ENDA ETI741 TEMPERATURE INDICATOR


Add to my manuals
3 Pages

advertisement

ENDA ETI741 TEMPERATURE INDICATOR | Manualzz

Read this document carefully before using this device. The guarantee will be expired by damaging of the device if you don't attend to the directions in the user manual. Also we don't accept any compensations for personal injury, material damage or capital disadvantages.

ENDA ETI741 TEMPERATURE INDICATOR

Thank you for choosing ENDA ETI741 temperature indicator.

ETI 741

* 72 x 72mm sized.

* 4 digits display.

* Selectable sensor type.

* Input offset feature.

* Parameter access protection on 3 levels.

* Programming just by using keypad.

* CE marked according to European Norms.

* Measurement at °C and °F units.

SET

ENDA

°F °C

TEMPERATURE INDICATOR

TECHNICAL SPECIFICATIONS

Sensor type

K (NiCr-Ni) Thermocouple EN 60584

Pt 100 Resistance Thermometer

Pt 100 Resistance Thermometer

EN 60751

EN 60751

Temperature range

°C °F

0... 600 °C

0...1200

°C

0... 400 °C

0...1600

°C

-200...600

-99.9...300.0

°C

°C

+32... +1112

+32... +2192

+32... +752

+32... +2912

°F

°F

°F

°F

°F

-328... +1112 °F

-99.9...+543.0

°F

Accuracy

0,2% (of full scale)

0,2% ( f

0,2% ( f )

0,2% ( f )

0,2% ( f )

0,2% ( f )

0,2% ( f )

1 digit

1 digit

1 digit

1 digit

1 digit

1 digit

1 digit

ENVIRONMENTAL CONDITIONS

Ambient/storage temperature

Max. relative humidity

Rated pollution degree

Height

-25... +70 °C

°C

According to EN 60529 Front panel : IP65

Rear panel : IP20

Max. 2000m

Do not use the device in locations subject to corrosive and flammable gases.

ELECTRICAL CHARACTERISTICS

Supply

Power consumption

Wiring

Line resistance

Data retention

EMC

Safety requirements

230V AC +10 -20 , 50/60Hz or 24V AC ±10 , 50/60Hz or optional 9-30V DC / 7-24V AC ±10% SMPS

Max. 7VA

2.5mm² screw-terminal connections

For thermocouple max.100ohm, for 3 wired Pt 100 max. 20ohm

EEPROM (minimum 10 years)

EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)

EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)

HOUSING

Housing type

Dimensions

Weight

Enclosure material

Suitable for flush-panel mounting according to DIN 43 700.

W72xH72xD97mm

Approx. 395g (after packing)

Self extinguishing plastics.

While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.

1/3 ETI741-E-04-R

SET

if key is pressed while holding key, the programming mode is enabled.

Entering from the programme mode to the run mode:

If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the normal mode is entered.

SET

SET

ConF.

CAL .

2/3

SeCU.

ýnP.

inP. =

Type of sensor and scale.

Pt = Pt 100

-200 to +600°C

Pt.0

= Pt 100

-99.0 to +300.0°C

FE.cn.

= J

(Iron vs. Copper-Nickel) 0 to +600°C nc.nA.

= K

(Nickel-Cr.vs. Nickel-Alum.) 0 to +1200°C

c.cn. = T

(Copper vs. Copper-Nickel) 0 to +400°C

P10.r.

= S

P13.r.

= R

(Platinum-10%Rhodium vs. Pt.) 0 to +1600°C

(Platinum-13%Rhodium vs. Pt.) 0 to +1600°C

OFFS.

oFFS.

= Offset value.

Offset value is added to the measurement value.

Adjusted between -99 and +99°C.

The normal value is 0.

S.cod.

S.cod.

= Calibration menu access code

It should be 333.

Rt.CA.

rt.CA.

= The environment temperature is calibrated by this parameter. It is not displayed if input type is selected Pt 100.

S.Cod.

S.cod.

= Security menu access code.

It should be 444.

A.Con.

A.Con.

= Parameters of configuration menu access level code.

nonE = Not visible.

P.yES = Visible and modification can be done.

P. no = Visible and not modified.

A.CAL.

A.CAL.

= Parameters of calibration menu access level code.

no = Not visible

yES = Calibration can be done.

UnIt

.

UnIt

= The temperature unit.

