Omron CS/CJ Series CS1W-SCB21-V1, SCB41-V1 Serial Communications Board, CS/CJ Series CS1W-SCU21-V1, CJ1W-SCU21-V1, SCU41-V1 Serial Communications Unit Operation Manual
Below you will find brief information for Serial Communications Board CS/CJ Series CS1W-SCB21-V1, Serial Communications Board CS/CJ Series SCB41-V1, Serial Communications Unit CS/CJ Series CS1W-SCU21-V1. This manual describes the CS/CJ-series Serial Communications Boards and Units, which are designed to facilitate serial communication between the CPU unit and external devices using a variety of standard protocols. The Units and Boards provide a simple and reliable way to expand the capabilities of your PLC system by allowing you to connect to devices such as barcode readers, temperature controllers, and other industrial equipment. Using this manual, you will learn how to install and configure the Serial Communications Units and Boards to communicate with your external devices via RS-232C, RS-422A, or RS-485 interfaces.
Advertisement
Advertisement
Cat. No. W336-E1-07
SYSMAC
CS/CJ Series
CS1W-SCB21-V1/SCB41-V1
Serial Communications Boards
CS1W-SCU21-V1 and
CJ1W-SCU21-V1/SCU41-V1
Serial Communications Units
OPERATION MANUAL
SYSMAC CS/CJ Series
Serial Communications Boards and
Serial Communications Units
Operation Manual
Revised November 2005
Terms and Conditions of Sale
1.
Offer; Acceptance. These terms and conditions (these "Terms") are deemed part of all quotes, agreements, purchase orders, acknowledgments, price lists, catalogs, manuals, brochures and other documents, whether electronic or in writing, relating to the sale of products or services (collectively, the "Products") by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron objects to any terms or conditions proposed in Buyer’s purchase order or other documents which are inconsistent with, or in addition to, these Terms.
2.
Prices; Payment Terms. All prices stated are current, subject to change without notice by Omron. Omron reserves the right to increase or decrease prices on any unshipped portions of outstanding orders. Payments for Products are due net 30 days unless otherwise stated in the invoice.
3.
Discounts. Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (i) the invoice is paid according to Omron’s payment terms and (ii) Buyer has no past due amounts.
4.
Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms.
5.
Orders. Omron will accept no order less than $200 net billing.
6.
Governmental Approvals. Buyer shall be responsible for, and shall bear all costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7.
Taxes. All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Omron or required to be collected directly or indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Omron.
8.
Financial. If the financial position of Buyer at any time becomes unsatisfactory to Omron, Omron reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts.
9.
Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall constitute delivery to Buyer; c. All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Omron), at which point title and risk of loss shall pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid; d. Delivery and shipping dates are estimates only; and e. Omron will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty.
See http://oeweb.omron.com or contact your Omron representative for published information.
14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and their employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. Without limiting the foregoing, Buyer (at its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party.
16. Property; Confidentiality. Any intellectual property in the Products is the exclusive property of Omron Companies and Buyer shall not attempt to duplicate it in any way without the written permission of Omron. Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Omron. All information and materials supplied by Omron to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party.
17. Export Controls. Buyer shall comply with all applicable laws, regulations and licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of regulated technology or information.
18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right and no course of dealing between Buyer and Omron shall operate as a waiver of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder without Omron's written consent. (c) Law. These Terms are governed by the law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. (e) Severability. If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. (f) Setoff. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. (g) Definitions. As used herein, “including” means “including without limitation”; and “Omron Companies” (or similar words) mean Omron Corporation and any direct or indirect subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1.
Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-
ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
2.
Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
3.
Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
4.
Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product.
5.
Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Additionally, there may be property damage.
!WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Additionally, there may be property damage.
!Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PLC” means Programmable Controller. “PC” is used, however, in some Programming Device displays to mean Programmable Controller.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1,2,3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1999
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvii
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xviii
8
9
6
7
2
3
4
5
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xviii xviii xix xx
Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit Versions of CS/CJ-series Serial Communications Boards/Units . . . . . . . . . . . . . . . . .
xxii xxiv
Functions Added in the Unit Version 1.3 Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xxviii
Functions Added in the Unit Version 1.2 Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xxviii
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
1-1 Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
1-2 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 Protocol Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-5 System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-7 Comparison to Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8 Selecting the Serial Communications Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9 Basic Operating Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
16
26
38
3
7
44
45
SECTION 2
Initial Settings and I/O Memory Allocations . . . . . . . . . . . .
63
2-1 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
64
2-2 Data Exchange with the CPU Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 I/O Memory Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
73
75
SECTION 3
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
3-1 Installing a Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
92
3-2 Installing Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 RS-232C and RS-422A/485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
93
97
116
SECTION 4
Using Host Link Communications . . . . . . . . . . . . . . . . . . . . 125
4-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
126
126
4-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 Communications Timing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-5 Changes from Previous Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Host Link Function for Replacing Existing PLCs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
130
134
139
141
vii
viii
TABLE OF CONTENTS
SECTION 5
Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
5-1 Overview of the Protocol Macro Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
148
5-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Using Protocol Macros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Simple Backup Function (Backup of Protocol Macro Data). . . . . . . . . . . . . . . . . . . . . . . . .
5-6 Enhanced Protocol Macro Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
155
161
178
189
192
SECTION 6
Serial Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
6-1 Serial Gateway Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 DM Area Allocations (Using Serial Gateway Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
198
203
6-3 Auxiliary Area and CIO Area in Serial Gateway Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Using the Serial Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5 Protocol Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-6 Serial Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7 Conditions Requiring Routing Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8 Communications Frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
206
210
214
226
230
237
SECTION 7
No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
7-1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
250
7-2 Allocation DM Area for No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Basic Operating Procedure in No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
252
254
260
SECTION 8
Using 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263
8-1 Overview of 1:N NT Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
264
8-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
266
267
SECTION 9
Using Modbus-RTU Slave Mode (Unit Version 1.3 or Later)273
9-1 Modbus-RTU Slave System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
274
9-2 Setup Area Allocations (Modbus-RTU Slave Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Auxiliary Area and CIO Area Allocations (Modbus-RTU Slave Mode) . . . . . . . . . . . . . . .
9-4 Communications Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-5 Changes from Previous Products. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-6 Modbus-RTU Slave Function for Replacing Existing PLCs . . . . . . . . . . . . . . . . . . . . . . . . .
275
278
290
295
298
TABLE OF CONTENTS
SECTION 10
Loopback Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
10-1 Executing Loopback Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
304
10-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-3 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
305
306
SECTION 11
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . 307
11-1 Indicator Error Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
308
11-2 Status Area Error Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4 Error Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-5 Cleaning and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-6 Replacement Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
311
312
347
354
355
Appendices
A Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B CompoWay/F Master Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C C-mode (Host Link) Command Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Host Link FINS Command Master . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1) . . . . . . . . . . . . . . .
F E5
@K Digital Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
G E5
@K Digital Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H E5ZE Temperature Controller Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I E5ZE Temperature Controller Write Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
J E5
@J Temperature Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
K ES100
@ Digital Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L K3T
@ Intelligent Signal Processor Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
M V500/V520 Bar Code Reader Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
N 3Z4L Laser Micrometer Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
O Visual Inspection System Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P V600/V620 ID Controller Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Q Hayes Modem AT Command Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R Changing Communications Port Settings Using STUP(237) . . . . . . . . . . . . . . . . . . . . . . .
441
465
485
501
523
359
363
393
417
543
559
599
621
633
669
689
727
735
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 739
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 749
ix
x
About this Manual:
This manual describes the installation and operation of the SYSMAC CS/CJ-series CS1W-SCB21-V1/
SCB41-V1 Serial Communications Boards and CS1W-SCU21-V1 and CJ1W-SCU21-V1/SCU41-V1
Serial Communications Units and includes the sections described on the next page.
The Serial Communications Boards are classified as Inner Boards and the Serial Communications
Unit is classified as a CPU Bus Unit.
Please read this manual and all related manuals listed in the following table carefully and be sure you understand the information provided before attempting to install and operate a Serial Communications
Board or Unit.
Name
SYSMAC CS/CJ-series
CS1W-SCB21-V1/41-V1, CS1W-SCU21-V1,
CJ1W-SCU21-V1/41-V1
Serial Communications Boards and
Serial Communications Unit Operation Manual (this manual)
SYSMAC CS/CJ-series
CQM1H-PRO-E1, CQM1-PRO01-E,
C200H-PRO27-E
Programming Consoles Operation Manual
SYSMAC CS-series CS1G/H-CPU
@@H, CS1G/H-
CPU
@@-EV1
Programmable Controllers Operation Manual
SYSMAC CJ-series
CJ1G/H-CPU
@@H, CJ1M-CPU@@,
CJ1G-CPU
@@
Programmable Controllers Operation Manual
SYSMAC CS/CJ-series CS1G/H-CPU
@@-EV1,
CS1G/H-CPU
@@H,
CJ1G-CPU
@@-E, CJ1G/H-CPU@@H
Programmable Controllers Programming Manual
SYSMAC CS/CJ-series CS1G/H-CPU
@@H, CS1G/
H-CPU
@@-EV1, CJ1G/H-CPU@@H, CJ1G-CPU@@,
CJ1M-CPU
@@
Programmable Controllers
Instructions Reference Manual
SYSMAC CS/CJ-series
CS1G-/H-CPU
@@H, CS1G/H-CPU@@-E, CS1W-
SCB21-V1/41-V1, CS1W-SCU21-V1, CJ1G/H-
CPU
@@H, CJ1G-CPU@@, CJ1W-CPU@@, CJ1W-
SCU21/41
Communications Commands Reference Manual
SYSMAC WS02-CXPC1-E-V60
CX-Programmer Operation Manual
Cat. No.
W336
W341
W339
W393
W394
W340
W342
W446
Contents
Describes the use of Serial Communications Unit and Boards to perform serial communications with external devices, including the usage of standard system protocols for OMRON products.
Provides information on how to program and operate
CS/CJ-series PLCs using a Programming Console.
Describes the installation and operation of the CSseries PLCs.
Describes the installation and operation of the CJseries PLCs.
Describes the ladder diagram programming functions and other functions supported by CS-series and CJseries PLCs.
Describes the ladder diagram programming instructions supported by CS-series and CJ-series PLCs.
Describes the Host Link and FINS communications commands used with CS-series and CJ-series PLCs.
SYSMAC WS02-PSTC1-E
CX-Protocol Operation Manual
SYSMAC CS/CJ-series
CS1W-ETN01, CS1W-ETN11, CJ1W-ETN11
Ethernet Unit Operation Manual
W344
W343
Provides information on how to use the CX-Programmer, a programming device that supports the CSseries and CJ-series PLCs.
Describes the use of the CX-Protocol to create protocol macros as communications sequences to communicate with external devices.
Describes the installation and operation of CS1W-
ETN01, CS1W-ETN11, and CJ1W-ETN11 Ethernet
Unit.
xi
About this Manual, Continued
This manual contains the following sections.
Section 1 introduces the hardware and software functions of the Serial Communications Boards and the Serial Communications Units, including the communications modes, system configurations, and specifications.
Section 2 describes the components of the Serial Communications Boards and the Serial Communications Units, the settings required for operation, and the memory allocated in the I/O memory of the
CPU Unit for controlling and monitoring communications.
Section 3 describes how to mounting the Serial Communications Boards and Serial Communications
Units, and how to connect the ports to external devices.
Section 4 describes the procedure and other information required to use Host Link communications.
Section 5 describes the procedure and other information required to use protocol macros.
Section 6 provides an overview of the Serial Gateway, information on I/O memory allocations, and procedures for using the functions. Information on protocol conversion, routing table requirements, and communications frames is also provided. The Serial Gateway can be used only for Unit Ver. 1.2 or later.
Section 7 describes the procedure and other information required to use the no-protocol mode. This mode is supported for Unit Ver. 1.2 or later only.
Section 8 describes the procedure and other information required to use 1:N NT Links to Programmable Terminals.
Section 9 describes the procedure and other information required to conduct loopback test to check the serial ports.
Section 10 describes the troubleshooting and maintenance procedures for the Serial Communications
Boards and the Serial Communications Units.
Appendix A to Appendix Q provide the specifications of the standard system protocols.
Appendix R provides information on using STUP(237) to change serial port settings.
xii
!WARNING
Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-
INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xiii
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
xiv
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xv
xvi
PRECAUTIONS
This section provides general precautions for using the CS/CJ-series Serial Communications Boards and Units.
The information contained in this section is important for the safe and reliable application of Programmable
Controllers. You must read this section and understand the information contained before attempting to set up or operate a PLC system.
7
8
9
5
6
3
4
1
2
Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1
6-2
6-3
Applicable Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Concepts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Conformance to EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4
6-5
EMI Measures for Serial Communications Boards and Units . . . . .
EMS Measures for Serial Communications Units . . . . . . . . . . . . . .
Unit Versions of CS/CJ-series Serial Communications Boards/Units . . . . . .
Functions Added in the Unit Version 1.3 Upgrade . . . . . . . . . . . . . . . . . . . . .
Functions Added in the Unit Version 1.2 Upgrade . . . . . . . . . . . . . . . . . . . . .
xvii
Intended Audience
1
2
Intended Audience
1
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!WARNING
It is extremely important that a PLC and all PLC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PLC System to the above-mentioned applications.
3 Safety Precautions
!WARNING
Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the PLC or another external factor affecting the PLC operation. Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
• The PLC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed.
As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
• The PLC outputs may remain ON or OFF due to deposition or burning of the output relays or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
• When the 24-V DC output (service power supply to the PLC) is overloaded or short-circuited, the voltage may drop and result in the outputs
xviii
Operating Environment Precautions
4
being turned OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
!WARNING
Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
!WARNING
Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
!WARNING
Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!Caution Execute online edit only after confirming that no adverse effects will be caused by extending the cycle time. Otherwise, the input signals may not be readable.
4 Operating Environment Precautions
!Caution Do not operate the control system in the following places:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution The operating environment of the PLC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PLC
System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system. Follow all installation instructions and precautions provided in the operation manuals.
xix
Application Precautions
5 Application Precautions
Observe the following precautions when using the PLC System.
5
!WARNING
Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
• Always connect to a ground of 100
Ω or less when installing the Units. Not connecting to a ground of 100
Ω or less may result in electric shock.
• Always turn OFF the power supply to the PLC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Serial Communications Units, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Mounting or dismounting terminal blocks.
!Caution Failure to abide by the following precautions could lead to faulty operation of the PLC or the system, or could damage the PLC or PLC Units. Always heed these precautions.
• Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
• Tighten the mounting screws at the bottom of Serial Communications
Units to a torque of 0.4 N
⋅m. An incorrect tightening torque may result in malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Always check polarity before wiring RS-422A/485 connectors. The polarity for the SDA/B and RDA/B signals can be different for some external devices.
• Check to be sure that terminating resistors have been correctly installed for RS-422A/485 systems before starting operation.
• Disconnect the LG terminal of the Power Supply Unit from the GR terminal when performing insulation and dielectric strength tests.
• Never turn OFF the power supply while writing protocol macro data.
• Wire all connections correctly according to instructions in this manual.
• Check terminal blocks completely before mounting them.
• Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning.
xx
Application Precautions
5
• Be sure that the Bus Connection Unit and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
• Check the user program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation.
• Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PLC (including the setting of the startup operating mode).
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Do not install the product near devices generating strong high-frequency noise.
• Do not drop the product or subject it to excessive vibration or shock.
• Observe the following precautions for communications cables.
• Do not lay communications cables near power lines or high-voltage lines.
• Always lay communications cables in ducts.
• Do not pull on the communications cables or bend the communications cables beyond their natural limit. Doing either of these may break the cables.
• Do not place objects on top of the communications cables or other wiring lines. Doing so may break the cables.
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static built-up. Not doing so may result in malfunction or damage.
• Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation.
• Do not touch circuit boards or the components mounted to them with your bare hands. There are sharp leads and other parts on the boards that may cause injury if handled improperly.
• When transporting or storing Boards, wrap them in material that will protect LSIs, ICs, and other components from static electricity and be sure that they remain within the storage temperature range.
• When creating Host Link FINS command frames using the CMND(490) instruction, always set the unit number for Host Link incremented by one
(1 to 32) for the remote destination (send destination) node address (word
C+3, bits 08 to 15 of the CMND(490) instruction). Do not set the unit number of the actual Host Link slave (0 to 31). Using the Host Link unit number without incrementing by one will access the PLC with the entered
Host Link unit number less one.
For example, specify the remote PLC with Host Link unit number 2 by entering 3 for the remote destination node address. If 2 is entered, the
PLC with Host Link unit number 1 will be accessed.
To access a PLC on a Host Link FINS network using the Serial Gateway from CX-Programmer, however, enter the actual Host Link unit number, without incrementing by one. (Select Change PLC, click the Display
Serial Gateway Guide Button, and set unit number in the Host Link
SYSWAY Settings field of the Serial Gateway Guide Dialog Box.
xxi
Conformance to EC Directives
6
6-1
6-2
6
• When the Serial Gateway is executed during protocol macro execution, the communications sequence contents and the FINS command reception timing may suspend step transition of the communications sequence
(when the next step does not contain the RECEIVE command, the Serial
Gateway will be executed by interrupting the sequence before the next step, and the step transition will be suspended).
Use the Serial Gateway send start timeout function to monitor at the source of the FINS command whether step transition in the communications sequence has been suspended due to execution of the Serial Gateway. If the converted command does not start to be sent within the set time, either retry executing the FINS command or change the communications sequence.
• The following operations will result if the Serial Gateway is executed either using a pre-Ver. 1.2 Board/Unit or using a Ver. 1.2 or later Unit/Board without Serial Gateway or protocol macro mode set for serial communications at the serial port.
• If either NT Link or loopback test mode is used for serial communications, or if protocol macro mode is used with a pre-Ver. 1.2 Board/Unit, an undefined command response will be returned (end code: 0401 hex).
• If Host Link mode is used for serial communications, the message will be converted into a FINS command using Host Link slave-initiated communications and transferred (this will mainly result in a response timeout being returned, depending on the remote device (end code:
0205 hex))
• If a no-protocol instruction is sent to a pre-Ver. 1.2 Board/Unit or the serial port of a Board/Unit with Unit Ver. 1.2 or later using a serial communications mode other than no-protocol mode, the following operations will occur.
• If TXD(236)/RXD(235) is sent to the Board, Auxiliary Area bit A424204
(Inner Board Service Failure Flag) will turn ON.
• If TXDU(256)/RXDU(255) is sent to the Unit and the serial communications mode is set to protocol macro, NT Link, loopback test, or Serial
Gateway mode, an undefined command error (end code: 0401 hex) will be returned.
If the serial communications mode is set to Host Link mode and the instruction will be converted to a slave-initiated function FINS command and transferred. (Depending on the remote device, a response timeout
(end code: 0205 hex) is likely to be returned.)
Conformance to EC Directives
Applicable Directives
• EMC Directives
• Low Voltage Directive
Concepts
EMC Directives
OMRON devices that comply with EC Directives also conform to the related
EMC standards so that they can be more easily built into other devices or the overall machine. The actual products have been checked for conformity to
EMC standards (see the following note). Whether the products conform to the
xxii
Conformance to EC Directives
6-3
6-4
6
standards in the system used by the customer, however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will vary depending on the configuration, wiring, and other conditions of the equipment or control panel on which the OMRON devices are installed.
The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
Note Applicable EMS (Electromagnetic Susceptibility) and EMI (Electromagnetic
Interference) standards in the EMC (Electromagnetic Compatibility) standards are as follows:
Unit/Board
CS1W-SCB21-V1/
SCB41-V1
CS1W-SCU21-V1
CJ1W-SCU21-V1
CJ1W-SCU41-V1
EN61131-2
EMS
EN61000-6-2
EMI
EN61000-6-4
(Radiated emission: 10-m regulations)
Low Voltage Directive
Always ensure that devices operating at voltages of 50 to 1,000 VAC and 75 to 1,500 VDC meet the required safety standards for the PLC (EN61131-2).
Conformance to EC Directives
The CS/CJ-series PLCs comply with EC Directives. To ensure that the machine or device in which the CS/CJ-series PLC is used complies with EC directives, the PLC must be installed as follows:
1,2,3...
1.
The CS/CJ-series PLC must be installed within a control panel.
2.
You must use reinforced insulation or double insulation for the DC power supplies used for the communications power supply and I/O power supplies.
3.
CS/CJ-series PLCs complying with EC Directives also conform to the
Common Emission Standard (EN61000-6-4). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must therefore confirm that the overall machine or equipment complies with EC Directives.
EMI Measures for Serial Communications Boards and Units
The CS/CJ-series PLCs conform to the Common Emission Standards
(EN61000-6-4) of the EMC Directives. However, the noise generated from
Serial Communications Board or Unit communications cables may not satisfy these standards. In such a case, commercially available ferrite cores must be placed on the communications cable or other appropriate countermeasures must be provided external to the PLC.
xxiii
Unit Versions of CS/CJ-series Serial Communications Boards/Units
Recommended Ferrite Cores
The following ferrite core (data line noise filter) is recommended:
0443-164151 by Fair-Rite Products Corp.
Low impedance, 25 MHz: 90
Ω, 100 MHz: 160 Ω
7
Recommended Mounting Method
Mount the core on one turn of the communications cable, as shown in the following illustration.
Mount the cores as lost to the end of the communications cable as possible, as shown in the following illustration.
Serial
Communications
Unit/Board
6-5 EMS Measures for Serial Communications Units
The immunity testing conditions for the CJ1W-SCU41-V1 Serial Communications Unit are as follows: A ferrite core is mounted on the test cable connected to the RS-422A/485 port.
Refer to 6-4 EMI Measures for Serial Communications Boards and Units for
information on mounting the ferrite core.
7 Unit Versions of CS/CJ-series Serial Communications
Boards/Units
Unit Versions
A “unit version” has been introduced to manage CS/CJ-series Serial Communications Units/Boards according to differences in functionality accompanying upgrades.
1. Unit Version Notation on Products
The unit version code is provided on the nameplate of the CS-series Serial
Communications Boards and Units for which unit versions are being managed, as shown below for the Loop Control Board. This system applies to
Serial Communications Units or Boards with unit version 1.2 or later.
• Serial Communications Boards
xxiv
Unit Versions of CS/CJ-series Serial Communications Boards/Units
Example: CS1W-SCB21-V1 CS-series
Serial Communications Board
Nameplate
Unit version 1.3
CS1W-SCB21-V1
SERIAL COMMUNICATION BOARD
Lot No. 051020 Ver.1.3
OMRON Corporation
MADE IN JAPAN
7
• Serial Communications Units
Example: CS1W-SCU21-V1 CS-series
Serial Communications Unit
Nameplate
CS1W-SCU21-V1
SERIAL COMMUNICATION UNIT
:
Lot No. 051020 0000 Ver.1.3
OMRON Corporation MADE IN JAPAN
Unit version 1.3
2. Confirming Unit Versions with Support Software
CX-Programmer version 5.0 can be used to confirm the unit version in the
Unit Manufacturing Information.
■Boards
In the I/O Table Window, right-click on the CPU Unit, and then select Unit
Manufacturing Information – Inner Board
■Units
1.
In the I/O Table Window, right-click on the Serial Communications Unit, and then select Unit Manufacturing Information.
2.
The following Unit Manufacturing Information Dialog Box will be displayed.
xxv
Unit Versions of CS/CJ-series Serial Communications Boards/Units
7
The unit version is displayed.
Example: In this Unit Manufacturing Information Dialog Box, unit version 1.3 is displayed. Use this dialog box to confirm the unit version of the Serial Communications Unit that is connected online.
3. Using the Unit Version Labels
Unit version labels are provided with the product. These labels can be attached to the front of previous Serial Communications Boards/Units to differentiate between Serial Communications Boards/Units of different unit versions.
Unit Version Notation
The unit versions are indicated in this manual as follows:
Notation in product nameplate
Ver. 1.3 or later after the lot number
Ver.1.2 after the lot number
Blank after the lot number
Notation in this manual
CS/CJ-series Serial Communications Units with unit version 1.3 or later
CS/CJ-series Serial Communications Units with unit version 1.2
Pre-Ver. 1.2 CS/CJ-series
Serial Communications Units
Remarks
Information for which no particular version is specified applies to all unit versions.
xxvi
Unit Versions of CS/CJ-series Serial Communications Boards/Units
7
Function Support by Unit Version
Product
CS Series Serial Communications Boards
Earlier version
(pre-ver. 1.2)
CS1W-SCB21-V1
CJ Series
Serial Communications Units
Serial Communications Units
Serial gateway
Host Link 1:1 links
CS1W-SCB41-V1
CS1W-SCU21-V1
CJ1W-SCU21
CJ1W-SCU41
Not supported
Not supported
No-protocol
Host Link compatible device selection
Not supported
Not supported
Unit version 1.2
Unit version 1.3
CS1W-SCB21-V1 (Same as pre-ver. 1.2)
CS1W-SCB41-V1 (Same as pre-ver. 1.2)
CS1W-SCU21-V1 (Same as pre-ver. 1.2)
CJ1W-SCU21-V1
CJ1W-SCU41-V1
Supported
Supported
Supported
Supported
On-request I/O refreshing
Continuous I/O refreshing
Select to clear or hold contents.
CS1W-SCB21-V1 (Same as pre-ver. 1.2)
CS1W-SCB41-V1 (Same as pre-ver. 1.2)
CS1W-SCU21-V1 (Same as pre-ver. 1.2)
CJ1W-SCU21-V1 (Same as pre-ver. 1.2)
CJ1W-SCU41-V1 (Same as pre-ver. 1.2)
Supported (Same as prever. 1.2)
Supported (Same as prever. 1.2)
Supported (Same as prever. 1.2)
Supported (Same as prever. 1.2)
On-request I/O refreshing
Continuous I/O refreshing
(Same as pre-ver. 1.2)
Select to clear or hold contents. (Same as pre-ver.
1.2)
Protocol macro
Link word specification data exchange timing
Reception buffer processing for
PMCR(260) instruction execution
Baud rate (bps)
On-request I/O refreshing only
Clearing only
Standard system protocol additions
MODBUS slave protocol added
38,400 max. (57,600 and
115,200 not supported)
Not supported
57,600 supported.
Supported
-----
57,600 supported. (Same as pre-ver. 1.2)
Supported (Same as prever. 1.2)
Supported
Note Make sure that a CS/CJ-series CPU Unit with unit version 3.0 or later is used when using no-protocol mode.
Unit Versions and Manufacturing Dates/Lot Numbers
Classification
Inner Boards
CPU Bus Units
CPU Unit Support Software
Type
Serial Communications Boards
Serial Communications Units
CX-Programmer
Model
CS1W-SCB21-V1
CS1W-SCB41-V1
May 2004
Pre-Ver. 1.2
June 2003
Unit version 1.2
(Lot No.: 040617 and later)
December 2005
Unit version 1.3
CS1W-SCU21-V1
CS1W-SCU21-V1
Pre-Ver. 1.2
Unit version 1.2
(Lot No.: 040617 and later)
CS1W-SCU41-V1
WS02-CXPC1-JV
@
Ver. 4.0 or earlier Ver. 5.0
Unit version 1.3
Version 6.1
xxvii
Functions Added in the Unit Version 1.3 Upgrade
8
8 Functions Added in the Unit Version 1.3 Upgrade
Functions Added in Version Upgrade
The following table provides a comparison between the functions provided in the upgrade to unit version 1.3 or later of CS1W-SCB
@@-V1 Serial Communications Boards and CS1W-SCU
@@-V1, CJ1W-SCU@@-V1 Serial Communications Units, and the functionality of earlier versions.
Serial communications mode
Item
Modbus-RTU slave mode
Previous unit versions
Not supported
Unit version 1.3 and later
Supported
9 Functions Added in the Unit Version 1.2 Upgrade
Upgraded Models
The model numbers of CS-series Serial Communications Units/Boards have not changed. A “-V1” suffix has been added to the model numbers of CJseries Serial Communications Units with the unit version 1.2 upgrade, as shown in the following table.
PLC
CS
Series
CJ
Series
Product Specifications
Serial Communications
Boards
Serial Communications
Units
Serial Communications
Units
RS-232C
×
1,
RS-232C
×
1
RS-232C
×
1,
RS-422A/485
×
1
RS-232C
×
1,
RS-232C
×
1
RS-232C
×
1,
RS-232C
×
1
RS-232C
×
1,
RS-422A/485
×
1
Model Model number after upgrade to unit version 1.2
CS1W-SCB21-V1
→
Same
CS1W-SCB41-V1
→
Same
CS1W-SCU21-V1
→
Same
CJ1W-SCU21
CJ1W-SCU41
→
CJ1W-SCU21-V1
→
CJ1W-SCU41-V1
xxviii
Functions Added in the Unit Version 1.2 Upgrade
9
Functions Added in Version Upgrade
The following table provides a comparison between the functions provided in the upgrade to unit version 1.2 or later of CS1W-SCB
@@-V1 Serial Communications Boards and CS1W-SCU
@@-V1, CJ1W-SCU@@-V1 Serial Communications Units, and the functionality of earlier versions.
Serial communications mode
Item
Serial Gateway
Host Link
No-protocol
Earlier versions
(pre-Ver.1.2)
Not supported
Unit version 1.2 or later
1:1 protocol Not supported (1:N
Host Links only)
Host Link compatible device selection
Not supported (not completely compatible with C-series
Host Link and CVM1/
CV-series Host Link)
Not supported
Supported
The received FINS command can be converted into serial communications protocol and then converted into either of the following protocols (using the Serial Gateway mode).
• CompoWay/F
• Modbus-RTU
• Modbus-ASCII
• Host Link FINS (This protocol can be used to make the PLC function as the Host Link Master.)
The Serial Gateway can also be used in protocol macro mode. This option enables, for example, programming or monitoring of a serially connected
PLC from a CX-Programmer that is connected to the PLC during execution of protocol macros (e.g.,
Host Link Master).
Supported
This protocol functions the same as the 1:1 Host
Link supported by the earlier C200H, C1000H, and
C2000H Series, thereby enabling the use of host computer programs for 1:1 Host LInks created using these earlier PLCs.
Note: CS/CJ-series, C200HS/HX/HG/HE(-Z),
CPM
@
, CQM1
@
, and CVM1/CV Series all support
1:N Host Links only. C200H and C500 Host LInk
Units support both 1:1 and 1:N Host Links.
The compatible device mode enables full compatibility of Host Link functions (see note) with C-series
Host Link and CVM1/CV-series Host Link.
Note: E.g., differences in specifications for delimiter words in response frame data
Supported, but only when using a CS/CJ-series
CPU Unit with unit version 3.0 or later.
(The no-protocol mode that was previously possible only at the built-in RS-232C port of CPU Unit is now available for the Serial Communications
Boards and Units.)
This protocol is mainly used for communications with devices that perform input or output only, such as bar code readers and printers.
This mode enables no-protocol communications even if the CPU Unit’s built-in RS-232C port is being used for another application.
xxix
Functions Added in the Unit Version 1.2 Upgrade
9
Enhanced protocol macro functions
Standard system protocol
Item
Link word specification data exchange timing
Reception buffer processing for PMCR(260) instruction execution (immediately before communications sequence execution)
Baud rate for protocol macro mode
Host Link C-mode Command
Master
Host Link FINS Command
Master
Earlier versions
(pre-Ver.1.2)
On-request I/O refreshing only
(request to refresh sent to CPU Unit at every send/receive command execution, and data exchanged during I/O refresh)
In this method, after the send command is executed, a delay occurs before the actual message is sent.
Unit version 1.2 or later
Continuous I/O refreshing (selected in DM Area settings) is supported in addition to the on-request
I/O refreshing available in earlier models.
Continuous I/O refreshing is performed from the
CPU Unit during protocol macro execution, regardless of requests from the Board/Unit, and data in the Board/Unit is accessed during send/receive command execution. When the send command is executed with this method, the actual message can be sent immediately.
Clearing to zero only Select to clear or hold the contents of the reception buffer during full-duplex communications (set in the allocation DM Area).
This enables the data in the reception buffer received in the previous communications sequence to be held after switching the communications sequence during full-duplex communications.
57,600 bps supported (115,200 bps not supported) 38,400 bps max.
(57,600 bps not supported)
None (protocols must be created using CX-
Protocol)
Provided
A Host Link Master can be used to easily access the Host Link slave PLC
(e.g., A PLC slave on a moving body can be accessed via a WMseries Wireless Modem in a Host Link.)
Host Link C-mode commands can be used to access a C-series or CS/
CJ-series PLC slave.
Host Link FINS commands can be used to access a CS/CJ-series or CVM1/CV-series PLC slave.
This protocol can also be used to access slave
PLCs on the network.
Mitsubishi Computer Link
Master (A-compatible, 1C frame, model 1)
CompoWay/F Master ---
Provided
Computer Link commands can be used to access a
Mitsubishi PLC (Sequencer CPU Module) slave.
Communications sequences with different send and receive protocols are provided by using send/ receive commands with ASCII conversion.
The communications sequences have been expanded to include CompoWay/F commands such as VARIABLE AREA READ/WRITE and
OPERATING INSTRUCTIONS.
xxx
SECTION 1
Introduction
This section introduces the hardware and software functions of the Serial Communications Boards and the Serial
Communications Units, including the communications modes, system configurations, and specifications.
1-2-1 Serial Communications Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-1 Host Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-5 Serial Gateway Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-6 No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3-7 Modbus-RTU Slave Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-4-1 Serial Communications Boards and Units . . . . . . . . . . . . . . . . . . . .
1-6-1 Serial Communications Boards and Unit . . . . . . . . . . . . . . . . . . . . .
1-6-2 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-6-3 Protocol Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-8 Selecting the Serial Communications Mode . . . . . . . . . . . . . . . . . . . . . . . . . .
1-9-2 Explanation of Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Using this Manual
Section 1-1
1-1 Using this Manual
This manual is structured to provide information on Host Link, protocol macro, and 1:N NT link communications in functional units, as would be required in actual applications. You should read Section 1 Introduction first, and then read information in the rest of the manual and related manuals as required by your specific application.
Information
Overview and appearance of the Serial Communications Boards and Serial Communications Unit
Overview, features, and specifications of serial communications
Section or Manual
1-2 Overview
2-1 Component Names and Functions
1-3 Protocol Overview
1-4 Features
1-6 Specifications
4-1 Host Link Communications
5-1 Overview of the Protocol Macro Functions
8-1 Overview of 1:N NT Links
1-9 Basic Operating Procedure Basic procedures and operations
Selecting serial communications modes
System configurations for serial communications modes
1-8 Selecting the Serial Communications Mode
1-5 System Configurations
Memory Area allocations to the Serial Communications Boards and Serial Communications Unit
2-2 Data Exchange with the CPU Unit
2-3 I/O Memory Allocations
Section 3 Installation and Wiring Installing and wiring the Serial Communications
Boards and Serial Communications Unit
Memory Area allocations to individual serial communications modes
4-2, 5-2, and 8-2 Setup Area Allocations
4-3, 5-3, and 8-3 Auxiliary Area and CIO Area Allocations
4-4 Communications Timing Communications timing for slave-initiated Host Link communications
Ladder diagram programming in protocol macros 5-4 Using Protocol Macros
Loopback tests for ports Section 10 Loopback Test
Changing the communications port settings during operation
Troubleshooting and maintenance
The contents of standard system protocols and connection methods to OMRON components
Details on Host Link communications (including ladder diagram programming for slave-initiated communications)
Details on C-mode commands
Details on FINS commands
Details on the protocol macro function
Appendix R Changing Communications Port
Settings Using STUP(237)
Section 11 Troubleshooting and Maintenance
Appendix A to Appendix N
SYSMAC CS/CJ-series
CS1G/H-CPU
@@-E, CS1W-SCB21/41,
CS1W-SCU21 Communications Commands
Reference Manual (W342)
SYSMAC WS02-PSTC1-E
CX-Protocol Operation Manual (W344)
2
Overview
Section 1-2
1-2 Overview
This section gives an overview of the Serial Communications Boards and the
Serial Communications Unit.
1-2-1 Serial Communications Boards
Serial Communications Boards are Inner Boards for the CS-series PLCs. One
Board can be installed in the Inner Board slot of a CPU Unit. Two serial ports are provided for connecting host computers, Programmable Terminals (PTs), general-purpose external devices, and Programming Devices (excluding Programming Consoles). This makes it possible to easily increase the number of serial ports for a CS-series PLC.
Serial Communications
Board
Inner Board slot
Models
The following two models are available:
CS1W-SCB21-V1
Two RS-232C ports
CS1W-SCB41-V1
One RS-232C port + one RS-422A/485 port
RS-232C port
RS-232C port
RS-232C port
RS-422A/485 port
Connectable Devices
The following serial communications modes are supported by the Serial Communications Unit: Host Link (SYSMAC WAY) (see note 1), protocol macro,
1:N NT Link (see note 2), no-protocol (see note 1), Modbus-RTU slave (see note 3), and loopback test modes. The devices shown in the following diagram can be connected.
General-purpose external device
Programmable
Terminal (PT)
Programming
Device (excluding
Programming
Console)
Host computer
Serial Communications Board
CPU Unit
General-purpose external device
Programmable
Terminal (PT)
Programming
Device (excluding
Programming
Console)
Host computer
3
Overview
Note
Section 1-2
(1) The Host Link 1:1 and no-protocol modes are supported by unit version
1.2 or later.
(2) Only a 1:N NT Link is supported. A 1:1 NT Link is not supported.
(3) The Modbus-RTU slave mode is supported by unit version 1.3 or later.
A serial communications mode for the Serial Gateway is also provided, enabling connection with the following devices.
Modbus-RTU-compatible device (e.g., Inverter)
Modbus-ASCII-compatible device (e.g., Servo)
PLC (Host Link)
CompoWay/Fcompatible
OMRON component
FINS message
Serial Communications Board with unit version
1.2 or later
CPU Unit
Protocol conversion
Protocol conversion
FINS message
CompoWay/Fcompatible
OMRON component
PLC (Host Link)
Modbus-RTU-compatible device (e.g., Inverter)
Modbus-ASCII-compatible device (e.g., Servo)
1-2-2 Serial Communications Units
The Serial Communications Units are CPU Bus Unit. One or more Units can be mounted to the CPU Unit or a CS/CJ Expansion Rack. A total of up to 16
CPU Bus Units can be controlled by one CPU Unit. The CS-series Serial
Communications Unit must be used for a CS-series PLC and a CJ-series
Serial Communications Unit must be used for a CJ-series PLC.
Two serial ports are provided for connecting host computers, Programmable
Terminals (PTs), general-purpose external devices, and Programming
Devices (excluding Programming Console). This makes it possible to easily increase the number of serial ports for the CS/CJ-series PLC.
CS Series
Serial Communications Unit
4
Overview
Section 1-2
CJ Series
CS1W-SCU21-V1 (Two RS-232C ports)
RS-232C port
RS-232C port
Serial Communications Unit
PA205R
POWER SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
OPEN
RUN
ERR/ALM
INH
PRPHL
COMM
MCPWR
BUSY
AC100-240V
INPUT
L1
L2/N
PERIPHERAL
RUN
OUTPUT
AC240V
DC24V
PORT
CJ1W-SCU21-V1 (Two RS-232C ports)
SCU41
RUN ERC
RDY
TERM
OFF
ERH
ON
SD1 RD1
TER1
SD2 RD2
23
4567 UNIT
NO.
WIRE
2 4
PORT1
(RS422
/485)
PORT2
RS-232C port
CJ1W-SCU41-V1 (One RS-232C and One RS-422A/485 Port)
RS-422A/485 port
RS-232C port
Connectable Devices
The following serial communications modes are supported by the Serial Communications Boards: Host Link (SYSMAC WAY) (see note 1), protocol macro,
1:N NT Link (see note 2), no-protocol (see note 1), Modbus-RTU slave (see note 3), and loopback test modes. The devices shown in the following diagram can be connected.
5
Overview
General-purpose external device
Programmable
Terminal (PT)
Programming
Device (excluding
Programming
Console)
Host computer
Serial Communications Unit
Section 1-2
CS/CJ-series PLC
General-purpose external device
Programmable
Terminal (PT)
Programming
Device (excluding
Programming
Console)
Host computer
Note
(1) The Host Link 1:1 and no-protocol modes are supported by unit version
1.2 or later.
(2) Only a 1:N NT Link is supported. A 1:1 NT Link is not supported.
(3) The Modbus-RTU slave mode is supported by unit version 1.3 or later.
A serial communications mode for the Serial Gateway is also provided, enabling connection with the following devices.
Modbus-RTU-compatible device (e.g., Inverter)
Modbus-ASCII-compatible device (e.g., Servo)
PLC (Host Link)
CompoWay/Fcompatible
OMRON component
FINS message
Serial Communications Unit with unit version 1.2 or later
CPU Unit
Protocol conversion
Protocol conversion
FINS message
CompoWay/Fcompatible
OMRON component
PLC (Host Link)
Modbus-RTU-compatible device (e.g., Inverter)
Modbus-ASCII-compatible device (e.g., Servo)
Functions Added in the
“-V1” Upgrade
The CS1W-SCB21-V1 and CS1W-SCB41-V1 Serial Communications Boards and CS1W-SCU21-V1 Serial Communications Unit* were upgraded to support the Simple Backup Function in the “-V1” upgrade.
Note
*The CS-series Serial Communications Boards/Units without the “-V1” suffix do not support this Simple Backup Function, but the CJ1W-SCU21/41 does support this function even though the model number lacks the “-V1” suffix.
• Simple Backup Function
The CPU Unit’s Simple Backup Function can be used to automatically backup, restore, and compare the Protocol Macro data (both standard system protocol and user-set protocol data) in the Serial Communication
6
Protocol Overview
Section 1-3
Board or Unit’s flash memory with the data in the CPU Unit’s Memory Card.
The Protocol Macro data is backed up, restored, or compared along with all of the data in the CPU Unit. (The Simple Backup Function can be used with CS1-H and CJ1-H CPU Units only.)
1-3 Protocol Overview
A Serial Communications Board is an Inner Board for CS-series CPU Units that provides RS-232C and/or RS-422A/485 serial ports. An Inner Board is an option and is installed in the CPU Unit.
A Serial Communications Unit is a CPU Bus Unit that provides two RS-232C serial ports or one RS-232C and one RS-422A/485 port. The following eight serial communications modes can be used as required for each serial port.
• Host Link: For connections between host computers and PLCs
• Protocol macro: For communications between PLCs and general-purpose external devices
• 1:N NT Link: For communications between PLCs and Programmable
Terminals (PTs)
• Loopback test: For testing the communications ports
• Serial Gateway
• No-protocol
• 1:1 Host Link
• Modbus-RTU slave mode
Note
(1) The Serial Gateway can also be executed in protocol macro mode.
(2) Modbus-ASCII mode is not supported.
PLC
Series
CS
CJ
CS/CJ
Product
Serial
Communications
Boards
Model number
CS1W-
SCB21-V1
CS1W-
SCB41-V1
Serial ports
RS-232C
RS-232C
RS-232C
Host Link Protocol macro
OK
RS-232C OK
OK
RS-
422A/485
OK
(see note 1)
RS-232C OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Serial communications mode
1:N NT Link
(see note 2)
Loopback test
OK
OK
OK
OK
OK
OK
Serial
Gate way
OK
OK
OK
OK
OK
OK
Serial
Gateway in protocol macr o mode
OK
OK
OK
OK
OK
OK
Noprotocol
(See note
3.)
OK
OK
OK
OK
OK
OK
1:1
Host
Link
OK
OK
OK
OK
OK
OK
Serial
Communications Unit
Serial
Communications Unit
CS1W-
SCU21-V1
CJ1W-
SCU21-V1
CJ1W-
SCU41-V1
Device to be connected
Supporting unit versions
RS-232C
RS-232C
OK
OK
RS-
422A/485
OK
(see note 1)
RS-232C OK
Host computer or
Programming
Device
OK
OK
OK
OK
Generalpurpose external device
All unit versions
OK
OK
OK
OK
PT
OK
OK
OK
OK
None
OK
OK
OK
OK
OK
OK
OK
OK
Depends on the protocol used at the conversion destination
OK
OK
OK
OK
Generalpurpose external devic e
Unit version 1.2 or later
OK
OK
OK
OK
Modbus-
RTU slave
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Host Link computer
Unit version
1.3 or later
7
Protocol Overview
Section 1-3
Note
1.
A 4-wire connection must be used when using Host Link communications for an RS-422A/485 connector.
2.
A 1:1 NT Link is not supported.
3.
No-protocol mode can be used with CS/CJ-series CPU Units with Unit Ver.
3.0 or later only.
A connection example for each serial communications mode is shown in the following sections for a Serial Communications Unit. The examples apply equally as well to the Serial Communications Boards.
1-3-1 Host Link Mode
In Host Link mode, C-mode commands (Host Link commands) or FINS commands can be sent from a host computer to read or write I/O memory in the
PLC or to control the PLC’s operating modes. The host computer can be a personal computer or a Programmable Terminal. The FINS commands are sent with other data, such a Host Link header and terminator.
In Host Link mode, SEND(090), RECV(098), and CMND(490) instructions can be used to send FINS commands from PLC to the host computer to read data, write data, or perform other operations. This is called slave-initiated communications or unsolicited communications. The FINS commands are sent with other data, such a Host Link header and terminator.
Note
1.
FINS commands can be sent across up to three different networks (counting the local network) to a PLC on a remote network or to a host computer connected to a PLC on a remote network.
2.
Programming Devices can also be connected in Host Link mode.
Sending C-mode Commands
Sending FINS Commands
FINS command
Host Link
Host Link terminator
Host Link header
Host Link
C-mode (Host Link) command
FINS commands can also be sent to
PLCs on remote networks.
FINS command
Host Link
FINS command
Host Link header
Host Link terminator
Remote network
(Controller Link or
Ethernet)
8
Protocol Overview
Slave-initiated Communications
Section 1-3
SEND(090),
RECV(098),
CMND(490)
SEND(090): Sends data to host computer
RECV(098): Reads data from host computer
CMND(490): Executes any FINS command
FINS command
Host Link
Host Link terminator
Host Link header
Slave-initiated FINS commands can also be sent from PLCs on remote networks.
SEND(090),
RECV(098),
CMND(490)
Host Link
Remote network
(Controller Link or Ethernet)
FINS command
Host Link terminator
FINS command
Host Link header
Unit Ver. 1.2 or later supports the 1:1 Host Link protocol for C200H, C1000H, and C2000H CPU Units, which enables the use of host programs for 1:1 Host
Links created for these PLCs. A Host Link-compatible device selection function is also provided for complete compatibility with the C-series Host Link and
CVM1/CV-series Host Link.
1-3-2 Protocol Macros
Data transfer procedures (protocols) with general-purpose external devices are created using the CX-Protocol to match the communications specifications (half-duplex or full-duplex, and start-stop synchronization) of the external device.
These protocols are stored in the Serial Communications Boards or the Serial
Communications Unit, and enable data to be exchanged with general-purpose external devices simply by executing the PMCR(260) instruction in the
CPU Unit.
Standard system protocols for exchanging data with OMRON devices (such as Temperature Controllers, Intelligent Signal Processors, Bar Code Readers, and Modems) are provided as a standard feature in the Serial Communications Boards, the Serial Communications Unit, and the CX-Protocol. The CX-
Protocol can also be used to change the standard system protocols according to user requirements.
PMCR(260)
Serial Communications Unit
Communications sequence
Protocol
General-purpose external device
9
Protocol Overview
Section 1-3
The following additional functions are supported for unit Ver. 1.2 or later.
• Serial Gateway can be executed during protocol macro execution.
• An new I/O refresh method is provided for constant data conversion of link words.
• The contents of the reception buffer can be held while the PMCR(260) instruction is executing.
• A baud rate of 57,600 bps is possible (115,200 bps is not possible).
1-3-3 1:N NT Links
A PLC can be connected to one or more Programmable Terminals (PTs) using an RS-232C or RS-422A/485 port. The I/O memory of the PLC is allocated to the Status Control Areas and the Status Notification Areas used by the PTs, as well as to display objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PLC to be controlled and monitored by operations from the PTs, without the use of a ladder diagram programming in the PLC. Up to eight PTs can be connected to a
PLC.
Note
The user does not need to be aware of NT Link commands. The user only has to allocate the PLC memory to the PTs.
Serial Communications Unit Serial Communications Unit
NT Link
(Set to 1:N)
1:N NT Link
Note
PT PT
1.
The serial port on the PT must be set to a 1:N NT Link.
2.
The Serial Communications Boards and Units do not support 1:1 NT Links.
The NT Link must be set to 1:N even if only one PT is connected. Connection is not possible to PTs that do not support 1:N NT Links.
3.
The NT20S, NT600S, NT30, NT30C, NT620, NT620C, and NT625C cannot be used if the cycle time of the CPU Unit is 800 ms or longer (even if only one of these PTs is used in a 1:N NT Link).
4.
The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board or Unit ports.
They can be used only by connecting to the peripheral port or RS-232C port on the CPU Unit.
5.
Set a unique unit number for each PT connected to the same PLC. If the same unit number is set for more than one PT, malfunctions will occur.
6.
NT Link serial communications are unique and are not compatible with other serial communications modes.
10
Protocol Overview
Section 1-3
1-3-4 Loopback Test
A connector with a loopback connection is attached to the specified serial port to perform loopback tests. Data is sent to this port, and the communications circuit is tested by comparing the transmitted data and the data returned by loopback.
Note
This loopback test is performed inside the specified serial port. It is not a loopback test using the RS-232C or RS-422A/485 communications path.
Loopback test
Loopback test switch
The loopback test results are stored.
1-3-5 Serial Gateway Mode
The received FINS message is automatically converted to either Compo-
Way/F, Modbus-RTU, Modbus-ASCII, or Host Link FINS, depending on the type of message.
CompoWay/F, Modbus-RTU, and Modbus-ASCII
FINS CompoWay/F (See note.)
Network
Serial
Communications
Unit
CMND
Send FINS command
CompoWay (See note.)
Serial
Gateway
FINS
CompoWay/F (See note.)
Note: Or Modbus-RTU commands or Modbus
ASCII commands
CompoWay-compatible
OMRON component,
Modbus-RTU-, or Modbus
ASCII-compatible device
FINS Host Link
FINS
Network
CMND
Send FINS command
Serial
Gateway
FINS
FINS
Host Link header
Host link terminator
FINS
Host Link header
PLC (Host Link)
CX-Programmer or other
Programming Device for using CX-Server as a communications driver
Host link terminator
1-3-6 No-protocol Mode
No-protocol mode supports data receiving or data sending using data receive or send commands, respectively (see note). No-protocol mode, however, can be used only with CS/CJ-series CPU Units with unit Ver. 3.0 or later in which a
Serial Communications Board or Unit with Unit Ver. 1.2 or later is installed.
Use the no-protocol mode when the data send and receive protocols are to be created by the user, or when connecting to devices that only receive or send data, such as bar code readers, or printers.
11
Features
Section 1-4
Note
Serial Communications Boards send/receive data using TXD(236)/RXD(235) instructions. Serial Communications Units send/receive data using
TXDU(256)/RXDU(255) instructions.
E.g., TXDU
E.g., Execute data transmission
Serial Communications Unit
No-protocol
ST Text CR+LF
Note: Start code and end code can be specified.
General-purpose external device
1-3-7 Modbus-RTU Slave Mode
Modbus-RTU slave mode enables sending Modbus-RTU commands from the host computer to read and write PLC I/O memory.
Modbus-RTU
Modbus command
Serial Communications Unit
1-4 Features
This section describes the features of the Serial Communications Boards, the
Serial Communications Unit, and the protocols.
1-4-1 Serial Communications Boards and Units
Serial Communications
Boards (CS Series Only)
A Serial Communications Board is installed as an option in a CPU Unit. Two serial ports can thus be added without using an I/O slot.
There are two types of Serial Communications Boards: One with two RS-
232C ports and one with one RS-232C and one RS-422A/485 port. The RS-
422A/485 port can be used for a 1:N connection with general-purpose external devices without using Link Adapters to support the protocol macro function or NT Link function.
Serial Communications
Unit (CS/CJ Series)
A total of up to 16 CPU Bus Units can be mounted on the CPU Rack or an
Expansion Rack. The total of 16 must include all Serial Communications Units and all other CPU Bus Units. The PLC can thus be expanded to provide additional serial ports as required by the system.
1-4-2 Protocols
Host Link Communications
Host Link communications are supported by all CS/CJ-series CPU Units.
Serial Communications Boards and Units can be used to connect a single
PLC to more than one host computer for Host Link communications, including slave-initiated communications. Host Link communications provide the following features.
Connect One Computer to
Multiple PLCs
An RS-422A/485 port can be used to connect one host computer to up to 32
CS/CJ-series PLCs.
12
Features
Computer Monitoring and
Control of PLCs
FINS Commands for
Complete Control
Redundant Error
Checking
Simultaneous Usage of
Both Ports
Slave-initiated
Communications
Send FINS Commands to
Remote Networks
Section 1-4
Host Link communications enable the host computer to monitor or control
PLC operations and to read and write I/O memory in the PLCs.
In addition to C-series (Host Link) commands, FINS commands are also supported. FINS commands give you the power to control CS/CJ-series PLC functionality.
Both vertical and horizontal (FCS) parity checks are performed on communications data to achieve essentially error-free communications. Combining error checking and retry processing goes one step further to eliminate nearly all the effects of communications problems.
Each Serial Communications Board and Unit provides two serial ports that can be used simultaneously to connect to two different host computers. A total of up to 16 CPU Bus Units, including the Serial Communications Units, can be mounted to one PLC. If all 16 CPU Bus Units are Serial Communications
Units, then up to 32 ports can be added.
Communications can be performed either by sending a command from a host computer and having the PLC return a response, or by sending a command from a PLC and having the computer send a response. Starting communications from a slave is called unsolicited communications, and is made possible through the SEND(090), RECV(098), and CMND(490) instructions. These can be used to send FINS commands to a host computer connected locally or to a host computer connected to a remote network up to three networks away
(counting the local network).
A FINS command contained within a Host Link header and terminator can be sent using Host Link communications to PLCs connected not only on Host
Link networks, but also other interconnected remote networks up to three networks away (counting the local network). Various types of networks can exist between the source of the command and the destination of the command.
Host Link
Bridge
Ethernet Network
Send FINS Commands to
Computers Connected to
Remote PLCs
Controller Link Network
Controller Link Network
Gateway
A FINS command contained within a Host Link header and terminator can be sent using Host Link communications to a host computer connected to a PLC on a remote network up to three networks away (counting the local network, but not counting the final Host Link connection). Various types of networks can exist between the PLC sending the command and the destination of the command.
13
Features
Section 1-4
Bridge
Host Link
Ethernet Network
SEND(090),
RECV(098),
CMND(490)
Controller Link Network
Controller Link Network
Gateway
Protocol Macros
Wide Range of
Communications
Protocols
Send Frames and Receive
Frames Matching
Specifications
Communications-related
Functions
Send/Receive Monitoring
Retry Processing
PLC Read/Write Variables in Send Frames and
Receive Frames
Switch 1:N
Communications or the
Data Write Destinations
Using Repeat Processing
PLC Interrupts During
Data Reception
Next Process Switching
According to Receive Data
New Error Check Codes
Step Queuing for Sync
Signal from the PLC
Half-duplex or Full-duplex
Transmissions
The main features of the protocol macro functions are described below. For details, refer to the CX-Protocol Operation Manual (W344).
Communications are possible with virtually any general-purpose external device, provided it has an RS-232C or RS-422A/485 port, supports halfduplex or full-duplex communications, and supports start-stop synchronization.
Send frames (command + data and other send frames) and receive frames
(response and other frames) can be created and registered according to the communications frame specifications of the external device.
Error check code calculations, frame length calculations during sending, and
ASCII
⇔Hexadecimal conversion of numeric data are supported.
Receive wait monitoring, receive completion monitoring, and send completion monitoring are supported. If monitoring times are exceeded, send/receive can either be terminated, or retry processing can be performed.
Send/receive retry processing can be automatically executed when an error occurs, simply by setting the number of retries.
Variables for reading PLC memory can be included in the actual send frames.
These can be used as destination addresses or data when reading PLC data while sending. Variables for writing to PLC memory can be also included in the actual receive frames. These can be used to write the contents of destination addresses or data to the PLC during reception.
Repeat processing (repeat counters) for send/receive processing can be specified in communications sequences. This enables the same data to be sent by switching destination addresses during communications 1:N (N = 32 max. due to restrictions in the physical layer) or by switching the PLC memory write destination addresses during data reception.
An interrupt can be created in the PLC’s CPU Unit during data reception, and an interrupt program can be executed in the CPU Unit. (The PLC interrupt function is supported only for the Serial Communications Boards. This function cannot be used with Serial Communications Units.)
The contents of up to 15 set of expected receive data can be compared with the receive data to determine the next process.
LRC2 (two’s complement of LRC), and SUM1 (one’s complement of SUM) have been added to the error check codes.
At any step of the communications sequence, the next process can be made to wait until a sync signal from the PLC’s CPU Unit has been input. This enables processing, such as data manipulations, to be performed in the CPU
Unit during the communications sequence.
With the conventional protocol macro functions, only half-duplex transmissions were possible. With half-duplex mode, the reception buffer is cleared
14
Features
Section 1-4
Control ER Signal at Any
Time
immediately after the send operation is completed. Therefore, if there was a rapid response from the remote device, for example, the data received between data sending and the completion of the send operation could not be accessed as receive data by the next receive operation.
Support for the full-duplex transmissions enables all the data received in a sequence to be accessed. Data can also be received from a remote device while sending.
Note
Full-duplex transmissions can be used with either RS-232C or RS-422A/485 as long as 1:1, 4-wire connections are used. Full-duplex transmissions cannot be used with 1:N connections or 2-wire connections.
Clear Reception Buffer at
Any Time
With full-duplex mode, the reception buffer is cleared only immediately before a communications sequence is executed. When a reception or other fault occurs, the receive data can be cleared at any time using the reception buffer clear (FLUSH) command.
With a connection to a modem, the ER signal is used to show the communications enabled status of a Serial Communications Board or Unit (Data Terminal
Equipment (DTE)). In conventional operations, the ER signal could be turned
ON only while a communications sequence was being executed.
Improving this function has enabled the ER signal to be turned ON or OFF at any time during a communications sequence. This enables modem connections and disconnections to be performed by a protocol macro.
The ER signal can also be kept ON, even after a communications sequence has been completed. In this case, the ER signal remains ON, even after it has been switched to a different serial communications mode (for example, Host
Link). This function enables remote programming and monitoring to be performed using remote Programming Devices, by switching to the Host Link mode with the STUP(237) instruction once the connection has been made with the modem.
15
System Configurations
Section 1-5
1-5 System Configurations
This section explains the system configuration supported by each serial communications mode.
Host Link Communications
PLC:
Computer
1:1
Port:
RS-232C
Connection configuration
Connection to Serial Communications Board.
Note 1.
Note 3.
Required devices
Connected serial port/Remarks
CS1W-SCB21-
V1
Port 1 or 2
CS1W-SCB41-
V1
Port 1
Possible command flow
Host computer to PLC:
C-mode or
FINS commands
PLC to Host computer:
FINS commands only
Note 2.
NT-AL001-E
Note 3.
NT-AL001-E
Resistance ON,
5-V power
Resistance ON
Connection to Serial Communications Unit.
NT-AL001-E
Converting
Link Adapter
5-V power supply
CS1W-SCU21-
V1
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
Port 1 or 2
Note 1.
CJ1W-SCU21-
V1
Port 1 or 2
Note 3.
NT-AL001-E
Resistance ON,
5-V power
Note 3.
Note 2.
NT-AL001-E
Resistance ON
CJ1W-SCU41-
V1
Port 2
RS-422A/
485
RS-232C
NT-AL001-E
Converting
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
16
System Configurations
PLC:
Computer
1:1
Port:
RS-422A/
485
Connection configuration
Connection to Serial Communications Board
Note 3.
Note 2.
NT-AL001-E
Resistance ON,
5-V power
Resistance ON
Connection to Serial Communications Unit
Note 3.
Note 2.
NT-AL001-E
Resistance ON,
5-V power
Resistance ON
Section 1-5
Required devices
CS1W-SCB41-
V1
NT-AL001-E
Converting
Link Adapter
5-V power supply
CJ1W-SCU41-
V1
NT-AL001-E
Converting
Link Adapter
5-V power supply
Connected serial port/Remarks
Port 2
RS-232C
⇔
RS422A/485
For NT-AL001-E
Link Adapter
Port 1
RS-422A/
485
RS-232C
RS-232C
⇔
RS422A/485
For NT-AL001-E
Link Adapter
Possible command flow
Host computer to PLC
(4-wire only):
C-mode or
FINS commands
PLC to Host computer
(4-wire only):
FINS commands only
Host computer to PLC
(4-wire only):
C-mode or
FINS commands
PLC to Host computer
(4-wire only):
FINS commands only
17
System Configurations
PLC:
Computer
1:N
Port:
RS-232C
Connection configuration
Connection to Serial Communications Board.
Note 3.
Note 2.
Resistance ON,
5-V power
NT-AL001-E
Resistance
ON
Section 1-5
Required devices
Connected serial port/Remarks
CS1W-SCB21-
V1
Port 1 or 2
CS1W-SCB41-
V1
Port 1
Possible command flow
Host computer to PLC
(RS-422A/485 section: 4-wire):
C-mode or
FINS commands
PLC to Host computer:
Commands cannot be sent.
NT-AL001-E
Converting
Link Adapter
5-V power supply
CS1W-SCU21-
V1
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
Port 1 or 2
Connection to Serial Communications Unit.
Note 3.
Note 2.
Resistance ON,
5-V power
NT-AL001-E
Resistance
ON
CJ1W-SCU21-
V1
Port 1 or 2
CJ1W-SCU41-
V1
Port 2
RS-422A/
485
RS-232C
NT-AL001-E
Converting
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
18
System Configurations
PLC:
Computer
1:N
Port:
RS-422A/
485
Note 3.
Connection configuration
Connection to Serial Communications Board
Note 4.
Resistance ON,
5-V power
Note 2.
Resistance ON
Connection to Serial Communications Unit
Note 3.
Resistance ON,
5-V power
Note 4.
Note 2.
Resistance ON
Section 1-5
Required devices
Connected serial port/Remarks
CS1W-SCB41-
V1
Port 2
NT-AL001-E
Converting
Link Adapter
5-V power supply
CJ1W-SCU41-
V1
NT-AL001-E
Converting
Link Adapter
5-V power supply
RS-232C
RS422A/485
For NT-AL001-E
Link Adapter
Port 1
RS-422A/
485
RS-232C
RS-232C
⇔
⇔
RS422A/485
For NT-AL001-E
Link Adapter
Possible command flow
Host computer to PLC
(4-wire only):
C-mode or
FINS commands
PLC to Host computer:
Commands cannot be sent.
Host computer to PLC
(4-wire only):
C-mode or
FINS commands
PLC to Host computer:
Commands cannot be sent.
19
System Configurations
Section 1-5
PLC:
Computer
Host computer to
Network
PLCs, 1:N
Connection configuration Required devices
Connected serial port/Remarks
Port 1 or 2
Connection to Serial Communications Board or Serial
Communications Unit
CS1W-SCB21-
V1,
CS1W-SCB41-
V1,
CS1W-SCU21-
V1, CJ1W-
SCU21-V1, or
CJ1W-SCU41-
V1
Port 1 or 2
Possible command flow
Host computer to PLC:
FINS commands only
PLC to Host computer:
FINS commands only
(RS-422A/485:
4-wire only)
Controller Link or
Ethernet network
Port 1 or 2
Port 1 or 2
RS-422A/
485
RS-232C
Communications Unit:
Controller Link
Unit or Ethernet Unit.
or
Communications can be sent across three different networks (counting the local network, but not including a
Host Link connection). Routing tables must be set in the PLCs.
Host Link
Gateway or bridge
Network 3
Network 1
Note
Network 2
Gateway
1.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
2.
The combined cable length for RS-422A/485 is 500 m including branch lines.
3.
The maximum cable length is limited to 2 m when an NT-AL001-E Link
Adapter is connected.
4.
Branch lines must be a maximum of 10 m long.
5.
Four-wire connections must be used for RS-422A/485 connections with
Host Link communications.
6.
“Resistance ON” indicates that the terminating resistance must be turned
ON.
20
System Configurations
Section 1-5
7.
“5-V power” indicates that a 5-V power supply is required for the Link
Adapter. Refer to the Link Adapter manual for details. Be sure that the power supply has sufficient capacity and accuracy and wire it away from highpower lines and another sources of noise. A 5-V power supply is not required for a Link Adapter connected to a Serial Communications Board or
Unit because power is supplied from pin 6 of the connector.
8.
The maximum baud rate of the NT-AL001-E Link Adapter is 64 Kbps. Do not use 115.2 Kbps when a Link Adapter is connected.
21
System Configurations
Section 1-5
Protocol Macros, Serial Gateway, No-protocol, or Modbus-RTU Slave
PLC:
External device
1:1
Port:
RS-232C
Connection configuration
Connection of a Serial Communications Board to a device with an
RS-232C or RS-422A/485 port.
Note 1.
RS-232C
Required devices
Connected serial port/Remarks
CS1W-SCB21-
V1
Port 1 or 2
RS-232C interface
Note 3.
NT-AL001-E
Note 2.
RS-232C RS-422A/485
Resistance
ON
Note 3.
NT-AL001-E
Note 2.
NT-AL001-E
Resistance ON
5-V power
RS-232C interface
RS-232C RS-422A/485
Resistance
ON
Resistance
ON
RS-422A/485 interface
Connection of a Serial Communications Unit to a device with an
RS-232C or RS-422A/485 port.
Note 1.
RS-232C
RS-232C interface
Note 3.
Note 2.
NT-AL001-E
RS-232C
RS-422A/485
Resistance ON
NT-AL001-E
Resistance ON
5-V power
RS-232C interface
Note 3.
Note 2.
NT-AL001-E
RS-232C RS-422A/485
Resistance ON
Resistance
ON
RS-422A/485 interface
CS1W-SCB41-
V1
Port 1
NT-AL001-E
Converting Link
Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
CS1W-SCU21-
V1
Port 1 or 2
CJ1W-SCU21-
V1
Port 1 or 2
CJ1W-SCU41-
V1
Port 2
RS-422A/
485
RS-232C
NT-AL001-E
Converting Link
Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
22
System Configurations
Section 1-5
PLC:
External device
1:1
Port: RS-
422A/ 485
Connection configuration
Connection of a Serial Communications Board to a device with an RS-
232C or RS-422A/485 port
Note 2.
Required devices
CS1W-SCB41-
V1
RS-422A/485
Resistance ON
Note 2.
Note 3.
RS-422A/485 interface
Resistance ON
Resistance ON
NT-AL001-E
RS-232C
RS-232C interface
RS-422A/
485
Resistance ON
5-V power
Connection of a Serial Communications Unit to a device with an RS-
232C or RS-422A/485 port
Note 2.
NT-AL001-E
Converting Link
Adapter
5-V power supply
CJ1W-SCU41-
V1
Connected serial port/Remarks
Port 2
Convert between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
Port 1
RS-422A/
485
RS-232C
RS-422A/485
Resistance ON
Note 2.
Note 3.
RS-422A/485 interface
Resistance ON
Resistance ON
NT-AL001-E
RS-232C
RS-232C interface
RS-422A/
485
Resistance ON
5-V power
NT-AL001-E
Converting Link
Adapter
5-V power supply
Convert between
RS-232C and
RS-422A/485
For NT-AL001-E
Link Adapter
23
System Configurations
PLC:
External device
1:N
Port: RS-
232C
Connection configuration
Connection of a Serial Communications Board to devices with
RS-232C or RS-422A/485 ports
Note 3.
NT-AL001-E
Note 2.
RS-232C
Resistance ON
RS-422A/485
RS-422A/485 interface
Resistance ON
Note 3.
NT-AL001-E
B600-AL001
RS-232C
RS-422A/485
Resistance
ON
RS-422A/485 interface
Note 2.
Note 4.
Resistance ON
Note 3.
NT-AL001-E
RS-232C
Resistance
ON
Note 2.
RS-422A/485
NT-AL001-E
RS-232C interface
RS-232C
RS-232C
Resistance ON
5-V power
RS-232C
Note 3.
Connection of a Serial Communications Unit to devices with
RS-232C or RS-422A/485 ports.
RS-422A/485 interface
Note 3.
NT-AL001-E
Note 2.
RS-232C
Resistance ON
RS-422A/485
Resistance ON
Note 3.
NT-AL001-E
B500-AL001
RS-232C
RS-422A/485
Resistance
ON
RS-422A/485 interface
Note 2.
Note 4.
Resistance ON
Note 3.
NT-AL001-E
RS-232C
Resistance
ON
Note 2.
NT-AL001-E
RS-232C
RS-232C interface
RS-422A/485
RS-232C
Resistance ON
5-V power
RS-232C
Note 3.
Section 1-5
Required devices
Connected serial port/Remarks
CS1W-SCB21-
V1
Port 1 or 2
CS1W-SCB41-
V1
Port 1
NT-AL001-E
Converting Link
Adapter
B500-AL001
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For RS-422A/485 branching
For NT-AL001-E
Link Adapter
CS1W-SCU21-
V1
Port 1 or 2
CJ1W-SCU21-
V1
Port 1 or 2
CJ1W-SCU41-
V1
Port 2
RS-422A/
485
RS-232C
NT-AL001-E
Converting Link
Adapter
B500-AL001
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For RS-422A/485 branching
For NT-AL001-E
Link Adapter
24
System Configurations
Section 1-5
PLC:
External device
1:N
Port: RS-
422A/485
Connection configuration
Connection of a Serial Communications Board to devices with RS-
232C or RS422A/485 ports
RS-422A/485 interface
Required devices
Connected serial port/Remarks
CS1W-SCB41-
V1
Port 2
Resistance ON
RS-422A/485
Note 2.
Resistance ON
Resistance ON
RS-422A/485
B500-AL001
RS-422A/485 interface
NT-AL001-E
Converting Link
Adapter
B500-AL001
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For RS-422A/485 branching
For NT-AL001-E
Link Adapter
Note 2.
Note 4.
Resistance ON
Resistors ON
Note 2.
RS-422A/485
NT-AL001-E
RS-232C
RS-232C interface
RS-232C
Resistance ON
5-V power
RS-232C
Note 3.
Connection of a Serial Communications Board to devices with RS-
232C or RS422A/485 ports
RS-422A/485 interface
Resistance ON
RS-422A/485
Note 2.
Resistance ON
CJ1W-SCU41-
V1
Port 1
RS-422A/
485
RS-232C
NT-AL001-E
Converting Link
Adapter
B500-AL001
Link Adapter
5-V power supply
Converts between
RS-232C and
RS-422A/485
For RS-422A/485 branching
For NT-AL001-E
Link Adapter
RS-422A/485
B500-AL001
RS-422A/485 interface
Resistance ON
Note 2.
Note 4.
Resistance ON
Resistors ON
Note 2.
RS-422A/485
NT-AL001-E
RS-232C
RS-232C interface
RS-232C
Resistance ON
5-V power
RS-232C
Note 3.
Note
1.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
2.
The combined cable length for RS-422A/485 is 500 m including branch lines.
25
Specifications
NT Link Communications
Section 1-6
3.
The maximum cable length is limited to 2 m when an NT-AL001-E Link
Adapter is connected.
4.
Branch lines must be a maximum of 10 m long.
NT Link communications are used to connect an OMRON Programmable
Controller (PLC) and Programmable Terminal (PT). Up to 8 PTs can be connected to one PLC. For details on the system configuration, refer to the user’s manual for the PT.
1-6 Specifications
1-6-1 Serial Communications Boards and Unit
CS Series
Classification
Model number
Serial ports
Protocol
Device name
Port 1
Port 2
Port 1
Port 2
Serial Communications Boards Serial Communications Unit
Inner Board CPU Bus Unit
CS1W-SCB21-V1 CS1W-SCB41-V1 CS1W-SCU21-V1
RS-232C
RS-232C
RS-232C
RS-422A/485
RS-232C
RS-232C
Host Link, protocol macro, NT Link, or loopback test can be selected for each port.
Unit Ver. 1.2 or later also supports Serial Gateway, no-protocol, and 1:1 Host Link modes. (Note: The Serial Gateway can also be executed in protocol macro mode.)
Number of mountable
Boards/Units
Data exchange with the CPU
Unit
CPU Unit
CPU Rack
Unit Ver. 1.3 or later also supports Modbus-RTU slave mode.
One Board per Inner Board slot
None
Expansion Rack
None
None
A total of up to 16 Units, including all other CPU Bus Units. No restrictions on the mounting location.
Ordinary refreshing of software switches and status
Transfer from the
CPU Unit set by the system
Allocated 25 words of the 100 words in the Inner Board CIO Area (constant data exchange with the CPU Unit)
Allocated 25 words of the 25 words in the
CPU Bus Unit CIO Area (constant data exchange with the CPU Unit)
Of the 768 words in the Inner Board DM
Area, each serial port is allocated 10 words (total 20 words).
Data is transferred from the CPU Unit at the following times:
• Startup or restart
• Ladder instruction: STUP(237)
• Port Settings Changing Flag turns ON
(Auxiliary Area)
Of the CPU Bus Unit DM Area, each serial port is allocated 10 words (total 20 words).
Data is transferred from the CPU Unit at the following times:
• Startup or restart
• Ladder instruction: STUP(237)
• Port Settings Changing Flag turns ON
(Auxiliary Area)
Supporting CPU Units
CS1 CPU Units
High-speed: CS1H-CPU67-V1/CPU66-V1/CPU65-V1/CPU64-V1/CPU63-V1
Standard: CS1G-CPU45-V1/CPU44-V1/CPU43-V1/CPU42-V1
CS1-H CPU Units
High-speed: CS1H-CPU67H/CPU66H/CPU65H/CPU64H/CPU63H
Standard: CS1G-CPU45H/CPU44H/CPU43H/CPU42H
Simple Backup Function
Note A CS1-H CPU Unit with Unit Ver. 3.0 or later is required to use the no-protocol mode.
The CPU Unit’s Simple Backup Function can be used to backup the Protocol Macro data in the Serial Communications Board/Unit to the CPU Unit’s Memory Card. The backed-up data can be restored or compared.
(The Simple Backup Function can be used only with a “-V1” model of Serial Communications Board/Unit in combination with a CS1-H CPU Unit.)
26
Specifications
Section 1-6
Device name
Applicable Backplanes
Serial Communications Boards
None
Serial Communications Unit
CPU Backplanes:
CS1W-
BC103/BC083/BC053/BC033/BC023
CS Expansion Backplanes:
CS1W-BI103/BI083/BI053/BI033
290 mA + x
200 g max.
Current consumption (See note.)
280 mA + x
Weight
100 g max.
360 mA + x
110 g max.
Note
The current consumption is for one Serial Communications Board or Unit.
When an NT-AL001-E Link Adapter is connected to the Serial Communications Board or Unit, power is supplied to the Link Adapter from the Board or
Unit. A current consumption of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply.
27
Specifications
Section 1-6
CJ Series
Classification
Model number
Serial ports
Protocol
Device name
Port 1
Port 2
Port 1
Port 2
Serial Communications Unit
CPU Bus Unit
CJ1W-SCU21-V1 CJ1W-SCU41-V1
RS-232C
RS-232C
RS-422A/485
RS-232C
Host Link, protocol macro, NT Link, or loopback test can be selected for each port.
Unit Ver. 1.2 or later also supports Serial Gateway, no-protocol, and 1:1
Host Link modes. (Note: The Serial Gateway can also be executed in protocol macro mode.)
Unit Ver. 1.3 or later also supports Modbus-RTU slave mode.
None
A total of up to 16 Units, including all other CPU Bus Units. No restrictions on the mounting location.
Allocated 25 words of the 25 words in the CPU Bus Unit CIO Area (constant data exchange with the CPU Unit)
Number of mountable Units
Data exchange with the CPU Unit
CPU Unit
CPU Rack
Expansion Rack
Ordinary refreshing of software switches and status
Transfer from the CPU
Unit set by the system
Supporting CPU Units
Simple Backup Function
Current consumption (See note.)
Weight
Of the CPU Bus Unit DM Area, each serial port is allocated 10 words
(total 20 words).
Data is transferred from the CPU Unit at the following times:
• Startup or restart
• Ladder instruction: STUP(237)
• Port Settings Changing Flag turns ON (Auxiliary Area)
CJ1 CPU Units
CJ1G-CPU45/CPU44
CS1-H CPU Units
High-speed: CJ1H-CPU66H/CPU65H
Standard: CJ1G-CPU45H/CPU44H/CPU43H/CPU42H
CJ1M CPU Units
CJ1M-CPU23/CPU22/CPU21/CPU13/CPU12/CPU11
Note A CS1-H CPU Unit with Unit Ver. 3.0 or later is required to use the no-protocol mode.
The CPU Unit’s Simple Backup Function can be used to backup the Protocol Macro data in the Serial Communications Board/Unit to the CPU
Unit’s Memory Card. The backed-up data can be restored or compared.
(The Simple Backup Function can be used only with a CJ1W-SCU21/41
Serial Communications Unit in combination with a CJ1-H CPU Unit.)
280 mA + x
110 g max.
380 mA + x
110 g max.
Note
The current consumption is for one Serial Communications Unit. When an NT-
AL001-E Link Adapter is connected to the Serial Communications Board or
Unit, power is supplied to the Link Adapter from the Board or Unit. A current consumption of 150 mA must be added for each Link Adapter that is connected. In the above specifications, “x” indicates that 150 mA must be added for each port to which an NT-AL001-E Link Adapter is connected to provide the required 5-V power supply.
1-6-2 General Specifications
The general specifications of the CS-series Serial Communications Boards and Serial Communications Unit conform to the general specifications of the
CS-series CPU Unit.
The general specifications of the CJ-series Serial Communications Unit conform to the general specifications of the CJ-series CPU Unit.
28
Specifications
Section 1-6
1-6-3 Protocol Specifications
Host Link Specifications
Item Description
Communications mode
Half-duplex (Full-duplex for slave-initiated communications)
Synchronous mode
Start-stop synchronization (asynchronous mode)
Baud rate (see note 1)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps
Communications distance (see note 1)
Default setting: 9,600 bps
RS-232C port: 15 m max. (see note 2)
Connection configuration
RS-442A/485 port: 500 m max. (The total combined cable length is 500 m max. T-branch lines must be a maximum of 10 m long.)
RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using an Converting Link Adapters.)
RS-422A/485 port: 1:N (N = 32 Units max.)
Number of connected
Units
Frame structure
32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection)
Error check codes
Command flow and support
C-mode commands
FINS commands
Header: @, address: (host link unit number) 0 to 31 (BCD), data: header code + text, error check code: FCS, terminator: *+CR
Header: @, address: (host link unit number) 0 to 31 (BCD), data: header code (always “FA”) + FINS header + FINS command + text, error check code: FCS, terminator: *+CR
Vertical parity: Even, odd. or none
FCS (horizontal parity converted to ASCII)
Command flow
Host computer to PLC
PLC to host computer
Commands Contents
C-mode commands 1:1 or 1:N communications with directly connected
PLCs (The specified frame format must be prepared on the host computer and then sent.)
FINS commands (in
Host Link protocol)
FINS commands (in
Host Link protocol)
1:1 or 1:N communications with directly connected
PLCs.
Communications using SEND(090), RECV(098), and CMND(490) from CPU Unit.
The host computer must interpret the commands and return a response in the correct format.
Connection between the host computer and PLC must be 1:1.
Note
1.
Confirm the baud rates and communications distance supported by connected devices.
2.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
29
Specifications
Section 1-6
Protocol Macro Function Specifications
Item
Number of protocols 20 max.
Number of sequences 1,000 max.
Per protocol Number of sequences
Number of messages
Number of reception matrixes
Sequence execution condition
Can be created and registered with the Protocol Support Tool
(CX-Protocol).
60 max.
300 max.
100 max.
Description
Communications mode
Synchronous mode
Baud rate (see note 1)
Using the CPU Unit’s PMCR(260) instruction (specifying the sequence number)
Half-duplex or full-duplex
Start-stop synchronization (asynchronous mode)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200/38,400 bps
Default setting: 9,600 bps
Communications distance (see note 1)
Note A baud rate of 57,600 bps can be selected when using Unit Ver.
1.2 or later (115,200 bps is not possible).
RS-232C port: 15 m max.
RS-442A/485 port: 500 m max. (The total combined cable length is
500 m max. T-branch lines must be a maximum of 10 m long.)
Connection configuration
Number of connected Units
Maximum number of data exchange words between PLC and protocol macro function
Operand setting
Link word setting
Direct setting
RS-232C port: 1:1 (1:N (N = 32 Units max.) is possible using a Converting Link Adapter.)
RS-422A/485 port: 1:N (N = 32 Units max.)
32 Units max. (unit numbers 0 to 31; unit number 0 is set for 1:1 connection)
250 words
500 words
500 words
Including the word that specifies the number of words (1 word)
O1, O2, I1, and I2: 500 words total
Maximum number of words per data attribute
30
Specifications
Section 1-6
Sequence contents
(step common parameters)
Item Description
Number of steps per sequence
Transmission control parameters
Response notification method (operand)
16 max.
X-on/X-off flow, RS/CS flow, delimiter control, or contention control, and modem control can be selected.
Scan notification or interrupt notification (i.e., writing the receive data in the I/O memory area specified in the 4th operand of the PMCR(260) instruction) can be selected.
Scan notification:
Writes the receive data to I/O memory during CPU Unit scanning.
Interrupt notification:
Writes the receive data to I/O memory as soon as it is received, and at the same time specifies the execution of the interrupt program for the
CPU Unit.
Note
The interrupt notification method can be executed only by a
Serial Communications Board. It cannot be used for a Serial
Communications Unit.
Scan method (fixed) Board and Unit
Interrupt notification Board only (see note 2)
Interrupt notification for reception case number
Board only (see note 2)
Monitoring time during send/receive processing
Receive wait, receive completion, or send completion can be monitored.
Setting range: 0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 minutes
Link word setting
Area in which data is exchanged between the CPU Unit and the Serial
Communications Board or Unit during Communications Board or Unit refreshing. Two areas are possible for each device: An area for storing receive data and an area for storing send data.
Note Unit Ver. 1.2 or later supports continuous I/O refreshing in addition to the previous on-request I/O refreshing.
31
Specifications
Step contents
Section 1-6
Item
Commands
Repeat counter
Retry count
Send wait time
Description
Send only (SEND), receive only (RECV), send and receive
(SEND&RECV), wait (WAIT), reception buffer clear (FLUSH), ER-ON
(OPEN), or ER-OFF (CLOSE)
1 to 255 times
0 to 9
(Only when the command is SEND&RECV)
0.01 to 0.99 s, 0.1 to 9.9 s, 1 to 99 s, or 1 to 99 minutes
(Only when the command is SEND or SEND&RECV)
With or without response write
(operand)
Next processing
When receive processing is completed (when the receive data is stored in the area specified in the 4th operand of the PMCR(260) instruction), whether or not to store the received messages can be selected.
When a step has ended normally, End (sequence completed), Next (proceed to the next step No.), Goto (go to the specified step No.), or Abort
(interrupt the step and terminate that sequence) can be selected.
Error processing
When a step has ended abnormally, End, Next, Goto, or Abort can be selected.
Send message
Data sent to the specified address when the command is SEND or
SEND&RECV.
Consists of a header (*1), address (*2), length, data (*2), error check code (*3), and terminator
(*1).
For an explanation of *1, *2, and *3, see the next page.
Receive message
Data sent from the specified address when the command is RECV or
SEND&RECV.
Reception matrix
When the command is RECV or
SEND&RECV, sets the expected receive messages
(15 max.), and switches to the next processing according to the message received.
Specifies the receive messages and the next processing for each of cases No. 00 to No. 15. Of the maximum 16 cases, one case must be set as
“Other” in the receive messages (in addition to the set receive messages).
Note
1.
The baud rate and the communications distance sometimes depend on the remote device.
2.
A macro syntax error will occur if the interrupt notification method is executed for a Serial Communications Unit.
32
Specifications
Section 1-6
Message unit contents
Item
*1:
Header and terminator data attributes
*2:
Data attributes of addresses and data in send/receive messages
Constant
Constant
Variable
Description
ASCII data, hexadecimal data, or control code
ASCII data, hexadecimal data, or control code (with an address, no control code is possible)
No conversion, conversion to ASCII data, or conversion to hexadecimal data
(the read/write direction can be specified)
Designation method
(X, Y)
X: Effective address (where read from, or where written to)
Y: Data size (1 to 1,000)
X
Note The data size is the number of bytes on the transmission path.
Word designation
Word read (I/O memory to send data)
Word write
(receive data to
I/O memory)
Specify using the 3rd operand of the
PMCR(260) instruction.
Specify using a link word.
I/O memory direct designation
Specify using the 4th operand of the
PMCR(260) instruction.
Set leading address + n
(The linear expression aN
+ b, including repeat counter
N, is also possible for n.)
Wild card *
Specify using a link word.
I/O memory direct designation
Any data or address can be received (only in receive messages)
Repeat counter N
33
Specifications
Section 1-6
Message unit contents
Trace function
Item
*2:
Data attributes of addresses and data in send/receive messages
Variables
*3:
Error check codes
Maximum length of send/receive messages
Maximum number of data attributes registered in one message
Maximum number of write data attributes registered in one message
Description
Y Linear expression including repeat counter
Wild card aN + b a: 0 to 1000; b: 1 to 1000
N: Repeat counter value
Word designation
*
Word read (I/O memory to send data)
Can be received regardless of the length (only in receive messages)
Specify using the 3rd operand of the
PMCR(260) instruction.
Specify using a link word.
Set leading address + n
(The linear expression aN
+ b, including repeat counter
N, is also possible for n.)
I/O memory direct designation
LRC, LRC2, CRC-CCITT, CRC-16, SUM, SUM1, and SUM2 can be calculated.
1,000 bytes. (A maximum length between 200 and 1,000 bytes can be set in the Setup Area.)
96 attributes (see note 1)
30 attributes (see note 2)
A total of up to 1,700 bytes (characters) of time-series data can be traced in send and receive messages.
Changes to the step No. and control signals such as RS and CS can also be traced.
Note
1.
The CX-Protocol can be used to register up to 96 attributes per message.
2.
A macro syntax error will occur when the protocol macro is executed if more than 31 write attributes are registered in one message.
Serial Gateway Specifications
Item Description
Conversion source FINS commands (received through network (including Host
Link FINS) or CPU bus)
Conversion functions • The received FINS command sent to the Board/Unit’s serial port is converted according to the FINS command code as follows:
2803 hex: FIN header removed and converted to Compo-
Way/F command.
2804 hex: FIN header removed and converted to Modbus-
RTU command.
2805 hex: FIN header removed and converted to Modbus-
ASCII command.
The converted command is sent to the serial port.
• When the received FINS command is sent to the Board or
Unit (user-specified FINS command code), the FINS command is enclosed in a Host Link header and terminator.
34
Specifications
Section 1-6
Item
Converted format
Description
• CompoWay/F commands
• Modbus-RTU commands
• Modbus-ASCII commands
• Host Link FINS commands
Serial Gateway mode or protocol macro mode Enabled serial communications mode
Queuing functions
Protocol macro execution processing
Response timeout monitoring
Send start timeout monitoring
Send delay
Up to five FINS commands can be converted and then queued for processing.
When a FINS command is received during protocol macro execution, the Serial Gateway is executed using an interrupt between steps in the communications sequence. If the next step is a RECEIVE command, the Serial Gateway will not be executed until the next step. For other conditions, the interrupt is executed immediately.
Note The reception buffer is cleared during Serial Gateway execution.
Note The Serial Gateway can be prohibited in protocol macro mode by turning ON the Serial Gateway Prohibit Switch in the CIO Area.
The time is monitored from when the message is converted into the specified protocol using the Serial Gateway until the response is received (in Serial Gateway mode or protocol macro mode).
Default: 5 s (setting range: 0.1 to 25.5 s)
Note When a timeout occurs, the FINS end code (0205 hex:
Response timeout) is returned to the source of the FINS command and a response is received after a timeout occurs.
The time is monitored from when the FINS command is received until it is converted into the specified protocol and starts to be sent (in protocol macro mode only).
Default: 5 s (setting range: 0.1 to 25.5 s)
Note When a timeout occurs, the FINS end code (0204 hex:
Remote node busy) is returned to the source of the
FINS command. The send processing will not be executed and the received FINS command will be discarded.
The time can be set from when the message is converted into another protocol using Serial Gateway conversion until the data is actually sent. (Serial Gateway or protocol macro mode)
Default: 0 s (setting range: 0.01 to 300.00 s)
35
Specifications
No-protocol Specifications
Section 1-6
Item
Communications mode
Baud rate
Full-duplex
Description
Messages (communications frame structure)
RS-232C port and RS-422A/485 ports:
1,200/2,400/4,800/9,600/19,200/38,400/57,600 bps
Default setting: 9,600 bps
Set either of the following types in the Setup Area in the allocation DM Area.
1. Data only (without start code and end code)
2. Start code + data
3. Data + end code
4. Start code + data + end code
5. Data + CR + LF
6. Start code + data +CR + LF
Set in allocated DM Area
(The start code can be included by setting it to between 00 and FF hex, and the end code can be included by setting it to between 00 and FF hex. To exclude the end code, set the number of receive data bytes.)
Start code None or 00 to FF hex
End code
Number of receive data bytes during reception
None, 00 to FF hex, or CR + LF
Set the number of receive data bytes between 1 and 256 bytes (according to the DM Area settings) when frame structure 1 or 2 above is used.
Sending messages • Serial Communications Board: TXD(236) instruction
• Serial Communications Unit: TXDU(256) instruction
Receiving messages • Serial Communications Board: RXD(235) instruction
• Serial Communications Unit: RXDU(255) instruction
Maximum message length
Data conversion
Communications protocol
Sending and receiving: Up to 259 bytes including the start code and end code (up to 256 bytes excluding start/end codes)
No conversion
None
Message delay time When the TXD(236) or TXDU(256) instruction is executed, after the send delay time, the data is sent from the port.
0 to 300 s (0 to 300,000 ms)
(Can be set in 10-ms units depending on the DM Area settings)
Receive counter
Reception buffer clear timing
The number of data bytes (0 to 256) received at the port can be counted.
The reception buffer is cleared immediately after executing the
RXD(235)/RXDU(255) instruction
36
Specifications
Section 1-6
Modbus-RTU Specifications
Item
Mode
Baud rate
Data length
Parity
Stop bits
Description
Modbus-RTU slave mode (See note.)
1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps
Default: 19,200 bps
8 bits
Odd, even, or none
Default: Even
Odd or even parity:1 bit
No parity: 2 bits
1 to 247 (broadcasting: 0) Address setting range
Frame format Slave address: 1 byte
Function code: 1 byte
Data: 0 to 252 bytes
CRC code: 2 bytes
Note
Modbus-ASCII mode is not supported.
Supported Commands
Function code
(hexadecimal)
01
02
03
04
05
06
Function
Reads multiple bits from the CIO, Work,
Holding, or Auxiliary Area of I/O memory.
Reads multiple bits from the CIO Area of
I/O memory.
Reads multiple words from the DM or EM
Area of I/O memory.
Reads multiple words from the CIO,
Work, Holding, or Auxiliary Area of I/O memory.
Writes a bit in I/O memory.
08
0F
10
Writes a word in the DM or EM Area of
I/O memory.
Executes an echoback test.
Writes multiple bits in I/O memory.
Writes multiple words in the DM or EM
Area of I/O memory.
Modbus name
Read Coils
Read Discrete Inputs
Read Holding Registers
Read Input Registers
Write Single Coil
Write Single Register
Diagnostic
Write Multiple Coils
Write Multiple Registers
37
Comparison to Previous Products
Section 1-7
1-7 Comparison to Previous Products
The following tables show a comparison between the CS/CJ-series Serial
Communications Boards and Unit and the C200HX/HG/HE Communications
Boards and Host Link Units.
Model
Communications ports
Item
Boards
Units
Boards
Units
Number mountable per PLC
Boards
Units
C200HX/HG/HE
C200HW-
COM02/COM03/COM04-
E/COM05-E/COM06-E
Communications Boards
C200H-LK101-PV1/LK201-
V1 Host Link Unit
CS
CS1W-SCB21-V1/SCB41-
V1
Serial Communications
Board
CS1W-SCU21-V1
Serial Communications Unit
None
CJ
CJ1W-SCU21-V1
CJ1W-SCU41-V1
Serial Communications Unit
NA 2 RS-232C ports or
1 RS-232C and 1
RS422A/485 port or
1 CPU bus I/F and 1 RS-
232C port or
1 RS-232C port or
1 RS-422A/485 port
1 RS-232C port or
1 RS-422A port or
1 optical fiber port
1 Board
2 Units (CPU Rack or
Expansion I/O Rack, but not two slots next to CPU Unit)
Up to 4 ports maximum, 6 ports including those on
CPU Unit.
2 RS-232C ports or
1 RS-232C and 1
RS422A/485 port
2 RS-232C ports
1 Board
16 Units (CPU Rack or CS
Expansion Rack, but total of all CPU Bus Units must be
16 or less)
Up to 32 ports maximum, 34 ports including those on CPU
Unit.
CJ1W-SCU21-V1
2 RS-232C ports
CJ1W-SCU41-V1
1 RS-232C and 1
RS422A/485 port
NA
16 Units (CPU Rack or CJ
Expansion Rack, but total of all CPU Bus Units must be
16 or less)
Up to 32 ports maximum, 34 ports including those on CPU
Unit.
38
Comparison to Previous Products
Section 1-7
Item
Serial communications modes
Boards Host Link communications
C200HX/HG/HE
Supported. (See note 1.) Supported. (1:1 Host Link communications can be selected when using Unit Ver. 1.2 or later, which enables reuse of host programs created using the C200H, C1000H, or
C2000H Series.)
A compatible device selection function has also been added. (See note 1.) This enables Host Link functionality that is fully compatible with C-series Host Links and
CVM1/CV-series Host Links.
Supported.
CS CJ
Supported (unified with 1:N NT Links).
Protocol macros
NT Link communications
No-protocol communications
1:1 Links
Supported (except
COM02/COM03)
Supported.
Supported.
Supported.
Loopback tests
Serial Gateway
Not supported.
Not supported.
Modbus-
RTU slave
Not supported.
Units Host Link communications
Supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2 or later: Supported.
Not supported (supported by Controller Link Units or PLC
Link Units).
Supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2 or later: Supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2: Not supported.
Unit Ver. 1.3 or later: Supported.
Supported. (1:1 Host Link communications can be selected when using Unit Ver. 1.2 or later, which enables reuse of host programs created using the C200H, C1000H, or
C2000H Series.)
A compatible device selection function has also been added. (See note 1.) This enables Host Link functionality that is fully compatible with C-series Host Links and
CVM1/CV-series Host Links.
Supported.
Supported (unified with 1:N NT Links).
Protocol macros
NT Link communications
No-protocol communications
1:1 Links
Not supported.
Not supported.
Not supported.
Not supported.
Loopback tests
Serial Gateway
Not supported.
Not supported.
Modbus-
RTU slave
Not supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2 or later: Supported.
Not supported (supported by Controller Link Units or PLC
Link Units).
Supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2 or later: Supported.
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2: Not supported.
Unit Ver. 1.3 or later: Supported.
39
Comparison to Previous Products
Section 1-7
Baud rate
Host Link communications
Item
Host Link communications
Protocol macros
NT Link
(1:N mode)
No-protocol communications
Serial Gateway
Supported commands
Cmode
(Host
Link) commands
FINS commands
Slave-initiated communications
Modbus-
RTU slave
C200HX/HG/HE
19,200 bps max.
19,200 bps max.
Standard NT Link
19,200 bps max.
Not supported.
Supported.
Not supported.
Boards: Data can be sent with TXD(236) instruction.
Units: Not supported.
Not supported.
Note
CS
115,200 bps max.
57,600 bps max.
115,200 bps max.
Supported.
Supported.
CJ
38,400 bps max. (57,600 bps max. for Unit Ver. 1.2 or later)
Standard NT Link, high-speed NT Link (See note 2.)
Boards and Units: FINS commands can be sent using
SEND(090), RECV(098), and CMND(490).
1.
For pre-Ver. 1.2 Units, the number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Host Link Units and CS/CJ-series Serial Communications
Boards or Serial Communications Units. A host computer program previously used for C-series Host Link Units may not function correctly if it is used in CS/CJ-series PLCs. When using Serial Communications
Boards/Units with Unit Ver. 1.2 or later, these programs can be reused by setting the Host Link compatible device mode to mode C (C500/120) or mode D (D200H). (Alternatively, check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS/CJ-series Communications Commands Refer-
ence Manual (W342) for details.)
2.
For CS-series PLCs, a high-speed NT Link is available only with Serial
Communications Boards/Units manufactured on or after December 20,
1999. With earlier models, only the standard NT Link is available.
Lot No: 20Z9
Pre-Ver. 1.2: Not supported.
Unit Ver. 1.2: Not supported.
Unit Ver. 1.3 or later: 115,200 bps max.
Manufactured on December 20th, 1999
The year is indicated with the last digit. In this case, "9" indicates "1999."
Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is "December."
Day of manufacture. In this example, the day is "20."
NT31/631(C)-V2 are the only PTs for which high-speed NT link is supported.
The following tables shows the improvements made in the protocol macro function.
40
Comparison to Previous Products
Section 1-7
Protocol Macro Comparison
Transmission mode
Commands
Item C200HX/HG/HE
Half-duplex
Send only: SEND, receive only:
RECV, or send and receive:
SEND and RECEIVE
CS/CJ
Half or full-duplex
Send only: SEND, receive only:
RECV, send and receive: SEND and RECEIVE, wait: WAIT, clear reception buffer: FLUSH,
ER-ON: OPEN, and ER-OFF:
CLOSE
WAIT: Progressing to next process controlled by signal from CPU Unit.
FLUSH: Clears contents of reception buffer.
OPEN: Used for modem control.
Keeps ER signal ON even after end of sequence.
CLOSE: Used for modem control. Turns OFF ER signal.
2.5 Kbytes
2 Kbytes
Reception buffer (per port)
Reception buffer flow control at Board/Unit (RS/CS or Xon/Xoff)
Send/receive message length
Start (CTS signal OFF to request canceling send from remote device)
Clear (CTS signal ON to request restarting send from remote device)
Bytes per send
Bytes per receive
For RS/CS flow,
Xon/Xoff flow, or delimiter control
256 bytes
200 bytes
At step transition
256 bytes max.
200 bytes max.
0.5 Kbytes
1,000 bytes max.
Default: 200 bytes. Setting range: 200 to 1,000 bytes.
Reception data is removed from the reception buffer in increments of the size set here.
Reception message length when using wildcard (*) for data length
Send/ receive data storage locations and data capacity
Operand specification
Link word specification
Direct specification (variable)
For RS/CS flow, Xon/Xoff flow, or delimiter control
Other
Other 256 bytes max.
200 bytes max.
256 bytes max.
As set above.
Default: 200 bytes
Setting range: 200 to 1,000 bytes.
Maximum send data size 127 words max. (not including word specifying the number of send words)
Maximum receive data size
127 words max. (not including word specifying the number of receive words)
Area 1 IN
OUT
128 words max. total
Area 2 data size
IN
OUT
Max. send or receive
250 words max. (including word specifying the number of send words)
250 words max. (including word specifying the number of receive words)
500 words max. total
(Unit Ver. 1.2 or later supports a continuous I/O refreshing
(selected in DM Area settings) in addition to the on-request I/O refreshing available in earlier models).)
