Trane Vertical Stack Fan Coil Catalogue

Add to My manuals
40 Pages

advertisement

Trane Vertical Stack Fan Coil Catalogue | Manualzz

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 1 Wednesday, July 17, 2013 9:37 AM

Catalog

Vertical Stack Fan Coil Units

Model RSG

3/4 through 4 ton capacity

July 2013

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 2 Wednesday, July 17, 2013 9:37 AM

Vertical Stack Fan Coil Units

Trane vertical stack fan coil units are used in high-rise hotels, condominiums, dormitories, military barracks, and residential buildings. Trane specializes in flexible response to customers’ needs.

We work closely with engineers at the design stage to ensure optimum use of the units within the

HVAC system.

Figure 1.

Fan coil - Model RSG

8

7

6

1

2

3

4

18 ga. galvanized cabinet with acoustical liner

Direct-drive centrifugal fan - PSC fan motor with sealed bearings standard

Piping package factory installed (HW preheat)

CW/HW coils - 2-pipe or 4-pipe

Drain pan - galvanized, positively sloped to outlet - standard

Optional electric heater (behind panel)

Optional electrical box for unit-mounted thermostat

Supply air opening (multiple openings available)

Figure 2.

Furred-in fan coil

Also available but not shown:

• Risers

• Double deflection supply air grille/ registers

• Return air panel

• Filter

• Fan shield/motor cover

5

Grille and return air panel standard color is white.

2 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 3 Wednesday, July 17, 2013 9:37 AM

Table of Contents

Vertical Stack Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Raised Base Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Supply Air Grille/Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Components and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Fans Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Control Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Tracer ZN521 Zone Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Tracer UC400 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Vertical Fan Coil Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2-Pipe Chilled Water Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2-Pipe Chilled Water Cooling Unit with Electric Heat . . . . . . . . . . . . . . . . 24

4-Pipe Chilled Water Cooling and Hot Water Heating Unit . . . . . . . . . . . 26

Fan Coil Units Without Risers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Riser Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Raised Base Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Raised Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Raised Base with Condensate Pump and Front Access Panel . . . . . . . . . 32

Return Air Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Return Air Panel with Flush Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Return Air Panel with Framed Out Drywall with Hinged Filter Access . . 34

Fan Coil Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Piping Packages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

UNT-PRC019-EN 3

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 4 Wednesday, July 17, 2013 9:37 AM

Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Riser Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Return Air Access Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Supply Air Grilles and Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Raised Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

4 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 5 Wednesday, July 17, 2013 9:37 AM

Model Number Description

The following is a complete description of the vertical stack fan coil model number.

Each digit in the model number has a corresponding code that identifies specific unit options. Example of model number:

RS-GF05-86MKX-WWX-R1PDABCDEFGA

Digits 1, 2 – Finished Goods

Identifier

Must always be “RS”

Digit 3 – Spacer

Digits 4, 5 – Unique Part

Identifier - Reserved

Must always be “GF”

Digits 6, 7 – Cabinet Footprint

05 = 17-in. x 17-in. Cabinet footprint (350 and 450 CFM models)

08 = 20-in. x 20-in. Cabinet footprint (600 and 800 CFM models)

12 = 20-in. x 24-in. Cabinet footprint (1000 and 1200 CFM models)

Digit 8 – Spacer

Digits 9, 10 – Unique Part

Identifier - Reserved

Must always be digits “86”

Digits 11, 12, 13 – Unique Part

Identifier – Reserved

Must always be entered as “MKX”

Digit 14 – Spacer

Digit 15 – Primary Cooling Means

C = Chilled Water (Single Purpose Coil)

W = Chilled Water (2-pipe Changeover

Coil - requires a change-over sensor)

X = No Cooling Coil

Digit 16 – Primary Heating Means

H = Hot Water (Single Purpose Coil)

W = Hot Water (2-pipe Changeover Coil)

E = Electric Resistance

X = No Heating Coil

Digit 17 – Auxiliary Heating

Means

E = Electric Resistance (requires additional change-over sensor)

X = No Heating Coil

Digit 18 – Spacer

Digit 19 – Cabinet Nominal CFM

E = 350

G = 450

K = 600

M = 800

P = 1000

R = 1200

Digit 20 – Unit Connection

Voltage

1 = 120/1/60

2 = 208/1/60

3 = 240/1/60

4 = 277/1/60

Digit 21 – Motor Type

P = PSC

D = ECM (Discrete speed)

V = ECM (Variable Speed)

Digit 22 – Water Coil and Fins

Per Inch (FPI)

Note: X/Y format, where X = Number of

Cooling rows and Y = Number of

Heating rows. Function (cooling only, changeover, etc) is handled in positions 15 and 16 of the model number.

3 row coils

K = 3/0 (2-pipe), 12 FPI

L = 3/1 (4-pipe), 12 FPI

M = 3/2 (4-pipe), 12 FPI

N = 3/0 (2-pipe), 14 FPI

P = 3/1 (4-pipe), 14 FPI

Q = 3/2 (4-pipe), 14 FPI

4-row coils

U = 4/0 (2-pipe), 12 FPI

V = 4/1 (4-pipe), 12 FPI

W = 4/2 (2-pipe), 12 FPI

X = 4/0 (2-pipe), 14 FPI

Y = 4/1 (4-pipe), 14 FPI

Z = 4/2 (4-pipe), 14 FPI

Digit 23 – Chilled Water Piping

Packages

Note: Manual air vent, drain cock, flexible braided hoses and unions on supply and return are standard features. Control valves are mounted on coil return.

A = 2-way control valve, shutoff valves on supply and return

B = 3-way control valve, shutoff valves on supply and return

C = 2-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return.

D = 3-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return.

E = 2-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return

F = 3-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return

G = 2-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return

H = 3-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return

Digit 24 – Hot Water Piping

Packages

Note: Manual air vent, drain cock, flexible braided hoses and unions on supply and return are standard features. Control valves are mounted on coil return.

A = 2-way control valve, shutoff valves on supply and return

B = 3-way control valve, shutoff valves on supply and return

C = 2-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return.

D = 3-way control valve, shutoff valve on supply, manual balancing valve with shutoff on return.

E = 2-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return

F = 3-way control valve, combo strainer/ shutoff valve on supply, manual balancing valve with shutoff on return

G = 2-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return

H = 3-way control valve, combo strainer/ shutoff valve on supply, automatic balancing valve with shutoff on return

Digit 25 – Electric Heat

Note: Must operate at supply voltage, subject to cabinet size and airflow.

0 = No Electric Heating Coil

A = 0.75 kW

B = 1.0 kW

C = 1.5 kW

D = 2.0 kW

E = 2.5 kW

F = 3.0 kW

G = 3.5 kW

H = 4.0 kW

J = 4.5 kW

K = 5.0 kW

M = 6.0 KW

P = 7.0 KW

R = 8.0 KW

Digit 26 – Control Type

(Provided and installed by factory unless otherwise noted)

0 = Low-voltage control by Others,

Installed by Others, Terminal Strip provided.

A = Auto Changeover, Non-

Programmable, Fan Speed Switch

B = Auto Changeover, Programmable, Fan

Speed Switch

C = Auto Changeover, Non-

Programmable, No Fan Speed Switch

D = Auto Changeover, Programmable, No

Fan Speed Switch

E = Manual Changeover, Non-

Programmable, Fan Speed Switch

F = Manual Changeover, Programmable,

Fan Speed Switch

UNT-PRC019-EN 5

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 6 Wednesday, July 17, 2013 9:37 AM

6

Model Number Description

G = Manual Changeover, Non-

Programmable, No Fan Speed Switch

H = Manual Changeover, Programmable,

No Fan Speed Switch

1 = Tracer™ ZN521 (zone sensor ordered separately)

2 = Tracer™ UC400 (zone sensor ordered separately)

Digit 27 – Actuator Operation

(Provided and installed by factory unless otherwise noted)

0 = None, Low Voltage, installed by others, outside of unit

C = Control Contractor Supplied, Low

Voltage, installed by factory

L = Line Voltage, 2-position

B = 24 V 2-position (normally closed spring return)

F = 3-Wire Floating Point

M = 0-10 or 2-10 V Modulating

Digit 28 – Cabinet Type/

Thermostat Location/Insulation

1 = Flush Mounted RA panel, remote mounted thermostat (Fiberglass insulation)

2 = Flush Mounted RA panel unit mounted thermostat (Fiberglass insulation)

3 = Hinge Mounted RA panel, remote mounted thermostat (Fiberglass insulation)

4 = Hinge Mounted RA panel unit mounted thermostat (Fiberglass insulation)

5 = Flush Mounted RA panel, remote mounted thermostat (Closed Cell

Insulation)

6 = Flush Mounted RA panel unit mounted thermostat (Closed Cell

Insulation)

7 = Hinge Mounted RA panel, remote mounted thermostat (Closed Cell

Insulation)

8 = Hinge Mounted RA panel unit mounted thermostat (Closed Cell

Insulation)

Digit 29 – Drain Pan

0 = None (Heating Only Unit)

1 = Acrylic coated galvanized steel double sloped drain pan

2 = Acrylic coated galvanized steel double sloped drain pan CW float switch

3 = Stainless Steel double sloped drain pan

4 = Stainless Steel double sloped drain pan CW float switch

Digit 30 – Design Sequence

Current design sequence is “A”

Riser Package

Digit 1, 2, 3 – Riser Package

Must always be “YRP”

Digit 4 – Configuration

A = 2-pipe system

S = 4-pipe system

Digit 5 – Spacer

Digit 6 – Riser Type

1 = Single

2 = Master

Digit 7 – Copper Pipe Type

1 = All risers - type “M”

2 = All risers - type “L”

3 = Supply, Return - type “L”, Condensate - type “M”

4 = Supply, Return - type “M”, No

Condensate

Digit 8, 9, 10 – Riser Insulation

Type*

0 = None

1 = Closed cell polyolefin

2 = Closed cell elastomeric

4 = Fiberglass

X = n/a

Digit 11 – Spacer

Digit 12, 13, 14 – Riser Insulation

Thickness*

0 = None

2 = 1/2 inch

4 = 1 inch

X = n/a

Note: * For a 2-pipe system:

First character: Use to describe the cooling supply and return (or heating supply and return)

Second character: Enter “X”

Third character: use to describe condensate

Note: *For a 4-pipe system:

First character: Use to describe cooling supply and return.

Second character: Use to describe heating supply and return.

Third character: Use to describe condensate.

Raised Base Package

Digit 1, 2, 3, 4 – Raised Base

Package

Must always be “YRBP”

Digit 5 – Spacer

Digit 6 – Unit Foot Print

1 = 350/450 (17 in. x 17 in.)

2 = 600/800 (20 in. x 20 in.)

3 = 1000/1200 (24 in. x 20 in.)

Digit 7, 8 – Raised Base Height

04 = 4 inches

08 = 8 inches

12 = 12 inches

Digit 9 – Access Panel**

0 = None

1 = Yes, front

Digit 10 – Condensate Pump*

(Voltages are connection voltages)

0 = No pump

1 = 120V

2 = 208V

3 = 240V

4 = 277V (c/w Transformer)

Note: Raised base is not insulated.

Optional access panel only available on the front side.

Note: *If condensate pump is required, raised base with condensate pump must be factory installed.

Electrical connections to the pump are by Trane.

Note: **Access panel is only available with a 12-inch raised base.

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 7 Wednesday, July 17, 2013 9:37 AM

Model Number Description

Supply Air Grille/

Registers

Digit 1, 2, 3 – Grille Supply

GSS = Grille Supply Steel

GSR = Grille Supply Steel with Register

GSA = Grille Supply Aluminum

GSB = Grille Supply Aluminum with

Register

Digit 4 – Spacer

Digit 5, 6 – Width**

XX = Round inches

Digit 7 – Type

0= Double deflection, horizontal front blades with mounting clips

1 = Double deflection, horizontal front blades with mounting holes

Digit 8, 9 – Height**

XX = round inches

Digit 10 – Color/Finish

W = Nailorhart White

C = Custom color

Note: * Mounting holes are on front flange of supply grille.

Note: ** Dimensions given for nominal frame size. These correspond to the nominal unit opening.

Table 1.

Return Air Grille Part

Numbers

Return Air Panel Type

Flush Mounted

Hinge Mounted

Flush Mounted

Hinge Mounted

Size 350/450/600/800

FSM 0145XA

GRS 14152W

Standard White

Size 1000/1200

Custom Color

FSM 0145XB

GRS 16154W

FSM 0145XAC

GRS 14152C

FSM 0145XBC

GRS 16154C

Table 2.

Register/Grille Quick

Reference

Nominal

Size

14 x 5

Grilles

GSS 14005W

Clips

Registers

GSR 14005W

Grilles

Screw Holes

GSS 14105W

Registers

GSR 14105W

14 x 8

14 x 10

14 x 12

14 x 14

GSS 14008W

GSS 14010W

GSS 14012W

GSS 14014W

GSR 14008W

GSR 14010W

GSR 14012W

GSR 14014W

GSS 14108W

GSS 14110W

GSS 14112W

GSS 14114W

GSR 14108W

GSR 14110W

GSR 14112W

GSR 14114W

16 x 12

16 x 14

GSS 16012W

GSS 16014W

GSR 16012W

GSR 16014W

GSS 16112W

GSS 16114W

Note:

For custom color grille, replace “W” with “C” at the end of the part number.

Registers and grilles are only available in the sizes listed in this table.

GSR 16112W

GSR 16114W

Filters

Table 3.

Filter Part Numbers

Filter Type

Pleated - MERV 13

Pleated - MERV 10

Throwaway Wire Frame - for Units with

Hinged Access Panel

Throwaway Cardboard Frame - for Units with Flush Mounted Access Panel

Note:

All filters are 1-inch thick.

Filter Part Numbers

Size 350/450/600/800 Size 1000/1200

14 x 25 nominal size

FPH 14125

FPY 14125

16 x 25 nominal size

FPH 16125

FPY 16125

FWX 14125A

FRX 14125

FWX 16125

FRX 16125

UNT-PRC019-EN 7

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 8 Wednesday, July 17, 2013 9:37 AM

Performance Data

Cooling Capacities

AHRI-certified cooling performance is based on ANSI/AHRI Standard 440-2008: Performance

Rating of Room Fan-Coils: 80/67°F entering air temperature, 45°F entering chilled water temperature with a 10°F delta T. All performance measured on high speed tap using a 120 V AC motor, 0.05 inches ESP without filters or grilles.

Table 4.

AHRI-certified ratings for cooling capacities

Size Coil

350

450

3HC

4HC

3HC

4HC

600

3HC

4HC

3HC

800

4HC

3HC

1000

4HC

3HC

1200

4HC

Note: EC motor also available.

Airflow

(cfm)

300

300

470

470

620

620

700

700

1010

1010

1140

1140

Total Capacity

(MBh)

8.5

Cooling

Sensible Capacity

(MBh)

5.3

Water Flow

(GPM)

2.3

24.6

31.6

36.3

34.3

39.7

9.2

11.8

12.9

19.8

22.4

21.6

15.1

20.0

22.1

22.1

24.4

5.6

7.7

8.3

12.6

13.7

13.8

5.8

7.4

8.5

8.0

9.3

2.4

3.1

3.4

4.7

5.3

5.1

WPD

(ft H2O)

5.2

17.9

18.9

16.5

20.4

18.9

5.3

10.0

7.5

18.6

19.1

19.7

Power Input (W)

PSC

132

132

175

175

259

259

290

290

446

446

621

621

8 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 9 Wednesday, July 17, 2013 9:37 AM

Performance Data

Heating Capacities

Heating performance is based on 70°F entering air temperature, and listed entering water temperatures. All performance data measured on high speed tap using a 120 V AC motor, 0.05 inches ESP without filters and grilles. 1-row and 2-row coils are in the preheat configuration as part of a 4-pipe system. 3-row and 4-row coils are only available as part of a 2-pipe system.

Table 5.

Heating capacities

Size

350

450

600

800

1000

1200

Total

Capacity

(MBh)

WPD

(ft H

2

0)

Rows

Heating 0.5 GPM

1-row

Preheat

10.2

2-row

Preheat 12.5

0.5

0.2

1-row

Preheat

11.5

0.5

LWT

(°F)

118

109

113

Total

Capacity

(MBh)

13.1

17.2

15.6

2-row

Preheat

14.1

0.2

102 20.6

1-row

Preheat - - - 19.5

2-row

Preheat

- - - 26.6

1-row

Preheat

- - - 20.2

2-row

Preheat - - - 27.5

1-row

Preheat

2-row

Preheat

- - - 24.5

- - - 32.0

1-row

Preheat - - - 25.3

2-row

Preheat

- - - 33.0

WPD

(ft H

2

0)

1.0 GPM

1.8

0.7

1.8

0.7

0.6

0.9

0.6

0.9

0.4

0.8

0.4

0.8

LWT

(°F)

133

125

128

118 26.6

120 25.2

2.3

106 35.9

119 26.4

104 38.0

110 33.6

95

108

93

Entering Water Temp. 160°F

Total

Capacity

(MBh)

WPD

(ft H

2

0)

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

15.3

20.8

19.0

47.2

35.3

49.6

2.0 GPM

6.7

2.6

6.7

2.6

3.3

2.3

3.3

1.6

2.7

1.6

2.7

144

139

141

133

134

123

133

121

126

112

124

109

16.2

22.3

20.4

29.3

27.9

40.3

29.4

43.0

38.3

55.3

40.5

58.9

3.0 GPM

14.5

5.7

14.5

5.7

5.1

7.1

5.1

7.1

3.4

5.7

3.4

5.7

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

LWT

(°F)

149 - - - - - -

145 - - - - - -

146 - - - - - -

140 - - - - - -

141

133

140

131

134

122

132

120

29.5

42.8

31.2

45.9

41.1

60.2

43.7

64.6

4.0 GPM

8.8

12.2

8.8

12.2

5.8

9.7

5.8

9.7

145

138

144

137

139

129

138

127

- - -

- - -

32.4

13.6

147

- - -

43.0

63.5

45.8

68.5

5.0 GPM

8.8

14.7

8.8

14.7

142

134

141

132

Size

350

450

600

800

1000

1200

Rows

Heating

3-row

Heating

4-row

Heating

3-row

Heating

4-row

Heating

3-row

Heating

4-row

Heating

3-row

Heating

4-row

Heating

3-row

Heating

4-row

Heating

3-row

Heating

4-row

Heating

Total

Capacity

(MBh)

WPD

(ft H

2

0)

10.5

11.9

11.7

13.2

0.5 GPM

0.2

0.1

0.2

0.1

LWT

(°F)

97

92

93

86

Total

Capacity

(MBh)

WPD

(ft H

2

0)

14.7

16.1

17.6

19.2

- - - 22.9

- - - 24.5

- - - 23.7

- - - 25.3

- - - 27.0

- - - 28.4

- - - 27.7

- - - 29.0

1.0 GPM

0.9

0.5

0.9

0.5

0.6

0.4

0.6

0.4

0.4

0.2

0.4

0.2

LWT

(°F)

Total

Capacity

(MBh)

Entering Water Temp. 140°F

WPD

(ft H

2

0)

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

104 23.3

101 25.7

93

90

92

89

85

82

84

81

31.8

34.7

33.7

36.7

41.5

44.9

43.6

47.2

2.0 GPM

110 18.0

3.3

107 19.7

2.0

3.3

2.0

2.2

1.7

2.2

1.7

1.4

0.9

1.4

0.9

3.0 GPM 4.0 GPM 5.0 GPM

122 19.3

7.2

127 - - - - - -

120

116

114

108

105

106

103

98

94

96

92

20.9

25.9

28.6

36.0

39.3

38.5

42.2

49.4

54.2

52.7

57.7

4.5

7.2

4.5

4.7

3.8

4.7

3.8

3.0

1.9

3.0

2.0

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

LWT

(°F)

Total

Capacity

(MBh)

WPD

(ft H

2

0)

LWT

(°F)

126 - - - - - -

122 - - - - - -

121 - - - - - -

116

113

114

111

107

103

104

101

38.2

41.6

41.3

45.1

54.3

59.7

58.4

64.4

8.2

6.6

8.2

6.6

5.1

3.3

5.1

3.3

121

119

119

117

112

110

110

107

- - -

- - -

43.0

46.9

57.4

63.1

62.3

68.7

12.6

10.2

7.7

5.1

7.8

5.1

123

121

117

114

115

112

UNT-PRC019-EN 9

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 10 Wednesday, July 17, 2013 9:37 AM

Performance Data

Sound Data

Table 6.

Sound data for vertical stack fan coils

Unit Size CFM

325

275

Fan Speed

High

Medium

Sound Pressure Level - dBA

31

29 350

450

225

500

425

Low

High

Medium

28

37

34

325

650

500

Low

High

Medium

31

39

37 600

425

725

Low

High

35

41

800

1000

600

500

1050

950

800

1175

Medium

Low

High

Medium

Low

High

39

37

45

43

41

50

1200 1100 Medium 47

1000 Low 44

Note: Sound level is measured at a distance of 8 ft. from the return air grille. Measurements are for a typical furnished and carpeted hotel suite. CFM in the above chart is approximate. Airflow is dependent on the number of coil rows, coil fins per inch, the amount of condensate on the fins, supply voltage, motor manufacturer, supply air configuration, filter cleanliness and altitude.

10 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 11 Wednesday, July 17, 2013 9:37 AM

Components and Options

Electric Heat

Table 7.

Kilowatts (kW) per model

Model

350/450

600/800

1000/1200 kW

Volts/ph/Hz

120V/1/60

208V/1/60

240V/1/60

277V/1/60

120V/1/60

208V/1/60

240V/1/60

277V/1/60

120V/1/60

208V/1/60

240V/1/60

277V/1/60

0.75

1.0

6.3

6.3

6.3

8.3

4.8

4.2

3.6

8.3

4.8

4.2

3.6

8.3

4.8

4.2

3.6

1.5

2.0

2.5

3.0

3.5

4.0

Heater Amps

4.5

5.0

6.0

7.0

8.0

16.7

9.6

8.3

7.2

16.7

9.6

8.3

7.2

16.7

9.6

8.3

7.2

12.5

7.2

6.3

5.4

12.5

7.2

6.3

5.4

12.5

7.2

6.3

5.4

12.0

10.4

9.0

14.4

12.5

10.8

16.8

14.6

12.6

12.0

10.4

9.0

12.0

10.4

9.0

14.4

12.5

10.8

14.4

12.5

10.8

16.8

14.6

12.6

16.8

14.6

12.6

19.2

16.7

14.4

19.2

16.7

14.4

21.6

18.8

16.2

24.0

20.8

18.1

21.6

18.8

16.2

24.0

20.8

18.1

28.8

25.0

21.7

28.8

25.0

21.7

33.7

29.2

25.3

38.5

33.3

28.9

• Heaters are wired for single stage operation.

• An auto-reset high limit device is included.

• Power connection is single point.

• The heater is located in the reheat position relative to the cooling coil.

• The fan coil unit does not include a fuse or fusible type disconnect. Motor sub-fusing as per electrical code.

Amps = Watts

Volts

Air temp. rise (Delta T) = kW x 3160 = MBH x 925

CFM CFM

S.A. = Supply Air

FLA = Full Load Amps

= S.A. fan motor Amps + Electric Heater Amps

MCA = Minimum Circuit Ampacity

= FLA x 1.25

MOP = Rating of maximum overcurrent protection device

= (2.25 x S.A. fan motor Amps) + Electric Heater Amps

UNT-PRC019-EN 11

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 12 Wednesday, July 17, 2013 9:37 AM

Components and Options

Requirements of Standards: UL 1995 and CSA C22.2 No.236

• If the value of the calculated rating does not equal a standard current rating of overcurrent protective device, the marked maximum rating shall be the next lower standard rating.

• Exception No. 1: The marked maximum rating of the overcurrent protective device shall be the standard rating next higher than the computed value if the next lower standard ratings is less than 125 percent of the current rating of an electric heater load, when the unit includes an electric heater.

• Exception No. 2: if the computed value of the overcurrent protective device is less than the minimum ampacity of the supply circuit, the marked rating of the device shall be increased to the largest standard overcurrent protective device rating appropriate for the marked minimum circuit ampacity.

• Exception No. 3: If the marked minimum circuit ampacity does not correspond to a standard protective device rating, the next higher standard rating of the protective device may be marked.

12 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 13 Wednesday, July 17, 2013 9:37 AM

Components and Options

Fans Curves

Figure 3.

Unit size 350

0.5

0.4

0.3

Low

0.2

0.1

0

0

6 Row

5 Row

4 Row

3 Row

100

Medium

200

High

Supply Air Volume (SCFM)

300

Figure 4.

Unit size 450

0.5

0.4

0.3

Low

0.2

0.1

0

200

6 Row

5 Row

4 Row

3 Row

Medium

300

High

400

Supply Air Volume (SCFM)

500

400

600

UNT-PRC019-EN 13

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 14 Wednesday, July 17, 2013 9:37 AM

Components and Options

Figure 5.

Unit size 600

0.5

0.4

0.3

0.2

Low

0.1

0

300

6 Row

5 Row

4 Row

3 Row

Medium

400

High

500

Supply Air Volume (SCFM)

600

Figure 6.

Unit size 800

0.5

0.4

0.3

0.2

Low

0.1

0

300

6 Row

5 Row

4 Row

3 Row

400

Medium

High

500 600

Supply Air Volume (SCFM)

700

700

800

14 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 15 Wednesday, July 17, 2013 9:37 AM

Components and Options

UNT-PRC019-EN

Figure 7.

Unit size 1000

0.5

0.4

0.3

Low

0.2

0.1

0

600

6 Row

5 Row

4 Row

3 Row

700

Medium High

800 900

Supply Air Volume (SCFM)

1000 1100 1200

Figure 8.

Unit size 1200

0.5

0.4

0.3

Low

Medium High

0.2

0.1

0

800

6 Row

5 Row

4 Row

3 Row

900 1000 1100

Supply Air Volume (SCFM)

1200 1300

Fan curves are based on 120V AC PSC motor at high, medium and low fan speed settings. The following test conditions apply:

• Centrifugal direct drive fan with double inlet and forward curved impeller.

• Cooling coil is dry.

• One-inch throwaway filter is clean.

15

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 16 Wednesday, July 17, 2013 9:37 AM

Components and Options

Motor Data

Table 8.

Motor data

Size

Connection Voltage

Volts/ph/Hz

120V/1/60

Max. Plate Ratings

HP

1/20

PSC

Amps

1.2

Max. Plate Ratings

HP

1/3

ECM

Amps

4.8

350

450

600

208-240V/1/60

277V/1/60

120V/1/60

208-240V/1/60

277V/1/60

120V/1/60

208-240V/1/60

277V/1/60

1/14

1/12

1/6

1/12

1/12

1/6

1/12

1/12

0.6

0.6

1.7

0.8

0.6

2.6

0.8

0.6

1/3

1/3

1/3

1/3

1/3

1/3

1/3

1/3

2.8

2.6

4.8

2.8

2.6

4.8

2.8

2.6

800

120V/1/60

208-240V/1/60

277V/1/60

120V/1/60

1/6

1/6

1/6

1/4

2.6

1.4

0.9

4.6

1/3

1/3

1/3

1/3

4.8

2.8

2.6

4.8

1000 208-240V/1/60

277V/1/60

120V/1/60

208-240V/1/60

1/4

1/4

1/3

1/3

2.2

1.6

6.4

3.1

1/3

1/3

1/2

1/2

2.8

2.6

6.8

4.1

1200

277V/1/60 1/3 2.1

1/2 3.6

Note:

EC motors have been programmed for three (3) discrete speed operation. Variable speed also available (not shown.) Motor nameplate data is shown in table. Fan motors are single phase and have a minimum of three speeds. Trane has several fan motor suppliers in order to ensure availability. Amp draws may differ between motors from different manufacturers. Trane reserves the right to change motor HP and therefore amp draws without notice

Control Packages

Trane offers a range of standard thermostats and controllers for the vertical stack fan coil units. For applications where a larger BAS is to be installed, Trane can provide factory mounting of the ZN521 or UC400 controllers.

Thermostats

Table 9.

Thermostat information

Thermostat

Voltage Manufacturer Model

Heat/Cool

Changeover Fan Operation

Available Fan

Speeds Application

24

24

120/208/240

24

24

120

Honeywell

Honeywell

Honeywell

HotelTech

HotelTech

HotelTech

TB8575A1000

TB7100A1000

TB6575A1000

LT24A

LT24A3

LT120A

1

Automatic or Manual

Automatic or Manual

Automatic or Manual

Automatic

Automatic

Automatic

User Selectable

User Selectable

User Selectable see Note 2 see Note 2 see Note 2

3

3

3

2

3

2

Residential or

Hospitality

Residential

Residential or

Hospitality

Hotel

Hotel

Hotel

208-230

277

HotelTech

HotelTech

LT220A

LT277A

Automatic

Automatic see Note 2 see Note 2

2

2

Hotel

Hotel

1. The Honeywell TB7100A1000 is a 7-day programmable thermostat.

2. The HotelTech thermostats feature automatic fan speed switching between the available speeds and off. The thermostat selects speed based on deviation of the room temperature from set point. The occupant can also manually select between the available speeds.

16 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 17 Wednesday, July 17, 2013 9:37 AM

Components and Options

Residential applications include: Condominiums, apartments, student residences/dormitories, assisted living/retirement facilities, and military barracks.

Trane recommends the remote mounting of low voltage (24V) thermostats to achieve optimal zone control. When thermostats are remote mounted, a terminal strip is provided inside the unit for field connection to the remote thermostat. Unit mounting of thermostat is also available, however all thermostats are shipped loose for field installation after the unit is installed, drywall is applied and the walls are painted.

The standard standalone thermostats listed above cycle a two position (on/off) valve and feature discrete speed fan speed operation. If modulating (0-10V DC or 3-wire floating point) valve actuators or modulating or 0-10V DC EC motors are a requirement, a thermostat or controller with the necessary analog outputs must be used.

Tracer ZN521 Zone Controller

The Tracer ZN521 is a factory-installed LonTalk ® control board designed to provide control of the

fan-coil products (see Figure 9 ).

Figure 9.

Tracer ZN521 controller

Features include:

• Automatic fan-speed reset

• Automatic ventilation reset

• Manual output test

• Filter maintenance

• Master slave

• Water valve override

• Freeze avoidance

• Interoperability

• Three generic I/O ports

The Tracer ZN521 controller is designed to be used in the following applications:

• As part of the Trane Tracer Summit building automation system, the Tracer ZN521 becomes an important part of the Trane Integrated Comfort system (ICS).

• The Tracer ZN521 can function as a completely standalone controller in situations where a building automation system (BAS) is not present.

• For situations when a non-Trane BAS is present, the Tracer ZN521 can be where ever a LonTalk front-end system is present.

Through building management of the HVAC system, optimizing energy consumption becomes possible at a zone level. Each unit is capable of functioning independently of one another during occupied and unoccupied hours of the day. This allows the temperature setpoint and ventilation

setting to be changed automatically based on zone usage (see Figure 10 ).

UNT-PRC019-EN 17

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 18 Wednesday, July 17, 2013 9:37 AM

Components and Options

18

Figure 10. Tracer ZN521 System

Tracer

Summit®

System

Rover™

(optional)

Fan coil

Fire safety system

Security system

Lighting system

Fan coil

To other building products

To other

Trane products

Two Systems in One

In an ICS environment, the Tracer ZN521 is pre-designed to install quickly and easily into the system. Since the controller is mounted on the unit, the start-up time for the entire system is minimized. Trane becomes the single source of responsibility for the equipment, unit controls, and building automation system.

Once power is applied to the controller, it will automatically start up and run based upon the setpoint on the local zone sensor. The Tracer ZN521 is certified to the interoperable L ON M ARK®

Space Comfort Controller profile. This allows the controller to be used with another vendor’s BAS and thereby still provide the high quality of factory installation. In addition, the Tracer ZN521 provides one of the most extensive interoperable data lists of any controller of its type in the industry.

Automatic Fan and Ventilation Reset

With the Tracer ZN521 controller, a multi-speed fan control for the fan coil delivers the airflow output customized to support the cfm space needs. When less cfm is necessary to meet the load of the zone (typically 75 to 80 percent of the time), the equipment operates on low speed. However, if the room temperature rises, the controller will switch to high speed.

Manual Output Test

The Tracer ZN521 controller includes a manual output test function. This function may be initiated from the blue test push button on the controller or through the Rover™ service tool. This feature is used to manually exercise the outputs in a defined sequence.

The purpose of this test sequence is to verify output and end device operation. The manual output test function may also be used in the following situations:

• Reset latching diagnostics

• Verify output wiring and operation

• Force the water valve(s) open to balance the hydronic system during installation set-up or service.

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 19 Wednesday, July 17, 2013 9:37 AM

UNT-PRC019-EN

Components and Options

Filter Maintenance

Filter status for the controller is based on the cumulative run hours of the unit fan. The controller compares the amount of fan run time against an adjustable fan run hour (stored in the controller) to determine when maintenance is recommended for the unit. The run-hours value may be user edited as required (through Rover). The valid range for the fan run hours limit is 0 to 5000 hours with a default of 600 hours. Once the run hours limit has been exceeded, the controller generates a maintenance required diagnostic (unit will not shut-down). The user will be notified of this diagnostic through the building automation system or when a Trane Service Tool is communicating with the controller.

Master Slave (Data Sharing)

Because the Tracer ZN521 controller utilizes L

ON

W

ORKS®

technology, the controller can send or receive data (setpoint, heat/cool mode, fan request, space temperature, etc.) to and from other controllers on the communication link with or without the existence of a building automation system. This applies to applications where multiple units might share one zone sensor for both stand-alone (with communication wiring between units) and a building automation system.

Water Valve Override

The Tracer ZN521 can be commanded via the Rover service tool to open all hydronic valves

100 percent. This allows for the faster water balancing of each unit and the entire system when the command is sent globally to all controllers. A properly balanced system is essential for proper and efficient operation.

Hydronic Coil Freeze Protection (Freeze Avoidance)

Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The

Tracer ZN521 does this from three different aspects. Any of these methods of protections will result in the unit fan being disabled, the outside air damper being shut, and the hydronic valves being opened 100 percent.

The three methods of freeze avoidance include:

1.

A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic if the coil temperature falls below 35°F.

2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and the valves are fully opened.

3. When in the unoccupied mode the Tracer ZN521 has an adjustable freeze avoidance setpoint.

If the outside air temperature is below the setpoint the unit will open the valves to allow water to flow through the coils.

Interoperability

Interoperability allows the owner freedom to select multiple vendors, and multiple products. With this advantage, the owner can choose the best products, the best application, and the best service from a variety of suppliers to meet their evolving building control needs in a cost effective manner.

Generic Binary Input/Output

The three generic binary inputs/outputs are not part of the normal control, but are actually controlled through the Tracer Summit system (when present) to issue commands to the Tracer

ZN521 control to turn the generic inputs/outputs of add-on equipment (such as baseboard heating, exhaust fans, occupancy sensor, lighting, etc.) on and off. This binary port is not affected when other binary diagnostics interrupt unit operation.

19

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 20 Wednesday, July 17, 2013 9:37 AM

Components and Options

Tracer UC400 Controller

The Tracer UC400 is a factory-installed BACnet ® MS/TP control designed to provide control of the fan coil (see

Figure 11 ). The Tracer UC400 controller is designed to be used in the following

applications: as stand-alone operation, part of the Trane Tracer SC building automation system, or part of another BACnet MS/TP Building Automation System. The Tracer UC400 can function as a completely standalone controller in situations where a building automation system (BAS) is not present.

Figure 11. Tracer UC400 Controller

Features include:

• Single Zone VAV

• Automatic ventilation reset

• Filter maintenance

• Water valve override

• Freeze avoidance

• Interoperability

• Unused I/O can be used as generic I/O

The Tracer UC400 is designed to install quickly and easily into the system. Trane becomes the single source of responsibility for the equipment, unit controls, and building automation system. As a standalone controller, the Tracer UC400 is ideally suited for fix-on-fail replacement of units with old pneumatic controllers, or in situations where a BAS will be added at a later date. Once power is applied to the controller, it will automatically start up and run based upon the setpoint on the local zone sensor. An individual time clock can be added to the unit for local scheduling. The Tracer

UC400 is BTL listed as B-ASC profile. This ensures the controller to be used with other BACnet ® building automation systems.

The Tracer UC400 controller delivers single zone VAV control and can be used in a stand-alone application or as part of a Trane Integrated Comfort™ System (ICS).

In the stand-alone configuration, Tracer UC400 receives operation commands from the zone sensor and/or the auto changeover sensor (on auto changeover units). The entering water temperature is read from the auto changeover sensor and determines if the unit is capable of cooling or heating.

The zone sensor module is capable of transmitting the following information to the controller:

• Timed override on/cancel request

• Zone setpoint

• Current zone temperature

• Fan mode selection (off-auto-high-med-low)

For optimal system performance, fan coils can operate as part of an ICS building automation system controlled by Tracer Summit. The controller is linked directly to the Summit control panel via a twisted pair communication wire, requiring no additional interface device (i.e., a command unit). The Trane ICS system can monitor or override Tracer UC400 control points. This includes such points as temperature and output positions.

20 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 21 Wednesday, July 17, 2013 9:37 AM

Components and Options

Single Zone VAV with Fully Modulating Fan Speed

With a single zone VAV with fully modulating fan speed, and EDM with modulating signal is required. The Tracer UC400 will minimize fan speed, and in turn energy usage, by only delivering

the air flow needed. See Figure 12

.

Figure 12. Cool mode nominal hydronic cooling control

UNT-PRC019-EN

Filter Maintenance

Filter status for the controller is based on the cumulative run hours of the unit fan. The controller compares the amount of fan run time against an adjustable fan run hour (stored in the controller) to determine when maintenance is recommended for the unit. The run-hours value may be user edited as required. The valid range for the fan run hours limit is 0 to 5000 hours with a default of

600 hours. Once the run hours limit has been exceeded, the controller generates a maintenance required diagnostic (unit will not shut-down). The user will be notified of this diagnostic through the building automation system or when a Trane ® service tool is communicating with the controller.

Hydronic Coil Freeze Protection (Freeze Avoidance)

Fan coil systems in cold climates need to take precautions to avoid hydronic coil freeze-up. The controller does this from three different aspects. Any of these methods of protections will result in the unit fan being disabled, the outside air damper being shut, and the hydronic valves being opened 100 percent.

The three methods of freeze avoidance include:

1.

A binary freeze protection thermostat is mounted on the coil and will cause a latching diagnostic if the coil temperature falls below 35°F.

2. An analog discharge air sensor monitors the temperature of the air coming off of the coil and if the temperature falls below 40°F the outside air damper is closed, the fan is turned off and the valves are fully opened.

3. When in the unoccupied mode, the controller has an adjustable freeze avoidance setpoint. If the outside air temperature is below the setpoint, the unit will open the valves to allow water to flow through the coils.

Interoperability

Interoperability allows the owner freedom to select multiple vendors, and multiple products. With this advantage, the owner can choose the best products, the best application, and the best service from a variety of suppliers to meet their evolving building control needs in a cost effective manner.

21

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 22 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Vertical Fan Coil Units

2-Pipe Chilled Water Cooling Unit

Figure 13.

2-pipe chilled water cooling unit - hot water changeover coil optional

16

13

14

15

C

B

TOP VIEW

1 1/2 in.

1/2 in.

D

6

1

4 in.

86 in.

2

E

8

3

9

4

5 6 in.

A

SIDE SECTION

(Flush Mounted Panel Option)

7

10

47 in.

SIDE VIEW

(Hinged Panel Option)

2 1/8 in.

9

12

6

11

F.F.L.

36 in.

FRONT VIEW

22 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 23 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 10. 2-pipe chilled water cooling unit callouts

18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.

Direct-drive centrifugal fan and PSC motor; EC motor optional.

Chilled water coil; hot water changeover optional.

Acrylic coated galvanized steel drain pan, pitched in two directions, insulated on the underside; stainless steel optional.

Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.

Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM:

5, 8, 10, 12, or 14 inches.

Flush mounted return air grille/access panel attached by quarter turn fasteners.

One inch disposable filter.

1/2-inch flange on front of unit. Allows direct application of drywall to the unit.

7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH-

SVX021A-EN installation manual for details.

Hinged return air grille/access panel (optional).

2 1/8-inch flange on front of unit. Drywall to be framed out in front of unit.

Unit mounting location for thermostat/controller.

Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.

Vertical centerline of coil connection run outs.

Connections are at the back, left or right sides of the unit.

Top supply air opening (knock out) for attachment of ductwork.

Table 11. 2-pipe chilled water cooling unit dimensions (inches)

Size

350

450

600

800

1000

1200

A

17

17

20

20

20

20

B

17

17

20

20

24

24

C

14

14

14

14

16

16

E

52

52

52

52

54

54

UNT-PRC019-EN 23

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 24 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

2-Pipe Chilled Water Cooling Unit with Electric Heat

Figure 14.

2-pipe chilled water cooling unit with electric heat

17

C

B

TOP VIEW

1 1/2 in.

2 1/8 in.

1/2 in.

D

7

1

2

4 in.

11

86 in.

3

E

9

4

10

5

6

6 in.

A

SIDE SECTION

(Flush Mounted Panel Option)

8

47 in.

13

9

SIDE SECTION

(Hinged Panel Option)

7

12

F.F.L.

36 in.

14

15

16

FRONT VIEW

24 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 25 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 12. 2-pipe chilled water cooling unit with electric heat callouts

18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.

Electric heater (primary or auxiliary).

Direct-drive centrifugal fan and PSC motor; EC motor optional.

Chilled water coil; hot water changeover optional.

Acrylic coated galvanized steel drain pan, pitched in two directions, insulated on the underside; stainless steel optional.

Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.

Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM:

5, 8, 10, 12, or 14 inches.

Flush mounted return air grille/access panel attached by quarter turn fasteners.

One inch disposable filter.

1/2-inch flange on front of unit. Allows direct application of drywall to the unit.

7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH-

SVX021A-EN installation manual for details.

Hinged return air grille/access panel (optional).

2 1/8-inch flange on front of unit. Drywall to be framed out in front of unit.

Unit mounting location for thermostat/controller.

Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.

Vertical centerline of coil connection run outs.

Connections are at the back, left or right sides of the unit.

Top supply air opening (knock out) for attachment of ductwork.

Table 13. 2-pipe chilled water cooling unit with electric heat dimensions (inches)

Size

350

450

600

800

1000

1200

A

17

17

20

20

20

20

B

17

17

20

20

24

24

C

14

14

14

14

16

16

E

52

52

52

52

54

54

UNT-PRC019-EN 25

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 26 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

4-Pipe Chilled Water Cooling and Hot Water Heating Unit

Figure 15.

4-pipe chilled water cooling and hot water heating unit

17

14

15

16

C

B

TOP VIEW

1

1/2 in.

D

1 1/2 in.

7

4 in.

2 1/8 in.

11

86 in.

2

3

E

9

4

5

10

6 6 in.

A

SIDE SECTION

(Flush Mounted Panel Option)

8

47 in.

SIDE SECTION

(Hinged Panel Option)

13

9

7

12

F.F.L.

36 in.

FRONT VIEW

26 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 27 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Table 14. 4-pipe chilled water cooling hot water heating unit callouts

18 ga. steel cabinet, lined with 1/2-inch fiberglass insulation coated on air side; 3/8-inch closed-cell foam optional.

Direct-drive centrifugal fan and PSC motor; EC motor optional.

Chilled water coil.

1/2-inch flange on front of unit. Allows direct application of drywall to the unit.

7/8-inch hole on each side of cabinet for power and control cable entry points on all units. See CLCH-

SVX021A-EN installation manual for details.

Hinged return air grille/access panel (optional).

2 1/8-inch flange on front of unit. Drywall to be framed out in front of unit.

Hot water coil.

Acrylic coated galvanized steel drain pan, pitched in two directions, insulated on the underside; stainless steel optional.

Drain hose from drain pan to condensate riser. The flexible hose forms a running trap.

Double deflection steel supply air grille at front, left, right or back or any combination when there are multiple openings. Dimension “D” varies with CFM:

5, 8, 10, 12, or 14 inches.

Flush mounted return air grille/access panel attached by quarter turn fasteners.

One inch disposable filter.

Unit mounting location for thermostat/controller.

Fan shield, acoustically lined. Identification and safety caution labels are affixed to this panel.

Vertical centerline of coil connection run outs.

Connections are at the back, left or right sides of the unit.

Top supply air opening (knock out) for attachment of ductwork.

Table 15. 4-pipe chilled water cooling and hot water heating unit dimensions (inches)

Size

350

450

600

800

1000

1200

A

17

17

20

20

20

20

B

17

17

20

20

24

24

C

14

14

14

14

16

16

E

52

52

52

52

54

54

UNT-PRC019-EN 27

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 28 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Fan Coil Units Without Risers

Figure 16. Fan Coil Units Without Risers

B K

B K

5

6

1 1/2 in.

86 in.

3 3/4 in.

5 1/4 in.

3 3/4 in.

Supply and return connections

1/2 in. or 3/4 in. nom.

Copper pipe

7"

R S

36 in.

Condensate connection

5/8 in. I.D. hose

C

4-pipe slave unit with BK connection

2 5/8 in.

C

2-pipe slave unit with BK connection

1 2 3

Inside unit

Outside unit

Stub-out detail - typical

4

Table 16. Fan coil units without risers - 2-pipe and 4-pipe slave units callouts

1/2-inch or 3/4-inch supply and return coil branch copper pipe

Union fitting

Ball valve (shut-off valve)

1/2-inch or 3/4-inch copper tail piece soldered into valve body at factory

Insulation lining on interior surface of fan coil cabinet

Fan coil cabinet

28 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 29 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Riser Packages

Figure 17.

Riser 2-Pipe Package

R C S

3 1/2 in. 3 1/2 in.

TOP VIEW

RA

R

C

S

RA RA

R C S

Left risers (LT) Back risers (BK) Right risers (RT)

CL

S C R

S = Supply riser

R = Return riser

C = Condensate riser

TOP VIEW

S C R

Reverse left risers (RL)

RA

S

C

R

RA RA

Reverse back risers (RB) Reverse right risers (RR)

Figure 18.

Riser 4-Pipe Package

2 5/8 in.

3 3/4 in.

2 5/8 in.

3 3/4 in.

TOP VIEW

RA

HWS

HWR

Cond.

CWR

CWS

RA RA

Left risers (LT)

Back risers (BK) Right risers (RT)

CL

TOP VIEW

HWS = Hot Water Supply Riser

HWR = Hot Water Return Riser

CWS = Chilled Water Supply Riser

CWR = Chilled Water Return Riser

Cond. = Condensate Riser

Reverse left risers (RL)

RA

CWS

CWR

Cond.

HWR

HWS

RA RA

Reverse back risers (RB) Reverse right risers (RR)

Reverse Riser orientations are used to aid in eliminating cross over piping when units on a riser stack change position from floor to floor or when two units share a common riser (Master/Slave).

TOP VIEW TOP VIEW

Right risers (RT)

R

C

S

R

C

S

Reverse right risers (RR)

Back risers (BK)

S

C

R

S

C

R

Reverse back risers (RB)

UNT-PRC019-EN 29

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 30 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Figure 19.

Riser Installation Dimensions (inches)

Standard Installation

Standard Installation Using

Spool Pieces

F

92 in.

L

F

92 in.

L

30

F

92 in.

L

F

F - L + 4 in.

92 in.

L

L = F + 2 inches

Spool Piece Length = F - L + 4 inches

L = F - Spool Length + 4 inches

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 31 Wednesday, July 17, 2013 9:37 AM

Raised Base Options

Raised Base

Figure 20.

Raised base - no access panel

Dimensions and Weights

12 in.

A

Front View

Available in 4-inch, 8-inch and 12-inch heights (shown)

Table 17. Raised base dimensions (inches)

Size

350

450

600

800

1000

1200

A

17

17

20

20

24

24

B

17

17

20

20

20

20

B

Side View

12 in.

UNT-PRC019-EN 31

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 32 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Raised Base with Condensate Pump and Front Access Panel

Figure 21.

Raised base with condensate pump and front access panel

Front View Side View

1

2

3

4

5

Front View

Available only with 12 inch raised base.

12 in.

3

Left Side View

8

F.F.L.

Drywall

6

7

Table 18. Raised base with condensate pump and front access panel callouts

Condensate riser (if applicable)

Drain tube factory installed

3/8-inch I.D. outlet tube by contractor

120V - 208V condensate pump

Front access panel (350 - 800 - 16 in. x 10 in.,

1000, 1200 - 18 in. x 10 in.

Screws for front access panel

12 inch raised base Opening for condensate hose running in and out

Note:

If the supply is 277V, an appropriately sized step-down transformer is included for condensate pump.

32 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 33 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Return Air Panels

Return Air Panel with Flush Mount

Figure 22.

Return air panel - flush mount with quarter turn fasteners

3 10

Up arrow indicates locked position

1

5

6

Top side section

4

7

8

2

2

9

3

10

Bottom side section

Table 19. Return air panel - flush mount with quarter turn fasteners callouts

Return air grille/access panel with quarter turn fasteners

Throwaway 1-inch filter.

1/2-inch deep collar around return air opening on fan coil unit

1/4 turn fastener with slotted head and square shaft

Pawl lock screw

Plastic washer

Spring retainer

Bottom hook of access panel

Pawl of the 1/4 turn fastener 1/2-inch drywall

Features

• Drywall attached directly to front of the unit

• Industry standard

• Fast access with quarter turn fasteners

• Easily removable for filter changing

UNT-PRC019-EN 33

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 34 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Return Air Panel with Framed Out Drywall with Hinged Filter Access

Figure 23.

Return air panel - framed out drywall with hinged filter access

5

6

6

2

3

4

1

Fan coil unit

Front of fan coil unit

Drywall stud by others

Drywall by others

2-in. collar on front of fan coil unit

6

Return air panel

34

Table 20. Return air panel with framed out drywall with hinged access filter access callouts

Hinged filter access door

Access panel retaining clip

Throwaway 1-inch filter

Grille frame

Filter channel

Sheet metal screw by contractor

Features

No exposed fasteners

Improved aesthetics

Easy filter changing - no tools required

Drywall is framed out around two-inch collar/flange

UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 35 Wednesday, July 17, 2013 9:37 AM

Dimensions and Weights

Fan Coil Weights

Table 21.

Weights for fan coil units

Size

350

450

600

800

1000

1200

Weight

140 lbs (63 kg)

150 lbs (68 kg)

170 lbs (77 kg)

180 lbs (82 kg)

210 lbs (95 kg)

220 lbs (100 kg)

The weights are approximate. Risers, external sheet metal accessories and supply air grilles are not included in the weight.

UNT-PRC019-EN 35

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 36 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications

Certifications

Performance: Unit performance is certified by AHRI in accordance with ANSI/AHRI 440-2008:

Performance Rating of Room Fan-Coils.

Safety: All standard units are agency listed in the United States and Canada and comply with the requirements of the current editions of UL 1995/CSA C22.2 No. 236.

Construction

The cabinets shall be fabricated from 18 gage steel lined with ½-inch fiberglass insulation bonded with a thermosetting resin and coated on the airstream side with an acrylic facing. In addition, there is an option available for 3/8-inch closed cell cabinet insulation.

The drain pan shall be an acrylic (black polyester powder) coated 20 gauge galvanized steel positively sloped in two directions towards the outlet. The drain pan shall be insulated on the underside with ½-inch fiberglass insulation (same as cabinet). The drain hose from the outlet to the condensate riser shall form a running trap. An optional Stainless Steel drain pan is also available.

A drain pan float switch is also available. The float switch will close CW control valve upon detection of high water level in condensate drain pan.

Fan

The galvanized metal fan wheels are centrifugal forward-curved and double-width. Fan wheels and housings are corrosion resistant.

Motors

The fan motor shall be a three speed P.S.C. type with internal thermal protection and sealed bearings. All motors have a maximum ambient operating temperature of 104°F and are permanently lubricated.

An optional ECM type brushless fan motor is available. The motor is available, programmed at the factory for three (3) discrete speed operation. A variable speed EC motor is also available for use with a 2-10V DC signal.

An unfused service disconnect switch shall be included, mounted inside the unit behind the motor cover.

Coils

Piping Packages

The piping package shall include: Ball type shut-off valves on the coil supply and returns (combined with balancing valves or strainers when used), and a two- or three-way control valve with twoposition actuator. Chilled water and hot water valves are normally closed.

Control valves are also available in 3 wire floating point or 2-10V DC modulating valves.

Additionally balancing valves (manual or automatic) and strainers supplied as riser system dictates. These devices are provided as combo-valves with the shut-off on supply and return and can be equipped with PT ports.

Electric Heat

The coil shall have aluminum fins mechanically bonded to ½-inch copper tube. The coil shall be factory pressure tested at not less than 300 psig. A manual air vent shall be incorporated at the high point, and a drain cock at the low point of the connecting pipework to the coil.

Units with electric heat shall be wired for single-stage operation with an open wire nickel-chrome element. An auto-reset high limit device shall be included.

36 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 37 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications

Filters

A one-inch disposable filter shall be shipped loose with the return air access panel.

Units equipped with one inch MERV 10 filters have a rating based on ASHRAE Standard 52.2. The average dust spot efficiency is no less than 35 to 40 percent when tested in accordance with

ASHRAE 52.1 atmospheric dust spot method.

Units equipped with one inch MERV 13 filters have a rating based on ASHRAE Standard 52.2. The average dust spot efficiency is no less than 90 percent efficiency on 1–3 micron particles and greater than 90 percent efficiency on 3–10 micron particles when tested in accordance with ASHRAE Test

Standard 52.2.

Controls

Thermostat (option)

The fan coil manufacturer shall supply a low voltage (24V) thermostat for remote mounting, or optionally unit mounted. Remote mounted thermostats are connected to a terminal strip that is mounted inside the unit. The thermostat is shipped loose for installation after the unit is installed, dry-wall is applied and the walls are painted.

Line voltage controls for unit mounting is also available. Thermostat quick-connect plug provided; thermostat ships loose for installation after drywall is applied and walls are painted.

Tracer ZN521 (option)

The Tracer ZN521 discrete speed controller can be used in a stand-alone application or used as part of a Trane Integrated Comfort System (ICS) with LonTalk® communication. The Tracer ZN521 offers the combined advantages of simple and dependable operation. Standard control features include options normally available on more elaborate control systems. All control options are available factory-mounted and can be field-configured using a service tool.

Tracer UC400 (option)

The Tracer UC400 controller delivers single zone VAV control in a stand-alone application or as part of a Trane Integrated Comfort system with BACnet® communication. Standard control features include options normally available on more elaborate control systems.

Riser Package

Risers are available in both type “L” and type “M” copper for supply, return and condensate pipes.

Riser insulation is available in ½-inch and one-inch wall thickness for closed cell foam (polyolefin), closed cell elastomeric (similar to Armaflex®) and fiberglass (wrapped with vapor barrier).

Riser diameter and insulation thickness are subject to physical limitations. Contact Trane when risers are larger than 2 1/2 inches in diameter. The risers shall have an approximately 2 1/2 inch swaged expansion at the top end to allow a 2 inch insertion of the riser from above without the use of couplings. Risers may be provided plain ended in lieu of swaged for field supplied/installed fittings (similar to Pro-Press®).

The riser insulation shall have a flame spread rating of 25 or less and a smoke developed rating of 50 or less in compliance with ASTM E 84. The insulation shall be continuous over the riser length within the height of the cabinet. Provision for insulation beyond the ends of the cabinet shall be the responsibility of the installing contractor.

The specification of riser anchoring, expansion loops and fire stopping requirements are not detailed in this specification and are not part of the Trane fan coils scope. Trane can provide expansion loops installed on the risers at the factory as per the engineers specification.

Hot water risers which are continuous over twelve or more floors may incorporate expansion compensation loops within the fan coil cabinet, location and spacing of expansion joints are the responsibility of the design engineer.

UNT-PRC019-EN 37

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 38 Wednesday, July 17, 2013 9:37 AM

Mechanical Specifications

Return Air Access Panel

The return air access panel shall have a fixed blade return air grille in the lower portion with filter access achieved by removal of the panel. The panel installs flush on to the drywall which has been applied directly to the front of the unit. The panel is of stamped steel construction and shall be finished in standard white baked enamel. The panel secures to the unit by a hook on the bottom edge and two quarter-turn fasteners in the upper corners. The panel is shipped loose for installation after the unit is installed, dry-wall is applied and the walls are painted.

There is also a return air access panel with hinged filter access as an option. Stamped steel construction with return air grille in lower portion of grille and hinged filter access in the top portion. Secured to the two-inch flange on the front of the unit with sheet metal screws. Drywall is framed out in front of the unit and is not applied directly to the unit face.

Supply Air Grilles and Registers

Supply air grilles and registers shall be provided for unit mounting locations. The grilles shall be steel, have double deflection airfoil blades and shall be finished in standard white baked enamel.

The grilles shall attach to the collar of the fan coil unit by spring clips. When a unit has more than one supply air opening a balancing damper (horizontal in the front) is included with the grille

(register) to balance the air flow (screw holes optional). Any supply air grilles which are part of supply air ductwork shall be provided by the sheet metal contractor. Grilles are shipped loose for installation after the unit is installed, dry-wall applied and the walls are painted.

A line of sight baffle with acoustical wrap shall be included in units which have left and right or front and back supply air openings.

There is also an option to upgrade the supply air grille material to aluminum as well as the option to provide custom colors for return air panels and supply air grilles/registers.

Raised Bases

Raised bases are available in heights of 4 inches, 8 inches or 12 inches. An access panel is available only in the 12-inch height option. If a condensate pump is required, 12-inch high raised base with access panel is required.

38 UNT-PRC019-EN

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 39 Wednesday, July 17, 2013 9:37 AM

Notes

Notes

UNT-PRC019-EN 39

UNT-PRC019-EN_072013_Vertical Stack Fan Coil.book Page 40 Wednesday, July 17, 2013 9:37 AM

4008161

ETL LISTED

CONFORMS TO

UL STD 1995

CERTIFIED TO

CSA STD C22.2 NO. 236

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

© 2013 Trane All rights reserved

UNT-PRC019-EN 15 July 2013

(NEW)

We are committed to using environmentally conscious print practices that reduce waste.

advertisement

Key Features

  • Compact design for easy installation
  • Direct-drive centrifugal fan for quiet operation
  • Piping package factory installed for convenience
  • Optional electric heater for supplemental warmth
  • Acoustical liner for noise reduction

Related manuals

Frequently Answers and Questions

What is the capacity range of the Trane Vertical Stack Fan Coil?
The capacity range is from 3/4 through 4 tons
What type of fan is used in the Trane Vertical Stack Fan Coil?
It uses a direct-drive centrifugal fan with sealed bearings.
Does the Trane Vertical Stack Fan Coil come with a drain pan?
Yes, it comes with a galvanized drain pan that is positively sloped to the outlet.