SIKA K32 MINI-PROGRAMMER Controller User manual
광고
광고
K32
CONTROLLER AND
MINI-PROGRAMMER
Quick guide
1. OUTLINE DIMENSIONS (mm) … … …
78 5,5 11,5
This action allows you to put the instruent in a defined con-dition (in the same condition it was at the first power up).
The default data are the typical values loaded in the instrument prior to shipment from factory.
To load the factory default parameter set, proceed as follows:
1) Press the P button for more than 5 seconds
2) The upper display will show “PASS” and the lower display “0”.
3) By UP and DOWN buttons set the value -481.
4) Push P button.
5)The instrument will turn OFF all LEDs then it will show “dFLt” messages and than it turn ON all LEDs of the display for 2 seconds and than it will restart as for a new power up.
The procedure is complete.
6. OPERATIVE MODES ……… …… ...
6.4.1 - Keyboard function when the instrument is in Auto mode
KEY U: It will perform the action programmed by [116] uSrb (U button function during RUN TIME) parameter.
KEY P: It allows entry into parameter modification procedures.
KEY UP: It allows you to start the “Direct set point modification” function (see below).
KEY DOWN: it allows you to display the “additional informations” (see below).
Parameter Description Range
4 SSc
5 FSc
6 unit
7 FiL
8 inE
Initial scale readout
Final scale readout
Engineering unit (E.U.)
Digital filter on the measured value
Selection of the Sensor
Out of
Range type that enables the safety output value
-1999 ÷ FSC (E.U.)
SSc ÷ 9999 (E.U.)
°c or °F
0 ( oFF) ÷ 20.0 (s) or = Over range ur = Under range our = Over e Under
6.4.2 Direct set point modification
This function allows to modify rapidly the set point value selected by
9 oPE Safety
[79] SPAt or to the set point of the segment group currently in
64 progress.
Digital input oFF = No function
OU T 12 V D C
(Max 20 mA)
2 = Alarm acknowledge
The upper display will show the acronym of the selected set point (e.g.
SP2) and the lower display will show its value. ext.
gen.
71 set point of the group currently in use.
5 = HEAt with SP1 and
2) By UP and DOWN buttons, assign to this parameter the desired
2. CONNECTION DIAGRAM … …… …
3) Do not push any button for more than 5 second or push the P button. In both cases the instrument memorize the new value and come back to the “standard display”.
0..50/60 mV, 0..1 V
NOTE: If the selected set point has not been promoted to the Operator
6 = Timer run/hold/reset
7 = Timer run
8 = Timer reset
9 = Timer run/hold
0/1..5 V , 0/2..10 V value.
10 = Program run
0/4..20 mA ACTIVE level, the instrument allows you to see the value but not to modify it.
CooL with “SP2”
11 = Program reset
12 = Program hold
6.4.3 - Additional informations
4..20 mA
4 = Stand by mode
13 = Program run/hold
ACTIVE
NOTE: when the programmer is running, the instrument will show the
This instrument is able to show you some additional informations that can help you to manage your system. measured value
14 = Program run/reset
15 = Manual mode
4..20 mA
PASSIVE
(2 wires )
1) When the instrument is showing the “standard display” push UP
3 = Hold of the button. The display will show “H” or “c” followed by a number. This
16 = Sequential set point selection
DIG DIG
1) Push DOWN button. value is the current power output applied to the process. The “H” show
PTC RS485
1 = Alarm Reset
17 = SP1 / SP2 select.
NTC
In1 In2
The instrument is showing the “standard display”. you that the action is a Heating action while the “c” show you that the
10 diF1
18 = Set point Binary
Pt100
B G N D A action is a Cooling action.
-100 ÷ 100 (%) selection
TC/mV 2) Push UP button again. When the programmer is running the
19 = Digital inputs in
1 2 3 4 5 6 7 8 9 10 11 12 instrument will show the segment currently performed and the Event parallel to the UP and
INPUT status as shown below: output value
1 function
Down keys
Relays OUT1,2: 8A-AC1 (3A-AC3) / 250 V SSR: 20 mA / 10 VDC where the first figure can be “r” for a ramp or “S” for a soak, the next
SSR
RELAYS
SUPPLY C
13 14 15 16 17 18 19
SUPPLY O U T 4
N O C
O U T 3
N O C
2 0
NC
O U T 2
21
N O C
22 23
NC
O U T 1
24
N O
11 diF2 Digital input
2 function oFF = No function
1 = Alarm Reset
2 = Alarm acknowledge
(ACK)
PLS. NOTE : digit show the number of the segment (ex. S3 indicates stasis 3) and the two less significant digits show you the status of the two event
(LSD is the Event 2).
3) Push UP button again. When the programmer is running the instrument will show the theoretical remaining time to the end of the
3 = Hold of the measured value
4 = Stand by mode
THE COMPLETE MANUAL IS AVAILABLE FREE OF CHARGE AT www.SIKA.it
2.1 - MOUNTING REQUIREMENTS
This instrument is intended for permanent installation, for indoor use only, in an electrical panel which encloses the rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1) it should be easily accessible
2) there is minimum vibrations and no impact
3) there are no corrosive gases
4) there are no water or other fluid (i.e. condensation)
5) the ambient temperature is in accordance with the operative temperature (from 0 to 50 °C)
6) the relative humidity is in accordance with the instrument specifications ( 20% to 85 %)
The instrument can be mounted on panel with a maximum thick of 15 mm. When the maximum front protection (IP65) is desired, the optional gasket must be monted.
2.2 - GENERAL NOTES ABOUT INPUT WIRING program preceded by a P letter:
4) Push UP button again. When the wattmeter function is running the instrument will show “U” followed by the measured energy.
Note: The energy calculation will be in accordance with the [123]
Co.tY parameter setting.
5) Push UP button again. When the “Worked time count” is running the instrument will show “d” for days or “h” for hours followed by the measured time.
6) Push UP button again. The instrument will come back to the
“standard display”.
NOTE: The additional information visualization is subject to a time out. of 10 seconds.
7 . ERROR MESSAGGES ……… …
7.1 - OUT OF RANGE SIGNALS
The display shows the OVER-RANGE and UNDER-RANGE conditions with the following indications:
5 = HEAt with SP1 and
CooL with “SP2”
6 = Timer run/hold/reset
7 = Timer run
8 = Timer reset
9 = Timer run/hold
10 = Program run
11 = Program reset
12 = Program hold
13 = Program run/hold
14 = Program run/reset
15 = Manual mode
16 = Sequential set point selection
17 = SP1 / SP2 selection
18 = Set point Binary selection
19 = Digital inputs in parallel to the UP and
Down keys
Out group (parameters relative to the outputs)
1) Don’t run input wires together with power cables.
2) External components (like zener barriers, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents.
3) When a shielded cable is used, it should be connected at one point only.
4) Pay attention to the line resistance; a high line resistance may cause measurement errors.
5) To avoid electrical shock, connect power line at last.
6) For supply connections use No 16 AWG or larger wires rated for at last 75 °C.
7)Use copper conductors only.
8) Before connecting the instrument to the power line, make sure that line voltage is equal to the voltage shown on the identification label.
9) The power supply input is NOT fuse protected. Please, provide a T type 1A, 250 V fuse externally.
4. CONFIGURATION PROCEDURE ….
4.3. - HOW TO ENTER INTO THE CONFIGURATION MODE
1) Push the P button for more than 3 seconds.
The upper display will show 0 and the lower display “PASS”.
2) Using UP and/or DOWN buttons set the programmed password.
NOTES: a) The factory default password for configuration parameters is 30. b) All parameter modification are protected by a time out. If no button is pressed for more than 10 second the instrument return automatically back to the Standard display, the new value of the last selected parameter is lost and the parameter modification procedure is closed.
When you desire to remove the time out (e.g. for the first configuration of an instrument) you can use a password equal to 1000 plus the programmed password (e.g. 1000 + 30 [default] = 1030).
It is always possible to end manually the parameter configuration procedure (see the next paragraph). c) During parameter modification the instrument continue to perform the control.
In certain conditions, when a configuration change can produce a heavy bump to the process, it is advisable to temporarily stop the controller from controlling during the programming procedure (its control output will be Off)
A password equal to 2000 + the programmed value (e.g. 2000 + 30 =
2030).
