advertisement
EPPE C
X
POWER QUALITY ANALYSIS
EPPE - Power Quality Analysis
EPPE C X
Various models
Integrated sensor card (PV systems, wind power plants, industrial plants)
Replaceable measurement data memory
(2 GB)
Integrated energy meter
6 current inputs (differential current measurement)
Webserver
Dual processor system
EPPE - Power Quality Analysis
EPPE C X
5" TFT graphical touch screen
Configuration and data download via USB flash drive
Multi-client capability
IEC 61850 protocol
EPPE - Power Quality Analysis
EPPE C X – Analog Inputs
Model 1:
4 current inputs
4 voltage inputs
Monitoring of one voltage system
Direct current measurement up to 40 A permanently
Voltage measurement up to 600 VAC
Accuracy < 0.05%
Sampling rate of 200 kHz
EPPE - Power Quality Analysis
EPPE C X – Analog Inputs
Model 2
8 voltage inputs
- 8 x 600 V
- 4 x 600 V / 4 x 3 V
Monitoring of 2 voltage systems
- Cost optimisation
- Monitoring to EN50160
Connection of current clamps and current sensors
EPPE - Power Quality Analysis
EPPE C X – Sensor Card
Additional sensor card (optional)
High flexibility
Various sensors can be connected
- temperature, light irradiation, wind speed ,…
Control of external machines / plants
Differential current measurement
…
EPPE - Power Quality Analysis
EPPE C X – Sensor Card
4 analog inputs
Sampling rate 200KHz
Measuring ranges:
- 300 V rms
(voltage measurement, sensors)
- 10 V (sensors)
- 2 V rms
(current clamps / sensors)
- 20 mA (sensors)
4 analog inputs
Sampling rate 100 Hz
Measuring ranges:
- 10 V (sensors)
EPPE - Power Quality Analysis
EPPE C X – Sensor Card
2 direct temperature inputs
Sampling rate: 100Hz
Type: PT 100, 500, 1000
1 analog output
Adjustable process output to control external systems
Selectable output signal:
- 10 V / - 20 mA
EPPE - Power Quality Analysis
EPPE C X – Communication / Power supply
Ethernet (RJ45)
Optical Ethernet (optical fibre)
RS232, RS485
USB passive / active
Data download and configuration via USB flash drive
Connection options for external modems, UMTS router ,…etc.
Communication protocols Modbus,
IEC 61850, etc.
EPPE - Power Quality Analysis
EPPE C X – Communication / Power supply
Replaceable measurement data memory
Power supply units: 85…265 VAC,
90…350 VDC, 9…72 VDC
„Maintenance-free“ internal emergency power supply
EPPE - Power Quality Analysis
EPPE C X – Time synchronisation
Internal real-time clock
NPT/SNTP
DCF 77
IRIG-B
Internal GPS receiver
External GPS central clock
Seconds and minutes pulse
Interlink interface for the synchronisation of EPPE CX devices with each other
EPPE - Power Quality Analysis
EPPE C X – Binary Inputs
14 Binary inputs
Statistical evaluations
(recording),
Logging of states / signals
Monitoring system
operating times / status of other systems (machines), e.g. how long the ventilator/heating system has been used
EPPE - Power Quality Analysis
EPPE C X – Binary Outputs
2 Relay outputs / 6 electron. relay outputs
Monitoring function, status information on the device, e.g. factory master control system
Messages: new record, system error,…
EPPE - Power Quality Analysis
EPPE C X - Overview
4 x analog input (voltage 600 VAC, 200 kHz, accuracy 0.05%)
4 x analog input (voltage 600 VAC, voltage 3 VAC,
current 40 AAC, 200 kHz, accuracy
0.05%)
14 x binary input (24…300 VDC)
8 x relay output (2 mech. / 6 electron.)
Time synchronisation: GPS, DCF, NTP, PC, IRIG-B, pulse input,
intercommunication interfaces
Power Supply
: 85…265 VAC, 90…350 VDC, 9…72 VDC
Communication: Ethernet, 3 x USB (active/passive),
optical Ethernet (optical fibre) RS232, RS485
Sensor card
4 x analog input (300 V, 10 V, 2 V, 20 mA, 200 kHz)
4 x analog input (10 V, 100 Hz)
2 x temperature input (PT 100, PT 500, PT 1000)
1 x process output (10 V / 20 mA)
EPPE - Power Quality Analysis
EPPE C X - Front
EPPE - Power Quality Analysis
EPPE C X – Display Functions
• Simplified menu navigation
• Displaying up to the 63rd harmonic
• Zoom functions
EPPE - Power Quality Analysis
EPPE C X – Display Functions
• Zoom functions
EPPE - Power Quality Analysis
EPPE C X – Display Functions
• Improved auto-scaling
• Displaying fault records directly on the device
• Date, time, criterion, …
EPPE - Power Quality Analysis
EPPE C X – Standard Models
4 Standard models
Price optimisation
Short delivery time
Standard equipment:
• 14 binary inputs
• 8 relay outputs (2 mech. / 6 electron.)
• 5"-TFT graphical touch screen (640 x 480 pixel)
• Membrane keypad with 4 function keys
• Data memory: 2 GB flash (replaceable)
• Communication interfaces: 1 x RS232, 1 x RS485, 3 x USB, 1 x Ethernet
• Time synchronisation: GPS, DCF, NTP, IRIG-B, Interlink interface
EPPE - Power Quality Analysis
EPPE C X – Standard Models
Power quality analyser EPPE CX – IAC
• Analog inputs: 4 x 600 V Ph-N, 4 x 40 A
• Internal power supply unit, voltage range 85-265 VAC / 90-350 VDC
Power quality analyser EPPE CX – IDC
• Analog inputs: 4 x 600 V Ph-N, 4 x 40 A
• Internal power supply unit, voltage range 36-72 VDC
Power quality analyser EPPE CX – UAC
• Analog inputs: 4 x 600 V Ph-N, 4 x 600V Ph-N
• Internal power supply unit, voltage range 85-265 VAC / 90-350 VDC
Power quality analyser EPPE CX
– UDC
• Analog inputs: 4 x 600 V Ph-N, 4 x 600 V
• Internal power supply unit, voltage range 36-72 VDC
EPPE - Power Quality Analysis
EPPE C X – Configureable Model
Power quality analyser EPPE CX – Basic unit
Equipment:
• Slot to accommodate one internal power supply unit
• Slot to accommodate one analog measuring module
• Slot to accommodate one optional sensor measuring module
• 14 binary inputs
• 8 relay outputs (2 mech. / 6 electron.)
• 5"-TFT graphical touch screen (640 x 480 pixel)
• Membrane keypad with 4 function keys
• Data memory: 2 GB flash (replaceable)
• Communication interfaces: 1 x RS232, 1 x RS485, 3 x USB, 1 x Ethernet
• Optional: optical Ethernet (optical fibre)
• Time synchronisation: GPS, DCF, NTP, IRIG-B, Interlink interface
• Optional: Communication protocols IEC 61850, DNP3.0, Profibus
EPPE - Power Quality Analysis
EPPE Software
Features
All applications in one software package
Configuration of the measuring system
Automatic device and data handling
Evaluation and report creation
Online monitoring
Clearly designed user interface
Intuitive operation
Short familiarisation period
High effectzivity
EPPE - Power Quality Analysis
EPPE Software
Device management
Clear structure
Status reports on the devices
Different installation levels (region, measurement location
,…etc.)
Graphical device overview
Integration of personal maps, cicuit diagrams, etc.)
Device status
Zoom functions
EPPE - Power Quality Analysis
EPPE Software
Device list / Graphical overview Device parameter / status Analysis
EPPE - Power Quality Analysis
EPPE Software
Configuration
Simple configuration according to specific standards (e.g. EN50160)
Cyclic measurement
Averaging interval
Min./max. values
Min./max. time
Events
Configurable limit values
Fault recorder
Configurable sampling rate
(up to 30 kHz)
Configurable pre-fault, fault and postfault period
Fault records on binary channels
Energy meter
Logical links
EPPE - Power Quality Analysis
EPPE Software
Analysis
Trend analysis
Time period adjustable at any time
Numerous graphic analysis tools
Superimposition of signal characteristics
Graphical display of the extreme value duration distribution
Formula editor for mathematical signal characteristics
Automatic generation of PQ reports
Data export for third party systems
(PQDIF, Comtrade, CSV)
Automatic calculation of a differential current measurement
Navigator for a better overview and selection of the time window
EPPE - Power Quality Analysis
EPPE Software
Navigator
EPPE - Power Quality Analysis
EPPE Software
Evaluation
Event analysis
Event analysis with signature display
Event classification
Graphic analysis tools
Navigator for a better overview and selection of the time window
EPPE - Power Quality Analysis
EPPE Software
Evaluation
Limit value overview
Automatic evaluation according to specific standards (e.g. EN50160)
Tabular and graphical overview of limit value violations
Navigator for a better overview and selection of the time window
EPPE - Power Quality Analysis
EPPE Software
Evaluation
Fault record analysis
Graphical display of the fault characteristic
Vector analysis
Harmonic analysis
Superimposition of signal characteristics
Formula editor for mathematical signal analysis
Typification of power system faults
Navigator for a better overview and selection of the time window
Generation of fault reports
Data export for third party systems
EPPE - Power Quality Analysis
EPPE Software
EPPE - Power Quality Analysis
EPPE Software
Software Versions
3 software versions which differ in functionality and in the number of measuring instruments to be managed:
1. EPPE software “Basic“
- Functionality limited to power quality measurements in compliance with valid standards (e.g. to EN50160)
- Management of up to 5 EPPE measuring instruments
2. EPPE software “Professional“
- Full range of functions
- Management of up to 5 EPPE measuring instruments
3. EPPE software
“Premium“
- Full range of functions
- Management of an unlimited number of EPPE measuring instruments
EPPE - Power Quality Analysis
EPPE C X – Application Example: EN50160 (Low
Cost)
EPPE - Power Quality Analysis
EPPE C X – Application Example: EN50160
EPPE - Power Quality Analysis
EPPE C X – Application Example: EN50160
EPPE - Power Quality Analysis
EPPE C X – Application Example: PV Plant
EPPE - Power Quality Analysis
EPPE C X – Application Example: Wind Power Plant
EPPE - Power Quality Analysis
EPPE C X – Application Example: Differential Current Measurement