Ascon Tecnologic K48 Controller and Mini-programmer Quick Guide
Reklama
Reklama
K48
Controller and
Mini-programmer
Quick Guide -Code: FK48ENG09
Ascon Tecnologic S.r.l
Via Indipendenza, 56
27029 Vigevano (PV) - ITALY
Tel.: +39 0381 69871
FAX: +39 0381 698730 http:\\www.ascontecnologic.com
[email protected]
1 - OUTLINE DIMENSIONS (mm)
98
Tun
K48
285.3
Prg
Out1 Out2 = + Out3
9.5
Panel + Gasket max. 9 mm
Bracket type 1
Bracket type 2
2 - CONNECTION DIAGRAM
Out1, Out2: Relay 8A-AC1 (3A-AC3)/250VAC
Out3: Relay 5A-AC1 (2A-AC3)/250VAC
SSR: 8mA/8VDC
DI1
DI2
INPUT
TC
Pt100
PTC-NTC
OUT3
Power supply
OUT2
Out 10 VDC max. 20 mA
4...200 mA passive (2 wires)
Ext.
gen.
4... 20 mA active
0/4...20 mA active
0... 50/60 mV; 0... 1 V; 0/1... 5 V; 0/2... 10 V
OUT1
Note: The complete manual is available, free of charge, at:
www.ascontecnologic.com
2.1 Mounting requirements
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back. Select a mounting location having the following characteristics:
1. It should be easily accessible;
2. There is minimum vibrations and no impact;
3. There are no corrosive gases;
4. There are no water or other fluid (condensation);
5. The ambient temperature is in accordance with the operative temperature (0... 50°C);
6. The relative humidity is in accordance with the instrument specifications (20... 85%).
The instrument can be mounted on panel with a maximum thickness of 15 mm.
When the maximum front protection (IP65) is desired, the optional gasket must be monted.
2.2 Genereal notes about wiring
1. Do not run input wires together with power cables;
2. External components (like zener barriers, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents;
3. When a shielded cable is used, it should be connected at one point only;
4. Pay attention to the line resistance; a high line resistance may cause measurement errors;
5. To avoid electrical shock, connect power at last;
6. For supply connections use No. 16 AWG or larger wires rated for at last 75°C;
7. Use copper conductors only;
8. Before connecting the instrument to the power line, make sure that line voltage is equal to the voltage shown on the identification label.
9. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
3 - CONFIGURATION PROCEDURE
3.1 How to enter the configuration mode
1. Push the button for more than 3 seconds.
The display will show alternately 0 and PASS;
2. Using and/or buttons set the programmed password.
Notes:
a) The factory default password for configuration parameters is 30.
b) The parameter changes are protected by a time out. If no key is pressed for more than 10 seconds the instrument automatically returns back to the Standard display, the new value of the last selected parameter will be lost and the parameter modification procedure closed.
Sometimes can be useful to enter the parameter configuration procedure with no timeout
(e.g. for the first time an instrument is configured). In this case, use a password equal to the previously set password + 1000 digits (e.g.
1000 + 30 [default] = 1030).
It is always possible to manually end the parameter configuration procedure (see the next paragraph).
c) During parameter modification the instrument continues performing the control.
In certain conditions, when a configuration change can produce a heavy bump to the process, it is advisable to temporarily stop the control procedure during the programming procedure (the control output will be OFF).
In this case use a password equal to the previously set password + 2000 digits
(e.g. 2000 + 30 [default] = 2030).
The control procedure will automatically restart when the configuration procedure will be manually closed.
3. Push the button.
If the password is correct the display will show the acronym of the first parameter group preceded by the symbol .
In other words the display will show
The instrument is in configuration mode.
.
3.2 How to exit the configuration mode
Push button for more than 5 seconds. The instrument will come back to the “standard display”.
3.3 Keyboard functions during parameters modification
A short pression allows to exit the current parameter group and select a new parameter group.
A long pression allows to close the configuration parameter procedure (the instrument returns to the “standard display”).
When the display is showing a group, the key allows to enter in the selected group.
When the display is showing a parameter, the key allows you to store the value shown and go to the next parameter within the same group.
Increases the value of the selected parameter.
Decreases the value of the selected parameter.
