Omron CS1 Series PLC System Overview
The CS1 Series PLCs are a powerful and flexible control system that can be used for a wide range of applications. The CS1 Series is designed to be fast, have a large program and data memory, and be easy to use and maintain. They include a wide range of I/O modules and offer advanced communications capabilities.
Advertisement
Advertisement
S Y S T E M O V E R V I E W
Superior Control Performance . . . . . . . . . . . . . 3
Large Program and Data Memory with Increased I/O Capacity . . . . . . . . . . . . . . . 4
Programming Flexibility for
New and Existing Applications . . . . . . . . . . . . . 5
Large and Diverse I/O Offering . . . . . . . . . . . . . 6
Enhanced Design and
Development Environment . . . . . . . . . . . . . . . . 7
Powerful Information Management . . . . . . . . 19
Improved Connectivity and Compatibility . . . . 23
Maintenance and Management . . . . . . . . . . . 26
Analog Signal Processing at All System Levels . . . . . . . . . . . . . . . . . . . 31
Full Range of Positioning and Speed Control . . . . . . . . . . . . . . . . . . . . . 32
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
5
System Overview
Superior Control Performance
3
Fastest Processing Speeds in the Industry
CS1 Series PLCs offer you flexibility and power for almost any control application.
Comparing CS1 Controllers with the Existing Omron C200H Alpha Series Controllers
The following is a comparison of the existing Omron C200H Alpha Series controllers (previously among the fastest available) to the new CS1 Series.
The examples below show how CS1 can manage the complete control and logic execution of your application in one-half to one fifth the time of the existing C200H Alpha Series controllers.
Up to 5 Times Faster Execution Speed
Faster instruction processing includes:
•
0.04
µ s for LD
(Load Instruction: a sequence input instruction)
•
0.25
µ s for MOV
(Move instruction: data movement instructions)
•
0.17
µ s for CMP
(Compare instruction: symbol comparison instruction)
Special instructions are processed almost as fast as basic ones (e.g., as fast as 0.25
µ s for some instructions).
Up to 15 Times Faster
Peripheral Servicing and I/O Refresh Speeds
CS1 refresh time for 96 input points: 0.02 ms. For 96 output points: 0.02 ms. For Serial Communications Modules
(256 words of data): 0.02 ms (4 times faster).
C200H Alpha Series
I/O refresh
64-pt Input Module
32-pt Input Module
0.2 ms
0.1 ms
CS1 Series
I/O refresh
96-pt Input Module 0.02 ms
96-pt Output Module
0.02 ms
C200H Alpha Series CS1 Series 64-pt Output Module
32-pt Output Module
0.13 ms
0.1 ms
Communications
Module (256 words)
0.45 ms
0.104 to
0.208
µ s
0.04
µ s
Communications
Module (256 words)
0.17 ms
0.417 to
0.625
µ s
0.25
µ s
0.417 to
0.521
µ s
0.17
µ s
Up to 3 Times Faster Overall Cycle Speed
The following examples are for 20K-step programs.
C200H Alpha Series CS1 Series
I/O refresh
Peripheral service
15 ms
I/O refresh
Peripheral service
5 ms
6
System Overview
Large Program and Data Memory with
Increased I/O Capacity
3
CS1 Series PLCs Provide Ample Capacity for Advanced Control and Data Processing
Comparing CS1 Controllers with the Existing Omron C200H Alpha Series Controllers
Up to 4 Times the Program Capacity
Create programs with up to 250K steps.
Program instructions require 1 to 7 steps of memory.
One step of CS1 Program Memory will generally provide the same (and sometimes more) available memory as the previous one Word of C200H Alpha memory.
Up to 4.5 Times the Data Memory
Use up to 448K words of built-in data memory.
C200H Alpha Series CS1 Series
C200H Alpha Series
63.2K
words max.
CS1 Series
D0000
100K words
32K words
Up to 13 banks
(416K words)
D32767
E0_00000
EC_00000
448K words
250K steps max.
Up to 4.3 Times the I/O Capacity
Handle up to 5120 local I/O points.
More than 5120 I/O points can be supported by utilizing remote I/O options such as: CompoBus/S, DeviceNet, or
SYSMAC Bus remote I/O.
C200H Alpha Series CS1 Series
16 Times the Number of Timers/Counters
Program up to 4096 timers and 4096 counters (each).
C200H Alpha Series CS1 Series
512 timers and counters total
4096 timers and
4096 counters (each)
1184 I/O points
5120 I/O points
7
Additional Information: Refer to the CS1 Operation Manual (W339) for more details and information.
System Overview
Programming Flexibility for New and Existing Applications
3
Expansive Instruction Set
Symbol Comparison, Data Control, Network Communications,
Text String Processing, and many other new instructions.
New Instructions
Text String Processing, FIFO and LIFO, Record Processing for Table Data, File Memory Processing, Repeat Processing
(FOR/NEXT), Command Send (CMND), Index Register
Processing, Floating-point, and more.
3
Large Capacity Data Handling with Each Instruction
The basic operand specifications have been converted from
BCD to binary to increase data handling capacity.
Item
Block transfers
Indirect addressing range
C200H Alpha Series CS1 Series
0 to 9999 words
DM 00000 to
DM 9999
0 to 65535 words
D00000 to
D32767
3
Powerful Conversion Utility
You Can Use Existing Legacy Programs
CX-Programmer can be used to help convert programs from other Omron PLCs.
The utility will import existing SSS, LSS, CVSS, CPT and
SYSWIN program files.
Instruction
Operand
Binary specification
0000 (0 decimal) to FFFF (65,535 decimal)
Large capacity
C Series
CV Series
CX-Programmer
Conversion Utility CS1 Series
Additional Information: For more detail on the entire instruction set, please refer to Section 7, Instruction Set.
8
9
System Overview
Large and Diverse I/O Offering
3
Preserve Your Investment in Omron I/O with an Easy Migration Path
CS1 Supports All the New CS1W I/O Modules and MORE
Almost all of the Basic I/O Modules and Special I/O Modules and a portion of the Communications Modules used for the C200H,
C200HS and C200H Alpha can be used, as can C200HW Expansion I/O Racks. In addition, many new and enhanced CS1W
Basic, Special, and Communications Modules are supported. This provides an easy migration from your existing system, while also improving overall performance.
All C200H
I/O Modules
(except for
C200H-
ID001/002)
All C200H
Special I/O
Modules
C200H Communications Modules:
SYSMAC BUS Remote I/O Master Module, DeviceNet Master Module,
CompoBus/S Master Module, and B7A Link Module
CS1 I/O Modules
CS1 Special I/O Modules
Note: Refer to the CS1 Series PLC manuals for compatibility details.
CS1 CPU Bus Modules (including Communications Modules)
System Overview
Enhanced Design and Development Environment
3
Task Programming for Structured Programming and Multi-person Development
CS1 Utilizes Tasks
With CS1 Series Controllers, programs can be divided into programming units called tasks. There are both cyclic tasks, which are executed within each cycle in a specified order, and interrupt tasks, which are executed when an interrupt occurs.
Comparison to Previous Controllers
Previously, a PLC program was something like one long scroll. Task programs can be arranged or executed in a variety of ways.
Tasks
Previous PLC Program CS1 Task Programs
Program A
Program A
Cyclic task 0
Program
Program B
Program B
Cyclic task 1
Program X
Interrupt task Cyclic task n
3
Advantages of Task Programming
Program Standardization
Task programs are created in units divided by function or by purpose. These functional units can be reused easily when programming new PLCs or systems with similar functionality.
Standard Programming Units
Easier-to-Understand Programs
With CS1, tasks are used to separate a program functionally making the program much easier to understand.
Previously, with continuous (scroll-like) programs, individual functional units were extremely difficult to find.
Continuous
Unstructured Programs
Tasks
(used in CS1)
Program ABC
Program A
Program B
Program C
Program ABD
Program A
Program B
Program D
Shorter Cycle Times
With CS1’s task programming, special instructions enable control of the execution of tasks, so only the required tasks are executed during any particular cycle.
Previously, with a continuous (scroll-like) program, many instructions (like jump) had to be used to avoid executing specific parts of the program.
TKOF
A
Wait
:
;
System Overview
Enhanced Design and Development Environment
3
CX-Programmer Windows
Development Software
CX-Programmer provides a wealth of functionality in an efficient and intuitive environment.
Windows Graphical User Interface provides an easy-to-understand environment with project windows that clearly show the data structure.
Mnemonics are supported in statement lists on ladder diagram displays and can later be converted to ladder diagram form.
You can monitor different parts of the same program in separate windows. View or scroll in both overview and detailed modes on split screens (2-way or 4-way).
Features
Easy Operation
•
Operate either with or without using a mouse.
•
Navigate using directory style display sections.
•
Enter input/output instructions with function keys.
•
Utilize the search function to locate desired instructions or information.
•
Display operand input ranges.
•
Split the screen 2 ways or 4 ways.
•
Convert text inputs to ladder diagrams. Either enter mnemonics into ladder diagram displays or convert text from text editors.
•
Program with I/O tags (names) rather than specific addresses.
Many Display and Monitoring Options
•
Present value monitoring of specified addresses.
•
Watch Windows enable monitoring of specific address locations.
•
Output Windows can display: errors, search results, file read errors, and program comparison results.
Data Compatibility with Windows Applications
•
Import I/O table data such as name, address, and I/O comment from Microsoft Excel
spreadsheets.
Flexible Maintenance Functions
•
Force-setting/resetting.
•
Differential monitoring.
•
Timer/Counter set value changes.
•
Cross-references.
•
Data trace and time chart monitoring.
•
Online editing of multiple locations and controllers.
•
Online editing of different tasks from different computers.
Remote Programming and Monitoring
•
Easily access (local or remote) networked PLCs through the connected PLC.
•
Access remote PLCs via modem connections.
•
Store/read comments inside various I/O modules
•
Handle CPU data (programs, parameters, memory contents, or comments) in memory files on optional Flash
Memory Cards,or built-in data file (EM) file memory.
•
Drag and drop files between Memory Cards in a computer or in the CPU. (FTP File Transfer)
•
Display time-stamped error histories (including user-generated error logs) from the CPU.
•
Protect programs from access using passwords.
System Overview
Enhanced Design and Development Environment
3
Assign and Download I/O Allocations, Comments, and Symbol Names with Microsoft
Excel
Utilize standard applications to reduce costs of program development.
I/O tables, including symbols, address, and I/O comments, can be entered into standard spreadsheets, such as
Microsoft
Excel and then used within CX-Programmer.
Microsoft Excel Spreadsheet
(or another spreadsheet)
Numeric Table in
CX-Programmer
1.
Copy I/O allocation tables and other data with MS-Excel.
2.
Paste the data into a numeric table.
Entering Operands for
Instructions
3.
Select from the numeric table when entering instruction operands. Use the presearch function to make program development even easier.
<
System Overview
Enhanced Design and Development Environment
3
Create Programs with a Text Editor
Mnemonic programs can be created with any standard text editor, such as Notepad, and then pasted into CX-Programmer as a statement list to be used as part of the program. The data can also be converted to ladder-diagram format.
1.
Copy mnemonics entered within a text editor.
Text Editor
Ladder Window
2.
Paste the text into statement list block.
Ladder Window
Statement List
3.
Then convert to ladder-diagram form.
43
System Overview
Enhanced Design and Development Environment
3
Automatic Address Allocations Allow Increased Flexibility
Symbols can be entered in a generic format for future automatic conversion to addresses.
1.
Enter symbols into the variable table, omitting specific addresses.
Local or Global Variable Table
Automatic Address Allocation Dialog Box
2.
Specify allocation word ranges in the automatic address allocation dialog box.
3.
Addresses will be automatically allocated to local or global variables memory areas.
44
System Overview
Enhanced Design and Development Environment
3
Simply Drag and Drop Programs Between Projects or Applications
Copy and paste programs to reuse them quickly using menu commands, or drag and drop.
Note: When programs are copied, any automatic allocations will still be effective, allowing similar program sections to be created.
45
System Overview
Enhanced Design and Development Environment
3
Split-Program Displays to Monitor Multiple Sections of Logic
A program can be displayed on split-screens (vertically and horizontally), allowing up to four areas of the same program to be displayed at the same time. You can monitor the entire program while also monitoring or entering specific instructions.
Split-Window Display
1.
Select the split command from the window menu.
2.
Monitoring more than one location at the same time.
Continuous Scrolling
4.
They scroll together.
3.
See the overall program while entering or monitoring specific instructions.
46
System Overview
Enhanced Design and Development Environment
3
Automatically Jump to Error Location
Jump directly to an error location from the program displayed in the check results (output window).
1.
Double-click the program within the check results
(output window).
2.
Automatically jump to the error location in the ladder-view window.
47
System Overview
Enhanced Design and Development Environment
3
Hot-Key Instruction and Symbol Recognition Reduces
Program Development Efforts
Input instructions and basic output instructions can be entered with a minimum number of key strokes.
Input with a single key.
3
Undo Undesired Programming Actions
1.
If you delete programming by mistake, just select the Undo command.
2.
The deleted instruction will be restored.
48
System Overview
Enhanced Design and Development Environment
3
Easy Online Connections with CX-Net and CX-Server
CX-Programmer provides a variety of software communications drivers. It contains both CX-Net for network configuration and management, as well as CX-Server for communications management.
You can connect to any Controller on a network. Simply enter the name of the target and gateway Controllers in order to access or monitor not only the local, but also remote Controllers.
Easily connect to local PLCs.
Or, connect just as easily to PLCs on complex networks using PLC names.
49
System Overview
Enhanced Design and Development Environment
Index Registers, Data Table, Repeat Instructions, Block Programs, Text Strings, and More.
3
Simplify Programs with Index Registers
Index registers can be used as memory pointers to enable easy indexing or changing of addresses specified for instructions.
Using an index register can often enable one instruction to perform the processing previously performed by many instructions.
Previous Simplification using index register
I/O
Pointer
Instruction A m
Instruction A m + 1
Instruction A
IR0
Repeate d
Index register
Instruction A m + 2
IR0 + 1
Indirect addressing using index register
3
Easily Handle and Manage Data
Data Table Instructions
One-word Records
Instructions are provided to find the maximum value, minimum value, and search values.
3
Step-saving Repeat Processing
Instructions are provided that let you easily repeat sections of a program. Repeat execution can also be ended for a specified condition.
1 word
1 word
1 record
1 record
Process table data, e.g., search for maximum value
Repeated n times.
Multi-word Records
Areas of memory can be defined as tables with a specified record size (words). Index registers can be used with such tables to easily sort records, search for values, or otherwise process the records in the table.
For example, the temperature, pressure, and other settings for each model of a product can be set in separate records.
3
Easy Program Logic Flow Control with
Block Programming Sections
A block of mnemonic programming instructions can be executed based on a single execution condition. IF/THEN,
WAIT, TIMER WAIT, and other instructions can be used inside the block programming section to easily program logic flow control that is difficult to program with ladder diagrams.
Ex.: Product Data by Model
Many words 1 record
Record 1
Record 2
Temp. setting
Pressure setting
Block programming section
Many words 1 record
Record N
Many words 1 record
4:
System Overview
Enhanced Design and Development Environment
3
Macro (MCRO) Instruction
Macro instructions can be used to enable multiple execution of the same subroutine program with different operands from different locations in the programs.
3
Easily Handle Text Strings
Manufacturing instructions can be obtained from a host computer or other external source, stored in memory, and then manipulated as text strings as required. The text strings can be searched, retrieved, reordered, or processed in the
CS1 Series CPU.
Host computer
Operands
PLC
Operands
Text processing within the CPU
Subroutine
Manufacturing instructions in text form
4;
System Overview
Powerful Information Management
3
Seamless Communications Between Network Types and Layers
Network hierarchies stretch from device networks through information-level networks. With Omron’s Factory Intelligent Network
Services (FINS) commands, CS1 provides seamless multi-network communications.
Omron FINS Gateway Software, Ethernet Driver
Network middleware that supports FINS message communications but also can provide ActiveX Control
Interface for Microsoft Visual Basic or Third Party HMI and SCADA software applications.
Ethernet Ethernet Module
Ethernet
Message Communications:
PLC to PLC Or PLC to host computer.
FTP Server Function:
File transfers from host computer.
Memory Card installed in CPU.
Controller Link
Socket Service:
Data transfers using TCP or
UDP (with FINS) socket services.
E-Mail Notification:
E-Mail notification from PLC to host computer for errors and other events.
Omron FINS Gateway
Software Controller Link
Driver
Controller Link
Support Board
DeviceNet
Configurator Software
Controller Link
••••
Simple Network configuration
(twisted-pair or fiber-optic cable).
••••
Data link and message communications.
⋅⋅⋅⋅
Large-capacity, flexible data links.
⋅⋅⋅⋅
Message communications and large-capacity data transfers.
••••
Links PLCs and personal computers.
••••
Optical Controller Link Modules provide a bypass function for faulty nodes, as well as increased distance.
DeviceNet (C ompoBus/D)
••••
Remote I/O message communications.
⋅⋅⋅⋅
Message communications between PLCs.
⋅⋅⋅⋅
Explicit DeviceNet messages.
••••
Various connection methods.
••••
Wide range of slaves devices
I/O terminals, remote adapters, analog
I/O terminals, sensor terminals,
I/O link modules, temperature input terminals, multiple I/O terminal, and so forth.
CompoBus/S
••••
High-speed remote I/O.
••••
Many types of slave devices
I/O terminals, remote I/O modules, sensor amp terminals, sensor terminals, bit chain terminals.
Note: FINS = Factory Intelligent Network Services. This is supported by Ethernet, Controller Link, and DeviceNet network types.
4<
System Overview
Powerful Information Management
3
Ethernet: Information Network
Ethernet Links Production Management and Production Sites Using Various Communications Services
Remote Programming and Monitoring
CX-Programmer running on a computer connected via
Ethernet can be used to program and monitor all the PLCs connected to the Ethernet Network.
FINS Message Service
Send FINS messages between PLCs or between PLCs and host computers. The FINS Gateway Runtime Software with
Ethernet Drivers can be used to handle messages from applications without having to program FINS commands directly.
CX-Programmer
Ethernet
Ethernet
FINS message
FINS message
Socket Service
Transfer data using either UDP or TCP protocol.
User-specified data
Ethernet
Note: FINS = Factory Intelligent Network Services
FTP Service
Use FTP (File Transfer Protocol) to transfer files between
Memory Cards in the CPU and computer memory.
Mail Service
Send electronic mail from the PLC to a host computer when a flag turns ON, when an error occurs, or at scheduled time intervals.
Ethernet
File data transfer
Ethernet
Additional Information: Refer to manual W343 for more details and information on CS1 Series Ethernet capabilities.
53
System Overview
Powerful Information Management
3
Network Connectivity with Twisted-pair or Fiber-Optic Cable
Controller Link can easily connect PLCs at the factory site in a fully functional control-level network.
Data Links
Efficient, large-capacity data links can be created between
PLCs or between PLCs and host computers. The FINS
Gateway Controller Link Software Drivers can be used to handle data links from applications without having to program FINS commands directly.
Data Links provide an automatic sharing of data between controllers. The data can be stored in the same or different Data Memory areas in each controller.
Note: FINS = Factory Intelligent Network Services
Remote Programming and Monitoring
CX-Programmer connected via the CPU serial or peripheral port can be used to program and monitor PLCs on the
Controller Link Network.
CX-Programmer
FINS Message Communications
Large volumes of data can be transferred between PLCs and host computers whenever necessary. The FINS Gateway Controller Link Software Drivers can be used to handle messages without having to program FINS commands directly.
FINS messages and FINS protocol support allow intelligent, seamless communications and data transfer among networked PLCs.
RS-232C
Controller Link
FINS message
Note: A Controller Link Network Support Board (NSB) can be used to connect a Personal Computer directly to the Controller Link
Network. FINS Gateway Software is recommended for these applications.
Additional Information: Refer to manual W309 for more details and information on CS1-Series Controller Link Capabilities.
54
System Overview
Powerful Information Management
3
DeviceNet: Device Layers
A multi-vendor network for bit-level communications, providing both control signals and diagnostic data.
Remote I/O Communications
Remote I/O can be freely allocated according to application needs.
Message Communications
Send FINS messages between Omron PLCs and explicit messages between Omron PLCs and devices from other manufacturers.
DeviceNet
(CompoBus/D)
Remote I/O
Select from a Wide Range of Slaves
Connect discrete I/O, analog I/O, temperature inputs, sensor
(photoelectric or proximity) inputs, and small slave PLCs
(e.g., CQM1 Series).
Connect to DeviceNet products from other manufacturers.
55
System Overview
Improved Connectivity and Compatibility
More Serial Communications Ports, More Protocols. Up to 34 Port Connections with Protocol Macro Support
3
Protocol Macros
CS1 Series PLC
RS-232C
RS-232C
Non-
Omron PC
Non-Omron
Temperature
Controller
Differences in data transfer protocols can make communications between devices by different manufacturers very difficult, even when electrical standards are the same.
Omron’s protocol macros solve this problem by enabling easy creation of communication protocols designed to match the protocol of a connected device. Protocol macros will let you communicate with essentially any device with an RS-232C, RS-422, or RS-485 port without having to write a special communications program within your logic.
The Two Main Functions of Protocol Macros
1. Creating Communications Frames
The communications frames can easily be created according to the specifications required by the connected device. Data from I/O memory in the CPU can be included as part of a communications frame to read or write I/O memory.
I/O memory
Read
Variable R ( )
Create
Address
Data
Terminator
Check code
Header
Variable W ( )
Write
I/O memory
Send
Receive
2. Creating Send/Receive Procedures
The required processing, including send and receive communications frames, can be performed one step at a time according to the results of the previous step. All of
THIS Is Created from One Ladder Instruction!
CPU
PMCR
Port/Unit
Required processing
Connected device
Step 0
Step n
(as required)
3
Two Types of Protocols
Standard System Protocols
Data transfers with Omron components can be performed using standard system protocols. There is no need to develop your own protocols in this case.
CS1 Series PLC Standard system protocol
Example: E5CK Temperature Controller
Omron component
Example: E5CK
User-created Protocols
Data transfers with non-Omron components can be created using Omron’s CX-Protocol Software Tool to define parameters.
CX-Protocol creates protocols.
CS1 Series PLC
CD-ROM
Non-Omron component
RS-232C
Additional Information: Refer to manual W344, CX-Protocol, or manual W336, CS1 Series Serial Communications Operation Manual.
56
System Overview
Improved Connectivity and Compatibility
3
Protocols for Advanced Programming
Omron provides all of the capabilities and capacity you need for the advanced programming required for human-machine interfaces (HMI), communications, data processing, and other required applications.
Host Links
Host Link (C-mode) commands or FINS commands can be sent to a host computer to read/write I/O memory, read/control the operating mode, and perform other operations for the PLC.
Unsolicited messages can also be sent from the PLC to the host computer by sending FINS commands from the ladder program using the SEND, RECV, and CMND instructions.
Custom Protocols
I/O instructions for communications ports (TXD and RXD) can be used for simple data transfers (custom protocols), such as to receive data from bar code readers or send data to a printer. Start/end codes can be specified, and other control signals can be handled. (Custom protocols can be used only for the
CPU’s built-in RS-232C port.)
CPU
TXD or
RXD
1:N NT Links
The PLC can be connected to an Omron NT Series Operator
Interface Terminal via RS-232C or RS-422A/-485 ports. I/O memory in the PLC can be allocated to various functions, including status control areas, status notifications areas, touch switches, lamps, memory tables, and other devices.
General-purpose Protocols Using BASIC Programs
An ASCII/BASIC Module can be used to create essentially any protocol for an external device using BASIC language, providing the ability to handle applications for which protocol macros cannot be created.
ASCII/BASIC Module: C200H-ASC02/11/21/31
Omron NT31 Omron NT631
Note: By utilizing 1:N NT Links, up to eight (N= 1 to 8)
NT Series Touch Screens can be connected to a single CS1
Serial Communications Port.
Additional Information: Refer to manual W336, CS1 Series Serial Communications Operations Manual.
57
System Overview
Improved Connectivity and Compatibility
3
Protocol List
The following protocols are supported for serial communications
Protocol
Host Link
(SYSMAC WAY)
Main Destinations
Computers, Omron
Operator Interface
Terminals
Description
Communications between host computers and PLCs.
Custom General-purpose devices Custom communications with general-purpose external devices.
Protocol Macros General-purpose devices
(including Omron components)
Sending/receiving messages
(communications frames) matched to the communications specifications of external devices.
1:N NT Links Omron Operator
Interface Terminals
High-speed communications using direct access with Operator
Interface Terminals.
Peripheral bus
General (written in BASIC)
Support Software Communications with Support
Software tools running on host computers.
General-purpose devices Unrestricted communications with external devices.
Commands/Instructions
Host Link commands or FINS commands
(unsolicited messages supported)
TXD and RXD instructions
PMCR instruction
None
None
BASIC
Overview of Serial Communications
Host Computer
Support Software
CX-Programmer
CX-Protocol
Programming
Console
ASCII Module
Serial
Communications
Module
Host Link
Serial
Communications
Board
CPU
NT-Series
Touch Screen
Peripheral Bus (Protocol bus)
NT Link
General-purpose
External Device
Protocol Macro
General-purpose
External Device
Temperature Controller,
Bar Code Reader, etc.
Protocol Macro
Protocol Macro
Microcomputer and other devices
Non-Omron
PLC and other devices
58
System Overview
Maintenance and Management
3
File Applications
Manipulate PLC File Data
-
Program Standardization
-
System Startup
-
File Transfer
The user program, parameters, I/O memory names, I/O comments, and block comments can all be handled as file data. File data can be used to standardize programs and initialize data for each system, and comments can be stored as file data on Flash Memory Cards.
CX-Programmer or a Programming Console can be connected to a CS1 Series PLC to transfer files between the CPU’s memory and
Memory Cards (or EM File Memory).
As Windows files, file icons can be dragged and dropped to a Memory Card or computer file server to easily copy the files (FTP).
Note: A Memory Card Adapter can be used to mount Memory Cards into a PCMCIA card slot on a computer to use them as computer memory storage devices.
CPU
System A
Memory
EM File
Memory
Memory
Card
System B
Manage Data Onsite Simply by Utilizing a Programming Console
A Programming Console can be connected to the PLC to transfer files between the
Memory Cards and CPU’s memory (or
EM File Memory). A Programming Console and Memory Card are all you need to change data onsite.
Download
PC Card Adapter
Memory Card
System C
User program
PC Setup
I/O tables
DM data
Stored and standardized by system or
Programming Device
Upload
Programming
Console
Change Program Simply by Changing Cards
File data can be automatically transferred from the Memory Card to the CPU when power is turned ON, enabling Memory
Cards to be used for operation in the same way as is possible with ROM.
Step 1
Save transfer files in Memory Card.
Step 2
Create Memory Cards for each product or line.
A B C
Step 3
Replace the Memory
Card and turn ON power.
Power ON
Manipulate Files During Operation
File read and write instructions can be used during operation to transfer files between the
CPU’s memory and Memory Cards (or EM
File Memory). Trend data, quality control data, other data from memory can be stored during operation in Memory Cards or EM File
Memory.
FWRIT
EM
File memory
Saved as file
59
System Overview
Maintenance and Management
3
A Wide Range of Special Functions
Cycle Time and Interrupt Functions
Application
1.
Reducing the cycle time.
Solutions
•
Place tasks that are not being executed on standby.
•
Create subroutines for portions of tasks executed only under special conditions.
•
Disable cyclic refreshing for Special I/O Modules when not required each cycle.
Shorter cycle time
2.
Eliminating deviations in I/O response time.
•
Set the cycle time to a fixed time.
Set fixed time.
3.
Stopping operation for long cycle times.
•
Use the cycle time monitoring function to stop operation when the cycle time is too long.
(Functions as a Cycle Time Watchdog Timer.)
Over time
Operation stopped.
4.
Reducing I/O response time for specific I/O.
Interrupt task
•
Use an I/O interrupt task to execute an interrupt logic sequence when a specific input turns ON and then directly refresh external I/O when the appropriate instruction is executed in the interrupt program.
External I/O can be directly refreshed either by using immediate refreshing for instruction operands or by using the IORF instruction to refresh all or a specified portion of external I/O.
Interrupt input
Highspeed I/O
5.
Input signals (e.g., from photomicrosensors) that are shorter than the cycle time.
Cycle time
•
Use the high-speed pulse input function of the C200H High-density I/O Modules C200H
Special I/O Modules). These Modules can detect 1-ms or 4-ms pulses (except
C200H-OD501/OD215).
•
Use the IORF instruction to refresh inputs during program execution to further increase processing speed.
Detected
Input pulse
(This table continues on the next page.)
Additional Information: For more details on information provided above and continuing on the next 3 pages, refer to manual W339, the CS1 Operation
Manual.
5:
System Overview
Maintenance and Management
3
A Wide Range of Special Functions
Cycle Time and Interrupt Functions (continued)
Application
1.
Executing programs without being affected by the cycle time.
Solutions
•
Use I/O interrupt tasks to execute interrupt programs when specific inputs turn ON.
Interrupt program
2.
Monitoring operating conditions at a specific time interval.
•
Use a scheduled interrupt task to execute an interrupt program at a specific time interval.
Interrupt program
3.
Executing emergency processing for power interruptions.
Power OFF
Interrupt program
•
Use the power OFF interrupt task to execute an interrupt program before the CPU stops. Immediate refreshing can be used inside this interrupt program to refresh specified outputs.
4.
Generating CPU interrupts when data is received from a serial port.
•
Use an interrupt from the Serial Communications Board to execute an interrupt program when specific messages are received by the Board.
RS-232C
Interrupt program
External device
Maintenance and Troubleshooting Functions
Requirements
1.
Creating a user-defined error for specific conditions (e.g., errors or specific signals from the system) but allow the CPU to continue running.
(Non-fatal error)
Solutions
•
Use the FAL instruction to create a non-fatal user-defined error. An entry can also be left in the error history when the error occurs.
Generates a non-fatal error.
2.
Creating a user-defined error for specific conditions (e.g., errors or specific signals from the system) and stop the CPU as a result.
(Fatal error)
•
FAL can also be used just to leave error history records for specific conditions that are not necessarily errors.
•
Use the FALS instruction to create a fatal user-defined error. An entry can also be left in the error history when the error occurs.
Generates a fatal error.
•
FALS can also be used to automatically stop operation for specific conditions that are not necessarily errors.
(This table continues on the next page.)
5;
System Overview
Maintenance and Management
3
A Wide Range of Special Functions
Maintenance and Troubleshooting Functions (continued)
Application
3.
Determining if a specific output turns ON within a specified time after an input turns
ON, generating an error if the output does not turn ON, and determining the address in the program responsible for the output not turning ON.
Solutions
•
Use the FPD instruction to perform time or logic diagnosis of a specified portion of the program.
Time diagnosis
Program section
Logic diagnosis
4.
5.
Creating a history of user-defined and system errors that have occurred.
Creating an external output when a non-fatal error occurs.
•
Use the error log to record up to 20 time-stamped error records.
•
Use the Non-fatal Error Flag.
Error contents
Error
Placed in time-stamped error log
20 records
6.
Turning OFF all output from Output
Modules for specific conditions.
•
Use the Load OFF Bit.
7.
8.
Turning OFF all output from Output
Modules during trial system operation.
Maintaining I/O memory status when starting operation.
ON
Non-fatal error occurs.
OFF
•
Use the I/O memory hold function to start program execution with the same I/O memory status as the last time the program was executed.
Operation started
9.
Status held
Correcting the program during operation.
•
Use CX-Programmer to change the program as required during operation.
Program
Changes
10.
Sampling specified I/O memory bits or word data.
•
Scheduled sampling
•
Sampling once per cycle
•
User-defined sampling
•
Use the data tracing function.
Scheduled traces Cyclic traces
I/O memory
I/O memory
Trace memory
Trace memory
Continuous instructions
Sampling instruction
I/O memory
Trace memory
5<
System Overview
Maintenance and Management
3
A Wide Range of Special Functions
Remote Programming and Monitoring
Application
1.
Monitoring and editing online for remote
PLCs using telephone lines.
Solutions
•
Perform online programming and monitoring with a CX-Programmer running on a computer connected to the PLC via a modem.
2.
Online monitoring and editing with
CX-Programmer for a remote PLC connected to a network.
RS-232C
Modem
Modem
RS-232C
•
Use a Serial Communications Board or Module, connect to a PLC via a modem, use an instruction to switch to host link mode, and then program or monitor from
CX-Programmer. (It’s not necessary to cut the connection during the procedure.)
•
Use the host link gateway function to program or monitor any PLC connected to a
Controller Link or Ethernet Network to which the PLC connected to the computer running CX-Programmer is connected (via RS-232C).
3.
Programming and editing a PLC on a remote network.
Host Link
Network
•
Use the gateway function to edit any PLC connected to a network up to two networks away (3 networks including the local network). For example, a PLC on the Controller
Link Network shown below can be accessed from CX-Programmer running on a computer connected to a PLC on the Ethernet Network.
Network 2
Network 1: Ethernet Network 3: Controller Link
Additional Information: For more details on information provided on the previous 4 pages, refer to manual W339, the CS1 Operation Manual.
63
System Overview
Analog Signal Processing at All System Levels
3
Analog I/O Modules
Input Analog Signals
Input temperature data directly from
Temperature Sensors.
Analog Input and Analog Output Modules
•
Analog signals can be handled with modules that provide 4 or 8 analog input points or modules that provide 4 or 8 output points.
•
There is also a module that provides both 4 analog input points and 4 analog output points.
Temperature Sensor Modules
•
Up to 4 analog inputs can be directly input to each module from thermocouples or from platinum resistance thermometers.
64
System Overview
Full Range of Positioning and Speed Control
3
Simple Control by Writing Position Data from the CPU
Position Control Modules
C200HW-NC P P P
•
High-speed position control.
•
Easy creation of position control data.
•
No maintenance for position data in position control module.
•
Plug-and-play with Omron’s pulse servo drives.
•
1-axis, 2-axis, and 4-axis options.
Open-loop Control, Automatic Trapezoid or S-curve Acceleration/Deceleration, Pulse Outputs
Achieve a direct control operation with the Position Control Module.
Use high-speed pulse outputs with CPU commands (10 ms for C200HW-NC113).
Configure the system quickly with Windows-based Support Software and store the configuration data.
Save position data in flash memory in the Position Control Module; no backup battery maintenance required.
3
Analog Control Using Multi-task G-Language
Motion Control Module
C200H-MC
P P P ô ô and CS1W-MC P P
ô
PP
•
Advanced position control.
•
Reduced load on CPU ladder program for position control.
•
Start and stop directly with general-purpose Input.
•
Start system without origin search.
•
Manual positioning and easy sync control.
•
2-axis and 4-axis options.
•
Control up to 32-axis per PLC system.
•
Point-to-point or continuous-path.
•
Plug-and-play with Omron’s analog servo drives.
Semiclosed-loop Control, Automatic Trapezoid or S-curve Acceleration/Deceleration, Analog Outputs
Control machines with rectangular coordinate systems. (Multi-jointed horizontal robots and cylindrical robots cannot be controlled because coordinate conversion is not supported.)
Utilize the multi-task G-language to simplify the creation of motion control programs.
Supports general-purpose inputs.
Connect to motors and drives with absolute or incremental encoders.
Use the automatic pulse generator.
65
Introduction to CPU Components . . . . . . . . . 35
Specifications . . . . . . . . . . . . . . . . . . . . . . . . 36
CPU Specifications
Common Specifications
Function Specifications
General Specifications
Connection with Peripheral Devices . . . . . . . . 40
C P U O V E R V I E W
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
67
3
Nomenclature
Inner Board Compartment
An Inner Board can be mounted here.
(Serial Communications Board)
Peripheral Port
The peripheral port allows connection to programming devices, such as a
Programming Console or host computer.
RS-232C Port
The RS-232C port is connected to
Peripheral Devices other than Programming Consoles, such as host computers, general-purpose external devices, and Operator Interface Terminals.
CPU Overview
Introduction to CPU Components
Indicators
Memory Card
Connector
Memory Card Indicators
The MCPWR indicator flashes green when power is being supplied. The
BUSY indicator flashes orange when the Memory Card is being accessed.
Memory Card Power Supply Switch
The Memory Card power supply switch should be pressed to turn OFF power before removing the Memory
Card.
Memory Card Eject Button
Press the Memory Card eject button to remove the Memory Card.
Memory Card
With CS1 series PLCs, Memory Cards and specified ranges of the EM Area can be used as file memory. File memory can be used to store the entire user program, I/O memory contents, and/or parameter area contents.
File memory options Memory type
EM File Memory
EM area
Bank 0
Bank n
RAM
Capacity
8 MB
15 MB
30 MB
EM Area capacity of the CPU
(Max. capacity for CS1H-CPU67:
832 KB).
Model
HMC-EF861
HMC-EF171
HMC-EF371
N/A -- memory is contained within the CPU model.
Bank C
EM File
Memory
Note: Memory Card Adapter: HMC-AP001 (The Memory Card Adapter can be used to mount Memory Cards in PCMCIA card slots to use the
Cards on a laptop computer.
68
CPU Overview
Specifications
3
CPU Specifications
Model
CS1G-CPU42-E(V
P
)
CS1G-CPU43-E(V
P
)
CS1G-CPU44-E(V
P
)
CS1G-CPU45-E(V P )
CS1H-CPU63-E(V
P
)
CS1H-CPU64-E(V
P
)
CS1H-CPU65-E(V P )
CS1H-CPU66-E(V
P
)
CS1H-CPU67-E(V P )
I/O capacity (expansion rack capacity)
Program capacity
Data memory capacity
(See Note.)
LD instruction processing speed
960 bits (Up to 2 Expansion Racks) ) 10K steps 32K words 0.08
µ s
20K steps 32K words
1,280 bits (Up to 3 Expansion Racks) 30K steps 64K words
5,120 bits (Up to 7 Expansion Racks) 60K steps 128K words
( ) 20K steps 32K words 0.04
µ s
30K steps 64K words
60K steps 128K words
120K steps
256K words
250K steps
448K words
Built-in ports
Peripheral t d
Note: The available data memory capacity is the sum of the Data Memory (DM) and the Extended Data Memory (EM).
3
Common Specifications
Options
I B d h
Board
Item
Control method
I/O control method
Programming
Instruction length
Ladder instructions
Number of tasks
Interrupt types
CIO
(Core
I/O)
Area
CIO
Area as work bits if used as shown here.
(See
Note.)
Specification
Stored program
Cyclic scan and immediate processing are both possible.
Ladder diagram (mnemonic and block are supported)
1 to 7 steps per instruction (depends on instruction type)
Approx. 400 (3-digit function codes)
Basic instructions: 0 04
µ s min Special instructions: 0 12
µ s min (CS1H style CPUs)
288 (cyclic tasks: 32, interrupt tasks: 256)
Cyclic tasks are executed each cycle and are controlled with TKON(820) and TKOF(821) instructions.
The following 4 types of interrupt tasks are supported: Power OFF tasks: 1 max.,
Scheduled interrupt tasks: 2 max., I/O interrupt tasks: 32 max., External interrupt tasks: 256 max.
Scheduled Interrupts: Interrupts generated at a time scheduled by CPU’s built-in timer.
I/O Interrupts: Interrupts from Interrupt Input Modules.
Power OFF Interrupts: Interrupts executed when CPU’s power is turned OFF.
External I/O Interrupts: Interrupts from Special I/O Modules, CS1 Special Modules, or Inner Board (Serial
Communications Board)
I/O Area 5120 : CIO 000000 to CIO 031915 (320 words from CIO 0000 to CIO 0319 )
Setting of first rack words can be changed from default (CIO 0000) so that CIO 0000 to CIO 0999 can be used.
(80 modules; 8 racks maximum)
I/O bits are allocated to Basic I/O Modules, such as CS1 Basic I/O Modules, C200H Basic I/O Modules, and
C200H Group-2 High-density I/O Modules.
3200 (200 words): CIO 100000 to CIO 119915 (words CIO 1000 to CIO 1199 )
Link bits are used for data links and are allocated to Modules in Controller Link Systems and PC Link Systems.
Link Area
(DataLink and
PC Link)
CS1 CPU Bus
Area
6400 (400 words): CIO 150000 to CIO 189915 (words CIO 1500 to CIO 1899 )
CS1 CPU Bus Module bits store operating status of CS1 CPU Bus Modules. (25 words per module, 16 modules max.)
Special I/O Area 15,360 (960 words): CIO 200000 to CIO 295915 (words CIO 2000 to CIO 2959 )
Note that some I/O Modules are classified as Special I/O Modules. Special I/O Module bits are allocated to
CS1 Special I/O Modules and C200H Special I/O Modules.
(10 words per module, 96 modules max.); the maximum number of slots, however, is limited to 80 including expansion slots, so maximum number of modules is actually 80.)
Inner Board Area 1,600 (100 words): CIO 190000 to CIO 199915 (words CIO 1900 to CIO 1999 )
SYSMAC BUS
Area (Remote
I/O)
Inner Board bits are allocated to Inner Boards. (100 I/O words max.)
800 (50 words): CIO 300000 to CIO 304915 (words CIO 3000 to CIO 3049 )
SYSMAC BUS bits are allocated to Slave Racks connected to SYSMAC BUS Remote I/O Masters.
(10 words per rack, 5 racks max.)
Note: For CIO area, first number represents total number of available bits.
69
CPU Overview
Specifications
3
Common Specifications (continued)
Item
CIO
(Core
I/O) contd.
(The
Area can be used bits if not used
Relay Terminal
Area
(Remote I/O)
C200H Special I/O
Area
DeviceNet
(CompoBus/D
Area)
PC Link Area shown here.)
(See
Note.)
Work Area
Internal I/O Area
Holding Area
Auxiliary Area
Temporary Area
Timer Area
Counter Area
DM Area
EM Area
Data Registers
Index Registers
Task Flag Area
Trace Memory
File Memory
Specification
512 (32 words): CIO 310000 to CIO 313115 (words CIO 3100 to CIO 3131 )
I/O Terminal bits are allocated to I/O Terminal Modules (but not to Slave Racks) connected to SYSMAC BUS
Remote I/O Master Modules. (1 word per Terminal, 32 Terminals max.)
8196 (512 words): CIO 000000 to CIO 051115 (words CIO 0000 to CIO 0511)
C200H Special I/O bits are allocated to C200H Special I/O Modules and allow access separate from I/O refreshing.
1600 (100 words): Outputs: CIO 005000 to CIO 009915 (words CIO 0050 to CIO 0099)
Inputs: CIO 035000 to CIO 039915 (words CIO 0350 to CIO 0399)
DeviceNet bits are allocated to Slaves according to DeviceNet remote I/O communications.
64 bits (4 words): CIO 024700 to CIO 025015 (words CIO 0247 to CIO 0250)
When a PC Link module is used in a PC Link, use these bits to monitor PC Link errors and operating status of other CPUs in PC Link.
4800 (300 words): CIO 120000 to CIO 149915 (words CIO 1200 to CIO 1499)
37,504 (2,344 words): CIO 380000 to CIO 614315 (words CIO 3800 to CIO 6143)
These bits in CIO Area are used as work bits in programming to control program execution. They cannot be used for external I/O.
8192 bits (512 words): W00000 to W51115 (words W000 to W511)
Control programs only. (I/O from external I/O terminals is not possible.)
Note: When using work bits in programming, use bits in Work Area first before using bits from other areas.
8192 bits (512 words): H00000 to H51115 (words H000 to H511)
Holding bits are used to control execution of program, and maintain their ON/OFF status when PLC is turned
OFF or operating mode is changed.
Read only: 7168 bits (448 words): A00000 to A44715 (words A000 to A447)
Read/write: 8192 bits (512 words): A44800 to A95915 (words A448 to A959)
Auxiliary bits are allocated to specific functions.
16 bits (TR00 to TR15) Temporary bits are used to store ON/OFF execution conditions at program branches.
4096 bits: T0000 to T4095 (used for timers only)
4096 bits: C0000 to C4095 (used for counters only)
32K words: D00000 to D32767
Used as a general-purpose data area for reading and writing data in word units (16 bits). Words in DM Area maintain their status when PLC is turned OFF or operating mode is changed.
CS1 Special I/O DM Area: D20000 to D29599 (100 words ' 96 Modules). Used to set parameters.
CS1 CPU Bus DM Area: D30000 to D31599 (100 words
'
16 Modules). Used to set parameters.
Inner Board DM Area: D32000 to D32099. Used to set parameters for Inner Boards.
32K words per bank, 13 banks max.: E0_00000 to EC_32767 max. (Not available on some CPUs.)
Used as a general-purpose data area for reading and writing data in word units (16 bits). Words in EM Area maintain their status when PLC is turned OFF or operating mode is changed.
The EM Area is divided into banks, and addresses can be set by either of the following methods:
•
Changing current bank using EMBC(281) instruction and setting addresses for current bank.
•
Setting bank numbers and addresses directly.
EM data can be stored in files by specifying number of first bank. (EM file memory)
DR0 to DR15. Store offset values for indirect addressing. Data registers can be used independently in each task. One register is 16 bits (1 word).
IR0 to IR15. Store PLC memory addresses for indirect addressing. Index registers can be used independently in each task. One register is 32 bits (2 words).
32 (TK0000 to TK0031). Task Flags are read-only flags that are ON when corresponding cyclic task is executable and OFF when corresponding task is not executable or in standby status.
Up to 31 bits and 6 words in I/O memory can be specified for sampling. Trace memory capacity is 4000 words.
Memory Cards: Compact flash memory cards can be used (MS-DOS format).
EM file memory: Part of EM Area can be converted to file memory (MS-DOS format).
Omron Memory Cards with 8-MB, 15-MB, or 30-MB capacities can be used.
Note: For CIO area, first number represents total number of available bits.
6:
CPU Overview
Specifications
3
Function Specifications
Item
Constant cycle time
Cycle time monitoring
I/O refreshing options
I/O memory holding when changing operating modes
Load OFF
Input time constant setting
Specification
1 to 32,000 ms (Unit: 1 ms)
Possible (Module stops operating if cycle is too long): 1 to 40,000 ms (Unit: 10 ms)
Cyclic refreshing, immediate refreshing, refreshing by IORF(097).
Depends on ON/OFF status of IOM Hold Bit in Auxiliary Area.
Mode setting at power-up
File storage
Troubleshooting
Online editing
Program protection
All outputs on Output Modules can be turned OFF when CPU is operating in RUN or MONITOR mode.
Time constants can be set for inputs from CS1 Basic I/O Modules. The time constant can be increased to reduce influence of noise and chattering or it can be decreased to detect shorter pulses on inputs.
Possible
Automatic reading of programs from Memory Card (autoboot).
Memory Card Storage Data: User program: Program file format I/O memory, PC Setup: Data file format
(binary)
Memory Card Read/Write: User program instructions with Peripheral Devices (such as Programming
Console), computer.
Memory Card data and EM (Extended Data Memory) Area can be handled as files.
Force-set/reset, differential monitoring, data tracing (scheduled, each cycle, or when instruction is executed), instruction error tracing.
User programs can be overwritten in program-block units when CPU is in MONITOR mode. This function is not available for block programming areas.
Overwrite protection: Set using DIP switch.
Copy protection: Password set using Peripheral Device.
Error check
Error log
Serial communications
User-defined errors (i.e., user can define fatal errors and non-fatal errors)
The FPD(269) instruction can be used to check execution time and logic of each programming block.
Up to 20 errors are stored in error log. Information includes error code, error details, and time error occurred.
Built-in peripheral port: Peripheral Device (including Programming Console), Host Link, NT Link communication
Built-in RS-232C port: Peripheral Device (excluding Programming Console), Host Links, no-protocol communications, NT Links
Communications Board (sold separately): Protocol macros, Host Links, NT Links
Provided on all models.
Clock
Note: Used to store time when power is turned ON and when errors occur.
Power OFF detection time 10 to 25 ms (not fixed)
Power OFF detection delay time 0 to 10 ms (user-defined, default: 0 ms)
Memory protection Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of counter
Completion Flags and present values.
Communication of commands to a computer
Remote programming and monitoring
Three-level communications routing
Comment storage
Program check
Control output signals
Battery
Self-diagnostics
Other diagnostic functions
Note: If IOM Hold Bit in Auxiliary Area is turned ON, and PC Setup is set to maintain IOM Hold Bit status when power to PLC is turned ON, contents of CIO Area, Work Area, part of Auxiliary Area, timer
Completion Flag and PVs, Index Registers, and Data Registers will be saved for up to 20 days.
FINS commands can be sent to a computer by executing Network Communications Instructions from the
CPU.
Host Link communications can be used for remote programming and remote monitoring through a
Controller Link System.
Host Link communications can be used for remote programming and remote monitoring from devices on networks up to two levels away (Controller Link Network, Ethernet Network).
I/O comments can be stored in the CPU in Memory Cards or EM file memory.
Program checks are performed at beginning of operation for items such as no END instruction and instruction errors. A Peripheral Device can also be used to check programs.
RUN output: The contacts will turn ON (close) while the CPU is operating. These terminals are provided only on C200HW-PA204R and C200HW-PA209R Power Supplies.
Battery Set: CS1W-BAT01 (lifetime is typically 3 to 5 years)
CPU errors (watchdog timer), I/O verification errors, I/O bus errors, memory errors, and battery errors.
Storage of number of times power has been interrupted, the times of the interrupts, and system operation time (in Auxiliary Area).
6;
CPU Overview
Specifications
3
General Specifications
Item
Power Supply Options
Supply voltage
Operating voltage range
Power consumption
Inrush current
Output capacity (to
Output terminal (service supply)
RUN output
(See Note 2.)
Specifications
C200HW-PA204 C200HW-PA204S C200HW-PA204R C200HW-PA209R
100 to 120 VAC or 200 to 240 VAC, 50/60 Hz
85 to 132 VAC or 170 to 264 VAC
120 VA max.
30 A max.
180 VA max.
30 A max./100 to
120 VAC
40 A max./200 to
240 VAC
4.6 A, 5 VDC (including CPU power)
0.625 A, 26 VDC
Total: 30 W
Not provided
0.625 A, 26 VDC or 0.8 A, 24 VDC
Total: 30 W
24 VDC load current consumption
Less than 0.3 A:
+17%/11%
0.3 A or greater:
+10%/11%
(Lot No. 0187 or higher)
Not provided
9 A, 5 VDC (including
CPU power )
1.3 A, 26 VDC
Total: 45 W
Not provided Contact configuration:
SPST-NO
Switch capacity:
250 VAC, 2 A
(resistive load)
250 VAC, 0.5 A
(induction load),
24 VDC, 2 A
Contact configuration:
SPST-NO
Switch capacity:
240 VAC, 2 A
(resistive load)
120 VAC, 0.5 A
(inductive load)
24 VDC, 2 A
(resistive load)
24 VDC, 2 A
(inductive load)
20 M
Ω min. (at 500 VDC) between AC external and GR terminals (See Note 1.)
C200HW-PD024
24 VDC
19.2 to 28.8 VDC
40 W max.
30 A max.
4.6 A, 5 VDC (including
CPU power )
0.625 A, 26 VDC
Total: 30 W
Not provided
Not provided
Insulation resistance 20 M
Ω min. (at 500 VDC) between DC external and
GR terminals
(See Note 1.)
1,000 VAC 50/80 Hz for 1 min between DC external
Dielectric strength 2,300 VAC 50/60 Hz for 1 min between AC external and GR terminals (See Note 1.)
Leakage current: 10 mA max.
Noise immunity
Vibration resistance
1,000 VAC 50/60 Hz for 1 min between AC external and GR terminals (See Note 1.)
Leakage current: 10 mA max.
1,500 Vp-p, pulse width: 100 ns to 1
µ s, rise time: 1 ns pulse (via noise simulation)
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 1G (9.8 m/s
2
(Time coefficient: 8 minutes
' coefficient factor 10 = total time 80 min.)
) in X, Y, and Z directions for 80 minutes
CPU mounted to a DIN track: 2 to 55 Hz, 0.3 G in X, Y, and Z directions for 20 minutes
15G (147 m/s
2
)3 times each in X, Y, and Z directions (according to JIS CO912) leakage current: 10 mA max. (See Note 1.)
0 to 55 E C
Shock resistance
Ambient operating temperature
Ambient operating humidity
Atmosphere
Ambient storage temperature
Grounding
Enclosure
Weight
CPU Rack
Dimensions (WxHxD)
(See Note 3.)
10% to 90% (with no condensation)
Must be free from corrosive gases.
--20 to 70
E
C (excluding battery)
Less than 100
Ω
Mounted in a panel.
All models are each 6 kg max.
2 slots: 198.5
'
157
'
123 mm
3 slots: 260
'
130
'
123 mm
5 slots: 330 ' 130 ' 123 mm
Conforms to UL, CSA, NK, and EC directives.
8 slots: 435
10 slots: 505
'
'
130
130
'
'
123 mm
123 mm
Standards
Note: 1.
Disconnect the Power Supply’s LG terminal from the GR terminal when testing insulation and dielectric strength.
2.
Only when mounted to a Backplane.
3.
Depth is 153 mm for C200H-PA209R. For more details, see Mounting Dimensions within the Basic System Configuration section.
6<
CPU Overview
Connection with Peripheral Devices
3
Personal Computer (with CX-Programmer Software)
Peripheral Port Connection
Peripheral port
RS-232C,
9-pin
Peripheral Port
Connecting Cable
Peripheral Port Connecting Cables
Length
0.1 m
2.0 m
6.0 m
Computer connector
D-sub, 9-pin
D-sub, 9-pin
D-sub, 9-pin
Cable
CS1W-CN118
CS1W-CN226
CS1W-CN626
RS-232C Port Connection
RS-232C Port Connecting Cables
Length
2.0 m
Computer connector
D-sub, 9-pin
Cable
C200HS-CN220-EU
RS-232C cable
RS-232C,
9-pin
RS-232C ports
3
Programming Consoles
CQM1-PRO01-E C200H-PRO27-E
CS1W-KS001-E
Key Sheet
CQM1-PRO01-E
Programming Console
Cable provided with
CQM1-PRO01-E.
Peripheral port
CS1W-KS001-E
Key Sheet
C200H-PRO27-E
Programming Console
CS1W-CN224: 2.0 m
CS1W-CN624: 6.0 m
Peripheral port
Model
CQM1-PRO01-E
CS1W-CN114
Adapter Cable
Cable length
0.05 m
Cable
CS1W-CN114
Model
C200H-PR027-E
Cable length
2.0 m
6.0 m
Cable
CS1W-CN224
CS1W-CN624
73
B A S I C S Y S T E M C O N F I G U R A T I O N
CPU Rack and Expansion Rack
Configurations . . . . . . . . . . . . . . . . . . . . . . 42
CPU Racks and Products . . . . . . . . . . . . . . . . 43
Expansion Rack Products . . . . . . . . . . . . . . . 44
Expansion Rack Configuration Options . . . . . . 45
Mounting Dimensions . . . . . . . . . . . . . . . . . . 46
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
Basic System Configuration
CPU Rack and Expansion Rack Configurations
CPU
Rack
CPU Rack
3
CPU Rack
A CPU Rack consists of a CPU, Power Supply, CPU
Rack (Basic I/O Modules, Special I/O Modules, and
CPU Bus Modules). The Serial Communications Board and
Memory Cards are optional.
Power
Supply
Module
Basic I/O Modules
Special I/O Modules
CS1 CPU Bus Modules
Memory Card
Serial
Communications
Board
I/O
Connecting
Cable I/O Rack
Expansion
Rack
Basic I/O Modules
Special I/O Modules
CS1 CPU Bus Modules
3
Expansion Racks
Both C200HW and CS1 Expansion Racks can be used.
•
C200HW Expansion I/O Racks can be connected to CS1
CPU Racks, CS1 Expansion Racks, or to other C200HW
Expansion I/O Racks.
•
CS1 Expansion Racks can be connected to CPU Racks or to other CS1 Expansion Racks.
An Expansion Rack consists of a Power Supply, a CS1 or C200HW Expansion I/O Rack (Basic I/O Modules,
Special I/O Modules, and CS1 CPU Bus Modules).
Note: Refer to the Ordering Guide Section for rack and module capability.
Power
Supply
Module
Additional Information: To simplify specification of your CS1 System, refer to the worksheets provided in the Reference Section of this catalog.
75
Basic System Configuration
CPU Racks and Products
3
CPU Rack
Name
CPU Rack
Configuration
CPU Rack
CPU
Power Supply
Memory Card
Serial Communications Board
Remarks f ll i t bl f d l b
3
Products Used with CPU Racks
Name
CPUs
CPU Rack
Boards ti C bl
C bl (f i h l )
Specifications
I/O bits: 960, Program capacity: 10K steps
Data Memory: 32K words (DM: 32K words, EM: None)
Model
CS1G-CPU42-E(V
P
I/O bits: 960, Program capacity: 20K steps
Data Memory: 32K words (DM: 32K words, EM: None)
I/O bits: 1,280, Program capacity: 30K steps
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 banks)
I/O bits: 5,120, Program capacity: 60K steps
Data Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CS1G-CPU43-E(V
CS1G-CPU44-E(V
CS1G-CPU45-E(V
P
P
P
I/O bits: 5,120, Program capacity: 20K steps
Data Memory: 32K words (DM: 32K words, EM: None)
I/O bits: 5120, Program capacity: 30K steps
Data Memory: 64K words (DM: 32K words, EM: 32K words x 1 bank)
I/O bits: 5120, Program capacity: 60K steps
Data Memory: 128K words (DM: 32K words, EM: 32K words x 3 banks)
CS1H-CPU63-E(V
CS1H-CPU64-E(V
CS1H-CPU65-E(V
P
P
P
I/O bits: 5120, Program capacity: 120K steps
Data Memory: 256K words (DM: 32K words, EM: 32K words x 7 banks)
I/O bits: 5120, Program capacity: 250K steps
Data Memory: 448K words (DM: 32K words, EM: 32K words x 13 banks)
2 slots (Connection is not possible to Expansion Rack)
3 slots
5 slots
8 slots
10 slots
100 to 120 VAC or 200 to 240 VAC, Output capacity: 4.6 A, 5 VDC
100 to 120 VAC or 200 to 240 VAC (0.8 A 24 VDC service power )
Output capacity: 4.6 A, 5 VDC
100 to 120 VAC or 200 to 240 VAC (with RUN output) Output capacity: 4.6 A, 5
VDC
CS1H-CPU66-E(V
CS1H-CPU67-E(V
CS1W-BC023
CS1W-BC033
CS1W-BC053
CS1W-BC083
CS1W-BC103
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
P
P
24 VDC, Output capacity: 4.6 A, 5 VDC C200HW-PD024
100 to 120 VAC or 200 to 240 VAC (with RUN output) Output capacity: 9 A, 5 VDC C200HW-PA209R
Flash memory, 8 MB
Flash memory, 15 MB
Flash memory, 30 MB
Memory Card adapter
2 x RS-232C ports (protocol macro function supported)
1 x RS-232C port + 1 x RS-422/485 port (protocol macro function supported)
HMC-EF861
HMC-EF171
HMC-EF371
HMC-AP001
CS1W-SCB21
CS1W-SCB41
CQM1-PRO01-E
Connects the CQM1-PRO01-E Programming Console. (Length: 0.05 m)
Connects the C200H-PRO27-E Programming Console. (Length: 2.0 m)
Connects the C200H-PRO27-E Programming Console. (Length: 6.0 m)
Connects computer, D-Sub 9-pin receptacle (Length: 0.1 m)
Connects computer, D-Sub 9-pin (Length: 2.0 m)
Connects computer, D-Sub 9-pin (Length: 6.0 m)
Connects computer, D-Sub 9-pin (Length: 2.0 m)
C200H-PRO27-E
CS1W-CN114
CS1W-CN224
CS1W-CN624
CS1W-CN118
CS1W-CN226
CS1W-CN626
C200HS-CN220-EU
)
)
)
)
)
)
)
)
)
Peripheral Device Connecting
Cables (for RS-232C port)
Battery Set For CS1 Series only.
CS1W-BAT01
76
Basic System Configuration
Expansion Rack Products
3
Expansion Rack Options
Rack
CS1 Expansion Rack
C200HW Expansion
I/O Rack
Configuration
CS1 Expansion I/O Rack
Power Supply
C200HW Expansion I/O Backplane
Power Supply
Remarks
One of each item is required.
connected after a C200HW
Expansion I/O Rack.
3
Products Used in Expansion Racks
Name Specifications
CS1 Expansion I/O Racks 3 slots
5 slots
8 slots
C200HW Expansion I/O
R k
10 slots
3 slots
5 slots
Power Supply
8 slots
10 slots
100 to 120 VAC or 200 to 240 VAC
Output capacity: 4.6 A, 5 VDC
100 to 120 VAC or 200 to 240 VAC
(with power output terminal: 0.8 A, 24 VDC)
CS1 to CS1 Expansion
I/O R k C ti
Output capacity: 4.6 A, 5 VDC
100 to 120 VAC or 200 to 240 VAC (with RUN output)
Output capacity: 4.6 A, 5 VDC
24 VDC
100 to 120 VAC or 200 to 240 VAC (with RUN output)
Output capacity: 9 A, 5 VDC
Connects CS1 Expansion I/O Racks to CPU Racks or th CS1 E i I/O R k
CS1 to C200HW i I/O R k
C200HW to C200HW i I/O R k
Connects C200HW Expansion I/O Racks to CPU Racks i I/O R k
Connects C200HW Expansion I/O Racks to other i I/O R k
0.3 m
0.7 m
2 m
3 m
5 m
10 m
12 m
0.3 m
0.7 m
2 m
3 m
5 m
10 m
12 m
0.3 m
0.7 m
2 m
5 m
10 m
Cable Length Model
NA CS1W-BI033
CS1W-BI053
CS1W-BI083
CS1W-BI103
C200HW-BI031
C200HW-BI051
C200HW-BI081
C200HW-BI101
C200HW-PA204
C200HW-PA204S
C200HW-PA204R
C200HW-PD024
C200HW-PA209R
CS1W-CN313
CS1W-CN713
CS1W-CN223
CS1W-CN323
CS1W-CN523
CS1W-CN133
CS1W-CN133-B2
CS1W-CN311
CS1W-CN711
CS1W-CN221
CS1W-CN321
CS1W-CN521
CS1W-CN131
CS1W-CN131-B2
C200H-CN311
C200H-CN711
C200H-CN221
C200H-CN521
C200H-CN131
77
Basic System Configuration
Expansion Rack Configuration Options
3
Expansion Rack Patterns
The following diagrams show the three possible patterns of Expansion Racks.
Note: Total cable length must be 12 m or less.
1. CPU Rack with CS1 Expansion Racks
CPU Rack
2. CPU Rack with C200HW Expansion I/O Racks
CPU Rack
CS1 I/O
Connecting
Cable
CS1 to
C200H I/O
Connecting
Cable
CS1 Expansion Rack
C200HW
Expansion I/O Rack
CS1 I/O
Connecting
Cable
CS1 Expansion Rack
7 Racks max.
C200H I/O
Connecting
Cable
C200H I/O
Connecting
Cable
CS1 Expansion Rack
C200HW
Expansion I/O Rack
C200HW
Expansion I/O Rack
CS1 I/O
Connecting
Cable
3. CPU Rack with CS1 Expansion Racks and C200HW Expansion I/O Racks
CPU Rack
CS1 I/O
Connecting
Cable CS1 Expansion Rack
3 Racks max.
CS1 to C200H
I/O Connecting
Cable
C200H I/O
Connecting
Cable
C200H I/O
Connecting
Cable
C200HW Expansion I/O Rack 7 Racks max.
(3 C200HW Expansion I/O Racks max.)
C200HW Expansion I/O Rack
78
Basic System Configuration
Mounting Dimensions
3
Dimensions
Unit: mm (inch)
H
B
Note: The depth dimension “D” (indicated for all racks) represents the full depth of the mounted rack. The total system depth can range from a
118 mm, min.(4.65 in) to 223 mm, max. (8.78 in), depending on the
CPU, Power Supply, Modules, and Connectors used. Refer to the following page. For more details, see Section 3 in Manual W339.
A
W
D
(See Note.)
Unit: mm (inch)
Model
CS1W-BC023
CS1W-BC033
CS1W-BC053
CS1W-BC083
CS1W-BC103
H
157 (6.18)
130 (5.12)
130 (5.12)
130 (5.12)
130 (5.12)
W
198.5 (7.81)
260 (10.24)
330 (12.99)
435 (17.13)
505 (19.88)
D
22.2 (0.87)
22.2 (0.87)
22.2 (0.87)
22.2 (0.87)
22.2 (0.87)
B
145 (5.71)
118 (4.65)
118 (4.65)
118 (4.65)
118 (4.65)
A
172.3 (6.79)
246 (9.69)
316 (12.44)
421 (16.57)
491 (19.33)
Model
CS1W-BI033
CS1W-BI053
CS1W-BI083
CS1W-BI0103
Model
C200HW-BI031
C200HW-BI051
C200HW-BI081
C200HW-BI101
H
130 (5.12)
130 (5.12)
130 (5.12)
130 (5.12)
H
130 (5.12)
130 (5.12)
130 (5.12)
130 (5.12)
W
260 (10.24)
330 (12.99)
435 (17.13)
505 (19.88)
W
189 (7.44)
259 (10.20)
364 (14.33)
434 (17.09)
D
22.2 (0.87)
22.2 (0.87)
22.2 (0.87)
22.2 (0.87)
D
17 (0.67)
17 (0.67)
17 (0.67)
17 (0.67)
B
118 (4.65)
118 (4.65)
118 (4.65)
118 (4.65)
A
246 (9.69)
316 (12.44)
421 (16.57)
491 (19.33)
Additional Information: For more details and further specifications, refer to Manual W339, Section 3.
79
Basic System Configuration
Mounting Dimensions
3
Mounting Height and Bending Radius
Unit: mm (inch)
The height of all systems is from 118 (4.65) to 153 (6.02) depending on the modules that are mounted. Additional height is required to connect Peripheral
Devices and Cables. Be sure to allow sufficient mounting height.
118 (4.65) to
153 (6.02)
180 (7.09) to
223 (8.78)
Note: I/O Connecting Cables are 12 m (39.37 ft) l ong max. and require sufficient space to maintain the min. bending radius.
CS1 I/O Connecting Cable
Cable diameter: 8.6 (0.34)
R
;
69 (2.72)
C200HW I/O Connecting Cable
Cable diameter: 5.1 (0.20)
CS1 to C200HW I/O Connecting Cable
Cable diameter: 5.1 (0.20)
R
;
41 (1.61)
R
;
41 (1.61)
Additional Information: More details on Basic System Configuration, Expansion Rack Patterns and Mounting Dimensions can be found in Manual W339.
7:
7;
I / O T Y P E S A N D A L L O C A T I O N S
I/O Types . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Basic I/O Modules
Special I/O Modules
CS1 CPU Bus Modules
I/O Allocations . . . . . . . . . . . . . . . . . . . . . . . . 52
Basic I/O Modules
CS1 Special I/O Modules
CS1 CPU Bus Modules
SYSMAC BUS Racks
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
83
I/O Types and Allocations
I/O Types
In CS1 Series Controllers, part of the I/O memory is allocated to each module. Modules are divided into the following three groups for allocations.
•
Basic I/O Modules
•
Special I/O Modules
•
CS1 CPU Bus Modules
Basic I/O Modules
CS1 Basic I/O Modules C200H Basic I/O Modules
(See Note 2.)
C200H Group-2
High-density I/O Modules
(See Note 2.)
Allocations
Basic I/O Module Area:
CIO 0000 to CIO 0319 (See Note 1.)
(Memory is allocated in word units based on mounting position in the racks.)
Note: 1. The rack’s first word setting can be changed from the default setting (CIO 0000) to any word from CIO 0000 to CIO 9999.
2. The unit number setting on the front of C200H Group-2 High-density I/O Modules is ignored. Words are allocated to these modules based on their location in the rack.
3
Special I/O Modules
Allocations
Special I/O Module Area:
CIO 2000 to CIO 2959
(Each module is allocated ten words based on its unit number.)
Note: 1. Although there are 96 unit number settings, a maximum of 80 modules can actually be mounted to a PLC System because the maximum number of slots possible is 80.
2. Some modules (namely C200H High-Density I/O
Modules) are actually treated as Special I/O Modules.
CS1 Special I/O Modules
(See Note 1.)
C200H Special I/O Modules
(See Note 2.)
3
CS1 CPU Bus Modules
Allocations
CS1 CPU Bus Module Area:
CIO 1500 to CIO 1899
(Each Module is allocated 25 words based on its unit number.)
CS1 CPU Bus Modules
Additional Information: Refer to Manual W339 for more detail on I/O types and allocations.
84
I/O Types and Allocations
I/O Allocations
3
Basic I/O Modules
Allocation Methods
Basic I/O Modules include CS1 Basic I/O Modules, C200H Basic I/O Modules, and C200H Group-2 High-density I/O Modules.
Allocated words in the CIO Area: CIO 0000 to CIO 0319
Basic I/O Modules can be mounted to the CPU Rack, CS1 Expansion Racks, and C200HW Expansion I/O Racks.
Note: CS1 Basic I/O Modules cannot be mounted to C200HW Expansion I/O Racks.
1. CPU Rack
Basic I/O Modules on the CPU Rack are allocated words of memory from left to right (as the modules are mounted); modules are allocated as many words as required in word units (i.e., 8-pt. and 16-pt. modules = 1 word, 32-pt. modules = 2 words, etc.).
CIO
0000
CPU Rack
Example
IN
8
CIO
0000
IN
16
CIO
0001
IN
64
CIO
0002 to
0005
OUT
8
CIO
0006
OUT
32
CIO
0007 to
0008
CPU Rack
2. Allocations to CS1 Expansion and C200HW Expansion I/O Racks
I/O allocations to Basic I/O Modules continues from the CPU Rack to the Expansion Racks. Words are allocated from left to right and each module is allocated as many words as it requires, just like modules in the CPU Rack.
CIO
0000
CPU Rack
Words allocated in order from Rack nearest CPU
Rack.
CS1 Expansion Rack
CS1 Expansion Rack
Additional Information: Refer to Manual W339 for more detail on I/O types and allocations.
85
I/O Types and Allocations
I/O Allocations
3
Special I/O Modules
Allocation Methods
Special I/O Modules include CS1 Special I/O Modules and C200H Special I/O Modules.
Each of these modules is allocated ten words in the Special I/O Area (CIO 2000 to CIO 2959), based upon the unit number setting of the module.
Special I/O Modules can be mounted to the CPU Rack, CS1 Expansion Racks, and C200HW Expansion I/O Racks (See Note).
Note: CS1 Special I/O Modules cannot be mounted to C200HW Expansion I/O Racks.
Each Module is allocated 10 words in the Special I/O Module Area, as shown in the following table.
1
2
Unit number
0
Words allocated
CIO 2000 to CIO 2009
CIO 2010 to CIO 2019
CIO 2020 to CIO 2029
15 CIO 2150 to CIO 2159
95 CIO 2950 to CIO 2959
•
Special I/O Modules are ignored during I/O allocation to Basic I/O Modules. Slots containing Special I/O Modules are treated as empty slots.
•
Although unit number settings of 0-95 are available on CS1 Special I/O Modules, a total of only 80 Special I/O Modules is possible.
3
CS1 CPU Bus Modules
Allocation Methods
CS1 CPU Bus Modules include CS1 Communications and Network Modules.
Each CS1 CPU Bus Module is allocated 25 words in the CS1 CPU Bus Module Area (CIO 1500 to CIO 1899).
CS1 CPU Bus Modules can be mounted to the CPU Rack or CS1 Expansion Racks.
Each Module is allocated 25 words in the CPU Bus Area, as shown in the following table.
1
2
Unit number
0
Words allocated
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
15 CIO 1875 to CIO 1899
•
CS1 CPU Bus Modules are ignored during I/O allocation to Basic I/O Modules. Slots containing CS1 CPU Bus Modules are treated as empty slots.
Additional Information: Refer to Manual W339 for more detail on I/O types and allocations.
86
I/O Types and Allocations
I/O Allocations
3
SYSMAC BUS Racks
Allocation Methods
Each SYSMAC BUS Remote I/O Slave Rack is allocated 10 words in the SYSMAC BUS Area (CIO 3000 to CIO 3049) according to the unit number (0 to 4) set on the slave module. No words in the I/O Area are allocated to modules on slave racks.
Each slot in the slave rack is allocated one of the rack’s 10 words. The words are allocated from left to right. One word is allocated to every slot even if the slot is empty and the last two words allocated to each rack are not used because the slave racks have only 8 slots.
The master module and slave module themselves do not require any words.
SYSMAC BUS Remote I/O
Master Module
SYSMAC BUS Remote I/O
1 2 3 4 5 6 7 8
Remote I/O Slave Rack
1718 19 20 21 22 23 24
Slave Module with unit number 0
9 10 11 12 13 14 15 16
Slave Module with unit number 2
Slave Module with unit number 1
:
1
2
:
3
8
Not used.
Not used.
9
:
10
:
16
Not used.
Not used.
17
18
: :
24
Not used.
Not used.
•
•
•
•
•
(continued)
Slave Module with unit number 0
Slave Module with unit number 1
Slave Module with unit number 2
Additional Information: More detail on I/O types and allocations can be found in Manual W339. More information on remote I/O networks can be found in two
Manuals: W136 and W120.
87
M O D U L E S
I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . 58
B7A I/O Modules . . . . . . . . . . . . . . . . . . . . . . 58
Interrupt Input Module . . . . . . . . . . . . . . . . . 61
Analog Timer Module . . . . . . . . . . . . . . . . . . 62
Analog I/O Modules . . . . . . . . . . . . . . . . . . . . 63
Temperature Sensor Input Modules . . . . . . . . 66
Temperature Control Modules . . . . . . . . . . . . 67
Heat/Cool Control Modules . . . . . . . . . . . . . . 68
Process Control Modules . . . . . . . . . . . . . . . . 69
Fuzzy Logic Module . . . . . . . . . . . . . . . . . . . . 71
Cam Positioner Module . . . . . . . . . . . . . . . . . 72
Position Control Modules . . . . . . . . . . . . . . . 73
Motion Control Modules . . . . . . . . . . . . . . . . 74
High-speed Counter Modules . . . . . . . . . . . . . 76
Radio Frequency ID Sensor Modules . . . . . . . 77
Serial Communications Boards/Module . . . . . 78
ASCII/BASIC Modules . . . . . . . . . . . . . . . . . . 79
Voice Module . . . . . . . . . . . . . . . . . . . . . . . . 82
Ethernet Module . . . . . . . . . . . . . . . . . . . . . . 84
Controller Link Boards and Modules . . . . . . . 85
DeviceNet (CompoBus/D) Modules and DeviceNet Products . . . . . . . . . . . . . . . . 86
Profibus-DP Master . . . . . . . . . . . . . . . . . . . . 91
CompoBus/S Master Module and CompoBus/S Products . . . . . . . . . . . . . . 92
SYSMAC Bus Remote I/O Modules . . . . . . . . 97
I/O Wiring Accessories . . . . . . . . . . . . . . . . . 98
C200H and CS1 I/O Module Connectors
XW2Z Cables with XW2B Screw Terminal Blocks
Relay Input Blocks and Bases
Relay Output Blocks and Bases
B7A Input/Output Module Accessories
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
89
ITEM
Interrupt Input Module
Analog Timer Module
Temperature Sensor Input Modules
Temperature Control Modules
Heat/Cool Control Modules
Process Control Modules
Fuzzy Logic Module
Cam Positioner Module
Position Control Modules
High-speed Counter Modules
Radio Frequency ID Sensor Modules
ASCII/BASIC Modules
Voice Module
Ethernet Module
T i l
Profibus-DP Module
SYSMAC Bus Remote I/O Modules
I/O Wiring Accessories
Modules
B7A Input Module (16 inputs)
B7A Input Module (32 inputs)
B7A Output Module (16 outputs)
B7A Output Module (32 outputs)
B7A Mixed I/O Module
(16 inputs,16 outputs)
B7A Mixed I/O Module
(32 inputs, 32 outputs)
Serial Communications Boards
Serial Communications Module
Controller Link Modules
DeviceNet Master Modules
DeviceNet I/O Link Modules
DeviceNet Slaves
Multiple I/O Terminals
Profibus-DP Master
CompoBus/S Master Modules
CompoBus/S Slave Terminals
Remote I/O Master Modules
Various Wiring Accessories
CLASSIFICATION/GROUP
C200H Group-2 High Density
C200H Special I/O
CS1 Basic I/O
C200H Group-2 High Density
CS1 Basic I/O
C200H Special I/O
CS1 Basic I/O
MODEL
C200H-ID211/212
C200H-IA PPP
C200H-IM211/212
C200H-ID111/216/217
C200H-ID215/501
CS1W-ID291
C200H-OC22
P
(
P
)
C200H-OD PPP
C200H-OA2 PP ( P )
C200H-OD218/219
C200H-OD215
C200H-OD501
CS1W-OD291/292
C200H-MD115/215/501
C200H-MD291/292
C200H-B7AI1
C200H-B7A12
C200H-B7AO1
C200H-B7A02
C200H-B7A21
C200H-B7A22
PAGE
60
C200H Basic I/O
C200H Basic I/O
C200H Special I/O
CS1 Special I/O
C200H Special I/O
CS1 Special I/O
C200H Special I/O
CS1 Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
C200H Special I/O
CS1 Special I/O
C200H Special I/O
C200H Special I/O
C200HS-INT01
C200H-TM001
C200H-AD00 P
CS1W-AD00
P
C200H-DA00
P
CS1W-DA00 P
C200H-MAD01
CS1W-MAD44
C200H-TS PPP
C200H-TC
PPP
C200H-TV PPP
C200H-PID
PPP
C200H-FZ001
C200H-CP114
C200HW-NC
PP
3
C200H-MC221
CS1W-MC
P
21
C200H-CT PPP (-V1)
C200H-IDS
PPP
(-V1)
CS1W-SCB21/41
CS1W-SCU21
Inner Board
CS1 CPU Bus
C200H Special I/O
C200H Special I/O
CS1 CPU Bus
C200H-ASC02/11/21/31
C200H-OV001
CS1W-ETN01
CS1 CPU Bus CS1W-CLK11/21
Personal Computer Interface Board 3F8F5-CLK11/21
C200H Special I/O
3F8F6-CLK21
C200HW-DRM21-V1
C200H Special I/O
DeviceNet Slave
Multiple I/O
C200H Special I/O
C200H Special I/O
CompoBus/S Slave
SYSMAC Bus Remote I/O
C200HW-DRT21
DRT1 Series
GT1 Series
C200HW-PRM21
C200H-SRM21-V1
SRT1 Series (SRT2)
C200H-RM
PPP
61
62
79
82
84
87
88
91
92
93
97
98
69
71
72
66
67
68
73
74
75
76
77
8:
Modules
Input Modules
Basic and Special I/O
Input Modules
C200H-I P P P
8-pt Modules
P
Output Modules
C200H-O
P P P P
5-/8-pt Modules
P
Input Modules
C200H-I P P P
16-pt Modules
P
Output Modules
C200H-O P P P
16-pt Modules
P
Input Modules
C200H-ID
P P P
32-/64-pt Modules
Output Modules
C200H-OD P P P
32-/64-pt Modules
Input Modules
C200H-ID P P P
32-pt Modules
Output Modules
C200H-OD
P P
32-pt Modules
P
Mixed I/O Modules
C200H-MD P P P
16-/16-pt Modules
Input Modules
CS1W-ID291
96-pt Modules
Output Modules
CS1W-OD29 P
96-pt Modules
Mixed I/O Modules
CS1W-MD29
P
48-/48-pt Modules
3
DC Input Modules
Classification
C200H Basic I/O
C200H Group-2 I/O
(B i I/O A )
CS1 Basic I/O
C200H Special I/O Module
Input voltage
12 to 24 VDC
24 VDC
24 VDC
24 VDC
12 to 24 VDC
24 VDC
24 VDC
24 VDC
Inputs Connections
8 pts
16 pts
Removable terminal block
32 pts Connector (See Note.) )
64 pts
64 pts
32 pts
96 pts Connector (See Note.) )
32 pts
Remarks Model
Input current: 10 mA C200H-ID211
Input current: 7 mA C200H-ID212
—
—
—
Input current: 6 mA
-
High-speed inputs
C200H-ID216
C200H-ID217
C200H-ID111
C200H-ID218
CS1W-ID291
C200H-ID215
3
TTL Input Modules
Classification
C200H Special I/O
Input voltage
5 VDC
Inputs Connections
32 pts Connector (See Note.)
Remarks
High-speed inputs
3
AC Input Modules
Classification
C200H Basic I/O
Input voltage/Current
100 to 120 VAC, 10 mA
100 to 120 VAC, 10 mA
200 to 240 VAC, 10 mA
200 to 240 VAC, 10 mA
Inputs Connections
8 pts Removable terminal block
16 pts
8 pts
16 pts
3
AC/DC Input Modules
Classification
C200H Basic I/O
Input voltage/Current Inputs Connections
12 to 24 VAC/VDC, 10 mA 8 pts Removable terminal block
24 VAC/VDC, 7 mA 16 pts
3
B7A Input Modules
Classification
C200H Basic I/O
C200H Basic I/O (Group-2 High-density)
Input voltage
—
—
Note: Refer to the I/O Wiring Accessories Section.
Inputs Connections
16 pts 3-wired, 500 m max distance
32 pts
Model
C200H-ID501
Model
C200H-IA121
C200H-IA122
C200H-IA221
C200H-IA222
Model
C200H-IM211
C200H-IM212
Model
C200H-B7AI1
C200H-B7A12
Additional Information: For more details and specifications on any of these modules, refer to manual W339, Appendix A.
8;
Basic and Special I/O
Modules
Output Modules
3
Relay Contact Output Modules
Classification
C200H Basic I/O Modules
Outputs Max. switching capacity
8 pts 2 A at 250 VAC
12 pts
16 pts
16 pts
5 pts
8 pts
3
Transistor Output Modules
Classification
C200H Basic I/O Modules
C200H Group-2 I/O Modules
C200H Special I/O Module
CS1 Basic I/O Modules
Outputs Output Voltage/Max. switching capacity
8 pts
8 pts
12 to 48 VDC, 1 A sinking
24 VDC, 2.1 A, sinking
8 pts
8 pts
12 pts
12 pts
16 pts
24 VDC, 0.8 A, sourcing, load short protection
5 to 24 VDC, 0.3 A, sourcing
24 VDC, 2.1 A, sinking
5 to 24 VDC, 0.3 A, sourcing
24 VDC, 0.3 A, sinking
24 VDC, 1.0 A, sourcing, load short protection 16 pts
32 pts
64 pts
32 pts
32 pts
24 VDC, 1.0 A, sinking
16 mA at 4.5 V to 100 mA at 26.4 V, sinking
Note: 128 pt dynamic outputs are possible.
96 pts 12 to 24 VDC, 0.1 A sinking
12 to 24 VDC, 0.1 A sourcing
3
TTL Output Modules
Classification
C200H Special I/O Module
Outputs Output voltage/Max. switching capacity
32 pts 5 VDC, 35 mA
Connections
Removable terminal block
Connections
Removable t i l bl k
Connector
(S N t )
Connector
Connector
(See Note.)
Connector
(S N t )
Connections Remarks
Connector
(See Note.)
128-pt dynamic outputs possible
Model
C200H-OC221
C200H-OC222
C200H-OC225
C200H-OC226
C200H-OC223
C200H-OC224
Model
C200H-OD411
C200H-OD213
C200H-OD214
C200H-OD216
C200H-OD211
C200H-OD217
C200H-OD212
C200H-OD21A
C200H-OD218
C200H-OD219
C200H-OD21B
C200H-OD215
CS1W-OD291
CS1W-OD292
Model
C200H-OD501
3
Triac Output Modules
Classification
C200H Basic I/O Modules
Outputs
8 pts
8 pts
12 pts
8 pts
12 pts
3
B7A Output Modules
Classification
C200H Basic I/O
C200H Basic I/O
(Group-2 High--density)
Outputs
16 pts
32 pts
Note: Refer to the I/O Wiring Accessories Section.
Output voltage/Max. switching capacity
250 VAC, 1.0 A, 50/60 HZ
120 VAC, 1.2 A, 50/60 HZ
250 VAC, 0.3 A, 50/60 HZ
250 VAC, 1.2 A, 50/60 HZ
250 VAC, 0.5 A, 50/60 HZ
Output voltage Connections
(See Note.) 3-wire, 500 m max. distance
(See Note.) Connector (See Note.)
Connections
Removable terminal bl k
Model
C200H-OA221
C200H-OA122E
C200H-OA222
C200H-OA223
C200H-OA224
Model
C200H-B7AO1
C200H-B7A02
Additional Information: For more details and specifications on any of these modules, refer to manual W339, Appendix A.
8<
Modules
Mixed I/O Modules
Basic and Special I/O
3
B7A Mixed I/O Modules
Classification
Note: Refer to I/O Wiring Accessories Section provided at the end of the complete Module Section.
3
Mixed I/O Modules
TTL I/O Module
DC Input/Transistor
Output Modules
Voltage
( (See Note.) )
Classification Inputs/
Outputs
C200H
Special I/O
16 inputs/
16 outputs
16 inputs/
16 outputs voltage
5 VDC
Inputs/Outputs Connections
16 inputs/16 outputs Connector (See Note.)
32 inputs/32 outputs Connector (See Note.) capacity
5 VDC, 35 mA Connector
( (See Note.) )
High-speed outputs i possible
CS1 Basic
I/O Modules
16 inputs/
16 outputs
48 inputs/
48 outputs
48 inputs/
48 outputs
24 VDC 16 mA at 4.5 V to
100 mA at
26.4 VDC, sinking
12 VDC 24 VDC, 50 mA, sinking
24 VDC 12 to 24 VDC,
0.1 A, sinking
12 to 24 VDC,
0.1 A, sourcing
---
---
Model
C200H-B7A21
C200H-B7A22
C200H-MD501
C200H-MD215
C200H-MD115
CS1W-MD291
CS1W-MD292
Note: In addition to the normal I/O functions, C200H High-density I/O Modules (Special I/O Modules) provide the following functions.
•
Dynamic I/O (except for OD501/OD502): Instead of normal static inputs and normal static outputs, dynamic outputs and dynamic inputs are used to increase I/O capacity to 128 inputs and 128 outputs through the use of strobe signal outputs. These functions can be used to reduce wiring to devices with more digits, such as displays and keyboards.
•
High-speed Inputs (except OD501/OD215): Eight of the inputs can be set as high-speed inputs to accurately input short pulses from devices like photomicroswitches.
Additional Information: For more details and specifications on any of these modules, refer to manual W339.
93
3
System Configuration
CPU
Basic I/O
Modules
Interrupt Input Module
Execute an Interrupt Task Within 1.2 ms After an Input Signal Is Received
I/O interrupt task
C200HS-INT01
When an input on the Interrupt Input Module turns ON, the
CPU is notified immediately, cyclic task execution is interrupted, and an I/O interrupt task is executed.
3
Specifications
Classifications Input voltage Inputs
C200H Basic I/O Module 12 to 24 VDC 8 pts
Input response time
ON: 0.2 ms min.
OFF: 0.52 ms min.
Connections
Removable terminal block
Allocations
(CIO 0319 to CIO 2000)
16 bits
Part number
C200HS-INT01
Note: 1. Interrupt response time = Input ON time of 0.2 ms + software interrupt response time of 1 ms max.
2. A CSI Series PLC System can support a maximum of four Interrupt Input Modules.
Additional Information: For more details and specifications on any of these modules, refer to manual W339.
94
Modules
Analog Timer Module
Easy On-site Time Adjustments
Basic I/O
3
System Configuration
Analog Timer Module
Timer set input
Timer pause input
T0
Set value
Resistance
T3
Set value
Resistance C200H-TM001
Provides four timers that can be easily adjusted on-site using front-panel adjustments such as external variable resistors:
No Programming Device required. Using timer pause inputs enables the functionality of an accumulative timer.
3
Specifications
Classification Timers Setting range
C200H Basic
I/O Module
4 pts 0.1 to 1.0 s, 1 to 10 s,
2 to 60 s, 1 to 10 min
Time setting method
Internal or external variable resistor
CPU bits
Timer set input, timer pause input, and time up output
Allocations
(CIO 0319 to
CIO 2000)
16 bits
Model
C200H-TM001
Time up outputs
4 pts
Additional Information: For more details and specifications on any of these modules, refer to manual W339.
95
Modules
Analog Input Modules
Convert Analog Signals to Binary Data
Convert varying input signals such as 1 to 5 V or 4 to 20 mA to binary values between 0000 and 0FA0 Hex and store the results in the allocated memory each cycle. The ladder diagram can be used to transfer the data to the DM Area, or the
SCALING instructions (e.g., SCL(194)) can be used to scale the data to the desired range.
3
System Configuration
Analog I/O
Module
CPU Module
Temperature, Pressure,
Speed, Flow rate
Preamp
C200H-AD001/AD002 C200H-AD003
CS1W-AD041
CS1W-AD081
3
Features
•
Wire burnout detection.
•
Peak-value hold function.
•
Mean function.
•
Scaling function.
•
Switching calculation functions.
•
1 ms/channel response time.
•
Offset and gain adjustment.
Note: The functions provided depend upon the model being used.
Transducer
Voltage, Current,
Power factor
3
Specifications
Model
Classification
C200H-AD001 C200H-AD002 C200H-AD003 CS1W-AD041 CS1W-AD081
C200H Special I/O Modules CS1 Special I/O Modules
Inputs
Voltage 1 to 5 V
Voltage 0 to 10 V
Voltage 0 to 5 V
4 pts
Yes
Yes
---
8pts 8 pts 4 pts
Yes
Yes
Yes
8 pts
Signal range settings
Resolution
Conversion speed
Overall accuracy (at 25
°
C)
Voltage --10 to 10 V ---
Current 4 to 20 mA Yes
Individual
1/4000
Yes Yes Yes
Yes
Individual
1/4000
2.5 ms/pt max.
2.5 ms/pt max.
1.0 ms/pt max.
1.0 ms/pt max.
±
0.5% FS Voltage:
±
0.25% FS
Current:
±
0.4% FS
Voltage:
±
0.2% FS
Current:
±
0.4% FS
Voltage:
±
0.2% FS
Current:
±
0.4% FS
Terminal block Connector Terminal block Terminal block Connections
Features
Input disconnection detection
Wire burnout detection Yes
Peak-hold function
Mean function
Scaling function
Yes
Yes
Yes
---
Yes ---
Yes
Yes
Yes
Yes
Yes
Additional Information: For more details and specifications on any of these modules, refer to these manuals: W127 (C200H Analog I/O Modules); W229
(C200H-AD002 Modules); W325 (C200H Analog I/O Modules); W345 (CS1 Series Analog I/O Modules).
96
Modules
Analog Output Modules
Convert Binary Data to Analog Signals
Binary data between 0000 to 0FA0 Hex in allocated memory can be converted to analog signals for output, such as
1 to 5 V or 4 to 20 mA, for output. You only need to place the data in the allocated words within the ladder diagram.
3
System Configuration
Analog I/O
Module
CPU Module
C200H-DA001
C200H-DA002
C200H-DA003
C200H-DA004
CS1W-DA041
CS1W-DA08V
CS1W-DA08C
3
Features
•
Output limit.
•
Upper/Lower limit alarms.
•
Pulse outputs (with duty ratio).
•
Output hold function.
Note: The functions provided depend upon the model being used.
3
Specifications
Classification
Outputs range
Resolution
Current
Signal range settings
Connections
Features Output limit
Upper/Lower limit alarms
1 to 5 V
0 to 10 V
Yes
Yes
0 to 5 V —
--10 to 10 V —
C200H Special I/O Modules
2 pts 4 pts
—
—
—
Yes
4 to 20 mA Yes
Individual
1/4095 Voltage: 1/8190
Current: 1/4095
Conversion speed
Overall accuracy (at 25
°
C)
2.5 ms/pt max.
±
0.5% FS Voltage:
±
0.3% FS
Current:
±
0.5% FS
Terminal block
Yes
Yes
Pulse outputs
(with duty ratio)
Output hold function
Yes
—
Regulator
(Temperature control)
Servocontroller
Vari. speed controller
Chart recorder
(Position control)
(Speed control)
8 pts
Yes
Yes
—
Yes
—
8 pts
—
—
—
—
Yes
CS1 Special I/O Modules
4 pts 8 pts 8 pts
Yes
Yes
Yes
Yes
Yes
Individual
—
—
—
—
—
Yes
1/4000 1/4000
1.0 ms/pt max.
1.0 ms/pt max.
±
0.3% FS
±
0.5% FS Voltage:
±
0.3% FS
Current:
±
0.5% FS
—
—
Terminal Block
—
—
—
Yes
—
Yes
Additional Information: For more details and specifications on any of these modules, refer to these manuals: W325 (C200H Analog I/O Modules); W260
(C200H-DA002 Modules); W325 (C200H Analog I/O Modules); W345 (CS1 Series Analog I/O Modules).
97
Modules
Analog Mixed I/O Modules
Analog Inputs and Outputs within One Module
One module performs both analog input and analog output operations. The module can also be used for ratio and bias processing, which can be performed on analog inputs to output the results as analog outputs.
3
System Configuration
Analog I/O
Module
CPU Module
C200H-MAD01 CS1W-MAD44
Temperature, Pressure,
Speed, Flow rate
Preamp
Transducer
Regulator
(Temperature control)
Servocontroller
Vari. speed controller
Chart recorder
(Position control)
(Speed control)
3
Features
•
Mean function.
•
Peak hold function.
•
Wire burnout detection.
•
Output hold function.
•
Ratio conversions.
Voltage, Current,
Power factor
3
Specifications
Part number
Classification
Inputs
Outputs
Resolution
Conversion speed
Connections
Features
Current
Inputs
Outputs
1 to 5 V
0 to 5 V
0 to 10 V
--10 to 10 V
4 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
--10 to 10 V
4 to 20 mA
Mean function
Peak hold
Wire burnout detection
Output hold
Ratio conversion
---
Yes
Yes
Yes
C200H-MAD01
C200H Special I/O Module
2 pts
2 pts
Yes
Yes
---
Yes
Yes
Yes
1/4000 (inputs/outputs)
—
1/4000 (inputs/outputs)
1.0 ms/pt max (inputs/outputs) 1.0 ms/pt max (inputs/outputs)
Voltage:
±
0.2% FS; Current:
±
0.4% FS Voltage:
±
0.2% FS; Current:
±
0.4% FS
Voltage:
±
0.3% FS; Current:
±
0.5% FS Voltage:
±
0.3% FS; Current:
±
0.5% FS
Terminal block
Yes
Yes
Terminal block
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
CS1W-MAD44
CS1 Special I/O Module
4 pts
4 pts
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Additional Information: For more details and specifications on any of these modules, refer to these manuals: W345 (CS1 Series Analog I/O Modules), W127
(C200H Analog I/O Modules).
98
Modules
Temperature Sensor Input Modules
Process Signals From Up To Four Temperature Sensors
Process input signals from up to four thermocouples or platinum resistance thermometers into the specified ranges of
4-digit BCD. The temperatures are written to the allocated words every cycle, and can be transferred to the DM Area or other memory locations.
3
System Configuration
C200H-TS001
C200H-TS101
C200H-TS102
Temperature sensors
4 points
Thermocouple or
RTD inputs
3
Features
•
Process signals from up to four temperature sensors with one module. (The same type of temperature sensor and the same temperature ranges are used for all 4 inputs.)
•
Values from temperature sensors are placed in memory in the CPU in 4-digit BCD format.
•
Line disconnection detection provided.
3
Specifications
Model
Classification
Inputs
Thermocouples
Platinum resistance thermometers
Input signal range settings
Data stored in memory
Conversion speed
Overall accuracy (at 25
°
C)
Connections
Note: Temperature Sensor Terminals are available as DeviceNet
Slaves. These also support all of the listed Thermocouple types.
K
J
C200H-TS001 C200H-TS101 C200H-TS102
C200H Special I/O Modules
4 pts
Yes
Yes
JPt100 —
—
—
Yes
PT100 — —
One setting for all 4 points
—
—
—
Yes
4-digit BCD
4.8 s max. (when 4 pts are set for Module).
±
1% + 1
°
C
Terminal block
Additional Information: For more details and specifications on any of these modules, refer to manual W124.
99
Two independent single-loop PID temperature controllers in one module accept inputs from thermocouples or platinum resistance thermometers to control a transistor, voltage, or current output. Words allocated to the module in memory can be manipulated from the ladder diagram to start/stop operation, set the target value, read the process value, or to perform other operations.
3
System Configuration
Modules
Temperature Control Modules
One Module Functions as Two Temperature Controllers
Two temperature sensors
Output cable
Manipulated variable
Data Setting
Console
C200H-DSC01
Data Setting Console C200H-TC P P P
3
Features
•
Supports 2-loop PID control (two degrees of freedom) or ON/OFF control.
•
Utilize data from two temperature sensors
(thermocouples: R, S, K, J, T, E, B, N, L, or U) or platinum resistance thermometers (JPt00, Pt100).
•
Open-collector, voltage, or current outputs.
•
Sampling period: 500 ms.
•
Two internal alarms per loop.
•
Record up to eight sets of target values, alarm values, and PID parameters.
•
Connects to Data Setting Console for easy setup or monitoring.
3
Specifications
Classification
C200H Special I/O Module
Temperature sensor inputs
Thermocouples (R, S, K, J, T, E, B, N, L, or U) )
Control outputs Model
Transistor—Open-collector (pulse) C200H-TC001
Voltage (pulse) C200H-TC002
Current (linear) C200H-TC003
, ) Transistor—Open-collector (pulse) C200H-TC101
Voltage (pulse)
Current (linear)
C200H-TC102
C200H-TC103
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W225.
Data Setting Console
Specifications
Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc.
Model
C200H-DSC01
Additional Information: For more details and specifications on any of these modules, refer to manual W225.
9:
Modules
Heat/Cool Control Module
One Module Provides Two Loops of Specialized Temperature Control
For temperature control of critical processes, choose this module with both heating and cooling outputs. Two independent temperature controllers use inputs from thermocouples or platinum resistance thermometers to control heating and cooling through transistor, voltage, or current outputs. Words allocated to the module in memory can be manipulated from the ladder diagram to start or stop operation, enter the set point, read the process value, or perform other operations.
3
System Configuration
C200H-TV P P P C200H-DSC01
Data Setting Console
3
Features
•
Supports PID control and ON/OFF control.
•
Utilize data from two temperature sensors
(thermocouples: R, S, K, J, T, E, B, N, L, or U) or platinum resistance thermometers (JPt00, Pt100).
•
Open-collector, voltage, or current outputs.
•
Sampling period: 500 ms.
•
Detects heater burnout though current detectors for both loops.
•
Record up to eight sets of set points, alarm values, and PID parameters.
•
Connects to Data Setting Console.
Two temperature sensors Output cable
Data Setting
Console
Manipulate variable
MV Heat Cool
MV
Heat Cool
PV PV
3
Specifications
Classification Temperature sensor inputs
C200H Special I/O Module Thermocouples
(R S K J T E B N L U)
Platinum resistance t (JPt00 Pt100)
Heating control output Cooling control output
Open-collector (pulse) Transistor—
Voltage (pulse) ll t ( l )
Current (linear)
Open-collector (pulse)
Voltage (pulse)
Current (linear)
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W240.
Model
C200H-TV001
C200H-TV002
C200H-TV003
C200H-TV101
C200H-TV102
C200H-TV103
Data Setting Console
Specifications
Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc.
Model
C200H-DSC01
Additional Information: For more details and specifications on any of these modules, refer to manual W240.
9;
Modules
Process Control Modules
Ideal for Loop Control of Pressure, Flow, and Other Variables
Two independent, single-loop PID controllers use analog input signals, such as 4 to 20 mA or 1 to 5 V to control pressure flow and other process variables. Words allocated to the module in memory can be manipulated from the ladder diagram to start/stop operation, set the set point, read the process value, or perform other operations.
3
System Configuration
C200H-DSC01
Data Setting Console C200H-PID01
C200H-PID02
C200H-PID03
Two analog inputs
Output cable
Data Setting
Console
Manipulated variable
3
Features
•
Supports 2 independent loops of PID control or
ON/OFF control.
•
Accepts a variety of analog input signals.
•
Open-collector, voltage, or current outputs.
•
Sampling period: 100 ms.
•
Manual outputs supported.
•
Set two internal alarms for each loop.
•
Record up to eight sets of set points, alarm values, and
PID parameters.
•
Digital filters can be set to dampen rapid changes in inputs.
•
Connects to Data Setting Console for easy setup and monitoring.
3
Specifications
Classifications
C200H Special I/O Module
Analog signal input Control output
Open-collector (pulse)
Voltage (pulse)
Current (linear))
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W241.
Model
C200H-PID01
C200H-PID02
C200H-PID03
Data Setting Console
Specifications Model
Monitoring, setting, and changing present values, set points, alarm values, PID parameters, bank numbers, etc.
C200H-DSC01
Additional Information: For more details and specifications on any of these modules, refer to manual W241.
9<
Modules
Loop Control Options
Loop Control Options and Features
Method PID instruction in CPU
Number of loops 1 loop/instruction
Measurement input signal
None (from Analog Input
Module)
Measurement accuracy
Dependant on Analog
Input Module
Sampling period 10 ms to 99.99 s
(sampling period can vary with cycle time)
Control Continuous PID
Control output signals
Alarms
Auto/manual switching
RUN/STOP switching
Data setting banks
Temperature Control Module
2 loops/module
Heat/Cool Control Module
2 loops/module
Thermocouple or temperature resistance thermometer
Thermocouples: (Larger of
±
0.5% or
±
2
°
C)
±
1 digit max.
Temperature resistance thermometers: (Larger of
±
0.5% or
±
1
°
C)
±
1 digit max.
500 ms
Continuous PID (with auto-tuning), time-ratio PID
(with autotuning), ON/OFF
None (from Analog Output
Module)
None
Yes (By storing value in address of manipulated variable separate from instruction)
Yes (controlled by input conditions for PID instruction)
None
Transistor, voltage, current
Selected from 9 types
No
Yes
8 banks
Continuous PID (with autotuning), time-ratio PID (with autotuning), ON/OFF, heating output, cooling output
No
Yes
PID Control Module
2 loops/module
4 to 20 mA, 1 to 5 V,0 to
5 V or 0 to 10 V
±
0.5% FS
±
1 digit max.
100 ms
Continuous PID (with autotuning), time-ratio PID
(with autotuning),
ON/OFF
Transistor, voltage, current
Yes
Yes
:3
Modules
Fuzzy Logic Module
Take Advantage of High-speed Fuzzy Logic
Use the Fuzzy Support Software to create rule, membership functions, and other fuzzy data and transfer them to the module after checking the knowledge. The ladder program in the CPU can be used to set fuzzy inputs for processing by the
Fuzzy Logic Module, and then the results can then be read using the ladder program.
3
System Configuration
IBM PC/AT or compatible
Analog Output Module
Analog Input Module
C500-SU981-E
Fuzzy Support
Software
C200H-FZ001
3
Features
•
Contains a high-performance fuzzy logic processor for high-speed fuzzy processing.
•
Handles jobs that used to be performed by using the experience of skilled operators.
•
Eight inputs and four outputs.
•
Eight conditions and two conclusions per rule, 128 rules total.
Analog inputs
Analog outputs
CS1
RS-232C cable
(to 9-pin connector)
3
Specifications
Classification Fuzzy logic (See Note 2.)
C200H
Special I/O
Module
Rule form
8 conditions and
2 conclusions
Rules
128
Inputs
Data
8 words max.
FS range
0 to 4095
Outputs
Data FS range
4 words max.
0 to 4095 6 ms max. for
Module, 3 to
4 times the cycle time for system
Model
C200H-FZ001
Note: 1. Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W208.
2. Fuzzy Support Software, part number C500-SU981-E is required to configure the Fuzzy Logic Module and should be ordered separately.
Additional Information: For more details and specifications on any of these modules, refer to manual W208.
:4
Modules
Cam Positioner Module
One Module Functions as 48 Mechanical Cams
Angles are detected though an externally connected resolver
(angle detector), and cam outputs are produced for preset
ON/OFF angle data.
3
System Configuration
C200H-CP114
Cam Positioner Module
C200H-CP114
C200H-DSC01
Data Setting Console
CS1
Cam output
Control panel
C200H-DSC01
Data Setting
Console 3
Features
•
Supports 16 external outputs and 32 internal outputs for a total of 48 cam outputs.
•
Utilize up to 7 ON/OFF data for each cam.
•
The Data Setting Console allows easy monitoring of cam data settings and present cam angles.
Index table
Motor Resolver
3
Specifications
Classification No. of cam outputs
C200H Special I/O Module 48
(external outputs: 16; internal outputs: 32)
Control
Module
1
°
Resolver response speed
800 r/min max.
Resolver response time
200
µ s
(sampling frequency:
5 KHz)
Model
C200H-CP114
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W224.
Data Setting Console
Specifications
Monitoring and changing of cam data settings and present angles.
Model
C200H-DSC01
Additional Information: For more details and specifications on any of these modules, refer to manual W224.
:5
These Position Control Modules support open-loop control with pulse-train outputs. Automatic trapezoid or S-curve acceleration and deceleration profiles are supported. Models are available with 1, 2, or 4 axes. Use in combination with pulse input servo drive and servomotors or stepper motors that accept pulse-train inputs.
3
System Configuration
Modules
Position Control Modules
High-speed, High-precision Positioning with 1, 2, or 4 Axes
Inputs
Servo Terminal
Servomotor or
Stepper Motor
Pulse-input Servo Drive
C200HW-NC113
C200HW-NC213
C200HW-NC413
3
Features
C200HW-NC113/NC213/NC413
•
Simple positioning systems can be created by directly specifying operation from the CPU.
•
Positioning data is saved in internal flash memory, eliminating the need to maintain a backup battery.
•
S-curve acceleration/deceleration, forced starting, and other features are also supported.
•
The SYSMAC-NCT Support Tool enables easy creation of positioning data and storage of the data in files, for simplified programming and setup.
•
S-curve profile can be set independently for each axis.
•
With 4-axis model, up to four axes can be used together with linear interpolation, or all can be operated independently.
3
Specifications
Model (See Note 1.)
Classification
Control method
Control output signals
C200HW-NC113
C200H Special I/O Modules
1
--9,999,999 to +9,999,999 pulses
C200HW-NC213
Open-loop, automatic trapezoid acceleration/deceleration
Pulse-train outputs
2 Controlled axes
Position data
No. of positions
Speed data
100 per axis
1 to 500 kpps
No. of speeds 100 per axis
Acceleration/ deceleration times 0 to 250 s (time to max. speed)
Direct operation
S-curves
Supported
Supported
Flash memory
Windows-based Support
Software
Supported
Supported
C200HW-NC413
4
Note: 1. NCT Support Tool Software, part number WS01-NCTF1-E is required to configure the Position Control Module and should be ordered separately.
2. Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W334.
Additional Information: For more details and specifications on any of these modules, refer to manual W334.
:6
Modules
Motion Control Module
High-precision, Two-axis Motion Control with Multi-tasking G-code Language Programming
The Motion Control Module provides semiclosed-loop control with analog outputs for up to 2 axes, and supports G-code language for advanced position control. Multi-tasking allows you to run the two axes independently for a wider range of applications.
3
System Configuration
CX-Motion or
MC Support Software
(IBM PC/AT or compatible)
C200H-MC221
3
Features
•
High-speed control of up to 2 axes within one module.
•
Multi-task programming with G-language.
G-language is ideal for motion control and enables easy creation of multi-axis programs. It also reduces the load on the CPU.
•
Compatible with absolute encoders.
•
Encoder response frequency: 250 kpps.
•
Operation also possible with manual pulse generator.
•
Special cables available for easy connection to Omron
Servo Drives.
•
High-speed response for commands from CPU.
Teaching Box
Analog Input
Servo Drive
Motion Control
Screw Terminal Block
3
Specifications
Model
Classification
Control method
Control output signals
Controlled axes
Number of tasks
Number of programs
Program capacity
Position data capacity
Maximum command value
Acceleration/deceleration times
S-curve speed curves
C200H-MC221 (See Note 1.)
C200H Special I/O Module
Semiclosed loop
Analog
2 axes
2 (task = unit of program execution)
100 max. when 1 task is used.50 max. when 2 tasks are used.
800 blocks max. when 1 task is used; 400 blocks max. when 2 tasks are used.
2,000 positions max.
--39,999,999 to +39,999,999 pulses
0 to 9,998 ms (in 2-ms increments)
Supported
Note: 1. To program and configure the Motion Control Module requires either CX-Motion (part number WS02-MCTC1-E) or MC Support Software (part number CV500-ZN3AT1-E). Order separately.
2. Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W315.
Additional Information: For more details and specifications on any of these modules, refer to manual W315, catalog GCSMD1, and contact your sales representative for additional information.
:7
Modules
New
CS1 Series Motion Control Modules
High speed, High Precision, 2- or 4-axis Motion Control with New Multi-Tasking G-code Language Programming
The Motion Control Module provides semiclosed-loop control with analog outputs for up to 4 axes, and supports
G-language for advanced position control. Multi-tasking allows you to run the two axes independently for a wider range of applications.
3
System Configuration
CX-Motion
Support Software
(IBM PC/AT or compatible)
CS1W-MC221 CS1W-MC421
Analog Input
Servo Drive
Teaching Box
3
CX-Motion Software
•
Multi-lingual.
•
Utilizes CX-Server communications.
•
Supports Single-Port Multiple
Access (SPMA).
•
Easy setup and configuration.
•
Online monitoring and data trace of axis motion data.
Motion Control
Terminal Block
3
Features
•
High-speed control of up to 2-or 4-axes within one module.
•
Control up to 32 axes per system.
•
Utilize new CX-Motion software.
•
Encoder response frequency: 500 kpps.
•
Point-to-point and continuous path control.
•
Helical circular interpolation available.
•
Initiate interrupts to the CPU using D-Code.
•
High speed actuation times.
•
2-axis = 8 ms; 4-axis = 12 ms.
•
Error counter reset.
•
New G-code (G-32) for winding applications.
3
Specifications
Model
Classification
Control method
Control axes
Number of tasks
Number of programs
Program capacity
Position data capacity
Maximum command value
Acceleration/deceleration times
S-curve speed curves
CS1W-MC221
CS1 Special I/O module
CS1W-MC421
Semi-closed loop
2 axes
2
4 axes
4
100 max. when 1 task is used; 50 max. when 2 tasks are used; 25 max. when 4 tasks are used
2,000 blocks
2,000 positions max.
--39,999,999 to + 39,999,999
0 to 100,000 ms (in 2 ms increments)
Supported
Note: 1. CX-Motion (part number WS02-MCTC1-E) is required to program and configure the CS1 Series Motion Control Modules and should be ordered separately.
2. Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W359.
Additional Information: For more details and specifications on any of these modules, refer to manual W359.
:8
Modules
High-speed Counter Modules
Two External Inputs and Eight External Outputs with a Variety of Operating Modes
C200H-CT021
C200H-CT001-V1
C200H-CT002
The High-speed Counter Module counts high-speed pulses that are too fast for normal input modules, and then it produces outputs according to the count value. Models are available with either one or with two counter points.
The C200H-CT001-V1 connects to incremental encoders and other devices with open-collector outputs. It is a high-speed reversible counter that counts one pulse input up to 50 kcps.
The C200H-CT002 connects to incremental encoders and other devices with RS-422 line driver outputs. It is a highspeed reversible counter that counts one pulse input up to
75 kcps.
The C200H-CT021 connects to incremental encoders and other devices with either open-collector or RS-422 line driver outputs (selected when wiring). It is a high-speed reversible counter that counts two pulse inputs up to 50 or 75 kcps.
3
System Configuration
3
Features
•
Three input modes: differential phases, up/down inputs, pulse and direction inputs
•
Multiplication function (x1/x4) for differential phase input
•
External control inputs: two.
•
External outputs: eight.
•
3 functions with 6 counting modes:
Drum Function: Linear mode, circular mode.
Preset Counter Function: Preset mode.
Counting Function: Gate mode (normal and cumulative), latch mode, sampling mode.
•
Long-distance inputs and noise resistance (line driver input).
Counter inputs
Encoder
8 External Outputs
3
Specifications
Classification Number of counters
1
Encoder A and B input, pulse input, Z signal Maximum counting speed
50 kcps C200H Special
I/O Module
2
Open-collector Input voltage: 5 VDC, 12 VDC, or 24
VDC
RS-422 line driver (equivalent to Am26LS31)
Open-collector Input voltage: 12 VDC or 24 VDC
RS-422 line driver (equivalent to Am26LS31)
75 kcps
50 kcps
75 kcps
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W141.
Model
C200H-CT001-V1
C200H-CT002
C200H-CT021
Additional Information: For more details and specifications on any of these modules, refer to manual W141.
:9
Modules
Radio Frequency ID Controller Modules
Integrate an RFID System with a CS1 Series Controller, Easily Configured with a Programming Console
Radio Frequency ID Systems provide data tracking for parts and assemblies in environments too dirty or cluttered for bar coding. RFID is not line-of-sight, so the reusable Data Carriers can be placed inconspicuously. Omron’s read/write systems allow collection and retention of assembly directions, test data and special customer requirements.
The PLC-mounted RFID Controller Modules send read/write commands from the CPU to read/write data in reusable data carrier tag memory.
The C200H-IDS01-V1 is used with the V600 Series for shortdistance communications with electromagnetic coupling, and the C200H-IDS21 is used with the V620 Series for long-distance communications with microwaves.
The Programming Console can be connected directly to the
RFID Controller Module to send commands to Read/Write
Data Carriers and monitor the results. The Programming Console is particularly useful with initial system startup.
3
System Configuration
Programming Console
Read/Write Head
C200H-IDS01-V1
(electromagnetic, for short distances)
C200H-IDS21
(microwave, for long distances)
3
Features
•
Connects RFID System to the CS1 Series Controller.
•
Read data from Data Carriers simply by sending a read command.
•
Read/write up to 1,024 bytes of data.
•
Record error logs with up to 30 records.
•
Use a Programming Console to monitor and control operation.
Data Carrier
3
Specifications
Classification
C200H Special I/O Module
Connectable ID System
V600 Series (electromagnetic, for short distances)
V620 Series (microwave, for long distances)
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W250.
Model
C200H-IDS01-V1
C200H-IDS21
Additional Information: For more details and specifications on any of these modules, refer to manual W250 (IDSC RFID Controller User Manual) and W341 (CS1
Series Programming Console).
::
Modules
CS1 CPU Bus I/O
Serial Communications Boards
Serial Communications Module
Support Protocol Macros, Host Link Communications, and 1:N NT Links for a Variety of Applications
Increase the number of serial ports available (RS-232C or
RS-422A/485) by choosing either a Serial Communications
Board or Serial Communications Module. Specify Protocol
Macros, Host Link Communications, or 1:N NT Links separately for each port. With the CS1 Series, you can easily provide the right number of serial ports for your system.
Serial
Communications Boards
CS1W-SCB21
CS1W-SCB41
Serial
Communications
Module
CS1W-SCU21
3
System Configuration
Host computer
Programming device
Serial Communications
Board
Operator
Interface
Serial Communications
Module
3
Features
•
Serial Communications Board:
Increase the number of serial ports without using I/O slots.
Connect general-purpose external devices 1:N using
RS-422A/485.
Generate interrupts in CPU when data is received.
•
Serial Communications Module:
Mount up to 16 modules (including all other CPU Bus
Modules) on CPU racks or Expansion Racks. Ideal for systems that require many serial ports.
Machine Machine
Microcomputer
(or other device)
Device
Non-Omron
PLC
Device
3
Specifications
Module Classification
Serial Communications Board Inner Board
Serial Communications Module CS1 CPU Bus Module f
Serial communications modes
Serial h
1:N NT Link t P t l
Model
RS-232C x 2 CS1W-SCB21
RS-232C x 1, RS-422A/485 x 1 CS1W-SCB41
RS-232C x 2 CS1W-SCU21
Additional Information: For more details and specifications on any of these modules, refer to manual W336 (CS1 Series Serial Communications Boards and
Modules); Also refer to W342 (CS1 Series Communications Commands).
:;
Special I/O
Modules
ASCII/BASIC Modules
Easily Perform ASCII Data Communications and Utilize BASIC Programming Language
3
System Configuration
The ASCII Modules support BASIC language programming and RS-232C and RS422A/485 serial communications.
BASIC programming enables ASCII communications with essentially any external device. It can also be used as a special processing module to aid the CPU without using external communications.
The C200H-ASC21/ASC21/ASC31 Modules provide shared memory with the CPU, and both the ASCII Module and the
CPU can access the shared memory asynchronously, providing for high-speed data exchanges between the two devices without using interrupts.
Terminal
(e.g., Windows
Hyperterminal)
C200H-ASC02
C200H-ASC11
C200H-ASC21
C200H-ASC31
BASIC program
RS-232C
RS-232C
General-purpose external device
3
Features
•
Perform ASCII communications with a wide range of external devices.
•
The C200H-ASC11/ASC21/ASC31 function as special processing Modules with BASIC programming.
•
Large-capacity user memory: 200 kbytes
•
Model available with RS-422A/485 port for 1:N communications.
•
Various forms of data exchanges with CPU: Select the best method for the read/write trigger and timing.
•
High-speed data exchanges possible with shared memory
(not dependant on I/O refresh) of module and CPU.
•
A wide range of interrupt processes: Interrupts from CPU to ASCII Module, communications interrupt, key interrupts, timer interrupts, error interrupts, etc.
•
Easy control of transmission control signals.
•
Calculation instructions for error check codes.
•
Many BASIC functions (break points, 1-step execution, execution stop monitoring, etc.)
•
Error log supported with up to 30 error records.
3
Specifications
Classification
C200H Special
User memory
24 kbytes
Shared memory
Provided d i I/O
None
)
Serial communications ports
RS-232C x 2
RS-232C x 1, RS-422A/485 x 1
RS-232C x 2, RS-232C x 1 for terminal
RS-232C x 2
Model
C200H-ASC11
C200H-ASC21
C200H-ASC31
C200H-ASC02
Additional Information: For more details and specifications on any of these modules, refer to manuals W165 and W306.
:<
Modules
Protocol Macros
Easily Create Protocols for Data Exchange with External Devices; Execute with One Instruction
3
System Configuration
Standard system protocols
(provided in Module or Board)
Omron component
Protocols for communications with external devices can be easily created according to the communications standards required by the external device. Protocol macros enable communications with essentially any external device with an
RS-232C or RS-422A/485 port without programming difficult communications within the CPU ladder logic.
Standard system protocols are provided for communications with Omron components, such as Temperature Controllers,
Panel Meters, Bar Code Readers, and Modems. A software tool called CX-Protocol is also available to enable creation of protocols for most any external device.
CX-Protocol
User-created protocols
3
Types of Protocol
Protocols
Standard system protocols
User-created protocols
External devices
OMRON components
General-purpose external device
Required products
Serial Communications
Board or Module
Create and transfer protocols
Serial Communications
Board or Module +
CX-Protocol (Protocol
Development Software)
General-purpose external device
Note: To effectively create a custom protocol for any non-Omron external devices, you must have a detailed understanding of the protocol for each external device.
3
Standard System Protocols
Device
CompoWay/F-compatible components and devices
Send/receive sequences
CompoWay/F commands
Model
OMRON CompoWay/F slave components
E5CK Process
Controllers
Temperature
1/16 DIN Process Controller with Communications
(53 x 53 mm)
Temperature Controllers with Digital Indications (Type J with communications) (96 x 96 mm or 48 x 96 mm)
1/4 DIN Advanced Process Controllers with
Communications (96 x 96 mm)
Multi-loop Temperature Controller with communications
(8 control points)
Digital Panel Meter
Present value read, set point read,
Set point write, alarm write, PID E5 P J-A2HO
ES100
P
E5ZE
Bar Code
R d
Laser Scanner type
CCD type
Laser Micrometer
Visual
I ti
High speed, high precision, low cost
High-precision inspection/positioning
Character inspection software/positioning software
RFID
C t ll
Electromagnetic coupling
Microwave
Hayes Compatible Modem (AT Command)
Display value read, comparison value read, write, etc.
K3T
P
, , V500
Measurement condition set, continuous measurement start, etc.
V520
3Z4L t t
F200
F300
F350 Measurement, positioning, inspection, character inspection, etc.
, , V600
V620
Modem initialize, dial, send, etc.
---
3
CX-Protocol Software
Software part number WS02-PSTC1-E, is available for customers who have applications that require development of custom communications protocols.
Additional Information: For more details, refer to manual W344 (CX-Protocol Operation Manual).
;3
Modules
Serial Communications Summary
This table summarizes the variety of serial communications options available when using a CS1 Series Controller.
Serial Communications Options
Module Ports Serial communications mode (protocol/device)
Protocol macros
Host Link NT Links Noprotocol
Peripheral bus
Program-ming
Devices
Programming
Console bus
Programming
Console
BASIC programming
Message Model communications
CPU
Serial
Modules
ASCII/ i
Port 1: Peripheral
Port 2: RS-232C
Port 1: RS-232C
Port 2: RS-232C
Port 1: RS-232C Yes
Port 2: RS-422A/485 Yes
Port 1: RS-232C
Port 2: RS-232C
Port 1: RS-232C
Port 2: RS-232C
Yes
Yes
No
No
Generalpurpose external devices
No
No
Yes
Yes
Port 1: RS-232C
Port 2: RS-232C
No
No
Port 1: RS-232C No
Port 2: RS-422A/485 No
Port 1: RS-232C
Port 2: RS-232C
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Host computers
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Omron
NT Series
HMI
No
No
No
No
No
No
No
No
No
No
No
No
Generalpurpose external devices
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
No
No
All
CS1W-
CS1W-
CS1W-
C200H-
C200H-
C200H-
C200H-
;4
Modules
Voice Module
Special I/O
Provides Audible Notification of System Conditions or Alarms
Use the Voice Module for operator interface messages.
Record up to 60 voice messages on site, or use a tape recorder and transfer the messages to the module.
Messages can also be uploaded or downloaded through the RS-232C port on the front panel. The built-in speaker enables immediate message verification. Message length and sound quality are selectable.
C200H-OV001
•
Microphone jack enables live message broadcast.
•
Flexible message length.
•
Messages can be interrupted to start another message.
•
Messages can be recorded in phrase and word combination formats.
•
Upload or download messages through the RS-232C port on the front panel.
3
System Configuration
C200H Alpha or CS1 Series
Controller
Voice Input
Input Devices
•
Computer
•
Microphone
•
Tape recorder
Microphone
(dynamic, 600
Ω
)
Cassette tape recorder
(50 k
Ω
, 3.3 V max., audio use)
Voice Module
Voice Output
Module’s internal amplifier output
LINE OUT (600
Ω
)
Speaker
(8
Ω
, commercially available)
Output Devices
•
Computer
•
Printer
•
Speaker
External amplifier
Speaker
;5
Special I/O
Modules
Voice Module
3
Specifications
Classification
Model
Voice synthesis method
Message
Message output (switch-selectable)
Built-in monitor speaker
Input frequency
Output frequency characteristics
Low-pass filter (LPF) selector function (see note)
Message memory
Self-diagnosis function
Battery life
I/O words required
Internal current consumption
Weight
)
C200H Special I/O Module
C200H-OV001
Recording time
Adaptive differential pulse-coded modulation (ADPCM)
32, 48, or 64 s (switch-selectable)
Capacity (sentences and phrases) 60 max.
MIC IN
LINE IN
Microphone input: Unbalanced dynamic microphone (600
Ω
)
Tape input: Input impedance: 50 k
Ω
, unbalanced; Maximum input voltage: 3.3 V
SPEAKER OUT
LINE OUT
Built-in amplifier output: 0.14 W (8
Ω speaker)
External amplifier output: 600
Ω unbalanced transformer output
Maximum output voltage: 0.5 V rms (effective value)
Balanced and unbalanced external amplifiers are connectable
Diameter 27 mm, 0.1 W (8
Ω
)
32-second recordings: 8 kHz
48-second recordings: 5.3 kHz
64-second recordings: 4 kHz
External communication function (save recorded messages)
32-second recordings: 100 Hz to 3.2 kHz
48/64-second recordings: 100 Hz to 2.2 kHz
Cutoff frequency: 3.2 kHz for 32-second recordings, 2.2 kHz for
48/64-second recordings
128K bytes RAM (battery powered)
RS-232C (Baud rate: 19,200/9,600/4,800/2,400 bps.
XON/XOFF: yes/no, CTS/RTS: yes/no)
CPU watchdog timer, LOW battery voltage detection
5 years at 25
°
C (battery life is shorter for higher temperatures)
10 (Special I/O area)
5 VDC, 0.3 A max.
400 g max.
Note: The recording time of the Voice Module is varied by changing the module’s input frequency. For improved sound quality, the cutoff frequency of the low-pass filter is automatically changed to a lower frequency when the recording time is increased from 32 to either 48 or
64 seconds. (The output frequency is set to 100 Hz to 2.2 kHz when the recording time is set to 48 or 64 seconds.)
Additional Information: For more details, refer to manual W172.
;6
Modules
Ethernet Module
CS1 CPU Bus I/O
Provides Interface and Communications Between Information-Level Devices
Achieve a wide range of capability from PLCs connected to an
Ethernet network. Transfer data with TCP/IP or UDP/IP socket services, execute OMRON’s standard FINS commands, transfer files with FTP, or send e-mail with SMTP. Select the communications services that are required and flexibly connect
PLCs on an information level Ethernet network.
3
System Configuration
CS1W-ETN01
3
Features
•
Access socket services simply by manipulating specific bits in memory.
•
Take advantage of electronic mail (SMTP).
•
Interconnect to Controller Link and other networks.
•
Use Ethernet standard protocols: TCP/IP and UDP/IP.
•
Use Omron’s standard FINS message communications.
•
Transfer files with host computers using FTP.
•
Set communications parameters with CX-Programmer.
•
Connect CS1, C200H Alpha, CVM1, and CV Series
PLCs.
Ethernet Module
Ethernet network
Ethernet Module
3
Specifications
Classification
CS1 CPU Bus Module
Communications services
FINS communications, FTP server, socket services, and e-mail services
Model
CS1W-ETN01
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W343.
Additional Information: For more details and specifications on any of these modules, refer to manual W343.
;7
CS1 CPU Bus I/O
Modules
Controller Link Modules and Controller Link Support Boards
Omron’s Control-Level Network
Controller Link is Omron’s premier control-level network.
It supports automatic data links between two PLCs or between PLCs and host computer(s), as well as links for programmed data transfers. You get high-capacity, flexible data links and high-capacity data transfers with messages.
For a low-cost communications system, twisted-pair cables can be used.
3
System Configuration
Data Links
Controller Link
Module
PLC PLC PLC
CS1W-CLK21
Controller Link
Wired Module
CS1W-CLK11
Controller Link
Fiber-optic Module
Shared memory data transfers (continuous) for I/O bits, link bits, DM Area words, etc.
3G8F5-CLK21-E (Wired) and
3G8F5-CLK11-E (Fiber-optic)
Personal Computer Boards Message Communications
Controller Link
Module
PLC PLC
CS1
PLC
Programmed data transfers (as required)
Communications instruction in user program
3
Features
•
Achieve high-capacity, flexible data links.
•
Transfer large volumes of data through a message service.
•
Connect through twisted-pair cables or fiber-optic cables.
•
Connect CS1, C200H Alpha, CVM1, and CV Series PLCs.
•
Complete error correction and troubleshooting functions.
•
Set communications parameters with CX-Programmer.
3
Specifications
Module/Board
Controller Link
Controller Link t B d
Classification
CS1 CPU Bus
Personal t b d
Communications Media
Data links and message communications
Wired
Fiberoptic
Wired
Fiberoptic
Specifications
Multiple modules can be mounted to CPU
R k CS1 E i R k
Model
CS1W-CLK21
CS1W-CLK11
CPU Processor Intel 386 or better, ISA bus
IBM PC DOS V 7 0 MS DOS V 6 2
Microsoft C Ver. 70A
3G8F5-CLK21-E
3G8F5-CLK11-E
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W309.
Additional Information: For more details and specifications on any of these modules, refer to manual W309 (Controller Link Modules); W308 (Controller Link
Support Software); W307 (Controller Link Support Boards).
;8
Modules
Special I/O
DeviceNet Master and I/O Link Modules
Open, Device Level Remote I/O Network
This is Omron’s offering of the DeviceNet open field network
—a multi-bit, multi-vendor network for machine control and information. Remote I/O for automatic data transfers between the CPU and Slaves (with no programming in the CPU) combines with message communications (that can be programmed in the CPU) to send read/write messages to slaves and control slave operation.
One of the slaves that can be connected is the Multiple I/O
Terminal, a building-block system that combines Multiple I/O
Remote I/O Access Modules. The Multiple I/O Terminal provides flexible expansion through easily connected, distributed
I/O Modules.
C200HW-DRM21-V1
DeviceNet Master
Module
C200HW-DRT21
DeviceNet I/O Link
Module
3
System Configuration
3
Features
•
Multi-vendor network compatible with other DeviceNet components.
•
Use both remote I/O and message communications.
•
Freely allocate up to 4,800 points of remote I/O.
(Configurator required.)
•
Connect up to 63 slaves.
•
Network multiple PLCs with DeviceNet Master Modules.
•
Ideal for multi-bit control as a multi-level network.
•
Maximum transmission distance of 500 m at 125 Kbps.
Perfect for conveyor systems.
•
A wide range of connection methods, including
T-branches and multidrops, for flexible line expansions or alterations.
•
Read a remote controller’s memory as remote I/O by mounting a C200HW-DRT21 DeviceNet I/O Link Module.
•
Use RS-232C to connect external devices for message communications.
3
Specifications
DeviceNet Master Module
Classification
C200H Special
I/O Module
Communications
Remote I/O and messages
DeviceNet
Master Module
DeviceNet I/O
Link Module
Slaves
DeviceNet
Multiple I/O Terminal
Specifications
Mount one Module without Configurator and up to 16 Modules using Configurator.
500 Kbps: 100 m
125 Kbps: 500 m
63 nodes max.
Model
C200HW-DRM21-V1
Note: 1. Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W267.
2. Some DeviceNet systems may require the of the DeviceNet Configurator software and Communications Board, part number
3G8F5-DRM21-E. Part number 3G8E2-DRM21-E is the PCMCIA version of the DeviceNet Configurator Software for the laptop PCs.
Additional Information: For more details and specifications on all of the Omron DeviceNet products, refer to Catalog No. P10FAZ1 (DeviceNet Products Catalog), and manual W267 (DeviceNet Operation Manual).
;9
Special I/O
Modules
DeviceNet products
DeviceNet Slave Modules
Slave
Basic I/O
Modules
Analog
Modules
Special
Modules
Remote Transistor Input
Modules
Remote Transistor Output
Modules i t I/O
Remote Adapters
Sensor Modules
Temperature Input
B7AC Interface Module
CQM1 I/O Link Module
Analog Input Modules
Analog Output Modules
C200H I/O Link Module
RS-232C Module d l
B7AC Interface Module
I/O points
8 inputs
16 inputs
8 outputs
16 outputs
Features
NPN (PNP) versions
NPN (PNP) versions
NPN (PNP) versions
NPN (PNP) versions
Mounting
DIN rail or screws
Model
DRT1-ID08(-1)
(See Note 2.)
DRT1-ID16(-1)
(See Note 2.)
DRT1-OD08(-1)
(See Note 2.)
DRT1-OD16(-1)
(See Note 2.)
DRT1-ID08C
DRT1-OD08C
DRT1-MD16C
8 inputs (NPN)
8 outputs (NPN)
8 inputs and
8 outputs (NPN)
16 inputs
I/O Connector.
Screws
16 outputs
NPN (PNP) versions
NPN (PNP) versions
16 inputs (NPN)
8 inputs and
8 outputs (NPN)
(See Note.) ith 2 i t
30 points
(10 words/B7AC)
16 inputs and
16 outputs
2 or 4 inputs
(2 or 4 words)
(voltage or current)
4 inputs (4 words)
(voltage or current)
Thermocouple inputs.
Platinum resistance thermometer inputs.
Connect to three B7ACs with one
Module (three ports).
Mount up to 3 or 7 Modules to CQM1
(depending on model).
Input ranges:
1 to 5 V, 0 to 5 V, 0 to 10 V, --10 to
10 V, 0 to 20 mA, 4 to 20 mA
(selectable) 1/6,000 resolution.
Input ranges:
1 to 5 V, 0 to 5 V, 0 to 10 V,
0 to 20 mA, 4 to 20 mA (selectable)
1/30,000 resolution
2 outputs (2 words) Output ranges:
1 to 5 V, 0 to 10 V, --10 to 10 V,
0 to 20 mA, 4 to 20 mA (selectable)
1/6,000 resolution
512 inputs
(32 words) max.
512 outputs
(32 words) max.
Mount up to 16 Modules to C200H
Alpha or CS1 Controller
16 inputs (1 word) Two RS-232C ports
Set and Control via explicit messages
30 points
(10 words/B7AC)
RS-232C status input to memory
Connect to three B7ACs with one
Module (three ports).
DIN rail or screws
DRT1-ID16X(-1)
(See Note 2.)
DRT1-OD16X(-1)
(See Note 2.)
DRT1-HD16S
DRT1-ND16S
DRT1-TS04T
DRT1-TS04P
M5 screws DRT1-B7AC
To CQM1
DIN rail or screws
To backplane
DIN rail or screws
CQM1-DRT21
DRT1-AD04
DRT1-AD04H
(high-resolution)
DRT1-DA02
C200HW-DRT21
DRT1-232C
M5 screws DRT1-B7AC
Note: 1. I/O points for the I/O Link Module are internal I/O points in the CPU.
2. These modules are available in both NPN and PNP. Adding a “-1” suffix to the part number indicates the PNP version.
Additional Information: For more details and specifications, refer to manual W347 (C200HW-DRT21) and manual W348 (DRT1-COM GT1 Series DeviceNet
Multiple I/O Terminals Operation Manual).
;:
Modules
Multiple I/O Products
DeviceNet Slaves with Additional I/O Flexibility
3
System Configuration
DeviceNet Master Module
Multiple I/O Terminal
DeviceNet network
I/O Module Connecting Cables
A Communications Module can be connected to the
DeviceNet Master Module to interface various types of I/O
Modules. Allocations and address settings are not required for the I/O Modules, enabling flexible, simple distributed I/O.
3
Features
•
To expand I/O, merely add I/O Modules to the
Communications Module.
•
Create a low-cost multibit system.
•
Select from a wide range of I/O Modules.
Communications
Module
I/O Modules
I/O Module Interface: 8 Modules max.
3 m total, 1 m between Modules
1024 I/O points max.
3
Multiple I/O Terminal Modules
Communications Module
Number of Slaves
8
Number of Slave I/O points
1,024 max., input and output combined
Digital I/O Modules
Module Classification
Terminal
Bl k t
Connectort type
Multi-point
Digital input
Digital output
Digital input
Digital output
Digital input
Digital output
Digital input
Digital output
Digital input
Digital output
Internal I/O circuit common
I/O pts
NPN (+ common) 16
PNP (-- common)
NPN (-- common)
PNP (+ common)
NPN (+ common)
PNP (-- common)
NPN (-- common)
PNP (+ common)
NPN (+ common)
PNP (-- common)
NPN (-- common)
PNP (+ common)
NPN (+ common)
PNP (-- common)
NPN (-- common)
PNP (+ common)
NPN (+ common) 32
PNP (-- common)
NPN (-- common)
PNP (+ common)
Molex
Rated voltage
24 VDC
I/O
Connections
M3 terminal bl k
Rated voltage
I/O specifications
24 VDC DC/Tr
0.5 A DC/Tr
25-pin D-sub
Fujitsu
(See Note.)
DC/Tr
0.5 A DC/Tr
DC/Tr
0.5 A DC/Tr
DC/Tr
0.5 A DC/Tr
DC/Tr
0.5 A DC/Tr
Note: See the G79 and XW2Z Cables in the tables on the following pages.
Standards Model
UL, CSA, EC DRT1-COM
Standards Model
, GT1-ID16
GT1-ID16-1
GT1-OD16
GT1-OD16-1
GT1-ID16MX
GT1-ID16MX-1
GT1-OD16MX
CE
GT1-OD16MX-1
GT1-ID16ML
GT1-ID16ML-1
GT1-OD16ML
GT1-OD16ML-1
GT1-ID16DS
GT1-ID16DS-1
GT1-OD16DS
GT1-OD16DS-1
UL, CSA, EC GT1-ID32ML
GT1-ID32ML-1
GT1-OD32ML
GT1-OD32ML-1
Additional Information: For more details and specifications on Multiple I/O Terminal Modules, refer to manual W348.
;;
Modules
Multiple I/O Products
Relay Output Modules
Classification I/O points
Relay output
Analog Input Modules
Classification
16 points
8 points
I/O
8 inputs
4 inputs
I/O connection method
M3 terminal bl k
I/O connections Supply voltage
Connectors 24 VDC
Terminal block
Analog Output Modules
Classification I/O I/O connections
4 outputs Connector
Terminal block
Supply voltage
24 VDC
Supply voltage
24 VDC
I/O specifications
2 A, AC/DC, SPST-NO
5 A, AC/DC, SPST-NO
I/O specifications
1 t 5 V 0 t 10 V 10 t 10 V
I/O specifications
0 to 5 V, 1 to 5 V, 0 to 10 V, --10 to 10 V
0 to 5 V, 1 to 5 V, 0 to 10 V, --10 to 10 V, 4 to
20 mA
Standards
CE GT1-ROS16
UL, CSA, EC GT1-ROP08
Standards Model
, GT1-AD08MX
GT1-AD04
Standards
Model
Model
, GT1-DA04MX
GT1-DA04
Counter Module
Classification
Counter Module
External I/O
1 input, 2 outputs
Connecting Cable
Name
I/O Module Connecting Cable
I/O connection method Operating mode
Terminal block Linear counter, 50 kHz
Specification
1 m
Standards
EC
Model
GT1-CT01
Model
GCN1-100
1.0
2.0
3.0
5.0
3
G79 Cables with Connectors
Dimensions (For 32-pt modules, with Fujitsu connectors.) ) Length (m)
A
1.0
B
.75
1.25
1.75
2.75
4.75
Straight length
Model
For input
G79-I100C-75
G79-I150C-125
G79-I200C-175
G79-I300C-275
G79-I500C-475
For output
G79-O100C-75
G79-O150C-125
G79-O200C-175
G79-O300C-275
G79-O500C-475
Length L (m)
1.0
1.5
2.0
3.0
5.0
Dimensions (For 16-pt modules, with Fujitsu connectors.)
L = Cable length
Model
G79-100C
G79-150C
G79-200C
G79-300C
G79-500C
Note: 1. These cables are to be used with the GT1-
====
ML, Fujitsu Connector Style of Multiple Terminal I/O Modules.
2. See the I/O Wiring Accessories Section for more detail regarding I/O block options that can be used with GT1 connector-style modules.
Additional Information: For more details and specifications on Multiple I/O Terminal Modules, refer to manual W348.
;<
Modules
Multiple Terminal I/O Products
3
XW2Z Cables with Connectors
Length L (m)
0.5
1.0
1.5
2.0
3.0
5,000
Dimensions (For 32-pt modules, with Fujitsu connectors.) Model
XW2Z-050B
XW2Z-100B
XW2Z-150B
XW2Z-200B
XW2Z-300B
XW2Z-500B
Length L (m)
0.5
1.0
1.5
2.0
3.0
5.0
Dimensions (For 16-pt modules, with Fujitsu connectors.) Model
XW2Z-050A
XW2Z-100A
XW2Z-150A
XW2Z-200A
XW2Z-300A
XW2Z-500A L = Cable length
Note: 1. These cables are to be used with the GT1-
====
ML, Fujitsu Connector Style of Multiple Terminal I/O Modules to connect to XW2B
Wiring Blocks.
2. See the I/O Wiring Accessories Section for more detail regarding I/O block options that can be used with GT1 connector-style modules.
Additional Information: For more details and specifications on Multiple I/O Terminal Modules, refer to manual W348.
<3
Special I/O
Modules
Profibus-DP Master
Open Field Bus Networking and Device-Level Control
There are two types of master devices: DP Master Class 1
(DPM1) and DP Master Class 2 (DPM2). A DPM1 is a central controller which exchanges information with the decentralized stations (i.e., DP slaves) with a specified message cycle.
DPM2 devices are programmers, configuration devices or operator panels. They are used during startup for configuration of the DP system or for operation and monitoring purposes.
3
System Configuration Capabilities
Profibus-DP configurations can include multiple active
(master) stations as well as multiple passive (slave) stations.
Master stations form a logical token ring and support communication to assigned slave stations to manage both master--master and master--slave communications and control.
3
System Configuration
CS1 Series Controller
Transmission
CPU
Power
Supply
Transmission
Repeater
Station 32
Transmission
C200HW-PRM21
3
Features
•
Profibus DP Master Module for C200HS,
C200H Alpha and CS1.
•
Special I/O Module, similar to DeviceNet Master.
•
Can be mounted in any backplane slot, including expansion backplane.
•
Up to 10 Master Modules per C200HS or
C200H Alpha or CS1.
•
Each Master supports up to 124 slaves.
•
Supports 9.6 k to 12 Mbps communication speeds.
•
All mandatory Profibus-DP functions, including
SYNC/FREEZE, are supported.
Transmission
Profibus
Station
2
Station
3
Station
31
Station
33
Station
34
3
Specifications
Item
Profibus DP Master Module for C200HS, C200H Alpha and CS1
Software, Configuration Profibus (SyConDP)
.
Model
C200HW-PRM21
WS02-PDC1-E
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W349.
Additional Information: For more details and specifications on any of these modules, refer to manual W349.
<4
Modules
CompoBus/S Master Module
Special I/O
High-speed Bus for Distributed Machine Control and Reduced Wiring Cost
CompoBus/S is a high-speed bus that automatically transfers remote I/O status to the CPU without any programming in the
CPU. High-speed remote I/O is supported by a communications cycle time of 1 ms maximum for 256 I/O points.
3
System Configuration
CompoBus/S Master Module
C200HW-SRM21-V1
3
Features
•
Distributed machine control with a high-speed communications cycle.
•
Use a 500 m trunk line for a wide range of machine control.
•
Easy expansions at any location with T-branches.
•
Reduce wiring costs with Belden #9409 twisted-pair cable, VCTF cable, or a special flat cable.
•
Sensor connectors for easy wiring.
•
Supports a variety of digital and analog slave modules.
3
Specifications
Classification
C200H Special I/O Module
Communications
Remote I/O
Remote I/O
CompoBus/S network
Specifications
Mount up to 16 Modules
Slaves
32 Terminals max.
Note: Basic connector(s) included. For dedicated Omron cables, connectors and accessories, refer to manual W266.
Model
C200HW-SRM21-V1
Additional Information: For more details and specifications on this module, refer to manual W266 (CompoBus/S Operation Manual).
<5
Modules
CompoBus/S Products
3
CompoBus/S Slave Options
Slave
Remote I/O Transistor Terminals
Remote I/O Transistor Terminals d t f h i t
Remote I/O Transistor Terminal with Sensor t
Remote I/O Transistor Terminal with MIL t
Remote I/O Printed Circuit Board Modules
Sensor Amp Terminals
Expansion Sensor Amp Terminals
Sensor Remote Terminal Blocks
Bit Chain Terminal
I/O Points
4 inputs (NPN)
4 inputs (PNP)
8 inputs (NPN)
8 inputs (PNP)
16 inputs (NPN)
16 inputs (PNP)
4 outputs (NPN)
4 outputs (PNP)
8 outputs (NPN)
8 outputs (PNP)
16 outputs (NPN)
16 outputs (PNP)
16 inputs (NPN, + common)
16 inputs (PNP, -- common)
16 inputs/outputs (NPN, -- common)
16 inputs/outputs (PNP, + common)
16 outputs (NPN, -- common)
16 outputs(PNP, + common)
8 inputs (NPN, + common)
8 inputs (PNP, -- common)
8 outputs (NPN, -- common)
8 outputs (PNP, + common)
16 inputs (NPN, + common)
16 inputs (PNP, -- common)
16 outputs (NPN, -- common)
16 outputs (PNP, + common)
8 outputs
16 outputs
8 outputs
16 outputs
16 inputs
16 outputs
4 inputs (1 word x 4 terminals)
4 inputs (4 words x 1 terminal)
4 inputs (1 word x 4 terminals)
4 inputs (4 words x 1 terminal)
8 inputs
8 outputs
4 inputs and 4 outputs
8 inputs or 8 outputs
Model (See Note 2.)
SRT2-ID04
SRT2-ID04-1
SRT2-ID08
SRT2-ID08-1
SRT2-ID16
SRT2-ID16-1
SRT2-OD04
SRT2-OD04-1
SRT2-OD08
SRT2-OD08-1
SRT2-OD16
SRT2-OD16-1
SRT2-ID16T
SRT2-ID16T-1
SRT2-MD16T
SRT2-MD16T-1
SRT2-OD16T
SRT2-OD16T-1
SRT2-VID08S
SRT2-VID08S-1
SRT2-VOD08S
SRT2-VOD08S-1
SRT2-VID16ML
SRT2-VID16ML-1
SRT2-VOD16ML
SRT2-VOD16ML-1
SRT2-ROC08
SRT2-ROC16
SRT2-ROF08
SRT2-ROF16
SRT2-ID16P
SRT2-OD16P
SRT1-TID04S
SRT1-TKD04S
SRT1-XKD04S
SRT1-XID04S
SRT1-ID08S
SRT1-OD08S
SRT1-ND08S
SRT2-BIT
Power supply
Separate power
Local power
Local power
Local power
---
Network power
(See Note 1.)
---
Network power
Local power supply
(See Note 1.)
Note: 1. Network Power Supply:
Separate Power Supplies:
Local Power Supply:
Slaves that can receive power from a CompoBus/S flat cable.
Slaves requiring both communications and I/O power supplies
(Communications power can come from a CompoBus/S flat cable.)
Slaves requiring an external power supply
(Communications power cannot come from a CompoBus/S flat cable.)
2. SRT1 vs. SRT2: SRT1 supports only high-speed transmission (750 kbps at 100 m); SRT2 also supports high speed, as well as long distance transmission (500 m at 93.75 kbps).
Additional Information: For more details and specifications on this module, refer to manual W266 (CompoBus/S Operation Manual).
<6
Modules
CompoBus/S Products
3
Vertical-Style Modules
Model
SRT2-VID08S
SRT2-VID08S-1
SRT2-VID16ML
SRT2-VID16ML-1
SRT2-VOD08S
SRT2-VOD08S-1
SRT2-VOD16ML
SRT2-VOD16ML-1
Specifications
Connection with sensor connector (for cable connection), 8 transistor inputs, multiple power supplies
(NPN)
Connection with sensor connector (for cable connection), 8 transistor inputs, multiple power supplies
(PNP)
Connection with MIL connector, 16 transistor inputs, multiple power supplies (NPN)
Connection with MIL connector, 16 transistor inputs, multiple power supplies (PNP)
Connection with sensor connector (for cable connection), 8 transistor outputs, multiple power supplies (NPN)
Connection with sensor connector (for cable connection), 8 transistor outputs, multiple power supplies (PNP)
Connection with MIL connector, 16 transistor outputs, multiple power supplies (NPN)
Connection with MIL connector, 16 transistor outputs, multiple power supplies (PNP)
Note: All models are compatible with both High-speed and Long-distance Communications Modes.
3
Mounting Brackets for Vertical-Style Modules
Model
SRT2-ATT01
SRT2-ATT02
Description side-mounting bracket surface-mounting bracket
3
Analog Input/Output Modules
Model
SRT2-AD04
SRT2-DA02
Specifications
4 analog inputs (switchable between 4, 3, 2, and 1 points), network power supply
2 analog outputs (switchable between 2 and 1 points), network power supply
Note: Both models are compatible with both High-speed and Long-distance Communications Modes.
3
I/O Link Module for CPM1A/CPM2A
Model
CPM1A-SRT21
Specifications
8 inputs, 8 outputs, data exchange with CPM1A/CPM2A CPUs
Note: This model is compatible with both High-speed and Long-distance Communications Modes.
<7
Modules
CompoBus/S Products
3
Communications Cables
Note: Manufactured by Weidmüller.
Relevant Slaves: Vertical-Style Modules (Connector Terminals)
Model
BL3.5/6F (Product No. 160668)
Description
Communications cables, communications power supply and I/O power supply connectors
3
Connectors
Model
Branch Connector SCN1-TH4
Extension Connector
Connector Terminator
Terminal-block Terminator
SCN1-TH4E
SCN1-TH4T
SRS1-T
Description
Use this connector to create a branch line from the main line.
(Used with Omron Flat Cable only.)
Use this connector to extend the Omron Flat Cable.
This connector has a built-in terminator.
(Used with Omron Flat Cable only.)
This terminal block has a built-in terminator.
(Can be used with VCTF cable and Omron Flat Cable.)
3
MIL Connectors
Note: Related Slaves: Connector Terminals with MIL Connectors
Model
XG4M-2030-T
Description
MIL Connector
3
Sensor Connectors for SRT1-
=
D08S and SRT2-V
=
D08S
Model
XS8A-0441
XS8A-0442
Marking
XS8-1
XS8-2
Applicable wire size
0.3 to 0.5 mm 2
0.14 to 0.2 mm 2
Note: Related Slaves: Connector Terminals with Sensor Connectors, Remote Terminals with Connector Output Transistors, Sensor Terminals
<8
Modules
Communications Networks
Communications Modules
The following tables provide an overview and specifications for Omron’s major networks for CS1 Series Controllers.
Note: SYSLINK and Profibus-DP products are released and under continual development.
3
Overview
Level
Information t k
Network
Ethernet
Functions
Host computer to PLC
PLC to PLC
Host computer to CPU memory card
Communications
FTP server
Socket services (TCP/IP/UDP/IP)
Controller Link
UNIX computer or other socket service to PLC
Computers connected FINS messages
Control t k
Device networks
Controller Link
PC Link
DeviceNet
(CompoBus/D)
DeviceNet
(CompoBus/D)
CompoBus/S
PLC
PLC to PLC
PLC to PLC
PLC to PLC
PLC to components
( )
Data links (offsets and automatic setting)
FINS messages
Data links (offsets and automatic setting)
Simple data links
FINS messages on open network
HIgh-capacity remote I/O on open network
(fixed or user allocations)
High-speed remote I/O with OMRON network device (fixed allocations).
Module/Board
Ethernet Module;
St d d 3 d t (NSB)
Controller Link Support
Controller Link Module
Controller Link Module
PC Link Module
DeviceNet Master Module and Configurator
DeviceNet Master Module and Configurator
CompoBus/S Master
Module
3
Communications Specifications
Network Ethernet Controller Link
Commui ti
Messages Yes
Data links —
Remote I/O —
Maximum speed 10 Mbps
Total distance
Maximum nodes
Communications media
Data link capacity
(for network)
Remote I/O capacity
2.5 km
100
Coax
STP, UTP, fiber-optic
—
—
PC Link
Yes
Yes
-
2 Mbps
Comm cycle:
Approx. 34 ms (Wired:
32 nodes, 2-Kbits +
2-Kword data links)
Twisted-pair: 1 km
(at 500 bps)
Fiber-optic: 20 km
32
Special twisted-pair cable or fiber-optic cable
32,000 words
—
Yes
-
128 Kbps
500 m
32
Twisted-pair cable or fiber-optic cable
64 words
DeviceNet
(CompoBus/D)
Yes
—
Yes
500 Kbps
Comm cycle:
Approx. 5 ms
(128 inputs and
128 outputs)
500 m (at 125 bps)
63 (64 total)
Special DeviceNet cable
—
— —
Supporting PLCs CS1 Series,
CVM1,
CV Series,
C200HX/HG/HE
CS1 Series, CVM1,
CV Series,
C200HX/HG/HE
(Fiber-optic: CS1 only)
CS1 Series,
C200HX/HG/HE,
C200H, C200HS,
C1000H, C2000H
4,800 pts (with
Configurator)
1,600 pts (without
Configurator)
CS1 Series, CVM1,
CV Series,
C200HX/HG/HE,
CQM1 (with I/O Link)
CompoBus/S
—
—
Yes
750 Kbps
Comm cycle:
Approx. 1 ms
(128 inputs and
128 outputs)
Trunk line: 100 m or up to 500 m
32
2-core VCTF cable, special flat cable
—
256 pts
CS1 Series,
C200HX/HG/HE,
CQM1, SRM1
<9
Communications Modules
Modules
SYSMAC BUS Remote I/O Master Modules
Ideal For Distribution of I/O at Long Distances from the CPU
The SYSMAC BUS Remote I/O system is ideal for distribution of I/O and connection with other devices at long distances from the CPU. Multiple remote I/O systems can be connected to a single CPU allowing maximum configuration flexibility.
A SYSMAC BUS Remote I/O system consists of a Remote
Master and one or more Remote Slave modules. Both small and large rack-style I/O can be mixed in the same remote I/O system. Remote terminal blocks allow for distribution of
8-point and 16-point I/O blocks in a wired remote I/O system.
Stand-alone fiber-optic I/O modules allow distribution of
8-point I/O blocks in a fiber-optic remote I/O system. I/O Link modules allow connection of a PLC to a fiber-optic remote I/O system. Special link adapters are available for extended distances and mixing media types.
Note: Basic connector(s) included. For dedicated OMRON cables, connectors and accessories, refer to manual W120.
C200H-RM001-PV1
(Fiber-optic Master)
C200H-RM201
(Wired Master)
3
Features
•
High-speed distribution with twisted pair wiring or select fiber-optic cable versions.
•
Variety of I/O styles and types in a remote I/O system.
•
RS-485 communications at 187.5 Kbps.
•
Connect C200H I/O, C500 I/O, G7 remote I/O terminals, programmable terminals.
•
Support hundreds of remote I/O signals at a maximum distance of 200 meters.
3
System Configuration
Fiber-optic Remote I/O System
Note: Maximum of two modules can be mounted.
C200H-RM001-PV1
Fiber-optic Remote I/O Master Module
C200H-RT001-P/RT002-P
Remote I/O Slave Module
Slave Rack
Wired Remote I/O System
Note: Maximum of two modules can be mounted.
C200H-RM201
Wired Remote I/O Master Module
C200H-RT201/RT202
Remote I/O Slave Module
Slave Rack
Fiber- optic
Cable
C200H-BC
PP
1-V2
Backplane
C500 Slave Rack
C500-RT001/002-(P)V1
Remote I/O Slave Module
(Count one
C500 Module as two C200H
Modules.)
5 Slave Racks max., C500
Slave Rack counted as 2.
Twisted-pair cable
C200H-BC
PP
1-V2
Backplane
C500 Slave Rack
(Count one C500
Module as two
C200H Modules.)
5 Slave Racks max., C500
Slave Rack counted as 2.
C500-RT201
Remote I/O Slave Module
G7TC I/O
Block
G71 I/O Interface
32 Module
(32 words) max.
I/O Link Module
Terminator
(See note below.)
G72C I/O Terminal
To other Slaves (Operator Interface Terminals,
I/O Link Modules, and other devices).
Fiber-optic I/O
Module
Repeater
Module
Fiber-optic I/O
Module
Note: 64 modules (32 words) max.; repeater module not counted and required for more than 32 modules.
Additional Information: For more details and specifications on any of these modules, refer to manual W136 (Fiber-optic Remote I/O) and W120
( SYSMAC BUS Fiber and Wired Remote I/O).
<:
Modules
I/O Module Connectors
I/O Wiring Accessories
A B C
3
C200H and CS1 I/O Module Connectors
Discrete I/O modules are available in a number of voltages, and densities. There are terminal block, and connector types.
Connector-style high-density I/O modules with 32, 64 or 96 discrete I/O points per module include solder connectors with the module.
Optional wiring methods are available using Omron’s I/O blocks, screw terminal, crimp and ribbon connectors, as well as, with pre-terminated cables. These versatile high-density configuration options minimize rack space and wiring time.
The Omron I/O Blocks provide single-point isolation and up to
5 A current capacity per point. Replaceable relays and solidstate plug-in modules allow easy maintenance.
There are six styles of discrete I/O modules in the C200H and
CS1 group. The profiles of each are shown here.
Modules include the appropriate connectors. Replacement connectors and terminal blocks for each style are given here.
E
F
D E
3
Specifications
Style type
(See graphic above.)
A
B
C
I/O module
C200H Basic I/O
C200H Basic I/O
D
F
CS1-Series Basic I/O Modules
I/O points
5 pts, 8 pts
12 pts, 16 pts
32 pts
96 pts
Connector type
Screw terminal
Screw terminal
Solder, 40-pin
Crimp, 40-pin
Ribbon-crimp, 40-pin
Solder, right angle
Crimp, right angle
Solder, 24-pin
Crimp, 24-pin
Ribbon-crimp, 24-pin
Solder, 56-pin
Crimp, 56-pin
Ribbon-crimp, 56-pin
Part number
4571022-4, PTC-2103
4571023-4, PTC-219
C500-CE401
C500-CE402
C500-CE403
C500-CE404
C500-CE405
C500-CE241
C500-CE242
C500-CE243
C500-CE561
C500-CE562
C500-CE563
<;
I/O Wiring Accessories
Modules
XW2Z Cables with XW2B Screw Terminal Blocks
3
XW2B Terminal Wiring Blocks
XW2B-20G5
XW2B-40G5
XW2B-60G5 XW2B-20G4
XW2B-40G4
XW2B-60G4
XW2B-40G5-T XW2B-20G5-D
3
Specifications
Part number
XW2B-20G4
XW2B-20G5
XW2B-40G5-T
XW2B-20G5-D
XW2B-40G4
XW2B-40G5
XW2B-60G4
XW2B-60G5
XW2Z-
=
00A
XW2Z-
=
00B
XW2Z-
===
H-
=
Description
20-point terminal w/M2.4 screws
20-point terminal w/M3.5 screws
40-point terminal w/M3.5 screws (Has two connectors; same as using two
XW2B-20G5s)
20-point terminal w/M3.5 screws
(Daisy chain application)
40-point terminal w/M2.4 screws
40-point terminal w/M3.5 screws
60-point terminal w/M3 screws
Compatible PLC I/O Module (Category)
2 hi h D it I/O M d l
60-point terminal w/M3.5screws
Connecting cable
Connecting cable
Connecting cable
Note: For Connecting Cable part numbers, refer to the pages that follow.
CS1W-ID291, CS1W-OD291, CS1W-OD292, CS1W-MD291,
CS1W-MD292, CS1-Series 96-pt. Basic I/O modules
CS1W-ID291, CS1W-OD291, CS1W-OD292, CS1W-MD291,
CS1W-MD292, CS1-Series 96-pt. Basic I/O modules
C200H 32-point High Density I/O Modules
C200H Group 2 High Density I/O Modules
CS1 Series 96-point Basic I/O Modules
<<
Modules
I/O Wiring Accessories
XW2Z Cables with XW2B Screw Terminal Blocks
3
32-point High-density Modules
Configuration
I/O Module
C200H-ID215
C200H-OD215
C200H-MD115
C200H-MD215
C200H-MD501
C200H-ID501
C200H-OD501
Connecting Cables
XW2Z-100A
XW2Z-200A
XW2Z-300A
XW2Z-500A
Note: The odd numbers on the screw terminals correspond to column A in the PLC module.
The even numbers correspond to column B in the PLC module.
Screw Terminals
XW2B-20G4
XW2B-20G5
XW2B-40G5-T (same as using two XW2B-20G5 Terminals)
XW2B-20G5-D
3
32-point and 64-point Group-2 High-density Modules
Configuration
I/O Module
C200H-ID216
C200H-ID217
C200H-OD218
C200H-OD219
(For 32 pt use one screw terminal)
Note: The odd numbers on the screw terminals correspond to column A in the PLC module.
The even numbers correspond to column B in the PLC module.
Connecting Cables
XW2Z-100B
XW2Z-200B
XW2Z-300B
XW2Z-500B
Screw Terminals
XW2B-40G4
XW2B-40G5
433
I/O Wiring Accessories
Modules
XW2Z Cables with XW2B Terminal Wiring Blocks
3
XW2Z Cables to Connect C200H 32-point I/O Modules and
32-/64-point Group-2 High-density I/O Modules
Part number: 1 to 1 connections Cable length Module type
XW2Z-100-B
XW2Z-200-B
XW2Z-300-B
XW2Z-500-B
1 m (3.28 ft)
2 m (6.56 ft)
3 m (9.84 ft)
5 m (16.40 ft)
C200H 32-pt and 64-pt Group-2
Hi h D i I/O M d l
3
XW2Z-
PPP
H-
P
for 96-point CS1 PLC I/O Modules (Connector Type)
XW2Z--
P
00H--1
A
XW2Z--
P
00H--2
A
B
Part number: 1 to 1 connections with XW2B-60G
=
XW2Z-050H-1
XW2Z--
P
00H--3
A
B
C
Cable length A (above)
0.5 m (1.64 ft)
XW2Z--700H-1
XW2Z--010H-1
Part number: 1 to 2 connections with XW2B-40G
= and XW2B-20G
=
7 m (22.97 ft)
10 m (32.81 ft)
Cable length A (above) Cable length B (above)
XW2Z--010H-2 10 m (32.81 ft) 10 m (32.81 ft)
434
Modules
I/O Wiring Accessories
XW2Z Cables with XW2B Screw Terminal Blocks
3
XW2Z-
PPP
H-
P
for 96-point CS1 PLC I/O Modules (Connector Type) — continued
Part number: 1 to 3 connections for XW2B-20G
=
Cable length A
(Refer to A in the figure on the previous page.)
Cable length B
(Refer to B in the figure on the previous page.)
Cable length C
(Refer to C in the figure on the previous page.)
XW2Z-010H-3 10 m (32.81) 9.75 m (31.99 ft) 10 m (32.81)
3
Combinations of Omron CS1-Series High-density I/O Modules and Screw Terminal Blocks
PLC I/O module
CS1W-ID291,
CS1W-OD291, CS1W-OD292
CS1W-MD291, CS1W-MD292
CS1W-ID291,
CS1W-OD291, CS1W-OD292
CS1W-MD291, CS1W-MD292
CS1W-ID291,
CS1W-OD291, CS1W-OD292
CS1W-MD291, CS1W-MD292
I/O points
96 points
96 points
96 points
Terminal blocks
Two XW2B-60G
P terminal blocks
Two XW2B-40G4 + XW2B-20G4 or two XW2B-40G5 + XW2B-20G5 terminal blocks
Six XW2B-20G4 or six XW2B--20G5 terminal blocks
Dedicated cable
Two XW2Z-
PPP
H-1 cables
Two XW2Z-
PPP
H-2 cables
Two XW2ZPPP H-3 cables
Note: For detailed information about connector pin-outs, refer to CS1 Operation Manual (W339), Appendix A.
435
I/O Wiring Accessories
Modules
Relay Input Blocks and Bases
Input Blocks connect to Omron’s high-density input modules or
G71 SYSMAC BUS or wired remote I/O stand-alone slaves. Using the Blocks with High-density Input Modules saves Rack space and reduces total system cost. The Block and Slave combination is a cost-effective distributed control system when dealing with a small number of input points at a given location. Both applications provide fully isolated input points.
•
Mix and match input modules, either AC or DC relay and SSR.
•
Blocks available with a wide variety of input voltages 12 VDC,
24 VDC, 110/120 VAC, and 220/240 VAC.
•
Modules are easily changed for flexibility and servicing.
•
Built-in surge suppressors and LED indicators.
•
Mounts easily on DIN Rail
All Remote I/O Blocks require a 24 VDC power supply. Omron recommends the S82K family of power supplies.
Removable
Relay Module
+
_
0 1 2 3
4 5 6 7 8 9 10 11 12 13 14
15
C0 C1 C2
C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13
C14 C15
G7TC-I
3
Specifications
Relay Input Bases without Relays
Part number
No. of points
Input voltage
Supply voltage
Internal circuit
Applicable Input Relay part numbers
P7TF-IS16-DC24V
16
User-selectable
24 VDC
NPN (neg. com.)
G7T-1122S-DC24V
G3TA-IDZR02S-DC5-24V
Relay Input Blocks with Relays Included
Part number
No. of points
Input voltage
Supply voltage
Internal circuit
Input Relay part number
G7TC-ID16-DC12V
16
12 VDC
12 VDC
NPN (neg. com.)
G7T-1122S-DC12V
P7TF-IS16-AC110/120V
16
User-selectable
24 VDC
NPN (neg. com.)
G7T-1122S-AC110/120V
G3TA-IAZR02S-AC100-240V
G7TC-ID16-DC24V
16
24 VDC
24 VDC
NPN (neg. com.)
G7T-1122S-DC24V
P7TF-IS16-AC220/240V
16
User-selectable
24 VDC
NPN (neg. com.)
G7T-1122S-AC220/240V
G3TA-IAZR02S-AC100-240V
G7TC-IA16-AC110/120V
16
110--120 VAC
24 VDC
NPN (neg. com.)
G7T-1122S-AC110/120V
Part number
No. of points
Input voltage
Supply voltage
Internal circuit
Input Relay part number
G7TC-IA16-AC220/240V
16
User-selectable
24 VDC
NPN (neg. com.)
G7T-1122S-DC24V
Relay Input Bases without Relays
Part number
No. of points
Input voltage
Supply voltage
Internal circuit
Applicable Input Relay part numbers
G70A-ZIM16-5-DC24V
16
User--selectable
110 VDC max., 240 VAC max. (See Note.)
NPN/PNP
G2R-1A3--SND-DC24V
G2R-13-SND-DC24V
G3R-IAZR1SN AC100-240
G3R-IDZR1SN DC12-24
G3R-IDZR1SN DC5
Note: Relay specifications can be found on the next page.
436
Modules
I/O Wiring Accessories
Relay Input Blocks and Bases
3
Input Relay Specifications
Part number
Input device
Input voltage
Input current
ON time
OFF time
G7T-1122S-DC12V
Relay
12 VDC
42 mA
15 ms
15 ms
Part number
Input device
Input voltage
Input current
ON time
OFF time
Part number
Input device
Input voltage
Input current
ON time
OFF time
G7T-1122S-AC220/240V
Relay
220-240 VAC
3.2-3.5 mA
15 ms
15 ms
G2R-1A3-SND-DC24V
Relay
230 VAC/24 VDC
3.1 mA/21.8 mA
15 ms max.
10 ms VAC/5 ms VDC
G7T-1122S-DC24V
Relay
24 VDC
21 mA
15 ms
15 ms
G7T-1122S-AC110/120V
Relay
110--120 VAC
6.4--7.0 mA
15 ms
15 ms
G3TA-IAZR02S-AC100/240V
Transistor SSR
100-240 VAC
5 mA
20 ms
20 ms
G3TA-IDZR02S-DC5-24V
Transistor SSR
5-24 VDC
5 mA
0.5 ms
0.5 ms
G2R-13-SND-DC24V
Relay
230 VAC/24 VDC
3.1 mA/21.8 mA
15 ms max.
10 ms VAC/5 ms VDC
Part number
Input device
Input voltage
Input current
ON time
OFF time
G3R-IAZR1SN AC100-240
Triac SSR
60 to 264 VAC
15 mA max.
20 ms max.
20 ms max.
G3R-IDZR1SN DC12-24
Transistor SSR
6.6 to 32 VDC
8 mA max.
0.1 ms max.
0.1 ms max.
G3R-IDZR1SN DC5
Transistor SSR
4 to 6 VDC
8 mA max.
0.1 ms max.
0.1 ms max.
437
3
16-point Module
Configuration
I/O Wiring Accessories
Modules
Relay Input Blocks and Bases
Input Module
C200H-ID212
C200H-IM212
Connecting Cables
G79-Y050C, 0.5 m
G79-Y100C, 1 m
G79-Y150C, 1.5 m
G79-Y200C, 2 m
G79-Y500C, 5 m
Input Blocks
G7TC-ID16
G7TC-IA16
P7TF-IS16
438
Modules
I/O Wiring Accessories
Relay Input Blocks and Bases
3
32-point High-density Modules
Configuration
Input Module
C200H-ID215
C200H-MD215 (Input side only)
Connecting Cables
G79-100C, 1 m
G79-150C, 1.5 m
G79-200C, 2 m
G79-300C, 3 m
G79-500C, 5 m
3
32-point and 64-point Group-2 High-density Modules
Configuration
Input Module
C200H-ID216
C200H-ID217
(For 32 pt module use two 16 input blocks)
Input Blocks
G7TC-ID16
G7TC-IA16
P7TF-IS16
Input Blocks
G7TC-ID16
G7TC-IA16
P7TF-IS16
Connecting Cables
G79-I100C-75, 1 m
G79-I150C-125, 1.5 m
G79-I200C-175, 2 m
G79-I300C-275, 3 m
G79-I500C-475, 5 m
439
I/O Wiring Accessories
Modules
Relay Output Blocks and Bases
Output blocks connect to Omron’s high-density output modules or G71 SYSMAC BUS or wired remote output stand-alone slaves. Using the blocks with highdensity output modules saves rack space and reduces total system cost. The block and slave combination is a cost-effective distributed control system when dealing with a small number of output points at a given location.
Both applications provide fully isolated output points with large switching capacities.
Features
•
8-point and 16-point blocks available.
•
Mix and match output modules, AC and DC relay or SSR isolated.
•
5-A switching capacity.
•
Modules are easily changed for flexibility and servicing.
•
Built-in surge suppressors and LED indicators.
•
Easy DIN-rail mounting.
AC OUT
Removable
Relay Module
AC OUT
Removable
Relay Module
AC OUT AC OUT AC OUT AC OUT
AC OUT AC OUT AC OUT
+
_
0 1 2 3 4 5 6
7
C0 C1 C2 C3 C4 C5 C6 C7
G7TC-OC08
AC OUT AC OUT AC OUT AC OUT
AC OUT AC OUT AC OUT AC OUT AC OUT AC OUT AC OUT AC OUT AC OUT AC OUT
AC OUT
+
_
0 1 2 3 4 5 6
7 8 9 10 11 12 13 14 15
C0 C1
C2 C3 C4 C5 C6 C7 C8 C9 C10 C11
C12 C13 C14 C15
G7TC-OC16
43:
Modules
I/O Wiring Accessories
Relay Output Blocks and Bases
3
Block and Base Specifications
Relay Output Bases without Relays
Part number
No. of points
Switching capacity
Current consumption
Internal circuit
Applicable relay part numbers
P7TF-OS16-DC12V
16
User-selected
80 mA, 12 VDC
NPN (pos. com.)
G7T-1112S-DC12V
G7T-1012S-DC12V
Part number
No. of points
Switching capacity
Current consumption
Internal circuit
Applicable relay part numbers
P7TF-OS16-1-DC24V
16
User-selected
80 mA, 24 VDC
PNP (neg. com.)
G7T-1112S-DC24V
G7T-1012S-DC24V
G3TA-OA202S-DC24V
G3TA-ODX02S-DC24V
G3TA-OD201S-DC24V
P7TF-OS08-DC12V
8
User-selected
40 mA, 12 VDC
NPN (pos. com.)
G7T-1112S-DC12V
G7T-1012S-DC12V
P7TF-OS08-DC24V
8
User-selected
40 mA, 12 VDC
NPN (pos. com.)
G7T-1112S-DC24V
G7T-1012S-DC24V
G3TA-OA202S-DC24V
G3TA-ODX02S-DC24V
G3TA-OD201S-DC24V
G70A-ZOC16-4-DC24V
16
User-selectable
24 VDC
PNP (-- common)
G2R-1-SND-DC24,
G2R-1-SND-DC12
G3R-OA202SZN DC5-24
G3R-ODX02SN DC5-24
G3R-OD201SN DC5-24
P7TF-OS16-DC24V
16
User-selected
80 mA, 24 VDC
NPN (pos. com.)
G7T-1112S-DC24V
G7T-1012S-DC24V
G3TA-OA202S-DC24V
G3TA-ODX02S-DC24V
G3TA-OD201S-DC24V
P7TF-OS08-1-DC24V
8
User-selected
40 mA, 12 VDC
PNP (neg. com.)
G7T-1112S-DC24V
G7T-1012S-DC24V
G3TA-OA202S-DC24V
G3TA-ODX02S-DC24V
G3TA-OD201S-DC24V
Part number
No. of points
Input voltage
Supply voltage
G70A-ZOC16-3-DC24V
16
User-selectable
24 VDC
Internal circuit NPN (+ common)
Applicable Input Relay part numbers G2R-1--SND-DC24,
G2R-1--SND-DC12
G3R-OA202SZN DC5-24
G3R-ODX02SN DC5-24
G3R-OD201SN DC5-24
Relay Output Blocks with Relays Installed
Part number
No. of points
Max. switching current
Max. switching voltage
Max. switching power
Current consumption
Internal circuit
Relay part number
G7TC-OC16-DC12V
16
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
752 mA, 12 VDC
NPN (pos. com.)
G7T-1112S-DC12V
Part number
No. of points
Max. switching current
Max. switching voltage
Max. switching power
Current consumption
Internal circuit
Relay part number
G7TC-OC08-DC24V
8
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
208 mA, 24 VDC
NPN (pos. com.)
G7T-1112S-DC24V
Note: Specifications can be found on the next page.
G7TC-OC16-DC24V
16
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
416 mA, 24 VDC
NPN (pos. com.)
G7T-1112S-DC24V
G7TC-OC08-1-DC24V
8
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
208 mA, 24 VDC
PNP (neg. com.)
G7T-1112S-DC24V
G7TC-OC16-1-DC24V
16
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
416 mA, 24 VDC
PNP (neg. com.)
G7T-1112S-DC24V
43;
I/O Wiring Accessories
Modules
Relay Output Blocks and Bases
Relay Output Blocks with Relays Installed, Relay Pulling Tool Included
Part number
No. of points
Max. switching current
Max. switching voltage
G70D-SOC16 DC24
16
5 A
250 VAC, 30 VDC
G70D-SOC16-1DC24
16
5 A
250 VAC, 30 VDC
Max. switching power
Current consumption
Internal circuit
Relay part number
1,250 VA, 150 W
200 mW
NPN (+ common)
G6D-1A DC24V
1,250 VA, 150 W
200 mW
PNP (-- common)
G6D-1A DC24V
G70D-FOM16
16
100
µ
A to 0.3 A
3 to 264 VAC,
3 to 125 VDC
—
—
NPN (+ common)
G3DZ-2R6PL DC24V
G70D-FOM16-1 DC24
16
100
µ
A to 0.3 A
3 to 264 VAC,
3 to 125 VDC
—
—
PNP (-- common)
G3DZ-2R6PL DC24V
Relay Output Blocks with Relays Installed
Part number
No. of points
Max. switching current
Max. switching voltage
G70D-VSOC16
16
5 A
250 VAC, 30 VDC
Max. switching power
Power consumption
Internal circuit
Relay part number
1,250 VA, 150 W
200 mW
NPN (+ common)
G6D-1A DC24V
G70D-VFOM16
16
100
µ
A to 0.3 A
3 to 264 VAC,
3 to 125 VDC
—
—
NPN (+ common)
G3DZ-2R6PL DC24V
43<
Part number
Output type
Input voltage
Max. switching current
Max. switching voltage
Max. switching power
ON time
OFF time
Part number
Output type
Input voltage
Load current
Load voltage
ON time
OFF time
Part number
Output type
Input voltage
Load voltage
Load current
ON time
OFF time
Part number
Output type
Input voltage
Max. switching current
Max. switching voltage
Max. switching power
ON time
OFF time
Part number
Output type
Input voltage
Load current
Load voltage
ON time
OFF time
Modules
I/O Wiring Accessories
Relay Output Blocks and Bases
3
Output Relay Specifications
Part number
Output type
Input voltage
Max. switching current
Max. switching voltage
Max. switching power
ON time
OFF time
G7T-1112S-DC12V
NO Relay
12 VDC
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
15 ms
15 ms
G7T-1012S-DC12V
NC Relay
12 VDC
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
15 ms
15 ms
G3TA-ODX02S-DC24V
Transistor SSR
24 VDC
2 A
4-60 VDC
0.5 ms
2 ms
G7T-1112S-DC24V
NO Relay
24 VDC
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
15 ms
15 ms
G7T-1012S-DC24V
NC Relay
24 VDC
5 A
250 VAC, 125 VDC
12 W, DC; 440 VA, AC
15 ms
15 ms
G3TA-OD201S-DC24V
Transistor SSR
24 VDC
40 to 200 VDC, 1 A
1 A, 40 to 200 VDC
2 ms
2 ms
G3TA-OA202SZ-DC24V
Triac SSR
24 VDC
2 A
75 to 264 VDC
1/2 of power supply cycle + 1 ms
1/2 of power supply cycle + 1 ms
G2R-1-SND-DC24
Relay
24 VDC
10 A
380 VAC, 125 VDC
2500 VA, 300 W
15 ms max.
5 ms max.
G3R-OA202SZN DC5-24
Triac SSR
5-24 VDC
0.05 to 2 A
G3R-ODX02SN DC5-24
Transistor SSR
5-24 VDC
0.01 to 2 A
75 to 264 VAC 4 to 60 VDC
1/2 of load power supply cycle + 1 ms 1 ms max.
1/2 of load power supply cycle + 1 ms 2 ms max.
G2R-1-SND-DC12
Relay
12 VDC
10 A
380 VAC, 125 VDC
2500 VA, 300 W
15 ms max.
5 ms max.
G3R-OD201SN DC5-24
Transistor SSR
5-24 VDC
0.01 to 1.5 A
4 to 200 VDC
1 ms max.
2 ms max.
443
3
16-point Modules
Configuration
I/O Wiring Accessories
Modules
Relay Output Blocks and Bases
Output Module
C200H-OC225
C200H-OD212
Connecting Cable
G79-Y050C, 0.5 m
G79-Y100C, 1.0 m
G79-Y150C, 1.5 m
G79-Y200C, 2.0 m
G79-Y500C, 5.0 m
3
32-point Modules
Configuration
Output Blocks
G7TC-OC16
P7TF-OS16
Output Module
C200H-MD115 (Output side only)
C200H-MD215 (Output side only)
C200H-OD215
Connecting Cables
G79-100C, 1 m
G79-150C, 1.5 m
G79-200C, 2 m
G79-300C, 3 m
G79-500C, 5 m
Output Blocks
G7TC-OC16
P7TF-OS16
444
Modules
I/O Wiring Accessories
Relay Output Blocks and Bases
3
32-point Group-2 High-density Modules
Configuration
Output Module
C200H-OD218
Connecting Cable
G79-O100C-75
G79-O150C-125
G79-O200C-175
G79-O300C-275
G79-O500C-475
3
64-point Group-2 High-density Modules
Configuration
Output Module
C200H-OD219
Output Blocks
G7TC-OC16
P7TF-OS16
Output Blocks
G7TC-OC16
P7TF-OS16 Connecting Cable
G79-O100C-75
G79-O150C-125
G79-O200C-175
G79-O300C-275
G79-O500C-475
445
I/O Wiring Accessories
Modules
Relay Output Blocks and Bases
3
Connecting Cables for C200H Basic I/O, 32-point High-density I/O, and
32-/64-point Group-2 High-density I/O Modules
Item crimp hook one connector two connectors
Length
1 m (3.28 ft)
1.5 m (4.92 ft)
2 m (6.56 ft)
3 m (9.84 ft)
5 m (16.40 ft)
1 m (3.28 ft)
1.5 m (4.92 ft)
2 m (6.56 ft)
3 m (9.84 ft)
5 m (16.40 ft)
1 m (3.28 ft) + 0.75 m (2.46 ft)
1.5 m (4.92 ft) + 1.25 m (4.10 ft)
2 m (6.56 ft) + 1.75 m (5.74 ft)
3 m (9.84 ft) + 2.75 m (9.02 ft)
5 m (16.40 ft) + 4.75 m (15.58 ft)
Part number
G79--Y100C
G79--Y150C
G79--Y200C
G79--Y300C
G79--Y500C
G79--100C
G79--150C
G79--200C
G79--300C
G79--500C
G79--O100C--75
G79--O150C--125
G79--O200C--175
G79--O300C--275
G79--O500C--475
3
G79 Cables Used to Connect CS1W 96-point High-density I/O Modules to Relay Terminal Blocks G7TC, G70A, or G70D.
Connections that Apply to this List Are
:
••••
Input Blocks: G7TC-ID16, G7TC-IA16
••••
Output Blocks: G7TC-OC16, G70D-(V)SOC16, G70D-FOM16, G70A-ZOC16-3
••••
I/O Modules: CS1W-ID291, CS1W-OD29
=
, CS1W-MD29 =
Cable length (Refer to A below.)
1.5 m (4.92 ft)
2 m (6.56 ft)
3 m (9.84 ft)
Cable length (Refer to B below.)
1.25 m (4.10 ft)
1.75 m (5.74 ft)
2.75 (9.02 ft)
Cable length (Refer to C below.)
1 m (3.28 ft)
1.5 m (4.92 ft)
1.75 m (5.74 ft)
Cable part number
G79-150C-125-100
G79-200C-175-150
G79-300C-275-250
Configuration
CS1W 96-point High-density I/O Connector to Relay Terminal Wiring Block
B
A
C
Straight length
446
Modules
I/O Wiring Accessories
B7A Input/Output Module Accessories
3
Performance Specifications
Part number
I/O points
Transmission distance
Transmission delay
Internal current consumption
C200H-B7AI1 C200H-B7AO1 C200H-B7A12
B7A Interface Modules
C200H-B7A02
Group-2 B7A Interface Modules
16 points or
15 points and
1 error input
16 output points 32 input points or 30 input points and 2 error inputs
C200H-B7A21
32 output points 16 output points and 16 input points or
15 input points +
1 error input
500 m max. if power is supplied to the Interface Module and B7A
Link Terminal separately.
100 m max. if power is supplied to the Interface Module and B7A
Link Terminal from a single power supply.
19.2 ms typical, 31 ms max.
Standard:
500 m max. using separate power supplies.
100 m max. using a common power supply.
High-speed:
100 m max. using separate power supplies.
50 m max. using a common power supply.
C200H-B7A22
32 output points and 32 input points or
30 input points +
2 error inputs
If shielded cable is not used, the maximum transmission distance is 10 m regardless of whether a common or separate power supplies are used.
Standard: 19.2 ms typical, 31 ms max.
High-speed: 3 ms typical, 5 ms max. (See Note 1.)
5 VDC, 100 mA max.
(S N 2 )
Weight
12 to 24 VDC
±
10%
0.01 A min.
0.03 A min.
200 g max.
0.05 A min.
300 g max.
0.06 A min.
0.05 A min.
0.08 A min.
Note: 1. The transmission delay is changed by using the DIP switch.
2. The value of the external power supply does not include the value required by the B7A Link Terminal.
3
Connectable B7A Link Terminals
Input Terminals
Type
Screw terminals
Transmission delay
Printed circuit board models
Link terminal adapters
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Part number
B7A-T6
P
1
B7AS-T6
P
1
B7A-T6 P 6
B7AS-T6
P
6
B7A-T6D2
B7A-T6D7
B7A-T
P
E3
B7A-T
P
E8
Output Terminals
Type
Screw terminals
Description/transmission delay
Printed circuit board models
Link terminal adapters
Standard (19.2 ms)
High-speed (3 ms)
Standard (19.2 ms)
High-speed (3 ms)
Note: All of the available B7A Input and Output Terminals and Adapters are presented on the following pages.
Part number
B7A-R6
PP
1
B7AS-R6
PP
1
B7A-R6
PP
6
B7AS-R6
PP
6
B7A-R6A52
B7A-R6A57
B7A-R
P
A
P
3
B7A-R
P
A
P
8
447
I/O Wiring Accessories
Modules
B7A Input/Output Module Accessories
3
B7A I/O Link Terminals
Type
Screw terminals Input
Output
Description
10 pts NPN IN
16 pts NPN IN
16 pts PNP IN
16 pts PNP IN
10 pts NPN OUT, 0.1 A/point
-- Com 19.2 ms
±
Com 19.2 ms
-- Com 19.2 ms
-- Com 3 ms
±
Com 19.2 ms
±
Com 3 ms
±
Com 19.2 ms
±
Com 3 ms
±
Com 19.2 ms
±
Com 3 ms
+ Com 19.2 ms, HOLD
Part number
B7A-T10S1
B7A-T10S3
B7A-T6A1
B7A-T6A6
B7A-T6B1
B7A-T6B6
B7AS-T6B1
B7AS-T6B6
B7A-T6C1
B7A-T6C6
B7A-R10SC01
B7A-R6B11 + Com 19.2 ms, HOLD
+ Com 3 ms, HOLD B7A-R6B16
+ Com 19.2 ms, LOAD OFF B7A-R6B31
+ Com 3 ms, LOAD OFF
+ Com 19.2 ms, HOLD
B7A-R6B36
B7AS-R6B11
+ Com 3 ms, HOLD B7AS-R6B16
+ Com 19.2 ms, LOAD OFF B7AS-R6B31
+ Com 3 ms, LOAD OFF
+ Com 19.2 ms, HOLD
B7AS-R6B36
B7A-R6C11
+ Com 3 ms, HOLD B7A-R6C16
+ Com 19.2 ms, LOAD OFF B7A-R6C31
+ Com 3 ms, LOAD OFF B7A-R6C36
-- Com 19.2 ms, HOLD
-- Com 3 ms, HOLD
B7A-R6F11
B7A-R6F16
-- Com 19.2 ms, LOAD OFF B7A-R6F31
-- Com 3 ms, LOAD OFF B7A-R6F36
-- Com 19.2 ms, HOLD
-- Com 3 ms, HOLD
B7A-R6G11
B7A-R6G16
-- Com 19.2 ms, LOAD OFF B7A-R6G31
-- Com 3 ms, LOAD OFF B7A-R6G36
(This table continues on the next page.)
448
Modules
I/O Wiring Accessories
B7A Input/Output Module Accessories
3
B7A I/O Link Terminals (continued)
Type
Printed circuit board Input
Output
Link terminal adapters Input
Output
Description
10 pts TTL IN
16 pts TTL IN
10 pts NPN OUT
16 pts NPN OUT
16 NPN IN Connector
32 NPN IN Connector
16 NPN OUT Connector
32 NPN OUT Connector
32 OUT Connector for Mitsubishi
19.2 ms
19.2 ms
3 ms
19.2 ms, HOLD
Part number
B7A-T10M2
B7A-T6D2
B7A-T6D7
B7A-T10MC
19.2 ms, HOLD/LOAD OFF B7A-R6A52
3 ms, HOLD/LOAD OFF B7A-R6A57
19.2 ms
3 ms
19.2 ms
3 ms
19.2 ms Hold
B7A-T6E3
B7A-T6E8
B7A-T3E3
B7A-T3E8
B7A-R6A13
3 ms Hold
19.2 ms Load Off
3 ms Load OFF
19.2 ms Hold
3 ms Hold
19.2 ms Load Off
3 ms Load Off
19.2 ms Hold
B7A-R6A18
B7A-R6A33
B7A-R6A38
B7A-R3A13
B7A-R3A18
B7A-R3A33
B7A-R3A38
B7A-R3A38-M
3
Cables
The following Belden Cables can be used for B7A I/O Link Terminal connections to B7A I/O Modules.
Omron B7A system
B7A 2-wire
B7A 3-wire
Belden cable
9486
8770
449
P E R I P H E R A L H A R D W A R E A N D S O F T W A R E
Compolet and FINS Gateway Software . . . . . 118
NT631/31 Series Operator
Interface Terminals . . . . . . . . . . . . . . . . . . . 120
Motion Control . . . . . . . . . . . . . . . . . . . . . . 124
R88M-U AC Servo Motors and
R88D-U AC Servo Drives
XW2B Servo Terminal Blocks
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
Peripheral Hardware and Software
Compolet and FINS Gateway Software
Faster and Easier Development of PLC Communications with ActiveX Control
3
CS1 Series Compolet
C-Series Compolet and
CV Series Compolet
System Configuration
Microsoft Visual Basic
SYSMAC LINK
HostLink
Controller Link
Ethernet
Production information and instructions
Progress control
Data histories
Quality control
Daily report management
ActiveX Control
Compolet
Windows NT/95
Omron C-Series,
CV Series,
CS1 Series
Omron C-Series,
CV Series,
CS1 Series
Reduce Development Time for Custom-HMI Applications
Difficult, time-consuming communications programs can now be created far more easily. ActiveX Control directly manipulates
Omron PLC operations, eliminating the need for knowledge of FINS communications commands.
3
Features
Interface Functional area
Properties Communications with Omron Controllers
Accessing variable areas in Omron Controllers
Methods
CPU information
Omron Controller operating status
Omron Controller area information
Omron Controller error information
Accessing variable areas in Omron Controllers
Creating I/O tables
Force-setting/resetting bits
Executing FINS services
Function
Specifying addresses and displaying routing tables.
Accessing the following areas as arrays: DM, IR, SR, Timer, Counter,
HR, AR, LR, and EM.
Accessing model information and the time.
Dsiplaying operatinng status and changing operating modes.
Accessing program area sizes, DM Area word capacity, etc.
Clearing fatal and non-fatal errors or accessing error information as text strings.
Accessing continuous word contents and using it as text strings, number arrays, variants, etc.
Creaing I/O tables remotely.
Force-setting and force-resetting bits and clearing forced bit status.
Sending low-level FINS commands and reading the results.
44;
3
Operating Environment
* CS1 Series Compolet is also available.
Peripheral Hardware and Software
Compolet and FINS Gateway Software
Compolet Software
For C-Series Controllers
Omron C Compolet *
FINS Gateway
FINS Gateway Version 2
Runtime versions: Ethernet, SYSMAC LINK, Controller Link, Serial Communications
+
For CV Series Controllers
Omron CV Compolet
FINS Gateway Version 2
Runtime versions: Serial Communications only
Note: These are required to utilize Compolet’s FINS Gateway: Microsoft Visual Basic (the application development environment for ActiveX Control), an HTML browser for the online manual (the online manual is provided in HTML, so it can be viewed with Microsoft Internet Explorer).
3
Specifications
Computer
CPU (memory)
Operating System
SYSMAC LINK Support Board
ControllerLink Support Board
Ethernet Board
Supported networks
Required software
IBM PC/AT or compatible (x86 or better) Approx. 5 MB of memory is required for installation.
Pentium 133 MHz or faster (32 MB min.).
Microsoft Windows NT4.0 or Microsoft Windows 95.
OMRON 3G8F5-SLK21/SLK22. One board per computer.
OMRON 3G8F5-CLK11/CLK21. One board per computer.
Any commerial Ethernet board (NSB) for Windows NT/95.
SYSMAC LINK (FINS communications and data links), ControllerLink (FINS communications and data links), Ethernet (FINS communications), RS-232C serial communications,
CompoWay/F (RS-232C).
FINS Gateway for the network being used, and Microsoft Visual Basic.
Data Read Settings Window ActiveX Window Tool Box Window
Property Settings Window
Programming Window
44<
Peripheral Hardware and Software
NT631/31 Series Operator Interface Terminals
Supporting the CS1 Series with More Power than Ever Before
3
Bright Displays
The NT31 and NT631 Operator Interfaces use high resolution LCD with a cathode tube backlight for a bright, clear display.
The NT631 TFT screen technology provides superior brightness and sharpness for improved viewing at any angle.
NT31C
NT631C
3
Multiple-window Capability for More Efficient
Screen Application and Development
Up to two child windows can be displayed at the same time within an individual screen. The child windows can be opened or closed manually or by
PLC control from the window Control/Notify area.
Child windows can also be repositioned on the screen manually or by the PLC from the Window
Control/Notify area.
Additional Information: For more details on NT Series Operator Interface Terminals, refer to: SB NT631/NT31 (NT631/31 Operator Interface Brochure);
V043 (NT31/31C Operation Manual); V044 (NT631/631C Operation Manual); or V041 (NT Series Support Tool Users Manual).
453
Peripheral Hardware and Software
NT631/31 Series Operator Interface Terminals
3
Enhanced Functionality
Omron’s NT products have been enhanced by improved brightness, more programmable screen objects, improved connectivity, memory modules, and programming software that is easier to use.
3
Programming Console
Functionality on Operator
Interface Terminals
The same functionality as provided by the C200H-
PRO27-E Programming Console can be accessed on an Operator Interface screen. Write or read ladder diagrams in mnemonic form and perform other operations for convenient onsite maintenance.
Additional Information: For more details on NT Series Operator Interface Terminals, refer to: SB NT631/NT31 (NT631/31 Operator Interface Brochure);
V043 (NT31/31C Operation Manual); V044 (NT631/631C Operation Manual); or V053 (NT Series Support Tool Users Manual).
454
Peripheral Hardware and Software
NT631/31 Series Operator Interface Terminals
3
1:N NT Links for Operator Interface Terminals
•
Connect up to eight NT-Series Operator Interface Terminals to a CS1 Series serial port.
•
NT-Series Operator Interface Terminal communications are given a high priority by the CS1 CPU.
Omron CS1-series PLC
Connect up to 8 NT Terminals per port
RS-422A
NT631 NT631
NT31 NT31
CS1 Ports that support 1:N NT Links
•
CS1G/CS1H CPU Peripheral Port
•
CS1G/CS1H CPU Serial Port
•
CS1W-SCB21 (port 1 or 2)
•
CS1W-SCB41 (port 1 or 2)
•
CS1W-SCU21 (port 1 or 2)
NT631
The number of NT-Series Operator Interface Terminals that can be connected depends on the model of Serial
Communications Board and the model of CPU being used.
NT31 and NT631 communication ports can be configured to RS-422A.
455
Peripheral Hardware and Software
NT631/31 Series Operator Interface Models
Product
NT631 Operator Interface
(S N t )
Specifications
10.5-inch TFT color touch screen
11.3-inch STN color touch screen
Electroluminescent
NT31 Operator Interface
(S N t )
5.7-inch STN color touch screen
STN black and white
Body color: Beige
Body color: Black
Body color: Beige
Body color: Black
Body color: Beige
Body color: Black
Body color: Beige
Body color: Black
Body color: Beige
Body color: Black
Model
NT631C-ST151-EV1
NT631C-ST151B-EV1
NT631C-ST141-EV1
NT631C-ST141B-EV1
NT631-ST211-EV1
NT631-ST211B-EV1
NT31C-ST141-EV1
NT31C-ST141B-EV1
NT31-ST121-EV1
NT31-ST121B-EV1
(See Note.)
Cables
Options
Memory Unit for screen transfers For both NT631 and NT31 NT-MF261
Screen transfers Programming Cable
Printer To print hard copies of screens
Omron NT to PLC Communications For NT631C/NT631
For NT31C/NT31
For NT31C/NT31 (5 sheets) Non-reflective Protective Sheets
(display area only)
Non-reflective Protective Sheets
(display area only)
Chemical-resistant Cover
)
Bar Code Reader
RS-232C/RS-422 Converter
For NT631C/NT631
For NT31C/NT31
For NT631C-ST151 P
For NT631C-ST141
P
For NT31C/31
Refer to the Bar Code Reader catalog.
Used to allow multiple 1:N
NT Link connections
C200H-CN229
NT-CNT121
NT631C-CN
NT31C-CN
NT31C-CFL01
V520-RH21-6
NT-AL001
PP
PP
NT30-KBA04
For NT631C/NT631 (5 sheets) NT610-KBA04
NT625-KBA01
NT30-KBA01
NT631C-CFL01
NT631C-CFL02
0-EU
0-EU
Note: Models without “EV1” can support the new features described in this section by installing the new system program from the
“EV3” Support Software. High-quality fonts and Memory Unit functions, however, cannot be used.
Additional Information: For more details on NT Series Operator Interface Terminals, refer to: SB NT 631/NT31 (NT631/31 Operator Interface Brochure);
V043 (NT31/31C Operation Manual); V044 (NT631/631C Operation Manual); or V041 (NT Series Support Tool Users Manual).
456
Peripheral Hardware and Software
Motion Control:
R88M-U AC Servomotors and R88D-U AC Servo Drives
Powerful Functions in a Compact Design for High-speed, High-precision Control
3
AC Servo Drives
•
High-speed response of 250 Hz servo frequency to reduce positioning time.
•
Auto-tuning automatically adjusts the control system gain.
•
Read/write parameters via personal computer connection. Display current, speed, and I/O signals in graphic form to easily confirm operation.
3
AC Servo Motors
•
Speed control range of 5000:1 for smooth low-speed operation.
•
Low rotor inertia design yields a high power rate.
•
Motors available with Incremental or absolute encoders with capacities from 30 W to 750 W.
•
Maximum rotational speed of 4,500 rpm shortens positioning time and improves production.
3
System Configuration
C200H or CS1W
Motion Control Module
Operation signals
Feedback pulses
Analog command voltages
Feedback pulses
R88D-UA
AC Servo Drive
(analog inputs and power supply included)
R88M-U
AC Servo Motor
(30 to 750 W with incremental/absolute encoder)
Note: Motors with absolute encoders can be used with the CV500-MC221/MC421 Motion Control Modules.
457
CVM1 Series or CV series
Programmable
Controller
+
C500-NC113/NC211
Position
Control Module
CS1 Series or
C200H Alpha
Series
Programmable
Controller
+
C200HW-
NC113/NC213/413
Position Control
Module
Pulse string signals
Operation signals
Feedback pulses
R88D-UP
AC Servo Driver
(pulse string inputs and power supply included)
R88M-U
AC Servo Motor
(30 to 750 W with incremental encoder)
Peripheral Hardware and Software
Motion Control: XW2B Servo Terminal Blocks
3
Combinations of Servo Terminal Blocks, Servo Drives, and Position Control Modules
Position Control Modules Position Control
Module Connecting
Cables
Servo Terminal
Modules
C200HW-NC113 (1 axis)
XW2ZPPP J-A6 XW2B-20J6-1B Servo Drive
Connecting Cables
Servo Drives
Position Control Modules Position Control
Module Connecting
Cables
Servo Terminal
Modules
U-series Connecting
Cables
XW2Z-
PPP
J-B1
U-series
Servo Drives
R88D-UP
PPP
C200HW-NC213 (2 axes)
C200HW-NC413 (4 axes)
XW2Z-
PPP
J-A7 XW2B-40J6-2B
Additional Information: For more details, refer to Manual I501 (Analog Control); I502 (Pulse Control); and, Catalog GC SMD1.
458
459
I N S T R U C T I O N S E T
Sequence Input . . . . . . . . . . . . . . . . . . . . . . 129
Sequence Output . . . . . . . . . . . . . . . . . . . . . 130
Sequence Control . . . . . . . . . . . . . . . . . . . . 130
Timer and Counter . . . . . . . . . . . . . . . . . . . . 131
Symbol Comparison . . . . . . . . . . . . . . . . . . 132
Data Movement . . . . . . . . . . . . . . . . . . . . . . 133
Data Shift . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Increment/Decrement . . . . . . . . . . . . . . . . . 134
Symbol Math . . . . . . . . . . . . . . . . . . . . . . . . 135
Conversion . . . . . . . . . . . . . . . . . . . . . . . . . 136
Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Special Math . . . . . . . . . . . . . . . . . . . . . . . . 137
Floating-point Math . . . . . . . . . . . . . . . . . . . 138
Table Data Processing . . . . . . . . . . . . . . . . . 139
Data Control . . . . . . . . . . . . . . . . . . . . . . . . 139
Subroutine . . . . . . . . . . . . . . . . . . . . . . . . . 139
Interrupt Control . . . . . . . . . . . . . . . . . . . . . 140
Step Instructions . . . . . . . . . . . . . . . . . . . . . 140
Basic I/O Module . . . . . . . . . . . . . . . . . . . . . 140
Serial Communications . . . . . . . . . . . . . . . . 140
Network . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
File Memory . . . . . . . . . . . . . . . . . . . . . . . . 141
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Debugging . . . . . . . . . . . . . . . . . . . . . . . . . 141
Failure Diagnosis . . . . . . . . . . . . . . . . . . . . . 142
System Instructions . . . . . . . . . . . . . . . . . . 142
Block Programming . . . . . . . . . . . . . . . . . . . 142
Text String Processing . . . . . . . . . . . . . . . . . 144
Task Control . . . . . . . . . . . . . . . . . . . . . . . . 144
System Overview
CPU Overview
Basic System Configuration
I/O Types and Allocations
Modules
Peripheral Hardware and Software
Instruction Set
Ordering Guide
Reference Information
45;
Name
LOAD
LOAD NOT
AND
AND NOT
OR
OR NOT
AND LOAD
OR LOAD
AND LD
OR LD
NOT NOT
CONDITION ON UP
CONDITION OFF DOWN
BIT TEST LD TST
Mnemonic Function code
LD ---
LD NOT ---
AND ---
AND NOT ---
OR
OR NOT
---
---
---
---
520
521
522
350
BIT TEST NOT LD TSTN 351
BIT TEST AND TST 350
BIT TEST NOT AND TSTN 351
BIT TEST OR TST 350
BIT TEST NOT OR TSTN 351
Instruction Set
Sequence Input Instructions
Function
Indicates a logical start and creates an ON/OFF execution condition based on the ON/OFF status of the specified operand bit.
Indicates a logical start and creates an ON/OFF execution condition based on the reverse of the ON/OFF status of the specified operand bit.
Takes a logical AND of the status of the specified operand bit and the current execution condition.
Reverses the status of the specified operand bit and takes a logical AND with the current execution condition.
Takes a logical OR of the ON/OFF status of the specified operand bit and the current execution condition.
Reverses the status of the specified bit and takes a logical OR with the current execution condition.
Takes a logical AND between logic blocks.
Takes a logical OR between logic blocks.
Reverses the execution condition.
UP(521) turns ON the execution condition for one cycle when the execution condition goes from OFF to ON.
DOWN(522) turns ON the execution condition for one cycle when the execution condition goes from ON to OFF.
LD TST(350), AND TST(350), and OR TST(350) are used in the program like LD, AND, and
OR; the execution condition is ON when the specified bit in the specified word is ON and
OFF when the bit is OFF.
LD TSTN(351), AND TSTN(351), and OR TSTN(351) are used in the program like LD NOT,
AND NOT, and OR NOT; the execution condition is OFF when the specified bit in the specified word is ON and ON when the bit is OFF.
LD TST(350), AND TST(350), and OR TST(350) are used in the program like LD, AND, and
OR; the execution condition is ON when the specified bit in the specified word is ON and
OFF when the bit is OFF.
LD TSTN(351), AND TSTN(351), and OR TSTN(351) are used in the program like LD NOT,
AND NOT, and OR NOT; the execution condition is OFF when the specified bit in the specified word is ON and ON when the bit is OFF.
LD TST(350), AND TST(350), and OR TST(350) are used in the program like LD, AND, and
OR; the execution condition is ON when the specified bit in the specified word is ON and
OFF when the bit is OFF.
LD TSTN(351), AND TSTN(351), and OR TSTN(351) are used in the program like LD NOT,
AND NOT, and OR NOT; the execution condition is OFF when the specified bit in the specified word is ON and ON when the bit is OFF.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
45<
Instruction Set
Sequence Output Instructions
Name
OUTPUT
OUTPUT NOT
Mnemonic Function code
OUT ---
OUT NOT ---
KEEP
DIFFERENTIATE
UP
DIFFERENTIATE
DOWN
SET
RESET
MULTIPLE BIT
SET
MULTIPLE BIT
RESET
KEEP
DIFU
DIFD
SET
RSET
SETA
RSTA
011
013
014
---
---
530
531
Function
Outputs the result (execution condition) of the logical processing to the specified bit.
Reverses the result (execution condition) of the logical processing, and outputs it to the specified bit.
Operates as a latching relay.
DIFU(013) turns the designated bit ON for one cycle when the execution condition goes from
OFF to ON (rising edge).
DIFD(014) turns the designated bit ON for one cycle when the execution condition goes from
ON to OFF (falling edge).
SET turns the operand bit ON when the execution condition is ON.
RSET turns the operand bit OFF when the execution condition is ON.
SETA(530) turns ON the specified number of consecutive bits.
RSTA(531) turns OFF the specified number of consecutive bits.
Sequence Control Instructions
Name
END
Mnemonic Function code
END 001
NO OPERATION NOP
INTERLOCK IL
ILC INTERLOCK
CLEAR
JUMP JMP
JUMP END
CONDITIONAL
JUMP
JME
CJP
CONDITIONAL
JUMP
CJPN
MULTIPLE JUMP JMP0
MULTIPLE JUMP
END
FOR-NEXT
LOOPS
BREAK LOOP
JME0
FOR
BREAK
FOR-NEXT
LOOPS
NEXT
516
512
514
513
000
002
003
004
005
510
511
515
Function
Indicates the end of a program.
END(001) completes the execution of a program for that cycle. No instructions written after
END(001) will be executed. Execution proceeds to the program with the next task number.
When the program being executed has the highest task number in the program, END(001) marks the end of the overall main program.
This instruction has no function. (No processing is performed for NOP(000).)
Interlocks all outputs between IL(002) and ILC(003) when the execution condition for IL(002) is OFF. IL(002) and ILC(003) are normally used in pairs.
Interlocks all outputs between IL(002) and ILC(003) when the execution condition for IL(002) is OFF. IL(002) and ILC(003) are normally used in pairs.
When the execution condition for JMP(004) is OFF, program execution jumps directly to the first JME(005) in the program with the same jump number. When the execution condition is
ON, all instructions are executed normally.
JME(005) indicates the destination of jumps made for JMP(004), CJP(510), and CJPN(511).
The operation of CJP(510) is the basically the opposite of JMP(004).
When the execution condition for CJP(510) is ON, program execution jumps directly to the first JME(005) in the program with the same jump number. When the execution condition is
OFF, all instructions are executed normally.
The operation of CJPN(511) is almost identical to JMP(004).
When the execution condition for CJP(004) is OFF, program execution jumps directly to the first JME(005) in the program with the same jump number. When the execution condition is
ON, all instructions are executed normally.
When the execution condition for JMP0(515) is OFF, all instructions from JMP0(515) to the next JME0(516) in the program are processed as NOP(000). When the execution condition is
ON, all instructions are executed normally. Use JMP0(515) and JME0(516) in pairs. There is no limit on the number of pairs that can be used in the program.
JME0(516) indicates the destination of jumps made for JMP0(515).
The instructions between FOR(512) and NEXT(513) are repeated a specified number of times. FOR(512) and NEXT(513) are used in pairs.
Programmed in a FOR-NEXT loop to cancel the execution of the loop for a given execution condition. The remaining instructions in the loop are processed as NOP(000) instructions.
The instructions between FOR(512) and NEXT(513) are repeated a specified number of times. FOR(512) and NEXT(513) are used in pairs.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
463
Name
TIMER
COUNTER
HIGH-SPEED TIMER
ONE-MS TIMER
ACCUMULATIVE TIMER TTIM
LONG TIMER TIML
MULTI-OUTPUT TIMER MTIM
REVERSIBLE COUNTER CNTR
RESET
TIMER/COUNTER
CNR
Mnemonic Function code
TIM ---
CNT ---
TIMH
TMHH
015
540
087
542
543
012
545
Instruction Set
Timer and Counter Instructions
Function
TIM operates a decrementing timer with units of 0.1-s. The setting range for the set value (SV) is 0 to 999.9 s.
CNT operates a decrementing counter. The setting range for the set value (SV) is 0 to 9,999.
TIMH(015) operates a decrementing timer with units of 10-ms. The setting range for the set value (SV) is 0 to 99.99 s.
TMHH(540) operates a decrementing timer with units of 1-ms. The setting range for the set value (SV) is 0 to 9.999 s. The timing charts for TMHH(540) are the same as those given above for TIMH(015).
TTIM(087) operates an incrementing timer with units of 0.1-s. The setting range for the set value (SV) is 0 to 999.9 s.
TIML(542) operates a decrementing timer with units of 0.1-s that can time up to
9999999.9 S (approx. 115 days).
MTIM(543) operates a 0.1-s incrementing timer with eight independent SVs and
Completion Flags. The setting range for the set value (SV) is 0 to 999.9 s.
CNTR(012) operates a reversible counter.
Resets the timers or counters within the specified range of timer or counter numbers.
Sets the set value (SV) to the maximum of 9999.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
464
Instruction Set
Symbol Comparison Instructions
Name
Symbol
Comparison
(Unsigned)
Symbol
Comparison
(Double-word, unsigned)
Symbol
Comparison
(Signed)
Symbol
Comparison
(Double-word, signed)
COMPARE
DOUBLE
COMPARE
SIGNED BINARY
COMPARE
DOUBLE
SIGNED BINARY
COMPARE
TABLE
COMPARE
MULTIPLE
COMPARE
BLOCK
COMPARE
CMPL
CPS
CPSL
TCMP
MCMP
BCMP
Mnemonic Function code
LD, AND,
OR + =, <>,
<, <=, >, >=
300 (=)
305 (<>)
310 (<>)
315 (<=)
320 (>)
325(>=)
LD, AND,
OR + =, <>,
<, <=, >, >=
+ L
LD, AND,
OR + =, <>,
<, <=, >, >=
+S
301 (=)
306 (<>)
311 (<>)
316 (<=)
321 (>)
326 (>=)
302 (=)
307 (<>)
312 (<>)
317 (<=)
322 (>)
327 (>=)
LD, AND,
OR + =, <>,
<, <=, >, >=
+SL
CMP
303 (=)
308 (<>)
313 (<>)
318 (<=)
323 (>)
328 (>=)
020
060
114
115
085
019
068
Function
Symbol comparison instructions (unsigned) compare two values (constants and/or the contents of specified words) in 16-bit binary data and create an ON execution condition when the comparison condition is true. There are three types of symbol comparison instructions,
LD (LOAD), AND, and OR.
Symbol comparison instructions (double-word, unsigned) compare two values (constants and/or the contents of specified double-word data) in unsigned 32-bit binary data and create an ON execution condition when the comparison condition is true. There are three types of symbol comparison instructions, LD (LOAD), AND, and OR.
Symbol comparison instructions (signed) compare two values (constants and/or the contents of specified words) in signed 16-bit binary (4-digit hexadecimal) and create an ON execution condition when the comparison condition is true. There are three types of symbol comparison instructions, LD (LOAD), AND, and OR.
Symbol comparison instructions (double-word, signed) compare two values (constants and/or the contents of specified double-word data) in signed 32-bit binary (8-digit hexadecimal) and create an ON execution condition when the comparison condition is true.
There are three types of symbol comparison instructions, LD (LOAD), AND, and OR.
Compares two unsigned binary values (constants and/or the contents of specified words) and outputs the result to the Arithmetic Flags in the Auxiliary Area.
Compares two double unsigned binary values (constants and/or the contents of specified words) and outputs the result to the Arithmetic Flags in the Auxiliary Area.
Compares two signed binary values (constants and/or the contents of specified words) and outputs the result to the Arithmetic Flags in the Auxiliary Area.
Compares two double signed binary values (constants and/or the contents of specified words) and outputs the result to the Arithmetic Flags in the Auxiliary Area.
Compares the source data to the contents of 16 consecutive words and turns ON the corresponding bit in the result word when the contents of the words are equal.
Compares 16 consecutive words with another 16 consecutive words and turns ON the corresponding bit in the result word where the contents of the words are not equal.
Compares the source data to 16 ranges (defined by 16 lower limits and 16 upper limits) and turns ON the corresponding bit in the result word when the source data is within the range.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
465
Name Mnemonic Function code
MOVE
DOUBLE MOVE
MOV
MOVL
MOVE NOT MVN
DOUBLE MOVE NOT MVNL
MOVE BIT
MOVE DIGIT
MULTIPLE BIT
TRANSFER
MOVB
MOVD
XFRB
BLOCK TRANSFER XFER
BLOCK SET BSET
DATA EXCHANGE
DOUBLE DATA
EXCHANGE
XCHG
XCGL
021
498
022
499
082
083
062
070
071
073
562
SINGLE WORD
DISTRIBUTE
DATA COLLECT
DIST
COLL
080
081
MOVR 560 MOVE TO
REGISTER
MOVE
TIMER/COUNTER
PV TO REGISTER
MVRW 561
Instruction Set
Data Movement Instructions
Function
Transfers a word of data to the specified word.
Transfers two words of data to the specified words.
Transfers the complement of a word of data to the specified word.
Transfers the complement of two words of data to the specified words.
Transfers the specified bit.
Transfers the specified digit or digits. (Each digit is made up of 4 bits.)
Transfers the specified number of consecutive bits.
Transfers the specified number of consecutive words.
Copies the same word to a range of consecutive words.
Exchanges the contents of the two specified words.
Exchanges the contents of a pair of consecutive words with another pair of consecutive words.
Transfers the source word to a destination word calculated by adding an offset value to the base address.
Transfers the source word (calculated by adding an offset value to the base address) to the destination word.
Sets the PC memory address of the specified word, bit, or timer/counter Completion Flag in the specified Index Register. (Use MOVRW(561) to set the PC memory address of a timer/counter PV in an Index Register.)
Sets the PC memory address of the specified timer or counter’s PV in the specified Index
Register. (Use MOVR(560) to set the PC memory address of a word, bit, or timer/counter
Completion Flag in an Index Register.)
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
466
Instruction Set
Data Shift Instructions
Name
SHIFT REGISTER
REVERSIBLE SHIFT
REGISTER
ASYNCHRONOUS SHIFT
REGISTER
Mnemonic Function code
SFT
SFTR
ASFT
WORD SHIFT WSFT
ARITHMETIC SHIFT LEFT ASL
DOUBLE SHIFT LEFT
ARITHMETIC SHIFT
RIGHT
ASLL
ASR
010
084
017
016
025
570
026
DOUBLE SHIFT RIGHT
ROTATE LEFT
DOUBLE ROTATE LEFT
ROTATE LEFT WITHOUT
CARRY
ASRL
ROL
ROLL
RLNC
DOUBLE ROTATE LEFT
WITHOUT CARRY
RLNL
ROTATE RIGHT ROR
DOUBLE ROTATE RIGHT RORL
ROTATE RIGHT
WITHOUT CARRY
RRNC
DOUBLE ROTATE RIGHT
WITHOUT CARRY
RRNL
571
027
572
574
576
028
573
575
577
ONE DIGIT SHIFT LEFT SLD
ONE DIGIT SHIFT RIGHT SRD
SHIFT N-BIT DATA LEFT NSFL
SHIFT N-BIT DATA RIGHT NSFR
SHIFT N-BITS LEFT
DOUBLE SHIFT N-BITS
LEFT
NASL
NSLL
SHIFT N-BITS RIGHT
DOUBLE SHIFT N-BITS
RIGHT
NASR
NSRL
074
075
578
579
580
582
581
583
Function
Operates a shift register.
Creates a shift register that shifts data to either the right or the left.
Shifts all non-zero word data within the specified word range either towards St or toward E, replacing 0000Hex word data.
Shifts data between St and E in word units.
Shifts the contents of Wd one bit to the left.
Shifts the contents of Wd and Wd +1 one bit to the left.
Shifts the contents of Wd one bit to the right.
Shifts the contents of Wd and Wd +1 one bit to the right.
Shifts all Wd bits one bit to the left including the Carry Flag (CY).
Shifts all Wd and Wd +1 bits one bit to the left including the Carry Flag (CY).
Shifts all Wd bits one bit to the left not including the Carry Flag (CY).
Shifts all Wd and Wd +1 bits one bit to the left not including the Carry Flag (CY).
Shifts all Wd bits one bit to the right including the Carry Flag (CY).
Shifts all Wd and Wd +1 bits one bit to the right including the Carry Flag (CY).
Shifts all Wd bits one bit to the right not including the Carry Flag (CY). The contents of the rightmost bit of Wd shifts to the leftmost bit and to the Carry Flag (CY).
Shifts all Wd and Wd +1 bits one bit to the right not including the Carry Flag (CY).
The contents of the rightmost bit of Wd +1 is shifted to the leftmost bit of Wd, and to the Carry Flag (CY).
Shifts data by one digit (4 bits) to the left.
Shifts data by one digit (4 bits) to the right.
Shifts the specified number of bits to the left.
Shifts the specified number of bits to the right.
Shifts the specified 16 bits of word data to the left by the specified number of bits.
Shifts the specified 32 bits of word data to the left by the specified number of bits.
Shifts the specified 16 bits of word data to the right by the specified number of bits.
Shifts the specified 32 bits of word data to the right by the specified number of bits.
Increment/Decrement Instructions
Name
INCREMENT BINARY
DOUBLE INCREMENT
BINARY
DECREMENT BINARY
DOUBLE DECREMENT
BINARY
INCREMENT BCD
DOUBLE INCREMENT
BCD
DECREMENT BCD
DOUBLE DECREMENT
BCD
Mnemonic Function code
++
++L
590
591
-- --
-- --L
++B
++BL
-- --B
-- --BL
592
593
594
595
596
597
Function
Increments the 4-digit hexadecimal content of the specified word by 1.
Increments the 8-digit hexadecimal content of the specified words by 1.
Decrements the 4-digit hexadecimal content of the specified word by 1.
Decrements the 8-digit hexadecimal content of the specified words by 1.
Increments the 4-digit BCD content of the specified word by 1.
Increments the 8-digit BCD content of the specified words by 1.
Decrements the 4-digit BCD content of the specified word by 1.
Decrements the 8-digit BCD content of the specified words by 1.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
467
Name Mnemonic Function code
+ 400 SIGNED BINARY ADD
WITHOUT CARRY
DOUBLE SIGNED BINARY
ADD WITHOUT CARRY
SIGNED BINARY ADD WITH
CARRY
+L
+C
DOUBLE SIGNED BINARY
ADD WITH CARRY
+CL
BCD ADD WITHOUT CARRY +B
DOUBLE BCD ADD
WITHOUT CARRY
+BL
+BC
+BCL
BCD ADD WITH CARRY
DOUBLE BCD ADD WITH
CARRY
SIGNED BINARY
SUBTRACT WITHOUT
CARRY
DOUBLE SIGNED BINARY
SUBTRACT WITHOUT
CARRY
--
--L
401
402
403
404
405
406
407
410
411
SIGNED BINARY
SUBTRACT WITH CARRY
DOUBLE SIGNED BINARY
WITH CARRY
BCD SUBTRACT WITHOUT
CARRY
DOUBLE BCD SUBTRACT
WITHOUT CARRY
BCD SUBTRACT WITH
CARRY
--C
--CL
--B
--BL
--BC
412
413
414
415
416
DOUBLE BCD SUBTRACT
WITH CARRY
--BCL
SIGNED BINARY MULTIPLY *
SIGNED BINARY MULTIPLY *L
UNSIGNED BINARY
MULTIPLY
*U
DOUBLE UNSIGNED
BINARY MULTIPLY
*UL
BCD MULTIPLY
DOUBLE BCD MULTIPLY
SIGNED BINARY DIVIDE
DOUBLE SIGNED BINARY
DIVIDE
*B
*BL
/
/L
417
420
421
422
423
424
425
430
431
UNSIGNED BINARY DIVIDE /U
DOUBLE UNSIGNED
BINARY DIVIDE
/UL
BCD DIVIDE
DOUBLE BCD DIVIDE
/B
/BL
432
433
434
435
Instruction Set
Symbol Math Instructions
Function
Adds 4-digit (single-word) hexadecimal data and/or constants.
Adds 8-digit (double-word) hexadecimal data and/or constants.
Adds 4-digit (single-word) hexadecimal data and/or constants with the Carry
Flag (CY).
Adds 8-digit (double-word) hexadecimal data and/or constants with the Carry
Flag (CY).
Adds 4-digit (single-word) BCD data and/or constants.
Adds 8-digit (double-word) BCD data and/or constants.
Adds 4-digit (single-word) BCD data and/or constants with the Carry Flag (CY).
Adds 8-digit (double-word) BCD data and/or constants with the Carry Flag (CY).
Subtracts 4-digit (single-word) hexadecimal data and/or constants.
Subtracts 8-digit (double-word) hexadecimal data and/or constants.
Subtracts 4-digit (single-word) hexadecimal data and/or constants with the Carry
Flag (CY).
Subtracts 8-digit (double-word) hexadecimal data and/or constants with the
Carry Flag (CY).
Subtracts 4-digit (single-word) BCD data and/or constants.
Subtracts 8-digit (double-word) BCD data and/or constants.
Subtracts 4-digit (single-word) BCD data and/or constants with the Carry Flag
(CY).
Subtracts 8-digit (double-word) BCD data and/or constants with the Carry Flag
(CY).
Multiplies 4-digit signed hexadecimal data and/or constants.
Multiplies 8-digit signed hexadecimal data and/or constants.
Multiplies 4-digit unsigned hexadecimal data and/or constants.
Multiplies 8-digit unsigned hexadecimal data and/or constants.
Multiplies 4-digit (single-word) BCD data and/or constants.
Multiplies 8-digit (double-word) BCD data and/or constants.
Divides 4-digit (single-word) signed hexadecimal data and/or constants.
Divides 8-digit (double-word) signed hexadecimal data and/or constants.
Divides 4-digit (single-word) unsigned hexadecimal data and/or constants.
Divides 8-digit (double-word) unsigned hexadecimal data and/or constants.
Divides 4-digit (single-word) BCD data and/or constants.
Divides 8-digit (double-word) BCD data and/or constants.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
468
Instruction Set
Conversion Instructions
Name
BCD-TO BINARY
DOUBLE
BCD-TO-DOUBLE
BINARY
BINARY-TO-BCD
DOUBLE BINARY-
TO-DOUBLE BCD
2’S COMPLEMENT
DOUBLE 2’S
COMPLEMENT
16-BIT TO 32-BIT
SIGNED BINARY
DATA DECODER
Mnemonic Function code
BIN
BINL
023
058
BCD
BCDL
NEG
NEGL
SIGN
MLPX
024
059
160
161
600
076
DATA ENCODER
ASCII CONVERT
ASCII TO HEX
COLUMN TO LINE
LINE TO COLUMN
SIGNED
BCD-TO-BINARY
DOUBLE SIGNED
BCD-TO-BINARY
SIGNED
BINARY-TO-BCD
DOUBLE SIGNED
BINARY-TO-BCD
DMPX
ASC
HEX
LINE
COLM
BINS
BISL
BCDS
BDSL
077
086
162
063
064
470
472
471
473
Function
Converts BCD data to binary data.
Converts 8-digit BCD data to 8-digit hexadecimal (32-bit binary) data.
Converts a word of binary data to a word of BCD data.
Converts 8-digit hexadecimal (32-bit binary) data to 8-digit BCD data.
Calculates the 2’s complement of a word of hexadecimal data.
Calculates the 2’s complement of two words of hexadecimal data.
Expands a 16-bit signed binary value to its 32-bit equivalent.
Reads the numerical value in the specified digit (or byte) in the source word, turns ON the corresponding bit in the result word (or 16-word range), and turns OFF all other bits in the result word (or 16-word range).
4-to-16 bit conversion
FInds the location of the first or last ON bit within the source word (or 16-word range), and writes that value to the specified digit (or byte) in the result word.
16-to-4 bit conversion
Converts 4-bit hexadecimal digits in the source word into their 8-bit ASCII equivalents.
Converts up to 4 bytes of ASCII data in the source word to their hexadecimal equivalents and writes these digits in the specified destination word.
Converts a column of bits from a 16-word range (the same bit number in 16 consecutive words) to the 16 bits of the destination word.
Converts the 16 bits of the source word to a column of bits in a 16-word range of destination words (the same bit number in 16 consecutive words).
Converts one word of signed BCD data to one word of signed binary data.
Converts double signed BCD data to double signed binary data.
Converts one word of signed binary data to one word of signed BCD data.
Converts double signed binary data to double signed BCD data.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
469
Name
LOGICAL AND
DOUBLE
LOGICAL AND
Mnemonic Function code
ANDW
ANDL
LOGICAL OR
DOUBLE
LOGICAL OR
ORW
ORWL
EXCLUSIVE OR XORW
034
610
035
611
036
612 DOUBLE
EXCLUSIVE OR
EXCLUSIVE
NOR
DOUBLE
EXCLUSIVE
NOR
COMPLEMENT
DOUBLE
COMPLEMENT
XORL
XNRW
XNRL
COM
COML
037
613
029
614
Instruction Set
Logic Instructions
Function
Takes the logical AND of corresponding bits in single words of word data and/or constants.
Takes the logical AND of corresponding bits in double words of word data and/or constants.
Takes the logical OR of corresponding bits in single words of word data and/or constants.
Takes the logical OR of corresponding bits in double words of word data and/or constants.
Takes the logical exclusive OR of corresponding bits in single words of word data and/or constants.
Takes the logical exclusive OR of corresponding bits in double words of word data and/or constants.
Takes the logical exclusive NOR of corresponding single words of word data and/or constants.
Takes the logical exclusive NOR of corresponding bits in double words of word data and/or constants.
Turns OFF all ON bits and turns ON all OFF bits in Wd.
Turns OFF all ON bits and turns ON all OFF bits in Wd and Wd+1.
Name
BINARY ROOT
BCD SQUARE
ROOT
ARITHMETIC
PROCESS
FLOATING
POINT DIVIDE
BIT COUNTER
Mnemonic Function code
ROTB 620
ROOT
APR
072
069
FDIV
BCNT
079
067
Special Math Instructions
Function
Computes the square root of the 32-bit binary content of the specified words and outputs the integer portion of the result to the specified result word.
Computes the square root of an 8-digit BCD number and outputs the integer portion of the result to the specified result word.
Calculates the sine, cosine, or a linear extrapolation of the source data.
The linear extrapolation function allows any relationship between X and Y to be approximated with line segments.
Divides one 7-digit floating-point number by another. The floating-point numbers are expressed in scientific notation (7-digit mantissa and 1-digit exponent).
Counts the total number of ON bits in the specified word(s).
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
46:
Instruction Set
Floating-point Math Instructions
Name
FLOATING TO
16-BIT
FLOATING TO
32-BIT
16-BIT TO
FLOATING
32-BIT TO
FLOATING
FLOATING
POINT ADD
FLOATING
POINT
SUBTRACT
FLOATING-
POINT DIVIDE
FLOATING-
POINT
MULTIPLY
DEGREES TO
RADIANS
RADIANS TO
DEGREES
SINE
COSINE
TANGENT
ARC SINE
ARC COSINE
/F
û F
SQUARE ROOT SQRT
EXPONENT
LOGARITHM
EXP
LOG
EXPONENTIAL
POWER
PWR
RAD
DEG
SIN
COS
TAN
ASIN
Mnemonic Function code
FIX 450
FIXL 451
FLT
FLTL
+F
--F
452
453
454
455
ACOS
ARC TANGENT ATAN
457
456
458
459
460
461
462
463
464
465
466
467
468
840
Function
Converts a 32-bit floating-point value to 16-bit signed binary data and places the result in the specified result word.
Converts a 32-bit floating-point value to 32-bit signed binary data and places the result in the specified result words.
Converts a 16-bit signed binary value to 32-bit floating-point data and places the result in the specified result words.
Converts a 32-bit signed binary value to 32-bit floating-point data and places the result in the specified result words.
Adds two 32-bit floating-point numbers and places the result in the specified result words.
Subtracts one 32-bit floating-point number from another and places the result in the specified result words.
Divides one 32-bit floating-point number by another and places the result in the specified result words.
Multiplies two 32-bit floating-point numbers and places the result in the specified result words.
Converts a 32-bit floating-point number from degrees to radians and places the result in the specified result words.
Converts a 32-bit floating-point number from radians to degrees and places the result in the specified result words.
Calculates the sine of a 32-bit floating-point number (in radians) and places the result in the specified result words.
Calculates the cosine of a 32-bit floating-point number (in radians) and places the result in the specified result words.
Calculates the tangent of a 32-bit floating-point number (in radians) and places the result in the specified result words.
Calculates the arc sine of a 32-bit floating-point number and places the result in the specified result words. (The arc sine function is the inverse of the sine function; it returns the angle that produces a given sine value between --1 and 1.)
Calculates the arc cosine of a 32-bit floating-point number and places the result in the specified result words. (The arc cosine function is the inverse of the cosine function; it returns the angle that produces a given cosine value between --1 and 1.)
Calculates the arc tangent of a 32-bit floating-point number and places the result in the specified result words. (The arc tangent function is the inverse of the tangent function; it returns the angle that produces a given tangent value.)
Calculates the square root of a 32-bit floating-point number and places the result in the specified result words.
Calculates the natural (base e) exponential of a 32-bit floating-point number and places the result in the specified result words.
Calculates the natural (base e) logarithm of a 32-bit floating-point number and places the result in the specified result words.
Raises a 32-bit floating-point number to the power of another 32-bit floating-point number.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
46;
Name
SET STACK
Mnemonic Function code
SSET 630
632 PUSH ONTO
STACK
FIRST IN FIRST
OUT
LAST IN FIRST
OUT
DIMENSION
RECORD TABLE
PUSH
FIFO
LIFO
DIM
SET RECORD
LOCATION
GET RECORD
NUMBER
SETR
GETR
DATA SEARCH
SWAP BYTES
SRCH
SWAP
FIND MAXIMUM MAX
FIND MINIMUM MIN
SUM
FRAME
CHECKSUM
SUM
FCS
633
634
631
635
636
181
637
182
183
184
180
Instruction Set
Table Data Processing Instructions
Function
Defines a stack of the specified length beginning at the specified word and initializes the words in the data region to all zeroes.
Writes one word of data to the specified stack.
Reads the first word of data written to the specified stack (the oldest data in the stack).
Reads the last word of data written to the specified stack (the newest data in the stack).
Defines a record table by declaring the length of each record and the number of records. Up to 16 record tables can be defined.
Writes the location of the specified record (the PC memory address of the beginning of the record) in the specified Index Register.
Returns the record number of the record at the PC memory address contained in the specified Index Register.
Searches for a word of data within a range of words.
Switches the leftmost and rightmost bytes in all of the words in the range.
Finds the maximum value in the range.
Finds the minimum value in the range.
Adds the bytes or words in the range and outputs the result to two words.
Calculates the ASCII FCS value for the specified range.
Name Mnemonic Function code
PID CONTROL PID
LIMIT CONTROL LMT
DEAD BAND
CONTROL
BAND
190
680
681
DEAD ZONE
CONTROL
SCALING
ZONE
SCL
682
194
SCALING 2
SCALING 3
AVERAGE
SCL2
SCL3
AVG
486
487
195
Data Control Instructions
Function
Executes PID control according to the specified parameters.
Controls output data according to whether or not input data is within upper and lower limits.
Controls output data according to whether or not input data is within the dead band range.
Adds the specified bias to input data and outputs the result.
Converts unsigned binary data into unsigned BCD data according to the specified linear function.
Converts signed binary data into signed BCD data according to the specified linear function.
An offset can be input in defining the linear function.
Converts signed BCD data into signed binary data according to the specified linear function.
An offset can be input in defining the linear function.
Calculates the average value of an input word for the specified number of cycles.
Subroutine Instructions
Name Mnemonic Function code
SBS 091
Function
SUBROUTINE
CALL
SUBROUTINE
ENTRY
SUBROUTINE
RETURN
MACRO
SBN
RET
092
093
Calls the subroutine with the specified subroutine number and executes that program.
Indicates the beginning of the subroutine program with the specified subroutine number.
Indicates the end of a subroutine program.
MCRO 099 Calls the subroutine with the specified subroutine number and executes that program using the input parameters in S to S+3 and the output parameters in D to D+3.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
46<
Instruction Set
Interrupt Control Instructions
Name
SET INTERRUPT
MASK
Mnemonic Function code
MSKS 690
Function
Sets up interrupt processing for I/O interrupts or scheduled interrupts. Both I/O interrupt tasks and scheduled interrupt tasks are masked (disabled) when the PC is first turned on.
MSKS(690) can be used to unmask or mask I/O interrupts and set the time intervals for scheduled interrupts.
Reads the current interrupt processing settings that were set with MSKS(690).
READ
INTERRUPT
MASK
CLEAR
INTERRUPT
DISABLE
INTERRUPTS
ENABLE
INTERRUPTS
MSKR
CLI
DI
EI
692
691
693
694
Clears or retains recorded interrupt inputs for I/O interrupts or sets the time to the first scheduled interrupt for scheduled interrupts.
Disables execution of all interrupt tasks except the power OFF interrupt.
Enables execution of all interrupt tasks that were disabled with DI(693).
Step Instructions
Name
STEP DEFINE
Mnemonic Function code
STEP 008
STEP START SNXT 009
Function
STEP(008) functions in following 2 ways, depending on its position and whether or not a control bit has been specified.
(1)Starts a specific step.
(2)Ends the step programming area (i.e., step execution).
SNXT(009) is used in the following three ways:
(1)To start step programming execution.
(2)To proceed to the next step control bit.
(3)To end step programming execution.
Basic I/O Module Instructions
Name
I/O REFRESH
7-SEGMENT
DECODER
INTELLIGENT
I/O READ
INTELLIGENT
I/O WRITE
Mnemonic Function code
IORF
SDEC
097
078
IORD 222
IOWR 223
Function
Refreshes the specified I/O words.
Converts the hexadecimal contents of the designated digit(s) into 8-bit, 7-segment display code and places it into the upper or lower 8-bits of the specified destination words.
Reads the contents of the I/O Module’s memory area.
Outputs the contents of the CPU’s I/O memory area to the Special I/O Module.
Serial Communications Instructions
Name
PROTOCOL
MACRO
TRANSMIT
RECEIVE
CHANGE
SERIAL PORT
SETUP
Mnemonic Function code
PMCR 260
TXD
RXD
STUP
236
235
237
Function
Calls and executes a communications sequence registered in a Serial Communications
Board or Serial Communications Module.
Outputs the specified number of bytes of data from the RS-232C port built into the CPU.
Reads the specified number of bytes of data from the RS-232C port built into the CPU.
Changes the communications parameters of a serial port on the CPU, Serial
Communications Module (CPU Bus Module), or Serial Communications Board. STUP(237) thus enables the protocol mode to be changed during operation.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
473
Name
NETWORK SEND
NETWORK RECEIVE
DELIVER COMMAND
Name
READ DATA FILE
WRITE DATA FILE
Mnemonic Function code
SEND
RECV
CMND
090
098
490
Instruction Set
Network Instructions
Function
Transmits data to a node in the network.
Requests data to be transmitted from a node in the network and receives the data.
Sends FINS commands and receives the response.
Mnemonic Function code
FREAD 700
FWRIT 701
File Memory Instructions
Function
Reads the specified data or amount of data from the specified data file in file memory to the specified data area in the CPU.
Overwrites or appends data in the specified data file in file memory with the specified data from the data area in the CPU. If the specified file doesn’t exist, a new file is created with that filename.
Name
DISPLAY MESSAGE
Mnemonic Function code
MSG 046
Display Instructions
Function
Reads the specified sixteen words of extended ASCII and displays the message on a Peripheral Device such as a Programming Console.
Name Mnemonic Function code
CALENDAR ADD CADD
CALENDAR SUBTRACT CSUB
HOURS TO SECONDS SEC
730
731
065
SECONDS TO HOURS
CLOCK ADJUSTMENT
HMS
DATE
066
735
Clock Instructions
Function
Adds time to the calendar data in the specified words.
Subtracts time from the calendar data in the specified words.
Converts time data in hours/minutes/seconds format to an equivalent time in seconds only.
Converts seconds data to an equivalent time in hours/minutes/seconds format.
Changes the internal clock setting to the setting in the specified source words.
Name
TRACE MEMORY
SAMPLING
Mnemonic Function code
TRSM 045
Debugging Instructions
Function
When TRSM(045) is executed, the status of a preselected bit or word is sampled and stored in Trace Memory. TRSM(045) can be used anywhere in the program, any number of times.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
474
Instruction Set
Failure Diagnosis Instructions
Name
FAILURE ALARM
SEVERE FAILURE
ALARM
FAILURE POINT
DETECTION
Mnemonic Function code
FAL 006
FALS 007
FPD 269
Function
Generates or clears user-defined non-fatal errors. Non-fatal errors do not stop operation.
Generates user-defined fatal errors. Fatal errors stop PLC operation.
Diagnoses a failure in an instruction block by monitoring the time between execution of FPD(269) and execution of a diagnostic output and finding which input is preventing an output from being turned ON.
System Instructions
Name
SET CARRY
CLEAR CARRY
SELECT EM BANK
EXTEND MAXIMUM
CYCLE TIME
Mnemonic Function code
STC
CLC
EMBC
WDT
040
041
281
094
Function
Sets the Carry Flag (CY).
Turns OFF the Carry Flag (CY).
Changes the current EM bank.
Extends the maximum cycle time, but only for the cycle in which this instruction is executed.
Block Programming Instructions
Name Mnemonic Function code
096 BLOCK PROGRAM
BEGIN
BPRG
BLOCK PROGRAM END BEND 801
BLOCK PROGRAM
PAUSE
BLOCK PROGRAM
RESTART
CONDITIONAL BLOCK
EXIT
CONDITIONAL BLOCK
EXIT
CONDITIONAL BLOCK
EXIT (NOT)
CONDITIONAL BLOCK
BRANCHING
BPPS
BPRS
811
812 input_condition EXIT
EXIT bit_address
EXIT NOT bit_address input_condition IF
806
806
806
802
CONDITIONAL BLOCK
BRANCHING
CONDITIONAL BLOCK
BRANCHING (NOT)
IF bit_address
802
IF NOT bit_address
802
CONDITIONAL BLOCK
BRANCHING (ELSE)
ELSE
CONDITIONAL BLOCK
BRANCHING END
IEND
ONE CYCLE AND WAIT input_condition WAIT
803
804
805
Function
Define a block programming area. For every BPRG(096) there must be a corresponding BEND(801).
Define a block programming area. For every BPRG(096) there must be a corresponding BEND(801).
Pause and restart the specified block program from another block program.
Pause and restart the specified block program from another block program.
EXIT(806) without an operand bit exits the program if the execution condition is ON.
EXIT(806) without an operand bit exits the program if the execution condition is ON.
EXIT(806) without an operand bit exits the program if the execution condition is ON.
If the execution condition is ON, the instructions between IF(802) and ELSE(803) will be executed and if the execution condition is OFF, the instructions between
ELSE(803) and IEND(804) will be executed.
If the operand bit is ON, the instructions between IF(802) and ELSE(803) will be executed. If the operand bit is OFF, the instructions between ELSE(803) and
IEND(804) will be executed.
The instructions between IF(802) and ELSE(803) will be executed and if the operand bit is ON, the instructions be ELSE(803) and IEND(804) will be executed is the operand bit is OFF.
If the ELSE(803) instruction is omitted and the operand bit is ON, the instructions between IF(802) and IEND(804) will be executed
If the operand bit is OFF, only the instructions after IEND(804) will be executed.
If the execution condition is ON for WAIT(805), the rest of the instruction in the block program will be skipped.
(This table continues on the next page.)
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
475
Name
ONE CYCLE AND
WAIT
ONE CYCLE AND
WAIT (NOT)
TIMER WAIT
COUNTER WAIT
LEND NOT
Mnemonic Function code
WAIT bit_address
805
WAIT NOT bit_address
805
TIMW
CNTW
813
814
HIGH-SPEED TIMER
WAIT
TMHW
LOOP
LEND
LEND
LOOP input_condition
LEND
815
809
810
LEND bit_address
810
LEND NOT bit_address
810
Instruction Set
Block Programming Instructions (continued)
Function
If the operand bit is OFF (ON for WAIT NOT(805)), the rest of the instructions in the block program will be skipped. In the next cycle, none of the block program will be executed except for the execution condition for WAIT(805) or WAIT(805) NOT. When the execution condition goes ON (OFF for WAIT(805) NOT), the instruction from WAIT(805) or WAIT(805) NOT to the end of the program will be executed.
If the operand bit is OFF (ON for WAIT NOT(805)), the rest of the instructions in the block program will be skipped. In the next cycle, none of the block program will be executed except for the execution condition for WAIT(805) or WAIT(805) NOT. When the execution condition goes ON (OFF for WAIT(805) NOT), the instruction from WAIT(805) or WAIT(805) NOT to the end of the program will be executed.
Delays execution of the rest of the block program until the specified time has elapsed.
Execution will be continued from the next instruction after TIMW(813) when the timer times out.
Delays execution of the rest of the block program until the specified count has been achieved. Execution will be continued from the next instruction after CNTW(814) when the counter counts out.
Delays execution of the rest of the block program until the specified time has elapsed.
Execution will be continued from the next instruction after TMHW(815) when the timer times out.
LOOP(809) designates the beginning of the loop program.
LEND(810) or LEND(810) NOT specifies the end of the loop. When LEND(810) or
LEND(810) NOT is reached, program execution will loop back to the next previous
LOOP(809) until the operand bit for LEND(810) or LEND(810) NOT turns ON or OFF
(respectively) or until the execution condition for LEND(810) turns ON.
If the operand bit is OFF for LEND(810) (or ON for LEND(810) NOT), execution of the loop is repeated starting with the next instruction after LOOP(809). If the operand bit is
ON for LEND(810) (or OFF for LEND(810) NOT), the loop is ended and execution continues to the next instruction after LEND(810) or LEND(810) NOT.
LEND(810) or LEND(810) NOT specifies the end of the loop. When LEND(810) or
LEND(810) NOT is reached, program execution will loop back to the next previous
LOOP(809) until the operand bit for LEND(810) or LEND(810) NOT turns ON or OFF
(respectively) or until the execution condition for LEND(810) turns ON.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
476
Instruction Set
Text String Processing Instructions
Name
MOV STRING
CONCATENATE
STRING
Mnemonic Function code
MOV$
+$
GET STRING LEFT LEFT$
GET STRING RIGHT RGHT$
GET STRING
MIDDLE
MID$
664
656
652
653
654
FIND IN STRING
STRING LENGTH
REPLACE IN
STRING
FIND$
LEN$
RPLC$
DELETE STRING DEL$
EXCHANGE STRING XCHG$
CLEAR STRING
INSERT INTO
STRING
CLR$
INS$
String Comparison LD, AND,
OR +
=$, <>$,
<$, <=$,
>$, >=$
660
650
661
658
665
666
657
670 (=$)
671 (<>$)
672 (<$)
673 (<=$)
674 (>$)
675 (>=$
Function
Transfers a text string.
Links one text string to another text string.
Fetches a designated number of characters from the left (beginning) of a text string.
Reads a designated number of characters from the right (end) of a text string.
Reads a designated number of characters from any position in the middle of a text string.
Finds a designated text string from within a text string.
Calculates the length of a text string.
Replaces a text string with a designated text string from a designated position.
Deletes a designated text string from the middle of a text string.
Replaces a designated text string with another designated text string.
Clears an entire text string with NUL (00 hex).
Deletes a designated text string from the middle of a text string.
Sting comparison instructions (=$, <>$, <$, <=$, >$, >=$) compare two text strings from the beginning, in terms of value of the ASCII codes. If the result of the comparison is true, an ON execution condition is created for a LOAD, AND, or OR.
Task Control Instructions
Name
TASK ON
TASK OFF
Mnemonic Function code
TKON
TKOF
820
821
Function
Makes the specified task executable.
Puts the specified task into standby status.
Additional Information: For more detailed information regarding these instructions, refer to manual W340.
477
Download
Advertisement
Key features
Fastest Processing Speeds in the Industry
Large Program and Data Memory with Increased I/O Capacity
Programming Flexibility for New and Existing Applications.
Large and Diverse I/O Offering
Enhanced Design and Development Environment
Powerful Information Management
Improved Connectivity and Compatibility
Maintenance and Management
Analog Signal Processing at All System Levels
Full Range of Positioning and Speed Control
Frequently asked questions
The CS1 Series is a line of programmable logic controllers (PLCs) from Omron. They are designed to be fast, have a large program and data memory, and be easy to use and maintain.
The CS1 Series has a number of key features, including high-speed processing, large program and data memory, a wide range of I/O modules, and advanced communications capabilities. It also includes Task Programming for easier program development.