Below you will find brief information for rooftop unit 50LJS 007, rooftop unit 50TJS 008, rooftop unit 50TJS 009, rooftop unit 50TJS 012, rooftop unit 50TJS 014. This document provides step-by-step instructions on how to install, start-up and service single-package rooftop units. It includes safety considerations, physical data, electrical data, wiring and piping diagrams, troubleshooting and start-up checklist.
Advertisement
Advertisement
50LJS/TJS 007-014
Single-
Package Rooftop Units
(50/60 Hz)
Insta llation, StartUp and ervice I Instruct tions
SAFETY CONSIDERATIONS
CONTENTS
Safety Consideration………………………
Base unit Dimentions ......…………………..
Physical Data ...……………………………..
Installation…………………………………..
Electrical data .…………………………….. 12
Pre-Start-Up………………………………..
Start-Up……………………………………..
Operating Sequence ………………………
Service………………………………………
Wiring & Piping Diagrams…………………
Troubleshooting…………………………….
Start-Up Checklist…………………………..
Page.
1
2
5
8
12
13
16
16
19
32
34
INSTALLATION
Step 1 — Provide Unit Support
Step 2 — Field Fabricate Ductwork —
Step 4 — Rig and Place Unit —
Step 3 — Install External Trap for Condensate
Drain —
2
ROOF CURB
ACCESSORY
“A”
CRRFCURB003A00 1 ′-2″ [356]
CRRFCURB004A00 2 ′-0″ [610]
UNIT SIZE
50TFF
008-014
“B”
2 ′-8 7 /
16
″
[827]
1
“C”
′-10 15 /
16
[583]
″
“D” ALT
DRAIN
HOLE
1 3 /
4
″
[44.5]
“E”
GAS
3 /
4
″
[19] NPT
1 /
2
″
[12.7] NPT
3 /
4
″
[19] NPT
1 1
1 1
“F”
POWER
3 /
4
″ [19] NPT
/
4
″ [31.7] NPT
3 /
/
4
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels, 1
″ thick polyurethane foam, 1 3 /
4
lb density.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
4
″ [19] NPT
″ [31.7] NPT
1 /
2
“G”
CONTROL
1 /
2
″ [12.7]
NPT
″ [12.7]
NPT
CONNECTOR
PACKAGE
ACCESSORY
CRBTMPWR001A00
CRBTMPWR002A00
CRBTMPWR003A00
CRBTMPWR004A00
6. Service clearance 4 ft on each side.
7.
Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
002A00 are for thru-the-curb connections.
Packages CRBTMP003A00 and 004A00 are for thru-the-bottom connections.
Fig. 2 — Roof Curb Details
3
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
0.5
B-C
1.0
A-C
1.0
Fig. 3 — Unit Leveling Tolerance
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Connection
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
Fig. 5 — External Trap Condensate Drain
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer.
UNIT
50TJ
MAX
WEIGHT lb kg in.
‘‘A’’ mm
DIMENSIONS in.
‘‘B’’ mm in.
‘‘C’’ mm
008 755 342 77.42
1967 40.25
1022 41.31
1050
009 760 345 77.42
1967 40.25
1022 41.31
1050
012 915 415 77.42
1967 40.25
1022 49.31
1253
014 930 422 77.42
1967 40.25
1022 49.31
1253
All panels must be in place when rigging.
Fig. 6 — Rigging Details
4
Fig. 7 — Dimensional Drawing
5
Physical data (60Hz) — English
UNIT MODEL LJS007 TJS008 009 012 014
Electrical Configuration
Nominal Cooling Capacity
OPERATING WEIGHT
V-Ph-Hz 460,380,208 and 230 -3-60
TR 6 7.5 8.5 10 12.5
Kbtu/hr 72 90 102 120 150
Unit lbs 520
Economizer lbs
Roof Curb lbs 115
755 760
44
143
44
143 143 143
COMPRESSOR
Type
Quantity no.
Oil (per compressor) oz 77 47
Hermetic,
2
52 52
2
77
REFRIGERANT
Type
Operating Charge / Circuit lbs-oz 9 - 0 4 - 14 6 - 14 5 – 14 8- 10
CONDENSER FAN
Type
Quantity No
Nominal CFM
Motor hp … rpm
CONDENSER COIL
Type
Rows … Fins/inch
Total Face Area
CFM hp…rpm no….per in. sq. ft
4100
1/3 ….850
2 …17
12.25
7150
1/4 …. 1100
Propeller
2 2
22 22
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
1 …17
20.5
7150
1/4 …. 1100
2 …17
18
7700
1/4 …. 1100
2 …17
17.42
7700
1/4 …. 1100
2 …17
25
EVAPORATOR FAN
Type
Size
Drive Type
CFM
Nominal Motor hp, rpm
EVAPORATOR COIL
Type
Rows … Fins / inch
Total Face Area
HIGH PRESSURE SWITCH
Standard Compressor IPRV setting
Cutout / Reset (Auto)
In.
3 ….15
8 8
Centrifugal
1
10 x10 15 x15 15 x15
Belt Driven
2.9 , 1725
3 …..15
426
15 x15
2.9 , 1725
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
3 …. 15
10
320
27 / 44
1
15 x15
CFM 2100 2800 3000 4000 4500 hp, rpm no…per in. sq. ft
Psig
Psig
1.7 , 1725
4 …15
5.5
2.9 , 1725
LOW PRESSURE SWITCH
Cutout / Reset
FREEZE-PROTECTION SWITCH
Opens / Closes
Psig
0 F
OUTDOOR AIR INLET SCREENS
Type
Quantity no
Size in. 20x24x1
RETURN AIR FILTERS
Type
Quantity no 2
Size in.
4
16x25x2
3.7 , 1725
4 …. 15
11.1
30 ± 5 / 45 ± 5
Cleanable
20x25x1
1
16x25x1
Throw
4
6
Physical data (50 Hz) — English
UNIT MODEL
Electrical Configuration
Nominal Cooling Capacity
LJS007 LJ008
V-PH-Hz
TR 6
Kbtu/hr 72 78
TJS008 TJS009
400 - 3 – 50 (+/- 10%)
7.0
84
9.0
108
TJS012
10
120
TJS014
12.0
144
OPERATING WEIGHT
760 915 930
Roof Curb lbs 115
44
143
COMPRESSOR
Oil (per compressor)
REFRIGERANT
Operating Charge
Circuit 1
Circuit 2
CONDENSER FAN
Quantity …. Diameter
Nominal CFM
Motor* hp … rpm
CONDENSER COIL
Rows … Fins/inch
Total Face Area type Scroll Hermetic, Reciprocating
2 oz 53 53 55 type R -22
65 lbs-oz lbs-oz
8 - 0
-
9 - 6
-
5 - 4
5 - 4
6 - 3
6 - 3
6 - 5
6 - 5 type Propellar no….in.
1 …. 26
CFM hp…rpm
4300
1/3 ….960
8650
2 …. 22
8650 9225
1/3 …. 1100 type no….per in.
sq. ft 12.25
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2 …17 1 …17 2 …17
13.1
20.5
18 17.42
Scroll
53
7 - 12
7 - 12
9225
25
EVAPORATOR FAN
Quantity …. Size
Drive Type
Nominal CFM
Input Watts @ Nominal CFM
Motor** hp, rpm
Max. Continuous Bhp
Motor Pulley Pitch Dia.
Fan Pulley Pitch Dia.
EVAPORATOR COIL
Rows … Fins / inch
Total Face Area no….in.
type
CFM
Watts hp , rpm hp in.
in.
type no…per in.
sq. ft
Psig
1 …10 x 10
2200
800
2.4
4.4
5.19
1 …. 15 x15
2800
Belt Driven
3000
900 1000
1.5, 1425
2.4
3.4
5.5
4000
1500
2 , 1425
2.9
4.4
7
Enhanced Copper Tubes, Aluminum Double-Wavy Fins
4 …15 3 ….15
5.5
8 10
4750
2000
3 , 1425
3.7
5
4 …. 15
11.1
HIGH PRESSURE SWITCH
Standard Compressor IPRV setting
Cutout / Reset (Auto)
426
320
LOW PRESSURE SWITCH
Psig
Cutout / Reset (Manual) 27 / 44
FREEZE-PROTECTION SWITCH
Opens / Closes
0 F
30 ± 5 / 45 ± 5
OUTDOOR AIR INLET SCREENS type Cleanable
(With Optional Economizer)
Quantity …. Size no….in.
1 ….20x24x1
1 … 20x25x1 + 1 ….16x25x1
RETURN AIR FILTERS
Quantity …. Size type Throw away no….in.
* Condenser Motor Efficiency: 80%.
**Evaporator Motor Efficiency: LJS007,008 = 81%. TJS008-014 = 85%.
2 ….16x25x2
4 …. 16x20x2 4 … 20x20x2
7
Step 5 — Make Electrical Connections
8
LEGEND
C — Contactor
COMP(S) — Compressor(s)
IFC — Indoor (Evaporator)
NEC
TB
Fan Contactor
— National Electrical
Code
— Terminal Block
Terminal Block
Connection
Splice Connection
Field Wiring
Factory Wiring
Fig. 8 — Power Wiring Connections
Table 3 - Electrical Data – 50LJS007, 50TJS008 – 014 ( 60 Hz )
UNIT
MODEL
50LJS
007
50TJS
008
50TJS
009
50TJS
012
50TJS
014
NOMINAL
V-Ph-Hz
208/230-3-
60
460-3-60
208/230-3-
60
460-3-60
208/230-3-
60
460-3-60
208/230-3-
60
460-3-60
208/230-3-
60
460-3-60
IFM
TYPE
STD
STD
STD
STD
STD
VOLTAGE
RANGE
COMPRESSOR
MIN MAX RLA
(ea)
187 254 20
414 508 8.4
187 254 11.7
OFM (ea) IFM ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
LRA
146
73
78
Qty Hp FLA FLA NOMINAL KW**
1 1/3 1.9
1 -1
4
1.8
2 1/4 1.4
7.5
FLA MCA
4.9/6.5 13.8/15.7
34.7/34.7
7.6/10.5 22.2/25.3
34.7/38
12.0/16.0 33.6/38.4
15.8/21.0 44.4/50.4
19.9/26.5 55.8/63.7
48.1/54.4
61.6/69.4
75.9/86
MOCP FLA
42/42
42/42
42/42
50/60
70/80
80/90
20
20
20
25
32/32
32/32
32/34
43/49
56/63
69/78
15
15
18
21
40
45
45/45
34
37
42/42
7.8/9.6 21.7/25.0
40.1/40.1
12.0/14.7 33.4/38.5
48.9/55.4
45/45
50/60
42/42
45/51
18.6/22.8 51.7/59.7
71.9/81.8
80/90 66/75
24.0/29.4 66.7/77.0
90.6/103.5 100/1110 83/95
SIZE
LRA
173/173
92
260/260
414 508 6.6
187 254 13.7
414 508 7.5
187 254 15
414 508 8.8
187 254 20
414 508 8.4
53
106
62
114
79
146
73
2 1/2 1.8
3.4
2 1/4 1.4
7.5
2 1/2 1.8
3.4
2 1/4 1.4
7.5
2 1/2 1.8
3.4
2 1/4 1.4
10.6
2 1/2 1.8
4.8
31.9/39.0 88.4/102.0 117.7/134.8 125/150 108/124
20 19
30 25
30
50
60
26
41
49
7.8/9.6 21.7/25.0
44.6/44.6
12.0/14.7 33.4/38.5
48.9/55.4
70
50/50
50/50
50/60
61
47/47
47/47
47/51
18.6/22.8 51.7/59.7
71.9/81.8
80/90 66/75
24.0/29.4 66.7/77.0
90.6/103.5
100/110 83/95
31.9/39.0 88.4/102.0 117.7/134.8 125/150 108/124
25
25
30
50
60
70
50/50
24
24
26
41
49
61
47/47
7.8/9.6 21.7/25.0
44.6/44.6
12.0/14.7 33.4/38.5
48.9/55.4
50/50
60/60
47/47
47/51
24.0/29.4 66.7/77.0
90.6/103.5
100/110 83/95
31.9/39.0 88.4/102.0 117.7/134.8 125/150 108/124
37.5/46.0 104.2/120.3 137.5/157.6 150/175 127/147
25
30
24
26
50
60
70
70
80/80
80/80
41
49
61
72
68/68
68/68 7.8/9.6 21.7/25.0
65.2/65.2
12.0/14.7 33.4/38.5
65.2/65.2
70/70 68/68
24.0/29.4 66.7/77.0
96.6/109.5
100/110 89/101
31.9/39.0 88.4/102.0 123.7/140.8 125/150 114/129
37.5/46.0 104.2/120.3 143.5/163.6 150/175 132/151
40
40
50
60
70
80
31
31
44
51
63
75
153
351/351
176
337/337
167
383/383
192
9
Table 4 - Electrical Data – 50LJS007, 50TJS008 – 014 ( 60 Hz Cont.)
UNIT
MODEL
NOMINAL
V-Ph-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPRESSOR
(ea)
OFM (ea) IFM ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
SIZE
MIN MAX RLA LRA Qty Hp FLA FLA NOMINAL FLA MCA MOCP FLA LRA
50LJS
007
50TJS
008
50TJS
009
50TJS
012
50TJS
014
380-3-60 STD 342 418 10.7 70 1 1/3 0.8 2.5
380-3-60 STD 342 418 5.8 54 2 1/4 0.8 4.3
380-3-60 STD 342 418 8.2 42 2 1/4 0.8 4.3
380-3-60 STD 342 418 10.4 55 2 1/4 0.8 4.3
380-3-60 STD 342 418 10.7 70 2 1/4 0.8 6.1
-
-
-
-
-
-
-
-
17.1 22 18.5
100
- 19.01 26 20 145
- 24.38 27.01 25 127
29.3 32.5 26 155
32 36 30 193
Table 5 - Electrical Data – 50LJS007, 50TJS008 – 014 ( 50 Hz )
UNIT
MODEL
NOMINAL
V-Ph-Hz
IFM
TYPE
VOLTAGE
RANGE
COMPRESSOR
(ea)
OFM (ea) IFM ELECTRIC HEAT* POWER SUPPLY
DISCONNECT
MIN MAX RLA LRA Qty Hp FLA FLA NOMINAL MCA MOCP FLA
SIZE
LRA
50LJS
007
400-3-50 STD 342 440 12 100 1 1/3 1.5 2.6
50TJS
008
400-3-50 STD 342 440 6.6 53 2 1/2 1.8 3.4
50TJS
009
400-3-50 STD 342 440 7.5 62 2 1/2 1.8 3.4
50TJS
012
400-3-50 STD 342 440 9 82 2 1/2 1.8 3.4
4.2 6.1
19.1 --
8 11.5
19.2
16 23.2
35 --
17.7 25.6
37.5 --
9.7 13.9
21.7 19
11.5 16.5
24.9
19.3 27.8
39.1 35
22.9 33.1
45.6 41
29 41.8
56.5 51
9.7 13.9
21.7 21
11.5 16.5
24.9
19.3 27.8
39.1 35
22.9 33.1
45.6 41
29 41.8
56.5 51
9.7 16.5
23.9 24
19.3 27.8
38.1
22.9 33.1
44.6 41
29 41.8
55.5 51
34.7 50.1
65.9 61
50TJS
014
400-3-50 STD 342 440 12 100 2 1/2 1.8 4.8
19.3 30.3
43.9
22.9 36.1
51.1 47
29 45.5
62.8 58
34.7 54.6
74.2 68
10
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES
LEGEND
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v,
480 v, and 600 v. Heaters are rated at 240 v, 480 v, or 600 v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. To determine heater capacity at actual unit voltage, multiply 240 v, 480 v, or 600 v capacity by multipliers found in table on page 51.
†Used to determine minimum disconnect size per NEC.
**Heaters are field installed only.
†† Fuse or HACR circuit breaker.
||Fusing in single point box provides the required branch circuit protection.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The
Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 100 x max voltage deviation from average voltage average voltage
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
452 + 464 + 455
3
=
1371
3
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
11
RACEWAY
HOLE IN
END PANEL
(HIDDEN)
Fig. 9 — Conduit Installation
DISCONNECT
MOUNTING
LOCATION
EMT OR RIGID
CONDUIT
(FIELD SUPPLIED)
BRACKET AND
CONDUIT DRIP
BOOT
CENTER
POST
Fig. 12 — Field Control Wiring Raceway
Step 6 — Adjust Factory-Installed Options
MAIN
CONTROL
BOX
COM-
PRESSOR
NO. 2
COM-
PRESSOR
NO. 1
SINGLE
POINT
BOX
SINGLE
POINT BOX
MOUNTING SCREW
EMT — Electro-Metallic Tubing
Fig. 10 — Typical Component Location
CONTROL
WIRING
APOLLO
CONTROL
WIRING TO
THERMOSTAT
LEGEND
AHA — Adjustable Heat Anticipator
CC — Cooling Compensator
TC — Thermostat-Cooling
TH — Thermostat-Heating
Field Wiring
Factory Wiring
NOTE: Connect W2 when 2-stage accessory electric heaters are used.
Fig. 11 — Low-Voltage Connections
COMPRESSOR
NO. 2
COMPRESSOR
NO. 1
Fig. 13 — Apollo Control Factory-Installed in
Typical Unit
12
FILTER
ACCESS
PANEL
OUTDOOR AIR
OPENING
PANEL
SCREWS
(SIDE)
MANUAL
OUTDOOR-AIR
ADJUSTMENT
SCREWS
DAMPER
BLADE
Fig. 14 — Damper Panel with Manual
Outdoor-Air Damper Installed
13
Fig. 15 — Outdoor-Air Hood Details
SCREW
HOLES
(TOP)
HOOD
HOOD
SCREEN
LOCATION
(SCREEN
NOT
SHOWN)
Fig. 16 — Damper with Hood Attached
Fig. 19 — Outdoor-Air Hood Details
Fig. 17 — Position Setting
FILTER
ACCESS
PANEL
BLOCK-OFF
PANEL
EVAPORATOR
COIL
ACCESS
PANEL
Fig. 18 — Access Panel Location
Fig. 20 — Vertical Discharge Block-Off Plate
(Sizes 012, 014 only)
14
Fig. 21 — Durablade Economizer Installed in Unit
EXAMPLE:
Given —
Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1 in. wg
Outdoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm
Determine —Setting = 6 in.
Fig. 24 — Durablade Economizer Damper
Minimum Position Setting
ECONOMIZER
CONTROL
BOARD
BAROMETRIC
RELIEF
DAMPER
ECONOMIZER
MOTOR
ECONOMIZER
MOUNTING
SCREWS
Fig. 22 — Horizontal Durablade Economizer
Installation (90-Degree Rotation)
9
8
7
6
5
4
3
2
1
0
Fig. 25 — Minimum Position Damper Setting
BLOCK-OFF PLATE
Fig. 23 — Horizontal Discharge Block-Off Plate
15
Fig. 27 — Wiring Connections for
Outdoor-Air Thermostat
Fig. 28 — Durablade Economizer Barometric Relief
Damper Characteristics
ENTHALPY
CONTROL
ECONOMI$ER
PLUG
ACTUATOR
CONTROLLER GEAR-DRIVEN
DAMPER
HOOD
OPEN
POSITION MINIMUM
10
30
D
60
M
U
70
H
%
90
WN IN HIGH ENTHALPY
REV.
97-3672
NOTE: Outdoor-Air Thermostat or Enthalpy Control can be attached to either side inside hood.
Fig. 26 — Outdoor-Air Thermostat/
Enthalpy Control Installation
OUTDOOR AIR
TEMPERATURE
SENSOR
BAROMETRIC
RELIEF DAMPERS
Fig. 29 — 7 1 /
2
to 12 1 /
2
Ton EconoMi$er Assembly
16
FILTER
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
Fig. 30 — Typical Access Panel Locations
OUTDOOR AIR
OPENING
PANEL
1/8 x 7/8 IN.
SEAL STRIP
OUTDOOR AIR
HOOD TOP
1/8 x 7/8 IN.
SEAL STRIP
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
ASSEMBLED
EXHAUST HOOD
OUTDOOR AIR
HOOD SIDES
Fig. 32 — Outdoor Air Hood Assembly
OUTDOOR AIR
OPENING PANEL
1/8 x 7/8 IN.
SEAL STRIP
3/4 x 3/4 IN.
SEAL STRIP
EXHAUST AIR
HOOD TOP
SCREEN
RETAINER
EXHAUST AIR
HOOD SIDES
EXHAUST AIR SCREEN
EXHAUST AIR
BOTTOM BRACKET
Fig. 31 — Exhaust Air Hood Assembly
Fig. 33 — Completed Hood Assembly
INSTALL
RETURN AIR
BLOCK-OFF
PLATE
BLOWER
FILTER
REMOVE FACTORY INSTALLED
BLOCK-OFF PLATE
(7-1/2 AND 8-1/2 TON UNITS ONLY)
Fig. 34 — Return Air Block-Off Plate Installation
7 1 /
2
to 12 1 /
2
Ton Units Only)
17
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 37 — Supply Air Sensor Placement
UNIT FILTER
RACK
ECONOMI$ER CLIP
HVAC UNIT
ECONOMI$ER
UNIT BASE
ECONOMI$ER REAR
FLANGE
Fig. 35 — Rear EconoMi$er Flange Installation
WIRING HARNESS
OUTDOOR AIR
BLOCK-OFF PLATE
Fig. 36 — EconoMi$er Installed in
7 1 /
2
to 12 1 /
2
Ton Unit
Fig. 38 — EconoMi$er Control Adjustment
Potentiometers (Factory Settings)
18
Table 3 — Changeover Set Points
SETTINGS
Dry Bulb (°F)
Single Enthalpy* (Btu/lb)
Differential Temperature*
(°F, Not Adjustable)
Differential Enthalpy*
(Btu/lb, Not Adjustable)
*Field-installed accessory.
A
73
27
2
1
B
69
25
2
1
C
66
24
2
1
D
63
22
2
1
Table 4 — Default Potentiometer Settings
POTENTIOMETER
CO
2
SP (PPM)
MECH CLG LOCKOUT
ECON SP
MIN POS (%)
DEFAULT SETTING
1,000
47°
D
20
CONTROL
CURVE
A
B
C
D
CONTROL POINT
F (C) APPROX
AT 50% RH
73 [23]
70 [21]
57 [19]
53 [17]
Fig. 39 — Enthalpy Settings for
EconoMi$er Economizer
Step 7 — Adjust Evaporator-Fan Speed —
19
0.5
0.4
0.3
0.2
0.1
0
0 200 400 600 800 1000 1200 1400 1600
FLOW (CUBIC FEET/MINUTE)
Fig. 40 — 7 1 /
2
to 12 1 /
2
Ton Barometric Relief
Capacity
Performance data (cont)
Table 6 - FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
50TJ S008 (7 1
2
/ TONS) — STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
2250
2300
2400
2500
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Rpm
465
471
482
494
501
507
520
533
546
559
572
585
598
610
623
636
649
655
0.2
Bhp
0.43
0.45
0.50
0.54
0.57
0.59
0.65
0.71
0.77
0.83
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.37
Watts
638
684
731
779
835
883
940
998
473
487
524
554
577
592
1056
1123
1190
1224
Rpm
554
559
569
581
587
592
604
615
626
637
648
660
671
682
694
707
720
727
0.4
Bhp
0.64
0.66
0.71
0.76
0.79
0.82
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.60
1.71
1.77
External Static Pressure (in. wg)
0.6
Watts Rpm Bhp Watts
0.8
Rpm Bhp
827
875
932
989
1056
1114
1182
1258
630
646
684
723
747
771
1335
1422
1517
1569
630
635
645
654
659
663
672
683
693
704
715
727
739
750
761
772
783
789
0.86
0.89
0.95
1.01
1.05
1.08
1.14
1.20
1.27
1.35
1.43
1.52
1.62
1.72
1.82
1.93
2.03
2.09
803
827
875
924
956
981
1031
1081
1140
1207
1275
1353
1439
1526
1613
1709
1796
1849
695
699
708
717
722
727
737
747
756
765
775
785
795
806
817
828
840
846
Watts Rpm
1.0
Bhp Watts
1.09
1.12
1.18
1.25
1.29
1.32
989
1014
1064
1123
1156
1182
757
760
768
776
780
784
1.34
1.37
1.44
1.51
1.55
1.58
1199
1224
1284
1344
1378
1404
1.40
1.49
1.57
1.66
1250
1327
1396
1473
1.74
1543 832 2.05
1814
1.83
1627 841 2.15 1901
1.91
2.01
1691
1779
851
860
2.26
2.36
1997
2084
2.11
2.23
2.35
2.42
1866
1971
2076
2136
793
802
813
823
870
880
890
896
1.66
1.75
1.84
1.94
2.47
2.57
2.69
2.75
1473
1552
1630
1718
2180
2266
2369
2420
50TJ S008 (7 1 / TONS — STANDARD MOTOR (BELT DRIVE)* (cont)
Airflow
(Cfm)
2250
2300
2400
2500
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
Rpm
810
816
824
832
836
839
846
855
863
872
882
892
902
912
921
930
940
945
1.2
Bhp
1.62
1.65
2.57
2.69
2.82
2.95
3.07
3.14
1.72
1.79
1.83
1.87
1.95
2.04
2.13
2.22
2.33
2.45
LEGEND
Watts — Input Watts to Motor
Watts
1962
2058
2162
2266
2369
2479
2587
2686
2743
1439
1465
1526
1587
1621
1656
1726
1805
1884
Rpm
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
850
859
872
882
887
891
898
906
913
921
930
939
948
958
968
978
—
—
1.4
Bhp
1.91
1.94
2.88
3.01
3.15
3.29
—
—
*Motor drive range: 590 to 840 rpm.
All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .
2.01
2.09
2.13
2.17
2.26
2.35
2.44
2.54
2.65
2.76
External Static Pressure (in. wg)
1.6
Watts Rpm Bhp Watts
1.8
Rpm Bhp
1691
1718
1779
1849
1884
1919
1997
2076
2154
2240
2335
2428
2529
2637
2751
2862
—
—
873 2.20
888 2.24
909 2.32
925 2.40
931 2.45
936 2.49
946 2.58
954 2.67
961 2.77
969 2.88
976 2.99
984 3.10
993 3.21
1002 3.34
—
—
—
—
—
—
—
—
1945
1980
2050
2119
2162
2197
2275
2352
2436
2529
2620
2710
2799
2902
—
—
—
—
883 2.50
903 2.55
931 2.64
955 2.72
964 2.77
973 2.82
987 2.91
997 3.01
1006 3.12
1014 3.22
1021 3.34
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Watts
2206
2249
2326
2394
2436
2479
2554
2637
2727
2807
2902
—
—
—
—
—
—
—
Rpm
—
—
—
—
—
—
—
—
—
—
2.0
Bhp
895 2.78
911 2.85
935 2.96
972 3.06
986 3.11
999 3.16
1019 3.26
1034 3.36
—
—
—
—
—
—
—
—
—
—
Watts
—
—
—
—
—
—
—
—
—
—
2445
2504
2595
2678
2718
2759
2839
2917
2. Maximum usable watts input is 2120 and maximum continuous bhp is 2.
90. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
6. Motor Efficiency: 85%.
20
Performance data (cont)
Table 7 - FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
50TJ S009 (8 1/2 TONS) STANDARD MOTOR (BELT DRIVE)*
External Static Pressure (in. wg)
Airflow
(Cfm)
0.2
0.4
0.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
0.8
Rpm Bhp
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
649
655
661
674
687
699
712
719
501
507
520
533
546
559
572
585
598
610
623
636
1.33
1.37
1.41
1.49
1.57
1.60
1.75
1.80
0.57
0.59
0.65
0.71
0.77
0.83
0.90
0.96
1.03
1.10
1.17
1.25
1190
1224
1258
1327
1396
1473
1552
1595
577
592
638
684
731
779
835
883
940
998
1056
1123
694
707
720
727
733
746
759
772
785
792
587
592
604
615
626
637
648
660
671
682
1.50
1.60
1.71
1.77
1.82
1.93
2.05
2.17
2.30
2.37
0.79
0.82
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
659
663
672
683
693
704
715
727
739
750
761
772
783
789
795
806
817
828
840
846
1335
1422
1517
1569
1613
1709
1814
1919
2032
2093
747
771
827
875
932
989
1056
1114
1182
1258
1.05
1.08
1.14
1.20
1.27
1.35
1.43
1.52
1.62
1.72
1.82
1.93
2.03
2.09
2.15
2.26
2.38
2.50
2.64
2.71
956
981
1031
1081
1140
1207
1275
1353
1439
1526
1613
1709
1796
1849
1901
1997
2102
2206
2326
2386
722
727
737
747
756
765
775
785
795
806
817
828
840
846
852
863
874
885
897
903
1.29
1.32
1.40
1.49
1.57
1.66
1.74
1.83
1.91
2.01
2.11
2.23
2.35
2.42
2.48
2.61
2.75
2.88
3.03
3.10
Watts
1156
1182
1250
1327
1396
1473
1543
1321
1691
1779
1866
1971
2076
2136
2188
2300
2420
2529
2653
2710
1.0
Rpm Bhp
890
896
901
912
923
935
947
—
780
784
793
802
813
823
832
841
851
860
870
880
2.69
2.75
2.80
2.93
3.08
3.23
3.39
—
1.55
1.58
1.66
1.75
1.84
1.94
2.05
2.15
2.26
2.36
2.47
2.57
Watts
2369
2420
2462
2571
2694
2815
2940
—
1378
1404
1473
1552
1630
1718
1814
1901
1997
2084
2180
2266
50TJ S009 (8 1/2 TONS) STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
(Cfm)
1.2
1.4
1.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1.8
Rpm Bhp
2550
2660
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
836
839
846
855
863
872
882
892
902
912
921
930
940
945
949
959
—
—
—
—
1.83
1.87
1.95
2.04
2.13
2.22
2.33
2.45
2.57
2.69
2.82
2.95
3.07
3.14
3.20
3.33
—
—
—
—
LEGEND
Watts — Input Watts to Motor
1621
1656
1726
1805
1884
1962
2058
2162
2266
2369
2479
2587
2686
2743
2781
2894
—
—
—
—
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
930
939
948
958
968
978
887
891
898
906
913
921
—
—
—
—
—
—
—
—
2.13
2.17
2.26
2.35
2.44
2.54
2.65
2.76
2.88
3.01
3.15
3.29
—
—
—
—
—
—
—
—
1884
1919
1997
2076
2154
2240
2335
2428
2529
2637
2751
2862
—
—
—
—
—
—
—
—
*Motor drive range: 685 to 935 rpm. All other rpms require fieldsupplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .
—
—
—
—
—
—
—
—
931 2.45
936 2.49
946 2.58
954 2.67
961 2.77
969 2.88
976 2.99
984 3.10
993 3.21
1002 3.34
—
—
—
—
—
—
—
—
—
—
—
—
2162
2197
2275
2352
2436
2529
2620
2710
2799
2902
—
—
—
—
—
—
—
—
—
—
964
973
987
1006
1014
—
—
—
—
—
—
—
—
—
—
—
—
—
2.77
2.82
2.91
997 3.01
3.12
3.22
1021 3.34
—
—
—
—
—
—
—
—
—
—
—
—
—
Watts
2436
2479
2554
2637
2727
2807
2902
—
—
—
—
—
—
—
—
—
—
—
—
—
Rpm
986 3.11
999 3.16
1019 3.26
1034 3.36
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2.0
Bhp
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Watts
2718
2759
2839
2917
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2. Maximum usable watts input is 2120 and maximum continuous bhp is 2.
90. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
6. Motor Efficiency: 85%.
21
Performance data (cont)
Table 8 - FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
50TJ S012 (10 TONS) STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm
0.2
0.4
External Static Pressure (in. wg)
0.6
0.8
1.0
1.2
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
532 0.64
544 0.70
557 0.75
570 0.81
583 0.88
596 0.94
609 1.01
630 605 0.81
677 616 0.86
716 628 0.93
763 639 0.99
763 670 0.97
803 680 1.03
859 690 1.10
891
940
998
725
735
746
1.12
1.20
1.28
1014
1081
1148
778
787
796
1.28
1.36
1.44
1148
1216
1284
907 700 1.18
1064 757 1.36
1216 805 1.52
1353
818 651 1.06
965 711 1.25
1123 767 1.44
1284 815 1.61
1430
867 663 1.14
1031 721 1.33
1190 777 1.52
1353 826 1.71
1517
924 674 1.22
1097 732 1.42
1267 787 1.61
1430 836 1.80
1595
622 1.09
989 686 1.30
1165 744 1.50
1335 797 1.70
1508 847 1.91
1691
635 1.16
1047 698 1.39
1241 755 1.59
1413 808 1.80
1595 857 2.01
1779
649 1.25
1123 713 1.48
1318 767 1.68
1491 818 1.90
1683 867 2.11
1866
662 1.33
1190 722 1.57
1396 778 1.78
1578 829 2.01
1779 878 2.22
1962
675 1.42
1267 734 1.67
1482 790 1.89
1674 839 2.12
1875 888 2.33
2058
689 1.52
1353 746 1.77
1569 801 1.99
1761 851 2.23
1971 898 2.45
2212
825 1.43
1275
835 1.52
1353
844 1.61
1430
854 1.70
1508
863 1.79
1587
871 1.88
1665
880 1.98
1753
890 2.09
1849
901 2.20
1945
912 2.32
2050
922 2.44
2203
933 2.56
2309
943 2.69
2424
702 1.61
1430 759 1.88
1665 813 2.11
1866 862 2.34
2067 908 2.58
2326
715 1.72
1526 772 1.99
1761 825 2.22
1962 873 2.46
2221 919 2.71
2442
729 1.83
1621 785 2.10
1858 837 2.35
2076 885 2.59
2335 929 2.85
2569
953 2.81
2533
963 2.94
2651
973 3.08
2782
742 1.94
1718 797 2.22
1962 848 2.48
2238 896 2.72
2451 940 2.98
2688
756 2.06
1823 810 2.34
2067 860 2.61
2353 908 2.86
2578 951 3.12
2727
984
994
3.22
3.38
2914
3068
770 2.18
1927 823 2.46
2221 872 2.75
2505 919 3.00
2707 963 3.27
2847 1003 3.43
3202
783 2.31
2041 836 2.60
2344 884 2.89
2605 931 3.14
2838 974 3.41
2956 1013 3.59
3349
797 2.44
2203 849 2.73
2460 897 3.04
2661 943 3.30
2870 984 3.44
3211 1023 3.75
3501
50TJ S012 (10 TONS) STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
(Cfm)
1.4
1.6
1.8
2.0
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
4200
4300
4400
4500
4600
4700
4800
4900
5000
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
874 1.60
1422
880 1.68
1491
888 1.77
1569
897 1.86
1648
907 1.97
1744
916 2.07
1831
926 2.18
1927
926 1.82
1613
933 1.87
1656
934 1.94
1718
940 2.03
1853
974 2.11
1920 1012 2.41
2134
983 2.16
1963 1017 2.44
2177
988 2.18
1980 1025 2.47
2230
989 2.24
2031 1032 2.53
2282
947 2.14
1946
956 2.25
2039
991
997
2.32
2.43
2099
2195
1038
1043
2.57
2.64
2318
2380
966 2.41
2134 1004 2.54
2291 1045 2.74
2478
934 2.28
2015
943 2.41
2160
976 2.48
2238 1013 2.66
2397 1051 2.85
2569
985 2.60
2334 1023 2.79
2514 1059 2.98
2688
952 2.51
2265 994 2.72
2451 1032 2.92
2633 1068 3.12
2819
962 2.63
2371 1003 2.84
2560 1042 3.06
2763 1078 3.26
2952
973 2.77
2496 1011 2.97
2679 1051 3.20
2895 1087 3.41
3097
983 2.91
2624 1021 3.11
2810 1060 3.34
3029 1090 3.51
3276
994 3.05
2754 1031 3.25
2943 1068 3.48
3166 1097 3.70
3453
1004 3.19
2885 1042 3.41
3097 1080 3.63
3388 1105 3.91
3642
1015 3.33
2020 1051 3.45
3218 1090 3.75
3493 1112 4.12
3843
1025 3.48
3166 1060 3.61
3369 1100 3.92
3655 1119 4.35
4057
1037 3.58
3335 1070 3.84
3325 1111 4.10
3822 1126 4.59
4284
1048 3.75
3494 1080 3.95
3686 1121 4.28
3995 1133 4.85
4523
1060 3.92
3659 1089 4.13
3854 1132 4.48
4174 1140 5.12
4775
1072 4.11
3830 1099 4.32
4027 1144 4.67
4359 — — —
LEGEND
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
*Standard motor drive range: 685 to 935 rpm.
All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Motor and Drive Package range.
2. Maximum usable watts input is 2 120 with standard motor,
Max imum continuous bhp is 2.90 with standard motor.
3. Values include losses for filters, unit casings, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative for details.
5. Interpolation is permissible. Do not extrapolate.
6. Motor Efficiency: 85%
22
Performance data (cont)
Table 9 - FAN PERFORMANCE — HORIZONTAL DISCHARGE UNITS
50TJ S014 (12 1 /
2
TONS) STANDARD MOTOR (BELT DRIVE)*
Airflow
(Cfm)
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
3700
3800
3900
4000
4100
4200
4300
4400
4500
Rpm
869
885
901
917
933
949
965
981
997
1014
742
758
773
789
805
821
837
853
607
621
636
650
665
680
696
711
727
0.2
Bhp
2.92
3.09
3.26
3.44
3.62
3.81
4.01
4.21
4.42
4.64
1.82
1.94
2.06
2.19
2.32
2.47
2.61
2.76
0.97
1.05
1.13
1.21
1.30
1.39
1.49
1.60
1.70
Watts
2602
2755
2910
3074
3239
3414
3600
3785
3981
4186
1641
1742
1845
1957
2070
2202
2325
2459
947
1010
1073
1137
1210
1283
1365
1456
1540
Rpm
882
897
911
926
941
956
972
987
1002
1018
774
786
799
812
826
840
854
868
670
681
693
705
717
728
739
750
762
0.4
Bhp
3.01
3.17
3.33
3.50
3.68
3.87
4.06
4.26
4.46
4.68
1.96
2.07
2.18
2.30
2.43
2.57
2.71
2.85
1.18
1.25
1.32
1.40
1.48
1.57
1.66
1.75
1.85
Watts
2683
2828
2973
3129
3294
3470
3646
3832
4018
4223
1759
1854
1948
2053
2166
2290
2414
2539
1113
1170
1226
1291
1357
1431
1506
1582
1666
External Static Pressure (in. wg)
0.6
Rpm
828
840
852
863
875
956
968
981
995
1008
1022
1036
887
898
909
920
932
943
732
742
751
761
772
783
794
805
817
Bhp
2.23
2.34
2.46
2.57
2.70
2.83
2.96
3.09
3.24
3.38
3.54
3.70
3.87
4.05
4.23
4.42
4.62
4.83
1.37
1.45
1.53
1.61
1.71
1.81
1.91
2.02
2.12
Watts
1992
2088
2193
2290
2405
2521
2638
2755
2891
3019
3166
3313
3470
3637
3804
3981
4167
4363
1267
1332
1398
1464
1548
1632
1717
1811
1897
Rpm
877
888
899
910
921
932
943
955
967
978
990
1002
1013
1025
1037
1042
1058
1070
782
795
808
819
830
839
848
857
867
0.8
Bhp
2.46
2.59
2.72
2.86
2.99
3.13
3.28
3.42
3.57
3.72
3.87
4.03
4.20
4.37
4.55
4.73
4.91
5.11
1.56
1.66
1.76
1.86
1.96
2.05
2.14
2.24
2.35
Watts
2193
2307
2423
2548
2665
2792
2928
3056
3193
3331
3470
3618
3775
3934
4102
4270
4437
4624
1423
1506
1590
1674
1759
1836
1914
2000
2096
Rpm
929
938
947
957
966
976
987
998
1009
1029
1031
1042
1053
1065
1076
1088
—
—
833
842
851
861
871
883
896
908
919
1.0
Bhp
2.75
2.87
2.98
3.11
3.24
4.56
4.74
4.92
5.10
—
—
3.38
3.53
3.69
3.86
4.03
4.20
4.38
1.73
1.82
1.92
2.02
2.13
2.25
2.38
2.51
2.63
Watts
2450
2557
2656
2773
2891
3019
3157
3304
3461
3618
3775
3943
4111
4279
4447
4614
—
—
1565
1641
1725
1811
1905
2009
2123
2237
2343
50TJ S014 (12 1 /
2
TONS) STANDARD MOTOR (BELT DRIVE)* (cont)
External Static Pressure (in. wg)
Airflow
(Cfm)
1.2
1.4
1.6
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm
879
889
898
908
917
925
935
945
955
967
980
992
1003
1014
1024
1033
1042
1051
1061
1071
1081
1092
1103
1114
—
—
—
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
3700
3800
3900
4000
4100
4200
4300
4400
4500
1.95
2.03
2.12
2.21
2.32
2.44
2.56
2.68
2.82
2.96
3.11
3.26
4.30
4.46
4.64
4.84
5.04
5.24
—
3.41
3.56
3.71
3.84
3.98
4.14
—
—
1751
1819
1897
1974
2070
2175
2281
2387
2512
2638
2773
2910
3047
3184
3322
3442
3572
3720
3818
4018
4186
4372
4558
4745
—
—
—
—
—
—
—
2.89
3.02
3.16
3.30
3.45
3.61
3.79
3.96
4.14
4.31
4.49
4.66
4.81
4.98
5.15
—
2.17
2.26
2.36
2.46
2.55
2.65
2.77
1005
1015
1025
1036
1049
1061
1073
1084
1095
1105
1114
1123
1132
—
—
—
—
—
927
934
942
950
960
969
979
988
996
973
980
987
994
1001
1009
1018
1028
1037
1046
1056
1064
1073
1083
1093
1103
1115
1128
1140
1152
—
—
—
—
—
—
—
2819
2946
3083
3230
3396
3553
3720
3878
4046
4204
4344
4503
4661
—
—
—
—
—
1940
2018
2105
2193
2272
2370
2468
2575
2692
—
—
—
—
2.38
2.48
2.59
2.70
2.81
2.92
3.03
3.14
3.25
—
—
—
3.38
3.52
3.67
3.83
4.00
4.17
4.34
4.53
4.74
4.94
5.14
2123
2210
2307
2405
2503
2602
2701
2801
2901
3019
3147
3285
3433
3590
3748
3906
4157
4279
4465
4652
—
—
—
—
—
—
—
1084
1093
1103
1112
1121
1129
1138
1148
1158
1168
—
—
—
—
—
—
—
—
1013
1022
1030
1037
1045
1051
1058
1066
1074
LEGEND
Bhp — Brake Horsepower Input to Fan
FIOP — Factory-Installed Option
Watts — Input Watts to Motor
*Standard motor drive range: 860 to 1080 rpm. Alternate motor drive range:
900 to 1260 rpm. All other rpms require field-supplied drive.
NOTES:
1. Boldface Out of Drive Package or Motor range .
4. Use of a field-supplied motor may affect wire sizing. Contact your Carrier representative for details.
1.8
Bhp
—
—
—
—
3.66
3.79
3.92
4.07
4.23
4.40
4.58
4.76
4.95
5.15
—
—
—
—
2.57
2.69
2.81
2.92
3.04
3.17
3.29
3.41
3.54
Watts
3276
3396
3516
3655
3804
3962
4130
4326
4475
4661
—
—
—
—
—
—
—
—
2290
2396
2503
2602
2710
2828
2937
3047
3166
2.0
Bhp
—
—
—
—
3.67
3.81
3.95
4.09
4.22
4.36
4.50
4.66
4.82
5.01
5.20
—
—
—
—
—
2.73
2.87
3.01
3.14
3.21
3.40
3.53
Rpm
1106
1113
1121
1129
1137
1147
1157
1166
1175
1184
1193
—
—
—
—
—
1046
1058
1068
1077
1085
1092
1100
—
—
—
—
Watts
3285
3414
3544
3674
3795
3925
4055
4202
4354
4531
4707
—
—
—
—
—
2432
2557
2683
2801
2919
3037
3157
—
—
—
—
2. Maximum usable watts input is 3313 with standard motor.
Maximum continuous bhp is 3.70 with standard motor .
Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence.
Using your fan motors up to the wattage ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
3. Values include losses for filters, unit casing, and wet coils.
23
5. Interpolation is permissible. Do not extrapolate.
6. Motor Efficiency: 85%
UNIT
50LJS007
0
1205
1/2
1180
50TJS008
50TJS009
50TJS012
880
880
900
855
855
875
50TJS014 1017 992
* Approximate fan RPM shown
Table 10 - FAN RPM AT MOTOR PULLEY SETTINGS*— 50 Hz
MOTOR PULLEY TURNS OPEN
1 1 1/2 2 2 1/2 3 3 1/2 4
1150 1125 1095 1070 1040 1015 985
UNIT
50LJS007
50TJS008,009
50TJS012
50TJS014
SOUND
RATING
(Bels)
8.2
8.6
8.8
8.8
Table 11 - OUTDOORS SOUND POWER
OCTAVE BANDS
63 125 250 500 1000 2000
78.5 84 77.5 73 70.5 72
83.2 87.4 83.5 82.8 83 77.7
97.6 90.4 85.7 84.8 83.9 77.5
83.7 87.2 83.4 82.8 83 77.7
4000
65
71.8
71.3
71.8
4 1/2
960
8000
58.5
67
65.8
67
650
650
715
832
5
930
620
620
690
814
DURABLADE ECONOMIZER BAROMETRIC RELIEF
DAMPER CHARACTERISTICS
24
MOTOR MOUNTING
PLATE NUTS
Fig. 41 — Typical Belt-Drive Motor
Mounting for Sizes 008,009
START-UP
Unit Preparation —
Return-Air Filters —
Outdoor-Air Inlet Screens —
Compressor Mounting —
Internal Wiring —
Refrigerant Service Ports —
Compressor Rotation —
Fig. 42 — Typical Belt-Drive Motor
Mounting for Sizes 012,014
Fig. 43 — Evaporator-Fan Pulley Adjustment
25
Cooling — To start unit, turn on main power supply. Set system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room temperature. Compressor starts on closure of contactor.
Heating (If Accessory Electric Heater is
Installed) — To start unit, turn on main power supply.
Ventilation (Continuous Fan) —
Operating Sequence
26
Cleaning —
SERVICE Lubrication
Evaporator Fan Belt Inspection —
Condenser-Fan Adjustment (Fig. 47)
Manual Outdoor-Air Damper —
Economizer Adjustment —
Condenser Coil Grille —
Fig. 44 — Cleaning Condenser Coil
27
Fig. 45 — Propping Up Top Panel
Fig. 46 — Separating Coil Sections
50TJ
208/230 V
460 and 575 V
FAN HEIGHT
‘‘A’’, in.
2.75
3.50
Fig. 47 — Condenser Fan Adjustment
Refrigerant Charge
°
°
°
28
Fig. 48 — Cooling Charging Chart; 50TJ008
CIRCUIT NO. 1 CIRCUIT NO. 2
Fig. 49 — Cooling Charging Chart; 50TJ009
CIRCUIT NO. 1
CIRCUIT NO. 2
Fig. 50 — Cooling Charging Chart; 50TJ012
29
Fig. 51 — Cooling Charging Chart; 50TJ014
30
CIRCUIT NO. 1 CIRCUIT NO. 2
Fig. 49 — Cooling Charging Chart; 50TJ009
CIRCUIT NO. 1
CIRCUIT NO. 2
Fig. 50 — Cooling Charging Chart; 50TJ012
31
Fig. 51 — Cooling Charging Chart; 50TJ014
32
PROBLEM
Damper does not open.
EconoMi$er operation limited to minimum position.
Damper position less than minimum position set point.
Damper does not return to minimum position.
Damper does not close on power loss.
CAUSE
Indoor (evaporator) fan is off.
No power to
G terminal.
Controller fault.
Thermostat fault.
Actuator fault.
Supply air low limit strategy controlling.
Table 13 — EconoMi$er Service Analysis
No power to EconoMi$er controller.
Minimum position set incorrectly.
EconoMi$er changeover set point set too high or too low.
Supply air temperature sensor faulty.
OAT sensor faulty.
REMEDY
Check to ensure that 24 vac is present at Terminal C1 (common power) on the IFC
(indoor [evaporator] fan contactor) or that 24 vac is present at the IFO (indoor [evaporator] fan on) terminal. Check whether 24 vac is present at PL (plug) 6-1 (red wire) and/or
PL6-3 (black wire). If 24 vac is not present, check wiring (see unit label diagram).
Check proper thermostat connection to G on the connection board.
Check to ensure that 24 vac is present across terminals 24 VAC and 24 v COM on the
EconoMi$er control. If 24 vac is not present, check wiring (see unit label diagram).
If 24 vac is present, status light should be on constantly.
If IFM is on, check to ensure 24 vac is present on G terminal of the EconoMi$er controller. If 24 vac is not present, check wiring (see unit label diagram).
If STATUS light is flashing one flash, the EconoMi$er controller is experiencing a fault condition. Cycle power to the controller. If condition continues, replace the EconoMi$er controller.
If STATUS light is flashing two flashes, the EconoMi$er controller believes the thermostat is wired incorrectly. Check wiring between the thermostat and the connection board in the electrical panel. The fault condition is caused by Y2 being energized before Y1.
Check the wiring between the EconoMi$er controller and the actuator. Hold CONFIG button between three and ten seconds to verify the actuator’s operation. (This process takes three minutes to complete.)
Verify that the MIN POS (%) is set greater than zero. Adjust MIN POS (%) to 100% to verify operation, and then set to correct setting.
Set at correct value. See Table 2.
If STATUS light is flashing four flashes, the supply air temperature sensor is faulty.
Check wiring or replace sensor.
If STATUS light is flashing five flashes, the OAT (outdoor-air temperature) sensor is faulty.
Check wiring or replace sensor.
The supply air temperature is less than 45 F, causing the minimum position to decrease.
Refer to the Start-Up instructions. Verify correct setting of MIN POS (%). If correct,
EconoMi$er is operating correctly.
CO
2
ventilation strategy controlling.
Damper travel is restricted.
If a CO
2
sensor is being used, and the damper position is greater than minimum position, the ventilation control strategy is controlling. Refer to
the Start-Up instructions. EconoMi$er is operating correctly.
Check to ensure the damper is not blocked.
33
Typical wiring schematic — 50LJS007
208-230V
19
Typical wiring schematic — 50LJS007
380,400,460V
2
0
Typical wiring schematic — 50TJS008-014
208,230,460V
21
Typical wiring schematic — 50TJS008-014
380V
22
Typical wiring schematic —
50
LJS007 400V
19
Typical wiring schematic — 50TJ
S 008 400V
20
Typical wiring schematic — 50TJ
S008-014 400V
21
START-UP CHECKLIST
(Remove and Store in Job File)
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED AS SHOWN IN THE INSTALLATION
INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL WITHIN TOLERANCES LISTED IN THE
INSTALLATION INSTRUCTIONS
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
CHECK PULLEY ALIGNMENT AND BELT TENSION; REFER TO INSTALLATION INSTRUCTIONS
III. START-UP
ELECTRICAL
TEMPERATURES
REFRIGERANT
° °
° °
VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGES 35-37
(COOLING MODE ONLY)
VERIFY 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
201
1 50TJS-03 IOM
Download
Advertisement
Key features
Single-package design
Installation, start-up and service instructions
Safety considerations
Detailed wiring and piping diagrams
Troubleshooting guide
Start-up checklist
Frequently asked questions
This document provides instructions on how to install, start-up and service single-package rooftop units.
Installation and servicing air-conditioning equipment can be hazardous. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
The evaporator-fan speed can be adjusted using the belt-drive motor mounting.
The condenser coil can be cleaned by separating the coil sections and using a brush or vacuum cleaner.
The condenser fan can be adjusted by changing the fan height.