Note: The group selection is cyclic as well as the selection of the parameters in a group.
3.4 Factory reset - Default parameters loading procedure
Sometimes, e.g. when you reconfigure an instrument previously used for other works or from other people or when you have made too many errors during configuration and you decided to reconfigure the instrument, it is possible to restore the factory configuration.
This action allows you to put the instrument in a defined condition (in the same condition it was at the first Power ON).
The default data are the typical values loaded in the instrument prior to shipping from factory. To load the factory default parameter set, proceed as follows:
1. Press the button for more than 5 seconds;
2. The display will show alternately “PASS” and “0”;
3. Using and buttons, set the value -481;
5. The instrument will turn OFF all LEDs then it will show “dFLt” messages and than it turn ON all
LEDs of the display for 2 seconds and than it will restart as at the first power ON.
The procedure is complete.
4 - OPERATIVE MODES
4.1 Keyboard function when the instrument is in Auto mode
Performs the action programmed by [116] uSrb
( button function during RUN TIME) parameter.
Enters the parameter modification procedures.
Starts the "Direct set point modification" function (see below).
Displays the "Additional information"
(see below).
4.2 Direct set point modification
This function allows to modify rapidly the set point value selected by [79] SPAt or to the set point of the segment group currently in progress. The instrument is showing the "standard display".
1. Push button. The display will show alternately the acronym of the selected set point (e.g. SP2) and its value.
Note: When the programmer is running, the instrument will show the set point of the group currently in use.
2. By and buttons, assign to this parameter the desired value.
3. Do not push any button for more than 5 second or push the button. In both cases the instrument memorize the new value and come back to the "standard display".
Note: If the selected set point has not been promoted to the Operator level, the instrument allows you to see the value but not to modify it.
4.3 Additional information
This instrument is able to show you some additional information that can help you to manage your system.
1. When the instrument is showing the "standard display" push button. The display will show "H" or
"c" followed by a number. This value is the current power output applied to the process. "H" means
Heating action while "c" means Cooling action.
2. Push button again. When the programmer is running the instrument will show the segment currently performed and the Event status as shown below: where the first figure can be "r" for a ramp or
"S" for a soak, the next digit shows the number of the segment (ex. S3 indicates stasis 3) and the two Less Significant Digits show you the status of the two event (LSD is the Event 2).
3. Push button again. When the programmer is running the instrument will show the theoretical remaining time to the end of the program preceded by a P letter:
4. Push button again. When the wattmeter function is running the instrument will show "U" followed by the measured energy.
Note: The energy calculation will be in accordance with the [126] Co.tY parameter setting.
5. Push button again. When the "Worked time count" is running the instrument will show "d" for days or "h" for hours followed by the measured time.
6. Push button again. The instrument reurns to the "standard display".
Note: The additional information visualization is subject to a time out of 10 seconds.
5 - ERROR MESSAGES
5.1 Out of Range Signals
The display shows the OVER-RANGE and UNDER-
RANGE conditions with the following indications:
Over-range Under-range
The sensor break will be signalled as an out of range:
Note: When an over-range or an under-range is detected, the alarms operate as in presence of the maximum or the minimum measurable value respectively.
To check the out of span Error condition, proceed as follows:
1. Check the signal source and the connecting line.
2. Make sure that the input signal is in accordance with the instrument configuration. Otherwise, modify the input configuration (see section 3).
3. If no error is detected, send the instrument to your supplier to be checked.
5.2 List of possible errors
ErAT Fast Auto-tune cannot start. The measure value is too close to the set point. Push the button in order to delete the error message.
NoAt Auto-tune not finished within 12 hours.
ErEP Possible problem of the instrument memory.
The message desappears automatically.
If the error continues, send the instrument to the supplier.
6 - GENERAL NOTES
6.1 Proper Use
Every possible use not described in the complete manual (www.ascontecnologic.com) must be considered as a improper use.
This instrument is in compliance with EN 61010-1
"Safety requirements for electrical equipment for measurement, control and laboratory use"; for this reason it coud not be used as a safety equipment.
Ascon Tecnologic S.r.l. and its legal representatives do not assume any responsibility for any damage to people, things or animals deriving from violation, wrong or improper use or in any case not in compliance with the instrument's features.
