Tebis TX100 Configurator


Add to my manuals
19 Pages

advertisement

Tebis TX100 Configurator | Manualzz
5
Tebis TX100 Configurator
quicklink Radio ON / OFF Input / Output products
Electrical / Mechanical characteristics: see product user's instructions
Product reference Description
TX100 version
TRE400
1 lighting output + 1 input - IP55
> V2.5.1
TRB501
1 output 10A + 1 binary input
> V2.6.0
TRE400 / TRB501
1
TP device
RF devices
6T 8074-02a
Input
Output
Loads connected
Visualisation
system
TRE400
TRB501
Summary
1. Presentation...................................................................................................................................................................... 3
1.1 General points ............................................................................................................................................................. 3
1.2 Function Description.................................................................................................................................................... 3
2. Configuration and settings ................................................................................................................................................ 5
2.1 Configuration ............................................................................................................................................................... 5
2.2 On / Off Lighting functions ........................................................................................................................................... 6
2.3 Dimmer Lighting functions ........................................................................................................................................... 8
2.4 Shutters / Blinds function........................................................................................................................................... 10
2.5 Heating / Air-Conditioning function ............................................................................................................................ 13
2.6 Scene Functions........................................................................................................................................................ 15
2.7 Repeater Function ..................................................................................................................................................... 15
3. "+ info" and "expert" mode of the TX100 ........................................................................................................................ 16
3.1 Mode + Info ............................................................................................................................................................... 16
3.2 Expert mode .............................................................................................................................................................. 16
4. Factory reset ................................................................................................................................................................... 18
4.1 Factory reset using the TX100 .................................................................................................................................. 18
4.2 Factory reset on the product...................................................................................................................................... 18
5. Main characteristics ........................................................................................................................................................ 18
TRE400 / TRB501
2
6T 8074-02a
1. Presentation
1.1 General points
All the radio emitters / receivers referred to in this document are quicklink
RF devices. They can be recognised by the
configuration cfg push button with which they are all equipped. Quicklink
indicates the configuration without tools mode.
These products can also be configured to E mode by the TX100 or in S mode by ETS via the media coupler TR131.
In this case, the version of the TR131 must fulfill the following characteristics:
• Firmware: > 1.2.5
• Plug-in: > 1.0.11
This document describes the configuration principle with the TX100 tool and the functions available in this mode.
Within the same installation, a single configuration mode may be used.
To reuse with TX100, a product that has already been programmed in another installation whatever the inital
configuration (quicklink , TX100 or ETS), it is necessary to carry out a factory reset on the device.
Fot the combined input / output products, the factory reset will reinstall the local commands (the input of the product controls the
load connected with the product). To associate a different function to these inputs with the TX100, the local control link must dirst
be deleted (select the input and output numbers for the product and delete the link).
Specifics of the quicklink radio emitters / receivers:
All the lighting ON / OFF transmitters / receivers are operational when delivered (pre-configured). The product inputs control its
output for the most commonly used function (ON / OFF control via toggle switch push button). To use the inputs with a different
function, simply delete the existing link using the TX100 before reprogramming this input.
1.2 Function Description
The TX100 is used to re-configure the input and output of the TRE400 or the TRB501:
Description
TRB501
C
L
N
fct
S1
TRE400
A
B
cfg
A
LN
E1 S2
1 2 34 5 6 78
75%
LED
LED
cfg
IFW
IFW
fct
FIJ
FIJ
C
/ 1 1
B
L
N
A
B
C
Button and LED configuration cfg
1 input for push button or switch
Button and LED function fct
TRE400 / TRB501
3
6T 8074-02a
1.2.1 Inputs
The radio transmitters enable commands to be transmitted for lighting, shutters and blinds, heating / air-conditioning, and scenes.
■ Emission of commands
• Lighting control
• Toggle switch, ON, OFF, ON / OFF, Timer, Priority, Dimming
• Shutters / Blinds control
• Up, Down, Stop, Slat angle, Priority, Wind alarm, Rain alarm
• 1-button control
• Set point selection (Heating)
• Comfort / Night set-point, Comfort, Night set-point, Frost protection / Auto, Frost protection, Auto, Standby, Comfort /
Standby, Priority
• Scene control
1.2.2 Outputs
The main functions are the following:
■ ON / OFF
The ON / OFF function is used to switch a lighting circuit ON or OFF. The command may come from switches, pushbuttons or
automatic controls.
■ Status indication
The Status indication function displays the status of the output contact. It allows a Toggle function to be created by sending the
status indication to each push button of the group.
■ Timer
The Timer function is used to switch a lighting circuit ON or OFF for an adjustable time. Depending on the operation mode
selected, the output may be delayed for ON or OFF switching. The timer can be interrupted before the end of the time delay.
■ Priority
The Priority function allows overriding an output to a definite status, ON or OFF. This command has the highest priority. No other
command is taken into account if a priority is active. Only a priority end command re-enables the other commands.
Application: maintaining lighting ON for safety reasons.
■ Scene
The Scene function groups a set of outputs. These outputs can be set to an adjustable predefined status. Pressing a push button
activates a scene. Each output may be integrated into 8 different scenes.
TRE400 / TRB501
4
6T 8074-02a
2. Configuration and settings
2.1 Configuration
These functions are available in the TX100's Standard configuration mode by creating links with the appropriate output devices.
The radio emitters / receivers always function in bidirectional mode.
■ Configuration principle
➜ Programming the product:
• Go to Prog mode and do a long key-press on the
button of TX100 to launch the products tutorial for the installation.
➜ To number the radio inputs:
• Go to the Num numbering menu ➜ Inputs ➜ ,
• Press on the input key to be numbered. A beep will sound when the input is detected, the configurer will automaticallu
allocate a number to it,
• Proceed the same way for the other inputs.
➜ To allocate a function to an input key:
• Go to the Num numbering menu,
• Select the number of the input key required,
• Press
,
• Select the function and validate using
TRE400 / TRB501
.
5
6T 8074-02a
2.2 On / Off Lighting functions
The ON / OFF Lighting functions command the ON / OFF Lighting outputs symbolized by the
display.
icon on the right part of the
After numbering, the functions and the links appear on the left side of the screen of the TX100.
Selection of the
link type to be
created
Prog
1
59
95
Auto
All
Outputs
Inputs
The
Num
symbol indicates that it is a radio input. To select the functions, switch to the numbering mode.
The table here after shows all type of links compatible with the product:
Possible link type
ON
Link description
Output operation
The ON function switches the lighting
circuit ON.
The activation of the input will cause the light to turn
on.
Successive activations will keep the light on.
OFF
The OFF function switches the lighting
circuit OFF.
The activation of the input will cause the light to turn
off.
Successive activations will keep the light off.
Toggle switch
The Toggle switch function allows inverting Each activation of the input caises the state of the
the status of the lighting circuit.
output contact to be inverted.
Switch
The Switch function switches the lighting
circuit ON or OFF.
Closing the input contact causes the light to turn on.
The Timer ON function switches the
lighting circuit ON for an adjustable time.
Select the time delay after confirming the
link:
Setting range [0 s - 24 h]
Timer ON
TRE400 / TRB501
Opening the input contact causes the light to turn
off.
The activation of the input by a short key-press <1 s
causes a timed illumination of the light.
Interruption of the time delay:
The activation of the input by a long key-press >1 s
causes the time delay in progress to be stopped.
Increase of the duration of the delay time:
Timer commands repeated n times during the first
Not active, 1 s, 2 s, 3 s, 5 s, 10 s, 15 s, 20 ten seconds after the beginning of the time delay
s,
multiply the duration of the time delay by n times the
30 s, 45 s, 1 min, 1 min 15 s, 1 min 30 s,
value of the Timer parameter.
2 min, 2 min 30 s, 3 min, 5 min, 15 min,
20 min, 30 min, 1 h, 2 h, 3 h, 5 h, 12 h,
Restart of the timer:
24 h.
A command given 10 sec after the beginning of the
time delay restarts the timer only once.
6
6T 8074-02a
Possible link type
Link description
Output operation
The Timer OFF function switches the
lighting circuit off for an adjustable time.
Select the time delay after confirming the
link:
Setting range [0 s - 24 h]
Timer OFF
The activation by short key-press <1 s causes a
timed extinction of the light.
Interruption of the time delay:
The activation of the input by a long key-press >1 s
causes the time delay in progress to be stopped.
Increase of the duration of the delay time:
Timer commands repeated n times during the first
Not active, 1 s, 2 s, 3 s, 5 s, 10 s, 15 s, 20 ten seconds after the beginning of the time delay
s,
multiply the duration of the time delay by n times the
30 s, 45 s, 1 min, 1 min 15 s, 1 min 30 s,
value of the Timer parameter.
2 min, 2 min 30 s, 3 min, 5 min, 15 min,
20 min, 30 min, 1 h, 2 h, 3 h, 5 h, 12 h,
Restart of the timer:
24 h.
A command given 10 sec after the beginning of the
time delay restarts the timer only once.
Closing the input contact causes the the output to
be prioritised to ON.
Opening the input contact causes the output's ON
priority to be cancelled.
Priority ON
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
The Priority ON function forces the lighting priority and authorise other commands to be
circuit ON and maintains it ON.
followed again.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority.
• Inversion: the output is inverted in relation to
the status active during Priority.
Closing the input contact causes the output priority
to be switched to OFF.
Opening the input contact causes the cancellation
of the OFF output priority.
Priority OFF
The OFF Priority function forces the
lighting circuit OFF and maintains it OFF.
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
priority and authorise other commands to be
followed again.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority.
• Inversion: the output is inverted in relation to
the status active during Priority.
TRE400 / TRB501
7
6T 8074-02a
2.3 Dimmer Lighting functions
The dimmer Lighting functions command the dimmer Lighting output symbolized by the
icon on the right part of the display.
Refer to the configuration manuals for the various dimmer Lighting output devices for information on installing and configuring
these devices.
After numbering the push buttons, the functions and the links available appear in the left-hand part of the TX100 screen.
Selection of the
link type to be
created
Prog
X
1
59
95
Auto
All
Outputs
Inputs
The
Num
symbol indicates that it is a radio input. To select the functions, switch to the numbering mode.
The table here after shows all type of links compatible with the product:
Possible link type
ON
OFF
Link description
Output operation
The ON function switches the lighting
circuit ON.
The OFF function switches the lighting
circuit OFF.
The activation of the input causes the light at the
last memorised level to turn on.
Successive activations keep the light at the last
memorised level on.
The activation of the input causes the light to be
turned off to 0%.
Successive activations will keep the light off.
Toggle switch
The activation of the input causes the change
between Lighting at the last memorised level and
The Toggle switch function allows inverting Off at 0%.
the status of the lighting circuit.
Successive activations invert the state of the output
contact each time.
1 push button
dimmer
The activation of the input by a short key-press
causes the change between Lighting at the last
The 1-push button Dimmer function allows
memorised level and Off at 0%.
dimming the light with one single push
button.
The activation of the input by a long press causes
the level of lighting to increase or decrease.
2 push buttons
dimmer: Increase
The Increase Function allows increasing
the output level.
2 push buttons
The Reduction function allows decreasing
dimmer: Decrease the output level.
Switch
TRE400 / TRB501
The Switch function switches the lighting
circuit ON or OFF.
8
The activation of the input by a short press causes
lighting to return to the last memorised level.
The activation of the input by a long press causes
the lighting level to increase.
The activation of the input by a short press causes
the light to turn off.
The activation of the input by a long press causes
the lighting level to decrease.
The closing of the input contact causes the lighting
to return to the last memorised level.
The opening of the input contact causes the light to
turn off at 0%.
6T 8074-02a
Possible link type
Link description
Output operation
The Timer ON function switches the
lighting circuit ON for an adjustable time.
Select the time delay after confirming the
link:
Setting range [0 s - 24 h]
Timer ON
Not active, 1 s, 2 s, 3 s, 5 s, 10 s, 15 s, 20
s,
30 s, 45 s, 1 min, 1 min 15 s, 1 min 30 s,
2 min, 2 min 30 s, 3 min, 5 min, 15 min,
20 min, 30 min, 1 h, 2 h, 3 h, 5 h, 12 h,
24 h.
The Timer OFF function switches the
lighting circuit off for an adjustable time.
Select the time delay after confirming the
link:
Setting range [0 s - 24 h]
Timer OFF
Not active, 1 s, 2 s, 3 s, 5 s, 10 s, 15 s, 20
s,
30 s, 45 s, 1 min, 1 min 15 s, 1 min 30 s,
2 min, 2 min 30 s, 3 min, 5 min, 15 min,
20 min, 30 min, 1 h, 2 h, 3 h, 5 h, 12 h,
24 h.
The activation of the input by a short key-press <1 s
causes a timed illumination of the light (at the last
memorised level).
Interruption of the time delay:
The activation of the input by a long press >1 s
causes the time delay in progress to stop and
switching off at 0% (OFF).
Increase of the duration of the delay time:
Timer commands repeated n times during the first
ten seconds after the beginning of the time delay
multiply the duration of the time delay by n times the
value of the Timer parameter.
Restart of the timer:
A command given 10 sec after the beginning of the
time delay restarts the timer only once.
The activation by short key-press <1 s causes a
timed extinction of the light.
Interruption of the time delay:
The activation of the input by a long press >1 s
causes the time delay in progress to stop and the
light to turn on at the last memorised level.
Increase of the duration of the delay time:
Timer commands repeated n times during the first
ten seconds after the beginning of the time delay
multiply the duration of the time delay by n times the
value of the Timer parameter.
Restart of the timer:
A command given 10 sec after the beginning of the
time delay restarts the timer only once.
Closing the input contact causes the the output to
be prioritised to ON.
Opening the input contact causes the output's ON
priority to be cancelled.
Priority ON
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
The Priority ON function forces the lighting
priority and authorise other commands to be
circuit ON and maintains it ON.
followed again.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority.
• Inversion: the output is inverted in relation to
the status active during Priority.
Closing the input contact causes the output priority
to be switched to OFF.
Opening the input contact causes the cancellation
of the OFF output priority.
Priority OFF
The OFF Priority function forces the
lighting circuit OFF and maintains it OFF.
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
priority and authorise other commands to be
followed again.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority.
• Inversion: the output is inverted in relation to
the status active during Priority.
TRE400 / TRB501
9
6T 8074-02a
2.4 Shutters / Blinds function
The Shutters / Blinds function commands Shutters / Blinds outputs symbolized by the
icon in the right part of the display.
Refer to the configuration manuals for the various Shutters / Blinds output devices for information on installing and configuring
these devices.
After numbering the push buttons, the functions and the links available appear in the left-hand part of the TX100 screen.
Selection of the
link type to be
created
Prog
1
59
95
Auto
All
Inputs
Num
Outputs
The
symbol indicates that it is a radio input. To select the functions, switch to the numbering mode.
The table here after shows all type of links compatible with the product:
Possible link type
Link description
Output operation
In Shutters mode*:
• The activation of the input causes the timed
closing of the output contact Up* (Up fonction
of a shutter or blind).
Up / Stop
The Up / Stop function allows moving up
or stopping a shutter or a blind, or
inclining the slats of a blind.
In Blinds mode*
• The activation of the input by short key-press
causes the output contact Up to close briefly
(Blind slat angle function),
• The activation of the input by long key-press
causes the timed closing of the output contact
Up (Up fonction of a shutter or blind).
When a time delay is in progress, the activation of
the input by a short key-press causes the contact to
open (Stop function).
In Shutters mode*:
• The activation of the input causes the timed
closing of the output contact Down* (Down
function of a shutter or a blind).
Down / Stop
The Down function allows moving down
or stopping a shutter or a blind, or
inclining the slats of a blind.
In Blinds mode*:
• The activation of the input by a short keypress causes the output contact Down to
close briefly (Blind slat angle function),
• The activation of the input by long key-press
causes the timed closing of the output contact
Down (Up fonction of a shutter or blind).
When a time delay is in progress, the activation of
the input by a short key-press causes the contact to
open (Stop function).
Only the Shutter mode functions are active. The
blind Slat angle function is not accessible.
Up / Down / Stop
TRE400 / TRB501
The Up / Down function allows moving
up, down or stopping a shutter or a blind
with one single push button.
10
Successive activations cause the Shutter mode to
function following Up cycles (delayed closing of the
Up output) Stop (opening of the output contacts)
Down (delayed closing of the Down output)*.
6T 8074-02a
Possible link type
Link description
Output operation
Up
The Up function raises a roller shutter or
a blind.
Closing the input contact causes the timed closing
of the output contact Up (Up fonction of a shutter or
blind).
Down
Closing the input contact causes the timed closing
The Down function lowers a roller shutter
of the output contact Down (Down function of a
or a blind.
shutter or a blind).
Up / Down
The Up / Down function raises or lowers
a roller shutter or a blind.
Down / Up
Closing the input contact causes the timed closing
of the output contact Down (Down function for a
The Down / Up funtion is used to lower or
rolling shutter or blinds) and opening the input
to raise a rolling shutter or blind.
contact causes the timed closing of the output
contact Up (Up fonction of a shutter or blind).
Closing the input contact causes the timed closing
of the output contact Up (Up function for a rolling
shutter or blinds) and opening the input contact
causes the timed closing of the output contact
Down (Down function of a shutter or a blind).
The activation of the input causes the timed closing
of the output contact Up (Up fonction of a shutter or
blind)*.
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
priority and authorise other commands to be
followed again.
Up priority
The Priority up function forces the Up
movement of a shutter or a blind.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority,
• Inversion: the output is inverted in relation to
the status active during Priority (➜ Shutter
Down).
A priority is also cancelled by another Priority
command.
The activation of the input causes the timed closing
of the output contact Down (Down function of a
shutter or a blind)*.
Down priority
The Down Priority function forces the
Down movement of a shutter or a blind.
Priority is the function with the highest priority. Only
a cancellation command for the priority can end the
priority and authorise other commands to be
followed again.
After confirming the link, select the behaviour to
follow Priority Cancellation:
• Maintain: the output is maintained in the same
status as during Priority,
• Inversion: the output is inverted in relation to
the status active during Priority (➜ Shutter up).
A priority is also cancelled by another Priority
command.
* The modes and delay durations are parameterisable (see the TX100 configuration manuals for the Shutter / Blind output
actuators).
Possible link type
Wind alarm*
TRE400 / TRB501
Link description
Output operation
The Wind alarm function enables alarms
to be sent from automatic controls.
11
When the input contact is closed, the information
Alarm active (1) is sent.
When the input contact is opened, the information
Alarm inactive (0) is sent.
6T 8074-02a
Rain alarm*
The Rain alarm function enables alarms to
be sent from automatic controls.
When the input contact is closed, the information
Alarm active (1) is sent.
When the input contact is opened, the information
Alarm inactive (0) is sent.
* These functions have the highest priority. The Wind alarm function has a higher priority than the rain alarm function. No other
command is taken into consideration if an Alarm is active. Only the end of the alarm enables again the other commands.
TRE400 / TRB501
12
6T 8074-02a
2.5 Heating / Air-Conditioning function
The Heating / Air-Conditioning functions command a thermostat or a regulator symbolized by the
display.
icon on the right part of the
Refer to the thermostat, ambiance controller and regulator configuration manuals for information on installing and configuring
these devices.
Selection of the
link type to be
created
Prog
1
95
Auto
All
Inputs
The
Num
Outputs
symbol indicates that it is a radio input. To select the functions, switch to the numbering mode.
The table here after shows all type of links compatible with the product:
Possible link type
Link description
Output operation
The associated input contact is a switch or an
output from a programming clock.
Comfort / Night
set-point
The function Comfort / Night set-point
enables switching between the Comfort
and Night set-point modes.
Closing the contact causes Comfort mode to be
activated.
Opening the contact causes Night set-point mode to
be activated.
The effect of this command is cancelled by any
other mode activation command.
Override in
comfort mode
Override in
Economy mode
The function "Override in comfort mode"
activates the Comfort mode.
The function "Override in economy mode"
activates the economy mode.
Closing the input contact causes Comfort mode to
be activated.
The effect of this command is cancelled by any
other mode activation command.
Closing the input contact causes Night set-point
mode to be activated.
The effect of this command is cancelled by any
other mode activation command.
The associated input contact is a switch or an
output from a programming clock.
auto
Frost protection /
Auto
The Frost protection / Auto function
enables switching between the Frost
protection and Automatic modes.
Closing the contact causes the Frost protection
mode to be activated.
Opening the contact causes a return to Automatic
mode.
The effect of this command is cancelled by any
other mode activation command.
Frost protection
override
TRE400 / TRB501
The Frost protection override function is
used to activate the Frost protection
functon in the case of heating or the
Protection mode in the case of air
conditioning.
13
Closing the input contact causes the Frost
protection mode to be activated (Protection in case
of air-con).
The effect of this command is cancelled by any
other mode activation command.
6T 8074-02a
Possible link type
Auto
(Return home)
Standby override
Link description
Output operation
The Auto function cancels the override in
progress to return to the set point
corresponding to Automatic mode.
The Standby override funtion is used to
activate Standby mode.
The Comfort / Standby function enables
Comfort / Standby switching between the Comfort and
Standby modes.
Closing the input contact causes Auto mode to be
activated.
The effect of this command is cancelled by any
other mode activation command.
Closing the input contact causes Standby mode to
be activated.
The effect of this command is cancelled by any
other mode activation command.
Closing the input contact causes the setpoint to
switch between Comfort and Standby.
The setpoint changes each time the input contact is
closed.
The effect of this command is cancelled by any
other mode activation command.
The associated input contact is a switch or an
output from a programming clock.
Closing the contact causes the activation and
maintenance of Comfort mode.
Opening the contact causes the cancellation of the
priority and the return to the normally active mode.
Comfort Priority
The Comfort Priority function is used to
activate and maintain Comfort mode.
The Comfort Priority function is a function with a
higher priority than the override or time delay
commands. Only a cancellation command for the
priority can end the priority and authorise other
commands to be followed again.
The effect of the command is cancelled by any
other priority command (Night set-point, Frost
protection) or by a Stop or Windows contact
command.
The associated input contact is a switch or an
output from a programming clock.
Priority frost
protection
The Frost protection override function is
used to activate the Frost protection
functon in the case of heating or the
Protection mode in the case of air
conditioning.
Closing the contact causes Frost protection mode
to be activated and maintained (Protection in case
of air-con).
Opening the contact causes the cancellation of the
priority and the return to the normally active mode.
The Priority frost protection function is a function
with a higher priority than override or time delay
commands. Only a cancellation command for the
priority can end the priority and authorise other
commands to be followed again.
The effect of the command is cancelled by any
other priority command (Night set-point, Frost
protection) or by a Stop or Windows contact
command.
TRE400 / TRB501
14
6T 8074-02a
2.6 Scene Functions
■ Link creation
The Scene function groups a set of outputs. These outputs can be set to an adjustable predefined status. Pressing a push button
activates a scene. Each output may be integrated into 8 different scenes.
It is possible to create links between a push-button and the outputs which are to be part of the scene by selecting a Scene
function (number 1 to 8).
Easy Prog
Selection of the link
type to be created
3
21
6
29
Auto
Possible link type
...
Scene 1 to 8
26
Expert
Link description
Num
Output operation
The Scene function groups a set of
outputs.
The status of each output can be defined:
These outputs can be set to an adjustable
- By output settings,
predefined status.
- Via learning, with the push buttons on the insPressing a push button activates a scene.
tallation or on the front of certain devices.
Each output may be integrated into
8 different scenes.
■ Learning and memorisation of scenes
This procedure enables a scene to be modified and memorised by locally using the push buttons in the room, on a remote control
RF.
• Activate the scene with a short key-press on the transmitter that launches the scene,
• Put the outputs (Lighting, Shutters, Thermostat, etc.) into the sesired status using the usual local controls (push button,
remote control, etc.),
• Memorise the status of the inputs with a long key-press greater than 5s on the transmitter that launches the scene. The
memorisation is indicated by the momentary activation of the outputs.
2.7 Repeater Function
It increases the radio range of the system by re-sending the messages received by the product. Inactive by default, the Repeater
function can be activated from the Product Management / TX100 Repeater menu.
TRE400 / TRB501
15
6T 8074-02a
3. "+ info" and "expert" mode of the TX100
3.1 Mode + Info
The mode +Info can be accessed in the Prog and Visu modes of the TX100. This display mode is active for the installation
products until it is deactivated.
Prog
1
Auto
Visu
1
+ info
1
Num
Auto
+ info
Outputs
The +Info mode allows the status indication to be linked from an output to a viewing product: Area controller, LED output, etc.
The status indication sends the current status over the network each time the status changes.
1
The status indication is represented by the symbol
.
The status indication adds itself to the list of inputs on the left of the TX100 screen with the same number as the output.
3.2 Expert mode
■ General points
The Expert mode allows:
• Non-configurable KNX products to be integrated by ETS (viewing tool, Internet gateway, domovea) in the installation,
• Specific links, not available in the Standard configuration mode, to be created.
In Expert mode, the functions are displayed through the communication objects used in the configuration ETS mode. The objects
appear as a list located under the input and output numbers.
Expert prog
11
11
OnOff
OnOff
Timer
Timer
Forced
Forced
Scene
Scene
On Off
Standard
The Expert mode allows links to be established between objects with the same format by giving them the same group address.
TRE400 / TRB501
16
6T 8074-02a
■ List of the available objects
On / Off and Dimmer Lighting controls
Designation
TX100
Designation ETS
Function
Format
Description
OnOff
On/Off
ON / OFF
EIS1 1 bit
Allows an ON / OFF command to be
transmitted.
IOnOff
InfoOn/Off
ON / OFF information
EIS1 1 bit
Indicates the output's status.
DimCtrl
DimmingCtrl
Dimming command
1 bit
Allows changing the output level of a
dimmer.
Timer
TimedStartstop
Timer
EIS1 1 bit
Allows you to activate or interrupt the
timer.
Forced
Forced
Priority
EIS2 2 bit
Forces an output.
Shutters / Blinds control
Designation
TX100
Designation ETS
Function
Format
Description
StepStop
StepStop
Slat angle
1 bit
Sends a slat angle command for a
blind.
UpDown
UpDown
Up / Down
1 bit
Sends an Up or Down command for a
roller shutter or a blind.
IUpDown
InfoMoveUpDown
Up / Down information
1 bit
Provides the status of the Up / Down
output (control 1 BP).
Forced
Forced
Priority
EIS2 2 bit
Forces an Up or Down command.
Wind Alm
Wind Alm
Wind alarm
1 bit
The WindAlm object enables the wind
alarm to be activated.
RainAlm
RainAlm
Rain alarm
1 bit
The RainAlm object enables the rain
alarm to be activated.
Heating / Air-Conditioning control
Designation
TX100
Designation ETS
Function
Format
Description
HvacMode
HvacMode
Heating mode
1 byte
Activates a heating or air-conditioning
mode (Comfort, Reduced, ...).
IOnOff
InfoOn/Off
ON / OFF information
EIS1 1 bit
Indicates the output's status.
Timer
TimedStartstop
Timer
EIS1 1 bit
Starts a delayed deviation.
Forced
Forced
Priority
EIS2 2 bit
Forces a heating or air-conditioning
mode.
Scene
Designation
TX100
Scene
TRE400 / TRB501
Designation ETS
SceneNumber
Function
Format
Scene
1 byte
17
Description
Activates the scene by its number.
6T 8074-02a
4. Factory reset
This function enables the device to be returned to its initial configuration (configuration when it came out of the factory). After a
device reset, the device can be re-used in a new installation. The factory reset can either be performed directly on the product, or
using the TX100 Product Management / Factory Reset menu. The latter solution is recommended if the product is part of the
installation configured by TX100.
This function is started by the Slat angle / Stop objectOperating modesRight
4.1 Factory reset using the TX100
The device belongs to the installation: it appears in the Reset menu's list of devices that can be reset to Factory configuration.
• Select the product in the list,
• Press
and confirm the erasing.
After a device reset, the installation must be learnt again in order to relocate the devices reset to Factory configuration.
4.2 Factory reset on the product
The factory reset can be performed on the product, if the data of the TX100 project has been lost or if the product is not part of the
installation.
Factory reset on the product:
• Press and hold the "Cfg" button (> 10 seconds), release the button as soon as the "Cfg" LED starts to flash,
• Wait for the "Cfg" LED to go out, indicating that the factory reset is complete.
To reuse with TX100, a product that has already been programmed in another installation whatever the inital
configuration (quicklink , TX100 or ETS), it is necessary to carry out a factory reset on the device.
Fot the combined input / output products, the factory reset will reinstall the local commands (the input of the product controls the
load connected with the product). To associate a different function to these inputs with the TX100, the local control link must dirst
be deleted (select the input and output numbers for the product and delete the link).
5. Main characteristics
Product
TRE400 / TRB501
Max. number of group addresses
87
Max. number of links
95
TRE400 / TRB501
18
6T 8074-02a
TRE400 / TRB501
19
6T 8074-02a