The control will restart automatically when the configuration procedure will be manually closed.
3) Push the P button
If the password is correct the display will show the acronym of the first parameter group preceded by the symbol .
In other words the display will show
The instrument is in configuration mode.
.
4.4. - HOW TO EXIT FROM THE CONFIGURATION MODE
Push U button for more than 5 seconds.
The instrument will come back to the “standard display”.
4.5. - KEYBOARD FUNCTION DURING PARAMETER
MODIFICATION
KEY U : A short press allows you to exit from the current parameter group and select a new parameter group.
A long press allows you to close the configuration parameter procedure (the instrument will come back to the “standard display”).
KEY P : When the display is showing a group, It allows you to enter in the selected group.
When the display is showing a parameter, it allows you to memorize the selected value and to go to the next parameter within the same group.
KEY UP : It allows you to increase the value of the selected parameter.
KEY DOWN : It allows you to decrease the value of the selected parameter.
NOTE: The group selection is cyclic as well as the selection of the parameters in a group.
4.6. - FACTORY RESET - DEFAULT PARAMETERS LOADING
PROCEDURE
Sometime, e.g. when you re-configure an instrument previously used for other works or from other people or when you have made too many errors during configuration and you decided to re-configure the instrument, it is possible to restore the factory configuration.
Over-range Under-range
The sensor break will be signalled as an out of range :
NOTE: When an over-range or an under-range is detected, the alarms operate as in presence of the maximum or the minimum measurable value respectively.
To check the out of span Error condition, proceed as follows:
1) Check the input signal source and the connecting line.
2) Make sure that the input signal is in accordance with the instrument configuration.
Otherwise, modify the input configuration (see section 4).
3) If no error is detected, send the instrument to your supplier to be checked.
7.2 - LIST OF POSSIBLE ERRORS
ErAT - Fast Auto-tune can’t start. The measure value is too close to the set point. Push the P button in order to delete the error message.
NoAt - Auto-tune not finished within 12 hours.
ErEP- Possible problem of the instrument memory. The messages desappears automatically. When the error continues, send the instrument to your supplier.
8. NOTE GENERALI …… … …………… …..
8.1 - PROPER USE
Every possible use not described in the complete manual
(www.SIKA.it) must be considered as a improper use.
This instrument is in compliance with EN 61010-1 “Safety requirements for electrical equipment for measurement, control and laboratory use”; for this reason it coud not be used as a safety equipment.
Whenever a failure or a malfunction of the control device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional safety devices.
SIKA GmbH and its legal representatives do not assume any responsibility for any damage to people, things or animals deriving from violation, wrong or improper use or in any case not in compliance with the instrument’s features.
8.2 - GUARANTEE AND REPAIRS
This product is under warranty against manufacturing defects or faulty materials that are found within 12 months from delivery date.
The guarantee is limited to repairs or to the replacement of the instrument.
The tampering of the instrument or an improper use of the product will bring about the immediate withdrawal of the warranty’s effects.
In the event of a faulty instrument, either within the period of warrantee, or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company.
The faulty product must be shipped to SIKA with a detailed description of the faults found, without any fees or charge for SIKA, except in the event of alternative agreements.
Before supplying tension to the instrument, make sure that it is perfectly dry.
PARAMETERS TABLE … … ………… …..
InP group (parameters relative to the inputs)
Parameter Description Range
1 HcFG It shows the current hw
2 SEnS Sensor
TC, Pt100 input
TC, PTC,
NTC input
I input
V input
3 dP Decimal fig.
TC/RTD - TC/PTC -
Current - Volt
J, crAL, S , r, t, ir.J, ir.cA, Pt1, 0.50 (mV),
0.60 (mV),12.60 (mV)
J, crAL, S , r, t, Ir.J,
Ir.cA, Ptc, ntc, 0.50
(mV), 0.60 (mV), 12.60
(mV)
0.20 (mA), 4.20 (mA)
0.5(V), 1.5(V), 0.10(V),
2.10(V),0.1 (V)
0÷3
Def.
