EPPE CX


Add to my manuals
39 Pages

advertisement

EPPE CX | Manualzz

EPPE C

X

POWER QUALITY ANALYSIS

EPPE - Power Quality Analysis

EPPE C X

Various models

Integrated sensor card (PV systems, wind power plants, industrial plants)

Replaceable measurement data memory

(2 GB)

Integrated energy meter

6 current inputs (differential current measurement)

Webserver

Dual processor system

EPPE - Power Quality Analysis

EPPE C X

5" TFT graphical touch screen

Configuration and data download via USB flash drive

Multi-client capability

IEC 61850 protocol

EPPE - Power Quality Analysis

EPPE C X – Analog Inputs

Model 1:

4 current inputs

4 voltage inputs

Monitoring of one voltage system

Direct current measurement up to 40 A permanently

Voltage measurement up to 600 VAC

Accuracy < 0.05%

Sampling rate of 200 kHz

EPPE - Power Quality Analysis

EPPE C X – Analog Inputs

Model 2

8 voltage inputs

- 8 x 600 V

- 4 x 600 V / 4 x 3 V

Monitoring of 2 voltage systems

- Cost optimisation

- Monitoring to EN50160

Connection of current clamps and current sensors

EPPE - Power Quality Analysis

EPPE C X – Sensor Card

Additional sensor card (optional)

High flexibility

Various sensors can be connected

- temperature, light irradiation, wind speed ,…

Control of external machines / plants

Differential current measurement

EPPE - Power Quality Analysis

EPPE C X – Sensor Card

4 analog inputs

Sampling rate 200KHz

Measuring ranges:

- 300 V rms

(voltage measurement, sensors)

- 10 V (sensors)

- 2 V rms

(current clamps / sensors)

- 20 mA (sensors)

4 analog inputs

Sampling rate 100 Hz

Measuring ranges:

- 10 V (sensors)

EPPE - Power Quality Analysis

EPPE C X – Sensor Card

2 direct temperature inputs

Sampling rate: 100Hz

Type: PT 100, 500, 1000

1 analog output

Adjustable process output to control external systems

Selectable output signal:

- 10 V / - 20 mA

EPPE - Power Quality Analysis

EPPE C X – Communication / Power supply

Ethernet (RJ45)

Optical Ethernet (optical fibre)

RS232, RS485

USB passive / active

Data download and configuration via USB flash drive

Connection options for external modems, UMTS router ,…etc.

Communication protocols Modbus,

IEC 61850, etc.

EPPE - Power Quality Analysis

EPPE C X – Communication / Power supply

Replaceable measurement data memory

Power supply units: 85…265 VAC,

90…350 VDC, 9…72 VDC

„Maintenance-free“ internal emergency power supply

EPPE - Power Quality Analysis

EPPE C X – Time synchronisation

Internal real-time clock

NPT/SNTP

DCF 77

IRIG-B

Internal GPS receiver

External GPS central clock

Seconds and minutes pulse

Interlink interface for the synchronisation of EPPE CX devices with each other

EPPE - Power Quality Analysis

EPPE C X – Binary Inputs

 14 Binary inputs

 Statistical evaluations

(recording),

 Logging of states / signals

 Monitoring system

operating times / status of other systems (machines), e.g. how long the ventilator/heating system has been used

EPPE - Power Quality Analysis

EPPE C X – Binary Outputs

 2 Relay outputs / 6 electron. relay outputs

 Monitoring function, status information on the device, e.g. factory master control system

 Messages: new record, system error,…

EPPE - Power Quality Analysis

EPPE C X - Overview

4 x analog input (voltage 600 VAC, 200 kHz, accuracy 0.05%)

4 x analog input (voltage 600 VAC, voltage 3 VAC,

current 40 AAC, 200 kHz, accuracy

0.05%)

14 x binary input (24…300 VDC)

8 x relay output (2 mech. / 6 electron.)

Time synchronisation: GPS, DCF, NTP, PC, IRIG-B, pulse input,

intercommunication interfaces

Power Supply

: 85…265 VAC, 90…350 VDC, 9…72 VDC

Communication: Ethernet, 3 x USB (active/passive),

optical Ethernet (optical fibre) RS232, RS485

Sensor card

4 x analog input (300 V, 10 V, 2 V, 20 mA, 200 kHz)

4 x analog input (10 V, 100 Hz)

2 x temperature input (PT 100, PT 500, PT 1000)

1 x process output (10 V / 20 mA)

EPPE - Power Quality Analysis

EPPE C X - Front

EPPE - Power Quality Analysis

EPPE C X – Display Functions

• Simplified menu navigation

• Displaying up to the 63rd harmonic

• Zoom functions

EPPE - Power Quality Analysis

EPPE C X – Display Functions

• Zoom functions

EPPE - Power Quality Analysis

EPPE C X – Display Functions

• Improved auto-scaling

• Displaying fault records directly on the device

• Date, time, criterion, …

EPPE - Power Quality Analysis

EPPE C X – Standard Models

4 Standard models

Price optimisation

Short delivery time

Standard equipment:

14 binary inputs

8 relay outputs (2 mech. / 6 electron.)

