ENDA ETI741 TEMPERATURE INDICATOR
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
ENDA ETI741 TEMPERATURE INDICATOR
Thank you for choosing ENDA ETI741 temperature indicator.
ETI 741
°F
* 72 x 72mm sized.
* 4 digits display.
* Selectable sensor type.
* Input offset feature.
* Parameter access protection on 3 levels.
* Programming just by using keypad.
* CE marked according to European Norms.
* Measurement at °C and °F units.
°C
SET
ENDA
TEMPERATURE INDICATOR
TECHNICAL SPECIFICATIONS
Sensor type
Temperature range
°F
°C
J (Fe-CuNi) Thermocouple
K (NiCr-Ni) Thermocouple
T (Cu-CuNi) Thermocouple
S (Pt10Rh-Pt) Thermocouple
R (Pt13Rh-Pt) Thermocouple
Pt 100 Resistance Thermometer
Pt 100 Resistance Thermometer
EN 60584
EN 60584
EN 60584
EN 60584
EN 60584
EN 60751
EN 60751
0... 600 °C
0...1200°C
0... 400°C
0...1600°C
0...1600°C
-200...600 °C
-99.9...300.0 °C
+32... +1112 °F
+32... +2192 °F
+32... +752 °F
+32... +2912 °F
+32... +2912°F
-328... +1112 °F
-99.9...+543.0°F
Accuracy
0,2% (of full scale)
0,2% (of full scale)
0,2% (of full scale)
0,2% (of full scale)
0,2% (of full scale)
0,2% (of full scale)
0,2% (of full scale)
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature 0 ... +50°C/ -25... +70 °C
80% up to 31°C decreasing linearly 50% at 40°C .
Max. relative humidity
According to EN 60529
Front panel : IP65
Rated pollution degree
Rear panel : IP20
Height
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gases.
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
Line resistance
Data retention
EMC
Safety requirements
230V AC +10% -20%, 50/60Hz or 24V AC ±10%, 50/60Hz or optional 9-30V DC / 7-24V AC ±10% SMPS
Max. 7VA
2.5mm² screw-terminal connections
For thermocouple max.100ohm, for 3 wired Pt 100 max. 20ohm
EEPROM (minimum 10 years)
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting according to DIN 43 700.
W72xH72xD97mm
Approx. 395g (after packing)
Self extinguishing plastics.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
1/3
ETI741-E-04-R
SET
if
key is pressed while holding
key, the programming mode is enabled.
Entering from the programme mode to the run mode:
If no key is pressed within 20 seconds during programming mode, the data is stored automatically and the normal mode is entered.
SET
Alternatively, the same function occurs first pressing
key and then pressing
keys together.
SET
SET
CAL.
ConF.
ýnP.
OFFS.
inP. = Type of sensor and scale.
Pt = Pt 100 -200 to +600°C
Pt.0 = Pt 100 -99.0 to +300.0°C
FE.cn. = J (Iron vs. Copper-Nickel) 0 to +600°C
nc.nA. = K (Nickel-Cr.vs. Nickel-Alum.) 0 to +1200°C
c.cn. = T (Copper vs. Copper-Nickel) 0 to +400°C
P10.r. = S (Platinum-10%Rhodium vs. Pt.) 0 to +1600°C
P13.r. = R (Platinum-13%Rhodium vs. Pt.) 0 to +1600°C
S.cod.
oFFS. = Offset value.
Rt.CA.
Offset value is added to the measurement value.
Adjusted between -99 and +99°C.
The normal value is 0.
UnIt.
UnIt = The temperature unit.
Selectable as °C or °F.
TC.CA.
Returns to the normal
operation mode.
NOTE 1
SET
SET
TC.CA.
Run
CAL.
5 seconds
later
End.
Pt.CA.
press and
hold
SeCU.
S.cod. = Calibration
S.Cod.
menu access code
It should be 333.
S.cod. = Security menu
access code.
It should be 444.
A.Con. = Parameters of
rt.CA. = The environment
temperature is calibrated by
this parameter. It is not
displayed if input type is
selected Pt 100.
A.Con.
tC.CA. = In this case, the
A.CAL.
calibration of thermocouple
input can be made.
(See Note 1 below)
configuration menu access level
code.
nonE = Not visible.
P.yES = Visible and modification
can be done.
P. no = Visible and not modified.
A.CAL. = Parameters of
calibration menu access level
code.
no = Not visible
yES = Calibration can be done.
Pt.CA. = In this case, the
calibration of Pt 100 input
can be made.
