Satec C192PF8-RPR Installation and Operation Manual


Add to my manuals
75 Pages

advertisement

Satec C192PF8-RPR Installation and Operation Manual | Manualzz
C192PF8-RPR
Power Factor
Manager &
Reactive Power Regulator
Installation
and Operation
Manual
BG0347 Rev. A1
C192PF8-RPR
Power Factor Manager and
Reactive Power Regulator
Installation and Operation
Manual
LIMITED WARRANTY
The manufacturer offers the customer an 24-month functional warranty on the
instrument for faulty workmanship or parts from date of dispatch from the
distributor. In all cases, this warranty is valid for 36 months from the date of
production. This warranty is on a return to factory basis.
The manufacturer does not accept liability for any damage caused by instrument
malfunction. The manufacturer accepts no responsibility for the suitability of the
instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions
herein will void the warranty.
Your instrument may be opened only by a duly authorized representative of the
manufacturer. The unit should only be opened in a fully anti-static environment.
Failure to do so may damage the electronic components and will void the
warranty.
NOTE
The greatest care has been taken to manufacture and calibrate your instrument.
However, these instructions do not cover all possible contingencies that may
arise during installation, operation or maintenance, and all details and variations
of this equipment are not covered by these instructions.
For additional information regarding installation, operation or maintenance of this
instrument, contact the manufacturer or your local representative or distributor.
IMPORTANT
Please read the instructions this manual before performing installation, and
take note of the following precautions:
Ensure that all incoming AC power and other power sources are
turned OFF before performing any work on the instrument. Failure to
do so may result in serious or even fatal injury and/or equipment
damage.
Before connecting the instrument to the power source, check the labels on
the side of the instrument to ensure that your instrument is equipped with
the appropriate power supply voltage, input voltages, currents and
communication protocol for your application.
Under no circumstances should the instrument be connected to a
power source if it is damaged.
To prevent potential fire or shock hazard, do not expose the
instrument to rain or moisture.
i
The secondary of an external current transformer must never be allowed to
be open circuit when the primary is energized. An open circuit can cause
high voltages, possibly resulting in equipment damage, fire and even serious
or fatal injury. Ensure that the current transformer wiring is made through
shorting switches and is secured using an external strain relief to reduce
mechanical strain on the screw terminals, if necessary.
Setup procedures must be performed only by qualified personnel
familiar with the instrument and its associated electrical equipment.
DO NOT open the instrument under any circumstances.
Modbus is a trademark of Modicon, Inc.
Read this manual thoroughly before connecting the meter to the current
carrying circuits. During operation of the meter, hazardous voltages are
present on input terminals. Failure to observe precautions can result in
serious or even fatal injury or damage to equipment.
BG0347 Rev. A1
ii
Table of Contents
Chapter 1 Introduction....................................................................... 1
1.1
1.2
About This Manual .................................................................................... 1
About The C192PF8-RPR .......................................................................... 1
Chapter 2 Installation......................................................................... 7
2.1
2.2
Mechanical Installation ............................................................................. 7
Electrical Installation................................................................................. 8
Chapter 3 Using The Menus .............................................................. 18
Chapter 4 Setup Menus ..................................................................... 20
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
Basic Setup Menu...................................................................................... 20
Communications Port Setup Menu .......................................................... 22
Digital Input Setup Menu........................................................................... 23
Analog Output Setup Menu ...................................................................... 24
Pulsing Output Setup Menu...................................................................... 26
Alarm/Event Setpoints Setup Menu ......................................................... 27
Relay Operation Control Menu ................................................................. 32
Display Setup Menu................................................................................... 33
User Selectable Options Menu ................................................................. 34
Access Control Menu ................................................................................ 36
Reset/Synchronization Menu.................................................................... 37
Manual Relay Control Menu...................................................................... 38
PFC Setup Menu ........................................................................................ 39
PFC Manual Mode Menu............................................................................ 43
Chapter 5 PFC Setup and Operation ................................................ 44
5.1
5.2
5.3
Capacitor Bank Control Options .............................................................. 44
PFC Operation ........................................................................................... 45
Capacitor Banks Protection...................................................................... 52
Chapter 6 Data Display ...................................................................... 55
6.1
6.2
6.3
Navigating in the Display Mode................................................................ 55
Data Display Formats ................................................................................ 57
Device Diagnostics Display ...................................................................... 61
Chapter 7 Viewing Status Information ............................................. 63
7.1
7.2
The Status Information Menu ................................................................... 63
Status Display Formats............................................................................. 64
Appendix: Technical Specifications................................................. 66
iii
Chapter 1 Introduction
1.
1.1 About This Manual
This manual is intended for the user of the C192PF8-RPR Power Factor Manager
and Reactive Power Regulator. The C192PF8-RPR is a multi-function
microprocessor-based instrument used for power factor or reactive power
correction and for the measurement, monitoring, and management of electrical
parameters in low-voltage and mid-voltage power systems.
This chapter gives an overview of this manual and an introduction to the
C192PF8-RPR.
Chapter 2, Installation, provides instructions for mechanical and electrical
installation.
Chapter 3, Using the Menus, presents the structure of menus for setup and status
viewing.
Chapter 4, Setup Menus, provides instructions for performing parameter setup via
the front panel.
Chapter 5, PFC Setup and Operation, provides instructions for performing setup
for the Power Factor Controller (PFC) and describes front-panel operations in
PFC manual mode.
Chapter 6, Data Display, guides you through the display pages.
Chapter 7, Viewing Status Information, tells you how to access additional status
information on the instrument. This information may be useful during installation.
Technical Specifications for the C192PF8-RPR are found in the Appendix.
1.2 About The C192PF8-RPR
The C192PF8-RPR is a compact three-phase AC Powermeter with a built-in
Power Factor Controller (PFC) and Reactive Power Regulator (RPR), designed to
meet the requirements of users ranging from electrical panel builders to
substation operators. The C192PF8-RPR performs power factor or reactive
power correction functions, basic voltage, current, frequency, power, power factor
and energy measurements, plus total harmonic (THD, TDD, K-Factor)
measurements.
The C192PF8-RPR is suitable for mounting on 136×136 mm square cut-outs.
Features
Power Factor Controller
• Control of up to 8 capacitor banks
Chapter 1 Introduction
1
•
•
•
•
•
•
•
•
Manual, self-adapting automatic and optimizing automatic operation
Full four-quadrant operation
Selectable target power factor or reactive power setpoints
Two PFC setpoint ranges for day and night operations selectable via a
status input
Target power factor range from 0.5 (inductive) to -0.5 (capacitive)
True and displacement power factor setups
True and fundamental’s reactive power setups
Extensive capacitor banks protection via programmable alarm setpoints
(no-volt, over-voltage and high harmonics override conditions)
Display
The front panel features bright LED displays (three windows, up to 43 pages) with
adjustable display update time. Display auto scroll is available on the main screen
with a programmable scroll interval of 2 to 15 seconds. Automatic return to the
main screen is available after 30 seconds of uninterrupted use. The front panel
also includes:
• Relay status bar showing output status of the 8 relays
• Alarm/Manual Mode LED providing a local indication when a predefined
alarm condition appears (the LED is lit constantly) or when the PFC
operates in Manual Mode (the LED flashes). The alarm LED is shut off
manually (by pressing on both up and down keys for more than 5 sec)
• RXD/TXD LEDs showing communications receive/transmit status
Setup is menu driven, with optional password protection. 16 programmable
setups are provided for alarm and control functions (for programmable
parameters, see ‘Measured Parameters’ below).
Communications are available using an RS-232 or RS-485 standard (factory
set), with Modbus protocol. 120 user assignable registers are available in Modbus
protocols.
Eight relays are provided for capacitor banks switching, energy pulsing (KYZ) or
alarm and remote control. Contacts of six relays may switch loads up to 250V, 5A
AC and are recommended for alarm and remote control; contacts of two relays
may switch loads up to 250V, 3A AC and may be used for energy pulsing.
One optically isolated analog output is provided for remote monitoring or
control. Current loop options are 0-20 and 4-20 mA. The analog output must be
used with an external power supply.
Four common-use event/time counters are provided for counting user-defined
events or their duration. These can be used for counting total operation time of
generators or overload time of transformers or power lines. The counters are
operated and released by user-defined triggers.
Eight dedicated relay operation (switching cycle) counters are provided for
counting the number of PFC relay operations (number of complete switching
cycles).
2
Chapter 1 Introduction
One digital input can be used as a status input for monitoring external contacts
or as an external synchronization input for power demand interval
synchronization. When no external synchronization pulse is provided, the power
demand interval can be synchronized through communications.
Three user-selectable options are provided:
Power calculation mode
Power calculations can be made using directly measured reactive power or
through non-active power based on direct apparent power measurements.
Energy rollover value
This option specifies the point at which the energy value rolls over to zero.
Phase energy calculations mode
This option is used to enable or disable phase energy calculations.
Measured Parameters
Note: Real-time values are measured over 1 cycle of fundamental frequency; Average
values are sliding average of 8, 16 or 32 real-time measurements.
Parameter
Display
Com
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Average Amps, Volts, Frequency
Average RMS voltage per phase L-N
Average RMS voltage per phase L-L
Average RMS current per phase
Average frequency
Average neutral current
Voltage & current unbalance
Amps & Volt Demand Parameters
Ampere demand per phase
Volt demand per phase
Ampere maximum demand per phase
Voltage maximum demand per phase
Average Power Values
Average active power per phase
Average reactive power per phase
Average apparent power per phase
Average total active power
Average total reactive power
Average total apparent power
Average power factor per phase
Average total power factor
Power Demand Parameters
Active power accumulated demand
Chapter 1 Introduction
√
Output
Analog Pulse
$ = setup via PC
# = setup via panel
Alarm
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
3
Parameter
Apparent power accumulated demand
Active power demand
Active power sliding demand
Apparent power demand
Apparent power sliding demand
Active power predicted demand
Apparent power predicted demand
Active power maximum demand
Apparent power maximum demand
Energy Per Phase
Active energy import per phase
Reactive energy import per phase
Apparent energy per phase
Total Energy
Total active energy import
Total active energy export
Total reactive energy import
Total reactive energy export
Total reactive energy net
Total reactive energy absolute
Total apparent energy
Min/Max Log
Min/Max volts
Min/Max amps, neutral current
Min/Max frequency
Min/Max kW, kvar, kVA, PF
Real-time Amps, Volts, Frequency
RT RMS voltage per phase L-N
RT RMS voltage per phase L-L
RT RMS current per phase
RT frequency
RT neutral current
Real-time Power Values
RT active power per phase
RT reactive power per phase
RT apparent power per phase
RT total active power
RT total reactive power
RT total apparent power
RT power factor per phase
RT total power factor
4
Display
Com
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Analog
#$
Output
Pulse
Alarm
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
#$
Chapter 1 Introduction
Parameter
Real-time Harmonic Values
RT voltage THD per phase
RT current THD per phase
RT current TDD per phase
RT K-Factor per phase
Average Harmonic Values
Average Voltage THD per phase
Average Current THD per phase
Average Current TDD per phase
Average K-Factor per phase
Fundamental Frequency Values (H01)
Voltage & current per phase
kW, PF per phase
kvar, kVA per phase
Total kW, PF
Total kvar, kVA
Phase Rotation
Counters
Status Input
Relay Status
Remote Relay Control
Alarm Trigger Status
Self-Diagnostic Tests
Display
Com
Analog
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
Output
Pulse
Alarm
#$
#$
#$
#$
√
√
√
√
√
√
√
√
√
#$
√
√
√
√
√
√
#$
#$
For 4Ln3 and 3Ln3 wiring configurations line to line and line to neutral voltages are
displayed and transmitted via communication simultaneously and can be used as triggers
for alarm set points; analog output uses line to neutral voltages. For other configurations
only line to line voltages are used.
Chapter 1 Introduction
5
Instrument Dimensions
Figure 1-1 C192PF8-RPR Dimensions
6
Chapter 1 Introduction
Chapter 2 Installation
2.
2.1 Mechanical Installation
Prepare the panel cut-out, 136 x 136 mm, prior to mounting.
STEP 1: Place the instrument through the cut-out.
STEP 2: Assemble the latches onto the outer wall of the enclosure.
STEP 3: Tighten the screws.
Figure 2-1 Mounting the C192PF8-RPR
Chapter 2 Installation
7
2.2 Electrical Installation
Before installation ensure that all incoming power sources are shut
OFF. Failure to observe this practice can result in serious or even fatal
injury and damage to equipment.
Connections to the C192PF8-RPR are made via terminals (voltage and current
inputs, power supply, communication, relay and analog output) as shown in
Figure 2-2.
2.2.1 Power Supply Connection
The power supply can be dedicated-fused, or from a monitored voltage if it is
within the instrument’s power supply range. Use an external circuit breaker or
switch.
AC power supply: line to terminal 12; neutral to terminal 10.
DC power supply: positive to terminal 12; negative to terminal 10.
2.2.2 Current Inputs
Connect the current inputs to terminals 1, 3, 4, 6, 7, and 9. The instrument is
connected to the current transformer as shown in Figures 2-3 through 2-10.
2.2.3 Ground
Connect the chassis ground C192PF8-RPR terminal to the switchgear earth
2
ground using dedicated wire of greater than 2.5 mm /13 AWG.
2.2.4 Voltage Inputs
Connect the voltage inputs to terminals 2, 5, 8 and 11. For 690V input, use any of
the eight wiring configurations shown in Figures 2-3 through 2-10.
For 120V input, use any of the four wiring configurations shown in Figures 2-5
through 2-8.
8
Chapter 2 Installation
Figure 2-2 C192PF8-RPR Connections - Rear View
Chapter 2 Installation
9
2.2.5 Wiring Configurations
Wiring Configuration
(See parameter setup instructions in Section 4.1)
3-wire direct connection using 2 CTs (2-element)
Wiring
Setup Mode
Connection
3dir2
Figure 2-3
4-wire WYE direct connection using 3 CTs (3-element)
4Ln3 or 4LL3
Figure 2-4
4-wire WYE connection using 3 PTs, 3 CTs (3-element)
4Ln3 or 4LL3
Figure 2-5
3-wire open delta connection using 2 PTs, 2 CTs (2-element)
3OP2
Figure 2-6
3-wire open delta connection using 2 PTs, 3 CTs (2½-element) 3OP3
Figure 2-7
4-wire WYE connection using 2 PTs, 3 CTs (2½-element)
3Ln3 or3LL3
Figure 2-8
4-wire delta direct connection using 3 CTs (3-element)
4Ln3 or 4LL3
Figure 2-9
3-wire/4-wire connection using the current from one phase
(1 CT) and the L-L voltage from the other two phases
2LL1
Figure 2-10
Figure 2-3
Three Wire Direct Connection Using 2 CTs (2-element)
Wiring Mode = 3dir2
Chapter 2 Installation
10
Figure 2-4
Four Wire WYE Direct Connection Using 3 CTs (3-element)
Wiring Mode = 4LL3 or 4Ln3
Figure 2-5
Four Wire WYE Connection Using 3 PTs, 3 CTs (3-element)
Wiring Mode = 4LL3 or 4Ln3
Chapter 2 Installation
11
Figure 2-6
Three Wire Open Delta Connection Using 2 PTs, 2 CTs (2-element)
Wiring Mode = 3OP2
12
Figure 2-7
Three Wire Open Delta Connection Using 2 PTs, 3 CTs (2½-element)
Wiring Mode = 3OP3
Chapter 2 Installation
Figure 2-8
Four Wire WYE Connection Using 2 PTs, 3 CTs (2½-element)
Wiring Mode = 3Ln3 or 3LL3
Figure 2-9
Four Wire Delta Direct Connection Using 3 CTs (3 element)
Wiring Mode = 4LL3 or 4Ln3
Chapter 2 Installation
13
Figure 2-10
Three/Four Wire Direct Connection Using 1 CT
Wiring Mode = 2LL1
2.2.6 Relay
Eight relays are provided for capacitor bank control (or energy pulsing/alarms).
Figure 2-11 Relay Connection
14
Chapter 2 Installation
2.2.7 Status Input
One status input is provided for status monitoring or external synchronization
input for power demand period.
Figure 2-12 Status Input Connection
2.2.8 Analog Output
The C192PF8-RPR provides one optically isolated analog output with current
output options of 0-20 mA and 4-20 mA (current loop load of up to 500 Ohm). The
analog output must be used with a 24 V DC external power supply.
Figure 2-13 Analog Output Connection
Chapter 2 Installation
15
2.2.9 Communications
The C192PF8-RPR is provided with an RS-232 or RS-485 communication port.
Figures 2-14 through 2-18 illustrate the connections.
25-PIN DB25 MALE CONNECTOR
RS-232
15
POWERMETER
14
SG
GND
TxD
TxD
RxD
RxD
7
2
MODEM
3
DSR/CTS
C99-11012
Figure 2-14 RS-232 Connection for 25-pin Modem Connector
RS-232
15
POWERMETER
13
14
9-PIN DB9 MALE CONNECTOR
SG
GND
TxD
TxD
RxD
RxD
5
3
MODEM
2
c99-11013
Figure 2-15 RS-232 Connection for 9-pin Modem Connector
25-PIN DB25 FEMALE CONNECTOR
RS-232
15
POWERMETER
13
14
SG
GND
TxD
RxD
RxD
TxD
DSR
DTR
RTS
CTS
7
3
2
IBM PC/COMPATIBLE
6
20
4
5
c99-11014
Figure 2-16 RS-232 Simple 3-Wire Computer Connection, 25-pin
16
Chapter 2 Installation
9-PIN DB9 FEMALE CONNECTOR
RS-232
15
POWERMETER
13
14
SG
GND
TxD
RxD
RxD
TxD
DSR
DTR
RTS
CTS
5
2
3
IBM PC/COMPATIBLE
6
4
7
8
c99-11015
Figure 2-17 RS-232 Simple 3-Wire Computer Connection, 9-pin
Figure 2-18 RS-485 Multi-drop Computer Connection
NOTE: Where the manufacturer's RS-232/RS-485 converter is used on a computer
connection, R1 is not applicable since it is built in to the converter.
Activity on the communications port lines is indicated via the TXD and RXD LEDs,
on the front panel and via the Status Information menu (see Chapter 6).
A full description of the communication protocols may be found in the C192PF8RPR and Modbus Communications Manuals provided with your instrument.
Chapter 2 Installation
17
Chapter 3 Using The Menus
3.
Press and release
appear:
Press
Press
SELECT
to enter the setup mode. The primary menus will
StA
-
Status Information Menu (see Chapter 6)
OPS
-
Setup Options Menu
CHG
-
Setup Change Menu (see Chapter 4)
SELECT
again to activate the window of the desired primary menu.
ENTER.
Select CHG to initialize or modify the instrument setup, or to clear the accumulated values
stored in the instrument. Entry to this menu can be protected by a password.
SELECT
CHG
ENTER
Select StA to view extended status information which may be useful during installation and
in certain applications.
SELECT
StA
ENTER
Select OPS for viewing (not editing) the instrument setup options.
SELECT
OPS
ENTER
After selecting either OPS or CHG, the list of setup menus is displayed in the
upper window. Figure 3-1 presents a complete menu list. Depending on the
model of your instrument, some menus may not appear.
Password
The Setup Change Menu can be secured by a user-defined password comprised
of 4 digits. The instrument is shipped with password protection disabled. To
enable password protection, go to the Access Control Menu (see Section 4.10).
The Password Menu appears if password protection is enabled.
PASS
To enter a password:
0000
Set the first digit using the up and down arrow keys.
Press SELECT to advance to the next digit.
Set the other password digits in the same manner.
Press ENTER to continue setup. If your password is incorrect, you will return
to the Primary Selection Menu.
18
Chapter 3 Using the Menus
SELECT
ENTER
Status Information
StA
Setup Options
ENTER
OPS
Setup Change
Password
CHG
PASS
PFC Manual Mode
PFC.H
PFC Setup
PFC
PFC Status
PFC
Device Diagnostics
diAG
Reset Functions
rSt
Manual Relay Control
rEL
Basic Setup
Status Inputs
bASc
St.In
Port Setup
Counter #1
Port
Cnt.1
dinP
Analog Output
Aout
Pulsing Setpoints
PulS
Event Setpoints
SetP
Selects an active window
ENTER
Enters menu/sub-menu
ESC
Quits menu/sub-menu
Counter #2
Cnt.2
Counter #3
Cnt.3
Counter #4
Cnt.4
Relay Operation
Counter #1
CYC.1
Relay Operation
rELo
Display Setup
diSP
Scrolls options forward
Selectable Options
Scrolls options backward
PHAS
Relay Status
rELc
Digital Input
SELECT
Phase Rotation
OPtS
Relay Operation
Counter #2
CYC.2
...
Relay Operation
Counter #8
CYC.8
Access Control
AccS
Figure 3-1 Menu Structure
Chapter 3 Using the Menus
19
Chapter 4 Setup Menus
4. CHAPTER 3 SETUP MENUS
NOTE: Instrument setup can be performed directly on the front panel using the setup
menus or via communications using PAS communication software. PAS is supplied with
your instrument and provides full setup capabilities for your instrument. For information on
using PAS, refer to the user documentation supplied with your instrument.
Setup
Basic
Communication port
User Selectable options
Analog output
Digital input
Alarm/Event set points
Pulsing output
PFC setup
Assignable registers
Display
Display
+
++
++
+
+
+
+
+
++
PAS
+
+
+
+
+
+
+
++
++
-
++ Recommended method
4.1 Basic Setup Menu
SELECT
CHG
ENTER
bASc
ENTER
This menu contains the basic configuration options which define the general
operating characteristics of your instrument, such as wiring mode, input scales,
the size of the RMS averaging buffer, etc. Table 4-1 lists the basic setup options,
their code names and applicable ranges.
Activate the middle window to scroll through the list of available options, and then
activate the lower window to set the option value.
bASc
To select and view a setup option:
ConF
Press SELECT to activate the middle window
Use the up/down arrow keys to scroll to the desired option. The current
value for this option appears in the lower window.
To change the value of the selected option:
4L-n
Press SELECT to make the lower window active.
Press the up/down arrow keys to scroll to the desired value.
Press ENTER to store the selected value, or press ESC to quit the
setup menu.
20
Chapter 4 Setup Menus
Table 4-1 Basic Setup Options (∗ default setting)
Code
ConF
Pt
Ct
d.P
n.dp
A.dP
buF
rSt
Freq
LoAd
Parameter
Wiring mode
Options
Description
3OP2
3-wire open delta using 2 CTs
(2 element)
4-wire Wye using 3 PTs (3 element), line to
4Ln3∗
neutral voltage readings
3dir2
3-wire direct connection using 2 CTs (2
element)
4LL3
4-wire Wye using 3 PTs (3 element), line to
line voltage readings
3OP3
3-wire open delta using 3 CTs
(2½ element)
3Ln3
4-wire Wye using 2 PTs (2½ element), line to
neutral voltage readings
3LL3
4-wire Wye using 2 PTs (2½ element), line to
line voltage readings
2LL1
3-wire/4-wire connection using the current
from one phase (1 CT) and the L-L voltage
from the two other phases
PT ratio
1.0*-6,500.0 The phase potential transformer ratio
CT primary current 1-6,500A
The primary rating of the phase current
transformer
(5∗)
Power demand
1, 2, 5, 10, The length of the demand period for power
period
15*, 20, 30, demand calculations, in minutes. E = external
synchronization
60, E
Number of power 1-15
The number of demand periods to be averaged
demand periods
for sliding window demands
(1*)
1 = block interval demand calculation
0-1800 s
Ampere/Volt
The length of the demand period for
(900*)
demand period
volt/ampere demand calculations
0 = measuring peak current
Averaging buffer
The number of measurements for RMS sliding
8∗,16,32
size
averaging
Reset
Protects all reset functions, both via the front
diS∗, En
enable/disable
panel or communications.
Nominal frequency 50, 60 Hz
The nominal power utility frequency
Maximum demand 0-6,500A
The maximum demand load current used in
load current
TDD calculations (0 = CT primary current)
(0∗)
When the power demand period is specified in minutes, synchronization of the demand
interval can be made through communications (see the C192PF8-RPR Modbus
Reference Guides) or via the front panel (see Section 4.11). If the power demand period
is set to External Synchronization, an external synchronization pulse denoting the start
of the next demand interval can be provided through a digital input or can be simulated
by using the synchronization command sent via communications.
60 Hz default for North America; elsewhere, default is 50Hz.
Chapter 4 Setup Menus
21
NOTES
1) The maximum value for CT PRIMARY CURRENT × PT RATIO is 10,000,000. If this
product is greater, power related values will be zeroed.
2)
Always specify WIRING MODE, PT RATIO and CT PRIMARY CURRENT prior to
setting up alarm setpoints, otherwise the alarm/event setpoints which use these
parameters will automatically be disabled.
3)
You will not be able to change the WIRING MODE, PT RATIO and CT PRIMARY
CURRENT when the PFC is in operating state (see Section 4.13).
4.2 Communications Port Setup Menu
SELECT
CHG
Port
ENTER
ENTER
This menu allows you to access the communications port options that the
C192PF8-RPR uses to communicate with a master computer. Table 4-2 lists the
communications options, their code names and applicable choices.
Activate the middle window to scroll through the list of available options, and then
activate the lower window to set the option value.
Port
To select and view a setup option:
Prot
Press SELECT to activate the middle window.
Use the up/down arrow keys to scroll to the desired option. The option
setting will appear in the lower window.
To change the selected option:
rtu
Press SELECT to activate the lower window.
Press the up/down arrow keys to scroll to the desired value.
Press ENTER to store the selected value or press ESC to quit the
setup menu.
Table 4-2 Communications Options (∗ default setting)
Code
22
Parameter
Options
Description
Prot
Communications
protocol
ASCII
rtu∗
ASCII protocol
Modbus RTU protocol
Addr
Address
0∗-99 ASCII
1∗-247 Modbus
Powermeter address
bAud
Baud rate
110
300
600
1200
2400
4800
9600∗
19.20
110 baud
300 baud
600 baud
1200 baud
2400 baud
4800 baud
9600 baud
19,200 baud
dAtA
Data format
7E
8n
7 bits, even parity
8 bits, no parity
Chapter 4 Setup Menus
Code
Parameter
Options
8E∗
CPtb
ASCII compatibility
mode
diS∗, En
Description
8 bits, even parity
Disables/enables ASCII
compatibility mode. For
more information, see ASCII
Communications Protocol
Reference Guide
4.3 Digital Input Setup Menu
SELECT
CHG
ENTER
dinP
ENTER
This menu is used to set up a digital input provided by the C192PF8-RPR.
The digital input can be configured as:
- a status input to monitor external contact status, or
- an external synchronization pulse input to receive an external
synchronization pulse indicating the beginning of a new demand interval
for power demand measurements.
The setup menu is used for allocating an external synchronization pulse input. If
you do not allocate the digital input as an external synchronization input, it is
automatically configured as a status input
To change the digital input allocation:
External
Press SELECT to activate the middle window.
synchronization
Use the up/down arrow keys to set the input allocation
input
status.
Press ENTER to store your new inputs allocation.
E.Snc
Press ESC to leave the allocation unchanged or to quit
1
the menu.
“1” indicates that the input is allocated as the external synchronization pulse
input; “0” indicates that the input is allocated as the status input.
NOTES
1.
A digital input configured as the status input can be monitored via the Status
Information Menu (see Chapter 6) and communications.
2.
If the digital input has been allocated as the external synchronization pulse input,
synchronization of the demand interval through communications is not available.
Chapter 4 Setup Menus
23
4.4 Analog Output Setup Menu
[This section is relevant to instruments ordered with this option.]
CHG
SELECT
Aout
ENTER
ENTER
This menu allows you to set up an output value and its zero and full scales for the
internal analog output. Table 4-3 explains the analog output setup options, and
Table 4-4 lists all measurement parameters that can be directed to analog output.
Output parameter
Zero-scale output
Full-scale output
Aout
Aout
Aout
Outp
Lo
Hi
rt
U1
0
828
To view the setup options for the analog output:
Press SELECT to activate the middle window.
Use the up/down arrow keys to scroll to the desired option. The value
associated with this option is displayed in the lower window.
To change the setup options for the selected channel:
Press SELECT to activate the lower window.
Use the up/down arrow keys to scroll to the desired value.
Press ENTER to store the selected value, or press ESC to leave the value
unchanged.
Press ENTER again to store the setup for the channel.
To quit the setup without changes:
From the middle or lower window, press ESC .
To quit the menu:
From the upper window, press ESC or ENTER .
NOTES
1. Except for the signed power factor, the output scale is linear within the value range.
The scale range will be inverted if the full scale specified is less than the zero scale.
24
2.
The output scale for the signed power factor is symmetrical with regard to ±1.000 and
is linear from -0 to -1.000, and from 1.000 to +0 (note that -1.000 ≡ +1.000). Negative
power factor is output as [-1.000 minus measured value], and non-negative power
factor is output as [+1.000 minus measured value]. To define the entire power factor
range from -0 to +0, the scales would be specified as -0.000/0.000.
3.
Each time you select the output parameter for the analog channel, its zero and full
scales are set by default to the lower and upper parameter limits, respectively.
Chapter 4 Setup Menus
Table 4-3 Analog Output Setup Options
Code
Option
Description
OutP
Lo
Output parameter
The output parameter for the analog output channel
Zero scale (0/4 mA)
The reading of the parameter corresponding to a zeroscale current output
Hi
Full scale (1/20 mA)
The reading of the parameter corresponding to a full-scale
current output
Table 4-4 Analog Output Parameters
Code
nonE
r. U 1
r. U 2
r. U 3
r. C1
r. C2
r. C3
r. P
r. q
r. S
r. PF
r. PF.LG
r. PF.Ld
r. Fr
Parameter
Unit
Output disabled
Real-time Measurements
Voltage L1/L12
Voltage L2/L23
Voltage L3/L31
Current L1
Current L2
Current L3
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Frequency
Scale
0
V/kV
V/kV
V/kV
A
A
A
kW/MW
kvar/Mvar
kVA/MVA
Hz
0 to Vmax
0 to Vmax
0 to Vmax
0 to Imax
0 to Imax
0 to Imax
-Pmax to Pmax
-Pmax to Pmax
0 to Pmax
-0.000 to 0.000
0 to 1.000
0 to 1.000
0 to 100.00
Average Measurements
A. U 1
A. U 2
A. U 3
A. C1
A. C2
A. C3
A. P
A. q
A. S
A. PF
A. PF.LG
A. PF.Ld
A. neU.C
A. Fr
Voltage L1/L12
Voltage L2/L23
Voltage L3/L31
Current L1
Current L2
Current L3
Total kW
Total kvar
Total kVA
Total PF
Total PF lag
Total PF lead
Neutral current
Frequency
V/kV
V/kV
V/kV
A
A
A
kW/MW
kvar/Mvar
kVA/MVA
A
Hz
0 to Vmax
0 to Vmax
0 to Vmax
0 to Imax
0 to Imax
0 to Imax
-Pmax to Pmax
-Pmax to Pmax
0 to Pmax
-0.000 to 0.000
0 to 1.000
0 to 1.000
0 to Imax
0 to 100.00
kW/MW
kVA/MVA
0 to Pmax
0 to Pmax
Present Demands
Accd.P
Accd.S
Accumulated kW demand
Accumulated kVA demand
Imax (20% over-range) = 1.2 × CT primary current [A]
Direct wiring (PT Ratio = 1):
Chapter 4 Setup Menus
25
Vmax (690 V input option) = 828.0 V
Vmax (120 V input option) = 144.0 V
Pmax = (Imax × Vmax × 3) [kW x 0.001] @ wiring modes 4Ln3, 3Ln3
Pmax = (Imax × Vmax × 2) [kW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3
NOTE: Pmax is rounded to nearest whole kW units.
If Pmax is more than 9999.000 kW, it is truncated to 9999.000 kW
Wiring via PTs (PT Ratio > 1):
Vmax (690 V input option) = 144 × PT Ratio [V]
Vmax (120 V input option) = 144 × PT Ratio [V]
Pmax = (Imax × Vmax × 3)/1000 [MW x 0.001] @ wiring modes 4Ln3, 3Ln3
Pmax = (Imax × Vmax × 2)/1000 [MW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3
NOTE: Pmax is rounded to nearest whole kW units.
The actual frequency range is 45.00 - 65.00 Hz
4.5 Pulsing Output Setup Menu
SELEC
CHG
PulS
ENTER
ENTER
This menu allows you to program any of the eight relays provided by your
C192PF8-RPR instrument to output energy pulses. Relays #7 and #8 are
especially recommended for use as pulsing relays because of their high
endurance. Available pulsing parameters are listed in Table 4-5.
rEL.1
To select a pulse relay:
Ac.Ei
Use the up/down arrow keys to scroll to the desired relay. The
pulsing parameter assigned to the relay is displayed in the
middle window, and the amount of unit-hours per pulse is
displayed in the lower window.
To change the pulse relay setup:
1
Press SELECT to activate the middle window.
Use the up/down arrow keys to scroll to the desired output
parameter. Selecting nonE disables pulsing through this relay.
Press SELECT to activate the lower window.
Use the up/down arrow keys to set the amount of unit-hours
per pulse. The available range is 1-9999.
Press ENTER to store the new setup, or press ESC to quit the
setup without changes.
To quit the pulsing setup menu:
From the upper window, press ESC or ENTER .
Table 4-5 Pulsing Output Parameters
Code
nonE
Ac.Ei
Ac.EE
rE.Ei
26
Parameter
Output disabled
Active energy import
Active energy export
Reactive energy import
Units
kWh import (positive)
kWh export (negative)
kvarh import (inductive)
Chapter 4 Setup Menus
Code
rE.EE
rE.Et
AP.Et
Parameter
Reactive energy export
Reactive energy total
Apparent energy total
Units
kvarh export (capacitive)
kvarh total (absolute)
kVAh total
NOTES
1.
You will not be able to store your setup in the instrument if you assigned a parameter
to a relay output with a zero number of unit-hours per pulse.
2.
If a relay you allocated for pulsing has been manually operated or released, it reverts
automatically to normal operation.
3.
If a relay you allocated for pulsing has been engaged by an alarm/event setpoint, the
setpoint is automatically disabled.
4.6 Alarm/Event Setpoints Setup Menu
SELECT
CHG
ENTER
SEtP
ENTER
Your instrument provides 16 alarm/event setpoints that can monitor a wide variety
of events; in turn, these events can be programmed to trigger specific actions.
This menu is used to specify the events to be monitored by the setpoints, and
actions to be triggered by those events.
To program a setpoint, you might need to define up to six setup parameters which
include: the setpoint trigger parameter, operate and release limits, optional
operate and release delays, and the setpoint action. Table 4-6 explains the
setpoint setup parameters. For the entire list of available triggers and setpoint
actions, refer to Tables 4-7 and 4-8.
Example:
Trigger
Setpoint 1 is set to monitor the real-time high current
SP 1
on phase 1 (the trigger parameter).
parameter
triG
RHi.C1
SP 1
On
1200
SP 1
OFF
1100
Operate limit }
}
}
}
Release limit }
Chapter 4 Setup Menus
The operate (On) and release (OFF) limits which
determine setpoint operation are defined as 1200A
and 1100A respectively.
27
SP 1
On d
5
SP 1
OFFd
10
SP 1
Act
rEL.1
Operate delay }
}
}
}
Release delay }
The delays before operation (On d) and release
(OFFd) are set at 5 seconds and 10 seconds
respectively.
Setpoint action
The action to be triggered is operation of relay #1.
To select a setpoint:
Scroll to the desired setpoint using the up/down arrow keys.
To view the setup options for the setpoint:
Press SELECT to activate the middle window.
Use the up/down arrow keys to scroll to the desired setup option. The value
associated with this option is displayed in the lower window.
To change the selected setup option:
Press SELECT to activate the lower window.
Use the up/down arrow keys to scroll to the desired value.
Press ENTER to store the new value.
Press ESC to leave the value unchanged.
To store your new setup for the setpoint:
From the middle window, press ENTER .
To quit the setpoint setup without changes:
From the middle window, press ESC .
To quit the setpoints setup menu:
From the upper window, press ESC or ENTER .
NOTES
28
1.
When you enter the setpoints setup menu at the protected level, monitoring of
setpoints is temporarily suspended until you return to the main setup menu.
2.
Each time you select a new trigger parameter, the operate and release limits are set
by default to zero.
3.
You will not be able to store your setpoint setup to the instrument if a setpoint action is
directed to a relay allocated for pulsing.
4.
The setpoint action directed to a relay output can be overridden using commands sent
via communications. A relay can be manually operated or released. When the relay
reverts to normal operation, it is automatically returned under setpoint control.
Chapter 4 Setup Menus
Table 4-6 Setpoint Setup Options (middle window)
Code
Option
trig
Trigger parameter
On
OFF
Operate limit
Release limit
On d
Operate delay
OFF d
Release delay
Act
Setpoint action
Description
The measurement parameter or signal to be monitored
by the setpoint.
The threshold at which the setpoint becomes operative.
The threshold at which the setpoint is released (becomes
inoperative).
The time delay (0.1 second resolution) before operation
when the operate condition is fulfilled.
The time delay (0.1 second resolution) before release
when the release condition is fulfilled.
The action performed when the setpoint is operative.
Table 4-7 Setpoint Triggers (lower window, when middle window is triG)
Code
nonE
St.On
St.OFF
FAult
no-U
UncoP
POS.ro.
NEG.ro.
r. Hi. U
r. Hi. LU
r. Lo. U
r. Lo. LU
r. Hi. C
r. Lo. C
r. thd.U
r. thd.C
r. HFc.C
r. tdd.C
r. Hi.Fr
r. Lo.Fr
A. Hi.C1
A. Hi.C2
A. Hi.C3
A. Lo.C1
A. Lo.C2
Parameter
Setpoint disabled
Status Input
Status input ON
Status input OFF
Fault Triggers
Device Fault (diagnostics error)
No-Volt
Uncompensated reactive power
Phase Reversal
Positive phase rotation reversal
Negative phase rotation reversal
Real-time Values on any Phase
High voltage
High L-L voltage
Low voltage
Low L-L voltage
High current
Low current
High voltage THD
High current THD
High K-factor
High current TDD
Real-time Auxiliary Measurements
High frequency
Low frequency
Average Values per Phase
High current L1
High current L2
High current L3
Low current L1
Low current L2
Chapter 4 Setup Menus
Unit
Range
V
V
V
V
A
A
%
%
%
%
0 to Vmax
0 to Vmax
0 to Vmax
0 to Vmax
0 to Imax
0 to Imax
0 to 999.9
0 to 999.9
1.0 to 999.9
0 to 100.0
Hz
Hz
0 to 100.00
0 to 100.00
A
A
A
A
A
0
0
0
0
0
to
to
to
to
to
Imax
Imax
Imax
Imax
Imax
29
Code
A. Lo.C3
A. Hi. U
A. Hi. LU
A. Lo. U
A. Lo. LU
A. Hi. C
A. Lo. C
A. Hi.P.i
A. Hi.P.E
A. Hi.q.i
A. Hi.q.E
A. Hi. S
A. PF.LG
A. PF.Ld
Ar neU.C
Ar Hi.Fr
Ar Lo.Fr
Hi d.U1
Hi d.U2
Hi d.U3
Hi d.C1
Hi d.C2
Hi d.C3
Hi d.P
Hi d.S
Hi Sd.P
Hi Sd.S
Hi Ad.P
Hi Ad.S
Hi Pd.P
Hi Pd.S
Parameter
Low current L3
Average Values on any Phase
High voltage
High L-L voltage
Low voltage
Low L-L voltage
High current
Low current
Average Total Values
High total kW import (positive)
High total kW export (negative)
High total kvar import (positive)
High total kvar export (negative)
High total kVA
Low total PF Lag
Low total PF Lead
Average Auxiliary Measurements
High neutral current
High frequency
Low frequency
Present Demands
High
High
High
High
High
High
High
High
High
High
High
High
High
High
volt demand L1
volt demand L2
volt demand L3
ampere demand L1
ampere demand L2
ampere demand L3
block interval kW demand
block interval kVA demand
sliding window kW demand
sliding window kVA demand
accumulated kW demand
accumulated kVA demand
predicted sliding window kW demand
predicted sliding window kVA demand
A
Unit
Range
0 to Imax
V
V
V
V
A
A
0
0
0
0
0
0
to
to
to
to
to
to
Vmax
Vmax
Vmax
Vmax
Imax
Imax
kW
kW
kvar
kvar
kVA
0
0
0
0
0
0
0
to
to
to
to
to
to
to
Pmax
Pmax
Pmax
Pmax
Pmax
1.000
1.000
A
Hz
Hz
0 to Imax
0 to 100.00
0 to 100.00
V
V
V
A
A
A
kW
kVA
kW
kVA
kW
kVA
kW
kVA
0
0
0
0
0
0
0
0
0
0
0
0
0
0
to
to
to
to
to
to
to
to
to
to
to
to
to
to
Vmax
Vmax
Vmax
Imax
Imax
Imax
Pmax
Pmax
Pmax
Pmax
Pmax
Pmax
Pmax
Pmax
For parameter limits, see notes to Table 4-4.
The setpoint is operated when the actual phase sequence does not match the indicated
normal phase rotation.
The actual frequency range is 45.00 - 65.00 Hz.
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for
any other wiring mode, they will be line-to-line voltages.
The Device Fault trigger is active when the self-diagnostics test detects a critical
(unrecoverable) error. This could happen when a corrupted configuration setup or
incompatible setup setting is detected. In this event, the device will reset the corrupted
setup to default. The trigger is cleared when the setup is rewritten or device diagnostics
is cleared either through the Status Information Menu (see Section 7.1), or through
communications. When a non-critical error is detected, the device will only set a
corresponding fault bit in the self-check diagnostics register and restart operations.
30
Chapter 4 Setup Menus
The No-Volt trigger is intended for the use as a fast setpoint override condition for PFC
operations in order to protect the capacitor banks against voltage interruptions. When
used with the Hard Switch-Off action, it can de-energize the output relays in
approximately 25 ms. This avoids bringing the still charged capacitors back after the
voltage is restored. When used with other setpoint actions, this trigger can provide the
response time to alarm conditions at 25-75 ms.
The Uncompensated reactive power trigger is active when the device fails to bring the
power factor or reactive power into the target setpoint range.