6.2 Warranty and repairs
This product is under warranty against manufacturing defects or faulty materials that are found within 12 months from delivery date.
The warranty is limited to repairs or to the replacement of the instrument.
The tampering of the instrument or an improper use of the product will bring about the immediate withdrawal of the warranty's effects.
In the event of a faulty instrument, either within the period of warranty, or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company.
The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found, without any fees or charge for Ascon Tecnologic, except in the event of alternative agreements.
Before supplying tension to the instrument, make sure that it is perfectly dry.
WARNING
Whenever a failure or a malfunction of the device may cause dangerous situations for persons, things or animals, please remember that the plant must be equipped with additional devices which will guarantee safety.
4 - PARAMETERS TABLES
]
InP group (parameters relative to the inputs)
1
2
5
6
3
4
7
8
9 no.
10
11
Par.
HcFG
SEnS
SSc
FSc unit
FiL inE oPE diF1 diF2
Description
It shows the current hardware
Range
TC/RTD, TC/PTC, Current, Voltage
Default Vis. Promo.
According to the HW
Not displayed
Sensor selection (according to the HW)
TC, Pt100 input
TC, PTC, NTC input
I input
V input
Initial scale readout
Final scale readout
Engineering unit
Digital filter on the measured value
Selection of the Sensor Out of Range type that will enable the safety output value
Safety output value
Digital input 1 function
Digital input 2 function
J, crAL, S , r, t, ir.J, ir.cA, Pt1, 0... 50 (mV),
0... 60 (mV), 12... 60 (mV)
J, crAL, S , r, t, Ir.J, Ir.cA, Ptc, ntc, 0... 50 (mV),
0... 60 (mV), 12... 60 (mV)
J
Ptc
0... 20 (mA), 4... 20 (mA) 4.20
0... 5(V), 1... 5(V), 0... 10(V), 2... 10(V), 0... 1 (V) 0.10
0... 3
From -1999 to FSC (E.U.)
From SSc to 9999 (E.U.)
°C or °F
From 0 (OFF)... 20.0 (s)
0
-1999
9999
0 = °C
1.0
or = ur =
Over-range
Under-range our = Over and Under
-100... 100 (%)
14 =
15 =
16 =
17 =
18 =
19 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
13 = oFF = No function
1 = Alarm Reset
2 =
3 =
4 =
5 =
Alarm acknowledge (ACK)
Hold of the measured value
Stand by mode
HEAt with SP1 and CooL with “SP2”
Timer run/hold/reset [transition]
Timer run [transition]
Timer reset [transition]
Timer run/hold [Status]
Program run
Program reset
Program hold
Program run/hold
20 =
Program run/reset
Instrument in Manual mode
Sequential set point selection
SP1/SP2 selection
Set point Binary selection
Digital inputs in parallel to the
UP and DOWN keys
Timer RUN/Reset
See diF1 our
0 nonE nonE
A-4
A-5
A-6
A-7
A-8
C-0
C-0
C-0
A-13
A-14
]
Out Group (parameters relative to the outputs)
no.
Par.
12
13 o1F
Description
Out 1 function o1AL Alarms linked up with out 1
Range
NonE = Output not used
H.rEG = Heating output c.rEG = Cooling output
AL = Alarm output t.out = Timer output t.HoF = Timer out -OFF in hold
P.End = Program end indicator
P.HLd = Program hold indicator
P. uit = Program wait indicator
P.run = Program run indicator
P.Et1 = Program Event 1
P.Et2 = Program Event 2 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure indicator bo.PF = Out-of-range, burn out and Power failure indicator diF.1 = DO repeats the DI1 status diF.2 = DO repeats the DI2 status
St.bY = Stand by status indicator on = Out 1 ever ON
0... 31
+1 =
+2 =
Alarm 1
Alarm 2
+4 =
+8 =
Alarm 3
Loop break alarm
+16 = Sensor Break (burn out)
Default
H.reg
AL1
Vis. Promo.
A-16
A-17
no.
Par.