5"-TFT graphical touch screen (640 x 480 pixel)

Membrane keypad with 4 function keys

Data memory: 2 GB flash (replaceable)

Communication interfaces: 1 x RS232, 1 x RS485, 3 x USB, 1 x Ethernet

Time synchronisation: GPS, DCF, NTP, IRIG-B, Interlink interface

EPPE - Power Quality Analysis

EPPE C X – Standard Models

Power quality analyser EPPE CX – IAC

• Analog inputs: 4 x 600 V Ph-N, 4 x 40 A

• Internal power supply unit, voltage range 85-265 VAC / 90-350 VDC

Power quality analyser EPPE CX – IDC

• Analog inputs: 4 x 600 V Ph-N, 4 x 40 A

• Internal power supply unit, voltage range 36-72 VDC

Power quality analyser EPPE CX – UAC

• Analog inputs: 4 x 600 V Ph-N, 4 x 600V Ph-N

• Internal power supply unit, voltage range 85-265 VAC / 90-350 VDC

Power quality analyser EPPE CX

– UDC

• Analog inputs: 4 x 600 V Ph-N, 4 x 600 V

• Internal power supply unit, voltage range 36-72 VDC

EPPE - Power Quality Analysis

EPPE C X – Configureable Model

Power quality analyser EPPE CX – Basic unit

Equipment:

Slot to accommodate one internal power supply unit

Slot to accommodate one analog measuring module

Slot to accommodate one optional sensor measuring module

• 14 binary inputs

• 8 relay outputs (2 mech. / 6 electron.)

• 5"-TFT graphical touch screen (640 x 480 pixel)

• Membrane keypad with 4 function keys

• Data memory: 2 GB flash (replaceable)

• Communication interfaces: 1 x RS232, 1 x RS485, 3 x USB, 1 x Ethernet

Optional: optical Ethernet (optical fibre)

• Time synchronisation: GPS, DCF, NTP, IRIG-B, Interlink interface

Optional: Communication protocols IEC 61850, DNP3.0, Profibus

EPPE - Power Quality Analysis

EPPE Software

Features

All applications in one software package

Configuration of the measuring system

Automatic device and data handling

Evaluation and report creation

Online monitoring

Clearly designed user interface

Intuitive operation

Short familiarisation period

High effectzivity

EPPE - Power Quality Analysis

EPPE Software

Device management

Clear structure

Status reports on the devices

Different installation levels (region, measurement location

,…etc.)

Graphical device overview

Integration of personal maps, cicuit diagrams, etc.)

Device status

Zoom functions

EPPE - Power Quality Analysis

EPPE Software

Device list / Graphical overview Device parameter / status Analysis

EPPE - Power Quality Analysis

EPPE Software

Configuration

 Simple configuration according to specific standards (e.g. EN50160)

 Cyclic measurement

 Averaging interval

 Min./max. values

 Min./max. time

 Events

 Configurable limit values

 Fault recorder

Configurable sampling rate

(up to 30 kHz)

 Configurable pre-fault, fault and postfault period

 Fault records on binary channels

 Energy meter

 Logical links

EPPE - Power Quality Analysis

EPPE Software

Analysis

Trend analysis

Time period adjustable at any time

Numerous graphic analysis tools

Superimposition of signal characteristics

Graphical display of the extreme value duration distribution

Formula editor for mathematical signal characteristics

Automatic generation of PQ reports

Data export for third party systems

(PQDIF, Comtrade, CSV)

Automatic calculation of a differential current measurement

Navigator for a better overview and selection of the time window

EPPE - Power Quality Analysis

EPPE Software

Navigator

EPPE - Power Quality Analysis

EPPE Software

Evaluation

Event analysis

Event analysis with signature display

Event classification

Graphic analysis tools

Navigator for a better overview and selection of the time window

EPPE - Power Quality Analysis

EPPE Software

Evaluation

Limit value overview

Automatic evaluation according to specific standards (e.g. EN50160)

Tabular and graphical overview of limit value violations

Navigator for a better overview and selection of the time window

EPPE - Power Quality Analysis

EPPE Software

Evaluation

Fault record analysis

Graphical display of the fault characteristic

Vector analysis

Harmonic analysis

Superimposition of signal characteristics

Formula editor for mathematical signal analysis

Typification of power system faults

Navigator for a better overview and selection of the time window

Generation of fault reports

Data export for third party systems

EPPE - Power Quality Analysis

EPPE Software

EPPE - Power Quality Analysis

EPPE Software

Software Versions

3 software versions which differ in functionality and in the number of measuring instruments to be managed:

1. EPPE software “Basic“

- Functionality limited to power quality measurements in compliance with valid standards (e.g. to EN50160)

- Management of up to 5 EPPE measuring instruments

2. EPPE software “Professional“

- Full range of functions

- Management of up to 5 EPPE measuring instruments

3. EPPE software

Premium

- Full range of functions

- Management of an unlimited number of EPPE measuring instruments

EPPE - Power Quality Analysis

EPPE C X – Application Example: EN50160 (Low

Cost)

EPPE - Power Quality Analysis

EPPE C X – Application Example: EN50160

EPPE - Power Quality Analysis

EPPE C X – Application Example: EN50160

EPPE - Power Quality Analysis

EPPE C X – Application Example: PV Plant

EPPE - Power Quality Analysis

EPPE C X – Application Example: Wind Power Plant

EPPE - Power Quality Analysis

EPPE C X – Application Example: Differential Current Measurement

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement