advertisement
Installation and Operation Instructions
Georgian™ Wood Burning Fireplace
P/N 126637-01 Rev. G 07/2017
Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 126637-02.
C
PFS
®
US
REPORT NO. F09-095
P126637-01
Models
Georgian 36 Georgian 42 Georgian 50
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Installateur : Laissez cette notice avec l’appareil.
Consommateur : Conservez cette notice pour consultation ultérieure.
This wood burning fireplace complies with UL127
CAN/ULC-S610-M87 standard as a FACTORY
BUILT FIREPLACE.
Ce foyer au bois est conforme aux UL 127 CAN/ULC-
S610-M87 norme comme une USINE CONSTRUITE
CHEMINÉE.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to
ANSI Z21.60 or Z21.84 standards or for use with a vent-free gas log heater approved to ANSI Z21.11.2 standard
.
FOR CANADA: The authority having jurisdiction
(such as the municipal building department, fire department, etc.) should be contacted before installation to determine the need to obtain a permit.
POUR LE CANADA: L’autorité compétente (comme le service municipal du bâtiment, les pompiers, etc.) doit
être contacté avant l’installation afin de déterminer la nécessité d’obtenir un permis.
This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation.
Do not alter or modify the fireplace or its components under any circumstances. Any modification or alteration of the fireplace system, including but not limited to the fireplace, chimney components and accessories, may void the warranty, listings and approvals of this system and could result in an unsafe and potentially dangerous installation.
IMPORTANT! TO ASSURE PROPER ALIGNMENT OF GLASS DOORS: INSTALL THIS FIREPLACE IN A SQUARE
AND PLUMB CONDITION, USING SHIMS AS NECESSARY AT SIDES AND/OR BOTTOM.
NOTE: DIAGRAMS AND ILLUSTRATIONS THROUGHOUT THE MANUAL ARE NOT TO SCALE.
Thank you for your purchase. We appreciate your business!
Please carefully read and follow all instructions in this manual. Pay
special attention to all warnings and safety information.
Following these safety, care, and operation instructions will help ensure many years of dependable and enjoyable service from your fireplace.
Please read and understand these instructions before installing or operating.
TABLE OF CONTENTS
Safety .............................................................................................2
Specifications .................................................................................4
Fireplace Installation ......................................................................7
Venting Installation ........................................................................9
Mosaic Brick Panel and Estate Refractory Panel Installation........16
Optional Gas Line Installation ......................................................18
Glass Door Installation .................................................................19
Operation and Maintenance Guidelines ........................................20
Technical Service .........................................................................21
Replacement Parts .......................................................................21
Parts ............................................................................................22
Accessories ..................................................................................26
Important Notices Canada ...........................................................28
Draft Smoke Guidelines - Appendix A .........................................29
Warranty ......................................................................................31
SAFETY
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
IMPORTANT: Check local codes before installing this fireplace.
Before beginning the installation of the fireplace, read these instructions through completely.
• This INNOVATIVE HEARTH PRODUCTS, LLC (IHP) fireplace and its components are safe when installed according to this installation manual. Unless you use IHP components, which have been designed and tested for the fireplace system, you may cause a fire hazard.
• The IHP warranty will be voided by and IHP disclaims any responsibility for the following actions.
a. Modification of the fireplace, components, doors, air inlet system and damper control.
b. Use of any component part not manufactured or approved by
IHP in combination with an IHP fireplace system.
Proper installation is the most important step in ensuring safe and continuous operation of the fireplace. Consult the local building codes as to the particular requirements concerned with the installation of all factory built fireplaces.
WARNING: Do not install a fireplace insert in this box unless the manufacturer's instructions with the insert specifically state this fireplace has been tested for use with this insert.
FOR YOUR SAFETY
• Do not store or use gasoline or any other flammable vapors or liquids in the vicinity of this or any other appliance.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
• Do not place clothing or other flammable materials on or near the appliance.
• Never leave children unattended when a fire is burning in the fireplace.
WARNING: Use solid wood or processed solid fuel firelogs only. When processed wood fuel fire logs are used, do not poke or stir the logs while they are burning.
Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use.
This fireplace is not intended to be used as a substitute for a furnace to heat an entire home. Use for supplemental heat only.
2 Astria.us.com
126637-01_G
SAFETY Continued
Overfiring of a fireplace is a condition where excessive temperatures are reached, beyond the design capabilities of the appliance. The damage that occurs from overfiring is not covered under the manufacturer’s limited warranty.
WARNING: CONTINUED OVERFIRING CAN PER-
MANENTLY DAMAGE YOUR FIREPLACE SYSTEM.
SOME EXAMPLES OF CONDITIONS THAT COULD
CAUSE OVERFIRING ARE:
• BURNING QUANTITIES OF SCRAP LUMBER, PINE BRANCH-
ES, PAPER OR CARDBOARD BOXES WHICH EXCEED THE
VOLUME OF THE NORMAL LOG FIRE.
• BURNING TRASH, CHEMICALS OR CHEMICALLY TREATED
COMBUSTIBLES.
WARNING: BURNING IMPROPER FUEL (I.E. CHAR-
COAL) CAN RESULT IN CARBON MONOXIDE POISON-
ING, WHICH MAY LEAD TO DEATH!
Carbon Monoxide Poisoning – Early signs of carbon monoxide poisoning resemble the flu with headaches, dizziness, or nausea. If you have these signs, get fresh air at once! Have the appliance inspected by a qualified service technician. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Ventilation Requirements - Provide adequate air for combustion. The fresh air requirements of this appliance must be met within the space where it will be installed.
Disposal of Ashes
Ashes should be placed in a metal container with a tightfitting lid. The closed container of ashes should be placed on a noncombustible floor or on the ground, well away from all combustible materials, pending final disposal.
If the ashes are disposed of by burial in soil or otherwise locally dispersed, they should be retained in the closed container until all cinders have thoroughly cooled.
WHEN USING THE DECORATIVE APPLIANCE, THE
FIREPLACE DAMPER MUST BE SET IN THE FULLY
OPEN POSITION.
Smoke Detectors - Since there are always several potential sources of fire in any home, we recommend installing smoke detectors. If possible, install the smoke detector in a hallway adjacent to the room (to reduce the possibility of occasional false activation from the heat produced by the appliance). If your local code requires a smoke detector be installed within the same room, you must follow the requirements of your local code. Check with your local building department for requirements in your area.
Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or ’freshen up’ a fire in this fireplace. Keep all such liquids well away from the fireplace while it is in use.
Use SOLID WOOD only for fuel. It is best to use dry and well seasoned hardwood. Softwoods tend to burn very quickly. DO NOT use treated wood, charcoal, coal, trash, driftwood or woods that have been dipped in tar, pitch, pine tar, creosote, etc. Wood products made with synthetic binders, such as plywood, produce abnormally high temperatures and sputtering, smoking fires. When burning artificial logs, please read and follow the instructions provided by the manufacturer.
Creosote – Formation and Need for Removal
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled moisture to form creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning fire. As a result, creosote residue accumulates on the flue lining. When ignited this creosote makes an extremely hot fire.
The chimney shall be inspected at least twice a year during the heating season to determine when a creosote buildup has occurred. When creosote has accumulated
(1/8" [3 mm] or more) it shall be removed to reduce the risk of a chimney fire.
Never burn treated construction lumber or scraps.
These woods burn excessively hot and may contain chemicals used to treat insects and fungus. When burned, these chemicals can pose a significant hazard.
126637-01_G
WARNING: Children and adults should be alerted to the hazards of high surface temperatures and to stay away to avoid burns or clothing ignition. Young children should be carefully supervised when in the same room as fireplace.
Astria.us.com
3
36" MODEL
SPECIFICATIONS
29
" (737 mm)
22-
1
/
2
" (572 mm)
14-
1
/
2
"
(369 mm)
26-
5
/
8
"
(677 mm)
15-
5
/
8
"
(397 mm)
4-
1
/
2
" (115 mm)
22-
1
/
2
"
(572 mm)
35-
1
/
4
" (896 mm)
36" HEARTH
19 "
(483 mm)
20-
1
/
4
(Ref.)
"
(515 mm)
1-
1
/
4
" (32 mm)
4
67
"
(1702 mm)
11 "
(280 mm)
61 "
(1550 mm)
49
"
(1245 mm)
30 "
(762 mm)
7 "
1
" (26 mm)
58 "
(1474 mm)
OUTSIDE AIR
ACCESS
GAS LINE
ACCESS
36
" (915 mm)
45-
1
/
8
" (1159 mm)
1 "
(26 mm)
4-
1
/
2
10-
1
/
2
"
(267 mm)
9-
1
/
2
"
(242 mm)
" (115 mm)
3-
1
/
2
"
(89 mm)
7-
1
/
4
"
(185 mm)
11 "
(280 mm)
15-
1
/
4
"
(388 mm)
Figure 1 - 36" Model Georgian 36
Astria.us.com
126637-01_G
42" MODEL
SPECIFICATIONS Continued
5
/
8
" (16 mm)
30-
1
/
2
" (775 mm)
22-
3
/
4
" (578 mm)
15-
3
/
4
"
(400 mm)
29 "
(737 mm)
17-
5
/
8
"
(448 mm)
4-
3
/
8
" (112 mm)
26-
3
/
8
"
(670 mm)
41-
3
/
8
" (1051 mm)
42" HEARTH
21-
3
/
4
"
(553 mm)
23
"
(585 mm)
(Ref.)
1-
1
/
4
" (32 mm)
126637-01_G
67
"
(1702 mm)
11 "
(280 mm)
61
"
(1550 mm)
49 "
(1245 mm)
30
"
(762 mm)
7
"
(178 mm)
1
" (26 mm)
58
"
(1474 mm)
OUTSIDE AIR
ACCESS
GAS LINE
ACCESS
42 " (1067 mm)
51-
1
/
8
" (1299 mm)
1
"
(26 mm)
4-
1
/
2
10-
1
/
2
"
(267 mm)
9-
1
/
2
"
(242 mm)
" (115 mm)
3-
1
/
2
"
(89 mm)
8-
1
/
2
"
(216 mm)
13 "
(331 mm)
17
"
(432 mm)
Figure 2 - 42" Model Georgian 42
Astria.us.com
5
50" MODEL
SPECIFICATIONS Continued
6
38-
1
/
2
" (978 mm)
24
" (610 mm)
19-
1
/
4
"
(489 mm)
28-
1
/
2
"
(724 mm)
17-
5
/
8
"
(448 mm)
4-
3
/
8
"
(112 mm)
34-
3
/
8
"
(874 mm)
493 /
8
"
(1255 mm)
50" HEARTH
21-
3
/
4
"
(553 mm)
23
"
(585 mm)
(Ref.)
11 /
4
"
(32 mm)
67
"
(1702 mm)
61 "
(1550 mm)
58
"
(1474 mm)
49 "
(1245 mm)
11
"
(280 mm)
30 "
(762 mm)
7 "
(178 mm)
1
"
(26 mm)
OUTSIDE
AIR
ACCESS
GAS LINE
ACCESS
50
" (1270 mm)
59-
1
/
4
" (1505 mm)
10-
1
/
2
"
(267 mm)
9-
1
/
2
"
(242 mm)
4-
1
/
2
"
(115 mm)
3-
1
/
2
"
(89 mm)
8-
1
/
2
"
(216 mm)
13
"
(331 mm)
17 "
(432 mm)
Figure 3 - 50" Model Georgian 50
Astria.us.com
126637-01_G
FIREPLACE INSTALLATION
SELECTING LOCATION
To determine the safest and most efficient location for the fireplace, you must take into consideration the following guidelines:
1. The location must allow for proper clearances (see Figures 4 and
5).
2. Consider a location where fireplace will not be affected by drafts, air conditioning ducts, windows or doors.
3. A location that avoids cutting of joists or roof rafters will make installation easier.
4. An outside air kit is available with this fireplace (see Optional
Outside Air Kit on page 9).
MINIMUM CLEARANCE TO COMBUSTIBLES
Back and sides of fireplace 1
1
/
2
" min.
Ceiling 42" min.
Front of fireplace 48" min.
Floor** 0" min.
Perpendicular wall to opening 18" min.
36" Models 12" min.
Top spacers 0" min.
Mantel clearances see Mantels, page 8
Chimney outer pipe surface 2" min.
36" Model 1" min.
* Not required at nailing flanges
** See step 2 of Framing
6. Using screws or nails, secure fireplace to framing through flanges located on sides of fireplace.
455 /
8
" (1159 mm)
51-
5
/
8
" (1312 mm)
59-
3
/
4
" (1518 mm)
58-
1
/
8
"
(1477 mm)
67-
1
/
8
"
(1705 mm)
(36" Models)
(42" Models)
(50" Models)
Figure 4 - Framing Dimensions
30-
1
/
8
"
(766 mm)
28-
1
/
4
" (718 mm)
(36" Models)
WARNING: Do not pack required air spaces with insulation or other materials.
61
" (1550 mm) - (36" Models)
65 " (1651 mm) - (42" Models)
71
" (1804 mm) - (50" Models)
Minimum/Maximum Chimney Height for Residential Installation
Minimum height of chimney, measured from base of fireplace to flue gas outlet of termination, is 16 feet for straight flue or a flue with one elbow set. Maximum distance between elbows is 6 feet. For systems with two elbow sets, minimum height is 22 feet. Maximum height of any system is 50 feet. This measurement includes fireplace, chimney sections and height of termination assembly at level of the flue gas outlet (see Figure 15, page 12).
FRAMING
1. Frame opening for fireplace using dimensions shown in Figures 4 and 5.
2. If fireplace is to be installed directly on carpeting, tile or any combustible material other than wood flooring, fireplace must be installed upon a metal or wood panel extending full width and depth of fireplace.
3. Set fireplace directly in front of this opening and slide unit back until nailing flanges touch side framing.
4. Check level of the fireplace and shim with sheet metal if necessary.
5. Before securing fireplace to prepared framing, ember protector
(provided) must be placed between hearth extension (not supplied) and under bottom front edge of fireplace to protect against glowing embers falling through. If fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your required platform height. Ember protector should extend under fireplace a minimum of 1
1
/
2 prevent corrosion.
". Ember protector should be made of galvanized sheet metal (28 gauge minimum to
861 /
2
" (2198 mm) - (36" Models)
92
" (2337 mm) - (42" Models)
100 " (2540 mm) - (50" Models)
Figure 5 - Corner Installation
Maintain
1-
1
/
2
" (39 mm)
Clearance at
Sides and Back of Fireplace
1-
1
/
2
" (39 mm)
Clearance
Not Required at
Nailing Flanges
126637-01_G Astria.us.com
7
WARNING: Hearth extension is to be installed only as shown in Figure 6.
FIREPLACE INSTALLATION Continued
HEARTH EXTENSION
A hearth extension projecting a minimum of 20" in front of and a minimum of 12" beyond each side of fireplace opening is required to protect combustible floor construction in front of fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer of noncombustible, inorganic material having a thermal conductivity of k=0.84 BTU IN/FT, HR. F (or less) at 1" thick.
For example, if the material selected has a k factor of 0.25, such as glass fiber, the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "k" of materials can be obtained from manufacturer or supplier of noncombustible material. If hearth extension is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal, glass, marble, stone, etc. Provide a means to prevent hearth extension from shifting and seal gap between fireplace frame and hearth extension with a noncombustible material (see Figure 6).
MANTELS
A mantel may be installed if desired (see Figure 7). Woodwork such as wood trims, mantels or any other combustible material projecting from front face must not be placed within 12" (36" Models) or 18" (42/50" Models) of fireplace opening. Combustible materials above 12" (36" Models) or 18" (42/50" Models) and projecting more than 1
1
/
2
" from fireplace must not be placed less than 15" (36" Models) or 21" (42/50" Models) from the top opening of the fireplace (NFPA STD 211, Sec. 7-3.3.3).
Mantels or any other combustible material also may come up to side edge of black metal face of fireplace as long as projections from front face fall within limit shown in Figure 7.
6" (153 mm)
Ref.
12
1
/
4
"
(312 mm) Ref.
33°
Combustible
Material
Safe Zone for
Projection of
Combustible
Materials
Fireplace Front
Ember Protector
Fireplace Front Raised
Hearth
Ember Protector
Seal Gap
Hearth
Extension
15" (381 mm) Min.
(36" Models)
21" (534 mm) Min.
(42/50" Models)
3" (77 mm)
1
Nom.
1
/
2
" (39 mm)
Max.
12" (305 mm) Min.
(36" Models)
18" (458 mm) Min.
(42/50" Models)
Fireplace Opening
Upper Section of Fireplace
Fireplace Front Elevated
Seal Gap
Ember Protector
Top View of Fireplace
7
3
/
4
" (197 mm)
36" Models
11
1
/
2
" (293 mm)
(42/50" Models)
FIREBOX
Figure 6 - Hearth Extension
33°
SAFE ZONE
Min. to
Perpendicular
Side Wall
12" (305 mm)
36" Models
18" (458 mm)
42/50" Models
3" (77 mm) Max.
4
1
/
2
" (115 mm)
Combustible
Material Must
Not Overlap
Front Face
Figure 7 - Mantel Clearances to Combustible Material
8 Astria.us.com
126637-01_G
OPTIONAL OUTSIDE AIR KIT (MODEL AK4/AK4F)
The installation of an outside air kit should be performed during the rough framing of the fireplace due to the nature of it's location.
Outside combustion air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4).
terminate in attic space.
VENTING INSTALLATION
CAUTION: Combustion air inlet ducts shall not
The maximum height for the air vent can not exceed
3 feet below the flue gas outlet of the termination.
Vented
Crawl Space
(Check Local
Codes Before
Installing in a
Vented Crawl
Space)
Secure to Collars with Metal Tape, Screws or Straps (Min. of 1/4" x 20" in size)
Air Inlet
Location
Must Allow
For Bushes or Snow
Vent Hood
Required for Wall
Installation
Air Inlet
Eyebrow
PART NO.
Signature
12-12DM
12-12HT
18-12DM
18-12HT
24-12DM
24-12HT
36-12DM
36-12HT
48-12DM
48-12HT
RLT-12D
RLT-12HT
LINEAL GAIN
DESCRIPTION
Fireplace
Pipe Section
Pipe Section
Pipe Section
Pipe Section
Pipe Section
66
10
16
23
34
46
1
5
5
5
5
5
/
/
/
/
/
/
2
8
8
8
8
8
GAIN
" (1690 mm)
" (270 mm)
" (423 mm)
" (600 mm)
" (880 mm)
" (1185 mm)
STL-12D
Round Termination
Square Chase-
Top with Slip
Section
7
3
/
4
"* (197 mm)
7" (178 mm) to
15"* (381 mm)
* The lineal gain for the terminations is measured to the flue gas outlet height.
15" Galvanized
Outer Pipe
12
3
/
8
" Stainless
Inner Pipe
Hemmed
End
Figure 8 - Outside Air Kit
CHIMNEY PIPE
Figure 9 - Lineal Gain
WARNING: Label part number 900599-01 must be applied by the installer to all chimney pipe sections but is not required on sections that will be visible after the installation is complete. Label must wrap around the circumference of the pipe.
See accessories, page 25 for Kit F2659.
The IHP chimney system consists of 12", 18", 24", 36" and 48" snaplock, double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) and are given in the lineal gain chart (see Figure 9). Lineal Gain is the actual measurable length of a part after two or more parts are connected.
For Canada, use chimney parts designated "HT".
WARNING: The opening in the collar around the chimney at the top of the fireplace must not be obstructed. Never use blown insulation to fill the chimney enclosure.
ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY
SYSTEM
Each double wall chimney section consists of a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. The pipe sections must be assembled independently as the chimney is installed. When connecting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over 5 the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked together.
When installing double wall snap-lock chimney together, it is important to assure the joint between the chimney sections is locked. Check by pulling chimney upward after locking. The chimney will not come apart if properly locked. It is not necessary to add screws to keep the chimney together (exception, see Figure 10, page 10).
The height of a vertical chimney pipe supported ONLY by the fireplace, must not exceed 20 feet. Chimney heights above 20 feet must be supported.
126637-01_G Astria.us.com
9
10
VENTING INSTALLATION Continued
41
1
/
45"
46
3
/
51"
53
1
/
56
1
/
59
1
/
18"
21
1
/
23
3
/
27
3
/
30"
33"
36"
38
1
/
OFFSET RISE
A
CHIMNEY LENGTH
B 12" 18" 24" 36" 48"
4
9
12
3
3
/
/
3
15"
/
8
4
4
" 16
3
/
" 25
1
/
" 30
3
/
34
3
/
8
4
"
4
"
"
2
" 1
ELBOW SET ONLY
1
1
4
4
4
40"
" 46
1
/
4
" 49
1
/
4
" 56
3
/
60
3
/
66"
4
71"
" 75"
"
" 80
86
89
1
3
1
/
/
/
4
97"
" 101"
4
" 106
1
/
4
" 111
1
/
4
4
4
4
"
"
"
"
1
1
4
" 1
2
"
1
1
1
1
4
" 1 1
4
"
2
" 1
1
1
1
1
1
1
2
1
1 1
2
1
1
61
3
/
64
3
/
68
1
/
70"
74
1
/
4
4
" 115
1
/
4
" 120
3
/
2
"
4
" 1 1
4
" 127" 1
130" 1
" 137
1
/
2
"
2
1 1
2
2
2 1
2
2 1
2 1
4
OFFSET CHART (22-50 FT. SYSTEM HEIGHT)
USING ELBOW OFFSETS (30E-12DM)
1. To achieve desired offset, you may install combinations of 12",
18", 24", 36" and 48" length of double wall pipe (see offset chart and Figure 10).
2. Chimney weight above offset rests on return elbow. Straps must be securely nailed to rafters or joists (see Figure 11, details A and
B).
3. Maximum length of pipe between supports (return elbow or
12S-12DM) is 6' of angle run. Maximum of two 6' angle run sections per chimney system (see Figure 12, page 11).
4. All pipe connections between the offset and return must be secured with two screws on the outer pipe only (see Figure
10). Do not penetrate the inner stainless.
Straps
Straps
Detail B
Angle Firestop
See Detail A
2" (51 mm)
Min.
See Detail B
Screws
B
Straps
Straps
Detail A
Return Elbow
Figure 11 - Ceiling Support Pipe 12S-12DM
CAUTION: THE STRUCTURAL INTEGRITY OF THE
MANUFACTURED HOME FLOOR, WALL, AND CEILING/
ROOF MUST BE MAINTAINED.
WARNING: DO NOT INSTALL IN SLEEPING ROOM
OF MOBILE HOMES.
A
Figure 10 - Elbow Offset
Astria.us.com
126637-01_G
Offset
Elbow
Return
Elbow
Offset
Elbow
VENTING INSTALLATION Continued
Return
Elbow
Return
Elbow
Offset
Elbow
6' (1.88 m)
Max.
Return
Elbow
6' (1.88 m)
Max.
Ceiling
Support Pipe
12S-12DM
Return
Elbow
6' (1.88 m)
Max.
6' (1.88 m)
Max.
Offset
Elbow
6' (1.88 m)
Max.
Offset
Elbow
6' (1.88 m)
Max.
A B C
Figure 12 - Typical Offset Terminations
FIRESTOP SPACERS (FS-10, 1100EFS-10DM FOR 36" MODELS)
Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in Figure 13.
They also provide complete separation from one floor space to another or attic space as required by most codes. When the double wall pipe passes through a framed opening into an attic space, the firestop must be placed into an attic floor as shown in Figure 14.
IMPORTANT NOTICE
When penetrating a ceiling into an attic, a firestop thimble (FST10) is required to avoid intrusion by insulation and recommended to negotiate a joist.
Firestop Thimble FST10
Existing Ceiling
Frame
Firestop Spacer
Firestop
Spacer
Screws or Staples
(Min. of 8)
Existing
Ceiling Frame
Figure 14a - Firestop Thimble
Screws or Staples
(Min. of 8)
Figure 13 - Firestop Spacer with Living Space Above Ceiling
Figure 14 - Firestop Spacer with Attic Space Above Ceiling
126637-01_G
PENETRATING ROOF
To maintain a 1" (36" Models) or 2" (42/50" Models) clearance to the pipe on a roof with a pitch, a rectangular opening must be cut.
1. Determine center point through which pipe will penetrate roof.
2. Determine center point of roof. Pitch is distance the roof drops over a given span, usually 12". A 6/12 pitch means that roof drops
6" for each 12" measured horizontally down from roof rafters.
3. Use roof opening chart (Figure 15, page 12) to determine correct opening length and flashing required.
4. Remove shingles around opening measured. Cut out this section.
5. Add next sections of pipe until end penetrates roof line. Check to see that proper clearances are maintained. Extend chimney by adding sections of double wall pipe until pipe is minimum of 30" above highest point of roof cutout. Termination and chimney must extend a minimum of 36" above highest point where it passes through roof.
Astria.us.com
11
12
17 "
(432 mm)
Min.
1
" (26 mm)
Min
1
" (26 mm)
Min
VENTING INSTALLATION Continued
30 " (762 mm)
Min.
1 " (26 mm)
Min
Opening "A"
FLASHING INSTALLATION (V6F-10DM OR V12F-10DM)
Determine the flashing to be used with the roof opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing base. Secure in position by nailing through shingles (see Figure 16). DO NOT NAIL
THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof, it is required that putty tape be used between the flashing and the roof. The flashing must be secured to the roof using #8 x 3/4" screws and then sealed with roof coating to prevent leakage through the screw holes. A roof coating must also be applied around the perimeter of the flashing to provide a proper seal.
Pitch
Flat
0-6/12
Slope Opening "A"
Max.
0°
26.6°
17" (432 mm)
19" (483 mm)
Used Flashing
Model No.
V6F-10DM
V6F-10DM
6/12-12/12 45.0° 24" (610 mm) V12F-10DM
Roof Opening 36" Models
Storm Collar
Flashing
Cone
Nail Only Outer
Perimeter of Flashing
Overlap Shingles
Top and Sides Only
191 /
2
"
(496 mm)
2 " (51 mm)
Min
30
" (762 mm)
Min.
2
" (51 mm)
Min
2
" (51 mm)
Min
Underlap Shingles at Bottom
Figure 16 - Flashing Installation
Opening
"A"
Storm Collar Installation (SC2-1)
Place storm collar over pipe and slide down until it is snug against the open edge of the flashing (see Figure 17). Apply waterproof caulk around the perimeter of the collar to provide a proper seal.
Pitch Slope Opening "A"
Max.
1
/
2
" (496 mm)
Used Flashing
Model No.
Flat 0° 19V6F-10DM
0-6/12 26.6° 22" (559 mm) V6F-10DM
6/12-12/12 45.0° 27" (432 mm) V12F-10DM
Roof Opening 42" and 50" Models
Figure 15 - Roof Opening Measurements
Chimney Pipe
Storm Collar
Waterproof Caulk
Flashing
Astria.us.com
Figure 17 - Storm Collar
126637-01_G
VENTING INSTALLATION Continued
Terminations/Spark Arrestor
The fireplace system must be terminated with the listed round top or chase terminations. In any case, refer to the installation instructions supplied with the termination.
10 FOOT RULE
All flue gas outlet chimney terminations must extend a minimum of
3 feet in height above the highest point where it passes through the roof and must be at least 2 feet above the highest point of the roof that is within a horizontal distance of 10 feet (see Figure 20).
CAUTION: Do not seal openings on the rooftop flashing. Follow the installation instructions provided with the termination being used.
10 '
(3.05 m)
Level of Flue
Gas Outlet
Stainless
Inner Flue
Pipe
RLT-12D
Level of Flue
Gas Outlet
2 ' (0.61 m) Min.
3 '
(0.91 m)
Min
10 '
(3.05 m)
Secure
Termination to
Outer Pipe with
3 Screws
Waterproof
Caulking
2
' (0.61 m)
Min.
3 '
(0.91 m)
Min
Storm Collar
Figure 20 - 10 Foot Rule
Flashing
Overlap Shingles
(Top and Sides of
Flashing Base)
Figure 18 - Termination
Underlap
Shingles
CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24", center to center and stacked at a vertical height difference of 18" (see Figure 19).
Note: If a decorative shroud is to be installed, contact the manufacturer for specifications.
SQUARE TOP TERMINATIONS INSTALLATION STL-12D AND
STL-12DMP
1. Construct chase as illustrated in Figure 21. Note: The shortest vertical side must be at least 30" high and minimum inside dimension must be at least 19" as shown in Figure 21.
2. Add pipe sections to chimney system as outlined in fireplace installation instructions until last piece of chimney is a maximum of 6" below top of chase (see Figure 21).
30"
(762 mm)
Min.
19"
(483 mm)
6" (153 mm) Max.
18" (458 mm)
Min. Typ.
24" (610 mm)
24" (610 mm)
126637-01_G
Figure 19 - Multiple Chase Installation
Astria.us.com
Figure 21 - Constructing Chase
13
VENTING INSTALLATION Continued
3. Fabricate a flashing having a 16-1/2" diameter hole centered over chimney end with a 2" collar around hole (see Figure 22).
Attach noncombustible spacers at each corner and place flashing over chase.
4. Secure flashing through sides with 8-penny nails or sheet rock screws.
5. Place galvanized sleeve through hole in flashing and around last section of chimney (see Figure 23).
6. Place termination cap over opening and slip stainless steel inner pipe into stainless steel chimney section. Lower termination assembly until cap rests evenly over flashing hole. Secure cap at each corner with sheet metal screws (see Figure 24).
Termination
Sheet Metal Screw
1" Noncombustible
Spacer
Chase Top
1" Space
1/4" Screen
16-1/2" Diameter
28 Gauge
Galvanized Steel
2" Collar
As Required
Figure 22 - Constructing Chase Top Flashing
Termination Cap
Note: Do Not Seal
Ventilation Openings
1" Spacer
Screw
Note: Do Not Seal
Ventilation Openings
Chase Facia
Figure 24 - Securing Termination to Chase Top Flashing with Sheet
Metal Screws
ROUND TOP TERMINATIONS INSTALLATION RLT-12D, AND
RLT-12HT
1. Construct chase as illustrated in Figure 25. Note: The shortest vertical side must be at least 30" high and the minimum inside dimension must be at least 19" as shown in Figure 25.
2. Add pipe sections to chimney system as outlined in fireplace installation instructions until the last piece of chimney is a minimum of 6" above chase top (see Figure 25).
3. Fabricate a flashing having a 16-1/2" diameter hole centered over chimney end with a 2" collar around hole (see Figure 26, page 15).
19"
(483 mm) Min.
6" (153 mm) Min.
36"
(915 mm)
Min.
3"
(77 mm)
Min.
30"
(762 mm)
Min.
Galvanized Sleeve
2" (51 mm) Min.
Figure 23 - Installing Termination Cap
Figure 25 - Constructing Chase
14 Astria.us.com
126637-01_G
VENTING INSTALLATION Continued
4. Attach noncombustible spacers at each corner and place flashing over chase (see Figure 27). Secure flashing through sides with
8-penny nails or sheet rock screws.
5. Place termination cap over opening. Slip stainless steel inner pipe of termination into inner stainless steel chimney section
(see Figure 28). Place galvanized steel over chimney outlet (see
Figure 29).
6. Attach storm collar where chimney pierces opening in flashing. Caulk where storm collar touches outer chimney pipe (see
Figure 29).
Note: Do Not Seal
Ventilation Openings
Caulk
Storm Collar
1" Spacer
Chase Top
Flashing
1" Space
16-1/2" Diameter
2" Collar
"X" Minimum
As Required
28 Gauge
Galvanized Steel
Figure 26 - Constructing Chase Top Flashing
1" Noncombustible Spacer
Chase Top
Termination Cap
6" (153 mm)
Min.
3"
(77 mm)
Min.
Chase
Flashing
Double Wall Chimney
"X" Minimum
Figure 29 - Chase Installation
NONCHASE INSTALLATION
1. Slip on proper pitch roof flashing and mount storm collar above it. Caulk top of storm collar where it contacts outer chimney pipe.
2. Mount round top termination and secure it to outer chimney pipe with 3 sheet metal screws.
Termination
Cap
Sheet Metal Screw
Caulk
1" Space
1/4" Screen
Note: Do Not Seal
Ventilation Openings
Chase Facia
Figure 27 - Chase Top Flashing
Inner Pipe of
Chimney
Overlap Shingles
(Top and Sides)
Storm Collar
Flashing
Underlap
Shingles
(Bottom Only)
Termination
Outer Pipe
Inner Pipe
126637-01_G
Figure 28- Installing Termination Cap
Figure 30 - Non-Chase Installation
FINISHING FIREPLACE
Combustible materials, such as wallboard, sheet rock, drywall, plywood, etc. may make direct contact with sides and top around the fireplace face. It is important that combustible materials do not overlap the face itself. Brick, glass, tile or other noncombustible materials may overlap the front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a noncombustible facing material, use only noncombustible mortar or adhesive.
Astria.us.com
15
MOSAIC MASONRY BRICK PANELS AND ESTATE REFRACTORY PANELS INSTALLATION
WARNING
LIFTING HAZARD
SINGLE -PERSON LIFT COULD
CAUSE INJURY.
USE ASSISTANCE WHEN MOVING
OR LIFTING.
Slot
Right Face
NOTE: A Mosaic Masonry or Estate liner is required for use with your
Georgian36, Georgian42, or Georgian50 Firebox. (Not supplied, see pages 24 and 25 for models available).
MOSAIC MASONRY BRICK INSTALLATION
Hearth
Figure 32 - Slots for Firebrick Walls
IMPORTANT: Installation of brick panels should be done after the fireplace is placed in a permanent location.
Note: Remove grate, screen assemblies and all hardware components out of the box prior to installation.
INSTALLATION
1. Install bottom brick panel. Using at least two people, hold bottom brick panel by its side edges. Place the back edge of bottom panel into the firebox first and carefully lower the front edge of panel. Make sure bottom panel is centered in the firebox and flush with the front of the fireplace. Be careful not to pinch your fingers between the panel and firebox (Figure 31).
2. Install the left and right side leading bricks (Figure 31).
4. Secure the firebrick wall using 2 of the retainers provided. The bracket will slip underneath the metal lip on the top of the wall and screw into the inner dome of the fireplace (Figure 33).
Right Wall
Retaining
Bracket
Leading
Brick
Figure 33 - Installing Side Walls
Side leading brick Panel
Hearth Panel
Figure 31 - Installing Hearth and Leading Brick panels
3. Install the left and right firebrick walls. There is a bracket with 2 tabs on the bottom of each firebrick wall. Angle the wall into the fireplace opening and into the slots on the side of the hearth (Figure 32), then tilt the top of the panel toward the firebox surround.
5. Install the rear firebrick wall last. Place the wall face side down on the hearth with the bottom of the wall toward the rear of the firebox and the top toward the front of the fireplace. Tilt the wall up toward the back of the firebox. Secure with 2 rear retaining brackets provided (Figure 34, page 17).
6. It is recommended that the joints between all firebrick walls be grouted for a more finished look, see grouting instructions. For more information and to watch a how to video go to Astria.us.com. and select Technical Support.
16 Astria.us.com
126637-01_G
MOSAIC MASONRY BRICK PANELS AND ESTATE REFRACTORY PANELS INSTALLATION Continued
Retaining Bracket
INSTALLING SCREEN
1. Slide round end of screen rod into rings at top of screen. Attach one push-on nut to end of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole on the left and right side of smoke shelf (Figure 35).
3. Mount flat end of screen rod with #10 x 5/8" to center of smoke shelf.
4. Install other screen rod in same manner.
Rating Plate
Hole for Screen Rod
Figure 34 - Installing Rear Wall
Leading
Bricks
GROUTING INSTRUCTIONS
Note: Grouting material provided with mosaic brick kit
1. Moisten brick surface with damp sponge or spray bottle just prior to application. When bricks are wet, any excess grout mixture on bricks will easily wipe off.
2. In a heavy duty mixing bucket, add equal parts cement and sand.
Add enough water and mix together well using a power drill with mixing wand attachment to a yogurt like consistency. Not adding enough water can lead to grout falling out after burning.
3. The overall length of piping bag should be about 16". If the bag is longer than 16", cut it down to size by removing end with larger opening. This will make the bag easier to handle.
4. Put grout mixture into piping bag making sure the smaller opening is downward and over a moist towel to avoid spilling.
Place a wet towel over the bucket making sure it is directly on the surface of grout mixture. This will keep the mixture moist and it will not dry out before use.
5. Grout all joints where two firebrick walls come together.
6. Using a trowel, remove excess grout mixture by moving trowel in the direction of the joint. Grout mixture in the joint should now be flush with brick surface. If not enough grout is applied into each space, grout may fall out after burning.
7. Using a joint striker, smooth out grout line. Allow 72 hours
before operating fireplace.
WARNING: Risk of fire! Replace grate with IHP approved grate only. The grate has been designed to keep the operation of your fireplace safe and efficient.
Figure 35 - Installing Fireplace Screen
INSTALLING GRATE RETAINERS
1. Place the provided grate retainers on the hearth as shown in Figure 36. The back of the retainer will be flush with the rear firebrick wall. Mark the center of the hole on the hearth with a marker.
2. Drill two holes in the hearth in the marked locations using a masonry 3/16" drill bit.
3. Secure grate retainer with masonry screws provided.
126637-01_G Astria.us.com
Figure 36 - Installing Grate Retainers
17
MOSAIC MASONRY BRICK PANELS AND ESTATE
REFRACTORY PANELS INSTALLATION Continued
LEFT BRICK
PANEL
UPPER CORNER
BRACKET (2x)
REAR BRICK
PANEL
OPTIONAL GAS LINE INSTALLATION
ESTATE REFRACTORY PANELS INSTALLATION
Note: Remove grate, screen assemblies and all hardware components out of the box prior to installation.
