ProSoft Technology MVI69E MBS communication module User manual
광고
광고
MVI69E-MBS
CompactLogix Platform
Modbus Serial Enhanced
Communication Module
USER MANUAL
June 28, 2017
Your Feedback Please
We always want you to feel that you made the right decision to use our products. If you have suggestions, comments, compliments or complaints about our products, documentation, or support, please write or call us.
ProSoft Technology
9201 Camino Media, Suite 200
Bakersfield, CA 93311
+1 (661) 716-5100
+1 (661) 716-5101 (Fax) www.prosoft-technology.com [email protected]
MVI69E-MBS User Manual
June 28, 2017
ProSoft Technology
®
, is a registered copyright of ProSoft Technology, Inc. All other brand or product names are or may be trademarks of, and are used to identify products and services of, their respective owners.
In an effort to conserve paper, ProSoft Technology no longer includes printed manuals with our product shipments.
User Manuals, Datasheets, Sample Ladder Files, and Configuration Files are provided at: http://www.prosoft-technology.com
Content Disclaimer
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither ProSoft Technology nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Information in this document including illustrations, specifications and dimensions may contain technical inaccuracies or typographical errors. ProSoft Technology makes no warranty or representation as to its accuracy and assumes no liability for and reserves the right to correct such inaccuracies or errors at any time without notice. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of ProSoft Technology. All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components. When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use ProSoft Technology software or approved software with our hardware products may result in injury, harm, or improper operating results. Failure to observe this information can result in injury or equipment damage.
Copyright © 2017 ProSoft Technology, Inc. All Rights Reserved.
Printed documentation is available for purchase. Contact ProSoft Technology for pricing and availability.
North America: +1 (661) 716-5100
Asia Pacific: +603.7724.2080
Europe, Middle East, Africa: +33 (0) 5.3436.87.20
Latin America: +1.281.298.9109
Important Safety Information
North America Warnings
A
This Equipment is Suitable For Use in Class I, Division 2, Groups A, B, C, D or Non-Hazardous Locations Only.
B
Warning
– Explosion Hazard – Substitution of Any Components May Impair Suitability for Class I, Division 2.
C
Warning
– Explosion Hazard – Do Not Disconnect Equipment Unless Power Has Been Switched Off Or The
Area is Known To Be Non-Hazardous.
D
The subject devices are powered by a Switch Model Power Supply (SMPS) that has regulated output voltage of
5 VDC.
ATEX/IECEx Warnings and Conditions of Safe Usage:
Power, Input, and Output (I/O) wiring must be in accordance with the authority having jurisdiction.
A
Warning - Explosion Hazard - When in hazardous locations, turn off power before replacing or wiring modules.
B
Warning - Explosion Hazard - Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
C
These products are intended to be mounted in an ATEX/IECEx Certified, tool-secured, IP54 enclosure. The devices shall provide external means to prevent the rated voltage being exceeded by transient disturbances of more than 40%. This device must be used only with ATEX certified backplanes.
D
Before operating the reset switch, be sure the area is known to be non-hazardous.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Agency Approvals and Certifications
Agency
ATEX; Category 3, Zone 2
CE Mark
CSA; CB Safety
Environmental
KCC
RoHS Compliant
UL/cUL; Class 1, Div. 2 Groups A, B, C, D
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Contents
User Manual
Contents
Your Feedback Please ........................................................................................................................ 2
Content Disclaimer .............................................................................................................................. 2
Important Safety Information ............................................................................................................... 3
1 Start Here
1.1
1.2
1.3
1.4
1.5
9
System Requirements ............................................................................................. 10
Deployment Checklist .............................................................................................. 11
Package Contents ................................................................................................... 11
Setting Jumpers ...................................................................................................... 12
Installing the Module in the Rack ............................................................................ 13
2 Adding the Module to RSLogix
2.1
2.2
2.3
2.1.1
2.1.2
2.4
2.5
2.3.1
2.3.2
2.6
2.6.1
2.6.2
17
Creating the Module in an RSLogix 5000 Project ................................................... 17
Creating a Module in the Project Using an Add-On Profile ..................................... 18
Creating a Module in the Project Using a Generic 1769 Module Profile ................. 22
Installing ProSoft Configuration Builder .................................................................. 24
Generating the AOI (.L5X File) in ProSoft Configuration Builder ............................ 25
Setting Up the Project in PCB ................................................................................. 25
Creating and Exporting the .L5X File ...................................................................... 28
Creating a New RSLogix 5000 Project .................................................................... 30
Importing the Add-On Instruction ............................................................................ 31
Adding Multiple Modules in the Rack (Optional) ..................................................... 35
Adding another module in PCB ............................................................................... 35
Adding Another Module in RSLogix 5000 ............................................................... 37
3 Configuring the MVI69E-MBS Using PCB
3.1
3.1.1
3.1.2
3.2
3.1.3
3.1.4
3.3
3.2.1
3.2.2
3.2.3
3.2.4
3.4
43
Basic PCB Functions ............................................................................................... 44
Creating a New PCB Project and Exporting an .L5X File ....................................... 44
Renaming PCB Objects .......................................................................................... 44
Editing Configuration Parameters ........................................................................... 44
Printing a Configuration File .................................................................................... 46
Module Configuration Parameters .......................................................................... 47
Module Parameters ................................................................................................. 47
Modbus Port x Parameters...................................................................................... 48
Modbus Port x Commands ...................................................................................... 52
Ethernet 1 ................................................................................................................ 55
Downloading the Configuration File to the Processor ............................................. 56
Uploading the Configuration File from the Processor ............................................. 59
4 MVI69E-MBS Backplane Data Exchange
4.1
4.2
4.3
4.3.1
63
General Concepts of the MVI69E-MBS Data Transfer ........................................... 63
Backplane Data Transfer......................................................................................... 64
Normal Data Transfer .............................................................................................. 65
Write Block: Request from the Processor to the Module ........................................ 65
ProSoft Technology, Inc.
June 28, 2017
Page 5 of 154
Contents
User Manual
4.4
4.3.2
4.3.3
4.4.1
4.4.2
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Read Block: Response from the Module to the Processor ..................................... 65
Read and Write Block Transfer Sequences ........................................................... 66
Data Flow Between the Module and Processor ..................................................... 70
Slave Mode ............................................................................................................. 70
Master Mode ........................................................................................................... 72
5 Using Controller Tags
5.1
5.1.1
5.2
5.3
5.2.1
5.3.1
5.3.2
5.3.3
5.3.4
5.3.5
75
Controller Tags ....................................................................................................... 75
MVI69E-MBS Controller Tags ................................................................................ 76
User-Defined Data Types (UDTs)........................................................................... 77
MVI69E-MBS User-Defined Data Types ................................................................ 77
MBS Controller Tag Overview ................................................................................ 79
MBS.CONFIG ......................................................................................................... 80
MBS.DATA .............................................................................................................. 80
MBS.CONTROL...................................................................................................... 80
MBS.STATUS ......................................................................................................... 85
MBS.UTIL ............................................................................................................... 86
6 Diagnostics and Troubleshooting
6.1
6.2
6.2.1
6.2.2
6.3
6.3.1
6.4
6.4.1
6.4.2
6.4.3
6.4.4
6.5
6.4.5
6.5.1
6.6
6.5.2
6.5.3
87
Ethernet LED Indicators .......................................................................................... 88
LED Status Indicators ............................................................................................. 88
Clearing a Fault Condition ...................................................................................... 89
Troubleshooting ...................................................................................................... 89
Connecting the PC to the Module's Ethernet Port .................................................. 90
Setting Up a Temporary IP Address ....................................................................... 90
Using the Diagnostics Menu in PCB ....................................................................... 93
Diagnostics Menu ................................................................................................... 95
Monitoring Network Configuration Information ....................................................... 96
Monitoring Backplane Information .......................................................................... 97
Port x Module Information ....................................................................................... 98
Monitoring Data Values in the Module’s Database................................................. 99
Communication Error Codes ................................................................................ 100
Standard MODBUS Protocol Exception Code Errors ........................................... 100
Module Communication Error Codes ................................................................... 100
Command List Entry Errors .................................................................................. 100
Connecting to the Module’s Web Page ................................................................ 101
7 Reference
7.1
7.2
7.1.1
7.1.2
7.2.1
7.2.2
7.2.3
Page 6 of 154
7.2.4
7.2.5
7.2.6
7.2.7
7.2.8
103
Product Specifications .......................................................................................... 103
Hardware Specifications ....................................................................................... 104
General Specifications - Modbus Master/Slave .................................................... 104
About the Modbus Protocol .................................................................................. 105
Modbus Master ..................................................................................................... 105
Modbus Slave ....................................................................................................... 105
Function Codes Supported by the Module ........................................................... 106
Read Coil Status (Function Code 01) ................................................................... 106
Read Input Status (Function Code 02) ................................................................. 107
Read Holding Registers (Function Code 03) ........................................................ 109
Read Input Registers (Function Code 04) ............................................................ 110
Force Single Coil (Function Code 05) .................................................................. 111
ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
(9956)
7.4.14
(9957)
7.4.15
7.4.16
7.4.17
7.4.18
7.4.19
7.4.20
7.4.21
7.5
7.5.1
7.6
7.6.1
7.6.2
7.6.3
7.6.4
7.2.9
7.2.10
7.2.11
7.3
7.2.12
7.3.1
7.4
7.3.2
7.4.1
7.4.2
7.4.3
7.4.4
7.4.5
7.4.6
7.4.7
7.4.8
7.4.9
7.4.10
7.4.11
7.4.12
7.4.13
Contents
User Manual
Preset Single Register (Function Code 06) ........................................................... 112
Diagnostics (Function Code 08) ............................................................................ 113
Force Multiple Coils (Function Code 15) ............................................................... 115
Preset Multiple Registers (Function Code 16) ...................................................... 116
Floating-Point Support ........................................................................................... 117
ENRON Floating Point Support ............................................................................. 118
Configuring the Floating Point Data Transfer ........................................................ 118
Function Blocks ..................................................................................................... 124
Event Command Blocks (1000 to 1255, 2000 to 2255) ........................................ 125
Slave Polling Disable Blocks ................................................................................. 126
Slave Polling Enable Blocks (3001, 3101) ............................................................ 126
Slave Polling Status Blocks (3002 to 3006, 3102 to 3106) ................................... 127
Command Control Blocks (5001 to 5006, 5101 to 5106) ..................................... 128
Add Event with Data Blocks (8000, 8001) ............................................................. 129
Get Event with Data Status Block (8100) .............................................................. 130
Get Configuration File Information Block (9000 or -9000) .................................... 131
Get Configuration File Block (9001 or -9001)........................................................ 132
Get General Module Status Data Block (9250) ..................................................... 133
Set Port and Command Active Bits Block (9500) ................................................. 135
Get Port and Command Active Bits Block (9501) ................................................. 136
Pass-through Formatted Block for Functions 6 and 16 with Word Data Block
137
Pass-through Formatted Block for Functions 6 and 16 with Float Data Block
138
Pass-through Formatted Block for Function 5 (9958) ........................................... 139
Pass-through Formatted Block for Function 15 (9959) ......................................... 140
Pass-through Formatted Block for Function 23 (9961) ......................................... 141
Pass-through Block for Function 99 (9970)........................................................... 142
Pass Module Time to Processor Block (9973) ...................................................... 143
Reset Status Block (9997)..................................................................................... 144
Cold-boot Control Block (9999) ............................................................................. 144
Ethernet Port Connection ...................................................................................... 145
Ethernet Cable Specifications ............................................................................... 145
Modbus Application Port Connection .................................................................... 146
RS-232 Wiring ....................................................................................................... 146
RS-422 Wiring ....................................................................................................... 149
RS-485 Wiring ....................................................................................................... 149
DB9 to RJ45 Adaptor (Cable 14) .......................................................................... 150
8 Support, Service & Warranty
8.1
8.2
151
Contacting Technical Support ............................................................................... 151
Warranty Information ............................................................................................. 152
153 Index
ProSoft Technology, Inc.
June 28, 2017
Page 7 of 154
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module User Manual
ProSoft Technology, Inc.
June 28, 2017
Page 8 of 154
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
1 Start Here
Start Here
User Manual
In This Chapter
System Requirements ........................................................................... 10
Installing the Module in the Rack ........................................................... 13
To get the most benefit from this User Manual, you should have the following skills:
Rockwell Automation
®
RSLogix™ software: launch the program, configure ladder logic, and transfer the ladder logic to the processor
Microsoft Windows
®
: install and launch programs, execute menu commands, navigate dialog boxes, and enter data
Hardware installation and wiring: install the module, and safely connect
Modbus and CompactLogix or MicroLogix 1500-LRP devices to a power source and to the MVI69E-
MBS module’s application port(s)
ProSoft Technology, Inc.
June 28, 2017
Page 9 of 154
Start Here
User Manual
1.1 System Requirements
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The MVI69E-MBS module requires the following minimum hardware and software components:
Rockwell Automation CompactLogix or MicroLogix 1500-LRP
®
processor
(firmware version 10 or higher), with compatible power supply and one free slot in the rack, for the MVI69E-MBS module.
Important: The MVI69E-MBS module has a power supply distance rating of 4 (L43 and L45 installations on first 2 slots of 1769 bus). It consumes 500 mA at 5 VDC.
Important: For 1769-L23x processors, please make note of the following limitation:
1769-L23E-QBFC1B = 450 mA at 5 VDC (No MVI69E module can be used with this processor.)
The module requires 500 mA of available 5 VDC power
Rockwell Automation RSLogix 5000 programming software version 16 or higher
Rockwell Automation RSLinx
®
communication software version 2.51 or higher
ProSoft Configuration Builder (PCB) (included)
ProSoft Discovery Service (PDS) (included in PCB)
Pentium
®
II 450 MHz minimum. Pentium III 733 MHz (or better) recommended
Supported operating systems: o o
Microsoft Windows
®
7
Microsoft Windows Vista o o
Microsoft Windows XP Professional with Service Pack 1 or 2
Microsoft Windows 2000 Professional with Service Pack 1, 2, or 3 o
Microsoft Windows Server 2003
128 Mbytes of RAM minimum, 256 Mbytes of RAM recommended
100 Mbytes of free hard disk space (or more based on application requirements)
256-color VGA graphics adapter, 800 x 600 minimum resolution (True Color
1024 x 768 recommended)
Note: The Hardware and Operating System requirements in this list are the minimum recommended to install and run software provided by ProSoft Technology
®
. Other third party applications may have different minimum requirements. Refer to the documentation for any third party applications for system requirements.
Page 10 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
1.2 Deployment Checklist
Start Here
User Manual
Before you begin to configure the module, consider the following questions. Your answers will help you determine the scope of your project, and the configuration requirements for a successful deployment.
Are you creating a new application or integrating the module into an existing application?
Most applications can use the Sample Add-On Instruction or Sample Ladder
Logic without any modification.
Which slot number in the chassis does the MVI69E-MBS module occupy?
For communication to occur, you must enter the correct slot number in the sample program.
Are the RSLogix 5000 and RSLinx software installed?
RSLogix and RSLinx are required to communicate to the CompactLogix or
MicroLogix 1500-LRP processor.
How many words of data do you need to transfer in your application (from
CompactLogix or MicroLogix 1500-LRP to Module / to CompactLogix or
MicroLogix 1500-LRP from Module)?
1.3 Package Contents
The following components are included with your MVI69E-MBS module, and are all required for installation and configuration.
Important: Before beginning the installation, please verify that all of the following items are present.
Qty. Part Name
1
Part Number
MVI69E-MBS Module MVI69E-MBS
2
2
Adapter Cable
Screw Terminal
Adapter
Cable #14
1454-9F
Part Description
Modbus Serial Enhanced Communication
Module
RJ45 to DB9 Male Adapter cable. For DB9 connection to module’s serial application ports
DB9 female to 9-pin screw terminal. Used for RS422 or RS485 connections to Port 1 and 2 of the module
Ethernet straight-through cable 1 Ethernet Cable RL-CBL025
If any of these components are missing, please contact ProSoft Technology
Technical Support for replacement parts.
ProSoft Technology, Inc.
June 28, 2017
Page 11 of 154
Start Here
User Manual
1.4 Setting Jumpers
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
When the module is manufactured, the port selection jumpers are set to RS-232.
To use RS-422 or RS-485, you must set the jumpers to the correct position. The following diagram describes the jumper settings.
Note: Jumper pin placement on the circuit board may vary.
The Setup Jumper acts as "write protection" for the module’s firmware. In "write protected" mode, the Setup pins are not connected, and the module’s firmware cannot be overwritten. The module is shipped with the Setup jumper OFF. If an update of the firmware is needed, apply the Setup jumper to both pins.
Page 12 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The following illustration shows the MVI69E-MBS jumper configuration, with the
Setup Jumper OFF.
Start Here
User Manual
1.5 Installing the Module in the Rack
Make sure the processor and power supply are installed and configured before installing the MVI69E-MBS module. Refer to the Rockwell Automation product documentation for installation instructions.
Warning: Please follow all safety instructions when installing this or any other electronic devices.
Failure to follow safety procedures could result in damage to hardware or data, or even serious injury or death to personnel. Refer to the documentation for each device to be connected to verify that suitable safety procedures are in place before installing or servicing the device.
After you verify the jumper placements, insert the MVI69E-MBS into the rack.
Use the same technique recommended by Rockwell Automation to remove and install CompactLogix or MicroLogix 1500-LRP modules.
Warning: This module is not hot-swappable! Always remove power from the rack before inserting or removing this module, or damage may result to the module, the processor, or other connected devices.
ProSoft Technology, Inc.
June 28, 2017
Page 13 of 154
Start Here
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
1 Align the module using the upper and lower tongue-and-groove slots with the adjacent module and slide forward in the direction of the arrow.
2 Move the module back along the tongue-and-groove slots until the bus connectors on the MVI69 module and the adjacent module line up with each other.
Page 14 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3
Push the module’s bus lever back slightly to clear the positioning tab and move it firmly to the left until it clicks. Ensure that it is locked firmly in place.
Start Here
User Manual
4 Close all DIN-rail latches.
ProSoft Technology, Inc.
June 28, 2017
Page 15 of 154
Start Here
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5 Press the DIN-rail mounting area of the controller against the DIN-rail. The latches momentarily open and lock into place.
Page 16 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
2 Adding the Module to RSLogix
In This Chapter
Creating the Module in an RSLogix 5000 Project .................................. 17
Installing ProSoft Configuration Builder ................................................. 24
Generating the AOI (.L5X File) in ProSoft Configuration Builder ........... 25
Creating a New RSLogix 5000 Project .................................................. 30
Importing the Add-On Instruction ........................................................... 31
Adding Multiple Modules in the Rack (Optional) .................................... 35
To add the MVI69E-MBS module in RSLogix 5000, you must:
1 Create a new project in RSLogix 5000.
2 Add the module to the RSLogix 5000 project. There are two ways to do this: o o
You can use the Add-On Profile from ProSoft Technology. This is the preferred way, but requires RSLogix version 15 or later.
You can manually create the module using a generic 1769 profile, and then manually configure the module parameters. Use this method if you have RSLogix version 14 or earlier.
3 Create an Add-On Instruction file using ProSoft Configuration Builder (PCB) and export the Add-On Instruction to an RSLogix 5000 compatible file (.L5X file).
4 Import the Add-On Instruction (the .L5X file) into RSLogix 5000.
The .L5X file contains the Add-On Instruction, user-defined data types, controller tags and ladder logic required to configure the MVI69E-MBS module.
2.1 Creating the Module in an RSLogix 5000 Project
In an RSLogix 5000 project, there are two ways you can add the MVI69E-MBS module to the project.
You can use an Add-On Profile (AOP) from ProSoft Technology. The AOP contains all the configuration information needed to add the module to the project. This is the preferred way, but requires RSLogix version 15 or later.
Refer to Creating a Module in the Project Using an Add-On Profile (page 18).
