Installation, Operation, and Maintenance
IntelliPak™
Commercial Single-Zone Rooftop Air Conditioners with CV, VAV, or SZVAV Controls
“A” and later Design Sequence
SAHL
*20, *25, *30, *40, *50, *55, *60, *70, *75
SEHL, SFHL, SLHL, SSHL, SXHL
*20, *25, *30, *40, *50, *55, *60, *70, *75,
*24, *29, *36, *48, *59, *73, *80, *89
SXHK, SEHK, SFHK, SLHK, SSHK
*90, *11, *12, *13
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
October 2011
RT-SVX36G-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices.
Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION:
Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTION s
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
© 2011 Trane All rights reserved RT-SVX36G-EN
Warnings, Cautions and Notices
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
• Before installing/servicing this unit, technicians MUST put on all Personal Protective
Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
• If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment
(PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Risk of Roof Collapsing!
Confirm with a structural engineer that the roof structure is strong enough to support the
combined weight of the roofcurb and the unit. Refer to “Unit Dimensions & Weight
Information,” p. 32 for typical unit and curb weights. Failure to ensure proper structural roof
support could cause the roof to collapse, which could result in death or serious injury and property damage.
Unit Nameplate
One Mylar unit nameplate is located on the outside upper left corner of the control panel door. It includes the unit model number, serial number, electrical characteristics, weight, refrigerant charge, as well as other pertinent unit data. A small metal nameplate with the Model Number, Serial
Number, and Unit Weight is located just above the Mylar nameplate, and a third nameplate is located on the inside of the control panel door.
Compressor Nameplate
The Nameplate for the Scroll Compressor is located on the compressor lower housing.
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.
Precautionary Measures
• Avoid breathing fiberglass dust.
• Use a NIOSH approved dust/mist respirator.
RT-SVX36G-EN 3
Warnings, Cautions and Notices
• Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
• Wash clothes separately from other clothing: rinse washer thoroughly.
• Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact - Wash affected areas gently with soap and warm water after handling.
Overview of Manual
This booklet describes proper installation, start-up, operation, and maintenance procedures for 20 through 130 Ton rooftop air conditioners designed for Constant Volume (CV) and Variable Air
Volume (VAV) applications. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
These units are equipped with electronic Unit Control Modules (UCM) which provides operating functions that are significantly different than conventional units. Refer to the “Start-Up” and “Test
Mode” procedures within this Installation, Operation, & Maintenance manual and the latest edition of the appropriate programming manual for CV or VAV applications before attempting to operate or service this equipment.
Note: The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians.
Note: One copy of the appropriate service literature ships inside the control panel of each unit.
It is important that periodic maintenance be performed to help assure trouble free operation.
Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Unit Inspection
As soon as the unit arrives at the job site
• Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
• Verify that the power supply complies with the unit nameplate specifications.
• Verify that the power supply complies with the electric heater specifications on the unit nameplate.
• Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
• Check for material shortages. Refer to the Component Layout and Ship with Location illustration.
• If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing.
• Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
4 RT-SVX36G-EN
Storage
Warnings, Cautions and Notices
WARNING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
• If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
• Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible.
The owner must provide reasonable evidence that the damage did not occur after delivery.
• Remove the protective plastic coverings that shipped over the compressors.
Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if: a. the unit is stored before it is installed; or, b. the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit's heater for temporary heat without first completing the startup procedure detailed under “Starting the Unit”.
Trane will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit's electrical and/or mechanical components.
RT-SVX36G-EN 5
6
Table of Contents
Model Number Descriptions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
General Information
Commonly Used Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Rooftop Module (RTM - 1U48 Standard on all units) . . . . . . . . . . . . . . . . 13
Modulating Dehumidification Module MDM . . . . . . . . . . . . . . . . . . . . . . 15
Ventilation Override Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Interprocessor Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LonTalk/BACnet Communication Interface Module . . . . . . . . . . . . . . . . . 15
Exhaust/Comparative Enthalpy Module . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Generic Building Automation System Module . . . . . . . . . . . . . . . . . . . . . 17
Input Devices & System Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Constant Volume (CV), Single Zone Variable Air Volume (SZVAV) & Variable
Air Volume (VAV) Sensors and Controls
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Constant Volume (CV) Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Single Zone Variable Air Volume (SZVAV) Only
. . . . . . . . . . . . . . . . . . . . . . . 23
Constant Volume (CV), Single Zone Variable Air Volume (SZVAV), & Variable
Air Volume (VAV) Units
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Single Zone Variable Air Volume (VAV) Units
. . . . . . . . . . . . . . . . . . . . . . . . . 26
Space Temperature Averaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Installation
If a Trane Curb Accessory Kit is Not Used: . . . . . . . . . . . . . . . . . . . . . . . . 45
General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Main Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Requirements for Electric Heat Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Requirements for Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Requirements for Hot Water Heat (SLH_) . . . . . . . . . . . . . . . . . . . . . . . . . 49
Requirements for Steam Heat (SSH_) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
RT-SVX36G-EN
RT-SVX36G-EN
Requirements for Modulating Reheat Dehumidification . . . . . . . . . . . . . 50
Condensate Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
O/A Sensor & Tubing Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Remove Evaporative Condenser Fan Shipping Brackets . . . . . . . . . . . . . 54
Evaporative Condenser Make-up Water and Drain Line Installation . . . 55
Hot Water Heat Units (SLH_) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Disconnect Switch External Handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Power Wire Sizing and Protection Device Equations . . . . . . . . . . . . . . . . 74
Controls using DC Analog Input/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 77
Constant Volume System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Variable Air Volume and Constant Volume System Controls . . . . . . . . . 77
Installation Checklist
20-130 Ton, Air-Cooled and Evaporative Condensing . . . . . . . . . . . . . . . 91
Unit Start Up
Cooling Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Modulating Gas Sequence of Operation—Full and Limited Modulating Gas
Wet Heat Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Voltage Supply and Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . 106
Verifying Proper Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
System Airflow Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Exhaust Airflow Measurement (Optional with all Units) . . . . . . . . . . . . 116
Return Plenum Pressure Control (Units equipped with Return Fan) . . 118
Economizer Damper Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Compressor Start-Up (All Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Compressor Operational Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Evaporative Condenser Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Thermostatic Expansion Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Gas Furnace Start-Up (Constant Volume & Variable Air Volume Systems)
156
Full Modulating Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
7
8
Limited Modulating Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Startup Checklists
24-89 Ton — Evaporative Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Maintenance
Scroll Compressor Replacements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
VFD Programming Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Unit Wiring Diagram Numbers
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Warranty
Commercial Equipment Rated 20 Tons and Larger and Related Accessories
197
Index
RT-SVX36G-EN
Model Number Descriptions
S A H L * 5 0 4 0 A 6 8 A 6 B D 8 0 0 1 0 0 W 0 0 G 0 B 0 0 0 R 0 0 0 8 0 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
DIGIT 1 - UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 - UNIT FUNCTION
A = DX Cooling, No Heat
E = DX Cooling, Electric Heat
F = DX Cooling, Natural Gas Heat
L = DX Cooling, Hot Water Heat
S = DX Cooling, Steam Heat
X = DX Cooling, No Heat, Extended
Casing
DIGIT 3 - UNIT AIRFLOW
H = Single Zone
DIGIT 4 - DEVELOPMENT
SEQUENCE
L = Sixth
DIGITS 5,6,7 - NOMINAL
CAPACITY
*20 = 20 Tons Air-Cooled
*25 = 25 Tons Air-Cooled
*30 = 30 Tons Air-Cooled
*40 = 40 Tons Air-Cooled
*50 = 50 Tons Air-Cooled
*55 = 55 Tons Air-Cooled
*60 = 60 Tons Air-Cooled
*70 = 70 Tons Air-Cooled
*75 = 75 Tons Air-Cooled
*24 = 24 Tons Evap Condenser
*29 = 29 Tons Evap Condenser
*36 = 36 Tons Evap Condenser
*48 = 48 Tons Evap Condenser
*59 = 59 Tons Evap Condenser
*73 = 73 Tons Evap Condenser
*80 = 80 Tons Evap Condenser
*89 = 89 Tons Evap Condenser
DIGIT 8 - POWER SUPPLY
(See Notes)
4 = 460/60/3 XL E = 200/60/3 XL
5 = 575/60/3 XL F = 230/60/3 XL
Note: SEHL units (units with electric heat) utilizing 208V or 230V require dual power source.
DIGIT 9 - HEATING CAPACITY
Note: When the second digit calls for “F”
(Gas Heat), the following values apply: Additionally, please note G and M available ONLY on 50 Ton models and above.
G = Low Heat-Limited Modulation
H = High Heat-2-Stage
J = High Heat-Limited
L = Low Heat-2-Stage
M = Low Heat- Full Modulation
0 = No Heat
P = High Heat-Full Modulation
When the second digit calls for “E”
(electric heat), the following values apply:
D = 30 kW
H = 50 kW
R = 130 kW
U = 150 kW
L = 70 kW
N = 90 kW
Q = 110 kW
V = 170 kW
W = 190 kW
Note:When the second digit calls for “L”
(Hot Water) or “S” (Steam) Heat, one of the following valve size values must be in Digit 9:
High Heat Coil: 1 = .50", 2 = .75", 3 = 1",
4 = 1.25", 5 = 1.5", 6 = 2".
Low Heat Coil: A = .50", B = .75", C = 1",
D = 1.25", E = 1.5", F = 2".
DIGIT 10 - DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru
Z, or any digit 1 thru 9.
DIGIT 11 - EXHAUST/RETURN
OPTION
0 = None
1 = Barometric
2 = 100% Exhaust 1.5 HP w/Statitrac
3 = 100% Exhaust 3 HP w/Statitrac
4 = 100% Exhaust 5 HP w/Statitrac
5 = 100% Exhaust 7.5 HP w/Statitrac
6 = 100% Exhaust 10 HP w/Statitrac
7 = 100% Exhaust 15 HP w/Statitrac
8 = 100% Exhaust 20 HP w/Statitrac
A = 50% Exhaust 1.5 HP
B = 50% Exhaust 3 HP
C = 50% Exhaust 5 HP
D = 50% Exhaust 7.5 HP
E = 100% Exhaust 1.5 HP w/o Statitrac
(CV Only)
F = 100% Exhaust 3 HP w/o Statitrac
(CV Only)
G = 100% Exhaust 5 HP w/o Statitrac
(CV Only)
H = 100% Exhaust 7.5 HP w/o Statitrac
(CV Only)
J = 100% Exhaust 10 HP w/o Statitrac
(CV Only)
K = 100% Exhaust 15 HP w/o Statitrac
(CV Only)
L = 100% Exhaust 20 HP w/o Statitrac
(CV Only)
9 = 100% Return 3 HP w/Statitrac
M = 100% Return 5 HP w/Statitrac
N = 100% Return 7.5 HP w/Statitrac
P = 100% Return 10 HP w/Statitrac
R = 100% Return 15 HP w/Statitrac
T = 100% Return 20 HP w/Statitrac
U = 100% Return 3 HP w/o Statitrac
(CV Only)
V = 100% Return 5 HP w/o Statitrac
(CV Only)
W = 100% Return 7.5 HP w/o Statitrac
(CV Only)
X = 100% Return 10 HP w/o Statitrac
(CV Only)
Y = 100% Return 15 HP w/o Statitrac
(CV Only)
Z = 100% Return 20 HP w/o Statitrac
(CV Only)
DIGIT 12 - EXHAUST/RETURN
AIR FAN DRIVE
(Exhaust/Return Fan)
0 = None 8 = 800 RPM
4 = 400 RPM
5 = 500 RPM
9 = 900 RPM
A = 1000 RPM
6 = 600 RPM
7 = 700 RPM
B = 1100 RPM
(Return Fan only)
C = 1200 RPM H = 1700 RPM
D = 1300 RPM J = 1800 RPM
E = 1400 RPM K = 1900 RPM
F = 1500 RPM
G = 1600 RPM
DIGIT 13 - FILTER
A = Throwaway
B = Cleanable Wire Mesh
C = High-Efficiency Throwaway
D = Bag With Prefilter
E = Cartridge With Prefilter
F = Throwaway Filter Rack Less Filter
Media
G = Bag Filter Rack Less Filter Media
RT-SVX36G-EN 9
Model Number Descriptions
DIGIT 14 - SUPPLY AIR FAN HP
1 = 3 HP
2 = 5 HP
3 = 7.5 HP
4 = 10 HP
5 = 15 HP
6 = 20 HP
7 = 25 HP
8 = 30 HP
9 = 40 HP
DIGIT 15 - SUPPLY AIR FAN
DRIVE
5 = 500 RPM
6 = 600 RPM
7 = 700 RPM
8 = 800 RPM
9 = 900 RPM
A = 1000 RPM
B = 1100 RPM
C = 1200 RPM
D = 1300 RPM
E = 1400 RPM
F = 1500 RPM
DIGIT 16 - FRESH AIR
A = No Fresh Air
B = 0-25% Manual
DIGIT 17 - SYSTEM CONTROL
1 = CV - Zone Temperature Control
2 = CV - Discharge Temperature Control
4 = CV - Zone Temperature Control
Space Pressure Control w/
Exhaust/Return VFD w/o Bypass
5 = CV - Zone Temperature Control
Space Pressure Control w/
Exhaust/Return VFD and Bypass
6 = VAV Discharge Temperature Control w/ VFD w/o Bypass
7 = VAV Discharge Temperature Control w/ VFD and Bypass
8 = VAV Discharge Temperature Control
Supply and Exhaust/Return Fan w/
VFD w/o Bypass
9 = VAV Discharge Temperature
Control Supply and Exhaust/Return
Fan with VFD and Bypass
A = VAV – Single Zone VAV – w/ VFD w/o Bypass
B = VAV – Single Zone VAV – w/ VFD w/ Bypass
C = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/o Bypass
D = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/ Bypass
DIGIT 18 - ZONE SENSOR
0 = None
A = Dual Setpoint Manual or Auto
Changeover (BAYSENS108*)
B = Dual Setpoint Manual or Auto
Changeover w/ System Function
Lights (BAYSENS110*)
C = Room Sensor w/ Override and
Cancel Buttons (BAYSENS073*)
D = Room Sensor w/ Temperature
Adjustment and Override and
Cancel Buttons (BAYSENS074*)
L = Programmable Zone Sensor w/
System Function Lights for both
CV and VAV (BAYSENS119*)
Note: *Asterisk indicates current model number digit A, B, C, etc. These sensors can be ordered to ship with the unit.
DIGIT 19 - AMBIENT CONTROL
0 = Standard
1 = 0° Fahrenheit
DIGIT 20 - AGENCY APPROVAL
0 = None (cULus Gas Heater, see note)
1 = cULus
Note: Includes cULus classified gas heating section only when second digit of Model No. is a "F."
DIGITS 21 - 38 -
MISCELLANEOUS
21 A = Unit Disconnect Switch
22 B = Hot Gas Bypass
C = Hot Gas Reheat w/out Hot Gas
Bypass
D = Hot Gas Reheat and Hot Gas
Bypass
23 0 = Without Economizer
C = Economizer Control w/
Z = Economizer Control w/
Reference Enthalpy
W = Economizer Control w/Dry Bulb
24 E = Low Leak Fresh Air Dampers
25 F = High Duct Temperature
Thermostat
26 G = High Capacity
27 * = Air-Cooled Aluminum
Condenser Coil
J = Corrosion Protected Condenser
Coil
A = Evap Condenser
B = Evap Condenser w/ Sump
Heater
C = Evap Condenser w/ Dolphin
WaterCare System
D = Evap Condenser w/ Sump
Heater and Dolphin WaterCare
System
E = Evap Condenser w/
Conductivity Controller
F = Evap Condenser w/
Conductivity Controller and
Sump Heater
28 B = GBAS 0-10V
K = GBAS 0-5V
R = Rapid Restart
30 M = Remote Human Interface
31 N = Ventilation Override Module
32 R = Extended Grease Lines
33 T = Access Doors
34 V = Inter-Processor
Communication Bridge
35 M = BACnet Communication
Interface (BCI) Module
Y = Trane Communication Interface
(TCI) Module
7 = Trane LonTalk Communication
Interface (LCI) Module
36 8 = Spring Isolators
37 6 = Factory-Powered 15A GFI
Convenience Outlet/Disconnect
Switch
38 J = Temperature Sensor
Tip: EXAMPLE
Model numbers:
SAHL*5040A68A6BD800100W00
G0B000R000800 describes a unit with the following characteristics:
DX Cooling Only unit w/ no extended casing, 50 ton nominal cooling capacity, 460/60/3 power supply,100 percent exhaust with
Statitrac, 10 HP exhaust fan motor with drive selection No. 8 (800
RPM), throwaway filters, 20 HP supply fan motor with drive selection No. B (1100 RPM), 0-
100% economizer w/ dry bulb control, supply and exhaust VFD w/o bypass, no remote panel, standard ambient control, cULus agency approval. High capacity unit, extended grease lines and spring isolators.
The service digit for each model number contains 38 digits; all 38 digits must be referenced.
10 RT-SVX36G-EN
Model Number Descriptions
S X H K * 1 1 4 0 A H 8 C E C D 8 0 0 1 * * Z * * * * * * * * * * * * * * *
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
DIGIT 1 - UNIT TYPE
S = Self-Contained (Packaged Rooftop)
DIGIT 2 - UNIT FUNCTION
E = DX Cooling, Electric Heat
F = DX Cooling, Natural Gas Heat
L = DX Cooling, Hot Water Heat
S = DX Cooling, Steam Heat
X = DX Cooling, No Heat, Extended
Casing
DIGIT 3 - UNIT AIRFLOW
H = Single Zone
DIGIT 4 - DEVELOPMENT
SEQUENCE
K = R-410A Development Sequence
DIGITS 5,6,7 - NOMINAL
CAPACITY
*90 = 90 Tons Air-Cooled
*11 = 105 Tons Air-Cooled
*12 = 115 Tons Air-Cooled
*13 = 130 Tons Air-Cooled
DIGIT 8 - POWER SUPPLY
(See Notes)
4 = 460/60/3 XL
5 = 575/60/3 XL
DIGIT 9 - HEATING CAPACITY
0 = No Heat
H = High Heat - 2-Stage
J = High Heat - Limited Modulation
P = High Heat - Full Modulation
Note:When the second digit calls for “E”
(electric heat), the following values apply in the ninth digit:
W = 190 kW
Note: When the second digit calls for “L”
(Hot Water) or “S” (Steam) Heat, one of the following valve size values must be in Digit 9:
High Heat Coil: 3 = 1", 4 = 1.25", 5 = 1.5",
6 = 2", 7 = 2.5”.
Low Heat Coil: C = 1", D = 1.25", E = 1.5",
F = 2", G = 2.5”.
DIGIT 10 - DESIGN SEQUENCE
A = First (Factory Assigned)
Note: Sequence may be any letter A thru
Z, or any digit 1 thru 9.
DIGIT 11 - EXHAUST/RETURN
OPTION
0 = None
7 = 100% Exhaust 15 HP w/Statitrac
8 = 100% Exhaust 20 HP w/Statitrac
9 = 100% Exhaust 25 HP w/Statitrac
F = 50% Exhaust 15 HP
H = 100% Exhaust 30 HP w/ Statitrac
J = 100% Exhaust 40 HP w/ Statitrac
K = 100% Exhaust 15 HP w/o Statitrac
(CV Only)
L = 100% Exhaust 20 HP w/o Statitrac
(CV Only)
M = 100% Exhaust 25 HP w/o Statitrac
(CV Only)
N = 100% Exhaust 30 HP w/o Statitrac
(CV Only)
P = 100% Exhaust 40 HP w/o Statitrac
(CV Only)
DIGIT 12 - EXHAUST AIR FAN
DRIVE
(Exhaust Fan)
0 = None
5 = 500 RPM
6 = 600 RPM
7 = 700 RPM
8 = 800 RPM
DIGIT 13 - FILTER
A = Throwaway
C = High-Efficiency Throwaway
D = Bag With Prefilter
E = Cartridge With Prefilter
F = Throwaway Filter Rack Less Filter
Media
G = Bag Filter Rack Less Filter Media
DIGIT 14 - SUPPLY AIR FAN HP
C = 30 HP (2-15 HP)
D = 40 HP (2-20 HP)
E = 50 HP (2-25 HP)
F = 60 HP (2-30 HP)
G = 80 HP (2-40 HP)
DIGIT 15 - SUPPLY AIR FAN
DRIVE
A = 1000 RPM
B = 1100 RPM
C = 1200 RPM
D = 1300 RPM
E = 1400 RPM
F = 1500 RPM
G = 1600 RPM
DIGIT 16 - FRESH AIR
D = 0-100% Economizer (Std.)
DIGIT 17 - SYSTEM CONTROL
1 = CV - Zone Temperature Control
2 = CV - Discharge Temperature Control
4 = CV - Zone Temperature Control
Space Pressure Control w/
Exhaust VFD w/o Bypass
5 = CV - Zone Temperature Control
Space Pressure Control w/
Exhaust VFD and Bypass
6 = VAV Discharge Temperature Control w/ VFD w/o Bypass
7 = VAV Discharge Temperature Control w/ VFD and Bypass
8 = VAV Discharge Temperature Control
Supply and Exhaust Fan w/ VFD w/o Bypass
9 = VAV Discharge Temperature Control
Supply and Exhaust Fan w/ VFD and Bypass
A = VAV – Single Zone VAV – w/ VFD w/o Bypass
B = VAV – Single Zone VAV – w/ VFD w/ Bypass
C = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/o Bypass
D = VAV – Single Zone VAV – Supply and
Exhaust/Return Fan w/ VFD w/ Bypass
DIGIT 18 - ZONE SENSOR
0 = None
A = Dual Setpoint Manual or Auto
Changeover (BAYSENS108*)
B = Dual Setpoint Manual or Auto
Changeover w/ System Function
Lights (BAYSENS110*)
C = Room Sensor w/ Override and
Cancel Buttons (BAYSENS073*)
D = Room Sensor w/ Temperature
Adjustment and Override and
Cancel Buttons (BAYSENS074*)
L = Programmable Zone Sensor w/
System Function Lights for both
CV and VAV (BAYSENS119*)
Note: *Asterisk indicates current model number digit A, B, C, etc. These sensors can be ordered to ship with the unit.
DIGIT 19 - AMBIENT CONTROL
0 = Standard
DIGIT 20 - AGENCY APPROVAL
0 = None (cULus Gas Heater, see note)
1 = cULus
Note: Includes cULus classified gas heating section only when second digit of Model No. is a “F.”
RT-SVX36G-EN 11
Model Number Descriptions
DIGITS 21 - 38 -
MISCELLANEOUS
21 A = Unit Disconnect Switch
22 B = Hot Gas Bypass
23 C = Economizer Control w/
23 Z = Economizer Control w/
Reference Enthalpy
23 W = Economizer Control w/Dry Bulb
24 E = Low Leak Fresh Air Dampers
25 F = High Duct Temperature
Thermostat
26 G = High Capacity Evap. Coil
(90 & 105 Ton)
H = High Cap. Evap. Coil and High
Eff. Cond. Coil (90 Ton)
27 K = Generic B.A.S Module
R = Rapid Restart
29 M = Remote Human Interface
30 N = Ventilation Override Module
31 R = Extended Grease Lines
32 T = Access Doors
33 V = Inter-Processor
Communication Bridge
34 W = BCI with Wireless
Communications Interface
(WCI)
Y = Trane Communication Interface
(TCI) Module
34 M = BACnet Communication
Interface (BCI) Module
34 7 = Trane LonTalk Communication
Interface (LCI) Module
35 6 = Factory-Powered 15A GFI
Convenience Outlet
Tip: EXAMPLE
Model numbers:
SXHK*1140AH8CECD8001**Z describes a unit with the following characteristics:
DX cooling with extended casing, no heat, 105 ton nominal cooling capacity, 460/60/3 power supply,
100 percent exhaust with Statitrac,
30 h.p. exhaust fan motor with drive selection No. 8 - (800 RPM), high-efficiency throwaway filters,
50 hp supply fan motor with 1200
RPM, economizer, w/ reference enthalpy control, Supply and
Exhaust with VFD but no bypass, cULus agency approval.
The service digit for each model number contains 36 digits; all 36 digits must be referenced.
12 RT-SVX36G-EN
General Information
Commonly Used Acronyms
For convenience, a number of acronyms and abbreviations are used throughout this manual. These acronyms are alphabetically listed and defined below.
• AC = Air Cooled Condenser
• BAS = Building automation systems
• BCI = BACnet Communication Interface module
• CFM = Cubic-feet-per-minute
• CKT. = Circuit
• CLV = Cooling valve (reheat only)
• CV = Constant volume
• CW = Clockwise
• CCW = Counterclockwise
• E/A = Exhaust air
• EC = Evaporative Condenser
• ECEM = Exhaust/comparative enthalpy module
• F/A = Fresh air
• GBAS = Generic building automation system
• HGBP = Hot gas bypass
• HGRH = Hot gas reheat
• HI = Human Interface
•
•
•
•
•
•
•
•
•
•
•
•
•
•
MDM = Modulating Dehumidification Module
MPM = Multipurpose module
MWU = Morning warm-up
NSB = Night setback
O/A = Outside air psig = Pounds-per-square-inch, gauge pressure
PTFE = Polytetrafluoroethylene (Teflon®)
• R/A = Return air
• RAH = Return air humidity
• RH = Right-hand
RHP = Reheat pumpout solenoid valve
RHV = Reheat valve
RPM = Revolutions-per-minute
RT = Rooftop unit
RTM = Rooftop module
S/A = Supply air
SCM = Single circuit module
• HVAC = Heating, ventilation and air conditioning
• I/O = Inputs/outputs
• IOM = Installation/operation/ maintenance manual
• IPC = Interprocessor communications
• SZ = Single-zone (unit airflow)
• SZVAV = Single zone variable air volume
• TCI = Tracer communications module
• UCM = Unit control modules
• IPCB = Interprocessor communications bridge • VAV = Variable air volume
• LCI-I = LonTalk Communication Interface for IntelliPak • VCM = Ventilation control module
• LH = Left-hand
• MCHE = Microchannel Coil
• MCM = Multiple compressor module
•
•
•
VOM = Ventilation override module w.c. = Water column
WCI = Wireless Communication Interface
Unit Description
Each Trane commercial, single-zone rooftop air conditioner ships fully assembled and charged with the proper refrigerant quantity from the factory.
An optional roof curb, specifically designed for the S_HL units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Trane Commercial Rooftop Units are controlled by a microelectronic control system that consists of a network of modules and are referred to as Unit Control Modules (UCM). The acronym UCM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/Integral control algorithms perform specific unit functions which provide the best possible comfort level for the customer.
They are mounted in the control panel and are factory wired to their respective internal components. They receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Refer to the following discussion for an explanation of each module function.
Rooftop Module (RTM - 1U48 Standard on all units)
The Rooftop Module (RTM) responds to cooling, heating, and ventilation requests by energizing the proper unit components based on information received from other unit modules, sensors, remote panels, and customer supplied binary inputs. It initiates supply fan, exhaust fan, exhaust damper, return fan, return damper, variable frequency drive output, and economizer operation based on that information.
RT-SVX36G-EN 13
General Information
Table 1.
RTM Resistance Input vs. Setpoint Temperatures
RTM cooling or heating setpoint input used as the source for a ZONE temp setpoint (°F)
65
70
75
80 n/a n/a
40
45
50
55
60
RTM cooling setpoint input used as the source for SUPPLY AIR temp setpoint cooling (°F)
65
70
75
80
85
90
40
45
50
55
60
Resistance (Ohms) Max.
Tolerance 5%
597
500
403
305
208
111
1084
992
899
796
695
Table 2.
RTM Resistance Value vs. System Operating Mode
Resistance applied to RTM MODE input Terminals (Ohms)
Max. Tolerance 5%
2320
4870
7680
10770
13320
16130
19480
27930
Constant Volume Units
Fan Mode
Auto
Auto
Auto
On
On
On
Auto
On
System Mode
Off
Cool
Auto
Off
Cool
Auto
Heat
Heat
Compressor Modules
(SCM & MCM - 1U49 standard on all units)
The compressor modules, (Single Circuit & Multiple Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the compressor operation through feedback information it receives from various protection devices.
Human Interface Module
(HI - 1U65 standard on all units)
The Human Interface module enables the operator to adjust the operating parameters for the unit using it's 16 key keypad. The 2 line, 40 character LCD screen provides status information for the various unit functions as well as menus for the operator to set or modify the operating parameters.
Heat Module
(1U50 used on heating units)
The Heat module, upon receiving a request for Heating, energizes the appropriate heating stages or strokes the Modulating Heating valve as required.
14 RT-SVX36G-EN
General Information
Modulating Dehumidification Module MDM
(Optional 1U107 - used with Dehumidification Control)
The MDM supports specific control inputs and outputs for Modulating Dehumidification control including Modulating Reheat and Cooling valve control as well as the Reheat Pumpout Relay output.The Modulating Dehumidification control Algorithm provides control requests to the MDM to accomplish proper Dehumidification control.
Ventilation Override Module
(VOM - Optional 1U51)
Important:
The ventilation override system should not be used to signal the presence of smoke caused by a fire as it is not intended nor designed to do so.
The Ventilation Override module initiates specified functions such as; space pressurization, exhaust, purge, purge with duct pressure control, and unit off when any one of the five (5) binary inputs to the module are activated. The compressors and condenser fans are disabled during the ventilation operation. If more than one ventilation sequence is activated, the one with the highest priority is initiated.
Interprocessor Communications Board
(IPCB - Optional 1U55 used with the Optional Remote Human Interface)
The Interprocessor Communication Board expands communications from the rooftop unit UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2 “Off”, Switch 3 “On”.
LonTalk/BACnet Communication Interface Module
(LCI/BCI - Optional 1U54/1U104 - used on units with Trane ICSTM or 3rd party
Building Automation Systems)
The LonTalk or BACnet Communication Interface modules expand communications from the unit
UCM network to a Trane Tracer Summit or a 3rd party building automation system and allow external setpoint and configuration adjustment and monitoring of status and diagnostics.
Exhaust/Comparative Enthalpy Module
(ECEM - Optional 1U52 used on units with Statitrac and/or comparative enthalpy options)
The Exhaust/Comparative Enthalpy module receives information from the return air humidity sensor, the outside air humidity sensor, and the return air temperature sensor to utilize the lowest possible humidity level when considering economizer operation. In addition, it receives space pressure information which is used to maintain the space pressure to within the setpoint control band. Refer to
Figure 1, p. 16 for the Humidity vs. Voltage input values.
RT-SVX36G-EN 15
General Information
Figure 1.
Humidity vs. Voltage
Ventilation Control Module
VCM
The Ventilation Control Module (VCM) is located in the filter section of the unit and is linked to the unit's UCM network. Using a “velocity pressure” sensing ring located in the fresh air section, allows the VCM to monitor and control the quantity of fresh air entering the unit to a minimum airflow setpoint.
An optional temperature sensor can be connected to the VCM which enables it to control a field installed fresh air preheater.
An optional CO
2
sensor can be connected to the VCM to control CO
2
reset. The reset function adjust the minimum CFM upward as the CO
2
concentrations increase. The maximum effective (reset) setpoint value for fresh air entering the unit is limited to the systems operating CFM. The following table lists the Minimum Outside Air CFM vs. Input Voltage.
Table 3.
Minimum Outside Air Setpoint w/VCM Module and Traq Sensing
Unit (AC/EC)
20 & 25, 24 & 29 Ton
30/36 Ton
40/48 Ton
50/59, 55 Ton
60-75, 73-89 Ton
90-130 Ton
Input Volts
0.5-4.5 VDC
0.5-4.5 VDC
0.5-4.5 VDC
0.5-4.5 VDC
0.5-4.5 VDC
0.5-4.5 VDC
CFM
0-14000
0-17000
0-22000
0-28000
0-33000
0-46000
The velocity pressure transducer/solenoid assembly is illustrated below. Refer to the “Traq Sensor
Sequence of Operation” section for VCM operation.
16 RT-SVX36G-EN
Figure 2.
Velocity Pressure Transducer/Solenoid Assembly
General Information
Generic Building Automation System Module
(GBAS - Optional 1U51 used with non-Trane building control systems; 0-5 or
0-10 VDC)
The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the rooftop unit and accepts external setpoints in form of analog inputs for cooling, heating, supply air pressure, and a binary Input for demand limit. Refer to the
“Field Installed Control Wiring” section for the input wiring to the GBAS module and the various desired setpoints with the corresponding DC voltage inputs for both VAV and CV applications.
Phase Monitor (1U3)
Continuously monitors line voltage to protect against phase, loss, imbalance and reversal. If a fault is found with the supply voltage a LED on the phase monitor will indicate a fault and a unit External
Auto Stop is activated through the controls.
Multipurpose Module
MPM (1U105)
The Multipurpose Module (MPM) receives information from the Return Plenum Pressure sensor and provides for Return Fan control to maintain this pressure to the Active Return Plenum Pressure
Setpoint and Deadband. The liquid line pressure sensor inputs for the refrigeration circuits are received through the MPM in support of head pressure control on Evaporative condenser units.
Input Devices & System Functions
The descriptions of the following basic Input Devices used within the UCM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit's electrical schematic for the specific module connections.
RT-SVX36G-EN 17
General Information
Constant Volume (CV), Single Zone Variable Air Volume (SZVAV) &
Variable Air Volume (VAV) Sensors and Controls
Supply Air Temperature Sensor (3RT9)
This an analog input device monitors the supply air temperature for; supply air temperature control
(used with discharge temperature control), supply air temperature reset (used with discharge temperature control), supply air temperature low limiting (used with discharge temperature control), supply air tempering. It is mounted in the supply air discharge section of the unit and is connected to the RTM (1U48).
Return Air Temperature Sensor (3RT6)
This analog input device is used with a return humidity sensor when the comparative enthalpy option is ordered. It monitors the return air temperature and compares it to the outdoor temperature to establish which temperature is best suited to maintain the cooling requirements.
It is mounted in the return air section and is connected to the ECEM (1U52).
Entering Evaporator Temperature Sensor (3RT28 and 3RT29)
This analog input device is used with the Leaving Evaporator Temp sensor to provide Low Charge
Protection of the refrigerant systems. The difference in these two temperatures will be monitored during compressor operation and compressor circuits will be shut down if this difference exceeds a Human Interface selectable setpoint value.
Leaving Evaporator Temperature Sensor (3RT14 and 3RT15)
An analog input device used to monitor the refrigerant temperature inside the evaporator coil to prevent coil freezing. It is attached to the suction line near the evaporator coil and is connected to the MCM. It is factory set for 30°F and has an adjustable range of 25°F to 35°F. The compressors are staged “Off” as necessary to prevent icing. After the last compressor stage has been turned
“Off”, the compressors will be allowed to restart once the evaporator temperature rises 10°F above the “coil frost cutout temperature” and the minimum three minute “Off” time has elapsed.
Filter Switch (3S21)
This binary input device measures the pressure differential across the unit filters. It is mounted in the filter section and is connected to the RTM (1U48). A diagnostic SERVICE signal is sent to the remote panel if the pressure differential across the filters is at least 0.5" w.c. The contacts will automatically open when the pressure differential across the filters decrease to 0.4" w.c. The switch differential can be field adjusted between 0.17" w.c. to 5.0" w.c. ± 0.05" w.c.
Supply and Exhaust/Return Airflow Proving Switches (3S68 and 3S69)
3S68 is a binary input device used to signal the RTM when the supply fan is operating. It is located in the supply fan section of the unit and is connected to the RTM (1U48). During a request for fan operation, if the differential switch is detected to be open for 40 consecutive seconds; compressor operation is turned “Off”, heat operation is turned “Off”, the request for supply fan operation is turned “Off” and locked out, exhaust dampers (if equipped) are “closed”, economizer dampers (if equipped) are “closed”, and a manual reset diagnostic is initiated.
3S69 is a binary input device used on all rooftop units equipped with an exhaust/return fan. It is located in the exhaust/return fan section of the unit and is connected to the RTM (1U48). During a request for fan operation, if the differential switch is detected to be open for 40 consecutive seconds, the economizer is closed to the minimum position setpoint, the request for exhaust/return fan operation is turned “Off” and locked out, and a manual reset diagnostic is initiated. The fan failure lockout can be reset; at the Human Interface located in the unit's control panel, by Tracer, or by cycling the control power to the RTM (1S70 Off/On).
18 RT-SVX36G-EN
RT-SVX36G-EN
General Information
Lead-Lag
Is a selectable mode of operation on 20 thru 130 Ton units within the Human Interface. It alternates the starting between the first compressor of each refrigeration circuit. On 40 - 89 Ton units only the compressor banks will switch, not the order the compressors within a bank, providing the first compressor in each circuit had been activated during the same request for cooling.
Supply and Exhaust/Return Fan Circuit Breakers (with 1CB1 and 1CB2)
The supply fan and exhaust fan motors are protected by circuit breakers 1CB1 and 1CB2 respectively for 208 -230 V applications. They will trip and interrupt the power supply to the motors if the current exceeds the breaker's “must trip” value. For 460 -575 V applications, fan motors will be protected with manual motor protectors. The rooftop module (RTM) will shut all system functions “Off” when an open fan proving switch is detected.
Manual Motor Protectors (380V through 575V Only)
Manual motor protectors will be used as branch circuit protection for compressors and supply fan motors. These devices are capable of providing both overload and short-circuit protection. Before operating, the manual motor protector must be switched with the rotary on/off switch to the “ON” position and the overload setpoint dial must be set to the appropriate rating of the motor.
Important:
In order to avoid nuisance trips, the overload setpoint dial must be adjusted to the following calculated value:
Overload Setting = (Motor FLA)
Overload Setting = (Compressor RLA) x 1.12
Return Plenum Pressure High Limit
The Return Plenum Pressure High Limit Setpoint has a non-adjustable value of 3.5 iwc. When the return plenum pressure exceeds the Return Plenum Pressure High Limit for more than 1 second, a “Return Pressure shutdown” signal is sent, and an automatically resetting diagnostic is set. After the return fan is off, the Return Pressure Shutdown signal is cancelled. The unit will not be allowed to restart within 15 seconds of shutdown. Three consecutive occurrences of the Return Plenum
Pressure exceeding the Return Plenum Pressure Limit will cause a manual reset diagnostic. The occurrence counter will be reset every time the unit goes through a reset, transitions from Stop to
Auto, or transitions into and out of Occupied or Unoccupied control.
Low Pressure Control (LPC)
LPC is accomplished using a binary input device. LP cutouts are located on the suction lines near the scroll compressors. The LPC contacts are designed to close when the suction pressure exceeds
41± 4 psig. If the LP control is open when a compressor is requested to start, none of the compressors on that circuit will be allowed to operate. They are locked out and a manual reset diagnostic is initiated.
The LP cutouts are designed to open if the suction pressure approaches 25± 4 psig. If the LP cutout opens after a compressor has started, all compressors operating on that circuit will be turned off immediately and will remain off for a minimum of three minutes. If the LP cutout trips four consecutive times during the first three minutes of operation, the compressors on that circuit will be locked out and a manual reset diagnostic is initiated.
Saturated Condenser Temperature Sensors (2RT1 and 2RT2)
These analog input devices are mounted inside a temperature well located on a condenser tube bend. They monitor the saturated refrigerant temperature inside the condenser coil and are connected to the SCM/MCM (1U49). As the saturated refrigerant temperature varies due to operating conditions, the condenser fans are cycled “On” or “Off” as required to maintain acceptable operating pressures. For evaporative condensers, this value is determined by the MPM which converts a pressure to a temperature value that is sent to the MCM to be used for head pressure control.
19
General Information
20
Head Pressure Control
This is accomplished using two saturated refrigerant temperature sensors. During a request for compressor operation, when the condensing temperature rises above the “lower limit” of the control band, the Compressor Module (SCM/MCM) starts sequencing condenser fans “On”. If the operating fans can not bring the condensing temperature to within the control band, more fans are turned on.
As the saturated condensing temperature approaches the lower limit of the control band, fans are sequenced “Off”. The minimum “On/Off” time for condenser fan staging is 5.2 seconds. If the system is operating at a given fan stage below 100% for 30 minutes and the saturated condensing temperature is above the “efficiency check point” setting, a fan stage will be added. If the saturated condensing temperature falls below the “efficiency check point” setting, the fan control will remain at the present operating stage. If a fan stage cycles four times within a 10 minute period, the control switches from controlling to the “lower limit” to a temperature equal to the “lower limit” minus the “temporary low limit suppression” setting. It will utilize this new “low limit” temperature for one hour to reduce condenser fan short cycling.
For Evaporative Condensing units, Head pressure is monitored with pressure transducers attached to the Saturated Condensing line and converted to a temperature by the MPM. This temperature is used to control the variable speed fan and control the sump pump. When the temperature rises above the Upper Limit (120F) the Sump Pump is energized. If the Condensing Temperature drops below the Lower Limit (70F) the Sump Pump is de-energized.
High Pressure Controls
High Pressure controls are located on the discharge lines near the scroll compressors. They are designed to open when the discharge pressure approaches 650 ± 10 psig. The controls reset automatically when the discharge pressure decreases to approximately 550 ± 10 psig. However, the compressors on that circuit are locked out and a manual reset diagnostic is initiated after the fourth occurrence of a high pressure condition.
Outdoor Air Humidity Sensor (3U63)
This is an analog input device used on applications with 100% economizer. It monitors the outdoor humidity levels for economizer operation. It is mounted in the fresh air intake section and is connected to the RTM (1U48).
Return Air Humidity Sensor (3U64)
This is an analog input device used on applications with the comparative enthalpy option. It monitors the return air humidity level and compares it to the outdoor humidity level to establish which conditions are best suited to maintain the cooling requirements. It is mounted in the return air section and is connected to the ECEM (1U52).
Space/Duct Humidity Sensor (5U108)
Analog input device used on applications with modulating dehumidification option and/or humidification field installed option. It is used to monitor the humidity level in the space and for comparison with the dehumidification and humidification setpoints to maintain space humidity requirements. It is field mounted in the space and connected to the RTM or ECEM (1TB16).
Low Ambient Control
The low ambient modulating output on the compressor module is functional on all units with or without the low ambient option. When the compressor module has staged up to it's highest stage
(stage 2 or 3 depending on unit size), the modulating output will be at 100% (10 VDC). When the control is at stage 1, the modulating output (0 to 10 VDC) will control the saturated condensing temperature to within the programmable “condensing temperature low ambient control point”.