Acc. hw
J
Ptc
4.20
0.10
0
Vis.
Promo
Unvis
A-4
A-5
Parameter Description Range
12 o1F Out 1 function
13 o1AL Alarms linked up with the out
1
14 o1Ac Out 1 action
15 o2F Out 2 function
16 o2AL Alarms linked up with the out
2
NonE = Not used
H.rEG = Heating output c.rEG = Cooling output
AL = Alarm output t.out = Timer output t.HoF = Timer out -OFF in hold
P.End = Program end
P.HLd = Program hold
P. uit = Program wait
P.run = Program run
P.Et1 = Progr. Event 1
P.Et2 = Progr. Event 2 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure bo.PF = Out-of-range, burn out and Power failure diF.1 = The output repeats the digital input
1 status diF.2 = The output repeats the digital input
2 status
St.bY = Stand by status from 0 to 31
+1 = AL 1, +2 = AL 2,
+4 = AL 3, +8 = Loop break alarm, + 16 =
Sensor break (burn out) dir = Direct action rEU = Reverse action dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
NonE = Not used
H.rEG = Heating output c.rEG = Cooling output
AL = Alarm output t.out = Timer output t.HoF = Timer out -OFF in hold
P.End = Program end
P.HLd = Program hold
P. uit = Program wait
P.run = Program run
P.Et1 = Progr. Event 1
P.Et2 = Progr. Event 2 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure bo.PF = Out-of-range, burn out and Power failure indicator diF.1 = The output repeats the digital input
1 status diF.2 = The output repeats the digital input
2 status
St.bY = Stand by status from 0 to 31
+1 = AL 1, +2 = AL 2
+4 = AL 3, +8 = Loop break alarm, + 16 =
Sensor break (burn out)
17 o2Ac Out 2 action dir = Direct action rEU = Reverse action
Def.
-
1999
9999
0 =
°c
1.0 our
0 nonE nonE
Def. dir
Vis.
Promo
A-6
A-7
A-8
C-0
C-0
C-0
A-13
A-14
Vis.
Promo
H.reg A-16
AL1 A-17 dir
AL
C-0
A-19
AL1 A-20
C-0
Parameter Description Range Def.
Vis.
Promo dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
18 o3F Out 3 function
19 o3AL Alarms linked up with the out
3
NonE = Not used
H.rEG = Heating output c.rEG = Cooling output
AL = Alarm output t.out = Timer output t.HoF = Timer out -OFF in hold
P.End = Program end
P.HLd = Program hold
P. uit = Program wait
P.run = Program run
P.Et1=Program Event 1
P.Et2=Program Event 2 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure bo.PF = Out-of-range, burn out and Power failure indicator diF.1 = The output repeats the digital input
1 status diF.2 = The output repeats the digital input
2 status
St.bY = Stand by status
AL from 0 to 31
+1 = AL 1, +2 = AL 2
+4 = AL 3, +8 = Loop break alarm, + 16 =
Sensor break (burn out)
AL2
20 o3Ac Out 3 action dir = Direct action rEU = Reverse action dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
21 o4F Out 4 function dir
NonE = Not used
H.rEG = Heating output c.rEG = Cooling output
AL = Alarm output t.out = Timer output t.HoF = Timer out -OFF in hold
P.End = Program end r
P.HLd = Program hold
P. uit = Program wait
P.run = Program run
P.Et1=Program Event 1
P.Et2=Program Event 2 or.bo = Out-of-range or burn out indicator
P.FAL = Power failure bo.PF = Out-of-range, burn out and Power failure indicator diF.1 = The output repeats the digital input
1 status diF.2 = The output repeats the digital input
2 status
St.bY = Stand by status indicator
AL
22 o4AL Alarms linked up with the out
4 from 0 to 31
+1 = AL 1, +2 = AL 2
+4 = AL 3, +8 = Loop break alarm, + 16 =
Sensor break (burn out)
AL2
A-22
A-23
C-0
A-24
A-25
23 o4Ac Out 4 action dir = Direct action rEU = Reverse action dir.r = Direct with reversed LED
ReU.r = Reverse with reversed LED
AL1 group (parameters relative to AL1 - alarm 1) dir C-0
Parameter Descript. Range Def.
Vis.
Promo
24 AL1t Alarm 1 type nonE = Not used
LoAb = Absolute low
HiAb = Absolute high
LHAb = Absolute band
SE.br =Sensor break
LodE = Deviation low (relative)
HidE = Deviation high (relative)
LHdE = Relative band
LoAb A-47
25 Ab1 Alarm 1 function
From 0 to 15
+1 = Not active at power up
+2 = Latched alarm
(manual reset)
+4 = Acknow. alarm
+8 = Relative alarm not active at SP change
0 C-0
26 AL1L - For High and low alarms, it is the low limit of the AL1 threshold - For band alarm, it is low alarm threshold
From -1999 to AL1H
( E.U.)
-
1999
A-48
9999 A-49 27 AL1H - For High and low alarms, it is the high limit of the AL1 threshold - For band alarm, it is high alarm threshold
From AL1L to 9999
( E.U.)
28 AL1 AL1 threshold From AL1L to AL1H
(E.U.)
0 A-50
29 HAL1 AL1 hysteresis From 1 to.9999 E.U. 1
30 AL1d AL1 delay From 0(oFF) to 9999
(s) oFF
A-51
C-0
31 AL1o Alarm 1 enabling during Standby mode
0 = Never
1 = During stand by
2 = During overrang and underrange
3 = During overrange, underrange and stand-by
No C-0
AL2 group (parameters relative to AL2 - alarm 2)
Parameter Descript. Range Def.
Vis.
Promo
1
Parameter Descript. Range Def.
Vis.
Promo
32 AL2t Alarm 2 type nonE = Not used
LoAb = Absolute low
HiAb = Absolute high
LHAb = Absolute band
SE.br = Sensor break
LodE = Deviation low
(relative)
HiAb A-54
33 Ab2 Alarm 2 function
From 0 to 15
+1 = Not active at power up
+2 = Latched alarm
(manual reset)
+4 = Acknowledg. alarm
+8 = Relative alarm not active at SP change
0 C-0
-
1999
A-56 34 AL2L - For High and low alarms, it is the low limit of the AL2 threshold - For band alarm, it is low alarm threshold
From -1999 to AL2H
(E.U.)
35 AL2H - For High and low alarms, it is the high limit of the AL2 threshold - For band alarm, it is high alarm threshold
From AL2L to 9999
(E.U.)
36 AL2 AL2 threshold From AL2L to AL2H
(E.U.)
37 HAL2 AL2 hysteresis From 1 to 9999
(E.U.)
38 AL2d AL2 delay From 0 (oFF) to
9999 (s)
39 AL2o Alarm 2 enabling
0 = Never
1 = During stand by during Standby mode
2 = During overrang and underrange
3 = During overrange, underrange and stand-by
AL3 group (parameters relative to AL3 - alarm 3)
Parameter Descript.
40 AL3t Alarm 3 type
41 Ab3 Alarm 3 function
9999 A-57
0
1 oFF C-0 no
A-58
A-59
C-0
Range nonE = Not used
LoAb = Absolute low
HiAb = Absolute high
LHAb = Absolute band
SE.br = Sensor breack
LodE = Deviation low
(relative)
HidE = Deviation high
(relative)
LHdE = Relative band
From 0 to 15
+1 = Not active at power up
+2 = Latched alarm
(manual reset)
+4 = Acknowled. alarm
+8 = Relative alarm not active at SP change
0
Def.
Vis.
Promo nonE C-0
C-0
-
1999
C-0 42 AL3L - For High and low alarms, it is the low limit of the AL3 threshold -
For band alarm, it is low alarm threshold
From -1999 to AL2H
(E.U.)
43 AL3H - For High and low alarms, it is the high limit of the
AL3 threshold -
For band alarm, it is high alarm threshold
From AL3L to 9999
(E.U.)
9999 C-0
44 AL3 AL3 threshold
45 HAL3 AL3 hysteresis
From AL3L to AL2H
(E.U.)
From 1 to 9999 (E.U.)
