- Home
- Domestic appliances
- Large home appliances
- Water heaters & boilers
- Lennox
- EL195
- Installation manual
advertisement
▼
Scroll to page 2
of
52
INSTALLATION INSTRUCTIONS EL195DF 2011 Lennox Industries Inc. Dallas, Texas, USA ELITE® SERIES GAS FURNACE DOWNFLOW AIR DISCHARGE 506594−01 02/2011 Supersedes 01/2011 Litho U.S.A. THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death. CAUTION As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment. WARNING DOWNFLOW Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier. AIR FLOW Table of Contents Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EL195DF Parts Arrangement . . . . . . . . . . . . . . . . . . . . . EL195DF Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . Shipping and Packing List . . . . . . . . . . . . . . . . . . . . . . . . Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Use of Furnace as a Construction Heater . . . . . . . . . . . General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Combustion, Dilution and Ventilation Air . . . . . . . . . . . . Setting Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pipe and Fittings Specifications . . . . . . . . . . . . . . . . . . . Joint Cementing Procedure . . . . . . . . . . . . . . . . . . . . . . . Venting Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 3 4 4 4 5 6 6 9 12 12 12 14 14 506594−01 02/11 *2P0211* Vent Piping Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unit Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Pressure Measurement . . . . . . . . . . . . . . . . . . . . . . Proper Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Altitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Testing Non Direct Appliances for Proper Air . . . . . . . . Other Unit Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . Blower Motor Performance . . . . . . . . . . . . . . . . . . . . . . . Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Planned Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Control Diagnostic Codes . . . . . . . . . . . . . . . Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Repair Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Start Up Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 15 30 32 36 38 38 38 39 40 41 42 44 44 45 49 50 *P506594-01* EL195DF Unit Dimensions − inches (mm) 9/16 (14) COMBUSTION AIR INTAKE RETURN AIR OPENING B EXHAUST AIR OUTLET 2−1/16 (52) 5 (127) 27−3/4 (705) 19−7/16 (494) 9/16 (14) B ELECTRICAL INLET (Either Side) 2 (51) Either Side CONDENSATE TRAP CONNECTION (Either Side) GAS PIPING INLET (Either Side) 9−1/8 (232) Right 6−9/16 (167) Left C Supply Air 6−7/16 (163) Either Side 9 (229) Either Side 19−1/4 Supply (489) Air 3/4 (19) FRONT VIEW Model No. 9/16 (14) FLOW 33 (838) 3/4 (19) TOP VIEW 1−1/2 (38) Front Panel A AIR 9/16 (14) 2−1/4 (57) 3/4 (19) SIDE VIEW A B C in. mm in. mm in. mm EL195DF045P36B EL195DF070P48B 17−1/2 446 16−3/8 416 16 406 EL195DF090P60C EL195DF110P60C 21 533 19−7/8 505 19−1/2 495 Page 2 EL195DF Parts Arrangement BLOWER MOTOR (hidden) CONTROL BOX (Includes integrated control, transformer and door switch) BAG ASSEMBLY (shipping location) COMBUSTION AIR INDUCER BLOWER DECK DuralokPlusTM HEAT EXCHANGER ASSEMBLY OUTER ACCESS PANEL COLD END HEADER BOX COMBUSTION AIR INDUCER PRESSURE SWITCH PRIMARY LIMIT BURNER BOX ASSEMBLY (includes sensor, rollout switches and ignitor) GAS VALVE FIGURE 1 Page 3 Check equipment for shipping damage. If you find any damage, immediately contact the last carrier. EL195DF Gas Furnace The EL195DF Category IV gas furnace is shipped ready for installation in the downflow position. The furnace is equipped for installation in natural gas applications. A conversion kit (ordered separately) is required for use in propane/LP gas applications. The EL195DF can be installed as a Direct Vent or Non− Direct Vent gas central furnace. NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. See figure 2 for applications involving roof termination. DIRECT VENT INSTALLATION COMBUSTION AIR INTAKE OUTSIDE OF HOUSE NON−DIRECT VENT INSTALLATION EXHAUST OUTLET The following items may also be ordered separately: 1 − Thermostat 1 − LP/Propane changeover kit 1 − High altitude pressure switch Safety Information WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier. EXHAUST OUTLET CAUTION As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment. COMBUSTION AIR INTAKE INSIDE OF HOUSE EL195DF EL195DF FIGURE 2 Shipping and Packing List Package 1 of 1 contains 1 − Assembled EL195DF unit 1 − Bag assembly containing the following: 3 − Wire nuts 1 − Snap bushing 1 − Snap plug 1 − Wire tie 1 − Condensate trap 1 − Condensate trap cap 1 − Condensate trap clamp 1 − 2" diameter Air intake screen DANGER Danger of explosion. There are circumstances in which odorant used with LP/propane gas can lose its scent. In case of a leak, LP/propane gas will settle close to the floor and may be difficult to smell. An LP/propane leak detector should be installed in all LP applications. Use only the type of gas approved for use with this furnace. Refer to unit nameplate. EL195DF units are CSA International certified to ANSI Z21.47 and CSA 2.3 standards. Building Codes In the USA, installation of gas furnaces must conform with local building codes. In the absence of local codes, units must be installed according to the current National Fuel Gas Code (ANSI-Z223.1/NFPA 54). The National Fuel Gas Code is available from the following address: American National Standards Institute, Inc. 11 West 42nd Street New York, NY 10036 In Canada, installation must conform with current National Standard of Canada CSA-B149 Natural Gas and Propane Installation Codes, local plumbing or waste water codes and other applicable local codes. In order to ensure proper unit operation in non−direct vent applications, combustion and ventilation air supply must be provided according to the current National Fuel Gas Code or CSA-B149 standard. Locations and Clearances This furnace is CSA International certified for installation clearances to combustible material as listed on the unit nameplate and in the table in figure 10. Accessibility and service clearances must take precedence over fire protection clearances. For installation in a residential garage, the furnace must be installed so that the burner(s) and the ignition source are located no less than 18 inches (457 mm) above the floor. The furnace must be located or protected to avoid physical damage by vehicles. When a furnace is installed Page 4 in a public garage, hangar, or other building that has a hazardous atmosphere, the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CSA B149 standards. NOTE − Furnace must be adjusted to obtain a temperature rise within the range specified on the unit nameplate. Failure to do so may cause erratic limit operation and premature heat exchanger failure. This EL195DF furnace must be installed so that its electrical components are protected from water. Installation in Combination with a Cooling Coil When this furnace is used with cooling units (figure 3), it shall be installed in parallel with, or on the upstream side of, cooling units to avoid condensation in the heating compartment. With a parallel flow arrangement, a damper (or other means to control the flow of air) must adequately prevent chilled air from entering the furnace. If the damper is manually operated, it must be equipped to prevent operation of either the heating or the cooling unit, unless it is in the full HEAT or COOL setting. When installed, this furnace must be electrically grounded according to local codes. In addition, in the United States, installation must conform with the current National Electric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available from the following address: National Fire Protection Association 1 Battery March Park Quincy, MA 02269 In Canada, all electrical wiring and grounding for the unit must be installed according to the current regulations of the Canadian Electrical Code Part I (CSA Standard C22.1) and/or local codes. Heating Unit Installed Parallell to Air Handler Unit NOTE − This furnace is designed for a minimum continuous return air temperature of 60°F (16°C) or an intermittent operation down to 55°F (13°C) dry bulb for cases where a night setback thermostat is used. Return air temperature must not exceed 85°F (29°C) dry bulb. The EL195DF furnace may be installed in alcoves, closets, attics, basements, garages, utility rooms and crawl spaces. This furnace design has not been CSA certified for installation in mobile homes, recreational vehicles, or outdoors. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Use of Furnace as Construction Heater Lennox does not recommend the use of EL195DF units as a construction heater during any phase of construction. Very low return air temperatures, harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit. EL195DF units may be used for heating of buildings or structures under construction, if the following conditions are met: • The vent system must be permanently installed per these installation instructions. • A room thermostat must control the furnace. The use of fixed jumpers that will provide continuous heating is not allowed. • The return air duct must be provided and sealed to the furnace. • Return air temperature range between 60°F (16°C) and 80°F (27°C) must be maintained. • Air filters must be installed in the system and must be maintained during construction. • Air filters must be replaced upon construction completion. • The input rate and temperature rise must be set per the furnace rating plate. AIR HANDLER GAS UNIT • One hundred percent (100%) outdoor air must be provided for combustion air requirements during construction. Temporary ducting may supply outdoor air to the furnace. Do not connect duct directly to the furnace. Size the temporary duct following these instructions in section for Combustion, Dilution and Ventilation Air in a confined space with air from outside. Dampers Dampers (open during cooling operation only) (open during heating operation only) • The furnace heat exchanger, components, duct system, air filters and evaporator coils must be thoroughly cleaned following final construction clean−up. • All furnace operating conditions (including ignition, input rate, temperature rise and venting) must be verified according to these installation instructions. FIGURE 3 Page 5 General These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities having jurisdiction before installation. In addition to the requirements outlined previously, the following general recommendations must be considered when installing a EL195DF furnace: • Place the furnace as close to the center of the air distribution system as possible. The furnace should also be located close to the chimney or vent termination point. • When the furnace is installed in non−direct vent applications, do not install the furnace where drafts might blow directly into it. This could cause improper combustion and unsafe operation. • When the furnace is installed in non−direct vent applications, do not block the furnace combustion air opening with clothing, boxes, doors, etc. Air is needed for proper combustion and safe unit operation. • When the furnace is installed in an attic or other insulated space, keep insulation away from the furnace. • When the furnace is installed in an unconditioned space, consider provisions required to prevent freezing of condensate drain system. CAUTION EL195DF unit should not be installed in areas normally subject to freezing temperatures. WARNING Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool. Breathing this may cause lung cancer. (Fiberglass wool is known to the State of California to cause cancer.) Fiberglass wool may also cause respiratory, skin, and eye irritation. To reduce exposure to this substance or for further information, consult material safety data sheets available from address shown below, or contact your supervisor. Lennox Industries Inc. P.O. Box 799900 Dallas, TX 75379−9900 Combustion, Dilution & Ventilation Air WARNING Insufficient combustion air can cause headaches, nausea, dizziness or asphyxiation. It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure. Excessive exposure to contaminated combustion air will result in safety and performance related problems. Avoid exposure to the following substances in the combustion air supply: Permanent wave solutions Chlorinated waxes and cleaners Chlorine base swimming pool chemicals Water softening chemicals De−icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (such as perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners for clothes dryers Masonry acid washing materials In the past, there was no problem in bringing in sufficient outdoor air for combustion. Infiltration provided all the air that was needed. In today’s homes, tight construction practices make it necessary to bring in air from outside for combustion. Take into account that exhaust fans, appliance vents, chimneys, and fireplaces force additional air that could be used for combustion out of the house. Unless outside air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a downdraft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation. In the absence of local codes concerning air for combus− tion and ventilation, use the guidelines and procedures in this section to install EL195DF furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas pip−ing. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI− Z223.1/NFPA 54). This reprinted material is not the complete and official position of the ANSI on the referenced subject, which is represented only by the standard in its entirety. In Canada, refer to the CSA B149 installation codes. If the EL195DF is installed as a Non−Direct Vent Furnace, follow the guidelines in this section. NOTE − In Non−Direct Vent installations, combustion air is taken from indoors and flue gases are discharged out− doors. CAUTION Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes. Page 6 All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel−burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a downdraft. Insufficient air causes incomplete combustion which can result in carbon monoxide. In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components. The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space. dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside. Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of total input rating of all gas−fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm2). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See figure 4. EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE ROOF TERMINATED EXHAUST PIPE Unconfined Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the air from outside section. Confined Space A confined space is an area with a volume less than 50 cubic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com− bined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms. When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially Page 7 SIDE WALL TERMINATED EXHAUST PIPE (ALTERNATE LOCATION) OPENINGS (To Adjacent Unconfined Space) NOTE − Each opening shall have a free area of at least one square inch per 1,000 Btu (645mm 2 per .29kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64516mm. 2). FIGURE 4 Air from Outside If air from outside is brought in for combustion and ventilation, the confined space shall be provided with two permanent openings. One opening shall be within 12" (305mm) of the top of the enclosure and one within 12" (305mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch per 4,000 Btu (645mm2 per 1.17kW) per hour of total input rating of all equipment in the enclosure. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu (645mm2 per .59kW) per total input rating of all equipment in the enclosure (See figure 5). EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE (Inlet Air from Crawl Space and Outlet Air to Ventilated Attic) VENTILATION LOUVERS (Each end of attic) ROOF TERMINATED EXHAUST PIPE EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE (All Air Through Ventilated Attic) ROOF TERMINATED EXHAUST PIPE VENTILATION LOUVERS (Each end of attic) OUTLET AIR OUTLET AIR SIDE WALL TERMINATED EXHAUST PIPE (ALTERNATE LOCATION) INLET AIR VENTILATION LOUVERS (For unheated crawl space) NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure. INLET AIR (Ends 12" above bottom) SIDE WALL TERMINATED EXHAUST PIPE (ALTERNATE LOCATION) NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all equipment in the enclosure. FIGURE 6 FIGURE 5 If air from outside is brought in for combustion and ventilation, the confined space must have two permanent openings. One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. These openings must communicate directly or by ducts with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors or indirectly through vertical ducts. Each opening shall have a minimum free area of 1 square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of total input rating of all equipment in the enclosure. See figures 5 and 6. When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch (645 mm2) per 2,000 Btu (.56 kW) per total input rating of all equipment in the enclosure. See figure 7. When ducts are used, they shall be of the same cross−sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be no less than 3 inches (75 mm). In calculating free area, the blocking effect of louvers, grilles, or screens must be considered. If the design and free area of protective covering is not known for calculating the size opening required, it may be assumed that wood louvers will have 20 to 25 percent free area and metal louvers and grilles will have 60 to 75 percent free area. Louvers and grilles must be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation. EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE ROOF TERMINATED EXHAUST PIPE OUTLET AIR SIDE WALL TERMINATED EXHAUST PIPE (ALTERNATE LOCATION) INLET AIR NOTE−Each air duct opening shall have a free area of at least one square inch per 2,000 Btu (645mm2 per .59kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each opening shall have a free area of at least 1 square inch per 4,000 Btu (645mm 2 per 1.17kW) per hour of the total input rating of all other equipment in the enclosure. FIGURE 7 Page 8 Installation − Setting Equipment SETTING EQUIPMENT Unit must be level side−to−side. Unit may be positioned from level to 1/2" toward the front to aid in draining. WARNING Do not install the furnace on its front, back or in the horizontal position. See figure 9. Do not connect the return air ducts to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal injury or death. Select a location that allows for the required clearances that are listed on the unit nameplate. Also consider gas supply connections, electrical supply, vent connection, condensate trap and drain connections, and installation and service clearances [24 inches (610 mm) at unit front]. The unit must be level from side to side. Unit may be positioned from level to 1/2" toward the front to aid in draining. See figure 8. Allow for clearances to combustible materials as indicated on the unit nameplate. Minimum clearances for closet or alcove installations are shown in figure 10. AIR FLOW AIR FLOW UNIT FRONT UNIT FRONT 1/2" max. SIDE VIEW SIDE VIEW AIR FLOW WARNING Blower access panel must be securely in place when blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death. Front Back FRONT VIEW FIGURE 8 Horizontal NOTE − Do not install the furnace on its front, back or in the horizontal position FIGURE 9 Page 9 Installation on Non−Combustible Flooring Figure 11 WARNING 1 − Cut floor opening keeping in mind clearances listed on unit rating plate. Also keep in mind gas supply connections, electrical supply, flue and air intake connections and sufficient installation and servicing clearances. See table 1 for correct floor opening size. 2 − Flange warm air plenum and lower the plenum into the opening. 3 − Set the unit over the plenum and seal the plenum to the unit. 4 − Ensure that the seal is adequate. Improper installation of the furnace can result in personal injury or death. Combustion and flue products must never be allowed to enter the return air system or air in the living space. Use sheet metal screws and joint tape to seal return air system to furnace. In platform installations with furnace return, the furnace should be sealed airtight to the return air plenum. A door must never be used as a portion of the return air duct system. The base must provide a stable support and an airtight seal to the furnace. Allow absolutely no sagging, cracks, gaps, etc. For no reason should return and supply air duct systems ever be connected to or from other heating devices such as a fireplace or stove, etc. Fire, explosion, carbon monoxide poisoning, personal injury and/or property damage could result. TABLE 1 NON−COMBUSTIBLE FLOOR OPENING SIZE Front to Rear Cabinet Width The unit may be installed three ways in downflow applications: on non−combustible flooring, on combustible flooring using an additive base, or on a reverse−flow cooling coil cabinet. Do not drag the unit across the floor in the downflow position. Floor and furnace flange damage will result. Refer to figure 10 for clearances in downflow applications. Side to Side in. mm in. mm B Cabinet (17.5") 19 − 3/4 502 16 − 5/8 422 C Cabinet (21") 19 − 3/4 502 20−1/8 511 NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger than the unit opening. See dimension drawing on page 2. Downflow Application Installation Clearances FURNACE Top Left Side PROPERLY SIZED FLOOR OPENING Right Side SUPPLY AIR PLENUM Bottom Top 0 *Front 0 Back 0 Sides 0† Vent 0 Floor NC‡ *Front clearance in alcove installation must be 24 in. (610 mm). Maintain a minimum of 24 in. (610 mm) for front service access. †Allow proper clearances to accommodate condensate trap and vent pipe installation. ‡The furnace may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustible floor. FIGURE 10 FIGURE 11 Installation on Combustible Flooring Figure 12 1 − When unit is installed on a combustible floor, a downflow combustible flooring base must be installed between the furnace and the floor. The base must be ordered separately. See table 2 for opening size to cut in floor. CAUTION The furnace and combustible flooring base shall not be installed directly on carpeting, tile, or other combustible material other than wood flooring. Page 10 TABLE 2 COMBUSTIBLE FLOORING BASE OPENING SIZE Cabinet Width Catalog Number B Cabinet (17.5") C Cabinet (21") Front to Rear Side to Side FURNACE in. mm in. mm 11M60 22 559 18 − 3/4 476 11M61 22 559 22 − 3/4 578 COOLING COIL PROPERLY SIZED FLOOR OPENING PLENUM FURNACE SUPPLY AIR PLENUM PROPERLY SIZED FLOOR OPENING COMBUSTIBLE FLOORING BASE FIGURE 13 Return Air Opening −− Downflow Units Return air may be brought in only through the top opening of a furnace installed in the downflow position. The following steps should be taken when installing plenum: 1 − Bottom edge of plenum should be flanged with a hemmed edge (See figure 14 or 15). FIGURE 12 2 − After opening is cut, set the combustible flooring base into opening. 3 − Check fiberglass strips on the combustible flooring base to make sure they are properly glued and positioned. 4 − Lower supply air plenum into the combustible flooring base until plenum flanges seal against fiberglass strips. NOTE − Be careful not to damage fiberglass strips. Check for a tight seal. 5 − Set the furnace over the plenum. 2 − Sealing strips should be used to ensure an airtight seal between the cabinet and the plenum. 3 − In all cases, plenum should be secured to top of furnace using sheet metal screws. 4 − Make certain that an adequate seal is made. PLENUM (Field Provided) SEALING STRIP (Field Provided) SECURE FROM OUTSIDE CABINET ÉÉÉÉ CABINET SIDE PANEL Side View 6 − Ensure that the seal between the furnace and plenum is adequate. Installation on Cooling Coil Cabinet Figure 13 NOTE − Downflow combustible flooring kit is not used. FIGURE 14 PLENUM (Field Provided) 1 − Refer to reverse−flow coil installation instructions for correctly sized opening in floor and installation of cabinet. 2 − When cooling cabinet is in place, set and secure the furnace according to the instructions that are provided with the cooling coil. Secure the furnace to the cabinet. SECURE FROM INSIDE CABINET ÉÉÉÉ Side View FIGURE 15 3 − Seal the cabinet and check for air leaks. Page 11 SEALING STRIP (Field Provided) CABINET SIDE PANEL Filters Pipe & Fittings Specifications This unit is not equipped with a filter or rack. A field−provided filter is required for the unit to operate properly. Table 3 lists recommended minimum filter size. A filter must be in place whenever the unit is operating. TABLE 3 Furnace Cabinet Width Minimum Filter Size 17−1/2" 16 x 25 x 1 (1) All pipe, fittings, primer and solvent cement must conform with American National Standard Institute and the American Society for Testing and Materials (ANSI/ASTM) standards. The solvent shall be free flowing and contain no lumps, undissolved particles or any foreign matter that adversely affects the joint strength or chemical resistance of the cement. The cement shall show no gelation, stratification, or separation that cannot be removed by stirring. Refer to the table 4 below for approved piping and fitting materials. 21" CAUTION Duct System Use industry-approved standards to size and install the supply and return air duct system. Refer to ACCA Manual D. This will result in a quiet and low-static system that has uniform air distribution. NOTE − This furnace is not certified for operation in heating mode (indoor blower operating at selected heating speed) with an external static pressure which exceeds 0.5 inches w.c. Operation at these conditions may result in improper limit operation. Supply Air Plenum If the furnace is installed without a cooling coil, a removable access panel should be installed in the supply air duct. The access panel should be large enough to permit inspection of the heat exchanger. The furnace access panel must always be in place when the furnace is operating and it must not allow leaks into the supply air duct system. Return Air Plenum NOTE − Return air must not be drawn from a room where this furnace, or any other gas−fueled appliance (i.e., water heater), or carbon monoxide−producing device (i.e., wood fireplace) is installed. When return air is drawn from a room, a negative pressure is created in the room. If a gas appliance is operating in a room with negative pressure, the flue products can be pulled back down the vent pipe and into the room. This reverse flow of the flue gas may result in incomplete combustion and the formation of carbon monoxide gas. This raw gas or toxic fumes might then be distributed throughout the house by the furnace duct system. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the furnace cabinet to ensure a tight seal. If a filter is installed, size the return air duct to fit the filter frame. Solvent cements for plastic pipe are flammable liquids and should be kept away from all sources of ignition. Do not use excessive amounts of solvent cement when making joints. Good ventilation should be maintained to reduce fire hazard and to minimize breathing of solvent vapors. Avoid contact of cement with skin and eyes. TABLE 4 PIPING AND FITTINGS SPECIFICATIONS Schedule 40 PVC (Pipe) Schedule 40 PVC (Cellular Core Pipe) D1785 F891 Schedule 40 PVC (Fittings) D2466 Schedule 40 CPVC (Pipe) F441 Schedule 40 CPVC (Fittings) SDR−21 PVC or SDR−26 PVC (Pipe) SDR−21 CPVC or SDR−26 CPVC (Pipe) Schedule 40 ABS Cellular Core DWV (Pipe) F438 D2241 F442 F628 Schedule 40 ABS (Pipe) D1527 Schedule 40 ABS (Fittings) D2468 ABS−DWV (Drain Waste & Vent) (Pipe & Fittings) D2661 PVC−DWV (Drain Waste & Vent) Pipe & Fittings) D2665 PRIMER & SOLVENT CEMENT PVC & CPVC Primer PVC Solvent Cement CPVC Solvent Cement ABS Solvent Cement ASTM SPECIFICATION F656 D2564 F493 D2235 PVC/CPVC/ABS All Purpose Cement For Fittings & Pipe of the same material D2564, D2235, F493 ABS to PVC or CPVC Transition Solvent Cement D3138 CANADA PIPE & FITTING & SOLVENT CEMENT PVC & CPVC Pipe and Fittings PVC & CPVC Solvent Cement ABS to PVC or CPVC Transition Cement Page 12 MARKING ULCS636 Low temperature solvent cement is recommended during cooler weather. Metal or plastic strapping may be used for vent pipe hangers. Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket. IMPORTANT EL195DF exhaust and intake connections are made of PVC. Use PVC primer and solvent cement when using PVC vent pipe. When using ABS vent pipe, use transitional solvent cement to make connections to the PVC fittings in the unit. Canadian Applications Only − Pipe, fittings, primer and solvent cement used to vent (exhaust) this apUse PVC primer and solvent cement or ABS solvent cement pliance must be certified to ULC S636 and supplied by a meeting ASTM specifications, refer to Table 4. As an altersingle manufacturer as part of an approved vent (exnate, use all purpose cement, to bond ABS, PVC, or CPVC haust) system. In addition, the first three feet of vent pipe when using fittings and pipe made of the same materipipe from the furnace flue collar must be accessible for als. Use transition solvent cement when bonding ABS to eiinspection. ther PVC or CPVC. TABLE 5 OUTDOOR TERMINATION KITS USAGE STANDARD EL195 UNIT 045 070 090 110 VENT PIPE DIA. (in.) CONCENTRIC Outdoor Exhaust Accelerator (Dia. X Length) Outdoor Exhaust Accelerator (Dia. X Length) 2" Wall Plate Kit 3" Wall Plate Kit 2" Wall Ring Kit FlushMount Kit 1−1/2" Concentric Kit 2" Concentric Kit 3" Concentric Kit 1−1/2" X 12" 2" X 12" 22G44 or 30G28 44J40 or 81J20 15F74 51W11** 71M80 or 44W92 69M29 or 44W92 60L46 or 44W93 2 YES YES YES* YES YES YES 2−1/2 YES YES YES* YES YES YES 3 YES YES YES* YES YES YES 2 YES YES YES* YES YES YES 2−1/2 YES YES YES* YES YES YES 3 YES YES YES* YES YES YES 2 YES YES YES YES YES YES 2−1/2 YES YES YES YES YES YES 3 YES YES YES YES YES YES 3 YES YES YES YES YES YES *Requires field−provided and installed 1−1/2" exhaust accelerator. ** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all EL195DF−045, −070 and −090 installations. Termination kits 44W92, 44W93, 30G28 and 81J20 approved for use in Canadian installations to meet CSAB149. The 44W92 Concentric kit is provided with a 1−1/2" accelerator which must be installed on the exhaust outlet when this kit is used with the EL195DF045P36B and EL195DF070P36B furnaces. Page 13 Venting Practices Joint Cementing Procedure All cementing of joints should be done according to the specifications outlined in ASTM D 2855. Piping Suspension Guidelines SCHEDULE 40 PVC − 5’ all other pipe* − 3’ NOTE − A sheet metal screw may be used to secure the intake pipe to the connector, if desired. Use a drill or self tapping screw to make a pilot hole. DANGER * See table 4 for allowable pipe. DANGER OF EXPLOSION! NOTE − Isolate piping at the point where it exits the outside wall or roof in order to prevent transmission of vibration to the structure. Fumes from PVC glue may ignite during system check. Allow fumes to dissipate for at least 5 minutes before placing unit into operation. Wall Thickness Guidelines 24" maximum 3/4" minimum 1 − Measure and cut vent pipe to desired length. 2 − Debur and chamfer end of pipe, removing any ridges or rough edges. If end is not chamfered, edge of pipe may remove cement from fitting socket and result in a leaking joint. inside Wall outside NOTE − Check the inside of vent pipe thoroughly for any obstruction that may alter furnace operation. 3 − Clean and dry surfaces to be joined. 4 − Test fit joint and mark depth of fitting on outside of pipe. FIGURE 16 5 − Uniformly apply a liberal coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket. 6 − Promptly apply solvent cement to end of pipe and inside socket surface of fitting. Cement should be applied lightly but uniformly to inside of socket. Take care to keep excess cement out of socket. Apply second coat to end of pipe. NOTE − Time is critical at this stage. Do not allow primer to dry before applying cement. CHIMNEY OR GAS VENT (Check sizing for water heater only) FURNACE (Replaced by EL193) If an EL195DF furnace replaces a furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance. NOTE − Assembly should be completed within 20 seconds after last application of cement. Hammer blows should not be used when inserting pipe. 9 − Handle joints carefully until completely set. WATER HEATER OPENINGS (To Adjacent Room) 7 − Immediately after applying last coat of cement to pipe, and while both inside socket surface and end of pipe are wet with cement, forcefully insert end of pipe into socket until it bottoms out. Turn PVC pipe 1/4 turn during assembly (but not after pipe is fully inserted) to distribute cement evenly. DO NOT turn ABS or cellular core pipe. 8 − After assembly, wipe excess cement from pipe at end of fitting socket. A properly made joint will show a bead around its entire perimeter. Any gaps may indicate an improper assembly due to insufficient solvent. REPLACING FURNACE THAT WAS PART OF A COMMON VENT SYSTEM FIGURE 17 1 − In areas where piping penetrates joists or interior walls, hole must be large enough to allow clearance on all sides of pipe through center of hole using a hanger. Page 14 2 − When furnace is installed in a residence where unit is shut down for an extended period of time, such as a vacation home, make provisions for draining condensate collection trap and lines. Exhaust Piping (Figures 19 and 20) Route piping to outside of structure. Continue with installation following instructions given in piping termination section. CAUTION Do not discharge exhaust into an existing stack or stack that also serves another gas appliance. If vertical discharge through an existing unused stack is required, insert PVC pipe inside the stack until the end is even with the top or outlet end of the metal stack. CAUTION Use the following steps to correctly size vent pipe diameter. 045, 070, 090 or 110 1 Furnace capacity? 2 Which termination? 3 Which needs most elbows? 4 How many? Standard or Concentric? See table 5 Intake or exhaust The exhaust vent pipe operates under positive pressure and must be completely sealed to prevent leakage of combustion products into the living space. Vent Piping Guidelines The EL195DF can be installed as either a Non−Direct Vent or a Direct Vent gas central furnace. NOTE − In Non-Direct Vent installations, combustion air is taken from indoors and flue gases are discharged outdoors. In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged outdoors. Intake and exhaust pipe sizing −− Size pipe according to tables 6 and 7. Table 6 lists the minimum vent pipe lengths permitted. Table 7 lists the maximum pipe lengths permitted. TABLE 6 MINIMUM VENT PIPE LENGTHS EL195DF MODEL MIN. VENT LENGTH* 045, 070, 090, 110 15 ft. or 5 ft plus 2 elbows or 10 ft plus 1 elbow *Any approved termination may be added to the minimum length listed. Regardless of the diameter of pipe used, the standard roof and wall terminations described in section Exhaust Piping Terminations should be used. Exhaust vent termination pipe is sized to optimize the velocity of the exhaust gas as it exits the termination. Refer to table 8. In some applications which permit the use of several different sizes of vent pipe, a combination vent pipe may be used. Contact Lennox’ Application Department for assistance in sizing vent pipe in these applications. IMPORTANT Do not use screens or perforated metal in exhaust or intake terminations. Doing so will cause freeze−ups and may block the terminations. Page 15 5 Desired pipe size? 6 What is the altitude? 7 Use table 7 to find max intake or exhaust pipe length. 2", 2−1/2" or 3" FIGURE 18 NOTE − It is acceptable to use any pipe size which fits within the guidelines allowed in table 7. NOTE − All horizontal runs of exhaust pipe must slope back toward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm) of horizontal run is mandatory for drainage. NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings. NOTE − Exhaust piping should be checked carefully to make sure there are no sags or low spots. TABLE 7 Maximum Allowable Intake or Exhaust Vent Length *Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size. Number Of 90° Elbows Used 1 2 3 4 5 6 7 8 9 10 Number Of 90° Elbows Used 1 2 3 4 5 6 7 8 9 10 Number Of 90° Elbows Used 1 2 3 4 5 6 7 8 9 10 Number Of 90° Elbows Used 1 2 3 4 5 6 7 8 9 10 045 81 76 71 66 61 56 51 46 41 36 2" Pipe Model 070 090 66 44 61 39 56 34 51 29 46 24 41 19 36 14 31 n/a 26 n/a 21 n/a 045 81 76 71 66 61 56 51 46 41 36 2" Pipe Model 070 090 66 44 61 39 56 34 51 29 46 24 41 19 36 14 31 n/a 26 n/a 21 n/a 045 73 68 63 58 53 48 43 38 33 28 045 73 68 63 58 53 48 43 38 33 28 Standard Termination at Elevation 0 − 4500 ft 2−1/2" Pipe Model 110 045 070 090 110 24 115 115 93 58 19 110 110 88 53 14 105 105 83 48 n/a 100 100 78 43 n/a 95 95 73 38 n/a 90 90 68 33 n/a 85 85 63 28 n/a 80 80 58 23 n/a 75 75 53 18 n/a 70 70 48 13 Standard Termination Elevation 4500 − 10,000 ft 2−1/2" Pipe Model 110 045 070 090 110 n/a 115 115 93 58 n/a 110 110 88 53 n/a 105 105 83 48 n/a 100 100 78 43 n/a 95 95 73 38 n/a 90 90 68 33 n/a 85 85 63 28 n/a 80 80 58 23 n/a 75 75 53 18 n/a 70 70 48 13 Concentric Termination at Elevation 0 − 4500 ft 2" Pipe 2−1/2" Pipe Model Model 070 090 110 045 070 090 110 58 42 22 105 105 89 54 53 37 17 100 100 84 49 48 32 12 95 95 79 44 43 27 90 90 74 39 38 22 85 85 69 34 33 17 80 80 64 29 28 12 75 75 59 24 n/a 23 70 70 54 19 18 65 65 49 14 n/a 13 60 60 44 n/a Concentric Termination Elevation 4501 − 10,000 ft 2" Pipe 2−1/2" Pipe Model Model 070 090 110 045 070 090 110 58 42 105 105 89 54 53 37 100 100 84 49 48 32 95 95 79 44 43 27 90 90 74 39 38 22 85 85 69 34 n/a 33 17 80 80 64 29 28 12 75 75 59 24 23 70 70 54 19 18 65 65 49 14 n/a 13 60 60 44 n/a Page 16 045 138 133 128 123 118 113 108 103 98 93 3" Pipe Model 070 090 137 118 132 113 127 108 122 103 117 98 112 93 107 88 102 83 97 78 92 73 110 118 113 108 103 98 93 88 83 78 73 045 138 133 128 123 118 113 108 103 98 93 3" Pipe Model 070 090 137 118 132 113 127 108 122 103 117 98 112 93 107 88 102 83 97 78 92 73 110 118 113 108 103 98 93 88 83 78 73 045 121 116 111 106 101 96 91 86 81 76 3" Pipe Model 070 090 121 114 116 109 111 104 106 99 101 94 96 89 91 84 86 79 81 74 76 69 110 114 109 104 99 94 89 84 79 74 69 045 121 116 111 106 101 96 91 86 81 76 3" Pipe Model 070 090 121 114 116 109 111 104 106 99 101 94 96 89 91 84 86 79 81 74 76 69 110 114 109 104 99 94 89 84 79 74 69 TYPICAL EXHAUST PIPE CONNECTIONS Pipe size determined in table 7. 2” 2” 2” 2” 2” or 3” TRANSITION *2” INTAKE DO NOT transition from smaller to larger pipe size in horizontal runs of exhaust pipe. EXHAUST TOP VIEW * When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible. NOTE − Exhaust pipe and intake pipe must be the same diameter. FIGURE 19 TYPICAL INTAKE PIPE CONNECTIONS Pipe size determined in table 7. 2” 2” 2” 2” 2” or TRANSITION 3” *2” *2” 3” TRANSITION *2” INTAKE EXHAUST TOP VIEW * When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible. NOTE − Intake pipe and exhaust pipe must be the same diameter. FIGURE 20 Page 17 Intake Piping The EL195DF furnace may be installed in either direct vent or non−direct vent applications. In non−direct vent applications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered. Guidelines listed in Combustion, Dilution and Ventilation Air section must be followed. Follow the next two steps when installing the unit in Direct Vent applications, where combustion air is taken from outdoors and flue gases are discharged outdoors. The provided air intake screen must not be used in direct vent applications (outdoors). 1 − Use cement to secure the intake pipe to the inlet air connector. 2 − Route piping to outside of structure. Continue with installation following instructions given in general guide lines for piping terminations and intake and exhaust piping terminations for direct vent sections. Refer to table 7 for pipe sizes. TYPICAL AIR INTAKE PIPE CONNECTIONS NON−DIRECT VENT APPLICATIONS AIR INTAKE SCREEN (Provided) NOTE − Air intake screen and elbow may be rotated, so that screen may be positioned to face forward or to either side. General Guidelines for Vent Terminations In Non-Direct Vent applications, combustion air is taken from indoors and the flue gases are discharged to the outdoors. The EL195DF is then classified as a non-direct vent, Category IV gas furnace. In Direct Vent applications, combustion air is taken from outdoors and the flue gases are discharged to the outdoors. The EL195DF is then classified as a direct vent, Category IV gas furnace. In both Non-Direct Vent and Direct Vent applications, the vent termination is limited by local building codes. In the absence of local codes, refer to the current National Fuel Gas Code ANSI Z223−1/NFPA 54 in U.S.A., and current CSA−B149 Natural Gas and Propane Installation Codes in Canada for details. Position termination according to location given in figure 22 or 23. In addition, position termination so it is free from any obstructions and 12" above the average snow accumulation. At vent termination, care must be taken to maintain protective coatings over building materials (prolonged exposure to exhaust condensate can destroy protective coatings). It is recommended that the exhaust outlet not be located within 6 feet (1.8m) of a condensing unit because the condensate can damage the painted coating. NOTE − If winter design temperature is below 32°F (0°C), exhaust piping should be insulated with 1/2" (13mm), Armaflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to outside air; exterior exhaust pipe should be insulated with 1/2" (13mm) Armaflex or equivalent. In extreme cold climate areas, 3/4" (19mm) Armaflex or equivalent may be necessary. Insulation on outside runs of exhaust pipe must be painted or wrapped to protect insulation from deterioration. Exhaust pipe insulation may not be necessary in some specific applications. NOTE − During extremely cold temperatures, below approximately 20°F (6.7°C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze−ups. Heating cable installation kit is available from Lennox. See Condensate Piping section for part numbers. FIGURE 21 Follow the next two steps when installing the unit in NonDirect Vent applications where combustion air is taken from indoors and flue gases are discharged outdoors. 1 − Use field−provided materials and the factory−provided air intake screen to route the intake piping as shown in figure 21. Maintain a minimum clearance of 3" (76mm) around the air intake opening. The air intake opening (with the protective screen) should always be directed forward, or sideways. 2 − Use cement to secure the intake pipe to the connector, if desired. IMPORTANT Do not use screens or perforated metal in exhaust terminations. Doing so will cause freeze−ups and may block the terminations. IMPORTANT For Canadian Installations Only: In accordance to CSA International B149 installation codes, the minimum allowed distance between the combustion air intake inlet and the exhaust outlet of other appliances shall not be less than 12 inches (305mm). Page 18 VENT TERMINATION CLEARANCES FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA INSIDE CORNER DETAIL G H A D E B L Fixed Closed Operable F B B C Operable I Fixed Closed M B K J A B VENT TERMINAL A= Clearance above grade, veranda, porch, deck or balcony B= Clearance to window or door that may be opened C= Clearance to permanently closed window D= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (mm) from the center line of the terminal E= F= G= Clearance to unventilated soffit Clearance to outside corner AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED US Installations1 Canadian Installations2 12 inches (305mm) or 12 in. 305mm) above average snow accumulation. 12 inches (305mm) or 12 in. 305mm) above average snow accumulation. 4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above opening 6 inches (152mm) for appliances <10,000 Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and <100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw) * 12" * 12" * Equal to or greater than soffit depth. * Equal to or greater than soffit depth. * Equal to or greater than soffit depth. * No minimum to outside corner * Clearance to inside corner * Equal to or greater than soffit depth. * No minimum to outside corner * H= Clearance to each side of center line extended above meter / regulator assembly * 3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly 3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly I= Clearance to service regulator vent outlet Clearance to non−mechanical air supply inlet to building or the combustion air inlet to any other appliance * 3 feet (.9m) 3 feet (.9m) J= K= L= M= 1 In 2 In Clearance to mechanical air supply inlet Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda, porch, deck or balcony 4 feet (1.2 m) below or to side of opening; 1 foot (30 cm) above opening 3 feet (.9m) above if within 10 feet (3m) horizontally 7 feet (2.1m) *12 inches (305mm) accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code accordance with the current CSA B149.1, Natural Gas and Propane Installation Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible. FIGURE 22 Page 19 6 inches (152mm) for appliances <10,000 Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and <100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw) 6 feet (1.8m) 7 feet (2.1m) 12 inches (305mm) *For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions." VENT TERMINATION CLEARANCES FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA INSIDE CORNER DETAIL G H A D E B L Fixed Closed Operable F B B C I Fixed Closed Operable M B K J A B VENT TERMINAL AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED US Installations1 Canadian Installations2 A= Clearance above grade, veranda, porch, deck or balcony 12 inches (305mm) or 12 in. 305mm) above average snow accumulation. 12 inches (305mm) or 12 in. 305mm) above average snow accumulation. B= Clearance to window or door that may be opened 6 inches (152mm) for appliances <10,000 Btuh (3kw), 9 inches (mm) for appliances > 10,000 Btuh (3kw) and <50,000 Btuh (15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw) 6 inches (152mm) for appliances <10,000 Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and <100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw) C= Clearance to permanently closed window * 12" * 12" D= Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (mm) from the center line of the terminal E= Clearance to unventilated soffit F= Clearance to outside corner G= Clearance to inside corner H= Clearance to each side of center line extended above meter / regulator assembly I= Clearance to service regulator vent outlet Clearance to non−mechanical air supply inlet to building or the combustion air inlet to any other appliance J= K= L= M= 1 In 2 In Clearance to mechanical air supply inlet Clearance above paved sidewalk or paved driveway located on public property Clearance under veranda, porch, deck or balcony * Equal to or greater than soffit depth * Equal to or greater than soffit depth * No minimum to outside corner * 3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly * 3 feet (.9m) 6 inches (152mm) for appliances <10,000 Btuh (3kw), 9 inches (mm) for appliances > 10,000 Btuh (3kw) and <50,000 Btuh (15 kw), 12 inches (305mm) for appliances > 50,000 Btuh (15kw) 3 feet (.9m) above if within 10 feet (3m) horizontally * 7 feet (2.1m) *12 inches (305mm) accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code accordance with the current CSA B149.1, Natural Gas and Propane Installation Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings. * Equal to or greater than soffit depth * Equal to or greater than soffit depth * No minimum to outside corner * 3 feet (.9m) within a height 15 feet (4.5m) above the meter / regulator assembly 3 feet (.9m) 6 inches (152mm) for appliances <10,000 Btuh (3kw), 12 inches (305mm) for appliances > 10,000 Btuh (3kw) and <100,000 Btuh (30kw), 36 inches (.9m) for appliances > 100,000 Btuh (30kw) 6 feet (1.8m) 7 feet (2.1m) 12 inches (305mm) *For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, clearance will be in accordance with local installation codes and the requirements of the gas supplier and these installation instructions." Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible. FIGURE 23 Page 20 Details of Intake and Exhaust Piping Terminations for Direct Vent Installations NOTE − In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors. NOTE − Flue gas may be slightly acidic and may adversely affect some building materials. If any vent termination is used and the flue gasses may impinge on the building material, a corrosion−resistant shield (minimum 24 inches square) should be used to protect the wall surface. If the optional tee is used, the protective shield is recommended. The shield should be constructed using wood, plastic, sheet metal or other suitable material. All seams, joints, cracks, etc. in the affected area should be sealed using an appropriate sealant. See figure 26. Intake and exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 24 through 36 show typical terminations. 1 − Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure. 2 − Intake and exhaust pipes should be placed as close together as possible at termination end (refer to illustrations). Maximum separation is 3" (76mm) on roof terminations and 6" (152mm) on side wall terminations. 3 − On roof terminations, the intake piping should terminate straight down using two 90° elbows (See figure 24). 4 − Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See table 8. TABLE 8 EXHAUST PIPE TERMINATION SIZE REDUCTION EL195 MODEL Exhaust Pipe Size Termination Pipe Size *045 and *070 *090 110 2" (51mm), 2−1/2" (64mm), 3" (76mm) 1−1/2" (38mm) 2" (51mm) 2" (51mm) *EL195DF−045, −070 and −090 units with the flush−mount termination must use the 1−1/2"accelerator supplied with the kit. 5 − On field−supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. Intake piping should be as short as possible. See figures 27 and 28. NOTE − Care must be taken to avoid recirculation of exhaust back into intake pipe. 6 − On field supplied terminations, a minimum distance Page 21 between the end of the exhaust pipe and the end of the intake pipe without a termination elbow is 8" and a minimum distance of 6" with a termination elbow. See figures 27 and 28. Inches(mm) 3"(76mm) MAX. SIZE TERMINATION PIPE PER TABLE 8. UNCONDITIONED ATTIC SPACE 8" (203mm) MIN 1/2" (13mm) FOAM INSULATION IN UNCONDITIONED SPACE 12" (305mm) ABOVE AVERAGE SNOW ACCUMULATION 3" (76mm) OR 2" (51mm) PVC PROVIDE SUPPORT FOR INTAKE AND EXHAUST LINES DIRECT VENT ROOF TERMINATION KIT (15F75 or 44J41) FIGURE 24 2" EXTENSION FOR 2" PVC PIPE 1" EXTENSION FOR 3" PVC PIPE FURNACE EXHAUST PIPE 4’’ FURNACE INTAKE PIPE GLUE EXHAUST END FLUSH INTO TERMINATION 1−1/2" ACCELERATOR (all −070 and −090 units) FLUSH−MOUNT SIDE WALL TERMINATION KIT 51W11 FIGURE 25 7 − If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24" (610mm) as shown in figures 27 and 28. In addition, close coupled wall termination kits must be extended for use in this application. See figures 34 and 35. When exhaust and intake piping must be run up an outside wall, the exhaust piping must be terminated with pipe sized per table 8.The intake piping may be equipped with a 90° elbow turndown. Using turndown will add 5 feet (1.5m) to the equivalent length of the pipe. 8 − A multiple furnace installation may use a group of up to four terminations assembled together horizontally, as shown in figure 31. B B D D C Intake C 3 1 Front View of Intake and Exhaust A Exhaust A 2 Intake Exhaust TABLE 9 D 1 E B 12" C 2 A A− Clearance above grade or average snow accumulation B−Horizontal separation between intake and exhaust C−Minimum from end of exhaust to inlet of intake D−Exhaust pipe length E−Wall support distance from top of each pipe (intake/exhaust) 2" (51mm) Vent Pipe 3" (76mm) Vent Pipe 12" (508MM) Min. 12" (508MM) Min. 6" (152MM) Min. 24" (610 MM) Max 6" (152MM) Min. 24" (610 MM) Max 9" (227MM) Min. 9" (227MM) Min. 12" (305MM) Min. 12" (305MM) Min. 16" (405 MM) Max. 20" (508MM) Max. 6" (152MM) Max. 6" (152MM) Max. NOTE − See unit installation instructions for proper exhaust pipe termination size reduction. exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required. 2 As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches square) should be used to protect the wall surface. If optional tee is used, the protective shield is recommended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints, cracks, etc. in affected area, should be sealed using an appropriate sealant. 3Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet. 1 The FIGURE 26 Page 22 FIELD SUPPLIED WALL TERMINATION OR (15F74) WALL RING TERMINATION KIT With INTAKE ELBOW FIELD SUPPLIED WALL TERMINATION OR (15F74) WALL RING TERMINATION KIT NOTE − FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION NOTE − FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION 1/2" (13mm) ARMAFLEX INSULATION IN UNCONDITIONED SPACE 1/2" (13mm) ARMAFLEX INSULATION IN UNCONDITIONED SPACE SIZE TERMINATION PER TABLE 8 SIZE TERMINATION PER TABLE 8 D D B C B STRAIGHT APPPLICATION A C A 1/2" (13mm) ARMAFLEX INSULATION IN UNCONDITIONED SPACE 1/2" (13mm) ARMAFLEX INSULATION IN UNCONDITIONED SPACE D E * WALL SUPPORT D E * WALL SUPPORT B B A A C EXTENDED APPLICATION 2" (51mm) Vent Pipe 3" (76mm) Vent Pipe 12" (508MM) 12" (508MM) B−Maximum horizontal separation between intake and exhaust 6" (152MM) 6" (152MM) C−Minimum from end of exhaust to inlet of intake 8" (203MM) 8" (203MM) D−Maximum exhaust pipe length 12" (305MM) 20" (508MM) 6" (152MM) E−Maximum wall support distance from top of each pipe (intake/exhaust) 6" (152MM) EXTENDED APPLICATION C See venting table 7 for maximum venting lengths with this arrangement. * Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust) A−Minimum clearance above grade or average snow accumulation STRAIGHT APPPLICATION See venting table 7 for maximum venting lengths with this arrangement. * Use wall support every 24" (610 mm). Use two wall supports if extension is greater than 24" (610 mm) but less than 48" (1219 mm). NOTE − One wall support must be 6" (152 mm) from top of each pipe (intake and exhaust) 2" (51mm) Vent Pipe 3" (76mm) Vent Pipe 12" (508MM) 12" (508MM) 6" (152MM) 6" (152MM) 6" (152MM) 6" (152MM) D−Maximum exhaust pipe length 12" (305MM) 20" (508MM) E−Maximum wall support distance from top of each pipe (intake/exhaust) 6" (152MM) 6" (152MM) A−Minimum clearance above grade or average snow accumulation B−Maximum horizontal separation between intake and exhaust C−Minimum from end of exhaust to inlet of intake FIGURE 28 FIGURE 27 Page 23 1−1/2" (38mm) accelerator provided on 71M80 & 44W92 kits for EL195DF045P36B− & 070P36B 12” (305mm) SIZE TERMINATION PIPE PER TABLE 8. INTAKE AIR FLASHING (Not Furnished) INTAKE Minimum Above Average Snow Accumulation EXHAUST VENT Front View Top View SHEET METAL STRAP (Clamp and sheet metal strap must be field installed to support the weight of the termination kit.) CLAMP FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION 1/2" (13mm) Foam Insulation in Unconditioned Space FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION OUTSIDE WALL DIRECT VENT WALL TERMINATION KIT (30G28 or 81J20) FIGURE 29 FIGURE 32 1−1/2" (38mm) accelerator provided on 71M80 & 44W92 kits for EL195DF045P36B− & 070P36B EXHAUST AIR EXHAUST VENT Front View INTAKE AIR WALL INTAKE AIR 6 (152mm) MIN. DIRECT VENT CONCENTRIC ROOFTOP TERMINATION 71M80, 69M29 or 60L46 (US) 44W92 or 44W93 (Canada) FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION OUTSIDE EXHAUST VENT SIZE TERMINATION PIPE PER TABLE 8. INTAKE AIR EXHAUST AIR Top View INTAKE AIR INTAKE 12" (305mm) Min. AIR above grade or average snow accumulation. GRADE CLAMP (Not Furnished) DIRECT VENT CONCENTRIC WALL TERMINATION 71M80, 69M29 or 60L46 (US) 44W92 or 44W93 (Canada) 1/2" (13mm) Foam Insulation in Unconditioned Space FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION EXHAUST VENT INTAKE AIR FIGURE 30 8" (206mm) MIN. OUTSIDE WALL EXHAUST VENT 12" (305mm) 5−1/2" (140mm) 5" (127mm) DIRECT VENT WALL TERMINATION KIT (22G44 or 44J40) FIGURE 33 INTAKE AIR 18" MAX. (457mm) Front View EXHAUST VENT Inches (mm) optional intake elbow 12" (305mm) Min. above grade or average snow acINTAKE cumulation. AIR Side View OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT INSTALLATION OF DIRECT VENT WALL TERMINATION KIT (22G44, 44J40, 30G28 or 81J20) FIGURE 31 Page 24 WALL TERMINATION KITS (CLOSE−COUPLE) EXTENDED VENT FOR GRADE CLEARANCE 2 inch (51 mm) 22G44 (US) 3 inch (76 mm) 44J40 (US) If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field− fabricated piping must be installed. WALL SUPPORT* FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION 8” (203 mm) Min. for 2” (51 mm) & 3” (76 mm) DIA. pipe between the end of the exhaust pipe and intake pipe 12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust 12” (305 mm) EXHAUST AIR 6” (152 mm) Maximum 1/2” (13 mm) FOAM INSULATION (Field Furnished) INTAKE AIR INTAKE AIR EXHAUST AIR 5” (127 mm) 8” (203 mm) Min. 12” (305 mm) Minimum Above Grade or Average Snow Accumulation ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ GRADE 12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust 12” (305 mm) Minimum Above Grade or Average Snow Accumulation ÉÉÉÉÉÉÉÉÉÉÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉ 5−1/2” (140 mm) GRADE *Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48". FIGURE 34 WALL TERMINATION KITS (CLOSE−COUPLE) EXTENDED VENT FOR GRADE CLEARANCE 2 inch (51 mm) 30G28 (WTK Canada) 3 inch (76 mm) 81J20 (WTK Canada) See Installation Instructions for additional information. If intake and exhaust pipe is less than 12 in. (305 mm) above snow accumulation or other obstructions, field− fabricated piping must be installed. WALL SUPPORT* FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION 12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust 12” (305 mm) EXHAUST AIR 6” (152 mm) Maximum 1/2” (13 mm) FOAM INSULATION (Field Furnished) INTAKE AIR 6” (152 mm) Minimum INTAKE AIR EXHAUST AIR 5” (127 mm) 6” (152 mm) Minimum 12” (305 mm) Minimum Above Grade or Average Snow Accumulation ÉÉÉÉÉÉÉÉÉÉÉÉ GRADE 12” (305 mm) Max. for 2” (51 mm) Dia. Exhaust 20” (508 mm) Max. for 3” (76 mm) Dia. Exhaust 12” (305 mm) Minimum Above Grade or Average Snow Accumulation ÉÉÉÉÉÉÉÉÉÉÉÉ *Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48". FIGURE 35 Page 25 5−1/2” (140 mm) GRADE EL195DF DIRECT VENT APPLICATION STRAIGHT−CUT OR USING EXISTING CHIMNEY ANGLE−CUT IN DIRECTION SIZE TERMINATION PIPE PER TABLE 8. OF ROOF SLOPE * 8" − 12" (203mm − 305mm) Minimum 12" (305MM) above chimney top plate or average snow accumulation 3" − 8" (76mm− 203mm) INTAKE PIPE INSULATION (optional) 12" (305mm) ABOVE AVE. SNOW ACCUMULATION EXHAUST VENT 1/2" (13mm) WEATHERPROOF INSULATION SHOULDER OF FITTINGS PROVIDE SUPPORT OF PIPE ON TOP PLATE SHEET METAL TOP PLATE 1/2" (13mm) FOAM INSULATION 3" (76mm) OR 2" (51mm) PVC ALTERNATE INTAKE PIPE UNCONDITIONED ATTIC SPACE PROVIDE SUPPORT FOR EXHAUST LINES INSULATE TO FORM SEAL 3" − 8" (76mm− 203mm) EXTERIOR PORTION OF CHIMNEY NON−DIRECT VENT ROOF TERMINATION KIT (15F75 or 44J41) *SIZE TERMINATION PIPE PER TABLE 8. FIGURE 37 NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated. 12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm) 1/2" (13mm) ARMAFLEX INSULATION IN UNCONDITIONED SPACE FIGURE 36 Details of Exhaust Piping Terminations for Non-Direct Vent Applications Exhaust pipes may be routed either horizontally through an outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 37 through 40 show typical terminations. 1 − Exhaust piping must terminate straight out or up as shown. The termination pipe must be sized as listed in table 8.The specified pipe size ensures proper velocity required to move the exhaust gases away from the building. 2 − On field supplied terminations for side wall exit, exhaust piping may extend a maximum of 12 inches (305mm) for 2" PVC and 20 inches (508mm) for 3" (76mm) PVC beyond the outside wall. See figure 38. FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION SIZE TERMINATION PIPE PER TABLE 8. 1/2" (13mm) ARMAFLEX INSULATION PVC REDUCER 12" MIN. (305mm) Above Grade or average snow accumulation NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION OR (15F74) WALL TERMINATION KIT FIGURE 38 3 − If exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported every 24 inches (610mm) as shown in figure 39. When exhaust piping must be run up an outside wall, any reduction in exhaust pipe size must be done after the final elbow. Page 26 12" (305mm) MAX. for 2" (51mm) 20" (508mm) MAX. for 3" (76mm) UNCONDITIONED SPACE 6" (152mm) Max SIZE TERMINATION PIPE PER TABLE 8. *WALL SUPPORT OUTSIDE WALL FIELD−PROVIDED REDUCER MAY BE REQUIRED TO ADAPT LARGER VENT PIPE SIZE TO TERMINATION NOTE − If necessary the condensate trap may be installed up to 5´ away from the furnace. Use PVC pipe to connect trap to furnace condensate outlet. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap. CONDENSATE TRAP AND PLUG LOCATIONS 12" (305mm) ABOVE GRADE OR AVERAGE SNOW ACCUMULATION 1/2" (13mm) FOAM INSULATION IN UNCONDITIONED SPACE *Use wall support every 24" (610). Use two supports if extension is greater than 24" but less than 48". Trap (same on right side) 1/2" (13mm) FOAM INSULATION NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION EXTENDED OR (15F74) WALL TERMINATION VENT PIPE EXTENDED 1−1/2 in. Plug (same on left side) FIGURE 39 EL195DF NON−DIRECT VENT APPLICATION USING EXISTING CHIMNEY STRAIGHT−CUT OR ANGLE−CUT IN DIRECTION OF ROOF SLOPE SIZE TERMINATION PIPE PER TABLE 8. 3" − 8" (76mm− 203mm) Minimum 12" (305MM) above chimney top plate or average snow accumulation EXHAUST VENT 1/2" (13mm) WEATHERPROOF INSULATION SHOULDER OF FITTINGS PROVIDE SUPPORT OF PIPE ON TOP PLATE SHEET METAL TOP PLATE INSULATE TO FORM SEAL 3" − 8" (76mm− 203mm) EXTERIOR PORTION OF CHIMNEY NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If vertical discharge through an existing unused chimney or stack is required, insert piping inside chimney until the pipe open end is above top of chimney and terminate as illustrated. In any exterior portion of chimney, the exhaust vent must be insulated. FIGURE 40 Condensate Piping This unit is designed for either right- or left-side exit of condensate piping. Refer to figure 41 for condensate trap locations. Page 27 FIGURE 41 1 − Determine which side condensate piping will exit the unit, location of trap, field−provided fittings and length of PVC pipe required to reach available drain. 2 − Remove plug (figure 41) from the cold end header box at the appropriate location on the side of the unit. Install field−provided 1/2" NPT male fitting into cold end header box. Use teflon tape or appropriate pipe dope. 3 − Install the cap over the clean out opening at the base of the trap. See figure 44. 4 − Install drain trap using appropriate PVC fittings, glue all joints. Glue the provided drain trap as shown in figure 44. Route the condensate line to an open drain. NOTE − If necessary the condensate trap may be installed up to 5 feet away from the furnace. Piping from furnace must slope down a minimum of 1/4" per ft. toward trap. NOTE − Vinyl tubing may be used for condensate drain. Tubing must be 1−1/4" OD X 1" ID and should be attached to the drain on the trap using a hose clamp. 5 − If unit will be started immediately upon completion of installation, prime trap per procedure outlined in Unit Start−Up section. Condensate line must slope downward away from the trap to drain. If drain level is above condensate trap, condensate pump must be used. Condensate drain line should be routed within the conditioned space to avoid freezing of condensate and blockage of drain line. If this is not possible, a heat cable kit may be used on the condensate trap and line. Heat cable kit is available from Lennox in various lengths; 6 ft. (1.8m) − kit no. 26K68; 24 ft. (7.3m) − kit no. 26K69; and 50 ft. (15.2m) − kit no. 26K70. EL195DF with Evaporator Coil Condensate trap and evaporator coil must drain separately as shown. Field−Provided Vent CONDENSATE TRAP LOCATION (shown with right side exit of condensation) Drain Field Provided Vent min. 1" Above Condensate Drain FIGURE 43 Trap can be installed a maximum of 5 ft. from furnace. (*PVC Only) CAUTION 1" min. Do not use copper tubing or existing copper condensate lines for drain line. 5’ max. CAUTION A separate drain line must be run to the drain from the condensate trap to ensure proper drainage and pressure switch operation. DO NOT connect the condensate trap drain into the drain line from the evaporator coil. to drain *Piping from furnace must slope down a minimum of 1/4" per ft. toward trap. FIGURE 42 Page 28 TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC OPTIONAL Condensate Drain Connection Adapter 1/2 inch slip X 1/2 inch mpt (Not Furnished) Adapter 1/2 inch slip X 1/2 inch mpt (Not Furnished) 90° Street Elbow 1/2 inch PVC (Not Furnished) 1 (25) Minimum Vent 5 Feet Maximum Above Top of Condensate Drain Connection In Unit 90° Elbow 1/2 inch PVC (Not Furnished) Condensate Drain Connection In Unit OPTIONAL Drain Piping 1/2 inch PVC Pipe (Not Furnished) 1/2 inch PVC Pipe (Not Furnished) Coupling 1/2 inch slip X slip (Not Furnished) Drain Assembly for 1/2 inch Drain Pipe 1/2 inch PVC Pipe (Not Furnished) 90° Street Elbow 1/2 inch PVC (Furnished) To Drain To Drain Condensate Drain Connection In Unit Drain Trap Assembly (Furnished) 90° Elbow 1/2 inch PVC (Not Furnished) Drain Assembly for 3/4 inch Drain Pipe Drain Trap Clean Out 90° Elbow 3/4 inch PVC (Not Furnished) To Drain 90° Elbow 3/4 inch PVC (Not Furnished) To Coupling 3/4 inch slip X slip Drain (Not Furnished) Drain Trap Assembly with 1/2 inch Piping Drain Trap Assembly with 3/4 inch Piping 1 inch (25mm) Minimum Above Top of Condensate Drain Connection In Unit 1 inch (25mm) Minimum Above Top of Condensate Drain Connection In Unit Vent Drain Trap Assembly (Furnished) Vent 7 (178) Condensate Drain Connection In Unit Condensate Drain Connection In Unit To Drain To Drain FIGURE 44 Page 29 Gas Piping IMPORTANT Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petroleum gases. CAUTION If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line. Leak Check After gas piping is completed, carefully check all piping connections (factory− and field−installed) for gas leaks. Use a leak detecting solution or other preferred means. The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures less than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.). WARNING Do not exceed 600 in−lbs (50 ft−lbs) torque when attaching the gas piping to the gas valve. 1 − Gas piping may be routed into the unit through either the left- or right-hand side. Supply piping enters into the gas valve from the side of the valve as shown in figure 46. 2 − When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 10 lists recommended pipe sizes for typical applications. NOTE − Use two wrenches when connecting gas piping to avoid transferring torque to the manifold. 3 − Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See figures 46. 4 − Piping should be sloped 1/4 inch per 15 feet (6mm per 5.6m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate. 5 − A 1/8" N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See figure 53. 6 − In some localities, codes may require installation of a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type. MANUAL MAIN SHUT−OFF VALVE WILL NOT HOLD NORMAL TEST PRESSURE 1/8" N.P.T. PLUGGED TAP FURNACE ISOLATE GAS VALVE CAP FIGURE 45 IMPORTANT When testing pressure of gas lines, gas valve must be disconnected and isolated. See figure 45. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa). WARNING FIRE OR EXPLOSION HAZARD Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Page 30 Left Side Piping (Standard) MANUAL MAIN SHUT−OFF VALVE (With 1/8 in. NPT Plugged Tap Shown) AUTOMATIC GAS VALVE MANUAL MAIN SHUT−OFF VALVE (With 1/8 in. NPT Plugged Tap Shown) GROUND JOINT UNION AUTOMATIC GAS VALVE Plug Plug GROUND JOINT UNION Bellows Grommet DRIP LEG Right Side Piping (Alternate) FIELD PROVIDED AND INSTALLED DRIP LEG Bellows Grommet NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 46 TABLE 10 GAS PIPE CAPACITY − FT3/HR (kL/HR) Length of Pipe−Feet(m) 50 60 70 (15.240) (18.288) (21.336) Nominal Iron Pipe Size −Inches(mm) Internal Diameter −Inches(mm) 10 (3.048) 20 (6.096) 30 (9.144) 40 (12.192) 1/2 (12.7) .622 (17.799) 175 (4.96) 120 (3.40) 97 (2.75) 82 (2.32) 73 (2.07) 66 (1.87) 3/4 (19.05) .824 (20.930) 360 (10.19) 250 (7.08) 200 (5.66) 170 (4.81) 151 (4.28) 1 (25.4) 1.049 (26.645) 680 (19.25) 465 (13.17) 375 (10.62) 320 (9.06) 1−1/4 (31.75) 1.380 (35.052) 1400 (39.64) 950 (26.90) 770 (21.80) 1−1/2 (38.1) 1.610 (40.894) 2100 (59.46) 460 (41.34) 2 (50.8) 2.067 (52.502) 3950 (111.85) 2−1/2 (63.5) 2.469 (67.713) 3 (76.2) 4 (101.6) 80 (24.384) 90 (27.432) 100 (30.480) 61 (1.73) 57 (1.61) 53 (1.50) 50 (1.42) 138 (3.91) 125 (3.54) 118 (3.34) 110 (3.11) 103 (2.92) 285 (8.07) 260 (7.36) 240 (6.80) 220 (6.23) 205 (5.80) 195 (5.52) 660 (18.69) 580 (16.42) 530 (15.01) 490 (13.87) 460 (13.03) 430 (12.18) 400 (11.33) 1180 (33.41) 990 (28.03) 900 (25.48) 810 (22.94) 750 (21.24) 690 (19.54) 650 (18.41) 620 (17.56) 2750 (77.87) 2200 (62.30) 1900 (53.80) 1680 (47.57) 1520 (43.04) 1400 (39.64) 1300 (36.81) 1220 (34.55) 1150 (32.56) 6300 (178.39) 4350 (123.17) 3520 (99.67) 3000 (84.95) 2650 (75.04) 2400 (67.96) 2250 (63.71) 2050 (58.05) 1950 (55.22) 1850 (52.38) 3.068 (77.927) 11000 (311.48) 7700 (218.03) 6250 (176.98) 5300 (150.07) 4750 (134.50) 4300 (121.76) 3900 (110.43) 3700 (104.77) 3450 (97.69) 3250 (92.03) 4.026 (102.260) 23000 (651.27) 15800 (447.39) 12800 (362.44) 10900 (308.64) 9700 (274.67) 8800 (249.18) 8100 (229.36) 7500 (212.37) 7200 (203.88) 6700 (189.72) NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas. Page 31 Removal of the Furnace from Common Vent In the event that an existing furnace is removed from a venting system commonly run with separate gas appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. Conduct the following test while each appliance is operating and the other appliances (which are not operating) remain connected to the common venting system. If the venting system has been installed improperly, you must correct the system as indicated in the general venting requirements section. 4 − Follow the lighting instructions. Turn on the appliance that is being inspected. Adjust the thermostat so that the appliance operates continuously. 5 − After the main burner has operated for 5 minutes, test for leaks of flue gases at the draft hood relief opening. Use the flame of a match or candle. 6 − After determining that each appliance connected to the common venting system is venting properly, (step 3) return all doors, widows, exhaust fans, fireplace dampers, and any other gas−burning appliances to their previous mode of operation. 7 − If a venting problem is found during any of the preceding tests, the common venting system must be modified to correct the problem. WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation: Resize the common venting system to the minimum vent pipe size determined by using the appropriate tables in Appendix G. (These are in the current standards of the National Fuel Gas Code ANSI Z223.1. Electrical CAUTION 1 − Seal any unused openings in the common venting system. 2 − Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition. 3 − Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. Electrostatic discharge can affect electronic components. Take precautions to neutralize electrostatic charge by touching your hand and tools to metal prior to handling the control. The unit is equipped with a field make−up box on the left hand side of the cabinet. A field−provided make−up box can be installed on the exterior of the right side of the furnace to facilitate installation. If the make−up box is moved to the right side, clip the wire ties that bundle the wires together and install on the outside of the cabinet. See figure 48. The excess wire must be pulled into the blower compartment. Secure the excess wire to the existing harness to protect it from damage. Page 32 Complete the wiring connections to the equipment. Use the provided unit wiring diagram and the field wiring diagram shown in figure 50. Use 18−gauge wire or larger that is suitable for Class II rating for thermostat connections. INTERIOR MAKE−UP BOX (FACTORY− INSTALLED LEFT SIDE) Electrically ground the unit according to local codes or, in the absence of local codes, according to the current National Electric Code (ANSI/NFPA No. 70) for the USA and current Canadian Electric Code part 1 (CSA standard C22.1) for Canada. A green ground wire is provided in the field make−up box. NOTE − The EL195DF furnace contains electronic components that are polarity sensitive. Make sure that the furnace is wired correctly and is properly grounded. MAKE−UP BOX INSIDE CABINET Left side Generator Use − Voltage Requirements The following requirements must be kept in mind when specifying a generator for use with this equipment: The furnace requires 120 volts + 10% (Range: 108 volts to 132 volts) The furnace operates at 60 Hz + 5% (Range: 57 Hz to 63 Hz) The furnace integrated control requires both polarity and proper ground. Both polarity and proper grounding should be checked before attempting to operate the furnace on either permanent or temporary power Generator should have a wave form distortion of less than 5% THD (total harmonic distortion) Accessory Terminals FIGURE 47 EXTERIOR MAKE−UP BOX (FIELD PROVIDED RIGHT SIDE) MAKE−UP BOX OUTSIDE CABINET One line voltage EAC" 1/4" spade terminal is provided on the furnace integrated control. See figure 52 for integrated control configuration. This terminal is energized when the indoor blower is operating. Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If an accessory rated at greater than one amp is connected to this terminal, it is necessary to use an external relay. Right Side FIGURE 48 Refer to figure 50 for field wiring and figure 51 for schematic wiring diagram and troubleshooting. The power supply wiring must meet Class I restrictions. Protected by either a fuse or circuit breaker, select circuit protection and wire size according to unit nameplate. NOTE − Unit nameplate states maximum current draw. Maximum Over−Current Protection allowed is 15 AMP. Holes are on both sides of the furnace cabinet to facilitate wiring. Install a separate (properly sized) disconnect switch near the furnace so that power can be turned off for servicing. Before connecting the thermostat or the power wiring, check to make sure the wires will be long enough for servicing at a later date. Remove the blower access panel to check the length of the wire. Page 33 One line voltage HUM" 1/4" spade terminal is provided on the furnace integrated control. See figure 52 for integrated control configuration. This terminal is energized in the heating mode when the combustion air inducer is operating. Any humidifier rated up to one amp can be connected to this terminal with the neutral leg of the circuit being connected to one of the provided neutral terminals. If a humidifier rated at greater than one amp is connected to this terminal, it is necessary to use an external relay. One 24V "H" 1/4" spade terminal is provided on the furnace integrated control. See figure 52 for integrated control configuration. The terminal is energized in the heating mode when the combustion air inducer is operating and the pressure switch is closed. Any humidifier rated up to 0.5 amp can be connected to this terminal with the ground leg of the circuit connected to ground or the "C" terminal. EL195DF and CONDENSING UNIT THERMOSTAT DESIGNATIONS (Refer to specific thermostat and outdoor unit.) Thermostat POWER R W1 Y G C Furnace HEAT COOLING INDOOR BLOWER COMMON R W Y G C Condensing Unit *CONDENSING UNIT CONDENSING UNIT CONDENSING UNIT COMMON Install the room thermostat according to the instructions provided with the thermostat. See figure 49 for thermostat designations. If the furnace is being matched with a heat pump, refer to the FM21 installation instruction or appropriate dual fuel thermostat instructions. Indoor Blower Speeds 1 − When the thermostat is set to FAN ON," the indoor blower will run continuously on the fan speed when there is no cooling or heating demand. 2 − When the EL195DF is running in the heating mode, the indoor blower will run on the heating speed. 3 − When there is a cooling demand, the indoor blower will run on the cooling speed. *NOTE − R" REQUIRED ON SOME OUTDOOR UNITS FIGURE 49 TYPICAL EL195DF FIELD WIRING DIAGRAM IGNITOR *NOTE − R" REQUIRED ON SOME OUTDOOR UNITS *R FIGURE 50 Page 34 TYPICAL EL195DF WIRING DIAGRAM FIGURE 51 Page 35 INTEGRATED CONTROL (Automatic Hot Surface Ignition System) HUM LINE XFMR EAC COOL HEAT PARK FLAME FAN HUM Red LED TERMINAL DESIGNATIONS Humidifier (120VAC) Input (120VAC) Transformer (120VAC) Indoor Air Quality Accessories (120VAC) Blower − Cooling Speed (120VAC) Blower − Heating Speed (120VAC) Dead terminals to park alternate speed taps Flame sensor Continuous blower Humidifier (24VAC) Recall Blower off delay jumper FIGURE 52 Unit Start−Up WARNING FOR YOUR SAFETY READ BEFORE OPERATING Danger of explosion. Can cause injury or product or property damage. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting off the electrical supply. WARNING Do not use this furnace if any part has been underwater. A flood−damaged furnace is extremely dangerous. Attempts to use the furnace can result in fire or explosion. Immediately call a qualified service technician to inspect the furnace and to replace all gas controls, control system parts, and electrical parts that have been wet or to replace the furnace, if deemed necessary. CAUTION Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch. BEFORE LIGHTING the unit, smell all around the furnace area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. The gas valve on the EL195DF is equipped with a gas control switch. Use only your hand to move switch. Never use tools. If the switch will not move by hand, do not try to repair it. Force or attempted repair may result in a fire or explosion. Page 36 Placing the furnace into operation: MANIFOLD PRESSURE ADJUSTMENT SCREW (under barbed fitting) EL195DF units are equipped with an automatic hot surface ignition system. Do not attempt to manually light burners on this furnace. Each time the thermostat calls for heat, the burners will automatically light. The ignitor does not get hot when there is no call for heat on these units. MANIFOLD PRESSURE OUTLET PORT Priming Condensate Trap The condensate trap should be primed with water prior to start−up to ensure proper condensate drainage. Either pour 10 fl. oz. (300 ml) of water into the trap, or follow these steps to prime the trap: 1 − Follow the lighting instructions to place the unit into operation. 2 − Set the thermostat to initiate a heating demand. 3 − Allow the burners to fire for approximately 3 minutes. INLET PRESSURE PORT GAS VALVE SHOWN IN ON POSITION FIGURE 53 12− If the appliance will not operate, follow the instructions Turning Off Gas to Unit" and call your service technician or gas supplier. Turning Off Gas to Unit 4 − Adjust the thermostat to deactivate the heating demand. 5 − Wait for the combustion air inducer to stop. Set the thermostat to initiate a heating demand and again allow the burners to fire for approximately 3 minutes. 6 − Adjust the thermostat to deactivate the heating demand and wait for the combustion air inducer to stop. At this point, the trap should be primed with sufficient water to ensure proper condensate drain operation. WARNING If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or death. Gas Valve Operation (Figure 53) 1 − STOP! Read the safety information at the beginning of this section. 2 − Set the thermostat to the lowest setting. 3 − Turn off all electrical power to the unit. 4 − This furnace is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand. 5 − Remove the access panel. 6 − Move gas valve switch to OFF. See figure 53. 7 − Wait five minutes to clear out any gas. If you then smell gas, STOP! Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you do not smell gas go to next step. 8 − Move gas valve switch to ON. See figure 53. 9 − Replace the access panel. 10− Turn on all electrical power to to the unit. 11− Set the thermostat to desired setting. NOTE − When unit is initially started, steps 1 through 11 may need to be repeated to purge air from gas line. Page 37 1 − Set the thermostat to the lowest setting. 2 − Turn off all electrical power to the unit if service is to be performed. 3 − Remove the access panel. 4 − Move gas valve switch to OFF. 5 − Replace the access panel. Failure To Operate If the unit fails to operate, check the following: 1 − Is the thermostat calling for heat? 2 − Are access panels securely in place? 3 − Is the main disconnect switch closed? 4 − Is there a blown fuse or tripped breaker? 5 − Is the filter dirty or plugged? Dirty or plugged filters will cause the limit control to shut the unit off. 6 − Is gas turned on at the meter? 7 − Is the manual main shut-off valve open? 8 − Is the internal manual shut-off valve open? 9 − Is the unit ignition system in lockout? If the unit locks out again, inspect the unit for blockages. Heating Sequence Of Operation 1 − When thermostat calls for heat, combustion air inducer starts. 2 − Combustion air pressure switch proves blower operation. Switch is factory−set and requires no adjustment. 3 − After a 15−second prepurge, the hot surface ignitor energizes. 4 − After a 20−second ignitor warm−up period, the gas valve solenoid opens. A 4−second Trial for Ignition period begins." 5 − Gas is ignited, flame sensor proves the flame, and the combustion process continues. 6 − If flame is not detected after first ignition trial, the ignition control will repeat steps 3 and 4 four more times before locking out the gas valve (WATCHGUARD" flame failure mode). The ignition control will then automatically repeat steps 1 through 6 after 60 minutes. To interrupt the 60−minute WATCHGUARD" period, move thermostat from Heat" to OFF" then back to Heat". Heating sequence then restarts at step 1. Manifold Pressure Measurement 1 − Remove the threaded plug from the outlet side of the gas valve and install a field−provided barbed fitting. Connect to a manometer to measure manifold pressure. 2 − Start unit and allow 5 minutes for unit to reach steady state. 3 − While waiting for the unit to stabilize, notice the flame. Flame should be stable and should not lift from burner. Natural gas should burn blue. 4 − After allowing unit to stabilize for 5 minutes, record manifold pressure and compare to value given in table 12. NOTE − Shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to remove barbed fitting and replace threaded plug. Gas Pressure Adjustment Gas Flow (Approximate) TABLE 11 GAS METER CLOCKING CHART Seconds for One Revolution Natural LP ML193 Unit 1 cu ft 2 cu ft 1 cu ft 2 cu ft Dial Dial Dial DIAL −045 80 160 200 400 −070 55 110 136 272 −090 41 82 102 204 −110 33 66 82 164 Natural−1000 btu/cu ft LP−2500 btu/cu ft NOTE − To obtain accurate reading, shut off all other gas appliances connected to meter. Furnace should operate at least 5 minutes before checking gas flow. Determine time in seconds for two revolutions of gas through the meter. (Two revolutions assures a more accurate time). Divide by two and compare to time in table 11. If manifold pressure matches table 12 and rate is incorrect, check gas orifices for proper size and restriction. Remove temporary gas meter if installed. Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap. Remove the threaded plug, install a field−provided barbed fitting and connect a manometer to measure supply pressure. See table 12 for proper supply line pressure. Replace the threaded plug after measurements have been taken. TABLE 12 Manifold and Supply Pressure (Outlet) inches w.c. Fuel Model Input Sizes Nat All sizes LP/Propane All sizes Manifold Pressure in.wg. Supply Pressure in.wg. Min. Max. 3.5 4.5 10.0 10.0 11.0 13.0 Proper Combustion Furnace should operate minimum 15 minutes with correct manifold pressure and gas flow rate before checking combustion. Take combustion sample beyond the flue outlet and compare to the tables below. The maximum carbon monoxide reading should not exceed 50 ppm. TABLE 13 EL195 CO2% For Nat CO2% For LP Unit −045 −070 7.2 − 8.2 8.6 − 9.6 −090 −110 The maximum carbon monoxide reading should not exceed 50 ppm. High Altitude Information NOTE − In Canada, certification for installations at elevations over 4500 feet (1372 m) is the jurisdiction of local authorities. EL195DF units require no manifold pressure adjustments for operation at altitudes up to 10,000 feet (3048 m) above sea level. Units installed at altitude of 4501 − 10,000 feet (1373 to 3048m) may require a pressure switch change which can be ordered separately. Table 14 lists conversion kit and pressure switch requirements at varying altitudes. The combustion air pressure switch is factory−set and requires no adjustment. Page 38 TABLE 14 Conversion Kit and Pressure Switch Requirements at Varying Altitudes EL195 Unit Natural to LP/Propane High Altitude Natural Burner Orifice Kit High Altitude LP/Propane Burner Orifice Kit 0 − 7500 ft (0 − 2286m) 7501 − 10,000 ft (2286 − 3038m) 7501 − 10,000 ft (2286 − 3038m) −045 −070 −090 *69W73 73W37 *68W68 −110 High Altitude Pressure Switch 4501 − 7500 ft (1373 − 2286m) 7501 −10,000 ft (2286 − 3048m) No Change 74W90 77W43 73W22 77W42 73W22 77W43 73W22 * Conversion requires installation of a gas valve manifold spring which is provided with the gas conversion kit. Pressure switch is factory set. No adjustment necessary. All models use the factory−installed pressure switch from 0−4500 feet (0−1370 m). Testing of Non−Direct Vent Applications for Proper Venting and Sufficient Combustion Air WARNING CARBON MONOXIDE POISONING HAZARD! Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation. After the EL195DF gas furnace has been started, the following test should be conducted to ensure proper venting and sufficient combustion air has been provided to the EL195DF as well as to other gas-fired appliances which are separately vented. If a EL195DF furnace replaces a Category I furnace which was commonly vented with another gas appliance, the size of the existing vent pipe for that gas appliance must be checked. Without the heat of the original furnace flue products, the existing vent pipe is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance. The test should be conducted while all appliances (both in operation and those not in operation) are connected to the venting system being tested. If the venting system has been installed improperly, or if provisions have not been made for sufficient amounts of combustion air, corrections must be made as outlined in the previous section. 1 − Seal any unused openings in the venting system. 2 − Visually inspect the venting system for proper size and horizontal pitch. Determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition. Page 39 3 − To the extent that it is practical, close all building doors and windows and all doors between the space in which the appliances connected to the venting system are located and other spaces of the building. 4 − Close fireplace dampers. 5 − Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. 6 − Follow the lighting instruction to place the appliance being inspected into operation. Adjust thermostat so appliance will operate continuously. 7 − Use the flame of match or candle to test for spillage of flue gases at the draft hood relief opening after 5 minutes of main burner operation. 8 − If improper venting is observed during any of the above tests, the venting system must be corrected or sufficient combustion/make-up air must be provided. The venting system should be re-sized to approach the minimum size as determined by using the appropriate tables in appendix G in the current standards of the National Fuel Gas Code ANSI−Z223.1/NPFA 54 in the U.S.A., and the appropriate Natural Gas and Propane appliances venting sizing tables in the current standard of the CSA−B149 Natural Gas and Propane Installation Codes in Canada. 9 − After determining that each appliance remaining connected to the common venting system properly vents when tested as indicated in step 3, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use. Other Unit Adjustments NOTE − See troubleshooting flow charts if any safety switches are found to be open. Primary Limit The primary limit is located on the heating compartment vestibule panel. This limit is factory set and requires no adjustment. Flame Rollout Switches (Two) These manually reset switches are located on the front of the burner box. 3 − Check amp-draw on the blower motor. Motor Nameplate__________Actual__________ HEAT FAN-OFF TIME IN SECONDS Pressure Switch Fan Control Fan On Delay The heat fan on time of 30 seconds is not adjustable. The cool fan on delay is 2 seconds and not adjustable. Fan Off Delay The heat fan off delay (amount of time that the blower operates after the heat demand has been satisfied) may be adjusted by changing the jumper position across the five pins on the integrated control. The unit is shipped with a factory fan off setting of 90 seconds. The fan off delay affects comfort and is adjustable to satisfy individual applications. Adjust the fan off delay to achieve a supply air temperature between 90° and 110°F at the moment that the blower is de−energized. Longer off delay settings provide lower return air temperatures; shorter settings provide higher return air temperatures. See figure 54. The cool fan off delay (amount of time that the blower operates after the cool demand has been satisfied) is 45 seconds and not adjustable. Thermostat Heat Anticipation Set the heat anticipator setting (if adjustable) according to the amp draw listed on the wiring diagram that is attached to the unit. Electrical 1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace operating). 60 90 120 180 60 90 120 180 After the furnace has been started and supply and return air temperatures have been allowed to stabilize, check the temperature rise. If necessary, adjust the blower speed to maintain the temperature rise within the range shown on the unit nameplate. Increase the blower speed to decrease the temperature. Decrease the blower speed to increase the temperature rise. Failure to adjust the temperature rise may cause erratic limit operation. 60 90 120 180 Temperature Rise NO JUMPER To adjust fan−off timing, reposition jumper across pins to achieve desired setting. 60 Second 90 Second 120 Second 180 Second off Time off Time off Time off Time 60 90 120 180 The pressure switch is located in the heating compartment on the cold end header box. This switch checks for proper combustion air inducer operation before allowing ignition trial. The switch is factory−set and must not be adjusted. FIGURE 54 Blower Speeds Follow the steps below to change the blower speeds. 1 − Turn off electrical power to furnace. 2 − Remove blower access panel. 3 − Disconnect existing speed tap at integrated control speed terminal. NOTE − Termination of any unused motor leads must be insulated. 4 − Place unused blower speed tap on integrated control PARK" terminal or insulate. 5 − Refer to blower speed selection chart on unit wiring diagram for desired heating or cooling speed. See Blower performance data beginning on the next page. 6 − Connect selected speed tap at integrated control speed terminal. 7 − Resecure blower access panel. 8 − Turn on electrical power to furnace. 9 − Recheck temperature rise. Exhaust and Air Intake Pipe 1 − Check exhaust and air intake connections for tightness and to make sure there is no blockage. 2 − Is pressure switch closed? Obstructed exhaust pipe will cause unit to shut off at pressure switch. Check termination for blockages. 3 − Obstructed pipe or termination may cause rollout switches to open. Reset manual flame rollout switches on burner box assembly if necessary. Page 40 BLOWER DATA EL195DF045P36B PERFORMANCE (Less Filter) External Static Pressure in. w.g. EL195DF090P60C PERFORMANCE (Less Filter) Air Volume / Watts at Various Blower Speeds High MediumHigh MediumLow Low cfm Watts cfm Watts cfm Watts cfm Watts External Static Pressure in. w.g. High MediumHigh MediumLow Low cfm Watts cfm Watts cfm Watts cfm Watts 0.00 1615 650 1385 555 1205 465 1045 390 0.10 1605 640 1380 545 1195 455 1035 380 0.10 2295 1240 2135 940 1885 795 1500 665 0.20 1500 620 1345 525 1165 445 1015 370 0.20 2200 1220 2085 915 1865 775 1525 655 0.30 1450 590 1290 490 1125 420 975 365 0.30 2160 1210 1990 875 1830 755 1545 640 0.40 1350 560 1235 480 1090 405 920 345 0.40 2055 1170 1935 865 1790 725 1530 620 0.50 1300 545 1170 450 1035 380 880 330 0.50 1970 1130 1855 835 1705 700 1500 600 0.60 1195 500 1095 425 840 320 0.60 1890 1105 1765 805 1635 675 1495 580 990 365 0.00 Air Volume / Watts at Various Blower Speeds 2305 1255 2145 950 1900 810 1515 670 0.70 1140 480 1020 395 895 345 780 300 0.70 1775 1075 1680 785 1565 655 1430 560 0.80 1025 450 920 370 840 330 695 270 0.80 1690 1050 1590 760 1485 630 1370 540 0.90 945 800 335 700 290 605 250 0.90 1580 1010 1485 735 1405 610 1270 510 430 EL195DF070P48B PERFORMANCE (Less Filter) External Static Pressure in. w.g. EL195DF110P60C PERFORMANCE (Less Filter) Air Volume / Watts at Various Blower Speeds High MediumHigh MediumLow Low cfm Watts cfm Watts cfm Watts cfm Watts External Static Pressure in. w.g. 0.00 Air Volume / Watts at Various Blower Speeds High MediumHigh MediumLow Low cfm Watts cfm Watts cfm Watts cfm Watts 0.00 1885 935 1830 815 1810 720 1700 640 0.10 1850 910 1805 795 1785 705 1680 630 0.10 2365 1235 2195 905 1960 775 1625 635 0.20 1775 890 1750 775 1710 690 1620 610 0.20 2275 1200 2125 890 1950 760 1635 625 0.30 1715 870 1685 755 1640 660 1575 595 0.30 2200 1180 2060 880 1900 735 1620 610 0.40 1645 855 1620 735 1595 650 1495 575 0.40 2115 1150 1995 850 1845 710 1620 600 0.50 1575 835 1525 715 1485 625 1440 555 0.50 2040 1115 1940 835 1795 695 1585 580 0.60 1505 815 1450 690 1425 610 1360 540 0.60 1955 1090 1855 810 1745 670 1540 565 0.70 1390 790 1360 675 1340 590 1270 525 0.70 1860 1070 1730 765 1640 650 1515 550 0.80 1280 770 1270 650 1255 570 1210 505 0.80 1735 1030 1620 740 1590 620 1415 535 0.90 1200 740 1185 635 1160 550 1090 485 0.90 1640 1010 1535 715 1480 600 1330 510 Page 41 2375 1250 2205 915 1975 785 1630 640 2 − Have a shallow pan ready to empty condensate water. Service 3 − Remove the clean out cap from the condensate trap and empty water. Inspect the trap then reinstall the drain plug. WARNING ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage. Before servicing, disconnect all electrical power to furnace. When servicing controls, label all wires prior to disconnecting. Take care to reconnect wires correctly. Verify proper operation after servicing. At the beginning of each heating season, system should be checked as follows by a qualified service technician: Blower Check the blower wheel for debris and clean if necessary. The blower motors are prelubricated for extended bearing life. No further lubrication is needed. WARNING The blower access panel must be securely in place when the blower and burners are operating. Gas fumes, which could contain carbon monoxide, can be drawn into living space resulting in personal injury or death. Filters All air filters are installed external to the unit. Filters should be inspected monthly. Clean or replace the filters when necessary to ensure proper furnace operation. Table 3 lists recommended filter sizes. Exhaust and air intake pipes Check the exhaust and air intake pipes and all connections for tightness and to make sure there is no blockage. NOTE − After any heavy snow, ice or frozen fog event the furnace vent pipes may become restricted. Always check the vent system and remove any snow or ice that may be obstructing the plastic intake or exhaust pipes. Electrical 1 − Check all wiring for loose connections. 2 − Check for the correct voltage at the furnace (furnace operating). 3 − Check amp−draw on the blower motor. Motor Nameplate__________Actual__________ Winterizing and Condensate Trap Care 1 − Turn off power to the furnace. Cleaning Heat Exchanger If cleaning the heat exchanger becomes necessary, follow the below procedures and refer to figure 1 when disassembling unit. Use papers or protective covering in front of furnace while removing heat exchanger assembly. 1 − Turn off electrical and gas supplies to the furnace. 2 − Remove the furnace access panels. 3 − Disconnect the wires from the gas valve. 4 − Remove gas supply line connected to gas valve. Remove the burner box cover (if equipped) and remove gas valve/manifold assembly. 5 − Remove sensor wire from sensor. Disconnect 2-pin plug from the ignitor. 6 − Disconnect wires from flame roll−out switches. 7 − Loosen clamps at vent elbow. Disconnect condensate drain tubing from flue collar. and remove the vent elbow. 8 − Loosen clamps and remove combustion air intake flexible connector if equipped. 9 − Remove four burner box screws at the vestibule panel and remove burner box. Set burner box assembly aside. NOTE − If necessary, clean burners at this time. Follow procedures outlined in Burner Cleaning section. 10 − Mark and disconnect all combustion air pressure tubing from cold end header collector box. 11 − Mark and remove wires from pressure switch assembly. Remove pressure switch assembly. Keep tubing attached to pressure switch assembly. 12 − Disconnect the plug from the combustion air inducer. Remove two screws which secure combustion air inducer to collector box. Remove combustion air inducer assembly. Remove ground wire from vest panel. 13 − Remove electrical junction box from the side of the furnace. 14 − Disconnect condensate line from cold end header box. Remove cold end header box. 15 − Loosen clamps on exhaust and air intake pipe seal plate. Slide exhaust and intake pipes up and out to clear blower deck. Remove exhaust and air intake pipe seal plate. 16 − Mark and disconnect any remaining wiring to heating compartment components. Disengage strain relief bushing and pull wiring and bushing through the hole in the blower deck. 17 − Remove the primary limit from the vestibule panel. 18 − Remove two screws from the front cabinet flange at the blower deck. Spread cabinet sides slightly to allow clearance for removal of heat exchanger. Page 42 19 − Remove screws along vestibule sides which secure vestibule panel and heat exchanger assembly to cabinet. Remove two screws from blower rail which secure top heat exchanger flange. Remove heat exchanger from furnace cabinet. 20 − Back wash heat exchanger with soapy water solution or steam. If steam is used it must be below 275°F (135°C) . 21 − Thoroughly rinse and drain the heat exchanger. Soap solutions can be corrosive. Take care to rinse entire assembly. 22 − Reinstall heat exchanger into cabinet making sure that the clamshells of the heat exchanger assembly are engaged properly into the support bracket on the blower deck. Remove the indoor blower to view this area through the blower opening. 23 − Re-secure the supporting screws along the vestibule sides and top to the cabinet. 24 − Reinstall cabinet screws on front flange at blower deck. 25 − Reinstall the primary limit on the vestibule panel. 26 − Route heating component wiring through hole in blower deck and reinsert strain relief bushing. 27 − Reinstall electrical junction box. 28 − Reinstall exhaust and air intake pipe seal plate. Reinstall exhaust and air intake pipes and tighten clamps on pipe seal plate. 29 − Reinstall the cold end header box. 30 − Reinstall the combustion air inducer. Reconnect the combustion air inducer to the wire harness. 31 − Reinstall pressure switch assembly and reconnect pressure switch wiring. 32 − Carefully connect combustion air pressure switch tubing from pressure switches to proper ports on cold end header collector box. 33 − Reinstall condensate trap. 34 − Secure burner box assembly to vestibule panel using four existing screws. Make sure burners line up in center of burner ports. 35 − Reconnect exhaust piping and exhaust drain tubing. 36 − Reconnect flame roll−out switch wires. 37 − Reconnect sensor wire and reconnect 2−pin plug from ignitor. 38 − Reinstall gas valve manifold assembly. Reconnect gas supply line to gas valve. 39 − Reinstall burner box cover if equipped. 40 − Reconnect plug to gas valve. 41 − Replace the blower compartment access panel. Page 43 42 − Follow lighting instructions on unit nameplate to light and operate furnace for 5 minutes to ensure the furnace is operating properly. 43− Check all piping connections, factory and field, for gas leaks. Use a leak detecting solution or other preferred means. CAUTION Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed. Do not use matches, candles, flame or other sources of ignition to check for gas leaks. 44 − Replace access panel. Cleaning the Burner Assembly (if needed) 1 − Turn off electrical and gas power supplies to furnace. Remove upper and lower furnace access panels. 2 − Disconnect the 2−pin plug from the gas valve. 3 − Remove the burner box cover (if equipped). 4 − Disconnect the gas supply line from the gas valve. Remove gas valve/manifold assembly. 5 − −Loosen clamps and remove combustion air intake flexible connector (if equipped). 5 − Mark and disconnect sensor wire from the sensor. Disconnect plug from the ignitor at the burner box. 6 − Remove four screws which secure burner box assembly to vest panel. Remove burner box from the unit. 7 − Use the soft brush attachment on a vacuum cleaner to gently clean the face of the burners. Visually inspect the inside of the burners and crossovers for any blockage caused by foreign matter. Remove any blockage. 8 − Reinstall the burner box assembly using the existing four screws. Make sure that the burners line up in the center of the burner ports. 9 − Reconnect the sensor wire and reconnect the 2−pin plug to the ignitor wiring harness. 10 − Reinstall combustion air intake flexible connector (if equipped), secure using existing clamps. 11 − Reinstall the gas valve manifold assembly. Reconnect the gas supply line to the gas valve. Reinstall the burner box cover. 12 − Reconnect plug to gas valve. 13 − Replace the blower compartment access panel. 14 − Refer to instruction on verifying gas and electrical connections when re−establishing supplies. 15 − Follow lighting instructions to light and operate furnace for 5 minutes to ensure that heat exchanger is clean and dry and that furnace is operating properly. 16 − Replace access panel. Planned Service A service technician should check the following items during an annual inspection. Power to the unit must be shut off for safety. Fresh air grilles and louvers (on the unit and in the room where the furnace is installed) − Must be open and unobstructed to provide combustion air. Burners − Must be inspected for rust, dirt, or signs of water. Vent pipe − Must be inspected for signs of water, cracked, damaged or sagging pipe, or disconnected joints. Unit appearance − Must be inspected for rust, dirt, signs of water, burnt or damaged wires, or components. Blower access door − Must be properly in place and provide a seal between the return air and the room where the furnace is installed. Return air duct − Must be properly attached and provide an air seal to the unit. Operating performance − Unit must be observed during operation to monitor proper performance of the unit and the vent system. Combustion gases − Flue products must be analyzed and compared to the unit specifications. Problems detected during the inspection may make it necessary to temporarily shut down the furnace until the items can be repaired or replaced. Instruct the homeowners to pay attention to their furnace. Situations can arise between annual furnace inspections that may result in unsafe operation. For instance, items innocently stored next to the furnace may obstruct the combustion air supply. This could cause incomplete combustion and the production of carbon monoxide gas. Ignition Control Board Diagnostic Codes RED LED Flash Code Off Heartbeat1 Diagnostic Codes / Status of Furnace No power to control or board fault detected Control powered − displayed during all modes of operation if no errors are detected 1 Reverse Line Voltage Polarity 2 Improper Earth Ground 3 Burner failed to light, or lost flame during heat demand 4 Low Flame Signal − check flame sensor 5 Watchguard − burner failed to light, exceeded maximum number of retries or recycles. 6 Ignitor Circuit Failure − not available on this control 7 Primary or Secondary Limit Open or Watchguard Mode − Limit Switch Open longer than 3 minutes 8 Rollout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard − Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation of combustion air inducer 12 Flame Sensed without gas valve energized 13 Low Line Voltage Notes Note1 A "Heartbeat" is indicated by a "Slow Flash" − 1 sec on 1 sec off, repeating Note Error codes are indicated by a "Rapid Flash" − the LED flashes X times at 1/2 sec on 1/2 sec off, remains off for 3 sec, then repeats Note Last 10 error codes are stored in memory − To recall, press and release button, most recent will be displayed first, LED off for 3 sec, then next error code is displayed, etc. To clear error codes, depress and hold button longer than 5 seconds. Page 44 Troubleshooting: Heating Sequence of Operation HEATING SEQUENCE OF OPERATION ABNORMAL HEATING MODE NORMAL HEATING MODE POWER ON GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER DELAY OFF. LED SLOW FLASH (RESET CONTROL BY TURNING MAIN POWER OFF.) NO CONTROL SELF−CHECK OKAY? YES NO LED FLASHES CODE 1 − POLARITY REVERSED. IS POLARITY CORRECT? YES NO LED FLASHES CODE 2 − IMPROPER GROUND. IS THERE A PROPER GROUND? YES NO LED FLASHES CODE 13 − LOW LINE VOLTAGE. CONTROL WILL NOT RESPOND TO A CALL FOR HEATING UNTIL VOLTAGE RISES ABOVE 75 VOLTS. IS VOLTAGE ABOVE 70 VOLTS? YES ROLLOUT SWITCH CLOSED? LED FLASHES CODE 8 − ROLLOUT SWITCH OPEN. GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES AND POWER IS RESET OR T’STAT IS INTERRUPTED FOR MINIMUM OF 1 SECOND. NO YES BURNER OFF? LED FLASHES CODE 12 − FLAME SENSED WITHOUT GAS VALVE ENERGIZED. GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON HEATING SPEED. NO (Flame sensed without gas valve energized) YES NO NORMAL OPERATION: LED SLOW FLASH YES THERMOSTAT CALLS FOR HEAT: LED SLOW FLASH NO YES LED FLASHES CODE 7 − PRIMARY LMIT OPEN. COMBUSTION AIR INDUCER OFF.INDOOR BLOWER ON PRIMARY LIMIT SWITCH. CLOSED? YES NO IS COMBUSTION AIR PRESSURE SWITCH OPEN? YES LED FLASHES CODE 11 − PRESSURE SWITCH CLOSED. GAS VALVE OFF COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY. (Sequence holds until pressure switch opens or thermostat resets control.) IS COMBUSTION AIR INDUCER ENERGIZED? YES HAS COMBUSTION AIR PRESSURE SWITCH CLOSED IN 2.5 MINUTES? NO YES CONTINUED NEXT PAGE Page 45 LED FLASHES CODE 9 − PRESSURE SWITCH FAILED TO CLOSE OR OPENED DURING HEAT DEMAND. PRESSURE SWITCH IS IN WATCHGUARD MODE. GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY. IS 5-MINUTE RESET PERIOD COMPLETE? YES Troubleshooting: Heating Sequence of Operation (Continued) HEATING SEQUENCE CONTINUED NORMAL HEATING MODE ABNORMAL HEATING MODE 15-SECOND COMBUSTION AIR INDUCER PREPURGE INITIATED BY CLOSED PRESSURE SWITCH. YES NO IS VOLTAGE ABOVE 70 VOLTS? IGNITOR WARM-UP −− 20 SECONDS. YES 4-SECOND TRIAL FOR IGNITION. GAS VALVE OPENS. IGNITOR ENERGIZED FOR FIRST 3 SECONDS OF THE TRIAL. YES FLAME STABILIZATION PERIOD. NO YES LED FLASHES CODE 13 − LOW LINE VOLTAGE. ONCE VOLTAGE IS ABOVE 75 VOLTS, HEATING SEQUENCE RESTARTS. GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER OFF. HAS CONTROL FAILED TO SENSE FLAME FOR NO FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND? NO 4 SECONDS FLAME RECTIFICATION CURRENT CHECK. CAN FLAME BE PROVEN WITHIN 4 SECONDS AFTER GAS VALVE OPENS? (0.5 microamps) YES YES NO NO HAS CONTROL RESET IGNITION SEQUENCE FOUR TIMES? FLAME PRESENT? YES YES NO FLAME SIGNAL 1.5 MICROAMPS OR GREATER? YES INDOOR BLOWER ON AFTER 30−SECOND DELAY YES PRIMARY LIMIT SWITCH CLOSED? YES LED SIGNAL WATCHGUARD FAILURE CODE WATCHGUARD MODE. GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH DELAY IS 60-MINUTE RESET PERIOD COMPLETE? LED FLASHES CODE 4 − LOW FLAME SIGNAL. (Does not affect operation of control) LED FLASHES CODE 7 − PRIMARY LIMIT OPEN GAS VALVE DE−ENERGIZED. NO COMBUSTION AIR INDUCER DE−ENERGIZED. INDOOR BLOWER ON UNTIL SWITCH CLOSES. LIMIT SWITCH CLOSED? YES HAS PRIMARY LIMIT RESET TIME EXCEEDED 3 MINUTES? YES YES LED FLASHES CODE 7 − PRIMARY LIMIT OPEN. GAS VALVE, COMB. AIR INDUCER AND INDOOR BLOWER OFF. LEDs SIGNAL LIMIT SWITCH OPEN UNTIL MAIN POWER IS INTERRUPTED OR T’STAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM. 60−MINUTE WATCHGUARD PERIOD STARTS AT TIME LIMIT CLOSES. IS 60−MIN. PERIOD COMPLETE? NO NO ROLLOUT SWITCH CLOSED? YES COMBUSTION AIR PRESSURE SWITCH CLOSED? YES THERMOSTAT DEMAND SATISFIED. YES LED SLOW FLASH. YES COMB. AIR INDUCER CONTINUES 5-SECOND POST PURGE AFTER T’STAT DEMAND IS SATISFIED. INDOOR AIR BLOWER COMPLETES SELECTED OFF" DELAY BEFORE SHUTTING OFF. NO LED FLASHES CODE 8 − ROLLOT SWITCH OPEN. GAS VALVE POWER OFF. COMBUSTION AIR INDUCER POWER ON. INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM. HAS GAS VALVE DE−ENERGIZED. YES PRESSURE NO COMBUSTION AIR INDUCER ON. SWITCH INDOOR BLOWER OFF WITH DELAY OPENED 5 HAS CAB SWITCH CLOSED IN 2.5 MINUTES? TIMES IN SAME HEAT NO DEMAND? 5-MINUTE PRESSURE SWITCH WATCHGUARD MODE. 1 HR PRESSURE SWITCH WATCHGUARD MODE LED FLASHES CODE 10 Page 46 Troubleshooting: Cooling Sequence of Operation COOLING SEQUENCE OF OPERATION NORMAL COOLING MODE ABNORMAL COOLING MODE POWER ON IGNITION CONTROL MAIN POWER ON. NO CONTROL SELF DIAGNOSTIC CHECK. IS CONTROL OPERATING NORMALLY? GAS VALVE OFF. COMBUSTION AIR INDUCER OFF. INDOOR BLOWER OFF WITH NORMAL DELAY. SIGNAL CIRCUIT BOARD FAILURE AT LED. INTERRUPT MAIN POWER TO RESET CONTROL. YES NO IS THERE A PROPER GROUND? YES NO IS POLARITY CORRECT? YES LED FLASHES CODE 2 IMPROPER GROUND CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION. LED FLASHES CODE 1 POLARITY REVERSED CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION. NO LED FLASHES CODE 13 LOW VOLTAGE. CONTROL WILL CONTINUE TO CALL FOR COOLING IN THIS CONDITION. IS VOLTAGE ABOVE 70 VOLTS? YES NO ROLLOUT SWITCH MONITORED CONTINUOUSLY. IS ROLLOUT SWITCH CLOSED? YES LED: SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE. THERMOSTAT CALLS FOR COOLING. COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2-SECOND DELAY (COOLING SPEED). EAC TERM. ENERGIZED. THERMOSTAT OPENS. COMPRESSOR OFF. SYSTEM FAN AND EAC TERM. OFF WITH 45-SECOND DELAY. Page 47 LED FLASHES CODE 8 ROLLOUT SWITCH OPEN. GAS VALVE OFF. COMBUSTION AIR INDUCER ON. INDOOR BLOWER ON. SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF/ON FOR 1 SEC. MINIMUM. Troubleshooting: Continuous Fan Sequence of Operation CONTINUOUS FAN SEQUENCE OF OPERATION LED: SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT SEQUENCE. MANUAL FAN SELECTION MADE AT THERMOSTAT. CONTROL (G) ENERGIZES SYSTEM FAN AT FAN SPEED. EAC TERMINAL IS ENERGIZED. THERMOSTAT CALLS FOR HEAT (W). YES NO THERMOSTAT CALLS FOR COOLING. YES SYSTEM FAN SWITCHED TO COOL SPEED. EAC TERM. REMAINS ON. NO SYSTEM FAN CONTINUES FAN SPEED WITHOUT INTERRUPTION. EAC TERMINAL REMAIN ON. HUM TERMINAL IS ENERGIZED WITH COMBUSTION AIR BLOWER. SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 SECOND DELAY. EAC AND HUM TERMINAL REMAIN ON. THERMOSTAT OPENS. MANUAL FAN SELECTION MADE AT THERMOSTAT. CONTROL (G) ENERGIZES SYSTEM FAN AT FAN SPEED. EAC TERM. ENERGIZED. THERMOSTAT OPENS. HUM. TERMINAL OFF AFTER POST PURGE BY COMBUSTION AIR BLOWER. SYTEM FAN SWITCHES TO FAN SPEED AFTER BLOWER OFF DELAY. EAC CONTINUES WITHOUT INTERRUPTION. Page 48 Repair Parts List The following repair parts are available through Lennox dealers. When ordering parts, include the complete furnace model number listed on the CSA nameplate −− Example: EL195DF04536B. All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier. Heating Parts Cabinet Parts Outer access panel Blower access panel Top Cap Control Panel Parts Transformer Integrated control board Door interlock switch Blower Parts Blower wheel Motor Motor mounting frame Motor capacitor Blower housing cutoff plate Flame Sensor Heat exchanger assembly Gas manifold Combustion air inducer Gas valve Main burner cluster Main burner orifices Pressure switch Ignitor Primary limit control Flame rollout switches Page 49 Start−Up & Performance Check List UNIT SET UP Furnace: Model Number_______________ Serial Number_________________ Line Voltage SUPPLY AIR 2 4 1 GAS SUPPLY Natural Gas LP Propane Gas 3 Piping Connections Tight 2 Leak Tested Flter Supply Line Pressure W.C.________ RETURN AIR 1 Gas Supply Pressure 3 1 DUCT SYSTEM SUPPLY AIR DUCT Sealed Insulated (if necessary) 2 RETURN DUCT INTAKE / EXHAUST PIPE Sealed All Joints Primed and Glued Filter Installed and Clean Terminations Installed Properly Grilles Unobstructed Horizontal Pipes Sloped (if applicable) 4 Condensate Trap Primed / Line Sloped VOLTAGE CHECK Supply Voltage _____ Electrical Connections Tight Pipes Supported Heat Cable Installed and Operable (if applicable) Page 50 UNIT OPERATION HEATING MODE 1 2 COOLING MODE GAS MANIFOLD PRESSURE W.C._____ COMBUSTION SAMPLE CO2%______CO PPM_______ 3 INDOOR BLOWER AMPS______ 4 TEMPERATURE RISE 3 INDOOR BLOWER AMPS______ 4 TEMPERATURE DROP Return Duct Temperature _________ Supply Duct Temperature _ _______ Temperature Drop = _________ 5 Supply Duct Temperature ________ Return Duct Temperature _ _____ Temperature Rise = ________ 5 6 TOTAL EXTERNAL STATIC Supply External Static _______ Return External Static + ______ Total External Static = _______ 8 DRAIN LINE Leak Free 9 CONDENSATE LINE THERMOSTAT Adjusted and Programmed Leak Free 7 TOTAL EXTERNAL STATIC (dry coil) Supply External Static _______ Return External Static + ______ Total External Static = _______ Explained Operation to Owner VENT PIPE Leak Free Combustion CO2 2 7 SUPPLY AIR Thermostat Temperatures 8 Gas Manifold Pressure 9 4 1 Blower Motor Amps 3 6 Duct Static 5 RETURN AIR Contractor’s: Name_________________________Telephone_____________Checklist Completed____________________ Job Address_____−________________________________Technician’s Name___________________________________ Page 51 Requirements for Commonwealth of Massachusetts Modifications to NFPA−54, Chapter 10 Revise NFPA−54 section 10.8.3 to add the following requirements: For all side wall, horizontally vented, gas−fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above the finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 1 − INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall, horizontally vented, gas−fueled equipment, the installing plumber or gasfitter shall observe that a hard−wired carbon monoxide detector with an alarm and battery backup is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery−operated or hard−wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall, horizontally vented, gas−fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard−wired carbon monoxide detectors. a − In the event that the side wall, horizontally vented, gas−fueled equipment is installed in a crawl space or an attic, the hard−wired carbon monoxide detector with alarm and battery back−up may be installed on the next adjacent floor level. b − In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery−operated carbon monoxide detector with an alarm shall be installed. 2 − APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 3 − SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented, gas−fueled heating appliance or equipment. The sign shall read, in print size no less than one−half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS." 4 − INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas−fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4. EXEMPTIONS: The following equipment is exempt from 24 CMR 5.08(2)(a) 1 through 4: 1 − The equipment listed in Chapter 10 entitled Equipment Not Required to Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and 2 − Product Approved side wall, horizontally vented, gas− fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include: 1 − Detailed instructions for the installation of the venting system design or the venting system components: and 2 − A complete parts list for the venting system design or venting system. MANUFACTURER REQUIREMENTS − GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of Product Approved side wall, horizontally vented, gas−fueled equipment does not provide the parts for venting the flue gases, but identifies special venting systems," the following requirements shall be satisfied by the manufacturer: 1 − The referenced special venting system" instructions shall be included with the appliance or equipment installation instructions; and 2 The special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. A copy of all installation instructions for all Product Approved side wall, horizontally vented, gas−fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation. Page 52
advertisement