Status/Annunciator Output
This is an internal function within the RTM (1U48) module that provides;
RT-SVX36G-EN
RT-SVX36G-EN
General Information
a. diagnostic and mode status signals to the remote panel (LEDs) and to the Human Interface.
b. control of the binary Alarm output on the RTM. c. control of the binary outputs on the GBAS module to inform the customer of the operational status and/or diagnostic conditions.
Low Ambient Compressor Lockout
Utilizes an analog input device. When the system is configured for low ambient compressor lockout, the compressors are not allowed to operate if the temperature of the outside air falls below the lockout setpoint. When the temperature rises 5°F above the lockout setpoint, the compressors are allowed to operate. The setpoint for units without the low ambient option is 50°F. For units with the low ambient option, the setpoint is 0°F. The setpoints are adjustable at the Human Interface inside the unit control panel.
Space Pressure Transducer (3U62)
This is an analog input device that modulates the exhaust dampers to keep the space pressure within the building to a customer designated control band. It is mounted in the filter section just above the exhaust damper actuator and is connected to the ECEM (1U52). Field supplied pneumatic tubing must be connected between the space being controlled and the transducer assembly.
Morning Warm-Up - Zone Heat (not SZVAV)
When a system changes from an unoccupied to an occupied mode, or switches from STOPPED to
AUTO, or power is applied to a unit with the MWU option, the heater in the unit or external heat will be brought on if the space temperature is below the MWU setpoint. The heat will remain on until the temperature reaches the MWU setpoint. If the unit is VAV, then the VAV box/unocc relay will continue to stay in the unoccupied position and the VFD output will stay at 100% during the
MWU mode. When the MWU setpoint is reached and the heat mode is terminated, then the VAV box/unocc relay will switch to the occupied mode and the VFD output will be controlled by the duct static pressure. During Full Capacity MWU the economizer damper is held closed for as long as it takes to reach setpoint. During Cycling Capacity MWU the economizer damper is allowed to go to minimum position after one hour of operation if setpoint has not been reached.
Compressor Motor Winding Thermostats
CSHD compressors (20-70 Ton) Air-Cooled and (24-80 Ton) Evaporative Condensers
The compressors contains an internal line break overload which stops the compressors under a number of operating conditions that cause excessive motor temperature. These include rapid cycling, loss of charge, abnormally high suction temperatures, excessive amperage, phase loss and low voltage
CSHN Compressors (75 - 130 Ton) Air-Cooled and (89 Ton) Evaporative Condensers
PTC sensors are embedded in the motor windings of each Scroll compressor. These sensors are wired to the protection module which protects the motor from over temperature that can occur under a number of abnormal operating conditions. These include rapid cycling, loss of charge, abnormally high suction temperatures, low voltage and excessive amperage.
During a request for compressor operation, if the Compressor Module (SCM) detects a problem outside of it's normal parameters, it turns any operating compressor(s) in that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
Discharge Line Thermostat
The first compressor on each circuit is equipped with a Discharge Line Thermostat. If the temperature of the line exceeds 210°F the thermostat interrupts the 115V circuit for the compressors and both of the compressors on that circuit will be de-energized. Once the temperature drops below 170°F the thermostat will close and allow the compressor to be energized.
21
General Information
Freeze Avoidance
Freeze Avoidance is a feature which helps prevent freezing of hydronic heat coils and avoiding nuisance hydronic heat freezestat trips. This is accomplished by opening inactive hydronic heat valve(s) at low ambient temperatures.
Typically, when the unit is in a mode where the supply fan is off, the OA temperature is monitored.
If it falls below 45 ºF (5 degrees above the freezestat), the hydronic heat valve(s) are opened to the
Standby Freeze Avoidance Position. When the OA temperature rises above 47 ºF, occupied mode is requested, or the supply fan is requested ON the hydronic heat valve(s) release to normal control.
When the supply fan is commanded on, the OA dampers will remain closed for one minute to remove the heat from the hydronic heating coil. This prevents freezestat trips and falsely loading the supply air temperature causing premature compressor operation. This function is disabled if the Standby Freeze Avoidance Position is set to 0%.
Supply Air Temperature Low Limit
Uses the supply air temperature sensor input to modulate the economizer damper to minimum position in the event the supply air temperature falls below the occupied heating setpoint temperature.
Freezestat (4S12)
This is a binary input device used on units with Hydronic Heat. It is mounted in the heat section and connected to the Heat Module (1U50). If the temperature of the air entering the heating coil falls to 40°F, the normally open contacts on the freezestat closes signalling the Heat Module (1U50) and the Rooftop Module (RTM) to:
• Drive the Hydronic Heat Actuator (4U15) to the full open position.
• Turn the supply fan “Off”.
• Closes the outside air damper;
• Turns “On” the SERVICE light at the Remote Panel.
• Initiates a “Freezestat” diagnostic to the Human Interface.
High Duct Temp Thermostats (Optional 3S16, 3S17)
These are binary input devices used with a Trane Communication Interface Module (TCI). They provide “high limit” shutdown of the unit and requires a manual reset. They are factory set to open if the supply air temperature reaches 240°F, or the return air temperature reaches 135°F. Once tripped, the thermostat can be reset by pressing the button located on the sensor once the air temperature has decreased approximately 25°F below the cutout point.
Compressor Circuit Breakers (1CB8, 1CB9, 1CB10, 1CB11)
The Scroll Compressors are protected by circuit breakers for 208 - 230 volt units which interrupt the power supply to the compressors if the current exceeds the breakers “must trip” value. For 460 -
575 volt units the Scroll compressors will be protected with Manual Motor protectors. During a request for compressor operation, if the Compressor Module detects a problem outside of it's normal parameters, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
Constant Volume (CV) Units
Zone Temperature - Cooling
Relies on input from a sensor located directly in the space, while a system is in the occupied
“Cooling” mode. It modulates the economizer (if equipped) and/or stages the mechanical cooling
“On and Off” as required to maintain the zone temperature to within the cooling setpoint deadband.
22 RT-SVX36G-EN
General Information
Zone Temperature - Heating
Relies on input from a sensor located directly in the space, while a system is in the occupied
“Heating” mode or an unoccupied period, to stage the heat “on and off” or to modulate the heating valve (hydronic heat only) as required to maintain the zone temperature to within the heating setpoint deadband. The supply fan will be requested to operate any time there is a requested for heat. On gas heat units, the fan will continue to run for 60 seconds after the furnace is turned off.
Supply Air Tempering
On CV Zone Temperature Control units, if the supply air temperature falls 10°F below the zone temperature setpoint up to half of the available heat capacity will be brought on until the supply air temperature reaches 10°F above zone temperature setpoint.
Single Zone Variable Air Volume (SZVAV) Only
The IntelliPak controls platform will support Single Zone VAV as an optional unit control type in order to meet ASHRAE 90.1. The basic control will be a hybrid VAV/CV configured unit that provides discharge temperature control to a varying discharge air temperature target setpoint based on the space temperature and/or humidity conditions. Concurrently, the unit will control and optimize the supply fan speed to maintain the zone temperature to a zone temperature setpoint.
Supply Fan Output Control
Units configured for Single Zone VAV control will utilize the same supply fan output control scheme as on traditional VAV units except the VFD signal will be based on zone heating and cooling demand instead of the supply air pressure.
VFD Control
Single Zone VAV units will be equipped with a VFD-controlled supply fan which will be controlled via a 0-10VDC signal from the Rooftop Module (RTM). With the RTM supply fan output energized and the RTM VFD output at 0VDC, the fan speed output is 37% (22Hz) from the VFD by default; and at 10VDC the fan speed output is 100% (60Hz). The control scales the 0-10VDC VFD output from the
RTM linearly to control between the 37-100% range. The VFD will modulate the supply fan motor speed, accelerating or decelerating as required to maintain the zone temperature to the zone temperature setpoint. When subjected to high ambient return conditions the VFD will reduce its output frequency to maintain operation. Bypass control is offered to provide full nominal airflow in the event of drive failure.
Ventilation Control
Units configured for Single Zone VAV control will require special handling of the OA Damper
Minimum Position control in order to compensate for the non-linearity of airflow associated with the variable supply fan speed and damper combinations. Units configured for TRAQ with or without DCV will operate identically to traditional units with no control changes.
Space Pressure Control
For units configured with Space Pressure Control with or without Statitrac, the new schemes implemented for economizer minimum position handling require changes to the existing Space
Pressure Control scheme in order to prevent over/under pressurization. The overall scheme will remain very similar to VAV units with Space Pressure Control with the exception of the dynamic
Exhaust Enable Setpoint.
For SZVAV an Exhaust Enable Setpoint must be selected during the 100% Fan Speed Command.
Once selected, the difference between the Exhaust Enable Setpoint and Design OA Damper
Minimum Position at 100% Fan Speed Command will be calculated. The difference calculated will be used as an offset and added to the Active Building Design OA Minimum Position Target in order to calculate the dynamic Exhaust Enable Target, which will be used throughout the Supply Fan
Speed/OA Damper Position range.
RT-SVX36G-EN 23
General Information
24
The Exhaust Enable Target could be above or below the Active Building Design OA Minimum
Position Target Setpoint, based on the Active Exhaust Enable Setpoint being set above or below the Building Design Minimum Position at 100% Fan Speed Command. Note that an Exhaust Enable
Setpoint of 0% will result in the same effect on Exhaust Fan control as on VAV applications with and without Statitrac.
Occupied Cooling Operation
For normal cooling operation, cooling capacity will be staged or modulated in order to meet the calculated discharge air target setpoint. If the current active cooling capacity is controlling the discharge air within the deadband, no additional cooling capacity change will be requested. As the
Discharge Air Temperature rises above the deadband, the algorithm will request additional capacity as required (additional compressors or economizer). As the Discharge Air Temperature falls below the deadband, the algorithm will request a reduction in active capacity.
Default Economizer Operation
By default, the unit will be setup to optimize the minimum supply fan speed capability during
Economizer Only operation. If the economizer is able to meet the demand alone, due to desirable ambient conditions, the supply fan speed will be allowed to increase above the minimum prior to utilizing mechanical cooling if discharge air setpoint falls below the discharge air Lower Limit
(Cooling) setpoint.
Unoccupied Mode
In Unoccupied mode the unit will utilize setback setpoints, 0% Minimum OA Damper position, and
Auto Fan Mode operation as on normal CV units. The Supply Fan speed, and cooling and modulating types of heat, will be controlled to the discharge air target setpoint as is done during occupied periods. The Supply fan speed during staged heat control will be forced to 100% as on normal CV units.
Occupied Heating Operation
Occupied heating operation has two separate control sequences; staged and modulated. All staged heating types will drive the supply fan to maximum flow and stage heating to control to the Zone
Heating Setpoint. For units with Hydronic and Gas heat, modulated SZVAV Heating. On an initial call for heating, the supply fan will drive to the minimum heating airflow. On an additional call for heating, the heat will control in order to meet the calculated discharge air target setpoint. As the load in the zone continues to request heat operation, the supply fan will ramp-up while the control maintains the heating discharge air temperature. Heating can be configured for either the energy saving SZVAV Heating solution as described above, or the traditional, less efficient CV Heating solution.
Compressor (DX) Cooling
Compressor control and protection schemes will function identical to that of a traditional unit.
Normal compressor proving and disable input monitoring will remain in effect as well as normal
3-minute minimum on, off, and inter-stage timers. Also, all existing head pressure control schemes will be in effect.
Cooling Sequence
If the control determines that there is a need for active cooling capacity in order to meet the calculated discharge air target setpoint, once supply fan proving has been made, the unit will begin to stage compressors accordingly. Note that the compressor staging order will be based on unit configuration and compressor lead/lag status.
Once the discharge air target setpoint calculation has reached the Minimum Setpoint and compressors are being utilized to meet the demand, as the discharge air target setpoint value continues to calculate lower the algorithm will begin to ramp the supply fan speed up toward 100%.
Note that the supply fan speed will remain at the compressor stage’s associated minimum value
RT-SVX36G-EN
General Information
(as described below) until the discharge air target setpoint value is calculated below the discharge air temperature Minimum Setpoint (limited discharge air target setpoint).
As the cooling load in the zone decreases the zone cooling algorithm will reduce the speed of the fan down to minimum per compressor stage and control the compressors accordingly. As the compressors begin to de-energize, the supply fan speed will fall back to the Cooling Stage’s associated minimum fan speed, but not below. As the load in the zone continues to drop, cooling capacity will be reduced in order to maintain the discharge air within the ± ½ discharge air target deadband.
Constant Volume (CV), Single Zone Variable Air Volume (SZVAV), &
Variable Air Volume (VAV) Units
Occupied Heating - Supply Air Temperature
When a Discharge Temperature Control unit is equipped with “Modulating Heat”, and the system is in an occupied mode, and the field supplied changeover relay contacts (5K87) have closed, the supply air temperature will be controlled to the customer specified supply air heating setpoint. It will remain in the heating status until the changeover relay contacts are opened.
Occupied Cooling - Supply Air Temperature
When a Discharge Temperature Control unit is in the occupied mode, the supply air temperature will be controlled to the customers specified supply air cooling setpoint by modulating the economizer and/or staging the mechanical cooling “On and Off” as required. The changeover relay contacts must be open on units with “Modulating Heat” for the cooling to operate.
Daytime Warm-up (CV & VAV Only)
On Discharge Temperature Control units equipped with heat, if the zone temperature falls below the daytime warm-up initiate temperature during the occupied mode, the system will switch to full airflow. During this mode, the VAV box/unocc relay, RTM K3, will be energized (this is to signal the
VAV boxes to go to 100%). After the VAV box max stroke time has elapsed (factory set at 6 minutes), the VFD output will be set to 100%. The airflow will be at 100% and the heat will be turned on to control to the occupied heating setpoint. When the zone temperature reaches the daytime warmup termination setpoint, the heat will be turned off, the K3 relay will be de-energized, releasing the
VAV boxes, the VFD output will go back to duct static pressure control and the unit will return to discharge air control. If the occ zone heating setpoint is less than the DWU terminate setpoint, the heat will turn off when the occ zone heat setpoint is reached, but it will stay in DWU mode and cycle the heat to maintain setpoint.
Unoccupied Heating - Zone Temperature
When a Discharge Temperature Control unit is equipped with gas, electric, or hydronic heat and is in the unoccupied mode, the zone temperature will be controlled to within the customers specified setpoint deadband. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in the unoccupied position and the VFD output will be at 100%. This means that if there is a call for heat (or cool) and the supply fan comes on, it will be at full airflow and the VAV boxes in the space will need to be 100% open as signaled by the VAV box/unocc relay.
Supply Air Tempering
On Discharge Temperature Control units equipped with “Modulating Heat”, if the supply air temperature falls 10°F below the supply air temperature setpoint, the hydronic heat valve will modulate to maintain the supply air temperature to within the low end of the setpoint deadband.
RT-SVX36G-EN 25
General Information
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer when a unit is equipped with or a
Variable Frequency Drive to position to set the supply fan speed to maintain the supply duct static
pressure to within the static pressure setpoint deadband. See Figure 3 below.
Figure 3.
Transducer Voltage Output vs. Pressure Input
-0.75 to 9.0 Iwc Pressure Transducer Voltage Output vs. Pressure Input
4.50
4.00
3.50
3.00
2.50
2.00
1.50
1.00
0.50
0.00
-0.
75
-0.
25
0.
25
0.
75
1.
25
1.
75
2.
25
2.
75
3.
25
3.
75
4.
25
4.
75
5.
25
Pressure (inches w.c.)
5.
75
6.
25
6.
75
7.
25
7.
75
8.
25
8.
75
Single Zone Variable Air Volume (VAV) Units
Occupied Heating - Supply Air Temperature
When a Discharge Temperature Control unit is equipped with “Modulating Heat”, and the system is in an occupied mode, and the field supplied changeover relay contacts (5K87) have closed, the supply air temperature will be controlled to the customer specified supply air heating setpoint. It will remain in the heating status until the changeover relay contacts are opened.
Occupied Cooling - Supply Air Temperature
When a Discharge Temperature Control unit is in the occupied mode, the supply air temperature will be controlled to the customers specified supply air cooling setpoint by modulating the economizer and/or staging the mechanical cooling “On and Off” as required. The changeover relay contacts must be open on units with “Modulating Heat” for the cooling to operate.
Daytime Warm-up
On Discharge Temperature Control units equipped with heat, if the zone temperature falls below the daytime warm-up initiate temperature during the occupied mode, the system will switch to full airflow. During this mode, the VAV box/unocc relay, RTM K3, will be energized (this is to signal the
VAV boxes to go to 100%). After the VAV box max stroke time has elapsed (factory set at 6 minutes), the VFD/IGV output will be set to 100%. The airflow will be at 100% and the heat will be turned on to control to the occupied heating setpoint. When the zone temperature reaches the daytime warmup termination setpoint, the heat will be turned off, the K3 relay will be de-energized, releasing the VAV boxes, the VFD/IGV output will go back to duct static pressure control and the unit will return to discharge air control. If the occ zone heating setpoint is less than the DWU
26 RT-SVX36G-EN
RT-SVX36G-EN
General Information
terminate setpoint, the heat will turn off when the occ zone heat setpoint is reached, but it will stay in DWU mode and cycle the heat to maintain setpoint.
Unoccupied Heating - Zone Temperature
When a Discharge Temperature Control unit is equipped with gas, electric, or hydronic heat and is in the unoccupied mode, the zone temperature will be controlled to within the customers specified setpoint deadband. During an unoccupied mode for a VAV unit, the VAV box/unocc relay will be in the unoccupied position and the VFD/IGV output will be at 100%. This means that if there is a call for heat (or cool) and the supply fan comes on, it will be at full airflow and the VAV boxes in the space will need to be 100% open as signaled by the VAV box/unocc relay.
Supply Air Tempering
On Discharge Temperature Control units equipped with “Modulating Heat”, if the supply air temperature falls 10°F below the supply air temperature setpoint, the hydronic heat valve will modulate to maintain the supply air temperature to within the low end of the setpoint deadband.
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer when a unit is equipped with Inlet Guide
Vanes or a Variable Frequency Drive to position the Inlet Guide Vanes or set the supply fan speed to maintain the supply duct static pressure to within the static pressure setpoint deadband. See
.
27
General Information
Figure 4.
Unit Component Layout and "Ship with" Locations
Space Temperature Averaging
Space temperature averaging for Constant Volume applications is accomplished by wiring a number of remote sensors in a series/parallel circuit.
The fewest number of sensors required to accomplish space temperature averaging is four. The
Space Temperature Averaging with Multiple Sensors figure illustrates a single sensor circuit
(Single Zone), four sensors wired in a series/parallel circuit (Four Zone), nine sensors wired in a series/parallel circuit (Nine Zone). Any number squared, is the number of remote sensors required.
Wiring termination will depend on the type of remote panel or control configuration for the system.
Refer to the wiring diagrams that shipped with the unit.
28 RT-SVX36G-EN
Figure 5.
Space Temperature Averaging
General Information
RT-SVX36G-EN
Space Temperature Averaging with Multiple Sensors Unit Control Modules
(UCM)
Unit control modules are microelectronic circuit boards designed to perform specific unit functions. These modules through Proportional/Integral control algorithms provide the best possible comfort level for the customer. They are mounted in the control panel and are factory wired to their respective internal components. They receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for economizing, mechanical cooling, heating, and ventilation. Figure 9 below illustrates the typical location of each “1U” designated module.
29
General Information
Figure 6.
Control Module Locations for S_HL, 20-36 Ton Units
Figure 7.
Control Module Locations for S_HL 40 - 89 Ton Units
30 RT-SVX36G-EN
Installation
Unit Inspection
As soon as the unit arrives at the job site
[ ] Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
[ ] Verify that the power supply complies with the unit nameplate specifications.
[ ] Verify that the power supply complies with the electric heater specifications on the unit nameplate.
[ ] Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
[ ] Check for material shortages. Refer to the Component Layout and Ship with location illustration.
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing.
[ ] Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
WARNING
No Step Surface!
FOR ACCESS TO COMPONENTS, THE BASE SHEET METAL SURFACE MUST BE REINFORCED.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating. Failure to comply could result in death or severe personal injury from falling.
[ ] If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:
1.
the unit is stored before it is installed; or,
2. the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit's heater for temporary heat without first completing the startup procedure detailed under “Starting the Unit”.
Trane will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit's electrical and/or mechanical components.
RT-SVX36G-EN 31
Installation
Unit Clearances
illustrates the minimum operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “shortcircuiting” of exhaust and economizer airflows, or recirculation of hot condenser air.
Unit Dimensions & Weight Information
Description Reference
Air-Cooled Condenser
Unit dimensions, 20-75 Ton (SAHL)
,
,
,
Unit dimensions, 90-130 Ton
Typical unit and operation weights
Center-of-Gravity illustration and related dimensional data
Evaporative Condenser
Unit dimensions, 20-89 Ton
(SEH_, SFH_, SLH_, SSH_, and SXH_)
Typical unit and operation weights
(a)
Center-of-Gravity illustration and related dimensional data
,
,
(a) Weights shown represent approximate operating weights. Actual weights are stamped on the unit nameplate.
32 RT-SVX36G-EN
Figure 8.
Minimum operation and service clearances for single and multiple unit installation
Single Unit Installation
Legend
A
B
C
D
J
K
L
M
E
F
G
H
=
=
=
=
=
=
=
=
=
=
=
=
Return Air Opening
Fresh Air Intake
Supply Air Opening
Condenser Section
Optional 2’10-3/4” Exhaust/Return Access Door (180° swing)
Hinged 2’10-3/4” Filter Access Door (180° swing)
Hinged 2’10-3/4” Heater Access Door (180° swing)
Hinged 2’10-3/4” Supply Fan Access Door (180° swing) (90-130 ton)
Hinged 2’4-1/2” Control Panel Door (180° swing) (90-130 ton)
Hinged 2’10-3/4” VFD Access Door (180° swing)
Hinged 2’10-3/4” Evap Condenser Access Door (180° swing)
Hinged 2’8” Control Panel Door (180° swing) (20-36 ton)
Hinged 3’6” Control Panel Door (180° swing) (40-89 ton)
L
L
M
Installation
RT-SVX36G-EN 33
Installation
Figure 9.
SAHL cooling-only units (20 - 75) Use Table 4 ,
1” CONDENSATE DRAIN
CONNECTION (Both Sides)
Table 4.
Unit dimensional data
Unit Size
20 & 25 Ton
30 Ton
40 Ton
50 Ton
60 Ton
70 & 75 Ton
A
21’-9 3/4”
21’-9 3/4”
29’-8”
29’-8”
29’-8”
29’-8”
B
6’-9”
6’-9”
6’-9”
6’-9”
6’-9”
6’-9”
C
7'-6 1/2"
7'-6 1/2"
7'-6 1/2"
7'-6 1/2"
9'-8"
9'-8"
D
7’-3 1/4”
Dimensions
E
3'-9 5/16"
7’-3 1/4”
7’-3 1/4”
7’-3 1/4”
7’-3 1/4”
7’-3 1/4”
4'-9 5/16"
5'-9 5/16"
6'-9 5/16"
5'-9 5/16"
5'-9 5/16"
F
12'-6”
12'-6”
15'-11 1/8"
15'-11 1/8"
15'-11 1/8"
15'-11 1/8"
G
1"
1"
1"
1"
1"
1"
8’
8’
7’
8’
8’
H
7’
J
1'-3 1/2”
1'-3 1/2”
2'-5”
2'-5”
2'-5”
2'-5”
34 RT-SVX36G-EN
Installation
Table 5.
Unit base dimensional data
Unit Size A B C D
20 - 30 Ton 14'-0 1/4" 2'-2 1/2" 11 3/4"
40 - 50 Ton 16'-1 13/16” 2'-5" 11 3/4"
60 Ton 16'-1 13/16”
70 - 75 Ton 16'-1 13/16”
2'-5"
2'-5"
1'-4 9/16"
1'-4 9/16"
5'-7"
5'-7"
6'-10 7/8"
6'-10 7/8"
Dimensions
E w/exhaust fan w/return fan w/ exhaust fan
F w/ return fan fan
3'-4 3/8" 2'-9 15/16” 5 13/16" 28 5/8” 6'-6 15/16"
3'-4 3/8" 3' - 1 1/2” 5 13/16" 32 15/16” 7'-8 3/16"
4'-5 3/8"
4'-5 3/8"
4' - 2 1/2” 5 13/16"
4' - 2 1/2” 5 13/16"
26 7/16”
26 7/16”
7'-8 3/16"
7'-8 3/16"
G w/exhaust w/return fan
3'
3'-4”
4'-5”
4'-5”
Table 6.
Electrical entrance data
Unit Size
20, 25, 30 & 50 Ton
40, 60, 70 & 75 Ton
F
8 7/32"
8 3/4"
G H J K
6 31/32" 15 21/32" 13 21/32" 9 17/32"
7 3/4" 17 7/8"
Dimensions
15 7/8"
L
8 1/2"
M N
18 1/16" 19 9/16"
9 29/32" 10 1/16" 20 13/32" 22 5/32"
RT-SVX36G-EN 35
Installation
Figure 10. SEHL, SFHL, SLHL, SSHL, SXHL units (20 - 89 ton) Use
,
1” NPT CONDENSATE
DRAIN CONNECTION (Both Sides)
DRAIN HOLE
Table 7.
Unit Dimensional Data
Unit Size A
20 & 25 Ton 24'-1 3/8"
30 Ton 24'-1 3/8"
B
6’-9”
6’-9”
C D
Air-Cooled Unit Dimensions
E
7'-6 1/2" 7’-3 1/4” 3'-9 5/16"
7'-6 1/2" 7’-3 1/4” 4'-9 5/16"
F
13'-3"
13'-3"
G
1"
1"
H
7'
7'
40 Ton 32'-10 1/2” 6’-9” 7'-6 1/2" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8'
J K L M N O
1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
2'-5" 8 1/8" 6 1/4" 9"
50 Ton
60 Ton
32'-10 1/2"
32'-10 1/2”
6’-9”
6’-9”
70 & 75 Ton 32'-10 1/2” 6’-9”
Unit Size A
24 & 39 Ton 26’5 1/2”
36 Ton 26’5 1/2”
B
6’-9”
6’-9”
7'-6 1/2" 7’-3 1/4” 6'-9 5/16" 15'-11 1/8" 1"
9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1"
8'
8'
2'-5"
2'-5"
8 1/8" 6 1/4" 9"
8 1/8" 6 1/4" 9"
9'-8" 7’-3 1/4” 5'-9 5/16" 15'-11 1/8" 1" 8' 2'-5” 8 1/8" 6 1/4" 9"
C D
Evaporative Condensing Unit Dimensions
E
7’-6 1/2” 8’-4 3/4” 3’-9 5/16”
F
13’-3”
G
1"
H
7”
J K L M N O
1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
7’-6 1/2” 8’-4 3/4” 4’-9 5/16” 13’-3” 1" 7” 1'-3 1/2" 16'-7" 16'-6" 8 1/8" 6 1/4" 9"
36 RT-SVX36G-EN
Installation
Table 7.
Unit Dimensional Data
Unit Size
48 Ton
A B
32’-10 1/2” 6’-9”
C D
Evaporative Condensing Unit Dimensions
E F G
7’-6 1/2” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1"
H
8”
J
2'-5"
59 Ton
73 Ton
32’-10 1/2” 6’-9”
32’-10 1/2” 6’-9”
7’-6 1/2” 8’-4 3/4” 6’-9 5/16” 15’-11 1/8” 1"
9’-8” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1"
8”
8”
2'-5"
2'-5"
80 & 89 Ton 32’-10 1/2” 6’-9” 9’-8” 8’-4 3/4” 5’-9 5/16” 15’-11 1/8” 1"
Note:
19'-6” for SFHL “High Heat” units or 20'-3” for SFHL “Low Heat” units.
8” 2'-5”
K L M N O
8 1/8" 6 1/4" 9"
8 1/8" 6 1/4" 9"
8 1/8" 6 1/4" 9"
8 1/8" 6 1/4" 9"
Table 8.
Unit Base Dimensional Data - Air Cooled and Evaporative Condenser
Dimensions w/ exhaust fan
E w/ return fan w/ exhaust fan
G
Unit Size
(AC/EC)
20-30
/24-36 Ton
40 & 50
/48 & 59 Ton
60/73 Ton
70-75
/80-89 Ton
A B C
16'-3 3/16" 2'-2 1/2" 5 13/16"
19'-10 5/16"
19'-10 5/16"
19'-10 5/16"
2'-5"
2'-5"
2'-5"
7 1/16"
6 1/16"
6 1/16"
D
5'-7"
5'-7"
Note 1
Note 1
H J K L
20-30
/24-36 Ton
40 & 50
/48 & 59 Ton
15'-5 5/16" 16'-9 3/4" 8 13/16"
18'-11 11/16" Note 2
60/73 Ton 18'-11 11/16" Note 2
70-75
/80-89 Ton
18'-11 11/16" Note 2
8 3/16"
8 3/16"
8 3/16"
9 1/16"
9 1/16"
9 1/16"
9 1/16"
3'-4 3/8" 2'-9 15/16” 5 13/16" 6'-6 15/16"
3'-4 3/8"
4'-5 3/8"
4'-5 3/8"
3'-1 1/2”
4'-2 1/2”
4'-2 1/2”
Notes:
1. 5'-5 15/16” for SEHL units or 7'-8 1/2” for SFHL, SLHL, SSHL, SXHL units.
2. 20'-1 3/4” for SFHL “High Heat” units or 20'-6 3/4” for SFHL “Low Heat” units.
F
5 13/16" 7'-8 3/16"
5 13/16" 7'-8 3/16"
5 13/16" 7'-8 3/16"
w/ return fan w/ exhaust fan
F w/ return fan
3' 5 13/16" 28 5/8”
3'-4”
4'-5”
4'-5”
5 13/16" 32 15/16”
5 13/16" 26 7/16”
5 13/16" 26 7/16”
RT-SVX36G-EN 37
Installation
Figure 11. Evaporative condenser water connection locations
38
A
B
Drain Connection
1 1/4” PVC, Female
Water Supply Connection
3/4” PVC, Female
A
B
8.16
19.84
Tons
(EC)
24, 29 & 36 Ton
48 & 59 Ton
73, 80 & 89 Ton
Drain Connection
A B
60.03
82.86
78.56
79.31
102.14
102.14
C
D
Inlet Water Connection
C D
12.01
12.01
23.71
12.94
12.94
24.64
RT-SVX36G-EN
Installation
Table 9.
Electrical entrance data
Unit Size
(AC/EC)
20, 25 & 30 Ton
40-75 / 24-89 Ton
F
8 7/32"
8 15/16”
G
6 31/32"
7 15/16”
H
Dimensions
J K
15 21/32" 13 21/32"
17 7/8" 15 7/8"
9 17/32"
9 29/32"
L
8 1/2"
10 3/16”
M
18 1/16"
20 13/32"
N
19 9/16"
22 5/32"
Table 10. CPVC dimensional data
Unit Size
(AC/EC) Furnace Size/MBH
Dimensions (Note)
Length Height
20 & 25, 24 & 29 Ton
Low = 235
High = 500
195-5/32"
195-5/32"
9-5/32"
9-5/32"
30, 36 Ton
Low = 350
High = 500
Low = 350
195-5/32"
195-5/32"
240-1/8"
9-5/32"
9-5/32"
9-5/32"
40, 48 Ton
50-75, 59-89 Ton
High = 850
Low = 500
High = 850
231-1/8"
240-1/8"
231-1/8"
9-5/32"
9-5/32"
9-5/32"
Note:
The length dimension is from the exhaust end of the unit. The height dimension is from the bottom of the unit base rail.
RT-SVX36G-EN 39
Installation
Figure 12. S_HK cooling and heating units (90-130 ton)
14’ - 1/4”
19’ - 3/8”
20’ - 2 1/2”
(See CPVC Dimensional Table)
40 RT-SVX36G-EN
Installation
Figure 13. Center of gravity data
Table 11. Center of gravity data
Unit Model Unit Size
Units without 100%
Exhaust/Return Fan
Dim. A Dim. B
Units with
Exhaust/Return Fan
Dim. A Dim B.
Units with Supply &
Exhaust/Return VFD
Dim. A Dim. B
SAHL
SEHL, SLHL,
SSHL, SXHL
40
50
55
60
75
20
25
30
50
55
60
70
20
25
30
40
13’ 6”
14’ 6”
13’ 11”
17’ 4”
18’ 6”
18’ 6”
17’ 0”
17’ 0”
18’ 6”
15’ 8”
15’ 8”
14’ 1”
18’ 4”
19’ 1”
19’ 1”
18’ 6”
5’ 10”
4’ 9”
4’ 9”
4’ 9”
4’ 11”
4’ 0”
4’ 0”
5’ 9”
4’ 10”
4’ 10”
4’ 10”
4’ 0”
4’ 0”
4’ 0”
5’ 10”
5’ 10”
13’ 10”
13’ 11”
12’ 1”
16’ 2”
16’ 4”
16’ 5”
16’ 9”
16’ 10”
16’ 4”
14’ 0”
14’ 0”
13’ 3”
17’ 2”
18’ 11”
18’ 11”
17’ 2”
5’ 8”
4’ 8”
4’ 8”
4’ 8”
4’ 10”
4’ 11”
4’ 11”
5’ 7”
4’ 9”
4’ 9”
4’ 9”
4’ 11”
4’ 11”
4’ 11”
5’ 8”
5’ 8”
16’ 9”
13’ 5”
13’ 6”
13’ 8”
17’ 6”
17’ 2”
17’ 3”
17’ 6”
12’ 4”
12’ 4”
12’-8”
16’ 7”
16’ 9”
16’ 9”
15’ 2”
15’ 3”
SFHL
30
40
50
55
70
75
20
25
18’ 3”
19’ 2”
15’ 9”
15’ 10”
14’ 2”
19’ 6”
19’ 1”
19’ 2”
5’ 10”
5’ 10”
4’ 10”
4’ 9”
4’ 9”
4’ 11”
4’ 11”
4’ 11”
17’ 11”
18’ 10”
14’ 1”
14’ 2”
13’ 4”
17’ 4”
18’ 0”
18’ 0”
5’ 8”
5’ 8”
4’ 9”
4’ 8”
4’ 8”
4’ 10”
4’ 10”
4’ 10”
16’ 4”
17’ 2”
14’ 7”
14’ 7”
13’ 10”
17’ 9”
17’ 4”
17’ 4”
5’ 9”
5’ 9”
4’ 10”
4’ 9”
4’ 9”
4’ 10”
4’ 11”
4’ 11”
SXHK,SEHK,
SLHK,SSHK
60
70
75
90
105
90
19’ 7”
18' 3”
19’ 2”
18’ 9”
19’ 1”
18’ 11”
5’ 9”
5’ 9”
5’ 9”
5’ 10”
5’ 11”
6’ 0”
17’ 4”
17’ 0”
18’ 10”
20’ 4”
20’ 7”
20’ 6”
5’ 7”
5’ 7”
5’ 7”
6’ 2”
6’ 2”
6’ 3”
17’ 8”
16’ 5”
17’ 3”
17’ 9”
18’ 1”
17’ 10”
5’ 9”
5’ 8”
5’ 9”
5’ 10”
6’ 0”
5’ 11”
SFHK
SXHK, SEHK,
SLHK, SSHK
105
115
130
19’ 3”
19’ 2”
19’ 5”
6’ 0”
5’ 10”
5’ 10”
20’ 9”
20’ 8”
20’ 11”
6’ 4”
6’ 2”
6’ 2”
18’ 4”
18’ 1”
18’ 6”
6’ 7”
6’ 0”
6’ 0”
SFHK
115
130
19’ 4”
19’ 6”
6’ 0”
6’ 0”
20’ 9”
21’ 10”
6’ 3”
6’ 3”
18’ 3"
18’ 8”
6’ 1”
6’ 0”
Note:
Dimensions shown for the center-of-gravity are approximate and are based on a unit equipped with: Standard coils, 100% economizer, throwaway filters, 460 volt XL start, high capacity heat (as applicable).
5’ 9”
4’ 9”
4’ 9”
4’ 9”
4’ 10”
4’ 11”
4’ 0”
5’ 8”
4’ 10”
4’ 10”
4’ 10”
4’ 11”
4’ 11”
4’ 11”
5’ 9”
5’ 9”
RT-SVX36G-EN 41
Installation
Table 12. Air-cooled condenser - approximate operating weights (Lbs./Kg)
Unit
20
25
30
40
50
55
60
70
75
90
105
115
130
SA
8604
3903
8843
4011
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7175
3255
7425
3368
8338
3782
4092
1856
4181
1896
4572
2074
6433
2918
Kg
Lb.
Kg
Lb.
Lb
Kg
Lb
Kg
Lb.
Kg
Lb.
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Without Exhaust Fan
SX SE SF
4422
2006
4521
2050
4932
2237
6737
3056
7725
3504
7975
3617
8658
3927
8666
3931
9173
4161
13100
5955
13710
6232
13900
6318
14350
6523
4712
2137
4791
2173
5202
2359
7217
3273
8185
3713
8455
3835
9118
4136
9146
4148
9653
4379
13250
6023
13860
6300
14080
6400
14510
6595
4422
2006
4521
2050
4932
2237
6737
3056
7725
3504
7975
3617
8658
3927
8666
3931
9173
4161
13890
6314
14500
6591
14740
6700
15150
6886
SL/SS
8516
3863
9023
4093
13370
6077
13980
7555
3427
7815
3545
8498
3855
6355
14100
6409
14540
6609
4312
1956
4391
1992
4812
2183
6577
2983
SA
9547
4330
9786
4439
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
7894
3581
8144
3694
9282
4210
4390
1991
4485
2034
5029
2281
7103
3222
SX
With Exhaust Fan
SE SF
9609
4358
10116
4589
14440
6564
15050
8444
3830
8694
3944
9602
4355
6841
15240
6927
15690
7132
4720
2141
4825
2188
5389
2444
7407
3360
9609
4358
10116
4589
15230
6923
15840
8444
3830
8694
3944
9602
4355
7200
16080
7309
16490
7495
4720
2141
4825
2188
5389
2444
7407
3360
10089
4576
10596
4806
14590
6632
15200
8904
4039
9174
4161
10062
4564
6909
15420
7009
15850
7205
5010
2272
5095
2311
5659
2567
7887
3577
Notes:
1. Weights shown for air-cooled units include the following features: standard coils, 100% economizer, throwaway filters, maximum motor sizes, 460V
XL, high heat.
2. Weights shown represent approximate operating weights and have a ±5% accuracy. To calculate weight for a specific unit configuration, utilize
TOPSS™ or contact the local Trane sales representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT NAMEPLATE.
SL/SS
9459
4290
9966
4521
14710
6686
15320
8274
3753
8534
3871
9442
4283
6964
15440
7018
15880
7218
4610
2091
4695
2129
5269
2390
7247
3287
42 RT-SVX36G-EN
Installation
Table 13. Evaporative condenser - approximate operating weights (lbs/kg)
Unit
24
29
36
48
59
73
80
89 kg lbs kg lbs kg lbs kg lbs lbs kg lbs kg lbs kg lbs kg
SX
6549
2971
6599
2993
7121
3230
9001
4083
9213
4179
11303
5127
11430
5185
11820
5361
Without Exhaust Fan
SE SF
6679
3030
6729
3052
7251
3289
9156
4153
9368
4249
11458
5197
11585
5255
11975
5432
6944
3150
6994
3172
7513
3409
9631
4369
9843
4465
11933
5413
12060
5470
12450
5647
SL/SS
6763
3068
6813
3090
7335
3327
9359
4245
9571
4341
11691
5303
11818
5361
12208
5537
SX
6907
3133
6963
3158
7538
3419
9585
4348
9856
4471
12128
5501
12255
5559
12645
5736
With Exhaust Fan
SE SF
7037
3192
7093
3217
7668
3478
9740
4418
10011
4541
12283
5571
12410
5629
12800
5806
7302
3312
7358
3338
7933
3598
10215
4633
10486
4756
12758
5787
12885
5845
13275
6021
Notes:
1. Weights shown for evaporative condensing units include the following features: high capacity evaporative coil. Add 520 lbs for 24, 29, 36, 48 and 59 units and 680 lbs for 73, 80 and 89 units for installed sump base water weight for evaporative condenser total operating weight.
2. Weights shown represent approximate operating weights and have a ±5% accuracy. To calculate weight for a specific unit configuration, utilize TOPSS or contact the local Trane sales representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT NAMEPLATE.
SL/SS
7121
3230
7177
3255
7752
3516
9943
4510
10214
4633
12516
5677
12643
5735
13033
5912
Table 14. Roof curb max weight
(a)
Roof Curb Max. Weight
Unit SAHL
490
S*HL
510
20/24
222
490
231
510
25/29
222
490
231
510
30/36
222
515
231
550
40/48
234
515
249
550
50/55/59
234
515
249
550
60/73
234 249
(a) Roof curb weights include the curb and pedestal.
Unit
70/80
75/89
90
105
115
130
Roof Curb Max. Weight
SAHL
610
S*HL
640
N/A
N/A
N/A
N/A
277
610
277
N/A
N/A
N/A
N/A
349
770
349
770
290
640
290
770
349
770
349
RT-SVX36G-EN 43
Installation
Trane Roof Curb and Ductwork
The roof curbs for 20 through 130 Ton units consists of two main components; a pedestal to support the unit’s condenser section and a “full perimeter” enclosure to support the unit’s air handler section.
Before installing any roof curb, verify;
1.
That it is the correct curb for the unit,
2. That it includes the necessary gaskets and hardware,
3. That the purposed installation location provides the required clearance for proper operation.
4. Insure that the curb is level and square. The top surface of the curb must be true to assure an adequate curb-to-unit seal.
Step-by-step curb assembly and installation instructions ship with each Trane accessory roof curb kit. Follow the instructions carefully to assure proper fit-up when the unit is set into place.
Note: To assure proper condensate flow during operation, the unit (and curb) must be as level as possible. The maximum slope allowable for rooftop unit applications, excluding SSH_'s, is
4" end-to-end and 2" side-to-side. Units with steam coils (SSH_'s) must be set level!
If the unit is elevated, a field constructed catwalk around the unit is strongly recommended to provide easy access for unit maintenance and service.
Recommendations for installing the Supply Air and Return Air ductwork joining the roof curb are included in the curb instruction booklet. Curb ductwork must be fabricated and installed by the installing contractor before the unit is set into place.
Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations.
Do not cut out the entire roof deck within the curb perimeter.
Pitch Pocket Location
The location of the main supply power entry for S_HL 20 through 89 Ton rooftop units is located
at the bottom right-hand corner of the control panel. Figure 9
and
illustrate the location for the electrical entrance through the base in order to enter the control panel. If the power supply conduit penetrates the building’s roof beneath this opening, it is recommended that a pitch pocket be installed before the unit is placed onto the roof curb. The center line dimensions shown in the illustration below indicates the center line of the electrical access hole in the unit base when it is positioned on the curb, ±3/8 inch. The actual diameter of the hole in the roof should be at least 1/
2 inch larger than the diameter of the conduit penetrating the roof. This will allow for the clearance variable between the roof curb rail and the unit base rail illustrated in
.
The pitch pocket dimensions listed are recommended to enhance the application of roofing pitch after the unit is set into place. The pitch pocket may need to be shifted as illustrated to prevent interference with the curb pedestal.
44 RT-SVX36G-EN
Installation
Figure 14. Pitch pocket location
Table 15. Pitch pocket dimensions
Unit
S*HL
S*HL
S*HL
Tonnage
20, 25 & 30
24, 29, & 36
40 - 89
“A” Dimension "B" Dimension
4' 5-9/16"
6' 9-11/16”
9' 5-11/16"
5-9/16"
5-1/2”
5-1/2"
* = All unit functions (SAHL, SEHL, SFHL, SSHL, SLHL and SXHL)
Notes:
For design special evaporative-cooled condensing units, please see the curb installers guide for proper pitch pocket locations.
If a Trane Curb Accessory Kit is Not Used:
a. The ductwork can be attached directly to the factory-provided flanges around the unit’s supply and return air openings. Be sure to use flexible duct connections at the unit.
b. For “built-up” curbs supplied by others, gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
Notes:
•
If a “built-up” curb is provided by others, keep in mind that these commercial rooftop units do not have base pans in the condenser section.
•
If this is a REPLACEMENT UNIT keep in mind that the CURRENT DESIGN commercial rooftop units do not have base pans in the condenser section.
•
Trane roof curbs are recommended. If using a non-Trane roof curb with right-angle return airflow approaches to a return fan inlet, a rigid, solid flow baffle wall should be installed across
the full width of the roof curb return airflow path in the position shown in Figure 15, p. 46 to
reduce potential airflow disturbances at the return fan inlet that could contribute to unusual return fan noise.
RT-SVX36G-EN 45
Installation
Figure 15. Solid flow baffle wall installation for non-Trane roof curbs
Return Fan
Flow Baffle
Roof Curb
Return Airflow
Return Airflow
Duct
Unit Rigging & Placement
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury.
Note: Use spreader bars as shown in the diagram. Refer to the Installation manual or nameplate for the unit weight. Refer to the Installation Instructions located inside the side control panel for further rigging information.
1.
A Center-of-Gravity illustration and the dimensional data is shown in Figure 13, p. 41
.
2. Attach adequate strength lifting slings to all four lifting lugs on 20 through 75 Ton units. The minimum distance between the lifting hook and the top of the unit should be 7 feet for 20
through 75 Ton units. Figure 16, p. 47 illustrates the installation of spreader bars to protect the
unit and to facilitate a uniform lift.
lists the typical unit operating weights.
3. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
4. Lift the unit and position it over the curb and pedestal. (These units have a continuous base rail around the air handler section which matches the curb.
5. Align the base rail of the unit’s air handler section with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit. (The pedestal simply supports the unit’s condenser section)
A cross section of the juncture between the unit and the roof curb is shown in
.
46 RT-SVX36G-EN
Figure 16. Unit rigging
Figure 17. Typical unit base and roof curb cross section
Installation
RT-SVX36G-EN 47
Installation
General Unit Requirements
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The checklist listed below is a summary of the steps required to successfully install a Commercial rooftop unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions called out in the applicable sections of this manual.
• Check the unit for shipping damage and material shortage; file a freight claim and notify Trane office.
• Verify that the installation location of the unit will provide the required clearance for proper operation.
• Assemble and install the roof curb per the current edition of the curb installation guide.
• Fabricate and install ductwork; secure ductwork to curb.
• Install pitch pocket for power supply through building roof. (If applicable)
• Rigging the unit.
• Set the unit onto the curb; check for levelness.
• Ensure unit-to-curb seal is tight and without buckles or cracks.
• Install and connect condensate drain lines to each evaporator drain connection.
• Remove the shipping hold-down bolts and shipping channels from the supply and exhaust/ return fans ordered with rubber or spring isolators.
• Check all optional supply and exhaust/return fan spring isolators for proper adjustment.
• Verify all discharge and liquid line service valves (one per circuit) are back seated.
Main Electrical Power Requirements
• Verify that the power supply complies with the unit nameplate specifications.
• Inspect all control panel components; tighten any loose connections.
• Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect and unit
• Properly ground the unit.
Note: All field-installed wiring must comply with NEC and applicable local codes.
Field Installed Control Wiring
• Complete the field wiring connections for the constant volume controls as applicable. Refer to
“Field Installed Control Wiring” for guidelines.
• Complete the field wiring connections for the variable air volume controls as applicable. Refer to “Field Installed Control Wiring” for guidelines.
Note: All field-installed wiring must comply with NEC and applicable local codes.
48 RT-SVX36G-EN
Installation
Requirements for Electric Heat Units
All SEHL Units (380 minimum voltage).
• Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
• Inspect the heater junction box and control panel; tighten any loose connections.
• Check electric heat circuits for continuity.
SEHL Units w/200V or 230V Electric Heat: (Requires Separate Power Supply to
Heater)
• Connect properly sized and protected power supply wiring for the electric heat from a dedicated, field- supplied/installed disconnect to terminal block 4TB2, or to an optional unit mounted disconnect switch 4S15.
Requirements for Gas Heat
• Gas supply line properly sized and connected to the unit gas train.
• All gas piping joints properly sealed.
• Drip leg Installed in the gas piping near the unit.
• Gas piping leak checked with a soap solution. If piping connections to the unit are complete, do not pressurize piping in excess of 0.50 psig or 14 inches w.c. to prevent component failure.
• Main supply gas pressure adequate.
• Flue Tubes clear of any obstructions.
• Factory-supplied flue assembly installed on the unit.
• Connect the 3/4” CPVC furnace drain stubout to a proper condensate drain.
Requirements for Hot Water Heat (SLH_)
• Route properly sized water piping through the base of the unit into the heating section.
• Install the factory-supplied, 3-way modulating valve.
• Complete the valve actuator wiring.
Requirements for Steam Heat (SSH_)
• Install an automatic air vent at the top of the return water coil header.
• Route properly sized steam piping through the base of the unit into the heating section.
• Install the factory-supplied, 2-way modulating valve
• Complete the valve actuator wiring.
• Install 1/2”, 15-degree swing-check vacuum breaker(s) at the top of each coil section. Vent breaker(s) to the atmosphere or merge with return main at discharge side of steam trap.
• Position the steam trap discharge at least 12" below the outlet connection on the coil.
• Use float and thermostatic traps in the system, as required by the application.
O/A Pressure Sensor and Tubing Installation (All units with Statitrac or Return Fans)
• O/A pressure sensor mounted to the roof bracket.
• Factory supplied pneumatic tubing installed between the O/A pressure sensor and the connector on the vertical support.
• Field supplied pneumatic tubing connected to the proper fitting on the space pressure transducer located in the filter section, and the other end routed to a suitable sensing location within the controlled space (Statitrac only).
RT-SVX36G-EN 49
Installation
Requirements for Modulating Reheat Dehumidification
• Install (5U108) humidity sensor in space or return duct
• Complete field wiring of humidity sensor to ECEM (1TB16). Refer to “Field Installed Control wiring” for guidelines.
Figure 18. Condensate Drain Locations
Sloped Drain Pan Option
(2) condensate drain openings both sides
Note: Connect all sloped drain pan connections on each side of the unit (total 4) to the trapped
Each drain pan connection must be trapped.
The drains may be trapped individually or connected and then trapped.
Condensate Drain Connections
Each S_HL and S_HK unit is provided with four 1" evaporator condensate drain connections (two on each side of the unit).
Due to the size of these units, all condensate drain connections must be connected to the evaporator drain connections. Refer to the appropriate illustration in
location of these drain connections.
A condensate trap must be installed due to the drain connection being on the “negative pressure” side of the fan. Install the P-Traps at the unit using the guidelines in
Pitch the drain lines at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double-trap condition which could result in condensate backup due to “air lock”.
Units with Gas Furnace
Units equipped with a gas furnace have a 3/4” CPVC drain connection stubbed out through the vertical support in the gas heat section. It is extremely important that the condensate be piped to
a proper drain. Refer to the appropriate illustration in Figure 9
and
for the location of the drain connection.
Note: Units equipped with an optional modulating gas furnace will likely operate in a condensing mode part of the time.
50 RT-SVX36G-EN
Installation
An additional 1-1/4” non-connectable water drain is located in the base rail within the heating section.
Ensure that all condensate drain line installations comply with applicable building and waste disposal codes.
Figure 19. Condensate Trap Installation
L
G
RT-SVX36G-EN
Removing Supply and Exhaust/Return Fan Shipping Channels (Motors >5Hp)
Each supply fan assembly and exhaust fan assembly for S_HL units shipped with a motor larger than 5 HP is equipped with rubber isolators (as standard) or optional spring isolators. Each return fan assembly for S_HL units shipped with a motor larger than 5 HP is equipped with spring isolators. Shipping channels are installed beneath each fan assembly and must be removed. To locate and remove these channels, refer to
, and use the following procedures:
Rubber Isolators:
1.
Remove and discard the shipping bolts from the fan assembly rails.
2. Elevate the fan-and-motor assembly and slide the shipping channels out from between the fan assembly rails and the unit's base rail.
3. Lower the fan-and-motor assembly onto the isolators. Make sure that the pins at the top of the isolators are engaged in the corresponding holes on the fan assembly.
4. Verify that the fan assembly is being supported by the isolators.
Spring Isolators:
See
and
Figure 21 for spring isolator locations.
1.
Remove and discard the shipping tie down bolts.
2. Remove the shipping channels and discard.
Note: Fan assemblies not equipped with rubber or spring isolators have mounting bolts at the same locations and must not be removed.
Note: If return fan backside spring isolator repair/replacement is required, access the backside of the return fan by entering the unit filter section. Remove the top pivot bearings from the three fixed- position return damper blades (bolted together as a single section with an angle brace). Lift the three-blade section as a single unit from the return damper assembly and set aside or lean in against the return fan frame. Then enter the return fan compartment from the filter section to perform service work on the rear isolators.
51
Installation
Figure 20. Removing Supply and Exhaust Fan Assembly Shipping Hardware (20-89 Ton)
Figure 21. Removing Return Fan Assembly Shipping Hardware (20-89 Ton)
52 RT-SVX36G-EN
Figure 22. Removing supply and exhaust fan assembly shipping hardware (90-130 Ton)
Installation
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units designed to operate on variable air volume applications, units equipped with a return fan, or constant volume units with 100% modulating exhaust w/Statitrac.
On VAV systems, a duct pressure transducer (3U60) and the outside air sensor is used to control the discharge duct static pressure to within a customer-specified parameter.
On CV & VAV units equipped with 100% modulating exhaust w/Statitrac, a space pressure transducer (3U62) and the outside air sensor is used to control the exhaust fan and dampers to relieve static pressure to within a customer-specified parameter within the controlled space.
On units equipped with a return fan, a return pressure transducer (3U106) is connected to the
O/A sensor for comparison with return plenum pressure.
Refer to Figure 23, p. 56 and the following steps to install the sensor and the pneumatic tubing.
1.
Remove the O/A pressure sensor kit located inside the filter section. The kit contains the following items;
•
O/A static pressure sensor with sensor mounting
•
Bracket
•
50' of 3/16” O.D. pneumatic tubing
•
Mounting hardware
RT-SVX36G-EN 53
Installation
2. Using two #10-32 x 1-3/4” screws provided, install the sensor's mounting bracket to the factory installed bracket (near the filter section).
3. Using the #10-32 x 1/2” screws provided, install the O/A static pressure sensor vertically to the sensor bracket.
4. Remove the dust cap from the tubing connector located below the sensor in the vertical support.
5. Attach one end of the 50' x 3/16” O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing.
Units with Statitrac:
6. Open the filter access door, and locate the DSP control devices illustrated in Figure 23
. There are three tube connectors mounted on the left of the solenoid and transducers. Connect one end of the field provided 3/16” O.D. pneumatic tubing for the space pressurization control to the bottom fitting. Route the opposite end of the tubing to a suitable location inside the building.
This location should be the largest open area that will not be affected by sudden static pressure changes.
Remove Evaporative Condenser Fan Shipping Brackets
To remove shipping brackets
Important:
Remove fan shipping brackets before startup. Failure to remove brackets could result in fan damage.
Evaporative condensers are shipped with fan shipping brackets to reduce damage caused by vibration during shipment. The fan shipping brackets must be removed prior to unit startup.
To remove the shipping brackets start from the side opposite to the drain actuator
1.
Loosen the screw for the bracket that holds the inlet louvers below the door side.
2. Remove inlet louvers and set to the side.
Note: Service technician may need to step on the horizontal surface of FRP coated base.
Step with care.
3. Unscrew the bolt in the middle of the door. Keep the bolt in a safe place.
4. Lift one door with handle until it touches the top. Swivel bottom of door to remove it from the door opening and set it to the side.
5. Slide and remove the middle mist eliminator section so that the shipping bracket is visible.
6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should drop down but still remain engaged with a hook on the bracket.
7.
Go to the other side of the unit and follow the procedure for inlet louver and door removal
(see steps 1 - 6).
8. Hold the bracket with one hand and remove remaining two screws.
9. Remove the bracket and all the removed screws from the unit.
Important:
Make sure there are no screws remaining in the coil area.
10. Reinstall inlet louvers, mist eliminators and louvers.
Check that the direction of arrow on the inlet louver is correct.
54 RT-SVX36G-EN
Installation
Evaporative Condenser Make-up Water and Drain Line Installation
Make-up Water and Drain Lines
Water Supply Source
The supply line should be designed to provide a minimum supply of water within customary domestic supply pressures, 35 to 60 psig; dynamic pressure (measured with the valve open) which will allow approximately 30 GPM to enter the sump through the makeup water valve, when the sump is empty. The unit uses about 2-4 GPM. Attach a hand valve at the inlet for use during inspection and maintenance; an inlet strainer is recommended as well. Make-up water inlet connection is a ¾” PVC slip connector. Care must be taken to ensure the water line upstream of the water solenoid valve will not freeze. Insulating the line and utilizing heat tape is recommended if ambient temperatures below 32° F are expected.
Water Quality
Overall performance of any water-cooled device can be affected by suspended particulates, mineral concentration, trash and debris resulting in clogging and heat transfer loss. The evaporativecooled condenser is designed to greatly minimize problems with these impurities. However, float valves and solenoid valves are used to control the incoming water. If the incoming water contains contaminants, sand or other objects, an incoming line strainer with a 80 to 100 mesh screen is required. The inlet line should be flushed prior to connection to the unit, whether or not there is a strainer.
Note: Backflow preventer to be field provided and installed by others.
Water Drain Schedule 80 PVC pipe of 1¼” is normally adequate for sump water drain. Periodically, the sump is emptied and flushed to eliminate accumulated dirt, debris, and minerals.
Concentration of these foreign substances will increase as the system operates. The evaporative process releases essentially pure water vapor into the atmosphere, leaving the impurities behind that accumulate in the sump. Although these impurities are present in the original make-up water, their concentration will be higher in the sump discharge. Care and judgment should be exercised when selecting a discharge site.
Local Site Discharge
Rooftop or simple storm sewer discharge is generally acceptable. Do not routinely direct the sump discharge onto an area where these higher concentrations will adversely affect that area, i.e. continued sump discharge into a flower bed for example, where the input water contains CaCO3
(lime) will eventually decrease the pH of the soil.
Sewer Discharge
The quantities of mineral and debris flushed are actually very small, and do not cause problems when diluted in normal sewer flow. However, local, state or federal standards and restrictions must be followed in any given locality
Make Up Water Solenoid Valve
This valve is controlled by the UCM based on water level in the sump, as well as whether a call for mechanical cooling exists. During low ambient temperatures, the solenoid valve will be deenergized preventing water from further filling sump. The sump drain valve opens to empty sump of water. Operation can be extended to 10 deg by providing an optional sump heater.
Drain Valve
The drain valve is shipped to “drain during power loss conditions”. If “hold during power loss
conditions” is desired, refer to “Evaporative Condenser Drain Valve Setup” on page 98.
RT-SVX36G-EN 55
Installation
Figure 23. Pressure sensing
Outside Air Sensing Kit
Duct, Space and Return Plenum Pressure Transducer Tubing Schematic
Return Plenum
Transducer
Sensing Tube to Return
Plenum
56
Duct and Space Static Pressure
Control Component Layout
(O/A Sensor)
Return Plenum
Sensing Tube
Connects Here
Return Fan Plenum Pressure
Control Component Layout
If equipped with Return Fan and
Statitrac, Statitrac Static Reference
Tubing Connects here
Return Plenum
Return Plenum
RT-SVX36G-EN
Installation
Gas Heat Units (SFH_)
All internal gas piping is factory-installed and pressure leak-tested before shipment. Once the unit is set into place, the gas supply line must be field-connected to the elbow located inside the gas heat control compartments.
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury.
When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure regulator on the cylinder to prevent excessively high unit pressures. Never pressurize unit above the maximum recommended unit test pressure as specified in applicable unit literature. Failure to properly regulate pressure could result in a violent explosion, which could result in death or serious injury or equipment or property-only-damage.
Access holes are provided on the unit as illustrated in
to accommodate a side or
bottom pipe entry on 20 through 89 Ton units and in Figure 12, p. 40
on 90-130 Ton units. Following the guidelines listed below will enhance both the installation and operation of the furnace.
Note: In the absence of local codes, the installation must conform with the American National
Standard Z223-1a of the National Fuel Gas Code, (latest edition).
1.
To assure sufficient gas pressure at the unit, use Table 16 as a guide to determine the
appropriate gas pipe size for the unit heating capacity listed on the unit's nameplate.
2. If a gas line already exist, verify that it is sized large enough to handle the additional furnace capacity before connecting to it.
3. Take all branch piping from any main gas line from the top at 90 degrees or at 45 degrees to prevent moisture from being drawn in with the gas.
4. Ensure that all piping connections are adequately coated with joint sealant and properly tightened. Use a piping compound that is resistant to liquid petroleum gases.
5. Provide a drip leg near the unit.
6. Install a pressure regulator at the unit that is adequate to maintain 7" w.c. for natural gas while the furnace is operating at full capacity.
Note: Gas pressure in excess of 14" w.c. or 0.5 psig will damage the gas train.
Failure to use a pressure regulating device will result in incorrect gas pressure. This can cause erratic operation due to gas pressure fluctuations as well as damage the gas valve.
Over sizing the regulator will cause irregular pulsating flame patterns, burner rumble, potential flame outages, and possible gas valve damage.
If a single pressure regulator serves more than one rooftop unit, it must be sized to ensure that the inlet gas pressure does not fall below 7" w.c. with all the furnaces operating at full capacity. The gas pressure must not exceed 14" w.c. when the furnaces are off.
7.
Provide adequate support for all field installed gas piping to avoid stressing the gas train and controls.
8. Leak test the gas supply line using a soap-and-water solution or equivalent before connecting it to the gas train.
9. Check the supply pressure before connecting it to the unit to prevent possible gas valve damage and the unsafe operating conditions that will result.
RT-SVX36G-EN 57
Installation
Note: Do not rely on the gas train shutoff valves to isolate the unit while conducting gas pressure/ leak test. These valves are not designed to withstand pressures in excess of 14" w.c. or 0.5 psig.
Connecting the Gas Supply Line to the Furnace Gas Train
Follow the steps below to complete the installation between the supply gas line and the furnace.
through
Figure 27 for the appropriate gas train configuration.
1.
Connect the supply gas piping using a “ground-joint” type union to the furnace gas train and check for leaks.
2. Adjust the inlet supply pressure to the recommended 7" to 14" w.c. parameter for natural gas.
3. Ensure that the piping is adequately supported to avoid gas train stress.
Table 16. Sizing Natural Gas Pipe Mains and Branches
Gas Supply
Pipe Run (ft)
10
60
70
80
90
20
30
40
50
100
125
150
175
200
1-1/4"
Pipe
1050
400
370
350
320
730
590
500
440
305
275
250
225
210
1-1/2"
Pipe
1600
Gas Input (Cubic Feet/Hour)*
2"
Pipe
3050
2-1/2"
Pipe
4800
1100
890
760
670
610
560
530
490
460
410
380
350
320
2100
1650
1450
1270
1150
1050
990
930
870
780
710
650
610
3300
2700
2300
2000
1850
1700
1600
1500
1400
1250
1130
1050
980
3"
Pipe
8500
5900
4700
4100
3600
3250
3000
2800
2600
2500
2200
2000
1850
1700
4"
Pipe
17500
12000
9700
8300
7400
6800
6200
5800
5400
5100
4500
4100
3800
3500
Table 17. Specific Gravity Multipliers
Specific Gravity
0.50
0.55
0.60
0.65
Multiplier
1.10
1.04
1.00
0.96
58 RT-SVX36G-EN
Installation
Table 18. Modulating Gas Heat Settings
Heater Size (MBH)
500
850
1000
Gas Orifice
#21
#H
#N
Natural Gas
Full Modulation Partial Modulation
Air Damper
Actuator Voltage
Range (VDC)
Air Damper
Actuator Voltage
Range (VDC)
7 - 10
6 - 10
5 - 10
7 - 9.7
6 - 8.7
5 - 8.7
Valve Actuator
Left (Coarse)
Setting
2.3
1.3
0.9
Right (Fine)
Setting
-1
-1
0
Heater Size (MBH) Gas Orifice
Full Modulation Partial Modulation
Air Damper
Actuator Voltage
Range (VDC)
LP
Air Damper
Actuator Voltage
Range (VDC)
Valve Actuator
Left (Coarse)
Setting
Right (Fine)
Setting
500
850
#34 / #53
#32
7 - 10
6 - 10
7 - 9.7
6 - 8.7
6
3.2
1
1
1000 #29 5 - 10 5 - 8.7
1.9
0
Note:
Valve actuator settings are approximate and may require “fine tuning” to properly set. Right (fine) settings given are in notches from the “zero” midpoint location on sight gage.
Table 19. Gas Heating Capacity Altitude Correction Factors
Sea Level - 2000 2001 - 2500 2501 - 3500
Altitude (Ft.)
3501 - 4500 4501 - 5500
Capacity
Multiplier
1.00
.92
.88
.84
Note:
Correction factors are per AGA Std. 221.30 - 1964, Part VI, 6.12. Local codes may supersede.
.80
5501 - 6500
.76
6501 - 7500
.72
Notes:
1. If more than one unit is served by the same main gas supply, consider the total gas input (cubic feet/hr.) and the total length when determining the appropriate gas pipe size.
2. Obtain the Specific Gravity and BTU/Cu.Ft. from the gas company.
3. The following example demonstrates the considerations necessary when determining the actual pipe size.
Example: A 40' pipe run is needed to connect a unit with a 500 MBH furnace to a natural gas supply having a rating of 1,000 BTU/Cu.Ft. and a specific gravity of 0.60
Cu.Ft/Hour = Furnace MBH Input
Gas BTU/Cu.Ft. X Multiplier (
)
Cu.Ft/Hour = 500
4.
Table 16 indicates that a 1-1/4” pipe is required.
Figure 24. Unit Gas Trains (Natural Gas) 235 and 350 MBH
RT-SVX36G-EN 59
Installation
Figure 25. Unit Gas Trains (Natural Gas) 500 and 850 MBH
Figure 26. Unit Gas Trains (Natural Gas) 1000 MBH
60 RT-SVX36G-EN
Figure 27. Modulating 500 - 1000 MBH
Installation
Flue Assembly Installation
1.
Locate the flue assembly and the extension (refer to Figure 28
for extension usage) in the ship with section of the unit.
2. Install the flue extension onto the flue assembly as shown in
3. Slide the pipe clamp onto the heater flue tube located inside the heater compartment.
4. Insert the tube on the flue assembly into the hole located in the vertical support for the heat section.
5. Butt both flue tube sections together and center the pipe clamp over joint.
6. Using the pre-punch holes in the flue assembly, extension, and the vertical support, install the
appropriate number of mounting brackets. Refer to Figure 28
for details.
RT-SVX36G-EN 61
Installation
Figure 28. Flue Assembly
Hot Water Heat Units (SLH_)
Hot water heating coils are factory installed inside the heater section of the unit. Once the unit is set into place, the hot water piping and the factory provided three way modulating valve must be installed. The valve can be installed inside the heat section or near the unit. If the valve is installed in a remote location, use field supplied wiring to extend the control wires from the heater section to the valve. Two access holes are provided in the unit base as illustrated in
.
Following the guidelines listed below will enhance both the installation and operation of the “wet heat” system.
illustrate the recommended piping configuration for the hot water coil.
Table 20 lists the coil connection sizes.
Note: The valve actuators are not waterproof. Failure to protect the valve from moisture may result in the loss of heating control.
1.
Support all field-installed piping independently from the heating coil.
2. Use swing joints or flexible connectors adjacent to the heating coil. (These devices will absorb the strains of expansion and contraction).
3. All return lines and fittings must be equal to the diameter of the “outlet” connection on the hot water coil.
4. Install a “Gate” type valve in the supply branch line as close as possible to the hot water main and upstream of any other device or takeoff.
5. Install a “Gate” type valve in the return branch line as close as possible to the return main and down stream of any other device.
6. Install a strainer in the hot water supply branch as shown in Figure 29 and
.
62 RT-SVX36G-EN
Installation
7.
Install the 3-way valve in an upright position, piped for valve seating against the flow. Ensure that the valve's location lends itself to serviceability.
8. The Type “W” hot water coil used in SLHL units is self-venting only when the tube water velocity exceeds 1.5 feet per second (fps). If the tube velocity is less than 1.5 feet per second, either: a. install an automatic air vent at the top of the return header, using the tapped pipe connection; or, b. vent the coil from the top of the return header down to the return piping. At the vent connection, size the return piping to provide sufficient water velocity.
9. Install a “Globe” type valve in the Bypass line as shown in Figure 29
and
Table 20. Connection Sizes for Hot Water and Steam Coil
(a)
Coil Connections
(diameter in inches)
Unit Model and Size
Heat Section
Capacity
(b)
Supply Return
SLH*-20 to 130
SSHL-20 to 36
SSHL-40 to 89
(c)
SSHK-90 to 130
High or Low Heat
High or Low Heat
High Heat Low Heat
Low Heat
(c)
2-1/2"
3"
3"
2-1/2"
1-1/4"
1-1/2"
1-1/2” 1”
(a) Type W coils—with center offset headers—are used in SLH_ units; Type NS coils are used in SSH_ units.
(b) See Digit 9 of the unit model number to determine the heating capacity.
(c) SSH_ - 40 to 89 Ton units have multiple headers.
Steam Heat Units (SSH_)
Steam heating coils are factory installed inside the heater section of the unit. The coils are pitched, within the units, to provide the proper condensate flow from the coil. To maintain the designed degree of pitch for the coil, the unit must be level.
Once the unit is set into place, the steam piping and the factory provided two way modulating valve must be installed. The valve can be installed inside the heater section or near the unit. If the valve is installed in a remote location, use field supplied wiring to extend the control wires from the heater section to the valve. Two access holes are provided in the unit base as illustrated in
.
Following the guidelines listed below will enhance both the installation and operation of the “wet heat” system.
illustrate the recommended piping configurations for the steam coil.
Table 20 lists the coil connection sizes.
Note: The valve actuators are not waterproof. Failure to protect the valve from moisture may result in the loss of heating control.
1.
Support all field-installed piping independently from the heating coil.
2. Use swing joints or flexible connectors adjacent to the heating coil. (These devices will absorb the strains of expansion and contraction.)
3. Install the 2-way valve in an upright position. Ensure that the valve's location lends itself to serviceability.
4. Pitch the supply and return steam piping downward 1" per 10' of run in the direction of flow.
5. All return lines and fittings must be equal to the diameter of the “outlet” connection on the steam coil(s). If the steam trap connection is smaller that the coil “outlet” diameter, reduce the pipe size between the strainer and the steam trap connections only.
RT-SVX36G-EN 63
Installation
6. Install a 1/2” 15 degree swing-check vacuum breaker at the top of the return coil header using the tapped pipe connection. Position the vacuum breaker as close to the coil as possible.
Note: Vacuum breakers should have extended lines from the vent ports to the atmosphere or connect each vent line to the return pipe on the discharge side of the steam traps.
7.
Install a “Gate” type valve in the supply branch line as close as possible to the steam main and upstream of any other device.
8. Install a “Gate” type valve in the return branch line as close as possible to the condensate return main and downstream of any other device.
9. Install a strainer as close as possible to the inlet of the control valve and steam trap(s).
10. Steam trap selection should be based on the maximum possible condensate flow and the recommended load factors.
11. Install a Float-and-Thermostatic (FT) type trap to maintain proper flow. They provide gravity drains and continuous discharge operation. FT type traps are required if the system includes either; a. an atmospheric pressure/gravity condensate return; or, b. a potentially low pressure steam supply.
12. Position the outlet or discharge port of the steam trap at least 12" below the outlet connection on the coil(s). This will provide adequate hydrostatic head pressure to overcome the trap losses and assure complete condensate removal.
40 through 130 Ton units
Utilizes two steam coils stacked together. These two coils must be piped in a parallel arrangement.
The steps listed below should be used in addition to the previous steps. Figure 32 illustrates the
recommended piping configuration for the steam coils.
Figure 29. Hot Water Piping (20 - 75 Ton)
64 RT-SVX36G-EN
Figure 30. Hot Water Piping (90 - 130 Ton)
Figure 31. Steam Coil Piping (20 - 36 Ton)
Installation
RT-SVX36G-EN 65
Installation
Figure 32. Steam Coil Piping (40 - 130 Ton)
Disconnect Switch External Handle
(Factory Mounted Option)
Units ordered with the factory mounted disconnect switch comes equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle locations and its three positions are shown below;
“ON” - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit.
“OFF” - Indicates that the disconnect switch is open, interrupting the main power supply to the unit controls.
“OPEN COVER/RESET” - Turning the handle to this position releases the handle from the disconnect switch, allowing the control panel door to be opened.
Once the door has been opened, it can be closed with the handle in any one of the three positions outlined above, provided it matches the disconnect switch position. See
.
The handle can be locked in the “OFF” position. While holding the handle in the “OFF” position, push the spring loaded thumb key, attached to the handle, into the base slot. Place the lock shackle between the handle and the thumb key. This will prevent it from springing out of position.
66 RT-SVX36G-EN
Installation
supply power wiring is properly sized and installed, follow the guidelines outlined below.
Figure 33. Disconnect Switch Handle Positions
RT-SVX36G-EN
Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Verify that the power supply available is compatible with the unit's nameplate rating for all components. The available power supply must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the 3-phase power supply to the unit.
CAUTION
Hot Surface!
Surface temperatures may exceed 300°F (150°C) on condensing unit and carbon tank. To avoid possible skin burns, stay clear of these surfaces. If servicing is required allow surfaces to cool or wear protective gear. Failure to do so could result in minor to moderate injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
67
Installation
Electric Heat Units (SEH_)
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
SEHL (20 through 89 Ton) electric heat units operating on 200/230 volts require two power supplies as illustrated in
Figure 34 . Unless the unit was ordered with the optional factory mounted non-
fused disconnect switches, two field-supplied disconnect switches must be installed. The power wires for the electric heat is routed into the electric heat control panel using the thru-the-base access provided in the heating section. Refer to the appropriate illustration in
Base layout and Electrical Entrance diagram), for dimensional data.
On 20-130 ton units operating on 460/575 volts, only one power entry is required, as illustrated in
Use the information provided in Table 21, p. 71 and the “Power Wire Sizing & Protection Device
Equations”, to determine the appropriate wire size and Maximum Over current Protection for the heaters/unit.
Note: Each power supply must be protected from short circuit and ground fault conditions. To comply with NEC, protection devices must be sized according to the “Maximum Over current Protection” (MOP) or “Recommended Dual Element” (RDE) fuse size data on the unit nameplate.
Provide grounding for the supply power circuit in the electric heat control box.
Main Unit Power Wiring
68
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Figure 37, p. 84 lists the field connection wire ranges for both the main power terminal block 1TB1
and the optional main power disconnect switch 1S14. Table 21, p. 71 lists the component electrical data for 20 through 130 ton units. The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to the “Power Wire Sizing & Protection
Device Equations”, for determining; a. the appropriate electrical service wire size based on “Minimum Circuit Ampacity” (MCA), b. the “Maximum Over current Protection” (MOP) device, c. the “Recommended Dual Element fuse size” (RDE).
1.
If the unit is not equipped with an optional factory installed non-fused disconnect switch, a field supplied disconnect switch must be installed at or near the unit in accordance with the National
Electrical Code (NEC latest edition). Refer to the “Power Wire Sizing & Protection Device
Equations” (DSS calculation), for determining the correct size.
2. Location for the electrical service entrance is illustrated in
Figure 10, p. 36 . Complete the unit's
power wiring connections onto either the main terminal block 1TB1, or the factory mounted
RT-SVX36G-EN
Installation
non-fused disconnect switch 1S14, inside the unit control panel. Refer to the customer connection diagram that shipped with the unit for specific termination points.
3. Provide proper grounding for the unit in accordance with local and national codes.
Figure 34. Typical Field Power Wiring (20 - 89 Ton)
RT-SVX36G-EN 69
Installation
Figure 35. Typical Field Power Wiring (90 - 130 Ton)
70
Figure 36. Customer Connection Wire Range
RT-SVX36G-EN
RT-SVX36G-EN
Installation
Table 21. Compressor electrical service sizing data (20 - 130 ton)
(a)
Tonnage (AC/EC)
20 (Std)
200V
No. of
Compressors RLA
2 41.4
LRA
267
20/24 (Hi)
25 (Std)
25/29 (Hi)
30 (Std)
30/36 (Hi)
40 (Std)
40/48 (Hi)
50 (Std)
50(Hi)
55 (Std)/59 (Hi) 4
2
2
2
4
4
2
2
1
1
1
2
1
1
2
1
60 (Std)
60/73 (Hi)
70/80(Std)
75 (Std)
75/89 (Hi)
90 (Std & High)
2
4
2
2
4
2
2
4
105 (Hi)
115 (Std)
2
2
2
2
N/A
N/A
N/A
N/A
130 (Std) 4 N/A
(a) Evaporative Condenser Units only available in 460V
51.9
51.9
56.9
60.5
83.9
60.5
83.9
N/A
31.3
37.3
37.3
41.4
41.4
47
47
47
41.4
41.4
47
41.4
51.9
51.9
51.9
56.9
485
320
485
N/A
315
315
351
320
N/A
N/A
N/A
N/A
N/A
267
304
304
304
203
267
267
267
315
315
315
351
267
267
304
267
230V
RLA
35.5
47
47
48.8
52
74.5
52
74.5
N/A
N/A
N/A
N/A
N/A
N/A
30.4
31.8
31.8
35.5
35.5
42.3
42.3
42.3
35.5
35.5
42.3
35.5
47
47
47
48.8
LRA
267
485
320
485
N/A
315
315
351
320
N/A
N/A
N/A
N/A
N/A
267
304
304
304
203
267
267
267
315
315
315
351
267
267
304
267
460V
RLA
18.6
22.2
22.2
25.5
25.4
37.2
25.4
37.2
36
36
45
36
45
45
13.1
15.9
15.9
18.6
18.6
20.2
20.2
20.2
18.6
18.6
20.2
18.6
22.2
22.2
22.2
25.5
LRA
142
215
160
215
215
158
158
197
160
215
260
215
260
260
142
147
147
147
98
142
142
142
158
158
158
197
142
142
147
142
575V
RLA
15.8
19.2
19.2
23.1
20.3
29.8
20.3
29.8
29
29
36
29
36
36
11.9
14.5
14.5
15.8
15.8
17.1
17.1
17.1
15.8
15.8
17.1
15.8
19.2
19.2
19.2
23.1
LRA
103
175
135
175
175
136
136
146
135
175
210
175
210
210
103
122
122
122
84
103
103
103
136
136
136
135
103
103
122
103
71
Installation
Table 22. Electrical service sizing data — motors — 20-130 tons
200
FLA
Nominal
Tons
20
25
30
40
8.2
12.3
12.3
16.4
50, 55
60
70
75
90
24.6
24.6
24.6
24.6
N/A
105 N/A
230
FLA
Nominal Voltage
460
FLA
Air-Cooled Condenser Fan Motor
8.2
3.6
12.3
12.3
16.4
24.6
24.6
24.6
24.6
N/A
N/A
5.4
5.4
7.2
10.8
10.8
10.8
10.8
14.4
18.0
115 N/A
130 N/A
Motor Horsepower
N/A 18.0
N/A 21.6
Supply/Exhaust/Return
2
Fan Motor
3
5
7½
10
15
20
25
30
40
(a)
11.0
15.2
21.5
29.0
40.7
56.1
70.5
85.5
N/A
8.6
13.2
18.8
25.2
37.8
49.4
62.0
73.2
N/A
Note:
Return fan motors are available in 3-20 Hp.
(a) 40 Hp motor available as standard in 460 & 575 volt only.
4.3
6.6
9.4
12.6
18.9
24.7
31.0
36.6
47.6
3.8
5.4
7.5
10.1
15.1
19.6
24.5
29.2
39.0
575
FLA
2.8
4.2
4.2
5.6
8.4
8.4
8.4
8.4
11.2
14.0
14.0
16.8
72 RT-SVX36G-EN
RT-SVX36G-EN
Installation
Table 23. Electrical service sizing data —electric heat module (electric heat units only) —
20-130 tons
Voltage
Module kW
30
200
FLA
83.3
230
FLA
72.2
50
70
90
110
138.8
194.3
249.8
305.3
120.3
168.4
216.5
264.6
130
150
170
190
Note:
Electric heat FLA are determined at 208, 240, 480 and 600 volts.
460
FLA
36.1
60.1
84.2
108.3
132.3
156.4
180.4
204.5
228.5
575
FLA
28.9
48.1
67.4
86.6
105.9
125.1
144.3
163.6
182.8
Table 24. Electrical service sizing data evaporative condenser - All tonnages (24-89T)
Qty
1
Condenser Fan
HP
5.4
FLA
5.9
Qty
1
Sump Pump
HP
0.5
FLA
1.55
Sump Heater kW FLA
3 3.8
Table 25. Electrical service sizing data — control power transformer heating and cooling modes — 20-130 tons
Voltage Nominal Tons
(Air-cooled/
Evaporative condensing)
20,25,30/24,29,36
20,25,30/24,29,36
40,50,55,60/48,59,73
40,50,55,60/48,59,73
70,75/80,89
70,75/80,89
90,105,115,130
90,105,115,130
Digit 2
Unit
Function
A,E,L,S,X
F
A,E,L,S,X
F
A,E,L,S,X
F
E,L,S,X
F
200
8
5
5
5
8
1
4
3
230
7
4
4
4
7
1
3
2
460
3
2
2
2
3
1
2
1
575
3
2
2
2
3
1
1
1
Table 26. Electrical service sizing data — crankcase heaters
(heating mode on 460/575 volt only) — 20-130 tons
Nominal Tons
(Air-cooled/
Evaporative condensing)
20-30/24-36
40-60/48-73
70-75/80-89
90-105
115-130
(Add) FLA
1
3
4
2
3
73
Installation
Table 27. Voltage utilization range
Unit Voltage
200/60/3
230/60/3
380/50/3
415/50/3
460/60/3
575/60/3
Voltage
Utilization Range
180-220
207-253
342-418
373-457
414-506
517-633
Power Wire Sizing and Protection Device Equations
To correctly size the main power wiring for the unit, use the appropriate calculation(s) listed below.
Read the load definitions that follow and use Calculation #1 for determining the MCA (Minimum
Circuit Ampacity), MOP (Maximum Over current Protection), and RDE (Recommended Dual
Element fuse size) for SAH_ (Cooling Only) units, SXH_ (Extended Casing) units, SLH_ and SSH_
(Cooling with Wet Heat) units, and SFH_ (Cooling with Gas Heat) units Use Calculation #2 for SEH_
(Cooling with electric Heat) units.
Load Definitions:
LOAD 1 = CURRENT OF THE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR)
LOAD 2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS
LOAD 3 = CURRENT OF ELECTRIC HEATERS
LOAD 4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE
CONTROL POWER TRANSFORMER FOR ALL MODES
20 - 40 Ton Units, add 3 FL Amps
50 - 75 Ton Units, add 6 FL Amps
90 - 130 Ton Units, add 8 FL Amps
CRANKCASE HEATERS FOR HEATING MODE 460/575V ONLY
20 - 30 Ton Units, Add 1 Amp
40 - 60 Ton Units, Add 2 Amps
70 - 75 Ton Units, Add 3 Amps
90 - 130 Ton Units, Add 4 Amps
• Calculation #1 - SAH_, SXH_, SLH_, SSH_, and SFH_ Units.
MCA = (1.25 x LOAD 1) + LOAD 2 + LOAD 4 MOP = (2.25 x LOAD 1) + LOAD 2 + LOAD 4
Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240 - 6, select the next lower standard fuse rating.
Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed
800 amps.
RDE = (1.5 x LOAD1) + LOAD2 + LOAD4
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240 - 6, select the next higher standard fuse rating.
Note: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value.
• Calculation #2 - Rooftop units with Electric Heat (SEH_ 20 - 130 Tons) a. Single Source Power (380V, 415V, 460V, and 575V)
74 RT-SVX36G-EN
RT-SVX36G-EN
Installation
To arrive at the correct MCA, MOP, and RDE values for these units, you must perform two sets of calculations. First calculate the MCA, MOP, and RDE values as if the unit was operating in the cooling mode (use the equations given in Calculation #1 above). Then calculate the MCA, MOP, and
RDE values as if the unit was operating in the heating mode as follows. (Keep in mind when determining LOADS that the compressors do not operate while the unit is in the heating mode).
For units using heaters less than 50 Kw: MCA = 1.25 x (LOAD 1 + LOAD 2 + LOAD 4) + (1.25 x LOAD 3)
For units using heaters equal to or greater than 50 Kw: MCA = 1.25 x (LOAD 1 + LOAD 2 + LOAD
4) + LOAD 3
The nameplate MCA value will be the larger of the cooling mode MCA value or the heating mode
MCA value calculated above.
MOP = (2.25 x LOAD 1) + LOAD 2 + LOAD 3 + LOAD 4
The selected MOP value will be the larger of the cooling mode MOP value or the heating mode MOP value calculated above.
Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240 - 6, select the next lower standard fuse rating.
Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed
800 amps.
RDE = (1.5 x LOAD 1) + LOAD 2 + LOAD 3 + LOAD 4
The selected RDE value will be the larger of the cooling mode RDE value or the heating mode RDE value calculated above.
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240 - 6, select the next higher standard fuse rating.
Note: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value.
b. Dual Source Power units (200V and 230V)
These units will have two circuit values shown on the nameplate. The first circuit value will be the refrigeration (cooling mode) values calculated using calculation #1 above. The second set of circuit values shown on the nameplate will be for the electric heating circuit as follows.
MCA = (1.25 x LOAD 3) MOP = (1.25 x LOAD 3)
Select a fuse rating for the electric heating circuit that’s equal to the MOP value obtained in the equation above. If the MOP value does not equal a standard fuse size as listed in NEC 240 - 6, select the next lower standard fuse rating (see note below for exception).
Note: If selected MOP is less than the MCA obtained in the equation above, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed 800 amps.
RDE = LOAD 3
Select a fuse rating for the electric heating circuit that’s equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240 - 6, select the next higher standard fuse rating.
Note: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value.
Disconnect Switch Sizing (DSS)
• Calculation #1 - SX, SF, SA, SL, or SS Single Power Source Units
DSS = 1.15 X (LOAD 1 + LOAD 2 + LOAD 4)
• Calculation #2 - All SEH_ Single Power Source Units
DSS = 1.15 X (LOAD 3 + Supply Fan FLA + Exhaust Fan FLA)
75
Installation
PLUS
DSS = 1.15 X (LOAD 1 + LOAD 2 + LOAD 4)
Use the larger value of the two calculations to size the electrical service.
• Calculation #3 - SEHL (200/230 Volt) 20 - 75 Ton Dual Power Source Units
DSS = 1.15 X LOAD3 for the Electric heater AND Calculation #1 for the Refrigeration Components
Field Installed Control Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
The Rooftop Module (RTM) must have a mode input in order to operate the rooftop unit. The flexibility of having several system modes depends upon the type of sensor and/or remote panel selected to interface with the RTM. An overall layout of the various control options available for a
Constant Volume application, with the required number of conductors for each device, is illustrated
Figure 37, p. 85 illustrates the various control options with the required number
of conductors for a Variable Air Volume application.
Note: All field wiring must conform to NEC guidelines as well as state and local codes.
The various field installed control panels, sensors, switches, and contacts discussed in this section require both AC and DC consideration. These diagrams are representative of standard applications and are provided for general reference only. Always refer to the wiring diagram that shipped with the unit for specific electrical schematic and connection information.
Controls Using 24 VAC
Before installing any connecting wiring, refer to Figure 9, p. 34 and
Figure 10, p. 36 for the electrical
access locations provided on the unit and Table 28 for AC conductor sizing guidelines, and;
1.
Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit's termination point does not exceed three (3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring.
Table 28. AC Conductors
Distance from unit to control
000-460 feet
461-732 feet
733-1000 feet
Recommended wire size
18 gauge
16 gauge
14 gauge
76 RT-SVX36G-EN
Installation
4. Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring.
Controls using DC Analog Input/Outputs
Before installing any connecting wiring between the unit and components utilizing a DC analog
input/output signal, refer to the appropriate illustration in Figure 9, p. 34 -
for the electrical access locations provided on the unit and
Table 29 for conductor sizing guidelines and;
1.
Use standard copper conductor thermostat wire unless otherwise specified.
2. Ensure that the wiring between the controls and the unit's termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run.
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls.
Table 29. DC Conductors
Distance from unit to control
000-150 feet
151-240 feet
241-385 feet
386-610 feet
611-970 feet
Recommended wire size
22 gauge
20 gauge
18 gauge
16 gauge
14 gauge
3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.
Units equipped with a Trane Communication Interface (TCI), BACnet Communication Interface
(BCI), or LonTalk communication Interface (LCI) option which utilizes a serial communication link;
• Must be 18 AWG shielded twisted pair cable (Belden 8760 or equivalent).
• Must not exceed 5,000 feet maximum for each link.
• Must not pass between buildings.
Constant Volume System Controls
Remote Panel w/o NSB - (BAYSENS110*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto) with four system status LED's. It is a manual or automatic changeover control with dual setpoint capability. It can be used with a remote zone sensor BAYSENS077*. Refer to
for the Temperature vs. Resistance coefficient.
Zone Temperature Control Zone Panel (5U68) - (BAYSENS108*)
This electronic sensor features four system switch settings (Heat, Cool, Auto, and Off) and two fan settings (On and Auto). It is a manual or automatic changeover control with dual setpoint capability.
Variable Air Volume and Constant Volume System Controls
Remote Panel w/o NSB (5U59) - (BAYSENS021*)
The remote panel w/o Night setback has a system switch as well as a S/A temperature setpoint indicator, a local sensor, and four LED's. These features allow the operator to control system operation, and monitor unit operating status from a remote location. Use the installation instructions that shipped with the panel to install it, and the unit's field wiring diagram to connect it to the unit.
RT-SVX36G-EN 77
Installation
78
Discharge Temperature Control Changeover Contacts (5K87)
These contacts are connected to the RTM when daytime heating on Discharge Temperature Control units with internal or external hydronic heat is required. Daytime (occupied) heating switches the system to a Zone Temperature Control type mode of operation. Refer to the unit wiring diagram for the field connection terminals in the unit control panel. The switch must be rated at 12 ma @
24 VDC minimum.
Remote Human Interface Module (5U66)
The remote Human Interface module enables the operator to set of modify the operating parameters of the unit using it's 16 key keypad and view the operating status of the unit on the 2 line, 40 character LCD screen without leaving the building. However, the Remote Human Interface module can not be used to perform any service functions.
One remote panel is designed to monitor and control up to four units providing each of the units are equipped with an IPCB module. Use the installation instructions that shipped with the module
to install it, and the appropriate illustrations in Figure 34, p. 69
to connect it to the unit.
Remote Zone Sensor (BAYSENS073*)
This electronic analog sensor features remote zone sensing and timed override with override cancellation. It is used when the RTM has been programmed as the source for zone temperature control. Refer to
Table 30 for the Temperature vs. Resistance coefficient.
Remote Zone Sensor (BAYSENS074*)
This electronic analog sensor features single setpoint capability and timed override with override cancellation. It is used with a Trane Integrated Comfort
TM
system. Refer to Table 30 for the
Temperature vs. Resistance coefficient.
Remote Zone Sensor (5RT16, 5U57, and 5U69) (BAYSENS016*)
This bullet type analog Temperature sensor can be used for; outside air (ambient) sensing, return air temperature sensing, supply air temperature sensing, remote temperature sensing
(uncovered), morning warm-up temperature sensing, and for supply air temperature reset. Wiring procedures vary according to the particular application and equipment involved. When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair (Belden
8760 or equivalent). Refer to
Table 30 for the Temperature vs. Resistance coefficient.
Remote Zone Sensor (5RT16, 5U57, and 5U69) (BAYSENS077*)
This electronic analog sensor can be used with BAYSENS119* or 021A Remote Panels. When this sensor is wired to a BAYSENS119* Remote Panel, wiring must be 18 AWG Shielded Twisted Pair
(Belden 8760 or equivalent). Refer to the specific Remote Panel for wiring details.
Remote Panel w/ NSB - (BAYSENS119*)
This 7 day programmable sensor features four periods for Occupied\Unoccupied programming per day. If the power is interrupted, the program is retained in permanent memory. If power is off longer than 2 hours, only the clock and day may have to be reset.
The six programming keys located on the front panel allows selection of four system modes (Heat,
Cool, Auto, and Off), two fan modes (On and Auto). It has dual temperature selection with programmable start time capability.
The occupied cooling setpoint ranges between 40°and 80° Fahrenheit. The warm-up setpoint ranges between 50° and 90° Fahrenheit with a 2 degrees deadband. The Unoccupied cooling setpoint ranges between 45 and 98 degrees Fahrenheit. The heating setpoint ranges between 43 and 96 degrees Fahrenheit. Two liquid crystal displays (LCD) display zone temperature, temperature setpoints, week day, time, and operational mode symbols.
RT-SVX36G-EN
RT-SVX36G-EN
Installation
The DIP switches on the subbase are used to enable or disable applicable functions, i.e.; Morning
Warm-up, Economizer minimum CFM override during unoccupied status, Fahrenheit or
Centigrade, Supply air tempering, Remote zone temperature sensor, 12/24 hour time display,
Smart fan, and Computed recovery.
During an occupied period, an auxiliary relay rated for 1.25 amps @ 30 volts AC with one set of
single pole double throw contacts is activated. See Table 30 for the Temperature vs. Resistance
coefficient.
Remote Minimum Position Potentiometer (5U70) (BAYSTAT023*)
The remote minimum position potentiometer is used on units with an economizer. It allows the operator to remotely set the economizer's minimum position (which controls the amount of outside air entering the unit). Use the installation instructions that shipped with the potentiometer to install it, and the appropriate illustrations in
to connect it to the unit.
External Auto/Stop Switch (5S67)
A field supplied single pole single throw switch (5S67) may be used to shut down the unit operation. This switch is a binary input wired to the RTM. When opened, the unit shuts down immediately and can be cancelled by closing the switch. Refer to the appropriate illustrations in
or
Figure 41, p. 89 for the proper connection terminals in the unit control panel. The
switch must be rated for 12 ma @ 24 VDC minimum.
VOM Contacts (5K90, 5K91, 5K92, 5K93, 5K94)
If the unit is equipped with a Ventilation Override Module (VOM), a number of special functions can be specified by the building owner or contractor. These functions can include, but are not limited to; (1) Unit Off, (2) Pressurization, (3) Exhaust/Return, (4) Purge, and (5) Purge with Duct Pressure
Control. They are controlled by binary inputs wired to the VOM. These functions can be initiated by; a toggle switch, a time clock, or an ICSTM output. The switch must be rated for 12 ma @ 24 VDC minimum. The following preset sequences can be modified by the customer;
• VOM Mode “A” Priority 1 - Unit Off:
– Supply fan - OFF
– Inlet vanes/VFD - 0% (if equipped)
– Exhaust/Return fan - OFF, Exhaust/Return dampers Closed
– O/A dampers - Closed
– Heat - All stages OFF, Modulating Heat output at 0 VDC
– Occupied/Unoccupied output - De-energized (Occupied)
– VO Relay - Energized
– Pre-heater State - Off (if equipped)
• VOM Mode “B” Priority 2 - Pressurize:
– Supply fan - ON
– Inlet Vanes/VFD - 100% (if equipped)
– Exhaust/Return fan - OFF, Exhaust/Return dampers - Closed
– O/A dampers - Open
– Heat - All stages OFF, Modulating Heat output at 0 VDC
– Occupied/Unoccupied output - Energized (Unoccupied)
– VO Relay - Energized
– Pre-heater State - Off (if equipped)
• VOM Mode “C” Priority 3 - Exhaust/Return:
79
Installation
– Supply fan - OFF
– Inlet Vanes/VFD - 0% (if equipped)
– Exhaust/Return fan - ON, Exhaust/Return dampers - Open
– O/A dampers - Closed
– Heat - All stages OFF, Modulating Heat output at 0 VDC
– Occupied/Unoccupied output - De-energized (Occupied)
– VO Relay - Energized
– Pre-heater State - Off (if equipped)
• VOM Mode “D” Priority 4 - Purge:
– Supply fan - ON
– Inlet Vanes/VFD - 100% (if equipped)
– Exhaust/Return fan - ON, Exhaust/Return dampers - Open
– O/A dampers - Open
– Heat - All stages OFF, Modulating Heat output at 0 VDC
– Occupied/Unoccupied output - Energized (Unoccupied)
– VO Relay - Energized
– Pre-heater State - Off (if equipped)
• VOM Mode “E” Priority 5 - Purge with duct pressure control:
– Supply fan - ON
– Inlet Vanes/VFD - (if equipped) Controlled by S/A Pressure Control with supply air pressure high limit disabled.
– Exhaust/Return fan - ON, Exhaust/Return dampers - Open
– O/A dampers - Open
– Heat - All stages OFF, Modulating Heat output at 0 VDC
– Occupied/Unoccupied output - Energized (Unoccupied)
– VO Relay - Energized
– Pre-heater State - Off (if equipped)
“OFF” - will appear in the Ventilation Override screen after all VOM binary inputs have been reset
(opened).
Due to codes in some areas, the definitions for some or all of the VOM modes may have to be locked into the program by the user. Once the definitions are locked, the Ventilation Override Module must be replaced in order to reprogram that sequence.
or Figure 41, p. 89 for the proper connection terminals in the unit control
panel for each of the VOM initiating device’s and the appropriate Programming, Troubleshooting
Guide (PTG Latest Edition) for programming instructions.
80 RT-SVX36G-EN
Installation
RT-SVX36G-EN
Emergency Override Definitions (with LCI-I/BCI-I module installed)
When an LCI-I/BCI-I module is installed, the user can initiate one of five (5) Emergency Override sequences that have the following predefined unit operation:
PRESSURIZE
– Supply Fan - On
– Inlet Vanes - Open (if equipped)
– Exhaust/Return Fan - Off (if equipped)
– Exhaust/Return Dampers - Closed (if equipped)
– OA Dampers - Open
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - Energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
DEPRESSURIZE
– Supply Fan - Off
– Inlet Vanes - Closed (if equipped)
– Exhaust/Return Fan - On (if equipped)
– Exhaust/Return Dampers -Open (if equipped)
– OA Dampers - Closed
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - De-energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
PURGE
– Supply Fan - On
– Inlet Vanes - Open (if equipped)
– Exhaust/Return Fan - On (if equipped)
– Exhaust/Return Dampers - Open (if equipped)
– OA Dampers - Open
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - Energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
SHUTDOWN
– Supply Fan - Off
– Inlet Vanes - Closed (if equipped)
– Exhaust/Return Fan - Off (if equipped)
81
Installation
82
– Exhaust/Return Dampers - Closed (if equipped)
– OA Dampers - Closed
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - De-energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
FIRE
– Supply Fan - Off
– Inlet Vanes - Closed (if equipped)
– Exhaust/Return Fan - Off (if equipped)
– Exhaust/Return Dampers - Closed (if equipped)
– OA Dampers - Closed
– Heat - All heat stages Off (staged gas and elec.), Hydronic
– Heat & Mod Gas Heat output at 0%.
– Occupied/Unoccupied output - De-energized
– VO Relay - Energized (with VOM module installed)
– OA Preheater State - Off (with VCM module installed)
The UCM network relies on various sensors located throughout the system to provide temperature information in the form of an analog input. All of the sensors used have the same temperature vs. resistance co-efficient and are made from Keystone Carbon D97 material with a 1 degree
Centigrade tolerance.
Table 30. Temperature vs. resistance coefficient
Temperature (°F)
Resistance
(in. 1000 Ohms) Temperature (°F)
Resistance
(in. 1000 Ohms)
-40 346.1
71 11.6
-30 241.7 72 11.31
-20 170.1 73 11.03
-10 121.4 74 10.76
-5 103 75 10.5
0 87.56 76 10.25
5 74.65 77 10
10 63.8 78 9.76
15 54.66 79 9.53
20 46.94 80 9.3
25 40.4 85 8.25
30 34.85 90 7.33
35 30.18 100 5.82
40 26.22 105 5.21
45 22.85 110 4.66
50 19.96 120 3.76
55 17.47 130 3.05
60 15.33 140 2.5
65 13.49 150 2.05
66 13.15 160 1.69
67 12.82 170 1.4
68 12.5 180 1.17
69 12.19 190 0.985
70 11.89 200 0.83
RT-SVX36G-EN
RT-SVX36G-EN
Installation
Emergency Stop Switch (5S71)
A normally closed (N.C.) switch (5S71) wired to the RTM may be used during emergency situations to shut down all unit operations. When opened, an immediate shutdown occurs. An emergency stop diagnostic is entered into the Human Interface and the unit must be manually reset. Refer to the appropriate illustrations in
or Figure 41, p. 89 for the proper connection
terminals in the unit control panel. The switch must be rated for 12 ma @ 24 VDC minimum.
Occupied/Unoccupied Contacts (5K86)
To provide Night Setback control if a remote panel with NSB (5U58) was not ordered, a field supplied contact (5K86) must be installed. This binary input provides the Occupied/Unoccupied status information of the building to the RTM. It can be initiated by a time clock, or a Building
Automation System control output. The relay’s contacts must be rated for 12 ma @ 24 VDC minimum. Refer to the appropriate illustrations in
Figure 41, p. 89 for the proper
connection terminals in the unit control panel.
Demand Limit Relay (5K89)
If the unit is equipped with a Generic BAS Module (1U51), (i.e. unit model number digit 21+ is a “K”), a normally open (N.O.) switch may be used to limit the electrical power usage during peak periods.
When demand limit is initiated, the mechanical cooling and heating operation is limited to either
50% or 100%. Demand limit can be initiated by a toggle switch closure, a time clock, or an ICSTM control output. These contacts must be rated for 12 ma @ 24 VDC minimum.
Outside Air Sensor (3RT3) - (BAYSENS016*)
This device senses the outdoor air temperature and sends this information in the form of an analog input to the RTM. It's factory installed on units with an economizer, but can be field provided/ installed and used for informational purposes on units without an economizer. Refer to the appropriate illustrations in
for the proper connection terminals in the unit control panel. Refer to
for Temperature vs. Resistance coefficient.
Generic Building Automation System (1U51)
The Generic Building Automation System (GBAS) module allows a non-Trane building control system to communicate with the rooftop unit and accepts external setpoints in form of analog inputs for cooling, heating, demand limiting, and supply air pressure parameters.
Generic Building Automation System Module (GBAS 0-5 VDC) - Provided for those cases where non-Tracer building management system is used. The GBAS module provides a binary input for
Demand Limiting, four (4) analog inputs for setpoint adjustment and five (5) relay outputs for diagnostic reporting. Inputs can use a potentiometer or 0-5 VDC signal.
Generic Building Automation System Module (GBAS 0-10 VDC) - Used to provide broad control capabilities for building automation systems other than Trane's Tracer system. The GBAS module provides a binary input for Demand Limiting, four (4) analog inputs for setpoint adjustment and four (4) analog outputs as well as one (1) relay output for diagnostic reporting. Inputs can use a potentiometer or 0-10 VDC signal.
Refer to
Figure 41 for the input wiring to the GBAS module and the various desired setpoints with
the corresponding DC voltage inputs for both VAV and CV applications.
For complete application details of the module, refer to Engineering Bulletin UN-PRB001-EN.
Wall or Duct Mount Humidity Sensor (5U108) - (BAYSENS036*)
This field-installed humidity sensor is mounted in the space or in the return air duct, sending an analog input to the RTM or ECEM. It must be ordered/installed for dehumidification control with modulating hot gas reheat, but can also be used for humidification applications.
83
Installation
Figure 37. Typical ventilation override binary output wiring diagram for 20-89 ton CV control options.
Refer to wiring notes on
.
84 RT-SVX36G-EN
Installation
Figure 37. (continued from previous page) Typical ventilation override binary output wiring diagram for 20-89 ton CV control options. Refer to wiring notes on
.
RT-SVX36G-EN 85
Installation
Figure 38. Field connection diagram notes for 20 - 89 ton CV or VAV applications
86 RT-SVX36G-EN
Figure 39. Typical field wiring diagram for 20-89 ton VAV control option
Installation
RT-SVX36G-EN
2307-9177
87
Installation
Figure 40. Typical field wiring diagram for 20-89 ton VAV control option
88 RT-SVX36G-EN
Figure 41. Typical GBAS analog input wiring diagram for 20-89 ton CV & VAV control options
Installation
RT-SVX36G-EN 89
Installation
Table 31. GBAS Voltage vs. Setpoint
Setpoint
Occ Zone Cooling Setpoint(CV only)
Unocc Zone Cooling Setpoint
Occ Zone Heating Setpoint(CV only)
Unocc Zone Heating Setpoint
SA Cooling Setpoint (VAV only)
SA Cooling Setpoint (SZVAV only)
Zone Cooling Setpoint (SZVAV only)
Zone/Return Critical Temperature Setpoint (RR only)
SA Heating Setpoint (VAV only)
SA Heating Setpoint (SZVAV only)
Space Static Pressure Setpoint
SA Static Pressure Setpoint
Min OA Flow Setpoint 1
MWU Setpoint
Econ Dry Bulb Enable Setpoint
SA_Reheat_Setpoint
Minimum Position Setpoint 3
Occ Dehumidification Setpoint
Unocc Dehumidification Setpoint
Occ Humidification Setpoint
Unocc Humidification Setpoint
Notes:
1. If DCV is enabled this is used for Design Minimum OA Flow Setpoint
2. If DCV is enabled, this is used for Design Minimum OA Damper Position Setpoint
GBAS 0-5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
Table 32. GBAS 0-10 VDC output range
Setpoint
Outdoor Air Temperature
Zone Temperature
Supply Air Temperature (VAV and CV
Discharge Temperature Control only)
Supply Air Pressure (VAV only)
Space Pressure
Space RH
OA RH
Space CO2 Level
Cooling Capacity %
Heating Capacity %
Outdoor Air Damper Position
Outdoor Airflow
GBAS 0-10 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
GBAS 0-10 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
Valid Range
-40 to 200°F
-40 to 200°F
-40 to 200°F
0.0 to 7.91 wc
-0.67-0.67 wc
0-100%
0-100%
50-2000 PPM
0-100%
0-100%
0-100%
0 to 65,000 CFM
Valid Range
50 to 90°F
50 to 90°F
50 to 90°F
50 to 90°F
40 to 90°F
40 to 70°F
50 to 80°F
75 to 95°F
40 to 180°F
65 to 95°F
-0.20 to 0.30 IWC
0.7 to 5.1 IWC
0 to Unit Max Flow
50 to 90°F
50 to 140°F
60 to 90°F
0 to 100%
40 to 65%
40 to 65%
20 to 50%
20 to 50%
90 RT-SVX36G-EN
Installation Checklist
20-130 Ton, Air-Cooled and Evaporative Condensing
The checklist listed below is a summary of the steps required to successfully install a commercial rooftop unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process.
Important:
This checklist does not replace the detailed instructions called out in the applicable sections of this manual.
Table 33. Installation Checklist
General Unit Requirements
Check the unit for shipping damage and material shortage; file a freight claim and notify Trane office.
Verify that the installation location of the unit will provide the required clearance for proper operation.
Assemble and install the roof curb per the current edition of the curb installation guide.
Fabricate and install ductwork; secure ductwork to curb.
Install pitch pocket for power supply through building roof. (If applicable)
Rigging the unit.
Set the unit onto the curb; check for levelness.
Ensure unit-to-curb seal is tight and without buckles or cracks.
Install and connect condensate drain lines to each evaporator drain connection.
Remove the shipping hold-down bolts and shipping channels from the supply and exhaust/return fans ordered with rubber or spring isolators.
Check all optional supply and exhaust/return fan spring isolators for proper adjustment.
Verify all discharge and liquid line service valves (one per circuit) are back seated.
Main Electrical Power Requirements
Verify that the power supply complies with the unit nameplate specifications.
Inspect all control panel components; tighten any loose connections.
Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect and unit.
Properly ground the unit.
Note:
All field-installed wiring must comply with NEC and applicable local codes.
Field Installed Control Wiring
Complete the field wiring connections for the constant volume controls as applicable. Refer to “Field Installed Control Wiring” for guidelines.
Complete the field wiring connections for the variable air volume controls as applicable. Refer to “Field Installed Control Wiring” for guidelines.
Note:
All field-installed wiring must comply with NEC and applicable local codes.
Requirements for Electric Heat Units
All SEHL Units (380 minimum voltage)
Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
Inspect the heater junction box and control panel; tighten any loose connections.
Check electric heat circuits for continuity.
SEHL Units w/200V or 230V Electric Heat: (Requires Separate Power Supply to Heater)
Connect properly sized and protected power supply wiring for the electric heat from a dedicated, field- supplied/installed disconnect to terminal block 4TB2, or to an optional unit mounted disconnect switch 4S15.
Continued on next page
Task
Completed
RT-SVX36G-EN 91
Installation Checklist
Table 33. Installation Checklist (continued)
Requirements for Gas Heat
Gas supply line properly sized and connected to the unit gas train.
All gas piping joints properly sealed.
Drip leg Installed in the gas piping near the unit.
Gas piping leak checked with a soap solution. If piping connections to the unit are complete, do not pressurize piping in excess of 0.50 psig or 14 inches w.c. to prevent component failure.
Main supply gas pressure adequate.
Flue Tubes clear of any obstructions.
Factory-supplied flue assembly installed on the unit.
Connect the ¾” CPVC furnace drain stubout to a proper condensate drain.
Requirements for Hot Water Heat (SLH_)
Route properly sized water piping through the base of the unit into the heating section.
Install the factory-supplied, 3-way modulating valve.
Complete the valve actuator wiring.
Requirements for Steam Heat (SSH_)
Install an automatic air vent at the top of the return water coil header.
Route properly sized steam piping through the base of the unit into the heating section.
Install the factory-supplied, 2-way modulating valve
Complete the valve actuator wiring.
Install ½”, 15-degree swing-check vacuum breaker(s) at the top of each coil section. Vent breaker(s) to the atmosphere or merge with return main at discharge side of steam trap.
Position the steam trap discharge at least 12" below the outlet connection on the coil.
Use float and thermostatic traps in the system, as required by the application.
O/A Pressure Sensor and Tubing Installation (All units with Statitrac or Return Fans)
O/A pressure sensor mounted to the roof bracket.
Factory supplied pneumatic tubing installed between the O/A pressure sensor and the connector on the vertical support.
Field supplied pneumatic tubing connected to the proper fitting on the space pressure transducer located in the filter section, and the other end routed to a suitable sensing location within the controlled space (Statitrac only).
Requirements for Modulating Reheat Dehumidification
Install (5U108) humidity sensor in space or return duct
Complete field wiring of humidity sensor to ECEM (1TB16). Refer to “Field Installed Control wiring” for guidelines.
Evaporative Condenser
Remove fan bracket
Hookup inlet and drain piping
Install Heat tape if needed
Setup drain hold or drain on power loss
Setup Mechanical Float
Setup drain time
Setup water quality management (3rd party or Trane factory-installed Dolphin Water Care™ System)
Options setup
Calibrate Conductivity Controller
Setup blowdown set points on the conductivity sensor
Task
Completed
92 RT-SVX36G-EN
Unit Start Up
Cooling Sequence of Operation
Time delays are built into the controls to increase reliability and performance by protecting the compressors and maximizing unit efficiency.
NOTICE:
Compressor Failure!
Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors are started. This will protect the compressors from premature failure.
Compressor Crankcase Heaters
Each compressor is equipped with a crankcase heater controlled by a 600 volt auxiliary switch on the compressor contactor. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
When power has been “Off” for an extended period, allow the crankcase heater to operate a minimum of 24 hours before starting the unit.
SZVAV Cooling Sequence of Operation
Single Zone VAV units will be equipped with a VFD controlled supply fan which will be controlled via the 0-10VDC RTM VFD output and the RTM Supply Fan output. With the RTM Supply Fan output energized and the RTM VFD output at 0Vdc the fan speed output is 37% (22Hz) from the VFD motor, by default, and at 10VDC the Fan Speed output is 100% (60Hz). The control scales the 0-10Vdc VFD output from the RTM linearly to control between the 37%-100% controllable range.
If the RTM determines that there is a need for active cooling capacity in order to meet the calculated
Temperature Setpoint (Tset), the unit will begin to stage compressors accordingly once supply fan proving has been made. Note that the compressor staging order will be based on unit configuration and compressor lead/lag status.
Once the Tset calculation has reached its bottom limit (Tset Lower Limit Setpoint) and compressors are being utilized to meet the demand, the Tset value continues to calculate below the Tset Lower
Limit Setpoint and the algorithm will begin to ramp the Supply Fan Speed up toward 100%. Note that the supply fan speed will remain at the compressor stage’s associated minimum value (as described below) until the Tset value is calculated below the Tset Lower Limit Setpoint.
As the cooling load in the zone decreases the zone cooling algorithm will reduce the speed of the fan down to minimum per compressor stage and control the compressor outputs accordingly. As the compressors begin to de-energize, the Supply Fan speed will fall back to the Cooling Stage’s associated minimum fan speed, but not below. As the load in the zone continues to drop cooling capacity will be reduced in order to maintain the discharge air within the ± ½ Tset deadband.
Cooling Stages Minimum Fan Speed
As the unit begins to stage compressors to meet the cooling demand, the following minimum
Supply Fan Speeds will be utilized for each corresponding Cooling Stage. Note that the Supply Fan
Speed will be allowed to ramp up beyond 37% as determined by the active Tset calculation; the speeds below are only the minimum speeds per cooling stage. Note that when transitioning between active cooling stages, compressors may energize prior to the supply fan reaching the minimum speed for the associated step.
RT-SVX36G-EN 93
Unit Start Up
1.
2-Stage DX Cooling - The minimum fan speed for units with 2 stages of DX Cooling will be 37% of the unit’s full airflow capacity. At Stage 1 of DX Cooling the minimum Fan Speed will be 37% and at Stage 2 of DX Cooling the Fan Speed will be at a minimum of 67%.
2. 3-Stage DX Cooling - There are no IntelliPak applications with 3 stages of DX Cooling.
3. 4-Stage DX Cooling - The minimum fan speed for units with 4 stages of DX Cooling will be 37% of the unit’s total airflow. At Stage 1 the minimum Supply Fan Speed will be 37%, at Stage 2 the minimum Supply Fan Speed will be 58%, and at Stages 3 & 4 the minimum Supply Fan
Speed will be 67%.
Rapid Restart
This feature will occur after every power cycle. Once power is restored (e.g., via a backup generator), the RTM will maximize cooling capacity within 3-5 minutes. Once the space has returned to its Zone Temperature Setpoint, the RTM controls the load using normal capacity control algorithms. The supply fan will be turned on immediately after a power cycle, module initialization, or after the Unit Start Delay has timed out. The supply fan proving switch input must be closed prior to continuing with Rapid Restart.
Once the supply fan proving switch input has closed, the unit will consider the outside air temperature to determine whether economizing or DX mechanical cooling will be utilized to provide the necessary cooling. If the outside air temperature is less than 50°F and economizing is enabled, the outside air damper will be utilized. If the outside air temperature is above 50°F, the outside air damper will remain closed and DX mechanical cooling will occur for the duration of
Rapid Restart.
Supply Fan Operation – Speed Control:
• VAV: The supply fan speed will ramp to 50%, then release to normal discharge static pressure control, limited only by the high duct static limit functionality.
• CV: The supply fan speed will turn on full airflow.
• SZVAV: The supply fan speed will ramp to full airflow.
Figure 42. Typical rapid restart timeline
94
Units without an Economizer
Upon entering an “occupied” mode of operation, the RTM receives input from the remote panel to start the supply fan. For constant volume applications, the RTM supply fan contacts K2 close which energizes the supply fan contactor 1K16. When the supply fan starts, the fan proving switch
(3S68) closes, signaling the RTM that airflow has been established. The VFD will begin to ramp the fan, (if equipped).
RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
When a cooling request is sent to the RTM from a zone temperature sensor, the RTM evaluates the operating condition of the system using the supply air temperature input and the outdoor temperature input before sending the request to the SCM/MCM. Once the request is sent to the
SCM/MCM, the compressor module checks the compressor protection circuit before closing
“Stage 1” (K10 on SCM or K11 on MCM). After the first functional stage has started, the compressor module monitors the saturated refrigerant temperature and closes the condenser fan output contact “1A”, when the saturated refrigerant temperature rises above the “lower limit” setpoint.
Units with an Economizer
Upon entering an “occupied” mode of operation, the RTM receives input from the remote panel to start the supply fan. For constant volume applications, the RTM supply fan contacts K2 close which energizes the supply fan contactor 1K16. When the supply fan starts, the fan proving switch
(3S68) closes, signaling the RTM that airflow has been established. The RTM opens the economizer dampers to the specified “minimum position”.
When a cooling request is sent to the RTM from the zone temperature sensor, the RTM evaluates the operating condition of the system using the supply air temperature input and the outdoor temperature input before sending the request to the SCM/MCM for mechanical cooling. If the outdoor conditions are suitable for cooling (temperature and humidity are within specified setpoints), the RTM will attempt to maintain the zone temperature without using any compressors.
If the zone temperature can not be maintained within the setpoint deadband, the RTM sends a cooling request to the SCM/MCM. The compressor module checks the compressor protection circuit before closing “Stage 1” (K10 on SCM or K11 on MCM). After the first functional stage has started, the compressor module monitors the saturated refrigerant temperature and closes the condenser fan output contact “1A”, when the saturated refrigerant temperature rises above the
“lower limit” setpoint.
Units with Return Fan
The return fan is started once the supply fan is verified ON by the supply fan proving function. If equipped, the variable speed return fan is modulated to control return plenum pressure to the
Return Plenum Pressure Setpoint and Return Plenum Pressure Deadband.
For the first two minutes of return fan operation, the outside air damper control and if equipped, building space pressure control are disabled so that the exhaust damper remains closed. After the two minute delay, the outside air damper is released to normal ventilation requests, and exhaust damper control will either track the outside air damper or if equipped, the exhaust damper control is released to normal space pressure control.
Units with Traq Sensor
The fresh air enters the unit through the Traq Sensor assembly and is measured by velocity pressure flow rings. The velocity pressure flow rings are connected to a pressure transducer/ solenoid assembly. The solenoid is used for calibration purposes to compensate for temperature swings that could affect the transducer. The Ventilation Control Module (VCM) utilizes the velocity pressure input, the RTM outdoor air temperature input, and the minimum outside air CFM setpoint to modify the volume (CFM) of fresh air entering the unit as the measured airflow deviates from setpoint.
When the optional temperature sensor is installed and the Preheat function is enabled, the sensor will monitor the combined (averaged) fresh air and return air temperatures. As this mixed air temperature falls below the Preheat Actuate Temperature Setpoint, the VCM will activate the preheat binary output used to control a field installed heater. The output will be deactivated when the temperature rises 5 above the Preheat Actuate Temperature Setpoint.
When the optional CO
2
sensor is installed and the CO
2
Reset is enabled, as the CO
2
concentration increases above the CO
2
Reset Start Value, the VCM will modify the minimum outside air CFM setpoint to increase the amount of fresh air entering the unit. The setpoint will be adjusted upward until the CO
2
Maximum Reset Value is reached. The maximum effective (reset) setpoint value for fresh air entering the unit is limited to the systems operating CFM. As the CO
2
concentration
95
Unit Start Up
decreases, the effective (reset) setpoint value is adjusted downward toward the minimum outside air CFM setpoint.
Figure 43. CO
2
Reset
96
Low Charge Protection
For each refrigeration circuit, the entering and leaving evaporator temperatures are used to calculate superheat. When the calculated superheat exceeds the Evaporator Temperature
Differential Setpoint minus 5°F but not the Evaporator Temperature Differential Setpoint, an information only, auto-reset, High Superheat diagnostic is initiated. If the calculated superheat exceeds the Evaporator Temperature Differential Setpoint, a manual reset, low refrigerant charge diagnostic is initiated and all compressors on the circuit are locked out.
Frostat
™
Control
The compressor module utilizes an evaporator temperature sensor (3RT14 & 15), mounted on the suction line of each circuit, to protect the evaporator from freezing. If the evaporator temperature approaches the specified setpoint, adjustable between 25°F and 35°F, the compressor(s) will be cycled “off”. The compressors will not be allowed to restart until the evaporator temperature has risen 10°F above the specified cutout temperature and the compressor(s) have been off for a minimum of three minutes.
Lead-Lag Operation
When Lead-Lag is enabled, each time the system cycles after having stages 1 and 2 “On”, “Stage
2” (K11 on SCM or K3 on MCM) and the corresponding condenser fan output “2A” will start first.
The compressor module cycles the compressors “On” and “Off” to keep the zone temperature within the cooling setpoint deadband. The condenser fans are cycled “On” and “Off” to maintain the saturated refrigerant temperature within the specified controlband.
Units Equipped with 100% Modulating Exhaust Dampers
The exhaust dampers are controlled through an Exhaust/Comparative Enthalpy Module (ECEM).
The ECE module receives input form a space transducer and modulates the exhaust dampers to maintain the space pressure to within the specified setpoint controlband.
Units equipped with Hot Gas Reheat (Modulating Dehumidification)
When space humidity exceeds setpoint and the unit is loaded 50% or less, the modulating dehumidification function activates the reheat mode, providing dehumidification of the space.
The reheat valve and cooling valve are modulated to control the discharge air temperature to the reheat discharge air temperature setpoint. In reheat mode, the reheat valve is commanded to control the discharge air (15 to 85%) to the reheat setpoint; the cooling valve mirrors the reheat valve position (85 to 15%). The reheat coil pumpout valve is energized when the unit is in active cooling, and de-energized during all other times - including reheat mode.
RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Units with Evaporative Condenser Sequence of Operation
Upon a power up without water in the sump, the condenser sump drain will be controlled to allow the sump to hold water. The fill relay will be energized if there is a call for mechanical cooling and if the outdoor air temperature is greater than 10°F on units with a sump heater installed or greater than 40°F on units without sump heat.
Once the fill solenoid is energized, the sump will begin to fill. The minimum water level switch will close and the fill relay will be de-energized. The sump water temperature sensor is invalid unless the minimum water level switch is closed.
If the sump water temperature is less than the setpoint (default is 38°F), the sump heater will be energized until the water temperature reaches the setpoint plus 5 degrees (43°F for default). The fill solenoid will remain closed for 20 minutes or until the water temperature is greater than 35°F.
Once a water temperature of 35°F or greater is achieved, the fill solenoid is energized, the sump will continue to fill, and a five minute timer is started.
When the timer expires, the compressor lockout will be released and mechanical cooling will be allowed. Head pressure control will be regulated by a variable speed fan until the liquid line pressure from either circuit reaches the upper limit, which is set on the Human Interface under the setup menu 120°F default. The liquid line pressure is converted to a temperature for display at the
Human Interface. When the temperature exceeds the upper limit, the condenser sump pump will be energized. When the sump pump is energized, water is pumped from the sump and sprayed over the condenser coil. If the liquid line pressure from either circuit falls below the lower limit the sump pump will be de-energized.
When the sump pump is energized or de-energized a change in state is observed from an auxiliary contactor to ensure proper sump pump operation. A change in states must be observed by the auxiliary contactor within 6 seconds of the command to change states or mechanical cooling will be locked out on a sump pump failure causing a manual reset diagnostic to be set.
The fill solenoid will remain energized and the water level will be controlled by the mechanical float valve. If the maximum level float ever closes, an information-only diagnostic is set and the fill solenoid is de-energized. This is an indication that the mechanical float is not adjusted properly or a failure of the mechanical float valve has occurred. If the maximum level input is open for two continuous minutes, the diagnostic will be cleared and the fill solenoid will be energized.
If the sump water temperature ever drops below 35°F, the drain actuator will be controlled in order to drain the water from the sump. If there is a call for mechanical cooling and the outdoor air temp is greater than 10°F on units with sump heat installed or greater than 40°F on units without sump heat, the unit will be allowed to refill the sump.
The drain control can be configured via the Human Interface, and by the drain actuator installation, to hold or drain water on power loss; the default is set to drain. Periodic purge is a cyclic opening of the drain to remove debris and buildup from the sump and add additional fresh water to the sump. Periodic purge has an adjustable interval from the setup menu on the Human Interface with a range of 1-12 hours or can be set to disabled - the default position if periodic purge is not required.
The duration of the blowdown, or the time that the drain valve is opened, is adjustable to a range of 5 - 255 seconds, with 60 seconds being the default.
The optional conductivity controller also uses this timer to open the drain, when required, based on water quality. During this purge, the fill solenoid will remain energized to provide fresh water to the sump to replace water being released during the blowdown. Water treatment blowdown is provided by shorting the designated input on the customer-supplied terminal strip. This gives the customer more flexibility in determining water conditions via external controls. Once the input is detected closed, the drain valve will be opened for a time equal to the Human Interface adjustable periodic purge duration.
Once the duration timer expires, or if the minimum level switch opens, the drain valve will be closed and the water treatment blowdown input will be ignored for 15 minutes. During this blowdown the fill relay will remain open to provide fresh water to the sump. The adjustable duration time period should be set so that during drain operation 1 inch of water is drained from the sump with the fill
97
Unit Start Up
solenoid valve closed. If the minimum water level switch opens during a blowdown cycle, the unit will de-energize the sump pump in order to protect the compressors and sump heater from insufficient water levels. Once the water level reaches the minimum level input and this input closes for 10 seconds, the compressors and sump heater operations will be allowed to restart.
Evaporative Condenser Drain Valve Setup
The drain valve is shipped to “Drain During Unit Power Loss Conditions.” This means that when the unit disconnect is turned off, the 1S2 toggle switch is turned off, or the unit loses power, the drain will open. The valve is spring loaded and will travel from fully closed to fully open in approximately 25 seconds.
This is desirable in cold climates where a risk of freezing exists. In milder climates it may be desirable to keep the water in the sump when unit power is off to avoid unnecessarily wasting water whenever the unit disconnect is turned off.
To convert the unit to “Hold During Unit Power Loss Conditions”:
1.
Remove power from the unit.
2. Remove the weather shield cover ( Figure 44, p. 98 ).
3. Loosen the shaft set screw (
), remove the locking clip, and remove the shaft adapter
5. Reinstall the shaft adapter and locking clip and reinstall the actuator onto the base. Make sure the arrow on the shaft adapter is set to 0°.
6. Make sure the valve is in the fully closed position, then tighten the shaft set screw.
7.
Reinstall the weather shield cover.
8. Restore power to the unit.
9. At the Human Interface, press SETUP, NEXT until 'Head Pressure Control Setup Submenu” is seen. Press ENTER.
10. Change the “Sump Drain Valve Relay Control” from Drain to Hold
Figure 44. Drain valve actuator with weather shield
Weather Shield
Shaft Set Screw
Drain Valve Actuator
98 RT-SVX36G-EN
Figure 45. Actuator shaft adapter removal/assembly
Locking clip
1
2
Shaft adapter
Figure 46. Actuator is shipped in “drain during power loss” configuration
Unit Start Up
RT-SVX36G-EN
To drain during power loss, set shaft adapter to 0 degrees
To hold during power loss, set shaft adapter to 90 degrees
Set Drain Duration Timer
Enter service test mode from unit Human Interface. Navigate to the compressor condenser fan submenu. Under head pressure control, use manual control.
Close drain valve and energize water inlet solenoid valve until water reaches nominal level. Once level is achieved, de-energize fill solenoid. Open drain valve and time how long it takes for the water level to drop one inch, make sure to take into account the closing time of the valve.
99
Unit Start Up
100
Chemical Water Treatment Tree
The Trane evaporative condenser comes with a PVC tree to allow easier inputs for third party water treatment. The tee labeled A is a ¾ inch NPT threaded input, see
. Tees
B and C are 1/2 inch NPT threaded inputs. The ball valve can be used to stop the water flow through the tree to allow the customer to add hookup of water treatment, or to change and update water treatment with the unit running.
Units with Dolphin WaterCare or conductivity sensor will have the conductivity sensor installed into the ¾ inch tee with the other tees plugged. For all other units, A, B and C will be plugged, see
. Ensure the ball valve is in the open position when water treatment is being operated in the system to make sure water flows through the tree and transports treatment to the unit sump.
Conductivity Controller
Upon startup, the conductivity controller must be calibrated and setup for operation. Below are the necessary steps to accomplish those tasks. The controller has two setpoints that control two relays. Both of these setpoints will need to be set by Dolphin or a local water treatment expert.
• The first setpoint is the standard point blowdown point.
– When the setpoint is exceeded the relay (K1) will be energized and a blowdown request will close the Water treatment request binary input on the MCM.
Figure 47. Chemical Water
Treatment Tree
A
B
C
• The second setpoint will be the emergency point
– The second setpoint will open the normally closed K2 relay which will interrupt the sump proving circuit which will generate a manual lockout. This second setpoint will be used to protect the unit from extremely high conductivity that would indicate a failure in the system.
• Inside the enclosure for the controller, there will be a thermostat and strip heater that will protect LCD from cracking at low ambient conditions. The thermostat closes at 15°F and opens at 25°F.
Procedure to calibrate conductivity
Note: Visit this webpage for additional documentation: <http://www.gfsignettools.com/products/ pdf/8860eng.pdf>
• Use a calibrated thermometer and a known conductivity rating
• There are two different options for having a liquid with known conductivity
• Purchase a liquid with known conductivity rating
• Purchase a handheld conductivity reader
• Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree
• Enter service test mode on the unit and turn the pump on, ensuring the compressors are set to Off
• With the conductivity controller connected to the sensor and power, enter the CALIBRATE menu by holding down the enter key for 2 seconds
• When asked for the calibration key code, hit the UP-UP-UP-DOWN arrow keys in sequence
RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
• Using the UP and DOWN arrows go to Chan 1 Cell: Standard. Ensure this channel is set to standard
• If not press the RIGHT arrow key and set to standard then press the ENTER key to return to the
CALIBRATION menu
• Using the UP and DOWN arrows go to Chan 1 Cell. Ensure that the cell constant is set to 1.0
• If not press the RIGHT arrow key and set the cell constant to 1.0 then press the ENTER key to return to the CALIBRATION menu
• Using the UP and DOWN arrows go to Chan 1 Set: Temperature and press the RIGHT arrow key to enter the edit mode
• Adjust the temperature on the controller to match the actual temperature
• Press the ENTER key to save the input and return to the CALIBRATE menu
• Using the UP and DOWN arrows, go to the Chan 1 Set: Conductivity and press the RIGHT arrow key to enter the edit mode
• Adjust the conductivity on the controller to match the actual conductivity rating of the liquid
• Press the ENTER key to save the conductivity rating and return to the CALIBRATE menu
• When finished calibrating the controller, press the UP and DOWN key simultaneously to return to normal operating mode
Procedure to set purge setpoints on the conductivity controller
Note: Visit this webpage for additional documentation: <http://www.gfsignettools.com/products/ pdf/8860eng.pdf>
• Work with local water treatment expert to identify nominal purge and emergency purge conductivity value.
• Close the ball valve on the chemical treatment tree and remove the conductivity sensor from the tree.
• Enter Service test mode on the unit HI and energize the sump pump, ensuring the compressors are set to “OFF”
• With the conductivity controller connected to the sensor and power, enter the CALIBRATE menu by holding down the enter key for 2 seconds
• When asked for the calibration key code, hit the UP-UP-UP-DOWN arrow keys in sequence
• Using the UP and DOWN arrows, go to Relay 1 Setpoint: and press the RIGHT arrow key to enter edit mode (K1)
• Adjust the set point to the nominal blowdown conductivity value
• Press the ENTER key to return to the CALIBRATE menu
• Using the UP and DOWN arrows, go to Relay 2 Setpoint: and press the RIGHT arrow key to enter edit mode (K2)
• Adjust the set point to the emergency conductivity value
• Press the ENTER key to return to the CALIBRATE menu
• When finished setting the values, press the UP and DOWN key simultaneously to return to normal operating mode
101
Unit Start Up
Gas Heating Sequence of Operation
Standard Two Stage Gas Furnace
The control system for the rooftop units are wired to ensure that the heating and cooling do not occur simultaneously. Refer to the wiring diagram that shipped with the unit while reviewing the following sequence of operation.
Honeywell Ignition System
When a heating requirement exists, the Rooftop Module (RTM) starts the supply fan and sends a request for heat to the Heat Module. The Heat Module closes K1 contacts and starts the combustion blower motor (4B11). The combustion blower motor starts on low speed through the normally closed combustion blower relay (4K33) contacts.
The supply airflow switch (4S38) and the combustion air switch (4S25) closes. Power is applied through the high limit cutout (4S26) to the Honeywell ignition control board (4U18). The ignition control board (4U18) starts a pre-purge timing cycle. At the end of the pre-purge cycle, the ignition transformer (4T7) and the pilot solenoid valve (4L9) are energized. This starts a 10 second trial for pilot ignition. When the pilot flame is established and sensed by the flame sensing rod (4U19), stage
1 of the main gas valve (4L7) and the 60 seconds sequencing time delay relay (4DL6) is energized.
The system will operate in the low heat mode until there is an additional call for heat is established by closing the K3 contacts on the Heat Module.
On Discharge Temperature Control systems, the sequencing time delay relay (4DL6) will energize the combustion blower motor relay (4K33) which switches the combustion blower motor to high speed and energizes the 2nd stage solenoid on the gas valve (4L7) after approximately 60 seconds.
If the flame rod (4U19) does not detect a pilot flame within the 10 second trial for ignition period, the control will lockout. If a flame failure occurs during operation, the gas valve (4L7), the sequencing time delay relay (4DL6), and the combustion blower relay (4K33) is de-energized. The system will purge and attempt to relight the pilot. If a flame is not detected after this attempt, the
Honeywell ignition control (4U18) will lock out. The combustion blower motor will continue to operate as long as a heating demand exists and the system switch (4S24) is “On”.
Once the heating demand has been satisfied, the combustion blower and the Honeywell ignition control board (4U18) is de-energized.
Propane Gas
Units that operate on propane gas after 1990 have two (2) additional controls that affect the combustion blower motor operation and the sequence of the gas valve operation.
With the post purge time delay relay (4DL4), the additional service switch (4S24), and the additional
115 volt control relay (4K31) installed, the sequence of operation is as follows:
Power is applied to the Honeywell ignition control board (4U18) through the high limit switch
(4S26). The Honeywell ignition control board (4U18) will sequence through its pre-purge timing and pilot ignition sequence to The post purge time delay relay (4DL4) delays the starting of the combustion blower motor by approximately 60 seconds. Once the timing has elapsed, the combustion blower motor will start, closing the combustion air switch (4S25).
Energize the control relay (4K31) and the sequence time delay relay (4DL6). 24 volts is applied from the new service switch (4S24) through the normally open control relay (4K31) contacts to energize the 1st stage solenoid on the gas valve (4L7).
On an additional call for heat, the K3 contacts on the Heat Module will close to energize the combustion blower relay (4K33) which switches the combustion blower motor to high speed and closes its normally open contacts allowing 24 volts to energize the 2nd stage on the gas valve (4L7).
Once the heating demand has been satisfied, the Honeywell ignition control board (4U18) and the post purge time delay relay (4DL4) is de-energized. The combustion blower motor will continue to operate for approximately 15 seconds to purge the heat exchanger on the “Off” cycle.
102 RT-SVX36G-EN
Unit Start Up
Modulating Gas Sequence of Operation—Full and Limited Modulating Gas Furnace
The control system for the rooftop units are wired to ensure that the heating and cooling do not occur simultaneously. Refer to the modulating heat wiring diagram that shipped with the unit while reviewing the following sequence of operation. As you review the sequence of operations, keep the following in mind:
• The furnace will not light unless the manual gas valves are open and the control circuit switch
4S24 is closed.
• The control systems are wired to ensure that heating and cooling cannot occur simultaneously.
• The unit supply fans must run continuously so air flow switch 4S38 will stay closed.
• Modulating Gas heat is available during both occupied and unoccupied operation.
Whenever there is a call for heat, 1U50-K1 energizes and combustion blower motor 4B11 begins to operate at High speed on the 850 and 1000 MBH heaters. The blower will operate on low speed for the 500 MBH. A relay 4K119 in parallel with the main gas valve actuator control output, insures the actuator will be open prior to proof of flame. This will force the combustion air actuator 4U82 to the open position, causing the auxiliary switch on 4U82 to close. This insures complete purging of the combustion chamber during the 60 second purge cycle.
Ignition control IC board 4U18 will not energize, however, unless the supply air flow switch 4S38, combustion air flow switch 4S25, high limit cutout 4S26, the auxiliary switch on combustion air actuator 4U82 and the proof of closure switch on gas valve 4L22 are closed. These are all part of the safety interlock system.
With all these conditions satisfied, the IC board energizes and initiates an internal 60 second prepurge time delay. When the pre-purge period expires, 4U18 energizes both the ignition transformer
4T7 and solenoid 4L9 on the intermittent pilot valve. At that point, 4U18 gives electrode 4E1 approximately 10 seconds to establish a pilot flame. (The presence of this flame is proven by flame rod 4U19.)
If 4U18 does not detect a pilot flame at the end of this period, it will shut down and lock out the ignition / combustion circuit.
If the pilot is ignited within 10 seconds, the IC board de-energizes the ignition transformer 4T7 and electrode 4E1. At this point, relay 4K119 will energize, starting the combustion air actuator and the furnace. The feedback signal from the discharge temperature sensor will cause the modulating output from the heat module to change the damper position as required to maintain the outlet temperature within the desired band.
Flame Failure
In the event that IC board 4U18 loses the “proof-of-flame” input signal during furnace operation, it will make one attempt at reignite. If a flame is not reestablished within the 10 second trial period,
4U18 will shut down and lock out the ignition /combustion control circuit. (Combustion blower motor 4B11 continues to run as long as a heating requirement exists and control circuit switch 4S24 is ON.)
Once locked out on flame failure, the IC board will not reactivate the ignition/combustion control circuit until it is reset manually. To do this, press the reset button on the front of the IC board case.
A set of relay contacts are available for external use for heat fail (Information Only).
Note: The modulating gas heaters are factory adjusted for the proper air/gas ratio at minimum and nameplate rated firing MBH for most areas in the country.
RT-SVX36G-EN 103
Unit Start Up
Electric Heat Sequence of Operation
The control system for the rooftop units are wired to ensure that the heating and cooling do not occur simultaneously. Refer to the electric heat wiring diagrams that shipped with the unit while reviewing the following sequence of operation. As you review the sequence of operations, remember these points:
Whenever there is a call for heat, 1U50-K1 energizes. This energizes HEAT 1 contactors 4K34 and
4K35 which, in turn, energize two of the six 4HR3 heating elements.
Note: Electric heater 4HR3 will only energize if both of the heat section’s high limit safety controls—4S27 and 4S33—are closed.
• High limit Switch 4S27 will trip if exposed to a temperature of 133 + 5°F, and reset automatically once the temperature falls to 110 + 5°F. It is mounted on the control-box-side of the electric heat element assembly.
• Linear high limit 4S33 is encased in a capillary that extends across the unit’s supply air opening, and is anchored near the bottom of the heat section control box. It is designed to trip if the temperature across any 6" span of the capillary exceeds 185 + 10°F. Refer to
HEAT 2 (4K36, 4K37) and HEAT 3 (4K38, 4K39) contactors are not energized unless the 1st stage bank of heating elements already operating are not satisfying the heating load.
Wet Heat Sequence of Operation
Electrical circuitry for units with steam or hot water heat is limited to the connections associated with the modulating valve actuator (4U15) and the freezestat (4S12).
Like the furnaces described earlier, SL/SH control systems are wired to ensure that simultaneous heating and cooling do not occur. The supply fan will cycle “On” and “Off” with each call for heat during both an occupied and unoccupied period.
Whenever there is a call for heat, 1U50-K3 energizes. This allows a modulated voltage signal to be sent to the “Wet” heat actuator 4U15. Depending on the value of this signal, 4U15 regulates the flow of steam or hot water through the coil by positioning the valve stem at some point between fully closed (6 VDC) and fully open (8.5 VDC).
Freeze Protection
A freezestat (4S12) is mounted inside the heat section of SLH_ and SSH_ units to prevent the “wet” heat coil from freezing during the “Off” cycle.
If the temperature of the air leaving the heating coils falls to 40°F, the freezestat's normally-open contacts close, completing the heat fail circuit on the UCM. When this occurs: a. The supply fan is turned “Off”.
b. “Wet” heat actuator 4U15 fully opens to allow hot water or steam to pass through the heating coil and prevent freeze-up.
c. A “Heat Fail” diagnostic is displayed on the Human Interface LCD screen.
For heating control settings and time delay specifications, refer to
Use the checklist provided below in conjunction with the “General Unit Requirement” checklist to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section before starting the unit for the first time.
• Turn the field supplied disconnect switch, located upstream of the rooftop unit, to the “Off” position.
104 RT-SVX36G-EN
Unit Start Up
RT-SVX36G-EN
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Turn the 115 volt control circuit switch 1S1 to the “Off” position. It is located in the secondary of the 1T1 transformer.
• Turn the 24 volt control circuit switch 1S70 to the “Off” position. It is located in the secondary of the 1T2 & 1T3 transformers.
• Turn the “System” selection switch (at the Remote Panel) to the “Off” position and the “Fan” selection switch (if Applicable) to the “Auto” or “Off” position.
• Check all electrical connections for tightness and “point of termination” accuracy.
• Verify that the condenser airflow will be unobstructed.
• Check the compressor crankcase oil level. Oil should be visible in the compressor oil sight glass.
The oil level should be 1/2 to 3/4 high in the sight glass with the compressor “Off”.
• Verify that the compressor discharge service valve and the liquid line service valve is back seated on each circuit.
NOTICE:
Compressor Damage!
Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines may result in compressor damage. Compressor service valves must be fully opened before start-up (suction, discharge, liquid line, and oil line).
Do not start the unit in the cooling mode if the ambient temperature is below the following minimum recommended operating temperatures:
Standard unit with or without HGBP -
+55 F for 20 & 40 Ton
+50 F for 25 & 30 Ton
+45 F for 70 thru 130 Ton
+35 F for 50 Ton
+30 F for 60 Ton
Units with Low Ambient option without HGBP - 0°F
Units with Low Ambient option with HGBP - +10°F
Note: To prevent compressor damage due to no refrigerant flow, do not pump the system down with the compressor(s) below 25 PSIG under any circumstance.
• Check the supply fan belts for proper tension and the fan bearings for sufficient lubrication. If the belts require adjustment, or if the bearings need lubricating, refer to the Service/
Maintenance section of this manual for instructions.
• Inspect the interior of the unit for tools and debris. Install all panels in preparation for starting the unit.
Electrical Phasing
Unlike traditional reciprocating compressors, scroll compressors are phase sensitive. Proper phasing of the electrical supply to the unit is critical for proper operation and reliability. Color paint dots on the terminal block should match that of the associated wire attached to the lug.
105
Unit Start Up
The compressor motor is internally connected for clockwise rotation with the incoming power supply phased as A, B, C.
Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following the steps below:
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Turn the field supplied disconnect switch that provides power to terminal block 1TB1 or to the unit mounted disconnect switch 1S14 to the “Off” position.
• Connect the phase sequence indicator leads to the terminal block or unit mounted disconnect switch as follows;
Table 34.
Phase sequence leads
Black (Phase A)
Red (Phase B)
Yellow (Phase C)
Unit power terminal
L1
L2
L3
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
• Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT
SWITCH 1S14.
• Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect switch or circuit protection switch and reverse any two power wires.
• Restore the main electrical power and recheck the phasing. If the phasing is correct, open the disconnect switch or circuit protection switch and remove the phase sequence indicator.
Voltage Supply and Voltage Imbalance
Voltage Supply
Electrical power to the unit must meet stringent requirements for the unit to operate properly.
Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit.
106 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Voltage Imbalance
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance =
100 X AV - VD where;
AV
AV (Average Voltage) =
Volt 1 + Volt 2 + Volt 3
3
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
221 + 230 + 227
3
= 226 Avg.
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
100 X 226 - 221
226
= 2.2%
The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.
107
Unit Start Up
108 RT-SVX36G-EN
Unit Start Up
RT-SVX36G-EN
/2B2/2B19/ 2B /2B5/2B15/ 2B
109
Unit Start Up
110 RT-SVX36G-EN
Unit Start Up
Table 36. Service test guide for component operation — Part II of II
Component
Being Tested
A
B
1A
1B
2A
2B
1A
1B
Component Configuration
Econo Exhaust VFD
Damper Damper Output
Occ
Unocc
Relay
COMPRESSOR
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
20 - 30 Ton
0% Default
0%
40 - 60 Ton
Default
0%
0%
Default
Default
0%
0%
Default
Default
70 - 105 Ton
0% Default
0% Default
2A
2B
1A & 1B
2A & 2B
A-2B1
B-2B2
A-2B1
B-2B2/2B3
1A-2B1
1B-2B2
2A-2B4
2B-2B5
1A-2B1
1B-2B2/2B3
2A-2B4
2B-2B5/2B6
1A-2B1
1B-2B2/2B3
2A-2B4
2B-2B5/2B6
1A-2B3/2B14
1B-2B1/2B2
2A-2B6/2B13
2B-2B4/2B5
1A-2B3/2B14
1B-2B1/2B2/2B19
2A-2B6/2B13
2B-2B4/2B5/2B15
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
0%
0%
Default
Default
115 - 130 Ton
0% Default
0% Default
CONDENSER FANS
20 Ton
0%
0%
0%
40 Ton
Default
0%
25 - 30 Ton
Default
Default
Default
0%
0%
0%
0%
50 Ton
Default
Default
Default
Default
0%
0%
Default
Default
0%
0%
60 - 75 Ton
Default
Default
0%
0%
0%
0%
Default
Default
Default
Default
90 Ton
0%
0%
0%
0%
Default
Default
Default
Default
105 & 115 Ton
0% Default
0%
0%
0%
Default
Default
Default
Reheat
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Sump
Pump
Sump
Heater
Dolphin
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1A-2B3/2B14
1B-2B1/2B2/2B19/2B20
2A-2B6/2B13
2B-2B4/2B5/2B15/2B21
1A
SUPPLY FAN
RETURN FAN
EXHAUST FAN
RT-SVX36G-EN
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
130 Ton
0%
0%
0%
Default
Default
Default
Closed 0% Default
24, 29, 36, 48, 59, 73, 80, 89 Ton
Closed 100% Default
Closed 100% Unocc
Closed
Closed
100%
100%
Unocc
Default
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
111
Unit Start Up
Table 36. Service test guide for component operation — Part II of II (continued)
Component
Being Tested
Component Configuration
Econo Exhaust VFD
Damper Damper Output
Occ
Unocc
Relay
Reheat
Closed Closed 100% Unocc OFF
GAS HEAT
(Full Capacity)
STAGE 1
STAGE 2
(High Fire Adjustment)
FULL MODULATING
(Low Fire Adjustment)
LIMITED MODULATING
(High Fire Adjustment)
LIMITED MODULATING
(Low Fire Adjustment)
ELECTRIC HEAT
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
100%
100%
100%
100%
100%
100%
Unocc
Unocc
Unocc
Unocc
Unocc
Unocc
OFF
OFF
OFF
OFF
OFF
OFF
Stage 1
Stage 2
Stage 3
HYDRONIC HEAT
PRE-HEATER
FRESH AIR DAMPERS
EXHAUST DAMPERS
REHEAT
Cooling Valve
Reheat Valve
Pumpout Solenoid
EVAP COND
Sump Pump
Sump Heater
Closed
Closed
Closed
Closed
Closed
100%
Open
100%
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
100%
Open
Closed
Closed
Closed
Closed
Closed
100%
100%
100%
0%
0%
0%
0%
0%
0%
0%
0%
100%
Unocc
Unocc
Unocc
Default
Default
Default
Default
Default
Default
Default
Default
Default
OFF
OFF
OFF
OFF
OFF
OFF
OFF
100-0
0-100
ON
OFF
OFF
Sump
Pump
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
Sump
Heater
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Dolphin
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
Note: See Service test guide notes, p. 110 .
Important:
Do not operate the compressors for extended periods of time without the condenser fans; high head pressure will develop.
Table 37. Service test guide component operation—evaporative condenser
Component Being Tested
Compressors
Sump Pump
Condenser Fans
Fill Valve Relay
Drain Valve Actuator
Sump Heater
Requirements (ON) Requirements (OFF)
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
Sump minimum level switch must be closed for a minimum of five minutes No Requirements
No Requirements No Requirements
No Requirements
No Requirements
No Requirements
No Requirements
No Requirements
No Requirements
Notes:
1. Sump freeze protection is active during AUTO but is inactive in service test modes (head pressure control set to MANUAL).
2. Water treatment drain request will be ignored in service test.
112 RT-SVX36G-EN
Unit Start Up
Verifying Proper Fan Rotation
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
1.
Ensure that the “System” selection switch at the remote panel is in the “Off” position and the
“Fan” selection switch for constant volume units is in the “Auto” position. (VAV units do not utilize a “Fan” selection input.)
2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
5. Use Table 35, p. 108 to program the unit Fans for operation by scrolling through the displays.
All of the Fans (Supply, Exhaust, and Condenser fans) can be programed to be “On”, if desired.
Verify proper fan rotation for VFDs with bypass.
for the condenser fan locations and the Human Interface designator.
6. Once the configuration for the Fans is complete, press the NEXT key until the LCD displays the
“Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start.
This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
7.
Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fans will begin to operate.
8. Check the supply fan and the exhaust fans (if equipped) for proper rotation. The direction of rotation is indicated by an arrow on the fan housings. Check the condenser fans for clockwise rotation when viewed from the top.
If all of the fans are rotating backwards; a. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
b. Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the open position while working at the unit.
RT-SVX36G-EN 113
Unit Start Up
c. Interchange any two of the field connected main power wires at the unit terminal block 1TB1 or the factory mounted disconnect switch 1S14.
Note: Interchanging “Load” side power wires at the fan contactors will only affect the individual fan rotation. Ensure that the voltage phase sequence at the main terminal block 1TB1 or the factory mounted disconnect switch 1S14 is ABC as outlined in the “Electrical Phasing” section.
If some of the fans are rotating backwards;
• Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Open the field supplied disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the open position while working at the unit.
• Interchange any two of the fan motor leads at the contactor for each fan that is rotating backwards.
System Airflow Measurements
Constant Volume Systems
1.
Ensure that the “System” selection switch at the remote panel is in the “Off” position and the
“Fan” selection switch for constant volume units is in the “Auto” position. (VAV units do not utilize a “Fan” selection input.)
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT
SWITCH 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
114 RT-SVX36G-EN
Unit Start Up
Figure 48. Condenser fan location with human interface designator
20 Tons
25-30 Tons
40 Tons
50 Tons
60-75 Tons
RT-SVX36G-EN
5. Use Table 35, p. 108 to program the Supply Fan for operation by scrolling through the displays.
6. Once the configuration for the Fan is complete, press the NEXT key until the LCD displays the
“Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start.
This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
7.
Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fans will begin to operate.
115
Unit Start Up
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
8. With the system in the SERVICE MODE and the supply fan rotating in the proper direction, measure the amperage at the supply fan contactor 1K16 & 1K15 (additional contactor for 90 thru
75 Ton units). If the amperage exceeds the motor nameplate value, the static pressure is less than design and the airflow is too high. If the amperage is below the motor nameplate value, static pressure may be too high and CFM may be too low. To determine the actual CFM (± 5%); a. Measure the actual fan RPM b. Calculate the Theoretical BHP
Actual Motor Amps
Motor Nameplate Amps
X Motor HP c. Plot this data onto the appropriate Fan Performance Curve in
. Where the two points intersect, read straight down to the CFM line.
Use this data to assist in calculating a new fan drive if the CFM is not at design specifications.
An alternate method with less accuracy is to measure the static pressure drop across the evaporator coil. This can be accomplished by; i. drilling a small hole through the unit casing on each side of the coil.
Note: Coil damage can occur if care is not taken when drilling holes in this area.
ii. Measure the difference between the pressures at both locations. iii. Plot this value onto the appropriate pressure drop curve in Figure 54 . Use the data in
(Component Static Pressure Drops) to assist in calculating a new fan drive if the
CFM is not at design specifications. iv. Plug the holes after the proper CFM has been established.
9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
Exhaust Airflow Measurement (Optional with all Units)
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1.
Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT
SWITCH 1S14.
2. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
116 RT-SVX36G-EN
Unit Start Up
3. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
4. Use Table 35, p. 108 to program the following system components for operation by scrolling through the displays;
– Exhaust Fan
– Exhaust Dampers (100% Open, if applicable)
– Fresh Air dampers (100% Open)
– Variable Frequency Drive (100%, if applicable)
– RTM Occ/Unocc Output (Default)
5. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
6. Press the TEST START key to start the test. Remember that the delay designated in step 5 must elapse before the fans will begin to operate.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
7.
With the exhaust dampers open and the exhaust/return fan operating at full airflow capability, measure the amperage at the exhaust fan contactor 1K17. If the amperage exceeds the motor nameplate value, the static pressure is less than design and airflow is too high. If the amperage is below the motor nameplate value, static pressure may be too high and CFM may be too low.
To determine the actual CFM (± 5%); a. Measure the actual fan RPM b. Calculate the Theoretical BHP
Actual Motor Amps
Motor Nameplate Amps
X Motor HP
Use
- Table 43 to calculate a new fan drive if the CFM is not at design specifications.
8. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
Traq Sensor Airflow Measurement (Optional with all units equipped with an economizer)
1.
Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
2. Use Table 35, p. 108 to program the following system components for Economizer operation by scrolling through the displays;
– Supply Fan (On)
– Fresh Air dampers (Selected % Open)
RT-SVX36G-EN 117
Unit Start Up
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– Outside Air CFM Setpoint
– Outside Air Pre-Heater Operation (if applicable)
3. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
4. Press the TEST START key to start the test. Remember that the delay designated in step 3 must elapse before the fans will begin to operate.
5. With the unit operating in the “TEST MODE”, the amount of outside air flowing through the Traq sensor can be view by switching to the “STATUS MENU” screen “OA CFM”.
6. Scroll to the “ECONOMIZER ENABLE/ECONOMIZER POSITION” screen by pressing the
“NEXT” key and read the corresponding damper opening percentage (%).
7.
Press the STOP key at the Human Interface Module in the unit control panel to stop the unit operation.
Return Plenum Pressure Control (Units equipped with Return Fan)
“Return Plenum Pressure Max Setpoint” determination:
1.
Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
2. If not already STOPPED, press the STOP key on the Human Interface (HI)
3. Under HI Service Menu, insure all outputs are OFF or CLOSED.
4. Press the Start Service Test key.
5. Adjust the Exhaust Damper Position to approx. 85%.
6. Start the Supply Fan and Return Fan.
7.
Adjust the Supply Fan and Return Fan speeds to 100%.
8. Slowly adjust the Outside Air Damper to approx. 100%.
9. While measuring the building static pressure, slowly adjust the Return Fan Speed down until the building pressure reaches design conditions.
10. Make note of the return plenum pressure reading on the HI.
11. Set the “Return Plenum Pressure Max Setpoint” parameter on the HI to the value noted in the previous step.
“OA Normalization” determination (Units equipped with TRAQs):
1.
Perform a normal airflow balance of the unit.
2. Insure Exhaust Damper is approx. 85%, and the Supply Fan and Return Fan speed is 100%, and the Outdoor Air Damper is approx. 100%.
3. Make note of the total TRAQ airflow reading on the Human Interface (HI).
4. Set the “OA Normalization” parameter on the HI to the value noted in the previous step.
118 RT-SVX36G-EN
Unit Start Up
Fan Performance Tables
Figure 49. 20 & 25 / 24 & 29 Ton supply fan performance
8.0
7.5
7.0
6.5
1700 RPM
1600 RPM
6.0
5.5
5.0
1500 RPM
1400 RPM
4.5
4.0
1300 RPM
1200 RPM
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0
1100 RPM
1000 RPM
900 RPM
800 RPM
700 RPM
600 RPM
500 RPM
2000
3 HP
4000 6000
7.5 HP
5 HP
8000
20 HP
10 HP
15 HP
10000
CFM
12000
50%
90%
14000 16000 18000 20000
60%
70%
80%
S_HL*20 & 25, 24 & 29 Ton
Dual 15 X 15 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust Fan
Fan Curve Limits
- Minimum Motor HP = 3
- Maximum Motor HP
C20 & C25 = 15 HP
- Maximum RPM
3 HP - 5 HP = 1100
7.5 HP - 15 HP = 1655
- Maximum CFM
C20 = 9,000
C25 = 11,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
Figure 50. 30/36 ton supply fan performance
8.0
7.5
7.0
6.5
6.0
5.5
5.0
1400 R P M
1300 R P M
1200 R P M
4.5
4.0
3.5
1100 R P M
1000 R P M
3.0
2.5
900 R P M
800 R P M
2.0
1.5
1.0
0.5
0.0
0
700 R P M
600 R P M
500 R P M
2000 4000
3 HP
6000
5 HP
8000
7.5 HP
10 HP
10000
CFM
15 HP
12000
20 HP
25 HP
14000 16000
70%
18000 20000
50%
S_HL* 30/36 Ton
Dual 18 X 18 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 5
- Maximum Motor HP = 20
- Maximum RPM = 1379
- Maximum CFM = 13,500
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
60%
80%
90% wocfm
RT-SVX36G-EN 119
Unit Start Up
Figure 51. 40 & 50, 55 / 48 & 59 ton supply fan performance
5.0
4.5
4.0
3.5
8.0
7.5
7.0
6.5
6.0
5.5
3.0
2.5
1200 RPM
1100 RPM
1000 RPM
900 RPM
800 RPM
700 RPM
10 HP
7.5 HP
15 HP
25 HP
20 HP
30 HP
40 HP
50%
2.0
1.5
600 RPM
5 HP
1.0
0.5
0.0
0
500 RPM
2000 4000 6000 8000
90%
10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000
CFM
60%
70%
80%
S_HL* 40 & 50, 55, 48 & 59 Ton
Dual 20 X 20 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
40,
*
50 = 30 HP
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
*40 = 18,000
*50 = 22,500
*55 = 24,750
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
0
Figure 52. 60-75, 73-89 ton supply fan performance
6.0
5.5
5.0
4.5
4.0
3.5
8.0
7.5
7.0
6.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
0
1100 RPM
1000 RPM
900 RPM
800 RPM
700 RPM
600 RPM
500 RPM
3000
1200 RPM
6000 9000
10 HP
7.5 HP
20 HP
15 HP
30 HP
50 HP
40 HP
25 HP
80%
90% wocfm
12000 15000 18000
CFM
21000 24000 27000 30000 33000 36000
50%
60%
S_HL*60, *70, *75 Ton
*73, *80, *89 Ton
Dual 22 X 22 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 40
- Maximum RPM = 1130
- Maximum CFM
60 = 27,000
70* & 75* = 30,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
70%
120 RT-SVX36G-EN
Figure 53. 90, 105, 115 and 130 ton supply fan performance
9
8
1600 RPM
1500 RPM
4
0
%
W
O
C
F
M
5
0
%
W
O
C
F
M
7
1400 RPM
6
1300 RPM
5
1200 RPM
4
3
2
1100 RPM
1000 RPM
900 RPM
20
H
P
25
H
P
30
H
P
6
0
%
W
O
C
F
M
40
HP
50
HP
60 H
P
75 HP
100 HP
70
%
W
O
C
F
M
80
%
W
OC
FM
90%
WO
CFM
1
0
0 10000 20000 30000
CFM
40000 50000 60000
Unit Start Up
RT-SVX36G-EN 121
Unit Start Up
Pressure Drop Tables
Figure 54. Wet airside pressure drop at 0.075 lb/cu.ft. 20 - 89 ton evaporator coil
Figure 55. Dry airside pressure drop at 0.075 lb/cu.ft. 20 - 89 ton evaporator coil
122 RT-SVX36G-EN
Figure 56. Wet airside pressure drop at 0.075 lb/cu.ft. 90 - 130 ton evaporator coil
Evaporator Wet Airside Pressure Drop at 0.075 lb/cu.ft. 20-130 Ton
2.0
20-
25 T
30 T
40 T
60,
70,
75T
90 T
S
TD
90 H ig h 115,
130 T
1.0
0.9
0.8
0.7
0.6
0.5
0.4
105 T
50
T
0.3
0.2
0.1
4000 6000 800010000 20000
Unit Airflow, CFM
40000 60000
Figure 57. Dry airside pressure drop at 0.075 lb/cu.ft. 90 - 130 ton evaporator coil
Evaporator Dry Airside Pressure Drop at 0.075 lb/cu.ft. 20-130 Ton
2.0
20-
25 T
30
T 40 T
50
T
60,
70,
75 T
90 T
S
TD
90 H ig h 115,
130 T
1.0
0.9
0.8
0.7
0.6
0.5
0.4
105 T
0.3
0.2
0.1
4000 6000 800010000 20000
Unit Airflow, CFM
RT-SVX36G-EN
40000 60000
Unit Start Up
123
Unit Start Up
Std Ro
124
Nom (AC/ EC)
RT-SVX36G-EN
Std Ro
Econ. w/ or w/
Std Ro
Perm Wire
Unit Start Up
Nom (AC/ EC)
RT-SVX36G-EN
Cfm Std
125
Unit Start Up
Table 40. Component static pressure drops (in. W.G.)—exhaust damper for return fan
Nom Tons
(AC/EC)
20/24
25/29
30/36
40/48
Cfm
4000
10000
11000
12500
14000
6000
9000
12000
14000
6000
8000
9000
10000
12000
5000
6000
7500
15000
17000
8000
10000
12000
16000
17000
20000
22000
Exhaust Damper for Return Fan
0.08
0.55
0.67
0.85
1.08
0.19
0.44
0.79
1.08
0.19
0.35
0.44
0.55
0.79
0.13
0.19
0.3
1.2
1.6
0.18
0.28
0.41
0.73
0.82
1.15
1.39
Nom Tons Cfm
10000
50/55/59
60/73
70/80
75/89
26000
28000
31000
33000
12000
16000
20000
22000
24000
26000
28000
31000
24000
28000
30000
12000
16000
20000
22000
24000
14000
17000
20000
24000
28000
12000
16000
20000
Exhaust Damper for Return Fan
0.28
1.47
1.73
-
-
0.31
0.56
0.88
1.05
1.27
1.47
1.73
-
1.27
1.73
1.99
0.31
0.56
0.88
1.05
1.27
0.56
0.75
1.15
1.66
2.26
0.31
0.56
0.88
Notes:
1. Exhaust Damper drop is only added when Return Fan is ordered.
2. Use Return CFM for exhaust damper drop add on return fan selections.
33000 -
126 RT-SVX36G-EN
Unit Start Up
Table 41. 20-89 tons - modulating 100% exhaust fan performance
Cfm
Nominal Std 0.250
0.500
0.750
Negative Static Pressure
1.000
1.250
1.500
1.750
2.000
Tons
(AC/EC) Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4000 399 0.38
538 0.75
640 1.08
730 1.45
811 1.87
882 2.34
947 2.88
20/24
25/29
6000 453
8000 547
10000 640
4000 399
6000 453
8000 547
10000 640
12000 737
0.74
1.59
2.79
0.38
0.74
1.59
2.79
4.44
570
619
538
570
619
712
1.17
1.81
0.75
1.17
1.81
3.25
675
711
640
675
711
767
1.65
2.48
1.08
1.65
2.48
3.48
765
797
730
765
797
837
2.22
3.01
1.45
2.22
3.01
4.26
845
811
845
876
911
2.78
1.87
2.78
3.66
5.04
822
912
947
2.34
3.27
4.40
947
975
2.88
3.77
1017
1036
3.55
4.30
30/36
4000 399
6000 453
8000 547
10000 640
12000 737
14000 837
0.38
0.74
1.59
2.79
4.44
6.67
538 0.75
640
570 1.17
675
619 1.81
711
712
806
3.25
5.22
767
860
1.08
1.65
2.48
3.48
5.64
730
765
797
837
905
1.45
2.22
3.01
4.26
5.89
811
845 2.78
912 3.27
975 3.77
1036 4.30
876 3.66
947 4.40 1013 5.18
1075 5.94
911
956
1.87
5.04
6.49
882
980
2.34
947 2.88
5.70 1045 6.46
1017
1106
40/48
7500 334
9000 362
12000 435
0.75
1.09
2.19
438 1.21
535
449 1.57
536
496 2.70
563
1.77
2.16
3.35
616
618
628
2.35
2.84
4.04
686 2.98
750 3.64
809 4.34
689 3.52
753 4.24
812 4.99
693 4.83
757 5.71
817 6.63
14000
16000
9000
486
537
362
3.22
4.55
1.09
2.19
3.85
6.21
542
592
449
3.86
5.35
1.57
594
636
536
496 2.70
563
567 4.56
614
642 7.16
685
4.47
6.00
2.16
3.35
5.18
7.97
653
683
618
628
667
724
5.25
6.74
2.84
4.04
5.96
8.69
707 6.04
763 6.91
819 7.86
735 7.64
783 8.53
831 9.47
689 3.52
753 4.24
812 4.99
693 4.83
757 5.71
817 6.63
880
867
873
50/55/59
60/73
12000 435
15000
18000
511
590
20000 644
12000 351
15000 412
18000 478
21000
24000
27000
12000
547
617
688
351
8.26
1.49
2.68
4.41
692 9.35
735 10.33
772
423 2.09
502 3.00
572
460 3.15
521
516 4.88
557
3.96
5.54
585
607
6.75
9.83
578 7.36
612 7.92
644 10.59
672 11.22
15.11
711 15.09
736 15.45
1.49
423 2.09
502 3.00
647
702
761
572
11.17
4.02
5.02
6.49
8.71
11.88
16.18
4.02
720 6.80
771 7.66
824 8.60
876
766 9.54
812 10.54
856 11.55
898
807
634
646
662
11.97
5.07
6.24
7.66
844 12.91
690
702
715
6.09
7.53
9.01
885
740
754
766
14.00
7.04
8.83
10.48
926
784
801
814
688 9.77
735 11.03
781 12.46
827
732 12.77
766 13.89
805 15.22
846
788 17.02
815 17.92
844 18.99
876
634 5.07
690 6.09
740 7.04
784
70/75
80/89
15000 412
18000 478
21000 547
24000 617
2.68
4.41
6.75
9.83
460
516
3.15
4.88
521
557
3.96
5.54
578 7.36
612 7.92
644 10.59
672 11.22
585
607
5.02
6.49
647 8.71
702 11.88
646
662
6.24
7.66
702
715
7.53
9.01
754
766
8.83
10.48
801
814
688 9.77
735 11.03
781 12.46
827
732 12.77
766 13.89
805 15.22
846
27000 688 15.11
711 15.09
736 15.45
761 16.18
788 17.02
815 17.92
844 18.99
876
Note:
Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
864
867
873
874
3.55
7.31
5.06
5.77
8.53
8.89
10.48
5.77
7.53
9.63
12.56
15.13
7.91
10.14
12.01
14.03
16.72
20.31
7.91
10.14
12.01
14.03
16.72
20.31
RT-SVX36G-EN 127
Unit Start Up
Table 42. 90-130 Tons modulating 100% exhaust fan performance
Cfm Negative Static Pressure
Nominal Std
Tons
0.250
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
2.500
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
90-130
28000 516 11.42 551 12.41 586 13.70 622 15.25 657 16.71 690 18.16 723 19.90 754 21.74 785 23.60 815 25.45
30000 550 13.94 579 14.86 614 16.25 646 17.72 680 19.45 712 20.93 743 22.54 773 24.41 803 26.38 832 28.36
32000 583 16.82 609 17.68 642 19.12 672 20.58 704 22.34 735 24.12 764 25.67 793 27.42 822 29.41 850 31.50
34000 617 20.09 640 20.92 670 22.30 700 23.87 728 25.53 759 27.51 788 29.30 815 30.96 842 32.82 869 34.93
36000 650 23.76 672 24.58 699 25.86 728 27.55 755 29.19 782 31.11 811 33.21 838 35.05 864 36.81 889 38.77
38000 684 27.86 704 28.68 728 29.87 757 31.60 783 33.33 808 35.14 834 37.30 861 39.48 887 41.38 911 43.23
40000 718 32.41 737 33.24 758 34.36 785 36.02 811 37.91 835 39.71 859 41.74 885 44.08 910 46.33 934 48.32
Notes:
1. Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
2. Refer to General Data Table for minimum and maximum hp's.
Table 43. 20-89 tons - 50% exhaust fan performance
Cfm
Std 0.200
0.400
Negative Static Pressure (In. W.G.)
0.600
0.800
1.000
Nominal
Tons
(AC/EC)
20/25
24/29
30/36
40/48
50/55/59
60/73
1.200
1.400
Air
2000
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
364 0.17
487 0.30
582 0.45
658 0.58
731 0.73
797 0.90
856 1.08
4000
5000
6000
7000
3000
5000
7000
3000
4000
5000
6000
2000
3000
9000 578
11000 688
3000
5000
288
372
7000
9000
472
578
435
529
623
722
364
435
529
623
722
824
288
372
472
11000 688
4000 271
6000 339
8000 425
10000 517
12000 612
13000 659
0.83
1.82
3.41
5.80
0.54
0.90
1.73
3.13
5.15
6.44
0.86
1.56
2.47
3.64
0.38
0.83
1.82
3.41
5.80
0.38
0.51
0.86
1.56
2.47
0.30
0.51
430
522
621
725
364
391
460
543
633
679
592
687
779
874
393
430
522
621
725
393
522
592
687
779
487
522
0.66
1.55
3.06
5.36
0.29
0.71
1.55
2.88
4.84
6.09
0.76
1.32
2.13
3.23
0.22
0.66
1.55
3.06
5.36
0.22
0.36
0.76
1.32
2.13
0.17
0.36
557
606
695
793
499
517
542
600
678
720
728
778
870
965
547
557
606
695
793
547
694
728
778
870
658
694
1.05
2.04
3.76
6.24
0.82
1.22
1.96
3.34
5.43
6.76
1.03
1.67
2.72
4.02
0.55
1.05
2.04
3.76
6.24
0.55
0.67
1.03
1.67
2.72
0.45
0.67
495
563
661
760
438
456
497
571
655
699
654
735
830
922
477
495
563
661
760
477
614
654
735
830
582
614
621
653
725
823
550
572
591
632
702
741
765
797
836
905
731
765
797
836
905
1.51
2.13
2.96
1000 4.48
611 0.94
621
653
1.57
2.59
725
823
611
4.34
7.06
0.94
1.11
1.51
2.13
2.96
0.73
1.11
1.57
2.59
4.34
7.06
1.30
2.01
2.72
3.94
5.95
7.31
1.29
2.29
4.06
6.66
1.07
1.60
2.30
3.59
5.68
7.04
1.29
1.79
2.86
4.30
0.74
1.29
2.29
4.06
6.66
0.74
0.88
1.29
1.79
2.86
0.58
0.88
830
861
896
1.34
1.77
2.45
680
698
758
850
601
622
639
668
726
680
698
758
850
668
797
830
861
0.90
1.34
1.77
896
944
2.45
3.16
1032 4.59
668 1.16
1.87
2.91
4.65
7.42
1.16
1.87
2.91
4.65
7.42
1.56
2.43
3.20
4.37
6.29
886
919
953
1.54
2.05
2.72
732
742
794
875
651
668
684
707
752
732
742
794
875
721
856
886
919
1.08
1.54
2.05
953
994
2.72
3.59
1062 4.72
721 1.39
2.16
3.24
5.01
7.76
1.39
2.16
3.24
5.01
7.76
1.87
2.85
3.73
4.87
6.71
128 RT-SVX36G-EN
Unit Start Up
Table 43. 20-89 tons - 50% exhaust fan performance
4000
6000
8000
271
339
425
0.29
0.71
1.55
364
391
460
0.54
0.90
1.73
438
456
497
0.82
1.22
1.96
499
517
542
1.07
1.60
2.30
550
572
591
1.30
2.01
2.72
70/75
80/89
10000 517
12000 612
13000 659
2.88
4.84
6.09
543
633
679
3.13
5.15
6.44
571
655
699
3.34
5.43
6.76
600
678
720
3.59
5.68
7.04
632
702
741
3.94
5.95
7.31
Note:
Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
601
622
639
668
726
1.56
2.43
3.20
4.37
6.29
651
668
684
707
752
1.87
2.85
3.73
4.87
6.71
Table 44. 90-130 Tons - 50% exhaust fan performance
Cfm
Nom
Tons
Std 0.250
0.500
0.750
Negative Static Pressure (In. W.G.)
1.000
1.250
1.500
1.750
2.000
2.250
2.500
Air RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
12000 452 3.68 495 4.21
536 4.85 576 5.46 614 6.17 651 6.95 687 7.73 722 8.55 759 9.46 797 10.45
90-130
14000 516 5.71 551 6.21
586 6.85 622 7.63 657 8.36 690 9.09 723 9.96 754 10.88 785 11.79 815 12.72
16000 583 8.41 609 8.85
643 9.57 672 10.29 704 11.18 735 12.07 764 12.84 793 13.72 822 14.72 850 15.76
18000 650 11.88 672 12.29 699 12.94 729 13.79 755 14.59 782 15.56 811 16.62 838 17.53 864 18.41 889 19.39
20000 718 16.20 737 16.62 758 17.18 785 18.03 811 18.97 835 19.86 859 20.87 885 22.05 910 23.18 934 24.17
Note:
Shaded areas indicate non-standard drive selections. These drive selections must be manually factory selected.
RT-SVX36G-EN 129
Unit Start Up
Table 45. Return fan performance—20, 25, 30 tons AC; 24, 29, 36 tons EC (24.5”)
CFM
Std.
Air
4000
4500
5000
5500
6000
6500
7000
7500
8000 967
8500 1021
9000 1075
9500 1130
10000 1186
10500 1241
0.25
RPM BHP
557 0.29
605
654
704
0.36
0.44
0.53
756
808
861
913
0.64
0.76
0.90
1.06
1.24
1.44
1.67
1.92
2.20
2.50
0.50
RPM BHP
638 0.48
682
727
773
821
868
917
968
0.57
0.67
0.79
0.92
1.06
1.21
1.39
1019 1.58
1071 1.80
1123 2.04
1175 2.31
1228 2.60
1280 2.92
0.75
RPM BHP
710 0.68
Negative Static Pressure
1.00
1.25
RPM BHP RPM BHP
776 0.89
838 1.10
749
790
834
879
925
972
1019
1068
1116
1166
1217
1269
1321
0.79
0.91
1.04
1.20
1.36
1.55
1.74
1.96
2.19
2.45
2.73
3.04
3.37
811
850
889
932
976
1021
1068
1115
1162
1210
1258
1307
1357
1.02
1.16
1.30
1.47
1.66
1.87
2.10
2.34
2.60
2.88
3.17
3.50
3.85
869
905
943
982
1024
1067
1112
1158
1204
1252
1299
1347
1395
1.25
1.41
1.58
1.77
1.97
2.19
2.44
2.71
3.00
3.30
3.62
3.97
4.34
1.50
RPM BHP
899 1.32
926
957
992
1030
1070
1112
1155
1199
1244
1290
1337
1384
1432
1.49
1.67
1.86
2.06
2.29
2.53
2.79
3.08
3.39
3.72
4.07
4.45
4.85
1.75
RPM BHP
969 1.60
980
1007
1040
1076
1114
1154
1196
1238
1283
1327
1373
1419
1466
1.73
1.93
2.15
2.38
2.61
2.87
3.15
3.45
3.79
4.14
4.52
4.91
5.33
11000 1297
11500 1353
12000 1408
2.84
3.20
3.60
1334 3.27
1387 3.64
1441 4.06
1373
1425
1477
3.74
4.13
4.56
1409
1460
1512
4.23
4.64
5.08
1443
1493
1544
4.74
5.16
5.62
1480
1528
1576
5.26
5.71
6.18
1515
1561
1610
5.79
6.25
6.75
1546
1594
1642
6.29
6.79
7.32
12500 1464
13000 1520
13500 1576
14000 1633
4.03
4.49
4.99
5.52
1496
1551
1606
1661
4.50
4.98
5.50
6.05
1530
1583
1636
1690
5.01
5.51
6.03
6.60
1565
1617
1669
1721
5.56
6.06
6.60
7.19
1596
1648
1700
1752
6.11
6.64
7.20
7.79
1626
1677
1728
1780
6.68
7.22
7.80
8.42
1658
1707
1756
1807
7.28
7.84
8.42
9.05
1689
1737
1785
1834
Notes:
1. Max fan RPM 1715 for 24.5" Class I Fan
2. Max motors Available are as follows: 20T: 3HP, 25T: 5HP, 30T: 7.5 HP
3. Max CFM available is as follows; 20T: 9000, 25T: 11000, & 30T: 13500
4. Min CFM is 4000 for 20T, 25T, & 30T
5. Return fan belt drive RPM selections will be available to cover 500-1600 RPM range +/- 50 RPM
6. Performance data includes cabinet and rain hood effect. Damper pressure drop must be added to the return duct static per Table 40, p. 126
7. Shaded area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.
7.87
8.44
9.06
9.70
1277
1320
1363
1408
1454
1500
2.00
RPM BHP
1038 1.89
1033
1057
1087
1.99
2.20
2.44
1121
1157
1195
1235
2.70
2.95
3.22
3.51
3.84
4.19
4.56
4.96
5.38
5.84
130 RT-SVX36G-EN
Unit Start Up
Table 46. Return fan performance—40, 50, 55 tons AC; 48, 59 tons EC (27”)
CFM
Std.
Air
7500
8000
8500
9000
0.25
RPM BHP
709 0.82
748
788
827
0.95
1.09
1.24
9500 867
10000 908
10500 948
11000 989
1.41
1.60
1.81
2.04
11500 1030
12000 1071
12500 1112
13000 1153
13500 1194
14000 1236
14500 1277
15000 1319
15500 1361
16000 1402
16500 1444
17000 1486
4.21
4.62
5.05
5.51
6.00
6.52
2.28
2.55
2.83
3.14
3.47
3.83
0.50
RPM BHP
766
803
840
878
916
955
1.16
1.31
1.47
1.64
1.83
2.04
994 2.27
1033 2.51
1072 2.78
1112 3.06
1152 3.37
1192 3.70
1232 4.05
1272 4.42
1313 4.82
1353 5.25
1394 5.71
1435 6.18
1476 6.69
1517 7.23
0.75
RPM BHP
815 1.50
Negative Static Pressure
1.00
1.25
RPM BHP RPM BHP
861 1.85
906 2.22
851
887
924
1.67
1.86
2.05
895
930
965
2.04
2.24
2.46
938
971
1005
2.43
2.64
2.88
961
999
1036
1074
1346
1386
1426
1466
1506
1547
1112
1151
1189
1228
1267
1307
2.27
2.50
2.75
3.01
3.29
3.59
3.92
4.27
4.63
5.03
5.45
5.90
6.37
6.87
7.40
7.96
1001
1038
1075
1112
1149
1187
1225
1263
1301
1340
1379
1417
1457
1496
1535
1575
2.70
2.95
3.23
3.51
3.82
4.14
4.48
4.86
5.24
5.66
6.10
6.55
7.05
7.57
8.12
8.70
1040
1075
1111
1147
1184
1221
1258
1296
1333
1371
1410
1448
1486
1525
1564
1603
3.14
3.41
3.70
4.01
6.75
7.23
7.74
8.28
8.85
9.44
4.33
4.69
5.06
5.45
5.85
6.29
1.50
RPM BHP
949 2.60
979
1010
1043
1076
1111
1145
1181
1216
1253
1290
1327
1364
1401
2.82
3.05
3.31
3.58
3.88
4.18
4.51
4.86
5.24
5.62
6.04
6.47
6.94
1248
1284
1320
1356
1393
1430
1.75
RPM BHP
991 2.99
1018
1049
1080
3.22
3.48
3.75
1112
1145
1179
1213
4.03
4.34
4.68
5.02
5.38
5.78
6.19
6.63
7.08
7.57
1279
1314
1349
1385
1421
1457
2.00
RPM BHP
1033 3.39
1058
1087
1115
3.64
3.92
4.19
1146
1179
1212
1245
4.50
4.83
5.18
5.53
1439
1477
1514
7.42
7.92
8.44
1467
1504
1542
8.08
8.61
9.16
1494
1531
1569
8.73
9.29
9.87
1553
1591
9.01
9.58
1580
1617
9.74
10.34
1606
1643
10.47
11.10
1629 10.20
1655 10.97
1681 11.75
17500 1528
18000 1570
18500 1612
7.07
7.65
8.26
1558 7.80
1599 8.40
1640 9.03
1587
1627
1668
8.55
9.17
9.81
1615
1655
9.30
9.94
1642
1681
10.07
10.73
1668
1707
10.85
11.53
1694
1732
11.64
12.33
1718
1757
12.43
13.15
1695 10.62
1721 11.43
1746 12.23
1771 13.07
1794 13.89
19000 1654
19500 1696
8.91
9.59
1682
1723
9.70
10.40
1709
1749
10.50
11.22
1735
1775
11.31
12.06
1760
1800
12.14
12.90
1785
1825
12.97
13.76
1809
1848
13.82
14.62
1833
1872
14.67
15.50
20000 1738 10.30
1765 11.13
1790 11.97
1816 12.83
1840 13.69
1864 14.56
1888 15.46
1910 16.34
20500 1780 11.05
1806 11.90
1831 12.76
1856 13.63
1880 14.52
1903 15.41
1926 16.31
1949 17.22
21000 1822 11.84
1848 12.71
1872 13.59
1897 14.48
1920 15.39
1943 16.29
1966 17.23
1988 18.14
21500 1864 12.66
1889 13.55
1914 14.45
1937 15.36
1960 16.29
1983 17.22
2005 18.16
2027 19.11
22000 1899 13.05
1926 14.11
1952 15.16
1977 16.20
2001 17.23
2024 18.24
2047 19.27
2069 20.28
22500 1941 13.91
1967 14.98
1992 16.05
2017 17.12
2041 18.19
2064 19.23
2086 20.27
2108 21.31
5.92
6.33
6.76
7.23
7.70
8.20
Notes:
1. Max fan RPM 1981 For 27" Class II Fan
2. Max Motor Available 15 HP For 27" Fan Size
3. Max motors Available are as follows: 40T: 10 HP & 50/55T: 15 HP
4. Max CFM is as follows: 40T: 18000, 50/55T: 22500)
5. Min CFM is as follows: 40T: 7500 & 50/55T: 9000
6. Return fan belt drive RPM selections will be available to cover 700-1900 RPM range +/- 50 RPM
7. Performance data includes cabinet and rain hood effect. Damper pressure drop will have to be added to the return duct static per Table 40, p. 126
8. Shaded area indicates nonstandard BHP or RPM selections. Contact a local Trane representative for more information.
RT-SVX36G-EN 131
Unit Start Up
Table 47. Return fan performance—60, 70, 75 tons AC; 73, 80, 89 tons EC (36.5” fan)
CFM
Std.
Air
12000
13000
14000
15000
16000
17000
18000
19000
0.25
RPM BHP
459 1.07
490
520
552
1.27
1.49
1.73
583
615
646
678
2.00
2.30
2.64
3.01
0.50
RPM BHP
502 1.59
530
560
590
1.83
2.09
2.38
619
650
680
711
2.70
3.05
3.43
3.85
RPM
0.75
BHP
541 2.13
Negative Static Pressure
1.00
1.25
RPM BHP RPM BHP
578 2.71
613 3.31
567
595
623
2.40
2.70
3.03
603
628
655
3.01
3.34
3.70
636
660
686
3.65
3.99
4.39
652
681
711
741
3.39
3.78
4.20
4.67
682
710
739
768
4.09
4.52
4.98
5.48
712
739
766
794
4.82
5.28
5.78
6.31
1.50
RPM BHP
647 3.91
668
691
715
4.29
4.69
5.11
740
766
792
819
5.57
6.06
6.60
7.16
RPM
1.75
BHP
681 4.54
700
721
744
4.94
5.38
5.85
767
792
817
844
6.34
6.85
7.41
8.03
2.00
RPM BHP
713 5.20
731
751
771
5.64
6.10
6.59
794
818
842
867
7.14
7.67
8.27
8.89
20000
21000
22000
23000
24000
25000
711
743
775
808
840
873
3.42
3.87
4.36
4.89
5.46
6.08
742
773
805
836
868
900
4.30
4.78
5.31
5.88
6.49
7.15
771
801
832
863
894
925
5.17
5.70
6.28
6.90
7.56
8.26
797
827
857
887
918
948
6.02
6.60
7.22
7.89
8.60
9.35
823
852
881
911
941
970
6.90
7.51
8.17
8.88
9.63
10.42
847
875
904
933
962
992
7.77
8.41
9.11
9.87
871
898
926
954
8.66
9.36
10.09
10.86
894
920
947
975
9.59
10.30
11.06
11.88
10.67
983 11.71
1004 12.75
11.49
1012 12.59
1032 13.67
26000
27000
906
939
6.75
7.47
931
963
7.86
8.62
956
987
9.00
9.79
979
1010
10.16
11.01
1001
1031
11.28
12.18
1021
1052
12.37
13.33
1041
1071
13.49
14.47
1061
1090
14.63
15.65
Notes:
1. Max fan RPM 1151 for 36.5" Class I Fan
2. Max motor available 20 HP for 36.5" fan size
3. Max motor available 20 HP for 60, 70 & 75T/ 73, 80 & 89T
4. Max CFM is 27000 for 60, 70 & 75T/ 73, 80 & 89T
5. Min CFM is 12000 for 60, 70 & 75T/ 73, 80 & 89T
6. Return fan belt drive RPM selections will be available to cover 500-1100 RPM range +/- 50 RPM
7. Performance data includes cabinet and rain hood effect. Damper pressure drop will have to be added to return duct static per table Table 40, p. 126
Economizer Damper Adjustment
Exhaust Air Dampers
Verify that the exhaust dampers (if equipped) close tightly when the unit is off. Adjust the damper linkage as necessary to ensure proper closure. An access panel is provided under each damper assembly.
Fresh Air & Return Air Damper Operation
The fresh air and return air damper linkage is accessible from the filter section of the unit. The damper linkage connecting the fresh air dampers to the return air dampers is preset from the factory in the number 1 position. Refer to
for the appropriate linkage position for the unit and operating airflow (CFM).
WARNING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Note: Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.
Arbitrarily adjusting the fresh air dampers to open fully when the return air dampers are closed or; failing to maintain the return air pressure drop with the fresh air dampers when the return air
132 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
dampers are closed, can overload the supply fan motor and cause building pressurization control problems due to improper CFM being delivered to the space.
The fresh air/return air damper linkage is connected to a crank arm with a series of holes that allows the installer or operator to modify the amount of fresh air damper travel in order to match the return static pressure. Refer to
for the equivalent return air duct losses that correspond to each of the holes illustrated in
.
To Adjust the Fresh Air Damper Travel:
1.
Drill a 1/4” hole through the unit casing up stream of the return air dampers. Use a location that will produce an accurate reading with the least amount of turbulence. Several locations may be necessary, and average the reading.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.
2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the applicable programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
5. Use Table 35, p. 108 to program the following system components for operation by scrolling through the displays;
– Supply Fan (On)
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– Fresh Air Dampers (Closed)
6. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
7.
Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate.
8. With the fresh air dampers fully closed and the supply fan operating at 100% airflow requirements, measure the return static pressure at the location determined in step 1.
9. Press the STOP key at the Human Interface Module in the unit control panel to stop the fan operation.
133
Unit Start Up
WARNING
Rotating Components!
The following procedure involves working with rotating components. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury.
10. Open the field supplied main power disconnect switch upstream of the rooftop unit. Lock the disconnect switch in the “Open” position while working on the dampers.
11. Compare the static pressure reading to the static pressure ranges and linkage positions in
Table 48, p. 134 for the unit size and operating CFM.
To relocate the fresh air/return air connecting rod to balance the fresh air damper pressure drop against the return static pressure, use the following steps. If no adjustment is necessary, proceed to step 17.
12. Remove the drive rod and swivel from the crank arm(s). If only one hole requires changing, loosen only that end.
13. Manually open the return air dampers to the full open position.
14. Manually close the fresh air dampers.
15. Reattach the drive rod and swivel to the appropriate hole(s). The length of the drive rod may need to be adjusted to align with the new hole(s) location. If so, loosen the lock nut on the drive rod against the swivel. Turn the swivel “in” or “out” to shorten or lengthen the rod as necessary.
For some holes, both ends of the rod may need to be adjusted.
16. Tighten the lock nut against the swivel(s).
17. Plug the holes after the proper CFM has been established.
Table 48. F/A Damper travel adjustment
Position of Connecting Rod
Damper Crank Arm Hole
Configuration
Position #1
Position #2
Position #3
2 - 3
2 - 4
2 - 5
Position #4
Position #5
2 - 6
1 - 8
Position #6 1 - 7
Note:
As shipped from the factory, the connect rod is installed in Position #1.
Use
Table 49, p. 135 to select the appropriate crank arm hole configuration based on the;
a. specific unit b. operating CFM c. and return static pressure.
134 RT-SVX36G-EN
Unit Start Up
Table 49. Fresh air damper pressure drop (inches w.c.) — Air-Cooled and Evaporative Condensing
CFM
4000
(20, 25 Ton and 24, 29 Ton) Units
Damper Position
#1
0.03
#2 #3
0.04
0.06
#4 #5
0.13
0.16
6000
8000
9000
10000
11000
0.03
0.19
0.30
0.45
0.62
0.04
0.10
0.21
0.32
0.35
0.48
0.51
0.70
0.71
0.95
0.20
0.30
0.52
0.75
0.76
1.08
1.05
1.57
1.42
2.15
#6
0.33
0.90
1.75
2.40
-
-
CFM
10000
14000
18000
20000
22000
24000
(50, 55 and 59 Ton) Units
Damper Position
#1
0.03
#2
0.04
#3
0.09
#4
0.18
#5
0.23
0.09
0.31
0.45
0.58
0.75
0.12
0.36
0.51
0.66
0.88
0.20
0.50
0.70
0.75
1.10
0.35
0.79
1.05
1.30
1.75
0.50
1.10
1.57
1.95
2.50
#6
0.55
1.36
-
-
-
-
CFM
6000
8000
10000
11000
12000
13000
#1
0.03
(30, 36 Ton) Units
#2
Damper Position
#3 #4 #5
0.04
0.07
0.15
0.20
0.03
0.15
0.20
0.31
0.42
0.05
0.11
0.19
0.26
0.25
0.37
0.36
0.50
0.48
0.62
0.21
0.30
0.43
0.62
0.60
0.85
0.79
1.10
0.97
1.42
#6
0.43
0.90
1.50
1.85
2.40
-
(60, 70, 75 Ton and 73, 80, 89 Ton) Units
CFM
14000
#1
0.03
#2
Damper Position
#3 #4 #5
0.04
0.12
0.25
0.35
#6
1.05
18000
22000
26000
28000
30000
0.19
0.45
0.70
0.88
1.05
0.21
0.51
0.80
1.03
1.22
0.32
0.70
1.02
1.30
1.55
0.52
1.05
1.58
2.20
2.65
0.75
1.57
2.30
-
-
1.75
-
-
-
-
CFM
8000
10000
12000
14000
16000
18000
#1
(40, 48 Ton) Units
Damper Position
#2 #3 #4 #5
0.03
0.03
0.10
0.20
0.41
0.56
0.04
0.08
0.05
0.11
0.13
0.21
0.25
0.37
0.46
0.60
0.65
0.74
0.16
0.21
0.21
0.30
0.38
0.55
0.60
0.85
0.94
1.38
1.28
1.92
#6
0.52
0.90
1.40
1.85
-
-
CFM
27000
32000
36000
40000
43000
46000
#1
(90 - 130 Ton) Units
Damper Position
#2 #3 #4 #5
0.31
0.55
0.75
1.00
1.20
1.40
0.36
0.64
0.88
1.18
1.42
1.58
0.50
0.72
1.10
1.50
1.92
2.29
0.79
1.25
1.75
2.50
-
-
1.10
1.88
2.50
-
-
-
#6
2.40
-
-
-
-
-
NOTICE:
Compressors Failure!
Unit must be powered and crankcase heaters energized at least 8 hours BEFORE compressors are started. This will protect the compressors from premature failure.
RT-SVX36G-EN 135
Unit Start Up
136
Compressor Start-Up (All Systems)
1.
Ensure that the “System” selection switch at the remote panel is in the “Off” position.
2. Before closing the disconnect switch, ensure that the compressor discharge service valve and the liquid line service valve for each circuit is back seated.
NOTICE
Compressor Damage!
Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines could result in compressor damage.
COMPRESSOR SERVICE VALVES MUST BE FULLY
OPENED BEFORE START-UP (SUCTION, DISCHARGE,
AND LIQUID LINE).
3. Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14 to allow the crankcase heater to operate a minimum of 8 hours before continuing.
Figure 58. Fresh air and return air linkage adjustment
RETURN AIR
DAMPERS
Top View
3
2
1
FILTER
SECTION
5
6
4
FRESH AIR
DAMPERS
7
8
Note: Compressor Damage could occur if the crankcase heater is not allowed to operate the minimum of 8 hours before starting the compressor(s).
4. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
5. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the RT-SVP01*-EN for
CV applications or RT-SVP02*-EN for VAV applications for the SERVICE TEST screens and programming instructions.
6. Use Table 35, p. 108 to program the following system components for operation by scrolling through the displays;
• 20 to 36 Ton
– Compressor 1A (On)
– Compressor 1B (Off)
– Condenser Fans
• 40 through 130 Ton
– Compressor 1A (On)
– Compressor 1B (Off)
– Compressor 2A (Off)
– Compressor 2B (Off)
– Condenser Fans
7.
Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer
for the various compressor locations.
RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
8. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
9. Press the TEST START key to start the test. Remember that the delay designated in step 8 must elapse before the system will begin to operate.
10. It is very important to review and follow the Electrical Phasing procedure described in the startup procedure of the IOM. If the compressors are allowed to run backward for even a very short period of time, internal compressor damage may occur and compressor life may be reduced. If a scroll compressor is rotating backwards, it will not pump, make a loud rattling sound and low side shell gets hot. Immediately shut off the unit. If the phasing is incorrect, interchange any two compressor leads to correct the motor phasing.
11. Press the STOP key at the Human Interface Module in the unit control panel to stop the compressor operation.
12. Repeat steps 5 through 11 for each compressor stage and the appropriate condenser fans.
Refrigerant Charging
1.
Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer
for the various compressor locations.
2. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
3. Use Table 35, p. 108 to program the following system components for the number 1 refrigeration circuit by scrolling through the displays;
Supply Fan (On)
– OCC/UNOCC Relay (Unoccupied for VAV units)
– All Compressors for each circuit (On)
– Condenser Fans for each circuit (On)
4. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
5. Press the TEST START key to start the test. Remember that the delay designated in step 4 must elapse before the system will begin to operate.
6. After all of the compressors and condenser fans for the number 1 circuit have been operating for approximately 30 minutes, observe the operating pressures. Use the appropriate pressure curve in
p. 149 to determine the proper operating pressures. For
superheat and subcooling guidelines, refer to “Thermostatic Expansion Valves and Charging by Subcooling” at the end of this section.
Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all Federal, State and local laws. Refer to general service bulletin MSCU-SB-1 (latest edition).
7.
Verify that the oil level in each compressor is correct.
8. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
9. Repeat steps 1 through 8 for the number 2 refrigeration circuit.
137
Unit Start Up
Compressor Crankcase Heaters
20 - 73 and 80 ton units are equipped with 90 watt heaters installed on each compressor. 75 and
89 - 130 ton units are equipped with 160 watt heaters per compressor.
Compressor Operational Sounds
At Low Ambient Start-Up
When the compressor starts up under low ambient conditions, the initial flow rate of the compressor is low due to the low condensing pressure. Under this condition, it is not unusual to hear the compressor rattle until the suction pressure climbs and the flow rate increases.
Compressor – Blink Codes
The CSHN*** compressors come equipped with a compressor protection device capable of detecting phase reversal, phase loss, and phase unbalance. The compressor protection device uses a Green and Red LED to indicate the compressor status. A solid Green LED denotes a fault free condition; a blinking Red LED indicates an identifiable fault condition.
Note: If the compressor has tripped, the resistance will be 4500 ohms or greater; when reset, they will be less than 2750 ohms.
Blink Code: The blink code consists of different on / off time of the Red LED which is repeated continuously until either the fault is cleared or until power is cycled.
Table 50. CPM Blink Codes
Fault
PTC overheat or PTC reset delay active
Phase loss
Incorrect phase sequence
LED on
short blink long blink short blink
LED off
long blink long blink short blink
LED on
short blink long blink short blink
LED off
long blink long blink long blink
138 RT-SVX36G-EN
Unit Start Up
Figure 59. Compressor locations
20-36 Ton
40-89 Ton
Compressor B
HI Designator “K11”
Compressor A
HI Designator “K10”
Compressor 2B
HI Designator “K4”
Compressor 2A
HI Designator “K3”
Compressor 1B
HI Designator “K12”
Compressor 1A
HI Designator “K11”
90-130 Ton
Compressor 2B
HI Designator “K4”
Compressor 2A
HI Designator “K3”
Compressor 1B
HI Designator “K12”
Compressor 1A
HI Designator “K11”
Evaporative Condenser Startup
Important:
Water treatment by a qualified water treatment expert is required to ensure proper equipment life and product performance. Dolphin Water Care is an option offered by
Trane that is NOT a substitute for regular water treatment by a qualified water treatment professional. If a water treatment system is not operating on the unit, do not proceed.
Startup for evaporative and air-cooled condensers is initially the same. In addition, the following is required for evaporative condensers prior to startup:
• All water and drain connections must be checked and verified
• Evaporative condensers will ship with a fan support bracket to reduce damage caused by vibration during shipment. The shipping support brackets must be removed prior to unit startup. See “To remove shipping brackets,” p. 140 and Figure 60, p. 141 for removal instructions.
• Verify that inlet water pressure is 35-60 PSIG, dynamic pressure (measured with the valve open)
• Verify that drain valve is set to “drain during power loss” or “hold during power loss” per job specification
• Upon a call for cooling, the sump will fill with water. Verify that the sump fills to a level within the slot on the max float bracket as shown in
RT-SVX36G-EN 139
Unit Start Up
To remove shipping brackets
Important:
Remove fan shipping brackets before startup. Failure to remove brackets could result in fan damage.
Evaporative condensers are shipped with fan shipping brackets to reduce damage caused by vibration during shipment. The fan shipping brackets must be removed prior to unit startup.
To remove the shipping brackets start from the side opposite to the drain actuator:
1.
Loosen the screw for the bracket that holds the inlet louvers below the door side.
2. Remove inlet louvers and set to the side.
Note: Service technician may need to step on the horizontal surface of FRP coated base.
Step with care.
3. Unscrew the bolt in the middle of the door. Keep the bolt in a safe place.
4. Lift one door with handle until it touches the top. Swivel bottom of door to remove it from the door opening and set it to the side.
5. Slide and remove the middle mist eliminator section so that the shipping bracket is visible.
6. Use screw gun to unscrew the two screws that hold the fan shipping bracket. The bracket should drop down but still remain engaged with a hook on the bracket.
7.
Go to the other side of the unit and follow the procedure for inlet louver and door removal
(see steps 1 - 6).
8. Hold the bracket with one hand and remove remaining two screws.
9. Remove the bracket and all the removed screws from the unit.
Important:
Make sure there are no screws remaining in the coil area.
10. Reinstall inlet louvers, mist eliminators and louvers.
11. Check that the direction of arrow on the inlet louver is correct.
140 RT-SVX36G-EN
Figure 60. Fan shipping bracket removal
Mist Eliminator
Fan Shipping Bracket Screws
Fan Shipping Bracket
Unit Start Up
Figure 61. Float bracket setting
Actuator Side
Access Doors
Inlet Louvers
RT-SVX36G-EN
Fill sump so float shuts off when water is within these slots
141
Unit Start Up
Pressure Curves
To Check Operating Pressures
1.
Start the unit and allow the pressures to stabilize.
Note: If unit includes the Modulating Dehumidification Control option, pressure curves apply to the cooling mode only.
2. Measure the outdoor air dry bulb temperature (F) entering the condenser coil.
3. Measure the discharge and suction pressure (psig) next to the compressor.
4. Plot the outdoor dry bulb temperature and the operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the discharge pressure. The measured discharge pressure should be within ± 7 psig of the graph.
Note: To check operating pressure, see instructions
Figure 62. 20 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
105 °F Ambient
500
95 °F Ambient
450
400
350
85 °F Ambient
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
142 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
500
450
400
350
300
250
90
Figure 63. 20 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
105 °F Ambient
500
95 °F Ambient
450
85 °F Ambient
400
350
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 64. 25 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
105 °F Ambient
95 °F Ambient
85 °F Ambient
75 °F Ambient
65 °F Ambient
100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
143
Unit Start Up
Figure 65. 25 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
500
450
400
350
300
105 °F Ambient
95 °F Ambient
85 °F Ambient
75 °F Ambient
65 °F Ambient
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 66. 30 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
105 °F Ambient
500
450
95 °F Ambient
400
350
85 °F Ambient
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
144 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Figure 67. 30 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
550
105 °F Ambient
500
95 °F Ambient
450
85 °F Ambient
400
75 °F Ambient
350
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 68. 40 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
400
105 °F Ambient
350
300
250
95 °F Ambient
85 °F Ambient
75 °F Ambient
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
145
Unit Start Up
Figure 69. 40 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
105 °F Ambient
400
95 °F Ambient
350
85 °F Ambient
300
250
75 °F Ambient
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 70. 50/55 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
400
105 °F Ambient
350
300
250
95 °F Ambient
85 °F Ambient
75 °F Ambient
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
146 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Figure 71. 50/55 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
400
105 °F Ambient
95 °F Ambient
350
85 °F Ambient
300
250
75 °F Ambient
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 72. 60 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
400
105 °F Ambient
350
300
250
95 °F Ambient
85 °F Ambient
75 °F Ambient
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
147
Unit Start Up
Figure 73. 60 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
105 °F Ambient
400
95 °F Ambient
350
85 °F Ambient
300
75 °F Ambient
250
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 74. 70 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
105 °F Ambient
400
95 °F Ambient
350
85 °F Ambient
300
75 °F Ambient
250
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
148 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Figure 75. 75 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
105 °F Ambient
400
95 °F Ambient
350
85 °F Ambient
300
75 °F Ambient
250
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 76. 75 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
450
105 °F Ambient
400
95 °F Ambient
350
85 °F Ambient
300
75 °F Ambient
250
65 °F Ambient
200
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
149
Unit Start Up
Figure 77. 90 ton standard operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
90 Ton Standard Capacity
550
105 °F Ambient
500
95 °F Ambient
450
400
85 °F Ambient
75 °F Ambient
350
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 78. 90 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
90 Ton High Capacity
550
105 °F Ambient
500
95 °F Ambient
450
85 °F Ambient
400
350
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
150 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
Figure 79. 90 ton high operating, high efficiency pressure curve
(all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
90 Ton High Capacity High Efficiency
550
105 °F Ambient
500
95 °F Ambient
450
85 °F Ambient
400
350
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
Note: To check operating pressure, see instructions
Figure 80. 105 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
105 Ton High Capacity
550
105 °F Ambient
500
95 °F Ambient
450
85 °F Ambient
400
350
75 °F Ambient
65 °F Ambient
300
250
90 100 110 120 130 140
Suction Pressure, PSIG
150 160 170 180
151
Unit Start Up
Figure 81. 115 ton high operating pressure curve (all compressors and condenser fans “On”)
COOLING CYCLE PRESSURE CURVE
105 Ton High Capacity
550
550
500
500
105 °F Ambient
105 °F Ambient
350
350
300
300
250
90
250
90
100
100
110
110
120
120
130 140 150
Suction Pressure, PSIG
130 140 150
Suction Pressure, PSIG
75 °F Ambient
75 °F Ambient
65 °F Ambient
65 °F Ambient
160
160
170
170
180
180
Note: To check operating pressure, see instructions
Figure 82. 130 ton high operating pressure curve (all compressors and condenser fans “On”)
105 Ton High Capacity
550
500
500
450
400
350
300
250
90
105 °F Ambient
105 °F Ambient
105 °F Ambient
95 °F Ambient
85 °F Ambient
75 °F Ambient
75 °F Ambient
65 °F Ambient
100 110 120 130 140
Suction Pressure, PSIG
130
150 160 170 180
Thermostatic Expansion Valves
The reliability and performance of the refrigeration system is heavily dependent upon proper expansion valve adjustment. Therefore, the importance of maintaining the proper superheat cannot be over emphasized. Expansion valves are preset at the factory. In typical applications, field adjustment should not be required unless the valves are replaced or damaged.
152 RT-SVX36G-EN
Unit Start Up
On air-cooled units, the expansion valves shipped installed were factory set to control between 14-
18°F at the ARI full load rating conditions (approximately 45°/125°F saturated suction/discharge).
On evaporative condenser units, the expansion valves shipped installed were factory set to control between 18-22°F at the ARI full load rating conditions (approximately 45°/105°F saturated suction/ discharge). At part load, expect lower superheat. Systems operating with lower superheat could cause serious compressor damage due to refrigerant floodback.
Tables are based on outdoor ambient between 65° & 105°F, relative humidity above 40 percent.
Measuring the operating pressures can be meaningless outside of these ranges.
Measuring Superheat
1.
Measure the suction pressure at the suction line gauge access port located near the compressor.
2. Using a Refrigerant/Temperature chart, convert the pressure reading to a corresponding saturated vapor temperature.
3. Measure the suction line temperature as close to the expansion valve bulb, as possible. Use a thermocouple type probe for an accurate reading.
4. Subtract the saturated vapor temperature obtained in step 2 from the actual suction line temperature obtained in step 3. The difference between the two temperatures is known as
“superheat”.
When adjusting superheat, recheck the system subcooling before shutting the system “Off”.
Note: If unit includes the modulating reheat dehumidification control option, adjust superheat only in the cooling mode of operation.
Charging by Subcooling
The outdoor ambient temperature must be between 65° and 105° F and the relative humidity of the air entering the evaporator must be above 40 percent. When the temperatures are outside of these ranges, measuring the operating pressures can be meaningless.
Do not attempt to charge the system with the low ambient dampers and/or hot gas bypass operating (if applicable). Disable the low ambient dampers in the “Open” position (refer to the
“Low Ambient Damper” section) and de-energize the hot gas bypass valves before taking performance measurements.
With the unit operating at “Full Circuit Capacity”, acceptable subcooling range for air-cooled condenser units is between 14°F to 22°F. For evaporative condenser units, acceptable subcooling ranges is between 8°F to 14°F.
Note: If unit includes the modulating reheat dehumidification control option, adjust subcooling only in the cooling mode of operation.
Measuring Subcooling
1.
At the liquid line service valve, measure the liquid line pressure. Using an R-410A pressure/ temperature chart, convert the pressure reading into the corresponding saturated temperature.
2. Measure the actual liquid line temperature as close to the liquid line service valve as possible.
To ensure an accurate reading, clean the line thoroughly where the temperature sensor will be attached. After securing the sensor to the line, insulate the sensor and line to isolate it from the ambient air. Use a thermocouple type probe for an accurate reading.
3. Determine the system subcooling by subtracting the actual liquid line temperature (measured in step 2) from the saturated liquid temperature (converted in step 1).
RT-SVX36G-EN 153
Unit Start Up
Low Ambient Dampers
Operation
Low Ambient Dampers are available as a factory installed option on 20 - 75 Ton units or can be fieldinstalled. Dampers are used to extend the operation of these units from the standard operational temperatures to a minimum of 0° F without hot gas bypass or 10° F with hot gas bypass. (These values apply when wind speed across the condenser coil is less than 5 m.p.h. If typical wind speeds are higher than 5 m.p.h., a wind screen around the unit may be required.) By restricting the airflow across the condenser coils, saturated condensing temperatures can be maintained as the ambient temperatures change.
The low ambient modulating output(s) on the compressor module controls the low ambient damper actuator for each refrigerant circuit in response to saturated condensing temperature.
When the head pressure control has staged up to fan stage 2 or 3, the modulating output (0 to 10
VDC) will be at 100% (10 VDC). When the head pressure control is at fan stage 1, the modulating output will control the saturated condensing temperature to within the programmable
“condensing temperature low ambient control point”.
The following Table gives the minimum starting temperatures for both “Standard” & “Low”
Ambient units. Do not start the unit in the cooling mode if the ambient temperature is below the recommended operating temperatures.
Table 51. Minimum starting temperatures for air-cooled units
(a)
Unit Size
20 & 40
Minimum Starting Ambient
(b)
Low Ambient
Standard
(c)
55°
with HGBP
10°
without HGBP
0°
25 & 30
50, 55
60
70-130
50°
35°
30°
45°
10°
10°
10°
10°
0°
0°
0°
0°
(a) Minimum starting temperatures for Evaporative Condenser units is 40 a sump heater and 10
(b) Min. starting ambients in
(c) With or Without HGBP
°
F with a sump heater.
°
° F without
F and is based on unit operating at min. step of unloading & 5 mph wind across condenser.
Damper Installation
When a unit is ordered with the low ambient option (i.e., Digit 19 is a “1” in the model number), a damper is factory installed over the condenser fans 2B1 & 2B4 (depending on unit size). Refer to
for the damper locations.
For field installation, mount the dampers over the condenser fans at the locations shown in
with each kit.)
Damper Adjustment (Factory or Field Installed)
The UCM has a factory default setpoint of 90°F. This setpoint can be adjusted using the Human
Interface programming procedures.
Inspect the damper blades for proper alignment and operation. Dampers should be in the closed position during the “Off” cycle. If adjustment is required;
1.
Never depress the actuator clutch while the actuator is energized.
2. At the Human Interface, program the actuator for 0% on circuit #1 and/or circuit #2. (The output signal will go to 0.0 VDC.)
3. Loosen the actuator clamp.
154 RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
4. Firmly hold the damper blades in the closed position.
5. Retighten the actuator clamp.
To check damper operation, program the actuator for 100% on circuit #1 and/or circuit #2. (The output signal will go to 10 VDC and the damper will drive to the full open position.
Electric, Steam and Hot Water Start-Up
(Constant Volume & Variable Air Volume Systems)
1.
Ensure that the “System” selection switch at the remote panel is in the “Off” position.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
2. Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT
SWITCH 1S14.
3. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 to the “On” position.
4. Open the Human Interface access door, located in the unit control panel, and press the SERVICE
MODE key to display the first service screen. Refer to the latest edition of the appropriate programming manual for CV or VAV applications for the SERVICE TEST screens and programming instructions.
5. Use Table 35, p. 108 to program the following system components for operation by scrolling through the Human Interface displays;
• Electric Heat
– Supply Fan (On)
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– Heat Stages 1 & 2 (On)
• Steam or Hot Water Heat
– Supply Fan (On)
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– Hydronic Heat Actuator (100% Open)
– Open the main steam or hot water valve supplying the rooftop heater coils.
6. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
155
Unit Start Up
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to work with live and exposed rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
7.
Press the TEST START key to start the test. Remember that the delay designated in step 6 must elapse before the fan will begin to operate.
8. Once the system has started, verify that the electric heat or the hydronic heat system is operating properly by using appropriate service technics; i.e. amperage readings, delta tees, etc.
9. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
Gas Furnace Start-Up (Constant Volume & Variable Air Volume Systems)
It is important to establish and maintain the appropriate air/fuel mixture to assure that the gas furnace operates safely and efficiently.
Since the proper manifold gas pressure for a particular installation will vary due to the specific BTU content of the local gas supply, adjust the burner based on carbon dioxide and oxygen levels.
The volume of air supplied by the combustion blower determines the amount of oxygen available for combustion, while the manifold gas pressure establishes fuel input. By measuring the percentage of carbon dioxide produced as a by-product of combustion, the operator can estimate the amount of oxygen used and modify the air volume or the gas pressure to obtain the proper air/ fuel ratio. Arriving at the correct air/fuel mixture for a furnace results in rated burner output, limited production of carbon monoxide, and a steady flame that minimizes nuisance shutdowns.
Two Stage Gas Furnace
156
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury.
When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure regulator on the cylinder to prevent excessively high unit pressures. Never pressurize unit above the maximum recommended unit test pressure as specified in applicable unit literature. Failure to properly regulate pressure could result in a violent explosion, which could result in death or serious injury or equipment or property-only-damage.
High-Fire Adjustment
1.
Use Table 35, p. 108 to program the following system components for operation by scrolling through the Human Interface displays;
• Gas Heat
– Supply Fan (On)
RT-SVX36G-EN
RT-SVX36G-EN
Unit Start Up
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– Heat Stages 1 & 2 (On)
– Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position.
– Open the manual gas valve, located in the gas heat section.
2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
3. Press the TEST START key to start the test. Remember that the delay designated in step 2 must elapse before the system will begin to operate.
4. Once the system has started, check the appearance of the flame through the sight glass provided on the front of the heat exchanger. In appearance, a normal flame has a clearly defined shape, and is primarily (75%) blue in color with an orange tip.
5. Check the manifold gas pressure by using the manifold pressure port on the gas valve. Refer
to Table 52 for the required manifold pressure for high-fire operation. If it needs adjusting,
remove the cap covering the high-fire adjustment screw on the gas valve. Refer to
the adjustment screw location. Turn the screw clockwise to increase the gas pressure or counterclockwise to decrease the gas pressure.
6. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas.
Refer to the illustration in
. Take several samples to assure that an accurate reading is obtained. Refer to
for the proper carbon dioxide levels. A carbon dioxide level exceeding the listed range indicates incomplete combustion due to inadequate air or excessive gas.
Combustion Air Adjustment (O
2
)
7.
Use an oxygen analyzer and measure the percentage of oxygen in the flue gas. Take several samples to assure an accurate reading. Compare the measured oxygen level to the combustion curve in
. The oxygen content of the flue gas should be 4% to 5%. If the oxygen level is outside this range, adjust the combustion air damper to increase or decrease the amount of air entering the combustion chamber. Refer to
Figure 87, p. 162 for the location of the
combustion air damper.
8. Recheck the oxygen and carbon dioxide levels after each adjustment. After completing the highfire checkout and adjustment procedure, the low-fire setting may require adjusting.
Low-Fire Adjustment (500 MBH, 850 & 1,000 MBH only)
1.
Use the TEST initiation procedures outlined in the previous section to operate the furnace in the low-fire state (1st Stage).
2. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas.
Refer to the illustration in
Figure 83, p. 158 . Take several samples to assure that an accurate
reading is obtained. Refer to Figure 84, p. 159 for the proper carbon dioxide levels. If the
measured carbon dioxide level is within the listed values, no adjustment is necessary. A carbon dioxide level exceeding the listed range indicates incomplete combustion due to inadequate air or excessive gas.
3. Check the manifold gas pressure by using the manifold pressure port on the gas valve. Refer
to Figure 84 for the required manifold pressure during low-fire operation. If it needs adjusting,
remove the cap covering the low-fire adjustment screw on the gas valve. Refer to
for the adjustment screw location. Turn the screw clockwise to increase the gas pressure or counterclockwise to decrease the gas pressure.
Note: Do not adjust the combustion air damper while the furnace is operating at low-fire.
157
Unit Start Up
4. Check the carbon dioxide levels after each adjustment.
5. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
Table 52. Recommended manifold pressures and CO
2
levels during furnace operation (see notes)
Manifold
Furnace Stage
High-Fire
Low-Fire
High-Fire
Low-Fire
High-Fire
Low-Fire
High-Fire
Low-Fire
High-Fire
Low-Fire
MBH
235
117
350
175
500
250
850
500
1000
500
Firing Rate
100%
50%
100%
50%
100%
50%
100%
50%
100%
50%
Note:
1. Manifold pressures are given in inches w.c.
2. High fire manifold pressure is adjustable on all heaters.
3. Low fire manifold pressure is non-adjustable on 235 MBH and 350 MBH heaters.
%CO
2
8.5 - 9.5
6.0 - 7.0
8.5- 9.5
6.0 - 7.0
8.5 - 9.5
6.0 - 7.0
8.5 - 9.5
6.0 - 7.0
8.5 - 9.5
6.0 - 7.0
Pressure
3.0 - 3.5
0.9
3.0 - 3.5
0.9
3.0 - 3.5
1.25
3.0 - 3.5
1.25
3.0 - 3.5
1.25
Figure 83. Flue gas carbon dioxide and oxygen measurements
158 RT-SVX36G-EN
Unit Start Up
Figure 84. Natural gas combustion curve (ratio of oxygen to carbon dioxide in percent)
18
17
16
15
14
13
12
11
10
9
8
7
3
2
1
0
6
5
4
A
Curve Fuel
A = 1,000 BTU per cu. ft.
of Natural Gas.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Percent Oxygen
Figure 85. Gas valve adjustment screw locations
Full Modulating Gas Furnace
Full Modulating gas heaters are available for the 500, 850 and 1000 MBH heater sizes. These heaters are available in the same cabinet sizes as the current heaters.
The firing rate of the unit can vary from the pilot rate of 125 MBH up to the nameplate rating of the unit. The turn down ratios, therefore, vary from 4:1 for the 500 MBH to 8:1 for the 1000 MBH heater.
Heat Exchanger
The heat exchanger drum, tubes and front and rear headers are constructed from stainless steel alloys.
Unit control
The unit is controlled by a supply air temperature sensor located in the supply air stream for
Discharge Temperature Control units. Zone Temperature Control units have two sensors, one located in the supply air stream and the zone sensor. The temperature sensor signal is sent to the
Heat module of the IntelliPak Unit Control. The control signal from the Heat Module is an inverse proportional 5 -10 VDC. The higher the voltage signal, the lower the call for heat.
The 5 -10 VDC. signal controls the angular position of the combustion air damper through a direct coupled damper actuator motor. The position of the air damper in turn controls the combustion air
RT-SVX36G-EN 159
Unit Start Up
160 pressure that is sensed by the modulating gas valve. The greater the combustion air pressure, the greater the call for gas and the higher the firing rate of the heater. As the temperature setpoint is reached, the Modulating Heat control will cause the combustion air actuator to change the damper position to a lower firing rate that matches the heat load of the space.
1.
Use Table 35, p. 108 to program the following system components for operation by scrolling through the Human Interface displays;
• Gas Heat
– Supply Fan (On)
– Variable Frequency Drive (100% Output, if applicable)
– RTM Occ/Unocc Output (Unoccupied)
– High Fire (90%)
– Turn the 115 volt control circuit switch 4S24 located in the heater control panel to the “On” position.
– Open the manual gas valve, located in the gas heat section.
2. Once the configuration for the appropriate heating system is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
3. Press the TEST START key to start the test. Remember that the delay designated in step 2 must elapse before the system will begin to operate.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating components. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks.
Failure to follow all safety precautions could result in rotating components cutting and slashing technician which could result in death or serious injury.
4. Once the system has started, check the appearance of the flame through the sight glass provided on the front of the heat exchanger. In appearance, a normal flame has a clearly defined shape, and is primarily (75%) blue in color with an orange tip.
5. Check the inlet gas pressure at the modulating gas valve. The inlet pressure should be 6" to 8" w.c.
6. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas.
Refer to the illustration in Figure 83, p. 158 . Take several samples to assure that an accurate
reading is obtained. If the measured carbon dioxide level is between 8.0% and 9.5%, no adjustment is necessary. If the CO
2
is outside this range, it indicates incomplete combustion due to inadequate air or excessive gas.
The pressure ratio and bias adjustment screws are located on top of the regulator under a sealed plate. The actual settings can be seen through windows on each side of the regulator. Refer to the illustration in
Note: The burner capacity is controlled by the movement of the air damper. This has been preset at the factory and normally does not need field adjustment. The combustion quality (air/gas) is controlled by the settings on the regulator (the plus (+) and minus (-) indications relate to the change in gas flow.
7.
Set the air/gas ratio to the desired value using the #1 adjustment screw until the optimum values between (8.0 and 9.5%) are obtained (course setting).
RT-SVX36G-EN
Unit Start Up
8. Use Table 35, p. 108 to program the minimum (5%) firing rate. Allow the system to operate for approximately 10 minutes.
9. Use a carbon dioxide analyzer and measure the percentage of carbon dioxide in the flue gas.
If the measured carbon dioxide level is between 6.0% and 8.0%, no adjustment is necessary. If an adjustment is needed, turn the #2 adjustment screw on the regulator in the Plus (+) direction to increase the CO
2
and in the Minus (-) direction to decrease the CO
2
. Refer to the illustration in
for the adjustment screw location.
Note: It is normal for the low fire CO
2
to be lower than the high fire.
10. If the measured carbon dioxide level is below the recommended values for low heat, return the burner to 90% fire rate and repeat steps 6 and 7, to achieve optimum combustion.
11. Program the burner for 100% operation and recheck the CO
2
or O
2
value.
12. Check the flue gas values at several intermediate output levels. If corrections are necessary;
– Adjust the pressure ratio screw 1 at high fire operation only.
– Adjust the bias screw 2 at low fire operation only.
13. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
Limited Modulating Gas Furnace
Limited Modulating gas heaters are available for the 500, 850 and 1000 MBH heater sizes. These heaters are available in the same cabinet sizes as the current heaters.
The firing rate of the unit can vary from 33% rated MBH up to the nameplate rating of the unit. The turn down ratios, therefore, is limited to 3:1.
Heat Exchanger
The heat exchanger drum, tubes and front and rear headers utilities the same materials as the standard two stage furnace.
Unit control
The unit is controlled by a supply air temperature sensor located in the supply air stream for
Discharge Temperature Control units. Zone Temperature Control units have two sensors, one located in the supply air stream and the zone sensor. The temperature sensor signal is sent to the
Heat module of the IntelliPak Unit Control. The control signal from the Heat Module is an inverse proportional 5 -10V DC. The higher the voltage signal, the lower the call for heat.
The 5 -10V DC. signal controls the angular position of the combustion air damper through a direct coupled damper actuator motor. The position of the air damper in turn controls the combustion air pressure that is sensed by the modulating gas valve. The greater the combustion air pressure, the greater the call for gas and the higher the firing rate of the heater. As the temperature setpoint is reached, the Modulating Heat control will cause the combustion air actuator to change the damper position to a lower firing rate that matches the heat load of the space.
1.
To verify and check system optimum combustion, use Table 35, p. 108 to program the limited modulating heat system components for 90% operation by scrolling through the Human
Interface displays.
2. Follow the checkout procedures discussed in the previous steps.
Note: The minimum firing rate for a limited modulating gas furnace in step 8 is 33%. Travel of the combustion air damper is limited by a welded stop.
RT-SVX36G-EN 161
Unit Start Up
3. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
Figure 86. Modulating gas regulator
1.
Adjustment and indication of the air to gas ratio.
11
2. Adjustment and indication of the bias.
3. Connection for the Ambient compensation line.
4. Connection for the gas pressure sensing line.
5. Connection for the air pressure sensing line.
Note: There are no serviceable parts on the
SKP70 actuator. Should it become inoperative, replace the actuator.
Figure 87. Typical gas furnace
162 RT-SVX36G-EN
Unit Start Up
Final Unit Checkout
After completing all of the checkout and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling and heating), perform these final checks before leaving the unit:
1.
Close the disconnect switch or circuit protector switch that provides the supply power to the unit's terminal block 1TB1 or the unit mounted disconnect switch 1S14.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.
2. Turn the 115 volt control circuit switch 1S1 “Off”.
3. Turn the 24 volt control circuit switch 1S70 to the “On” position.
4. At the Human Interface Module, press the “SETUP” key. The LCD screen will display various preset “parameters of operation” based on the unit type, size, and the installed options.
Compare the factory preset information to the specified application requirements. If adjustments are required, follow the step-by-step instructions provided in the appropriate programming manual for CV or VAV applications.
5. Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.
6. Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone
Temperature” settings for constant volume systems are correct.
7.
Verify that the Remote panel “System” selection switch and the “Supply Air Temperature” settings for Discharge Temperature Control systems are correct.
8. Inspect the unit for misplaced tools, hardware, and debris.
9. Turn the 115 volt control circuit switch 1S1 “On”.
10. Press the “AUTO” key at the Human Interface Module to begin system operation. The system will start automatically once the dampers modulate and a request for either heating or cooling has been given.
11. Verify that all exterior panels including the control panel doors and condenser grilles are secured in place.
RT-SVX36G-EN 163
Startup Checklists
20-75 Ton — Air-Cooled
Job Name
Job Location
Sales Order #
Unit DL # (special units)
Starting Sales Office
This checklist is intended to be a guide for the start up technician. Many of the recommended checks and actions could expose the technician to electrical and mechanical hazards. Refer to the appropriate sections in the unit IOM for appropriate procedures, component specifications and safety instructions.
Important:
This checklist is not intended to be a substitution for the contractors installation instruction.
Serial #
Model #
Ship Date
Date
Technician
Table 53. Startup checklist — 20-75 ton air-cooled
Verify Task
Completed
Access/Egress
Initial Site Inspection
Unit exterior inspected for damage (dents, bends, missing panels, doors work properly)
Unit clearances adequate to avoid air recirculation etc.
Verify crankcase heaters are working and on for 8 hours prior to unit start (may require 480V availability)
Wear electrical PPE
Lockout tag out unit
Verify unit interior is free from debris/obstructions etc.
All unit drain lines and traps installed properly
Remove electrical access panel fastened by (9) bolt/screws or open access doors
Verify unit is grounded. Confirm a ground wire is coming from power source.
Verify main power feed wire gauge is properly size for current load
Verify all wiring connections are tight
Verify all field control wiring for CV or VAV controls complete
Verify all automation and remote controls installed/wired
Verify shipping hardware and plastic covers for compressors has been removed
Verify hold down bolts and channels from fan sections removed
Fan section spring isolators checked/adjusted (approx ¼” gap above shipping block)
Verify damper linkages are tight/adjusted and tip seals are in good condition
Verify compressor oil levels at proper level (½ -¾ high in glass)
Compressor discharge service valves, oil valves and liquid lines valves open/back seated
All fan belts tensioned, bearings greased and sheaves in alignment
Verify supply and exhaust fan pulley bolts are tight
Verify fans rotate freely
Verify refrigerant charge on each circuit
Remove lock out tag out
Wear electrical PPE
Verify correct voltage supplied to unit and electric heaters (see IOM for assistance)
Verify incoming voltage phase balanced
Continued on next page
164 RT-SVX36G-EN
Startup Checklists
Table 53. Startup checklist (continued)— 20-75 ton air-cooled
Verify all fans rotate in proper direction
Verify fan amperages within nameplate specs (Please document on log sheet)
Unit Configuration and Setup
Verify model number in the UCM configuration matches unit model number on name plate
Configure unit using IOM and critical control parameters listed in Table 54, p. 166
Air Cooled Condenser (Digit 27)
All coil fins inspected and straightened
Condenser fans are rotating freely
Verify the fan blade set-screws to the motor shaft of the condenser fan assemblies are tight
Electric Heat (If Applicable)
Electric heat circuits have continuity
Perform electric heat start-up procedure outlined in IOM
Gas Heat (If Applicable)
Gas heat piping includes drip leg previously installed by controlling contractor
Gas heat flue assembly fully installed
Gas heat condensate line + heat tape installed where applicable
Verify heating system matches name plate
Optional Gas Burner (Digit 9)
2 Stage Gas Burner Set-up procedure in IOM
Modulating Burner Set-up procedure in IOM
Hot Water Heat (If Applicable)
Verify hot water pipes are proper size, routed through the base and no leaks are present
Verify swing joints or flexible connectors are installed next to hot water coil
Verify gate valve is installed in the supply and return branch line
Verify three way modulating valve is installed with valve seating against the flow
Verify coil venting is installed if water velocity is less than 1.5 feet per second
Steam Water Heat (If Applicable)
Verify steam pipes are proper size, routed through the base and no leaks are present
Verify steam heat swing check vacuum breakers installed and vented
Verify 2-way modulating valve has been installed
Verify steam trap installed properly with discharge 12" below the outlet connection on the coil
System Checkout
Verify system airflow
Verify dampers open and close properly
Adjust fresh air damper travel
Verify compressor operation, voltage and amperage matches name plate information (Please document on log sheet)
Verify superheat and subcooling normal (Please document on log sheet)
Operating log completed
All panels/doors secured
Complete all required documentation
Verify Task
Completed
RT-SVX36G-EN 165
Startup Checklists
Table 54. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
Suggested
Parameter
8°F
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
Supply Air Temperature Control Setpoint
Supply Air Temperature Deadband
Supply Air Pressure Setpoint
Supply Air Pressure Deadband
Building Static Pressure Setpoint
Building Static Pressure Deadband
Standby Freeze Avoidance
55°F
1.8" w.c.
0.1" w.c.
0.03" w.c.
0.04" w.c.
20%
10%
10%
Exhaust Enable Setpoint
Economizer Minimum Position Setpoint
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
Fixed Reference
Enthalpy Changeover
H
T
OA
OA
> 75°F
> 28 Btu
T
OA
> 65°F T
OA
> 65°F T
T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 70°F T
> 75°F
OA
> 70°F T
OA
> 70°F
Differential Comparative
Enthalpy Changeover
H
OA
> H
RA
Note:
) below for dry bulb changeover.
Examples:
(a) Minneapolis, Minnesota is in “Region 6" and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be 75°F.
(b) Charleston, South Carolina is in “Region 3" and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting should be 65°F.
24-89 Ton — Evaporative Condenser
Important:
Water treatment is required before beginning startup. Failure to do so will damage the unit and result in premature unit degradation.
This checklist is intended to be a guide for the start up technician. Many of the recommended checks and actions could expose the technician to electrical and mechanical hazards. Refer to the appropriate sections in the unit IOM for appropriate procedures, component specifications and safety instructions.
Important:
This checklist is not intended to be a substitution for the contractors installation instruction.
Job Name
Job Location
Sales Order #
Unit DL # (special units)
Starting Sales Office
Serial #
Model #
Ship Date
Date
Technician
166 RT-SVX36G-EN
Startup Checklists
Table 55. Startup checklist — 24-89 ton evaporative cooling
Access/Egress
Initial Site Inspection
Unit exterior inspected for damage (dents, bends, missing panels, doors work properly)
Unit clearances adequate to avoid air recirculation etc.
Verify crankcase heaters are working and on for 8 hours prior to unit start (may require 480V availability)
Wear electrical PPE
Lockout tag out unit
Verify unit interior is free from debris/obstructions etc.
All unit drain lines and traps installed properly
Remove electrical access panel fastened by (9) bolt/screws or open access doors
Verify unit is grounded. Confirm a ground wire is coming from power source.
Verify main power feed wire gauge is properly size for current load
Verify all wiring connections are tight
Verify all field control wiring for CV or VAV controls complete
Verify all automation and remote controls installed/wired
Verify shipping hardware and plastic covers for compressors has been removed
Verify hold down bolts and channels from fan sections removed
Fan section spring isolators checked/adjusted (approx ¼” gap above shipping block)
Verify damper linkages are tight/adjusted and tip seals are in good condition
Verify compressor oil levels at proper level (½ -¾ high in glass)
Compressor discharge service valves, oil valves and liquid lines valves open/back seated
All fan belts tensioned, bearings greased and sheaves in alignment
Verify supply and exhaust fan pulley bolts are tight
Verify fans rotate freely
Verify refrigerant charge on each circuit
Remove lock out tag out
Wear electrical PPE
Verify correct voltage supplied to unit and electric heaters (see IOM for assistance)
Verify incoming voltage phase balanced
Verify all fans rotate in proper direction
Verify fan amperages within nameplate specs (Please document on log sheet)
Unit Configuration and Setup
Verify model number in the UCM configuration matches unit model number on name plate
Configure unit using IOM and critical control parameters listed in Table 55, p. 167
Evaporative Condenser (Digit 27)
Verify condenser fan shipping bracket has been removed from above mist eliminators in evaporative condenser module
Verify all water and drain connections are complete
Verify inlet water pressure is between 35-60 psig, dynamic pressure (measured with valve open) for min. flow rate of 30 GPM
Verify drain valve function is set to “drain during power loss” or “hold during power loss” per job specification
Verify water treatment system has been installed/approved - discontinue startup if proof of active water treatment does not exist
Verify conductivity controller calibration has been documented and min and max setpoints have been setup
Continued on next page
Verify Task
Completed
RT-SVX36G-EN 167
Startup Checklists
Table 55. Startup checklist (continued)— 24-89 ton evaporative cooling
Electric Heat (If Applicable)
Electric heat circuits have continuity
Perform electric heat start-up procedure outlined in IOM
Gas Heat (If Applicable)
Gas heat piping includes drip leg previously installed by controlling contractor
Gas heat flue assembly fully installed
Gas heat condensate line + heat tape installed where applicable
Verify heating system matches name plate
Optional Gas Burner (Digit 9)
2 Stage Gas Burner Set-up procedure in IOM
Modulating Burner Set-up procedure in IOM
Hot Water Heat (If Applicable)
Verify hot water pipes are proper size, routed through the base and no leaks are present
Verify swing joints or flexible connectors are installed next to hot water coil
Verify gate valve is installed in the supply and return branch line
Verify three way modulating valve is installed with valve seating against the flow
Verify coil venting is installed if water velocity is less than 1.5 feet per second
Steam Water Heat (If Applicable)
Verify steam pipes are proper size, routed through the base and no leaks are present
Verify steam heat swing check vacuum breakers installed and vented
Verify 2-way modulating valve has been installed
Verify steam trap installed properly with discharge 12" below the outlet connection on the coil
System Checkout
Verify system airflow
Verify dampers open and close properly
Adjust fresh air damper travel
Verify compressor operation, voltage and amperage matches name plate information (Please document on log sheet)
Verify superheat and subcooling normal (Please document on log sheet)
Operating log completed
All panels/doors secured
Complete all required documentation
Verify Task
Completed
168 RT-SVX36G-EN
Startup Checklists
Table 56. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
Suggested
Parameter
8°F
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
Supply Air Temperature Control Setpoint
Supply Air Temperature Deadband
Supply Air Pressure Setpoint
Supply Air Pressure Deadband
Building Static Pressure Setpoint
Building Static Pressure Deadband
Standby Freeze Avoidance
55 °F
1.8" w.c.
0.1" w.c.
0.03" w.c.
0.04" w.c.
20%
10%
10%
Exhaust Enable Setpoint
Economizer Minimum Position Setpoint
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
Fixed Reference
Enthalpy Changeover
H
T
OA
OA
> 75°F
> 28 Btu
T
OA
> 65°F T
OA
> 65°F T
T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 70°F T
> 75°F
OA
> 70°F T
OA
> 70°F
Differential Comparative
Enthalpy Changeover
H
OA
> H
RA
Note:
) below for dry bulb changeover.
Examples:
(a) Minneapolis, Minnesota is in “Region 6” and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be 75°F.
(b) Charleston, South Carolina is in “Region 3” and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting should be 65°F.
RT-SVX36G-EN 169
Startup Checklists
90-130 Ton — Air Cooled
Important:
Verify water treatment is functional before beginning startup.
This checklist is intended to be a guide for the start up technician. Many of the recommended checks and actions could expose the technician to electrical and mechanical hazards. Refer to the appropriate sections in the unit IOM for appropriate procedures, component specifications and safety instructions.
Important:
This checklist is not intended to be a substitution for the contractors installation instruction.
Job Name
Job Location
Sales Order #
Unit DL # (special units)
Starting Sales Office
Serial #
Model #
Ship Date
Date
Technician
Table 57. IntelliPak startup checklist — 90-130 ton air cooled
Verify Task
Completed
Access/Egress
Initial Site Inspection
Unit exterior inspected for damage (dents, bends, missing panels, doors work properly)
Unit clearances adequate to avoid air recirculation etc.
Verify crankcase heaters are working and on for 8 hours prior to unit start (may require 480V availability)
Wear electrical PPE
Lockout tag out unit
Verify unit interior is free from debris/obstructions etc.
All unit drain lines and traps installed properly
Remove electrical access panel fastened by (9) bolt/screws or open access doors
Verify unit is grounded. Confirm a ground wire is coming from power source.
Verify main power feed wire gauge is properly size for current load
Verify all wiring connections are tight
Verify all field control wiring for CV or VAV controls complete
Verify all automation and remote controls installed/wired
Verify shipping hardware and plastic covers for compressors has been removed
Verify hold down bolts and channels from fan sections removed
Fan section spring isolators checked/adjusted (approx ¼” gap above shipping block)
Verify damper linkages are tight/adjusted and tip seals are in good condition
Verify compressor oil levels at proper level (½ -¾ high in glass)
Compressor discharge service valves, oil valves and liquid lines valves open/back seated
All fan belts tensioned, bearings greased and sheaves in alignment
Verify supply and exhaust fan pulley bolts are tight
Verify fans rotate freely
Verify refrigerant charge on each circuit
Remove lock out tag out
Wear electrical PPE
Verify correct voltage supplied to unit and electric heaters (see IOM for assistance)
Verify incoming voltage phase balanced
170 RT-SVX36G-EN
Startup Checklists
Table 57. IntelliPak startup checklist (continued)— 90-130 ton air cooled
Verify all fans rotate in proper direction
Verify fan amperages within nameplate specs (Please document on log sheet)
Unit Configuration and Setup
Verify model number in the UCM configuration matches unit model number on name plate
Configure unit using IOM and critical control parameters listed in Table 55, p. 167
Air Cooled Condenser (Digit 27)
All coil fins inspected and straightened
Condenser fans are rotating freely
Verify the fan blade set-screws to the motor shaft of the condenser fan assemblies are tight
Electric Heat (If Applicable)
Electric heat circuits have continuity
Perform electric heat start-up procedure outlined in IOM
Gas Heat (If Applicable)
Gas heat piping includes drip leg previously installed by controlling contractor
Gas heat flue assembly fully installed
Gas heat condensate line + heat tape installed where applicable
Verify heating system matches name plate
Optional Gas Burner (Digit 9)
2 Stage Gas Burner Set-up procedure in IOM
Modulating Burner Set-up procedure in IOM
Hot Water Heat (If Applicable)
Verify hot water pipes are proper size, routed through the base and no leaks are present
Verify swing joints or flexible connectors are installed next to hot water coil
Verify gate valve is installed in the supply and return branch line
Verify three way modulating valve is installed with valve seating against the flow
Verify coil venting is installed if water velocity is less than 1.5 feet per second
Steam Water Heat (If Applicable)
Verify steam pipes are proper size, routed through the base and no leaks are present
Verify steam heat swing check vacuum breakers installed and vented
Verify 2-way modulating valve has been installed
Verify steam trap installed properly with discharge 12" below the outlet connection on the coil
System Checkout
Verify system airflow
Verify dampers open and close properly
Adjust fresh air damper travel
Verify compressor operation, voltage and amperage matches name plate information (Please document on log sheet)
Verify superheat and subcooling normal (Please document on log sheet)
Operating log completed
All panels/doors secured
Complete all required documentation
Verify Task
Completed
RT-SVX36G-EN 171
Startup Checklists
Table 58. Critical control parameters
Notes:
1. Using the Human Interface (HI), go to SETUP Menu and input setting for parameters listed below.
2. Use the map shown below to determine region of country based on unit site location.
Suggested
Parameter
8°F
Economizer Settings
Region 1 Region 2 Region 3 Region 4 Region 5 Region 6 Region 7
Supply Air Temperature Control Setpoint
Supply Air Temperature Deadband
Supply Air Pressure Setpoint
Supply Air Pressure Deadband
Building Static Pressure Setpoint
Building Static Pressure Deadband
Standby Freeze Avoidance
55 °F
1.8" w.c.
0.1" w.c.
0.03" w.c.
0.04" w.c.
20%
10%
10%
Exhaust Enable Setpoint
Economizer Minimum Position Setpoint
Fixed Dry Bulb Economizer C/O
Type a (Moist)*
Fixed Dry Bulb Economizer C/O
Type b (Dry)*
Fixed Dry Bulb Economizer C/O
Type c (Marine)*
Fixed Reference
Enthalpy Changeover
H
T
OA
OA
> 75°F
> 28 Btu
T
OA
> 65°F T
OA
> 65°F T
T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 65°F T
> 75°F T
OA
OA
> 70°F T
> 75°F
OA
> 70°F T
OA
> 70°F
Differential Comparative
Enthalpy Changeover
H
OA
> H
RA
Note:
) below for dry bulb changeover.
Examples:
(a) Minneapolis, Minnesota is in “Region 6” and resides in “Moist” subregion, thus designation is 6b. Economizer changeover setting should be 75°F.
(b) Charleston, South Carolina is in “Region 3” and resides in “Moist” subregion, thus the designation is 3c. Economizer changeover setting should be 65°F.
172 RT-SVX36G-EN
Figure 88. Dry bulb changeover map
Startup Checklists
RT-SVX36G-EN 173
Maintenance
Table 59. Control settings and time delays
Control Description Elec. Designation Contacts Open
Compressor Circuit Breakers
20 - 130
Combustion Airflow Switch
(Gas Heat Only)
High Limit Cutout
(Gas Heat Only)
Supply Airflow Switch
(Gas Heat Only)
Disch High Limit
(Electric Heat Only)
1CB8 thru 1CB11
4S25
4S26
4S38
4S27
See
see note 1
250 + 15 F
0.03 - 0.12" wc
133 + 5 F
Linear High Limit
(Electric Heat Only)
4S33
185 + 10 F (std./UL)
165 F + 10 F (CSA)
Freezestat
(Hydronic Heat Only)
Gas Heat Units
4S12 (N.O.) Auto Reset
Prepurge Timer: Fenwall
Honeywell
Sequencing Time Delay Relay
4DL5
4U18
4DL6
N.C. - timed to close internal timing function
N.C. - timed to close
Note:
The combustion airflow switch (4S25) differential is 0.02" - 0.08" wc.
Contacts Closed
See
0.1 - 0.25" wc rise in press diff
210 F
0.15 + 0.05" wc rise in press diff
110 + 5 F
145 F (std./UL)
125 F (CSA)
40 F
60 seconds
60 seconds
60 seconds + 20%
Table 60. Compressor circuit breakers (1CB8 - 1CB11) electrical characteristics
200 V
Unit Size
20
Hi Cap.
25
Hi Cap.
30
Hi Cap
40
Hi Cap
50
Hi Cap
55
60
Hi Cap
70
75
Hi Cap
Comp Designation
1A,1B
1A,1B
1A
1B
1A
1B
1A,1B
1A
1B
1A,2A
1B,2B
1A,1B,2A,2B
1A,2A, 1B,2B
1A,2A,
1B,2B
1A,1B,2A,2B
1A,2A
1B,2B
1A,1B,2A,2B
1A,1B,2A,2B
1A,2A
1B,2B
1A,2A
1B,2B
Must Hold
50.4
57.2
57.2
57.1
63.1
63.1
69.3
73.7
105.2
73.7
105.2
63.1
63.1
57.1
38.1
45.5
45.5
50.4
50.4
50.4
50.4
57.1
50.4
63.1
Must Trip
58
65.7
65.7
65.7
72.5
72.5
79.7
84.7
121
84.7
121
72.5
72.5
65.7
43.8
52.3
52.3
58
58
58
58
65.7
58
72.5
Must Hold
43.3
51.4
51.4
51.4
57.1
57.1
59.4
63.1
90.7
63.1
90.7
57.1
69.3
59.4
37
38.7
38.7
43.3
43.2
43.2
43.2
51.4
43.2
57.1
230 V
Must Trip
49.7
59.2
59.2
59.2
65.7
65.7
68.3
72.5
104.3
72.5
104.3
65.7
79.7
68.3
42.5
44.5
44.5
49.7
49.7
49.7
49.7
59.2
49.7
65.7
174 RT-SVX36G-EN
Figure 89. Unit internal fuse replacement data for air handling units
Maintenance
RT-SVX36G-EN 175
Maintenance
Table 61. Filter data
Unit Model
(AC/EC)
20 & 25 / 24 & 29 Ton
Panel-Type Filters
Qty Size of each Qty.
4
12 20 X 20 X 2
3
2
16 20 X 20 X 2
6
5
16 20 X 25 X 2
6
3
20 20 X 25 X 2
9
6
35
25
16 X 20 X 2
24 X 24 X 2
(a)
Bag-Type Filters
8
3
15
(b)
Size of each
12 X 24 X 19
24 X 24 X 19
12 X 24 X 19
Cartridge Filters (box-
Qty.
4
3
2
type)
Size of each
12 X 24 X 12
24 X 24 X 12
12 X 24 X 12
Qty.
4
3
2
Panel-Type
Prefilters
(c)
Size of each
12 X 24 X 2
24 X 24 X 2
12 X 24 X 2
30/36 Ton
24 X 24 X 19
12 X 24 X 19
6
5
24 X 24 X 12
12 X 24 X 12
6
5
24 X 24 X 2
12 X 24 X 2
40/48 Ton
24 X 24 X 19
12 X 24 X 19
6
3
24 X 24 X 12
12 X 24 X 12
6
3
24 X 24 X 2
12 X 24 X 2
50, 55 / 59 Ton
24 X 24 X 19
12 X 24 X 19
9
6
24 X 24 X 12
12 X 24 X 12
9
6
24 X 24 X 2
12 X 24 X 2
60, 70 & 75 /
73, 80 & 89 Ton
24 X 24 X 19
12 X 24 X 19
8
3
24 X 24 X 12
12 X 24 X 12
8
3
24 X 24 X 2
20 X 24 X 2
90-130
24 X 24 X 19 15 24 X 24 X 12 15 24 X 24 X 2
(a) Dimensions shown for “Panel-Type Filters” apply to “Throw away”, “Cleanable Wire Mesh”, and “High Efficiency Throw away” Filters.
(b) S_HL units ordered with “Bag-Type Filters” or “Cartridge Filters” (box-type) include a bank of “Panel-Type Prefilters”
(c) The same “Panel-Type Prefilters” are used with “Bag-Type” and “Cartridge (box-type)” filters.
Table 62. “Wet heat” coil fin data
Unit Model
(AC/EC) Coil Type Coil Rows
Total Coil Face
Area (sq. ft.)
Fins per
Foot
Fins per
Foot
20, 25, 30 / 24, 29, 36 Ton
40, 50, 55 / 48, 59 Ton
60, 70, 75 / 73, 80, 89 Ton
40, 50 / 48, 59 Ton
WC Prima Flo (hot water)
WC Prima Flo (hot water)
WC Prima Flo (hot water)
NS (steam)
2
2
2
1
13.75
19.25
26.25
13.75 (1) 5.5 (1)
80
80
80
42
110
110
110
96
90-130 Ton NS (steam) 1 17.5 (2) 52 96
Note:
To determine unit heating capacity (i.e. “low heat” or “high heat”), see digit 9 of the model number stamped on the unit nameplate.
Table 63. Grease recommendations
Recommended Grease
Exxon Unirex #2
Mobil 532
Mobil SHC #220
Texaco Premium
Recommended Operating Range
-20°F to 205°F
Table 64. Refrigerant coil fin data
Tonnage
20
25
30
40
50, 55
Size
(ft2)
20.3
20.3
25.5
32.5
38
Evaporator Coil
Rows/Fin
Series
4/168
Tube Diameter/
Surface
1/2/Enhanced
4/168
5/168
5/168
4/168
1/2/Enhanced
3/8”/Enhanced
3/8”/Enhanced
1/2/Enhanced
Size
(ft2)
58
58
58
116
116
Aluminum Fins
Rows/Fin
Series
3/252
Condenser Coil
Tube Diameter/
Surface
5/16/Enhanced
Copper Fins
Rows/Fin
Series
3/156
Tube Diameter/
Surface
5/16/Enhanced
3/252
4/252
3/252
4/252
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
3/156
4/156
3/156
4/156
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
176 RT-SVX36G-EN
Maintenance
Table 64. Refrigerant coil fin data (continued)
Tonnage
60
70
75
90 Std
90 Hi Cap
90 Hi EER
105 Hi Cap
115 Std Cap
130 Std Cap
Size
(ft2)
43
43
43
59.3
59.3
59.3
59.3
59.3
59.3
Evaporator Coil
Rows/Fin
Series
Tube Diameter/
Surface
6/168
6/168
6/168
4/148
6/148
6/148
5/148
6/148
6/148
3/8”/Enhanced
3/8”/Enhanced
3/8”/Enhanced
1/2 / Enhanced
1/2 / Enhanced
1/2 / Enhanced
1/2 / Enhanced
1/2 / Enhanced
1/2 / Enhanced
Size
(ft2)
152
152
152
152
152
136
136
136
152
Aluminum Fins
Rows/Fin
Series
Condenser Coil
Tube Diameter/
Surface
Copper Fins
Rows/Fin
Series
Tube Diameter/
Surface
3/252
3/252
3/252
3/144
3/144
4/144
4/144
4/144
4/144
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
3/8 Smooth
3/8 Smooth
3/8 Smooth
3/8 Smooth
3/8 Smooth
3/8 Smooth
3/156
4/156
4/156
NA
NA
NA
NA
NA
NA
5/16/Enhanced
5/16/Enhanced
5/16/Enhanced
NA
NA
NA
NA
NA
NA
Fan Belt Adjustment
The supply fan belts and optional exhaust fan belts must be inspected periodically to assure proper unit operation.
Replacement is necessary if the belts appear frayed or worn. Units with dual belts require a matched set of belts to ensure equal belt length.
When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent) illustrated below; adjust the belt tension as follows;
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1.
To determine the appropriate belt deflection; a. Measure the center-to-center shaft distance (in inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64; the resulting value represents the amount of belt deflection that corresponds to the proper belt tension.
2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the gauge plunger.
4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O-ring is even with the top of the next belt—
-or even with a straightedge placed across the fan and motor sheaves. Refer to
.
Figure 90. Browing (or gates) tension gauge
RT-SVX36G-EN 177
Maintenance
5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection.
6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in
. If the “force” reading is outside the range, readjust the belt tension.
Note: Actual belt deflection “force” must not exceed the maximum “force” value shown in
7.
Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension will decrease rapidly until the new belts are “run in”.
Table 65. Belt tension measurement and deflection ranges
Belts Cross
Section
A
B
Small P.D.
Range
3.0 - 3.6
3.8 - 4.8
5.0 - 7.0
3.4 - 4.2
4.4 - 5.6
5.8 - 8.8
Deflection Force (lbs.)
Super Gripbelts Gripnotch
Min.
Max.
Min Max.
3
3 1/2
4
4
5 1/8
6 3/8
4 1/2
5
5 1/2
5 1/2
7 1/8
8 3/4
3 7/8
4 1/2
5
5 3/4
6 1/2
7 3/8
5 1/2
6 1/4
6 7/8
8
9 1/8
10 1/8
Steel Cable Gripbelts
Min Max
3 1/4
3 3/4
4 1/4
4 1/2
5 3/4
7
4
4 3/4
5 1/4
5 1/2
7 1/4
8 3/4
Belts Cross
Section
5V
Small P.D.
Range
4.4 - 8.7
7.1 - 10.9
11.8 - 16.0
Deflection Force (lbs.)
358 Gripbelts
Min.
Max.
— —
10 1/2
13
15 3/4
19 1/2
358 Gripnotch
Min
10
12 7/8
15
Max.
15
18 3/4
22
Figure 91. Belt deflection
178 RT-SVX36G-EN
Maintenance
Scroll Compressor Replacement
The compressor manifold system was purposely designed to provide proper oil return to each compressors. The refrigerant manifold system must not be modified in any way.
Note: Altering the compressor manifold piping may cause oil return problems and compressor failure.
Should a compressor replacement become necessary and a suction line filter drier is to be installed, install it a minimum of 16 or 25 inches upstream of the oil separator tee. See
Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all Federal, State and local laws. Refer to general service bulletin MSCU-SB-1 (latest edition).
Refrigeration System
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Trane representative.
Failure to use R-410A rated service equipment or components could result in equipment exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
WARNING
Refrigerant under High Pressure!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to recover refrigerant to relieve pressure or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in an explosion which could result in death or serious injury or equipment damage.
Refrigerant Evacuation and Charging
The unit is fully charged with R-410A refrigerant from the factory. However if it becomes necessary to remove or recharge the system with refrigerant, it is important that the following actions are taken. Failure to do so may cause permanent damage to the compressor.
Charge Storage
Due to the reduced capacity of the microchannel condenser coil compared to the round tube plate fin evaporator coil, pumping refrigerant into the condenser coil to service the refrigerant system is no longer an option.
RT-SVX36G-EN 179
Maintenance
NOTICE:
Compressor Damage!
In order to prevent compressor damage, you MUST follow recommendations below:
Important:
Do NOT release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
• To prevent cross contamination of refrigerants and oils, use only dedicated R-410A service equipment.
• Disconnect unit power before evacuation and do not apply voltage to compressor while under vacuum. Failure to follow these instructions will result in compressor failure.
• Due to the presence of POE oil, minimize system open time. Do not exceed 1 hour.
• When recharging R-410A refrigerant, it should be charged in the liquid state.
• For the initial charging with the compressors off; charging to the liquid line is required to minimize starting the compressors with liquid refrigerant in the compressor oil sump.
• If suction line charging is needed to complete the charging process, only do so with the compressor operating.
• Allow the crankcase heater to operate a minimum of 8 hours before starting the unit.
Compressor Oil
The appropriate oil charge for a 7.5 ton scroll compressor is 6.3 pints. For 9 through 15 ton light commercial scroll compressors is 7 pints. For a 15, 20 and 25 ton large commercial scroll compressors (75 ton units), use 14.2 pints.
Scroll Compressor Replacements
Discoloration of the oil indicates that an abnormal condition has occurred. If the oil is dark and smells burnt, it has overheated because of: compressor operating at extremely high condensing temperatures; high superheat; a compressor mechanical failure; or, occurrence of a motor burnout.
If a motor burnout is suspected, use an acid test kit (KIT15496) to check the condition of the oil. Test results will indicate an acid level has exceeded the limit if a burnout occurred. Oil test kits must be used for POE oil (OIL00079 for a quart container or OIL00080 for a gallon container) to determine whether the oil is acidic. If a motor burnout has occurred, change the oil in both compressors in a tandem set.
CSHD Compressors (20-70 & 80 Ton)
For CSHD compressors this will require that the oil be removed using a suction or pump device through the oil equalizer Rotolock fitting, see
a dedicated device for removing oil. It is good practice to flush the suction device with clean oil prior to use.
Place a catch pan under the oil equalizer Rotolock connection fitting on the compressor to catch the oil that will come out of the compressor when the oil equalizer tube is removed from the compressor.
Prior to reinstalling the oil equalizer line to each compressor, replace the PTFE gasket on the oil equalizer Rotolock fitting on each compressor. See
Figure 93, p. 181 . Torque Rotolock nut to the values listed in Table 67, p. 181 .
Figure 92. CSHD
180 RT-SVX36G-EN
RT-SVX36G-EN
Maintenance
Charge the new oil into the Schrader valve on the shell of the compressor. Due to the moisture absorption properties of POE oil, do not use POE oil from a previously opened container. Also discard any excess oil from the container that is not used.
Figure 93. PTFE gasket
CSHN Compressors (75 & 89-130 Ton)
CSHN compressors have an oil drain valve, See
Figure 94 , which allows the oil to be drained out of
the compressor. After the refrigerant has been recovered, pressurize the system with nitrogen to help remove the oil from the compressor.
Charge the new oil into the Schrader valve or oil drain valve on the shell of the compressor. Due to the moisture absorption properties of POE oil, do not use POE oil from a previously opened container. Also discard any excess oil from the container that is not used.
Figure 94. CSHN
Oil equalizer Rotolock connection fitting
¼ Schrader port
Oil drain valve
Table 66. Oil charge per compressor
Compressor
CSHD 092
CSHD 110 thru 183
CSHN 176 thru 315
Pints
6.3
7.0
14.2
Table 67. Torque requirements for rotolock fittings
CSHD*
CSHN*
64 +/- 12 ft-lbs
100 +/- 10 ft-lbs
Note: Always replace gasket when reassembling oil equalizer lines.
181
Maintenance
Electrical Phasing:
If it becomes necessary to replace a compressor, it is very important to review and follow the
Electrical Phasing procedure described in the startup procedure of the IOM.
If the compressors are allowed to run backward for even a very short period of time, internal compressor damage may occur and compressor life may be reduced. If allowed to run backwards for an extended period of time the motor windings can overheat and cause the motor winding thermostats to open. This will cause a “compressor trip” diagnostic and stop the compressor
If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed. Check the electrical phasing at the compressor terminal box. If the phasing is correct, before condemning the compressor, interchange any two leads to check the internal motor phasing.
Precision Suction Restrictor:
Tandem manifold compressors that have unequal capacity sizes utilize a precision suction restrictor to balance the oil levels in the compressors. For tandem manifold compressors in Intellipak units, this restrictor
is placed in the compressor indicated in Table 68 .
When replacing this compressor, it is imperative that the proper restrictor is selected from those provided with the replacement compressor.
When the compressors are restarted verify that correct oil levels are obtained with both compressors operating.
Figure 95. Precision suction restrictor
Table 68. Suction restrictor location (AC/EC)
25 Ton Standard Capacity
25 & 29 Ton High Capacity
30 & 36 Ton High Capacity
40 Ton Standard Capacity
50 Ton Standard Capacity
CSHD125
CSHD125
CSHD161
CSHD110
CSHD120
60 Ton Standard Capacity
75 Ton Standard Capacity
75 & 89 Ton High Capacity
105 Ton High Capacity
115 Ton High Capacity
CSHD142
CSHN176
CSHN184
CSHN250
CSHN250
182 RT-SVX36G-EN
Suction Line Filter/Drier
Figure 96. Suction line filter/drier installation
16 “ min
CONDENSER - SUCTION
FILTER / DRIER PLACEMENT
There is a min. 16" straight distance from the Tee (Elbow) to anything in this line.
Maintenance
RT-SVX36G-EN
Table 69. Supply and exhaust/return fan VFD programming parameters
Menu Parameter
1-21
Description
Motor Power
Setting
Set Based on Motor
Nameplate
Description
Set only for applications using 3hp motors
Set to 2.2kW/3hp
Set only for 200/230v 60hz & 380/415
50Hz applications
Load & Motor
1-22
1-24
1-25
Motor Voltage
Motor Current
Motor Speed
Set Based on Motor
Nameplate
Set Based on Motor
Nameplate
Set Based on Motor
Nameplate
Sets the motor FLA
Sets the motor RPM
Limits & Warnings 215 Current Limit 100% Rated Current Limits the maximum current to motor
Note:
These parameters are motor specific and the actual motor nameplate rating must be used. Do not use the unit name plate values.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN.
183
Maintenance
VFD Programming Parameters
Units shipped with an optional variable frequency drive (VFD) are preset and run tested at the factory. If a problem with a VFD occurs, ensure that the programmed parameters listed in
have been set before replacing the drive.
Note: Check to make sure that parameter 1-23 is set to 60 Hz. To check parameter 1-23 press the
[Main Menu] button (press [Back] button if the main menu does not display), use the [
] button to scroll down to Load & Motor, press OK, use the [
] button to select 1-2, press OK, and finally use the [
] button until parameter 1-23 is displayed. Parameter 1-23 can then be modified by pressing OK button and using [
] and [
] buttons. When the desired selection has been made, press the OK button.
Should replacing the a VFD become necessary, the replacement is not configured with all of Trane's operating parameters. The VFD must be programmed before attempting to operate the unit.
To verify and/or program a VFD, use the following steps:
1.
At the unit, turn the 115 volt control circuit switch 1S70 to the “Off” position.
2. Turn the 24 volt control circuit switch to the “Off' position.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
HIGH VOLTAGE IS PRESENT AT TERMINAL BLOCK 1TB1 OR UNIT DISCONNECT SWITCH 1S14.
3. To modify parameters: a. Press Main Menu button (press [Back] button if the main menu does not display) b. Use the [ ] and [ ] buttons to find the parameter menu group (first part of parameter number) c. Press [OK] d. Use [ ] and [ ] buttons to select the correct parameter sub-group (first digit of second part of parameter number) e. Press [OK] f. Use [ ] and [ ] buttons to select the specific parameter g. Press [OK] h. To move to a different digit within a parameter setting, use the [<] and [>] buttons
(Highlighted area indicates digit selected for change) i. Use [ ] and [ ] buttons to adjust the digit j. Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting
4. Repeat step (3) for each menu selection setting in Table 69 .
5. To reset programming parameters back to the factory defaults: a. Go to parameter 14-22 Operation Mode b. Press [OK] c. Select “Initialization” d. Press [OK]
184 RT-SVX36G-EN
Maintenance
e. Cut off the mains supply and wait until the display turns off.
f. Reconnect the mains supply - the frequency converter is now reset.
g. Ensure parameter 14-22 Operation Mode has reverted back to “Normal Operation”.
Notes:
•
Item 5 resets the drive to the default factory settings. The program parameters listed in Table 69
will need to be verified or changed as described in Item 3 and 4.
•
Some of the parameters listed in the Table are motor specific. Due to various motors and efficiencies available, use only the values stamped on the specific motor nameplate. Do not use the Unit nameplate values.
•
A backup copy of the current setup may be saved to the LCP before changing parameters or resetting the drive. See LCP Copy in the VFD Operating Instructions for details.
6. Follow the start-up procedures for supply fan in the “Variable Air Volume System” section or the “Exhaust/return Airflow Measurement” start-up procedures for the exhaust/return fan.
7.
After verifying that the VFD(s) are operating properly, press the STOP key at the Human
Interface Module to stop the unit operation.
8. Follow the applicable steps in the “Final Unit Checkout” section to return the unit to its normal operating mode.
Monthly Maintenance
Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Filters
• Inspect the return air filters. Clean or replace them if necessary. Refer to the
for filter information.
Cooling Season
• Check the unit’s drain pans and condensate piping to ensure that there are no blockages.
• Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Coil Cleaning” later in this section.
• Manually rotate the condenser fans to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.
• Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.
• Verify that all damper linkages move freely; lubricate with white grease, if necessary.
• Check supply fan motor bearings; repair or replace the motor as necessary.
• Check the fan shaft bearings for wear. Replace the bearings as necessary.
• Lubricate the supply fan shaft bearings with a lithium based grease. Refer to
for recommended greases.
Note: The bearings are manufactured using a special synthetic lithium based grease designed for long life and minimum lube intervals. Over lubrication can be just as harmful as not enough.
RT-SVX36G-EN 185
Maintenance
186
• Use a hand grease gun to lubricate these bearings; add grease until a light bead appears all around the seal. Do not over lubricate!
• After greasing the bearings, check the setscrews to ensure that the shaft is held securely to the bearings and fan wheels. Make sure that all bearing supports are tight.
• Check the supply fan belt(s). If the belts are frayed or worn, replace them. Refer to the “Fan Belt
Adjustment” section for belt replacement and adjustments.
• Check the condition of the gasket around the control panel doors. These gaskets must fit correctly and be in good condition to prevent water leakage.
• Verify that all wire terminal connections are tight.
• Remove any corrosion present on the exterior surfaces of the unit and repaint these areas.
• Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.)
• Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.
• With the unit running, check and record the:
– ambient temperature;
– compressor oil level (each circuit);
– compressor suction and discharge pressures (each circuit);
– superheat and subcooling (each circuit);
Record this data on an “operator’s maintenance log” like the one shown in
the operating pressures indicate a refrigerant shortage, measure the system superheat and system subcooling. For guidelines, refer to “Charging by Subcooling”.
Important:
Do NOT release refrigerant to the atmosphere! If adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws.
Refer to general service bulletin MSCU-SB-1 (latest edition).
Heating Season
Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
• Inspect the unit’s air filters. If necessary, clean or replace them.
• Check supply fan motor bearings; repair or replace the motor as necessary.
• Lubricate the supply fan shaft bearings with a lithium based grease. Refer to
for recommended greases.
Note: The bearings are manufactured using a special synthetic lithium based grease designed for long life and minimum lube intervals. Too much lubrication in a bearing can be just as harmful as not enough.
• Use a hand grease gun to lubricate the bearings; add grease until a light bead appears all around the seal. Do not over lubricate!
• After greasing the bearings, check the setscrews to ensure that the shaft is held securely. Make sure that all bearing braces are tight.
RT-SVX36G-EN
Maintenance
Coil Cleaning
• Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs.
• Gas Heat Units only - Check the heat exchanger for any corrosion, cracks, or holes.
• Check the combustion air blower for dirt. Clean as necessary.
Note: Typically, it is not necessary to clean the gas furnace. However, if cleaning does become necessary, remove the burner inspection plate from the rear of the heat exchanger to access the drum. Be sure to replace the existing gaskets with new ones before reinstalling the inspection plate.
• Open the main gas valve and apply power to the unit heating section; then initiate a “Heat” test using the start-up procedure described in “Gas Furnace Start-Up”.
• Verify that the ignition system operates properly.
NOTICE:
Coil Cleaners!
Coil cleaners can damage roofs, surrounding buildings, vehicles, etc. Cleaning substances should be checked to ensure that they will not cause damage to surroundings. Coils and roof (if applicable) should be rinsed thoroughly. Do not spray coil cleaners in windy conditions.
Regular coil maintenance, including annual cleaning enhances the unit’s operating efficiency by minimizing:
•
compressor head pressure and amperage draw;
•
water carryover;
•
fan brake horsepower; and,
•
static pressure losses.
At least once each year—or more often if the unit is located in a “dirty” environment—clean the evaporator, microchannel condenser, and reheat coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
To clean refrigerant coils, use a soft brush and a sprayer.
Important:
DO NOT use any detergents with microchannel condenser coils. Pressurized water or air ONLY.
For evaporator and reheat coil cleaners, contact the local Trane Parts Center for appropriate detergents.
1.
Remove enough panels from the unit to gain safe access to coils.
WARNING
No Step Surface!
Do not walk on the sheet metal base. Walking on the base could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Important:
Bridging between the main supports required before attempting to enter into the unit. Bridging may consist of multiple 2 by 12 boards or sheet metal grating.
2. Straighten any bent coil fins with a fin comb.
RT-SVX36G-EN 187
Maintenance
188
3. For accessible areas, remove loose dirt and debris from both sides of the coil. For dual row microchannel condenser coil applications, seek pressure coil wand extension through the local
Trane Parts Center.
4. When cleaning evaporator and reheat coils, mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution to 150° F maximum to improve its cleansing capability.
Important:
DO NOT use any detergents with microchannel coils. Pressurized water or air ONLY.
5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used: a. The minimum nozzle spray angle is 15 degrees.
b. Do not allow sprayer pressure to exceed 600 psi.
c. Spray the solution perpendicular (at 90 degrees) to the coil face.
d. For evaporator and reheat coils, maintain a minimum clearance of 6" between the sprayer nozzle and the coil. For microchannel condenser coils, optimum clearance between the sprayer nozzle and the microchannel coil is 1"-3”.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. For evaporator and reheat coils, allow the cleaning solution to stand on the coil for five minutes.
7.
Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in Step 1; then restore power to the unit.
10. For evaporator and reheat coils, use a fin comb to straighten any coil fins which were inadvertently bent during the cleaning process.
Microchannel Condenser Coil Repair and Replacement
If microchannel condenser coil repair or replacement is required, seek HVAC Knowledge Center information or Service Guide document RT-SVB83*-EN for further details.
Steam or Hot Water Coils
To clean a steam or hot water coil, use a soft brush, a steam-cleaning machine, and water.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
1.
Verify that switches 1S1 and 1S70 are turned “OFF”, and that the main unit disconnect is locked open.
2. Remove enough panels and components from the unit to gain sufficient access to the coil.
3. Straighten any bent coil fins with a fin comb. (Use the data in Table 62, p. 176 to determine the
appropriate fin comb size.)
4. Remove loose dirt and debris from both sides of the coil with a soft brush.
5. Use the steam-cleaning machine to clean the leaving-air side of the coil first; start at the top of the coil and work downward; then clean the entering-air side of the coil, starting at the top of the coil and working downward.
6. Check both sides of the coil; if it still appears dirty, repeat Step 5.
7.
Reinstall all of the components and panels removed in Step 2; then restore power to the unit.
RT-SVX36G-EN
RT-SVX36G-EN
Maintenance
Evaporative Condenser Coil
Sump Water Management
Water Supply
Overall performance of any water- cooled device can be affected by suspended particulates, mineral concentration, trash and debris resulting in clogging and heat transfer loss. The unit is designed to greatly minimize problems with these impurities, however, float valves and solenoid valves are used to control the incoming water.
If the incoming water contains contaminants, sand or other objects, it is best to insert an incoming line strainer having a mesh of 80 to 100. The inlet line should be flushed prior to connection to the unit, whether or not there is a strainer.
There is an air gap between the water inlet float valve and sump water level to prevent back flow; however, if local code dictates, a backflow prevention valve may be required (field-provided and installed by others).
Water Drain
Local Site Discharge: Rooftop or simple storm sewer discharge is generally acceptable. Do not routinely direct the sump discharge onto an area that will be adversely affected. For example, continued sump discharge into a flower bed where the input water contains CaCO3 (lime) will eventually decrease the pH of the soil.
Sewer Discharge: The quantities of mineral and debris flushed are actually very small and do not cause problems when diluted in normal sewer flow. However, local, state or federal standards and restrictions must be followed in any given locality.
Traditional Bleed Method
ASHRAE recommendation for continuous bleed rates:
With good, quality makeup water, the bleed rates (0.8 - 2 GPH/ton) may be as low as one-half the evaporation rate (1.6 -2 GPH), and the total water consumption would range from 2.4 GPH/ton for air conditioning to 3 GPH/ton for refrigeration (Chapter 36.17 of ASHRAE's “Systems and
Equipment Handbook”)
Operation and Care
The sump should be inspected at least every 6 months for possible build up of scale pieces that has been shed from the coils. The sump flush frequency or bleed rate should be increased if large amounts of scale are present.
If the water has a “milky or cloudy” appearance, then minerals are concentrating in the sump and the number of flushes should be increased.
If the water remains clear between flushes, then the number of flushes can be decreased. Through field trials, the optimum flush frequency can be determined. Please note that in some areas, water quality can vary during different times of the year. The sump water clarity should be checked periodically.
The evaporative condenser has several design features to reduce the possibility of biological growth in the sump. These features include:
• Air inlets constructed to eliminate direct sunlight in the sump
• The sump flush sequence replenishes the sump with fresh water 1 to 12 times per day depending on the flush setting
• The copper tubing in the coils is a natural biocide
Important:
Do not use chlorine tablets directly on stainless steel surface as it can adversely affect its corrosion resistance.
189
Maintenance
Always consult local codes for water treatment and waste water removal requirements. Consult a water treatment expert for water analysis and chemical treatment methods and recommendations for specific applications.
If deemed necessary after consultation with local water experts, there are various means of water treatment available which can be field installed.
Copper Coil Cleaning
With proper water treatment, scale should not form on the coil, and coil cleaning should not be required. In the event that scale starts to form on the coil, it is imperative that it is removed immediately. The formation of scale can greatly reduce the performance and reliability of the coil.
To remove any scale that forms use only 100% citric acid based cleaners such as “Now” or other pure citric acid products.
Important:
Do not use HCL-, muriatic acid, or ammonia-based cleaners as they can adversely affect copper.
Do not power wash condenser fan. See RT-SVB83*-EN for additional information.
Table 70. Evaporative Condenser Models—Maintenance and Troubleshooting
Component
Fan Motor
Sump Pump
Sump
Action
None Required
Inspect/Clean
Inspect/Clean
Maintenance Schedule
Frequency
1 – 2 times per year
1 – 2 times per year depending on water hardness and unit run time
Comments
Non-grease bearings
Clean inlet openings to pump
Sump can be drained and hosed out using hose bib provided at water fill solenoid valve.
Vacuuming scale out is an alternate method.
Float should be free for full float travel Sump Float Switch
Sump Float
Make Up Valve
Inspect
Inspect for proper water level
Spray Nozzles
Conductivity Sensor
Inspect/Clean
Inspect/Clean
Conductivity Controller Inspect/Recalibrate
Component
Fan Motor
Sump Pump
Sump Pump
Spray Nozzle
Problem
Does not run
Does not run
Low Flow
Dry area on coil
1 – 2 times per year
1 – 2 times per year
1 – 2 times per year
1 – 2 times per year
1 – 2 times per year
Troubleshooting
Check
Inspection through access panel
Clean sensor to ensure accurate readings
Recalibrate controller
Fix
Condenser Fan Relay closure and control voltage indicating a call from compressor control panel for the condenser fan to operate. Sump Pump
Overload Trip. Fan Motor Overload Trip. Fan fuse trip.
Check each motor overload and reset if necessary. Check amp draw for each leg.
Sump Pump Overload Trip Low Water Level or faulty float switch. Unit in ‘Dry Mode’ Operation
Reset – check amps on each leg to determine if faulty motor. Check and clean debris around float switch. Check Ambient thermostat setting and mode of operation (close on rise). See section 2 for T’stat setup instructions.
Pump may be operating backwards or impeller inlet may be slightly blocked.
Change pumping direction by changing any two legs to the pump motor. Disconnect Power and remove pump to inspect for possible impeller obstruction.
Check for proper spray pattern over each quadrant.
Remove debris from clogged nozzle.
190 RT-SVX36G-EN
Maintenance
Fall Restraint
WARNING
Falling Off Equipment!
This unit is built with fall restraint slots located on unit top that MUST be used during servicing. These slots are to be used with fall restraint equipment that will not allow an individual to reach the unit edge. However such equipment will NOT prevent falling to the ground, for they are NOT designed to withstand the force of a falling individual. Failure to use fall restraint slots and equipment could result in individual falling off the unit which could result in death or serious injury.
The fall restraint is located approximately 3 feet from the unit edge. Figure 97, p. 191
Figure 97. Fall restraint
Fall restraint
RT-SVX36G-EN 191
Maintenance
Final Process
For future reference, you may find it helpful to record the unit data in the blanks provided.
Complete Model Number:
Unit Serial Number:
Unit “DL” Number (“Design special” units only):
Wiring diagram numbers (from unit control panel):
-schematic(s)
-connections
Unit Address (TCI)
Network ID (LCI or BCI)
192 RT-SVX36G-EN
Maintenance
RT-SVX36G-EN 193
Unit Wiring Diagram Numbers
Note: Wiring diagrams can be accessed via e-Library by entering the diagram number in the literature order number search field or by calling technical support.
Table 72. Unit Wiring Diagram Numbers
Diagram
Number
2313-1002
2313-1003
2313-1004
2313-1005
2313-1007
2313-1008
2313-1009
2313-1010
2307-9110
2307-9184
2307-9111
2307-9185
2307-9112
2307-9105
2307-9179
2307-9106
2307-9180
2307-9107
2307-9181
2307-9108
2307-9182
2307-9128
2307-9129
2307-9130
2307-9131
2307-9186
2307-9113
2307-9187
2307-9114
2307-9115
2307-9188
2313-1016
2307-3891
Tons
90-130
20-75
90-130
20-30
40-75
90-130
24-89
20-130
24/36-89
24/36-89
24/36-89
24/36-89
29
29
29
29
20-75
90-130
20-75
90-130
20-75
20, 30, 75
90-130
20, 30, 75
90-130
20, 30, 75
90-130
20, 30, 75
90-130
25
25
25
25
2307-3892 20-130
2307-3955
2307-3956
2307-3894
2307-3895
2307-9148
Continued on next page
20-130
20-130
20-130
20-130
20-30
Description
Power Schematic - Standard
Power Schematic - Standard
Power Schematic - w/ Supply Fan VFD
Power Schematic - w/ Supply Fan VFD
Power Schematic - w/ Exhaust/Return VFD
Power Schematic - w/ Exhaust VFD
Power Schematic - w/ Supply & Exhaust/Return VFD
Power Schematic - w/ Supply & Exhaust VFD
Power Schematic - Standard
Power Schematic - w/ Supply Fan VFD
Power Schematic - w/ Exhaust/Return VFD
Power Schematic - w/ Supply & Exhaust/Return VFD
Power Schematic - Evap Cooled Standard
Power Schematic - Evap Cooled w/ Exh/Ret VFD
Power Schematic - Evap Cooled w/ Sup VFD
Power Schematic - Evap Cooled w/ Sup & Exh/Ret VFD
Power Schematic - Evap Cooled Standard
Power Schematic - Evap Cooled w/ Sup VFD
Power Schematic - Evap Cooled w/ Exh/Ret VFD
Power Schematic - Evap Cooled w/ Sup & Exh/Ret VFD
Schematic Rooftop Module - Standard
Schematic Rooftop Module - Standard
Schematic Rooftop Module - w/ Supply Fan VFD
Schematic Rooftop Module - w/ Supply Fan VFD
Schematic Rooftop Module - w/ Exhaust/Return VFD
Schematic Rooftop Module - w/ Exhaust VFD
Schematic Rooftop Module - w/ Supply Fan & Exhaust/Return VFD
Schematic Rooftop Module - w/ Supply Fan & Exhaust VFD
Schematic Single Circuit Compressor Module
Schematic Multiple Circuit Compressor Module
Schematic Standard Compressor or w/ Supply Fan or w/ Exhaust VFD
Schematic Evap Cooled
Schematic - Heat & GBAS Modules Electric, 2-Stage Gas, Hydronic Heat
Schematic Heat & GBAS Modules - w/ Supply VFD or w/ Supply & Exhaust/Return VFD, Elec,
2-Stage Gas, Hydronic Heat
Schematic - Standard or w/ Exhaust/Return VFD, Modulating Gas Heat
Schematic and Connection Wiring 500, 850 & 1000MBH 2 Stage Natural Gas Heat
Schematic Wiring Diagram ECE, VOM, TCI, IPCB, HI & RHI Modules
Schematic Wiring Diagram ECE, VOM, TCI, IPCB, HI & RHI Modules- w/ Exhaust/Return VFD
Connection Control Box - Standard
194 RT-SVX36G-EN
Unit Wiring Diagram Numbers
Table 72. Unit Wiring Diagram Numbers
Diagram
Number
2307-9153
2313-1025
2313-1026
2307-9158
2307-9162
2307-9199
2307-9159
2307-9163
2307-9200
2307-9160
2307-9164
2307-9201
2307-9161
2307-9165
2307-9202
2313-1028
2307-9190
2307-9149
2307-9154
2307-9191
2307-9150
2307-9155
2307-9192
2307-9151
2307-9156
2307-9193
2313-1023
2313-1024
2313-1029
2313-1030
2313-1031
2307-9167
2307-9171
2307-9204
2307-9168
2307-9172
2307-9205
2307-9169
2307-9173
2307-9206
2307-9170
2307-9174
2307-9207
2313-1033
Tons
40-75
90-130
20-30
40-75
90-130
20-30
40-75
90-130
24-89
24-89
24-89
20-30
40-75
90-130
20-30
40-75
90-130
20-30
40-75
90-130
20-30
40-75
90-130
20-30
40-75
90-130
24-89
24-89
90-130
20-30
40-75
90-130
20-30
40-75
90-130
24-89
24-89
24-89
24-89
20-30
40-75
90-130
20-30
40-75
Description
Connection Control Box - Standard
Connection Control Box - Standard
Connection Control Box - w/ Supply Fan VFD
Connection Control Box - w/ Supply Fan VFD
Connection Control Box - w/ Supply Fan VFD
Connection Control Box - w/ Exhaust/Return VFD
Connection Control Box - w/ Exhaust/Return VFD
Connection Control Box - w/ Exhaust VFD
Connection Control Box - w/ Supply & Exhaust/Return VFD
Connection Control Box - w/ Supply & Exhaust/Return VFD
Connection Control Box - w/ Supply & Exhaust VFD
Connection Control Box Evap Cooled Standard
Connection Control Box Evap Cooled w/ Sup VFD
Connection Control Box Evap Cooled w/ Exh/Ret VFD
Connection Control Box Evap Cooled w/ Sup & Exh/Ret VFD
Connections Common Control Modules - Standard
Connection Unit Control Modules -Standard
Connections Common Control Modules - Standard
Connections Common Control Modules- w/ Supply Fan VFD
Connection Unit Control Modules - w/ Supply Fan VFD
Connections Common Control Modules- w/ Supply Fan VFD
Connections Common Control Modules - w/ Exhaust/Return VFD
Connection Unit Control Modules - w/ Exhaust/Return VFD
Connections Common Control Modules - w/ Exhaust VFD
Connections Common Control Modules - w/ Supply & Exhaust/Return VFD
Connection Unit Control Modules - w/ Supply & Exhaust/Return VFD
Connections Common Control Modules - w/ Supply & Exhaust VFD
Connection Module Evap Cooled Standard
Connection Module Evap Cooled w/ Sup VFD
Connection Module Evap Cooled w/ Exh/Ret VFD
Connection Module Evap Cooled w/ Sup & Exh/Ret VFD
Connections Raceway- Standard
Connections Raceway- Standard
Connections Raceway- Standard
Connections Raceway - w/ Supply Fan VFD
Connections Raceway - w/ Supply Fan VFD
Connections Raceway - w/ Supply Fan VFD
Connections Raceway - w/ Exhaust/Return VFD
Connections Raceway - w/ Exhaust/Return VFD
Connections Raceway - w/ Exhaust VFD
Connections Raceway - w/ Supply & Exhaust/Return VFD
Connections Raceway - w/ Supply & Exhaust/Return VFD
Connections Raceway - w/ Supply & Exhaust VFD
Connection Raceway Evap Cooled Standard
RT-SVX36G-EN 195
Unit Wiring Diagram Numbers
Table 72. Unit Wiring Diagram Numbers
Diagram
Number
2313-1034
Tons
24-89
Continued on next page
2313-1035
2313-1036
2307-9176
2307-9177
2313-1038
2313-1039
2313-1011
2307-4327
2307-9102
2307-9103
2306-8932
24-89
24-89
20-75
20-75
24-89
24-89
20-130
20-40
20-130
20-130
20-75
2306-8933
2306-8934*
2307-2175
2306-8935
2306-8934*
2307-2171
2307-2172
2307-2173
2307-2174
2309-3199
2309-3576
2309-3577
2309-3579
2309-3203
2309-3580
2309-3581
2309-3583
2309-3201
2309-3578
2309-3205
2309-3582
20-75
30-75
20-75
20-89
90-130
90-130
20-75
20-89
20-75
30-75
90-130
30-75
90-130
20-75
20-75
90-130
90-130
20-130
20-130
20-130
20-130
Description
Connection Raceway Evap Cooled w/ Sup VFD
Connection Raceway Evap Cooled w/ Exh/Ret VFD
Connection Raceway Evap Cooled w/ Sup & Exh/Ret VFD
Field Connection - Constant Volume
Field Connection - Variable Air Volume
Field Connection - Evap Cooled CV
Field Connection - Evap Cooled VAV
Schematic/Connection - 2-Stage Natural Gas Heat 235 & 1000 MBH
Schematic/Connection - 2-Stage Natural Gas Heat 235 & 350 MBH
Schematic/Connection - 2-Stage Natural Gas Heat 500, 850 & 1000 MBH
Schematic/Connection - Modulating Natural Gas Heat 500, 850 & 1000 MBH
Schematic - Electric Heat - 460/575V - 2 Circuit
Schematic - Electric Heat All Voltages - 3 Circuit
Schematic - Electric Heat All Voltages - 6 Circuit
Connection - Electric Heat - 460/575V - 6 Circuit - 190 KW
Schematic - Electric Heat - 200V - 7 Circuit
Schematic - Electric Heat - 460/575V - 6 Circuit - 190 KW
Connection - Electric Heat - 460/575V - 2 Circuit - 3 or 1 Step
Connection - Electric Heat - All Voltages - 3 Circuit - 3 or 1 Step
Connection - Electric Heat - All Voltages - 6 Circuit - 3 or 1 Step
Connection - Electric Heat - 200V - 7 Circuit - 3 or 1 Step
Schematic/Connection - Supply VFD - w/ ByPass
Schematic/Connection - Supply VFD - w/ ByPass
Schematic/Connection - Supply VFD #1 - w/ ByPass
Schematic/Connection - Supply VFD #2 - w/ ByPass
Schematic/Connection - Supply VFD - w/o ByPass
Schematic/Connection - Supply VFD - w/o ByPass
Schematic/Connection - Supply VFD #1 - w/o ByPass
Schematic/Connection - Supply VFD #2 - w/o ByPass
Schematic/Connection - Exhaust/Return VFD - w/ ByPass
Schematic/Connection - Exhaust/Return VFD - w/ ByPass
Schematic/Connection - Exhaust/Return VFD - w/o ByPass
Schematic/Connection - Exhaust/Return VFD - w/o ByPass
196 RT-SVX36G-EN
Warranty
Commercial Equipment Rated 20 Tons and Larger and Related Accessories
PRODUCTS COVERED - This warranty* is extended by Trane Inc. and applies only to commercial equipment rated 20 Tons and larger and related accessories.
The Company warrants for a period of 12 months from initial start-up or 18 months from date of shipment, whichever is less, that the Company products covered by this order (1) are free from defects in material and workmanship and (2) have the capacities and ratings set forth in the
Company’s catalogs and bulletins, provided that no warranty is made against corrosion, erosion or deterioration. The Company’s obligations and liabilities under this warranty are limited to furnishing f.o.b. factory or warehouse at Company designated shipping point, freight allowed to
Buyer’s city (or port of export for shipment outside the conterminous United States) replacement equipment (or at the option of the Company parts therefore) for all Company products not conforming to this warranty and which have been returned to the manufacturer. The Company shall not be obligated to pay for the cost of lost refrigerant. No liability whatever shall attach to the
Company until said products have been paid for and then said liability shall be limited to the purchase price of the equipment shown to be defective.
The Company makes certain further warranty protection available on an optional extra-cost basis.
Any further warranty must be in writing, signed by an officer of the Company.
The warranty and liability set forth herein are in lieu of all other warranties and liabilities, whether in contract or in negligence, express or implied, in law or in fact, including implied warranties of merchantability and fitness for particular use. In no event shall the Company be liable for any incidental or consequential damages.
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES
AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW
OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
PARTICULAR USE, IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES.
Manager - Product Service
Trane Inc.
Clarksville, Tn 37040-1008
PW-215-2688
*A 10 year limited warranty is provided on optional Full Modulation Gas Heat Exchanger.
*Optional Extended Warranties are available for compressors and heat exchangers of Combination
Gas-Electric Air Conditioning Units.
RT-SVX36G-EN 197
Index
Symbols
"Gate" type valve
,
"Ship with" Locations
“Wet heat” coil fin data
Numerics
1U51
3RT3
5K86
5K87
5K89
5K90
5K91
5K92
5K93
5K94
5RT16
5S67
5S71
5U108
5U57
5U59
5U66
5U68
5U69
5U70
A
AC
AC Conductors
Acronyms
Actuator
Actuator shaft adapter removal/ assembly
adjusting the fresh air damper
Airflow Measurements
Altitude Correction Factors
B
BACnet Communication Interface
Module
BAS
BAYSENS016
BAYSENS016*
BAYSENS021
BAYSENS021*
BAYSENS036*
BAYSENS073
BAYSENS073*
BAYSENS074
BAYSENS074*
BAYSENS077
BAYSENS077*
BAYSENS108
BAYSENS110
BAYSENS110*
BAYSENS119
BAYSENS119*
BAYSTAT023*
BCI
,
C
calibrate conductivity
Center of Gravity
Center of Gravity Data
center-of-gravity
Charge Storage
Charging by Subcooling
Chemical Water Treatment Tree
Clearances
clearances
CO2 Reset
Coil Cleaning
Component Static Pressure
Drops
Compressor Circuit Breakers
Compressor Module
Compressor Motor Winding
Thermostats
Compressor Start-Up
concealed damage
Condensate Drain Connections
Condensate Drain Locations
Condensate trap
condensate trap
Condenser fan location
condensing temperature
condensing temperature rises above the "lower limit"
Conductivity Controller
Connection Sizes
Connection sizes for hot water and steam coil
Constant Volume
,
Constant Volume (CV) Units
Constant Volume & Variable Air
Volume Units
Constant Volume System
Controls
Control Module Locations
Controls using 24 VAC
Cooling Sequence of Operation
Cross Section
Customer connection wire range
CV control options
D
Daytime Warm-up
DC Analog Input/Outputs
DC Conductors
Demand Limit Relay
dimensional data
DIP switch settings
discharge pressure
Discharge Temperature Control
Changeover Contacts
Disconnect Switch
Drain Valve
Drain valve actuator
Drain Valve Setup
DSP control devices
Ductwork
E
economizer
Economizer Damper
Adjustment
efficiency check point
Electric Heat
,
,
,
Electric Heat Units
Electrical Phasing
Emergency Override Definitions
Emergency Stop Switch
Entering Evaporator Temperature
Sensor
Evaporative Condenser - Sequence of
Operation
Evaporative Condenser - Water &
Drain Line Installation
Evaporative Condenser Fan Shipping
Brackets
Evaporative-Cooled Condenser
Sequence of Operation
Evaporator Temperature Differential
Setpoint
Exhaust Airflow Measurement
exhaust fan
Exhaust/Comparative Enthalpy
Module
Exhaust/Return Fan Shipping
Channels
External Auto/Stop Switch
198 RT-SVX36G-EN
Index
F
F/A Damper travel adjustment
Factory Mounted Disconnect
Switch
factory mounted disconnect switch
factory mounted non-fused disconnect switch
Fan Performance Tables
Field Connection Diagram
Field Installed Control Wiring
Filter data
Filter Switch
filters
float and thermostatic traps
,
Float-and-Thermostatic
Flue Assembly
flue assembly
Freeze Avoidance
Freeze Protection
Freezestat
Fresh Air and Return Air Linkage
Adjustment
Fresh air damper pressure drop
fuse replacement
fuse replacement data
G
Gas Heat Units
Gas Heating Sequence of
Operation
Gas Train
Gas Trains
gas trains
GBAS
,
Generic Building Automation
System
Generic Building Automation System
Module
Grease recommendations
H
Head Pressure Control
Heat Module
heating coil falls to 40°F
High Duct Temp Thermostats
High Pressure Controls
High Superheat diagnostic
Honeywell Ignition System
Hot Water and Steam Coil
Hot Water Heat Units
Hot Water Piping
Hot water piping
,
hot water piping
Human Interface Module
I
Input Devices & System
Functions
Installation Checklist
Interprocessor Communications
Board
L
Lead-Lag
Leaving Evaporator Temperature
Sensor
Low Ambient Compressor
Lockout
Low Ambient Control
Low Charge Protection
Low Pressure Control
M
Main Unit Power Wiring
Make-up Water and Drain Line
Installation
Manual Motor Protectors
Microchannel Coil Repair and
Replacement
Minimum Position
Potentiometer
Model Number Descriptions
Modulating Dehumidification
Module MDM
modulating gas
Modulating Gas Heat Settings
Modulating Gas Sequence of
Operation
Morning Warm-Up
Morning Warm-up
morning warm-up
Morning Warm-Up - Zone Heat
Multipurpose Module
N
nameplate
Non-Trane roof curbs
O
O/A Sensor & Tubing Installation
Occupied Cooling
occupied heating
,
Occupied/Unoccupied Contacts
operating weights
operating weights, air-cooled condenser
operating weights, evaporative condenser
operation and service clearances
Outdoor Air Humidity Sensor
Outside Air Sensor
P
Pitch Pocket Location
Power Wire Sizing
Power Wire Sizing & Protection
Device Equations
Power Wiring
Pressure Drop Tables
Pressure Sensing
Propane Gas
Protection Device Equations
P-Traps
purge setpoints
R
Rapid Restart
Refrigerant Charging
Refrigerant coil fin data
Remote Panel w/ NSB
Remote Panel w/o NSB
Remote Zone Sensor
Removing Supply and Exhaust Fan
Shipping Channels
Return air
Return Air Humidity Sensor
Return Air Temperature Sensor
Return Fan
return fan
,
Return Fan Performance
Return Plenum Pressure
Control
Return Plenum Pressure High
Limit
Roof Curb
Roof Curb and Ductwork
Rooftop Module
RTM resistance input vs. setpoint temperatures
Rubber Isolators
S
S_HK Cooling and Heating Units
SAHL cooling-only units
Saturated Condenser Temperature
Sensors
Scroll Compressor
Replacement
RT-SVX36G-EN 199
Index
SEHL, SFHL, SLHL, SSHL, SXHL units
Shipping Channels
Shipping Hardware
Sizing Natural Gas Pipe Mains and
Branches
Sizing natural gas pipe mains and branches
Space Pressure Transducer
Space Temperature Averaging
,
Space/Duct Humidity Sensor
Specific Gravity Multipliers
Spring Isolators
Status/Annunciator Output
Steam Coil Piping
Steam Heat
Steam Heat Units
Steam or Hot Water
steam or hot water
suction line filter
Suction line filter/drier installation
superheat
,
supply air
Supply Air Pressure
SUPPLY AIR temp setpoint cooling
Supply Air Temperature Low
Limit
Supply Air Temperature Sensor
Supply Air Tempering
Supply and Exhaust Airflow Proving
Switches
Supply and Exhaust Fan Circuit
Breakers
Supply and exhaust fan VFD programming parameters
Supply and Exhaust/Return Fan
Circuit Breakers
swing-check vacuum breaker
SZVAV
,
,
T
Temperature vs. Resistance
Coefficient
Thermostatic Expansion
Valves
,
Trane Communication Interface
Transducer
Traq Sensor
TraqTM Sensor Airflow
Measurement
Two Stage Gas Furnace
Typical field wiring
,
Typical gas furnace
Typical ventilation override binary
U
Unit Component Layout
Unit Dimensions
Unit Inspection
Unit Nameplate
Unit Rigging & Placement
Unit Start Up
V
Variable Air Volume (VAV) and
Constant Volume (CV) Units
Variable Air Volume and Constant
Volume System Controls
Ventilation Control Module
Ventilation Override Module
Voltage Imbalance
Voltage Supply
Voltage utilization range
VOM Contacts
W
Wall or Duct Mount Humidity
Sensor
water connection locations
Water Quality
Weights
weights, evaporative condenser
weights, roof curb
Wet Airside Pressure
Wet Heat Sequence of
Operation
wing-check vacuum breaker
,
Wiring Diagram
,
Wiring Diagram Numbers
Z
Zone Temperature - Cooling
Zone Temperature - Heating
Zone Temperature Control Zone
Panel
200 RT-SVX36G-EN
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2011 Trane All rights reserved
RT-SVX36G-EN 21 Oct 2011
Supersedes RT-SVX36E-EN (04 Apr 2011)