Extinguishant Control Panel Features Product Overview


Add to my manuals
2 Pages

advertisement

Extinguishant Control Panel Features Product Overview | Manualzz

Sigma

XT

Extinguishant

Control Panel

Sigma XT is a new generation extinguishant releasing panel which is fully compliant with

European standard BS

EN12094-1.

(Fixed firefighting systems

– components for gas extinguishing systems).

The simple, programmable configuration options and easy to install construction make Sigma XT panels the ideal choice for small to medium sized systems using all extinguishant agents.

Programmable

Functions

Access Level 2

Test Zones 1 to 3

Disable Zones 1 to 3

Disable 1st Stage Alarms

Disable Pre-activated 1st Stage Relay

Disable Pre-activated 2nd Stage Relay

Disable Extract Fan Output

Disable Manual Release Input

Disable Extinguishant Sub System

Activate Extract Fan Output

Activate Alarm Delays

Access Level 3

Sounder Delay

Coincidence Detection

Disable Panel Features

Zone Alarm Delays (Detectors)

Zone Alarm Delay (Call Points)

Configure Zone for I.S Barrier Use

Zone Short Circuit Alarm

Zone Non Latching

Zone Inputs Delay

Extinguishant Release Time Delay

Extinguishant Release Duration Timer

Extinguishant Reset Delay Timer

Page 48

BS EN12094-1

KM 96761

Model No. K11031M2

Features

Complies with EN12094-1

Three detection zones as standard

Any single zone or any combinations of zones can be configured to release

Configurable first stage sounder delays

Configurable detection delays

Zero time delay upon manual release option

Compatible with I.S. barriers

Non-latching zone input option to receive signals from other systems such as aspirating equipment

Configurable extinguishant delays up to 60 seconds in 5 second steps

Configurable extinguishant duration up to 5 minutes in 5 second steps

Countdown timer shows time remaining until release

Supports up to seven, four wire status indicators

Built in Extract Fan control

Product Overview

Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma

XT extinguishant releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.

With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.

The extensive configuration options of the Sigma

XT allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-1).

The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety.

The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.

With all of the electronics mounted on a single, easily removable, steel plate Sigma XT panels are both robust and easy to install.

Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range.

1st Stage

Sounders

10K 10K

2nd Stage

Sounders

10K

Specifications

DS40.04.2008

Remote

Control

Inputs

To Status

Units

S

O

L

Auxiliary Signalling Relays

S

S

S

S

S

S

S

S

E R0V SIL AL FLT

AUX

24V

REMOTE

RST

CONTROL

DATA POWER

STATUS UNITS

S1 S2 ZONE 1 ZONE 2 ZONE 3 2ND

SOUNDER

NC C

1ST

STAGE

NO NC C NO

2ND

STAGE

MODE

SELECT

MAN.

RELEASE

HOLD

NO C

REL

PRESS.

SWITCH

EXTING.

LOW

PRES.

EXTRACT

SWITCH

NC C

FAULT

RELAY

NO NC C

LOCAL

FIRE

NO NC C

FIRE

RELAY

NO

Sigma XT PCB

Panels Technical

Product

Code

K11031M2

K11031F2

Description

Surface mounting panel

Flush mounting panel *

Size

(mm)

385 x 310 x 90

415 x 315 x 86

Compatible Status & Hold Off Units

K911000M8

K911000F8

K911100M8

K911100F8

K911110M8

K911110F8

K911113M8

K911113F8

K91000M10

6 lamp unit (surface)

6 lamp unit (flush)

6 lamp unit c/w mode select (surface)

6 lamp unit c/w mode select

6 lamp unit c/w mode select and manual release

(flush)

(surface)

6 lamp unit c/w mode select and manual release

(flush)

10 lamp unit c/w mode select (surface) and manual release

10 lamp unit c/w mode select and manual release

(flush)

Extinguishant hold off switch (surface)

W911000W8

W911100W8

W911110W8

W911113W8

IP65 - 6 lamp unit (surface)

IP65 - 6 lamp unit c/w mode select (surface)

IP65 - 6 lamp unit c/w mode select (surface) and manual release

IP65 - 10 lamp unit c/w mode select (surface) and manual release

Tamper resistant Vision Window **

K18002

* Flush version not Kitemark Appoved

** Vision Window can be easily retrofitted to any Sigma XT panel

Mains supply

Mains supply fuse

Power supply rating

Maximum ripple current

Battery type (Yuasa NP)

Battery charge voltage

Battery charge current

Battery fuse

Maximum current draw from batteries

Quiescent current of panel in mains fail

R0V output

Sounder outputs

Fault relay contact rating

Fire relay contact rating

Local fire relay contact rating

First stage contact rating

Second stage contact rating

Extract contact rating

Zone quiescent current

Terminal capacity

Number of detectors per zone

Number of sounders per circuit

Detection circuit end of line

Monitored input end of line

Sounder circuit end of line

Extinguishant output end of line

No. of detection circuits

No. of sounder circuits

Extinguishant release output

Extinguishant release delay

Extinguishant release duration

SIL, AL, FLT, RST inputs

Zone normal threshold

Detector alarm threshold

Call point alarm threshold

Short circuit threshold

Head removal condition

Cabling

Monitored inputs normal threshold

Monitored inputs alarm threshold

Monitored inputs Short circuit threshold

Status unit/Ancillary board connection

Status unit power output

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

230V AC +10%/-15% (100 Watts maximum)

1.6 Amp (F1.6A L250V)

3 Amps total including battery charge 28V +/- 2V

200 millivolts

Two 12 Volt 7Ah sealed lead acid in series

27.6VDC nominal (temperature compensated)

0.7A maximum

20mm, 3.15A glass

3 Amps

0.095A

Fused at 500mA with electronic fuse

24V Fused at 500mA with electronic fuse

30VDC 1A Amp maximum

30VDC 1A Amp maximum

30VDC 1A Amp maximum

30VDC 1A Amp maximum

30VDC 1A Amp maximum

30VDC 1A Amp maximum

2mA maximum

0.5mm

² to 2.5mm

² solid or stranded wire

Dependent on type (maximum 32)

Dependent on type (max. 0.5A per sounder circuit)

6K8 5% ½ Watt resistor

6K8 5% ½ Watt resistor

10K 5% ¼ Watt resistor

1N4004 Diode

3

2 x 1st Stage, 1 x 2nd Stage

Fused at 1 Amp

Adjustable 0 to 60 seconds (in 5 second steps)

Adjustable 60 to 300 seconds (in 5 second steps)

Switched -ve, max resistance 100 Ohms

8K ohms to 1K ohm

999 ohms to 400 ohms

399 ohms to 100 ohms

99 ohms to 0 ohms

15.5 to 17.5 volts

FP200 or equivalent

8K ohms to 1K ohm

999 ohms to 100 ohms

99 ohms to 0 ohms

Two wire RS485 connection

Fused at 500mA with electronic fuse

The manufacturer reserves the right to amend specifications without prior notice