128 words max. (no conversion) 500 words max. (no conversion)
41
Comparison to Previous Products
Section 1-7
Reception buffer clearing timing
Reception buffer reception processing records
Transmission control signal operations
Item
Character trace reception
Half-duplex
Full-duplex
Half-duplex
Full-duplex
Half-duplex
Full-duplex
RTS signal
CTS signal
ER signal
Synchronization with CPU Unit after start of sequence execution
C200HX/HG/HE
Before executing sequences.
Before executing RECV processing.
None
CS/CJ
Before executing sequences.
After executing SEND processing.
Upon FLUSH command execution.
Before executing sequences.
Upon FLUSH command execution.
(Unit Ver. 1.2 or later: Either clear or hold before executing sequences.)
Only during RECV processing.
Except when executing SEND processing.
None During sequence execution
(reception processing not performed except during sequence execution).
Recorded except during SEND processing.
None
RTS/CTS flow control: RTS signal turned ON when reception buffer reaches 200 bytes.
Modem control: RTS signal turned ON when data is sent and turned OFF when send is completed.
RTS/CTS flow control: Data send is on standby when CTS signal turns ON; data can be sent when CTS signal turns
OFF.
Modem control: ON when sequence execution is started,
OFF when completed.
Turns ON only for modem controls.
During sequence execution
(even during SEND processing)
RTS/CTS flow control: RTS signal turned ON when reception buffer reaches approximately 2
Kbytes.
Modem control: RTS signal turned ON when data is sent and turned OFF when send is completed.
RTS/CTS flow control: Data send is on standby when CTS signal turns ON; data can be sent when CTS signal turns
OFF.
Modem control: ON when sequence execution is started,
OFF when completed. Also can be turned ON or OFF as required during modem control by executing OPEN to turn ON the ER signal or by executing
CLOSE to turn OFF the ER signal in sequence steps. The ER signal can also be controlled across multiple steps.
During RTS/CTS flow control and modem control, the ER signal will be controlled according to modem control operations, the RTS signal will turn ON when sending, and the RTS/CTS flow control operations will be used for the RTS and CTS signals for receptions.
None The WAIT command can be used to stop transitions between steps to allow transitions from the CPU Unit.
This is useful, for example, to perform processing in the CPU
Unit after a specific step but before executing the next step.
42
Comparison to Previous Products
Item
Send/receive messages Reception length
Interrupt notification function
Error check codes
Simple Backup Function
C200HX/HG/HE
No check.
No LRC2 or SUM1 checks.
Supported.
None
Section 1-7
CS/CJ
The length of data set in the expected reception message will be fetched from the reception buffer as the message.
LRC2 and SUM1 supported.
Boards: Supported.
The CPU Unit’s Simple Backup
Function can be used to backup the Protocol Macro data in the
Serial Communications
Board/Unit to the CPU Unit’s
Memory Card. The backed-up data can be restored or compared.
(When a CS1-H CPU Unit is being used, this function is supported by the CS1W-SCB21-
V1, CS1W-SCB41-V1, and
CS1W-SCU21-V1. When a
CJ1-H CPU Unit is being used, this function is supported by the
CJ1W-SCU21(-V1) and CJ1W-
SCU41(-V1).)
43
Selecting the Serial Communications Mode
Section 1-8
1-8 Selecting the Serial Communications Mode
Connect Device
• Host computer
• OMRON component
• OMRON component
Communicating using an OMRON protocol
Serial Communications Mode
Host Link
Host computer coagulative precipitation
Command interpretation by PLC
PLC
Command sent to host computer
Reference
(Host computer:PLC
• Communications
= 1:1 or 1:N) Commands Reference
C-mode commands or FINS commands
Manual (W342)
• Section 4 Using Host
Link Communications
(Host computer:PLC
= 1:1) FINS commands
Creating communications frame for a host computer protocol
Standard system protocol
User-created protocol
Protocol macro
Modbus-RTU
Slave
Protocol macro
Protocol macro
Use a standard system protocol.
Modbus-RTU commands sent from host
Use the CX-Protocol to change a standard system protocol.
• Section 5 Using
Protocol Macros
• CX-Protocol Operation
Manual (W344)
Section 9 Using Modbus-
RTU Slave Mode
(Unit Version 1.3 or later)
• Section 5 Using
Protocol Macros
• Appendices B to O
• Section 5 Using
Protocol Macros
• CX-Protocol Operation
Manual (W344)
CompoWay/
F-compatible
Execute using PMCR instruction.
Execute using CMND instruction.
Through network
Serial Gateway
Serial Gateway
• Modbus-compatible device
(including
OMRON
components)
Modbus-RTUcompatible
Execute using CMND instruction.
Through network
• Modbus-compatible device
(including
OMRON
components)
Modbus-ASCIIcompatible
• OMRON PLC
CS/CJ Series or
CVM1/CV Series
• Reusing host computer programs for existing PLC
Execute using CMND instruction.
Through network
Execute using CMND/SEND/RECV instruction.
Through network
• Reusing host computer programs for 1:1 Host Link created using C200H/C1000H/C2000H PLCs
• Reusing host computer programs for Host Link created using CVM1-series PLCs
• General- purpose external device
• General- purpose external device
Protocol (including no-protocol) used mainly for stop-start synchronous data sending and reception
Protocol macro
Sending/receiving data in a single direction from/to a device such as a bar code reader or printer
User-created protocol using ladder program
No-protocol
Use the CX-Protocol to create a new protocol.
Serial Gateway
Serial Gateway
Serial Gateway
Serial Gateway
Serial Gateway
1:1 Host Link
Used with Host Link compatible device selection function (Select
C mode or D mode)
Host Link compatible device selection function (Select B mode)
• Section 5 Using
Protocol Macros
• CX-Protocol Operation
Manual (W344)
44
Basic Operating Procedure
• Programming
Device (but not a
Programming
Console)
Remote programming and monitoring via a modem
Host Link
Note When a Programming Device is connected to the PLC, the Peripheral Bus can be used by connecting to the ports on the CPU Unit.
This is faster than using Host Link communications.
• OMRON
Programmable
Terminal (PT)
High-speed communications for multiple PTs
(up to eight).
Low-speed communications and only one PT
1:N NT Link
Note The PT must also be set for a 1:N NT Link.
Communications will not be possible if the
PT is set for a 1:1 NT Link.
Host Link
Section 1-9
• Section 4 Using Host
Link Communications
• Communications
Commands Reference
Manual (W342)
• Section 8 Using 1:N
NT Links
• Section 4 Using Host
Link Communications
1-9 Basic Operating Procedure
1-9-1 Overview
1,2,3...
An overview of the basic operating procedure is provided here. Refer to the following pages for details.
1.
Turn OFF the power supply to the PLC.
2.
Set the unit number if a Serial Communications Unit is being used.
Set the unit number using the rotary switch on the front panel of the Unit.
3.
Install the Board or Unit.
4.
Connect the Unit and the external device(s).
5.
Turn ON the power supply to the PLC
6.
Create the I/O tables if a Serial Communications Unit is being used.
Create the I/O tables using a Programming Device, such as a Programming Console.
I/O tables must be created when a Serial Communications Unit (CPU Bus
Unit) is used with a CS/CJ-series PLC. (This aspect of operation is different from using Communications Boards with the C200HX/HG/HE, C200H, or
C200HS.)
7.
Set the Setup Area allocated in the DM Area.
Make settings using a Programming Device, such as a Programming Console, or the CX-Protocol.
The following words are allocated as the Setup Area in the DM Area:
Board:20 words beginning at D32000
Unit: 20 of the 100 words starting from (D30000 + 100
× unit number)
Make the following settings:
• Serial communications mode (Host Link, protocol macro, NT Link, loopback test, Serial Gateway, or no-protocol)
• Baud rate
• Transmission mode for protocol macros (half-duplex or full-duplex), the maximum length of send/receive data, etc.
8.
Make the new settings in the Setup Area valid by performing one of the following.
• Turn the power OFF and then ON again.
45
Basic Operating Procedure
Section 1-9
• Restart the Board by turning ON the Inner Board Restart Bit (A60800) or restart the Unit turning ON one of the CPU Bus Unit Restart Bits
(A50100 to A50115, where the bit number corresponds to the unit number).
• Restart the port on the Serial Communications Board by turning ON one of the Communications Board Port Settings Change Bits (A63601 for port 1 and A63602 for port 2) or restart the port on the Serial Communications Unit by tuning ON one of the Communications Unit Port
Settings Change Bits (A620 to A635: The word will be A620 + unit number and the bit will be bit 01 for port 1 and bit 02 for port 2).
• Execute the STUP(237) instruction. The STUP(237) instruction is executed in the ladder program to change the serial communications mode of a serial port. See Appendix O Changing Port Settings Using
STUP(237).
9.
Execute communications.
Use the software switches or the allocated flags and words allocated in the
CIO Area in the ladder program to control communications.
The following words are allocated in the CIO Area:
Board: 25 words from CIO1900
Unit: 25 words from CIO 1500 + 25
× unit number
1-9-2 Explanation of Procedure
Turning OFF the Power
Setting the Unit Number for Serial
Communications Units
Check that the PLC power has been turned OFF. If the power is ON, turn it
OFF.
When a Serial Communications Unit is used, set the unit number switch at the top of the front panel of the Unit to between 0 and F. The number that is set will determine which words are allocated as the Setup Area in the DM Area and which words are allocated in the CIO Area.
CS-series Units
CJ-series Units
SCU21-V1
RUN
ERC
SD1
RD1
UNIT
No.
3210
FEDC
RDY
ERH
SD2
RD2
Unit number switch
SCU41
RUN ERC SD1 RD1 TER1
RDY ERH SD2 RD2
TERM
OFF
WIRE
2
ON
4
01
23
4567
CDE
UNIT
NO.
Unit number switch
46
Basic Operating Procedure
First word in Setup Area allocated in DM Area: m = D30000 + 100
× unit number
(20 words are used beginning from m,
10 words for each port)
Unit No.
Unit No. 0
Words
D30000 to D30099
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599
First word allocated in the CIO Area: n = CIO 1500 + 25
× unit number
(all words are used beginning with n)
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
CIO 1675 to CIO 1699
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
CIO 1775 to CIO 1799
CIO 1800 to CIO 1824
CIO 1825 to CIO 1849
CIO 1850 to CIO 1874
CIO 1875 to CIO 1899
Section 1-9
With a Serial Communications Board, the following words are always allocated.
Setup Area in the DM Area:
D32000 to D32767
D32000 to D32009 Port 1 Setup Area
D32010 to D32019 Port 2 Setup Area
D32020 to D32767 Reserved for the system
Words allocated in the CIO Area:
CIO 1900 to CIO 1999
CIO 1900 Software switch
CIO 1901 to CIO 1904 Board status
CIO 1905 to CIO 1914 Port 1 status
CIO 1915 to CIO 1924 Port 2 status
CIO 1925 to CIO 1999 Reserved for the system
Installing the Board or
Unit
1,2,3...
Serial Communications Board (CS Series Only)
1.
Press in the lever on the Inner Board installation cover, first on the top and then on the bottom, and remove the cover.
Press in the lever on the top.
Press in the lever on the bottom.
47
Basic Operating Procedure
2.
Install the Serial Communications Board.
Section 1-9
1,2,3...
CS-series Serial Communications Unit
1.
Catch the hook on the top of the back of the Unit on the Backplane, and then rotate the Unit downward to mount it.
Hook
Backplane
2.
Insert the Unit firmly into the Backplane connector.
3.
Tighten the screw at the bottom of the Unit with a Phillips screwdriver to a torque of 0.4 N
•m. For this operation, the Phillips screwdriver must be placed at a slight angle. Therefore, leave sufficient space at the bottom of the Unit.
Duct
CPU Unit
I/O Power
Supply Unit
Remote I/O
Unit
Duct
Phillips screwdriver
At least 20 mm
Backplane
At least 20 mm
48
Basic Operating Procedure
Section 1-9
1,2,3...
CJ-series Serial Communications Unit
1.
Align the connectors properly and then press in on the Unit to connect it.
Connector
PA205R
POWER SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
OPEN
RUN
ERR/ALM
INH
PRPHL
COMM
MCPWR
BUSY
SCU41
RUN ERC SD1
RD1 TER1
RD2
RDY ERH
TERM
OFF
SD2
ON
UNIT
NO.
WIRE
2 4
PORT1
(RS422
/485)
AC100-240V
INPUT
L1
L2/N
PERIPHERAL
PORT2
RUN
OUTPUT
AC240V
DC24V
PORT
2.
Slide the sliders on the top and bottom of the Unit until they lock the Units together.
Slider
Connections
PA205R
POWER
SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
OPEN
RUN
ERR/ALM
INH
PRPHL
COMM
MCPWR
BUSY
SCU41
RUN ERC SD1
RD1 TER1
RD2
RDY ERH
TERM
OFF
SD2
ON
UNIT
NO.
WIRE
2 4
PORT1
(RS422
/485)
Release
Lock
AC100-240V
INPUT
L1
L2/N
PERIPHERAL
PORT2
RUN
OUTPUT
AC240V
DC24V
PORT
Note
If the sliders are not locked properly, the Serial Communications Units may not function correctly.
Connect the external devices using RS-232C or RS-422A cables. For details on the connector pin layout and the connection methods, see Section 3 Instal-
lation and Wiring, and refer to the relevant manuals for the external devices to be connected.
Types of Port for Different Models
The types of port for the different models of Serial Communication Boards and Units are shown in the following table.
PLC Series
CS Series
CJ Series
Type of Unit
Serial Communications Board
Serial Communications Unit
Model
CS1W-
SCB21-V1
CS1W-
SCB41-V1
CS1W-
SCU21-V1
Port 1
RS-232C
RS-232C
RS-232C
Port 2
RS-232C
RS-422A/485
RS-232C
CJ1W-SCU21-
V1
CJ1W-SCU41-
V1
RS-232C RS-232C
RS-422A/485 RS-232C
When an RS-422A/485 port is used, the following setting is required.
49
Basic Operating Procedure
Section 1-9
• TERM: Terminating resistance ON/OFF switch
OFF: Terminating resistance OFF
ON: Terminating resistance ON
• WIRE: 2-wire or 4-wire selector switch
2: 2-wire; 4: 4-wire
OFF
2
ON
4
TERM
WIRE
Connection Example for Host Link Communications
The host computer can be connected to a PLC 1:1, or NT-AL001-E Converting Link Adapters can be used to convert from RS-232C to RS-422A/485 to connect the host computer to PLCs 1:N.
Serial Communications Board
Serial Communications Unit
Turning ON Power
50
NT-AL001-E
Terminating resistance ON, 5-V power supply required
Terminating resistance
ON
Also perform other required processing, such as setting switches on the external device(s).
Connection Example for Protocol Macros, Serial Gateway, No-protocol
Mode, and Modbus-RTU Slave
Serial Communications
Board
RS-232C
RS-422A/485
Terminating resistance ON
General-purpose external device
General-purpose external device
General-purpose external device
Terminating resistance ON
General-purpose external device
Also perform other required processing, such as setting switches on the external device(s).
Connection Example for 1:N NT Links
Refer to the manual for the PT.
Connecting Programming Devices
Connect the Programming Console, CX-Programmer, or CX-Protocol to the
CPU Unit as required.
Turn ON the PLC power supply to the PLC.
Basic Operating Procedure
Section 1-9
Creating I/O Tables for
Serial Communications
Units
I/O tables must be created for Serial Communications Units. Create the I/O table using a Programming Device, such as a Programming Console or CX-
Programmer.
Setting the Setup Area in the DM Area
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32001
D32002
D32003
D32011
D32012
D32013
Set the serial communications mode and the communications specifications for the Board or Unit. Use a Programming Device, such as a Programming
Console or CX-Programmer, or the CX-Protocol to set the Setup Area.
Host Link Communications
The following table shows the default (standard) settings for Host Link communications.
m = D30000 + 100
× unit number m
Unit
(CS/CJ Series)
Port 1 Port 2
m+10 15
Bit
0
Setting Meaning
m+1 m+2 m+3 m+11 m+12 m+13
08 to 11 5
00 to 03 0
15
15
0
0
00 to 07 00
Start bit: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Baud rate: 9,600 bps
Host Link mode
The baud rate setting is disabled when the default settings are used.
Send delay: 0 ms
CTS control: No
Host Link unit number: 0
Board
(CS Series only)
Port 1 Port 2
D32003
D32003
D32013
D32013
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32001 D32011
1:1 Host Link Mode
Example: When using a Serial Communications Board/Unit with Unit Ver. 1.2
or later, host computer programs that were created using the earlier models
C500-LK101, C500-LK201, C500-LK103, or C500-LK203 can be executed using 1:1 Host Link protocol. m = D30000 + 100
× unit number
Unit
(CS/CJ Series)
Port 1 Port 2
m+3 m+3 m+13 m+13
Bit
14
10-08
Setting
1
3 hex
Meaning
1:N/1:1 Host Link setting: 1:1 Host Link
Host Link compatible device mode: C mode
(C500/120)
Protocol Macros
The following table shows the default (standard) settings for protocol macros.
m = D30000 + 100
× unit number m
Unit
(CS/CJ Series)
Port 1 Port 2
m + 10 15
Bit
0
Setting Meaning
m + 1 m + 11
11 to 08
03 to 00
6
0
Start bit: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Baud rate: 9,600 bps
Protocol Macro mode
9,600 bps when the default settings are used.
51
Basic Operating Procedure
Section 1-9
Board
(CS Series only)
Port 1 Port 2
D32008
D32009
D32018
D32019
Board
(CS Series only)
Port 1
D32000
D32001
Port 2
D32010
D32011
D32006 D32016
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32002
D32003
D32007
D32012
D32013
D32017
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32002
D32003
D32007
D32012
D32013
D32017
Unit
(CS/CJ Series)
Port 1 Port 2
m + 8 m + 9 m + 18 m + 19
Bit
15
15 to 00
Setting Meaning
0 Half-duplex
00C8 hex Maximum number of bytes in protocol macro send/receive data: 200 bytes m + 6
NT Link Mode
The following table shows the default (standard) settings for NT link when the maximum PT unit number is 5.
m = D30000 + 100
× unit number
Bit Setting Meaning
Port 1
m m + 1
Unit
(CS/CJ Series)
Port 2
m + 10 m + 11 m + 16
11 to 08
03 to 00
02 to 00
2
0
5
1:N NT Link
The baud rate is set to the standard NT link setting when the default settings are used.
1:N NT Link maximum unit number
(example)
Serial Gateway
Using Serial Gateway Alone
1.
Make the settings in the Setup Area.
m = D30000 + 100
× unit number
Meaning
m
Unit
(CS/CJ Series)
Port 1 Port 2
m+10
Bit Setting
m+2 m+3 m+7 m+12 m+13 m+17
15
11 to 08
15
15
15 to 08
0
9 hex
0
0
00 hex
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2
Baud rate: 9,600 bps
Serial communications mode: Serial Gateway
Send delay: 0 ms
CTS control: No
Response timeout monitoring time: 5 s
2.
Set the local network table in the routing tables as required (using CX-Net).
Using Serial Gateway During Protocol Macro Execution
1.
Make the settings in the Setup Area.
m = D30000 + 100
× unit number m
Unit
(CS/CJ Series)
Port 1 Port 2
m+10
Bit
11 to 08
Setting
6 hex
Meaning
m+2 m+3 m+7 m+12 m+13 m+17
15
15
15 to 08
07 to 00
0
0
00 hex
00 hex
Serial communications mode: Protocol macro
Send delay: 0 ms
CTS control: No
Response timeout monitoring time: 5 s
Serial Gateway send start timeout monitoring time: 5 s
52
Basic Operating Procedure
Section 1-9
Board
(CS Series only)
1900
Board
(CS Series only)
Port 1
1909
Port 2
1919
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32001
D32002
D32003
D32004
D32005
D32011
D32012
D32013
D32014
D32015
2.
Set the allocated Software Switches.
n = 1500 + 25
× unit number
Function Unit
(CS/CJ Series)
Bit
n 12
04
Port 2
Port 1
Serial Gateway Prohibit Switch (protocol macros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
Serial Gateway Prohibit Switch (protocol macros)
0: Serial Gateway not prohibited
1: Serial Gateway prohibited
The enable/disable status for the Serial Gateway is automatically indicated by the following flag.
Bit Meaning Unit
(CS/CJ Series)
Port 1
n+9
Port 2
n+19 08 Serial Gateway Prohibited Flag
1: Serial Gateway prohibited
1: Serial Gateway not prohibited
3.
Set the local network table in the routing tables as required (using CX-Net).
No-protocol Mode
The following example is for the default (standard) communications conditions, with the send delay set to 100 ms, start code included (e.g., @), end code included (CR + LF), and number of receive bytes set to 100 bytes.
Bit Setting Meaning
m
Unit
(CS/CJ Series)
Port 1 Port 2
m+10 15 0 m+1 m+2 m+3 m+4 m+5 m+11 m+12 m+13 m+14 m+15
11 to 08
03 to 00
15
11 to 00
15
15 to 08
12
09 to 08
07 to 00
3 hex
0 hex
1
00 hex
1
40 hex
1
11
64 hex
Start bits: 1 bit
Data length: 7 bits
Parity: Even
Stop bits: 2 bits
Baud rate: 9,600 bps
No-protocol
The baud rate is 9,600 bps when the default settings are used.
Send delay: User-specified
Send delay setting range: 10 decimal (000A hex), Unit: 10 ms
CTS control 1: Yes
Start code: @ (40 hex)
Start code: Yes
End code: CR + LF
Number of receive data bytes: 100 bytes
53
Basic Operating Procedure
Section 1-9
Board
(CS Series only)
Port 1
D32000
Port 2
D32010
D32001
D32006
D32020
D32021
D32011
D32016
D32030
D32031
Modbus-RTU Slave Mode
The following example is for the default (standard) communications conditions, with the Modbus slave address set to 1 and the default allocation areas for Coils, Input Registers, and Holding Registers.
m = D30000 + 100
× unit number m
Unit
(CS/CJ Series)
Port 1 Port 2
m+10 15
Bit
0
Setting Meaning
m+1 m+6 m+20 m+21 m+11 m+16 m+30 m+31
11 to 08
03 to 00
15 to 08
07 to 00
15 to 08
07 to 00
A hex
0 hex
1 hex
0 hex
0 hex
0 hex
Defaults
Parity: Even
Stop bits: 1 bit
Baud rate: 19,200 bps
(Start bits: 1 bit, Data length: 8 bits)
Modbus-RTU slave
Disabled for default communications conditions (baud rate: 19,200 bps)
Modbus slave address: 1
Coils allocation area: CIO Area
Input Registers allocation area: CIO Area
Holding Registers allocation area: DM Area
Validate the New Settings
Make the new settings in the Setup Area valid by performing one of the following.
• Turn the power OFF and then ON again. The Setup Area allocated in the
DM Area will be read when the power is turned ON.
• Restart the Board by turning ON the Inner Board Restart Bit (A60800) or restart the Unit turning ON one of the CPU Bus Unit Restart Bits (A50100 to A50115, where the bit number corresponds to the unit number). (See following table.)
• Restart the port on the Serial Communications Board by turning ON one of the Communications Board Port Settings Change Bits (A63601 for port
1 and A63602 for port 2) or restart the port on the Serial Communications
Unit by tuning ON one of the Communications Unit Port Settings Change
Bits (A620 to A635: The word will be A620 + unit number and the bit will be bit 01 for port 1 and bit 02 for port 2).
54
Basic Operating Procedure
Section 1-9
Inner Board Restart Bit and CPU
Bus Unit Restart Bits
Board A60800
Units A50100 (Unit No. 0)
A50101 (Unit No. 1)
A50102 (Unit No. 2)
A50103 (Unit No. 3)
A50104 (Unit No. 4)
A50105 (Unit No. 5)
A50106 (Unit No. 6)
A50107 (Unit No. 7)
A50108 (Unit No. 8)
A50109 (Unit No. 9)
A50110 (Unit No. A)
A50111 (Unit No. B)
A50112 (Unit No. C)
A50113 (Unit No. D)
A50114 (Unit No. E)
A50115 (Unit No. F)
Executing
Communications
Communications Board/Unit Port Settings
Change Bits
Unit number Port 1 Port 2
Board A63601 A63602
Units Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
A62001 A62002
A62101 A62102
A62201 A62202
A62301 A62302
A62401 A62402
A62501 A62502
A62601 A62602
A62701 A62702
A62801 A62802
A62901 A62902
A63001 A63002
A63101 A63102
A63201 A63202
A63301 A63302
A63401 A63402
A63501 A63502
• Execute the STUP(237) instruction. The Board or Unit Setup Area can be changed while the PLC power supply is ON. The STUP(237) instruction can be used, for example, when a communications sequence for a modem connection is executed in Protocol Macro Mode to switch the operating mode to Host Link Mode when a certain condition is established. This enables monitoring or programming of the CPU Unit to be carried out from a host computer. See Appendix O Changing Port Set-
tings Using STUP(237).
The required data and ladder program are created to perform communications in the serial communications mode that has been set.
Host Link Communications
Sending C-mode and FINS Commands from Host Computers to PLCs
To send C-mode commands or FINS commands, programs must be created on the host computer to send commands to PLCs and to receive responses back from the PLCs. Refer to the CS/CJ-series Communications Commands
Reference Manual (W342) for details.
Programming to send commands and receive responses.
Host computer
Serial Communications Board/Unit
Command
Sending FINS Commands from PLCs to Host Computers
SEND(090), RECV(098), and CMND(490) can be used to execute slave-initiated communications. Also, programming is required at the host computer to
55
Basic Operating Procedure
Section 1-9
received data and return responses. An example is provided below for
SEND(090).
Programming to return responses.
Input condition
Host computer
Serial Communications
Board/Unit
SEND(090),
RECV(098),
CMND(490)
Command
CPU Unit
SEND(090) can be used to send data from the PLC to a host computer. If the input condition turns ON when the Communications Port Enabled Flag is ON,
10 words of data from CIO 0100 to CIO 0109 will be sent to the host computer connected to port 1 on the Serial Communications Unit with network address
0, node address 0, and unit address 10 Hex.
Communications Port
Enabled Flag for Port 0
A20200
@SEND (90)
0100
0000
D00200
First send word: CIO 0100
"0000" used to send to a host computer.
First control data word: D00200
The control data for the above instruction is shown in the following table.
Word
D00200
D00201
D00202
D00203
D00204
Contents
000A
0100
0010
0000
0000
Meaning
Number of send words: 10
Bits 00 to 07: Destination network address 0
Bits 08 to 10: Serial Communications Unit port 1
Bits 00 to 07: Destination unit address 10 Hex
Bits 08 to 15: Destination node address 0
Bits 00 to 04: Number of retries is 0
Bits 08 to 11: Communications port 0
Bit 15: Response required
Response monitoring time: 2 s (default value for 0000)
A program would be required at the host computer to receive the above data and return a response.
Protocol Macros
When a standard system protocol (provided in the Serial Communications
Board, Serial Communications Unit, and CX-Protocol) is executed.
Using Standard System Protocols
Uses standard system protocol No. 600
Board or Unit
Executed with
PMCR(260)
(237)
CPU Unit
External device
Example: K3N Series
Digital Panel Meter
1,2,3...
1.
Setting the Send Data
56
Basic Operating Procedure
Section 1-9
Input condition
Protocol Macro
Executing Flag
191915
Refer to information on the 3rd operand of PMCR(260) in Appendix B
CompoWay/F Master Protocol and set the number of send data words in
S, and set the send data starting in S+1.
2.
Coding PMCR(260)
Example:
The following example shows how to use a Serial Communications Board to read the present value for a K3N-series Digital Panel Meter using the
CompoWay/F Master standard system protocol sequence No. 600:
Send/receive with ASCII conversion and response.
Communications Port
Enabled Flag for Port 7
A20207
C1
C2
S
D
PMCR(260) (260)
#72E1
#0258
D00000
D00010
Communications port 7 and serial port 2
Destination unit address E1: Serial Communications Board
Sequence No. 600
First word of send data
First storage word for receive data
ER
FAL (006) 01
If the input condition turns ON when the Protocol Macro Executing Flag
(CIO 191915 for Port 2) is OFF and the Communications Port Enabled
Flag (A20207: Internal logic port, communications port 7) is ON, communications sequence No. 600 of the standard system protocol in the Serial
Communications Board is called, and data is sent and received via port 2 of the Serial Communications Board.
Send Data
S:D00000
D00001
D00002
D00003
D00004
D00005
D00006
0007
0000
0101
000C
C000
0000
0001
Receive Data
7 words from D00000 to D00006
K3N node No. : 00
CompoWay/F command "0101" (reads the K3N present value)
Number of send bytes
CompoWay/F command send data
(Variable type, read start address, 00, number of elements)
D:D00010
D00011
D00012
D00013
0004
4 words from D00010 to D00013
Response code is stored.
The read data (in this case, the present value of K3N) is stored.
3.
Executing the PMCR(260) Instruction
4.
For details on confirming operation, see Section 12 Tracing and I/O Mem-
ory Monitoring in the CX-Protocol Operation Manual (W344).
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
57
Basic Operating Procedure
Section 1-9
Executing User-created Protocols
CX-Protocol
Use the CX-Protocol to create protocols.
Board or Unit
PMCR(260)
1,2,3...
CPU Unit
External device
Section references in the following procedure refer to the CX-Protocol Opera-
tion Manual (W344).
1.
For details on designing protocols, see Section 4 and Section 5.
a.
Create a communications sequence status transition chart.
b.
From the status transition chart, divide the processing contents into sequence steps.
c.
Determine the communications sequence message contents.
2.
Use the CX-Protocol to create and send a project (protocol data).
See 1.10 for the outline flow.
a.
Creating a new project:
See 5.1 Creating a New Project or Protocol.
b.
Creating a new communications sequence:
See 5.2 Creating a New Sequence or 7.1 Setting a Sequence.
c.
Creating steps:
See 5.2 Creating a New Sequence and 8.1 Setting a Step.
d.
Creating messages:
See 9.1 Setting a Message.
Note After creating messages, steps can also be created by specifying message names.
e.
Transferring the created project to a Board or Unit:
See 11.1 Transferring and Reading Protocol Data between Personal
Computers and Serial Communications Boards.
3.
Create the ladder program.
a.
Setting Send Data
• Specifying Operands
Set the send data in the I/O memory after the S+1 operand of the PM-
CR(260) instruction. Set the number of send data words (including S itself) in S.
• Direct Designations
Set the send data in the I/O memory specified by the read variables in the send message.
• Specifying Link Words
Set the send data in the O1 or O2 area of the Link Word Area.
b.
Coding PMCR(260)
Example for a Serial Communications Board
58
Basic Operating Procedure
Section 1-9
Input condition
Protocol Macro
Executing Flag
191915
Communications Port
Enabled Flag for Port 7
A20207
C1
C2
S
D
PMCR(260)
#72E1
#0064
D00000
D00010
Communications port 7 and serial port 2
Destination unit address E1: Serial Communications Board
Sequence No. 100
First word of send data
First storage word for receive data
ER
FAL (006) 01
If the input condition turns ON when the Protocol Macro Executing Flag
(CIO 191915 for port 2) is OFF and the Communications Port Enabled
Flag (A20207 for internal logic port, communications port 7) is ON, communications sequence No. 100 registered in the Serial Communications
Board is called, and data is sent and received via port 2 of the Serial Communications Board.
The amount of send data depends on the number of words specified in
D00000 (the number of words after D00001 plus 1 for D00000 itself), and is sent from the next word after D00001.
S:D00000
D00001
Number of words
Send data
Number of send words plus 1 for D00000
Number of words
The receive data is stored in consecutive words beginning with D00011, and the number of words actually stored in D00010 (the number of words after D00011 plus 1 for D00010 itself) is stored.
S:D00000
D00011
Number of words
Receive data
Number of send words plus 1 for D00010
Number of words c.
Execute PMCR(260)
4.
For details on the confirming operation, see Section 12 Tracing and I/O
Memory Monitoring.
• Transmission Line Tracing
The data in the send/receive messages flowing over the transmission line (RS-232C or RS-422A/485) and the control codes are traced.
• I/O Memory Monitoring
Monitors send/receive data and the status of the various flags.
1:N NT Links
Refer to the user’s manual for the PT.
Serial Gateway Mode
• Sending FINS commands from the PLC
Send FINS commands using the CMND(490) instruction. For details, refer
to 6-8-5 Sending Commands Using the CMND(490) Instruction.
• Sending FINS commands from the PT
Execute the PT’s SAP (Smart Active Parts) library.
• Sending FINS commands from a Programming Device that uses CX-
Server as the communications driver, such as the CX-Programmer.
59
Basic Operating Procedure
Section 1-9
System Configuration Example
CX-Programmer Ver. 5.0 or later
Serial Communications Board/Unit with unit Ver. 1.2 or later
(Select SCU (Unit 0 to 15) in the UNIT field.)
Set the relay PLC.
(Select in the Change PLC Dialog Box.)
Serial Gateway function port (Select port 1/2 in the
PORT field according to the calculated address.)
PLC name: PLC2
Serial
Gateway
Host Link FINS
Network type: Select [PLC2].
Select the Use SYSWAY with the port option in the Host Link (SYSWAY) settings.
PLC name: PLC1
Target PLC Host Link unit number
Enter the Host Link unit number in the
Host Link Unit Number field for the target
PLC in the Host Link (SYSWAY) settings.
1.
Register the PLC to be connected serially (using Host Link FINS) in the project gateway (e.g., PLC2).
2.
In the Change PLC Dialog Box of the target PLC (e.g., PLC1), select the relay PLC (gateway PLC) in the Network Type pull-down menu (e.g.,
[PLC2] (See note.)) and click the Settings Button to the right of the Network Type pull-down menu.
Note The PLC name enclosed in square brackets (e.g., [PLC2]) indicates the gateway PLC.
Select the PLC to be used as the relay PLC (e.g., [PLC2]) in the
Network Type pull-down menu.
3.
The Network Settings Dialog Box will be displayed. Click the Guide for Se-
rial Gateway Button. The Serial Gateway Guide Dialog Box will be displayed.
4.
The Serial Gateway Guide Dialog Box will be displayed.
Select the unit and the port number under the Calculate Address Area, the serial port number address is automatically calculated in the Calculated
Address Field.
Select the Use SYSWAY with the port option, and enter the actual Host
Link unit number for the target (communications partner) PLC in the Host
Link Unit Number field (see note).
Finally, click the Apply Button.
60
Basic Operating Procedure
Section 1-9
The Serial
Communications port address is automatically calculated.
Select the Unit.
Select the port.
Select this option.
Enter the unit number for the actual Host Link (values are incremented by 1 automatically).
Note
When using the CX-Programmer, enter the actual Host Link unit number. Do not add 1 to the value. The CX-Programmer will automatically add 1 internally.
No-protocol Mode
Use the following procedure when creating ladder programs.
a) Sending to Serial Communications Boards
Execute the TXD(236) instruction to send the program to the external device from the PLC.
Note For the TXD(236) instruction, include a NO condition of the Send
Ready Flag (bit A35605/A35613) in an AND in the input condition.
Execute the RXD(235) instruction to receive the program at the PLC from the external device.
Note For the RXD(235) instruction, include a NO condition of the Reception Completed Flag (bit A35606/A35614) in an AND in the input condition.
b) Sending to Serial Communications Units
Execute the TXDU(256) instruction to send the program to the external device from the PLC.
Note For the TXDU(256) instruction, include a NO condition of the Communications Port Enabled Flag (bits A20200 to A20207) and a NC condition of the TXDU(256) Executing Flag (word n+9/n+19, bit 05) in an AND in the input condition.
Execute the RXDU(255) instruction to receive the program at the PLC from the external device.
Note For the RXDU(255) instruction, include NO conditions of the Reception Completed Flag (word n+9/n+19, bit 06) and the Communications Port Enabled Flags (bits A20200 to A20207) in an AND in the input condition.
61
Basic Operating Procedure
Section 1-9
Modbus-RTU Slave Mode
Modbus-RTU commands are sent from the host computer to the PLC.
Programming to send commands and receive responses.
Host computer
Serial Communications Board/Unit
Command
The host computer must be programmed to send the Modbus-RTU commands and receive responses.
62
SECTION 2
Initial Settings and I/O Memory Allocations
This section describes the components of the Serial Communications Boards and the Serial Communications Units, the settings required for operation, and the memory allocated in the I/O memory of the CPU Unit for controlling and monitoring communications.
2-1 Component Names and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1-1 Serial Communications Boards (CS Series Only) . . . . . . . . . . . . . .
2-1-2 CS-series Serial Communications Unit . . . . . . . . . . . . . . . . . . . . . .
2-1-3 CJ-series Serial Communications Unit . . . . . . . . . . . . . . . . . . . . . . .
2-2-1 Serial Communications Board (CS Series Only) . . . . . . . . . . . . . . .
2-2-2 Serial Communications Units (CS/CJ Series) . . . . . . . . . . . . . . . . .
2-3-3 Related Auxiliary Area Bits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
63
Component Names and Functions
2-1 Component Names and Functions
2-1-1 Serial Communications Boards (CS Series Only)
CS1W-SCB21-V1 CS1W-SCB41-V1
Indicators
Section 2-1
Port 1
RS-232C
Terminating resistance switch
Port 2
RS-232C
2-wire or 4-wire switch
Port 2
RS-422A/485
SCB21-V1 SCB41-V1
Indicators
CPU Unit Indicators
Indicator Color
RDY
Green Lit
Status Meaning
Operating normally, and protocol macro preparations have been completed.
Flashing Operating normally, and protocol macros are being prepared. ()
Not lit An error has occurred in the Serial Communications Board.
COMM1
COMM2
Yellow
Yellow
Lit
Not lit
Lit
Board/Unit error, CPU Unit watchdog timer error,
Board watchdog timer error
Port 1 is being used for sending or receiving.
Port 1 is not being used for sending or receiving.
Port 2 is being used for sending or receiving.
Not lit Port 2 is not being used for sending or receiving.
Note Depending on the interval of flashing, the meaning is as follows:
Protocol data being initialized: 0.3 s
Protocol data being overwritten: 1.0 s
Protocol data error: 1.0 s and CPU Unit ERR/ALM indicator is flashing
A Serial Communications Board is mounted as an Inner Board in the CPU
Unit and thus affect the CPU Unit ERR/ALM indicator.
Indicator Color
ERR/ALM
Red Lit
Status
Flashing
Not lit
Fatal error
Non-fatal error
Normal operation
Meaning
If a fatal error occurs, the CPU
Unit will stop operation in either
RUN or MONITOR mode.
If a non-fatal error occurs, the
CPU Unit will continue operation in either RUN or MONITOR mode.
The CPU Unit is operating normally.
64
Component Names and Functions
RS-232C Ports
Note
Note
Section 2-1
If an error in the Inner Board is the cause of the error indicated on the ERR/
ALM indicator, information on the error will be stored in A424: Inner Board
Error Information. Refer to Inner Board Error Information under 2-3-3 Related
Auxiliary Area Bits.
For actions required when an error occurs, refer to Section 11 Troubleshooting
and Maintenance.
Port 1 and port 2 are RS-232C ports on the CS1W-SCB21-V1. Only port 1 is an RS-232C port on the CS1W-SCB41-V1.
Protocol
Communications method
Synchronization
Baud rate
Connections
Transmission distance
Interface
Host Link
Full-duplex
Protocol macro
Full-duplex or halfduplex
1:N NT Links
Half-duplex
Start-stop synchronization (asynchronous)
1,200/2,400/4,800/
9,600/19,200/
38,400/57,600/
115,200 bps
1,200/2,400/4,800/
9,600/19,200/
38,400 bps
Standard NT link or high-speed NT link
1:1 (1:N is possible using Link Adapters)
15 m max. (see note 2)
Complies with EIA RS-232C
1.
High-speed NT link is only available with Serial Communications Boards/
Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available.
2.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
Connector Pin Layout
2
3
Pin No.
1 (see note 1)
4 (see note 2)
5 (see note 2)
6 (see note 3)
7 (see note 2)
8 (see note 2)
Abbreviation
FG
SD
RD
RTS (RS)
CTS (CS)
5V
DSR (DR)
DTR (ER)
9 SG
Shell (see note 1) FG
Shield
Signal name
Send data
Receive data
Request to send
Clear to send
Power supply
Data set ready
Data terminal ready (see note 4)
Signal ground
Shield
---
Output
Input
Output
Input
---
Input
Output
---
---
I/O
1.
Pin No. 1 and the shell are connected to the ground terminal (GR) of the
Power Supply Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit.
2.
The status of the RTS (RS), CTS (CS), DSR (DR), and DTR (ER) signals can be monitored in the words allocated in the CIO Area. For details, refer
to 2-3 I/O Memory Allocations.
3.
Pin 6 (5 V) is required when the NT-AL001-E Link Adapter is connected.
For details on connection methods, refer to 3-3 Wiring.
65
Component Names and Functions
Section 2-1
RS-422A/485 Port
4.
The DSR signal is used to monitor the signal cable. It can also be used as a CD (carrier detect) signal. (The DSR signal does not affect system operation, and is available for use by the user.)
!Caution Do not connect the 5-V power supply of Pin 6 to any external device other than an NT-AL001-E Link Adapter. Otherwise, the external device and the
Serial Communications Board or Unit may be damaged.
The following cables are provided for connection to NT-AL001-E Link Adapters. We recommend that these cables be used.
NT-AL001-E connecting cables: XW2Z-070T-1 (0.7 m)
XW2Z-200T-1 (2 m)
Applicable Connectors
Plug: XM2A-0901 (manufactured by OMRON) or equivalent
Hood: XM2S-0911-E (manufactured by OMRON) or equivalent
One plug and one hood are provided for each port.
Recommended Cables
UL2426 AWG28
× 5P IFS-RVV-SB (UL-approved, Fujikura Ltd.)
AWG28
× 5P IFVV-SB (not UL-approved, Fujikura Ltd.)
UL2426-SB (MA) 5P
× 28AWG (7/0.127) (UL-approved, Hitachi Cable, Ltd.)
CO-MA-VV-SB 5P
× 28AWG (7/0.127) (not UL-approved, Hitachi Cable, Ltd.)
Cable length: 15 m max.
Port 2 of the CS1W-SCB41-V1 is an RS-422A/485 port.
Protocol
Communications method
Synchronization
Baud rate
Connections
Transmission distance
Interface
Host Link
Full-duplex
Protocol macro
Full-duplex or halfduplex
Start-stop synchronous (asynchronous)
1,200/2,400/4,800/
9,600/19,200/
38,400/57,600/
115,200 bps
1:N (N: 32 Units max.)
1,200/2,400/4,800/
9,600/19,200/
38,400 bps
1:N NT Links
Half-duplex
Standard NT link or high-speed NT link
1:N (N: 8 Units max.)
500 m max. (The total combined cable length is 500 m max. Tbranch lines must be a maximum of 10 m long.)
Complies with EIA RS-485
Note High-speed NT link is only available with Serial Communications Boards/Units manufactured on or after December 20th, 1999. With earlier models, only standard NT link is available.
66
Component Names and Functions
Section 2-1
Note
Terminating Resistance
Switch: TERM
Connector Pin Layout
Pin No.
1 (see note 1)
2 (see note 1)
3
4
5
6 (see note 1)
7
8 (see note 1)
9
RDB
NC
Shell (see note 2) FG
Abbreviation
SDA
SDB
NC
NC
NC
RDA
NC
Signal name
Send data -
Send data +
Not used
Not used
Not used
Receive data -
Not used
Receive data +
Not used
Shield
Output
Output
---
---
---
Input
---
Input
---
---
I/O
1.
When 2-wire connections are used, use Pins 1 and 2, or Pins 6 and 8.
2.
The shell is connected to the ground terminal (GR) of the Power Supply
Unit inside of the Serial Communications Board. Therefore, the cable shield can be grounded by grounding the GR of the Power Supply Unit.
3.
With SDA/B or RDA/B, the signal polarity may be reversed by the remote device. Be sure to check the polarity before wiring.
Applicable Connectors
Plug: XM2A-0901 (OMRON) or equivalent
Hood: XM2S-0911-E (OMRON) or equivalent
One plug and one hood are provided for each port.
Recommended Cables
CO-HC-ESV-3P
× 7/0.2 (manufactured by Hirakawa Hewtech Corp.)
Cable length: 500 m max. (The total combined cable length is 500 m max. Tbranch lines must be a maximum of 10 m long.)
The terminating resistance switch is provided on the CS1W-SCB41-V1 only.
When an RS-422/485 port is used, set the switch to ON if the Serial Commu-
nications Board is on the end of the transmission line. Refer to Section 3
Installation and Wiring for the ON/OFF settings.
Label
TERM
Name
Terminating resistance switch
Settings
ON: Terminating resistance ON
OFF: Terminating resistance OFF
Factory setting
OFF: Terminating resistance OFF
2-Wire or 4-Wire Switch:
WIRE
Note The status of terminating resistance setting can be monitored in the words
allocated in the CIO Area. For details, refer to 2-3 I/O Memory Allocations.
The 2-wire or 4-wire switch is provided on the CS1W-SCB41-V1 only.
When an RS-422/485 port is used, set the switch to “2” when 2-wire connections are used, and set the switch to “4” when 4-wire connections are used.
For details, refer to Section 3 Installation and Wiring.
WIRE
Label Name
2-wire or 4-wire switch
Settings
2: 2-wire
4: 4-wire
Factory setting
2: 2-wire
67
Component Names and Functions
External Dimensions
CS1W-SCB21-V1 CS1W-SCB41-V1 Mounted in the CPU Unit
Section 2-1
SCB21-V1 SCB41-V1
2-1-2 CS-series Serial Communications Unit
CS1W-SCU21-V1
Indicators
Unit number switch
Port 1
RS-232C
Port 2
RS-232C
Indicators
Indicator
RUN
Color
Green
RDY
Green
Lit
Status
Not lit
Lit
Flashing
Not lit
Operating normally
Meaning
Unit hardware error.
Protocol macro preparations have been completed.
Protocol macros are being prepared. (see note
1)
Hardware error in Serial Communications Unit.
68
Component Names and Functions
Section 2-1
UNIT No. Switch: Unit
Number
RS-232C Ports
Note
Indicator
ERH
Color
Red
ERC
SD1
RD1
SD2
RD2
Red
Yellow
Yellow
Yellow
Yellow
Lit
Status
Flashing
Not lit
Lit
Flashing
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Meaning
CPU Unit error, or this Unit has not been registered in the I/O table. Routing tables incorrectly registered in the Unit.
System Setup error (see note 2)
CPU Unit is operating normally and the Setup
Area settings are normal.
Unit hardware error, or loopback test error
Protocol data syntax error or protocol data error (SUM error).
Unit is operating normally.
Port 1 is being used for sending.
Port 1 is not being used for sending.
Port 1 is being used for receiving.
Port 1 is not being used for receiving.
Port 2 is being used for sending.
Port 2 is not being used for sending.
Port 2 is being used for sending.
Port 2 is not being used for sending.
1.
Depending on the interval of flashing, the meaning is as follows:
Protocol data being initialized: 0.3 s
Protocol data initialized, or being overwritten: 1.0 s
Protocol data error: 1.0 s and CPU Unit ERC indicator is flashing
2.
The Setup Area is allocated in the DM Area according to the unit number
setting. For details, refer to 2-3 I/O Memory Allocations.
For the action required when an error occurs, refer to Section 11 Trouble-
shooting and Maintenance.
Set the CPU Bus Unit unit number for the Unit. The CIO Area and DM Area are allocated according to the unit number setting. The words that are allocated are used for the software switches, Status Area, and the System Setup.
Set the unit number between 0 and F. The factory setting is for unit number 0.
The specifications of the RS-232C are the same as those for the RS-232C port on the Serial Communications Board. See RS-232C Ports on page 65.
Dimensions (Unit: mm)
-V1
69
Component Names and Functions
2-1-3 CJ-series Serial Communications Unit
CJ1W-SCU21-V1
CJ1W-SCU41-V1
SCU21
RUN ERC SD1 RD1
RDY ERH SD2 RD2
01
23
4567
CDE
UNIT
NO.
PORT1
Indicators
Unit number switch
SCU41
RUN ERC SD1 RD1 TER1
RDY ERH SD2 RD2
TERM
OFF
WIRE
2
ON
4
01
23
4567
CDE
UNIT
NO.
PORT1
(RS422
/485)
Port 1: RS-232C
Section 2-1
Indicators
Terminating resistance switch
Unit number switch
2-wire/4-wire switch
Port 1: RS-422A/485
PORT2
Port 2: RS-232C
PORT2
Port 2: RS-232C
Indicators
Indicator
RUN
Color
Green
RDY
ERH
ERC
SD1
RD1
TER1
(see note
3)
SD2
RD2
Green
Red
Red
Yellow
Yellow
Yellow
Yellow
Yellow
Lit
Status
Not lit
Lit
Flashing
Not lit
Lit
Flashing
Not lit
Lit
Flashing
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Lit
Not lit
Operating normally
Meaning
Unit hardware error.
Protocol macro preparations have been completed.
Protocol macros are being prepared (see note
1).
Hardware error in Serial Communications Unit.
CPU Unit error, or this Unit has not been registered in the I/O table. Routing tables incorrectly registered in the Unit.
System Setup error (see note 1)
CPU Unit is operating normally and the Setup
Area settings are normal.
Unit hardware error
Protocol data syntax error or protocol data error (SUM error).
Unit is operating normally.
Port 1 is being used for sending.
Port 1 is not being used for sending.
Port 1 is being used for receiving.
Port 1 is not being used for receiving.
Terminating resistance is connected internally for port 1.
Terminating resistance is not connected internally for port 1.
Port 2 is being used for sending.
Port 2 is not being used for sending.
Port 2 is being used for receiving.
Port 2 is not being used for receiving.
70
Component Names and Functions
Note
Unit Number Switch
RS-422A/485 Port: Port 1
RS-232C Port: Port 2
Dimensions (Unit: mm)
Section 2-1
1.
Depending on the interval of flashing, the meaning is as follows:
Protocol data being initialized: 0.3 s
Protocol data initialized, or being overwritten: 1.0 s
Protocol data error: 1.0 s and CPU Unit ERC indicator is flashing
2.
The Setup Area is allocated in the DM Area according to the unit number
setting. For details, refer to 2-3 I/O Memory Allocations.
3.
Only the CJ1W-SCU41-V1 is equipped with a TER1 indicator.
For the action required when an error occurs, refer to Section 11 Trouble-
shooting and Maintenance.
Set the CPU Bus Unit unit number for the Unit. The CIO Area and DM Area are allocated according to the unit number setting. The words that are allocated are used for the software switches, Status Area, and the System Setup.
Set the unit number between 0 and F. The factory setting is for unit number 0.
The specifications of the RS-422A/485 are the same as those for the -RS-
422A/485 port on the Serial Communications Board. See RS-422A/485 Port on page 66.
The specifications of the RS-232C are the same as those for the RS-232C port on the Serial Communications Board. See RS-232C Ports on page 65.
CJ1W-SCU21-V1
31 65
SCU21
RUN ERC SD1 RD1
RDY ERH SD2 RD2
01
23
4567
CDE
UNIT
NO.
PORT1
PORT2
71
Component Names and Functions
CJ1W-SCU41-V1
31
SCU41
RUN ERC SD1 RD1 TER1
RDY ERH SD2 RD2
TERM
OFF
WIRE
2
ON
4
01
23
4567
CDE
UNIT
NO.
PORT1
(RS422
/485)
PORT2
65
Section 2-1
72
Data Exchange with the CPU Unit
Section 2-2
2-2 Data Exchange with the CPU Unit
Data exchange with the CPU Units uses the I/O memory allocated to the
Serial Communications Board and Serial Communications Unit. For details on
allocations, refer to 2-3 I/O Memory Allocations.
2-2-1 Serial Communications Board (CS Series Only)
CPU Unit Serial Communications Board
CIO 1900
Inner Board Area in
CIO Area
Software switch
Local memory
25 words
Status
CIO 1999
D32000
Inner Board Area in
DM Area
Local memory
(System Setup)
System Setup (see note 1)
20 words
D32099
A636
A608
A424
Auxiliary Area
Port Settings
Change Bits
(see note 2)
Restart Bits
Error Information
Error information
Note
1.
Set the Serial Communications Board mode and the communications settings (System Setup) in the words allocated in the DM Area. Use a Programming Device, such as a Programming Console or the CX-
Programmer, to make these settings. The System Setup is transferred to the Serial Communications Board at the following times:
• When the power to the CPU Unit is turned ON, when the Serial Communications Board is restarted (A60800 is turned ON), or when the
STUP(237) instruction is executed.
• When the Port 1 Port Settings Change Bit (A63601) or Port 2 Port Settings Change Bit (A63602) is turned ON.
2.
When STUP(237) is executed, the CPU Unit automatically turns ON the
Port 1 or Port 2 Port Settings Change Bit and updates the System Setup.
For details on the STUP(237) instruction, see Appendix O Changing Com-
munications Port Settings Using STUP(237).
73
Data Exchange with the CPU Unit
Section 2-2
2-2-2 Serial Communications Units (CS/CJ Series)
CPU Unit
Serial Communications Unit
Unit No. : 0
Local memory
Unit No. 0
CPU Bus Unit Area in CIO Area
CIO 1500
CIO 1501
25 words
Software switches
25 words
Status
CIO 1524
CIO 1525
CIO 1526
25 words
Unit No. 1
CIO 1549
Unit No. 15
Unit No. 0
Unit No. 1
CIO 1875
25 words
CIO 1899
CPU Bus Unit Area in DM Area
D30000
D30001
100 words
System Setup
(see note 1)
D30099
D30100
D30101
100 words
D30199
Local memory (System Setup)
20 words
Unit No. 15
Unit No. 0
Unit No. 1
Unit No. 15
D31500
100 words
D31599
A620
A621
A635
A501
Unit 15
Auxiliary Area
Unit 0
Note
Port Settings
Change Bits
(see note 2)
Restart Bits
1.
Set the Serial Communications Unit mode and the communications settings (System Setup) in the words allocated in the DM Area. Use a Programming Device, such as a Programming Console or the CX-
Programmer, to make these settings. The System Setup is transferred to the Serial Communications Unit at the following times:
• When the power to the CPU Unit is turned ON, when the Serial Communications Unit is restarted (a bit between A50100 to A50115 is turned ON), or when the STUP(237) instruction is executed.
74
I/O Memory Allocations
Section 2-3
• When the Port 1 Port Settings Change Bit (a bit between A62001 to
A63501 (see note a)) or Port 2 Port Settings Change Bit (a bit between
A62002 to A63502 (see note b)) is turned ON.
Note a) Bits are allocated in the following order: Unit number 0: A62001, unit number 1: A62101, unit number 2: A62201, and so on through unit number F: A63501.
b) Bits are allocated in the following order: Unit number 0: A62002, unit number 1: A62102, unit number 2: A62202 and so on through unit number F: A63502.
2.
When STUP(237) is executed, the CPU Unit automatically turns ON the
Port 1 or Port 2 Port Settings Change Bit and updates the System Setup.
For details on the STUP(237) instruction, see Appendix O Changing Com-
munications Port Settings Using STUP(237).
2-3 I/O Memory Allocations
This section explains the DM Area, CIO Area, and Auxiliary Area allocations to the Serial Communications Boards and Serial Communications Units. The
Serial Communications Board uses the allocations for the Inner Board of the
CPU Unit. The Serial Communications Unit is allocated I/O memory as a CPU
Bus Unit according to the unit number setting.
2-3-1 DM Area
Serial Communications
Boards (CS Series Only)
The Setup Area allocated in the DM Area consists of 20 words between
D32000 and D32767, except for the Modbus-RTU slave mode, which uses 40 words for the Setup Area. These words are used to set the serial communications mode, communications specifications, and other settings for the Serial
Communications Board.
The 20 words from D32000 to D32009 and D32020 to D32029 are used for port 1, and the 20 words from D32010 to D32019 and D32030 to D32039 are used for port 2. The remaining words are reserved for the system.
Setup Area Allocated in the DM Area
D32000 to D32767
Words
D32000 to D32009
D32010 to D32019
D32020 to D32029
D32030 to D32039
D32040 to D32767
Usage
Port 1 Settings
Port 2 Settings
Port 1 Settings for Modbus-RTU slave mode
Port 2 Settings for Modbus-RTU slave mode
Reserved for the system
75
I/O Memory Allocations
Serial Communications
Units (CS/CJ Series)
Setting the Setup Areas
Section 2-3
The Setup Area allocated in the DM Area is used to set the serial communications mode, communications specifications, and other settings for the Serial
Communications Units. The words from D30000 to D31599 (100 words per
Unit
× 16 Units) are allocated according to the unit number settings.
m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Words
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
Unit No. 9
Unit No. A
D30900 to D30999
D31000 to D31099
Unit No. B D31100 to D31199
Unit No. C D31200 to D31299
Unit No. D D31300 to D31399
Unit No. E D31400 to D31499
Unit No. F D31500 to D31599 m to m + 9: Port 1 Settings m + 10 to m + 19: Port 2 Settings m + 20 to m + 29: Port 1 Settings for Modbus-
RTU slave mode m + 30 to m + 39: Port 1 Settings for Modbus-
RTU slave mode m + 40 to m + 99: Reserved for the system
The following methods can be used to set the Unit settings in the Setup
Areas.
• Use a Programming Device, such as a Programming Console (see note a), CX-Protocol, or CX-Programmer.
• Use the STUP(237) instruction (see note b) in the ladder diagram program. If it is necessary to change the System Setup while the ladder diagram program is being executed, use this method to change the System
Setup.
Note a) If settings are changed from a Programming Device, cycle the power to the CPU Unit, use a Restart Bit to restart the Unit or
Board, or use the Port Settings Change Bits to restart the port. Re-
fer to 2-2 Data Exchange with the CPU Unit for the specific ad-
dresses to use.
b) For the procedure used to change the System Setup using the
STUP(237) instruction, refer to Appendix R Changing Communi-
cations Port Settings Using STUP(237).
The usage of the System Setup differs according to the serial communications mode. For details, refer to the following sections.
Host Link communications: Section 4 Using Host Link Communications.
Protocol macros: Section 5 Using Protocol Macros.
1:N NT Links:
Loopback test:
Section 8 Using 1:N NT Links.
Section 10 Loopback Test.
76
I/O Memory Allocations
Section 2-3
Setup Area
m = D30000 + 100
× unit number
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit Setting contents
Port 1 Port 2 Port 1 Port 2
D32000 D32010 m m + 10 15 Port settings (see note 1) 0: Defaults; 1: User settings
12 to 14 Reserved
08 to 11 Serial communications mode (see note 2)
0 hex: Default (Host Link); 2 hex: 1:N NT Links (see note 3); 3 hex:
No-protocol; 5 hex: Host Link; 6 hex: Protocol macro; 9 hex: Serial
Gateway; A hex: Modbus-RTU slave; F hex: Loopback test
05 to 07 Reserved
04 Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
03 Data length 0: 7 bits; 1: 8 bits
D32001 D32011 m + 1
02
01
Stop bits
Parity
00 Parity m + 11 04 to 15 Reserved
0: 2 bits; 1: 1 bit
0: Yes; 1: No
0: Even; 1: Odd
00 to 03 Baud rate (Unit: bps) (see note 4)
0 hex: Default (9,600); 3 hex: 1,200; 4 hex: 2,400; 5 hex: 4,800; 6 hex:
9,600; 7 hex: 19,200;
8 hex: 38,400; 9 hex: 57,600; A hex: 115,200
Note: The maximum baud rates depend on the Unit version, as listed in the following table.
Unit version
Pre-Ver. 1.2
Units
Unit Ver. 1.2 or later
Unit Ver. 1.3 or later
Serial communications mode
Host Link or Loopback test
Protocol macro
Maximum baud rate setting (bits/s)
A hex: 115,200
8 hex: 38,400
NT Link 0 to 9 hex: Standard NT Link
A hex: High-speed NT Link
A hex: 115,200 Host Link, Serial gateway, or
Loopback test
No-protocol or Protocol macro 9 hex: 57,600
NT Link
Modbus-RTU slave
0 to 9 hex: Standard NT Link
A hex: High-speed NT Link
A hex: 115,200
77
I/O Memory Allocations
Section 2-3
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Bit
Port 1 Port 2 Port 1 Port 2
D32002 D32012 m+ 2 m + 12 15
00 to 14
D32003
D32004
D32005
D32006
D32007
D32013
D32014
D32015
D32016
D32017 m + 3 m + 4 m + 5 m + 6 m + 7
Setting contents
m + 13 15
14
11 to 13
08 to 10
Host
Link,
Serial
Gateway,
Protocol macro,
Noprotocol
Send delay 0: Default (0 ms); 1: User-specified
Send delay (user-specified): 0 to 300 s (0 to 300,000 ms)
(0000 to 7530 hex; 0 to 30,000 decimal)
(Unit: 10 ms)
CTS control (see note 5) 0: No; 1:Yes
1:N/1:1 protocol setting (Unit Ver. 1.2 or later only)
1: 1:1 protocol; 0: 1:N protocol
If the Host Link compatible device mode is set to 0 to 2 hex
(mode A or B), the setting in this bit is invalid (fixed to 1:N Host
Links)
Reserved
Host Link compatible device mode (Unit Ver. 1.2 or later only)
0 hex: Default (mode A)
1 hex: Mode A (CS/CJ/C)
2 hex: Mode B (CVM1/CV)
3 hex: Mode C (C200H)
4 hex: Mode D (C500/120)
00 to 07 Host
Link m + 14 08 to 15 No-
00 to 07 protocol m + 15 13 to 15
12
Host Link unit number (00 to 1F hex)
Start code (00 to FF hex)
End code (00 to FF hex)
Reserved
10 to 11
08 to 09
00 to 07
Start code inclusion setting
0: No; 1: Yes
Reserved
End code inclusion setting
00: No (specify number of receive data bytes)
01: Yes
11: CR + LF specified
Number of receive data bytes
00 hex (default): 256 bytes
01 to FF hex: 1 to 255 bytes m + 16 03 to 15 Modbus-
RTU slave
00 to 07 Protocol macro
Modbus-RTU slave address
01 to F7 hex: 1 to 247
00 to 02 1:N NT Links maximum unit number (0 to 7) m + 17 08 to 15 Serial
Gateway/
Protocol macro
Response timeout monitoring time (Unit Ver. 1.2 or later only)
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
(Unit: 100 ms)
Serial Gateway send start timeout monitoring time (Unit Ver.
1.2 or later only)
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
(Unit: 100 ms)
78
I/O Memory Allocations
Section 2-3
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
D32008 D32018 m + 8 m + 18 15
Bit
D32009 D32019 m + 9
Setting contents
04 to 14
03
02
00 to 01 m + 19 00 to 15
Protocol macro
Transmission method
0: Half-duplex; 1:Full-duplex
Reserved
Clearing/holding the contents of the reception buffer in fullduplex mode (Unit Ver. 1.2 or later only)
0: Clear; 1: Hold
Link word specification data exchange timing (Unit Ver. 1.2 or later only)
0: On-request I/O refreshing
1: Continuos I/O refreshing
Reserved
Maximum number of bytes in protocol macro send/receive data (00C8 to 03E8 hex: 200 to 1,000 bytes)
Note
1.
The default settings used for Host Link, protocol macro, and loopback test modes areas follows: Baud rate: 9,600 bps, start bits: 1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
The default settings used for Modbus-RTU slave mode are as follows:
Baud rate: 19,200 bps, data length: 8 bits, parity: even, and stop bits: 1 bits.
2.
A System Setup error will occur if 1, 3, 4, or 7 to E is set, and the Unit will operate with the default Host Link settings (9,600 bps, unit number 00).
3.
The PTs connected to the port must also be set for a 1:N NT Link. Communications will not be possible if a PT is set for a 1:1 NT Link.
4.
Do not set B to F settings, and baud rates that are not supported by the serial communications mode. A System Setup error will result. Settings of
1 and 2 are reserved for the system and should not be used.
5.
With CTS control, turn ON the request to send (RTS) signal before stating to send, and be sure the clear to send (CTS) signal is ON before sending data. When there is no CTS control, turn ON the request to send (RTS) signal before sending, and then send data without checking the request to send (RTS) signal.
6.
For settings below 00C8, use 00C8 Hex; for settings above 03E8, use
03E8 Hex.
2-3-2 CIO Area
Serial Communications
Boards (CS Series Only)
Words in the CIO Area are allocated as Software Switches, which are manipulated from the CPU Unit to control the operation of the Serial Communications Board or Unit, and for a Status Area, which contains status and error information for the Serial Communications Board or Unit.
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for the Software Switches and Status Area. CIO 1900 contains software switches, and the 24 words from CIO 1901 to CIO 1924 are used for the Status Area.
Inner Board CIO Area
CIO 1900 to CIO 1999
Usage Words
CIO 1900
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
Software switch
Board status
Port 1 status
79
I/O Memory Allocations
Serial Communications
Units (CS/CJ Series)
Section 2-3
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Port 2 status
Reserved for the system
Words are allocated in the CIO Area for Software Switches and Status Area.
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. The first word is used for Software Switches, and the remaining 24 words are used for the Status Area.
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
CIO 1675 to CIO 1699
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E
Unit No. F
CIO 1850 to CIO 1874
CIO 1875 to CIO 1899 n: Software switches (Ports 1 and 2) n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
80
I/O Memory Allocations
Software Switches
Status Area
Section 2-3
Software Switches are used to output control signals from the CPU Unit to the
Serial Communications Board or Unit. The software switches are used for loopback tests and to abort, release wait status, and control other functions for protocol macros. For details on the software switch functions, refer to Sec-
tion 5 Using Protocol Macros and Section 10 Loopback Test.
n = CIO 1500 + 25
× unit number
Bit Function
CIO
1900
Words
Board
(CS only)
n
Unit
(CS/
CJ)
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Port 2 Reserved
Loopback Test Switch (loopback tests)
1: Start, 0: Stop
Reserved
Serial Gateway Prohibited Switch (protocol macros)
1: Prohibited, 0: Not prohibited
Abort Switch (protocol macros)
1: Abort, 0: Aborted
One-shot Trace Switch (protocol macros, see note)
1: Start, 0: Stop
Continuous Trace Switch
(protocol macros, see note)
1: Start, 0: Stop
Wait Release Switch (protocol macros)
1: Release wait, 0: Wait released
Port 1 Reserved
Loopback Test Switch (loopback tests)
1: Start, 0: Stop
Reserved
Serial Gateway Prohibited Switch (protocol macros)
1: Prohibited, 0: Not prohibited
Abort Switch (protocol macros)
1: Abort, 0: Aborted
One-shot Trace Switch (protocol macros, see note)
1: Start, 0: Stop
Continuous Trace Switch
(protocol macros, see note)
1: Start, 0: Stop
Wait Release Switch (protocol macros)
1: Release wait, 0: Wait released
Note The One-shot Trace Switch and Continuous Trace Switch are used for the
Serial Communications Board/Unit only when executing traces from the CX-
Protocol in protocol macro mode. Do not manipulate these switches from a ladder diagram.
The Status Area is used for status information input from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit sets communications status, the transmission control signal status, the transmission error status, and the protocol status.
81
I/O Memory Allocations
Section 2-3
n = CIO 1500 + 25
× unit number
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO 1901 n + 1
CIO 1902
CIO 1903
CIO 1904
CIO
1905
CIO
1906
CIO
1907
CIO
1915
CIO
1916
CIO
1917
02 to 15 Reserved n + 2 n + 3
01
00
00 to 15
00 to 15
1: Error log EEPROM error
1: Protocol data error
Reserved
Reserved n + 4 00 to 15 Reserved n + 5 n + 15 12 to 15 Port set-
08 to 11 ting status
05 to 07
04
03
02
Serial communications mode
(see note 1)
Serial communications mode
Baud rate
Reserved
0: Error log EEPROM normal
0: Protocol data normal
Start bits: Always 1
Data length: 7 or 8 bits
Stop bits: 1 or 2 bits
01
00 n + 6 n + 16 15
14
13
Bit
02 to 12
01
00 n + 7 n + 17 11 to 15 Commu-
10 nications status
09
08
Contents
Parity: Yes/No
Parity: Even/Odd
Hardware settings
(see note 2)
0 No 0 RS-232C 1 RS-422A/485 1 Reserved
0 1 0 1
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: System Setup error; 0: System Setup normal
1: Port operating; 0: Port stopped
Reserved
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive
Reserved
1: Local Unit busy receiving (Flow control)
0: Local Unit ready to receive
07
06
05
04
03
00 to 02
Transmission control signal status
DTR (ER) signal
DSR (DR) signal
Reserved
CTS (CS) signal
RTS (RS) signal
Reserved
82
I/O Memory Allocations
Section 2-3
Words Bit Contents
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO
1908
CIO
1918 n + 8 n + 18 15
14
13
12
Transmission error status
1: Transmission error (see note 3); 0: No transmission error
1: Tfs (send finished monitoring time) exceeded (see note 4);
0: Normal
1: Tfr (receive finished monitoring time) exceeded (see note
4); 0: Normal
1: Tr (receive wait monitoring time) exceeded (see note 4)
0: Normal
Number of retries (see note 4)
1: FCS check error (see note 5); 0: FCS check normal
08 to 11
07
06
05
04
03
1: Command error (see note 4); 0: No command error
1: Timeout (protocol macros: Tfs, Tfr, or Tr) error or Serial
Gateway send/response timeout (see note 6); 0: Normal
1: Overrun error (see note 7); 0: Normal
1: Framing error (see note 8); 0: Normal
02
00, 01
1: Parity error (see note 8); 0: Normal
Reserved
00 to 15 Protocol status (See Protocol Status on page 83.) CIO
1909 to
CIO
1914
CIO
1919 to
CIO
1924 n + 9 to n + 14 n + 19 to n + 24
Note
Protocol Status
1.
The port settings in the Setup Area allocated in the DM Area is read. For details on the contents that are read, see 2-3-1 DM Area. If a System Setup error occurs, the default settings will be read.
2.
The port types for the Serial Communications Board or Unit and the terminating resistance switch setting are read.
3.
Turned ON if an overrun error (bit 04), a framing error (bit 03), or a parity error (bit 02) occurs with the Host Link mode. If any of the error bits 00 to
14 turns ON in the protocol macro mode but then communications are recovered within the specified number of retries, the bit will turn OFF. The bit will remain ON if recovery is not possible within the specified number of retries.
4.
Used only with protocol macros. Not used with any other serial communications mode.
5.
Used with protocol macros or Serial Gateway. This bit turns ON (is set to
1) if an error occurs in the transmission path while using the Serial Gateway. With Modbus-RTU slave mode, this bit turns ON if there is a CRC error.
6.
Used with protocol macros or Serial Gateway. This bit turns ON (is set to
1) if a send start timeout or response timeout occurs while using the Serial
Gateway.
7.
Not used with NT Links or loopback tests. This bit also turns ON (is set to
1) if 260 bytes or more are stored in the reception buffer during no-protocol communications.
8.
Not used with NT Links or loopback tests.
The protocol status is used in protocol macro mode, NT Link mode, or loopback tests. It is not used with other modes. The contents depend on the serial communications mode, as shown in the following tables.
83
I/O Memory Allocations
Section 2-3
Protocol Macro Mode
n = CIO 1500 + 25
× unit number
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO
1909
CIO
1919 n + 9 n + 19 15
14
13
12
11
10
09
08
CIO
1910
CIO
1920
Bit Contents
Port operating status
Protocol Macro Executing Flag
Step Troubleshooting Flag
Aborted Flag
Tracing Flag
Sequence End Completion Flag
Sequence Abort Completion Flag
Sequence Waiting Flag
Serial Gateway Prohibited Flag
1: Prohibited; 0: Not prohibited
04 to 07
00 to 03
Reserved
Error codes
0: No error
2: Sequence number error
3: Data read/write area exceeded error
4: Protocol data syntax error n + 10 n + 20 12 to 15 Reserved
00 to 11 Communications Sequence Number
000 to 999 (000 to 3E7 hex)
CIO
1911
CIO
1912
CIO
1913
CIO
1914
CIO
1921
CIO
1922
CIO
1923
CIO
1924 n + 11 n + 21 12 to 15 Reserved
08 to 11 Executed Step Number (code)
0 to 15 (0 to F hex)
04 to 07 Reserved
00 to 03 Executed Reception Case Number (code)
0 to 15 (0 to F hex) n + 12 n + 22 00 to 15 Executed Reception Case Number Storage Flag
0 to 15: Correspond to bits 00 to 15 n + 13 n + 23 00 to 15 Executed Step Number Storage Flag
0 to 15: Correspond to bits 00 to 15 n + 14 n + 24 08 to 15 Repeat Counter Setting Value
0 to 255 (00 to FF hex)
00 to 07 Repeat Counter Present Value
0 to 255 (00 to FF hex)
NT Links
n = CIO 1500 + 25
× unit number
Board
(CS Series only)
Port 1
CIO
1909
CIO
1910 to
CIO
1914
Port 2
CIO
1919
CIO
1920 to
CIO
1924
Words
Unit
(CS/CJ Series)
Port 1
n + 9
Port 2
n + 19 n + 10 to n + 14 n + 20 to n + 24
Bit Contents
08 to 15 PT Priority Registered Flag
00 to 07 PT Communications Flag
00 to 15 Reserved
84
I/O Memory Allocations
Section 2-3
Loopback Tests
n = CIO 1500 + 25
× unit number
Contents Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
CIO
1909
Port 2
CIO
1919
Port 1
n + 9
Port 2
n + 19
Bit
15
09 to 14
08
07
Test status
1: Error; 0: Normal
Reserved
1: DSR (DR) signal check error; 0: Normal
1: CTS (CS) signal check error; 0: Normal
Reserved
1: Timeout error; 0: Normal
06
05
04
03
02
01
1: Parity error; 0: Normal
1: Overrun error; 0: Normal
1: Framing error; 0: Normal
Reserved
00 1: Conveyor error; 0: Normal
00 to 15 Number of tests executed CIO
1910
CIO
1911
CIO
1912 to
CIO
1914
CIO
1920
CIO
1921
CIO
1922 to
CIO
1924 n + 10 n+11 n + 12 to n + 14 n + 20 n+21 n + 22 to n + 24
00 to 15 Number of test errors
00 to 15 Reserved
No-protocol Mode
n = CIO 1500 + 25
× unit number
Contents Words
Board
(CS Series only)
Unit
(CS/CJ Series)
---
Port 1
---
Port 2 Port 1
n + 09
Port 2
n + 19
----n + 10 n + 20
Bit
15 to 08 Reserved
07
06
Reception Overflow Flag
1: Board/Unit has received the specified number of bytes or more
0: Board/Unit has not received the specified number of bytes or more
Reception Completed Flag
1: Reception completed; 0: No reception or reception in progress
05 TXDU(256) Executing Flag
1: Executing; 0: Not executing
04 to 00 Reserved
15 to 00 Receive counter (number of receive data bytes)
The number of bytes of received data between
0 and 256 bytes is indicated using 0000 to 0100 hex.
85
I/O Memory Allocations
Section 2-3
Modbus-RTU Slave Mode
n = CIO 1500 + 25
× unit number
Contents Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1
CIO
1909
CIO
1910
CIO
1911
Port 2
CIO
1919
CIO
1920
CIO
1921
Port 1
n + 09 n + 10 n + 11
Port 2
n + 19 n + 20 n + 21
CIO
1912
CIO
1913
CIO
1914
CIO
1922
CIO
1923
CIO
1924 n + 12 n + 13 n + 14 n + 22 n + 23 n + 24
Bit
15 to 00 Number of normally received commands
15 to 00 Number of normally sent responses
15 to 00 Number of overrun errors, framing errors, and parity errors (transmission errors)
15 to 00 Number of CRC errors (transmission errors)
15 to 00 Number of command format errors (illegal function codes and illegal addresses)
15 to 00 Reserved.
2-3-3 Related Auxiliary Area Bits
Serial Communications
Boards (CS Series Only)
Port 1 and Port 2 Port Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
Word
A636
Bit
03 to 15 Reserved
02
Contents
1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved
86
I/O Memory Allocations
Note
Section 2-3
Inner Board Error Information
Word Bit
A424 12 to 15 Non-fatal
11 errors
(see note
10
1)
09
08
07
06
05
04
03
02
01
00
Fatal errors
(see note
2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area,
1: Protocol data error (SUM error); 0: Normal
1: System Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
1: Inner Board service disabled (See note 3.); Normal
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
1.
When any one of bits 04 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
3.
This bit turns ON if a TXD(236)/RXD(235) instruction is sent during no-protocol communications to an Inner Board that does not support no-protocol mode (no Unit Ver. indicated).
For details on each type of error, refer to Section 11 Troubleshooting and
Maintenance.
Restart Bit: A60800
The Restart Bit can be turned ON and then OFF to restart the Serial Communications Board without turning OFF the PLC power supply.
Bit
A60800 Inner Board Restart Bit
Function
87
I/O Memory Allocations
Section 2-3
No-protocol Mode Bits
Word
Boards (CS Series only)
Port 1 Port 2
Bit Word Bit
A356 07 A356 15
A357
06
05
00 to 04
00 to 15 A358
Contents
14
Reception Overflow Flag
1: Board/Unit has received the specified number of bytes or more
0: Board/Unit has not received the specified number of bytes or more
Reception Completed Flag
1: Reception completed; 0: No reception or reception in progress
13 Send Ready Flag
1: Send enabled; 0: Send disabled
08 to 12 Reserved
00 to 15 Receive counter (number of receive data bytes)
The number of bytes of received data between 0 and 256 bytes is indicated using 0000 to 0100 hex.
Serial Communications
Units (CS/CJ Series)
Port 1 and Port 2 Port Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Unit ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF. The port 1 or port 2 Port Settings Change Bits and Restart Bits are allocated in the Auxiliary
Area according to the unit number as shown below.
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
n
Words Bit
03 to 15 Reserved
02
01
Contents
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
00 Reserved n = A620 + unit number
Unit
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Port 1 Settings Change Bit Port 2 Settings Change Bit
A62001 A62002
A62101
A62201
A62102
A62202
A62301
A62401
A62501
A62601
A62302
A62402
A62502
A62602
A62701
A62801
A62901
A62702
A62802
A62902
88
I/O Memory Allocations
Section 2-3
Unit
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
Port 1 Settings Change Bit Port 2 Settings Change Bit
A63001
A63101
A63201
A63301
A63401
A63501
A63002
A63102
A63202
A63302
A63402
A63502
A50100
A50101
A50102
Unit
A50103
A50104
A50105
A50106
A50107
A50108
A50109
A50110
A50111
A50112
A50113
A50114
A50115
Restart Bit
A Restart Bit can be turned ON and then OFF to restart the Serial Communications Board without turning OFF the PLC power supply.
Function
Unit No. 0 Restart Bit
Unit No. 1 Restart Bit
Unit No. 2 Restart Bit
Unit No. 3 Restart Bit
Unit No. 4 Restart Bit
Unit No. 5 Restart Bit
Unit No. 6 Restart Bit
Unit No. 7 Restart Bit
Unit No. 8 Restart Bit
Unit No. 9 Restart Bit
Unit No. A Restart Bit
Unit No. B Restart Bit
Unit No. C Restart Bit
Unit No. D Restart Bit
Unit No. E Restart Bit
Unit No. F Restart Bit
TXDU(256)/RXDU(255) Instruction Bits for No-protocol Mode
Word
A202
A203 to
A210
A219
Bit Contents
00 to 07 Network Communications Enabled Flag
Turns ON when execution of network communications instructions (SEND(090), RECV(098), CMND(490), and PMCR(260)) including TXDU(256) and RXDU(255) instructions is enabled.
00 to 15 Network Communications Completion Code
Stores the completion code for network communications instructions (SEND(090), RECV(098), CMND(490), and
PMCR(260)) including TXDU(256) and RXDU(255) instructions that have been executed.
00 to 07 Communication Port Error Flags
Turn ON if an error occurs during execution of network communications instructions (SEND(090), RECV(098), CMND(490), and PMCR(260)) including TXDU(256) and RXDU(255) instructions.
89
I/O Memory Allocations
Section 2-3
90
SECTION 3
Installation and Wiring
This section describes how to mounting the Serial Communications Board and Serial Communications Units, and how to connect the ports to external devices.
3-1 Installing a Serial Communications Board . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1-1 Precautions in Handling the Board . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Installing Serial Communications Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-1 System Configuration Precautions . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2-2 CS-series Serial Communications Unit . . . . . . . . . . . . . . . . . . . . . .
3-2-3 CJ-series Serial Communications Unit . . . . . . . . . . . . . . . . . . . . . . .
3-2-4 Unit Handling Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-1 Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-3 Communications Modes and Ports . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-4 Connector Pin Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-5 Mounting Height and Connector Cover Dimensions . . . . . . . . . . . .
3-3-6 Reducing Electrical Noise for External Wiring . . . . . . . . . . . . . . . .
3-3-7 2-Wire and 4-Wire Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3-8 NT-AL001-E Link Adapter Settings. . . . . . . . . . . . . . . . . . . . . . . . .
3-3-9 Connections for Host Link Communications . . . . . . . . . . . . . . . . . .
3-3-11 1:N NT Link Connections with Programmable Terminals. . . . . . . .
3-3-12 Connections in Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4 RS-232C and RS-422A/485 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-1 Recommended RS-232C Wiring Examples . . . . . . . . . . . . . . . . . . .
3-4-2 Recommended RS-422A/485 Wiring Examples . . . . . . . . . . . . . . .
3-4-3 Wiring Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-5 Assembling Connector Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-6 Connecting to Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
91
Installing a Serial Communications Board
Section 3-1
3-1 Installing a Serial Communications Board
Installation Procedure
Note
1,2,3...
This section describes how to install a Serial Communications Board in the option slot of a CPU Unit. Only one Serial Communications Board can be installed in each CPU Unit.
1.
Always turn OFF the power before installing or removing the Serial Communications Board. Installing or removing the Serial Communications
Board with the power ON can cause the CPU Unit to malfunction, damage internal components, or cause communications errors.
2.
Before handling the Serial Communications Board, touch a grounded metallic object in order to discharge any static build-up from your body.
1.
Press the catches at the top and bottom of the Inner Board compartment cover.
Press the top catch.
Press the bottom catch.
2.
Remove the Inner Board compartment cover.
Inner Board Connector
3.
Insert the Serial Communications Board.
92
Installing Serial Communications Units
Section 3-2
3-1-1 Precautions in Handling the Board
• Turn OFF the power supply to the CPU Unit before mounting or connecting the Board.
• Separate the port connector lines from the high-tension or power lines to reduce external noise.
• Leave the port cover attached when not using a communications port.
-V1
Port cover
3-2 Installing Serial Communications Units
3-2-1 System Configuration Precautions
• Words in I/O memory are allocated to the Serial Communications Unit according to the setting of the unit number switch on the front panel of the
Unit. Allocations are not affected by the slot in which the Unit is mounted.
Refer to 2-3 I/O Memory Allocations.
• For CS-series PLCs, Serial Communications Units can be mounted to
CS1W-BC
@@8 CPU Backplanes and CS1W-BI@@3 Expansion Backplanes. Up to 16 Serial Communications Units can be mounted for each
PLC (as long as no other CPU Bus Units are mounted).
• For CJ-series PLCs, Serial Communications Units can be connected in the CPU Rack or Expansion Rack. (No more than 10 optional Units can be connected in each Rack.) Up to 16 Serial Communications Units can be connected in each PLC (as long as no other CPU Bus Units are mounted).
93
Installing Serial Communications Units
Section 3-2
3-2-2 CS-series Serial Communications Unit
Use the following steps to mount or remove Serial Communications Units.
1,2,3...
1.
Mount the Unit to the Backplane by hooking the top of the Unit into the slot on the Backplane and rotating the Unit downwards.
Hook
Backplane
2.
Make sure that the connector on the back of the Unit is properly inserted into the connector in the Backplane.
3.
Use a Phillips screwdriver to tighten the screw on the bottom of the Unit.
The screwdriver must be held at a slight angle, so be sure to leave enough space below the Rack.
Duct
CPU Unit
I/O Power
Supply Unit
Remote I/O
Rack
Duct
Phillips screwdriver
20 mm min.
Backplane
20 mm min.
Note Tighten the screw to a torque of 0.4 N
⋅m.
To remove the Unit, loosen the screw with a Phillips screwdriver, rotate the
Unit upwards, and then remove it.
94
Installing Serial Communications Units
Section 3-2
3-2-3 CJ-series Serial Communications Unit
1,2,3...
1.
Align the connectors properly and then press in on the Unit to connect it.
Connector
PA205R
POWER
SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
OPEN
RUN
ERR/ALM
INH
PRPHL
COMM
MCPWR
BUSY
AC100-240V
INPUT
L1
L2/N
RUN
SD1
RDY
ERH
TERM
OFF
SD2
ON
RD1
TER1
RD2
23
4567
UNIT
NO.
WIRE
2 4
PORT1
(RS422
/485)
PERIPHERAL
PORT2
RUN
OUTPUT
AC240V
DC24V
PORT
2.
Slide the sliders on the top and bottom of the Unit until they lock the Units together.
Slider
PA205R
POWER SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
OPEN
RUN
ERR/ALM
INH
PRPHL
COMM
MCPWR
BUSY
RUN
SD1
RDY ERH
TERM
OFF
SD2
ON
RD1 TER1
RD2
UNIT
NO.
WIRE
2 4
PORT1
(RS422
/485)
Release
Lock
AC100-240V
INPUT
L1
L2/N
PERIPHERAL
PORT2
RUN
OUTPUT
AC240V
DC24V
PORT
Note If the sliders are not locked properly, the Serial Communications Units may not function correctly.
To remove the Unit, move the sliders to the release position and then pull the
Units gently apart.
95
Installing Serial Communications Units
Section 3-2
3-2-4 Unit Handling Precautions
• Always turn OFF the CPU Unit before mounting or removing a Serial
Communications Unit or connecting or disconnecting cables to/from the
Serial Communications Unit.
• Place the port connecting cables in a different duct from those for highvoltage lines or power lines to prevent the effects of electrical noise from these lines.
• Do not remove the protective label from the top of the Unit until wiring has been completed. This label prevents wire strands and other foreign matter from entering the Unit during wiring. Remove the label after wiring has been completed to allow air circulation needed for cooling.
• If a serial port is not being used, leave the cover on the port to prevent dust from entering.
CS-series Unit
Remove label after wiring.
CJ-series Unit
Port cover
SCU41
RUN
ERC
RDY
ERH
TERM
OFF
SD1
SD2
ON
RD1 TER1
RD2
23
01
4567
UNIT
NO.
WIRE
2
4
PORT1
(RS422
/485)
PORT2
Remove label after wiring.
Port cover
96
Wiring
Section 3-3
3-3 Wiring
3-3-1 Wiring Precautions
• Before connecting or disconnecting the communications cables, always make sure that the PLC is turned OFF.
• Tighten the communications connector screws firmly with your fingers.
• Serial Communications Boards and Units can be connected to various devices. For compatibility, refer to the operation manuals for the devices to which they are to be connected.
3-3-2 Port Types
The following port types are provided on the Serial Communications Boards and Units.
PLC Series
CS Series
CJ Series
Unit type
Serial Communications Board
Serial Communications Unit
Model
CS1W-
SCB21-V1
CS1W-
SCB41-V1
CS1W-
SCU21-V1
CS1W-
SCU21-V1
CS1W-
SCU41-V1
Port 1
RS-232C
RS-232C
RS-232C
RS-232C
Port 2
RS-232C
RS-422A/485
RS-232C
RS-232C
RS-422A/485 RS-232C
The following sections describe the connection methods used for each serial communications mode of the Serial Communications Board and Unit ports.
3-3-3 Communications Modes and Ports
The following table shows the relationship between the communications ports and the communications modes for the Serial Communications Boards and
Unit. Serial Communications Units provide only RS-232C ports.
RS-422A/485
1:N 4-wire 1:1 2-wire 1:N 2-wire
Communications mode
Host Link
1:1 Host Link
Protocol macros
Serial Gateway
No-protocol
NT Link
Modbus-RTU slave
YES
YES
YES
YES
YES
YES
YES
1:1
RS-232C
1:N
(see note 1)
YES
(see note 2)
YES
(see note 2)
YES
YES
YES
YES
YES
1:1 4-wire
YES
YES
YES
YES
YES
YES
YES
YES
No
YES
YES
YES
YES
YES
No
No
YES
YES
No
YES
YES
No
No
YES
YES
No
YES
YES
Note
1.
The NT-AL001-E Link Adapter can be used to convert between RS-232C and RS-422A/485 to enable 1:N communications.
2.
Use 4-wire connections between Link Adapters.
97
Wiring
Section 3-3
3-3-4 Connector Pin Layout
RS-232C Ports
7
8
5
6
3
4
1
2
9
Hood
Pin Abbreviation
FG
SD
RD
RTS (RS)
CTS (CS)
5V
DSR (DR)
DTR (ER)
SG
FG
Signal name
Shield
Send data
Receive data
Request to send
Clear to send
Power supply
Data set ready
Data terminal ready
Signal ground
Shield
---
Output
Input
Output
I/O
Input
---
Input
Output
---
---
Refer to 2-1 Component Names and Functions for signal precautions.
RS-422A/485 Ports
5
6
3
4
1
2
7
8
9
Hood
Pin Abbreviation
SDA
SDB
NC
NC
NC
RDA
NC
RDB
NC
FG
Send data -
Send data +
Unused
Unused
Unused
Receive data -
Unused
Receive data +
Unused
Shield
Output
I/O
Output
---
---
---
Input
---
Input
---
---
Note When the 2-wire connections are used, use either pins 1 and 2, or pins 6 and
8.
Refer to 2-1 Component Names and Functions for signal precautions.
The internal circuits are shown in the following diagram.
Receiver
Driver
Terminating resistance: 220
Ω
Terminating resistance switch
Port 2
Pin 8
Pin 6
2-wire or 4-wire switch
Pin 2
Pin 1
Note The signal names SDA/B and RDA/B do not always have the same polarity as that shown above. Check the polarity of the external device before making connections.
98
Wiring
Section 3-3
3-3-5 Mounting Height and Connector Cover Dimensions
When mounting the Serial Communications Board or Unit, make sure to provide space for the mounting height and connector cover dimensions shown below.
CS1W-SCB21-V1 Serial Communications Board
(mounted to CPU Unit)
CS1W-SCB41-V1 Serial Communications Board
(mounted to CPU Unit)
Cable connector
Cable connector
223
123
223
123
CS1W-SCU21-V1 Serial Communications Unit
CJ1W-SCU21-V1/41-V1 Serial Communications Unit
Cable connector
Cable connector
150
65
223
123
Note The mounting heights shown above are applicable when the attached connectors, connector covers, and recommended cables are used. The mounting height may differ when other connectors, connector covers, and cables are used. Determine the mounting height, taking into account the connectors, connector covers, and the minimum bending radius of the cables.
3-3-6 Reducing Electrical Noise for External Wiring
Observe the following precautions for external wiring.
• When multi-conductor signal cable is being used, avoid using I/O wires and other control wires in the same cable.
• If wiring racks are running in parallel, allow at least 300 mm between the racks.
99
Wiring
Section 3-3
Low-current cables
Communications cables
PLC power supply and general control circuit wiring
Power lines
Control cables
Power cables
300 mm min.
300 mm min.
Ground to 100
Ω or less.
• If the I/O wiring and power cables must be placed in the same duct, they must be shielded from each other using grounded steel sheet metal.
Communications cables
PLC power supply and general control circuit wiring
Power lines
Steel sheet metal
200 mm min.
Ground to 100
Ω or less.
3-3-7 2-Wire and 4-Wire Connections
The transmission circuits for 2-wire and 4-wire connections are different, as shown in the following diagram.
Example of 4-Wire
Connections
Example of 2-Wire
Connections
2/4-wire switch
(DPDT)
Board
Other Unit
Other Unit
2/4-wire switch
(DPDT)
Other Unit
Not connected
Board
Other Unit
Note
1.
Use the same transmission circuit (2-wire or 4-wire) for all nodes.
2.
Do not use 4-wire connections when the 2/4-wire switch on the Board is set to 2-wire.
3.
In protocol macro mode, do not use full-duplex transmissions when the 2/
4-wire switch on the Unit is set to 2-wire. Otherwise, the data sent from the
Serial Communications Board or Unit will be directly returned as receive data. In this case, the Board or Unit cannot determine whether the data in the reception buffer is its own send data or the data received from a remote node, and thus cannot perform receive processing properly. To avoid this problem, always use half-duplex transmissions with a 2-wire setting. Either half-duplex or full-duplex transmissions can be used with a 4-wire setting.
100
Wiring
Section 3-3
3-3-8 NT-AL001-E Link Adapter Settings
The NT-AL001-E Link Adapter has a DIP switch for setting RS-422A/485 communications conditions. When connecting the Unit or Board, refer to the DIP switch settings shown in the following table.
Pin
3
4
1
2
5
6
Function
Not used. Always set this pin to ON.
Built-in terminating resistance setting
ON: Connects terminating resistance.
OFF: Disconnects terminating resistance.
2/4-wire setting
2-wire: Set both pins to ON.
4-wire: Set both pins to OFF.
Transmission mode ()
Constant transmission: Set both pins to OFF.
Transmission performed when CTS signal in
RS-232C interface is at high level: Set pin 5 to
OFF and pin 6 to ON.
Transmission performed when CTS signal in
RS-232C interface is at low level: Set pin 5 to
ON and pin 6 to OFF.
Factory setting
ON
ON
OFF
OFF
ON
OFF
Note When connecting to a CS/CJ-series CPU Unit, turn OFF pin 5 and turn ON pin 6.
3-3-9 Connections for Host Link Communications
Port connections for Host Link communications are shown in the following table. Up to 32 Units and Boards can be connected for 1:N connections.
Port
RS-232C
Computer to
PLC: C-mode or
FINS commands
PLC to computer: FINS commands
Configuration
1:1
Schematic diagram, RS-232C ports
RS-232C
Schematic diagram, RS-422A/485 ports
RS-232C
NT-AL001-E
Resistance ON
5-V power
RS-422A/485
Resistance ON
RS-232C
Computer to
PLC: C-mode or
FINS commands
1:N
NT-AL001-E
RS-422A/485
RS-232C
Resistance ON
5-V power
NT-AL001-E
RS-232C
Resistance ON
RS-232C RS-422A/485
NT-AL001-E
NT-AL001-E
Resistance ON
5-V power RS-232C
RS-232C
Resistance ON
RS-232C
RS-232C
NT-AL001-E
Resistance ON
5-V power
RS-422A/485
B500-AL001
RS-422A
/485
Resistance ON
Note
1.
Four-wire connections must be used for RS-422A/485 connections with
Host Link communications.
2.
“Resistance ON” indicates the terminating resistance must be turned ON.
3.
“5-V power” indicates that a 5-V power supply is required for the Link
Adapter. Refer to the Link Adapter manual for details. A 5-V power supply
101
Wiring
Section 3-3
is not required for a Link Adapter connected to a Serial Communications
Board or Unit because power is supplied from pin 6 of the connector.
4.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
Connection Examples
Host Computer
Connections
The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-
pair cables. Refer to 3-4 RS-232C and RS-422A/485 Wiring for actual wiring
methods.
1:1 Connections Using RS-232C Ports
IBM PC/AT or Compatible Computers
Serial Communications
Board or Unit
RS-232C interface
Signal
Pin
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
Computer
Pin Signal
CD
RD
SD
DTR
SG
DSR
RTS
CTS
CI
RS-232C interface
D-sub, 9-pin connector (male)
Using NT-AL001-E Converting Link Adapters
Computer
Shield
NT-AL001-E Link Adapter
RS-232C
Interface
Signal
RS-232C
FG
SD
RD
RTS
CTS
Pin
DSR
DTR
SG
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal Pin
RS-422A
NT-AL001-E Link Adapter
Pin Signal
Signal
Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
(See note)
Serial Communications
Board or Unit
Pin Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
Interface
5-V (+) power (-)
D-sub, 9-pin Terminal block connector (male)
D-sub, 9-pin connector (male)
D-sub, 9-pin connector (male)
D-sub, 9-pin connector (male)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
102
Wiring
Section 3-3
!Caution Do not use the 5-V power from pin 6 of the RS-232C port for anything but the
NT-AL001-E Link Adapter. Using this power supply for any other external device may damage the Serial Communications Board/Unit or the external device.
1:N Connections Using RS-232C Ports
Computer
Signal
Shield
RS-232C
Interface
FG
SD
RD
RTS
CTS
DSR
DTR
SG
NT-AL001-E Link Adapter
Pin Signal Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
RS-422A
5-V (+) power (-)
D-sub, 9-pin connector (male)
Terminal block
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
NT-AL001-E Link Adapter
Pin Signal
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Serial Communications
Board/Unit
RS-232C
(See note)
Pin Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
Interface
DIP Switch Settings
Pin 1: ON
Pin 2: OFF
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
D-sub, 9-pin connector (male)
NT-AL001-E Link Adapter
Pin
Signal Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Serial Communications
Board/Unit
Pin
RS-232C
(See note)
Pin
Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
RS-232C
Interface
D-sub, 9-pin connector (male)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
103
Wiring
Section 3-3
1:1 Connections Using RS-422A/485 Ports
Computer
Signal
RS-232C
Interface
FG
SD
RD
RTS
CTS
Shield
DSR
DTR
SG
NT-AL001-E Link Adapter
Pin
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Signal
Serial Communications
Board/Unit
Pin
Signal
RS-422A
/ 485 Interface
Hood
4-wire
Terminating resistance ON
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (-)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
104
Wiring
Section 3-3
1:N Connections Using RS-422A/485 Ports
Computer
NT-AL001-E Link Adapter
RS-232C
Interface
Signal
FG
SD
RD
RTS
CTS
Shield
DSR
DTR
SG
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (-)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
B500-AL001 Link Adapter
Pin Signal Signal Pin
RS-422A/
485 Interface
Serial Communications
Board/Unit
Shield
Pin Signal
RS-422A/
485 Interface
Signal
Pin
Hood
4-wire
Terminating resistance OFF
D-sub, 9-pin connector (male)
Shield
Serial Communications
Board/Unit
Pin Signal
RS-422A/
485 Interface
Hood
4-wire
Terminating resistance ON
Computer
RS-232C
Interface
Signal
FG
SD
RD
RTS
CTS
DSR
DTR
SG
Shield
RS-232C
NT-AL001-E Link Adapter
Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal Pin
D-sub, 9-pin Terminal block connector (male)
5-V (+) power (-)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
Serial Communications
Board/Unit
RS-422A Pin Signal
RS-422A/
485 Interface
Hood
4-wire
Terminating resistance OFF
Serial Communications
Board/Unit
Pin Signal
RS-422A/
485 Interface
Hood
4-wire
Terminating resistance ON
105
Wiring
Section 3-3
Programmable Terminal (PT) Connections
Direct Connections from RS-232C to RS-232C Ports
Note
Serial Communications
Board or Unit
RS-232C
Interface
Signal
FG
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Hood
D-sub, 9-pin connector (male)
PT
Pin Signal
Hood FG
--
SD
RD
RTS
CTS
5V
--
--
SG
RS-232C
Interface
D-sub, 9-pin connector (male)
• Communications Mode: Host Link (unit number 0 only for Host Link)
NT Link (1:N, N = 1 Unit only)
• OMRON Cables with Connectors:
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
1:1 Connections from RS-422A/485 to RS-422A/485 Ports
Serial Communications
Board/Unit
Signal
Pin
RS-422A
/485 Interface
Short bar
Signal
(See note 2.)
