advertisement
Multi-Alert
™
& Mini-Alert
™
Sounders and Strobes
Multi-Alert Models
Sounder
MA12/24D
Strobes
SS24LO
SS24M
SS24LOLA
Sounder/Strobes
MASS24LO
MASS24M
MASSLOLA
Mini-Alert Sounders
Red
PA400
Beige
PA400
PA400R-F PA400B-F
White
PA400W
PA400W-F
PA400W
Add-on Strobes
Red
PS24LO
White
PS24LOW
MA12/24D
PA400R-F
Product Overview
Multi-Alert Sounder:
12 and 24V operation
8 field-selectable tones
Multi-Alert Strobes and Sounder/Strobes:
24V operation
1.5 or 15 candela
UL1638 listed
Mini-Alert Sounders:
12 and 24V operation
1.5 cd add-on strobe available
System Sensor's Multi-Alert sounder and sounder/strobes are suited to provide primary or secondary signaling for fire and security applications. The MA and MASS models provide eight field-selectable warning tones.
The Multi-Alert models mount directly to 4 ″ square back boxes. Optional mounting plates are available for either flush or semi-flush installations. Model MA12/24D is suitable for outdoor applications when installed with the WBB weather-proof back box.
Multi-Alert Strobes.
System Sensor’s Multi-Alert strobes are UL1638 compliant electronic visible warning signals that flash approximately every 1.5 seconds. All circuits are polarized to be compatible with DC alarm supervision.
Mini-Alert Sounders.
System Sensor’s PA400 series Mini-Alert sounders operate at 12 and 24 volts and are ideal for hotel, motel or residential fire system applications, where a smaller notification device is desired. The PA400 sounders are available with or without FIRE identification, and are offered in red, beige, and white.
Engineering Specifications
Multi-Alert Sounders shall be a System Sensor Model MA 12/24D capable of operating at 12 and 24VDC. Sounder shall be listed to Underwriter’s Laboratories Standard UL464 for fire protective signaling systems. Sounder shall have an operating temperature between –31°F and 151°F. Sounder shall have eight tone options, selected by means of clips.
Mini-Alert Sounders shall be a System Sensor Model ——— capable of operating at 12 and 24VDC. Sounder shall be listed to Underwriter's Laboratories Standard UL464 for fire protective signaling systems. Sounder shall have an operating temperature between 14°F and 140°F.
Multi-Alert and Mini-Alert Sounder/Strobes shall be a System Model ——— capable of operating at 24VDC. Sounder/strobe shall be listed to Underwriter’s Laboratories Standards UL464 and UL1638 for fire protective signaling systems.
Sounder/strobe shall have an operating temperature between 32°F and 120°F. Strobe shall be powered independently of the sounder and shall operate at 24VDC, with a UL range rating of 22.5 to 30VDC. Actual operating voltage must be between
18 and 33VDC. Strobe shall have a minimum light output of 1.5 or 15 candela and shall be UL1638 listed for private mode applications.
Multi-Alert Sounder Specifications
Dimensions
4
″ x 4″ x 2
1 /
4
″
Weight
5.7 oz. (162 g)
Operating Voltage
12VDC to 24VDC FWR unfiltered*
Mounting
Sur face 4
″ x 4″ back box (1
1 /
2
″ to 2
1 /
8
″ deep)
Flush 4
″ x 4″ BBD deep back box (2 3 /
4
″ deep)
Semi-flush 4
″ x 4″ back box (1
1 /
2
″ to 2
1 /
8
″ deep) with MP-SF mounting plate
Input Terminals
12 to 18 AWG
*Actual 12 V operating voltage cannot be less than 9.6VDC or greater than 18.7VDC.
Actual 24 V operating voltage cannot be less than 18VDC or greater than 33VDC.
