advertisement
vacon 100
ac drives
installation manual
vacon • 0
INDEX
Document: DPD00873C
Order code: DOC-INS04123+DLUK
Rev. C
Version release date: 3.5.12
24-hour support +358 (0)201 212 575 • Email: [email protected]
vacon • 1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Approvals
1.
A
PPROVALS
Approvals granted to this Vacon product are listed on the following pages.
1.1
EC Declaration of conformity
Find the EC Declaration of Conformity on the next page.
1.2
UL approval
cULus approval file number E171278.
1.3
C-tick approval
C-tick approval file number N16307.
vacon • 2
24-hour support +358 (0)201 212 575 • Email: [email protected]
1
vacon • 3 Approvals
1
EC DECLARATION OF CONFORMITY
We
Manufacturer's name: Vacon Oyj
Manufacturer's address: P.O.Box 25
R u n s o r i n t i e 7
F I N 6 5 3 8 1 V a a s a
F i n l a n d hereby declare that the product
Product name: Vacon 100 AC drive
Model designation: Vacon 0100-3L-0003-5...0310-5
Vacon 0100-3L-0003-2...0310-2 has been designed and manufactured in accordance with the following standards:
Safety: EN 61800-5-1 (2007)
E N 6 0 2 0 4 1 ( 2 0 0 9 ) ( a s r e l e v a n t )
EMC: EN61800-3 (2004)
E N 6 1 0 0 0 3 1 2 and conforms to the relevant safety provisions of the Low Voltage Directive
(2006/95/EC) and EMC Directive 2004/108/EC.
It is ensured through internal measures and quality control that the product conforms at all times to the requirements of the current Directive and the relevant standards.
In Vaasa, 29th of February, 2012
The year the CE marking was affixed:
Vesa Laisi
P r e s i d e n t
2012
9226.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Safety vacon • 4
2.
S
AFETY
This manual contains clearly marked cautions and warnings which are intended for your personal safety and to avoid any unintentional damage to the product or connected appliances.
Please read the information included in cautions and warnings carefully.
The cautions and warnings are marked as follows:
= DANGEROUS VOLTAGE!
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
9000.emf
= WARNING or CAUTION
13006.emf
Table 1. Warning signs
2.1
Danger
The components of the power unit of Vacon 100 are live when the AC drive is connected to mains potential. Coming into contact with this voltage is extremely
dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals are live when
Vacon 100 is connected to mains, even if the motor is not running.
After disconnecting the AC drive from the mains, wait 5 minutes before doing any work on the connections of Vacon100. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure absence of voltage before start- ing any electrical work!
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage present even when Vacon 100 is disconnected from mains.
Before connecting the AC drive to mains make sure that the front and cable covers of Vacon 100 are closed.
During a coast stop (see Application Manual), the motor is still generating voltage to the drive. Therefore, do not touch the components of the AC drive before the motor has completely stopped. Wait 5 minutes before starting any work on the drive.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
2
2 vacon • 5
2.2
Warnings
Safety
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
Vacon 100 AC drive is meant for fixed installations only.
Do not perform any measurements when the AC drive is connected to the mains.
The touch current of Vacon 100 AC drives exceeds 3.5mA AC. According to standard EN61800-5-1, a reinforced protective ground connection must be ensured.
If the AC drive is used as a part of a machine, the machine manufacturer is
responsible for providing the machine with a supply disconnecting device (EN
60204-1).
Only spare parts delivered by Vacon can be used.
At power-up, power brake or fault reset the motor will start immediately if the start signal is active, unless the pulse control for Start/Stop logic has been selected.
Futhermore, the I/O functionalities (including start inputs) may change if parameters, applications or software are changed.Disconnect, therefore, the motor if an unexpected start can cause danger.
The motor starts automatically after automatic fault reset if the autoreset function is activated. See the Application Manual for more detailed information.
Prior to measurements on the motor or the motor cable, disconnect the motor cable from the AC drive.
Do not touch the components on the circuit boards. Static voltage discharge may damage the components.
Check that the EMC level of the AC drive corresponds to the requirements of your
supply network. See chapter 7.3.
In a domestic environment, this product may cause radio interference in which case supplementary mitigation measures may be required.
The AC drives are suitable for use on a circuit capable of delivering not more than
100,000 rms symmetrical amperes, 600V maximum.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Safety
2.3
Earthing and earth fault protection
vacon • 6
CAUTION!
13006.emf
The Vacon 100 AC drive must always be earthed with an earthing conductor connected to the earthing terminal marked with .
The touch current of Vacon 100 exceeds 3.5mA AC. According to EN61800-5-1, one or more of the following conditions for the associated protective circuit shall be satisfied:
A fixed connection and a) the protective earthing conductor shall have a cross-sectional area of at least 10 mm 2
Cu or 16 mm 2 Al.
or b) an automatic disconnection of the supply in case of discontinuity of the protective
earthing conductor. See chapter 5.
or c) provision of an additional terminal for a second protective earthing conductor of the same cross-sectional area as the original protective earthing conductor.
Cross-sectional area of phase conductors (
[mm 2 ]
S 16
16 S 35
35 < S
S )
Minimum cross-sectional area of the corresponding protective earthing conductor
[mm 2 ]
S
16
S /2
The values above are valid only if the protective earthing conductor is made of the same metal as the phase conductors. If this is not so, the cross-sectional area of the protective earthing conductor shall be determined in a manner which produces a conductance equivalent to that which results from the application of this table.
Table 2. Protective earthing conductor cross-section
The cross-sectional area of every protective earthing conductor which does not form a part of the supply cable or cable enclosure shall, in any case, be not less than
• 2.5 mm 2 if mechanical protection is provided or
• 4 mm 2 if mechanical protection is not provided. For cord-connected equipment, provisions shall be made so that the protective earthing conductor in the cord shall, in the case of failure of the strain-relief mechanism, be the last conductor to be interrupted.
However, always follow the local regulations for the minimum size of the protective earthing conductor.
NOTE: Due to the high capacitive currents present in the AC drive, fault current protective switches may not function properly.
24-hour support +358 (0)40 837 1150 • Email: [email protected]
2
vacon • 7 Safety
13006.emf
Do not perform any voltage withstand tests on any part of Vacon 100. There is a certain procedure according to which the tests shall be performed. Ignoring this procedure may result in damaged product.
2.4
Electro-magnetic compatibility (EMC)
Vacon 100 AC drives comply with IEC 61000-3-12 provided that the short-circuit power S
SC
is greater than or equal to 120 R
SCE
at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
SC
greater than or equal to 120 R
SCE
.
2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Receipt of delivery vacon • 8
3.
R
ECEIPT OF DELIVERY
Check the correctness of delivery by comparing your order data to the drive information found on the package label. If the delivery does not correspond to your order, contact the supplier
Vacon type designation code
Vacon order number
Batch ID
Serial number
Supply voltage
Rated output current
IP class
Application code
Customer’s order number
9112.emf
Figure 1. Vacon package label
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
vacon • 9 Receipt of delivery
3.1
Type designation code
Vacon type designation code is formed of a nine-segment code and optional +codes. Each segment of the type designation code uniquely corresponds to the product and options you have ordered. The code is of the following format:
VACON
This segment is common for all products.
0100
Product range:
0100 = Vacon 100
3L
Input/Function:
3L = Three-phase input
VACON0100-3L-0061-5 +xxxx +yyyy
+xxxx +yyyy
Additional codes. (Several options possible)
Examples of additional codes:
+IP54
AC drive with IP protection class IP54
0061
Drive rating in ampere; e.g. 0061 = 61 A
5
Supply voltage:
2 = 208-240 V
5 = 380-500 V
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Receipt of delivery vacon • 10
3.2
Unpacking and lifting the AC drive
MR4
MR5
MR6
MR7
MR8
MR9
The weights of the AC drives vary greatly according to the size. You may need to use a piece of special lifting equipment to move the drive from its package. Note the weights of each individual frame size in Table 3 below.
Frame
Weight, IP21/IP54
[kg]
6.0
10.0
20.0
37.5
66.0
108.0
Weight, IP00
[kg]
62.0
97.0
Weight, IP21/IP54
[lb.]
13.2
22.0
44.1
82.7
145.5
238.1
Table 3. Frame weights
Weight, IP00
[lb.]
136.7
213.8
If you decide to use a piece of lifting equipment see picture below for recommendations to lift the drive.
3.2.1
Lifting frames MR8 and MR9
Max. 45°
NOTE: First detach the drive from the pallet it has been bolted to.
NOTE: Place the lifting hooks symmetrically in at least two holes.The lifting device must be able to carry weight of the drive.
NOTE: The maximum allowed lifting angle is 45 degrees.
9012.emf
Figure 2. Lifting bigger frames
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
vacon • 11 Receipt of delivery
Vacon 100 AC drives have undergone scrupulous tests and quality checks at the factory before they are delivered to the customer. However, after unpacking the product, check that no signs of transport damages are to be found on the product and that the delivery is complete.
Should the drive have been damaged during the shipping, please contact primarily the cargo insurance company or the carrier.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Receipt of delivery vacon • 12
3.3
Accessories
After having opened the transport package and lifted the drive out, check immediately that these various accessories were included in the delivery. The contents of the accessories bag differ by drive size and IP protections class:
3.3.1
Frame MR4
Item Quantity Purpose
M4x16 screw
M4x8 screw
M5x12 screw
Control cable grounding lamella
EMC cable clamps, size M25
Grounding clamp
‘Product modified’ label
IP21: Cable grommet
IP54: Cable grommet
11
1
1
3
3
2
1
3
6
Screws for power cable clamps
(6), control cable clamps (3), grounding clamps (2)
Screw for optional grounding
Screw for drive external grounding
Control cable grounding
Clamping power cables
Power cable grounding
Information about modifications
Cable run-through sealing
Cable run-through sealing
Table 4. Contents of accessories bag, MR4
3.3.2
Frame MR5
Item Quantity Purpose
M4x16 screw 13
M4x8 screw
M5x12 screw
Control cable grounding lamella
EMC cable clamps, size M25
EMC cable clamps, size M32
Grounding clamp
‘Product modified’ label
IP21: Cable grommet, hole diameter 25.3 mm
IP54: Cable grommet, hole diameter 25.3 mm
Cable grommet, hole diameter 33.0 mm
1
1
3
1
2
2
1
1
4
2
Table 5. Contents of accessories bag, MR5
Screws for power cable clamps
(6), control cable clamps (3), grounding clamps (4)
Screw for optional grounding
Screw for drive external grounding
Control cable grounding
Clamping brake resistor cable
Clamping power cables
Power cable grounding
Information about modifications
Cable run-through sealing
Cable run-through sealing
Cable run-through sealing
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
3 vacon • 13
3.3.3
Frame MR6
Receipt of delivery
Item Quantity Purpose
M4x20 screw
M4x16 screw
M4x8 screw
M5x12 screw
Control cable grounding lamella
EMC cable clamps, size M32
EMC cable clamps, size M40
Grounding clamp
‘Product modified’ label
Cable grommet, hole diameter 33.0 mm
Cable grommet, hole diameter 40.3 mm
IP54: Cable grommet, hole diameter 25.3 mm
10
3
1
1
3
1
2
2
1
1
2
3
Screws for power cable clamps (6) and grounding clamps (4)
Screws for control cable clamps
Screw for optional grounding
Screw for drive external grounding
Control cable grounding
Clamping brake resistor cable
Clamping power cables
Power cable grounding
Information about modifications
Cable run-through sealing
Cable run-through sealing
Cable run-through sealing
Table 6. Contents of accessories bag, MR6
3.3.4
Frame MR7
Item Quantity Purpose
M5x30 slotted nut
M4x16 screw
M6x12 screw
Control cable grounding lamella
EMC cable clamps, size M50
Grounding clamp
‘Product modified’ label
Cable grommet, hole diameter 50.3 mm
IP54: Cable grommet, hole diameter 25.3 mm
6
3
1
3
3
2
1
3
3
Nuts for power cable clamps
Screws for control cable clamps
Screw for drive external grounding
Control cable grounding
Clamping power cables
Power cable grounding
Information about modifications
Cable run-through sealing
Cable run-through sealing
Table 7. Contents of accessories bag, MR7
3.3.5
Frame MR8
Item Quantity Purpose
M4x16 screw
Control cable grounding lamella
Cable lugs KP34
Cable insulator
Cable grommet, hole diameter 25.3 mm
IP00: Touch protection shield
IP00: M4x8 screw
3
3
3
11
4
1
2
Screws for control cable clamps
Control cable grounding
Clamping power cables
Avoiding contact between cables
Control cable run-through sealing
Avoiding contact with live parts
Fixing the touch protection shield
Table 8. Contents of accessories bag, MR8
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Receipt of delivery
3.3.6
Frame MR9 vacon • 14
Item Quantity Purpose
M4x16 screw
Control cable grounding lamella
Cable lugs KP40
Cable insulator
Cable grommet, hole diameter 25.3 mm
IP00: Touch protection shield
IP00: M4x8 screw
3
3
5
10
4
1
2
Screws for control cable clamps
Control cable grounding
Clamping power cables
Avoiding contact between cables
Control cable run-through sealing
Avoiding contact with live parts
Fixing the touch protection shield
Table 9. Contents of accessories bag, MR9
24-hour support +358 (0)201 212 575 • Email: [email protected]
3
vacon • 15 Receipt of delivery
3.4
‘Product modified’ sticker
In the Accessories bag included in the delivery you will find a silver
Product modified
sticker.
The purpose of the sticker is to notify the service personnel about the modifications made in the AC drive. Attach the sticker on the side of the AC drive to avoid losing it. Should the AC drive be later modified mark the change on the sticker.
Product modified
Date:
Date:
Date:
9004.emf
Figure 3. ‘Product modified’ sticker
3.5
Disposal
When the device reaches the end of its operating life do not dispose of it as a part of standard household garbage. Main components of the product can be recycled, but some need to be fragmented to separate different types of materials and components that need to be treated as special waste from electrical and electronic components. To ensure environmentally sound and safe recycling treatment, the product can be taken to appropriate recycling center or returned to the manufacturer.
Observe local and other applicable laws as they may mandate special treatment for specific components or special treatment may be ecologically sensible.
3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting vacon • 16
4.
M
OUNTING
The AC drive must be mounted in vertical position on the wall or on the back plane of a cubicle.
Ensure that the flatness variation shall not exceed 3 mm. Should the conditions of the mounting place require horizontal mounting, the functionalities within the given nominal values stat-
ed in chapter 8 cannot be guaranteed.
The AC drive shall be fixed with the screws and other possible components included in the delivery.
4.1
Dimensions
4.1.1
Wall mount
IP21
Ø7
Ø13
128
100
190
Ø25
100
9080.emf
Figure 4. Vacon AC drive dimensions, MR4, wall mount
IP54
Ø25
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
vacon • 17
Ø7
Ø14
144
115
100*
Ø7
214
Mounting
IP21
Ø33 Ø25 Ø33
IP54
Ø25
Ø7
100*
115
*Optional mounting holes (for NX replacement)
Figure 5. Vacon AC drive dimensions, MR5, wall mount
Ø9
195
148
Ø 15,5
229
IP21
Ø40 Ø33 Ø40
9081.emf
Ø25
IP54
Ø25
4
Ø9
148
9082.emf
Figure 6. Vacon AC drive dimensions, MR6, wall mount
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting
259
Ø20
237
190 Ø9
Ø16
Ø51
IP21 vacon • 18
Ø25
Ø50
IP54
9083.emf
Figure 7. Vacon AC drive dimensions, MR7, wall mount
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
vacon • 19
117 188
663 22 262
Mounting
4
966
Figure 8.Vacon AC drive dimensions, MR8 IP21 and IP54
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
vacon • 20 Mounting
9.3
663
10.8
18
683
15.1
794
Figure 9. Vacon AC drive dimensions, MR8 IP00
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
vacon • 21 Mounting
318
166
4
Figure 10. Vacon AC drive dimensions, MR9 IP21 and IP54
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting vacon • 22
Figure 11. Vacon AC drive dimensions, MR9 IP00
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
vacon • 23 Mounting
4.1.2
Flange mount
The AC drive can also be recessed into the cabinet wall or similar surface. A special flange mount option
Cabinet wall
(or similar)
Cabinet wall or similar
Front
Rear
IP54
4
IP00
9070.emf
Figure 12. Example of flange mount (frame MR9)
4.1.2.1
Flange mount - Frames MR4 to MR6
Figure 13. presents the dimensions of the mounting opening and Figure 14. the depth dimen-
sions of the drives with the flange mount option.
F
A
C
Figure 13. Flange mount cutout dimensions for MR4 to MR6
9069.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting vacon • 24
Frame
MR4
MR5
MR6
A B C D E
310
408
534
137
152
203
337
434
560
144
160
211
110
132
184
Table 10. Flange mount cutout dimensions for MR4 to MR6 [mm]
F
316
414
541
MR4 MR5 MR6
9074.ai
Figure 14. MR4 to MR6, flange mount, depth dimensions
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
4 vacon • 25 Mounting
4.1.2.2
Flange mount MR7 to MR9
Figure 15. presents the dimensions of the mounting opening and Figure 17. the dimensions of
the drives with the flange mount option.
Remember to seal the contact surface between the flange and the cutout with the gasket tape provided. If the parts or the drive delivered are already equipped with a sealing no action is
Drive outline
9075.emf
Opening outline
A E
C
Figure 15. Flange mount cutout dimensions for MR7 to MR9
Frame
MR7
MR8
MR9
A
655
859
975
B
240
298
485
C
682
888
1050
D
268
359
530
Table 11. Flange mount cutout dimensions for MR7 to MR9
E
13.5
17
54
Drive
Opening outline ( ) Gasket tape ( )
9254.emf
Figure 16. Sealing the cutout
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting
110
MR7
149
MR8
233
MR9
Ø22 vacon • 26
9076.emf
108
Figure 17. MR7 to MR9, flange mount, depth dimensions
247
257
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
4 vacon • 27 Mounting
4.2
Cooling
The AC drives produce heat in operation and are cooled down by air circulated by a fan. Enough free space shall therefore be left around the AC drive to ensure sufficient air circulation and cooling. Different acts of maintenance also require certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient temperature of the drive.
A
C
A
B B
Type
MR4
MR5
MR6
MR7
MR8
MR9
Min clearance [mm]
A
*
B * C D
20 20 100 50
20 20 120 60
20 20 160 80
20 20 250 100
20 20 300 150
20 20 350 200
*. Min clearances A and B for drives with IP54 enclosure is 0
mm.
Table 12. Min. clearances around AC drive
D
9013.emf
Figure 18. Installation space
A = clearance around the AC drive (see also B)
B = distance from one AC drive to another or distance to cabinet wall
C = free space above the AC drive
D = free space underneath the AC drive
MR4
MR5
MR6
MR7
MR8
MR9
Table 13. Required cooling air
Type
Cooling air required
[m 3 /h]
45
75
190
185
335
621
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Mounting
Note that if several units are mounted above each other the required free space equals C + D (see
Figure 19.). Moreover, the outlet air used for cool-
ing by the lower unit must be directed away from the air intake of the upper unit by means of e.g. a piece of metal plate fixed to cabinet wall between
the drives as shown in Figure 19.
C+D vacon • 28
FRONT
9014.emf
SIDE
Figure 19. Installation space when drives are mounted on top of each other
24-hour support +358 (0)201 212 575 • Email: [email protected]
4
vacon • 29 Power cabling
5.
P
OWER CABLING
The mains cables are connected to terminals L1, L2 and L3 and the motor cables to terminals
marked with U, V and W. See principal connection diagram in Figure 20. See also Table 14 for
the cable recommmendations for different EMC levels.
Keypad
Control
L1
L2
L3
Power unit
U/T1
V/T2
W/T3
M
9050.emf
Figure 20. Principal connection diagram
Use cables with heat resistance of at least +70°C. The cables and the fuses must be dimensioned according to the AC drive nominal OUTPUT current which you can find on the rating plate.
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 30
EMC levels
Cable type 1 st
environment 2nd environment
Category C2 Category C3 Level C4
Mains cable
Motor cable
1
3*
1
2
Control cable 4 4 4
Table 14. Cable types required to meet standards
1
2
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the
specific mains voltage. (MCMK or similar recommended). See Figure 21.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recom-
mended cable transfer impedance (1...30MHz) max. 100mohm/m]. See Figure 21.
*360º earthing of the shield with cable glands in motor end needed for EMC level C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-O or similar).
PE conductor and shield
PE conductors
9007.emf
Figure 21.
Shield
NOTE: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).
NOTE: If safety switch is connected the EMC protection shall be continuous over the whole cable installation.
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 31 Power cabling
5.1
UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with a minimum heat-resistance of +60/75°C. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum.
5.1.1
Cable dimensioning and selection
Table shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.
Recommended fuse types are gG/gL.
These instructions apply only to cases with one motor and one cable connection from the AC drive to the motor. In any other case, ask the factory for more information.
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 32
5.1.1.1
Cable and fuse sizes
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. The manufacturer offers recommendations also for high speed J (UL & CSA ), aR (UL recognized, IEC
60269-4) and gS (IEC 60269-4) fuse ranges.
Table 15. Cable and fuse sizes for Vacon 100
Frame
MR4
MR5
MR6
MR7
MR8
Type
I
L
[A]
0075 2
0072 4
0088 2
0087 4
0105 2
0105 4
0140 2
0140 4
0003 2—0004 2
0003 4—0004 4
3.7—4.8
3.4—4.8
0006 2—0008 2
0005 4—0008 4
6.6—8.0
5.6—8.0
0011 2—0012 2
0009 4—0012 4
11.0—12.5
9.6—12.0
16
0018 2
0016 4
0024 2
0023 4
18.0
16.0
24.0
23.0
20
25
0031 2
0031 4
0038 4
31.0
31.0
38.0
6
10
32
40
0048 2
0046 4
0062 2
0061 4
48.0
46.0
62.0
61.0
50
63
75,0
72,0
88,0
87,0
80
100
105,0
140,0
125
160
0170 2
0170 4
0205 2
0205 4
170,0
205,0
200
250
Fuse
(gG/gL)
[A]
Mains, motor and brake resistor
*
cable
Cu [mm
2
]
Terminal cable size
Main terminal
[mm
2
]
Earth terminal
[mm
2
]
3*1.5+1.5
3*1.5+1.5
3*2.5+2.5
1—6 solid
1—4 stranded
1—6 solid
1—4 stranded
1—6 solid
1—4 stranded
1—6
1—6
1—6
3*6+6
3*6+6
3*10+10
3*10+10
3*16+16 (Cu)
3*25+16 (Al)
3*25+16 (Cu)
3*35+10 (Al)
3*35+16 (Cu)
3*50+16 (Al)
3*35+16 (Cu)
3*70+21 (Al)
3*50+25 (Cu)
3*70+21 (Al)
3*70+35 (Cu)
3*95+29 (Al)
3*95+50 (Cu)
3*150+41 (Al)
3*120+70 (Cu)
3*185+57 (Al)
1—10 Cu
1—10 Cu
1—10 Cu
2.5—50 Cu/Al
2.5—50 Cu/Al
2.5—50 Cu/Al
6-70 mm 2
6-70 mm 2
6-70 mm 2
1—10
1—10
1—10
2.5—35
2.5—35
2.5—35
Cu/Al 6-70 mm
Cu/Al 6-70 mm
Cu/Al 6-70 mm
Bolt size M8
Bolt size M8
Bolt size M8
2
2
2
Bolt size M8
Bolt size M8
Bolt size M8
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 33 Power cabling
Table 15. Cable and fuse sizes for Vacon 100
Frame Type
I
L
[A]
Fuse
(gG/gL)
[A]
Mains, motor and brake resistor
*
cable
Cu [mm
2
]
Terminal cable size
Main terminal
[mm
2
]
Earth terminal
[mm
2
]
MR9
0261 2
0261 4
0310 2
0310 4
261,0
310,0
315
350
3*185+95 (Cu)
2*3*120+41 (Al)
2*3*95+50 (Cu)
2*3*120+41 (Al)
Bolt size M8
Bolt size M8
Bolt size M8
Bolt size M8
*. If you use a multi-conductor cable, NOTE that one of the conductors of the brake resistor cable remains unconnected. Use of single cable is also allowed provided that the minimum cable cross-sectional area given in this table is observed.
The cable dimensioning is based on the criteria of the International Standard IEC60364-5-52:Cables must be PVC-isolated; Max ambient temperature +30°C, max temperature of cable surface +70°C; Use only cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel, NOTE HOWEVER that the requirements of both the cross-sectional area and the max number of cables must be observed.
For the correction factors for each temperature, see International Standard IEC60364-5-52.
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 34
5.1.1.2
Cable and fuse sizes, North America
The recommended fuse types are gG/gL (IEC 60269-1) or class T (UL & CSA). The fuse voltage rating should be selected according to the supply network. The final selection should be made according to local regulations, cable installation conditions and cable specification. Bigger fuses than what is recommended below shall not be used.
Check that the fuse operating time is less than 0.4 seconds. Operating time depends on used fuse type and impedance of the supply circuit. Consult the factory about faster fuses. Vacon offers recommendations also for high speed J (UL & CSA ), aR (UL recognized, IEC 60269-4) and gS (IEC 60269-4) fuse ranges.
Frame
MR4
MR5
MR6
MR7
Type
0011 2
0009 4
0012 2
0012 4
0018 2
0016 4
0024 2
0023 4
0003 2
0003 4
0004 2
0004 4
0006 2
0005 4
0008 2
0008 4
3,7
3.4
4.8
6.6
5.6
8.0
0031 2
0031 4
31.0
0038 4 38.0
11.0
9.6
12.5
12.0
18.0
16.0
24.0
23.0
0048 2
0046 4
0062 2
0061 4
**
48.0
46.0
62.0
61.0
0075 2
0072 4
0088 2
0087 4
0105 2
0105 4
75,0
72,0
88,0
87,0
105,0
Table 16. Cable and fuse sizes for Vacon 100
I
L
[A]
Fuse
(class T)
[A]
Mains, motor, brake resistor
* and ground cable,
Cu
Terminal cable size
Main terminal Earth terminal
6
6
10
10
15
20
25
30
40
50
60
80
100
110
150
AWG14
AWG14
AWG14
AWG14
AWG14
AWG14
AWG10
AWG10
AWG8
AWG4
AWG4
AWG4
AWG2
AWG1
AWG1/0
AWG24-AWG10 AWG17-AWG10
AWG24-AWG10 AWG17-AWG10
AWG24-AWG10 AWG17-AWG10
AWG24-AWG10 AWG17-AWG10
AWG24-AWG10 AWG17-AWG10
AWG24-AWG10 AWG17-AWG10
AWG20-AWG5
AWG20-AWG5
AWG20-AWG5
AWG13-AWG0
AWG13-AWG0
AWG13-AWG0
AWG17-AWG8
AWG17-AWG8
AWG17-AWG8
AWG13-AWG2
AWG13-AWG2
AWG13-AWG2
AWG9-AWG2/0 AWG9-AWG2/0
AWG9-AWG2/0 AWG9-AWG2/0
AWG9-AWG2/0 AWG9-AWG2/0
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 35 Power cabling
Table 16. Cable and fuse sizes for Vacon 100
Frame Type
I
L
[A]
Fuse
(class T)
[A]
Mains, motor, brake resistor
* and ground cable,
Cu
Terminal cable size
Main terminal Earth terminal
MR8
MR9
0140 2
0140 4
0170 2
0170 4
0205 2
0205 4
0261 2
0261 4
0310 2
0310 4
140,0
170,0
205,0
261,0
310,0
200
225
250
350
400
AWG3/0
250 kcmil
350 kcmil
2*250 kcmil
2*350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
AWG1-350 kcmil
*. If you use a multi-conductor cable, NOTE that one of the conductors of the brake resistor cable remains unconnected. Use of single cable is also allowed provided that the minimum cable cross-sectional area given in this table is observed.
**. The 460V models require 90-degree wire to meet UL regulations
The cable dimensioning is based on the criteria of the Underwriters’ Laboratories UL508C:Cables must be PVC-isolated; Max ambient temperature +30°C, max temperature of cable surface +70°C; Use only cables with concentric copper shield; Max number of parallel cables is 9.
When using cables in parallel, NOTE HOWEVER that the requirements of both the cross-sectional area and the max number of cables must be observed.
For important information on the requirements of the earthing conductor, see standard Underwriters’ Laboratories
UL508C. For the correction factors for each temperature, see the instructions of standard Underwriters’ Laboratories UL508C.
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 36
5.2
Brake resistor cables
Vacon 100 AC drives are equipped with terminals for an optional external brake resistor. These terminals are marked with R+ and R- (MR4-MR6) or DC+/R+ and R- (MR7 and bigger). The recommended sizes for the brake resistor cables are listed in tables on pages 32 to 34.
9000.emf
If you use a multi-conductor cable, NOTE that one of the conductors of the brake resistor cable remains unconnected! Cut off the remaining conductor in order to avoid contact with a conducting component.
See brake resistor ratings on page 80.
5.3
Cable installation
• Before starting, check that none of the components of the AC drive is live. Read care-
fully the warnings in chapter 2.
• Place the motor cables sufficiently far from other cables
• Avoid placing the motor cables in long parallel lines with other cables.
• If the motor cables run in parallel with other cables note the minimum distances between the motor cables and other cables given in table below.
Distance between cables, [m]
0.3
1.0
Shielded cable, [m]
50
200
• The given distances also apply between the motor cables and signal cables of other systems.
• The maximum lengths of motor cables (shielded) are 100 m (MR4), 150 m (MR5 and
MR6) and 200 m (MR7 to MR9).
• The motor cables should cross other cables at an angle of 90 degrees.
•
If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
5
Power cabling vacon • 37
5.3.1
Frames MR4 to MR7
1
Strip the motor, mains and brake resistor cables as advised below.
Earth conductor Earth conductor
C1
A1 C2
D1
B1 D2
E
MAINS MOTOR
Figure 22. Stripping of cables
Frame
MR4 15
MR5 20
MR6 20
MR7 20
A1 B1 C1 D1 C2
35
40
90
80
10
10
15
20
20
30
60
80
7
10
15
20
35
40
60
80
Table 17. Cables stripping lengths [mm]
D2 E
Leave as short as possible
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
vacon • 38 Power cabling
2
Open the cover of the AC drive.
M4x55
3
9174.emf
Figure 23. Opening cover
Remove the screws of the cable protection plate. Do not open the cover of the power unit!
M4x8
9228.emf
Figure 24. Removing screws
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 39 Power cabling
4
Insert the cable grommets (included in the delivery) in the openings of the cable entry plate (included) as shown in the picture (upper pictures EU version, lower pictures US version).
5
5
9017.emf
Figure 25. Examples of cable entry plates with grommets, IP21
• Insert the cables - supply cable, motor cable and optional brake cable - in the openings of the cable entry plate.
• Then cut the rubber grommets open to slide the cables through. Should the grommets fold in while inserting the cable, just draw the cable back a bit to straighten the grommets up.
• Do not cut the grommet openings wider than what is necessary for the cables you are using.
IMPORTANT NOTE FOR IP54 INSTALLATION:
To meet the requirements of the enclosure class IP54, the connection between the grommet and the cable must be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible, the tightness of the connection must be ensured with insulation tape or a cable tie.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 40
6
9071.emf
Figure 26. Grommet cutting and sealing
Detach the cable clamps and the grounding clamps (Figure 27) and place the
cable entry plate with the cables in the groove on the AC drive frame (Figure 28).
M4x16
(2.2 Nm)
9229.emf
Figure 27. Detaching cable clamps
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 41 Power cabling
R+ RU V W
5
7
9232.emf
Figure 28. Cable entry plate and cables
Connect the stripped cables (see Figure 22 and Table 17) as shown in Figure 29.
• Expose the shield of all three cables in order to make a 360-degree connection with the cable clamp (1).
• Connect the (phase) conductors of the supply, brake and motor cables into their respective terminals (2).
• Form the rest of the cable shield of all three cables into “pigtails” and
make a grounding connection with a clamp as shown in Figure 29 (3).
Make the pigtails just long enough to reach and be fixed to the terminal - not longer.
L1L2L3 R+ R- U V W
3
3
1
2
9230.emf
Figure 29. Cable connection
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 42
Tightening torques of cable terminals:
Frame Type
Tightening torque
[Nm]/[lb-in.]
Power and motor terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
MR4
MR5
MR6
MR7
[Nm] lb-in.
0003 2—0012 2
0003 4—0012 4
0.5—0.6 4.5—5.3
1.5
0018 2—0031 2
0016 4—0031 4
1.2—1.5 10.6—13.3 1.5
0048 2—0062 2
0038 4—0061 4
10
0075 2—0105 2
0072 4—0105 4 8/15
*
88.5
1.5
70.8/132.8* 1.5
[Nm] lb-in.
13.3
13.3
13.3
13.3
*. Cable clamping (Ouneva Pressure Terminal Connector)
Table 18. Tightening torques of terminals
2.0
2.0
2.0
[Nm]
8/15* lb-in.
17.7
17.7
17.7
70.8/132.8*
8
Check the connection of the earth cable to the motor and the AC drive terminals marked with .
NOTE: Two protective conductors are required according to standard EN61800-
5-1. See Figure 30 and chapter Earthing and earth fault protection. Use an M5
size screw and tighten it to 2.0 Nm (17.7 lb-in.).
9233.emf
= M5; 2 Nm
Figure 30. Additional protective earthing connector
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 43 Power cabling
9 Re-mount the cable protection plate (Figure 31) and the cover of the AC drive.
5
1,5Nm
5.3.2
Figure 31. Re-mounting of cover components
Frames MR8 and MR9
1
Strip the motor, mains and brake resistor cables as advised below.
9234.emf
A1
Earth conductor
C1
B1
D1
Earth conductor
C2
D2
E
MAINS MOTOR
Figure 32.Stripping of cables
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 44
Frame
MR8
MR9
A1
40
40
B1
180
180
C1
25
25
D1
300
300
C2
25
25
Table 19. Cables stripping lengths [mm]
D2 E
300 Leave as short as
300 possible
2
MR9 only: Remove the main cover of the AC drive.
M4 x 10
9046.emf
Figure 33. Removing main cover (MR9)
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
5 vacon • 45
3
Remove the cable cover (1) and the cable fitting plate (2).
Power cabling
M4x8
M4 x 8
1
2
9029.emf
9039.emf
Figure 34. Removing cable cover and cable fitting plate (MR8).
1
M4 x 8
2
9041.emf
Figure 35. Removing cable cover and cable fitting plate (MR9).
M5 x 10
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling
4
MR9 only: Loosen the screws and remove the sealing plate.
vacon • 46
MR9
Figure 36.Removing sealing plate (MR9)
5
Remove the EMC shield plate.
9048.emf
M4x8
M5
Wing nut
M4x8
9026.emf
Figure 37. Removing EMC shield plate, left: MR8, right: MR9
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 47 Power cabling
6 Locate the terminals. OBSERVE the exceptional placement of motor cable terminals especially in frame MR8!
L1 L2 L3 DC-
DC+
R+ R-
U V W
R+
L1 L2 L3 DC- DC+ RU V W
7
9027.emf
Figure 38.Power terminals, left: MR8, right: MR9
Cut the rubber grommets open to slide the cables through. Should the grommets fold in while inserting the cable, just draw the cable back a bit to straighten the grommets up. Do not cut the grommet openings wider than what is necessary for the cables you are using.
5
9030.emf
Figure 39.Cutting the cable grommets
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 48
8
Place the grommet with the cable so that the frame end plate fits in the groove on the grommet, see Figure 40.
To meet the requirements of the enclosure class IP54, the connection between the grommet and the cable must be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible, the tightness of the connection must be ensured with insulation tape or a cable tie. As an
9
Figure 40. Placing the grommet
9040.emf
If you use thick cables insert the cable insulators in between the terminals in order to avoid contact between the cables.
9032.emf
Figure 41.Inserting the cable insulators
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
5 vacon • 49 Power cabling
10
Connect the cables stripped as shown in Figure 32.
• Connect the (phase) conductors of the supply, brake and motor cables into their respective terminals (a).
• Form the rest of the cable shield of all cables into “pigtails” and make a grounding connection as shown in Figure 42 (b) using the clamp from the
Accessories bag
.
• NOTE: If you use several cables on one connector observe the position of cable lugs on top of each other. See Figure 43 below.
L1 L2 L3
DC-
DC+
R+ R-
R+
L1 L2 L3 DC-DC+ RU V W a
U V W b a a b b
9025.emf
Figure 42. Connecting power cables, left: MR8, right: MR9
Connector
Cable lug Cable lug
9015.emf
Figure 43. Placing two cable lugs on top of each other
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 50
Tightening torques of cable terminals:
Frame
MR8
MR9
Type
Tightening torque
[Nm]/[lb-in.]
Power and motor terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding clamps
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
0140 2—0205 2
0140 4—0205 4
20
0261 2—0310 2
0261 4—0310 4
20
[Nm]
177
177 lb-in.
1.5
1.5
[Nm] lb-in.
13.3
13.3
Table 20. Tightening torques of terminals
20
20
[Nm]
177
177 lb-in.
11 Expose the shield of all three cables in order to make a 360-degree connection with the cable clamp.
9035.emf
Figure 44. Exposing cable shields
12
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 51
13 Re-attach then the cable fitting plate and then the cable cover.
Power cabling
M4x8
M4x8
9034.emf
Figure 45. Reattaching cable fitting plate and cover
14 MR9 only: Now re-mount the main cover (unless you want to make the control connections first).
5
M4x10
9047.emf
Figure 46. Re-mounting the main cover (MR9)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Power cabling vacon • 52
15
Check the connection of the earth cable to the motor and the AC drive terminals marked with .
NOTE: Two protective conductors are required according to standard EN61800-
5-1. See chapter Earthing and earth fault protection.
Connect the protective conductor using a cable shoe and an M8 screw (included in the Accessories bag ) on either of the screw connectors as advised in Figure 47.
9045.emf
Figure 47. Connecting the protective conductor
24-hour support +358 (0)201 212 575 • Email: [email protected]
5
vacon • 53 Power cabling
5.4
Installation in corner-grounded network
Corner grounding is allowed for the drive types rating from 72 A to 310 A at 380…480 V supply and from 75 A to 310 A at 208…240 V supply.
In these circumstances the EMC protection class must be changed to level C4 following the in-
structions in chapter 7.3 of this manual.
Corner grounding is not allowed for the drive types with rating from 3.4 A to 61 A at 380…480 V supply and 3.7 A to 62 A with 208…240 V supply.
5
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 54
6.
C
ONTROL UNIT
The control unit of the AC drive consists of the standard boards and additional boards (option
boards, see chapter 6.3) connected to the slot connectors of the control board.
10
1
12
2
3
9
11
8
7
6
5
4
9117.emf
Figure 48. Location of control unit components
Locations of essential control unit components:
1 = Terminals for standard I/O connections; See chapter 6.1.
2 = Ethernet connection
3 = Terminals for three relays connections (or optionally two relays and a termistor); See
4 = Optional boards; See chapter 6.3
5 = DIP switch for RS485 bus termination; See chapter 6.2.2
6 = DIP switch for Analogue output signal selection; See chapter 8.2.1
7 = DIP switch for isolating digital inputs from ground, see chapter 6.1.2.2
8 = DIP switch for Analogue input 2 signal selection; See chapter 8.2.1
9 = DIP switch for Analogue input 1 signal selection; See chapter 8.2.1
10 = RTC Battery
11 = Fan (in frames MR4 and MR5 and protection class IP54 only)
12 = Ethernet led status
When delivered from the factory, the control unit of the AC drive contains the standard controlling interface - the control terminals of the control board and the relay board - unless otherwise specifically ordered. On the next pages you will find the arrangement of the control I/O and the relay terminals, the general wiring diagram and the control signal descriptions.
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 55 Control unit
The control board can be powered externally (+24VDC, 1000mA, ±10%) by connecting the ex-
ternal power source to terminal #30, see page 56. This voltage is sufficient for parameter set-
ting and for keeping the control unit active. Note however that the measurements of the main circuit (e.g. DC-link voltage, unit temperature) are not available when the mains is not connected.
6.1
Control unit cabling
The standard control unit connections are presented in Figure 49 below. The control board is
equipped with 22 fixed control I/O terminals and the relay board with 8. All signal descriptions
6.1.1
Control cable sizing
The control cables shall be at least 0.5 mm 2
screened multicore cables, see Table 14. The max-
imum terminal wire size is 2.5 mm 2 for the relay and other terminals.
Find the tightening torques of the control and relay board terminals in Table below.
Table 21. Control cable tightening torques
Terminal screw
Nm
Tightening torque lb-in.
All I/O and relay terminals
(screw M3)
0.5
4.5
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 56
6.1.2
Control terminals and DIP switches
The terminals of the
Basic I/O board
and the
Relay boards
are described below. For more in-
formation on the connections, see chapter 8.2.1.
The terminals shown on shadowed background are assigned for signals with optional functions selectable with DIP switches. See more information in chapter 6.1.2.1 on page 57.
Reference potentiometer 1...10kΩ
2-wire transmitter
Actual value
I = (0)4...20mA
mA
1
2
3
4
5
15
16
17
12
13
14
8
9
6
7
10
11
18
19
30
+10 Vref
AI1+
AI1-
AI2+
AI2-
GND
DI4
DI5
DI6
CM
24Vout
GND
DI1
DI2
DI3
CM
24Vout
AO1+
AO1-/GND
+24Vin
Reference output
Analogue input, voltage or current
Analogue input common, (current)
Analogue input, voltage or current
Analogue input common, (current)
24V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Common for DI1-DI6
24V auxiliary voltage
I/O ground
Digital input 4
Digital input 5
Digital input 6
Common for DI1-DI6
Analogue signal
(+output)
Analogue output common
24V auxiliary input voltage
Serial bus, negative
Serial bus, positive
Relay output 1
Frequency reference
Frequency reference
Start forward
Start reverse
External fault
DI4
Open
Closed
Open
Closed
DI5
Open
Open
Closed
Closed
Freq. ref.
Analog input 1
Preset Freq. 1
Preset Freq. 2
Preset Freq. 3
Fault reset
Output frequency
Modbus RTU
*)
*)
RUN
RUN
24
25
26
21
22
23
32
33
A
B
RS485
RS485
RO1/1 NC
RO1/2 CM
RO1/3 NO
RO2/1 NC
RO2/2 CM
RO2/3 NO
RO3/2 CM
RO3/3 NO
Relay output 2
Relay output 3
FAULT
READY
9111.emf
Figure 49. Control I/O terminal signals on basic I/O board and connection example
*Digital inputs can be isolated from ground with a DIP switch, see chapter 6.1.2.2.
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 57 Control unit
6.1.2.1
Selection of terminal functions with dip switches
The shadowed terminals in Figure 49 allow for three functional selections each with the so-
called dip switches
. The switches have two positions, up and down. See figure to locate the switches and make appropriate selections for your requirements.
AI1
U = Voltage signal (Default!)
I = Current signal
AI2
U = Voltage signal
I = Current signal (Default!)
AO1
U = Voltage signal
I = Current signal (Default!)
RS-485 bus termination
OFF (Default!)
ON
9108.emf
Figure 50. Dip switches
6.1.2.2
Isolating digital inputs from ground
The digital inputs (terminals 8-10 and 14-16) on the basic I/O board can be isolated from
ground by changing the position of a dip switch on the control board. See Figure 51.
6
Digital inputs
Floating
Connected to GND (Default!)
9109.emf
Figure 51. Change position of this jumper to isolate the digital inputs from ground.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 58
6.2
Fieldbus connection
The AC drive can be connected to fieldbus either through RS485 or Ethernet. The connection for RS485 is on the basic I/O board (terminals A and B) and the connection for Ethernet is under the drive cover, left to the control keypad. See Figure 52.
DIP switches
Ethernet connector
RS485 terminals
A = Data- B = Data+
17 18 19 30
I/O terminals
Grounding bar
9113.emf
Figure 52. Ethernet and RS485 connections
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 59 Control unit
6.2.1
Prepare for use through ethernet
6.2.1.1
Ethernet cable data
1
Connector
Cable type
Cable length
Shielded RJ45 connector; NOTE: Max length of the connector 40mm.
CAT5e STP
Max .100m
Table 22. Ethernet cable data
Connect the Ethernet cable (see specification on page 59) to its terminal and run the cable through the rubber grommets as other I/O cables.
2
Protection class IP21: Cut free the opening on the AC drive cover for the Ethernet cable.
Protection class IP54: Cut the rubber grommets open to slide the cables through. Should the grommets fold in while inserting the cable, just draw the cable back a bit to straighten the grommets up. Do not cut the grommet openings wider than what is necessary for the cables you are using.
IMPORTANT: To meet the requirements of the enclosure class IP54, the connection between the grommet and the cable must be tight. Therefore, lead the first bit of the cable out of the grommet straight before letting it bend. If this is not possible, the tightness of the connection must be ensured with insulation tape or a cable tie.
6
9068.emf
Figure 53.Leading the cables, left: IP21, right: IP54
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 60
3
Remount the AC drive cover. NOTE: When planning the cable runs, remember to keep the distance between the Ethernet cable and the motor cable at a minimum
of 30 cm.
Ethernet cable
9056.emf
Figure 54. Distance between cables, left: IP21, right: IP54
For more detailed information, see the user’s manual of the fieldbus you are using.
6.2.2
Prepare for use through RS485
6.2.2.1
RS485 cable data
Connector
Cable type
Cable length
2.5 mm 2
STP (Shielded Twisted Pair), type Belden
9841 or similar
Depends on the used fieldbus. See respective bus manual.
Table 23. RS485 cable data
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 61 Control unit
Strip about 15 mm of the RS485 cable (see specification on page 60) and cut off
the grey cable shield. Remember to do this for both bus cables.
Leave no more than 10 mm of the cable outside the terminal block and strip the cables at about 5 mm to fit in the terminals. See picture below.
10
1
9189.emf
5
Also strip the cable now at such a distance from the terminal that you can fix it to the frame with the grounding clamp. Strip the cable at a maximum length of 15 mm. Do not strip the aluminum cable shield!
15
m m
9188.emf
2 Then connect the cable to its appropriate terminals on Vacon 100 AC drive standard terminal block, terminals A and B (A = negative, B = positive). See Figure 55.
6
Figure 55. Connecting the RS485 cable
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 62
Using the cable clamp included in the delivery of the drive, ground the shield of the RS485 cable to the frame of the AC drive.
Cable clamp
3
9200.emf
If the AC drive is the last device on the bus, the bus termination must be set.
Locate the DIP switches to the right of the control keypad of the drive and turn the switch for the RS485 bus termination resistor to position ON. Biasing is built in the termination resistor (resistance = 120 ohm). See also step 7 on page 63.
4
9110.emf
RS-485 bus termination
OFF
ON
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 63
Unless already done for the other control cables, cut free the opening on the AC drive cover for the
RS485 cable (protection class IP21).
5
Control unit
9201.emf
6
6
Remount the AC drive cover and run the RS485 cables as shown in picture.
NOTE: When planning the cable runs, remember to keep the distance between the Ethernet, I/O and Fieldbus cables and the motor cable at a
minimum of 30 cm. It is recommended to route the fieldbus cables away from the power cables as shown in the picture.
7
Fieldbus cables
9202.emf
The bus termination must be set for the first and the last device of the fieldbus line. See picture below. See also step 4 on page 62. We recommend that the first device on the bus and, thus, terminated was the Master device.
Vacon 100 Vacon 100 Vacon 100 Vacon 100
Termination activated
Fieldbus
= Bus termination
Resistance = 120 ohm
Termination deactivated
Vacon 100
9042.emf
Termination
activated with
DIP switch
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit
6.3
Option board installation
vacon • 64
13006.emf
NOTE! It is not allowed to add or replace option boards or fieldbus boards on an AC drive with the power switched on. This may damage the boards.
The option boards are placed in the board slots on the drive.
The table below gives information about which option board can be placed in which board slot on the drive.
Table 24. Option board compatibilities for board slots
Option board type
OPTB1
OPTB2
OPTB4
OPTB5
OPTB9
OPTBF
OPTBH
OPTBJ
OPTC4
OPTCP
OPTE3
OPTE5
OPTE6
OPTE7
Board description
I/O expander board
Thermistor relay board
I/O expander board
Relay board
I/O expander board
I/O expander board
Temperature measurement board
Safe Torque-Off board
LonWorks fieldbus board
Ethernet, Profinet I/O option board
Profibus DPV1 fieldbus board
Profibus DPV1 fieldbus board
(D type connector)
CanOpen fieldbus board
DeviceNet fieldbus board
Insertable in slots
C, D, E
C, D, E
C, D, E
C, D, E
C, D, E
C, D, E
C, D, E
E
D, E
D, E
D, E
E
D, E
D, E
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
Control unit vacon • 65
1
Open the cover of the AC drive.
DANGER
The relay outputs and other I/O-terminals may have a dangerous control voltage present even when the drive is disconnected from mains.
M4x55
6
9174.emf
Figure 56.Opening the main cover
Make sure that the sticker on the connector of the board says “dv” (dual voltage).
This indicates that the board is compatible with Vacon 100. See below:
2
Slot coding
9116.emf
NOTE: Incompatible boards cannot be installed on Vacon 100. Compatible boards have a slot coding that enable the placing of the board (see above)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 66
To reveal the option board slots, open the control unit cover as shown in picture below.
3
4
9235.emf
Close the cover of the control unit and remount the keypad.
D E
3024.emf
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 67 Control unit
6.4
Battery installation for Real Time Clock (RTC)
Enabling the functions of the
Real Time Clock (RTC)
requires that an optional battery is installed in the Vacon 100 drive.
Use ½ AA battery with voltage of 3.6V and capacity of 1000...1200 mAh (e.g. Panasonic BR-1/2
AA or Vitzrocell SB-AA02). The battery will last approximately ten years .
The place for the battery can be found in all frames left to the control keypad (see Figure 48).
Detailed information on the functions of the Real Time Clock (RTC) can be found in the Vacon
100 Application Manual.
6
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Control unit vacon • 68
6.5
Galvanic isolation barriers
The control connections are isolated from the mains potential and the GND terminals are permanently connected to ground. See Figure 57.
The digital inputs are galvanically isolated from the I/O ground. The relay outputs are additionally double-isolated from each other at 300VAC (EN-50178).
10Vref
GND
+24V
GND
AI1+
AI1-
AI2+
AI2-
DI1...
DI6
CM
AO1+
AO1-
+24Vin
RS485
RO1/1
RO1/2
RO1/3
RO2/1
RO2/2
RO2/3
TI1+
TI1-
CONTROL
UNIT
L1
L2
L3
POWER UNIT
U
V
W
9057.emf
DCDC+/R+ R-
Figure 57. Galvanic isolation barriers
24-hour support +358 (0)201 212 575 • Email: [email protected]
6
vacon • 69 Commissioning
7.
C
OMMISSIONING
Before commissioning, note the following directions and warnings:
13006.emf
13006.emf
13006.emf
13006.emf
13006.emf
Internal components and circuit boards of Vacon 100 (except for the galvanically isolated I/O terminals) are live when it is connected to mains potential. Coming into contact with this voltage is extremely dangerous and may cause death or severe injury.
The motor terminals U, V, W and the brake resistor terminals (R+/R- (MR4-MR6) or DC+/R+ and R- (MR7 and bigger)) are live when Vacon 100 is connected to mains, even if the motor is not running.
The control I/O-terminals are isolated from the mains potential. However, the
relay outputs and other I/O-terminals may have a dangerous control voltage present even when Vacon 100 is disconnected from mains.
Do not make any connections to or from the AC drive when it is connected to the mains.
After disconnecting the AC drive from the mains, wait 5 minutes before doing any work on the connections of Vacon100. Do not open the cover before this time has expired. After expiration of this time, use a measuring equipment to absolutely ensure that no voltage is present. Always ensure abscence of voltage before electrical work!
Before connecting the AC drive to mains make sure that the front and cable covers of Vacon 100 are closed.
9000.emf
7
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Commissioning vacon • 70
7.1
Commissioning of the drive
Read carefully the safety instructions in Chapter 1 and above and follow them.
After the installation:
Check that both the AC drive and the motor are grounded.
Check that the mains, brake and motor cables comply with the requirements given in
Check that the control cables are located as far as possible from the power cables, see
Check that the shields of the shielded cables are connected to protective earth marked with .
Check the tightening torques of all terminals
Check that the wires do not touch the electrical components of the drive.
Check that the common inputs of digital input groups are connected to +24V or ground of the I/O terminal or the external supply.
Check the quality and quantity of cooling air (chapter 4.2 and Table 13).
Check the inside of the AC drive for condensation.
Check the installation space for foreign objects.
Check that all Start/Stop switches connected to the I/O terminals are in Stop-posi- tion.
Before connecting the AC drive to mains: Check mounting and condition of all fuses and other protective devices.
Run the Startup Wizard (see the Application Manual).
7.2
Running the motor
MOTOR RUN CHECK LIST
13006.emf
13006.emf
Before starting the motor, check that the motor is mounted properly and ensure that the machine connected to the motor allows the motor to be started.
Set the maximum motor speed (frequency) according to the motor and the machine connected to it.
Before reversing the motor make sure that this can be done safely.
13006.emf
Make sure that no power correction capacitors are connected to the motor cable.
13006.emf
Make sure that the motor terminals are not connected to mains potential.
13006.emf
24-hour support +358 (0)201 212 575 • Email: [email protected]
7
vacon • 71 Commissioning
7.2.1
Cable and motor insulation checks
1.
Motor cable insulation checks
Disconnect the motor cable from terminals U, V and W of the AC drive and from the motor.
Measure the insulation resistance of the motor cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1M at ambient temperature of 20°C.
2.
Mains cable insulation checks
Disconnect the mains cable from terminals L1, L2 and L3 of the AC drive and from the mains. Measure the insulation resistance of the mains cable between each phase conductor as well as between each phase conductor and the protective ground conductor. The insulation resistance must be >1Mat ambient temperature of 20°C
3.
Motor insulation checks
Disconnect the motor cable from the motor and open the bridging connections in the motor connection box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at least the motor nominal voltage but not exceed 1000
V. The insulation resistance must be >1M at ambient temperature of 20°C. Always follow the instructions of the motor manufacturer.
7
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Commissioning vacon • 72
7.3
Installation in it system
If your supply network is an IT (impedance-grounded) system but your AC drive is EMC-protected according to class C2 you need to modify the EMC protection of the AC drive to EMClevel C4. This is done by removing the built-in EMC jumpers with a simple procedure described below:
Warning! Do not perform any modifications on the AC drive when it is connected to mains.
13006.emf
7.3.1
Frames MR4 to MR6
1
Remove the main cover of the AC drive (see page 38) and locate the jumpers con-
necting the built-in RFI-filters to ground. See Figure 58.
2
9236.emf
9237.emf
MR4 MR5
MR6
Figure 58. Locations of the EMC-jumpers in frames MR4 to MR6
9238.emf
Disconnect the RFI-filters from ground by removing the EMC-jumpers. NOTE!
The cable cover must be removed in MR4 and MR5 before the jumper(s) can be reached. See Figure 59.
Figure 59. Removing the jumper, MR6 as example
24-hour support +358 (0)201 212 575 • Email: [email protected]
9060.emf
7
vacon • 73 Commissioning
7.3.2
Frames MR7 and MR8
Follow the procedure described below to modify the EMC protection of the AC drive of frames
MR7 and MR8 to EMC-level C4.
1 Remove the main cover of the AC drive and locate the jumper. MR8 only: Push
down the grounding arm. See Figure 60.
2
9066.emf
Figure 60.Grounding arm, MR8
MR7 and MR8: Locate the EMC box under the cover. Remove the screws of the box cover to expose the EMC-jumper. Detach the jumper and re-fix the box cover.
7
Figure 61. Detaching the EMC jumper, MR7-8
9065 emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Commissioning vacon • 74
3 Additionally for MR7, locate the DC grounding busbar between connectors R- and U and detach the busbar from the frame by undoing the M4 screw.
9062.emf
Figure 62. MR7: Detaching the DC grounding busbar from frame
7.3.3
Frame MR9
Follow the procedure described below to modify the EMC protection of the AC drive of frame
MR9 to EMC-level C4.
1
Find the connector in the accessories bag. Remove the main cover of the AC drive and locate the place for the connector next to the fan. Push the connector in its place. See Figure 63.
Connector
Figure 63. Placing the connector
24-hour support +358 (0)201 212 575 • Email: [email protected]
9063.emf
7
7 vacon • 75 Commissioning
2
Further remove the extension box cover, the touch shield and the I/O plate with I/
O grommet plate. Locate the EMC jumper on the EMC board (see magnification below) and remove it.
9067.emf
Figure 64. Removing the EMC jumper
CAUTION! Before connecting the AC drive to mains make sure that the EMC protection class settings of the drive are appropriately made.
NOTE! After having performed the change write ‘EMC level modified’ on the sticker included in the Vacon 100 delivery (see below) and note the date. Unless already done, attach the sticker close to the name plate of the AC drive.
Product modified
Date:
EMC-level modified C2->T
Date:
Date: DDMMYY
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Commissioning vacon • 76
7.4
Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is recommended to ensure a trouble-free operation and a long lifetime of the drive. We recommend to follow the table below for maintenance intervals.
NOTE: Because of capacitor type (thin film capacitors), reforming of capacitors is not necessary.
Maintenance interval
Regularly and according to general maintenance interval
6...24 months (depending on environment)
24 months (depending on the environment)
3...6 years
6...10 years
10 years
Maintenance action
• Check tightening torques of terminals
• Check filters
• Check input and output terminals and control I/O terminals.
• Check operation of cooling fan
• Check for corrosion on terminals, busbars and other surfaces
• Check door filters in case of cabinet installation
• Clean heatsink and cooling tunnel
• Change internal IP54 fan
• Change main fan
• Replace the RTC battery
NOTE! See the service manual for information on cleaning tools.
24-hour support +358 (0)201 212 575 • Email: [email protected]
7
8 vacon • 77 Technical data
8.
T
ECHNICAL DATA
8.1
8.1.1
AC drive power ratings
Mains voltage 208-240 V
Table 25. Power ratings of Vacon 100, supply voltage 208-240V.
Mains voltage 208-240V, 50-60 Hz, 3~
0075
0088
0105
0140
0170
0205
0261
0310
0003
0004
0007
0008
0011
0012
0018
0024
0031
0048
0062
Drive type
Low
*
Continuous current I
L
[A]
11.0
12.5
18.0
24.0
3.7
4.8
6.6
8.0
31.0
48.0
10% overload current
[A]
12.1
13.8
19.8
26.4
4.1
5.3
7.3
8.8
34.1
52.8
Loadability Motor shaft power
Continuous current I
H
[A]
High*
50% overload current
[A]
Max current I
S
2s
8.0
11.0
12.5
18.0
2.6
3.7
4.8
6.6
25.0
31.0
12.0
16.5
18.8
27.0
3.9
5.6
7.2
9.9
37.5
46.5
16.0
19.6
25.0
36.0
5.2
7.4
9.6
13.2
46.0
62.0
230V supply
10% overload 40°C
[kW]
2.2
3.0
4.0
5.5
0.55
0.75
1.1
1.5
7.5
11.0
50% overload 50°C
[kW]
10% overload 40°C
[hp]
1.5
2.2
3.0
4.0
0.37
0.55
0.75
1.1
5.5
7.5
230V supply
3.0
4.0
5.0
7.5
0.75
1.0
1.5
2.0
10.0
15.0
50% overload 50°C
[hp]
2.0
3.0
4.0
5.0
0.5
0.75
1.0
1.5
7.5
10.0
62.0
75.0
88.0
105.0
143.0
170.0
208.0
261.0
310.0
68.2
82.5
96.8
115.5
154.0
187.0
225.5
287.1
341.0
48.0
62.0
75.0
88.0
114.0
140.0
170.0
211.0
251.0
72.0
93.0
112.5
132.0
171.0
210.0
255.0
316.5
376.5
96.0
124.0
150.0
176.0
210.0
280.0
340.0
410.0
502.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
90.0
11.0
15.0
18.5
22.0
30.0
37.0
45.0
55.0
75.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
125.0
15.0
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
*
NOTE! The rated currents in given ambient temperatures (in Table 29) are achieved only when
the switching frequency is equal to or less than the factory default.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical data vacon • 78
8.1.2
Mains voltage 380-500 V
Table 26. Power ratings of Vacon 100, supply voltage 380-500V.
Mains voltage 380-500V, 50-60 Hz, 3~
0031
0038
0046
0061
0072
0087
0105
0140
0003
0004
0005
0008
0009
0012
0016
0023
0170
0205
0261
0310
Drive type
Low
*
Continuous current I
L
[A]
31.0
38.0
46.0
61.0
72.0
87.0
105.0
140.0
9.6
12.0
16.0
23.0
3.4
4.8
5.6
8.0
170.0
205.0
261.0
10% overload current
[A]
34.1
41.8
50.6
67.1
79.2
95.7
115.5
154.0
10.6
13.2
17.6
25.3
3.7
5.3
6.2
8.8
187.0
225.5
287.1
Loadability Motor shaft power
Continuous current I
H
[A]
High*
50% overload current
[A]
Max current I
S
2s
23.0
31.0
38.0
46.0
61.0
72.0
87.0
105.0
8.0
9.6
12.0
16.0
2.6
3.4
4.3
5.6
140.0
170.0
205.0
34.5
46.5
57.0
69.0
91.5
108.0
130.5
157.5
12.0
14.4
18.0
24.0
3.9
5.1
6.5
8.4
210.0
255.0
307.5
46.0
62.0
76.0
92.0
122.0
144.0
174.0
210.0
16.0
19.2
24.0
32.0
5.2
6.8
8.6
11.2
280.0
340.0
410.0
400 V supply
10% overload 40°C
[kW]
37.0
45.0
55.0
75.0
15.0
18.5
22.0
30.0
4.0
5.5
7.5
11.0
1.1
1.5
2.2
3.0
90.0
110.0
132.0
30.0
37.0
45.0
55.0
11.0
15.0
18.5
22.0
3.0
4.0
5.5
7.5
0.75
1.1
1.5
2.2
75.0
90.0
110.0
480 V supply
50% overload 50°C
[kW]
10% overload 40°C
[hp]
50% overload 50°C
[hp]
20.0
25.0
30.0
40.0
50.0
60.0
75.0
100.0
5.0
7.5
10.0
15.0
1.5
2.0
3.0
4.0
125.0
150.0
200.0
40.0
50.0
60.0
75.0
15.0
20.0
25.0
30.0
4.0
5.0
7.5
10.0
1.0
1.5
2.0
3.0
100.0
125.0
150.0
310.0
341.0
251.0
376.5
502.0
160.0
132.0
250.0
200.0
*
NOTE! The rated currents in given ambient temperatures (in Table 29) are achieved only when
the switching frequency is equal to or less than the factory default.
24-hour support +358 (0)201 212 575 • Email: [email protected]
8
8 vacon • 79 Technical data
8.1.3
Definitions of overloadability
Low overload = Following continuous operation at rated output current, 110% rated output current (I
L
) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated output
Example: current (I
L
).
If the duty cycle requires 110% rated current for 1 min in every 10min, the remaining 9 min must be at approximately 98% rated current or less to maintain an r.m.s value
>=100%.
Current
I
L*110%
I
L*110%
I
L
1 min 9 min
Time
9011.emf
Figure 65. Low overload
High overload = Following continuous operation at rated output current, 150 % rated output current (I
H
) for 1 min, followed by a period of load current less than rated current, and of such duration that the r.m.s output current, over the duty cycle, does not exceed rated
Example: output current (I
H
).
If the duty cycle requires 150% rated current for 1 min in every 10min, the remaining 9 min must be at approximately 92% rated current or less to maintain an r.m.s value
>=100%.
Current
I
H*150%
I
H*150%
I
H
1 min 9 min
Time
9009.emf
Figure 66. High overload
NOTE! For more information, please refer to standard IEC61800-2, chapter 5.2.2 (IEC: 1998)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical data vacon • 80
8.1.4
Brake resistor ratings
Make sure that the resistance is higher than the minimum resistance defined. The power handling capacity must be sufficient for the application.
Recommended brake resistor types and calculated resistances for Vacon 100 AC drives:
Frame Duty cycle Type of brake resistor
Resistance
[ohm]
63.0
MR4
MR5
MR6
MR7
MR8
MR9
Light duty
*
Heavy duty*
Light duty
Heavy duty
Light duty
Heavy duty
Light duty
Heavy duty
Light duty
Heavy duty
Light duty
Heavy duty
BRR 0022 LD 5
BRR 0022 HD 5
BRR 0031 LD 5
BRR 0031 HD 5
BRR 0045 LD 5
BRR 0045 HD 5
BRR 0061 LD 5
BRR 0061 HD 5
BRR 0105 LD 5
BRR 0105 HD 5
BRR 0300 LD 5
BRR 0300 HD 5
63.0
41.0
41.0
21.0
21.0
14.0
14.0
6.5
6.5
3.3
3.3
*
Light duty cycle for brake resistor cyclic use (one LD pulse within 120-second period). The light duty resistor is rated for a 5-second ramp from full power to zero;
Heavy duty cycle for brake resistor cyclic use (one HD pulse within 120-second period). The heavy duty resistor is rated for a 3-second full power braking with a 7second ramp to zero
Predefined power pulses
Heavy duty
Light duty
9252.emf
Time
Figure 67. LD and HD pulse shapes
24-hour support +358 (0)201 212 575 • Email: [email protected]
8
8 vacon • 81 Technical data
100
Brake power [%]
0
0 3 5 10 120
123 125 130
Time [s]
Figure 68. Duty cycles of LD and HD pulses
240
9253.emf
Table 27. Minimum resistance value and braking power with recommended resistor types, mains voltage 208-240V
Frame
MR4
MR5
MR6
MR7
MR8
MR9
Mains voltage 208-240 V, 50/60 Hz, 3~
Brake min. resistance
[ohm]
Brake power
*
@405 Vdc
[kW]
30.0
20.0
10.0
5.5
3.0
1.4
*
With recommended resistor types
2.6
3.9
7.8
11.7
25.2
49.7
Table 28. Minimum resistance value and braking power with recommended resistor types, mains voltage 380-500V
Type
MR4
MR5
MR6
MR7
MR8
MR9
Mains voltage 380-500 V, 50/60 Hz, 3~
Brake min. resistance
[ohm]
Brake power
*
@845 Vdc
[kW]
63.0
41.0
21.0
14.0
6.5
3.3
*
With recommended resistor types
11.3
17.0
34.0
51.0
109.9
216.4
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical data vacon • 82
8.2
Vacon 100 - technical data
Table 29. Vacon 100 technical data
Mains connection
Motor connection
Control characteristics
Input voltage U in
Starting delay
Output voltage
208...240V; 380…500V; -10%…+10%
Input frequency 50...60 Hz -5...+10%
Connection to mains Once per minute or less
4 s (MR4 to MR6); 6 s (MR7 to MR9)
0-U in
Continuous output current
Switching frequency
(see parameter
P3.1.2.3)
I
L
: Ambient temperature max. +40°C overload 1.1 x I
L
(1 min./10 min)
I
H
: Ambient temperature max. +50°C overload 1.5 x I
H
(1 min./10 min)
Output frequency 0…320 Hz (standard)
Frequency resolution 0.01 Hz
1.5…10 kHz;
Defaults:
MR4-6: 6 kHz (except 0012 2, 0031 2, 0062 2,
0012 4, 0031 4 and 0061 4: 4 kHz)
MR7: 4 kHz
MR8-9: 3 kHz
Automatic switching frequency derating in case of overload.
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 8…320 Hz
Acceleration time
Deceleration time
0.1…3000 sec
0.1…3000 sec
24-hour support +358 (0)201 212 575 • Email: [email protected]
8
8 vacon • 83 Technical data
Ambient conditions
Ambient conditions
(cont.)
EMC (at default settings)
Noise level
Safety
Table 29. Vacon 100 technical data
Ambient operating temperature
I
L
current: -10°C (no frost)…+40°C
I
H
current: -10°C (no frost)…+50°C
Max. operating temperature: +50°C
Storage temperature -40°C…+70°C
Relative humidity 0...95% R
H
, non-condensing, non-corrosive
Air quality:
• chemical vapours
• mechanical particles
Altitude
Vibration
EN61800-5-1/
EN60068-2-6
Tested according to IEC 60068-2-60 Test Ke:
Flowing mixed gas corrosion test, Method 1
(H
2
S [hydrogen sulfide] and SO
2
[sulfur dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
100% load capacity (no derating) up to 1,000m
1-% derating for each 100m above 1,000m
Max. altitudes:
208...240V: 4,000m (TN and IT systems)
380...500V: 4,000m (TN and IT systems)
Voltage for relay outputs:
Up to 3,000m : Allowed up to 240V
3,000m...4,000m: Allowed up to 120V
Corner-grounding: up to 2,000m only (see
5…150 Hz
Displacement amplitude 1 mm (peak) at
5…15.8 Hz (MR4…MR9)
Max acceleration amplitude 1 G at
15.8…150 Hz (MR4…MR9)
Shock
EN61800-5-1
EN60068-2-27
Enclosure class
Immunity
Emissions
Average noise level
(min...max) sound pressure level in dB(A)
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
IP21/Type 1 standard in entire kW/HP range
IP54/Type 12 option
NOTE! Keypad or panel adapter required for
IP54/Type 12
Fulfils EN61800-3 (2004), first and second environment
+EMC2: EN61800-3 (2004), Category C2
The drive can be modified for IT-networks.
MR4: 45...56
MR5: 57...65
MR7: 43...73
MR8: 58...73
MR6: 63...72
MR9: 54...75
Sound pressure depends on the cooling fan speed which is controlled in accordance with the drive temperature.
EN 61800-5-1 (2007), CE; (see unit nameplate for more detailed approvals)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical data
Protections vacon • 84
Table 29. Vacon 100 technical data
Overvoltage trip limit
Undervoltage trip limit
240-volt drives: 456 V
500-volt drives: 911 V
Depends on supply voltage (0,8775*supply voltage):
Supply voltage 240 V: Trip limit 211 V
Supply voltage 400 V: Trip limit 351 V
Supply voltage 500 V: Trip limit 421 V
Earth fault protection Yes
Mains supervision Yes
Motor phase supervision Yes
Overcurrent protection Yes
Unit overtemperature protection
Yes
Motor overload protection Yes
Motor stall protection Yes
Motor underload protection
Short-circuit protection of +24V and +10V reference voltages
Yes
Yes
24-hour support +358 (0)201 212 575 • Email: [email protected]
8
8 vacon • 85 Technical data
8.2.1
Technical information on control connections
Table 30. Technical information on standard I/O board
Standard I/O board
Terminal Signal Technical information
1
2
3
4
5
6
7
Reference output
Analogue input, voltage or current
Analogue input common
(current)
Analogue input, voltage or current
Analogue input common
(current)
24V aux. voltage
I/O ground
+10V, +3%; Maximum current 10 mA
Analogue input channel 1
0- +10V (Ri = 200 k
)
4-20 mA (Ri =250
)
Resolution 0.1 %, accuracy ±1 %
Selection V/mA with dip-switches (see page 57)
Short-circuited protected.
Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
Analogue input channel 2
Defauit: 4-20 mA (Ri =250
)
0-10 V (Ri=200k
)
Resolution 0.1 %, accuracy ±1 %
Selection V/mA with dip-switches (see page 57)
Short-circuited protected.
Differential input if not connected to ground;
Allows 20V differential mode voltage to GND
+24V, ±10%, max volt. ripple < 100mVrms; max. 250mA
Short-circuit protected.
Ground for reference and controls (connected internally to frame earth through 1M
)
8
9
10
Digital input 1
Digital input 2
Digital input 3
Positive or negative logic
Ri = min. 5k
0...5V = “0”
15…30V = "1"
11 Common A for DIN1-DIN6
Digital inputs can be disconnected from ground, see chapter 6.1.2.2.
12
13
24V aux. voltage
I/O ground
+24V, ±10%, max volt. ripple < 100mVrms; max. 250mA
Short-circuit protected
Ground for reference and controls (connected internally to frame earth through 1M
)
14
15
16
30
A
B
Digital input 4
Digital input 5
Digital input 6
Positive or negative logic
Ri = min. 5k
0...5V = “0”
15…30V = "1"
17 Common A for DIN1-DIN6
Digital inputs can be isolated from ground, see chapter 6.1.2.2.
18 Analogue signal (+output) Analogue output channel 1, selection 0 -20mA, load <500
19 Analogue output common
Default: 0-20 mA
0-10V
Resolution 0.1 %, accuracy ±2 %
Selection V/mA with dip-switches (see page 57)
Short-circuited protected.
24V auxiliary input voltage Can be used as external power backup for the control unit.
RS485
RS485
Differential receiver/transmitter
Set bus termination with dip switches (see page 57). Termination resis-
tance = 220 ohm.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Technical data vacon • 86
Standard relay board (+SBF3)
Terminal Signal Technical information
21
22
23
24
25
26
32
33
Relay output
1
*
Change-over contact (SPDT) relay. 5,5 mm isolation between channels.
Switching capacity 24VDC/8A
Min.switching load
250VAC/8A
125VDC/0.4A
5V/10mA
Relay output
2*
Change-over contact (SPDT) relay. 5,5 mm isolation between channels.
Switching capacity 24VDC/8A
250VAC/8A
Min.switching load
125VDC/0.4A
5V/10mA
Relay output 3*
Normally-open (NO or SPST) contact relay. 5,5 mm isolation between channels.
Switching capacity 24VDC/8A
250VAC/8A
Min.switching load
125VDC/0.4A
5V/10mA
*
If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to standard EN 60204-1, section
7.2.9
Optional relay board (+SBF4)
Terminal
21
22
23
24
25
26
Signal Technical information
Relay output 1
*
Change-over contact (SPDT) relay. 5,5 mm isolation between channels.
Switching capacity 24VDC/8A
250VAC/8A
Min.switching load
125VDC/0.4A
5V/10mA
Relay output 2*
Change-over contact (SPDT) relay. 5,5 mm isolation between channels.
Switching capacity 24VDC/8A
250VAC/8A
Min.switching load
125VDC/0.4A
5V/10mA
28
29
TI1+
TI1-
Thermistor input. Rtrip = 4.7 k
(PTC); Measuring voltage 3.5V
*
If 230VAC is used as control voltage from the output relays, the control circuitry must be powered with a separate isolation transformer to limit short circuit current and overvoltage spikes. This is to prevent welding on the relay contacts. Refer to standard EN 60204-1, section
7.2.9
24-hour support +358 (0)201 212 575 • Email: [email protected]
8
Find your nearest Vacon office on the Internet at: www.vacon.com
Manual authoring: [email protected]
Vacon Plc.
Runsorintie 7
65380 Vaasa
Finland
Subject to change without prior notice
© 2012 Vacon Plc.
Document ID:
Order code:
Rev. C
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 72 Commissioning
- 73 Commissioning of the drive
- 73 Running the motor
- 74 7.2.1 Cable and motor insulation checks
- 75 Installation in it system
- 75 7.3.1 Frames MR4 to MR
- 76 7.3.2 Frames MR7 and MR
- 77 7.3.3 Frame MR
- 79 Maintenance
- 80 Technical data
- 80 AC drive power ratings
- 80 8.1.1 Mains voltage 208-240 V
- 81 8.1.2 Mains voltage 380-500 V
- 82 8.1.3 Definitions of overloadability
- 83 8.1.4 Brake resistor ratings
- 85 Vacon 100 - technical data
- 88 8.2.1 Technical information on control connections
- 82 Tel. +358 (0) 201 2121 • Fax +358 (0)