Table 4-8 Setpoint Actions (lower window, when middle window is Act)
Code
NonE
ALAr
Hrd.OF
SFt.OF
StoP
rEL.1
rEL.2
rEL.3
rEL.4
rEL.5
rEL.6
rEL.7
rEL.8
In.Cn.1
In.Cn.2
In.Cn.3
In.Cn.4
ti.Cn.1
ti.Cn.1
ti.Cn.1
ti.Cn.1
Action
No action
Assert local alarm
Hard (immediate) switch-off of the PFC relays
Soft (in turn) switch-off of the PFC relays
Stop (freeze) automatic operation of the PFC
Operate relay #1
Operate relay #2
Operate relay #3
Operate relay #4
Operate relay #5
Operate relay #6
Operate relay #7
Operate relay #8
Increment counter #1
Increment counter #2
Increment counter #3
Increment counter #4
Count operating time using counter #1
Count operating time using counter #2
Count operating time using counter #3
Count operating time using counter #4
When a setpoint is operated, its status is always stored to the alarm status register
even if no action is assigned to the setpoint. The alarm status register can be polled
and cleared through communications.
This action causes the alarm LED on the front panel to light, giving the user a local
alarm indication. The alarm LED operates in latched mode, i.e., even if an alarm
condition disappears, the alarm LED continues to operate until the user acknowledges
the alarm from the front panel (see Section 5.1). An alarm LED can be operated from
any number of setpoints using an OR scheme.
These actions are intended for the use with the PFC alarm protection setpoints in order
to protect the capacitor banks against harmful conditions that can cause damage.
When an alarm override condition is detected, the Hard Switch-Off action immediately
switches out all the capacitor banks including those defined as permanently switched
in. When used with the No-Volt trigger condition (see Note
to Table 4-7), this action
provides the fastest possible response to voltage interruptions.
The Soft Switch-Off action switches off the capacitor banks progressively in pre-set
disconnection intervals, as long as the alarm condition is present. This allows escaping
the over-voltage or high harmonics conditions with minimum required cycling of the
capacitor banks. The capacitor banks that are defined as permanently switched in will
Chapter 4 Setup Menus
31
not be affected. After the alarm condition passes, the PFC will return to automatic
operation after the safety delay which is 50 times the power factor setpoint operate
delay (see Note to Table 4-11).
The Stop action freezes the PFC operations in automatic operation modes. The PFC
avoids any automatic switching operations on the capacitor banks while the alarm
condition is present. This action does not affect operations in the Manual/Remote mode.
Alarm relays operate in unlatched mode. This means that a relay is operated while an
alarm condition is present and is automatically released when an alarm condition
disappears. Each relay can be operated from any number of setpoints using an OR
scheme, i.e., a relay will be operative while either of the alarm conditions is still present.
This action converts a common-use event counter to the dedicated time counter that
measures time at 0.1-hour resolution while the setpoint is operative. Each time counter
has a non-volatile shadow counter that counts time at 1-second resolution before the
corresponding time counter is incremented. The time counters can be inspected via the
Status Information Menu. They are labeled by an hour mark in the middle window.
4.7 Relay Operation Control Menu
SELECT
CHG
ENTER
rELo
ENTER
This menu allows you to set the relay operation mode: non-failsafe or failsafe.
Failsafe relay operation is the opposite of normal operation where relay contacts
are closed when a relay is operated (activated), and are open when a relay is
released (de-activated). In failsafe mode, an alarm is activated by a nonenergized relay which will open in all cases when an alarm condition is present or
an alarm setpoint is not operational either due to a loss of control power or due to
corruption of the setpoint setup configuration. A failsafe relay is closed only if it is
under setpoint control and no alarm conditions exist, or if it is manually operated
from the front panel or via communications.
rELo
rEL.1
nor
To select a relay:
Press SELECT to activate the middle window, and then use
the up/down arrow keys to scroll to the desired relay.
To change the relay operation mode:
Press SELECT to activate the lower window.
Use the up/down arrow keys to set the desired option.
Select nor for normal (non-failsafe) relay operation, or
select FSAFE for failsafe relay operation.
Press ENTER to store your new setting or press ESC to
leave your previous setting unchanged.
To quit the setup menu:
From the middle window, press ESC or ENTER .
NOTES
32
1.
You will not be able to change the relay operation mode if a relay has been allocated
for pulsing or is controlled by the PFC.
2.
When a failsafe relay is allocated for pulsing or to the PFC, it automatically reverts to
normal operation.
Chapter 4 Setup Menus
4.8 Display Setup Menu
SELECT
CHG
diSP
ENTER
ENTER
This menu allows you to view and change display properties. Table 4-9 lists
available options with their code names and applicable ranges.
Table 4-9 Display Options (∗ default setting)
Display
Code
Parameter
Options
diSP
UPdt
Display update
time
0.1 - 10.0 s
(0.5)*
Defines interval between
display updates
ScrL
Auto scroll
nonE*
2-15 s
Disables/enables auto scroll
on common measurements
display (main screen) and
defines scroll interval
rEtn
Auto return to
the main screen
diS*, En
Disables/enables auto return
to the main screen after 30
seconds of uninterrupted use
Ph.P
Phase powers
display mode
diS*, En
Disables/enables display of
phase powers in common
measurements (main
screen)
Fund
Fundamental
values display
mode
diS*, En
Disables/enables display of
fundamental values in
common measurements
(main screen)
UPdt
Description
0.5
diSP
ScrL
5
diSP
rEtn
diS
diSP
Ph.P
diS
diSP
Fund
diS
Chapter 4 Setup Menus
33
To select a display option:
Press SELECT to activate the middle window, and then use the up/down arrow
keys to scroll to the desired option.
To change the display option:
Press SELECT to activate the lower window.
Use the up/down arrow keys to set the desired option.
Press ENTER to store your new setting or press ESC to leave your previous
setting unchanged.
To quit the display setup menu:
From the middle window, press ESC or ENTER .
4.9 User Selectable Options Menu
SELECT
CHG
ENTER
OPtS
ENTER
This menu allows you to change options which relate to the instrument features
and functionality. Table 4-10 lists all available options with their code names and
applicable ranges.
OPtS
P.cAL
rEAc
To select an option:
Press SELECT to activate the middle window, and then use the
up/down arrow keys to scroll to the desired option.
To change the selected option:
Press SELECT to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press ENTER to store your new setting or ESC to leave the
previous setting unchanged.
To quit the display setup menu:
From the middle window, press ESC or ENTER .
Table 4-10 User Selectable Options (∗ default setting)
Code
P.cAL
roLL
34
Parameter
Power calculation
mode
Energy roll value
Options
rEAc*
nAct
10.E4
10.E5
10.E6
10.E7
10.E8*
Description
Using reactive power
Using non-active power
10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh
Chapter 4 Setup Menus
Code
Ph.En
Parameter
Phase energy
measurements
Options
diS*, En
Description
Enables/disables measurements of energies
per phase
Power calculation mode (P.cAL):
Mode 1: Reactive power calculation (rEAc)
Active power P and reactive power Q are measured directly and apparent power
S=√P +Q
2
2
Mode 2: Non-active power calculation (nAct)
Active power is measured directly, apparent power S = V × I (where V, I - rms
2
2
voltage and currents) and non-active power N = √ S - P
Mode 1 is recommended for electrical networks with low harmonic distortion (voltage
THD < 5%, current THD < 10%); Mode 2 is recommended for all other cases.
Energy roll value example: If roll value = 10.E4, the energy counter contains 4 digits,
i.e., energy is displayed up to 9.999 MWh (Mvarh, MVAh) with resolution 0.001 MWh.
Rollover
Value
10.E4
10.E5
10.E6
10.E7
10.E8
Maximum Energy
kWh (kvarh, kVAh)
9,999
99,999
999,999
9,999,999
99,999,999
Maximum Display Reading
MWh (Mvarh, MVAh)
9.999
99.999
999.99
9,999.9
99,999
Display Resolution
MWh (Mvarh, MVAh)
0.001
0.001
0.01
0.1
1
The roll value may be changed in accordance with the average load of the power line.
For example, if average power is 400 kW and the counter must be reset every 3 months
(2160 hours), then energy during this period equals 864000 kWh (6 digits) and the roll
value = 10.E6.
Chapter 4 Setup Menus
35
4.10 Access Control Menu
SELECT
CHG
ENTER
AccS
ENTER
This menu can be only accessed via the Setup Change Menu (CHG). It is used in
order to:
• change the user password
• enable or disable password check
To view an option setting:
Press SELECT to activate the middle window.
Use the up/down arrow keys to scroll to the desired option (PASS or CtrL).
Password Setting
Password Protection Control
AccS
AccS
PASS
CtrL
8780
OFF
To change the password:
Press SELECT to activate the lower window.
Use the up/down arrow keys to modify the password. The password can be
up to four digits long.
Press ENTER to store your new password, or ESC to leave the password
unchanged.
To enable/disable password checking:
Press SELECT to activate the middle window, and then use the up/down
arrow keys to move to the CtrL entry.
Press SELECT to activate the lower window.
Use the up/down arrow keys to change the password checking status: select
OFF to disable password protection, or select On to enable password
protection.
Press SELECT to store your new option, or ESC to leave the option
unchanged.
To quit the setup menu:
From the middle window, press ESC or ENTER .
Store your password in a safe place. If you do not provide the correct
password, you will need to contact your local distributor for the super-user
password to override password protection.
36
Chapter 4 Setup Menus
4.11 Reset/Synchronization Menu
SELECT
CHG
ENTER
rSt
ENTER
This menu allows you to reset to zero the accumulators and Min/Max registers in
your instrument, and also to synchronize the power demand interval. The menu
can be only accessed via the Setup Change Menu (CHG). If the reset is disabled
from the Basic Setup Menu (see Section 4.1), you will not be able to enter this
menu.
The following designations are used to specify a data location to be affected:
EnrG Resets total accumulated energies
Resets all total maximum demands
dnd
P.dnd Resets total power maximum demands
A.dnd Resets volt/ampere maximum demands
Lo.Hi Resets Min/Max registers (does not affect maximum demands)
Resets all event/time counters
Cnt
Cnt.1 Resets event/time counter # 1
Cnt.2 Resets event/time counter # 2
Cnt.3 Resets event/time counter # 3
Cnt.4 Resets event/time counter # 4
Resets all PFC relay operation (banks switching cycle) counters
CYC
CYC.1 Resets PFC relay operation counter # 1
CYC.2 Resets PFC relay operation counter # 2
CYC.3 Resets PFC relay operation counter # 3
CYC.4 Resets PFC relay operation counter # 4
CYC.5 Resets PFC relay operation counter # 5
CYC.6 Resets PFC relay operation counter # 6
CYC.7 Resets PFC relay operation counter # 7
CYC.8 Resets PFC relay operation counter # 8
d.Snc Provides synchronization of the power demand interval (see NOTES below)
rSt
EnrG
do
To reset the desired locations:
Press SELECT to activate the middle window, and then use the
up/down arrow keys to scroll to the desired data location entry.
Press SELECT to activate the lower window.
Press and hold ENTER for about 5 seconds until the do label
is replaced with done, and then release the key. You will return
to the middle window.
Press ESC to quit the menu.
NOTES:
1.
If changing data in the instrument via the front panel is not secured by a password, fast
reset of the Min/Max registers, maximum demands and energies can be done from the
Chapter 4 Setup Menus
37
data display mode (see Section 5.1), and reset of counters from the Status Information
Menu (see Section 6.1) without entering the reset menu.
2.
If you select the d.Snc entry, take into consideration the following:
a) If the power demand period is specified in minutes (see Section 4.1, Basic Setup
Options), this action provides synchronization of the instrument’s internal timer. If
the time expired from the beginning of the current demand interval is more then 30
seconds, the new demand interval starts immediately, otherwise synchronization is
delayed until the next demand interval.
b) The synchronization is made at the moment delayed by exactly 5 seconds from the
time you first pressed ENTER while you hold the key.
4.12 Manual Relay Control Menu
SELECT
CHG
ENTER
rELc
ENTER
This menu allows you to manually activate (force operated) or de-activate (force
released) a relay if it is not allocated for pulsing and not controlled by the PFC.
When a relay is controlled by the alarm setpoint, this command will override the
setpoint alarm conditions until the relay is returned to normal operation.
rELc
rEL.1
OPEr
To select a relay:
Press SELECT to activate the middle window, and then use
the up/down arrow keys to scroll to the desired relay.
To change the relay status:
Press SELECT to activate the lower window.
Use the up/down arrow keys to set the desired option.
Select nor for normal (setpoint-controlled) relay operation,
select OPEr to activate a relay, or rELS to de-activate a
relay.
Press ENTER to store your new setting or press ESC to
leave your previous setting unchanged.
To quit the setup menu:
From the middle window, press ESC or ENTER .
NOTE
You will not be able to override the relay operation mode if a relay has been allocated for
pulsing or is controlled by the PFC.
38
Chapter 4 Setup Menus
4.13 PFC Setup Menu
SELECT
CHG
ENTER
PFC
ENTER
This menu allows you to configure the PFC setup options and to set the PFC
operation mode. Table 4-11 lists the PFC setup options, their code names and
applicable ranges. For more information on the PFC options and operation, refer
to Chapter 5, PFC Operation.
PFC
To select and view a setup option:
run
Press SELECT to activate the middle window
Use the up/down arrow keys to scroll to the desired option. The current
value for this option appears in the lower window.
To change the value of the selected option:
Aut.1
Press SELECT to make the lower window active.
Press the up/down arrow keys to scroll to the desired value.
Press ENTER to store the selected value, or press ESC to quit the
setup menu.
Table 4-11 PFC Setup Options (∗ default setting)
Code
run
Parameter
PFC operation mode
Options
OFF∗
Aut.1
Aut.2
Hand
triG
PFC setpoint trigger
PF
PF.H01
rE.P∗
rE.H01
SEtP
Operational setpoints
Chapter 4 Setup Menus
SP1
Description
The PFC is OFF/Shut down the PFC
Self-adapting automatic mode. The
capacitor banks are connected and
disconnected progressively starting from
the first available bank.
Optimizing automatic mode. The capacitor
banks are connected and disconnected in
pre-optimized steps to reduce the number
of switching operations.
Safe manual operation mode. The banks
are connected and disconnected
progressively starting from the first
available bank when user commands are
entered from the front panel or through
communications (see Section 4.14, PFC
Manual Mode Menu).
True power factor (based on true RMS
calculations) - PFC mode
Fundamental harmonic's power factor
(power factor displacement) - PFC mode
True reactive power (based on true RMS
calculations) - RPR mode
Fundamental harmonic's reactive power RPR mode
The target setpoint range is defined by
setpoint SP1
39
Code
U.CAP
Nominal voltage of the
capacitor banks
L.PF1
Low target PF1 (in PFC
mode)
High target PF1 (in PFC
mode)
Low target PF2 (in PFC
mode)
High target PF2 (in PFC
mode)
Low target kvar 1 (in
RPR mode)
High target kvar 1 (in
RPR mode)
Low target kvar 2 (in
RPR mode)
High target kvar 2 (in
RPR mode)
Setpoint operate delay,
sec
H.PF1
L.PF2
H.PF2
L.rE1
H.rE1
L.rE2
H.rE2
OP.d
On.d
OFF.d
rEc.d
CAP1
CAP2
40
Parameter
Options
SP1-2∗
Description
Two target setpoint ranges are defined by
setpoints SP1 and SP2 (generally, to
differentiate between day and night
operations). The active setpoint range is
selected through a digital (status) input.
1V to 999V if PT RATIO = 1
0∗,
0.01kV to 99.99 kV if PT RATIO > 1
1V to 999V,
0 = disable automatic adjustment of the
0.01kV to
capacitor bank powers to the measured
99.99kV
line voltage (assuming that those have
been adjusted manually)
0.500 to -0.500 Low target power factor for setpoint SP1
0.500 to -0.500 High target power factor for setpoint SP1
0.500 to -0.500 Low target power factor for setpoint SP2
0.500 to -0.500 High target power factor for setpoint SP2
-10000 to 10000
(-750)
-10000 to 10000
(1200)
-10000 to 10000
(-750)
-10000 to 10000
(1200)
1 to 3600 s (3∗)
Low target kvar for setpoint SP1
High target kvar for setpoint SP1
Low target kvar for setpoint SP2
High target kvar for setpoint SP2
The amount of time that the power factor
must be continuously outside the setpoint
range in order to run the automatic power
factor correction
Switch-on time
3 to 3600 s
The amount of idling time after a capacitor
(connection interval), sec
bank switches in, when further switching
(600∗)
operations are prohibited
Switch-off time
3 to 3600 s
The amount of idling time after a capacitor
(disconnection interval),
bank switches out, when further switching
(600∗)
sec
operations are prohibited
Re-connection
5 to 3600 s
The capacitor bank reclose delay to allow
(discharge) time, sec
the capacitors to discharge after
(300∗)
disconnecting
Size of the capacitor
On, nonE,
Power rating of the capacitor bank.
bank #1, kvar
1 to 10000 kvar nonE = not used,
(1500∗)
On = permanently switched in
Size of the capacitor
On, nonE,
Power rating of the capacitor bank.
bank #2, kvar
1 to 10000 kvar nonE = not used,
(1500∗)
On = permanently switched in
Chapter 4 Setup Menus
Code
CAP3
Parameter
Size of the capacitor
bank #3, kvar
CAP4
Size of the capacitor
bank #4, kvar
CAP5
Size of the capacitor
bank #5, kvar
CAP6
Size of the capacitor
bank #6, kvar
CAP7
Size of the capacitor
bank #7, kvar
CAP8
Size of the capacitor
bank #8, kvar
Options
On, nonE,
1 to 10000 kvar
(1500∗)
On, nonE,
1 to 10000 kvar
(1500∗)
On, nonE∗,
1 to 10000 kvar
Description
Power rating of the capacitor bank.
nonE = not used,
On = permanently switched in
Power rating of the capacitor bank.
nonE = not used,
On = permanently switched in
Power rating of the capacitor bank.
nonE = not used,
On = permanently switched in
Power rating of the capacitor bank.
On, nonE∗,
1 to 10000 kvar nonE = not used,
On = permanently switched in
Power rating of the capacitor bank.
On, nonE∗,
1 to 10000 kvar nonE = not used,
On = permanently switched in
Power rating of the capacitor bank.
On, nonE∗,
1 to 10000 kvar nonE = not used,
On = permanently switched in
When the PFC is programmed to operate with two setpoint ranges, the active setpoint
range is selected by the external contact status through the instrument's digital input:
open = SP1, closed = SP2 setpoint range. To sense an external contact status, the
digital input should be configured as a status input (see Section 4.3).
Nominal voltage is shown in units of Volts as a whole number, or in kVolts with two
decimal places.
These parameters appear only if setpoint SP2 is selected as an operational setpoint.
Setting this parameter to 'On' forces a capacitor bank to be permanently switched in
when the PFC is put into an operation mode, and to be switched out when the PFC
shuts down, following all switching and re-close time delays. The permanently switched
banks continue under PFC protection but are not involved into either switching program.
This delay is also used in automatic operation modes as the reference restoration time
when an alarm setpoint override condition takes place followed by the soft release of
the capacitor banks (see Section 4.6). When the alarm condition is no longer present,
the PFC will delay restoration of the automatic switching program for an amount of time
equal to 50 times the power factor setpoint operate delay. This prevents excess cycling
in over-voltage and high harmonics conditions.
NOTES:
1. The PFC setup parameters, except the operation mode, are protected from being
changed while the PFC is running. Ensure that the PFC is OFF before configuring setup
parameters. To disable protection after shutting the PFC down, exit the setup menu,
and then re-enter the menu once more.
2. The PFC may not be put in operation mode if no capacitor banks are specified in the
PFC setup either as controlled or permanently switched banks.
3. The power rating values for the capacitor banks are not allowed to be in descending
order. Each capacitor bank must have the same or higher power value than the
previous bank. When entering the bank powers, the starting value is prompted at equal
to the power of the previous bank and is not permitted to drop below this value.
Chapter 4 Setup Menus
41
4. The target power factor limits are always specified for the I and IV quadrants regardless
of the location of the instrument on the source or load side. The PFC will automatically
account for the direction of power flow providing full four-quadrant operation.
5. If both target power factor limits are specified for the same quadrant, the high power
factor limit should never be less than the low limit. If the target limits are being set for
two quadrants, the lagging (inductive) power factor should be specified as the low limit
and the leading (capacitive) one as the high target limit. Whenever these relations are
not fulfilled, the instrument will automatically adjust the high target power factor to the
low target limit.
42
Chapter 4 Setup Menus
4.14 PFC Manual Mode Menu
SELECT
CHG
PFC.H
ENTER
ENTER
This menu allows you to manually operate (connect or disconnect) the PFC
capacitor banks in progressive order by entering commands from the front panel.
The menu can be only accessed via the Setup Change Menu (CHG) if the PFC is
running in Manual Mode (see Section 4.13, PFC Setup).
When in the Manual Mode menu, the present measured power factor value is
displayed in the upper window, the PFC operation status in the flashing middle
window and measured reactive power in the lower window. Depending on the
selected power factor setpoint trigger, the power factor and reactive power are
based on the true RMS measurements or on the fundamental harmonic values.
The PFC operation status reported in the middle window is explained in Table 4-12.
The up/down arrow keys are used as the command keys and act in Manual Mode
as follows:
Switches in a capacitor bank
Switches out a capacitor bank
The capacitor banks are connected and disconnected progressively from the first
controlled bank to the last, following all pre-set switching and re-connection
delays. Whenever a number of the banks with the same size are available, the
PFC will use at each step the bank that has the minimum number of switching
cycles. A new command will not be accepted until the PFC has completed the
previous command, i.e., until the reported PFC operation status is Ready, Full or Idle.
0.980
rdY
124.5
To switch in a capacitor bank:
Ensure that the PFC is ready, and then press and release the up
arrow key.
To switch out a capacitor bank:
Ensure that the PFC is ready, and then press and release the
down arrow key.
To quit the menu:
Press ENTER or
ESC
.
Table 4-12 PFC Operation Status
Code
rdY
ALAr
buSY
FULL
IdLE
Operation Status
Ready
Alarm
Busy
Full
Idle
Description
A switching program is complete
Operations are stopped by an alarm setpoint
Waiting until a switching delay is expired
All capacitor banks are switched in
All capacitor banks are switched out
NOTE
The Manual Mode commands do not affect the capacitor banks that are defined as
permanently switched banks. These always switch in automatically when the PFC is put into
operation, including in Manual Mode.
Chapter 4 Setup Menus
43
Chapter 5 PFC Setup and Operation
5. PFC Setup and Operation
This chapter describes how to setup the Power Factor Controller for your
application and explains its important features. Brief instructions are included for
certain setup and display operations. Complete setup instructions are found in
Section 4.13, PFC Setup; complete display information is found in Chapter 6
(Data Display) and Chapter 7 (Viewing Status Information).
5.1 Capacitor Bank Control Options
The C192PF8-RPR offers you three options to control capacitor banks in order to
meet the conditions of your electrical equipment and avoid unnecessary
switching. All options may be used at the same time when applied to different
banks.
Automatic Control
This option puts the banks under full PFC control and allows them to be used in
either a manual or automatic PFC switching program.
To put the capacitor bank under PFC control, specify the bank size in kvar to allow for
manual or automatic bank switching (see Section 4.13, PFC Setup).
Manual Control
This option allows some of the banks to be manually switched in using direct
control over the output relays. You can use this option for checking or repairing
capacitor banks.
This option does not use the PFC to control the capacitor banks. Switching is
done outside the PFC by directly forcing the output relays from the front panel
(see Section 4.12, Manual Relay Control Menu) or via communications. The
switched in banks remain connected until they are disconnected manually.
The size of the capacitor banks intended for direct manual control should be set to none
(see Section 4.13, PFC Setup), thus moving them out of the PFC control.
Since the PFC does not manage the capacitor banks, and forcing the output
relays also overrides the common alarm setpoint conditions, neither PFC setpoint
protection nor common alarm setpoints can be used to protect the capacitor
banks against harmful alarm conditions. This should be done separately, outside
the C192PF8-RPR.
Permanently Switched (Non-Programmable) Banks
This option allows some of the banks to be automatically switched in whenever
the PFC is put into operation and to remain permanently connected any time the
PFC is operating. This option is intended to avoid excess cycling of the capacitor
banks that draw near their cycling limit, or to put constant capacitive load onto the
network to avoid non-necessary switching.
44
Chapter 5 PFC Setup and Operation
To specify the bank as a permanently switched bank, set the bank size parameter to On
(see Section 4.13, PFC Setup).
The permanently switched banks are switched in automatically when the PFC is
put into either manual or automatic operation mode and before a switching
program begins, and are switched out when the PFC shuts down, following all
switching and re-connection time delays. These banks remain under PFC
protection but are not involved into either switching program (assumed to be nonprogrammable banks).
5.2 PFC Operation
5.2.1 Modes of Operation
The PFC can operate in three control modes: self-adapting automatic mode,
optimizing automatic mode, and manual mode. Both automatic modes provide
automatic power factor (in Power Factor Controller mode) or reactive power (in
Reactive Power Regulator mode) correction whereby the PFC automatically
accounts for deficient or excessive reactive power and makes necessary
adjustments.
Self-adapting Automatic Mode (Auto 1)
Self-adapting mode is a simple automatic operation mode suitable to most
applications. The PFC switches in additional banks when the measured power
factor lags against the target power factor or the measured reactive power is over
the high target kvar (excessive inductive load is detected), and switches out
redundant banks when the measured power factor leads against the target power
factor limits or the measured reactive power is under the low target kvar
(excessive capacitive load is detected).
The capacitor banks are switched in and switched out progressively, always
starting from the low-size bank available at this step, following the pre-set
switching and re-connection delays.
The self-adapting program is complete when one of the following is true:
1. The measured power factor (in PFC mode) or kvar (in RPR mode) attains the
pre-set PFC setpoint range.
2. In PFC mode, the deviation from the target power factor is less than 0.7 of
the smallest size bank.
Automatic Optimization Mode (Auto 2)
This is a highly optimized operation mode that provides minimum switching
operations. At each step, the PFC accounts for deficient inductive or capacitive
reactive power to attain the target power factor or target kvar and selects the
exact combination of the banks among those presently available that requires the
minimum number of switching operations.
Whenever no combination is found that allows achieving the target setpoint
range, the PFC will select a combination that provides minimum deviation from
Chapter 5 PFC Setup and Operation
45
the target. When no leading (capacitive) target power factor is allowed, only
combinations that provide lagging (inductive) power factor will be checked.
The banks are connected and disconnected starting from the low-size banks,
following all pre-set switching and re-connection delays. Alternation of switching
operations is provided when needed to avoid excessive deviation from the target
power factor.
The optimization program is complete when one of the following is true:
1. The measured power factor (in PFC mode) or kvar (in RPR mode) attains the
pre-set PFC setpoint range.
2. In PFC mode, the deviation from the target power factor is less than 0.7 of
the lowest-size bank.
3. The optimal combination may not be achieved. The controlled power factor
or kvar is brought to the value that is as close as possible to the target.
Manual Mode
This mode can be used for manual adjustment of the power factor or kvar and for
testing purposes. In manual operation mode, power factor or kvar correction is
triggered by user commands entered from the front panel (see Section 4.14, PFC
Manual Mode Menu) or through communications. Each command switches in or
switches out a single capacitor bank. When there are no banks that can be
operated or an alarm condition is present, the user command is discarded.
The banks are switched in and switched out progressively, always starting from
the lowest-size bank available, following the pre-set switching and re-connection
delays.
Manual Mode is a safe, fully protected operation mode provided that the setpoint protection
overrides especially dedicated to the PFC are also operational here. Whenever the
capacitor banks are protected through the alarm setpoints and an alarm override condition
is present, the manual command will be overridden resulting in immediate or soft switch-off
of the capacitor banks.
Changing the Operation Mode
From the PFC setup menu (see Section 4.13, PFC Setup), set the operation mode
parameter to the desired mode. This entry is always enabled unless the PFC is in Shut
Down mode.
Changing from one operation mode to another mode can be done while the PFC
is running, with no need to shut it down. The new program will start immediately
from the present point achieved. No extra cycling will be made if the previous
automatic program was completed. Changing to Manual Mode will stop all
switching operations.
After changing to an automatic mode, the disconnected capacitor banks will be
put into operation after the full discharge time.
The PFC setup options (as well as certain basic configuration options) may not be changed
while the PFC is running.
46
Chapter 5 PFC Setup and Operation
Shutting the PFC Down
From the PFC setup menu, set the PFC operation mode to OFF. This will put the PFC into
Shut Down mode.
Shut Down mode provides step-by-step disconnection of all the capacitor banks
that are under the PFC control. The banks switch out progressively, following
disconnection intervals (switch-off delays). After all the banks are switched out,
the PFC is put into OFF state.
5.2.2 PFC Setpoints
The PFC can operate in Power Factor Controller (PFC) mode or Reactive Power
Regulator (RPR) mode depending on the target setpoint parameter set for the
PFC.
The PFC can provide power factor or reactive power regulation using one of four
measured values as a target setpoint:
- true power factor;
- fundamental’s power factor (displacement) ;
- true reactive power;
- fundamental’s reactive power.
When automatic operation is enabled, PFC operations are triggered automatically
by the PFC setpoint whenever the measured value is outside the user-defined
setpoint range.
PFC Setpoint Trigger
In order to operate reliably under various harmonic conditions, the PFC allows
you to choose one of the following two calculation methods for the power factor or
kvar trigger:
1. True power factor or true kvar based on the true RMS calculations. It
accounts for harmonics through the 15th, and is recommended for electrical
networks where voltage THD is no more than 5%. For higher levels of
harmonics, the power factor and kvar readings will vary too frequently, which
may result in excess cycling of the capacitors unless you drastically increase
the setpoint operate delay.
2. The power factor displacement or fundamental’s kvar based on the
fundamental harmonic measurements. It does not account for presence of
high harmonics and will give stable results in all conditions regardless of the
present harmonics level.
Operational Setpoints
Two target setpoint ranges can be defined, generally, for day and night operation,
which are switched externally through the instrument digital input. They are
designated as setpoints SP1 and SP2.
Unless you do intend to switch the setpoint ranges, specify the operational
setpoints as SP1. In this event, only the setpoint SP1 will be operational, and the
Chapter 5 PFC Setup and Operation
47
PFC will not take into account the status of the digital input. The second setpoint
will not even appear in the PFC setup menu.
If you want to use different target setpoints and switch them depending on the
time schedule or another external condition, specify the operational setpoints as
SP1-2. In this event, both SP1 and SP2 setpoint ranges will be available for
setup, and should be defined for proper operation. The PFC will always consider
the status of the digital input in order to select an appropriate setpoint range:
open = SP1, closed = SP2. Before running the PFC, configure the digital input as
a status input (see Section 4.3).
Power Factor Setpoint Ranges
The setpoint range limits are designated as L.PF1 (low target power factor) and
Hi.PF1 (high target power factor) for the first setpoint, and as L.PF2 and H.PF2
for the second setpoint.
The allowable range for either power factor setpoint is 0.5 (inductive) to -0.5
(capacitive). The default setpoint range is 0.80 to 0.98.
The target power factor limits are always specified for the I (first) and IV (fourth)
quadrants with positive (imported) active power, regardless of the location of the
instrument on the source or load side. The PFC will automatically account for the
direction of power flow providing full four-quadrant operation.
If both target power factor limits are specified for the same quadrant, the high
power factor limit should never be less than the low limit. If the target limits are
being set for two quadrants, the lagging (inductive) power factor should be
specified as the low limit and the leading (capacitive) one as the high target limit.
Whenever these relations are not fulfilled, the instrument will automatically adjust
the high target power factor to the low target limit.
Reactive Power Setpoint Ranges
The setpoint range limits are designated as L.rE1 (low target reactive power) and
Hi.rE1 (high target reactive power) for the first setpoint, and as L.rE2 and H.rE2
for the second setpoint.
The allowable range for either reactive power setpoint is -10,000 (capacitive) to
10,000 (inductive).
The target reactive power limits are always specified for the I (first) and IV (fourth)
quadrants with positive (imported) active power, regardless of the location of the
instrument on the source or load side.
The high reactive power limit should never be less than the low limit. Whenever
this is not fulfilled, the instrument will automatically adjust the high target reactive
power to the low target limit.
PFC Setpoint Operate Delay
The PFC setpoints will not respond to the poor power factor or kvar if the time
that the measured value is outside the setpoint range is less than the user48
Chapter 5 PFC Setup and Operation
defined setpoint operate delay. This makes the trigger less sensitive to fast
changes in load thus avoiding excess switching.
The operate delay timer is reloaded each time the measured power factor
oversteps the setpoint range limits.
The allowable range for the operate delay is 1 to 3600 sec. The default value is 3
sec.
Low Lacking Reactive Power
To avoid excess cycling, the power factor setpoint will not trigger the PFC if the
lacking reactive power is less than 0.7 of the lowest-size bank (usually with no
load or in presence of very low load).
5.2.3 Switching Block Delays
All bank-switching operations are performed following safety block delays in order
to avoid excess transient voltages and currents, and to prevent possible damage
to the contactors and capacitors.
Switch-on Delay (Connection Interval)
This is the amount of time after the capacitor bank switches in during which the
following switching operations are prohibited.
The PFC will not perform either connection or disconnection of the banks until the
switch-on delay timer expires. This avoids multiple switching of the capacitor
banks that would otherwise cause excess current pulses.
The switch-on delay can be adjusted from 3 to 3600 sec. The default setting is
600 sec.
Switch-off Delay (Disconnection Interval)
This is the amount of time after the capacitor bank switches out during which the
following switching operations are prohibited.
The PFC will not perform either connection or disconnection of the banks until the
switch-off delay timer expires. This avoids multiple switching of the capacitor
banks that would otherwise cause excess transient voltages and currents in the
circuits.
The switch-off delay can be adjusted from 3 to 3600 sec. The default setting is
600 sec.
Re-connection (Re-close) Delay
This is the amount of time after the capacitor bank switches out during which the
re-connection of the bank is prohibited, in order to allow the capacitors to
discharge. This avoids bringing the still-charged capacitors back after the voltage
is restored that would otherwise cause permanent damage to the contactors and
the capacitors because of extremely high over-voltage.
Chapter 5 PFC Setup and Operation
49
Normally, the capacitors discharge through fixed resistors that are connected to
the capacitors directly or via auxiliary contacts of the contactors. Refer to the
capacitor data sheet for the recommended discharge time for your capacitors.
The re-connection delay can be adjusted in the range of 3 to 3600 sec. The
default setting is 300 sec.
5.2.4 Arranging the Capacitor Banks
Sizing of the Capacitor Banks
In order to provide reliable operation of the PFC, the sequence of the capacitor
banks should admit different power combinations that must match the reactive
load of your power network. The total power of all capacitor banks should be
sufficient to provide refine power factor correction in worst cases of excessive
inductive load.
It is recommended to use one of the following sequences of the capacitor banks,
where all bank powers are multiples of the power of the first bank:
c, c, c,....c;
c, 2c, 2c,....2c;
c, 2c, 4c,....4c;
etc.
where:
c =
2c =
4c =
etc.
the power of the first capacitor bank, kvar;
twice the power of the first capacitor bank, kvar;
four times the power of the first capacitor bank, kvar;
From the PFC setup menu (see Section 4.13, PFC Setup), specify the power ratings for the
capacitor banks in kvar, progressively, starting from the first sized bank. The capacitor
banks have the same numbers as the output relays to which they must be connected.
The power ratings are not allowed to follow in descending order. Each bank must
have the same or greater size against the previous bank. When entering the bank
power, the starting size is prompted at the power of the previous bank and will not
be allowed to drop below this value.
The sized capacitor banks are not required to occupy adjacent output relays.
They may alternate with permanently switched banks and not connected banks
(see Section 5.1). In all cases, the first bank sized in kvar will be taken as the
reference bank for PFC operations, and all sized banks will be treated in one
sequence.
Adjusting the Bank Rated Power to the Operating Voltage
The PFC calculates the network response to switching operations using the bank
rated powers, normally given for the nominal (rated) voltage. Since the power of
the capacitor banks extremely depends on the operating voltage, the PFC needs
to adjust bank rated powers to the true operating voltage in the circuits.
50
Chapter 5 PFC Setup and Operation
The C192PF8-RPR allows you to choose between manual and automatic
adjustment of the capacitor bank powers. If you choose to make this manually,
specify the bank nominal voltage in the PFC setup as zero, and then enter the
reactive powers for each bank being recalculated for the operating voltage of the
banks, as follows:
Q = Qr
V2
Vn2
where:
Q
Qr
V
Vn
-
reactive power of the bank, kvar
rated reactive power of the bank, kvar
operating voltage, V
nominal (rated) voltage of the bank, V
If you allow for automatic adjustment of the bank powers, specify in the PFC
setup the nominal voltage of your capacitor banks and the individual rated power
for each capacitor bank. PFC will automatically account for the measured
operating voltage to adjust the capacitor bank powers.
5.2.5 Relay Operation (Switching Cycle) Counters
In all modes of operation, the PFC tries to equate cycling for the banks with the
same size. Whenever a number of the banks with the equal power are available,
the PFC will use the bank that has the minimum number of switching cycles.
In order to control cycling of the capacitor banks and the contactors used for
capacitor switching, the PFC maintains the individual operation counter (switching
cycle counter), for each output relay. The cycle counter contains the number of
complete switching cycles of the bank. The PFC updates the counter when it
switches in the corresponding bank.
The present status of the cycle counters can be inspected through the Status
Information Menu (see Chapter 7) or via communications. Each counter can be
cleared individually or all counters together by a single operation (see Section
4.11 and Chapter 7).
Chapter 5 PFC Setup and Operation
51
5.3 Capacitor Banks Protection
5.3.1 PFC Protective Actions
The reason for the PFC protection mechanism is to protect the capacitor banks
and contactors against harmful conditions that would lead to extremely high overvoltage, or would cause undesirable effects such as high transient voltages and
currents and high harmonics. The effect of the PFC protection is automatic
disconnection of the capacitor banks that should occur immediately in the event
of danger to capacitors, or progressively, in less dangerous situations, until alarm
conditions disappear (with minimal cycling whenever possible).
In the C192PF8-RPR, all protective functions are provided through the universal
mechanism of programmable alarm setpoints (see Section 4.6, Alarm/Event
Setpoints Menu).
The PFC itself has no embedded protection functions that may automatically disconnect
the capacitor banks in such situations. With no setpoint protection, the capacitor banks will
remain unprotected against damaging conditions unless external protection is used.
Any number of the 16 programmable setpoints can be used for PFC protection.
Section 5.3.2 provides instructions on how to program certain highly
recommended setpoints for typical alarm conditions. Notice that the effect of the
setpoints does not depend on their order in the setpoint list.
Protection of the capacitors against short circuits should be carried out separately using
either fuses or switches with over-current protection.
The three following setpoint actions are specially intended for the use with the
PFC alarm protection setpoints.
Hard Switch-Off
When alarm override condition is detected, the Hard Switch-Off action
immediately switches out all the capacitor banks including those defined as
permanently switched in. When used with the No-Volt trigger condition (see Table
4-7), this action provides the fastest possible response to voltage interruptions.
Soft Switch-Off
The Soft Switch-Off action switches off the capacitor banks progressively in preset disconnection intervals, while the alarm condition is present. This allows
circumventing over-voltage or high harmonics conditions with minimum cycling of
the capacitor banks. The banks that are defined as permanently switched in are
not affected. After the alarm condition, the PFC will return to automatic operation
after the safety delay which is 50 times the power factor setpoint operate delay.
Stop (Freeze) PFC
This action freezes automatic operation of the PFC until the alarm condition
disappears. No switching operations on the capacitor banks will be performed.
This action does not affect operations in manual mode.
52
Chapter 5 PFC Setup and Operation
5.3.2
PFC Protection Setpoints
Protection against Voltage Interruptions
The fast disconnection of the capacitor banks is required in the event of shortterm voltage interruptions that would cause damage to the still-charged
capacitors when the voltage is restored.
The No-Volt alarm override condition (see Table 4.6) along with the Hard SwitchOff action can de-energize the output relays in approximately 25 ms whenever
voltage interruption is detected.
From the Event/Alarm Setpoints Menu, set the setpoint parameters as follows:
Trigger
Operate Limit
Release Limit
Operate Delay
Release Delay
Action
=
=
=
=
=
=
no-U
none
none
0
3.0 sec
Hrd.OF
The setpoint release delay defines the amount of time before the PFC returns to
normal operation after the alarm. Set it to a non-zero value (3.0 sec in the above
example).
Over-voltage Protection
Over-voltage override condition prevents damage to capacitors at high voltage
increases that would be caused by faulty connections of the capacitors or by
voltage resonance at a higher frequency.
The high voltage override condition along with the Soft Switch-Off action is
recommended for over-voltage protection. The setpoint can respond to high
measured voltage over 120% of the operating voltage with response time of 0.3
to 300 sec. The setpoint is released without a delay when the voltage returns to a
level of 105-110% of the operating voltage. To avoid non-necessary
disconnecting of the banks, the setpoint is released immediately when the alarm
condition disappears.
From the Event/Alarm Setpoints Menu, set the setpoint parameters as follows (example):
Trigger
Operate Limit
Release Limit
Operate Delay
Release Delay
Action
=
=
=
=
=
=
r.hi. U
115-120% of the operating voltage
110% of the operating voltage
10 sec
0
SFt.OF
After the alarm, the PFC will not return to automatic operation for a period of time that is
50 times the power factor setpoint operate delay.
Chapter 5 PFC Setup and Operation
53
Protection against High Harmonics
High THD protection prevents damage to capacitors at high levels of voltage
harmonics, which can be caused by voltage resonance at a higher frequency.
The effect of the high THD setpoint protection is limited progressive disconnection
of the capacitor banks until resonance conditions disappear, and then, after a
long safety delay, returning the PFC into normal operation.
The setpoint can operate at high THD of 3 to 300% depending on the network
conditions with a delay of 0.3 to 300 seconds. The setpoint is released when the
voltage THD drops to a level of 10-20% of the setpoint operate limit. To avoid unnecessary disconnecting of the banks, the setpoint is released without a delay.
From the Event/Alarm Setpoints Menu, set the setpoint parameters as follows (example):
Trigger
Operate Limit
Release Limit
Operate Delay
Release Delay
Action
=
=
=
=
=
=
r.thd.U
5-10%
4-5% of the Operate Limit
20 sec
0
SFt.OF
After the alarm, the PFC will not return to automatic operation for a period of time that is
50 times the power factor setpoint operate delay.
Protection by External Triggers
A protection setpoint can also be used to disconnect the capacitor banks in
response to an external contact status provided through the instrument status
input. This may be useful in substations with generators or large synchronous
motors that generate a large amount of reactive power. The contact should be
closed if generators or motors are working and opened if they are not working.
The control signal can be provided from normally open auxiliary contacts of the
start-up contactors.
From the Event/Alarm Setpoints Menu, set the setpoint parameters as follows (example):
Trigger
Operate Limit
Release Limit
Operate Delay
Release Delay
Action
54
=
=
=
=
=
=
St. On
none
none
5 sec
1 sec
Hrd.OF or SFt.OF
Chapter 5 PFC Setup and Operation
Chapter 6 Data Display
6.
6.1 Navigating in the Display Mode
The front panel has a simple interface that allows you to display numerous
measurement parameters in up to 43 display pages. For easier reading, the
parameters are divided into three groups, each accessible by a designated key.
These are:
Common measurements
Min/Max measurements
Total Harmonic measurements
Energy measurements
-
no selection key
selected by the MAX/MIN key
selected by the THD/TDD key
selected by the ENERGY key
The up/down arrow keys are used as follows in the Display Mode:
Scrolls through the pages downward (forward)
Scrolls through the pages upward (backward)
Returns to the first page within current measurement group
When pressed for 5 seconds, clears the alarm LED
Relay status bar indicates relays
currently switched on
small LEDs indicate current
measurement
group and
parameter
Communication LEDs
Round LEDs - indicate
measurement group
Alarm/Manual Mode LED:
constantly lit=Alarm
blinking=PFC manual mode
The front panel display is updated approximately twice per second; you can
adjust the display update rate via the Display Setup Menu (see Section 4.8).
Table 5-1 lists all displayed parameters and their LED indicators.
Relay Status Bar
The relay status bar displays the present status of the relays. When a relay is
activated (switched on) the corresponding LED is lit.
Chapter 6 Data Display
55
Alarm/Man Mode LED
This LED has two functions. The blinking LED indicates that the PFC is operating
in Manual Mode.
The constantly lit LED gives you an alarm indication. It is controlled by the
alarm/event setpoints (see Section 4.6) and operates in latched mode. Even if
alarm conditions are no longer present, the alarm LED will continue to warn. To
clear the alarm LED, press the up and down arrow keys simultaneously for 5
seconds.
Auto Scroll
If display Auto Scroll option is enabled (see Section 4.8), the common
measurements display (main screen) will scroll automatically after 30 seconds of
uninterrupted use.
To stop auto scrolling at the current page, press either arrow key.
Auto Return to the Main Screen
If display Auto Return option is enabled (see Section 4.8), the display will
automatically return to the main screen from any other measurement screen after
30 seconds of uninterrupted use.
Fast Reset of Accumulated Data
When changing data via the front panel is not secured by a password, you can
reset the Min/Max registers, maximum demands and energies from the display
mode without entering the reset menu.
NOTES
1. The common measurements display does not have a designated indicator LED. If no
indicator LED is lit up below the display, this means that the common measurement
parameters are being displayed at this time. To return to the common measurements
from another group, just press the same key that you used to display this group (the key
pointed to by an illuminated LED) until the illuminated LED goes out.
2. When you move to another measurement group, the instrument stores your last
location; when you return to the previous group, the instrument restores the last page.
At power up, the instrument always returns to the common measurements group and
shows you the last page that was displayed prior to loss of power.
Selecting a Display Page
Press the down/up arrow keys to scroll through display pages.
Selecting Common Measurements
Press the key pointed to by the illuminated round LED below the front panel
display. If no LED is lit up, this means that the front panel displays the common
measurements parameters.
Selecting Min/Max Measurements
Press the MAX/MIN key. Use the up/down arrow keys to scroll through
Min/Max measurements.
56
Chapter 6 Data Display
Selecting Total Harmonic Measurements
Press the THD/TDD key until the THD or TDD LED is illuminated. Use the
up/down arrow keys to scroll through the different harmonic parameters.
Selecting Energy Measurements
Press the ENERGY key. Use the up/down arrow keys to scroll through the
different energy readings.
Fast Reset of Accumulated Data
Select a display page where the data you want to reset is displayed. To reset:
• Min/Max log registers: select a Min/Max page from the Min/Max
measurements display (where a MAX or MIN round LED is illuminated).
• Ampere and volt maximum demands: select the ampere or volt maximum
demand page from the Min/Max measurements display (where a MAX DMD
LED is illuminated, and volts or amps LEDs at the right are lit).
• Power maximum demands: select the power maximum demand page from
the Min/Max measurements display (where a MAX DMD LED is illuminated,
and kVA/MVA and kW/MW LEDs at the right are lit).
• Total and phase energies: select the energy measurements display.
While holding the SELECT key, press and hold
The displayed data is reset to zero.
ENTER
for about 5 seconds.
6.2 Data Display Formats
Table 5-1 specifies all front panel local displays available in the display mode.
The display windows are labeled in the table as follows: 1 = upper window, 2 =
middle window, 3 = lower window.
Table 5-1 Displayed Parameters
Page
Window
1
1
2
3
1
2
3
1
2
3
1
2
3
2
3
4
Chapter 6 Data Display
Indicator
LED
PF
kVA
kvar
V1/V1-2
V2/V2-3
V3/V3-1
V1/V1-2
V2/V2-3
V3/V3-1
A1
A2
A3
Parameter
Digits
Unit
Common Measurements
Total power factor
Total kVA
Total kvar
Voltage L12
Voltage L23
L. Voltage L31
Voltage L1
Voltage L2
P. Voltage L3
Current L1
Current L2
Current L3
4
4
4
4
4
4
4
4
4
4
4
4
kVA/MVA
kvar/Mvar
V/kV
V/kV
V/kV
V/kV
V/kV
V/kV
A
A
A
57
Page
Window
5
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
3
1
3
6
7
8
9
10
11
12
13
14
15
16
17
18
1
58
1
2
3
Indicator
LED
A NEUT
Hz
kW
PF
kW
kVA
kvar
PF
kW
kVA
kvar
PF
kW
kVA
kvar
PF
kvar
kVA
kW
PF
kW
PF
kW
PF
kW
MIN
V1/V1-2
V2/V2-3
V3/V3-1
Parameter
Digits
Neutral current
Frequency
Total kW
Power factor L1
Ph.L1
kW L1
kVA L1
Ph.L1
kvar L1
Power factor L2
Ph.L2
kW L2
kVA L2
Ph.L2
kvar L2
Power factor L3
Ph.L3
kW L3
kVA L3
Ph.L3
kvar L3
H01 total power factor
H01 (Fundamental harmonic)
Total kvar
H01 (Fundamental harmonic)
H01 total kVA
H01 total kW
H01 power factor L1
H1.L1
H01 kW L1
H01 power factor L2
H1.L2
H01 kW L2
H01 power factor L3
H1.L3
H01 kW L3
U.Unb
Voltage unbalance
C.Unb
Current unbalance
Min/Max Measurements
4
4
4
4
Min. real-time voltage L1/L12
Min. real-time voltage L2/L23
Min. real-time voltage L3/L31
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
Unit
A
Hz
kW/MW
Label
kW/MW
kVA/MVA
Label
kvar/Mvar
Label
kW/MW
kVA/MVA
Label
kvar/Mvar
Label
kW/MW
kVA/MVA
Label
kvar/Mvar
Label
kvar/Mvar
Label
kVA/MVA
kW/MW
Label
kW/MW
Label
kW/MW
4
Label
kW/MW
Label
%
Label
%
4
4
4
V/kV
V/kV
V/kV
4
4
Chapter 6 Data Display
Page
Window
2
1
2
3
1
2
3
1
2
3
3
4
5
6
7
8
9
10
11
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
2
1
3
1
2
3
1
2
3
1
2
3
Chapter 6 Data Display
Indicator
LED
A1
A2
A3
PF
kVA
kvar
A NEUT
Hz
kW
MAX
V1/V1-2
V2/V2-3
V3/V3-1
A1
A2
A3
PF
kVA
kvar
A NEUT
Hz
kW
MAX DMD
V1
V2
V3
A1
A2
A3
PF
kVA
kW
THD
V1/V1-2
V2/V2-3
V3/V3-1
A1
A2
A3
TDD
A1
A2
A3
Parameter
Digits
Min.
Min.
Min.
Min.
Min.
Min.
Min.
Min.
Min.
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
current L1
current L2
current L3
total power factor
total kVA
total kvar
neutral current
frequency
total kW
4
4
4
4
4
4
4
4
4
Max.
Max.
Max.
Max.
Max.
Max.
Max.
Max.
Max.
Max.
Max.
Max.
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
real-time
voltage L1/L12
voltage L2/L23
voltage L3/L31
current L1
current L2
current L3
total power factor
total kVA
total kvar
neutral current
frequency
total kW
4
4
4
4
4
4
4
4
4
4
4
4
Unit
A
A
A
kVA/MVA
kvar/Mvar
A
Hz
kW/MW
V/kV
V/kV
V/kV
A
A
A
kVA/MVA
kvar/Mvar
A
Hz
kW/MW
Max. volt demand L1/L12
Max. volt demand L2/L23
Max. volt demand L3/L31
Max. ampere demand L1
Max. ampere demand L2
Max. ampere demand L3
Power factor at max. kVA demand
Max. sliding window kVA demand
Max. sliding window kW demand
Total Harmonic
Measurements
4
4
4
4
4
4
4
4
4
V/kV
V/kV
V/kV
A
A
A
Voltage
Voltage
Voltage
Current
Current
Current
4
4
4
4
4
4
%
%
%
%
%
%
4
4
4
%
%
%
THD
THD
THD
THD
THD
THD
L1/L12
L2/L23
L3
L1
L2
L3
Current TDD L1
Current TDD L2
Current TDD L3
kVA/MVA
kW/MW
59
Page
Window
1
1
2
3
1
2
3
1
3
1
2
3
1
2
3
MWh
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
MWh
2
3
4
5
6
7
8
9
10
11
12
13
14
Indicator
LED
Mvarh
MVAh
MWh
Mvarh
Mvarh
MVAh
MWh
Mvarh
MVAh
MWh
Mvarh
MVAh
Parameter
Total Energies
Ac.En.
IP.
MWh import
rE.En.
IP.
Mvarh import
AP.En.
MVAh
Ac.En.
EP.
MWh export
rE.En.
EP.
Mvarh export
Phase Energies
Ac.En.
IP.L1
MWh import L1
rE.En.
IP.L1
Mvarh import L1
AP.En.
L1
MVAh L1
Ac.En.
IP.L2
MWh import L2
rE.En.
IP.L2
Mvarh import L2
AP.En.
L2
MVAh L2
Ac.En.
IP.L3
MWh import L3
rE.En.
IP.L3
Mvarh import L3
AP.En.
L3
MVAh L3
Digits
5
5
5
5
5
5
5
5
5
5
5
5
5
5
Unit
Label
Label
MWh
Label
Label
Mvarh
Label
MVAh
Label
Label
MWh
Label
Label
Mvarh
Label
Label
MWh
Label
Label
Mvarh
Label
Label
MVAh
Label
Label
MWh
Label
Label
Mvarh
Label
Label
MVAh
Label
Label
MWh
Label
Label
Mvarh
Label
Label
MVAh
Display readings for all electrical quantities except Min/Max log and energies are
sliding average values.
60
Chapter 6 Data Display
When using direct wiring (PT Ratio = 1), voltages are displayed in 0.1 V units, currents
in 0.01 A units, and powers in 0.001 kW/kvar/kVA units. For wiring via PTs (PT Ratio >
1), voltages are displayed in 1V units, currents in 0.01 A units, and powers in 0.001
MW/Mvar/MVA units. When the value width is over the window resolution, the right
most digits are truncated
By default, the maximum range for energy readings is 99,999,999 MWh/Mvarh/MVAh.
Beyond this value, the reading will roll over to zero. When the energy reading exceeds
the window resolution, the right-most digits are truncated. To avoid truncation, you can
change the energy roll value to lower limit via the User Selectable Options menu (see
Section 4.9). Negative (exported) energy readings are displayed without a sign.
Per phase power and power factor readings are displayed only in 4LN3/4LL3 and
3LN3/3LL3 wiring modes (see Section 4.1) if the phase powers display is enabled in
the Display Setup menu (see Section 4.8).
Phase energy readings are displayed only in 4LN3/4LL3 and 3LN3/3LL3 wiring modes if
they are enabled in the User Selectable Options menu (see Section 4.9).
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for
any other wiring mode, they will be line-to-line voltages.
Displayed only in the 4LN3 or 3LN3 wiring mode.
6.3 Device Diagnostics Display
When the device restarts, either after power up, or as a result of the device
diagnostics test, the C192PF8-RPR display shows for one second the diagnostics
code. Diagnostics codes are listed in Table 5-2. Code ‘8’ indicates normal power
up.
Table 5-2 Self-Test Diagnostics Codes
Code
2
3
4
5
7
8
9
Meaning
RAM error
Watch dog timer reset
Sampling failure
CPU exception trap
Software exception trap
Normal power up
External reset (warm restart)
The C192PF8-RPR performs full diagnostics tests after restart and periodically
during operation. The diagnostics results are written to the appropriate bits of the
device self-check diagnostics register accessible through communications (see
the communications reference guides shipped with your instrument). When a
non-critical error is detected, the C192PF8-RPR sets a corresponding fault bit in
the diagnostics register and restart operations showing the last recorded
diagnostics code on the display. Frequent failures may be the result of excessive
electrical noise in the region of the instrument. If the instrument continuously
resets itself, contact your local distributor.
Chapter 6 Data Display
61
When the device detects a corrupted configuration setup or incompatible setup
setting, it sets a corresponding fault bit in the diagnostics register, resets the
corrupted setup to default and rises a critical (unrecoverable) error. Diagnostics
status can be viewed through the Status Information Menu (see Section 7.2), and
tested through a setpoint via the Device Fault trigger. The device fault is cleared
when the setup is rewritten, or device diagnostics is cleared either through the
Status Information Menu (see Section 7.1), or through communications.
62
Chapter 6 Data Display
Chapter 7 Viewing Status Information
7.
Through the Status Information Menu (StA), it is possible to view the status of various
instrument features.
7.1 The Status Information Menu
StA
SELECT
ENTER
To enter the Status Information Menu:
From the display mode, press SELECT to enter the Primary Selection Menu.
Press SELECT to activate the StA window.
Press ENTER . .
To select a display page:
Press the up/down arrow keys to scroll through the display pages.
To quit the menu and return to the display mode:
Press
ESC
or
ENTER
.
Front Panel Display
When you are in the Status Information Menu, the front panel display is updated
approximately four times per second and shows you a wide variety of status
information that you can review by scrolling through display pages.
The abbreviated labels in the upper and/or middle window designate the status
parameters. The upper window flashes, indicating that you are in the Status
Information Menu display.
Fast Reset of Counters
When changing data via the front panel is not secured by a password, you can
reset the counters from the Status Information Menu display without entering the
reset menu:
Select a display page where the counter you want to reset is displayed.
While holding the SELECT key, press and hold ENTER for about 5 seconds.
The displayed data is reset to zero.
Reset of Device Diagnostics
To clear the device diagnostics:
Select the Device diagnostics page.
While holding the SELECT key, press and hold
until the Err message is reset to None.
Chapter 7 Viewing Status Information
ENTER
for about 5 seconds
63
7.2 Status Display Formats
Table 7-1 lists all the displays available from the Status Information Menu. The
display windows are labeled in the table as follows: 1 = upper window, 2 = middle
window, 3 = lower window.
Table 7-1 Status Information Display
Page
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
64
Window
1
2
3
1
2
3
1
2
3
1
2
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
1
3
Parameter
PFC
PFC operation mode (see Table 7-2)
PFC operation status (see Table 7-3)
diAG
Device diagnostics: Err (device fault)/nonE
PHAS
rOt
Phase rotation sequence (POS/NEG/ERR)
rEL
Relay #1 - #4 status
Relay #5 - #8 status
St.In
Status input
Cnt.1
Event/Time counter #1
Cnt.2
Event/Time counter #2
Cnt.3
Event/Time counter #3
Cnt.4
Event/Time counter #4
CYC.1
PFC relay operation (switching cycle) counter
CYC.2
PFC relay operation (switching cycle) counter
CYC.3
PFC relay operation (switching cycle) counter
CYC.4
PFC relay operation (switching cycle) counter
CYC.5
PFC relay operation (switching cycle) counter
CYC.6
PFC relay operation (switching cycle) counter
CYC.7
PFC relay operation (switching cycle) counter
CYC.8
PFC relay operation (switching cycle) counter
Digits
Unit
Label
4
4
Label
4
Label
Label
4
Label
4
4
Label
1
Label
5
Label
5
Label
5
Label
5
Label
#1
5
#2
5
#3
5
#4
5
#5
5
#6
5
#7
5
#8
5
Label
Label
Label
Label
Label
Label
Label
Chapter 7 Viewing Status Information
Table 7-2 PFC Operation Modes
Code
OFF
Sh.dn
Aut.1
Aut.2
HAnd
Operation Mode
The PFC is switched OFF
The PFC is shutting down
Self-adapting automatic operation mode
Optimizing automatic operation mode
Manual operation mode
Table 7-3 PFC Operation Status
Code
ready
ALAr
busy
Lo.rEA
Ind.L
CAP.L
FULL
IdLE
OFF
Operation Status
Ready
Alarm
Busy
Low reactive power
(automatic mode)
Excessive inductive load
(automatic mode)
Excessive capacitive load
(automatic mode)
Full (manual mode)
Idle (manual mode)
OFF
Chapter 7 Viewing Status Information
Description
A switching program is complete
Operations are stopped by an alarm setpoint
Waiting until a switching delay is expired
Insufficient reactive power to trigger PFC
Non-compensated inductive load
Non-compensated capacitive load
All capacitor banks are switched in
All capacitor banks are switched out
The PFC is switched off
65
Appendix: Technical Specifications
8. ions
Input and Output Ratings
3 galvanically
690 V:
isolated voltage (standard)
inputs
120 V:
(optional)
3 galvanically
5 A:
isolated current (standard)
inputs
1 A:
(optional)
Voltage and current input
terminals
Optically isolated
communication port
Relay outputs
Analog output (optional)
4-20 mA
0-20 mA
Status input
Display
Galvanically isolated power
supply (factory set)
120&230V AC / 120&220 V DC
12 V DC
24 V DC
48 V DC
66
DIRECT INPUT (690V + 15% line-to-line voltage and
400V +15% line-to-neutral) Burden: <0.5 VA
INPUT USING PT Burden: <0.15 VA
INPUT USING PT (120V +20% line-to-line voltage)
Burden: <0.1 VA
Maximum 6A RMS
Burden: <0.1 VA
Overload withstand: 10A RMS continuous, 250A RMS for
1 second
Maximum 1.2 A RMS Burden: <0.02 VA
Overload withstand: 2A RMS continuous, 50A RMS for 1
second
UL recognized Screws: Brass, M4
Maximum wire section: 2.5 mm2 (12 AWG)
EIA RS-485 or RS-232 standard (factory set)
RS-232: point-to-point, up to 15 meters
RS-485: multidrop, up to 32 loads, up to 1200 meters
(4000 ft.)
2
Maximum wire section: 1.5 mm (14 AWG)
5 relays rated at 5A, 250 V AC / 5A, 30 V DC / 0.5A, 110
V DC 2 contacts (SPST Form A)
1 relay rated at 5A, 250 V AC / 5A, 30 V DC / 0.5A, 110
V DC
3 contacts (SPDT Form C)
2 relays rated at 3A, 250 V AC / 3A, 30 V DC / 0.5A, 110
V DC 2 contacts (SPST Form A)
Maximum wire section: 1.5 mm2 (16 AWG)
Accuracy 0.5%, Non-linearity 0.2%
Load up to 510 Ohm
24V DC external power supply required
Dry contact for external synchronization or monitoring
Maximum impedance on: 300 ohm
3 windows, high-brightness seven-segment digit LEDs
Color relay status LED
85-265V AC 50/60 Hz and 88-290V DC 10 W
9.6 - 19 V DC
19 - 37 V DC
37 - 72 V DC
Appendix: Technical Specifications
Environmental Conditions
Operating temperature
-20°C to +60°C (-4°F to +140°F)
Storage temperature
-25°C to +80°C (-13°F to +176°F)
0 to 95% non-condensing
Humidity
Construction
Instrument body
Case enclosure: flame resistant ABS & Polycarbonate Blend
Dimensions: 144 x 144 x 86 mm ( 5.67 x 5.67 x 3.39 “)
Mounting: 136 x 136 mm square cut-out (DIN 43700)
Instrument weight
0.9 kg (2.04 lb.)
Standards Compliance
UL File # E129258 Pending
CE:
EMC: 89/336/EEC as amended by 92/31/EEC and 93/68/EEC
LVD: 72/23/EEC as amended by 93/68/EEC and 93/465/EEC
Harmonized standards to which conformity is declared:
EN55011:1991; EN50082-1:1992; EN61010-1:1993; A2/1995
Installation Category II, Pollution Degree 2
EN50081-2:1994 EMC Generic Emission Standard - Industrial Environment
EN50082-2:1995 EMC Generic Immunity Standard - Industrial Environment
EN55022: 1994 Class A
EN61000-4-2: 1995 Electrostatic Discharge
EN61000-4-4: 1995 Electrical Fast Transient
EN61000-4-8: 1993 Power Frequency Magnetic Field
ENV50140: 1993 Radio Frequency Electromagnetic Field, Amplitude Modulated
ENV50204: 1995 (200Hz) Radio Frequency Electromagnetic Field, Pulse
Modulated
ENV50141: 1993 Radio Frequency Common Mode, Amplitude Modulated
ANSI C37.90.1: 1989 Surge Withstand Capability
ANSI IEEE C62.41-1991 Surge Voltages in Low-Voltage AC Power Circuits
Appendix: Technical Specifications
67
Measurement Specifications
Parameter
Voltage
Line current
Full scale
120V×PT
@ 120V
or
400V×PT
@ 690V
Rdg
For Ln reading
and for
3OP2/3OP3
wiring modes
Accuracy, %
Range
FS Conditions
0.25 10% to 120% FS 0 to 999,000 V
Display resolution (%Rdg)
@ range
Direct wiring (PT=1):
0.1 V @ 0.1V to 999.9 V
Wiring via PTs (PT>1):
0.001 kV @ 0.001kV to 9.999 kV
≤0.1% @ 10.00 kV to 999.0 kV
208V×PT
For LL reading
@ 120V
or except
3OP2/3OP3
690V×PT
wiring modes
@ 690V
CT PRIMARY CURRENT
Starting voltage 1.5% FS
0.25 2% to 120% FS
0 to 9999 A
Active power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
-2,000,000 to
+2,000,000 kW
Reactive power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≤ 0.9
-2,000,000 to
+2,000,000 kvar
Apparent power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
0 to
2,000,000 kVA
Power factor
1
1
|PF| ≥ 0.5,
I ≥ 10% FSI
-0.999 to +1.000
Frequency
68
0.02
0.01 A @ 0.01A to 99.99 A
≤0.1% @ 100.0 A to 9999 A
Starting current 0.5% FS
Direct wiring (PT=1):
0.001 kW @ 0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW @ 0.001MW to 9.999 MW
≤0.1% @ 10.00 MW to 2000 MW
Direct wiring (PT=1):
0.001 kvar @ 0.001kvar to 9.999 kvar
Wiring via PTs (PT>1):
0.001 Mvar @ 0.001Mvar to 9.999 Mvar
≤0.1% @ 10.00 Mvar to 2000 Mvar
Direct wiring (PT=1):
0.001 kVA @ 0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA @ 0.001MVA to 9.999 MVA
≤0.1% @ 10.00 MVA to 2000 MVA
0.001
45.00 to 65.00 Hz 0.01 Hz
Appendix: Technical Specifications
Parameter
Neutral (unbalanced)
current
Full scale
CT PRIMARY CURRENT
Rdg
Accuracy, %
FS Conditions
0.5 2% to 120% FS
Range
0 to 9999 A
Display resolution (%Rdg)
@ range
0.01 A @ 0.01A to 99.99 A
≤0.1% @ 100.0 A to 9999 A
Starting current 0.5% FS
Ampere demand
KW demand (block & sliding)
KVA demand (block & sliding )
999.9
Total Harmonic
Distortion
THD U (I), % U1 (I1)
100
Total Demand
Distortion TDD (I), %
Active energy
Import & Export
same as for current
same as for kW
same as for kVA
0 to 999.9
0.1
1.5
0.2 ≥ 0.1% FS,
U (I) ≥ 10% FSU
(FSI)
0 to 100
0.1
1.5 ≥ 1% FSI,
I ≥ 10% FSI
0 to 99,999 MWh 1 kWh @ 1 to 99,999 kWh
same as for power
10 kWh @ 100 to 999.99 MWh
100 kWh @ 1,000 to 9,999.9 MWh
1MWh @ 10,000 to 99,999 MWh
0 to 99,999 Mvarh 1 kvarh @ 1 to 99,999 kvarh
Reactive energy
same as for power
Import & Export
10 kvarh @ 100 to 999.99 Mvarh
100 kvarh @ 1,000 to 9,999.9 Mvarh
1Mvarh @ 10,000 to 99,999 Mvarh
0 to 99,999 MVAh 1 kVAh @ 1 to 99,999 kVAh
Apparent energy
same as for power
10 kVAh @ 100 to 999.99 MVAh
100 kVAh @ 1,000 to 9,999.9 MVAh
1MVAh @ 10,000 to 99,999 MVAh
PT = external potential transformer ratio
CT, CT Primary Current = primary current rating of external current transformer
FSI = current full scale
U1 = voltage fundamental
FSU = voltage full scale
I1 = current fundamental
@ 10% to 120% of voltage FS and 2% to 120% of current FS
Higher resolution is achievable via communications
Where the current is > 10% FS, the energy accuracy is better than 1.5% Rdg.
Additional Notes
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not include inaccuracies introduced
by the user's potential and current transformers.
2. Specifications assume: voltage and current wave forms with THD ≤ 5% for kvar, kVA and PF; reference operating temperature: 20 - 26°C.
3. Ordinary measurement error is considerably less than the specified accuracy which indicates maximum error.
Appendix: Technical Specifications
69
Index
A
accuracy, 70
active energy, 4, 70
active power, 3, 4, 35, 69
alarms, 14
ampere demand, 21, 30, 60
analog output, 2, 5, 8, 15, 24, 25
analog outputs, 22
B
basic setup, 20, 39
burden, 67
C
communications, 70
controller, 55
CT, 2, 21, 22, 25, 33, 69, 70
CT PRIMARY CURRENT, 22, 69, 70
current inputs, 8, 67
current transformers, 70
mounting, 1, 7
O
open delta, 10, 21, 39, 40
options, 15
overload withstand, 67
P
panel cut-out, 7
password, 2, 18, 36, 37, 57, 64
PComTest, 20
power, i, 2, 3, 4, 8, 15, 21, 22, 23, 24, 32, 34,
35, 37, 38, 50, 51, 55, 57, 58, 59, 60, 62,
63, 67, 69, 70
power demand, 3, 4, 15, 21, 23, 37, 38
power factor, 1, 50, 55, 69
power source, i, 8
power supply, 67
PT, 8, 21, 22, 25, 26, 62, 67, 69, 70
PT RATIO, 22
pulsing, 2, 14, 26, 27, 28, 32, 33, 38
D
demand, 3, 4, 15, 21, 23, 25, 30, 37, 38, 58,
60, 70
demand period, 15, 21, 38
display, 1, 2, 32, 33, 34, 38, 45, 56, 57, 58,
62, 64, 65
display mode, 33, 38, 57, 58, 64
E
energy, 1, 2, 3, 4, 14, 26, 27, 35, 58, 62, 70
external synchronization, 3, 15, 21, 23, 67
F
frequency, 1, 3, 4, 21, 29, 30, 60, 69
R
reactive energy, 4, 70
reactive power, 3, 4, 34, 35, 55, 69
relays, 2, 14, 26, 32, 67
reset, 21, 35, 37, 57, 58, 62, 64
S
self tests, 62
setpoints, 22, 27, 28, 31, 32, 57
setup menus, 18, 20
setup mode, 18
sliding demand, 4
standards, 67, 68
status, 1, 3, 15, 18, 23, 31, 36, 55, 64, 65
I
inputs, 23, 67
L
T
technical specifications, 67
terminals, ii, 8, 67
V
Load bar graph, 56
M
measurement, 70
menu, 18, 20, 22, 23, 24, 26, 27, 28, 32, 33,
34, 36, 37, 38, 39, 43, 62, 64
Modbus, ii, 17, 21, 22
70
voltage inputs, 67
W
wiring configuration, 5, 8, 10
Wye, 10, 21, 39
Index

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement