- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- User manual
advertisement
SOHO E-MEDICAL INDUSTRY EMERGENCY
6
VFI
TYPE
ONLINE Tower
1:1 700-3000 VA
USB plug
GS Nemko certified
Supercaps
UPS
Plug & Play installation
HIGHLIGHTS
• Power factor 0,9
• Operating flexibility
• Emergency function
• Battery optimisation
• Runtime expandability
• Low noise level
Sentinel Pro has a unique and modern design and improved performance developed by the Riello UPS research and development team. Sentinel Pro uses on-line double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads such as servers, and IT and voice/data applications.
For business continuity applications requiring long battery runtimes, battery autonomy can be extended up to several hours using ER models fitted with more powerful battery chargers.
The front display panel has been entirely redesigned, adding an LCD display that shows the input and output voltages, battery readings and UPS operating status information. The inverter and the microprocessor control stage has been completely redesigned to provide increased efficiency and greater configuration options.
Maximum expandability: the Sentinel Pro is supplied as standard with a USB port and an expansion slot for protocol conversion or relay contacts boards.
With energy savings in mind, Sentinel
Pro is also fitted with a shut-off button to reduce energy consumption to zero during prolonged periods of inactivity (ECO LINE).
Sentinel Pro is available in 700 VA, 1000
VA, 1500 VA, 2200 VA and 3000 VA models.
Operating flexibility
Different operating modes that can be programmed according to user requirements and the load to be powered have been introduced in order to reduce energy consumption.
• On line: maximum load protection and output voltage waveform quality
• Economy Mode: the UPS uses line interactive technology, with the load powered by the mains, reducing consumption and thus improving efficiency (up to 98%).
• Smart Active Mode: the UPS automatically selects on-line or line interactive operation, depending on the quality of the mains supply, checking the number, frequency and type of disturbances present.
• Stand by Off (emergency): The UPS supplies the load only when the mains fails. The inverter begins working with a progressive start-up sequence to prevent inrush currents.
• Frequency converter operation (50 or 60
Hz).
Emergency function
This configuration ensures the operation of emergency systems that must be supplied in the event of a mains power failure, such as emergency lighting, fire detection/ extinguishing systems and alarms. When the mains power supply fails, the inverter begins powering the loads with a progressive startup (Soft Start) in order to prevent overload.
Sentinel Pro is compliant for installation in medium-voltage transformer rooms in accordance with applicable legislation, for the power supply with reserve charge of medium-voltage coils.
Battery optimisation
The Sentinel Pro range has a deep discharge protection device to optimise battery life.
Periodically the UPS carries out a battery efficiency test (which can also be manually activated); its wide input voltage tolerance range helps to reduce battery usage and maintain performance over time.
Runtime expandability
Optional battery extension packs can be connected to increase UPS runtime. In addition the Sentinel Pro range includes
ER versions with no internal batteries and more powerful battery chargers for longer runtimes.
Low noise level
Thanks to the use of high frequency components and load-based fan speed control, the noise produced by the UPS is less than 40 dBA.
Features
• Filtered, stabilised and reliable voltage: double conversion on-line technology
(VFI compliant with IEC 62040-3) with filters for the suppression of atmospheric disturbances.
• High overload capability (up to 150%)
• Programmable Auto-restart when mains is restored
• Battery start-up (cold start)
DETAILS
SEP 3000 - SEP 3000 ER
SEP 2200 - SEP 2200 ER
SEP 700
SEP 1500
SEP 1000
SEP 1000 ER
USB PORT
RS232
SERIAL
INTERFACE
REPO
CONNECTOR
COMMUNICATION SLOT
BATTERY EXPANSION
CONNECTOR
OUTPUT SOCKETS
INPUT SOCKET
• Power factor correction (UPS input power factor, close to 1)
• Wide input voltage tolerance range
(from 140 V to 276 V) without battery intervention.
• Runtime extendable up to several hours
• Fully configurable using UPS Tools configuration software
• Highly reliable batteries (automatic and manually-activated battery test)
• High level of UPS reliability (total microprocessor control)
• Low impact on the mains (sinusoidal take up).
Advanced communications
• Multi-platform communication for all operating systems and network environments: PowerShield 3 supervision and shutdown software for Windows operating systems 10, 8, 7, Hyper-V, 2016,
2012, and previous versions, Mac OS X,
Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems
• UPS Tools configuration and customisation software supplied as standard
• RS232 serial port and opto-isolated contacts
• USB port
• Slot for communications boards.
2-YEAR WARRANTY
OPTIONS
SOFTWARE
PowerShield 3
PowerNetGuard
ACCESSORIES
NETMAN 204
MULTICOM 302
MULTICOM 352
MULTICOM 372
MULTICOM 382
MULTICOM 401
MULTI I/O
Interface kit AS400
MULTIPANEL
Manual Bypass 16 A
Automatic Bypass 16 A
BATTERY BOX
MODELS BB SEP 36-A3 / BB SEP 36-M1 BB SEP 72-A3 / BB SEP 72-M1 BB SEP 36-B1 / BB SEP 72-B1
Dimensions
(mm)
BB
158
422
190
BB
446
BB
215
655
MODELS
POWER
INPUT
Nominal voltage
Voltage range without battery intervention
Voltage tolerance
Maximum permitted voltage
Nominal frequency
Frequency range
Power factor
Current distortion
BYPASS
Voltage tolerance
Frequency tolerance
Overload Times
OUTPUT
Voltage distortion with linear load / with non-linear load
Frequency
Static variation
Dynamic variation
Waveform
Current crest factor
Efficiency
ECO and Smart Active Modes
BATTERIES
Type
Recharge time
OTHER FEATURES
Net weight (kg)
Gross weight (kg)
Dimensions (WxDxH) (mm)
Packaging dimensions
(WxDxH) (mm)
Protection against overvoltage
Protections
Communications
Input plugs
Output sockets
Standards
Operating temperature
Relative humidity
Colour
Noise level at 1 m (ECO Mode)
Standard equipment provided
SEP 700 SEP 1000 SEP 1000 ER SEP 1500 SEP 2200 SEP 2200 ER SEP 3000 SEP 3000 ER
700 VA/630 W 1000 VA/900 W 1500 VA/1350 W 2200 VA/1980 W 3000 VA/2700 W
10,9
12,5
140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
2-4 hours
13,3
14,9
7
8,6
158 x 422 x 235
245 x 500 x 340
220-230-240 Vac
230 Vac ± 20%
300 Vac
50/60 Hz
50 Hz ± 5% / 60 Hz ± 5%
> 0,99
≤7%
180 - 264 Vac
Frequency selected (from ±1,5Hz to ±5Hz configurable)
125% for 5 seconds, 150% for 1 second
< 2% / < 4%
Selectable: 50 Hz or 60 Hz or self-learning
± 1%
≤ 5% in 20 msec.
Sinusoidal
3 : 1
14,8
15,5
98%
VRLA AGM maintenance-free lead based; Supercaps
N.A.
2-4 hours N.A.
25,6
28,8
2-4 hours
14
17
28
31,2
190 x 446 x 333
325 x 585 x 470
300 joules
Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery
USB / DB9 with RS232 and contacts / Slot for communications interface
1 IEC 320 C14 1 IEC 320 C20
4 IEC 320 C13 8 IEC 320 C13 + 1 IEC 320 C19
Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 and Directives 2004/108/EL
0 °C / +40 °C
< 95% non-condensing
Black
< 40 dBA
Power cable, IEC-IEC cable, USB cable, safety manual, quick start guide