advertisement
LINE VOLTAGE
THERMOSTATS
1A11-2
HIGH
FAN
MED LOW
VALVE
(SOL)
L1*
(HOT) GND
CUSTOMER
CONNECTIONS
THERMOSTAT
SCHEMATIC
HIGH
FAN
SWITCH
MED
LOW
HEAT
RED
SYSTEM
SWITCH
HEAT
OFF
COOL
COOL
BLUE
*L1 is Power In
Note: Above FAN and SYSTEM switches shown in
MED and HEAT positions respectively.
1A11-2
5-wire with ground, for single valve, manual heat/cool changeover
1A11-2 LIGHT DUTY FAN COIL THERMOSTAT
For Direct Control of Line Voltage Valves and/or Blower Motors on
Fan Coil Units Featuring Manual Changeover From Heat to Cool and a 3-Speed Fan Switch, Subbase Included
FEATURES
• Mounts to a standard vertical outlet box or on a two-gang outlet box. May also be
mounted on a 4” x 4” junction box with an adapter (not provided).
• Wiring color coded for ease of installation.
• 3-speed manual fan switch: High – Medium – Low.
• System Switch: Heat – OFF – Cool. “OFF” breaks both valve and fan circuits.
• Beige color.
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . 4 1 /
2
” H x 4 1 /
2
” W x 2 1 /
4
” D
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. approved
PARTS AND ACCESSORIES
• Thermostat guards – see pages 24-25
– Thermostat cycles both fan and valve
– Thermostat cycles fan only (if valve is not used tape orange lead)
– System “OFF” breaks both valve and fan circuits
– Thermostat cycles valve only with continuous fan (interchange valve and L1 leads)
Model
Number
1A11-2
Range
36 to 90°F
(2 to 32°C)
Differential
1.5°F
Switch
Action
SPDT 5.5A
2.75A
Contact Ratings
Motor Ratings (inductive) Full Load
120 VAC 240 VAC 277 VAC
2.3A
Motor Ratings (inductive) Locked Rotor
120 VAC
33.0A
240 VAC
16.5A
277 VAC
13.8A
Pilot Duty
120/240
277 VAC
120A
30 www.white-rodgers.com