Altronix AL600ULB Installation instructions

Add to My manuals
2 Pages

advertisement

Altronix AL600ULB Installation instructions | Manualzz

AL600ULB - UL Recognized

Power Supply/Charger

Rev. 100302

Overview:

The AL600ULB is a power supply that converts a 28VAC / 200VA input, to a 12VDC or a 24VDC output,

(see specifications).

Specifications:

Agency Listings:

• UL Recognized component for Access Control

System Units (UL 294), Standard for Safety for Fire Protective Signaling Systems (UL 1481).

Input:

• Input 28VAC / 200VA.

Output:

• 12VDC or 24VDC selectable output.

• 6 amp continuous supply current

@ 12VDC or 24VDC.

• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.

• Maximum charge current 0.7 amp.

Battery Backup (continued):

• Automatic switch over to stand-by battery when AC fails.

• Zero voltage drop when switched over to battery backup.

Visual Indicators:

• AC input and DC output LED indicators.

Supervision:

• AC fail supervision (form "C" contacts).

• Low battery and battery presence supervision

(form "C" contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (approximate):

4.3”W x 7.1”L x 2.3”H

Power Supply Output Selection:

Output VDC

12VDC

24VDC

Switch Position

SW1 CLOSED

SW1 OPEN

Stand-by Specifications:

Output

12VDC / 40 AH Battery

4 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 6 amp

Alarm = 6 amp

24VDC / 12 AH Battery

24 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 1.0 amp

Alarm = 6 amp

Stand-by = 200mA

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6 amp

60 hr. of Stand-by &

5 Minutes of Alarm

Stand-by = 300mA

Alarm = 6 amp

24VDC / 40 AH Battery Stand-by = 6 amp

Alarm = 6 amp

Stand-by = 300mA

Alarm = 6 amp

Installation Instructions:

The AL600ULB should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes.

1. Mount the AL600ULB in location/enclosure.

2. Set the AL600ULB to the desired DC output voltage by setting SW1 to the appropriate position

(refer to Power Supply Output Selection chart).

3. Connect two (2) 28VAC / 200VA transformers (connected in parallel) to terminals marked [AC]. Use 14 AWG or larger for all power connections (Battery, DC output, AC input).

Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).

Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires).

Minimum .25” spacing must be provided.

4. Measure output voltage before connecting device. This helps avoid potential damage.

5. Connect devices to be powered to terminals marked [+ DC –] (Fig. 1).

When servicing the unit, AC mains should be removed.

6. For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

Connect battery to terminals marked [+ BAT –] (Fig. 1).

7. Connect appropriate signaling notification devices to [AC FAIL & BAT FAIL] (Fig. 1) supervisory relay outputs. Note: When used in fire alarm, burglar alarm or access control applications,

“AC Fail” relay must be used to provide a visual indication of AC power on.

RL2

RL3

IC2

OPEN = 24V SW1 CLOSED = 12V

IC3

Maintenance:

Unit should be tested at least once a year for the proper operation as follows: PTC2

RLY1

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level

DC

AC

+ DC --+ BAT ---

(refer to Power Supply Voltage Output Specification chart).

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage

AC both at battery terminal and at the board terminals marked [+ BAT –] to insure there is no break in the battery connection wires.

Note: Maximum charging current under discharge is 0.7 amp.

AC

Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.

Fig. 1

LED Diagnostics:

Red (DC)

ON

ON

OFF

OFF

Green (AC)

ON

OFF

ON

OFF

Power Supply Status

Normal operating condition.

Loss of AC, Stand-by battery supplying power.

No DC output.

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Legend

AC/AC

+ DC –

AC FAIL

NC, C, NO

BAT FAIL

NC, C, NO

+ BAT –

Function/Description

Connect 28VAC to these terminals from 2 connected in parallel transformers.

12VDC or 24VDC @ 6 amp continuous non-power limited output.

Used to notify loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally energized when AC power is present.

Contact rating 1 amp @ 30VDC. AC Fail condition will report approximately one (1) to one minute after loss of AC. To delay report for 6 hours cut jumper J1 on the

Power Supply Board (AC trouble output delay option). If this mode is selected the Power

Supply Board must be reset by removing all power to it for 30 seconds.

Used to indicate low battery condition, e.g. connect to alarm panel.

Relay normally energized when DC power is present.

Contact rating 1 amp @ 30VDC. Low battery conditions will report approximately 21VDC

(24VDC output setting) or approximately 10.5VDC (12VDC output setting). Battery presence detection will report approximately 1 minute after battery remains undetected

(missing or removed).

Stand-by battery connections. Maximum charge current 1.2 amp.

Altronix is not responsible for any typographical errors.

Altronix Corp.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.

IIAL600ULB G27J

MEMBER

advertisement

Related manuals

Download PDF

advertisement