Omron CS1 W-SCB21/SCB41 Serial Communication Board, CS1 W-SCU21 Serial Communication Unit Operation Manual
The CS1 CS1W-SCB21/SCB41, CS1 CS1W-SCU21 are Inner Boards and CPU Bus Units respectively used for serial communications in CS1 series programmable controllers. They provide up to two RS-232C ports for connecting to host computers, programming devices, general-purpose external devices, and Programmable Terminals. They support various communication modes: Host Link, Protocol Macros, 1:N NT Links, and loopback test.
Advertisement
Advertisement
Cat.No. W336–E1–2 Inner Board CS1 CPU Bus Unit SYSMAC CS1 Series CS1W-SCB21/SCB41 Serial Communications Boards CS1W-SCU21 Serial Communications Unit OPERATION MANUAL SYSMAC CS1 Series Serial Communications Boards and Serial Communications Unit Operation Manual Revised February 2000 Notice: OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property. DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. ! WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ! Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage. ! OMRON Product References All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product. The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means “word” and is abbreviated “Wd” in documentation in this sense. The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else. Visual Aids The following headings appear in the left column of the manual to help you locate different types of information. Note Indicates information of particular interest for efficient and convenient operation of the product. 1, 2, 3... 1. Indicates lists of one sort or another, such as procedures, checklists, etc. OMRON, 1999 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication. v TABLE OF CONTENTS PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison to Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting the Serial Communications Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 2 Initial Settings and I/O Memory Allocations . . . . . . . . . . 2-1 2-2 2-3 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Exchange with the CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Memory Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 3 Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3-2 3-3 3-4 Installing the Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS-232C and RS-422A/485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 4 Using Host Link Communications . . . . . . . . . . . . . . . . . . 4-1 4-2 4-3 4-4 4-5 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 5 Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5-2 5-3 5-4 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 6 Using 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1 6-2 6-3 Overview of 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xi xii xii xii xiii xiii xv 1 2 3 5 8 11 17 22 27 28 39 40 46 48 59 60 61 63 83 91 92 92 96 99 103 107 108 115 120 136 149 150 152 153 vii TABLE OF CONTENTS SECTION 7 Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 7-2 7-3 Executing Loopback Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SECTION 8 Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . 8-1 8-2 8-3 8-4 8-5 8-6 Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Status Area Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replacement Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159 160 161 162 163 164 167 167 182 188 189 Appendices A Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B CompoWay/F Master Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C E5jK Digital Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D E5jK Digital Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E E5ZE Temperature Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F E5ZE Temperature Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G E5jJ Temperature Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H ES100j Digital Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I K3Tj Intelligent Signal Processor Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J V500/V520 Bar Code Reader Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K 3Z4L Laser Micrometer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . L Visual Inspection System Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . M V600/V620 ID Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . N Hayes Modem AT Command Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . O Changing Communications Port Settings Using STUP(237) . . . . . . . . . . . . . . . . . . . . . . . . . Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii 193 195 211 229 245 267 287 301 343 365 377 411 431 469 477 481 489 About this Manual: This manual describes the installation and operation of the SYSMAC CS1-series CS1W-SCB21/SCB41 Serial Communications Boards and CS1W-SCU21 Serial Communications Unit and includes the sections described on the next page. The Serial Communications Boards are classified as Inner Boards and the Serial Communications Unit is classified as a CPU Bus Unit. Please read this manual and all related manuals listed in the following table carefully and be sure you understand the information provided before attempting to install and operate a Serial Communications Board or Unit. Name Cat. No. SYSMAC CS1-series W336 CS1W-SCB21/41, CS1W-SCU21 Serial Communications Boards and Serial Communications Unit Operation Manual (This manual) SYSMAC CS1-series W342 CS1G/H-CPUjj-E, CS1W-SCB21/41, CS1W-SCU21 Communications Commands Reference Manual Contents Describes the use of Serial Communications Unit and Boards to perform serial communications with external devices, including the usage of standard system protocols for OMRON products. Communications commands are described in the CS1G/H-CPUjj-E Programmable Controllers Communications Commands Reference Manual (W342). Creating protocol macros is described in the CX-Protocol Operation Manual (W344). Describes the C-series (Host Link) and FINS communications commands used with CS1-series PCs. SYSMAC CS1-series CS1G/H-CPUjj-E Programmable Controllers Operation Manual SYSMAC CS1-series CS1G/H-CPUjj-E Programmable Controllers Programming Manual SYSMAC CS1-series C200H-PRO27-E, CQM1-PRO01-E Programming Consoles Operation Manual W339 Describes the installation and operation of the CS1-series PCs. W340 Describes the ladder diagram programming instructions supported by CS1-series PCs. W341 Provides information on how to program and operate CS1-series PCs using a Programming Console. SYSMAC WS02-CXPjj-E CX-Programmer Operation Manual --- Provides information on how to use the CX-Programmer, a programming device that supports the CS1-series PCs. SYSMAC WS02-PSTC1-E CX-Protocol Operation Manual W344 Describes the use of the CX-Protocol to create protocol macros as communications sequences to communicate with external devices. SYSMAC CS1-series CS1W-ETN01 Ethernet Unit Operation Manual W343 Describes the installation and operation of CS1W-ETN01 Ethernet Unit. ! WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given. ix TABLE OF CONTENTS This manual contains the following sections. Section 1 introduces the hardware and software functions of the Serial Communications Board and the Serial Communications Unit, including the communications modes, system configurations, and specifications. Section 2 describes the components of the Serial Communications Boards and the Serial Communications Units, the settings required for operation, and the memory allocated in the I/O memory of the CPU Unit for controlling and monitoring communications. Section 3 describes how to mounting the Serial Communications Board and Serial Communications Units, and how to connect the ports to external devices. Section 4 describes the procedure and other information required to use Host Link communications. Section 5 describes the procedure and other information required to use protocol macros. Section 6 describes the procedure and other information required to use 1:N NT Links to Programmable Terminals. Section 7 describes the procedure and other information required to conduct loopback test to check the serial communications ports. Section 8 describes the troubleshooting and maintenance procedures for the Serial Communications Boards and the Serial Communications Unit. Appendix A to Appendix N provide the specifications of the standard system protocols. Appendix O provides information on using STUP(237) to change serial communications port settings. x PRECAUTIONS This section provides general precautions for using the CS1-series Serial Communications Boards and Units. The information contained in this section is important for the safe and reliable application of Programmable Controllers. You must read this section and understand the information contained before attempting to set up or operate a PC system. 1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xii xii xii xiii xiii xv xi 3 Safety Precautions 1 Intended Audience This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent). • Personnel in charge of installing FA systems. • Personnel in charge of designing FA systems. • Personnel in charge of managing FA systems and facilities. 2 General Precautions The user must operate the product according to the performance specifications described in the operation manuals. Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative. Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms. This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation. ! WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications. 3 Safety Precautions ! WARNING The CPU Unit refreshes I/O even when the program is stopped (i.e., even in PROGRAM mode). Confirm safety thoroughly in advance before changing the status of any part of memory allocated to I/O Units, Special I/O Units, or CPU Bus Units. Any changes to the data allocated to any Unit may result in unexpected operation of the loads connected to the Unit. Any of the following operation may result in changes to memory status. • Transferring I/O memory data to the CPU Unit from a Programming Device. • Changing present values in memory from a Programming Device. • Force-setting/-resetting bits from a Programming Device. • Transferring I/O memory files from a Memory Card or EM file memory to the CPU Unit. • Transferring I/O memory from a host computer or from another PC on a network. ! WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock. ! WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock. xii 5 Application Precautions ! WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock. ! Caution 4 Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable. Operating Environment Precautions ! Caution Do not operate the control system in the following places: • Locations subject to direct sunlight. • Locations subject to temperatures or humidity outside the range specified in the specifications. • Locations subject to condensation as the result of severe changes in temperature. • Locations subject to corrosive or flammable gases. • Locations subject to dust (especially iron dust) or salts. • Locations subject to exposure to water, oil, or chemicals. • Locations subject to shock or vibration. ! Caution Take appropriate and sufficient countermeasures when installing systems in the following locations: • Locations subject to static electricity or other forms of noise. • Locations subject to strong electromagnetic fields. • Locations subject to possible exposure to radioactivity. • Locations close to power supplies. ! Caution 5 The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system. Follow all installation instructions and precautions provided in the operation manuals. Application Precautions Observe the following precautions when using the PC System. ! WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury. • Always connect to a class-3 ground (to 100 Ω or less) when installing the Units. Not connecting to a class-3 ground may result in electric shock. • Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock. • Mounting or dismounting Serial Communications Boards, Serial Communications Units, or any other Units. • Assembling the Units. • Setting DIP switches or rotary switches. • Connecting cables or wiring the system. xiii 5 Application Precautions ! Caution Failure to abide by the following precautions could lead to faulty operation of the PC or the system, or could damage the PC or PC Units. Always heed these precautions. • Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes. • Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction. • Tighten the mounting screws at the bottom of Serial Communications Units to a torque of 0.4 Nm. An incorrect tightening torque may result in malfunction. • Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit. • Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction. • Always check polarity before wiring RS-422A/485 connectors. The polarity for the SDA/B and RDA/B signals can be different for some external devices. • Check to be sure that terminating resistors have been correctly installed for RS-422A/485 systems before starting operation. • Disconnect the functional ground terminal before conducting voltage withstand tests. • Never turn OFF the power supply while writing protocol macro data. • Wire all connections correctly according to instructions in Section 3 Installation and Wiring. • Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning. • Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction. • Check the user program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation. • Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation. • Changing the operating mode of the PC. • Force-setting/force-resetting any bit in memory. • Changing the present value of any word or any set value in memory. • Do not lay communications cables near power lines or high-voltage lines. • Always lay communications cables in ducts. • Do not pull on the communications cables or bend the communications cables beyond their natural limit. Doing either of these may break the cables. • Do not place objects on top of the communications cables or other wiring lines. Doing so may break the cables. • Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static built-up. Not doing so may result in malfunction or damage. • Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation. xiv Conformance to EC Directives 6 • Do not touch circuit boards or the components mounted to them with your bare hands. There are sharp leads and other parts on the boards that may cause injury if handled improperly. • When transporting or storing Boards, wrap them in material that will protect LSIs, ICs, and other components from static electricity and be sure that they remain within the storage temperature range. 6 Conformance to EC Directives 6-1 Applicable Directives • EMC Directives • Low Voltage Directive 6-2 Concepts EMC Directives OMRON devices that comply with EC Directives also conform to the related EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards (see the following note). Whether the products conform to the standards in the system used by the customer, however, must be checked by the customer. EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards. Note Applicable EMC (Electromagnetic Compatibility) standards are as follows: EMS (Electromagnetic Susceptibility): EN61131-2 EMI (Electromagnetic Interference): EN50081-2 (Radiated emission: 10-m regulations) Low Voltage Directive Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to 1,500 VDC meet the required safety standards for the PC (EN61131-2). 6-3 Conformance to EC Directives The CS1-series PCs comply with EC Directives. To ensure that the machine or device in which the CS1-series PC is used complies with EC directives, the PC must be installed as follows: 1, 2, 3... 1. The CS1-series PC must be installed within a control panel. 2. You must use reinforced insulation or double insulation for the DC power supplies used for the communications power supply and I/O power supplies. 3. CS1-series PCs complying with EC Directives also conform to the Common Emission Standard (EN50081-2). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives. xv 6 Conformance to EC Directives 6-4 EMI Measures The CS1-series PCs conform to the Common Emission Standards (EN50081-2) of the EMC Directives. However, the noise generated from Serial Communications Board or Unit communications cables may not satisfy these standards. In such a case, commercially available ferrite cores must be placed on the communications cable or other appropriate countermeasures must be provided external to the PC. Recommended Ferrite Cores The following ferrite core (data line noise filter) is recommended: 0443-164151 by Fair-Rite Products Corp. Low impedance, 25 MHz: 90 Ω, 100 MHz: 160 Ω Recommended Mounting Method Mount the core on one turn of the communications cable, as shown in the following illustration. Mount the cores as lost to the end of the communications cable as possible, as shown in the following illustration. Serial Communications Unit/Board xvi SECTION 1 Introduction This section introduces the hardware and software functions of the Serial Communications Board and the Serial Communications Unit, including the communications modes, system configurations, and specifications. 1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-1 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2-2 Serial Communications Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Protocol Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-1 Host Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-2 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-3 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3-4 Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-1 Serial Communications Boards and Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4-2 Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6-1 Serial Communications Boards and Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6-2 Protocol Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Comparison to Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting the Serial Communications Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9-2 Explanation of Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3 3 4 5 5 6 7 8 8 8 8 11 17 17 18 22 27 28 28 29 1 Section Using this Manual 1-1 1-1 Using this Manual This manual is structured to provide information on Host Link, protocol macro, and 1:N NT link communications in functional units, as would be required in actual applications. You should read Section 1 Introduction first, and then read information in the rest of the manual and related manuals as required by your specific application. Information Section or Manual Overview and appearance of the Serial Communications Boards and Serial Communications Unit 1-2 Overview Overview, features, and specifications of serial communications 1-3 Protocol Overview 2-1 Component Names and Functions 1-4 Features 1-6 Specifications 4-1 Host Link Communications 5-1 Overview of the Protocol Macro Functions 6-1 Overview of 1:N NT Links Basic procedures and operations 1-9 Basic Operating Procedure Selecting serial communications modes 1-8 Selecting the Serial Communications Mode System configurations for serial communications modes Memory Area allocations to the Serial Communications Boards and Serial Communications Unit 1-5 System Configurations Installing and wiring the Serial Communications Boards and Serial Communications Unit Memory Area allocations to individual serial communications modes Section 3 Installation and Wiring Communications timing for slave-initiated Host Link communications Ladder diagram programming in protocol macros 2-3 I/O Memory Allocations 4-2, 5-2, and 6-2 Setup Area Allocations 4-3, 5-3, and 6-3 Auxiliary Area and CIO Area Allocations 4-4 Communications Timing 5-4 Using Protocol Macros Loopback tests for ports Section 7 Loopback Test Changing the communications port settings during operation Troubleshooting and maintenance Appendix O Changing Communications Port Settings Using STUP(237) Section 8 Troubleshooting and Maintenance The contents of standard system protocols and connection methods to OMRON components Details on Host Link communications (including ladder diagram programming for slave-initiated communications) Appendix A to Appendix N Details on C-mode commands Details on FINS commands Details on the protocol macro function 2 2-2 Data Exchange with the CPU Unit SYSMAC CS1-series CS1G/H-CPUjj-E, CS1W-SCB21/41, CS1W-SCU21 Communications Commands Reference Manual (W342) SYSMAC WS02-PSTC1-E CX-Protocol Operation Manual (W344) Section Overview 1-2 1-2 Overview This section gives an overview of the Serial Communications Boards and the Serial Communications Unit. 1-2-1 Serial Communications Boards Serial Communications Boards are Inner Boards for the CS1-series PCs. One Board can be installed in the Inner Board slot of a CPU Unit. Two serial communications ports are provided for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). This makes it possible to easily increase the number of serial communications ports for a CS1-series PC. Serial Communications Board Inner Board slot The following two models are available: Models CS1W-SCB21 Two RS-232C ports Connectable Devices General-purpose external device CS1W-SCB41 One RS-232C port + one RS-422A/485 port RS-232C port RS-232C port RS-232C port RS-422A/485 port The following serial communications modes are supported by the Serial Communications Unit: Host Link (SYSMAC WAY), protocol macro, 1:N NT Link, and loopback test modes. The devices shown in the following diagram can be connected. Programmable Terminal (PT) Programming Device (excluding Programming Console) Host computer Serial Communications Board CPU Unit General-purpose external device Programmable Terminal (PT) Programming Host computer Device (excluding Programming Console) Note A 1:1 NT Link is not supported. 3 Section Overview 1-2 1-2-2 Serial Communications Unit The Serial Communications Unit is a CS1-series CPU Bus Unit. One or more Units can be mounted to the CPU Unit or a CS1 Expansion Rack. A total of up to 16 CPU Bus Units can be controlled by one CPU Unit. Two serial communications ports are provided for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Console). This makes it possible to easily increase the number of serial communications ports for the CS1-series PC. Serial Communications Unit Model CS1W-SCU21 (Two RS-232C ports) RS-232C port RS-232C port Connectable Devices General-purpose external device The following serial communications modes are supported by the Serial Communications Boards: Host Link (SYSMAC WAY), protocol macro, 1:N NT Link, and loopback test modes. The devices shown in the following diagram can be connected. Programmable Terminal (PT) Programming Device (excluding Host computer Programming Console) Serial Communications Unit General-purpose external device Programmable Terminal (PT) Programming Device (excluding Programming Console) Host computer Note A 1:1 NT Link is not supported. 4 CPU Unit Section Protocol Overview 1-3 1-3 Protocol Overview A Serial Communications Board is an Inner Board that provides RS-232C and/ or RS-422A/485 serial communications ports. An Inner Board is an option and is installed in the CPU Unit. A Serial Communications Unit is a CPU Bus Unit that provides two RS-232C serial communications ports. The following four serial communications modes can be used as required for each serial communications port. • Host Link: For connections between host computers and PCs • Protocol macro: For communications between PCs and general-purpose external devices • 1:N NT Link: For communications between PCs and Programmable Terminals (PTs) • Loopback test: For testing the communications ports Product Model number Serial Communications Boards CS1W-SCB21 Serial Communications Unit CS1W-SCU21 Serial communications ports RS-232C RS-232C RS-232C RS-422A/485 CS1W-SCB41 RS-232C RS-232C Device to be connected Serial communications mode Host Link OK OK OK OK (See note 1.) OK OK Host computer or Programming Device Protocol macro OK OK OK OK 1:N NT Link (See note 2.) OK OK OK OK Loopback test OK OK OK OK OK OK General-purpose external device OK OK PT OK OK None A connection example for each serial communications mode is shown in the following sections for a Serial Communications Unit. The examples apply equally as well to the Serial Communications Boards. Note 1. A 4-wire connection must be used when using Host Link communications for an RS-422A/485 connector. 2. A 1:1 NT Link is not supported. 1-3-1 Host Link Mode In Host Link mode, C-mode commands (Host Link commands) or FINS commands can be sent from a host computer to read or write I/O memory in the PC or to control the PC’s operating modes. The host computer can be a personal computer or a Programmable Terminal. The FINS commands are sent with other data, such a Host Link header and terminator. In Host Link mode, SEND(090), RECV(098), and CMND(490) instructions can be used to send FINS commands from PC to the host computer to read data, write data, or perform other operations. This is called slave-initiated communications or unsolicited communications. The FINS commands are sent with other data, such a Host Link header and terminator. Note 1. FINS commands can be sent across up to three different networks (counting the local network) to a PC on a remote network or to a host computer connected to a PC on a remote network. 2. Programming Devices can also be connected in Host Link mode. 5 Section Protocol Overview 1-3 Sending C-mode Commands Host Link C-mode (Host Link) command Sending FINS Commands FINS commands can also be sent to PCs on remote networks. FINS command Host Link Host Link FINS command FINS command Host Link terminator Host Link terminator Host Link header Host Link header Remote network (Controller Link or Ethernet) Slave-initiated Communications SEND(090), RECV(098), CMND(490) SEND(090): Sends data to host computer RECV(098): Reads data from host computer CMND(490): Executes any FINS command Host Link FINS command Host Link terminator Host Link header Slave-initiated FINS commands can also be sent from PCs on remote networks. SEND(090), RECV(098), CMND(490) Host Link Remote network (Controller Link or Ethernet) FINS command Host Link terminator FINS command Host Link header 1-3-2 Protocol Macros Data transfer procedures (protocols) with general-purpose external devices are created using the CX-Protocol to match the communications specifications (half-duplex or full-duplex, and start-stop synchronization) of the external device. These protocols are stored in the Serial Communications Boards or the Serial Communications Unit, and enable data to be exchanged with general-purpose external devices simply by executing the PMCR(260) instruction in the CPU Unit. 6 Section Protocol Overview 1-3 Standard system protocols for exchanging data with OMRON devices (such as Temperature Controllers, Intelligent Signal Processors, Bar Code Readers, and Modems) are provided as a standard feature in the Serial Communications Boards, the Serial Communications Unit, and the CX-Protocol. The CX-Protocol can also be used to change the standard system protocols according to user requirements. PMCR(260) Serial Communications Unit Send/receive sequence Protocol General-purpose external device 1-3-3 1:N NT Links A PC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated to the Status Control Areas and the Status Notification Areas used by the PTs, as well as to display objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PTs, without the use of a ladder diagram programming in the PC. Up to eight PTs can be connected to a PC. Note The user does not need to be aware of NT Link commands. The user only has to allocate the PC memory to the PTs. Serial Communications Unit Serial Communications Unit NT Link (Set to 1:N) PT Note 1:N NT Link PT 1. The serial port on the PT must be set to a 1:N NT Link. 2. The Serial Communications Boards and Units do not support 1:1 NT Links. The NT Link must be set to 1:N even if only one PT is connected. Connection is not possible to PTs that do not support 1:N NT Links. 3. The NT20S, NT600S, NT30, NT30C, NT620, NT620C, and NT625C cannot be used if the cycle time of the CPU Unit is 800 ms or longer (even if only one of these PTs is used in a 1:N NT Link). 4. The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board or Unit ports. They can be used only by connecting to the peripheral port or RS-232C port on the CPU Unit. 5. Set a unique unit number for each PT connected to the same PC. If the same unit number is set for more than one PT, malfunctions will occur. 6. NT Link serial communications are unique and are not compatible with other serial communications modes. 7 Section Features 1-4 1-3-4 Loopback Test A connector with a loopback connection is attached to the specified serial communications port to perform loopback tests. Data is sent to this port, and the communications circuit is tested by comparing the transmitted data and the data returned by loopback. Note This loopback test is performed inside the specified serial communications port. It is not a loopback test using the RS-232C or RS-422A/485 communications path. Loopback test Loopback test switch The loopback test results are stored. 1-4 Features This section describes the features of the Serial Communications Boards, the Serial Communications Unit, and the protocols. 1-4-1 Serial Communications Boards and Units Serial Communications Board A Serial Communications Board is installed as an option in a CPU Unit. Two serial communications ports can thus be added without using an I/O slot. There are two types of Serial Communications Boards: One with two RS-232C ports and one with one RS-232C and one RS-422A/485 port. The RS-422A/485 port can be used for a 1:N connection with general-purpose external devices without using Link Adapters to support the protocol macro function or NT Link function. Serial Communications Unit A total of up to 16 CPU Bus Units can be mounted on the CPU Rack or an Expansion Rack. The total of 16 must include all Serial Communications Units and all other CPU Bus Units. The PC can thus be expanded to provide additional serial communications ports as required by the system. 1-4-2 Protocols Host Link Communications Host Link communications are supported by all CS1-series CPU Units. Serial Communications Boards and Units can be used to connect a single PC to more than one host computer for Host Link communications, including slave-initiated communications. Host Link communications provide the following features. Connect One Computer to Multiple PCs An RS-422A/485 port can be used to connect one host computer to up to 32 CS1-series PCs. Computer Monitoring and Control of PCs Host Link communications enable the host computer to monitor or control PC operations and to read and write I/O memory in the PCs. FINS Commands for Complete Control In addition to C-series (Host Link) commands, FINS commands are also supported. FINS commands give you the power to control CS1-series PC functionality. Redundant Error Checking Both vertical and horizontal (FCS) parity checks are performed on communications data to achieve essentially error-free communications. Combining error checking and retry processing goes one step further to eliminate nearly all the effects of communications problems. Simultaneous Usage of Both Ports Each Serial Communications Board and Unit provides two serial communications ports that can be used simultaneously to connect to two different host computers. A total of up to 16 CPU Bus Units, including the Serial Communications Units, can be mounted to one PC. If all 16 CPU Bus Units are Serial Communications Units, then up to 32 ports can be added. 8 Section Features 1-4 Slave-initiated Communications Communications can be performed either by sending a command from a host computer and having the PC return a response, or by sending a command from a PC and having the computer send a response. Starting communications from a slave is called unsolicited communications, and is made possible through the SEND(090), RECV(098), and CMND(490) instructions. These can be used to send FINS commands to a host computer connected locally or to a host computer connected to a remote network up to three networks away (counting the local network). Send FINS Commands to Remote Networks A FINS command contained within a Host Link header and terminator can be sent using Host Link communications to PCs connected not only on Host Link networks, but also other interconnected remote networks up to three networks away (counting the local network). Various types of networks can exist between the source of the command and the destination of the command. Bridge Host Link Ethernet Network Controller Link Network Controller Link Network Gateway Send FINS Commands to Computers Connected to Remote PCs Host Link A FINS command contained within a Host Link header and terminator can be sent using Host Link communications to a host computer connected to a PC on a remote network up to three networks away (counting the local network, but not counting the final Host Link connection). Various types of networks can exist between the PC sending the command and the destination of the command. Bridge Ethernet Network SEND(090), RECV(098), CMND(490) Controller Link Network Controller Link Network Gateway Protocol Macros The main features of the protocol macro functions are described below. For details, refer to the CX-Protocol Operation Manual (W344). Wide Range of Communications Protocols Communications are possible with virtually any general-purpose external device, provided it has an RS-232C or RS-422A/485 port, supports half-duplex or full-duplex communications, and supports start-stop synchronization. Send Frames and Receive Frames Matching Specifications Send frames (command + data and other send frames) and receive frames (response and other frames) can be created and registered according to the communications frame specifications of the external device. Communications-related Functions Error check code calculations, frame length calculations during sending, and ASCII⇔Hexadecimal conversion of numeric data are supported. Send/Receive Monitoring Receive wait monitoring, receive completion monitoring, and send completion monitoring are supported. If monitoring times are exceeded, send/receive can either be terminated, or retry processing can be performed. 9 Section Features 1-4 Retry Processing Send/receive retry processing can be automatically executed when an error occurs, simply by setting the number of retries. PC Read/Write Variables in Send Frames and Receive Frames Variables for reading PC memory can be included in the actual send frames. These can be used as destination addresses or data when reading PC data while sending. Variables for writing to PC memory can be also included in the actual receive frames. These can be used to write the contents of destination addresses or data to the PC during reception. Switch 1:N Communications or the Data Write Destinations Using Repeat Processing Repeat processing (repeat counters) for send/receive processing can be specified in communications sequences. This enables the same data to be sent by switching destination addresses during communications 1:N (N = 32 max. due to restrictions in the physical layer) or by switching the PC memory write destination addresses during data reception. PC Interrupts During Data Reception An interrupt can be created in the PC’s CPU Unit during data reception, and an interrupt program can be executed in the CPU Unit. (The PC interrupt function is supported only for the Serial Communications Boards. This function cannot be used with Serial Communications Units.) Next Process Switching According to Receive Data The contents of up to 15 set of expected receive data can be compared with the receive data to determine the next process. New Error Check Codes LRC2 (two’s complement of LRC), and SUM1 (one’s complement of SUM) have been added to the error check codes. Step Queuing for Sync Signal from the PC At any step of the send/receive sequence, the next process can be made to wait until a sync signal from the PC’s CPU Unit has been input. This enables processing, such as data manipulations, to be performed in the CPU Unit during the send/receive sequence. Half-duplex or Full-duplex Transmissions With the conventional protocol macro functions, only half-duplex transmissions were possible. With half-duplex mode, the reception buffer is cleared immediately after the send operation is completed. Therefore, if there was a rapid response from the remote device, for example, the data received between data sending and the completion of the send operation could not be accessed as receive data by the next receive operation. Support for the full-duplex transmissions enables all the data received in a sequence to be accessed. Data can also be received from a remote device while sending. Note Full-duplex transmissions can be used with either RS-232C or RS-422A/485 as long as 1:1, 4-wire connections are used. Full-duplex transmissions cannot be used with 1:N connections or 2-wire connections. Clear Reception Buffer at Any Time With full-duplex mode, the reception buffer is cleared only immediately before a send/receive sequence is executed. When a reception or other fault occurs, the receive data can be cleared at any time using the reception buffer clear (FLUSH) command. Control ER Signal at Any Time With a connection to a modem, the ER signal is used to show the send/receive enabled status of a Serial Communications Board or Unit (Data Terminal Equipment (DTE)). In conventional operations, the ER signal could be turned ON only while a send/receive sequence was being executed. Improving this function has enabled the ER signal to be turned ON or OFF at any time during a send/receive sequence. This enables modem connections and disconnections to be performed by a protocol macro. 10 Section System Configurations 1-5 The ER signal can also be kept ON, even after a send/receive sequence has been completed. In this case, the ER signal remains ON, even after it has been switched to a different serial communications mode (for example, Host Link). This function enables remote programming and monitoring to be performed using remote Programming Devices, by switching to the Host Link mode with the STUP(237) instruction once the connection has been made with the modem. 1-5 System Configurations This section explains the system configuration supported by each serial communications mode. Host Link Communications PC:Computer 1:1 Connection configuration Connection to Serial Communications Board. Port: RS-232C Required devices CS1W-SCB21 Connected Possible serial commu- command flow nications port/ Remarks Host computer Port 1 or 2 to PC: C-mode or FINS commands CS1W-SCB41 Port 1 Note 1. Note 3. PC to Host computer: FINS commands only Note 3. Note 2. NT-AL001-E NT-AL001-E Resistance ON, 5-V power NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 5-V power For supply NT-AL001-E Link Adapter Resistance ON Connection to Serial Communications Unit. CS1W-SCU21 Port 1 or 2 Note 1. Note 3. Note 3. Note 2. NT-AL001-E Resistance ON, 5-V power 1:1 Port: RS-422A/ 485 NT-AL001-E Resistance ON Connection to Serial Communications Board. NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 5-V power supply For NT-AL001-E Link Adapter CS1W-SCB41 Port 2 Note 3. Note 2. NT-AL001-E Resistance ON, 5-V power Resistance ON NT-AL001-E RS-232C ⇔ Converting Link RS422A/485 Adapter 5-V power supply For NT-AL001-E Link Adapter Host computer to PC (4-wire only): C-mode or FINS commands PC to Host computer (4-wire only): FINS commands only 11 Section System Configurations PC:Computer 1:N Port: RS-232C Connection configuration Connection to Serial Communications Board. Note 3. Required devices CS1W-SCB21 Note 2. NT-AL001-E Resistance ON Resistance ON, 5-V power CS1W-SCB41 Connected Possible serial commu- command flow nications port/ Remarks Host computer Port 1 or 2 to PC (RS-422A/485 section: 4-wire): C-mode or Port 1 FINS commands NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 5-V power For supply NT-AL001-E Link Adapter Connection to Serial Communications Unit. CS1W-SCU21 1-5 PC to Host computer: Commands cannot be sent. Port 1 or 2 Note 2. Note 3. NT-AL001-E Resistance ON Resistance ON, 5-V power 1:N Port: RS-422A/ 485 Connection to Serial Communications Board. NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 5-V power For supply NT-AL001-E Link Adapter CS1W-SCB41 Resistance ON, 5-V power Note 4. Note 2. Resistance ON NT-AL001-E RS-232C ⇔ Converting Link RS422A/485 Adapter 5-V power supply 12 Port 2 Note 3. For NT-AL001-E Link Adapter Host computer to PC (4-wire only): C-mode or FINS commands PC to Host computer: Commands cannot be sent. Section System Configurations PC:Computer Host computer to Network PCs, 1:N Connection configuration Required devices Connection to Serial Communications Board or Serial CS1W-SCB21, Communications Unit CS1W-SCB41, or CS1W-SCU21 Connected Possible serial commu- command flow nications port/ Remarks Host computer Port 1 or 2 to PC: FINS commands only Port 1 or 2 Controller Link or Ethernet network 1-5 Communications Unit: Controller Link Unit or Ethernet Unit. PC to Host computer: FINS commands only (RS-422A/485: 4-wire only) or Communications can be sent across three different networks (counting the local network, but not including a Host Link connection). Routing tables must be set in the PCs. Gateway or bridge Host Link Network 3 Network 1 Network 2 Gateway Note 1. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. 2. The combined cable length for RS-422A/485 is 500 m including branch lines. 3. The maximum cable length is limited to 2 m when an NT-AL001-E Link Adapter is connected. 4. Branch lines must be a maximum of 10 m long. 5. Four-wire connections must be used for RS-422A/485 connections with Host Link communications. 6. “Resistance ON” indicates that the terminating resistance must be turned ON. 7. “5-V power” indicates that a 5-V power supply is required for the Link Adapter. Refer to the Link Adapter manual for details. Be sure that the power supply has sufficient capacity and accuracy and wire it away from high-power lines and another sources of noise. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications Board or Unit because power is supplied from pin 6 of the connector. 8. The maximum baud rate of the NT-AL001-E Link Adapter is 64 Kbps. Do not use 115.2 Kbps when a Link Adapter is connected. 13 Section System Configurations 1-5 Protocol Macros PC: External device 1:1 Port: RS-232C Connection configuration Required devices Connection of a Serial Communications Board to a device with an RS-232C or RS-422A/485 port. CS1W-SCB21 Connected serial communications port/ Remarks Port 1 or 2 CS1W-SCB41 Port 1 Note 1. RS-232C RS-232C interface Note 3. Note 2. NT-AL001-E RS-232C RS-422A/485 Resistance ON Note 2. Note 3. NT-AL001-E Resistance ON 5-V power RS-232C interface NT-AL001-E RS-232C RS-422A/485 Resistance ON RS-422A/485 Resistance interface ON Connection of a Serial Communications Unit to a device with an RS-232C or RS-422A/485 port. NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 5-V power For supply NT-AL001-E Link Adapter CS1W-SCU21 Port 1 or 2 Note 1. RS-232C RS-232C interface Note 3. Note 2. NT-AL001-E RS-232C RS-422A/485 Resistance ON Note 2. Note 3. NT-AL001-E Resistance ON 5-V power NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 RS-232C interface NT-AL001-E RS-232C RS-422A/485 Resistance ON 5-V power supply For NT-AL001-E Link Adapter CS1W-SCB41 Port 2 RS-422A/485 interface Resistance ON 1:1 Connection of a Serial Communications Board to a device with an RS-232C or RS-422A/485 port. Port: Note 2. RS-422A/ 485 RS-422A/485 interface RS-422A/485 Resistance ON Resistance ON Note 2. NT-AL001-E Resistance ON 14 Note 3. RS-232C RS-422A/ Resistance ON 485 5-V power RS-232C interface NT-AL001-E Convert Converting Link between Adapter RS-232C and RS-422A/485 5-V power For supply NT-AL001-E Link Adapter Section System Configurations PC: External device 1:N Port: RS-232C Connection configuration Connection of a Serial Communications Board to a device with an RS-232C or RS-422A/485 port Note 3. 1-5 CS1W-SCB21 Connected serial communications port/ Remarks Port 1 or 2 CS1W-SCB41 Port 1 Required devices RS-422A/485 interface Note 2. NT-AL001-E RS-232C Resistance ON RS-422A/485 Resistance ON Note 3. RS-422A/485 interface NT-AL001-E RS-232C B600-AL001 RS-422A/485 NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 Resistance ON Note 2. Resistance ON Note 4. Note 3. RS-232C Resistance ON RS-232C interface NT-AL001-E NT-AL001-E B500-AL001 Link Adapter For RS-422A/485 branching 5-V power supply For NT-AL001-E Link Adapter CS1W-SCU21 Port 1 or 2 RS-232C Note 2. RS-232C RS-422A/485 Resistance ON 5-V power RS-232C Note 3. Connection of a Serial Communications Unit to a device with an RS-232C or RS-422A/485 port. RS-422A/485 interface Note 3. Note 2. NT-AL001-E RS-232C Resistance ON RS-422A/485 Resistance ON Note 3. RS-422A/485 interface NT-AL001-E RS-232C NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 B500-AL001 RS-422A/485 Resistance ON Note 2. Note 4. B500-AL001 Link Adapter For RS-422A/485 branching 5-V power supply For NT-AL001-E Link Adapter Resistance ON Note 3. NT-AL001-E RS-232C Resistance ON Note 2. RS-422A/485 NT-AL001-E RS-232C RS-232C RS-232C interface Resistance ON RS-232C Note 3. 5-V power 15 Section System Configurations PC: External device 1:N Port: RS-422A/ 485 Connection configuration Connection of a Serial Communications Board to a device with an RS-232C or RS-422A/485 port Required devices CS1W-SCB41 1-5 Connected serial communications port/ Remarks Port 2 RS-422A/485 interface Resistance ON RS-422A/485 Note 2. Resistance ON RS-422A/485 interface B500-AL001 Resistance ON RS-422A/485 Note 2. Note 4. NT-AL001-E Resistors ON NT Link Communications 16 For RS-422A/485 branching 5-V power supply For NT-AL001-E Link Adapter RS-232C interface RS-232C Resistance ON 5-V power B500-AL001 Link Adapter Resistance ON Note 2. RS-422A/485 Note NT-AL001-E Converts Converting Link between Adapter RS-232C and RS-422A/485 RS-232C RS-232C Note 3. 1. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. 2. The combined cable length for RS-422A/485 is 500 m including branch lines. 3. The maximum cable length is limited to 2 m when an NT-AL001-E Link Adapter is connected. 4. Branch lines must be a maximum of 10 m long. NT Link communications are used to connect an OMRON Programmable Controller (PC) and Programmable Terminal (PT). Up to 8 PTs can be connected to one PC. For details on the system configuration, refer to the user’s manual for the PT. Section Specifications 1-6 1-6 Specifications 1-6-1 Serial Communications Boards and Unit Device name Serial Communications Board Classification Model number Serial communications ports Protocol Number of mountable Boards/Units Data exchange with the CPU Unit Inner Board Serial Communications Unit CPU Bus Unit CS1W-SCB21 CS1W-SCB41 CS1W-SCU21 Port 1 RS-232C RS-232C RS-232C Port 2 RS-232C RS-422A/485 RS-232C Port 1 Port 2 CPU Unit CPU Rack Host Link, protocol macro, NT Link, or loopback test can be selected for each port. Expansion Rack None None A total of up to 16 Units, including all other CPU Bus Units. No restrictions on the mounting location. Ordinary refreshing of software switches and status Allocated 25 words of the 100 words in the Inner Board CIO Area (constant data exchange with the CPU Unit) Allocated 25 words of the 25 words in the CPU Bus Unit CIO Area (constant data exchange with the CPU Unit) Transfer from the CPU Unit set by the system Of the 768 words in the Inner Board DM Area, each serial port is allocated 10 words (total 20 words). Of the CPU Bus Unit DM Area, each serial port is allocated 10 words (total 20 words). Data is transferred from the CPU Unit at the following times: Data is transferred from the CPU Unit at the following times: D Startup or restart D Startup or restart D Ladder instruction: STUP(237) D Ladder instruction: STUP(237) D Port Settings Changing Flag turns ON (Auxiliary Area) D Port Settings Changing Flag turns ON (Auxiliary Area) Supporting CPU Units Applicable Backplanes One Board per Inner Board slot None High-speed: CS1H-CPU67/CPU66/CPU65/CPU64/CPU63 Standard: CS1G-CPU45/CPU44/CPU43/CPU42 None CPU Backplanes: CS1W-BC103/BC083/BC053/BC033 /BC023 CS1 Expansion Backplanes: CS1W-BI103/BI083/BI053/BI033 Current consumption (see note) 280 mA + x 360 mA + x 290 mA + x Weight 100 g max. 110 g max. 200 g max. Note The current consumption is for one Serial Communications Board or Unit. When an NT-AL001-E Link Adapter is connected to the Serial Communications Board or Unit, power is supplied to the Link Adapter from the Board or Unit. A current consumption of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply. 17 Section Specifications 1-6 1-6-2 Protocol Specifications Host Link Specifications Item Description Communications mode Half-duplex (Full-duplex for slave-initiated communications) Synchronous mode Start-stop synchronization (asynchronous mode) Baud rate (see note 1) RS-232C port and RS-422A/485 ports: 1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps Communications distance (see note 1) Connection configuration Default setting: 9,600 bps RS-232C port: 15 m max. (see note 2) RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using an Converting Link Adapters.) RS-422A/485 port: 1:N (N = 32 Units max.) Number of connected Units Frame structure 32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection) Error check codes Vertical parity: Even, odd. or none FCS (horizontal parity converted to ASCII) Command flow Commands Contents Host computer C-mode commands 1:1 or 1:N communications with directly connected to PC PCs (The specified frame format must be prepared on the host computer and then sent.) Command flow and support C-mode commands FINS commands PC to host computer Header: @, address: (host link unit number) 0 to 31 (BCD), data: header code + text, error check code: FCS, terminator: *+CR Header: @, address: (host link unit number) 0 to 31 (BCD), data: header code (always “FA”) + FINS header + FINS command + text, error check code: FCS, terminator: *+CR FINS commands (in Host Link protocol) FINS commands (in Host Link protocol) 1:1 or 1:N communications with directly connected PCs. Communications using SEND(090), RECV(098), and CMND(490) from CPU Unit. The host computer must interpret the commands and return a response in the correct format. Connection between the host computer and PC must be 1:1. Note 1. Confirm the baud rates and communications distance supported by connected devices. 2. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. Protocol Macro Function Specifications Item Number of protocols Number of sequences Per protocol 20 max. 1,000 max. Number of sequences Number of messages Number of reception matrixes Sequence execution condition Description Can be created and registered with the Protocol Support Tool (CX-Protocol). 60 max. 300 max. 100 max. Communications mode Using the CPU Unit’s PMCR(260) instruction (specifying the sequence number) Half-duplex or full-duplex Synchronous mode Start-stop synchronization (asynchronous mode) 18 Section Specifications Item Description Baud rate (see note 1) RS-232C port and RS-422A/485 ports: 1,200/2,400/4,800/9,600/19,200/38,400 bps Communications distance (see note 1) Connection configuration Number of connected Units Maximum number of data exchange words between PC and protocol macro function Sequence contents (step common parameters) 1-6 Operand setting Default setting: 9,600 bps RS-232C port: 15 m max. RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a Converting Link Adapter.) RS-422A/485 port: 1:N (N = 32 Units max.) 32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection) 250 words Including the word that specifies the number of words (1 word) Link word setting 500 words O1, O2, I1, and I2: 500 words total Direct setting 500 words Maximum number of words per data attribute Number of steps per sequence Transmission control parameters Response notification method (operand) 16 max. X-on/X-off flow, RS/CS flow, delimiter control, or contention control, and modem control can be selected. Scan notification or interrupt notification (i.e., writing the receive data in the I/O memory area specified in the 4th operand of the PMCR(260) instruction) can be selected. Scan notification: Writes the receive data to I/O memory during CPU Unit scanning. Interrupt notification: Writes the receive data to I/O memory as soon as it is received, and at the same time specifies the execution of the interrupt program for the CPU Unit. Monitoring time during send/receive processing Link word setting Note The interrupt notification method can be executed only by a Serial Communications Board. It cannot be used for a Serial Communications Unit. Scan method Board and Unit (fixed) Interrupt Board only (See note 2.) notification Interrupt Board only (See note 2.) notification for reception case number Receive wait, receive completion, or send completion can be monitored. Setting range: 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 minutes Area in which data is exchanged between the CPU Unit and the Serial Communications Board or Unit during Communications Board or Unit refreshing. Two areas are possible for each device: An area for storing receive data and an area for storing send data. 19 Section Specifications Item Step contents Description Commands Send only (SEND), receive only (RECV), send and receive (SEND&RECV), wait (WAIT), reception buffer clear (FLUSH), ER-ON (OPEN), or ER-OFF (CLOSE) Repeat counter Retry count 1 to 255 times 0 to 9 (Only when the command is SEND&RECV) 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 minutes (Only when the command is SEND or SEND&RECV) When receive processing is completed (when the receive data is stored in the area specified in the 4th operand of the PMCR(260) instruction), whether or not to store the received messages can be selected. When a step has ended normally, End (sequence completed), Next (proceed to the next step No.), Goto (go to the specified step No.), or Abort (interrupt the step and terminate that sequence) can be selected. Send wait time With or without response write (operand) Next processing Error processing Send message When a step has ended abnormally, End, Next, Goto, or Abort can be selected. Consists of a header (*1), address (*2), length, Data sent to the data (*2), error check code (*3), and terminator specified address when the command (*1). is SEND or For an explanation of *1, *2, and *3, see the next SEND&RECV. page. Receive message Data sent from the specified address when the command is RECV or SEND&RECV. Reception matrix When the command is RECV or SEND&RECV, sets the expected receive messages (15 max.), and switches to the next processing according to the message received. Note 20 1-6 Specifies the receive messages and the next processing for each of cases No. 00 to No. 15. Of the maximum 16 cases, one case must be set as “Other” in the receive messages (in addition to the set receive messages). 1. The baud rate and the communications distance sometimes depend on the remote device. 2. A macro syntax error will occur if the interrupt notification method is executed for a Serial Communications Unit. Section Specifications Item Message unit contents 1-6 Description *1: Header and terminator data attributes Constant ASCII data, hexadecimal data, or control code *2: Data attributes of addresses and data in send/ receive messages Constant Variable ASCII data, hexadecimal data, or control code (with an address, no control code is possible) No conversion, conversion to ASCII data, or conversion to hexadecimal data (the read/write direction can be specified) Desig(X, Y) nation X: Effective address (where read from, or where written to) method Y: Data size (1 to 1,000) X Note The data size is the number of bytes on the transmission path. Word Word read (I/O Specify using Set leading designation memory to address + n the 3rd opersend data) (The linear exand of the pression aN + PMCR(260) b, including reinstruction. peat counter Specify using N, is also posa link word. sible for n.) I/O memory direct designation Word write (re- Specify using ceive data to the 4th operI/O memory) and of the PMCR(260) instruction. Specify using a link word. I/O memory direct designation Wild card * Repeat counter N Any data or address can be received (only in receive messages) 21 Section Comparison to Previous Products Item Message con- *2: tents Data attributes of addresses and data in send/ receive messages 1-7 Description Variables Y Linear expression including repeat counter aN + b Wild card * a: 0 to 1000; b: 1 to 1000 N: Repeat counter value Can be received regardless of the length (only in receive messages) Word designa- Word read (I/O Specify using Set leading tion memory to address + n the 3rd opersend data) (The linear exand of the pression aN + PMCR(260) b, including reinstruction. peat counter Specify using N, is also posa link word. sible for n.) I/O memory direct designation *3: Error check codes Maximum length of send/receive messages LRC, LRC2, CRC-CCITT, CRC-16, SUM, SUM1, and SUM2 can be calculated. 1,000 bytes. (A maximum length between 200 and 1,000 bytes can be set in the Setup Area.) Maximum number of data attributes registered in one message 96 attributes (see note 1) Maximum number of 30 attributes (see note 2) write data attributes registered in one message Trace function A total of up to 1,700 bytes (characters) of time-series data can be traced in send and receive messages. Changes to the step No. and control signals such as RS and CS can also be traced. Note 1-7 1. The CX-Protocol can be used to register up to 96 attributes per message. 2. A macro syntax error will occur when the protocol macro is executed if more than 31 write attributes are registered in one message. Comparison to Previous Products The following tables show a comparison between the CS1-series Serial Communications Boards and Unit and the C200HX/HG/HE Communications Boards and Host Link Units. Item Model 22 C200HX/HG/HE CS1 Boards C200HW-COM02/COM03/COM04-E /COM05-E/COM06-E Communications Boards CS1W-SCB21/SCB41 Serial Communications Board Units C200H-LK101-PV1/LK201-V1 Host Link Unit CS1W-SCU21 Serial Communications Unit Section Comparison to Previous Products Item Communications ports Boards C200HX/HG/HE 1-7 CS1 2 RS-232C ports 2 RS-232C ports or or 1 RS-232C and 1 RS422A/485 port 1 RS-232C and 1 RS422A/485 port or 1 CPU bus I/F and 1 RS-232C port or 1 RS-232C port or Units 1 RS-422A/485 port 1 RS-232C port 2 RS-232C ports or 1 RS-422A port or 1 optical fiber port Number mountable per PC Serial communications modes Boards Boards Units Host Link communications Protocol macros NT Link communications No-protocol communications 1:1 links Serial communications modes Units Baud rate 1 Board 16 Units (CPU Rack or CS1 Expansion Rack, but total of all CPU Bus Units must be 16 or less) Up to 4 ports maximum, 6 ports including those on CPU Unit. Up to 32 ports maximum, 34 ports including those on CPU Unit. Supported. (See note 1.) Supported. (See note 1.) Supported (except for COM02 and COM03). Supported. Supported. Supported. Supported. Supported (unified with 1:N NT Links). Not supported (included with protocol macros). Not supported (supported by Controller Link Units or PC Link Units). Loopback tests Not supported. Supported. Host Link communications Protocol macros NT Link communications No-protocol communications 1:1 links Supported. Supported. Not supported. Not supported. Supported. Supported (unified with 1:N NT Links). Not supported (included with protocol macros). Not supported (supported by Controller Link Units or PC Link Units). Loopback tests Not supported. Supported. Host Link communications Protocol macros 19,200 bps max. 115,200 bps max. 19,200 bps max. Standard NT link 38,400 bps max. Standard NT link, high-speed NT link (see note 2) Supported. Not supported. Boards: Data can be sent with TXD(236) instruction. Supported. Supported. Boards and Unit: FINS commands can be sent using SEND(090), RECV(098), and CMND(490). NT link (1:N mode) Host Link communications 1 Board 2 Units (CPU Rack or Expansion I/O Rack, but not two slots next to CPU Unit) C-mode commands FINS commands Slave-initiated communications Not supported. Not supported. Units: Not supported. 23 Section Comparison to Previous Products Note 1-7 1. The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Host Link Units and CS1-series Serial Communications Boards/Units. A host computer program previously used for C-series Host Link Units may not function correctly if used for CS1-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS1-series Communications Commands Reference Manual (W342) for details. 2. High-speed NT link is available only with Serial Communications Boards/ Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available. Lot No: 20Z9 Manufactured on December 20th, 1999 The year is indicated with the last digit. In this case, “9” indicates “1999.” Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is “December.” Day of manufacture. In this example, the day is “20.” NT31/631(C)-V2 are the only PTs for which high-speed NT link is supported. The following tables shows the improvements made in the protocol macro function. Protocol Macro Comparison Item Transmission mode Commands C200HX/HG/HE Half-duplex Send only: SEND, receive only: RECV, or send and receive: SEND and RECEIVE CS1 Half or full-duplex Send only: SEND, receive only: RECV, send and receive: SEND and RECEIVE, wait: WAIT, clear reception buffer: FLUSH, ER-ON: OPEN, and ER-OFF: CLOSE WAIT: Progressing to next process controlled by signal from CPU Unit. FLUSH: Clears contents of reception buffer. OPEN: Used for modem control. Keeps ER signal ON even after end of sequence. Reception buffer (per port) Reception buffer flow Start (CTS signal OFF control at Board/Unit to request canceling (RS/CS or Xon/Xoff) send from remote device) Clear (CTS signal ON to request restarting send from remote device) Send/receive message Bytes per send length Bytes per For RS/CS receive flow, Xon/Xoff flow, or delimiter control Other 24 256 bytes CLOSE: Used for modem control. Turns OFF ER signal. 2.5 Kbytes 200 bytes 2 Kbytes At step transition 0.5 Kbytes 256 bytes max. 200 bytes max. 1,000 bytes max. Default: 200 bytes. Setting can be changed to between 200 and 1,000. Reception data is removed from the reception buffer in increments of the size set here. 256 bytes max. Section Comparison to Previous Products Item Reception message length when using wildcard (*) for data length Send/ receive data storage locations and data capacity For RS/CS flow, Xon/Xoff flow, or delimiter control 200 bytes max. CS1 As set above. Other 256 bytes max. Default: 200 bytes. Setting can be changed to between 200 and 1,000. 127 words max. (not including word specifying the number of send words) 250 words max. (including word specifying the number of send words) 127 words max. (not including word specifying the number of receive words) 128 words max. total 250 words max. (including word specifying the number of receive words) 500 words max. total 128 words max. (no conversion) 500 words max. (no conversion) Before executing sequences. Before executing sequences. Before executing RECV processing. Before executing SEND processing. Operand Max. send data size specification Max. receive data size Link word Area 1 specification IN OUT Area 2 IN OUT Direct Max. send or receive specification data size (variable) Reception buffer clearing Half-duplex timing C200HX/HG/HE 1-7 Upon FLUSH command execution. Full-duplex Reception buffer reception processing None Half-duplex Only during RECV processing. Full-duplex None Character trace reception Half-duplex records Full-duplex Recorded except during SEND processing. None. Before executing sequences. Upon FLUSH command execution. Except when executing SEND processing. During sequence execution (reception processing not performed except during sequence execution). During sequence execution (even during SEND processing) 25 Section Comparison to Previous Products Item Transmission control signal operations RTS signal CTS signal ER signal C200HX/HG/HE 1-7 CS1 RTS/CTS flow control: RTS signal turned ON when reception buffer reaches 200 bytes. RTS/CTS flow control: RTS signal turned ON when reception buffer reaches approximately 2 Kbytes. Modem control: RTS signal turned ON when data is sent and turned OFF when send is completed. RTS/CTS flow control: Data send is on standby when CTS signal turns ON; data can be sent when CTS signal turns OFF. Modem control: RTS signal turned ON when data is sent and turned OFF when send is completed. RTS/CTS flow control: Data send is on standby when CTS signal turns ON; data can be sent when CTS signal turns OFF. Modem control: ON when sequence execution is started, OFF when completed. Modem control: ON when sequence execution is started, OFF when completed. Also can be turned ON or OFF as required during modem control by executing OPEN to turn ON the ER signal or by executing CLOSE to turn OFF the ER signal in sequence steps. The ER signal can also be controlled across multiple steps. Turns ON only for modem controls. During RTS/CTS flow control and modem control, the ER signal will be controlled according to modem control operations, the RTS signal will turn ON when sending, and the RTS/CTS flow control operations will be used for the RTS and CTS signals for receptions. Synchronization with CPU Unit after start of sequence execution Send/receive messages Reception length Error check codes Interrupt notification function 26 None No check. No LRC2 or SUM1 checks. Supported. The WAIT command can be used to stop transitions between steps to allow transitions from the CPU Unit. This is useful, for example, to perform processing in the CPU Unit after a specific step but before executing the next step. The length of data set in the expected reception message will be fetched from the reception buffer as the message. LRC2 and SUM1 supported. Boards: Supported. Units: Not supported. Section Selecting the Serial Communications Mode 1-8 1-8 Selecting the Serial Communications Mode Serial Communications Mode Connect Device • Host computer Communicating using an OMRON protocol Host Link Host computer Command interpretation by PC PC Command sent to host computer • OMRON component Reference (Host computer:PC • Communications = 1:1 or 1:N) Commands Reference C-mode commands Manual (W342) or FINS commands • Section 4 Using Host Link Communications (Host computer:PC = 1:1) FINS commands • Section 5 Using Protocol Macros Creating communications frame for a host computer protocol Protocol macro Standard system protocol Protocol macro Use a standard system protocol. User-created protocol Protocol macro Use the CX-Protocol to change a standard system protocol. • CX-Protocol Operation Manual (W344) • Generalpurpose external device Protocol (including no-protocol) used mainly for stop-start synchronous data sending and reception • Programming Device (but not a Programming Console) Remote programming and monitoring via a modem • OMRON Programmable Terminal (PT) High-speed communications for multiple PTs (up to eight). Low-speed communications and only one PT Protocol macro Use the CX-Protocol to create a new protocol. • Section 5 Using Protocol Macros • Appendices B to O • Section 5 Using Protocol Macros • CX-Protocol Operation Manual (W344) • Section 5 Using Protocol Macros • CX-Protocol Operation Manual (W344) Host Link Note When a Programming Device is connected to the PC, the Peripheral Bus can be used by connecting to the ports on the CPU Unit. This is faster than using Host Link communications. 1:N NT Link Note • Section 4 Using Host Link Communications • Communications Commands Reference Manual (W342) • Section 6 Using 1:N NT Links The PT must also be set for a 1:N NT Link. Communications will not be possible if the PT is set for a 1:1 NT Link. Host Link • Section 4 Using Host Link Communications 27 Section Basic Operating Procedure 1-9 1-9 Basic Operating Procedure 1-9-1 Overview An overview of the basic operating procedure is provided here. Refer to the following pages for details. 1, 2, 3... 28 1. Turn OFF the power supply to the PC. 2. Set the unit number if a Serial Communications Unit is being used. Set the unit number using the rotary switch on the front panel of the Unit. 3. Install the Board or Unit. 4. Connect the Unit and the external device(s). 5. Turn ON the power supply to the PC 6. Create the I/O tables if a Serial Communications Unit is being used. Create the I/O tables using a Programming Device, such as a Programming Console. I/O tables must be created when a Serial Communications Unit (CPU Bus Unit) is used with a CS1-series PC. (This aspect of operation is different from using Communications Boards with the C200HX/HG/HE, C200H, or C200HS.) 7. Set the Setup Area allocated in the DM Area. Make settings using a Programming Device, such as a Programming Console, or the CX-Protocol. The following words are allocated as the Setup Area in the DM Area: Board: 20 words beginning at D32000 Unit: 20 of the 100 words starting from (D30000 + 100 unit number) Make the following settings: • Serial communications mode (Host Link, protocol macro, NT Link, or loopback test) • Baud rate • Transmission mode for protocol macros (half-duplex or full-duplex), the maximum length of send/receive data, etc. 8. Make the new settings in the Setup Area valid by performing one of the following. • Turn the power OFF and then ON again. • Restart the Board by turning ON the Inner Board Restart Bit (A60800) or restart the Unit turning ON one of the CS1 CPU Bus Unit Restart Bits (A50100 to A50115, where the bit number corresponds to the unit number). • Restart the port on the Serial Communications Board by turning ON one of the Communications Board Port Settings Change Bits (A63601 for port 1 and A63602 for port 2) or restart the port on the Serial Communications Unit by tuning ON one of the Communications Unit Port Settings Change Bits (A620 to A635: The word will be A620 + unit number and the bit will be bit 01 for port 1 and bit 02 for port 2). • Execute the STUP(237) instruction. The STUP(237) instruction is executed in the ladder program to change the serial communications mode of a serial port. See Appendix O Changing Port Settings Using STUP(237). 9. Execute communications. Use the software switches or the allocated flags and words allocated in the CIO Area in the ladder program to control communications. The following words are allocated in the CIO Area: Board: 25 words from CIO1900 Unit: 25 words from CIO 1500 + 25 unit number Section Basic Operating Procedure 1-9 1-9-2 Explanation of Procedure Turning OFF the Power Check that the PC power has been turned OFF. If the power is ON, turn it OFF. Setting the Unit Number for Serial Communications Units When a Serial Communications Unit is used, set the unit number switch at the top of the front panel of the Unit to between 0 and F. The number that is set will determine which words are allocated as the Setup Area in the DM Area and which words are allocated in the CIO Area. Unit number switch First word in Setup Area allocated in DM Area: m = D30000 + 100 unit number (20 words are used beginning from m, 10 words for each port) Words Unit No. First word allocated in the CIO Area: n = CIO 1500 + 25 unit number (all words are used beginning with n) Unit No. Words Unit No. 0 D30000 to D30099 Unit No. 0 CIO 1500 to CIO 1524 Unit No. 1 D30100 to D30199 Unit No. 1 CIO 1525 to CIO 1549 Unit No. 2 D30200 to D30299 Unit No. 2 CIO 1550 to CIO 1574 Unit No. 3 D30300 to D30399 Unit No. 3 CIO 1575 to CIO 1599 Unit No. 4 D30400 to D30499 Unit No. 4 CIO 1600 to CIO 1624 Unit No. 5 D30500 to D30599 Unit No. 5 CIO 1625 to CIO 1649 Unit No. 6 D30600 to D30699 Unit No. 6 CIO 1650 to CIO 1674 Unit No. 7 D30700 to D30799 Unit No. 7 CIO 1675 to CIO 1699 Unit No. 8 D30800 to D30899 Unit No. 8 CIO 1700 to CIO 1724 Unit No. 9 D30900 to D30999 Unit No. 9 CIO 1725 to CIO 1749 Unit No. A D31000 to D31099 Unit No. A CIO 1750 to CIO 1774 Unit No. B D31100 to D31199 Unit No. B CIO 1775 to CIO 1799 Unit No. C D31200 to D31299 Unit No. C CIO 1800 to CIO 1824 Unit No. D D31300 to D31399 Unit No. D CIO 1825 to CIO 1849 Unit No. E D31400 to D31499 Unit No. E CIO 1850 to CIO 1874 Unit No. F D31500 to D31599 Unit No. F CIO 1875 to CIO 1899 With a Serial Communications Board, the following words are always allocated. Setup Area in the DM Area: D32000 to D32767 Words allocated in the CIO Area: CIO 1900 to CIO 1999 D32000 to D32009 Port 1 Setup Area CIO 1900 Software switch D32010 to D32019 Port 2 Setup Area CIO 1901 to CIO 1904 Board status D32020 to D32767 Reserved for the system CIO 1905 to CIO 1914 Port 1 status CIO 1915 to CIO 1924 Port 2 status CIO 1925 to CIO 1999 Reserved for the system 29 Section Basic Operating Procedure Installing the Board or Unit 1, 2, 3... 1-9 Serial Communications Board 1. Press in the lever on the Inner Board installation cover, first on the top and then on the bottom, and remove the cover. Press in the lever on the top. Press in the lever on the bottom. 2. Install the Serial Communications Board. Serial Communications Unit 1, 2, 3... 1. Catch the hook on the top of the back of the Unit on the Backplane, and then rotate the Unit downward to mount it. Hook Backplane 2. Insert the Unit firmly into the Backplane connector. 3. Tighten the screw at the bottom of the Unit with a Phillips screwdriver to a torque of 0.4 Nm. For this operation, the Phillips screwdriver must be 30 Section Basic Operating Procedure 1-9 placed at a slight angle. Therefore, leave sufficient space at the bottom of the Unit. Duct At least 20 mm CPU Unit I/O Power Supply Unit Backplane Remote I/O Unit At least 20 mm Duct Phillips screwdriver Connections Connect the external devices using RS-232C or RS-422A cables. For details on the connector pin layout and the connection methods, see Section 3 Installation and Wiring, and refer to the relevant manuals for the external devices to be connected. Types of Port for Different Models The types of port for the different models of Serial Communication Boards and Units are shown in the following table. Type of Unit Serial Communications Board Serial Communications Unit Model Port 1 CS1W-SCB21 CS1W-SCB41 CS1W-SCU21 RS-232C RS-232C RS-232C Port 2 RS-232C RS-422A/485 RS-232C When an RS-422A/485 port is used with a Serial Communications Board, the following setting is required. • TERM: Terminating resistance ON/OFF switch OFF: Terminating resistance OFF ON: Terminating resistance ON • WIRE: 2-wire or 4-wire selector switch 2: 2-wire; 4: 4-wire OFF 2 ON 4 TERM WIRE 31 Section Basic Operating Procedure 1-9 Connection Example for Host Link Communications The host computer can be connected to a PC 1:1, or NT-AL001-E Converting Link Adapters can be used to convert from RS-232C to RS-422A/485 to connect the host computer to PCs 1:N. Serial Communications Board Serial Communications Unit NT-AL001-E Terminating resistance ON, 5-V power supply required Terminating resistance ON Also perform other required processing, such as setting switches on the external device(s). Connection Example for Protocol Macros Serial Communications Board RS-232C RS-422A/485 Terminating resistance ON General-purpose external device General-purpose external device General-purpose external device Terminating resistance ON General-purpose external device Also perform other required processing, such as setting switches on the external device(s). Connection Example for 1:N NT Links Refer to the manual for the PT. Connecting Programming Devices Connect the Programming Console, CX-Programmer, or CX-Protocol to the CPU Unit as required. Turning ON Power Turn ON the PC power supply to the PC. Creating I/O Tables for Serial Communications Units I/O tables must be created for Serial Communications Units. Create the I/O table using a Programming Device, such as a Programming Console or CX-Programmer. Setting the Setup Area in the DM Area Set the serial communications mode and the communications specifications for the Board or Unit. Use a Programming Device, such as a Programming Console or CX-Programmer, or the CX-Protocol to set the Setup Area. 32 Section Basic Operating Procedure 1-9 Host Link Communications The following table shows the default (standard) settings for Host Link communications. m = D30000 + 100 Board Unit Port 1 Bit Setting unit number Meaning Port 1 D32000 Port 2 D32010 m Port 2 m+10 15 0 Start bit: 1 bit Data length: 7 bits Parity: Even Stop bits: 2 bits Baud rate: 9,600 bps D32001 D32011 m+1 m+11 08 to 11 00 to 03 5 0 D32002 D32003 D32012 D32013 m+2 m+3 m+12 m+13 15 0 Host Link mode The baud rate setting is disabled when the default settings are used. Send delay: 0 ms 15 00 to 07 0 00 CTS control: No Host Link unit number: 0 Protocol Macros The following table shows the default (standard) settings for protocol macros. m = D30000 + 100 Board Port 1 D32000 Port 2 D32010 Unit Port 1 m Bit Setting unit number Meaning Port 2 m + 10 15 0 Start bit: 1 bit Data length: 7 bits Parity: Even Stop bits: 2 bits Baud rate: 9,600 bps 6 0 Protocol Macro mode The baud rate setting is disabled when the default settings are used. Half-duplex D32001 D32011 m+1 m + 11 11 to 08 03 to 00 D32008 D32018 m+8 m + 18 15 0 D32009 D32019 m+9 m + 19 15 to 00 00C8 hex Maximum number of bytes in protocol macro send/receive data: 200 bytes NT Link Mode The following table shows the default (standard) settings for NT link when the maximum PT unit number is 5. m = D30000 + 100 Board Port 1 D32000 Port 2 D32010 D32001 D32011 D32006 D32016 Unit Port 1 Bit Setting unit number Meaning m Port 2 m + 10 11 to 08 2 1:N NT Link m+1 m + 11 03 to 00 0 The baud rate is set to the standard NT link setting when the default settings are used. m+6 m + 16 02 to 00 5 1:N NT Link maximum unit number (example) Validate the New Settings Make the new settings in the Setup Area valid by performing one of the following. • Turn the power OFF and then ON again. The Setup Area allocated in the DM Area will be read when the power is turned ON. • Restart the Board by turning ON the Inner Board Restart Bit (A60800) or restart the Unit turning ON one of the CS1 CPU Bus Unit Restart Bits (A50100 to A50115, where the bit number corresponds to the unit number). (See following table.) 33 Section Basic Operating Procedure 1-9 • Restart the port on the Serial Communications Board by turning ON one of the Communications Board Port Settings Change Bits (A63601 for port 1 and A63602 for port 2) or restart the port on the Serial Communications Unit by tuning ON one of the Communications Unit Port Settings Change Bits (A620 to A635: The word will be A620 + unit number and the bit will be bit 01 for port 1 and bit 02 for port 2). Inner Board Restart Bit and CS1 CPU Bus Unit Restart Bits Board Units A60800 Communications Board/Unit Port Settings Change Bits Unit number A50100 (Unit No. 0) A50101 (Unit No. 1) A50102 (Unit No. 2) A50103 (Unit No. 3) A50104 (Unit No. 4) A50105 (Unit No. 5) A50106 (Unit No. 6) A50107 (Unit No. 7) A50108 (Unit No. 8) A50109 (Unit No. 9) A50110 (Unit No. A) A50111 (Unit No. B) A50112 (Unit No. C) A50113 (Unit No. D) A50114 (Unit No. E) A50115 (Unit No. F) Board Units Unit No. 0 Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4 Unit No. 5 Unit No. 6 Unit No. 7 Unit No. 8 Unit No. 9 Unit No. A Unit No. B Unit No. C Unit No. D Unit No. E Unit No. F Port 1 Port 2 A63601 A62001 A62101 A62201 A62301 A62401 A62501 A62601 A62701 A62801 A62901 A63001 A63101 A63201 A63301 A63401 A63501 A63602 A62002 A62102 A62202 A62302 A62402 A62502 A62602 A62702 A62802 A62902 A63002 A63102 A63202 A63302 A63402 A63502 • Execute the STUP(237) instruction. The Board or Unit Setup Area can be changed while the PC power supply is ON. The STUP(237) instruction can be used, for example, when a send/receive sequence for a modem connection is executed in Protocol Macro Mode to switch the operating mode to Host Link Mode when a certain condition is established. This enables monitoring or programming of the CPU Unit to be carried out from a host computer. See Appendix O Changing Port Settings Using STUP(237). Executing Communications The required data and ladder program are created to perform communications in the serial communications mode that has been set. Host Link Communications Sending C-mode and FINS Commands from Host Computers to PCs To send C-mode commands or FINS commands, programs must be created on the host computer to send commands to PCs and to receive responses back from the PCs. Refer to the CS1-series Communications Commands Reference Manual (W342) for details. Programming to send commands and receive responses. Host computer Serial Communications Board/Unit Command 34 Section Basic Operating Procedure 1-9 Sending FINS Commands from PCs to Host Computers SEND(090), RECV(098), and CMND(490) can be used to execute slave-initiated communications. Also, programming is required at the host computer to received data and return responses. An example is provided below for SEND(090). Programming to return responses. Host computer Serial Communications Board/Unit SEND(090), RECV(098), CMND(490) Command CPU Unit SEND(090) can be used to send data from the PC to a host computer. If the input condition turns ON when the Communications Port Enabled Flag is ON, 10 words of data from CIO 0100 to CIO 0109 will be sent to the host computer connected to port 1 on the Serial Communications Unit with network address 0, node address 0, and unit address 10 Hex. Communications Port Enabled Flag for Port 0 Input condition A20200 @SEND (90) 0100 0000 D00200 First send word: CIO 0100 “0000” used to send to a host computer. First control data word: D00200 The control data for the above instruction is shown in the following table. Word Contents Meaning D00200 000A Number of send words: 10 D00201 0100 Bits 00 to 07: Destination network address 0 D00202 0010 D00203 0000 Bits 08 to 10: Serial Communications Unit port 1 Bits 00 to 07: Destination unit address 10 Hex Bits 08 to 15: Destination node address 0 Bits 00 to 04: Number of retries is 0 Bits 08 to 11: Communications port 0 Bit 15: Response required D00204 0000 Response monitoring time: 2 s (default value for 0000) A program would be required at the host computer to receive the above data and return a response. Protocol Macros When a standard system protocol (provided in the Serial Communications Board, Serial Communications Unit, and CX-Protocol) is executed. Using Standard System Protocols Uses standard system protocol No. 600 Board or Unit Executed with PMCR(260)( 237) CPU Unit External device Example: K3N Series Digital Panel Meter 35 Section Basic Operating Procedure 1, 2, 3... 1-9 1. Setting the Send Data Refer to information on the 3rd operand of PMCR(260) in Appendix B CompoWay/F Master Protocol and set the number of send data words in S, and set the send data starting in S+1. 2. Coding PMCR(260) Example: The following example shows how to use a Serial Communications Board to read the present value for a K3N-series Digital Panel Meter using the CompoWay/F Master standard system protocol sequence No. 600: Send/receive with ASCII conversion and response. Input condition Protocol Macro Executing Flag 191915 Communications Port Enabled Flag for Port 7 A20207 PMCR(260) (260) #72E1 C1 C2 S D #0258 D00000 D00010 Communications port 7 and serial port 2 Destination unit address E1: Serial Communications Board Sequence No. 600 First word of send data First storage word for receive data ER FAL (006) 01 If the input condition turns ON when the Protocol Macro Executing Flag (CIO 191915 for Port 2) is OFF and the Communications Port Enabled Flag (A20207: Internal logic port, communications port 7) is ON, send/receive sequence No. 600 of the standard system protocol in the Serial Communications Board is called, and data is sent and received via port 2 of the Serial Communications Board. Send Data S:D00000 D00001 D00002 D00003 D00004 D00005 D00006 0007 0000 0101 000C C000 0000 0001 7 words from D00000 to D00006 K3N node No. : 00 CompoWay/F command “0101” (reads the K3N present value) Number of send bytes CompoWay/F command send data (Variable type, read start address, 00, number of elements) Receive Data D:D00010 D00011 D00012 D00013 0004 4 words from D00010 to D00013 Response code is stored. The read data (in this case, the present value of K3N) is stored. 3. Executing the PMCR(260) Instruction 4. For details on confirming operation, see Section 12 Tracing and I/O Memory Monitoring in the CX-Protocol Operation Manual (W344). • Transmission Line Tracing The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced. • I/O Memory Monitoring Monitors send/receive data and the status of the various flags. 36 Section Basic Operating Procedure 1-9 Executing User-created Protocols CX-Protocol Use the CX-Protocol to create protocols. Board or Unit PMCR(260) CPU Unit External device Section references in the following procedure refer to the CX-Protocol Operation Manual (W344). 1, 2, 3... 1. For details on designing protocols, see Section 4 and Section 5. a) Create a send/receive sequence status transition chart. b) From the status transition chart, divide the processing contents into sequence steps. c) Determine the send/receive message contents. 2. Use the CX-Protocol to create and send a project (protocol data). See 1.10 for the outline flow. a) Creating a new project: See 5.1 Creating a New Project or Protocol. b) Creating a new send/receive sequence: See 5.2 Creating a New Sequence or 7.1 Setting a Sequence. c) Creating steps: See 5.2 Creating a New Sequence and 8.1 Setting a Step. d) Creating messages: See 9.1 Setting a Message. Note After creating messages, steps can also be created by specifying message names. e) Transferring the created project to a Board or Unit: See 11.1 Transferring and Reading Protocol Data between Personal Computers and Serial Communications Boards. 3. Create the ladder program. a) Setting Send Data • Specifying Operands Set the send data in the I/O memory after the S+1 operand of the PMCR(260) instruction. Set the number of send data words (including S itself) in S. • Direct Designations Set the send data in the I/O memory specified by the read variables in the send message. • Specifying Link Words Set the send data in the O1 or O2 area of the Link Word Area. b) Coding PMCR(260) 37 Section Basic Operating Procedure 1-9 Example for a Serial Communications Board Input condition Protocol Macro Executing Flag 191915 Communications Port Enabled Flag for Port 7 A20207 PMCR(260) C1 C2 S D #72E1 #0064 D00000 D00010 Communications port 7 and serial port 2 Destination unit address E1: Serial Communications Board Sequence No. 100 First word of send data First storage word for receive data ER FAL (006) 01 If the input condition turns ON when the Protocol Macro Executing Flag (CIO 191915 for port 2) is OFF and the Communications Port Enabled Flag (A20207 for internal logic port, communications port 7) is ON, send/receive sequence No. 100 registered in the Serial Communications Board is called, and data is sent and received via port 2 of the Serial Communications Board. The amount of send data depends on the number of words specified in D00000 (the number of words after D00001 plus 1 for D00000 itself), and is sent from the next word after D00001. S:D00000 D00001 Number of words Send data Number of send words plus 1 for D00000 Number of words The receive data is stored in consecutive words beginning with D00011, and the number of words actually stored in D00010 (the number of words after D00011 plus 1 for D00010 itself) is stored. S:D00000 D00011 Number of words Receive data Number of send words plus 1 for D00010 Number of words c) Execute PMCR(260) 4. For details on the confirming operation, see Section 12 Tracing and I/O Memory Monitoring. • Transmission Line Tracing The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced. • I/O Memory Monitoring Monitors send/receive data and the status of the various flags. 1:N NT Links Refer to the user’s manual for the PT. 38 SECTION 2 Initial Settings and I/O Memory Allocations This section describes the components of the Serial Communications Boards and the Serial Communications Units, the settings required for operation, and the memory allocated in the I/O memory of the CPU Unit for controlling and monitoring communications. 2-1 2-2 2-3 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-1 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1-2 Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Exchange with the CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-1 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2-2 Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Memory Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-1 DM Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-2 CIO Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3-3 Related Auxiliary Area Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 40 44 46 46 47 48 48 51 55 39 Section Component Names and Functions 2-1 2-1 Component Names and Functions 2-1-1 Serial Communications Boards CS1W-SCB21 CS1W-SCB41 Indicators Port 1 RS-232C Terminating resistance switch 2-wire or 4-wire switch Port 2 RS-232C Indicators Indicator RDY Color Green Port 2 RS-422A/485 Status Lit Flashing Not lit Meaning Operating normally, and protocol macro preparations have been completed. Operating normally, and protocol macros are being prepared. (See note) An error has occurred in the Serial Communications Board. Board/Unit error, CPU Unit watchdog timer error, Board watchdog timer error COMM1 Yellow COMM2 Yellow Lit Not lit Lit Not lit Port 1 is being used for sending or receiving. Port 1 is not being used for sending or receiving. Port 2 is being used for sending or receiving. Port 2 is not being used for sending or receiving. Note Depending on the interval of flashing, the meaning is as follows: Protocol data being initialized: 0.3 s Protocol data being overwritten: 1.0 s Protocol data error: 1.0 s and CPU Unit ERR/ALM indicator is flashing CPU Unit Indicators A Serial Communications Board is mounted as an Inner Board in the CPU Unit and thus affect the CPU Unit ERR/ALM indicator. Indicator Color ERR/ALM Red Status Meaning Lit Fatal error Flashing Non-fatal error Not lit Normal operation If a fatal error occurs, the CPU Unit will stop operation in either RUN or MONITOR mode. If a non-fatal error occurs, the CPU Unit will continue operation in either RUN or MONITOR mode. The CPU Unit is operating normally. If an error in the Inner Board is the cause of the error indicated on the ERR/ALM indicator, information on the error will be stored in A424: Inner Board Error Information. Refer to Inner Board Error Information under 2-3-3 Related Auxiliary Area Bits. 40 Section Component Names and Functions 2-1 For actions required when an error occurs, refer to Section 8 Troubleshooting and Maintenance. RS-232C Ports Port 1 and port 2 are RS-232C ports on the CS1W-SCB21. Only port 1 is an RS-232C port on the CS1W-SCB41. Protocol Protocol macro Full-duplex Baud rate 1,200/2,400/4,800/ 9,600/19,200/ 38,400/57,600/ 115,200 bps 1:1 (1:N is possible Connections Transmission distance Interface Note Host Link Communications method Synchronization 1:N NT Links Full-duplex or Half-duplex half-duplex Start-stop synchronization (asynchronous) 1,200/2,400/4,800/ 9,600/19,200/ 38,400 bps Standard NT link or high-speed NT link using Link Adapters) 15 m max. (see note 2) Complies with EIA RS-232C 1. High-speed NT link is only available with Serial Communications Boards/ Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available. 2. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. Connector Pin Layout Pin No. Note Abbreviation Signal name I/O 1 (see note 1) FG Shield --- 2 SD Send data Output 3 RD Receive data Input 4 (see note 2) RTS (RS) Request to send Output 5 (see note 2) CTS (CS) Clear to send Input 6 (see note 3) 5V Power supply --- 7 (see note 2) DSR (DR) Data set ready Input 8 (see note 2) DTR (ER) Output 9 SG Data terminal ready (See note 4) Signal ground Shell (see note 1) FG Shield --- --- 1. Pin No. 1 and the shell are connected to the ground terminal (GR) of the Power Supply Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit. 2. The status of the RTS (RS), CTS (CS), DSR (DR), and DTR (ER) signals can be monitored in the words allocated in the CIO Area. For details, refer to 2-3 I/O Memory Allocations. 3. Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected. For details on connection methods, refer to 3-3 Wiring. 4. The DSR signal is used to monitor the signal cable. It can also be used as a CD (carrier detect) signal. (The DSR signal does not affect system operation, and is available for use by the user.) ! Caution Do not connect the 5-V power supply of Pin 6 to any external device other than an NT-AL001-E Link Adapter. Otherwise, the external device and the Serial Communications Board or Unit may be damaged. 41 Section Component Names and Functions 2-1 The following cables are provided for connection to NT-AL001-E Link Adapters. We recommend that these cables be used. NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m) XW2Z-200T-1 (2 m) Applicable Connectors Plug: XM2A-0901 (manufactured by OMRON) or equivalent Hood: XM2S-0911-E (manufactured by OMRON) or equivalent One plug and one hood are provided for each port. Recommended Cables UL2426 AWG28 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.) AWG28 5P IFVV-SB (not UL-approved, Fujikura Ltd.) UL2426-SB (MA) 5P 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.) CO-MA-VV-SB 5P 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.) Cable length: 15 m max. RS-422A/485 Port Port 2 of the CS1W-SCB41 is an RS-422A/485 port. Protocol Host Link Protocol macro 1:N NT Links Communications method Synchronization Full-duplex Full-duplex or half-duplex Start-stop synchronous (asynchronous) Half-duplex Baud rate 1,200/2,400/4,800/ 1,200/2,400/4,800/ 9,600/19,200/ 9,600/19,200/ 38,400/57,600/ 38,400 bps 115,200 bps 1:N (N: 32 Units max.) Standard NT link or high-speed NT link Connections Transmission distance Interface 1:N (N: 8 Units max.) 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.) Complies with EIA RS-485 Note High-speed NT link is only available with Serial Communications Boards/Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available. Connector Pin Layout Pin No. Note 42 Abbreviation Signal name I/O 1 (see note 1) SDA Send data – Output 2 (see note 1) SDB Send data + Output 3 NC Not used --- 4 NC Not used --- 5 NC Not used --- 6 (see note 1) RDA Receive data – Input 7 NC Not used --- 8 (see note 1) RDB Receive data + Input 9 NC Not used --- Shell (see note 2) FG Shield --- 1. When 2-wire connections are used, use Pins 1 and 2, or Pins 6 and 8. 2. The shell is connected to the ground terminal (GR) of the Power Supply Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit. 3. With SDA/B or RDA/B, the signal polarity may be reversed by the remote device. Be sure to check the polarity before wiring. Applicable Connectors Plug: XM2A-0901 (OMRON) or equivalent Hood: XM2S-0911-E (OMRON) or equivalent One plug and one hood are provided for each port. Section Component Names and Functions 2-1 Recommended Cables CO-HC-ESV-3P 7/0.2 (manufactured by Hirakawa Hewtech Corp.) Cable length: 500 m max. (The total combined cable length is 500 m max. Tbranch lines must be a maximum of 10 m long.) Terminating Resistance Switch: TERM The terminating resistance switch is provided on the CS1W-SCB41 only. When an RS-422/485 port is used, set the switch to ON if the Serial Communications Board is on the end of the transmission line. Refer to Section 3 Installation and Wiring for the ON/OFF settings. Label TERM Name Terminating resistance switch Settings ON: Terminating resistance ON OFF: Terminating resistance OFF Factory setting OFF: Terminating resistance OFF Note The status of terminating resistance setting can be monitored in the words allocated in the CIO Area. For details, refer to 2-3 I/O Memory Allocations. 2-Wire or 4-Wire Switch: WIRE The 2-wire or 4-wire switch is provided on the CS1W-SCB41 only. When an RS-422/485 port is used, set the switch to “2” when 2-wire connections are used, and set the switch to “4” when 4-wire connections are used. For details, refer to Section 3 Installation and Wiring. Label WIRE Name 2-wire or 4-wire switch Settings 2: 2-wire Factory setting 2: 2-wire 4: 4-wire External Dimensions CS1W-SCB21 CS1W-SCB41 Mounted in the CPU Unit 43 Section Component Names and Functions 2-1 2-1-2 Serial Communications Units CS1W-SCU21 Indicators Unit number switch Port 1 RS-232C Port 2 RS-232C Indicators Indicator RUN Color Green RDY Green Status Lit Not lit Lit Flashing Not lit ERH Red Lit Flashing Not lit ERC Note 44 Red SD1 Yellow RD1 Yellow SD2 Yellow RD2 Yellow Lit Flashing Not lit Lit Not lit Lit Not lit Lit Not lit Lit Not lit Meaning Operating normally Unit hardware error. Protocol macro preparations have been completed. Protocol macros are being prepared. (See Note 1.) Hardware error in Serial Communications Unit. CPU Unit error, or this Unit has not been registered in the I/O table. Routing tables incorrectly registered in the Unit. System Setup error (See note 2) CPU Unit is operating normally and the Setup Area settings are normal. Unit hardware error, or loopback test error Protocol data syntax error or protocol data error (SUM error). Unit is operating normally. Port 1 is being used for sending. Port 1 is not being used for sending. Port 1 is being used for receiving. Port 1 is not being used for receiving. Port 2 is being used for sending. Port 2 is not being used for sending. Port 2 is being used for sending. Port 2 is not being used for sending. 1. Depending on the interval of flashing, the meaning is as follows: Protocol data being initialized: 0.3 s Protocol data initialized, or being overwritten: 1.0 s Protocol data error: 1.0 s and CPU Unit ERC indicator is flashing 2. The Setup Area is allocated in the DM Area according to the unit number setting. For details, refer to 2-3 I/O Memory Allocations. For the action required when an error occurs, refer to Section 8 Troubleshooting and Maintenance. Component Names and Functions Section 2-1 UNIT No. Switch: Unit Number Set the CPU Bus Unit unit number for the Unit. The CIO Area and DM Area are allocated according to the unit number setting. The words that are allocated are used for the software switches, Status Area, and the System Setup. Set the unit number between 0 and F. The factory setting is for unit number 0. RS-232C Ports The specifications of the RS-232C are the same as those for the RS-232C port on the Serial Communications Board. See RS-232C Ports on page 41. External Dimensions 45 Section Data Exchange with the CPU Unit 2-2 2-2 Data Exchange with the CPU Unit Data exchange with the CPU Units uses the I/O memory allocated to the Serial Communications Board and Serial Communications Unit. For details on allocations, refer to 2-3 I/O Memory Allocations. 2-2-1 Serial Communications Boards CPU Unit Serial Communications Board Inner Board Area in CIO Area CIO 1900 Local memory Software switch 25 words Status CIO 1999 Local memory (System Setup) Inner Board Area in DM Area D32000 System Setup (see note 1) 20 words D32099 Auxiliary Area Port Settings Change Bits (see note 2) A636 Restart Bits A608 Error Information Error information A424 Note 1. Set the Serial Communications Board mode and the communications settings (System Setup) in the words allocated in the DM Area. Use a Programming Device, such as a Programming Console or the CX-Programmer, to make these settings. The System Setup is transferred to the Serial Communications Board at the following times: • When the power to the CPU Unit is turned ON, when the Serial Communications Board is restarted (A60800 is turned ON), or when the STUP(237) instruction is executed. • When the Port 1 Port Settings Change Bit (A63601) or Port 2 Port Settings Change Bit (A63602) is turned ON. 2. When STUP(237) is executed, the CPU Unit automatically turns ON the Port 1 or Port 2 Port Settings Change Bit and updates the System Setup. For details on the STUP(237) instruction, see Appendix O Changing Communications Port Settings Using STUP(237). 46 Section Data Exchange with the CPU Unit 2-2 2-2-2 Serial Communications Units Serial Communications Unit CPU Unit Unit No. : 0 Local memory CPU Bus Unit Area in CIO Area CIO 1500 CIO 1501 Software switches 25 words Unit No. 0 25 words Status CIO 1524 CIO 1525 CIO 1526 25 words Unit No. 1 CIO 1549 CIO 1875 25 words Unit No. 15 CIO 1899 CPU Bus Unit Area in DM Area Local memory (System Setup) D30000 D30001 Unit No. 0 100 words System Setup (see note 1) 20 words D30099 D30100 D30101 100 words Unit No. 1 D30199 D31500 Unit No. 15 100 words D31599 Auxiliary Area Unit No. 0 Unit No. 1 A620 A621 Unit No. 15 A635 A501 Unit 15 Note Port Settings Change Bits (see note 2) Restart Bits Unit 0 1. Set the Serial Communications Unit mode and the communications settings (System Setup) in the words allocated in the DM Area. Use a Programming Device, such as a Programming Console or the CX-Programmer, to make these settings. The System Setup is transferred to the Serial Communications Unit at the following times: • When the power to the CPU Unit is turned ON, when the Serial Communications Unit is restarted (a bit between A50100 to A50115 is turned ON), or when the STUP(237) instruction is executed. • When the Port 1 Port Settings Change Bit (a bit between A62001 to A63501 (see note a)) or Port 2 Port Settings Change Bit (a bit between A62002 to A63502 (see note b)) is turned ON. 47 Section I/O Memory Allocations 2-3 Note a) Bits are allocated in the following order: Unit number 0: A62001, unit number 1: A62101, unit number 2: A62201, and so on through unit number F: A63501. b) Bits are allocated in the following order: Unit number 0: A62002, unit number 1: A62102, unit number 2: A62202 and so on through unit number F: A63502. 2. When STUP(237) is executed, the CPU Unit automatically turns ON the Port 1 or Port 2 Port Settings Change Bit and updates the System Setup. For details on the STUP(237) instruction, see Appendix O Changing Communications Port Settings Using STUP(237). 2-3 I/O Memory Allocations This section explains the DM Area, CIO Area, and Auxiliary Area allocations to the Serial Communications Boards and Serial Communications Units. The Serial Communications Board uses the allocations for the Inner Board of the CPU Unit. The Serial Communications Unit is allocated I/O memory as a CPU Bus Unit according to the unit number setting. 2-3-1 DM Area Serial Communications Board The Setup Area allocated in the DM Area consists of 20 words between D32000 and D32767. These words are used to set the serial communications mode, communications specifications, and other settings for the Serial Communications Board. The 10 words from D32000 to D32009 are used for port 1, and the 10 words from D32010 to D32019 are used for port 2. The remaining words are reserved for the system. Setup Area Allocated in the DM Area D32000 to D32767 Words 48 Usage D32000 to D32009 Port 1 Settings D32010 to D32019 Port 2 Settings D32020 to D32767 Reserved for the system Section I/O Memory Allocations Serial Communications Units 2-3 The Setup Area allocated in the DM Area is used to set the serial communications mode, communications specifications, and other settings for the Serial Communications Units. The words from D30000 to D31599 (100 words per Unit 16 Units) are allocated according to the unit number settings. The first 10 words are used for port 1, and the next 10 words are used for port 2. The other 80 words are reserved for the system. m = D30000 + 100 Unit No. Setting the Setup Areas unit number Words Unit No. 0 D30000 to D30099 m to m + 9: Port 1 Settings Unit No. 1 D30100 to D30199 m + 10 to m + 19: Port 2 Settings Unit No. 2 D30200 to D30299 m + 20 to m + 99: Reserved for the system Unit No. 3 D30300 to D30399 Unit No. 4 D30400 to D30499 Unit No. 5 D30500 to D30599 Unit No. 6 D30600 to D30699 Unit No. 7 D30700 to D30799 Unit No. 8 D30800 to D30899 Unit No. 9 D30900 to D30999 Unit No. A D31000 to D31099 Unit No. B D31100 to D31199 Unit No. C D31200 to D31299 Unit No. D D31300 to D31399 Unit No. E D31400 to D31499 Unit No. F D31500 to D31599 The following methods can be used to set the Unit settings in the Setup Areas. • Use a Programming Device, such as a Programming Console (see note a), CX-Protocol, or CX-Programmer. • Use the STUP(237) instruction (see note b) in the ladder diagram program. If it is necessary to change the System Setup while the ladder diagram program is being executed, use this method to change the System Setup. Note a) If settings are changed from a Programming Device, cycle the power to the CPU Unit, use a Restart Bit to restart the Unit or Board, or use the Port Settings Change Bits to restart the port. Refer to 2-2 Data Exchange with the CPU Unit for the specific addresses to use. b) For the procedure used to change the System Setup using the STUP(237) instruction, refer to Appendix O Changing Communications Port Settings Using STUP(237). The usage of the System Setup differs according to the serial communications mode. For details, refer to the following sections. Host Link communications: Protocol macros: 1:N NT Links: Loopback test: Section 4 Using Host Link Communications. Section 5 Using Protocol Macros. Section 6 Using 1:N NT Links. Section 7 Loopback Test. 49 Section I/O Memory Allocations 2-3 Setup Area m = D30000 + 100 Words Board Unit Port 1 Port 2 Port 1 Port 2 D32000 D32010 m m + 10 D32001 D32011 m+1 m + 11 D32002 D32012 m+ 2 m + 12 D32003 D32013 m + 3 m + 13 D32004 D32014 m + 4 m + 14 D32005 D32006 D32015 m + 5 D32016 m + 6 m + 15 m + 16 D32007 D32008 D32017 m + 7 D32018 m + 8 m + 17 m + 18 D32009 D32019 m + 9 m + 19 Note unit number Bit Setting contents 15 12 to 14 08 to 11 Port settings (see note 1) 0: Defaults; 1: User settings Reserved Serial communications mode (see note 2) 0: Default (Host Link); 2: 1:N NT Links (see note 3); 5: Host Link; 6: Protocol macro; F: Loopback test 05 to 07 04 Reserved Start bits 0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting) Data length 0: 7 bits; 1: 8 bits Stop bits 0: 2 bits; 1: 1 bit Parity 0: Yes; 1: No Parity 0: Even; 1: Odd Reserved Baud rate (Unit: bps) (see note 4) 0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200; 8: 38,400; 9: 57,600; A: 115,200 Host Send delay time 0: Default (0 ms); 1: Setting in bits 00 to 14 Link Send delay (0000 to 7530 hex) (Unit: 10 ms) 03 02 01 00 04 to 15 00 to 03 15 00 to 14 15 08 to 14 00 to 07 00 to 15 CTS control (see note 5) 0: No; 1:Yes Reserved Host Link unit number (00 to 1F hex) Reserved 00 to 15 Reserved 03 to 15 00 to 02 00 to 15 Reserved 1:N NT Links maximum unit number (0 to 7) Reserved 15 00 to 14 00 to 15 Protocol macro transmission method 0: Half-duplex; 1:Full-duplex Reserved Maximum number of bytes in protocol macro send/receive data (00C8 to 03E8) (see note 6) 1. The default settings used are as follows: Baud rate: 9,600 bps, start bits: 1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits (with the Host Link, protocol macro, and loopback test serial communications modes). 2. A System Setup error will occur if 1, 3, 4, or 7 to E is set, and the Unit will operate with the default Host Link settings (9,600 bps, unit number 00). 3. The PTs connected to the port must also be set for a 1:N NT Link. Communications will not be possible if a PT is set for a 1:1 NT Link. 4. Do not set B to F settings, and baud rates that are not supported by the serial communications mode. A System Setup error will result. Settings of 1 and 2 are reserved for the system and should not be used. 5. With CTS control, turn ON the request to send (RTS) signal before stating to send, and be sure the clear to send (CTS) signal is ON before sending data. When there is no CTS control, turn ON the request to send (RTS) signal before sending, and then send data without checking the request to send (RTS) signal. 6. For settings below 00C8, use 00C8 Hex; for settings above 03E8, use 03E8 Hex. 50 Section I/O Memory Allocations 2-3 2-3-2 CIO Area Words in the CIO Area are allocated as Software Switches, which are manipulated from the CPU Unit to control the operation of the Serial Communications Board or Unit, and for a Status Area, which contains status and error information for the Serial Communications Board or Unit. Serial Communications Board Words CIO 1900 to CIO 1999 in the Inner Board Area are used for the Software Switches and Status Area. CIO 1900 contains software switches, and the 24 words from CIO 1901 to CIO 1924 are used for the Status Area. Inner Board CIO Area CIO 1900 to CIO 1999 Words Serial Communications Units Usage CIO 1900 Software switch CIO 1901 to CIO 1904 Board status CIO 1905 to CIO 1914 Port 1 status CIO 1915 to CIO 1924 Port 2 status CIO 1925 to CIO 1999 Reserved for the system Words are allocated in the CIO Area for Software Switches and Status Area. Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. The first word is used for Software Switches, and the remaining 24 words are used for the Status Area. CPU Bus Unit Area CIO 1500 to CIO 1899 n = CIO 1500 + 25 unit number Unit No. Words Unit No. 0 CIO 1500 to CIO 1524 n: Software switches (Ports 1 and 2) Unit No. 1 CIO 1525 to CIO 1549 n + 1 to n + 4: Unit status Unit No. 2 CIO 1550 to CIO 1574 n + 5 to n + 14: Port 1 status Unit No. 3 CIO 1575 to CIO 1599 n + 15 to n + 24: Port 2 status Unit No. 4 CIO 1600 to CIO 1624 Unit No. 5 CIO 1625 to CIO 1649 Unit No. 6 CIO 1650 to CIO 1674 Unit No. 7 CIO 1675 to CIO 1699 Unit No. 8 CIO 1700 to CIO 1724 Unit No. 9 CIO 1725 to CIO 1749 Unit No. A CIO 1750 to CIO 1774 Unit No. B CIO 1775 to CIO 1799 Unit No. C CIO 1800 to CIO 1824 Unit No. D CIO 1825 to CIO 1849 Unit No. E CIO 1850 to CIO 1874 Unit No. F CIO 1875 to CIO 1899 51 Section I/O Memory Allocations Software Switches 2-3 Software Switches are used to output control signals from the CPU Unit to the Serial Communications Board or Unit. The software switches are used for loopback tests and to abort, release wait status, and control other functions for protocol macros. For details on the software switch functions, refer to Section 5 Using Protocol Macros and Section 7 Loopback Test. n = CIO 1500 + 25 unit number Words Board CIO 1900 Units n Bit 15 14 Function Port 2 13 12 11 10 Reserved Loopback Test Switch (loopback tests) 1: Start, 0: Stop Reserved Reserved Abort Switch (protocol macros) 1: Abort, 0: Aborted One-shot Trace Switch (protocol macros, see note) 1: Start, 0: Stop 09 Continuous Trace Switch (protocol macros, see note) 1: Start, 0: Stop 08 Wait Release Switch (protocol macros) 1: Release wait, 0: Wait released Reserved Loopback Test Switch (loopback tests) 1: Start, 0: Stop Reserved Reserved Abort Switch (protocol macros) 1: Abort, 0: Aborted One-shot Trace Switch (protocol macros, see note) 1: Start, 0: Stop 07 06 05 04 03 02 Port 1 01 Continuous Trace Switch (protocol macros, see note) 1: Start, 0: Stop 00 Wait Release Switch (protocol macros) 1: Release wait, 0: Wait released Note The One-shot Trace Switch and Continuous Trace Switch are used for the Serial Communications Board/Unit only when executing traces from the CX-Protocol in protocol macro mode. Do not manipulate these switches from a ladder diagram. The Status Area is used for status information input from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit sets communications status, the transmission control signal status, the transmission error status, and the protocol status. n = CIO 1500 + 25 unit number Status Area Words Board Port 1 Port 2 CIO 1901 CIO 1902 52 Units Port 1 Port 2 n+1 n+2 Bit 02 to 15 01 00 00 to 15 Contents Reserved 1: Error log EEPROM error 1: Protocol data error Reserved 0: Error log EEPROM normal 0: Protocol data normal Section I/O Memory Allocations Bit Words Board Units Port 1 Port 2 Port 1 Port 2 Contents CIO 1903 n+3 00 to 15 Reserved CIO 1904 n+4 00 to 15 Reserved CIO 1905 CIO 1915 n+5 n + 15 Port setting status CIO 1906 CIO 1916 n+6 n + 16 12 to 15 08 to 11 05 to 07 04 03 02 01 00 15 14 13 12 to 02 01 00 CIO 1907 CIO 1917 n+7 n + 17 15 to 11 10 09 08 07 06 05 04 03 00 to 02 CIO 1908 CIO 1918 n+8 n + 18 15 14 13 12 08 to 11 07 06 05 04 03 02 00, 01 CIO 1909 to CIO 1914 CIO 1919 to CIO 1924 n+9 to n + 14 n + 19 to n + 24 00 to 15 2-3 Serial communications mode (See note 1) Serial communications mode Baud rate Reserved Start bits: Always 1 Data length: 7 or 8 bits Stop bits: 1 or 2 bits Parity: Yes/No Parity: Even/Odd Hardware settings (See note 2) 0 No 0 RS-232C 1 RS-422A/485 1 Reserved 0 1 0 1 0: Terminating resistance OFF 1: Terminating resistance ON Reserved 1: System Setup error; 0: System Setup normal 1: Port operating; 0: Port stopped Commu- Reserved nications 1: Remote Unit busy receiving (Flow control) status 0: Remote Unit ready to receive Reserved 1: Local Unit busy receiving (Flow control) 0: Local Unit ready to receive TransDTR (ER) signal mission DSR (DR) signal control Reserved signal status CTS (CS) signal RTS (RS) signal Reserved Transmission error status 1: Transmission error (See note 3); 0: No transmission error 1: Tfs (send finished monitoring time) exceeded (See note 4); 0: Normal 1: Tfr (receive finished monitoring time) exceeded (See note 4); 0: Normal 1: Tr (receive wait monitoring time) exceeded (See note 4) 0: Normal Number of retries (See note 4) 1: FCS check error (See note 4); 0: FCS check normal 1: Command error (See note 4); 0: No command error 1: Timeout (Tfs, Tfr, or Tr) error (See note 4); 0: Normal 1: Overrun error (See note 5); 0: Normal 1: Framing error (See note 5); 0: Normal 1: Parity error (See note 5); 0: Normal Reserved Protocol status (See Protocol Status on page 54.) 53 Section I/O Memory Allocations Note 2-3 1. The port settings in the Setup Area allocated in the DM Area is read. For details on the contents that are read, see 2-3-1 DM Area. If a System Setup error occurs, the default settings will be read. 2. The port types for the Serial Communications Board or Unit and the terminating resistance switch setting are read. 3. Turned ON if an overrun error (bit 04), a framing error (bit 03), or a parity error (bit 02) occurs with the Host Link mode. If any of the error bits 00 to 14 turns ON in the protocol macro mode but then communications are recovered within the specified number of retries, the bit will turn OFF. The bit will remain ON if recovery is not possible within the specified number of retries. 4. Used only with protocol macros. Not used with any other serial communications mode. 5. Used with Host Link communications or protocol macros. Not used with any other serial communications mode. Protocol Status The protocol status is used in protocol macro mode, NT Link mode, or loopback tests. It is not used with other modes. The contents depend on the serial communications mode, as shown in the following tables. Protocol Macro Mode n = CIO 1500 + 25 Words Bit Board Port 1 Port 2 CIO CIO 1909 1919 Unit Port 1 Port 2 n+9 n + 19 CIO 1910 CIO 1920 n + 10 CIO 1911 CIO 1921 n + 11 15 14 13 12 11 10 09 04 to 08 00 to 03 Port operating status n + 20 12 to 15 00 to 11 n + 21 12 to 15 08 to 11 Reserved Send/Receive Sequence Number 000 to 999 (000 to 3E7 hex) Reserved Executed Step Number (code) 0 to 15 (0 to F hex) Reserved Executed Reception Case Number (code) 0 to 15 (0 to F hex) Executed Reception Case Number Storage Flag 0 to 15: Correspond to bits 00 to 15 Executed Step Number Storage Flag 0 to 15: Correspond to bits 00 to 15 Repeat Counter Setting Value 0 to 255 (00 to FF hex) Repeat Counter Present Value 0 to 255 (00 to FF hex) 04 to 07 00 to 03 CIO 1912 CIO 1913 CIO 1914 CIO 1922 CIO 1923 CIO 1924 n + 12 n + 22 00 to 15 n + 13 n + 23 00 to 15 n + 14 n + 24 08 to 15 00 to 07 54 Contents Protocol Macro Executing Flag Step Troubleshooting Flag Aborted Flag Tracing Flag Sequence End Completion Flag Sequence Abort Completion Flag Sequence Waiting Flag Reserved Error codes 0: No error 2: Sequence number error 3: Data read/write area exceeded error 4: Protocol data syntax error 5: CPU Unit error unit number Section I/O Memory Allocations 2-3 NT Links n = CIO 1500 + 25 Words Board Port 1 Port 2 Bit unit number Contents Unit Port 1 Port 2 CIO 1909 CIO 1919 n+9 n + 19 CIO 1910 to CIO 1914 CIO 1920 to CIO 1924 n + 10 to n + 20 to 00 to 15 n + 14 n + 24 08 to 15 00 to 07 PT Priority Registered Flag PT Communications Flag Reserved Loopback Tests n = CIO 1500 + 25 Words Board Port 1 Port 2 CIO 1909 CIO 1919 Bit unit number Contents Unit Port 1 Port 2 n+9 n + 19 15 09 to 14 08 07 06 05 04 03 02 01 00 Test status 1: Error; 0: Normal Reserved 1: DSR (DR) signal check error; 0: Normal 1: CTS (CS) signal check error; 0: Normal Reserved 1: Timeout error; 0: Normal 1: Parity error; 0: Normal 1: Overrun error; 0: Normal 1: Framing error; 0: Normal Reserved 1: Conveyor error; 0: Normal CIO 1910 CIO 1920 n + 10 n + 20 00 to 15 Number of tests executed CIO 1911 CIO 1921 n+11 n+21 00 to 15 Number of test errors CIO 1912 to CIO 1914 CIO 1922 to CIO 1924 n + 12 to n + 22 to 00 to 15 n + 14 n + 24 Reserved 2-3-3 Related Auxiliary Area Bits Serial Communications Board Port 1 and Port 2 Port Settings Change Bits These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. 55 Section I/O Memory Allocations 2-3 Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used. Word A636 Bit Contents 03 to 15 02 01 00 Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved Inner Board Error Information Word A424 Bit 12 to 15 11 10 Contents Non-fatal errors (Note 1) Reserved 1 Error log EEPROM error; 0: Normal 1: Protocol macro execution error; 0: Normal This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area, 09 08 07 06 05 04 03 02 01 00 Note Fatal errors (Note 2) 1: Protocol data error (SUM error); 0: Normal 1: System Setup error; 0: Normal 1: Routing table error; 0: Normal Reserved 1: Cyclic monitoring error; 0: Normal Reserved Reserved Reserved 1: Inner Bus error; 0: Normal 1: Inner Board watchdog timer error; 0: Normal 1. When any one of bits 04 to 11 is ON, A40208 (Inner Board Error Flag) (nonfatal error) will be ON. 2. When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON. For details on each type of error, refer to Section 8 Troubleshooting and Maintenance. Restart Bit: A60800 The Restart Bit can be turned ON and then OFF to restart the Serial Communications Board without turning OFF the PC power supply. Bit A60800 Serial Communications Units 56 Function Inner Board Restart Bit Port 1 and Port 2 Port Settings Change Bits These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Unit ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. The port 1 or port 2 Port Settings Change Bits and Restart Bits are allocated in the Auxiliary Area according to the unit number as shown below. Section I/O Memory Allocations 2-3 Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used. n = A620 + unit number Words n Bit Contents 03 to 15 02 01 00 Unit Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved Unit No. 0 Port 1 Settings Change Port 2 Settings Change Bit Bit A62001 A62002 Unit No. 1 A62101 A62102 Unit No. 2 A62201 A62202 Unit No. 3 A62301 A62302 Unit No. 4 A62401 A62402 Unit No. 5 A62501 A62502 Unit No. 6 A62601 A62602 Unit No. 7 A62701 A62702 Unit No. 8 A62801 A62802 Unit No. 9 A62901 A62902 Unit No. A A63001 A63002 Unit No. B A63101 A63102 Unit No. C A63201 A63202 Unit No. D A63301 A63302 Unit No. E A63401 A63402 Unit No. F A63501 A63502 Restart Bit A Restart Bit can be turned ON and then OFF to restart the Serial Communications Board without turning OFF the PC power supply. Unit Function A50100 Unit No. 0 Restart Bit A50101 Unit No. 1 Restart Bit A50102 Unit No. 2 Restart Bit A50103 Unit No. 3 Restart Bit A50104 Unit No. 4 Restart Bit A50105 Unit No. 5 Restart Bit A50106 Unit No. 6 Restart Bit A50107 Unit No. 7 Restart Bit A50108 Unit No. 8 Restart Bit A50109 Unit No. 9 Restart Bit A50110 Unit No. A Restart Bit A50111 Unit No. B Restart Bit A50112 Unit No. C Restart Bit A50113 Unit No. D Restart Bit A50114 Unit No. E Restart Bit A50115 Unit No. F Restart Bit 57 SECTION 3 Installation and Wiring This section describes how to mounting the Serial Communications Board and Serial Communications Units, and how to connect the ports to external devices. 3-1 3-2 3-3 3-4 Installing the Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1-1 Precautions in Handling the Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2-1 System Configuration Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2-2 Mounting to the Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2-3 Unit Handling Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-1 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-2 Port Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-3 Communications Modes and Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-4 Connector Pin Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-5 Mounting Height and Connector Cover Dimensions . . . . . . . . . . . . . . . . . . . . . . 3-3-6 Reducing Electrical Noise for External Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-7 2-Wire and 4-Wire Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-8 NT-AL001-E Link Adapter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-9 Connections for Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-10 Connections for Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3-11 1:N NT Link Connections with Programmable Terminals . . . . . . . . . . . . . . . . . . 3-3-12 Connections in Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RS-232C and RS-422A/485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-1 Recommended RS-232C Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-2 Recommended RS-422A/485 Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-3 Wiring Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-4 Soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-5 Assembling Connector Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4-6 Connecting to Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 60 61 61 61 62 63 63 63 63 64 65 66 66 67 68 75 82 83 83 83 84 86 88 88 89 59 Section Installing the Serial Communications Board 3-1 3-1 Installing the Serial Communications Board Installation Procedure This section describes how to install a Serial Communications Board in the option slot of a CPU Unit. Only one Serial Communications Board can be installed in each CPU Unit. Note 1, 2, 3... 1. Always turn OFF the power before installing or removing the Serial Communications Board. Installing or removing the Serial Communications Board with the power ON can cause the CPU Unit to malfunction, damage internal components, or cause communications errors. 2. Before handling the Serial Communications Board, touch a grounded metallic object in order to discharge any static build-up from your body. 1. Press the catches at the top and bottom of the Inner Board compartment cover. Press the top catch. Press the bottom catch. 2. Remove the Inner Board compartment cover. Inner Board Connector 3. Insert the Serial Communications Board. 3-1-1 Precautions in Handling the Board • Turn OFF the power supply to the CPU Unit before mounting or connecting the Board. • Separate the port connector lines from the high-tension or power lines to reduce external noise. 60 Section Installing Serial Communications Units 3-2 • Leave the port cover attached when not using a communications port. Port cover 3-2 Installing Serial Communications Units 3-2-1 System Configuration Precautions • Words in I/O memory are allocated to the Serial Communications Unit according to the setting of the unit number switch on the front panel of the Unit. Allocations are not affected by the slot in which the Unit is mounted. Refer to 2-3 I/O Memory Allocations. • Serial Communications Units can be mounted to CS1W-BCjj3 CPU Backplanes and CS1W-BIjj3 CS1 Expansion Backplanes. Up to 16 Serial Communications Units can be mounted for each PC (as long as no other CPU Bus Units are mounted). 3-2-2 Mounting to the Backplane Use the following steps to mount or remove Serial Communications Units. 1, 2, 3... 1. Mount the Unit to the Backplane by hooking the top of the Unit into the slot on the Backplane and rotating the Unit downwards. Hook Backplane 2. Make sure that the connector on the back of the Unit is properly inserted into the connector in the Backplane. 61 Installing Serial Communications Units Section 3-2 3. Use a Phillips screwdriver to tighten the screw on the bottom of the Unit. The screwdriver must be held at a slight angle, so be sure to leave enough space below the Rack. Duct 20 mm min. CPU Unit I/O Power Supply Unit Remote I/O Rack Backplane 20 mm min. Duct Phillips screwdriver Note Tighten the screw to a torque of 0.4 N-m. To remove the Unit, loosen the screw with a Phillips screwdriver, rotate the Unit upwards, and then remove it. 3-2-3 Unit Handling Precautions • Always turn OFF the CPU Unit before mounting or removing a Serial Communications Unit or connecting or disconnecting cables to/from the Serial Communications Unit. • Place the port connecting cables in a different duct from those for high-voltage lines or power lines to prevent the effects of electrical noise from these lines. • Do not remove the protective label from the top of the Unit until wiring has been completed. This label prevents wire strands and other foreign matter from entering the Unit during wiring. Remove the label after wiring has been completed to allow air circulation needed for cooling. 62 Section Wiring 3-3 • If a serial communications port is not being used, leave the cover on the port to prevent dust from entering. Remove label after wiring. Port cover 3-3 Wiring 3-3-1 Wiring Precautions • Before connecting or disconnecting the communications cables, always make sure that the PC is turned OFF. • Tighten the communications connector screws firmly with your fingers. • Serial Communications Boards and Units can be connected to various devices. For compatibility, refer to the operation manuals for the devices to which they are to be connected. 3-3-2 Port Types The following port types are provided on the Serial Communications Boards and Units. Unit type Serial Communications Board Serial Communications Unit Model Port 1 CS1W-SCB21 CS1W-SCB41 CS1W-SCU21 RS-232C RS-232C RS-232C Port 2 RS-232C RS-432A/485 RS-232C The following sections describe the connection methods used for each serial communications mode of the Serial Communications Board and Unit ports. 3-3-3 Communications Modes and Ports The following table shows the relationship between the communications ports and the communications modes for the Serial Communications Boards and Unit. Serial Communications Units provide only RS-232C ports. RS-232C Communications mode 1:1 Host Link YES Protocol macros YES 1:N (see note 1) YES (see note 2) YES NT Link YES YES Note RS-422A/485 1:1 4-wire 1:N 4-wire 1:1 2-wire 1:N 2-wire YES YES No No YES YES YES YES YES YES YES YES 1. The NT-AL001-E Link Adapter can be used to convert between RS-232C and RS-422A/485 to enable 1:N communications. 2. Use 4-wire connections between Link Adapters. 63 Section Wiring 3-3 3-3-4 Connector Pin Layout RS-232C Ports Pin Abbreviation Signal name I/O 1 FG Shield --- 2 SD Send data Output 3 RD Receive data Input 4 RTS (RS) Request to send Output 5 CTS (CS) Clear to send Input 6 5V Power supply --- 7 DSR (DR) Data set ready Input 8 DTR (ER) Data terminal ready Output 9 SG Signal ground --- Hood FG Shield --- Refer to 2-1 Component Names and Functions for signal precautions. RS-422A/485 Port Pin Abbreviation Signal name I/O 1 SDA Send data – Output 2 SDB Send data + Output 3 NC Unused --- 4 NC Unused --- 5 NC Unused --- 6 RDA Receive data – Input 7 NC Unused --- 8 RDB Receive data + Input 9 NC Unused --- Hood FG Shield --- Note When the 2-wire connections are used, use either pins 1 and 2, or pins 6 and 8. Refer to 2-1 Component Names and Functions for signal precautions. Port 2 Pin 8 Receiver Terminating resistance: 220 Ω Terminating resistance switch Pin 6 2-wire or 4-wire switch Pin 2 Driver Pin 1 Note The signal names SDA/B and RDA/B do not always have the same polarity as that shown above. Check the polarity of the external device before making connections. 64 Section Wiring 3-3 3-3-5 Mounting Height and Connector Cover Dimensions When mounting the Serial Communications Board or Unit, make sure to provide space for the mounting height and connector cover dimensions shown below. CS1W-SCB41 Serial Communications Board (mounted to CPU Unit) Cable connector Backplane connector Cable connector Backplane connector CS1W-SCB21 Serial Communications Board (mounted to CPU Unit) Cable connector Backplane connector CS1W-SCU21 Serial Communications Unit Note The mounting heights shown above are applicable when the attached connectors, connector covers, and recommended cables are used. The mounting height may differ when other connectors, connector covers, and cables are used. Determine the mounting height, taking into account the connectors, connector covers, and the minimum bending radius of the cables. 65 Section Wiring 3-3 3-3-6 Reducing Electrical Noise for External Wiring Observe the following precautions for external wiring. • When multi-conductor signal cable is being used, avoid using I/O wires and other control wires in the same cable. • If wiring racks are running in parallel, allow at least 300 mm between the racks. Low-current cables Communications cables Control cables PC power supply and general control circuit wiring Power cables 300 mm min. 300 mm min. Power lines Ground to 100 Ω or less. • If the I/O wiring and power cables must be placed in the same duct, they must be shielded from each other using grounded steel sheet metal. Communications cables PC power supply and general control circuit wiring Power lines Steel sheet metal 200 mm min. Ground to 100 Ω or less. 3-3-7 2-Wire and 4-Wire Connections The transmission circuits for 2-wire and 4-wire connections are different, as shown in the following diagram. Example of 2-Wire Connections Example of 4-Wire Connections 2/4-wire switch (DPDT) 2/4-wire switch (DPDT) Other Unit Board Board Note 66 Other Unit Other Unit Not connected Other Unit 1. Use the same transmission circuit (2-wire or 4-wire) for all nodes. 2. Do not use 4-wire connections when the 2/4-wire switch on the Board is set to 2-wire. 3. In protocol macro mode, do not use full-duplex transmissions when the 2/4-wire switch on the Unit is set to 2-wire. Otherwise, the data sent from the Serial Communications Board or Unit will be directly returned as receive data. In this case, the Board or Unit cannot determine whether the data in the receive buffer is its own send data or the data received from a remote node, and thus cannot perform receive processing properly. To avoid this problem, always use half-duplex transmissions with a 2-wire setting. Either half-duplex or full-duplex transmissions can be used with a 4-wire setting. Section Wiring 3-3 3-3-8 NT-AL001-E Link Adapter Settings The NT-AL001-E Link Adapter has a DIP switch for setting RS-422A/485 communications conditions. When connecting the Unit or Board, refer to the DIP switch settings shown in the following table. Pin Function Factory setting 1 Not used. Always set this pin to ON. ON 2 Built-in terminating resistance setting ON 3 ON: Connects terminating resistance. OFF: Disconnects terminating resistance. 2/4-wire setting OFF 4 2-wire: Set both pins to ON. 4-wire: Set both pins to OFF. OFF 5 Transmission mode (see note) ON Constant transmission: Set both pins to OFF. 6 Transmission performed when CTS signal in RS-232C interface is at high level: Set pin 5 to OFF and pin 6 to ON. OFF Transmission performed when CTS signal in RS-232C interface is at low level: Set pin 5 to ON and pin 6 to OFF. Note When connecting to a CS1-series CPU Unit, turn OFF pin 5 and turn ON pin 6. 67 Section Wiring 3-3 3-3-9 Connections for Host Link Communications Port connections for Host Link communications are shown in the following table. Up to 32 Units and Boards can be connected for 1:N connections. Port RS-232C Configuration 1:1 Schematic diagram, Serial Communications Board Computer to PC: C-mode or FINS commands Schematic diagram, Serial Communications Unit RS-232C RS-232C PC to computer: FINS commands RS-232C NT-AL001-E RS-422A/485 RS-232C Resistance ON 5-V power RS-232C 1:N RS-232C Computer to PC: C-mode or FINS commands RS-422A/485 NT-AL001-E Resistance ON 5-V power RS-232C Resistance ON NT-AL001-E RS-232C RS-422A/485 NT-AL001-E Resistance ON RS-232C 5-V power Resistance ON RS-232C NT-AL001-E RS-422A/485 RS-232C Resistance ON Resistance ON 5-V power NT-AL001-E RS-232C 1:1 NT-AL001-E Resistance ON RS-232C RS-232C --- Computer to PC: C-mode or FINS commands RS-232C PC to computer: FINS commands RS-422A/485 RS-422A/485 NT-AL001-E RS-232C NT-AL001-E RS-422A/485 Resistance ON 5-V power 1:N RS-422A/485 Resistance ON B500-AL001 --- RS-232C Computer to PC: C-mode or FINS commands NT-AL001-E Resistance ON 5-V power RS-422A /485 Resistance ON Note 1. Four-wire connections must be used for RS-422A/485 connections with Host Link communications. 2. “Resistance ON” indicates the terminating resistance must be turned ON. 3. “5-V power” indicates that a 5-V power supply is required for the Link Adapter. Refer to the Link Adapter manual for details. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications Board or Unit because power is supplied from pin 6 of the connector. 4. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. Connection Examples The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 3-4 RS-232C and RS-422A/485 Wiring for actual wiring methods. 68 Section Wiring 3-3 Host Computer Connections 1:1 Connections Using RS-232C Ports IBM PC/AT or Compatible Computers Serial Communications Board or Unit Computer Signal Pin RS-232C interface Pin Signal FG SD RD RTS CTS 5V DSR DTR SG CD RD SD DTR SG DSR RTS CTS CI RS-232C interface D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) Using NT-AL001-E Converting Link Adapters Computer Signal RS-232C Interface Shield RS-232C NT-AL001-E Link Adapter Pin Signal FG SD RD RTS CTS RS-422A Pin Signal NC SD RD RTS CTS 5V DSR DTR SG DSR DTR SG 5-V (+) power (–) Signal Pin Serial Communications Board or Unit NT-AL001-E Link Adapter Signal Pin RS-232C (See note) NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) D-sub, 9-pin D-sub, 9-pin connector (male) Pin Signal FG SD RD RTS CTS 5V DSR DTR SG RS-232C Interface D-sub, 9-pin connector (male) connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m ! Caution Do not use the 5-V power from pin 6 of the RS-232C port for anything but the NT-AL001-E Link Adapter. Using this power supply for any other external device may damage the Serial Communications Board/Unit or the external device. 69 Section Wiring 3-3 1:N Connections Using RS-232C Ports Computer Signal FG SD RS-232C RD Interface RTS CTS DSR DTR SG 5-V (+) power (–) Shield Pin Signal Signal Pin RS-422A Pin Signal NC SD RD RTS CTS 5V DSR DTR SG Terminal block D-sub, 9-pin connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF Serial Communications Board/Unit NT-AL001-E Link Adapter NT-AL001-E Link Adapter Signal Pin RS-232C Pin (See note) DIP Switch Settings Pin 1: ON Pin 2: OFF Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON NT-AL001-E Link Adapter Pin Signal D-sub, 9-pin connector (male) Serial Communications Board/Unit Signal Pin RS-232C Pin (See note) NC SD RD RTS CTS 5V DSR DTR SG DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON Signal FG SD RD RS-232C RTS Interface CTS 5V DSR DTR SG NC SD RD RTS CTS 5V DSR DTR SG Signal FG SD RD RS-232C RTS Interface CTS 5V DSR DTR SG D-sub, 9-pin connector (male) Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 70 Section Wiring 3-3 1:1 Connections Using RS-422A/485 Ports Computer NT-AL001-E Link Adapter Serial Communications Board Pin Signal Signal FG SD RS-232C RD Interface RTS CTS DSR DTR SG 5-V (+) power (–) Shield Pin Signal Pin Signal NC SD RD RTS CTS 5V DSR DTR SG RS-422A / 485 Interface Hood 4-wire Terminating resistance ON D-sub, 9-pin Terminal block connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF 71 Section Wiring 1:N Connections Using RS-422A/485 Ports Serial Communications Board B500-AL001 Link Adapter NT-AL001-E Link Adapter Computer Signal FG SD RS-232C RD Interface RTS CTS Pin Signal Pin Signal Shield RS-422A/ 485 Interface Hood 4-wire Terminating resistance OFF Signal Pin D-sub, 9-pin connector (male) D-sub, 9-pin Terminal block connector (male) 5-V (+) power (–) Pin Signal RS-422A/ 485 Interface NC SD RD RTS CTS 5V DSR DTR SG DSR DTR SG Shield Signal Pin Signal Pin Serial Communications Board Pin Signal DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF RS-422A/ 485 Interface Hood Shield 4-wire Terminating resistance ON Serial Communications Board NT-AL001-E Link Adapter Computer RS-422A Shield Signal RS-232C Interface FG SD RD RTS CTS DSR DTR SG 5-V (+) power (–) RS-232C Pin Signal Pin Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin Terminal block connector (male) RS-422A/ 485 Interface Hood 4-wire Terminating resistance OFF Serial Communications Board Pin Signal DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF 72 RS-422A/ 485 Interface Hood 4-wire Terminating resistance ON 3-3 Section Wiring 3-3 Programmable Terminal (PT) Connections Direct Connections from RS-232C to RS-232C Ports Serial Communications Board or Unit PT Signal Pin Pin Signal Hood FG -SD RD RS-232C RTS Interface CTS 5V --SG FG Hood FG SD RS-232C RD Interface RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) • Communications Mode: Host Link (unit number 0 only for Host Link) NT Link (1:N, N = 1 Unit only) • OMRON Cables with Connectors: XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 1:1 Connections from RS-422A/485 to RS-422A/485 Ports Serial Communications Board Signal Pin PT Short bar Signal RS-422A /485 Interface Hood D-sub, 9-pin connector (male) RS-422A /485 Interface Hood Terminal block or D-sub connector Communications Mode: Host Link (unit number 0 only for Host Link) NT Link (1:N, N = 1 Unit only) Note Serial Communications Board settings: Terminating resistance ON, 4-wire. 73 Section Wiring 3-3 1:N, 4-wire Connections from RS-422A/485 to RS-422A/485 Ports Serial Communications Board Signal Pin Signal RS-422A /485 Interface RS-422A /485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block or D-sub connector Short bar Signal RS-422A /485 Interface FG Terminal block or D-sub connector Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 4-wire. 1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports Serial Communications Board Signal Pin Signal RS-422A /485 Interface RS-422A /485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block or D-sub connector Short bar Signal RS-422A /485 Interface FG Terminal block or D-sub connector Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 2-wire. 74 Section Wiring 3-3 3-3-10 Connections for Protocol Macros This section describes the connections for protocol macros. Up to 32 Boards or Units can be used for 1:N connections. Port RS-232C Configuration 1:1 Schematic diagram, Serial Communications Board RS-232C Schematic diagram, Serial Communications Unit RS-232C RS-232C interface RS-232C interface NT-AL001-E Resistance ON 5-V power NT-AL001-E RS-232C RS-422A/485 Resistance ON NT-AL001-E Resistance ON RS-232C interface RS-232C interface NT-AL001-E NT-AL001-E RS-422A/485 RS-232C Resistance ON RS-232C 1:N RS-422A/ 485 interface RS-422A/ 485 interface RS-422A/485 interface RS-232C RS-422A/485 RS-232C NT-AL001-E Resistance ON RS-422A/485 interface NT-AL001-E RS-232C RS-422A/485 Resistance ON RS-422A/485 Resistance ON NT-AL001-E RS-232C RS-422A/485 interface B500-AL001-E Resistance ON NT-AL001-E Resistance ON NT-AL001-E Resistance ON RS-422A/485 Resistance ON 5-V power RS-422A/485 interface B500-AL001-E RS-232C RS-422A Resistance /485 ON Resistance RS-422A /485 ON NT-AL001-E RS-232C NT-AL001-E Resistance ON 5-V power RS-422A/485 RS-232C RS-232C RS-232C Resistance ON RS-232C interface NT-AL001-E NT-AL001-E RS-232C interface RS-232C RS-232C Resistance ON RS-422A/485 RS-232C Resistance ON 5-V power RS-232C RS-232C 75 Section Wiring Port RS-422A/ 485 Configuration 1:1 Schematic diagram, Serial Communications Board RS-422A/485 interface RS-422A/485 NT-AL001-E 3-3 Schematic diagram, Serial Communications Unit --- RS-232C interface RS-232C RS-422A/485 Resistance ON 5-V power RS-422A/ 485 1:N RS-422A/485 interface Resistance ON --- RS-422A/485 Resistance ON RS-422A/485 interface B500-AL001-E Resistance ON RS-422A/485 Resistance ON NT-AL001-E RS-232C interface RS-232C Resistance ON RS-422A/485 Resistance ON 5-V power Note 76 RS-232C RS-232C 1. The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support. 2. The combined cable length for RS-422A/485 is 500 m including branch lines. 3. The maximum cable length is limited to 2 m when an NT-AL001-E Link Adapter is connected. 4. Branch lines must be a maximum of 10 m long. Section Wiring 3-3 Connection Examples The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-pair cables. Refer to 3-4 RS-232C and RS-422A/485 Wiring for actual wiring methods. Connecting RS-232C Ports 1:1 Connections to E5CK Controller Serial Communications Unit or Board Signal Pin FG SD RD RTS CTS DSR DTR SG OMRON E5CK Controller RS-232C: Terminal Block Terminal Signal SD RD SG RS-232C Shield D-sub, 9-pin connector (male) Connections to a Personal Computer with RTS-CTS Flow Control Serial Communications Board or Unit RS-232C port Computer FG SD RD RTS CTS FG SD RD RTS CTS 5V DSR DTR SG DSR DTR SG Connecting a Host Computer with NT-AL001-E Converting Link Adapters Serial Communications Board or Unit RS-232C NT-AL001-E Link Adapter Signal Pin Shield Pin Signal RS-232C Interface FG SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) NT-AL001-E Link Adapter Signal Pin Pin RS-422A NC SD RD RTS CTS 5V DSR DTR SG Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG Computer RS-232C Signal FG SD RD RS-232C RTS Interface CTS DSR DTR SG (See note) Terminal block D-sub, 9-pin connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF (4-wire) Pin 4: OFF Pin 5: OFF Pin 6: ON DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF (4-wire) Pin 4: OFF Pin 5: OFF Pin 6: OFF 5-V (+) power (–) Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 77 Section Wiring Connections to a Modem Modem FG SD RD RTS CTS DSR SG CD ST2 RT DTR CI ST1 78 Serial Communications Board or Unit RS-232C port FG SD RD RTS CTS 5V DSR DTR SG 3-3 Section Wiring 3-3 1:N Connections Using RS-232C Ports Device supporting RS-422A/485 communications (4-wire) Serial Communications Unit or Board NT-AL001-E Signal Pin RS-232C Pin Signal Signal Pin Shield RS-232C interface FG SD RD RTS CTS 5V DSR DTR SG NC SD RD RTS CTS 5V DSR DTR SG Terminal block D-sub, 9-pin connector (male) DIP SW Pin 1: ON Pin 2: ON Terminating resistance Pin 3: OFF 4-wire Pin 4: OFF Pin 5: OFF Pin 6: ON Serial Communications Unit or Board NT-AL001-E RS-232C Pin Signal Signal Pin Signal Pin Shield RS-232C interface FG SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) Signal RS-422A /485 interface Device supporting RS-422A/485 communications (4-wire) Signal (See note) D-sub, 9-pin connector (male) RS-422A Shield NC SD RD RTS CTS 5V DSR DTR SG (See note) Terminal block D-sub, 9-pin connector (male) RS-422A /485 interface Device supporting RS-422A/485 communications (2-wire) Signal RS-422A /485 interface Device supporting RS-422A/485 communications (2-wire) Signal RS-422A /485 interface DIP SW Pin 1: ON Pin 2: ON Terminating resistance Pin 3: ON 2-wire Pin 4: ON Pin 5: OFF Pin 6: ON Note We recommend using the following NT-AL001-E Link Adapter Connecting Cables to connect to NT-AL001-E Link Adapters. XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 79 Section Wiring 1:1 Connections Using RS-422A/485 Ports Device supporting RS-422A/485 communications (2-wire) Serial Communications Board Signal Pin Shield Signal Pin /485 interface RS-422A /485 interface Serial Communications Board Signal RS-422A RS-422A /485 interface Hood Hood D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) Serial Communications Board RS-422A Signal Pin Shield RS-422A /485 interface Hood D-sub, 9-pin connector (male) Pin Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) DIP Switch Settings Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: OFF 80 Computer NT-AL001-E Link Adapter Signal RS-232C FG SD RD RS-232C RTS Interface CTS DSR DTR SG 5-V (+) power (–) Shield Device supporting RS-422A/485 communications (4-wire) Signal RS-422A /485 interface 3-3 Section Wiring 3-3 1:N Connections Using RS-422A/485 Ports Device supporting RS-422A/485 communications (2-wire) Serial Communications Board Signal Pin Signal RS-422A/ 485 interface RS-422A/ 485 interface Hood Device supporting RS-422A/485 communications (2-wire) D-sub, 9-pin connector (male) Signal RS-422A/ 485 interface Device supporting RS-422A/485 communications Shield (4-wire) Serial Communications Board Signal Pin Pin Signal RS-422A/ 485 Interface Signal Signal Pin RS-422A/ 485 interface RS-422A/ 485 interface Hood D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) Signal Pin Device supporting RS-422A/485 communications (4-wire) Shield Signal RS-422A/ 485 interface Serial Communications Board NT-AL001-E Link Adapter Signal Pin Pin Signal RS-422A/ 485 Interface Pin Shield Shield Signal FG SD RD RTS CTS NC SD RD RTS CTS 5V DSR DTR SG Hood D-sub, 9-pin con4-wire Terminating nector (male) resistance ON Signal RS-232C Interface DSR DTR SG DIP Switch D-sub, 9-pin conPin 2: OFF, nector (male) otherwise same as below. (+) 5-V (–) power NT-AL001-E Link Adapter Pin DIP Switch Pin 1: ON Pin 2: ON (terminating resistance) Pin 3: OFF Pin 4: OFF Pin 5: OFF Pin 6: ON Signal Signal Pin NC SD RD RTS CTS 5V DSR DTR SG Shield Terminal block D-sub, 9-pin connector (male) Shield Signal FG SD RD RTS CTS RS-232C Interface DSR DTR SG (+) 5-V (–) power 81 Section Wiring 3-3 3-3-11 1:N NT Link Connections with Programmable Terminals The connections used for each port type in NT Link mode are the same as for protocol macro mode. See 3-3-10 Connections for Protocol Macros. Up to eight Units or Boards can be used for a 1:N connection. Direct Connections from RS-232C to RS-232C Ports Serial Communications Board or Unit PT Signal Pin Pin Signal Hood FG -SD RD RS-232C RTS Interface CTS 5V --SG FG Hood FG SD RS-232C RD Interface RTS CTS 5V DSR DTR SG D-sub, 9-pin connector (male) D-sub, 9-pin connector (male) • Communications Mode: Host Link (unit number 0 only for Host Link) NT Link (1:N, N = 1 Unit only) • OMRON Cables with Connectors: XW2Z-070T-1: 0.7 m XW2Z-200T-1: 2 m 1:N, 4-wire Connections from RS-422A/485 to RS-422A/485 Ports Serial Communications Board Signal Pin PT Signal RS-422A /485 Interface RS-422 A/485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block or D-sub connector Short bar PT Signal RS-422A /485 Interface FG Terminal block or D-sub connector Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 4-wire. 82 Section RS-232C and RS-422A/485 Wiring 3-4 1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports Serial Communications Board Signal PT Signal Pin RS-422A/ 485 Interface RS-422A /485 Interface Hood D-sub, 9-pin connector (male) FG Terminal block Short bar PT Signal RS-422A /485 Interface FG Terminal block Communications Mode: 1:N NT Link Note Serial Communications Board settings: Terminating resistance ON, 2-wire. 3-3-12 Connections in Loopback Test Connect the communications ports as shown below. Serial Communications Board or Unit RS-232C port Pin Signal SD RD RTS CTS FG DTR DSR 3-4 Serial Communications Board RS-422A/485 port Pin Signal RS-232C and RS-422A/485 Wiring 3-4-1 Recommended RS-232C Wiring Examples It is recommended that RS-232C cables be connected as described below especially when the Serial Communications Board or Unit is used in an environment where it is likely to be subject to electrical noise. 1, 2, 3... 1. Always use shielded twisted-pair cables as communications cables. Model UL2464 AWG28x5P IFS-RVV-SB (UL product) AWG28x5P IFVV-SB (non-UL product) UL2464-SB (MA) 5Px28AWG (7/0.127) (UL product) CO-MA-VV-SB 5Px28AWG (7/0.127) (non-UL product) Manufacturer Fujikura Ltd. Hitachi Cable, Ltd. 2. Combine signal wires and SG (signal ground) wires in a twisted-pair cable. At the same time, bundle the SG wires to the connectors on the Serial Communications Board/Unit and the remote device. 3. Connect the shield of the communications cable to the Hood (FG) terminal of the RS-232C connector on the Serial Communications Board/Unit. At the same time, ground the ground (GR) terminal of the Power Supply Unit on the CPU Rack or CS1 Expansion Rack to 100 Ω or less. 83 Section RS-232C and RS-422A/485 Wiring 3-4 4. A connection example is shown below. Example: Twisted-pair Cable Connecting SD-SG, RD-SG, RTS-SG, and CTS-SG Terminals Actual Wiring Example Serial Communications Board/Unit Pin Twist the shaded lines to make SG signal wires them thinner and connect to Pin No. 1 (FG). Cover this section with heat-shrink tube to avoid contact with other sections. Remote device Signal Signal SD RD RTS CTS SG Hood FG FG RD SD CTS RTS SG FG Bundle the SG wires. Aluminum foil Shield XM2S-0911-E Note The Hood (FG) is internally connected to the ground terminal (GR) on the Power Supply Unit via the CPU Rack or CS1 Expansion Rack. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Although there is conductivity between the Hood (FG) and pin 1 (FG), connect the Hood (FG) to the shield because the Hood (FG) has smaller contact resistance with the shield than pin 1 (FG), and thus provides better noise resistance. Serial Communications Board/Unit Power Supply Unit Hood and GR are internally connected. Ground to 100 Ω or less Grounding the GR terminal grounds the Hood (FG). 3-4-2 Recommended RS-422A/485 Wiring Examples Recommended RS-422A/485 Cable 1, 2, 3... 1. Always use shielded twisted-pair cables as communications cables. Model CO-HC-ESV-3Px7/0.2 Manufacturer Hirakawa Hewtech Corp. 2. Connect the shield of the communications cable to the Hood (FG) of the RS-422A/485 connector on the Serial Communications Board or Unit. At the same time, ground the ground (GR) terminal of the Power Supply Unit on the CPU Rack or CS1 Expansion Rack to 100 Ω or less. Note Always ground the shield only at the Board/Unit end. Grounding both ends of the shield may damage the device due to the potential difference between the ground terminals. 84 Section RS-232C and RS-422A/485 Wiring 3-4 Connection examples are shown below. 2-Wire Connections Serial Communications Board/Unit Remote device Pin Signal Signal Hood Shield 4-Wire Connections Serial Communications Board/Unit Pin Remote device Signal Signal Hood Shield Using a B500-AL001-E Link Adapter Serial Communications Board/Unit Pin Signal B500-AL001 Pin Signal Remote device Signal Signal Pin RS-422 interface Hood Signal Pin Remote device Signal • With NT-AL001-E RS-232C/RS-422 Link Adapter Serial Communications Board/Unit Pin Signal NT-AL001-E Pin Signal RD SD CTS RTS 5V DSR DTR SG SD RD RTS CTS 5V DSR DTR SG Hood FG Shield (See note.) Signal Pin Remote device Signal Remote device Signal 85 Section RS-232C and RS-422A/485 Wiring 3-4 Note The following cables are available for this connection. Length Model 70 cm XW2Z-070T-1 2m XW2Z-200T-1 It is recommended that one of these cables be used to connect the RS-232C port on the Serial Communications Board or Unit to the NT-AL001-E RS-232C/ RS-422 Link Adapter. Note The Hood (FG) is internally connected to the ground terminal (GR) on the Power Supply Unit via the CPU Rack or CS1 Expansion Rack. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit. Serial Communications Board/Unit Power Supply Unit Hood and GR are internally connected. Ground to 100 Ω or less Grounding the GR terminal grounds the Hood (FG). 3. Be sure to turn ON the terminating resistance at the last Unit at the end of the RS-422A/485 cable. 3-4-3 Wiring Connectors Use the following steps to wire connectors. Cable Preparation See the following diagrams for the length of the cable portion to be cut in each step. Shield Connected to Hood (FG) 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield. 25 mm (RS-422A) 40 mm (RS-232C) 86 Section RS-232C and RS-422A/485 Wiring 3-4 3. Trim off the braided shield using scissors so that the remaining shield length is 10 mm. 10 mm 4. Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm. 5 mm 5. Fold back the braided shield. 6. Wrap aluminum foil tape around the folded shield. Aluminum foil tape Shield Not Connected to Hood (FG) 1, 2, 3... 1. Cut the cable to the required length. 2. Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield. 25 mm (RS-422A) 40 mm (RS-232C) 3. Trim off all the braided shield using scissors. 4. Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm. 5 mm 5. Wrap adhesive tape around the conductor from which the braided shield was removed. Adhesive tape 87 Section RS-232C and RS-422A/485 Wiring 3-4 3-4-4 Soldering 1, 2, 3... 1. Thread a heat-shrinking tube through each conductor. 2. Temporarily solder each conductor to the corresponding connector terminals. 3. Completely solder each conductor. Soldering iron Heat-shrinking tube Inside diameter: 1.5 mm, l = 10 4. Return the heat-shrinking tube to the soldered portion, then heat the tube to shrink it in place. Heat-shrinking tube 3-4-5 Assembling Connector Hood Assemble the connector hood as shown below. End connected to FG Adhesive tape End not connected to FG Aluminum foil tape Grounding plate 88 RS-232C and RS-422A/485 Wiring Section 3-4 3-4-6 Connecting to Unit Tighten the screws firmly with your fingers. 89 SECTION 4 Using Host Link Communications This section describes the procedure and other information required to use Host Link communications. 4-1 4-2 4-3 4-4 4-5 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2-2 Setup Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-1 Auxiliary Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-1 Simultaneous Commands and Communications Ports . . . . . . . . . . . . . . . . . . . . . 4-4-2 Communications Control Signals and Communications Timing . . . . . . . . . . . . . 4-4-3 Flags for Network Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-4 Timing of Commands Addressed to a Host Computer . . . . . . . . . . . . . . . . . . . . . 4-4-5 Reception Buffers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4-6 Error Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5-1 RS-232C Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5-2 RS-422A/485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 92 92 94 96 96 97 99 99 100 100 101 103 103 103 103 105 91 Section Setup Area Allocations 4-1 4-2 Host Link Communications Host Link System can be used to send C-mode commands or FINS commands from a host computer (e.g., personal computer or PT) to a PC to read/write I/O memory, control operating modes, etc. The PC can also use the SEND(090), RECV(098), and CMND(490) instructions to send FINS commands to the host computer for “slave-initiated communications.” Using the PC to control communications enables controlling and monitoring of the overall system operating status. Refer to the CS1-series Communications Commands Reference Manual (W342) for details on C-mode and FINS commands. Host-initiated Communications Communications in a Host Link System are normally started by the host computer. Command Host computer CS1-series PC Response The host computer sends a command to the PC. The PC processes the command and returns a response to the host computer. This process is repeated, allowing the host computer to monitor and control PC operation. Both C-mode and FINS commands can be used in host-initiated communications. PC-initiated Communications The PC can also initiate communications with the host computer, as may be necessary when errors occur on the line controlled by the PC or to confirm the operating status of the host computer. Command Host computer CS1-series PC Response The PC sends a command to the host computer through a Serial Communications Unit or Board. The host computer processes the command and, when necessary, returns a response to the PC. Using PC-initiated communications requires that a program be prepared on the host computer to process commands received from a PC and return the required responses. Only FINS commands can be used in PC-initiated communications. Note Always transfer uppercase letters when using Host Link communications. Lowercase letters cannot be processed. 4-2 Setup Area Allocations This section describes the Setup Area allocated to the Serial Communications Board and Serial Communications Units in the DM Area when Host Link communications are used. 4-2-1 Setup Area Words The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when Host Link communications are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to the unit numbers). 92 Section Setup Area Allocations Serial Communications Board 4-2 Setup Area Allocated in the DM Area: D32000 to D32099 Words Usage D32000 to D32003 Port 1 Settings D32010 to D32013 Port 2 Settings D32004 to D32009 Not used in Host Link Communications D32014 to D32019 D32020 to D32767 Serial Communications Units Reserved for the system Setup Area Allocated in the DM Area: D30000 to D31599 First Word in Setup Area Allocated in the DM Area: m = D30000 + 100 unit number Unit No. Words Unit No. 0 D30000 to D30099 m to m + 3: Port 1 Settings Unit No. 1 D30100 to D30199 m + 10 to m + 13: Port 2 Settings Unit No. 2 D30200 to D30299 Unit No. 3 D30300 to D30399 m + 14 to m + 9 and m + 14 to m + 19: Not used in Host Link communications Unit No. 4 D30400 to D30499 Unit No. 5 D30500 to D30599 Unit No. 6 D30600 to D30699 Unit No. 7 D30700 to D30799 Unit No. 8 D30800 to D30899 Unit No. 9 D30900 to D30999 Unit No. A D31000 to D31099 Unit No. B D31100 to D31199 Unit No. C D31200 to D31299 Unit No. D D31300 to D31399 Unit No. E D31400 to D31499 Unit No. F D31500 to D31599 m + 20 to m + 99: Reserved for the system 93 Section Setup Area Allocations 4-2 4-2-2 Setup Area Contents m = D30000 + 100 Words Board Port 1 Port 2 D32000 D32010 Bit Unit Port 1 Port 2 m m + 10 D32001 D32011 m+1 m + 11 D32002 D32012 m+ 2 m + 12 D32003 D32013 m+3 m + 13 Port Settings Unit No. Setting contents 15 12 to 14 08 to 11 Port settings 0: Defaults; 1: User settings Reserved Serial communications mode 0: Default (Host Link) 5: Host Link 05 to 07 04 Reserved Start bits 0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting) Data length 0: 7 bits; 1: 8 bits Stop bits 0: 2 bits; 1: 1 bit Parity 0: Yes; 1: No Parity 0: Even; 1: Odd Reserved Baud rate (bps) 0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200; 8: 38,400; 9: 57,600; A: 115,200 03 02 01 00 04 to 15 00 to 03 15 00 to 14 15 08 to 14 00 to 07 Send delay time 0: Default (0 ms); 1: Setting in bits 00 to 14 Send delay (0000 to 7530 hex) (Unit: 10 ms) CTS control 0: No; 1:Yes Reserved Host Link unit number (00 to 1F hex) The setting for the port settings determine if the default settings or user settings will be used for port 1 and port 2. Be sure to use the same settings as the RS-232C port on the host computer connected via the Host Link System. If the default port settings are specified, then the setting of bits 00 to 04 and the baud rate in D32001 will be ignored. The default settings used are as follows: Baud rate: 9,600 bps, start bits: 1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits. If user port settings are specified, set bits 00 to 04 and set the baud rate in D32001. Setting Example: 0100 Hex = Host link mode with default port settings. Serial Communications Mode Set the serial communications mode to 5 Hex to use Host Link communications. The default setting of 0 Hex can also be used to operate in Host Link mode with unit number 00. Start Bits, Data Length, Stop Bits, Parity, Baud Rate If user settings are specified for the port settings, the number of start bits, data length, number of stop bits, parity, and baud rate must be set. The start bits setting, however, will be ignored and 1 start bit will always be used. Do not set the baud rate setting to between B and F. A setup error will occur if these settings are used, and the default setting of 9,600 bps will be used. Do not use setting 1 and 2, which are reserved for the system. 94 Section Setup Area Allocations Send Delay 4-2 If response frames cannot be completely received regardless of the communications processing used at the host computer, a send delay can be set for the response. Any setting higher than 7530 Hex will be treated as 7530 Hex. Case 1 Serial Communications Board or Unit Response sent Host computer Send delay Command sent Case 2 Serial Communications Board or Unit Second command frame First command frame Host computer Delimiter Send delay Case 3 Serial Communications Board or Unit SEND(090), RECV(098) or CMND(490) Host computer Command sent Send delay CTS Control Response sent If CTS control is enabled, the RTS signal is turned ON before starting to transfer and then the send is started after confirming that the CTS signal is ON. If CTS control is not enabled, the RTS signal is turned ON before starting to transfer and then the send is started without checking the status of the CTS signal. CTS Control No CTS Control Send processing Send processing RTS = ON RTS = ON N CTS = ON? Y Host Link Unit Number N N One character sent One character sent All characters sent? All characters sent? Y Y RTS = OFF RTS = OFF Send processing ended Send processing ended Set the setting to 00 to 1F Hex to set Host Link unit numbers 0 to 31. 95 Section Auxiliary Area and CIO Area Allocations 4-3 4-3 Auxiliary Area and CIO Area Allocations This section describes the bits and words used by the Serial Communications Board and Serial Communications Units in the Auxiliary Area and the Status Area allocated in the CIO Area. The Software Switches allocated in the CIO Area are not used for Host Link communications. 4-3-1 Auxiliary Area Allocations Port 1 and Port 2 Port Settings Change Bits These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used. Serial Communications Board Word A636 Bit 03 to 15 02 01 00 Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved Serial Communications Units Words n Inner Board Error Information (Serial Communications Board Only) Bit 03 to 15 02 01 00 n = A620 + unit number Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved A424 contains error information for the Serial Communications Board. Word A424 Bit 12 to 15 11 10 Contents Non-fatal errors (Note 1) Reserved 1 Error log EEPROM error; 0: Normal 1: Protocol macro execution error; 0: Normal This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area, 09 08 07 06 05 04 03 02 01 00 Note 96 Fatal errors (Note 2) 1: Protocol data error (SUM error); 0: Normal 1: Setup error; 0: Normal 1: Routing table error; 0: Normal Reserved 1: Cyclic monitoring error; 0: Normal Reserved Reserved Reserved 1: Inner Bus error; 0: Normal 1: Inner Board watchdog timer error; 0: Normal 1. When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag) (nonfatal error) will be ON. 2. When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON. For details on errors, refer to Section 8 Troubleshooting and Maintenance. Section Auxiliary Area and CIO Area Allocations 4-3 4-3-2 CIO Area Allocations Words in the CIO Area are allocated for a Status Area, which contains status and error information for the Serial Communications Board or Unit. These allocations are described in this section. Serial Communications Board Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status Area. Only the words shown in the following table are used for the Status Area with Host Link communications. Inner Board CIO Area CIO 1900 to CIO 1999 Words Serial Communications Units Board status CIO 1905 to CIO 1908 Port 1 status CIO 1915 to CIO 1918 Port 2 status Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. Only the words shown in the following table are used for the Status Area with Host Link communications. CPU Bus Unit Area CIO 1500 to CIO 1899 n = CIO 1500 + 25 unit number Unit No. Status Area Words Unit No. 0 CIO 1500 to CIO 1524 n + 1 to n + 4: Unit status Unit No. 1 CIO 1525 to CIO 1549 n + 5 to n + 8: Port 1 status Unit No. 2 CIO 1550 to CIO 1574 n + 15 to n + 18: Port 2 status Unit No. 3 CIO 1575 to CIO 1599 Unit No. 4 CIO 1600 to CIO 1624 Unit No. 5 CIO 1625 to CIO 1649 Unit No. 6 CIO 1650 to CIO 1674 Unit No. 7 CIO 1675 to CIO 1699 Unit No. 8 CIO 1700 to CIO 1724 Unit No. 9 CIO 1725 to CIO 1749 Unit No. A CIO 1750 to CIO 1774 Unit No. B CIO 1775 to CIO 1799 Unit No. C CIO 1800 to CIO 1824 Unit No. D CIO 1825 to CIO 1849 Unit No. E CIO 1850 to CIO 1874 Unit No. F CIO 1875 to CIO 1899 The Status Area is used for status information input from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status. n = CIO 1500 + 25 unit number Words Board Port 1 Port 2 CIO 1901 CIO 1902 Usage CIO 1901 to CIO 1904 Units Port 1 Port 2 n+1 n+2 Bit 02 to 15 01 00 00 to 15 Contents Reserved 1: Error log EEPROM error 1: Protocol data error Reserved 0: Error log EEPROM normal 0: Protocol data normal 97 Section Auxiliary Area and CIO Area Allocations Bit Words Board Units Port 1 Port 2 Port 1 Port 2 CIO 1903 n+3 CIO 1904 n+4 CIO 1905 CIO 1915 n+5 n + 15 CIO 1906 CIO 1916 n+6 n + 16 Contents 00 to 15 Reserved 00 to 15 Reserved 12 to 15 08 to 11 05 to 07 04 03 02 01 00 15 Port setting status 14 n+7 n + 17 11 to 15 10 09 08 07 06 05 04 03 00 to 02 CIO 1908 CIO 1918 n+8 n + 18 Note 15 05 to 14 04 03 02 00, 01 Serial communications mode (Note 1) Baud rate (Note 1) Reserved Start bits: Always 1 Data length: 7 or 8 bits (Note 1) Stop bits: 1 or 2 bits (Note 1) Parity: Yes/No (Note 1) Parity: Even/Odd (Note 1) 0: No; 0: RS-232C; 1: RS-422A/485; 1: Reserved 0: 1: 0: 1: Reserved 0: Terminating resistance OFF 1: Terminating resistance ON Reserved 1: Setup error; 0: Setup normal 1: Port operating; 0: Port stopped 02 to 12 01 00 CIO 1917 Setup settings Hardware settings 13 CIO 1907 4-3 Commu- Reserved nications 1: Remote Unit busy receiving (Flow control) status 0: Remote Unit ready to receive (Note 2) Reserved 1: Local Unit busy receiving (Flow control) 0: Local Unit ready to receive (Note 3) TransER signal mission DTR signal control Reserved signal status CTS signal RTS signal Reserved Transmission error status 1: Transmission error; 0: No transmission error Not used. 1: Overrun error; 0: Normal 1: Framing error; 0: Normal 1: Parity error; 0: Normal Reserved 1. The settings in the Setup Area are reflected here. The default settings will be used and will be stored here if a setup error occurs. 2. The status of this bit is not stable in Host Link mode. 3. Always 0 in Host Link mode. Error Log EEPROM Error 98 This bit will be set to 1 if an error occurs in reading or writing the error log stored in EEPROM on the assumption that the EEPROM has reached its useful life. If a Serial Communications Unit is being used, the ERC indicator will also light. If a Serial Communications Board is being used, A42411 will turn ON and the ERR/ ALM indicator on the CPU Unit will flash, indicating a non-fatal error. Section Communications Timing 4-4 Protocol Data Error This bit will be turned ON if a checksum error is detected in the protocol data at startup. The checksum is checked for all serial communications modes. If a Serial Communications Unit is being used, the ERC indicator will also flash. If a Serial Communications Board is being used, A42409 will turn ON, the ERR/ALM indicator on the CPU Unit will flash, and the RDY indicator will flash at 1-second intervals, indicating a non-fatal error. The operation of Host Link communications is not affected by a protocol data error. Port Setting Status The settings in the Setup Area for the following items will be stored: Serial communications mode, baud rate, start bits, data length, stop bits, parity, ports, terminating resistance, setup error, and port operating/stopped status. The port operating/stopped status will always be 1 for Host Link mode. Communications Status The flow control and buffer status is stored. These bits are cleared at startup or when a port is restarted using STUP(237) or a Port Settings Change Bit (Auxiliary Area). Transmission Control Signal Status The status of the following transmission control signals is stored: ER signal, DTR signal, CTS signal, and RTS signal. 1: High, 0: Low Transmission Error Status The Transmission Error Flag (bit 15) will turn ON if any of the following flags turn ON: Overrun Error (bit 04), Framing Error (bit 03), or Parity Error (bit 02). 4-4 Communications Timing This section describes the timing of sending commands and controlling communications in the Host Link mode. 4-4-1 Simultaneous Commands and Communications Ports The CS1-series CPU Units provide eight logical ports that can be used when executing SEND(090), RECV(098), and CMND(490). Therefore, up to eight commands can be executed for one physical port during any one cycle. The maximum number of messages, however, that can be sent or received in one CPU Bus Unit service time is two messages from the CPU Unit to the Board or Unit and two messages from the Board or Unit to the CPU Unit. Board or Unit CPU Unit Logical port 5 Instruction 1 1 Instruction 2 6 Instruction 3 3 Instruction 4 7 Instruction 5 2 Instruction 6 0 Instruction 7 4 Instruction 8 One port must be specified for each instruction. Note 1. If more than eight communications instructions are being used, then exclusive control must be performed to make sure that not more than eight are executed at the same time. Refer to descriptions of network communications instructions in the CS1-series Communications Commands Reference Manual (W342). 2. The same communications port numbers are used by both the communications instructions (SEND(090), RECV(098), and CMND(490)) and the PROTOCOL MACRO instruction (PMCR(260)). The same port number cannot be used by more than one of these instructions at the same time. 99 Section Communications Timing 4-4 4-4-2 Communications Control Signals and Communications Timing If CTS control is enabled in the Setup Area, the RTS output signal will be turned ON from the Board or Unit and the send process will go on standby until the CTS input signal turns ON. Either release this busy status by incorporating the RTS output signal for the CTS input signal at the host computer, or loop the RTS output signal back to the CTS input signal at the Unit or Board. Note The status of the RTS and CTS signals can be confirmed in the Transmission Control Signal Status in the Status Area. Refer to page 97. 4-4-3 Flags for Network Communications This section describes the flags in the Auxiliary Area that are used when executing SEND(090), RECV(098), and CMND(490). Communications Port Enabled Flags A Communications Port Enabled Flag turns ON when SEND(090), RECV(098), and CMND(490) can be executed. The flag will turn OFF during execution of these commands and turn ON again when the command execution is completed. When creating the ladder diagram, use these flags as input conditions when executing these instructions. Word A202 Communications Port Error Flags Bit 08 to 15 07 06 05 04 03 02 01 00 Content Reserved Communications Port Enabled Flag, Port No. 7 Communications Port Enabled Flag, Port No. 6 Communications Port Enabled Flag, Port No. 5 Communications Port Enabled Flag, Port No. 4 Communications Port Enabled Flag, Port No. 3 Communications Port Enabled Flag, Port No. 2 Communications Port Enabled Flag, Port No. 1 Communications Port Enabled Flag, Port No. 0 A Communications Port Error Flag will turn ON in the following cases. • When an error is generated during execution of SEND(090), RECV(098), or CMND(490). • When an error response or retry error has been generated for the port. These Flags will turn OFF when the corresponding Communications Port Enabled Flag is turned OFF at the start of operation or at the start of executing the SEND(090), RECV(098), or CMND(490). Word A219 Communications Port Completion Codes 100 Bit 08 to 15 07 06 05 04 03 02 01 00 Content Reserved Communications Port Error Flag, Port No. 7 Communications Port Error Flag, Port No. 6 Communications Port Error Flag, Port No. 5 Communications Port Error Flag, Port No. 4 Communications Port Error Flag, Port No. 3 Communications Port Error Flag, Port No. 2 Communications Port Error Flag, Port No. 1 Communications Port Error Flag, Port No. 0 The Communications Port Completion Code words will contain the FINS end code after SEND(090), RECV(098), or CMND(490) has been executed. Section Communications Timing 4-4 If the Communications Port Enabled Flag turns OFF when operation is started or SEND(090), RECV(098), or CMND(490) are executed, the contents of these words will be cleared. Word Content A203 Communications Port Completion Code, Port No. 0 A204 Communications Port Completion Code, Port No. 1 A205 Communications Port Completion Code, Port No. 2 A206 Communications Port Completion Code, Port No. 3 A207 Communications Port Completion Code, Port No. 4 A208 Communications Port Completion Code, Port No. 5 A209 Communications Port Completion Code, Port No. 6 A210 Communications Port Completion Code, Port No. 7 A211 to A218 Reserved Flag Transitions Communications Port Enabled Flag Network communications instructions (PMCR(260)/SEND(090)/ RECV(098)/CMND(490)) Instruction 1 being executed Instruction 2 being executed Instruction 3 being executed Communications Port Error Flag Communications Port Completion Code (Normal end) End of previous processing (No unit corresponding to unit address) (Normal end) 4-4-4 Timing of Commands Addressed to a Host Computer Commands addressed to a host computer are sent at the timing shown in the following diagrams. Host Computer Sending Data Response Required Host computer Serial Communications Board/Unit Command (1) Command Response (2) Response Communications Port Enabled Flag Command acknowledged Command completed No Response Required Host computer Serial Communications Board/Unit Command (1) Command (2) Response Communications Port Enabled Flag Command acknowledged Command completed Command transmission to the host computer can start even when the port is receiving a command from the host computer (1). The transmission of a response to the command from the host computer is postponed until the transmission of the command to the host computer is completed (2). 101 Section Communications Timing 4-4 When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port. Host Computer Receiving Data Response Required Host computer (1) (2) Response Command Command Serial Communications Board/Unit Response Communications Port Enabled Flag Command completed Command acknowledged No Response Required (1) (2) Response Command Command Host computer Serial Communications Board/Unit Communications Port Enabled Flag Command completed Command acknowledged At (1) in the diagram, the response to a command sent from the host computer is being transmitted from the port. In this case, the command transmission to the host computer is postponed until the response transmission is completed (2). When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port. Response Wait Time After Host Computer Sends Data Response Required Response Command Host computer (1) Serial Communications Board/Unit Command Response wait time Response (2) Communications Port Enabled Flag Command completed Command acknowledged No Response Required Command Host computer (1) Command Serial Communications Board/Unit Response wait time Response (2) Communications Port Enabled Flag Command acknowledged Command completed When response wait time has been set in the command format from the host computer, commands to the host computer will not be transmitted until the response time has elapsed (1). Transmission of responses to commands from the host computer will be postponed until the command transmission to the host computer has been completed (2). 102 Changes from Previous Products Section 4-5 When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port. 4-4-5 Reception Buffers In Host Link mode, each port has a reception buffer of 1,200 bytes. This is sufficient to hold the maximum Host Link frame length for an FA command response frame (1,115 bytes) + 85 bytes. If a frame larger than 1,200 bytes is sent from the host computer (from @ to the carriage return), the frame will be discarded and no response will be returned. 4-4-6 Error Responses When Host Link FA commands are used for FINS commands, an error code will returned as the end code in the FINS response whenever there is a mistake in the FINS command settings or an FINS response is required that is too long for the legal response frame. An end code of 110B Hex is returned when the response exceeds the maximum response length. The Host Link response frame will contain the requested read data after the end code through the end of the maximum legal response frame length. 4-5 Changes from Previous Products There are differences between Host Link Systems created using the CS1-series Serial Communications Boards and Unit in comparison to Host Link Systems created with Host Link Units and CPU Units in other PC product series. These differences are described in this sections. 4-5-1 RS-232C Ports Take the following differences into consideration when changing from an existing Host Link System to one using an RS-232C port on a CS1-series CPU Unit, Serial Communications Boards, or Serial Communications Unit (CS1H/GCPUjj RS-232C port, CS1W-SCU21 ports, CS1W-SCB21 ports, or CS1WSCB41 port 1). 103 Section Changes from Previous Products Previous products C-series Host Link Units Model number Changes required for CS1-series product Wiring 3G2A5-LK201-E C500-LK203 3G2A6-LK201-E 4-5 The connector has been changed from a 25-pin to a 9-pin connector. The CS1-series products do not support the ST1, ST2, and RT signals and wiring them is not required. Other The following changes are necessary for systems that sync with ST1, ST2, and RT. Synchronized transfers will no longer be possible. Full-duplex transmissions will be possible with the CS1-series product, but the host computer’s communications program, hardware, or both will need to be altered. The following changes are necessary for systems that did not sync with ST1, ST2, and RT. C-series CPU Units It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS1 command specifications. (See note.) It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS1 command specifications. (See note.) C200H-LK201 The connector has been changed from a 25-pin to a 9-pin connector. SRM1 No changes have been made in wiring. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS1 command specifications. CPM1 CPM1A CQM1-CPUjj-E C200HS-CPUjj-E C200HX/HG/HECPUjj-E C200HW-COMjj-E CVM1 or CV-series CPU Units CVM1/CV-CPUjj No changes have been made in wiring. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS1 command specifications. CVM1 or CV-series Host Link Unit CV500-LK201 Port 1: The connector has been changed from a 25-pin to a 9-pin connector. The following changes are necessary for half-duplex transmissions that use CD. Port 2 set for RS-232C: The SG signal has been changed from pin 7 to pin 9. Check the system for timing problems when using SEND, RECV, or CMND to initiate communications from the PC or timing problems in sending commands from the host computer. If necessary, switch to full-duplex transmissions. The following changes are necessary for full-duplex transmissions that do not use CD. Half-duplex It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS1 command specifications. 104 Section Changes from Previous Products 4-5 Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Host Link Units and CS1-series Serial Communications Boards/Units. A host computer program previously used for C-series Host Link Units may not function correctly if used for CS1-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS1-series Communications Commands Reference Manual (W342) for details. 4-5-2 RS-422A/485 Ports Take the following differences into consideration when changing from an existing Host Link System to one using an RS-422A/485 port on a CS1-series Serial Communications Board (CS1W-SCB41 port 2). Previous products C-series Host Link Units Changes required for CS1-series product Model number 3G2A5-LK201-E C200H-LK202 3G2A6-LK202-E C200HX/HG/HE Communications Board C200HW-COMjj-E CVM1 or CV-series CPU Units CVM1/CV-CPUjj CVM1 or CV-series Host Link Unit CV500-LK201 Wiring Wiring pins have been changed as shown below. SDA: SDB: RDA: RDB: SG: Pin 9 to pin 1 Pin 5 to pin 2 Pin 6 to pin 6 Pin 1 to pin 8 Pin 3 to Not connected FG: Pin 7 to pin Connector hood No changes have been made in wiring. No changes have been made in wiring. Other It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS1 command specifications. (See note.) It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS1 command specifications. It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS1 command specifications. Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Host Link Units and CS1-series Serial Communications Boards/Units. A host computer program previously used for C-series Host Link Units may not function correctly if used for CS1-series PCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS1-series Communications Commands Reference Manual (W342) for details. 105 SECTION 5 Using Protocol Macros This section describes the procedure and other information required to use protocol macros. 5-1 5-2 5-3 5-4 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1 Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-2 Using the Protocol Macro Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-3 Protocol Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3-1 Auxiliary Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3-3 Software Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3-4 Status Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4-1 Executing Send/Receive Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4-2 Ladder Program Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4-3 Ladder Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108 108 108 110 115 115 116 120 120 122 124 126 136 136 140 141 107 Section Overview of the Protocol Macro Functions 5-1 5-1 Overview of the Protocol Macro Functions 5-1-1 Protocol Macro Functions The protocol macro function is used to control devices by using the PMCR(260) instruction in the ladder program to execute the data send/receive sequences (protocols) with the various communications devices, such as general-purpose devices, connected to the RS-232C or RS-422A/485 port. Standard system protocols are provided in the Serial Communications Board or Unit for controlling OMRON devices (such as Digital Controllers and Temperature Controllers). Using the Protocol Support Tool called the CX-Protocol, the protocol macro function can be used to create new protocols for commercially available measuring instruments and devices, and to create protocols by modifying one of the standard system protocols. The standard system protocols are also provided with the CX-Protocol. For details on the use of the CX-Protocol and the protocol macro function, refer to the CX-Protocol Operation Manual (W344). 5-1-2 Using the Protocol Macro Function The following three methods are available for using the protocol macro function. Using the Standard System Protocols CPU Unit When connecting OMRON devices, data is sent and received between the CS1-series CPU Unit and these devices by specifying the sequence number of the standard system protocol provided in the Serial Communications Board, Serial Communications Unit, and CX-Protocol, and executing the sequence using the PROTOCOL MACRO instruction (PMCR(260)). Serial Communications Board or Unit Standard system protocol Sequence No. 001 Sequence number Messages Sequence No. specification Step 0 *Send/receive messages are stored in the area one or more words after the send data address or the receive data address specified in the PMCR(260) instruction. Step 1 OMRON devices I/O memory Shared memory I/O refreshing Note The devices for which standard system protocols are provided are listed below. For details, refer to 5-4 Using Protocol Macros. Digital Controllers (E5jK, ES100j), Temperature Controllers (E5ZE, E5jJ), Intelligent Signal Processors (K3Tj), Bar Code Readers (V500/V520), Laser Micrometers (3Z4L), Visual Inspection Units (F200/F300/F350), ID Controllers (V600/V620), Hayes Modem AT Command, and devices supporting the CompoWay/F protocol. 108 Section Overview of the Protocol Macro Functions Modifying Standard System Protocols 5-1 When connecting OMRON devices, if there is no standard system protocol or you wish to modify part of the protocol, use the CX-Protocol to modify the standard system protocol, transfer this as a separate send/receive sequence to the Serial Communications Board or Unit, and execute the PMCR(260) instruction. Modifying and transferring standard system protocols Serial Communications Board or Unit CPU Unit Sequence No. specification Modified standard system protocol Command execution (SEND, RECV, SEND&RECV) Messages Step 0 Sequence number Step 1 Step 2 RS-232C or RS-422A/485 General-purpose external device I/O memory Shared memory I/O refreshing Creating a New Protocol When connecting a general-purpose external device that has an RS-232C or RS-422A/485 port, use the CX-Protocol to create a new protocol containing the communications specifications for the general-purpose external device, transfer these specifications to the Serial Communications Board or Unit, and execute the PMCR(260) instruction. Creating and transferring a new protocol Serial Communications Board or Unit CPU Unit Newly created protocol Sequence number Step 0 Sequence No. specification Command execution (SEND, RECV, SEND&RECV) Messages Step 1 RS232C or RS-422A/485 Step 2 General-purpose external device I/O memory Shared memory I/O refreshing 109 Section Overview of the Protocol Macro Functions 5-1 In this manual, the protocol structure is explained in simple terms, and examples are given of the use of the PMCR(260) instruction when controlling OMRON devices using standard system protocols. For details on the protocols, the method of modifying the standard system protocols, and the method of creating new sequences, refer to the CX-Protocol Operation Manual (W344). 5-1-3 Protocol Structure Protocols consist of send/receive sequences. A sequence consists of steps. These steps can be repeated, or they can be branched or ended depending on the responses received. A step consists of a command, send/receive messages, processing results, and the next process (which depends on the processing results). Example: Reading the process values for a Temperature Controller Protocol Send/receive sequence Step 0 Step 1 Transmission of process value reading message and reception of response message Messages A protocol consists of processing sequences (such as reading the process value for a Temperature Controller) for a general-purpose external device. A sequence consists of a group of steps, each of which consists of a send/receive/ control command, send/receive message, processing result, and a next step that depends on the processing results. For example, with a sequence that reads the process value for a Temperature Controller, the sequence sends the send message for the connected Temperature Controller (a character string in which the Process Value Read command is inserted between the header + address and the check code + terminator) and receives the receive message (a character string in which the Process Value Read command response is inserted between the header + address and the check code + terminator). Serial Communications Unit CPU Unit Command Send message (Example: PROCESS VALUE READ command) SEND (send) RX00⋅⋅⋅ Header Address Send data Check code Terminator Receive message (Example: Response) RECV (receive) Serial Communications Board RS-232C or RS-422A/485 RX01⋅⋅⋅ Header Address Send data Check code Terminator General-purpose external device 110 Section Overview of the Protocol Macro Functions 5-1 Depending on the response received, the user can either choose to resend the same send message (retry processing), or to perform the next process (for example, read the process value for a Temperature Controller with a different address). One protocol One-step structure With the SEND, RECV, or SEND&RECV command Sequence No. 000 to 999 (60 sequences max./protocol) Step 0 Step 1 Transmission control parameter Link word setting Step 0 Step 1 Command (see note 1) Command (see Note 1) Messages (see note 2) Send/receive processing monitoring time Response notification method With the WAIT, FLUSH, OPEN, or CLOSE command 15 steps max. Repeated 15 steps max. Next process Y N (no) Message list (see note 2) Send message list Normal end N (error) Next process Error processing S Next step Header Address Data Check Terminator S To specified step Receive message list S Sequence end S Sequence interrupt Header Address Data Check Terminator Reception matrix list (see note 2) Reception matrix Case No. 15 Case No. 00 Receive message Next process Note 1. The SEND, RECV, SEND&RECV, WAIT, FLUSH (reception buffer clear), OPEN (ER-ON), or CLOSE (ER-OFF) commands can be used. 2. Three types of reception matrix are available for switching the processing, depending on whether the messages are send messages, receive (wait) messages, or multiple receive (wait) messages. Unlike sequences, these matrixes are managed as lists. Sequence Parameters Parameter Transmission control parameters Link words Monitoring time Response notification method Meaning Control methods, such as flow control Settings for shared words between the PC and the Serial Communications Board. Monitoring time for send/receive processing Timing for writing received data to I/O memory in the PC 111 Section Overview of the Protocol Macro Functions Step Parameters Parameter Command Messages 5-1 Meaning One of the following: SEND, RECV, SEND&RECV, WAIT, FLUSH, OPEN, or CLOSE Send message Receive message Send message and receive message The message sent for SEND. The expected message for RECV. The message sent and the expected message for SEND&RECV. Reception matrix Repeat counter Retry count Send wait time Response write enable (for operand specification) Next process Error processing 112 A group of expected messages that can be used to switch to different next processes when RECV or SEND&RECV is used. The number of times to repeat the step (0 to 255). The repeat counter can be used to change send/receive messages. Used for SEND&RECV to retry the command for errors (0 to 9). Used for SEND or SEND&RECV to create a wait time before sending data. Specification of whether or not to write the received data to memory. Specifies the next step or to end the sequence when the current step is completed normally. Specifies the next step or to end the sequence when the current step ends in an error. Section Overview of the Protocol Macro Functions 5-1 Standard System Protocol Example Process Value Read Sequence for E5jK Controller Read Protocol Level Sequence Item Setting Link words Transmission control parameters Response notification method Reception wait time Tr Reception finished wait time Tfr Send finished wait time Tfs Step number Repeat counter Command Retry count Send wait time Send message Receive message Response write enable Next process Error process Header <h> Terminator <t> Error check code <c> Length <l> Address <a> Message edited Steps Send message SD (00) _1 Receive message Header <h> Terminator <t> Error check code <c> Length <l> Address <a> Message edited RV (00) _1 --Modem control Scan 3s 3s 3s 00 Reset/001 SEND&RECV 3 --SD (00) _1 RV (00) _1 Write End Abort “@” [2A0D] LRC (horizontal parity) (0) (2 bytes of ASCII) --$ (R (1) ) ,2) <h> + <a> + “1” + “00” + “0000” + <c> + <t> Data “@” [2A0D] LRC (horizontal parity) (0) (2 bytes of ASCII) --& (R (1) ) ,2) <h> + <a> + “00” + “00” + & (W (1) ,4) + <c> + <t> Data DM Area Settings for Standard System Protocol Board The following data is set in the Setup Area in the DM Area for a standard system protocol. m = D30000 + 100 Unit unit number Contents Setting for a standard system protocol Set to match the parameters of the external device. Set to 6 Hex to specify Protocol Macro Mode. Set to match the baud rate of the external device. Set to 0 Hex to specify half-duplex. Port 1 D32000 Port 2 D32010 Port 1 m Port 2 m + 10 D32001 D32011 m+1 m + 11 Bits 00 to 04: Communications parameters Bits 08 to 11: Serial communications mode Bits 00 to 03: Baud rate D32008 D32018 m+8 m + 18 Bit 15: Transmission method D32009 D32019 m+9 m + 19 Bits 00 to 15: Max. No. of send/receive bytes Set to 03E8 Hex to specify 1,000 bytes. 113 Section Overview of the Protocol Macro Functions Handling Communications Problems for Standard System Protocols The CS1-series PCs provide standard system protocols to enable communications with OMRON components without having to create send/receive sequences. The sequences in the standard system protocols can be executed merely by setting operands for the PMCR(260) instruction. Processing for communications line problems during communications for the standard system protocols are set to normal settings, as shown in the following table. If these settings are not suitable to the application or if improvements are desired, use the CX-Protocol to modify the following settings in the required sequences. For details on the use of the CX-Protocol, refer to the CX-Protocol Operation Manual (W344). Refer to the appendices for the settings in the standard system protocols. Level Sequence parameters Step parameters Item Link words Transmission control parameters Response notification method Reception wait time Tr Reception finished wait time Tfr Send finished wait time Tfs Repeat counter Command Retry count Send wait time Send message Receive message Response write enable Next process Error process 114 5-1 Possible changes in settings No reason to change. The monitoring times are set to 3 seconds for most sequences. The settings are different for send-only and receive-only sequences, as well as for sequences that require time for responses. No reason to change. The retry count is general set to 3 retries (4 tries total) for sequences that use the SEND&RECV command. Different settings are used for sequences that have other commands. No reason to change. Section Setup Area Allocations 5-2 5-2 Setup Area Allocations This section explains the Setup Area allocated in the DM Area when a Serial Communications Board or a Serial Communications Unit is used in protocol macro mode. 5-2-1 Setup Area Words The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when Protocol Macros are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to unit numbers). Serial Communications Board Setup Area Allocated in the DM Area: D32000 to D32099 Words Serial Communications Units Unit No. Usage D32000 to D32001 D32008 to D32009 Port 1 Settings D32010 to D32011 D32018 to D32019 Port 2 Settings D32002 to D32007 D32012 to D32017 Not used with the protocol macro mode D32020 to D32767 Reserved for the system Setup Area Allocated in the DM Area: D30000 to D31599 First Word in Setup Area Allocated in the DM Area: m = D30000 + 100 unit number DM Area Unit No. 0 D30000 to D30099 m to m + 1, m + 8 to m + 9: Port 1 Settings Unit No. 1 D30100 to D30199 m + 10 to m + 11, m + 18 to m + 19: Port 2 Settings Unit No. 2 D30200 to D30299 m + 2 to m + 7, m + 12 to m + 17: Not used Unit No. 3 D30300 to D30399 m + 20 to m + 99: Not used Unit No. 4 D30400 to D30499 Unit No. 5 D30500 to D30599 Unit No. 6 D30600 to D30699 Unit No. 7 D30700 to D30799 Unit No. 8 D30800 to D30899 Unit No. 9 D30900 to D30999 Unit No. A D31000 to D31099 Unit No. B D31100 to D31199 Unit No. C D31200 to D31299 Unit No. D D31300 to D31399 Unit No. E D31400 to D31499 Unit No. F D31500 to D31599 115 Section Setup Area Allocations 5-2 5-2-2 Setup Area Allocations Board Port 1 Port 2 D32000 D32010 Unit Port 1 Port 2 m m + 10 15 12 to 14 08 to 11 05 to 07 04 m+1 D32001 D32011 D32002 to D32007 D32012 to D32017 D32008 D32018 m+8 m + 18 D32009 D32019 m+9 m + 19 m+2 to m+7 Port Settings m = D30000 + 100 × unit number Setting contents Bit DM Area 03 02 01 00 04 to 15 00 to 03 m + 11 m + 12 to m+17 Port settings 0: Defaults, 1: User settings Reserved Serial communications mode 6: Protocol macro Reserved Start bits 0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting) Data length 0: 7 bits; 1: 8 bits Stop bits 0: 2 bits; 1: 1 bit Parity 0: Yes; 1: No Parity 0: Even; 1: Odd Reserved Baud rate (Unit: bps) 0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6:9,600; 7: 19,200; 8: 38,400 00 to 15 Not used. 15 00 to 14 00 to 15 Transmission method 0: Half-duplex; 1: Full-duplex Reserved Maximum number of bytes in send/receive data: 00C8 to 03E8 Hex The setting for the port settings determines if the default settings or user settings will be used for port 1 and port 2. Be sure to use the same settings as the RS-232C port on the host computer connected via the Host Link System. If the default port settings are specified, then the settings of bits 00 to 04 and the baud rate in D32001 will be ignored. The default settings used are as follows: Baud rate: 9,600 bps, start bits: 1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits. If user port settings are specified, set bits 00 to 04 and set the baud rate in D32001. Setting Example: 0600 Hex = Protocol macro mode with default port settings and baud rate. Serial Communications Mode Set the serial communications mode to 6 Hex to use protocol macros. Start Bits, Data Length, Stop Bits, Parity, and Baud Rate If user settings are specified for the port settings, the number of start bits, data length, number of stop bits, parity, and baud rate must be set. The start bits setting, however, will be ignored and 1 start bit will always be used. Do not set the baud rate setting to between 9 and F. A setup error will occur if these settings are used, and the default setting of 9,600 bps will be used. Do not use settings 1 and 2, which are reserved for the system. Transmission Method 116 Set half-duplex (0) or full-duplex (1) as the transmission mode for the external device. Section Setup Area Allocations 5-2 Note Half-duplex: Allows data to be sent between two Units in one direction only at any one time. A B or A B Full-duplex: Allows data to be exchanged both ways between two Units at the same time. A B With half-duplex transmissions, the reception buffer is cleared immediately before the sequence is executed and immediately following SEND completion (SEND or SEND&RECV command). Therefore, the data received before and during SEND execution cannot be accessed as receive data by the next RECV command. Note When using SEND with half-duplex transmission, there is a time lag, t1, between data send processing completion and SEND completion. Therefore, if there is a rapid response from the remote device and a response is returned for SEND after data is sent (communications or other command) and before SEND is completed, the response during that time cannot be received using half-duplex transmissions. If this problem occurs, use the full-duplex transmissions. Also, if the external device is connected using 2-wire connections from an RS-422A/485 port, send and receive data cannot both be on the same transmission line at the same time. This will create an additional lag time, t2, or 150 µs. If responses are being received quickly from the external device, i.e., faster than t1 +t2, create a send delay at the external device or take other measures to allow for the lag times. SEND operation Data send processing t1 t2 = 150 µs Rapid response Time lags (see following table) Data cannot be received during this time. Data reception Reception buffer cleared Time Lag t1 Baud rate (bps) Time lag (µs) 1,200 1,116 2,400 578 4,800 288 9,600 144 19,200 73 38,400 36 117 Section Setup Area Allocations 5-2 With full-duplex mode, the reception buffer is cleared immediately before the sequence is executed. While both the SEND&RECV commands are being executed, data is input into the reception buffer and is used as the macro data. Transmission mode Half-duplex Full-duplex (See note 1) Time reception buffer cleared Immediately before send/receive sequence execution and immediately following SEND completion by the SEND or SEND&RECV command Immediately before send/receive sequence execution (See note 2) Data reception From SEND completion to RECV completion, or following SEND completion to immediately before SEND execution All during send/receive sequence execution Character trace All during trace execution Timing chart (example) Send/receive sequence Reception buffer cleared RECV SEND RECV Data reception (See note 3.) Character trace All during trace execution Send/receive sequence Reception buffer cleared RECV SEND RECV Data reception Character trace Note Maximum Number of Send/Receive Data Bytes 1. With full-duplex, RS-232C or RS-422A/485 (1:1 and 4-wire connections) can be used. RS-422A/485 1:N or 2-wire transmissions cannot be used. 2. The FLUSH command is used to clear the reception buffer, and can be used at any time. 3. Although the received data is discarded until completion of SEND execution, it is reflected in the character trace. From 200 bytes up to a maximum of 1,000 bytes can be set in hexadecimal, i.e., between 00C8 Hex and 03E8 Hex. Any setting below 00C8 Hex, will be treated as 00C8 Hex; any setting above 03E8 Hex, will be treated as 03E8 Hex. Note Flow Control and Maximum Number of Send/Receive Data Bytes There is a 2.5-Kbyte reception buffer for each serial port in a Serial Communications Board or Unit. When using flow control, initiate flow control after receiving about 2 Kbytes, and then release control after processing all but 0.5 Kbytes of receive data. Up to 1,000 bytes (500 words) of data can be stored for each RECV command if 2 Kbytes of receive data is first stored in the buffer and 1,000 bytes (03E8 Hex) is set as the maximum number of send/receive data bytes. 118 Section Setup Area Allocations 5-2 RS/CS Flow Control Half-duplex Communications With CS1-series half-duplex protocol macro communications (see note), or with C200HX/HG/HE protocol macro communications, flow control can be released by turning ON the RS signal (CS signal at the communications partner) while the RECV command is being executed. The timing of this operation is shown below. (Signal names used below are those at the Serial Communications Board.) PMCR(260) instruction PMCR(260) instruction Command SD signal RS turned OFF after 0.1 to 4 ms RD signal RS signal RS signal ON while RECV command is executed. 1, 2, 3... Data received before SEND is completed is discarded. Data received while the PMCR(260) instruction is not being executed is discarded (controlled by turning OFF the RS signal). The OFF status of the RS signal is maintained after execution of the PMCR(260) instruction. 1. With protocol communications in half-duplex mode, the RS signal is ON only while the RECV command is being executed. 2. The receive data (RD signal) from the communications partner is initially stored in the reception buffer. 3. The data in the reception buffer is analyzed, and a search is performed for data matching an expected message registered with the RECV command. 4. When matching data is found, the RS signal is turned OFF. The search starts after the final data has been received. It takes between 100 µs and 4 ms from starting the search until the RS signal turns OFF. 5. While the SEND command is being executed, and while the PMCR instruction is not being executed, the RS signal stays OFF and receive data is discarded. Note RS/CS flow control in half-duplex mode is supported only by CS1-series Serial Communications Boards/Units manufactured on or after December 20th, 1999. With earlier models, half-duplex mode will operate in the same way as full-duplex mode. Lot No: 20Z9 Manufactured on December 20th, 1999 The year is indicated with the last digit. In this case, “9” indicates “1999.” Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is “December.” Day of manufacture. In this example, the day is “20.” 119 Section Auxiliary Area and CIO Area Allocations Full-duplex Mode 5-3 There is a 2.5-Kbyte reception buffer for each serial port in a CS1-series Serial Communications Board or Unit. When using flow control, initiate flow control after receiving about 2 Kbytes, and then release control after processing all but 0.5 Kbytes of receive data. Up to 1,000 bytes (500 words) of data can be stored for each RECV command if 2 Kbytes of receive data is first stored in the buffer and 1,000 bytes (03E8 Hex) is set as the maximum number of send/receive data bytes. The timing of this operation is shown below. (Signal names used below are those at the Serial Communications Board.) PMCR(260) instruction Command Receive Send PMCR(260) instruction Receive Send Receive SD signal RS turned ON when only 0.5 Kbytes in buffer. RD signal RS signal RS signal turned OFF when 2 Kbytes of data accumulates in reception buffer. 1, 2, 3... Data received from the end of the last RECV command until the next PMCR(260) execution is discarded. The RS signal does not operate. 1. With full-duplex protocol communications, the RS signal is turned OFF when 2 Kbytes of data has been stored in the reception buffer (i.e., with 0.5 Kbytes remaining). 2. The receive data (RD signal) from the communications partner is initially stored in the reception buffer. 3. The data in the reception buffer is analyzed, and a search is performed for data matching an expected message registered with the RECV command. 4. When matching data is found, all the previous data is deleted from the reception buffer. 5. If this results in the amount of data stored in the reception buffer dropping to less than 0.5 Kbytes (i.e., more than 2 Kbytes remaining), the RS signal is turned ON. 6. Data that is received while the PMCR(260) instruction is not being executed is discarded. 7. In full-duplex mode, the data left over after the analysis performed with the last RECV command and any subsequent data received before the next PMCR(260) execution is discarded. During this interval, RS flow control cannot be used. Note Full-duplex mode is supported only by the CS1 Series. 5-3 Auxiliary Area and CIO Area Allocations This section describes the bits and words used by the Serial Communications Board and Serial Communications Units in the Auxiliary Area and the Software Switches and Status Area allocated in the CIO Area. 5-3-1 Auxiliary Area Allocations Port 1 and Port 2 Port Settings Change Bits 120 These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. Section Auxiliary Area and CIO Area Allocations 5-3 Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used. Serial Communications Board Word A636 Bit 03 to 15 02 01 00 Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved Serial Communications Units n = A620 + unit number Words n Inner Board Error Information (Serial Communications Board Only) Bit 03 to 15 02 01 00 Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved A424 contains error information for the Serial Communications Board. Word A424 Bit 12 to 15 11 10 Contents Non-fatal errors (Note 1) Reserved 1 Error log EEPROM error; 0: Normal 1: Protocol macro execution error; 0: Normal This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area, 09 08 07 06 05 04 03 02 01 00 Note Fatal errors (Note 2) 1: Protocol data error (SUM error); 0: Normal 1: Setup error; 0: Normal 1: Routing table error; 0: Normal Reserved 1: Cyclic monitoring error; 0: Normal Reserved Reserved Reserved 1: Inner Bus error; 0: Normal 1: Inner Board watchdog timer error; 0: Normal 1. When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag) (nonfatal error) will be ON. 2. When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON. For details on errors, refer to Section 8 Troubleshooting and Maintenance. 121 Section Auxiliary Area and CIO Area Allocations 5-3 Auxiliary Area Bit Descriptions Name Address Timing Meaning Initialize ON OFF Board/Unit Watchdog Timer Error Flags Board: A42400 The corresponding flag will turn ON Startup when the Board or Unit is faulty. If the (See note.) problem persists even when the Board or Unit is remounted or used with (Unit numbers 0 another CPU Unit, replace the Board or to F correspond Unit. to bits 00 to 15 of A417.) At error Startup Inner Bus Error Flag Board: A42401 Protocol Macro Execution Error Flag Board: A42410 Port 1/2 Port Settings Change Bits Board: A63601 and A63602 Units: A40207 and A417 (No flags are provided for Units.) (No flags are provided for Units.) Units: A620 + unit number, bits 01 and 02 The flag will turn ON when an error occurs in the Inner bus. If the problem persists even when the Board is remounted or used with another CPU Unit, replace the Board. Startup At error Startup The flag will turn ON when and attempt was made to read or write data at an illegal address (error code 3) or a protocol macro syntax error occurred (error code 4). Startup At error Start of Sequence The communications port setting can be changed and the port restarted by turning on the corresponding bit. Startup STUP(237) execution or user manipulation After port settings have been changed and the port has been restarted. Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming Console or other Programming Device. 5-3-2 CIO Area Allocations The following areas are allocated as the status area and the software switch area, which show the status of the Serial Communications Board and Serial Communications Unit or the error information. Serial Communications Board Words CIO 1900 to CIO 1999 in the Inner Board Area are used for Software Switches and Status Area. Only the words shown in the following table are used for Protocol Macros. Inner Board CIO Area CIO 1900 to CIO 1999 Words 122 Usage CIO 1900 Software switches CIO 1901 to CIO 1904 Board status CIO 1905 to CIO 1914 Port 1 status CIO 1915 to CIO 1924 Port 2 status CIO 1925 to CIO 1999 Reserved for the system Section Auxiliary Area and CIO Area Allocations Serial Communications Unit 5-3 Words CIO 1500 to CIO 1899 of the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each unit number is allocated 25 words. With the protocol macro mode, the words shown in the following table are used for the Software Switches and Status Area. CPU Bus Unit Area CIO 1500 to CIO 1899 n = CIO 1500 + 25 unit number Unit No. Words Unit No. 0 CIO 1500 to CIO 1524 n: Software switches (port 1/Port 2) Unit No. 1 CIO 1525 to CIO 1549 n + 1 to n + 4: Unit status Unit No. 2 CIO 1550 to CIO 1574 n + 5 to n + 14: Port 1 status Unit No. 3 CIO 1575 to CIO 1599 n + 15 to n + 24: Port 2 status Unit No. 4 CIO 1600 to CIO 1624 Unit No. 5 CIO 1625 to CIO 1649 Unit No. 6 CIO 1650 to CIO 1674 Unit No. 7 CIO 1675 to CIO 1694 Unit No. 8 CIO 1700 to CIO 1724 Unit No. 9 CIO 1725 to CIO 1749 Unit No. A CIO 1750 to CIO 1774 Unit No. B CIO 1775 to CIO 1799 Unit No. C CIO 1800 to CIO 1824 Unit No. D CIO 1825 to CIO 1849 Unit No. E CIO 1850 to CIO 1874 Unit No. F CIO 1875 to CIO 1899 123 Section Auxiliary Area and CIO Area Allocations 5-3 5-3-3 Software Switches The Software Switches are used from the CPU Unit to control the Serial Communications Board and Serial Communications Unit. Software Switches are used to output control signals from the CPU Unit to the Serial Communications Board or Unit. n = CIO 1500 + 25 × unit number Bit Words Board CIO 1900 Contents Unit n 15 14 12, 13 11 10 09 08 07 06 04, 05 03 02 01 00 Port 2 Port 1 Reserved Used for loopback tests Reserved Abort Switch One-shot Trace Switch Continuous Trace Switch Wait Release Switch Reserved Used for loopback tests Reserved Abort Switch One-shot Trace Switch Continuous Trace Switch Wait Release Switch Software Switches Bit CIO 1900 CIO n 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 0 0 0 0 0 0 Port 1 Wait Release Switch Port 1 Continuous Trace Switch Port 1 One-shot Trace Switch Port 1 Abort Switch Port 1 Loopback Test Switch Port 2 Wait Release Switch Port 2 Continuous Trace Switch Port 2 One-shot Trace Switch Port 2 Abort Switch Port 2 Loopback Test Switch 124 Section Auxiliary Area and CIO Area Allocations Software Switch Descriptions Name 5-3 The Software Switches function as described in the following table. Bits in CIO 1900 or CIO n Abort Switch Bits 03 and 11 One-shot Trace Switch (Note 2) Bits 02 and 10 Timing Meaning Protocol processing will be aborted when the switch is turned ON. (Processing may be completed if the switch is turned ON too late.) The CX-Protocol will start a one-shot trace when the Switch turns ON. The trace is ended when the Switch is turned OFF. Initialize Startup (Note 1) ON Manipulated by user. OFF Manipulated by system. Manipulated by CX-Protocol. At end of one-shot trace Manipulated by CX-Protocol. Manipulated by CX-Protocol. Manipulated by user. At end of WAIT command The Board or Unit will be cleared when the trace buffer becomes full. Continuous Trace Switch (Note 2) Bits 01 and 09 Wait Release Switch Bits 00 and 08 (Not supported by C200HX/HG/HE) Note The CPU Unit will manipulate the One-shot Trace Switch and Continuous Trace Switch when trace operations are performed from the CX-Protocol. Do not manipulate these switches directly from a ladder diagram. The CX-Protocol will start a continuous trace when the Switch turns ON. The trace is ended when the Switch is turned OFF. Standby status for the WAIT command will be released when the switch is turned ON. 1. The Software Switches will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes, when STUP(237) is executed, when the Board or Unit is restarted, or when the communications port is reset. 2. The first switch of the One-shot Trace Switch and Continuous Trace Switch to turn ON will determine the trace operation. If a Trace Switch turns ON when a trace operation is already in progress, the switch will not be effective even when the current trace operation is completed unless the switch is first turned OFF. If the One-shot Trace Switch and Continuous Trace Switch turn ON simultaneously, the Continuous Trace Switch will take priority. 125 Section Auxiliary Area and CIO Area Allocations 5-3 5-3-4 Status Area The Status Area is used to input status information from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status. Words Board Units Port 1 Port 2 Port 1 Port 2 CIO 1901 n+1 n = CIO 1500 + 25 × unit number Contents Bit CIO 1902 n+2 02 to 15 01 00 00 to 15 CIO 1903 n+3 00 to 15 Reserved CIO 1904 CIO CIO 1905 1915 n+4 n+5 00 to 15 Reserved Port Setup setting settings status CIO 1906 CIO 1916 n+6 n + 15 12 to 15 n + 16 08 to 11 05 to 07 04 03 02 01 00 15 14 13 CIO 1907 CIO 1917 n+7 n + 17 12 to 02 01 00 15 to 11 10 09 08 07 06 05 04 03 126 Reserved 1: Error log EEPROM error 1: Protocol data error Reserved Port setting status Hardware settings (See note 2) 0: Error log EEPROM normal 0: Protocol data normal Serial communications mode: Always 6 Hex (see note) Baud rate (Note 1) Reserved: Always 0 Start bits: Always 1 Data length: 7 or 8 bits (Note 1) Stop bits: 1 or 2 bits (Note 1) Parity: Yes/No (Note 1) Parity: Even/Odd (Note 1) 0 No 0 RS-232C 1 RS-422A/485 1 Reserved 0 1 0 0: Terminating resistance OFF 1: Terminating resistance ON Reserved 1: System Setup error; 0: System Setup normal 1: Port operating; 0: Port stopped Commu- Reserved nications 1: Remote Unit busy receiving (Flow control) status 0: Remote Unit ready to receive Reserved 1: Local Unit busy receiving (Flow control) 0: Local Unit ready to receive TransDTR (ER) signal 1: High, 0: Low mission DSR (DR) signal 1: High, 0: Low control Reserved signal status CTS (CS) signal 1: High, 0: Low RTS (RS) signal 1: High, 0: Low 1 Section Auxiliary Area and CIO Area Allocations Bit Words Board Units Port 1 Port 2 Port 1 Port 2 CIO CIO n+8 n + 18 15 1908 1918 14 13 12 CIO 1909 to CIO 1914 CIO 1919 to CIO 1924 n+9 to n + 14 n + 19 to n + 24 Note 08 to 11 07 06 05 04 03 02 00, 01 00 to 15 5-3 Contents Transmission error status 1: Transmission error 0: No transmission error 1: Tfs (send finished monitoring time) exceeded 0: Normal 1: Tfr (receive finished monitoring time) exceeded 0: Normal 1: Tr (receive wait monitoring time) exceeded 0: Normal Number of retries: 0 to 9: 0 to 9 hex 1: FCS check error; 0: FCS check normal 1: Command error; 0: No command error 1: Timeout (Tfs, Tfr, or Tr) error; 0: Normal 1: Overrun error; 0: Normal 1: Framing error; 0: Normal 1: Parity error; 0: Normal Reserved Protocol status (See Protocol Status on page 54.) 1. The settings in the Setup Area are reflected here. The default settings will be used and will be stored here if a setup error occurs. 2. With a Board, the same bit is used as for A42409 (protocol data error) of the Auxiliary Area. Status Area Descriptions Name Error log data error Address Board: CIO 190101 Unit: n + 1 bit 01 Protocol data error Board: CIO 190100 Unit: n + 1 bit 00 Board only: A42409 Meaning Timing Initialize If a write to EEPROM fails for the error log, Startup it is assumed the EEPROM is beyond its (See useful life and this flag is turned ON. With a note.) Serial Communications Unit, the ERC indicator will also light. Although this has no effect on communications and other functions, replace the Board or Unit promptly for ease of maintenance. ON At error OFF Startup This flag is turned ON if an error is detected Startup in the protocol data SUM check when the (See power is turned ON. With a Serial Commu- note.) nications Board, the ERR/ALM indicator on the CPU Unit will also flash and the RDY indicator will flash at 1-second intervals. A42409 (Board only) of the Auxiliary Area will also turn ON. At error When protocol data has been successfully transferred. With a Serial Communications Unit, the RDY and ERC indicator will flash. This error may occur if the communications connector becomes disconnected or the PC power is turned OFF during protocol data transfer. Use the CX-Protocol to transfer of the protocol data again. 127 Section Auxiliary Area and CIO Area Allocations Name Address Meaning Initialize Setup error Board: CIO 190601 (port 1) CIO 191601 (port 2) Unit: n + 6 bit 01 (port 1) n + 16 bit 01 (port 2) Timing ON 5-3 OFF This flag is turned ON if a Setup error ocStartup curs in the allocated DM Area, After chang- (See ing the Setup, turn ON the power again, re- note.) start the Board/Unit, restart the port, or execute the STUP(237) instruction. At error Startup (See note.) Serial port communications are in progress. Startup (See note.) At error After protocol data has been transferred. This flag indicates the receive status of a remote Unit during SEND when Xon/Xoff flow control or RS/CS flow control is set in the transmission control parameters. When Xon/Xoff flow control is set, the reception buffer is cleared when the sequence starts, so the status area is set to remote Unit receive wait (0). Startup (See note.) When status is read. After busy status has been released. Startup When status is read. After busy status has been released. The status of each transmission control sig- Startup nal (ER, DTR, CTS, and RTS) for each port is always read to these flags. When status is read. After busy status has been released. Board only: A42408 (not available for Unit) Port operating Board: CIO 190600 (port 1) CIO 191600 (port 2) Unit: n + 6 bit 00 (port 1) n + 16 bit 00 (port 2) Remote Unit receive busy/receive wait Board: CIO 190710 (port 1) CIO 191710 (port 2) Unit: n + 7 bit 10 (port 1) n + 17 bit 10 (port 2) 1: Remote Unit receive busy (Reception is disabled because the reception buffer is full.) 0: Remote Unit receive wait (Reception is enabled.) Local Unit receive busy/receive wait Board: CIO 190708 (port 1) CIO 191708 (port 2) This flag indicates the receive status of a local Unit (Board or Unit) during RECV when Xon/Xoff flow control is set in the transmission control parameters. Unit: n + 7 bit 08 (port 1) n + 17 bit 08 (port 2) 1: Local Unit receive busy (Reception is disabled because the reception buffer is more than 4/5 (= 2 Kbytes) full.) 0: Local Unit receive wait (Reception is enabled because the reception buffer is less than 1/5 (= 0.5 Kbytes) full.) This bit is cleared when the power is turned ON, at port restart by the STUP(237) instruction or by the Port 1 or Port 2 Port Settings Change Bit (Auxiliary Area), or when the next sequence is started. Transmission control signal status Board: CIO 1907 bits 03, 04, 06, 07 (port 1) CIO 1917 bits 03, 04, 06, 07 (port 2) Unit: n + 7 bits 03, 04, 06, 07 (port 1) n + 17 bits 03, 04, 06, 07 (port 2) 128 1: High, 0: Low Section Auxiliary Area and CIO Area Allocations Name Address Meaning Initialize Transmission error status Port setting status Board: CIO 1908 bits 00 to 15 (port 1) CIO 1918 bits 00 to 15 (port 2) When an error occurs during transmission, Startup the corresponding flag is turned ON. The Transmission Error Flag (bit 15) is turned ON when the protocol macro has moved to error processing due to an error in bits 00 to 14. Unit: n + 8 bits 00 to 15 (port 1) n + 18 bits 00 to 15 (port 2) The cause of the error and of the SEND&RECV retry will be shown in bits 00 to 15. Board: CIO 1906 bits 00 to 15 (port 1) CIO 1916 bits 00 to 15 (port 2) The following are read in port setting status: Startup Unit: n + 6 bits 00 to 15 (port 1) n + 16 bits 00 to 15 (port 2) Timing ON 5-3 OFF At error When sequence begins. When status is read. When protocol data has been successfully transferred. When communications are restored by protocol macro retry processing, the error in bits 00 to 14 is stored. The Transmission Error Flag (bit 15), however, will remain OFF. If another error occurs during retry processing, the status of the bit indicating the cause will be held. The serial communications modes and communications specifications set in the Setup Area (D32000, D32010, m, or m+10). The ports and the terminating resistance hardware settings. Setup errors, and Port Operating/Stopped Flags. In Protocol Macro mode, the port will be stopped if a protocol data error occurs while protocol data is being transferred. If there is no protocol data error after the protocol data has been transferred, the flag will be turned ON. Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming Console or other Programming Device. Protocol Macro Function With the protocol macro function, each port is provided with a reception buffer that will hold 2.5 Kbytes max. The reception buffer can be used to hold a large quantity of data when it is being received at once, or when the send/receive sequence is waiting due to the WAIT command. If the protocol macro function is used and receive operations are performed when the reception buffer is full, the receive data will overwrite the 2.5 Kbytes of previously received data in the buffer. Therefore, always set flow control when performing these operations. Overrun Errors, Framing Errors, Parity Errors and Error Flags If an overrun error, framing error, or parity error is detected when the protocol macro function is being used, the receive data will be stored in the buffer with the error status included. The corresponding error flags will turn ON or OFF according to the following conditions. Error Data In Data Agreeing with Expected Receive Message When RECV is executed, an expected receive message is searched for in the reception buffer. If the data that has been received agrees with an expected receive message, it is processed as receive data. If error details are included in the receive data, the corresponding error flags will turn ON. 129 Section Auxiliary Area and CIO Area Allocations 5-3 The following example shows when 100 bytes of data is received that agrees with an expected receive message. (P) Error Flag ON 100 bytes (P) P: Parity error Data Not Agreeing with Expected Receive Message If error details are included in data that do not agree with an expected receive message, the data will simply be discarded and the error flag status will remain unchanged. For trace information, all error details in the reception buffer will be stored within capacity for the trace data. The following example shows when a parity error occurs for data that does not agree with an expected receive message. (P) Data discarded (P) h t Protocol Status The information shown in the following table is input from the Board or Unit to the Protocol Status Words in the CPU Unit. Board Port 1 Port 2 CIO CIO 1909 1919 Unit Port 1 Port 2 n+9 n + 19 CIO 1910 CIO 1920 n + 10 n + 20 CIO 1911 CIO 1921 n + 11 n + 21 15 14 13 12 11 10 09 08 to 04 03 to 00 15 to 12 11 to 00 15 to 12 11 to 08 07 to 04 03 to 00 130 CIO 1922 CIO 1923 n = CIO 1500 + 25 × unit number Setting contents Bit Words CIO 1912 CIO 1913 Error flags remain unchanged n + 12 n + 22 15 to 00 n + 13 n + 23 15 to 00 Port Operating Status Protocol Macro Executing Flag Step Error Processing Flag Abort Flag Tracing Flag Sequence End Completion Flag Sequence Abort Completion Flag Sequence Wait Flag Reserved Error codes Reserved Send/Receive Sequence No. 000 to 999 (000 to 3E7 hex) Reserved Executed Step No. (code) 0 to 15 (0 to F hex) Reserved Executed Reception Case No. (code) 0 to 15 (0 to F hex) Executed Reception Case No. Flag No. 0 to 15: Correspond to bits 00 to 15 Executed Step No. Flag No. 0 to 15: Correspond to bits 00 to 15 Section Auxiliary Area and CIO Area Allocations Bit Words Board Port 1 Port 2 CIO CIO 1914 1924 Unit Port 1 Port 2 n + 14 n + 24 15 to 08 07 to 00 5-3 Setting contents Repeat Counter Setting Value 1 to 255 (01 to FF hex) (See note.) Repeat Counter Present Value 1 to 255 (01 to FF hex) (See note.) Note When the repeat counter is used to read words and 0 is read, 0 will be stored and the step will be skipped. Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 CIO 1909 (port 1) or 0 0 0 0 0 CIO 1919 (port 2) n + 9 (port 1) or n + 19 (port 2) Error code Sequence Wait Flag 1: Sequence wait status 0: Other than above Sequence Abort Completion Flag 1: Sequence aborted 0: Other than above Sequence End Completion Flag 1: Sequence ended 0: Other than above 1: Trace executing Tracing Flag 0: Other than above 1: Protocol macro processing aborted Abort Flag Step Error Processing Flag 0: Other than above 1: Step processing error 0: Step processing normal Protocol Macro Executing Flag 1: Protocol macro executing 0: Protocol macro executed 131 Section Auxiliary Area and CIO Area Allocations 5-3 Protocol Status Area Timing Name Address Meaning Protocol Macro Executing Flag Board: CIO 190915 (port 1) CIO 191915 (port 2) Initialize This flag is turned ON when a PMCR(260) Startup. instruction (sequence) is executed. The flag (See remains OFF when execution fails. note.) Unit: n + 9 bit 15 (port 1) n + 19 bit 15 (port 2) When the sequence is completed and receive data is written, the flag is turned OFF after all the receive data has been written to I/O memory. ON When command is executed. OFF When command has finished executing. This flag is turned OFF when the sequence is completed (either when it is ended by End, or when it is ended by Abort). When the scan response notification method is set for the sequence, first a check is made to see if the received data has been written to I/O memory before the Protocol Macro Executing Flag is turned OFF. Step Error Processing Flag Abort Flag Board: CIO 190914 (port 1) CIO 191914 (port 2) Unit: n + 9 bit 14 (port 1) n + 19 bit 14 (port 2) Board: CIO 190913 (port 1) CIO 191913 (port 2) Unit: n + 9 bit 13 (port 1) n + 19 bit 13 (port 2) Tracing Flag Board: CIO 190912 (port 1) CIO 191912 (port 2) Sequence End Completion Flag Unit: n + 9 bit 12 (port 1) n + 19 bit 12 (port 2) Board: CIO 190911 (port 1) CIO 191911 (port 2) Unit: n + 9 bit 11 (port 1) n + 19 bit 11 (port 2) This flag is turned ON when a step has ended abnormally. It is turned OFF if the step ends normally as a result of a retry. Startup. (See note.) 1: Step ended abnormally 0: Step ended normally When ver- When seification quence error ocstarts. curs after receiving. This flag is turned ON when processing is Startup. ended using the Abort Switch from the user (See program. When the Abort Switch is turned note.) ON at the end of a sequence, the sequence may end with either End or Abort status. When a forced abort occurs. When sequence starts. Startup. (See note.) When trace begins. When sequence starts. When sequence ends. When sequence starts, and when trace ends. When sequence aborts. When sequence starts. Depending on the instruction from the CXProtocol, this flag is turned ON while timeseries data for send and receive messages is being traced. This flag is turned ON when a sequence is completed for the next process or for an error process with an END command. When a sequence has ended normally, setting END (ABORT when the sequence has ended abnormally) enables this flag to be used to determine whether or not the sequence execution has ended normally. 1: Sequence ended 0: Sequence not ended Sequence Abort Completion Flag Board: CIO 190910 (port 1) CIO 191910 (port 2) 1: Sequence aborted Unit: n + 9 bit 10 (port 1) n + 19 bit 10 (port 2) 132 This flag is turned ON when a sequence is ended for the next process or for an error processing with an ABORT command. 0: Sequence not aborted Startup. (See note.) Section Auxiliary Area and CIO Area Allocations Name Address Meaning Initialize Sequence Wait Flag Board: CIO 190909 (port 1) CIO 191909 (port 2) Unit: n + 9 bit 09 (port 1) n + 19 bit 09 (port 2) Protocol Macro Error Code Board: CIO 1909 bits 00 to 03 (port 1) CIO 1919 bits 00 to 03 (port 2) Unit: n + 9 bits 00 to 03 (port 1) n + 19 bits 00 to 03 (port 2) This flag is turned ON when a sequence is waiting due to the WAIT command. Waiting is released when the Wait Release Switch is turned ON in the ladder program, and the sequence will move to the next step. Startup. (See note.) Timing ON 5-3 OFF When WAIT command is executing. When Wait Release Switch is ON, and when sequence starts. At error When sequence starts. The current send/receive sequence number Startup is set when the sequence execution starts. (See This number does not change when a senote.) quence number error (error code 2) occurs. When sequence starts. None. Step numbers 0 to 15 (0 to F hex) are Startup stored for the steps for which execution has (See been completed. note.) When step is executed. When sequence starts. Make sure to set the Wait Release Switch from the ladder program to turn ON the switch. If the Forced Set Key on Programming Console is used, the Wait Release Switch will remain ON, and may stop the protocol macro function from being able to turn OFF the flag. The list of error codes is provided at the end Startup of this table on page 135. (See note.) If a Serial Communications Board is used and either error code 3 (data read/write area exceeded error) or 4 (protocol data syntax error) is stored, A4241 (protocol macro syntax error) will be turned ON, the ERR/ALM indicator on the CPU Unit will flash, and a non-fatal error will occur. If a Serial Communications Unit is used, the ERC indicator will flash. Only error codes 0, 2, 3, and 4 are used. When an error occurs, the error code is held until the next sequence starts. The error code is cleared when the STUP(237) instruction is executed, when the Unit/Board is restarted, or when the next sequence execution starts. When a Board is used, clear the non-fatal error resulting from error codes 3 and 4 by removing the cause of the error, and then clear the error display by executing the next sequence or the STUP(237) instruction, by restart, or by switching the CPU Unit to PROGRAM mode. Send/Receive Sequence No. Board: CIO 1910 bits 00 to 11 (port 1) CIO 1920 bits 00 to 11 (port 2) Unit: n + 10 bits 00 to 11 (port 1) n + 20 bits 00 to 11 (port 2) Executed Step No. (code) Board: CIO 1911 bits 08 to 11 (port 1) CIO 1921 bits 08 to 11 (port 2) Unit: n + 11 bits 08 to 11 (port 1) n + 21 bits 08 to 11 (port 2) 133 Section Auxiliary Area and CIO Area Allocations Name Address Meaning Initialize Executed Reception Case No. (code) Executed Reception Case No. Flags Board: CIO 1910 bits 00 to 03 (port 1) CIO 1920 bits 00 to 03 (port 2) Reception matrix case numbers 0 to 15 (0 Startup to F hex) are stored for which reception has (See been completed. The number is cleared note.) when the sequence execution starts, when the STUP(237) instruction is executed, and at restarts. Unit: n + 10 bits 00 to 03 (port 1) n + 20 bits 00 to 03 (port 2) The Executed Reception Case No. is stored only when the reception matrix is set using the RECV or SEND&RECV command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed. Board: CIO 1912 bits 00 to 15 (port 1) CIO 1922 bits 00 to 15 (port 2) Reception matrix case numbers 0 to 15 for Startup which reception has been completed corre- (See spond to individual bits (00 to 15), and are note.) turned ON to indicate execution. The numbers are cleared when the sequence execution starts, when the STUP(237) instruction is executed, at restarts, and when the execution of each step starts. Unit: n + 12 bits 00 to 15 (port 1) n + 22 bits 00 to 15 (port 2) Executed Step No. Flags Board: CIO 1913 bits 00 to 15 (port 1) CIO 1923 bits 00 to 15 (port 2) Unit: n + 13 bits 00 to 15 (port 1) n + 23 bits 00 to 15 (port 2) 134 Timing ON 5-3 OFF When ma- When setrix is requence ceived. starts. When ma- When setrix is requence ceived. starts. The reception matrix case number can be checked from the ladder program when the WAIT command is executed or when the sequence is ended after the reception matrix RECV command is executed. The Executed Reception Case No. Flag in the bit corresponding to the stored case number will be turned ON only when the reception matrix is set for the RECV or SEND&RECV command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed. Case numbers 0 to 15 for the steps for Startup. which execution has been completed corre- (See spond to individual bits (00 to 15), and are note.) turned ON in ascending order. Once a bit has been executed, the bit corresponding to the executed step is turned ON in ascending order to hold the bit ON during the sequence (and after completion). When step is executed. When sequence starts. Section Auxiliary Area and CIO Area Allocations Name Address Meaning Initialize Repeat Counter Set Value Board: CIO 1914 bits 08 to 15 (port 1) CIO 1924 bits 08 to 15 (port 2) Timing ON 5-3 OFF The number of times a step is repeated is set in these bits. Startup. (See note.) When step starts. When sequence starts. The repeat counter variable N is set. The value is cleared when the sequence execution starts, when the STUP(237) instruction is executed, and at restarts. Startup. (See note.) When repeat counter is refreshed. When sequence starts. Unit: n + 14 bits 08 to 15 (port 1) n + 24 bits 08 to 15 (port 2) Repeat Counter Present Value Board: CIO 1914 bits 00 to 07 (port 1) CIO 1924 bits 00 to 07 (port 2) The present value N varies according to the method used to initialize the value. For resets, the variable N is set to 0 when the step is started, and the step is executed according to the set number of times. For holds, the variable N for the present value is held when the step is started, and the step is executed according to the set number of times. Unit: n + 14 bits 00 to 07 (port 1) n + 24 bits 00 to 07 (port 2) If the Repeat Counter Setting Value is set to read word R ( ), and 0 is read, then 0 will be stored and this step will be skipped (the next process setting will be ignored), and the sequence will move to the next step (+ 1). For details, refer to the CX-Protocol Operation Manual (W344). Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming Console or other Programming Device. Error Codes The contents of the error codes are shown in the following table. Code Error contents Protocol macro execution 0 No error Executed 2 Sequence No. Error Not executed The sequence number specified by the PMCR(260) instruction does not exist in the Board or Unit. 3 Data Read/Write Area Exceeded Error 4 When data is written or read to the CPU Unit, the specified area range was exceeded. Protocol Data Syntax Error Execution stops after the error occurs. A code that cannot be executed occurs while the protocol macro was executed. (Example: A header occurs after a terminator.) 135 Section Using Protocol Macros 5-4 5-4 Using Protocol Macros 5-4-1 Executing Send/Receive Sequences Use the PMCR(260) instruction to execute send/receive sequences. PMCR(260) Instruction Specifications (@) PMCR (260) C1 C2 Control data 1 (communications port No., serial port No., destination unit address) Control data 2 (send/receive sequence No. ) S First send word R First receive data storage word Control Data 1 (C1) 15 12 11 Communications port No. 08 07 Serial port No. 00 Destination unit address The following items are specified in C1. Communications Port No. (Internal Logical Port Number) Specify internal logical port 0 to 7 Hex for executing the PMCR(260) instruction. Note A CS1-series CPU Unit has eight internal logical ports for executing FINS commands. Specify the logical port number to be used for execution. These ports are also used by the SEND(090), RECV(098), and CMND(490) instructions used for Host Link communications. Refer to 4-4-1 Simultaneous Commands and Communications Ports for details. Serial Port No. (Physical Port) Set the physical port number of the Serial Communications Board or Unit connected to the remote device. Port 1: 1 Hex, Port 2: 2 Hex Destination Unit Address Specify the Unit address of the Serial Communications Board or Unit to execute the protocol macro. Serial Communications Board: E1 Hex Serial Communications Unit: Unit number (see note) + 10 Hex Setting range: 10 to 1F Hex Note This is the unit number (0 to F) for the CPU Bus Unit set on the rotary switch on the front panel of the Unit. Control Data 2 (C2) C2 specifies the send/receive sequence number in hexadecimal (000 to 999). Setting range: 0000 to 03E7 Hex First Send Data Word (S) S specifies the first word of the area in which the data required for sending is stored. CH S 15 11 12 0 08 07 0 00 Number of send words Total number of words including S S+1 Send data S+n The number of send words in S+1 and the following words is stored in the rightmost 8 bits of S. The setting range is 01 to FA Hex (250 words or less). S is also included in the number of words. The data to be sent is stored in S+1 and the following words. Note When there is no send data, set S to #0000. 136 Section Using Protocol Macros First Receive Data Storage Word (R) CH 5-4 R specifies the first word of the area used to initialize the reception buffer or the first word of the area used to store the receive data. 15 R 11 12 0 08 07 0 Number of receive words 00 Number of words including R R+1 Receive data R+n Before Execution of PMCR(260) The contents of R+1 and following words are set in the reception buffer. The number of words of data from R through the end of the receive data is specified in the rightmost 8 bits of R. The range that can be set is 02 to FA Hex (2 to 250 words). If 00 Hex or 01 Hex is set, the reception buffer will remain cleared after PMCR(260) execution and before executing the send/receive sequence. After Execution of PMCR(260) The number of words of receive data in R+1 and the following words is stored in the rightmost 8 bits of R. The range is 01 to FA Hex (250 words or less). R is also included in the number of words. The receive data is stored in R+1 and the following words. Note 1. The function of the receive data storage words (start from R for the number of words specified in R) differs before and after execution of PMCR(260). a) Before Execution of PMCR(260) The contents of the receive data storage words is used as initialization data for the reception buffer before the send/receive sequence is executed. b) After Execution of PMCR(260) Data received for the RECV command is stored in the receive data storage words if there is response data to be written. 2. When there is no receive data, set R to #0000. PMCR(260) Operation When PMCR(260) is executed, the send/receive sequence specified in C2 is executed for the communications port specified in bits 12 to 15 of C1 (internal logical port 0 to 7) from the serial communications port specified in bits 08 to 11 (physical port) of C1 of the device with the unit address specified in bits 00 to 07 of C1. If an operand is specified as a variable in the send message, data starting in S+1 for the number of words specified in S is used as the send data. If an operand is specified as a variable in the receive message, data will be received in words starting from R+1 and the number of words of received data will be automatically stored in R. If reception processing fails, the data that was stored started at R+1 (i.e., the number of words specified in R) is again read from the reception buffer and stored again beginning at R+1. This ensures that the current data will not be cleared and that the previous receive data will be maintained when receptions fail. 137 Section Using Protocol Macros 5-4 Flags Name Error Flag Label ER ON OFF The Network Communications Instruction Execution Flags for all serial communications ports (internal logical ports) were ON when the instruction was executed. All other cases The specified serial port (physical port) is not in protocol macro mode. Access Error Flag AER C1 or C2 data is outside the setting range. A read/write-protected area was specified for send data or receive data. All other cases A write-protected area was specified for receive data. Operand Areas and Address Ranges Area C1 C2 S R CIO Area CIO 0000 to CIO 6143 Work Area W000 to W511 Holding Area H000 to H511 Auxiliary Area A000 to A959 A448 to A959 Timer Area T0000 to T4095 --- Counter Area C0000 to C4095 --- Data Memory (DM) Area D00000 to D32767 Extended Data Memory (EM) Area E00000 to E32767 (see note) Extended Data Memory (EM) Area (including bank specification) Indirect DM/EM address, Binary En_00000 to En_32767 (n = 0 to C) (see note) (see note) Data Registers @D00000 to @32767, @E00000 to @E32767, @En_00000 to @En_32767 *D00000 to *D32767, *E00000 to *E32767, *En_00000 to *En_32767 See Control Data 0000 to 037E Hex #0000 to FFFF 1 (C1). (0 to 999) (Binary data) DR0 to DR15 --- Index Registers, direct --- Index Registers, indirect ,IR0 to ,IR15 –2048 to +2047,IR0 to –2048 to +2047,IR15 DR0 to DR15,IR0 to IR15 ,IR0+(++) to ,IR15+(++) ,–(– –)IR0 to ,–(– –)IR15 Indirect DM/EM address, BCD Constant Area (see note) (see note) Note The EM Area cannot be specified for the receive data when the interrupt notification function is being used for a Serial Communications Board. If the EM Area is specified, a protocol macro syntax error will occur and A42410 will turn ON. 138 Section Using Protocol Macros 5-4 Network Communications Flags The following table shows the Auxiliary Area flags that are used when the PMCR(260) instruction is executed. Communications Port Enabled Flags These flags turn ON when execution of the PMCR(260) instruction is enabled. Depending on the PMCR(260) instruction, they turn OFF at execution, and turn ON when the port enters an enabled status. Word A202 Communications Port Error Flags Bit 08 to 15 07 06 05 04 03 02 01 00 Contents Reserved Communications Port No. 7 Enabled Flag Communications Port No. 6 Enabled Flag Communications Port No. 5 Enabled Flag Communications Port No. 4 Enabled Flag Communications Port No. 3 Enabled Flag Communications Port No. 2 Enabled Flag Communications Port No. 1 Enabled Flag Communications Port No. 0 Enabled Flag These flags turn ON in the following cases: • When an error occurs while the PMCR(260) instruction is being executed • When an error response corresponding to each communications port occurs, or a resend error occurs When operations start or when the PMCR(260) instruction is executed, if the Communications Port Enabled Flag turns OFF, then the corresponding Error Flag also turns OFF. Word A219 Communications Port Completion Codes Bit 08 to 15 07 06 05 04 03 02 01 00 Contents Reserved Communications Port No. 7 Error Flag Communications Port No. 6 Error Flag Communications Port No. 5 Error Flag Communications Port No. 4 Error Flag Communications Port No. 3 Error Flag Communications Port No. 2 Error Flag Communications Port No. 1 Error Flag Communications Port No. 0 Error Flag The response codes (FINS completion codes) are set when the PMCR(260) instruction is executed. The contents of these words are also cleared when the Communications Port Enabled Flag turns OFF at the start of operations or when the PMCR(260) instruction is executed. Word Contents A203 Communications Port No. 0 Completion Code A204 Communications Port No. 1 Completion Code A205 Communications Port No. 2 Completion Code A206 Communications Port No. 3 Completion Code A207 Communications Port No. 4 Completion Code A208 Communications Port No. 5 Completion Code A209 Communications Port No. 6 Completion Code A210 Communications Port No. 7 Completion Code A211 to A218 Reserved Note Refer to 8-3-3 Protocol Macros for information on completion codes. 139 Section Using Protocol Macros 5-4 Flag Transitions Communications Port Enabled Flag Instruction 1 being executed Network communications instructions (PMCR(260)/SEND(090)/ RECV(098)/CMND(490)) Instruction 2 being executed Instruction 3 being executed Communications Port Error Flag Communications Port Completion Code (No unit corresponding to unit address) (Normal end) End of previous processing (Normal end) Note Before executing a PMCR(260) instruction, be sure that the communications port is set to the Protocol Macro serial communications mode. If a PMCR(260) instruction is executed for a communications port set in Host Link mode, a meaningless message may be sent from the port. The current serial communications mode can be checked in bits 12 to 15 (Protocol Macro = 6 Hex) of the following words. Boards: CIO 1905 for port 1 and CIO 1915 for port 2. Units: CIO n + 5 for port 1 and CIO n + 15 for port 2. Refer to 2-3-1 DM Area for DM Area allocations and settings. 5-4-2 Ladder Program Structure When creating a ladder program, note the following points. • To ensure that a PMCR(260) instruction is not executed while another PMCR(260) instruction is being executed, use the Protocol Macro Executing Flag in an NC input condition. • Use an OFF condition for the Protocol Macro Executing Flag and perform processing to read the results of sequence execution, or perform processing when a sequence ends in an error. Programming Example Input condition Communications Port Enabled Flags Protocol Macro Executing Flag Protocol Macro Executing Flag Reading of sequence execution results Processing of sequence errors Note When executing the PMCR(260) instruction, be sure to check that the serial communications mode for the port used for communications is set to protocol macro. If the PMCR(260) instruction is executed with the serial communications mode set to Host Link (SYSWAY), messages that cannot be used for the application will be output from the serial communications port. The serial communications mode settings can be confirmed in bits 12 to 15 of the following words in the CIO Area: Serial Communications Board, port 1: 1905, port 2: 1915; Serial Communications Unit, port 1 = n+5, port 2 = n+15. The setting for protocol macro is 6 Hex. For details of DM Area allocations, refer to 2-3-1 DM Area. 140 Section Using Protocol Macros 5-4 5-4-3 Ladder Program Example The following diagram shows an example in which sequence number 000 (Present Value Read) of a Temperature Controller (E5jK Read Protocol) is executed using the protocol for an OMRON Temperature Controller connected to port 2 (RS-422A/485) of a Serial Communications Board. Connections Serial Communications Board Port 2 Specifies the Temperature Controller Unit No. , sends the PRESENT VALUE READ command send data, and receives the present value set in the response in the specified word. Send data Receive data Temperature Controller E5jK Unit No. 00 Temperature Controller E5jK Unit No. 01 Temperature Controller E5jK Unit No. 31 32 Units max. Send Word Allocation for Sequence No. 000 (Present Value Read) First word of send data S Number of send data words S+1 (Undefined) Unit No. Word Contents (data format) Data S Number of send data words (4-digit BCD) 0002 (fixed) S+1 Unit No. (2-digit BCD) 00 to 31 Receive Word Allocation for Sequence No. 000 (Present Value Read) Receive data storage words R R+1 Number of receive data words Present value Word Contents (data format) Data R Number of receive data words (4-digit BCD) 0002 R+1 Present value (4-digit BCD) Scaling Lower limit to upper limit 141 Section Using Protocol Macros Operand Settings for the PMCR(260) Instruction Reading the present value of E5jK Unit No. 03 and storing it in DM00201 C1: Control data 2: Port 2 0: Logical port 0 E1: Destination unit address C2: Control data 0000: Sequence No. 000 S: First send data word Number of send data words = 2 Unit No. = 03 R: First receive data storage word Present value 142 5-4 Number of receive data words = 2 Present value is stored. (4-digit BCD) Section Using Protocol Macros Ladder Programming Example Input condition 000000 The following diagram shows an example in which sequence number 000 (PRESENT VALUE READ) of a Temperature Controller (E5jK Read System) is executed using the PMCR(260) instruction. If the sequence has been completed normally, the present value that has been read is transferred to another word. Communications Port No. 0 Enabled Flag A20200 Protocol Macro Executing Flag 191915 PMCR #02E1 #0000 D00100 D00200 Protocol Macro Executing Flag 191915 DIFD (14) 000100 000100 Protocol Macro Executing Flag 191915 5-4 If input condition CIO 000000 is ON, Communications Port No. 0 Enabled Flag A20200 is ON, and Protocol Macro Executing Flag CIO 191915 is OFF, then sequence No. 000 is executed for Serial Communications Board port 2 and the present value is stored in DM00201. If Protocol Macro Executing Flag CIO 191915 turns OFF, CIO 000100 turns ON (and remains ON for one cycle). Step Error Processing Flag 191914 MOV (21) D00201 Step Error Processing Flag D00300 If Protocol Macro Executing Flag CIO 191915 is OFF and Step Error Processing Flag CIO 191914 is OFF when CIO 000100 turns ON, then the received present value in DM00201 is moved to DM00300. 191914 FAL (06) 00 If CIO 000100 is ON (sequence end) and Step Error Processing Flag CIO 191914 is ON, the sequence ends abnormally and a FAL(06) instruction (Non-Fatal Diagnostic Instruction) is executed. FAL (06) 01 If the Communications Port Error Flag for port 0 turns ON, a FAL(06) instruction (Non-Fatal Diagnostic Instruction) is executed. Communications Port No. 0 Error Flag A21900 Protocol Macro Executing Flag CIO 191915 Sequence executed Sequence completed Sequence re-executed 00100 One cycle When sequence ended normally: Step Error Processing Flag CIO 191914 Present value in DM00201 moved to DM00300 FAL instruction executed When sequence ended abnormally: Step Error Processing Flag CIO 191914 143 Section Using Protocol Macros 5-4 Receive Data Storage Area before Executing PMCR(260) When the PMCR(260) instruction is executed, the reception buffer is cleared to 0 once immediately before the send/receive sequence is executed. If a ladder program is used that regularly reads the present value data, as shown in the following diagram, the present value data would normally be cleared to 0 if the data is not retrieved due to an error, such as a reception error. If reception processing fails, however, the data that was stored started at R+1 (i.e., the number of words specified in R) is again read from the reception buffer and stored again beginning at R+1. This ensures that the current data will not be cleared and that the previous receive data will be maintained when receptions fail. Make sure to set the number of words m for the data that is to be held. If the data is set to 0 or 1, the most recent receive data will not be held. Instead, it will be cleared to 0. Example: The following protocol can be used to regularly execute the PMCR(260) instruction to retrieve receive data by performing the send/receive operation once only. Always ON Flag Communications Port Enabled Flag Protocol Macro Executing Flag Set Reception buffer PMCR(260) Value is stored when reception fails. R R m words Not holding the receive area. Send/receive sequence Reception buffer RECV Clear Failed Stores cleared values Receive area R + 1 onwards Holding the receive area. Send/receive sequence Set Reception buffer Clear Receive area R + 1 onwards RECV Failed Stores set values Receive Data Storage Area Function The receive data storage area is used according to the following procedure. 1, 2, 3... 1. When the PMCR(260) instruction is executed, 250 words of the reception buffer in the Serial Communications Board or Serial Communications Unit are cleared. 2. Before executing the send/receive sequence, the contents of one less than the number of words specified in R starting from word R + 1 are used to overwrite the contents of the reception buffer (excluding the first word).This becomes the initial value of the reception buffer, and the results of the RECV command execution are waited for. If the contents of the reception buffer exceeds the contents of the number of words specified in R (or the whole area if the number of words is specified as 00), then the initial value will be set to 0000 Hex. 144 Section Using Protocol Macros 5-4 3. The data that has been received as the result of executing the RECV command will be stored in the reception buffer (except for the first word) from the specified first word (offset) and will be verified against the expected receive messages. If writing the response data is not specified, the receive data will be saved in the reception buffer and will not be stored in the CPU Unit. 4. If writing the response data is specified, the data in the reception buffer up to the most recent data (except for the first word), will be stored in from words R+1 onwards. The data stored for the number of words (including R) up to the last word will be saved. Whenever the number of data words stored exceeds the maximum, the number of words in R will be updated. 5. Steps 3 and 4 are repeated until the protocol macro operation is completed. No. of words specified here I/O memory I/O memory Changed No. of words is stored and updated. Set CPU Unit Overwrites initial value Serial Communications Board or Unit Reception buffer Write response specified Reception buffer After PMCR(260) instruction is executed the internal processing buffer is cleared Stores receive data RECV Overwrites receive data Offset Stored from the specified first word Receive data Note Processing When a Sequence Ends Abnormally As shown in the following examples, if END is set when a sequence ends normally and ABORT is set when a sequence ends abnormally, it is possible to determine whether each sequence has ended normally or abnormally by using the Sequence End Completion Flag and the Sequence Abort Completion Flag. 145 Section Using Protocol Macros Example 1 Sequence Step No. 00 5-4 Example 2 Sequence Step No. 00 Error Error Sequence ended abnormally Step No. 01 Step No. 01 Step No. 02 Sequence ended abnormally Error Error Sequence ended abnormally Sequence ended normally Sequence ended normally Sequence ended normally When the sequence ends normally When the sequence ends normally Protocol Macro Executing Flag Protocol Macro Executing Flag Sequence executed Sequence completed Sequence re-executed Sequence executed Sequence completed Sequence re-executed Sequence End Completion Flag Sequence End Completion Flag Error processing for step No. 00 Step Error Processing Flag Step Error Processing Flag When the sequence ends abnormally When the sequence ends abnormally Protocol Macro Executing Flag Protocol Macro Executing Flag Sequence executed Sequence Abort Completion Flag Sequence completed Sequence re-executed Sequence executed Sequence completed Sequence re-executed Sequence Abort Completion Flag Error processing for step No. 00 Step Error Processing Flag Step Error Processing Flag Note 146 The Step Error Processing Flag is used to see whether error processing has been executed for an individual step in a sequence, and not for the overall steps. Therefore, as shown in Example 2 above, after executing error processing during a sequence (step No. 00), the flag will remain ON, even if the next step ends normally. Care is therefore required because it is not always possible to use this flag to determine whether the overall sequence has ended abnormally. Using Protocol Macros Section 5-4 Note Abort Switch Precaution The Abort Switch can be used to abort the sequence that is being executed. The Abort Switch can be turned ON from a ladder diagram or from a Programming Device. It will be turned OFF automatically by the system when abort processing has been completed. Do not attempt to force the Abort Switch to stay ON from a ladder diagram or from a Programming Device. 147 SECTION 6 Using 1:N NT Links This section describes the procedure and other information required to use 1:N NT Links to Programmable Terminals. 6-1 6-2 6-3 Overview of 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2-2 Setup Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-1 Auxiliary Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3-3 Status Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150 152 152 153 153 153 154 156 149 Section Overview of 1:N NT Links 6-1 6-1 Overview of 1:N NT Links A PC can be connected to Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PC is allocated as a Status Control Area and a Status Notification Area for the PT, as well as to objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PC to be controlled and monitored by operations from the PT, without the use of ladder programming in the PC. One PC can be connected to up to eight PTs. The user does not need to be aware of the 1:N NT Links commands. All that is necessary is to allocate PC memory for the PTs. This section explains the Setup Area and the Protocol Status Flags when a Serial Communications Board or Unit is used with 1:N NT Links. For details on the operating PTs, refer to the operation manual for the PT. Serial Communications Unit Serial Communications Unit NT Link (Set to 1:N) PT Note 150 1:N NT Link PT 1. Set the serial port on the PT to a 1:N NT Link. The Serial Communications Board or Unit will not be able to communicate if the PT port is set for a 1:1 NT Link. Connection is not possible to PTs that do not support 1:N NT Links. 2. The number of PTs that can be connected to one port is limited by the CPU Unit’s cycle time when a Serial Communications Board or Unit is used in a 1:N NT Link, as shown in the following diagrams. Although some communications will be possible even if these restrictions are exceeded, communications errors will occur depending on the PT operating conditions and communications load. Always abide by these restrictions. 3. The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board or Unit ports. They can be used only by connecting to the peripheral port or RS-232C port on the CPU Unit. 4. Set a unique unit number for each PT connected to the same PC. If the same unit number is set for more than one PT, malfunctions will occur. Section Overview of 1:N NT Links 6-1 5. NT Link serial communications are unique and are not compatible with other serial communications modes. Example for NT31/NT631(C) PTs Priority Registered PTs per port CPU Unit’s cycle time (ms) Priority Not Registered PTs per port CPU Unit’s cycle time (ms) 6. The NT20S, NT600S, NT30, NT30C, NT620, NT620C, and NT625C cannot be used if the cycle time of the CPU Unit is 800 ms or longer (even if only one of these PTs is used in a 1:N NT Link). 7. With some PTs, timeout settings can be changed to eliminate some of the communications errors. Refer to the operation manual for the PT for details. 8. If more PTs are required by the system than allowed by the above restrictions, connect the PTs in smaller groups to different ports and increase the number ports by adding Serial Communications Units or a Serial Communications Board (if one is not already being used). 151 Section Setup Area Allocations 6-2 6-2 Setup Area Allocations This section explains the Setup Area (Allocation DM Area) when a Serial Communications Board or a Serial Communications Unit is used in 1:N NT Link mode. 6-2-1 Setup Area Words The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when 1:N NT Links are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to the unit numbers). Serial Communications Board Setup Area Allocated in the DM Area: D32000 to D32767 Words Serial Communications Units Unit No. 152 Usage D32000, D32006 Port 1 Settings D32010, D32016 Port 2 Settings D32001 to D32005 D32007 to D32009 D32011 to D32015 D32017 to D32019 Not used with1:N NT Links D32020 to D32767 Reserved for the system Setup Area Allocated in the DM Area: D30000 to D31599 First Word in Setup Area Allocated in the DM Area: m = D30000 + 100 unit number DM Area Unit No. 0 D30000 to D30099 m, m + 6: Port 1 Settings Unit No. 1 D30100 to D30199 m + 10, m + 16: Port 2 Settings Unit No. 2 D30200 to D30299 Unit No. 3 D30300 to D30399 m + 1 to m + 5, m + 7 to m + 9, m + 11 to m + 15, m + 17 to m + 19: Not used with 1:N NT Links Unit No. 4 D30400 to D30499 Unit No. 5 D30500 to D30599 Unit No. 6 D30600 to D30699 Unit No. 7 D30700 to D30799 Unit No. 8 D30800 to D30899 Unit No. 9 D30900 to D30999 Unit No. A D31000 to D31099 Unit No. B D31100 to D31199 Unit No. C D31200 to D31299 Unit No. D D31300 to D31399 Unit No. E D31400 to D31499 Unit No. F D31500 to D31599 m+20 to m+99: Not used Section Auxiliary Area and CIO Area Allocations 6-3 6-2-2 Setup Area Contents DM Area Board Unit Port 1 Port 2 Port 1 Port 2 D32000 D32010 m m + 10 D32001 D32011 m+1 m + 11 D32006 D32016 m+6 m + 16 Bit 15 14 to 12 11 to 08 07 to 05 04 03 02 01 00 15 to 04 03 to 00 15 to 03 02 to 00 m = D30000 + 100 Setting contents unit number Port settings Setting not required. Reserved Serial communications mode: Always 2 Hex (1:N NT Link) Reserved Start bits Setting not required. Data length Setting not required. Stop bits Setting not required. Parity Setting not required. Parity Setting not required. Reserved Baud rate (bps) 0 to 9 Hex: Standard NT link A Hex: High-speed NT link (see note) Reserved Maximum 1:N NT Link (1:N) unit number (0 to 7 Hex) Note High-speed NT link is available only with Serial Communications Boards/Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available. Lot No: 20Z9 Manufactured on December 20th, 1999 The year is indicated with the last digit. In this case, “9” indicates “1999.” Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is “December.” Day of manufacture. In this example, the day is “20.” NT31/631(C)-V2 are the only PTs for which high-speed NT link is supported. Except for the baud rate, the 1:N NT Link communications specifications are fixed. Therefore, the port settings, start bits, stop bits, and parity need not be set. Even if they are set, they are ignored. Serial Communications Mode Set the serial communications mode to 2 Hex to use 1:N NT Link mode. Maximum 1:N NT Links Unit No. With 1:N NT Links, up to eight Programmable Terminals (PTs) can be connected. The highest connected unit number is set here. 6-3 Auxiliary Area and CIO Area Allocations This section describes the bits and words used by the Serial Communications Board and Serial Communications Units in the Auxiliary Area and the Status Area allocated in the CIO Area. The Software Switches allocated in the CIO Area are not used for 1:N NT Links. 6-3-1 Auxiliary Area Allocations Port 1 and Port 2 Port Settings Change Bits These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. 153 Section Auxiliary Area and CIO Area Allocations 6-3 Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used. Serial Communications Board Word A636 Bit 03 to 15 02 01 00 Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved Serial Communications Units Words n Inner Board Error Information (Serial Communications Board Only) Bit 03 to 15 02 01 00 n = A620 + unit number Contents Reserved 1: Port 2 Settings Change Bit 1: Port 1 Settings Change Bit Reserved A424 contains error information for the Serial Communications Board. Word A424 Bit 12 to 15 11 10 Contents Non-fatal errors (Note 1) Reserved 1 Error log EEPROM error; 0: Normal 1: Protocol macro execution error; 0: Normal This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area, 09 08 07 06 05 04 03 02 01 00 Note Fatal errors (Note 2) 1: Protocol data error (SUM error); 0: Normal 1: Setup error; 0: Normal 1: Routing table error; 0: Normal Reserved 1: Cyclic monitoring error; 0: Normal Reserved Reserved Reserved 1: Inner Bus error; 0: Normal 1: Inner Board watchdog timer error; 0: Normal 1. When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag) (nonfatal error) will be ON. 2. When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON. For details on errors, refer to Section 8 Troubleshooting and Maintenance. 6-3-2 CIO Area Allocations Words in the CIO Area are allocated for a Status Area, which contains status and error information for the Serial Communications Board or Unit. These allocations are described in this section. Serial Communications Board 154 Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status Area. Only the words shown in the following table are used for the Status Area with 1:N NT Links. Inner Board CIO Area CIO 1900 to CIO 1999 Section Auxiliary Area and CIO Area Allocations Words Serial Communications Units 6-3 Usage CIO 1901 to CIO 1904 Board status CIO 1905 to CIO 1914 Port 1 status CIO 1915 to CIO 1924 Port 2 status CIO 1925 to CIO 1999 Reserved Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. Only the words shown in the following table are used for the Status Area with 1:N NT Links. CPU Bus Unit Area CIO 1500 to CIO 1899 n = CIO 1500 + 25 unit number Unit No. Words Unit No. 0 CIO 1500 to CIO 1524 n + 1 to n + 4: Unit status Unit No. 1 CIO 1525 to CIO 1549 n + 5 to n + 14: Port 1 status Unit No. 2 CIO 1550 to CIO 1574 n + 15 to n + 24: Port 2 status Unit No. 3 CIO 1575 to CIO 1599 Unit No. 4 CIO 1600 to CIO 1624 Unit No. 5 CIO 1625 to CIO 1649 Unit No. 6 CIO 1650 to CIO 1674 Unit No. 7 CIO 1675 to CIO 1694 Unit No. 8 CIO 1700 to CIO 1724 Unit No. 9 CIO 1725 to CIO 1749 Unit No. A CIO 1750 to CIO 1774 Unit No. B CIO 1775 to CIO 1799 Unit No. C CIO 1800 to CIO 1824 Unit No. D CIO 1825 to CIO 1849 Unit No. E CIO 1850 to CIO 1874 Unit No. F CIO 1875 to CIO 1899 155 Section Auxiliary Area and CIO Area Allocations 6-3 6-3-3 Status Area Contents The Status Area is used to input status information from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status. n = CIO 1500 + 25 Words Board Port 1 Port 2 CIO 1901 Bit Units Port 1 Port 2 n+1 Contents CIO 1902 n+2 02 to 15 01 00 00 to 15 CIO 1903 n+3 00 to 15 Reserved CIO 1904 CIO CIO 1905 1915 n+4 n+5 00 to 15 n + 15 Reserved Port Setup setting Area status CIO 1906 n+6 n + 16 CIO 1916 12 to 15 08 to 11 05 to 07 04 03 02 01 00 15 14 Reserved 1: Error log data error 1: Protocol data error Reserved Port setting status Hardware settings 13 CIO 1907 CIO 1917 n+7 n + 17 02 to 12 01 00 11 to 15 10 CIO 1908 CIO 1909 to CIO 1914 CIO 1918 CIO 1919 to CIO 1924 n+8 n + 18 n+9 to n + 14 n + 19 to n + 24 0: Error log data normal 0: Protocol data normal Serial communications mode: Always 2 Hex Baud rate: 0 to 9 Hex, A Hex (see note) Reserved Start bit: Always 0 Hex Data length: Always 1 Hex Stop bit: Always 1 Hex Parity, Yes/No: Always 0 Hex Parity, Even/Odd: Always 1 Hex 0: No; 0: RS-232C; 1: RS-422A/485; 1: Reserved 0: 1: 0: 1: Reserved 0: Terminating resistance OFF 1: Terminating resistance ON 07 06 05 04 03 00 to 02 00 to15 Reserved 1: Setup error 0: Setup normal 1: Port operating 0: Port stopped Commu- Reserved nications 1: Remote Unit receive busy (flow control) status 0: Remote Unit receive wait (Always 0 Hex) Reserved 1: Local Unit receive busy (flow control) 0: Local Unit receive wait (Always 0 Hex) TransER signal mission DTR signal control Reserved signal status CTS signal RTS signal Reserved Reserved 15 to 00 Protocol status 09 08 unit number Note The baud rate that is input to the CPU Unit will depend on the setting in the System Setup. If the default value is used because of a System Setup error, this default setting is input. 156 Section Auxiliary Area and CIO Area Allocations 6-3 Error Log EEPROM Error This bit will be set to 1 if an error occurs in reading or writing the error log stored in EEPROM on the assumption that the EEPROM has reached its useful life. If a Serial Communications Unit is being used, the ERC indicator will also light. If a Serial Communications Board is being used, A42411 will turn ON and the ERR/ ALM indicator on the CPU Unit will flash, indicating a non-fatal error. Protocol Data Error This bit will be turned ON if a checksum error is detected in the protocol data at startup. The checksum is checked for all serial communications modes. If a Serial Communications Unit is being used, the ERC indicator will also flash. If a Serial Communications Board is being used, A42409 will turn ON, the ERR/ALM indicator on the CPU Unit will flash, and the RDY indicator will flash at 1-second intervals, indicating a non-fatal error. The operation of the 1:N NT Links will not be affected by a protocol data error. Port Setting Status The settings in the Setup Area for the following items will be stored: Serial communications mode, baud rate, start bits, data length, stop bits, parity, ports, terminating resistance, terminating resistance, setup error, and port operating/ stopped status. The port operating/stopped status will always be 1 for 1:N NT Links. Communications Status The flow control and buffer status is stored. This status is not used for 1:N NT Links. These bits are cleared at startup or when a port is restarted using STUP(237) or a Port Settings Change Bit (Auxiliary Area). Transmission Control Signal Status The status of the transmission control signals is stored. Protocol Status The bits corresponding to the unit numbers of the connected PTs for which priority processing has been set and the bits corresponding to the unit numbers for which communications are being executed are turned ON. Words Board Port 1 Port 2 CIO CIO 1909 1919 CIO 1910 to CIO 1914 CIO 1920 to CIO 1924 Bit Contents Unit Port 1 Port 2 n+9 n + 19 15 to 08 07 to 00 n + 10 to n + 20 to 15 to 00 n + 14 n + 24 15 14 13 12 11 10 PT Priority Registered Flag PT Communications Execution Flag Reserved 09 PT Priority Registered Flag Unit No. 7 to Unit No. 0 08 07 06 05 04 03 02 01 00 PT Communications Execution Flag Unit No. 7 to Unit No. 0 157 SECTION 7 Loopback Test This section describes the procedure and other information required to conduct loopback test to check the serial communications ports. 7-1 7-2 7-3 Executing Loopback Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-3 Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1-4 Indicators Used for the Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 160 160 160 161 161 162 159 Section Executing Loopback Tests 7-1 7-1 Executing Loopback Tests 7-1-1 Overview Executing a loopback test will allow you to test a port communications circuit by connecting a loopback-wire connector to the port of a Serial Communications Board or Unit, looping back the transmitted data to make it the received data for the Unit or Board, and then comparing and checking the data. Loopback test switch Loopback test The loopback test results are stored. 7-1-2 Connection Method Make the connections according to the type of port, as shown in the following diagrams. RS-232C Port Pin 2 3 4 5 1 8 7 Signal SD RD RTS CTS FG DTR DSR RS-422A/485 Port Pin Signal 1 2 6 8 SDA SDB RDA RDB 7-1-3 Procedure The loopback test is performed using the procedure shown below. 1, 2, 3... 160 1. Connect the connector of the port to be used to execute the loopback test. See 7-1-2 Connection Method for details. 2. Set the serial communications mode in the Setup Area to Loopback Test (F Hex). Refer to 7-2 Setup Area Allocations. 3. Set the following communications settings for the loopback test in the Setup Area: Baud rate, stop bits, parity, and data length. Refer to 7-2 Setup Area Allocations. 4. Cycle the power, restart the Unit or Board, or restart the port. Use the following bits to restart the Board or Unit. Board: A60800 Units: A501, bits 00 to 15 (bits correspond to unit numbers 0 to F) Use the following bits to restart the port. Board: A636, bit 01 for port 1 and bit 02 for port 2 Units: A620 + unit number, bit 01 for port 1 and bit 02 for port 2 5. Turn ON the Loopback Test Switch. To end the test, turn OFF the switch. The Loopback Test Switches are as follows: Board: CIO 1900, bit 06 for port 1 and bit 14 for port 2 Unit: n, bit 06 for port 1 and bit 14 for port 2 (n = CIO 1500 + 25 x Unit No.) Refer to 7-3 CIO Area Allocations. Section Setup Area Allocations 7-2 6. Use the protocol status to check the results. Refer to 7-3 CIO Area Allocations. 7-1-4 Indicators Used for the Loopback Test When the test is being executed, the indicators shown below will flash. Use the protocol status to check whether or not the test has been executed normally. Serial Communications Board Port 1: COMM1 indicator Port 2: COMM2 indicator Serial Communications Unit Port 1: SD1/RD1 indicator Port 2: SD2/RD2 indicator 7-2 Setup Area Allocations This section describes the Setup Area allocated to the Serial Communications Board and Serial Communications Units in the DM Area when loopback tests are performed. The loopback test is performed using the Host Link mode protocol. The Setup is basically the same as for the Host Link mode. Bit DM Area Board Port 1 Port 2 D32000 D32010 D32001 D32011 Unit Port 1 Port 2 m m + 10 m+1 Serial Communications Mode m + 11 15 14 to 12 11 to 08 07 to 05 04 03 02 01 00 15 to 04 03 to 00 m = D30000 + 100 Settings unit number Port settings 0: Defaults, 1: User settings Reserved Serial communications mode: Always F Hex (Loopback test) Reserved Start bits 0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting) Data length 0: 7 bits, 1: 8 bits Start bits 0: 2 bits, 1: 1 bit Parity 0: Yes, 1: No Parity 0: Even, 1: Odd Reserved Baud rate ( bps) 0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200; 8: 38,400; 9: 57,600; A: 115,200 Set the serial communications mode to F Hex to perform a loopback test. For the other settings, refer to 4-2 Setup Area Allocations. 161 Section CIO Area Allocations 7-3 7-3 CIO Area Allocations The loopback test execution results can be read form the protocol status area allocated in the CIO Area. Protocol Status The information shown in the following table is input to the CPU Unit in the protocol status area. If an error occurs, the flags will be turned ON Bit Word Board Port 1 Port 2 CIO CIO 1909 1919 CIO 1910 CIO 1911 CIO 1912 to CIO 1914 CIO 1920 CIO 1921 CIO 1922 to CIO 1924 n = 1500 + 25 unit number Contents Unit Port 1 n+9 Port 2 n + 19 n + 10 n + 11 Test status n + 20 15 14 to 09 08 07 06 05 04 03 02 01 00 15 to 00 n + 21 15 to 00 Test error count n + 12 to n + 22 to 15 to 00 n + 14 n + 24 Error Reserved DTR check error CTS check error Reserved Timeout error Parity error Overrun error Framing error Reserved Conveyor error Test execution count Reserved The test execution count and test error count are cleared at startup. If the number of tests or the number of test errors is counted to FFFF (hex), the value of the count will remain at FFFF, but testing will continue. 162 SECTION 8 Troubleshooting and Maintenance This section describes the troubleshooting and maintenance procedures for the Serial Communications Boards and the Serial Communications Unit. 8-1 8-2 8-3 8-4 8-5 8-6 Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1-1 Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1-2 Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Status Area Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3-2 1:N NT Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3-3 Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-1 Error Log Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-2 Error Log Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-3 Error Log Table Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-4 Error Codes and Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-5 Error Codes and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-6 Reading and Clearing Error Log Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-7 CONTROLLER DATA READ: 05 01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-8 ERROR LOG READ: 21 02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4-9 ERROR LOG CLEAR: 21 023 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5-1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5-2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replacement Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6-1 Precautions when Replacing Board or Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6-2 Settings after Replacing Board or Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6-3 Replacing the Board or Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164 164 165 167 167 167 173 175 182 182 182 182 183 185 186 186 187 188 188 188 188 189 189 190 190 163 Section Indicator Error Displays 8-1 8-1 Indicator Error Displays 8-1-1 Serial Communications Board Indicators RDY Possible cause Remedy ERR/ALM CPU Unit Lit Not lit The Board has started normally. --- Not lit Lit The Board is faulty (hardware self-diagnostic function). If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board. A bus error has occurred. Firmly secure the Board to the CPU Unit. An initialization recognition error has occurred (the Board is not correctly recognized by the CPU Unit). If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board. Not lit Flashing An initialization recognition error has occurred (the Serial Communications Unit was not recognized by the CPU Unit). If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board. Not lit Not lit The CPU Unit is not receiving normal power supply. Check the power supply voltage and supply the correct electric power to the Unit. The Board is not correctly secured to the CPU Unit. Firmly secure the Board. The Board is faulty. If all the indicators are not lit when the Board is mounted to another CPU Unit, replace the Board. An error (such as a CPU Unit WDT error) has occurred in the CPU Unit. Eliminate the cause of the error. If the error persists, replace the CPU Unit. The Board is faulty. If all the indicators are not lit when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit. A bus error has occurred. Check the operating environment and eliminate the cause of the error. Lit Lit Firmly secure the Board. Refer to A42400 and A42401. Lit Flashing The communications circuit is faulty. Conduct a loopback test. If an error occurs, replace the Board. A protocol data syntax error has occurred. Correct the protocol data and transfer it to the Board. Try executing a normal sequence for the serial port where the error is occurring or switch the CPU Unit to PROGRAM mode and remove the cause of the error. 164 A system setting error has occurred. Correct the Setup Area settings, and cycle the power, restart the Board, restart the port, or execute STUP(237). The routing tables are not set correctly. When the routing tables are used, set them correctly. When the routing tables are not used, delete the Board settings from the table. An error has occurred in the CPU Unit. Eliminate the cause of the error. If the error persists, replace the CPU Unit. The error log EEPROM is faulty. Cycle the power supply. If the error persists, replace the CPU Unit. Section Indicator Error Displays Indicators ERR/ALM CPU Unit Flashing Flashing Possible cause 8-1 Remedy RDY A protocol data write error has occurred or protocol data has been destroyed. If the indicator status remains the same when the protocol data is retransmitted, replace the Board. There is no protocol data. Transfer protocol data to the Board. Serial Communications Board Error Information (A424) Bit 00 Flag Fatal error 01 04 05 07 08 09 10 11 For Serial Communications Boards, refer to the following Auxiliary Area word (A424) as well as the indicator displays shown on the previous page. When an error occurs, the corresponding flag is turned ON. Nonfatal error Possible cause Remedy Inner Board WDT error The Board is faulty. Firmly secure the Board to the CPU Unit. If the error persists when the Board is mounted to another CPU Unit, replace the Board. Inner Bus error A bus error has occurred. Firmly secure the Board to the CPU Unit. If the error persists when the Board is mounted to another CPU Unit, replace the Board. Inner Board service failure Cyclic monitoring error An initial recognition error has occurred. The Inner Bus access right cannot be retained for more than the specified time. This flag will not turn ON in the present system. Routing table error System setting error The routing tables are not set correctly. A system setting error has occurred. Correct the routing tables and retransfer them. Protocol data error Protocol macro execution error A protocol data checksum error has occurred. A syntax error has occurred during protocol macro execution. If the error persists when protocol data is retransmitted, replace the Board. Correct the protocol data and retransfer it. Error Log data error The service life of the EEPROM has expired. CPU Unit and system load is too high. Review the application. Correct the Setup Area settings, cycle the power supply, restart the Board, or restart the port, or execute STUP(237). Try executing a correct sequence for the serial port where the error is occurring or switch the CPU Unit to PROGRAM mode and remove the cause of the error. If this error persists even if the power supply is cycled, replace the Board. When a fatal error occurs, the ERR and ALM indicators on the CPU Unit will light. When a non-fatal error occurs, the ERR and ALM indicators on the CPU Unit will flash. Refer to the indicator error displays. Note The ERR/ALM indicator will continue to flash even after the cause of a non-fatal error has been removed for the Serial Communications Board. The indicator can be stopped by clearing the error from a Programming Console or other Programming Device for errors for bits 05, 07, 08, 09, and 10. Press the FUN Key and then the MONITOR Key from the Programming Console. Refer to the CX-Programmer Operation Manual for the CX-Programmer procedure. 8-1-2 Serial Communications Units Indicators RUN Lit ERC ERH RDY Not lit Not lit Lit Possible cause The Serial Communications Unit has started normally. Remedy --- 165 Section Indicator Error Displays RUN Indicators ERC ERH Not lit Lit Possible cause Remedy 8-1 RDY --- --- The Serial Communications Unit is found to be faulty (by the hardware self-diagnostic function). If the ERC indicator lights up when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit. Not lit Not lit Lit --- There is more than one identical unit number within the same CPU Unit. Assign a unique unit number to each Serial Communications Unit on the CPU Rack and Expansion Racks. An initial recognition error has occurred (the Serial Communications Unit was not correctly recognized by the CPU Unit). If the ERH indicator lights up when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit. An initial recognition error has occurred (the Serial Communications Unit was not correctly recognized by the CPU Unit). If the ERC and ERH indicators light when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit. Not lit Lit Lit --- Not lit Not lit Not lit Not lit The CPU Unit is not receiving normal power supply. Check the power supply voltage and supply the correct electric power to the Unit. The Serial Communications Unit is not cor- Firmly secure the Unit. rectly secured to the Backplane. The Serial Communications Unit is not mounted in an appropriate slot. Mount the Unit in an appropriate slot. The Serial Communications Unit is faulty. If all the indicators are not lit when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit. Lit --- Flash- --ing A system setting error has occurred. Correct the Setup Area settings, cycle the power supply, restart the Unit/Board, or restart the port, or execute STUP(237). Lit Lit --- The error log EEPROM is faulty. If the problem persists even if the power supply is cycled, replace the Unit. Lit Flash- --ing Lit Flash- --ing --- Flash- A protocol data write error has occurred or ing protocol data has been destroyed. Lit If the indicator status remains the same when the protocol data is retransmitted, replace the Unit. There is no protocol data. Transfer protocol data to the Unit. A protocol data syntax error has occurred. Correct the protocol data and transfer it to the Unit. The ERC indicator can also be turned OFF by executing a normal sequence for the serial port for which the error is occurring or by switching the CPU Unit to PROGRAM mode temporarily. Lit Lit --- Flash- The flash memory for protocol data is ing faulty. Transfer the protocol data to the Unit. If the problem persists after correct protocol data is transferred, replace the Unit. Lit --- Lit --- The routing tables are not set correctly. When the routing tables are used, set them correctly. When the routing tables are not used, delete the Unit settings from the table. An error (such as a CPU Unit WDT error) has occurred in the CPU Unit. Eliminate the cause of the error. If the error persists, replace the CPU Unit. A CPU Unit service monitoring error has occurred. Check the operating environment and eliminate the cause of the error. (Check to be sure that the problem is not caused by another CPU Bus Unit having the same unit number.) A bus error has occurred. Check the operating environment and eliminate the cause of the error. Firmly secure the Unit. 166 Section Troubleshooting 8-2 8-3 Status Area Error Indications This section describes status area error information. Status Area Error Information When an error occurs, the corresponding flag is turned ON. n = CIO 1500 + 25 Word Board CIO 1901 Bit Flag name Possible cause unit number Remedy Unit n+1 01 Error Log data error The error log EEPROM is faulty. If the problem persists even if the power supply is cycled, replace the Board/Unit. 00 Protocol data error A protocol data checksum error has occurred. If the error persists when protocol data is retransmitted, replace the Board or Unit. Correct the Setup Area settings, cycle the power supply, restart the Unit/Board, or restart the port, or execute the STUP(237) instruction. CIO 1906 CIO 1916 n+6 n + 16 01 System Setup error A System Setup error has occurred. CIO 1907 CIO 1917 n+7 n + 17 10 Remote node receive busy The remote node is Cancel the communications with in receive buffer busy the remote node until this flag is status when flow turned OFF. control is set for the protocol. 08 Local node receive busy The local node is in receive buffer busy status. 8-3 Increase the transmission interval to reduce transmission load to the remote node for which flow control is set. Troubleshooting This section describes how to resolve transmission and reception problems. “m” and “n” in the tables represent the following word addresses for the Board and Unit. Symbol Board Units m D32000 D30000 + 100 x unit number n CIO 1900 CIO 1500 + 25 x unit number 8-3-1 Host Link Communications Serial communications mode Serial commu- --nications mode is not set to Host Link. Indicator status Status information, etc. --- CIO Area Cause Bits 12 to 15 (Serial Serial communicaCommunications tions mode is not Mode) of CIO Area set correctly. words n + 5/n + 15 are set to a value other than 5 Hex. Remedy Set bits 08 to 11 (Serial Communications Mode) of DM Area words m/m + 10 to 0 or 5 Hex (Host Link). 167 Section Troubleshooting Serial communications mode Serial communications mode is set to Host Link. Indicator status Status information, etc. The --SDj/RDj and COMj indicators do not flash at all. (Communications have not been electrically established.) CIO Area --- Cause Check the wiring. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (CS1W-SCB41 only). Reset the port to the correct wiring setting. Adapters such as the NT-AL001-E are incorrectly wired or set. Commands are not being set from the host. For the Unit, the SDj indicator does not flash at all (Communications have been electrically established.) CIO Area words n + 8/n + 18 (transmission error status) are set to 0000 Hex. CIO Area words n + 5/n + 15 (port settings in the System Setup) do not correspond to the settings of the remote device. --- The System Setup in DM Area words m + 2 and m + 3/m + 12 and m + 13 of the Board or Unit (Host Link Unit No., Host Link send delay time, etc.) does not correspond to the settings for the remote device. The command format and data length of the data sent from the host are incorrect. Cables are incorrectly connected. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect (CS1W-SCB41 only). Adapters such as the NT-AL001-E are incorrectly wired or set. 168 Remedy Cables are incorrectly connected. This is a hardware error. The RDj and There is no COMj indica- transmission error. tors are flashing, but the response has not been returned from the host. 8-3 Wire all nodes using the 4-wire method. Reset the serial communications port at the host, and rewrite the program. Set bits 08 to 11 (Serial Communications Mode) of DM Area words m/m + 10 to F Hex (Loopback Test Serial Communications Mode). Then, connect the connector wire for a loopback test and conduct a loopback test by turning ON bit 14 (Loopback Test Switch) of CIO Area word n. The test data is reflected in CIO Area words n+9/n+19. If an error occurs during the test, replace the Board or Unit. Reset the settings in DM Area words m + 2 and m + 3/m + 12 and m + 13 of the Board or Unit (Host Link Unit No., Host Link send delay time, etc.), so that they correspond to the settings at the host device. Correct the command frame (header, Host Link Unit No., terminator, etc.) and the program. Check the wiring and switch settings, and correct if necessary. Section Troubleshooting Serial communications mode Serial communications mode is set to Host Link. Indicator status Status information, etc. The RDj and There is no COMj indica- transmission error. tors are flashing, but the response has not been returned from the host. CIO Area --- Cause Remedy This is a transmission circuit hardware error. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit. Reset the frame parameters correctly. The following settings in the FA command frame are incorrect. For the Unit, the SDj indicator does not flash at all. (Communications have been electrically established.) 8-3 The ICF is set to have no response. The value of the remote destination address (DNA, DA1, DA2) has not been properly set. The send delay Reset the parameters in time setting is too the System Setup correctlong. ly. CTS control is ON and bit 04 of CIO Area words n + 7/n + 17 (CTS signal) is OFF. The CTS control is set, but the RTS signal from the remote Unit has not entered in the CTS signal of the local Unit. Perform one of the following: Wire the local Unit RTS signal to the CTS signal using loopback. Disable the CTS control. Enter the RTS signal of the remote Unit into the CTS signal of the local Unit, and then use CTS control. There is a transmission error. In CIO Area words n + 8/ n + 18, bit 15 (transmission error status) is turned ON, and bit 04 (overrun error), bit 03 (framing error), or bit 02 (parity error) is turned ON. The communications conditions and baud rate do not match the settings at the host. There is noise interference. Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n + 8/ n + 18. Use shielded twisted-pair cables. Lay power lines separately using ducts. Review the installation environment to reduce noise interference. 169 Section Troubleshooting Cause 8-3 Serial communications mode Indicator status Status information, etc. CIO Area Serial communications mode is set to Host Link. The RDj/SDj and COMj indicators are flashing, and an error response has returned to the host. There is no transmission error. CIO Area words n + 8/ n + 18 (transmission error status) are set to 0000 Hex. A command was sent from the host with incorrect parameters. Review the host’s settings and program (such as parameter settings) based on the response contents. There is a transmission error. The communications conditions and baud rate do not match the settings at the host. The RDj/SDj and COMj indicators are flashing, but sometimes there is no response returned. There is a transmission error sometimes. In CIO Area words n + 8/ n + 18, bit 15 (transmission error status) is turned ON, and bit 04 (overrun error), bit 03 (framing error), or bit 02 (parity error) is turned ON. In CIO Area words n + 8/ n + 18, bit 15 (transmission error status) is turned ON, and bit 04 (overrun error), bit 03 (framing error), or bit 02 (parity error) is turned ON. Terminating resistance switch (TERM ON/OFF) status Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n + 8/ n + 18. Review the System Setup. The baud rate is outside the allowable range, and the stop bits do not match, causing the bits to be out of alignment. Review the host’s settings and program (such as baud rate and frame format). Cables are incorrectly connected. Check the wiring. The RS-422A/485 port terminating resistance setting is incorrect. Turn ON the terminating resistance of the Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes. Adapters such as the NT-AL001-E are incorrectly wired or the terminating resistance is incorrectly set. CIO Area words n + 8/ n + 18 (transmission error status) are not set to 0000 Hex. Remedy Transmission errors are occurring that are caused by noise interference. Use shielded twisted-pair cables. Lay power lines separately using ducts. Review the installation environment to reduce noise interference. 170 Section Troubleshooting Serial communications mode Indicator status Host Link (with unsolicited communications) The SDj/RDj and COMj indicators are all flashing. Status information, etc. CIO Area Cause SEND(090)/ The AER Flag (one RECV(098)/ of the condition CMND(490) flags) is ON. instructions have been executed but have not been sent. 8-3 Remedy The contents of the S, C, and D operands for the SEND(090), RECV(098), and CMND(490) instructions is set in a read-protected area. Bit 00 to 07 of word The contents of the A219 (Communica- S, C, and D opertions Port Error ands for the Flag) are set to 1 SEND(090), (ON). RECV(098), and CMND(490) instructions is set incorrectly. The communicaThe ER Flag (one tions port number of the condition to be used is exeflags) is ON. cuting a SEND(090)/ The Communications Port Enabled RECV(098)/ CMND(490) inFlag (A20200 to struction or A20207)is OFF PMCR(260) in(execution disstruction. abled) Check the contents of the S, C, and D operands of the SEND(090), RECV(098), and CMND(490) instructions, and correct if necessary. The Communications Port Enabled Flag (A20200 to A20207) is set as an NC the execution condition for SEND(090), RECV(098), and CMND(490) instructions. Program is incorrect. Set the Communications Port Enabled Flag as an NC execution condition for SEND(090), RECV(098), and CMND(490) instructions. Bit 15 of DM Area words m + 3/m + 13 (CTS control) is turned ON, and bit 04 of CIO Area words n + 7/n + 17 (CTS signal) is turned OFF. The Board or Unit is set for CTS control, but the RTS signal from the host is not input into the CTS signal of the local Unit. Perform one of the following error processing methods. Check the contents of the S, C, and D operands of the SEND(090), RECV(098), and CMND(490) instructions, and correct if necessary. Either use a different communications port number than the one being used to execute the SEND(090)/ RECV(098)/ CMND(490) instruction or PMCR(260) instruction, or wait for the same communications port number to be enabled and execute the instruction. Loopback the RTS and CTS signals on the local Unit. Set to no CTS control. Input the RTS signal from the remote Unit into the CTS signal of the local Unit for CTS control. 171 Section Troubleshooting Serial communications mode Host Link, slave-initiated communications Indicator status The SDjand COMj indicators are flashing, but there is no response from the host. Status information, etc. CIO Area A transmis--sion error has not been detected at the host. ----- --- CIO Area words n + 5/n + 15 (port setting status in Setup Area settings) do not correspond with the settings at the host. Cause There is a hardware error in the reception circuit. Cables are incorrectly wired. There is a hardware error in the reception circuit. Adapters such as the NT-AL001-E are incorrectly wired or set. --- The communications conditions and baud rate do not match the settings at the host. 8-3 Remedy Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit. Check the wiring and correct. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit. Check the program at the host. When unsolicited communications are used with Host Link mode, there must be a response returned from the host for every command sent from the Board or Unit. Reset the parameters in the System Setup and at the host correctly. Note The System Setup cannot be changed unless the power supply is cycled, the Board or Unit is restarted, the port is restarted, or the STUP(237) instruction is executed. Refer to 1-7 Comparison to Previous Products for details. 172 Section Troubleshooting 8-3 8-3-2 1:N NT Link Mode Serial communications mode Indicator display Status information, etc. Serial communications mode is not set to NT Link. --- --- Serial communications mode is set to NT Link. The SDj/RDj --and COMjindicators do not flash at all. (Communications have not been electrically established.) --The SDj and COMj indicators are flashing, but the Unit or Board cannot communicate with the Programmable Terminal (PT). Words allocated in the CIO Area Cause Remedy Bits 12 to 15 of the words allocated in the CIO Area n+5/n+15 are set to a value other than 2 Hex. Serial communications mode is not set correctly. Review the Setup Area settings. --- This is a hardware error. Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit. --- The baud rate setting is different to the PT’s baud rate setting. There is a setting error for the PT serial port. Either change the baud rate setting in the System Setup or change the baud rate setting for the PT. Correct the PT serial port settings. The I:N NT Link unit number of the PT is incorrect. Review the NT Link unit number of the PT. The same 1:N NT Link unit number has been set for more than one PT The maximum alReview the Setup Area lowable NT Link unit settings. number is incorrectly set for the system. Cables are incorrectly connected. Review the wiring or switch settings. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect. Adapters such as the NT-AL001-E are incorrectly wired or set. A communications error frequently occurs due to noise, etc. There is a PT hardware error. Review the wiring and installation environment. Replace the PT. 173 Section Troubleshooting Serial communications mode Indicator display Serial communications mode is set to NT Link. The SDj/RDj and COMj indicators are flashing, but a communications error sometimes occurs in the PT. Status information, etc. --- Words allocated in the CIO Area --- Cause 8-3 Remedy Cables are incorrectly connected. Review the wiring or switch settings. The RS-422A/485 port setting (2-wire or 4-wire) is incorrect. Check whether the terminating resistances of the host computer and the last Unit are set to ON, and the terminating resistances of other Units are set to OFF. Adapters such as the NT-AL001-E are incorrectly wired or set. A communications error frequently occurs due to noise, etc. The communications monitoring time for the PT is insufficient. The load on the PC is too high. Review the wiring and installation environment. Increase the number of retries for the PT as required. Increase the communications monitoring time for the PT. Lighten the load on the PC. Reduce the number of PTs connected to each serial port by using other ports for some of the PTs. Adjust the timeout and retry settings in the PT. Note 174 1. The PT serial port must be set for a 1:N NT Link. The PT will not be able to communicate with a Serial Communications Board or Unit if the PT is set for a 1:1 NT Link. 2. The System Setup cannot be changed unless the power supply is cycled, the Board or Unit is restarted, the port is restarted, or the STUP(237) instruction is executed. Refer to 1-7 Comparison to Previous Products for details. Section Troubleshooting 8-3 8-3-3 Protocol Macros Serial communications mode Indicator display Status information, etc. Words allocated in the CIO Area Cause Remedy Serial com- --munications mode is not set to protocol macro. --- Bits 12 to 15 of the words allocated in the CIO Area n+5/n+15 are set to a value other than 6 Hex. Serial communications Set bits 11 to 08 (Serial mode is not set correctly. Communications Mode) of the Allocation DM Area m/m+10 to 6 Hex (Protocol Macro). Serial communications mode is set to protocol macro. The PMCR(260) instruction is executed, but bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 does not turn ON. Bits 00 to 07 of the Communications Port Error Flags in A219 are set to 1 (ON). The PMCR(260) instruction operand settings or execution timing are incorrect. See note 1. As PMCR(260) instruction execution conditions, bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 is set as a NO execution condition. The program is incorrect. As PMCR(260) instruction execution conditions, set bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 to a NC execution condition. The SDj/RDj and COMj indicators do not flash at all. (Communications has not been electrically established.) The ER Flag (one of The problem cause is Condition Flags) is one of the following: set to ON. – The data range for the PMCR(260) instruction C1 operand is incorrect. – The number of data words in the S or D operand exceeds 250. – The Communications Port Error Flag is set to OFF. The AER Flag (one An illegal address is of the Conditions specified for the S or D Flags) is ON. operands of the PMCR(260) instruction. Bits 00 to 03 (Error The sequence number Code) of the words specified in the allocated in the CIO PMCR(260) instruction Area n+9/n+19 are C2 operand is a value set to 2 Hex (Seother than 000 Hex to quence Number Er- 3E7 Hex (000 to 999 in ror). decimal notation). Check the PMCR(260) instruction C1, C2, C3, S, and D operand settings for errors. Bits 00 to 03 (Error Code) of the words allocated in the CIO Area n+9/n+19 are set to 3 Hex (Data Read/Write Range Error). Specify another area, or reduce the size of the data to be sent or received. Correct any mistakes in the operands of PMCR(260). Set the PMCR(260) instruction C2 operand to a value between 000 Hex and 03E7 Hex (between 000 and 999 in decimal notation). Check whether the send/ The specified send/rereceive sequence numceive sequence number ber is correct. does not exist in the protocol data. The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit. 175 Section Troubleshooting Serial communications mode Serial communications mode is set to protocol macro. Indicator display Status information, etc. Words allocated in the CIO Area Cause Remedy The SDj/RDj and COMj indicators do not flash at all. (Communications have not been electrically established.) The PMCR(260) instruction is executed, but bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 does not turn ON. Bits 00 to 03 (Error Code) of the words allocated in the CIO Area n+9/n+19 are set to 4 Hex (Protocol Data Syntax Error). The protocol data in the Board or Unit is incorrect. Use CX-Protocol to correct and transfer the protocol data. The Network Communications Instruction Execution Enabled Flag (A20200 to A20207) is set to OFF (Execution Disabled). The SEND(090), RECV(098), CMND(490), or another PMCR(260) instruction is currently being executed using the same communications port number. Execute the PMCR(260) instruction using a communications port number (set in bits 12 to 15 of C1) other than that used for the SEND(090), RECV(098), CMND(490), or another PMCR(260) instruction. As PMCR(260) instruction execution conditions, set the Network Communications Instruction Execution Enabled Flag (A20200 to A20207) to a NO execution condition. As PMCR(260) The program is incorinstruction execurect. tion conditions, the Network Communications Instruction Execution Enabled Flag (A20200 to A20207) is set as a NC execution condition. Bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 is turned ON when the PMCR(260) instruction is executed, but data cannot be sent or received properly. 176 8-3 Bit 00 (Port Active) of the words allocated in the CIO Area n+6/n+16 remains 0 (Port Inactive). Send processing is not executed. Bit 10 (Remote Node Receive Busy) of the words allocated in the CIO Area n+7/n+17 is set to ON (Remote Node Busy). Bit 09 (Sequence Wait) of the words allocated in the CIO Area n+9/n+19 is set to ON (Sequence Wait Status). Protocol data is being transferred, or a SUM value error has occurred. Wait for the transfer of protocol data to finish or use CX-Protocol to transfer the protocol data. The send wait time specified in send/receive sequence step units is too long. The CS signal from the remote node cannot turn ON (the remote node remains in busy status) because the transmission control parameter “RS/CS Flow Control” is set to “Yes.” The WAIT command cannot be released. Use CX-Protocol to check whether the send wait time is correctly set. Release the remote node busy status to enable the local node CS signal to turn ON. Review the program so that bits 00 and 08 (Wait Release Switch) of word n in the words allocated in the CIO Area can be switched from OFF to ON. Section Troubleshooting Serial communications mode Serial communications mode is set to protocol macro. Indicator display Status information, etc. The SDj/RDj and COMj indicators do not flash at all. (Communications has not been electrically established.) Bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 momentarily turns ON when the PMCR(260) instruction is executed, but it cannot remain ON. Send data has already been transmitted, but there is no response from the remote node. Bits 03 and 11 Abort Switch is force-set. Release the forced or (Abort Switch) of the Abort Switch. words allocated in the CIO Area n are force-set. --- This is a hardware error. Bit 10 (Sequence Abort End Flag) of the Protocol words allocated in the CIO Area n+9/n+19 is set to ON. Bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 remains ON when the PMCR(260) instruction is executed without setting the monitoring time in sequence units. The sequence is aborted (the step is interrupted). Protocol macro data is not set correctly. The SDj/RDj and COMj indicators are flashing, but the Unit or Board cannot perform communications. Words allocated in the CIO Area Cause 8-3 The Setup Area settings such as the baud rate and frame format differ from those of the remote node. Remedy Set bits 11 to 08 (Serial Communications Mode) of the Allocation DM Area to F Hex (Loopback Test Serial Communications Mode), connect the connector wired for a loopback test, then conduct a loopback test by turning ON bit 14 of word n. The test data is reflected in the Allocation DM Area n+9/n+19. If an error occurs during the test, replace the Board or Unit. Use CX-Protocol transmission line trace to check whether the protocol data and Setup Area settings are correct. The sequence is running and does not end (the words allocated in the CIO Area is in receive status). 177 Section Troubleshooting Serial communications mode Serial communications mode is set to protocol macro. Indicator display Status information, etc. Words allocated in the CIO Area Cause The SDj/RDj and COMj indicators are flashing, but the Unit or Board cannot perform communications. Send data has already been transmitted, but there is no response from the remote node. The contents of the words allocated in the CIO Area n+5/n+15 (System Port Settings) do not match those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on. Bit 15 (Transmission Error) of the words allocated in the CIO Area n+8/n+18 is set to ON. The wiring is faulty. There is an error in bits 0 to 14. The A transmission SDj/RDj error occurs. and COMj indicators are flashing, but the Unit or Board cannot perform communications or a communications error sometimes occurs. Data is received through CX-Protocol transmission line trace, but the protocol macros behave as if no data is received. The remote node sometimes returns no response to sent data. Response may be received by performing retries. 178 Bit 15 (Transmission Error) of the words allocated in the CIO Area n+8/n+18 is set to ON. There is an error in bits 0 to 14. The contents of the words allocated in the CIO Area n+5/n+15 (System Port Settings) do not match those of the remote node. --- --- The setting of the 2/4-wire switch for the RS-422A/485 port does not match the actual wiring (for the CS1W-SCB41 Board only). The wiring of adapters such as the NT-AL001-E is faulty. The Setup Area settings such as the baud rate and frame format differ from those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on. Because response from the remote node in halfduplex mode is received too fast, the data received from the time the data send processing was completed until the Send operation was completed is discarded. The transmission timing is too fast for the remote node to receive data. 8-3 Remedy Review the Setup Area settings. Review the remote node settings and the program (including the baud rate, frame format, and so on). Check the wiring. Turn ON the terminating resistances of the Board and the last node. Turn OFF the terminating resistances of other nodes. Review the Setup Area settings. Review the remote node settings and the program (including the baud rate, frame format, and so on). Use full-duplex mode. Set or increase the transmission wait time (time to await data transmission) in step units. Section Troubleshooting Serial communications mode Serial communications mode is set to protocol macro. Indicator display Status information, etc. The A transmission SDj/RDj error sometimes occurs. and COMj indicators are flashing, but the Unit or Board cannot perform communications or a communications error sometimes occurs. The RDY and ERC indicators are flashing (ERR/ ALM). The RDY indicator is lit and the ERC indicator is flashing (ERR/ ALM). Words allocated in the CIO Area Bit 15 (Transmission Error) of the words allocated in the CIO Area n+8/n+18 is set to ON. There is an error in bits 0 to 14. Cause The wiring is faulty. 8-3 Remedy Check the wiring. The RS-422A/485 port terminating resistance setting is incorrect. Turn ON the terminating resistance of the Board and the last node by using the terminating resisAdapters such as the tance switch. Turn OFF NT-AL001-E are incorrectly wired, or the termi- the terminating resisnating resistance setting tance of other nodes. is incorrect. A communications error Use shielded twisted frequently occurs due to pair cables. noise and so on. House the communications cables in a different duct from those for power lines and so on. --- Bit 00 (Protocol Data Error) of the words allocated in the CIO Area n+1 is set to ON. The protocol macro data SUM value is abnormal. --- Bits 00 to 03 (Port Status Error Code) of the words allocated in the CIO Area n+9/n+19 are set to a value other than 0 Hex. (An error has occurred.) An error has been detected in the protocol macros, making the operation impossible. Review the operating environment to prevent noise problems. Use CX-Protocol to transfer the correct protocol data. See page 181. 179 Section Troubleshooting 8-3 Note The following table shows the measures to correct the errors indicated by network communications end codes (A203 to A210). Network communications end code Error details Bits Bits 08 to 15 00 to 07 02 Hex 02 Hex There is no Board or Unit corresponding to the unit address. 04 Hex 01 Hex The specified service is not supported. Remedy Check whether a different Board/Unit or serial port (physical port) is specified in the PMCR(260) instruction C1 operand (communications port number). Check whether a different Board/Unit or serial port (physical port) is specified in the PMCR(260) instruction C1 operand (communications port number). Check whether the serial communications mode of the serial port specified in the C1 operand is protocol macro. If not, set the serial communications mode to protocol macro. Check whether the serial communications mode of the serial port specified in the C1 operand is protocol macro. If not, set the serial communications mode to protocol macro. 02 Hex 05 Hex The watchdog timer expires because no response is received from the remote node within the specified time. 11 Hex 06 Hex The specified send/receive sequence number does not exist. The send/receive sequence number specified in the PMCR(260) instruction C2 operand is unregistered. PMCR(260) instruction cannot be executed because protocol macro is currently being executed. An attempt is made to execute the PMCR(260) instruction while protocol macros are being executed. No registration table exists. The problem cause is one of the following: 22 Hex 24 Hex 01 Hex 01 Hex Use CX-Protocol to register the send/receive sequence number. Modify the ladder program so that bit 15 (Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 is set to a NC execution condition for the PMCR(260) instruction. • Protocol macro (send/receive sequence) data has not been registered. • Protocol macro (send/receive sequence) data is currently being registered or transferred. • Protocol macro (send/receive sequence) data contains a SUM value error. Use CX-Protocol to transfer the correct protocol macro (send/receive sequence) data. 180 Section Troubleshooting 8-3 Note The following table shows the measures to correct the errors indicated in bits 00 to 03 (Error Code) of words allocated in the CIO Area words n+9/n+19. Error code 0 Hex No display Normal --- --- 1 Hex No display Reserved --- --- 2 Hex No display Sequence number error The send/receive sequence number specified in the PMCR(260) instruction’s C2 operand is not registered. Correct the send/receive sequence number. The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit. For operand specification: Check the PMCR(260) instruction S and D operand specifications. There is a code that cannot be executed during protocol execution. Check the following items and correct the problem. 3 Hex 4 Hex Indicator Error details ERC: Flashing ERR/ALM : Flashing Data read/write range error ERC: Flashing ERR/ ALM: Flashing Protocol data syntax error Cause Remedy Use CX-Protocol to register the specified send/receive sequence number. For direct specification of link words: Use CX-Protocol to check the specified range. • Check whether the total specified number of link words in the area (O1, O2, I1, I2) exceeds 500. • The same area with link word specification is used by both ports 1 and 2. • A write instruction with constant specification is specified. • An EM Area read/write instruction is specified as an interrupt notification (for Boards only). • An interrupt notification is specified at the Unit (for Units only). • There are more than 30 write attributes set for one message. • The length of a send/receive message is set to 0 bytes. • The length of a send/receive message is longer than the maximum send/receive message bytes setting. • No messages are registered for matrix reception. • Both RTS/CTS flow control and Xon/Xoff flow control are set for the same transmission line. 181 Section Error Logs 8-4 8-4 Error Logs The error log function records the errors detected in the Serial Communications Board or Serial Communications Unit together with the time that the error occurred. 8-4-1 Error Log Table RAM Error Log Table For every error that occurs, one record is logged in the RAM error log table in the Board or Unit for up to 64 errors. EEPROM Error Log Table Records of errors that are particularly serious are logged in both the RAM error log table and the EEPROM error log table in the Board or Unit when they occur. The contents of errors logged in the EEPROM error log table remain even if the power to the Board or Unit is turned OFF or the Board or Unit is restarted. The contents of the EEPROM error log table is automatically read to the RAM error log table when the power is turned ON. One record is logged in the EEPROM error log table for each error that occurs for up to 32 errors max. 8-4-2 Error Log Specifications Item Specifications Record length 10 bytes per record Record configuration Error code: 2 bytes Details: 2 bytes Time: 6 bytes Data format Binary (time information is in BCD) Number of records RAM: 64 records max. EEPROM: 32 records max. Storage order Records are stored in order from the oldest to the most recent errors. When the number of errors recorded in the RAM error log table reaches 64 (or 32 records for the EEPROM error log table), the oldest records will be deleted to store the most recent errors. 8-4-3 Error Log Table Configuration 15 08 07 00 Bit Error code Details Minute Second Day Hour Year Record (oldest) Month Error code Details Minute Second Day Hour Year Month Record Error code Details Error Codes and Details 182 Minute Second Day Hour Year Month Record (newest) Refer to the list of error codes and details on page 183. Section Error Logs 8-4 Time of Error The time the error occurred is recorded including the year (rightmost two digits), month, day, hour, minute, and second in 1-byte BCD (binary coded decimal). Reading and Clearing Error Log Tables The error log table can be read or cleared using FINS commands sent to the Serial Communications Board or Serial Communications Unit. Refer to 8-4-6 Reading and Clearing Error Log Tables for details. Note The Serial Communications Board and Serial Communications Unit use the time information read from the CPU Unit. If the time cannot be read from the CPU Unit, the time of the error in the error log will be recorded as all zeros. For all CS1-series PCs, the time of the CPU Unit’s built-in clock must be set when the power is turned ON after the battery is mounted. If the built-in clock time is not set, the time recorded in the error log will be incorrect, and when the error log is read, the time will be irregular. 8-4-4 Error Codes and Details Error code 0001 Hex 0002 Hex 0006 Hex 000F Hex 0011 Hex 0012 Hex Details Error contents CPU Unit watchdog timer error CPU Unit service monitoring error Other CPU Unit errors CPU Unit initial processing error CPU Unit initial processing error CPU Unit memory error 0014 Hex Inner bus error 0108 Hex Send not possible because Unit is not detected 010B Hex Send not possible due to CPU Unit error 010D Hex Send not possible due to remote address setting error 010E Hex Send not possible because routing tables are not set properly First byte Always 00 Hex Yes Bit 11: The unit number is not included in the the registered I/O tables. Yes Other bits not used. Always 00 Hex Always 00 Hex Yes Not fixed Not fixed Yes 01 Hex: Read error 03 Hex: Routing tables No 02 Hex: Write error 05 Hex: CPU Bus Unit/Inner Board DM Area Always 00 Hex Yes Always 00 Hex Event Send/Receive Errors Send source network address y 80 Bit 15: OFF Bits 08 to 14: 00 Bits 00 to 07: Send source network address No No No Responses: Send destination network address t 80 Bit 15: Bits 08 to 14: Bits 00 to 07: 0117 Hex Internal reception buffer full Send destination Bit 15: Bits 08 to 14: Illegal packet discarded Bits 00 to 07: Parity error Framing error Overrun error FCS check error No Commands: Send source network address t 80 Bit 15: OFF Bits 08 to 14: Send source network address Bits 00 to 07: Send source node address Send not possible due to header setting error 011B Hex 011C Hex 011D Hex 011E Hex Yes Monitoring time (Unit: 1 ms) 0112 Hex 0118 Hex Second byte Always 00 Hex Stored in EEPROM 01 Hex: Port 1 02 Hex: Port 2 ON Send destination network address Send destination node address network address y 80 ON 00 Send destination network address Always 00 Hex No No No No No No No 183 Section Error Logs Error code Error contents Details First byte 021A Hex 0300 Hex 0301 Hex 0302 Hex Setting table logic error Parameter packet discarded Protocol macro operation error Always 00 Hex Second byte 03 Hex: Routing tables Stored in EEPROM No 05 Hex: CPU Bus Unit/Inner Board DM Area Same contents as event send/receive errors. No 01 Hex: Port 1 Protocol macro error code No Always 00 Hex No 02 Hex: Port 2 Illegal protocol packet discarded. 01 Hex: Port 1 0601 Hex Board/Unit error Check the operating environment. Yes 0602 Hex CPU Bus Unit/Inner Board memory error 01 Hex: Read error 06 Hex: Error log No 02 Hex: Write error 07 Hex: Protocol data 184 8-4 02 Hex: Port 2 Section Error Logs 8-4 8-4-5 Error Codes and Troubleshooting Error code Serial communications mode Troubleshooting 0001 Hex Replace the CPU Unit. Protocol macro Yes Host Link 1:N NT Link Yes Yes Loopback test Yes 0002 Hex Check the operating environment. Yes Yes Yes Yes 0006 Hex Check the unit number setting. Yes Yes Yes Yes Recreate the I/O tables. 000F Hex Check the operating environment. Yes Yes Yes Yes 0011 Hex Check the operating environment. Yes Yes Yes Yes 0012 Hex Check the relevant data. Yes Yes Yes Yes 0014 Hex Check the operating environment. Yes Yes Yes Yes 0108 Hex Check the unit number setting. Yes Yes Yes Yes 010B Hex Eliminate the cause of the error, referring to Yes the CPU Unit’s operation manual. Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes No No Yes Yes Yes Yes Yes Yes Yes Yes No Yes No No 010D Hex 010E Hex 0112 Hex 0117 Hex 0118 Hex 011B Hex If the error persists, replace the CPU Unit. Set the destination address in the routing tables. Set the destination address in the routing tables. Make sure to use the FINS command addresses correctly. Increase the number of retries or correct the system so that communications do not jam. Check whether there is a node sending irregular data. Correct the transmission method and baud rate settings. 011C Hex Check for noise interference. Correct the transmission method and baud rate settings. No Yes No No 011D Hex Check for noise interference. Correct the transmission method and baud rate settings. No Yes No No 011E Hex Check for noise interference. Correct the transmission method and baud rate settings. No Yes No No Check for noise interference. Check whether the FCS calculation method is correct. 021A Hex Reset the relevant table. Yes Yes Yes Yes 0300 Hex Conduct a loopback test, and eliminate the Yes cause of the error. Eliminate the cause of the error, referring to Yes the processing of protocol macro error codes on page 181. Yes Yes Yes No No No 0302 Hex A new command is received during command processing. Correct the applications at the host computer. No Yes No No 0601 Hex Check the operating environment. Yes Yes Yes Yes 0602 Hex Depending on the error details, delete the Yes error log and transfer protocol macro data. If the error persists, replace the Board/Unit. Yes Yes Yes 0301 Hex 185 Section Error Logs 8-4 8-4-6 Reading and Clearing Error Log Tables The error log table can be read or cleared by sending FINS commands to the Serial Communications Board or Serial Communications Unit. Refer to the CSseries Communications Command Reference Manual (W342) for details on FINS commands. Set the send destination unit address for the FINS commands to the unit number of the Serial Communications Board or Serial Communications Unit, as follows: Serial Communications Board: E1 hexadecimal Serial Communications Unit: 10 hexadecimal + unit number 8-4-7 CONTROLLER DATA READ: 05 01 Reads the following data for the Serial Communications Board or Serial Communications Unit. • Serial Communications Board or Unit Model • Serial Communications Board or Unit Version Command Format 05 01 Command code Response Format 05 01 Command code End code 20 bytes 20 bytes Board/Unit Model Board/Unit Version Parameters Model, Version (Response) The Serial Communications Board or Serial Communications Unit model and version are specified in the response each as ASCII data up to 20 bytes max. If the data is less than 20 bytes, the remaining bytes will be expressed as 20 hexadecimal (space). Board or Unit Serial Communications Unit (two RS-232C ports) Serial Communications Board (two RS-232C ports) Serial Communications Board (one RS-232C and one RS-422A/485 port) Model CS1W-SCU21 CS1W-SCB21 CS1W-SCB41 Version: “V1.00V1.00V1.00V1.00” Trace function version Macro function version Board or Unit version Communications control version 186 Section Error Logs 8-4 8-4-8 ERROR LOG READ: 21 02 This command reads the Board or Unit’s error log. Command Format 21 02 Command code Beginning record no. No. of records Response Format 21 02 Command code End code Max. no. of No. of stored records stored records No. of records 10 bytes 10 bytes Error log data Error log data Parameters Beginning record number (command) Specify the first record to be read as 2-byte (4-digit) hexadecimal. The first record number is 0000 Hex and the setting range is 0000 to 003F Hex (0 to 63 decimal). Number of records (command, response) Specify the number of records to read. The setting range is 0001 to 0040 Hex (1 to 64 decimal). The number of read records will be returned with the response. If there is no error log, the response will be 0000. Maximum number of stored records (response) Indicates the maximum number of records that can be stored. The number is always 0040 Hex (64 records) for Serial Communications Boards and Units. Number of stored records (response) Indicates the number of records recorded at the time the command is executed. The number of stored records will be returned with the response within the range of 0000 to 0040 Hex (0 to 64 decimal). When the FA command for Host Link communications is used to read the error log, set the number of stored records to between 0001 and 0035 Hex (1 to 53 decimal). Higher numbers cannot be set because they would cause the response to exceed the maximum Host Link frame length. If a larger number is set and the setting agrees with the actual number of stored records, 110B Hex will be returned as the end code followed by all the records that can be returned without exceeding the maximum frame length. Error log data (response) The specified number of error log records will be returned in sequence starting from the beginning record number. The total number of bytes for the error log data required is calculated as follows: No. of records x 10 bytes The configuration of each error log record is returned in 10 bytes, as follows: 1st byte 07 10th byte 01 Error code Details Minute Day Hour Year Month Second Error Code and Details Indicates the error contents of the error recorded. Refer to 8-4-4 Error Codes and Details. 187 Section Cleaning and Inspection 8-5 Minute, Second, Day, Hour, Year, Month Records the time the error occurred. Comments If the error log does not contain the specified number of records, the records up to the last recorded stored at the time the command was executed will be returned, and a normal response will be returned. The number of records actually read will be returned as the number of stored records. If the beginning record is specified higher than the current number of records in the error log, an end code of 1103 Hex will be returned. If the beginning record number is specified as 0000, the response will be completed normally, even if no error log is recorded. If the number of records is set to 0000, the end code will be returned as 110C Hex. 8-4-9 ERROR LOG CLEAR: 21 023 This command clears all stored error log records to 0. Command Format 21 03 Command code Response Format 21 03 Command code Comments 8-5 End code The ERROR LOG CLEAR: 21 03 command clears the error log records that are stored in the RAM error log table and the EEPROM error log table. Cleaning and Inspection Use the cleaning and inspection methods described here for daily maintenance of the devices. 8-5-1 Cleaning To keep the Serial Communications Board in optimum condition, regularly clean the Board or Unit, as follows: • Wipe the surface of the Board or Unit daily with a soft, dry cloth. • If any dirt cannot be removed with a dry cloth, moisten the cloth with a mild detergent diluted to 2%, and squeeze out any excess moisture before wiping the Board or Unit. • Do not adhere materials, such as gum, vinyl, or tape to the Board or Unit for long periods of time. Doing so may cause scratches on the device. Remove any adhered materials when cleaning the Board or Unit. Note Never use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths. 8-5-2 Inspection To keep the Board or Unit in optimum condition, regular inspections must be performed. Normally, inspect the devices once every six months or every year. Inspect the devices at more regular intervals when they are being used in environments subject to high temperatures, high humidity, or high dust levels. 188 Section Replacement Precautions Materials for Inspection 8-6 Prepare the following materials before performing any inspections. Materials Required Daily For daily inspection, a Phillips screwdriver, flat-blade screwdriver, tester (or digital voltmeter), industrial strength alcohol, and all-cotton cloth are required. Materials Required Occasionally For some inspections, a synchroscope, a pen oscilloscope, a temperature gage, and a hydroscope will be required. Inspection Items Inspect the following items to check whether the Board or Unit is operating within the specified criterion. If the Board or Unit is not within the criterion, improve the ambient operating environment and readjust the device. Item Details Operating Check the ambient temperature environment and the temperature of the control panel. Check the ambient humidify and the humidity of the control panel. Check for accumulated dust. Installation Check that the Board or Unit is mounted securely. Check for loose screws on the communications cables. Check for damaged communications cables. 8-6 Criterion 0 to 55°C Inspection materials Temperature gage 10% to 90% RH Hydroscope (no condensation or icing) No dust Visual inspection Board or Unit --must be mounted securely. Screws must be Phillips securely screwdriver tightened. Cables should be fully intact. Visual inspection Replacement Precautions A malfunction of the Serial Communications Board or Serial Communications Unit may affect the operation of remote communications devices, so be sure to perform repairs or replace the faulty Board or Unit promptly. Make sure a spare Serial Communications Board or Unit is available to replace a faulty one, so that functionality can be restored without delay. 8-6-1 Precautions when Replacing Board or Unit Observe the following precautions when replacing the Serial Communications Board or Serial Communications Unit. • Always turn OFF the power to the PC before replacing the Board or Unit. • Be sure to check that the Board or Unit replacing the faulty one is not defective. • If the defective Board or Unit is to be dispatched to the manufacturer for repair, be sure to include documentation stating the nature of the fault in as much detail as possible, and send to your nearest OMRON branch or sales office, listed at the back of this manual. If the contacts are defective, clean the contacts with a clean all-cotton cloth moistened with industrial-strength alcohol. Remove any cloth particles before mounting the Board or Unit. Note Turn OFF the power to all serial external devices when replacing the Board or Unit to prevent malfunctions. 189 Section Replacement Precautions 8-6 8-6-2 Settings after Replacing Board or Unit After replacing the Serial Communications Board or Serial Communications Unit, make sure that wiring and settings, such as hardware switch settings, the Unit/Board Setup, and protocol macro data are the same as the Board or Unit that was replaced. Note 1. If the CPU Unit is to be replaced, transfer to the replacement CPU Unit the contents of the Holding Areas and DM Area required for operating the Unit before starting operation. If the relationship between the DM Area and Holding Area and the program is not maintained, unexpected malfunctions may result. 2. The System Setup of the Serial Communications Board or Unit is saved in the DM Area of the CPU Unit. If the CPU Unit is to be replaced, either transfer the System Setup data to the CX-Programmer before replacing the CPU Unit or reset the System Setup. 8-6-3 Replacing the Board or Unit Standard System Protocols, Host Link Communications, or 1:N NT Links 1, 2, 3... 1. Turn OFF the power to the PC to which the Serial Communications Board or Unit to be replaced is mounted, and to all serially connected external devices. 2. Disconnect the communications cables connected to the Serial Communications Board or Unit to be replaced, and also remove the Board or Unit. 3. Set the hardware switches of the replacement Board or Unit to the same settings of the Board or Unit being replaced before mounting, as follows: • CS1W-SCB21: No setting switches. • CS1W-SCB41: Terminating resistance switch and 2/4-wire switch. • CS1W-SCU21: Unit number switch. 4. Turn ON the power of the PC to which the replacement Serial Communications Board or Unit is mounted, and to all serially connected external devices, and start operating the system. 5. Check from the indicators and status display that the system is operating normally. Protocol Macros Designed with CX-Protocol 1, 2, 3... 1. Connect Programming Console or CX-Protocol to the PC to which the replacement Serial Communications Board or Unit is mounted, and switch to PROGRAM mode. 2. Save the protocol macro data using the CX-Protocol. Refer to the CX-Protocol Operation Manual (W344) for details. 3. Turn OFF the power to the PC to which the Serial Communications Board or Unit to be replaced is mounted, and to all serially connected external devices. 4. Disconnect the communications cables connected to the Serial Communications Board or Unit to be replaced, and also remove the Board or Unit. 5. Set the hardware switches of the replacement Board or Unit to the same settings of the Board or Unit being replaced before mounting, as follows: • CS1W-SCB21: No setting switches. • CS1W-SCB41: Terminating resistance switch and 2/4-wire switch. • CS1W-SCU21: Unit number switch. 6. Turn ON the power of the PC to which the replacement Serial Communications Board or Unit is mounted, and to all serially connected external devices, and start operating the system. 190 Replacement Precautions Section 8-6 7. Switch the CPU Unit to PROGRAM mode, and using the CX-Protocol, transfer the protocol macro data to the Board or Unit. 8. Switch the CPU Unit to MONITOR mode, and start operating the system. 9. Check from the indicators and status display that the system is operating normally. Note 1. The protocol macro data for the Board or Unit is stored in the flash memory of the Board or Unit. 2. When protocol macro data designed with the CX-Protocol is used, a backup of the protocol macro data created from the CX-Protocol must be transferred to the Board or Unit after replacing. 3. The System Setup of the Serial Communications Board or Unit is allocated to the DM Area saved in the battery backup of the CPU Unit, and if the exclusively designed macro data is not used, the System Setup can be used as before, simply by setting the hardware. 191 Appendix A Introduction Appendices B the N provide information on the standard system protocols provided with the CX-Protocol, the Serial Communications Boards, and the Serial Communications Units. Refer to 5-4 Using Protocol Macros for details on using PMCR(260). Using Standard System Protocols Standard system protocols can be executed merely by specifying the sequences number to be executed in the second operand of PMCR(260) and settings the data described in the appendices in the proper format starting at the word specified with the third operand of PMCR(260). The data received as a response to executing the sequence will be automatically stored starting at the word specified with the fourth operand of PMCR(260). Procedure 1, 2, 3... 1. Set the sequence number as a hexadecimal value in the second operand of PMCR(260). 2. Specify the address of the first word containing the data required for the sequence as the third operand (S: First word of send data) of PMCR(260). 3. Specify the address of the first word where respond data is to be stored as the fourth operand (D: First receive data storage word) of PMCR(260). Unless there is a reason to specify otherwise, set 0000 Hex in D at the initial value. Example The following data would be used to execute sequence number 600 in the CompoWay/F Master Protocol for a transmission with ASCII conversion. PMCR(260) Send/receive sequence number 600 (0258 Hex) #0258 S D S: Send Data Word Allocation (3rd Operand) First word of send data +0 Number of send data words +1 (Undefined) Node number +2 (Undefined) SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data S+0 Number of send data words (4 digits Hex) 0005 to 00FA Hex (5 to 250 decimal) S+1 (Undefined) Node No. (2 digits 00 to 99 BCD) S+2 MRC (2 digits Hex) SRC (2 digits Hex) S+3 Number of send bytes (4 digits Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 0492 S+4 on Send data (4-digit Hex) The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. Set the command code for the required service 193 Appendix A Introduction D: Receive Data Word Allocation (4th Operand) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data D+0 Number of receive data words (4 digits Hex) 0003 to 00FA Hex (3 to 250 decimal) D+1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. D+2 on Receive data (4-digit Hex) The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here. Standard System Protocols The following 13 standard system protocols are provided with the CX-Protocol, Serial Communications Boards, and Serial Communications Unit. Protocol name CompoWay/F Master E5jK Digital Controller Read E5jK Digital Controller Write E5ZE Temperature Controller Read Function Protocol for sending CompoWay/F commands as a Master to OMRON CompoWay/F slave components and receiving responses. Protocol for controlling an E5jK Digital Controller via the Communications Board. Procedures for reading the MV the operating parameter settings Protocol for controlling an E5jK Digital Controller via the Communications Board. Procedures for writing set points and operating parameters. Protocol for controlling an E5ZE Temperature Controller via the Communications Board. Procedures for reading measured temperature and operating parameter settings. E5ZE Temperature Controller Write E5jJ Temperature Controller Protocol for controlling an E5ZE Temperature Controller via the Communications Board. Procedures for writing control temperatures and operating parameters. Protocol for controlling a E5jJ Temperature Controller via the Communications Board. Procedures for writing set points, reading output amounts, and reading/writing operating parameters. ES100j Controller Protocol for controlling an ES100j Controller via the Communications Board. Procedures for writing adjustment parameters, reading operation amounts, and writing/reading operating parameters. Digital Panel Meter Protocol for controlling a Digital Panel Meter via the Communications Board. Procedures for writing comparison values and reading display values are set. Protocol for controlling a Bar Code Reader via the Communications Board. Procedures for controlling the Bar Code Reader in remote mode, reading the data that has been read by the Bar Code Reader, and reading/writing operating parameters. V500/V520 Bar Code Reader 3Z4L Laser Micrometer Protocol for controlling a Laser Micrometer via the Communications Board. Procedures for controlling the Laser Micrometer in remote mode, reading measured data, and writing/reading operating parameters. F200/F300/F350 Visual Inspection Systems Protocol for controlling a Visual Inspection System via the Communications Board. Procedures for controlling the Visual Inspection System in remote mode, reading measured values, and writing/reading operating parameters. V600/V620 ID Controllers Protocol for controlling an ID Controller via the Communications Board. Procedures for performing Read/Write operations of the ID Controller and writing/reading operating parameters. Hayes modem AT commands Protocol for controlling a Hayes modem (AT commands) via the Communications Board. Procedures for initialization of the modem, dialing, data transmission, switching to escape mode, and disconnecting the line. 194 Appendix B CompoWay/F Master Protocol The CompoWay/F Master Protocol is used to send CompoWay/F commands with the CS1-series PC serving as the host (master). CompoWay/F CompoWay/F is a protocol used by many OMRON components for serial communications. A host computer of a PC can function as a host (master) to send CompoWay/F commands (message frames) to OMRON components, which function as slaves. The components will return responses to these commands. Using CompoWay/F commands, the host can read/write data, settings, and operating status to control the operation of the components. CompoWay/F has the following features. • The same message frame format is used, eliminating the need for special protocols for each component. The same commands can thus be used for serial communications with all CompoWay/F components. • The CompoWay/F protocol conforms to OMRON’s standard FINS command protocol, providing compatibility with other networks and more flexible expansions in the future. The CompoWay/F Master Protocol is provided as a standard system protocol to enable the CS1-series PC to executed read/write sequences for CompoWay/F commands. System Configuration for Standard System Protocol RS-232C Connections CS1-series PC: Host CompoWay/F response RS-232C OMRON CompoWay/F component: Slave CompoWay/F command RS-422A/486 Connections CS1-series PC: Host CompoWay/F response RS-422A/485 CompoWay/F command OMRON CompoWay/F components: Slaves 195 Appendix B CompoWay/F Master Protocol Communications Specifications Item Specification Transmission path connections Communications Multipoint Synchronization Start-stop Baud rate 1,200/2,400/4,800/9,600/19,200/38,400 bps Default: 9,600 bps ASCII Transmitted code Data length RS-232C, RS-422A/485, 4-wire half-duplex, 2-wire half-duplex 7 bits or 8 bits (Default: 7 bits) Note: A 7-bit code is used with 0 added to the beginning. 1 bit or 2 bits (Default: 2 bits) Stop bits Error detection Horizontal parity (none, even, or odd) (Default: Even) BCC (block check character) *1: Start-stop Sync Data Configuration for Protocol Macros LRC, 1 byte, equivalent to binary Transmission Procedure The PC or host computer serving as the master sends a command and the component serving as the slave returns a response for the command message contained in the command. One response message is returned for each command message. The movement of command and response messages is shown below. Master (PC or host computer) Command message Slave (component) Response message Command and Response Formats Note In the following diagrams “Hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters. Command Format Node No. Subaddress ”00” 1 byte Command 2 bytes 2 bytes 1 byte Node No. Subaddress End code Text Data ”0” 1 byte 1 byte 1 byte 1 byte Response Format 1 byte 2 bytes ”00” ”00” 2 bytes 2 bytes Response Text Data (See note.) Note 1. Data is not saved in the response if there is a command frame error (i.e., if the end code is not 00 or 0F). 2. Other values are possible for the subaddress and SID. 196 Appendix B CompoWay/F Master Protocol Command Frame Contents Item Meaning STX A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte. Node number The node number identifies the source of the command frame. Specify “XX” to broadcast a transmission. There will be no response made to a broadcast. Subaddress Set “00” for most components. Other values must be set for special components. SID Set “0” for most components. Other values must be set for special components. Command and text The command and required text are placed here. Refer to the command codes and text for individual sequences. MRC and SRC The command code specifies the service being used. Refer to the command codes and text for individual sequences. ETX A code, 03 Hex, indicating the end of text. BCC The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX. Response Frame Contents Item Meaning STX A code, 02 Hex, indicating the beginning of a communications frame (text). This code must always be set as the first byte. Node number The node number identifies the source of the command frame. “XX” is specified to broadcast a transmission. There will be no response made to a broadcast. Subaddress “00” for most components. Other values must be set for special components. SID “0” for most components. Other values must be set for special components. End code (See note.) The results of executing the command frame. Note: The response code (MRES and SRES) indicates the results for the command code; the end code indicates the results for the command frame. These are not the same. Response and text MRES and SRES The response and requested text are placed here. Refer to the response and text for individual sequences. The response code specifies the results of processing the service requested by the command code. Refer to the response codes and text for individual sequences. ETX A code, 03 Hex, indicating the end of text. BCC The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX. 197 Appendix B CompoWay/F Master Protocol Note The end codes are described in the following table. End code Name Meaning “00” Normal end The command frame was processed normally without any of the following errors. “0F” Command error The specified command could not be executed. Refer to the response code for more information. “10” Parity error A parity error was detected for one of the characters that was received. “11” Framing error A framing error was detected for one of the characters that was received. “12” Overrun error A overrun error was detected for one of the characters that was received. “13” BCC error The BCC for the receive frame was incorrect. “14” Format error An illegal command or illegal character was received in the command and text (characters other than ASCII 0 to 9 or A to F). “16” Subaddress error The receive frame contained an illegal subaddress. “18” Frame length error The receive frame was too long. Example The command and response frames for a K3Nj-series Intelligent Signal Processor are shown below. Command Frame Node No. Subaddress Command Text SID Data Command code Command Data contents VARIABLE AREA READ Command code “01” “01” Data contents Variable type Address VARIABLE AREA WRITE “01” “02” Variable type Address PARAMETER AREA READ “02” “01” Address PARAMETER AREA WRITE “02” “02” Parameter type Parameter type No. of elements “00” No. of elements No. of elements Address No. of elements PROCESSOR STATUS READ CONTROLLER STATUS READ ECHOBACK TEST “05” “06” “08” “03” “01” “01” Text data OPERATION COMMAND “30” “05” Command code “00” Write data Write data Response Format Node No. Subaddress End code Response Text Data Command code 198 Response code Appendix B CompoWay/F Master Protocol Example: VARIABLE AREA READ The following command and text are used to read the present value, maximum value, minimum value, and status of the Intelligent Signal Processor. Command and Text Variable type 2 bytes 1, 2, 3... 2 bytes No. of elements First read address 2 bytes 4 bytes 4 bytes 1. Variable Type Variable type “C0” Contents Present value, maximum value, minimum value, status , and comparison value 2. First Read Address Specify the address of the data to be read in 4 digits Hex. 3. Number of Elements: 4 Digits Hex Number of elements “0001” Process Read the data and end normally. Note If “0000” is specified, nothing will be read and a normal end will be returned. A parameter error will occur for any settings other than “0000” and “0001.” Response Text Response code 2 bytes 2 bytes 1, 2, 3... 4 bytes Read data 8 bytes 1. Response Code: MRES, SRES Response code Meaning “0000” Normal end “1001” Command too long “1002” Command too short “1100” Parameter error “1101” Area type error “1103” First address range error “2203” Operating error 2. Read Data The specified data is returned in 8 digits of hexadecimal data. 199 Appendix B CompoWay/F Master Protocol CompoWay/F Master Protocol Sequences The CompoWay/F Master Protocol provides six communications sequences that can be used for the following: • Converting to ASCII data or not converting to ASCII data • Sending to a specified Unit or broadcasting • Specifying from the command code or specifying from the subaddress and SID. Structure of the Protocol The following table shows the structure of the CompoWay/F Master Protocol. Sequence No. Communications sequence name Function 600 (0258) Send with ASCII conversion, with response Converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word. 601 (0259) Broadcast with ASCII conversion, no response Send with no conversion and with response Ladder interface Send word allocation Yes Receive word allocation Yes A broadcast version of sequence No. 600. No responses are received. Sends specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. This is the same as sequence No. 600 without data conversion and can be used when conversion is not required. Yes No Yes Yes Broadcast with no conversion and no response 604 (025C) General-purpose send with no conversion and with response A broadcast version of sequence No. 602. No responses are received. Sends specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. This sequence can be used whenever it is necessary to specify the subaddress or SID. Yes No Yes Yes 605 (025D) General-purpose broadcast with no conversion and no response A broadcast version of sequence No. 604. No responses are received. Yes No 602 (025A) 603 (025B) Note The hexadecimal equivalents of sequences numbers are given in parentheses. Sequence No. 600 can be used for the normal CompoWay/F Master function (ASCII conversion, specification from command code). Refer to the communications specifications for the OMRON CompoWay/F component to which the command is being sent and set the command code and required data starting at the words specified for the 3rd operand of PMCR(260). The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is described next. 200 Appendix B CompoWay/F Master Protocol CompoWay/F Message Frames and PMCR(260) Operands The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is shown below, using communications sequence No. 600 as an example. Command Frame Node No. Variable type Subaddress First read address Command No. of elements Send data PMCR(260) Instruction Send/receive sequence number 600 (0258 Hex) S S+1 Number of send data words (Undefined) Node number S+2 S+3 Number of send bytes S+4 Send data S+5 S+6 Response Frame Node No. Subaddress End code Response code Response code Receive data Read data Receive data PMCR(260) Instruction D D+1 D+2 Number of receive data words Response code Receive data D+3 Send with ASCII Conversion, with Response: (Sequence No. 600 (Hex 0258)) This sequence converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word. 201 Appendix B CompoWay/F Master Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 MRC SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 to 00FA Hex (5 to 250 decimal) +1 (Undefined) Node No. (2 digits 00 to 99 BCD) +2 MRC (2 digits Hex) SRC (2 digits Hex) +3 Number of send bytes (4 digits Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 03D8 Hex (0 to 984 decimal) +4 on Send data (4-digit Hex) The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. Set the command code for the required service Note 1. Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. 2. When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Send data words Send frame 1 2 3 4 “56” “78” “12” “34” 5 6 7 8 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 to 00FA Hex (3 to 250 decimal) +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data (4-digit Hex) The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here. Note When ASCII data is converted to hexadecimal data, data is stored starting from the receive data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Receive frame “01” “23” “45” Receive data words “67” 4 5 6 7 0 1 2 3 202 Appendix B CompoWay/F Master Protocol Example: The following example illustrates reading the present value from a K3Nj-series Intelligent Signal Processor. CS1-series PC CompoWay/F response Read data = present value Intelligent Signal Processor K3Nj-jjjj-FLK1/2/3/4/5/6 CompoWay/F command VARIABLE AREA READ Command code: 01 01 First read address Sequence No. 600 (Send with ASCII Conversion, with Response) is used. The specified data beginning with the command code is converted ASCII and sent to the Intelligent Signal Processor with the specified node number. The response is converted to hexadecimal and stored starting at the specified word. The command frame for reading the present value for a K3Nj-jjjj-FLK1/2/3/4/5/6 Intelligent Signal Processor (command code 01 01) is shown below. The following data is specified in the operands for PMCR(260). • Rightmost byte of S+1: Node number (2 digits BCD) • S+2: Command code: MRC + SRC = “0101” • S+4 on: Send data = Variable type + first read address + 00 + number of elements. STX Node No. (02Hex) (×101) (×101) Subaddress 00 Command code SID MRC 0 01 SRC 01 Send data ETX Variable type First read address (Note) Always 00 No. of elements C0 0000 00 0001 BCC (03Hex) Data in shaded portions is specified in the PMCR(260) instruction. Note A first read address of 0000 specifies the present value. An address of 0001 specifies the maximum value; 0002, the minimum value; and 0003, the status. The response frame is shown below. The response code and receive data are stored according to the operands for PMCR(260) as follows: • D+1: Response code • D+2 and on: Receive data STX Node No. Subaddress End code Command code MRC (02 Hex) (×101) (×101) 01 Response code Receive data Note 1 Read data (Note 2) SRC 01 00 00 0000 ETX BCC (03 Hex) Data in shaded portions is stored at the location specified by the operand in the PMCR(260) instruction. Note 1. Response Codes Response code Meaning “0000” Normal end “1001” Command too long “1002” Command too short “1100” Parameter error “1101” Area type error “1103” First address range error “2203” Operating error 2. The read data is returned as 4-digit hexadecimal as follows: F0019999 to 00099999 Hex. 203 Appendix B CompoWay/F Master Protocol The 3rd and 4th operands of the PMCR(260) instruction are specified as follows. Send Data Word Allocation (3rd Operand of PMCR(260)) Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 Hex +1 (Undefined) Node No. (2 digits 0000 Hex BCD) +2 MRC (2 digits Hex) SRC (2 digits Hex) +3 Number of send bytes (4 digits BCD) 000C Hex +4 Send data (12 digits Hex) C000 Hex 0101 Hex +5 0000 Hex +6 0001 Hex Receive Data Word Allocation (4th Operand of PMCR(260)) Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) EX is stored at reception (0004 Hex) +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. The normal end response code is 0000. Receive data (8 digits Hex) +2 The 4 bytes of read data. +3 Broadcast with ASCII Conversion, No Response (Sequence No. 601 (Hex 0259)) This sequence converts the specified data beginning with the command code to ASCII and broadcasts it. No responses are received. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 MRC +2 SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 to 00FA Hex (5 to 250 decimal) +1 (Undefined) --- +2 MRC (2 digits Hex) +3 Number of send bytes (4 digits Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 03D8 Hex (0 to 984 decimal) +4 on Send data (4-digit Hex) The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent. SRC (2 digits Hex) Set the command code for the required service Note 1. Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. 204 Appendix B CompoWay/F Master Protocol 2. When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units. Send data words Send frame 1 2 3 4 “56” “78” “12” “34” 5 6 7 8 Receive Data Word Allocation (4th Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) Send with No Conversion and with Response (Sequence No. 602 (Hex 025A)) This sequence sends the specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 MRC SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) +1 (Undefined) Node No. (2 digits 00 to 99 BCD) +2 MRC (2 digits Hex) SRC (2 digits Hex) +3 Number of send bytes (4 digits Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 01EC Hex (0 to 492 decimal) +4 on Send data The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent. +0 +1 +2 +3 +4 +5 0005 to 00FA Hex (5 to 250 decimal) Set the command code for the required service +6 etc. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 to 00FA Hex (3 to 250 decimal) +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data (Hex) The data from just after the response code until just before the ETX is stored here without conversion. +0 +1 +2 +3 +4 +5 +6 etc. 205 Appendix B CompoWay/F Master Protocol Broadcast with No Conversion and No Response (Sequence No. 603 (Hex 025B)) This sequence broadcasts the specified data beginning with the command code No responses are received and no conversions are performed on the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 MRC +2 SRC +3 Number of send bytes +4 Send data Offset Contents (data format) Number of send data words (4 digits Hex) 0005 to 00FA Hex (5 to 250 decimal) +1 (Undefined) --- +2 MRC (2 digits Hex) +3 Number of send bytes (4 digits Hex) Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 01EC Hex (0 to 492 decimal) +4 on Send data The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent. SRC (2 digits Hex) +0 +1 +2 +3 +4 +5 +6 etc. Receive Data Word Allocation (4th Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) 206 Data +0 Set the command code for the required service Appendix B CompoWay/F Master Protocol General-purpose Send with No Conversion and with Response (Sequence No. 604 (Hex 025C)) This sequence sends the specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Node No. +2 (Undefined) Subaddress +3 (Undefined) SID +4 Number of send bytes +5 Send data Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) +1 Always 00 Hex Node No. (2 digits 00 to 99 BCD) +2 MRC (2 digits Hex) Subaddress (2 digits Hex) Specify the subaddress of the device being communicated with. +3 Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries). +4 Number of send bytes (4 digits Hex) Number of data bytes from the MCR until the byte just before the ETX. 0000 to 01EA Hex (0 to 490 decimal) +5 on Send data The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent. +0 +1 +2 +3 +4 +5 0006 to 00FA Hex (6 to 250 decimal) +6 etc. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Response code +2 Response data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 to 00FA Hex (3 to 250 decimal) +1 Response code (4 digits Hex) The response code will be stored in hexadecimal form. +2 on Receive data The data from just after the response code until just before the ETX is stored here without conversion. +0 +1 +2 +3 +4 +5 +6 etc. 207 Appendix B CompoWay/F Master Protocol General-purpose Broadcast with No Conversion and No Response (Sequence No. 605 (Hex 025D)) This sequence broadcasts the specified data beginning with the subaddress and SID. No responses are received and no conversions are performed on the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 +2 (Undefined) Subaddress +3 (Undefined) SID +4 Number of send bytes +5 Send data Offset Contents (data format) Number of send data words (4 digits Hex) 0006 to 00FA Hex (6 to 250 decimal) +1 Always 0000 Hex --- +2 MRC (2 digits Hex) Subaddress (2 digits Hex) Specify the subaddress of the device being communicated with. +3 Always 00 Hex SID (1 digit Hex) Set the service ID of the required service (e.g., retries). +4 Number of send bytes (4 digits Hex) Number of data bytes from the MCR until the byte just before the ETX. 0000 to 01EA Hex (0 to 490 decimal) +5 on Send data The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent. +0 +1 +2 +3 +4 +5 +6 etc. Receive Data Word Allocation (4th Operand of PMCR(260)) None. (Specify a dummy value for the operand, such as #0000.) 208 Data +0 Appendix B CompoWay/F Master Protocol Connections Connection methods between a Serial Communications Board or Unit and the K3Nj-series Intelligent Signal Processor are shown below. RS-232C • RS-232C connections are one-to-one. • The max. cable length is 15 m. Use an RS-232C optical interface (Z3RN) when extending the transmission line beyond 15 m. • Use shielded, twisted-pair cable. Intelligent Signal Processor Serial Communications Unit/Board RS-232C RS-232C Abbrevi- Pin ation No. Pin No. Abbreviation FG 1 1 FG SG 9 7 SG SD 2 2 SD RD 3 3 RD RTS 4 4 RTS CTS 5 5 CTS DSR 7 6 DSR DTR 8 20 DTR Shield Serial Communications Unit/Board Abbreviation Pin No. Pin No. SG SD 9 2 3 4 5 7 8 5 3 2 RD RTS CTS DSR DTR FG 1/ Shell TX RX K3Nj-jjjj-FLK1 Intelligent Signal Processor RS-232C RS-232C MAX232C or equivalent 7 8 6 4 MAX232C or equivalent Abbreviation SG SD RD RTS CTS DSR TX RX DTR Shield K3Nj-jjjj-FLK4 209 Appendix B CompoWay/F Master Protocol RS-422 4-wire Connections • RS-422 connections can be one-to-one, or one-to-N when a 3G2A9-AL001 Link Adapter is used. A maximum of 32 Serial Communications Boards and Unit can be connected in one-to-N systems. • The total cable length can be 500 m max. • Use shielded, twisted-pair cable. • Be sure to turn ON the terminating resistance switches at the device at each end of the transmission line. Serial Communications Board Intelligent Signal Processor RS-422 Abbreviation Pin No. Shell SN751177N or equivalent Terminal 220 Ω block switch Abbreviation 6 8 1 2 *1: Set the 2-/4-wire switch to the 4-wire setting. *2: Turn ON the terminating resistance switch. 220 Ω Shield The terminator (220 Ω) is set with the terminal block switch. RS-485 2-wire Connections • RS-485 connections can be one-to-one or one-to-N. A maximum of 32 Serial Communications Units/Boards can be connected in one-to-N systems. • The total cable length can be 500 m max. • Use shielded, twisted-pair cable. • Be sure to turn ON the terminator switches only in the devices at each end of the transmission line. Intelligent Signal Processor Turn OFF all terminal block switches except at the end-station. RS-485 Abbreviation Termi- Abbrevinal ation Shell 220 Ω SN751177N or equivalent Terminal block switch 1 2 + Shield *1: Set the 2-/4-wire switch to the 2-wire setting. Intelligent Signal Processor end-station *2: Turn ON the terminating resistance switch. Termi- Abbrevinal ation Terminal 220 Ω block switch ON + Terminal block switch ON at the end station. Shield Note SYSMAC BUS Wired Remote I/O devices cannot be connected. 210 Appendix C E5jK Digital Controller Read Protocol The E5jK Digital Controller Read Protocol reads and controls various parameters in remote mode for the Controller connected to the Serial Communications Unit/Board via RS-232C or RS-485 cable. Structure of the Protocol The following table shows the structure of the E5jK Digital Controller Read Protocol. Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation Yes 000 (0000) Read process value Reads the process value. 001 (0001) Read set point during SP ramp Yes Yes 002 (0002) Read MV Reads the set point during SP ramp. Reads the MV (heating, cooling). Yes Yes 003 (0003) Read set point Reads the set point. Yes Yes 004 (0004) Read alarm value Reads alarm value 1, 2. Yes Yes 005 (0005) Read proportional band, integral time, and derivative time Reads the proportional band, integral (reset) time, and derivative (rate) time Yes Yes 006 (0006) Read cooling coefficient Reads the cooling coefficient. Yes Yes 007 (0007) Read dead band Reads the dead band. Yes Yes 008 (0008) Read manual reset value Reads the manual reset value. Yes Yes 009 (0009) Read hysteresis Yes Yes 010 (000A) Read control period Reads the hysteresis (heating, cooling). Reads the control period (heating, cooling). Reads the SP ramp time unit and SP ramp set value. Reads the LBA detection time. Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 011 (000B) Read SP ramp time unit and set value 012 (000C) Read LBA detection time 013 (000D) Read MV at stop and PV error 014 (000E) Read MV limits Reads the MV at stop and the MV at PV error. Reads the MV limits. 015 (000F) Read input digital filter Reads the input digital filter. Yes Yes 016 (0010) Read alarm hysteresis Reads the alarm 1, 2 hysteresis. Yes Yes 017 (0011) Read input shifts Reads the input shift limits. Yes Yes 018 (0012) Read level 0 parameters Reads parameters in level 0. Yes Yes 019 (0013) Read level 1 parameters 1 Reads parameters in level 1. Yes Yes 020 (0014) Read level 1 parameters 2 Reads parameters in level 1. Yes Yes 021 (0015) Read level 2 parameters 1 Reads parameters in level 2. Yes Yes 022 (0016) Read level 2 parameters 2 Reads parameters in level 2. Yes Yes 023 (0017) General-purpose read Reads the value of the specified parameter. Yes Yes Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd or 4th operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 211 Appendix C E5jK Digital Controller Read Protocol Connection Configuration The connection configuration for using the E5jK Digital Controller Read Protocol is shown below. RS-232C Connection CS1j E5jK Serial Communications Unit/Board RS-232C port → Serial Communications Unit/Board E5jK RS-232C: D-sub 9 pin female Signal name RS-232C: Terminal block Pin No. Terminal No. FG SD RD RTS CTS DSR DST SG Signal name SD RD SG Shielded cable Note 1. The communications configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use shielded twisted-pair cable (AWG28i or greater). RS-485 Connection CS1j E5jK Serial Communications Board RS-485 port → E5jK → Up to 31 units can be connected. E5jK → Note 1. The communications configuration is a one-to-one configuration or a one-to-N configuration. In the oneto-N configuration, up to 32 units including the Serial Communications Unit/Board can be connected. 2. The maximum cable length is 500 m. Use a shielded twisted-pair cable for the cable (AWG28i or greater). 212 Appendix C E5jK Digital Controller Read Protocol 3. Connect a terminator only at both ends of the transmission path. For instance, in the example shown below, connect a terminator to the Serial Communications Unit/Board and unit No.30 and do not connect any terminator to units No.0 to No.29. Use a resistance of 120Ω (1/2W) for the terminators (the total resistance of both ends must be 54Ω or more). Serial Communications Board RS-485: D-sub 9 pin female Pin No. Shielded cable E5CK (No. 0) A<B: [1] Mark A>B: [0] Space E5CK (No. 30) RS-485: Terminal block RS-485: Terminal block Terminal No. Terminal No. Terminator (120 /2 W) Read Process Value (Sequence No. 000 (Hex 0000)) Reads the process value and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Process value Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Process value (4 digits BCD) Scaling lower limit to upper limit Read Set Point during SP Ramp (Sequence No. 001 (Hex 0001)) Reads the set point during the SP ramp and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 213 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point during SP ramp Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Set point during SP ramp (4 digits BCD) Set point lower limit to upper limit Read MV (Sequence No. 002 (Hex 0002)) Reads the MV (manipulated variable) for heating and cooling and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 MV (heating) +2 MV (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 MV (heating) (4 digits BCD) F050 to 1050, 0000 to 1050 for heating/cooling control F indicates a negative value. +2 MV (cooling) (4 digits BCD) F050 to 1050 F indicates a negative value. Read Set Point (Sequence No. 003 (Hex 0003)) Reads the set point and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point Offset 214 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Set point (4 digits BCD) Set point lower limit to upper limit Appendix C E5jK Digital Controller Read Protocol Read Alarm Value (Sequence No. 004 (Hex 0004)) Reads alarm value 1 and alarm value 2 and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Alarm value 1 +2 Alarm value 2 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Proportional Band, Integral Time, and Derivative Time (Sequence No. 005 (Hex 0005)) Reads the proportional band, integral time, and derivative time and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Proportional band +2 Integral time +3 Derivative time Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0004 +1 Proportional band (4 digits BCD) 0000 to 9999 +2 Integral time (4 digits BCD) 0000 to 3999 +3 Derivative time (4 digits BCD) 0000 to 3999 215 Appendix C E5jK Digital Controller Read Protocol Read Cooling Coefficient (Sequence No. 006 (Hex 0006)) Reads the cooling coefficient and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Cooling coefficient Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Cooling coefficient (4 digits BCD) 0001 to 9999 Read Dead Band (Sequence No. 007 (Hex 0007)) Reads the dead band and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Dead band Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Dead band (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Manual Reset Value (Sequence No. 008 (Hex 0008)) Reads the manual reset value and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset 216 Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Manual reset value Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Manual reset value (4 digits BCD) 0000 to 1000 Read Hysteresis (Sequence No. 009 (Hex 0009)) Reads the hysteresis for heating and for cooling and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Hysteresis (heating) +2 Hysteresis (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Hysteresis (heating) (4 digits BCD) 0001 to 9999 +2 Hysteresis (cooling) (4 digits BCD) 0001 to 9999 Read Control Period (Sequence No. 010 (Hex 000A)) Reads the control period for heating and for cooling and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Control period (heating) +2 Control period (cooling) Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Control period (heating) (4 digits BCD) 0001 to 0099 +2 Control period (cooling) (4 digits BCD) 0001 to 0099 217 Appendix C E5jK Digital Controller Read Protocol Read SP Ramp Time Unit and Set Value (Sequence No. 011 (Hex 000B)) Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 SP ramp time unit +2 SP ramp set value Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 SP ramp time unit (4 digits BCD) 0000: s, 0001: hr +2 SP ramp set value (4 digits BCD) 0000 to 9999 Read LBA Detection Time (Sequence No. 012 (Hex 000C)) Reads the LBA (loop break alarm) detection time and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 LBA detection time Offset 218 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 LBA detection time (4 digits BCD) 0000 to 9999 Appendix C E5jK Digital Controller Read Protocol Read MV at Stop Time and at PV Error (Sequence No.013 (Hex 000D)) Reads the MV at stop time and at PV error and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 MV at stop time +2 MV at PV error Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 MV at stop time (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +2 MV at PV error (4 digits BCD) F050 to 1050 F indicates a negative value. Read MV Limits (Sequence No. 014 (Hex 000E)) Reads the MV upper limit, MV lower limit, and MV change rate limit and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 MV upper limit +2 MV lower limit +3 MV change rate limit Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0004 +1 MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 0000 to 1050 for heating/cooling control +2 MV lower limit (4 digits BCD) F050 to MV upper limit –1 F indicates a negative value values. A050 to 1050 for heating/cooling control A indicates a negative value. +3 MV change rate limit (4 digits BCD) 0000 to 1000 219 Appendix C E5jK Digital Controller Read Protocol Read Input Digital Filter (Sequence No. 015 (Hex 000F)) Reads the input digital filter and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Input digital filter Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Input digital filter (4 digits BCD) 0000 to 9999 Read Alarm Hysteresis (Sequence No. 016 (Hex 0010)) Reads the alarm 1 hysteresis and alarm 2 hysteresis and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Alarm 1 hysteresis +2 Alarm 2 hysteresis Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +2 Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 Read Input Shift Limits (Sequence No. 017 (Hex 0011)) Reads the input shift upper limit and input shift lower limit and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset 220 Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Input shift upper limit +2 Input shift lower limit Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Input shift upper limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Read Level 0 Parameters (Sequence No. 018 (Hex 0012)) Reads parameters in level 0 (process value, set point during SP ramp, MV (heating), MV (cooling), and set point) from multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Process value +2 Set point during SP ramp +3 MV (heating) +4 MV (cooling) +5 Set point ~ 1st unit ~ +36 Process value +37 Set point during SP ramp +38 MV (heating) +39 MV (cooling) +40 Set point 8th unit (max.) 221 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 5 + 1 +1 1st unit Process value (4 digits BCD) Scaling lower limit to upper limit +2 1st unit Set point during SP ramp (4 digits BCD) Set point lower limit to upper limit +3 1st unit MV (heating) (4 digits BCD) F050 to 1050 F indicates a negative value. 0000 to 1050 for heating/cooling control +4 1st unit MV (cooling) (4 digits BCD) 0000 to 1050 +5 1st unit Set point (4 digits BCD) Set point lower limit to upper limit D D D +40 (max.) 8th unit Set point (4 digits BCD) Set point lower limit to upper limit Read Level 1 Parameters 1 (Sequence No. 019 (Hex 0013)) Reads parameters in level 1 (alarm value 1, alarm value 2 , alarm value 3, proportional band, integral time, and derivative time) from multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Alarm value 1 +2 Alarm value 2 +3 Alarm value 3 +4 Proportional band +5 Integral time +6 Derivative time ~ 222 1st unit ~ +43 Alarm value 1 +44 Alarm value 2 +45 Alarm value 3 +46 Proportional band +47 Integral time +48 Derivative time 8th unit (max.) Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 6 + 1 +1 1st unit Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +2 1st unit Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +3 1st unit Alarm value 3 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +4 1st unit Proportional band (4 digits BCD) 0001 to 9999 +5 1st unit Integral time (4 digits BCD) 0000 to 3999 +6 1st unit Derivative time (4 digits BCD) 0000 to 3999 D D D +48 (max.) 8th unit Derivative time (4 digits BCD) 0000 to 3999 Read Level 1 Parameters 2 (Sequence No. 020 (Hex 0014)) Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 223 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Cooling coefficient +2 Dead band +3 Manual reset value +4 Hysteresis (heating) +5 Hysteresis (cooling) +6 Control period (heating) +7 Control period (cooling) ~ 1st unit ~ Cooling coefficient +50 +51 Dead band +52 Manual reset value +53 Hysteresis (heating) +54 Hysteresis (cooling) +55 Control period (heating) +56 Control period (cooling) Offset 8th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 7 + 1 +1 1st unit Cooling coefficient (4 digits BCD) 0001 to 9999 +2 1st unit Dead band (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +3 1st unit Manual reset value (4 digits BCD) 0000 to 1000 +4 1st unit Hysteresis (heating) (4 digits BCD) 0001 to 9999 +5 1st unit Hysteresis (cooling) (4 digits BCD) 0001 to 9999 +6 1st unit Control period (heating) (4 digits BCD) 0001 to 0099 +7 1st unit Control period (cooling) (4 digits BCD) 0001 to 0099 D D D +56 (max.) 224 8th unit Control period (cooling) (4 digits BCD) 0001 to 0099 Appendix C E5jK Digital Controller Read Protocol Read Level 2 Parameters 1 (Sequence No. 021 (Hex 0015)) Reads parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop, MV at PV Error, MV upper limit, MV lower limit, and MV change rate limit) from multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 SP ramp time unit +2 SP ramp set value +3 LBA detection time +4 MV at stop +5 MV at PV error +6 MV upper limit +7 MV lower limit +8 MV change rate limit ~ 1st unit ~ +57 SP ramp time unit +58 SP ramp set value +59 LBA detection time +60 MV at stop +61 MV at PV error +62 MV upper limit +63 MV lower limit +64 MV change rate limit 8th unit (max.) 225 Appendix C E5jK Digital Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 8 + 1 +1 1st unit SP ramp time unit (4 digits BCD) 0000: s, 0001: hr +2 1st unit SP ramp set value (4 digits BCD) 0000 to 9999 +3 1st unit LBA detection time (4 digits BCD)} 0000 to 9999 +4 1st unit MV at stop (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +5 1st unit MV at PV error (4 digits BCD) F050 to 1050 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +6 1st unit MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 0000 to 1050 for heating/cooling control +7 1st unit MV lower limit (4 digits BCD) F050 to MV upper limit –1 F indicates a negative value. A050 to 1050 for heating/cooling control A indicates a negative value. +8 1st unit MV change rate limit (4 digits BCD) 0000 to 1000 D D D +64 (max.) 8th unit MV change rate limit (4 digits BCD) 0000 to 1000 Read Level 2 Parameters 2 (Sequence No. 022 (Hex 0016)) Reads parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) from multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset 226 (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Appendix C E5jK Digital Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Input digital filter +2 Alarm 1 hysteresis +3 Alarm 2 hysteresis +4 Alarm 3 hysteresis +5 Input shift upper limit +6 Input shift lower limit 1st unit ~ ~ +43 Input digital filter +44 Alarm 1 hysteresis +45 Alarm 2 hysteresis +46 Alarm 3 hysteresis +47 Input shift upper limit +48 Input shift lower limit Offset 8th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 6 + 1 +1 1st unit Input digital filter (4 digits BCD) 0000 to 9999 +2 1st unit Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +3 1st unit Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 +4 1st unit Alarm 3 hysteresis (4 digits BCD) 0001 to 9999 +5 1st unit Input shift upper limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +6 1st unit Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. D D D +48 (max.) 8th unit Input shift lower limit (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. 227 Appendix C E5jK Digital Controller Read Protocol General-purpose Read (Sequence No. 023 (Hex 0017)) Reads the specified parameter and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 (Undefined) Number of send data words Unit No. +2 (Undefined) Parameter No. Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Parameter No. (2 digits BCD) Refer to the manual for the E5jK. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Read data (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. Note To read parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No. 075) in advance. 228 Appendix D E5jK Digital Controller Write Protocol The E5jK Digital Controller Write Protocol writes and controls various settings in remote mode for the Controller connected to the Serial Communications Unit/Board via RS-232C or RS-485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The following table shows the structure of the E5jK Digital Controller Write Protocol. Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation No 050 (0032) Write set point Writes the set point. 051 (0033) Write alarm value Writes alarm value 1, 2. Yes No 052 (0034) Write proportional band, integral time, and derivative time Writes the proportional band, integral time, and derivative time. Yes No 053 (0035) Write cooling coefficient Writes the cooling coefficient. Yes No 054 (0036) Write dead band Writes the dead band. Yes No 055 (0037) Write manual reset value Writes the manual reset value. Yes No 056 (0038) Write hysteresis Writes the hysteresis (heating, cooling) Yes No 057 (0039) Write control period Yes No 058 (003A) Write SP ramp time units and set value Write LBA detection time Writes the control period (heating, cooling) Writes the SP ramp time unit and SP ramp set value. Writes the LBA detection time. Yes No Yes No 060 (003C) Write MV at stop time and PV error 061 (003D) Write MV limits Writes the MV at stop and the MV at PC error. Writes the MV limits. Yes No Yes No 062 (003E) Write input digital filter Writes the input digital filter. Yes No 063 (003F) Write alarm hysteresis Writes alarm 1, 2 hysteresis. Yes No 064 (0040) Write input shift values Writes the input shift values. Yes No 065 (0041) Write level 0 parameters Writes parameters in level 0. Yes No 066 (0042) Write level 1 parameters 1 Writes parameters in level 1. Yes No 067 (0043) Write level 1 parameters 2 Writes parameters in level 1. Yes No 068 (0044) Write level 2 parameters 1 Writes parameters in level 2. Yes No 069 (0045) Write level 2 parameters 2 Writes parameters in level 2. Yes No 070 (0046) General-purpose write Yes No 071 (0047) Yes No 072 (0048) Switch to level 0 (software reset) Run/stop Writes the value of the specified parameter. Switches the setting level to level 0. Initiates Run or Stop. Yes No 073 (0049) Remote/local Switches the mode to remote or local. Yes No 074 (004A) Execute/cancel AT Executes or cancels AT. Yes No 075 (004B) Switch to level 1 Switches the setting level to level 1. Yes No Resets the E5jK. Yes No 059 (003B) 076 (004C) Software reset Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd or 4th operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 229 Appendix D E5jK Digital Controller Write Protocol Connections The connections are the same as that for the E5jK Digital Controller Read Protocol. Write Set Point (Sequence No. 050 (Hex 0032)) Writes the set point. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. set point +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Set point (4 digits BCD) Set point lower limit to upper limit Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Alarm Value (Sequence No. 051 (Hex 0033)) Writes alarm value 1 and alarm value 2. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. +2 Alarm value 1 +3 Alarm value 2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Alarm value 1 (4 digits BCD) 0000 to 999 +3 Alarm value 2 (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (3rd Operand of PMCR(260)) None. Write Proportional Band, Integral Time, and Derivative Time (Sequence No. 052 (Hex 0034)) Writes the proportional band, integral time, and derivative time. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) +2 +3 Integral time +4 Derivative time Offset 230 Unit No. Proportional band Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Proportional band (4 digits BCD) 0001 to 9999 +3 Integral time (4 digits BCD) 0000 to 3999 +4 Derivative time (4 digits BCD) 0000 to 3999 Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Cooling Coefficient (Sequence No. 053 (Hex 0035)) Writes the cooling coefficient. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Cooling coefficient +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Cooling coefficient (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Dead Band (Sequence No. 054 (Hex 0036)) Writes the dead band. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Dead band +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Dead band (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Manual Reset Value (Sequence No. 055 (Hex 0037)) Writes the manual reset value. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Manual reset value +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Manual reset value (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Hysteresis (Sequence No. 056 (Hex 0038)) Writes the hysteresis for heating and for cooling. 231 Appendix D E5jK Digital Controller Write Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Hysteresis (heating) +3 Hysteresis (cooling) Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Hysteresis (heating) (4 digits BCD) 0001 to 9999 +3 Hysteresis (cooling) (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Control Period (Sequence No. 057 (Hex 0039)) Writes the control period for heating and for cooling. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Control period (heating) +3 Control period (cooling) Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Control period (heating) (4 digits BCD) 0001 to 0099 +3 Control period (cooling) (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write SP Ramp Time Unit and Set Value (Sequence No. 058 (Hex 003A)) Writes the SP ramp time unit and SP ramp set value. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 SP ramp time unit +3 SP ramp set value Offset 232 Unit No. +2 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 SP ramp time unit (4 digits BCD) 0000: 0001: +3 SP ramp set value (4 digits BCD) 0000 to 9999 Minutes Hours Appendix D E5jK Digital Controller Write Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write LBA Detection Time (Sequence No. 059 (Hex 003B)) Writes the LBA detection time. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. LBA detection time +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 LBA detection time (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write MV at Stop Time and at PV Error (Sequence No. 060 (Hex 003C)) Writes the MV at stop time and the MV at PV error. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 MV at stop time +3 MV at PV error Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 MV at stop time (4 digits BCD) 0000 to 1050 +3 MV at PV error (4 digits BCD) 0000 to 1050 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write MV Limits (Sequence No. 061 (Hex 003D)) Writes the MV upper limit, MV lower limit, and MV change rate limit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. +2 MV upper limit +3 MV lower limit +4 MV change rate limit 233 Appendix D E5jK Digital Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 Heating/cooling control time: 0000 to 1050 +3 MV lower limit (4 digits BCD) 0000 to MV upper limit – 1 +4 MV change rate limit (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Input Digital Filter (Sequence No. 062 (Hex 003E)) Writes the input digital filter. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Input digital filter +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input digital filter (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Alarm Hysteresis (Sequence No. 063 (Hex 003F)) Writes the alarm 1 hysteresis and alarm 2 hysteresis. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Alarm 1 hysteresis +3 Alarm 2 hysteresis Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +3 Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Input Shift Value (Sequence No. 064 (Hex 0040)) Writes the input shift upper limit and input shift lower limit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data 234 +0 +1 Number of send data words (Undefined) Unit No. +2 Input shift upper limit +3 Input shift lower limit Appendix D E5jK Digital Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input shift upper limit (4 digits BCD) 0000 to 9999 +3 Input shift lower limit (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Level 0 Parameters (Sequence No. 065 (Hex 0041)) Writes parameters (set points) in level 0 to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Set point +3 (Undefined) +4 Unit No. 2nd unit Set point +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Set point +17 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Set point (4 digits BCD) Set point lower limit to upper limit D D D +17 (max.) 8th unit Set point (4 digits BCD) Set point lower limit to upper limit Receive Data Word Allocation (4th Operand of PMCR(260)) None. 235 Appendix D E5jK Digital Controller Write Protocol Write Level 1 Parameters 1 (Sequence No. 066 (Hex 0042)) Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and derivative time) to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. +3 Alarm value 1 +4 Alarm value 2 +5 Alarm value 3 +6 Proportional band +7 Integral time +8 Derivative time 1st unit ~ +51 ~ (Undefined) Unit No. +52 Alarm value 1 +53 Alarm value 2 +54 Alarm value 3 +55 Proportional band +56 Integral time +57 Derivative time Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 7 + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Alarm value 1 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +4 1st unit Alarm value 2 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +5 1st unit Alarm value 3 (4 digits BCD) A999 to 9999 F indicates a negative value and A indicates –1. +6 1st unit Proportional band (4 digits BCD) 0001 to 9999 +7 1st unit Integral time (4 digits BCD) 0000 to 3999 +8 1st unit Derivative time (4 digits BCD) 0000 to 3999 D D D +57 (max.) 8th unit Derivative time (4 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. 236 0000 to 3999 Appendix D E5jK Digital Controller Write Protocol Write Level 1 Parameter 2 (Sequence No. 067 (Hex 0043)) Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. +3 Cooling coefficient +4 Dead band +5 Manual reset value +6 Hysteresis (heating) +7 Hysteresis (cooling) +8 Control period (heating) +9 Control period (cooling) ~ ~ (Undefined) +58 1st unit Unit No. +59 Cooling coefficient +60 Dead band +61 Manual reset value +62 Hysteresis (heating) +63 Hysteresis (cooling) +64 Control period (heating) +65 Control period (cooling) Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 8 + 2 +1 +2 Number of units (4 digits Hex) 1st unit Unit No. (2 digits BCD) 0001 to 0008 00 to 31 +3 1st unit Cooling coefficient (4 digits BCD) 0001 to 9999 +4 1st unit Dead band (4 digits BCD) 0000 to 9999 +5 1st unit Manual reset value (4 digits BCD) 0000 to 1000 +6 1st unit Hysteresis (heating) (4 digits BCD) 0001 to 9999 +7 1st unit Hysteresis (cooling) (4 digits BCD) 0001 to 9999 +8 1st unit Control period (heating) (4 digits BCD) 0001 to 0099 +9 1st unit Control period (cooling) (4 digits BCD) 0001 to 0099 D D D +65 (max.) 8th unit Control period (cooling) (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 237 Appendix D E5jK Digital Controller Write Protocol Write Level 2 Parameters 1 (Sequence No. 068 (Hex 0044)) Writes parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop time, MV at PV error, MV upper limit, MV lower limit, and MV change rate limit) to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 +2 Number of units (Undefined) Unit No. SP ramp time unit +3 +4 SP ramp set value +5 LBA detection time +6 MV at stop +7 MV at PV error +8 MV upper limit +9 MV lower limit +10 MV change rate limit 1st unit ~ +65 ~ (Undefined) Unit No. +66 SP ramp time unit +67 SP ramp set value +68 LBA detection time +69 MV at stop +70 MV at PV error +71 MV upper limit +72 MV lower limit +73 MV change rate limit Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 9 + 2 +1 +2 Number of units (4 digits BCD) 1st unit Unit No. (2 digits BCD) 0001 to 0008 00 to 31 +3 1st unit SP ramp time unit (4 digits BCD) 0000 to 0001 +4 1st unit SP ramp set value (4 digits BCD) 0000 to 9999 +5 1st unit LBA detection time (4 digits BCD) 0000 to 9999 +6 1st unit MV at stop (4 digits BCD) 0000 to 1050 +7 1st unit MV at PV error (4 digits BCD) 0000 to 1050 +8 1st unit MV upper limit (4 digits BCD) MV lower limit + 1 to 1050 +9 1st unit MV lower limit (4 digits BCD) 0000 to MV upper limit –1 +10 1st unit MV change rate limit (4 digits BCD) 0000 to 1000 D D D +73 (max.) 8th unit MV change rate limit (4 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. 238 0000 to 1000 Appendix D E5jK Digital Controller Write Protocol Write Level 2 Parameters 2 (Sequence No. 069 (Hex 0045)) Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Input digital filter +4 alarm 1 hysteresis +5 alarm 2 hysteresis +6 alarm 3 hysteresis +7 Input shift upper limit +8 Input shift lower limit 1st unit ~ +51 ~ (Undefined) Unit No. +52 Input digital filter +53 alarm 1 hysteresis +54 alarm 2 hysteresis +55 alarm 3 hysteresis +56 Input shift upper limit +57 Input shift lower limit Offset 8th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 7 + 2 +1 Number of units (4 digits BCD) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Input digital filter (4 digits BCD) 0000 to 9999 +4 1st unit Alarm 1 hysteresis (4 digits BCD) 0001 to 9999 +5 1st unit Alarm 2 hysteresis (4 digits BCD) 0001 to 9999 +6 1st unit Alarm 3 hysteresis (4 digits BCD) 0001 to 0099 +7 1st unit Input shift upper limit (4 digits BCD) 000 to 9999 +8 1st unit Input shift lower limit (4 digits BCD) 000 to 9999 D D D +57 (max.) 8th unit Input shift lower limit (4 digits BCD) 000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 239 Appendix D E5jK Digital Controller Write Protocol General-purpose Write (Sequence No. 070 (Hex 0046)) Writes the specified parameter. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Parameter No. Write data +3 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Parameter No. (2 digits BCD) Refer to the manual of E5jK. +3 Write data (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note To write parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No. 075) in advance. Switch to Level 0 (Software Reset) (Sequence No. 071 (Hex 0047)) Resets the operation of the E5jK and waits until communications are enabled. This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note When this sequence is executed, a software reset command is issued and the operation of the E5jK is reset (equivalent to turning on the power supply). About five seconds will be required until communications are enabled. 240 Appendix D E5jK Digital Controller Write Protocol Run/Stop (Sequence No. 072 (Hex 0048)) Switches the mode to Run or Stop according to the command code. This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. 1st unit Command code +3 (Undefined) +4 Unit No. 2nd unit Command code +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Command code +17 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Run 0001: Stop D D D +17 (max.) 8th unit Command code (4 digits BCD) 0000: Run 0001: Stop Receive Data Word Allocation (4th Operand of PMCR(260)) None. Remote/Local (Sequence No. 073 (Hex 0049)) Switches to remote operation or local operation according to the command mode. This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 +2 +3 +4 +5 Number of send data words Number of units (Undefined) Unit No. (Undefined) Unit No. +17 2nd unit Command code ~ +16 1st unit Command code ~ (Undefined) Unit No. 8th unit (max.) Command code 241 Appendix D E5jK Digital Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Local 0001: Remote D D D +17 (max.) 8th unit Command code (4 digits BCD) 0000: Local 0001: Remote Receive Data Word Allocation (4th Operand of PMCR(260)) None. Execute/Cancel AT (Sequence No. 074 (Hex 004A)) Executes or cancels AT (autotuning) according to the command code. This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Command code +3 (Undefined) +4 Unit No. 2nd unit Command code +5 ~ ~ (Undefined) +16 Unit No. 8th unit (max.) Command code +17 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Command code (4 digits BCD) 0000: Stop 0001: Execute AT 40% 0002: Execute AT 100% D D D +17 (max.) 8th unit Command code (4 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. 242 0000: Stop 0001: Execute AT 40% 0002: Execute AT 100% Appendix D E5jK Digital Controller Write Protocol Switch to Level 1 (Sequence No. 075 (Hex 004B)) Switches the setting level to level 1 (setup mode, extended mode). This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. (Undefined) Unit No. ~ +9 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Software Reset (Sequence No. 076 (Hex 004C)) Resets the operation of the E5jK (equivalent to turning on the power supply). This sequence can be executed for multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ ~ (Undefined) +9 Offset Unit No. (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0008 +2 to 9 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Communications with the E5jK are disabled for about five seconds after this sequence is executed. 243 Appendix E E5ZE Temperature Controller Read Protocol The E5ZE Temperature Controller Read Protocol reads and controls various parameters in remote mode for the Temperature Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422/485 cable. Note All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks. Structure of the Protocol The following table shows the structure of the E5ZE Temperature Controller Read Protocol Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation Yes 100 (0064) Read set point Reads the set points. 101 (0065) Read process value Reads the process values. Yes Yes 102 (0066) Read output value Reads the output values. Yes Yes 103 (0067) Reads the set points, process values, and output values. Reads the proportional bands, integral times, and derivative times. Reads the control periods. Yes Yes Yes Yes 105 (0069) Read set point, process value, and output value Read proportional band, integral time, and derivative time Read control period Yes Yes 106 (006A) Read output mode Reads the output modes. Yes Yes 107 (006B) Read alarm mode 104 (0068) Reads the alarm modes. Yes Yes 108 (006C) Read alarm temperature Reads the alarm temperatures. Yes Yes 109 (006D) Read hysteresis Reads the hysteresis. Yes Yes 110 (006E) Read operation status Reads the operation status. Yes Yes 111 (006F) Read error status Reads the error status. Yes Yes 112 (0070) Read setting unit Reads the setting units. Yes Yes 113 (0071) Read input shift value Reads the input shift values. Yes Yes 114 (0072) Read manual reset value Reads the manual reset values. Yes Yes 115 (0073) Read ramp value Reads the ramp values. Yes Yes 116 (0074) Read present set point Reads the present set points. Yes Yes 117 (0075) Read output value limits Reads the output value limits. Yes Yes 118 (0076) Yes Yes Yes Yes Yes Yes Yes Yes Yes 123 (007B) Read cooling coefficient Reads the output value change rate limits. Reads the HB alarm and HS alarm valid channels. Reads the heater burnout/SSR failure detection currents. Reads the heater currents and SSR leakage currents. Reads the dead bands and overlap bands. Reads the cooling coefficients. Yes 122 (007A) Read output value change rate limit Read HB alarm and HS alarm valid channels Read heater burnout/SSR failure detection currents Read heater current and SSR leakage current Read dead band/overlap band Yes Yes 119 (0077) 120 (0078) 121 (0079) Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd or 4th operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 245 Appendix E E5ZE Temperature Controller Read Protocol Connections This section shows connections for using the E5ZE Temperature Controller Read Protocol. RS-232C Connections CS1j E5ZE Serial Communications Unit/ Board RS-232C port → RS-232C Signal name Signal Pin abbreviNo. ation NC SD RD RTS CTS DSR SG NC NC NC NC NC NC RS-232C NC NC NC NC NC NC DTR NC NC NC NC NC Abbreviation Signal direction Pin No. Signal ground or common return line Send data SG --- 7 SD Output 2 Receive data RD Input 3 Request to send RTS Output 4 Clear to send CTS Input 5 Data set ready DSR Input 6 Data terminal ready DTR Output 20 Disabled (Do not connect.) NC --- 1, 8 to 19, 21 to 25 Serial Communications Unit/Board/Unit E5ZE RS-232C: D-sub 9-pin female Signal name FG SG SD RD RTS CTS DSR DTR Pin No. RS-232C: D-sub 9-pin female Shield Pin No. LT1181CS or equivalent Signal name SG SD RD RTS CTS DSR DTR Note 1. The maximum communications cable length is 15 m. Use a shielded twisted-pair cable for the cable. 2. Use a 25-pin D-sub Plug (OMRON XM2A-2501). 3. Use XM2S-2511 Hood (OMRON) or an equivalent. 246 Appendix E E5ZE Temperature Controller Read Protocol RS422/485 Connections • RS-485 2-wire Connections Pin No. Signal name Abbreviation Signal direction 1 Disabled (Do not connect.) --- --- 2 Disabled (Do not connect.) --- --- 3 Signal ground SG --- 4 Terminal B (+ side) B I/O 5 Terminal A (– side) A I/O Turn off the communications switch to disconnect terminating resistance. Serial Communications Board RS-485: D-sub 9-pin female Signal name Pin No. SN751177N or equivalent Terminating resistance E5ZE 240 Ω RS-485: Terminals Terminal Signal name Shell Shield E5ZE RS-485: Terminals *1: Set the 2-/4-wire switch to the 2-wire setting. Shield Terminal Signal name Terminating resistance *2: Turn ON the terminating resistance switch. Note Terminal block pins 1 and 2 cannot be connected. If these blocks are used, operation of the E5ZE may fail. 247 Appendix E E5ZE Temperature Controller Read Protocol • RS-422 4-wire Connections Pin No. Signal name Abbreviation 1 Receive data B RDB Input 2 Receive data A RDA Input 3 Signal ground SG --- 4 Send data B SDB Output 5 Send data A SDA Output Serial Communications Board RS-422: D-sub 9-pin female Signal name Turn off the communications switch to disconnect terminating resistance. SN751177N or equivalent E5ZE RS-422: Terminals Pin No. Terminal Shell Shield *1: Set the 2-/4-wire switch to the 4-wire setting. *2: Turn ON the terminating resistance switch. Terminating resistance Signal name Terminating resistance Shield Terminal block Terminal Terminating resistance Signal name Terminating resistance 240 Ω 248 Signal direction Appendix E E5ZE Temperature Controller Read Protocol Switch Settings This section shows the switch settings for using the E5ZE Temperature Controller Read Protocol. Communications Parameter DIP Switch DTS-4 1 2 3 4 Pins 3 and 4: Terminating resistance Pins 1 and 2: RS-422/RS-485 Factory defaults: All OFF OFF OFF 1 and 2 RS-422 or RS-485 OFF OFF ON ON 3 4 OFF 3 4 OFF OFF ON OFF 1 2 ON ON RS-485 3 4 RS-422 3 4 Parameter Terminating ON resistance 1 2 Pins 3 and 4 Unit Number Switch Setting 0 1 2 3 4 5 6 7 8 9 A B C D E F Unit No. 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F Y Factory defaults Baud Rate DIP Switch ON 1 2 3 45 6 7 8 Factory default: 9,600 bps (pin 1 ON, pin 2 OFF) ON 2 ON 1 ON 2 ON 1 2,400 2 4,800 1 9,600 2 19,200 1 Baud rate (bps) Pins 1 and 2 Read Set Point (Sequence No. 100 (Hex 0064)) Reads the set points and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. 249 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point (rightmost 4 digits) +2 Set point (leftmost 1 digit) ~ Offset Channel 0 ~ +15 Set point (rightmost 4 digits) +16 Set point (leftmost 1 digit) Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) F indicates a negative value. D D D +15 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Set point (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer the manual for the E5ZE. F indicates a negative value. Read Process Value (Sequence No. 101 (Hex 0065)) Reads the process values and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Process value (rightmost 4 digits) +2 Process value (leftmost 1 digit) +3 Process value (rightmost 4 digits) +4 Process value (leftmost 1 digit) ~ 250 Channel 0 Channel 1 ~ +15 Process value (rightmost 4 digits) +16 Process value (leftmost 1 digit) Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Process value (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Process value (leftmost 1 digit) (1 digit BCD) F indicates a negative value. D D D +15 Channel 7 Process value (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Process value (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. F indicates a negative value. Read Output Values (Sequence No. 102 (Hex 0066)) Reads the output values of the control outputs and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Output value +2 Cooling output value +3 Output value +4 Cooling output value ~ Channel 0 Channel 1 ~ +15 Output value +16 Cooling output value Channel 7 251 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Output value (4 digits BCD) 0000 to 1000 +2 Channel 0 Cooling output value (4 digits BCD) 0000 to 1000 +3 Channel 1 Output value (4 digits BCD) 0000 to 1000 +4 Channel 1 Cooling output value (4 digits BCD) 0000 to 1000 D D D +15 Channel 7 Output value (4 digits BCD) 0000 to 1000 +16 Channel 7 Cooling output value (4 digits BCD) 0000 to 1000 Read Set Point, Process Value, and Output Value (Sequence No. 103 (Hex 0067)) Reads the set points, process values, and output values and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to OF Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point (rightmost 4 digits) +2 Set point (leftmost 1 digit) +3 Process value (rightmost 4 digits) +4 Process value (leftmost 1 digit) +5 Output value ~ +36 Set point (leftmost 1 digit) +38 Process value (rightmost 4 digits) +40 252 ~ Set point (rightmost 4 digits) +37 +39 Channel 0 Process value (leftmost 1 digit) Output value Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0029 (0041 decimal) +1 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) +3 Channel 0 Process value (rightmost 4 digits) (4 digits BCD) +4 Channel 0 Process value (leftmost 1 digit) (1 digit BCD) +5 Channel 0 Output value (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. 0000 to 1000 D D D Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +36 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +37 Channel 7 Set point (leftmost 1 digit) (1 digit BCD) +38 Channel 7 Process value (rightmost 4 digits) (4 digits BCD) +39 Channel 7 Process value (leftmost 1 digit) (1 digit BCD) +40 Channel 0 Output value (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. 0000 to 1000 Read Proportional Band, Integral Time, and Derivative Time (Sequence No. 104 (Hex 0068)) Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Constant P +2 Constant I +3 Constant D ~ +22 Channel 0 ~ Constant P +23 Constant I +24 Constant D Channel 7 253 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0019 (0025 decimal) +1 Channel 0 Constant P (4 digits BCD) 0000 to 9999 +2 Channel 0 Constant I (4 digits BCD) 0000 to 3999 +3 Channel 0 Constant D (4 digits BCD) 0000 to 3999 D D D +22 Channel 7 Constant P (4 digits BCD) 0000 to 9999 +2 3 Channel 7 Constant I (4 digits BCD) 0000 to 3999 +24 Channel 7 Constant D (4 digits BCD) 0000 to 3999 Read Control Period (Sequence No. 105 (Hex 0069)) Reads the control periods and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Control period +2 Cooling control period +3 Control period +4 Cooling control period ~ Channel 1 ~ +15 Control period +16 Cooling control period Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Control period (4 digits BCD) 0001 to 0099 +2 Channel 0 Cooling control period (4 digits BCD) 0001 to 0099 D D D 254 +15 Channel 7 Control period (4 digits BCD) 0001 to 0099 +16 Channel 7 Cooling control period (4 digits BCD) 0001 to 0099 Appendix E E5ZE Temperature Controller Read Protocol Read Output Mode (Sequence No. 106 (Hex 006A)) Reads the output modes (normal/reverse) and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words Number of receive data words +0 (Undefined) +1 Offset Set code Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Set code (2 digits Hex) 00 to FF Read Alarm Mode (Sequence No. 107 (Hex 006B)) Reads the alarm modes and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 (Undefined) Alarm 1 set code +2 (Undefined) Alarm 2 set code +3 (Undefined) Alarm 1 set code +4 (Undefined) Alarm 2 set code ~ Channel 0 Channel 1 ~ +15 (Undefined) Alarm 1 set code +16 (Undefined) Alarm 2 set code Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Alarm 1 set code (2 digits Hex) 00 to 0C +2 Channel 0 Alarm 2 set code (2 digits Hex) 00 to 0C D D D +15 Channel 7 Alarm 1 set code (2 digits Hex) 00 to 0C +16 Channel 7 Alarm 2 set code (2 digits Hex) 00 to 0C 255 Appendix E E5ZE Temperature Controller Read Protocol Read Alarm Temperatures (Sequence No. 108 (Hex 006C)) Reads the alarm temperatures and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Alarm 1 set value (rightmost 4 digits) +2 Alarm 1 set value (leftmost 1 digit) +3 Alarm 2 set value (rightmost 4 digits) +4 Alarm 2 set value (leftmost 1 digit) ~ +29 Channel 0 ~ Alarm 1 set value (rightmost 4 digits) +30 Alarm 1 set value (rightmost 1 digit) +31 Alarm 2 set value (rightmost 4 digits) +32 Alarm 2 set value (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0021 (0033 decimal) +1 Channel 0 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +2 Channel 0 Alarm 1 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. +3 Channel 0 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +4 Channel 0 Alarm 2 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. D D D 256 +29 Channel 7 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +30 Channel 7 Alarm 1 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. +31 Channel 7 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 F indicates a negative number. +32 Channel 07 Alarm 2 set value (leftmost 1 digit) (4 digits BCD) 0000 to 0009 F indicates a negative number. Appendix E E5ZE Temperature Controller Read Protocol Read Hysteresis (Sequence No. 109 (Hex 006D)) Reads the hysteresis and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Hysteresis +2 Cooling hysteresis +3 Hysteresis +4 Cooling hysteresis ~ Channel 0 Channel 1 ~ +15 Hysteresis +16 Cooling hysteresis Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Hysteresis (4 digits BCD) 0000 to 0999 +2 Channel 0 Cooling hysteresis (4 digits BCD) 0000 to 0999 D D D +15 Channel 7 Hysteresis (4 digits BCD) 0000 to 0999 +16 Channel 7 Cooling hysteresis (4 digits BCD) 0000 to 0999 Read Operation Status (Sequence No. 110 (Hex 006E)) Reads the operation status of the E5ZE and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Status code Channel 0 +2 Status code Channel 1 ~ +8 ~ Status code Channel 7 257 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Status code (4 digits Hex) 0000 to FFFF +2 Channel 1 Status code (4 digits Hex) 0000 to FFFF D D D +8 Channel 7 Status code (4 digits Hex) 0000 to FFFF Read Error Status (Sequence No. 111 (Hex 006F)) Reads the contents of errors if they have occurred and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Status code Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Status code (4 digits BCD) 0000 to FFFF Read Setting Unit (Sequence No. 112 (Hex 0070)) Reads the setting units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set code Offset 258 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Set code (4 digits BCD) 0000: unit of 1 0001: unit of 0.1 Appendix E E5ZE Temperature Controller Read Protocol Read Input Shift Value (Sequence No. 113 (Hex 0071)) Reads the input shift values and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Input shift value +2 Input shift value Channel 0 Channel 1 ~ ~ Input shift value +8 Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. +2 Channel 1 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. D D D +8 Channel 7 Input shift value (4 digits BCD) 0000 to 0999 F indicates a negative number. Read Manual Reset Value (Sequence No. 114 (Hex 0072)) Reads the manual reset value and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Manual reset value +2 Manual reset value ~ +8 Channel 0 Channel 1 ~ Manual reset value Channel 7 259 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Manual reset value (4 digits BCD) 0000 to 1000 +2 Channel 1 Manual reset value (4 digits BCD) 0000 to 1000 D D D +8 Channel 7 Manual reset value (4 digits BCD) 0000 to 1000 Read Ramp Value (Sequence No. 115 (Hex 0073)) Reads the ramp values and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 +2 +3 +4 Number of receive data words (Undefined) Time unit (Undefined) Time unit Ramp value Channel 0 (Undefined) Ramp value Channel 1 (Undefined) ~ +15 +16 Offset ~ (Undefined) Time unit Ramp value Channel 7 (Undefined) Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Ramp value (3 digits BCD) 000 to 999 +2 Channel 0 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours D D D 260 +15 Channel 7 Ramp value (3 digits BCD) 000 to 999 +16 Channel 7 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours Appendix E E5ZE Temperature Controller Read Protocol Read Present Set Point (Sequence No. 116 (Hex 0074)) Reads the present set points during ramp operation and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Present set point (rightmost 4 digits) +2 Present set point (leftmost 1 digit) ~ Channel 0 ~ +15 Present set point (rightmost 4 digits) +16 Present set point (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Present set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +2 Channel 0 Present set point (leftmost 1 digit) (1 digit BCD) F indicates a negative value. D D D +15 Channel 7 Present set point (rightmost 4 digits) (4 digits BCD) +16 Channel 7 Present set point (leftmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. F indicates a negative value. Read Output Value Limit (Sequence No. 117 (Hex 0075)) Reads the output value limits and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F 261 Appendix E E5ZE Temperature Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Output value lower limit +2 Output value upper limit +3 Cooling control output value lower limit +4 Cooling control output value upper limit ~ Channel 0 ~ +29 Output value lower limit +30 Output value upper limit +31 Cooling control output value lower limit Channel 7 +32 Cooling control output value upper limit Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0021 (0033 decimal) +1 Channel 0 Output value lower limit (4 digits BCD) 0000 to 1000 +2 Channel 0 Output value upper limit (4 digits BCD) 0000 to 1000 +3 Channel 0 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 +4 Channel 0 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 D D D +31 Channel 7 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 +32 Channel 7 Cooling control output value upper limit (4 digits BCD) 0000 to 1000 Read Output Value Change Rate Limit (Sequence No. 118 (Hex 0076)) Reads the output value change rate limits and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Output value change rate limit Channel 0 +2 Output value change rate limit Channel 1 ~ +8 262 ~ Output value change rate limit Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Output value change rate limit (4 digits BCD) 0000 to 1000 +2 Channel 1 Output value change rate limit (4 digits BCD) 0000 to 1000 D D D +8 Channel 7 Output value change rate limit (4 digits BCD) 0000 to 1000 Read HB Alarm and HS Alarm Valid Channels (Sequence No. 119 (Hex 0077)) Reads the valid or invalid channels for HB alarms and HS alarms and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 Offset Set code Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Set code (2 digits Hex) 00 to FF Read Heater Burnout and SSR Failure Detection Currents (Sequence No. 120 (Hex 0078)) Reads the heater burnout and SSR failure detection currents and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F 263 Appendix E E5ZE Temperature Controller Read Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Heater burnout detection current +2 SSR failure detection current +3 Heater burnout detection current +4 SSR failure detection current Channel 0 Channel 1 ~ ~ +15 Heater burnout detection current +16 SSR failure detection current Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Heater burnout detection current (4 digits BCD) 0000 to 0500 +2 Channel 0 SSR failure detection current (4 digits BCD) 0000 to 0500 D D D +15 Channel 7 Heater burnout detection current (4 digits BCD) 0000 to 0500 +16 Channel 7 SSR failure detection current (4 digits BCD) 0000 to 0500 Read Heater Current and SSR Leakage Current (Sequence No.121 (Hex 0079)) Reads the heater currents and SSR leakage currents and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Heater current +2 SSR leakage current +3 Heater current +4 SSR leakage current ~ 264 Channel 0 Channel 1 ~ +15 Heater current +16 SSR leakage current Channel 7 Appendix E E5ZE Temperature Controller Read Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0011 (0017 decimal) +1 Channel 0 Heater current (4 digits BCD) 0000 to 0500 +2 Channel 0 SSR leakage current (4 digits BCD) 0000 to 0500 D D D +15 Channel 7 Heater current (4 digits BCD) 0000 to 0500 +16 Channel 7 SSR leakage current (4 digits BCD) 0000 to 0500 Note The read data will be 0000 for all channels for which HB and HS alarms are not enabled and for all channels for which control is stopped. Read Dead Band/Overlap Band (Sequence No. 122 (Hex 007A)) Reads the dead bands/overlap bands and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Dead band/overlap band +2 Dead band/overlap band ~ Channel 0 Channel 1 ~ Dead band/overlap band +8 Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Dead band/overlap band (4 digits BCD) 0000 to 0999 Channel 1 Dead band/overlap band (4 digits BCD) 0000 to 0999 +2 F indicates a number. F indicates a number. D D D +8 Channel 7 Dead band/overlap band (4 digits BCD) 0000 to 0999 F indicates a number. 265 Appendix E E5ZE Temperature Controller Read Protocol Read Cooling Coefficient (Sequence No. 123 (Hex 007B)) Reads the cooling coefficients and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Cooling coefficient +2 Cooling coefficient ~ +8 Channel 0 Channel 1 ~ Cooling coefficient Offset Channel 7 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0009 +1 Channel 0 Cooling coefficient (4 digits BCD) 0000 to 0100 +2 Channel 1 Cooling coefficient (4 digits BCD) 0000 to 0100 D D D +8 266 Channel 7 Cooling coefficient (4 digits BCD) 0000 to 0100 Appendix F E5ZE Temperature Controller Write Protocol The E5ZE Temperature Controller Write Protocol writes and controls various settings in remote mode for the Temperature Controller connected via a RS-232C or RS-422/485 cable from the PC via the Serial Communications Unit/Board. Note 1. Negative values cannot be written. All values must be set as unsigned BCD. 2. All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks. Structure of the Protocol The following table shows the structure of the E5ZE Temperature Controller Write Protocol. Sequence No. 150 (0096) 151 (0097) 152 (0098) 153 (0099) 154 (009A) 155 (009B) 156 (009C) 157 (009D) 158 (009E) 159 (009F) 160 (00A0) 161 (00A1) 162 (00A2) 163 (00A3) 164 (00A4) 165 (00A5) 166 (00A6) 167 (00A7) 168 (00A8) 169 (00A9) 170 (00AA) Communications sequence name Function Ladder interface Send Receive word word allocation allocation Write set point (setting unit 1) Writes the set points using a setting unit of 1. Yes No Writes the set points using a setting unit of 0.1. Write proportional band, integral time, Writes the proportional bands, integral times, and derivative time and derivative times. Write control period Writes the control periods. Yes No Yes No Yes No Write output mode Writes the output modes. Yes No Write alarm mode Writes the alarm modes. Yes No Write alarm temperature (setting unit 1) Write alarm temperature (setting unit 0.1) Write hysteresis Writes the alarm temperatures using a setting unit of 1. Writes the alarm temperatures using a setting unit of 0.1. Writes the hysteresis. Yes No Yes No Yes No Start autotuning Starts autotuning. Yes No Cancel autotuning Cancels autotuning. Yes No Write setting unit Writes the setting units. Yes No Write input shift value Writes the input shift values. Yes No Write manual reset value Writes the manual reset values. Yes No Write ramp value Writes the ramp values. Yes No Write manual output value Writes the manual output values. Yes No Write output value limit Writes the output value limits. Yes No Write output value change rate limit Write output value change rate limits. Yes No Save settings Saves settings. Yes No Initialize settings Initializes settings. Yes No Write HB alarm and HS alarm valid channels Writes the HB alarm and HS alarm valid channels. Yes No Write set point (setting unit 0.1) 267 Appendix F E5ZE Temperature Controller Write Protocol Sequence No. Communications sequence name 171 (00AB) 172 (00AC) 173 (00AD) 174 (00AE) 175 (00AF) 176 (00B0) Write heater burnout and SSR failure detection currents Write dead band/overlap band Writes the heater burnout and SSR failure detection currents. Writes the dead bands/overlap bands. Yes No Yes No Write cooling coefficient Writes the cooling coefficients. Yes No Start control Starts temperature control. Yes No Stop operation or control Stops temperature control or manual operation. Starts manual operation. Yes No Yes No Start manual operation Function Ladder interface Send Receive word word allocation allocation Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd or 4th operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). Connections The connections are the same as that for the E5ZE Temperature Controller Read Protocol. Write Set Point (Setting Unit 1) (Sequence No. 150 (Hex 0096)) Writes the set points using a setting unit of 1 (4 digits). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 +2 Set point +3 (Undefined) +4 Set point +5 (Undefined) Unit No. Channel 0 Channel 1 ~ ~ +16 Set point +17 (Undefined) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Set point (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. D D D +16 Channel 7 Set point (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +17 Not used --- Receive Data Word Allocation (4th Operand of PMCR(260)) None. 268 Appendix F E5ZE Temperature Controller Write Protocol Note When the setting unit for the set point is 0.1 (5 digits), use Write Set Point (Setting Unit 0.1), Sequence No.151. Write Set Point (Setting Unit 0.1) (Sequence No. 151 (Hex 0097)) Writes the set points using a setting unit of 0.1 (5 digits). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Set point (rightmost 4 digits) +3 Set point (leftmost 1 digit) +4 Set point (rightmost 4 digits) +5 Set point (leftmost 1 digit) ~ Channel 0 Channel 1 ~ +16 Set point (rightmost 4 digits) +17 Set point (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Set point (rightmost 4 digits) (4 digits BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. +3 Channel 0 Set point (leftmost 1 digit) (1 digit BCD) D D D +16 Channel 7 Set point (rightmost 4 digits) (4 digits BCD) +17 Channel 7 Set point (rightmost 1 digit) (1 digit BCD) Varies according to the temperature sensor type. Refer to the manual for the E5ZE. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence No.150. 269 Appendix F E5ZE Temperature Controller Write Protocol Write Proportional Band, Integral Time, and Derivative Time (Sequence No. 152 (Hex 0098)) Writes the proportional bands (constant P), integral times (constant I), and derivative times (constant D). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 +2 Constant P +3 Constant I +4 Constant D Unit No. Channel 0 ~ ~ +23 Constant P +24 Constant I +25 Constant D Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 001A (0026 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Constant P (4 digits BCD) 0000 to 9999 +3 Channel 0 Constant I (4 digits BCD) 0000 to 3999 +4 Channel 0 Constant D (4 digits BCD) 0000 to 3999 D D D +23 Channel 7 Constant P (4 digits BCD) 0000 to 9999 +24 Channel 7 Constant I (4 digits BCD) 0000 to 3999 +25 Channel 7 Constant D (4 digits BCD) 0000 to 3999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 270 Appendix F E5ZE Temperature Controller Write Protocol Write Control Period (Sequence No. 153 (Hex 0099)) Writes the control periods and cooling control periods. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Control period +3 Cooling control period +4 Control period +5 Cooling control period ~ Channel 1 ~ +16 Control period +17 Cooling control period Offset Channel 0 Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Control period (4 digits BCD) 0001 to 0099 +3 Channel 0 Cooling control period (4 digits BCD) 0001 to 0099 +4 Channel 1 Control period (4 digits BCD) 0001 to 0099 +5 Channel 1 Cooling control period (4 digits BCD) 0001 to 0099 D D D +16 Channel 7 Control period (4 digits BCD) 0001 to 0099 +17 Channel 7 Cooling control period (4 digits BCD) 0001 to 0099 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 271 Appendix F E5ZE Temperature Controller Write Protocol Write Output Mode (Sequence No. 154 (Hex 009A)) Writes the output mode (normal/reverse). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Write code Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (2 digits Hex) 00 to FF Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Alarm Mode (Sequence No. 155 (Hex 009B)) Writes the alarm modes for alarm 1 and alarm 2. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Alarm 1 set code +3 (Undefined) Alarm 2 set code +4 (Undefined) Alarm 1 set code +5 (Undefined) Alarm 2 set code ~ Channel 0 Channel 1 ~ +16 (Undefined) Alarm 1 set code +17 (Undefined) alarm 2 set code Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set code (2 digits Hex) 00 to 0C +3 Channel 0 Alarm 2 set code (2 digits Hex) 00 to 0C +4 Channel 1 Alarm 1 set code (2 digits Hex) 00 to 0C +5 Channel 1 Alarm 2 set code (2 digits Hex) 00 to 0C D D D +16 Channel 7 Alarm 1 set code (2 digits Hex) 00 to 0C +17 Channel 7 Alarm 2 set code (2 digits Hex) 00 to 0C Receive Data Word Allocation (4th Operand of PMCR(260)) None. 272 Appendix F E5ZE Temperature Controller Write Protocol Write Alarm Temperature (Setting Unit 1) (Sequence No. 156 (Hex 009C)) Writes the alarm temperatures using a setting unit of 1 (4 digits) Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Alarm 1 set value +3 (Undefined) +4 Alarm 2 set value +5 (Undefined) ~ Channel 0 ~ Alarm 1 set value +30 +31 (Undefined) +32 Alarm 2 set value +33 (Undefined) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0022 (0034 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set value (4 digits BCD) 0000 to 9999 +3 Not used +4 Channel 0 Alarm 2 set value (4 digits BCD) +5 Not used 0000 to 9999 D D D +32 Channel 7 Alarm 2 set value (4 digits BCD) +33 Not used 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 273 Appendix F E5ZE Temperature Controller Write Protocol Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157 (Hex 009D)) Writes the alarm temperatures using a setting unit of 0.1 (5 digits) Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Alarm 1 set value (rightmost 4 digits) +3 Alarm 1 set value (leftmost 1 digit) +4 Alarm 2 set value (rightmost 4 digits) +5 Alarm 2 set value (leftmost 1 digit) ~ +30 Channel 0 ~ Alarm 1 set value (rightmost 4 digits) +31 Alarm 1 set value (leftmost 1 digit) +32 Alarm 2 set value (rightmost 4 digits) +33 Alarm 2 set value (leftmost 1 digit) Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0022 (0034 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Alarm 1 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +3 Channel 0 Alarm 1 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 +4 Channel 0 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +5 Channel 0 Alarm 2 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 D D D +32 Channel 7 Alarm 2 set value (rightmost 4 digits) (4 digits BCD) 0000 to 9999 +33 Channel 7 Alarm 2 set value (leftmost 1 digits) (4 digits BCD) 0000 to 0009 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 274 Appendix F E5ZE Temperature Controller Write Protocol Write Hysteresis (Sequence No. 158 (Hex 009E)) Writes the hysteresis for control outputs for ON/OFF control. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Hysteresis +3 Cooling hysteresis +4 Hysteresis +5 Cooling hysteresis Channel 0 Channel 1 ~ ~ +16 Hysteresis +17 Cooling hysteresis Offset Channel 7 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Hysteresis (4 digits BCD) 0000 to 0999 +3 Channel 0 Cooling hysteresis (4 digits BCD) 0000 to 0999 +4 Channel 1 Hysteresis (4 digits BCD) 0000 to 0999 +5 Channel 1 Cooling hysteresis (4 digits BCD) 0000 to 0999 D D D +16 Channel 7 Hysteresis (4 digits BCD) 0000 to 0999 +17 Channel 7 Cooling hysteresis (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Start Autotuning (Sequence No. 159 (Hex 009F)) Starts autotuning (AT). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 (Undefined) +2 Offset Unit No. Channel Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel (Channel) No. (1 digit BCD) 0 to 7 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 275 Appendix F E5ZE Temperature Controller Write Protocol Cancel Autotuning (Sequence No. 160 (Hex 00A0)) Cancels Autotuning (AT) for all channels. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Setting Unit (Sequence No. 161 (Hex 00A1)) Writes the setting unit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Write code +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (4 digits BCD) 0000: unit of 1 0001: unit of 0.1 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Input Shift Value (Sequence No. 162 (Hex 00A2)) Writes the input shift values. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data 276 +0 +1 Number of send data words (Undefined) Unit No. +2 Input shift value Channel 0 +3 Input shift value Channel 1 +4 Input shift value Channel 2 +5 Input shift value Channel 3 +6 Input shift value Channel 4 +7 Input shift value Channel 5 +8 Input shift value Channel 6 +9 Input shift value Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 000A (000A decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Input shift value (4 digits BCD) 0000 to 0999 +3 Channel 1 Input shift value (4 digits BCD) 0000 to 0999 +4 Channel 2 Input shift value (4 digits BCD) 0000 to 0999 D D D +8 Channel 6 Input shift value (4 digits BCD) 0000 to 0999 +9 Channel 7 Input shift value (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Manual Reset Value (Sequence No. 163 (Hex 00A3)) Writes the manual reset values. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Manual reset value Channel 0 +3 Manual reset value Channel 1 +4 Manual reset value Channel 2 +5 Manual reset value Channel 3 +6 Manual reset value Channel 4 +7 Manual reset value Channel 5 +8 Manual reset value Channel 6 +9 Manual reset value Channel 7 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 000A (0010 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Manual reset value (4 digits BCD) 0000 to 1000 +3 Channel 1 Manual reset value (4 digits BCD) 0000 to 1000 +4 Channel 2 Manual reset value (4 digits BCD) 0000 to 1000 D D D +8 Channel 6 Manual reset value (4 digits BCD) 0000 to 1000 +9 Channel 7 Manual reset value (4 digits BCD) 0000 to 1000 277 Appendix F E5ZE Temperature Controller Write Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Ramp Value (Sequence No. 164 (Hex 00A4)) Writes the ramp values. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. (Undefined) +2 Ramp value Time unit +3 (Undefined) +4 Ramp value Time unit +5 Channel 0 (Undefined) Channel 1 (Undefined) ~ ~ (Undefined) +16 Ramp value Time unit +17 Offset Channel 7 (Undefined) Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Ramp value (3 digits BCD) 000 to 999 +3 Channel 0 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours +4 Channel 1 Ramp value (3 digits BCD) 000 to 999 +5 Channel 1 Time unit (one ASCII character) S: Second M: Minute H: Hour D D D +16 Channel 7 Ramp value (3 digits BCD) 000 to 999 +17 Channel 7 Time unit (one ASCII character) S: Seconds; M: Minutes; H: Hours Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Manual Output Value (Sequence No. 165 (Hex 00A5)) Writes the manual output values for control output in manual operation. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 Output value +3 Cooling output value +4 Output value +5 Cooling output value ~ 278 Channel 0 Channel 1 ~ +16 Output value +17 Cooling output value Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output value (4 digits BCD) 0000 to 1000 +3 Channel 0 Cooling output value (4 digits BCD) 0000 to 1000 +4 Channel 1 Output value (4 digits BCD) 0000 to 1000 +5 Channel 1 Cooling output value (4 digits BCD) 0000 to 1000 D D D +16 Channel 7 Output value (4 digits BCD) 0000 to 1000 +17 Channel 7 Cooling output value (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Output Value Limit (Sequence No. 166 (Hex 00A6)) Writes the output value limits that restrict the values of the control outputs. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 +2 Number of send data words (Undefined) Unit No. Output value lower limit +3 Output value upper limit +4 Cooling output value lower limit +5 Cooling output value upper limit ~ Channel 0 ~ +30 Output value lower limit +31 Output value upper limit +32 Cooling output value lower limit +33 Cooling output value upper limit Channel 7 279 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0022 (0034 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output value lower limit (4 digits BCD) 0000 to 1000 +3 Channel 0 Output value upper limit (4 digits BCD) 0000 to 1000 +4 Channel 0 Cooling output value lower limit (4 digits BCD) 0000 to 1000 +5 Channel 0 Cooling output value upper limit (4 digits BCD) 0000 to 1000 D D D +32 Channel 7 Cooling output value lower limit (4 digits BCD) 0000 to 1000 +33 Channel 7 Cooling output value upper limit (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Output Value Change Rate Limit (Sequence No. 167 (Hex 00A7)) Writes the output value change rate limits that restrict the rates of change in the control value output. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data 280 +0 +1 Number of send data words (Undefined) Unit No. +2 Output change rate limit Channel 0 +3 Output change rate limit Channel 1 +4 Output change rate limit Channel 2 +5 Output change rate limit Channel 3 +6 Output change rate limit Channel 4 +7 Output change rate limit Channel 5 +8 Output change rate limit Channel 6 +9 Output change rate limit Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 000A (0010 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Output change rate limit (4 digits BCD) 0000 to 1000 +3 Channel 1 Output change rate limit (4 digits BCD) 0000 to 1000 +4 Channel 2 Output change rate limit (4 digits BCD) 0000 to 1000 D D D +8 Channel 6 Output change rate limit (4 digits BCD) 0000 to 1000 +9 Channel 7 Output change rate limit (4 digits BCD) 0000 to 1000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Save Settings (Sequence No. 168 (Hex 00A8)) Saves the settings. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. Initialize Settings (Sequence No. 169 (Hex 00A9)) Initializes all the settings to the factory defaults. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. 281 Appendix F E5ZE Temperature Controller Write Protocol Write HB and HS Alarm Valid Channels (Sequence No. 170 (Hex 00AA)) Writes the valid or invalid channels of HB alarm and HS alarm. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Unit No. +2 (Undefined) Write code Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Write code (2 digits Hex) 00 to FF Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Heater Burnout and SSR Failure Detection Current (Sequence No. 171 (Hex 00AB)) Writes the currents for detecting heater burnouts and SSR failures. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 Heater burnout detection current +3 SSR failure detection current +4 Heater burnout detection current +5 SSR failure detection current ~ 282 Channel 0 Channel 1 ~ +16 Heater burnout detection current +17 SSR failure detection current Channel 7 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0012 (0018 decimal) (fixed) +1 +2 Unit No. (2 digits Hex) Channel 0 Heater burnout detection current (4 digits BCD) 00 to 0F 0000 to 0500 +3 Channel 0 SSR failure detection current (4 digits BCD) 0000 to 0500 +4 Channel 1 Heater burnout detection current (4 digits BCD) 0000 to 0500 +5 Channel 1 SSR failure detection current (4 digits BCD) 0000 to 0500 D D D +16 Channel 7 Heater burnout detection current (4 digits BCD) 0000 to 0500 +17 Channel 7 SSR failure detection current (4 digits BCD) 0000 to 0500 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Dead Band/Overlap Band (Sequence No. 172 (Hex 00AC)) Writes the dead bands or overlap bands for control outputs during heating/cooling control. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 Dead band/overlap band Channel 0 +3 Dead band/overlap band Channel 1 +4 Dead band/overlap band Channel 2 +5 Dead band/overlap band Channel 3 +6 Dead band/overlap band Channel 4 +7 Dead band/overlap band Channel 5 +8 Dead band/overlap band Channel 6 +9 Dead band/overlap band Channel 7 283 Appendix F E5ZE Temperature Controller Write Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 000A (0010 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Dead band/overlap band (4 digits BCD) 0000 to 0999 +3 Channel 1 Dead band/overlap band (4 digits BCD) 0000 to 0999 +4 Channel 2 Dead band/overlap band (4 digits BCD) 0000 to 0999 D D D +8 Channel 6 Dead band/overlap band (4 digits BCD) 0000 to 0999 +9 Channel 7 Dead band/overlap band (4 digits BCD) 0000 to 0999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Cooling Coefficient (Sequence No. 173 (Hex 00AD)) Writes the cooling coefficients for the cooling proportional bands for heating/cooling control. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. +2 Cooling coefficient Channel 0 +3 Cooling coefficient Channel 1 +4 Cooling coefficient Channel 2 +5 Cooling coefficient Channel 3 +6 Cooling coefficient Channel 4 +7 Cooling coefficient Channel 5 +8 Cooling coefficient Channel 6 +9 Cooling coefficient Channel 7 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 000A (0010 decimal) (fixed) +1 Unit No. (2 digits Hex) 00 to 0F +2 Channel 0 Cooling coefficient (4 digits BCD) 0000 to 0100 +3 Channel 1 Cooling coefficient (4 digits BCD) 0000 to 0100 +4 Channel 2 Cooling coefficient (4 digits BCD) 0000 to 0100 D D D 284 +8 Channel 6 Cooling coefficient (4 digits BCD) 0000 to 0100 +9 Channel 7 Cooling coefficient (4 digits BCD) 0000 to 0100 Appendix F E5ZE Temperature Controller Write Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Start Control (Sequence No. 174 (Hex 00AE)) Starts temperature control for all channels in the specified Unit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. Stop Operation or Control (Sequence No. 175 (Hex 00AF)) Stops temperature control or manual operation for all channels of the specified Unit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. Start Manual Operation (Sequence No. 176 (Hex 00B0)) Starts manual operation based on the output values that were set for all channels of the specified Unit. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits Hex) 00 to 0F Receive Data Word Allocation (4th Operand of PMCR(260)) None. 285 Appendix G E5jJ Temperature Controller Protocol The E5jJ Temperature Controller Protocol performs various settings and controls in remote mode for the Temperature Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The following table shows the structure of the E5jJ Temperature Controller Protocol. Sequence No. Communications sequence name Function 200 (00C8) Select remote mode Switches the Controller to remote mode. 201 (00C9) Select local mode 202 (00CA) Select backup mode 203 (00CB) 204 (00CC) Select RAM write mode Save set point 205 (00CD) Write parameters 1 206 (00CE) Write parameters 2 207 (00CF) Write input shift value 208 (00D0) Read parameters 1 209 (00D1) Read parameters 2 210 (00D2) Read input shift value 211 (00D3) Read output value 212 (00D4) Read process value 213 (00D5) Read set point limit 214 (00D6) Read heater current 215 (00D7) Read initial status 216 (00D8) General-purpose write 217 (00D9) General-purpose read Ladder interface Send word allocation Yes Receive word allocation No Switches the Controller to local mode. Yes No Switches from set point write mode to backup mode. Switches from set point write mode to RAM write mode. Saves the set point. Yes No Yes No Yes No Writes the set point, alarm value 1, alarm value 2, and heater burnout alarm value. Writes the proportional band, integral time, and derivative time. Writes the input shift value. Yes No Yes No Yes No Reads the set point, alarm value 1, alarm value 2, and heater burnout alarm value. Reads the proportional band, integral time, and derivative time. Reads the input shift value and writes it in IOM. Reads the output value and stores it in IOM. Yes Yes Yes Yes Yes Yes Yes Yes Reads the process value and stores it in IOM. Reads the set point limits and stores them in IOM. Reads the heater current and stores it in IOM. Reads the initial status and stores it in IOM. Yes Yes Yes Yes Yes Yes Yes Yes Writes the specified parameter by setting a header code. Reads the specified parameter by setting a header code. Yes No Yes Yes Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd or 4th operands of PMCR. NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 287 Appendix G E5jJ Temperature Controller Protocol Connections The connections for using the E5jJ Temperature Controller Protocol are shown below. RS-232C Connections CS1j E5jJ Serial Communications Unit/Board RS-232C port → RS-232C Signal name Abbreviation Signal direction Pin No. Signal ground or common return line Send data SG --- 25, 27 SD Output 26 Receive data RD Input 28 Serial Communications Unit/Board RS-232C: D-sub 9-pin female Signal name FG SG SD RD RTS CTS E5AJ RS-232C: Terminal Block Pin No. Termi- Signal name nal Shield MAX232C or equivalent SG SG SD RD TX RX DSR DTR Note 1. The connection configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use shielded twisted-pair cable. RS-422A/485 Connections CS1j E5jJ Serial Communications Board RS-422A/485 port → RS-422A.485 E5jJ → RS-422A.485 Up to 32 units can be connected. E5jJ → RS-422A.485 288 Appendix G E5jJ Temperature Controller Protocol • RS-422A 4-wire connections Signal name Abbreviation Signal direction Pin No. Send data A SDA Output 26 Send data B SDB Output 25 Receive data A RDA Input 28 Receive data B RDB Input 29 Signal ground SG --- 27 Serial Communications Board RS-422A: D-sub 9-pin female E5AJ Signal Pin name No. SN751177N or equivalent Terminating resistance RS-422A: Terminal Block Termi- Signal nal name Shell Terminating resistance 240 Ω E5AJ Shield *1: Set the 2-/4-wire switch to the 4-wire setting. Terminating resistance (240 Ω) is connected via the terminator switch. RS-422A: Terminal Block Shield *2: Turn ON the terminating resistance switch. Termi- Signal nal name Terminator switch • RS-485 2-wire Connections Signal name Abbreviation Signal Pin name No. Shell Pin No. Terminal A A I/O 26, 28 Terminal B B I/O 25, 29 Signal ground SG --- 27 SN751177N or equivalent Serial Communications Board RS-485: D-sub 9-pin female Signal direction E5AJ Terminating resistance RS-485: Terminal Block Termi-Signal nal name SDA SDB Shield Terminating resistance (240 Ω) is connected via the terminator switch. *1: Set the 2-/4-wire switch to the 2-wire setting. *2: Turn ON the terminating resistance switch. E5AJ Terminator switch RS-485: Terminal Block Shield Termi- Signal name nal 289 Appendix G E5jJ Temperature Controller Protocol Note 1. The connection configuration is a one-to-one or a one-to-N configuration. Using a one-to-N configuration, up to 32 units can be connected including the Serial Communications Boards. 2. The maximum cable length is 500 m. Use shielded twisted-pair cable. 3. Connect terminating resistance to the devices only at both ends of the transmission path. 4. The total terminating resistance at both ends must be at least 100 Ω for RS-422A or 54 Ω for RS-485. Select Remote Mode (Sequence No. 200 (Hex 00C8)) Switches the Controller to remote mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Select Local Mode (Sequence No. 201 (Hex 00C9)) Switches the Controller to local mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Select Backup Mode (Sequence No. 202 (Hex 00CA)) Switches from the set point write mode to backup mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 290 Data +0 Appendix G E5jJ Temperature Controller Protocol Select RAM Write Mode (Sequence No. 203 (Hex 00CB)) Switches from set point write mode to RAM write mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Save Set Point (Sequence No. 204 (Hex 00CC)) Saves the set point. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Parameters 1 (Sequence No. 205 (Hex 00CD)) Writes the set point, alarm value 1, alarm value 2, and a heater burnout alarm value to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 +2 Number of send data words Number of units (Undefined) Unit No. +3 set point +4 Alarm value 1 +5 Alarm value 2 +6 Heater burnout alarm value ~ +122 1st unit ~ (Undefined) Unit No. +123 set point +124 Alarm value 1 +125 Alarm value 2 +126 Heater burnout alarm value 25th unit (max.) 291 Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 5 + 2 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Set point (4 digits BCD) 0000 to 9999 +4 1st unit Alarm value 1 (4 digits BCD) 0000 to 9999 +5 1st unit Alarm value 2 (4 digits BCD) 0000 to 9999 +6 1st unit Heater burnout alarm value 2 (4 digits BCD) 0000 to 9999 +7 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +126 (max.) 25th unit Heater burnout alarm value 2 (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Parameters 2 (Sequence No. 206 (Hex 00CE)) Writes the proportional bands, integral times, and derivative times to multiple units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 +3 (Undefined) Unit No. Proportional band +4 Integral time +5 Derivative time ~ +122 292 1st unit ~ (Undefined) Unit No. +123 Proportional band +124 Integral time +125 Derivative time 31th unit (max.) Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 4 + 2 +1 +2 +3 Number of units (4 digits Hex) 1st unit Unit No. (2 digits BCD) 1st unit Proportional band (4 digits BCD) 0001 to 001F (1 to 31 decimal) 00 to 31 0000 to 9999 +4 1st unit Integral time (4 digits BCD) 0000 to 9999 +5 1st unit Derivative time (4 digits BCD) 0000 to 9999 +6 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +125 (max.) 31th unit Derivative time (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Input Shift Value (Sequence No. 207 (Hex 00CF)) Writes the input shift value. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Input shift value +2 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Input shift value (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None 293 Appendix G E5jJ Temperature Controller Protocol Read Parameters 1 (Sequence No. 208 (Hex 00D0)) Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. ~ ~ (Undefined) +26 Offset (max.) Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point +2 Alarm value 1 +3 Alarm value 2 +4 Heater burnout alarm value ~ 294 1st unit ~ +97 Set point +98 Alarm value 1 +99 Alarm value 2 +100 Heater burnout alarm value 25th unit (max.) Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 4 + 1 +1 1st unit Set point (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 1st unit Alarm value 1 (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +3 1st unit Alarm value 2 (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +4 1st unit Heater burnout alarm value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +5 2nd unit Set point (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. D D D +100 (max.) 25th unit Heater burnout alarm value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Parameters 2 (Sequence No. 209 (Hex 00D1)) Reads the proportional bands, integral times, and derivative times for multiple units and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. (Undefined) Unit No. ~ +32 ~ Offset (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units+ 2 +1 Number of units (4 digits Hex) 0001 to 001F (1 to 31 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +32 (max.) 31th unit Unit No. (2 digits BCD) 00 to 31 295 Appendix G E5jJ Temperature Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Proportional band +2 Integral time +3 Derivative time 1st unit ~ ~ +91 Proportional band +92 Integral time +93 Derivative time Offset 31th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 3 + 1 +1 1st unit Proportional band (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 1st unit Integral time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +3 1st unit Derivative time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +4 2nd unit Proportional band (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. D D D +93 (max.) 31th unit Derivative time (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Input Shift Value (Sequence No. 210 (Hex 00D2)) Reads the input shift value and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Input shift value Offset 296 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Input shift value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Appendix G E5jJ Temperature Controller Protocol Read Output Value (Sequence No. 211 (Hex 00D3)) Reads the output value and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Output value Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 +1 Output value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Process Value (Sequence No. 212 (Hex 00D4)) Reads the process value and status data and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Process value +2 Status data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Process value (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Status data (4 digits Hex) 0000 to 9999 Read Set Point Limit (Sequence No. 213 (Hex 00D5)) Reads the set point limits and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. 297 Appendix G E5jJ Temperature Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set point lower limit +2 Set point upper limit Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Set point lower limit (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Set point upper limit (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Read Heater Current (Sequence No. 214 (Hex 00D6)) Reads the heater current and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Heater current +2 Status data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Heater current (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. +2 Status data (4 digits Hex) 0000 to 0011 Read Initial Status (Sequence No. 215 (Hex 00D7)) Reads the initial status and stores the results in the specified word. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset 298 Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix G E5jJ Temperature Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 +2 (Undefined) Offset Status Alarm 1 type Alarm 2 type Input type Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 +1 Status (2 digits Hex) 00 to 99 +2 Alarm 1 type (1 digit Hex) Alarm 2 type (1 digit Hex) Input type (1 digit BCD) 0 to 9 0 to 9 0 to 9 General-purpose Write (Sequence No. 216 (Hex 00D8)) Writes the parameter specified by setting a header code. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. Header code (ASC) +2 (Undefined) +3 Data code Send data +4 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Header code (two ASCII characters) Header codes that can be set MB, WS, W%, WW, WB, WN, WV +3 Data code (2 digits BCD) 01 to 02 +4 Write data (4 digits BCD) 0000 to 9999 Receive Data Word Allocation (4th Operand of PMCR(260)) None. General-purpose Read (Sequence No. 217 (Hex 00D9)) Reads the parameter specified by setting a header Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Unit No. Header code (ASC) +2 (Undefined) +3 Offset Data code Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 Header code (two ASCII characters) Header codes that can be set RS, R%, RW, RB, RN, RV, RO +3 Data code (2 digits BCD) 01 to 02 299 Appendix G E5jJ Temperature Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data Offset Contents (data format) Number of receive data words (4 digits Hex) 0002 +1 Read data (4 digits BCD) 0000 to 9999 When the left digit is –1, A is set and when it is –, F is set. Note The completion code is not included in the read data. 300 Data +0 Appendix H ES100j Digital Controller Protocol The ES100j Digital Controller Protocol controls in remote mode and reads various settings from the Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable. Note Negative values cannot be written. All values must be set as unsigned BCD. Structure of the Protocol The structure of the ES100j Digital Controller Protocol is shown below. Sequence No. 250 (00FA) Transmission sequence name Read event data 251 (00FB) Read time signals 252 (00FC) Read error detection data 253 (00FD) Read heater burnout data 254 (00FE) Read PV data Function Ladder interface Send word allocation Yes Receive word allocation Yes Reads time signals 1 to 10 in the variable area. Reads error groups 1 to 15 in the variable area. Reads the heater burnout alarm. Yes Yes Yes Yes Yes Yes Reads PV data in the variable area. Yes Yes Reads events 1 to 10 in the variable area. 255 (00FF) Read SP data Reads SP data in the variable area. Yes Yes 256 (0100) Read MV Reads the MV in the variable area. Yes Yes 257 (0101) Read control monitor data Read adjustment parameters Write adjustment parameters Read PID control parameters 1 Reads control monitor data (SP, PV, and MV) in the variable area. Reads adjustment parameters in the parameter area. Writes adjustment parameters in the parameter area. Reads PID parameters No. 1 to 4 from the PID control parameters in the parameter area. Yes Yes Yes Yes Yes No Yes Yes 261 (0105) Read PID control parameters 2 Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area. Yes Yes 262 (0106) No Yes No Yes Yes 265 (0109) Write local SP Yes No 266 (010A) Read program parameters Writes PID parameters No. 1 to 4 from PID control parameters in the parameter area. Writes PID parameters No. 5 to 8 from PID control parameters in the parameter area. Reads the local SP in the program parameter area. Writes local SP in the program parameter area. Reads local SP, step time, PID No. wait code, and events 1 to 10 set values in the program parameter area. Yes 264 (0108) Write PID control parameters 1 Write PID control parameters 2 Read local SP Yes Yes 267 (010B) Write program parame- Writes the local SP, step time, PID No., wait ters code, and event 1 to 10 set values in the program parameter area. Yes No 258 (0102) 259 (0103) 260 (0104) 263 (0107) 268 (010C) Remote setting mode Switches the setting mode to remote setting. Yes No 269 (010D) Local setting mode Switches the setting mode to local setting. Yes No 270 (010E) External setting mode Yes No 271 (010F) Run command Switches the setting mode to external setting. Starts control. Yes No 272 (0110) Reset (stop) Stops control. Yes No 301 Appendix H ES100j Digital Controller Protocol Sequence No. Transmission sequence name Function Ladder interface Send word Receive word allocation allocation Yes No 273 (0111) Auto mode Switches the control mode to auto. 274 (0112) Manual mode Switches the control mode to a manual. Yes No 275 (0113) Execute A.T. Executes A.T. Yes No 276 (0114) Cancel A.T. Cancels A.T. Yes No 277 (0115) Change pattern No. Changes the pattern No. Yes No 278 (0116) Change bank No. Changes the bank No. Yes No 279 (0117) Read controller status Reads the controller status. Yes Yes 280 (0118) General-purpose command Sends specified data and stores the received data in the specified words. Yes Yes Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). Connections Connections for using the ES100j Digital Controller Protocol are shown below. RS-232C Connections ES100j CS1j Serial Communications Unit/ Board RS-232C port → Serial Communications Unit/Board ES100j-j01j RS-232C: D-sub 9-pin female Signal name RS-232C: Terminal Block Pin No. Terminal FG SD 17 SD RD 16 RD RTS 15 SG CTS DSR DTR SG Shield 302 Signal name Appendix H ES100j Digital Controller Protocol RS-422A/485 Connections ES100j CS1j Serial Communications Board (CS1W-SCB41) RS-422A/485 port → RS-422A/485 ES100j → RS-422A/485 Up to 32 units can be connected. ES100j → RS-422A/485 • RS-422A 4-wire Connections Serial Communications Board ES100j-j04j RS--422A Terminal Block RS-422A: D-sub 9-pin female Signal name Pin No. Shield Terminal Signal name *1: Set the 2-/4-wire switch to the 4-wire setting. Next ES100 *2: Turn ON the terminating resistance switch. • RS-485 2-wire Connections Serial Communications Board ES100j-j04j RS-485: D-sub 9-pin female Signal name Pin No. RS--485 Terminal Block Shield Terminal SDA SBA Shell Next ES100 *1: Set the 2-/4-wire switch to the 2-wire setting. *2: Turn ON the terminating resistance switch. 303 Appendix H ES100j Digital Controller Protocol Switch Settings There are two switches located on the board on the left of the Unit. Set SW1 to the interface: RS-422A or RS-485. Set SW2 to the center on all terminating Units and to the same setting as SW1 on all other Units. 422A← S →485 422A← S →485 Read Event Data (Sequence No. 250 (Hex 00FA)) Reads events 1 to 10 in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +26 ~ Offset 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Event 1 Event 2 +2 Event 3 Event 4 +3 Event 5 Event 6 +4 Event 7 Event 8 +5 Event 9 Event 10 ~ 304 1st unit ~ +121 Event 1 Event 2 +122 Event 3 Event 4 +123 Event 5 Event 6 +124 Event 7 Event 8 +125 Event 9 Event 10 25th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units x 5 + 1 +1 1st unit Event data 1 (2 digits Hex) Event data 2 (2 digits Hex) 00 to FF 00 to FF +2 1st unit Event data 3 (2 digits Hex) Event data 4 (2 digits Hex) 00 to FF 00 to FF +3 1st unit Event data 5 (2 digits Hex) Event data 6 (2 digits Hex) 00 to FF 00 to FF +4 1st unit Event data 7 (2 digits Hex) Event data 8 (2 digits Hex) 00 to FF 00 to FF +5 1st unit Event data 9 (2 digits Hex) Event data 10 (2 digits Hex) 00 to FF 00 to FF D D D +125 (max.) 25th unit Event data 9 (2 digits Hex) Event data 10 (2 digits Hex) 00 to FF 00 to FF Read Time Signal (Sequence No. 251 (Hex 00FB)) Reads time signals from 1 to 10 in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +26 1st unit Offset Unit No. 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 305 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Time signal 1 Time signal 2 +2 Time signal 3 Time signal 4 +3 Time signal 5 Time signal 6 +4 Time signal 7 Time signal 8 +5 Time signal 9 Time signal 10 +121 Time signal 1 Time signal 2 +122 Time signal 3 Time signal 4 +123 Time signal 5 Time signal 6 +124 Time signal 7 Time signal 8 +125 Time signal 9 Time signal 10 ~ 1st unit ~ Offset 25th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 5 + 1 +1 1st unit Time signal 1 data (2 digits Hex) Time signal 2 data (2 digits Hex) 00 to FF 00 to FF +2 1st unit Time signal 3 data (2 digits Hex) Time signal 4 data (2 digits Hex) 00 to FF 00 to FF +3 1st unit Time signal 5 data (2 digits Hex) Time signal 6 data (2 digits Hex) 00 to FF 00 to FF +4 1st unit Time signal 7 data (2 digits Hex) Time signal 8 data (2 digits Hex) 00 to FF 00 to FF +5 1st unit Time signal 9 data (2 digits Hex) Time signal 10 data (2 digits Hex) 00 to FF 00 to FF D D D +125 (max.) 25th unit Time signal 9 data (2 digits Hex) Time signal 10 data (2 digits Hex) 00 to FF 00 to FF Read Error Detection Data (Sequence No. 252 (Hex 00FC)) Reads error groups from 0 to 15 in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +17 306 ~ 16th unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0010 (1 to 16 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +17 (max.) 16th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Error group 0 Error group 1 +2 Error group 2 Error group 3 +3 Error group 4 Error group 5 +4 Error group 6 Error group 7 +5 Error group 8 Error group 9 +6 Error group 10 Error group 11 +7 Error group 12 Error group 13 Error group 14 Error group 15 Error group 14 Error group 15 +8 ~ +128 1st unit ~ Offset 16th unit (max.) Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 8 + 1 +1 1st unit Error group 0 data (2 digits Hex) Error group 1 data (2 digits Hex) 00 to FF 00 to FF +2 1st unit Error group 2 data (2 digits Hex) Error group 3 data (2 digits Hex) 00 to FF 00 to FF D D +7 1st unit Error group 12 data (2 digits Hex) Error group 13 data (2 digits Hex) 00 to FF 00 to FF +8 1st unit Error group 14 data (2 digits Hex) Error group 15 data (2 digits Hex) 00 to FF 00 to FF +9 2nd unit Error group 0 data (2 digits Hex) Error group 1 data (2 digits Hex) 00 to FF 00 to FF D D +128 (max.) 16th unit Error group 14 data (2 digits Hex) Error group 15 data (2 digits Hex) 00 to FF 00 to FF 307 Appendix H ES100j Digital Controller Protocol Read Heater Burnout Data (Sequence No. 253 (Hex 00FD)) Reads the heater burnout alarm in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit ~ ~ (Undefined) +33 Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 (Undefined) Heater burnout alarm 1st unit +2 (Undefined) Heater burnout alarm 2nd unit +3 (Undefined) Heater burnout alarm 3rd unit +4 (Undefined) Heater burnout alarm ~ 4th unit ~ (Undefined) +32 Offset Heater burnout alarm Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units +1 +1 1st unit Heater burnout alarm (2 digits Hex) 00 to FF +2 2nd unit Heater burnout alarm (2 digits Hex) 00 to FF +3 3rd unit Heater burnout alarm (2 digits Hex) 00 to FF +4 4th unit Heater burnout alarm (2 digits Hex) 00 to FF D D D +32 (max.) 308 32nd unit (max.) 32nd unit Heater burnout alarm (2 digits Hex) 00 to FF Appendix H ES100j Digital Controller Protocol Read PV Data (Sequence No. 254 (Hex 00FE)) Reads the PV data for the variable type “analog data” in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 PV data (rightmost 4 digits) +2 PV data (leftmost 4 digits) +3 PV data (rightmost 4 digits) +4 PV data (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 PV data (rightmost 4 digits) +64 PV data (leftmost 4 digits) 32nd unit 309 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 2 + 1 +1 1st unit PV data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit PV data (leftmost 4 digits) (4 digits BCD) +3 2nd unit PV data (rightmost 4 digits) (4 digits BCD) +4 2nd unit PV data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. D D D +63 32nd unit PV data (rightmost 4 digits) (4 digits BCD) +64 32nd unit PV data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read SP Data (Sequence No. 255 (Hex 00FF)) Reads the SP data for the variable type “analog data” in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 310 32nd unit Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 SP data (rightmost 4 digits) +2 SP data (leftmost 4 digits) +3 SP data (rightmost 4 digits) +4 SP data (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 SP data (rightmost 4 digits) +64 SP data (leftmost 4 digits) Offset 32nd unit Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 2 + 1 +1 1st unit SP data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit SP data (leftmost 4 digits) (4 digits BCD) +3 2nd unit SP data (rightmost 4 digits) (4 digits BCD) +4 2nd unit SP data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. D D D +63 32nd unit SP data (rightmost 4 digits) (4 digits BCD) +64 32nd unit SP data (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read MV Data (Sequence No. 256 (Hex 0100)) Reads the MV for the variable type “analog data” in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ 32nd unit (max.) 311 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 MV (rightmost 4 digits) +2 MV (leftmost 4 digits) +3 MV (rightmost 4 digits) +4 MV (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 MV (rightmost 4 digits) +64 MV (leftmost 4 digits) Offset 32nd unit Contents (data format) Data +0 Number of receive data words (4 digits Hex) Number of units 2 + 1 +1 1st unit MV (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit MV (leftmost 4 digits) (4 digits BCD) +3 2nd unit MV (rightmost 4 digits) (4 digits BCD) +4 2nd unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. D D D +63 32nd unit MV (rightmost 4 digits) (4 digits BCD) +64 32nd unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. Read Control Monitor Data (Sequence No. 257 (Hex 0101)) Reads the control monitor data (SP/PV/MV) in the variable area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words Number of units +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ +22 312 1st unit 2nd unit ~ (Undefined) Unit No. 21st unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0015 (1 to 21 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +22 (max.) 21st unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 SP data (rightmost 4 digits) +2 SP data (leftmost 4 digits) +3 PV data (rightmost 4 digits) +4 PV data (leftmost 4 digits) +5 MV (rightmost 4 digits) +6 MV (leftmost 4 digits) ~ 1st unit ~ +121 SP data (rightmost 4 digits) +122 SP data (leftmost 4 digits) +123 PV data (rightmost 4 digits) +124 PV data (leftmost 4 digits) +125 MV (rightmost 4 digits) +126 MV (leftmost 4 digits) Offset 21st unit Contents (data format) Data +0 1st unit Number of receive data words (4 digits Hex) Number of units 6 + 1 +1 1st unit SP data (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit SP data (leftmost 4 digits) (4 digits BCD) +3 1st unit PV data (rightmost 4 digits) (4 digits BCD) +4 1st unit PV data (leftmost 4 digits) (4 digits BCD) +5 1st unit MV (rightmost 4 digits) (4 digits BCD) +6 1st unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. 00000000 to 09999000 F indicates a negative number. D D D +125 21st unit MV (rightmost 4 digits) (4 digits BCD) +126 21st unit MV (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. 313 Appendix H ES100j Digital Controller Protocol Read Adjustment Parameters (Sequence No. 258 (Hex 0102)) Reads the adjustment parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset 314 Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 +2 +3 +4 +5 +6 +7 +8 +9 +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 +20 +21 +22 +23 +24 +25 Number of receive data words Fixed SP Control output 1 pulse cycle Control output 2 pulse cycle Fuzzy strength Cooling coefficient Heater burnout alarm setting Position-proportional dead band Switching output hysteresis ON/OFF count alarm setting ON/OFF control hysteresis Manual reset SP setting lower limit SP setting upper limit +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 SP rise rate limit SP fall rate limit MV rate-of-change limit Secondary loop fixed SP Secondary loop P (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) +36 (leftmost 4 digits) +37 (rightmost 4 digits) Secondary loop I +38 +39 Secondary loop D (leftmost 4 digits) (rightmost 4 digits) +40 (leftmost 4 digits) +41 (rightmost 4 digits) +42 Secondary loop manual reset (leftmost 4 digits) 315 Appendix H ES100j Digital Controller Protocol Offset 316 Contents (data format) Data +0 Number of receive data words (4 digits Hex) 002B (0043 decimal) +1 to 2 Fixed SP (8 digits BCD) +3 to 4 Control output 1 pulse cycle (8 digits BCD) 00000000 to 09999000 F indicates a negative number. +5 to 6 Control output 2 pulse cycle (8 digits BCD) +7 to 8 Fuzzy strength (8 digits BCD) +9 to 10 Cooling coefficient (8 digits BCD) +11 to 12 Heater burnout alarm setting (8 digits BCD) +13 to 14 Position-proportional dead band (8 digits BCD) +15 to 16 Switching output hysteresis (8 digits BCD) +17 to 18 ON/OFF count alarm setting (8 digits BCD) +19 to 20 ON/OFF control hysteresis (8 digits BCD) +21 to 22 Manual reset (8 digits BCD) +23 to 24 SP setting lower limit (8 digits BCD) +25 to 26 SP setting upper limit (8 digits BCD) +27 to 28 SP rise rate limit (8 digits BCD) +29 to 30 SP fall rate limit (8 digits BCD) +31 to 32 MV rate-of-change limit (8 digits BCD) +33 to 34 Secondary loop fixed SP (8 digits BCD) +35 to 36 Secondary loop P (8 digits BCD) +37 to 38 Secondary loop I (8 digits BCD) +39 to 40 Secondary loop D (8 digits BCD) +41 to 42 Secondary loop manual reset (8 digits BCD) Appendix H ES100j Digital Controller Protocol Write Adjustment Parameters (Sequence No. 259 (Hex 0103)) Writes the adjust parameters in the parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) +2 +3 Fixed SP +4 +5 Control output 1 pulse cycle +6 +7 Control output 2 pulse cycle +8 +9 Fuzzy strength +10 +11 +12 +13 +14 +15 +16 +17 +18 +19 Cooling coefficient Heater burnout alarm setting Position-proportional dead band Switching output hysteresis ON/OFF count alarm setting +20 +21 ON/OFF control hysteresis +22 +23 Manual reset +24 +25 +26 +27 +28 +29 +30 +31 +32 +33 +34 +35 +36 +37 +38 +39 +40 +41 +42 +43 SP setting lower limit SP setting upper limit SP rise rate limit SP fall rate limit MV change rate limit Secondary loop fixed SP Secondary loop P Secondary loop I Secondary loop D Secondary loop manual reset Unit No. (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) (rightmost 4 digits) (leftmost 4 digits) 317 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 002C (0044 decimal) (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 Fixed SP (8 digits BCD) 00000000 to 09999000 +4 to 5 Control output 1 pulse cycle (8 digits BCD) +6 to 7 Control output 2 pulse cycle (8 digits BCD) +8 to 9 Fuzzy strength (8 digits BCD) +10 to 11 Cooling coefficient (8 digits BCD) +12 to 13 Heater burnout alarm setting (8 digits BCD) +14 to 15 Position-proportional dead band (8 digits BCD) +16 to 17 Switching output hysteresis (8 digits BCD) +18 to 19 ON/OFF count alarm setting (8 digits BCD) value +20 to 21 ON/OFF control hysteresis (8 digits BCD) +22 to 23 Manual reset (8 digits BCD) +24 to 25 SP setting lower limit (8 digits BCD) +26 to 27 SP setting upper limit (8 digits BCD) +28 to 29 SP rise rate limit (8 digits BCD) +30 to 31 SP fall rate limit (8 digits BCD) +32 to 33 MV rate-of-change limit (8 digits BCD) +34 to 35 Secondary loop fixed SP (8 digits BCD) +36 to 37 Secondary loop P (8 digits BCD) +38 to 39 Secondary loop I (8 digits BCD) +40 to 41 Secondary loop D (8 digits BCD) +42 to 43 Secondary loop manual reset (8 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Read PID Control Parameters 1 (Sequence No. 260 (Hex 0104)) Reads PID parameters No. 1 to 4 from PID control parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset 318 Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 PID No. 1 P (rightmost 4 digits) +2 PID No. 1 P (leftmost 4 digits) +3 PID No. 1 I (rightmost 4 digits) +4 PID No. 1 I (leftmost 4 digits) +5 PID No. 1 D (rightmost 4 digits) +6 PID No. 1 D (leftmost 4 digits) +7 PID No. 1 MV lower limit (rightmost 4 digits) +8 PID No. 1 MV lower limit (leftmost 4 digits) +9 PID No. 1 MV upper limit (rightmost 4 digits) +10 PID No. 1 MV upper limit (leftmost 4 digits) +11 PID No. 1 PV bias value (rightmost 4 digits) +12 PID No. 1 PV bias value (leftmost 4 digits) +13 PID No. 1 Automatic selection range upper limit (rightmost 4 digits) PID No. 1 Automatic selection range upper limit +14 ~ (leftmost 4 digits) ~ +51 PID No. 4 MV upper limit (rightmost 4 digits) +52 PID No. 4 MV upper limit (leftmost 4 digits) +53 PID No. 4 PV bias value (rightmost 4 digits) +54 PID No. 4 PV bias value (leftmost 4 digits) +55 PID No. 4 Automatic selection range upper limit (rightmost 4 digits) +56 PID No. 4 Automatic selection range upper limit (leftmost 4 digits) Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0039 (0057 decimal) +1 to 2 PID No. 1 P (8 digits BCD) 00000000 to 09999000 +3 to 4 PID No. 1 I (8 digits BCD) +5 to 6 PID No. 1 D (8 digits BCD) +7 to 8 PID No. 1 MV lower limit (8 digits BCD) +9 to 10 PID No. 1 MV upper limit (8 digits BCD) +11 to 12 PID No. 1 PV bias value (8 digits BCD) +13 to 14 PID No. 1 Automatic selection range upper limit (8 digits BCD) D D D +43 to 44 PID No. 4 P (8 digits BCD) +45 to 46 PID No. 4 I (8 digits BCD) +47 to 48 PID No. 4 D (8 digits BCD) +49 to 50 PID No. 4 MV lower limit (8 digits BCD) +51 to 52 PID No. 4 MV upper limit (8 digits BCD) +53 to 54 PID No. 4 PV bias value (8 digits BCD) +55 to 56 PID No. 4 Automatic selection range upper limit (8 digits BCD) 319 Appendix H ES100j Digital Controller Protocol Read PID Control Parameters 2 (Sequence No. 261 (Hex 0105)) Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 PID No. 5 P (rightmost 4 digits) +2 PID No. 5 P (leftmost 4 digits) +3 PID No. 5 I (rightmost 4 digits) +4 PID No. 5 I (leftmost 4 digits) +5 PID No. 5 D (rightmost 4 digits) +6 PID No. 5 D (leftmost 4 digits) +7 PID No. 5 MV lower limit (rightmost 4 digits) +8 PID No. 5 MV lower limit (leftmost 4 digits) +9 PID No. 5 MV upper limit (rightmost 4 digits) +10 PID No. 5 MV upper limit (leftmost 4 digits) +11 PID No. 5 PV bias value (rightmost 4 digits) +12 PID No. 5 PV bias value (leftmost 4 digits) +13 PID No. 5 Automatic selection range upper limit (rightmost 4 digits) +14 PID No. 5 Automatic selection range upper limit (leftmost 4 digits) ~ 320 ~ +51 PID No. 8 MV upper limit (rightmost 4 digits) +52 PID No. 8 MV upper limit (leftmost 4 digits) +53 PID No. 8 PV bias value (rightmost 4 digits) +54 PID No. 8 PV bias value (leftmost 4 digits) +55 PID No. 8 Automatic selection range upper limit (rightmost 4 digits) +56 PID No. 8 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0039 (0057 decimal) +1 to 2 PID No. 5 P (8 digits BCD) 00000000 to 09999000 +3 to 4 PID No. 5 I (8 digits BCD) +5 to 6 PID No. 5 D (8 digits BCD) +7 to 8 PID No. 5 MV lower limit (8 digits BCD) +9 to 10 PID No. 5 MV upper limit (8 digits BCD) +11 to 12 PID No. 5 PV bias value (8 digits BCD) +13 to 14 PID No. 5 Automatic selection range upper limit (8 digits BCD) D D D +43 to 44 PID No. 8 P (8 digits BCD) +45 to 46 PID No. 8 I (8 digits BCD) +47 to 48 PID No. 8 D (8 digits BCD) +49 to 50 PID No. 8 MV lower limit (8 digits BCD) +51 to 52 PID No. 8 MV upper limit (8 digits BCD) +53 to 54 PID No. 8 PV bias value (8 digits BCD) +55 to 56 PID No. 8 Automatic selection range upper limit (8 digits BCD) 321 Appendix H ES100j Digital Controller Protocol Write PID Control Parameters 1 (Sequence No. 262 (Hex 0106)) Writes PID parameters No. 1 to 4 to the PID control parameters in the parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 Number of send data words (Undefined) Unit No. +2 PID No. 1 P (rightmost 4 digits) +3 PID No. 1 P (leftmost 4 digits) +4 PID No. 1 I (rightmost 4 digits) +5 PID No. 1 I (leftmost 4 digits) +6 PID No. 1 D (rightmost 4 digits) +7 PID No. 1 D (leftmost 4 digits) +8 PID No. 1 MV lower limit (rightmost 4 digits) +9 PID No. 1 MV lower limit (leftmost 4 digits) +10 PID No. 1 MV upper limit (rightmost 4 digits) +11 PID No. 1 MV upper limit (leftmost 4 digits) +12 PID No. 1 PV bias value (rightmost 4 digits) +13 PID No. 1 PV bias value (leftmost 4 digits) +14 PID No. 1 Automatic selection range upper limit (rightmost 4 digits) +15 PID No. 1 Automatic selection range upper limit (leftmost 4 digits) ~ 322 ~ +52 PID No. 4 MV upper limit (rightmost 4 digits) +53 PID No. 4 MV upper limit (leftmost 4 digits) +54 PID No. 4 PV bias value (rightmost 4 digits) +55 PID No. 4 PV bias value (leftmost 4 digits) +56 PID No. 4 Automatic selection range upper limit (rightmost 4 digits) +57 PID No. 4 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 003A (0058 decimal) (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 PID No. 1 P (8 digits BCD) 00000000 to 09999000 +4 to 5 PID No. 1 I (8 digits BCD) +6 to 7 PID No. 1 D (8 digits BCD) +8 to 9 PID No. 1 MV lower limit (8 digits BCD) +10 to 11 PID No. 1 MV upper limit (8 digits BCD) +12 to 13 PID No. 1 PV bias value (8 digits BCD) +14 to 15 PID No. 1 Automatic selection range upper limit (8 digits BCD) D D D +44 to 45 PID No. 4 P (8 digits BCD) +46 to 47 PID No. 4 I (8 digits BCD) +48 to 49 PID No. 4 D (8 digits BCD) +50 to 51 PID No. 4 MV lower limit (8 digits BCD) +52 to 53 PID No. 4 MV upper limit (8 digits BCD) +54 to 55 PID No. 4 PV bias value (8 digits BCD) +56 to 57 PID No. 4 Automatic selection range upper limit (8 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. 323 Appendix H ES100j Digital Controller Protocol Write PID Control Parameters 2 (Sequence No. 263 (Hex 0107)) Writes the PID parameters No. 5 to 8 to the PID control parameters in the parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data Number of send data words +0 (Undefined) +1 Unit No. +2 PID No. 5 P (rightmost 4 digits) +3 PID No. 5 P (leftmost 4 digits) +4 PID No. 5 I (rightmost 4 digits) +5 PID No. 5 I (leftmost 4 digits) +6 PID No. 5 D (rightmost 4 digits) +7 PID No. 5 D (leftmost 4 digits) +8 PID No. 5 MV lower limit (rightmost 4 digits) +9 PID No. 5 MV lower limit (leftmost 4 digits) +10 PID No. 5 MV upper limit (rightmost 4 digits) +11 PID No. 5 MV upper limit (leftmost 4 digits) +12 PID No. 5 PV bias value (rightmost 4 digits) +13 PID No. 5 PV bias value (leftmost 4 digits) +14 PID No. 5 Automatic selection range upper limit (rightmost 4 digits) +15 PID No. 5 Automatic selection range upper limit (leftmost 4 digits) ~ 324 ~ +52 PID No. 8 MV upper limit (rightmost 4 digits) +53 PID No. 8 MV upper limit (leftmost 4 digits) +54 PID No. 8 PV bias value (rightmost 4 digits) +55 PID No. 8 PV bias value (leftmost 4 digits) +56 PID No. 8 Automatic selection range upper limit (rightmost 4 digits) +57 PID No. 8 Automatic selection range upper limit (leftmost 4 digits) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 003A (0058 decimal) (fixed) +1 Unit No. (2 digits BCD) 00 to 31 +2 to 3 PID No. 5 P (8 digits BCD) 00000000 to 09999000 +4 to 5 PID No. 5 I (8 digits BCD) +6 to 7 PID No. 5 D (8 digits BCD) +8 to 9 PID No. 5 MV lower limit (8 digits BCD) +10 to 11 PID No. 5 MV upper limit (8 digits BCD) +12 to 13 PID No. 5 PV bias value (8 digits BCD) +14 to 15 PID No. 5 Automatic selection range upper limit (8 digits BCD) D D D +44 to 45 PID No. 8 P (8 digits BCD) +46 to 47 PID No. 8 I (8 digits BCD) +48 to 49 PID No. 8 D (8 digits BCD) +50 to 51 PID No. 8 MV lower limit (8 digits BCD) +52 to 53 PID No. 8 MV upper limit (8 digits BCD) +54 to 55 PID No. 8 PV bias value (8 digits BCD) +56 to 57 PID No. 8 Automatic selection range upper limit (8 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Read Local SP (Sequence No. 264 (Hex 0108)) Reads the local SP in the program parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 (Undefined) Unit No. +5 Pattern No. Step No. ~ 1st unit 2nd unit ~ +64 (Undefined) Unit No. +65 Pattern No. Step No. 32nd unit 325 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 D D D +64 32nd unit Unit No. (2 digits BCD) +65 (max.) 32nd unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 31 00 to 63 00 to 63 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Local SP (rightmost 4 digits) +2 Local SP (leftmost 4 digits) +3 Local SP (rightmost 4 digits) +4 Local SP (leftmost 4 digits) ~ 1st unit 2nd unit ~ +63 Local SP (rightmost 4 digits) +64 Local SP (leftmost 4 digits) Offset Contents (data format) 32nd unit Data +0 Number of receive data words (4 digits Hex) Number of units 2 + 1 +1 1st unit Local SP (rightmost 4 digits) (4 digits BCD) 00000000 to 09999000 F indicates a negative number. +2 1st unit Local SP (leftmost 4 digits) (4 digits BCD) +3 2nd unit Local SP (rightmost 4 digits) (4 digits BCD) +4 2nd unit Local SP (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 D D D 326 +63 32nd unit Local SP (rightmost 4 digits) (4 digits BCD) +64 32nd unit Local SP (leftmost 4 digits) (4 digits BCD) 00000000 to 09999000 Appendix H ES100j Digital Controller Protocol Write Local SP (Sequence No. 265 (Hex 0109)) Writes the local SP to the program parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 Pattern No. Step No. 1st unit Local SP (rightmost 4 digits) +4 Local SP (leftmost 4 digits) +5 +6 (Undefined) Unit No. +7 Pattern No. Step No. 2nd unit Local SP (rightmost 4 digits) +8 Local SP (leftmost 4 digits) +9 ~ ~ +122 (Undefined) Unit No. +123 Pattern No. Step No. Local SP (rightmost 4 digits) +124 31st unit Local SP (leftmost 4 digits) +125 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 4 + 2 +1 Number of units (4 digits Hex) 0001 to 001F (1 to 31 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) +4 1st unit Local SP (rightmost 4 digits) (4 digits BCD) +5 1st unit Local SP (leftmost 4 digits) (4 digits BCD) 00 to 63 00 to 63 00000000 to 09999000 D D D +122 31st unit Unit No. (2 digits BCD) +123 31st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) +124 31st unit Local SP (rightmost 4 digits) (4 digits BCD) +125 31st unit Local SP (leftmost 4 digits) (4 digits BCD) 00 to 31 00 to 63 00 to 63 00000000 to 09999000 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 327 Appendix H ES100j Digital Controller Protocol Read Program Parameters (Sequence No. 266 (Hex 010A)) Reads the local SP, step time, PID set No., wait code, and events from 1 to 10 set values in the program parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 (Undefined) Unit No. +5 Pattern No. Step No. +6 (Undefined) Unit No. +7 Pattern No. Step No. +8 (Undefined) Unit No. Pattern No. Step No. +9 Offset 1st unit 2nd unit 3rd unit 4th unit Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0004 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 D D D 328 +8 4th unit Unit No. (2 digits BCD) +9 (max.) 4th unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 31 00 to 63 00 to 63 Appendix H ES100j Digital Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Local SP (rightmost) +2 Local SP (leftmost) +3 Step bank time (rightmost) +4 Step bank time (leftmost) +5 PID set No. (rightmost) +6 PID set No. (leftmost) +7 Wait code (rightmost) +8 +9 +10 Event 1 setting (rightmost) Event 1 setting (leftmost) ~ ~ +27 Event 10 setting (rightmost) +28 Event 10 setting (leftmost) ~ ~ +85 Local SP (rightmost) +86 Local SP (leftmost) +87 Step bank time (rightmost) +88 Step bank time (leftmost) +89 PID set No. (rightmost) +90 +91 +92 +93 +94 PID set No. (leftmost) +112 4th unit (max.) Wait code (rightmost) Wait code (leftmost) Event 1 setting (rightmost) Event 1 setting (leftmost) ~ +111 1st unit Wait code (leftmost) ~ Event 10 setting (rightmost) Event 10 setting (leftmost) 329 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) +0 Number of receive data words (4digits Hex) Number of units 28 + 1 +1 to 2 1st unit Local SP (8 digits BCD) 00000000 to 09999000 F indicates a negative number. +3 to 4 1st unit Step time) (8 digits BCD) +5 to 6 1st unit PID set No. (8 digits BCD) +7 to 8 1st unit Wait code (8 digits BCD) +9 to 10 1st unit Event 1 setting (8 digits BCD) +11 to 12 1st unit Event 2 setting (8 digits BCD) D D +27 to 28 1st unit Event 10 setting (8 digits BCD) +29 to 30 1st unit Local SP (8 digits BCD) D D 330 Data +109 to 110 4th unit Event 9 setting (8 digits BCD) +111 to 112 (max.) 4th unit Event 10 setting (8 digits BCD) Appendix H ES100j Digital Controller Protocol Write Program Parameters (Sequence No. 267 (Hex 010B)) Writes the local SP, step time, PID set No., wait code, and events from 1 to 10 settings in the program parameter area. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of units +2 (Undefined) Unit No. +3 Pattern No. Step No. +4 Local SP (rightmost) +5 Local SP (leftmost) +6 Step bank time (rightmost) +7 Step bank time (leftmost) +8 +9 +10 +11 +12 +13 PID set No. (rightmost) PID set No. (leftmost) Wait code (rightmost) Event 1 setting (rightmost) Event 1 setting (leftmost) ~ +30 +31 1st unit Wait code (leftmost) ~ Event 10 setting (rightmost) Event 10 setting (leftmost) ~ ~ +92 (Undefined) Unit No. +93 Pattern No. Step No. ~ ~ +120 Event 10 setting (rightmost) +121 Event 10 setting (leftmost) 4th unit (max.) 331 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 30 + 2 +1 Number of units (4 digits BCD) 0001 to 0004 +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (2 digits BCD) Step No. (2 digits BCD) 00 to 63 00 to 63 00000000 to 09999000 +4 to 5 1st unit Local SP (8 digits BCD) +6 to 7 1st unit Step time (8 digits BCD) +8 to 9 1st unit PID set No. (8 digits BCD) +10 to 11 1st unit Wait code (8 digits BCD) +12 to 13 1st unit Event 1 setting (8 digits BCD) +14 to 15 1st unit Event 2 setting (8 digits BCD) D D +30 to 31 1st unit Event 10 setting (8 digits BCD) +32 to 33 2nd unit Unit No. (2 digits BCD) D D +111 to 112 4th unit Event 9 setting (8 digits BCD) +120 to 121 (max.) 4th unit Event 10 setting (8 digits BCD) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Remote Setting Mode (Sequence No. 268 (Hex 010C)) Switches the setting mode to the remote setting mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 332 ~ 32nd unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Local Setting Mode (Sequence No. 269 (Hex 010D)) Switches the setting mode to the local setting mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +33 1st unit Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. External Setting Mode (Sequence No. 270 (Hex 010E)) Switches the setting mode to the external setting mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ 32nd unit (max.) 333 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Run Command (Sequence No. 271 (Hex 010F)) Starts control. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 (Undefined) +2 Unit No. 1st unit Pattern No./Bank No. +3 ~ +64 ~ (Undefined) Unit No. Pattern No. Bank No. +65 Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No./Bank No. (4 digits BCD) 0000 to 0063 +24 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Pattern No./Bank No. (4 digits BCD) 0000 to 0063 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 334 Appendix H ES100j Digital Controller Protocol Reset (Stop) (Sequence No. 272 (Hex 0110)) Stops control. Send Data Word Allocation (2nd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Auto Mode (Sequence No. 273 (Hex 0111)) Switches the control mode to the auto mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit ~ ~ (Undefined) +33 Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 335 Appendix H ES100j Digital Controller Protocol Manual Mode (Sequence No. 274 (Hex 0112)) Switches the control mode to the manual mode. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. 1st unit +3 (Undefined) Unit No. 2nd unit (Undefined) Unit No. ~ +33 ~ Offset 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Execute A.T. (Sequence No. 275 (Hex 0113)) Executes A.T. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 +2 +3 Number of send data words Number of units (Undefined) Unit No. ~ +64 +65 336 1st unit PID set No. ~ (Undefined) Unit No. PID set No. 32nd unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit PID set No. (4 digits BCD) 0000 to 0008 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit PID set No. (4 digits BCD) 0000 to 0008 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Cancel A.T. (Sequence No. 276 (Hex 0114)) Cancels A.T. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Number of units +1 +2 (Undefined) Unit No. +3 (Undefined) Unit No. ~ 2nd unit ~ (Undefined) +33 1st unit Offset Unit No. 32nd unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +33 (max.) 32nd unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 337 Appendix H ES100j Digital Controller Protocol Change Pattern No. (Sequence No. 277 (Hex 0115)) Changes the pattern number. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Unit No. 1st unit Pattern No. +3 ~ +64 ~ (Undefined) Unit No. 32nd unit (max.) Pattern No. +65 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Pattern No. (4 digits BCD) 0001 to 0063 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Pattern No. (4 digits BCD) 0001 to 0063 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Change Bank No. (Sequence No. 278 (Hex 0116)) Changes the bank number. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 +1 +2 +3 Number of send data words Number of units (Undefined) Unit No. 1st unit Bank No. ~ +64 +65 338 ~ (Undefined) Bank No. Unit No. 32nd unit (max.) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units 2 + 2 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 +3 1st unit Bank No. (4 digits BCD) 0000 to 0007 +4 2nd unit Unit No. (2 digits BCD) 00 to 31 D D D +64 32nd unit Unit No. (2 digits BCD) 00 to 31 +65 (max.) 32nd unit Bank No. (4 digits BCD) 0000 to 0007 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Read Controller Status (Sequence No. 279 (Hex 0117)) Reads the Controller status. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Unit No. (Undefined) Unit No. ~ 1st unit ~ +26 Offset 25th unit (max.) Contents (data format) Data +0 Number of send data words (4 digits Hex) Number of units + 2 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 1st unit Unit No. (2 digits BCD) 00 to 31 D D D +26 (max.) 25th unit Unit No. (2 digits BCD) 00 to 31 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Operation status Hold +2 Auto/manual SP mode +3 Setting mode Valid pattern No. +4 A.T. Valid PID set No. +5 Wait Operation mode ~ 1st unit ~ +121 Operation status Hold +122 Auto/manual SP mode +123 Setting mode Valid pattern No. +124 A.T. Valid PID set No. +125 Wait Operation mode 25th unit (max.) 339 Appendix H ES100j Digital Controller Protocol Offset Contents (data format) +0 Number of receive data words (4 digits Hex) +1 1st unit Operation status (2 digits BCD) Data Number of units 5 + 1 00: Reset 01: Run Hold (2 digits BCD) 00: Not hold 01: Hold +2 1st unit Auto/manual (2 digits BCD) 00: Auto mode 01: Manual mode SP mode (2 digits BCD) 00: Local SP mode 01: Remote SP mode 02: Fixed SP mode +3 1st unit Setting mode (2 digits BCD) 00: Local setting mode 01: Remote setting mode 02: External setting mode +4 Valid pattern No. (2 digits BCD) 00 to 63 1st unit A.T. (2 digits BCD) 00: Not A.T. 01: A.T. +5 Valid PD set No. (2 digits Hex) 01 to 08 1st unit Wait (2 digits BCD) 00: Not waiting 01: Waiting 02: Wait alarm output Operation mode (2 digits BCD) 00: Setting level 1 (without technical mode) 01: Setting level 1 (with technical mode) 02: Setting level 2 (without technical mode) 03: Setting level 2 (with technical mode) D D D +125 (max.) 25th unit Wait (2 digits BCD) 00: Not waiting 01: Waiting 02: Wait alarm output Operation mode (2 digits BCD) 00: Setting level 1 (without technical mode) 01: Setting level 1 (with technical mode) 02: Setting level 2 (without technical mode) 03: Setting level 2 (with technical mode) General-purpose Command (Sequence No. 280 (Hex 0118)) Sends the specified data and stores the received data in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of send data bytes +2 Send data (ASCII code) +3 Send data (ASCII code) ~ +249 340 ~ Send data (max. = 496 characters) Appendix H ES100j Digital Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Number of send data bytes (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) Send data (2 characters ASCII) Refer to the manual for the ES100j. j +2 The number of send bytes not including @, the FCS, or the terminator. D Use ASCII (Up to 496 characters total.) D D +249 (max.) Send data (1 character ASCII) Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data (ASCII code) +2 Receive data (ASCII code) ~ ~ Receive data +249 Offset (Undefined) (max.=251 characters) Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0001 to 00FA (1 to 250 decimal) +1 Receive data (2 characters ASCII) Refer to the manual for the ES100V. Returned as ASCII (Up to 498 characters total.) D D D +249 (max.) Receive data (1 character ASCII) Note 1. At transmission, a header code “@” is attached before the data and the FCS and a terminator “*”CR are attached following the send data. First word of send +0 data +1 0006 +2 “AB” +3 “CD” 0007 +4 “EF” +5 “GH” @ABCDEFG[FCS]*CR 2 bytes 2. At reception, data excluding the header code “@” at the beginning of the receive data and the FCS and terminator “*”CR at the end of the data is stored in the receive data storage words. First word of send +0 data +1 0006 +2 “AB” +3 “CD” @ABCDEFG[FCS]*CR 2 bytes +4 +5 0007 “EF” “G” 3. Refer to the manual for the ES100j for the contents of send data and receive data. 341 Appendix I K3Tj Intelligent Signal Processor Protocol The K3Tj Intelligent Signal Processor Protocol is used to make various settings or control remotely the Intelligent Signal Processor connected to the Serial Communications Unit/Board via RS-232C or RS-422/485 cable. Protocol Configuration The configuration of the K3Tj Intelligent Signal Processor Protocol is shown as follows: Sequence No. Communications sequence name Function Ladder interface Send word allocation Yes Receive word allocation No 300 (012C) Reset (by unit number) Performs the same processing as when an input is received on the reset terminal. 301 (012D) Reset (continuous units) Performs the same processing as when an input is received on the reset terminal. Yes No 302 (012E) Writes the set value HH, H, L, or LL. Writes the set value HH. Yes No Yes No Writes the set value H. Yes No Writes the set value L. Yes No Writes the set value LL. Yes No Writes the set value to a bank which is not in use (K3TR: HH to LL, K3TC: O1 to O5). Yes No Writes the set value HH to a bank which is not in use. Writes the set value H to a bank which is not in use. Writes the set value L to a bank which is not in use. Writes the set value LL to a bank which is not in use. Writes the set value O5 to a bank which is not in use. Writes the set value O4 to a bank which is not in use. Writes the set value O3 to a bank which is not in use. Writes the set value O2 to a bank which is not in use. Writes the set value O1 to a bank which is not in use. Reads the set value HH, H, L, or LL. Reads the set value HH. Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Reads the set value H. Yes Yes 303 (012F) 304 (0130) 305 (0131) 306 (0132) 307 (0133) 308 (0134) Write set value (by unit number) Write set value HH (continuous units) Write set value H (continuous units) Write set value L (continuous units) Write set value LL (continuous units) Write set value with bank (by unit number) Write set value HH with bank (continuous units) 309 (0135) Write set value H with bank (continuous units) 310 (0136) Write set value L with bank (continuous units) 311 (0137) Write set value LL with bank (continuous units) 312 (0138) Write set value O5 with bank (continuous units) 313 (0139) Write set value O4 with bank (continuous units) 314 (013A) Write set value O3 with bank (continuous units) 315 (013B) Write set value O2 with bank (continuous units) 316 (013C) Write set value O1 with bank (continuous units) 317 (013D) Read set value (by unit number) 318 (013E) Read set value HH (continuous units) 319 (013F) Read set value H (continuous units) Notes See Note1 See Note1 See Note1 See Note1 See Note1 See Note2 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 343 Appendix I K3Tj Intelligent Signal Processor Protocol Sequence No. Communications sequence name 320 (0140) Read set value L (continuous units) Read set value LL (continuous units) Read set value with bank (by unit number) 321 (0141) 322 (0142) 323 (0143) Read set value HH with bank (continuous units) 324 (0144) Read set value H with bank (continuous units) 325 (0145) Read set value L with bank (continuous units) 326 (0146) Read set value LL with bank (continuous units) 327 (0147) Read set value O5 with bank (continuous units) 328 (0148) Read set value O4 with bank (continuous units) 329 (0149) Read set value O3 with bank (continuous units) 330 (014A) Read set value O2 with bank (continuous units) 331 (014B) Read set value O1 with bank (continuous units) 332 (014C) Read holding data (by unit number) 333 (014D) Read holding data PH (continuous units) 334 (014E) Read holding data BH (continuous units) 335 (014F) Read display value (PV) (by unit number) 336 (0150) Read display value (PV ) (continuous units) 337 (0151) Read model (by unit number) 338 (0152) Read model (continuous units) 339 (0153) General-purpose command Function Reads the set value L. Ladder interface Send word Receive word allocation allocation Yes Yes Reads the set value LL. Yes Yes Reads set value of a bank which is not in use (K3TR: HH to LL, K3TC: O1 to O5). Yes Yes Reads the set value HH of a bank which is not in use. Reads the set value H of a bank which is not in use. Reads the set value L of a bank which is not in use. Reads the set value LL of a bank which is not in use. Reads the set value O5 of a bank which is not in use. Reads the set value O4 of a bank which is not in use. Reads the set value O3 of a bank which is not in use. Reads the set value O2 of a bank which is not in use. Reads the set value O1 of a bank which is not in use. Reads the peak/bottom data (maximum, minimum). Reads the peak data (maximum). Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Reads the bottom data (minimum). Reads the display value (PV). Yes Yes Yes Yes Reads the display value (PV). Yes Yes Reads the model data. Yes Yes Reads the model data. Yes Yes Send specified data or receives specified data and writes it to the receive data words. Yes Yes Notes See Note1 See Note1 See Note2 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note1 See Note3 See Note3 See Note3 Note 1. Special specifications are required to use communications + comparison output. 2. Special specifications are required to use communications + comparison output for the K3TR and K3TC. The operands HH, H, L, and LL are for the K3TR, and the operands O5, O4, O3, O2, and O1 are for the K3TC. 3. Not available for the K3TC. 4. The hexadecimal equivalents of sequences numbers are given in parentheses. 5. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 344 Appendix I K3Tj Intelligent Signal Processor Protocol Connections The connections used for the K3Tj Intelligent Signal Processor Protocol are shown below. RS-232C Connections CS1j K3Tj Serial Communications Unit/Board RS-232C port Signal name Protective ground or earth FG Signal direction --- Signal ground or common return line SG --- 7 Send data SD Output 2 Receive data RD Input 3 Request to send RS Output 4 Clear to send CS Input 5 Data set ready DR Input 6 Data terminal ready ER Output 20 Serial Communications Unit/Board RS-232C: D-sub 9-pin female Signal Pin Name No. FG Abbreviation 1 Intelligent Signal Processor RS-232C: Terminal block Shield Pin No. Termi- Signal nal Name MAX232C or equivalent FG SG SG SD SD RD RD RTS RTS CTS CTS DSR DSR DTR DTR Note 1. The connection configuration is a one-to-one configuration and the maximum cable length is 15 m. 2. Use shielded twisted-pair cable. 345 Appendix I K3Tj Intelligent Signal Processor Protocol RS-422/485 Connections CS1j Serial Communications Board (CS1W-SCB41) RS-422/485 port K3Tj K3Tj Up to 32 units can be connected K3Tj • RS-422 4-wire Connections Signal name Signal direction Pin No. SDA Output 9 Send data B SDB Output 5 Receive data A RDA Output 6 Receive data B RDB Input 1 Signal ground SG --- 3 Protective ground FG --- 7 Serial Communications Board RS-422: D-sub 9-pin female Termi- Signal nal. Name Shell *1: Set the 2-/4-wire switch to the 4-wire setting. *2: Turn ON the terminating resistance switch. Intelligent Signal Processor RS-422: Terminal block Signal Pin Name No. 346 Abbreviation Send data A Shield Pin No. SN751177N or equivalent Terminal block SW Terminating resistance (approx. 220 Ω) is connected via the terminal block switch. Appendix I K3Tj Intelligent Signal Processor Protocol • RS-485 2-wire Connections Signal name Abbreviation Signal direction Terminal Inverting output – Input or output 19 Non-inverting output + Input or output 18 Serial Communications Board RS-485: D-sub 9-pin female Signal Pin Name No. Intelligent Signal Processor Turn ON the terminal block switch for terminators only. RS-485: Terminal block SN751177N or equivalent Terminal block SW Termi-Signal nal. Name SDA SDB Shield Intelligent Signal Processor Unit designated as terminator. *1: Set the 2-/4-wire switch to the 2-wire setting. RS-485: Terminal block *2: Turn ON the terminating resistance switch. Termi-Signal nal. Name Terminal block SW ON The terminal block switch is turned ON. Shield Note 1. The connection configuration is a one-to-one or a 1-to-N configuration. For 1-to-N connections, up to 32 units including the Serial Communications Boards/Units can be connected. 2. The maximum cable length is 500 m. Use shielded twisted-pair cables (AWG28i or greater). 3. Connect terminating resistance at both ends of the transmission path. 4. Turn the terminal block switch ON at the terminators. 5. Turn the terminal block switches OFF for units that are not terminators. 347 Appendix I K3Tj Intelligent Signal Processor Protocol Reset (by Unit Number) (Sequence No. 300 (Hex 012C)) This sequence performs the same processing as when an input is received on the reset terminal. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of Number of send data words +0 +1 Number of units (Undefined) +2 Relevant unit No. ~ ~ (Undefined) +33 Offset Relevant unit No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0003 to 0022 (3 to 34 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 D D D +33 Relevant unit No. (2 digits BCD) 00 to 99 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Reset Control (Continuous Units) (Sequence No. 301 (Hex 012D)) This sequence performs reset control for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0002 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) Receive Data Word Allocation (4th Operand of PMCR(260)) None. 348 Data Appendix I K3Tj Intelligent Signal Processor Protocol Write Set Value (by Unit Number) (Sequence No. 302 (Hex 012E)) This sequence writes each set value (HH, H, L, LL). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Relevant unit No. Operand +3 Set value +4 (Undefined) +5 Set value ~ +122 ~ (Undefined) Relevant unit No. Operand +123 Set value +124 (Undefined) +125 Set value Offset Contents (data format) +0 Number of send data words (4 digits BCD) 0006 to 007E (6 to 126 decimal) Data +1 Number of units (4 digits Hex) 0001 to 001F (1 to 31 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H”), +4 to +5 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 4C4C (“LL”) 4C20 (“L”) Example –1234 +4 2345 +4 1234 +5 0001 +5 000F D D D +124 to +125 Set value (5 digits BCD) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Set Value HH (Continuous Units) (Sequence No. 303 (Hex 012F)) This sequence writes set value HH for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words +1 Number of units +2 Set value +3 (Undefined) ~ +64 +65 Set value ~ Set value (Undefined) Set value 349 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 to 0042 (4 to 66 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 to +3 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F D D D +64 to +65 Set value (5 digits BCD) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Set Value H (Continuous Units) (Sequence No. 304 (Hex 0130)) This sequence writes set value H for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value L (Continuous Units) (Sequence No. 305 (Hex 0131)) This sequence writes set value L for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value LL (Continuous Units) (Sequence No. 306 (Hex 0132)) This sequence writes set value LL for continuous units. The word allocation is identical to that of sequence No. 303 (Write Set Value HH (Continuous Units)). Write Set Value with Bank (by Unit Number) (Sequence No. 307 (Hex 0133)) This sequence writes set value of a bank which is not in use (K3TR: HH to LL, K3TC:O1 to O5). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Relevant unit No. +3 (Undefined) Bank No. +4 +5 +6 Operand Set value (Undefined) Set value ~ +122 (Undefined) Relevant unit No. +123 (Undefined) Bank No. +124 +125 +126 350 ~ Operand Set value (Undefined) Set value Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 007F (7 to 127 decimal) +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Bank No. (2 digits BCD) 01 to 04 +4 Operand (Two ASCII characters) 4848 (“HH”), 4820 (“H ”), 4C20 (“L ”), 4C4C (“LL”), +5 to +6 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) 4F31 (“O1”) 4F32 (“O2”) 4F33 (“O3”) 4F34 (“O4”) 4F35 (“O5”) Example 12345 +5 +6 Example –1234 2345 +5 1234 0001 +6 000F D D D +125 to +126 Set value (5 digits BCD) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Set Value HH with Bank (Continuous Units) (Sequence No. 308 (Hex 0134)) This sequence writes set value HH of a bank not in use for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 +3 +4 (Undefined) Bank No. Set value (Undefined) Set value ~ +95 +96 +97 ~ (Undefined) Bank No. Set value (Undefined) Set value 351 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 to 0062 (5 to 98 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Bank No. (2 digits BCD) 01 to 04 +3 to +4 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F D D D +96 to +97 Set value (5 digits BCD) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) None. Write Set Value H with Bank (Continuous Units) (Sequence No. 309 (Hex 0135)) This sequence writes set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value L with Bank (Continuous Units) (Sequence No. 310 (Hex 0136)) This sequence writes set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value LL with Bank (Continuous Units) (Sequence No. 311 (Hex 0137)) This sequence writes set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O5 with Bank (Continuous Units) (Sequence No. 312 (Hex 0138)) This sequence writes set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O4 with Bank (Continuous Units) (Sequence No. 313 (Hex 0139)) This sequence writes set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O3 with Bank (Continuous Units) (Sequence No. 314 (Hex 013A)) This sequence writes set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). 352 Appendix I K3Tj Intelligent Signal Processor Protocol Write Set Value O2 with Bank (Continuous Units) (Sequence No. 315 (Hex 013B)) This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Write Set Value O1 with Bank (Continuous Units) (Sequence No. 316 (Hex 013C)) This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)). Read Set Value (by Unit Number) (Sequence No. 317 (Hex 013D)) Reads set value HH, H, L, or LL. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units (Undefined) +2 Relevant unit No. Operand +3 ~ ~ (Undefined) +64 Relevant unit No. Operand +65 Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0004 to 0042 (4 to 66 decimal) Data +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H”), 4C4C (“LL”) 4C20 (“L”) 4F31 (“01”) 4F35 (“05”) D D D +64 to +65 Operand (ASCII 2 characters) Same as above Receive Data Word Allocation (4th Operand of PMCR(260))) Receive data storage words +0 +1 +2 +3 Number of receive data words (Undefined) End code Set value (Undefined) Set value ~ +94 +95 +96 ~ (Undefined) End code Set value (Undefined) Set value 353 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0004 to 0061 (4 to 97 decimal) +1 End code (2 digits Hex) 00 to 22 +2 to +3 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 Example –1234 +2 2345 +2 1234 +3 0001 +3 000F D D D +95 to +96 Set value (5 digits BCD) Same as above Read Set Value HH (Continuous Units) (Sequence No. 318 (Hex 013E)) This sequence reads set value HH for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) Receive Data Word Allocation (4th Operand of PMCR(260)) This sequence is similar to sequence No. 317 (Read Set Value (by Unit Number)). Read Set Value H (Continuous Units) (Sequence No. 319 (Hex 013F)) This sequence reads set value H for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). Read Set Value L (Continuous Units) (Sequence No. 320 (Hex 0140)) This sequence reads set value L for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). Read Set Value LL (Continuous Units) (Sequence No. 321 (Hex 0141)) This sequence reads set value LL for continuous units. The word allocation is identical to that of sequence No. 318 (Read Set Value HH (Continuous Units)). 354 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value with Bank (by Unit Number) (Sequence No. 322 (Hex 0142)) Reads the set value of a bank which is not in use (K3TR: HH to LL, K3TC:01 to 05) and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) Number of units +2 (Undefined) Relevant unit No. +3 (Undefined) Bank No. +1 Operand +4 ~ ~ +95 (Undefined) Relevant unit No. +96 (Undefined) Bank No. Operand +97 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 to 0062 (5 to 98 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Bank No. (2 digits BCD) 01 to 04 +4 Operand (ASCII 2 characters) 4848 (“HH”), 4820 (“H ”), 4C20 (“L ”), 4C4C (“LL”), 4F31 (“O1”) 4F32 (“O2”) 4F33 (“O3”) 4F34 (“O4”) 4F35 (“O5”) D D D + 97 Operand (ASCII 2 characters) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Set value (Undefined) +2 Set value ~ +63 ~ Set value +64 (Undefined) Set value Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0003 to 0041 (3 to 65 decimal) Data +1 to +2 Set value (5 digits BCD) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 Example –1234 +1 2345 +1 1234 +2 0001 +2 000F D D D +63 to +64 Set value (5 digits BCD) Same as above 355 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value HH with Bank (Continuous Units) (Sequence No. 323 (Hex 0143)) This sequence reads set value HH of a bank not in use for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words +1 Number of units (Undefined) +2 Bank No. ~ ~ (Undefined) +33 Offset Bank No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 0022 (3 to 34 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Bank No. (2 digits BCD) 01 to 04 D D D + 33 Bank No. (2 digits BCD) Same as above Receive Data Word Allocation (4th Operand of PMCR(260)) The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)). Read Set Value H with Bank (Continuous Units) (Sequence No. 324 (Hex 0144)) This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value L with Bank (Continuous Units) (Sequence No. 325 (Hex 0145)) This sequence reads set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value LL with Bank (Continuous Units) (Sequence No. 326 (Hex 0146)) This sequence reads set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O5 with Bank (Continuous Units) (Sequence No. 327 (Hex 0147)) This sequence reads set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O4 with Bank (Continuous Units) (Sequence No. 328 (Hex 0148)) This sequence reads set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). 356 Appendix I K3Tj Intelligent Signal Processor Protocol Read Set Value O3 with Bank (Continuous Units) (Sequence No. 329 (Hex 0149)) This sequence reads set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O2 with Bank (Continuous Units) (Sequence No. 330 (Hex 014A)) This sequence reads set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Set Value O1 with Bank (Continuous Units) (Sequence No. 331 (Hex 014B)) This sequence reads set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)). Read Holding Data (Sequence No. 332 (Hex 014C)) Reads the peak/bottom data (maximum, minimum) and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words +1 Number of units (Undefined) +2 Relevant unit No. Operand +3 ~ ~ (Undefined) +64 Relevant unit No. Operand +65 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 to 0042 (4 to 66 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 +3 Operand (ASCII 2 characters) 5048 (“PH”) 4248 (“BH”) D D D +65 Operand (ASCII 2 characters) Same as above 357 Appendix I K3Tj Intelligent Signal Processor Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Peak/bottom data (Undefined) +2 Peak/bottom data (Undefined) +3 Status ~ ~ +94 Peak/bottom data (Undefined) +95 Peak/bottom data (Undefined) +96 Status Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0004 to 0061 (4 to 97 decimal) Data +1 to +2 Peak/bottom data (5 digits BCD) 00000 to 99999 Negative sign: F (most significant digit) Example 12345 +3 Status (2 digits Hex) Example –1234 +1 2345 +1 1234 +2 0001 +2 F000 d0 bit: If overflow: 1 Others: 0 d1 bit: If underflow: 1 Others: 0 d2 bit: Not used d3 bit: During forced zero operation: 1 (K3TH,K3TR: 0) Others: 0 d4 bit: Not used d5 bit: During hold input: 1 Others: 0 d6 bit: Bank input 1: 1 (K3TH, K3TX: 0) Others: 0 d7 bit: Bank input 2: 1 (K3TH, K3TX: 0) Others: 0 D D D +96 Status Same as above Read Holding Data PH (Continuous Units) (Sequence No. 333 (Hex 014D)) This sequence reads peak holding data for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words +1 Number of units Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) Receive Data Word Allocation (4th Operand of PMCR(260)) The data allocation is similar to sequence No. 332 (Read Holding Data (by Unit Number)). 358 Appendix I K3Tj Intelligent Signal Processor Protocol Read Holding Data BH (Continuous Units) (Sequence No. 334 (Hex 014E)) This sequence reads bottom holding data for continuous units. The word allocation is identical to that of sequence No. 333 (Read Holding Data PH (Continuous Units)). Read Display Value (PV) (by Unit Number) (Sequence No. 335 (Hex 014F)) Reads the display value (PV) and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Relevant unit No. (Undefined) Relevant unit No. ~ +33 ~ Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 0022 (3 to 34 decimal) +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 D D D + 33 Relevant unit No. (2 digits BCD) 00 to 99 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 +2 +3 Number of receive data words Display value (Undefined) ~ +94 +95 +96 Display value Status ~ Display value (Undefined) Display value Status 359 Appendix I K3Tj Intelligent Signal Processor Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0004 to 0061 (4 to 97 decimal) +1 to +2 Display value (5 digits Hex) 00000 to 99999 Negative sign: F (5th digit in BCD) Example 12345 +3 Status (4 digits Hex) Example –1234 +1 2345 +1 1234 +2 0001 +2 000F d0 bit: If overflow: 1 Others: 0 d1 bit: If underflow: 1 Others: 0 d2 bit: Not used d3 bit: During forced zero operation: 1 (K3TH, K3TR, K3TC: 0) d4 bit: In test mode: 1 Others: 0 d5 bit: While holding input: 1 Others: 0 d6 bit: Bank input 1: 1 (K3TH, K3TX: 0) Others: 0 d7 bit: Bank input 2: 1 (K3TH, K3TX: 0) Others: 0 d8 bit: LL comparison output: 1 Others: 0 OUT1 comparison output: 1 (K3TC) d9 bit: L comparison output: 1 Others: 0 OUT2 comparison output: 1 (K3TC) d10 bit: H comparison output: 1 Others: 0 OUT4 comparison output: 1 (K3TC) d11 bit: HH comparison output: 1 Others: 0 OUT5 comparison output: 1 (K3TC) d12 bit: PASS comparison output: 1 Others: 0 OUT3 comparison output: 1 (K3TC) d13 bit: Not used d14 bit: Not used d15 bit: Not used D D D +96 360 Status (4 digits BIN) Same as above Others: 0 Appendix I K3Tj Intelligent Signal Processor Protocol Read Display Value (PV) (Continuous Units) (Sequence No. 336 (Hex 0150)) This sequence reads display value (PV) for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Number of units (4 digits Hex) 0001 to 0020 (1 to 32 decimal) Receive Data Word Allocation (4th Operand of PMCR(260)) This sequence is similar to sequence No. 335 (Read Display Value (PV) (Continuous Units)). Model Data Read (by Unit Number) (Sequence No. 337 (Hex 0151)) Reads model data and stores the results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units +2 (Undefined) Relevant unit No. (Undefined) Relevant unit No. ~ +26 ~ Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 001B (3 to 27 decimal) +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) +2 Relevant unit No. (2 digits BCD) 00 to 99 D D D + 26 Relevant unit No. (2 digits BCD) Same as above Note The number of Units can be up to 25 maximum. 361 Appendix I K3Tj Intelligent Signal Processor Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words Input specifications +1 Input specifications +2 Display specifications Output specifications +3 +4 Input contents +5 Operation mode ~ ~ Input specifications +121 +122 Input specifications Display specifications Output specifications +123 +124 Input contents +125 Operation mode Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0006 to 007E (6 to 126 decimal) Data +1 to +2 Input specifications (ASCII 3 characters) 544131 (“TA1”) (K3TH) 544231 (“TB1”) (K3TH) 564432 (“VD2”) (K3TX) 414432 (“AD2”) (K3TX) 564132 (“VA2”) (K3TX) 414132 (“AA2”) (K3TX) 524231 (“RB1”) (K3TR, K3TC) +2 Display specifications (ASCII 1 character) 41 (“A”) (common) 42 (“B”) (K3TH, K3TX) 43 (“C”) (K3TR, K3TC) +3 Output specifications (ASCII 2 characters) 5331 (“S1”) (RS-232C) 5332 (“S2”) (RS-485) 5333 (“S3”) (RS-422) 5335 (“S5”) (RS-485 + comparison output) 5336 (“S6”) (RS-422 + comparison output) +4 Input contents (ASCII 2 characters) Leftmost digit: 30 (“0”) to 31 (“1”) +5 Operation mode (ASCII 2 characters) 3030 (“00”) (K3TH, K3TX) 3031 (“00”) to 3133 (“12”) (K3TR) 5542 (“UB”) (K3TC) 5543 (“UC”) (K3TC) Rightmost digit: 31 (“1”) to 45 (“E”) D D D +125 Operation mode (ASCII 2 characters) Same as above Model Data Read (Continuous Units) (Sequence No. 338 (Hex 0152)) This sequence reads model data for continuous units. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Number of units Offset 362 Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Number of units (4 digits Hex) 0001 to 0019 (1 to 25 decimal) Appendix I K3Tj Intelligent Signal Processor Protocol Note The number of Units can be up to 25 maximum. Receive Data Word Allocation (4th Operand of PMCR(260)) The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)). General-purpose Command (Sequence No. 339 (Hex 0153)) Sends the specified data and writes the receive data to the receive data words. The characters such as “@”, FCS, terminators need not be set in the send and receive data words. These characters will be automatically added for transmission and automatically removed before saving data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ Send data +249 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Send data byte length (4 digits BCD) 0001 to 01F0 (1 to 496 decimal) Number of bytes of send data not including @, the FCS, and the terminator. +2 to +249 Send data (ASCII) ASCII code Send data: 496 characters max. Receive Data Word Allocation (3rd Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data +2 Receive data +3 Receive data ~ ~ Receive data +249 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0001 to 00FA (1 to 250 decimal) +1 to +249 Receive data (ASCII) ASCII code Receive data: 498 characters max. 363 Appendix J V500/V520 Bar Code Reader Protocol The V500/V520 Bar Code Reader Protocol is used to make various settings or control remotely the Bar Code Reader connected the Serial Communications Unit/Board via RS-232C cable. Protocol Configuration The configuration of the V500/V520 Bar Code Reader Protocol is shown below. Sequence No. Communications sequence name Function Ladder interface 350 (015E) BCR read start Instructs the Reader to start a BCR read. Send word allocation No 351 (015F) BCR read stop Instructs the Reader to stop a BCR read. No No 352 (0160) Data read No Yes 353 (0161) Complete data read No Yes 354 (0162) BCR function write (V500) BCR function read (V500) Log data output request (V500) Preset data set (V500) Data read by the Reader is received and saved in the receive words. Instructs the Reader to start a read. After the data read by the Reader is received and saved to the receive words, reading is stopped. Writes the operation mode and read functions. Reads the operation mode and read functions. Requests output of log data sent to host. Yes No No Yes Yes Yes Writes preset data. Yes No BCR connection confirmation (V500) Log data clear (V500) Confirms if the Reader is correctly set. No No Clear log data. No No 360 (0168) Continuous data read (scan) (V500) No Yes 361 (0169) Continuous data read (interrupt) (V500) Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method. Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt No.100). No Yes 362 (016A) BCR initialize Yes No 363 (016B) Continuous data read (scan) (V520) Clears the log, confirms BCR connection, and sets BCRs. Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method. Performing the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt No.100). No Yes No Yes 365 (016D) General-purpose command 1 Used to send data of a specified data length, and receive only ACK as the receive data. Yes No 366 (016E) Used to send data of a specified data length, and receive ACK together with the return of other receive data. The frame format of the receive data, however, has to contain STX and ETX. Yes Yes 355 (0163) 356 (0164) 357 (0165) 358 (0166) 359 (0167) 364 (016C) Continuous data read (interrupt) (V520) General-purpose command 2 Receive word allocation No 365 Appendix J V500/V520 Bar Code Reader Protocol Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 3. Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the CS1WSCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Connections The connections for using the V500/V520 Bar Code Reader Protocol are shown below. V500 Connections 100 VAC V520-R12j CS1j Reader Serial Communications Unit/Board RS-232C port V500-C11 ID Controller V509-W040 Reader Cable Serial Communications Unit/Board: D-sub 9 pin female Signal Name 366 Pin No. V500-C11: D-sub 9 pin female Pin No. Signal Name FG FG SD SD RD RD RTS RTS CTS CTS DSR DSR DTR DTR SG SG Appendix J V500/V520 Bar Code Reader Protocol V520 Connections V520-R121 Reader CS1j Serial Communications Unit/Board RS-232C port V509-W011 Reader Cable Serial Communications Unit/Board: D-sub 9 pin female Signal Name Pin No. V520-R121: D-sub 9 pin female Pin No. Signal Name FG SD SD RD RD RTS RTS CTS CTS DTR DSR SG DTR SG System Setting Shown below are the system settings of the V500-C11 and V520-R121 when this protocol is used. Note The portions enclosed by in boxes are used for this protocol. V500-C11 • BCR Functions Read trigger Read control method “READ SIGNAL INPUT”, “ONLINE READ COMMAND” “SINGLE READ”, “CONTINUOUS READ” • Host Interface Prefix Suffix Bar code output NONE, “STX” “ETX” , “CR ” “OUTPUT” , “NO OUTPUT” V520-R121 Start code Stop code Operation mode Data output mode NONE, “STX” “ETX” , “CR” External trigger, host trigger 1-shot, continuous 367 Appendix J V500/V520 Bar Code Reader Protocol BCR Read Start (Sequence No. 350 (Hex 015E)) This sequence instructs the Bar Code Reader to start reading. Send Data Word Allocation 3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. BCR Read Stop (Sequence No. 351 (Hex 015F)) This sequence instructs the Bar Code Reader to stop reading. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Data Read (Sequence No. 352 (Hex 0160)) This sequence receives read data and saves it to the receive data storage words. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data +3 Read data +4 Read data ~ ~ +15 Read data +16 Read data Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0002 to 0011 (2 to 17 decimal) Data +1 to +16 Read data (ASCII) 30 (‘0’) to 39 (‘9’), 41 (‘A’) to 5A (‘Z’), 3F (‘?’) Up to 32 characters in ASCII Note The reception wait time is not set for this sequence. Complete Data Read (Sequence No. 353 (Hex 0161)) This sequence instructs the Bar Code Reader to start reading, receives the data read by the Bar Code Reader, stores the data in the receive data storage words, and then instructs the Reader to stop reading. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) It is similar to sequence No. 352 (Data read). Note The reception wait time is not set for this sequence. 368 Appendix J V500/V520 Bar Code Reader Protocol BCR Function Write (V500) (Sequence No. 354 (Hex 0162)) This sequence sets the operation mode and read functions in the Bar Code Reader. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words +1 Operation mode +2 Types of bar code (Undefined) +3 (Undefined) Number of digits +4 Modulus check (Undefined) (Undefined) Number of Multistep matches labels Horizontal control +5 Buzzer +6 In-zone control Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0007 (fixed) +1 Operation mode (ASCII 1 character) 41 (‘A’) : ONLINE *42 (‘B’) : ONLINE CONTROL In-zone control (ASCII 1 character) *41 (‘A’) : ON 42 (‘B’) : OFF +2 Bar code type (ASCII 1 character) 41 (‘A’) : 42 (‘B’) : 43 (‘C’) : 44 (‘D’) : 45 (‘E’) : 46 (‘F’) : 47 (‘G’) : 48 (‘H’) : 49 (‘I’) : 4A (‘J’) : 4B (‘K’) : +3 Number of digits (2 digits BCD) 00 to 32 00: Any number of digits allowed. +4 Modulus check (ASCII 1 character) 41 (‘A’) : 42 (‘B’) : 43 (‘C’) : 44 (‘D’) : 45 (‘E’) : 46 (‘F’) : 47 (‘G’) : +5 Number of matches (1 digit BCD) 1 to 5 Multistep labels (1 digit BCD) 1 to 4 Buzzer (ASCII 1 character) 41 (‘A’) : ON for normal read 42 (‘B’) : ON for no-read 43 (‘C’) : OFF Horizontal control mode (ASCII 1 character) 41 (‘A’) : Normal (continuous rotating) 42 (‘B’) : In-zone startup +6 Data JAN NW7 NORMAL NW7 SMALL NW7 HEX CODE39 NORMAL CODE39 ST/SP OUTPUT 2 of 5 (ITF) CODE128 CODE93 2 of 5 (3BAR) 2 of 5 (5BAR) No-check Modulus 10 (all bar codes) Modulus 11 (except JAN) Modulus 16 (NW7 only) Modulus 43 (CODE39 only) Modulus 47 (CODE93 only) Modulus 103 (CODE128 only) Note Selecting the values marked with asterisks is required for this protocol. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 369 Appendix J V500/V520 Bar Code Reader Protocol BCR Function Read (V500) (Sequence No. 355 (Hex 0163)) This sequence reads the settings of functions in the Bar Code Reader. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Operation mode In-zone control +2 Types of bar code (Undefined) +3 (Undefined) Number of digits +4 Modulus check (Undefined) +5 (Undefined) Number of Multistep matches. labels. Horizontal control Buzzer +6 Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0007 (fixed) +1 Operation mode (ASCII 1 character) 41 (‘A’) : ONLINE 42 (‘B’) : ONLINE CONTROL In-zone control (ASCII 1 character) 41 (‘A’) : ON 42 (‘B’) : OFF +2 Bar code type (ASCII 1 character) 41 (‘A’) : 42 (‘B’) : 43 (‘C’) : 44 (‘D’) : 45 (‘E’) : 46 (‘F’) : 47 (‘G’) : 48 (‘H’) : 49 (‘I’) : 4A (‘J’) : 4B (‘K’) : +3 Number of digits (2 digits BCD) 00 to 32 +4 Modulus check (ASCII 1 character) 41 (‘A’) : 42 (‘B’) : 43 (‘C’) : 44 (‘D’) : 45 (‘E’) : 46 (‘F’) : 47 (‘G’) : +5 Number of matches (1 digit BCD) 1 to 5 Multistep labels (1 digit BCD) 1 to 4 Buzzer (ASCII 1 character) 41 (‘A’) : ON for normal read 42 (‘B’) : ON for no-read 43 (‘C’) : OFF Horizontal control mode (ASCII 1 character) 41 (‘A’) : Normal (continuous rotating) 42 (‘B’) : In-zone startup +6 370 Data JAN NW7 NORMAL NW7 SMALL NW7 HEX CODE39 NORMAL CODE39 ST/SP Output 2 of 5 (ITF) CODE128 CODE93 2 of 5 (3BAR) 2 of 5 (5BAR) No-check Modulus 10 (all bar codes) Modulus 11 (except JAN) Modulus 16 (NW7 only) Modulus 43 (CODE39 only) Modulus 47 (CODE93 only) Modulus 103 (CODE128 only) Appendix J V500/V520 Bar Code Reader Protocol Log Data Output Request (V500) (Sequence No. 356 (Hex 0164)) This sequence requests output of the log data sent to host. Send Data Word Allocation (3rd Operand of PMCR(260)) First word send data of +0 Number of send data words (Undefined) +1 Number of units Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0002 (fixed) Data +1 Number of units (2 digits BCD) 01 to 99 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Log data +2 Log data ~ ~ +248 Log data +249 Log data Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0001 to 00FA (1 to 250 decimal) Data +1 to +249 Log data (ASCII) Log data with the number of designated data is stored including the separator GS (1D). If the log data (including separator) exceeds 498 bytes, only 498 bytes are stored. Note No retries are performed for this sequence. 371 Appendix J V500/V520 Bar Code Reader Protocol Preset Data Set (V500) (Sequence No. 357 (Hex 0165)) This sequence sets preset data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data Number of send data words +0 +1 (Undefined) Number of presets +2 (Undefined) Preset data No. (Undefined) +3 Number of units +4 Preset data +5 Preset data ~ ~ +18 Preset data +19 Preset data ~ ~ +(18N+2) (Undefined) +(18N+3) (Undefined) Preset data No. Number of units +(18N+4) Preset data +(18N+5) Preset data ~ ~ +(18N+18) Preset data +(18N+19) Preset data Offset Contents (data format) +0 Number of send data words (4 digits Hex) 18N+2 (N is number of presets 1 to 5) +1 Number of presets (1 digit BCD) 1 to 5 +2 Preset data No. (1 digit BCD) 1 to 5 +3 Data length (2 digits BCD) 01 to 32 +4 to +19 Preset data (ASCII) Combination of the following ASCII characters and up to 32 characters maximum: 30 (’0’) to 39 (’9’) 41 (’A’) to 5A (’Z’), 3F (’?’) The area that is not used is undefined +20 to +91 Data Store repeatedly the contents of words with offsets +2 to +19 the same number of times as the number of presets (N) Receive Data Word Allocation (4th Operand of PMCR(260)) None. BCR Connection Confirmation (V500) (Sequence No. 358 (Hex 0166)) This sequence confirms whether the Bar Code Reader is connected correctly or not. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 372 V500/V520 Bar Code Reader Protocol Appendix J Log Data Clear (V500) (Sequence No. 359 (Hex 0167)) This sequence clears the log data. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Data Continuous Read (Scan) (V500) (Sequence No. 360 (Hex 0168)) This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data word allocation is similar to that of sequence No. 352 (Data read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Bar Code Reader still keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence. Note The reception wait time is not set for this sequence. Data Continuous Read (Interrupt) (V500) (Sequence No. 361 (Hex 0169)) This sequence performs the following operations repeatedly: Instruct the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation similar to that of sequence No. 352 (data read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Bar Code Reader keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence. 3. The reception wait time is not set for this sequence. 4. Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the CS1WSCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. BCR Initialize (V500) (Sequence No. 362 (Hex 016A)) This sequence clears the log data, confirms BCR connection and sets the BCR functions. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of sequence No. 354 (BCR Function Set). Receive Data Word Allocation (4th Operand of PMCR(260)) None. Data Continuous Read (Scan) (V520) (Sequence No. 363 (Hex 016B)) This sequence performs the following operations repeatedly: instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data. 373 Appendix J V500/V520 Bar Code Reader Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 352 (Data Read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR Read Stop) to end the sequence. 3. The reception wait time is not set for this sequence. Data Continuous Read (Interrupt) (V520) (Sequence No. 364 (Hex 016C)) This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The send data word allocation is similar to that of sequence No. 352 (Data Read). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR Read Stop) to end the sequence. 3. The reception wait time is not set for this sequence. 4. Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the CS1WSCU21 Serial Communications Unit. A protocol syntax error will occur is an attempt is made to execute either sequence with the Serial Communications Unit. General-purpose Command 1 (Sequence No. 365 (Hex 016D)) This general-purpose command is used to send data with a specified data length, and receive back only ACK. STX and ETX are automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ +248 Send data +249 Send data Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Send data byte length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) The byte length of the send data excluding STX and ETX. +2 to +249 Send data (ASCII) Inscribe send data up to 496 bytes (max.) by ASCII. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 374 Data Appendix J V500/V520 Bar Code Reader Protocol General-purpose Command 2 (Sequence No. 366 (Hex 016E)) This general-purpose command is used to send data with a specified data length, and receive back ACK in addition to other receive data. The frame format of the receive data, however, has to contain STX and ETX. STX and ETX are automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data ~ ~ +248 Send data +249 Send data Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) Data +1 Send data byte length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) The byte length of the send data excluding STX and ETX. +2 to +128 Send data (ASCII) Set send data up to 496 bytes (max.) by ASCII. Receive Data Storage Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data Receive data +2 ~ ~ +126 Receive data +127 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0001 to 00FA (1 to 250 decimal) +1 to +127 Receive data (ASCII) Up to 498 bytes of ASCII receive data are stored. Note Shown below is the receive data frame format. The reception data without ACK, STX, and ETX is stored. Receive data (498 bytes max.) STX ETX ACK 375 Appendix K 3Z4L Laser Micrometer Protocol The 3Z4L Laser Micrometer Protocol is used to make various settings or control remotely the Laser Micrometer connected to the Serial Communications Unit/Board via RS-232C cable. Protocol Configuration The configuration of the 3Z4L Laser Micrometer Protocol is shown below. Sequence No. Communications sequence name 400 (0190) 3Z4L clear 401 (0191) Memory switch set 402 (0192) 403 (0193) 404 (0194) Function Ladder interface Send word allocation Receive word allocation Resets errors, data, analog output, decision result and places the Laser Micrometer into standby. No No Yes No mm unit set Sets memory switches and the area for the work position LED. Sets the display unit to mm. No No E unit set Sets the display unit to E. No No Calibration set Calibrates the Laser Micrometer. Yes No No No Yes No Yes No Releases measurement conditions that have been set. Requests the measurement conditions that have been set and other settings. Yes No No Yes When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results. If the sample measurement condition is zero, starts a zero run measurement. No Yes No No 412 (019C) Continuous measurement start (scan) (3000-series) Starts a continuous measurement. The scan notification method is used for receive data. No Yes 413 (019D) Continuous measurement start (interrupt) (3000-series) Starts a continuous measurement. The interrupt notification method is used for receive data. No Yes No No*1 No Yes Notes Calibration setting release. 405 (0195) Calibration release 406 (0196) Program number set (3000-series) Measurement condition set (3000-series) Measurement condition release (3000-series) Measurement condition list request (3000-series) 407 (0197) 408 (0198) 409 (0199) 410 (019A) Single run measurement start (3000-series) 411 (019B) Zero run measurement start (3000-series) Releases the calibration of the Laser Micrometer. Switches the program number to a specified number. Sets measurement conditions. See Note 2 Measurement termination (3000-series) 414 (019E) 415 (019F) Measurement termination (3000-series) Data request (3000-series) Terminates a continuous measurement. Requests display data in the idle measurement status or the latch data generated by the measurement command. 377 Appendix K 3Z4L Laser Micrometer Protocol Sequence No. Communications sequence name 416 (01A0) Statistic processing execution (3000-series) Lights the statistic processing LED and processes the statistics. No No 417 (01A1) Statistic processing nonexecution (3000-series) Turns OFF the statistic processing LED. Statistics are not processed. No No 418 (01A2) All statistic memory clear (3000-series) Clears statistic processing memories of all programs. No No 419 (01A3) Statistic memory clear (3000-series) Clears statistic processing memories of program under display. No No 420 (01A4) Statistic result request (3000-series) Requests statistic processing result. No Yes 421 (01A5) Memory switch set 1 (3000-series) Sets memory switches. Yes No 422 (01A6) Memory switch set 2 (3000-series) Sets memory switches. Yes No 423 (01A7) Simple AVG times set (3000-series) Taking the simple average as the averaging method, sets the averaging times per measurement interval 4. Yes No 424 (01A8) AVG move interval set (3000-series) Taking the average move as the averaging method, sets the measurement interval number. Yes No 425 (01A9) AVG move (H) times set (3000-series) Taking the average move and highspeed data output as the averaging method, sets the averaging times per measurement interval 4. Yes No 426 (01AA) AVG move (L) times set (3000-series) Taking the average move and lowspeed data output as the averaging method, sets the averaging times per measurement interval 4. Yes No 427 (01AB) Automatic detection set (3000-series) Sets work automatic detection function. Yes No 428 (01AC) Automatic detection release (3000-series) Releases the settings of work automatic detection function. No No 429 (01AD) Automatic detection list request (3000-series) Requests the settings of work automatic detection function. No Yes 430 (01AE) 3Z4L initialize (3000-series) Clears the 3Z4L, sets the mm unit, sets the memory unit, does not processes statistics, and clears all statistic memory. Yes No 431 (01AF) Measurement condition set (4000-series) Sets measurement conditions. Yes No 432 (01B0) Measurement condition release (4000-series) Releases measurement conditions that have been set. Yes No 433 (01B1) Measurement condition list re- Requests the measurement condiquest (4000-series) tions that have been set and other settings. No Yes 434 (01B2) Single run measurement start (4000-series) When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results. No Yes 435 (01B3) Deflection measurement start (4000-series) Starts a deflection measurement. No No 436 (01B4) Continuous measurement start (scan) (4000-series) Starts a continuous measurement. The scan notification method is used for receive data. No Yes 378 Function Ladder interface Send word Receive allocation word allocation Notes Appendix K 3Z4L Laser Micrometer Protocol Sequence No. Communications sequence name 437 (01B5) Continuous measurement start (interrupt) (4000-series) 438 (01B6) Measurement termination (4000-series) Data request (4000-series) Function Starts a continuous measurement. The interrupt notification method is used for receive data. Terminates continuous measurement. 439 (01B7) Requests measurement data in the idle measurement status or the latch data generated by the measurement command. 440 (01B8) Forced positive zero Sets the forced zero direction to (4000-series) positive (+). 441 (01B9) Forced negative zero Sets the forced zero direction to (4000-series) negative (–). 442 (01BA) Forced zero release (4000-se- Releases the forced zero direction. ries) 443 (01BB) 3Z4L initialize (4000-series) Clears the 3Z4L, sets the mm unit, and clears the memory unit settings. 444 (01BC) General-purpose command 1 Used to send data of a specified data length, and receive only OK as the receive data. Ladder interface Send word Receive allocation word allocation No Yes No No *1 No Yes No No No No No No Yes No Yes No 445 (01BD) General-purpose command 2 Used to send data of a specified data length, and receive data other than OK. Yes Yes 446 (01BE) High calibration set Sets the Laser Micrometer’s high calibration. Sets the Laser Micrometer’s low calibration. Yes No Yes No 447 (01BF) Low calibration set Notes See Note 2 *1 Depends on the measurement contents. Note 1. Sequences with interrupt notification are not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 3. The hexadecimal equivalents of sequences numbers are given in parentheses. 379 Appendix K 3Z4L Laser Micrometer Protocol Connections The connections for the 3Z4L Laser Micrometer Protocol are shown below. RS-232C Connection Sensor Signal cable CS1j Serial Communications Board/ Unit RS-232C Port Controller Serial Communications Unit/Board: D-sub 9 pin (female) Signal name FG SD RD RTS CTS DSR DTR SG Controller: D-sub 25 pin (female) Pin No. Pin No. 1 2 3 4 5 7 8 9 1 2 3 4 5 6 7 20 Signal name FG TXD RXD RTS CTS DSR SG DTR DIP Switch Settings Shown below are the settings of 3Z4L-3000, 3Z4L-4000-series DIP switches required to use the system protocol sequences. 3Z4L-3000 Series • DIP Switch 1 No. Setting Baud rate 1 2 Status ON/OFF ON/OFF 3 Handshaking procedure ON/OFF 4 RS-232C interface use selection ON/OFF 5 6 ON/OFF ON/OFF • DIP Switch 2 No. 1 2 Setting Selection for measurement section 3 ON/OFF ON/OFF Setting of minimum read value ON/OFF 7 Setting of transparent body measurement function ON/OFF 8 Setting of simultaneous measurement function ON/OFF 5 6 Set these settings according to the sensor connected. ON/OFF 4 380 Status ON/OFF ON/OFF Set these settings for 4 digits in the decimal portion. Appendix K 3Z4L Laser Micrometer Protocol • DIP Switch 3 No. Setting Setting of measurement function by 2 measurement instruments 1 2 3 Status ON/OFF ON/OFF ON/OFF 4 ON/OFF 5 Error data exclusion function ON/OFF 6 Multistep selection function ON/OFF This protocol does not support the error data exclusion function 3Z4L-4000 Series • DIP Switch 1 No. Setting Baud rate 1 2 Status ON/OFF ON/OFF 3 Hand-shake procedure ON/OFF 4 Delimiter ON/OFF 5 ON/OFF RS-232C interface use selection 6 7 8 ON/OFF ON/OFF ON/OFF • DIP Switch 2 No. 1 2 Setting Selection for measurement section 3 Status ON/OFF ON/OFF ON/OFF 4 ON/OFF ON/OFF 6 Setting of minimum read value 7 Display unit ON/OFF 8 External command setting ON/OFF 5 Set these settings according to the sensor connected. ON/OFF Set these settings for 4 digits in the decimal portion. 381 Appendix K 3Z4L Laser Micrometer Protocol Delimiter Control Code Setting 3Z4L-4000 Series The delimiter control codes must be set on DIP switch SW1 for the 3Z4L-4000 Series. Turn off pins 4 and 5, set the delimiter codes to CR+LF, and set the delimiter code control setting in the sequence to CR+LF. See the setting for CR+LF in the following diagram. 1 2 3 4 5 6 7 8 Turn OFF. Turn OFF (to use a general-purpose interface) Turn ON (to use a general-purpose interface) Delimiter Setting Delimiter CR+LF CR LF Pin 4 OFF ON OFF Pin 5 OFF OFF ON Pin Handshaking ON: OFF: Control (recognize DRT input) 3-wire method (non-protocol) Baud Rate Baud rate 1200 2400 Pin 1 OFF ON Pin 2 OFF OFF Pin 382 4800 9600 OFF ON ON ON Appendix K 3Z4L Laser Micrometer Protocol 3Z4L-3000 Series The delimiter control code does not need to be set on the DIP switch for the 3Z4L-3000 Series. Set the delimiter control codes in the sequence to CR+LF for the send code and to CR or CR+LF for the receive code. See the settings in the following diagram. 1 2 3 4 5 6 Turn OFF. Turn OFF (to use a general-purpose interface) Turn ON (to use a general-purpose interface) Handshaking ON: OFF: Control (recognize DRT input) 3-wire method (non-protocol) Baud Rate Baud rate 1200 2400 4800 9600 Pin 1 OFF ON OFF ON Pin 2 OFF OFF ON ON Pin The High-speed 3Z4L-3000-series Meters must have the delimiter control codes set using the memory switches. Set both the send and receive codes to CR+LF. Protocol Configuration The configuration of the 3Z4L Laser Micrometer Protocol for the 5000 and 6000 Series is shown below. Sequence No. Operation Communications sequence name 5000 Series Yes 6000 Series Yes Memory switch set No*1 No*1 402 (0192) mm unit set Yes Yes 403 (0193) E unit set Yes Yes 404 (0194) Calibration set No No 405 (0195) Calibration release Yes Yes 406 (0196) Program number set (3000-series) No*1 Yes 407 (0197) Measurement condition set (3000-series) No No 408 (0198) Measurement condition release (3000-series) No No 409 (0199) Measurement condition list request (3000-series) No No 410 (019A) Single run measurement start (3000-series) Yes Yes 411 (019B) Zero run measurement start (3000-series) Yes Yes 412 (019C) Continuous measurement start (scan) (3000-series) No Yes 413 (019D) Continuous measurement start (interrupt) (3000-series) No Yes No Yes 400 (0190) 3Z4L clear 401 (0191) 414 (019E) Measurement termination (3000-series) 415 (019F) Data request (3000-series) No Yes 416 (01A0) Statistic processing execution (3000-series) Yes Yes 383 Appendix K 3Z4L Laser Micrometer Protocol Sequence No. Communications sequence name Operation 5000 Series 6000 Series 417 (01A1) Statistic processing non-execution (3000-series) Yes Yes 418 (01A2) All statistic memory clear (3000-series) Yes Yes 419 (01A3) Statistic memory clear (3000-series) Yes Yes 420 (01A4) Statistic result request (3000-series) No No 421 (01A5) Memory switch set 1 (3000-series) No*1 No*1 422 (01A6) Memory switch set 2 (3000-series) No*1 No*1 423 (01A7) Simple AVG times set (3000-series) Yes Yes 424 (01A8) AVG move interval set (3000-series) Yes Yes 425 (01A9) AVG move (H) times set (3000-series) Yes Yes 426 (01AA) AVG move (L) times set (3000-series) Yes*2 No 427 (01AB) Automatic detection set (3000-series) No No 428 (01AC) Automatic detection release (3000-series) Yes Yes 429 (01AD) Automatic detection list request (3000-series) Yes Yes Yes*3 Yes*3 430 (01AE) 3Z4L initialize (3000-series) 431 (01AF) Measurement condition set (4000-series) No No 432 (01B0) Measurement condition release (4000-series) No No 433 (01B1) Measurement condition list request (4000-series) No No 434 (01B2) Single run measurement start (4000-series) Yes No 435 (01B3) Deflection measurement start (4000-series) Yes*4 No 436 (01B4) Continuous measurement start (scan) (4000-series) Yes No 437 (01B5) Continuous measurement start (interrupt) (4000-series) Yes No 438 (01B6) Measurement termination (4000-series) Yes No 439 (01B7) Data request (4000-series) Yes No 440 (01B8) Forced positive zero (4000-series) Yes Yes 441 (01B9) Forced negative zero (4000-series) Yes Yes 442 (01BA) Forced zero release (4000-series) 443 (01BB) 3Z4L initialize (4000-series) 444 (01BC) Yes Yes Yes*3 Yes*3 General-purpose command 1 Yes Yes 445 (01BD) General-purpose command 2 Yes Yes 446 (01BE) High calibration set No No 447 (01BF) Low calibration set No No Note 1. *Normal responses will be returned for these sequences for 5000-series and 6000-series Laser Micrometers, but no processing will be performed. 2. *This sequence will be processed the same as sequence No. 425 AVG move (H) times set for 5000-series Laser Micrometers. 3. *Memory switch settings will be ignored for these sequences for 5000-series and 6000-series Laser Micrometers. 4. *This sequence will be processed the same as sequence No. 411 Zero run measurement start for 5000-series Laser Micrometers. 384 Appendix K 3Z4L Laser Micrometer Protocol 3Z4L Clear (Sequence No. 400 (Hex 0190)) This sequence resets errors, data, analog output, and decision result, and puts the Laser Micrometer into standby. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Memory Switch Set (Sequence No. 401 (Hex 0191)) This sequence sets memory switches and the area for the work position LED. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Offset Z V Data Contents (data format) 3000-series 4000-series +0 Number of send data words (4 digits Hex) 0003 (fixed) 0003 (fixed) +1 w (1 digit BCD) Using buzzer sound: 0 to 3 Number of digits for extinguishing indicator: 0 to 2 x (1 digit BCD) Automatic latch release time: 0 to 9 I/O IF RUN Input: 0 or 1 y (1 digit BCD) Using print timer, the setting for simultaneous measurement: 0 to 3 (high-speed), 0 to 1 (other) Display of Err–0: 0 or 1 z (1 digit BCD) Display of the comma for 1/1000s digit, number of display digits: 0 to 5 (high-speed), 0 to 3 (other) Averaging method: 0 to 2 (high-speed), 0 (other) v (1 digit BCD) Measurement interval 4: 0 to 6 Use of comma: 0 or 1 +2 Receive Data Word Allocation (4th Operand of PMCR(260)) None. mm Unit Set (Sequence No. 402 (Hex 0192)) This sequence sets the display unit to mm. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. E Unit Set (Sequence No. 403 (Hex 0193)) This sequence sets the display unit to E. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. 385 Appendix K 3Z4L Laser Micrometer Protocol Calibration Set (Sequence No. 404 (Hex 0194)) This sequence calibrates the Laser Micrometer. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Decimal portion +2 (Undefined) Sign +3 (Undefined) High calibration gauge dimension Decimal portion +4 +5 Decimal integer portion (Undefined) +6 (Decimal integer portion) Sign (Undefined) Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0007 (fixed) +1 HC gauge dimension (Decimal portion) (4 digits BCD) 0000 to 9999 +2 +3 +4 to +6 Low calibration gauge dimension Data Example –123.4567 +1 4567 +2 0123 +3 2D00 Example –123.4567 HC gauge dimension (integer portion) (3 digits BCD) 000 to 999 HC gauge dimension (Sign) (ASCII 1 character) if +: 20(‘ ’) if –: 2D(‘–’) LC gauge dimensions Same as HC gauge dimensions +1 4567 +2 0123 +3 2D00 Note 1. Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser Micrometer. If this sequence (No. 404) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged. 2. The HC gauge dimension and LC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Calibration Release (Sequence No. 405 (Hex 0195)) This sequence releases the calibration of the Laser Micrometer. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence releases both the high and low calibration. 386 Appendix K 3Z4L Laser Micrometer Protocol Program Number Set (3000-series) (Sequence No. 406 (Hex 0196)) This sequence switches the program number to a specified number. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Program number (1 digit BCD) Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Program number (1 digit BCD) 0 to 9 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Retry processing is not performed for this sequence. Measurement Condition Set (3000-series) (Sequence No. 407 (Hex 0197)) This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Unused) +2 Segment number (SG) +3 +4 +5 (Undefined) +7 +8 (Undefined) Sign +11 (Undefined) Sign +14 (Undefined) Sign +17 (Undefined) Sign +20 (Undefined) Sign +23 (Undefined) Sign +24 +25 +26 +29 (Undefined) Integer portion Multistep selection limit value (L1) (Undefined) Integer portion Multistep selection limit value (L2) (Undefined) Integer portion Multistep selection limit value (L3) (Undefined) Integer portion Multistep selection limit value (L4) (Undefined) Decimal portion (Undefined) Sign +27 +28 Upper limit value (LH) Decimal portion +21 +22 Integer portion Decimal portion +18 +19 (Undefined) Decimal portion +15 +16 Lower limit value (LL) Decimal portion +12 +13 Integer portion Decimal portion +9 +10 Measurement interval number (M) Decimal portion +6 Integer portion Multistep selection limit value (L5) (Undefined) Decimal portion (Undefined) Sign Integer portion Multistep selection limit value (L6) (Undefined) 387 Appendix K 3Z4L Laser Micrometer Protocol Decimal portion +30 +31 +32 +33 (Undefined) Reference value (REF) Integer portion Sign (Undefined) (Undefined) Analog output scale number (SCL) +34 Decimal portion +36 +37 +38 +39 Offset classification (OF) (Undefined) +35 (Undefined) Integer portion Sign Offset value (Undefined) (Undefined) +40 (Undefined) +41 (Undefined) Data output conditions (PR) Schedule output timer Sample measurement pulse (PRT) (SMP) +42 (Undefined) +43 +44 (Unused) +45 (Unused) +46 0 +47 0 +48 0 +49 0 +50 0 +51 0 +52 0 +53 0 Setting Yes/No flags Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0054 (fixed) +1 Unused Undefined +2 to +4 Segment number (ASCII 6 characters) Combination of 31(‘1’) to 36(‘6’), 20(‘ ’) +5 Measurement interval number (1 digit BCD) 1 to 4 +6 Lower limit value (decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 +8 Lower limit value (Sign) (ASCII 1 character) if +: 20(‘ ’) if –: 2D(‘–’) +9 to +11 Upper limit value Same as lower limit values +12 to +14 Multistep selection limit value (L1) Same as lower limit values +15 to +17 Multistep selection limit value (L2) Same as lower limit values +18 to +20 Multistep selection limit value (L3) Same as lower limit values +21 to +23 Multistep selection limit value (L4) Same as lower limit values +24 to +26 Multistep selection limit value (L5) Same as lower limit values +27 to +29 Multistep selection limit value (L6) Same as lower limit values +7 388 Sample measurement classification Data Example –123.4567 +6 000 to 999 4567 +7 0123 +8 2D00 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +30 to +32 Reference value Same as lower limit values +33 Analog output scale number (1 digit BCD) 1 to 3 +34 to +35 Offset classification (ASCII 3 characters) 4F4620 (“OF”), 4F4D20 (“OM”) +36 to +38 Offset value Same as lower limit values +39 Data output conditions (1 digit BCD) 0 to 6 +40 Scheduled output timer (3 digits BCD) 000 to 999 +41 Sample measurement pulse (3 digits BCD) 000 to 999 +42 to +43 Sample measurement classification (ASCII 3 characters) 415647 (“AVG”), 4D4158 (“MAX”) 4D494E (“MIN”), 524E47 (“RNG”) +44 to +45 Unused Undefined +46 Yes/No for segment setting (1 digit BCD) Set: Yes/No for measurement interval number setting (1 digit BCD) Set: Yes/No for upper/lower limit value setting (1 digit BCD) Set: Yes/No for multistep selection limit value (1 digit BCD) Set: Yes/No for reference setting (1 digit BCD) Set: +51 Yes/No for offset value setting (1 digit BCD) Set: +52 Yes/No for data output condition setting (1 digit BCD) Set: Yes/No for sample measurement pulse setting (1 digit BCD) Set: +47 +48 +49 +50 +53 Data 1 (SG) Don’t set: 0 1 (M) Don’t set: 0 1 (LL,LH) Don’t set: 0 1 (L1,L2,L3,L4,L5,L6) Don’t set: 0 1 (REF,SCL) Don’t set: 0 1 (OF or OM) Don’t set: 0 1 (PR,PRT) Don’t set: 0 1 (SMP, MAX or MIN or RNG or AVG) Don’t set: 0 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. This sequence cannot be used to set the error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 2. The following settings must be made together with this sequence; they cannot be set separately. Lower limit, upper limit Multistep selection limit Reference value, analog output scale number Data output conditions, scheduled print timer 3. The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion. 389 3Z4L Laser Micrometer Protocol Appendix K Measurement Condition Release (3000-series) (Sequence No. 408 (Hex 0198)) This sequence releases the measurement conditions that have been set. Send Data Word Allocation (3rd Operand of PMCR(260)) Send data word allocation is similar to that of sequence No. 407 (Measurement Condition Set). However, only the setting Yes/No flags at +46 to +53 from the send data leading word can be used. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. The following conditions are used when the measurement conditions are released: Segment becomes 1, measurement interval becomes 1, the number of sample measurement pulses becomes 1. 2. The following conditions cannot be released with this sequence: error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 3. The following settings cannot be released separately using this sequence. Lower limit, Upper limit Multistep selection limit Reference value, analog output scale number Data output conditions, scheduled print timer Measurement Condition List Request (3000-series) (Sequence No. 409 (Hex 0199)) This sequence requests the measurement condition settings that have been set and other settings. Send Data Word Allocation (3rd Operand of PMCR(260)) None. 390 Appendix K 3Z4L Laser Micrometer Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) First word of send data +0 Number of receive data words (Undefined) +1 Program number (P) +2 Segment number (SG) +3 +4 (Undefined) +5 Measurement interval number (M) Decimal portion +6 +7 (Undefined) +8 Sign Integer portion Lower limit value (LL) (Undefined) Decimal portion +9 +10 (Undefined) +11 Sign Integer portion Upper limit value (LH) (Undefined) Decimal portion +12 +13 (Undefined) +14 Sign Integer portion Multistep selection limit value (L1) (Undefined) Decimal portion +15 +16 (Undefined) Integer portion +17 Sign (Undefined) Multistep selection limit value (L2) Decimal portion +18 +19 (Undefined) +20 Sign Integer portion Multistep selection limit value (L3) (Undefined) Decimal portion +21 +22 (Undefined) Integer portion +23 Sign (Undefined) Multistep selection limit value (L4) Decimal portion +24 +25 (Undefined) Integer portion +26 Sign (Undefined) Multistep selection limit value (L5) Decimal portion +27 +28 (Undefined) Integer portion +29 Sign (Undefined) Multistep selection limit value (L6) Decimal portion +30 +31 (Undefined) Integer portion +32 Sign (Undefined) (Undefined) +33 Reference value (REF) Analog output scale number (SCL) +34 (Undefined) +35 Decimal portion +36 +37 (Undefined) Integer portion +38 Sign (Undefined) +40 (Undefined) +41 (Undefined) Scheduled output timer Sample measurement pulse +39 (Undefined) +44 +45 Offset value (LH) Data output condition (PR) +42 +43 Offset classification (OF) (PRT) (SMP) Sample measurement classification Statistical processing calculation classification (Undefined) 391 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 002E (0046 decimal) (fixed) +1 Program number (1 digit BCD) 0 to 9 +2 to +4 Segment number (ASCII 6 characters) Combination of 31(‘1’) to 36(‘6’), 20(‘ ’) +5 Measurement interval number (1 digit BCD) 1 to 4 +6 Lower limit value (Decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 +8 Lower limit value (Sign) (BIN) If +: 0 If – : F +9 to +11 Upper limit value Same as lower limit values +12 to +14 Multistep selection limit value (L1) Same as lower limit values +15 to +17 Multistep selection limit value (L2) Same as lower limit values +18 to +20 Multistep selection limit value (L3) Same as lower limit values +21 to +23 Multistep selection limit value (L4) Same as lower limit values +24 to +26 Multistep selection limit value (L5) Same as lower limit values +27 to +29 Multistep selection limit value (L6) Same as lower limit values +30 to +32 Reference value Same as lower limit values +33 Analog output scale number (1 digit BCD) 1 to 3 +34 to +35 Offset classification (ASCII 3 characters) 4F4620 (“OF”), 4F4D20 (“OM”) +36 to +38 Offset value Same as lower limit values +39 Data output condition (1 digit BCD) 0 to 6 +40 Scheduled output timer (3 digits BCD) 000 to 999 +41 Sample measurement pulse (3 digits BCD) 000 to 999 +42 to +43 Sample measurement classification (ASCII 3 characters) 415647 (“AVG”), 4D4158 (“MAX”) 4D494E (“MIN”), 524E47 (“RNG”) +44 to +45 Statistical processing calculation classification (ASCII 3 characters) 535420 (“ST”), 4E5354 (“NST”) +7 Data Example –123.4567 000 to 999 +6 4567 +7 0123 +8 F000 Note This sequence cannot be used to request the lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function). 392 Appendix K 3Z4L Laser Micrometer Protocol Single Run Measurement Start (3000-series) (Sequence No. 410 (Hex 019A)) When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data stor- +0 age words +1 Number of receive data words (Undefined) Program number Decision result +2 Decimal portion +3 +4 (Undefined) +5 Sign Integer portion Measurement value (Undefined) Decimal portion +6 +7 (Undefined) Integer portion Sign (Undefined) +8 Deviation value Offset Contents (data format) +0 Number of receive data words (4 digit Hex) With no reference setting: 0006 With reference setting: 0009 +1 Program number (1 digit BCD) 0 to 9 +2 Decision result (ASCII 2 characters) With no limit setting: 0000 Measurement value (decimal portion) (4 digits BCD) Measurement value (integer portion) (3 digits BCD) 0000 to 9999 +5 Measurement value (Sign) (BIN) If +: 0 +6 to +8 Deviation value Same as measurement value *The deviation will be stored in this area only when reference setting is made. +3 +4 Data With limit setting: 2B4E (“+N”), 4F4B (“OK”), 2D4E (“–N”) Example –123.4567 +3 000 to 999 4567 +4 0123 +5 F000 If –: F Zero Run Measurement Start (3000-series) (Sequence No. 411 (Hex 019B)) If the sample measurement condition is zero, a zero run measurement is started. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note The zero run measurement keeps measuring until sequence No. 414 (Measurement Termination) is executed. 393 3Z4L Laser Micrometer Protocol Appendix K Continuous Measurement Start (Scan) (3000-series) (Sequence No. 412 (Hex 019C)) A continuous measurement is started. The scan notification method is used for the receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 414 (Measurement Termination) to end the sequence. Continuous Measurement Start (Interrupt) (3000-series) (Sequence No. 413 (Hex 019D)) A continuous measurement is started. The interrupt notification method is used for the receive data and the interrupt No. is 101. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 414 (Measurement Termination) to end the sequence. 3. Sequences No. 413 and No. 437 (Continuous Measurement Start with Interrupt) not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. Measurement Termination (3000-series) (Sequence No. 414 (Hex 019E)) This sequence terminates a continuous measurement. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) For continuous measurement: Not available For Zero Run Measurement The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Note This sequence may be aborted it is executed during continuous measurements. Measurements will be terminated even if the sequence is aborted. The sequence will be aborted if executed when the Laser Micrometer is sending measurement results. The chances that the sequence will be aborted are higher if the scheduled data output value is set to a lower value. Data Request (3000-series) (Sequence No. 415 (Hex 019F)) This sequence requests display data in the idle measurement status or the latch data generated by the measurement command. 394 3Z4L Laser Micrometer Protocol Appendix K Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start). Statistic Processing Execution (3000-series) (Sequence No. 416 (Hex 01A0)) This sequence lights the statistic processing LED and implements the statistic processing. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Statistic Processing Non-execution (3000-series) (Sequence No. 417 (Hex 01A1)) This sequence turns the statistic processing LED off and does not carry out the statistic processing. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. All Statistic Memory Clear (3000-series) (Sequence No. 418 (Hex 01A2)) This sequence clears statistic processing memories of all programs. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Statistic Processing Memory Clear (3000-series) (Sequence No. 419 (Hex 01A3)) This sequence clears statistic processing memories of the program under display. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Statistic Result Request (3000-series) (Sequence No. 420 (Hex 01A4)) This sequence requests the statistic processing results. Send Data Word Allocation (3rd Operand of PMCR(260)) None. 395 Appendix K 3Z4L Laser Micrometer Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 Program number (P) +2 Number of statistic data (N) (Undefined) +3 Decimal portion +4 +5 (Undefined) Integer portion +6 Sign (Undefined) Average value (AVG) Decimal portion +7 +8 (Undefined) Integer portion +9 Sign (Undefined) Maximum value (MAX) Decimal portion +10 +11 (Undefined) +12 Sign Minimum value (MIN) Integer portion (Undefined) Decimal portion +13 +14 (Undefined) +15 Sign Range (R) Integer portion (Undefined) Decimal portion +16 +17 (Undefined) Integer portion +18 Sign (Undefined) Offset Standard deviation (SD) Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0013 (0019 decimal) (fixed) +1 Program number (1digit BCD) 0 to 9 +2 to +3 Number of statistic data (6 digits BCD) 000000 to 999999 +4 Average value (decimal portion) (4 digits BCD) 0000 to 9999 +5 Average value (integer portion) (4 digits BCD) 000 to 999 +6 Average value (Sign) (BIN) If +: 0 If –: F +7 to +9 Maximum value Same as average value +10 to +12 Minimum value Same as average value +13 to +15 Range Same as average value +16 to +18 Standard deviation Same as average value Example –123.4567 +4 4567 +5 0123 +6 F000 Note The number of digits of the Decimal portion is fixed to 4 digits. If a deviation calculation results in a value with 5 decimal places, it will be stored with one digit overflowing into the integer portion. Examples: The value –0.1234 is stored as follows: Area of decimal portion: 1234; Area of integer portion: 0000; Sign area: F000 The value –0.12345 is stored as follows: Area of decimal portion: 2345; Area of integer portion: 0001; Sign area: F000 396 Appendix K 3Z4L Laser Micrometer Protocol Memory Switch Set 1 (3000-series, High-speed Type) (Sequence No. 421 (Hex 01A5)) This sequence sets memory switches. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Offset Z V Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 w (1 digits BCD) 0: For single run or zero run measurement start displaying ‘–––.’ 1: For single run or zero run measurement start displaying the previous measured value x (1 digit BCD) 0: Perform single run measurement to the RUN signal of I/O IF 1: Repeat measurement while the RUN signal of I/O IF is input y (1 digit BCD) *0: RS-232C Delimiter CR+LF 1: RS-232C Delimiter CR 2: RS-232C Delimiter LF z (1 digit BCD) 0: RS-232C no parity check 1: RS-232C odd parity check 2: RS-232C even parity check +2 v (1 digit BCD) 0: Displaying ‘Err-0’ 1: Displaying ‘0’ Note Settings marked with asterisks are required for this protocol. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 2. The setting (y, z) of RS-232C takes effect when the power supply is turned back on. 397 Appendix K 3Z4L Laser Micrometer Protocol Memory Switch Set 2 (3000-series, High-speed Type) (Sequence No. 422 (Hex 01A6)) This sequence sets memory switches. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words W X Y (Undefined) +2 Z V Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0003 (fixed) Data +1 w (1 digit BCD) 0: Work automatic detection is not performed 1: Work automatic detection is performed Diameter detection method (1 scan) 2: Work automatic detection is performed Diameter detection method (8 scan) 3: Work automatic detection is performed Position detection method (1 scan) +2 x (1 digit BCD) For expansion 0 (fixed) y (1 digit BCD) For expansion 0 (fixed) z (1 digit BCD) For expansion 0 (fixed) v (1 digit BCD) *0: Error data exclusion function is not used 1: Error data exclusion function is used Note Settings marked with asterisks are required for this protocol. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. Simple AVG Times Set (3000-series, High-speed Type) (Sequence No. 423 (Hex 01A7)) This sequence uses the simple average as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 1 to 2048 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 398 Appendix K 3Z4L Laser Micrometer Protocol AVG Move Interval Set (3000-series, High-speed Type) (Sequence No. 424 (Hex 01A8)) This sequence uses the average move as the averaging method and sets the measurement interval number. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Measurement interval number Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Measurement interval number (1 digit BCD) 1 to 4 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. AVG Move (H) Times Set (3000-series, High-speed Type) (Sequence No. 425 (Hex 01A9)) This sequence uses the average move and high-speed data output as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 16 to 2048 (32 to 2048 for 5000/6000 Series) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. AVG Move (L) Times Set (3000-series, High-speed Type) (Sequence No. 426 (Hex 01AA)) This sequence uses the average move and low-speed data output as the averaging method and sets the averaging times per measurement interval 4. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of averaging times Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Number of averaging times (4 digits BCD) 32 to 2048 Receive Data Word Allocation (4th Operand of PMCR(260)) None. 399 Appendix K 3Z4L Laser Micrometer Protocol Note 1. This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 2. This sequence will be processed the same as sequence No. 425 AVG move (H) times set for 5000-series Laser Micrometers. Automatic Detection Set (3000-series, High-speed Type) (Sequence No. 427 (Hex 01AB)) This sequence sets the work automatic detection function. Send Data Word Allocation (3rd Operand of PMCR(260)) Receive data storage words +0 +1 Number of send data words (Undefined) The number of measuring times +2 Invalid time +3 Decimal portion (Undefined) +4 Integer portion Sign +5 Detection lower limit (Undefined) Decimal portion +6 (Undefined) +7 Integer portion Sign +8 Detection upper limit (Undefined) Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0009 (fixed) +1 Number of measurements (3 digits BCD) 001 to 999 +2 Invalid time (4 digits BCD) 0001 to 9999 +3 Detection lower limit (decimal portion) (4 digits BCD) 0000 to 9999 Detection lower limit (integer portion) (3 digits BCD) 000 to 999 +5 Detection lower limit (Sign) (ASCII 1 character) If +: 20 (‘ ’) If – : 2D (‘–’) +6 to +8 Detection upper limit Same as detection lower limit +4 Data Example –123.4567 +3 4567 +4 0123 +5 2D00 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 2. The detection lower and upper limit must be set with 3 digits for the integer portion and 4 digits for the decimal portion. Automatic Detection Release (3000-series, High-speed Type) (Sequence No. 428 (Hex 01AC)) This sequence releases the setting of work automatic detection function. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 400 Appendix K 3Z4L Laser Micrometer Protocol Automatic Detection List Request (3000-series, High-speed Type) (Sequence No. 429 (Hex 01AD)) This sequence requests the settings of work automatic detection function. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 Number of receive data words (Undefined) The number of measuring times +2 Invalid time +3 Decimal portion +4 (Undefined) +5 Sign Integer portion Detection lower limit (Undefined) Decimal portion +6 +7 (Undefined) Integer portion +8 Sign (Undefined) Detection upper limit Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0009 (fixed) +1 The number of measuring times (3 digits BCD) 000 to 999 +2 Invalid time (4 digits BCD) 0001 to 9999 +3 Detection lower limit (decimal portion) (4 digits BCD) Detection lower limit (integer portion) (3 digits BCD) 0000 to 9999 +5 Detection lower limit (Sign) (BIN) If +: 0 If –: F +6 to +8 Detection upper limit Same as detection lower limit +4 Data 000 to 999 Example –123.4567 +3 4567 +4 0123 +5 F000 Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON. 3Z4L Initialize (3000-series) (Sequence No. 430 (Hex 01AE)) This sequence clears the 3Z4L, sets the mm unit, sets memory switches, does not process statistics, and clears the statistic memory. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Memory switch settings will be ignored for this sequence for 5000-series and 6000-series Laser Micrometers. 401 Appendix K 3Z4L Laser Micrometer Protocol Measurement Condition Set (4000-series) (Sequence No. 431 (Hex 01AF)) This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Segment number (SG) +2 (Undefined) Measurement interval number (M) Decimal portion +3 +4 (Undefined) +5 Sign +7 (Undefined) +8 Sign (Undefined) Integer portion (Undefined) +11 Sign (Undefined) Integer portion (Undefined) (Unused) +14 (Unused) 402 Analog output scale number (SCL) (Unused) +15 +18 Reference value (REF) (Undefined) +13 +17 Upper limit value (LH) Decimal portion +9 +10 +16 Lower limit value (LL) Decimal portion +6 +12 Integer portion (Undefined) Data output conditions (PR) (Undefined) Data output timer (BCD 3 digits) (PRT) (Undefined) Number of seconds for latch timer (RLT) +19 0 +20 0 +21 0 +22 0 +23 0 +24 0 Setting Yes/No flags Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0019 (0025 decimal) (fixed) Data +1 Segment number (1 digit BCD) 1 to 5 +2 Measurement interval number (1 digit BCD) 1 to 7 +3 Lower limit value (Decimal portion) (4 digits BCD) 0000 to 9999 +4 Lower limit value (integer portion) (3 digits BCD) 000 to 999 Example –123.4567 +3 +5 Lower limit value (Sign) (ASCII 1 character) If +: 20 (‘ ’) If – : 2D (‘–’) +6 to +8 Upper limit value Same as lower limit value +9 to +11 Reference value Same as lower limit value +12 Analog output scale number (1 digit BCD) 0 to 3 +13 to +15 Unused +16 Data output conditions (1 digit BCD) 0 to 6 +17 Data output timer value (3 digits BCD) 000 to 999 +18 Number of seconds for latch timer (2 digits BCD) 00 to 99 +19 Yes/No for segment setting (1 digit BCD) Set: 1(SG) Don’t set: 0 +20 Yes/No for measurement interval number setting (1 digit BCD) Set: 1(M) Don’t set: 0 +21 Yes/No for upper/lower limit value setting (1 digit BCD) Set: 1(LL, LH) Don’t set: 0 +22 Yes/No for reference setting (1 digit BCD) Set: 1(REF, SCL) Don’t set: 0 +23 Yes/No for data output condition setting (1 digit BCD) Set: 1(PR, PRT) Don’t set: 0 +24 Yes/No for latch timer setting (1 digit BCD) Set: 1(RLT) Don’t set: 0 4567 +4 0123 +5 2D00 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. The following settings must be made together with this sequence; they cannot be set separately. Lower limit, upper limit Reference value, data output timer Data output conditions, scheduled print timer 2. The limit value and reference value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion. 403 Appendix K 3Z4L Laser Micrometer Protocol Measurement Condition Release (4000-series) (Sequence No. 432 (Hex 01B0)) This sequence clears the measurement conditions that have been set. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of sequence No. 431 (Measurement Condition Setting). However, only the setting Yes/No flags at +19 to +24 from the send data leading word can be used. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. The following conditions are used when the measurement conditions are released: Segment becomes 1 and the measurement interval becomes 1. 2. The following settings cannot be cleared separately using this sequence. They all must be cleared at the same time. Lower limit, Upper limit Data output conditions, Scheduled print timer The scale (SCL) and data output timer (PRT) cannot be cleared. 3. This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. Measurement Condition List Request (4000-series) (Sequence No. 433 (Hex 01B1)) This sequence requests the measurement condition settings that have been set and other settings. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 (Undefined) Segment number (SG) +2 (Undefined) Measurement interval number (M) Decimal portion +3 +4 (Undefined) Integer portion +5 Sign (Undefined) Decimal portion +6 +7 (Undefined) Integer portion +8 Sign (Undefined) Upper limit value (LH) Decimal portion +9 +10 (Undefined) Integer portion +11 Sign (Undefined) +12 Lower limit value (LL) (Undefined) Reference value (REF) Analog output scale number (SCL) +13 Forced zero number (ZERO+) +14 (Undefined) +15 +16 +17 +18 404 (Undefined) (Undefined) Data output condition (PR) Data output timer (BCD 3 digits) (PRT) (Undefined) Number of seconds for latch timer (RLT) Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0013 (0019 decimal) (fixed) +1 Segment number (1 digit BCD) 1 to 5 +2 Measurement interval number (1 digit BCD) 1 to 7 +3 Lower limit value (Decimal portion) (4 digits BCD) Lower limit value (Integer portion) (3 digits BCD) 0000 to 9999 +5 Lower limit value (Sign) (BIN) If +: 0 If –: F +6 to +8 Upper limit value Same as lower limit value +9 to +11 Reference value Same as lower limit value +12 Analog output scale number (1 digit BCD) 0 to 3 +13 to +15 Forced zero number (ASCII 5 characters) 5A45524F2B (“ZERO+”) 4E4F524D20 (“NORM ”) 5A45524F2D (“ZERO–”) +16 Data output condition (1 digit BCD) 0 to 6 +17 Data output timer value (3 digits BCD) 000 to 999 +18 Number of seconds for latch timer (2 digits BCD) 00 to 99 +4 Data Example –123.4567 +3 000 to 999 4567 +4 0123 +5 F000 Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON. Single Run Measurement Start (4000-series) (Sequence No. 434 (Hex 01B2)) When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Decision result +2 Decimal portion +3 (Undefined) +4 Sign Integer portion Measurement value (Undefined) Decimal portion +5 +6 (Undefined) Integer portion +7 Sign (Undefined) Deviation value 405 Appendix K 3Z4L Laser Micrometer Protocol Offset Contents (data format) +0 Number of receive data words (4 digits Hex) With no reference setting: 0005 +1 Decision result (ASCII 2 characters) With no limit setting: 0000 Measurement value (decimal portion) (4 digits BCD) Measurement value (integer portion) (3 digits BCD) 0000 to 9999 Measurement value (Sign) (BIN) If +: 0 Deviation value Same as measurement value +2 +3 +4 +5 to +7 Data With reference setting: 0008 With limit setting: 2B4E (“+N”), 4F4B (“OK”), 2D4E (“–N”) 000 to 999 Example –123.4567 +2 4567 +3 0123 +4 F000 If –: F *The deviation will be stored in this area only when reference setting is made. Deflection Measurement Start (4000-series) (Sequence No. 435 (Hex 01B3)) This sequence starts a deflection measurement. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. The deflection measurement keeps measuring until sequence No. 438 (Measurement Termination) is executed. 2. This sequence will be processed the same as sequence No. 411 Zero run measurement start for 5000-series Laser Micrometers. Continuous Measurement Start (Scan) (4000-series) (Sequence No. 436 (Hex 01B4)) This sequence starts a continuous measurement. The scan notification method is used for the receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 438 (Measurement Termination) to end the sequence. Continuous Measurement Start (Interrupt) (4000-series) (Sequence No. 437 (Hex 01B5)) This sequence starts a continuous measurement. The interrupt notification method is used for the receive data and the interrupt No. is 101. Send Data Word Allocation (3rd Operand of PMCR(260)) None. 406 3Z4L Laser Micrometer Protocol Appendix K Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Note 1. Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled. 2. Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No. 438 (Measurement Termination) to end the sequence. 3. Sequences No. 413 and No. 437 (Continuous Measurement Start with Interrupt) are not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. Continuous Measurement Termination (4000-series) (Sequence No. 438 (Hex 01B6)) This sequence terminates continuous measurement. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) For continuous measurement: None. For Deflection Measurement The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Note This sequence may be aborted if it is executed during continuous measurements. Measurements will be terminated even if the sequence is aborted. The sequence will be aborted if executed when the Laser Micrometer is sending measurement results. The chances that the sequence will be aborted are higher if the scheduled data output value is set to a lower value. Data Request (4000-series) (Sequence No. 439 (Hex 01B7)) This sequence requests display data in the idle measurement status or latch data generated by the measurement command. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start). Forced Positive Zero (4000-series) (Sequence No. 440 (Hex 01B8)) This sequence sets the forced zero direction to positive (+) Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Forced Negative Zero (4000-series) (Sequence No. 441 (Hex 01B9)) This sequence sets the forced zero direction to negative (–) Send Data Word Allocation (3rd Operand of PMCR(260)) None. 407 Appendix K 3Z4L Laser Micrometer Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Forced Zero Release (4000-series) (Sequence No. 442 (Hex 01BA)) This sequence releases the forced zero direction. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 3Z4L Initialize (4000-series) (Sequence No. 443 (Hex 01BB)) This sequence clears the 3Z4L, sets the mm unit, and sets memory switches. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting). Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Memory switch settings will be ignored for this sequence for 5000-series and 6000-series Laser Micrometers. General-purpose Command 1 (4000-series) (Sequence No. 444 (Hex 01BC)) This general-purpose command is used to send data with a specified data length, and receive back only OK. The terminator (CR) is automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data D D Send data +248 +249 Offset Send data Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Send data byte length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) The number of bytes of send data excluding the terminator (CR) +2 to +249 Send data (ASCII) Send data up to 496 bytes maximum Receive Data Word Allocation (4th Operand of PMCR(260)) None. 408 CR Specify in ASCII. Appendix K 3Z4L Laser Micrometer Protocol General-purpose Command 2 (4000-series) (Sequence No. 445 (Hex 01BD)) This general-purpose command is used to send data with a specified data length, and receive back receive data other than OK. The terminator (CR) is automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data +3 Send data D D Send data +128 +249 Offset Send data CR Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Send data byte length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) The number of bytes of send data excluding the terminator (CR) +2 to +249 Send data (ASCII) Send data up to 496 bytes maximum Specify in ASCII. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data +2 Receive data D D +126 Receive data +249 Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits BCD) 0001 to 00FA (1 to 250 decimal) +1 to +249 Receive data (ASCII) When the receive data exceed 498 bytes, only 498 bytes are stored. High Calibration Set (Sequence No. 446 (Hex 01BE)) This sequence sets the Laser Micrometer’s high calibration. Send Data Word Allocation (3rd Operand of PMCR(260)) Allocations are the same as for sequence No. 404 (Calibration Set) except that the LC gauge dimension in words +4 to +5 are not used. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser Micrometer. If sequence No. 404 (Calibration Set) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged. 2. The HC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion. 409 3Z4L Laser Micrometer Protocol Appendix K Low Calibration Set (Sequence No. 447 (Hex 01BF)) This sequence sets the Laser Micrometer’s low calibration. Send Data Word Allocation (3rd Operand of PMCR(260)) Allocations are the same as for sequence No. 404 (Calibration Set) except that the HC gauge dimension in words +1 to +3 are not used. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser Micrometer. If sequence No. 404 (Calibration Set) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged. 2. The LC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion. 410 Appendix L Visual Inspection System Protocol The Visual Inspection System Protocol is used to make various settings or control remotely the Visual Recognition Device connected to the Serial Communications Unit/Board via RS-232C cable. Protocol Configuration The configuration of the Visual Inspection System Protocol is shown below. Sequence No. Communications sequence name Function 450 (01C2) Measurement execution (F200) Carries out one measurement one and stores the measurement results in the specified words. 451 (01C3) Continuous measurement execution (scan) (F200) 452 (01C4) Ladder interface Send word allocation No Receive word allocation Yes Carries out continuously setting the F200 and storing the measurement results in the specified words. No Yes Continuous measurement execution (interrupt) (F200) Carries out continuously setting the F200 and storing the measurement results in the specified words. No Yes 453 (01C5) Reference object registration (group) (F200) Performs reference position registration and evaluation criterion registration at the same time. No No 454 (01C6) Reference object registration (reference position) (F200) Registers the reference position for measuring the amount of position displacement when a position displacement compensation is used. Reference object regis- Registers the reference value to distration (evaluation crite- criminate the output format. rion) (F200) No No No No 456 (01C8) Evaluation condition change (F200) Changes the upper and lower limit values of the evaluation condition of the designated output No. Yes No 457 (01C9) Arbitrary measurement value acquisition (F200) Stores the measurement values of arbitrary measurement item regardless of output format in the specified words. Yes Yes 460 (01CC) Measurement execution (F300) Carries out one measurement and stores the measurement results in the specified words. No Yes 461 (01CD) Continuous measurement execution (scan) (F300) Carries out continuously setting the F300 and storing the measurement results in the specified words. No Yes 462 (01CE) Continuous measurement execution (interrupt) (F300) Carries out continuously setting the F300 and storing the measurement results in the specified words. No Yes 463 (01CF) Reference object registration command 1 execution (F300) Performs a measurement for the input image and updates the reference object data of the full window. No No 464 (01D0) Reference object registration command 2 execution (F300) Performs a measurement for the input image and updates the reference object data of the full window Yes No 465 (01D1) Illumination fluctuation follow execution (F300) Measurement execution and positioning (F350) Executes an illumination fluctuation follow. Carries out one measurement and stores the measurement results in the specified words. No No No Yes 455 (01C7) 470 (01D6) Notes See Note 3 See Note 3 411 Appendix L Visual Inspection System Protocol Sequence No. Communications sequence name 471 (01D7) Camera designation and positioning (F350) Scene switching and positioning (F350) Inspection execution and character inspection (F350) 472 (01D8) Function Designates the camera for measurement. Switches to a designated scene No. Ladder interface Send word Receive word allocation allocation Yes No Yes No Carries out one inspection and outputs inspection results to the video monitor. No No 474 (01DA) Character string inspection and character inspection (F350) Changes the inspection character string of a designated inspection area No. to a designated character string. Yes No 480 (01E0) Camera change (decrease by 1) (F200/300) Decreases the display camera No. by 1. No No 481 (01E1) Camera change (increase by 1) (F200/300) Increases the display camera No. by 1. No No 482 (01E2) Binary level modification (F200/300) Modifies the binary levels (upper limit and lower limit values) of a designated window number No. Yes No 483 (01E3) Reset (F200/300) Resets the F200/F300. No No Decreases the scene No. by 1. No No Increases the scene No. by 1. No No Switches to a designated scene No. Yes No Terminates the measurement and returns to the home menu. Sets and executes commands that are otherwise not supported. Sets and executes commands that are otherwise not supported. No No Yes No Yes Yes 473 (01D9) 490 (01EA) Scene switch (decrease by 1) 491 (01EB) Scene switch (increase by 1) 492 (01EC) Scene switch (arbitrary) 493 (01ED) Measurement, inspection termination 494 (01EE) General-purpose command (send) 495 (01EF) General-purpose command send/(receive) Notes Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses. 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 3. Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. 412 Appendix L Visual Inspection System Protocol Connections The connections for using the Visual Inspection System Protocol are shown below. RS-232C Connections F200/300/350 CS1j RS-232C Serial Communications Unit/Board RS-232C port → RS-232C Unit Pin No. Signal name Abbreviation 1 Protective ground or earth FG (GND) 2 Send data SD (TXD) 3 Receive data RD (RXD) 4 Request to send RS (RTS) 5 Clear to send CS (CTS) 6 Data set ready DR (DSR) 7 Signal ground SG (GND) 8 Carrier detection (Data word receive) CD (DCD) 20 Data terminal ready ER (DTR) Serial Communications Unit/ Board: D-sub 9 pin (female) Signal Name Pin No. F300-E: D-sub 25 pin (female) Pin No. Signal Name SD (TXD) SD (TXD) RD (RXD) RD (RXD) RTS RTS CTS CTS DSR DSR SG SG CD (DCD) DTR FG 1 DTR • For RS/CS Flow Control Serial Communications Unit/ Board: D-sub 9 pin (female) Signal Name Pin No. F300-E: D-sub 25 pin (female) Pin No. Signal Name SD (TXD) SD (TXD) RD (RXD) RD (RXD) RTS RTS CTS CTS DSR DSR SG SG CD (DCD) DTR FG 1 DTR 413 Appendix L Visual Inspection System Protocol Measurement Execution (F200) (Sequence No. 450 (Hex 01C2)) This sequence carries out one measurement and stores the measurement results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 Evaluation result Decimal portion +3 Integer portion +4 +5 Output No. (Undefined) +2 Sign Measurement value 0 Offset Content (data format) Data +0 Number of receive data words (4 digits Hex) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 Measurement value (integer portion) (7 digits BCD) +3 3456 +3 3456 +4 0012 +4 0012 Measurement value (sign) (1 digit) +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be stored. 2. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 3. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. Continuous Measurement Execution (Scan) (F200) (Sequence No. 451 (Hex 01C3)) This sequence carries out continuously the setting of the F200 and stores measurement results in the specified words. The scan notification method is used for the receive data. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 Number of receive data words (Undefined) +2 Integer portion +4 414 Evaluation result Decimal portion +3 +5 Output No. (Undefined) Sign 0 Measurement value Appendix L Visual Inspection System Protocol Offset Content (data format) Data +0 Number of receive data words (4 digits Hex) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be designated. 2. Turn ON the Abort Switch to end this sequences. Abort Switches for port 1 are CIO 190003 for the Serial Communications Board and CIO 1500 + 25 x unit number, bit 03 for Serial Communications Units. Abort Switches for port 2 are CIO 190011 for the Serial Communications Board and CIO 1500 + 25 x unit number, bit 11 for Serial Communications Units. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 4. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. Continuous Measurement Execution (Interrupt) (F200) (Sequence No. 452 (Hex 01C4)) This sequence carries out continuously setting the F200 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 Evaluation result Decimal portion +3 Integer portion +4 +5 Output No. (Undefined) +2 Sign Offset Measurement value 0 Content (data format) Data +0 Number of receive data words (4 digits BCD) 0006 +1 Output No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be designated. 415 Visual Inspection System Protocol Appendix L 2. Turn ON the Abort Switch to end this sequences. Abort Switches for port 1 are CIO 190003 for the Serial Communications Board and CIO 1500 + 25 x unit number, bit 03 for Serial Communications Units. Abort Switches for port 2 are CIO 190011 for the Serial Communications Board and CIO 1500 + 25 x unit number, bit 11 for Serial Communications Units. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 4. If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words. 5. Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. Reference Object Registration (Group) (F200) (Sequence No. 453 (Hex 01C5)) This sequence performs reference position registration and criterion registration at the same time. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Reference Object Registration (Reference Position) (F200) (Sequence No. 454 (Hex 01C6)) This sequence registers the reference position for measuring the amount of position displacement when a position displacement compensation is used. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Reference Object Registration (Criterion) (F200) (Sequence No. 455 (Hex 01C7)) This sequence registers a reference value to discriminate the output format. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Evaluation Condition Change (F200) (Sequence No. 456 (Hex 01C8)) This sequence changes the upper and lower limit values of evaluation condition of the designated output No. 416 Appendix L Visual Inspection System Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 +2 Number of send data words (Undefined) +3 +4 +6 Integer portion (Undefined) Sign +5 (Undefined) Integer portion (Undefined) Sign +9 Upper limit value Decimal portion (Undefined) +7 +8 Output No. Decimal portion (Undefined) Offset Lower limit value (Undefined) Content (data format) Data +0 Number of send data words (4 digits Hex) 000A (0010 decimal) +1 Output No. (2 digits BCD) 00 to 07 +2 to +5 Upper limit value (decimal portion) (3 digits BCD) Upper limit value (integer portion) (7 digits BCD) Upper limit value (sign) (ASCII 2 digits) +6 to +9 Lower limit value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 +2 0567 +2 0678 +3 1234 +3 2345 +4 0000 +4 0001 2D00 +5 3000 +5 Same as upper limit. Lower limit value (integer portion) (7 digits BCD) Lower limit value (sign) (ASCII 2 digits) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Only one output No. can be designated. 2. Enter values so that upper limit ≥ lower limit. 3. Enter upper limit and lower limit values within the range –2147483.648 to 2147483.648. Arbitrary Measurement Value Acquisition (F200) (Sequence No. 457 (Hex 01C9)) This sequence stores measurement values of arbitrary measurement items regardless of output format in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) Data 1 +2 (Undefined) Data 2 417 Appendix L Visual Inspection System Protocol Offset Content (data format) Data +0 Number of send data words (4 digits Hex) 0003 +1 Data 1 (2 digits BCD) 00: Area 01: Center of gravity x 02: Center of gravity y 03: Main axis angle 04: Output format 05: Reference value of output format 06: X displacement 07: Y displacement 08: Angle displacement 09: X reference position 10: Y reference position 11: Angle reference position +2 Data 2 (2 digits BCD) When 00 to 03 is set to data 1 Window No.: 00 to 07 When 04 to 05 is set to data 1 Output No.: 00 to 07 When 06 to 11 is set to data 1 Camera No.: 00 to 01 Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 Number of receive data words (Undefined) +3 Decimal portion Integer portion +2 Sign Offset Measurement value 0 Content (data format) +0 Number of receive data words (4 digits BCD) +1 to +3 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Data 0004 Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. Note 1. Only one output No. can be designated. 2. Measurement is not performed with this command. The measurement results of the last measurement will be stored in the specified words. 3. This command can acquire only the measurement value of the window No. set by output format. 4. For data 1 and 2 , the receive data is compared with the send data. If the receive data is not the same as the send data, the following flags will be turned ON: The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO 1919114 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units. 5. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.647 For calibration ON setting : –9999999.999 to 9999999.999 6. If a measurement value exceeds the range of measurement values when calibration is turned off, unexpected data is stored in the specified words. 418 Appendix L Visual Inspection System Protocol Measurement Execution (F300) (Sequence No. 460 (Hex 01CC)) This sequence carries out one measurement and stores measurement results in the specified words Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data stor-+0 age words +1 Number of receive data words (Undefined) Window No. Evaluation result (Undefined) +2 Decimal portion +3 Integer portion +4 Sign +5 Data 1 0 Decimal portion +6 Integer portion +7 Sign +8 Data 2 0 Decimal portion +9 Integer portion +10 Sign +11 Data 3 0 Decimal portion +12 Integer portion +13 Sign +14 Data 4 0 Decimal portion +15 Integer portion +16 Sign +17 Offset +0 Data 5 0 Content (data format) Number of receive data words (4 digits Hex) Data 0006: 1 measurement item 0009: 2 measurement items 000C: 3 measurement items 000F: 4 measurement items 0012: 5 measurement items +1 Window number (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items is up to 5, but only one window number can be read. 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 419 Appendix L Visual Inspection System Protocol 4. The priority of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle Main axis angle aberration (reserved) Edge angle Edge angle (reserved) Center X, center Y Center X aberration (reserved), center Y aberration (reserved) Inclination Inclination aberration (reserved) Intersecting point X, intersecting point Y Intersecting point X aberration (reserved), intersecting point Y aberration (reserved) Continuous Measurement Execution (Scan) (F300) (Sequence No. 461 (Hex 01CD)) This sequence carries out continuously the settings of F300 and stores measurement results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 Number of receive data words (Undefined) Integer portion +4 Sign Decimal portion Integer portion +7 Sign Decimal portion Integer portion +10 Sign Decimal portion Integer portion +13 Sign Decimal portion Integer portion +16 420 Data 4 0 +15 +17 Data 3 0 +12 +14 Data 2 0 +9 +11 Data 1 0 +6 +8 Evaluation result Decimal portion +3 +5 Window No. (Undefined) +2 Sign 0 Data 5 Appendix L Visual Inspection System Protocol Offset +0 Content (data format) Number of receive data words (4 digits Hex) Data 0006: 1 measurement item 0009: 2 measurement items 000C: 3 measurement items 000F: 4 measurement items 0012: 5 measurement items +1 Window No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Measurement value (integer portion) (7 digits BCD) Measurement value (sign) (1 digit) Example –123.456 Example +123.456 +3 3456 +3 3456 +4 0012 +4 0012 +5 F000 +5 0000 F is stored for negative values. +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items are up to 5, but only one window number can be read. 3. The range of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 4. The priority order of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle Main axis angle aberration (reserved) Edge angle Edge angle (reserved) Center X, center Y Center X displacement (reserved), center Y displacement (reserved) Inclination Inclination displacement (reserved) Intersecting point X, intersecting point Y Intersecting point X displacement (reserved), intersecting point Y displacement (reserved) 421 Appendix L Visual Inspection System Protocol Continuous Measurement Execution (Interrupt) (F300) (Sequence No. 462 (Hex 01CE)) This sequence carries out continuously setting the F300 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 +2 Integer portion +4 Sign Decimal portion Integer portion +7 Sign Decimal portion Integer portion +10 Sign Decimal portion Integer portion +13 Sign Data 4 0 Decimal portion +15 Integer portion +16 +17 Data 3 0 +12 +14 Data 2 0 +9 +11 Data 1 0 +6 +8 Evaluation result Decimal portion +3 +5 Window No. (Undefined) Sign Offset +0 Data 5 0 Content (data format) Number of receive data words (4 digits Hex) Data 0006: 1 measurement item 0009: 2 measurement items 000C: 3 measurement items 000F: 4 measurement items 0012: 5 measurement items +1 Window No. (2 digits BCD) 00 to 07 +2 Evaluation result (1 digit BCD) 0: OK 1: NG +3 to +5 Measurement value (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 Measurement value (integer portion) (7 digits BCD) +3 3456 +3 3456 +4 0012 +4 0012 Measurement value (sign) (1 digit) +5 F000 +5 0000 F is stored for negative values. +6 to +8 Same as +3 to +5. Same as +3 to +5. +9 to +11 Same as +3 to +5. Same as +3 to +5. +12 to +14 Same as +3 to +5. Same as +3 to +5. +15 to +17 Same as +3 to +5. Same as +3 to +5. Note 1. Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9. 2. The number of measurement items is up to 5, but only one window number can be read. 422 Appendix L Visual Inspection System Protocol 3. The ranges of measurement values are as follows: For calibration OFF setting : –2147483.648 to 2147483.648 For calibration ON setting : –9999999.999 to 9999999.999 4. The priority of measurement items being output are as follows: Area Center of gravity X, Center of gravity Y Displacement in center of gravity X (reserved), displacement in center of gravity Y (reserved) Main axis angle Main axis angle displacement (reserved) Edge angle Edge angle(reserved) Center X, center Y Center X displacement (reserved), center Y displacement (reserved) Inclination Inclination displacement (reserved) Intersecting point X, intersecting point Y Intersecting point X displacement (reserved), intersecting point Y displacement (reserved) 5. Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21 Serial Communications Unit. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit. Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set. Reference Object Registration Command 1 Execution (F300) (Sequence No. 463 (Hex 01CF)) This sequence performs a measurement for the input image and updates reference object data of the full window. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Reference Object Registration Command 2 Execution (F300) (Sequence No. 464 (Hex 01D0)) This sequence performs a measurement for the input image and updates the reference object data of a designated window. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Window No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Window No. (1 digit BCD) 0 to 7 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Illumination Fluctuation Follow Execution (F300) (Sequence No. 465 (Hex 01D1)) This sequence executes an illumination fluctuation follow. Send Data Word Allocation (3rd Operand of PMCR(260)) None. 423 Appendix L Visual Inspection System Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) None. Measurement Execution and Positioning (F350) (Sequence No. 470 (Hex 01D6)) This sequence carries out one measurement and stores the measurement results in the specified words. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words Decimal portion +1 +2 Sign Integer portion X displacement Decimal portion +3 Integer portion Sign +4 Y displacement Decimal portion +5 Sign +6 Offset 0 Integer portion Correlation value Content (data format) Data +0 Number of receive data words (4 digits Hex) 0007 +1 to +2 X displacement (decimal portion) (3 digits BCD) Example –123.456 Example +123.456 X displacement (integer portion) (3 digits BCD) +1 3456 +1 3456 +2 F012 +2 0012 X displacement (sign) (1 digit) (See note.) +3 to +4 Y displacement (decimal portion) (3 digits BCD) Y displacement (integer portion) (3 digits BCD) F is stored for negative values. Example –123.456 +1 3456 +1 3456 +2 F012 +2 0012 Y displacement (sign) (1 digit) (See note.) +5 to +6 Correlation value (decimal portion) (3 digits BCD) Correlation value (integer portion) (3 digits BCD) Example +123.456 F is stored for negative values. Example –12.345 +1 +2 Correlation value (sign) (1 digit) (See note.) Example +12.345 2345 +1 2345 F001 +2 0001 F is stored for negative values. Note 1. The number of models that can be stored in a designated word is 1. 2. If a measurement is carried out without executing a camera designation, a measurement is executed for all cameras in which the measurement model is registered. 3. When the correlation value is less than 70 and the measurement value overflows, the following flags will be turned ON. The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO 1919114 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units. 4. Data to be output is within the range 999.999 (upper limit) to –999.999 (lower limit). 5. Retry processing is not performed for this sequence. 6. Turn the Abort Bit ON and then OFF to end this sequence. 424 Appendix L Visual Inspection System Protocol Camera Designation and Positioning (F350) (Sequence No. 471 (Hex 01D7)) This sequence designates the cameras for measurement. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 (Undefined) +2 (Undefined) Offset First camera No. Last camera No. Content (data format) Data +0 Number of send data words (4 digit Hex) 0003 +1 First camera No. (1 digit BCD) 0 to 7 +2 Last camera No. (1 digit BCD) 0 to 7 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Set values so that the first camera No.< last camera No. 2. If a designated camera No. is abnormal, the following flags will be turned ON. The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO 191914 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units. Scene Switching and Positioning (F350) (Sequence No. 472 (Hex 01D8)) This sequence switches to a designated scene No. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Scene No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 +1 Scene No. (2 digits BCD) 00 to 15 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. If a scene No. is abnormal, the following flags will be turned ON. The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO 191914 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units. 2. Retry processing is not performed for this sequence. 3. Turn ON the Abort Switch to end this sequence. Inspection Execution and Character Inspection (F350) (Sequence No. 473 (Hex 01D9)) This sequence carries out one inspection and outputs the inspection results to a video monitor. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 425 Appendix L Visual Inspection System Protocol Character String Inspection and Character Inspection (F350) (Sequence No. 474 (Hex 01DA)) This sequence changes the inspection character string of a designated inspection area No. to a designated character string. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Inspection area No. (Undefined) +2 Number of designated character strings Designated character string +3 ~ ~ Designated character string Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 to 000F (0004 to 0015 decimal) +1 Number of designated character strings (4 digits Hex) 0000 to 0018 (0000 to 0024 decimal) +2 Inspection area No. (1 digit BCD) 0 to 7 +3 to Number of designated character strings (ASCII) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Camera Change (Decrease by 1) (F200/300) (Sequence No. 480 (Hex 01E0)) This sequence decreases the display camera No. by 1. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Camera Change (Increase by 1) (F200/300) (Sequence No. 481 (Hex 01E1)) This sequence increases the display camera No. by 1. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Binary Level Modification (F200/300) (Sequence No. 482 (Hex 01E2)) This sequence modifies the binary levels (upper limit and lower limit values) of a designated output No. (F200) or window number No. (F300). Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data 426 +0 Number of send data words (Undefined) +1 Window No. +2 (Undefined) Upper limit value +3 (Undefined) Lower limit value or Output No. Appendix L Visual Inspection System Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 +1 Window No. (1 digit BCD) 0 to 7 +2 Upper limit value (3 digits BCD) 000 to 255 +3 Lower limit value (3 digits BCD) 000 to 255 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Enter values so that the upper limit ≥ lower limit. Reset (F200/300) (Sequence No. 483 (Hex 01E3)) This sequence resets the F200/F300 (to starting status). Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Scene Switching (Decrease by 1) (Sequence No. 490 (Hex 01EA)) This sequence decreases the scene No. by 1. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Scene Switching (Increase by 1) (Sequence No. 491 (Hex 01EB)) This sequence increases the scene No. by 1. Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Scene Switching (Arbitrary) (Sequence No. 492 (Hex 01EC)) This sequence switches to a designated scene No. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words (Undefined) +1 Offset Scene No. Contents (data format) Data +0 Number of send data words (4 digits BCD) 0002 +1 Scene No. (2 digits BCD) 00 to 15 Receive Data Word Allocation (4th Operand of PMCR(260)) None. Measurement, Inspection Termination (Sequence No. 493 (Hex 01ED)) This sequence terminates the measurement and returns to the home menu. 427 Appendix L Visual Inspection System Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) None. Receive Data Word Allocation (4th Operand of PMCR(260)) None. General-purpose Command (Send) (Sequence No. 494 (Hex 01EE)) This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Command length +1 Command +2 (Undefined) ~ ~ Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Command length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) +2 to Command (ASCII) Specify ASCII data. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. The processing depends on the command. 2. For a command with a response, use sequence #495. General-purpose Command (Send/Receive) (Sequence No. 495 (Hex 01EF)) This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words Command length +1 Command +2 (Undefined) ~ Offset 428 ~ Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Command length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) +2 to Command (ASCII) Specify ASCII data. Appendix L Visual Inspection System Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) The reception data is stored in the reception data words without the delimiter (CR+LF), Receive data storage words +0 Number of receive data words +1 Command length Command +2 (Undefined) ~ Offset ~ Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Command length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) +2 to Command (ASCII) ASCII data is returned. Note 1. The processing depends on the command. 2. For a command without a response, use sequence #495. 429 Appendix M V600/V620 ID Controller Protocol The V600/V620 ID Controller Protocol is used to make various settings or control remotely the ID Controller Connected to the Serial Communications Unit/Board via RS-232C or RS-422 cable. Protocol Configuration The configuration of the V600/V620 ID Controller Protocol is shown below. Sequence No. Communications sequence name 500 (01F4) Read (ASCII/1) 501 (01F5) Read (ASCII/2) 502 (01F6) Read (ASCII/4) 503 (01F7) Read (ASCII/8) 504 (01F8) Read (Hex/1) 505 (01F9) Read (Hex/2) 506 (01FA) Read (Hex/4) 507 (01FB) Read (Hex/8) 508 (01FC) Auto-read (ASCII/1) 509 (01FD) Auto-read (Hex/1) 510 (01FE) Polling Auto-read (ASCII) 511 (01FF) Polling Auto-read Subcommand (ASCII/2) Function Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 2. Used when the maximum number of Heads to be read from the Carrier is 4. Used when the maximum number of Heads to be read from the Carrier is 8. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 2. Used when the maximum number of Heads to be read from the Carrier is 4. Used when the maximum number of Heads to be read from the Carrier is 8. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is 1. Used when the number of Heads to be read from the Carrier is from 1 to 8. Used when the number of Heads to be read from the Carrier is 2. Ladder interface Send word allocation Yes Receive word allocation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes 512 (0200) Polling Auto-read Subcommand (ASCII/4) Used when the maximum number of Heads to be read from the Carrier is 4. Yes Yes 513 (0201) Polling Auto-read Subcommand (ASCII/8) Used when the maximum number of Heads to be read from the Carrier is 8. Yes Yes 514 (0202) Polling Auto-read (Hex) Polling Auto-read Subcommand (Hex/2) Used when the number of Heads to be read from the Carrier is from 1 to 8. Used when the number of Heads to be read from the Carrier is 2. Yes No Yes Yes 516 (0204) Polling Auto-read Subcommand (Hex/4) Used when the maximum number of Heads to be read from the Carrier is 4. Yes Yes 517 (0205) Polling Auto-read Subcommand (Hex/8) Used when the maximum number of Heads to be read from the Carrier is 8. Yes Yes 518 (0206) Write (ASCII/1) Used when the number of Heads to be written to the Carrier is 1. Yes No 515 (0203) 431 Appendix M V600/V620 ID Controller Protocol Sequence No. Communications sequence name 519 (0207) Write (ASCII/2) 520 (0208) Write (ASCII/4) 521 (0209) Write (ASCII/8) 522 (020A) Write (Hex/1) 523 (020B) Write (Hex/2) 524 (020C) Write (Hex/4) 525 (020D) Write (Hex/8) 526 (020E) Auto-write (ASCII/1) 527 (020F) Auto-write (Hex/1) 528 (0210) Polling Auto-write (ASCII/2) Polling Auto-write Subcommand (ASCII/2) 529 (0211) 530 (0212) Function Used when the number of Heads to be written to the Carrier is 2. Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 8. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 2. Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 8. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 1. Used when the number of Heads to be written to the Carrier is 2. Used when the number of Heads to be written to the Carrier is 2. Ladder interface Send word Receive word allocation allocation Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Polling Auto-write (ASCII/4) Polling Auto-write Subcommand (ASCII/4) Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 4. Yes No Yes No Polling Auto-write (ASCII/8) Polling Auto-write Subcommand (ASCII/8) Used when the maximum number of Heads to be written to the Carrier is 8. Used when the maximum number of Heads to be written to the Carrier is 8. Yes No Yes No Polling Auto-write (Hex/2) Polling Auto-write Subcommand (Hex/2) Used when the number of Heads to be written to the Carrier is 2. Used when the number of Heads to be written to the Carrier is 2. Yes No Yes No Polling Auto-write (Hex/4) Polling Auto-write Subcommand (Hex/4) Used when the maximum number of Heads to be written to the Carrier is 4. Used when the maximum number of Heads to be written to the Carrier is 4. Yes No Yes No Polling Auto-write (Hex/8) Polling Auto-write Subcommand (Hex/8) Used when the maximum number of Heads to be written to the Carrier is 8. Used when the maximum number of Heads to be written to the Carrier is 8. Yes No Yes No Yes Yes 541 (021D) Control management Writes and verify the CRC code for the check blocks designated by the user. Performs I/O or an I/O read. Yes Yes 542 (021E) Reads information from the latest error log. Yes Yes Cancels command processing except polling command processing and returns to the command waiting status. Yes Yes 531 (0213) 532 (0214) 533 (0215) 534 (0216) 535 (0217) 536 (0218) 537 (0219) 538 (021A) 539 (021B) 540 (021C) Data check 543 (021F) 432 Error information read Command processing cancel Appendix M V600/V620 ID Controller Protocol Sequence No. Communications sequence name Function Ladder interface Send word Receive word allocation allocation Yes Yes 544 (0220) Polling auto-read command processing cancel Cancels polling auto-read processing. 545 (0221) Polling auto-write command processing cancel Cancels polling auto-write processing. Yes Yes 546 (0222) General-purpose command Sends arbitrary data and stores receive data to receive data words. Yes Yes Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 3. The Read/Write Head is abbreviated as R/W Head and the Data Carrier is abbreviated as simply Carrier in this appendix. Connections Connections when using the V600/V620 ID Controller Protocol are shown below. RS-232C Connections CS1j Head Serial Communications Unit/ Board RS-232C port Data Carrier ID Controller Serial Communications Unit/Board D-sub 9 pin (female) Signal ID Controller (CD1D): D-sub 9 pin (female) Pin No. Pin No. Signal FG GR SD SD RD RD RTS RTS CTS CTS SG SG Shield Serial Communications Unit/Board: D-sub 9 pin (female) ID Controller (CA1A): D-sub 25 pin (female) Shield 433 Appendix M V600/V620 ID Controller Protocol RS-422 Connections CS1j Serial Communications Board (CS1W-SCB41) RS-422 port Head Data Carrier Head Data Carrier ID Controller ID Controller Up to 16 units can be connected Serial Communications Board: D-sub 9 pin (female) Signal name FG ID Controller (CD1D): D-sub 9 pin (female) Signal Pin No. name Pin No. Shell Shield Note 1. Ground the cable shield at either the ID Controller or the Serial Communications Unit/Board to prevent malfunction. 2. Turn ON the pin 6 on DIP switch SW6 to set the host communications procedure to the 1-to-N procedure for 1-to-N connections. 434 Appendix M V600/V620 ID Controller Protocol DIP Switch Settings V600/620-CD1D DIP Switches DIP Switch 1 1 2 3 4 5 6 7 8 Not used (Always keep it OFF.) Local communications mode setting Speed priority setting Distance priority setting • SW7 Setting This setting is only valid if the EEPROM-type (batterylesstype) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (battery-type) DC. SW7 must be set to OFF when the V620 is used. Baud rate (bps) 2,400 4,800 9,600 19,200 Display mode Error display mode I/O display mode Data length (bit) STOP bits (bit) 7 7 7 7 8 8 8 8 2 2 1 1 2 1 1 1 Parity type E O E O N N E O 435 Appendix M V600/V620 ID Controller Protocol DIP Switch 2 1 2 3 4 5 6 7 8 Not used (Always keep it OFF.) Communications protocol setting with host devices 1-to-N protocol 1-to-1 protocol Note When selecting the “1-to-N” protocol, setting is limited to N=1. In this case, the FCS check code may be added. • ID Controller Unit Number Setting (Valid Only for 1-to-N Protocol) Unit No. No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 Note 1. Be careful not to set to the same unit number twice. 2. Set them to OFF for the 1-to-1 protocol. Synchronous condition OFF (LL level) ON (HL level) Trailing edge Leading edge 436 Appendix M V600/V620 ID Controller Protocol V600-CAjA DIP Switches DIP Switch 1 Note Factory Setting: All OFF Mode 1 1 2 3 4 5 6 7 8 SW7 and SW8: Be sure to set to OFF. • Baud Rate Setting • Communications Format Data length (bit) Baud rate (bps) 1,200 2,400 4,800 9,600 19,200 1=ON, 0=OFF 1=ON, 0=OFF Note STOP bit (bit) Parity type 2 2 1 1 2 1 1 1 E O E O N N E O (See note 2) 7 7 7 7 8 8 8 8 (See note 1) 1. Data length setting 7 bits: ASCII code 8 bits: JIS8 unit code 2. Parity setting E: Even parity O: Odd parity N: No parity designation DIP Switch 2 1 2 3 4 5 6 7 8 • SW8: Receive Side Terminating Resistance Setting (Valid Only for the V600-CA2A) Connected (ID Controller send side) Not connected • SW7: Receive Side Terminating Resistance Setting (Valid Only for the V600-CA2A) Connected (ID Controller receive side) Not connected • SW6: Communications Protocol Setting 1-to-N protocol 1-to-1 protocol • ID Controller Unit Number Setting (Valid Only for the 1-to-N Protocol) Unit No. • Local Communications Mode Setting No. 0 No. 1 No. 2 No. 3 No. 4 No. 5 No. 6 No. 7 No. 8 No. 9 No. 10 No. 11 No. 12 No. 13 No. 14 No. 15 Speed priority setting Distance priority setting • SW1 Setting This setting is only valid if the EEPROM-type (batteryless-type) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (batterytype) DC. • SW6 Setting When selecting the 1-to-N protocol for the V600-CA1A/RS-232C interface, the setting is limited to N=1. In this case, the FCS check code may be added. Note 1. Be careful not to set to the same unit number twice. 2. Set them to OFF for the 1-to-1 protocol. 437 Appendix M V600/V620 ID Controller Protocol Read (ASCII/1) (Sequence No. 500 (Hex 01F4)) This sequence is used when the number of Heads to be read from the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Undefined) +2 Head CH No. Leading address No. +3 (Undefined) +4 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CAjA) +2 R/W Head channel (CH) No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hex) 0000 to FFFF +4 Read bytes (2 digits Hex) 01 to F4 (1 to 244 bytes) Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data ~ ~ Read data +122 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 007B (2 to 123 decimal) +1 to +122 Read data (ASCII) Number of read bytes stored in ASCII Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words, as shown in the following diagram. Data Carrier Receive data storage words +0 +1 +2 +3 +4 Example for 5 bytes Each byte (address) in the Data Carrier contains the code for one ASCII character. 438 +0 +1 +2 Appendix M V600/V620 ID Controller Protocol Read (ASCII/2) (Sequence No. 501 (Hex 01F5)) This sequence is used when the number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 000A (6 to 10 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0002 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 76 (1 to 118 bytes) N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ CH 1 ~ CH 2 Read data +59 +60 Not used +61 Read data ~ Read data +119 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 0120 +(60(N–1)+1) to +(60(N–1)+59) Read data (ASCII) Number of read bytes store in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 439 Appendix M V600/V620 ID Controller Protocol Read (ASCII/4) (Sequence No. 502 (Hex 01F6)) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 +9 (Undefined) Read bytes (Undefined) Unit No. ~ +14 ~ (Undefined) +15 Head CH No. 4 CH Leading address No. +16 (Undefined) +17 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0012 (6 to 18 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0004 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 30 (1 to 48 bytes) N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ +24 Read data +25 Read data ~ +48 440 ~ CH 2 ~ Read data ~ +96 CH 1 Read data ~ +73 ~ ~ Read data 4 CH Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 0097 +(24(N–1)+1) to +(24(N–1)+24) Read data (ASCII) Number of read bytes stored in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. Read (ASCII/8) (Sequence No. 503 (Hex 01F7)) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Read bytes ~ +30 ~ (Undefined) Unit No. (Undefined) +31 Head CH No. Leading address No. +32 (Undefined) +33 Offset 8 CH Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0022 (6 to 34 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 14 (1 to 20 bytes) N: Number of Heads 441 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ +10 Read data +11 Read data ~ ~ CH 1 ~ CH 2 Read data +20 ~ ~ Read data +71 ~ ~ +80 CH 8 Read data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 0081 +(10(N–1)+1) to +(10(N–1)+10) Read data (ASCII) Number of read bytes stored in ASCII N: Number of Heads Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. Read (Hex/1) (Sequence No. 504 (Hex 01F8)) This sequence is used when the number of Heads to be read from the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Undefined) +2 Head CH No. Leading address No. +3 (Undefined) +4 Offset Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0005 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CAjA) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hex) 0000 to FFFF +4 Read bytes (2 digits Hex) 01 to 7A (1 to 122 bytes) Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data +2 Read data ~ +61 442 ~ Read data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 003E (6 to 62 decimal) +1 to +61 Read data (Hex) Number of read bytes stored in hexadecimal data Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words, as shown in the following diagram. Data Carrier Receive data storage words +0 Example for 6 bytes +1 +0 +1 +2 Each byte (address) in the Data Carrier contains 2 digits. Read (Hex/2) (Sequence No. 505 (Hex 01F9)) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads +2 (Undefined) +3 Unit No. (Undefined) +4 Head CH No. CH 1 Leading address No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. Leading address No. +8 (Undefined) +9 Offset CH 2 Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 000A (6 to 10 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0002 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 3C (1 to 60 bytes) N: Number of Heads 443 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +30 Read data +31 Not used ~ CH 1 ~ +60 Not used +61 Read data ~ ~ CH 2 Read data +90 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 005B (2 to 91 decimal) +(60(N–1)+1) to +(60(N–1)+30) Read data (Hex) Number of read bytes stored in hexadecimal code N: Number of Heads Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words. Read (Hex/4) (Sequence No. 506 (Hex 01FA)) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 +2 +3 +4 Number of send data words Number of Heads (Undefined) (Undefined) Unit No. Head CH No. +5 (Undefined) Read bytes +6 (Undefined) Unit No. +7 +8 +9 (Undefined) Head CH No. +15 +16 +17 444 CH 2 Leading address No. (Undefined) Read bytes ~ +14 CH 1 Leading address No. ~ (Undefined) (Undefined) Unit No. Head CH No. Leading address No. (Undefined) Read bytes CH 4 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0012 (6 to 18 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0004 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 18 (1 to 24 bytes) N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +12 Read data +13 (Not used) ~ CH 1 ~ +24 (Not used) +25 Read data ~ ~ CH 2 Read data +36 ~ ~ Read data +73 ~ ~ CH 4 Read data +84 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 0055 (2 to 85 decimal) +(24(N–1)+1) to +(24(N–1)+12) Read data (Hex) Number of read bytes stored in hexadecimal data Note Data for Data Carriers designated for hexadecimal is received beginning with the largest offset from the receive data words. 445 Appendix M V600/V620 ID Controller Protocol Read (Hex/8) (Sequence No. 507 (Hex 01FB)) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 +5 (Undefined) Read bytes +6 (Undefined) Unit No. (Undefined) +7 Head CH No. CH 2 Leading address No. +8 (Undefined) +9 Read bytes ~ +30 ~ (Undefined) Unit No. (Undefined) +31 Head CH No. Leading address No. +32 (Undefined) +33 Offset CH 8 Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0022 (6 to 34 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) 01 to 0A (1 to 10 bytes) N: Number of Heads 446 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Read data ~ ~ +5 Read data +6 Not used ~ CH 1 ~ +10 Not used +11 Read data ~ ~ CH 2 Read data +15 ~ ~ Read data +71 ~ ~ CH 8 Read data +75 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 004C (2 to 76 decimal) +(10(N–1)+1) to +(10(N–1)+5) Read data (CH 1) (Hex) Number of read bytes stored in hexadecimal data N: Number of Heads Note Data for Data Carriers designated for hexadecimal is sent beginning with the largest offset from the receive data words. Auto-read (ASCII/1) (Sequence No. 508 (Hex 01FC)) This sequence is used when the maximum number of Heads to be read from the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)). Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Auto-read (Hex/1) (Sequence No. 509 (Hex 01FD)) This sequence is used when the maximum number of Heads to be read from the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)). Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Polling Auto-read (ASCII) (Sequence No. 510 (Hex 01FE)) This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8. 447 Appendix M V600/V620 ID Controller Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) Number of send data words First word of send +0 data +1 Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 (Undefined) +5 Read bytes ~ +(4(N–1)+2) ~ (Undefined) Unit No. (Undefined) +(4(N–1)+3) Head CH No. Leading address No. +(4(N–1)+4) (Undefined) +(4(N–1)+5) Offset CH N * N: Number of Heads Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0022 (6 to 34 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) If number of Heads is 2 or less 01 to 76 (1 to 118 bytes) If number of Heads is 4 or less 01 to 30 (1 to 48 bytes) If number of Heads is 8 or less 01 to 20 (1 to 20 bytes) N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 510 before executing Sequence No. 511, 512, 513. 2. Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (ASCII/2) (Sequence No. 511 (Hex 01FF)) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). Note 1. Execute Sequence No. 510 before executing Sequence No. 511. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. 448 V600/V620 ID Controller Protocol Appendix M Polling Auto-read Sub-command (ASCII/4) (Sequence No. 512 (Hex 0200)) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). Note 1. Execute Sequence No. 510 before executing Sequence No. 512. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (ASCII/8) (Sequence No. 513 (Hex 0201)) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). Note 1. Execute Sequence No. 510 before executing Sequence No. 513. 2. Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words. 3. Retry processing is not performed for this sequence. 449 Appendix M V600/V620 ID Controller Protocol Polling Auto-read (Hex) (Sequence No. 514 (Hex 0202)) This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8. Send Data Word Allocation (3rd Operand of PMCR(260)) Number of send data words First word of send +0 data +1 Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. CH 1 Leading address No. +4 (Undefined) +5 Read bytes ~ +(4(N–1)+2) ~ (Undefined) Unit No. (Undefined) +(4(N–1)+3) Head CH No. Leading address No. +(4(N–1)+4) (Undefined) +(4(N–1)+5) Offset CH N * N: Number of Heads Read bytes Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0022 (6 to 34 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0008 +(4(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(4(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 +(4(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(4(N–1)+5) Read bytes (2 digits Hex) If number of Heads is 2 or less 01 to 3C (1 to 60 bytes) R/W Head CH 2 designation: 2 If number of Heads is 4 or less 01 to 18 (1 to 24 bytes) If number of Heads is 8 or less 01 to 0A (1 to 10 bytes) N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 514 before executing Sequence No. 515, 516, 517. 2. Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read. Polling Auto-read Sub-command (Hex/2) (Sequence No. 515 (Hex 0203)) This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 505 (Read (Hex/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 505 (Read (Hex/2)). Note 1. Execute Sequence No. 514 before executing Sequence No. 515. 450 Appendix M V600/V620 ID Controller Protocol 2. Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words. 3. Retry processing is not performed for this sequence. Polling Auto-read Sub-command (Hex/4) (Sequence No. 516 (Hex 0204)) This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 506 (Read (Hex/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 506 (Read (Hex/4)). Note 1. Execute Sequence No. 514 before executing Sequence No. 516. 2. Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words. Polling Auto-read Sub-command (Hex/8) (Sequence No.517 (Hex 0205)) This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head. Send Data Word Allocation 3rd Operand of PMCR(260)) The send data word allocation is similar to that of sequence No.507 (Read (Hex/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514. Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of sequence No.507 (Read (Hex/8)). Note 1. Execute sequence No.514 before executing sequence No.517. 2. Data from Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words. 3. Retry processing is not performed for this sequence. Write (ASCII/1) (Sequence No.518 (Hex 0206)) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 +2 Number of send data words (Undefined) (Undefined) Unit No. Head CH No. +3 Leading address No. +4 Number of write bytes +5 Write data ~ ~ Max +249 Write data 451 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 00FA (6 to 250 decimal) +1 Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hex) 0000 to FFFF +4 Number of write bytes (4 digits Hex) 0001 to 01EA (1 to 490 decimal) +5to +249 Write data (ASCII) Input in ASCII Up to 248 bytes (max.) can be set Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words, as shown in the following diagram. Data Carrier Receive data storage words +0 +1 +2 Example for 5 bytes +0 +1 +2 +3 +4 Each byte (address) in the Data Carrier contains the code for one ASCII character. Write (ASCII/2) (Sequence No. 519 (Hex 0207)) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 +2 +3 Number of send data words Number of Heads (Undefined) (Undefined) Unit No. Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ ~ +64 Write data +65 (Not used) +66 +67 (Undefined) (Undefined) Head CH No. Leading address No. +69 Number of write bytes +70 Write data ~ 452 Unit No. +68 +128 CH 1 CH 2 ~ Write data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 0081 (7 to 129 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0002 +(64(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(64(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(64(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(64(N–1)+5) Number of write bytes (4 digits Hex) 0001 to 0076 (1 to 118 decimal) +(64(N–1)+6) to (64(N–1)+64) Write data (ASCII) Input in ASCII. Up to 118 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words. 453 Appendix M V600/V620 ID Controller Protocol Write (ASCII/4) (Sequence No. 520 (Hex 0208)) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ CH 1 ~ Write data +29 (Undefined) +30 Unit No. (Undefined) +31 Head CH No. +32 Leading address No. +33 Number of write bytes +34 Write data ~ CH 2 ~ Write data +57 ~ +86 ~ (Undefined) +87 Unit No. (Undefined) Head CH No. +88 Leading address No. +89 Number of write bytes +90 Write data ~ CH 4 ~ Write data +113 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 0072 (7 to 114 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0004 +(28(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(28(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(28(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(28(N–1)+5) Number of write bytes (4 digits Hex) 0001 to 0030 (1 to 48 decimal) +(28(N–1)+6) to (28(N–1)+29) Write data (ASCII) Input in ASCII. Up to 48 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Write designated for ASCII is sent beginning with the smallest offset from the send data words. 454 Appendix M V600/V620 ID Controller Protocol Write (ASCII/8) (Sequence No. 521 (Hex 0209)) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write bytes +6 Write data ~ CH 1 ~ Write data +15 (Undefined) +16 Unit No. (Undefined) +17 Head CH No. +18 Leading address No. +19 Number of write bytes +20 Write data ~ CH 2 ~ Write data +29 ~ +100 ~ (Undefined) +101 Unit No. (Undefined) Head CH No. +102 Leading address No. +103 Number of write bytes +104 Write data ~ CH 8 ~ Write data +113 Offset Contents (data format) Data +0 Number of send data words(4 digits Hex) 0007 to 0072 (7 to 114 decimal) +1 Number of Heads (4 digits BCD) 0001 to 0008 +(14(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(14(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(14(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(14(N–1)+5) Number of write bytes (4 digits Hex) 0001 to 0014 (1 to 20 decimal) +(14(N–1)+6) to (14(N–1)+15) Write data (ASCII) Input in ASCII Up to 20 bytes (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words. 455 Appendix M V600/V620 ID Controller Protocol Write (Hex/1) (Sequence No. 522 (Hex 020A)) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Undefined) +2 Head CH No. +3 Leading address No. +4 Number of write digits +5 Write data ~ ~ (Undefined) Max +35 Offset Write data Contents (data format) Data +0 Number of send data words (4 digits Hex) 0006 to 0024 (6 to 36 decimal) +1 Relevant Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Leading address No. (4 digits Hex) 0000 to FFFF +4 Number of write digits (4 digits Hex) 0002 to 007A (2 to 122 decimal) +5 to 35 Write data (Hex) Input in hexadecimal Up to 122 digits (max.) Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Data of which Data Carrier designated for hexadecimal is sent beginning with the largest offset from the send data words, as shown in the following diagram. 2. Always set an even number of digits for the write data. Data Carrier Receive data storage words +0 +1 Example for 6 bytes +0 +1 +2 Each byte (address) in the Data Carrier contains 2 digits. 456 Appendix M V600/V620 ID Controller Protocol Write (Hex/2) (Sequence No. 523 (Hex 020B)) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) Number of send data words First word of send +0 data +1 Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ CH 1 ~ +19 Write data +20 (Not used) ~ ~ +65 (Not used) (Undefined) +66 Unit No. (Undefined) +67 Head CH No. +68 Leading address No. +69 Number of write digits +70 Write data ~ CH 2 ~ Write data +83 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 0054 (7 to 84 decimal) +1 Number of Heads (4 digits Hex) 0002 to 0002 +(64(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(64(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(64(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(64(N–1)+5) Number of write digits (4 digits Hex) 0002 to 0038 (2 to 56 decimal) +(64(N–1)+6) to (64(N–1)+19) Write data (Hex) Input in hexadecimal Up to 56 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. 457 Appendix M V600/V620 ID Controller Protocol Write (Hex/4) (Sequence No. 524 (Hex 020C)) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 24 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words Number of Heads (Undefined) +2 Unit No. (Undefined) +3 Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ CH 1 ~ +11 Write data +12 Not used ~ ~ +29 Not used +30 (Undefined) +31 Unit No. (Undefined) Head CH No. +32 Leading address No. +33 Number of write digits +34 Write data ~ CH 2 ~ Write data +39 ~ +86 ~ (Undefined) Unit No. (Undefined) +87 Head CH No. +88 Leading address No. +89 Number of write digits +90 Write data ~ CH 4 ~ Write data +95 Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 0060 (7 to 96 decimal) +1 Number of Heads (4 digits Hex) 0001 to 0004 +(28(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(28(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(28(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(28(N–1)+5) Number of write digits (4 digits Hex) 0002 to 0018 (2 to 24 decimal) +(28(N–1)+6) to (28(N–1)+11) Write data (Hex) Input in hexadecimal code Up to 24 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. 458 Appendix M V600/V620 ID Controller Protocol Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. Write (Hex/8) (Sequence No. 525 (Hex 020D)) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 +2 +3 Number of send data words Number of Heads (Undefined) Unit No. (Undefined) Head CH No. +4 Leading address No. +5 Number of write digits +6 Write data ~ +8 +9 ~ (Undefined) Write data Not used ~ +15 +16 +17 ~ Not used (Undefined) Unit No. (Undefined) Head CH No. +18 Leading address No. +19 Number of write digits +20 Write data ~ +22 +101 (Undefined) Write data (Undefined) Unit No. ~ (Undefined) Head CH No. +102 Leading address No. +103 Number of write digits +104 Write data ~ +106 CH 2 ~ ~ +100 CH 1 CH 8 ~ (Undefined) Write data 459 Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0007 to 006B (7 to 107 decimal) +1 Number of Heads (4 digits Hex) 0001 to 0004 +(14(N–1)+2) Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +(14(N–1)+3) R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +(14(N–1)+4) Leading address No. (4 digits Hex) 0000 to FFFF +(14(N–1)+5) Number of write digits (4 digits Hex) 0002 to 000A (2 to 10 decimal) +(14(N–1)+6) to (14(N–1)+8) Write data (Hex) Input in hexadecimal code Up to 10 digits (max.) can be set N: Number of Heads Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Write data designated for hexadecimal is sent beginning with the largest offset from the send data words. 2. Always set an even number of digits for the write data. Auto-write (ASCII/1) (Sequence No. 526 (Hex 020E)) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 518 (Write(ASCII/1)). Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Auto-write (Hex/1) (Sequence No. 527 (Hex 020F)) This sequence is used when the number of Heads to be written to the Carrier is 1. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 522 (Write (Hex/1)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 522 (Write (Hex/1)). Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the Abort Bit must be turned OFF to terminate the sequence. Polling Auto-write (ASCII/2) (Sequence No. 528 (Hex 0210)) This sequence is used when the number of Heads to be written to the Carrier is 2. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. 460 V600/V620 ID Controller Protocol Appendix M Polling Auto-write Subcommand (ASCII/2) (Sequence No. 529 (Hex 0211)) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 528 before executing Sequence No. 529. 2. Retry processing is not performed for this sequence. Polling Auto-write (ASCII/4) (Sequence No. 530 (Hex 0212)) This sequence is used when the number of Heads to be written to the Carrier is 4. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 520 (Write(ASCII/4)). Note Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling autowrite. Polling Auto-write Subcommand (ASCII/4) (Sequence No. 531 (Hex 0213)) This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 530 before executing Sequence No. 531. 2. Retry processing is not performed for this sequence. Polling Auto-write (ASCII/8) (Sequence No. 532 (Hex 0214)) This sequence is used when the number of Heads to be written to the Carrier is 8. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (ASCII/8) (Sequence No. 533 (Hex 0215)) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). However, the leading address No., number of write, and write data are not used and become undefined. 461 V600/V620 ID Controller Protocol Appendix M Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 532 before executing Sequence No. 533. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hex/2) (Sequence No. 534 (Hex 0216)) This sequence is used when the number of Heads to be written to the Carrier is 2. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hex/2) (Sequence No. 535 (Hex 0217)) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)). However, the leading address No., number of write digits, and write data are not used and become undefined. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 534 before executing Sequence No. 535. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hex/4) (Sequence No. 536 (Hex 0218)) This sequence is used when the number of Heads to be written to the Carrier is 4. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hex/4) (Sequence No. 537 (Hex 0219)) This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 24 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (4th Operand of PMCR(260)) None. 462 Appendix M V600/V620 ID Controller Protocol Note 1. Execute Sequence No. 536 before executing Sequence No. 537. 2. Retry processing is not performed for this sequence. Polling Auto-write (Hex/8) (Sequence No. 538 (Hex 021A)) This sequence is used when the number of Heads to be written to the Carrier is 8. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)). Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)). Note 1. Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write. 2. Retry processing is not performed for this sequence. Polling Auto-write Subcommand (Hex/8) (Sequence No. 539 (Hex 021B)) This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head. Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)). However, the leading address No., number of write, and write data are not used and become undefined. Receive Data Word Allocation (4th Operand of PMCR(260)) None. Note 1. Execute Sequence No. 538 before executing Sequence No. 539. 2. Retry processing is not performed for this sequence. Data Check (Sequence No. 540 (Hex 021C)) This sequence writes and verifies the CRC code for check blocks designated by the user. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) +2 (Undefined) +3 Processing designation Unit No. Head CH No. (Undefined) +4 Leading address of check object +5 (Undefined) Number of check block bytes Offset Contents (data format) +0 Number of send data words (4 digits Hex) 0006 (fixed) Data +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) 00 to 15 (CA2A) +2 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. +3 Processing designation (2 digits Hex) Verification: 43 (C) Calculation: 4B (K) Management of number of write times: 4C (L) +4 Leading address of check object (4 digits Hex) 0000 to FFFF Number of check block bytes (2 digits Hex) If verification, calculation is designated: 03 to FF (set 00 for 256 bytes) If management of number of write times is designated: 00 to FF +5 (If management of number of write times is designated, H’ jjj0 to H’ jjj5 or H’ jjj8 to H’ jjjD) 463 Appendix M V600/V620 ID Controller Protocol Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words (Undefined) +1 Completion code Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0002 (fixed) Data +1 Completion code (2 digits Hex) (Verification, calculation designation) 00: Normal completion for calculation processing 75: Data in normal condition for verification processing 76: Error Data alarm for verification processing (If management of number of write times is designated) 75:Number of write times is under those which is specified. 76:alarm for number of write times is over those which is specified. Note If L (management of number of write times) is designated by processing designation, management of number of write times for Data Carrier of EEPROM is performed. Control (Sequence No. 541 (Hex 021D)) This sequence performs I/O operations or I/O reads. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 Number of send data words data +1 (Undefined) Unit No. +2 (Undefined) Offset OUT1 operation OUT2 operation Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) +2 OUT1 operation (1 digit BCD) 0: No operation 1: turned ON 2: turned OFF OUT2 operation (1 digit BCD) 0: No operation 1: turned ON 2: turned OFF Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 +1 Number of receive data words Current input status Offset Output status after operation Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 (fixed) +1 Leftmost 1 byte Current input status Leftmost 4 bits: IN1 operation Rightmost 4 bits: IN2 operation 1: ON status 0: OFF status Output status after operation Leftmost 4 bits: OUT1 operation Rightmost 4 bits: OUT2 operation 1: ON status 0: OFF status Note 1. The V600/620-CAjA does not support this command. 2. This sequence executes the equivalent of the CONTROL command. Error Information Read (Sequence No. 542 (Hex 021E)) This sequence reads information from the latest error log. 464 Appendix M V600/V620 ID Controller Protocol Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) 00 to 07 (CD1D) Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Error log ~ ~ Error log +75 Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0004 to 004C (4 to 76 decimal) +1 to +75 Error log (ASCII) One item of data is stored with 5 characters of generated command, generated Head No., generated error code. Note 1. The V600/620-CAjA does not support this command. 2. Up to 30 error records can be stored. 3. The most resent error records are stored first. Command Processing Cancel (Sequence No. 543 (Hex 021F)) This sequence cancels command processing except for polling command processing. The command waiting status is entered. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Offset Unit No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0002 (fixed) +1 Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 (Undefined) Unit No. Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0002 (fixed) Data +1 Completion code (2 digits Hex) 00: Normal termination 14: Auto or communications command processing not executed 75: Cancelled before the end of expansion command receive or before sync input went active or before detection of the existence of Data Carrier 76: Cancelled during read/write processing for Data Carrier 465 Appendix M V600/V620 ID Controller Protocol Polling Auto-read Command Processing Cancel (Sequence No. 544 (Hex 0220)) This sequence cancels polling auto-read processing. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send +0 data +1 Number of send data words (Undefined) Unit No. (Not used) +2 (Undefined) +3 Offset Head channel No. Contents (data format) Data +0 Number of send data words (4 digits Hex) 0004 (fixed) +1 Unit No. (2 digits BCD) Arbitrary (However, there is a limit for the maximum Unit No. depending on the model) +2 Not used +3 R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1 R/W Head CH 2 designation: 2 The CD1D must be set to 1. Receive Data Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 (Undefined) Completion code Offset Contents (data format) +0 Number of receive data words (4 digits Hex) 0002 (fixed) Data +1 Completion code (2 digits Hex) 75: Cancelled before communications processing with Data Carrier 76: Cancelled after communications processing with Data Carrier Polling Auto-write Command Processing Cancel (Sequence No. 545 (Hex 0221)) This sequence cancels polling auto-write processing Send Data Word Allocation (3rd Operand of PMCR(260)) The send data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel) Receive Data Word Allocation (4th Operand of PMCR(260)) The receive data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel) General-purpose Command (Sequence No. 546 (Hex 0222)) This sequence transmits arbitrary data and stores receive data to the receive data words. The characters “@”, FCS (terminator) are not required in the send data words and receive data words. These characters will be automatically added for transmission and automatically removed before saving data. Send Data Word Allocation (3rd Operand of PMCR(260)) First word of send data +0 Number of send data words +1 Send data byte length +2 Send data ~ +249 466 ~ Send data Appendix M V600/V620 ID Controller Protocol Offset Contents (data format) Data +0 Number of send data words (4 digits Hex) 0003 to 00FA (3 to 250 decimal) +1 Send data byte length (4 digits Hex) 0001 to 01F0 (1 to 496 decimal) The number of bytes in the send data except for @, the FCS, and the terminator. +2 to +249 Send data (ASCII) Input send data up to 496 characters (max.) in ASCII Receive Data Storage Word Allocation (4th Operand of PMCR(260)) Receive data storage words +0 Number of receive data words +1 Receive data ~ +249 ~ Receive data Offset Contents (data format) Data +0 Number of receive data words (4 digits Hex) 0002 to 00FA (2 to 250 decimal) +1 to +249 Receive data (ASCII) Receive data is stored in ASCII. Up to 498 characters (max.) 467 Appendix N Hayes Modem AT Command Protocol The Hayes Modem AT Command Protocol is used to make various settings or control remotely a Hayes modem connected to the Serial Communications Unit/Board via RS-232C cable. Protocol Configuration The configuration of the Hayes Modem AT Command Protocol is shown below. Sequence No. Communications sequence name Ladder interface Function Send word allocation Yes Receive word allocation No 550 (0226) Initialize modem (general-purpose) Initializes the modem connected to the Serial Communications Unit/Board. The initialization command is set in the words specified for the second operand of PMCR(260). 560 (0230) 570 (023A) 580 (0244) Initialize modem (specialized) Initializes certain OMRON Modems. No No 561 (0231) 571 (023B) 581 (0245) Dial Dials from the modem connected to the Serial Communications Unit/Board. AT commands and telephone numbers are set set in the words specified for the 3rd operand of PMCR(260). This sequence can be used only for certain OMRON modems. Yes No 552 (0228) Password After the line is connected, the password sent from the other exchange is verified to confirm that the line is connected to the desired exchange. The normal value of a password is set in the words specified for the 3rd operand of PMCR(260). Yes No 553 (0229) Data send/receive (general purpose sequence) Sends arbitrary data to the exchange which the line is connected. Send data is set in the words specified for the 2nd operand of PMCR(260). Receive data is stored in the words specified for the fourth operand of PMCR(260). Yes Yes 554 (022A) Escape No No 555 (022B) Hang up Shifts the modem to escape mode (the condition in which command input is available during data communications). The escape code is fixed to “+++” After shifting to escape mode, the line is disconnected. Executes continuously from initialization to dialling operations for certain OMRON Modems. No No Yes*1 No No No 562 (0232) Initialize and dial 572 (023C) 582 (0246) 590 (024E) Escape to hang up Executes continuously from shifting to the escape mode to hanging up. Note 1. Refer to sequences No. 561, No. 571, and No. 581 for dialing operations. 2. Ladder Interface Settings YES: User settings are required for the 3rd and 4th operands of PMCR(260). NO: Send word allocation: Set the constant 0000 for the 3rd operand (S). Receive word allocation: Set the constant 0000 for the 4th operand (D). 3. The hexadecimal equivalents of sequences numbers are given in parentheses. 469 Appendix N Hayes Modem AT Command Protocol Connections The connections when using the Hayes Modem AT Command Protocol is shown below. RS-232C Connection Modem Modem: D-sub 25-pin (female) FG SD RD RTS CTS DSR SG CD Telephone line Modem C200HX/C200HG/C200HE D-sub 9-pin (female) FG SD RD RTS CTS 5V DSR DTR SG ST2 RT DTR CI ST1 Compatible Modems Although most of the sequences in this protocol can be used regardless of modem, the sequences Initialize Modem (specialized) and Dial sequences can be used only for the following Modems: • MD24FB10V (OMRON Modem) • MD144FB5V (OMRON Intelligent Modem) • ME1414BIII, ME2814BII (OMRON FAX/DATA Modem) For other modems, create a modem initialization sequence using the general-purpose Initialize Modem sequence and dial using the Data Send/Receive sequence (Sequence No. 553). 470 Appendix N Hayes Modem AT Command Protocol Modem Settings When this protocol is used, it is required that the modem connected to the Serial Communications Unit/Board be initialized to the following conditions: Command echo No Result code display format Numeric format Speed display, busy/dialling tone detection at connection Error correction data compression display Baud rate display enabled, busy and dialling tone detection enabled. Error correction/data compression display enabled MNP setting Error correction provided (auto-reliable mode) MNP class setting MNP class 4 V.42 compression, Error correction Not enabled Flow control between terminal modems Not enabled ER signal control Always ON Escape code + Note 1. It is recommended that, in addition to the above settings, the abort timer should be set so that communications are cut off if a communications error happened due to incidents such as cable disconnection between the Serial Communications Unit/Board and modem. The abort timer is set to 10 minutes for the modem initialization (specialized) (Sequences No. 560, No. 570, No. 580: Initialize Modem (Specialized)). Refer to modem’s manual for further information about abort timers. 2. The data format of the modem (baud rate, data length, parity, stop bit) is set by AT commands issued from a device connected to the modem. Its settings should conform to communications conditions of the device which issues AT commands. Therefore when communications are made between the modem and Serial Communications Unit/Board, it is required that communications conditions should be set by issuing AT commands from the Serial Communications Unit/Board. 3. Modem settings become invalid if the power supply is turned off and must be set again. However, a memory backup function can be used to protect settings so that even after the power supply to the modem is turned off, it can communicate with the previous setting conditions. For Initialize Modem (specialized), the modem initialization command is built in as message data. However, for Initialize Modem (general-purpose), the command must be specified in the send data for PMCR(260). OPR 1 (Communications port settings) OPR 2 #0226 (Sequence No. 550) OPR 3 Address for first word containing initialization command character string S None (Set #0000) OPR 4 S+0 Number of words from address set for operand 2 to end of data 4 digits Hex S+1 Number of bytes for send data (initialization command) 4 digits Hex S+2 : S+n Send data (initialization command) (Fill data to left for odd numbers of bytes) ASCII Setting Example for Modem Initialization Command • MD24FB10V Using Sequence #550 (OMRON) The following command is set in the words specified by the 3rd operand of PMCR(260). ATE0V0X4\V2\N3%C0*C0\X1&M0S26=10 0012 0020 A T E 0 V 0 X 4 \ V 2 \ N 3 %C 0 * C 0 \ X 1 & M 0 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR(260) when it is used (words) Note Turn ON pin 4 of DIP switches SW3 on for this Modem (ER signal always ON). 471 Appendix N Hayes Modem AT Command Protocol MD144FB5V (OMRON, No longer manufactured.) The following command is set in the words specified by the second operand of PMCR(260). ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10 0017 0029 A T E 0 V 0 X 4 \ V 2 \ N 3 %C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9 6 0 0 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR(260) when it is used (words) ME1414BIII/ME2814BII (OMRON) The following command is set in the words specified by the second operand of PMCR(260). AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10 0018 002C A T \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 %C 0 & D 0 & E 0 \ X 1 S 2 6 = 1 0 Character string length of modem initialization command (bytes) Code length of PMCR(260) when it is used (words) Note Turn ON DIP switch SW3 on in the rear of the Modem. Dialling (Sequences No. 561 (Hex 0231), No. 571 (Hex 023B), and No. 581 (Hex 0245)) To dial a telephone numbers for the OMRON ME1414BIII/ME2814BII Modems using sequences No. 561, 571, 581, set the dialling command and telephone number in the words specified by the 3rd operand of PMCR(260). However, for other Modems, make the following settings for the Data Send/Receive sequence. This is an example of telephone number settings for the above mentioned 4 OMRON Modems. Operand and Send Data Word Settings of PMCR(260) OPR 2 472 MD24FB10V #0231 MD144FB5V #023B ME1414BIII/ME2814BII #0245 OPR 3 First address S of send data (dialling operation) OPR 4 None (Set #0000) S+0 Number of words from address set for operand 2 to end of data 4 digits Hex S+1 Number of bytes of send data (dialling operation) 4 digits Hex S+2 : S+n Send data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII Appendix N Hayes Modem AT Command Protocol Setting Example If telephone number is 03-0123-4567 000A 0010 4154 4454 3033 2D30 3132 332D 3435 3637 AT DT 03 –0 12 3– 45 67 Character string length of dialling operation sent to modem (bytes) Code length of PMCR(260) when it is used (words) Note 1. This example uses a tone line. Change ATDT to ATDP for pulse lines. 2. Fill the telephone number to the left in the words if the character string length of the dialling operation is an odd number of bytes. 0008 000B 4154 4454 3031 2D32 3334 3500 AT DT 01 –2 34 5j Character string length of dialling operation sent to modem (bytes) Code length of PMCR(260) when it is used (words) Password Verification (Sequence No. 552 (Hex 0228)) A password can be verified by executing sequence No. 552 of this protocol. It is required to set in advance the value of the password in the words specified by the second operand of PMCR(260). Operand and Send Data Word Settings of PMCR(260) OPR 2 #0228 OPR 3 Address of first word where the password is set S OPR4 None (Set #0000) S+0 Number of words from address set for operand 3 to end of data 4 digits Hex S+1 Number of bytes of comparison data (normal value of password) 4 digits Hex S+2 : S+n Comparison value (password normal value) (Fill data to left for odd numbers of bytes) ASCII Setting Example When password is OMRON-CO. 0006 0008 4F4D 524F 4E2D 434F OM RO N– CO Character string length of password sent to modem (bytes) Code length of PMCR(260) when it is used (words) 473 Appendix N Hayes Modem AT Command Protocol Password Verification Operation The number of retries is 3 for password verification. PC Personal computer (remote exchange) Password verification (starting #552) Dispatching character string “Password: ” Receiving character string (Retry up to 3 times) Password Issuing password Receiving password Verifying password Verification result Terminating process When Protocol Macro Execution Flag turns ON: Port 1: CIO 190915 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 15 for Serial Communications Units. Port 2: CIO 191915 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 15 for Serial Communications Units. Data Send/Receive (Sequence No. 553 (Hex 0229)) Data Send/Receive can be executed using sequence No. 553. The send data sent to another exchange is set in the words specified by the 3rd operand of PMCR(260). Data received by the PC is stored in the words specified by the 4th operand of PMCR(260). Operand and Send/Receive Data Word Settings of PMCR(260) OPR 2 #0229 OPR 3 First address C1 of the words where send data is set OPR 4 First address C2 of the words where receive data is stored • Send Data Words C1+0 Number of words from address set for operand 2 to end of data 4 digits Hex C1+1 Number of bytes of send data 4 digits Hex C1+2 : C1+n Send data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII • Receive Data Storage Words 474 C2+0 Number of bytes of receive data 4 digits Hex C2+1 : C2+n Receive data (dialling operation) (Fill data to left for odd numbers of bytes) ASCII Appendix N Hayes Modem AT Command Protocol Setting Example When send data is THIS IS SAMPLE. 0009 000E 5448 4953 2049 5320 5341 4D50 4C45 TH IS I S SA MP LE Character string length of send data sent to modem (bytes) Code length of PMCR(260) when it is used (words) A maximum of 200 bytes (including the CR) can be received. When the received data is RETURN OK, the content stored in the receive words is as follows: 0006 5245 5455 524E 204F RE TU RN O 4B00 K Length of received character string (words) Note An error will occur is the reception data is not received within 90 seconds after the data is sent. Escape Mode (Sequence No. 554 (Hex 022A)) Shifting to the escape mode can be made using sequence No. 554. No setting is necessary for this sequence. Note The character string to shift the online mode to the escape mode (i.e., the escape code) is ‘+’ for modem settings. Hang Up Command (Sequence No. 555 (Hex 022B)) The hang up command (to disconnect the line) can be executed using sequence No. 555. No setting is necessary for this sequence. Communication Errors Three result codes are monitored after an AT command is sent to the modem. When a result code is returned, it will be checked. If the code is not the normal result code (“OK”, “CONNECT 9600/REL4”, “CONNECT 2400/REL4”, in words), after a fixed time of waiting to send, the following retry processing will be repeated 2 times to send the AT command again and waiting for another result code. The receive monitoring time and send wait time for each sequence are shown below. Sequence No. 550 (0226) Initialize modem (general-purpose) Initialize modem (specialized) Receive monitoring time 10 s 10 s Send wait time for retries 1s 1s Dial 90 s 90 s Password None 3s 553 (0229) Data send/receive (general-purpose) 90 s None 554 (022A) Escape 10 s 1.5 s (after first try) 555 (022B) Hang up Initialize and dial 10 s 90s 1.5 s (after first try) Initializing: 1 s Dialling: 90 s Escape and hang up 10 s 1.5 s (after first try) 560 570 580 561 571 581 552 562 572 582 590 (0230 (023A) (0244) (0231) (023B) (0245) (0228) (0232) (023C) (0246) (024E) Sequence name Note The hexadecimal equivalents of sequences numbers are given in parentheses. 475 Appendix O Changing Communications Port Settings Using STUP(237) The STUP(237) instruction can be used to change the serial communications mode, communications specifications, and other settings for each port of the Serial Communications Board or Unit during CPU Unit operation. Executing the STUP(237) Instruction Use the STUP(237) instruction to change the communications port settings. For example, the STUP(237) instruction can be used to switch the protocol to Host Link mode without leaving RUN mode and allow the user to monitor and program the CPU Unit from the host computer when the specified conditions are met while send/receive sequences for modem and line connections are being executed in protocol macro mode. STUP Instruction Specifications Control data (serial port number, remote unit address) First words of port settings Control Data (C) Serial port number Remote unit address Set the following items. Serial Port Number Set the serial port number (physical port number) of the Serial Communications Board or Unit to which the remote node is connected. PORT1: 1 (hex)/PORT2: 2 (hex) Remote Unit Address Specify the unit address of the Serial Communications Board or Unit for which the serial port setting is to be changed. Serial Communications Board: E1 (hex) Serial Communications Unit: Unit number + 10 (hex) Setting: 10 to 1F (hex) Note The CPU Bus Unit number (0 to F) is set using the rotary switch on the front panel of the Unit. First Word of Port Settings (S) Set the address of the first word containing the serial port settings. The data is stored starting from word S in the say way as the port settings in the 10-word area allocated in the DM Area for each port. For details on the Setup Area, see 2-3 I/O Memory Allocations or 4-2, 5-2, 6-2, and 7-2 Setup Area Allocations. 15 S S+1 00 Serial port system setting 10 words per port S+9 When the STUP(237) instruction is executed, the CPU Unit changes the contents of the relevant DM Area in the Unit, then automatically turns ON the Port Settings Change Bit (words A620 to A635) in the Auxiliary Area. A620 + unit number Port 1 Port Settings Change Bit: Bit 1 Port 2 Port Settings Change Bit: Bit 2 477 Appendix O Changing Communications Port Settings Using STUP(237) When the cyclic service finishes changing the communications port settings in the Serial Communications Board or Unit, the Board or Unit automatically restarts the port and turns OFF the Port Settings Change Bit. Data Contents Area C S CIO Area 0000 to 6143 0000 to 6134 Work Area W000 to W511 W000 to W502 Holding Area H000 to H511 H000 to H502 Auxiliary Area A000 to A959 A000 to A950 Timer Area T0000 to T4095 T0000 to T4086 Counter Area C0000 to C4095 C0000 to C4086 Data Memory (DM) Area D00000 to D32767 D00000 to D32758 Extended Data Memory (EM) Area E00000 to D32767 E00000 to E32758 Extended Data Memory (EM) Area (including bank specification) Indirect DM/EM address, Binary En_00000 to En_32767 (n = 0 to C) En_00000 to En_32758 (n = 0 to C) Indirect DM/EM address, BCD *D00000 to *D32767, *E00000 to *E32767, *En_00000 to *En_32767 Constants See Control Data (C). #0000 to FFFF (Binary data) Data Registers DR0 to DR15 --- Index Registers, Direct --- Index Registers, Indirect ,IR0 to ,IR15 –2048 to +2047 ,IR0 to –2048 to +2047,IR15 DR0 to DR15 ,IR0 to IR15 ,IR0+(++) to ,IR15+(++) ,–(– –)IR0 to ,–(– –)IR15 @D00000 to @D32767, @E00000 to @E32767, @En_00000 to @En_32767 Error Flags (ER) The Error Flag will turn ON in the following cases: • The data specified in S is outside the allowable range. • The Port Settings Change Bit is already ON when the instruction is executed. Ladder Program Example When CIO 000000 turns ON, the settings for port 2 for the Serial Communications Board will be changed to the values set in the 10 words from D00200 to D00209. In the following example, the protocol is changed to Host Link mode. Ladder Program 000000 @STUP #02E1 D00200 478 Changing Communications Port Settings Using STUP(237) Appendix O Settings S: S+1: S+2: S+3: : S+9: D00200 D00201 D00202 D00203 0500 0000 0000 0000 Port setting: Defaults Protocol mode: 1 hex (Host Link) Baud rate: Default (9,600 bps) Transmission delay time: 0 ms CTS control: None Unit number: 00 Transmit D32010 D32011 D32012 D32013 0500 0000 0000 0000 Settings for port 2 of Serial Communications Board (D32010 to D32019) D32019 479 Index Numbers C-series Units, changes in communications specifications, 105 C200H Communications Boards, 22, 105 1:1 NT Link, 3 C200H Host Link Units, 22 1:N NT Link, 3, 5, 7 Auxiliary Area allocations, 153 CIO Area allocations, 154 commands, 150 connecting Programmable Terminals, 82 connection example, 32 CPU Bus Unit Area allocations, 155 errors, 173 executing communications, 38 Inner Board CIO Area allocations, 155 Inner Board error information, 154 overview, 150 Setup Area allocations, 153 Status Area allocations, 156 C200HX/HG/HE Communications Board, changes in communications specifications, 105 2-wire and 4-wire connections, transmission circuits, 66 2-wire or 4-wire switch, 43 3Z4L Laser Micrometer, 108 connections, 380 protocols, sequences, 377–410 A cables, preparation, 86 CIO Area, 51 allocations, 29 1:N NT Link, 154 Host Link, 97 loopback test, 162 protocol macro, 122 Serial Communications Boards, 51 Serial Communications Units, 51 CPU Bus Unit Area allocations 1:N NT Link, 155 Host Link, 97 protocol macro, 123 Inner Board Area allocations 1:N NT Link, 155 Host Link, 97 protocol macro, 122 Status Area allocations 1:N NT Link, 156 Host Link, 97 protocol macro, 126 cleaning, 188 Abort Flag, 130, 132 Abort Switch, 147 Access Error Flag, 138 Auxiliary Area allocations 1:N NT Link, 153 Host Link, 96 protocol macro, 120 bits, 55 B CMND(490) instruction, 5 commands CONTROLLER DATA READ: 05 01, 186 ERROR LOG CLEAR: 21 023, 188 ERROR LOG READ: 21 02, 187 communications distance Host Link, 18 protocol macro, 19 communications modes. See 1:N NT Link; Host Link; Loopback Test; protocol macro; serial communications modes Communications Port Completion Codes, 100, 139 Communications Port Enabled Flags, 100, 139 B500-AL001-E Link Adapter, 85 Communications Port Error Flags, 100, 139 Backplanes, applicable Backplanes, 17 communications timing, 99 commands addressed to host computer, 101 Bar Code Readers, 7 baud rate Host Link, 18 protocol macro, 19 Board/Unit Watchdog Timer Error Flags, 122 C comparison, previous products, 22, 105 CompoWay/F Master command and response formats, 196 communications specifications, 196 connections, 209 message frames, 201 protocols, 200 sequences, 195, 200 transmission procedure, 196 C-mode commands, 5 CompoWay/F protocol, 108 C-series Host Link Units, changes in communications specifications, 104 connectors connector hoods, 88 481 Index cover dimensions, 65 pin layout RS-232C ports, 64 RS-422A/485 ports, 64 wiring, 86 CONTROLLER DATA READ: 05 01, 186 CPU Bus Unit Area, allocations, 51 1:N NT Link, 155 Host Link, 97 protocol macro, 123 EC Directives, xv EMC Directives, xv EMI measures, xvi error check codes, Host Link, 18 error codes, 130, 135, 183 troubleshooting, 185 Error Flag, 138 CS1 CPU Bus Units, 4 error log specifications, 182 table configuration, 182 EEPROM, 182 RAM, 182 reading and clearing, 186 CS1 Expansion Racks, 4 ERROR LOG CLEAR: 21 023, 188 CS1W-SCB21 Serial Communications Board, 3 specifications, 17 ERROR LOG READ: 21 02, 187 CS1W-SCB41 Serial Communication Board, 3 specifications, 17 errors 1:N NT Link, 173 framing error, 129 Host Link, 167 overrun error, 129 parity error, 129 protocol macro, 175 troubleshooting, 167 CPU Bus Unit DM Area, 17 CPU Units, supporting CPU Units, 17 CS1 CPU Bus Unit Restart Bits, 34 CS1W-SCU21 Serial Communications Unit, 4 specifications, 17 CTS control, 95 current consumption, 17 CV-series Units, changes in communications specifications, 104, 105 error responses, 103 ES100 Digital Controller, connections, 302 CVM1 Units, changes in communications specifications, 104, 105 ES100_ Digital Controller, 108 protocols, sequences, 301–341 CX-Protocol, 6, 32 Executed Reception Case No. (code), 130, 134 Executed Reception Case No. Flag, 130, 134 D dimensions Serial Communications Boards, 43 Serial Communications Units, 45 DM Area, allocations, 29 Serial Communications Boards, 48 Serial Communications Units, 49 Executed Step No. (code), 130, 133 Executed Step No. Flag, 130, 134 external dimensions, connector cover, 65 F F200/F300/F350 Visual Inspection Unit, 108 ferrite cores, xvi E E5_J Temperature Controller, 108 connections, 288 protocols, sequences, 287–300 E5_K Digital Controller, 108 connections read, 212 write, 212 read protocols, sequences, 211–228, 229–243 E5ZE Temperature Controller, 108 connections read, 246 write, 246 read protocols, sequences, 245–266 write protocols, sequences, 267–285 482 FINS commands, 5 framing errors, 129 H Hayes Modem AT Command, 108 compatible modems, 470 connections, 470 protocols, sequences, 469–475 heat-shrinking tubes, 88 Host Link, 3, 5 Auxiliary Area allocations, 96 CIO Area allocations, 97 commands, 5 communications timing, 99 Index connection example, 32 CPU Bus Unit Area allocations, 97 error responses, 103 errors, 167 executing communications, 34 host-initiated communications, 92 Inner Board CIO Area allocations, 97 Inner Board error information, 96 PC-initiated communications, 92 ports, 63 connections, 68 reception buffers, 103 Setup Area allocations, 94 system configuration, 11 unit numbers, 95 L ladder programs, protocol macro, 140 Link Adapters, 63, 67, 69, 77, 85, 86 loopback test, 3, 5, 8 CIO Area allocations, 162 connections, 160 executing, 160 indicators, 161 port connections, 83 procedure, 160 protocol status, 55 Setup Area allocations, 161 Low Voltage Directive, xv Host Link Units, changes in communications specifications, 105 M I I/O memory allocations, 48 I/O tables, 32 indicators CPU Unit, 40 error displays Serial Communications Boards, 164 Serial Communications Units, 165 loopback test, 161 Serial Communications Boards, 40 Serial Communications Units, 44 Inner Board CIO Area, allocations, 155 1:N NT Link, 155 Host Link, 97 protocol macro, 122 Inner Board DM Area, 17 maintenance cleaning, 188 inspection, 188 modem compatibility, 470 settings, 471 mounting height, 65 N noise reduction, 66 NT Link ports, 63 protocol status, 55 NT Link commands, 7 NT-AL001-E Link Adapter, 13 DIP switch settings, 67 Inner Board Restart Bit, 34 Inner Boards, 5 error information, 56 1:N NT Link, 154 Host Link, 96 protocol macro, 121 Inner Bus Error Flag, 122 inspection, 188 O operating environment, precautions, xiii overrun errors, 129 P installation Serial Communications Boards, 30, 60 Serial Communications Units, 30, 61 parameters sequence, 111 step, 112 Intelligent Signal Processors, 7 parity errors, 129 K K3T_ Intelligent Signal Processor, 108 connections, 345 protocols, sequences, 343–363 PMCR(260) instruction, 6, 201 operand settings, 142 specifications, 136 Port Settings Change Bits, 34, 122 1:N NT Link, 153 Host Link, 96 protocol macro, 120 Serial Communications Boards, 55 483 Index Serial Communications Units, 56 Port Settings Changing Flag, 17 precautions applications, xiii general, xi installation, xiii installing Serial Communications Boards, 60 installing Serial Communications Units, 62 noise reduction, 66 operating environment, xiii replacement, 189 safety, xii system configuration, 61 wiring, xiii, 63 previous products, comparison, 22, 105 E5ZE Temperature Controller write, sequences, 267–285 ES100_ Digital Controller, sequences, 301–341 Hayes Modem AT Command, sequences, 469–475 K3T_ Intelligent Signal Processor, sequences, 343–363 Protocol Support Software, list, 194 structure, 110 V500/V520 Bar Code Reader, sequences, 365–375 V600/V620 ID Controller, sequences, 431–467 Visual Inspection System, sequences, 411–429 PT Communications Execution Flag, 157 PT Priority Registered Flag, 157 PTs. See Programmable Terminals R Programmable Terminals, 4 1:N NT Link connections, 82 RS-232C port connections, 73 reception buffers, 103, 129 Programming Console, 4 reception matrixes, 111 Programming Devices, 4 CX-Programmer, 32 Programming Console, 32 RECV(098) instruction, 5 protocol macro, 3, 5, 6 applications, 136 Auxiliary Area allocations, 120 CIO Area allocations, 122 connection example, 32 connections, 75 CPU Bus Unit Area allocations, 123 errors, 175 executing communications, 35 functions, 108 Inner Board CIO Area allocations, 122 Inner Board error information, 121 ladder programs, 140 ports, 63 protocol status, 54 Setup Area allocations, 116 Software Switches, 124 specifications, 18 standard system protocols, 108 Status Area allocations, 126 system configuration, 14 time lag, 117 Reset Counter Present Value, 131, 135 Protocol Macro Error Code, 133 Protocol Macro Executing Flag, 130, 132 Protocol Macro Execution Error Flag, 122 protocol specifications, 18 protocol status loopback test, 55 NT Link, 55 protocol macro, 54, 130 protocols, 194 3Z4L Laser Micrometer, sequences, 377–410 CompoWay/F, sequences, 195 creating, 109 E5_J Temperature Controller, sequences, 287–300 E5_K Digital Controller read, sequences, 211–228, 229–243 E5ZE Temperature Controller read, sequences, 245–266 484 reception case number, 130 Repeat Counter Setting Value, 131, 135 Restart Bit Serial Communications Boards, 56 Serial Communications Units, 57 RS-232C connections, 209 RS-232C ports 1:1 connections, 77 1:N connections, 79 changes from previous products, 103 connector pin layout, 41, 64 direct connections 1:N NT Link, 82 Programmable Terminals, 73 host computer connections, 69 Programmable Terminal connections, 73 specifications, 41 wiring, 83 RS-422 connections, 210 RS-422A/485 ports 1:1 connections, 80 1:N connections, 81 changes from previous products, 105 connector pin layout, 42, 64 host computer connections, 71 Programmable Terminal connections, 73 specifications, 42 wiring, 84 RS-485 connections, 210 S send delay, 95 SEND(090) instruction, 5 Send/Receive Sequence No., 130, 133 send/receive sequences, 136 Index Sequence Abort Completion Flag, 130, 132 Sequence End Completion Flag, 130, 132 sequence parameters, 111 Sequence Wait Flag, 130, 133 sequences, CompoWay/F Master Broadcast with ASCII Conversion, No Response, 204 Broadcast with No Conversion and No Response, 206 General-purpose Broadcast with No Conversion and No Response, 208 General-purpose Send with No Conversion and with Response, 207 Send with ASCII Conversion, with Response, 201 Send with No Conversion and with Response, 205 sequences, 3Z4L Laser Micrometer 3Z4L Clear, 385 3Z4L Initialize (3000-series), 401 3Z4L Initialize (4000-series), 408 All Statistic Memory Clear (3000-series), 395 Automatic Detection List Request (3000-series), 401 Automatic Detection Release (3000-series), 400 Automatic Detection Set (3000-series), 400 AVG Move (H) Times Set (3000-series), 399 AVG Move (L) Times Set (3000-series), 399 AVG Move Interval Set (3000-series), 399 Calibration Release, 386 Calibration Set, 386 Continuous Measurement Start (Interrupt) (3000-series), 394 Continuous Measurement Start (Interrupt) (4000-series), 406 Continuous Measurement Start (Scan) (3000-series), 394 Continuous Measurement Start (Scan) (4000-series), 406 Continuous Measurement Termination (4000-series), 407 Data Request (3000-series), 394 Data Request (4000-series), 407 Deflection Measurement Start (4000-series), 406 E Unit Set, 385 Forced Negative Zero (4000-series), 407 Forced Positive Zero (4000-series), 407 Forced Zero Release (4000-series), 408 General-purpose Command 1 (4000-series), 408 General-purpose Command 2 (4000-series), 409 Measurement Condition List Request (3000-series), 390 Measurement Condition List Request (4000-series), 404 Measurement Condition Release (3000-series), 390 Measurement Condition Release (4000-series), 404 Measurement Condition Set (3000-series), 387 Measurement Condition Set (4000-series), 402 Measurement Termination (3000-series), 394 Memory Switch Set, 385 Memory Switch Set 1 (3000-series), 397 Memory Switch Set 2 (3000-series), 398 mm Unit Set, 385 Program Number Set (3000-series), 387 Settings, 380 Simple AVG Times Set (3000-series), 398 Single Run Measurement Start (3000-series), 393 Single Run Measurement Start (4000-series), 405 Statistic Processing Calculation Non-execution (3000-series), 395 Statistic Processing Execution (3000-series), 395 Statistic Processing Memory Clear (3000-series), 395 Statistic Result Request (3000-series), 395 Zero Run Measurement Start (3000-series), 393 sequences, E5_J Temperature Controller General-purpose Read, 299 General-purpose Write, 299 Read Heater Current, 298 Read Initial Status, 298 Read Input Shift Value, 296 Read Output Value, 297 Read Parameters 1, 294 Read Parameters 2, 295 Read Process Value, 297 Read Set Point Limit, 297 Save Set Point, 291 Select Backup Mode, 290 Select Local Mode, 290 Select RAM Write Mode, 291 Select Remote Mode, 290 Write Input Shift Value, 293 Write Parameters 1, 291 Write Parameters 2, 292 sequences, E5_K Digital Controller Execute/Cancel AT, 242 General-purpose Read, 228 General-purpose Write, 240 Read Alarm Hysteresis, 220 Read Alarm Value, 215 Read Control Period), 217 Read Cooling Coefficient, 216 Read Dead Band, 216 Read Hysteresis), 217 Read Input Digital Filter, 220 Read Input Shift Limits, 220 Read LBA Detection Time, 218 Read Level 0 Parameters, 221 Read Level 1 Parameters 1, 222 Read Level 1 Parameters 2, 223 Read Level 2 Parameters 1, 225 Read Level 2 Parameters 2, 226 Read Manual Reset Value, 216 Read MV, 214 Read MV at Stop Time and at PV Error, 219 Read MV Limits, 219 Read Process Value, 213 Read Proportional Band, Integral Time, and Derivative Time, 215 Read Set Point, 214 Read Set Point during SP Ramp, 213 Read SP Ramp Time Unit and Set Value, 218 Remote/Local, 241 Run/Stop), 241 Software Reset, 243 Switch to Level 0 (Software Reset), 240 Switch to Level 1, 243 Write Alarm Hysteresis, 234 Write Alarm Value, 230 Write Control Period, 232 Write Cooling Coefficient), 231 Write Dead Band), 231 Write Hysteresis, 231 Write Input Digital Filter, 234 Write Input Shift Value, 234 Write LBA Detection Time, 233 Write Level 0 Parameters, 235 Write Level 1 Parameter 2, 237 Write Level 1 Parameters 1, 236 Write Level 2 Parameters 1, 238 485 Index Write Level 2 Parameters 2, 239 Write Manual Reset Value, 231 Write MV at Stop Time and at PV Error, 233 Write MV Limits, 233 Write Proportional Band, Integral Time, and Derivative Time, 230 Write Set Point, 230 Write SP Ramp Time Unit and Set Value, 232 sequences, E5ZE Temperature Controller Cancel Autotuning, 276 Initialize Settings, 281 Read Alarm Mode, 255 Read Alarm Temperatures, 256 Read Control Period, 254 Read Cooling Coefficient, 266 Read Dead Band/Overlap Band, 265 Read Error Status, 258 Read HB Alarm and HS Alarm Valid Channels, 263 Read Heater Burnout and SSR Failure Detection Currents, 263 Read Heater Current and SSR Leakage Current, 264 Read Hysteresis, 257 Read Input Shift Value, 259 Read Manual Reset Value, 259 Read Operation Status, 257 Read Output Mode, 255 Read Output Value Change Rate Limit, 262 Read Output Value Limit, 261 Read Output Values, 251 Read Present Set Point, 261 Read Process Value, 250 Read Proportional Band, Integral Time, and Derivative Time, 253 Read Ramp Value, 260 Read Set Point, 249 Read Set Point, Process Value, and Output Value, 252 Read Setting Unit, 258 Save Settings, 281 Start Autotuning, 275 Start Control, 285 Start Manual Operation, 285 Stop Operation or Control, 285 Write Alarm Mode, 272 Write Alarm Temperature (Setting Unit 0.1), 274 Write Alarm Temperature (Setting Unit 1), 273 Write Control Period, 271 Write Cooling Coefficient, 284 Write Dead Band/Overlap Band, 283 Write HB and HS Alarm Valid Channels, 282 Write Heater Burnout and SSR Failure Detection Current, 282 Write Hysteresis, 275 Write Input Shift Value, 276 Write Manual Output Value, 278 Write Manual Reset Value, 277 Write Output Mode, 272 Write Output Value Change Rate Limit, 280 Write Output Value Limit, 279 Write Proportional Band, Integral Time, and Derivative Time, 270 Write Ramp Value, 278 Write Set Point (Setting Unit 0.1), 269 Write Set Point (Setting Unit 1), 268 Write Setting Unit, 276 486 sequences, ES100_ Digital Controller Auto Mode, 335 Cancel A.T., 337 Change Bank No., 338 Change Pattern No., 338 Execute A.T., 336 External Setting Mode, 333 General-purpose Command, 340 Local Setting Mode, 333 Manual Mode, 336 Read Adjustment Parameters, 314 Read Control Monitor Data, 312 Read Controller Status, 339 Read Error Detection Data, 306 Read Event Data, 304 Read Heater Burnout Data, 308 Read Local SP, 325 Read MV Data, 311 Read PID Control Parameters 1, 318 Read PID Control Parameters 2, 320 Read Program Parameters, 328 Read PV Data, 309 Read SP Data, 310 Read Time Signal, 305 Remote Setting Mode, 332 Reset (Stop), 335 Run Command, 334 Write Adjustment Parameters, 317 Write Local SP, 327 Write PID Control Parameters 1, 322 Write PID Control Parameters 2, 324 Write Program Parameters, 331 sequences, Hayes Modem AT Command Data Send/Receive (General-purpose), 474 Dial, 472 Dial, 472 Dial, 472 Escape, 475 Escape to Hang Up, 469 Hang Up, 475 Initialize and Dial, 469 Initialize and Dial, 469 Initialize and Dial, 469 Initialize Modem (Specialized), 471 Initialize Modem (Specialized), 471 Initialize Modem (Specialized), 471 Password, 473 Set Modem (General-purpose), 471 sequences, K3T_ Intelligent Signal Processor General-purpose Command, 363 Model Data Read (by Unit Number), 361 Model Data Read (Continuous Units), 362 Read Display Value (PV) (by Unit Number), 359 Read Display Value (PV) (Continuous Units), 361 Read Holding Data, 357 Read Holding Data BH (Continuous Units), 359 Read Holding Data PH (Continuous Units), 358 Read Set Value (by Unit Number), 353 Read Set Value H (Continuous Units), 354 Read Set Value H with Bank (Continuous Units), 356 Read Set Value HH (Continuous Units), 354 Read Set Value HH with Bank (Continuous Units), 356 Read Set Value L (Continuous Units), 354 Read Set Value L with Bank (Continuous Units), 356 Read Set Value LL (Continuous Units), 354 Index Read Set Value LL with Bank (Continuous Units), 356 Read Set Value O1 with Bank (Continuous Units), 357 Read Set Value O2 with Bank (Continuous Units), 357 Read Set Value O3 with Bank (Continuous Units), 357 Read Set Value O4 with Bank (Continuous Units)), 356 Read Set Value O5 with Bank (Continuous Units), 356 Read Set Value with Bank (by Unit Number), 355 Reset (by Unit Number), 348 Reset Control (Continuous Units), 348 Write Set Value (by Unit Number), 349 Write Set Value H (Continuous Units), 350 Write Set Value H with Bank (Continuous Units), 352 Write Set Value HH (Continuous Units), 349 Write Set Value HH with Bank (Continuous Units), 351 Write Set Value L (Continuous Units), 350 Write Set Value L with Bank (Continuous Units), 352 Write Set Value LL (Continuous Units), 350 Write Set Value LL with Bank (Continuous Units), 352 Write Set Value O1 with Bank (Continuous Units), 353 Write Set Value O2 with Bank (Continuous Units), 353 Write Set Value O3 with Bank (Continuous Units), 352 Write Set Value O4 with Bank (Continuous Units), 352 Write Set Value O5 with Bank (Continuous Units), 352 Write Set Value with Bank (by Unit Number), 350 sequences, V500/V520 Bar Code Reader BCR Connection Confirmation (V500), 372 BCR Function Read (V500), 370 BCR Function Write (V500), 369 BCR Initialize (V500), 373 BCR Read Start, 368 BCR Read Stop, 368 Complete Data Read, 368 Data Continuous Read (Interrupt) (V500), 373 Data Continuous Read (Interrupt) (V520), 374 Data Continuous Read (Scan) (V500), 373 Data Continuous Read (Scan) (V520), 373 Data Read, 368 General-purpose Command 1, 374 General-purpose Command 2, 375 Log Data Clear (V500), 373 Log Data Output Request (V500), 371 Preset Data Set (V500), 372 System Setting, 367 sequences, V600/V620 ID Controller Auto-read (ASCII/1), 447 Auto-read (Hexadecimal/1), 447 Auto-write (ASCII/1), 460 Auto-write (Hexadecimal/1), 460 Command Processing Cancel, 465 Control, 464 Data Check, 463 Error Information Read, 464 General-purpose Command, 466 Polling Auto-read (ASCII), 447 Polling Auto-read (ASCII/2), 448 Polling Auto-read (ASCII/4), 449 Polling Auto-read (ASCII/4), 449 Polling Auto-read (Hexadecimal), 450 Polling Auto-read (Hexadecimal/2), 450 Polling Auto-read (Hexadecimal/4), 451 Polling Auto-read (Hexadecimal/8), 451 Polling Auto-read Command Processing Cancel, 466 Polling Auto-write (ASCII/2), 460 Polling Auto-write (ASCII/4), 461 Polling Auto-write (ASCII/8), 461 Polling Auto-write (Hexadecimal/2), 462 Polling Auto-write (Hexadecimal/4), 462 Polling Auto-write (Hexadecimal/8), 463 Polling Auto-write Command Processing Cancel, 466 Polling Auto-write Subcommand (ASCII/2), 461 Polling Auto-write Subcommand (ASCII/4), 461 Polling Auto-write Subcommand (ASCII/8), 461 Polling Auto-write Subcommand (Hexadecimal/2), 462 Polling Auto-write Subcommand (Hexadecimal/4), 462 Polling Auto-write Subcommand (Hexadecimal/8), 463 Read (ASCII/1), 438 Read (ASCII/2), 439 Read (ASCII/4), 440 Read (ASCII/8), 441 Read (Hexadecimal/1), 442 Read (Hexadecimal/2), 443 Read (Hexadecimal/4), 444 Read (Hexadecimal/8), 446 Write (ASCII/1), 451 Write (ASCII/2), 452 Write (ASCII/4), 454 Write (ASCII/8), 455 Write (Hexadecimal/1), 456 Write (Hexadecimal/2), 457 Write (Hexadecimal/4), 458 Write (Hexadecimal/8), 459 sequences, Visual Inspection System Arbitrary Measurement Value Acquisition (F200), 417 Binary Level Modification (F200/300), 426 Camera Change (Decrease by 1) (F200/300), 426 Camera Change (Increase by 1) (F200/300), 426 Camera Designation and Positioning (F350), 425 Character String Inspection and Character Inspection (F350), 426 Continuous Measurement Execution (Interrupt) (F200), 415 Continuous Measurement Execution (Interrupt) (F300), 422 Continuous Measurement Execution (Scan) (F200), 414 Continuous Measurement Execution (Scan) (F300), 420 Evaluation Condition Change (F200), 416 General-purpose Command (Send), 428 General-purpose Command (Send/Receive), 428 Illumination Fluctuation Follow Execution (F300), 423 Inspection Execution and Character Inspection (F350), 425 Measurement Execution (F200), 414 Measurement Execution (F300), 419 Measurement Execution and Positioning (F350), 424 Measurement, Inspection Termination, 427 Reference Object Registration (Criterion) (F200), 416 Reference Object Registration (Group) (F200), 416 Reference Object Registration (Reference Position) (F200), 416 Reference Object Registration Command 1 Execution (F300), 423 Reference Object Registration Command 2 Execution (F300), 423 Reset (F200/300), 427 Scene Switching (Arbitrary), 427 Scene Switching (Decrease by 1), 427 Scene Switching (Increase by 1), 427 Scene Switching and Positioning (F350), 425 Serial Communications Boards, 3 CIO Area allocations, 51 component names, 40 data exchange, 46 487 Index DM Area allocations, 48 error information, 165 indicator error displays, 164 installation, 30, 60 replacement, 190 specifications, 17 serial communications modes, 63 See also 1:N NT Link; Host Link; Loopback Test; protocol macro 1:1 NT Link, 3 1:N NT Link, 3, 5, 7, 150 Host Link, 3, 5, 92 loopback test, 3, 5, 8, 160 protocol macro, 3, 5, 6, 108 selection, 27 Serial Communications Units, 4 CIO Area allocations, 51 component names, 44 data exchange, 47 DM Area allocations, 49 indicator error displays, 165 installation, 30, 61 precautions, 62 replacement, 190 specifications, 17 Setup Area, 32, 93 allocations, 49 1:N NT Link, 153 Host Link, 94 loopback test, 161 protocol macro, 116 Software Switches, 51, 52, 124 soldering, 88 specifications protocol, 18 Serial Communications Boards, 17 Serial Communications Units, 17 standard system protocol, 108, 193 communications problems, 114 DM Area settings, 113 examples, 113 modifying, 109 Status Area, 52 allocations 1:N NT Link, 156 Host Link, 97 protocol macro, 126 error information, 167 Step Error Processing Flag, 130, 132 step number, 130 488 step parameters, 112 STUP(237) instruction, 17 executing, 477 specifications, 477 system configuration Host Link, 11 precautions, 61 protocol macro, 14 T terminating resistance switch, 43 trace function, protocol macro, 22 Tracing Flag, 130, 132 troubleshooting, 167 1:N NT Link errors, 173 error codes, 185 Host Link errors, 167 protocol macro errors, 175 U unit number switch, 45 V V500/V520 Bar Code Reader, 108 connections, 366 protocols, sequences, 365–375 V600/V620 ID Controller, 108 connections, 433 protocols, sequences, 431–467 Visual Inspection System connections, 413 protocols, sequences, 411–429 Visual Inspection Units, 108 W weight, 17 wiring connectors, 86 precautions, 63 RS-232C ports, 83 RS-422A/485 ports, 84 Revision History A manual revision code appears as a suffix to the catalog number on the front cover of the manual. Cat. No. W336-E1-2 Revision code The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. Revision code 1 Date February 1999 Original production Revised content 2 February 2000 Changes were made on the following pages. Page 4: “Boards” corrected to “Unit” in “Connectable Devices.” Pages 23-24: Information on 1: N NT link added. Page 29: “1694” corrected to ”1699” in “Unit No. 7” row of table on right. Page 31: “RS-422” changed to “RS-422A” in “Connections.” Page 33: Information on NT link changed. Pages 41-42: Information about high-speed NT link added. Page 50: Information on NT link removed from “Note 4.” Page 97: “1694” corrected to ”1699” in “Unit No. 7” row. Page 118: “Note 3” removed from bottom right box in table. Information on RS/CS flow added. Page 138: Note added. Page 151: Information on D32001 added. Information on high-speed NT link added. Page 154: Information on baud rate and note added. Page 163: “Execution error” changed to “syntax error” in table. Page 171: Information added to “cause” column. Page 347, 348, 349, 350, 352, 353, 358: “Negative sign” information changed. 489 ">
Download
Advertisement
Key features
Inner Board and CPU Bus Unit
Two RS-232C ports
Supports Host Link, Protocol Macros, 1:N NT Links
Loopback test
Connects to host computers, programming devices, external devices, PTs
Simple installation and wiring
Enhanced communications capabilities for CS1 series PCs
Frequently asked questions
These units support Host Link, Protocol Macros, 1:N NT Links, and loopback test.
They can be connected to host computers, programming devices, general-purpose external devices, and Programmable Terminals.
Each unit provides two RS-232C ports.
You can select the communication mode using the settings in the CPU Unit.
The loopback test allows you to verify the functionality of the serial communication ports.