(See Note 2 below)
SET
When holding
key the message run flashes. In this case if
key is pressed, calibration for TC input
starts. Then the messages C.Str, a four digit number and Cal are seen in sequence on the lower display. After 5
seconds End message is seen. If the four digit number is 4999 or 5000 or 5001, it means TC calibration was
successful. Otherwise calibration procedure should be repeated.
Before starting calibration procedure, 50.000mV referance voltage must be applied to the
thermocouple inputs.
Returns to the normal
operation mode
NOTE 2
SET
SET
Pt.CA.
Run
CAL.
5 seconds
later
Error Messages
----
PFA
PSC
Temperature sensor
is broken or
over temperature
Pt 100 or a sensor
line is short circuited
---Temperature value is
higher than the end
of the scale
Temperature value is
higher than the end
of the scale
End.
Press and
hold
SET
When holding
key the message run flashes. In this case if
key is pressed, calibration for Pt 100
input starts. The messages C.Str, a four digit number and Cal are seen in sequence on the lower display. After
5 seconds End message is seen. If the four digit number is 3190 or 3191 or 3192, this means Pt 100
calibration was successful. Otherwise, Calibration procedure should be repeated.
Modification of Parameter
SET
HyS.H.
SET
6
Before starting calibration procedure, make a connection between terminal 8 and 9. Then connect a
212.052ohm referance resistor should be connected between terminal 9 and terminal 10 or apply 300 °C
from Pt-100 calibrator.
5
SET
If
6
SET
key is pressed and held 0.6 seconds,
the value of the selected parameter changes
rapidly. If waited enough, the value
increases 100 at each step. After 1 second
following the release of the key, initial
condition is returned. The same procedure
is valid for the decrement key.
SET
Values on the displays are default values.
When holding
key, the value of parameter flashes and using
2/3
keys the requested value can be adjusted.
ETI741-E-04-R
DIMENSIONS
Depth
97mm
2
ETI 741
°C
78mm
72mm
°F
SET
ENDA
TEMPERATURE INDICATOR
Temperature
compansation sensor
Connection
cables
2
+0.7
68
75mm
mm
mm
1
For removing mounting clamps:
- Push the flush-mounting
clamp in direction 1 as
shown in the figure left.
- Then, pull out the clamp in
direction 2.
+0.7
1
Panel cut-out
68
Flush mounting
clamp
84mm
Panel
Rubber packing
Note 1) While panel mounting, additional distance required
for connection cables should be considered.
2) Panel thickness should be maximum 10mm.
3) If there is no 90mm free space at back side of the device,
it would be difficult to remove it from the panel.
CONNECTION DIAGRAM
ENDA ETI741 is intended for installation in control panels. Make sure that the device is used only for intended
purpose. The installation and electrical connections must be carried on by a qualified staff and must be according
to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the
device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe
soiling and make sure that the operation temperature is not exceeded. All input and output lines that are not
connected to the supply network must be laid out as shielded and twisted cables. These cables should not be
close to the power cables or components. The shielding must be grounded on the instrument side.
NOTE :
230V AC +10% -20%
50/60Hz 7VA
switch
230V AC Supply
Cable size: 1,5mm²
Fuse should
be connected.
For J-K-T-S-R type thermocouple :
Use suitable compensation cables. Don't use
jointed cables. Pay attention to the polarities of the
thermocouple cables as shown in the figure right.
For resistance thermometer :
When 2 wired Pt 100 is used,
terminals 8 and 9 must be
short circuited.
8
+
SENSOR INPUT :
11
12
Line
Neutral
9
10
9
+
Pt 100
TC
-
184-253V AC 11
50/60Hz 7VA 12
Fuse
F 100 mA 250V AC
+
SUPPLY :
10
TC
SN: XXXXXXXXX
8
9
Pt 100
10
Note : 1) Mains supply cords shall meet the requirements of IEC 60799
or IEC 60245.
2) In accordance with the safety regulations, the power supply
switch shall bring the identification of the relevant instrument
and it should be easily accessible by the operator.
Order Code : ETI741-     
1
Supply Voltage
230VAC...230V AC
24VAC.....24V AC
SM...........9-30V DC / 7-24V AC
SÝSEL MÜHENDÝSLÝK ELEKTRONÝK SAN. VE TÝC. A.Þ.
Yukarý Dudullu Barbaros Cad. Kutup Sok. No:20 34775 - ÜMRANÝYE/ÝSTANBUL - TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
3/3
url : www.enda.com.tr
ENDA INDUSTRIAL ELECTRONICS
ETI741-230VAC
TEMPERATURE INDICATOR
Holding screw 0.4-0.5Nm
Equipment is protected througout
by DOUBLE INSULATION.
ETI741-E-04-R