Selectable as °C or °F.

TC.CA.

tC.CA.

= In this case, the calibration of thermocouple input can be made.

(See Note 1 below)

NOTE 1

Returns to the normal operation mode.

TC.CA.

SET

Run press and hold

SET

CAL.

5 seconds later

End.

SET

When holding key the message run flashes. In this case if key is pressed, calibration for TC input starts. Then the messages C.Str, a four digit number and Cal are seen in sequence on the lower display. After 5 seconds End message is seen. If the four digit number is 4999 or 5000 or 5001, it means TC calibration was successful. Otherwise calibration procedure should be repeated.

Before starting calibration procedure, 50.000mV referance voltage must be applied to the thermocouple inputs.

NOTE 2

SET

Pt.CA.

Press and hold

Run

SET

CAL.

Returns to the normal operation mode

5 seconds later

End.

SET

When holding key the message run flashes. In this case if key is pressed, calibration for Pt 100 input starts. The messages C.Str, a four digit number and Cal are seen in sequence on the lower display. After

5 seconds End message is seen. If the four digit number is 3190 or 3191 or 3192, this means Pt 100 calibration was successful. Otherwise, Calibration procedure should be repeated.

Before starting calibration procedure, make a connection between terminal 8 and 9. Then connect a

212.052ohm referance resistor should be connected between terminal 9 and terminal 10 or apply 300 °C from Pt-100 calibrator.

Values on the displays are default values.

Pt.CA.

Pt.CA.

= In this case, the calibration of Pt 100 input can be made.

(See Note 2 below)

----

Temperature value is higher than the end of the scale

Error Messages

----

Temperature value is higher than the end of the scale

PFA

Temperature sensor is broken or over temperature

PSC

Pt 100 or a sensor line is short circuited

HyS.H.

SET

6

Modification of Parameter

SET

5

SET

6

SET

SET

When holding key, the value of parameter flashes and using keys the requested value can be adjusted.

If key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If waited enough, the value increases 100 at each step. After 1 second following the release of the key, initial condition is returned. The same procedure is valid for the decrement key.

ETI741-E-04-R

DIMENSIONS

ETI 741

°F °C

Depth

97mm

2

SET

ENDA

TEMPERATURE INDICATOR

Connection cables

1 1

2

For removing mounting clamps:

- Push the flush-mounting

clamp in direction 1 as

shown in the figure left.

- Then, pull out the clamp in

direction 2.

Flush mounting clamp

Panel

Rubber packing

Note 1) While panel mounting, additional distance required

for connection cables should be considered.

2) Panel thickness should be maximum 10mm.

3) If there is no 90mm free space at back side of the device,

it would be difficult to remove it from the panel.

Temperature compansation sensor

Panel cut-out

+0.7

68 mm

75mm

CONNECTION DIAGRAM

ENDA ETI741 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The shielding must be grounded on the instrument side.

NOTE :

SUPPLY :

184-253V AC

50/60Hz 7VA

11

12

Line

Neutral

Fuse

F 100 mA 250V AC switch

Fuse should be connected.

SENSOR INPUT :

For J-K-T-S-R type thermocouple :

Use suitable compensation cables. Don't use

jointed cables. Pay attention to the polarities of the

thermocouple cables as shown in the figure right.

For resistance thermometer :

When 2 wired Pt 100 is used,

terminals 8 and 9 must be

short circuited.

8

9

10

Pt 100

230V AC Supply

Cable size: 1,5mm²

+

+

-

9

10

-

TC

Note : 1) Mains supply cords shall meet the requirements of IEC 60799

or IEC 60245.

2) In accordance with the safety regulations, the power supply

switch shall bring the identification of the relevant instrument

and it should be easily accessible by the operator.

Order Code : ETI741-     

1

Supply Voltage

230VAC...230V AC

24VAC.....24V AC

SM...........9-30V DC / 7-24V AC

230V AC +10% -20%

50/60Hz 7VA

11

12

8

9

10

+

Pt 100

-

TC

SN: XXXXXXXXX

ENDA

INDUSTRIAL ELECTRONICS

ETI741-230VAC

TEMPERATURE INDICATOR

Holding screw 0.4-0.5Nm

Equipment is protected througout by DOUBLE INSULATION.

SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.

Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL - TURKEY

Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01 url : www.enda.com.tr

3/3 ETI741-E-04-R