Enda EU4430 is an advanced PID Universal Controller offering precise temperature control with its versatile features and wide compatibility. It supports various sensor types, including thermocouples (J, K, L, T, S, R) and resistance thermometers (PT100), providing flexibility for different applications.
EU4430 allows you to select between heating or cooling control modes, enabling you to manage temperature in various systems. The dual setpoint values let you easily switch between different temperature targets.
Moreover, this controller boasts a range of input options, including 0-20mA, 4-20mA, 0-10V, 2-10V, 0-25mV, and 0-50mV. This versatility allows you to connect various sensors and transmitters seamlessly.
advertisement
Please read this document carefully before using this product. The guarantee will be invalidated if the device is damaged by not following instructions detailed in the manual. The company shall not be responsible for any damage or losses however caused, which may be experienced as a result of the installation or use of this product.
ENDA EU
4430
PID UNIVERSAL CONTROLLER
Thank you for choosing ENDA EU 4430 U niversal C ontroller Devices .
48x48mm sized.
Dual setpoint value can be selected.
PT100 ,J, K, L, T, S, R sensor ( thermocouple ) types can be selected.
0-20mA, 4-20mA, 0-10V, 2-10V, 0-25mV and 0-50mV input selections.
Auto calculation for PID parameters (SELF TUNE).
Self tune for automatic PID calculation or manually enter PID parameters if known.
Three different feature can be assigned to digital input.
Three different feature can be assigned to F function key.
Soft-Start feature.
Analogue, SSR or Relay Output Control selection.
0-20mA and 4-20mA Analogue Output Control selection.
A1 Relay output programmable as primary Alarm or PID Cooling Control output.
C/A2 Relay output can be used as secondary Alarm or Temperature Control output.
Heating/Cooling control selection.
Zero point input shift .
In case of sensor failure, periodically, auto-periodically running or relay state can be selected.
RS485 Modbus RTU communication protocol feature (Specify at order).
CE marked according to European Norms.
Order Code : EU4430
1 - Supply Voltage
230VAC...90 - 250V AC
24VAC.....24V AC
SM...........9-30V DC /
7-24V AC
1 2
2 - Modbus (Optional)
RS.....
... RS-485 Modbus Available
(Optional / Specify at order).
Blank ....
N/A
Please see EU4430 Modbus Address
Map and Connection Diagram Guide for
Modbus feature.
Input Type
PT100 Resistance Thermometer EN 60751
PT100 Resistance Thermometer EN 60751
J (Fe-CuNi) EN 60584
J (Fe-CuNi) EN 60584
K (NiCr-Ni)
K (NiCr-Ni)
EN 60584
EN 60584
L (Fe-CuNi)
L (Fe-CuNi)
Thermocouple
Thermocouple
T (Cu-CuNi) EN 60584
T (Cu-CuNi) EN 60584
0-20mA input
4-20mA input
0-10V input
2-10V input
0-25mV input
0-50mV input
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Max. Relative humidity
Rated pollution degree
Height
Scale Range
°C
-199.9...600.0
°C
-200...600 °C
-30.0....600.0°C
-30....600°C
-30.0...999.9°C
-30...1300°C
-30.0....600.0°C
-30....600°C
-30.0...400.0°C
-30....400°C
-40...1700°C
°F
-199.9...999.9
-328....1112
°F
°F
-22.0....999.9 °F
-22....1112 °F
-22.0....999.9 °F
-22....2372 °F
-22.0....999.9 °F
-22....1112 °F
-22.0....752.0 °F
-22......752
°F
-40....3092
°F
°F
-1999...+9999 (max. scale range 10000)
-1999...+9999 (max. scale range 10000)
-1999...+9999 (max. scale range 10000)
-1999...+9999 (max. scale range 10000)
-1999...+9999 (max. scale range 10000)
-1999...+9999 (max. scale range 10000)
Accuracy
0,2% ( for full scale )
0,2% ( for full scale )
0,2% ( for full scale )
0,2% ( for full scale )
0,2% ( for full scale )
0,2% ( for full scale )
0 ... +50°C/-25 ... +70°C
Relative humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.
According to EN 60529; Front panel : IP6 5, Rear panel : IP20
Max.
2000m
0,2% ( for full scale )
0,2% ( for full scale )
1 digit
1 digit
0,5% (for full scale)
0,5% (for full scale)
0,5% (for full scale)
1 digit
1 digit
1 digit
0,5% (for full scale)
0,5% (for full scale)
0,5% (for full scale)
0,5% (for full scale)
0,5% (for full scale)
1 digit
1 digit
1 digit
1 digit
1 digit
0,5% (for full scale) 1 digit
0,5% (for full scale) 1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
1 digit
KEEP AWAY device from exposed to corrosive, volatile and flammable gases or liquids and DO NOT USE the device in similar hazardous locations.
ELECTRICAL CHARACTERISTICS
Supply
Power consumption
Wiring
90-250V AC 50/60Hz, 24V AC ±%10 50/60Hz or 9-30VDC / 7-24VAC ± %10 SMPS
Max. 5VA
Power screw-terminal connections: 2.5mm²', Signal screw-terminal connections: 1,5mm².
Line resistance
Data retention
Max.
100 O hm
EEPROM (minimum 10 years)
EN 61326-1: 2013 (Performance criterion B satisfied for EN 61000-4-3 standard).
EN 61010-1: 2010 (Pollution degree 2, overvoltage category II)
EMC
Safety requirements
OUTPUTS
C/A2 Output
A1 Output
ANL/SSR Output
Life expectancy for relay
C ONTROL
C ontrol type
Control algorithm
A/D converter
Sampling time
Proportional band
Control period
Hysteresis
Output power
HOUSING
Housing type
Relay : 250V AC, 8A (for resistive load), NO+NC (Control or Alarm2 Output selection).
Relay : 250V AC, 8A (for resistive load), NO (Alarm1 and Cooling Control Output selection).
Max. SSR Output ; 0-20mA, 4-20mA, 24V 20mA. Max. load resistance ; 600 Ohm (12 bit 0.2% accuracy).
Without load 30.000.000 switching; 250V AC, 8 A (resistive load) 300.000 switching.
Single Setpoint and Alarm Control.
On-Off / P, PI, PD, PID (selection).
14 bit .
Min. 1 00ms .
Can be adjusted between %0 .0
and %100 .0 . If Pb=%0 .0
, ON OFF c ontrol is selected.
Can be adjusted between 1 and 125secs.
Can be adjusted between 1 and 50°C/F.
Setpoint value ratio can be adjusted between %0 and %100 .
Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W48xH48xD87mm
Weight Approx. 250g
Enclosure material Self extinguishing plastics
Avoid any liquid contact when the device is switched on.
DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.
ENDA TM
EU4430-EN-01-181119 1/4
DIMENSIONS
1
Depth
87mm
2
To removing the device from the panel :
While pressing both side of the device in direction 1 and push it in direction 2 .
Connection
Cables
1 2
PANEL CUT-OUT
45 mm
Note :
1) While panel mounting, additional distance required for connection cables should be considered.
2 ) Panel thickness should be 9mm maximum.
3) If there is no free space at back side of the device, it would be difficult to remove it from the panel.
100mm clearance should be left behind the device.
Flush mounting clamp
51mm
Panel
Holding screw
0.4-0.5Nm.
Equipment is protected throughout by
DOUBLE INSULATION
CONNECTION DIAGRAM
ENDA EU4430 PID Temperature Controllers are intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations
ENDA
INDUSTRIAL
ELECTRONICS
E U 44 3 0-230VAC
P ID UNIVERSAL CONTROLLER
1
2 11
3
902 5 0V AC
50/60Hz 5VA
12
4
5
+
-
ANL/SSR
OUT
AC 250V 2A
RESISTIVE
LOAD
OUT1
13
14
6 15
DIN
7
8
+ mA,mV, V
9
10 -
PT100 TC
MADE IN TURKEY
AC 250V 2A
RESISTIVE
LOAD
OUT2
SN: XXXXXXXXX
8 680407 724116
16
17
ENDA E U 44 3 0-230VAC -RS
INDUSTRIAL
ELECTRONICS
P ID UNIVERSAL CONTROLLER
1
2
3
+
-
A
RS- 485
B
RS-485 COM.
902 5 0V AC
50/60Hz 5VA
11
12
4
5
-
+
ANL/SSR
OUT
AC 250V 2A
RESISTIVE
LOAD
OUT1
13
6
14
DIN
15
7
8
+ mA,mV, V
AC 250V 2A
RESISTIVE
LOAD
OUT2
16
9 SN: XXXXXXXXX
17
TC
10 -
PT100
8 680407 724123
MADE IN TURKEY
ENDA
INDUSTRIAL
ELECTRONICS
E U 44 3 0-2 4 VAC
P ID UNIVERSAL CONTROLLER
1
2 11
3
2 4 V AC ±10%
50/60Hz 5VA
12
4
5
+
-
ANL/SSR
OUT
AC 250V 2A
RESISTIVE
LOAD
OUT1
13
14
6 15
DIN
7
8
AC 250V 2A
RESISTIVE
LOAD
OUT2
+ mA,mV, V
9
10
SN: XXXXXXXXX
-
PT100 TC
MADE IN TURKEY
8 680407 724154
16
17
ENDA E U 44 3 0-2 4 VAC -RS
INDUSTRIAL
ELECTRONICS
P ID UNIVERSAL CONTROLLER
1
2
3
+
A
-
B
RS- 485
RS-485 COM.
2 4 V AC ±10%
50/60Hz 5VA
11
12
4
5
-
+
ANL/SSR
OUT
AC 250V 2A
RESISTIVE
LOAD
OUT1
13
6
14
DIN
15
7
8
+ mA,mV, V
AC 250V 2A
RESISTIVE
LOAD
OUT2
16
9 SN: XXXXXXXXX
17
TC
10 -
PT100
8 680407 724161
MADE IN TURKEY
NOTE :
SUPPLY VOLTAGE
184-253V AC or
21.6-26.4V AC
50/60Hz 5VA
11
12
Fuse should be connected.
Line
Neutral
F 100 mA 250V AC
Swich
Supply
230V AC or 24V AC
Cable Size : 1,5mm²
SENSOR INPUT:
For Thermocouples :
Use the correct compensating cable. Do not make a n y s u p p l e m e n t t o c a b l e s . C o n n e c t t h e thermocouple cables to the right places at the input terminal.
For resistance (PT100) Sensor :
In order to using 2-wire resistance sensors (PT100),
8th and 9th terminals must be short circuited. Please check connection diagrams carefully.
TC
PT100
+
-
9
10
8
9
10
+
-
For 0-20mA,4-20mA, 0-10V, 2-10V,
0-25mV and 0-50mV inputs :
Check carefully sensor pinouts a n d t e r m i n a l s i g n s b e f o r e connecting the device.
0-20mA
0-10V
0-25mV
0-50mV
Inputs
+
-
9
10
+
-
Logic output of the instrument is not electrically insulated from the internal circuits. Therefore, when using a grounding thermocouple, do not connect the logic output terminals to the ground.
Note :
1) Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.
* MODBUS CONNECTION DIAGRAM
Master
B A B A
Termination should be accomplished by attaching 120 Ohm resistors to the start and at the end of the communication line.
Slave - 1
Please see EUPx420 Series Modbus Address Map and Connection Diagram Guide for Modbus feature.
