Lennox EL195 Gas Furnace Installation Manual

Add to My manuals
52 Pages

advertisement

Lennox EL195 Gas Furnace Installation Manual | Manualzz
INSTALLATION
INSTRUCTIONS
EL195DF
2011 Lennox Industries Inc.
Dallas, Texas, USA
ELITE® SERIES GAS FURNACE
DOWNFLOW AIR DISCHARGE
506594−01
02/2011
Supersedes 01/2011
Litho U.S.A.
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be ignored.
When you see this symbol on labels or in manuals, be alert
to the potential for personal injury or death.
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
WARNING
DOWNFLOW
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
AIR FLOW
Table of Contents
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EL195DF Parts Arrangement . . . . . . . . . . . . . . . . . . . . .
EL195DF Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . .
Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . .
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Use of Furnace as a Construction Heater . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion, Dilution and Ventilation Air . . . . . . . . . . . .
Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . .
Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . .
Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
3
4
4
4
5
6
6
9
12
12
12
14
14
506594−01
02/11
*2P0211*
Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . .
Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Testing Non Direct Appliances for Proper Air . . . . . . . .
Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . .
Blower Motor Performance . . . . . . . . . . . . . . . . . . . . . . .
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Planned Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Integrated Control Diagnostic Codes . . . . . . . . . . . . . . .
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 1
15
30
32
36
38
38
38
39
40
41
42
44
44
45
49
50
*P506594-01*
EL195DF Unit Dimensions − inches (mm)
9/16
(14)
COMBUSTION
AIR INTAKE
RETURN AIR
OPENING
B
EXHAUST AIR
OUTLET
2−1/16 (52)
5
(127)
27−3/4
(705)
19−7/16
(494)
9/16
(14)
B
ELECTRICAL INLET
(Either Side)
2 (51)
Either Side
CONDENSATE
TRAP CONNECTION
(Either Side)
GAS PIPING INLET
(Either Side)
9−1/8 (232) Right
6−9/16 (167) Left
C
Supply
Air
6−7/16 (163)
Either Side
9 (229)
Either Side
19−1/4 Supply
(489)
Air
3/4
(19)
FRONT VIEW
Model No.
9/16
(14)
FLOW
33
(838)
3/4
(19)
TOP VIEW
1−1/2 (38)
Front Panel
A
AIR
9/16
(14)
2−1/4
(57)
3/4
(19)
SIDE VIEW
A
B
C
in.
mm
in.
mm
in.
mm
EL195DF045P36B
EL195DF070P48B
17−1/2
446
16−3/8
416
16
406
EL195DF090P60C
EL195DF110P60C
21
533
19−7/8
505
19−1/2
495
Page 2
EL195DF Parts Arrangement
BLOWER MOTOR
(hidden)
CONTROL BOX
(Includes integrated control,
transformer and door switch)
BAG ASSEMBLY
(shipping location)
COMBUSTION
AIR INDUCER
BLOWER DECK
DuralokPlusTM
HEAT EXCHANGER
ASSEMBLY
OUTER
ACCESS
PANEL
COLD END HEADER BOX
COMBUSTION AIR INDUCER
PRESSURE SWITCH
PRIMARY LIMIT
BURNER BOX ASSEMBLY
(includes sensor, rollout switches and ignitor)
GAS VALVE
FIGURE 1
Page 3
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
EL195DF Gas Furnace
The EL195DF Category IV gas furnace is shipped ready
for installation in the downflow position.
The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications.
The EL195DF can be installed as a Direct Vent or Non−
Direct Vent gas central furnace.
NOTE − In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non−Direct Vent installations, combustion air is taken from
indoors and flue gases are discharged outdoors. See figure
2 for applications involving roof termination.
DIRECT VENT INSTALLATION
COMBUSTION
AIR INTAKE
OUTSIDE OF
HOUSE
NON−DIRECT VENT
INSTALLATION
EXHAUST
OUTLET
The following items may also be ordered separately:
1 − Thermostat
1 − LP/Propane changeover kit
1 − High altitude pressure switch
Safety Information
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal injury or loss of life. Installation and service must
be performed by a licensed professional installer (or
equivalent), service agency or the gas supplier.
EXHAUST
OUTLET
CAUTION
As with any mechanical equipment, personal injury
can result from contact with sharp sheet metal
edges. Be careful when you handle this equipment.
COMBUSTION
AIR INTAKE INSIDE
OF HOUSE
EL195DF
EL195DF
FIGURE 2
Shipping and Packing List
Package 1 of 1 contains
1 − Assembled EL195DF unit
1 − Bag assembly containing the following:
3 − Wire nuts
1 − Snap bushing
1 − Snap plug
1 − Wire tie
1 − Condensate trap
1 − Condensate trap cap
1 − Condensate trap clamp
1 − 2" diameter Air intake screen
DANGER
Danger of explosion.
There are circumstances in which odorant used with
LP/propane gas can lose its scent. In case of a leak,
LP/propane gas will settle close to the floor and may
be difficult to smell. An LP/propane leak detector
should be installed in all LP applications.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
EL195DF units are CSA International certified to ANSI
Z21.47 and CSA 2.3 standards.
Building Codes
In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must
be installed according to the current National Fuel Gas Code
(ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is
available from the following address:
American National Standards Institute, Inc.
11 West 42nd Street
New York, NY 10036
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes
and other applicable local codes.
In order to ensure proper unit operation in non−direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA-B149 standard.
Locations and Clearances
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in figure 10. Accessibility and service clearances must take precedence over fire protection
clearances.
For installation in a residential garage, the furnace must
be installed so that the burner(s) and the ignition source
are located no less than 18 inches (457 mm) above the
floor. The furnace must be located or protected to avoid
physical damage by vehicles. When a furnace is installed
Page 4
in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards.
NOTE − Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature heat
exchanger failure.
This EL195DF furnace must be installed so that its electrical components are protected from water.
Installation in Combination with a Cooling Coil
When this furnace is used with cooling units (figure 3), it
shall be installed in parallel with, or on the upstream side of,
cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other
means to control the flow of air) must adequately prevent
chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full
HEAT or COOL setting.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following address:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
Heating Unit Installed Parallell to Air Handler Unit
NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases
where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb.
The EL195DF furnace may be installed in alcoves, closets,
attics, basements, garages, utility rooms and crawl
spaces.
This furnace design has not been CSA certified for installation in mobile homes, recreational vehicles, or outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of EL195DF units as
a construction heater during any phase of construction.
Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit.
EL195DF units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
• The return air duct must be provided and sealed to the
furnace.
• Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
• Air filters must be installed in the system and must be
maintained during construction.
• Air filters must be replaced upon construction completion.
• The input rate and temperature rise must be set per the
furnace rating plate.
AIR HANDLER
GAS UNIT
• One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the
furnace. Do not connect duct directly to the furnace.
Size the temporary duct following these instructions in
section for Combustion, Dilution and Ventilation Air in a
confined space with air from outside.
Dampers
Dampers
(open during cooling
operation only)
(open during heating
operation only)
• The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction clean−up.
• All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified
according to these installation instructions.
FIGURE 3
Page 5
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
In addition to the requirements outlined previously, the following general recommendations must be considered
when installing a EL195DF furnace:
• Place the furnace as close to the center of the air distribution system as possible. The furnace should also be
located close to the chimney or vent termination point.
• When the furnace is installed in non−direct vent applications, do not install the furnace where drafts might blow
directly into it. This could cause improper combustion
and unsafe operation.
• When the furnace is installed in non−direct vent applications, do not block the furnace combustion air opening
with clothing, boxes, doors, etc. Air is needed for proper
combustion and safe unit operation.
• When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace.
• When the furnace is installed in an unconditioned
space, consider provisions required to prevent freezing
of condensate drain system.
CAUTION
EL195DF unit should not be installed in areas normally subject to freezing temperatures.
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool. Breathing this may cause lung
cancer. (Fiberglass wool is known to the State of California to cause cancer.)
Fiberglass wool may also cause respiratory, skin,
and eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.
Lennox Industries Inc.
P.O. Box 799900
Dallas, TX 75379−9900
Combustion, Dilution & Ventilation Air
WARNING
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result
in safety and performance related problems. Avoid
exposure to the following substances in the combustion air supply:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De−icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside
for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional
air that could be used for combustion out of the house.
Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than
inside pressure) will build to the point that a downdraft
can occur in the furnace vent pipe or chimney. As a result,
combustion gases enter the living space creating a potentially dangerous situation.
In the absence of local codes concerning air for combus−
tion and ventilation, use the guidelines and procedures in
this section to install EL195DF furnaces to ensure efficient and safe operation. You must consider combustion
air needs and requirements for exhaust vents and gas
pip−ing. A portion of this information has been reprinted
with permission from the National Fuel Gas Code (ANSI−
Z223.1/NFPA 54). This reprinted material is not the complete and official position of the ANSI on the referenced
subject, which is represented only by the standard in its
entirety.
In Canada, refer to the CSA B149 installation codes.
If the EL195DF is installed as a Non−Direct Vent Furnace, follow the guidelines in this section.
NOTE − In Non−Direct Vent installations, combustion air
is taken from indoors and flue gases are discharged out−
doors.
CAUTION
Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.
Page 6
All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all
fuel−burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as
the furnace, much more air is required to ensure proper
combustion and to prevent a downdraft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents
and other contaminants which can corrode furnace components.
The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in
an unconfined or a confined space.
dangerous negative pressure condition. Air for combustion
and ventilation can be brought into the confined space either from inside the building or from outside.
Air from Inside
If the confined space that houses the furnace adjoins a
space categorized as unconfined, air can be brought in by
providing two permanent openings between the two
spaces. Each opening must have a minimum free area of 1
square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of
total input rating of all gas−fired equipment in the confined
space. Each opening must be at least 100 square inches
(64516 mm2). One opening shall be within 12 inches (305
mm) of the top of the enclosure and one opening within 12
inches (305 mm) of the bottom. See figure 4.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
ROOF TERMINATED
EXHAUST PIPE
Unconfined Space
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around
the windows and doors, follow the procedures in the air
from outside section.
Confined Space
A confined space is an area with a volume less than 50 cubic
feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com−
bined input rating of all appliances installed in that space. This
definition includes furnace closets or small equipment rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts
which are sealed to the furnace casing and which terminate
outside the space containing the furnace. This is especially
important when the furnace is mounted on a platform in a
confined space such as a closet or small equipment room.
Even a small leak around the base of the unit at the platform
or at the return air duct connection can cause a potentially
Page 7
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
OPENINGS
(To Adjacent
Unconfined
Space)
NOTE − Each opening shall have a free area of at least one square
inch per 1,000 Btu (645mm 2 per .29kW) per hour of the total input
rating of all equipment in the enclosure, but not less than 100 square
inches (64516mm. 2).
FIGURE 4
Air from Outside
If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305mm)
of the top of the enclosure and one within 12" (305mm) of
the bottom. These openings must communicate directly
or by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly
through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2
per 1.17kW) per hour of total input rating of all equipment
in the enclosure. When communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2
per .59kW) per total input rating of all equipment in the enclosure (See figure 5).
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
VENTILATION LOUVERS
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
VENTILATION LOUVERS
(Each end of attic)
OUTLET
AIR
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
INLET
AIR
VENTILATION
LOUVERS
(For unheated
crawl space)
NOTE−The inlet and outlet air openings shall each have a free area
of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
INLET AIR
(Ends 12" above
bottom)
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
NOTE−The inlet and outlet air openings shall each have a free area of
at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 6
FIGURE 5
If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of
the top of the enclosure and one opening within 12 inches
(305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl
or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a
minimum free area of 1 square inch (645 mm2) per 4,000
Btu (1.17 kW) per hour of total input rating of all equipment
in the enclosure. See figures 5 and 6. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645
mm2) per 2,000 Btu (.56 kW) per total input rating of all
equipment in the enclosure. See figure 7.
When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they
connect. The minimum dimension of rectangular air ducts
shall be no less than 3 inches (75 mm). In calculating free
area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protective covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have
20 to 25 percent free area and metal louvers and grilles
will have 60 to 75 percent free area. Louvers and grilles
must be fixed in the open position or interlocked with the
equipment so that they are opened automatically during
equipment operation.
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
INLET AIR
NOTE−Each air duct opening shall have a free area of at least one
square inch per 2,000 Btu (645mm2 per .59kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area
of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 7
Page 8
Installation − Setting Equipment
SETTING EQUIPMENT
Unit must be level side−to−side. Unit may be positioned
from level to 1/2" toward the front to aid in draining.
WARNING
Do not install the furnace on its front, back or in the
horizontal position. See figure 9. Do not connect the
return air ducts to the back of the furnace. Doing so
will adversely affect the operation of the safety control devices, which could result in personal injury or
death.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
condensate trap and drain connections, and installation
and service clearances [24 inches (610 mm) at unit
front]. The unit must be level from side to side. Unit may
be positioned from level to 1/2" toward the front to aid in
draining. See figure 8.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 10.
AIR FLOW
AIR FLOW
UNIT
FRONT
UNIT
FRONT
1/2"
max.
SIDE VIEW
SIDE VIEW
AIR FLOW
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into
living space resulting in personal injury or death.
Front
Back
FRONT VIEW
FIGURE 8
Horizontal
NOTE − Do not install the furnace on its front, back or in the horizontal position
FIGURE 9
Page 9
Installation on Non−Combustible Flooring Figure 11
WARNING
1 − Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply connections, electrical supply, flue and air intake connections
and sufficient installation and servicing clearances.
See table 1 for correct floor opening size.
2 − Flange warm air plenum and lower the plenum into the
opening.
3 − Set the unit over the plenum and seal the plenum to
the unit.
4 − Ensure that the seal is adequate.
Improper installation of the furnace can result in personal injury or death. Combustion and flue products
must never be allowed to enter the return air system
or air in the living space. Use sheet metal screws and
joint tape to seal return air system to furnace.
In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the
return air duct system. The base must provide a
stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc.
For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury
and/or property damage could result.
TABLE 1
NON−COMBUSTIBLE FLOOR OPENING SIZE
Front to Rear
Cabinet Width
The unit may be installed three ways in downflow applications: on non−combustible flooring, on combustible flooring
using an additive base, or on a reverse−flow cooling coil
cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage
will result.
Refer to figure 10 for clearances in downflow applications.
Side to Side
in.
mm
in.
mm
B Cabinet (17.5")
19 − 3/4
502
16 − 5/8
422
C Cabinet (21")
19 − 3/4
502
20−1/8
511
NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See dimension drawing on page 2.
Downflow Application Installation Clearances
FURNACE
Top
Left Side
PROPERLY
SIZED FLOOR
OPENING
Right Side
SUPPLY AIR
PLENUM
Bottom
Top
0
*Front
0
Back
0
Sides
0†
Vent
0
Floor
NC‡
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap and
vent pipe installation.
‡The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor.
FIGURE 10
FIGURE 11
Installation on Combustible Flooring Figure 12
1 − When unit is installed on a combustible floor, a downflow combustible flooring base must be installed between the furnace and the floor. The base must be ordered separately. See table 2 for opening size to cut in
floor.
CAUTION
The furnace and combustible flooring base shall not
be installed directly on carpeting, tile, or other combustible material other than wood flooring.
Page 10
TABLE 2
COMBUSTIBLE FLOORING BASE OPENING SIZE
Cabinet
Width
Catalog
Number
B Cabinet
(17.5")
C Cabinet
(21")
Front to Rear
Side to Side
FURNACE
in.
mm
in.
mm
11M60
22
559
18 − 3/4
476
11M61
22
559
22 − 3/4
578
COOLING COIL
PROPERLY
SIZED FLOOR
OPENING
PLENUM
FURNACE
SUPPLY AIR
PLENUM
PROPERLY
SIZED FLOOR
OPENING
COMBUSTIBLE
FLOORING BASE
FIGURE 13
Return Air Opening −− Downflow Units
Return air may be brought in only through the top opening
of a furnace installed in the downflow position. The following steps should be taken when installing plenum:
1 − Bottom edge of plenum should be flanged with a
hemmed edge (See figure 14 or 15).
FIGURE 12
2 − After opening is cut, set the combustible flooring base
into opening.
3 − Check fiberglass strips on the combustible flooring
base to make sure they are properly glued and positioned.
4 − Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass
strips.
NOTE − Be careful not to damage fiberglass strips.
Check for a tight seal.
5 − Set the furnace over the plenum.
2 − Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 − In all cases, plenum should be secured to top of furnace using sheet metal screws.
4 − Make certain that an adequate seal is made.
PLENUM
(Field Provided)
SEALING STRIP
(Field Provided)
SECURE FROM
OUTSIDE CABINET
ÉÉÉÉ
CABINET
SIDE PANEL
Side View
6 − Ensure that the seal between the furnace and plenum
is adequate.
Installation on Cooling Coil Cabinet Figure 13
NOTE − Downflow combustible flooring kit is not used.
FIGURE 14
PLENUM
(Field Provided)
1 − Refer to reverse−flow coil installation instructions for
correctly sized opening in floor and installation of cabinet.
2 − When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided
with the cooling coil. Secure the furnace to the cabinet.
SECURE FROM
INSIDE CABINET
ÉÉÉÉ
Side View
FIGURE 15
3 − Seal the cabinet and check for air leaks.
Page 11
SEALING STRIP
(Field Provided)
CABINET
SIDE PANEL
Filters
Pipe & Fittings Specifications
This unit is not equipped with a filter or rack. A field−provided filter is required for the unit to operate properly. Table
3 lists recommended minimum filter size.
A filter must be in place whenever the unit is operating.
TABLE 3
Furnace
Cabinet Width
Minimum Filter Size
17−1/2"
16 x 25 x 1 (1)
All pipe, fittings, primer and solvent cement must conform
with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no
lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of
the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Refer to the table 4 below for approved piping and fitting materials.
21"
CAUTION
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. Refer to ACCA Manual
D. This will result in a quiet and low-static system that has
uniform air distribution.
NOTE − This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.5 inches
w.c. Operation at these conditions may result in improper
limit operation.
Supply Air Plenum
If the furnace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must
not allow leaks into the supply air duct system.
Return Air Plenum
NOTE − Return air must not be drawn from a room
where this furnace, or any other gas−fueled appliance
(i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed.
When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating
in a room with negative pressure, the flue products can
be pulled back down the vent pipe and into the room. This
reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This
raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system.
Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to
ensure a tight seal. If a filter is installed, size the return air
duct to fit the filter frame.
Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of
ignition. Do not use excessive amounts of solvent
cement when making joints. Good ventilation should
be maintained to reduce fire hazard and to minimize
breathing of solvent vapors. Avoid contact of cement
with skin and eyes.
TABLE 4
PIPING AND FITTINGS SPECIFICATIONS
Schedule 40 PVC (Pipe)
Schedule 40 PVC (Cellular Core Pipe)
D1785
F891
Schedule 40 PVC (Fittings)
D2466
Schedule 40 CPVC (Pipe)
F441
Schedule 40 CPVC (Fittings)
SDR−21 PVC or SDR−26 PVC (Pipe)
SDR−21 CPVC or SDR−26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
F438
D2241
F442
F628
Schedule 40 ABS (Pipe)
D1527
Schedule 40 ABS (Fittings)
D2468
ABS−DWV (Drain Waste & Vent)
(Pipe & Fittings)
D2661
PVC−DWV (Drain Waste & Vent)
Pipe & Fittings)
D2665
PRIMER & SOLVENT CEMENT
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
ASTM
SPECIFICATION
F656
D2564
F493
D2235
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
D2564, D2235, F493
ABS to PVC or CPVC Transition Solvent
Cement
D3138
CANADA PIPE & FITTING & SOLVENT
CEMENT
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ABS to PVC or CPVC Transition Cement
Page 12
MARKING
ULCS636
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used for
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth
of fitting socket.
IMPORTANT
EL195DF exhaust and intake connections are made
of PVC. Use PVC primer and solvent cement when
using PVC vent pipe. When using ABS vent pipe, use
transitional solvent cement to make connections to
the PVC fittings in the unit.
Canadian Applications Only − Pipe, fittings, primer
and solvent cement used to vent (exhaust) this apUse PVC primer and solvent cement or ABS solvent cement
pliance must be certified to ULC S636 and supplied by a
meeting ASTM specifications, refer to Table 4. As an altersingle manufacturer as part of an approved vent (exnate, use all purpose cement, to bond ABS, PVC, or CPVC
haust) system. In addition, the first three feet of vent
pipe when using fittings and pipe made of the same materipipe from the furnace flue collar must be accessible for
als. Use transition solvent cement when bonding ABS to eiinspection.
ther PVC or CPVC.
TABLE 5
OUTDOOR TERMINATION KITS USAGE
STANDARD
EL195
UNIT
045
070
090
110
VENT
PIPE
DIA.
(in.)
CONCENTRIC
Outdoor
Exhaust
Accelerator
(Dia. X
Length)
Outdoor
Exhaust
Accelerator
(Dia. X
Length)
2" Wall Plate
Kit
3" Wall Plate
Kit
2" Wall
Ring Kit
FlushMount
Kit
1−1/2"
Concentric
Kit
2"
Concentric
Kit
3"
Concentric
Kit
1−1/2" X 12"
2" X 12"
22G44
or 30G28
44J40
or 81J20
15F74
51W11**
71M80
or
44W92
69M29
or
44W92
60L46
or 44W93
2
YES
YES
YES*
YES
YES
YES
2−1/2
YES
YES
YES*
YES
YES
YES
3
YES
YES
YES*
YES
YES
YES
2
YES
YES
YES*
YES
YES
YES
2−1/2
YES
YES
YES*
YES
YES
YES
3
YES
YES
YES*
YES
YES
YES
2
YES
YES
YES
YES
YES
YES
2−1/2
YES
YES
YES
YES
YES
YES
3
YES
YES
YES
YES
YES
YES
3
YES
YES
YES
YES
YES
YES
*Requires field−provided and installed 1−1/2" exhaust accelerator.
** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all EL195DF−045, −070 and −090 installations.
Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149.
The 44W92 Concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the EL195DF045P36B and
EL195DF070P36B furnaces.
Page 13
Venting Practices
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
Piping Suspension Guidelines
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
NOTE − A sheet metal screw may be used to secure
the intake pipe to the connector, if desired. Use a drill
or self tapping screw to make a pilot hole.
DANGER
* See table 4 for allowable pipe.
DANGER OF EXPLOSION!
NOTE − Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Fumes from PVC glue may ignite during system
check. Allow fumes to dissipate for at least 5 minutes
before placing unit into operation.
Wall Thickness Guidelines
24" maximum
3/4" minimum
1 − Measure and cut vent pipe to desired length.
2 − Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
inside
Wall
outside
NOTE − Check the inside of vent pipe thoroughly for
any obstruction that may alter furnace operation.
3 − Clean and dry surfaces to be joined.
4 − Test fit joint and mark depth of fitting on outside of pipe.
FIGURE 16
5 − Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
6 − Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply second coat to end of pipe.
NOTE − Time is critical at this stage. Do not allow primer to dry before applying cement.
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced
by EL193)
If an EL195DF furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked.
Without the heat of the original furnace flue products, the
existing vent pipe is probably oversized for the single water
heater or other appliance. The vent should be checked for
proper draw with the remaining appliance.
NOTE − Assembly should be completed within 20 seconds after last application of cement. Hammer blows
should not be used when inserting pipe.
9 − Handle joints carefully until completely set.
WATER
HEATER
OPENINGS
(To Adjacent
Room)
7 − Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular
core pipe.
8 − After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent.
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
FIGURE 17
1 − In areas where piping penetrates joists or interior
walls, hole must be large enough to allow clearance on
all sides of pipe through center of hole using a hanger.
Page 14
2 − When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining condensate collection trap and lines.
Exhaust Piping (Figures 19 and 20)
Route piping to outside of structure. Continue with installation following instructions given in piping termination section.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end
is even with the top or outlet end of the metal stack.
CAUTION
Use the following steps to correctly size vent pipe diameter.
045, 070,
090 or 110
1
Furnace capacity?
2
Which termination?
3
Which needs
most elbows?
4
How many?
Standard or
Concentric?
See table 5
Intake or
exhaust
The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space.
Vent Piping Guidelines
The EL195DF can be installed as either a Non−Direct
Vent or a Direct Vent gas central furnace.
NOTE − In Non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors.
Intake and exhaust pipe sizing −− Size pipe according to
tables 6 and 7. Table 6 lists the minimum vent pipe lengths
permitted. Table 7 lists the maximum pipe lengths permitted.
TABLE 6
MINIMUM VENT PIPE LENGTHS
EL195DF
MODEL
MIN. VENT LENGTH*
045, 070, 090, 110
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
*Any approved termination may be added to the minimum length listed.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
pipe is sized to optimize the velocity of the exhaust gas as
it exits the termination. Refer to table 8.
In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be
used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications.
IMPORTANT
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze−ups
and may block the terminations.
Page 15
5
Desired pipe size?
6
What is the altitude?
7
Use table 7 to find
max intake or
exhaust pipe length.
2", 2−1/2"
or 3"
FIGURE 18
NOTE − It is acceptable to use any pipe size which fits within
the guidelines allowed in table 7.
NOTE − All horizontal runs of exhaust pipe must slope back
toward unit. A minimum of 1/4" (6mm) drop for each 12"
(305mm) of horizontal run is mandatory for drainage.
NOTE − Exhaust pipe MUST be glued to furnace exhaust
fittings.
NOTE − Exhaust piping should be checked carefully to
make sure there are no sags or low spots.
TABLE 7
Maximum Allowable Intake or Exhaust Vent Length
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
Number Of
90° Elbows
Used
1
2
3
4
5
6
7
8
9
10
Number Of
90° Elbows
Used
1
2
3
4
5
6
7
8
9
10
Number Of 90°
Elbows Used
1
2
3
4
5
6
7
8
9
10
Number Of 90°
Elbows Used
1
2
3
4
5
6
7
8
9
10
045
81
76
71
66
61
56
51
46
41
36
2" Pipe
Model
070
090
66
44
61
39
56
34
51
29
46
24
41
19
36
14
31
n/a
26
n/a
21
n/a
045
81
76
71
66
61
56
51
46
41
36
2" Pipe
Model
070
090
66
44
61
39
56
34
51
29
46
24
41
19
36
14
31
n/a
26
n/a
21
n/a
045
73
68
63
58
53
48
43
38
33
28
045
73
68
63
58
53
48
43
38
33
28
Standard Termination at Elevation 0 − 4500 ft
2−1/2" Pipe
Model
110
045
070
090
110
24
115
115
93
58
19
110
110
88
53
14
105
105
83
48
n/a
100
100
78
43
n/a
95
95
73
38
n/a
90
90
68
33
n/a
85
85
63
28
n/a
80
80
58
23
n/a
75
75
53
18
n/a
70
70
48
13
Standard Termination Elevation 4500 − 10,000 ft
2−1/2" Pipe
Model
110
045
070
090
110
n/a
115
115
93
58
n/a
110
110
88
53
n/a
105
105
83
48
n/a
100
100
78
43
n/a
95
95
73
38
n/a
90
90
68
33
n/a
85
85
63
28
n/a
80
80
58
23
n/a
75
75
53
18
n/a
70
70
48
13
Concentric Termination at Elevation 0 − 4500 ft
2" Pipe
2−1/2" Pipe
Model
Model
070
090
110
045
070
090
110
58
42
22
105
105
89
54
53
37
17
100
100
84
49
48
32
12
95
95
79
44
43
27
90
90
74
39
38
22
85
85
69
34
33
17
80
80
64
29
28
12
75
75
59
24
n/a
23
70
70
54
19
18
65
65
49
14
n/a
13
60
60
44
n/a
Concentric Termination Elevation 4501 − 10,000 ft
2" Pipe
2−1/2" Pipe
Model
Model
070
090
110
045
070
090
110
58
42
105
105
89
54
53
37
100
100
84
49
48
32
95
95
79
44
43
27
90
90
74
39
38
22
85
85
69
34
n/a
33
17
80
80
64
29
28
12
75
75
59
24
23
70
70
54
19
18
65
65
49
14
n/a
13
60
60
44
n/a
Page 16
045
138
133
128
123
118
113
108
103
98
93
3" Pipe
Model
070
090
137
118
132
113
127
108
122
103
117
98
112
93
107
88
102
83
97
78
92
73
110
118
113
108
103
98
93
88
83
78
73
045
138
133
128
123
118
113
108
103
98
93
3" Pipe
Model
070
090
137
118
132
113
127
108
122
103
117
98
112
93
107
88
102
83
97
78
92
73
110
118
113
108
103
98
93
88
83
78
73
045
121
116
111
106
101
96
91
86
81
76
3" Pipe
Model
070
090
121
114
116
109
111
104
106
99
101
94
96
89
91
84
86
79
81
74
76
69
110
114
109
104
99
94
89
84
79
74
69
045
121
116
111
106
101
96
91
86
81
76
3" Pipe
Model
070
090
121
114
116
109
111
104
106
99
101
94
96
89
91
84
86
79
81
74
76
69
110
114
109
104
99
94
89
84
79
74
69
TYPICAL EXHAUST PIPE CONNECTIONS
Pipe size determined in table 7.
2”
2”
2”
2”
2”
or
3”
TRANSITION
*2”
INTAKE
DO NOT transition from smaller
to larger pipe size in horizontal
runs of exhaust pipe.
EXHAUST
TOP VIEW
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
FIGURE 19
TYPICAL INTAKE PIPE CONNECTIONS
Pipe size determined in table 7.
2”
2”
2”
2”
2”
or
TRANSITION
3”
*2”
*2”
3”
TRANSITION
*2”
INTAKE
EXHAUST
TOP VIEW
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Intake pipe and exhaust pipe must be the same diameter.
FIGURE 20
Page 17
Intake Piping
The EL195DF furnace may be installed in either direct
vent or non−direct vent applications. In non−direct vent
applications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered. Guidelines listed in Combustion, Dilution and
Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1 − Use cement to secure the intake pipe to the inlet air
connector.
2 − Route piping to outside of structure. Continue with
installation following instructions given in general
guide lines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table 7 for pipe sizes.
TYPICAL AIR INTAKE PIPE CONNECTIONS
NON−DIRECT VENT APPLICATIONS
AIR
INTAKE
SCREEN
(Provided)
NOTE − Air intake screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken
from indoors and the flue gases are discharged to the outdoors. The EL195DF is then classified as a non-direct
vent, Category IV gas furnace.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the outdoors. The EL195DF is then classified as a direct vent,
Category IV gas furnace.
In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current
CSA−B149 Natural Gas and Propane Installation Codes in
Canada for details.
Position termination according to location given in figure 22
or 23. In addition, position termination so it is free from any
obstructions and 12" above the average snow accumulation.
At vent termination, care must be taken to maintain
protective coatings over building materials (prolonged
exposure to exhaust condensate can destroy protective
coatings). It is recommended that the exhaust outlet not be
located within 6 feet (1.8m) of a condensing unit because
the condensate can damage the painted coating.
NOTE − If winter design temperature is below 32°F (0°C),
exhaust piping should be insulated with 1/2" (13mm), Armaflex or equivalent when run through unheated space.
Do not leave any surface area of exhaust pipe open to outside air; exterior exhaust pipe should be insulated with
1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be
necessary. Insulation on outside runs of exhaust pipe
must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary
in some specific applications.
NOTE − During extremely cold temperatures, below
approximately 20°F (6.7°C), units with long runs of vent
pipe through unconditioned space, even when insulated,
may form ice in the exhaust termination that prevents the
unit from operating properly. Longer run times of at least 5
minutes will alleviate most icing problems. Also, a heating
cable may be installed on exhaust piping and termination
to prevent freeze−ups. Heating cable installation kit is
available from Lennox. See Condensate Piping section
for part numbers.
FIGURE 21
Follow the next two steps when installing the unit in NonDirect Vent applications where combustion air is taken
from indoors and flue gases are discharged outdoors.
1 − Use field−provided materials and the factory−provided
air intake screen to route the intake piping as shown in
figure 21. Maintain a minimum clearance of 3" (76mm)
around the air intake opening. The air intake opening
(with the protective screen) should always be directed
forward, or sideways.
2 − Use cement to secure the intake pipe to the connector,
if desired.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze−ups and
may block the terminations.
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches
(305mm).
Page 18
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
Operable
I
Fixed
Closed
M
B
K
J
A
B
VENT TERMINAL
A=
Clearance above grade, veranda,
porch, deck or balcony
B=
Clearance to window or
door that may be opened
C=
Clearance to permanently
closed window
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
E=
F=
G=
Clearance to unventilated soffit
Clearance to outside corner
AIR SUPPLY INLET
AREA WHERE TERMINAL
IS NOT PERMITTED
US Installations1
Canadian Installations2
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
* 12"
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
Clearance to inside corner
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
H=
Clearance to each side of center line extended above meter / regulator assembly
* 3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the combustion air inlet to any other appliance
* 3 feet (.9m)
3 feet (.9m)
J=
K=
L=
M=
1 In
2 In
Clearance to mechanical air supply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
3 feet (.9m) above if within 10 feet
(3m) horizontally
7 feet (2.1m)
*12 inches (305mm)
accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two
sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 22
Page 19
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1,
clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions."
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
Fixed
Closed
Operable
F
B
B
C
I
Fixed
Closed
Operable
M
B
K
J
A
B
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE TERMINAL
IS NOT PERMITTED
US Installations1
Canadian Installations2
A=
Clearance above grade, veranda,
porch, deck or balcony
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
B=
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
C=
Clearance to permanently
closed window
* 12"
* 12"
D=
Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
E=
Clearance to unventilated soffit
F=
Clearance to outside corner
G=
Clearance to inside corner
H=
Clearance to each side of center line extended above meter / regulator assembly
I=
Clearance to service regulator
vent outlet
Clearance to non−mechanical air
supply inlet to building or the combustion air inlet to any other appliance
J=
K=
L=
M=
1 In
2 In
Clearance to mechanical air supply inlet
Clearance above paved sidewalk or
paved driveway located on public property
Clearance under veranda, porch,
deck or balcony
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
* 3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw)
3 feet (.9m) above if within 10 feet
(3m) horizontally
* 7 feet (2.1m)
*12 inches (305mm)
accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
accordance with the current CSA B149.1, Natural Gas and Propane Installation Code
A vent shall not terminate directly above a sidewalk or paved driveway that is located
between two single family dwellings and serves both dwellings.
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
* No minimum to outside corner
*
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
6 feet (1.8m)
7 feet (2.1m)
12 inches (305mm)
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements
of the gas supplier and these installation instructions."
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two
sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 23
Page 20
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.
NOTE − Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gasses may impinge on the building material, a corrosion−resistant shield (minimum 24 inches
square) should be used to protect the wall surface. If the
optional tee is used, the protective shield is recommended.
The shield should be constructed using wood, plastic,
sheet metal or other suitable material. All seams, joints,
cracks, etc. in the affected area should be sealed using an
appropriate sealant. See figure 26.
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In attic
or closet installations, vertical termination through the roof
is preferred. Figures 24 through 36 show typical terminations.
1 − Exhaust and intake exits must be in same pressure
zone. Do not exit one through the roof and one on the
side. Also, do not exit the intake on one side and the
exhaust on another side of the house or structure.
2 − Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof
terminations and 6" (152mm) on side wall terminations.
3 − On roof terminations, the intake piping should terminate straight down using two 90° elbows (See figure
24).
4 − Exhaust piping must terminate straight out or up as
shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve
the velocity of exhaust away from the intake piping.
See table 8.
TABLE 8
EXHAUST PIPE TERMINATION SIZE REDUCTION
EL195
MODEL
Exhaust Pipe Size
Termination
Pipe Size
*045 and *070
*090
110
2" (51mm), 2−1/2" (64mm),
3" (76mm)
1−1/2" (38mm)
2" (51mm)
2" (51mm)
*EL195DF−045, −070 and −090 units with the flush−mount termination
must use the 1−1/2"accelerator supplied with the kit.
5 − On field−supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. Intake piping
should be as short as possible. See figures 27 and 28.
NOTE − Care must be taken to avoid recirculation of
exhaust back into intake pipe.
6 − On field supplied terminations, a minimum distance
Page 21
between the end of the exhaust pipe and the end of
the intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
figures 27 and 28.
Inches(mm)
3"(76mm) MAX.
SIZE TERMINATION
PIPE PER TABLE 8.
UNCONDITIONED
ATTIC SPACE
8" (203mm) MIN
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 24
2" EXTENSION FOR
2" PVC PIPE
1" EXTENSION FOR
3" PVC PIPE
FURNACE
EXHAUST
PIPE
4’’
FURNACE
INTAKE
PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
1−1/2" ACCELERATOR
(all −070 and −090 units)
FLUSH−MOUNT SIDE WALL TERMINATION KIT 51W11
FIGURE 25
7 − If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other obstructions, piping must be supported every 24"
(610mm) as shown in figures 27 and 28. In addition,
close coupled wall termination kits must be extended
for use in this application. See figures 34 and 35.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated
with pipe sized per table 8.The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5m) to the equivalent length of the
pipe.
8 − A multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in figure 31.
B
B
D
D
C
Intake
C
3
1
Front View of
Intake and Exhaust
A
Exhaust
A
2
Intake
Exhaust
TABLE 9
D
1
E
B
12"
C
2
A
A− Clearance above
grade or average snow
accumulation
B−Horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
D−Exhaust pipe length
E−Wall support distance
from top of each pipe
(intake/exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (508MM) Min.
12" (508MM) Min.
6" (152MM) Min.
24" (610 MM) Max
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
9" (227MM) Min.
12" (305MM) Min. 12" (305MM) Min.
16" (405 MM) Max. 20" (508MM) Max.
6" (152MM) Max.
6" (152MM) Max.
NOTE − See unit installation instructions for proper exhaust pipe termination size reduction.
exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
1 The
FIGURE 26
Page 22
FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
With INTAKE ELBOW
FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL RING TERMINATION KIT
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
1/2" (13mm) ARMAFLEX
INSULATION IN UNCONDITIONED SPACE
1/2" (13mm) ARMAFLEX
INSULATION IN UNCONDITIONED SPACE
SIZE TERMINATION
PER TABLE 8
SIZE TERMINATION
PER TABLE 8
D
D
B
C
B
STRAIGHT
APPPLICATION
A
C
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE
D
E
* WALL
SUPPORT
D
E
* WALL
SUPPORT
B
B
A
A
C
EXTENDED
APPLICATION
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (508MM)
12" (508MM)
B−Maximum horizontal
separation between
intake and exhaust
6" (152MM)
6" (152MM)
C−Minimum from
end of exhaust to
inlet of intake
8" (203MM)
8" (203MM)
D−Maximum exhaust
pipe length
12" (305MM)
20" (508MM)
6" (152MM)
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
6" (152MM)
EXTENDED
APPLICATION
C
See venting table 7 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
A−Minimum clearance
above grade or average
snow accumulation
STRAIGHT
APPPLICATION
See venting table 7 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
12" (508MM)
12" (508MM)
6" (152MM)
6" (152MM)
6" (152MM)
6" (152MM)
D−Maximum exhaust
pipe length
12" (305MM)
20" (508MM)
E−Maximum wall support
distance from top of each
pipe (intake/exhaust)
6" (152MM)
6" (152MM)
A−Minimum clearance
above grade or average
snow accumulation
B−Maximum horizontal
separation between
intake and exhaust
C−Minimum from
end of exhaust to
inlet of intake
FIGURE 28
FIGURE 27
Page 23
1−1/2" (38mm) accelerator
provided on 71M80 & 44W92
kits for EL195DF045P36B− &
070P36B
12” (305mm)
SIZE
TERMINATION
PIPE PER
TABLE 8.
INTAKE
AIR
FLASHING
(Not Furnished)
INTAKE
Minimum
Above Average
Snow
Accumulation
EXHAUST VENT
Front View
Top View
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
CLAMP
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
1/2" (13mm) Foam Insulation
in Unconditioned Space
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
OUTSIDE WALL
DIRECT VENT WALL TERMINATION KIT
(30G28 or 81J20)
FIGURE 29
FIGURE 32
1−1/2" (38mm) accelerator
provided on 71M80 &
44W92 kits for
EL195DF045P36B− &
070P36B
EXHAUST
AIR
EXHAUST VENT
Front View
INTAKE
AIR
WALL
INTAKE AIR
6 (152mm) MIN.
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE
SIZE TO TERMINATION OUTSIDE
EXHAUST VENT
SIZE
TERMINATION
PIPE PER
TABLE 8.
INTAKE
AIR
EXHAUST
AIR
Top View
INTAKE
AIR
INTAKE 12" (305mm) Min.
AIR
above grade or
average snow accumulation.
GRADE
CLAMP
(Not Furnished)
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
44W92 or 44W93 (Canada)
1/2" (13mm) Foam Insulation
in Unconditioned Space
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
EXHAUST VENT
INTAKE AIR
FIGURE 30
8" (206mm) MIN.
OUTSIDE WALL
EXHAUST
VENT
12"
(305mm)
5−1/2"
(140mm)
5"
(127mm)
DIRECT VENT WALL TERMINATION KIT
(22G44 or 44J40)
FIGURE 33
INTAKE
AIR
18" MAX.
(457mm)
Front View
EXHAUST VENT
Inches (mm)
optional intake elbow
12" (305mm) Min.
above grade or
average snow acINTAKE
cumulation.
AIR
Side View
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
(22G44, 44J40, 30G28 or 81J20)
FIGURE 31
Page 24
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
WALL SUPPORT*
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe
between the end of the exhaust pipe and intake pipe
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12”
(305 mm)
EXHAUST
AIR
6” (152 mm)
Maximum
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
INTAKE
AIR
INTAKE
AIR
EXHAUST
AIR
5” (127 mm)
8” (203 mm) Min.
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉ
5−1/2”
(140 mm)
GRADE
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 34
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
If intake and exhaust pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions, field−
fabricated piping must be installed.
WALL SUPPORT*
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12”
(305 mm)
EXHAUST
AIR
6” (152 mm)
Maximum
1/2” (13 mm)
FOAM INSULATION
(Field Furnished)
INTAKE
AIR
6” (152 mm)
Minimum
INTAKE
AIR
EXHAUST
AIR
5” (127 mm)
6” (152 mm)
Minimum
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
GRADE
12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust
20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust
12” (305 mm) Minimum
Above Grade or Average
Snow Accumulation
ÉÉÉÉÉÉÉÉÉÉÉÉ
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 35
Page 25
5−1/2”
(140 mm)
GRADE
EL195DF DIRECT VENT APPLICATION
STRAIGHT−CUT OR
USING EXISTING CHIMNEY ANGLE−CUT
IN DIRECTION
SIZE TERMINATION
PIPE PER TABLE 8.
OF ROOF SLOPE *
8" − 12"
(203mm − 305mm)
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
3" − 8"
(76mm−
203mm)
INTAKE PIPE
INSULATION (optional)
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
1/2" (13mm) FOAM
INSULATION
3" (76mm) OR
2" (51mm) PVC
ALTERNATE
INTAKE PIPE
UNCONDITIONED
ATTIC SPACE
PROVIDE SUPPORT
FOR EXHAUST LINES
INSULATE
TO FORM
SEAL
3" − 8"
(76mm−
203mm)
EXTERIOR
PORTION OF
CHIMNEY
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
*SIZE TERMINATION
PIPE PER TABLE 8.
FIGURE 37
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE
FIGURE 36
Details of Exhaust Piping Terminations for Non-Direct
Vent Applications
Exhaust pipes may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred. Figures 37 through 40 show typical terminations.
1 − Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
table 8.The specified pipe size ensures proper velocity required to move the exhaust gases away from the
building.
2 − On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches
(305mm) for 2" PVC and 20 inches (508mm) for 3"
(76mm) PVC beyond the outside wall. See figure 38.
FIELD−PROVIDED
REDUCER MAY
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
SIZE TERMINATION
PIPE PER TABLE 8.
1/2" (13mm)
ARMAFLEX
INSULATION
PVC REDUCER
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR
(15F74) WALL TERMINATION KIT
FIGURE 38
3 − If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm) as
shown in figure 39. When exhaust piping must be run
up an outside wall, any reduction in exhaust pipe size
must be done after the final elbow.
Page 26
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
UNCONDITIONED
SPACE
6" (152mm)
Max
SIZE TERMINATION
PIPE PER
TABLE 8.
*WALL SUPPORT
OUTSIDE WALL
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
NOTE − If necessary the condensate trap may be installed
up to 5´ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
CONDENSATE TRAP AND PLUG LOCATIONS
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
1/2" (13mm) FOAM
INSULATION IN
UNCONDITIONED
SPACE
*Use wall support every 24" (610). Use
two supports if extension is greater
than 24" but less than 48".
Trap
(same on
right side)
1/2" (13mm) FOAM
INSULATION
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION EXTENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED
1−1/2 in.
Plug
(same on left
side)
FIGURE 39
EL195DF NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
SIZE TERMINATION
PIPE PER TABLE 8.
3" − 8"
(76mm−
203mm)
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
3" − 8"
(76mm−
203mm)
EXTERIOR
PORTION OF
CHIMNEY
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 40
Condensate Piping
This unit is designed for either right- or left-side exit of condensate piping. Refer to figure 41 for condensate trap locations.
Page 27
FIGURE 41
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of
PVC pipe required to reach available drain.
2 − Remove plug (figure 41) from the cold end header box
at the appropriate location on the side of the unit. Install
field−provided 1/2" NPT male fitting into cold end header box. Use teflon tape or appropriate pipe dope.
3 − Install the cap over the clean out opening at the base of
the trap. See figure 44.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in figure 44. Route the condensate line to an open drain.
NOTE − If necessary the condensate trap may be installed
up to 5 feet away from the furnace. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
NOTE − Vinyl tubing may be used for condensate drain.
Tubing must be 1−1/4" OD X 1" ID and should be
attached to the drain on the trap using a hose clamp.
5 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start−Up section.
Condensate line must slope downward away from the
trap to drain. If drain level is above condensate trap,
condensate pump must be used. Condensate drain
line should be routed within the conditioned space to
avoid freezing of condensate and blockage of drain
line. If this is not possible, a heat cable kit may be used
on the condensate trap and line. Heat cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit
no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft.
(15.2m) − kit no. 26K70.
EL195DF with Evaporator Coil
Condensate trap and
evaporator coil must drain
separately as shown.
Field−Provided Vent
CONDENSATE TRAP LOCATION
(shown with right side exit of condensation)
Drain
Field Provided Vent
min. 1" Above
Condensate Drain
FIGURE 43
Trap can be installed a
maximum of 5 ft. from furnace.
(*PVC Only)
CAUTION
1" min.
Do not use copper tubing or existing copper
condensate lines for drain line.
5’ max.
CAUTION
A separate drain line must be run to the drain
from the condensate trap to ensure proper
drainage and pressure switch operation. DO
NOT connect the condensate trap drain into the
drain line from the evaporator coil.
to drain
*Piping from furnace must slope down a
minimum of 1/4" per ft. toward trap.
FIGURE 42
Page 28
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC
OPTIONAL Condensate Drain Connection
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
90° Street Elbow
1/2 inch PVC
(Not Furnished)
1 (25) Minimum
Vent
5 Feet
Maximum
Above Top of Condensate Drain
Connection In Unit
90° Elbow 1/2 inch PVC
(Not Furnished)
Condensate Drain
Connection In Unit
OPTIONAL Drain Piping
1/2 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Coupling 1/2 inch slip X slip
(Not Furnished)
Drain Assembly for 1/2 inch Drain Pipe
1/2 inch PVC Pipe
(Not Furnished)
90° Street Elbow
1/2 inch PVC
(Furnished)
To
Drain
To
Drain
Condensate Drain
Connection In Unit
Drain Trap
Assembly
(Furnished)
90° Elbow
1/2 inch PVC
(Not Furnished)
Drain Assembly for 3/4 inch Drain Pipe
Drain Trap
Clean Out
90° Elbow
3/4 inch PVC
(Not Furnished)
To
Drain
90° Elbow
3/4 inch PVC
(Not Furnished)
To Coupling 3/4 inch slip X slip
Drain
(Not Furnished)
Drain Trap Assembly with 1/2 inch Piping
Drain Trap Assembly with 3/4 inch Piping
1 inch (25mm) Minimum Above Top of
Condensate Drain Connection In Unit
1 inch (25mm) Minimum Above Top of
Condensate Drain Connection In Unit
Vent
Drain Trap Assembly
(Furnished)
Vent
7
(178)
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
To
Drain
To
Drain
FIGURE 44
Page 29
Gas Piping
IMPORTANT
Compounds used on threaded joints of gas piping
must be resistant to the actions of liquified petroleum gases.
CAUTION
If a flexible gas connector is required or allowed by
the authority that has jurisdiction, black iron pipe
shall be installed at the gas valve and extend outside
the furnace cabinet. The flexible connector can then
be added between the black iron pipe and the gas
supply line.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory− and field−installed) for gas leaks. Use
a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures less
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
WARNING
Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve.
1 − Gas piping may be routed into the unit through either
the left- or right-hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
figure 46.
2 − When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 10
lists recommended pipe sizes for typical applications.
NOTE − Use two wrenches when connecting gas piping to avoid transferring torque to the manifold.
3 − Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas
line should not touch side of unit. See figures 46.
4 − Piping should be sloped 1/4 inch per 15 feet (6mm per
5.6m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers
or straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.
5 − A 1/8" N.P.T. plugged tap or pressure post is located
on the gas valve to facilitate test gauge connection.
See figure 53.
6 − In some localities, codes may require installation of a
manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the
ground joint type.
MANUAL MAIN SHUT−OFF
VALVE WILL NOT HOLD
NORMAL TEST PRESSURE
1/8" N.P.T. PLUGGED TAP
FURNACE
ISOLATE
GAS VALVE
CAP
FIGURE 45
IMPORTANT
When testing pressure of gas lines, gas valve must
be disconnected and isolated. See figure 45. Gas
valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could
result in serious injury, death, or property damage.
Never use an open flame to test for gas leaks. Check
all connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to certain
metals. Carefully rinse piping thoroughly after leak
test has been completed.
Page 30
Left Side Piping
(Standard)
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap Shown)
AUTOMATIC
GAS VALVE
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap
Shown)
GROUND
JOINT
UNION
AUTOMATIC
GAS VALVE
Plug
Plug
GROUND
JOINT
UNION
Bellows Grommet
DRIP LEG
Right Side Piping
(Alternate)
FIELD
PROVIDED
AND INSTALLED
DRIP LEG
Bellows Grommet
NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 46
TABLE 10
GAS PIPE CAPACITY − FT3/HR (kL/HR)
Length of Pipe−Feet(m)
50
60
70
(15.240) (18.288) (21.336)
Nominal
Iron Pipe Size
−Inches(mm)
Internal
Diameter
−Inches(mm)
10
(3.048)
20
(6.096)
30
(9.144)
40
(12.192)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
1
(25.4)
1.049
(26.645)
680
(19.25)
465
(13.17)
375
(10.62)
320
(9.06)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2−1/2
(63.5)
2.469
(67.713)
3
(76.2)
4
(101.6)
80
(24.384)
90
(27.432)
100
(30.480)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95)
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
Page 31
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances, the venting system is likely to be too large to
properly vent the remaining attached appliances.
Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the
venting system has been installed improperly, you must
correct the system as indicated in the general venting requirements section.
4 − Follow the lighting instructions. Turn on the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5 − After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6 − After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation.
7 − If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances
connected to the venting system are not in
operation:
Resize the common venting system to the minimum
vent pipe size determined by using the appropriate
tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1.
Electrical
CAUTION
1 − Seal any unused openings in the common venting system.
2 − Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
3 − Close all building doors and windows and all doors between the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common
venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
Electrostatic discharge can affect electronic components. Take precautions to
neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
The unit is equipped with a field make−up box on the left
hand side of the cabinet. A field−provided make−up box can
be installed on the exterior of the right side of the furnace to
facilitate installation. If the make−up box is moved to the
right side, clip the wire ties that bundle the wires together
and install on the outside of the cabinet. See figure 48. The
excess wire must be pulled into the blower compartment.
Secure the excess wire to the existing harness to protect it
from damage.
Page 32
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
shown in figure 50. Use 18−gauge wire or larger that is suitable for Class II rating for thermostat connections.
INTERIOR MAKE−UP BOX
(FACTORY− INSTALLED LEFT SIDE)
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and
current Canadian Electric Code part 1 (CSA standard
C22.1) for Canada. A green ground wire is provided in the
field make−up box.
NOTE − The EL195DF furnace contains electronic components that are polarity sensitive. Make sure that the furnace
is wired correctly and is properly grounded.
MAKE−UP
BOX INSIDE
CABINET
Left side
Generator Use − Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
The furnace requires 120 volts + 10% (Range: 108
volts to 132 volts)
The furnace operates at 60 Hz + 5% (Range: 57 Hz to
63 Hz)
The furnace integrated control requires both polarity
and proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power
Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion)
Accessory Terminals
FIGURE 47
EXTERIOR MAKE−UP BOX
(FIELD PROVIDED RIGHT SIDE)
MAKE−UP
BOX
OUTSIDE
CABINET
One line voltage EAC" 1/4" spade terminal is provided on
the furnace integrated control. See figure 52 for integrated
control configuration. This terminal is energized when the
indoor blower is operating. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an external relay.
Right Side
FIGURE 48
Refer to figure 50 for field wiring and figure 51 for schematic
wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE − Unit nameplate states maximum current draw.
Maximum Over−Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
Before connecting the thermostat or the power wiring,
check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to
check the length of the wire.
Page 33
One line voltage HUM" 1/4" spade terminal is provided on
the furnace integrated control. See figure 52 for integrated
control configuration. This terminal is energized in the
heating mode when the combustion air inducer is operating. Any humidifier rated up to one amp can be connected
to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay.
One 24V "H" 1/4" spade terminal is provided on the furnace
integrated control. See figure 52 for integrated control configuration. The terminal is energized in the heating mode
when the combustion air inducer is operating and the pressure switch is closed. Any humidifier rated up to 0.5 amp
can be connected to this terminal with the ground leg of the
circuit connected to ground or the "C" terminal.
EL195DF and CONDENSING UNIT
THERMOSTAT DESIGNATIONS
(Refer to specific thermostat and outdoor unit.)
Thermostat
POWER
R
W1
Y
G
C
Furnace
HEAT
COOLING
INDOOR BLOWER
COMMON
R
W
Y
G
C
Condensing
Unit
*CONDENSING
UNIT
CONDENSING
UNIT
CONDENSING
UNIT COMMON
Install the room thermostat according to the instructions provided with the thermostat. See figure 49 for
thermostat designations. If the furnace is being
matched with a heat pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions.
Indoor Blower Speeds
1 − When the thermostat is set to FAN ON," the indoor
blower will run continuously on the fan speed when
there is no cooling or heating demand.
2 − When the EL195DF is running in the heating mode, the
indoor blower will run on the heating speed.
3 − When there is a cooling demand, the indoor blower will
run on the cooling speed.
*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS
FIGURE 49
TYPICAL EL195DF FIELD WIRING DIAGRAM
IGNITOR
*NOTE − R" REQUIRED ON SOME OUTDOOR UNITS
*R
FIGURE 50
Page 34
TYPICAL EL195DF WIRING DIAGRAM
FIGURE 51
Page 35
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
HUM
LINE
XFMR
EAC
COOL
HEAT
PARK
FLAME
FAN
HUM
Red LED
TERMINAL DESIGNATIONS
Humidifier (120VAC)
Input (120VAC)
Transformer (120VAC)
Indoor Air Quality Accessories (120VAC)
Blower − Cooling Speed (120VAC)
Blower − Heating Speed (120VAC)
Dead terminals to park alternate speed taps
Flame sensor
Continuous blower
Humidifier (24VAC)
Recall
Blower off delay
jumper
FIGURE 52
Unit Start−Up
WARNING
FOR YOUR SAFETY READ BEFORE OPERATING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical supply.
WARNING
Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in
fire or explosion. Immediately call a qualified service technician to inspect the furnace and to replace
all gas controls, control system parts, and electrical
parts that have been wet or to replace the furnace,
if deemed necessary.
CAUTION
Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch.
BEFORE LIGHTING the unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the
floor.
The gas valve on the EL195DF is equipped with a gas
control switch. Use only your hand to move switch. Never
use tools. If the switch will not move by hand, do not try to
repair it. Force or attempted repair may result in a fire or
explosion.
Page 36
Placing the furnace into operation:
MANIFOLD PRESSURE
ADJUSTMENT SCREW
(under barbed fitting)
EL195DF units are equipped with an automatic hot surface ignition system. Do not attempt to manually light
burners on this furnace. Each time the thermostat calls
for heat, the burners will automatically light. The ignitor
does not get hot when there is no call for heat on these
units.
MANIFOLD
PRESSURE
OUTLET
PORT
Priming Condensate Trap
The condensate trap should be primed with water prior to
start−up to ensure proper condensate drainage. Either
pour 10 fl. oz. (300 ml) of water into the trap, or follow
these steps to prime the trap:
1 − Follow the lighting instructions to place the unit into operation.
2 − Set the thermostat to initiate a heating demand.
3 − Allow the burners to fire for approximately 3 minutes.
INLET
PRESSURE
PORT
GAS VALVE SHOWN IN ON POSITION
FIGURE 53
12− If the appliance will not operate, follow the instructions
Turning Off Gas to Unit" and call your service technician or gas supplier.
Turning Off Gas to Unit
4 − Adjust the thermostat to deactivate the heating demand.
5 − Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes.
6 − Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop.
At this point, the trap should be primed with sufficient
water to ensure proper condensate drain operation.
WARNING
If you do not follow these instructions exactly, a fire
or explosion may result causing property damage,
personal injury or death.
Gas Valve Operation (Figure 53)
1 − STOP! Read the safety information at the beginning of
this section.
2 − Set the thermostat to the lowest setting.
3 − Turn off all electrical power to the unit.
4 − This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
5 − Remove the access panel.
6 − Move gas valve switch to OFF. See figure 53.
7 − Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step.
8 − Move gas valve switch to ON. See figure 53.
9 − Replace the access panel.
10− Turn on all electrical power to to the unit.
11− Set the thermostat to desired setting.
NOTE − When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
Page 37
1 − Set the thermostat to the lowest setting.
2 − Turn off all electrical power to the unit if service is to be
performed.
3 − Remove the access panel.
4 − Move gas valve switch to OFF.
5 − Replace the access panel.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse or tripped breaker?
5 − Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 − Is the unit ignition system in lockout? If the unit locks out
again, inspect the unit for blockages.
Heating Sequence Of Operation
1 − When thermostat calls for heat, combustion air inducer
starts.
2 − Combustion air pressure switch proves blower operation. Switch is factory−set and requires no adjustment.
3 − After a 15−second prepurge, the hot surface ignitor energizes.
4 − After a 20−second ignitor warm−up period, the gas
valve solenoid opens. A 4−second Trial for Ignition period begins."
5 − Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6 − If flame is not detected after first ignition trial, the ignition control will repeat steps 3 and 4 four more times
before locking out the gas valve (WATCHGUARD"
flame failure mode). The ignition control will then automatically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60−minute WATCHGUARD" period,
move thermostat from Heat" to OFF" then back to
Heat". Heating sequence then restarts at step 1.
Manifold Pressure Measurement
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting.
Connect to a manometer to measure manifold pressure.
2 − Start unit and allow 5 minutes for unit to reach steady
state.
3 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
4 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
12.
NOTE − Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 11
GAS METER CLOCKING CHART
Seconds for One Revolution
Natural
LP
ML193
Unit
1 cu ft
2 cu ft
1 cu ft
2 cu ft
Dial
Dial
Dial
DIAL
−045
80
160
200
400
−070
55
110
136
272
−090
41
82
102
204
−110
33
66
82
164
Natural−1000 btu/cu ft
LP−2500 btu/cu ft
NOTE − To obtain accurate reading, shut off all other gas
appliances connected to meter.
Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a
more accurate time). Divide by two and compare to time
in table 11. If manifold pressure matches table 12 and rate
is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed.
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a field−provided barbed fitting and connect a
manometer to measure supply pressure. See table 12 for
proper supply line pressure. Replace the threaded plug after measurements have been taken.
TABLE 12
Manifold and Supply Pressure (Outlet) inches w.c.
Fuel
Model
Input Sizes
Nat
All sizes
LP/Propane
All sizes
Manifold
Pressure
in.wg.
Supply
Pressure
in.wg.
Min.
Max.
3.5
4.5
10.0
10.0
11.0
13.0
Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet
and compare to the tables below. The maximum carbon
monoxide reading should not exceed 50 ppm.
TABLE 13
EL195
CO2% For Nat CO2% For LP
Unit
−045
−070
7.2 − 8.2
8.6 − 9.6
−090
−110
The maximum carbon monoxide reading should not exceed 50 ppm.
High Altitude Information
NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities.
EL195DF units require no manifold pressure adjustments
for operation at altitudes up to 10,000 feet (3048 m) above
sea level. Units installed at altitude of 4501 − 10,000 feet
(1373 to 3048m) may require a pressure switch change
which can be ordered separately. Table 14 lists conversion
kit and pressure switch requirements at varying altitudes.
The combustion air pressure switch is factory−set and requires no adjustment.
Page 38
TABLE 14
Conversion Kit and Pressure Switch Requirements at Varying Altitudes
EL195
Unit
Natural to
LP/Propane
High Altitude
Natural Burner
Orifice Kit
High Altitude
LP/Propane
Burner Orifice Kit
0 − 7500 ft
(0 − 2286m)
7501 − 10,000 ft
(2286 − 3038m)
7501 − 10,000 ft
(2286 − 3038m)
−045
−070
−090
*69W73
73W37
*68W68
−110
High Altitude Pressure Switch
4501 − 7500 ft
(1373 − 2286m)
7501 −10,000 ft
(2286 − 3048m)
No Change
74W90
77W43
73W22
77W42
73W22
77W43
73W22
* Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit.
Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m).
Testing of Non−Direct Vent Applications
for Proper Venting and Sufficient
Combustion Air
WARNING
CARBON MONOXIDE POISONING HAZARD!
Failure to follow the steps outlined below for each
appliance connected to the venting system being
placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being
placed into operation, while all other appliances connected to the venting system are not in operation.
After the EL195DF gas furnace has been started, the following test should be conducted to ensure proper venting
and sufficient combustion air has been provided to the
EL195DF as well as to other gas-fired appliances which
are separately vented.
If a EL195DF furnace replaces a Category I furnace which
was commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the
single water heater or other appliance. The vent should be
checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has
been installed improperly, or if provisions have not been
made for sufficient amounts of combustion air, corrections
must be made as outlined in the previous section.
1 − Seal any unused openings in the venting system.
2 − Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
Page 39
3 − To the extent that it is practical, close all building doors
and windows and all doors between the space in which
the appliances connected to the venting system are located and other spaces of the building.
4 − Close fireplace dampers.
5 − Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate a
summer exhaust fan.
6 − Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
7 − Use the flame of match or candle to test for spillage of
flue gases at the draft hood relief opening after 5 minutes of main burner operation.
8 − If improper venting is observed during any of the
above tests, the venting system must be corrected or
sufficient combustion/make-up air must be provided.
The venting system should be re-sized to approach
the minimum size as determined by using the appropriate tables in appendix G in the current standards
of the National Fuel Gas Code ANSI−Z223.1/NPFA 54
in the U.S.A., and the appropriate Natural Gas and
Propane appliances venting sizing tables in the current standard of the CSA−B149 Natural Gas and Propane Installation Codes in Canada.
9 − After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their previous
condition of use.
Other Unit Adjustments
NOTE − See troubleshooting flow charts if any safety
switches are found to be open.
Primary Limit
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no adjustment.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of
the burner box.
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
HEAT FAN-OFF TIME IN SECONDS
Pressure Switch
Fan Control
Fan On Delay
The heat fan on time of 30 seconds is not adjustable. The
cool fan on delay is 2 seconds and not adjustable.
Fan Off Delay
The heat fan off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position across the five pins
on the integrated control. The unit is shipped with a factory
fan off setting of 90 seconds. The fan off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is
de−energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures. See figure 54.
The cool fan off delay (amount of time that the blower operates after the cool demand has been satisfied) is 45 seconds and not adjustable.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
60
90
120
180
60
90
120
180
After the furnace has been started and supply and return air
temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to
maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the temperature. Decrease the blower speed to increase
the temperature rise. Failure to adjust the temperature rise
may cause erratic limit operation.
60
90
120
180
Temperature Rise
NO JUMPER
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
60 Second
90 Second
120 Second
180 Second
off Time
off Time
off Time
off Time
60
90
120
180
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory−set and must not be adjusted.
FIGURE 54
Blower Speeds
Follow the steps below to change the blower speeds.
1 − Turn off electrical power to furnace.
2 − Remove blower access panel.
3 − Disconnect existing speed tap at integrated control
speed terminal.
NOTE − Termination of any unused motor leads must be
insulated.
4 − Place unused blower speed tap on integrated control
PARK" terminal or insulate.
5 − Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed. See Blower
performance data beginning on the next page.
6 − Connect selected speed tap at integrated control
speed terminal.
7 − Resecure blower access panel.
8 − Turn on electrical power to furnace.
9 − Recheck temperature rise.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 − Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check termination for blockages.
3 − Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
Page 40
BLOWER DATA
EL195DF045P36B PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
EL195DF090P60C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
High
MediumHigh
MediumLow
Low
cfm Watts cfm Watts cfm Watts cfm Watts
External
Static
Pressure
in. w.g.
High
MediumHigh
MediumLow
Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00
1615 650 1385 555 1205 465 1045 390
0.10
1605 640 1380 545 1195 455 1035 380
0.10
2295 1240 2135 940 1885 795 1500 665
0.20
1500 620 1345 525 1165 445 1015 370
0.20
2200 1220 2085 915 1865 775 1525 655
0.30
1450 590 1290 490 1125 420
975
365
0.30
2160 1210 1990 875 1830 755 1545 640
0.40
1350 560 1235 480 1090 405
920
345
0.40
2055 1170 1935 865 1790 725 1530 620
0.50
1300 545 1170 450 1035 380
880
330
0.50
1970 1130 1855 835 1705 700 1500 600
0.60
1195 500 1095 425
840
320
0.60
1890 1105 1765 805 1635 675 1495 580
990
365
0.00
Air Volume / Watts at Various Blower Speeds
2305 1255 2145 950 1900 810 1515 670
0.70
1140 480 1020 395
895
345
780
300
0.70
1775 1075 1680 785 1565 655 1430 560
0.80
1025 450
920
370
840
330
695
270
0.80
1690 1050 1590 760 1485 630 1370 540
0.90
945
800
335
700
290
605
250
0.90
1580 1010 1485 735 1405 610 1270 510
430
EL195DF070P48B PERFORMANCE (Less Filter)
External
Static
Pressure
in. w.g.
EL195DF110P60C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
High
MediumHigh
MediumLow
Low
cfm Watts cfm Watts cfm Watts cfm Watts
External
Static
Pressure
in. w.g.
0.00
Air Volume / Watts at Various Blower Speeds
High
MediumHigh
MediumLow
Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00
1885 935 1830 815 1810 720 1700 640
0.10
1850 910 1805 795 1785 705 1680 630
0.10
2365 1235 2195 905 1960 775 1625 635
0.20
1775 890 1750 775 1710 690 1620 610
0.20
2275 1200 2125 890 1950 760 1635 625
0.30
1715 870 1685 755 1640 660 1575 595
0.30
2200 1180 2060 880 1900 735 1620 610
0.40
1645 855 1620 735 1595 650 1495 575
0.40
2115 1150 1995 850 1845 710 1620 600
0.50
1575 835 1525 715 1485 625 1440 555
0.50
2040 1115 1940 835 1795 695 1585 580
0.60
1505 815 1450 690 1425 610 1360 540
0.60
1955 1090 1855 810 1745 670 1540 565
0.70
1390 790 1360 675 1340 590 1270 525
0.70
1860 1070 1730 765 1640 650 1515 550
0.80
1280 770 1270 650 1255 570 1210 505
0.80
1735 1030 1620 740 1590 620 1415 535
0.90
1200 740 1185 635 1160 550 1090 485
0.90
1640 1010 1535 715 1480 600 1330 510
Page 41
2375 1250 2205 915 1975 785 1630 640
2 − Have a shallow pan ready to empty condensate water.
Service
3 − Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the
drain plug.
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result
in dangerous operation, serious injury, death or
property damage.
Improper servicing could result in dangerous operation, serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
WARNING
The blower access panel must be securely in place
when the blower and burners are operating. Gas
fumes, which could contain carbon monoxide, can
be drawn into living space resulting in personal injury or death.
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 3
lists recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE − After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
1 − Check all wiring for loose connections.
2 − Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp−draw on the blower motor.
Motor Nameplate__________Actual__________
Winterizing and Condensate Trap Care
1 − Turn off power to the furnace.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow
the below procedures and refer to figure 1 when disassembling unit. Use papers or protective covering in front of furnace while removing heat exchanger assembly.
1 − Turn off electrical and gas supplies to the furnace.
2 − Remove the furnace access panels.
3 − Disconnect the wires from the gas valve.
4 − Remove gas supply line connected to gas valve. Remove the burner box cover (if equipped) and remove
gas valve/manifold assembly.
5 − Remove sensor wire from sensor. Disconnect 2-pin
plug from the ignitor.
6 − Disconnect wires from flame roll−out switches.
7 − Loosen clamps at vent elbow. Disconnect condensate
drain tubing from flue collar. and remove the vent elbow.
8 − Loosen clamps and remove combustion air intake
flexible connector if equipped.
9 − Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly
aside.
NOTE − If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
10 − Mark and disconnect all combustion air pressure tubing from cold end header collector box.
11 − Mark and remove wires from pressure switch assembly. Remove pressure switch assembly. Keep tubing
attached to pressure switch assembly.
12 − Disconnect the plug from the combustion air inducer.
Remove two screws which secure combustion air inducer to collector box. Remove combustion air inducer assembly. Remove ground wire from vest panel.
13 − Remove electrical junction box from the side of the furnace.
14 − Disconnect condensate line from cold end header
box. Remove cold end header box.
15 − Loosen clamps on exhaust and air intake pipe seal
plate. Slide exhaust and intake pipes up and out to
clear blower deck. Remove exhaust and air intake
pipe seal plate.
16 − Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck.
17 − Remove the primary limit from the vestibule panel.
18 − Remove two screws from the front cabinet flange at
the blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger.
Page 42
19 − Remove screws along vestibule sides which secure
vestibule panel and heat exchanger assembly to cabinet. Remove two screws from blower rail which secure
top heat exchanger flange. Remove heat exchanger
from furnace cabinet.
20 − Back wash heat exchanger with soapy water solution
or steam. If steam is used it must be below 275°F
(135°C) .
21 − Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly.
22 − Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are
engaged properly into the support bracket on the
blower deck. Remove the indoor blower to view this
area through the blower opening.
23 − Re-secure the supporting screws along the vestibule
sides and top to the cabinet.
24 − Reinstall cabinet screws on front flange at blower
deck.
25 − Reinstall the primary limit on the vestibule panel.
26 − Route heating component wiring through hole in blower deck and reinsert strain relief bushing.
27 − Reinstall electrical junction box.
28 − Reinstall exhaust and air intake pipe seal plate. Reinstall exhaust and air intake pipes and tighten clamps
on pipe seal plate.
29 − Reinstall the cold end header box.
30 − Reinstall the combustion air inducer. Reconnect the
combustion air inducer to the wire harness.
31 − Reinstall pressure switch assembly and reconnect
pressure switch wiring.
32 − Carefully connect combustion air pressure switch
tubing from pressure switches to proper ports on
cold end header collector box.
33 − Reinstall condensate trap.
34 − Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
35 − Reconnect exhaust piping and exhaust drain tubing.
36 − Reconnect flame roll−out switch wires.
37 − Reconnect sensor wire and reconnect 2−pin plug from
ignitor.
38 − Reinstall gas valve manifold assembly. Reconnect
gas supply line to gas valve.
39 − Reinstall burner box cover if equipped.
40 − Reconnect plug to gas valve.
41 − Replace the blower compartment access panel.
Page 43
42 − Follow lighting instructions on unit nameplate to light
and operate furnace for 5 minutes to ensure the furnace is operating properly.
43− Check all piping connections, factory and field, for gas
leaks. Use a leak detecting solution or other preferred
means.
CAUTION
Some soaps used for leak detection are corrosive to
certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use
matches, candles, flame or other sources of ignition
to check for gas leaks.
44 − Replace access panel.
Cleaning the Burner Assembly (if needed)
1 − Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2 − Disconnect the 2−pin plug from the gas valve.
3 − Remove the burner box cover (if equipped).
4 − Disconnect the gas supply line from the gas valve. Remove gas valve/manifold assembly.
5 − −Loosen clamps and remove combustion air intake
flexible connector (if equipped).
5 − Mark and disconnect sensor wire from the sensor. Disconnect plug from the ignitor at the burner box.
6 − Remove four screws which secure burner box assembly to vest panel. Remove burner box from the unit.
7 − Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage.
8 − Reinstall the burner box assembly using the existing
four screws. Make sure that the burners line up in the
center of the burner ports.
9 − Reconnect the sensor wire and reconnect the 2−pin
plug to the ignitor wiring harness.
10 − Reinstall combustion air intake flexible connector (if
equipped), secure using existing clamps.
11 − Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burner box cover.
12 − Reconnect plug to gas valve.
13 − Replace the blower compartment access panel.
14 − Refer to instruction on verifying gas and electrical connections when re−establishing supplies.
15 − Follow lighting instructions to light and operate furnace for 5 minutes to ensure that heat exchanger is
clean and dry and that furnace is operating properly.
16 − Replace access panel.
Planned Service
A service technician should check the following items during an annual inspection. Power to the unit must be shut off
for safety.
Fresh air grilles and louvers (on the unit and in the room
where the furnace is installed) − Must be open and unobstructed to provide combustion air.
Burners − Must be inspected for rust, dirt, or signs of water.
Vent pipe − Must be inspected for signs of water, cracked,
damaged or sagging pipe, or disconnected joints.
Unit appearance − Must be inspected for rust, dirt, signs
of water, burnt or damaged wires, or components.
Blower access door − Must be properly in place and provide a seal between the return air and the room where the
furnace is installed.
Return air duct − Must be properly attached and provide
an air seal to the unit.
Operating performance − Unit must be observed during
operation to monitor proper performance of the unit and the
vent system.
Combustion gases − Flue products must be analyzed and
compared to the unit specifications.
Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items
can be repaired or replaced.
Instruct the homeowners to pay attention to their
furnace. Situations can arise between annual furnace inspections that may result in unsafe operation. For instance,
items innocently stored next to the furnace may obstruct
the combustion air supply. This could cause incomplete
combustion and the production of carbon monoxide gas.
Ignition Control Board Diagnostic Codes
RED LED
Flash Code
Off
Heartbeat1
Diagnostic Codes / Status of Furnace
No power to control or board fault detected
Control powered − displayed during all modes of operation if no errors are detected
1
Reverse Line Voltage Polarity
2
Improper Earth Ground
3
Burner failed to light, or lost flame during heat demand
4
Low Flame Signal − check flame sensor
5
Watchguard − burner failed to light, exceeded maximum number of retries or recycles.
6
Ignitor Circuit Failure − not available on this control
7
Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 minutes
8
Rollout Switch Open
9
Pressure Switch failed to close or opened during heat demand
10
Watchguard − Pressure Switch opened 5 times during one heat demand
11
Pressure Switch stuck closed prior to activation of combustion air inducer
12
Flame Sensed without gas valve energized
13
Low Line Voltage
Notes
Note1
A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating
Note
Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec
off, remains off for 3 sec, then repeats
Note
Last 10 error codes are stored in memory − To recall, press and release button, most recent will
be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes,
depress and hold button longer than 5 seconds.
Page 44
Troubleshooting: Heating Sequence of Operation
HEATING SEQUENCE OF OPERATION
ABNORMAL HEATING MODE
NORMAL HEATING MODE
POWER ON
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
LED SLOW FLASH
(RESET CONTROL BY TURNING MAIN POWER OFF.)
NO
CONTROL SELF−CHECK OKAY?
YES
NO
LED FLASHES CODE 1 − POLARITY REVERSED.
IS POLARITY CORRECT?
YES
NO
LED FLASHES CODE 2 − IMPROPER GROUND.
IS THERE A PROPER GROUND?
YES
NO
LED FLASHES CODE 13 − LOW LINE VOLTAGE.
CONTROL WILL NOT RESPOND TO A CALL FOR
HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
IS VOLTAGE
ABOVE 70 VOLTS?
YES
ROLLOUT SWITCH CLOSED?
LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES
AND POWER IS RESET OR T’STAT IS INTERRUPTED
FOR MINIMUM OF 1 SECOND.
NO
YES
BURNER OFF?
LED FLASHES CODE 12 − FLAME SENSED
WITHOUT GAS VALVE ENERGIZED.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
NO
(Flame sensed without gas valve energized)
YES
NO
NORMAL OPERATION:
LED SLOW FLASH
YES
THERMOSTAT CALLS FOR HEAT:
LED SLOW FLASH
NO
YES
LED FLASHES CODE 7 − PRIMARY LMIT
OPEN. COMBUSTION AIR INDUCER
OFF.INDOOR BLOWER ON
PRIMARY LIMIT SWITCH. CLOSED?
YES
NO
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
YES
LED FLASHES CODE 11 − PRESSURE
SWITCH CLOSED.
GAS VALVE OFF COMBUSTION AIR
INDUCER OFF. INDOOR BLOWER
OFF WITH DELAY.
(Sequence holds until pressure switch
opens or thermostat resets control.)
IS COMBUSTION AIR INDUCER
ENERGIZED?
YES
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
NO
YES
CONTINUED NEXT PAGE
Page 45
LED FLASHES CODE 9 − PRESSURE SWITCH FAILED
TO CLOSE OR OPENED DURING HEAT DEMAND.
PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS
VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE
RESET PERIOD COMPLETE?
YES
Troubleshooting: Heating Sequence of Operation (Continued)
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE
ABNORMAL HEATING MODE
15-SECOND COMBUSTION AIR INDUCER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
NO
IS VOLTAGE ABOVE 70 VOLTS?
IGNITOR WARM-UP −− 20 SECONDS.
YES
4-SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR
FIRST 3 SECONDS OF THE TRIAL.
YES
FLAME STABILIZATION PERIOD.
NO
YES
LED FLASHES CODE 13 −
LOW LINE VOLTAGE.
ONCE VOLTAGE IS ABOVE
75 VOLTS, HEATING
SEQUENCE RESTARTS.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER OFF.
HAS CONTROL FAILED TO SENSE FLAME FOR
NO
FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
NO
4 SECONDS
FLAME RECTIFICATION CURRENT
CHECK. CAN FLAME BE PROVEN WITHIN
4 SECONDS AFTER GAS VALVE OPENS?
(0.5 microamps)
YES
YES
NO
NO
HAS CONTROL RESET IGNITION
SEQUENCE FOUR TIMES?
FLAME PRESENT?
YES
YES
NO
FLAME SIGNAL 1.5 MICROAMPS OR GREATER?
YES
INDOOR BLOWER ON
AFTER 30−SECOND DELAY
YES
PRIMARY LIMIT SWITCH CLOSED?
YES
LED SIGNAL WATCHGUARD FAILURE CODE
WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY
IS 60-MINUTE RESET PERIOD COMPLETE?
LED FLASHES CODE 4 − LOW FLAME
SIGNAL.
(Does not affect operation of control)
LED FLASHES CODE 7 − PRIMARY LIMIT OPEN
GAS VALVE DE−ENERGIZED.
NO COMBUSTION AIR INDUCER DE−ENERGIZED.
INDOOR BLOWER ON UNTIL SWITCH CLOSES.
LIMIT SWITCH CLOSED?
YES
HAS PRIMARY LIMIT RESET
TIME EXCEEDED 3 MINUTES?
YES
YES
LED FLASHES CODE
7 − PRIMARY LIMIT
OPEN. GAS VALVE,
COMB. AIR INDUCER
AND INDOOR BLOWER OFF. LEDs SIGNAL LIMIT SWITCH
OPEN UNTIL MAIN
POWER IS
INTERRUPTED OR
T’STAT IS CYCLED
OFF/ON FOR 1 SEC.
MINIMUM. 60−MINUTE
WATCHGUARD PERIOD STARTS AT
TIME LIMIT CLOSES.
IS 60−MIN. PERIOD
COMPLETE?
NO
NO
ROLLOUT SWITCH CLOSED?
YES
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
YES
THERMOSTAT DEMAND SATISFIED.
YES
LED SLOW FLASH.
YES
COMB. AIR INDUCER CONTINUES 5-SECOND
POST PURGE AFTER T’STAT DEMAND IS SATISFIED.
INDOOR AIR BLOWER COMPLETES SELECTED OFF"
DELAY BEFORE SHUTTING OFF.
NO
LED FLASHES CODE 8 − ROLLOT SWITCH OPEN.
GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER
ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT
SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
HAS
GAS VALVE DE−ENERGIZED.
YES PRESSURE NO
COMBUSTION AIR INDUCER ON.
SWITCH
INDOOR BLOWER OFF WITH DELAY
OPENED 5
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
TIMES IN
SAME HEAT
NO
DEMAND?
5-MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
1 HR PRESSURE SWITCH
WATCHGUARD MODE
LED FLASHES CODE 10
Page 46
Troubleshooting: Cooling Sequence of Operation
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE
ABNORMAL COOLING MODE
POWER ON
IGNITION CONTROL MAIN POWER ON.
NO
CONTROL SELF DIAGNOSTIC CHECK.
IS CONTROL OPERATING NORMALLY?
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH NORMAL DELAY.
SIGNAL CIRCUIT BOARD FAILURE AT LED.
INTERRUPT MAIN POWER TO RESET CONTROL.
YES
NO
IS THERE A PROPER GROUND?
YES
NO
IS POLARITY CORRECT?
YES
LED FLASHES CODE 2 IMPROPER GROUND
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
LED FLASHES CODE 1 POLARITY REVERSED
CONTROL WILL CONTINUE TO CALL FOR COOLING IN
THIS CONDITION.
NO
LED FLASHES CODE 13 LOW VOLTAGE. CONTROL
WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION.
IS VOLTAGE
ABOVE 70 VOLTS?
YES
NO
ROLLOUT SWITCH MONITORED CONTINUOUSLY.
IS ROLLOUT SWITCH CLOSED?
YES
LED: SLOW FLASH RATE REMAINS UNCHANGED
THROUGHOUT COOLING CYCLE.
THERMOSTAT CALLS FOR COOLING.
COMPRESSOR CONTACTOR AND SYSTEM FAN
ENERGIZED WITH 2-SECOND DELAY
(COOLING SPEED). EAC TERM. ENERGIZED.
THERMOSTAT OPENS.
COMPRESSOR OFF.
SYSTEM FAN AND EAC TERM. OFF
WITH 45-SECOND DELAY.
Page 47
LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS
VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR
BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH
CLOSES AND MAIN POWER IS INTERRUPTED OR
THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM.
Troubleshooting: Continuous Fan Sequence of Operation
CONTINUOUS FAN SEQUENCE OF OPERATION
LED: SLOW FLASH RATE REMAINS
UNCHANGED THROUGHOUT SEQUENCE.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERMINAL IS ENERGIZED.
THERMOSTAT CALLS FOR HEAT (W).
YES
NO
THERMOSTAT CALLS FOR COOLING.
YES
SYSTEM FAN SWITCHED TO COOL SPEED.
EAC TERM. REMAINS ON.
NO
SYSTEM FAN CONTINUES FAN SPEED WITHOUT
INTERRUPTION. EAC TERMINAL REMAIN ON.
HUM TERMINAL IS ENERGIZED WITH COMBUSTION
AIR BLOWER.
SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30
SECOND DELAY. EAC AND HUM TERMINAL REMAIN ON.
THERMOSTAT OPENS.
MANUAL FAN SELECTION MADE AT THERMOSTAT.
CONTROL (G) ENERGIZES SYSTEM FAN AT FAN
SPEED. EAC TERM. ENERGIZED.
THERMOSTAT OPENS.
HUM. TERMINAL OFF AFTER POST PURGE
BY COMBUSTION AIR BLOWER. SYTEM FAN
SWITCHES TO FAN SPEED AFTER BLOWER
OFF DELAY. EAC CONTINUES WITHOUT
INTERRUPTION.
Page 48
Repair Parts List
The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model
number listed on the CSA nameplate −− Example: EL195DF04536B. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.
Heating Parts
Cabinet Parts
Outer access panel
Blower access panel
Top Cap
Control Panel Parts
Transformer
Integrated control board
Door interlock switch
Blower Parts
Blower wheel
Motor
Motor mounting frame
Motor capacitor
Blower housing cutoff plate
Flame Sensor
Heat exchanger assembly
Gas manifold
Combustion air inducer
Gas valve
Main burner cluster
Main burner orifices
Pressure switch
Ignitor
Primary limit control
Flame rollout switches
Page 49
Start−Up & Performance Check List
UNIT SET UP
Furnace:
Model Number_______________
Serial Number_________________
Line Voltage
SUPPLY
AIR
2
4
1
GAS SUPPLY
Natural Gas
LP Propane Gas
3
Piping Connections Tight
2
Leak Tested
Flter
Supply Line Pressure W.C.________
RETURN AIR
1
Gas Supply Pressure
3
1
DUCT SYSTEM
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
2
RETURN DUCT
INTAKE / EXHAUST PIPE
Sealed
All Joints Primed and Glued
Filter Installed and Clean
Terminations Installed Properly
Grilles Unobstructed
Horizontal Pipes Sloped (if applicable)
4
Condensate Trap Primed / Line Sloped
VOLTAGE CHECK
Supply Voltage _____
Electrical Connections Tight
Pipes Supported
Heat Cable Installed and Operable (if applicable)
Page 50
UNIT OPERATION
HEATING MODE
1
2
COOLING MODE
GAS MANIFOLD PRESSURE W.C._____
COMBUSTION SAMPLE CO2%______CO PPM_______
3
INDOOR BLOWER AMPS______
4
TEMPERATURE RISE
3
INDOOR BLOWER AMPS______
4
TEMPERATURE DROP
Return Duct Temperature _________
Supply Duct Temperature _ _______
Temperature Drop = _________
5
Supply Duct Temperature ________
Return Duct Temperature _ _____
Temperature Rise = ________
5
6
TOTAL EXTERNAL STATIC
Supply External Static _______
Return External Static + ______
Total External Static = _______
8
DRAIN LINE
Leak Free
9
CONDENSATE LINE
THERMOSTAT
Adjusted and Programmed
Leak Free
7
TOTAL EXTERNAL STATIC (dry coil)
Supply External Static _______
Return External Static + ______
Total External Static = _______
Explained Operation to Owner
VENT PIPE
Leak Free
Combustion CO2
2
7
SUPPLY
AIR
Thermostat
Temperatures
8
Gas Manifold Pressure
9
4
1
Blower Motor Amps
3
6
Duct Static
5
RETURN AIR
Contractor’s: Name_________________________Telephone_____________Checklist Completed____________________
Job Address_____−________________________________Technician’s Name___________________________________
Page 51
Requirements for Commonwealth of Massachusetts
Modifications to NFPA−54, Chapter 10
Revise NFPA−54 section 10.8.3 to add the following requirements:
For all side wall, horizontally vented, gas−fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1 − INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall, horizontally vented, gas−fueled equipment, the installing
plumber or gasfitter shall observe that a hard−wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gasfitter shall observe that a battery−operated or hard−wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas−fueled equipment. It shall be the
responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard−wired carbon monoxide detectors.
a − In the event that the side wall, horizontally vented,
gas−fueled equipment is installed in a crawl space
or an attic, the hard−wired carbon monoxide detector with alarm and battery back−up may be installed
on the next adjacent floor level.
b − In the event that the requirements of this subdivision cannot be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery−operated carbon monoxide detector with an alarm shall be installed.
2 − APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance with the above provisions shall comply with
NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3 − SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas−fueled heating appliance or
equipment. The sign shall read, in print size no less
than one−half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS."
4 − INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas−fueled equipment
shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1 − The equipment listed in Chapter 10 entitled Equipment Not Required to Be Vented" in the most current
edition of NFPA 54 as adopted by the Board; and
2 − Product Approved side wall, horizontally vented, gas−
fueled equipment installed in a room or structure separate from the dwelling, building or structure used in
whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS −
GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas−fueled equipment provides a venting system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
1 − Detailed instructions for the installation of the venting
system design or the venting system components:
and
2 − A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS −
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas−fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems," the following requirements shall be
satisfied by the manufacturer:
1 − The referenced special venting system" instructions
shall be included with the appliance or equipment
installation instructions; and
2
The special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas−fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at
the completion of the installation.
Page 52

advertisement

Related manuals

Download PDF

advertisement