Sigma
XT
Extinguishant
Control Panel
Sigma XT is a new generation extinguishant releasing panel which is fully compliant with
European standard BS
EN12094-1.
(Fixed firefighting systems
– components for gas extinguishing systems).
The simple, programmable configuration options and easy to install construction make Sigma XT panels the ideal choice for small to medium sized systems using all extinguishant agents.
Programmable
Functions
Access Level 2
Test Zones 1 to 3
Disable Zones 1 to 3
Disable 1st Stage Alarms
Disable Pre-activated 1st Stage Relay
Disable Pre-activated 2nd Stage Relay
Disable Extract Fan Output
Disable Manual Release Input
Disable Extinguishant Sub System
Activate Extract Fan Output
Activate Alarm Delays
Access Level 3
Sounder Delay
Coincidence Detection
Disable Panel Features
Zone Alarm Delays (Detectors)
Zone Alarm Delay (Call Points)
Configure Zone for I.S Barrier Use
Zone Short Circuit Alarm
Zone Non Latching
Zone Inputs Delay
Extinguishant Release Time Delay
Extinguishant Release Duration Timer
Extinguishant Reset Delay Timer
Page 48
BS EN12094-1
KM 96761
Model No. K11031M2
Features
Complies with EN12094-1
Three detection zones as standard
Any single zone or any combinations of zones can be configured to release
Configurable first stage sounder delays
Configurable detection delays
Zero time delay upon manual release option
Compatible with I.S. barriers
Non-latching zone input option to receive signals from other systems such as aspirating equipment
Configurable extinguishant delays up to 60 seconds in 5 second steps
Configurable extinguishant duration up to 5 minutes in 5 second steps
Countdown timer shows time remaining until release
Supports up to seven, four wire status indicators
Built in Extract Fan control
Product Overview
Designed and manufactured to the highest standards in a quality controlled environment and with European EN12094-1 approvals, the Sigma
XT extinguishant releasing panel offers outstanding value and performance for all small to medium fixed firefighting installations.
With three detection zones as standard, extinguishant release can be configured to activate from any combination of detection zone inputs to allow (among other combinations) any two from three type activations such as would be required for detection in ceiling void, room and floor void applications.
The extensive configuration options of the Sigma
XT allow the functionality of the system to be extensively modified while still complying with the requirements of the controlling standard for the equipment (EN12094-1).
The panel contains a large LED display to enable easy configuration and control which also displays the time remaining until extinguishant release for added user safety.
The countdown timer is duplicated on up to seven remote status units to provide local indication of the extinguishant system status.
With all of the electronics mounted on a single, easily removable, steel plate Sigma XT panels are both robust and easy to install.
Sigma XT is supplied in an enclosure that matches the design and colour of the Sigma CP range.
1st Stage
Sounders
10K 10K
2nd Stage
Sounders
10K
Specifications
DS40.04.2008
Remote
Control
Inputs
To Status
Units
S
O
L
Auxiliary Signalling Relays
S
S
S
S
S
S
S
S
E R0V SIL AL FLT
AUX
24V
REMOTE
RST
CONTROL
DATA POWER
STATUS UNITS
S1 S2 ZONE 1 ZONE 2 ZONE 3 2ND
SOUNDER
NC C
1ST
STAGE
NO NC C NO
2ND
STAGE
MODE
SELECT
MAN.
RELEASE
HOLD
NO C
REL
PRESS.
SWITCH
EXTING.
LOW
PRES.
EXTRACT
SWITCH
NC C
FAULT
RELAY
NO NC C
LOCAL
FIRE
NO NC C
FIRE
RELAY
NO
Sigma XT PCB
Panels Technical
Product
Code
K11031M2
K11031F2
Description
Surface mounting panel
Flush mounting panel *
Size
(mm)
385 x 310 x 90
415 x 315 x 86
Compatible Status & Hold Off Units
K911000M8
K911000F8
K911100M8
K911100F8
K911110M8
K911110F8
K911113M8
K911113F8
K91000M10
6 lamp unit (surface)
6 lamp unit (flush)
6 lamp unit c/w mode select (surface)
6 lamp unit c/w mode select
6 lamp unit c/w mode select and manual release
(flush)
(surface)
6 lamp unit c/w mode select and manual release
(flush)
10 lamp unit c/w mode select (surface) and manual release
10 lamp unit c/w mode select and manual release
(flush)
Extinguishant hold off switch (surface)
W911000W8
W911100W8
W911110W8
W911113W8
IP65 - 6 lamp unit (surface)
IP65 - 6 lamp unit c/w mode select (surface)
IP65 - 6 lamp unit c/w mode select (surface) and manual release
IP65 - 10 lamp unit c/w mode select (surface) and manual release
Tamper resistant Vision Window **
K18002
* Flush version not Kitemark Appoved
** Vision Window can be easily retrofitted to any Sigma XT panel
Mains supply
Mains supply fuse
Power supply rating
Maximum ripple current
Battery type (Yuasa NP)
Battery charge voltage
Battery charge current
Battery fuse
Maximum current draw from batteries
Quiescent current of panel in mains fail
R0V output
Sounder outputs
Fault relay contact rating
Fire relay contact rating
Local fire relay contact rating
First stage contact rating
Second stage contact rating
Extract contact rating
Zone quiescent current
Terminal capacity
Number of detectors per zone
Number of sounders per circuit
Detection circuit end of line
Monitored input end of line
Sounder circuit end of line
Extinguishant output end of line
No. of detection circuits
No. of sounder circuits
Extinguishant release output
Extinguishant release delay
Extinguishant release duration
SIL, AL, FLT, RST inputs
Zone normal threshold
Detector alarm threshold
Call point alarm threshold
Short circuit threshold
Head removal condition
Cabling
Monitored inputs normal threshold
Monitored inputs alarm threshold
Monitored inputs Short circuit threshold
Status unit/Ancillary board connection
Status unit power output
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
230V AC +10%/-15% (100 Watts maximum)
1.6 Amp (F1.6A L250V)
3 Amps total including battery charge 28V +/- 2V
200 millivolts
Two 12 Volt 7Ah sealed lead acid in series
27.6VDC nominal (temperature compensated)
0.7A maximum
20mm, 3.15A glass
3 Amps
0.095A
Fused at 500mA with electronic fuse
24V Fused at 500mA with electronic fuse
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
30VDC 1A Amp maximum
2mA maximum
0.5mm
² to 2.5mm
² solid or stranded wire
Dependent on type (maximum 32)
Dependent on type (max. 0.5A per sounder circuit)
6K8 5% ½ Watt resistor
6K8 5% ½ Watt resistor
10K 5% ¼ Watt resistor
1N4004 Diode
3
2 x 1st Stage, 1 x 2nd Stage
Fused at 1 Amp
Adjustable 0 to 60 seconds (in 5 second steps)
Adjustable 60 to 300 seconds (in 5 second steps)
Switched -ve, max resistance 100 Ohms
8K ohms to 1K ohm
999 ohms to 400 ohms
399 ohms to 100 ohms
99 ohms to 0 ohms
15.5 to 17.5 volts
FP200 or equivalent
8K ohms to 1K ohm
999 ohms to 100 ohms
99 ohms to 0 ohms
Two wire RS485 connection
Fused at 500mA with electronic fuse
The manufacturer reserves the right to amend specifications without prior notice