PT
RS-422A
/485 Interface
Hood
D-sub, 9-pin connector (male)
Hood
Terminal block or
D-sub connector
Communications Mode: Host Link (unit number 0 only for Host Link)
NT Link (1:N, N = 1 Unit only)
1.
Serial Communications Board/Unit settings:
Terminating resistance ON, 4-wire.
2.
The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the manual for you PT for details.
106
Wiring
Section 3-3
1:N, 4-wire Connections from RS-422A/485 to RS-422A/485 Ports
Serial Communications
Board/Unit
Signal
Pin
RS-422A
/485 Interface
Signal
RS-422A
/485 Interface
Hood
D-sub, 9-pin connector (male)
FG
Terminal block or D-sub connector
Short bar
(See note 2.)
Signal
RS-422A
/485 Interface
Note
FG
Terminal block or D-sub connector
Communications Mode: 1:N NT Link
1.
Serial Communications Board/Unit settings:
Terminating resistance ON, 4-wire.
2.
The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the manual for you PT for details.
1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports
Serial Communications Board/Unit
Signal
Pin
RS-422A
/485 Interface
Hood
D-sub, 9-pin connector (male)
Signal
RS-422A
/485 Interface
FG
Terminal block or D-sub connector
Short bar
(See note 2.)
Signal
RS-422A
/485 Interface
Note
FG
Terminal block or D-sub connector
Communications Mode: 1:N NT Link
1.
Serial Communications Board/Unit settings:
Terminating resistance ON, 2-wire.
107
Wiring
Section 3-3
2.
The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the manual for you PT for details.
3-3-10 Connections for Protocol Macros, Serial Gateway, No-protocol
Mode, and Modbus-RTU Slave Mode
This section describes the connections for protocol macros, Serial Gateway, and no-protocol communications. Up to 32 Boards or Units can be used for
1:N connections.
Schematic diagram Port Configuration
RS-232C 1:1
RS-232C
RS-232C interface
RS-232C 1:N
NT-AL001-E
RS-232C
RS-422A/485
Resistance
ON
NT-AL001-E
RS-232C
RS-422A/485
Resistance
ON
NT-AL001-E
Resistance ON
5-V power
RS-232C interface
NT-AL001-E
Resistance ON
RS-232C RS-422A/485
RS-422A/
485 interface
RS-422A/485 interface
NT-AL001-E
RS-232C
B500-AL001-E
Resistance
ON
RS-422A
/485
Resistance ON
RS-422A/485 interface
NT-AL001-E
RS-232C
Resistance
ON
RS-422A/485
NT-AL001-E
Resistance ON
RS-232C
RS-232C
Resistance ON
5-V power
RS-232C
RS-232C interface
108
Wiring
Port
RS-422A/
485
Configuration
1:1
Schematic diagram
RS-422A/485 interface
RS-422A/485
Section 3-3
RS-422A/
485
1:N
Resistance
ON
NT-AL001-E
RS-232C
RS-422A/485
Resistance ON
5-V power
RS-232C interface
RS-422A/485 interface
RS-422A/485
Resistance
ON
RS-422A/485
B500-AL001-E
Resistance ON
RS-422A/485 interface
Note
Resistance ON
RS-232C interface
NT-AL001-E
RS-232C
Resistance
ON
RS-422A/485
RS-232C
Resistance ON
5-V power
RS-232C
1.
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not cover baud rates above 19.2 Kbps. Refer to the manual for the device being connected to confirm support.
2.
The combined cable length for RS-422A/485 is 500 m including branch lines.
3.
The maximum cable length is limited to 2 m when an NT-AL001-E Link
Adapter is connected.
4.
Branch lines must be a maximum of 10 m long.
109
Wiring
Section 3-3
Connection Examples
The connection examples in the remainder of this section show only the basic connection diagrams. We recommend that appropriate noise countermeasures be taken in actual applications, including the use of shielded twisted-
pair cables. Refer to 3-4 RS-232C and RS-422A/485 Wiring for actual wiring
methods.
Connecting RS-232C Ports 1:1
Connections to E5CK Controller
Serial Communications
Unit or Board
Signal
FG
Pin
SD
RD
RTS
CTS
DSR
DTR
SG
D-sub, 9-pin connector (male)
RS-232C
Shield
OMRON E5CK Controller
RS-232C: Terminal Block
Terminal Signal
SD
RD
SG
Connections to a Personal Computer with RTS-CTS Flow Control
Computer
FG
SD
RD
RTS
CTS
DSR
DTR
SG
Serial Communications
Board or Unit
RS-232C port
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Connecting a Host Computer with NT-AL001-E Converting Link Adapters
Serial Communications
Board or Unit
RS-232C
Interface
Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
D-sub, 9-pin connector (male)
RS-232C
NT-AL001-E Link Adapter
Pin
Shield
Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal Pin
RS-422A
(See note)
D-sub, 9-pin connector (male)
Terminal block
Pin
NT-AL001-E Link Adapter
Signal
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Computer
RS-232C
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
5-V (+) power (-)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF (4-wire)
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF (4-wire)
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
110
Wiring
Section 3-3
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
Connections to a Modem
Modem
FG
SD
RD
RTS
CTS
DSR
SG
CD
Serial Communications Board or Unit
RS-232C port
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
ST2
RT
DTR
CI
ST1
111
Wiring
Section 3-3
1:N Connections Using RS-232C Ports
Serial Communications
Unit or Board
NT-AL001-E
RS-232C interface
Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
RS-232C
Shield
Pin Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal
Pin
D-sub, 9-pin connector (male)
RS-232C interface
Signal
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
DIP SW
Pin 1: ON
Pin 2: ON Terminating resistance
Pin 3: OFF 4-wire
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Serial Communications
Unit or Board
Pin
RS-232C
Shield
Pin
NT-AL001-E
Signal
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Signal
D-sub, 9-pin connector (male)
(See note)
D-sub, 9-pin Terminal block connector (male)
(See note)
D-sub, 9-pin connector (male)
Pin
Terminal block
RS-422A
Shield
DIP SW
Pin 1: ON
Pin 2: ON Terminating resistance
Pin 3: ON 2-wire
Pin 4: ON
Pin 5: OFF
Pin 6: ON
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
Device supporting
RS-422A/485 communications
(2-wire)
Signal
RS-422A
/485 interface
Device supporting
RS-422A/485 communications
(2-wire)
Signal
RS-422A
/485 interface
Note We recommend using the following NT-AL001-E Link Adapter Connecting
Cables to connect to NT-AL001-E Link Adapters.
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
112
Wiring
Section 3-3
1:1 Connections Using RS-422A/485 Ports
Device supporting
RS-422A/485 communications
(2-wire)
Serial Communications Board/Unit
Signal Pin
Shield
RS-422A
/485 interface
Signal
RS-422A
/485 interface
Hood
D-sub, 9-pin connector (male)
Serial Communications Board/Unit
Signal Pin
Shield
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A
/485 interface
RS-422A
/485 interface
Hood
D-sub, 9-pin connector (male)
Serial Communications Board/Unit
RS-422A
/485 interface
Signal Pin
RS-422A
Shield
Hood
D-sub, 9-pin connector (male)
NT-AL001-E Link Adapter
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Computer
RS-232C
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
D-sub, 9-pin connector (male)
5-V (+) power (-)
DIP Switch Settings
Pin 1: ON
Pin 2: ON
(terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: OFF
113
Wiring
Section 3-3
1:N Connections Using RS-422A/485 Ports
Serial Communications Board/Unit
Signal Pin
Device supporting RS-422A/485 communications (2-wire)
Signal
RS-422A/
485 interface
RS-422A/
485 interface
Hood
Device supporting
RS-422A/485 communications
(2-wire)
D-sub, 9-pin connector (male)
Serial Communications Board/Unit
RS-422A/
485 Interface
Signal Pin
Signal RS-422A/
485 interface
Pin
Signal
RS-422A/
485 interface
Signal Pin
Shield
Device supporting
RS-422A/485 communications
(4-wire)
Signal
RS-422A/
485 interface
Hood
D-sub, 9-pin connector (male)
Signal
Pin
D-sub, 9-pin connector (male)
Device supporting
RS-422A/485 communications
(4-wire)
Shield
Signal
RS-422A/
485 interface
Serial Communications Board/Unit
Signal
Pin
RS-422A/
485 Interface
Hood
4-wire
D-sub, 9-pin con-
Terminating resistance ON nector (male)
Shield
NT-AL001-E Link Adapter
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Shield
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
DIP Switch
Pin 2: OFF, otherwise same as below.
D-sub, 9-pin connector (male)
(+) 5-V
(-) power
DIP Switch
Pin 1: ON
Pin 2: ON (terminating resistance)
Pin 3: OFF
Pin 4: OFF
Pin 5: OFF
Pin 6: ON
Shield
NT-AL001-E Link Adapter
Pin Signal Signal Pin
NC
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Terminal block
D-sub, 9-pin connector
(male)
Shield
Signal
FG
SD
RD
RTS
CTS
RS-232C
Interface
DSR
DTR
SG
(+) 5-V
(-) power
114
Wiring
Section 3-3
3-3-11 1:N NT Link Connections with Programmable Terminals
The connections used for each port type in NT Link mode are the same as for
protocol macro mode. Refer to 3-3-10 Connections for Protocol Macros,
Serial Gateway, No-protocol Mode, and Modbus-RTU Slave Mode. Up to eight Units or Boards can be used for a 1:N connection.
Direct Connections from RS-232C to RS-232C Ports
Serial Communications
Board or Unit
RS-232C
Interface
Signal
FG
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
Pin
Hood
D-sub, 9-pin connector (male)
PT
Pin Signal
Hood FG
--
SD
RD
RTS
CTS
5V
--
--
SG
RS-232C
Interface
D-sub, 9-pin connector (male)
• Communications Mode: Host Link (unit number 0 only for Host Link)
NT Link (1:N, N = 1 Unit only)
• OMRON Cables with Connectors:
XW2Z-070T-1: 0.7 m
XW2Z-200T-1: 2 m
1:N, 4-wire Connections from RS-422A/485 to RS-422A/485 Ports
Serial Communications
Board/Unit
Signal
Pin
RS-422A
/485 In terface
Signal
PT
RS-422
A/485
Inter face
Hood
D-sub, 9-pin connector (male) FG
Terminal block or
D-sub connector
Short bar
Signal
(See note 2.)
PT
RS-422A
/485 In
terface
Note
FG
Terminal block or
D-sub connector
Communications Mode: 1:N NT Link
1.
Serial Communications Board/Unit settings:
Terminating resistance ON, 4-wire.
2.
The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the manual for you PT for details.
115
RS-232C and RS-422A/485 Wiring
1:N, 2-wire Connections from RS-422A/485 to RS-422A/485 Ports
Serial Communications
Board/Unit
Signal
Pin
RS-422A/
485 Inter face
Hood
D-sub, 9-pin connector (male)
Signal
PT
RS-422A
/485 In
terface
Section 3-4
FG
Terminal block
Short bar
Signal
(See note 2.)
PT
RS-422A
/485 Interface
Note
FG
Terminal block
Communications Mode: 1:N NT Link
1.
Serial Communications Board/Unit settings:
Terminating resistance ON, 2-wire.
2.
The terminating resistant setting shown above is an example for the
NT631/NT631C. The setting method varies with the PT. Refer to the manual for you PT for details.
3-3-12 Connections in Loopback Test
Connect the communications ports as shown below.
RS-232C port
Pin Signal
SD
RD
RTS
CTS
FG
DTR
DSR
RS-422A/485 port
Pin
Signal
3-4 RS-232C and RS-422A/485 Wiring
3-4-1 Recommended RS-232C Wiring Examples
It is recommended that RS-232C cables be connected as described below especially when the Serial Communications Board or Unit is used in an environment where it is likely to be subject to electrical noise.
1,2,3...
1.
Always use shielded twisted-pair cables as communications cables.
Model
UL2464 AWG28x5P IFS-RVV-SB (UL product)
AWG28x5P IFVV-SB (non-UL product)
UL2464-SB (MA) 5Px28AWG (7/0.127) (UL product) CO-
MA-VV-SB 5Px28AWG (7/0.127) (non-UL product)
Manufacturer
Fujikura Ltd.
Hitachi Cable, Ltd.
116
RS-232C and RS-422A/485 Wiring
Section 3-4
Serial
Communications
Board/Unit
Pin Signal
Hood
SD
RD
RTS
CTS
SG
FG
FG
Shield
2.
Combine signal wires and SG (signal ground) wires in a twisted-pair cable.
At the same time, bundle the SG wires to the connectors on the Serial
Communications Board/Unit and the remote device.
3.
Connect the shield of the communications cable to the Hood (FG) terminal of the RS-232C connector on the Serial Communications Board/Unit. At the same time, ground the ground (GR) terminal of the Power Supply Unit on the CPU Rack or CS Expansion Rack to 100
Ω or less.
4.
A connection example is shown below.
Example: Twisted-pair Cable Connecting SD-SG, RD-SG, RTS-SG, and
CTS-SG Terminals
Actual Wiring Example
SG signal wires
Twist the shaded lines to make them thinner and connect to Pin
No. 1 (FG). Cover this section with heat-shrink tube to avoid contact with other sections.
Remote device
Signal
RD
SD
CTS
RTS
SG
FG
Bundle the SG wires.
Aluminum foil
XM2S-0911-E
CS-series PLC
SCU21
RUN
ERC
SD1
RD1
RDY
ERH
SD2
RD2
E
F 0 1
2
PORT1
PORT2
Note The Hood (FG) is internally connected to the ground terminal (GR) on the
Power Supply Unit via the CPU Rack or Expansion Rack. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply Unit.
Although there is conductivity between the Hood (FG) and pin 1 (FG), connect the Hood (FG) to the shield because the Hood (FG) has smaller contact resistance with the shield than pin 1 (FG), and thus provides better noise resistance.
Serial Communications Board/Unit
PA204S
Power Supply Unit
RUN
ERR/ALM
INH
PRPHL/COMN
SYSMAC CS1G
PROGRAMABLE CONTROLLER
CPU42
POWER
MCPWR
OPEN
OPEN
BUSY
L2/N
L1
AC100V-120V/
AC2100-240V/
INPUT
100-200
CLOSE
200-240
OPEN GR
PERIPHERAL
DC24V/0.8A
OUTPUT
PORT (RS-232C)
Hood and GR are internally connected.
Ground to 100
Ω or less
Grounding the GR terminal grounds the Hood (FG).
CJ-series PLC
GR
Power Supply Unit
PA205R
POWER
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
RUN
ERR/ALM
INH
PRPHL
COMM
OPEN
MCPWR
BUSY
AC100-240V
INPUT
L1
L2/N
PERIFHERAL
RUN
OUTPUT
AC240V
DC24V
Ground to
100
Ω or less.
Serial
Communications
Unit
SCU41
RUN ERC SD1 RD1 TER1
RDY ERH SD2 RD2
TERM
OFF
WIRE
2
ON
4
12
34567
UNIT
NO.
PORT1
(RS422
/485)
PORT2
PORT
Hood and GR are internally connected.
Grounding the GR terminal grounds the Hood (FG).
117
RS-232C and RS-422A/485 Wiring
Section 3-4
3-4-2 Recommended RS-422A/485 Wiring Examples
Recommended RS-422A/
485 Cable
1,2,3...
1.
Always use shielded twisted-pair cables as communications cables.
Model
CO-HC-ESV-3Px7/0.2
Manufacturer
Hirakawa Hewtech Corp.
2.
Connect the shield of the communications cable to the Hood (FG) of the
RS-422A/485 connector on the Serial Communications Board or Unit. At the same time, ground the ground (GR) terminal of the Power Supply Unit on the CPU Rack or CS Expansion Rack to 100
Ω or less.
Note Always ground the shield only at the Board/Unit end. Grounding both ends of the shield may damage the device due to the potential difference between the ground terminals.
Connection examples are shown below.
2-Wire Connections
Serial Communications
Board/Unit
Pin
Signal
Remote device
Signal
Hood
Shield
4-Wire Connections
Serial Communications
Board/Unit
Pin Signal
Remote device
Signal
Hood
Shield
Using a B500-AL001-E Link Adapter
Serial Communications
Board/Unit
Pin
Signal
B500-AL001
Pin
Signal Signal Pin
RS-422 interface
Hood
Signal
Pin
Remote device
Signal
Remote device
Signal
118
RS-232C and RS-422A/485 Wiring
Section 3-4
Serial Communications
Board/Unit
• With NT-AL001-E RS-232C/RS-422 Link Adapter
NT-AL001-E
Pin
Signal
2
7
8
9
5
6
3
4
Hood
SD
RD
RS
CS
5V
DR
ER
SG
FG
RS-232C
(See note.)
Shield
Pin
Signal
3
8
9
6
7
2
4
5
Hood
RD
SD
RS
CS
5V
DR
ER
SG
FG
Signal Pin
SDA
SDB
RDA
RDB
GRD
6
5
4
3
1
RS-422
Remote device
Signal
RDA
RDB
SDA
SDB
Remote device
Signal
RDA
RDB
SDA
SDB
FG
Note
1.
The following cables are available for this connection.
Length
70 cm
2 m
XW2Z-070T-1
XW2Z-200T-1
Model
It is recommended that one of these cables be used to connect the RS-
232C port on the Serial Communications Board or Unit to the NT-AL001-E
RS-232C/RS-422 Link Adapter. The recommended wiring for these cables is shown below.
SYSMAC PLC
NT-AL001-E
(internal)
Pin
Signal
1
2
5
6
3
4
7
8
9
Hood
FG
SD
RD
RS
CS
5V
DR
ER
SG
FG
Signal
Pin
Not used.
RD
SD
RS
CS
5V
DR
ER
SG
FG
1
3
6
7
8
2
4
5
9
Hood
Arrows indicate signal directions
Loopback
Loopback
Shield
2.
The XW2Z-070T-1 and XW2Z-200T-1 Connecting Cables for the NT-
AL001-E Link Adapter uses special wiring for the DTS and RTS signals.
Do not use these signals with other devices; they may be damaged.
3.
The Hood (FG) is internally connected to the ground terminal (GR) on the
Power Supply Unit via the CPU Rack or Expansion Rack. Therefore, FG is grounded by grounding the ground terminal (GR) on the Power Supply
Unit.
119
RS-232C and RS-422A/485 Wiring
Section 3-4
CS-series PLC
Serial Communications Board/Unit
CJ-series PLC
Serial
Communications Unit
Power Supply Unit
SCU21
RUN
ERC
SD1
RD1
RDY
ERH
SD2
RD2
E
F 0 1
2
RUN
ERR/ALM
INH
PRPHL/COMN
SYSMAC CS1G
PROGRAMABLE CONTROLLER
CPU42
POWER
MCPWR
OPEN
OPEN
BUSY
PA204S
Power Supply Unit
PA205R
POWER
SYSMAC
CJ1G-CPU44
PROGRAMMABLE
CONTROLLER
RUN
ERR/ALM
INH
PRPHL
COMM
OPEN
MCPWR
BUSY
SCU41
RUN ERC SD1 RD1 TER1
RDY ERH SD2 RD2
TERM
OFF
WIRE
2
ON
4
12
34567
UNIT
NO.
PORT1
(RS422
/485)
PORT1
L2/N
AC100V-120V/
AC2100-240V/
INPUT
L1
100-200
CLOSE
200-240
OPEN
AC100-240V
INPUT
L1
L2/N
GR
GR
PERIFHERAL
PORT2
PERIPHERAL
DC24V/0.8A
OUTPUT
RUN
OUTPUT
AC240V
DC24V
PORT2
PORT (RS-232C)
PORT
Hood and GR are internally connected.
Ground to 100
Ω or less
Grounding the GR terminal grounds the Hood (FG).
Ground to
100
Ω or less.
Hood and GR are internally connected.
Grounding the GR terminal grounds the Hood (FG).
4.
Be sure to turn ON the terminating resistance at the last Unit at the end of the RS-422A/485 cable.
3-4-3 Wiring Connectors
Use the following steps to wire connectors.
Cable Preparation
See the following diagrams for the length of the cable portion to be cut in each step.
Shield Connected to Hood (FG)
1,2,3...
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield.
25 mm (RS-422A)
40 mm (RS-232C)
3.
Trim off the braided shield using scissors so that the remaining shield length is 10 mm.
10 mm
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5 mm
120
RS-232C and RS-422A/485 Wiring
5.
Fold back the braided shield.
6.
Wrap aluminum foil tape around the folded shield.
Section 3-4
Aluminum foil tape
Shield Not Connected to Hood (FG)
1,2,3...
1.
Cut the cable to the required length.
2.
Remove the specified length of the sheath from the cable using a knife. Be careful not to scratch the braided shield.
25 mm (RS-422A)
40 mm (RS-232C)
3.
Trim off all the braided shield using scissors.
4.
Remove the insulation from each conductor using a stripper so that the exposed conductor length is 5 mm.
5 mm
5.
Wrap adhesive tape around the conductor from which the braided shield was removed.
Adhesive tape
3-4-4 Soldering
1,2,3...
1.
Thread a heat-shrinking tube through each conductor.
2.
Temporarily solder each conductor to the corresponding connector terminals.
3.
Completely solder each conductor.
121
RS-232C and RS-422A/485 Wiring
1 mm
Section 3-4
Soldering iron
Heat-shrinking tube
Inside diameter:
1.5 mm, l = 10
4.
Return the heat-shrinking tube to the soldered portion, then heat the tube to shrink it in place.
Heat-shrinking tube
3-4-5 Assembling Connector Hood
Assemble the connector hood as shown below.
End connected to FG
Grounding plate
Adhesive tape
Aluminum foil tape
End not connected to FG
122
RS-232C and RS-422A/485 Wiring
3-4-6 Connecting to Unit
CS-series Unit
Tighten the screws firmly with your fingers.
Section 3-4
CJ-series Unit
Tighten the screws firmly with your fingers.
123
SECTION 4
Using Host Link Communications
This section describes the procedure and other information required to use Host Link communications.
4-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2-2 Setup Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 Auxiliary Area Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4-1 Simultaneous Commands and Communications Ports . . . . . . . . . . .
4-4-2 Communications Control Signals and Communications Timing . . .
4-4-3 Flags for Network Communications. . . . . . . . . . . . . . . . . . . . . . . . .
4-4-4 Timing of Commands Addressed to a Host Computer. . . . . . . . . . .
4-5-2 RS-422A/485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6 Host Link Function for Replacing Existing PLCs . . . . . . . . . . . . . . . . . . . . .
4-6-1 Support for 1:1 Host Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-6-2 Host Link-compatible Device Selection . . . . . . . . . . . . . . . . . . . . . .
125
Host Link Communications
Section 4-1
4-1 Host Link Communications
Host Link System can be used to send C-mode commands or FINS commands from a host computer (e.g., personal computer or PT) to a PLC to read/write I/O memory, control operating modes, etc. The PLC can also use the SEND(090), RECV(098), and CMND(490) instructions to send FINS commands to the host computer for “slave-initiated communications.” Using the
PLC to control communications enables controlling and monitoring of the overall system operating status.
Refer to the CS/CJ-series Communications Commands Reference Manual
(W342) for details on C-mode and FINS commands.
Host-initiated
Communications
PLC-initiated
Communications
Communications in a Host Link System are normally started by the host computer.
Command
Host computer
CS/CJ-series PLC
Response
The host computer sends a command to the PLC. The PLC processes the command and returns a response to the host computer. This process is repeated, allowing the host computer to monitor and control PLC operation.
Both C-mode and FINS commands can be used in host-initiated communications.
The PLC can also initiate communications with the host computer, as may be necessary when errors occur on the line controlled by the PLC or to confirm the operating status of the host computer.
Command
Host computer CS/CJ-series PLC
Response
The PLC sends a command to the host computer through a Serial Communications Unit or Board. The host computer processes the command and, when necessary, returns a response to the PLC.
Using PLC-initiated communications requires that a program be prepared on the host computer to process commands received from a PLC and return the required responses. Only FINS commands can be used in PLC-initiated communications.
Note Always transfer uppercase letters when using Host Link communications.
Lowercase letters cannot be processed.
4-2 Setup Area Allocations
This section describes the Setup Area allocated to the Serial Communications
Board and Serial Communications Units in the DM Area when Host Link communications are used.
4-2-1 Setup Area Words
The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when Host Link communications are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to the unit numbers).
126
Setup Area Allocations
Serial Communications
Boards (CS Series only)
Serial Communications
Units (CS/CJ Series)
Section 4-2
Setup Area Allocated in the DM Area: D32000 to D32099
Words
D32000 to D32003
D32010 to D32013
D32004 to D32009
D32014 to D32019
D32020 to D32767
Usage
Port 1 Settings
Port 2 Settings
Not used in Host Link Communications
Reserved for the system
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area: m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
Words
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599 m to m + 3: Port 1 Settings m + 10 to m + 13: Port 2 Settings m + 14 to m + 9 and m + 14 to m + 19:
Not used in Host Link communications m + 20 to m + 99: Reserved for the system
127
Setup Area Allocations
Section 4-2
4-2-2 Setup Area Contents
m = D30000 + 100
× Unit No.
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2
D32000 D32010 m
Port 1 Port 2
m + 10 15
Bit
03
02
01
00
Port settings
Setting contents
0: Defaults; 1: User settings
12 to 14 Reserved
08 to 11 Serial communications mode
0: Default (Host Link)
5: Host Link
05 to 07 Reserved
04 Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
Data length
Stop bits
Parity
Parity
0: 7 bits; 1: 8 bits
0: 2 bits; 1: 1 bit
0: Yes; 1: No
0: Even; 1: Odd
D32001 D32011 m + 1
D32002
D32003
D32012
D32013 m+ 2 m + 3 m + 11 04 to 15 Reserved
00 to 03 Baud rate (bps)
0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200;
8: 38,400; 9: 57,600; A: 115,200 m + 12 15 Send delay time 0: Default (0 ms); 1: Setting in bits 00 to 14
00 to 14 Send delay (0000 to 7530 hex) (Unit: 10 ms) m + 13 15
14
CTS control 0: No; 1:Yes
1:N/1:1 protocol setting (Unit Ver. 1.2 or later only)
1: 1:1 protocol; 0: 1:N protocol
If the Host Link compatible device mode is set between 0 and 2 hex
(mode A or B), the setting in this bit is invalid (always 1:N Host
Links)
11 to 13 Reserved
08 to 10 Host Link compatible device mode
0 hex: Default (mode A)
1 hex: Mode A (CS/CJ/C)
2 hex: Mode B (CVM1/CV)
3 hex: Mode C (C200H)
4 hex: Mode D (C500/120)
00 to 07 Host Link unit number (00 to 1F hex)
Port Settings
Serial Communications
Mode
The setting for the port settings determine if the default settings or user settings will be used for port 1 and port 2. Be sure to use the same settings as the RS-232C port on the host computer connected via the Host Link System.
If the default port settings are specified, then the setting of bits 00 to 04 and the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 9,600 bps, start bits:
1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
If user port settings are specified, set bits 00 to 04 and set the baud rate in
D32001.
Setting Example: 0100 Hex = Host link mode with default port settings.
Set the serial communications mode to 5 Hex to use Host Link communications. The default setting of 0 Hex can also be used to operate in Host Link mode with unit number 00.
128
Setup Area Allocations
Section 4-2
Start Bits, Data Length,
Stop Bits, Parity, Baud
Rate
Send Delay
If user settings are specified for the port settings, the number of start bits, data length, number of stop bits, parity, and baud rate must be set. The start bits setting, however, will be ignored and 1 start bit will always be used.
Do not set the baud rate setting to between B and F. A setup error will occur if these settings are used, and the default setting of 9,600 bps will be used. Do not use setting 1 and 2, which are reserved for the system.
If response frames cannot be completely received regardless of the communications processing used at the host computer, a send delay can be set for the response. Any setting higher than 7530 Hex will be treated as 7530 Hex.
Case 1
Serial Communications Board or Unit
Response sent
Host computer
Command sent
Send delay
Case 2
Serial Communications Board or Unit
Host computer
First command frame
Second command frame
Delimiter
Send delay
Case 3
Serial Communications Board or Unit
Host computer
CTS Control
SEND(090),
RECV(098) or
CMND(490)
Command sent
Send delay Response sent
If CTS control is enabled, the RTS signal is turned ON before starting to transfer and then the send is started after confirming that the CTS signal is ON. If
CTS control is not enabled, the RTS signal is turned ON before starting to transfer and then the send is started without checking the status of the CTS signal.
129
Auxiliary Area and CIO Area Allocations
Section 4-3
CTS Control
Send processing
RTS = ON
CTS = ON?
Y
One character sent
N
N
No CTS Control
Send processing
RTS = ON
One character sent
N
Host Link Unit Number
All characters sent?
Y
RTS = OFF
Send processing ended
All characters sent?
Y
RTS = OFF
Send processing ended
Set the setting to 00 to 1F Hex to set Host Link unit numbers 0 to 31.
4-3 Auxiliary Area and CIO Area Allocations
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and the Status
Area allocated in the CIO Area. The Software Switches allocated in the CIO
Area are not used for Host Link communications.
4-3-1 Auxiliary Area Allocations
Port 1 and Port 2 Port
Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
Serial Communications Boards (CS Series only)
Word
A636
Bit
03 to 15 Reserved
02
Contents
1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved
Serial Communications Units (CS/CJ Series)
n
Words Bit Contents
03 to 15 Reserved
02 1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved n = A620 + unit number
130
Auxiliary Area and CIO Area Allocations
Section 4-3
Inner Board Error
Information (CS-series
Serial Communications
Board Only)
A424 contains error information for the Serial Communications Board.
Word Bit
A424 12 to 15 Non-fatal
11 errors
(Note 1)
10
09
08
07
06
05
04
03
02
01
00
Fatal errors
(Note 2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area,
1: Protocol data error (SUM error); 0: Normal
1: Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
Reserved
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
Note
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to Section 11 Troubleshooting and Maintenance.
4-3-2 CIO Area Allocations
Words in the CIO Area are allocated for a Status Area, which contains status and error information for the Serial Communications Board or Unit. These allocations are described in this section.
Serial Communications
Boards (CS Series only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status
Area. Only the words shown in the following table are used for the Status Area with Host Link communications.
Inner Board CIO Area
CIO 1900 to CIO 1999
Words
CIO 1901 to CIO 1904
CIO 1905 to CIO 1908
CIO 1915 to CIO 1918
Board status
Port 1 status
Port 2 status
Usage
Serial Communications
Units (CS/CJ Series)
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. Only the words shown in the following table are used for the Status
Area with Host Link communications.
131
Auxiliary Area and CIO Area Allocations
Section 4-3
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
CIO 1675 to CIO 1699
CIO 1700 to CIO 1724
Unit No. 9
Unit No. A
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
Unit No. B CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E CIO 1850 to CIO 1874
Unit No. F CIO 1875 to CIO 1899 n + 1 to n + 4: Unit status n + 5 to n + 8: Port 1 status n + 15 to n + 18: Port 2 status
Status Area
The Status Area is used for status information input from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status.
n = CIO 1500 + 25
× unit number
Contents Words
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO 1901 n + 1
CIO 1902
CIO 1903
CIO 1904 n + 2 n + 3 n + 4
Bit
02 to 15 Reserved
01 1: Error log EEPROM error
00 1: Protocol data error
00 to 15 Reserved
00 to 15 Reserved
00 to 15 Reserved
0: Error log EEPROM normal
0: Protocol data normal
132
Auxiliary Area and CIO Area Allocations
Section 4-3
Words Bit
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO
1905
CIO
1915 n + 5 n + 15 12 to 15
08 to 11
05 to 07
Port setting status
CIO
1906
CIO
1916
00 n + 6 n + 16 15
14
04
03
02
01
CIO
1907
CIO
1908
CIO
1917
CIO
1918
Setup settings
Contents
Serial communications mode (Note 1)
Baud rate (Note 1)
Reserved
Start bits: Always 1
Data length: 7 or 8 bits (Note 1)
Stop bits: 1 or 2 bits (Note 1)
Parity: Yes/No (Note 1)
Parity: Even/Odd (Note 1)
Hardware settings
0 No 0 RS-232C 1 RS-422A/485 1 Reserved
0 1 0 1 n + 8 n + 18
13
02 to 12
01
00 n + 7 n + 17 11 to 15 Commu-
10 nications status
09
08
07
06
05
04
03
00 to 02
15
05 to 14
04
Reserved
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: Setup error; 0: Setup normal
1: Port operating; 0: Port stopped
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive (Note 2)
Reserved
1: Local Unit busy receiving (Flow control)
0: Local Unit ready to receive (Note 3)
ER signal Transmission control signal status
Transmission error status
DTR signal
Reserved
CTS signal
RTS signal
Reserved
1: Transmission error; 0: No transmission error
Not used.
1: Overrun error; 0: Normal
03
02
00, 01
1: Framing error; 0: Normal
1: Parity error; 0: Normal
Reserved
Note
Error Log EEPROM Error
Protocol Data Error
1.
The settings in the Setup Area are reflected here. The default settings will be used and will be stored here if a setup error occurs.
2.
The status of this bit is not stable in Host Link mode.
3.
Always 0 in Host Link mode.
This bit will be set to 1 if an error occurs in reading or writing the error log stored in EEPROM on the assumption that the EEPROM has reached its useful life. If a Serial Communications Unit is being used, the ERC indicator will also light. If a Serial Communications Board is being used, A42411 will turn
ON and the ERR/ALM indicator on the CPU Unit will flash, indicating a nonfatal error.
This bit will be turned ON if a checksum error is detected in the protocol data at startup. The checksum is checked for all serial communications modes. If a
133
Communications Timing
Port Setting Status
Communications Status
Transmission Control
Signal Status
Transmission Error Status
Section 4-4
Serial Communications Unit is being used, the ERC indicator will also flash. If a Serial Communications Board is being used, A42409 will turn ON, the ERR/
ALM indicator on the CPU Unit will flash, and the RDY indicator will flash at 1second intervals, indicating a non-fatal error.
The operation of Host Link communications is not affected by a protocol data error.
The settings in the Setup Area for the following items will be stored: Serial communications mode, baud rate, start bits, data length, stop bits, parity, ports, terminating resistance, setup error, and port operating/stopped status.
The port operating/stopped status will always be 1 for Host Link mode.
The flow control and buffer status is stored. These bits are cleared at startup or when a port is restarted using STUP(237) or a Port Settings Change Bit
(Auxiliary Area).
The status of the following transmission control signals is stored: ER signal,
DTR signal, CTS signal, and RTS signal. 1: High, 0: Low
The Transmission Error Flag (bit 15) will turn ON if any of the following flags turn ON: Overrun Error (bit 04), Framing Error (bit 03), or Parity Error (bit 02).
4-4 Communications Timing
This section describes the timing of sending commands and controlling communications in the Host Link mode.
4-4-1 Simultaneous Commands and Communications Ports
The CS/CJ-series CPU Units provide eight logical ports that can be used when executing SEND(090), RECV(098), and CMND(490). Therefore, up to eight commands can be executed for one physical port during any one cycle.
The maximum number of messages, however, that can be sent or received in one CPU Bus Unit service time is two messages from the CPU Unit to the
Board or Unit and two messages from the Board or Unit to the CPU Unit.
Board or Unit Logical port CPU Unit
5
1
6
3
0
4
7
2
Instruction 1
Instruction 2
Instruction 3
Instruction 4
Instruction 5
Instruction 6
Instruction 7
Instruction 8
Note
One port must be specified for each instruction.
1.
If more than eight communications instructions are being used, then exclusive control must be performed to make sure that not more than eight are executed at the same time. Refer to descriptions of network communications instructions in the CS/CJ-series Communications Commands Refer-
ence Manual (W342).
134
Communications Timing
Section 4-4
2.
The same communications port numbers are used by both the communications instructions (SEND(090), RECV(098), and CMND(490)) and the
PROTOCOL MACRO instruction (PMCR(260)). The same port number cannot be used by more than one of these instructions at the same time.
4-4-2 Communications Control Signals and Communications Timing
If CTS control is enabled in the Setup Area, the RTS output signal will be turned ON from the Board or Unit and the send process will go on standby until the CTS input signal turns ON. Either release this busy status by incorporating the RTS output signal for the CTS input signal at the host computer, or loop the RTS output signal back to the CTS input signal at the Unit or Board.
Note The status of the RTS and CTS signals can be confirmed in the Transmission
Control Signal Status in the Status Area. Refer to page 132.
4-4-3 Flags for Network Communications
This section describes the flags in the Auxiliary Area that are used when executing SEND(090), RECV(098), and CMND(490).
Communications Port
Enabled Flags
A Communications Port Enabled Flag turns ON when SEND(090),
RECV(098), and CMND(490) can be executed. The flag will turn OFF during execution of these commands and turn ON again when the command execution is completed. When creating the ladder diagram, use these flags as input conditions when executing these instructions.
Word
A202
04
03
02
01
00
Bit
08 to 15
07
06
05
Content
Reserved
Communications Port Enabled Flag, Port No. 7
Communications Port Enabled Flag, Port No. 6
Communications Port Enabled Flag, Port No. 5
Communications Port Enabled Flag, Port No. 4
Communications Port Enabled Flag, Port No. 3
Communications Port Enabled Flag, Port No. 2
Communications Port Enabled Flag, Port No. 1
Communications Port Enabled Flag, Port No. 0
Communications Port
Error Flags
A Communications Port Error Flag will turn ON in the following cases.
• When an error is generated during execution of SEND(090), RECV(098), or CMND(490).
• When an error response or retry error has been generated for the port.
These Flags will turn OFF when the corresponding Communications Port
Enabled Flag is turned OFF at the start of operation or at the start of executing the SEND(090), RECV(098), or CMND(490).
Word
A219
04
03
02
01
00
Bit
08 to 15
07
06
05
Content
Reserved
Communications Port Error Flag, Port No. 7
Communications Port Error Flag, Port No. 6
Communications Port Error Flag, Port No. 5
Communications Port Error Flag, Port No. 4
Communications Port Error Flag, Port No. 3
Communications Port Error Flag, Port No. 2
Communications Port Error Flag, Port No. 1
Communications Port Error Flag, Port No. 0
135
Communications Timing
Section 4-4
Communications Port
Completion Codes
The Communications Port Completion Code words will contain the FINS end code after SEND(090), RECV(098), or CMND(490) has been executed.
If the Communications Port Enabled Flag turns OFF when operation is started or SEND(090), RECV(098), or CMND(490) are executed, the contents of these words will be cleared.
Word
A203
A204
A205
A206
A207
A208
A209
A210
A211 to A218
Content
Communications Port Completion Code, Port No. 0
Communications Port Completion Code, Port No. 1
Communications Port Completion Code, Port No. 2
Communications Port Completion Code, Port No. 3
Communications Port Completion Code, Port No. 4
Communications Port Completion Code, Port No. 5
Communications Port Completion Code, Port No. 6
Communications Port Completion Code, Port No. 7
Reserved
Flag Transitions
Communications Port
Enabled Flag
Network communications instructions
(PMCR(260)/SEND(090)/
RECV(098)/CMND(490))
Communications Port
Error Flag
Communications Port
Completion Code
Instruction 1 being executed
Instruction 2 being executed
Instruction 3 being executed
End of previous processing
(Normal end)
(No unit corresponding to unit address)
(Normal end)
4-4-4 Timing of Commands Addressed to a Host Computer
Commands addressed to a host computer are sent at the timing shown in the following diagrams.
136
Communications Timing
Host Computer Sending Data
Section 4-4
Response Required
Host computer Command
(1)
Command
Response
(2)
Response
Serial Communications
Board/Unit
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
(1)
Communications Port Enabled Flag
Command
(2)
Response
Host Computer Receiving Data
Response Required
Host computer
Serial Communications
Board/Unit
Command acknowledged Command completed
Command transmission to the host computer can start even when the port is receiving a command from the host computer (1). The transmission of a response to the command from the host computer is postponed until the transmission of the command to the host computer is completed (2).
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
Command
(1)
Response
(2)
Command
Response
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
Communications Port Enabled Flag
(1)
Response
(2)
Command
Command acknowledged Command completed
At (1) in the diagram, the response to a command sent from the host computer is being transmitted from the port. In this case, the command transmission to the host computer is postponed until the response transmission is completed (2).
137
Communications Timing
Section 4-4
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
Response Wait Time After Host Computer Sends Data
Response Required
Host computer
Serial Communications
Board/Unit
Command
(1)
Command
Response
Response
Response wait time
(2)
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
(1) Command
Response
Response wait time
(2)
Communications Port Enabled Flag
Command acknowledged Command completed
When response wait time has been set in the command format from the host computer, commands to the host computer will not be transmitted until the response time has elapsed (1). Transmission of responses to commands from the host computer will be postponed until the command transmission to the host computer has been completed (2).
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
4-4-5 Reception Buffers
In Host Link mode, each port has a reception buffer of 1,200 bytes. This is sufficient to hold the maximum Host Link frame length for an FA command response frame (1,115 bytes) + 85 bytes. If a frame larger than 1,200 bytes is sent from the host computer (from @ to the carriage return), the frame will be discarded and no response will be returned.
4-4-6 Error Responses
When Host Link FA commands are used for FINS commands, an error code will returned as the end code in the FINS response whenever there is a mistake in the FINS command settings or an FINS response is required that is too long for the legal response frame.
An end code of 110B Hex is returned when the response exceeds the maximum response length. The Host Link response frame will contain the requested read data after the end code through the end of the maximum legal response frame length.
Note We recommend programming retry processing at any device sending commands in case noise or other factors result in transmission errors.
138
Changes from Previous Products
Section 4-5
4-5 Changes from Previous Products
There are differences between Host Link Systems created using the CS/CJseries Serial Communications Boards and Unit in comparison to Host Link
Systems created with Host Link Units and CPU Units in other PLC product series. These differences are described in this sections.
4-5-1 RS-232C Ports
Previous products
C-series Host
Link Units
C-series CPU
Units
Take the following differences into consideration when changing from an existing Host Link System to one using an RS-232C port on a CS/CJ-series CPU
Unit, Serial Communications Boards, or Serial Communications Unit (CS1H/
G-CPU
@@ RS-232C port, CS1W-SCU21-V1 ports, CJ1W-SCU21/41 port 2,
CS1W-SCB21-V1 ports, or CS1W-SCB41-V1 port 1).
Model number
3G2A5-LK201-E
C500-LK203
3G2A6-LK201-E
C200H-LK201
SRM1
CPM1
CPM1A
CQM1-CPU
@@-E
C200HS-CPU
@@-E
C200HX/HG/HE-
CPU
@@-E
C200HW-COM
@@-E
Changes required for CS/CJ-series product
Wiring
The connector has been changed from a 25-pin to a
9-pin connector.
The CS/CJ-series products do not support the ST1, ST2, and RT signals and wiring them is not required.
The connector has been changed from a 25-pin to a
9-pin connector.
Other
The following changes are necessary for systems that sync with ST1, ST2, and RT.
Synchronized transfers will no longer be possible.
Full-duplex transmissions will be possible with the CS/CJ-series product, but the host computer’s communications program, hardware, or both will need to be altered.
The following changes are necessary for systems that did not sync with ST1, ST2, and RT.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/CJ command specifications.
139
Changes from Previous Products
Section 4-5
Previous products
CVM1 or CVseries CPU
Units
Model number
CVM1/CV-CPU
@@
CVM1 or CVseries Host Link
Unit
CV500-LK201
Changes required for CS/CJ-series product
Wiring
No changes have been made in wiring.
Other
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/CJ command specifications.
The following changes are necessary for half-duplex transmissions that use CD.
Port 1:
The connector has been changed from a 25-pin to a
9-pin connector.
Port 2 set for RS-232C:
The SG signal has been changed from pin 7 to pin 9.
Check the system for timing problems when using SEND, RECV, or CMND to initiate communications from the PLC or timing problems in sending commands from the host computer. If necessary, switch to full-duplex transmissions.
The following changes are necessary for full-duplex transmissions that do not use
CD.
Half-duplex It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CS/CJ command specifications.
Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Host Link
Units and CS/CJ-series Serial Communications Boards/Units. A host computer program previously used for C-series Host Link Units may not function correctly if used for CS/CJ-series PLCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS/CJ-series Communications Commands Refer-
ence Manual (W342) for details.
4-5-2 RS-422A/485 Ports
Take the following differences into consideration when changing from an existing Host Link System to one using an RS-422A/485 port on a CS/CJ-series
Serial Communications Board (CS1W-SCB41-V1 port 2 or CJ1W-SCU41 port
1).
Previous products
C-series Host Link
Units
C200HX/HG/HE
Communications
Board
Model number Changes required for CS/CJ-series product
Wiring Other
3G2A5-LK201-E Wiring pins have been changed as shown below.
C200H-LK202
3G2A6-LK202-E
SDA: Pin 9 to pin 1
SDB: Pin 5 to pin 2
RDA: Pin 6 to pin 6
RDB: Pin 1 to pin 8
SG: Pin 3 to
Not connected
FG: Pin 7 to pin
Connector hood
C200HW-COM
@@-E
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/
CJ command specifications.
140
Host Link Function for Replacing Existing PLCs
Section 4-6
Previous products
CVM1 or CVseries CPU Units
CVM1 or CVseries Host Link
Unit
Model number
CVM1/CV-CPU
@@
CV500-LK201
Changes required for CS/CJ-series product
Wiring
No changes have been made in wiring.
Other
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/
CJ command specifications.
Note For pre-Ver. 1.2 Units, the number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for Cseries Host Link Units and CS/CJ-series Serial Communications Boards/
Units. A host computer program previously used for C-series Host Link Units may not function correctly if it is used in CS/CJ-series PLCs. When using
Serial Communications Boards/Units with Unit Ver. 1.2 or later, these programs can be reused by setting the Host Link compatible device mode to mode C (C500/120) or mode D (D200H). (Alternatively, check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS/CJ-series Communications
Commands Reference Manual (W342) for details.)
4-6 Host Link Function for Replacing Existing PLCs
An enhanced Host Link function is provided to enable reuse of host computer programs created for the existing PLC. By selecting the 1:N/1:1 Host Link protocol and the Host Link compatible device mode according to the existing PLC model, the Board/Unit’s Host Link functions can be fully compatible with the
Host Link of the existing PLC.
4-6-1 Support for 1:1 Host Link
Pre-Ver. 1.2 Units
The C200H-LK101/201/202, C500-LK101/201/103/203, and C120-LK101/
201/202 Host Link Units for earlier C-series PLCs (C200H and C500) enable selection of either 1:1 or 1:N Host Links. The CS/CJ-series and later PLCs, however, only support 1:N Host Links. Therefore, the host computer programs created using 1:1 Host Link protocol cannot be reused in CS/CJ-series PLCs.
141
Host Link Function for Replacing Existing PLCs
Section 4-6
Unit Ver. 1.2 or Later
1:N/1:1 setting
1:N protocol
1:1 protocol
Host computer programs for 1:1 Host Links that have been created using a
C200H/C1000H/C2000H PLC can also be used with CS/CJ-series PLCs by selecting the 1:1 Host Link protocol. The 1:N/1:1 Host Link setting in the
Setup Area in the DM Area enable selection of 1:1 Host Links.
Details
A Host Link protocol that enables a single host to be connected to a single PLC
(1:1) or to multiple PLCs
(1:N).
In previous Boards/Units, only the 1:N protocol was supported.
Supported PLCs
C Series
Built-in port:
SRM1, CPM1, CPM1A,
CQM1-CPU
@@
, C200HS-
CPU
@@
, C200HE/HG/HX-
CPU
@@
, C200HW-COM
@@
CS/CJ Series
Built-in port:
CS1G/H-CPU
@@
H, CS1G/H-
CPU
@@
-V1, CS1D-
CPU
@@
H, CJ1G/H-
CPU
@@
H, CJ1G/M-CPU
@@
Earlier models (pre-Ver. 1.2):
CS1W-SCB21(-V1)/41(-V1),
CS1W-SCU21(-V1), CJ1W-
SCU21/41
CVM1/CV Series
CVM1/CV-CPU
@@
CVM1
(built-in port), CV500-LK201
Remarks
The CS/CJ Series, C200HS/
HX/HG/HE(-Z), CPM
@
, and
CQM1
@
Series all support only 1:N Host Links for the
CPU Unit’s built-in port and
Host Link Unit/Serial Communications Board.
The earlier Serial Communications Units/Boards support only 1:N Host Links.
The CVM1/CV Series supports only 1:N Host Links for the CPU Unit’s built-in port and Host Link Unit/Serial
Communications Unit/Board.
The C-series Host Link Units shown here support both 1:1 protocol and 1:N protocol.
A Host Link protocol that enables a single host to be connected to a single PLC only.
C Series
C500-LK101/201/103/203,
C120-LK101/201/202
C Series
C200H-LK101/201/202
C Series
C500-LK101/201/103/203,
C120-LK101/201/202
C Series
C200H-LK101/201/202
Note The differences between the command and response frames for 1:N Host
Links and 1:1 Host Links is as follows:
1:N Host Link
• Command Format
@ 0 0 R D
Host Link
Unit No.
Header code
• Response Format
@ 0 0 R D 0 0
Host Link
Unit No.
Header code
End code
× × * CR
FCS Terminator
× × * CR
FCS
Terminator
142
Host Link Function for Replacing Existing PLCs
Section 4-6
1:1 Host Link
The frame format for a 1:1 Host Link is the same as that for the 1:N Host Link, except the @, Host Link Unit No., and FCS are omitted.
• Command Format
R D
Header code
* CR
Terminator
• Response Format
R D 0 0
Header code
End code
* CR
Terminator
4-6-2 Host Link-compatible Device Selection
Pre-Ver. 1.2 Units
In earlier models, when the host computer program used by the C-series Host
Link Unit was reused in a CS/CJ-series PLC, data could not be read normally for some programs due to the differences in Host Link specifications.
Unit Ver. 1.2 or Later
RR
RL
RH
RC
RD
RJ
RG
When Serial Communications Units/Boards with Unit Ver. 1.2 or later are used, however, the Board/Unit’s Host Link specifications can be switched according to the CPU Unit or other Unit in which the host computer program is to be reused.
The Host Link specifications change according to the Host Link compatible device mode that is selected.
• When the following commands for reading I/O memory (RR, RL, RH, RC,
RD, RJ, and RG) are received, the number of data words in each response frame that is returned to the host is different.
Command Name
CIO AREA READ
LINK AREA READ
HR AREA READ
PV READ
DM AREA READ
AR AREA READ
T/C STATUS READ
• When the command for reading the status of the CPU Unit (MS) is received, the response format that is returned to the host according to the
FAL/FALS instruction execution status is different.
MS
Command Name
PROCESSOR STATUS READ
143
Host Link Function for Replacing Existing PLCs
Section 4-6
Host Link Compatible Device Modes
Host Linkcompatible device mode
Mode A (CS/
CJ/C)
Mode B
(CVM1/CV)
Mode C
(C200H)
Mode D
(C500/120)
Compatible models (models that supported host computer programs)
RR, RL, RH, RC, RD, and RJ commands
RG command
Number of words in each response frame
First frame Second frame
First frame Second frame
MS command
(See note.)
Response data format
30 words 31 words 121 words 125 words Variable length
C Series
SRM1 (built-in port)
CPM1 (built-in port)
CPM1A (built-in port)
CQM1-CPU
@@
(built-in port)
C200HS-CPU
@@
(built-in port)
C200HE/HG/HX-CPU
@@
(built-in port)
C200HW-COM
@@
(built-in port)
CS/CJ Series
CS1G/H-CPU
@@
H (built-in port)
CS1G/H-CPU
@@
-V1 (built-in port)
CS1D-CPU
@@
H (built-in port)
CJ1G/H-CPU
@@
H (built-in port)
CJ1G/M-CPU
@@
(built-in port)
Earlier models (pre-Ver. 1.2):
CS1W-SCB21(-V1)/41(-V1)
CS1W-SCU21(-V1)
CJ1W-SCU21/41
CVM1/CV Series
CVM1/CV-CPU
@@
CVM1 (built-in port), CV500-LK201
C Series (C200H)
C200H-LK101/201/202
C Series (C500/120)
C500-LK101/201/103/203, C120-
LK101/201/202
89 words 60 words
Fixed length
29 words 30 words 89 words 89 words Variable length
Note
1.
The response data formats for MS commands when FAL/FALS is not executed are as follows:
Types for which a space (20 hex) is added to the FAL/FALS message in the response data (indicated as fixed length in the above table).
Types for which a FAL/FALS message is not added to the response data
(indicated as variable length in the above table).
(A FAL/FALS message is added to the response data for both types if FAL/
FALS is executed.)
2.
The following condition is an exception:
When reusing the RG command created using a CVM1/CV-series PLC with mode B selected, the host computer program cannot be reused without being changed. The difference in the response returned when the RG command is reused and the Timer/Counter Flag for 121 words (maximum text area) is read is as follows:
Using mode B with a CS/CJ-series
Serial Communications Unit/Board with unit version 1.2 or later
First frame
121 words (including terminator)
CVM1/CV-series Host Link Unit First frame
121 words
Second frame
0 words (terminator only)
144
Host Link Function for Replacing Existing PLCs
Section 4-6
Relationship with 1:N/1:1 Protocol Settings
The 1:N/1:1 Host Link protocol setting depends on the compatible device mode, as follows:
• Mode A (CS/CJ/C), mode B (CVM1/CV): 1:N Host Links only
• Mode C (C200H), mode D (C500/120): Either 1:N or 1:1 Host Links
Allocated DM Area Settings (Setup Area)
m = D30000 + 100
× unit number
Port 1
D32003
Board
Port 2
D32013
Words
Port 1
m+3
Unit
Port 2
m+13 14
Bit Setting contents
D32003 D32013 m+3 m+13 08 to 10
1:N/1:1 protocol setting (Unit Ver. 1.2 or later only)
1: 1:1 protocol; 0: 1:N protocol
If the Host Link compatible device mode is set between
0 and 2 hex (mode A or B), the setting in this bit is invalid (always 1:N Host Links)
Host Link compatible device mode
0 hex: Default (mode A)
1 hex: Mode A (CS/CJ/C)
2 hex: Mode B (CVM1/CV)
3 hex: Mode C (C200H)
4 hex: Mode D (C500/120)
Setting Examples when Replacing PLCs
A host computer program that has been created using a C500-LK101/201/
103/203 Host Link Unit can be reused in a Serial Communications Board/Unit with Unit Ver. 1.2 or later by making the following settings to enable the 1:1
Host Link protocol.
• 1:N/1:1 Host Link protocol setting: 1 (ON = 1:1 Host Link)
• Host Link compatible device mode setting: 3 hex (mode C (C500/120))
145
Host Link Function for Replacing Existing PLCs
Section 4-6
146
SECTION 5
Using Protocol Macros
This section describes the procedure and other information required to use protocol macros.
5-1 Overview of the Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-1 Protocol Macro Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-1-2 Using the Protocol Macro Function . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2-2 Setup Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-1 Auxiliary Area Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3-3 Software Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-1 Executing Communications Sequences . . . . . . . . . . . . . . . . . . . . . .
5-4-2 Ladder Program Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4-3 Ladder Program Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5 Simple Backup Function (Backup of Protocol Macro Data) . . . . . . . . . . . . .
5-6 Enhanced Protocol Macro Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6-1 Data Exchange Timing for Link Words . . . . . . . . . . . . . . . . . . . . . .
5-6-2 Clearing/Holding Contents of Reception Buffer in Full-duplex Mode 194
5-6-3 High-speed Baud Rate for Protocol Macro Mode . . . . . . . . . . . . . . 195
147
Overview of the Protocol Macro Functions
Section 5-1
5-1 Overview of the Protocol Macro Functions
5-1-1 Protocol Macro Functions
The protocol macro function is used to control devices by using the
PMCR(260) instruction in the ladder program to execute the data communications sequences (protocols) with the various communications devices, such as general-purpose devices, connected to the RS-232C or RS-422A/485 port.
Standard system protocols are provided in the Serial Communications Board or Unit for controlling OMRON devices (such as Digital Controllers and Temperature Controllers).
Using the Protocol Support Tool called the CX-Protocol, the protocol macro function can be used to create new protocols for commercially available measuring instruments and devices, and to create protocols by modifying one of the standard system protocols. The standard system protocols are also provided with the CX-Protocol.
For details on the use of the CX-Protocol and the protocol macro function, refer to the CX-Protocol Operation Manual (W344).
5-1-2 Using the Protocol Macro Function
The following three methods are available for using the protocol macro function.
Using the Standard
System Protocols
CPU Unit
Sequence number
When connecting OMRON devices, data is sent and received between the
CS/CJ-series CPU Unit and these devices by specifying the sequence number of the standard system protocol provided in the Serial Communications
Board, Serial Communications Unit, and CX-Protocol, and executing the sequence using the PROTOCOL MACRO instruction (PMCR(260)).
Serial Communications Board or Unit
Standard system protocol
Sequence No. 001
Messages
* Send/receive messages are stored in the area one or more words after the send data address or the receive data address specified in the
PMCR(260) instruction.
Sequence No. specification
Step 0
Step 1
OMRON devices
I/O memory Shared memory
I/O refreshing
Modifying Standard
System Protocols
Note The devices for which standard system protocols are provided are listed
below. For details, refer to 5-4 Using Protocol Macros.
Digital Controllers (E5
@K, ES100@), Temperature Controllers (E5ZE,
E5
@J), Intelligent Signal Processors (K3T@), Bar Code Readers (V500/
V520), Laser Micrometers (3Z4L), Visual Inspection Units (F200/F300/
F350), ID Controllers (V600/V620), Hayes Modem AT Command, and devices supporting the CompoWay/F protocol.
When connecting OMRON devices, if there is no standard system protocol or you wish to modify part of the protocol, use the CX-Protocol to modify the standard system protocol, transfer this as a separate communications
148
Overview of the Protocol Macro Functions
Section 5-1
sequence to the Serial Communications Board or Unit, and execute the
PMCR(260) instruction.
CPU Unit
Sequence number
I/O memory
Modifying and transferring standard system protocols
Serial Communications Board or Unit
Sequence No. specification
Modified standard system protocol
Step 0
Step 1
Step 2
Command execution (SEND, RECV, SEND&RECV)
Messages
RS-232C or RS-422A/485
General-purpose external device
Shared memory
I/O refreshing
Creating a New Protocol
When connecting a general-purpose external device that has an RS-232C or
RS-422A/485 port, use the CX-Protocol to create a new protocol containing the communications specifications for the general-purpose external device, transfer these specifications to the Serial Communications Board or Unit, and execute the PMCR(260) instruction.
CPU Unit
Sequence number
I/O memory
Creating and transferring a new protocol
Serial Communications Board or Unit
Sequence No. specification
Newly created protocol
Step 0
Step 1
Step 2
Command execution (SEND, RECV, SEND&RECV)
Messages
RS232C or RS-422A/485
General-purpose external device
Shared memory
I/O refreshing
In this manual, the protocol structure is explained in simple terms, and examples are given of the use of the PMCR(260) instruction when controlling
149
Overview of the Protocol Macro Functions
Section 5-1
OMRON devices using standard system protocols. For details on the protocols, the method of modifying the standard system protocols, and the method of creating new sequences, refer to the CX-Protocol Operation Manual
(W344).
5-1-3 Protocol Structure
Protocols consist of communications sequences. A sequence consists of steps. These steps can be repeated, or they can be branched or ended depending on the responses received. A step consists of a command, send/ receive messages, processing results, and the next process (which depends on the processing results).
Example: Reading the process values for a Temperature Controller
Protocol
Communications sequence
Step 0
Step 1
Transmission of process value reading message and reception of response message
Messages
A protocol consists of processing sequences (such as reading the process value for a Temperature Controller) for a general-purpose external device. A sequence consists of a group of steps, each of which consists of a send/ receive/control command, send/receive message, processing result, and a next step that depends on the processing results.
For example, with a sequence that reads the process value for a Temperature
Controller, the sequence sends the send message for the connected Temperature Controller (a character string in which the Process Value Read command is inserted between the header + address and the check code + terminator) and receives the receive message (a character string in which the
Process Value Read command response is inserted between the header + address and the check code + terminator).
Serial
Communications Unit
(CS/CJ Series)
CPU Unit
Command
SEND
(send)
RECV
(receive)
Send message (Example: PROCESS VALUE READ command)
RX00
…
Header Address Send data Check code
Terminator
Receive message (Example: Response)
RX01
…
Header Address Send data Check code
Terminator
RS-232C or
RS-422A/485
Serial Communications Board
(CS Series only)
General-purpose external device
150
Overview of the Protocol Macro Functions
Section 5-1
Depending on the response received, the user can either choose to resend the same send message (retry processing), or to perform the next process
(for example, read the process value for a Temperature Controller with a different address).
One protocol
Sequence No. 000 to 999
(60 sequences max./protocol)
Transmission control parameter
Link word setting
Send/receive processing monitoring time
Response notification method
Step 0
Step 1
15 steps max.
Step 0
Step 1
15 steps max.
One-step structure
With the SEND, RECV, or
SEND&RECV command
Command (see Note 1)
Messages (see note 2)
Repeated
N (no)
Y
With the WAIT, FLUSH,
OPEN, or CLOSE command
Command
(see note 1)
Next process
Message list (see note 2)
Send message list Normal end
N (error)
Header Address Data Check Terminator
Receive message list
Next process
• Next step
Error processing
• To specified step
• Sequence end
• Sequence interrupt
Header Address Data Check Terminator
Reception matrix list (see note 2)
Reception matrix
Case No. 15
Case No. 00
Receive message Next process
Sequence Parameters
Note
1.
The SEND, RECV, SEND&RECV, WAIT, FLUSH (reception buffer clear),
OPEN (ER-ON), or CLOSE (ER-OFF) commands can be used.
2.
Three types of reception matrix are available for switching the processing, depending on whether the messages are send messages, receive (wait) messages, or multiple receive (wait) messages. Unlike sequences, these matrixes are managed as lists.
Parameter
Transmission control parameters
Meaning
Control methods, such as flow control
Link words Settings for shared words between the PLC and the
Serial Communications Board.
Monitoring time for send/receive processing Monitoring time
Response notification method Timing for writing received data to I/O memory in the
PLC
151
Overview of the Protocol Macro Functions
Step Parameters
Section 5-1
Command
Messages
Retry count
Send wait time
Response write enable (for operand specification)
Next process
Parameter Meaning
One of the following: SEND, RECV,
SEND&RECV, WAIT, FLUSH, OPEN, or
CLOSE
Send message The message sent for SEND.
Repeat counter
Receive message
Send message and receive message
Reception matrix
The expected message for RECV.
The message sent and the expected message for SEND&RECV.
A group of expected messages that can be used to switch to different next processes when RECV or SEND&RECV is used.
The number of times to repeat the step (0 to 255). The repeat counter can be used to change send/receive messages.
Used for SEND&RECV to retry the command for errors (0 to
9).
Used for SEND or SEND&RECV to create a wait time before sending data.
Specification of whether or not to write the received data to memory.
Error processing
Specifies the next step or to end the sequence when the current step is completed normally.
Specifies the next step or to end the sequence when the current step ends in an error.
Note We recommend programming retry processing at any device sending commands in case noise or other factors result in transmission errors.
152
Overview of the Protocol Macro Functions
Section 5-1
Standard System Protocol Example
Process Value Read Sequence for E5
@K Controller Read Protocol
Sequence
Level
Steps
Send message
SD (00) _1
Item
Link words
Transmission control parameters
Response notification method
---
Modem control
Scan
Reception wait time Tr 3 s
3 s Reception finished wait time Tfr
Send finished wait time
Tfs
Step number
Repeat counter
3 s
00
Reset/001
Command
Retry count
Send wait time
Send message
SEND&RECV
3
---
SD (00) _1
Receive message RV (00) _1
Response write enable Write
Next process
Error process
End
Abort
Header <h>
Terminator <t>
Error check code <c>
Length <l>
Address <a>
Message edited
Setting
“@”
[2A0D]
LRC (horizontal parity) (0) (2 bytes of ASCII)
---
$ (R (1) ) ,2)
<h> + <a> + "1" + "00" + "0000" + <c> + <t>
Data
Receive message
RV (00) _1
Header <h>
Terminator <t>
Error check code <c>
Length <l>
Address <a>
Message edited
“@”
[2A0D]
LRC (horizontal parity) (0) (2 bytes of ASCII)
---
& (R (1) ) ,2)
<h> + <a> + "00" + "00" + & (W (1) ,4) + <c> + <t>
Data
DM Area Settings for
Standard System Protocol
The following data is set in the Setup Area in the DM Area for a standard system protocol.
m = D30000 + 100
× unit number
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1
D32000 D32010 m
Port 2
Contents
m + 10 Bits 00 to 04: Communications parameters
Bits 08 to 11: Serial communications mode
Setting for a standard system protocol
Set to match the parameters of the external device.
Set to 6 Hex to specify Protocol Macro Mode.
153
Overview of the Protocol Macro Functions
Section 5-1
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1
D32001 D32011 m + 1
Port 2
m + 11
Contents
Bits 00 to 03: Baud rate
D32008
D32009
D32018
D32019 m + 8 m + 9
Setting for a standard system protocol
m + 18 Bit 15: Transmission method m + 19 Bits 00 to 15: Max. No. of send/ receive bytes
Set to match the baud rate of the external device.
Set to 0 Hex to specify half-duplex.
Set to 03E8 Hex to specify 1,000 bytes.
Handling
Communications
Problems for Standard
System Protocols
The CS/CJ-series PLCs provide standard system protocols to enable communications with OMRON components without having to create communications sequences. The sequences in the standard system protocols can be executed merely by setting operands for the PMCR(260) instruction.
Processing for communications line problems during communications for the standard system protocols are set to normal settings, as shown in the following table. If these settings are not suitable to the application or if improvements are desired, use the CX-Protocol to modify the following settings in the required sequences. For details on the use of the CX-Protocol, refer to the
CX-Protocol Operation Manual (W344). Refer to the appendices for the settings in the standard system protocols.
Level
Sequence parameters
Step parameters
Item
Link words
Transmission control parameters
Response notification method
Possible changes in settings
No reason to change.
Reception wait time Tr The monitoring times are set to 3 seconds
Reception finished for most sequences. The settings are differwait time Tfr ent for send-only and receive-only sequences, as well as for sequences that
Send finished wait require time for responses.
time Tfs
Repeat counter No reason to change.
Command
Retry count
Send wait time
The retry count is general set to 3 retries (4 tries total) for sequences that use the
SEND&RECV command. Different settings are used for sequences that have other commands.
No reason to change.
Send message
Receive message
Response write enable
Next process
Error process
154
Setup Area Allocations
Section 5-2
5-2 Setup Area Allocations
This section explains the Setup Area allocated in the DM Area when a Serial
Communications Board or a Serial Communications Unit is used in protocol macro mode.
5-2-1 Setup Area Words
The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when Protocol Macros are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to unit numbers).
Serial Communications
Boards (CS Series Only)
Setup Area Allocated in the DM Area: D32000 to D32099
Words
D32000 to D32001
D32008 to D32009
D32010 to D32011
D32018 to D32019
D32002 to D32007
D32012 to D32017
D32020 to D32767
Port 1 Settings
Port 2 Settings
Usage
Not used with the protocol macro mode
Reserved for the system
Serial Communications
Units (CS/CJ Series)
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area: m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
DM Area
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599 m to m + 1, m + 8 to m + 9: Port 1 Settings m + 10 to m + 11, m + 18 to m + 19: Port 2 Settings m + 2 to m + 7, m + 12 to m + 17: Not used m + 20 to m + 99: Not used
155
Setup Area Allocations
Section 5-2
5-2-2 Setup Area Allocations
m = D30000 + 100
× unit number
DM Area
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1 Port 2
D32000 D32010 m
Port 1 Port 2
m + 10 15
Bit Setting contents
Port settings
0: Defaults, 1: User settings
12 to 14 Reserved
08 to 11 Serial communications mode
6: Protocol macro
05 to 07 Reserved
04 Start bits 0: 1 bit; 1: 1 bit
(1 start bit is always used regardless of this setting)
03 Data length 0: 7 bits; 1: 8 bits
D32001
D32007
D32008
D32009
D32011
D32017
D32018
D32019 m + 1 m + 7 m + 8 m + 9
02
01
Stop bits
Parity
0: 2 bits; 1: 1 bit
0: Yes; 1: No
00 Parity 0: Even; 1: Odd m + 11 00 to 03 Baud rate (Unit: bps)
0: Default (9,600) 3: 1,200 4: 2,400
5: 4,800 6: 9,600 7: 19,200 8: 38,400
(The following setting can be selected even if protocol macro is set as the serial communications mode: Unit Ver. 1.2 or later only)
9: 57,600 m + 17 08 to 15 Serial Gateway response timeout monitoring time (Unit Ver. 1.2 or later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms m + 18
00 to 07 Serial Gateway send start timeout monitoring time (Unit Ver. 1.2 or later only)
0 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
Unit: 100 ms
15 Transmission method
00 to 14 Reserved
0: Half-duplex; 1: Full-duplex
03 Clearing/holding the contents of the reception buffer in full-duplex mode (Unit Ver. 1.2 or later only)
0: Clear; 1: Hold
02 Link word specification data exchange timing (Unit Ver. 1.2 or later only)
0: On-request I/O refreshing
1: Continuos I/O refreshing
00 to 01 Reserved m + 19 00 to 15 Maximum number of bytes in send/receive data:
00C8 to 03E8 Hex
Port Settings
The setting for the port settings determines if the default settings or user settings will be used for port 1 and port 2. Be sure to use the same settings as the RS-232C port on the host computer connected via the Host Link System.
If the default port settings are specified, then the settings of bits 00 to 04 and the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 9,600 bps, start bits:
1 bit, data length: 7 bits, parity: even, and stop bits: 2 bits.
156
Setup Area Allocations
Section 5-2
If user port settings are specified, set bits 00 to 04 and set the baud rate in
D32001.
Setting Example:
0600 Hex = Protocol macro mode with default port settings and baud rate.
Set the serial communications mode to 6 Hex to use protocol macros.
Serial Communications
Mode
Start Bits, Data Length,
Stop Bits, Parity, and
Baud Rate
If user settings are specified for the port settings, the number of start bits, data length, number of stop bits, parity, and baud rate must be set. The start bits setting, however, will be ignored and 1 start bit will always be used.
Do not set the baud rate setting to between A and F. A setup error will occur if these settings are used, and the default setting of 9,600 bps will be used. Do not use settings 1 and 2, which are reserved for the system.
Serial Gateway Response Timeout Monitoring Time (Unit Ver. 1.2 or Later Only)
The response timeout condition is monitored when a FINS command is converted to the specified protocol and sent.
0: 5 s (default); Setting range: 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The response monitoring time is 5 s when set to the default (0), or can be user-specified in the range 0.1 to 25.5 s by setting between 01 and FF hex.
Serial Gateway Send Start Timeout Monitoring Time (Unit Ver. 1.2 or Later Only)
When converting FINS commands to the specified protocol and sending them during execution of protocol macros, the timeout condition is monitored from when the FINS command is received until the command starts to be sent in the specified protocol.
0: 5 s (default); Setting range: 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The response monitoring time is 5 s when set to the default (0), or can be user-specified in between 0.1 and 25.5 s by setting the time to between 01 to
FF hex.
Transmission Method
Set half-duplex (0) or full-duplex (1) as the transmission mode for the external device.
Note Half-duplex: Allows data to be sent between two Units in one direction only at any one time.
A B or
A B
Full-duplex: Allows data to be exchanged both ways between two Units at the same time.
A B
With half-duplex transmissions, the reception buffer is cleared immediately before the sequence is executed and immediately following SEND completion
(SEND or SEND&RECV command). Therefore, the data received before and during SEND execution cannot be accessed as receive data by the next
RECV command.
Note When using SEND with half-duplex transmission, there is a time lag, t1, between data send processing completion and SEND completion. Therefore, if there is a rapid response from the remote device and a response is returned for SEND after data is sent (communications or other command) and before
SEND is completed, the response during that time cannot be received using half-duplex transmissions. If this problem occurs, use the full-duplex transmissions.
157
Setup Area Allocations
Section 5-2
Also, if the external device is connected using 2-wire connections from an RS-
422A/485 port, send and receive data cannot both be on the same transmission line at the same time. This will create an additional lag time, t2, or 150
µs.
If responses are being received quickly from the external device, i.e., faster than t1 +t2, create a send delay at the external device or take other measures to allow for the lag times.
SEND operation
Data send processing
Data reception
Rapid response t1 t2 = 150
µs
Time lags (see following table)
Data cannot be received during this time.
Reception buffer cleared
Time Lag t1
Baud rate (bps)
1,200
2,400
4,800
9,600
19,200
38,400
57,600
Time lag (
µs)
1,116
578
288
144
73
36
24
With full-duplex mode, the reception buffer is cleared immediately before the sequence is executed. While both the SEND&RECV commands are being executed, data is input into the reception buffer and is used as the macro data.
Timing chart (example) Transmission mode
Full-duplex
(See note 1)
Time reception buffer cleared
Data reception Character trace
communications sequence execution and immediately following SEND completion by the
SEND or
SEND&RECV command
Immediately before communications sequence execution
(See note 2) completion to
RECV completion, or following SEND completion to immediately before SEND execution
All during trace execution
All during communications sequence execution
All during trace execution
Communications sequence
Reception buffer cleared
Data reception
Character trace
Communications sequence
Reception buffer cleared
Data reception
Character trace
RECV
RECV
SEND
(See note 3.)
SEND
RECV
RECV
Note
1.
With full-duplex, RS-232C or RS-422A/485 (1:1 and 4-wire connections) can be used. RS-422A/485 1:N or 2-wire transmissions cannot be used.
2.
The FLUSH command is used to clear the reception buffer, and can be used at any time.
3.
Although the received data is discarded until completion of SEND execution, it is reflected in the character trace.
158
Setup Area Allocations
Section 5-2
Clearing/Holding the
Contents of the
Reception Buffer in
Full-duplex Mode (Unit
Ver. 1.2 or Later Only)
Set to either clear (OFF) or hold (ON) the contents of the reception buffer when the protocol macro starts.
OFF: Clear
When set to clear (OFF), the contents of the reception buffer will be cleared when the protocol macro is executed.
ON: Hold
When set to hold (ON), the contents of the reception buffer will not be lost if data acquisition fails after execution of the protocol macro.
This function prevents loss of data during full-duplex communications.
Data Conversion Timing for Link Word
Specifications (Unit Ver.
1.2 or Later Only)
Set to perform I/O refresh upon request or continuously, as follows:
OFF: On-request I/O refresh (Immediate refresh mode)
Data exchange is performed during I/O refresh when a refresh request is sent to the CPU Unit for each send/receive command that is executed. A time delay will occur after the send command is executed until the actual message is sent when this method is used.
ON: Continuous I/O refresh (Cyclic refresh mode)
During protocol macro execution, I/O refreshing is continuously performed with the CPU Unit, the data in the link word area is refreshed from the CPU
Unit, and the data in the Board/Unit is accessed during SEND/RECEIVE command execution. When the send command is executed with this method, the actual message can be sent immediately.
Maximum Number of
Send/Receive Data Bytes
From 200 bytes up to a maximum of 1,000 bytes can be set in hexadecimal, i.e., between 00C8 Hex and 03E8 Hex. Any setting below 00C8 Hex, will be treated as 00C8 Hex; any setting above 03E8 Hex, will be treated as 03E8
Hex.
Note Flow Control and Maximum Number of Send/Receive Data Bytes
There is a 2.5-Kbyte reception buffer for each serial port in a Serial Communications Board or Unit. When using flow control, initiate flow control after receiving about 2 Kbytes, and then release control after processing all but
0.5 Kbytes of receive data. Up to 1,000 bytes (500 words) of data can be stored for each RECV command if 2 Kbytes of receive data is first stored in the buffer and 1,000 bytes (03E8 Hex) is set as the maximum number of send/ receive data bytes.
159
Setup Area Allocations
RS/CS Flow Control
Half-duplex
Communications
Section 5-2
With CS/CJ-series half-duplex protocol macro communications (see note), or with C200HX/HG/HE protocol macro communications, flow control can be released by turning ON the RS signal (CS signal at the communications partner) while the RECV command is being executed. The timing of this operation is shown below. (Signal names used below are those at the Serial Communications Board.)
PMCR(260) instruction
PMCR(260) instruction
Command
SD signal
RD signal
RS signal
RS turned OFF after 0.1 to 4 ms
RS signal ON while RECV command is executed.
Data received before
SEND is completed is discarded.
Data received while the PMCR(260) instruction is not being executed is discarded (controlled by turning
OFF the RS signal).
The OFF status of the RS signal is maintained after execution of the
PMCR(260) instruction.
Full-duplex Mode
1,2,3...
1.
With protocol communications in half-duplex mode, the RS signal is ON only while the RECV command is being executed.
2.
The receive data (RD signal) from the communications partner is initially stored in the reception buffer.
3.
The data in the reception buffer is analyzed, and a search is performed for data matching an expected message registered with the RECV command.
4.
When matching data is found, the RS signal is turned OFF. The search starts after the final data has been received. It takes between 100
µs and
4 ms from starting the search until the RS signal turns OFF.
5.
While the SEND command is being executed, and while the PMCR(260) instruction is not being executed, the RS signal stays OFF and receive data is discarded.
Note RS/CS flow control in half-duplex mode is supported only by CS-series Serial
Communications Boards/Units manufactured on or after December 20th,
1999. With earlier models, half-duplex mode will operate in the same way as full-duplex mode.
Lot No: 20Z9 Manufactured on December 20th, 1999
The year is indicated with the last digit. In this case, "9" indicates 1999."
Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is "December."
Day of manufacture. In this example, the day is "20."
There is a 2.5-Kbyte reception buffer for each serial port in a CS/CJ-series
Serial Communications Board or Unit. When using flow control, initiate flow control after receiving about 2 Kbytes, and then release control after processing all but 0.5 Kbytes of receive data. Up to 1,000 bytes (500 words) of data
160
Auxiliary Area and CIO Area Allocations
Command
Section 5-3
can be stored for each RECV command if 2 Kbytes of receive data is first stored in the buffer and 1,000 bytes (03E8 Hex) is set as the maximum number of send/receive data bytes. The timing of this operation is shown below.
(Signal names used below are those at the Serial Communications Board.)
PMCR(260) instruction PMCR(260) instruction
Receive Send Receive Send Receive
SD signal
RS turned ON when only 0.5 Kbytes in buffer.
RD signal
RS signal
RS signal turned OFF when 2 Kbytes of data accumulates in reception buffer.
Data received from the end of the last RECV command until the next
PMCR(260) execution is discarded.
The RS signal does not operate.
1,2,3...
1.
With full-duplex protocol communications, the RS signal is turned OFF when 2 Kbytes of data has been stored in the reception buffer (i.e., with
0.5 Kbytes remaining).
2.
The receive data (RD signal) from the communications partner is initially stored in the reception buffer.
3.
The data in the reception buffer is analyzed, and a search is performed for data matching an expected message registered with the RECV command.
4.
When matching data is found, all the previous data is deleted from the reception buffer.
5.
If this results in the amount of data stored in the reception buffer dropping to less than 0.5 Kbytes (i.e., more than 2 Kbytes remaining), the RS signal is turned ON.
6.
Data that is received while the PMCR(260) instruction is not being executed is discarded.
7.
In full-duplex mode, the data left over after the analysis performed with the last RECV command and any subsequent data received before the next
PMCR(260) execution is discarded. During this interval, RS flow control cannot be used.
Note Full-duplex mode is supported only by the CS/CJ Series.
5-3 Auxiliary Area and CIO Area Allocations
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and the Software Switches and Status Area allocated in the CIO Area.
5-3-1 Auxiliary Area Allocations
Port 1 and Port 2 Port
Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
161
Auxiliary Area and CIO Area Allocations
Section 5-3
Inner Board Error
Information (CS-series
Serial Communications
Board Only)
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
Serial Communications Boards (CS Series Only)
Word
A636
Bit
03 to 15 Reserved
02
01
00
Contents
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved
Note
Serial Communications Boards (CS/CJ Series) n = A620 + unit number n
Words Bit
03 to 15 Reserved
02
Contents
1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved
A424 contains error information for the Serial Communications Board.
Word Bit
A424 12 to 15 Non-fatal
11 errors
(Note 1)
10
04
03
02
01
00
09
08
07
06
05
Fatal errors
(Note 2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3 or 4 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO
1919 in the CIO Area.
1: Protocol data error (SUM error); 0: Normal
1: Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
Reserved
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to SECTION 11 Troubleshooting and Maintenance.
162
Auxiliary Area and CIO Area Allocations
Section 5-3
Auxiliary Area Bit Descriptions
Name Address Meaning
Board/Unit
Watchdog
Timer Error
Flags
Inner Bus
Error Flag
Protocol
Macro Execution Error Flag
Port 1/2 Port
Settings
Change Bits
Board: A42400
Units: A40207 and A417
(Unit numbers 0 to F correspond to bits 00 to 15 of A417.)
Board: A42401
(No flags are provided for
Units.)
Board: A42410
(No flags are provided for
Units.)
Board: A63601 and A63602
Units: A620 + unit number, bits
01 and 02
The corresponding flag will turn ON when the Board or Unit is faulty. If the problem persists even when the Board or Unit is remounted or used with another CPU Unit, replace the Board or
Unit.
The flag will turn ON when an error occurs in the Inner bus. If the problem persists even when the Board is remounted or used with another CPU
Unit, replace the Board.
The flag will turn ON when and attempt was made to read or write data at an illegal address (error code 3) or a protocol macro syntax error occurred (error code
4).
The communications port setting can be changed and the port restarted by turning on the corresponding bit.
Initialize
Startup
(see note)
Timing
ON
At error
OFF
Startup
Startup
Sequence execution or user manipulation tings have been changed and the port has been restarted
Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming
Console or other Programming Device.
5-3-2 CIO Area Allocations
The following areas are allocated as the status area and the software switch area, which show the status of the Serial Communications Board and Serial
Communications Unit or the error information.
Serial Communications
Boards (CS Series Only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for Software
Switches and Status Area. Only the words shown in the following table are used for Protocol Macros.
Inner Board CIO Area
CIO 1900 to CIO 1999
Words
CIO 1900
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Usage
Software switches
Board status
Port 1 status
Port 2 status
Reserved for the system
163
Auxiliary Area and CIO Area Allocations
Section 5-3
Serial Communications
Units (CS/CJ Series)
Words CIO 1500 to CIO 1899 of the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each unit number is allocated
25 words. With the protocol macro mode, the words shown in the following table are used for the Software Switches and Status Area.
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
CIO 1675 to CIO 1694
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
Unit No. B CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E CIO 1850 to CIO 1874
Unit No. F CIO 1875 to CIO 1899
n: Software switches (port 1/Port 2) n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
5-3-3 Software Switches
The Software Switches are used from the CPU Unit to control the Serial Communications Board and Serial Communications Unit.
Software Switches are used to output control signals from the CPU Unit to the
Serial Communications Board or Unit.
164
Auxiliary Area and CIO Area Allocations
Section 5-3
n = CIO 1500 + 25
× unit number
CIO 1900
Words
Boards
(CS Series
Only)
n
Unit
(CS/CJ
Series)
11
10
09
08
07
06
05
04
15
14
13
12
03
02
01
00
Bit
Port 2
Port 1
Contents
Reserved
Used for loopback tests
Reserved
Serial Gateway Prohibit Switch (protocol macros)
0: Serial Gateway not prohibited; 1: Serial Gateway prohibited
Abort Switch
One-shot Trace Switch
Continuous Trace Switch
Wait Release Switch
Reserved
Used for loopback tests
Reserved
Serial Gateway Prohibit Switch (protocol macros)
0: Serial Gateway not prohibited; 1: Serial Gateway prohibited
Abort Switch
One-shot Trace Switch
Continuous Trace Switch
Wait Release Switch
Software Switches
Bit
CIO 1900
CIO n
15 14 13 12 11 10 09 08 07 06 05 04 03
0 0 0 0
02 01 00
Port 1 Wait Release Switch
Port 1 Continuous Trace Switch
Port 1 One-shot Trace Switch
Port 1 Abort Switch
Port 1 Serial Gateway Prohibit Switch (protocol macro)
Port 1 Loopback Test Switch
Port 2 Wait Release Switch
Port 2 Continuous Trace Switch
Port 2 One-shot Trace Switch
Port 2 Abort Switch
Port 2 Serial Gateway Prohibit Switch (protocol macro)
Port 2 Loopback Test Switch
165
Auxiliary Area and CIO Area Allocations
Section 5-3
Software Switch
Descriptions
The Software Switches function as described in the following table.
Name Bits in CIO 1900 or CIO n
Meaning
Serial Gateway Prohibit
Switch
Abort Switch
One-shot
Trace Switch
(Note 2)
Bits 04 and 12
Bits 03 and 11
Bits 02 and 10
The Serial Gateway (mode) is prohibited during protocol macro processing when this Switch turns ON.
The Serial Gateway is no longer prohibited when the Switch is turned OFF.
Protocol processing will be aborted when the switch is turned ON. (Processing may be completed if the Switch is turned ON too late.)
The CX-Protocol will start a one-shot trace when the Switch turns ON. The trace is ended when the Switch is turned OFF.
The Board or Unit will be cleared when the trace buffer becomes full.
The CPU Unit will manipulate the Oneshot Trace Switch and Continuous
Trace Switch when trace operations are performed from the CX-Protocol. Do not manipulate these switches directly from a ladder diagram.
Continuous
Trace Switch
(Note 2)
Wait Release
Switch
Bits 01 and 09
Bits 00 and 08
(Not supported by
C200HX/HG/HE)
The CX-Protocol will start a continuous trace when the Switch turns ON. The trace is ended when the Switch is turned OFF.
Standby status for the WAIT command will be released when the switch is turned ON.
Initialize
Startup
Startup
(Note 1)
Timing
ON
Manipulated by user
OFF
Manipulated by user
Manipulated by user
Manipulated by system
Manipulated by CX-Protocol
At end of one-shot trace
Manipulated by CX-Protocol
Manipulated by CX-Protocol
Manipulated by user
At end of
WAIT command
Note
1.
The Software Switches will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONI-
TOR modes, when STUP(237) is executed, when the Board or Unit is restarted, or when the communications port is reset.
2.
The first switch of the One-shot Trace Switch and Continuous Trace Switch to turn ON will determine the trace operation. If a Trace Switch turns ON when a trace operation is already in progress, the switch will not be effective even when the current trace operation is completed unless the switch is first turned OFF. If the One-shot Trace Switch and Continuous Trace
Switch turn ON simultaneously, the Continuous Trace Switch will take priority.
5-3-4 Status Area
The Status Area is used to input status information from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status.
166
Auxiliary Area and CIO Area Allocations
Section 5-3
n = CIO 1500 + 25
× unit number
Boards
(CS Series
Only)
Words
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO 1901 n + 1
CIO 1902
CIO 1903
CIO 1904
CIO
1905
CIO
1906
CIO
1915
CIO
1916
13
Bit
n + 2
02 to 15 Reserved
01 1: Error log EEPROM error
00 1: Protocol data error
00 to 15 Reserved n + 3 n + 4
00 to 15 Reserved
00 to 15 Reserved n + 5 n + 15 12 to 15 Port setting
08 to 11 status
05 to 07
Setup settings
04
03
02
01
00 n + 6 n + 16 15
14
Port setting status
Hardware settings
(See note 2)
Contents
0: Error log EEPROM normal
0: Protocol data normal
Serial communications mode: Always 6 Hex
(see note)
Baud rate (Note 1)
Reserved: Always 0
Start bits: Always 1
Data length: 7 or 8 bits (Note 1)
Stop bits: 1 or 2 bits (Note 1)
Parity: Yes/No (Note 1)
Parity: Even/Odd (Note 1)
0 No 0 RS-232C 1 RS-422A/485 1 Reserved
0 1 0 1
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: System Setup error; 0: System Setup normal
CIO
1907
CIO
1917
12 to 02
01
00 n + 7 n + 17 15 to 11 Commu-
10 nications status
09
08
1: Port operating; 0: Port stopped
Reserved
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive
Reserved
07
06
05
04
03
Transmission control signal status
1: Local Unit busy receiving (Flow control)
0: Local Unit ready to receive
DTR (ER) signal 1: High, 0: Low
DSR (DR) signal 1: High, 0: Low
Reserved
CTS (CS) signal 1: High, 0: Low
RTS (RS) signal 1: High, 0: Low
167
Auxiliary Area and CIO Area Allocations
Section 5-3
Words Bit Contents
Boards
(CS Series
Only)
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO
1908
CIO
1918 n + 8 n + 18 15
14
13
12
Transmis sion error status
1: Transmission error
0: No transmission error
1: Tfs (send finished monitoring time) exceeded
0: Normal
1: Tfr (receive finished monitoring time) exceeded
0: Normal
1: Tr (receive wait monitoring time) exceeded
0: Normal
Number of retries: 0 to 9: 0 to 9 hex 08 to 11 Number of retries
07
06
05
04
03
Transmis sion error status
1: FCS check error or Serial Gateway transmission path error;
0: FCS check normal
1: Command error; 0: No command error
1: Timeout (Tfs, Tfr, or Tr) error or Serial Gateway transmission timeout or Serial Gateway response timeout; 0: Normal
1: Overrun error; 0: Normal
1: Framing error; 0: Normal
02
00, 01
1: Parity error; 0: Normal
Reserved
00 to 15 Protocol status (See Protocol Status on page 83.) CIO
1909 to
CIO
1914
CIO
1919 to
CIO
1924 n + 9 to n + 14 n + 19 to n + 24
Note
1.
The settings in the Setup Area are reflected here. The default settings will be used and will be stored here if a setup error occurs.
2.
With a Board, the same bit is used as for A42409 (protocol data error) of the Auxiliary Area.
168
Auxiliary Area and CIO Area Allocations
Section 5-3
Status Area Descriptions
Name Address
Error log data error
Protocol data error
Board:
CIO 190101
Unit: n + 1 bit 01
Board:
CIO 190100
Unit: n + 1 bit 00
Board only:
A42409
Setup error Board:
CIO 190601 (port 1)
CIO 191601 (port 2)
Meaning
If a write to EEPROM fails for the error log, it is assumed the EEPROM is beyond its useful life and this flag is turned ON. With a
Serial Communications Unit, the ERC indicator will also light. Although this has no effect on communications and other functions, replace the Board or Unit promptly for ease of maintenance.
Initialize
Startup
(see note)
This flag is turned ON if an error is detected in the protocol data SUM check when the power is turned ON. With a Serial Communications Board, the ERR/ALM indicator on the
CPU Unit will also flash and the RDY indicator will flash at 1-second intervals. A42409
(Board only) of the Auxiliary Area will also turn ON.
With a Serial Communications Unit, the RDY and ERC indicator will flash.
This error may occur if the communications connector becomes disconnected or the
PLC power is turned OFF during protocol data transfer. Use the CX-Protocol to transfer of the protocol data again.
This flag is turned ON if a Setup error occurs in the allocated DM Area, After changing the
Setup, turn ON the power again, restart the
Board/Unit, restart the port, or execute the
STUP(237) instruction.
Startup
(see note)
Startup
(see note)
Timing
ON
At error
At error
At error
Port operating
Unit: n + 6 bit 01 (port 1) n + 16 bit 01 (port 2)
Board only:
A42408 (not available for Unit)
Board:
CIO 190600 (port 1)
CIO 191600 (port 2)
ON when the port can operate correctly.
OFF when protocol macro data is being transferred.
Startup
(see note)
At error
Unit: n + 6 bit 00 (port 1) n + 16 bit 00 (port 2)
Remote Unit receive busy/receive wait
Board:
CIO 190710 (port 1)
CIO 191710 (port 2)
Unit: n + 7 bit 10 (port 1) n + 17 bit 10 (port 2)
OFF
Startup
When protocol data has been successfully transferred
Startup
(see note)
After protocol data has been transferred
This flag indicates the receive status of a remote Unit during SEND when Xon/Xoff flow control or RS/CS flow control is set in the transmission control parameters. When
Xon/Xoff flow control is set, the reception buffer is cleared when the sequence starts, so the status area is set to remote Unit receive wait (0).
1: Remote Unit receive busy
(Reception is disabled because the reception buffer is full.)
0: Remote Unit receive wait (Reception is enabled.)
Startup
(see note)
When status is read
After busy status has been released
169
Auxiliary Area and CIO Area Allocations
Section 5-3
Name
Local Unit receive busy/receive wait
Transmission control signal status
Board:
Address
CIO 190708 (port 1)
CIO 191708 (port 2)
Unit: n + 7 bit 08 (port 1) n + 17 bit 08 (port 2)
Board:
CIO 1907 bits 03, 04,
06, 07 (port 1)
CIO 1917 bits 03, 04,
06, 07 (port 2)
Meaning
This flag indicates the receive status of a local Unit (Board or Unit) during RECV when
Xon/Xoff flow control is set in the transmission control parameters.
1: Local Unit receive busy (Reception is disabled because the reception buffer is more than 4/5 (= 2 Kbytes) full.)
0: Local Unit receive wait (Reception is enabled because the reception buffer is less than 1/5 (= 0.5 Kbytes) full.)
This bit is cleared when the power is turned
ON, at port restart by the STUP(237) instruction or by the Port 1 or Port 2 Port Settings
Change Bit (Auxiliary Area), or when the next sequence is started.
The status of each transmission control signal (ER, DTR, CTS, and RTS) for each port is always read to these flags.
1: High, 0: Low
Initialize
Startup
Startup
Timing
ON
When status is read
OFF
After busy status has been released
When status is read
After busy status has been released
Unit: n + 7 bits 03, 04, 06,
07 (port 1) n + 17 bits 03, 04, 06,
07 (port 2)
170
Auxiliary Area and CIO Area Allocations
Section 5-3
Name
Transmission error status/ number of retries
Address
Board:
CIO 1908 bits 00 to
15 (port 1)
CIO 1918 bits 00 to
15 (port 2)
Unit: n + 8 bits 00 to 15
(port 1) n + 18 bits 00 to 15
(port 2)
Port setting status
Board:
CIO 1906 bits 00 to
15 (port 1)
CIO 1916 bits 00 to
15 (port 2)
Unit: n + 6 bits 00 to 15
(port 1) n + 16 bits 00 to 15
(port 2)
Meaning
When an error occurs during transmission, the corresponding flag (in bits 02 to 07 or 12 to 15) is turned ON.
The number of retries is stored in bits 08 to
11.
Note 1: The Transmission Error Flag (bit 15) is turned ON only when the protocol macro has moved to error processing due to an error in bits 00 to 14.
2: The number of retries in bits 08 to 11 is not equal to the number of times processing is performed when an error occurs. It is the set number of retries.
When communications are restored by protocol macro retry processing, the error in bits
02 to 07 or 12 to 15 is stored. The Transmission Error Flag (bit 15), however, will remain
OFF. If another error occurs during retry processing, the status of the bit indicating the cause will be held.
The following are read in port setting status:
The serial communications modes and communications specifications set in the Setup
Area (D32000, D32010, m, or m+10).
The ports and the terminating resistance hardware settings.
Setup errors, and Port Operating/Stopped
Flags.
In Protocol Macro mode, the port will be stopped if a protocol data error occurs while protocol data is being transferred. If there is no protocol data error after the protocol data has been transferred, the flag will be turned
ON.
Initialize
Startup
Startup
Timing
ON
At error
When status is read
OFF
When sequence begins
When protocol data has been successfully transferred
Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming
Console or other Programming Device.
Protocol Macro Function
With the protocol macro function, each port is provided with a reception buffer that will hold 2.5 Kbytes max. The reception buffer can be used to hold a large quantity of data when it is being received at once, or when the communications sequence is waiting due to the WAIT command.
If the protocol macro function is used and receive operations are performed when the reception buffer is full, the receive data will overwrite the 2.5 Kbytes of previously received data in the buffer. Therefore, always set flow control when performing these operations.
Overrun Errors, Framing Errors, Parity Errors and Error Flags
If an overrun error, framing error, or parity error is detected when the protocol macro function is being used, the receive data will be stored in the buffer with the error status included. The corresponding error flags will turn ON or OFF according to the following conditions.
171
Auxiliary Area and CIO Area Allocations
Section 5-3
Error Data In Data Agreeing with Expected Receive Message
When RECV is executed, an expected receive message is searched for in the reception buffer. If the data that has been received agrees with an expected receive message, it is processed as receive data. If error details are included in the receive data, the corresponding error flags will turn ON.
The following example shows when 100 bytes of data is received that agrees with an expected receive message.
(P)
100 bytes
Error Flag ON
(P)
P: Parity error
Data Not Agreeing with Expected Receive Message
If error details are included in data that do not agree with an expected receive message, the data will simply be discarded and the error flag status will remain unchanged. For trace information, all error details in the reception buffer will be stored within capacity for the trace data.
The following example shows when a parity error occurs for data that does not agree with an expected receive message.
(P)
Data discarded
(P)
<h>
Error flags remain unchanged
<t>
Protocol Status
The information shown in the following table is input from the Board or Unit to the Protocol Status Words in the CPU Unit. n = CIO 1500 + 25
× unit number
Bit Setting contents
Boards
(CS Series Only)
Port 1
Words
Port 2 Port 1
Unit
(CS/CJ Series)
Port 2
CIO
1909
CIO
1919 n + 9 n + 19
CIO
1910
CIO
1920 n + 10 n + 20
11
10
09
08
15
14
13
12
Port
Operating
Status
Protocol Macro Executing Flag
Step Error Processing Flag
Abort Flag
Tracing Flag
Sequence End Completion Flag
Sequence Abort Completion Flag
Sequence Wait Flag
Serial Gateway Prohibited Flag (protocol macros)
1: Prohibited; 0: Not prohibited
04 to 07
03 to 00
Reserved
Error codes
15 to 12 Reserved
11 to 00 Communications Sequence No.
000 to 999 (000 to 3E7 hex)
172
Auxiliary Area and CIO Area Allocations
Section 5-3
Boards
(CS Series Only)
Port 1
CIO
1911
Port 2
CIO
1921
Words
Unit
(CS/CJ Series)
Port 1
n + 11
Port 2
n + 21
CIO
1912
CIO
1913
CIO
1914
CIO
1922
CIO
1923
CIO
1924 n + 12 n + 13 n + 14 n + 22 n + 23 n + 24
Bit Setting contents
15 to 12 Reserved
11 to 08 Executed Step No. (code)
0 to 15 (0 to F hex)
07 to 04 Reserved
03 to 00 Executed Reception Case No. (code)
0 to 15 (0 to F hex)
15 to 00 Executed Reception Case No. Flag
No. 0 to 15: Correspond to bits 00 to 15
15 to 00 Executed Step No. Flag
No. 0 to 15: Correspond to bits 00 to 15
15 to 08 Repeat Counter Setting Value
1 to 255 (01 to FF hex) (see note)
07 to 00 Repeat Counter Present Value
1 to 255 (01 to FF hex) (see note)
Note When the repeat counter is used to read words and 0 is read, 0 will be stored and the step will be skipped.