Multi-Alert Strobe Specifications
Dimensions
4
″ x 4″ x 2
15 /
16
″
Mounting
Sur face 4
″ x 4″ back box (1
1 /
2
″ to 2
1 /
8
″ deep)
Semi-flush 4
″ x 4″ back box (1
1 /
2
″ to 2
1 /
8
″ deep) with MP-SF mounting plate
Weight
8.2 oz. (232 g)
Operating Voltage
24VDC and FWR unfiltered*
Input Terminals
12 to 18 AWG
*Actual 24V operating voltage cannot be less than 18VDC or greater than 33VDC.
Mini-Alert Specifications
Dimensions
4 1 /
2
″ x 2 3 /
4
″x 1 1 /
8
″
Mounting
Sur face Single gang back box
Flush 4
″ x 4″ BBD deep back box (2 3 /
4
″deep)
Weight
2.4 oz. (159 g)
Input Terminals
12 to 18 AWG
Operating Voltage
12VDC to 24VDC FWR unfiltered*
*Actual 12V operating voltage cannot be less than 9.6VDC or greater than 18.7VDC.
Actual 24V operating voltage cannot be less than 18VDC or greater than 33VDC.
Operating Temperature Range
–32° to 151°F (–35° to 66°C)
Operating Temperature Range
–31° to 151°F (–35° to 66°C)
Operating Temperature Range
14° to 140°F (–10° to 60°C)
Ordering Information/Current Draw
Multi-Alert/Mini-Alert Model Numbers
Beige Red
MA12/24D
SS24LO
SS24M
SS24LOLA
MASS24LO
MASS24M
MASS24LOLA
PA400R
PA400R-F
PS24LO
PA400B
PA400B-F
White Description
Multi-Aler t sounder
Multi-Aler t strobe
Multi-Aler t strobe
Voltage
12/24VDC
24VDC
24VDC
Multi-Aler t strobe (“FUEGO” lens)
Multi-Aler t sounder /strobe
24VDC
24VDC
Multi-Aler t sounder /strobe 24VDC
Multi-Aler t sounder/strobe (“FUEGO” lens) 24VDC
PA400W Mini-Aler t sounder
PA400W-F Mini-Aler t sounder (“Fire” identification)
PS24LOW Add-on strobe
12/24VDC
12/24VDC
12/24VDC
Accessory Model Numbers
Description
MP-F/MP-FB
MP-SF/MP-SFB
BB-D
WBB
Flush mounting plate (red/beige)
Semi-flush mounting plate (red/beige)
Flush mounting deep back box, 2 3 /
4
″ deep
Weatherproof back box for MA 12/24D
* Current ranges from 10mA to 55mA depending upon voltage and sound selected
** Current ranges from 35mA to 80mA depending upon voltage and sound selected
*** Sound output varies depending upon voltage and sound selected.
Note: LO and M style strobe and sounder/strobe models are not MEA approved.
System Sensor Sales and Service
System Sensor Headquarters
3825 Ohio Avenue
St. Charles, IL 60174
Ph: 800-SENSOR2
Fx: 630/377-6495
Documents on Demand
1-800-736-7672 x3 www.systemsensor.com
System Sensor Canada
Ph: 905.812.0767
Fx: 905.812.0771
System Sensor Europe
Ph: 011.44.1403.276500
Fx: 011.44.1403.276501
System Sensor in China
Ph: 011.86.29.524.6253
Fx: 011.86.29.524.6259
System Sensor in Singapore
Ph: 011.65.273.2230
Fx: 011.65.273.2610
Average
Current
*
25 mA
75 mA
25 mA
**
**
**
12/15 mA
12/15 mA
5 mA
System Sensor– Far East
Ph: 011.85.22.191.9003
Fx: 011.85.22.736.6580
System Sensor– Australia
Ph: 011.613.54.281.142
Fx: 011.613.54.281.172
1.5
—
—
1.5
dB Output
Candela (UL)***
—
1.5
75–85
—
15.0
1.5
1.5
15.0
—
—
75–85
75–85
75–85
82
82
82
© 1999 System Sensor. The company reser ves the right to change product specifications without notice.