacken the screws securing the facia panel. Lift the
outercase panel so that its securing tabs are clear of the facia.
Remove the panel, allowing the facia to hinge down (Fig. 73).
6. Remove the screws securing the inner door panel. Lift the
panel slightly to disengage it from the studs on top of the case
(Fig. 74).
7. Unscrew the sump from the bottom of the condensate trap
assembly (Fig. 75).
Sump
8. Remove any deposits from the sump and trap. Clean as
necessary and replace the sump.
Fig. 75
38
© Baxi Heating UK Ltd 2008
13.0 Servicing
Burner
Viewing Window
13.1
Annual Servicing (Cont)
9. Undo the nut on the gas inlet pipe to the venturi (Fig. 77)
and pull the sensing pipe off the fan.
7.5 ± 1
4 ± 0.5
10. Disconnect the electrode leads, noting their position,
and the fan electrical plugs.
11. Undo the four nuts retaining the combustion box cover
to the heat exchanger.
12. Carefully draw the fan, collector and cover assembly
forward, being careful to retain the injector in the venturi
(Figs. 76 & 77).
10 ± 1
Electrode Position
13. Clean any debris from the heat exchanger and check
that the gaps between the tubes are clear.
Fan, Collector and Cover
Assembly
14. Inspect the burner, electrodes and insulation, cleaning or
replacing if necessary. Clean any dirt or dust from the air
box.
15. Reassemble in reverse order.
NOTE: The sensing pipe must be reconnected to the
fan, not the venturi.
Electrode
Leads
DHW Filter (Fig. 79)
16. If the flow of domestic hot water is diminished, it may
be necessary to clean the filter.
Fig. 76
17. Initially check the cold water inlet tap filter.
Venturi
18. Turn the tap off and draw off from a hot tap. Undo the
blanking cap and remove the threaded bush (Fig. 78).
19. Extract the filter and rinse thoroughly in clean water.
Reassemble and check the flow. If required clean the
restricter filter as described below.
Injector
Threaded
Fig. 78
Bush
Fig. 77
20. Pull off the Hall Effect sensor. Undo the restricter from
the inlet/return manifold (Fig. 79).
21. Rinse the filter thoroughly in clean water and reassemble
in reverse order.
Gas Inlet Pipe
22. Turn the selector switch fully anticlockwise against the
spring pressure to the reset position and hold for 5 seconds
to reset the boiler.
Hall Effect
Sensor
Blanking
Cap
Cold Water
Inlet Tap
23. Complete the relevant Service Interval Record section of
the Benchmark Commissioning Checklist at the rear of this
publication and then hand it back to the user.
Restricter
Hydraulic Inlet
Assembly
Fig. 79
© Baxi Heating UK Ltd 2008
Filter
39
14.0 Changing Components
Bracket
Igniter
Igniter Feed
Plug
IMPORTANT: When changing components ensure that
both the gas and electrical supplies to the boiler are
isolated before any work is started. When the
component has been changed turn the selector switch
fully anticlockwise against the spring pressure to the
reset position and hold for 5 seconds to reset the boiler
before recommissioning.
See Section 13.1 “Annual Servicing” for removal of case
panel, door etc.
Electrode
Leads
14.1
Igniter (Fig. 80)
1. Disconnect the igniter feed plug and the electrode leads,
noting their positions.
Fig. 80
2. Undo the screw securing the bracket to the boiler.
3. Remove the igniter and transfer the bracket to the new
component.
4. Reassemble in reverse order.
14.2
Spark and Sensing Electrodes (Fig. 81)
1. Disconnect the electrode leads, noting their positions.
2. Remove the retaining screws securing each of the
electrodes to the combustion box cover and remove the
electrodes.
3. Check the condition of the sealing gasket and replace if
necessary. Reassemble in reverse order.
Spark
Electrode
Electrode
Leads
Sensing
Electrode
Fig. 81
40
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.3
Fan (Fig. 83)
1. Undo the nut on the gas inlet pipe to the venturi (Fig. 83)
and pull the sensing pipe off the fan.
2. Disconnect the electrode leads, noting their position and
disconnect the fan electrical plugs.
3. Undo the screws securing the collector to the cover (33
models) or extension piece (24 & 28 models).
4. Remove the collector and fan assembly, being careful to
retain the injector in the venturi.