Bit
CIO 1909 (port 1) or
CIO 1919 (port 2)
15 14 13 12 11 10 09 08 07 06 05 04 03
0 0 0 0
02 01 00 n + 9 (port 1) or n + 19 (port 2)
Error code
Serial Gateway Prohibit Flag
(protocol macro)
Sequence Wait Flag
Sequence Abort Completion Flag
Sequence End Completion Flag
1: Prohibited
0: Not prohibited
1: Sequence wait status
0: Other than above
1: Sequence aborted
0: Other than above
1: Sequence ended
0: Other than above
Tracing Flag
1: Trace executing
0: Other than above
Abort Flag
1: Protocol macro processing aborted
0: Other than above
Step Error Processing Flag
Protocol Macro Executing Flag
1: Step processing error
0: Step processing normal
1: Protocol macro executing
0: Protocol macro executed
173
Auxiliary Area and CIO Area Allocations
Section 5-3
Name
Protocol
Macro Executing Flag
Step Error
Processing
Flag
Address
Board:
CIO 190915 (port 1)
CIO 191915 (port 2)
Unit: n + 9 bit 15 (port 1) n + 19 bit 15 (port 2)
Board:
CIO 190914 (port 1)
CIO 191914 (port 2)
Unit: n + 9 bit 14 (port 1) n + 19 bit 14 (port 2)
Abort Flag Board:
CIO 190913 (port 1)
CIO 191913 (port 2)
Protocol Status Area
Meaning
This flag is turned ON when a PMCR(260) instruction (sequence) is executed. The flag remains OFF when execution fails.
When the sequence is completed and receive data is written, the flag is turned OFF after all the receive data has been written to
I/O memory.
This flag is turned OFF when the sequence is completed (either when it is ended by End, or when it is ended by Abort).
When the scan response notification method is set for the sequence, first a check is made to see if the received data has been written to I/O memory before the Protocol Macro
Executing Flag is turned OFF.
This flag is turned ON when a step has ended abnormally. It is turned OFF if the step ends normally as a result of a retry.
1: Step ended abnormally
0: Step ended normally
Initialize
Startup
(see note)
Startup
(see note)
This flag is turned ON when processing is ended using the Abort Switch from the user program. When the Abort Switch is turned
ON at the end of a sequence, the sequence may end with either End or Abort status.
Startup
(see note)
Unit: n + 9 bit 13 (port 1) n + 19 bit 13 (port 2)
Tracing Flag Board:
CIO 190912 (port 1)
CIO 191912 (port 2)
Depending on the instruction from the CX-
Protocol, this flag is turned ON while timeseries data for send and receive messages is being traced.
Startup
(see note)
Sequence
End Completion Flag
Unit: n + 9 bit 12 (port 1) n + 19 bit 12 (port 2)
Board:
CIO 190911 (port 1)
CIO 191911 (port 2)
Sequence
Abort Completion Flag
Unit: n + 9 bit 11 (port 1) n + 19 bit 11 (port 2)
Board:
CIO 190910 (port 1)
CIO 191910 (port 2)
Unit: n + 9 bit 10 (port 1) n + 19 bit 10 (port 2)
This flag is turned ON when a sequence is completed for the next process or for an error process with an END command.
When a sequence has ended normally, setting END (ABORT when the sequence has ended abnormally) enables this flag to be used to determine whether or not the sequence execution has ended normally.
1: Sequence ended
0: Sequence not ended
This flag is turned ON when a sequence is ended for the next process or for an error processing with an ABORT command.
1: Sequence aborted
0: Sequence not aborted
Startup
(see note)
Timing
ON
When command is executed
OFF
When command has finished executing
When verification error occurs after receiving
When sequence starts
When a forced abort occurs
When trace begins
When sequence starts
When sequence starts
When sequence ends.
When sequence starts, and when trace ends.
When sequence aborts
When sequence starts
174
Auxiliary Area and CIO Area Allocations
Section 5-3
Name
Sequence
Wait Flag
Serial Gateway Prohibited Flag
Protocol
Macro Error
Code
Communications
Sequence
No.
Board:
Address
CIO 190909 (port 1)
CIO 191909 (port 2)
Unit: n + 9 bit 09 (port 1) n + 19 bit 09 (port 2)
CIO 190908
CIO 191908 n + 9 bit 08 n + 19 bit 08
Board:
CIO 1909 bits 00 to
03 (port 1)
CIO 1919 bits 00 to
03 (port 2)
Unit: n + 9 bits 00 to 03
(port 1) n + 19 bits 00 to 03
(port 2)
Board:
CIO 1910 bits 00 to
11 (port 1)
CIO 1920 bits 00 to
11 (port 2)
Meaning
This flag is turned ON when a sequence is waiting due to the WAIT command. Waiting is released when the Wait Release Switch is turned ON in the ladder program, and the sequence will move to the next step.
Make sure to set the Wait Release Switch from the ladder program to turn ON the switch. If the Forced Set Key on Programming Console is used, the Wait Release
Switch will remain ON, and may stop the protocol macro function from being able to turn
OFF the flag.
Initialize
Startup
(see note)
This flag is turned ON when the Serial Gateway (mode) is prohibited due to the status of the Serial Gateway Prohibit Switch in the user program. This flag turns OFF when the
Serial Gateway is not prohibited.
The list of error codes is provided at the end of this table on page 177.
If a Serial Communications Board is used and either error code 3 (data read/write area exceeded error) or 4 (protocol data syntax error) is stored, A4241 (protocol macro syntax error) will be turned ON, the ERR/ALM indicator on the CPU Unit will flash, and a non-fatal error will occur. If a Serial Communications Unit is used, the ERC indicator will flash. Only error codes 0, 2, 3, and 4 are used.
When an error occurs, the error code is held until the next sequence starts.
The error code is cleared when the
STUP(237) instruction is executed, when the
Unit/Board is restarted, or when the next sequence execution starts.
When a Board is used, clear the non-fatal error resulting from error codes 3 and 4 by removing the cause of the error, and then clear the error display by executing the next sequence or the STUP(237) instruction, by restart, or by switching the CPU Unit to PRO-
GRAM mode.
The current communications sequence number is set when the sequence execution starts. This number does not change when a sequence number error (error code 2) occurs.
Startup
Startup
(see note)
Startup
(see note)
Timing
ON
When
WAIT command is executing
OFF
When Wait
Release
Switch is
ON, and when sequence starts
When instruction is executing
At error
When sequence starts
When instruction execution is completed
When sequence starts
None
Unit: n + 10 bits 00 to 11
(port 1) n + 20 bits 00 to 11
(port 2)
175
Auxiliary Area and CIO Area Allocations
Section 5-3
Name
Executed
Step No.
(code)
Address
Board:
CIO 1911 bits 08 to
11 (port 1)
CIO 1921 bits 08 to
11 (port 2)
Meaning
Step numbers 0 to 15 (0 to F hex) are stored for the steps for which execution has been completed.
Initialize
Startup
(see note)
Timing
ON
When step is executed
OFF
When sequence starts
Executed
Reception
Case No.
(code)
Executed
Reception
Case No.
Flags
Executed
Step No.
Flags
Unit: n + 11 bits 08 to 11
(port 1) n + 21 bits 08 to 11
(port 2)
Board:
CIO 1910 bits 00 to
03 (port 1)
CIO 1920 bits 00 to
03 (port 2)
Unit: n + 10 bits 00 to 03
(port 1) n + 20 bits 00 to 03
(port 2)
Board:
CIO 1912 bits 00 to
15 (port 1)
CIO 1922 bits 00 to
15 (port 2)
Unit: n + 12 bits 00 to 15
(port 1) n + 22 bits 00 to 15
(port 2)
Board:
CIO 1913 bits 00 to
15 (port 1)
CIO 1923 bits 00 to
15 (port 2)
Unit: n + 13 bits 00 to 15
(port 1) n + 23 bits 00 to 15
(port 2)
Reception matrix case numbers 0 to 15 (0 to
F hex) are stored for which reception has been completed. The number is cleared when the sequence execution starts, when the STUP(237) instruction is executed, and at restarts.
The Executed Reception Case No. is stored only when the reception matrix is set using the RECV or SEND&RECV command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed.
Startup
(see note)
Reception matrix case numbers 0 to 15 for which reception has been completed correspond to individual bits (00 to 15), and are turned ON to indicate execution. The numbers are cleared when the sequence execution starts, when the STUP(237) instruction is executed, at restarts, and when the execution of each step starts.
The reception matrix case number can be checked from the ladder program when the
WAIT command is executed or when the sequence is ended after the reception matrix
RECV command is executed.
The Executed Reception Case No. Flag in the bit corresponding to the stored case number will be turned ON only when the reception matrix is set for the RECV or
SEND&RECV command. If a reception matrix is not set, the case number will be set to 0 (cleared) when another command is executed.
Startup
(see note)
Case numbers 0 to 15 for the steps for which execution has been completed correspond to individual bits (00 to 15), and are turned ON in ascending order. Once a bit has been executed, the bit corresponding to the executed step is turned ON in ascending order to hold the bit ON during the sequence (and after completion).
Startup
(see note)
When matrix is received
When matrix is received
When sequence starts
When sequence starts
When step is executed
When sequence starts
176
Auxiliary Area and CIO Area Allocations
Section 5-3
Name Address
Repeat
Counter Set
Value
Board:
CIO 1914 bits 08 to
15 (port 1)
CIO 1924 bits 08 to
15 (port 2)
Meaning
The number of times a step is repeated is set in these bits.
Initialize
Startup
(see note)
Timing
ON
When step starts
OFF
When sequence starts
Repeat
Counter
Present
Value
Unit: n + 14 bits 08 to 15
(port 1) n + 24 bits 08 to 15
(port 2)
Board:
CIO 1914 bits 00 to
07 (port 1)
CIO 1924 bits 00 to
07 (port 2)
Unit: n + 14 bits 00 to 07
(port 1) n + 24 bits 00 to 07
(port 2)
The repeat counter variable N is set. The value is cleared when the sequence execution starts, when the STUP(237) instruction is executed, and at restarts.
The present value N varies according to the method used to initialize the value. For resets, the variable N is set to 0 when the step is started, and the step is executed according to the set number of times. For holds, the variable N for the present value is held when the step is started, and the step is executed according to the set number of times.
If the Repeat Counter Setting Value is set to read word R (see note), and 0 is read, then 0 will be stored and this step will be skipped
(the next process setting will be ignored), and the sequence will move to the next step
(+ 1). For details, refer to the CX-Protocol
Operation Manual (W344).
Startup
(see note)
When repeat counter is refreshed
When sequence starts
Note The flags will also be initialized at the following times: When the operating mode is changed between PROGRAM and RUN or MONITOR modes and when the Board or Unit is restarted. If an error flag turns ON, remove the cause of the error and then reset the error indication from the Programming
Console or other Programming Device.
Error Codes
The contents of the error codes are shown in the following table.
Code
0
2
3
4
Error contents
No error
Sequence No. Error
The sequence number specified by the
PMCR(260) instruction does not exist in the Board or Unit.
Data Read/Write Area Exceeded Error
When data is written or read to the CPU Unit, the specified area range was exceeded.
Protocol Data Syntax Error
A code that cannot be executed occurs while the protocol macro was executed. (Example: A header occurs after a terminator.)
Protocol macro execution
Executed
Not executed
Execution stops after the error occurs.
177
Using Protocol Macros
Section 5-4
5-4 Using Protocol Macros
5-4-1 Executing Communications Sequences
Use the PMCR(260) instruction to execute communications sequences.
PMCR(260) Instruction Specifications
(@) PMCR (260)
C1
C2
S
Control data 1 (communications port No., serial port No., destination unit address)
Control data 2 (communications sequence No. )
First send word
R
First receive data storage word
Control Data 1 (C1)
15 12 11 08 07 00
Communications port No. Serial port No. Destination unit address
The following items are specified in C1.
Communications Port No. (Internal Logical Port Number)
Specify internal logical port 0 to 7 Hex for executing the PMCR(260) instruction.
Note A CS/CJ-series CPU Unit has eight internal logical ports for executing FINS commands. Specify the logical port number to be used for execution. These ports are also used by the SEND(090), RECV(098), and CMND(490) instruc-
tions used for Host Link communications. Refer to 4-4-1 Simultaneous Com-
mands and Communications Ports for details.
Serial Port No. (Physical Port)
Set the physical port number of the Serial Communications Board or Unit connected to the remote device.
Port 1: 1 Hex, Port 2: 2 Hex
Destination Unit Address
Specify the Unit address of the Serial Communications Board or Unit to execute the protocol macro.
Serial Communications Board: E1 Hex
Serial Communications Unit: Unit number (see note) + 10 Hex
Setting range: 10 to 1F Hex
Note This is the unit number (0 to F) for the CPU Bus Unit set on the rotary switch on the front panel of the Unit.
Control Data 2 (C2)
C2 specifies the communications sequence number in hexadecimal (000 to
999).
Setting range: 0000 to 03E7 Hex
First Send Data Word (S)
Word
S
S+1
15
0
S specifies the first word of the area in which the data required for sending is stored.
12 11 08 07 00
0
Number of send words
Total number of words including S
Send data
S+n
178
Using Protocol Macros
Section 5-4
The number of send words in S+1 and the following words is stored in the rightmost 8 bits of S. The setting range is 01 to FA Hex (250 words or less). S is also included in the number of words. The data to be sent is stored in S+1 and the following words.
Note When there is no send data, set S to #0000.
First Receive Data Storage
Word (R)
Word
R
15
R+1
0
R specifies the first word of the area used to initialize the reception buffer or the first word of the area used to store the receive data.
12 11
0
08 07
Number of receive words
00
Number of words including R
Receive data
R+n
PMCR(260) Operation
Note
Before Execution of PMCR(260)
The contents of R+1 and following words are set in the reception buffer. The number of words of data from R through the end of the receive data is specified in the rightmost 8 bits of R. The range that can be set is 02 to FA Hex (2 to
250 words). If 00 Hex or 01 Hex is set, the reception buffer will remain cleared after PMCR(260) execution and before executing the communications sequence.
After Execution of PMCR(260)
The number of words of receive data in R+1 and the following words is stored in the rightmost 8 bits of R. The range is 01 to FA Hex (250 words or less). R is also included in the number of words. The receive data is stored in R+1 and the following words. For details, refer to Receive Data Storage Area Function
1.
The function of the receive data storage words (start from R for the number of words specified in R) differs before and after execution of PMCR(260).
a) Before Execution of PMCR(260)
The contents of the receive data storage words is used as initialization data for the reception buffer before the communications sequence is executed.
b) After Execution of PMCR(260)
Data received for the RECV command is stored in the receive data storage words if there is response data to be written.
2.
When there is no receive data, set R to #0000.
When PMCR(260) is executed, the communications sequence specified in C2 is executed for the communications port specified in bits 12 to 15 of C1 (internal logical port 0 to 7) from the serial port specified in bits 08 to 11 (physical port) of C1 of the device with the unit address specified in bits 00 to 07 of C1.
If an operand is specified as a variable in the send message, data starting in
S+1 for the number of words specified in S is used as the send data. If an operand is specified as a variable in the receive message, data will be received in words starting from R+1 and the number of words of received data will be automatically stored in R.
If reception processing fails, the data that was stored started at R+1 (i.e., the number of words specified in R) is again read from the reception buffer and stored again beginning at R+1. This ensures that the current data will not be cleared and that the previous receive data will be maintained when receptions fail.
179
Using Protocol Macros
Section 5-4
Flags
Name
Error Flag
Label
ER
Access Error Flag AER
ON
• The Communications Port Enabled
Flag for the specified communications port (internal logical port) was
OFF when the instruction was executed.
• The specified serial port (physical port) is not set to protocol macro mode.
• The data setting in C1 is not within the allowed range.
• The number of words specified in S or D exceeds 249 (when a word address was specified for S or D).
A read/write-protected area was specified for send data or receive data.
A write-protected area was specified for receive data.
OFF
All other cases
All other cases
Operand Areas and Address Ranges
CIO Area
Work Area
Holding Area
Auxiliary Area
Timer Area
Area C1
CIO 0000 to CIO 6143
W000 to W511
H000 to H511
A000 to A959
T0000 to T4095
C2 S
Counter Area
Data Memory (DM) Area
C0000 to C4095
D00000 to D32767
Extended Data Memory (EM) Area
E00000 to E32767
Extended Data Memory (EM) Area
(including bank specification)
En_00000 to En_32767 (n = 0 to C)
Indirect DM/EM address, Binary
Indirect DM/EM address, BCD
Constant Area
@D00000 to @32767, @E00000 to @E32767,
@En_00000 to @En_32767
*D00000 to *D32767, *E00000 to *E32767,
*En_00000 to *En_32767
See Control Data 1
(C1).
DR0 to DR15
0000 to 037E Hex
(0 to 999)
#0000 to FFFF
(Binary data)
---
Data Registers
Index Registers, direct
Index Registers, indirect
---
,IR0 to ,IR15
-2048 to +2047,IR0 to -2048 to +2047,IR15
DR0 to DR15,IR0 to IR15
,IR0+(++) to ,IR15+(++)
,-(- -)IR0 to ,-(- -)IR15
R
A448 to A959
---
---
(see note)
(see note)
(see note)
(see note)
(see note)
Note The EM Area cannot be specified for the receive data when the interrupt notification function is being used for a Serial Communications Board. If the EM
Area is specified, a protocol macro syntax error will occur and A42410 will turn ON.
180
Using Protocol Macros
Section 5-4
Network Communications Flags
The following table shows the Auxiliary Area flags that are used when the
PMCR(260) instruction is executed.
Communications Port
Enabled Flags
These flags turn ON when execution of the PMCR(260) instruction is enabled.
Depending on the PMCR(260) instruction, they turn OFF at execution, and turn ON when the port enters an enabled status.
Word
A202
05
04
03
02
Bit
08 to 15
07
06
01
00
Contents
Reserved
Communications Port No. 7 Enabled Flag
Communications Port No. 6 Enabled Flag
Communications Port No. 5 Enabled Flag
Communications Port No. 4 Enabled Flag
Communications Port No. 3 Enabled Flag
Communications Port No. 2 Enabled Flag
Communications Port No. 1 Enabled Flag
Communications Port No. 0 Enabled Flag
Communications Port
Error Flags
These flags turn ON in the following cases:
• When an error occurs while the PMCR(260) instruction is being executed
• When an error response corresponding to each communications port occurs, or a resend error occurs
When operations start or when the PMCR(260) instruction is executed, if the
Communications Port Enabled Flag turns OFF, then the corresponding Error
Flag also turns OFF.
Word
A219
02
01
00
06
05
04
03
Bit
08 to 15
07
Contents
Reserved
Communications Port No. 7 Error Flag
Communications Port No. 6 Error Flag
Communications Port No. 5 Error Flag
Communications Port No. 4 Error Flag
Communications Port No. 3 Error Flag
Communications Port No. 2 Error Flag
Communications Port No. 1 Error Flag
Communications Port No. 0 Error Flag
Communications Port
Completion Codes
The response codes (FINS completion codes) are set when the PMCR(260) instruction is executed. The contents of these words are also cleared when the Communications Port Enabled Flag turns OFF at the start of operations or when the PMCR(260) instruction is executed.
Word
A203
A204
A205
A206
A207
A208
A209
A210
A211 to A218
Contents
Communications Port No. 0 Completion Code
Communications Port No. 1 Completion Code
Communications Port No. 2 Completion Code
Communications Port No. 3 Completion Code
Communications Port No. 4 Completion Code
Communications Port No. 5 Completion Code
Communications Port No. 6 Completion Code
Communications Port No. 7 Completion Code
Reserved
Note Refer to 11-3-5 Protocol Macros for information on completion codes.
181
Using Protocol Macros
Section 5-4
Flag Transitions
Communications Port
Enabled Flag
Network communications instructions
(PMCR(260)/SEND(090)/
RECV(098)/CMND(490))
Communications Port
Error Flag
Communications Port
Completion Code
Instruction 1 being executed
Instruction 2 being executed
Instruction 3 being executed
(Normal end)
(No unit corresponding to unit address)
(Normal end)
End of previous processing
Note Before executing a PMCR(260) instruction, be sure that the communications port is set to the Protocol Macro serial communications mode. If a
PMCR(260) instruction is executed for a communications port set in Host Link mode, a meaningless message may be sent from the port. The current serial communications mode can be checked in bits 12 to 15 (Protocol Macro = 6
Hex) of the following words. Boards: CIO 1905 for port 1 and CIO 1915 for
port 2. Units: CIO n + 5 for port 1 and CIO n + 15 for port 2. Refer to 2-3-1 DM
Area for DM Area allocations and settings.
5-4-2 Ladder Program Structure
When creating a ladder program, note the following points.
• To ensure that a PMCR(260) instruction is not executed while another
PMCR(260) instruction is being executed, use the Protocol Macro Executing Flag in an NC input condition.
• Use an OFF condition for the Protocol Macro Executing Flag and perform processing to read the results of sequence execution, or perform processing when a sequence ends in an error.
Programming Example
Input condition
Communications
Port Enabled Flags
Protocol Macro
Executing Flag
Protocol Macro
Executing Flag
Reading of sequence execution results
Processing of sequence errors
Note When executing the PMCR(260) instruction, be sure to check that the serial communications mode for the port used for communications is set to protocol macro. If the PMCR(260) instruction is executed with the serial communications mode set to Host Link (SYSWAY), messages that cannot be used for the application will be output from the serial port. The serial communications mode settings can be confirmed in bits 12 to 15 of the following words in the
CIO Area: Serial Communications Board, port 1: 1905, port 2: 1915; Serial
Communications Unit, port 1 = n+5, port 2 = n+15. The setting for protocol
macro is 6 Hex. For details of DM Area allocations, refer to 2-3-1 DM Area.
182
Using Protocol Macros
Section 5-4
5-4-3 Ladder Program Example
The following diagram shows an example in which sequence number 000
(Present Value Read) of a Temperature Controller (E5
@K Read Protocol) is executed using the protocol for an OMRON Temperature Controller connected to port 2 (RS-422A/485) of a Serial Communications Board.
Connections
Serial Communications
Board
Port 2
Specifies the Temperature Controller Unit No. , sends the PRESENT VALUE READ command send data, and receives the present value set in the response in the specified word.
Send data
Receive data
Temperature
Controller E5
#K
Unit No. 00
Temperature
Controller E5
#K
Unit No. 01
Temperature
Controller E5
#K
Unit No. 31
32 Units max.
Send Word Allocation for Sequence No. 000 (Present Value Read)
First word of send data
S
S + 1
Number of send data words
(Undefined) Unit No. S
Word
S + 1
Contents (data format)
Number of send data words
(4-digit BCD)
Unit No.
(2-digit BCD)
Data
0002 (fixed)
00 to 31
Receive Word Allocation for Sequence No. 000 (Present Value Read)
Receive data storage words
R
R + 1
Number of receive data words
Present value R
Word
R + 1
Contents (data format)
Number of receive data words
(4-digit BCD)
0002
Present value
(4-digit BCD)
Data
Scaling
Lower limit to upper limit
183
Using Protocol Macros
Operand Settings for the
PMCR(260) Instruction
Section 5-4
Reading the present value of E5
@K Unit No. 03 and storing it in DM00201
C1: Control data
C2: Control data
2: Port 2
0: Logical port 0
E1: Destination unit address
0000: Sequence No. 000
S: First send data word
Number of send data words = 2
Unit No. = 03
R: First receive data storage word
Present value
Number of receive data words = 2
Present value is stored.
(4-digit BCD)
184
Using Protocol Macros
Section 5-4
Ladder Programming
Example
Input condition
000000
Communications Port
No. 0 Enabled Flag
A20200
The following diagram shows an example in which sequence number 000
(PRESENT VALUE READ) of a Temperature Controller (E5
@K Read System) is executed using the PMCR(260) instruction. If the sequence has been completed normally, the present value that has been read is transferred to another word.
Protocol Macro
Executing Flag
191915
PMCR
#02E1
#0000
D00100
D00200
If input condition CIO 000000 is ON, Communications
Port No. 0 Enabled Flag A20200 is ON, and Protocol
Macro Executing Flag CIO 191915 is OFF, then sequence No. 000 is executed for Serial Communications
Board port 2 and the present value is stored in
DM00201.
Protocol Macro
Executing Flag
191915
DIFD (14) 000100
If Protocol Macro Executing Flag CIO 191915 turns OFF,
CIO 000100 turns ON (and remains ON for one cycle).
000100
Protocol Macro
Executing Flag
191915
Step Error
Processing Flag
191914
Step Error
Processing Flag
191914
MOV (21)
D00201
D00300
If Protocol Macro Executing Flag CIO 191915 is OFF and Step Error Processing Flag CIO 191914 is OFF when CIO 000100 turns ON, then the received present value in DM00201 is moved to DM00300.
Communications
Port No. 0 Error Flag
A21900
FAL (06) 01
If CIO 000100 is ON (sequence end) and Step Error
Processing Flag CIO 191914 is ON, the sequence ends abnormally and a FAL(06) instruction (Non-Fatal Diagnostic Instruction) is executed.
FAL (06) 02
If the Communications Port Error Flag for port 0 turns
ON, a FAL(06) instruction (Non-Fatal Diagnostic Instruction) is executed.
Protocol Macro
Executing Flag
CIO 191915
Sequence executed
Sequence completed
Sequence re-executed
00100
One cycle
Present value in DM00201 moved to DM00300
When sequence ended normally:
Step Error Processing
Flag CIO 191914
FAL instruction executed
When sequence ended abnormally:
Step Error Processing
Flag CIO 191914
185
Using Protocol Macros
Section 5-4
Receive Data Storage Area before Executing PMCR(260)
When the PMCR(260) instruction is executed, the reception buffer is cleared to 0 once immediately before the communications sequence is executed. If a ladder program is used that regularly reads the present value data, as shown in the following diagram, the present value data would normally be cleared to
0 if the data is not retrieved due to an error, such as a reception error. If reception processing fails, however, the data that was stored started at R+1 (i.e., the number of words specified in R) is again read from the reception buffer and stored again beginning at R+1. This ensures that the current data will not be cleared and that the previous receive data will be maintained when receptions fail. Make sure to set the number of words m for the data that is to be held. If the data is set to 0 or 1, the most recent receive data will not be held.
Instead, it will be cleared to 0.
Example:
The following protocol can be used to regularly execute the PMCR(260) instruction to retrieve receive data by performing the send/receive operation once only.
Always ON Flag
Communications
Port Enabled Flag
Protocol Macro
Executing Flag
PMCR(260)
Set
Value is stored when reception fails.
Reception buffer
R
R m words
Not holding the receive area.
Communications sequence
Reception buffer
Clear
Receive area
R + 1 onwards
Holding the receive area.
Communications sequence
Set
Reception buffer
Clear
Receive area
R + 1 onwards
RECV
Failed
RECV
Failed
Stores cleared values
Stores set values
1,2,3...
Receive Data Storage Area Function
The receive data storage area is used according to the following procedure.
1.
When the PMCR(260) instruction is executed, 250 words of the reception buffer in the Serial Communications Board or Serial Communications Unit are cleared.
2.
Before executing the communications sequence, the contents of one less than the number of words specified in R starting from word R + 1 are used to overwrite the contents of the reception buffer (excluding the first word).
This becomes the initial value of the reception buffer, and the results of the
RECV command execution are waited for. If the contents of the reception buffer exceeds the contents of the number of words specified in R (or the
186
Using Protocol Macros
Section 5-4
whole area if the number of words is specified as 00), then the initial value will be set to 0000 Hex.
3.
The data that has been received as the result of executing the RECV command will be stored in the reception buffer (except for the first word) from the specified first word (offset) and will be verified against the expected receive messages. If writing the response data is not specified, the receive data will be saved in the reception buffer and will not be stored in the CPU
Unit.
4.
If writing the response data is specified, the data in the reception buffer up to the most recent data (except for the first word), will be stored in from words R+1 onwards. The data stored for the number of words (including R) up to the last word will be saved. Whenever the number of data words stored exceeds the maximum, the number of words in R will be updated.
5.
Steps 3 and 4 are repeated until the protocol macro operation is completed.
I/O memory
No. of words specified here I/O memory
Changed
No. of words is stored and updated.
Set
CPU Unit
Overwrites initial value
Serial Communications
Board or Unit
Reception buffer
Reception buffer
Write response specified
Stores receive data
After PMCR(260) instruction is executed the internal processing buffer is cleared
Stored from the specified first word
RECV
Overwrites receive data
Offset
Receive data
Note Processing When a Sequence Ends Abnormally
As shown in the following examples, if END is set when a sequence ends normally and ABORT is set when a sequence ends abnormally, it is possible to determine whether each sequence has ended normally or abnormally by using the Sequence End Completion Flag and the Sequence Abort Completion Flag.
187
Using Protocol Macros
Example 1
Sequence
Step No. 00
Example 2
Sequence
Step No. 00
Section 5-4
Error
Sequence ended abnormally
Error
Step No. 01
Sequence ended normally
Error
Sequence ended abnormally
Step No. 01 Step No. 02
Sequence ended normally
Error
Sequence ended abnormally
Sequence ended normally
Protocol Macro
Executing Flag
When the sequence ends normally
Sequence End
Completion Flag
Sequence executed
Sequence completed
When the sequence ends normally
Protocol Macro
Executing Flag
Sequence re-executed
Sequence End
Completion Flag
Sequence executed
Sequence completed
Error processing for step No. 00
Step Error
Processing
Flag
Step Error
Processing
Flag
Sequence re-executed
When the sequence ends abnormally
Protocol Macro
Executing Flag
Sequence executed
Sequence completed
Sequence Abort
Completion Flag
Step Error
Processing
Flag
When the sequence ends abnormally
Protocol Macro
Executing Flag
Sequence re-executed
Sequence Abort
Completion Flag
Sequence executed
Sequence completed
Error processing for step No. 00
Step Error
Processing
Flag
Sequence re-executed
Note The Step Error Processing Flag is used to see whether error processing has been executed for an individual step in a sequence, and not for the overall steps. Therefore, as shown in Example 2 above, after executing error processing during a sequence (step No. 00), the flag will remain ON, even if the next step ends normally. Care is therefore required because it is not always possible to use this flag to determine whether the overall sequence has ended abnormally.
188
Simple Backup Function (Backup of Protocol Macro Data)
Section 5-5
Note Abort Switch Precaution
The Abort Switch can be used to abort the sequence that is being executed.
The Abort Switch can be turned ON from a ladder diagram or from a Programming Device. It will be turned OFF automatically by the system when abort processing has been completed. Do not attempt to force the Abort Switch to stay ON from a ladder diagram or from a Programming Device.
5-5 Simple Backup Function (Backup of Protocol Macro Data)
Overview
The “-V1” versions of the CS-series Serial Communications Boards/Unit
(CS1W-SCB21-V1, CS1W-SCB41-V1, and CS1W-SCU21-V1) and the
CJ1W-SCU21(-V1)/41(-V1) Serial Communications Unit* support the Simple
Backup Function when connected to a CS1-H or CJ1-H CPU Unit.
Note *The CS-series Serial Communications Boards/Units without the “-V1” suffix do not support this Simple Backup Function, but the CJ1W-SCU21/41 does support this function even though the model number lacks the “-V1” suffix.
The CPU Unit’s Simple Backup Function will automatically backup, restore, or compare the Protocol Macro data (both standard system protocol and userset protocol data) in the Serial Communications Board/Unit’s flash memory to the CPU Unit’s Memory Card. The Protocol Macro data is backed up, restored, or compared along with all of the data in the CPU Unit. (The Simple
Backup Function can be used with CS1-H and CJ1-H CPU Units only.)
When the Protocol Macro data in the Serial Communications Board/Unit is written to the Memory Card by the Simple Backup Operation, the data is saved as a Unit/Board Backup File with the filename shown below.
Note A Unit/Board Backup File for a Serial Communications Unit or Board is referred to as a “Protocol Data File” in this manual.
Filename: BACKUP
@@.PRM
(The value
@@ is the unit address. A Serial Communications Unit’s unit address is the Unit number + 10 Hex. A
Serial Communications Board’s unit address is E1 Hex.)
The Protocol Data File is accessed from the Memory Card during read and compare operations.
Serial Communications
Board/Unit
Memory Card power supply switch
CPU Unit
All data
Protocol data
• Backup
• Restore
• Compare
Memory Card
Note The following table shows the combinations of CPU Units and Serial Communications Board/Unit that support the Simple Backup Function.
189
Simple Backup Function (Backup of Protocol Macro Data)
Section 5-5
Precautions for Using the
Simple Backup Function
Applications
Operation
CPU Unit
CS1-H CPU Unit
CS1 CPU Unit
Serial Communications Board/Unit
CS1W-SCB21-V1,
CS1W-SCB41-V1, or
CS1W-SCU21-V1
Supported
Not supported
CS1W-SCB21,
CS1W-SCB41, or
CS1W-SCU21
Not supported
Not supported
CPU Unit
CJ1-H CPU Unit
CJ1 CPU Unit
CJ1M CPU Unit
Supported
Not supported
Supported
Serial Communications Board/Unit
CJ1W-SCU21(-V1)/41(-V1)
When using the Simple Backup Function in CS1H/G-CPU
@@
H products of
Lot No. 011101 or earlier* combined with the Serial Communications Board
(CS1W-SCB
@@
-V1), proper backup will not be possible if the backup file
(BACKUPE1.PRM) remains in the Memory Card.
*Reading lot numbers
CS1H/G-CPU
@@H Lot No. 01 11 01 ...Produced November 1, 2001
Production day (in this example: 1)
Production month (in this example: 11)
Production year (in this example: 2001)
In order to use the Simple Backup Function in this combination, delete the backup file (BACKUPE1.PRM) inside the Memory Card, then execute the backup.
If backup is executed without deleting this backup file, the RDY LED and the
CPU Unit’s ERR/ARM LED will both flash, and t he Protocol Data Error Flag (bit
A42409) will turn ON with the restore operation. The
Serial Communications Board will also automatically delete the backup file (BACKUPE1.PRM).
Use the Simple Backup Function when replacing all Units or creating backup files of all of the PLC’s data, including the data in the CPU Unit and Serial
Communications Boards or Units.
Use the following procedures to create a Protocol Data File on the Memory
Card, restore the Protocol Data File, and compare the protocol data with the
Memory Card’s Protocol Data File.
■ Backing Up the Protocol Data to the Memory Card
Follow these steps to back up the Serial Communications Board/Unit’s protocol data to the Memory Card:
1.
Make the following settings to pins 7 and 8 in the DIP Switch on the front of the CPU Unit.
Pin Setting
7
8
ON
OFF
2.
Press and hold the Memory Card power supply switch for 3 seconds.
190
Simple Backup Function (Backup of Protocol Macro Data)
Serial Communications
Board/Unit
Memory Card power supply switch
CPU Unit
All data
Protocol data
Memory Card
• Backup
Section 5-5
This procedure creates the Protocol Data File and writes it to the Memory
Card along with the other backup files.
When the Memory Card power supply switch is pressed, the MCPWR Indicator on the front of the CPU Unit will flash once and then remain lit while the data is being written. The Indicator will go OFF after the data has been written properly.
■ Restoring the Protocol Data from the Memory Card
Follow these steps to restore the Protocol Data File, i.e., read the protocol data from the Memory Card and set it in the Serial Communications Board/
Unit.
1.
Make the following settings to pins 7 and 8 in the DIP Switch on the front of the CPU Unit.
Pin Setting
7
8
ON
OFF
2.
Turn the PLC’s power supply from OFF to ON.
Serial Communications
Board/Unit
Turn ON power.
CPU Unit
All data
Protocol data
• Restore
Memory Card
This procedure reads the Serial Communications Board/Unit’s Protocol Data
File from the Memory Card and sets that data in the Serial Communications
Board/Unit.
When the PLC’s power is turned ON, the MCPWR Indicator on the front of the
CPU Unit will light and flash once. The MCPWR Indicator will remain lit while the data is being read. The Indicator will go OFF after the data has been read properly.
Serial Communications Board Operation
The Serial Communications Board’s RDY Indicator will flash during the restore operation and it will be lit when the restore operation is completed normally.
191
Enhanced Protocol Macro Functions
Section 5-6
If the restore operation fails, the RDY Indicator will continue to flash. The CPU
Unit’s ERR/ALM Indicator will flash and bit A42409 (the Protocol Data Error
Flag) will be turned ON.
Serial Communications Unit Operation
The Serial Communications Unit’s RDY Indicator will flash during the restore operation. Both the RDY Indicator and RUN Indicator will be lit when the restore operation is completed normally.
If the restore operation fails, the RDY Indicator will continue to flash and the
ERC Indicator will be lit.
■ Comparing the Protocol Data with the Memory Card’s Protocol Data File
Follow these steps to compare the Serial Communications Board/Unit’s protocol data with the Protocol Data File in the Memory Card:
1.
Make the following settings to pins 7 and 8 in the DIP Switch on the front of the CPU Unit.
Pin Setting
7
8
OFF
OFF
2.
Press and hold the Memory Card power supply switch for 3 seconds.
Serial Communications
Board/Unit
Memory Card power supply switch
CPU Unit
All data
Protocol data
• Compare
Memory Card
This procedure compares the protocol data in the Serial Communications
Board/Unit with the data in the Protocol Data File in the CPU Unit’s Memory
Card.
When the Memory Card power supply switch is pressed, the MCPWR Indicator on the front of the CPU Unit will flash once and then remain lit while the data is being compared. If the data matches, the Indicator will go OFF after the data has been compared.
5-6 Enhanced Protocol Macro Functions
Serial Communications Boards/Units with Unit Ver. 1.2 or later support the following enhanced protocol macro functions.
• Data exchange timing in link word specification
• Selection to clear or hold the contents of the reception buffer during fullduplex communications
• High-speed baud rate in protocol macro mode
192
Enhanced Protocol Macro Functions
Section 5-6
5-6-1 Data Exchange Timing for Link Words
Link word specification (a method of specifying the common area for data exchanged between the CPU Unit and the Board/Unit) is used as a method for specifying the storage location of send/receive data when executing communications sequences in protocol macro mode.
Pre-Ver. 1.2 Units
The link word area is refreshed between the CPU Unit and Board/Unit during every CPU Unit cycle. The actual refresh timing with the CPU Unit, however, does not correspond to whenever the I/O is refreshed. I/O refresh is performed when a request is received from the Board/Unit (according to the send/receive command executed in the communications sequence, and therefore not synchronized with the CPU Unit scantime). This is called onrequest I/O refreshing.
CPU Unit
Ladder program
PMCR
(1)
Board/Unit
Communications sequence
Step 0
Step 1 (send)
(1) to (4) are performed in order for the processing within this dotted line.
Send message according to send command
(4) Send
R (O1, 2)
Read and compile messa
I/O memory
Receive data
Send data
(2)
IN
OUT
Link word 1
I1
Receive data
O1
Send data
Earlier models refresh I/O when a request is received (using send/receive commands in the communications sequence).
Therefore, when a send command is executed ((1) in the above diagram), the read processing of data using variables from the I/O memory addresses in the
CPU Unit specified in the link words is performed at the start of I/O refreshing
(2). The send message is compiled based on this data (3), after which the actual message is sent (4). As a result, the actual message send timing is not when the send command is executed, but waits until the next I/O refresh with the CPU Unit.
Unit Ver. 1.2 or Later
The refresh between the CPU Unit and Board/Unit is the same as in earlier models as far as being the CPU Unit’s refresh timing. I/O refresh with the CPU
Unit, however, is continuous during execution of the PMCR(260) instruction, regardless of any request from the Board/Unit. When the send/receive command is executed, the data from within the Board/Unit is accessed and exchanged. This method is called continuous I/O refresh and is set in the
Setup Area allocated in the DM Area.
193
Enhanced Protocol Macro Functions
Section 5-6
CPU Unit
Ladder program
PMCR
I/O memory
Receive data
Send data
(1)
(2)
IN
OUT
Board/Unit
Communications sequence
Step 0
Step 1 (send)
(1) to (4) are performed in order for the processing within this dotted line.
Send message according to send command
(3) Send
R (O1, 2)
Read, compile message
Link word 1
I1
Receive data
O1
Send data
5-6-2 Clearing/Holding Contents of Reception Buffer in Full-duplex
Mode
Pre-Ver. 1.2 Units
The reception buffer is cleared to zeros when the PMCR(260) instruction is executed (immediately before communications sequence execution) in either half-duplex or full-duplex transmission mode using the protocol macro function. When data is exchanged in both directions in full-duplex mode, however, the data in the reception buffer that was received during SEND command processing in the immediately previous communications sequence is cleared to zeros when the PMCR(260) instruction is executed and the communications sequence is switched. This data cannot be received using the RECEIVE command in the communications sequence after switching.
Unit Ver. 1.2 or Later
The refresh timing continuously refreshes I/O regardless of the any request from the Board/Unit (using send/receive commands in the communications sequence).
Therefore, when a send command is executed in a step, the send message is compiled immediately based on data read from the Board/Unit, and the actual message is sent. Therefore, the actual message transmission is performed immediately when the send command is executed (there is no need to wait until the next I/O refresh with the CPU Unit). The receive command operation is similar. When the receive data is stored in the Board/Unit, receive command execution is completed. The actual received data is stored in I/O memory at the next I/O refresh with the CPU Unit.
• Setup Area Allocated in the DM Area m = D30000 + 100
× unit number
Bit Setting Words
Port 1
Board
Port 2 Port 1
D32008 D32018 m+8
Unit
Port 2
m+18 02 Link word specification data exchange timing
0: On-request I/O refreshing
1: Continuous I/O refreshing
In Unit Ver. 1.2 or later, the contents of the reception buffer can be cleared or held when the PMCR(260) instruction is executed during full-duplex transmission (immediately before executing the communications sequence). This option is set in the Setup Area. This function enables data in the reception buffer that was received in the previous communications sequence to be held, even if the communications sequence has been switched in full-duplex mode.
194
Enhanced Protocol Macro Functions
Section 5-6
• Setup Area Allocated in the DM Area m = D30000 + 100
× unit number
Bit Setting
Port 1
Board
Port 2
D32008 D32018
Words
Port 1
m+8
Unit
Port 2
m+18 03 Clearing/holding contents of reception buffer in full-duplex mode
0: Clear
1: Hold
5-6-3 High-speed Baud Rate for Protocol Macro Mode
Pre-Ver. 1.2 Units
The baud rate for protocol macro mode was 38,400 bps max.
Unit Ver. 1.2 or Later
A baud rate of 57,600 bps can be selected for protocol macro mode by setting it in the Setup Area.
• Setup Area Allocated in the DM Area m = D30000 + 100
× unit number
Bit Setting
Port 1
Board
Port 2
D32001 D32011
Words
Port 1
m+1
Unit
Port 2
m+11 00 to 03 Baud Rate (unit: bps)
(This setting is available even when protocol macros are used for serial communications)
9: 57,600
195
Enhanced Protocol Macro Functions
Section 5-6
196
SECTION 6
Serial Gateway
This section provides an overview of the Serial Gateway, information on I/O memory allocations, and procedures for using the functions. Information on protocol conversion, routing table requirements, and communications frames is also provided. The Serial Gateway can be used only for Unit Ver. 1.2 or later.
6-1-2 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1-4 Serial Gateway Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 DM Area Allocations (Using Serial Gateway Mode) . . . . . . . . . . . . . . . . . . .
6-3 Auxiliary Area and CIO Area in Serial Gateway Mode . . . . . . . . . . . . . . . . .
6-5-1 Types of Protocol Conversion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5-2 Converting FINS to CompoWay/F . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5-3 CompoWay/F Connection Examples . . . . . . . . . . . . . . . . . . . . . . . .
6-5-4 Converting FINS to Modbus-RTU . . . . . . . . . . . . . . . . . . . . . . . . . .
6-5-5 Converting from FINS to Modbus-ASCII . . . . . . . . . . . . . . . . . . . .
6-5-6 Converting from FINS to Host Link FINS . . . . . . . . . . . . . . . . . . . .
6-6-1 Serial Gateway Execution Timing for Protocol Macros . . . . . . . . . .
6-6-2 Serial Gateway Timeout Monitoring . . . . . . . . . . . . . . . . . . . . . . . .
6-7-1 Treating Serial Communications Paths as Networks . . . . . . . . . . . .
6-7-2 Using a PLC as the Target . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-7-3 Using a non-PLC Component as the Target . . . . . . . . . . . . . . . . . . .
6-8-1 CompoWay/F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8-2 Modbus-RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8-3 Modbus-ASCII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-8-5 Sending Commands Using the CMND(490) Instruction . . . . . . . . .
197
Serial Gateway Overview
Section 6-1
6-1 Serial Gateway Overview
6-1-1 Overview
FINS messages (commands) that are received are automatically converted into the corresponding protocol and then sent via serial communications. The responses are also automatically converted. FINS messages can be converted into the following protocols.
• CompoWay/F
• Modbus-RTU
• Modbus-ASCII
• Host Link FINS (FINS commands enclosed in Host Link header and terminator)
Note Serial Communications Boards/Units can receive FINS commands via a FINS network (including Host Link FINS) or via the CPU bus.
6-1-2 Operating Conditions
The Serial Gateway is enabled under the following conditions.
• When Serial Gateway mode is set as the serial communications mode.
• When protocol macro mode is set as the serial communications mode, and the Serial Gateway Prohibit Switch is OFF. (The serial gateway is also enabled during execution of PMCR(260) instructions.)
RS-232C or RS-422A/485
FINS message (via network or CPU bus)
FINS header
2803
CompoWay/F command
CompoWay/F command
FINS header
2804
Modbus-RTU command
FINS header
2805 Modbus-ASCII command
FINS header
Userspecified
User-specified data
Serial
Communications
Board/Unit
Modbus-RTU command
Modbus-ASCII command
Host Link header
User-specified
FINS command
Terminator
The Serial Gateway is enabled under the following conditions.
• In Serial Gateway mode
• In protocol macro mode with the Serial Gateway Prohibit Switch turned OFF
6-1-3 Features
Unifying to FINS Networks for CompoWay/F-compatible OMRON Components
■
Pre-Ver. 1.2 Units
To access an OMRON CompoWay/F-compatible component (e.g., Temperature Controller or Digital Panel Meter) by sending user-specified CompoWay/F commands from the PLC, the standard system protocol, CompoWay/F Master, must be executed. This operation is performed by executing the
PMCR(260) instruction in the ladder program of the CPU Unit on the same
PLC using the Board/Unit’s protocol macro function.
This protocol macro function, however, does not enable access through the network. (When execution of a user-specified CompoWay/F command is not required, a CJ1W-CIF21 Simple Communications Unit can be used to share specified data without using communications instructions.)
198
Serial Gateway Overview
Section 6-1
■
Unit Ver. 1.2 or Later
The Board’s/Unit’s Serial Gateway enables flexible access to OMRON CompoWay/F-compatible components from a device on the network (PT or PLC’s
CPU Unit). This enables unification of OMRON CompoWay/F-compatible components with FINS networks.
FINS Network System
Network
CMND(490) instructions
Serial
Network
Network
FINS
Access to CompoWay/Fcompatible Components from personal computers, PTs,
PLCs, and other devices via the network is possible.
Serial Communications Unit/Board with unit version 1.2 or later
Protocol conversion
CompoWay/F
Serial
CompoWay/F-compatible components
Unifying to FINS Networks for Modbus Slave-compatible Devices
■
Pre-Ver. 1.2 Units
Access to Modbus Slave-compatible devices (e.g., OMRON Inverters) from the PLC using any Modbus command requires execution of the PMCR(260) instruction in the ladder program of the CPU Unit on the same PLC, incorporating a communications sequence using the Board/Unit’s protocol macro function. Furthermore, using the protocol macro function prevents access through the network.
■
Unit Ver. 1.2 or Later
The Board/Unit’s Serial Gateway enables flexible access to Modbus Slavecompatible devices from devices on the network (PLC’s CPU Unit and personal computer). This enables unification of Modbus Slave-compatible devices with FINS networks.
199
Serial Gateway Overview
FINS Network System
Section 6-1
Network
CMND(490) instructions
Serial
Network
Network
FINS
Access to Modbus Slavecompatible devices from personal computers, PTs,
PLCs, and other devices via the network is possible.
Serial Communications Unit/Board with unit version 1.2 or later
Protocol conversion
Modbus command
Serial
Modbus Slave-compatible devices
Unifying to FINS Networks for Host Link Slave PLCs
■
Pre-Ver. 1.2 Units
Access to PLCs used as Host Link slaves from the PLC used as the Host Link master by executing user-specified FINS commands is not supported. (The
PLC cannot be used as a Host Link master. Therefore, incorporation of a communications sequence in the protocol macro is required.)
■
Unit Ver. 1.2 or Later
The Board/Unit’s Serial Gateway enables access to PLCs used as Host Link slaves from devices on the network (personal computer, PT, and PLC’s CPU
Unit) using user-specified FINS commands. This enables use of the PLC as a
Host Link master while maintaining transparency on the network.
200
Serial Gateway Overview
FINS Network System
Section 6-1
Network
CMND(490) instructions
Serial
Network
Network
FINS
Access to PLCs used as Host
Link Slaves from personal computers, PTs, PLCs, and other devices by using userspecified FINS commands is possible.
Serial Communications Unit/Board with unit version 1.2 or later
Protocol conversion
Serial
Host Link
FINS
CS/CJ-series or CVM1/CV-series PLCs
Serial Gateway Supported in Protocol Macro Mode
■
Pre-Ver. 1.2 Units
Programming or monitoring of a serially connected PLC from the CX-Programmer during execution of a protocol macro (e.g., Host Link Master Protocol) requires the CX-Programmer to be directly connected to the serially connected PLC. This configuration is not possible, however, if the serially connected PLC is on a moving body connected through a serial wireless modem.
■
Unit Ver. 1.2 or Later
The Serial Gateway can also be used in protocol macro mode. When protocol macros are used for serial communications, the Serial Gateway is prohibited by turning ON the Serial Gateway Prohibit Switch in the CIO Area and enabled by turning OFF this switch. This option enables, for example, programming or monitoring of a serially connected PLC from a CX-Programmer that is connected to the PLC during execution of protocol macros (e.g., Host
Link Master). This function also enables continuous programming/monitoring from the CX-Programmer when the serially connected PLC is on a moving body connected through a serial wireless modem, making it particularly effective.
CX-Programmer
The remote PLC is on a moving body. Therefore, direct serial connection for programming/monitoring the PLC is not possible. Access is possible, however, by using the Serial Gateway during execution of the protocol macro.
Serial Communications Unit/Board
PMCR(260) instruction
Serial
RS-232C
Host Link master protocol macro executing
WM30-S-V2 Wireless Modem
PLC
Serial Gateway
RS-232C
WM30-S-V2
Wireless Modem
AGV or other moving body
Access from CX-Programmer to remote PLC executing protocol macro is possible.
201
Serial Gateway Overview
Section 6-1
Note
If the Serial Gateway Prohibit Switch allocated in the CIO Area is OFF, the
Serial Gateway is enabled whether protocol macros are being executed or not. During execution of protocol macros, however, the Serial Gateway is processed using interrupts between steps in the communications sequence.
6-1-4 Serial Gateway Specifications
Item Details
Conversion source FINS command (received via network (including Host Link
FINS) or CPU bus)
Conversion functions • Received FINS commands are converted according to the following values before sending to the serial port of the
Board/Unit.
2803 hex: Removes FINS header and converts to Compo-
Way/F command
2804 hex: Removes FINS header and converts to Modbus-
RTU command
2805 hex: Removes FINS header and converts to Modbus-
ASCII command
• When a received FINS command is sent to the Board/Unit
(any FINS command code), the FINS command is enclosed in Host Link header and terminator.
After conversion • CompoWay/F commands
• Modbus-RTU commands
• Modbus-ASCII commands
• Host Link FINS commands
Serial Gateway mode or protocol macro mode Supported serial communications modes
Queuing
Processing during protocol macro execution
Up to 5 FINS commands can be queued for conversion/transmission standby.
When a FINS command is received during execution of a protocol macro, the Serial Gateway is executed as an interrupt between steps in the communications sequence. If the next step is a receive command, however, the Serial Gateway will not be executed and will be delayed. Under all other conditions, the serial gateway is executed immediately.
Response timeout monitoring
Note The reception buffer is cleared during Serial Gateway execution.
Note The Serial Gateway can be prohibited during protocol macro mode by turning ON the Serial Gateway Prohibit
Switch (in the CIO Area).
The time is monitored from when a message converted to another protocol using the Serial Gateway is sent until a response is received (enabled in Serial Gateway mode or protocol macro mode).
Default: 5 s; Setting range: 0.1 to 25.5 s
Note If a timeout occurs, the FINS end code is returned to the source of the FINS command (0205 hex: Response timeout). If a response is received after a timeout, however, the message is converted and returned to the source of the FINS command.
202
DM Area Allocations (Using Serial Gateway Mode)
Section 6-2
Item
Send start timeout monitoring
Send delay
Details
The time is monitored after a FINS command is received and converted into another protocol until transmission starts (protocol macro mode only).
Default: 5 s; Setting range: 0 to 25.5 s
Note If a timeout occurs, the FINS end code is returned to the source of the FINS command (0204 hex: Remote node busy). Send processing is not executed and the received FINS command is discarded.
The time after protocol conversion using the Serial Gateway until actual data is sent can be set (Serial Gateway mode or protocol macro mode only).
Default: 0 s; Setting range: 0 to 300 s
Note
The following operations will result if the Serial Gateway is executed either using a pre-Ver. 1.2 Board/Unit or using a Ver. 1.2 or later Unit/Board without
Serial Gateway or protocol macro mode set for serial communications at the serial port.
• If either NT Link or loopback test mode is used for serial communications, or if protocol macro mode is used with a pre-Ver. 1.2 Board/Unit, an undefined command response will be returned (end code: 0401 hex).
• If Host Link mode is used for serial communications, the message will be converted into a FINS command using Host Link slave-initiated communications and transferred (this will mainly result in a response timeout being returned, depending on the remote device (end code: 0205 hex))
6-2 DM Area Allocations (Using Serial Gateway Mode)
This section explains the Setup Area (words allocated in DM Area) when a
Serial Communications Board or Serial Communications Unit is used in Serial
Gateway mode.
Setup Area Words
The Serial Communications Boards and Serial Communications Units use the following words as a Setup Area in the DM Area when Serial Gateway mode is used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units, which are allocated words according to the unit numbers.
Serial Communications Boards (CS Series Only)
Words are allocated in the DM Area from D32000 to D32099 as the Setup
Area for the Serial Communications Board as follows:
D32000 to D32001
D32008 to D320009
D32010 to D32011
D32018 to D32019
Port 1 Settings
Port 2 Settings
D32002 to D32007
D32012 to D32017
Not used with Serial Gateway mode
D32020 to D32767 Reserved for the system
203
DM Area Allocations (Using Serial Gateway Mode)
Section 6-2
Serial Communications Units (CS/CJ Series)
Words are allocated in the DM Area from D30000 to D31599 as the Setup
Area for the Serial Communications Units as follows: m = D30000 + 100 ¥ unit number
Unit number
Unit No. 0
Unit No. 1
Unit No. 2
Word
D30000 to D30099
D30100 to D30199
D30200 to D30299
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
D30300 to D30399
D30400 to D30499
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599 m to m+1, m+8 to m+9: Port 1 Settings m+10 to m+11, m+18 to m+19: Port 2 Settings m+2 to m+27, m+212 to m+217: Not used.
m+20 to m+99: Not used.
Setup Area
■ Allocations m = D30000 + 100 ¥ unit number
Setting DM Area
Board (CS Series only)
Unit (CS/CJ
Series)
Port 1 Port 2
D32000 D32010 m
Port 1 Port 2
m+10
Bit
15 Port settings: 0 (default) or 1 (user-specified)
12 to 14 Reserved
08 to 11 Serial communications mode
(9 hex: Serial Gateway mode)
05 to 07 Reserved
04 Start bits
0: 1 bit; 1: 1 bit (Always 1 bit regardless of which bit is set)
03
02
Data length
0: 7 bits
1: 8 bits
Stop bits
0: 2 bits
1: 1 bit
01
00
Parity
0: Yes
1: No
Parity
0: Even
1: Odd
204
DM Area Allocations (Using Serial Gateway Mode)
Section 6-2
DM Area
Board (CS Series only)
Unit (CS/CJ
Series)
Port 1 Port 2 Port 1
D32001 D32011 m+1
Port 2
m+11
Bit Setting
D32002 D32012 m+2
D32003 D32013 m+3
D32007 D32017 m+7 m+12 m+13 m+17
04 to 15 Reserved
00 to 03 Baud rate (unit: bps)
0 hex: 9,600 (default); 3 hex: 1,200; 4 hex: 2,400; 5 hex: 4,800;
6 hex: 9,600; 7 hex: 19,200; 8 hex: 38,400; 9 hex: 57,600; A hex:
115,200
15 Send delay
0: default (0 ms); 1: User-specified
00 to 14 Send delay setting range: 0 to 399 s (0 to 300,000 ms)
0000 to 7530 hex (0 to 30,000 decimal) (Unit: 10 ms)
15 CTS control
0: No; 1: Yes
08 to 15 Serial Gateway response timeout monitoring time
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s (Unit: 100 ms)
00 to 07 Serial Gateway send start timeout monitoring time
(only protocol macro mode)
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s (Unit: 100 ms)
■ Details
Port Settings
Set whether to make the user-specified settings for port 1 or port 1. These settings are the same as for the RS-232C port of general-purpose external devices connected using a protocol macro.
0: Default; 1: User-specified setting
When the default (0) is set, the following details are set for the port and bits 00 to 04 do not need to be set separately.
Baud rate: 9,600 bps; Start bits: 1 bit; Data length: 7 bits; Parity: Even; Stop bits: 2 bits
When user-specified settings (1) are specified, set bits 00 to 04 and the baud rate (in the following word).
Setting example: 0900 hex: Serial Gateway mode, using default settings for port setting and baud rate.
Serial Communications Mode
Serial Gateway mode is used, so set to 9 hex.
Start Bits, Data Length, Stop Bits, Parity, Baud Rate
Set these bits if the port setting is set to user-specified settings. The start bit is always 1 bit (1) regardless of which value is set. Do not set the baud rate between B and F hex. Doing so will result in a system error and operation will proceed using the default (9,600 bps). Do not set 1 or 2 hex, which are reserved for the system.
User-specified Send Delay Time
After the FINS command is received by the Board/Unit and converted into the specified protocol, it is not transferred immediately, but sent after the delay time set within the following range
0000 to 7530 hex (0 to 30,000 decimal) (unit: 10 ms): 0 to 300 s (0 to
300,000 ms)
205
Auxiliary Area and CIO Area in Serial Gateway Mode
Section 6-3
CTS Control
When CTS control is enabled, transmission starts when the request to send signal (RS) turns ON after checking that the send enabled signal (CS) is ON.
When CTS control is disabled, transmission starts when the request to send signal (RS) turns ON, without checking whether the send enabled signal (CS) is ON.
Serial Gateway Response Timeout Monitoring Time
After a FINS command has been converted to the specified protocol and sent, the response timeout is monitored.
0: 5 s (default); 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The response monitoring time can either be set to the default (0) of 5 s or to a user-specified value between 01 and FF hex (0.1 to 25.5 s).
Note If a timeout occurs, the FINS end code (0205: Response timeout) is returned to the source of the FINS command. If a response is received after the timeout, however, the message is converted and returned to the source of the FINS command.
Serial Gateway Send Start Timeout Monitoring Time
When a FINS command is converted to the specified protocol and sent during protocol macro execution, the time is monitored from when the FINS command is received until it starts to be sent in the converted protocol.
0: 5 s (default); 01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
The send start monitoring time can either be set to the default (0) of 5 s or to a user-specified value between 01 and FF hex (0.1 to 25.5 s).
Note If a timeout occurs, the FINS end code (0204: Remote node busy) is returned to the source of the FINS command. Send processing will not be executed and the received FINS message will be discarded.
6-3 Auxiliary Area and CIO Area in Serial Gateway Mode
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and CIO Area
(Software Switches and Status) when Serial Gateway mode is used.
Auxiliary Area
Port 1 and Port 2 Port Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the serial ports.
When changing the communications settings and restarting the communications port have been completed, the bit will be automatically turned OFF.
Note
These bits are used both to change the communications port settings and to restart the communications port. Therefore, one of these bits can be turned
ON using an OUT instruction to restart a communications port without changing the settings in the DM Area. The STUP(237) instruction can also be used to simply restart a communications port by executing the STUP(237) instruction with the same port settings as those already being used.
206
Auxiliary Area and CIO Area in Serial Gateway Mode
Section 6-3
Serial Communications Boards (CS Series Only)
Word
A636
Bit
03 to 15
02
01
00
Setting
Reserved
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved
Serial Communications Units (CS/CJ Series)
n
Word Setting
Reserved
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved n = A620 + unit number
Inner Board Error Details (CS-series Serial Communications Boards Only)
A424 contains error information for the Serial Communications Board.
Word
A424
04
03
02
01
07
06
05
00
Bit
12 to 15
11
10
09
08
Non-fatal error (See note 1.)
Fatal error
(See note
2.)
Setting
Reserved
1: Error log EEPROM error; 0: Normal
Not used
Not used
1: Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
Reserved
Reserved
Reserved
1: Inner bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
Note
Bit
03 to 15
02
01
00
(1) If any of bits 05 to 11 turn ON (1), A40208 (Inner Board Error Flag) (nonfatal error) will turn ON (1).
(2) If either bit 00 or 01 turns ON (1), A40112 (Inner Board Fatal Error Flag) will turn ON (1).
For details on errors, refer to Section 11 Troubleshooting and Maintenance.
CIO Area
Words in the CIO Area are allocated as Software Switches, which are manipulated from the CPU Unit to control the operation of the Serial Communications Board or Unit, and for a Status Area, which contains status and error information for the Serial Communications Board or Unit.
Serial Communications Boards (CS Series Only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are allocated for the
Serial Communications Board. In Serial Gateway Mode, only the following words are used as the CIO Area. No other words are used.
207
Auxiliary Area and CIO Area in Serial Gateway Mode
Section 6-3
Inner Board CIO Area
CIO 1900 to CIO 1999
CIO 1900
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Software Switches (port 1/port 2)
Board status
Port 1 status
Port 2 status
Reserved for the system
Serial Communications Units (CS/CJ Series)
Words are allocated in the CIO Area for Software Switches and Status Area.
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. The first word is used for Software Switches, and the remaining 24 words are used for the Status Area.
Unit number
Word
Unit No. 0 CIO 1500 to CIO 1524
Unit No. 1 CIO 1525 to CIO 1549
Unit No. 2 CIO 1550 to CIO 1574
Unit No. 3 CIO 1575 to CIO 1599
Unit No. 4 CIO 1600 to CIO 1624
Unit No. 5 CIO 1625 to CIO 1649
Unit No. 6 CIO 1650 to CIO 1674
Unit No. 7 CIO 1675 to CIO 1699
Unit No. 8 CIO 1700 to CIO 1724
Unit No. 9 CIO 1725 to CIO 1749
Unit No. A CIO 1750 to CIO 1774
Unit No. B CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E CIO 1850 to CIO 1874
Unit No. F CIO 1875 to CIO 1899 n: Software switches (ports 1 and 2) n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
Status Area
The Status Area is used to read the Serial Communications Board’s or Unit’s setting status, communications status, transmission control signal status, and transmission error status.
Allocations
Board
(CS Series only)
Words
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
1901 n+1
Direction: Board/Unit to CPU Unit (input) n = CIO 1500 + 25 ¥ unit number
Bit Contents
1902
1903
1904 n+2 n+3 n+4
02 to 15 Reserved
01
00
1: Error log EEPROM error 0: Error log EEPROM normal
1: Protocol data error (SUM value error) 0: Protocol data normal
00 to 15 Reserved
00 to 15 Reserved
00 to 15 Reserved
208
Auxiliary Area and CIO Area in Serial Gateway Mode
Section 6-3
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
1905 1915 n+5 n+15
Bit
12 to 15 Port setting status
08 to 11
05 to 07
04
03
02
01
00
System settings
Contents
Serial communications mode: Always 9 hex (See note.)
Baud rate (See note.)
Reserved
Start bits: Always 0
Data length (See note.)
Stop bits (See note.)
Parity: Yes/No (See note.)
Parity: Even/Odd (See note.)
Note
The port settings in the Setup Area allocated in the DM Area are stored. If the
Board/Unit is operating on default settings due to a System Setup error the default settings will be stored.
Contents
Board
(CS Series only)
Words
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO
1906
CIO
1916 n+6 n+16 15
14
Bit
13
CIO
1907
CIO
1917 n+7 n+17
02 to 12
01
00
11 to 15
10
09
08
07
06
05
04
03
00 to 02
Port setting status
Hardware settings
0
0
No 0
1
RS-
232C
1 RS-
0
422A/
485
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: System Setup error; 0: System Setup normal
1 Reser
1 ved
Communications status
1: Port operating
Reserved
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive
Reserved
Transmission control signal status
1: Local Unit busy receiving (flow control)
0: Local Unit ready to receive
DTR (ER) signal
DSR (DR) signal
Reserved
CTS (CS) signal
RTS (RS) signal
Reserved
209
Using the Serial Gateway
Section 6-4
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
1908 1918 n+8 n+18
Bit
15
08 to 14
07
06
05
04
03
02
00, 01
Contents
Transmission error status
1: Transmission error; 0: No transmission error
Not used
1: FCS check error (transmission path error); 0: FCS check normal
Not used
1: Serial Gateway send start timeout or Serial Gateway response timeout
0: Normal
1: Overrun error (see note 7); 0: Normal
1: Framing error (see note 8); 0: Normal
1: Parity error (see note 8); 0: Normal
Reserved
6-4 Using the Serial Gateway
Use of the Serial Gateway basically requires only the DM Area (Setup Area) and CIO Area settings.
Note
If routing tables are required, set them using the CX-Net.
Step 1: Set the DM Area (Setup Area) and CIO Area.
Using Serial Gateway Alone
• DM Area (Setup Area) Settings
Words
Board
Port 1 Port 2
D32000 D32010 m
Port 1
Unit
Port 2
m+10
D32002
D32003
D32007
D32012
D32013
D32017 m+2 m+3 m+7 m+12 m+13 m+17 m = D30000 + 100 ¥ unit number
Bit Setting contents
08 to 11 Serial communications mode
9 hex: Serial Gateway mode
00 to 04 Communications conditions including start bits, data length, stop bits, parity (set to match the protocol at the conversion destination)
15 Send delay
0: Default (0 ms)
1: User-specified
00 to 14 User-specified send delay
0 to 300 s (0 to 300,000 ms):
0000 to 7530 hex (0 to
30,000 decimal)
(Unit: 10 ms)
15 CTS control
0: No; 1: Yes
08 to 15 Response timeout monitoring time
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
(Unit: 100 ms)
210
Using the Serial Gateway
Section 6-4
Using Serial Gateway with Protocol Macros
• DM Area (Setup Area) Settings
Words
Board
Port 1 Port 2
D32000 D32010 m
Port 1
Unit
Port 2
m+10
D32002
D32003
D32007
D32012
D32013
D32017 m+2 m+3 m+7 m+12 m+13 m+17 m = D30000 + 100 ¥ unit number
Bit Setting contents
08 to 11 Serial communications mode
9 hex: Protocol macro mode
15 Send delay
0: Default (0 ms); 1: Userspecified
00 to 14 User-specified send delay
0 to 300 s (0 to 300,000 ms):
0000 to 7530 hex (0 to 30,000 decimal)
(Unit: 10 ms)
15 CTS control
08 to 15 Response timeout monitoring time
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
(Unit: 100 ms)
00 to 07 Serial Gateway send start timeout monitoring time
00 hex: 5 s (default)
01 to FF hex (1 to 255 decimal): 0.1 to 25.5 s
(Unit: 100 ms)
• CIO Area
Word
Board Unit
1900 n
Bit
n = CIO 1500 + 25 ¥ unit number
Function
12
04
Port 2
Port 1
Serial Gateway Prohibit Switch (protocol macros)
0: Not prohibited; 1: Prohibited
Serial Gateway Prohibit Switch (protocol macros)
0: Not prohibited; 1: Prohibited
Use the following flag to check whether the Serial Gateway is currently prohibited or not.
Bit Contents
Board
Port 1 Port 2
1909 1919
Word
Port 1
Unit
Port 2
n+9 n+19 08 Serial Gateway Prohibited
Flag
1: Prohibited; 0: Not prohibited
211
Using the Serial Gateway
Section 6-4
Use the following flag to check whether a Serial Gateway response timeout or send start timeout has occurred.
Bit Contents
Board
Port 1 Port 2
1908 1918
Word
Port 1
n+8
Unit
Port 2
n+18 05 Serial Gateway response timeout, Serial Gateway send start timeout, or other timeout
(protocol macro Tfs, Tfr, or Tr)
1: Timeout; 0: Normal
Step 2: Set the Local Network Tables in the Routing Tables (Using CX-Net).
This step is necessary only when routing table settings are required.
1,2,3...
1.
Using CX-Net, select Setup from the Routing Table Menu. Select either the option FINS Local or FINS Network using the option button to display the Routing Table Window.
2.
Click the Table View Tab, and create the local network table at the left of the table.
3.
Set the unit address (see note 1) of the serial port to be treated as a network in the SIOU column as a decimal value. Set the network address to be allocated to the serial port in the Local Network column on the right.
Local Network Table
Example: The following diagram shows the local network table for used to allocated network address 3 to serial port 1 of a Serial Communications Unit with unit number 1.
Enter the serial port number as a decimal in the SIOU column.
Example: For serial port 1 of the Serial
Communications Unit with unit number 1,
80 hex + 04 hex x 1 = 84 hex = 132 decimal.
To treat the serial port indicated on the left as a network, enter the network address to be assigned in the Local
Network column.
Example: To assign network address 3, enter the decimal value 3 in the Local
Network column.
Local network table
SIOU
132
Local Network
3
Serial Port Number
The serial port number for the Board/Unit is set as follows:
Serial Communications Unit
Serial port 1
Serial port 2
Serial Communications Units
Serial port
Serial port 1
Serial port 2
Serial port number
80 hex + 04 hex
× unit number
81 hex + 04 hex
× unit number
Example for unit number 1
80 hex + 04 hex
×
1 = 84 hex
(132 decimal)
81 hex + 04 hex
×
1 = 85 hex
(133 decimal)
• Port Number for Serial Port 1
Unit number
Hexadecimal
Decimal
0 1 2 3 4 5 6 7 8 9 A B C D E F
80 84 88 8C 90 94 98 9C A0 A4 A8 AC B0 B4 B8 BC
128 132 136 140 144 148 152 156 160 164 168 172 176 180 184 188
• Port Number for Serial Port 2
Unit number
Hexadecimal
Decimal
0 1 2 3 4 5 6 7 8 9 A B C D E F
81 85 89 8D 91 95 99 9D A1 A5 A9 AD B1 B5 B9 BD
129 133 137 141 145 149 153 157 161 165 169 173 177 181 185 189
212
Using the Serial Gateway
Section 6-4
Serial Communications Board
Serial Communications Boards
Serial port
Serial port 1
Serial port 2
Serial port number
E4 hex (228 decimal)
E5 hex (229 decimal)
Serial port 1
Serial port 2
CPU Unit
Peripheral port
RS-232C port
CPU Unit
Serial port
Peripheral port
RS-232C port
Serial port number
FD hex (253 decimal)
FC hex (252 decimal)
Note
The following ladder program example shows how to return the Serial Gateway to the not prohibited status when the PMCR(260) instruction has been executed and the sequence is completed. (This example uses port number 1 of a Serial Communications Unit with unit number 0.)
W000.00
Execution condition
SET
1500.04
When execution condition W00000 is ON, the Serial Gateway Prohibited Flag
(port 1: Word n, bit 04: CIO 1500, bit 04) turns ON and the Serial Gateway is prohibited.
ASL
W000
At the same time, bit 00 of W000 is shifted one bit to the left.
W000.01 A20200 150915
Communications
Port Enabled
Flag for Port No.
0
Protocol
Macro
Executing
Flag (n+9, bit 15)
PMCR
C1
C2
S
D
When W00001 is ON, the Communications Enabled Flag for port No. 0
(internal logic port) is ON, and the Protocol Macro Executing Flag (port 1:
Word n+9, bit 15: CIO 150915) is OFF, the PMCR(260) instruction executes.
W000.02
Protocol Macro
Executing Flag
(n+9, bit 15)
ASL
W000
At the same time, bit 00 of W000 is shifted one bit to the left.
RSET
1500.04
When W00002 is ON, the sequence ends, and the Protocol Macro Executing
Flag (port 1: Word n+9, bit 15: CIO 150915) turns from ON to OFF, the Serial
Gateway Prohibited Flag (port 1: Word n, bit 04: CIO 150004) is reset to 0, and the Serial Gateway is no longer prohibited.
213
Protocol Conversion
Section 6-5
6-5 Protocol Conversion
6-5-1 Types of Protocol Conversion
Type of conversion
(from FINS)
Converting to
CompoWay/F
Converting to
Modbus-RTU
Converting to
Modbus-ASCII
Converting to
Host Link FINS
Serial port number on
Board/Unit
Frame before conversion
Destination address
Any address except Board/
Unit’s serial port number.
User-specified
FINS command
2803 hex
2804 hex
2805 hex
FINS data
CompoWay/F command
Modbus-RTU command
Modbus-ASCII command
Processing at
Board/Unit
CompoWay/F command with
FINS header removed sent to serial port.
Modbus-RTU command with
FINS header removed sent to serial port.
Modbus-ASCII command with
FINS header removed sent to serial port.
User-specified Transfers FINS command inside
Host Link header and terminator.
Protocol after conversion
(using serial communications)
CompoWay/F command
Modbus-RTU command
Modbus-ASCII command
FINS command for Host
Link communications
Target (communications partner)
OMRON Component (e.g., Temperature
Controller, Digital
Panel Meter, or
Smart Sensor)
Modbus-RTU
Slave-compatible device (including
OMRON 3G3JV,
3G3MV, and
3G3RV Inverters)
Modbus-ASCII
Slave-compatible device (e.g., temperature controller, indicator, or power monitor)
OMRON PLC
(CS/CJ Series, or
CVM1/CV
Series)
Note
For details on FINS response end codes, refer to Troubleshooting Using FINS
End Codes in 11-3-2 Serial Gateway (Serial Gateway or Protocol Macro
Mode).
6-5-2 Converting FINS to CompoWay/F
OMRON Components connected serially to a PLC via CompoWay/F can be accessed from the CPU Unit or PT using CompoWay/F commands enclosed in FINS messages.
• Sent FINS message: FINS header + FINS command code 2803 hex +
CompoWay/F command
• Message after conversion: CompoWay/F command
CPU Unit
(CMND(490) instruction) or
PT (Programmable Terminal)
FINS message
FINS header
2803 CompoWay/F command
CompoWay/F command encapsulated using FINS command 2803 hex
(Via network or CPU bus)
Serial Communications
Unit/Board
CompoWay/F command
CompoWay/F command
(RS-232C or RS-422A/485)
CompoWay/Fcompatible
OMRON
Component
214
Protocol Conversion
Section 6-5
CompoWay/F Slave-compatible Components
Temperature Controllers
Component
Thermac NEO
Thermac R
Model series
E5GN (G components)
E5CN
E5EN
E5AN
E5AR
E5ER
E5ZN
Timer/Counters
Smart Sensors
Cam Positioners
Safety Controllers
Plug-in Temperature Controllers
Digital Controller Boards
Digital Controllers
Timers/Counters
Digital Panel Meters Digital Panel Meters
Digital Load Cell Meters
Digital Rotary/Pulse Meters
Digital Incrementing Panel
Meters
Digital Time Interval Meters
Digital Temperature/Process
Meters
ZX Communications Interface
Units
---
---
E5ZM
ES100X
H8GN (G components)
K3GN (G components)
K3NX
K3NV
K3NR
K3NP
K3NC
K3NH
ZX-SF11
3F88L-160, 3F88L-162
F3SX
System Configuration Patterns
Sending FINS Messages Using CMND(490) in CPU Unit’s Ladder Program
The Board/Unit converts the FINS messages to CompoWay/F protocol for sending in this operation.
CPU Bus-to-Serial
Serial Communications Unit/Board
CPU Unit
CMND(490)
FINS header
2803
FINS message
CompoWay/F command
CompoWay/F command
RS-485 (CompoWay/F)
Access from CPU Unit (on the Same PLC)
Details
OMRON components connected serially to the Serial Communications Board/Unit using CompoWay/F can be accessed from a CPU Unit in the same PLC.
Routing tables to treat serial communications path as network
Optional
CompoWay/F-compatible
OMRON component
215
Protocol Conversion
Section 6-5
FINS message-to-Serial
CMND(490)
Access from CPU Unit (PLC on the Network)
FINS header
2803
FINS message
CompoWay/F command
Serial Communications Unit/Board
CPU Unit
Network (Ethernet, Controller
Link, DeviceNet)
Details
OMRON components connected serially to the Serial Communications Board/Unit using CompoWay/F can be accessed from a CPU Unit in a PLC connected to the network.
Routing tables to treat serial communications path as network
Optional
Protocol conversion
CompoWay/F command
RS-485 (CompoWay/F)
CompoWay/F-compatible
OMRON component
Executing Smart Active Parts Using an NS-series PT (Sending Internal FINS Messages)
The Board/Unit converts the FINS messages to CompoWay/F protocol for sending in this operation.
Access from PT on Ethernet or serial NT Link
NS-series PT
Ethernet
Smart Active Part
FINS message (sent internally)
FINS header 2803
CompoWay/F command
Serial Communications Unit/Board
CPU Unit
Details
Access via serial communications using
CompoWay/F is possible from a PT connected to the network by executing a
Smart Active Part that is connected serially, which automatically sends an internal
FINS command.
Routing tables to treat serial communications path as network
Optional
Protocol conversion
CompoWay/F command
RS-485 (CompoWay/F)
CompoWay/F-compatible
OMRON component
Note When the NS-series PT is connected serially to the PLC using serial communications mode
(1:N NT Links), and the NSseries PT sends FINS commands encapsulated in NT Link commands using Smart Active
Parts, the CPU Unit removes the
NT Link header, etc. from the received command, converting it to a FINS command, and transfers the command to the Serial
Communications Board/Unit.
The Serial Communications
Board/Unit uses the Serial Gateway to convert the command into the specified protocol. This operation enables serially connected devices to access the Serial
Communications Board/Unit from Smart Active Parts using an
NS-series PT.
Note
(1) The FINS header contains the following information.
• Remote destination network address (DNA)
216
Protocol Conversion
Section 6-5
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a network: Network address for specifying actual remote PLC.
• Remote destination node address (DA1)
• With routing tables that treat serial communications path as a network:
00 hex (local PLC’s internal communications) (For serial-to-serial-toserial conversion, increment the Host Link unit number by 1.)
• Without routing tables that treat serial communications path as a network: Node address for specifying actual remote PLC (For serial-toserial-to-serial conversion, increment the Host Link unit number by 1.)
• Remote destination unit address (DA2)
Unit address of serial port
(2) The contents of the CompoWay/F command enclosed in the FINS message that is sent is as follows:
Node number + subaddress + SID + command text (ASCII must be used.)
STX, ETX+BCC are not required when sending FINS. They are added automatically for serial communications.
6-5-3 CompoWay/F Connection Examples
Connection diagrams are provided here. OMRON recommends the use of shielded twisted-pair cables for actual wiring to enhance noise resistance. For
details on wiring methods, refer to 3-4 RS-232C and RS-422A/485 Wiring.
1:1 Connection Example Using RS-232C Port
Connection Example with E5CK Digital Controller
Serial Communications Unit/Board
Signal name Pin No.
RS-232C shield wire
Example: E5CK (OMRON Digital Controller)
RS-232C: Terminal Block
Terminal No.
Signal name
D-Sub 9-pin (Cable connector type: Male)
1:1 RS-485 Connection Example Using RS-422A/485 Port
Serial Communications Board/Unit
Signal name
Pin No.
Shield wire
RS-422A/485 interface
Component with RS-422A/485 communications function
(2-wire method)
Signal name
RS-422A/485 interface
Shell
D-Sub 9-pin (Cable connector type: Male)
Note
Be sure to connect terminating resistance of between 100 and 125
W
(1/2 W) to the terminals of the remote devices at either end of the RS-422A/485 transmission path. (Set the terminating resistance on the Board/Unit by turning
ON/OFF the Terminating Resistance Switch.)
217
Protocol Conversion
1:N RS-485 Connection Example Using RS-422A/485 Port
Serial Communications Board/Unit
Signal name
Pin No.
Component with RS-422A/485 communications function
(2-wire method)
Signal name
RS-422A/485 interface
RS-422A/485 interface
Section 6-5
Shell
D-Sub 9-pin (cable connector type: Male)
Component with RS-422A/485 communications function
(2-wire method)
Signal name
RS-422A/485 interface
Note
Be sure to connect terminating resistance of between 100 and 125
W
(1/2 W) to the terminals of the remote devices at either end of the RS-422A/485 transmission path. (Set the terminating resistance on the Board/Unit by turning
ON/OFF the Terminating Resistance Switch.)
6-5-4 Converting FINS to Modbus-RTU
Modbus-RTU Slave-compatible devices (including OMRON Inverters) connected serially to a PLC via Modbus-RTU can be accessed from the PLC or
PT using Modbus-RTU commands enclosed in FINS messages.
• Sent FINS message: FINS header + FINS command code 2804 hex +
Modbus-RTU command
• Message after conversion: Modbus-RTU command
CPU Unit
(CMND(490) instruction) or
PT (Programmable Terminal)
FINS header
2804 Modbus-RTU command
Modbus-RTU command encapsulated using FINS command 2804 hex
(Via network or CPU bus)
Serial Communications
Unit/Board
Modbus-RTU command
Modbus-RTU command
(RS-232C or RS-422A/485)
Modbus-RTU
Slavecompatible device
(OMRON
Inverter, etc.)
Modbus-RTU Slave-compatible OMRON Devices
Type Model series
Inverters 3G3JV
3G3MV
3G3RV
Temperature Controllers E5CN (New version)
218
Protocol Conversion
Section 6-5
System Configuration Patterns
Sending FINS Messages Using CMND(490) in CPU Unit’s Ladder Program
The Board/Unit converts the FINS messages to Modbus-RTU protocol for sending in this operation.
CPU Bus-to-Serial
Serial Communications Unit/Board
CPU Unit
Protocol conversion
CMND(490)
FINS header
2804
FINS message
Modbus-RTU command
Access from CPU Unit (on the Same PLC)
Details
OMRON Inverters connected serially to the Serial Communications Board/Unit using Modbus-RTU can be accessed from a CPU Unit in the same PLC.
Routing tables to treat serial communications path as network
Optional
Modbus-RTU command
RS-485 (Modbus-RTU)
Modbus-RTU
Slave device
(e.g, OMRON
Inverter)
FINS message-to-Serial
CMND(490)
FINS header
2804
FINS message
Modbus-RTU command
Serial Communications Unit/Board
CPU Unit
Network (Ethernet,
Controller Link,
DeviceNet)
Access from CPU Unit (on Network PLC)
Details
OMRON Inverters connected serially to the Serial Communications Board/Unit using Modbus-RTU can be accessed from a CPU Unit in a PLC connected to the network.
Routing tables to treat serial communications path as network
Optional
Protocol conversion
Modbus-RTU command
Modbus-RTU
Slave device
(e.g, OMRON
Inverter)
RS-485 (Modbus-RTU)
219
Protocol Conversion
Section 6-5
Executing Smart Active Parts Using an NS-series PT (Sending Internal FINS Messages)
The Board/Unit converts the FINS messages to Modbus-RTU protocol for sending in this operation.
Access from PT on Ethernet or serial NT Link
NS-series PT
Ethernet
Smart Active Parts
FINS message (sent internally)
FINS header 2804
Modbus-RTU command
Serial Communications Unit/Board
CPU Unit
Details
Access via serial communications using
Modbus-RTU is possible from a PT connected to the network by executing a
Smart Active Part that is connected serially, which automatically sends an internal
FINS command.
Routing tables to treat serial communications path as network
Optional
Protocol conversion
Modbus-RTU command
ORMON Inverter
RS-485 (Modbus-RTU)
Note When the NS-series PT is connected serially to the PLC using serial communications mode
(1:N NT Links), and the NSseries PT sends FINS commands encapsulated in NT Link commands using Smart Active
Parts, the CPU Unit removes the
NT Link header, etc. from the received command, converting it to a FINS command, and transfers the command to the Serial
Communications Board/Unit.
The Serial Communications
Board/Unit uses the Serial Gateway to convert the command into the specified protocol. This operation enables serially connected devices to access the Serial
Communications Board/Unit from Smart Active Parts using an
NS-series PT.
Note
(1) The FINS header contains the following information.
• Remote destination network address (DNA): Same as for CompoWay/F.
• Remote destination node address (DA1): Same as for CompoWay/F.
• Remote unit address (DA2): Same as for CompoWay/F.
(2) The contents of the Modbus-RTU command enclosed in the FINS message that is sent is as follows:
Slave address (binary) + FUNCTION code (binary) + Communications data (binary)
Start and CRC+End are not required when sending FINS. They are added automatically for serial communications.
220
Protocol Conversion
Section 6-5
6-5-5 Converting from FINS to Modbus-ASCII
Modbus-ASCII Slave-compatible devices connected serially to a PLC via
Modbus-ASCII can be accessed from the PLC using Modbus-ASCII commands enclosed in FINS messages.
• Sent FINS message: FINS header + FINS command code 2805 hex +
Modbus-ASCII command
• Message after conversion: Modbus-ASCII command
FINS message
CPU Unit
(CMND(490) instruction)
FINS header
2805
Modbus-ASCII command
Modbus-ASCII command encapsulated using FINS command 2805 hex
(Via network or CPU bus)
Serial Communications
Unit/Board
Modbus-ASCII command
Modbus-ASCII command
(RS-232C or RS-422A/485)
Modbus-
ASCII Slavecompatible device
System Configuration Patterns
Sending FINS Messages Using CMND(490) in CPU Unit’s Ladder Program
The Board/Unit converts the FINS messages to Modbus-ASCII protocol for sending in this operation.
Serial Communications Unit/Board
CPU Unit
Protocol conversion
CPU Bus-to-Serial
CMND(490)
FINS header
2805
FINS message
Modbus-ASCII command
Access from CPU Unit (on the Same PLC)
Details Routing tables to treat serial communications path as network
Optional Slaves connected serially to the Serial
Communications Board/Unit using Modbus-ASCII can be accessed from a CPU
Unit in the same PLC.
Modbus-ASCII command
Modbus-ASCII
Slave device
RS-485 (Modbus-ASCII)
FINS message-to-Serial
CMND(490)
Access from CPU Unit (on Network PLC)
Details Routing tables to treat serial communications path as network
Optional Slaves connected serially to the Serial
Communications Board/Unit using Modbus-ASCII can be accessed from a CPU
Unit in a PLC on the network.
FINS header
2805
FINS message
Modbus-ASCII command
Serial Communications Unit/Board
CPU Unit
Network (Ethernet, Controller
Link, DeviceNet)
Protocol conversion
Modbus-ASCII command
Modbus-ASCII
Slave device
RS-485 (Modbus-ASCII)
Note
(1) The FINS header contains the following information.
• Remote destination network address (DNA): Same as for CompoWay/F.
• Remote destination node address (DA1): Same as for CompoWay/F.
• Remote unit address (DA2): Same as for CompoWay/F.
(2) The contents of the Modbus-ASCII command enclosed in the FINS message that is sent is as follows:
Slave address (ASCII) + FUNCTION code (ASCII) + Communications data (ASCII)
221
Protocol Conversion
Section 6-5
The header “:” (3A hex) and LRC+CR/LF are not required when sending
FINS. They are added automatically for serial communications.
6-5-6 Converting from FINS to Host Link FINS
A PLC slave that is connected serially to the PLC master via Host Link can be accessed from the PLC master or personal computer (see note) using FINS messages. Accessing a device on another network via Host Link (serial communications) is also possible by using FINS messages. By converting the
FINS to Host Link FINS, the PLC can function as a Host Link master.
Note Applications such as CX-Programmer or CX-Protocol that use CX-
Server as a communications driver.
• Sent FINS message: FINS header + User-specified FINS command (see note 1)
• Message after conversion: FINS command enclosed in Host Link header and terminator (see note 2)
CX-Programmer or other application using CX-
Server or
CPU Unit
(CMND(490))
FINS message
User-specified
FINS command
(Via serial, network
,or CPU bus)
Host Link FINS command
Serial Communications
Unit/Board
Host Link header
User-specified FINS command
Terminator
FINS command encapsulated using Host Link
(RS-232C or RS-422A/485)
OMRON PLC (CS/CJ
Series, CVM1/CV
Series)
(To other network)
FINS command
System Configuration Patterns
Access from CX-Programmer (Sending Internal FINS Messages)
The Board/Unit converts the FINS messages to Host Link FINS for sending in this operation.
Serial-to-Serial
Serial Communications Unit/Board
CPU Unit
CX-Programmer, etc.
Protocol conversion
Peripheral or RS-232C port
Host Link header
User-specified
FINS command
Terminator
Host Link header
User-specified
FINS command
Terminator
Used as Host Link Master
Access from Serially Connected CX-Programmer
RS-422A/485 (Host Link)
Details
Personal computers (e.g., CX-
Programmer) connected serially (via tool bus or Host Link) to the PLC master can access a PLC slave that is connected serially to the PLC master via
Host Link.
Routing tables to treat serial communications path as network
Optional
CS/CJ-series or CVM1/CV-series PLC (Host Link Slave)
Use the following method to access the serially (serial-to-serial) connected
PLC from the CX-Programmer.
222
Protocol Conversion
Section 6-5
System Configuration Example
CX-Programmer Ver. 5.0 or later
Serial Communications Board/Unit with unit Ver. 1.2 or later
(Select SCU (Unit 0 to 15) in the UNIT field.)
Set the relay PLC.
(Select in the Change PLC Dialog Box.)
Serial Gateway function port (Select port 1/2 in the
PORT field according to the calculated address.)
PLC name: PLC2
Serial
Gateway
Host Link FINS
Network type: Select [PLC2].
Select the Use SYSWAY with the port option in the Host Link (SYSWAY) settings.
PLC name: PLC1
Target PLC Host Link unit number
Enter the Host Link unit number in the
Host Link Unit Number field for the target
PLC in the Host Link (SYSWAY) settings.
1,2,3...
1.
Register the PLC to be connected serially (using Host Link FINS) in the project gateway (e.g., PLC2).
2.
In the Change PLC Dialog Box of the target PLC (e.g., PLC1), select the relay PLC (gateway PLC) in the Network Type pull-down menu (e.g.,
[PLC2] (See note.)) and click the Settings Button to the right of the Network Type pull-down menu.
Note The PLC name enclosed in square brackets (e.g., [PLC2]) indicates the gateway PLC.
Select the PLC to be used as the relay PLC (e.g., [PLC2]) in the
Network Type pull-down menu.
3.
The Network Settings Dialog Box will be displayed. Click the Guide for Se-
rial Gateway Button.
4.
The Serial Gateway Guide Dialog Box will be displayed.
Select the unit and the port number under the Calculate Address Area, the serial port number address is automatically calculated in the Calculated
Address Field.
Select the Use SYSWAY with the port option, and enter the actual Host
Link unit number for the target (communications partner) PLC in the Host
Link Unit Number field (see note).
Finally, click the Apply Button.
223
Protocol Conversion
Section 6-5
The Serial
Communications port address is automatically calculated.
Select the Unit.
Select the port.
Select this option.
Enter the unit number for the actual Host Link (values are incremented by 1 automatically).
FINS message
User-specified
FINS command
Serial Communications Unit/Board
CPU Unit
Note
When using the CX-Programmer, enter the actual Host Link unit number. Do not add 1 to the value. The CX-Programmer will automatically add 1 internally.
Access from CX-Programmer Connected to Network
Network-to-Serial
CX-Programmer, etc.
Network (Ethernet, Controller
LInk, DeviceNet)
Details
Personal computers (e.g., CX-Programmer) connected through the network to the PLC master can access a PLC slave that is connected serially to the PLC master via Host Link.
Routing tables to treat serial communications path as network
Required
Protocol conversion
Host Link header
User-specified
FINS command
Terminator
Used as Host
Link Master
RS-422A/485
(Host Link)
CS/CJ-series or CVM1/CV-series PLC (Host Link Slave)
Network-to-Serial-to-Network
CX-Programmer, etc.
FINS message
User-specified
FINS command
Serial Communications Unit/Board
CPU Unit
Network (Ethernet,
Controller LInk, DeviceNet)
Note This configuration can be connected to other networks, as shown below.
Details
Personal computers (e.g., CX-Programmer) connected through the network to the PLC master can access a PLC on another network via a PLC slave that is connected serially to the PLC master via Host
Link.
Routing tables to treat serial communications path as network
Required
Protocol conversion
Used as Host
Link Master
Host Link header
User-specified
FINS command
User-specified
FINS command
Terminator
RS-422A/485
(Host Link)
CS/CJ-series or CVM1/CVseries PLC
(Host Link
Slave)
Network (Ethernet,
Controller LInk,
DeviceNet)
224
Protocol Conversion
Section 6-5
Sending FINS Messages or Sending/Receiving Data Using CMND(490), RECV(098),
SEND(090) in the CPU Unit’s Ladder Program
The Board/Unit converts the FINS messages to Host Link FINS in this operation.
Access from CPU Unit (on the Same PLC
)
CPU bus-to-Serial
Serial Communications Unit/Board
Protocol conversion
CPU Unit
FINS message
User-specified FINS command
CMND(490) or
SEND(090)/
RECV(098)
Host Link header
User-specified
FINS command
Terminator
Details
Slave PLCs connected serially to the Serial Communications Board/
Unit using Host Link can be accessed from the CPU Unit in the same PLC.
Routing tables to treat serial communications path as network
Optional
RS-422A/485
(Host Link)
Used as Host
Link Master
CS/CJ-series or CVM1/CV-series PLC (Host Link Slave)
Network-to-Serial
Serial Communications Unit/Board
CPU Unit
CMND(490) or
SEND(090)/RECV(098)
Access from CPU Unit (on Network PLC)
FINS message
User-specified
FINS command
Network (Ethernet,
Controller LInk, DeviceNet)
Details
Slave PLCs connected serially to the Serial Communications Board/
Unit using Host Link can be accessed from a CPU Unit in a
PLC connected to the network.
Routing tables to treat serial communications path as network
Required
Protocol conversion
Host Link header
User-specified
FINS command
Terminator
Used as Host
Link Master
RS-422A/485
(Host Link)
CS/CJ-series or CVM1/CV-series PLC (Host Link Slave)
Note This configuration can be connected to other networks, as shown below
Network-to-Serial-to-Network
Serial Communications Unit/Board
CPU Unit
Details
CMND(490) or
SEND(090)/
RECV(098)
FINS message
User-specified
FINS command
Network (Ethernet, Controller
LInk, DeviceNet)
CPU Units in PLCs connected to the network can access a PLC on another network via a PLC slave that is connected serially to the
Serial Communications Board/Unit via Host Link.
Routing tables to treat serial communications path as network
Required
Protocol conversion
Host Link header
User-specified
FINS command
Terminator
Used as Host
Link Master
User-specified
FINS command
RS-422A/485
(Host Link)
CS/CJ-series or
CVM1/CV-series PLC
(Host Link Slave)
Network (Ethernet,
Controller LInk, DeviceNet)
Note
(1) The FINS header contains the following information.
225
Serial Gateway
Section 6-6
• Remote destination network address (DNA)
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a network: Unit address of serial port.
• Remote destination node address (DA1)
• With routing tables that treat serial communications path as a network:
Unit number for Host Link incremented by 1 (1 to 32)
• Without routing tables that treat serial communications path as a network: Unit number for Host Link incremented by 1 (1 to 32)
• Remote destination unit address (DA2)
Any unit address except that for the serial port (The destination for the
FINS message must not be the serial port of the Board/Unit.)
• FINS command code: Any
(2) When creating Host Link FINS command frames using the CMND(490) instruction, always set the unit number for Host Link incremented by one
(1 to 32) for the remote destination (send destination) node address
(word C+3, bits 08 to 15 of the CMND(490) instruction). Do not set the unit number of the actual Host Link slave (0 to 31). Using the Host Link unit number without incrementing by one will access the PLC with the entered Host Link unit number less one.
For example, specify the remote PLC with Host Link unit number 2 by entering 3 for the remote destination node address. If 2 is entered, the PLC with Host Link unit number 1 will be accessed.
To access a PLC on a Host Link FINS network using the Serial Gateway from CX-Programmer, however, enter the actual Host Link unit number, without incrementing by one. (Select Change PLC, click the Display Se-
rial Gateway Guide Button, and set unit number in the Host Link
SYSWAY Settings field of the Serial Gateway Guide Dialog Box.
(3) The contents of the FINS command enclosed by the Host Link header and terminator is as follows:
@+Host Link unit number+Host Link header FA+FINS header+FINS command+Text+FCS+*+CR
6-6 Serial Gateway
6-6-1 Serial Gateway Execution Timing for Protocol Macros
The execution timing for the Serial Gateway during execution of protocol macros is described here. The operation when the FINS command is received with the Serial Gateway enabled during protocol macro mode is as follows:
• Next step contains the RECEIVE command: Priority is given to the
RECEIVE command, and the Serial Gateway is executed in the next step.
(See note 1).
• Next step contains any command except the RECEIVE command (SEND,
SEND&RECV, WAIT, FLUSH, OPEN, or CLOSE): Priority is given to the
Serial Gateway, for which conversion, transmission, and response reception processing is executed using interrupts between steps (see note 2).
Note
(1) The reception buffer is cleared during transfer processing using the Serial
Gateway. Therefore, when the FINS command is received, and the command in the following step is the RECEIVE command, the RECEIVE command takes priority over the Serial Gateway.
226
Serial Gateway
Section 6-6
(2) The Serial Gateway is executed using interrupts between steps. The interrupts are not executed within a step. (Therefore, the Serial Gateway is never executed after the SEND command in a SEND&RECV command.)
The processing flowchart is as follows:
Serial Gateway enabled, FINS command received
Command in next step
Any command except RECEIVE
RECEIVE command
RECEIVE command takes priority, and the next step is executed.
Serial Gateway takes priority and conversion, transmission, and response reception processing is executed on an interrupt between steps.
The next queued step is executed.
The details of the processing flow are as follows:
Protocol Macro Priority over Serial Gateway
When the Serial Gateway is enabled during protocol macro mode and a FINS command is received and if the command in the next step is a RECEIVE command, this next step will be executed without executing conversion, transmission, and response reception processing for the Serial Gateway.
After the step containing the RECEIVE command is completed, if the next step contains any command except the RECEIVE command (SEND,
SEND&RECV, WAIT, FLUSH, OPEN, or CLOSE), the protocol macro communications sequence is temporarily suspended before the next step is executed, and the FINS command conversion and transmission is executed on an interrupt between steps using the Serial Gateway.
Until the response is received, the command in the step is not executed. After the response is received, the protocol macro is resumed, starting execution from the communications sequence step that was suspended.
The step that is executing when a FINS command is received is not interrupted. Therefore, if the WAIT command is executing, the Serial Gateway will not be executed.
Immediate Execution of Serial Gateway
When the Serial Gateway is enabled during protocol macro mode and a FINS command is received and if the command in the next step is any command except the RECEIVE command (SEND, SEND&RECV, WAIT, FLUSH, OPEN, or CLOSE), the protocol macro communications sequence is temporarily suspended before the next step is executed, and the FINS command conversion and transmission is executed on an interrupt between steps using the Serial
Gateway.
Until the response is received, the command within the next step is not executed. After the response is received, the protocol macro is resumed, starting execution from the communications sequence step that was suspended.
227
Serial Gateway
Section 6-6
Step n
SEND&RECV
Reception
FINS command
Step n+1
(The next step is a RE-
CEIVE command, so the
RECEIVE command is executed and the Serial
Gateway waits.)
RECEIVE
(The next step is a SEND command (not RECEIVE) so the
Serial Gateway is executed.)
Sequence temporarily suspended
CompoWay/F or other command
CompoWay/F or other response
Step n+2
Sequence resumes
SEND
Note
If a multiple-frame command (see note) protocol macro is sent during protocol macro execution, set the Serial Gateway mode status to prohibited (in the CIO
Area). Otherwise, a FINS message converted using Serial Gateway will interrupt between steps of the executing protocol macro, and may occur in between frames of the multiple-frame command.
Note A multiple-frame command is a command in which the protocol macro command text is divided into multiple frames that are sent in sequence.
6-6-2 Serial Gateway Timeout Monitoring
The Serial Gateway supports the following two timeout monitoring functions.
These functions can be used to monitor the reception processing time of the remote device and the wait time of the Serial Gateway during execution of a protocol macro.
Response Timeout Monitoring (Serial Gateway Mode/Protocol Macro Mode)
During Serial Gateway mode or protocol macro mode, the time is monitored from when the message converted into the specified protocol by Serial Gateway is sent until a response is received from the remote device. (The default is
5 s. The setting range for a user-specified value is between 0.1 and 25.5 s.
This function is set in the DM Area.)
If a response is not received at the serial port within the set time, a FINS error response is returned to the source of the FINS command (end code: 0205 hex
(response timeout)). If a response is received after the timeout has occurred, however, the response received for each protocol is discarded and a FINS response is not returned to the source of the FINS command.
FINS command received
FINS transmission source:
FINS command
Response timeout monitoring time
FINS error response
0205 hex (Response timeout)
Time
Received response is discarded
Board/Unit:
Serial Gateway
Protocol conversion/transmission
Send in specified protocol
Receive processing
Remote device:
Receive
Actual response received after timeout
Note
If a Serial Gateway response timeout occurs, CIO word n+8/n+18, bit 05
(Serial Gateway Send Start Timeout or Serial Gateway Response Timeout)
228
Serial Gateway
Section 6-6
will turn ON (1). Therefore, if the end code 0205 hex is returned to the source of the FINS command and CIO word n+8/n+18, bit 05 is ON, a Serial Gateway response timeout has occurred.
Send Start Timeout Monitoring (Protocol Macro Mode Only)
During protocol macro mode, the time from when the FINS command is received until it is converted and starts sending can be monitored. (The default is 5 s. The setting range for a user-specified value is between 0.1 and
25.5 s. This function is set in the DM Area.)
If transmission does not start within the set monitoring time after receiving the
FINS command, a FINS error response (end code: 0204 hex (remote node busy)) is returned to the source of the FINS command (the FINS command is discarded without send processing being executed).
As a result, the suspended step transition can be monitored at the source of the FINS command. Step transition is suspended either due to the next step being a RECEIVE command or the current command is executing (WAIT,
SEND&RECV, RECEIVE, etc.).
FINS transmission source:
Board/Unit:
Protocol macro sequence
FINS command received
RECEIVE execution when next step at remote device contains RECEIVE command
Step n
RECEIVE command
Shift to Serial
Gateway
Serial Gateway execution when next step does not contain a
RECEIVE command
Time
Step n+1
Any command except RECEIVE
Serial Gateway execution (protocol conversion/transmission)
Protocol macro sequence resumes
Serial Gateway execution timing
Remote device:
Send in specified protocol
Send start timeout monitoring (monitors this time)
Receive processing
Response received
(1) If a Serial Gateway send start timeout occurs, CIO word n+8/n+18, bit 05
(Serial Gateway Send Start Timeout or Serial Gateway Response Timeout) will turn ON (1).
(2) When the Serial Gateway is executed during protocol macro execution, the communications sequence contents and the FINS command reception timing may suspend step transition of the communications sequence
(when the next step does not contain the RECEIVE command, the Serial
Gateway will be executed by interrupting the sequence before the next step, and the step transition will be suspended).
Use the Serial Gateway send start timeout function to monitor at the source of the FINS command whether step transition in the communications sequence has been suspended due to execution of the Serial Gateway. If the converted command does not start to be sent within the set time, either retry executing the FINS command or change the communications sequence.
229
Conditions Requiring Routing Tables
Section 6-7
6-6-3 Other Functions
Serial Gateway Send Delay (Serial Gateway Mode/Protocol Macro Mode)
The send delay function is used to prevent immediate transfer to the serial port of a FINS command after it has been received by the Serial Communications Unit/Board and converted into the specified protocol. With this function, the converted command is sent to the serial port after a set time. (The default is 0 s, and the setting range for user-specified value is 0 to 300 s. Set this function in the DM Area.)
For example, use the send delay function to prevent loss of send frames when receive processing at the connected device does not provide sufficient speed.
FINS command received
Time
FINS transmission source:
FINS command
Board/Unit:
Conversion
Send delay
Send
Receive processing
Remote device:
Serial Gateway FINS Message Queuing
The Serial Communications Unit/Board can hold processing on standby for up to five FINS commands for the Serial Gateway. If a sixth FINS command is received at the serial port, a FINS error response (end code: 2605 hex (service executing)) will be returned to the source of the FINS command.
6-7 Conditions Requiring Routing Tables
6-7-1 Treating Serial Communications Paths as Networks
When the Serial Gateway is executed, routing tables are either required or optional as follows:
• Routing tables are required to treat a serial communications path as a network when converting FINS messages to Host Link FINS for serial conversion via the network.
• Under other conditions, routing tables are optional.
The details are provided in the following tables.
Conditions Requiring Routing Tables According to Target
Target
PLC (CS/CJ Series, CVM1/CV
Series)
Protocol conversion
Host Link
FINS
Case Example
Routing FINS network including serial communications path (for
Serial Gateway)
Serial communications path connection only
Network-toserial conversion
Serial-toserial conversion
Routing tables for treating serial communications path as network
Required
Optional
230
Conditions Requiring Routing Tables
Section 6-7
Any component except PLC
Target Protocol conversion
Case Example
OMRON Component
CompoWay/
F
Modbus-RTU
Slave (including
OMRON Inverter)
Modbus-ASCII
Slave
Modbus-
RTU
Modbus-
ASCII
Routing FINS network including serial communications path (for
Serial Gateway)
Serial communications path connection only
Network-toserial conversion
Serial-toserial conversion
Routing tables for treating serial communications path as network
Optional
Optional
Specifying Address in FINS Command Source
Target
PLC (CS/CJ Series,
CVM1/CV Series)
Any component except
PLC
OMRON
Component
Modbus-
RTU Slave
(including
OMRON
Inverter)
Modbus-
ASCII Slave
Protocol conversion
Host Link
FINS
CompoWay/
F
Modbus-
RTU
Modbus-
ASCII
Routing tables for treating serial communications path as network
Remote network address
Created Network address assigned to the serial port according to the routing tables
Not created Serial port unit address
FINS header
Remote node address
Host Link unit number incremented by
1 (1 to 32)
(See note.)
Created Network address assigned to the serial port according to the routing tables
Not created Network address for specifying the actual remote PLC
00 hex (indicates communications in local PLC)
Node address for specifying the actual remote PLC
Remote unit address
Must be the actual unit address of the destination unit.
Must be the unit address of the serial port.
Note
To access from a CX-Programmer, Select Change PLC
-
Serial Gateway
Guide, and enter the actual Host Link unit number, The CX-Programmer will automatically increment the value by one.
6-7-2 Using a PLC as the Target
Network-to-Serial Conversion
Routing tables are required to enable the serial communications path to be treated as a network.
231
Conditions Requiring Routing Tables
Required Routing Tables
Section 6-7
Specify the addresses as shown in the following example.
FINS command sent
Address Specification
Address
Remote network address
Contents
(1) Serial communications path network address
Remote node address
Remote unit address
(2) Unit No. for Host Link incremented by 1.
(3) Actual remote unit address for
FINS command
Example
A s+1
CPU Unit: 00 hex
FINS network
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC
Routing tables for treating serial communications path as a network
Unit number
Network address
80 hex (128 decimal)
Calculated from unit number: 0, port 1
A
Serial communications path (Host Link FINS)
(1) Network address:
To serial communications path network address A
Target: PLC
(2) Node address: Unit numbers for Host Link (0 to 31) + 1
(3) Unit address: E.g., 00 hex for CPU Unit
Serial-to-Serial Conversion
Routing tables to enable the serial communications path to be treated as a network are optional.
Without Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Serial communications path (Host Link FINS)
Address Specification
Address
Remote network address
Contents
(1) Serial communications path unit address
Remote node address
Remote unit address
(2) Unit No. for Host Link incremented by 1.
(3) Actual remote unit address for FINS command
Example
80 hex (128 decimal)
Calculated from Unit No. 0, port 1 s+1
CPU Unit: 00 hex
Serial Communications Unit/Board
E.g., Unit number 0, port 1
No routing tables required to treat serial communications path as a network
Serial communications path (Host Link FINS)
(1) Network address:
To serial communications path unit address (e.g., 80 hex)
Target: PLC
(2) Node address: Unit numbers for Host Link (0 to 31) + 1
(3) Unit address: E.g., 00 hex for CPU Unit
232
Conditions Requiring Routing Tables
With Routing Tables
Section 6-7
Specify the addresses as shown in the following example.
FINS command sent
Address Specification
Address
Remote network address
Contents
(1) Serial communications path unit address
Remote node address
Remote unit address
(2) Unit No. for Host Link incremented by 1.
(3) Actual remote unit address for FINS command
Example
A s+1
CPU Unit: 00 hex
Serial communications path (Host Link FINS)
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC
Routing tables for treating serial communications path as a network
Unit number
80 hex (128 decimal)
Calculated from Unit No. 0, port 1
Network address
A
Serial communications path (Host Link FINS)
(1) Network address:
To serial communications path network address A
Target: PLC
(2) Node address: Unit numbers for Host Link (0 to 31) + 1
(3) Unit address: E.g., 00 hex for CPU Unit
6-7-3 Using a non-PLC Component as the Target
Network-to-Serial Conversion
Routing tables to enable the serial communications path to be treated as a network are optional.
Without Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Address Specification
Address
Remote network address
Remote node address
Remote unit address
Contents
Address to distinguish standard PLC
(1) Network address
(2) Node address
Example
N m
Serial port unit address
80 hex (128 decimal)
Calculated from unit number 0, port 1
FINS network: Network address N
Address to distinguish standard PLC
(1) Network address: To N
(2) Node address: To m
Unit address:
To serial port unit address (e.g., 80 hex)
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC
No routing tables required to treat serial communications path as a network
Serial communications path
(CompoWay/F, Modbus)
Target: OMRON Component or Modbus Slave
233
Conditions Requiring Routing Tables
With Routing Tables
Section 6-7
Specify the addresses as shown in the following example.
FINS command sent
Address Specification
Address
Remote network address
Contents
(1) Serial communications path network address
Remote node address
(2) Local PLC internal communications
Remote unit address
(3) Serial port unit address
Example
A
00 hex
80 hex (128 decimal)
Calculated from Unit No. 0, port 1
Node address:
Local PLC internal communications
To 00 hex
Unit address:
To serial port unit address
(e.g., 80 hex)
FINS network
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC
Routing tables for treating serial communications path as a network
Unit number
80 hex (128 decimal)
Calculated from Unit No. 0, port 1
Network address
A
Serial communications path
(CompoWay/F, Modbus)
(1) Network address:
To serial communications path network address A
Target: OMRON Component or Modbus Slave
Serial-to-Serial Conversion
Routing tables to enable the serial communications path to be treated as a network are optional.
Without Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Serial communications path (Host Link FINS)
Address for standard direct serial connection:
(1) Network address:
Direct serial connection
To 00 hex
(2) Node address: Local
PLC internal communications
To 00 hex
Unit address: To serial port unit address
(e.g., 80 hex)
Address Specification
Address
Remote network address
Remote node address
Remote unit address
Contents
Address for standard direct serial connection
Direct serial connection (See note.) ternal communications
Serial port unit address
Serial Communications Unit/Board
E.g., Unit number 0, port 1
Example
00 hex (See note.)
00 hex
80 hex (128 decimal)
Calculated from unit number 0, port 1
Note: Serial port unit address (e.g., 80 hex) can be set
No routing tables required to treat serial communications path as a network
Serial communications path
(CompoWay/F, Modbus)
Target: OMRON Component or Modbus Slave
With Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Address Specification
Address
Remote network address
Contents
(1) Serial communications path network address
Remote node address
(2) Local PLC internal communications
Remote unit address (3) Serial port unit address
Example
A
00 hex
80 hex (128 decimal)
Calculated from unit number 0, port 1
Serial communications path (Host Link FINS)
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC
Routing tables for treating serial communications path as a network
Unit number
Network address
80 hex (128 decimal)
Calculated from Unit No. 0, port 1
A
Unit address: To serial port unit address (e.g.,
80 hex)
Serial communications path
(CompoWay/F, Modbus)
(1) Network address:
To serial communications path network address A
Target: OMRON Component or Modbus Slave
234
Conditions Requiring Routing Tables
Section 6-7
Serial-to-Serial-to-Serial Conversion
Routing tables to enable the serial communications path to be treated as a network are optional.
Without Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Serial communications path (Host Link FINS)
(1) Network address:
To PLC_1 serial port unit address (e.g., 89 hex)
Serial communications path (Host Link FINS)
(2) Node address: PLC_2 unit numbers for Host Link
(0 to 31) + 1
Address Specification
Address
Remote network address
Contents
PLC_1 serial port unit address
Example
89 hex (137 decimal)
Calculated from PLC_1 unit number 2, port 2
Remote node address
Remote unit address
PLC_2 unit number for
Host Link + 1
PLC_2 serial port unit address s+1
80 hex (128 decimal)
Calculated from unit number
0, port 1
Serial Communications Unit/Board
E.g., Unit number 2, port 1
PLC_1
No routing tables required to treat serial communications path as a network
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC_2
No routing tables required to treat serial communications path as a network
(3) Unit address: To
PLC_2 serial port unit address (e.g., 80 hex)
Serial communications path
(CompoWay/F, Modbus)
Target: OMRON Component or Modbus Slave
With Routing Tables
Specify the addresses as shown in the following example.
FINS command sent
Serial communications path (Host Link FINS)
(2) Node address:
PLC_2 unit numbers for
Host Link (0 to 31) + 1
Address Specification
Address
Remote network address
Remote node address
Remote unit address
Contents
PLC_2 serial communications path network address A
Example
A
PLC_2 unit number for Host
Link + 1 s+1
PLC_2 serial port unit address
80 hex (128 decimal)
Calculated from unit number
0, port 1
Serial Communications Unit/Board
E.g., Unit number 2, port 1
Serial communications path (Host Link FINS)
PLC_1
No routing tables required to treat serial communications path as a network
Serial Communications Unit/Board
E.g., Unit number 0, port 1
PLC_2
Routing tables for treating serial communications path as a network
Unit number
80 hex (128 decimal)
Calculated from unit number 0, port 1
Network address
A
(3) Unit address: To
PLC_2 serial port unit address (e.g., 80 hex)
Serial communications path (Compo-
Way/F, Modbus)
(1) Network address: To PLC_1 serial communications path network address A
Target: OMRON Component or Modbus Slave
6-7-4 Explanation
To treat the serial communications path as a network, the serial port itself is recognized as a Communications Unit and is allocated a network address.
Serial Communications Unit/Board
Serial port
Communications
Unit
Unit address U
(See note.)
Expressed as:
Local network table in routing tables
Unit number
(See note.)
U
Network address n
Serial communications path
Network
Assigned to network address n
Set correspondence
Note: The unit number is set as a
CPU Bus Unit for Communications Units, but the unit address (80 hex/81 hex + unit number
× 4 hex, as a decimal) is set for the serial port.
235
Conditions Requiring Routing Tables
Section 6-7
The CX-Net in the CX-Programmer is used to set the relationship between the serial port’s unit address and the allocated network address in the local network tables of the routing tables. These settings are then transferred to the
CPU Unit to which the Serial Communications Unit/Board is mounted.
CX-Net in CX-
Programmer
Local network table in routing tables
Unit number
U n
Network address
Serial Communications Unit/Board
PLC
Set the unit address
U as a decimal for the unit number.
Local network table
Serial communications path
Unit address U (80 hex/81 hex
+ unit number
× 4 hex)
Network address n
• Serial Port 1 Unit Addresses
Unit number
Hexadecimal
Decimal
0 1 2 3 4 5 6 7 8 9 A B C D E F
80 84 88 8C 90 94 98 9C A0 A4 A8 AC B0 B4 B8 BC
128 132 136 140 144 148 152 156 160 164 168 172 176 180 184 188
• Serial Port 2 Unit Addresses
Unit number
Hexadecimal
Decimal
0 1 2 3 4 5 6 7 8 9 A B C D E F
81 85 89 8D 91 95 99 9D A1 A5 A9 AD B1 B5 B9 BD
129 133 137 141 145 149 153 157 161 165 169 173 177 181 185 189
These settings enable the serial communications path to be treated as a single FINS network. Further, the network address allocated to the serial port can be specified in the destination network address part of the FINS message. This enables messages to passed on to serial ports in a system comprised of multiple networks connected to a single PLC (including the serial communications path).
FINS message
Serial Communications Unit/Board
CPU Unit
Routing enabled
Local network table
Serial communications path
Specify on which path to send the message.
Reasons for Routing Tables
CompoWay/F, Modbus-RTU, Modbus-ASCII Protocol Conversion
Routing tables are not required to enable serial communications paths to be treated as networks. (The serial port can be specified in the node without using routing tables by specifying the node to which the Board/Unit is connected, and specifying the unit address as that of the serial port.)
236
Communications Frames
Section 6-8
Host Link FINS Protocol Conversion and Use of Network
Routing tables are required to enable the serial communications path to be treated as a network. This is because with Host Link FINS, the FINS remote node address is used to specify the target (communications partner PLC that is the Host Link slave). Therefore, the node to which the Board/Unit is mounted cannot always be specified, depending on the FINS remote node address. To specify the Unit at the target requires the FINS remote unit address. Therefore, the serial port cannot always be specified depending on the FINS unit address.
The network address for the serial communications path is used to specify from the network the node to which the Board/Unit is mounted and the serial port. Therefore, routing tables must be used to enable the serial communications path to be treated as a network.
Host Link FINS Protocol Conversion and Use of Serial Connection
Routing tables are not required to enable serial communications paths to be treated as networks. The serial port in the node can be specified without routing tables by specifying the network address as the unit address of the serial port.
6-8 Communications Frames
6-8-1 CompoWay/F
Command Frame
Frame before Conversion
FINS header
Remote network address
(DNA)
Remote node address
(DA1)
Remote unit address
(DA2)
Serial port allocated address or local network address
00 hex or local network node address
Serial port unit address
Etc.
FINS command
MRC SRC
28 03
CompoWay/F
(See note.)
Node No.
(
× 101)
(
× 102)
(ASCII code
2 bytes)
Subaddress
"00"
SID
"0"
(ASCII
(ASCII code
3030 hex) code
30 hex) etc.
Command
(MRC, SRC)
(ASCII code
4 bytes)
Text
(ASCII code)
Frame after Conversion
CompoWay/F
STX
(02 hex)
Node No.
(
× 101)
(
× 102)
Subaddress
"00"
(ASCII code (ASCII code
2 bytes) 3030 hex) etc.
SID
"0"
(ASCII code
30 hex)
Command
(MRC, SRC)
(ASCII code
4 bytes)
Text
(ASCII code)
ETX
(03 hex)
BCC
Note
CompoWay/F commands use ASCII as the transmission code. Therefore, be sure to use ASCII for the CompoWay/F command after the FINS command code 2803 hex (from node number to text) using CMND(490) or other instruction.
Example: If the CompoWay/F command MRC SRC is “01” “02” (where the quotation marks (“ ”) indicate ASCII characters), 0, 1, 0, 2 must be treated as
ASCII characters. Therefore, set “01” as 3031 hex (not 01 hex), and “02” as
3032 hex (not 02 hex).
237
Communications Frames
Section 6-8
Further, to write the CompoWay/F command to the command storage area using CMND(490) in frame order (without creating empty bytes), the SID component of the CompoWay/F command requires 1 byte of ASCII as 30 hex, so the subsequent components (s+3 and afterwards) must be set in one byte each.
Response Frame
Frame before Conversion
STX
(02 hex)
Node No.
(
× 101)
(
× 102)
(ASCII code
4 bytes)
Subaddress
"00"
(ASCII code
3030 hex) etc.
CompoWay/F
End code
(ASCII code
8 bytes)
Command
(MRC,
SRC)
(ASCII code
8 bytes)
Response
(MRES,
SRES)
(ASCII code
8 bytes)
Text
(ASCII code)
ETX
(03 hex)
BCC
Frame after Conversion
Remote network address
(DNA)
FINS header
Remote node address
(DA1)
Remote unit address
(DA2) etc.
FINS command
MRC
Serial port allocated address
00 hex Serial port unit address
28
SRC
03
FINS end code
MRES SRES
Userspecified
Userspecified
Node No.
(
× 101)
(
× 102)
(ASCII code
2 bytes)
CompoWay/F
(See note.)
Subaddress
"00"
(ASCII code
3030 hex) etc.
End code
(ASCII code
2 bytes)
Command
(MRC,
SRC)
(ASCII code
4 bytes)
Response
(MRES,
SRES)
(ASCII code
4 bytes)
Text
(ASCII code)
6-8-2 Modbus-RTU
Command Frame
Frame before Conversion
Remote network address
(DNA)
FINS header FINS command
Remote node address
(DA1)
Remote unit address
(DA2)
Etc.
MRC SRC
Serial port allocated address or local
00 hex Serial port or local unit address network address network node address
28 04 Slave address
(1 byte)
Modbus-RTU
(command section only)
FUNCTION code(1 byte)
Communications data
(n bytes)
Frame after Conversion
Start (silent interval of
3.5
characters)
(See note.)
Slave address
(1 byte)
FUNCTION code
(1 byte)
Modbus-RTU frame
Communications data
(n bytes)
Error check
CRC
(1 byte)
End (silent interval of
3.5
characters)
(See note.)
Note
The silent interval in the Modbus-RTU frame is automatically generated by the
Serial Communications Board/Unit.
238
Communications Frames
Response Frame
Frame before Conversion
Start (silent interval of
3.5
characters)
(See note.)
Slave address
(1 byte)
FUNCTION code
(1 byte)
Modbus-RTU frame
Communications data
(n bytes)
Error check
CRC
(1 byte)
End (silent interval of
3.5
characters)
(See note.)
Section 6-8
Frame after Conversion
Remote network address
(DNA)
FINS header FINS command FINS end code
SRC MRES SRES Remote node address
(DA1)
Remote unit address
(DA2)
Etc.
MRC
Serial port allocated address or local network address
00 hex Serial port or local unit address network node address
28 04 Userspecified
Userspecified
Slave address
(1 byte)
Modbus-RTU
(command section only)
FUNCTION code (1 byte)
Communications data
(n bytes)
6-8-3 Modbus-ASCII
Command Frame
Frame before Conversion
Remote network address
(DNA)
FINS header
Remote node address
(DA1)
Remote unit address
(DA2)
Etc.
FINS command
MRC SRC
Serial port allocated address or local network address
00 hex Serial port unit address or local network node address
28 05
Modbus-ASCII
(command section only)
Slave address
(ASCII code
2 characters:
4 bytes)
FUNCTION code
(ASCII code
2 characters:
4 bytes)
Communications data
(ASCII code n characters)
Frame after Conversion
Header
":"
(ASCII code
3A hex)
Slave address
(ASCII code
2 characters:
4 bytes)
FUNCTION code
(ASCII code
4 bytes)
Modbus-ASCII frame
Communications data
(ASCII code n characters)
2 characters:
CR
(0D hex)
LF
(0A hex)
239
Communications Frames
Response Frame
Frame before Conversion
Modbus-ASCII frame
Header
":"
(ASCII code
3A hex)
Slave address FUNCTION code
(ASCII code
2 characters:
4 bytes)
(ASCII code
2 characters:
4 bytes)
Communications data
(ASCII code n characters) or error code
CR
(0D hex)
LF
(0A hex)
Section 6-8
Frame after Conversion
Remote network address
(DNA)
FINS header
Remote node address
(DA1)
Remote unit address
(DA2)
Etc.
FINS command FINS end code
MRC SRC MRES SRES
Serial port allocated address or local network address
00 hex Serial port unit address or local network node address
28 05 Userspecified
Userspecified
Modbus-ASCII
(command section only)
Slave address
(ASCII code
2 characters:
4 bytes)
FUNCTION code
(ASCII code
2 characters:
4 bytes)
Communications data
(ASCII code n characters) or error code
6-8-4 Host Link FINS
Command Frame
Frame before Conversion
Remote network address
(DNA)
Serial port allocated address or serial port unit address
FINS header
Remote node address
(DA1)
Unit No.
for Host
Link
+ 1
(1 to 32)
Remote unit address
(DA2)
Any except serial port unit address
FINS command
Etc. MRC SRC
Userspecified
Userspecified
Frame after Conversion
Host Link header
Host
Link header code
FA
Etc.
@ Unit No. for
Host Link
(0 to 31)
FINS header
Text
FINS command
FINS text
User-specified
FINS text
Error check code
FCS
Terminator
*+CR
240
Communications Frames
Response Frame
Frame before Conversion
@
Host Link header
Unit No. for
Host Link
(0 to 31)
Host
Link header code
FA
Etc.
Text
FINS header FINS command
End code
Section 6-8
FINS text
Error check code
FCS
Terminator
*+CR
Frame after Conversion
Remote network address
(DNA)
Serial port allocated address or serial port unit address
FINS header
Remote node address
(DA1)
Unit No.
for Host
Link
+ 1
(1 to 32)
Remote unit address
(DA2)
Etc.
Any except serial port unit address
FINS command
MRC SRC
Userspecified
Userspecified
End code FINS text
User-specified
6-8-5 Sending Commands Using the CMND(490) Instruction
Use the following method to send FINS commands to the Serial Communications Board/Unit from the PLC.
Setting CMND(490) Operands
S Operand
• Set the FINS command code (2803/2804/2805 hex) in S.
• Set the data without spaces (see note) following the FINS command code in S+1 onwards.
Note
Frames are set in the same order as in I/O memory from leftmost to rightmost byte (without blank bytes (00 hex)).
C Operand
C+2 bits 00 to 07 (Send destination network address)
• With routing tables that treat serial communications path as a network:
Network address corresponding to serial port in the routing tables.
• Without routing tables that treat serial communications path as a network:
• CompoWay/F, Modbus: Depends on the system configuration.
• Host Link FINS: Always set the unit address of the serial port.
C+3 bits 08 to 15 (Remote destination node address)
• CompoWay/F, Modbus
• With routing tables that treat serial communications path as a network:
00 hex (indicates local PLC communications)
• Without routing tables that treat serial communications path as a network: Node address for specifying the actual remote PLC
• Host Link FINS
• Host Link unit number incremented by one (1 to 32)
C+3 bits 00 to 07 (Send destination unit address)
• CompoWay/F, Modbus
Always set the unit address of the serial port
241
Communications Frames
Section 6-8
Note Use either of the following methods to specify the serial port using the CMND(490) instruction.
• Set 80/81 hex + 4
¥
unit number directly as the serial port unit address in the send destination unit address bits 00 to 07 of C+3. (With this method, set the serial port number (physical port) to 0 hex (not used) in bits 08 to 11 of C+2)
• Set the unit address of the Serial Communications Board/Unit itself
(Board: E1 hex; Unit: 10 hex + unit number) in the send destination unit address bits 00 to 07 of C+3, and set the serial port numbers (Port number 1: 1 hex; Port number 2: 2 hex) in the serial port number (physical port) bits 08 to 11 of C+2.
• Host Link FINS
Always set the unit address of the actual destination unit.
Sending Modbus-RTU Commands
• Set the FINS command code 2804 hex indicating the Modbus-RTU conversion in S.
• Set the slave address (1 byte) + FUNCTION code (1 byte) + communications data (n bytes) in order of leftmost byte to rightmost bytes (see note) from S+1 onwards.
Note
For Modbus-RTU, set the Modbus-RTU slave address (1 byte) in the leftmost byte of S+1, and the FUNCTION code (1 byte) in the rightmost byte of S+.
Example of Sending Modbus-RTU Command Using CMND(490) Instruction
This example is for writing a frequency reference value from an OMRON
3G3MV Inverter connected through RS-485 to the Serial Communications
Unit via two networks, Ethernet-to-Controller Link.
Example: The CMND(490) instruction is executed in the PLC for Ethernet.
The Modbus-RTU command for writing frequency reference value data is sent via Ethernet to the 3G3MV Inverter (Modbus-RTU slave address: 02) that is connected to port 1 (Unit address: 80 hex + 4 hex
×
unit number 3 = 8C hex) of the Serial Communications Unit (Unit number: 3), that is mounted to the
PLC on the Controller Link (Network address: 2; Node address: 5). The frequency reference value 10.0 Hz (set as 100 decimal in units of 0.1 Hz) is written.
The Modbus-RTU command is configured from the following elements.
Modbus-RTU slave address: 02
FUNCTION code: 10 hex (DATA WRITE)
Write start register No.: 0002 hex (frequency reference)
Write data: 0064 hex (100 decimal)
242
Communications Frames
Network (Ethernet)
CMND instruction
Section 6-8
FINS message
FINS header
2804
Modbus-RTU command
Conversion Link Unit
Node address: 5
FINS message
FINS header
2804
Modbus-RTU command
Network (Controller Link)
Network address: 2
Serial Communications Unit
Unit No. 3, port 1
CPU Unit
Protocol conversion
Example: Write data for frequency reference value
(FUNCTION code 10 hex, register No. 0002 hex)
Modbus-RTU command
Port 1 unit address:
80 hex + 4 hex
× unit number 3 = 8C hex
RS-485 (Modbus-RTU)
3G3MV OMRON Inverter
List of Settings
• FINS Network Settings
Item Value
(Example)
Setting location
Send destination network address
(Controller Link network address of PLC to which Serial Communications Unit is mounted)
2 Set 02 hex in the control data C+2 bits 00 to 07 (network address) of CMND(490).
Note: Set 0 hex in the control data C+2 bits 08 to 11
(serial port number) of CMND(490).
Set 05 hex in the control data C+3 bits 08 to 15 (send destination node address) of CMND(490).
Send destination node address
(node address in Controller Link for PLC to which Serial Communications Unit is mounted)
5
Serial Communications Unit unit number
3
Serial Communications Unit serial port Port 1
Send destination unit address
(unit address of serial port on Serial
Communications Unit)
80 hex + 4 hex
×
unit number 3 = 8C hex (or
10 + unit number 3 - 13 hex, and serial port number 1 = 1 hex)
Use to calculate the following unit address for the serial port
80 hex + 4 hex
×
unit number 3 = 8C hex
Set 8C hex in the control data C+3 bits 00 to 07 (send destination unit address) of CMND(490).
(Alternatively, set 13 hex in the control data C+3 bits
00 to 07 (send destination unit address) and set 1 hex in C+2 bits 08 to 11 (serial port number).)
• Modbus-RTU Settings
Command Frame
Item
FINS command code: Converting to Modbus-RTU = 2804 hex
Modbus slave address (e.g., 02 hex)
FUNCTION code: DATA WRITE =
10 hex
Write data register No. (e.g., frequency reference = 0002 hex)
Set value
2804 hex
02 hex
10 hex
0002 hex
Setting location
Set 2804 hex in controller data s of the
CMND(490) instruction.
Set 0210 hex in controller data s+1 of the CMND(490) instruction.
Set 0002 hex in controller data s+2 of
CMND(490).
243
Communications Frames
Section 6-8
Item
Number of write data registers
(e.g, 1 register)
Number of attached data registers
Note: Set 02 hex of this value in the leftmost byte of S+4. Set 00 hex as the leftmost register No. in the rightmost byte of S+4.
Register No. 0002 hex data (e.g.,
0064 hex)
Note: Set 64 hex as the rightmost register No. in the leftmost byte of
S+5.
Set value
0001 hex
0200 hex
6400 hex
Setting location
Set 0001 hex in controller data s+3 of
CMND(490).
Set 0200 hex in controller data s+4 of
CMND(490).
Set 6400 hex in controller data s+5 of
CMND(490).
Response Frame
Item
Modbus Slave address (e.g., 02 hex)
FUNCTION code: Write data (= 10 hex)
Write data register No. (e.g., frequency reference = 0002 hex)
Write data registers (e.g., 1 register)
Setting
02 hex
10 hex
0002 hex
0001 hex
Setting location
Stored in D+2 of CMND(490)
Stored in D+3 of CMND(490)
Stored in D+4 of CMND(490)
[CMND S D C]
Command Details
Operand Offset
S:
D01000
+0:
+1:
+2:
+3:
+4:
+5:
D:
D02000
C:
D00000
+0:
+1:
+2:
+3:
+4:
+5:
Value Meaning
2804 hex Conversion to Modbus-RTU (FINS command code: 2804 hex)
0210 hex Modbus-RTU slave address: 02 hex, FUNCTION code: 10 hex (DATA WRITE)
0002 hex Write data register No.: 0002 hex (frequency reference)
0001 hex Number of write data registers: 0001 hex (1 register)
0200 hex Number of attached data bytes: 02 hex (2 bytes); Leftmost register No.: 00 hex
6400 hex Rightmost register No.: 64 hex (Frequency reference value: 10.0 Hz when unit is 0.1
Hz), blank = 00 hex
First response storage word
00 0C hex Number of command data bytes: 000C hex (12 bytes decimal)
00 0A hex Number of response data bytes: 000A hex (10 bytes decimal)
0002 hex Send destination network address: 02 hex; Serial port number: 0 hex (direct serial port unit address specification)
058C hex Send destination node address: 05 hex; Send destination unit address: 8C hex
0000 hex Response required; Communications port number: 0; Resends: 0 hex
0000 hex Response monitoring time: 2 s
Response
Operand Offset
D:
D02000
+0:
+1:
+2:
+3:
+4:
Value Meaning
2804 hex Conversion to Modbus-RTU (FINS command code: 2804 hex)
0000 hex FINS end code: 0000 hex (normal)
0210 hex Modbus-RTU slave address: 02 hex, FUNCTION code: 10 hex (DATA WRITE)
0002 hex Write data register No.: 0002 hex (frequency reference)
0001 hex Number of write data registers: 0001 hex (1 register)
244
Communications Frames
Section 6-8
Sending Host Link FINS Commands
• Set any FINS command code in S.
• Be sure to set the Host Link unit number (0 to 31) incremented by one (1 to 32) for the PLC slave corresponding to the send destination node address in C+3 bits 08 to 15.
Example of Sending Host Link FINS Commands Using CMND(490)
The following example is for sending FINS commands to a CS/CJ-series PLC connected to the Serial Communications Unit through an RS-422A/485 communications path via an Ethernet network.
Example: The CMND(490) instruction is executed in the PLC on the Ethernet.
The FINS command (e.g., OPERATING MODE CHANGE STOP: 0402 hex) is sent to the CS/CJ-series PLC (Host Link unit number = 1) that is connected to port 2 (unit address = 81 hex + 4 hex
¥ unit number 6 = 99 hex = 153 decimal, corresponding to network address 5 in the routing tables) of the Serial Communications Unit (unit number 6) that is connected to the PLC on the Ethernet. Routing is performed between the networks, so use the setting for routing tables.
CMND instruction
Ethernet unit node address: 4
Network (Ethernet)
FINS message
FINS command
Serial Communications Unit
Unit No. 6, port 2
CPU Unit
Protocol conversion
Local network table
E.g., Operation mode change
(operation stopped): 0402 hex
Unit No.
Serial port unit address: 153
Network address
Serial port network address: 5
Host Link header
Port 2 unit address:
81 hex + 4 hex
× unit
No. 6 = 99 hex
(153 decimal), which corresponds to network address 5.
Unit No. for Host Link = 0
FINS command
Terminator
Unit No. for Host Link = 1
RS-422A/485 (Host Link)
CS/CJ-series or
CVM1/CV-series PLC
(Host Link slave)
Unit No. for Host Link = 2
Settings
• FINS Network Settings
Item
Send destination network address
(network address allocated to target serial port in routing tables)
Send destination node address
(unit number for Host Link of
PLC connected to target serial port + 1)
Send destination unit address
(unit address of remote unit on PLC connected to target serial port)
Value (example)
Network address for serial communications path allocated in local network table settings is 5
Remote PLC unit number for Host
Link: 1
Therefore, set 1+1
= 2
CPU Unit: 00 hex
Setting location
• Set 05 hex in bits 00 to 07 (network address) of control data
C+2 in the CMND(490) instruction.
Note Set 0 hex in bits 08 to 11
(serial port number) of control data C+2 in the
CMND(490) instruction
• Set 02 hex in bits 08 to 15
(send destination node address) of control data C+3 in the CMND(490) instruction.
• Set 00 hex in bits 00 to 07 of control data C+3 in the
CMND(490) instruction.
245
Communications Frames
Section 6-8
Item
Serial Communications Unit unit number
6
Value (example)
Serial Communications Unit serial port
Port 2
Setting location
Use the following equation to calculate the unit address of the serial port.
81 hex + 4 hex
×
unit number 6
= 99 hex (153 decimal)
Use CX-Net to set the local network tables in the routing tables.
Unit number
Serial Communications Unit’s serial port unit address: 153
(decimal)
Network address
Serial port network address: 5
(decimal)
• Host Link FINS Settings
Command Frame
Item
FINS command code (e.g., change operating mode (stop operation))
FINS command parameter (e.g., always FFFF hex to change operating mode)
Setting
0402 hex
Setting location
Set in 0402 hex of control data S for CMND(490) instruction
FFFF hex Set in FFFF hex of control data s+1 for CMND(490) instruction
Response Frame
Item
FINS command code (E.g., change operating mode (stop operation))
FINS command end code (normal end:
0000 hex)
Setting
0402 hex
0000 hex
Setting location
Stored in D of CMND(490) instruction
Stored in D+1 of CMND(490) instruction
[CMND S D C]
Command Details
Operand Offset
S:
D01000
+0:
+1:
D:
D02000
C:
D00000
+0:
+1:
+2:
+3:
+4:
+5:
Value Meaning
0402 hex Change operating mode (stop operation) (FINS command code: 0402 hex)
FFFF hex Change operating mode (stop operation): Always FFFF hex
First response storage word
000C hex
000A hex
Command data bytes: 0004 hex (4 bytes decimal)
Response data bytes: 0004 hex (4 bytes decimal)
0005 hex Send destination network address: 05 hex; Serial port number: 0 hex (not used)
0200 hex Send destination node address: 02 hex (set the unit number for Host Link + 1); Send destination unit address: 00 hex
0000 hex Response required; Communications port number: 0; Resends: 0 hex
0000 hex Response monitoring time: 2 s
Response
Operand Offset
D:
D02000
+0:
+1:
Value Meaning
0402 hex Change operating mode (stop operation) (FINS command code: 0402 hex)
FFFF hex FINS end code: FFFF hex (normal end)
Note
1.
The method used to set the remote destination network address, node address, and unit address for sending data to or receiving data from the PLC
246
Communications Frames
Section 6-8
connected serially via Host Link to another PLC on the network (to which the Serial Communications Board/Unit is mounted) using the SEND(090)/
RECV(098) instructions is the same as for the CMND(490) instruction.
2.
When creating Host Link FINS command frames using the CMND(490) instruction, always set the unit number for Host Link incremented by one (1 to 32) for the remote destination (send destination) node address (word
C+3, bits 08 to 15 of the CMND(490) instruction). Do not set the unit number of the actual Host Link slave (0 to 31). Using the Host Link unit number without incrementing by one will access the PLC with the entered Host Link unit number less one.
For example, specify remote PLC with Host Link unit number 2 by entering
3 for the remote destination node address. If the 2 is entered, the PLC with
Host Link unit number 1 will be accessed.
To access a PLC on a Host Link FINS network using the Serial Gateway from CX-Programmer, however, enter the actual Host Link unit number, without incrementing by one. (Select Change PLC, click the Display Seri-
al Gateway Guide Button, and set unit number in the Host Link SYSWAY
Settings field of the Serial Gateway Guide dialog box.
Sending Modbus-ASCII Commands
• Set the FINS command code of 2805 hex in S, indicating conversion to
Modbus-RTU.
• In S+1 onwards, set the slave address (2 bytes ASCII) + FUNCTION code
(2 bytes ASCII) + communications data (2
×
n bytes ASCII) from leftmost bytes to rightmost bytes using ASCII.
Sending CompoWay/F Commands
• Set the FINS command code of 2803 hex in S, indicating conversion to
CompoWay/F.
• In S+1 onwards, set the CompoWay/F node number (2 bytes ASCII) + sub-address (2 bytes ASCII) + SID (1 byte ASCII) + CompoWay/F command MRC (2 bytes ASCII) + CompoWay/F command SRC (2 bytes
ASCII) + text (2
×
n bytes ASCII) from leftmost bytes to rightmost bytes using ASCII.
Note
Set the contents of S+3 when using CompoWay/F commands as follows:
Set the SID “0” as ASCII 30 hex (1 byte) in the leftmost byte, and the leftmost digit of the CompoWay/F command code MRC as ASCII (1 byte) in the rightmost byte. Next, set the bits of S+4 as follows:
Set the rightmost digits of the CompoWay/F command code MRC as ASCII in the leftmost byte, and the leftmost digit of the CompoWay/F command code
SRC as ASCII (1 byte) in the rightmost byte. Be sure to set one byte each for the subsequent data without any blank bytes.
247
Communications Frames
Section 6-8
248
SECTION 7
No-protocol Mode
This section describes the procedure and other information required to use the no-protocol mode. This mode is supported for Unit Ver. 1.2 or later only.
7-2 Allocation DM Area for No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . .
7-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-4 Basic Operating Procedure in No-protocol Mode. . . . . . . . . . . . . . . . . . . . . .
7-4-1 Procedure Using No-protocol Mode. . . . . . . . . . . . . . . . . . . . . . . . .
7-4-2 Connections (No-protocol Mode). . . . . . . . . . . . . . . . . . . . . . . . . . .
249
Overview
Section 7-1
7-1 Overview
7-1-1 Definition
No-protocol mode is a function used to send and receive data using communications port I/O instructions (TXD(236)/RXD(235) or TXDU(256)/RXDU(255)) without conversion or protocol. Therefore, in no-protocol mode communications procedures such as retry processing, data format conversion processing, and processing branching according to the receive data are not performed.
Note
No-protocol mode is supported only when using a Serial Communications
Board/Unit with Unit Ver. 1.2 or later in combination with a CS/CJ-series CPU
Unit with Unit Ver. 3.0 or later. Therefore, be sure to use a CS/CJ-series CPU
Unit with Unit Ver. 3.0 or later if the no-protocol mode is required.
The no-protocol mode enables single-directional data exchange with a general-purpose external device with an RS-232C port or RS-422A/485 port using the TXD(236)/RXD(235) or TXDU(256)/RXDU(255) instructions. For example, data can be sent to and received easily (with no protocol) such as data input from a bar code reader or data output to a printer.
Note
Use the TXD(236)/RXD(235) instructions for Serial Communications Boards and the TXDU(256)/RXDU(255) instructions for Serial Communications Units.
Serial Communications Board (unit Ver. 1.2 or later)
CPU Unit (unit Ver. 3.0 or later)
TXDU/RXDU
Serial Communications Unit (unit Ver. 1.2 or later)
CPU Unit (unit Ver. 3.0 or later)
TXDU/RXDU
RS-232C or RS-422A/485
General-purpose external device with serial port
(e.g, bar code reader or printer)
General-purpose external device with serial port
(e.g, bar code reader or printer)
RS-232C or RS-422A/485
Addition of a start code at the beginning of the data, and end code at the end of the data (or specifying the number of receive data bytes) is possible before sending/receiving. The RS and CS control signals can also be controlled.
Note No-protocol mode is only supported for RS-422A/485 if the four-wire method is used.
250
Overview
Section 7-1
7-1-2 Specifications
Item
Communications mode
Messages (communications frame structure)
Full-duplex
Description
Set either of the following types in the Setup Area in the allocation DM Area.
1. Data only (without start code and end code)
2. Start code + data
3. Data + end code
4. Start code + data + end code
5. Data + CR + LF
6. Start code + data +CR + LF
Set in allocated DM Area
(The start code can be included by setting to between 00 and
FF hex, and the end code can be included by setting to between 00 and FF hex. To exclude the end code, set the number of receive data bytes.)
Start code
End code
None, or 00 to FF hex
None, 00 to FF hex, or CR + LF
Number of receive data bytes during reception
Set the number of receive data bytes between
1 and 256 bytes (according to the DM Area settings) when frame structure 1 or 2 above is used.
Sending messages • Serial Communications Board: TXD(236) instruction
• Serial Communications Unit: TXDU(256) instruction
Receiving messages • Serial Communications Board: RXD(235) instruction
• Serial Communications Unit: RXDU(255) instruction
Maximum message length
Sending and receiving: Up to 259 bytes including the start code and end code (up to 256 bytes excluding start/end codes)
Data conversion
Communications protocol
No conversion
None
Message delay time When the TXD(236) or TXDU(256) instruction is executed, after the send delay time, the data is sent from the port.
0 to 300 s (0 to 300,000 ms)
(Can be set in 10-ms units, depending on the DM Area settings)
Receive counter The number of data bytes (0 to 256) received at the port can be counted.
Reception buffer clear timing
The reception buffer is cleared immediately after executing the
RXD(235)/RXDU(255) instruction
Send/Receive Message Frames for No-protocol Communications
Start
Code
No
End code
Yes
No
Data
256 bytes max.
Data
256 bytes max.
CR+LF
Data
256 bytes max.
Yes
Data
256 bytes max.
Data
256 bytes max.
Data
256 bytes max.
Note
1.
For multiple start codes, the first start code is enabled.
2.
For multiple end codes, the first end code is enabled.
251
Allocation DM Area for No-protocol Mode
Section 7-2
3.
If the end code will overlap with the send/receive data and cause data reception to be interrupted, use CR+LF as the end code.
4.
If the send delay is set in the allocation DM Area when sending TXD(236) or TXDU(256) (no-protocol mode), data will be sent when the send delay time has lapsed after execution of TXD(236) or TXDU(256), as shown below.
Send delay
Send
Time
TXD(236)
For details on the TXD(236), RXD(235), TXDU(256), and RXDU(255) instructions, refer to the CS/CJ-series Instructions Reference Manual (W340).
5.
If a no-protocol instruction is sent to a pre-Ver. 1.2 Board/Unit or the serial port of a Board/Unit with Unit Ver. 1.2 or later using a serial communications mode other than no-protocol mode, the following operations will occur.
• If TXD(236)/RXD(235) is sent to the Board, Auxiliary Area bit A424204
(Inner Board Service Failure Flag) will turn ON.
• If TXDU(256)/RXDU(255) is sent to the Unit and the serial communications mode is set to protocol macro, NT Link, loopback test, or Serial
Gateway mode, an undefined command error (end code: 0401 hex) will be returned.
If the serial communications mode is set to Host Link mode and the instruction will be converted to a slave-initiated function FINS command and transferred. (Depending on the remote device, a response timeout
(end code: 0205 hex) is likely to be returned.)
Note
Do not program TXD(236)/RXD(235) instructions addressed to the serial port
(port 1/2) of the Serial Communication Board in both cyclic tasks and interrupt tasks. If an interrupt task occurs during execution of a TXD(236)/RXD(235) instruction addressed to the serial port (port 1/2) of the Serial Communications Board within a cyclic task, the TXD(236)/RXD(235) instruction addressed to the serial port (port 1/2) of the Serial Communications Board within the interrupt task will not be executed. An error will occur and the ER
Flag will turn ON. (This operation is also not possible in both cyclic tasks and interrupt tasks for any combination of the TXD(236)/RXD(235) instruction and ports 1/2.)
7-2 Allocation DM Area for No-protocol Mode
This section describes the Setup Area allocated to the Serial Communications
Board and Serial Communications Units in the DM Area when no-protocol communications are used.
Setup Area Words
The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when no-protocol communications are used. The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to the unit numbers).
252
Allocation DM Area for No-protocol Mode
Section 7-2
Serial Communications Boards (CS Series only)
Setup Area Allocated in the DM Area: D32000 to D32099
Words Usage
D32000 to D32005 Port 1 Settings
D32010 to D32015 Port 2 Settings
D32006 to D32009
D32016 to D32019
Not used in no-protocol mode
D32020 to D32767 Reserved for the system
Serial Communications Units (CS/CJ Series)
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area: m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
Words
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599 m to m+5: Port 1 Settings m+10 to m+15: Port 2 Settings m+6 to m+9, m+16 to m+19: Not used.
m+20 to m+99: Not used.
Setup Area Contents
m = D30000 + 100
× Unit No
Setting contents
Board
(CS Series only)
Port 1
Words
Port 2 Port 1
Unit
(CS/CJ Series)
Port 2
D32000 D32010 m m+10
Bit
03
02
01
00
15 Port settings
12 to 14 Reserved
0: Defaults; 1: User settings
08 to 11 Serial communications mode
3: No-protocol
05 to 07 Reserved
04 Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
Data length
Stop bits
Parity
0: 7 bits; 1: 8 bits
0: 2 bits; 1: 1 bit
0: Yes; 1: No
Parity 0: Even; 1: Odd
253
Auxiliary Area and CIO Area Allocations
Section 7-3
Words
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1
D32001 D32011 m+1
Port 2
m+11
D32002
D32003
D32004
D32005
D32012
D32013
D32014
D32015 m+2 m+3 m+4 m+5 m+12 m+13 m+14 m+15
Bit Setting contents
04 to 15 Reserved
00 to 03 Baud rate (bps)
0: Default (9,600); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600; 7: 19,200;
8: 38,400; 9: 57,600
15 Send delay time 0: Default (0 ms); 1: Setting in bits 00 to 14
00 to 14 Send delay setting range: 0 to 300 s (0 to 300,000 ms): 0000 to
7530 hex (0 to 30,000 decimal) (Unit: 10 ms)
15 CTS control
08 to 15 Start code: 00 to FF hex
00 to 07 End code: 00 to FF hex
12 Start code 0: No; 1: Yes
08 to 09 End code
00: No (Specify number of receive data bytes)
01: Yes
11: CR + LF specification
00 to 07 Number of receive data bytes
01 to FF hex: 1 to 255 bytes
00 hex (default): 256 bytes
7-3 Auxiliary Area and CIO Area Allocations
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and the Status
Area and Software Switches allocated in the CIO Area used for no-protocol communications.
Auxiliary Area Allocations
Port 1 and Port 2 Port Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the serial port.
When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
Note
These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
Serial Communications Boards (CS Series only)
A636
Word Bit
03 to 15
02
01
00
Contents
Reserved
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved
254
Auxiliary Area and CIO Area Allocations
Section 7-3
Serial Communications Units (CS/CJ Series)
n
Words
n = A620 + unit number
Contents
Reserved
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved
Inner Board Error Information (CS-series Serial Communications Board Only)
A424 contains error information for the Serial Communications Board
Word
A424
08
07
06
05
04
03
02
01
00
Bit
12 to 15
11
10
09
Type
Non-fatal errors (Note
1)
Fatal errors
(Note 2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3,
4, or 5 is stored in the error code for bits
00 to 03 of CIO 1909 or CIO 1919 in the
CIO Area,
1: Protocol data error (SUM error); 0:
Normal
1: System setting error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
1: Inner Board service failure
(TXD(236)/RXD(235) sent to a pre-Ver.
1.2 Board that does not support no-protocol mode); Normal
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board WDT error; 0: Normal
Note
Bit
03 to 15
02
01
00
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to Section 11 Troubleshooting and Maintenance.
CIO Area Allocations
Words in the CIO Area are allocated as Software Switches, which are manipulated from the CPU Unit to control the operation of the Serial Communications Board or Unit, and for a Status Area, which contains status and error information for the Serial Communications Board or Unit.
Serial Communications Boards (CS Series Only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for the Software Switches and Status Area. CIO 1900 contains software switches, and the 24 words from CIO 1901 to CIO 1924 are used for the Status Area.In Noprotocol mode, only these words are used as the CIO Area. No other words are used.
CIO 1900
CIO 1901 to CIO 1904
Software switch
Board status
255
Auxiliary Area and CIO Area Allocations
Section 7-3
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Port 1 status
Port 2 status
Reserved for the system
Serial Communications Units (CS/CJ Series)
Words are allocated in the CIO Area for Software Switches and Status Area.
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. In no-protocol mode, the first word is used for Software Switches, and the remaining 24 words are used for the Status Area.
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
Unit No. 7
Unit No. 8
CIO 1675 to CIO 1699
CIO 1700 to CIO 1724
Unit No. 9 CIO 1725 to CIO 1749
Unit No. A CIO 1750 to CIO 1774
Unit No. B CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E CIO 1850 to CIO 1874
Unit No. F CIO 1875 to CIO 1899 n: Software switches (ports 1 and 2) n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
Status Area
The Status Area is used to read the Serial Communications Board’s or Unit’s setting status, communications status, transmission control signal status, and transmission error status.
Direction: Board/Unit to CPU Unit (input) n = CIO 1500 + 25
× unit number
Contents
Board
(CS Series only)
Words
Unit
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
1901 n+1
1902
1903
1904 n+2 n+3 n+4
Bit
02 to 15 Reserved
01 1: Error log data error
00 Not used
00 to 15 Reserved
00 to 15 Reserved
00 to 15 Reserved
0: Error log data normal
256
Auxiliary Area and CIO Area Allocations
Section 7-3
Port 1 Port 2 Port 1 Port 2
1906
1907
1916
1917
Words
Board
(CS Series only)
(CS/CJ Series)
1905 1915 n+5 n+6 n+7
Unit
n+15 n+16
12 to 15
08 to 11
05 to 07
04
03
02
01
00
15
14
13
Bit
Port setting status
Port setting status
Hardware settings
System settings
Contents
Serial communications mode: Always 3 hex
(See note.)
Baud rate (See note.)
Reserved
Start bits: Always 0
Data length (See note.)
Stop bits (See note.)
0
0
No 0
1
Parity: Yes/No (See note.)
Parity: Even/Odd (See note.)
RS-
232C
1
0
RS-
422A/
485
0: Terminating resistance OFF
1: Terminating resistance ON
02 to 12
01
Reserved
1: System Setup error; 0: System Setup normal
00 1: Port operating n+17 11 to 15 Com-
10 munications status
Reserved
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive
1
1
Reser ved
1908 1918 n+8
09
08
07
06
05
04
03
00 to 02
Transmission control signal status
Reserved
1: Local Unit busy receiving (Flow control)
0: Local Unit ready to receive
DTR (ER) signal
DSR (DR) signal
Reserved
CTS (CS) signal
RTS RS) signal
Reserved n+18 15 1: Transfer error; 0: Normal
05 to 14 Not used
04
03
02
00, 01
Transmission error status
1: Overrun error; 0: Normal
1: Framing error; 0: Normal
1: Parity error; 0: Normal
Reserved
Note
The port settings in the Setup Area allocated in the DM Area are stored. If the
Board/Unit is operating on default settings due to a System Setup error the default settings will be stored.
257
Auxiliary Area and CIO Area Allocations
Section 7-3
Sending Data (TXD(236)/TXDU(256))
n = CIO 1500 + 25
× unit number
Bit
Board
(CS Series only)
TXD(236)
Port 1
A35605
Port 2
A35613
Words
---
Unit
(CS/CJ Series)
TXDU(256)
Port 1 Port 2
---
---
---
---
---
---
---
---
---
Word n+9, bit 05
Word n+19, bit 05
A20200 to A20207
A203 to A210
A21900 to A21907
Send Ready Flag
1: Send enabled; 0: Send disabled (includes sending in progress)
This flag turns OFF when TXD(236) is executing at CPU Unit.
The flag turns ON when data transmission from Board to external device is completed.
TXDU(256) Executing Flag
1: Executing; 0: Not executing
Communications Port Enabled Flags
Turns ON (1) if execution of the network communications instructions (SEND(090), RECV(098), CMND(490),
PMCR(260)) including TXDU(256) and RXDU(255), is possible for the communications port.
Communications Port Completed Codes
Stores the response code when network communications instructions (SEND(090), RECV(098), CMND(490),
PMCR(260)) including TXDU(256) and RXDU(255) are executed.
Communications Port Error Flags
Turns ON (1) if an error occurs during execution of the network communications instructions (SEND(090), RECV(098),
CMND(490), PMCR(260)) including TXDU(256) and
RXDU(255).
258
Auxiliary Area and CIO Area Allocations
Section 7-3
Receiving Data (RXD(235)/RXDU(255))
n = CIO 1500 + 25
× unit number
Bit
Board
(CS Series only)
RXD(235)
Port 1
A35606
Port 2
A35614
Words
Unit
(CS/CJ Series)
RXDU(255)
Port 1
Word n+9, bit 06
Port 2
Word n+19, bit 06
A35607
A35700 to
A35715
A42404
---
---
---
CIO 190804
A35615
A35800 to
A35815
---
---
---
CIO 191804
Word n+9, bit 07
Word n+10, bits 00 to 15
---
Word n+20, bits 00 to 15
A20200 to A20207
A203 to A210
Word n+8, bit 04
Word n+19, bit 07
---
A21900 to A21907
Word n+18, bit 04
Reception Completed Flag
1: Reception completed; 0: No reception or reception in progress
This flag turns ON when the specified number of bytes are received at the Board/Unit.
The flag turns OFF immediately after the CPU Unit has completed writing to I/O memory the data received using the
RXD(235) or RXDU(255) instruction.
Reception Overflow Flag
1: The specified number of bytes or higher has been received at the Board/Unit (data continued to be received after the
Reception Completed Flag turned ON).
0: The number of bytes received at the Board/Unit has not exceeded the specified number (data did reception did not continue after the Reception Completed Flag turned ON).
This flag turns ON if the Board/Unit continues to receive data after completing data reception.
The flag turns OFF immediately after the CPU Unit has completed writing to I/O memory the data received using the
RXD(235) or RXDU(255) instruction.
Reception Counter (specified number of receive data bytes)
Counts in hexadecimal the number of data bytes received from 0 to 256 bytes (0000 to 0100 hex)
Inner Board Service Failure Flag (non-fatal error)
This flag turns ON when TXD(236)/RXD(235) is sent to a pre-
Ver. 1.2 Serial Communications Board that does not support no-protocol mode.
Communications Port Enabled Flags
Turns ON (1) if execution of the network communications instructions (SEND(090), RECV(098), CMND(490),
PMCR(260)) including TXDU(256) and RXDU(255), is possible for the communications port.
Communications Port Completed Codes
Stores the response code when network communications instructions (SEND(090), RECV(098), CMND(490),
PMCR(260)) including TXDU(256) and RXDU(255) are executed.
Communications Port Error Flags
Turns ON (1) if an error occurs during execution of the network communications instructions (SEND(090), RECV(098),
CMND(490), PMCR(260)) including TXDU(256) and
RXDU(255).
Overrun Error Flag
1: 260 bytes or higher received in the reception buffer before execution of RXD(235)/RXDU(255) during no-protocol mode)
0: Normal (Data received in reception buffer is less than 260 bytes)
Note: If an overrun error occurs, the Overrun Error Flag can be turned OFF by cycling the power or restarting the Board.
259
Basic Operating Procedure in No-protocol Mode
Section 7-4
Note
Reception Buffer Timing in No-protocol Mode:
If the RXD(235) instruction is sent to the CPU Unit’s built-in serial port, the reception buffer is not cleared after RXD(235) execution. Therefore, multiple
RXD(235) instructions can be received over several steps. If the RXD(235)/
RXDU(255) instruction is sent to the serial port of a Serial Communications
Board/Unit, the reception buffer is cleared after RXD(235)/RXDU(255) execution. Therefore, multiple RXD(235)/RXDU(255) instructions cannot be received over several steps.
7-4 Basic Operating Procedure in No-protocol Mode
7-4-1 Procedure Using No-protocol Mode
Allocation DM Area Settings for Serial Communications Unit/Board
Use a Programming Device or Support Software (Programming Console, CX-
Programmer, CX-Protocol) to set the allocation DM Area settings.
Instruction Execution
Executing in Ladder Program
• Execute the TXD(236) or TXDU(256) instruction when sending data to an external device from the PLC.
Note (a) When using the TXD(236) instruction to send to a Serial Communications Board, include a NO condition of the Send Ready Flag
(bit A35605/A35613) in an AND in the input condition.
(b) When sending the TXDU(256) instruction to a Serial Communications Unit, include a NO condition of the Communications Port
Enabled Flags (bits A20200 to A20207) and a NC condition of the
TXDU(256) Executing Flag (word n+9/n+19, bit 05) in an AND in the input condition.
• Execute the RXD(235) or RXDU(255) instruction when receiving data at the PLC from an external device.
Note (a) When sending the RXD(235) instruction to the Board or the
RXDU(255) instruction to the Unit, include a NO condition for the
Reception Completed Flag (bit A35606/A35614 for the Board or word n+9/n+19, bit 06 for the Unit) in an AND in the input condition.
(b) When sending the RXDU(255) instruction to the Unit, also include a NO condition for the Communications Enabled Flag (bits
A20200 to A20207) in an AND in the input condition.
For details on the TXD(236), RXD(235), TXDU(256), and RXDU(255) instructions, refer to the CS/CJ-series Instructions Reference Manual (W340).
7-4-2 Connections (No-protocol Mode)
The following connection example shows only a basic connection diagram.
We recommend that appropriate noise countermeasures be taken when performing actual wiring, including the use of shielded twisted-pair cables. Refer
to 3-4 RS-232C and RS-422A/485 Wiring for actual wiring methods.
260
Basic Operating Procedure in No-protocol Mode
Bar Code Reader Connected with RS-232C
Serial Communications Unit/Board
9-pin D-sub (female)
V509-W012
Signal
Pin No.
Extension Cable
FG
1
SD
2
RD
3
RS
4
CS
5
DR
7
ER
8
SG
9
SG
+5 V
Serial Communications Unit/Board
V509-W012 Extension Cable
V520-RH21-6
Bar Code Reader
DIN 8p
Pin No.
1
2
3
4
6
7
8
Signal
SD
RD
RS
CS
ER
SG
+5 V
100 VAC
V520-RH21-6
Bar Code Reader
82S-0305 +5 V
External Power Supply
Section 7-4
261
Basic Operating Procedure in No-protocol Mode
Section 7-4
262
SECTION 8
Using 1:N NT Links
This section describes the procedure and other information required to use 1:N NT Links to Programmable Terminals.
8-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-2-2 Setup Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3 Auxiliary Area and CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-1 Auxiliary Area Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8-3-3 Status Area Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
263
Overview of 1:N NT Links
Section 8-1
8-1 Overview of 1:N NT Links
A PLC can be connected to Programmable Terminals (PTs) using an RS-
232C or RS-422A/485 port. The I/O memory of the PLC is allocated as a Status Control Area and a Status Notification Area for the PT, as well as to objects, such as touch switches, lamps, and memory tables. This enables the status of the I/O memory in the PLC to be controlled and monitored by operations from the PT, without the use of ladder programming in the PLC. One
PLC can be connected to up to eight PTs.
The user does not need to be aware of the 1:N NT Links commands. All that is necessary is to allocate PLC memory for the PTs.
This section explains the Setup Area and the Protocol Status Flags when a
Serial Communications Board or Unit is used with 1:N NT Links. For details on the operating PTs, refer to the operation manual for the PT.
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
NT Link
(Set to 1:N)
1:N NT Link
Note
PT PT
1.
Set the serial port on the PT to a 1:N NT Link. The Serial Communications
Board or Unit will not be able to communicate if the PT port is set for a 1:1
NT Link. Connection is not possible to PTs that do not support 1:N NT
Links.
2.
The number of PTs that can be connected to one port is limited by the CPU
Unit’s cycle time when a Serial Communications Board or Unit is used in a
1:N NT Link, as shown in the following diagrams. Although some communications will be possible even if these restrictions are exceeded, communications errors will occur depending on the PT operating conditions and communications load. Always abide by these restrictions.
3.
The Programming Console functions of the PT (Expansion Mode) cannot be used when connected to Serial Communications Board or Unit ports.
They can be used only by connecting to the peripheral port or RS-232C port on the CPU Unit.
4.
Set a unique unit number for each PT connected to the same PLC. If the same unit number is set for more than one PT, malfunctions will occur.
264
Overview of 1:N NT Links
Section 8-1
5.
NT Link serial communications are unique and are not compatible with other serial communications modes.
Example for NT31/NT631(C) PTs
Priority
Registered
PTs per port
CPU Unit's cycle time (ms)
Priority Not
Registered
PTs per port
CPU Unit's cycle time (ms)
6.
The NT20S, NT600S, NT30, NT30C, NT620, NT620C, and NT625C cannot be used if the cycle time of the CPU Unit is 800 ms or longer (even if only one of these PTs is used in a 1:N NT Link).
7.
With some PTs, timeout settings can be changed to eliminate some of the communications errors. Refer to the operation manual for the PT for details.
8.
If more PTs are required by the system than allowed by the above restrictions, connect the PTs in smaller groups to different ports and increase the number ports by adding Serial Communications Units or a Serial Communications Board (if one is not already being used).
265
Setup Area Allocations
Section 8-2
8-2 Setup Area Allocations
This section explains the Setup Area (Allocation DM Area) when a Serial
Communications Board or a Serial Communications Unit is used in 1:N NT
Link mode.
8-2-1 Setup Area Words
The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when 1:N NT Links are used.
The words allocated to the Serial Communications Board are different from those allocated to the Serial Communications Units (which are allocated words according to the unit numbers).
Serial Communications
Boards (CS Series Only)
Setup Area Allocated in the DM Area: D32000 to D32767
D32000, D32006
D32010, D32016
Words
D32001 to D32005
D32007 to D32009
D32011 to D32015
D32017 to D32019
D32020 to D32767
Usage
Port 1 Settings
Port 2 Settings
Not used with1:N NT Links
Reserved for the system
Serial Communications
Units (CS/CJ Series)
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area: m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
Unit No. B
Unit No. C
Unit No. D
Unit No. E
Unit No. F
DM Area
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
D30500 to D30599
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
D31000 to D31099
D31100 to D31199
D31200 to D31299
D31300 to D31399
D31400 to D31499
D31500 to D31599 m to m + 1, m + 6: Port 1 Settings m + 10 to m + 11, m + 16: Port 2 Settings m + 2 to m + 5, m + 7 to m + 9, m + 12 to m + 15, m + 17 to m + 19: Not used with 1:N NT Links m+20 to m+99: Not used
266
Auxiliary Area and CIO Area Allocations
Section 8-3
8-2-2 Setup Area Contents
m = D30000 + 100
× unit number
DM Area
Boards
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2
D32000 D32010 m
Port 1 Port 2
m + 10 15
Bit Setting contents
Port settings Setting not required.
12 to 14 Reserved
08 to 11 Serial communications mode: Always 2 Hex (1:N
NT Link)
D32001
D32006
D32011
D32016 m + 1 m + 6
05 to 07 Reserved
04
Start bits
03
Data length
02
Stop bits
01
Parity
Setting not required.
Setting not required.
Setting not required.
Setting not required.
00
Parity Setting not required.
m + 11 04 to 15 Reserved
00 to 03 Baud rate (bps)
0 to 9 Hex: Standard NT Link
A Hex: High-speed NT Link (See note.) m + 16 03 to 15 Reserved
00 to 02 1:N NT Link Maximum unit number: 0 to
7 hex
Note With CS-series, a high-speed NT Link is available only with Serial Communications Boards or Serial Communications Units manufactured on or after
December 20th, 1999. With earlier models, only standard NT Link is available.
Lot No: 20Z9 Manufactured on December 20th, 1999
The year is indicated with the last digit. In this case, "9" indicates "1999."
Month of manufacture. October, November, and December are indicated with X, Y, and Z respectively. In this case, the month is "December."
Day of manufacture. In this example, the day is "20."
NT31/631(C)-V2 are the only PTs for which high-speed NT link is supported.
Except for the baud rate, the 1:N NT Link communications specifications are fixed. Therefore, the port settings, start bits, stop bits, and parity need not be set. Even if they are set, they are ignored.
Set the serial communications mode to 2 Hex to use 1:N NT Link mode.
Serial Communications
Mode
Maximum 1:N NT Links
Unit No.
With 1:N NT Links, up to eight Programmable Terminals (PTs) can be connected. The highest connected unit number is set here.
8-3 Auxiliary Area and CIO Area Allocations
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and the Status
Area allocated in the CIO Area. The Software Switches allocated in the CIO
Area are not used for 1:N NT Links.
267
Auxiliary Area and CIO Area Allocations
Section 8-3
8-3-1 Auxiliary Area Allocations
Port 1 and Port 2 Port
Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port by executing STUP(237) with the same port settings as the ones already being used.
Serial Communications Boards (CS Series Only)
Word
A636
Bit Contents
03 to 15 Reserved
02 1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved
Inner Board Error
Information (CS-series
Serial Communications
Board Only)
Note
Serial Communications Units (CS/CJ Series) n = A620 + unit number n
Words Bit
03 to 15 Reserved
02
01
00
Contents
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
Reserved
A424 contains error information for the Serial Communications Board.
Word Bit
A424 12 to 15 Non-fatal
11 errors
(Note 1)
10
04
03
02
01
00
09
08
07
06
05
Fatal errors
(Note 2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area,
1: Protocol data error (SUM error); 0: Normal
1: Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
Reserved
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to Section 11 Troubleshooting and Maintenance.
268
Auxiliary Area and CIO Area Allocations
Section 8-3
8-3-2 CIO Area Allocations
Words in the CIO Area are allocated for a Status Area, which contains status and error information for the Serial Communications Board or Unit. These allocations are described in this section.
Serial Communications
Boards (CS Series Only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status
Area. Only the words shown in the following table are used for the Status Area with 1:N NT Links.
Inner Board CIO Area
CIO 1900 to CIO 1999
Usage Words
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
CIO 1925 to CIO 1999
Board status
Port 1 status
Port 2 status
Reserved
Serial Communications
Units (CS/CJ Series)
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. Only the words shown in the following table are used for the Status
Area with 1:N NT Links.
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
CIO 1650 to CIO 1674
CIO 1675 to CIO 1694
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
Unit No. A
Unit No. B
CIO 1750 to CIO 1774
CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E
Unit No. F
CIO 1850 to CIO 1874
CIO 1875 to CIO 1899 n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
269
Auxiliary Area and CIO Area Allocations
Section 8-3
8-3-3 Status Area Contents
The Status Area is used to input status information from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status.
n = CIO 1500 + 25
× unit number
Words
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO 1901 n + 1
CIO 1902
CIO 1903
CIO 1904
CIO
1905
CIO
1915
Bit
02 to 15 Reserved
01
1: Error log data error
00
1: Protocol data error n + 2 n + 3
00 to 15 Reserved
00 to 15 Reserved n + 4 00 to 15 Reserved n + 5 n + 15 12 to 15 Port set-
08 to 11 ting status
05 to 07
Setup
Area
04
03
Contents
0: Error log data normal
0: Protocol data normal
Serial communications mode: Always 2 Hex
Baud rate: 0 to 9 Hex, A Hex ()
Reserved
Start bit: Always 0 Hex
Data length: Always 1 Hex
CIO
1906
CIO
1916
02
01
00 n + 6 n + 16 15
14
Port setting status
Hardware settings
Stop bit: Always 1 Hex
Parity, Yes/No: Always 0 Hex
Parity, Even/Odd: Always 1 Hex
0 No 0 RS-232C 1 RS-422A/485 1 Reserved
0 1 0 1
CIO
1907
CIO
1917
13
02 to 12
01
00 n + 7 n + 17 11 to 15 Commu-
10 nications status
09
08
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: Setup error 0: Setup normal
1: Port operating 0: Port stopped
Reserved
1: Remote Unit receive busy (flow control)
0: Remote Unit receive wait (Always 0 Hex)
Reserved
1: Local Unit receive busy (flow control)
0: Local Unit receive wait (Always 0 Hex)
07
06
05
04
Transmission control signal status
ER signal
DTR signal
Reserved
CTS signal
03
00 to 02 n + 8 n + 18 00 to15 Reserved
RTS signal
Reserved
CIO
1908
CIO
1909 to
CIO
1914
CIO
1918
CIO
1919 to
CIO
1924 n + 9 to n + 14 n + 19 to n + 24
15 to 00 Protocol status
270
Auxiliary Area and CIO Area Allocations
Section 8-3
Note The baud rate that is input to the CPU Unit will depend on the setting in the
System Setup. If the default value is used because of a System Setup error, this default setting is input.
Error Log EEPROM Error
This bit will be set to 1 if an error occurs in reading or writing the error log stored in EEPROM on the assumption that the EEPROM has reached its useful life. If a Serial Communications Unit is being used, the ERC indicator will also light. If a Serial Communications Board is being used, A42411 will turn
ON and the ERR/ALM indicator on the CPU Unit will flash, indicating a nonfatal error.
Protocol Data Error
This bit will be turned ON if a checksum error is detected in the protocol data at startup. The checksum is checked for all serial communications modes. If a
Serial Communications Unit is being used, the ERC indicator will also flash. If a Serial Communications Board is being used, A42409 will turn ON, the ERR/
ALM indicator on the CPU Unit will flash, and the RDY indicator will flash at 1second intervals, indicating a non-fatal error.
The operation of the 1:N NT Links will not be affected by a protocol data error.
Port Setting Status
Communications Status
The settings in the Setup Area for the following items will be stored: Serial communications mode, baud rate, start bits, data length, stop bits, parity, ports, terminating resistance, terminating resistance, setup error, and port operating/stopped status. The port operating/stopped status will always be 1 for 1:N NT Links.
The flow control and buffer status is stored. This status is not used for 1:N NT
Links. These bits are cleared at startup or when a port is restarted using
STUP(237) or a Port Settings Change Bit (Auxiliary Area).
The status of the transmission control signals is stored.
Transmission Control
Signal Status
Protocol Status
The bits corresponding to the unit numbers of the connected PTs for which priority processing has been set and the bits corresponding to the unit numbers for which communications are being executed are turned ON.
Boards
(CS Series Only)
Port 1
Words
Port 2 Port 1
Unit
(CS/CJ Series)
Port 2
CIO
1909
CIO
1910 to
CIO
1914
CIO
1919
CIO
1920 to
CIO
1924 n + 9 n + 19 n + 10 to n + 14 n + 20 to n + 24
Bit Contents
15 to 08 PT Priority Registered Flag
07 to 00 PT Communications Execution Flag
15 to 00 Reserved
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
PT Priority Registered Flag
Unit No. 7 to Unit No. 0
PT Communications Execution Flag
Unit No. 7 to Unit No. 0
271
Auxiliary Area and CIO Area Allocations
Section 8-3
272
SECTION 9
Using Modbus-RTU Slave Mode (Unit Version 1.3 or Later)
This section describes the procedure and other information required to use Modbus-RTU slave mode.
9-1-1 Communicating with CS/CJ-series CPU Units Using Modbus . . . .
9-2 Setup Area Allocations (Modbus-RTU Slave Mode) . . . . . . . . . . . . . . . . . . .
9-2-1 Setup Area Words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-2-2 Setup Area Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3 Auxiliary Area and CIO Area Allocations (Modbus-RTU Slave Mode) . . . .
9-3-1 Auxiliary Area Allocations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-3-2 CIO Area Allocations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-4-1 Simultaneous Commands and Communications Ports . . . . . . . . . . .
9-4-2 Communications Control Signals and Communications Timing . . .
9-4-3 Flags for Network Communications. . . . . . . . . . . . . . . . . . . . . . . . .
9-4-4 Timing of Commands Addressed to a Host Computer. . . . . . . . . . .
9-5-2 RS-422A/485 Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9-6 Modbus-RTU Slave Function for Replacing Existing PLCs . . . . . . . . . . . . .
9-6-1 Support for 1:1 Modbus-RTU Slave . . . . . . . . . . . . . . . . . . . . . . . . .
9-6-2 Modbus-RTU Slave-compatible Device Selection . . . . . . . . . . . . . .
273
Modbus-RTU Slave System
Section 9-1
9-1 Modbus-RTU Slave System
A Modbus-RTU Slave System can be used to send Modbus-RTU commands from a host computer (e.g., personal computer) to a PLC to read and write I/O memory.
Host-initiated
Communications
Communications in a Modbus-RTU Slave System are started by the host computer.
Command
Host computer CS/CJ-series PLC
Response
The host computer sends a command to the PLC. The PLC processes the command and returns a response to the host computer. This process is repeated, allowing the host computer to monitor and control PLC operation.
Note Only Modbus-RTU slave mode is supported. A Modbus-ASCII slave mode is not supported by the Serial Communications Boards or Serial Communications Units.
Modbus-RTU Specifications
Item
Mode
Baud rate
Data length
Parity
Stop bits
Description
Modbus-RTU slave mode (See note 1.)
1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps
Default: 19,200 bps
8 bits (See note 2.)
Odd, even, or none
Default: Even
Odd or even parity:1 bit
No parity: 2 bits (See note 3.)
1 to 247 (broadcasting: 0) (See note 4.) Address setting range
Frame format Slave address: 1 byte
Function code: 1 byte
Data: 0 to 252 bytes
CRC code: 2 bytes
Note
1.
Modbus-ASCII mode is not supported.
2.
The data length is fixed at 8 bits and cannot be changed by the user.
3.
The number of stop bits is automatically determined by the parity and cannot be set by the user.
4.
The address cannot be set to 0. In commands, 0 is used to indicate broadcast commands.
9-1-1 Communicating with CS/CJ-series CPU Units Using Modbus
There are four data models that are defined for Modbus. Settings in the DM
Area are used to the I/O memory area in the CS/CJ-series CPU Unit corresponding to each of these data models for use by the Serial Communications
Board/Unit. The I/O memory areas that can be set for each of the Modbus data models are given below.
1.
Discrete inputs:
2.
Coils:
CIO Area (fixed)
CIO, Work, Holding, or Auxiliary Area
3.
Input Registers: CIO, Work, Holding, or Auxiliary Area
4.
Holding Registers: DM or EM Area
274
Setup Area Allocations (Modbus-RTU Slave Mode)
Section 9-2
Note
The Modbus-RTU command that access a specific Modbus data model is used to read and write I/O memory areas in the CS/CJ-series CPU Unit.
CS/CJ-series CPU Unit
I/O Memory Modbus Data Models
CIO Area
:
0
1
2
Discrete Inputs
:
1
2
3
Modbus-RTU command
Work Area 0
1
:
2
Coils 1
2
:
3
Holding Area
:
2
0
1
DM Area 0
1
:
2
Input Registers
:
3
1
2
Holding Registers
1
2
:
3
Modbus Commands
Read Discrete Inputs
Read Holding Registers
Read Input Registers
Write Single Coil
Write Single Register
Write Multiple Coils
Write Multiple Registers
EM Area
0
1
:
2
DM Area settings are used to allocate the area for each data model except for discrete inputs.
Refer to 9-2 Setup Area Allocations (Modbus-RTU Slave Mode) for the DM
Area settings to allocate areas. Refer to 9-3-4 Command and Response
Details for details on Modbus-RTU commands.
1.
DM Area settings are read when the power is turned ON to the CPU Unit, when the Serial Communications Board/Unit is restarted, or when the port is restarted. Always cycle the power to the CPU Unit or restart the Serial
Communications Board/Unit or port after changing the settings.
2.
Addresses in Modbus data models start from 1, but addresses specified in
Modbus-RTU commands and addresses in the CS/CJ-series CPU Unit start from 0. To access address 0 in an area allocated in the CS/CJ-series
CPU Unit, specify address 100 in the Modbus-RTU command.
9-2 Setup Area Allocations (Modbus-RTU Slave Mode)
This section describes the Setup Area allocated to the Serial Communications
Board and Serial Communications Units in the DM Area when Modbus-RTU slave communications are used.
9-2-1 Setup Area Words
The Serial Communications Board and Serial Communications Units use the following words as a Setup Area in the DM Area when Modbus-RTU slave communications are used. The words allocated to the Serial Communications
Board are different from those allocated to the Serial Communications Units
(which are allocated words according to the unit numbers).
275
Setup Area Allocations (Modbus-RTU Slave Mode)
Serial Communications
Boards (CS Series only)
Serial Communications
Units (CS/CJ Series)
Section 9-2
Setup Area Allocated in the DM Area: D32000 to D32099
Words
D32000 to D32009
D32010 to D32019
D32020 to D32029
D32030 to D32039
D32040 to D32767
Usage
Port 1 Settings
Port 2 Settings
Port 1 Settings for Modbus-RTU slave mode
Port 2 Settings for Modbus-RTU slave mode
Reserved for the system
Setup Area Allocated in the DM Area: D30000 to D31599
First Word in Setup Area Allocated in the DM Area: m = D30000 + 100
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Words
D30000 to D30099
D30100 to D30199
D30200 to D30299
D30300 to D30399
D30400 to D30499
D30500 to D30599
Unit No. 6
Unit No. 7
Unit No. 8
Unit No. 9
D30600 to D30699
D30700 to D30799
D30800 to D30899
D30900 to D30999
Unit No. A
Unit No. B
D31000 to D31099
D31100 to D31199
Unit No. C D31200 to D31299
Unit No. D D31300 to D31399
Unit No. E
Unit No. F
D31400 to D31499
D31500 to D31599
276
Setup Area Allocations (Modbus-RTU Slave Mode)
Section 9-2
9-2-2 Setup Area Contents
m = D30000 + 100
× Unit No.
Board
(CS Series only)
Words
Unit
(CS/CJ Series)
Port 1
D32000
Port 2
D32010 m
Port 1 Port 2
m + 10
D32001
D32002 to
D32005
D32006
D32007 to
D32009
D32020
D32021
D32011
D32012 to
D32015
D32016
D32017 to
D32019
D32030
D32031 m + 1 m + 2 to m + 5 m + 6 m + 7 to m + 9 m + 20 m + 21
D32022 to
D32029
D32032 to
D32039 m + 22 to m + 29 m + 11 m + 12 to m + 15 m + 16 m + 17 to m + 19 m + 30 m + 31 m + 32 to m + 39
Bit Setting contents
15 Port settings 0: Defaults; 1: User settings
12 to 14 Reserved
08 to 11 Serial communications mode
A hex: Modbus-RTU slave
05 to 02 Reserved
01 Parity
00 Parity
0: Yes; 1: No
0: Even; 1: Odd
04 to 15 Reserved
00 to 03 Baud rate (bps)
0: Default (19,200); 3: 1,200; 4: 2,400; 5: 4,800; 6: 9,600;
7: 19,200; 8: 38,400; 9: 57,600; A: 115,200
15 Reserved.
14 to 00 Reserved.
15 to 08 Modbus Slave Address
01 to F7 hex (1 to 247)
07 to 00 Reserved.
15 to 08 Reserved.
07 to 00 Reserved.
15 to 08 Reserved.
07 to 00 Coils Allocation Area
00 hex: CIO Area
B0 hex: CIO Area, B1 hex: Work Area, B2 hex: Holding Area,
B3 hex: Auxiliary Area
15 to 08 Input Registers Allocation Area
00 hex: CIO Area
B0 hex: CIO Area, B1 hex: Work Area, B2 hex: Holding Area,
B3 hex: Auxiliary Area
07 to 00 Holding Registers Allocation Area
00 hex: DM Area
82 hex: DM Area
50 to 5C hex: EM Area, bank 0 to C
15 to 08 Reserved.
07 to 00 Reserved.
Port Settings
Serial Communications
Mode
The setting for the port settings determine if the default settings or user settings will be used for port 1 and port 2. Be sure to use the same settings as the communications port on the host computer connected via the Modbus-
RTU Slave System.
If the default port settings are specified, then the setting of bits 00 and 01 and the baud rate in D32001 will be ignored.
The default settings used are as follows: Baud rate: 19,200 bps, start bits:
1 bit, data length: 8 bits, parity: even, and stop bits: 1 bit.
If user port settings are specified, set bits 00 and 01 and set the baud rate in
D32001.
Set the serial communications mode to A hex to use Modbus-RTU Slave communications.
277
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
Parity and Baud Rate
If user settings are specified for the port settings, the parity and baud rate must be set.
Set the Modbus-RTU slave address to between 1 and 247 (1 and F7 hex).
Modbus-RTU Slave
Address
Allocation Areas for Coils, Input Registers, and Holding Registers
The I/O memory areas in the CS/CJ-series CPU Unit that correspond to the
Modbus Data Models (Coils, Input Registers, and Holding Registers) can be set. The Discrete Inputs data model always accesses the CIO Area.
Modbus data model Modbus address
Discrete Inputs
Coils
Input Registers
Holding Registers
1 to 5120
1 to 65536
1 to 8192
1 to 8192
1 to 15360
1 to 6144
1 to 512
1 to 512
1 to 960
1 to 32768
1 to 32768
Address specified in commands
0 to 5119
0 to 65535
Corresponding CS/
CJ-series CPU Unit address
CIO 0 to CIO 319
(bits 0 to 5119)
CIO 0 to CIO 4095
(bits 0 to 65535)
(See note.)
0 to 8191
0 to 8191
0 to 15359
0 to 6143
0 to 511
0 to 511
0 to 959
0 to 32767
0 to 32767
W0 to W511
(bits 0 to 8191)
H0 to H511
(bits 0 to 8191)
A0 to A959
(bits 0 to 15359)
CIO 0 to CIO 6143
W0 to W511
H0 to H511
A0 to A959
D0 to D32767
E
@_0 to E@_32767
Allocation area setting (in DM Area settings)
CIO Area (fixed: there is no setting)
CIO Area (default)
Work Area
Holding Area
Auxiliary Area
CIO Area (default)
Work Area
Holding Area
Auxiliary Area
DM Area (default)
DM Area bank
@
Note
1.
Bits in the following word addresses can be accessed in the CIO Area for
Coils: CIO 0 to CIO 4095
2.
Addresses in Modbus data models start from 1, but addresses specified in
Modbus-RTU commands and addresses in the CS/CJ-series CPU Unit start from 0. Refer to the above table when specifying addresses in applications.
9-3 Auxiliary Area and CIO Area Allocations (Modbus-RTU
Slave Mode)
This section describes the bits and words used by the Serial Communications
Board and Serial Communications Units in the Auxiliary Area and the Status
Area allocated in the CIO Area. The Software Switches allocated in the CIO
Area are not used for Modbus-RTU Slave communications.
9-3-1 Auxiliary Area Allocations
Port 1 and Port 2 Port
Settings Change Bits
These bits can be turned ON from the program using the OUT or other instructions to change communications settings and restart the Serial Communications Board ports. When changing the settings and restarting the port have been completed, the bit will automatically be turned OFF.
Note These bits are used both to change the port settings and to restart the port at the same time. One of these bits can be turned ON to restart a port without changing the port settings in the Setup Area allocated in the DM Area. The
STUP(237) instruction can also be used to just restart a communications port
278
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
by executing STUP(237) with the same port settings as the ones already being used.
Serial Communications Boards (CS Series only)
Word
A636
Bit Contents
03 to 15 Reserved
02 1: Port 2 Settings Change Bit
01
00
1: Port 1 Settings Change Bit
Reserved
Inner Board Error
Information (CS-series
Serial Communications
Board Only)
Serial Communications Units (CS/CJ Series)
n
Words Bit
03 to 15 Reserved
02
01
Contents
1: Port 2 Settings Change Bit
1: Port 1 Settings Change Bit
00 Reserved n = A620 + unit number
A424 contains error information for the Serial Communications Board.
Word Bit
A424 12 to 15 Non-fatal
11 errors
(Note 1)
10
06
05
04
03
09
08
07
02
01
00
Fatal errors
(Note 2)
Contents
Reserved
1 Error log EEPROM error; 0: Normal
1: Protocol macro execution error; 0: Normal
This bit will be turned ON when code 3, 4, or 5 is stored in the error code for bits 00 to 03 of CIO 1909 or CIO 1919 in the CIO Area,
1: Protocol data error (SUM error); 0: Normal
1: Setup error; 0: Normal
1: Routing table error; 0: Normal
Reserved
1: Cyclic monitoring error; 0: Normal
Reserved
Reserved
Reserved
1: Inner Bus error; 0: Normal
1: Inner Board watchdog timer error; 0: Normal
Note
1.
When any one of bits 05 to 11 is ON, A40208 (Inner Board Error Flag)
(non-fatal error) will be ON.
2.
When bit 00 or 01 is ON, A40112 (Inner Board Fatal Error Flag) will be ON.
For details on errors, refer to Section 11 Troubleshooting and Maintenance.
9-3-2 CIO Area Allocations
Words in the CIO Area are allocated for a Status Area, which contains status and error information for the Serial Communications Board or Unit. These allocations are described in this section.
Serial Communications
Boards (CS Series only)
Words CIO 1900 to CIO 1999 in the Inner Board Area are used for a Status
Area. Only the words shown in the following table are used for the Status Area with Modbus-RTU Slave communications.
279
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
Inner Board CIO Area
CIO 1900 to CIO 1999
Words
CIO 1901 to CIO 1904
CIO 1905 to CIO 1914
CIO 1915 to CIO 1924
Board status
Port 1 status
Port 2 status
Usage
Serial Communications
Units (CS/CJ Series)
Words CIO 1500 to CIO 1899 in the CPU Bus Unit Area in the CIO Area are allocated according to the unit number setting. Each Unit is allocated 25 words. Only the words shown in the following table are used for the Status
Area with Modbus-RTU Slave communications.
CPU Bus Unit Area
CIO 1500 to CIO 1899 n = CIO 1500 + 25
× unit number
Unit No.
Unit No. 0
Unit No. 1
Unit No. 2
Unit No. 3
Unit No. 4
Unit No. 5
Unit No. 6
Words
CIO 1500 to CIO 1524
CIO 1525 to CIO 1549
CIO 1550 to CIO 1574
CIO 1575 to CIO 1599
CIO 1600 to CIO 1624
CIO 1625 to CIO 1649
CIO 1650 to CIO 1674
Unit No. 7
Unit No. 8
Unit No. 9
Unit No. A
CIO 1675 to CIO 1699
CIO 1700 to CIO 1724
CIO 1725 to CIO 1749
CIO 1750 to CIO 1774
Unit No. B CIO 1775 to CIO 1799
Unit No. C CIO 1800 to CIO 1824
Unit No. D CIO 1825 to CIO 1849
Unit No. E CIO 1850 to CIO 1874
Unit No. F CIO 1875 to CIO 1899 n + 1 to n + 4: Unit status n + 5 to n + 14: Port 1 status n + 15 to n + 24: Port 2 status
Status Area
The Status Area is used for status information input from Serial Communications Board or Unit to the CPU Unit. The Status Area is where the Serial Communications Board or Unit set communications status, the transmission control signal status, and the transmission error status.
n = CIO 1500 + 25
× unit number
Contents Words
Boards
(CS Series only)
Units
(CS/CJ Series)
Port 1 Port 2 Port 1 Port 2
CIO 1901 n + 1
CIO 1902
CIO 1903
CIO 1904 n + 2 n + 3 n + 4
Bit
02 to 15 Reserved
01 1: Error log EEPROM error
00 1: Protocol data error
00 to 15 Reserved
00 to 15 Reserved
00 to 15 Reserved
0: Error log EEPROM normal
0: Protocol data normal
280
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
CIO
1909
CIO
1910
CIO
1911
CIO
1912
CIO
1913
CIO
1914
Words
Boards
(CS Series only)
Units
(CS/CJ Series)
CIO
1907
CIO
1908
CIO
1917
CIO
1918
Bit
Port 1 Port 2 Port 1 Port 2
CIO
1905
CIO
1915 n + 5 n + 15 12 to 15
08 to 11
05 to 07
Port setting status
04
03
02
01
CIO
1906
CIO
1916
00 n + 6 n + 16 15
14
13
Contents
02 to 12
01
00 n + 7 n + 17 11 to 15 Commu-
10 nications status
09
08
Setup settings
Serial communications mode (A hex: fixed)
Baud rate (Note 1)
Reserved
Start bits: Always 0
Data length: Always 1
Stop bits (Note 2)
Parity: Yes/No (Note 1)
Hardware settings
Parity: Even/Odd (Note 1)
0 No 0 RS-232C 1 RS-422A/485 1 Reserved
1 0 1 0
0: Terminating resistance OFF
1: Terminating resistance ON
Reserved
1: Setup error; 0: Setup normal
1: Port operating; 0: Port stopped
Reserved
1: Remote Unit busy receiving (Flow control)
0: Remote Unit ready to receive (Note 3)
Reserved
1: Local Unit busy receiving (Flow control)
0: Local Unit ready to receive (Note 4)
07
06
05
04
03
00 to 02 n + 8 n + 18 15
14 to 08
Transmission control signal status
ER signal
DTR signal
Reserved
CTS signal
RTS signal
Reserved
1: Transmission error; 0: No transmission error
Note used.
Transmission error status
07
06 to 05
04
03
1: CRC error, 0: Normal
Note used.
1: Overrun error; 0: Normal
1: Framing error; 0: Normal
02
00, 01
1: Parity error; 0: Normal
Reserved n + 9 n + 19 15 to 00 Number of normally received commands CIO
1919
CIO
1920
CIO
1921
CIO
1922
CIO
1923
CIO
1924 n + 10 n + 11 n + 12 n + 13 n + 14 n + 20 n + 21 n + 22 n + 23 n + 24
15 to 00
15 to 00
15 to 00
15 to 00
15 to 00
Number of normally sent responses
Number of overrun errors, framing errors, and parity errors (transmission errors)
Number of CRC errors (transmission errors)
Number of command format errors (illegal function codes and illegal addresses)
Reserved.
281
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
Error Log EEPROM Error
Protocol Data Error
Port Setting Status
Note
Communications Status
1.
The settings in the Setup Area are reflected here. The default settings will be used and will be stored here if a setup error occurs.
2.
Always 1 (1 stop bit) when there is parity and always 0 (2 stop bits) when there is no parity.
3.
The status of this bit is not stable in Modbus-RTU Slave mode.
4.
Always 0 in Modbus-RTU Slave mode.
This bit will be set to 1 if an error occurs in reading or writing the error log stored in EEPROM on the assumption that the EEPROM has reached its useful life. If a Serial Communications Unit is being used, the ERC indicator will also light. If a Serial Communications Board is being used, A42411 will turn
ON and the ERR/ALM indicator on the CPU Unit will flash, indicating a nonfatal error.
This bit will be turned ON if a checksum error is detected in the protocol data at startup. The checksum is checked for all serial communications modes. If a
Serial Communications Unit is being used, the ERC indicator will also flash. If a Serial Communications Board is being used, A42409 will turn ON, the ERR/
ALM indicator on the CPU Unit will flash, and the RDY indicator will flash at 1second intervals, indicating a non-fatal error.
The operation of Modbus-RTU Slave communications is not affected by a protocol data error.
The settings in the Setup Area for the following items will be stored: Serial communications mode, baud rate, start bits, data length, stop bits, parity, ports, terminating resistance, setup error, and port operating/stopped status.
The port operating/stopped status will always be 1 for Modbus-RTU Slave mode.
The flow control and buffer status is stored. This status is not used in the Modbus-RTU slave mode. These bits are cleared at startup or when a port is restarted using STUP(237) or a Port Settings Change Bit (Auxiliary Area).
The status of the following transmission control signals is stored: ER signal,
DTR signal, CTS signal, and RTS signal. 1: High, 0: Low
Transmission Control
Signal Status
Transmission Error Status
Number of Normally
Received Commands
Number of Normally Sent
Responses
Number of Overrun Errors,
Framing Errors, and Parity
Errors
The Transmission Error Flag (bit 15) will turn ON if any of the following flags turn ON: CRC error (bit 07), Overrun Error (bit 04), Framing Error (bit 03), or
Parity Error (bit 02).
The number of normal Modbus-RTU commands received from the communications port is stored.
The number of normal Modbus-RTU responses sent to the communications port is stored.
The number of overrun errors, framing errors, and parity errors that has occurred is stored.
Number of CRC Errors
Number of Command
Format Errors
The number of CRC errors that has occurred is stored.
The number of illegal function codes and illegal addresses in received Modbus-RTU commands is stored.
Note The above counters (number of normally received commands, number of normally sent responses, number of overrun errors, framing errors, and parity errors, number of CRC errors, and number of command format error) are
282
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
cleared to 0 when the power supply to the Serial Communications Board/Unit is turned ON. Counting will stop if they reach FFFF hex.
9-3-3 Supported Modbus-RTU Commands
The Modbus-RTU slave mode of the Serial Communications Board/Unit supports the following Modbus-RTU commands.
Function code
(hexadecimal)
01
02
Function
Reads multiple bits from the CIO, Work,
Holding, or Auxiliary Area of I/O memory.
Reads multiple bits from the CIO Area of
I/O memory.
03
04
05
06
Reads multiple words from the DM or EM
Area of I/O memory.
Reads multiple words from the CIO,
Work, Holding, or Auxiliary Area of I/O memory.
Writes a bit in I/O memory.
Writes a word in the DM or EM Area of I/
O memory.
08
0F
10
Executes an echoback test.
Writes multiple bits in I/O memory.
Writes multiple words in the DM or EM
Area of I/O memory.
Modbus name
Read Coils
Read Discrete Inputs
Read Holding Registers
Read Input Registers
Write Single Coil
Write Single Register
Diagnostic
Write Multiple Coils
Write Multiple Registers
The frame format used in Modbus-RTU slave mode is as follows:
Slave address
1 byte
Function code
1 byte
Data
0 to 252 bytes
CRC
2 bytes (See note.)
Note The CRC code is given in the order low byte, high byte.
Note
1.
Setting the slave address to 0 indicates a broadcast command. Responses are not returned for broadcast commands.
2.
DM Area settings are read when the power is turned ON to the CPU Unit, when the Serial Communications Board/Unit is restarted, or when the port is restarted.
3.
Program retry processing on the host computer (e.g., personal computer) when a transmission error or other communications error occurs.
9-3-4 Command and Response Details
Read Coils
Function
Reads multiple bits from the CIO, Work, Holding, or Auxiliary Area of I/O memory.
Command
Length
Function Code
Starting Address
Quantity of Coils
1 byte
2 bytes
2 bytes
Note The address depends on the area that is allocated.
Data
01 hex
0000 to FFFF hex (See note.)
1 to 3E8 hex (1 to 1000)
283
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
Response
Length
Function Code
Byte Count
Coil Status
1 byte
1 byte n byte
Reading 19 Bits from
CIO 0001.04 to
CIO 0002.06
Request
Function Code
Starting Address (H)
Starting Address (L)
Quantity of Coils (H)
Quantity of Coils (L)
Data
01 hex
00 hex
14 hex
00 hex
13 hex
Note Unused bits are filled with zeros.
01 hex
N n = N or N+1
Data
Response
Function Code
Byte Count
Coil Status 27 to 20
Coil Status 35 to 28
Coil Status 38 to 36
Data
01 hex
03 hex
CD hex
6B hex
05 hex
15
CIO 0 15
CIO 1 31
1
CIO 2 47
CIO 3 63
14
14
30
0
46
62
13
13
29
1
45
61
12
12
28
1
44
60
11
11
27
1
43
59
10
10
26
1
42
58
9
9
25
0
41
57
8
8
24
0
40
56
7
7
23
1
39
55
6
6
22
1
38
1
54
5
5
21
0
37
0
53
4
4
20
1
36
1
52
3
3
19
35
0
51
2
2
18
34
1
50
1
1
17
33
1
49
0
0
16
32
0
48
Note The subscript numbers in the shaded boxes indicate the ON/OFF (1/0) status of the bits that are read.