If using an AOP is not an option, you can manually create and configure the module using a generic 1769 profile. Use this method if you have RSLogix version 14 or earlier. Refer to Creating a Module in the Project Using a
Generic 1769 Module Profile (page 22).
ProSoft Technology, Inc.
June 28, 2017
Page 17 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2.1.1 Creating a Module in the Project Using an Add-On Profile
Installing an Add-On Profile
Download the AOP file (MVI69x_RevX.X_AOP.zip) from the product webpage
( www.prosoft-technology.com
) onto your local hard drive and then extract the files from the zip archive. Make sure you have shut down RSLogix 5000 and
RSLinx before you install the Add-On Profile (AOP).
1 Run the MPSetup.exe file to start the Setup Wizard. Follow the Setup Wizard to install the AOP.
2 Continue to follow the steps in the wizard to complete the installation.
Page 18 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
3 Click F
INISH
when complete. The AOP is now installed in RSLogix 5000. You do not need to reboot the PC.
Using an Add-On Profile
1 In RSLogix 5000, expand the
I/O C
ONFIGURATION
folder in the Project tree.
Right-click the appropriate communications bus and, and then click N
EW
M
ODULE
.
Page 19 of 154 ProSoft Technology, Inc.
June 28, 2017
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
This opens the Select Module Type dialog box. In the Module Type Vendor
Filters area, uncheck all boxes except the P
RO
S
OFT
T
ECHNOLOGY
box. A list of ProSoft Technology modules appears in the dialog box.
2 Select the MVI69E-MBS module in the list and click C
REATE
:
Page 20 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
3 A New Module dialog box opens. Edit the N
AME
and S
LOT
for the module and click OK.
Note : The I/O
T
ABLE
S
IZES
above should reflect the Block Transfer Size parameter set in PCB
(Section Module Configuration Parameters (page 47)).
A Block Transfer Size of 60 uses an I/O
T
ABLE
S
IZE
of 62/61 words.
A Block Transfer Size of 120 uses an I/O
T
ABLE
S
IZE
of 122/121 words.
A Block Transfer Size of 240 uses an I/O
T
ABLE
S
IZE
of 242/241 words.
Applications that require smaller amounts of data or faster update times, such as ControlNet networks, will benefit from smaller block transfer sizes.
The MVI69E-MBS module is now visible in the I/O Configuration tree.
ProSoft Technology, Inc.
June 28, 2017
Page 21 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2.1.2 Creating a Module in the Project Using a Generic 1769 Module
Profile
This procedure is not required if you installed the ProSoft Technology Add-On
Profile for this module.
1 Expand the
I/O C
ONFIGURATION
folder in the Project tree. Right-click the appropriate communications bus and choose N
EW
M
ODULE
.
This opens the Select Module Type dialog box.
2 Enter
GENERIC
in the search text box and select the G
ENERIC
1769 M
ODULE
. If you're using an earlier version of RSLogix, expand O
THER
in the Select
Module dialog box, and then select the G
ENERIC
1769 M
ODULE
.
Page 22 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3 Set the Module Properties values as follows:
Adding the Module to RSLogix
User Manual
Parameter
Name
Description
Comm Format
Slot
Value
Enter a module identification string. Example: MVI69EMBS
Enter a description for the module. Example: ProSoft communication module for Serial Modbus communications.
Select D
ATA
-INT
Enter the slot number in the rack where the MV69E-MBS module is installed.
101
62 / 122 / 242
Input Assembly Instance
Input Size
Output Assembly Instance
Output Size
100
61 / 121 / 241
Configuration Assembly Instance 102
Configuration Size 0
The following illustration shows an example where the module was configured for a block transfer size of 60 words (input block size = 62 words, output block size = 61 words):
The following options are available:
Block Transfer Size Input Block Size
60
120
240
62
122
242
Output Block Size
61
121
241
ProSoft Technology, Inc.
June 28, 2017
Page 23 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
4 On the Connection tab, set the R
EQUESTED
P
ACKET
I
NTERVAL
value for your project and click OK.
The MVI69E-MBS module is now visible in the I/O Configuration tree.
2.2 Installing ProSoft Configuration Builder
Use the ProSoft Configuration Builder (PCB) software to configure the module.
You can find the latest version of the ProSoft Configuration Builder (PCB) on our web site: http://www.prosoft-technology.com. The installation filename contains the PCB version number. For example, PCB_4.3.4.5.0238.
EXE
.
Installing PCB from the ProSoft website:
1 Open a browser window and navigate to http://www.prosoft-technology.com
2 Navigate to the ProSoft Configuration Builder download link, and save the file to your Windows desktop.
3 After the download completes, double-click the file to install. If you are using
Windows 7, right-click the PCB installation file and then choose R
UN AS
A
DMINISTRATOR
. Follow the instructions that appear on the screen.
4 If you want to find additional software specific to your MVI69E-MBS, enter the model number into the ProSoft website search box and press the Enter key.
Page 24 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
2.3 Generating the AOI (.L5X File) in ProSoft Configuration Builder
The following sections describe the steps required to set up a new configuration project in ProSoft Configuration Builder (PCB), and to export the .L5X file for the project.
2.3.1 Setting Up the Project in PCB
To begin, start P
RO
S
OFT
C
ONFIGURATION
B
UILDER
(PCB).
ProSoft Technology, Inc.
June 28, 2017
Page 25 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The PCB window consists of a tree view on the left, and an information pane and a configuration pane on the right side of the window. The tree view consists of folders for Default Project and Default Location, with a Default Module in the
Default Location folder. The following illustration shows the PCB window with a new project.
Your first task is to add the MVI69E-MBS module to the project.
Page 26 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
1 In the Tree view, right-click D
EFAULT
M
ODULE
, and then click C
HOOSE
M
ODULE
T
YPE
. This opens the
Choose Module Type
dialog box.
User Manual
2 In the Product Line Filter area of the dialog box, click MVI69. In the Select
Module Type dropdown list, click MVI69E-MBS, and then click OK to save your settings and return to the ProSoft Configuration Builder window. The
MVI69E-MBS icon is now visible in the tree view.
ProSoft Technology, Inc.
June 28, 2017
Page 27 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2.3.2 Creating and Exporting the .L5X File
There are two parameters in the PCB configuration that affect the format of the
.L5X file that is exported. Before exporting the .L5X file to the PC/Laptop, check the Block Transfer Size and Slot Number parameters.
1 Expand the MVI69E-MBS icon by clicking the [+] symbol beside it. Similarly, expand the icon. Double-click the icon to open the Edit -
Module dialog box.
2 Set the Block Transfer Size to the desired size of the data blocks transferred between the module and processor (60, 120 or 240 words). Block transfer size information can be found starting in the section on Normal Data Transfer
Page 28 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
3 Edit the Slot Number indicating where the module is placed in the 1769 bus.
4 Click OK to close the Edit
– Module dialog box. The .L5X file is now ready to be exported to the PC/Laptop.
5 Right-click the MVI69E-MBS icon in the project tree and choose E
XPORT
AOI
F
ILE
.
ProSoft Technology, Inc.
June 28, 2017
Page 29 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6 Save the .L5X file to the PC/Laptop in an easily found location, such as
Windows Desktop.
2.4 Creating a New RSLogix 5000 Project
1 Click the F
ILE
menu and then choose N
EW
.
2 Select your CompactLogix or MicroLogix 1500-LRP controller model.
3 Select R
EVISION
16 or newer.
4 Enter a name for your controller, such as My_Controller.
5 Select your CompactLogix or MicroLogix 1500-LRP chassis type.
Page 30 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
2.5 Importing the Add-On Instruction
1 Open the application in RSLogix 5000.
2 Expand the T
ASKS
folder, and expand the M
AIN
T
ASK
folder.
3 Expand the M
AIN
P
ROGRAM
folder. The M
AIN
R
OUTINE
contains rungs of logic.
The very last rung in this routine is blank. This is where you can import the
Add-On Instruction.
Note: You can place the Add-On Instruction in a different routine than the MainRoutine. Make sure to add a rung with a jump instruction (JSR) in the MainRoutine to jump to the routine containing the
Add-On Instruction.
4 Right-click an empty rung in the routine and choose I
MPORT
R
UNGS
.
ProSoft Technology, Inc.
June 28, 2017
Page 31 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5 Select the .L5X file that you exported from PCB (Creating and Exporting the
This opens the Import Configuration dialog box. Click T
AGS
under
M
AIN
R
OUTINE
to display the controller tags in the Add-On Instruction.
Page 32 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
Note: If you are using RSLogix version 16 or earlier, the Import Configuration dialog box does not contain the Import Content tree.
6 If the module is not located in the default slot (or is in a remote rack), edit the connection input and output variables that define the path to the module in the F
INAL
N
AME
column (N
AME
column for RSLogix version 16 or less). For example, if your module is located in slot 3, change Local:1:I in the F
INAL
N
AME
column to Local:3:I. Do the same for Local:1:O.
Note: If your module is located in Slot 1 of the local rack, this step is not required.
7 Click OK to confirm the import. RSLogix indicates that the import is in progress:
ProSoft Technology, Inc.
June 28, 2017
Page 33 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
When the import is completed, the new rung with the Add-On Instruction is visible.
The procedure also imports new user-defined data types, data objects and the Add-On instruction to be used in the project with the MVI69E-MBS module.
Page 34 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2.6 Adding Multiple Modules in the Rack (Optional)
Adding the Module to RSLogix
User Manual
Important: This procedure is for multiple MVI69E-MBS modules running in the same
CompactLogix or MicroLogix 1500-LRP rack
You can add additional modules of the same type to the rack.
1 Add a new MVI69E-MBS module to the ProSoft Configuration Builder (PCB) project.
2 Export the module configuration as an L5X file.
3 Add a new MVI69E-MBS to the RSLogix 5000 project.
4 Import the .L5X file into RSLogix 5000 for the new module as an Add-On
Instruction.
2.6.1 Adding another module in PCB
1 Start ProSoft Configuration Builder.
2 Right click D
EFAULT
L
OCATION
(which you can rename) and choose A
DD
M
ODULE
.
3 Right-click N
EW
M
ODULE
and choose C
HOOSE
M
ODULE
T
YPE
.
4 In the Choose Module Type dialog box, select MVI69E in the P
RODUCT
L
INE
F
ILTER
area, and then select MVI69E-MBS as the M
ODULE
T
YPE
. Click OK.
5 Select the MVI69E-MBS module in the tree and repeat the above steps to add a second (or more) module in the PCB project.
ProSoft Technology, Inc.
June 28, 2017
Page 35 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Note: You must give each MVI69E-MBS module a unique name. The default name on a duplicate module appends a number to the end such as MVI69E-MBS_000, MVI69E-MBS_001, etc.
6 You can rename the module by right clicking the module and choosing
Rename.
7 Configure the module parameters. See Module Configuration Parameters
(page 47) and then export the AOI .L5X file for the new module (right-click the
module and choose E
XPORT
AOI F
ILE
. See Creating and Exporting the .L5X
Page 36 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2.6.2 Adding Another Module in RSLogix 5000
Adding the Module to RSLogix
User Manual
You can place multiple MVI69E-MBS modules in the same rack provided it does not exceed the power distance rating of the CompactLogix or MicroLogix 1500-
LRP rack (see System Requirements (page 10)). Adding an additional module to
the rack is similar to installing a new module; however, the name of the module must be unique.
1 Start RSLogix 5000 and open the project.
2 In RSLogix 5000, locate the I/O
C
ONFIGURATION
folder. Right click
C
OMPACT
B
US
L
OCAL
and choose N
EW
M
ODULE
.
3 In the Select Module Type dialog box, select the MVI69E-MBS module. o o
If you are using an Add-On Profile (AOP), this adds the MVI69E-MBS module and configures the relevant parameters. You must be using
RSLogix version 15 or later to to use an AOP.
If using an AOP is not an option, select G
ENERIC
1769 M
ODULE
and click
C
REATE
.
ProSoft Technology, Inc.
June 28, 2017
Page 37 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
4 The New Module dialog box appears. Enter a unique name for the new module, and confirm the slot number of the new module.
5 Click OK. The new module is now visible.
6 You must also import the Add-On Instruction(AOI) for the new module (see
Adding another module in PCB (page 35)). In the Controller Organizer pane,
double-click M
AIN
R
OUTINE
to open the ladder for the routine.
Page 38 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
7 Right-click an empty rung in the routine, and then choose I
MPORT
R
UNGS
…
ProSoft Technology, Inc.
June 28, 2017
Page 39 of 154
Adding the Module to RSLogix
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
8 Select the .L5X file you created and exported for the new module, and click
I
MPORT
.
The new .L5X file has a unique filename that is specific to the new module.
9 This opens the I
MPORT
C
ONFIGURATION
dialog box. Click T
AGS
to show the controller tags in the AOI. You must edit the F
INAL
N
AME
column of the tags for the second module to make them unique.
Page 40 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Adding the Module to RSLogix
User Manual
10 Associate the I/O connection variables to the correct module in the corresponding slot number. The default values are Local:1:I and Local:1:O.
You must edit these values if the card is placed in a slot location other than slot 1 (Local:1:x means the card is located in slot 1). Since the second card is placed in slot 2, change the F
INAL
N
AME
to Local:2:I and Local:2:O. Also, you can append a ‘_2’ at the end of the F
INAL
N
AME
of ‘AOI69_MBS’ and ‘MBS’ arrays as shown below.
ProSoft Technology, Inc.
June 28, 2017
Page 41 of 154
Adding the Module to RSLogix
User Manual
11 Click OK.
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The setup procedure is now complete. Save the project. It is ready to download to the CompactLogix or MicroLogix 1500-LRP processor.
Page 42 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
User Manual
3 Configuring the MVI69E-MBS Using PCB
In This Chapter
Module Configuration Parameters ......................................................... 47
Downloading the Configuration File to the Processor ............................ 56
Uploading the Configuration File from the Processor ............................ 59
ProSoft Configuration Builder (PCB) provides a quick and easy way to manage module configuration files customized to meet your application needs.
You build and edit the module’s configuration in ProSoft Configuration Builder.
You use PCB to download the configuration file to the CompactLogix or
MicroLogix 1500-LRP processor, where it is stored in the MBS.CONFIG controller tag generated by the previously exported AOI. See Creating and
Exporting the .L5X File (page 28). When the MVI69E-MBS module boots up, it
requests the processor to send the configuration over the backplane in special
Configuration Blocks.
See the chapter Adding the Module to RSLogix (page 17) for the procedures to
create a new PCB project and export a .L5X file for the processor. This chapter describes the module configuration parameters in detail, as well as how to download the configuration to the processor using PCB.
ProSoft Technology, Inc.
June 28, 2017
Page 43 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
3.1 Basic PCB Functions
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3.1.1 Creating a New PCB Project and Exporting an .L5X File
Please see the chapter Adding the Module to RSLogix (page 17).
3.1.2 Renaming PCB Objects
You can rename objects such as the Default Project and Default Location folders in the tree view. You can also rename the Module icon to customize the project.
1 Right-click the object you want to rename and then choose R
ENAME
.
2 Type the new name for the object and press Enter.
3.1.3 Editing Configuration Parameters
1 Click the [+] sign next to the module icon to expand module information.
2 Click the
[+]
sign next to any icon to view module information and configuration options.
3 Double-click any icon to open an Edit dialog box.
To edit a parameter, select the parameter in the left pane and make your changes in the right pane.
Note: Depending on the parameter, you must enter text, or a valid number, or select from a list of options.
4 Click OK to save your changes.
Page 44 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
5 Double-click any icon to open an Edit dialog box with a table. Use this dialog box to build and edit Modbus Master commands.
User Manual
6 To add a row to the table, click A
DD
R
OW
.
ProSoft Technology, Inc.
June 28, 2017
Page 45 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7 To edit the row, click E
DIT
R
OW
. This opens an Edit dialog box.
3.1.4 Printing a Configuration File
1 In the main PCB window, right-click the MVI69E-MBS icon and then choose
V
IEW
C
ONFIGURATION
.
2 In the View Configuration dialog box, click the F
ILE
menu and then click
P
RINT
.
3 In the Print dialog box, choose the printer to use from the drop-down list, select the printing options, and then click OK.
Page 46 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3.2 Module Configuration Parameters
Configuring the MVI69E-MBS Using PCB
User Manual
3.2.1 Module Parameters
This section contains general module configuration parameters, including database allocation and backplane transfer options.
In the ProSoft Configuration Builder (PCB) tree view, double-click M
ODULE
.
Parameter
Module Name
Read Register Start
Read Register Count
Write Register Start
Write Register Count
Value
ASCII characters
(max. 80)
0 to 9999
0 to 10,000
0 to 9999
0 to 10,000
Description
Assigns a name to the module that can be viewed using the configuration/debug port. Use this parameter to identify the module and the configuration file.
Specifies the start of the Read Data area in module memory. Data in this area is transferred from the module to the processor.
Specifies the size of the Read Data area.
Specifies the start of the Write Data area in module memory. Data in this area is transferred from the processor to the module.
Specifies the size of the Write Data area.
Backplane Fail Count
Error/Status Block Pointer
Initialize Input Image
Block Transfer Size
Slot Number
0 to 65535
-1 to 9939
Yes or No
Specifies the number of consecutive backplane transfer failures that can occur before communications are halted.
Starting register location in the module’s database for the error/status table. If a value of -1 is entered, the error/status data is not placed in the database. This data must be placed in the read data range of module memory.
This data ncludes the module version information and all server
error/status data. Refer to MBS.STATUS (page 85) for more
information.
This parameter determines if the input image data and the module’s Read Register Data values are initialized with Read
Register Data values from the processor. If you set the parameter to No, the Read Register Data values in the module are set to 0 upon initialization. If you set the parameter to Yes, the data is initialized with Read Register Data values from the processor. This option requires associated ladder logic to pass the data from the processor to the module.
60, 120 or 240 Specifies the number of words in each block transferred between the module and processor.
1 to x Specifies the slot in the CompactLogix or MicroLogix 1500-LRP rack for the module.
Important: The sum of the Read Register Count and Write Register Count cannot exceed 10,000 total registers. Furthermore, neither the Read Data nor the Write Data area may extend above module register 9999. The Read Data and Write Data areas must not overlap.
ProSoft Technology, Inc.
June 28, 2017
Page 47 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3.2.2 Modbus Port x Parameters
This section applies to both MBS
P
ORT
1 and MBS
P
ORT
2.
In the ProSoft Configuration Builder tree view, double-click the M
ODBUS
P
ORT X
icon.
Configuration Parameters Common to Master and Slave
Parameter
Start Active
Type
Protocol
Baud Rate
Parity
Data Bits
Stop Bits
RTS On
RTS Off
Use CTS Line
Value Description
Yes or No
Master, Slave, or Slave with
Pass-Through
Specifies whether or not the port and commands are active upon module boot-up.
This parameter specifies which device type the port emulates.
See Slave Mode (page 70) for more information on Slave
Pass-Through options.
RTU or ASCII Specifies the Modbus protocol for the port.
Multiple options Specifies the baud rate for the port.
None, Odd,
Even
7 or 8
Specifies the type of parity error checking. All devices on this port must use the same parity setting.
1 or 2
0 to 65535 milliseconds
0 to 65535 milliseconds
Yes or No
Sets the number of data bits for each word used by the protocol. All devices communicating through this port must use the same number of data bits.
Sets the number of stop bits that signal the end of a character in the data stream. For most applications, use one stop bit. For slower devices that require more time to re-synchronize, use two stop bits. All devices communicating through this port must use the same number of stop bits.
Sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data is transmitted.
Sets the number of milliseconds to delay after the last byte of data is sent before the RTS modem signal is set low.
Specifies if the Clear To Send (CTS) modem control line is to be used or not. If you set the parameter to N
O
, the CTS line is not monitored. If you set the parameter to Y
ES
, the CTS line is monitored and must be high before the module sends data.
Normally, this parameter is required when half-duplex modems are used for communication (2-wire). This procedure is commonly referred to as hardware handshaking.