5. Undo the screws securing the fan to the venturi and fit the
new fan, replacing the seal if necessary.
6. Examine the burner gasket and replace if necessary.
Venturi
7. Reassemble in reverse order, ensuring that the injector is
in place and the sensing pipe is connected to the fan.
Injector
14.4
Venturi (Fig. 82)
Cover
1. Remove the collector and fan assembly as described in
section 14.3.
2. Extract the injector from the venturi.
Gas Inlet Pipe
Fig. 83
3. Undo the screws securing the fan to the venturi and the
venturi to the collector.
Burner
Gasket
IMPORTANT: When fitting the new venturi, ensure the
arrows on it’s base point into the collector (Fig. 84).
4. Examine the seals and burner gasket, replace if necessary.
Gas Inlet
Fan
5. Reassemble in reverse order, ensuring that the injector is
in place.
14.5
Venturi
Injector
Injector (Fig. 82)
1. Remove the collector and fan assembly as described in
section 14.3.
Collector
Fig. 82
2. Extract and replace the injector and reassemble in reverse
order.
Fig. 84
When fitting the venturi
ensure that the arrow is
pointing forward
© Baxi Heating UK Ltd 2008
41
14.0 Changing Components
Cover
14.6
Burner (Fig. 85)
Burner
1. Undo the screws securing the collector to the cover and
venturi. (On 24 & 28 models there is an extension piece
fitted to the cover, remove this also).
Gasket
Extension Piece
(24 & 28 models)
2. Withdraw the burner from the cover and replace with
the new one.
3. Examine the gasket, replacing if necessary.
4. Reassemble in reverse order.
Venturi
14.7
Insulation (Fig. 86)
1. Remove the electrode leads, noting their positions. Also
remove the electrodes as described in section 14.2.
Collector
Fig. 85
2. Undo the screws securing the collector to the venturi and
the nuts holding the cover to the heat exchanger. Draw the
collector and cover assembly away.
3. Remove the cover insulation piece.
4. Fit the new insulation carefully over the burner and align
it with the slots for the electrodes.
5. The rear insulation is retained by a screw and large
washer, remove these and draw the insulation out of the
heat exchanger.
6. Examine the cover seal and replace if necessary.
Heat
Exchanger
Rear
Insulation
Spark
Electrode
Venturi
Cover
Insulation
Seal
Fig. 86
Collector
Electrode
Leads
42
Sensing
Electrode
© Baxi Heating UK Ltd 2008
14.0 Changing Components
Electrical
Plug
14.8
Flue/Heat Exchanger
Thermostat Sensor
Flue/Heat Exchanger Thermostat Sensor
(Fig. 87)
1. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
2. Turn the sensor 90° anticlockwise to remove - it is a
bayonet connection.
3. Reassemble in reverse order.
Fig. 87
14.9
Water Pressure Sensor (Fig. 89)
1. Drain the primary circuit.
2. Disconnect the two wires from the sensor.
3. Undo the nut on the flow pipe securing and sealing the
sensor.
4. Remove the sensor, examine the sealing washer, replacing if
necessary.
5. Reassemble in reverse order. The component is not
polarised - either wire will fit each terminal.
14.10
Flow Pipe
Central Heating
Temperature Sensor
Central Heating Temperature Sensor (NTC)
(Fig. 88)
1. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
2. Unscrew the sensor from it’s pocket and reassemble in
reverse order. The plug will only fit one way.
14.11
Safety Thermostat (Fig. 88)
1. Pull the plug off the thermostat.
Safety Thermostat
2. Remove the screws securing the thermostat to the
mounting plate on the flow pipe.
3. Reassemble in reverse order, ensuring that the plug is
pushed fully on.
Fig. 88
14.12
DHW Temperature Sensor (NTC) (Fig. 89)
1. Turn off the mains cold water supply tap and draw off the
residual domestic hot water.
Pressure Sensor
Plate Heat
Exchanger
2. Ease the retaining tab on the sensor away and disconnect
the electrical plug.
3. Unscrew the sensor from the plate heat exchanger
manifold. Examine the sealing washer,replacing if necessary.
Fig. 89
© Baxi Heating UK Ltd 2008
DHW Temperature
Sensor
4. Reassemble in reverse order. The plug will only fit one way.
43
14.0 Changing Components
Heat Exchanger
Air Vent
14.11
Heat Exchanger Automatic Air Vent (Fig. 90)
1. Drain the boiler primary circuit and unscrew the
automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it
to the new automatic air vent.
Grommet
3. Reassemble in reverse order, transferring the grommet to
the new vent.
4. Ensure that the grommet is is sealed correctly to the
boiler top panel.
Fig. 90
14.12
Pump - Head Only (Fig. 91)
1. Drain the boiler primary circuit and remove the socket
head screws securing the pump head to the body and draw
the head away.
Pump Wiring
Cover
2. Undo the screw on the pump wiring cover and remove
the cover. Using a suitable flat bladed screw driver press the
cable securing levers downwards to release each wire after
noting their position.
Pump Body
3. A standard replacement Grundfos 15-60 head can now
be fitted. Connect the pump wiring to the new head. The
pump speed must be set to 3 (Fig. 92).
4. Reassemble in reverse order.
Socket Headed
Screw
14.13
Pump - Complete (Fig. 93)
1. Drain the boiler primary circuit.
Pump Head
2. Undo the two screws securing the body to the pipe and
manifold and draw the pump forwards.
Fig. 91
3. Undo the screw on the pump wiring cover and remove
the cover. Using a suitable flat bladed screw driver press the
cable securing levers downwards to release each wire after
noting their position.
Pump Setting
Fig. 92
4. Unscrew the automatic air vent from the pump body.
Automatic Air
Vent
5. Connect the wiring to the new pump. Examine the ‘O’
ring seals on the return pipe and manifold, replacing if
necessary.
Pump Wiring
Cover
6. Fit the air vent to the pump body and reassemble in
reverse order.
14.14
Automatic Air Vent (Fig. 93)
1. Drain the boiler primary circuit and unscrew the
automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary, and fit it
to the new automatic air vent.
Fig. 93
3. Reassemble in reverse order.
44
© Baxi Heating UK Ltd 2008
14.0 Changing Components
14.15
Gauge Retaining
Bracket
Pressure Gauge (Figs. 94 & 95)
1. Drain the boiler primary circuit and undo the nut on the
pressure gauge capillary.
2. Undo the screws securing the gauge retaining bracket.
Pressure Gauge
Fig. 94
3. Remove the bracket and gauge assembly. Depress the
barbs on the side of the gauge and remove the retaining
bracket.
4. Examine the sealing washer, replace if necessary.
5. Reassemble in reverse order.
14.16
Hall Effect Sensor (Fig. 96)
1. Ease the sensor upwards off the hydraulic inlet manifold
assembly.
2. Disconnect the electrical plug from the sensor.
Fig. 95
Pressure Gauge
Capillary
Hall Effect
Sensor
3. Connect the plug to the new sensor. Carefully fit the new
sensor to the hydraulic assembly, ensuring it is fully down.
14.17
Pressure Relief Valve (Fig. 97)
1. Drain the boiler primary circuit.
2. Disconnect the discharge pipe from the valve. Using a
suitable hexagon key undo the grub screw sufficiently to
release the valve.
3. Note the orientation of the valve, rotate it and withdraw
it from the manifold.
Hydraulic Inlet
Assembly
4. Fit the new valve and ‘O’ ring seal and set to the
previously noted orientation. Reassemble in reverse order.
Fig. 96
‘O’ ring seal
Grub Screw
Pressure Relief Valve
Fig. 97
Discharge Pipe
© Baxi Heating UK Ltd 2008
45
14.0 Changing Components
14.18
Plate Heat Exchanger (Fig. 98)
1. Drain the boiler primary circuit and remove the gas valve
as described in section 13.22.
Plate Heat Exchanger
2. While supporting the heat exchanger undo the screws
securing it to the brass manifolds.
3. Withdraw the heat exchanger upwards, taking care not to
damage any wires or controls.
Seals
4. There are four rubber seals between the manifolds and
heat exchanger which may need replacement.
LH Location Stud
Fig. 98
5. Ease the seals out of the manifold. Replace carefully,
ensuring that when the seal is inserted into the manifold it is
parallel and pushed fully in.
Rubber Seal
6. When fitting the new heat exchanger note that the left
hand location stud is offset towards the centre more than the
right hand one.
7. Reassemble in reverse order.
14.19
Diverter Valve - Motor Unit & Assembly
(Figs. 99 & 100)
1. To replace the motor unit, disconnect the multi-pin plug.
2. Pull off the retaining clip and remove the motor unit.
Motor Unit
3. The motor unit can now be replaced, or the valve
assembly removed.
Multi-pin Plug
4. Drain the primary circuit and draw off any hot water once
the isolating taps are closed.
Retaining Clip
5. Remove the spring clip retaining the bypass pipe to the
rear of the assembly and under the flow pipe nut at the left
hand side.
Valve
Assembly
6. Undo the nuts on the tap rail under the boiler. Remove
the screws securing the valve assembly to the boiler bottom
panel and plate heat exchanger.
Fig. 99
7. Remove the valve assembly. Examine any seals or washers,
replacing if necessary. Transfer the DHW NTC to the new
valve and reassemble in reverse order.
Pressure Sensor
Bypass Pipe
Spring Clip
Securing Screw
46
© Baxi Heating UK Ltd 2008
Fig. 100
14.0 Changing Components
14.20
P.C.B. (Fig. 102)
1. Note the settings of the temperature control knobs,
rotate them fully anticlockwise and carefully pull them off
the drive pins.
2. Completely undo the screws securing the control box
cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 101).
3. Note the position of all plugs and wires on the P.C.B. and
disconnect them.
4. Undo the securing screws and remove the P.C.B. Transfer
the control knob drive pins to the new P.C.B. and turn them
fully anticlockwise.
Control Box Cover
Fig. 101
P.C.B.
5. Reassemble in reverse order, ensuring that the
temperature controllers are reset to their previous positions.
14.21
Selector
Switch
Selector Switch (Fig. 102)
1. Note the setting of the selector switch knob and carefully
pull it off the facia.
Drive Pins
2. Completely undo the screws securing the control box
cover and release the cover retaining barbs from their slots.
Disengage the rear of the cover from the control box hinge
pin (Fig. 101).
3. Note the position of the electrical connections and the
orientation of the switch. Remove the electrical connections.
4. Remove the screws securing the switch to the facia panel.
Facia
5. Fit the new switch, ensuring that it is correctly positioned
and reassemble in reverse order.
Selector Switch Knob
Temperature Control Knobs
Fig. 102
© Baxi Heating UK Ltd 2008
47
Venturi Inlet
Pipe
14.0 Changing Components
Outlet Adaptor
14.23
Gas Valve (Fig. 103)
IMPORTANT: After replacing the valve the CO2 must be
checked and adjusted as detailed in Section 15.0
Combustion Check. Only change the valve if a suitable
calibrated combustion analyser is available.
Gas Valve
Sensing Pipe
1. Turn the gas cock off and undo the nut on the gas feed
elbow under the boiler.
Ignition Lead
2. Remove the screws securing the inlet pipe flange to the
boiler bottom panel.
3. Pull off the earth lead and sensing pipe.
4. Undo the nut on the venturi inlet pipe and slacken the nut
on the venturi. Ease the pipe aside and remove the gas valve.
Valve
Inlet Pipe
5. Remove the outlet adaptor and inlet pipe and transfer them
to the new valve. Examine the ‘O’ ring seals, replace if
necessary.
Gas Feed
Elbow
Fig. 103
6. Reassemble in reverse order.
Gas/Air
Adjustment Screw
NOTE: To assist the boiler to light prior to final setting,
use a suitable hexagon key to wind out the Gas/Air
adjustment screw until it is flush with the valve body, then
turn the screw 4 full turns clockwise (Fig. 103a). If the
boiler will not light, or the correct CO2 cannot be achieved
contact the ‘heateam’ technical helpline.
14.24
Fig. 103a
Expansion Vessel (Fig. 104)
1. Drain the primary circuit and undo the nut on the vessel
connection pipe.
2. Undo and remove the locknut securing the vessel spigot to
the boiler air box.
Retaining Bracket
3. Remove the bracket and vessel from the boiler.
Expansion Vessel
4. Locate the retaining bracket on the upper flange of the
vessel and fit to the boiler.
5. Reassemble in reverse order.
Lock Nut
Boiler Chassis
Fig. 104
48
© Baxi Heating UK Ltd 2008
15.0 Combustion Check
x2
15.1
Checking the CO2
IMPORTANT: The CO2 must only be checked and
adjusted if a suitable calibrated combustion analyser is
available.
1. The combustion (CO2) may be checked using a suitably
calibrated analyser after running the boiler for several
minutes.
Central Heating
Temperature Control
Selector Switch
2. To do this it is necessary to set the boiler to ‘Calibration
Mode’.
Domestic Hot Water
Temperature Control
Fig. 105
Display
3. Ensure that all external controls are calling for heat. The
actual current boiler temperature is shown on the display.
2
1
12
11
3
7
10
9
0
3
2
1
12
11
Central Heating
Temperature Control
4. Turn both temperature control knobs fully anticlockwise,
then quickly turn the DHW temperature knob 1/4 clockwise
twice and back fully anticlockwise (Fig. 105).
4
bar
5
4
0
AM
8
3
7
1
8
PM
9
5
10
4
2
Reset
5. The display will now alternate between ‘SF’ and the
current boiler temperature and both green LEDs will flash
(Figs. 106 & 107).
Domestic Hot Water
Temperature Control
6. Turn the CH temperature knob fully clockwise. As the
knob is turned the display will change, indicating the fan
speed.
7. The display will show ‘00’, indicating maximum rate, then
revert to ‘P ‘ alternating with the current boiler temperature
(Figs 108, 109 & 110).
Fig. 107
Fig. 106
8. Remove the plug from the flue adaptor test point. Insert
the analyser probe and allow time for the reading to settle
(Fig. 111).
The CO2 should be 8.7% ± 0.2
Fig. 109
Fig. 108
Fig. 110
Flue Adaptor Test
Point
Plug
10. The CO2 must then be checked at minimum rate. Turn
the CH temperature knob fully anticlockwise. As the knob is
turned the display will change, indicating the fan speed.
When the display reads ‘ 0’ the boiler runs at minimum rate.
The CO2 should be 8.4% ± 0.2.
Analyser Probe
Fig. 111
Min Rate
Adjustment Screw
(cap fitted)
Max Rate
Adjustment Screw
(cover removed)
11. With the boiler on minimum, the ‘Min. Rate’ adjustment
screw must be altered, using a suitable hexagon key, after
removing the cap (Fig. 112). If the CO2 is reset at either
boiler rate it must be rechecked at the other rate and also
adjusted if required.
Gas Valve
Fig. 112
© Baxi Heating UK Ltd 2008
9. It is possible to alter the CO2 by adjustment of the gas
valve. Remove the plastic cover from the ‘Max Rate’
adjustment screw. At maximum rate the ‘Max. Rate’
adjustment screw should be turned, using a suitable
hexagon key, until the correct reading is obtained (Fig. 112).
Turning clockwise will reduce the CO2. Anticlockwise will
increase the CO2.
12. The ‘Calibration Function’ is maintained for 20 minutes
unless the maximum CH temperature is exceeded. The
function can be disabled at any time by turning the DHW
knob.
49
16.0 Electrical
16.1
Central Heating
NTC Sensor
DHW
NTC Sensor
Illustrated Wiring Diagram
b
b
Overheat Stat
Hall Effect
Sensor
b
r
Water Pressure
Switch
b
r
Flue Sensor
1
4
2
g
br
r
5
b
w
b
g
g
bk
Fan
3
1
2
b
b
b
g/y
br
X400
1
X401
9 87 6 5 4 3 2 1
2
3
4
10 9 8 7 6 5 4 3 2 1
4
3
bk
b
X9
X501
bk
br
2
Control PCB
1
Timer
1
2
1
X1
2
3
4
1
5
X2
2
3
5
4
6
7
8
9
r
bk
X3
b
br
Flame
Sensing
Electrode
br
br
br
b
b
b
Pump
w
bk
b
br
b
r
br
w
r
L
Spark
Generator
N
b
bk
b
a
Diverter Valve
br
bk
g
w
br
Gas Valve
b
Link
g/y
Ignition
Electrode
b
bk
br
r
Mains Input Cable
br
bk
b
w
50
© Baxi Heating UK Ltd 2008
- brown
- black
- blue
- white
g
- green
g/y - green / yellow
r
- red
17.0 Short Parts List
Short Parts List
426
306
315
316
311
422
400
415
503
© Baxi Heating UK Ltd 2008
Description
Manufacturers
Part No.
326
Fan
5121447
426
Motor 3way Valve
248733
315
Igniter Electrode
5114702
316
Sensing Electrode
5114703
422
Gas Valve
5119647
404
Hall Effect Sensor
5114767
313
Burner 24
5122149
Burner 28
5114697
Burner 33
5114698
419
Water Pressure Switch
5114748
400
Plate Heat Exchanger 24
248048
Plate Heat Exchanger 28/33
5114708
415
Pump
248042
421
NTC Sensor
5114725
420
Overheat Thermostat
5114729
504
Pressure Gauge
248090
503
421
G.C.
No.
419
624
302
Key
No.
PCB 24
5121862
PCB 28
5120218
PCB 33
5120219
420
504
51
18.0 Fault Finding
18.1
NOTE: When instructed to turn the
selector to the reset position turn the
selector switch fully anticlockwise against
the spring pressure to the reset position
and hold for 5 seconds to reset the
boiler.
Initial Fault Finding Checks
1. Check that gas, water and electrical supplies are available
at the boiler.
2. Electrical supply = 230V ~ 50 Hz.
3. CH water system pressurised to 0.5 bar minimum when
the boiler is cold.
4. The preferred minimum gas pressure is 20 mbar.
5. Carry out electrical system checks, i.e. Earth Continuity,
Resistance to Earth, Short Circuit and Polarity with a suitable
meter.
NOTE: These checks must be repeated after any
servicing or fault finding.
6. Ensure all external controls are calling for heat and check
all external and internal fuses. Before any servicing or
replacement of parts, ensure the gas and electrical supplies
are isolated.
18.2
Error Codes
1. If a fault occurs on the boiler an error code may be shown
by the facia display.
Table Of Error Codes
E20
E28
E50
E110
E119
E125
E130
E133
E160
E193
Central Heating NTC Fault
Flue NTC Fault
Hot Water NTC Fault
Safety Thermostat Operated
Water Pressure Switch Not Operated
Circulation Fault (Primary Circuit)
Flue NTC Operated
Interruption Of Gas Supply or Flame Failure
Fan or Fan Wiring Fault
Pre-Circulation Fault
2. The codes are either two or three digit, preceded by the
letter 'E'. For example, code E133 will be displayed by 'E1'
alternating with '33'. E50 is shown as 'E' then '50'
E20, E28 & E50 indicate faulty or incorrect components.
E110 shows overheat of the primary water and E130
overheat of the flue system.
E119 is displayed when the primary water pressure is less
than 0.5 bar.
E133 indicates that the gas supply has been interrupted,
ignition has failed or the flame has not been detected.
E125 is displayed in either of two situations:i) If within 15 seconds of the burner lighting the boiler
temperature has not changed by 1°.
ii) If within 10 minutes of the burner lighting the boiler
temperature twice exceeds the selected temperature by 30°.
In these instances poor primary circulation is indicated.
3. By turning the selector switch to the 'Reset' position for a
minimum of 5 seconds when E110, E130 & E133 are
displayed it is possible to relight the boiler.
4. If this does not have any effect, or the codes are displayed
regularly further investigation is required.
52
© Baxi Heating UK Ltd 2008
18.0 Fault Finding
Refer to Section 16.0 “Illustrated Wiring Diagram” for position of terminals and components
Central Heating - Follow operational sequence (do
Turn selector switch to
The display illuminates
NO
Go to section ‘A’
YES
Error 110 flashing
Error 130 flashing
Error 133 flashing
YES
Turn the selector switch to
reset position for 5 seconds
YES
If the error 110 is still flashing.
Go to section ‘J’
NO
Error 20, 28 or 50 flashing
YES
Go to section ‘E’
NO
YES
Error 119 flashing
Go to section ‘C’
Ensure controls are set to
demand and verify the
contacts are closed
NO
NO
Turn Central Heating
thermostat to Maximum.
Pump runs
NO
Ensure all controls (and
integral clock if fitted) are
calling for heat
YES
Go to section ‘B’
YES
Error 125 or 193 flashing
YES
Ensure that primary
circulation is OK & that
there is no blockage
NO
3-way valve is open to Central
Heating circuit
NO
Go to section ‘K’
YES
Fan runs
NO
Error 160 flashing
Go to section ‘D’
NO
Error 160 flashing
Go to section ‘L’
YES
Fan runs at correct speed
YES
Spark at ignition electrodes for
up to 5 seconds and for 3
attempts
YES
NO
Error 133 flashing
YES
Go to section ‘H’
Turn the selector switch to
reset
Go to section ‘F’
NO
YES
Burner lights
Burner does not stay alights
after 5 seconds
YES
Error 133 flashing
Go to section ‘I’
YES
Pump continues to run for 3
minutes
(room thermostat open)
Check the Central Heating
NTC sensor
Go to section ‘E’
YES
NO
Burner output modulates to
maintain the temperature set
Error 130 flashing
Go to section ‘M’
YES
Burner goes out
© Baxi Heating UK Ltd 2008
YES
Fan stops after 10 seconds
YES
Operation sequence
successful
53
18.0 Fault Finding
Domestic Hot Water - Follow operational sequence
Turn selector switch to
The display illuminates
NO
Go to section ‘A’
YES
Error 110 flashing
Error 133 flashing
YES
Turn the selector switch to
reset position for 5 seconds
YES
If the error 110 is still flashing.
Go to section ‘J’
NO
YES
Error 20, 28 or 50 flashing
Go to section ‘E’
NO
YES
Error 119 flashing
Go to section ‘C’
Go to section ‘B’
NO
Turn Domestic Hot Water
thermostat to Maximum.
Open DHW tap fully.
DHW Hall Effect sensor
operated (red neon on the
sensor illuminated
YES
NO
DHW flow rate more than 2
l/min
YES
YES
NO
3-way valve is open to
Domestic Hot Water circuit
Is mains water filter and
assembly clean?
Is the magnetic detector free
to move in the Hall Effect
sensor
Go to section ‘K’
YES
Pump runs
NO
Error 125 flashing
Go to section ‘B’
NO
Error 160 flashing
Go to section ‘D’
NO
Error 160 flashing
Go to section ‘L’
YES
Fan runs
YES
Fan runs at correct speed
YES
Spark at ignition electrodes for
up to 5 seconds and for 3
attempts
YES
NO
Error 133 flashing
YES
Go to section ‘H’
Turn the selector switch to the
reset position for 5 seconds
Go to section ‘F’
NO
Burner lights
YES
Burner does not stay alights
after 5 seconds
YES
Error 133 flashing
Go to section ‘I’
NO
Reduce DHW flow rate
Burner modulates
NO
Clean DHW NTC sensor
and DHW heat exchanger
YES
Burner output modulates to
maintain the temperature set
YES
NO
Error 130 flashing
Go to section ‘M’
Close DHW tap
YES
DHW flow sensor senses no
flow. Burner goes out
54
© Baxi Heating UK Ltd 2008
YES
Fan stops after 10 seconds
YES
Pump runs for 30 seconds
YES
Operation sequence
successful
18.0 Fault Finding
Fault Finding Solutions Sections
A
Is there 230V at:
1.
Main terminals L and N
2.
Main terminal fuse
3.
B
NO
Check electrical supply
NO
Replace fuse
NO
Check wiring
PCB - X1 connector
terminals 1,2
NO
Display
illuminated
Replace PCB
Is there 230V at:
YES
1.
Pump
2.
PCB - X3 connector terminals 3 & 4
NO
If pump jammed, release
NO
Replace pump
Replace PCB
YES
Change pump supply cable
C
1.
YES
CH system pressure less than 0.5 bar
NO
2.
D
1.
Check the tap of the automatic air
vent is opened
Fan connections correct at fan. PCB X2 connector, is 230V AC across
terminals 5 & 7
Re-pressurise system
Check connection water pressure
switch terminal
COM - NO and PCB connector
X400 terminals 3,4
NO
YES
YES
Replace water
pressure switch
Open the automatic air vent
Fan jammed or faulty winding
YES
Replace fan
NO
Replace PCB
© Baxi Heating UK Ltd 2008
55
18.0 Fault Finding
E
E20 or E50 - Temperature sensors faulty.
Cold resistance approximately
10kΩ @ 25° C (DHW and CH sensors)
20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)
NO
Replace sensor or PCB (E28)
E28 - Incorrect PCB fitted
F
1.
2.
Check and correct the connection of the
tube between the venturi and gas valve
Gas at burner
NO
Ensure gas is on and purged
PCB - X3 connector is 230V AC across
terminals 1 & 2
YES
Replace gas valve
NO
Replace PCB
G
1.
Ensure that the Hall Effect Sensor is in position.
Check the connection between the PCB - X400
connector terminals 3,6,7 and the electronic sensor
YES
Check the voltage between red wire and blue
wire is more than 5V DC
YES
NO
Replace PCB
H
Check and correct if necessary
1. Ignition electrode and lead
2. Electrode connection
3. Spark gap and position
YES
Voltage at PCB - X2 connector is at
least 100V DC across terminals 2 & 5
(Note: from multimeter connect
‘common’ to 2 & ‘volts’ to 5).
Check wiring
Replace Hall
Effect Sensor
NO
YES
Burner
Viewing Window
7.5 ± 1
4 ± 0.5
Electrode Position
56
© Baxi Heating UK Ltd 2008
10 ± 1
Replace PCB
Replace igniter
18.0 Fault Finding
I
1.
2.
Check the gas supply pressure:
For Natural Gas greater than
10 - 11 mbar
Check and correct if necessary
1. The mechanical set of the gas valve
(CO2 values - see instruction)
2. Flame sensing electrode and lead connections
3. Flame sensing electrode position
YES
Flame current should be more than 0.5 μA
J
1.
Overheat thermostat operated or
faulty, i.e. continuity across
thermostat terminals
NO
NO
Replace PCB
Replace flame sensing electrode
Allow to cool. Continuity
across thermostat terminals
more than 1.5 ohm
YES
Replace safety thermostat
YES
Replace PCB
K
Is there 230V at:
1.
2.
Motor 3-way valve
YES
PCB - X3 connector terminals
5 & 6 central heating mode
5 & 7 domestic hot water mode
Replace motor 3-way valve
NO
Replace PCB
YES
Change pump supply cable
L
1.
M
1.
2.
Fan connections correct at fan.
PCB - X401 connector terminals 5,6,7 & 8
Temperature sensors faulty.
Cold resistance approximately
10kΩ @ 25° C (CH sensor)
20kΩ @ 25° C (Flue sensor)
(resistance reduces with increase in temp.)
If pump is running the heat exchanger could be
obstructed
© Baxi Heating UK Ltd 2008
YES
NO
YES
Replace fan
Replace sensor
Replace heat exchanger
57
BENCHMARK
No. 5 1 1 6 2 8 2
1.0 Introduction
GAS BOILER COMMISSIONING CHECKLIST
COLLECTIVE MARK
BOILER SERIAL No.
NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING
ROOM T/STAT & PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
CYLINDER T/STAT & PROGRAMMER/TIMER
COMBI BOILER
HEATING ZONE VALVES
FITTED
NOT REQUIRED
HOT WATER ZONE VALVES
FITTED
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
FITTED
AUTOMATIC BYPASS TO SYSTEM
FITTED
TIME & TEMPERATURE CONTROL TO HOT WATER
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE
m3/hr
ft3/hr
BURNER OPERATING PRESSURE (IF APPLICABLE)
N/A
mbar
CENTRAL HEATING FLOW TEMPERATURE
°C
CENTRAL HEATING RETURN TEMPERATURE
°C
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED?
YES
NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE
m3/hr
N/A
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
ft3/hr
mbar
COLD WATER INLET TEMPERATURE
°C
HOT WATER OUTLET TEMPERATURE
°C
WATER FLOW RATE
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING?
N/A
YES
CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
COMMISSIONING ENG’S NAME PRINT
1
58
© Baxi Heating UK Ltd 2008
SIGN
CORGI ID No.
DATE
1
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1 DATE
SERVICE 2 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 3 DATE
SERVICE 4 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 5 DATE
SERVICE 6 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 7 DATE
SERVICE 8 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 9 DATE
SERVICE 10 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
59
All descriptions and illustrations provided in this leaflet have been carefully
prepared but we reserve the right to make changes and improvements in
our products which may affect the accuracy of the information contained in
this leaflet. All goods are sold subject to our standard Conditions of Sale
which are available on request.
P O T T E RTON
A Tr a din g D i v i s i on of B a x i Heat i ng U K Lt d ( 3879156)
A D ivis io n of B a x i Gro u p
Brooks House, Coventry Road, Warwick. CV34 4LL
After Sales Service 08706 017 017 Technical Enquiries 08706 049 049
Website www.potterton.co.uk
e&oe
IT Comp No 925.659.2
UK Comp No 5116282 - Iss 7 - 4/08

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement