TPLP Pre-Assembled - Trenton Refrigeration


Add to my manuals
28 Pages

advertisement

TPLP Pre-Assembled - Trenton Refrigeration | Manualzz
TPLP
Pre-Assembled
Low Profile
Evaporators
PRODUCT DATA &
INSTALLATION
Bulletin T30-TPLP-PDI-11
Part #1087152
PRODUCT SUPPORT
web: t-rp.com/tplp
email: [email protected]
call: 1-844-893-3222 x520
scan:
Air & Electric Defrost
Electrical Power:
115/1/60, 208-230/1/60, 208-230/3/60, 460/1/60
See Page 22 for details
CONTENTS
Page
Nomenclature...................................................................................................................2
Features & Options.......................................................................................................... 2
Pre-Assembled Features................................................................................................. 3
Capacity Data..................................................................................................................
4
Electrical Data.................................................................................................................. 5-7
Wiring Diagrams - Models with standard PSC motors .................................................... 8-15
Wiring Diagrams - Models with optional EC Motors /
.............................. 16-19
Shipping Weights............................................................................................................. 20
Dimensional Data.............................................................................................................21-22
Recommended Expansion Valve Selections................................................................... 23
Installation Instructions....................................................................................................24-25
Project Information.......................................................................................................... 26
Product Support Resources: Service Parts, Troubleshooting, Warranty, etc.................
27
“As Built” Service Parts....................................................................................................Back
23/06/17
NOMENCLATURE
T
P
LP
3 15 L E
S2 B
R6 - PSC
Motor Designation:
PSC = PSC
EC2 = SmartSpeed ECM
T = Trenton
Pre-Assembled
Refrigerant Designation:
R2 = R407A / R407C / R22 / R448A
R6 = R404A
R7 = R407A / R448A
Low Profile Evaporator
Number of Fans
Generation:
Nominal Capacity:
x 1000 @ 10°F TD, Btu/H, R404A
B = 2nd
Voltage:
S1 = 115/1/60 (air defrost models only)
S2 = 208-230/1/60
S4 = 460/1/60 (2 to 6 fan models only)
T3 = 208-230/3/60
Application Range:
M = Medium to High Temp 6 FPI (10°F to 45°F (-12°C to 7°C) Evap Temp)
L = Low Temp 6 FPI (-40°F to 0°F(-40°C to -17°C) Evap Temp)
V = Low Temp 4 FPI (-40°F to 0°F (-40°C to -17°C) Evap Temp)
Defrost*:
A = Air
E = Electric
STANDARD FEATURES
• Compitable with Low GWP Refrigerants
• Schrader valve on suction header
• High efficiency and high strength fan guard
• Positive slope, hinged drain pan
• Front access
• Central drain connections (approximate)
• Internally enhanced tubing
• Universal drain fitting
• Convenient mounting brackets
• Large 3/4” ID (3/4” MPT) drain hole
• Ample electrical and header compartments
• Factory installed expansion valve,
• PSC Motors
solenoid valve and room thermostat
• Liquid line solenoid valve wire harness factory
installed
AVAILABLE OPTIONS
• EC motors with patented SmartSpeed®
Technology. See page 16
• Corrosion protection: alternate fin materials and
coatings
• Hot gas loop pan with hot gas defrost models
• Additional options available, please contact
factory
• Factory installed expansion valve,
solenoid valve and room thermostat
• Wire fan guard
T30-TPLP-PDI-11
-2-
23/06/17
TPLP
PRE-ASSEMBLED FEATURES
60Hz
Thermostat Mounted
on Front of Unit
Solenoid Valve and
TXV Mounted
Solenoid Valve Wire
pulled through and
labeled on each end
Schrader Valve
Located Outside
T30-TPLP-PDI-11
-3-
23/06/17
TPLP
60Hz
CAPACITY DATA - ALL MODELS
Medium Temperature Models - Capacity @ 6 F.P.I. *
Medium Temp. Models TPLP
Number Of Fans
R407A
R448A
Evap
R407C
Capacity
Temp.
BTUH
25°F
R404A
(WATTS)
(-4°C)
R507
R22
Air Flow
CFM (L/S)
Refrigerant **
Charge R407A
LB. (KG)
104M
1
4090
(1197)
3870
(1134)
4300
(1260)
4090
(1197)
1010
(477)
0.7
(0.3)
106M
1
5230
(1530)
4950
(1449)
5500
(1610)
5230
(1530)
950
(458)
1.1
(0.5)
107M
1
6460
(1891)
6120
(1791)
6800
(1990)
6460
(1891)
900
(425)
1.5
(0.7)
209M
2
8170
(2394)
7740
(2268)
8600
(2520)
8170
(2394)
2020
(953)
1.3
(0.6)
211M
2
10450
(3059)
9900
(2898)
11000
(3220)
10500
(3059)
1910
(901)
1.4
(0.6)
214M
2
13300
(3895)
12600
(3690)
14000
(4100)
13300
(3895)
1800
(850)
2.0
(0.9)
317M
3
16200
(4731)
15400
(4482)
17000
(4980)
16200
(4731)
2860
(1350)
3.0
(1.4)
320M
3
19000
(5567)
18100
(5274)
20000
(5860)
19000
(5567)
2700
(1274)
4.0
(1.8)
423M
4
21900
(6403)
20800
(6066)
23000
(6740)
21900
(6403)
3810
(1798)
3.9
(1.8)
426M
4
24700
(7230)
23500
(6849)
26000
(7610)
24700
(7230)
3600
(1699)
3.3
(1.5)
532M
5
30400
(8902)
28900
(8433)
32000
(9370)
30400
(8902)
4500
(2124)
6.5
(2.9)
639M
6
37100
(10830)
35200
(10260)
39000
(11400)
37100
(10830)
5400
(2549)
7.8
(3.5)
314L
3
13300
(3895)
14000
(4100)
2860
(1350)
3.0
(1.4)
317L
3
16200
(4731)
17000
(4980)
2700
(1274)
4.0
(1.8)
419L
4
18100
(5292)
19000
(5570)
3810
(1798)
3.9
(1.8)
422L
4
20900
(6118)
22000
(6440)
3600
(1699)
3.3
(1.5)
527L
5
25700
(7515)
27000
(7910)
4500
(2124)
6.5
(2.9)
631L
6
29500
(8626)
31000
(9080)
5400
(2549)
7.8
(3.5)
312V
3
11400
(3344)
12000
(3520)
2860
(1350)
3.0
(1.4)
315V
3
14300
(4171)
15000
(4390)
2700
(1274)
4.0
(1.8)
416V
4
15200
(4456)
16000
(4690)
3810
(1798)
3.9
(1.8)
419V
4
18100
(5292)
19000
(5570)
3600
(1699)
3.3
(1.5)
523V
5
21900
(6403)
23000
(6740)
4500
(2124)
6.5
(2.9)
627V
6
25700
(7515)
27000
(7910)
5400
(2549)
7.8
(3.5)
Low Temperature Models - Capacity @ 6 F.P.I. *
Low Temp. Models TPLP
Number Of Fans
Evap R407A
Capacity
Temp. R448A
BTUH
-20°F
R404A
(WATTS)
(-29°C)
R507
Air Flow
104L
1
3610
(1055)
3800
(1110)
1010
(477)
0.7
(0.3)
CFM (L/S)
Refrigerant **
Charge R407A
LB. (KG)
105L
1
4560
(1340)
4800
(1410)
950
(458)
1.1
(0.5)
106L
1
5510
(1615)
5800
(1700)
900
(425)
1.5
(0.7)
207L
2
7030
(2062)
7400
(2170)
2020
(953)
1.3
(0.6)
209L
2
8550
(2508)
9000
(2640)
1910
(901)
1.4
(0.6)
211L
2
10500
(3059)
11000
(3220)
1800
(850)
2.0
(0.9)
Low Temperature Models - Capacity @ 4 F.P.I. *
Low Temp. 4 FPI Models TPLP
Number Of Fans
Evap R407A
Capacity
Temp. R448A
BTUH
-20°F
R404A
(WATTS)
(-29°C)
R507
Air Flow
CFM (L/S)
Refrigerant **
Charge R407A
LB. (KG)
103V
1
2850
(836)
3000
(880)
1010
(477)
0.7
(0.3)
104V
1
3900
(1140)
4100
(1200)
950
(458)
1.1
(0.5)
105V
1
4750
(1397)
5000
(1470)
900
(425)
1.5
(0.7)
206V
2
6080
(1786)
6400
(1880)
2020
(953)
1.3
(0.6)
208V
2
7410
(2176)
7800
(2290)
1910
(901)
1.4
(0.6)
209V
2
8840
(2584)
9300
(2720)
1800
(850)
2.0
(0.9)
Capacities rated using 10°F (5.6°C) TD & 100°F (38°C) liquid temperature.
Capacities at other TD within a range of 8 to 15 °F (4.4 to 8.3°C) are directly proportional to TD, or use formula: Capacity = Rated capacity ÷ 10 x TD.
For capacities at TD outside of range 8 to 15 °F (4.4 to 8.3°C), or liquid temperature lower than 75°F (24°), consult factory.
Capacities for R448A, R407A and R407C are based on mean temperature. Mean temperature is the average temperature between the saturated suction
temperature and the temperature feeding the evaporator. For dew point ratings, consult factory.
For R449A, use R448A data.
* CAPACITY CORRECTION FACTORS FOR LOW TEMPERATURE UNITS
SATURATED SUCTION
TEMPERATURE °F (°C)
0
(-17.8)
-10
(23.3)
-20
(-28.9)
-30
(-34.4)
-40
(-40)
FACTOR
1.06
1.03
1.0
0.92
0.85
** REFRIGERANT CHARGE CONVERSION FACTORS
R448A
R407C
R404A
R507
R22
R134a
0.96
0.99
0.92
0.93
1.02
1.03
NO CORRECTION FACTOR REQUIRED FOR MEDIUM TEMP. UNITS
T30-TPLP-PDI-11
-4-
23/06/17
TPLP
60Hz
ELECTRICAL DATA
115/1/60 - AIR DEFROST MODELS
FAN MOTORS
MODEL
FPI
PSC MOTORS
TPLP
QTY.
104MAS1
106MAS1
107MAS1
209MAS1
211MAS1
214MAS1
317MAS1
320MAS1
423MAS1
426MAS1
532MAS1
639MAS1
1
1
1
2
2
2
3
3
4
4
5
6
6
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
1.0
1.0
1.0
2.0
2.0
2.0
3.0
3.0
4.0
4.0
5.0
6.0
EC MOTORS
MIN. CIRC. MAX. FUSE
WATTS
AMPACITY (A)
(AMPS)
100
1.3
15
100
1.3
15
100
1.3
15
200
2.3
15
200
2.3
15
200
2.3
15
300
3.3
15
300
3.3
15
400
4.3
15
400
4.3
15
500
5.3
15
600
6.3
15
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
1.0
1.0
1.0
2.0
2.0
2.0
3.0
3.0
4.0
4.0
5.0
6.0
WATTS
60
60
60
120
120
120
180
180
240
240
300
360
MIN. CIRC. MAX. FUSE
AMPACITY (A)
(AMPS)
1.3
15
1.3
15
1.3
15
2.3
15
2.3
15
2.3
15
3.3
15
3.3
15
4.3
15
4.3
15
5.3
15
6.3
15
ELECTRICAL DATA
208-230/1/60 - AIR DEFROST MODELS
FAN MOTORS
MODEL
FPI
PSC MOTORS
TPLP
QTY.
104MAS2
106MAS2
107MAS2
209MAS2
211MAS2
214MAS2
317MAS2
320MAS2
423MAS2
426MAS2
532MAS2
639MAS2
1
1
1
2
2
2
3
3
4
4
5
6
6
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
0.5
0.5
0.5
1.0
1.0
1.0
1.5
1.5
2.0
2.0
2.5
3.0
WATTS
100
100
100
200
200
200
300
300
400
400
500
600
EC MOTORS
MIN. CIRC.
MAX. FUSE
AMPACITY (A)
(AMPS)
0.6
15
0.6
15
0.6
15
1.1
15
1.1
15
1.1
15
1.6
15
1.6
15
2.1
15
2.1
15
2.6
15
3.1
15
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
0.6
0.6
0.6
1.2
1.2
1.2
1.8
1.8
2.4
2.4
3.0
3.6
WATTS
60
60
60
120
120
120
180
180
240
240
300
360
MIN. CIRC. MAX. FUSE
AMPACITY (A)
(AMPS)
0.8
15
0.8
15
0.8
15
1.4
15
1.4
15
1.4
15
2.0
15
2.0
15
2.6
15
2.6
15
3.2
15
3.8
15
ELECTRICAL DATA
460/1/60 - AIR DEFROST MODELS
FAN MOTORS
MODEL
FPI
T30-TPLP-PDI-11
PSC MOTORS
TPLP
QUANTITY
209MAS4
211MAS4
214MAS4
317MAS4
320MAS4
423MAS4
426MAS4
532MAS4
639MAS4
2
2
2
3
3
4
4
5
6
6
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
0.8
0.8
0.8
1.2
1.2
1.6
1.6
2.0
2.4
-5-
WATTS
200
200
200
300
300
400
400
500
600
MIN. CIRC. MAX. FUSE
AMPACITY (A)
(AMPS)
0.9
15
0.9
15
0.9
15
1.3
15
1.3
15
1.7
15
1.7
15
2.1
15
2.5
15
23/06/17
TPLP
FAN MOTORS
MODEL
PSC MOTORS
FPI
60Hz
ELECTRICAL DATA 208-230/1/60 & 208-230/3/60
ELECTRIC DEFROST MODELS
TPLP
QTY.
104ME*
106ME*
107ME*
1
1
1
DEFROST HEATERS
EC MOTORS
MAX.
FLA
MCA
HP
WATTS
FUSE
TOTAL
(A)
(AMPS)
1/15
0.5
100
0.6
15
1/15
0.5
100
0.6
15
1/15
0.5
100
0.6
15
208-230/1/60
208-230/3/60
MAX. TOTAL
MAX.
MAX.
FLA
MCA
TOTAL MCA
TOTAL MCA
HP
WATTS
FUSE WATTS
FUSE
FUSE
TOTAL
(A)
AMPS (A)
AMPS (A)
(AMPS)
(AMPS)
(AMPS)
1/15 0.6
60
0.8
15
1060
4.6
5.8
15
3.0
3.8
15
1/15 0.6
60
0.8
15
1060
4.6
5.8
15
3.0
3.8
15
1/15 0.6
60
0.8
15
1060
4.6
5.8
15
3.0
3.8
15
209ME*
2
1/15
1.0
200
1.1
15
1/15
1.2
120
1.4
15
1890
8.2
10.3
15
5.3
6.7
15
211ME*
214ME*
2
2
1/15
1/15
1.0
1.0
200
200
1.1
1.1
15
15
1/15
1/15
1.2
1.2
120
120
1.4
1.4
15
15
1890
1890
8.2
8.2
10.3
10.3
15
15
5.3
5.3
6.7
6.7
15
15
3
3
1/15
1/15
1.5
1.5
300
300
1.6
1.6
15
15
1/15
1/15
1.8
1.8
180
180
2.0
2.0
15
15
2730
2730
11.9
11.9
14.8
14.8
15
15
7.7
7.7
10
10
15
15
423ME*
426ME*
4
4
1/15
1/15
2.0
2.0
400
400
2.1
2.1
15
15
1/15
1/15
2.4
2.4
240
240
2.6
2.6
15
15
3560
3560
15.5
15.5
19.3
19.3
20
20
10
10
12
12
15
15
532ME*
5
1/15
2.5
500
2.6
15
1/15
3.0
300
3.2
15
4400
19.1
23.9
25
12
15.1
20
639ME*
6
1/15
3.0
600
3.1
15
1/15
3.6
360
3.8
15
5230
22.7
28.4
30
15
18
20
104LE*
105LE*
1
1
1/15
1/15
0.5
0.5
100
100
0.6
0.6
15
15
1/15
1/15
0.6
0.6
60
60
0.75
0.75
15
15
1060
1060
4.6
4.6
5.8
5.8
15
15
3.0
3.0
3.8
3.8
15
15
106LE*
1
1/15
0.5
100
0.6
15
1/15
0.6
60
0.75
15
1060
4.6
5.8
15
3.0
3.8
15
207LE*
209LE*
2
2
1/15
1/15
1.0
1.0
200
200
1.1
1.1
15
15
1/15
1/15
1.2
1.2
120
120
1.4
1.4
15
15
1890
1890
8.2
8.2
10.3
10.3
15
15
5.3
5.3
6.7
6.7
15
15
2
1/15
1.0
200
1.1
15
1/15
1.2
120
1.4
15
1890
8.2
10.3
15
5.3
6.7
15
3
3
4
4
1/15
1/15
1/15
1/15
1.5
1.5
2.0
2.0
300
300
400
400
1.6
1.6
2.1
2.1
15
15
15
15
1/15
1/15
1/15
1/15
1.8
1.8
2.4
2.4
180
180
240
240
2.0
2.0
2.6
2.6
15
15
15
15
2730
2730
3560
3560
11.9
11.9
15.5
15.5
14.8
14.8
19.3
19.3
15
15
20
20
7.7
7.7
10
10
10
10
12
12
15
15
15
15
527LE*
631LE*
103VE*
104VE*
105VE*
5
6
1
1
1
1/15
1/15
1/15
1/15
1/15
2.5
3.0
0.5
0.5
0.5
500
600
100
100
100
2.6
3.1
0.6
0.6
0.6
15
15
15
15
15
1/15
1/15
1/15
1/15
1/15
3.0
3.6
0.6
0.6
0.6
300
360
60
60
60
3.2
3.8
0.75
0.75
0.75
15
15
15
15
15
4400
5230
1060
1060
1060
19.1
22.7
4.6
4.6
4.6
23.9
28.4
5.8
5.8
5.8
25
30
15
15
15
12
15
3.0
3.0
3.0
15.1
18
3.8
3.8
3.8
20
20
15
15
15
206VE*
208VE*
209VE*
2
2
2
1/15
1/15
1/15
1.0
1.0
1.0
200
200
200
1.1
1.1
1.1
15
15
15
1/15
1/15
1/15
1.2
1.2
1.2
120
120
120
1.4
1.4
1.4
15
15
15
1890
1890
1890
8.2
8.2
8.2
10.3
10.3
10.3
15
15
15
5.3
5.3
5.3
6.7
6.7
6.7
15
15
15
3
3
1/15
1/15
1.5
1.5
300
300
1.6
1.6
15
15
1/15
1/15
1.8
1.8
180
180
2.0
2.0
15
15
2730
2730
11.9
11.9
14.8
14.8
15
15
7.7
7.7
10
10
15
15
416VE*
419VE*
4
4
1/15
1/15
2.0
2.0
400
400
2.1
2.1
15
15
1/15
1/15
2.4
2.4
240
240
2.6
2.6
15
15
3560
3560
15.5
15.5
19.3
19.3
20
20
10
10
12
12
15
15
523VE*
627VE*
5
6
1/15
1/15
2.5
3.0
500
600
2.6
3.1
15
15
1/15
1/15
3.0
3.6
300
360
3.2
3.8
15
15
4400
5230
19.1
22.7
23.9
28.4
25
30
12
15
15.1
18
20
20
317ME*
320ME*
211LE*
314LE*
317LE*
419LE*
422LE*
312VE*
315VE*
6
6
4
* = S2 or T3. Refer to Nomenclature for details
T30-TPLP-PDI-11
-6-
23/06/17
TPLP
FAN MOTORS
MODEL
FPI
QTY.
209MES4
211MES4
214MES4
317MES4
320MES4
423MES4
426MES4
532MES4
639MES4
207LES4
209LES4
211LES4
314LES4
317LES4
419LES4
422LES4
527LES4
631LES4
206VES4
208VES4
209VES4
312VES4
315VES4
416VES4
419VES4
523VES4
627VES4
2
2
2
3
3
4
4
5
6
2
2
2
3
3
4
4
5
6
2
2
2
3
3
4
4
5
6
6
6
4
DEFROST HEATERS
PSC MOTORS
TPLP
T30-TPLP-PDI-11
60Hz
ELECTRICAL DATA - 460/1/60
ELECTRIC DEFROST MODELS
HP
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
1/15
FLA
TOTAL
0.8
0.8
0.8
1.2
1.2
1.6
1.6
2.0
2.4
0.8
0.8
0.8
1.2
1.2
1.6
1.6
2.0
2.4
0.8
0.8
0.8
1.2
1.2
1.6
1.6
2.0
2.4
WATTS
200
200
200
300
300
400
400
500
600
200
200
200
300
300
400
400
500
600
200
200
200
300
300
400
400
500
600
MCA
(A)
0.9
0.9
0.9
1.3
1.3
1.7
1.7
2.1
2.5
0.9
0.9
0.9
1.3
1.3
1.7
1.7
2.1
2.5
0.9
0.9
0.9
1.3
1.3
1.7
1.7
2.1
2.5
-7-
MAX. FUSE
(AMPS)
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
TOTAL
WATTS
TOTAL
AMPS
MCA
(A)
MAX. FUSE
(AMPS)
1890
1890
1890
2730
2730
3560
3560
4400
5230
1890
1890
1890
2730
2730
3560
3560
4400
5230
1890
1890
1890
2730
2730
3560
3560
4400
5230
4.1
4.1
4.1
5.9
5.9
7.7
7.7
9.6
11.4
4.1
4.1
4.1
5.9
5.9
7.7
7.7
9.6
11.4
4.1
4.1
4.1
5.9
5.9
7.7
7.7
9.6
11.4
5.1
5.1
5.1
7.4
7.4
9.7
9.7
12.0
14.2
5.1
5.1
5.1
7.4
7.4
9.7
9.7
12.0
14.2
5.1
5.1
5.1
7.4
7.4
9.7
9.7
12.0
14.2
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
23/06/17
TPLP
PSC
60Hz
WIRING DIAGRAM - 115/1/60, 208-230/1/60
STANDARD PSC MOTORS
AIR DEFROST MODELS
WITHOUT DEFROST TIME CLOCK
WITH DEFROST TIME CLOCK
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
REQUIREMENTS
L1
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
REQUIREMENTS
L1
L2(N)
L2(N)
GND
GND
TM
3
4
X
2
1
FUSE OR
CIRCUIT
BREAKER
NOTE #3
FUSE OR
CIRCUIT
BREAKER
NOTE #3
N
OMIT
2ND FUSE
IF(N)
OMIT 2ND
FUSE
IF(N)
GND
F
4
TO MULTIPLE EVAPS
(IF APPLIC)
F
4
PUMP DOWN
SWITCH
(IF USED)
TO MULTIPLE
EVAPORATORS (IF APPLIC)
SPACE
THERMOSTAT
NOTE #4
LIQUID LINE
SOLENOID VALVE
NOTE #4
LIQUID LINE
SOLENOID VALVE
NOTE #4
SPACE
THERMOSTAT
NOTE #4
N.C.
N.C.
EVAPORATOR
EVAPORATOR
4
F
4
TERMINAL BOARD
F
TERMINAL BOARD
GND.
GND.
FAN MOTOR
POWER
PLUGS
FAN MOTOR
POWER
PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
TERMINALS
NOTES
-COMPONENT TERMINAL
1). USE COPPER CONDUCTORS ONLY
-TERMINAL BLOCK TERMINAL
2). USE 75°C WIRE (OR HIGHER)
CONDUCTORS/WIRING
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND DEFROST
HEATERS MUST NOT EXCEED MAXIMUM
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY OR
BY OTHERS
4). MAY BE FACTORY INSTALLED-MOUNTED AND
WIRED ON EVAPORATOR .
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
1-LP AIR 09/06
T30-TPLP-PDI-11
-8-
23/06/17
TPLP
PSC
60Hz
WIRING DIAGRAM - 460/1/60
STANDARD PSC MOTORS
AIR DEFROST MODELS
WITHOUT DEFROST TIME CLOCK
WITH DEFROST TIME CLOCK
460-1-60 Hz
380/400-1-50Hz
L1
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
GND
3
4
380/400-1-50Hz
L2(N)
L1
GND
TM
1
460-1-60 Hz
CONTROL VOLTAGE
L2
L1
CONTROL VOLTAGE
L2
GND
GND
FUSE OR
CIRCUIT
BREAKER
NOTE #3
X
2
FUSE OR
CIRCUIT
BREAKER
NOTE #3
OMIT 2ND
FUSE
IF(N)
N
L2(N)
L1
OMIT
2ND FUSE
IF(N)
GND
M2
M1
M2
M1
TO MULTIPLE
EVAPORATORS (IF APPLIC)
PUMP DOWN
SWITCH
(IF USED)
TO MULTIPLE
EVAPORATORS (IF APPLIC)
LIQUID LINE
SPACE
THERMOSTAT SOLENOID VALVE
NOTE #4
NOTE #4
LIQUID LINE
SPACE
THERMOSTAT SOLENOID VALVE
NOTE #4
NOTE #4
N.C.
N.C.
M1 M2
EVAPORATOR
EVAPORATOR
4
TERMINAL BOARD
GND.
M1 M2
N
GND.
FAN MOTOR
POWER
PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
N
FAN MOTOR
POWER
PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE
FOR MOTOR
QUANTITY
TERMINALS
NOTES
-COMPONENT TERMINAL
1). USE COPPER CONDUCTORS ONLY
-TERMINAL BLOCK TERMINAL
2). USE 75°C WIRE (OR HIGHER)
CONDUCTORS/WIRING
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND DEFROST
HEATERS MUST NOT EXCEED MAXIMUM
VALUE SHOWN ON EVAPORATOR NAMEPLATE.
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY OR
BY OTHERS
4). MAY BE FACTORY INSTALLED-MOUNTED AND
WIRED ON EVAPORATOR .
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
6-LP 460 AIR 09/06
T30-TPLP-PDI-11
4
TERMINAL BOARD
-9-
23/06/17
TPLP
PSC
WIRING DIAGRAM - 208-230/1/60
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR 10A MAX.
FOR ALL MODELS WITHOUT DEFROST HEATER CONTACTOR
USING MAXIMUM 15A HEATER OVERCURRENT PROTECTION
REFER TO EVAPORATOR
NAMEPLATE FOR ELECTRICAL
REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
L1 L2
GND
TM
3
1
4
FUSE OR
CIRCUIT
BREAKER
X
2
N
15A
COMPR INTERLOCK
(IF USED)
SPACE
THERMOSTAT
NOTE #4
WARNING
EVAP FIELD MODIFICATION
MUST BE MADE
N.C.
SEE NOTE:
LIQUID LINE
SOL VALVE
NOTE #4
PUMP DOWN
SWITCH
(IF USED)
1
RELOCATE WHITE WIRE FROM
2
INSTALL ORANGE JUMPER
N TO H1 AS SHOWN
(SUPPLIED LOOSE)
FROM H2 TO N
2
ORANGE JUMPER
4
X
F
BN
GND.
N
H2
H1
3
H3
1
DT
C
BK
RD
FD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
YL
WH
HEATER
LIMIT
SWITCH
DT-DEFROST TERM
FD-FAN DELAY
(10.0A MAX.)
DEFROST HEATERS
FAN MOTOR
POWER PLUGS
FAN
MTR
1
FAN
MTR
2
FAN
MTR
6
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
NOTES
EVAPORATOR
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
2-LP ED 12/07
T30-TPLP-PDI-11
- 10 -
23/06/17
TPLP
PSC
WIRING DIAGRAM - 208-230/1/60
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
FOR ALL MODELS USING DEFROST HEATER CONTACTOR
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
L1 L2
GND
TM
3
1
4
X
2
FUSE OR
CIRCUIT
BREAKER
NOTE #3
FUSE OR
CIRCUIT
BREAKER
NOTE #3
N
L1
L2
COMPR INTERLOCK
(IF USED)
T1
SPACE
THERMOSTAT
NOTE #4
LIQUID LINE
SOL VALVE
NOTE #4
X
F
N
BN
RD
DT
GND.
T2
N.C.
PUMP DOWN
SWITCH
(IF USED)
4
DEFROST HEATER
CONTACTOR
C
3
H2
H1
H3
YL
WH
C
BK
FD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY
HEATER
LIMIT
SWITCH
(10.0A MAX.)
DEFROST HEATERS
FAN MOTOR
POWER PLUGS
FAN
MTR
1
FAN
MTR
2
FAN
MTR
6
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
NOTES
EVAPORATOR
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
3-LP ED CONTACTOR SINGLE 12/07
T30-TPLP-PDI-11
- 11 -
23/06/17
TPLP
PSC
WIRING DIAGRAM - 208-230/3/60
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
FOR ALL MODELS USING 3 PHASE DEFROST HEATER CONTACTOR
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
L1 L2 L3
GND
TM
3
1
4
X
2
FUSE OR
CIRCUIT
BREAKER
NOTE #3
FUSE OR
CIRCUIT
BREAKER
NOTE #3
N
L1
L2
L3
T1
T2
T3
C
COMPR INTERLOCK
(IF USED)
SPACE
THERMOSTAT
NOTE #4
X
F
N
BN
RD
DT
GND.
N.C.
LIQUID LINE
SOL VALVE
NOTE #4
PUMP DOWN
SWITCH
(IF USED)
4
DEFROST HEATER
CONTACTOR
3
H2
H1
H3
YL
WH
C
BK
FD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY
HEATER
LIMIT
SWITCH
(10.0A MAX.)
DEFROST HEATERS
FAN MOTOR
POWER PLUGS
FAN
MTR
1
FAN
MTR
2
FAN
MTR
6
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
NOTES
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
3A-LP ED 3ph.CONTACTOR SINGLE 12/07
T30-TPLP-PDI-11
EVAPORATOR
- 12 -
23/06/17
TPLP
PSC
WIRING DIAGRAM - 460/1/60
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - SINGLE EVAPORATOR
FOR ALL 460V MODELS USING DEFROST HEATER AND FAN CONTACTORS
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
1
4
GND
GND
TM
3
L1 L2
L1 L2(N)
FUSE OR
CIRCUIT
BREAKER
NOTE #3
X
2
N
FUSE OR
CIRCUIT
BREAKER
NOTE #3
L2
L1
COMPR INTERLOCK
(IF USED)
L1
L2
T1
T2
C
EVAP FAN
CONTACTOR
M2
N.C.
LIQUID LINE
SOL VALVE
NOTE #4
PUMP DOWN
SWITCH
(IF USED)
M1
T2
T1
SPACE THERMOSTAT
NOTE #4
DEFROST HEATER
CONTACTOR
C
H1
H2
4
3
X
F
N
BN
DT
GND.
C
RD
BK
FD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY
COIL DEFROST HEATERS
YL
WH
HEATER
LIMIT
SWITCH
FAN MOTOR
POWER PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
NOTES
EVAPORATOR
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
7-LP ED CONTACTOR SINGLE 12/07
T30-TPLP-PDI-11
REFER TO
EVAPORTOR
DATA PLATE FOR
MOTOR QUANTITY
(10.0A MAX.)
- 13 -
23/06/17
TPLP
WIRING DIAGRAM - 208-230/1/60
PSC
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
FOR ALL MODELS USING DEFROST HEATER CONTACTOR
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
L1 L2
GND
TM
3
1
4
FUSE OR
CIRCUIT
BREAKER
NOTE #3
X
2
N
FUSE OR
CIRCUIT
BREAKER
NOTE #3
L1
L2
T1
T2
DEFROST HEATER
CONTACTOR
C
COMPR INTERLOCK
(IF USED)
WARNING
N.C.
PUMP DOWN
SWITCH
(IF USED)
4
X
F
3
N
BN
WH
DT
GND.
SPACE
THERMOSTAT
NOTE #4
EVAP#2 FIELD MODIFICATION
FUSE OR
CIRCUIT
BREAKER
NOTE #3
MUST BE MADE
SEE NOTE:
LIQUID LINE
SOL VALVE
NOTE #4
4
H2
H1
3
N
X
F
BN
YL
1
DT
2
GND.
REMOVE AND INSULATE
H1
H2
YL
C
BK
RD
WH
FD
FD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
HEATER
LIMIT
SWITCH
DT-DEFROST TERM
FD-FAN DELAY
2
AS SHOWN
RD
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
RELOCATE WHITE WIRE FROM
N AS SHOWN
C
BK
1
HEATER
LIMIT
SWITCH
DT-DEFROST TERM
FD-FAN DELAY
(10.0A MAX.)
(10.0A MAX.)
DEFROST HEATERS
DEFROST HEATERS
* Remove & Insulate
FAN MOTOR
POWER PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
PRIMARY
EVAPORATOR
FAN MOTOR
POWER PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
SECONDARY
EVAPORATOR
* Fan delay not used on second evap / use fan contactor if total fan amps exceeds 10A
NOTES
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
4-LP ED CONTACTOR MULTI 12/07
T30-TPLP-PDI-11
- 14 -
23/06/17
TPLP
WIRING DIAGRAM - 460/1/60
PSC
60Hz
STANDARD PSC MOTORS
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
FOR ALL 460V MODELS USING DEFROST HEATER AND FAN CONTACTORS
REFER TO EVAPORATOR NAMEPLATE
FOR ELECTRICAL REQUIREMENTS
DEFROST CLOCK
PARAGON # 8145
OR EQUIVALENT
3
4
1
L1 L2
L1 L2(N)
GND
GND
TM
FUSE OR
CIRCUIT
BREAKER
NOTE #3
X
2
N
FUSE OR
CIRCUIT
BREAKER
NOTE #3
DEFROST HEATER
L1
L2
T1
T2
EVAP FAN
CONTACTOR
SPACE
THERMOSTAT
NOTE #4
L2
T1
T2
CONTACTOR
C
COMPR INTERLOCK
(IF USED)
C
L1
FUSE OR
CIRCUIT
BREAKER
NOTE #3
N.C.
LIQUID LINE
SOL VALVE
NOTE #4
PUMP DOWN
SWITCH
(IF USED)
WARNING
EVAP#2 FIELD MODIFICATION MUST BE MADE
RELOCATE WHITE WIRE FROM
1
N AS SHOWN
*
M1
M2
H1
H2
4
3
F
M1
N
X
M2
H1
H2
4
F
3
DT
GND.
GND.
C
RD
BK
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DEFROST TERMINATION
& FAN DELAY
CONTROL
(10.0A MAX.)
DT-DEFROST TERM
FD-FAN DELAY
YL
DT-DEFROST TERM
FD-FAN DELAY
DEFROST HEATERS
WH
YL
HEATER
LIMIT
SWITCH
FAN MOTOR
POWER PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
1
FD
FD
DEFROST HEATERS
DT
C
RD
BK
N
X
BN
BN
WH
HEATER
LIMIT
SWITCH
(10.0A MAX.)
PRIMARY
EVAPORATOR
FAN MOTOR
POWER PLUGS
FAN
MTR
FAN
MTR
FAN
MTR
REFER TO
EVAPORATOR
DATA PLATE FOR
MOTOR QUANTITY
(10.0A MAX.)
SECONDARY
EVAPORATOR
* Note: Fan Delay not used on second evap
NOTES
TERMINALS
1). USE COPPER CONDUCTORS ONLY
-COMPONENT TERMINAL
2). USE 75°C WIRE (OR HIGHER)
-TERMINAL BLOCK TERMINAL
3). OVERCURRENT PROTECTION FOR
EVAPORATOR FAN MOTORS AND
DEFROST HEATERS MUST NOT EXCEED
MAXIMUM VALUE SHOWN ON
EVAPORATOR NAMEPLATE.
CONDUCTORS/WIRING
FACTORY WIRING
WIRING BY OTHERS
OPTIONAL FACTORY
OR BY OTHERS
4.) MAY BE FACTORY INSTALLED-MOUNTED
AND WIRED ON EVAPORATOR
ALL FIELD WIRING MUST BE DONE IN
COMPLIANCE WITH ALL APPLICABLE LOCAL
AND NATIONAL CODES.
8-LP 460v ED CONTACTOR MULTI 09/06
T30-TPLP-PDI-11
- 15 -
23/06/17
NO COMPLEX CONTROLS, NO COST ADDER, SIMPLE TO UNDERSTAND
TPLP
ECM
PATENT 60Hz
PENDING
DESIGN FEATURES
US Patents Nos.
8,635,883
& 9,151,525
• Standard on all EC Motors
• NO special controls required.
• Refrigeration mode – EC motor operates at full speed.
Consumption 60 W per motor
• Off Cycle mode – EC motor operates at reduced speed.
Consumption 13 W per motor.
• Energy saving benefit on motor and compressor wattage consumption:
20000
ENERGY CONSUMPTION COMPARISON:
with PSC vs ECM vs SmartSpeed Evaporator Fan Motors
Energy Consumption (Watt-Hours)
18000
Compressor w/ PSC
16000
Compressor w/ ECM
14000
Compressor w/ SmartSpeed
12000
10000
ADDITIONAL ENERGY SAVINGS WHEN
USING SMARTSPEED EVAPS
8000
6000
4000
EVAP w/ PSC
2000
EVAP w/ ECM
EVAP with SmartSpeed
0
0
50
100
150
200
250
300
350
400
450
500
Time (minutes)
Note: Data collected on a typical freezer application with a 3HP low temp condensing unit and a 4 fan TPLP evaporator
INSTALLATION NOTES
EC motors are factory wired for SmartSpeed operation on evaporators equipped with
a factory installed thermostat.
For SmartSpeed operation on Evaporators without a factory installed thermostat,
a field wired SPDT type thermostat is required.
T30-TPLP-PDI-11
- 16 -
23/06/17
TPLP
T30-TPLP-PDI-11
WIRING DIAGRAM - 115/1/60, 208-230/1/60
OPTIONAL EC MOTORS with
AIR DEFROST MODELS
- 17 -
ECM
60Hz
23/06/17
TPLP
T30-TPLP-PDI-11
WIRING DIAGRAM - 208-230/1/60
OPTIONAL EC MOTORS with
ELECTRIC DEFROST MODELS
- 18 -
ECM
60Hz
23/06/17
TPLP
WIRING DIAGRAM - 208-230/1/60
ECM
60Hz
OPTIONAL EC MOTORS with
ELECTRIC DEFROST MODELS - MULTIPLE EVAPORATORS
T30-TPLP-PDI-11
- 19 -
23/06/17
TPLP
60Hz
SHIPPING WEIGHTS
Air Defrost Models
Electric Defrost Models
MODEL
TPLP
SHIPPING WEIGHT
LB.
(kg)
LB.
(kg)
104MA
45
(20)
104ME
104LE
103VE
49
(22)
106MA
47
(21)
106ME
105LE
104VE
51
(23)
107MA
49
(22)
107ME
106LE
105VE
53
(24)
209MA
70
(32)
209ME
207LE
206VE
76
(34)
211MA
74
(33)
211ME
209LE
208VE
80
(36)
214MA
78
(35)
214ME
211LE
209VE
84
(38)
317MA
101
(46)
317ME
314LE
312VE
109
(49)
320MA
107
(48)
320ME
317LE
315VE
115
(52)
423MA
117
(53)
423ME
419LE
416VE
127
(58)
426MA
135
(61)
426ME
422LE
419VE
145
(66)
532MA
163
(74)
532ME
527LE
523VE
176
(80)
639MA
192
(87)
639ME
631LE
627VE
207
(94)
T30-TPLP-PDI-11
SHIPPING WEIGHT
MODEL
TPLP
- 20 -
23/06/17
TPLP
60Hz
DIMENSIONAL DATA
.438 SLOTS IN
MOUNTING BRACKETS
A
B
6 1/2
[165]
3
[76]
1 3/8
[35]
3/4 MPT / 3/4 FLARE
DRAIN CONNECTION
11 7/8
[302]
12
[305]
MINIMUM
4
[102]
TYP
ELECTRICAL
CONNECTIONS.
13 7/16
[341]
MTG SLOTS
REFRIGERATION
CONNECTIONS.
SUCTION & LIQUID.
AIR THROW
APPROX 35'
IN OPEN
SPACE
15 7/8
[403]
6 1/2
[165]
1, 2 AND 3 FAN
MODELS.
(TOP VIEW)
3 1/8
[79]
A
C
B
13 7/16
[341]
MTG SLOTS
6 1/2
[165]
MODEL
TPLP
4, 5 AND 6 FAN
MODELS.
(TOP VIEW)
NO. OF
FANS
IN
(mm)
IN
(mm)
IN
(mm)
SUCTION
CONNECTION
(ID) SWEAT
A
B
C
LIQUID CONNECTION (ID)
SWEAT
R407A R22
R404A
104M^
106M^
107M^
209M^
211M^
214M^
317M^
320M^
423M^
426M^
532M^
639M^
1
1
1
2
2
2
3
3
4
4
5
6
30 1/4
30 1/4
30 1/4
46 1/4
46 1/4
46 1/4
62 1/4
62 1/4
78 1/4
78 1/4
94 1/4
110 1/4
(768)
(768)
(768)
(1175)
(1175)
(1175)
(1581)
(1581)
(1988)
(1988)
(2394)
(2800)
17 1/4
17 1/4
17 1/4
33 1/4
33 1/4
33 1/4
49 1/4
49 1/4
32 5/8
32 5/8
32 5/8
48 5/8
(438)
(438)
(438)
(845)
(845)
(845)
(1251)
(1251)
(829)
(829)
(829)
(1235)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
32 5/8
32 5/8
48 5/8
48 5/8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(829)
(829)
(1235)
(1235)
5/8
5/8
5/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 3/8
1 3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
1/2
104L^
105L^
106L^
207L^
209L^
211L^
314L^
317L^
419L^
422L^
527L^
631L^
1
1
1
2
2
2
3
3
4
4
5
6
30 1/4
30 1/4
30 1/4
46 1/4
46 1/4
46 1/4
62 1/4
62 1/4
78 1/4
78 1/4
94 1/4
110 1/4
(768)
(768)
(768)
(1175)
(1175)
(1175)
(1581)
(1581)
(1988)
(1988)
(2394)
(2800)
17 1/4
17 1/4
17 1/4
33 1/4
33 1/4
33 1/4
49 1/4
49 1/4
32 5/8
32 5/8
32 5/8
48 5/8
(438)
(438)
(438)
(845)
(845)
(845)
(1251)
(1251)
(829)
(829)
(829)
(1235)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
32 5/8
32 5/8
48 5/8
48 5/8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(829)
(829)
(1235)
(1235)
5/8
5/8
5/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
17 1/4
17 1/4
17 1/4
33 1/4
33 1/4
33 1/4
49 1/4
49 1/4
32 5/8
32 5/8
32 5/8
48 5/8
(438)
(438)
(438)
(845)
(845)
(845)
(1251)
(1251)
(829)
(829)
(829)
(1235)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
32 5/8
32 5/8
48 5/8
48 5/8
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(829)
(829)
(1235)
(1235)
5/8
5/8
5/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2
103V^
104V^
105V^
206V^
208V^
209V^
312V^
315V^
416V^
419V^
523V^
627V^
^ = A or E.
1
30 1/4
(768)
1
30 1/4
(768)
1
30 1/4
(768)
2
46 1/4
(1175)
2
46 1/4
(1175)
2
46 1/4
(1175)
3
62 1/4
(1581)
3
62 1/4
(1581)
4
78 1/4
(1988)
4
78 1/4
(1988)
5
94 1/4
(2394)
6
110 1/4
(2800)
Refer to Nomenclature for details
T30-TPLP-PDI-11
- 21 -
23/06/17
TPLP
SPORLAN
MODEL
TPLP
60Hz
RECOMMENDED EXPANSION VALVE
SELECTIONS - MEDIUM TEMP. MODELS
FACTORY
INSTALLED
NOZZLE
ALCO
R404A
R507
R448A
R407A
R407C
R22
R134a
MODEL
TPLP
FACTORY
INSTALLED
NOZZLE
R448A
R407A
R407C
R22
R404A
R507
R134a
104M
N/A
EBQE-AA-*C
EBQE-AAA-VC
EBQE-AAA-JC
104M
N/A
HFESC 1/4 SC
HFESC 1/2 HC
HFESC 1/2 MC
106M
L-1/2
EBQE-AA-*C
EBQE-AA-VC
EBQE-AA-JC
106M
L-1/2
HFESC 1/2 SC
HFESC 1/2 HC
HFESC 3/4 MC
107M
L-1/2
EBQE-A-*C
EBQE-AA-VC
EBQE-AA-JC
107M
L-1/2
HFESC 1/2 SC
HFESC 1/2 HC
HFESC 3/4 MC
209M
L-3/4
EBQE-A-*C
EBQE-AA-VC
EBQE-AA-JC
209M
L-3/4
HFESC 1 SC
HFESC 1 HC
HFESC 3/4 MC
HFESC 1 MC
211M
L-1
EBQE-A-*C
EBQE-A-VC
EBQE-A-JC
211M
L-1
HFESC 1 SC
HFESC 1 HC
214M
L-1
EBQE-B-*C
EBQE-A-VC
EBQE-A-JC
214M
L-1
HFESC 1-1/4 SC
HFESC 1-1/2 HC
HFESC 1 MC
317M
L-1 1/2
EBQE-B-*C
EBQE-A-VC
EBQE-A-JC
317M
L-1 1/2
HFESC 1-1/2 SC
HFESC 1-1/2 HC
HFESC 1-1/2 MC
320M
L-1 1/2
EBQE-B-*C
EBQE-B-VC
EBQE-A-JC
320M
L-1 1/2
HFESC 1-1/2 SC
HFESC 2 HC
HFESC 1-3/4 MC
423M
L-2
EBQE-B-*C
EBQE-B-VC
EBQE-A-JC
423M
L-2
HFESC 2 SC
HFESC 2 HC
HFESC 1-3/4 MC
426M
L-2
EBQE-C-*C
EBQE-B-VC
EBQE-B-JC
426M
L-2
HFESC 2 SC
HFESC 2-1/2 HC
HFESC 2-1/2 MC
532M
L-2 1/2
EBQE-C-*C
EBQE-B-VC
EBQE-B-JC
532M
L-2 1/2
HFESC 3-1/2 SC
HFESC 2-1/2 HC
HFESC 2-1/2 MC
639M
G-3
EBQE-C-*C
EBQE-C-VC
EBQE-C-JC
639M
G-3
HFESC 3-1/2 SC
HFESC 3 HC
HFESC 4 MC
* Varies with refrigerant: S = R404A, P = R507
For R449A, use R448A data.
For R449A, use R448A data.
DANFOSS
MODEL
TPLP
FACTORY
INSTALLED
NOZZLE
R404A
R507
R448A
R407A
R407C †
R22
R134a
104M
N/A
TUAE-R404A-4-N
TUAE-R22-4-N
TUAE-R134a-4-N
106M
L-1/2
TUAE-R404A-5-N
TUAE-R22-5-N
TUAE-R134a-5-N
107M
L-1/2
TUAE-R404A-6-N
TUAE-R22-5-N
TUAE-R134a-5-N
209M
L-3/4
TUAE-R404A-7-N
TUAE-R22-6-N
TUAE-R134a-6-N
211M
L-1
TUAE-R404A-7-N
TUAE-R22-6-N
TUAE-R134a-6-N
214M
L-1
TUAE-R404A-8-N
TUAE-R22-7-N
TUAE-R134a-7-N
317M
L-1 1/2
TUAE-R404A-8-N
TUAE-R22-8-N
TUAE-R134a-8-N
320M
L-1 1/2
TUAE-R404A-9-N
TUAE-R22-8-N
TUAE-R134a-8-N
423M
L-2
TUAE-R404A-9-N
TUAE-R22-8-N
TUAE-R134a-9-N
426M
L-2
TCAE-R404A-TC1-N
TUAE-R22-9-N
TUAE-R134a-9-N
532M
L-2 1/2
TCAE-R404A-TC2-N
TUAE-R22-9-N
TCAE-R134a-TC1-N
639M
G-3
TCAE-R404A-TC3-N
TCAE-R22-TC1-N
TCAE-R134a-TC2-N
† If using 407C, superheat setting must be adjusted by
turning 1 - 1.5 turns clockwise.
For R449A, use R448A data.
Above selections based on:
1) 100°F (38°C) vapor free liquid entering expansion valve
2) 110°F (43°C) Condensing temperature
3) 8 -12°F (4.4 -6.7°C) evaporator TD
T30-TPLP-PDI-11
- 22 -
If correct nozzle is not
available, the proper
orifice size can be
drilled in the field using
the following chart
NOZZLE
ORIFICE
No.
DRILL
SIZE
1/2
.070
3/4
.086
1
.0995
IN.
1-1/2
.120
2
.1406
2-1/2
.157
3
.172
4
.199
5
.211
6
.242
8
.266
10
.281
23/06/17
TPLP
RECOMMENDED EXPANSION VALVE
SELECTIONS - LOW TEMP. MODELS
60Hz
SPORLAN - R407A R448A
MODEL
TPLP
104L
FACTORY INSTALLED
NOZZLE
L-1/2
0° F (-18° C) EVAP.
-10° F (-23° C) EVAP.
-20° F (-29° C) EVAP.
-30° F (-34° C) EVAP.
EBQE-AAA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
105L
L-3/4
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
106L
L-1
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
207L
L-1
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
209L
L-1-1/2
EBQE-AA-VC
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
-40° F (-40° C) EVAP.
211L
L-2
EBQE-A-VC
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-B-VZP40
314L
L-2
EBQE-A-VC
EBQE-A-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
317L
L-3
EBQE-A-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
419L
L-3
EBQE-A-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
422L
G-4
EBQE-B-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
527L
G-4
EBQE-B-VC
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
631L
G-5
EBQE-C-VC
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
103V
L-1/2
EBQE-AAA-VC
EBQE-AAA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
104V
L-3/4
EBQE-AAA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
105V
L-1
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
206V
L-1
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-AA-VZP40
EBQE-A-VZP40
208V
L-1 1/2
EBQE-AA-VC
EBQE-AA-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
209V
L-2
EBQE-A-VC
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-A-VZP40
312V
L-2
EBQE-A-VC
EBQE-A-VZP40
EBQE-A-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
315V
L-2 1/2
EBQE-A-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
416V
L-2 1/2
EBQE-A-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
419V
G-3
EBQE-A-VC
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
EBQE-B-VZP40
523V
G-4
EBQE-B-VC
EBQE-B-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
627V
G-5
EBQE-B-VC
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
EBQE-C-VZP40
For R449A, use R448A data.
SPORLAN - R404A
MODEL
TPLP
104L
FACTORY INSTALLED
NOZZLE
L-1/2
0° F (-18° C) EVAP.
EBQE-AA-SC
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
105L
L-3/4
EBQE-AA-SC
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
-10° F (-23° C) EVAP.
-20° F (-29° C) EVAP.
-30° F (-34° C) EVAP.
-40° F (-40° C) EVAP.
106L
L-1
EBQE-AA-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
207L
L-1
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
209L
1-1/2
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
211L
L-2
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
314L
L-2
EBQE-B-SC
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
317L
L-3
EBQE-B-SC
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
419L
L-3
EBQE-B-SC
EBQE-B-SZP
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
422L
G-4
EBQE-C-SC
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
527L
G-4
EBQE-C-SC
EBQE-C-SZP
EBQE-C-SZP
EBSE-6-SZP
EBSE-6-SZP
631L
G-5
EBSE-6-SC
EBSE-6-SZP
EBSE-6-SZP
EBSE-6-SZP
EBSE-6-SZP
103V
L-1/2
EBQE-AA-SC
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
104V
L-3/4
EBQE-AA-SC
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
105V
L-1
EBQE-AA-SC
EBQE-AA-SZP
EBQE-AA-SZP
EBQE-AA-SZP
206V
L-1
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
208V
L-1 1/2
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
209V
L-2
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
EBQE-A-SZP
312V
L-2
EBQE-A-SC
EBQE-A-SZP
EBQE-A-SZP
EBQE-B-SZP
EBQE-B-SZP
315V
L-2 1/2
EBQE-B-SC
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
416V
L-2 1/2
EBQE-B-SC
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
EBQE-B-SZP
419V
G-3
EBQE-B-SC
EBQE-B-SZP
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
523V
G-4
EBQE-C-SC
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
EBQE-C-SZP
627V
G-5
EBQE-C-SC
EBQE-C-SZP
EBQE-C-SZP
EBSE-6-SZP
EBSE-6-SZP
Above selections based on:
1) 100°F (38°C) vapor free liquid entering expansion valve
2) 110°F (43°C) Condensing temperature
3) 8 -12°F (4.4 -6.7°C) evaporator TD
T30-TPLP-PDI-11
- 23 -
23/06/17
TPLP
INSTALLATION INSTRUCTIONS
60Hz
INSTALLATION
EXPANSION VALVE (TXV) PRE-SELECTED
The installation and start-up of evaporators should only
be performed by qualified refrigeration mechanics.
This equipment should be installed in accordance with
all applicable codes, ordinances and local by-laws.
Locate the expansion valve bulb on a horizontal length of suction line preferably 3 to 6 inches from the suction
header. Locate the bulb at 4 or 8 clock position and
insulate with a waterproof type of insulation. Clamp the
bulb to ensure 100% contact of the bulb with the
suction line.
INSPECTION
Inspect all equipment before unpacking for visible signs
of damage or loss. Check shipping list against material
received to ensure shipment is complete.
After following the manufacturer’s installation instructions
and after the room has reached the desired
temperature the valve superheat should be checked.
This will confirm that the evaporator is operating
properly and performing to maximum efficiency. The
superheat should be around 6 (3.3°C) to 8°F (4.4°C) for
a 10 to 12°F T.D (5.6 to 6.7°C). Too high or low a super
heat will result in unsatisfactory system
performance and possible compressor problems.
IMPORTANT: Remember, you, the consignee, must
make any claim necessary against the transportation
company. Shipping damage or missing parts, when
discovered at the outset, will prevent later unnecessary
and costly delays.
If damage or loss during transport is evident, make
claim to carrier, as this will be their responsibility,
not the manufacturer’s.
Should carton be damaged, but damage to equipment is
not obvious, a claim should be filed for “concealed
damage” with the carrier.
MOUNTING
Refer to dimensional drawing for recommended
mounting arrangements. Ensure adequate clearance
is provided behind the coil as well as each end. The
evaporators may be mounted flush with ceiling with
bolts, or hanging down with rod hangers. When using
rod hangers, allow adequate space between the top of
the unit and the ceiling for cleaning to comply with NSF
Standard 7.
Ensure that the ceiling is level since the drain pan
has been sloped for drainage during the defrost
cycle.
IMPORTANT: The electrical characteristics of the unit
should be checked at this time to make sure they
correspond to those ordered and to electrical power
available at the job site.
Save all shipping papers, tags and instruction sheets for
reference by installer and owner.
APPLICATION
TPLP evaporators are designed for walker-in cooler and
freezer applications used with a wide range of refrigerants. For room temperatures above 35°F (2°C) AND
evaporating temperatures above 26°F (-3°C), positive
defrosting means (electric) may not be required,
otherwise, electric defrost defrost models should be
used. Electric defrost models come with defrost
termination and fan delay as standard to control the
defrost cycle termination and fan delay, while defrost
initiation means (e.g. defrost timer) is not included.
DRAIN LINE
The drain line should be run from the drain connection,
sloping at least 1” (25 mm) per foot and should have
the size at least as large as the drain connection. A
P-Trap in a warm area outside the room must be
provided to allow proper draining through the tubing.
Connection should be made to proper drainage facilities
that comply with local regulations.
To prevent freeze-up when the temperature of the
refrigerated space is 35°F (2°C) or lower, the drain line
should be heated along its run inside the cold room.
The heated drain line should be insulated. It is recommended that the heater be energized at all times. A
heat input of 20 watts per foot in a 28°F (-2°C) room
and 30 watts per foot for -20°F (-29°C) rooms, is
satisfactory. Drain line heaters are not required for
constant room temperature above 35°F (2°C).
Always trap evaporator drain line individually to prevent
vapor migration.
The coil must not be exposed to any abnormal
atmospheric or acidic environments. This may result in
corrosion to the cabinet and possible coil failure (leaks).
(Consult manufacturer for optional baked on phenolic
protective coatings).
LOCATION
The unit location in the room should be selected to ensure uniform air distribution throughout the entire space
to be refrigerated. Be sure that the product does not
obstruct the free circulation of air. Allow a minimum of
24” clearance at each end. Do not locate evaporators
over doors. Consideration should be given to the coil
location in order to minimize the piping run length to the
condensing unit and floor drain.
T30-TPLP-PDI-11
Ensure that the drain line has sufficient slope for
proper drainage (prevention of ice build up/blockage in pan).
- 24 -
23/06/17
TPLP
INSTALLATION INSTRUCTIONS
PIPING
Refrigeration grade piping must be used for all field
refrigeration piping. Refrigerant line sizes are important
and may not be the same size as the coil connections.
Consult ASHRAE handbook or other similar reference
book for proper line sizing.
Refrigerant piping and control system should be designed
to prevent possible liquid slugging (from oil or refrigerant)
of the compressors on start-up after the defrost cycle.
Also, it should prevent oil logging and minimize refrigerant
pressure drop.
WIRING
Wire system in accordance with governing standards and
local codes. See data and wiring diagrams on pages 4 to
20 for typical wiring arrangement. Electrical wiring is to be
sized in accordance with minimum circuit ampacity rating
(MCA). Size fuses used must not exceed the Maximum
Fuse Size ratings.
For ease of identifying the proper wiring terminal, unit
wiring is color coded and terminal block connections are
identified.
When fan delay thermostats (combination fan delay and
defrost termination) are installed, on start-up, the fans
do not operate until the coil temperature is reduced to
approximately 25oF (-4°C). It is normal for the fans to
cycle a few times until the room temperature is brought
down. At higher evaporating temperatures this control
may not close and therefore should either be by-passed
temporarily or replaced with an adjustable type. (set for a
higher temperature cut-in point).
MAINTENANCE
The unit should be periodically inspected for any dirt or ice
build-up on the fin surface and cleaned if necessary with
a soft whisk or brush. Also ensure coils inner (and outer)
drain pans do not have any ice build-up from improper
defrost operation. When replacing heater elements first
remove heater retainer brackets and heater clips.
T30-TPLP-PDI-11
- 25 -
60Hz
SYSTEM CHECK
Before Start-Up:
1. All wiring should be in accordance with local codes.
2. Refrigerant lines should be properly sized.
3. Thorough evacuation and dehydration has been
performed.
4. The suction, discharge, and receiver service valves must be open.
5. The system preferably include a liquid line filter drier moisture indicator and suction filter.
6. Pour enough water into the drain pan to allow a good check on drainage and seal the trap.
After Start-Up:
1.Check the oil level to be sure the oil charge is correct.
2. On initial start up the fans do not start until coil
temperature is pulled down to approximately 25°F (-4°C) on the coil. Also, it is normal for the fan to cycle a few times until the room temperature is pulled down.
3. If necessary, temporarily by-pass fan delay control (to run fans until room temp is lowered).
4. Be sure that the expansion valve is properly set to provide the correct amount of superheat.
5. After the box temperature is close to reaching the desired temperature, the evaporator superheat must be checked and adjustment made if necessary. In general, evaporators running with a TD of 10°F (5.6°C ) should have a superheat reading of 6° to 8°F (3.3°C to 4.4°C). For
evaporators with another T.D., the general rule is that the superheat should be around 60 to
80% of T.D.
6. Heavy moisture loads are usually encountered when starting the system for the first time. This may cause a rapid build-up of frost on the evaporator. During the initial pull down, we
suggest that the frost build-up be watched and defrosted manually as required.
7. Observe that the system goes through at least one complete DEFROST CYCLE.
23/06/17
TPLP
PROJECT INFORMATION
60Hz
System
Model Number
Date of Start-Up
Serial Number
Service Contractor
Refrigerant
Phone
Electrical Supply
E-Mail
T30-TPLP-PDI-11
- 26 -
23/06/17
TPLP
PRODUCT SUPPORT RESOURCES
60Hz
web: t-rp.com/tplp
email: [email protected]
call: 1-844-893-3222 x520
email: [email protected]
call: 1-844-893-3222 x529
web: t-rp.com/serv_parts.htm
email: [email protected]
call: 1-844-893-3222 x501
web: t-rp.com/warranty
email: [email protected]
call: 1-844-893-3222 ext. 501
email: [email protected]
call: 1-844-893-3222 x501
email: [email protected]
call: 1-844-893-3222 x503
T30-TPLP-PDI-11
- 27 -
23/06/17
“AS BUILT” SERVICE PARTS LIST
Service Parts List
Label
To Be Attached
HERE
NATIONAL REFRIGERATION &
AIR CONDITIONING CANADA CORP.
159 Roy Blvd.
Brantford Ontario Canada N3R 7K1
PHONE: (519) 751-0444 800-463-9517
FAX (519) 753-1140 www.t-rp.com
Due to National Refrigeration’s policy of continuous product improvement, we reserve the right to make changes without notice.
23/06/17