B A
Slave - 2
Up to 127 slave devices can be controlled.
* Applies to devices with Modbus function.
B
120 Ohm
A
Slave - 127
Barbaros Cad. No:18
ENDA TM
EU4430-EN-01-181119 2 /4
TERMS
( 6 )
F
( 1 ) PV and SV Indicators
Character Height
( 2 ),( 3 ),( 4 ),( 5 ) Keypads
( 6 ) Status Indicators
( 1 ) Indicates measured value and set values in “Running Mode”.
Indicates the parameters and names in “Programming Mode”.
( 2 ) Increment key in “Running Mode” and “Programming Mode”.
Parameter selection key in “Programming Mode”.
( 3 ) Decrement key
By pressing this key in “Running Mode”, software version can be displayed.
Parameter selection key in “Programming Mode”.
( 4 ) Selectable function key “Running Mode”.
Menu selection key in “Programming Mode”.
( 5 ) Control and Alarm set key in “Runnig Mode”.
Parameter set key in “Programming Mode”
PV 7 Segment 4 digits green LED , SV 7 Segment 4 digits green LED display.
PV Display 12.0mm , SV Display 8.13mm
Mi c ro switch
C ontrol, Alarm1 , Alarm2, Analog output, SSR output and status indicator symbols.
ALARM1 AND ALARM2 OUTPUT TYPES
Independent Alarm
A1.tp.
= indE
SV
ON
Deviation Alarm
A1.tp
=
dE.
SV
A1.St.
= Hi
Band
Alarm
A1.tp.
=
bAnd
SV
ON
OFF A1.St.
= lo
OFF
ON ON
A1.St.
= Lo
OFF A1.St.
= Hi
OFF a1,Hy A1.Hy
A1.Hy
A1.Hy
ASV
(ASV min. = beginning of scale
ASV max. = end of scale)
-300
SV+ASV
+300
(ASV min. =-300, ASV maks. = +300)
SV = CONT output set value ASV = Alarm output set value
SV-ASV SV+ASV
300 300
SV =CONT output set value ASV = AL1 output set value
(ASV min. = 0, ASV ma x . = +300)
Band Alarm With Inhibition
A1,tp.
=
bAn.i
SV+ASV
SV
SV-ASV
SV+ASV
SV
SV-ASV
ON
OFF
B eginning
ON
OFF
Band alarm is possible B eginning
Band alarm is possible
SV =Set point of CONT output ASV = Set point of AL1 output (ASV min. = 0, ASV max. = 300 )
SETTING UP ALARM CONTROL AND SETPOINT VALUES
3 seconds later
250
400
C1.SE.
400
C2.SE.
400 a1.SE.
500 a2.SE.
500 m.SEt
50
Tuşuna basılırsa kontrol ve alarm set değerleri ayar konumuna geçilir.
C1.SE.
399
C2.SE.
399 a1.SE.
499 a2SE.
499 m.SEt
49
C1.SE.
400
3 seconds later
C2.SE.
400
3 seconds later a1.SE.
500
3 seconds later a2.SE.
500
3 seconds later m.SEt
50
3 seconds later
If one of the d.in.c.
or f.kE.c.
parameters are set to the C2.S.A.
value, this parameter can be displayed.
If the C.O.SE.
parameter is set to SSR out, this parameter can be displayed.
If one of the d.in.c.
or f.kE.c.
parameters are set to the mAnu.
and if C. Pb is different from 0 , this parameter can be displayed.
pfa
400
ERROR MESSAGES
No communication with sensor.
(Sensor and/or cable broken or not connected)
----
Temperature value is higher than scale.
400
____
400
Temperature value is lower than scale.
ENDA TM
EU4430-EN-01-181119 3 /4
ENTERING TO PROGRAMMING MODE
If key is pressed while holding key, the "Programming Mode" is entered.
ENDA EU4430 PROGRAMMING DIAGRAM
RUNNING MODE
During in "Programming Mode", if no key is pressed for 20 sec, settings automatically saved and device returns to the "Running Mode" (to the home screen). Alternatively, by pressing key "Running Mode" is entered and by pressing both keys at once, settings automatically saved and device returns to the "Running Mode" (to the home screen).
Con.o.
C.s.Lo.
-30
A
C.s.lo. = Lower limit for C/A1
Output control, setpoint value.
Can be adjusted between 0 and
C.s.Hi.
Al1.o.
B
A1.S.L
-30 a1.s.l
= Alarm1 set value lower limit.
Can be adjusted between 0 and
A1.S.H
parameter value.
A1.S.H
600 a1.s.H
= Alarm1 set value upper limit.
Can be adjusted between A1.S,L and upper scale value.
C.s.Hi.
600
C.s.Hi. = Upper limit for C/A1
Output Control, setpoint value.
Can be adjusted between C.s.Lo.
and
Upper scale value.
A1
C. pb
4.0
C. Pb = P roportional band value for C/A1 Output .
Can be a djust ed between 0 .0
% and
100 .0.% If C.Pb
parameter set to
0.0% , On-Off control will be accepted.
C.Hys
2
C.Hys
= H ysteresis value for C/A1
O utput .
Can be a djust ed between between
1 °C and 50 °C.
A2
A2
A2
A2
A2
A3
C. ti
4.0
C. ti = Integral value for C/A1
Output .
Can be adjusted between 0.0 and
100.0 minutes. If C. ti parameter set to 0.0
, integral will be disabled.
C. td
1.00
C. Ct.
1
C.P.St.
0
C.EC.t.
E.PS.
C.E.p.s.
0 s.s.t.s.
0
C.typ
HEAt
C. td = C /A1 Output Derivative value .
Asjustable between 0.00
and 25.00
minutes.
If C. td parameter set to
0.0
, derivative will be disabled.
C. Ct.
= C/ A1 Output periodic time duration.
Adjustable between 1 and 250 seconds.
C.p.st
= C/ A2 output power percentage at C/A1 set value.
Can be adjusted be tween 0% and
100% .
B1
B1
B2
C.E.C,t.
= Control type selection for sensor failures.
If E.PS
selected, controlling will be performed to according to C.E.P.S.
proportional control parameter.
If Auto is selected, controlling will be performed to last recorded set value percentage before probe failure.
C.E.P.s
.
= C/ A1 Output power percent selection on probe failure.
Can be adjusted between %0 and
%100 .
If C.Pb
set to 0.0
(On/Off
Control) and C.E.P.S.
set to 0 , output will be OFF, on failure. If C.E.P.S.
set to different value from 0 , output will be
ON, in case of failure.
S.S.t.S.
= Soft start timer set value.
This parameter determines how many minutes will be reached to the setpoint value on power-up.
Can be adjusted between 0 and 250 minutes. If set to 0, the soft start feature will be canceled and the setpoint value will be reached maximum speed.
B3
B3
B3
B3
B2
C.typ.
= Output controlling type selection
HEAt.
= Heating control can be performed.
CooL = Cooling control can be performed.
A1.HY
2
A1.tP.
INDE.
A1.tp
= Alarm1 types .
Six alarm types can be selected.
indE.
= Independent alarm dE.
= Deviation alarm bAnd = Band alarm bAn.i
= Band with inhibition in.Co. = A1 output independent cooling control rE.Co
= A1 output relative cooling control
A1.St.
Hi.
A1.Er.
ON
A1.PB
0.0
A1.ti
0.0
A1s = Status selection for
Alarm1 Output
If Hi is selected, A1 output is above the Alarm1 set value ; ON. If lo is selected, A1 Output is above the
Alarm1 set value ; OFF.
A1.Er.
= Alarm1 condition selection on probe failure on = A1 Output is ON, in case of probe failure.
off = A1 Output is OFF, in case of probe failure.
A1.Pb
= A1 Output, proportional band value.
Can be adjusted between 0 % and
100 %.
If A1.Pb
Parameter set to %0, On-
Off control will be accepted.
A1.ti
= A1 Output, integral value.
Can be adjusted between 0.0 and
100.0 minute.
If A1.ti
parameter set to 0.0, integral will be disabled.
A1.td
0
A1.td
= A1 output derivative value.
Can be adjusted between 0.00 and
25.00 minutes.
If A1.td
parameter set to 0.00, devirative will be disabled.
A1.Ct
1
A1.Ct
= A1 Output Period Time.
Can be adjusted between 1 and 250 seconds .
A1.ps
0
A1.Ep
0 a1.Hy
= Hysteresis of the Alarm2 output.
Can be adjusted between 1 and 50°C.
A 1 . P S = A 1 o u t p u t p o w e r percentage at A1 set value.
Can be adjusted be tween 0% and
100%.
A1.EP
.
= A1 Output power percent selection on probe failure.
Can be adjusted between 0 % and
100 % .
A1
This parameter will be activated if the
C.Pb
parameter set to “0”.
A2
A3
This parameter will be activated if the
C.Pb
parameter different from “0”.
This parameter will be activated if the C.Pb
parameter set to “0” or
C.E.Ct
set to E.P.S.
B1
B2
B3
A1t.P
Parameter can not be displayed if inC.o.
or rEC.o.
is selected.
A1t.P
Parameter will be activated if inC.o.
or rEC.o.
is selected.
This parameter will be activated if the
A1.tp
parameter set to in.Co.
or rE.Co.
and if the A1.Pb
parameter is different from “0”
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Barbaros Cad. No:18 Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01 url : www.enda.com.tr
Al2.o.
C
If co.SE
parameter is different from C-A2 , this menu can be displayed in
SSR Out devices.
D1
Conf..
D inp.t.
J inp.t.
= Input Type Selection.
Please see “Input Type
Selection Table” for details at the right side of this page.
A2.S.L
-30 a2.s.l
= Alarm2 set value lower limit.
Can be adjusted between 0 and
A2.S.H
parameter value.
D1
Unit
°C
Unit =
Unit Selection.
°C = °C / °F = °F
A2.S.H
600
A2.HY
2
A2.tP
INDE.
a2.s.H
= Alarm2 set value upper limit.
Can be adjusted between A2.S,L and upper scale value.
a2.Hy
= Hysteresis of the Alarm2 output.
Can be adjusted between 1 and 50
A2.tp
= Alarm 2 types .
Four alarm types can be selected.
indE.
= Independent alarm dE.
= Deviation alarm bAnd = Band alarm bAn.i = Band with inhibition fltr.
20
C.o.sE
C-A2 offs.
0 d.Adr.
1 fLtr.
= Coefficient of Digital Filter.
Provides to filter for displayed value.
Adjustable between 1 and 200. If this parameter set to 1, digital filter runs quickly. If the parameter is set to 200, filter runs slowly. This parameter value shouldbe increased in interference environments.
C.o.sE
= Control output selection.
C-A2 = C/A2 (Relay) output selection.
SSR = SSR output selection.
0-20 = 0-20 mA analogue output selection.
4-20 = 4-20 mA analogue output selection.
oFFS.
= Offset Value.
The offset value is added to the measurement value. This feature is used to eliminate errors that may occur due to the distance from the measuring probe to the measuring point.
Can be adjusted between -99 and
100°C. Default value is 0.
D.aDr.
=Rs485 Connection Address.
Can be adjusted between 1 and 247.
A2.St.
hi.
A2.Er.
ON
A2s = Status selection for
Alarm2 Output
If Hi is selected, A2 output is above the Alarm2 set value ; ON. If lo is selected, A2 Output is above the Alarm2 set value ; OFF.
A2.Er.
= Alarm2 condition selection on probe failure on = A 2 Output is ON, in case of probe failure.
off = A2 Output is OFF, in case of probe failure.
D3
D3
D4 baud
9.60
baud = ModBus Baud Rate for
RS485
Can be adjusted to off, 2.40, 4.80,
9.60, 19.20 and 38.40.
d.in.C.
nonE d.in.C.
= Digital input setting parameter.
nonE = Digital input is closed.
C2.S.A.
= if digital input is activated, 2nd set value is used.
manu.
= Manual mode start in case of digital outputs are active and rational output generated according to period v a l u e i n C . C t p a r e m e t e r a n d percentage value in m.SEt
parameter.
dSP.o.
= If the digital input is activated, only temperature value will be indicated.
F.kE.C.
nonE
F.kE.C.
= Function key setting parameter.
nonE = Function key is OFF.
C2.S.A. = 2nd. set value can be used by using function key.
manu.
= Manual mode can be accessed by using function key.
dSP.o.
= Temperature value will be indicated by using function key.
A.o.Lo.
0
A.o.Lo.
= Minimum Output Percent for
Analog Output.
Can be adjusted between 0 and A.o.Hi.
s.tun.
E s.t.us.
Pid.t.
25 s.t.us.
= Self tune Control Parameter.
If keys are pressed together, main screen displayed and if the temperature is not high, pid.t.
message flashes on display and the self tune process starts automatically. If the initial temperature is higher to self-tune, tE.hi
. message appears and waits until the temperature goes down. Then Pid.t.
message appears and self tune procedure starts automatically. After the self tune procedure, C.Pb
, Ct , C.dt
and C.Ct.
values are stored in memory and "Running mode"
(main screen) is entered. After the successful self tune completion, S.tun.
menu will be removed automatically. In order to re-tune, s.t.sc.
parameter should be set to p.yEs
in
SECU menu.
25
400
Conf..
D7
D7
D7
STOPPING SELF TUNE s.tun.
When the self-tune operation needs to be terminated, “Programming Mode" should be entered by using keys and S.tun
menu should be selected. s.t.us.
By using key, S.t.uS
parameter is selected and self-tune process can be terminated by pressing with together
keys.
D d.P.SE.
0 d.P.SE.
= Decimal Point selection for mA Inputs .
Can be adjusted between 0 and 0.000 u.S.Lo.
u.S.Lo.
= Lower Scale Value for mA
Inputs.
Can be adjusted between -1999 and
( u.S.Hi.
- 10 ) .
u.S.Hi.
2000 u.S.Hi.
= Upper Scale Value for mA
Inputs.
Can be adjusted between ( u.S.lo
+
10 ) and 9999.
d.lth
10 d .
lth = Display Brightness
Can be adjusted between 1 and 20.
D4
A.o.Hi.
100
A.o.Hi.
= Maximum Analog Output
Percent for Analog Output.
Can be adjusted between A.o.Lo.
and100
D6
R.o.Hi.
600
R.o.Ho.
= Upper Scale Value for
Retransmission Output.
Can be adjusted between R.o.Lo.
and upper scale value.
D5
D6
R.trs.
nonE
R.o.Lo.
-30
R.trS.
= Control Parameter for
Retransmission Output.
nonE = Retransmission OFF.
0 - 2 0 = 0 - 2 0 m A A n a l o g retransmission output.
4-20 = 4-20mA Analog retransmission output.
R.o.Lo.
= Lower Scale Value for
R etransmission Output.
Can be adjusted between lower scale value and R.o.Hi.
.
SECU.
S.Cod.
0
F
S.Cod
= Security menu access code.
To accessing security menu, 430 should be entered.
While S.Cod
code 0 ( S.Cod = 0 ) , by held down the key and by pressing key for 4 seconds, dEfP message appears and default mode is entered.
Co.sc.
p.yEs
a.1..sc.
p.yEs
a.2.sc.
p.yEs
Cn.sC.
p.yEs
S.t.sc.
p.yEs
Cosc.
= Security Access Level for
CoN.o
Parameter.
nonE = Menu invisible.
P.yEs
= Modification can be done.
P. no = Only visible.
a.1.sc.
= Security Access Level for al1.o.
Parameter.
nonE = Menu invisible.
P.yEs
= Modification can be done.
P. no = Only visible.
a.2.sc.
= Security Access Level for al2..o.
Parameter.
nonE = Menu invisible.
P.yEs
= Modification can be done.
P. no = Only visible.
Cn.sC.
= Security Access Level for
Conf.
Parameter.
nonE = Menu invisible.
P.yEs
= Modification can be done.
P. no = Only visible.
Pno = Menu visible only.
S.t.Sc..
= Security Access Level for
S.tun...
Parameter.
nonE = Menu invisible.
P.yEs
= Modification can be done.
D1
Changes to this parameter may cause some parameter values to change.
D2
This parameter can be displayed if the
C.o.SE
Parameter set to A.con.
D3
This parameter availble in RS485-Modbus devices only.
D4
D5
This parameter can be displayed if the
CoSE.
parameter set to “0-20” or “4-20”.
This parameter can be displayed if the
CoSE.
parameter set to “ C-A2 ”.
D6
This parameter can be displayed if the
CoSE.
parameter set to “ C-A2 ” and if the
RtrS parameter set to “0-20” or “4-20”.
D7
This parameter can be displayed if the inPt parameter set to “ mV ” , “mA” or “V”.
P l e a s e s e e E U 4 4 3 0 M o d b u s
Address Map and Connection
Diagram Guide for Modbus feature.
C.HyS.
6
Parameter Setting Diagram
C.HyS.
6
C.HyS.
5
C.HyS.
6
When holding key, selected parameter flashes and desired value can be adjusted by using keys.
If key is pressed and held 0.6 seconds, the value of the selected parameter changes rapidly. If waited enough, the value increases
100 at each step. After 1 second following the release of the key, initial condition is returned. The same procedure is valid for the decrement key.
____
400
ANNOTATIONS
I n f o r m a t i o n t r a c k i n g m e t h o d a b o u t t h e parameters is as follows.
A B C D
A1
A2
A3
On the device screens shown on this page ;
- First line indicates the parameter name,
- Second line indicates the current parameter's value.
At the same time, the value shown in the second line is the default value of the device.
A1.td
0
Parameter name.
Parameter value
(default value).
Input Type Selection Chart inp.t.
= Input Type selection.
Pt.0
= PT100 - Decimal,
Pt.
= PT100 Non-decimal,
J.0
= J Type - Decimal, j = J Non-decimal, k.0
= K Type - Decimal, k = K Non-decimal,
L.0
= L Type - Decimal,
L = L Non-decimal, t.0
= T Type - Decimal, t = T Type, s = S Type , r = R Type
0-20 = 0-20 mA input,
4-20 = 4-20 mA input,
0-10 = 0-10 V input,
2-10 = 2-10 V input,
0-25 = 0-25 mV input,
0-50 = 0-50 mV input.
C h a n g e s t o t h i s parameter may cause s o m e p a r a m e t e r values to change.
pfa
400
ERROR MESSAGES
No communication with sensor.
(Sensor and/or cable broken or not connected)
----
400
Temperature value is higher than scale.
Temperature value is lower than scale.
4/4 EU4430-EN-01-181119
ENDA EU4430 PID TEMPERATURE CONTROLLER
MODBUS PROTOCOL ADDRESS MAP
1.1 Memory Map for Holding Registers
Parameter
Number
Holding Register
A dres s
Data
De c
Type
Paramet er Description
H4
H5
H6
H7
H8
H9
H0
H1
0000d (0000h)
000 1 d (000 1 h)
H2
H3
000 2 d (000 2 h)
000 3 d (000 3 h)
Word Control output, temperature setpoint value
Word Control output, 2nd temperature setpoint value
Word Control output, minimum setpoint value
Word
Control output, maximum setpoint value
000 4 d (000 4 h) Word Control output, proportional band setpoint value (Adjustable between 0 .0
% and 100 .0
% )
000 5 d (000 5 h) Word
Control output, hysteresis value (Adjustable between 1 and 50 °C or °F )
000 6 d (000 6 h) Word Control output, integral time (Adjustable between 0.1 and 100.0 minute )
000 7 d (000 7 h) Word Control output, derivative time (Adjustable between 0.01 and 10.00 minute )
000 8 d (000 8 h) Word Control output, time period setpoint value (Adjustable between 1 and 125 second)
000 9 d (000 9 h) Word Control output, set value power ratio (Adjustable between 0% and 100%)
H10
H11
00 10 d (000 A h) Word Control output energy percentage in case of sensor error (can be set between 0% to 100%)
00 11 d (000 B h) Word Control output, soft start value
H12
H13
H14
H15
H16
H17
00 12 d (000 C h) Word Alarm1 output temperature setpoint value
00 13 d (000 D h) Word Alarm1 output minimum setpoint value limit
00 14 d (000 E h) Word Alarm1 output maximum setpoint value limit
00 15 d (000 F h) Word Alarm1 output proportional band set value (Adjustable between 0 .0
% and 100 .0
% )
00 16 d (00 1 0h) Word Alarm1 output hysteresis value (Adjustable between 1 and 50 °C or °F )
00 17 d (00 11 h) Word
Alarm1 output, integral time (Adjustable between 0.1 and 100.0 minute )
H18
H19
H20
H21
00 18 d (00 12 h) Word Alarm1 output, derivative time (Adjustable between 0.01 and 10.00 minute )
00 19 d (00 13 h) Word Alarm1 output, time period setpoint value (Adjustable between 1 and 125 second)
00 20 d (00 14 h) Word Alarm1 output, set value power ratio (Adjustable between 0% and 100%)
H22
H23
H24
00 21 d (00 15 h) Word
Alarm1 output, set value power ratio in case of sensor failure (Adjustable between %0 and %100)
00 22 d (00 16 h)
00 23 d (00 17 h)
Word
Word
Alarm1 output type selection ( Values can be given from 0 to 4 ) (0 = Independent alarm ,
1 = Deviation alarm , 2 = Band alarm, 3 = Active alarm after in band time ,
4 = Alarm1 output, cooling control selection )
Alarm2 output, temperature setpoint value
00 24 d (00 18 h) Word Alarm2 output minimum setpoint value limit
H25
H26
H27
00 25 d (00 19 h) Word
Alarm2 output maximum setpoint value limit
00 26 d (00 1A h) Word Alarm2 output, hysteresis value (Adjustable between 1 and 50 °C or °F )
H33
H34
H35
00 27 d (00 1B h) Word Alarm2 output type selection ( Values can be given from 0 to 3 ) (0 = Independent alarm ,
1 = Deviation alarm , 2 = Band alarm, 3 = Active alarm after in band time )
H28
H32
00 28 d (00 1C h)
00 32 d (00 20 h)
Word
Input selection number (0 = PT100 Decimal, 1 = Pt100 Non-decimal, 2 = J Decimal,
3 = J Non-decimal, 4 = K Decimal, 5 = K Non-decimal, 6 = L Decimal, 7 = L Non-decimal,
8 = T Decimal, 9 = T Non-decimal, 10= S Non-decimal, 11 = R Non-decimal, 12 = 0-20mA,
13 = 4-20mA, 14 = 0-10V, 15 = 2-10V, 16 = 0-25mV, 17 = 0-40mV
H29
H30
H31
00 29 d (00 1D h)
00 30 d (00 1E h)
Word
Word
ModBus device address (Adjustable between 1 and 247)
Modbus communication speed (Baudrate) (0 = Modbus cancel, 1 = 2400 bps, 2 = 4800 bps,
3 = 9600 bps, 4 =19200 bps, 5 = 38400 bps)
00 31 d (00 1F h) Word Digital filter coefficient ( Adjustable between 1 and 200 , 1 = filter is disable )
Word
Control output, selection value ( 0 = C/A2 Control output selection, 1 = SSR/ANL is SSR,
2 = SSR/ANL is 0-20mA, 3 = SSR/ANL is 4-20mA.
ATTENTION !! H42 parameter will be 0 if this parameter set to different from 0.
00 33 d (00 21 h) Word
Analog output minimum out percentage
00 34 d (00 22 h) Word
Analog output maximum out percentage
00 35 d (00 23 h) Word
Offset value
H36 00 36 d (00 24 h) Word
Function control parameter.
( 23040d ( 5A00h ) self tune stops when this value is entered )
( 23041d ( 5A01h ) self tune starts when this value is entered )
( 23042d ( 5A02h ) returns to factory defaults when this value is entered)
H37
H38
H39
00 37 d (00 25 h) Word Reserverd
00 38 d (00 26 h)
00 39 d (00 27 h)
Word
Reserverd
Word Manual control output percentage (can be adjusted between 0% and 100%)
Read / Write
Permission
Parame ter
Name
Default
Value
C1.SE.
C2.SE.
C.S.Lo.
C.S.Hi.
C. Pb.
C.HyS..
C. ti.
C. td.
C. Ct.
C.C.p.S.
C.E.p.S.
S.St.S.
A1.SE.
A1.S.l.
A1.S.H.
A1.Pb.
A1.Hy.
A1.ti.
A1.td.
A1.Ct.
A1.P.S.
A1.E.P.
500
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
0
600
0
2
0
0
20
0
0
400
400
0
600
4
2
40
100
20
0
0
0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
A1.tP.
A2.SE.
A2.S.L.
A2.S.H.
A2.Hy.
A2.tP.
inP.t.
d.Adr.
baud.
FLtr.
C.o.SE..
A.o.Lo..
A.o.Hi..
oFFs.
----
----
---m.SEt
0
500
0
600
2
0
5
0
100
0
0
20
20
50
1
3
10
0
.
ENDA TM
EU4430-Modbus-EN-01-181121 1/ 3
ENDA EU4430 PID TEMPERATURE CONTROLLER
MODBUS PROTOCOL ADDRESS MAP
1.1 Memory Map for Holding Registers (continue)
Parameter
Number
Holding Register
Data
A dres s
Type
De c imal (Hex)
H40
H41
00 40 d (00 28 h)
00 41 d (00 29 h)
Word
Word
Paramet er Description
Digital input control parameter ( 0 = Digital input off, 1 = 2nd set value can be selected by digital input,
2 = Manual mode can be entered via digital input, 3 = Can be switched to display mode via digital input)
Function key control parameter ( 0 = Function key off, 1 = 2nd Set value can be selected by function key,
2 = Manual mode can be entered by using function key, 3 = Can be switched to display mode by using function key)
Read / Write
Permission
Parame ter
Name
R/W
R/W d.in.C.
F.kE.C.
Default
Value
0
0
H42 00 42 d (00 2A h) Word
Retransmission output control parameter:
If this parameter is 0 , Retransmission output; off
If this parameter is 1, Analog output; 0-20mA Retransmission output
If this parameter is 2, Analog output; 4-20mA Retransmission output
ATTENTION!! To setting up this parameter, H32 parameter must be set to 0.
R/W R.trS.
0
H43
H44
H45
H46
H47
H53
00 43 d (00 2B h)
00 44 d (00 2C h)
00 45 d (00 2D h)
00 46 d (00 2E h)
00 47 d (00 2F h)
00 53 d (00 35 h)
Word
Word
Word
Word
Word
Word
Retransmission output lower scala value.
Retransmission output upper scala value.
Decimal Point selection for mA anv V inputs.
User defined lower scale value for 0-20mA, 4-20mA, 0-10V and 2-10V input selections
User defined upper scale value for 0-20mA, 4-20mA, 0-10V and 2-10V input selections
Display Brightness (can be adjusted between 1 and 20)
R/W
R/W
R/W
R/W
R/W
R/W
R.o.Lo.
R.o.Hi.
d.P.SE.
u.S.Lo.
u.S.Hi.
d.lth
0
600
0
0
9999
10
H48
H49
H50
H51
H52
00 48 d (00 30 h)
00 49 d (00 31 h)
00 50 d (00 32 h)
00 51 d (00 33 h)
00 52 d (00 34 h)
Word
Word
Word
Word
Word
Control output menu, security parameter ( 0 = Menu invisible,
1 = Menu programmable, 2 = Menu only visible )
Alarm1 output menu security parameter ( 0 = Menu invisible,
1 = Menu programmable, 2 = Menu only visible )
Alarm2 output menu, security parameter ( 0 = Menu invisible,
1 = Menu programmable, 2 = Menu only visible )
Configuration menu, security parameter ( 0 = Menu invisible,
1 = Menu programmable, 2 = Menu only visible )
Self tune menu, security parameter ( 0 = Menu invisible,
1 = Self tune can be done)
R/W
R/W
R/W
R/W
R/W
Co.Sc.
A.1.Sc.
A.2.Sc.
Cn.Sc.
S.t..Sc.
1
1
1
1
1
1.2 Memory Map for Coils
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
Parameter
Number
Coil Address
(0000)h
(0001)h
(0002)h
(0003)h
(0004)h
(0005)h
(000 6 )h
(000 7 )h
(000 8 )h
(000 9 )h
Data
Type
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Bit
Paramet er Description
Alarm2 condition (0 = A ctive Low ,1 = Active High)
Alarm2 condition selection on probe failure (0 = Off , 1 = On )
Alarm 1 condition (0 = A ctive Low ,1 = Active High)
Alarm1 condition selection on probe failure (0 = Off , 1 = On )
Control output configuration ( 0 = Heat ; 1 = Cool )
Temperature unit (0 = °C ; 1 = °F)
Control outputs active (0 = Control outputs active , 1 = Only display mode )
Controlling according to 2nd temperature setpoint ( If C7 = 0 is H0, if C7 = 1 is H1)
Auto/Manual selection (0 = Automatic "Running mode" , 1 = Manual "Running mode". In this mode, output generated according to H39 parameter.)
Control procedure in case of probe failure (0 = H10 proportional control according to percentage value ,
1 = Error found before the setpoint control is done with the value of the proportional control
1.3 Memory Map for Input Registers
Parameter
Number
Input Register
A dres s
Data
De c imal (Hex)
Type
I0
I1
I2
I3
Paramet er Description
0000d (0000h)
000 1 d (000 1 h)
000 2 d (000 2 h)
Word Measured temperature
Word Analog output percentage
Word
Measurement error codes
0 = No error, 1 = Sensor short circuit, 2 = Lower scale error,
3 = Upper scale error, 4 = Sensor connection lost, 5 = Wrong input selection.
000 3 d (000 3 h) Word
Self tune condition codes
0 = No error, 1 = Initial temperature is higher than 60% setpoint value ,
2 = Calculating PID parameters , 3 = Calculating power set parameters
I4
I5
I6
000 4 d (000 4 h)
000 5 d (000 5 h)
000 6 d (000 6 h)
Word Current (active) temperature setpoint .
Word Reserved
Word Current (active) decimal point value (0 = No decimal point , 1 = 0.0 Decimal point is tenths
1
.
4
Memory Map for Software Revision Input Registers
Software
Revision
61472d (F020h)
14
Word
Software name and update is read in ASCII format and as 14 word.
For example : EU44 3 0-01 03 Feb 201 7 .
Memory Formats :
Word
1
Word
2
U E 4 4
Word
3
0 3
Word
4
0 -
Word
5
1
Word
6
Word
7
Word
8
Word
9
Word
10
Word
11
3 0 F b e
Word
12
Word
13
2 1 0
Word
14
. 7
NOTE :
To view each word correctly by changing the byte sequences should be displayed as ASCII TEXT
Read / Write
Permission
Parame ter
Name
Default
Value
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
A2.st.
A2.Er.
A1.St.
A1.Er.
C.tyP.
unit
----
----
----
0
0
0
0
0
1
0
1
0
R/W C.E.c.t.
0
Read / Write
Permission
R
R
R
R
R
R
R
R
ENDA TM
EU4430-Modbus-EN-01-181121 2 / 3
ENDA EU4430 PID TEMPERATURE CONTROLLER
MODBUS PROTOCOL ADDRESS MAP
1.
5
Memory Map for Discrete input
Parameter
Number
Discrete
I
nput
A
d
d
res
s
D0
D1
D2
D3
(0000)h
(0001)h
(0002)h
(000 3 )h
Data
Type
Bit
Bit
Bit
Bit
Paramet er Description
C/A2 Control output status (0 = OFF ,1 = ON)
A1 Output status (0 = OFF , 1 = ON )
SSR Output status (0 = OFF ,1 = ON)
Digital input status (0 = OFF ,1 = ON)
Read / Write
Permission
R
R
R
R
2
. MODBUS ERROR MESSAGES
Modbus protocol has two types error, communication error and operating error. Reason of the communication error is data corruption in transmission. Parity and CRC control should be done to prevent communication error. Receiver side checks parity and CRC of the data. If they are wrong, the message will be ignored. If format of the data is true but function doesn’t perform for any reason, operating error occurs. Slave realizes error and sends error message. Most significant bit of function is changed '1' to indicate error in error message by slave. Error code is sent in data section.
Master realizes error type via this message.
Error Code
01
02
03
Name
ILLEGAL FUNCTION
ModBus Error Codes
Description
The function code received in the query is not an allowable action for the slave. If a
Poll Program Complete command was issued, this code indicates that no program function preceded it.
ILLEGAL DATA ADDRESS
ILLEGAL DATA VALUE
The data address received in the query is not an allowable address for the slave.
A value contained in the query data field is not an allowable value for the slave.
Message sample ;
Structure of command message (Byte Format)
Device Address
Function Code
Beginning address of coils.
Number of coils (N)
CRC DATA
MSB
LSB
MSB
LSB
LSB
MSB
(0A)h
(01)h
(04)h
(A1)h
(00)h
(01)h
(AC)h
(63)h
Structure of response message (Byte Format)
Device Address
Function Code
Error Code
CRC DATA
LSB
MSB
(0A)h
(81)h
(02)h
(B0)h
(53)h
As you see in command message, coil information of (4A1)h = 1185 is required but there isn’t any coil with 1185 address.
Therefore error code with number (02) ( Illegal Data Address ) sends.
B A
Master
B A
Slave - 1
Termination should be accomplished by attaching 120 Ohm resistors to the start and at the end of the communication line.
* MODBUS CONNECTION DIAGRAM
B A
Slave - 2
Up to 127 slave devices can be controlled.
* Applies to devices with Modbus function.
B
120 Ohm
A
Slave - 127
ENDA TM
EU4430-Modbus-EN-01-181121 3 / 3