1. Install bottom brick panel. Using at least two people, hold bottom brick panel by its side edges. Place the back edge of bottom panel into the firebox first and carefully lower the front edge of panel. Make sure bottom panel is centered in the firebox and flush with the front of the fireplace. Be careful not to pinch your fingers between the panel and firebox.
2. Position "Z" shape retaining brackets on top of the notched area toward the rear of the bottom brick panel. Grate retaining bracket should be positioned as shown in Figure 36, page 17.
3. Install rear brick panel. This panel has a top and bottom side.
To determine correct position, match up the pattern on the rear panel with the right and left brick panels before installing. Make sure rear panel is centered before continuing.
4. Install the right and left brick panels with the gas line knock outs placed down toward the bottom refractory. Align the right an left brick panels with the rear panel so the grout lines line up.
5. Install upper corner brackets and tighten set screws (see Figure
36a).
6. Install grate by placing rear legs into slots in the grate retainer
(see Figure 36a)
Gas line hook up should be done by your supplier or a qualified service person.
Note: Before you proceed, make sure your gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate fittings.
1. Remove knockout indentation on refractory or firebrick wall located above refractory hearth floor. Knockout indentation must be firmly tapped with any solid object such as a 1/2" dowel until it is released. Remove fragmented portions of refractory (see Figure
37).
2. Remove gas line cover plate located on either side of fireplace and pull out insulation from gas line conduit sleeve. Save insulation for reuse. Replace screws.
3. Run a 1/2" black iron gas line into fireplace through the rear at gas line conduit sleeve (if using a raised platform, add height). Provide sufficient gas line into fireplace chamber for fitting connection (see
Figure 38, page 19).
Note: Secure incoming gas line to wood framing to provide rigidity for threaded end.
4. Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement, Install the gas appliance or cap-off gas line if desired.
CAUTION: All gas piping and connections must be tested for leaks after the installation is completed.
After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT
USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT
OPERATE ANY APPLIANCE IF A LEAK IS DETECTED.
LEAK TESTING SHOULD BE DONE BY A QUALIFIED
SERVICE PERSON.
GRATE
GRATE RETAINER
BRACKET (2x)
WARNING: Do not operate an unvented gas log set in this fireplace with the chimney removed.
RIGHT BRICK
PANEL
BOTTOM
BRICK PANEL
ASH PANEL
Figure 36a - Installing Refractory Panels
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas Conduit
Cover
Remove
Knockout
Side
Firebrick
Finished
Side
1/2" Dowel
Brick with
Access Hole
Figure 37 - Gas Line Access
18 Astria.us.com
126637-01_G
OPTIONAL GAS LINE INSTALLATION Continued
Outside of
Fireplace
Gas Line
Conduit
Incoming
1/2" Black
Iron Pipe
Side Firebrick
Finished Side
GLASS DOOR INSTALLATION
DOOR FRAME MODELS
BDMO36E/G/C, BDMO42E/G/C AND BDMO50E/G/C
Installation
1. Remove screws from smoke shelf (see Figure 39).
2. Mount top door frame and secure with screws provided (see
Figure 39).
3. Place bottom door frame on top of ash lip at front of fireplace
(see Figure 40).
4. Secure bottom door frame to brick with two hex screws provided as shown in Figure 40 using a 7/16" open end or adjustable wrench.
Repack
Insulation
Seal Opening with
Refractory
Cement
Provide Enough
Threaded End for
Fitting Connection
Figure 38 - Gas Line Installation
A gas line or gas log lighter may be installed for the purpose of installing a vented or vent-free decorative gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 or American
Gas Association draft requirements for Gas Fired Log Lighters for Wood
Burning Fireplaces, Draft NO. 4 dated August, 1993.
If you install a decorative gas appliance (vented gas log), the decorative gas appliance must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS
Z21.60 or Z21.84 and shall also be installed in accordance with the
National Fuel Gas Code, ANSI 7223NFPA 54 latest edition.
If you wish to install an unvented (vent-free) gas log set, only unvented gas log sets which have been found to comply with the standard for unvented room heaters, ANSI Z21.11.2 are to be installed in this fireplace.
WARNING: If the fireplace has been used for wood burning, the firebox and chimney must be cleaned of soot, creosote and ashes be a qualified chimney cleaner. Creosote will ignite if heavily heated.
WARNING: When using a decorative vented gas log, the damper must be removed or permanently locked in the fully open position and the glass doors must be in the fully open position.
126637-01_G
Bottom
Door Frame
Ash Lip
Top Door Frame
Smoke Shelf
Figure 39 - Installing Top Door Frame
Ash Lip
Hex Screw
Figure 40 - Installing Bottom Door Frame
WARNING: Discontinue use of the appliance immediately if doors are damaged and contact a qualified installer for repair. Only doors certified with the appliance shall be used.
WARNING: Do not slam or strike doors. Damage can result in a hazardous condition.
Astria.us.com
19
GLASS DOOR INSTALLATION Continued
INSTALLING GLASS DOORS
Spring clips have been installed but some adjustments may be needed. Install the doors using the following steps:
1. With bifold doors completely folded, insert bottom pivot pin into pivot hole located near bottom corner of front face opening and swing door to vertical position making sure top pins slide into door track. Door is installed when top door pin snaps into spring clip.
2. Repeat step 1 for remaining door.
If you find the doors do not close properly or do not appear level or straight, proceed with section on door adjustment,
Fold Door and
Slide Top Pins
Into Track
Spring Clip
Insert Pin into Spring
Clip
OPERATION AND MAINTENANCE GUIDELINES
GLASS DOORS
Glass doors are optional with the fireplace. When fireplace is in operation, doors must be fully opened or fully closed position only or a fire hazard may be created (see Figure 43, page 21).
A fireplace equipped with glass doors operates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount of air for combustion.
Excessive heat within the fireplace can result if too large a fire is built or if combustion air gate is not completely open. The following tips should be followed to assure that both the fireplace and glass door retain their beauty and function properly. Both the flue damper and glass doors must be fully opened before starting fire. This will provide sufficient combustion air and maintain safe temperatures in firebox.
IMPORTANT: The glass must be allowed to warm slowly and evenly.
The tempered glass will withstand a gradual temperature rise to 550° F, which is more than a normal fire will generate. Such materials as pitch/ wax laden logs, very dry mill end lumber and large amounts of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.
Insert Bottom Pivot
Pin into Hole
WARNING: Fireplaces equipped with glass doors should be operated only with doors fully opened or doors fully closed. Doors, if left partly open, may draw gas and flame out of the fireplace opening creating risks of both fire and smoke.
Pivot Hole
WARNING: Do not slam or strike doors. Damage can result in a hazardous condition.
Figure 41 - Installing Bi-Fold Doors
DOOR ADJUSTMENT
Remove doors and slightly loosen lower pivot clips and upper spring clips. Replace doors and fully close them. Use 1/8" shims (any material) to level doors. Once proper setting is achieved, carefully open doors enough so that you can access spring clips with a phillips screwdriver. Tighten screws. See Figure 42.
WARNING: Discontinue use of the appliance immediately if doors are damaged and contact a qualified installer for repair. Only doors certified with the appliance shall be used.
Cleaning Glass
Clean glass with any commercial glass cleaner or soap and water. Do not use any abrasive material to clean glass. Do not clean glass with any cool water if glass is still hot from the fire and smoke.
20
Figure 42 - Adjusting Bi-Fold Doors
Astria.us.com
126637-01_G
OPERATION AND MAINTENANCE GUIDELINES Continued TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. Please contact your IHP dealer for any questions or concerns a. When contacting your dealer please have your model and serial numbers of your fireplace ready. You can also visit our web site at Astria.us.com.
Doors Fully Closed
Fireplace Front
Doors Fully Opened
Fireplace Front
Figure 43 - Bi-Fold Glass Doors
OUTSIDE AIR AND DAMPER HANDLE OPERATION
The damper handle, which opens and closes the damper blade, is located in the upper front face of the fireplace. Pushing the handle forward and up through the keyway slot will free damper blade to automatically open. Pushing the handle forward and down will lock damper blade closed (see Figure 44). Damper must be locked in the full open position before operating fireplace (see Figure 44).
REPLACEMENT PARTS
See Pages 22 to 25 for a complete replacement parts list. Use only parts supplied from the manufacturer.
Normally, all parts should be ordered through your IHP distributor or dealer. Parts will be shipped at prevailing prices at time of order.
When ordering repair parts, always give the following information:
1. The model number of the fireplace.
2. The serial number of the fireplace.
3. The part number.
4. The description of the part.
5. The quantity required.
6. The installation date of the fireplace.
If you encounter any problems or have any questions concerning the installation or application of this fireplace, please contact your dealer.
IHP
1508 Elm Hill Pike, Suite 108
Nashville, TN 37210
Visit us at Astria.us.com.
Damper
Weight
To Close
Damper
Damper
Weight
To Open
Damper
126637-01_G
Figure 44 - Operating Damper Handle
Astria.us.com
21
PARTS
MODELS 36", 42", AND 50"
10
5
6
22
9
8
7
12
11
21
20
24
23
22
1
4
19
3
25
Astria.us.com
18
13
16/17
15
14
2
126637-01_G
PARTS
This list contains replaceable parts used in your firebox. When ordering parts, follow the instructions listed under Replacement Parts on page 21 of this manual.
WARNING: Contact an IHP dealer to obtain any of these parts. Never use substitute materials not approved by IHP. Use of non-approved parts can result in poor performance and safety hazards.
18
19
20
21
22
23
14
15
16
17
10
11
12
13
KEY NO. CATALOG NO. DESCRIPTION
1
8
9
6
7
4
5
2
3
**
**
**
**
**
**
**
**
**
**
Face Assembly
Firebox Bottom Assembly
Firebox Bottom
Firebox Surround
Outer Dome Assembly
Insulation Pan Support
Insulation Pan
Top Insulation
Fireplace Top Assembly, 36"
Fireplace Top Assembly, 42"
** Fireplace Top Assembly, 50"
J6997 Standoff
24
25
** Fireplace Surround Assembly
J4362 Clearance Spacer
J5329 Fireplace Handle Bracket
J6900 Outside Air Cover Plate
J6934 Gas Conduit Cover
J4368 Conduit One
J4369 Conduit Two
** Heat Shield Support
J6020 Ash Box Assembly
**
**
Inner Dome Assembly
Smoke Shield
** Damper Control Bracket
J4342 Screen 36"
J4341 Screen 42"
J4340 Screen 50"
J6928 Screen Rod 36"
J4391 Screen Rod 42"
J4390 Screen Rod 50"
J4347 Grate 36"
J4346 Grate 42"
J4345 Grate 50"
PARTS AVAILABLE NOT SHOWN
RP124174-01 Grate Retainer
J4357
J6906
Side Firebrick Wall Spacers
RP114913-01 Rear Firebrick Wall Spacers
Ember Protector
** Not a field replaceable part.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Georgian36
(F0693)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Georgian42
(F0694)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Georgian50
(F0695) QTY.
•
•
1
1
1
1
2
1
4
2
4
2
1
6
1
4
1
1
1
1
1
1
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
2
2
2
2
1
1
1
1
1
1
2
2
1
•
•
•
•
•
•
•
•
2
2
2
4
126637-01_G Astria.us.com
23
PARTS
MOSAIC MASONRY BRICK KITS
A Mosaic Masonry or Estate liner is required for use with your Georgian36, Georgian42, or Georgian50 Firebox. Catalog numbers are included for convenience.
WARNING: Contact an IHP dealer to obtain any of these parts. Never use substitute materials not approved by IHP. Use of non-approved parts can result in poor performance and safety hazards.
24
CATALOG NO. MODEL NO. DESCRIPTION
F0334 Mosaic36M2 Red Full Stacked
F0335 Mosaic36M4 Red Split Stacked
F0336 Mosaic36M2 Ivory Full Stacked
F0337 Mosaic36M4 Ivory Split Stacked
F0338 Mosaic36M3 Red Herr Full
F0339 Mosaic36M5 Red Herr Split
F0340 Mosaic36M3 Ivory Herr Full
F0341 Mosaic36M5 Ivory Herr Split
F0342 Mosaic42M2 Red Full Stacked
F0343 Mosaic42M4 Red Split Stacked
F0344 Mosaic42M2 Ivory Full Stacked
F0345 Mosaic42M4 Ivory Split Stacked
F0346 Mosaic42M3 Red Herr Full
F0347 Mosaic42M5 Red Herr Split
F0348 Mosaic42M3 Ivory Herr Full
F0349 Mosaic42M5 Ivory Herr Split
F0350 Mosaic50M2 Red Full Stacked
F0351 Mosaic50M4 Red Split Stacked
F0352 Mosaic50M2 Ivory Full Stacked
F0353 Mosaic50M4 Ivory Split Stacked
F0354 Mosaic50M3 Red Herr Full
F0355 Mosaic50M5 Red Herr Split
F0356 Mosaic50M3 Ivory Herr Full
F0357 Mosaic50M5 Ivory Herr Split
WARNING
LIFTING HAZARD
SINGLE -PERSON LIFT COULD
CAUSE INJURY.
USE ASSISTANCE WHEN MOVING
OR LIFTING.
IMPORTANT: Installation of brick panels should be done after the fireplace is placed in a permanent location.
Astria.us.com
126637-01_G
PARTS
ESTATE LINERS
An Estate or Mosaic Masonry liner is required for use with your Georgian36, Georgian42, or Georgian50 Firebox. Catalog numbers are included for convenience.
WARNING: Contact an IHP dealer to obtain any of these parts. Never use substitute materials not approved by IHP. Use of non-approved parts can result in poor performance and safety hazards.
126637-01_G
CATALOG NO. MODEL NO. DESCRIPTION
F0358 Estate36P2 Stacked "Rust"
F0359 Estate36P2 Stacked "Cappuccino"
F0360 Estate36P2 Stacked "Creamer"
F0361 Estate36P2 Stacked "Gray"
F0362 Estate36P3 Herringbone "Rust"
F0363 Estate36P3 Herringbone "Cappuccino"
F0364 Estate36P3 Herringbone "Creamer"
F0365 Estate36P3 Herringbone "Gray"
F0366 Estate42P2 Stacked "Rust"
F1367 Estate42P2 Stacked "Cappuccino"
F0368 Estate42P2 Stacked "Creamer"
F0369 Estate42P2 Stacked "Gray"
F0370 Estate42P3 Herringbone "Rust"
F0371 Estate42P3 Herringbone "Cappuccino"
F0372 Estate42P3 Herringbone "Creamer"
F0373 Estate42P3 Herringbone "Gray"
F0374 Estate50P2 Stacked "Rust"
F0375 Estate50P2 Stacked "Cappuccino"
F0376 Estate50P2 Stacked "Creamer"
F0377 Estate50P2 Stacked "Gray"
F0378 Estate50P3 Herringbone "Rust"
F0379 Estate50P3 Herringbone "Cappuccino"
F0380 Estate50P3 Herringbone "Creamer"
F0381 Estate50P3 Herringbone "Gray"
WARNING
LIFTING HAZARD
SINGLE -PERSON LIFT COULD
CAUSE INJURY.
USE ASSISTANCE WHEN MOVING
OR LIFTING.
IMPORTANT: Installation of brick panels should be done after the fireplace is placed in a permanent location.
Astria.us.com
25
26
ACCESSORIES
BI-FOLD GLASS DOORS (For Use With Mosaic Brick Only)
MODEL DESCRIPTION CAT NO.
F0932
F0933
F0934
F0935
F0936
F0953
F0954
F0955
F0956
F0957
F1003
F1004
F1005
F1006
F1007
F1008
F1009
F1010
F1011
F1012
F1013
F1014
BDMO36E GLASS DOOR, 36" EBONY
BDMO36G GLASS DOOR, 36" PEWTER
BDMO36C GLASS DOOR, 36" OILED BRONZE
BDMO42E GLASS DOOR, 42" EBONY
F1015
F1016
F1020
F1021
BDMO42G GLASS DOOR, 42" PEWTER
BDMO42C GLASS DOOR, 42" OILED BRONZE
BDMO50E GLASS DOOR, 50" EBONY
BDMO50G GLASS DOOR, 50" PEWTER
F1022 BDMO50C GLASS DOOR, 50" OILED BRONZE
BI-FOLD GLASS DOORS (For Use With Estate Refractory Panels Only
F1002 BDG36 GLASS DOOR, 36" BLACK
BDG36B
BDG36P
BDG42
BDG42B
BDG42P
BD50
BD50B
BD50P
GLASS DOOR, 36" BRUSHED BRASS
GLASS DOOR, 36" PLATINUM
GLASS DOOR, 42" BLACK
GLASS DOOR, 42" BRUSHED BRASS
GLASS DOOR, 42" PLATINUM
GLASS DOOR, 50" BLACK
GLASS DOOR, 50" BRUSHED BRASS
GLASS DOOR, 50" PLATINUM
12-12DM
18-12DM
24-12DM
36-12DM
48-12DM
12-12HT
18-12HT
24-12HT
36-12HT
48-12HT
DOUBLE WALL PIPE
12" Section Double Wall Pipe Snap Lock
18" Section Double Wall Pipe Snap Lock
24" Section Double Wall Pipe Snap Lock
36" Section Double Wall Pipe Snap Lock
48" Section Double Wall Pipe Snap Lock
12" Section Hi-Temp Double Wall Pipe Snap Lock
18" Section Hi-Temp Double Wall Pipe Snap Lock
24" Section Hi-Temp Double Wall Pipe Snap Lock
36" Section Hi-Temp Double Wall Pipe Snap Lock
48" Section Hi-Temp Double Wall Pipe Snap Lock
30° OFFSET AND RETURN
F0937
F0958
30E-12DM
30E-12HT
30 Degree Offset and Return
30 Degree Hi-Temp Offset and Return
OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION
F1091 AK4 Complete Outside Air Kit w/Collars Hood & 3' Flex
Astria.us.com
126637-01_G
F1093
ACCESSORIES Continued
OPTIONAL OUTSIDE AIR KIT FOR SIDEWALL INSTALLATION
AK4F Outside Air Kit Collar, Hood & 3' Flex for Floor Venting
F0946 SC2-1
STORM COLLAR
Storm Collar
FIRESTOP SPACER
J4384 1100EFS-10DM 1" Clearance Firestop Spacer
F0940
F0942
F0943
F0948
F0949
F0947
FS-10 2" Clearance Firestop Spacer
ROOF FLASHING
V6F-10DM Roof Flashing 0 to 6/12 Pitch
V12F-10DM Roof Flashing 6/12 to 12/12 Pitch
SQUARE CHASE-TOP TERMINATION
STL-12D
STL-12DMP
Square Top Termination with Slip Section
Square Top Termination with Slip Section (Pre-Painted
Black)
ROUND TOP TERMINATIONS
RLT-12D Round Top Termination with Louvered Screen
F0960 RLT-12HT Hi-Temp Round Top Termination with Louvered Screen
FIRESTOP THIMBLE
F0944 FST10 Firestop Thimble
F2659
LABEL-UL127-50PK
LABEL-UL127-
50PK
UL127 Venting Label - 50 PK
126637-01_G Astria.us.com
WARNING
HOT
WARNING
HOT
• Fire Risk
• Insulation and combustibles must not touch pipe
• Consult manual for clearance requirements
• Ensure proper connection
• Fire Risk
• Insulation and combustibles must not touch pipe
• Consult manual for clearance requirements
• Ensure proper connection
WARNING
HOT
• Fire Risk
• Insulation and combustibles must not touch pipe
• Consult manual for clearance requirements
• Ensure proper connection
900599-01
27
Canadian code CAN/ULC-S610-M87 and other pertinent codes require stainless steel chimney for the installation of this fireplace. A Cold Air Climate Kit is also required in Canada and is recommended for cooler regions in the United States. Below, find a list of approved stainless steel parts.
Chimney Parts List for Canada
Catalog
No.
F0953
F0954
F0955
F0956
F0957
12-12HT
18-12HT
24-12HT
36-12HT
48-12HT
12" Section Double Wall Pipe
18" Section Double Wall Pipe
24" Section Double Wall Pipe
36" Section Double Wall Pipe
48" Section Double Wall Pipe
F0958
F0959
30E-12HT 30" Offset and Return
12S-12HT Chimney Support
F0960
F0961
RLT-12HT Round Top w/ Louvers
AP-12HT Anchor Plate/Collar Assembly
(Masonry Fireplaces)
CAK-12 Cold Air Collar Kit F0951
*When ordered alone, this part cannot ship via parcel delivery services.
IMPORTANT NOTICES - CANADA
IMPORTANT NOTICE
A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance with the instructions by its manufacturer. A locally fabricated shroud may be used with IHP Shroud Leg Spacer
Kit (SLK) in accordance with instructions provided with the shroud.
NOTICE: The firebox canopy (hood) must not be modified or replaced with a canopy that may be provided with the unvented decorative room heater.
CAUTION: THE STRUCTURAL INTEGRITY OF
THE MANUFACTURED HOME FLOOR, WALL,
AND CEILING/ROOF MUST BE MAINTAINED.
WARNING: DO NOT INSTALL IN SLEEPING
ROOM OF MOBILE HOMES.
28 Astria.us.com
126637-01_G
APPENDIX A
Draft Requirements
Your wood-burning appliance is dependent upon a properly functioning chimney for optimum performance. It is important to match the wood-burning appliance to the chimney. The chimney has two functions:
1. It draws combustion air into the appliance (without air, no fuel will burn) and
2. It exhausts combustion by-products. Your new appliance is what is known as a “natural draft” appliance.
The appliance depends solely on the natural draft of the chimney system to draw combustion air into the unit. Draft is the force that moves air from the appliance up into the chimney. The amount of draft in your chimney depends on the length of the chimney, local geography, nearby obstructions and other factors. Too much draft may cause excessive temperatures in the appliance (overfiring). Slow or inadequate draft equals poor combustion and possible smoking problems. The following are some conditions that may contribute to poor chimney draft:
1. A chimney too large for your appliance.
2. A chimney with not enough height to produce adequate draft.
3. A chimney with excessive height (this may allow exhaust to cool too much before exiting, which will stall the rate the exhaust exits).
4. Offsets in the venting system are too restrictive (see Chimney
Guidelines).
Inadequate draft will cause the appliance to leak smoke into the room through the wood-burning appliance and the chimney connector joints.
Excessive draft may cause an uncontrollable burn or a glowing red appliance or chimney part.
Overfiring Damage - If the appliance or chimney connector glows, you are overfiring. Other symptoms may include: Cracking, warping or burning out of components, plated accessories may turn color, appliance glass may develop a haze, which will not come off with cleaning.
Overfiring of a appliance is a condition where excessive temperatures are reached, beyond the design capabilities of the appliance.
The damage that occurs from overfiring is not covered under the manufacturer’s limited warranty.
Also see Troubleshooting on Page 30.
WARNING
Neither the manufacturer nor the seller warrants “smoke free” operation nor are we responsible for inadequate system draft caused by mechanical systems, general construction conditions, inadequate chimney heights, adverse wind conditions and/or unusual environmental factors or conditions beyond our control.
Selecting the Proper Venting System
The appliance is merely one component of a larger system. The other equally important component is the venting system. This is necessary for achieving the required flow of combustion air to the fire chamber and for safely removing unwanted combustion by products from the appliance.
If the venting system’s design does not promote these ends, the system may not function properly. Poorly functioning venting systems may create performance problems as well as be a safety hazard. A draft
test should read greater than .04’ W.C. (inches water column) and
less than .08” W.C. As per NFPA-211 standard, the installer must take into account all variables within the installation and install the appliance in such a manner that satisfies the draft requirements of the appliance. See Chimney Guidelines to assist you in selecting the proper venting system for your installation.
American National Standards Institute ANSI/NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appli-
ances - See Draft Section: A chimney or vent shall be so designed and constructed to develop a flow sufficient to completely remove all flue and vent gases to the outside atmosphere. The venting system shall satisfy the draft requirements of the connected appliance in accordance with the manufacturer’s instructions.
Chimney Guidelines:
• Most wood-burning appliances requires approximately 12 feet minimum of “effective draw” provided by the venting system. As a rule of thumb, every 90 degree total direction change in the venting will result in a loss of approximately 5 feet of “effective draw.”
Example: If two 45 degree offsets are used, subtract 5 feet from the actual vertical vent height to determine your “effective draw.”
In this case if you had 14 feet of vertical vent, the effective draw would only be approximately 9 feet (14 ft. - 5 ft. = 9 ft.), therefore it may be necessary to add additional height to the venting system.
• Do not install an offset within the first two feet above the flue outlet on the appliance.
• In well insulated and weather tight homes, it may be difficult to establish a good draft up your chimney. The poor draft is caused by a shortage of air in the house. In this situation an Outside Air
Kit may need to be installed (See Negative Pressure Warning below and Outside Combustion Air in the Installation and Operation manual).
Negative Pressure Warning
These appliances are not designed to be operated in a negative pressure. In very airtight homes with large kitchen exhaust fans, furnace cold air returns, fresh air exchange systems and any other air system in close proximity to the heating appliance may create a negative pressure in the same room as the heating appliance. This can create dangerous back drafting of the appliance and chimney joints, drawing combustion by-products into the home. Be sure your home has adequate makeup air to eliminate negative pressures caused by the above-mentioned sources. Outside air connected to the appliance probably will not resolve such a problem as the appliance is not the source of negative pressure. IHP accepts no liability for damages resulting from negative pressures described here.
Ventilation Requirements - Provide adequate air for combustion.
The fresh air requirements of this appliance must be met within the space where it will be installed. Ventilation is essential when using a solid-fuel-burning appliance. In well insulated and weather tight homes, it may be difficult to establish a good draft up the chimney
(caused by a shortage of air in the home). The lack of air is caused by many common household appliances which exhaust air from the home (such as a furnace, heat pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances). Also, the combustion process of this appliance uses oxygen from inside the dwelling. If the available fresh air delivery in the dwelling is insufficient to support the demands of these appliances, problems can result
(i.e. excessive negative pressure can develop in the dwelling which will affect the rate at which this appliance can draft thus resulting in performance problems or smoking. To correct this problem it may help to open a window (preferably on the windward side of the house) or install an outside air kit.
126637-01_G Astria.us.com
29
APPENDIX A Continued
Smoking – Causes And Troubleshooting
To reduce the likelihood of smoking when opening the door, open the combustion air control or damper before opening the door.
Your appliance has been designed and tested to provide smoke free operation. Occasionally, there may be a small amount of smoking upon lighting the fire, until the chimney heats up but this should not continue. If the appliance continues to smoke it is probably for one of the following reasons:
A. Negative pressure in the house -
As the fire burns, air goes up the chimney. This air must be replaced through leakage into the house or through the outside air duct. When operating the appliance, open a nearby window temporarily to check if there is adequate replacement air supply.
B. Blowers operating (e.g.: range hood) - These blowers draw air out of the house and may actually cause a negative pressure in the house. Turn off all blowers and open a nearby window to determine if this is the cause of the problem.
C. Wet wood - Wet or tarred wood will smoulder and smoke instead of burning properly. Your dealer can help you determine if you have properly seasoned wood for burning.
D. Dirty or blocked chimney - Check to make sure the chimney is clear and clean. If dirty call a certified chimney sweep or use a properly sized chimney brush to clean.
E. Chimney not long enough - The minimum chimney height is twelve (12) feet (3.7 m) not including the appliance height. The chimney must extend at least three (3) feet (915 mm) above its point of contact with the roof and at least two (2) feet (610 mm) higher than any roof or wall within ten (10) feet (3 m) of it. When installed with offsets, the minimum chimney height is fifteen (15) feet. Additional height will increase draft and will decrease the tendency to smoke.
F. Poor chimney draft - With no fire, there should be sufficient draft to exhaust cigarette smoke introduced under the baffle or flue baffle.
Chimneys installed against an outside wall without protection may generate back draft problems which will cause start-up problems.
To prevent this, open a nearby window, roll up a piece of paper and light it. Then, hold it in the upper part of the firebox to warm up the chimney. Wait until the draft is sufficient, then start the fire.
G. Blower for forced air kit operating (some models) - Make sure that the blower is in the “off” position when you open the appliance door for reloading.
Locating The Appliance
The best location to install your appliance is determined by considering the location of windows, doors, and the traffic flow in the room where the appliance is located, allowing space in front of the unit for the hearth extension and the mantel, and taking into consideration the location of the hot air ducts (some models), outside air kit and chimney.
If possible, you should choose a location where the chimney will pass through the house without cutting floor or roof joists.
When selecting the location, the chimney outlet position and the direction of the wind are important factor affecting the chimney performance. To allow a maximum draft and to reduce wind turbulence, the chimney must:
• Penetrate the highest part of the roof.
• Be installed as far as possible of roof offsets, trees or any other obstructions that may cause wind turbulence and back drafts in the chimney.
• The least amount of offsets (elbows) possible. NOTE: A maximum of 2 offsets is allowed.
Marginal Location
Wind Direction
Location
Not
Recommended
Outside Air
Intake
Facing the Wind
Figure 1
Location Recommended
• Garbage;
• Lawn clippings or yard waste;
• Materials containing rubber, including tires;
• Materials containing plastic;
• Waste petroleum products, paints or paint thinners, or asphalt products;
• Materials containing asbestos;
• Construction or demolition debris;
• Railroad ties or pressure-treated wood; woods that have been dipped in tar, pitch, pine tar, creosote, etc.
• Manure or animal remains;
• Salt water driftwood or other previously salt water saturated materials;
• Unseasoned wood;
• Christmas tree branches;
• Paper products, colored paper, cardboard, plywood, or particleboard;
• Gasoline;
• Naphtha;
• Engine Oil;
• Flammable Liquids;
• Solvents;
• Grease; or
• Charcoal or Coal
NOTE: The use of a firewood moisture meter is recommended to ensure the firewood contains less than 20% moisture.
Seasoning Guide
Softwoods - 6 months to 18 months
Hardwoods - 12 months to 24 months
Logs that are 5” diameter across or larger should be split in half, three pieces if over 8 inches, and four pieces when over a foot across. If a tree has been dead for 2 - 4 years it still needs to be cut, split, and seasoned for 6 to 24 months depending on the wood.
Standard
Cord of
Wood
Tree
Location
Not
Recommended
Prohibited Fuels
These appliances are designed to burn natural well-seasoned wood.
The wood fuel should be air dried seasoned hardwoods, as compared to softwoods or to green or freshly cut hardwoods. Burning artificial logs, in some model appliances is allowed (see Installation and Operation manual); please read and follow the instructions provided by the manufacturer. DO NOT BURN:
Figure 2
30 Astria.us.com
126637-01_G
Innovative Hearth Products
Astria
®
Brand Wood-Burning Fireplace
20 Year Limited Warranty
THE WARRANTY
Innovative Hearth Products ("IHP") 20 Year Limited Warranty warrants your Astria
®
brand wood burning fi replace ("Product") to be free from defects in materials and workmanship at the time of manufacture. The Product body, fi rebox and ceramic glass carry the 20 Year Limited Warranty. Ceramic glass carries the 20 Year Limited Warranty against thermal breakage only. After installation, if covered components manufactured by IHP are found to be defective in materials or workmanship during the 20 Year
Limited Warranty period and while the Product remains at the site of the original installation, IHP will, at its option, repair or replace the covered components. If repair or replacement is not commercially practical, IHP will, at its option, refund the purchase price or wholesale price of the IHP product, whichever is applicable. IHP will also pay IHP prevailing labor rates, as determined in its sole discretion, incurred in repairing or replacing such components for up to fi ve years. THERE ARE EXCLUSIONS AND
LIMITATIONS to this 20 Year Limited Warranty as described herein.
COVERAGE COMMENCEMENT DATE
Warranty coverage begins on the date of purchase. In the case of new home construction, warranty coverage begins on the date of fi rst occupancy of the dwelling or six months after the sale of the Product by an independent IHP dealer/distributor, whichever occurs earlier. The warranty shall commence no later than 24 months following the date of product shipment from IHP, regardless of the installation or occupancy date.
EXCLUSIONS AND LIMITATIONS
This 20 Year Limited Warranty applies only if the Product is installed in the United States or Canada and only if operated and maintained in accordance with the printed instructions accompanying the Product and in compliance with all applicable installation and building codes and good trade practices.
This warranty is non-transferable and extends to the original owner only. The Product must be purchased through a listed supplier of IHP and proof of purchase must be provided. The Product body and fi rebox carry the 20 Year Limited Warranty from the date of installation. Vent components, trim components, paint and applied stains are excluded from this 20 Year Limited Warranty. The following do not carry a 20 Year Limited Warranty but are warranted as follows:
Air tubes, baffl es and brick retainers – Repair or replacement for one year from the date of installation
Cast iron parts – Replacement for one year from date of installation
Electrical components – Repair or replacement for one year from the date of installation
Fireplace screens, refractory and side shields (metal or refractory) – Repair or replacement for two years from date of installation. Excludes hairline cracks.
Fuel grates –These parts are considered consumable accessories and therefore are not warranted, with the exception of defects in material or workmanship which are covered for 90 days from the date of installation
Gaskets – Replacement for one year from date of installation
Gold & nickel plating – Replacement for two years from date of installation. Excludes tarnishing
Optional glass doors – Repair or replacement for 90 days from the date of installation
Labor coverage – Prevailing IHP labor rates apply for the warranty period of the component.
Parts not otherwise listed carry a 90 day warranty from the date of installation.
Whenever practicable, IHP will provide replacement parts, if available, for a period of 10 years from the last date of manufacture of the Product.
IHP will not be responsible for: (a) damages caused by normal wear and tear, accident, riot, fi re, fl ood or acts of God; (b) damages caused by abuse, negligence, misuse, or unauthorized alteration or repair of the Product affecting its stability or performance. (The Product must be subject to normal use with approved fuels listed in the Operation
Manual provided with the product. This includes burning such fi replace fuels as wood and natural or propane gas. Fuel products with abnormal burning characteristics, including but not limited to fuel such as driftwood, coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the
Product or may cause it to function improperly.); (c) damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product; (d) damages, repairs or ineffi ciency resulting from faulty installation or application of the Product.
Coverage of this 20 Year Limited Warranty is conditional upon use of an adequate fuel grate on factory-built fi replaces only, when applicable.
IHP is not responsible for inadequate fi replace system draft caused by air conditioning and heating systems, mechanical ventilation systems, or general construction conditions which may generate negative air pressure in the room in which the appliance is installed. Additionally IHP assumes no responsibility for smoking conditions caused by inadequate chimney height, adjoining trees or buildings, adverse wind conditions or unusual environmental factors and conditions. Certain IHP Products are listed for use with
Security Chimneys International, Ltd. or IHP chimney systems only. Use of chimney components other than that specifi ed in the Product manual will void the Product warranty.
This 20 Year Limited Warranty covers only parts and labor as provided herein. In no case shall IHP be responsible for materials, components or construction which are not manufactured or supplied by IHP or for the labor necessary to install, repair or remove such materials, components or construction. Additional utility bills incurred due to any malfunction or defect in equipment are not covered by this 20 Year Limited Warranty. All replacement or repair components will be shipped F.O.B. from the nearest stocking IHP factory.
LIMITATION ON LIABILITY
It is expressly agreed and understood that IHP’s sole obligation and the purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to replacement, repair, or refund, as specifi ed herein.
In no event shall IHP be liable for any incidental or consequential damages caused by defects in the Product, whether such damage occurs or is discovered before or after replacement or repair, and whether such damage is caused by IHP’s negligence. IHP has not made and does not make any representation or warranty of fi tness for a particular use or purpose, and there is no implied condition of fi tness for a particular use or purpose.
IHP makes no expressed warranties except as stated in this 20 Year Limited Warranty. The duration of any implied warranty is limited to the duration of this expressed warranty.
No one is authorized to change this 20 Year Limited Warranty or to create for IHP any other obligation or liability in connection with the Product. Some states and provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. The provisions of this 20 Year
Limited Warranty are in addition to and not a modifi cation of or subtraction from any statutory warranties and other rights and remedies provided by law.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
IHP reserves the right to investigate any and all claims against this 20 Year Limited Warranty and to decide, in its sole discretion, upon the method of settlement.
To receive the benefi ts and advantages described in this 20 Year Limited Warranty, the appliance must be installed and repaired by a licensed contractor approved by IHP.
Contact IHP at the address provided herein to obtain a listing of approved dealers/distributors. IHP shall in no event be responsible for any warranty work done by a
contractor that is not approved without fi rst obtaining IHP's prior written consent.
HOW TO REGISTER A CLAIM AGAINST WARRANTY
In order for any claim under this warranty to be valid, you must contact the IHP dealer/distributor from which you purchased the product. If you cannot locate the dealer/ distributor, then you must notify IHP in writing. IHP must be notifi ed of the claimed defect in writing within 90 days of the date of failure. Notices should be directed to the
IHP Warranty Department at 1508 Elm Hill Pike, Suite 108; Nashville, TN 37210 or visit our website at WWW.ASTRIA.US.COM.
Printed in U.S.A. © 2013 Innovative Hearth Products
126637-01_G Astria.us.com
Innovative Hearth Products
31
Astria.us.com.
Record the following important information about your fireplace:
Fireplace model number
Fireplace serial number
Date fireplace was Installed
Dealer name
P126637-01
Innovative Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © 2014 Innovative Hearth Products LLC
P/N 126637-01 Rev. G 07/2017 1508 Elm Hill Pike, Suite 108 • Nashville, TN 37210
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Safety
- 4 Specifications
- 7 Fireplace Installation
- 9 Venting Installation
- 16 Mosaic Brick Panel and Estate Refractory Panel Installation
- 18 Optional Gas Line Installation
- 19 Glass Door Installation
- 20 Operation and Maintenance Guidelines
- 21 Technical Service
- 21 Replacement Parts
- 22 Parts
- 26 Accessories
- 28 Important Notices Canada
- 29 Draft Smoke Guidelines - Appendix A
- 31 Warranty