Page 48 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Float Flag Yes or No
Configuring the MVI69E-MBS Using PCB
User Manual
Specifies how the Slave driver responds to Function Code 3, 6, and 16 commands (read and write Holding Registers) from a remote Master when it is moving 32-bit floating-point data.
Note: Most applications using floating-point data do not need this parameter enabled.
If the remote Master expects to receive or sends one complete
32-bit floating-point value for each count of one (1), then set this parameter to Y
ES
. When set to Y
ES
, the Slave driver returns values from two consecutive 16-bit internal memory registers (32 total bits) for each count in the read command, or receive 32-bits per count from the Master for write commands.
Example: Count = 10, Slave driver sends 20 16-bit registers for
10 total 32-bit floating-point values.
If, however, the remote Master sends a count of two (2) for each 32-bit floating-point value it expects to receive or send, or, if you do not plan to use floating-point data in your application, then set this parameter to N
O
, which is the default setting.
You also need to set the Float Start and Float Offset parameters to appropriate values whenever the Float Flag parameter is set to Y
ES
.
Float Start 0 to 32767
Float Offset 0 to 9999
Defines the first register of floating-point data. All requests with register values greater-than or equal to this value is considered floating-point data requests. This parameter is only used if the
Float Flag is enabled. For example, if you enter a value of
7000, all requests for registers 7000 and above are considered as floating-point data.
Defines the start register for floating-point data in the internal database. This parameter is used only if the Float Flag is enabled. For example, if you set the Float Offset value to 3000 and the float start parameter to 7000, data requests for register 7000 use the internal Modbus register 3000.
ProSoft Technology, Inc.
June 28, 2017
Page 49 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Additional Configuration Parameters as Master
The Type parameter must be M
ASTER
to configure these parameters. See
Configuration Parameters Common to Master and Slave (page 48).
Parameter
Response
Timeout
Value
0 to 65535 milliseconds
Retry Count
Minimum
Command Delay
0 to 10
0 to 32767 milliseconds
Error Delay
Counter
Inter-character
Timeout
Command Error
Offset
0 to 60000
0 to 65535 milliseconds
-1 to 9998
Description
Specifies the command response timeout period in 1 millisecond increments. This is the time that a port configured as a Master waits for a response from the addressed slave before re-transmitting the command (Retries) or skipping to the next command in the Command List. The value to specify depends on the communication network used and the expected response time (plus or minus) of the slowest device on the network.
Specifies the number of times a command is retried if it fails.
Specifies the number of milliseconds to wait between receiving the end of a slave's response to the most recently transmitted command and the issuance of the next command. You can use this parameter to place a delay after each command to avoid sending commands on the network faster than the slaves can receive them. This parameter does not affect retries of a command, as retries are issued when a command failure is recognized.
Specifies the number of poll attempts to be skipped before trying to re-establish communications with a slave that has failed to respond to a command within the time limit set by the
Response Timeout parameter. After the slave fails to respond, the master skips sending commands that should have been sent to the slave until the number of skipped commands matches the value entered in this parameter. This creates a sort of slow poll mode for slaves that are experiencing communication problems.
Specifies a time delay in milliseconds to be added to the 3.5 character time delay used by the module to recognize the end of a message. Certain applications may require validation of
Modbus messages with more than 3.5 character time between consecutive bytes (example: modem applications). A value of
0 causes the default end of message delay to be used
Sets the address in the module’s database where the command error data is placed. If the value is set to -1, the data is not transferred to the database. The valid range of values for this parameter is -1 to 4899. For example, if this parameter is configured for 1000, the command errors are copied to the database as follows:
1000: error code for command 0
1001: error code for command 1
…
An error code of 0 means that the command was successfully sent (no error).
Page 50 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
User Manual
Additional Configuration Parameters as Slave
The Type parameter must be S
LAVE
or P
ASS
T
HRU
S
LAVE
to configure these parameters. See Configuration Parameters Common to Master and Slave (page
Parameter
Minimum
Response Delay
Value
0 to 65535 milliseconds
Internal Slave ID 1 to 247
Bit Input Offset 0 to 9998
Word Input Offset 0 to 9998
Output Offset 0 to 9998
Holding Register
Offset
0 to 9998
Description
Sets the number of milliseconds to wait before responding to a command received on the port from a remote Master. This delay is sometimes required to accommodate slower Master devices.
Defines the Slave Node Address for the internal database. All requests received by the port with this address are processed by the module. Verify that each device has a unique address on a network.
Specifies the offset address into the internal Modbus database for network requests for Modbus function 2 commands. For example, if you set the value to 150, an address request of 0 returns the value at register 150 in the database.
Specifies the offset address into the internal Modbus database for network requests for Modbus function 4 commands. For example, if you set the value to 150, an address request of 0 returns the value at register 150 in the database.
Specifies the offset address into the internal Modbus database for network requests for Modbus function 1, 5 or 15 commands. For example, if you set the value to 100, an address request of 0 corresponds to register 100 in the database.
Specifies the offset address in the internal Modbus database for network requests for Modbus function 3, 6, or 16 commands. For example, if you set the value to 50, a request for address 0 corresponds to the register 50 in the database.
ProSoft Technology, Inc.
June 28, 2017
Page 51 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
3.2.3 Modbus Port x Commands
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
This section defines the master command list specifications for a Master port.
The information in this section applies to both MBS
P
ORT
1 and MBS
P
ORT
2.
In the ProSoft Configuration Builder tree view, double-click the M
ODBUS
P
ORT X
C
OMMANDS
icon.
In order to interface the MVI69E-MBS with Modbus slave devices, you must create a command list. The commands in the list specify the slave device to be addressed, the function to be performed (read or write), the data area in the device to interface with and the registers in the internal database to be associated with the device data.
The Master command list supports up to 250 commands. The command list is processed from top (Command #0) to bottom.
Read commands are executed without condition. You can set write commands to execute only if the data in the write command changes (Conditional Enable). If the register data values in the command have not changed since the command was last issued, the command is not executed. You can use this feature to optimize network performance.
The MVI69E-MBS Master (and Slave) communication drivers support several data read and write commands. When a command is configured, the type of data
(bit, 16-bit integer, 32-bit float, etc), and the level of Modbus support in the slave equipment needs to be considered.
Page 52 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Parameter Value Description
Enable 0 to 4
Internal Address 0 to 9999 (wordlevel) or
0 to 65535 (bitlevel)
Configuring the MVI69E-MBS Using PCB
User Manual
This field defines whether the command is to be executed under certain conditions.
Disabled (0) = The command is disabled and is not executed in the normal polling sequence.
Continuous (1) = The command is executed each scan of the command list if the Poll Interval (see below) is set to zero. If the Poll Interval is set to a nonzero value, the command is executed when the interval timer expires.
Conditional (2) = For write commands only. The command executes only if the internal data associated with the command changes.
Bit/Word Override upon Error (3) = For read commands only. If a command error occurs, the module overrides the associated database area with the Override Value Upon Error parameter value.
Float Override upon Error (4) = For read commands only. If a command error occurs, the module overrides the associated database area (2x word count) with the Override Value Upon
Error parameter value.
Specifies the module’s internal database register to be associated with the command. Allowable range is 0 to 9999 for Modbus Function Codes 3, 4, 6, or 16, and 0 to 65535 for
Modbus Function Codes 1, 2, 5, or 15.
If the command is a read function, the data read from the slave device is stored beginning at the module’s internal database register value entered in this field. This register value must be in the Read Data area of the module’s memory, defined by the Read Register Start and Read Register Count parameters in the Module section.
If the command is a write function, the data to be written to the slave device is sourced beginning from the module’s internal database register specified. This register value must come from the Write Data area of the module’s memory, defined by the Write Register Start and Write Register Count parameters in the Module section.
Note: When using a bit level command, you must define this field at the bit level. For example, when using function codes 1 or 2 for a Read command, you must have a enter of 160 to place the data in the MBS.DATA.ReadData[10] controller tag in RSLogix 5000 . Think of it as the 160th bit of MBS internal memory (MBS Internal register 10 * 16 bits per register =
160). Use this formula for function codes 5 or 15 for writing bits also.
This controller tag is a 16bit signed integer. This means you can only enter values of -32768 to 32767 in the tag. If a value to be entered is above the 32767 (but below 65535) threshold, it displays as a negative value in the tag. Simply subtract
65536 from the value to get the 'acceptable' value to enter into the tag.
Example: You need to use an Internal bit Address of 48000, but you cannot enter '48000' into the tag because it causes an error. 48000 - 65536 = -17536 You enter -17536 in the
Internal Address parameter for this command.
ProSoft Technology, Inc.
June 28, 2017
Page 53 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
Poll Interval 0 to 65535 seconds
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Register Count
Swap Code
1 to 125 (words) or
1 to 800 (coils)
0,1,2,3
Specifies the minimum interval between executions of continuous commands (Enable code = 1).
Example: If you set the value to 10, the command executes no more frequently than once every 10 seconds. When the command reaches the top of the command queue and 10 seconds has not elapsed, it is skipped until the poll interval has expired.
Specifies the number of registers or digital points to be associated with the command. Modbus Function Codes 5 and
6 ignore this field as they only apply to a single data point.
For Modbus Function Codes 1, 2 and 15, this parameter sets the number of single bit digital points (inputs or coils) to be associated with the command.
For Modbus Function Codes 3, 4 and 16, this parameter sets the number of 16-bit registers to be associated with the command.
Defines if the data received from the Modbus slave is to be ordered differently than received from the slave device. This parameter is helpful when dealing with floating-point or other multi-register values, as there is no standard method of storage of these data types in slave devices. You can set this parameter to order the register data received in an order useful by other applications.
No Change (0)= No change is made in the byte ordering
(ABCD = ABCD)
Word Swap (1)= The words are swapped (ABCD= CDAB)
Word and Byte Swap (2) = The words are swapped, then the bytes in each word are swapped (ABCD=DCBA)
Byte Swap (3) = The bytes in each word are swapped
(ABCD=BADC)
Note: Each pair of characters is a byte. Ex: AB and CD. Two pairs of characters is 16-bit register Ex: ABCD.
Node Address
MB Address in
Device
1 to 255
(0 = broadcast)
Specifies the Modbus slave node address on the network to be considered. Most Modbus devices only accept an address in the range of 1 to 247. If you set the value to zero, the command is a broadcast message on the network. The
Modbus protocol permits broadcast commands for write operations. Do not use this node address for read operations.
Modbus Function 1,2,3,4,5,6,15,16 Specifies the Modbus function to be executed by the command. These function codes are defined in the Modbus protocol.
1
– Read Coil Status (0xxxx)
2
– Read Input Status (1xxxx)
3
– Read Holding Registers (4xxxx)
4
– Read Input Registers (3xxxx)
5
– Force (Write Single) Coil (0xxxx)
6
– Force (Write Single) Holding Register (4xxxx)
15
– Preset (Write) Multiple Coils (0xxxx)
16
– Preset (Write) Multiple Registers (4xxxx)
0 to 9999 Specifies the register or digital point address offset within the
Modbus slave device. The MBS Master reads or writes from/to this address within the slave.
Refer to the documentation of each Modbus slave device for
Page 54 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
User Manual their register and digital point address assignments.
Note: The value entered here does not need to include the
"Modbus Prefix" addressing scheme. Also, this value is an offset of the zero-based Modbus addressing scheme.
Example: Using a Modbus Function Code 3 to read from address 40010 in the slave, a value of ‘9’ would be entered in this parameter. The firmware (internally) adds a ‘40001’ offset to the value entered. This is the same for all Modbus addresses (0x, 1x, 3x, 4x).
Override Value
Upon Error
This parameter is only applicable for Enable Codes 3
(Bit/Word Override) or 4 (Float Override).
If an error occurs associated to a read command the module automatically populates the associated database area with this override value.
3.2.4 Ethernet 1
This section defines the permanent IP address, Subnet Mask, and Gateway of the module.
In the ProSoft Configuration Builder tree view, double-click the E
THERNET
1 icon.
Parameter
IP Address
Netmask
Gateway
Description
Unique IP address assigned to the module
Subnet mask of module
Gateway (if used)
ProSoft Technology, Inc.
June 28, 2017
Page 55 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3.3 Downloading the Configuration File to the Processor
1 In the ProSoft Configuration Builder tree view, right-click the module icon and choose D
OWNLOAD FROM
PC
TO
D
EVICE
.
2 In the Download Configuration File dialog box, click RSW
HO
.
Page 56 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
3 Browse to, and then highlight the CompactLogix or MicroLogix 1500-LRP processor and click OK.
User Manual
4 Notice the CIPConnect path has been updated in the Download Configuration
File dialog box. Click T
EST
C
ONNECTION
to verify the path is active and can successfully connect to the processor.
ProSoft Technology, Inc.
June 28, 2017
Page 57 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5 When ready, click D
OWNLOAD
to download the configuration file to the processor. Following the download process, the module is automatically rebooted.
6 After rebooting, the ladder logic sends the configuration data from the processor to the module. When that is complete, the module starts Modbus communications.
Page 58 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
User Manual
3.4 Uploading the Configuration File from the Processor
1 In the ProSoft Configuration Builder tree view, right-click the MVI69E-MBS icon and choose U
PLOAD FROM
D
EVICE TO
PC.
ProSoft Technology, Inc.
June 28, 2017
Page 59 of 154
Configuring the MVI69E-MBS Using PCB
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
2 In the Upload Configuration File dialog box, the CIPConnect path should already be constructed if you have previously downloaded the configuration file from the same PC. If not, click RSW
HO
, browse to, then select the
CompactLogix or MicroLogix 1500-LRP Processor, and click OK.
Page 60 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Configuring the MVI69E-MBS Using PCB
3 Click T
EST
C
ONNECTION
to verify the path is active and can successfully connect to the processor.
User Manual
4 When ready, click U
PLOAD
. When upload is complete, click C
LOSE
.
5 PCB now displays the uploaded configuration file.
ProSoft Technology, Inc.
June 28, 2017
Page 61 of 154
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Page 62 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MVI69E-MBS Backplane Data Exchange
User Manual
4 MVI69E-MBS Backplane Data Exchange
In This Chapter
General Concepts of the MVI69E-MBS Data Transfer .......................... 63
Backplane Data Transfer ....................................................................... 64
Data Flow Between the Module and Processor ..................................... 70
4.1 General Concepts of the MVI69E-MBS Data Transfer
The MVI69E-MBS module uses ladder logic to communicate with the
CompactLogix or MicroLogix 1500-LRP processor across the backplane. The ladder logic handles the module data transfer, configuration data transfer, special block handling, and status data receipt.
The following topics describe several concepts that are important for understanding the operation of the MVI69E-MBS module. This is the order of operations on power-up:
1 The module begins the following logical functions: o o o
Initialize hardware components
Initialize CompactLogix or MicroLogix 1500-LRP backplane driver
Test and clear all RAM
2 Read configuration from the CompactLogix or MicroLogix 1500-LRP processor through ladder logic
3 Allocate and initialize Module Register space
4 Enable Modbus application port(s)
After the module has received the module configuration, the module begins communicating with other devices on the Modbus network, depending on the
Modbus configuration of the module.
ProSoft Technology, Inc.
June 28, 2017
Page 63 of 154
MVI69E-MBS Backplane Data Exchange
User Manual
4.2 Backplane Data Transfer
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The MVI69E-MBS module communicates directly over the CompactLogix or
MicroLogix 1500-LRP backplane. Data is paged between the module and the
CompactLogix or MicroLogix 1500-LRP processor across the backplane using the module's input and output images. The update frequency of the images is determined by the scheduled scan rate that you define for the module and the communication load on the module. Typical updates are in the range of 1 to 10 milliseconds per block of information.
This bi-directional data transfer is accomplished by the module filling in data in the module's input image to send to the processor. Data in the input image is placed in the Controller Tags in the processor by the ladder logic. The input image for the module may be set to 62, 122, or 242 words depending on the block transfer size parameter set in the configuration file. This data area permits fast throughput of data between the module and the processor. Applications that require smaller amounts of data or faster update times, such as ControlNet networks, will benefit from smaller block transfer sizes.
The processor inserts data to the module's output image to transfer to the module. The module's program extracts the data and places it in the module's internal database. The output image for the module may be set to 61, 121, or 241 words depending on the block transfer size parameter set in the configuration file.
The following illustration shows the data transfer method used to move data between the CompactLogix or MicroLogix 1500-LRP processor, the MVI69E-
MBS module and the Modbus Network.
Page 64 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MVI69E-MBS Backplane Data Exchange
User Manual
All data transferred between the module and the processor over the backplane is through the input and output images. Ladder logic in the CompactLogix or
MicroLogix 1500-LRP processor interfaces the input and output image data with data defined in the Controller Tags. All data used by the module is stored in its internal database. This database is defined as virtual MBS data tables with addresses from 0 to the maximum number of points for each data type.
4.3 Normal Data Transfer
4.3.1 Write Block: Request from the Processor to the Module
These blocks of data transfer information from the processor to the module. The structure of the output image used to transfer this data is shown below:
Offset Description Length (words)
0
1 to (n)
Write Block ID
Write Data
1
(n)
(n) = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration
file).
The Write Block ID is an index value that determines the location in the module’s database where the data is placed.
4.3.2 Read Block: Response from the Module to the Processor
These blocks of data transfer information from the module to the processor. The structure of the input image used to transfer this data is shown below:
Offset
0
1
2 to (n+1)
Description
Read Block ID
Write Block ID
Read Data
Length (words)
1
1
(n)
(n) = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the configuration
file).
ProSoft Technology, Inc.
June 28, 2017
Page 65 of 154
MVI69E-MBS Backplane Data Exchange
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
4.3.3 Read and Write Block Transfer Sequences
The Read Block ID is an index value that determines the location where the data is placed in the processor controller tag array of module read data. The number of data words per transfer depends on the configured Block Transfer Size parameter in the configuration file (possible values are 60, 120, or 240).
The Write Block ID associated with the block requests data from the processor.
Under normal program operation, the module sequentially sends read blocks and requests write blocks. For example, if the application uses three read and two write blocks, the sequence is as follows:
R1W1
R2W2R3W1R1W2R2W1R3W2R1W1
This sequence continues until interrupted by other write block numbers sent by the controller or by a command request from a node on the Modbus network or operator control through the module’s Configuration/Debug port.
The following example shows a typical backplane communication application.
If the backplane parameters are configured as follows:
Read Register Start:
Read Register Count:
Write Register Start:
Write Register Count:
0
480
480
480
The backplane communication would be configured as follows:
Database address 0 to 479 is continuously transferred from the module to the processor. Database address 480 to 959 is continuously transferred from the processor to the module.
The Block Transfer Size parameter configures how the Read Data and Write
Data areas are broken down into data blocks (60, 120, or 240).
Page 66 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
If Block Transfer Size = 60
MVI69E-MBS Backplane Data Exchange
User Manual
ProSoft Technology, Inc.
June 28, 2017
Page 67 of 154
MVI69E-MBS Backplane Data Exchange
User Manual
If Block Transfer Size = 120
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Page 68 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
If Block Transfer Size = 240
MVI69E-MBS Backplane Data Exchange
User Manual
ProSoft Technology, Inc.
June 28, 2017
Page 69 of 154
MVI69E-MBS Backplane Data Exchange
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
4.4 Data Flow Between the Module and Processor
The following topics describe the flow of data between the two pieces of hardware (CompactLogix or MicroLogix 1500-LRP processor and MVI69E-MBS module) and other nodes on the Modbus network. You can configure each port on the module to emulate a Modbus Master device or a Modbus Slave device.
4.4.1 Slave Mode
In Slave Driver mode, the MVI69E-MBS module responds to read and write commands issued by a master on the Modbus network. The following diagram shows the data flow for normal Slave mode.
4
5
Step
1
2
3
Description
Any time the module restarts (boots or reboots), the Modbus slave port driver receives configuration information from the MBS controller tags. This information configures the serial ports and defines slave node characteristics. The configuration information may also contain instructions to offset data stored in the database to addresses different from addresses requested in the received messages.
A Modbus Master device, such as a Modicon PLC or an HMI application, issues a read or write command to the module’s node address. The port driver qualifies the message before accepting it into the module. Rejected commands cause an Exception Response.
After the module accepts the command, the data is immediately transferred to or from the module’s internal database. On a read command, the data is read from of the database and a response message is built. On a write command, the data is written directly into the database and a response message is built.
After Steps 2 and 3 have been completed, either a normal response message or an
Exception Response message is sent to the Master.
Counters are available in the Status Block to permit the ladder logic program to determine the level of activity of the Slave driver.
Page 70 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MVI69E-MBS Backplane Data Exchange
User Manual
In Slave Pass-Through mode, write commands from the Master are handled differently than they are in Normal mode. In Slave Pass-Through mode, all write requests are passed directly to the processor and data is not written directly into the module’s database.
This mode is especially useful when both a Modbus Master and the module’s processor logic need to be able to read and write values to the same internal database addresses.
The following diagram shows the data flow for a slave port with pass-through enabled:
Step
1
2
3
Description
Same as normal mode.
Same as normal mode. a. In Pass-Through mode, if the Slave driver receives a read request, it looks for the data in module’s internal database, just as it would in Normal mode. b. The data needed to respond to the read command is retrieved directly from the internal database and returned to the Slave driver so it can build a response message. c. In Pass-Through mode, if the Slave Driver receives a write request, it does not send the data directly to the module’s internal database. It puts the data to be written into a special Input Image with a special Block ID code to identify it as a Pass-Through Write
Block and substitutes this special block in place of the next regular Read Data Block. The special block is processed by the ladder logic and the data to be written is placed into the
WriteData controller tag array at an address that corresponds to the Modbus Address received in the write command. d. During normal backplane communications, the data from the WriteData array, including the data updated by the Pass-
Through Write Block, is sent to the module’s internal database. This gives the ladder logic the opportunity to also change the values stored in these addresses, if need be, before they are written to the database.
Note: The ReadData array is not used in Pass-Through mode.
Same as normal mode.
Same as normal mode.
4
5
ProSoft Technology, Inc.
June 28, 2017
Page 71 of 154
MVI69E-MBS Backplane Data Exchange
User Manual
4.4.2 Master Mode
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
In Master mode, the MVI69E-MBS module issues read or write commands to slave devices on the Modbus network. These commands are user-configured in
PCB; refer to Modbus Port x Commands (page 52). This list is transferred to the
module when the module receives its configuration from the processor.
The commands can also be issued directly from the CompactLogix or MicroLogix
1500-LRP processor (Special Command Blocks).
Command status is returned to the processor for each individual command in the command list. The location of this command status list in the module’s internal database is user-defined. The following flow chart and associated table describe the flow of command data into and out of the module.
3
4
5
Step
1
2
Description
Upon module boot-up, the Master driver obtains configuration data from the MBS controller tags. The configuration data retrieved includes port configuration and the
Master Command List.
Special Commands can be issued directly from the CompactLogix or MicroLogix 1500-
LRP processor using Event Commands and Command Control. These command values are used by the Master driver to determine the types and order of commands to send to slaves on the network.
After configuration, the Master driver begins transmitting read and/or write commands to slave nodes on the network. If the Master driver is writing data to a slave, the data for the write command is retrieved from the module’s internal database.
Once the specified slave has successfully processed the command, it returns a response message to the Master driver for processing.
Data received from a slave in response to a read command is stored in the module’s internal database.
Status is returned to the processor for each command in the Master Command List.
Page 72 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MVI69E-MBS Backplane Data Exchange
User Manual
Important: Take care when constructing each command in the list to ensure predictable operation of the module. If two commands write to the same internal database address of the module, the results are invalid. All commands containing invalid data are ignored by the module.
Master Command List
For a port to function in Master Mode, its Master Command List must be defined
in Prosoft Configuration Builder; refer to Modbus Port x Commands (page 52).
This list contains up to 310 individual entries, with each entry containing the information required to construct a valid command. A valid command includes the following items:
Command enable mode: (0) disabled, (1) continuous or (2) conditional
Source or destination database address: The module database address where data is written or read.
Count: The number of words or bits to be transferred – up to 125 words for
Function Codes 3, 4, or 16, and up to 2000 bits for Function Codes 1, 2, or
15.
Note: 125 words is the maximum count allowed by the Modbus protocol. Some field devices may support less than the full 125 words. Check with the device manufacturer for the maximum count supported by the particular slave device.
Slave node address
Modbus Function Code: This is the type of command that is issued.
Source or destination address in the slave device
Command Error Codes
As the list is read in from the processor and as the commands are processed, an error value is maintained in the module for each command. The definition for
these command error codes is listed in Communication Error Codes (page 100).
You can view the command error codes through the Ethernet diagnostics port;
refer to Diagnostics and Troubleshooting (page 87). They can also be transferred
from the module’s database to the processor.
To transfer the Command Error List to the processor, set the Command Error
Offset parameter in the port configuration to a module database address that is in the module’s Read Data area; refer to Additional Configuration Parameters as
Note: The Command Error List must be placed in the Read Data area of the database, so it can be transferred to the processor in the input image.
ProSoft Technology, Inc.
June 28, 2017
Page 73 of 154
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Page 74 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5 Using Controller Tags
Using Controller Tags
User Manual
In This Chapter
User-Defined Data Types (UDTs) ......................................................... 77
MBS Controller Tag Overview ............................................................... 79
Controller tags are a feature of the RSLogix software and are part of the MVI69E-
MBS Add-On Instruction. Refer to the section Adding the Module to RSLogix
(page 17) for information on importing the Add-On Instruction into RSLogix.
5.1 Controller Tags
Data related to the MVI69E-MBS is stored in the ladder logic in variables called controller tags. You use controller tags to manage communication between the
MVI69E-MBS module and the CompactLogix or MicroLogix 1500-LRP processor:
View the read and write data being transferred between the module and the processor.
View status data for the module.
Set up and trigger special functions.
Initiate module restarts (Warm Boot or Cold Boot).
Individual controller tags can be grouped into collections of controller tags called controller tag structures. A controller tag structure can contain any combination of:
Individual controller tags
Controller tag arrays
Lower-level controller tag structures
The controller tags are included in the MVI69E-MBS Add-On Instruction ladder logic. After you import the Add-On Instruction, you can find the controller tags in the Controller Tags subfolder, located in the Controller folder in the Controller
Organizer pane of the main RSLogix 5000 window. This controller tag structure is arranged as a tree structure. Individual controller tags are found at the lowest level of the tree structure. Each individual controller tag is defined to hold data of a specific type, such as integer or floating-point data.
The Add-On Instruction also includes user-defined data types (UDTs). UDTs are collections of data types and declares the data types for the controller tag structures.
The MVI69E-MBS Add-On Instruction is extensively commented to provide information on the purpose and function of each user-defined data type and controller tag. For most applications, the Add-On Instruction works without needing any modification.
ProSoft Technology, Inc.
June 28, 2017
Page 75 of 154
Using Controller Tags
User Manual
5.1.1 MVI69E-MBS Controller Tags
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The main controller tag structure, MBS, is broken down into five lower-level controller tag structures.
The five lower-level controller tag structures contain other controller tags and controller tag structures. Click the [+] sign next to any controller tag structure to expand it and view the next level in the structure.
For example, if you expand the MBS.DATA controller tag structure, you see that it contains two controller tag arrays, MBS.DATA.ReadData and
MBS.DATA.WriteData, which are 600-element integer arrays by default.
The controller tags in the Add-On Instruction are commented in the D
ESCRIPTION
column.
Notice that the D
ATA
T
YPE
column displays the data types used to declare each controller tag, controller tag array or controller tag structure. Individual controller tags are declared with basic data types, such as INT and BOOL. Controller tag arrays are declared with arrays of basic data types. Controller tag structures are declared with user-defined data types (UDTs).
Page 76 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5.2 User-Defined Data Types (UDTs)
Using Controller Tags
User Manual
User-defined data types (UDTs) allow you to organize collections of data types into groupings. You can use these groupings, or data type structures, to declare the data types for controller tag structures. Another advantage of defining a UDT is that you may reuse it in other controller tag structures that use the same data types.
The Add-On Instruction for the MVI69E-MBS module has pre-defined UDTs. You can find them in the User-Defined subfolder, located in the Data Types folder in the Controller Organizer pane of the main RSLogix window. Like the controller tags, the UDTs are organized in a multiple-level tree structure.
5.2.1 MVI69E-MBS User-Defined Data Types
Twenty different UDTs are defined for the MVI69E-MBS Add-On Instruction. The main UDT, MBSMODULEDEF, contains all the data types for the module and was used to create the main controller tag structure, MBS. There are five UDTs one level below MBSMODULEDEF. These lower-level UDTs were used to create the MBS.CONFIG, MBS.DATA, MBS. CONTROL, MBS.STATUS, and MBS.UTIL controller tag structures.
Click the [+] signs to expand the UDT structures and view lower-level UDTs.
ProSoft Technology, Inc.
June 28, 2017
Page 77 of 154
Using Controller Tags
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
For example, if you expand MBS.DATA, you see that it contains two UDTs,
ReadData and WriteData. Both of these are 600-element integer arrays by default.
Notice that these UDTs are the data types used to declare the
MBS.DATA.ReadData and MBS.DATA.WriteData controller tag arrays.
The UDTs are commented in the D
ESCRIPTION
column.
Page 78 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Using Controller Tags
User Manual
Tip: If more than 600 words of Read or Write Data are needed, the MBS.DATA.ReadData and
MBS.DATA.WriteData controller tag arrays can be expanded. Simply edit the size of the ReadData or WriteData integer array in the D
ATA
T
YPE
column of the MBSDATA UDT. In the example below, the ReadData array size has been changed to 2000. Save and download the ladder program for this change to take effect.
5.3 MBS Controller Tag Overview
This and the following sections describe the MBS controller tags in detail.
Tag Name
MBS.CONFIG
MBS.DATA
MBS.CONTROL
MBS.STATUS
MBS.UTIL
Description
Configuration information
MBS input and output data transferred between the processor and the module
Governs the data movement between the PLC rack and the module
Status information
Generic tags used for internal ladder processing (DO NOT
MODIFY)
ProSoft Technology, Inc.
June 28, 2017
Page 79 of 154
Using Controller Tags
User Manual
5.3.1 MBS.CONFIG
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
When ProSoft Configuration Builder (PCB) downloads the configuration file from the PC to the processor, the processor stores the configuration file data in the
MBS.CONFIG.FileData array. Its CRC is also included in this array.
You cannot edit this array directly. You must use PCB to edit the module configuration since PCB calculates a unique CRC to protect data integrity. Any change to the configuration parameters directly in this array will not match the calculated CRC.
Tag Name
MBS.CONFIG.FileData
MBS.CONFIG.FileSize
MBS.CONFIG.FileCRC32
MBS.CONFIG.FileStatus
Description
This parameter contains the MBS configuration data after it has been downloaded from PCB. It is displayed in ASCII format.
Note: MBS configuration changes cannot be made directly in this array; the configuration must be downloaded with PCB.
Configuration file size (MBS.CONFIG.FileData array) in bytes.
CRC checksum of the configuration file stored in the array.
Configuration file status. 0 = No file present, 1 = File present
5.3.2 MBS.DATA
This structure contains the Read Data and Write Data arrays for processor-tomodule communication.
Tag Name
MBS.DATA.ReadData
MBS.DATA.WriteData
Description
Data area copied from the module to the processor. This array stores the Modbus data coming into the module from the
Modbus network.
Data area copied from the processor to the module. This array stores the outgoing data sent from the module to the Modbus network.
5.3.3 MBS.CONTROL
This array handles special tasks requested by the processor.
MBS.CONTROL.PortControl
This array allows port commands to be controlled by the processor.
Tag Name
MBS.CONTROL.PortControl.
Set
MBS.CONTROL.PortControl.
Get
MBS.CONTROL.PortControl.
Portx
MBS.CONTROL.PortControl.
Portx.Active
MBS.CONTROL.PortControl.
Portx.CmdEnableBits[x]
Range
0 or 1
0 or 1 n/a
0 or 1
0 or 1
Description
Sends Port Control to module
Reads Port Control from module
Definition of Port x Control
Port Control: Disable = 0, Enable = 1
Index of command to be controlled. Example:
Command 20 in port 1 command list can be controlled at CmdEnableBits[1].3. This is the 20 th
bit offset.
Page 80 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Using Controller Tags
User Manual
MBS.CONTROL.CmdControl
This array allows the processor to dynamically enable configured commands for execution.
Range
0 or 1
Tag Name
MBS.CONTROL.CmdControl.
CmdControlTrigger
MBS.CONTROL.CmdControl.
NumberOfCommands
MBS.CONTROL.CmdControl.
PortNumber
MBS.CONTROL.CmdControl.
CommandIndex[x]
0 to 6
1 or 2
0 or 1
Description
Command Control:
Disable = 0, Enable = 1
Total number of commands to be executed via
Command Control
Port number to be associated with Command Control function
Command Index of port command [x] to be enabled.
Up to 6 command indexes can be populated at a time.
MBS.CONTROL.EventCmd_DBData
This array allows the processor to dynamically build Modbus commands with data associated to the MBS database. This feature is meant for periodic execution such as resetting the clock and zeroing-out counters.
Tag Name
MBS.CONTROL.EventCmd_DB
Data.EventCmdTrigger
MBS.CONTROL.EventCmd_DB
Data.PortNumber
MBS.CONTROL.EventCmd_DB
Data.SlaveID
MBS.CONTROL.EventCmd_DB
Data.InternalDBAddress
Range
0 or 1
Description
Toggle to send Event Command.
0 = Disable, 1 = Enable
1 or 2 Port number to be associated with command Control function
1 to 248 Slave ID of Modbus slave
0 to 9999 Used only if UseModuleDBAddress=1. MVI69E database address (word address for functions
3,4,6,16 and bit address for 1,2,5,15)
0 to 125 Number of bit/words associated with this command. MBS.CONTROL.EventCmd_DB
Data.PointCount
MBS.CONTROL.EventCmd_DB
Data.SwapCode
MBS.CONTROL.EventCmd_DB
Data.ModbusFunctionCode
MBS.CONTROL.EventCmd_DB
Data.DeviceDBAddress
MBS.CONTROL.EventCmd_DB
Data.EventCmdStatusReturned
0 to 3
-
Swap code 0 = no swap, 1 = word swap, 2 = words
& byte swap, 3 = byte swap
Modbus function code (1,2,3,4,5,6,15, or 16)
0 to 9999 Modbus address of the target slave database
- Event status returned by the module
ProSoft Technology, Inc.
June 28, 2017
Page 81 of 154
Using Controller Tags
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MBS.CONTROL.EventCmd_ProcessorData
This array allows the processor to dynamically build Modbus commands with processor data. This feature is meant for periodic execution such as resetting the clock and zeroing-out counters.
Range
0 or 1
Tag Name
MBS.CONTROL.EventCmd_Processor
Data.CmdTrigger
MBS.CONTROL.EventCmd_Processor
Data.GetStatusTrigger
MBS.CONTROL.EventCmd_Processor
Data.PortNumber
MBS.CONTROL.EventCmd_Processor
Data.SlaveAddress
MBS.CONTROL.EventCmd_Processor
Data.ModbusFunctionCode
MBS.CONTROL.EventCmd_Processor
Data.DeviceDBAddress
MBS.CONTROL.EventCmd_Processor
Data.PointCount
MBS.CONTROL.EventCmd_Processor
Data.Data[x]
MBS.CONTROL.EventCmd_Processor
Data.EventCmdStatusReturned
MBS.CONTROL.EventCmd_Processor
Data.PortxStatus
MBS.CONTROL.EventCmd_Processor
Data.PortxStatus.Status
MBS.CONTROL.EventCmd_Processor
Data.PortxStatus.LastError
0 or 1
1 or 2
1 to 248
-
0 to 9999
0 to 125
0 to 49
-
-
-
-
Description
Toggle to send Event Command.
0 = Disable, 1 = Enable
Toggle to retrieve event status.
0 = Disable, 1 = Enable
Port number to be associated with command
Slave ID of Modbus slave
Modbus function code (5,6,15, or 16)
Modbus address of the target slave database
Number of bit/words associated with this command.
Data values to be sent to the slave
Command status
Port x Status array
Status code. See Communication Error
Last error code
Page 82 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Using Controller Tags
User Manual
MBS.CONTROL.SlavePoll
This array allows the processor to enable, disable and retrieve status for slaves.
Tag Name Range
MBS.CONTROL.SlavePoll.Portx -
MBS.CONTROL.SlavePoll.Portx.
EnableSlaves
0 or 1
1 to 60 MBS.CONTROL.SlavePoll.Portx.
EnableSlaveCount
MBS.CONTROL.SlavePoll.Portx.
EnableSlavesIDs[x]
-
Description
Port x slave polling control
Slave Poll request
0 = Disable, 1 = Enable
Number of slaves to be enabled
MBS.CONTROL.SlavePoll.Portx.
DisableSlaves
MBS.CONTROL.SlavePoll.Portx.
DisableSlaveCount
MBS.CONTROL.SlavePoll.Portx.
DisableSlavesIDs[x]
0 or 1
1 to 60
-
Data array associated to enable slave request where word x corresponds to slave ID x (0-based).
1 = Enable slave
Triggers disable slaves request
0 = Disable, 1 = Enable
Number of slaves to be disabled
MBS.CONTROL.SlavePoll.Portx.
GetSlavesStatus
MBS.CONTROL.SlavePoll.Portx.
SlavesStatus[x]
0 or 1
-
Data array associated to disable slave request where word x corresponds to slave ID x (0-based).
1 = Disable slave
Triggers request to read slave status
0 = Disable, 1 = Enabled
Data array with status
MBS.CONTROL.Time
This array allows the processor to get or set module time.
Tag Name
SetTime
GetTime
Year
Month
Day
Hour
Minute
Second
Milliseconds
Range Description
0 or 1 Sends the PLC time to the module
0 = Disable, 1 = Enable
0 or 1 Retrieves the time from the module to PLC
0 = Disable, 1 = Enable
0 to 9999 Four digit year value. Example: 2015
1 to 12 Month
1 to 31 Day
0 to 23 Hour
0 to 59 Minute
0 to 59 Second
0 to 999 Millisecond
ProSoft Technology, Inc.
June 28, 2017
Page 83 of 154
Using Controller Tags
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
MBS.CONTROL.GetStatus
This tag allows the processor to retrieve status from the module.
Tag Name
GetStatus
Range
0 or 1
Description
Triggers status retrieval from the module
0 = Disable, 1 = Enable
MBS.CONTROL.ResetStatus
This tag allows the processor to reset the module status counters.
Tag Name
ResetStatus
Range
0 or 1
Description
Triggers module status counter reset
0 = Disable, 1 = Enable
MBS.CONTROL.ColdBoot
This tag allows the processor to Coldboot the module (full reboot).
Tag Name
ColdBoot
Range
0 or 1
Description
Triggers a cold boot of the module
0 = Disable, 1 = Enable
MBS.CONTROL.WarmBoot
This tag allows the processor to Warmboot the module (driver reboot).
Tag Name
WarmBoot
Range
0 or 1
Description
Triggers a warm boot the module
0 = Disable, 1 = Enable
Page 84 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5.3.4 MBS.STATUS
Using Controller Tags
User Manual
This array contains status data for the module.
Tag Name
MBS.STATUS.PassCnt
MBS.STATUS.Product
MBS.STATUS.Rev
MBS.STATUS.OP
MBS.STATUS.Run
MBS.STATUS.PortxStats
Description
Program cycle counter
– this value is incremented each time a complete program cycle occurs in the module
Product code
Firmware revision level number
Operating level number
Run number
Port x status
MBS.STATUS.PortxStats.CmdListReq Total number of requests made from this port to slave devices on the network
MBS.STATUS.PortxStats.CmdListResp
Total number of slave response messages received on the port
MBS.STATUS.PortxStats.CmdListErr Total number of command errors processed on the port.
These errors could be due to a bad response or command
MBS.STATUS.PortxStats.PortReq
MBS.STATUS.PortxStats.PortResp
Total number of messages sent out of the port
Total number of messages received on the port
MBS.STATUS.PortxStats.PortErrSent Total number of message errors sent out of the port.
MBS.STATUS.PortxStats.PortErrRec Total number of message errors received on the port
MBS.STATUS.PortxStats.CurrErr
MBS.STATUS.PortxStats.LastErr
MBS.STATUS.Block
MBS.STATUS.Block.Read
Not used
Not used
Backplane transfer status
MBS.STATUS.Block.Write
MBS.STATUS.Block.Parse
MBS.STATUS.Block.Event
Total number of read blocks transferred from the module to the processor
Total number of write blocks transferred from the processor to the module
Total number of blocks successfully parsed that were received from the processor
Total number of event command blocks received from the processor
MBS.STATUS.Block.Cmd
MBS.STATUS.Block.Err
MBS.STATUS.PortxLastErr
MBS.STATUS.PortxPreviousErr
Total number of command blocks received from the processor
Total number of block transfer errors recognized by the module
For a slave port, this field contains the value of the current error code returned.
For a master port, this field contains the index of the currently executing command.
For a slave port, this field contains the value of the last error code returned.
For a master port, this field contains the index of the command with an error.
ProSoft Technology, Inc.
June 28, 2017
Page 85 of 154
Using Controller Tags
User Manual
5.3.5 MBS.UTIL
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The array is used for internal ladder processing, and must not be modified.
Tag Name
MBS.UTIL.ReadDataSizeGet
MBS.UTIL.WriteDataSizeGet
MBS.UTIL.ReadDataBlkCount
MBS.UTIL.WriteDataBlkCount
MBS.UTIL.RBTSremainder
MBS.UTIL.WBTSremainder
MBS.UTIL.BlockIndex
MBS.UTIL.LastRead
MBS.UTIL.LastWrite
MBS.UTIL.LastWriteInit
MBS.UTIL.ConfigFile
Description
Holds Read Data array size
Holds Write Data array size
Number of Read Data blocks
– this value is the Read
Register Count divided by the Block Transfer Size
Number of Write Data blocks
– this value is the Write Register
Count divided by the Block Transfer Size
Remainder from the Read Register Count divided by the
Block Transfer Size
Remainder from the Write Register Count divided by the
Block Transfer Size
Computed block offset for data
Latest Read Block ID received from the module
Latest Write Block ID to be sent to the module
Latest Write Block ID used during initialization
Holds variables for configuration file transfer
MBS.UTIL.ConfigFile.WordLength Length of configuration data to be included in block transfer
MBS.UTIL.ConfigFile.BlockCount Not used
MBS.UTIL.ConfigFile.FileOffset Offset in configuration file to use as a starting point for copying over configuration data
MBS.UTIL.ConnectionInputSize
MBS.UTIL.BlockTransferSize
Holds size of the Connection Input array
Size of the backplane transfer blocks
MBS.UTIL.SlotNumber
MBS.UTIL.EventBlockID
MBS.UTIL.EventCmdPending
MBS.UTIL.PollStatusOffset
MBS.UTIL.CmdsAddedToQueue
Slot number of the module in the rack
Holds Block ID for Event Command
Keeps an Event Command message from being sent to the module before the previous Event Command is completed
Offset in slave status data array to use as a starting point for copying over slave status data
Number of Command Control messages added to the command queue
MBS.UTIL.CmdControlBlockID
MBS.UTIL.CmdCntrlPending
Holds Block ID for Command Control
Keeps a Command Control message from being sent to the module before the previous Command Control is completed
MBS.UTIL.EventDataCmdPending Keeps an Event Command with Data message from being sent to the module before the previous Event Command with
Data is completed
MBS.UTIL.BootTimer
MBS.UTIL.PassThru[ ] Array
Timer used to clear both cold and warm boot requests
Holds variables used for processing pass-through messages
Page 86 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Diagnostics and Troubleshooting
User Manual
6 Diagnostics and Troubleshooting
In This Chapter
Connecting the PC to the Module's Ethernet Port ................................. 90
Using the Diagnostics Menu in PCB ...................................................... 93
Communication Error Codes ............................................................... 100
Connecting to the Module’s Web Page ............................................... 101
The MVI69E-MBS provides information on diagnostics and troubleshooting in the following forms:
LED status indicators on the front of the module provide general information on the module's status.
You can view status data contained in the module through the Ethernet port, using the troubleshooting and diagnostic capabilities of ProSoft Configuration
Builder (PCB).
You can transfer status data values from the module to processor memory and can monitor them in the processor manually or by customer-created logic.
ProSoft Technology, Inc.
June 28, 2017
Page 87 of 154
Diagnostics and Troubleshooting
User Manual
6.1 Ethernet LED Indicators
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The Ethernet LEDs indicate the module's Ethernet port status.
LED
Data
Link
State Description
OFF Ethernet connected at 10Mbps duplex speed
AMBER Solid Ethernet connected at 100Mbps duplex speed
OFF No physical network connection is detected. No Ethernet communication is possible. Check wiring and cables.
GREEN Solid or Blinking
Physical network connection detected. This LED must be ON solid for Ethernet communication to be possible.
6.2 LED Status Indicators
The LEDs indicate the module’s operating status.
LED
ETH
P1
P2
CFG
BP
OK
Status
On
Off
Green
Red
Off
Green
Red
Off
Green
Yellow
Red
Off
Green
Red
Green
Red
Indication
Ethernet communications are ok
No Ethernet cable connected
Data is being transferred between the module and the Modbus network on Port 1
Communication error detected
No Modbus network activity detected
Data is being transferred between the module and the Modbus network on Port 2
Communication error detected
No Modbus network activity detected
Configuration is ok
Module is reading configuration
Error setting up Modbus protocol driver, failed startup, or module shutting down
Processor is in Program mode
The LED is on when the module is performing a write operation on the backplane. Under normal operation, the LED should blink rapidly on and off.
Major fault or module shutting down
Module is ok
The program has detected an error or is being configured. If the
LED remains red for over 10 seconds, the program has probably halted.
During module configuration, the OK LED is red and the BP ACT LED is on. If the APP, BP ACT and OK LEDs blink at a rate of every one-second, this indicates a serious problem with the module. Call ProSoft Technology Technical
Support to arrange for repairs.
Page 88 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.2.1 Clearing a Fault Condition
Diagnostics and Troubleshooting
User Manual
Typically, if the OK LED on the front of the module remains RED for more than ten seconds, a hardware problem has been detected or the program has exited.
To clear the condition, follow these steps:
1 Turn off power to the rack.
2 Remove the card from the rack.
3 Verify that all jumpers are set correctly.
4 If the module requires a Compact Flash card, verify it is installed correctly.
5 Re-insert the card in the rack and turn the power back on.
6 Verify correct configuration data is being transferred to the module from the
CompactLogix or MicroLogix 1500-LRP controller.
If the module's OK LED does not turn GREEN, verify that the module is inserted completely into the rack. If this does not cure the problem, contact ProSoft
Technology Technical Support.
6.2.2 Troubleshooting
Use the following troubleshooting steps if you encounter problems when the module is powered up. If these steps do not resolve your problem, please contact
ProSoft Technology Technical Support.
Processor Errors
Problem description Steps to take
Processor fault Verify that the module is securely plugged into the slot that has been configured for the module in the I/O Configuration in RSLogix.
Verify that the slot location in the rack has been configured correctly in the ladder logic.
Processor I/O LED flashes
This indicates a problem with backplane communications. A problem could exist between the processor and any installed I/O module, not just the MVI69E-MBS. Verify that all modules in the rack are correctly configured.
Module Errors
Problem description Steps to take
BP ACT LED (not present on MVI56E modules) remains OFF or blinks slowly
MVI69 modules with scrolling LED display:
<Backplane Status> condition reads ERR
This indicates that backplane transfer operations are failing. Connect to the module’s Configuration/Debug port to check this.
To establish backplane communications, verify the following items:
The processor is in RUN or REM RUN mode.
The backplane driver is loaded in the module.
The module is configured for read and write data block transfer.
The ladder logic handles all read and write block situations.
The module is properly configured in the processor I/O configuration and ladder logic.
OK LED remains RED The program has halted or a critical error has occurred. Connect to the
Configuration/Debug (or Communication) port to see if the module is running. If the program has halted, turn off power to the rack, remove the card from the rack, then re-insert it, and then restore power to the rack.
ProSoft Technology, Inc.
June 28, 2017
Page 89 of 154
Diagnostics and Troubleshooting
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.3 Connecting the PC to the Module's Ethernet Port
With the module securely mounted, connect one end of the Ethernet cable to the
ETH1 Port, and the other end to an Ethernet hub or switch accessible from the same network as the PC. Or, connect directly from the Ethernet Port on the PC to the ETH
1
Port on the module.
6.3.1 Setting Up a Temporary IP Address
Important: ProSoft Configuration Builder (PCB) locates MVI69E-MBS modules through UDP broadcast messages. These messages may be blocked by routers or layer 3 switches. In that case, ProSoft Discovery Service is unable to locate the modules.
To use ProSoft Configuration Builder, arrange the Ethernet connection so that there is no router/ layer 3 switch between the computer and the module, OR reconfigure the router/ layer 3 switch to allow routing of the UDP broadcast messages.
1 In the tree view in ProSoft Configuration Builder (PCB), select the MVI69E-
MBS
module. (For instructions on opening and using a project in PCB, please
refer to Configuring the MVI69E-MBS Using PCB (page 43).
Page 90 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Diagnostics and Troubleshooting
2 Right-click the module icon in the tree and choose D
IAGNOSTICS
.
User Manual
3 In the Diagnostics window, click the S
ET
U
P
C
ONNECTION
button.
4 In the Connection Setup dialog box, click B
ROWSE
D
EVICE
(
S
)
to start ProSoft
Discovery Service. Right-click the module and choose A
SSIGN
T
EMPORARY
IP.
Page 91 of 154 ProSoft Technology, Inc.
June 28, 2017
Diagnostics and Troubleshooting
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
5
The module’s default IP address is usually 192.168.0.250. Choose an unused
IP within your subnet, and then click OK.
Important: The temporary IP address is only valid until the next time the module is initialized. For
information on how to set the module’s permanent IP address, see Ethernet 1 (page 55).
6 Close the ProSoft Discovery Service window. Enter the temporary IP address in the E
THERNET ADDRESS
field of the Connection Setup dialog box, then click
T
EST
C
ONNECTION
to verify that the module is accessible with the current settings.
7 If the Test Connection is successful, click C
ONNECT
. The Diagnostics window is now accessible.
Page 92 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.4 Using the Diagnostics Menu in PCB
Diagnostics and Troubleshooting
User Manual
ProSoft Configuration Builder (PCB) provides diagnostic menus for debugging and troubleshooting.
To connect to the module’s Configuration/Debug Ethernet port
1 In the tree view in ProSoft Configuration Builder, right-click the MVI69E-MBS module and then choose D
IAGNOSTICS
. For instructions on opening and using a project in PCB, please refer to Configuring the MVI69E-MBS Using PCB
2 After the Diagnostics window opens, click the S
ET UP
C
ONNECTION
button to browse for the module’s IP address.
ProSoft Technology, Inc.
June 28, 2017
Page 93 of 154
Diagnostics and Troubleshooting
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
3 In the Ethernet field of the Connection Setup dialog box, enter the current IP address, whether it is temporary or permanent. Click T
EST
C
ONNECTION
to verify that the module is accessible with the current settings.
4 If the T
EST
C
ONNECTION
is successful, click C
ONNECT
. The Diagnostics window is now visible.
Page 94 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.4.1 Diagnostics Menu
Diagnostics and Troubleshooting
User Manual
In the Diagnostics window in ProSoft Configuration Builder, the Diagnostics menu is available through the Ethernet configuration port. The menu is arranged as a tree structure.
ProSoft Technology, Inc.
June 28, 2017
Page 95 of 154
Diagnostics and Troubleshooting
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.4.2 Monitoring Network Configuration Information
In the Diagnostics window in Prosoft Configuration Builder, click NETWORK and then click C
ONFIG
to view the Ethernet network configuration information.
Page 96 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.4.3 Monitoring Backplane Information
Diagnostics and Troubleshooting
User Manual
In the Diagnostics window in ProSoft Configuration Builder, click BACKPLANE to view the backplane information. This menu has two submenus:
C
ONFIGURATION
S
TATUS
ProSoft Technology, Inc.
June 28, 2017
Page 97 of 154
Diagnostics and Troubleshooting
User Manual
6.4.4 Port x Module Information
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The MODBUS PORT 1 and MODBUS PORT 2 menus include the following submenus:
Configuration
Status (General status for the port)
Master Commands (Used when port is configured as a Modbus master)
Slave Status List (Status of each slave on the network, used when port is configured as a Modbus master)
Master Command Status (Status code for each master command, used when port is configured as a Modbus master)
Page 98 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Diagnostics and Troubleshooting
User Manual
6.4.5
Monitoring Data Values in the Module’s Database
In the Diagnostics window in ProSoft Configuration Builder, click DATABASE and then click D
ECIMAL
to view the contents of the MVI69E-
MBS module’s internal database. You can view data values in ASCII, Hexadecimal, and Float format.
ProSoft Technology, Inc.
June 28, 2017
Page 99 of 154
Diagnostics and Troubleshooting
User Manual
6.5 Communication Error Codes
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Note: If an error code is reported that is not listed below, check with the documentation of the
Modbus device(s) on the module's application ports. Modbus devices can produce device-specific error codes.
4
5
6
Code
1
2
3
6.5.1 Standard MODBUS Protocol Exception Code Errors
Description
Illegal Function Code
Illegal Data Address
Illegal Data Value
Failure in Associated Device
Acknowledge
Busy, Rejected Message
Code
-1
-2
-11
253
254
255
6.5.2 Module Communication Error Codes
Description
CTS modem control line not set before transmit
Timeout while transmitting message
Timeout waiting for response after request
Incorrect slave address in response
Incorrect function code in response
Invalid CRC/LRC value in response
Code
-41
-42
-43
-44
-45
-46
6.5.3 Command List Entry Errors
Description
Invalid enable code
Internal address > maximum address
Invalid node address (< 0 or > 255)
Count parameter set to 0
Invalid function code
Invalid swap code
Page 100 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
6.6
Connecting to the Module’s Web Page
Diagnostics and Troubleshooting
User Manual
The module’s internal web server provides access to module version and status information, as well as the ability to set the date and time, reboot the module, and download firmware upgrade to the module. Enter the assigned IP address of the module into a web browser or use the following steps in PCB.
1 In the PCB Diagnostics window, click the S
ET
U
P
C
ONNECTION
button.
2 In the Connection Setup dialog box, click B
ROWSE
D
EVICE
(
S
)
to start ProSoft
Discovery Service.
3 Right-click the module icon and choose V
IEW
M
ODULE
’
S
W
EBPAGE
to launch your default browser and display the module’s webpage.
ProSoft Technology, Inc.
June 28, 2017
Page 101 of 154
Diagnostics and Troubleshooting
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Page 102 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Reference
User Manual
7 Reference
In This Chapter
About the Modbus Protocol ................................................................. 104
Ethernet Port Connection .................................................................... 145
Modbus Application Port Connection .................................................. 146
7.1 Product Specifications
The MVI69E-MBS allows Rockwell Automation
®
CompactLogix or MicroLogix
1500-LRP
®
I/O compatible processors to interface easily with other Modbus protocol compatible devices.
The module acts as an input/output communications module between the
Modbus network and the CompactLogix or MicroLogix 1500-LRP backplane. The data transfer from the CompactLogix or MicroLogix 1500-LRP processor is asynchronous from the actions on the Modbus network. Databases are userdefined and stored in the module to hold the data required by the protocol.
Single-slot, 1769 backplane-compatible
The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module.
Ladder Logic is used for data transfer between module and processor.
Sample Add-On Instruction file included.
Configuration data obtained from and stored in the processor.
Supports CompactLogix or MicroLogix 1500-LRP processors with 1769 I/O bus capability and at least 500 mA of 5 VDC backplane current available.
ProSoft Technology, Inc.
June 28, 2017
Page 103 of 154
Reference
User Manual
7.1.1 Hardware Specifications
Specification
Dimensions
Current Load
Operating Temp.
Storage Temp.
Relative Humidity
LED Indicators
CFG Port (ETH)
App Ports (P1,P2)
Shipped with Unit
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Description
Standard 1769 Single-slot module
500 mA max @ 5 VDC
Power supply distance rating of 4 (L43 and L45 installations on first 4 slots of 1769 bus)
32° F to 140° F (0° C to 60°C)
-40° F to 185° F (-40° C to 85° C)
5% to 95% (with no condensation)
Module OK Status
Backplane Activity
Ethernet Port Activity
Configuration Activity
Diagnostics over Ethernet connection
RS-232, RS-485 or RS-422 (jumper selectable)
RJ45 Port (DB-9F with supplied cable)
500V Optical isolation from backplane
RJ45 to DB-9M cables for each application port
7.1.2 General Specifications - Modbus Master/Slave
Communication
Parameters
Baud rate: 110 to 115K baud
Stop bits: 1 or 2
Data size: 7 or 8 bits
Parity: None, Even, Odd
RTS timing delays: 0 to 65535 milliseconds
Modbus Modes RTU mode (binary) with CRC-16
ASCII mode with LRC error checking
Floating-Point
Data
Modbus Function
Codes Supported
Floating-point data movement supported, including configurable support for Enron, Daniel
®
, and other implementations
1: Read Coil Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single
Holding Register
8: Diagnostics (Slave Only,
Responds to
Subfunction 00)
15: Force( Write) Multiple Coils
16: Preset (Write) Multiple
Holding Registers
17: Report Slave ID (Slave Only)
22: Mask Write Holding
Register (Slave Only)
23: Read/Write Holding
Registers (Slave Only)
Page 104 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2 About the Modbus Protocol
Reference
User Manual
Modbus is a widely-used protocol originally developed by Modicon in 1978. Since that time, the protocol has been adopted as a standard throughout the automation industry.
The original Modbus specification uses a serial connection to communicate commands and data between Master and Slave devices on a network. Later enhancements to the protocol allow communication over other types of networks.
Modbus is a Master/Slave protocol. The Master establishes a connection to the remote Slave. When the connection is established, the Master sends the Modbus commands to the Slave. The MVI69E-MBS module can work as a Master and as a Slave.
The MVI69E-MBS module also works as an input/output module between itself and the Rockwell Automation backplane and CompactLogix or MicroLogix 1500-
LRP processor. The module uses an internal database to pass data and commands between the processor and Master and Slave devices on Modbus networks.
7.2.1 Modbus Master
A port configured as a virtual Modbus Master actively issues Modbus commands to other nodes on the Modbus network, supporting up to 250 commands on each port. The Master ports have an optimized polling characteristic that polls slaves with communication problems less frequently.
Command List Up to 250 commands per Master port, each fully configurable for function, slave address, register to/from addressing and word/bit count.
Polling of command list Configurable polling of command list, including continuous and on change of data, and dynamically user or automatic enabled.
Status Data Error codes available on an individual command basis. In addition, a slave status list is maintained per active
Modbus Master port.
7.2.2 Modbus Slave
A port configured as a Modbus slave permits a remote Master to interact with all data contained in the module. This data can be derived from other Modbus slave devices on the network, through a Master port, or from the CompactLogix or
MicroLogix 1500-LRP processor.
Node address
Status Data
1 to 247 (software selectable)
Error codes, counters and port status available per configured slave port
ProSoft Technology, Inc.
June 28, 2017
Page 105 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.3 Function Codes Supported by the Module
The format of each command in the list depends on the Modbus Function Code being executed. The following table lists the Function Codes supported by the
MVI69E-MBS module.
5
6
8
15
16
17
22
23
Function Code Definition
1
2
3
4
Read Coil Status 0x
Read Input Status 1x
Supported as Master
X
X
Read Holding Registers 4x X
Read Input Registers 3x X
Supported as Slave
X
X
X
X
Set Single Coil 0x
Single Register Write 4x
Diagnostics
Multiple Coil Write 0x
Multiple Register Write 4x
Report Slave ID
Mask Write 4X
Read/Write
X
X
X
X
X
X
X
X
X
X
X
X
Each command list record has the same general format. The first part of the record contains the information relating to the communication module and the second part contains information required to interface to the Modbus slave.
7.2.4 Read Coil Status (Function Code 01)
Query
This function allows you to obtain the ON/OFF status of logic coils (Modbus 0x range) used to control discrete outputs from the addressed slave only. Broadcast mode is not supported with this function code. In addition to the slave address and function fields, the message requires that the information field contain the initial coil address to be read (Starting Address) and the number of locations that are interrogated to obtain status data.
The addressing allows up to 2000 coils to be obtained at each request; however, the specific slave device may have restrictions that lower the maximum quantity.
The coils are numbered from zero; (coil number 1 = zero, coil number 2 = one, coil number 3 = two, and so on).
The following table is a sample read output status request to read coils 0020 to
0056 (37 coils) from slave device number 11.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display
Page 106 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Node
Address
0B
Function
Code
01
Data Start
Point High
00
Data Start
Point Low
13
Number of
Points High
00
Number of
Points Low
25
Error Check
Field (2 bytes)
CRC
Reference
User Manual
Response
An example response to Read Coil Status is as shown in the table below. The data is packed one bit for each coil. The response includes the slave address, function code, quantity of data characters, the data characters, and error checking. Data is packed with one bit for each coil (1 = ON, 0 = OFF). The low order bit of the first character contains the addressed coil, and the remainder follows. For coil quantities that are not even multiples of eight, the last characters are filled in with zeros at high order end. The quantity of data characters is always specified as quantity of RTU characters, that is, the number is the same whether RTU or ASCII is used.
Because the slave interface device is serviced at the end of a controller's scan, data reflects coil status at the end of the scan. Some slaves limit the quantity of coils provided each scan; thus, for large coil quantities, multiple PC transactions must be made using coil status from sequential scans.
Node
Address
Func
Code
Byte
Count
Data Coil
Status 20 to 27
Data Coil
Status 28 to 35
Data Coil
Status 36 to 43
Data Coil
Status 44 to 51
Data Coil
Status 52 to 56
Error Check
Field
(2 bytes)
0B 01 05 CD 6B B2 OE 1B CRC
The status of coils 20 to 27 is shown as CD (HEX) = 1100 1101 (Binary).
Reading from left to right, this shows that coils 27, 26, 23, 22, and 20 are all on.
The other Data Coil Status bytes are decoded similarly. Due to the quantity of coil statuses requested, the last data field, which is shown 1B (HEX) = 0001 1011
(Binary), contains the status of only 5 coils (52 to 56) instead of 8 coils. The 3 left most bits are provided as zeros to fill the 8-bit format.
7.2.5 Read Input Status (Function Code 02)
Query
This function allows you to obtain the ON/OFF status of discrete inputs (Modbus
1x range) in the addressed slave. PC Broadcast mode is not supported with this function code. In addition to the slave address and function fields, the message requires that the information field contain the initial input address to be read
(Starting Address) and the number of locations that are interrogated to obtain status data.
The addressing allows up to 2000 inputs to be obtained at each request; however, the specific slave device may have restrictions that lower the maximum quantity. The inputs are numbered form zero; (input 10001 = zero, input 10002 = one, input 10003 = two, and so on, for a 584).
ProSoft Technology, Inc.
June 28, 2017
Page 107 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The following table is a sample read input status request to read inputs 10197 to
10218 (22 coils) from slave number 11.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
0B
Function
Code
02
Data Start
Point High
00
Data Start
Point Low
C4
Number of
Points High
00
Number of
Points Low
16
Error Check
Field (2 bytes)
CRC
Response
An example response to Read Input Status is as shown in the table below. The data is packed one bit for each input. The response includes the slave address, function code, quantity of data characters, the data characters, and error checking. Data is packed with one bit for each input (1=ON, 0=OFF). The lower order bit of the first character contains the addressed input, and the remainder follows. For input quantities that are not even multiples of eight, the last characters are filled in with zeros at high order end. The quantity of data characters is always specified as a quantity of RTU characters, that is, the number is the same whether RTU or ASCII is used.
Because the slave interface device is serviced at the end of a controller's scan, the data reflect input status at the end of the scan. Some slaves limit the quantity of inputs provided each scan; thus, for large coil quantities, multiple PC transactions must be made using coil status for sequential scans.
Node
Address
0B
Func
Code
02
Byte
Count
03
Data Discrete
Input 10197 to
10204
AC
Data Discrete
Input 10205 to
10212
DB
Data Discrete
Input 10213 to
10218
35
Error Check
Field
(2 bytes)
CRC
The status of inputs 10197 to 10204 is shown as AC (HEX) = 10101 1100
(binary). Reading left to right, this show that inputs 10204, 10202, and 10199 are all on. The other input data bytes are decoded similar.
Due to the quantity of input statuses requested, the last data field which is shown as 35 HEX = 0011 0101 (binary) contains the status of only 6 inputs (10213 to
102180) instead of 8 inputs. The two left-most bits are provided as zeros to fill the 8-bit format.
Page 108 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.6 Read Holding Registers (Function Code 03)
Reference
User Manual
Query
This function allows you to retrieve the contents of holding registers 4xxxx
(Modbus 4x range) in the addressed slave. The registers can store the numerical values of associated timers and counters which can be driven to external devices. The addressing allows retrieving up to 125 registers at each request; however, the specific slave device may have restrictions that lower this maximum quantity. The registers are numbered form zero (40001 = zero, 40002 = one, and so on). The broadcast mode is not allowed.
The example below reads registers 40108 through 40110 (three registers) from slave number 11.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
Function
Code
03
Data Start
Registers
High
00
Data Start
Registers Low
Data Number of Registers
High
6B 00
Data Number of Registers
Low
03
Error Check
Field
(2 bytes)
CRC 0B
Response
The addressed slave responds with its address and the function code, followed by the information field. The information field contains 1 byte describing the quantity of data bytes to be returned. The contents of the registers requested
(DATA) are two bytes each, with the binary content right justified within each pair of characters. The first byte includes the high order bits and the second, the low order bits.
Because the slave interface device is normally serviced at the end of the controller's scan, the data reflect the register content at the end of the scan.
Some slaves limit the quantity of register content provided each scan; thus for large register quantities, multiple transmissions are made using register content from sequential scans.
In the example below, the registers 40108 to 40110 have the decimal contents
555, 0, and 100 respectively.
Node
Address
Function
Code
0B 03
Byte
Count
06
High
Data
02
Low
Data
2B
High
Data
00
Low
Data
00
High
Data
00
Low
Data
64
Error Check
Field
(2 bytes)
CRC
ProSoft Technology, Inc.
June 28, 2017
Page 109 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.7 Read Input Registers (Function Code 04)
Query
This function retrieves the contents of the controller's input registers from the
Modbus 3x range. These locations receive their values from devices connected to the I/O structure and can only be referenced, not altered from within the controller, The addressing allows retrieving up to 125 registers at each request; however, the specific slave device may have restrictions that lower this maximum quantity. The registers are numbered for zero (30001 = zero, 30002 = one, and so on). Broadcast mode is not allowed.
The example below requests the contents of register 30009 in slave number 11.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
Function
Code
Data Start
Point High
Data Start
Point Low
Data Number of Points High
Data Number of Points Low
00 01
Error Check
Field
(2 bytes)
CRC 0B 04 00 08
Response
The addressed slave responds with its address and the function code followed by the information field. The information field contains 1 byte describing the quantity of data bytes to be returned. The contents of the registers requested (DATA) are
2 bytes each, with the binary content right justified within each pair of characters.
The first byte includes the high order bits and the second, the low order bits.
Because the slave interface is normally serviced at the end of the controller's scan, the data reflect the register content at the end of the scan. Each PC limits the quantity of register contents provided each scan; thus for large register quantities, multiple PC scans are required, and the data provided is from sequential scans.
In the example below the register 30009 contains the decimal value 0.
Node
Address
0B
Function
Code
04
Byte Count Data Input
Register High
02 00
Data Input
Register Low
00
Error Check
Field
(2 bytes)
CRC
Page 110 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.8 Force Single Coil (Function Code 05)
Reference
User Manual
Query
This Function Code forces a single coil (Modbus 0x range) either ON or OFF.
Any coil that exists within the controller can be forced to either state (ON or
OFF). However, because the controller is actively scanning, unless the coil is disabled, the controller can also alter the state of the coil. Coils are numbered from zero (coil 0001 = zero, coil 0002 = one, and so on). The data value 65,280
(FF00 HEX) sets the coil ON and the value zero turns it OFF; all other values are illegal and do not affect that coil.
The use of slave address 00 (Broadcast Mode) forces all attached slaves to modify the desired coil.
Note: Functions 5, 6, 15, and 16 are the only messages that are recognized as valid for broadcast.
The example below is a request to slave number 11 to turn ON coil 0173.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
0B
Function
Code
05
Data Start Bit
High
00
Data Start Bit
Low
AC
Number of
Bits High
FF
Number of
Bits Low
00
Error Check
Field (2 bytes)
CRC
Response
The normal response to the Command Request is to re-transmit the message as received after the coil state has been altered.
Node
Address
Function
Code
Data Coil Bit
High
Data Coil Bit
Low
Data On/Off Data Error Check
Field (2 bytes)
0B 05 00 AC FF 00 CRC
The forcing of a coil via Modbus function 5 happens regardless of whether the addressed coil is disabled or not (In ProSoft products, the coil is only affected if
you implement the necessary ladder logic).
Note: The Modbus protocol does not include standard functions for testing or changing the
DISABLE state of discrete inputs or outputs. Where applicable, this may be accomplished via device specific Program commands (In ProSoft products, this is only accomplished through ladder
logic programming).
ProSoft Technology, Inc.
June 28, 2017
Page 111 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Coils that are reprogrammed in the controller logic program are not automatically cleared upon power up. Thus, if such a coil is set ON by function Code 5 and
(even months later), an output is connected to that coil, the output is "hot".
7.2.9 Preset Single Register (Function Code 06)
Query
This Function Code allows you to modify the contents of a Modbus 4x range in the slave. This writes to a single register only. Any holding register that exists within the controller can have its contents changed by this message. However, because the controller is actively scanning, it also can alter the content of any holding register at any time. The values are provided in binary up to the maximum capacity of the controller. Unused high order bits must be set to zero.
When used with slave address zero (Broadcast mode), all slave controllers load the specified register with the contents specified.
Note Functions 5, 6, 15, and 16 are the only messages that are recognized as valid for broadcast.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
The example below is a request to write the value ‘3’ to register 40002 in slave
11.
Node
Address
0B
Function
Code
06
Data Start Bit
High
00
Data Start
Bit Low
01
Preset Data
Register High
00
Preset Data
Register Low
03
Error Check
Field (2 bytes)
CRC
Response
The response to a preset single register request is to re-transmit the query message after the register has been altered.
Node
Address
0B
Function
Code
06
Data Register
High
00
Data Register
Low
01
Preset Data
Register High
00
Preset Data
Register Low
03
Error Check
Field (2 bytes)
CRC
Page 112 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.10 Diagnostics (Function Code 08)
Reference
User Manual
This function provides a series of tests for checking the communication system between a master device and a slave, or for checking various internal error conditions within a slave.
The function uses a two-byte sub-function code field in the query to define the type of test to be performed. The slave echoes both the function code and subfunction code in a normal response. Some of the diagnostics commands cause data to be returned from the remote device in the data field of a normal response.
In general, issuing a diagnostic function to a remote device does not affect the running of the user program in the remote device. Device memory bit and register data addresses are not accessed by the diagnostics. However, certain functions can optionally reset error counters in some remote devices.
A server device can, however, be forced into 'Listen Only Mode' in which it monitors the messages on the communications system but not respond to them.
This can affect the outcome of your application program if it depends upon any further exchange of data with the remote device. Generally, the mode is forced to remove a malfunctioning remote device from the communications system.
Sub-function Codes Supported
Only Sub-function 00 is supported by the MVI69E-MBS module.
00 Return Query Data
The data passed in the request data field is to be returned (looped back) in the response. The entire response message should be identical to the request.
Sub-function
00 00
Data Field (Request)
Any
Data Field (Response)
Echo Request Data
Example and State Diagram
Here is an example of a request to remote device to Return Query Data. This uses a sub-function code of zero (00 00 hex in the two-byte field). The data to be returned is sent in the two-byte data field (A5 37 hex).
Request
Field Name
Function
Sub-function Hi
Sub-function Lo
Data Hi
Data Lo
ProSoft Technology, Inc.
June 28, 2017
(Hex)
08
00
00
A5
37
Response
Field Name
Function
Sub-function Hi
Sub-function Lo
Data Hi
Data Lo
(Hex)
08
00
00
A5
27
Page 113 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
The data fields in responses to other kinds of queries could contain error counts or other data requested by the sub-function code.
Page 114 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.11 Force Multiple Coils (Function Code 15)
Reference
User Manual
Query
This function forces each coil (Modbus 0x range) in a consecutive block of coils to a desired ON or OFF state. Any coil that exists within the controller can be forced to either state (ON or OFF). However, because the controller is actively scanning, unless the coils are disabled, the controller can also alter the state of the coil. Coils are numbered from zero (coil 00001 = zero, coil 00002 = one, and so on). The desired status of each coil is packed in the data field, one bit for each coil (1= ON, 0= OFF). The use of slave address 0 (Broadcast Mode) forces all attached slaves to modify the desired coils.
Note: Functions 5, 6, 15, and 16 are the only messages (other than Loopback Diagnostic Test) that are recognized as valid for broadcast.
The following example forces 10 coils starting at address 20 (13 HEX). The two data fields, CD =1100 and 00 = 0000 000, indicate that coils 27, 26, 23, 22, and
20 are to be forced on.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
Func
Code
Coil
Address
High
Coil
Address
Low
Number of
Coils High
Number of
Coils Low
Byte
Count
Force
Data High
20 to 27
Force
Data Low
28 to 29
Error Check
Field (2 bytes)
00 13 00 0A 02 CD 01 CRC 0B 0F
Response
The normal response is an echo of the slave address, function code, starting address, and quantity of coils forced.
Node
Address
Func
Code
0B 0F
Coil
Address
High
00
Coil
Address
Low
13
Number of
Coils High
00
Number of
Coils Low
0A
Error Check
Field (2 bytes)
CRC
Writing to coils with Modbus function 15 is accomplished regardless of whether the addressed coils are disabled or not.
Coils that are not programmed in the controller logic program are not automatically cleared upon power up. Thus, if such a coil is set ON by function code 15 and (even months later) an output is connected to that coil, the output is hot.
ProSoft Technology, Inc.
June 28, 2017
Page 115 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.2.12 Preset Multiple Registers (Function Code 16)
Query
This Function Code allows you to modify the contents of a Modbus 4x range in the slave. This writes up to 125 registers at time. Since the controller is actively scanning, it also can alter the content of any holding register at any time.
Note: Function codes 5, 6, 15, and 16 are the only messages that are recognized as valid for broadcast.
The example below is a request to write 2 registers starting at register 40002 in slave 11.
Note: This is the structure of the message being sent out to the Modbus network. The byte values below are in hexadecimal display.
Node
Address
Func
Code
0B 10
Data Start
Address
High
00
Data Start
Address
Low
Number of Points
High
Number of Points
Low
Byte
Count
01 00 02 04
Data
High
00
Data
Low
0A
Data
High
Data
Low
01 02
Error
Check
Field (2
bytes)
CRC
0B
Response
The normal response to a function 16 query is to echo the address, function code, starting address and number of registers to be loaded.
Node
Address
Func
Code
Data Start
Address
High
Data Start
Address
Low
Number of Points
High
Number of Points
Low
Error Check
Field (2 bytes)
10 00 01 00 02 CRC
Page 116 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.3 Floating-Point Support
Reference
User Manual
You can easily move floating point data between the MBS module and other devices as long as the device supports IEEE 754 Floating Point format. This
IEEE format is a 32-bit single-precision floating-point format.
The logic necessary to move the floating-point data takes advantage of the COP instruction in RSLogix 5000. The COP instruction is unique for data movement commands in that it is an untyped function, meaning that no data conversion is done when data is moved between controller tags with different data types (that is, it is an image copy, not a value copy).
The COP instruction to move data from a floating-point controller tag into an integer controller tag (something you would do to move floating-point values to the module) is shown below.
This instruction moves one floating-point value in two 16-bit integer images to
MBS.DATA.WriteData[0], which is an integer tag. For multiple floating-point values increase the Length field by a factor of 2 per floating-point value.
The COP instruction to move data from MBS.DATA.ReadData[0], which is an integer tag, to a floating-point tag (something you would do to receive floatingpoint values from the module) is shown below.
This instruction moves two 16-bit integer registers containing one floating point value image into the floating-point tag. For multiple values increase the Length field.
ProSoft Technology, Inc.
June 28, 2017
Page 117 of 154
Reference
User Manual
7.3.1 ENRON Floating Point Support
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Many manufacturers have implemented special support in their drivers for what is commonly called the Enron version of the Modbus protocol. In this implementation, addresses greater than 7000 are presumed to contain floatingpoint values. The significance to this is that the count descriptor for a data transfer now denotes the number of floating-point values to transfer, instead of the number of words.
7.3.2 Configuring the Floating Point Data Transfer
A common question is how to handle floating-point data when using the module as a Modbus master. This really depends on the slave device and how it addresses this application.
Just because your application is reading or writing floating-point data, does not mean that you must configure the Float Flag, Float Start, and Float Offset parameters within the module.
These parameters are only used to support what is typically referred to as Enron or Daniel Modbus, where one register address must have 32 bits, or one floating point value. Below is an example:
Example #1
Modbus Address
47101
47102
47103
47104
Data Type
32 bit REAL
32 bit REAL
32 bit REAL
32 bit REAL
Parameter
TEMP Pump #1
Pressure Pump #1
TEMP Pump #2
Pressure Pump #2
With the module configured as a master, you only need to enable these parameters to support a write to this type of addressing (Modbus FC 6 or 16).
If the slave device uses addressing as shown in Example #2, then you do not need to do anything with the Float Flag or Float Start parameters, as this addressing scheme uses two Modbus addresses to represent each floating-point value:
Example #2
Modbus Address
47101
47103
47105
47107
Data Type
32 bit REAL
32 bit REAL
32 bit REAL
32 bit REAL
Parameter
TEMP Pump #1
Pressure Pump #1
TEMP Pump #2
Pressure Pump #2
Because each 32 bit REAL value is represented by two Modbus addresses
(example 47101 and 47102 represent TEMP Pump #1), then you do not need to set the Float Flag, or Float Start for the module for Modbus FC 6 or 16 commands being written to the slave.
The next few pages show three specific examples:
Page 118 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Example #1: master is issuing Modbus command with FC 16 (with Float Flag: Yes) to transfer Float data to slave.
Reference
User Manual
(Float specific module parameters)
Float Flag: "Y" tells the master to consider the data values that need to be sent to the slave as floating point data where each data value is composed of 2 words
(4 bytes or 32 bits).
Float Start - Tells the master that if this address number is <= the address number in Addr in Dev parameter to double the byte count quantity to be included in the Command FC6 or FC16 to be issued to the slave. Otherwise the master ignores the Float Flag: Y and treat data as composed of 1 word, 2 bytes.
(Modbus Command parameters)
DB Addr - Tells the master where in its data memory is the beginning of data to obtain and write out to the slave device.
Reg Count - Tells the master how many data points to send to the slave. Two counts mean two floating points with Float Flag: Y and the Addr in Dev greater than or equal to the Float Start Parameter.
Swap Code - Tells the master how to orient the Byte and Word structure of the data value. This is device dependent. Check Command Entry formats Section.
Func Code - Tells the master to write the float values to the slave. FC16.
Addr in Dev - Tells the master where in the slave's database to locate the data.
ProSoft Technology, Inc.
June 28, 2017
Page 119 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
In the above example, the master's Modbus command to transmit inside the
Modbus packet is as follows.
Reg Count Byte Count Data
DEC
HEX
Slave
Address
01
01
Function
Code
16
10
Address in
Device
7100
1B BC
2
00 02
8
08
85.37 22.86
BD 71 42 AA E1 48 41 B6
In this example, the master's Modbus packet contains the data byte and data word counts that have been doubled from the amount specified by Reg Count due to the Float flag set to Y. Some slaves look for the byte count in the data packet to know the length of the data to read from the wire. Other slaves know at which byte the data begins and read from the wire the remaining bytes in the packet as the data the master is sending.
Page 120 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Reference
User Manual
Example #2: master is issuing Modbus command with FC 16 (with Float Flag: No) to transfer
Float data.
Float Flag: "N" tells the master to ignore the floating values and treat each register data as a data point composed of 1 word, 2 bytes or 16 bits.
Float Start: Ignored.
DB Addr - same as when Float Flag: Y.
Reg Count - Tells the master how many data points to send to the slave.
Swap Code - same as when Float Flag: Y.
Func Code - same as when Float Flag: Y.
Addr in Dev - same as when Float Flag: Y as long as the slave's Float Flag = Y.
In the above example, the master's Modbus command to transmit inside the
Modbus packet is as follows.
Slave
Address
DEC 01
HEX 01
Function
Code
16
10
Address in
Device
7100
1B BC
Reg
Count
2
00 02
Byte
Count
4
04
Data
85.37
BD 71 42 AA
ProSoft Technology, Inc.
June 28, 2017
Page 121 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
In this example, the master's Modbus packet contains the data byte and data word counts that have NOT been doubled from the amount specified by Reg
Count due to the Float Flag set to N. The slave looks for the byte count in the data packet to know the length of the data to read from the wire. Because of insufficient byte count, some slaves read only half the data from the master's transmission. Other slaves read all 8 bytes in this example because they know where in the packet the data starts and ignore the byte count parameter inside the Modbus packet.
Example #3: master is issuing Modbus command with FC 3 to transfer Float data from slave.
Float Flag: Not applicable with Modbus Function Code 3.
Float Start: Not applicable with Modbus Function Code 3.
DB Addr - Tells the master where in its data memory to store the data obtained from the slave.
Reg Count - Tells the master how many registers to request from the slave.
Swap Code - same as above.
Func Code - Tells the master to read the register values from the slave. FC3.
Addr in Dev - Tells the master where in the slave's database to obtain the data.
Page 122 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
In the above example, the master's Modbus command to transmit inside the
Modbus packet is as follows.
Slave Address Function Code Address in Device Reg Count
DEC
HEX
01
01
3
03
6100
17 D4
2
00 02
Reference
User Manual
In the above example the (Enron/Daniel supporting) slave's Modbus command to transmit inside the Modbus packet is as follows.
Slave Address Function Code Byte Count Data
DEC
HEX
01
01
3
03
8
08
32.75 275.69
00 00 42 03 D8 52 43 89
In the above example the (a NON-Enron/Daniel supporting) slave's Modbus command that is transmitted inside the Modbus packet is as follows.
Slave Address Function Code Byte Count Data
DEC
HEX
01
01
3
03
4
04
32.75
00 00 42 03
ProSoft Technology, Inc.
June 28, 2017
Page 123 of 154
Reference
User Manual
7.4 Function Blocks
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Data contained in this database is paged through the input and output images by coordination of the CompactLogix or MicroLogix 1500-LRP ladder logic and the
MVI69E-MBS module's program. Each block transferred from the module to the processor or from the processor to the module contains a block identification code that describes the content of the block.
9961
9970
9972
9973
9997
9998
9999
Block ID Range
-1000 to -1166
-1 to -999
0
1 to 167
1000 to 1255
2000 to 2255
3000 to 3001
3002 to 3006
3100 to 3101
3102 to 3106
9250
9500
9501
9956
9957
9958
9959
5001 to 5006
5101 to 5106
8000
8001
8100
9000 or -9000
9001 or -9001
Description
Get input image data for initialization
Dummy block
Read or write data for small data sets
Read or write data
Event Command Port 1
Event Command Port 2
Port 1 slave polling control
Port 1 slave status
Port 2 slave polling control
Port 2 slave status
Port 1 Command Control
Port 2 Command Control
Add Event with data for Port 1
Add Event with data for Port 2
Get Event with data status
Specifications of configuration file data from the processor to the module
Get configuration file from the processor to the module (continued)
Get general module status data
Set port and command active bits
Get port and command active bits
Pass-through formatted block for functions 6 and 16 with word data
Pass-through formatted block for functions 6 and 16 with float data
Pass-through formatted block for function 5
Pass-through formatted block for function 15
Pass-through formatted block for function 23
Pass-through block for function 99
Set module time using received time
Pass module time to processor
Reset status block
Warm-boot control block
Cold-boot control block
Page 124 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.1 Event Command Blocks (1000 to 1255, 2000 to 2255)
Reference
User Manual
Blocks 1000 to 1255: Event Port 1
Blocks 2000 to 2255: Event Port 2
Event Command blocks send Modbus commands directly from the ladder logic to one of the Master ports. The Event Command is added to the high-priority queue and interrupts normal polling so that this special command can be sent as soon as possible.
Note: Overusing Event Commands may substantially slow or totally disrupt normal polling. Use
Event Commands sparingly. Event Commands are meant to be used as one-shot commands triggered by special circumstances or uncommon events.
Blocks 1000 to 1255 or 2000 to 2255: Request from Processor to Module
Offset Description
0
1
2
Write Block ID: 1000 to 1255 for a Port 1 command or 2000 to 2255 for a Port 2 command. The last 3 digits of the command specify the slave address to use for the command.
Internal address in the module to be used with the command.
Count parameter that determines the number of digital points or registers to associate with the command.
3
4
Swap type for the data.
Modbus Function Code to be associated with the command.
5 Modbus address in the slave device to be used in the command.
6 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Blocks 1000 to 1255 or 2000 to 2255: Response from Module to Processor
Offset Description
0
1
2
Read Block ID: 1000 to 1255 or 2000 to 2255 requested by the processor.
Write Block ID: To be used by the processor in its next Write block
Result of the event request. 1 = the command was placed in the command queue; 0 = no room was found in the command queue.
3 Number of commands in the command queue for the specified port.
4 to (n-1) Spare
ProSoft Technology, Inc.
June 28, 2017
Page 125 of 154
Reference
User Manual
7.4.2 Slave Polling Disable Blocks
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Block 3000: Port 1 Slave Polling Disable
Block 3100: Port 2 Slave Polling Disable
These blocks allow the processor to disable polling for specific slaves.
Block 3000 or 3100: Request from Processor to Module
Offset
0
1
2-61
Description
Write Block ID: 3000 for Port 1 and 3100 for Port 2 slave polling disable request.
Number of slaves listed in the block (1 to 60).
Slave indexes to disable in the command list for the selected port. The number of slaves to process is set in Word 1 of the block.
Block 3000 or 3100: Response from Module to Processor
Offset Description
0
1
Read Block ID: 3000 or 3100 requested by the processor.
Write Block ID: To be used by the processor in its next Write block.
2 Number of slaves processed in the last request. This number should match the value passed in Word 1of the request block.
3 to (n-1) Spare
7.4.3 Slave Polling Enable Blocks (3001, 3101)
Block 3001: Port 1 Slave Polling Enable
Block 3101: Port 2 Slave Polling Enable
These blocks allow the processor to enable polling for specific slaves.
Block 3001 or 3101: Request from Processor to Module
Offset
0
1
2 to 61
Description
Write Block ID: 3001 for Port 1 or 3101 for Port 2 slave polling enable request.
Number of slaves listed in the block (1 to 60).
Slave indexes to enable in the command list for the selected port. The number of slaves to process is set in Word 1 of the block.
Block 3001 or 3101: Response from Module to Processor
Offset
0
1
Description
Read Block ID: 3000 to 3101 or 3100 to 3101 requested by the processor.
Write Block ID: To be used by the processor in its next Write block.
2 Number of slaves processed in the last request. This number should match the value passed in Word 1of the request block.
3 to (n-1) Spare
Page 126 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.4 Slave Polling Status Blocks (3002 to 3006, 3102 to 3106)
Reference
User Manual
Blocks 3002 to 3006: Port 1 Slave Status
Blocks 3102 to 3106: Port 2 Slave Status
Two arrays are allocated in the module’s primary object to hold the polling status of each slave on the Master ports. You can use this status data to determine which slaves are currently active on the port, in communication error, or have their polling suspended and disabled.
Block 3002 to 3006 or 3102 to 3106: Request from Processor to Module
Offset Description
0 Write Block ID: 3002 to 3006 for Port 1 and 3102 to 3106 for Port 2 slave polling status request.
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 3002 to 3006 or 3102 to 3106: Response from Module to Processor
Offset
0
Description
Read Block ID: 3002 to 3006 or 3102 to 3106 requested by the processor.
1
2
3
4 to 61
Write Block ID: To be used by the processor in its next Write block.
Slave ID offset: Index of first slave in block
Number of slaves in this block
Slave polling status data
62 to (n-1) Spare
Slave Status values
Value
0
1
2
Description
OK
Exceeded retry count and in error delay count mode
Block 3000 or 3100
ProSoft Technology, Inc.
June 28, 2017
Page 127 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.5 Command Control Blocks (5001 to 5006, 5101 to 5106)
Blocks 5001 to 5006: Port 1 Command Control
Blocks 5101 to 5106: Port 2 Command Control
If the CompactLogix or MicroLogix 1500-LRP processor sends a command control block, the module places the commands referenced in the block in the command queue. Commands placed in the queue with this method need not have their enable bit set. Only valid commands are placed in the queue.
Up to 6 commands can be enabled and placed in the command queue with one write request from the CompactLogix or MicroLogix 1500-LRP processor.
Blocks 5001 to 5006 or 5101 to 5106: Request from Processor to Module
Offset
0
1
2
3
4
5
6
Description
Write Block ID: 5001 to 5006 for Port 1 or 5101 to 5106 for Port 2. The last digit indicates how many commands are to be placed in the command queue by this block.
Index in the command list for the first command to be entered into the command queue (applies to blocks 5001 to 5006 and 5101 to 5106).
Index for the second command (applies to blocks 5002 to 5006 and 5102 to 5106).
Index for the third command (applies to blocks 5003 to 5006 and 5103 to 5106).
Index for the fourth command (applies to blocks 5004 to 5006 and 5104 to 5106).
Index for the fifth command (applies to blocks 5005 to 5006 and 5105 to 5106).
Index for the sixth command (applies to blocks 5006 and 5106).
7 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Blocks 5001 to 5006 or 5101 to 5106: Response from Module to Processor
Offset Description
0
1
2
3
Read Block ID: 5001 to 5006 or 5101 to 5106 requested by the processor.
Write Block ID: To be used by the processor in its next Write block.
Number of commands in the block placed in the command queue.
Number of commands in the command queue for the specified port.
4 to (n-1) Spare
Page 128 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.6 Add Event with Data Blocks (8000, 8001)
Reference
User Manual
Block 8000: Add Event with Data for Port 1
Block 8001: Add Event with Data for Port 2
The 8000-series blocks are similar to the 1000 and 2000-series blocks. The
8000-series blocks source the command data from the processor, instead of from the module’s database.
Block 8000 or 8001: Request from Processor to Module
Offset Description
0
1
2
3
4
Write Block ID: 8000 for Port 1 or 8001 for Port 2 event command with data request
Slave address of Modbus device to reach with the command request
Modbus function code to use with command (5, 6, 15 or 16)
Modbus address in slave device
Count value for operation- bit count for function 15 (1 to 800 points) and word count for function 16 (1 to 50 words or 1 to 25 float values). For functions 5 and 6, the count is assumed to be 1.
5 to 54 Data to be used by command
55 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 8000 or 8001: Response from Module to Processor
Offset Description
0
1
Read Block ID: 8000 for Port 1 or 8001 for Port 2 event command with data request
Write Block ID: To be used by the processor in its next Write block.
2 Error Code for request:
0=no error
-1=port is not enabled
-2=port is not a master port
-3=port is not active (enabled)
-4=port busy with previous event command
-5=invalid Modbus command
-6=invalid point count for command
3 to (n-1) Spare
ProSoft Technology, Inc.
June 28, 2017
Page 129 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.7 Get Event with Data Status Block (8100)
Block 8100: Get Event with Data Status
This block requests status data for Event with Data Commands.
Block 8100: Request from Processor to Module
Offset Description
0 Write Block ID: 8100 status data request for Event with Data Commands.
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 8100: Response from Module to Processor
Page 130 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.8 Get Configuration File Information Block (9000 or -9000)
Reference
User Manual
Block 9000 or -9000: Get Configuration File Information
This block requests information from the processor about the configuration file, in preparation for transferring the configuration file from the processor to the module. It specifies the location in the configuration file to start copying and sending the information.
1
Block 9000 or -9000: Request from Module to Processor
Offset
0
Description
Read Block ID: 9000 or -9000 request for configuration file information from processor
Write Block ID: 9000 or -9000 to be used by the processor in its next Write block.
Offset
0
1
2
3
4
5-6
7-8
Block 9000 or -9000: Response from Processor to Module
Description
Write Block ID: 9000 or -9000 configuration file information
Module's slot number.
Size of the module's Input image to the processor.
Size of the module's Output image from the processor.
Status of configuration file.
These two registers contain the size of the configuration file in bytes.
These two registers contain the CRC for the configuration file.
ProSoft Technology, Inc.
June 28, 2017
Page 131 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.9 Get Configuration File Block (9001 or -9001)
Block 9001 or -9001: Get Configuration File Information
This block requests the configuration file from the processor. The module returns the requested contents of the configuration file.
Block 9001 or -9001: Request from Module to Processor
Offset
0
1
2-3
4-5
6-7
Description
Read Block ID: 9001 or -9001 request for configuration file from processor
Write Block ID: 9001 or -9001 to be used by the processor in its next Write block.
File offset: Offset of the first register in the configuration file to begin transferring data from. If the size of the configuration file exceeds the block transfer size, the file is transferred in multiple blocks, and the file offset tells the processor which part of the configuration file is being requested by the individual block.
Number of bytes of the configuration file to include in next block
Copy of the data contained in registers 2 to 3.
Block 9001 or -9001: Response from Processor to Module
Offset Description
0
1-2
Write Block ID: 9001 or -9001 configuration file data
File offset: Same as registers 2-3 of the previous request block
3-4 Data length: Same as registers 4-5 of the previous request block
5 to (n-1) Contents of configuration file. If the size of the configuration file exceeds the block transfer size, this information is transferred in multiple blocks.
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Page 132 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.10 Get General Module Status Data Block (9250)
Block 9250: Get General Module Status Data
This block requests the general module status.
Reference
User Manual
Block 9250: Request from Processor to Module
Offset Description
0 Write Block ID: 9250 request for general module status
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
14
15
16
17
18
Block 9250: Response from Module to Processor
Offset
0
1
2
3-4
5-6
7-8
9-10
11
12
13
19
20
Description
Read Block ID: 9250 requested by processor.
Write Block ID: To be used by the processor in its next Write block.
Program Scan Count: This value is incremented each time a complete program cycle occurs in the module.
Product Code: These two registers contain the product code of "MB6E" for the
MVI69E-MBS module.
Product Version: These two registers contain the product version for the current running software.
Operating System: These two registers contain the month and year values for the program operating system.
Run Number: These two registers contain the run number value for the currently running software.
Port 1 Command List Requests: Number of requests made from this port to slave devices on the network.
Port 1 Command List Response: Number of slave response messages received on the port.
Port 1 Command List Errors: Number of command errors processed on the port.
These errors could be due to a bad response or command.
Port 1 Requests: Total number of messages sent out of the port.
Port 1 Responses: Total number of messages received on the port.
Port 1 Errors Sent: Total number of message errors sent out of the port.
Port 1 Errors Received: Total number of message errors received on the port.
Port 2 Command List Requests: Number of requests made from this port to slave devices on the network.
Port 2 Command List Response: Number of slave response messages received on the port.
Port 2 Command List Errors: Number of command errors processed on the port.
These errors could be due to a bad response or command.
ProSoft Technology, Inc.
June 28, 2017
Page 133 of 154
Reference
User Manual
Offset
21
22
23
24
25
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
26
27
28
29
30
31
32
33
34
Description
Port 2 Requests: Total number of messages sent out the port.
Port 2 Responses: Total number of messages received on the port.
Port 2 Errors Sent: Total number of message errors sent out of the port.
Port 2 Errors Received: Total number of message errors received on the port.
Read Block Count: Total number of read blocks transferred from the module to the processor.
Write Block Count: Total number of write blocks transferred from the processor to the module.
Parse Block Count: Total number of blocks successfully parsed that were received from the processor.
Event Command Block Count: Total number of Event Command blocks received from the processor.
Command Control Block Count: Total number of Command Control blocks received from the processor.
Error Block Count: Total number of block errors recognized by the module.
Port 1 Current Error: For a slave port, this field contains the value of the current error code returned. For a master port, this field contains the index of the currently executing command.
Port 1 Last Error: For a slave port, this field contains the value of the last error code returned. For a master port, this field contains the index of the command with an error.
Port 2 Current Error: For a slave port, this field contains the value of the current error code returned. For a master port, this field contains the index of the currently executing command.
Port 2 Last Error: For a slave port, this field contains the value of the last error code returned. For a master port, this field contains the index of the command with an error.
35 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Page 134 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.11 Set Port and Command Active Bits Block (9500)
Block 9500: Set Port and command active bits
This block enables and disables ports, as well as individual Master commands for a port.
Reference
User Manual
Block 9500: Request from Processor to Module
Offset Description
0
1
2 to 21
22
Write Block ID: 9500 to set port and command enable/disable state
Port 1 active state: 0=disabled, 1=enabled
Command enable bits for Port 1 commands (0=disabled, 1=enabled)
Port 2 active state: 0=disabled, 1=enabled
23 to 42 Command enable bits for Port 2 commands (0=disabled, 1=enabled)
43 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9500: Response from Module to Processor
Offset
0
Description
Read Block ID: 9500 requested by processor.
1 Write Block ID: To be used by the processor in its next Write block.
2 to (n-1) Spare
ProSoft Technology, Inc.
June 28, 2017
Page 135 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.12 Get Port and Command Active Bits Block (9501)
Block 9501: Get Port and command active bits
This block requests the enabled/disabled status of ports and Master commands.
Block 9501: Request from Processor to Module
Offset Description
0 Write Block ID: 9501 to get port and command enable/disable state
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9501: Response from Module to Processor
Offset
0
1
Description
Read Block ID: 9501 requested by processor.
Write Block ID: To be used by the processor in its next Write block.
2
3 to 22
Port 1 active state: 0=disabled, 1=enabled
Command enable bits for Port 1 commands (0=disabled, 1=enabled)
23 Port 2 active state: 0=disabled, 1=enabled
24 to 43 Command enable bits for Port 2 commands (0=disabled, 1=enabled)
44 to (n-1) Spare
Page 136 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.13 Pass-through Formatted Block for Functions 6 and 16 with
Word Data Block (9956)
Reference
User Manual
Block 9956: Pass-Through Formatted Block for Functions 6 and 16 with Word
Data Block
If one or more of the slave ports on the module are configured for formatted
Pass-Through mode, the module sends input image blocks with identification codes of 9956, 9957, 9958 or 9959 to the processor for each write command received. Any incoming Modbus Function 5, 6, 15 or 16 command is passed from the port to the processor using a block identification number that identifies the
Function Code received in the incoming command.
The MBS Add-On Instruction handles the receipt of all Modbus write functions and to respond to commands issued by the remote Modbus Master device.
Note: Mutual exclusion on Pass-Through Block IDs 9956, 9957, 9958, and 9959 from both ports -
If both ports are configured as slave ports, when both of the slave ports receive write commands with the same Function Code, which would need to use the same block identifier from the above list, the module will process the command from the port which first received the command and will return an Exception Code error code 6 (node is busy - retry command later error) from the other port that received the command last. The Master retries the command on the busy port after a short delay. This prevents Pass-Through blocks on both ports from overwriting each other.
Block 9956: Request from Module to Processor
Offset
Description
0
1
Read Block ID: 9956
Write Block ID: 9956
2 Number of word registers in Modbus data set
3 Starting address for Modbus data set
4 to (n+1)
Data (Length in words = n - 2)
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-Through control block with an output image write block with the following format.
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Block 9956: Response from Processor to Module
Offset
0
1 to n
Description
Write Block ID: 9956
Spare (Length in words = n - 2)
ProSoft Technology, Inc.
June 28, 2017
Page 137 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.14 Pass-through Formatted Block for Functions 6 and 16 with
Float Data Block (9957)
Block 9957: Pass-Through Formatted Block for Functions 6 and 16 with Float
Data Block
Block 9957: Request from Module to Processor
Offset Description
0
1
Read Block ID: 9957
Write Block ID: 9957
2
3
Number of word registers in Modbus data set
Starting address for Modbus data set
4 to (n+1) Data (Length in words = n - 2)
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-Through block with a write block with the following format.
Block 9957: Response from Processor to Module
Offset
0
1 to n
Description
Write Block ID: 9957
Spare (Length in words = n - 2)
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Page 138 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.15 Pass-through Formatted Block for Function 5 (9958)
Block 9958: Pass-Through Formatted Block for Function 5
Block 9958: Request from Module to Processor
Offset Description
0
1
2
3
Read Block ID: 9958
Write Block ID: 9958
Number of word registers in Modbus data set
Starting address for Modbus data set
4 to (n+1) Data (Length in words = n - 2)
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-Through control block with an output image write block with the following format.
Block 9958: Response from Processor to Module
Offset
0
1 to n
Description
Write Block ID: 9958
Spare (Length in words = n - 2)
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Reference
User Manual
ProSoft Technology, Inc.
June 28, 2017
Page 139 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.16 Pass-through Formatted Block for Function 15 (9959)
Block 9959: Pass-Through Formatted Block for Function 15
When the module receives a function code 15 in Pass-Through mode, the module writes the data using block ID 9959 for multiple-bit data. First the bit mask clears the bits to be updated. This is accomplished in RSLogix 5000 by
ANDing the inverted mask with the existing data.
Next, the new data ANDed with the mask is ORed with the existing data. This protects the other bits in the INT registers from being affected. This function can only be used if the Block Transfer Size parameter is set to 120 or 240 words.
Block 9959: Request from Module to Processor
Offset Description
0
1
2
3
Read Block ID: 9959
Write Block ID: 9959
Length in words
Data address
4 to 28
29 to 53
Modbus Data
Bit mask to use with the data set. Each bit to be considered with the data set has a value of 1 in the mask. Bits to ignore in the data set has a value of 0 in the mask.
54 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-Through control block with a write block with the following format.
Block 9959: Response from Processor to Module
Offset
0
1 to (n-1)
Description
Write Block ID: 9959
Spare
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Page 140 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.17 Pass-through Formatted Block for Function 23 (9961)
Block 9961: Pass-Through Formatted Block for Function 23
Block 9961: Request from Module to Processor
Offset Description
0
1
2
3
Read Block ID: 9961
Write Block ID: 9961
Number of word registers in Modbus data set
Starting address for Modbus data set
4 to (n+1) Data (Length in words = n - 2)
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the pass-through control block with an output image write block with the following format.
Block 9961: Response from Processor to Module
Offset
0
1 to n
Description
Write Block ID: 9961
Spare (Length in words = n - 2)
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Reference
User Manual
ProSoft Technology, Inc.
June 28, 2017
Page 141 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.18 Pass-through Block for Function 99 (9970)
Block 9970: Pass-Through Block for Function 99
Block 9970: Request from Module to Processor
Offset Description
0
1
2
3
Read Block ID: 9970
Write Block ID: 9970
1
0
4 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
The ladder logic is responsible for parsing and copying the received message and performing the proper control operation as expected by the Master device.
The processor must then respond to the Pass-Through control block with an output image write block with the following format.
Block 9970: Response from Processor to Module
Offset
0
1 to n
Description
Write Block ID: 9970
Spare (Length in words = n - 2)
This informs the module that the command has been processed and can be cleared from the Pass-Through queue.
Page 142 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.4.19 Pass Module Time to Processor Block (9973)
Block 9973: Pass Module Time to Processor Block
This block uses the time information from the module to set the processor time.
Reference
User Manual
Block 9973: Request from Processor to Module
Offset Description
0 Write Block ID: 9973
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9973: Response from Module to Processor
Offset Description
4
5
6
7
0
1
2
3
Read Block ID: 9973
Write Block ID: To be used by the processor in its next Write block.
Year (0-9999)
Month (1-12)
Day (1-31)
Hour (0-23)
Minutes (0-59)
Seconds (0-59)
8 Milliseconds
9 to (n-1) Spare
ProSoft Technology, Inc.
June 28, 2017
Page 143 of 154
Reference
User Manual
7.4.20 Reset Status Block (9997)
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Block 9997: Reset Status Block
This block resets the module, port 1, and/or port 2 status.
Block 9997: Request from Processor to Module
Offset Description
0
1
Write Block ID: 9997
Reset Module status (0=no, else yes)
2 Reset Port 1 status (0=no, else yes)
3 Reset Port 2 status (0=no, else yes)
4 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 9997: Response from Module to Processor
Offset Description
0
1
Read Block ID: 9997
Write Block ID: To be used by the processor in its next Write block.
2 to (n-1) Spare
7.4.21 Cold-boot Control Block (9999)
Block 9999: Cold-boot Control Block
If the CompactLogix or MicroLogix 1500-LRP processor sends a block number
9999, the firmware performs a cold-boot operation. The firmware reloads the configuration file from the processor to the module and resets all MBS memory, error and status data.
Block 9999: Request from Processor to Module
Offset Description
0 Write Block ID: 9999
1 to (n-1) Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Page 144 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.5 Ethernet Port Connection
Reference
User Manual
7.5.1 Ethernet Cable Specifications
The recommended cable is Category 5 or better. A Category 5 cable has four twisted pairs of wires, which are color-coded and cannot be swapped. The module uses only two of the four pairs.
The Ethernet port or ports on the module are Auto-Sensing. You can use either a standard Ethernet straight-through cable or a crossover cable when connecting the module to an Ethernet hub, a 10/100 Base-T Ethernet switch, or directly to a
PC. The module detects the cable type and uses the appropriate pins to send and receive Ethernet signals.
Some hubs have one input that can accept either a straight-through or crossover cable, depending on a switch position. In this case, you must ensure that the switch position and cable type agree.
Refer to Ethernet Cable Configuration (page 145) for a diagram of how to
configure Ethernet cable.
Ethernet Cable Configuration
Note: The standard connector view shown is color-coded for a straight-through cable.
Crossover cable
RJ-45 PIN
1 Rx+
2 Rx-
3 Tx+
6 Tx-
RJ-45 PIN
3 Tx+
6 Tx-
1 Rx+
2 Rx-
Straight- through cable
RJ-45 PIN
1 Rx+
2 Rx-
3 Tx+
6 Tx-
RJ-45 PIN
1 Tx+
2 Tx-
3 Rx+
6 Rx-
ProSoft Technology, Inc.
June 28, 2017
Page 145 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Ethernet Performance
Ethernet performance in the MVI69E-MBS module can be affected in the following way:
Accessing the web interface (refreshing the page, downloading files, and so on) may affect performance
Also, high Ethernet traffic may impact MBS performance, so consider one of these options: o o
Use managed switches to reduce traffic coming to module port
Use CIPconnect for these applications and disconnect the module
Ethernet port from the network
7.6 Modbus Application Port Connection
The module supports RS-232, RS-422, and RS-485 wiring to remote devices.
7.6.1 RS-232 Wiring
When the RS-232 interface is selected, the use of hardware handshaking
(control and monitoring of modem signal lines) is user definable. If no hardware handshaking is used, here are the cable pin-outs to connect to the port.
Page 146 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
RS-232: Modem Connection (Hardware Handshaking Required)
This type of connection is required between the module and a modem or other communication device.
Reference
User Manual
The "Use CTS Line" parameter for the port configuration should be set to 'Y' for most modem applications.
RS-232: Null Modem Connection (Hardware Handshaking)
This type of connection is used when the device connected to the module requires hardware handshaking (control and monitoring of modem signal lines).
ProSoft Technology, Inc.
June 28, 2017
Page 147 of 154
Reference
User Manual
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field device communication port.
Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line parameter should be set to N and no jumper is required between Pins 7 (RTS) and 8
(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is required between the RTS and the CTS lines on the port connection.
Page 148 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
7.6.2 RS-422 Wiring
The RS-422 interface requires a single four or five wire cable. The Common connection is optional, depending on the RS-422 network devices used. The cable required for this interface is shown below:
Reference
User Manual
7.6.3 RS-485 Wiring
The RS-485 interface requires a single two or three wire cable. The Common connection is optional, depending on the RS-485 network devices used. The cable required for this interface is shown below:
Note: Terminating resistors are generally not required on the RS-485 network, unless you are experiencing communication problems that can be attributed to signal echoes or reflections. In these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module connector end of the RS-485 line may improve communication quality.
RS-485 and RS-422 Tip
If communication in the RS-422 or RS-485 mode does not work at first, despite all attempts, try switching termination polarities. Some manufacturers interpret + and -, or A and B, polarities differently.
ProSoft Technology, Inc.
June 28, 2017
Page 149 of 154
Reference
User Manual
7.6.4 DB9 to RJ45 Adaptor (Cable 14)
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Page 150 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Support, Service & Warranty
User Manual
8 Support, Service & Warranty
In This Chapter
Contacting Technical Support ............................................................. 151
8.1 Contacting Technical Support
ProSoft Technology, Inc. is committed to providing the most efficient and effective support possible. Before calling, please gather the following information to assist in expediting this process:
1 Product Version Number
2 System architecture
3 Network details
If the issue is hardware related, we will also need information regarding:
1 Module configuration and associated ladder files, if any
2 Module operation and any unusual behavior
3 Configuration/Debug status information
4 LED patterns
5 Details about the serial, Ethernet or Fieldbus devices interfaced to the module, if any.
Note: For technical support calls within the United States, ProSoft’s 24/7 after-hours phone support
is available for urgent plant-down issues. Detailed contact information for all our worldwide
locations is available on the following page.
ProSoft Technology, Inc.
June 28, 2017
Page 151 of 154
Support, Service & Warranty
User Manual
Internet
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Asia Pacific
(location in Malaysia)
Asia Pacific
(location in China)
Web Site: www.prosoft-technology.com/support
E-mail address: [email protected]
Tel: +603.7724.2080
E-mail: [email protected]
Languages spoken include: Chinese, English
Tel: +86.21.5187.7337 x888
E-mail: [email protected]
Languages spoken include: Chinese, English
Europe
(location in Toulouse,
France)
Europe
(location in Dubai, UAE)
North America
(location in California)
Tel: +33 (0) 5.34.36.87.20
E-mail: [email protected]
Languages spoken include: French, English
Tel: +971-4-214-6911
E-mail: [email protected]
Languages spoken include: English, Hindi
Tel: +1.661.716.5100
E-mail: [email protected]
Languages spoken include: English, Spanish
Latin America
(Oficina Regional)
Latin America
(location in Puebla, Mexico)
Tel: +52-222-3-99-6565
E-mail: [email protected]
Languages spoken include: Spanish
Brasil
(location in Sao Paulo)
Tel: +1-281-2989109
E-Mail: [email protected]
Languages spoken include: Spanish, English
Tel: +55-11-5083-3776
E-mail: [email protected]
Languages spoken include: Portuguese, English
8.2 Warranty Information
For complete details regarding ProSoft Technology’s TERMS & CONDITIONS
OF SALE, WARRANTY, SUPPORT, SERVICE AND RETURN MATERIAL
AUTHORIZATION INSTRUCTIONS please see the documents at: www.prosoft-technology/legal
Documentation is subject to change without notice.
Page 152 of 154 ProSoft Technology, Inc.
June 28, 2017
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
Index
0
00 Return Query Data • 113
A
About the Modbus Protocol • 105
Add Event with Data Blocks (8000, 8001) • 129
Adding another module in PCB • 35, 38
Adding Another Module in RSLogix 5000 • 37
Adding Multiple Modules in the Rack (Optional) • 35
Adding the Module to RSLogix • 17, 43, 44, 75
Additional Configuration Parameters as Master • 50,
73
Additional Configuration Parameters as Slave • 51
B
Backplane Data Transfer • 64
Basic PCB Functions • 44
C
Clearing a Fault Condition • 89
Cold-boot Control Block (9999) • 144
Command Control Blocks (5001 to 5006, 5101 to
5106) • 128
Command Error Codes • 73
Command List Entry Errors • 100
Communication Error Codes • 73, 82, 100
Configuration Parameters Common to Master and
Slave • 48, 50, 51
Configuring the Floating Point Data Transfer • 118
Configuring the MVI69E-MBS Using PCB • 43, 90, 93
Connecting the PC to the Module's Ethernet Port • 90
Connecting to the Module’s Web Page • 101
Contacting Technical Support • 151
Content Disclaimer • 2
Controller Tags • 75
Creating a Module in the Project Using a Generic 1769
Module Profile • 17, 22
Creating a Module in the Project Using an Add-On
Profile • 17, 18
Creating a New PCB Project and Exporting an .L5X
File • 44
Creating a New RSLogix 5000 Project • 30
Creating and Exporting the .L5X File • 28, 32, 36, 43
Creating the Module in an RSLogix 5000 Project • 17
D
Data Flow Between the Module and Processor • 70
DB9 to RJ45 Adaptor (Cable 14) • 150
Deployment Checklist • 11
ProSoft Technology, Inc.
June 28, 2017
Index
User Manual
Diagnostics (Function Code 08) • 113
Diagnostics and Troubleshooting • 73, 87
Diagnostics Menu • 95
Downloading the Configuration File to the Processor •
56
E
Editing Configuration Parameters • 44
ENRON Floating Point Support • 118
Ethernet 1 • 55, 92
Ethernet Cable Configuration • 145
Ethernet Cable Specifications • 145
Ethernet LED Indicators • 88
Ethernet Performance • 146
Ethernet Port Connection • 145
Event Command Blocks (1000 to 1255, 2000 to 2255)
• 125
Example and State Diagram • 113
F
Floating-Point Support • 117
Force Multiple Coils (Function Code 15) • 115
Force Single Coil (Function Code 05) • 111
Function Blocks • 124
Function Codes Supported by the Module • 106
G
General Concepts of the MVI69E-MBS Data Transfer •
63
General Specifications - Modbus Master/Slave • 104
Generating the AOI (.L5X File) in ProSoft
Configuration Builder • 25
Get Configuration File Block (9001 or -9001) • 132
Get Configuration File Information Block (9000 or -
9000) • 131
Get Event with Data Status Block (8100) • 130
Get General Module Status Data Block (9250) • 133
Get Port and Command Active Bits Block (9501) • 136
H
Hardware Specifications • 104
I
If Block Transfer Size = 120 • 68
If Block Transfer Size = 240 • 69
If Block Transfer Size = 60 • 67
Important Safety Information • 3
Importing the Add-On Instruction • 31
Installing an Add-On Profile • 18
Installing ProSoft Configuration Builder • 24
Installing the Module in the Rack • 13
LED Status Indicators • 88
L
Page 153 of 154
Index
User Manual
M
Master Command List • 73
Master Mode • 72
MBS Controller Tag Overview • 79
MBS.CONFIG • 80
MBS.CONTROL • 80
MBS.CONTROL.CmdControl • 81
MBS.CONTROL.ColdBoot • 84
MBS.CONTROL.EventCmd_DBData • 81
MBS.CONTROL.EventCmd_ProcessorData • 82
MBS.CONTROL.GetStatus • 84
MBS.CONTROL.PortControl • 80
MBS.CONTROL.ResetStatus • 84
MBS.CONTROL.SlavePoll • 83
MBS.CONTROL.Time • 83
MBS.CONTROL.WarmBoot • 84
MBS.DATA • 80
MBS.STATUS • 47, 85
MBS.UTIL • 86
Modbus Application Port Connection • 146
Modbus Master • 105
Modbus Port x Commands • 52, 72, 73
Modbus Port x Parameters • 48
Modbus Slave • 105
Module Communication Error Codes • 100
Module Configuration Parameters • 21, 36, 47
Module Parameters • 47
Monitoring Backplane Information • 97
Monitoring Data Values in the Module’s Database • 99
Monitoring Network Configuration Information • 96
MVI69E-MBS Backplane Data Exchange • 63
MVI69E-MBS Controller Tags • 76
MVI69E-MBS User-Defined Data Types • 77
N
Normal Data Transfer • 28, 65
P
Package Contents • 11
Pass Module Time to Processor Block (9973) • 143
Pass-through Block for Function 99 (9970) • 142
Pass-through Formatted Block for Function 15 (9959) •
140
Pass-through Formatted Block for Function 23 (9961) •
141
Pass-through Formatted Block for Function 5 (9958) •
139
Pass-through Formatted Block for Functions 6 and 16 with Float Data Block (9957) • 138
Pass-through Formatted Block for Functions 6 and 16 with Word Data Block (9956) • 137
Pinouts • 145
Port x Module Information • 98
Preset Multiple Registers (Function Code 16) • 116
Preset Single Register (Function Code 06) • 112
Printing a Configuration File • 46
Product Specifications • 103
Page 154 of 154
MVI69E-MBS ♦ CompactLogix Platform
Modbus Serial Enhanced Communication Module
R
Read and Write Block Transfer Sequences • 66
Read Block
Response from the Module to the Processor • 65
Read Coil Status (Function Code 01) • 106
Read Holding Registers (Function Code 03) • 109
Read Input Registers (Function Code 04) • 110
Read Input Status (Function Code 02) • 107
Reference • 103
Renaming PCB Objects • 44
Reset Status Block (9997) • 144
RS-232
Modem Connection (Hardware Handshaking
Required) • 147
Null Modem Connection (Hardware Handshaking)
• 147
Null Modem Connection (No Hardware
Handshaking) • 148
RS-232 Wiring • 146
RS-422 Wiring • 149
RS-485 and RS-422 Tip • 149
RS-485 Wiring • 149
S
Set Port and Command Active Bits Block (9500) • 135
Setting Jumpers • 12
Setting Up a Temporary IP Address • 90
Setting Up the Project in PCB • 25
Slave Mode • 48, 70
Slave Polling Disable Blocks • 126
Slave Polling Enable Blocks (3001, 3101) • 126
Slave Polling Status Blocks (3002 to 3006, 3102 to
3106) • 127
Standard MODBUS Protocol Exception Code Errors •
100
Start Here • 9
Sub-function Codes Supported • 113
Support, Service & Warranty • 151
System Requirements • 10, 37
T
Troubleshooting • 89
U
Uploading the Configuration File from the Processor •
59
User-Defined Data Types (UDTs) • 77
Using an Add-On Profile • 19
Using Controller Tags • 75
Using the Diagnostics Menu in PCB • 93
W
Warranty Information • 152
Write Block
Request from the Processor to the Module • 65
ProSoft Technology, Inc.
June 28, 2017