0
1
C-0
C-0
46 AL3d AL3 delay From 0 (oFF) to 9999 s oFF C-0
47 AL3o Alarm 3 0 = Never enabling during
Stand-by mode
1 = During stand by
2 = During overrange and underrange
3 = During overrange, no C-0 underrange and stand by
LbA group (parameters relative to the Loop Break Alarm)
Parameter Description Range Def.
Vis.
Promo
48 LbAt LBA time From 0 (oFF) to
9999 (s) oFF C-0
49 LbSt Delta measure used by LBA during Soft start
From 0 (oFF) to
9999 ( E.U.)
10 C-0
50 LbAS Delta measure used by LBA
From 1 to 9999
( E.U.)
51 LbcA Condition for LBA enabling uP = Active when
Pout = 100% dn = Active when
Pout = -100% both = Active in both cases
REG group (parameters relative to the control)
Parameter Description
52 cont Control type
20 C-0 both C-0
Range Def.
Vis.
Promo
A-25 Pid = PID (heat and/or cool)
On.FA = ON/OFF asymmetric hysteresis
On.FS = ON/OFF symmetric hysteresis nr = Heat/Cool
ON/OFF control with neutral zone
Pid
Parameter Description Range Def.
Vis.
Promo
53 Auto Autotuning selection
54 Aut.r Manual start of the
Autotuning
55 SELF Self tuning enabling
56 HSEt Hysteresis of the ON/OFF control
57 cPdt Time for compressor protection
58 Pb
59 int
-4 = Oscillating auto-tune with automatic restart at power up and after all SP change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating auto-tune with auto-matic start at the first power up only
-1 = Oscillating auto-tune with auto-matic restart at every power up
0 = Not used
1 = Fast auto tuning with automatic restart at every power up
2 = Fast autotune with automatic start at the first power up only
3 = FAST autotune with manual start
4 = FAST autotune with automatic restart at power up and after a SP change oFF = Not active on = Active
2 C-0 oFF A-26
YES = Active no = Not active
From 0 to 9999
( E.U.)
From 0 (oFF) to
9999 (s)
Proportional band
From 0 to 9999
( E.U.)
Integral time From 0 (oFF) to
9999 (s) no
1
C-0
A-27 oFF C-0
50 A-28
200 A-29
60 dEr Derivative time
61 Fuoc Fuzzy overshoot control
62 H.Act Heating
63 tcrH
64 PrAt Power ratio between heating and cooling action
65 c.Act Cooling output actuator
From 0.01 to
99.99
SSr = SSR rELY = relay
SLou = slow actuators
66 tcrc
67 rS output actuator
Heating output cycle time
Cooling output cycle time
Manual reset
(Integral preload)
From 0 (oFF) to
9999 (s)
From 0.00 to 2.00
SSr = SSR rELY = relay
SLou = slow actuators
From 0.1 to 130.0
(s)
From 0.1 to 130.0
(s)
From -100.0 to
100.0 (%)
50
0.50
SSr A-32
20.0 C-0
1.00 A-34
SSr A-35
20.0 C-0
0.0
A-30
A-31
C-0
68 od
69 St.P
70 SSt
Delay at power up
From 0.00 (oFF) to 99.59 (hh.mm)
Maximum power output used during soft start
From -100 to 100
(%)
Soft start time From 0.00 (oFF) to 8.00 (inF)
(hh.mm)
71 SStH Threshold for soft start disabling
From -1999 to
9999 (E.U.)
SP group (parameters relative to the Set Point) oFF C-0
0
999
9
C-0 oFF C-0
C-0
Parameter Description Range Def.
Vis.
Promo
72 nSP Number of used SP
From 1 to 4 1 A-38
73 SPLL Minimum set point value
From -1999 to SPHL -
1999
A-39
74 SPHL Maximum set point value
75 SP 1 Set point 1
From SPLL to 9999
From SPLL to SPLH
9999 A-40
0 O-41
76 SP 2 Set point 2 From SPLL to SPLH 0
77 SP 3 Set point 3 From SPLL to SPLH 0
O-42
O-43
78 SP 4 Set point 4 From SPLL to SPLH 0 O-44
79 SPAt Selection of the active
SP
80 SP.rt Remote set point type
From 1 ( SP 1) to nSP
RSP = The value coming from serial link is used as remote set point trin = The value will be added to the local set point selected by
SPAt and the sum becomes the operative set point
PErc = The value will be scaled on the input range and this value will be used as remote set point
1 trin
O-45
C-0
81 SP.Lr Local/remote
SP selection
Loc = local rEn = remote
Loc C-0
Parameter
82 SP.u
Description
Rate of rise for
POSITIVE
SP change
Range
From 0.01 to 100.00
( inF) E.U per minute
Def. inF
Vis.
Promo
C-0
83 SP.d Rate of rise for
NEGATIVE
SP change
0.01 ÷ 100.00 ( inF)
E.U per minute
Tin group (parameters relative to the timer)
Parameter Descript.
84 tr.F Independent timer function inF C-0
Range Def.
Vis.
Promo
NonE = Not used i.d.A = Delayed start timer i.uP.d = Delayed start at power up i.d.d = Feed-through timer i.P.L = Asymmetrical oscillator with start in
OFF i.L.P = Asymmetrical oscillator with start in
ON nonE A-62
85 tr.u Timer unit A-63
86 tr.t1
87 tr.t2
Time 1
Time 2 hh.nn = Hours and minutes nn.SS = Minutes and seconds
SSS.d = Second and tenth of seconds nn.S
S
1.00 From 00.01 to 99.59 when tr.u < 2
From 000.1 to 995.9 when tr.u = 2
When tr.u < 2:
From 00.00 (oFF) to
99.59 (inF)
When tr.u = 2:
From 000.0 (oFF) to
995.9 (inF)
1.00
A-647
A-65
88 tr.St Timer status rES = timer reset run = timer run
HoLd = timer hold
PrG group (parameters relative to the programmer) rES
Parameter
89 Pr.F
90 Pr.u
Descript.
Program action at power up
C-0
Range Def.
Vis.
Promo nonE = Not used
S.uP.d = Start at power up with 1st step in stand-by
S.uP.S = Start at power up u.diG = Start at
Run command detection only u.dG.d = Start at
Run command with
1st step in stand-by hh.nn = Hrs + min nn.SS = Min + sec nonE A-67 hh.nn A-68
91 Pr.E
Engineering unit of the soak
Instrument behaviour at the end of the program execution
92 Pr.Et Time of the end program indication cnt = continue
SPAt = go to the
SP selected by
SPAt
St.by = go to standby mode
From 0.00 (oFF) to
100.00 (inF) min. and sec.
SPAt A-71 oFF A-72
93 Pr.S1 SP of the first soak
From SPLL to
SPHL
0 A-73
94 Pr.G1 Gradient of the first ramp
From 0.1 to 1000.0
(inF= Step transfer)
E.U./minute inF A-74
From 0.00 to 99.59 0.10 A-75 95 Pr.t1 Time of the first soak
96 Pr.b1 Wait band of the first soak
97 Pr.E1 Events of the first group
From 0 (oFF) to
9999 (E.U.)
From 00.00 to
11.11
oFF A-76
00.00 C-0
98 Pr.S2 SP of the second soak
99 Pr.G2 Gradient of the second ramp
100 Pr.t2 Time of the second soak
OFF or from SPLL to SPHL
0 A-78
From 0.1 to 1000.0
(inF= Step transfer)
E.U/minute inF A-79
From 0.00 to 99.59 0.10 A-80
101 Pr.b2 Wait band of the second soak
From 0 (oFF) to
9999 (E.U.)
102 Pr.E2 Events of the second group
From 00.00 to
11.11
103 Pr.S3 SP of the third soak
OFF or from SPLL to SPHL oFF
00.00 C-0
0
A-81
A-83
104 Pr.G3 Gradient of the third ramp
105 Pr.t3 Time of the third soak
From 0.1 to 1000.0
(inF= Step transfer)
E.U./minute
106 Pr.b3 Wait band of the third soak
From 0 (oFF) to
9999 (E.U.) inF
From 0.00 to 99.59 0.10 A-85 oFF
A-84
A-86
107 Pr.E3 Events of the third group
108 Pr.S4 SP of the fourth soak
109 Pr.G4 Gradient of the fourth ramp
110 Pr.t4 Time of the fourth soak
111 Pr.b4 Wait band of the fourth soak
112 Pr.E4 Events of the fourth group
113 Pr.St Program status
From 00.00 to
11.11
00.00 C-0
OFF or from SPLL to SPHL
0 A-88
From 0.1 to 1000.0
(inF= Step transfer) inF A-89
E.U./minute
From 0.00 to 99.59 0.10 A-90
From 0 (oFF) to
9999 (E.U.)
From 00.00 to
11.11
rES = Prg reset run = Prg start
HoLd = Prg hold oFF
00.00 C-0 rES
A-91
C-0
Pan group (parameters relative to the operator interface)
Parameter Description Range Def.
Vis.
Promo
A-93 114 PAS2 Password level
2
From 0 (oFF) to
999
115 PAS3 Password level
3
From 3 to 999
20
30 C-0
116 uSrb U button function during run time nonE = Not used tunE = Starts auto tuning functions oPLo = Manual mode (OPLO)
AAc = Alarm reset
ASi = Alarm acknowledge chSP = Sequential set point selection
St.by = Stand-by mode
Str.t =
Run/hold/reset timer
P.run = Prgr start
P.rES = prgr reset
P.r.H.r =
Run/hold/reset program
117 diSP Display management nonE A-94
118 AdE Bargraph deviation
119 FiLd Filter on the displayed value nonE = Standard display
Pou = Power output
SPF = Final SP
Spo = Operative set point
AL1 = Alarm 1 threshold
AL2 = Alarm 2 threshold
AL3 = Alarm 3 threshold
Pr.tu = Prgr time up
Pr.td = Prgr time down
P.t.tu = Prgr total time up
P.t.td = Prgr total time down ti.uP = Timer time up ti.du = Timer time down
PErc = % of the power output used during soft start nonE A-95
2 A-96 From 0 (oFF) to
9999
From 0 .0(oFF) to
20.0 oFF C-0
120 dSPu Status of the instrument at power up
AS.Pr = Starts in the same way it was prior to the power down
Auto = Starts in
Auto mode oP.0 = Starts in manual mode with power output = 0
St.bY = Starts in stand-by mode
121 oPr.E
Operative mode enabling
ALL = All
Au.oP = Auto or manual (oPLo) only
Au.Sb = Auto and
Stand by only
122 oPEr Operative mode selection
Auto = Automatic oPLo = Manual
St.by = Stand-by
AS.Pr C-0
ALL C-0
Auto O-1
Ser group (parameters relative to the serial interface)
Parameter Description Range Def.
Vis.
Promo
123 Add Address 0 (oFF) ÷ 254 1 C-0
9600 C-0 124 bAu d
125
Baud rate trSP Selection of the value to be retransmitted
(Master)
1200 – 2400 –
9600 - 19.2 - 38.4 nonE = Not used rSP = Operative
SP
PErc = Current power output (%) nonE C-0
Con group (parameters relative to the consumption) Wattmeter
Parameter Description Range Def.
Vis.
Promo
126 co.ty
Measurement type nonE A-97 oFF = Not used
1 = Instantaneous power (kW)
2 = Power consumption
(kW/h)
3 = Energy used during prgr execut.
4 = Total worked days with threshold
5 = Total worked hrs with threshold
From 1 to 999
(Volt)
230 A-98 127 UoLt Nominal voltage of the load
128 cur Nominal current of the load
129 h.Job
Threshold of the worked hours/days
From 1 to 999 (A)
From 0( oFF) to
9999
10 oFF
A-99
A-100
CAL. group (parameters relative to the user Calibration)
Parameter
130 A.L.P
Description
Adjust low
Point
Range
From -1999 to
AH.P-10 (E.U.)
Def.
Vis.
Promo
0 A-9
131 A.L.o
Adjust low
Offset
132 A.H.P
Adjust High
Point
From -300 to 300
(E.U.)
From A.L.P +10
÷to 9999 (E.U.)
0 A-10
9999 A-11
133 A.H.o
Adjust High
Offset
From -300 to 300
(E.U.)
0 A-12
2