14
19
20
21
22
23
15
16
17
18 o1Ac Out 1 action
Description o2F Out 2 function o2AL Alarms linked up with the out 2 o2Ac Out 2 action o3F Out 3 function o3AL Alarms linked up with the out 3 o3Ac Out 3 action o4F Out 4 function o4AL Alarms linked up with the out 4 o4Ac Out 4 action
Range dir = Direct action rEU = Reverse action dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
See: 12 - o1F: Out1 functions
See: 13 - o1AL: Alarms linked up with out 1
See: 14 - o1Ac: Out 1 action
See: 12 - o1F: Out1 functions
See: 13 - o1AL: Alarms linked up with out 1
See: 14 - o1Ac: Out 1 action
See: 12 - o1F: Out1 functions
See: 13 - o1AL: Alarms linked up with out 1
See: 14 - o1Ac: Out 1 action
]
AL1 Group (parameters relative to AL1 - alarm 1)
dir
Default Vis. Promo.
C-0
AL A-19
+1 = AL1 A-20 dir C-0
AL A-22
+2 = AL2 A-23 dir C-0
AL A-24
+3 = AL3 A-25 dir C-0 no.
24
25
26
27
28
29
30
31
Par.
AL1t
Ab1
Alarm 1 type
Description
Alarm 1 function
Range nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAb = Absolute band alarm
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdE = Relative band alarm
0... 15
+1 =
+2 =
+4 =
+8 =
Not active at power ON
Latched alarm (manual reset)
Acknowledgeable alarm
Relative alarm not active at set point change
Default
LoAb
Vis. Promo.
A-47
0 C-0
AL1L
AL1H
For High and low alarms, it is the low limit of the AL1 threshold
For band alarm, it is low alarm threshold
For High and low alarms, it is the high limit of the AL1 threshold
For band alarm, it is high alarm threshold
AL1 AL1 threshold
HAL1 AL1 hysteresis
AL1d AL1 delay
AL1o
Alarm 1 enabling during Stand-by mode and out of range conditions
From -1999 to AL1H (E.U.)
From AL1L to 9999 (E.U.)
-1999
9999
From AL1L to AL1H (E.U.)
1... 9999 (E.U.)
From 0 (OFF) to 9999 (s)
0 =
1 =
2 =
3 =
Alarm 1 disabled during Stand-by and out of range
Alarm 1 enabled in stand by mode
Alarm 1 enabled in out of range condition
Alarm 1 enabled in stand by mode and in overrange condition
0
0
1 oFF
A-48
A-49
A-50
A-51
C-0
C-0
]
AL2 Group (parameters relative to AL2 - alarm 2)
36
37
38 no.
Par.
32
33
34
35
39
AL2t
Ab2
AL2L
Alarm 2 type
Alarm 2 function
Description
For High and low alarms, it is the low limit of the AL2 threshold
For band alarm, it is low alarm threshold
AL2H
AL2
For High and low alarms, it is the high limit of the AL2 threshold
For band alarm, it is high alarm threshold
AL2 threshold
HAL2 AL2hysteresis
AL2d AL2 delay
AL2o
Alarm 2 enabling during Stand-by mode and out of range conditions
Range
See: 24 - Ab1t: Alarm 1 Type
See: 25 - AL1f: Alarm 1 function
See: 26 - AL1L
See: 27 - AL1H
See: 28 - AL1: Alarm 1 threshold
See: 29 - HAL1: Alarm 1 hysteresis
See: 30 - AL1d: AL1 delay
See: 31 - AL1o: Alarm 1 enabling during Stand-by mode and out of range conditions
]
AL3 Group (parameters relative to AL3 - alarm 3)
Default Vis. Promo.
HiAb A-54
0 C-0
-1999
9999
0
1 oFF
0
A-56
A-57
A-58
A-59
C-0
C-0
Default Vis. Promo.
nonE C-0
0 C-0
44
45
46 no.
Par.
40
41
42
43
47
AL3t
Ab3
AL3L
AL3H
Alarm 3 type
Alarm 3 function
Description
For High and low alarms, it is the low limit of the AL3 threshold
For band alarm, it is low alarm threshold
For High and low alarms, it is the high limit of the AL3 threshold
For band alarm, it is high alarm threshold
See: 27 - AL1H
AL3 AL3 threshold
HAL3 AL3hysteresis
AL3d AL3 delay
AL3o
Alarm 3 enabling during Stand-by mode and out of range conditions
Range
See: 24 - Ab1t: Alarm 1 Type
See: 25 - AL1f: Alarm 1 function
See: 26 - AL1L
See: 28 - AL1: Alarm 1 threshold
See: 29 - HAL1: Alarm 1 hysteresis
See: 30 - AL1d: AL1 delay
See: 31 - AL1o: Alarm 1 enabling during Stand-by mode and out of range conditions
]
LBA Group
48
49
50 no.
Par.
Description
LbAt LBA time
LbSt Δ measure for LBA during Soft start
LbAS Δ measure for LBA
51 LbcA Condition for LBA enabling
Range
From 0 (oFF) to 9999 (s)
From 0 (oFF) to 9999 (E.U.)
1... 9999 (E.U.) uP = Active when Pout = 100% dn = Active when Pout = -100% both = Active in both cases
]
rEG Group
-1999
9999
0
1 oFF
0
Default Vis. Promo.
oFF
10
20
C-0
C-0
C-0 both
C-0
C-0
C-0
C-0
C-0
C-0
C-0
66
67
68
59
60
61
56
57
58 no.
Par.
52
53
54
55
62
63
64
65
69
70
71
Description Range cont Control type
Auto Autotuning selection
Aut.r
SELF
Manual start of the Autotuning
Self tuning enabling
-3 =
-2 =
-1 =
0 =
1 =
2 =
3 =
4 =
Pid = PID (heat and/or)
On.FA = ON/OFF asymmetric hysteresis
On.FS = ON/OFF symmetric hysteresis nr = Heat/Cool ON/OFF control with neutral zone
-4 = Oscillating auto-tune with automatic restart at power ON and after all point change
Oscillating auto-tune with manual start
Oscillating tune with automatic start at first power ON only
Oscillating autotune with auto restart at each power ON
Not used
Fast auto tuning with auto restart at each power ON
Fast auto-tune with auto start at first power ON only
FAST auto-tune with manual start
FAST auto-tune with automatic restart at power ON and after a set point change oFF = Not active on = Active
YES = The instrument do not perform the self-tuning no = The instrument is performing the self-tuning
HSEt Hysteresis of the ON/OFF control 0... 9999 (E.U.) cPdt Time for compressor protection From 0 (oFF) to 9999 (s)
Pb Proportional band 0... 9999 (E.U.) int dEr
Integral time
Derivative time
Fuoc Fuzzy overshoot control
H.Act
tcrH
PrAt
Heating output actuator
Heating output cycle time
Power ratio between heating and cooling action
From 0 (oFF) to 9999 (s)
From 0 (oFF) to 9999 (s)
0.00... 2.00
SSr = SSR rELY = Relay
SLou = Slow actuators
0.1... 130.0 (s)
0.01... 99.99
c.Act
Cooling output actuator tcrc Cooling output cycle time rS
SSr = SSR rELY = Relay
SLou = Slow actuators
0.1... 130.0 (s)
Manual reset (Integral pre-load) -100.0... +100.0 (%) od
St.P
SSt
Delay at power ON
Maximum power output used during soft start
Soft start time
From 0.00 (oFF) to 99.59 (hh.mm)
-100... 100 (%)
From 0.00 (oFF) to 8.00 (inF)(hh.mm)
SStH Threshold for soft start disabling -1999... +9999 (E.U.)
]
SP Group
no.
Par.
72
73
74
75
76
77
78
79
Description nSP Number of used set points
SPLL Minimum set point value
SPHL Maximum set point value
SP 1 Set point 1
SP 2 Set point 2
SP 3 Set point 3
SP 4 Set point 4
SPAt Selection of the active set point
1... 4
From -1999 to SPHL
From SPLL to 9999
From SPLL to SPLH
From SPLL to SPLH
From SPLL to SPLH
From SPLL to SPLH
From 1 (SP 1) to nSP
Range
2
Default Vis. Promo.
Pid oFF no
1 oFF
50
200
50
0.50
SSr
20.0
1.00
SSr
20.0
0.0
oFF
0 oFF
9999
A-25
C-0
A-26
C-0
C-0
C-0
C-0
C-0
A-27
C-0
A-28
A-29
A-30
A-31
A-32
C-0
A-34
A-35
C-0
C-0
Default Vis. Promo.
0
1
1
-1999
0
0
9999
0
A-38
A-39
A-40
O-41
O-42
O-43
O-44
O-45 no.
Par.
80
81
82
83
Description Range Default Vis. Promo.
SP.rt
Remote set point type
SP.Lr Local/remote set point selection
RSP = The value coming from serial link is used as remote set point trin = The value will be added to the local set point selected by SPAt and the sum becomes the operative set point
PErc = The value will be scaled on the input range and this value will be used as remote set point
Loc = local rEn = remote trin
Loc
SP.u
Rate of rise for POSITIVE set point change 0.01... 100.00 (inF) Eng. units per minute
SP.d
Rate of rise for NEGATIVE set point change 0.01...100.00 (inF) Eng. units per minute inF inF
C-0
C-0
C-0
C-0
]
Tin Group
no.
Par.
84 tr.F
85 tr.u
Description
Independent timer function
Timer unit
86 tr.t1
Time 1
87 tr.t2
Time 2
88 tr.St
Timer status
Range
NonE = Timer not used i.d.A = Delayed start timer i.uP.d = Delayed start at power up i.d.d = Feed-through timer i.P.L = Asymmetrical oscillator, start OFF i.L.P = Asymmetrical oscillator, start ON hh.nn = Hours and minutes nn.SS = Minutes and seconds
SSS.d = Second and tenth of seconds
When tr.u < 20: 0.01... 99.59
When tr.u = 200: 0.1... 995.9
When tr.u < 2: 00.00 (oFF)... 99.59 (inF)
When tr.u = 2: 000.0 (oFF)... 995.9 (inF) rES = Timer reset run = Timer run
HoLd = Timer hold
Default Vis. Promo.
nonE nn.SS
1.00
1.00
rES
A-62
A-63
A-64
A-65
C-0
]
Prg Group
no.
Par.
Description Range Default Vis. Promo.
89
90
91
Pr.F
Pr.u
Pr.E
Program action at power ON
Engineering unit of the soak
Instrument behaviour at the end of the program execution nonE = Programmer not used
S.uP.d = Start at power ON with a first step in stand-by
S.uP.S = Start at power ON u.diG = Start at Run command detection only u.dG.d = Start at Run command with a first step in stand-by hh.nn = Hours and minutes nn.SS = Minutes and seconds nonE hh.nn
cnt = Continue
SPAt = Go to the set point selected by SPAt
St.by = Go to stand-by mode
SPAt
92 Pr.Et
Time of the end program indication From 0.00 (oFF) to100.00 (inF) minutes and seconds
93 Pr.S1
Set point of the first soak
94 Pr.G1
Gradient of the first ramp
From SPLL to SPHL oFF
0
0.1... 1000.0 (inF= Step transfer) Engineering Unit/minute inF
95 Pr.t1
Time of the first soak
96 Pr.b1
Wait band of the first soak
97 Pr.E1
Events of the first group
98 Pr.S2
Set point of the second soak
99 Pr.G2
Gradient of the second ramp
100 Pr.t2
Time of the second soak
101 Pr.b2
Wait band of the second soak
102 Pr.E2
Events of the second group
0.00... 99.59
From 0 (oFF) to 9999 (E.U.)
00.00... 11.11
OFF or from SPLL to SPHL
0.00... 99.59
From 0 (oFF) to 9999 (E.U.)
00.00... 11.11
0.10
oFF
00.00
0
0.1... 1000.0 (inF= Step transfer) Engineering Unit/minute inF
0.10
oFF
00.00
103 Pr.S3
Set point of the third soak
104 Pr.G3
Gradient of the third ramp
105 Pr.t3
Time of the third soak
106 Pr.b3
Wait band of the third soak
107 Pr.E3
Events of the third group
108 Pr.S4
Set point of the fourth soak
109 Pr.G4
Gradient of the fourth ramp
110 Pr.t4
Time of the fourth soak
111 Pr.b4
Wait band of the fourth soak
112 Pr.E4
Events of the fourth group
113 Pr.St
Program status
OFF or from SPLL to SPHL 0
0.1... 1000.0 (inF= Step transfer) Engineering Unit/minute inF
0.00... 99.59
From 0 (oFF) to 9999 (E.U.)
00.00... 11.11
0.10
oFF
00.00
OFF or from SPLL to SPHL 0
0.1... 1000.0 (inF= Step transfer) Engineering Unit/minute inF
0.00... 99.59
From 0 (oFF) 9999 (E.U.)
0.10
oFF
00.00... 11.11
rES = Program reset run = Program start
HoLd = Program hold
00.00
0
A-67
A-68
A-71
C-0
A-78
A-79
A-80
A-81
C-0
A-83
A-84
A-85
A-86
C-0
A-72
A-73
A-74
A-75
A-76
C-0
A-88
A-89
A-90
A-91
C-0
]
PAN Group
Default Vis. Promo.
20
30
A-93
C-0 no.
Par.
Description
114 PAS2 Password level 2
115 PAS3 Password level 3
116 uSrb
117 diSP
118 AdE
119 FiLd
button function during run time
Display management
Bargraph deviation
Filter on the displayed value
120 dSPu Status of the instrument at power up
121 oPr.E
122 oPEr
Operative mode enabling
Operative mode selection
Range
From 0 (oFF) to 999
1... 999 nonE = Not used tunE = Starts auto tuning functions oPLo = Manual mode (OPLO)
AAc = Alarm reset
ASi = Alarm acknowledge chSP = Sequential set point selection
St.by = Stand-by mode
Str.t = Run/hold/reset timer
P.run = Program start
P.rES = program reset
P.r.H.r = Run/hold/reset program nonE = Standard display
Pou = Power output
SPF = Final set point
Spo = Operative set point
AL1 = Alarm 1 threshold
AL2 = Alarm 2 threshold
AL3 = Alarm 3 threshold
Pr.tu = Program time up
Pr.td = Program time down
P.t.tu = Program total time up
P.t.td = Program total time down ti.uP = Timer time up ti.du = Timer time down
Perc = Percent of the power output during soft start
From 0 (oFF) to 9999
From 0.0 (oFF) to 20.0
AS.Pr = Starts as it was prior to the power down
Auto = Starts in Auto mode oP.0 = Starts in manual mode with a power output =0
St.bY = Starts in stand-by mode
ALL = All
Au.oP = Autp or manual (oPLo) only
Au.Sb = Auto and Stand by only
Auto = Automatic oPLo = Manual
St.by = Stand-by
]
SER Group
nonE
2 oFF
AS.Pr
ALL
Auto
A-94
A-95
A-96
C-0
C-0
C-0
O-1 no.
Par.
123 Add
124 bAud Baud rate
125 trSP
Address
Description
Selection of the value to be retransmitted (Master)
Range
From 0 (oFF) to 254
1200
2400
9600
(bit/s)
(bit/s)
(bit/s)
19.2 (kbit/s)
38.4 (kbit/s) nonE = Not used rSP = Operative set point
PErc = Current power output (%)
]
con Group(Wattmeter)
no.
Par.
Description Range
126 co.ty
Measurement type o =
1 =
2 =
3 =
4 =
5 =
OFF = Not used
Instantaneous (kW)
Power consumption (kW/h)
Energy used during program execution
Total worked days with threshold
Total worked hours with threshold
127 UoLt
128 cur
Nominal load voltage
Nominal load current
1... 999 (Volt)
1... 999 (A)
129 h.Job
Threshold of the worked hours/days From 0(oFF) to 9999
]
cal Group (user calibration)
no.
Par.
Description
130 A.L.P
Adjust low Point
131 A.L.o
Adjust low Offset
132 A.H.P
Adjust High Point
133 A.H.o
Adjust High Offset
Range
From -1999 to AH.P-10 (E.U.)
-300... +300 (E.U.)
From A.L.P +10 to 9999 (E.U.)
-300... +300 (E.U.)
1
Default Vis. Promo.
C-0
9600 nonE nonE
230
10 oFF
C-0
C-0
Default Vis. Promo.
A-97
A-98
A-99
A-100
Default Vis. Promo.
0
0
9999
0
A-9
A-10
A-11
A-12