Read Discrete Inputs
Function
Command
Reads multiple bits from the CIO Area of I/O memory.
Function Code
Starting Address
Quantity of Coils
1 byte
2 bytes
2 bytes
Length Data
02 hex
0000 to 13FF hex
1 to 3E8 hex (1 to 1000)
Response
Length
Function Code
Byte Count
Coil Status
1 byte
1 byte n byte
Reading 19 Bits from
CIO 0001.04 to
CIO 0002.06
Request
Function Code
Starting Address (H)
Starting Address (L)
Quantity of Coils (H)
Quantity of Coils (L)
Data
02 hex
00 hex
14 hex
00 hex
13 hex
Note Unused bits are filled with zeros.
Data
02 hex
N (See note.) n = N or N+1
Response
Function Code
Byte Count
Coil Status 27 to 20
Coil Status 35 to 28
Coil Status 38 to 36
Data
02 hex
03 hex
CD hex
6B hex
05 hex
284
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
15
CIO 0 15
CIO 1 31
1
CIO 2 47
CIO 3 63
14
14
30
0
46
62
13
13
29
1
45
61
12
12
28
1
44
60
11
11
27
1
43
59
10
10
26
1
42
58
9
9
25
0
41
57
8
8
24
0
40
56
7
7
23
1
39
55
6
6
22
1
38
1
54
5
5
21
0
37
0
53
4
4
20
1
36
1
52
3
3
19
35
0
51
2
2
18
34
1
50
1
1
17
33
1
49
0
0
16
32
0
48
Note The subscript numbers in the shaded boxes indicate the ON/OFF (1/0) status of the bits that are read.
Read Holding Registers
Function
Reads multiple words from the DM or EM Area of I/O memory.
Command
Function Code
Starting Address
1 byte
2 bytes
Quantity of Registers 2 bytes
Length Data
03 hex
0 to 7FFF hex (See note.)
1 to 7D hex
Note The address depends on the area that is allocated.
Response
Reading 3 Words from
D1000 to D1002
Function Code
Byte Count
Register Value
1 byte
1 byte
N
× 2 bytes
Length
Note N = Quantity of Registers
Request
Data
Function Code
Starting Address (H)
03 hex
03 hex
Starting Address (L) E8 hex
Quantity of Registers (H) 00 hex
Quantity of Registers (L) 03 hex
Data
03 hex
N
× 2 (See note.)
Response
Function Code
Byte Count
Register Value (H) DM1000
Register Value (L) DM1000
Register Value (H) DM1001
Register Value (L) DM1001
Register Value (H) DM1002
Register Value (L) DM1002
Data
03 hex
06 hex
AB hex
12 hex
56 hex
78 hex
97 hex
13 hex
D1000
D1001
D1002
15 14
5
9
A
13 12 11 10
6
7
B
9 8 7 6
7
1
1
5 4 3 2
8
3
2
1 0
285
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
Read Input Registers
Function
Reads multiple words from the CIO, Work, Holding, or Auxiliary Area of I/O memory.
Command
Function Code
Starting Address
1 byte
2 bytes
Quantity of Registers 2 bytes
Length Data
04 hex
0 to 17FF hex (See note.)
1 to 7D hex
Note The address depends on the area that is allocated.
Response
Reading 3 Words from
D1000 to D1002
Function Code
Byte Count
Register Value
1 byte
1 byte
N
× 2 bytes
Length
Note N = Quantity of Registers
Request
Function Code
Starting Address (H)
Data
04 hex
03 hex
Starting Address (L) E8 hex
Quantity of Registers (H) 00 hex
Quantity of Registers (L) 03 hex
Data
04 hex
N
× 2 (See note.)
Response
Function Code
Byte Count
Register Value (H) DM1000
Register Value (L) DM1000
Register Value (H) DM1001
Register Value (L) DM1001
Register Value (H) DM1002
Register Value (L) DM1002
Data
04 hex
06 hex
AB hex
12 hex
56 hex
78 hex
97 hex
13 hex
D1000
D1001
D1002
15 14
5
9
A
13
Write Single Coil
Function
Command
12 11 10
6
7
B
9 8
Writes a bit in I/O memory.
7 6
7
1
1
5 4 3 2
8
3
2
1 0
Length
Function Code
Output Address
Output Value
1 byte
2 bytes
2 bytes
Note The address depends on the area that is allocated.
Data
05 hex
0 to FFFF hex (See note.)
0000 hex (OFF) or FF00 (ON)
286
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Response
Length
Function Code
Output Address
Output Value
1 byte
2 bytes
2 bytes
Writing 1 (ON) to
CIO 0002.02
Request
Function Code
Output Address (H)
Output Address (L)
Output Value (H)
Output Value (L)
Data
05 hex
00 hex
22 hex
FF hex
00 hex
Response
Function Code
Output Address (H)
Output Address (L)
Output Value (H)
Output Value (L)
Section 9-3
Data
05 hex
0 to FFFF hex
0000 hex (OFF) or FF00 (ON)
Data
05 hex
00 hex
22 hex
FF hex
00 hex
15
CIO 0 15
CIO 1 31
CIO 2 47
CIO 3 63
14
14
30
46
62
13
13
29
45
61
12
12
28
44
60
11
11
27
43
59
10
10
26
42
58
9
9
25
41
57
8
8
24
40
56
7
7
23
39
55
6
6
22
38
54
5
5
21
37
53
4
4
20
36
52
3
3
19
35
51
2
2
18
34
50
1
1
17
33
49
Note The shaded number indicate the ON/OFF status of the bit that is written.
0
0
16
32
48
Write Single Register
Function
Command
Writes a word in the DM or EM Area of I/O memory.
Length
Function Code
Register Address
Register Value
1 byte
2 bytes
2 bytes
Note The address depends on the area that is allocated.
Data
06 hex
0 to 7FFF hex (See note.)
0 to FFFF hex
Response
Function Code
Register Address
Register Value
1 byte
2 bytes
2 bytes
Length Data
06 hex
0 to 7FFF hex
0 to FFFF hex
Writing 3AC5 Hex to
D2000
Request Response
Function Code
Register Address (H)
Register Address (L)
Register Value (H)
Register Value (L)
Data
06 hex
07 hex
D0 hex
3A hex
C5 hex
Function Code
Register Address (H)
Register Address (L)
Register Value (H)
Register Value (L)
Data
06 hex
07 hex
D0 hex
3A hex
C5 hex
287
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Section 9-3
15
D2000
D2001
D2002
Diagnostic
Function
Command
14
3
13 12 11 10
A
9 8 7 6
C
5 4 3
Executes an echoback test. Send data will be returned.
Length
Function Code 1 byte
Sub-function Code 2 bytes
Data N
× 2 bytes (See note.)
Note From 2 to 125 (2 to 7D hex) bytes can be specified.
08 hex
0 hex
---
Response
Length
Function Code 1 byte
Sub-function Code 2 bytes
Data N
× 2 bytes (See note.)
Note Same as in command data.
08 hex
0 hex
---
Sending A537 Hex
Request
2
Response
Data
Data
5
1
Function Code
Sub-function Code (H)
Sub-function Code (L)
Data (H)
Data (L)
Data
08 hex
00 hex
00 hex
A5 hex
37 hex
Function Code
Sub-function Code (H)
Sub-function Code (L)
Data (H)
Data (L)
0
Data
08 hex
00 hex
00 hex
A5 hex
37 hex
Write Multiple Coils
Function
Writes multiple bits in I/O memory. Allocated memory is in the C10 Area
(fixed).
Command
Function Code
Starting Address
Quantity of Output
Byte Count
Output Value
1 byte
2 bytes
2 bytes
1 byte n byte
Length Data
0F hex
0 to FFFF hex
1 to 3E8 hex
N n = N or N + 1
Response
Function Code
Starting Address
Quantity of Output
1 byte
2 bytes
2 bytes
Length Data
0F hex
0 to FFFF hex
1 to7B0 hex
288
Auxiliary Area and CIO Area Allocations (Modbus-RTU
Writing 10 Bits Starting from CIO 0001.04
(xxxx xx11 1100 1101)
Request
Function Code
Starting Address (H)
Starting Address (L)
Quantity of Output (H)
Quantity of Output (L)
Byte Count
Output Value (H)
Output Value (L)
Data
0F hex
00 hex
14 hex
00 hex
0A hex
02 hex
3A hex
01 hex
Section 9-3
Response
Function Code
Starting Address (H)
Starting Address (L)
Quantity of Output (H)
Quantity of Output (L)
Data
0F hex
00 hex
14 hex
00 hex
0A hex
15
CIO 0 15
CIO 1 31
0
14
14
30
0
13
13
29
0
12
12
28
1
11
11
27
0
10
10
26
0
9
9
25
1
8
8
24
1
7
7
23
1
6
6
22
0
5
5
21
1
4
4
20
0
3
3
19
0
2
2
18
0
1
1
17
0
0
0
16
0
Note The subscript numbers in the shaded boxes indicate the ON/OFF (1/0) status of the bits that are written. Other bits in the same word are set to 0.
Write Multiple Registers
Function
Writes multiple words in the DM or EM Area of I/O memory.
Command
Function Code 1 byte
Starting Address 2 bytes
Quantity of Registers 2 bytes
Byte Count
Registers Value
1 byte
N
× 2 bytes
Length
Note N = Number of write bytes
Data
10 hex
0 to 7FFF hex
1 to 7B hex
N
× 2 (See note.) value
Response
Function Code 1 byte
Starting Address 2 bytes
Quantity of Registers 2 bytes
Length Data
10 hex
0 to 17FF hex
1 to7B hex
Writing 3AC5, 9713 Hex to 2 Words, D1000 and
D1001
Response Request
Function Code
Data
10 hex
Starting Address (H)
Starting Address (L)
03 hex
E8 hex
Quantity of Registers (H) 00 hex
Quantity of Registers (L) 02 hex
Byte Count
Registers Value (H)
Registers Value (L)
Registers Value (H)
Registers Value (L)
04 hex
3A hex
C5 hex
97 hex
13 hex
Function Code
Starting Address (H)
Starting Address (L)
Quantity of Registers (H)
Quantity of Registers (L)
Data
10 hex
03 hex
E8 hex
00 hex
02 hex
289
Communications Timing
Section 9-4
15
D1000
D1001
Error Format
14
3
13
9
12 11 10
A
9
7
8 7 6
C
5
1
4 3 2
5
1
3
0
Function Code
Exception Code
1 byte
1 byte
Length Data
Function code + 80 hex
Error code
Error code
01
02
03
04
Name Description
Illegal function • There is an error in the specified function code.
• A function code not supported by the Serial Communications Board/Unit was specified.
Illegal data address • There is an error in the specified starting address.
• The combination of the specified starting address and data length (quantity of registers/coils) exceeds the valid range.
• The specified data length (quantity of registers/ coils) exceeds the valid range.
• The specified data length (quantity of registers/ coils) differs from the actual data length.
• Less than 4 bytes of data was received.
Illegal data value
• There is an error in the specified data. (The data for the Write Single Coil Command is not 0000 hex or
FF00 hex.)
Slave device failure • Reading or writing could not be performed because an error occurred in the CPU Unit.
9-4 Communications Timing
This section describes the timing of sending commands and controlling communications in the Modbus-RTU Slave mode.
9-4-1 Simultaneous Commands and Communications Ports
The CS/CJ-series CPU Units provide eight logical ports that can be used when executing SEND(090), RECV(098), and CMND(490). Therefore, up to eight commands can be executed for one physical port during any one cycle.
The maximum number of messages, however, that can be sent or received in one CPU Bus Unit service time is two messages from the CPU Unit to the
Board or Unit and two messages from the Board or Unit to the CPU Unit.
290
Communications Timing
Section 9-4
Board or Unit Logical port
5
1
6
3
0
4
7
2
CPU Unit
Instruction 1
Instruction 2
Instruction 3
Instruction 4
Instruction 5
Instruction 6
Instruction 7
Instruction 8
One port must be specified for each instruction.
Note
1.
If more than eight communications instructions are being used, then exclusive control must be performed to make sure that not more than eight are executed at the same time. Refer to descriptions of network communications instructions in the CS/CJ-series Communications Commands Refer-
ence Manual (W342).
2.
The same communications port numbers are used by both the communications instructions (SEND(090), RECV(098), and CMND(490)) and the
PROTOCOL MACRO instruction (PMCR(260)). The same port number cannot be used by more than one of these instructions at the same time.
9-4-2 Communications Control Signals and Communications Timing
If CTS control is enabled in the Setup Area, the RTS output signal will be turned ON from the Board or Unit and the send process will go on standby until the CTS input signal turns ON. Either release this busy status by incorporating the RTS output signal for the CTS input signal at the host computer, or loop the RTS output signal back to the CTS input signal at the Unit or Board.
Note The status of the RTS and CTS signals can be confirmed in the Transmission
Control Signal Status in the Status Area. Refer to page 280.
9-4-3 Flags for Network Communications
This section describes the flags in the Auxiliary Area that are used when executing SEND(090), RECV(098), and CMND(490).
Communications Port
Enabled Flags
A Communications Port Enabled Flag turns ON when SEND(090),
RECV(098), and CMND(490) can be executed. The flag will turn OFF during execution of these commands and turn ON again when the command execu-
291
Communications Timing
Communications Port
Error Flags
Communications Port
Completion Codes
Section 9-4
tion is completed. When creating the ladder diagram, use these flags as input conditions when executing these instructions.
Word
A202
05
04
03
02
Bit
08 to 15
07
06
01
00
Content
Reserved
Communications Port Enabled Flag, Port No. 7
Communications Port Enabled Flag, Port No. 6
Communications Port Enabled Flag, Port No. 5
Communications Port Enabled Flag, Port No. 4
Communications Port Enabled Flag, Port No. 3
Communications Port Enabled Flag, Port No. 2
Communications Port Enabled Flag, Port No. 1
Communications Port Enabled Flag, Port No. 0
A Communications Port Error Flag will turn ON in the following cases.
• When an error is generated during execution of SEND(090), RECV(098), or CMND(490).
• When an error response or retry error has been generated for the port.
These Flags will turn OFF when the corresponding Communications Port
Enabled Flag is turned OFF at the start of operation or at the start of executing the SEND(090), RECV(098), or CMND(490).
Word
A219
02
01
00
06
05
04
03
Bit
08 to 15
07
Content
Reserved
Communications Port Error Flag, Port No. 7
Communications Port Error Flag, Port No. 6
Communications Port Error Flag, Port No. 5
Communications Port Error Flag, Port No. 4
Communications Port Error Flag, Port No. 3
Communications Port Error Flag, Port No. 2
Communications Port Error Flag, Port No. 1
Communications Port Error Flag, Port No. 0
The Communications Port Completion Code words will contain the FINS end code after SEND(090), RECV(098), or CMND(490) has been executed.
If the Communications Port Enabled Flag turns OFF when operation is started or SEND(090), RECV(098), or CMND(490) are executed, the contents of these words will be cleared.
Word
A203
A204
A205
A206
A207
A208
A209
A210
A211 to A218
Content
Communications Port Completion Code, Port No. 0
Communications Port Completion Code, Port No. 1
Communications Port Completion Code, Port No. 2
Communications Port Completion Code, Port No. 3
Communications Port Completion Code, Port No. 4
Communications Port Completion Code, Port No. 5
Communications Port Completion Code, Port No. 6
Communications Port Completion Code, Port No. 7
Reserved
292
Communications Timing
Flag Transitions
Communications Port
Enabled Flag
Network communications instructions
(PMCR(260)/SEND(090)/
RECV(098)/CMND(490))
Communications Port
Error Flag
Communications Port
Completion Code
Instruction 1 being executed
(Normal end)
End of previous processing
Instruction 2 being executed
Instruction 3 being executed
(No unit corresponding to unit address)
(Normal end)
Section 9-4
9-4-4 Timing of Commands Addressed to a Host Computer
Commands addressed to a host computer are sent at the timing shown in the following diagrams.
Host Computer Sending Data
Response Required
Host computer Command
(1)
Command
Response
(2)
Response
Serial Communications
Board/Unit
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
(1)
Communications Port Enabled Flag
Command
(2)
Response
Command acknowledged Command completed
Command transmission to the host computer can start even when the port is receiving a command from the host computer (1). The transmission of a response to the command from the host computer is postponed until the transmission of the command to the host computer is completed (2).
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
293
Communications Timing
Section 9-4
Host Computer Receiving Data
Response Required
Host computer
Serial Communications
Board/Unit
Command
Communications Port Enabled Flag
(1)
Response
(2)
Command
Response
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
Communications Port Enabled Flag
(1)
Response
(2)
Command
Command acknowledged Command completed
At (1) in the diagram, the response to a command sent from the host computer is being transmitted from the port. In this case, the command transmission to the host computer is postponed until the response transmission is completed (2).
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
Response Wait Time After Host Computer Sends Data
Response Required
Host computer
Serial Communications
Board/Unit
Command
(1)
Command
Response
Response
Response wait time
(2)
Communications Port Enabled Flag
Command acknowledged
Command completed
No Response Required
Host computer
Serial Communications
Board/Unit
Command
(1)
Command
Response
Response wait time
(2)
Communications Port Enabled Flag
Command acknowledged Command completed
When response wait time has been set in the command format from the host computer, commands to the host computer will not be transmitted until the response time has elapsed (1). Transmission of responses to commands from the host computer will be postponed until the command transmission to the host computer has been completed (2).
294
Changes from Previous Products
Section 9-5
When a response is not required from the host computer, the Communications Port Enabled Flag will turn ON when the command to the host computer has passed from the CPU Unit to the port.
9-4-5 Reception Buffers
In Modbus-RTU Slave mode, each port has a reception buffer of 1,200 bytes.
This is sufficient to hold the maximum Modbus-RTU Slave frame length for an
FA command response frame (1,115 bytes) + 85 bytes. If a frame larger than
1,200 bytes is sent from the host computer (from @ to the carriage return), the frame will be discarded and no response will be returned.
9-4-6 Error Responses
When Modbus-RTU Slave FA commands are used for FINS commands, an error code will returned as the end code in the FINS response whenever there is a mistake in the FINS command settings or an FINS response is required that is too long for the legal response frame.
An end code of 110B Hex is returned when the response exceeds the maximum response length. The Modbus-RTU Slave response frame will contain the requested read data after the end code through the end of the maximum legal response frame length.
Note We recommend programming retry processing at any device sending commands in case noise or other factors result in transmission errors.
9-5 Changes from Previous Products
There are differences between Modbus-RTU Slave Systems created using the CS/CJ-series Serial Communications Boards and Unit in comparison to
Modbus-RTU Slave Systems created with Modbus-RTU Slave Units and CPU
Units in other PLC product series. These differences are described in this sections.
9-5-1 RS-232C Ports
Take the following differences into consideration when changing from an existing Modbus-RTU Slave System to one using an RS-232C port on a CS/CJseries CPU Unit, Serial Communications Boards, or Serial Communications
295
Changes from Previous Products
Section 9-5
Previous products
C-series Modbus-RTU Slave
Units
Model number
3G2A5-LK201-E
C500-LK203
3G2A6-LK201-E
C-series CPU
Units
CVM1 or CVseries CPU
Units
C200H-LK201
SRM1
CPM1
CPM1A
CQM1-CPU
@@-E
C200HS-CPU
@@-E
C200HX/HG/HE-
CPU
@@-E
C200HW-COM
@@-E
CVM1/CV-CPU
@@
Unit (CS1H/G-CPU
@@ RS-232C port, CS1W-SCU21-V1 ports, CJ1W-
SCU21/41 port 2, CS1W-SCB21-V1 ports, or CS1W-SCB41-V1 port 1).
Changes required for CS/CJ-series product
Wiring Other
The connector has been changed from a 25-pin to a
9-pin connector.
The CS/CJ-series products do not support the ST1, ST2, and RT signals and wiring them is not required.
The following changes are necessary for systems that sync with ST1, ST2, and RT.
Synchronized transfers will no longer be possible.
Full-duplex transmissions will be possible with the CS/CJ-series product, but the host computer’s communications program, hardware, or both will need to be altered.
The following changes are necessary for systems that did not sync with ST1, ST2, and RT.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
The connector has been changed from a 25-pin to a
9-pin connector.
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/CJ command specifications.
CVM1 or CVseries Modbus-
RTU Slave Unit
CV500-LK201
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/CJ command specifications.
Port 1:
The connector has been changed from a 25-pin to a
9-pin connector.
Port 2 set for RS-232C:
The SG signal has been changed from pin 7 to pin 9.
The following changes are necessary for half-duplex transmissions that use CD.
Check the system for timing problems when using SEND, RECV, or CMND to initiate communications from the PLC or timing problems in sending commands from the host computer. If necessary, switch to full-duplex transmissions.
The following changes are necessary for full-duplex transmissions that do not use
CD.
Half-duplex It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different
CS/CJ command specifications.
296
Changes from Previous Products
Section 9-5
Note The number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for C-series Modbus-RTU
Slave Units and CS/CJ-series Serial Communications Boards/Units. A host computer program previously used for C-series Modbus-RTU Slave Units may not function correctly if used for CS/CJ-series PLCs. Check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS/CJ-series Communications Commands
Reference Manual (W342) for details.
9-5-2 RS-422A/485 Ports
Take the following differences into consideration when changing from an existing Modbus-RTU Slave System to one using an RS-422A/485 port on a CS/
CJ-series Serial Communications Board (CS1W-SCB41-V1 port 2 or CJ1W-
SCU41 port 1).
Previous products
C-series Modbus-
RTU Slave Units
C200HX/HG/HE
Communications
Board
CVM1 or CVseries CPU Units
CVM1 or CVseries Modbus-
RTU Slave Unit
Model number Changes required for CS/CJ-series product
Wiring Other
3G2A5-LK201-E Wiring pins have been changed as shown below.
C200H-LK202
3G2A6-LK202-E
SDA: Pin 9 to pin 1
SDB: Pin 5 to pin 2
RDA: Pin 6 to pin 6
RDB: Pin 1 to pin 8
SG: Pin 3 to
Not connected
FG: Pin 7 to pin
Connector hood
C200HW-COM
@@-E
No changes have been made in wiring.
CVM1/CV-CPU
CV500-LK201
@@
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different text lengths in frames or different CS/CJ command specifications. (See note.)
No changes have been made in wiring.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/
CJ command specifications.
It may be possible to use the host computer programs without alteration as long as the same communications settings (e.g., baud rate) are used. It may be necessary, however, to change programs to allow for different CS/
CJ command specifications.
Note For pre-Ver. 1.2 Units, the number of words that can be read and written per frame (i.e., the text lengths) when using C-mode commands is different for Cseries Modbus-RTU Slave Units and CS/CJ-series Serial Communications
Boards/Units. A host computer program previously used for C-series Modbus-
RTU Slave Units may not function correctly if it is used in CS/CJ-series PLCs.
When using Serial Communications Boards/Units with Unit Ver. 1.2 or later, these programs can be reused by setting the Modbus-RTU Slave compatible device mode to mode C (C500/120) or mode D (D200H). (Alternatively, check the host computer program before using it and make any corrections required to handle different frame text lengths. Refer to the CS/CJ-series Communica-
tions Commands Reference Manual (W342) for details.)
297
Modbus-RTU Slave Function for Replacing Existing PLCs
Section 9-6
9-6 Modbus-RTU Slave Function for Replacing Existing PLCs
An enhanced Modbus-RTU Slave function is provided to enable reuse of host computer programs created for the existing PLC. By selecting the 1:N/1:1
Modbus-RTU Slave protocol and the Modbus-RTU Slave compatible device mode according to the existing PLC model, the Board/Unit’s Modbus-RTU
Slave functions can be fully compatible with the Modbus-RTU Slave of the existing PLC.
9-6-1 Support for 1:1 Modbus-RTU Slave
Pre-Ver. 1.2 Units
The C200H-LK101/201/202, C500-LK101/201/103/203, and C120-LK101/
201/202 Modbus-RTU Slave Units for earlier C-series PLCs (C200H and
C500) enable selection of either 1:1 or 1:N Modbus-RTU Slaves. The CS/CJseries and later PLCs, however, only support 1:N Modbus-RTU Slaves.
Therefore, the host computer programs created using 1:1 Modbus-RTU Slave protocol cannot be reused in CS/CJ-series PLCs.
Unit Ver. 1.2 or Later
1:N/1:1 setting
1:N protocol
1:1 protocol
Host computer programs for 1:1 Modbus-RTU Slaves that have been created using a C200H/C1000H/C2000H PLC can also be used with CS/CJ-series
PLCs by selecting the 1:1 Modbus-RTU Slave protocol. The 1:N/1:1 Modbus-
RTU Slave setting in the Setup Area in the DM Area enable selection of 1:1
Modbus-RTU Slaves.
Details
A Modbus-RTU Slave protocol that enables a single host to be connected to a single PLC
(1:1) or to multiple PLCs
(1:N).
In previous Boards/Units, only the 1:N protocol was supported.
Supported PLCs
C Series
Built-in port:
SRM1, CPM1, CPM1A,
CQM1-CPU
@@
, C200HS-
CPU
@@
, C200HE/HG/HX-
CPU
@@
, C200HW-COM
@@
CS/CJ Series
Built-in port:
CS1G/H-CPU
@@
H, CS1G/H-
CPU
@@
-V1, CS1D-
CPU
@@
H, CJ1G/H-
CPU
@@
H, CJ1G/M-CPU
@@
Earlier models (pre-Ver. 1.2):
CS1W-SCB21(-V1)/41(-V1),
CS1W-SCU21(-V1), CJ1W-
SCU21/41
CVM1/CV Series
CVM1/CV-CPU
@@
CVM1
(built-in port), CV500-LK201
A Modbus-RTU Slave protocol that enables a single host to be connected to a single PLC only.
C Series
C500-LK101/201/103/203,
C120-LK101/201/202
C Series
C200H-LK101/201/202
C Series
C500-LK101/201/103/203,
C120-LK101/201/202
C Series
C200H-LK101/201/202
Remarks
The CS/CJ Series, C200HS/
HX/HG/HE(-Z), CPM
@
, and
CQM1
@
Series all support only 1:N Modbus-RTU Slaves for the CPU Unit’s built-in port and Modbus-RTU Slave Unit/
Serial Communications
Board.
The earlier Serial Communications Units/Boards support only 1:N Modbus-RTU Slaves.
The CVM1/CV Series supports only 1:N Modbus-RTU
Slaves for the CPU Unit’s built-in port and Modbus-RTU
Slave Unit/Serial Communications Unit/Board.
The C-series Modbus-RTU
Slave Units shown here support both 1:1 protocol and 1:N protocol.
298
Modbus-RTU Slave Function for Replacing Existing PLCs
Section 9-6
Note The differences between the command and response frames for 1:N Modbus-
RTU Slaves and 1:1 Modbus-RTU Slaves is as follows:
1:N Modbus-RTU Slave
:
1
2
DM Area set allocate the a model excep
• Response Format
@ 0 0 R D 0 0
Host Link
Unit No.
Header code
End code
× × * CR
FCS
Terminator
1:1 Modbus-RTU Slave
The frame format for a 1:1 Modbus-RTU Slave is the same as that for the 1:N
Modbus-RTU Slave, except the @, Modbus-RTU Slave Unit No., and FCS are omitted.
• Command Format
R D
Header code
* CR
Terminator
• Response Format
R D 0 0
Header code
End code
* CR
Terminator
9-6-2 Modbus-RTU Slave-compatible Device Selection
Pre-Ver. 1.2 Units
In earlier models, when the host computer program used by the C-series
Modbus-RTU Slave Unit was reused in a CS/CJ-series PLC, data could not be read normally for some programs due to the differences in Modbus-RTU
Slave specifications.
Unit Ver. 1.2 or Later
RR
RL
RH
RC
RD
RJ
RG
When Serial Communications Units/Boards with Unit Ver. 1.2 or later are used, however, the Board/Unit’s Modbus-RTU Slave specifications can be switched according to the CPU Unit or other Unit in which the host computer program is to be reused.
The Modbus-RTU Slave specifications change according to the Modbus-RTU
Slave compatible device mode that is selected.
• When the following commands for reading I/O memory (RR, RL, RH, RC,
RD, RJ, and RG) are received, the number of data words in each response frame that is returned to the host is different.
Command Name
CIO AREA READ
LINK AREA READ
HR AREA READ
PV READ
DM AREA READ
AR AREA READ
T/C STATUS READ
299
Modbus-RTU Slave Function for Replacing Existing PLCs
Section 9-6
• When the command for reading the status of the CPU Unit (MS) is received, the response format that is returned to the host according to the
FAL/FALS instruction execution status is different.
MS
Command Name
PROCESSOR STATUS READ
Modbus-RTU Slave Compatible Device Modes
Modbus-
RTU Slavecompatible device mode
Mode A (CS/
CJ/C)
Mode B
(CVM1/CV)
Mode C
(C200H)
Mode D
(C500/120)
Compatible models (models that supported host computer programs)
C Series
SRM1 (built-in port)
CPM1 (built-in port)
CPM1A (built-in port)
CQM1-CPU
@@
(built-in port)
C200HS-CPU
@@
(built-in port)
C200HE/HG/HX-CPU
@@
(built-in port)
C200HW-COM
@@
(built-in port)
CS/CJ Series
CS1G/H-CPU
@@
H (built-in port)
CS1G/H-CPU
@@
-V1 (built-in port)
CS1D-CPU
@@
H (built-in port)
CJ1G/H-CPU
@@
H (built-in port)
CJ1G/M-CPU
@@
(built-in port)
Earlier models (pre-Ver. 1.2):
CS1W-SCB21(-V1)/41(-V1)
CS1W-SCU21(-V1)
CJ1W-SCU21/41
CVM1/CV Series
CVM1/CV-CPU
@@
CVM1 (built-in port), CV500-LK201
C Series (C200H)
C200H-LK101/201/202
C Series (C500/120)
C500-LK101/201/103/203, C120-
LK101/201/202
RR, RL, RH, RC, RD, and RJ commands
RG command
Number of words in each response frame
MS command
(See note.)
Response data format
First frame Second frame
First frame Second frame
30 words 31 words 121 words 125 words Variable length
89 words 60 words
Fixed length
29 words 30 words 89 words 89 words Variable length
Note
1.
The response data formats for MS commands when FAL/FALS is not executed are as follows:
Types for which a space (20 hex) is added to the FAL/FALS message in the response data (indicated as fixed length in the above table).
Types for which a FAL/FALS message is not added to the response data
(indicated as variable length in the above table).
(A FAL/FALS message is added to the response data for both types if FAL/
FALS is executed.)
2.
The following condition is an exception:
When reusing the RG command created using a CVM1/CV-series PLC with mode B selected, the host computer program cannot be reused without being changed. The difference in the response returned when the RG command is reused and the Timer/Counter Flag for 121 words (maximum text area) is read is as follows:
300
Modbus-RTU Slave Function for Replacing Existing PLCs
Section 9-6
Using mode B with a CS/CJ-series
Serial Communications Unit/Board with unit version 1.2 or later
CVM1/CV-series Host Link Unit
First frame
121 words (including terminator)
First frame
121 words
Second frame
0 words (terminator only)
Relationship with 1:N/1:1 Protocol Settings
The 1:N/1:1 Modbus-RTU Slave protocol setting depends on the compatible device mode, as follows:
• Mode A (CS/CJ/C), mode B (CVM1/CV): 1:N Modbus-RTU Slaves only
• Mode C (C200H), mode D (C500/120): Either 1:N or 1:1 Modbus-RTU
Slaves
Allocated DM Area Settings (Setup Area)
m = D30000 + 100
× unit number
Port 1
D32003
Board
Port 2
D32013
Words
Port 1
m+3
Unit
Port 2
m+13 14
Bit Setting contents
D32003 D32013 m+3 m+13 08 to 10
1:N/1:1 protocol setting (Unit Ver. 1.2 or later only)
1: 1:1 protocol; 0: 1:N protocol
If the Modbus-RTU Slave compatible device mode is set between 0 and 2 hex (mode A or B), the setting in this bit is invalid (always 1:N Modbus-RTU Slaves)
Modbus-RTU Slave compatible device mode
0 hex: Default (mode A)
1 hex: Mode A (CS/CJ/C)
2 hex: Mode B (CVM1/CV)
3 hex: Mode C (C200H)
4 hex: Mode D (C500/120)
Setting Examples when Replacing PLCs
A host computer program that has been created using a C500-LK101/201/
103/203 Modbus-RTU Slave Unit can be reused in a Serial Communications
Board/Unit with Unit Ver. 1.2 or later by making the following settings to enable the 1:1 Modbus-RTU Slave protocol.
• 1:N/1:1 Modbus-RTU Slave protocol setting: 1 (ON = 1:1 Modbus-RTU
Slave)
• Modbus-RTU Slave compatible device mode setting: 3 hex (mode C
(C500/120))
301
Modbus-RTU Slave Function for Replacing Existing PLCs
Section 9-6
302
SECTION 10
Loopback Test
This section describes the procedure and other information required to conduct loopback test to check the serial ports.
10-1-2 Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-1-4 Indicators Used for the Loopback Test . . . . . . . . . . . . . . . . . . . . . . .
303
Executing Loopback Tests
Section 10-1
10-1 Executing Loopback Tests
10-1-1 Overview
Executing a loopback test will allow you to test a port communications circuit by connecting a loopback-wire connector to the port of a Serial Communications Board or Unit, looping back the transmitted data to make it the received data for the Unit or Board, and then comparing and checking the data.
Serial Communications Unit
(CS/CJ Series)
Loopback test switch
Loopback test
10-1-2 Connection Method
Make the connections according to the type of port, as shown in the following diagrams.
RS-232C Port
Pin
2
3
4
5
1
8
7
Signal
SD
RD
RTS
CTS
FG
DTR
DSR
RS-422A/485 Port
Pin
1
2
6
8
Signal
SDA
SDB
RDA
RDB
10-1-3 Procedure
1,2,3...
The loopback test is performed using the procedure shown below.
1.
Connect the connector of the port to be used to execute the loopback test.
See 10-1-2 Connection Method for details.
2.
Set the serial communications mode in the Setup Area to Loopback Test
(F Hex). Refer to 10-2 Setup Area Allocations.
3.
Set the following communications settings for the loopback test in the Set-
up Area: Baud rate, stop bits, parity, and data length. Refer to 10-2 Setup
Area Allocations.
4.
Cycle the power, restart the Unit or Board, or restart the port.
Use the following bits to restart the Board or Unit.
Board:
Units:
A60800
A501, bits 00 to 15 (bits correspond to unit numbers 0 to F)
Use the following bits to restart the port.
Board: A636, bit 01 for port 1 and bit 02 for port 2
Units: A620 + unit number, bit 01 for port 1 and bit 02 for port 2
304
Setup Area Allocations
Section 10-2
5.
Turn ON the Loopback Test Switch. To end the test, turn OFF the switch.
The Loopback Test Switches are as follows:
Board: CIO 1900, bit 06 for port 1 and bit 14 for port 2
Unit:
Unit No.) n, bit 06 for port 1 and bit 14 for port 2 (n = CIO 1500 + 25 x
Refer to 10-3 CIO Area Allocations.
6.
Use the protocol status to check the results.
Refer to 10-3 CIO Area Allocations.
10-1-4 Indicators Used for the Loopback Test
When the test is being executed, the indicators shown below will flash. Use the protocol status to check whether or not the test has been executed normally.
Serial Communications
Boards (CS Series Only)
Serial Communications
Units (CS/CJ Series)
Port 1: COMM1 indicator
Port 2: COMM2 indicator
Port 1: SD1/RD1 indicator
Port 2: SD2/RD2 indicator
10-2 Setup Area Allocations
This section describes the Setup Area allocated to the Serial Communications
Board and Serial Communications Units in the DM Area when loopback tests are performed.
The loopback test is performed using the Host Link mode protocol. The Setup is basically the same as for the Host Link mode.
m = D30000 + 100
× unit number
DM Area
Board
(CS Series only)
Unit
(CS/CJ Series)
Port 1 Port 2
D32000 D32010 m
Port 1 Port 2
m + 10 15
Bit Settings
Port settings 0: Defaults, 1: User settings
14 to 12 Reserved
11 to 08 Serial communications mode: Always F Hex (Loopback test)
07 to 05 Reserved
04 Start bits
0: 1 bit; 1: 1 bit (1 start bit is always used regardless of this setting)
D32001 D32011 m + 1
03
02
01
00
Data length
Start bits
Parity
Parity
0: 7 bits, 1: 8 bits
0: 2 bits, 1: 1 bit
0: Yes, 1: No
0: Even, 1: Odd m + 11 15 to 04 Reserved
03 to 00 Baud rate (bps)
0 hex: Default (9,600); 3 hex: 1,200; 4 hex: 2,400; 5 hex: 4,800;
6 hex: 9,600; 7 hex: 19,200; 8 hex: 38,400; 9 hex: 57,600;
A hex: 115,200
Serial Communications
Mode
Set the serial communications mode to F Hex to perform a loopback test.
For the other settings, refer to 4-2 Setup Area Allocations.
305
CIO Area Allocations
Section 10-3
10-3 CIO Area Allocations
The loopback test execution results can be read form the protocol status area allocated in the CIO Area.
Protocol Status
The information shown in the following table is input to the CPU Unit in the protocol status area. If an error occurs, the flags will be turned ON n = 1500 + 25
× unit number
Bit Contents
Board
(CS-series only)
Port 1 Port 2
Word
CIO
1909
CIO
1919
Port 1
n + 9
Unit
(CS/CJ-series)
Port 2
n + 19 n + 10 n + 20
15
14 to 09
08
07
06
Test status
Error
Reserved
DTR check error
CTS check error
Reserved
05
04
03
02
Timeout error
Parity error
Overrun error
Framing error
01
00
Reserved
Conveyor error
15 to 00 Test execution count CIO
1910
CIO
1911
CIO
1912 to
CIO
1914
CIO
1920
CIO
1921
CIO
1922 to
CIO
1924 n + 11 n + 21 15 to 00 Test error count n + 12 to n + 14 n + 22 to n + 24
15 to 00 Reserved
The test execution count and test error count are cleared at startup. If the number of tests or the number of test errors is counted to FFFF (hex), the value of the count will remain at FFFF, but testing will continue.
306
SECTION 11
Troubleshooting and Maintenance
This section describes the troubleshooting and maintenance procedures for the Serial Communications Boards and the
Serial Communications Unit.
11-1-1 Serial Communications Boards (CS Series Only) . . . . . . . . . . . . . .
11-1-2 Serial Communications Units (CS/CJ Series) . . . . . . . . . . . . . . . . .
11-3-1 Host Link Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-2 Serial Gateway (Serial Gateway or Protocol Macro Mode) . . . . . . .
11-3-3 No-protocol Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-3-4 1:N NT Link Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-2 Error Log Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-3 Error Log Table Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-4 Error Codes and Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-5 Error Codes and Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-6 Reading and Clearing Error Log Tables . . . . . . . . . . . . . . . . . . . . . .
11-4-7 CONTROLLER DATA READ: 05 01 . . . . . . . . . . . . . . . . . . . . . . .
11-4-8 ERROR LOG READ: 21 02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-4-9 ERROR LOG CLEAR: 21 023. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11-6-1 Precautions when Replacing Board or Unit . . . . . . . . . . . . . . . . . . .
11-6-2 Settings after Replacing Board or Unit. . . . . . . . . . . . . . . . . . . . . . .
11-6-3 Replacing the Board or Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
307
Indicator Error Displays
Section 11-1
11-1 Indicator Error Displays
11-1-1 Serial Communications Boards (CS Series Only)
Possible cause
Lit
Not lit
RDY
Indicators
ERR/ALM
CPU Unit
Not lit
Lit
Not lit
Not lit
Lit
Lit
Flashing
Flashing
Not lit
Lit
Flashing
Not lit
Remedy
The Board has started normally.
The Board is faulty (hardware self-diagnostic function).
A bus error has occurred.
An initialization recognition error has occurred (the Board is not correctly recognized by the CPU Unit).
An initialization recognition error has occurred (the Serial Communications Unit was not recognized by the CPU Unit).
---
If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board.
Firmly secure the Board to the CPU Unit.
If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board.
If the ERR and ALM indicators light when the Board is mounted to another CPU Unit, replace the Board.
The CPU Unit is not receiving normal power supply.
Check the power supply voltage and supply the correct electric power to the Unit.
Firmly secure the Board.
The Board is not correctly secured to the
CPU Unit.
The Board is faulty.
If all the indicators are not lit when the
Board is mounted to another CPU Unit, replace the Board.
Eliminate the cause of the error. If the error persists, replace the CPU Unit.
An error (such as a CPU Unit WDT error) has occurred in the CPU Unit.
The Board is faulty.
A bus error has occurred.
The communications circuit is faulty.
A protocol data syntax error has occurred.
A system setting error has occurred.
The routing tables are not set correctly.
An error has occurred in the CPU Unit.
The error log EEPROM is faulty.
A Protocol Data File (BACKUP being read (restored) from the CPU Unit’s
Memory Card to the Board.
@@
.PRM) is
If all the indicators are not lit when the
Serial Communications Unit is mounted to another CPU Unit, replace the Unit.
Check the operating environment and eliminate the cause of the error.
Firmly secure the Board.
Refer to A42400 and A42401.
Conduct a loopback test. If an error occurs, replace the Board.
Correct the protocol data and transfer it to the Board.
Try executing a normal sequence for the serial port where the error is occurring or switch the CPU Unit to PROGRAM mode and remove the cause of the error.
Correct the Setup Area settings, and cycle the power, restart the Board, restart the port, or execute STUP(237).
When the routing tables are used, set them correctly. When the routing tables are not used, delete the Board settings from the table.
Eliminate the cause of the error. If the error persists, replace the CPU Unit.
Cycle the power supply. If the error persists, replace the CPU Unit.
---
308
Indicator Error Displays
Section 11-1
Lit
RDY
Indicators
ERR/ALM
CPU Unit
Not lit
Possible cause Remedy
Flashing
Flashing
Flashing
Flashing
Serial Communications
Board Error Information
(A424)
A Protocol Data File (BACKUP
@@
.PRM) was read (restored) from the CPU Unit’s
Memory Card to the Board properly.
A protocol data write error has occurred or protocol data has been destroyed.
There is no protocol data.
The Protocol Data File (BACKUP
@@
.PRM) restore operation failed when restoring protocol data from the CPU Unit’s Memory
Card to the Board.
The Protocol Data Error Flag (bit A42409 in
CPU Unit’s Auxiliary Area) will be turned
ON if the restore operation fails.
---
If the indicator status remains the same when the protocol data is retransmitted, replace the Board.
Transfer protocol data to the Board.
Write (backup) the protocol data from the
Board to the Memory Card again and then execute the restore operation again.
If the restore operation fails two times in succession, use CX-Protocol to transfer the protocol data to the Board.
For Serial Communications Boards, refer to the following Auxiliary Area word
(A424) as well as the indicator displays shown on the previous page. When an error occurs, the corresponding flag is turned ON.
00
Bit
Fatal error
01
04
05
07
08
09
10
11
Non- fatal error
Flag
Inner Board
WDT error
Inner Bus error
Protocol data error
Protocol macro execution error
A protocol data checksum error has occurred.
A syntax error has occurred during protocol macro execution.
Possible cause
The Board is faulty.
Inner Board service failure
Cyclic monitoring error
Routing table error
System setting error
The TXD(236)/RXD(235) instruction was sent using noprotocol mode to a Board that does not support no-protocol communications (pre-Ver.1.2).
The Inner Bus access right cannot be retained for more than the specified time.
The routing tables are not set correctly.
A system setting error has occurred.
Error Log data error
A bus error has occurred.
The service life of the
EEPROM has expired.
Remedy
Firmly secure the Board to the CPU Unit. If the error persists when the Board is mounted to another CPU Unit, replace the Board.
Firmly secure the Board to the CPU Unit. If the error persists when the Board is mounted to another CPU Unit, replace the Board.
Install a Board with Unit Ver. 1.2 or later and then execute the TXD(236)/RXD(235) instruction.
CPU Unit and system load is too high. Review the application.
Correct the routing tables and retransfer them.
Correct the Setup Area settings, cycle the power supply, restart the Board, or restart the port, or execute STUP(237).
If the error persists when protocol data is retransmitted, replace the Board.
Correct the protocol data and retransfer it.
Try executing a correct sequence for the serial port where the error is occurring or switch the
CPU Unit to PROGRAM mode and remove the cause of the error.
If this error persists even if the power supply is cycled, replace the Board.
When a fatal error occurs, the ERR and ALM indicators on the CPU Unit will light. When a non-fatal error occurs, the ERR and ALM indicators on the CPU
Unit will flash. Refer to the indicator error displays.
Note The ERR/ALM indicator will continue to flash even after the cause of a nonfatal error has been removed for the Serial Communications Board. The indicator can be stopped by clearing the error from a Programming Console or
309
Indicator Error Displays
Section 11-1
other Programming Device for errors for bits 05, 07, 08, 09, and 10. Press the
FUN Key and then the MONITOR Key from the Programming Console. Refer to the CX-Programmer Operation Manual for the CX-Programmer procedure.
11-1-2 Serial Communications Units (CS/CJ Series)
Indicators
RUN ERC ERH RDY
Lit Not lit Not lit Lit
Lit
Lit
Lit
Not lit
---
Lit
---
Not lit
Flashing
---
Lit
Not lit
---
---
---
Flashing occurred.
Possible cause
A system setting error has occurred.
The error log EEPROM is faulty.
The routing tables are not set correctly.
An error (such as a CPU Unit WDT error) has occurred in the CPU Unit.
A CPU Unit service monitoring error has
A bus error has occurred.
A Protocol Data File (BACKUP
@@
.PRM) is being read (restored) from the CPU Unit’s
Memory Card to the Serial Communications
Unit.
Remedy
Not lit
Not lit
Not lit
Not lit
Lit
Not lit
Lit
Not lit
---
Lit
Lit
Not lit
---
---
---
Not lit
The Serial Communications Unit has started normally.
The Serial Communications Unit is found to be faulty (by the hardware self-diagnostic function).
There is more than one identical unit number within the same CPU Unit.
An initial recognition error has occurred (the
Serial Communications Unit was not correctly recognized by the CPU Unit).
An initial recognition error has occurred (the
Serial Communications Unit was not correctly recognized by the CPU Unit).
The CPU Unit is not receiving normal power supply.
The Serial Communications Unit is not correctly secured to the Backplane (CS-series only) or not correctly secured to the next Unit
(CJ-series only).
The Serial Communications Unit is not mounted in an appropriate slot.
The Serial Communications Unit is faulty.
---
If the ERC indicator lights up when the
Serial Communications Unit is mounted to another CPU Unit, replace the Unit.
Assign a unique unit number to each
Serial Communications Unit on the CPU
Rack and Expansion Racks.
If the ERH indicator lights up when the
Serial Communications Unit is mounted to another CPU Unit, replace the Unit.
If the ERC and ERH indicators light when the Serial Communications Unit is mounted to another CPU Unit, replace the Unit.
Check the power supply voltage and supply the correct electric power to the
Unit.
Firmly secure the Unit.
Mount the Unit in an appropriate slot.
If all the indicators are not lit when the
Serial Communications Unit is mounted to another CPU Unit, replace the Unit.
Correct the Setup Area settings, cycle the power supply, restart the Unit/Board, or restart the port, or execute
STUP(237).
If the problem persists even if the power supply is cycled, replace the Unit.
When the routing tables are used, set them correctly. When the routing tables are not used, delete the Unit settings from the table.
Eliminate the cause of the error. If the error persists, replace the CPU Unit.
Check the operating environment and eliminate the cause of the error. (Check to be sure that the problem is not caused by another CPU Bus Unit having the same unit number.)
Check the operating environment and eliminate the cause of the error.
Firmly secure the Unit.
---
310
Status Area Error Indications
Section 11-2
Indicators
RUN ERC ERH RDY
Lit Not lit Not lit Lit
Lit
Lit
Lit
Flashing
---
Flashing
---
Lit ---
Flashing
Lit
Flashing
Possible cause Remedy
A Protocol Data File (BACKUP
@@
.PRM) was read (restored) from the CPU Unit’s Memory
Card to the Serial Communications Unit properly.
A protocol data write error has occurred or protocol data has been destroyed.
---
There is no protocol data.
A protocol data syntax error has occurred.
• The flash memory for protocol data is faulty.
• The Protocol Data File (BACKUP
@@
.PRM) restore operation failed when restoring protocol data from the CPU Unit’s Memory
Card to the Serial Communications Unit.
If the indicator status remains the same when the protocol data is retransmitted, replace the Unit.
Transfer protocol data to the Unit.
Correct the protocol data and transfer it to the Unit.
The ERC indicator can also be turned
OFF by executing a normal sequence for the serial port for which the error is occurring or by switching the CPU Unit to
PROGRAM mode temporarily.
• Transfer the protocol data to the Unit.
If the problem persists after correct protocol data is transferred, replace the Unit.
• Write (backup) the protocol data from the Unit to the Memory Card again and then execute the restore operation again.
• If the restore operation fails two times in succession, use CX-Protocol to transfer the protocol data to the Serial
Communications Unit.
11-2 Status Area Error Indications
This section describes status area error information.
Status Area Error
Information
When an error occurs, the corresponding flag is turned ON.
n = CIO 1500 + 25
× unit number
Flag name Possible cause Remedy
CIO 1901
Word
Boards
(CS Series only)
n + 1
Units
(CS/CJ Series)
01
Bit
Error Log data error
CIO
1906
CIO
1907
CIO
1916
CIO
1917
00 n + 6 n + 16 01 n + 7 n + 17 10
08
Protocol data error
System Setup error
Remote node receive busy
Local node receive busy
The error log
EEPROM is faulty.
A protocol data checksum error has occurred.
A System Setup error has occurred.
The remote node is in reception buffer busy status when flow control is set for the protocol.
The local node is in reception buffer busy status.
If the problem persists even if the power supply is cycled, replace the Board/Unit.
If the error persists when protocol data is retransmitted, replace the
Board or Unit.
Correct the Setup Area settings, cycle the power supply, restart the Unit/Board, or restart the port, or execute the STUP(237) instruction.
Cancel the communications with the remote node until this flag is turned OFF.
Increase the transmission interval to reduce transmission load to the remote node for which flow control is set.
311
Troubleshooting
Section 11-3
11-3 Troubleshooting
This section describes how to resolve transmission and reception problems.
“m” and “n” in the tables represent the following word addresses for the
Board and Unit.
m n
Symbol Boards
(CS Series only)
D32000
CIO 1900
Units
(CS/CJ Series)
D30000 + 100 x unit number
CIO 1500 + 25 x unit number
11-3-1 Host Link Communications
Serial communications mode
Serial communications mode is not set to
Host Link.
---
Indicator status
Status information, etc.
---
CIO Area
Bits 12 to 15 (Serial
Communications
Mode) of CIO Area words n + 5/n + 15 are set to a value other than 5 Hex.
Cause
Serial communications mode is not set correctly.
Remedy
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10 to 0 or 5 Hex (Host Link).
312
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to Host
Link.
Indicator status
The SD not flash at all.
(Communications have not been electrically established.)
@/RD@ and COM
@ indicators do
The RD
@ and
COM
@ indicators are flashing, but the response has not been returned from the host.
For the Unit, the
SD
@ indicator does not flash at all (Communications have been electrically established.)
Status information, etc.
-----
There is no transmission error.
CIO Area Cause Remedy
CIO Area words n +
8/n + 18 (transmission error status) are set to 0000 Hex.
CIO Area words n +
5/n + 15 (port settings in the System
Setup) do not correspond to the settings of the remote device.
---
The System Setup in DM Area words m
+ 2 and m + 3/m +
12 and m + 13 of the Board or Unit
(Host Link Unit No.,
Host Link send delay time, etc.) does not correspond to the settings for the remote device.
The command format and data length of the data sent from the host are incorrect.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or set.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or set.
Commands are not being set from the host.
This is a hardware error.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4wire method.
Reset the serial port at the host, and rewrite the program.
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10 to F Hex (Loopback Test
Serial Communications
Mode). Then, connect the connector wire for a loopback test and conduct a loopback test by turning
ON bit 14 (Loopback Test
Switch) of CIO Area word n. The test data is reflected in CIO Area words n+9/n+19. If an error occurs during the test, replace the Board or
Unit.
Reset the settings in DM
Area words m + 2 and m +
3/m + 12 and m + 13 of the
Board or Unit (Host Link
Unit No., Host Link send delay time, etc.) so that they correspond to the settings at the host device.
Correct the command frame (header, Host Link
Unit No., terminator, etc.) and the program.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4wire method.
313
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to Host
Link.
Indicator status
Status information, etc.
The RD
@ and
COM
@ indicators are flashing, but the response has not been returned from the host.
For the Unit, the
SD
@ indicator does not flash at all. (Communications have been electrically established.)
There is no transmission error.
---
There is a transmission error.
CIO Area
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 04
(overrun error), bit
03 (framing error), or bit 02 (parity error) is turned ON.
Cause
CTS control is ON and bit 04 of CIO
Area words n + 7/n
+ 17 (CTS signal) is
OFF.
The CTS control is set, but the RTS signal from the remote
Unit has not entered in the CTS signal of the local Unit.
Remedy
This is a transmission circuit hardware error.
The following settings in the FA command frame are incorrect.
The ICF is set to have no response.
The value of the remote destination address (DNA, DA1,
DA2) has not been properly set.
The send delay time setting is too long.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit.
Reset the frame parameters correctly.
Reset the parameters in the System Setup correctly.
The communications conditions and baud rate do not match the settings at the host.
There is noise interference.
Perform one of the following:
Wire the local Unit RTS signal to the CTS signal using loopback.
Disable the CTS control.
Enter the RTS signal of the remote Unit into the CTS signal of the local Unit, and then use CTS control.
Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n
+ 8/ n + 18.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
314
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to Host
Link.
Indicator status
The RD
@/SD@ and COM
@ indicators are flashing, and an error response has returned to the host.
The RD
@/SD@ and COM
@ indicators are flashing, but sometimes there is no response returned.
Status information, etc.
There is no transmission error.
There is a transmission error.
There is a transmission error sometimes.
CIO Area
CIO Area words n +
8/ n + 18 (transmission error status) are set to 0000 Hex.
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 04
(overrun error), bit
03 (framing error), or bit 02 (parity error) is turned ON.
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 04
(overrun error), bit
03 (framing error), or bit 02 (parity error) is turned ON.
Cause
A command was sent from the host with incorrect parameters.
The communications conditions and baud rate do not match the settings at the host.
The baud rate is outside the allowable range, and the stop bits do not match, causing the bits to be out of alignment.
Remedy
Review the host’s settings and program (such as parameter settings) based on the response contents.
Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n
+ 8/ n + 18.
Review the System Setup.
Review the host’s settings and program (such as baud rate and frame format).
Terminating resistance switch (TERM
ON/OFF) status
CIO Area words n +
8/ n + 18 (transmission error status) are not set to 0000
Hex.
Cables are incorrectly connected.
The RS-422A/485 port terminating resistance setting is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or the terminating resistance is incorrectly set.
Transmission errors are occurring that are caused by noise interference.
Check the wiring.
Turn ON the terminating resistance of the Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
Programming retry processing for communications if necessary.
315
Troubleshooting
Section 11-3
Serial communications mode
Host Link (with unsolicited communications)
Indicator status
The SD
@/RD@ and COM
@ indicators are all flashing.
Status information, etc.
SEND(090)/
RECV(098)/
CMND(490) instructions have been executed but have not been sent.
The AER Flag (one of the condition flags) is ON.
Bit 00 to 07 of word
A219 (Communications Port Error
Flag) are set to 1
(ON).
CIO Area
The ER Flag (one of the condition flags) is ON.
The Communications Port Enabled
Flag (A20200 to
A20207)is OFF
(execution disabled)
The Communications Port Enabled
Flag (A20200 to
A20207) is set as an
NC the execution condition for
SEND(090),
RECV(098), and
CMND(490) instructions.
Bit 15 of DM Area words m + 3/m + 13
(CTS control) is turned ON, and bit
04 of CIO Area words n + 7/n + 17
(CTS signal) is turned OFF.
rect.
Cause
The contents of the
S, C, and D operands for the
SEND(090),
RECV(098), and
CMND(490) instructions is set in a read-protected area.
The contents of the
S, C, and D operands for the
SEND(090),
RECV(098), and
CMND(490) instructions is set incorrectly.
The communications port number to be used is executing a SEND(090)/
RECV(098)/
CMND(490) instruction or PMCR(260) instruction.
Program is incor-
The Board or Unit is set for CTS control, but the RTS signal from the host is not input into the CTS signal of the local
Unit.
Remedy
Check the contents of the
S, C, and D operands of the SEND(090),
RECV(098), and
CMND(490) instructions, and correct if necessary.
Check the contents of the
S, C, and D operands of the SEND(090),
RECV(098), and
CMND(490) instructions, and correct if necessary.
Either use a different communications port number than the one being used to execute the SEND(090)/
RECV(098)/ CMND(490) instruction or PMCR(260) instruction, or wait for the same communications port number to be enabled and execute the instruction.
Set the Communications
Port Enabled Flag as an
NC execution condition for
SEND(090), RECV(098), and CMND(490) instructions.
Perform one of the following error processing methods.
Loopback the RTS and
CTS signals on the local
Unit.
Set to no CTS control.
Input the RTS signal from the remote Unit into the
CTS signal of the local
Unit for CTS control.
316
Troubleshooting
Section 11-3
Serial communications mode
Host Link, slave-initiated communications
Indicator status
The SD
@ and
COM
@ indicators are flashing, but there is no response from the host.
Status information, etc.
A transmission error has not been detected at the host.
---
---
CIO Area Cause Remedy
---
---
CIO Area words n +
5/n + 15 (port setting status in Setup
Area settings) do not correspond with the settings at the host.
A hardware error has occurred in the reception circuit.
Cables are incorrectly wired.
There is a hardware error in the reception circuit.
Adapters such as the NT-AL001-E are incorrectly wired or set.
---
The communications conditions and baud rate do not match the settings at the host.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit.
Check the wiring and correct.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit.
Check the program at the host. When unsolicited communications are used with Host Link mode, there must be a response returned from the host for every command sent from the Board or Unit.
Reset the parameters in the System Setup and at the host correctly.
Note The System Setup cannot be changed unless the power supply is cycled, the
Board or Unit is restarted, the port is restarted, or the STUP(237) instruction
is executed. Refer to 1-7 Comparison to Previous Products for details.
317
Troubleshooting
Section 11-3
11-3-2 Serial Gateway (Serial Gateway or Protocol Macro Mode)
Responses Returned to the FINS Transmission Source
Conversion Failure/Conversion Successful but Transmission Failed
Board/Unit status
The Board/
Unit cannot convert the received (via
CPU bus)
FINS command into either of the protocols.
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to a mode other than
Serial Gateway mode or protocol macro mode.
NT Link, loopback test, or noprotocol mode
Host Link
Protocol macro, NT
Link, or loopback test mode
Host Link
---
---
---
---
Cause Remedy
FINS end code sent to
FINS transmission source
Words allocated in CIO
Area
0401 hex
(undefined command)
0205 hex
(response timeout), etc.
0401 hex
(undefined command)
Bits 12 to 15 of the words allocated in the CIO Area n+5/n+15
(serial communications mode) are set to a value other than 9 hex or 6 hex.
2 hex, F hex, or 3 hex
0 hex or 5 hex
Serial communications mode is not set correctly.
FINS command was sent using
Serial Gateway to a
Board/Unit with Unit Ver.
1.2 or later.
Set DM Area word m/ m+10 bits 08 to 11 (serial communications mode) either to 9 hex (Serial
Gateway mode) or 6 hex
(protocol macro mode).
6 hex, 2 hex,
F hex, or 3 hex
0205 hex
(response timeout), etc.
0 hex or 5 hex
FINS command was sent using
Serial Gateway to a pre-
Ver. 1.2
Board/Unit that does not support
Serial Gateway communications.
Replace the Board/Unit with one that supports
Serial Gateway mode
(Unit Ver. 1.2 or later), and set the serial communications mode to
Serial Gateway or protocol macro mode.
318
Troubleshooting
Section 11-3
Board/Unit status
The Board/
Unit cannot convert the received (via
CPU bus)
FINS command into either of the protocols.
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to
Serial Gateway or protocol macro mode.
The SD
RD
@ and
COM
@/
@ indicators do not flash at all.
(Communications have not been electrically established.)
The SD
@ and
COM
@ indicators do not flash.
FINS end code sent to
FINS transmission source
0205 hex
(response timeout), etc.
0202 hex (no
Unit) or
0401 hex
(undefined command)
---
---
Words allocated in CIO
Area
Cause
A hardware error has occurred.
The serial communications mode is set to
Serial Gateway or protocol macro mode
The SD
@ and
COM
@ indicators do not flash at all.
2605 hex
(service executing)
---
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or
Unit.
Remedy
The FINS destination address is not specified correctly.
The serial port received a sixth FINS command when five
FINS commands are already waiting.
Correct the FINS destination address specification, and then resend the
FINS message. (Refer particularly to 6-7 Condi-
tions Requiring Routing
Tables.)
Include retry processing at the FINS command transmission source for when the FINS response code 2605 hex is received.
319
Troubleshooting
Section 11-3
Board/Unit status
The Board/
Unit converted the received (via
CPU bus)
FINS command, but could not send the command to the remote device after conversion.
Serial communications mode
Serial communications mode is set to protocol macro mode
Error conditions
Indicator display
The SD
COM
@ and
@ indicators do not flash at all.
FINS end code sent to
FINS transmission source
0204 hex
(remote node busy)
2607 hex
(transmission command error
(no right to execute service))
0205 hex
(response timeout), etc.
Words allocated in CIO
Area
Cause
Bit 05 of CIO word n+9/ n+19 (Serial
Gateway
Send Start
Timeout/
Response
Timeout
Flag) is ON.
Bit 08 of CIO word n+9/ n+19 (Serial
Gateway Prohibited Flag) is ON (prohibited status)
Bit 15 of CIO word m+3/ m+13 (CTS control) is ON but bit 4 of
CIO word n+7/n+17 is
OFF.
CTS control is set to ON but the RS signal from the remote device has not been input to the
CS signal of the local node.
A Serial
Gateway send start timeout has occurred.
(The converted command will be discarded without being sent).
The FINS command was received by the Board/
Unit, but the step transition in the communications sequence of the protocol macro is suspended for either of the following reasons.
1) The next step is a
RECEIVE command.
2) The WAIT command is being executed.
The Serial
Gateway is prohibited.
Remedy
Correct the communications sequence.
Alternatively, include retry processing at the FINS command transmission source for when the FINS response code 0204 hex is received.
Adjust the time set for the serial gateway Send Start
Timeout Monitoring Time in
DM Area word m+7/m+17, as required.
Turn OFF bits 04/12 of CIO word n (Port 1/2 Serial Gateway Prohibit Switch).
Perform either of the following:
Loop the RS-CS signals of the local node.
Disable CTS control.
Input the RS signal from the remote node to the CS signal of the local node and use
CTS control.
320
Troubleshooting
Section 11-3
Transmission Successful but Response from Remote Device Not Received
Board/Unit status
The converted command could be sent to the remote device but a normal response is not received from the remote device.
Serial communications mode
The serial communications mode is set to Serial
Gateway or protocol macro mode.
Error conditions
Indicator display
The SD indicators are flashing but the RD
@ does not flash.
@ and COM
@
FINS end code sent to
FINS transmission source
0205 hex
(response timeout), etc.
Words allocated in CIO
Area
Cause Remedy
Bit 05 of CIO word n+8/ n+18 (Serial
Gateway Send
Start Timeout/ Response
Timeout) is
ON.
A Serial Gateway response timeout has occurred and the response data cannot be received after the timeout. Either of the following causes is possible.
A remote device that can receive the command after conversion does not exist at the specified FINS destination address.
The sent command frame is illegal.
Perform one of the following:
Check the device at the specified FINS destination address.
Revise the command frame to be converted.
The communications conditions and baud rate settings for the serial communications path do not match the settings at the remote device.
Cable connections are incorrect or faulty.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or terminating resistance is not set correctly.
A command was sent in a protocol not understood by the remote device.
A hardware error has occurred in the remote device.
Revise the settings in the Setup Area and at the remote device.
Review the wiring or switch settings.
Turn ON the terminating resistance switch at two locations (remote device or board) and turn OFF the terminating resistance switch at all other nodes.
Check the command specifications of the remote device and the source of command conversion.
Replace the remote device.
321
Troubleshooting
Section 11-3
Board/Unit status
The converted command could be sent to the remote device but a normal response is not received from the remote device.
Serial communications mode
Error conditions
Indicator display
FINS end code sent to
FINS transmission source
The serial communications mode is set to Serial
Gateway or protocol macro mode.
Either the
SD
@/RD@ and COM
@ indicators all flash.
0205 hex
(response timeout), etc.
The SD
@ and COM indicators
@ flash, but a response is not always returned.
The RD
@/
SD
@, and
COM
@ indicators all flash, but a response is not always returned.
0205 hex
(response timeout), etc.
Words allocated in CIO
Area
Cause
Bit 05 of CIO word n+8/ n+18 (Serial
Gateway Send
Start Timeout/ Response
Timeout) is
ON.
The response from the remote device is too fast and the data received by the
Board/Unit has been discarded.
Bit 02, 03, 04, or 15 of CIO word n+8/ n+18 (transfer error, overrun error, framing error, or parity error) is ON.
A hardware error has occurred in the reception circuit of the Board/
Unit.
A transmission error has occurred due to noise.
Remedy
Delay the response from the remote device.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or
Unit.
Use shielded twistedpair cables.
Lay power lines separately using ducts.
Increase the number of resends at the FINS transmission source.
Perform communications retry as required.
322
Troubleshooting
Section 11-3
Response Received from Remote Device but Error Remains
Board/Unit status
A normal
FINS end code is returned from the remote device, but there is no response data after the end code.
A response was received from the remote device after a response timeout error was received for a converted command that was sent to the remote device.
A FINS error end code was returned to the FINS transmission source.
Serial communications mode
Error conditions
Indicator display
FINS end code sent to FINS transmission source
0000 hex The serial communications mode is set to
Serial Gateway or protocol macro mode.
The RD
@/
SD
@ and
COM
@ indicators all flash.
0205 hex
(response timeout), etc.
0206 hex
(transmission error)
---
Other FINS error end code
Words allocated in
CIO Area
Cause
The FINS command requires a response, but the command after conversion does not require a response
(e.g., broadcasting)
Bit 05 of CIO word n+8/ n+18 (Serial
Gateway send start timeout or
Serial Gateway response timeout) is
ON.
A Serial Gateway response timeout occurred, but the response data was received normally after the timeout.
This is a result of the Serial Gateway response timeout monitoring time setting in DM Area word m+7/m+17 being too short.
Check the specifications of the command to be converted.
Remedy
Set a longer time for the
Serial Gateway response timeout monitoring time in
DM Area word m+7/m+17.
CIO word n+8/n+18 bit
07 (FCS check error) or bit 02
(parity error) is ON.
---
Either of the following errors occurred in the protocol after conversion.
Conversion to CompoWay/F command: BCC error or parity error
Conversion to Modbus-RTU command:
CRC error or parity error
Conversion to Modbus-ASCII command: CRC error or checksum error
Conversion to Host
Link FINS command: FCS error or parity error
The Serial Gateway was executed, but the FINS error completion occurred.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Increase the number of resends at the FINS transmission source.
Perform communications retry as required.
Perform error processing based on the following table of FINS end codes.
323
Troubleshooting
Section 11-3
Troubleshooting Using FINS End Codes
MRC
(Main response code)
Value
(hex)
Contents
00 Normal completion
SRC
(Sub-response code)
Value
(hex)
Contents
00 Normal completion
04 Remote node busy
---
02
10
Remote node error
Command format error
05
06
01
02
Response timeout at FINS transmission source
Serial Gateway response timeout
Transmission path error
Command too long
Command too short
Check point
---
Probable cause Corrective measure
---
Bit 05 in CIO word n+8/n+18 (Serial
Gateway timeout or
Serial Gateway response timeout)
Bit 05 in CIO word n+8/n+18 (Serial
Gateway timeout or
Serial Gateway response timeout)
Instruction control data
Error history
The Serial Gateway cannot be executed as an interrupt between steps in the protocol macro.
The message frame was destroyed by noise.
The response monitoring time is too short.
The send/receive frame was discarded.
Perform FINS send retry processing or change the communications sequence.
If Bit 05 of CIO word n+8/n+18 is OFF, a response timeout has occurred at the
FINS transmission source. Perform the following:
Test communications to check the noise conditions.
Increase the number of retries at the
FINS command transmission source.
Perform communications retries, if necessary.
Increase the length of the response monitoring time.
Take appropriate measures based on the error history.
Bit 05 in CIO word n+8/n+18 (Serial
Gateway timeout or
Serial Gateway response timeout)
CIO word n+8/n+18 bit 07 (FCS check error) or bit 02 (parity error)
Command data
Command data
A Serial Gateway response timeout has occurred.
Conversion to CompoWay/F command:
BCC error or parity error
Conversion to Modbus-RTU command:
CRC error or parity error
Conversion to Modbus-ASCII command: CRC error or checksum error
The command is longer than the maximum permissible length.
The command is shorter than the maximum permissible length.
If bit 05 of CIO word n+8/n+18 is ON, take appropriate measures for a
Serial Gateway response timeout.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Increase the number of resends at the
FINS transmission source.
Perform communications retry as required.
Check the command format and correct the command data.
Check the command format and correct the command data.
324
Troubleshooting
Section 11-3
Value
(hex)
11
MRC
(Main response code)
SRC
(Sub-response code)
Contents Contents Value
(hex)
Parameter error 0C
Check point
Parameter error Parameters in command data
26 Command error 05
07
Probable cause Corrective measure
Service already executing
No execution right
---
Serial Gateway prohibition status
The parameter settings are incorrect.
The service is being executed. (A sixth
FINS command has been received at the serial port when five
FINS commands are already waiting to be processed.)
Serial Gateway is prohibited (bit 08 of
CIO word n+9/n+19 is ON)
Check the command data and correct the parameter settings.
Include retry processing at the FINS command transmission source for when the FINS response code 2605 hex is received.
If the Serial Gateway is prohibited, turn OFF bit 04/12 in
CIO word n (Serial
Gateway Prohibit
Switch port 1/2).
11-3-3 No-protocol Mode
Reception Failure (RXD(235), RXDU(255))
Error conditions
Serial communications mode
Indicator display
Status and other conditions
--The serial communications mode is set to a mode other than no-protocol mode
---
Words allocated in CIO
Area
Cause
CIO Area word n+5/n+15 bits
12 to 15 (serial communications mode) is set to a value other than 3 hex.
The serial communications mode is not set correctly.
---
Remedy
325
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
Board ---
Status and other conditions
---
Unit: Protocol macro mode, NT
Link, loopback test
Unit: Host
Link
-----
Words allocated in CIO
Area
Cause Remedy
Bit A42404 (Inner Board service failure) in the Auxiliary
Area is ON during execution of the RXD(235) instruction.
During execution of the
RXDU(255) instruction
FINS end code such as
0401 hex
(undefined command) is returned.
FINS end code such as
0205 hex
(response timeout) is returned.
The serial communications mode is not set correctly.
Or
A no-protocol instruction was sent using no-protocol mode to a
Board that does not support no-protocol communications (pre-Ver.1.2).
The serial communications mode is not set correctly.
Or
A no-protocol instruction was sent using no-protocol mode to a
Board that does not support no-protocol communications (pre-Ver.1.2).
Set bits 08 to 11 of
DM Area word m/ m+10 (serial communications mode) to 3 hex (no-protocol mode).
Or
Install a Board with
Unit Ver. 1.2 or later that supports no-protocol communications, and after replacing, set the serial communications mode to no-protocol mode.
Set bits 08 to 11 of
DM Area word m/ m+10 (serial communications mode) to 3 hex (no-protocol mode).
Or
Install a Board with
Unit Ver. 1.2 or later that supports no-protocol communications, and after replacing, set the serial communications mode to no-protocol mode.
326
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
Status and other conditions
--The serial communications mode is set to noprotocol mode.
---
The RD
@ and COM
@ indicators flash but communications are not always possible.
Words allocated in CIO
Area
Cause Remedy
---
---
A transmission error has occurred.
---
---
CTS control is ON, but bit 04 of word n+7/n+17 (CS) is
OFF.
A hardware error has occurred.
The cables are not connected correctly.
The setting of the
2/4-wire switch for the RS-422A/485 port does not match the actual wiring.
The wiring of adapters such as the NT-AL001-E is incorrect.
CTS control is set, but the remote node’s RS signal is not being input in the local node’s CS signal.
Conduct a loopback test in serial communications mode to check the transmission lines.
If an error occurs during the test, replace the Board or Unit.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4-wire method.
CIO word n+8/n+18 bit 15
(transmission error) or bit 04
(overrun error) is ON.
The settings in the
Setup Area such as baud rate and frame format do not match those of the remote device.
The baud rate is outside the permissible range, or the bits have been displaced due to a stop bit error or other error.
Perform either of the following:
Loop the RS-CS signals of the local node.
Disable CTS control.
Input the RS signal from the remote node to the CS signal of the local node and use CTS control.
Correct the settings in the Setup
Area.
Revise the remote device settings and program (e.g., baud rate, frame format)
327
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to noprotocol mode.
---
Status and other conditions
With Serial
Communications Units:
The
RXDU(255) instruction was sent, but reception is not being executed.
Words allocated in CIO
Area
The ER Flag (type of condition flag) is ON.
The Communications Port
Error Flags A21900 to
A21907 are ON.
The Communications Port
Enabled Flags (A20200 to
A20207) are OFF (execution disabled).
Cause Remedy
FINS end code:
2201 hex (not possible during execution) was returned.
If the RXDU(255) instruction was executed, the operation is disabled due to the port being busy while receiving.
FINS end code:
2202 hex (not possible while stopped) was returned. Execution is not possible while the protocol is being switched using the
STUP(237) instruction.
The TXDU(256)/
RXDU(255) instruction, or
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction is being executed using the same communications port No.
The setting contents indicated by the operand in the
RXDU(255) instruction is incorrect.
The TXDU(256)/
RXDU(255) instruction, or
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction is being executed using the same communications port No.
Review the contents of the operand for the
RXDU(255) instruction.
Either use a communications port other than that executing the
TXDU(256),
RXDU(255),
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction, or wait until the required port can be used and execute the instruction.
Insert an AND in the input condition for a NO condition of the Communications Port Enabled
Flag.
Insert an AND in the input condition for a NC condition of the Serial Communications Unit’s
Port Settings
Change Bit
(A62001 to
A63504).
Either use a communications port other than that executing the
TXDU(256),
RXDU(255),
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction (Bits 12 to 15 of C1), or wait until the required port can be used and then execute the RXDU(255) instruction.
328
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to noprotocol mode.
---
Status and other conditions
With Serial
Communications Boards:
The
RXD(235) instruction was sent, but reception is not being executed.
---
---
Words allocated in CIO
The ER Flag (type of condition flag) is ON.
Auxiliary Area bit A42404
(Inner Board service failure:
(non-fatal error)) is ON.
The Overrun Error Flag is
ON.
Area
Board: CIO 190804/CIO
191804 is ON.
Unit: CIO Area word n+8/ n+18 bit 04 is ON.
Cause Remedy
The setting contents indicated by the operand in the
RXD(235) instruction is incorrect.
The RXD(235) instruction was sent to a pre-
Ver.1.2 Board that does not support no-protocol communications, or a
Board is not installed.
Data of 260 bytes or higher was received in the reception buffer during execution of the RXD(235)/
RXDU(255) instruction.
Review the contents of the operand for the
RXD(235) instruction.
Replace the Board with one that is
Unit Ver. 1.2 or later, or install a
Board.
Cycle the power or restart the Board, and clear the reception buffer.
Note: If an overrun error occurs, the
Overrun Error Flag can be turned OFF by cycling the power or restarting the Unit/Board or restarting the port.
The Reception Overrun Flag is ON
Board: Auxiliary Area bit
A35607/A35615 is ON.
Unit: CIO Area word n+9/ n+19 bit 07 is ON.
After reception was completed (after the Reception
Completed Flag turned ON), further data was received
(1 byte or more).
After data reception is completed
(after Reception
Completed Flag turns ON), reexecute the RXD(235)/
RXDU(255) instruction.
329
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
Status and other conditions
--The serial communications mode is set to noprotocol mode.
---
Words allocated in CIO
Area
The Reception Completed
Flag is OFF.
Board: Auxiliary Area bit
A35606/A35614 is OFF.
Unit: CIO Area word n+9/ n+19 bit 06 is OFF.
-----
Cause Remedy
Reception does not complete due to the following factors.
The start code/ end code setting is incorrect.
---
Revise the settings for the start code/end code in
DM Area word m+5/m+15.
No data has been received.
The specified number of data bytes has not been received.
Data of 260 bytes or more was received in the reception buffer before the
RXD(235)/
RXDU(255) instruction was executed.
A hardware error has occurred in the reception circuit of the Board/Unit.
Revise the specified number of receive data bytes in allocation DM
Area word m+5/ m+15.
Cycle the power or restart the Board and clear the reception buffer.
Note: If an overrun error occurs, the
Overrun Error Flag can be turned OFF by cycling the power or restarting the Unit/Board or restarting the port.
Conduct a loopback test in serial communications mode to check the transmission lines.
If an error occurs during the test, replace the Board or Unit.
330
Troubleshooting
Section 11-3
Transmission Failure (TXD(236), TXDU(256))
Error conditions
Serial communications mode
Indicator display
---
Status and other conditions
--Serial communications mode is no-protocol mode
Board
Unit: Protocol macro mode,
NT Link, loopback test
---
Unit: Host
Link
-----
---
Words allocated in CIO
Area
Cause Remedy
CIO Area word n+5/n+15 bits
12 to 15 (serial communications mode) is set to a value other than 3 hex.
Bit A42404 (Inner Board service failure) in the Auxiliary
Area is ON when the
TXD(236) instruction is executed.
During execution of the
TXDU(256) instruction
FINS end code such as
0401 hex
(undefined command) is returned.
FINS end code such as
0205 hex
(response timeout) is returned.
The serial communications mode is not set correctly.
The serial communications mode is not set correctly.
Or
A no-protocol instruction was sent using noprotocol mode to a Board that does not support no-protocol communications (pre-
Ver.1.2).
---
The serial communications mode is not set correctly.
Or
A no-protocol instruction was sent using noprotocol mode to a Board that does not support no-protocol communications (pre-
Ver.1.2).
Set bits 08 to 11 of
DM Area word m/ m+10 (serial communications mode) to 3 hex (no-protocol mode).
Or
Install a Board with
Unit Ver. 1.2 or later that supports noprotocol communications, and after replacing, set the serial communications mode to noprotocol mode.
Set bits 08 to 11 of
DM Area word m/ m+10 (serial communications mode) to 3 hex (no-protocol mode).
Or
Install a Board with
Unit Ver. 1.2 or later that supports noprotocol communications, and after replacing, set the serial communications mode to noprotocol mode.
331
Troubleshooting
Section 11-3 cations mode
Error conditions
Serial communiIndicator display
The serial communications mode is set to noprotocol mode.
The SD
@/
RD
@ and
COM
@ indicators do not flash at all.
(Communications have not been electrically established.)
---
Status and other conditions
-----
---
Words allocated in CIO
Area
Cause Remedy
The SD
@ and
COM
@ indicators flash but communications are not always possible.
---
A transmission error has occurred.
CTS control is ON, but bit 04 of word n+7/n+17 (CS) is
OFF.
CIO word n+8/n+18 bit 15
(transmission error) or bit 04
(overrun error) is ON.
A hardware error has occurred.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the
Board or Unit.
Check the wiring.
The cables are not connected correctly.
The setting of the
2/4-wire switch for the RS-422A/
485 port does not match the actual wiring.
The wiring of adapters such as the NT-AL001-E is incorrect.
Reset the port to the correct wiring setting.
Wire all nodes using the 4-wire method.
CTS control is set, but the remote node’s
RS signal is not being input in the local node’s CS signal.
The settings in the Setup Area such as baud rate and frame format do not match those of the remote device. The baud rate is outside the permissible range, or the bits have been displaced due to a stop bit error or other error.
Perform either of the following:
Loop the RS-CS signals of the local node.
Disable CTS control.
Input the RS signal from the remote node to the CS signal of the local node and use CTS control.
Correct the settings in the Setup
Area.
Revise the remote device settings and program (e.g., baud rate, frame format)
332
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to noprotocol mode.
---
Status and other conditions
With Serial
Communications Units:
The
TXDU(256) instruction was sent, but reception is not being executed.
Words allocated in CIO
Area
The ER Flag (type of condition flag) is ON.
The Communications Port
Error Flags A21900 to
A21907 are ON.
Cause Remedy
FINS end code:
2201 hex (not possible during execution) was returned. If the
TXDU(256) instruction was executed, the operation is disabled because the port being busy while receiving.
FINS end code:
2202 hex (not possible while stopped) was returned. Execution is not possible while the protocol is being switched using the STUP(237) instruction.
The setting contents indicated by the operand in the TXDU(256) instruction is incorrect.
The TXDU(256)/
RXDU(255) instruction, or
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction is being executed using the same communications port No.
Review the contents of the operand for the TXDU(256) instruction.
Either use a communications port other than that executing the
TXDU(256),
RXDU(255),
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction, or wait until the required port can be used and execute the instruction.
Insert an AND in the input condition for a NC condition of the Communications TXDU(256)
Executing Flag
(n+9/n+19 bit 05).
Insert an AND in the input condition for a NC condition of the Serial Communications Unit’s
Port Settings
Change Bits
(A62001 to
A63504).
333
Troubleshooting
Section 11-3
Error conditions
Serial communications mode
Indicator display
The serial communications mode is set to noprotocol mode.
---
Status and other conditions
With Serial
Communications Units:
The
TXDU(256) instruction was sent, but reception is not being executed.
Words allocated in CIO
Area
The Communications Port
Enabled Flags (A20200 to
A20207) are OFF (execution disabled).
The serial communications mode is set to noprotocol mode.
--With Serial
Communications Boards:
The
TXD(236) instruction was sent, but reception is not being executed.
---
The ER Flag (type of condition flag) is ON.
Auxiliary Area bit A42404
(Inner Board service failure:
(non-fatal error)) is ON.
Cause Remedy
The TXDU(256)/
RXDU(255) instruction, or
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction is being executed using the same communications port No.
The setting contents indicated by the operand in the TXD(236) instruction is incorrect.
The TXD(236) instruction was sent while the
Send Delay Flag
(bit A35605/
A35613) was
OFF.
Either use a communications port other than that executing the
TXDU(256),
RXDU(255),
SEND(090),
RECV(098),
CMND(490), or
PMCR(260) instruction (Bits 12 to 15 of C1), or wait until the required port can be used and then execute the TXDU(256) instruction.
Review the contents of the operand for the TXD(236) instruction.
Insert an AND in the input condition for a NO condition of the Send Delay
Flag (bit A35605/
A35613).
The TXD(236) instruction was sent to a pre-
Ver.1.2 Board that does not support nopr]otocol communications, or the
Board is not installed.
A hardware error has occurred in the transmission circuit.
Replace the Board with one that is Unit
Ver. 1.2 or later, or install a Board.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the
Board or Unit.
334
Troubleshooting
Section 11-3
11-3-4 1:N NT Link Mode
Serial communications mode
Serial communications mode is not set to NT
Link.
Serial communications mode is set to NT Link.
---
Indicator display
The SD
@/RD@ and COM
@ indicators do not flash at all.
(Communications have not been electrically established.)
The SD
@ and
COM
@ indicators are flashing, but the Unit or
Board cannot communicate with the Programmable Terminal (PT).
---
---
Status information, etc.
---
Words allocated in the
CIO Area
Bits 12 to 15 of the words allocated in the CIO
Area n+5/n+15 are set to a value other than
2 Hex.
---
Cause
Serial communications mode is not set correctly.
This is a hardware error.
Remedy
Review the Setup Area settings.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit.
--The baud rate setting is different to the
PT’s baud rate setting.
There is a setting error for the PT serial port.
Either change the baud rate setting in the System Setup or change the baud rate setting for the PT.
Correct the PT serial port settings.
The 1:N NT Link unit number of the PT is incorrect.
The same 1:N NT
Link unit number has been set for more than one PT
The maximum allowable NT Link unit number is incorrectly set for the system.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the
NT-AL001-E are incorrectly wired or set.
A communications error frequently occurs due to noise, etc.
There is a PT hardware error.
Review the NT Link unit number of the PT.
Review the Setup Area settings.
Review the wiring or switch settings.
Review the wiring and installation environment.
Replace the PT.
335
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to NT Link.
Indicator display
The SD
@/RD@ and COM
@ indicators are flashing, but a communications error sometimes occurs in the PT.
Status information, etc.
-----
Words allocated in the
CIO Area
Cause Remedy
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the
NT-AL001-E are incorrectly wired or set.
A communications error frequently occurs due to noise, etc.
Review the wiring or switch settings.
Check whether the terminating resistances of the host computer and the last
Unit are set to ON, and the terminating resistances of other Units are set to OFF.
The communications monitoring time for the PT is insufficient.
The load on the PLC is too high.
Review the wiring and installation environment.
Increase the number of retries for the PT as required.
Increase the communications monitoring time for the
PT.
Lighten the load on the
PLC.
Reduce the number of PTs connected to each serial port by using other ports for some of the PTs.
Adjust the timeout and retry settings in the PT.
Note
1.
The PT serial port must be set for a 1:N NT Link. The PT will not be able to communicate with a Serial Communications Board or Unit if the PT is set for a 1:1 NT Link.
2.
The System Setup cannot be changed unless the power supply is cycled, the Board or Unit is restarted, the port is restarted, or the STUP(237) in-
struction is executed. Refer to 1-7 Comparison to Previous Products for de-
tails.
336
Troubleshooting
Section 11-3
11-3-5 Protocol Macros
Serial communications mode
Serial communications mode is not set to protocol macro.
Serial communications mode is set to protocol macro.
Indicator
---
display
The SD
@/
RD
@ and
COM
@ indicators do not flash at all. (Communications has not been electrically established.)
Status information, etc.
Words allocated in the CIO Area
Cause Remedy
---
The PMCR(260) instruction is executed, but bit
15 (Protocol
Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 does not turn ON.
Bits 12 to 15 of the words allocated in the CIO Area n+5/ n+15 are set to a value other than 6
Hex.
Bits 00 to 07 of the
Communications
Port Error Flags in
A219 are set to 1
(ON).
As PMCR(260) instruction execution conditions, bit 15
(Protocol Macro Executing Flag) of the words allocated in the CIO Area n+9/ n+19 is set as a NO execution condition.
The ER Flag (one of
Condition Flags) is set to ON.
Serial communications mode is not set correctly.
The PMCR(260) instruction operand settings or execution timing are incorrect.
Set bits 11 to 08 (Serial
Communications Mode) of the Allocation DM Area m/m+10 to 6 Hex (Protocol Macro).
See note on page 342.
The program is incorrect. As PMCR(260) instruction execution conditions, set bit 15 (Protocol Macro
Executing Flag) of the words allocated in the
CIO Area n+9/n+19 to a
NC execution condition.
Check the PMCR(260) instruction C1, C2, C3, S, and D operand settings for errors.
The AER Flag (one of the Conditions
Flags) is ON.
Bits 00 to 03 (Error
Code) of the words allocated in the CIO
Area n+9/n+19 are set to 2 Hex
(Sequence Number
Error).
Bits 00 to 03 (Error
Code) of the words allocated in the CIO
Area n+9/n+19 are set to 3 Hex (Data
Read/Write Range
Error).
The problem cause is one of the following:
- The data range for the
PMCR(260) instruction
C1 operand is incorrect.
- The number of data words in the S or D operand exceeds 250.
- The Communications
Port Error Flag is set to
OFF.
An illegal address is specified for the S or D operands of the
PMCR(260) instruction.
The sequence number specified in the
PMCR(260) instruction
C2 operand is a value other than 000 Hex to
3E7 Hex (000 to 999 in decimal notation).
The specified communications sequence number does not exist in the protocol data.
The data range of the specified area is exceeded when data is being written to or read from the I/O memory of the CPU Unit.
Correct any mistakes in the operands of
PMCR(260).
Set the PMCR(260) instruction C2 operand to a value between 000 Hex and 03E7 Hex (between
000 and 999 in decimal notation).
Check whether the communications sequence number is correct.
Specify another area, or reduce the size of the data to be sent or received.
337
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to protocol macro.
Indicator display
The SD
@/
RD
@ and
COM
@ indicators do not flash at all. (Communications have not been electrically established.)
Status information, etc.
Words allocated in the CIO Area
Cause Remedy
The PMCR(260) instruction is executed, but bit
15 (Protocol
Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 does not turn ON.
Bits 00 to 03 (Error
Code) of the words allocated in the CIO
Area n+9/n+19 are set to 4 Hex (Protocol Data Syntax
Error).
The Network Communications Instruction Execution
Enabled Flag
(A20200 to A20207) is set to OFF (Execution Disabled).
The protocol data in the
Board or Unit is incorrect.
The SEND(090),
RECV(098), CMND(490), or another PMCR(260) instruction is currently being executed using the same communications port number.
Use CX-Protocol to correct and transfer the protocol data.
Execute the PMCR(260) instruction using a communications port number
(set in bits 12 to 15 of C1) other than that used for the SEND(090),
RECV(098), CMND(490), or another PMCR(260) instruction.
The program is incorrect. As PMCR(260) instruction execution conditions, set the Network Communications Instruction Execution Enabled Flag
(A20200 to A20207) to a
NO execution condition.
As PMCR(260) instruction execution conditions, the Network Communications Instruction
Execution Enabled
Flag (A20200 to
A20207) is set as a
NC execution condition.
Bit 00 (Port Active) of the words allocated in the CIO Area n+6/ n+16 remains 0 (Port
Inactive).
Send processing is not executed.
Bit 15 (Protocol
Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 is turned ON when the PMCR(260) instruction is executed, but data cannot be sent or received properly.
Bit 10 (Remote Node
Receive Busy) of the words allocated in the CIO Area n+7/ n+17 is set to ON
(Remote Node
Busy).
Bit 09 (Sequence
Wait) of the words allocated in the CIO
Area n+9/n+19 is set to ON (Sequence
Wait Status).
Protocol data is being transferred, or a SUM value error has occurred.
The send wait time specified in communications sequence step units is too long.
The CS signal from the remote node cannot turn
ON (the remote node remains in busy status) because the transmission control parameter “RS/
CS Flow Control” is set to
“Yes.”
The WAIT command cannot be released.
Wait for the transfer of protocol data to finish or use CX-Protocol to transfer the protocol data.
Use CX-Protocol to check whether the send wait time is correctly set.
Release the remote node busy status to enable the local node CS signal to turn ON.
Review the program so that bits 00 and 08 (Wait
Release Switch) of word n in the words allocated in the CIO Area can be switched from OFF to
ON.
338
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to protocol macro.
Indicator display
Status information, etc.
Words allocated in the CIO Area
Cause Remedy
The SD
@/
RD
@ and
COM
@ indicators do not flash at all. (Communications has not been electrically established.)
Bit 15 (Protocol
Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 momentarily turns ON when the PMCR(260) instruction is executed, but it cannot remain
ON.
Send data has already been transmitted, but there is no response from the remote node.
Bits 03 and 11 (Abort
Switch) of the words allocated in the CIO
Area n are force-set.
---
The SD
@/
RD
@ and
COM
@ indicators are flashing, but the Unit or
Board cannot perform communications.
Bit 10
(Sequence
Abort End Flag) of the Protocol words allocated in the CIO Area n+9/n+19 is set to ON.
Bit 15 (Protocol
Macro Executing Flag) of the words allocated in the CIO Area n+9/n+19 remains ON when the
PMCR(260) instruction is executed without setting the monitoring time in sequence units.
The sequence is aborted (the step is interrupted).
The sequence is running and does not end (the words allocated in the CIO
Area is in receive status).
Abort Switch is force-set.
Release the forced or
Abort Switch.
This is a hardware error.
Set bits 11 to 08 (Serial
Communications Mode) of the Allocation DM Area to F Hex (Loopback Test
Serial Communications
Mode), connect the connector wired for a loopback test, then conduct a loopback test by turning
ON bit 14 of word n. The test data is reflected in the Allocation DM Area n+9/n+19. If an error occurs during the test, replace the Board or Unit.
Protocol macro data is not set correctly.
The Setup Area settings such as the baud rate and frame format differ from those of the remote node.
Use CX-Protocol transmission line trace to check whether the protocol data and Setup Area settings are correct.
339
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to protocol macro.
Indicator display
Status information, etc.
Words allocated in the CIO Area
Cause Remedy
The SD
@/
RD
@ and
COM
@ indicators are flashing, but the
Unit or
Board cannot perform communications.
The SD
@/
RD
@ and
COM
@ indicators are flashing, but the Unit or
Board cannot perform communications or a communications error sometimes occurs.
Send data has already been transmitted, but there is no response from the remote node.
A transmission error occurs.
Data is received through CX-Protocol transmission line trace, but the protocol macros behave as if no data is received.
The remote node sometimes returns no response to sent data. Response may be received by performing retries.
---
The contents of the words allocated in the CIO Area n+5/ n+15 (System Port
Settings) do not match those of the remote node.
Bit 15 (Transmission
Error) of the words allocated in the CIO
Area n+8/n+18 is set to ON.
There is an error in bits 0 to 14.
Bit 15 (Transmission
Error) of the words allocated in the CIO
Area n+8/n+18 is set to ON.
There is an error in bits 0 to 14.
The contents of the words allocated in the CIO Area n+5/ n+15 (System Port
Settings) do not match those of the remote node.
---
The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on.
The wiring is faulty.
The setting of the 2/4wire switch for the RS-
422A/485 port does not match the actual wiring.
The wiring of adapters such as the NT-AL001-E is faulty.
The Setup Area settings such as the baud rate and frame format differ from those of the remote node. The baud rate is outside the allowable range, or there are bit errors due to mismatched stop bits and so on.
Review the Setup Area settings.
Review the remote node settings and the program
(including the baud rate, frame format, and so on).
Check the wiring.
Turn ON the terminating resistances of the Board and the last node. Turn
OFF the terminating resistances of other nodes.
Review the Setup Area settings.
Review the remote node settings and the program
(including the baud rate, frame format, and so on).
Because response from the remote node in halfduplex mode is received too fast, the data received from the time the data send processing was completed until the Send operation was completed is discarded.
The transmission timing is too fast for the remote node to receive data.
Use full-duplex mode.
Set or increase the transmission wait time (time to await data transmission) in step units.
340
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to protocol macro.
Indicator display
Status information, etc.
The SD
@/
RD
@ and
COM
@ indicators are flashing, but the Unit or
Board cannot perform communications or a communications error sometimes occurs.
A transmission error sometimes occurs.
The RDY and ERC indicators are flashing (ERR/
ALM).
The RDY indicator is lit and the
ERC indicator is flashing (ERR/
ALM).
---
---
Words allocated in the CIO Area
Bit 15 (Transmission
Error) of the words allocated in the CIO
Area n+8/n+18 is set to ON.
There is an error in bits 0 to 14.
The wiring is faulty.
The RS-422A/485 port terminating resistance setting is incorrect.
Adapters such as the NT-
AL001-E are incorrectly wired, or the terminating resistance setting is incorrect.
A communications error frequently occurs due to noise and so on.
Bit 00 (Protocol Data
Error) of the words allocated in the CIO
Area n+1 is set to
ON.
The protocol macro data
SUM value is abnormal.
Check the wiring.
Turn ON the terminating resistance of the Board and the last node by using the terminating resistance switch. Turn
OFF the terminating resistance of other nodes.
Use shielded twisted pair cables.
House the communications cables in a different duct from those for power lines and so on.
Review the operating environment to prevent noise problems.
Programming retry processing for communications if necessary.
Use CX-Protocol to transfer the correct protocol data.
Bits 00 to 03 (Port
Status Error Code) of the words allocated in the CIO
Area n+9/n+19 are set to a value other than 0 Hex. (An error has occurred.)
Cause
An error has been detected in the protocol macros, making the operation impossible.
Remedy
See note on page 343.
341
Troubleshooting
Section 11-3
Note The following table shows the measures to correct the errors indicated by network communications end codes (A203 to A210).
Network communications end code
Bits
08 to 15
Bits
00 to 07
Error details
02 Hex 02 Hex There is no Board or Unit corresponding to the unit address.
Remedy
Check whether a different Board/Unit or serial port (physical port) is specified in the PMCR(260) instruction C1 operand (communications port number).
04 Hex 01 Hex The specified service is not supported.
Check whether a different Board/Unit or serial port (physical port) is specified in the PMCR(260) instruction C1 operand (communications port number).
Check whether the serial communications mode of the serial port specified in the C1 operand is protocol macro. If not, set the serial communications mode to protocol macro.
02 Hex 05 Hex The watchdog timer expires because no response is received from the remote node within the specified time.
11 Hex 06 Hex The specified communications sequence number does not exist.
Check whether the serial communications mode of the serial port specified in the C1 operand is protocol macro. If not, set the serial communications mode to protocol macro.
The communications sequence number specified in the
PMCR(260) instruction C2 operand is unregistered.
Use CX-Protocol to register the communications sequence number.
22 Hex 01 Hex PMCR(260) instruction cannot be executed because protocol macro is currently being executed.
24 Hex 01 Hex No registration table exists.
An attempt is made to execute the PMCR(260) instruction while protocol macros are being executed.
Modify the ladder program so that bit 15 (Protocol Macro
Executing Flag) of the words allocated in the CIO Area n+9/ n+19 is set to a NC execution condition for the PMCR(260) instruction.
The problem cause is one of the following:
• Protocol macro (communications sequence) data has not been registered.
• Protocol macro (communications sequence) data is currently being registered or transferred.
• Protocol macro (communications sequence) data contains a SUM value error.
Use CX-Protocol to transfer the correct protocol macro
(communications sequence) data.
342
Troubleshooting
Section 11-3
Note The following table shows the measures to correct the errors indicated in bits
00 to 03 (Error Code) of words allocated in the CIO Area words n+9/n+19.
Error code
0 Hex
1 Hex
2 Hex
3 Hex ERC:
Flashing
ERR/ALM:
Flashing
Data read/write range error
4 Hex
Indicator
No display
No display
No display
ERC:
Flashing
ERR/
ALM:
Flashing
Error details
Normal
Reserved
Sequence number error
Protocol data syntax error
Cause Remedy
---
---
---
---
The communications sequence number specified in the PMCR(260) instruction’s C2 operand is not registered.
The data range of the specified area is exceeded when data is being written to or read from the I/
O memory of the
CPU Unit.
There is a code that cannot be executed during protocol execution.
Correct the communications sequence number.
Use CX-Protocol to register the specified communications sequence number.
For operand specification:
Check the PMCR(260) instruction S and
D operand specifications.
For direct specification of link words:
Use CX-Protocol to check the specified range.
Check the following items and correct the problem.
• Check whether the total specified number of link words in the area (O1, O2,
I1, I2) exceeds 500.
• The same area with link word specification is used by both ports 1 and 2.
• A write instruction with constant specification is specified.
• An EM Area read/write instruction is specified as an interrupt notification
(for Boards only).
• An interrupt notification is specified at the Unit (for Units only).
• There are more than 30 write attributes set for one message.
• The length of a send/receive message is set to 0 bytes.
• The length of a send/receive message is longer than the maximum send/ receive message bytes setting.
• No messages are registered for matrix reception.
• Both RTS/CTS flow control and Xon/
Xoff flow control are set for the same transmission line.
343
Troubleshooting
Section 11-3
11-3-6 Modbus-RTU Slave Mode
Serial communications mode
Serial communications mode is not set to
Modbus-RTU slave mode.
Serial communications mode is set to Modbus-RTU slave mode.
---
Indicator status
The SD not flash at all.
(Communications have not been electrically established.)
@/RD@ and COM
@ indicators do
The RD
@ and
COM
@ indicators are flashing, but the response has not been returned from the host.
For the Unit, the
SD
@ indicator does not flash at all (Communications have been electrically established.)
Status information, etc.
---
---
CIO Area
Bits 12 to 15 (Serial
Communications
Mode) of CIO Area words n + 5/n + 15 are set to a value other than A Hex.
---
There is no transmission error.
Cause
Serial communications mode is not set correctly.
Remedy
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10 to A Hex (Modbus-RTU slave mode).
CIO Area words n +
8/n + 18 (transmission error status) are set to 0000 Hex.
CIO Area words n +
5/n + 15 (port settings in the System
Setup) do not correspond to the settings of the remote device.
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or set.
Commands are not being set from the host.
This is a hardware error.
The System Setup in DM Area words m
+ 6/m + 16 of the
Board or Unit (Modbus-RTU slave address) does not correspond to the settings for the remote device.
The command format and data length of the data sent from the host are incorrect.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4wire method.
Reset the serial port at the host, and rewrite the program.
Set bits 08 to 11 (Serial
Communications Mode) of
DM Area words m/m + 10 to F Hex (Loopback Test
Serial Communications
Mode). Then, connect the connector wire for a loopback test and conduct a loopback test by turning
ON bit 14 (Loopback Test
Switch) of CIO Area word n. The test data is reflected in CIO Area words n+9/n+19. If an error occurs during the test, replace the Board or
Unit.
Correct the setting in DM
Area words m + 6/m + 16 of the Board or Unit (Modbus slave address) so that they correspond to the settings at the host device.
Correct the command frame (destination Modbus slave address) and the program.
344
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to Modbus-RTU slave mode.
Indicator status
The RD
@ and
COM
@ indicators are flashing, but the response has not been returned from the host.
For the Unit, the
SD
@ indicator does not flash at all (Communications have been electrically established.)
Status information, etc.
There is no transmission error.
---
There is a transmission error.
CIO Area Cause Remedy
---
Cables are incorrectly connected.
The RS-422A/485 port setting (2-wire or 4-wire) is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or set.
This is a transmission circuit hardware error.
Check the wiring.
Reset the port to the correct wiring setting.
Wire all nodes using the 4wire method.
Conduct a loopback test in serial communications mode to check the transmission lines. If an error occurs during the test, replace the Board or Unit.
Correct the destination
Modbus slave address in the command frame.
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 07(CRC error), bit 04 (overrun error), bit 03
(framing error), or bit 02 (parity error) is turned ON.
The destination
Modbus slave address in the command frame is set to
0, i.e., it is set for a broadcast.
The communications conditions and baud rate do not match the settings at the host.
There is noise interference.
There is an error in the CRC code appended to the host command frame.
Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n
+ 8/ n + 18.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
Append the correct CRC code.
345
Troubleshooting
Section 11-3
Serial communications mode
Serial communications mode is set to Modbus-RTU slave mode.
Indicator status
Status information, etc.
The RD
@/SD@ and COM
@ indicators are flashing, and an error response has returned to the host.
The RD
@/SD@ and COM
@ indicators are flashing, but sometimes there is no response returned.
There is no transmission error.
There is a transmission error.
There is a transmission error sometimes.
CIO Area
CIO Area words n +
8/ n + 18 (transmission error status) are set to 0000 Hex.
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 07(CRC error), bit 04 (overrun error), bit 03
(framing error), or bit 02 (parity error) is turned ON.
In CIO Area words n
+ 8/ n + 18, bit 15
(transmission error status) is turned
ON, and bit 07(CRC error), bit 04 (overrun error), bit 03
(framing error), or bit 02 (parity error) is turned ON.
There is a transmission error sometimes.
Cause
A command was sent from the host with incorrect parameters.
The communications conditions and baud rate do not match the settings at the host.
The baud rate is outside the allowable range, and the stop bits do not match, causing the bits to be out of alignment.
Remedy
Review the host’s settings and program (such as parameter settings) based on the response contents.
Review the System Setup, the host’s settings and program (such as commands and frame format) based on the response contents, and the transmission error codes in CIO Area words n
+ 8/ n + 18.
Review the System Setup.
Review the host’s settings and program (such as baud rate and frame format).
Terminating resistance switch (TERM
ON/OFF) status
Cables are incorrectly connected.
The RS-422A/485 port terminating resistance setting is incorrect.
Adapters such as the NT-AL001-E are incorrectly wired or the terminating resistance is incorrectly set.
Check the wiring.
Turn ON the terminating resistance of the Board and the last node by using the terminating resistance switch. Turn OFF the terminating resistance of other nodes.
There is a transmission error sometimes.
CIO Area words n +
8/ n + 18 (transmission error status) are not set to 0000
Hex.
Transmission errors are occurring that are caused by noise interference.
Use shielded twisted-pair cables.
Lay power lines separately using ducts.
Review the installation environment to reduce noise interference.
Programming retry processing for communications if necessary.
346
Error Logs
Section 11-4
11-4 Error Logs
The error log function records the errors detected in the Serial Communications Board or Serial Communications Unit together with the time that the error occurred.
11-4-1 Error Log Table
RAM Error Log Table
EEPROM Error Log Table
For every error that occurs, one record is logged in the RAM error log table in the Board or Unit for up to 64 errors.
Records of errors that are particularly serious are logged in both the RAM error log table and the EEPROM error log table in the Board or Unit when they occur. The contents of errors logged in the EEPROM error log table remain even if the power to the Board or Unit is turned OFF or the Board or Unit is restarted. The contents of the EEPROM error log table is automatically read to the RAM error log table when the power is turned ON. One record is logged in the EEPROM error log table for each error that occurs for up to 32 errors max.
11-4-2 Error Log Specifications
Item
Record length
Record configuration
Data format
Number of records
Storage order
Specifications
10 bytes per record
Error code: 2 bytes
Details:
Time:
2 bytes
6 bytes
Binary (time information is in BCD)
RAM: 64 records max.
EEPROM: 32 records max.
Records are stored in order from the oldest to the most recent errors.
When the number of errors recorded in the RAM error log table reaches 64 (or
32 records for the EEPROM error log table), the oldest records will be deleted to store the most recent errors.
347
Error Logs
Section 11-4
11-4-3 Error Log Table Configuration
15 08 07 00
Error code
Details
Bit
Minute Second
Day
Year
Hour
Month
Error code
Details
Minute Second
Day Hour
Year Month
Record
(oldest)
Record
Error code
Details
Minute Second
Day
Year
Hour
Month
Record
(newest)
Error Codes and Details
Time of Error
Refer to the list of error codes and details on page 348.
The time the error occurred is recorded including the year (rightmost two digits), month, day, hour, minute, and second in 1-byte BCD (binary coded decimal).
Reading and Clearing
Error Log Tables
The error log table can be read or cleared using FINS commands sent to the
Serial Communications Board or Serial Communications Unit. Refer to 11-4-6
Reading and Clearing Error Log Tables for details.
Note The Serial Communications Board and Serial Communications Unit use the time information read from the CPU Unit. If the time cannot be read from the
CPU Unit, the time of the error in the error log will be recorded as all zeros.
For all CS/CJ-series PLCs, the time of the CPU Unit’s built-in clock must be set when the power is turned ON after the battery is mounted. If the built-in clock time is not set, the time recorded in the error log will be incorrect, and when the error log is read, the time will be irregular.
11-4-4 Error Codes and Details
Error code
0001 Hex
0002 Hex
0006 Hex
000F Hex
0011 Hex
0012 Hex
Error contents
CPU Unit watchdog timer error
CPU Unit service monitoring error
Other CPU Unit errors
First byte
Always 00 Hex
Monitoring time (Unit: 1 ms)
Details
Second byte
Always 00 Hex
Bit 11: The unit number is not included in the registered I/
O tables.
Other bits not used.
Always 00 Hex Always 00 Hex CPU Unit initial processing error
CPU Unit initial processing error
Not fixed Not fixed
CPU Unit memory error 01 Hex: Read error
02 Hex: Write error
03 Hex: Routing tables
05 Hex: CPU Bus Unit/
Inner Board DM Area
Stored in
EEPROM
Yes
Yes
Yes
Yes
Yes
No
348
Error Logs
Section 11-4
Error code
0014 Hex
0108 Hex
010B Hex
010D Hex
010E Hex
0112 Hex
0117 Hex
0118 Hex
011B Hex
011C Hex
011D Hex
011E Hex
021A Hex
0300 Hex
0301 Hex
0302 Hex
0601 Hex
0602 Hex
Error contents
Inner bus error
Send not possible because
Unit is not detected
Send not possible due to
CPU Unit error
Send not possible due to remote address setting error
Send not possible because routing tables are not set properly
Send not possible due to header setting error
Internal reception buffer full
Illegal packet discarded
01 Hex: Port 1
02 Hex: Port 2
Details
First byte
Always 00 Hex
Second byte
Always 00 Hex
Event Send/Receive Errors
Commands:
Send source network address < 80
Bit 15:
Bits 08 to 14:
OFF
Send source network address
Bits 00 to 07: Send source node address
Send source network address
≥ 80
Bit 15: OFF
Bits 08 to 14: 00
Bits 00 to 07: Send source network address
Responses:
Send destination network address < 80
Bit 15:
Bits 08 to 14:
Bits 00 to 07:
ON
Send destination network address
Send destination node address
Send destination network address
≥ 80
Bit 15: ON
Bits 08 to 14:
Bits 00 to 07:
00
Send destination network address
Always 00 Hex
Stored in
EEPROM
Yes
No
No
No
No
No
No
No
Parity error
Framing error
Overrun error
No
No
No
FCS check error
Setting table logic error
Board/Unit error
CPU Bus Unit/Inner Board memory error
Always 00 Hex 03 Hex: Routing tables
05 Hex: CPU Bus Unit/
Inner Board DM Area
Parameter packet discarded Same contents as event send/receive errors.
Protocol macro operation error
01 Hex: Port 1
02 Hex: Port 2
No
Protocol macro error code No
Illegal protocol packet discarded.
01 Hex: Port 1
02 Hex: Port 2
Check the operating environment.
01 Hex: Read error
02 Hex: Write error
Always 00 Hex
06 Hex: Error log
07 Hex: Protocol data
No
No
No
Yes
No
349
Error Logs
Section 11-4
11-4-5 Error Codes and Troubleshooting
Error code
Troubleshooting
0001 Hex Replace the CPU Unit.
0002 Hex Check the operating environment.
0006 Hex Check the unit number setting.
Recreate the I/O tables.
000F Hex Check the operating environment.
0011 Hex Check the operating environment.
0012 Hex Check the relevant data.
0014 Hex Check the operating environment.
0108 Hex Check the unit number setting.
010B Hex Eliminate the cause of the error, referring to the CPU Unit’s operation manual.
If the error persists, replace the CPU Unit.
010D Hex Set the destination address in the routing tables.
010E Hex Set the destination address in the routing tables.
Yes
Yes
0112 Hex Make sure to use the FINS command addresses correctly.
0117 Hex Increase the number of retries or correct the system so that communications do not jam.
0118 Hex Check whether there is a node sending irregular data.
011B Hex Correct the transmission method and baud rate settings.
Check for noise interference.
011C Hex Correct the transmission method and baud rate settings.
Check for noise interference.
011D Hex Correct the transmission method and baud rate settings.
Check for noise interference.
No
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Protocol macro
Yes
Yes
Yes
Host
Link
Yes
Yes
Yes
Serial communications mode
Serial
Gateway
Yes
Yes
Yes
Noprotocol
Yes
Yes
Yes
1:N
NT
Link
Yes
Yes
Yes
Loopback test
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
Yes Yes No No No 011E Hex Correct the transmission method and baud rate settings.
Check for noise interference.
Check whether the FCS calculation method is correct.
021A Hex Reset the relevant table.
0300 Hex Conduct a loopback test, and eliminate the cause of the error.
0301 Hex Eliminate the cause of the error, referring to the processing of protocol macro error codes on page 343.
No
Yes
Yes
Yes
0302 Hex A new command is received during command processing. Correct the applications at the host computer.
0601 Hex Check the operating environment.
0602 Hex Depending on the error details, delete the error log and transfer protocol macro data.
If the error persists, replace the Board/Unit.
No
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Modbus-RTU
Slave
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
350
Error Logs
Section 11-4
Error code
Troubleshooting
0111 Hex Command too long
0122 Hex Service cannot be executed in current serial communications mode and was discarded.
0107 Hex There is no remote device.
No
Protocol macro
No
No
Host
Link
No
No
Serial communications mode
Serial
Gateway
Yes
Yes
Noprotocol
No
No
1:N
NT
Link
No
No
Loopback test
No
No
Modbus-RTU
Slave
No
No
No Yes No No No No
11-4-6 Reading and Clearing Error Log Tables
The error log table can be read or cleared by sending FINS commands to the
Serial Communications Board or Serial Communications Unit. Refer to the
CS/CJ-series Communications Command Reference Manual (W342) for details on FINS commands.
Set the send destination unit address for the FINS commands to the unit number of the Serial Communications Board or Serial Communications Unit, as follows:
Serial Communications Board: E1 hexadecimal
Serial Communications Unit: 10 hexadecimal + unit number
11-4-7 CONTROLLER DATA READ: 05 01
Reads the following data for the Serial Communications Board or Serial Communications Unit.
• Serial Communications Board or Unit Model
• Serial Communications Board or Unit Ver.
Command Format
05 01
Command code
Response Format
Parameters
05
01
20 bytes 20 bytes
Command code
End code Board/Unit
Model
Board/Unit
Version
Model, Version (Response)
The Serial Communications Board or Serial Communications Unit model and version are specified in the response each as ASCII data up to 20 bytes max.
If the data is less than 20 bytes, the remaining bytes will be expressed as 20 hexadecimal (space).
Model
CS1W-SCU21-V1
Board or Unit
CS-series Serial Communications Unit (two RS-232C ports)
CS-series Serial Communications Board (two RS-232C ports)
CS-series Serial Communications Board (one RS-232C and one RS-422A/485 port)
CS1W-SCB21-V1
CS1W-SCB41-V1
351
Error Logs
Section 11-4
Board or Unit
CJ-series Serial Communications Unit (two RS-232C ports)
CJ-series Serial Communications Unit (one RS-232C and one RS-422A/485 port)
Model
CJ1W-SCU21
CJ1W-SCU41
Version: "V1.00V1.00V1.00V1.00"
Trace function version
Macro function version
Board or Unit version
Communications control version
11-4-8 ERROR LOG READ: 21 02
This command reads the Board or Unit’s error log.
Command Format
21 02
Command code
Beginning record no.
No. of records
Response Format
21 02
10 bytes 10 bytes
Parameters
Command code
End code Max. no. of stored records
No. of stored records
No. of records
Error log data
Error log data
Beginning record number (command)
Specify the first record to be read as 2-byte (4-digit) hexadecimal. The first record number is 0000 Hex and the setting range is 0000 to 003F Hex (0 to 63 decimal).
Number of records (command, response)
Specify the number of records to read. The setting range is 0001 to 0040 Hex
(1 to 64 decimal). The number of read records will be returned with the response. If there is no error log, the response will be 0000.
Maximum number of stored records (response)
Indicates the maximum number of records that can be stored. The number is always 0040 Hex (64 records) for Serial Communications Boards and Units.
Number of stored records (response)
Indicates the number of records recorded at the time the command is executed. The number of stored records will be returned with the response within the range of 0000 to 0040 Hex (0 to 64 decimal).
When the FA command for Host Link communications is used to read the error log, set the number of stored records to between 0001 and 0035 Hex (1 to 53 decimal). Higher numbers cannot be set because they would cause the response to exceed the maximum Host Link frame length. If a larger number is set and the setting agrees with the actual number of stored records, 110B
Hex will be returned as the end code followed by all the records that can be returned without exceeding the maximum frame length.
352
Error Logs
Section 11-4
Error log data (response)
The specified number of error log records will be returned in sequence starting from the beginning record number. The total number of bytes for the error log data required is calculated as follows:
No. of records x 10 bytes
The configuration of each error log record is returned in 10 bytes, as follows:
10th byte 1st byte
07
01
Comments
Error code Details
Minute
Second
Day Hour Year Month
Error Code and Details
Indicates the error contents of the error recorded. Refer to 11-4-4 Error Codes
and Details.
Minute, Second, Day, Hour, Year, Month
Records the time the error occurred.
If the error log does not contain the specified number of records, the records up to the last recorded stored at the time the command was executed will be returned, and a normal response will be returned. The number of records actually read will be returned as the number of stored records.
If the beginning record is specified higher than the current number of records in the error log, an end code of 1103 Hex will be returned.
If the beginning record number is specified as 0000, the response will be completed normally, even if no error log is recorded.
If the number of records is set to 0000, the end code will be returned as 110C
Hex.
11-4-9 ERROR LOG CLEAR: 21 023
This command clears all stored error log records to 0.
Command Format
21 03
Command code
Response Format
Comments
21 03
Command code
End code
The ERROR LOG CLEAR: 21 03 command clears the error log records that are stored in the RAM error log table and the EEPROM error log table.
353
Cleaning and Inspection
Section 11-5
11-5 Cleaning and Inspection
Use the cleaning and inspection methods described here for daily maintenance of the devices.
11-5-1 Cleaning
To keep the Serial Communications Board in optimum condition, regularly clean the Board or Unit, as follows:
• Wipe the surface of the Board or Unit daily with a soft, dry cloth.
• If any dirt cannot be removed with a dry cloth, moisten the cloth with a mild detergent diluted to 2%, and squeeze out any excess moisture before wiping the Board or Unit.
• Do not adhere materials, such as gum, vinyl, or tape to the Board or Unit for long periods of time. Doing so may cause scratches on the device.
Remove any adhered materials when cleaning the Board or Unit.
Note Never use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths.
11-5-2 Inspection
Materials for Inspection
Inspection Items
To keep the Board or Unit in optimum condition, regular inspections must be performed. Normally, inspect the devices once every six months or every year.
Inspect the devices at more regular intervals when they are being used in environments subject to high temperatures, high humidity, or high dust levels.
Prepare the following materials before performing any inspections.
Materials Required Daily
For daily inspection, a Phillips screwdriver, flat-blade screwdriver, tester (or digital voltmeter), industrial strength alcohol, and all-cotton cloth are required.
Materials Required Occasionally
For some inspections, a synchroscope, a pen oscilloscope, a temperature gage, and a hydroscope will be required.
Inspect the following items to check whether the Board or Unit is operating within the specified criterion. If the Board or Unit is not within the criterion, improve the ambient operating environment and readjust the device.
Item
Operating environment
Installation
Details Criterion
Check the ambient temperature and the temperature of the control panel.
Check the ambient humidify and the humidity of the control panel.
Check for accumulated dust.
0 to 55
°C
10% to 90% RH
(no condensation or icing)
No dust
Check that the Board or Unit is mounted securely.
Check for loose screws on the communications cables.
Check for damaged communications cables.
Inspection materials
Temperature gage
Hydroscope
Visual inspection
--Board or Unit must be mounted securely.
Screws must be securely tightened.
Cables should be fully intact.
Phillips screwdriver
Visual inspection
354
Replacement Precautions
Section 11-6
11-6 Replacement Precautions
A malfunction of the Serial Communications Board or Serial Communications
Unit may affect the operation of remote communications devices, so be sure to perform repairs or replace the faulty Board or Unit promptly. Make sure a spare Serial Communications Board or Unit is available to replace a faulty one, so that functionality can be restored without delay.
11-6-1 Precautions when Replacing Board or Unit
Observe the following precautions when replacing the Serial Communications
Board or Serial Communications Unit.
• Always turn OFF the power to the PLC before replacing the Board or Unit.
• Be sure to check that the Board or Unit replacing the faulty one is not defective.
• If the defective Board or Unit is to be dispatched to the manufacturer for repair, be sure to include documentation stating the nature of the fault in as much detail as possible, and send to your nearest OMRON branch or sales office, listed at the back of this manual.
If the contacts are defective, clean the contacts with a clean all-cotton cloth moistened with industrial-strength alcohol. Remove any cloth particles before mounting the Board or Unit.
Note Turn OFF the power to all serial external devices when replacing the Board or
Unit to prevent malfunctions.
11-6-2 Settings after Replacing Board or Unit
After replacing the Serial Communications Board or Serial Communications
Unit, make sure that wiring and settings, such as hardware switch settings, the Unit/Board Setup, and protocol macro data are the same as the Board or
Unit that was replaced.
Note
1.
If the CPU Unit is to be replaced, transfer to the replacement CPU Unit the contents of the Holding Areas and DM Area required for operating the Unit before starting operation. If the relationship between the DM Area and
Holding Area and the program is not maintained, unexpected malfunctions may result.
2.
The System Setup of the Serial Communications Board or Unit is saved in the DM Area of the CPU Unit. If the CPU Unit is to be replaced, either transfer the System Setup data to the CX-Programmer before replacing the CPU Unit or reset the System Setup.
11-6-3 Replacing the Board or Unit
Standard System Protocols, Host Link Communications, or 1:N NT Links
1,2,3...
1.
Turn OFF the power to the PLC to which the Serial Communications Board or Unit to be replaced is mounted, and to all serially connected external devices.
2.
Disconnect the communications cables connected to the Serial Communications Board or Unit to be replaced, and also remove the Board or Unit.
3.
Set the hardware switches of the replacement Board or Unit to the same settings of the Board or Unit being replaced before mounting, as follows:
• CS1W-SCB21-V1: No setting switches.
• CS1W-SCB41-V1: Terminating resistance switch and 2/4-wire switch.
355
Replacement Precautions
Section 11-6
Protocol Macros Designed with CX-Protocol
Using CX-Protocol
1,2,3...
• CS1W-SCU21-V1:Unit number switch.
• CJ1W-SCU21: Unit number switch.
• CJ1W-SCU41: Unit number switch, terminating resistance switch, and 2/4-wire switch.
4.
Turn ON the power of the PLC to which the replacement Serial Communications Board or Unit is mounted, and to all serially connected external devices, and start operating the system.
5.
Check from the indicators and status display that the system is operating normally.
1.
Connect Programming Console or CX-Protocol to the PLC to which the replacement Serial Communications Board or Unit is mounted, and switch to
PROGRAM mode.
2.
Save the protocol macro data using the CX-Protocol. Refer to the CX-Pro-
tocol Operation Manual (W344) for details.
3.
Turn OFF the power to the PLC to which the Serial Communications Board or Unit to be replaced is mounted, and to all serially connected external devices.
4.
Disconnect the communications cables connected to the Serial Communications Board or Unit to be replaced, and also remove the Board or Unit.
5.
Set the hardware switches of the replacement Board or Unit to the same settings of the Board or Unit being replaced before mounting, as follows:
• CS1W-SCB21-V1: No setting switches.
• CS1W-SCB41-V1: Terminating resistance switch and 2/4-wire switch.
• CS1W-SCU21-V1:Unit number switch.
• CJ1W-SCU21: Unit number switch.
• CJ1W-SCU41: Unit number switch, terminating resistance switch, and 2/4-wire switch.
6.
Turn ON the power of the PLC to which the replacement Serial Communications Board or Unit is mounted, and to all serially connected external devices, and start operating the system.
7.
Switch the CPU Unit to PROGRAM mode, and using the CX-Protocol, transfer the protocol macro data to the Board or Unit. Refer to the CX-Pro-
tocol Operation Manual (W344) for details.
8.
Switch the CPU Unit to MONITOR mode, and start operating the system.
9.
Check from the indicators and status display that the system is operating normally.
Using the Simple Backup Function
This function can be used with a CS1-H or CJ1-H CPU Unit only.
1,2,3...
1.
Check the settings of pins 7 and 8 on the DIP switch on the front of the CPU
Unit. Turn ON pin 7 and turn OFF pin 8 to backup the protocol data from the Serial Communication Board/Unit to the Memory Card.
2.
Insert the Memory Card into the CPU Unit.
3.
Press and hold the Memory Card power supply switch for 3 seconds.
When the switch is pressed, the MCPWR Indicator on the front of the CPU
Unit will flash once and then remain lit while the data is being written. The
Indicator will go OFF after the data has been written properly.
356
Replacement Precautions
Section 11-6
4.
If necessary, compare the data in the Memory Card with the protocol data in the Serial Communication Board/Unit.
To compare the protocol data, turn OFF pins 7 and 8 on the DIP switch on the front of the CPU Unit and press the Memory Card power supply switch for 3 seconds. When the Memory Card power supply switch is pressed, the
MCPWR Indicator on the front of the CPU Unit will flash once and then remain lit while the data is being compared. If the data matches, the Indicator will go OFF after the data has been compared.
5.
Turn OFF the power to the PLC to which the Serial Communications Board or Unit to be replaced is mounted, and to all serially connected external devices.
6.
Disconnect the communications cables connected to the Serial Communications Board or Unit to be replaced, and also remove the Board or Unit.
7.
Set the hardware switches of the replacement Board or Unit to the same settings of the Board or Unit being replaced before mounting, as follows:
• CS1W-SCB21-V1: No setting switches.
• CS1W-SCB41-V1: Terminating resistance switch and 2/4-wire switch.
• CS1W-SCU21-V1: Unit number switch.
• CJ1W-SCU21: Unit number switch.
• CJ1W-SCU41: Unit number switch, terminating resistance switch, and 2/4-wire switch.
8.
To restore the protocol data from the Memory Card to the Serial Communications Board or Unit, turn ON pin 7 and turn OFF pin 8 on the DIP switch on the front of the CPU Unit for which the Board or Unit was replaced.
9.
Turn ON the PLC’s power supply. At this point, leave the power supplies
OFF to all serially connected external devices.
When the PLC’s power is turned ON, the MCPWR Indicator on the front of the CPU Unit will light and flash once. The MCPWR Indicator will remain lit while the data is being read. The Indicator will go OFF after the data has been read properly.
• Serial Communications Board Operation:
The Board’s RDY Indicator will flash during the restore operation and it will be lit when the restore operation is completed normally.
If the restore operation fails, the RDY Indicator will continue to flash.
The CPU Unit’s ERR/ALM Indicator will flash and bit A42409 (the Protocol Data Error Flag) will be turned ON.
• Serial Communications Unit Operation:
The Unit’s RDY Indicator will flash during the restore operation. Both the RDY Indicator and RUN Indicator will be lit when the restore operation is completed normally.
If the restore operation fails, the RDY Indicator will continue to flash and the ERC Indicator will be lit.
If the restore operation fails, return to step 1 and perform the replacement procedure again. If the restore operation fails two times in succession, use
CX-Protocol to transfer the protocol data to the Board. Refer to Using CX-
Protocol on page 356 for details.
10. If necessary, compare the data in the Memory Card with the protocol data in the Serial Communication Board/Unit.
To compare the protocol data, turn OFF the PLC’s power supply, turn OFF pins 7 and 8 on the DIP switch on the front of the CPU Unit, turn the PLC
357
Replacement Precautions
Section 11-6
Note
Precautions for Using the
Simple Backup Function
ON again, and press the Memory Card power supply switch for 3 seconds.
When the Memory Card power supply switch is pressed, the MCPWR Indicator on the front of the CPU Unit will flash once and then remain lit while the data is being compared. If the data matches, the Indicator will go OFF after the data has been compared.
11. Turn ON the power to all serially connected external devices, switch the
CPU Unit to MONITOR mode, and start the system.
12. Check the status of the Serial Communications Board or Unit’s indicators and status display and confirm that the system is operating normally.
1.
The protocol macro data for the Board or Unit is stored in the flash memory of the Board or Unit.
2.
When protocol macro data designed with the CX-Protocol is used, a backup of the protocol macro data created from the CX-Protocol must be transferred to the Board or Unit after replacing.
3.
The System Setup of the Serial Communications Board or Unit is allocated to the DM Area saved in the battery backup of the CPU Unit, and if the exclusively designed macro data is not used, the System Setup can be used as before, simply by setting the hardware.
When using the Simple Backup Function in CS1H/G-CPU
@@
H products of
Lot No. 011101 or earlier* combined with the Serial Communications Board
(CS1W-SCB
@@
-V1), proper backup will not be possible if the backup file
(BACKUPE1.PRM) remains in the Memory Card.
*Reading lot numbers
CS1H/G-CPU
@@H Lot No. 01 11 01 ...Produced November 1, 2001
Production day (in this example: 1)
Production month (in this example: 11)
Production year (in this example: 2001)
In order to use the Simple Backup Function in this combination, delete the backup file (BACKUPE1.PRM) inside the Memory Card, then execute the backup.
If backup is executed without deleting this backup file, the RDY LED and the
CPU Unit’s ERR/ARM LED will both flash, and t he Protocol Data Error Flag (bit
A42409) will turn ON with the restore operation. The
Serial Communications Board will also automatically delete the backup file (BACKUPE1.PRM).
358
Appendix A
Introduction
Appendices B the N provide information on the standard system protocols provided with the CX-Protocol, the
details on using PMCR(260).
Using Standard System Protocols
Standard system protocols can be executed merely by specifying the sequences number to be executed in the second operand of PMCR(260) and settings the data described in the appendices in the proper format starting at the word specified with the third operand of PMCR(260). The data received as a response to executing the sequence will be automatically stored starting at the word specified with the fourth operand of PMCR(260).
Procedure
1,2,3...
1.
Set the sequence number as a hexadecimal value in the second operand of PMCR(260).
2.
Specify the address of the first word containing the data required for the sequence as the third operand (S: First word of send data) of PMCR(260).
3.
Specify the address of the first word where respond data is to be stored as the fourth operand
(D: First receive data storage word) of PMCR(260). Unless there is a reason to specify otherwise, set 0000 Hex in D at the initial value.
Example
The following data would be used to execute sequence number 600 in the CompoWay/F Master Protocol for a transmission with ASCII conversion.
PMCR(260)
#0258
S
D
Communications sequence number 600 (0258 Hex)
S: Send Data Word Allocation (3rd Operand)
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node number
(Undefined)
SRC
Number of send bytes
Send data
Offset Contents (data format) Data
S+0
S+1
Number of send data words
(4 digits Hex)
(Undefined) Node No. (2 digits
BCD)
0005 to 00FA Hex (5 to 250 decimal)
00 to 99
S+2 MRC
(2 digits Hex)
S+3
SRC (2 digits Hex) Set the command code for the required ser-
Number of send bytes (4 digits Hex) vice
S+4 on
Send data (4-digit Hex)
Number of data bytes from the next byte after the command code until the byte just before the ETX. 0000 to 0492
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
359
Introduction
D: Receive Data Word Allocation (4th Operand)
Receive data storage words
+0
+1
Number of receive data words
Response code
Receive data
+2
Appendix A
Offset
D+0
D+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Response code (4 digits Hex)
D+2 on
Receive data (4-digit Hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here.
Standard System Protocols
The following 16 standard system protocols are provided with the CX-Protocol, Serial Communications Boards, and Serial Communications Unit.
Protocol name Function
CompoWay/F Master (See note.) Protocol for sending CompoWay/F commands as a Master to OMRON CompoWay/F slave components and receiving responses.
Host Link C-mode Command Master (See note.)
Host Link FINS Command Master
(See note.)
Protocol for sending C-mode (Host Link) commands to OMRON C-series or CS/CJseries PLCs used as slaves and receiving responses.
Protocol for sending Host Link FINS commands to OMRON CS/CJ-series or CVM1/
CV-series PLCs used as slaves and receiving responses.
Mitsubishi Computer Link Master
(A-compatible, 1C frame, model 1)
(See note.)
E5
@K Digital Controller Read
Protocol for sending Computer Link commands to Mitsubishi PLCs (Sequencer CPU) used as slaves and receiving responses.
E5
@K Digital Controller Write
E5ZE Temperature Controller
Read
Protocol for controlling an E5
@K Digital Controller via the Communications Board.
Procedures for reading the MV the operating parameter settings
Protocol for controlling an E5
@K Digital Controller via the Communications Board.
Procedures for writing set points and operating parameters.
Protocol for controlling an E5ZE Temperature Controller via the Communications
Board. Procedures for reading measured temperature and operating parameter settings.
E5ZE Temperature Controller
Write
E5
@J Temperature Controller
ES100
@ Controller
Digital Panel Meter
V500/V520 Bar Code Reader
3Z4L Laser Micrometer
F200/F300/F350 Visual Inspection Systems
Protocol for controlling an E5ZE Temperature Controller via the Communications
Board. Procedures for writing control temperatures and operating parameters.
Protocol for controlling a E5
@J Temperature Controller via the Communications
Board. Procedures for writing set points, reading output amounts, and reading/writing operating parameters.
Protocol for controlling an ES100
@ Controller via the Communications Board. Procedures for writing adjustment parameters, reading operation amounts, and writing/ reading operating parameters.
Protocol for controlling a Digital Panel Meter via the Communications Board. Procedures for writing comparison values and reading display values are set.
Protocol for controlling a Bar Code Reader via the Communications Board. Procedures for controlling the Bar Code Reader in remote mode, reading the data that has been read by the Bar Code Reader, and reading/writing operating parameters.
Protocol for controlling a Laser Micrometer via the Communications Board. Procedures for controlling the Laser Micrometer in remote mode, reading measured data, and writing/reading operating parameters.
Protocol for controlling a Visual Inspection System via the Communications Board.
Procedures for controlling the Visual Inspection System in remote mode, reading measured values, and writing/reading operating parameters.
360
Introduction
Protocol name
V600/V620 ID Controllers
Hayes modem AT commands
Note Unit ver. 1.2 or later only
Appendix A
Function
Protocol for controlling an ID Controller via the Communications Board. Procedures for performing Read/Write operations of the ID Controller and writing/reading operating parameters.
Protocol for controlling a Hayes modem (AT commands) via the Communications
Board. Procedures for initialization of the modem, dialing, data transmission, switching to escape mode, and disconnecting the line.
361
Introduction
Appendix A
362
Appendix B
CompoWay/F Master Protocol
The CompoWay/F Master Protocol is used to send CompoWay/F commands with the CS/CJ-series PLC serving as the host (master).
CompoWay/F
CompoWay/F is a protocol used by many OMRON components for serial communications. A host computer of a PLC can function as a host (master) to send CompoWay/F commands (message frames) to OMRON components, which function as slaves. The components will return responses to these commands. Using CompoWay/
F commands, the host can read/write data, settings, and operating status to control the operation of the components.
CompoWay/F has the following features.
• The same message frame format is used, eliminating the need for special protocols for each component.
The same commands can thus be used for serial communications with all CompoWay/F components.
• The CompoWay/F protocol conforms to OMRON’s standard FINS command protocol, providing compatibility with other networks and more flexible expansions in the future.
The CompoWay/F Master Protocol is provided as a standard system protocol to enable the CS/CJ-series PLC to execute read/write sequences for CompoWay/F commands.
System Configuration for Standard System Protocol
RS-232C Connections
CS/CJ-series PLC: Host
CompoWay/F response
RS-232C
OMRON CompoWay/F component: Slave
CompoWay/F command
RS-422A/486 Connections
CS/CJ-series PLC: Host
CompoWay/F response
RS-422A/485
CompoWay/F command
OMRON CompoWay/F components: Slaves
363
CompoWay/F Master Protocol
Appendix B
Communications Specifications
Item
Transmission path connections
Multipoint
Specification
Communications RS-232C, RS-422A/485, 4-wire half-duplex, 2-wire half-duplex
Synchronization Start-stop
Baud rate 1,200/2,400/4,800/9,600/19,200/38,400 bps
Default: 9,600 bps
Transmitted code ASCII
Data length 7 bits or 8 bits (Default: 7 bits)
Note: A 7-bit code is used with 0 added to the beginning.
Stop bits
Error detection
1 bit or 2 bits (Default: 2 bits)
Horizontal parity (none, even, or odd) (Default: Even)
BCC (block check character)
*1: Start-stop Sync Data Configuration for Protocol Macros
LRC, 1 byte, equivalent to binary
Transmission Procedure
The PLC or host computer serving as the master sends a command and the component serving as the slave returns a response for the command message contained in the command. One response message is returned for each command message. The movement of command and response messages is shown below.
Master (PLC or host computer)
Command message
Slave (component)
Response message
Command and Response Formats
Note In the following diagrams “Hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters.
Command Format
1 byte
Node No.
2 bytes
Subaddress
"00"
2 bytes
"0"
1 byte
Command
Text
Data
1 byte
1 byte
Response Format
1 byte
Node No.
2 bytes
Subaddress
End code
"00"
2 bytes
"00"
2 bytes
Response
Text
Data
(See note.)
1 byte 1 byte
Note 1.
Data is not saved in the response if there is a command frame error (i.e., if the end code is not 00 or
0F).
2.
Other values are possible for the subaddress and SID.
364
CompoWay/F Master Protocol
Appendix B
Command Frame Contents
STX
ETX
BCC
Item
Node number
Subaddress
SID
Command and text
MRC and SRC
Meaning
A code, 02 Hex, indicating the beginning of a communications frame
(text). This code must always be set as the first byte.
The node number identifies the source of the command frame. Specify “XX” to broadcast a transmission. There will be no response made to a broadcast.
Set “00” for most components. Other values must be set for special components.
Set “0” for most components. Other values must be set for special components.
The command and required text are placed here. Refer to the command codes and text for individual sequences.
The command code specifies the service being used. Refer to the command codes and text for individual sequences.
A code, 03 Hex, indicating the end of text.
The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX.
Response Frame Contents
Item Meaning
STX
Node number
Subaddress
SID
End code (.)
A code, 02 Hex, indicating the beginning of a communications frame
(text). This code must always be set as the first byte.
The node number identifies the source of the command frame. “XX” is specified to broadcast a transmission. There will be no response made to a broadcast.
“00” for most components. Other values must be set for special components.
“0” for most components. Other values must be set for special components.
The results of executing the command frame.
Note: The response code (MRES and SRES) indicates the results for the command code; the end code indicates the results for the command frame. These are not the same.
Response and text The response and requested text are placed here. Refer to the response and text for individual sequences.
MRES and SRES The response code specifies the results of processing the service requested by the command code. Refer to the response codes and text for individual sequences.
ETX
BCC
A code, 03 Hex, indicating the end of text.
The block check character (horizontal parity, 1 byte). The character is an exclusive OR of all data from just after the STX to the ETX.
Note The end codes are described in the following table.
End code
“00”
“0F”
“10”
“11”
“12”
“13”
“14”
“16”
“18”
Name Meaning
Normal end
Command error
Parity error
Framing error
Overrun error
BCC error
Format error
The command frame was processed normally without any of the following errors.
The specified command could not be executed. Refer to the response code for more information.
A parity error was detected for one of the characters that was received.
A framing error was detected for one of the characters that was received.
A overrun error was detected for one of the characters that was received.
The BCC for the receive frame was incorrect.
An illegal command or illegal character was received in the command and text (characters other than ASCII 0 to 9 or A to F).
Subaddress error The receive frame contained an illegal subaddress.
Frame length error The receive frame was too long.
365
CompoWay/F Master Protocol
Appendix B
Example
The command and response frames for a K3N
@-series Intelligent Signal Processor are shown below.
Command Frame
Node No.
Subaddress
Command
Text
SID
Data
Command
Command code
Command code
“01” “01” Variable type Address
Data contents
Data contents
VARIABLE AREA READ
VARIABLE AREA WRITE “01” “02” Variable type Address
“00” No. of elements
“00” No. of elements
No. of elements PARAMETER AREA READ
PARAMETER AREA WRITE
“02” “01” Parameter type
“02” “02” Parameter type
PROCESSOR STATUS READ “05” “03”
CONTROLLER STATUS READ “06” “01”
ECHOBACK TEST “08” “01” Text data
OPERATION COMMAND “30” “05” Command code
Address
Address
Response Format
No. of elements
Node No.
Subaddress End code
Response
Text
Write data
Write data
Data
Command code
Response code
366
CompoWay/F Master Protocol
Appendix B
Example: VARIABLE AREA READ
The following command and text are used to read the present value, maximum value, minimum value, and status of the Intelligent Signal Processor.
Command and Text
Variable type
First read address
No. of elements
2 bytes 2 bytes 2 bytes 4 bytes 4 bytes
1.
Variable Type
“C0”
Variable type Contents
Present value, maximum value, minimum value, status, and comparison value
2.
First Read Address
Specify the address of the data to be read in 4 digits Hex.
3.
Number of Elements: 4 Digits Hex
Number of elements
“0001”
Process
Read the data and end normally.
Note If “0000” is specified, nothing will be read and a normal end will be returned. A parameter error will occur for any settings other than “0000” and “0001.”
Response Text
2 bytes 2 bytes
Response code
4 bytes
1.
Response Code: MRES, SRES
Response code
“0000”
“1001”
“1002”
“1100”
“1101”
“1103”
“2203”
Read data
8 bytes
Normal end
Command too long
Command too short
Parameter error
Area type error
First address range error
Operating error
Meaning
2.
Read Data
The specified data is returned in 8 digits of hexadecimal data.
367
CompoWay/F Master Protocol
Appendix B
CompoWay/F Master Protocol Sequences
The CompoWay/F Master Protocol provides 18 communications sequences that can be used for the following:
• Converting to ASCII data or not converting to ASCII data
• Sending to a specified Unit or broadcasting
• Specifying from the command code or specifying from the subaddress and SID.
Structure of the Protocol
The following table shows the structure of the CompoWay/F Master Protocol.
Sequence
No.
Communications sequence name
Function
600 (0258) Send with ASCII conversion, with response
Send in order from rightmost to leftmost word.
Receive in order from leftmost to rightmost word.
601 (0259) Broadcast with ASCII conversion, no response
602 (025A) Send with no conversion and with response
603 (025B) Broadcast with no conversion and no response
604 (025C) General-purpose send with no conversion and with response
Converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
A broadcast version of sequence No. 600.
No responses are received.
Sends specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. This is the same as sequence No.
600 without data conversion and can be used when conversion is not required.
A broadcast version of sequence No. 602.
No responses are received.
Sends specified data beginning with the subaddress and SID to the specified Unit.
The response is stored starting at the specified word. This sequence can be used whenever it is necessary to specify the subaddress or SID.
A broadcast version of sequence No. 604.
No responses are received.
605 (025D) General-purpose broadcast with no conversion and no response
606 (025E) Send/receive with ASCII conversion and with response
Send: Leftmost to rightmost word order
Receive: Leftmost to rightmost word order
607 (025F) Send/receive with ASCII conversion and with response
Send: Rightmost to leftmost word order
Receive: Rightmost to leftmost word order
610 (0262) Variable area read
Converts specified data beginning with the command code (MRC, SRC) into ASCII and sends it to the specified Unit. The response is converted into hexadecimal and stored starting at the specified word.
Converts specified data beginning with the command code (MRC, SRC) into ASCII and sends it to the specified Unit. The response is converted into hexadecimal and stored starting at the specified word.
Reads the contents of the specified number of elements from the address of the specified variable type to the specified node number and stores the data starting at the specified word.
Ladder interface
Send word allocation
Yes
Receive word allocation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
368
CompoWay/F Master Protocol
Appendix B
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
Yes 611 (0263) Variable area write
612 (0264) Variable area broadcast send
613 (0265)
614 (0266) Variable area broadcast send
615 (0267)
616 (0268)
617 (0269)
618 (026A)
619 (026B)
620 (026C)
621 (026D)
Variable area fill
Parameter area read
Parameter area write
Parameter area broadcast write
Unit properties read
Unit status read
Echoback test
Operation command
Writes the contents of the specified number of elements from the address of the specified variable type to the specified node number.
Writes the specified number of elements from the address of the specified variable type using a broadcast address.
Writes the same data from the address of the specified variable type to the specified node number.
Writes the same data from the address of the specified variable using a broadcast address.
Reads the contents of the specified number of elements from the address of the specified parameter area to the specified node number and stores the data starting at the specified word.
Writes the contents of the specified number of elements from the address of the specified parameter area to the specified node number.
Writes the specified number of elements from the address of the specified parameter area using a broadcast address.
Reads the Controller/component model and communications buffer size and stores the data starting at the specified word.
Reads the Controller/component status and stores the data starting at the specified word.
Executes an echoback test at the specified node.
Remotely stops/starts operations of the device at the specified node number.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
No
Yes
Yes
Yes
Yes
Note The hexadecimal equivalents of sequences numbers are given in parentheses.
Sequence No. 600 can be used for the normal CompoWay/F Master function (ASCII conversion, specification from command code).
Refer to the communications specifications for the OMRON CompoWay/F component to which the command is being sent and set the command code and required data starting at the words specified for the 3rd operand of
PMCR(260).
The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is described next.
369
CompoWay/F Master Protocol
Appendix B
CompoWay/F Message Frames and PMCR(260) Operands
The relationship between the CompoWay/F command and response frames and the operands of PMCR(260) is shown below, using communications sequence No. 600 as an example.
Command Frame
Variable type
First read address
No. of elements
Node No.
Subaddress
Command
Send data
PMCR(260) Instruction
Communications sequence No. 600 (0258 Hex)
Number of send data words
S
S+1
S+2
S+3
S+4
S+5
S+6
(Undefined) Node number
Number of send bytes
Send data
Response Frame
Node No.
Subaddress End code
Response code
Response code
Receive data
Read data
Receive data
PMCR(260) Instruction
D
D+1
D+2
D+3
Number of receive data words
Response code
Receive data
Send/Receive with ASCII Conversion and with Response
The following three communications sequences are available for send/receive with ASCII conversion and response.
Send sequence Receive sequence Sequence
No.
600 (0258) Send word order: Rightmost to leftmost Receive word order: Leftmost to rightmost
Rightmost word
Send data words
1 2 3 4
Leftmost word 5 6 7 8
Send frame
"12" "34" "56" "78"
Receive frame
"12" "34" "56" "78"
Receive data words
5 6 7 8
Rightmost word
1 2 3 4
Leftmost word
370
CompoWay/F Master Protocol
Appendix B
Sequence
No.
Send sequence
606 (025E) Send word order: Leftmost to rightmost
Rightmost word
Send data words
1 2 3 4
Leftmost word
5 6 7 8
Receive sequence
Send frame
"56" "78" "12" "34"
Receive word order: Leftmost to rightmost
Receive frame
"12" "34" "56" "78"
Receive data words
5 6 7 8
Rightmost word
1 2 3 4
Leftmost word
607 (025F) Send word order: Rightmost to leftmost
Rightmost word
Send data words
1 2 3 4
Leftmost word
5 6 7 8
Send frame
"12" "34" "56" "78"
Receive word order: Rightmost to leftmost
Receive frame
"12" "34" "56" "78"
Receive data words
1 2 3 4
Rightmost word
5 6 7 8
Leftmost word
Send with ASCII Conversion, with Response:
(Sequence No. 600 (Hex 0258))
• Send word order: Rightmost to leftmost
• Receive word order: Leftmost to rightmost
This sequence converts the specified data beginning with the command code to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
Node No.
MRC
SRC
Number of send bytes
Send data
+4
Offset Contents (data format) Data
+0
+1
Number of send data words
(4 digits Hex)
(Undefined) Node No. (2 digits
BCD)
0005 to 00FA Hex (5 to 250 decimal)
00 to 99
+2 MRC
(2 digits Hex)
+3
SRC (2 digits Hex) Set the command code for the required ser-
Number of send bytes (4 digits Hex) vice
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0000 to 03D8 Hex (0 to 984 decimal)
+4 on
Send data (4-digit Hex) The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
Note 1.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent.
2.
Frames are created and sent starting from the rightmost to leftmost word of the address in I/O memory.
Send data words
1 2 3 4
5 6 7 8
Send frame
"12" "34" "56" "78"
371
CompoWay/F Master Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Receive data
Appendix B
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Response code (4 digits Hex)
+2 on
Receive data (4-digit Hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX will be converted from ASCII to hexadecimal and stored here.
Note Received frames are stored starting from the leftmost to rightmost word of the address in I/O memory.
Receive frame
"12" "34" "56" "78"
Receive data words
5 6 7 8
1 2 3 4
Example: The following example illustrates reading the present value from a K3N
@-series Intelligent Signal
Processor.
CS/CJ-series PLC
CompoWay/F response
Read data = present value
CompoWay/F command
VARIABLE AREA READ
Command code: 01 01
First read address
Intelligent Signal Processor
K3N
#-####-FLK1/2/3/4/5/6
Sequence No. 600 (Send with ASCII Conversion, with Response) is used. The specified data beginning with the command code is converted ASCII and sent to the Intelligent Signal Processor with the specified node number. The response is converted to hexadecimal and stored starting at the specified word.
The command frame for reading the present value for a K3N
@-@@@@-FLK1/2/3/4/5/6 Intelligent Signal Processor (command code 01 01) is shown below. The following data is specified in the operands for PMCR(260).
• Rightmost byte of S+1: Node number (2 digits BCD)
• S+2: Command code: MRC + SRC = “0101”
• S+4 on: Send data = Variable type + first read address + 00 + number of elements.
STX Node No.
Subaddress
(02 Hex) (
×10
1
) (
×10
1
) 00 0
SID Command code
MRC SRC
01 01
Variable type
C0
Send data
First read address
(Note)
Always
00
No. of elements
0000 00 0001
ETX
(03 Hex)
BCC
Data in shaded portions is specified in the PMCR(260) instruction.
Note A first read address of 0000 specifies the present value. An address of 0001 specifies the maximum value; 0002, the minimum value; and 0003, the status.
The response frame is shown below. The response code and receive data are stored according to the operands for PMCR(260) as follows:
372
CompoWay/F Master Protocol
Appendix B
• D+1: Response code
• D+2 and on: Receive data
STX Node No.
Subaddress
End code
Command code
MRC SRC
Response code
Note 1
Receive data
Read data
(Note 2)
ETX
(02 Hex) (
×10
1
) (
×10
1
) 01 01 00 00 0000 (03 Hex)
Data in shaded portions is stored at the location specified by the operand in the PMCR(260) instruction.
Note 1.
Response Codes
Response code
“0000”
“1001”
“1002”
“1100”
“1101”
“1103”
“2203”
Normal end
Command too long
Command too short
Parameter error
Area type error
First address range error
Operating error
Meaning
BCC
2.
The read data is returned as 4-digit hexadecimal as follows: F0019999 to 00099999 Hex.
The 3rd and 4th operands of the PMCR(260) instruction are specified as follows.
Send Data Word Allocation (3rd Operand of PMCR(260))
Offset Contents (data format)
+3
+4
+5
+6
+0
+1
Number of send data words
(4 digits Hex)
(Undefined)
+2 MRC
(2 digits Hex)
0007 Hex
Node No. (2 digits
BCD)
0000 Hex
SRC (2 digits Hex) 0101 Hex
Number of send bytes (4 digits BCD)
Send data (12 digits Hex)
000C Hex
C000 Hex
0000 Hex
0001 Hex
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Response code (4 digits Hex)
+2
+3
Receive data (8 digits Hex)
Data
EX is stored at reception (0004 Hex)
The response code will be stored in hexadecimal form.
The normal end response code is 0000.
The 4 bytes of read data.
373
CompoWay/F Master Protocol
Appendix B
Broadcast with ASCII Conversion, No Response
(Sequence No. 601 (Hex 0259))
This sequence converts the specified data beginning with the command code to ASCII and broadcasts it. No responses are received.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
MRC
SRC
Number of send bytes
Send data
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
(Undefined) +1
+2 MRC
(2 digits Hex)
+3
SRC
(2 digits Hex)
Number of send bytes (4 digits Hex)
+4 on
Send data (4-digit Hex)
Data
0005 to 00FA Hex (5 to 250 decimal)
---
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0000 to 03D8 Hex (0 to 984 decimal)
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent.
Note 1.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent.
2.
When hexadecimal data is converted to ASCII data, data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 4-byte units.
Send data words
1 2 3 4
5 6 7 8
Send frame
"56" "78" "12" "34"
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
Send with No Conversion and with Response
(Sequence No. 602 (Hex 025A))
This sequence sends the specified data beginning with the command code to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node No.
MRC SRC
Number of send bytes
Send data
374
CompoWay/F Master Protocol
Appendix B
Offset Contents (data format) Data
+0
+1
Number of send data words
(4 digits Hex)
(Undefined) Node No. (2 digits
BCD)
+2 MRC
(2 digits Hex)
SRC
(2 digits Hex)
+3 Number of send bytes (4 digits Hex)
+4 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
0005 to 00FA Hex (5 to 250 decimal)
00 to 99
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0000 to 01EC Hex (0 to 492 decimal)
The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Response code (4 digits Hex)
+2 on
Receive data (Hex)
+0
+2
+1
+3
+4
+6 etc.
+5
Data
0003 to 00FA Hex (3 to 250 decimal)
The response code will be stored in hexadecimal form.
The data from just after the response code until just before the ETX is stored here without conversion.
Broadcast with No Conversion and No Response
(Sequence No. 603 (Hex 025B))
This sequence broadcasts the specified data beginning with the command code No responses are received and no conversions are performed on the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
MRC
SRC
Number of send bytes
Send data
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
(Undefined) +1
+2 MRC
(2 digits Hex)
+3
SRC
(2 digits Hex)
Number of send bytes (4 digits Hex)
Data
0005 to 00FA Hex (5 to 250 decimal)
---
Set the command code for the required service
Number of data bytes from the next byte after the command code until the byte just before the ETX.
0000 to 01EC Hex (0 to 492 decimal)
375
CompoWay/F Master Protocol
Appendix B
Offset
+4 on
Contents (data format)
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
Data
The data specified in hexadecimal here is not converted and the number of bytes specified in S+3 is sent.
General-purpose Send with No Conversion and with Response
(Sequence No. 604 (Hex 025C))
This sequence sends the specified data beginning with the subaddress and SID to the specified Unit. The response is stored starting at the specified word. No conversions are performed on the send and receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node No.
(Undefined)
Subaddress
(Undefined)
SID
Number of send bytes
+5
Send data
Offset Contents (data format) Data
+0
+1
Number of send data words
(4 digits Hex)
Always 00 Hex Node No. (2 digits
BCD)
+2 MRC
(2 digits Hex)
+3 Always 00 Hex
Subaddress
(2 digits Hex)
SID (1 digit Hex)
+4
+5 on
Number of send bytes (4 digits Hex)
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
0006 to 00FA Hex (6 to 250 decimal)
00 to 99
Specify the subaddress of the device being communicated with.
Set the service ID of the required service
(e.g., retries).
Number of data bytes from the MCR until the byte just before the ETX.
0000 to 01EA Hex (0 to 490 decimal)
The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2
Response data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Response code (4 digits Hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
The response code will be stored in hexadecimal form.
376
CompoWay/F Master Protocol
Appendix B
Offset
+2 on
Contents (data format)
Receive data
+0
+2
+4
+6 etc.
+1
+3
+5
Data
The data from just after the response code until just before the ETX is stored here without conversion.
General-purpose Broadcast with No Conversion and No Response
(Sequence No. 605 (Hex 025D))
This sequence broadcasts the specified data beginning with the subaddress and SID. No responses are received and no conversions are performed on the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
(Undefined)
Subaddress
(Undefined)
SID
Number of send bytes
+5
Send data
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
Always 0000 Hex +1
+2 MRC
(2 digits Hex)
+3 Always 00 Hex
Subaddress
(2 digits Hex)
SID (1 digit Hex)
+4 Number of send bytes (4 digits Hex)
Data
0006 to 00FA Hex (6 to 250 decimal)
---
Specify the subaddress of the device being communicated with.
Set the service ID of the required service
(e.g., retries).
Number of data bytes from the MCR until the byte just before the ETX.
0000 to 01EA Hex (0 to 490 decimal)
The data specified in hexadecimal here is not converted and the number of bytes specified in S+4 is sent.
+5 on
Send data
+0
+2
+4
+6 etc.
+1
+3
+5
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
377
CompoWay/F Master Protocol
Appendix B
Connections
Connection methods between a Serial Communications Board or Unit and the K3N
@-series Intelligent Signal
Processor are shown below.
RS-232C
• RS-232C connections are one-to-one.
• The max. cable length is 15 m. Use an RS-232C optical interface (Z3RN) when extending the transmission line beyond 15 m.
• Use shielded, twisted-pair cable.
Serial Communications
Unit/Board
RS-232C
Abbreviation
Pin
No.
FG 1
SG
SD
9
2
RD
RTS
CTS
DSR
5
7
3
4
DTR 8
Shield
5
6
3
4
Intelligent
Signal
Processor
RS-232C
Pin
No.
Abbreviation
1 FG
7
2
SG
SD
RD
RTS
CTS
DSR
MAX232C or equivalent
20 DTR
K3N
#-####-FLK1
TX
RX
Serial
Communications
Unit/Board
RS-232C
Abbreviation
SG
SD
RD
RTS
CTS
DSR
DTR
Pin
No.
9
2
3
4
5
7
8
FG
1/
Shell
Shield
2
7
8
6
4
5
3
Intelligent
Signal
Processor
RS-232C
Pin
No.
Abbreviation
SG
SD
RD
RTS
CTS
DSR
DTR
MAX232C or equivalent
K3N
#-####-FLK4
TX
RX
378
CompoWay/F Master Protocol
Appendix B
RS-422 4-wire Connections
• RS-422 connections can be one-to-one, or one-to-N when a 3G2A9-AL001 Link Adapter is used. A maximum of 32 Serial Communications Boards and Unit can be connected in one-to-N systems.
• The total cable length can be 500 m max.
• Use shielded, twisted-pair cable.
• Be sure to turn ON the terminating resistance switches at the device at each end of the transmission line.
Serial Communications Board/Unit
RS-422
Abbreviation
Intelligent Signal
Processor
SN751177N or equivalent
Pin
No.
Abbreviation
220
Ω
Terminal block switch
Shell
6
8
1
2
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
Shield
220
Ω
The terminator (220
Ω) is set with the terminal block switch.
RS-485 2-wire Connections
• RS-485 connections can be one-to-one or one-to-N. A maximum of 32 Serial Communications Units/
Boards can be connected in one-to-N systems.
• The total cable length can be 500 m max.
• Use shielded, twisted-pair cable.
• Be sure to turn ON the terminator switches only in the devices at each end of the transmission line.
Serial Communications Board/Unit
RS-485
Abbreviation
Shell
1
2
Intelligent Signal Processor
Turn OFF all terminal block switches except at the end-station.
Terminal
Abbrevi ation
220
Ω
Terminal block switch
+
SN751177N or equivalent
Shield
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Intelligent Signal
Processor end-station
Terminal
Abbrevi ation
220
Ω
Terminal block switch ON
+
Terminal block switch ON at the end station.
Shield
Note SYSMAC BUS Wired Remote I/O devices cannot be connected.
Send/Receive with ASCII Conversion, with Response:
(Sequence No. 606 (Hex 025E))
• Send word order: Leftmost to rightmost
• Receive word order: Leftmost to rightmost
This sequence converts the specified data beginning with the command code (MRC, SRC) to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
379
CompoWay/F Master Protocol
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node No.
MRC
SRC
Number of send bytes
Send data
Appendix B
Offset
+0
+1
+2
+3
+4 on
Contents (data format) Data
Number of send data words
(4 digits Hex)
(Undefined) Node No.
(2 digits BCD)
0005 to 00FA hex (5 to 250 decimal)
00 to 99
MRC (2 digits hex) SRC (2 digits hex) Set the command code for the required service
Number of send bytes (4 digits hex)
Send data (4 digits hex)
Number of data bytes from the next byte after the command code (MRC, SRC) until the byte just before the ETX.
0000 to 03D8 hex (0 to 984 decimal)
Note: The data is converted to ASCII in the communications line, so the number of data bytes is doubled from S+4 and onwards.
The data specified in hexadecimal here will be converted to ASCII and the number of bytes specified in S+3 will be sent in word order from the leftmost to the rightmost word.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. The frames are created and sent in order from the leftmost word to rightmost word of the I/O memory address.
Send data words
1 2 3 4
5 6 7 8
Send frame
"56" "78" "12" "34"
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Response code
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
Response code (4 digits hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
+2 on
Receive data (4 digits hex)
The CompoWay/F command response code will be stored in hexadecimal code
The data from just after the response code until just before the ETX is converted from
ASCII to hexadecimal and stored in order from the leftmost word to the rightmost word.
The received frames are stored in order from the leftmost word to rightmost word of the I/O memory address.
Receive frame
"12" "34" "56" "78"
Receive data words
5 6 7 8
Rightmost word
1 2 3 4
Leftmost word
380
CompoWay/F Master Protocol
Appendix B
Send/Receive with ASCII Conversion with Response
(Sequence No. 607 (Hex 025F))
• Send word order: Rightmost to leftmost
• Receive word order: Rightmost to leftmost
This sequence converts the specified data beginning with the command code (MRC, SRC) to ASCII and sends it to the specified Unit. The response is converted to hexadecimal and stored starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Node No.
MRC
SRC
Number of send bytes
Send data
Offset
+0
+1
+2
+3
+4 on
Contents (data format) Data
Number of send data words
(4 digits hex)
(Undefined) Node No.
(2 digits BCD)
0005 to 00FA hex (5 to 250 decimal)
00 to 99
MRC (2 digits hex) SRC (2 digits hex) Set the command code for the required service
Number of send bytes (4 digits hex)
Send data (4 digits hex)
Number of data bytes from the next byte after the command code (MRC, SRC) until the byte just before the ETX.
0000 to 03D8 hex (0 to 984 decimal)
Note: The data is converted to ASCII in the communications line, so the number of data bytes is doubled from S+4 and onwards.
The data specified in hexadecimal here will be converted to ASCII and the number of send bytes specified in S+3 will be sent in word order from the rightmost to the leftmost word.
Set the number of send bytes to twice the number of bytes in memory. This is necessary because the data is converted to ASCII data before being sent. The frames are created and sent in order from the rightmost word to leftmost word of the I/O memory address.
Send data words
1 2 3 4
5 6 7 8
Send frame
"12" "34" "56" "78"
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Response code
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
+2 Receive data (4 digits hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The data from just after the response code until just before the ETX is converted from
ASCII to hexadecimal and stored in order from the rightmost word to the leftmost word.
381
CompoWay/F Master Protocol
Appendix B
The received frames are stored in order from the rightmost word to leftmost word of the I/O memory address.
Receive frame
"12" "34" "56" "78"
Receive data words
1 2 3 4
Rightmost word
5 6 7 8
Leftmost word
Variable Area Read
(Sequence No. 610 (Hex 0262))
This sequence reads the contents of the specified number of elements from the address of the specified variable type to the specified node number and stores the data starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Variable type
First read address
Node No.
Number of elements
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(Undefined) Node No. (2 digits BCD)
Variable type
(2 digits hex)
First read address (6 digits BCD)
Number of elements
(4 digits BCD)
Data
Always 0005 hex (5 decimal)
00 to 99
Set the area type (2 digits) and the first read word (6 digits). The leftmost 16 bits of the first read word specify the address and the rightmost 8 bits specify the bit location. Set the rightmost 8 bits to 00 when bit access is not required.
Set the number of elements to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Response code
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
Data
0003 to 00FA Hex (3 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The read data is stored.
+2 on
Receive data (4 digits hex)
The received frames are stored in order from the leftmost word to the rightmost word of the I/O memory address.
Receive frame
"12" "34" "56" "78"
Receive data words
1 2 3 4
Rightmost word
5 6 7 8
Leftmost word
382
CompoWay/F Master Protocol
Appendix B
Variable Area Write
(Sequence No. 611 (Hex 0263))
This sequence writes the contents of the specified number of elements from the address of the specified variable type to the specified node number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+4
+5
+6
+0
+1
+2
+3
Number of send data words
(Undefined)
Variable type
First write address
Node No.
Number of elements
Number of bytes to write
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Variable type
(2 digits hex)
First write address (6 digits BCD)
+4
Data
0007 to 00FA hex (7 to 250 decimal)
00 to 99
Set the area type (2 digits) and the first read word (6 digits). The leftmost byte of the first write address specifies the address and the rightmost byte specifies the bit location. Set the rightmost byte to 00 when bit access is not required.
Set the number of elements to write.
+5
Number of elements
(4 digits BCD)
Number of bytes to write
(4 digits hex)
+6 on
Write data
Set
the number of bytes to send in the communications line.
Note: The data is converted to ASCII in the communications line, so the number of data bytes is doubled from S+6 and onwards.
Set the data to write from the first write address.
Set the number of write bytes to twice the number of send data in memory. This is necessary because the data is converted to ASCII data before being written. When hexadecimal data is converted to ASCII data, data in the first write address +0 and +1 is stored in I/O memory in order from the rightmost word to leftmost word and the data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 2-word (4-byte) units.
4
3
2
1
Send data words
0 0 0 3
0 0 0 2
0 0 0 1
0 0 0 0
Send frame
1 2
0 0 0 0 0 0 0 1
3
0 0 0 2
4
0 0 0 3
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
383
CompoWay/F Master Protocol
Appendix B
Variable Area Broadcast Send
(Sequence No. 612 (Hex 0264))
This sequence writes the specified number of elements from the address of the specified variable type using a broadcast address.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Variable type
First write address
Number of elements
Number of bytes to write
+6
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Variable type
(2 digits hex)
First write address (6 digits BCD)
+4
Data
0007 to 00FA hex (7 to 250 decimal)
---
Set the area type (2 digits) and the first read word (6 digits). The leftmost byte of the first write address specifies the address and the rightmost byte specifies the bit location. Set the rightmost byte to 00 when bit access is not required.
Set the number of elements to write.
+5
+6 on
Number of elements
(4 digits BCD)
Number of bytes to write
(4 digits hex)
Write data
Set
the number of write bytes to send.
Note: The data is converted to ASCII in the communications line, so the number of data bytes is doubled from S+6 and onwards.
Set the data to write from the first write address.
Set the number of write bytes to twice the number of send data in memory. This is necessary because the data is converted to ASCII data before being written. When hexadecimal data is converted to ASCII data, data in the first write address +0 and +1 is stored in I/O memory in order from the leftmost word to the rightmost word and the data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 2-word (4-byte) units.
4
3
2
1
Send data words
0 0 0 3
0 0 0 2
0 0 0 1
0 0 0 0
Send frame
1 2
0 0 0 0 0 0 0 1
3
0 0 0 2
4
0 0 0 3
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
384
CompoWay/F Master Protocol
Appendix B
Variable Area Fill
(Sequence No. 613 (Hex 0265))
This sequence writes the same data from the address of the specified variable type to the specified node number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+5
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Variable type
Node No.
First write address
Number of elements
Number of bytes to write
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Variable type
(2 digits hex)
First write address (6 digits BCD)
Number of elements
(4 digits BCD)
Number of bytes to write
(4 digits hex)
Data
Always 0006 hex (6 decimal)
00 to 99
Set the area type (2 digits) and the first read word (6 digits). The leftmost byte of the first write address specifies the address and the rightmost byte specifies the bit location. Set the rightmost byte to 00 when bit access is not required.
Set the number of elements to write.
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
Variable Area Broadcast Send
(Sequence No. 614 (Hex 0266))
This sequence writes the same data from the address of the specified variable using a broadcast address.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Variable type
First write address
Number of elements
Write data
385
CompoWay/F Master Protocol
Appendix B
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined)
Variable type
(2 digits hex)
First write address (6 digits BCD)
Data
Always 0006 hex (6 decimal)
---
Set the area type (2 digits) and the first read word (6 digits). The leftmost byte of the first write address specifies the address and the rightmost byte specifies the bit location. Set the rightmost byte to 00 when bit access is not required.
Set the number of elements to write.
+4
+5
Number of elements
(4 digits BCD)
Write data (4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
Set the write data.
Parameter Area Read
(Sequence No. 615 (Hex 0267))
This sequence reads the contents of the specified number of elements from the address of the specified parameter area to the specified node number and stores the data starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
Parameter type
Node No.
First read address
Number of elements
+2
+3
+4
Offset
+0
+1
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Parameter type (4 digits hex)
Data
Always 0006 hex (6 decimal)
00 to 99
Set the parameter type.
First read address (4 digits hex) Set the first read address.
Number of elements (4 digits hex) Set the number of elements to read.
(The leftmost bit in the number of elements is always 1.)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
Response code
Variable type
First read address
Number of elements
Read data
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
Data
0006 to 00FA Hex (6 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
386
CompoWay/F Master Protocol
Appendix B
Offset
+2
Contents (data format)
Variable type (4 digits hex)
+4
+5
First read address
(4 digits hex)
Read data
(4 digits hex)
Data
The parameter type is stored in hexadecimal code.
The first read address is stored in hexadecimal code.
The read data is stored.
The received frames are stored in order from the leftmost word to the rightmost word of the I/O memory address.
Receive frame
"12" "34" "56" "78"
Receive data words
1 2 3 4
Rightmost word
5 6 7 8
Leftmost word
Parameter Area Write
(Sequence No. 616 (Hex 0268))
This sequence writes the contents of the specified number of elements from the address of the specified parameter area to the specified node number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
(Undefined)
Parameter type
Node No.
First write address
Number of elements
Number of bytes to write
Write data
+2
+3
+4
Offset
+0
+1
+5
+6 on
Contents (data format) Data
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Parameter type (4 digits hex)
First write address (4 digits hex)
0007 to 00FA Hex (7 to 250 decimal)
00 to 99
Set the parameter type.
Set the first write address.
Number of elements (4 digits hex) Set the number of elements to write.
(The leftmost bit in the number of elements is always 1.)
Number of bytes to write
(4 digits hex)
Write data
Set the number of bytes of write data to send in hexadecimal code.
Set the data to write from the first write address.
Set the number of write bytes to twice the of the actual number of send data bytes. This is necessary because the data is converted to ASCII data before being written. When hexadecimal data is converted to ASCII data, data in the first write address +0 and +1 is stored in I/O memory in order from the leftmost word to the rightmost word and the data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 2-word (4-byte) units.
2
1
4
3
Send data words
0 0 0 3
0 0 0 2
0 0 0 1
0 0 0 0
Send frame
1 2
0 0 0 0 0 0 0 1
3
0 0 0 2
4
0 0 0 3
387
CompoWay/F Master Protocol
Appendix B
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Offset
+0
+1
Number of receive data words
Response code
Contents (data format)
Number of receive data words
Response code (4 digits hex)
Data
Always 0002 Hex (2 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
Parameter Area Broadcast Send
(Sequence No. 617 (Hex 0269))
This sequence writes the specified number of elements from the address of the specified parameter area using a broadcast address.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
(Undefined)
Parameter type
First write address
Number of elements
Number of bytes to write
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
Contents (data format)
Number of send data words
(Undefined)
Parameter type (4 digits hex)
Data
0007 to 00FA Hex (7 to 250 decimal)
---
Set the parameter type in hexadecimal code.
First write address (4 digits hex) Set the first write address in hexadecimal code.
Number of elements (4 digits hex) Set the number of elements to write in hexadecimal code.
(The leftmost bit in the number of elements is always 1.)
Number of bytes to write
(4 digits hex)
Write data
Set the number of bytes of write data to send in hexadecimal code.
Set the data to write from the first write address.
Set the number of write bytes to twice the of the actual number of send data bytes. This is necessary because the data is converted to ASCII data before being written. When hexadecimal data is converted to ASCII data, data in the first write address +0 and +1 is stored in I/O memory in order from the leftmost word to the rightmost word and the data is sent starting from the send data word with the largest offset. This is done because ladder programming handles data in 2-word (4-byte) units.
4
3
2
1
Send data words
0 0 0 3
0 0 0 2
0 0 0 1
0 0 0 0
Send frame
1 2
0 0 0 0 0 0 0 1
3
0 0 0 2
4
0 0 0 3
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
388
CompoWay/F Master Protocol
Appendix B
Unit Properties Read
(Sequence No. 618 (Hex 026A))
This sequence reads the Controller/component model and communications buffer size and stores the data starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+0
+1
Number of send data words
(Undefined)
Node No.
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Data
Always 0002 hex (2 decimal)
00 to 99
Receive Data Word Allocation (4th Operand of PMCR(260))
+2
+3
+4
+5
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
Response code
Model number
Buffer size
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
(Undefined)
Model number (10 digits hex
Data
Always 0006 Hex (6 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The model number is stored in hexadecimal code.
(Undefined)
Buffer size (4 digits hex) The send/receive buffer size is stored in hexadecimal code.
Controller Status Read
(Sequence No. 619 (Hex 026B))
This sequence reads the Controller/component status and stores the data starting at the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+0
+1
Number of send data words
(Undefined)
Node No.
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Data
Always 0002 hex (2 decimal)
00 to 99
389
CompoWay/F Master Protocol
Appendix B
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Response code
Run status
Error status, etc.
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
+3
(2 digits hex)
Error status, etc.
Data
0003 to 00FA hex (3 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The run status, error status, and other status information is stored in hexadecimal code.
Echoback Test
(Sequence No. 620 (Hex 026C))
This sequence executes an echoback test at the specified node.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3 on
Number of send data words
(Undefined)
Node No.
Number of bytes to send
Test data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Node No.
(2 digits BCD)
Number of bytes to send
(4 digits hex)
Data
0004 to 00FA Hex (4 to 250 decimal)
00 to 99
0001 to 007A Hex (1 to 122 decimal)
Set the number of data bytes for the test.
The test data is sent.
+3 on
Test data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Response code
Test data
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
+2 Test data
Data
0003 to 00FA hex (3 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The test data is stored.
390
CompoWay/F Master Protocol
Appendix B
Operation Command
(Sequence No. 621 (Hex 026D))
This sequence remotely stops/starts operations of the device at the specified node number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Node No.
Number of send data bytes
+3 Command code
+4
Related information
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined)
(00 hex)
Node No.
(2 digits BCD)
Number of bytes to send
(4 digits hex)
+3
+4
Command code
(2 digits hex)
Related information
Data
0004 to 00FA Hex (4 to 250 decimal)
00 to 99
Set the number of send bytes for related information (Set to 0002 hex when there is no related information.)
Set the command code and related information.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Response code
+2 Command code
Related information
Offset
+0
+1
Contents (data format)
Number of receive data words
Response code (4 digits hex)
+2
+3
Command code
(4 digits hex)
Related information
Data
0003 to 00FA hex (3 to 250 decimal)
The CompoWay/F command response code is stored in hexadecimal code.
The command code and related information are stored.
391
CompoWay/F Master Protocol
Appendix B
392
Appendix C
C-mode (Host Link) Command Master
The C-mode (Host Link) command master protocol provides communications sequences using C-mode command codes for a PLC (CS/CJ Series) host (master).
This protocol enables any C-mode command to be sent from a Serial Communications Unit/Board installed in a CS/CJ-series PLC to a CS/CJ-series or C-series (see note) CPU Unit that is connected via RS-232C or RS-
422A/485.
Note C-series PLCs refer to the C200H, C200HS, C200HX/HG/HE(-Z), C120, C500, C500F, C1000HF,
CQM1, CPM1, CPM1A, CPM2A, CPM2C, SRM1, CQM1H, C1000H, and C2000H.
Serial Communications Board/Unit
CS/CJ-series
PLC
PMCR
(260)
Serial Communications Board/Unit
CS/CJ-series
PLC
PMCR
(260)
C-mode command
Response
C-mode command
Response
CS/CJ-series PLC CS/CJ-series PLC CS/CJ-series PLC
CS/CJ-series PLC
Note 1.
Multiple-frame commands and multiple-frame responses are not supported.
2.
Slave-initiated operations from the slave CPU Unit to the PLC master cannot be used.
Command and Response Formats
Note In the following diagrams “hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters.
• Command Frame
"@"
40 hex
1 byte
Host Link unit number
(X10
1
)(X10
0
)
2 bytes
• Response Frame
"@"
40 hex
Host Link unit number
(X10
1
)(X10
0
)
Command code
2 bytes
Command code End code
(X16
1
)(X16
0
)
Text
Text
FCS
1 byte
"
*"
2A hex
CR
0D hex
2 bytes
FCS
"
*"
2A hex
CR
0D hex
1 byte 2 bytes
2 bytes 2 bytes 1 byte 2 bytes
393
C-mode (Host Link) Command Master
Appendix C
Command Frame Contents
Item
@
Host Link unit number
Command code
Text
FCS
Terminator
Contents
Must be attached at the beginning of the command.
Set the unit number in BCD from 0 to 31 for each Host Link.
The command code is specified in two characters
Set parameters corresponding to command code.
Calculate 2-character FCS (frame check sequence) at host computer.
Set “*” and CR (0DH) as two characters to indicate the end of the command.
Response Frame Contents
Item
@
Host Link unit number
Command code
End code
Contents
Must be attached at the beginning of the response.
Set the unit number in BCD from 0 to 31 for each Host Link.
Text
FCS
Terminator
The command code that was received is returned.
The results (error status, etc.) of command execution is returned.
Returned only if there is read data.
The 2-character FCS (frame check sequence) is returned.
Two characters indicating the end of the command, “*” and CR
(0D hex), are returned.
For details on C-mode command codes for sending to CS/CJ-series CPU Units, refer to the CS/CJ Series
Communications Commands Reference Manual (W342). For details on C-mode command codes for sending to C-series CPU Units, refer to each of the C-series PLC operation manuals.
C-mode Command Code Master Protocol Sequences
The C-mode (Host Link) Command Code Master Protocol provides the following 22 communications sequences.
Structure of the Protocol
The following table shows the structure of the C-mode (Host Link) Command Code Master Protocol.
Sequence
No.
Communications sequence name
700 (02BC) Send/receive Cmode command
(with ASCII conversion)
701 (02BD) Send/receive Cmode command
(without conversion)
702 (02BE) CIO AREA READ
Function
Converts the text data for the specified C-mode command into ASCII and sends to the specified Host Link
Unit. The response is converted into hexadecimal and stored starting from the specified word.
Sends the text data for the specified C-mode command to the specified Host Link Unit without converting into
ASCII. The response is stored starting from the specified word without converting into hexadecimal.
Reads the contents of the specified number of CIO Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Yes
Yes
Ladder interface
Send word allocation
Receive word allocation
Yes Yes
Yes
Yes
394
C-mode (Host Link) Command Master
Appendix C
Sequence
No.
703 (02BF)
704 (02C0)
705 (02C1)
706 (02C2)
707 (02C3)
708 (02C4)
709 (02C5)
Communications sequence name
LR AREA READ
HR AREA READ
TIMER/COUNTER
PV READ
TIMER/COUNTER
STATUS READ
DM AREA READ
AR AREA READ
EM AREA READ
Function
Reads the contents of the specified number of LR Area
(CS/CJ Series: CIO 1000 to CIO 1199) words beginning with the designated word from the specified Host Link
Unit and stores starting from the specified storage word.
Reads the contents of the specified number of HR Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Reads the contents of the specified number of timer/ counter PV words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Ladder interface
Send word allocation
Receive word allocation
Yes Yes
Yes
Yes
Yes
Yes
Yes Reads the contents of the specified number of timer/ counter status words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Reads the contents of the specified number of DM Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Reads the contents of the specified number of AR Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Reads the contents of the specified number of EM Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes Yes 710 (02C6) CIO AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated CIO Area word. Writing is done in word units.
711 (02C7) LR AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated Link Area (CS/CJ
Series: CIO 1000 to CIO 1199) word. Writing is done in word units.
712 (02C8) HR AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated HR Area word. Writing is done in word units.
713 (02C9) TIMER/COUNTER
PV WRITE
Writes the specified write data to the specified Host Link
Unit starting from the designated timer/counter PV word.
Writing is done in word units.
714 (02CA) DM AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated DM Area word. Writing is done in word units.
715 (02CB) AR AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated AR Area word. Writing is done in word units.
716 (02CC) EM AREA WRITE Writes the specified write data to the specified Host Link
Unit starting from the designated EM Area word. Writing is done in word units.
717 (02CD) STATUS READ Reads the CPU Unit’s operating conditions (status) from the specified Host Link Unit and stores in the words starting from the designated word.
718 (02CE) STATUS CHANGE Changes the CPU Unit’s operating mode for the specified
Host Link Unit.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
395
C-mode (Host Link) Command Master
Appendix C
Sequence
No.
719 (02CF)
720 (02D0)
721 (02D1)
Communications sequence name
TEST
ABORT
INITIALIZE
Function
Yes
Ladder interface
Send word allocation
Receive allocation
Yes
word
Executes a data loopback test for the specified Host Link
Unit.
Initializes the port of the specified Host Link Unit.
Initialize the ports of all Host Link Units.
Yes
No
No
No
The values in parentheses are hexadecimal.
In normal operations sequence No. 700 (converts to ASCII and is specified from the command code to the designated Host Link unit number) is used for the C-mode Command Code Master function.
The relationship between the Host Link C-mode command code/response frame and the PMCR(260) instruction operand is shown in the following diagram.
Relationship Between Host Link C-mode Command/Response Frames and
PMCR(260) Operands
The relationship between Host Link C-mode command/response frames and PMCR(260) operands is shown in the following diagram using communications sequence No. 700 as an example.
Command Frame
"@"
Host Link unit number
40 hex (X101)(X100)
Command code Text FCS "
*"
2A hex
CR
0D hex
PMCR(260)
#02BC
S
D
Communications sequence No. 700
S
S+1
S+2
S+3
Number of send data words
(Undefined)
Host Link unit No.
(2 digits BCD)
User-specified C-mode command code
(ASCII)
Number of send bytes
S+4 Text for user-specified C-mode command
(ASCII)
396
C-mode (Host Link) Command Master
Response Frame
Host Link
"@" unit number
40 hex
(X10
1
)(X10
0
)
Command code End code
(X10
1
)(X10
0
)
Text
FCS
"
*"
2A hex
CR
0D hex
Appendix C
PMCR(260)
#02BC
S
D
Communications sequence No. 700
D
D+1
D+2
Number of receive data words
(Undefined)
End code
(2 digits BCD)
Receive data (hex)
User-specified Send/Receive Command with ASCII Conversion
(Sequence No. 700 (Hex 02BC))
This sequence converts the text data for the specified C-mode command into ASCII and sends to the specified
Host Link Unit. The response is converted into hexadecimal and stored starting from the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Host Link unit No.
C-mode command code
Number of send bytes
Text
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
C-mode command code
+3
+4
Number of send bytes
Text
Data
0004 to 0022 hex (4 to 34 decimal)
00 to 31
Specify the C-mode command code in
ASCII (e.g., RR is specified as 5252 hex.)
Specify the number of send bytes for the communications line.
0000 to 007A hex (0 to 122 decimal)
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Specify the text that corresponds to the command. The specified hexadecimal data will be converted into ASCII and sent.
397
C-mode (Host Link) Command Master
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
End code
Read data
Appendix C
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The read data is converted into hexadecimal stored.
Note The read data from the end code area (+1 word, rightmost byte) is stored for responses without end codes.
User-specified Send/Receive Command without Conversion
(Sequence No. 701 (Hex 02BD))
Sends the text data for the specified C-mode command to the specified Host Link Unit without converting into
ASCII. The response is stored starting from the specified word without converting into hexadecimal.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Host Link unit No.
C-mode command code
Number of send bytes
Text
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
C-mode command code
+3
+4
Number of send bytes
Text
Data
0004 to 0040 hex (4 to 64 decimal)
00 to 31
Specify the C-mode command code in
ASCII (e.g., RR is specified as 5252 hex.)
Specify the number of send bytes for the communications line.
0000 to 007A hex (0 to 122 decimal)
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Specify the text that corresponds to the command. The specified hexadecimal data will be converted into ASCII and sent.
398
C-mode (Host Link) Command Master
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
End code
Read data
Appendix C
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The read data is converted into hexadecimal stored.
Note The read data from the end code area (+1 word, rightmost byte) is stored for responses without end codes. Only the data stored in the end code area will be converted into ASCII.
CIO AREA READ (RR Command)
(Sequence No. 702 (Hex 02BE))
Reads the contents of the specified number of CIO Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
0000 to 6143
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
399
C-mode (Host Link) Command Master
Appendix C
LR AREA READ (RL Command)
(Sequence No. 703 (Hex 02BF))
Reads the contents of the specified number of LR Area (CS/CJ Series: CIO 1000 to CIO 1199) words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
0000 to 0199
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
400
C-mode (Host Link) Command Master
Appendix C
HR AREA READ (RH Command)
(Sequence No. 704 (Hex 02C0))
Reads the contents of the specified number of HR Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
0000 to 0511
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
401
C-mode (Host Link) Command Master
Appendix C
TIMER/COUNTER PV READ (RC Command)
(Sequence No. 705 (Hex 02C1))
Reads the contents of the specified number of timer/counter PV words (T0000 to T2047, C0000 to C2047) beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
+3 Number of read words
(4 digits BCD)
Timers: T0000 to T2047
Counters: C2048 to C4095
Note: Specify T0000 to T2047 for timers and in C2048 to C4095 for counters.
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
+3
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex or BCD)
(Depends on the method used to refresh the timer/counter PVs.)
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
402
C-mode (Host Link) Command Master
Appendix C
TIMER/COUNTER STATUS READ (RG Command)
(Sequence No. 706 (Hex 02C2))
Reads the contents of the specified number of timer/counter status words (T0000 to T2047, C0000 to C2047) beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
+3 Number of read words
(4 digits BCD)
Timers: T0000 to T2047 (timer No.s
0000 to 2047))
Counters: C2048 to C4095 (counter
No.s 0000 to 2047)
Note: Specify T0000 to T2047 for timers and in C2048 to C4095 for counters.
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
+3
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
+0
+4
+1
+5
+2
+6
+3
+7
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
ON: 1 hex
OFF: 0 hex
The Timer/Counter Completion Flag is
1 digit hex (4 bits) per point, and the
ON (1 hex) or OFF (0 hex) status is stored in order from the leftmost to rightmost digit in 1 word for each 4 points.
403
C-mode (Host Link) Command Master
Appendix C
DM AREA READ (RD Command)
(Sequence No. 707 (Hex 02C3))
Reads the contents of the specified number of DM Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
0000 to 9999
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
404
C-mode (Host Link) Command Master
Appendix C
AR AREA READ (RJ Command)
(Sequence No. 708 (Hex 02C4))
Reads the contents of the specified number of AR Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined)
First read word
Host Link unit No.
Number of read words
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
0000 to 0959
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
405
C-mode (Host Link) Command Master
Appendix C
EM AREA READ (RE Command)
(Sequence No. 709 (Hex 02C5))
Reads the contents of the specified number of EM Area words beginning with the designated word from the specified Host Link Unit and stores starting from the specified storage word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
(Undefined)
First read word
Host Link unit No.
Bank No.
Number of read words
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
(Undefined) Bank No.
(2 digits hex)
First read word (4 digits BCD)
Number of read words
(4 digits BCD)
Data
Always 0004 hex (4 decimal)
00 to 31
Current bank: Cannot be specified.
Bank specification: 00 to 0C hex
0000 to 0959
Depends on the remote CPU Unit.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined) End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Read data (4 digits hex)
+3
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The contents of the first read word is stored
The contents of the first read word +1 is stored
406
C-mode (Host Link) Command Master
Appendix C
CIO AREA WRITE (WR Command)
(Sequence No. 710 (Hex 02C6))
Writes the specified write data to the specified Host Link Unit starting from the designated CIO Area word.
Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
First write word
Host Link unit No.
Number of write bytes
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
Data
0005 to 0021 hex (5 to 33 decimal)
00 to 31
+4
+5
Write data
0000 to 6143
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
407
C-mode (Host Link) Command Master
Appendix C
LR AREA WRITE (WL Command)
(Sequence No. 711 (Hex 02C7))
Writes the specified write data to the specified Host Link Unit starting from the designated Link Area (CS/CJ
Series: CIO 1000 to CIO 1199) word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+4
+5
+0
+1
+2
+3
+4
Write data
Number of send data words
(Undefined) Host Link unit No.
First write word
Number of write bytes
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
0005 to 0021 hex (5 to 33 decimal)
00 to 31
Data
0000 to 0199
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
408
C-mode (Host Link) Command Master
Appendix C
HR AREA WRITE (WH Command)
(Sequence No. 712 (Hex 02C8))
Writes the specified write data to the specified Host Link Unit starting from the designated HR Area word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
First write word
Host Link unit No.
Number of write bytes
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
Data
0005 to 0021 hex (5 to 33 decimal)
00 to 31
+4
+5
Write data
0000 to 0511
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
409
C-mode (Host Link) Command Master
Appendix C
TIMER/COUNTER PV WRITE (WC Command)
(Sequence No. 713 (Hex 02C9))
Writes the specified write data to the specified Host Link Unit starting from the designated timer/counter PV word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
First write word
Host Link unit No.
Number of write bytes
Write data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Data
0005 to 0021 hex (5 to 33 decimal)
00 to 31
+3
+4
+5
Number of write bytes
(4 digits hex)
Write data
Timers: 0000 to 2047
Counters: 2048 to 4095
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
410
C-mode (Host Link) Command Master
Appendix C
DM AREA WRITE (WD Command)
(Sequence No. 714 (Hex 02CA))
Writes the specified write data to the specified Host Link Unit starting from the designated DM Area word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
First write word
Host Link unit No.
Number of write bytes
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
Data
0005 to 0021 hex (5 to 33 decimal)
00 to 31
+4
+5
Write data
0000 to 9999
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
411
C-mode (Host Link) Command Master
Appendix C
AR AREA WRITE (WJ Command)
(Sequence No. 715 (Hex 02CB))
Writes the specified write data to the specified Host Link Unit starting from the designated AR Area word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined)
First write word
Host Link unit No.
Number of write bytes
Write data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
Data
0005 to 0021 hex (5 to 33 decimal)
00 to 31
+4
+5
Write data
0448 to 0959
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
412
C-mode (Host Link) Command Master
Appendix C
EM AREA WRITE (WE Command)
(Sequence No. 716 (Hex 02CC))
Writes the specified write data to the specified Host Link Unit starting from the designated EM Area word. Writing is done in word units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
(Undefined)
Host Link unit No.
Bank No.
First write word
Number of write bytes
Write data
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
(Undefined) Bank No.
(2 digits hex)
First write word (4 bits hex)
Number of write bytes
(4 digits hex)
+5
+6
Write data
Data
0006 to 0022 hex (6 to 34 decimal)
00 to 31
Current bank: Cannot be specified.
Bank specification: 00 to 0C hex
0000 to 9999
Specify the number of write bytes for the communications line.
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+5 onwards.
Sends the write data to the first write word.
Sends the write data to the first write word +1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
413
C-mode (Host Link) Command Master
Appendix C
STATUS READ (MS Command)
(Sequence No. 717 (Hex 02CD))
Reads the CPU Unit's operating conditions (status) from the specified Host Link Unit and stores in the words starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+0
+1
Contents (data format)
Number of send data words
(Undefined)
Number of send data words
(Undefined) Host Link unit No.
Data
Always 0002 hex (2 decimal)
00 to 31 Host Link unit
No.
(2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
(Undefined) End code
Status data
Message
+2
+3
+4
+5
+6
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Status data (4 digits hex)
Message
Data
0003 hex or 0007 hex (3 or 7 decimal)
The end code is stored in hexadecimal.
The CPU Unit status is stored.
The message is stored only when FAL/
FALS messages are used.
STATUS CHANGE (SC Command)
(Sequence No. 718 (Hex 02CE))
Changes the CPU Unit's operating mode for the specified Host Link Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Host Link unit No.
Mode
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
(Undefined) Mode
(2 digits hex)
Data
Always 0003 hex (3 decimal)
00 to 31
00 hex: PROGRAM mode
02 hex: MONITOR mode
03 hex: RUN mode
414
C-mode (Host Link) Command Master
Appendix C
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(Undefined) End code
(2 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
TEST (TS Command)
(Sequence No. 719 (Hex 02CF))
Executes a data loopback test for the specified Host Link Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Host Link unit No.
Number of test data send bytes
Test data
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(Undefined) Host Link unit
No.
(2 digits BCD)
Number of test data send bytes
(4 digits hex)
Test data
Data
0004 to 0022 hex (2 to 34 decimal)
00 to 31
Specify the number of test data bytes.
The user-specified data is sent.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Test data
Offset
+0
+1
Contents (data format)
Number of receive data words
Test data
Data
0002 to 0031 hex (2 to 49 decimal)
The user-specified data is sent.
415
C-mode (Host Link) Command Master
Appendix C
ABORT (XZ Command)
(Sequence No. 720 (Hex 02D0))
Initializes the port of the specified Host Link Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+0
+1
Contents (data format)
Number of send data words
(Undefined)
Number of send data words
(Undefined)
Host Link unit No.
(2 digits BCD)
Data
Always 0002 hex (2 decimal)
00 to 31 Host Link unit
No.
(2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
INITIALIZE (** Command)
(Sequence No. 721 (Hex 02D1))
Initialize the ports of all Host Link Units.
Send Data Word Allocation (3rd Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
Receive Data Word Allocation (4th Operand of PMCR(260))
None. (Specify a dummy value for the operand, such as #0000.)
416
Appendix D
Host Link FINS Command Master
The Host Link FINS Command Master Protocol provides communications sequences using FINS commands with the CS/CJ-series PLC as the host (master).
This protocol is used to send user-specified or specific (e.g., MEMORY AREA READ) FINS commands enclosed in a Host Link header and terminator from a Serial Communications Unit/Board installed in a CS/CJseries PLC connected through RS-232C or RS-422A/485 to a CS/CJ-series CPU Unit or to a Special I/O Unit or CPU Bus Unit on the network.
Serial Communications Board/Unit
CS/CJ PLC
PMCR
(260)
Network
Communications Unit
CS/CJ or
CVM1/CV PLC
Protocol macro mode
(Host Link master)
FINS command
Host Link mode (Host Link master)
Communications Unit
CPU Unit
PLC on network
Personal computer on network
Communications Board
Network (Controller Link, Ethernet, etc.)
FINS command
Note Slave-initiated operation from the PLC slave is not supported.
1, 2, 3...
1.
Sending to a PLC Slave Directly Connected to the Serial Communications Unit/Board
Protocol macro mode
Serial Communications Unit/Board
PLC master
Host Link mode
PLC slave
FINS command
Note The remote destination network address (DNA) specifies the local network address (00 hex), the remote destination node address (DA1) specifies the local node (00 hex), and the remote destination unit address (DA2) specifies the CPU Unit in the PLC Slave (00 hex).
2.
Sending to a CPU Unit on the Network
Serial Communications Unit/Board
Protocol macro mode
PLC master
Host Link mode
PLC slave
PLC slave
Host Link
FINS command
Note
Network (e.g., Controller Link, Ethernet)
1.
The response monitoring time for both sending methods 1 and 2 is 3 s. These commands can be sent across up to 3 network levels.
2.
Slave-initiated FINS commands sent from the PLC slave to the PLC master are not supported for either method 1 or 2.
417
Host Link FINS Command Master
Appendix D
Command and Response Formats
Note In the following diagrams “hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters.
Command Frame
"@"
40 hex
Host Link unit number
(X10
1
)(X10
0
)
Host Link command code
"F" "A"
46 hex 41 hex
Response wait time "0"
30 hex
ICF "80"
38 hex 30 hex
RSV "00"
30 hex 30 hex
GCT "02"
30 hex 32 hex
1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte
@@ hex
DNA
@@ hex
1 byte 1 byte
@@ hex
DA1
@@ hex
1 byte 1 byte
@@ hex
DA2
@@ hex
1 byte 1 byte
30 hex
SNA "00"
30 hex
1 byte 1 byte
Text
SA1 "00"
30 hex 30 hex
1 byte 1 byte
@@ hex
FCS
@@ hex
SA2 "00"
30 hex 30 hex
1 byte 1 byte
"
*"
2A hex
1 byte
CR
0D hex
1 byte
SID "55"
35 hex 35 hex
1 byte 1 byte
Response Frame
Command code
@@@@@@@@ hex
4 bytes
"@"
40 hex
1 byte
Host Link unit number
(X10
1
)(X10
0
)
1 byte
30 hex
DNA "00"
30 hex
1 byte 1 byte
Host Link command code
"F" "A"
46 hex 41 hex
1 byte 1 byte
30 hex
DA1 "00"
30 hex
1 byte 1 byte
30 hex
"00"
30 hex
1 byte 1 byte
30 hex
DA2 "00"
30 hex
1 byte 1 byte
ICF "C0"
43 hex 30 hex
1 byte 1 byte
@@ hex
SNA
@@ hex
1 byte 1 byte
RSV "00"
30 hex 30 hex
1 byte 1 byte
@@ hex
SA1
@@ hex
1 byte 1 byte
GCT "02"
30 hex 32 hex
1 byte 1 byte
@@ hex
SA2
@@ hex
1 byte 1 byte
35 hex
SID "55"
35 hex
1 byte 1 byte
"
*"
2A hex
1 byte
CR
0D hex
1 byte
Command code
@@@@@@@@ hex
4 bytes
End code
@@@@@@@@ hex
4 bytes
Text
@@ hex
FCS
@@ hex
418
Host Link FINS Command Master
Appendix D
Command Frame Contents
Item
@
Host Link unit number
Command code
Contents
The @ symbol is automatically attached to the beginning of the command.
Specify the unit number for Host Link between 0 and 31 BCD.
Response wait time
ICF (Information control field)
RSV (Reserved)
GCT (Gateway count)
DNA (Destination network address)
DA1 (Destination node address)
DA2 (Destination unit address)
Specify a 2-character code. Always set “FA” (ASCII: 46, 41) when sending FINS commands. In this protocol, “FA” is automatically generated.
The response wait time sets the time from when the CPU Unit receives a command block until it starts to return a response. This time is automatically set to “0” (ASCII: 30).
Specify whether or not there are network relays. ICF is automatically set to “80” (ASCII: 38,30) indicating that network relays are used.
RSV is automatically set to “00” (ASCII: 30,30). Setting RSV is required only when sending to a CPU
Unit on a network.
This is the number of networks through which the transmission can be relayed. “02” (ASCII: 30,32) is automatically generated.
Specify the network, node, and unit addresses of the remote destination node.
DNA (Destination Network Address)
Set between 00 and 7F Hex (0 and 127 decimal). The network address (DNA) setting is required to specify the node address on the specified network.
DA1 (Destination Node Address)
Set in hexadecimal. The setting range depends on the network type. Set to 00 hex as the local node when sending commands to a PLC slave directly connected using serial communications.
DA2 (Destination Unit Address)
Set the address of the device on the FINS network (e.g., CPU Unit, Special I/O Unit, personal computer).
CPU Unit: 00 hex
CPU Bus Unit: Unit number + 10 hex
Example: Set 13 hex for unit number 3.
Special I/O Unit (except C200H Special I/O Units): Unit number + 20 hex
Example: Set 23 hex for unit number 3.
Specify the source network and node addresses. These settings are set to “00” (ASCII: 30, 30) regardless of whether or not there is a network relay.
SNA (Source network address)
SA1 (Source node address)
SA2 (Source unit address)
Specify the unit address of the unit at the PLC slave that is connected to the PLC master. SA2 is automatically set to “00” (ASCII: 30, 30) to indicate the CPU Unit. When “00” is set, internal processing converts the value to the unit address of each serial port.
SID (Service ID) The SID is used as a counter when resending. It is automatically set to “55” (ASCII: 35, 35).
Command code, text
Set the command code and text according to the FINS command and response formats.
A 2-character FCS is automatically set.
FCS (frame check sequence)
Terminator The terminator is a required delimiter at the end of a command. The terminator is automatically set to *CR (ASCII: 2A, 0D).
Response Frame Contents
Item
@
Host Link unit number, header code
ICF (Information control field)
RSV (Reserved)
GCT (Gateway count)
Contents
The @ symbol is automatically attached to the beginning of the response.
The same unit number and header code specified in the FINS command that was received will be returned.
For a CPU Unit on a network, “C0” (ASCII: 43, 30) will be returned.
This section is reserved for the system. Set “00” (ASCII: 30,30).
The same GCT that was specified in the command that was received will be returned.
419
Host Link FINS Command Master
Appendix D
Item
DNA (Destination network address)
DA1 (Destination node address)
DA2 (Destination unit address)
The same contents specified for SNA, SA1, and SA2 in the command that was received will be returned.
Contents
SNA (Source network address)
SA1 (Source node address)
SA2 (Source unit address)
The same contents specified for DNA, DA1, and DA2 in the command that was received will be returned.
SID (Service ID) The SID that was specified in the command that was received will be returned.
Command code, end code, text
The command code, end code, and text corresponding to the FINS command and response formats will be returned.
FCS (frame check sequence)
Terminator
A 2-character FCS is returned.
The terminator is a required delimiter at the end of a command. The terminator is automatically set to *CR (ASCII: 2A, 0D).
For details on FINS command codes for sending to CS/CJ-series CPU Units, refer to the CS/CJ Series Com-
munications Commands Reference Manual (W342).
Host Link FINS Command Code Master Protocol Sequences
The Host Link FINS Command Code Master Protocol provides the following 18 communications sequences.
Structure of the Protocol
The following table shows the structure of the Host Link FINS Command Code Master Protocol.
Sequence
No.
Communications sequence name
Function
750 (02EE)
751 (02EF)
752 (02F0)
753 (02F1)
754 (02F2)
FINS COMMAND
SEND/RECEIVE
MEMORY AREA
READ
CIO AREA READ
AR AREA READ
DM AREA READ
Sends user-specified FINS commands to the specified
Host Link Unit and stores the response starting from the designated word.
Sends command code 0101 hex to the specified Host
Link Unit, reads the contents of consecutive I/O memory area words, and stores the data starting from the designated word.
Sends command code 0101 hex to the specified Host
Link Unit, reads the contents of consecutive CIO Area words, and stores the data starting from the designated word.
Sends command code 0101 hex to the specified Host
Link Unit, reads the contents of consecutive AR Area words, and stores the data starting from the designated word.
Sends command code 0101 hex to the specified Host
Link Unit, reads the contents of consecutive DM Area words, and stores the data starting from the designated word.
755 (02F3) EM0 AREA READ Sends command code 0101 hex to the specified Host
Link Unit, reads the contents of consecutive EM Area words in Bank 0, and stores the data starting from the designated word.
Ladder interface
Send word allocation
Receive word allocation
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
420
Host Link FINS Command Master
Appendix D
Sequence
No.
Communications sequence name
Function
756 (02F4) MEMORY AREA
WRITE
Sends command code 0102 hex to the specified Host
Link Unit and writes data to consecutive I/O memory area words.
757 (02F5) CIO AREA WRITE Sends command code 0102 hex to the specified Host
Link Unit and writes data to consecutive CIO Area words.
758 (02F6) DM AREA WRITE Sends command code 0102 hex to the specified Host
Link Unit and writes data to consecutive DM Area words.
Yes
Yes
Yes
Ladder interface
Send word allocation
Receive allocation
Yes
word
Yes
Yes
759 (02F7) EM0 AREA WRITE Sends command code 0102 hex to the specified Host
Link Unit and writes data to consecutive EM Area words in Bank 0.
760 (02F8) MEMORY AREA
FILL
761 (02F9) CIO AREA FILL
Sends command code 0103 hex to the specified Host
Link Unit and writes the same data to consecutive I/O memory area words.
Sends command code 0103 hex to the specified Host
Link Unit and writes the same data to consecutive CIO
Area words.
762 (02FA) DM AREA FILL Sends command code 0103 hex to the specified Host
Link Unit and writes the same data to consecutive DM
Area words.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
763 (02FB) EM0 AREA FILL
764 (02FC) OPERATING MODE
CHANGE (RUN)
Sends command code 0103 hex to the specified Host
Link Unit and writes the same data to consecutive EM
Area words in Bank 0.
Sends command code 0401 hex to the specified Host
Link Unit and changes the CPU Unit’s operating mode to
MONITOR mode.
765 (02FD) OPERATING MODE
CHANGE (STOP)
Sends command code 0401 hex to the specified Host
Link Unit and changes the CPU Unit’s operating mode to
PROGRAM mode.
766 (02FE) UNIT DATA READ Sends command code 0501 hex to the specified Host
Link Unit and stores the Unit data starting from the designated word.
767 (02FF) UNIT STATUS
READ
Sends command code 0601 hex to the specified Host
Link Unit and stores the Unit’s operating conditions (status) starting from the designated word.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
The values in parentheses are hexadecimal
The relationship between the Host Link FINS command code/response frame and the PMCR(260) instruction operand is shown in the following diagram.
421
Host Link FINS Command Master
Command code
Text
FCS
*
CR
2A hex 0D hex
Appendix D
Relationship Between Host Link FINS Command/Response Frames and PMCR(260)
Operands
The relationship between Host Link FINS command/response frames and PMCR(260) operands is shown in the following diagram using communications sequence No. 750 as an example.
Command Frame
Response wait time
F A 0 8
SNA
0 0 0
SA1
0
ICF
0 0
SA2
0
SID
0
0 0 5 5
2
×
DNA
× ×
DA1
× × ×
@
40 hex
Host Link unit number
(
×10
1 )(
×10
0 )
PMCR
#02EE
S
D
Communications sequence No. 750
S
S+1
Number of send data words
Host Link unit No.
(2 digits BCD)
Remote destination network address (DNA)
(2 digits hex)
S+2
Remote destination node address (DA1) (2 digits hex)
Remote destination unit address
(DA2) (2 digits hex)
S+3
S+4
S+5
User-specified FINS command code
(MRC, SRC) (4 digits hex)
Number of bytes of FINS text from S+4 onwards
× 2
Text for user-specified FINS command code (hexadecimal)
Response Frame
@
40 hex
F A
×
SNA
×
Host Link unit number
(
×10
1
)(
×10
0
)
0
×
SA1
×
0
×
C
ICF
0
SA2
×
Command code
0
RSV
0
5
SID
5
End code
0
GCT
2 0
DNA
0 0
DA1
0 0
DA2
0
Text
FCS
*
2A hex
CR
0D hex
PMCR(260)
#02EE
S
D
Communications sequence No. 750
D
D+1
Number of send data words
End code (4 digits hex)
User-specified FINS receive data (4 digits hex)
422
Host Link FINS Command Master
Appendix D
FINS COMMAND SEND/RECEIVE
(Sequence No. 750 (Hex 02EE)
This sequence sends user-specified FINS commands to the specified Host Link Unit and stores the response starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+4
+0
Number of send data words
Host Link unit number
Remote destination node address (DA1)
MRC
Remote destination network address (DNA)
Remote destination unit address (DA2)
SRC
Number of FINS text bytes
+5
FINS text
Offset
+0
+1
+2
+3
+4
+5
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
0005 to 00FA hex (5 to 250 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
User-specified FINS command MRC
(2 digits hex)
SRC
(2 digits hex)
Number of FINS text bytes
(4 digits hex)
FINS text
0000 to 03D4 hex
Specify the number of FINS command text bytes for the communications line
(i.e., twice the number of bytes of FINS text in S+5 onwards)
The text for the user-specified FINS command to send.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
FINS receive text
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
FINS receive text
Data
0002 to 00FA hex (2 to 250 decimal)
The end code is stored in hexadecimal.
The received text is stored.
423
Host Link FINS Command Master
Appendix D
MEMORY AREA READ
(Sequence No. 751 (Hex 02EF)
This sequence sends command code 0101 hex to the specified Host Link Unit, reads the contents of consecutive I/O memory area words, and stores the data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Host Link unit number
+2
Remote destination node address
+3 Memory area code
Remote destination network address
Remote destination unit address
+4 First read address
+5
Number of read elements
Offset
+0
+1
+2
+3
+4
+5
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0006 hex (6 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Specify the memory area (2 digits hex) and the first read address (2 digits hex)
Memory area code
(2 digits hex)
First read address (6 digits hex)
Number of read elements
(4 digits hex)
Specify the number of read elements
(4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Receive data
Data
0003 to 00FA hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The receive data is stored.
424
Host Link FINS Command Master
Appendix D
CIO AREA READ
(Sequence No. 752 (Hex 02F0)
This sequence sends command code 0101 hex to the specified Host Link Unit, reads the contents of consecutive CIO Area words, and stores the data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+4
+0
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First read address
Number of read elements
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination network address (DNA)
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address (DA1)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First read address (4 digits hex)
Number of read elements
(4 digits hex)
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 17FF hex
Specify the first read address
(4 digits hex)
0001 to 00F0 hex
Specify the number of read elements
(4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Receive data
Data
0003 to 00F2 hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The receive data is stored.
425
Host Link FINS Command Master
Appendix D
AR AREA READ
(Sequence No. 753 (Hex 02F1)
This sequence sends command code 0101 hex to the specified Host Link Unit, reads the contents of consecutive AR Area words, and stores the data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
Host Link unit number
Remote destination network address
Remote destination node address
Remote destination unit address
First read address
Number of read elements
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination network address (DNA)
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address (DA1)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First read address (4 digits hex)
Number of read elements
(4 digits hex)
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 01BF hex
Specify the first read address
(4 digits hex)
0001 to 00F0 hex
Specify the number of read elements
(4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Receive data
Data
0003 to 00F2 hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The receive data is stored.
426
Host Link FINS Command Master
Appendix D
DM AREA READ
(Sequence No. 754 (Hex 02F2)
This sequence sends command code 0101 hex to the specified Host Link Unit, reads the contents of consecutive DM Area words, and stores the data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First read address
Number of read elements
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination network address (DNA)
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address (DA1)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First read address (4 digits hex)
Number of read elements
(4 digits hex)
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first read address
(4 digits hex)
0001 to 00F0 hex
Specify the number of read elements
(4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Receive data
Data
0003 to 00F2 hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The receive data is stored.
427
Host Link FINS Command Master
Appendix D
EM0 AREA READ
(Sequence No. 755 (Hex 02F3)
This sequence sends command code 0101 hex to the specified Host Link Unit, reads the contents of consecutive EM Area words in Bank 0, and stores the data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+4
+0
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First read address
Number of read elements
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination network address (DNA)
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address (DA1)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First read address (4 digits hex)
Number of read elements
(4 digits hex)
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first read address
(4 digits hex)
0001 to 00F0 hex
Specify the number of read elements
(4 digits hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Receive data
Data
0003 to 00F2 hex (3 to 250 decimal)
The end code is stored in hexadecimal.
The receive data is stored.
428
Host Link FINS Command Master
Appendix D
MEMORY AREA WRITE
(Sequence No. 756 (Hex 02F4))
This sequence sends command code 0103 hex to the specified Host Link Unit and writes the same data to consecutive I/O memory area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Host Link unit number
+2
Remote destination node address
+3 Memory area code
Remote destination network address
Remote destination unit address
+4 First write address
+5
+6
+7
Number of write elements
Number of write data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
+7
+8 on
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Memory area code
(2 digits hex)
Data
0008 to 00FA hex (8 to 250 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Specify the memory area (2 digits hex) and the first write address (2 digits hex)
First write address (6 digits hex)
Number of write elements
(4 digits hex)
Number of write data bytes
(4 digits hex)
Write data (4 digits hex)
Specify the number of write elements
(4 digits hex)
0004 to 03B8 hex
Specify the number of FINS command text bytes for the communications line
(i.e., twice the number of write data bytes in S+7 onwards)
Write data to send to the first write word
Write data to send to the first write word + 1 and onwards
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
429
Host Link FINS Command Master
Appendix D
CIO AREA WRITE
(Sequence No. 757 (Hex 02F5))
This sequence sends command code 0102 hex to the specified Host Link Unit and writes data to consecutive
CIO Area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+0
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First write address
+4
+5
Number of write elements
Number of write data bytes
+6 Write data
Offset
+0
+1
+2
+3
+4
+5
+6
+7 on
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (4 digits hex)
Data
0007 to 00F4 hex (7 to 244 decimal)
Host Link unit number: 00 to 31
DNA: 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 17FF hex
Specify the first write address
(4 digits hex)
Number of write elements
(4 digits hex)
Number of write data bytes
(4 digits hex)
Write data (4 digits hex)
0001 to 00EE hex
Specify the number of write elements
0004 to 03B8 hex
Specify the number of FINS command text bytes for the communications line
(i.e., twice the number of write data bytes in S+6 onwards)
Write data to send to the first write word
Write data to send to the first write word + 1 and onwards
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
430
Host Link FINS Command Master
Appendix D
DM AREA WRITE
(Sequence No. 758 (Hex 02F6))
This sequence sends command code 0102 hex to the specified Host Link Unit and writes data to consecutive
DM Area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+0 Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First write address
+4
+5
Number of write elements
Number of write data bytes
+6
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
+7 on
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (4 digits hex)
Data
0007 to 00F4 hex (7 to 244 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first write address
(4 digits hex)
Number of write elements
(4 digits hex)
Number of write data bytes
(4 digits hex)
Write data (4 digits hex)
0001 to 00EE hex
Specify the number of write elements
0004 to 03B8 hex
Specify the number of FINS command text bytes for the communications line
(i.e., twice the number of write data bytes in S+6 onwards)
Write data to send to the first write word
Write data to send to the first write word + 1 and onwards
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
431
Host Link FINS Command Master
Appendix D
EM0 AREA WRITE
(Sequence No. 759 (Hex 02F7))
This sequence sends command code 0102 hex to the specified Host Link Unit and writes data to consecutive
EM Area words in Bank 0.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+0
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
First write address
+4
+5
Number of write elements
Number of write data bytes
+6 Write data
Offset
+0
+1
+2
+3
+4
+5
+6
+7 on
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (4 digits hex)
Data
0007 to 00F5 hex (7 to 245 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first write address
(4 digits hex)
Number of write elements
(4 digits hex)
Number of write data bytes
(4 digits hex)
Write data (4 digits hex)
0001 to 00EE hex
Specify the number of write elements
0004 to 03B8 hex
Specify the number of FINS command text bytes for the communications line
(i.e., twice the number of write data bytes in S+6 onwards)
Write data to send to the first write word
Write data to send to the first write word + 1 and onwards
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
432
Host Link FINS Command Master
Appendix D
MEMORY AREA FILL
(Sequence No. 760 (Hex 02F8))
This sequence sends command code 0102 hex to the specified Host Link Unit and writes data to consecutive
I/O memory area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Host Link unit number
+2
Remote destination node address
+3 Memory area code
Remote destination network address
Remote destination unit address
+4
First write address
+5
+6
Number of write data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0007 hex (7 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Specify the memory area (2 digits hex) and the first write address (2 digits hex)
Memory area code
(2 digits hex)
First write address (6 digits hex)
Number of write elements
(4 digits hex)
Write data (4 digits hex)
Specify the number of write elements.
Specify the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
433
Host Link FINS Command Master
Appendix D
CIO AREA FILL
(Sequence No. 761 (Hex 02F9))
This sequence sends command code 0103 hex to the specified Host Link Unit and writes the same data to consecutive CIO Area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
Host Link unit number
Remote destination node address
First write address
Remote destination network address
Remote destination unit address
Number of write data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (6 digits hex)
Data
Always 0006 hex (6 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 17FF hex
Specify the first write address
(4 digits hex)
Specify the number of write elements.
Number of write elements
(4 digits hex)
Write data Specify the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Offset
+0
+1
+0
+1
Number of receive data words
End code
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal
(4 digits hex).
434
Host Link FINS Command Master
Appendix D
DM AREA FILL
(Sequence No. 762 (Hex 02FA))
This sequence sends command code 0103 hex to the specified Host Link Unit and writes the same data to consecutive DM Area words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
Host Link unit number
Remote destination node address
First write address
Remote destination network address
Remote destination unit address
Number of write data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (6 digits hex)
Data
Always 0006 hex (6 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first write address
(4 digits hex)
Specify the number of write elements.
Number of write elements
(4 digits hex)
Write data (4 digits hex) Specify the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Offset
+0
+1
+0
+1
Number of receive data words
End code
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
435
Host Link FINS Command Master
Appendix D
EM0 AREA FILL
(Sequence No. 763 (Hex 02FB))
This sequence sends command code 0103 hex to the specified Host Link Unit and writes the same data to consecutive EM Area words in Bank 0.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+1
+2
+3
+0
Number of send data words
Host Link unit number
Remote destination node address
First write address
Remote destination network address
Remote destination unit address
+4
+5
Number of write data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
First write address (6 digits hex)
Data
Always 0006 hex (6 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
0000 to 7FFF hex
Specify the first write address
(4 digits hex)
Specify the number of write elements.
Number of write elements
(4 digits hex)
Write data (4 digits hex) Specify the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Offset
+0
+1
+0
+1
Number of receive data words
End code
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
436
Host Link FINS Command Master
Appendix D
OPERATING MODE CHANGE (RUN)
(Sequence No. 764 (Hex 02FC))
This sequence sends command code 0401 hex to the specified Host Link Unit and changes the CPU Unit's operating mode to MONITOR mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0003 hex (3 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Offset
+0
+1
+0
+1
(4 digits hex)
Number of receive data words
End code
Contents (data format)
Number of receive data words
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
437
Host Link FINS Command Master
Appendix D
OPERATING MODE CHANGE (STOP)
(Sequence No. 765 (Hex 02FD))
This sequence sends command code 0402 hex to the specified Host Link Unit and changes the CPU Unit's operating mode to PROGRAM mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0003 hex (3 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
End code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
438
Host Link FINS Command Master
Appendix D
UNIT DATA READ
(Sequence No. 766 (Hex 02FE))
This sequence sends command code 0501 hex to the specified Host Link Unit and stores the Unit data starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0003 hex (3 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Unit data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Unit data
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
The unit data is stored.
439
Host Link FINS Command Master
Appendix D
UNIT STATUS READ
(Sequence No. 767 (Hex 02FF))
This sequence sends command code 0601 hex to the specified Host Link Unit and stores the Unit's operating conditions (status) starting from the designated word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
Host Link unit number
Remote destination node address
Remote destination network address
Remote destination unit address
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Host Link unit
No.
(2 digits BCD)
Remote destination node address (DA1)
(2 digits hex)
Remote destination network address (DNA)
(2 digits hex)
Remote destination unit address
(DA2)
(2 digits hex)
Data
Always 0003 hex (3 decimal)
Host Link unit number: 00 to 31
Remote destination network address
(DNA): 00 to 7F hex
Remote destination node address
(DA1): 00 to FE hex
Remote destination unit address (DA2):
00 to FE hex
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
End code
Unit status
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits hex)
End code (4 digits hex)
Unit status
Data
Always 0002 hex (2 decimal)
The end code is stored in hexadecimal.
The Unit’s operating status is stored.
440
Appendix E
Mitsubishi Computer Link Master
(A-compatible 1C Frame, Model 1)
The Mitsubishi Computer Link Master (A-compatible 1C frame, model 1) Protocol is used to send user-specified or specific (e.g., Device Memory Read/Write) Computer Link commands using the A-compatible 1C frame model 1 control protocol from a CS/CJ-series PLC (CPU Unit) connected through RS-232C or RS-422A to a
Mitsubishi PLC (Sequencer CPU Module installed in a Computer Link Module). This protocol enables the
OMRON PLC to be used as the host (master) to remotely execute RUN/STOP for or read/write the device memory of a Mitsubishi A/QnA/Q-series PLC that is connected either serially or on a MELSECNET/Ethernet network.
OMRON CS/CJ-series PLC
Serial Communications Unit/Board
CPU Unit
PMCR(260)
Executing standard system Computer Link Master Protocol
Computer Link command
RS-232C or RS-422A (Computer Link)
Mitsubishi PLC
Computer Link Unit
Communications Specifications
Item
Protocol
Transmission path connection
Communications method
Synchronization method
Transmission code
Data length
Stop bits
Error detection method
Specifications
Computer Link, A-compatible 1C frame, model 1
Multi-point
Host (OMRON CS/CJ-series PLC): Mitsubishi Sequencer CPU Module
1:1, 1:n (n = 32 max), m:n (m+n = 32 max)
Note 1: Specifying the PLC number enables access of the specified Sequencer CPU Module on the MELSECNET or Ethernet network.
Note 2: Sending data using slave-initiated communications from the Sequence CPU Unit to the Host (on-demand function) is not supported.
RS-232C, RS-422A (4-wire, half-duplex)
Start-stop synchronization
ASCII
7, 8 bits
Note: 8-bit units with “0” added to the beginning of the 7-bit code
1, 2 bits
Horizontal parity (none, 1 bit)
441
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Command Response Formats
Note In the following diagrams “hex” indicates hexadecimal values. Values in quotation marks, such as “00” indicate ASCII characters.
Command Frame
ENQ
05 hex
1 byte
Station
PLC
No.
No.
@@ hex @@ hex @@ hex @@ hex
2 bytes 2 bytes
Command code
2 bytes
Transmission delay
30 hex
1 byte
Characters (text)
Checksum
2 bytes
Response Frame
• Normal Response Type 1
Station
PLC
STX No.
No.
02 hex
@@ hex @@ hex @@ hex @@ hex
1 byte 1 byte 1 byte 1 byte 1 byte
• Normal Response Type 2
ACK
06 hex
Station
No.
PLC
No.
@@ hex @@ hex @@ hex @@ hex
1 byte 1 byte 1 byte 1 byte 1 byte
• Error Response
NAK
02 hex
1 byte
Station
No.
PLC
No.
@@ hex @@ hex @@ hex @@ hex
1 byte 1 byte 1 byte 1 byte
Characters (text)
Error code
2 bytes
ETX
03 hex
Checksum
1 byte 1 byte 1 byte
Command Frame Contents
Item
Control code
Station No.
PLC No.
Command code
Send delay
Device type
Contents
ENQ (05 hex) for A-compatible 1C frames, model 1.
This number distinguishes the remote destination Computer Link Module.
Setting range: 00 to 1 F hex (0 to 31 decimal), or FF hex (255 decimal) using global function. Set in
2 digits hexadecimal.
This number distinguishes the remote destination Sequencer CPU Module. Set in 2 digits hexadecimal
Accessing Sequencer CPU Module (local station) that is directly connected to the host using serial communications: All FF hex (255 decimal)
Accessing Sequencer CPU Module (local station) on the MELSECNET or Ethernet network that is not directly connected to the host using serial communications:01 to 40 hex (1 to 64 decimal) or 00 hex (0 decimal).
Specify the processing command to read/write device memory and execute remote RUN/STOP of the Mitsubishi Sequencer CPU Module at the remote destination.
This is the delay until a response is returned from the remote destination Computer Link Module.
The send delay is not supported by this protocol, and 0 hex (0 ms) is set in the command frame automatically.
Set the following device type characters in ASCII.
All characters except T/C: X, Y, M, L, S, B, F, M, D, W, R, D
T/C characters: TS (contact), TC (coil), CS (contact), CC (coil), TN (PV), CN (PV)
442
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Item
Device address
Device points
Contents
Specify the addresses for specified device types in hexadecimal.
Specify the number of bits for bit data and the number of words for word data in hexadecimal.
Mitsubishi Computer Link Master Protocol Sequences
The Mitsubishi Computer Link Master Protocol provides the following 19 communications sequences.
Structure of the Protocol
The following table shows the structure of the Mitsubishi Computer Link Master (A-compatible 1C frame, model
1) Protocol.
• Sending User-specified Commands
Sequence
No.
Communications sequence name
800 (0320) Send/receive userspecified Computer Link commands with ASCII conversion
801 (0321) Send/receive userspecified Computer Link commands without conversion
Computer Link command
User-specified
User-specified
Function
Converts the text data of a user-specified Computer Link command into ASCII and sends to the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
The response data is converted into hexadecimal and stored in the
CS/CJ-series CPU Unit starting from the specified word.
Sends the text data of a user-specified Computer Link command to the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows) without converting into
ASCII. The response data is stored in the CS/CJ-series CPU Unit starting from the specified word without converting into hexadecimal.
• Sending Device Read/Write Commands Common to ACPU
Sequence
No.
Communications sequence name
802 (0322) Device memory batch read as word data (all device types except T/C)
Computer Link command
WR (Device memory batch read as word data)
803 (0323) Device memory batch read as word data (T/C device type)
804 (0324) Device memory fill as word data (all device types except
T/C)
805 (0325) Device memory fill as word data (T/C device type)
WW (Device memory fill as word data)
Device type Function
Device other than
Timer/Counter
Reads the word data for the number of device points starting from the specified device address for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Timer/Counter
(T, C)
Device other than
Timer/Counter
Reads the word (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Writes the word data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and the PLC number that follows).
Timer/Counter
(T, C)
Writes the word (PV) data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the
PLC number that follows).
443
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Sequence
No.
Communications sequence name
806 (0326) Device memory batch read as bit data (all device types except T/C)
807 (0327) Device memory batch read as bit data (T/C device type)
808 (0328) Device memory fill as bit data (all device types except
T/C)
BW (Device memory fill as bit data)
809 (0329) Device memory fill as bit data (T/C device type)
Computer Link command
BR (Device memory batch read as bit data)
Device type Function
Device other than
Timer/Counter
Reads the bit data for the number of device points starting from the specified device address for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Timer/Counter
(T, C)
Device other than
Timer/Counter
Reads the bit (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Writes the bit data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and the PLC number that follows).
Timer/Counter
(T, C)
Writes the bit (PV) data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the
PLC number that follows).
444
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
• Sending Device Read/Write Commands Common to AnA/AnUCPU
Sequence
No.
Communications sequence name
810 (032A) Device memory batch read as word data (all device types except T/C)
Computer Link command
QR (Device memory batch read as word data)
811 (032B) Device memory batch read as word data (T/C device type)
812 (032C) Device memory fill as word data (all device types except
T/C)
813 (032D) Device memory fill as word data (T/C device type)
814 (032E) Device memory batch read as bit data (all device types except T/C)
815 (032F) Device memory batch read as bit data (T/C device type)
817 (0331) Device memory fill as bit data (T/C device type)
QW (Device memory fill as word data)
JR (Device memory batch read as bit data)
816 (0330) Device memory fill as bit data (all device types except
T/C)
JW (Device memory fill as bit data)
Device type Function
Device other than
Timer/Counter
Reads the word data for the number of device points starting from the specified device address for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Timer/Counter
(T, C)
Reads the word (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Device other than
Timer/Counter
Writes the word data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and the PLC number that follows).
Timer/Counter
(T, C)
Device other than
Timer/Counter
Writes the word (PV) data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the
PLC number that follows).
Reads the bit data for the number of device points starting from the specified device address for the specified device type (except T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Timer/Counter
(T, C)
Reads the bit (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Device other than
Timer/Counter
Writes the bit data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type
(except T, C) in the Mitsubishi Computer Link
Module with the specified station number (and the PLC number that follows).
Timer/Counter
(T, C)
Writes the bit (PV) data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the
PLC number that follows).
445
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
• Sending Commands Common to ACPU
Sequence
No.
Communications sequence name
818 (0332) Loopback test
Computer Link command
TT (Loopback test)
Function
Executes a loopback test at the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows). (E.g, if the data starting from the specified word + 3 is sent from the host, the Computer Link Module will return the data unchanged to the host.)
The values in parentheses are hexadecimal.
Send/Receive User-specified Computer Link Commands, with ASCII
Conversion
(Sequence No. 800 (Hex 0320)) Command Code: User-specified
This sequence converts the text data of a user-specified Computer Link command into ASCII and sends to the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows). The response data is converted into hexadecimal and stored in the CS/CJ-series CPU Unit starting from the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
Station No.
PLC No.
Command
Number of send bytes
Text data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Command (4 digits hex)
+3
+4
Number of send bytes
(4 digits hex)
Text data
Data
0004 to 00FA hex (4 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Specify the service command code to be used in ASCII.
0000 to 007A hex (0 to 122 decimal)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+4 onwards)
Set the text data for the command. The specified hexadecimal data will be converted into ASCII and sent.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Receive data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data bytes
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Receive data (4 digits hex)
Data
0002 to 00FA hex (2 to 250 decimal)
Station No: 00 to FF hex
PLC No.: 00 to FF hex
Any receive data is converted into hexadecimal and stored.
446
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Send/Receive User-specified Computer Link Commands without
Conversion
(Sequence No. 801 (Hex 0321)) Command Code: User-specified
This sequence sends the text data of a user-specified Computer Link command to the Mitsubishi Computer
Link Module with the specified station number (and the PLC number that follows) without converting into ASCII.
The response data is stored in the CS/CJ-series CPU Unit starting from the specified word without converting into hexadecimal.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
Station No.
Command
PLC No.
Number of send bytes
Text data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Command (4 digits hex)
+3
+4
Number of send bytes
(4 digits hex)
Text data
Data
0004 to 00FA hex (4 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Specify the service command code to be used in ASCII.
0000 to 007A hex (0 to 122 decimal)
Note: The text data is converted into
ASCII on the communications line, so specify twice the number of bytes of text data bytes in S+4 onwards.
Set the text data for the command. The specified hexadecimal data will be converted into ASCII and sent.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Receive data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data bytes
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Receive data (4 digits hex)
Data
0002 to 00FA hex (2 to 250 decimal)
Station No: 00 to FF hex
PLC No.: 00 to FF hex
Any receive data is converted into hexadecimal and stored.
447
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Word data (Any Device Type Except T/C)
(Sequence No. 802 (Hex 0322)) (Command Code: WR)
This sequence reads the word data for the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
+3
(2 digits hex)
Device No. (4 digits hex)
+4
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
Number of device words/bits
Data
Always 0005 hex (5 decimal) bits
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
PLC No.
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (2 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
448
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Word Data (T/C Device Type)
(Sequence No. 803 (Hex 0323)) (Command Code: WR)
This sequence reads the word (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+0
+1
+2
+3
+4
Number of send data words
Station No.
Device type
PLC No.
(Undefined)
(Undefined)
Device No.
Number of device words/bits
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
(3 digits hex) bits
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
PLC No.
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (2 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
449
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Word Data (Any Device Type Except T/C)
(Sequence No. 804 (Hex 0324)) (Command Code: WW)
This sequence writes the word data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+4
+5
+6
+1
+2
+3
Number of send data words
Station No.
PLC No.
(Undefined)
Device No.
Device type
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
+3
(2 digits hex)
Device No. (4 digits hex)
+4
Data
0007 to 00FA hex (7 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
+5
+6 bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Write data (4 digits hex)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Data
0002 or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
450
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Word Data (T/C Device Type)
(Sequence No. 805 (Hex 0325)) (Command Code: WW)
This sequence writes the word (PV) data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
Number of send data words
+1
+2
+3
+4
+5
+6
Station No.
PLC No.
Device type
(Undefined)
(Undefined)
Device No.
Number of device words/bits
Number of send data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Data
0007 to 00FA hex (7 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
(Undefined)
Device No. (3 digits hex) Set the first write address of the write data. bits
(2 digits hex)
Set the number of device words/bits to write.
Number of send data bytes
(4 digits hex)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Write data (4 digits hex) Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Data
0002 or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
451
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Bit Data (All Device Types Except T/C)
(Sequence No. 806 (Hex 0326)) (Command Code: BR)
This sequence reads the bit data for the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
+3
(2 digits hex)
Device No. (4 digits hex)
+4
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
Number of device words/bits
Data
Always 0005 hex (5 decimal) bits
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
PLC No.
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
452
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Bit Data (T/C Device Type)
(Sequence No. 807 (Hex 0327)) (Command Code: BR)
This sequence reads the bit (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+0
+1
+2
+3
+4
Number of send data words
Station No.
Device type
PLC No.
(Undefined)
(Undefined)
Device No.
Number of device words/bits
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
(3 digits hex) bits
(2 digits hex)
Data
Always 0005 hex (5 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
PLC No.
Read data
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
453
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Bit Data (All Device Types Except T/C)
(Sequence No. 808 (Hex 0328)) (Command Code: BW)
This sequence writes the bit data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
Number of send data words
+1
+2
+3
Station No.
(Undefined)
Device No.
PLC No.
Device type
+4
(Undefined)
+5
Number of device words/bits
Number of send data bytes
+6
Write data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
+3
(2 digits hex)
Device No. (4 digits hex)
+4
+5
+6
(Undefined)
Device words/bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Write data (4 digits hex)
Data
0007 to 00FA hex (7 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Read data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
454
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Bit Data (T/C Device Type)
(Sequence No. 809 (Hex 0329)) (Command Code: BW)
This sequence writes the bit (PV) data starting from the specified word + 6 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0 Number of send data words
+1
+2
+3
Station No.
Device type
(Undefined)
Device No.
PLC No.
+4
+5
+6
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
Offset
+0
+1
+2
+3
+4
+5
+6
Contents (data format)
Number of send data words
(4 digits hex)
Data
0007 to 00FA hex (7 to 250 decimal)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
(Undefined)
(Undefined)
Device No. (3 digits hex)
Device words/bits
(3 digits hex)
Number of send data bytes
(4 digits hex)
Write data (4 digits hex)
Set the first write address of the write data.
Set the number of device words/bits to write.
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Error code
(2 digits hex)
(Undefined)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
455
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Word Data (All Device Types Except T/C)
(Sequence No. 810 (Hex 032A)) (Command Code: QR)
This sequence reads the word data for the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
(Undefined)
Number of device words/bits
Data
Always 0006 hex (6 decimal)
+3
+4
+5
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
(2 digits hex)
Device No. (6 digits hex)
(Undefined) bits
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Read data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
456
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Word Data (T/C Device Type)
(Sequence No. 811 (Hex 032B)) (Command Code: QR)
This sequence reads the word (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+5
+0
+1
+2
+3
+4
+5
Number of send data words
Station No.
Device type
Device No.
PLC No.
(Undefined)
(Undefined)
Number of device words/bits
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Device No. (5 digits hex)
(Undefined) bits
(2 digits hex)
Data
Always 0006 hex (6 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Read data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
457
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Word Data (All Device Types Except T/C)
(Sequence No. 812 (Hex 032C)) (Command Code: QW)
This sequence writes the word data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
+3
+4
+5
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
(2 digits hex)
Device No. (6 digits hex)
(Undefined)
+6 bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Data
0008 to 00FA hex (8 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
+7 Write data (4 digits hex)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260)
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Data
0002 hex or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
458
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Word Data (T/C Device Type)
(Sequence No. 813 (Hex 032D)) (Command Code: QW)
This sequence writes the word (PV) data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
Number of send data words
Station No.
Device type
Device No.
PLC No.
(Undefined)
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
+3
+4
+5
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Device No. (5 digits hex)
(Undefined)
Data
0008 to 00FA hex (8 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
+6
+7 bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Write data (4 digits hex)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260)
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Data
0002 hex or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
459
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Bit Data (All Device Types Except T/C)
(Sequence No. 814 (Hex 032E)) (Command Code: JR)
This sequence reads the bit data for the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
(Undefined)
Number of device words/bits
Data
Always 0006 hex (6 decimal)
+3
+4
+5
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
(2 digits hex)
Device No. (6 digits hex)
(Undefined) bits
(2 digits hex)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Read data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
460
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Batch Read as Bit Data (T/C Device Type)
(Sequence No. 815 (Hex 032F)) (Command Code: JR)
This sequence reads the bit (PV) data for the number of device points starting from the specified device address for the specified device type (T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows), converts the data into hexadecimal, and stores it starting from the specified word + 2 in the CS/CJ-series CPU Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Offset
+0
+1
+2
+3
+4
+5
+0
+1
+2
+3
+4
+5
Number of send data words
Station No.
Device type
Device No.
PLC No.
(Undefined)
(Undefined)
Number of device words/bits
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Device No. (5 digits hex)
(Undefined) bits
(2 digits hex)
Data
Always 0006 hex (6 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first read address of the device to read.
Set the number of device words/bits to read.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Read data
PLC No.
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Read data (4 digits hex)
Data
0003 to 00FA hex (3 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the number read data converted into hexadecimal.
461
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Bit Data (All Device Types Except T/C)
(Sequence No. 816 (Hex 0330)) (Command Code: JW)
This sequence writes the bit data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (except T, C) in the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
Number of send data words
Station No.
(Undefined)
Device No.
PLC No.
Device type
(Undefined)
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
+3
+4
+5
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
(2 digits hex)
Device No. (6 digits hex)
(Undefined)
+6 bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Data
0008 to 00FA hex (8 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (1 character) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
+7 Write data (4 digits hex)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260)
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Data
0002 hex or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
462
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Device Memory Fill as Bit Data (T/C Device Type)
(Sequence No. 817 (Hex 0331)) (Command Code: JW)
This sequence writes the bit (PV) data starting from the specified word + 7 in the CS/CJ-series CPU Unit to the number of device points starting from the specified device address for the specified device type (T, C) in the
Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
Number of send data words
Station No.
Device type
Device No.
PLC No.
(Undefined)
(Undefined)
Number of device words/bits
Number of send data bytes
Write data
+3
+4
+5
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Device type (4 digits hex)
Device No. (5 digits hex)
(Undefined)
Data
0008 to 00FA hex (8 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the device type (2 characters) in
ASCII.
Set the first write address of the write data.
Set the number of device words/bits to write.
+6
+7 bits
(2 digits hex)
Number of send data bytes
(4 digits hex)
Write data (4 digits hex)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
Error code
(2 digits hex)
PLC No.
(2 digits hex)
(Undefined)
Specify the number of text data bytes for the communications line (i.e., twice the number of text bytes in S+6 onwards)
Set the write data.
Receive Data Word Allocation (4th Operand of PMCR(260)
Receive data storage words
+0
+1
+2
Number of receive data words
Station No.
Error code
PLC No.
(Undefined)
Data
0002 hex or 0003 hex (2 or 3 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Stores the error code converted to hexadecimal. No error code is stored for normal completion.
463
Mitsubishi Computer Link Master (A-compatible 1C Frame, Model 1)
Appendix E
Loopback Test
(Sequence No. 818 (Hex 0332)) (Command Code: TT)
This sequence executes a loopback test at the Mitsubishi Computer Link Module with the specified station number (and the PLC number that follows). (E.g, if the data starting from the specified word + 3 is sent from the host, the Computer Link Module will return the data unchanged to the host.)
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
Station No.
(Undefined)
Loopback data
PLC No.
Data length
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits hex)
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
+2
(2 digits hex)
+3 Loopback data
Data
Always 0005 hex (5 decimal)
Receive Data Word Allocation (4th Operand of PMCR(260)
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Station No.
Data length
Loopback data
PLC No.
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
Set the number of bytes of loopback data in S+3 onwards.
Set the loopback data to send.
Offset
+0
+1
+2
+3
Contents (data format)
Number of receive data words
Station No.
(2 digits hex)
PLC No.
(2 digits hex)
Data length
(2 digits hex)
Loopback data
Data
0002 to 00FA hex (2 to 250 decimal)
Station No.: 00 to FF hex
PLC No.: 00 to FF hex
The data length for the loopback data is stored.
The loopback data is stored unchanged.
464
Appendix F
E5
@K Digital Controller Read Protocol
The E5
@K Digital Controller Read Protocol reads and controls various parameters in remote mode for the
Controller connected to the Serial Communications Unit/Board via RS-232C or RS-485 cable.
Structure of the Protocol
The following table shows the structure of the E5
@K Digital Controller Read Protocol.
Sequence
No.
Communications sequence name
000 (0000) Read process value
001 (0001) Read set point during SP ramp
Function Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
002 (0002) Read MV
003 (0003) Read set point
004 (0004) Read alarm value
005 (0005) Read proportional band, integral time, and derivative time
006 (0006) Read cooling coefficient
007 (0007) Read dead band
008 (0008) Read manual reset value
009 (0009) Read hysteresis
010 (000A) Read control period
011 (000B) Read SP ramp time unit and set value
012 (000C) Read LBA detection time
013 (000D) Read MV at stop and PV error
014 (000E) Read MV limits
015 (000F) Read input digital filter
016 (0010) Read alarm hysteresis
017 (0011) Read input shifts
018 (0012) Read level 0 parameters
019 (0013) Read level 1 parameters 1
020 (0014) Read level 1 parameters 2
021 (0015) Read level 2 parameters 1
022 (0016) Read level 2 parameters 2
023 (0017) General-purpose read
Reads the process value.
Reads the set point during SP ramp.
Reads the MV (heating, cooling).
Reads the set point.
Reads alarm value 1, 2.
Reads the proportional band, integral (reset) time, and derivative
(rate) time
Reads the cooling coefficient.
Reads the dead band.
Reads the manual reset value.
Reads the hysteresis (heating, cooling).
Reads the control period (heating, cooling).
Reads the SP ramp time unit and
SP ramp set value.
Reads the LBA detection time.
Reads the MV at stop and the MV at PV error.
Reads the MV limits.
Reads the input digital filter.
Reads the alarm 1, 2 hysteresis.
Reads the input shift limits.
Reads parameters in level 0.
Reads parameters in level 1.
Reads parameters in level 1.
Reads parameters in level 2.
Reads parameters in level 2.
Reads the value of the specified parameter.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
465
E5
@K Digital Controller Read Protocol
Appendix F
Connection Configuration
The connection configuration for using the E5
@K Digital Controller Read Protocol is shown below.
RS-232C Connection
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
E5
#K
RS-232C
RS-232C port
→
RS-232C
E5
#K
Serial Communications Unit/Board
RS-232C: D-sub 9 pin female
Signal name
FG
SD
RD
RTS
CTS
DSR
DST
SG
Pin No.
RS-232C: Terminal block
Terminal No.
Signal name
13
14
1
SD
RD
SG
Shielded cable
Note 1.
The communications configuration is a one-to-one configuration and the maximum cable length is 15 m.
2.
Use shielded twisted-pair cable (AWG28i or greater).
466
E5
@K Digital Controller Read Protocol
RS-485 Connection
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-485 port
Appendix F
E5
#K
→
RS-485
E5
#K
→
RS-485
Up to 31 units can be connected.
E5
#K
→
RS-485
Note 1.
The communications configuration is a one-to-one configuration or a one-to-N configuration. In the one-to-N configuration, up to 32 units including the Serial Communications Unit/Board can be connected.
2.
The maximum cable length is 500 m. Use a shielded twisted-pair cable for the cable (AWG28i or greater).
3.
Connect a terminator only at both ends of the transmission path. For instance, in the example shown below, connect a terminator to the Serial Communications Unit/Board and unit No.30 and do not connect any terminator to units No.0 to No.29. Use a resistance of 120
Ω (1/2W) for the terminators (the total resistance of both ends must be 54
Ω or more).
Serial Communications Board/Unit
RS-485: D-sub
9 pin female
Pin No.
Shielded cable
1
2
FG
E5CK (No. 0)
RS-485: Terminal block
Terminal No.
13
14
A
B
E5CK (No. 30)
RS-485: Terminal block
Terminal No.
13
14
A
B
A<B: [1] Mark
A>B: [0] Space
Terminator (120
Ω, 1/2 W)
467
E5
@K Digital Controller Read Protocol
Appendix F
Read Process Value (Sequence No. 000 (Hex 0000))
Reads the process value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Process value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Process value (4 digits BCD)
Data
0002
Scaling lower limit to upper limit
Read Set Point during SP Ramp (Sequence No. 001 (Hex 0001))
Reads the set point during the SP ramp and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Set point during SP ramp
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set point during SP ramp
(4 digits BCD)
Data
0002
Set point lower limit to upper limit
Read MV (Sequence No. 002 (Hex 0002))
Reads the MV (manipulated variable) for heating and cooling and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
468
E5
@K Digital Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
MV (heating)
MV (cooling)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
MV (heating) (4 digits BCD)
Appendix F
+2 MV (cooling) (4 digits BCD)
Data
0003
F050 to 1050, 0000 to 1050 for heating/cooling control
F indicates a negative value.
F050 to 1050
F indicates a negative value.
Read Set Point (Sequence No. 003 (Hex 0003))
Reads the set point and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined)
Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Set point
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set point (4 digits BCD)
Data
Data
0002
Set point lower limit to upper limit
Read Alarm Value (Sequence No. 004 (Hex 0004))
Reads alarm value 1 and alarm value 2 and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
469
E5
@K Digital Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Alarm value 1
Alarm value 2
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Alarm value 1 (4 digits BCD)
Appendix F
+2 Alarm value 2 (4 digits BCD)
Data
0003
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 005 (Hex 0005))
Reads the proportional band, integral time, and derivative time and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Proportional band
Integral time
Derivative time
+1
+2
+3
Offset
+0
Contents (data format)
Number of receive data words
(4 digits Hex)
Proportional band (4 digits BCD)
Integral time (4 digits BCD)
Derivative time (4 digits BCD)
0004
0000 to 9999
0000 to 3999
0000 to 3999
Data
Read Cooling Coefficient (Sequence No. 006 (Hex 0006))
Reads the cooling coefficient and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
470
E5
@K Digital Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Cooling coefficient
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Cooling coefficient (4 digits BCD)
Data
Appendix F
0002
0001 to 9999
Read Dead Band (Sequence No. 007 (Hex 0007))
Reads the dead band and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Dead band
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Dead band (4 digits BCD)
Data
Data
0002
A999 to 9999
F indicates a negative value and A indicates
–1.
Read Manual Reset Value (Sequence No. 008 (Hex 0008))
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Manual reset value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Manual reset value (4 digits BCD)
0002
0000 to 1000
Data
471
E5
@K Digital Controller Read Protocol
Read Hysteresis (Sequence No. 009 (Hex 0009))
Reads the hysteresis for heating and for cooling and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Hysteresis (heating)
Hysteresis (cooling)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
Hysteresis (heating)
(4 digits BCD)
Hysteresis (cooling)
(4 digits BCD)
0003
0001 to 9999
0001 to 9999
Data
Appendix F
Read Control Period (Sequence No. 010 (Hex 000A))
Reads the control period for heating and for cooling and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Control period (heating)
Control period (cooling)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
Control period (heating)
(4 digits BCD)
Control period (cooling)
(4 digits BCD)
0003
0001 to 0099
0001 to 0099
Data
472
E5
@K Digital Controller Read Protocol
Appendix F
Read SP Ramp Time Unit and Set Value (Sequence No. 011 (Hex
000B))
Reads the SP ramp time unit and SP ramp set value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
SP ramp time unit
SP ramp set value
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
SP ramp time unit (4 digits BCD)
SP ramp set value (4 digits BCD)
0003
0000: s, 0001: hr
0000 to 9999
Data
Read LBA Detection Time (Sequence No. 012 (Hex 000C))
Reads the LBA (loop break alarm) detection time and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
LBA detection time
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
LBA detection time (4 digits BCD)
0002
0000 to 9999
Data
473
E5
@K Digital Controller Read Protocol
Appendix F
Read MV at Stop Time and at PV Error (Sequence No.013 (Hex
000D))
Reads the MV at stop time and at PV error and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
MV at stop time
MV at PV error
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
MV at stop time (4 digits BCD)
+2 MV at PV error (4 digits BCD)
Data
0003
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
F050 to 1050
F indicates a negative value.
Read MV Limits (Sequence No. 014 (Hex 000E))
Reads the MV upper limit, MV lower limit, and MV change rate limit and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
MV upper limit
MV lower limit
MV change rate limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
MV upper limit (4 digits BCD)
Data
0004
MV lower limit + 1 to 1050
0000 to 1050 for heating/cooling control
474
E5
@K Digital Controller Read Protocol
Appendix F
Offset
+2
Contents (data format)
MV lower limit (4 digits BCD)
Data
F050 to MV upper limit –1
F indicates a negative value values.
A050 to 1050 for heating/cooling control
A indicates a negative value.
0000 to 1000 +3 MV change rate limit
(4 digits BCD)
Read Input Digital Filter (Sequence No. 015 (Hex 000F))
Reads the input digital filter and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Input digital filter
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Input digital filter (4 digits BCD)
0002
0000 to 9999
Data
Read Alarm Hysteresis (Sequence No. 016 (Hex 0010))
Reads the alarm 1 hysteresis and alarm 2 hysteresis and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Alarm 1 hysteresis
Alarm 2 hysteresis
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
Alarm 1 hysteresis
(4 digits BCD)
Alarm 2 hysteresis
(4 digits BCD)
0003
0001 to 9999
0001 to 9999
Data
475
E5
@K Digital Controller Read Protocol
Appendix F
Read Input Shift Limits (Sequence No. 017 (Hex 0011))
Reads the input shift upper limit and input shift lower limit and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Input shift upper limit
Input shift lower limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Input shift upper limit (4 digits BCD)
+2 Input shift lower limit (4 digits BCD)
Data
0003
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
Read Level 0 Parameters (Sequence No. 018 (Hex 0012))
Reads parameters in level 0 (process value, set point during SP ramp, MV (heating), MV (cooling), and set point) from multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined) Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
476
E5
@K Digital Controller Read Protocol
Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Number of receive data words
Process value
Set point during SP ramp
MV (heating)
MV (cooling)
Set point
+36
+37
+38
+39
+40
~
+0
+1
+2
+3
+4
+5
Process value
Set point during SP ramp
MV (heating)
MV (cooling)
Set point
~
+0
Offset
+1
+2
+3
+4
+5
+40
(max.)
1st unit
8th unit (max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Process value (4 digits BCD)
1st unit
Set point during SP ramp
(4 digits BCD)
1st unit
MV (heating) (4 digits BCD)
1st unit
MV (cooling) (4 digits BCD)
1st unit
Set point (4 digits BCD)
•
•
•
8th unit
Set point (4 digits BCD)
Data
Number of units
× 5 + 1
Scaling lower limit to upper limit
Set point lower limit to upper limit
F050 to 1050
F indicates a negative value.
0000 to 1050 for heating/cooling control
0000 to 1050
Set point lower limit to upper limit
Set point lower limit to upper limit
Read Level 1 Parameters 1 (Sequence No. 019 (Hex 0013))
Reads parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and derivative time) from multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+9
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
477
E5
@K Digital Controller Read Protocol
Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Number of receive data words
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
+43
+44
+45
+46
+5
+6
~
+47
+48
+0
+1
+2
+3
+4
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
~
+0
Offset
+1
1st unit
8th unit (max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Alarm value 1 (4 digits BCD)
+2
+3
+4
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Alarm value 3 (4 digits BCD)
Data
Number of units
× 6 + 1
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
0001 to 9999
+5
+6
+48
(max.)
1st unit
Proportional band
(4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
•
•
•
8th unit
Derivative time (4 digits BCD)
0000 to 3999
0000 to 3999
0000 to 3999
Read Level 1 Parameters 2 (Sequence No. 020 (Hex 0014))
Reads parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) from multiple units and stores the results in the specified words.
478
E5
@K Digital Controller Read Protocol
Appendix F
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+9
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
~
Number of receive data words
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
+50
+51
+52
+53
+54
+55
+56
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
~
1st unit
8th unit (max.)
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Cooling coefficient (4 digits BCD)
1st unit
Dead band (4 digits BCD)
+3
+4
+5
+6
+7
1st unit
Manual reset value
(4 digits BCD)
1st unit
Hysteresis (heating)
(4 digits BCD)
1st unit
Hysteresis (cooling) (4 digits BCD)
1st unit
Control period (heating)
(4 digits BCD)
1st unit
Control period (cooling)
(4 digits BCD)
Data
Number of units
× 7 + 1
0001 to 9999
A999 to 9999
F indicates a negative value and A indicates
–1.
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
479
E5
@K Digital Controller Read Protocol
Appendix F
Offset
+56
(max.)
Contents (data format)
•
•
•
8th unit
Control period (cooling)
(4 digits BCD)
0001 to 0099
Data
Read Level 2 Parameters 1 (Sequence No. 021 (Hex 0015))
Reads parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop, MV at PV
Error, MV upper limit, MV lower limit, and MV change rate limit) from multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Number of receive data words
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
+57
+58
+59
+60
+61
+62
+63
+64
+3
+4
+5
+6
+0
+1
+2
+7
+8
~
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
~
1st unit
8th unit (max.)
480
E5
@K Digital Controller Read Protocol
Appendix F
Offset
+0
+1
+2
+3
+4
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
SP ramp time unit (4 digits BCD)
1st unit
SP ramp set value (4 digits BCD)
1st unit
LBA detection time (4 digits BCD)
1st unit
MV at stop (4 digits BCD)
+5
+6
+7
1st unit
MV at PV error (4 digits BCD)
1st unit
MV upper limit (4 digits BCD)
1st unit
MV lower limit (4 digits BCD)
Data
Number of units
× 8 + 1
0000: s, 0001: hr
0000 to 9999
0000 to 9999
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
F050 to 1050
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
MV lower limit + 1 to 1050
0000 to 1050 for heating/cooling control
F050 to MV upper limit –1
F indicates a negative value.
A050 to 1050 for heating/cooling control
A indicates a negative value.
0000 to 1000 +8
+64
(max.)
1st unit
MV change rate limit
(4 digits BCD)
•
•
•
8th unit
MV change rate limit
(4 digits BCD)
0000 to 1000
Read Level 2 Parameters 2 (Sequence No. 022 (Hex 0016))
Reads parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) from multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
481
E5
@K Digital Controller Read Protocol
Appendix F
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+44
+45
+46
+47
+5
+6
+43
~
+48
Number of receive data words
Input digital filter
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
Input digital filter
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
+0
Offset
+1
+2
+3
+4
+5
+6
+48
(max.)
~
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Input digital filter (4 digits BCD)
1st unit
Alarm 1 hysteresis
(4 digits BCD)
1st unit
Alarm 2 hysteresis
(4 digits BCD)
1st unit
Alarm 3 hysteresis
(4 digits BCD)
1st unit
Input shift upper limit (4 digits BCD)
1st unit
Input shift lower limit (4 digits BCD)
•
•
•
8th unit
Input shift lower limit (4 digits BCD)
1st unit
8th unit (max.)
Data
Number of units
× 6 + 1
0000 to 9999
0001 to 9999
0001 to 9999
0001 to 9999
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
A999 to 9999
F indicates a negative value and A indicates –1.
482
E5
@K Digital Controller Read Protocol
Appendix F
General-purpose Read (Sequence No. 023 (Hex 0017))
Reads the specified parameter and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
Number of send data words
(Undefined)
Unit No.
(Undefined)
Parameter No.
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Parameter No. (2 digits BCD)
0003 (fixed)
Data
00 to 31
Refer to the manual for the E5
@K.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Read data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Read data (4 digits BCD)
0002
Data
A999 to 9999
F indicates a negative value and A indicates
–1.
Note To read parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No. 075) in advance.
483
Appendix G
E5
@K Digital Controller Write Protocol
The E5
@K Digital Controller Write Protocol writes and controls various settings in remote mode for the Controller connected to the Serial Communications Unit/Board via RS-232C or RS-485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The following table shows the structure of the E5
@K Digital Controller Write Protocol.
Sequence
No.
Communications sequence name
Function
050 (0032) Write set point
051 (0033) Write alarm value
052 (0034) Write proportional band, integral time, and derivative time
053 (0035)
054 (0036)
Write cooling coefficient
Write dead band
Writes the set point.
Writes alarm value 1, 2.
Writes the proportional band, integral time, and derivative time.
Writes the cooling coefficient.
Writes the dead band.
055 (0037) Write manual reset value Writes the manual reset value.
056 (0038) Write hysteresis Writes the hysteresis (heating, cooling)
057 (0039) Write control period
058 (003A) Write SP ramp time units and set value
Writes the control period (heating, cooling)
Writes the SP ramp time unit and SP ramp set value.
059 (003B) Write LBA detection time Writes the LBA detection time.
060 (003C) Write MV at stop time and
PV error
Writes the MV at stop and the MV at PLC error.
061 (003D) Write MV limits
062 (003E) Write input digital filter
Writes the MV limits.
Writes the input digital filter.
063 (003F) Write alarm hysteresis
064 (0040) Write input shift values
Writes alarm 1, 2 hysteresis.
Writes the input shift values.
065 (0041) Write level 0 parameters Writes parameters in level 0.
066 (0042) Write level 1 parameters 1 Writes parameters in level 1.
067 (0043) Write level 1 parameters 2 Writes parameters in level 1.
068 (0044) Write level 2 parameters 1 Writes parameters in level 2.
069 (0045) Write level 2 parameters 2 Writes parameters in level 2.
070 (0046) General-purpose write Writes the value of the specified parameter.
Switches the setting level to level 0.
071 (0047) Switch to level 0
(software reset)
072 (0048) Run/stop
073 (0049) Remote/local
074 (004A) Execute/cancel AT
Initiates Run or Stop.
Switches the mode to remote or local.
Executes or cancels AT.
075 (004B) Switch to level 1
076 (004C) Software reset
Switches the setting level to level 1.
Resets the E5
@K.
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
485
E5
@K Digital Controller Write Protocol
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
Appendix G
Connections
The connections are the same as that for the E5
@K Digital Controller Read Protocol.
Write Set Point (Sequence No. 050 (Hex 0032))
Writes the set point.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Read data
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Set point (4 digits BCD)
0003 (fixed)
Data
00 to 31
Set point lower limit to upper limit
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Alarm Value (Sequence No. 051 (Hex 0033))
Writes alarm value 1 and alarm value 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Alarm value 1
Alarm value 2
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Alarm value 1 (4 digits BCD)
Alarm value 2 (4 digits BCD)
0004 (fixed)
00 to 31
0000 to 999
0000 to 9999
Receive Data Word Allocation (3rd Operand of PMCR(260))
None.
Data
486
E5
@K Digital Controller Write Protocol
Appendix G
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 052 (Hex 0034))
Writes the proportional band, integral time, and derivative time.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
Proportional band
Integral time
Derivative time
+1
+2
+3
+4
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Proportional band (4 digits BCD)
Integral time (4 digits BCD)
Derivative time (4 digits BCD)
0005 (fixed)
00 to 31
0001 to 9999
0000 to 3999
0000 to 3999
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Cooling Coefficient (Sequence No. 053 (Hex 0035))
Writes the cooling coefficient.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Cooling coefficient
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Cooling coefficient (4 digits BCD)
0003 (fixed)
00 to 31
0001 to 9999
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Dead Band (Sequence No. 054 (Hex 0036))
Writes the dead band.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Dead band
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Dead band (4 digits BCD)
0003 (fixed)
00 to 31
0000 to 9999
Data
487
E5
@K Digital Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Appendix G
Write Manual Reset Value (Sequence No. 055 (Hex 0037))
Writes the manual reset value.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Manual reset value
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Manual reset value (4 digits BCD)
0003 (fixed)
00 to 31
0000 to 1000
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Hysteresis (Sequence No. 056 (Hex 0038))
Writes the hysteresis for heating and for cooling.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Hysteresis (heating)
Hysteresis (cooling)
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Hysteresis (heating)
(4 digits BCD)
Hysteresis (cooling)
(4 digits BCD)
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Write Control Period (Sequence No. 057 (Hex 0039))
Writes the control period for heating and for cooling.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Control period (heating)
Control period (cooling)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0004 (fixed)
00 to 31
Data
488
E5
@K Digital Controller Write Protocol
Appendix G
Offset
+2
+3
Contents (data format)
Control period (heating)
(4 digits BCD)
Control period (cooling)
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0001 to 0099
0001 to 0099
Data
Write SP Ramp Time Unit and Set Value (Sequence No. 058 (Hex
003A))
Writes the SP ramp time unit and SP ramp set value.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
SP ramp time unit
SP ramp set value
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
SP ramp time unit (4 digits BCD)
+3 SP ramp set value (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0004 (fixed)
00 to 31
0000: Minutes
0001: Hours
0000 to 9999
Write LBA Detection Time (Sequence No. 059 (Hex 003B))
Writes the LBA detection time.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
LBA detection time
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
LBA detection time (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0003 (fixed)
00 to 31
0000 to 9999
489
E5
@K Digital Controller Write Protocol
Appendix G
Write MV at Stop Time and at PV Error (Sequence No. 060 (Hex
003C))
Writes the MV at stop time and the MV at PV error.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
MV at stop time
MV at PV error
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
MV at stop time (4 digits BCD)
MV at PV error (4 digits BCD)
0004 (fixed)
00 to 31
0000 to 1050
0000 to 1050
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write MV Limits (Sequence No. 061 (Hex 003D))
Writes the MV upper limit, MV lower limit, and MV change rate limit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
MV upper limit
MV lower limit
MV change rate limit
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
MV upper limit (4 digits BCD)
+3
+4
MV lower limit (4 digits BCD)
MV change rate limit
(4 digits BCD)
0005 (fixed)
Data
00 to 31
MV lower limit + 1 to 1050
Heating/cooling control time: 0000 to 1050
0000 to MV upper limit – 1
0000 to 1000
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
490
E5
@K Digital Controller Write Protocol
Write Input Digital Filter (Sequence No. 062 (Hex 003E))
Writes the input digital filter.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Input digital filter
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Input digital filter (4 digits BCD)
0003 (fixed)
00 to 31
0000 to 9999
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Alarm Hysteresis (Sequence No. 063 (Hex 003F))
Writes the alarm 1 hysteresis and alarm 2 hysteresis.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Alarm 1 hysteresis
Alarm 2 hysteresis
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Alarm 1 hysteresis
(4 digits BCD)
Alarm 2 hysteresis
(4 digits BCD)
0004 (fixed)
00 to 31
0001 to 9999
0001 to 9999
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Input Shift Value (Sequence No. 064 (Hex 0040))
Writes the input shift upper limit and input shift lower limit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Input shift upper limit
Input shift lower limit
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Input shift upper limit (4 digits BCD)
Input shift lower limit (4 digits BCD)
0004 (fixed)
00 to 31
0000 to 9999
0000 to 9999
Data
Appendix G
491
E5
@K Digital Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Appendix G
Write Level 0 Parameters (Sequence No. 065 (Hex 0041))
Writes parameters (set points) in level 0 to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+5
~
+16
+17
+0
+1
+2
+3
+4
Number of send data words
Number of units
(Undefined)
Set point
Unit No.
Set point
Set point
~
1st unit
2nd unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
Data
Number of units
× 2 + 2
0001 to 0008
00 to 31
Set point lower limit to upper limit
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Set point (4 digits BCD)
•
•
•
8th unit
Set point (4 digits BCD)
Set point lower limit to upper limit
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
492
E5
@K Digital Controller Write Protocol
Appendix G
Write Level 1 Parameters 1 (Sequence No. 066 (Hex 0042))
Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and derivative time) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
~
+51
+52
+53
+54
+55
+56
+57
Number of send data words
Number of units
(Undefined) Unit No.
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
(Undefined) Unit No.
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
~
1st unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 7 + 2
0001 to 0008
00 to 31
+3
Unit No. (2 digits BCD)
1st unit
Alarm value 1 (4 digits BCD)
+4
+5
+6
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Alarm value 3 (4 digits BCD)
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
0001 to 9999
+7
+8
+57
(max.)
1st unit
Proportional band (4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
•
•
•
8th unit
Derivative time (4 digits BCD)
0000 to 3999
0000 to 3999
0000 to 3999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
493
E5
@K Digital Controller Write Protocol
Appendix G
Write Level 1 Parameter 2 (Sequence No. 067 (Hex 0043))
Writes parameters in level 1 (cooling coefficient, dead band, manual reset value, hysteresis (heating), hysteresis (cooling), control period (heating), and control period (cooling)) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+58
+59
+60
+61
+62
+63
+64
+65
+0
+1
+6
+7
+8
+2
+3
+4
+5
+9
~
Number of send data words
Number of units
(Undefined) Unit No.
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
(Undefined) Unit No.
Cooling coefficient
Dead band
Manual reset value
Hysteresis (heating)
Hysteresis (cooling)
Control period (heating)
Control period (cooling)
~
1st unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
Data
Number of units
× 8 + 2
0001 to 0008
00 to 31
0001 to 9999
+4
+5
+6
+7
+8
+9
+65
(max.)
Unit No. (2 digits BCD)
1st unit
Cooling coefficient (4 digits BCD)
1st unit
Dead band (4 digits BCD)
1st unit
Manual reset value (4 digits BCD)
1st unit
Hysteresis (heating)
(4 digits BCD)
1st unit
Hysteresis (cooling)
(4 digits BCD)
1st unit
Control period (heating)
(4 digits BCD)
1st unit
Control period (cooling)
(4 digits BCD)
•
•
•
8th unit
Control period (cooling)
(4 digits BCD)
0000 to 9999
0000 to 1000
0001 to 9999
0001 to 9999
0001 to 0099
0001 to 0099
0001 to 0099
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
494
E5
@K Digital Controller Write Protocol
Appendix G
Write Level 2 Parameters 1 (Sequence No. 068 (Hex 0044))
Writes parameters in level 2 (SP ramp time unit, SP ramp set value, LBA detection time, MV at stop time, MV at
PV error, MV upper limit, MV lower limit, and MV change rate limit) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+66
+67
+68
+69
+70
+71
+72
+73
+2
+3
+4
+5
+6
+7
+8
+9
+10
+65
~
Number of send data words
Number of units
(Undefined)
SP ramp time unit
Unit No.
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
(Undefined)
SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
Unit No.
~
1st unit
8th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits BCD)
Data
Number of units
× 9 + 2
0001 to 0008
00 to 31
+3
+4
+5
+6
+7
+8
+9
+10
+73
(max.)
Unit No. (2 digits BCD)
1st unit
SP ramp time unit (4 digits BCD)
1st unit
SP ramp set value (4 digits BCD)
1st unit
LBA detection time (4 digits BCD)
1st unit
MV at stop (4 digits BCD)
1st unit
MV at PV error (4 digits BCD)
1st unit
MV upper limit (4 digits BCD)
1st unit
MV lower limit (4 digits BCD)
1st unit
MV change rate limit (4 digits BCD)
•
•
•
8th unit
MV change rate limit
(4 digits BCD)
0000 to 0001
0000 to 9999
0000 to 9999
0000 to 1050
0000 to 1050
MV lower limit + 1 to 1050
0000 to MV upper limit –1
0000 to 1000
0000 to 1000
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
495
E5
@K Digital Controller Write Protocol
Appendix G
Write Level 2 Parameters 2 (Sequence No. 069 (Hex 0045))
Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input shift upper limit, and input shift lower limit) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
~
Number of send data words
Number of units
(Undefined) Unit No.
Input digital filter alarm 1 hysteresis alarm 2 hysteresis alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
+51
+52
+53
+54
+55
+56
+57
(Undefined)
Input digital filter alarm 1 hysteresis alarm 2 hysteresis
Unit No.
alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
~
1st unit
8th unit (max.)
+0
Offset
+1
+3
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits BCD)
Data
Number of units
× 7 + 2
0001 to 0008
00 to 31
0000 to 9999
+4
+5
+6
+7
+8
+57
(max.)
Unit No. (2 digits BCD)
1st unit
Input digital filter (4 digits BCD)
1st unit
Alarm 1 hysteresis
(4 digits BCD)
1st unit
Alarm 2 hysteresis
(4 digits BCD)
1st unit
Alarm 3 hysteresis
(4 digits BCD)
1st unit
Input shift upper limit (4 digits BCD)
1st unit
Input shift lower limit (4 digits BCD)
•
•
•
8th unit
Input shift lower limit (4 digits BCD)
0001 to 9999
0001 to 9999
0001 to 0099
000 to 9999
000 to 9999
000 to 9999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
496
E5
@K Digital Controller Write Protocol
Appendix G
General-purpose Write (Sequence No. 070 (Hex 0046))
Writes the specified parameter.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
(Undefined)
Parameter No.
Write data
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Parameter No. (2 digits BCD)
Write data (4 digits BCD)
Data
0004 (fixed)
00 to 31
Refer to the manual of E5
@K.
0000 to 9999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note To write parameters in the setup mode or extended mode, execute Switch to Level 1 (Sequence No.
075) in advance.
Switch to Level 0 (Software Reset) (Sequence No. 071 (Hex
0047))
Resets the operation of the E5
@K and waits until communications are enabled. This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+3
~
+9
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
+2 to 9 Unit No.
(2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note When this sequence is executed, a software reset command is issued and the operation of the E5
@K is reset (equivalent to turning on the power supply). About five seconds will be required until communications are enabled.
497
E5
@K Digital Controller Write Protocol
Appendix G
Run/Stop (Sequence No. 072 (Hex 0048))
Switches the mode to Run or Stop according to the command code. This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+5
+16
~
+17
+0
+1
+2
+3
+4
Number of send data words
Number of units
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
+0
Offset
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 2 + 2
0001 to 0008
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
•
•
•
8th unit
Command code (4 digits BCD)
0000: Run
0001: Stop
0000: Run
0001: Stop
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Remote/Local (Sequence No. 073 (Hex 0049))
Switches to remote operation or local operation according to the command mode. This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
+16
+17
Number of send data words
Number of units
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
498
E5
@K Digital Controller Write Protocol
Appendix G
+0
Offset
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+17
(max.)
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
•
•
•
8th unit
Command code (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Number of units
× 2 + 2
0001 to 0008
00 to 31
0000: Local
0001: Remote
0000: Local
0001: Remote
Execute/Cancel AT (Sequence No. 074 (Hex 004A))
Executes or cancels AT (autotuning) according to the command code. This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
+16
+17
Number of send data words
Number of units
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
(Undefined)
Unit No.
Command code
~
1st unit
2nd unit
8th unit (max.)
Data
Number of units
× 2 + 2
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1
+3
Number of units (4 digits Hex) unit
Unit No. (2 digits BCD)
1st unit
Command code (4 digits BCD)
+17
(max.)
•
•
•
8th unit
Command code (4 digits BCD)
0001 to 0008
00 to 31
0000: Stop
0001: Execute AT 40%
0002: Execute AT 100%
0000: Stop
0001: Execute AT 40%
0002: Execute AT 100%
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
499
E5
@K Digital Controller Write Protocol
Appendix G
Switch to Level 1 (Sequence No. 075 (Hex 004B))
Switches the setting level to level 1 (setup mode, extended mode). This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+9
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Software Reset (Sequence No. 076 (Hex 004C))
Resets the operation of the E5
@K (equivalent to turning on the power supply). This sequence can be executed for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+9
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined)
Unit No.
~
(max.)
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+2 to 9 Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 0008
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Communications with the E5
@K are disabled for about five seconds after this sequence is executed.
500
Appendix H
E5ZE Temperature Controller Read Protocol
The E5ZE Temperature Controller Read Protocol reads and controls various parameters in remote mode for the Temperature Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422/485 cable.
Note All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks.
Structure of the Protocol
The following table shows the structure of the E5ZE Temperature Controller Read Protocol
Sequence
No.
Communications sequence name
Function
100 (0064) Read set point
101 (0065) Read process value
102 (0066) Read output value
103 (0067) Read set point, process value, and output value
104 (0068) Read proportional band, integral time, and derivative time
Reads the set points.
Reads the process values.
Reads the output values.
Reads the set points, process values, and output values.
Reads the proportional bands, integral times, and derivative times.
Reads the control periods.
Reads the output modes.
105 (0069) Read control period
106 (006A) Read output mode
107 (006B) Read alarm mode
108 (006C) Read alarm temperature
109 (006D) Read hysteresis
110 (006E) Read operation status
111 (006F) Read error status
112 (0070) Read setting unit
113 (0071) Read input shift value
114 (0072) Read manual reset value
115 (0073) Read ramp value
116 (0074) Read present set point
117 (0075) Read output value limits
118 (0076) Read output value change rate limit
119 (0077) Read HB alarm and HS alarm valid channels
120 (0078) Read heater burnout/SSR failure detection currents
121 (0079) Read heater current and SSR leakage current
122 (007A) Read dead band/overlap band
123 (007B) Read cooling coefficient
Reads the alarm modes.
Reads the alarm temperatures.
Reads the hysteresis.
Reads the operation status.
Reads the error status.
Reads the setting units.
Reads the input shift values.
Reads the manual reset values.
Reads the ramp values.
Reads the present set points.
Reads the output value limits.
Reads the output value change rate limits.
Reads the HB alarm and HS alarm valid channels.
Reads the heater burnout/SSR failure detection currents.
Reads the heater currents and
SSR leakage currents.
Reads the dead bands and overlap bands.
Reads the cooling coefficients.
Ladder interface
Send word allocation
Yes
Yes
Yes
Yes
Receive word allocation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
501
E5ZE Temperature Controller Read Protocol
NO:
Send word allocation:
Receive word allocation:
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
Connections
This section shows connections for using the E5ZE Temperature Controller Read Protocol.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC
PS
E5ZE
RS-232C
RS-232C port
→
RS-232C
Appendix H
Pin
No.
Signal abbreviation
NC
SD
RD
RTS
CTS
DSR
SG
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
DTR
NC
NC
NC
NC
NC
Signal name
Signal ground or common return line
Send data
Receive data
Request to send
Clear to send
Data set ready
Data terminal ready
Disabled (Do not connect.)
Serial Communications
Unit/Board/Unit
RS-232C: D-sub
9-pin female
Signal name
Pin
No.
FG
SG
SD
RD
RTS
CTS
DSR
DTR
7
8
4
5
2
3
1
9
Shield
Abbrevi ation
SG
SD
RD
RTS
CTS
DSR
DTR
NC
---
Signal direction
Output
Input
Output
Input
Input
Output
---
E5ZE
RS-232C: D-sub
9-pin female
Pin
No.
Signal name
3
4
5
7
2
6
20
SG
SD
RD
RTS
CTS
DSR
DTR
LT1181CS or equivalent
V
TX
RX
7
Pin No.
4
5
2
3
6
20
1, 8 to 19, 21 to 25
Note 1.
The maximum communications cable length is 15 m. Use a shielded twisted-pair cable for the cable.
2.
Use a 25-pin D-sub Plug (OMRON XM2A-2501).
3.
Use XM2S-2511 Hood (OMRON) or an equivalent.
502
E5ZE Temperature Controller Read Protocol
Appendix H
RS422/485 Connections
• RS-485 2-wire Connections
3
4
5
1
2
Pin No.
Signal name
Disabled (Do not connect.)
Disabled (Do not connect.)
Signal ground
Terminal B (+ side)
Terminal A (– side)
Serial Communications Board/Unit
RS-485: D-sub
9-pin female
Signal name
Pin
No.
FG
B
A
Hood
2
1
Shield
Abbreviation
---
---
SG
B
A
---
Signal direction
---
---
I/O
I/O
Turn off the communications switch to disconnect terminating resistance.
SN751177N or equivalent
E5ZE
RS-485: Terminals
Terminating resistance
240
Ω
5 V
51 k
Ω
4.7 k
Ω
4.7 k
Ω RX
Terminal
Signal name
51 k
Ω
3
4
5
SG
B
A
TX
6.8 V
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Shield
E5ZE
RS-485: Terminals
Ter minal
Signal name
3
4
5
SG
B
A
Terminating resistance
240
Ω
Note Terminal block pins 1 and 2 cannot be connected. If these blocks are used, operation of the E5ZE may fail.
503
E5ZE Temperature Controller Read Protocol
Appendix H
• RS-422 4-wire Connections
3
4
1
2
5
Pin No.
Serial Communications Board/Unit
RS-422: D-sub
9-pin female
Signal name
Pin
No.
FG
SDB
Hood
2
SDA
RDB
RDA
1
8
6
Shield
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
Signal name
Receive data B
Receive data A
Signal ground
Send data B
Send data A
Abbreviation
RDB
RDA
SG
SDB
SDA
Signal direction
Input
Input
---
Output
Output
Turn off the communications switch to disconnect terminating resistance.
E5ZE
RS-422:
Terminals
Terminal
Signal name
1
RDB
RDA
2
4
SDB
5 SDA
Terminating resistance
Terminating resistance
240
Ω
Shield
4.7 k
Ω
5 V
51 k
Ω
4.7 k
Ω
6.8 V
51 k
Ω
4
5
1
2
Terminal block
Terminal
Signal name
Terminating resistance
240
Ω
RDB
RDA
SDB
SDA
SN751177N or equivalent
RX
TX
Terminating resistance
240
Ω
504
E5ZE Temperature Controller Read Protocol
Appendix H
Switch Settings
This section shows the switch settings for using the E5ZE Temperature Controller Read Protocol.
Communications Parameter DIP Switch
Pins 3 and 4: Terminating resistance
Pins 1 and 2: RS-422/RS-485
Unit Number Switch
Pins
3 and 4
Parameter
Terminating resistance
ON
OFF
Factory defaults: All OFF
RS-422
ON
ON
1 and 2 RS-422 or RS-485
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
RS-485
ON
ON
Baud Rate DIP Switch
Setting
0 1 2 3 4 5 6 7 8 9 A B C D E F
Unit No.
00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F
Factory defaults
Baud rate
(bps)
Pins 1 and 2
ON
1 2 3 4 5 6 7 8
19,200
Factory default: 9,600 bps
(pin 1 ON, pin 2 OFF)
9,600 4,800
ON
ON
ON
2,400
ON
505
E5ZE Temperature Controller Read Protocol
Appendix H
Read Set Point (Sequence No. 100 (Hex 0064))
Reads the set points and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+15
+16
Number of receive data words
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
~
Channel 0
Channel 7
Offset
+0
+1
+15
+16
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
Data
0011 (0017 decimal)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Set point (leftmost 1 digit) (1 digit BCD)
•
•
•
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Set point (leftmost 1 digit) (1 digit BCD)
Varies according to the temperature sensor type. Refer the manual for the E5ZE.
F indicates a negative value.
Read Process Value (Sequence No. 101 (Hex 0065))
Reads the process values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
506
E5ZE Temperature Controller Read Protocol
Appendix H
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
+15
+16
Process value (leftmost 1 digit)
(1 digit BCD)
•
•
•
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
~
Channel 0
Channel 1
Channel 7
Data
0011 (0017 decimal)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Read Output Values (Sequence No. 102 (Hex 0066))
Reads the output values of the control outputs and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+15
+16
~
Number of receive data words
Output value
Cooling output value
Output value
Cooling output value
Output value
Cooling output value
~
Channel 0
Channel 1
Channel 7
507
E5ZE Temperature Controller Read Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Output value (4 digits BCD)
+3
+4
+15
+16
Cooling output value (4 digits BCD)
Channel 1
Output value (4 digits BCD)
Channel 1
Cooling output value (4 digits BCD)
•
•
•
Channel 7
Output value (4 digits BCD)
Channel 7
Cooling output value (4 digits BCD)
Data
0011 (0017 decimal)
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Read Set Point, Process Value, and Output Value
(Sequence No. 103 (Hex 0067))
Reads the set points, process values, and output values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+5
~
+36
+37
+38
+0
+1
+2
+3
+4
+39
+40
Number of receive data words
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Output value
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Output value
~
Channel 0
Channel 7
508
E5ZE Temperature Controller Read Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
Data
0029 (0041 decimal)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
+3
+4
0
Output value (4 digits BCD)
•
•
•
+36 Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
+37
Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
+38
Channel 7
Set point (leftmost 1 digit) (1 digit BCD)
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
+39
+40
Set point (leftmost 1 digit) (1 digit BCD)
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
Channel 0
Output value (4 digits BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
0000 to 1000
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
0000 to 1000
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 104 (Hex 0068))
Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+22
+23
+24
+0
+1
+2
+3
~
Number of receive data words
Constant P
Constant I
Constant D
Constant P
Constant I
Constant D
~
Channel 0
Channel 7
509
E5ZE Temperature Controller Read Protocol
+22
+23
+24
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Constant P (4 digits BCD)
+3
Constant I (4 digits BCD)
Channel 0
Constant D (4 digits BCD)
•
•
•
Channel 7
Constant P (4 digits BCD)
Channel 7
Constant I (4 digits BCD)
Channel 7
Constant D (4 digits BCD)
Data
0019 (0025 decimal)
0000 to 9999
0000 to 3999
0000 to 3999
0000 to 9999
0000 to 3999
0000 to 3999
Read Control Period (Sequence No. 105 (Hex 0069))
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+15
+16
Number of receive data words
Control period
Cooling control period
Control period
Cooling control period
Control period
Cooling control period
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Control period (4 digits BCD)
Data
0011 (0017 decimal)
0001 to 0099
0001 to 0099
+15
+16
Cooling control period
(4 digits BCD)
•
•
•
Channel 7
Control period (4 digits BCD)
Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099
0001 to 0099
Appendix H
510
E5ZE Temperature Controller Read Protocol
Read Output Mode (Sequence No. 106 (Hex 006A))
Reads the output modes (normal/reverse) and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set code (2 digits Hex)
0002
00 to FF
Data
Read Alarm Mode (Sequence No. 107 (Hex 006B))
Reads the alarm modes and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+15
+16
Number of receive data words
(Undefined) Alarm 1 set code
(Undefined)
(Undefined)
Alarm 2 set code
Alarm 1 set code
(Undefined) Alarm 2 set code
(Undefined)
(Undefined)
Alarm 1 set code
Alarm 2 set code
~
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Alarm 1 set code (2 digits Hex)
+15
+16
Alarm 2 set code (2 digits Hex)
•
•
•
Channel 7
Alarm 1 set code (2 digits Hex)
Channel 7
Alarm 2 set code (2 digits Hex)
Channel 0
Channel 1
Channel 7
Data
0011 (0017 decimal)
00 to 0C
00 to 0C
00 to 0C
00 to 0C
Appendix H
511
E5ZE Temperature Controller Read Protocol
Appendix H
Read Alarm Temperatures (Sequence No. 108 (Hex 006C))
Reads the alarm temperatures and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+1
+2
+3
+4
+0
Number of receive data words
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
+29
~
+30
+31
+32
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (rightmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
~
Channel 0
Channel 7
`
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
+3
+4
+29
+30
+31
+32
Data
0021 (0033 decimal)
0000 to 9999
F indicates a negative number.
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
•
•
•
Channel 7
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 07
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
0000 to 9999
F indicates a negative number.
0000 to 0009
F indicates a negative number.
512
E5ZE Temperature Controller Read Protocol
Read Hysteresis (Sequence No. 109 (Hex 006D))
Reads the hysteresis and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
~
Channel 0
Channel 1
Channel 7
Data
0011 (0017 decimal)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Hysteresis (4 digits BCD)
+15
+16
Cooling hysteresis (4 digits BCD)
•
•
•
Channel 7
Hysteresis (4 digits BCD)
Channel 7
Cooling hysteresis (4 digits BCD)
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
Read Operation Status (Sequence No. 110 (Hex 006E))
Reads the operation status of the E5ZE and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Appendix H
513
E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+8
Number of receive data words
Status code
Status code
Status code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Status code (4 digits Hex)
~
Channel 0
Channel 1
Channel 7
0009
0000 to FFFF
0000 to FFFF
+8
Status code (4 digits Hex)
•
•
•
Channel 7
Status code (4 digits Hex)
0000 to FFFF
Data
Read Error Status (Sequence No. 111 (Hex 006F))
Reads the contents of errors if they have occurred and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Status code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Status code (4 digits BCD)
0002 (fixed)
00 to 0F
0002
0000 to FFFF
Data
Read Setting Unit (Sequence No. 112 (Hex 0070))
Reads the setting units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Appendix H
514
E5ZE Temperature Controller Read Protocol
Appendix H
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set code (4 digits BCD)
0002
0000: unit of 1
0001: unit of 0.1
Data
Read Input Shift Value (Sequence No. 113 (Hex 0071))
Reads the input shift values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+8
Number of receive data words
Input shift value
Input shift value
Input shift value
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Input shift value (4 digits BCD)
0009
Data
0000 to 0999
F indicates a negative number.
0000 to 0999
F indicates a negative number.
+8
Input shift value (4 digits BCD)
•
•
•
Channel 7
Input shift value (4 digits BCD)
0000 to 0999
F indicates a negative number.
Read Manual Reset Value (Sequence No. 114 (Hex 0072))
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
515
E5ZE Temperature Controller Read Protocol
Appendix H
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
Number of receive data words
Manual reset value
Manual reset value
+8
Manual reset value
Channel 0
~
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Manual reset value
(4 digits BCD)
0009
0000 to 1000
0000 to 1000
+8
Manual reset value
(4 digits BCD)
•
•
•
Channel 7
Manual reset value
(4 digits BCD)
0000 to 1000
Data
Read Ramp Value (Sequence No. 115 (Hex 0073))
Reads the ramp values and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
(Undefined)
Number of receive data words
Ramp value
Time unit
(Undefined)
(Undefined)
Ramp value
Time unit (Undefined)
+15
+16
(Undefined)
Time unit
Ramp value
(Undefined)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Ramp value (3 digits BCD)
~
Channel 0
Channel 1
Channel 7
Data
0011 (0017 decimal)
000 to 999
S: Seconds; M: Minutes; H: Hours
Time unit (one ASCII character)
•
•
•
516
E5ZE Temperature Controller Read Protocol
Appendix H
Offset
+15
+16
Contents (data format)
Channel 7
Ramp value (3 digits BCD)
Channel 7
Time unit (one ASCII character)
Data
000 to 999
S: Seconds; M: Minutes; H: Hours
Read Present Set Point (Sequence No. 116 (Hex 0074))
Reads the present set points during ramp operation and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+15
+16
Number of receive data words
Present set point (rightmost 4 digits)
Present set point (leftmost 1 digit)
Present set point (rightmost 4 digits)
Present set point (leftmost 1 digit)
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Present set point (rightmost 4 digits)
(4 digits BCD)
~
Channel 0
Channel 7
Data
0011 (0017 decimal)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
+15
+16
Present set point (leftmost 1 digit)
(1 digit BCD)
•
•
•
Channel 7
Present set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Present set point (leftmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
F indicates a negative value.
Read Output Value Limit (Sequence No. 117 (Hex 0075))
Reads the output value limits and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
517
E5ZE Temperature Controller Read Protocol
Appendix H
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0 Number of receive data words
+1
+2
Output value lower limit
Output value upper limit
+3
Cooling control output value lower limit
+4
Cooling control output value upper limit
~
+29
+30
Output value lower limit
Output value upper limit
+31
Cooling control output value lower limit
+32
Cooling control output value upper limit
~
Channel 0
Channel 7
Offset
+0
+1
+3
+4
+31
+32
Contents (data format) Data
Number of receive data words
(4 digits Hex)
Channel 0
Output value lower limit
(4 digits BCD)
0021 (0033 decimal)
0000 to 1000
0000 to 1000
Output value upper limit
(4 digits BCD)
Channel 0
Cooling control output value upper limit
(4 digits BCD)
Channel 0
Cooling control output value upper limit
(4 digits BCD)
•
•
•
Channel 7
Cooling control output value upper limit
(4 digits BCD)
Channel 7
Cooling control output value upper limit
(4 digits BCD)
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Read Output Value Change Rate Limit (Sequence No. 118 (Hex
0076))
Reads the output value change rate limits and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+8
~
Number of receive data words
Output value change rate limit
Output value change rate limit
Output value change rate limit
~
Channel 0
Channel 1
Channel 7
0002 (fixed)
00 to 0F
518
E5ZE Temperature Controller Read Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Output value change rate limit
(4 digits BCD)
+8
Output value change rate limit
(4 digits BCD)
•
•
•
Channel 7
Output value change rate limit
(4 digits BCD)
0009
0000 to 1000
0000 to 1000
0000 to 1000
Data
Read HB Alarm and HS Alarm Valid Channels
(Sequence No. 119 (Hex 0077))
Reads the valid or invalid channels for HB alarms and HS alarms and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Set code
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set code (2 digits Hex)
0009
00 to FF
Data
Read Heater Burnout and SSR Failure Detection Currents
(Sequence No. 120 (Hex 0078))
Reads the heater burnout and SSR failure detection currents and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
519
E5ZE Temperature Controller Read Protocol
Appendix H
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current
+4
~
+15
+16
Heater burnout detection current
SSR failure detection current
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Heater burnout detection current
(4 digits BCD)
+15
+16
SSR failure detection current
(4 digits BCD)
•
•
•
Channel 7
Heater burnout detection current
(4 digits BCD)
Channel 7
SSR failure detection current
(4 digits BCD)
~
Channel 0
Channel 1
Channel 7
Data
0011 (0017 decimal)
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
Read Heater Current and SSR Leakage Current
(Sequence No.121 (Hex 0079))
Reads the heater currents and SSR leakage currents and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+15
~
+16
Number of receive data words
Heater current
SSR leakage current
Heater current
SSR leakage current
Heater current
SSR leakage current
~
Channel 0
Channel 1
Channel 7
520
E5ZE Temperature Controller Read Protocol
Appendix H
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Heater current
(4 digits BCD)
Data
0011 (0017 decimal)
0000 to 0500
0000 to 0500
+15
+16
SSR leakage current
(4 digits BCD)
•
•
•
Channel 7
Heater current
(4 digits BCD)
Channel 7
SSR leakage current
(4 digits BCD)
0000 to 0500
0000 to 0500
Note The read data will be 0000 for all channels for which HB and HS alarms are not enabled and for all channels for which control is stopped.
Read Dead Band/Overlap Band (Sequence No. 122 (Hex 007A))
Reads the dead bands/overlap bands and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0 Number of send data words
+1
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+8
Number of receive data words
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Channel 0
~
Channel 1
Channel 7
Offset Contents (data format)
+0
+1
Number of receive data words
(4 digits Hex)
Channel 0
Dead band/overlap band
(4 digits BCD)
1
Dead band/overlap band
(4 digits BCD)
•
•
•
+8 Channel 7
Dead band/overlap band
(4 digits BCD)
0009
Data
0000 to 0999
F indicates a number.
0000 to 0999
F indicates a number.
0000 to 0999
F indicates a number.
521
E5ZE Temperature Controller Read Protocol
Appendix H
Read Cooling Coefficient (Sequence No. 123 (Hex 007B))
Reads the cooling coefficients and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+8
Number of receive data words
Cooling coefficient
Cooling coefficient
Cooling coefficient
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Channel 0
Cooling coefficient (4 digits BCD)
0009
0000 to 0100
0000 to 0100
+8
Cooling coefficient (4 digits BCD)
•
•
•
Channel 7
Cooling coefficient (4 digits BCD)
0000 to 0100
Data
522
Appendix I
E5ZE Temperature Controller Write Protocol
The E5ZE Temperature Controller Write Protocol writes and controls various settings in remote mode for the
Temperature Controller connected via a RS-232C or RS-422/485 cable from the PLC via the Serial Communications Unit/Board.
Note 1.
Negative values cannot be written. All values must be set as unsigned BCD.
2.
All sequences in this appendix operate on memory bank 0 and cannot be used for other memory banks.
Structure of the Protocol
The following table shows the structure of the E5ZE Temperature Controller Write Protocol.
Sequence
No.
Communications sequence name Function
Write set point (setting unit 1) Writes the set points using a setting unit of 1.
Ladder interface
Send word allocation
Receive word allocation
Yes No 150
(0096)
151
(0097)
152
(0098)
153
(0099)
154
(009A)
155
(009B)
156
(009C)
157
(009D)
158
(009E)
159
(009F)
160
(00A0)
161
(00A1)
162
(00A2)
163
(00A3)
164
(00A4)
165
(00A5)
166
(00A6)
167
(00A7)
168
(00A8)
Write set point (setting unit 0.1)
Write proportional band, integral time, and derivative time
Write control period
Writes the set points using a setting unit of
0.1.
Writes the proportional bands, integral times, and derivative times.
Writes the control periods.
Write output mode
Write alarm mode
Write alarm temperature (setting unit
1)
Write alarm temperature (setting unit
0.1)
Write hysteresis
Start autotuning
Cancel autotuning
Write setting unit
Write input shift value
Write manual reset value
Write ramp value
Write manual output value
Write output value limit
Write output value change rate limit
Save settings
Writes the output modes.
Writes the alarm modes.
Writes the alarm temperatures using a setting unit of 1.
Writes the alarm temperatures using a setting unit of 0.1.
Writes the hysteresis.
Starts autotuning.
Cancels autotuning.
Writes the setting units.
Writes the input shift values.
Writes the manual reset values.
Writes the ramp values.
Writes the manual output values.
Writes the output value limits.
Write output value change rate limits.
Saves settings.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
523
E5ZE Temperature Controller Write Protocol
Appendix I
Sequence
No.
Communications sequence name Function
169
(00A9)
170
(00AA)
171
(00AB)
172
(00AC)
173
(00AD)
174
(00AE)
175
(00AF)
176
(00B0)
Initialize settings
Write HB alarm and HS alarm valid channels
Write heater burnout and SSR failure detection currents
Write dead band/overlap band
Write cooling coefficient
Start control
Stop operation or control
Start manual operation
Initializes settings.
Writes the HB alarm and HS alarm valid channels.
Writes the heater burnout and SSR failure detection currents.
Writes the dead bands/overlap bands.
Writes the cooling coefficients.
Starts temperature control.
Stops temperature control or manual operation.
Starts manual operation.
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
Connections
The connections are the same as that for the E5ZE Temperature Controller Read Protocol.
Write Set Point (Setting Unit 1) (Sequence No. 150 (Hex 0096))
Writes the set points using a setting unit of 1 (4 digits).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
+16
+17
Number of send data words
(Undefined) Unit No.
Set point
(Undefined)
Set point
(Undefined)
Set point
(Undefined)
~
Channel 0
Channel 1
Channel 7
524
E5ZE Temperature Controller Write Protocol
Appendix I
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Data
0012 (0018 decimal) (fixed)
00 to 0F
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Set point
(4 digits BCD)
•
•
•
+16 Channel 7
Set point
(4 digits BCD)
Not used
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
+17
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
---
Note When the setting unit for the set point is 0.1 (5 digits), use Write Set Point (Setting Unit 0.1), Sequence
No.151.
Write Set Point (Setting Unit 0.1) (Sequence No. 151 (Hex 0097))
Writes the set points using a setting unit of 0.1 (5 digits).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Number of send data words
(Undefined) Unit No.
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
+5
~
+16
+17
+0
+1
+2
+3
+4
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
Data
0012 (0018 decimal) (fixed)
00 to 0F
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
+16
+17
Set point (leftmost 1 digit) (1 digit BCD)
•
•
•
Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Channel 7
Set point (rightmost 1 digit)
(1 digit BCD)
Varies according to the temperature sensor type. Refer to the manual for the E5ZE.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note When the setting unit for the set point is 1 (4 digits), use Write Set Point (Setting Unit 1), Sequence
No.150.
525
E5ZE Temperature Controller Write Protocol
Appendix I
Write Proportional Band, Integral Time, and Derivative Time
(Sequence No. 152 (Hex 0098))
Writes the proportional bands (constant P), integral times (constant I), and derivative times (constant D).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
~
+23
+24
+25
Number of send data words
(Undefined) Unit No.
Constant P
Constant I
Constant D
Constant P
Constant I
Constant D
~
Channel 0
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Constant P (4 digits BCD)
+4
+23
+24
+25
Constant I (4 digits BCD)
Channel 0
Constant D (4 digits BCD)
•
•
•
Channel 7
Constant P (4 digits BCD)
Channel 7
Constant I (4 digits BCD)
Channel 7
Constant D (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
001A (0026 decimal) (fixed)
00 to 0F
0000 to 9999
0000 to 3999
0000 to 3999
0000 to 9999
0000 to 3999
0000 to 3999
526
E5ZE Temperature Controller Write Protocol
Write Control Period (Sequence No. 153 (Hex 0099))
Writes the control periods and cooling control periods.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+5
~
+16
+17
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
Control period
Cooling control period
Control period
Cooling control period
Control period
Cooling control period
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Control period (4 digits BCD)
Data
0012 (0018 decimal) (fixed)
00 to 0F
0001 to 0099
0001 to 0099
+4
Cooling control period
(4 digits BCD)
Channel 1
Control period (4 digits BCD)
0001 to 0099
0001 to 0099
+16
+17
Cooling control period
(4 digits BCD)
•
•
•
Channel 7
Control period (4 digits BCD)
Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099
0001 to 0099
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Appendix I
527
E5ZE Temperature Controller Write Protocol
Write Output Mode (Sequence No. 154 (Hex 009A))
Writes the output mode (normal/reverse).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
(Undefined) Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Write code (2 digits Hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0003 (fixed)
00 to 0F
00 to FF
Data
Write Alarm Mode (Sequence No. 155 (Hex 009B))
Writes the alarm modes for alarm 1 and alarm 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+16
~
+17
Number of send data words
(Undefined)
(Undefined)
(Undefined)
Unit No.
Alarm 1 set code
Alarm 2 set code
(Undefined)
(Undefined)
(Undefined)
(Undefined)
Alarm 1 set code
Alarm 2 set code
Alarm 1 set code alarm 2 set code
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set code (2 digits Hex)
Data
0012 (0018 decimal) (fixed)
00 to 0F
00 to 0C
00 to 0C
+4
Alarm 2 set code (2 digits Hex)
Channel 1
Alarm 1 set code (2 digits Hex)
00 to 0C
00 to 0C
+16
+17
Alarm 2 set code (2 digits Hex)
•
•
•
Channel 7
Alarm 1 set code (2 digits Hex)
Channel 7
Alarm 2 set code (2 digits Hex)
00 to 0C
00 to 0C
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Appendix I
528
E5ZE Temperature Controller Write Protocol
Appendix I
Write Alarm Temperature (Setting Unit 1) (Sequence No. 156
(Hex 009C))
Writes the alarm temperatures using a setting unit of 1 (4 digits)
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Number of send data words
(Undefined) Unit No.
Alarm 1 set value
(Undefined)
Alarm 2 set value
(Undefined)
+30
+31
~
+32
+33
+0
+1
+2
+3
+4
+5
Alarm 1 set value
(Undefined)
Alarm 2 set value
(Undefined)
~
Channel 0
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set value
(4 digits BCD)
Data
0022 (0034 decimal) (fixed)
00 to 0F
0000 to 9999
+4
+5
+32
Channel 0
Alarm 2 set value
(4 digits BCD)
Not used
•
•
•
Channel 7
Alarm 2 set value
(4 digits BCD)
Not used +33
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0000 to 9999
0000 to 9999
529
E5ZE Temperature Controller Write Protocol
Appendix I
Write Alarm Temperature (Setting Unit 0.1) (Sequence No. 157
(Hex 009D))
Writes the alarm temperatures using a setting unit of 0.1 (5 digits)
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+30
+31
+32
+33
+0
+1
+2
+3
+4
+5
~
Number of send data words
(Undefined) Unit No.
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
~
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Channel 0
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
+4
+5
+32
+33
00 to 0F
0000 to 9999
0000 to 0009
Alarm 1 set value (leftmost 1 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 0
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
•
•
•
Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
Channel 7
Alarm 2 set value (leftmost 1 digits)
(4 digits BCD)
0000 to 9999
0000 to 0009
0000 to 9999
0000 to 0009
Data
0022 (0034 decimal) (fixed)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
530
E5ZE Temperature Controller Write Protocol
Write Hysteresis (Sequence No. 158 (Hex 009E))
Writes the hysteresis for control outputs for ON/OFF control.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
+16
+17
Number of send data words
(Undefined) Unit No.
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
Hysteresis
Cooling hysteresis
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Hysteresis (4 digits BCD)
Data
0012 (0018 decimal) (fixed)
00 to 0F
0000 to 0999
0000 to 0999
+4
Cooling hysteresis (4 digits BCD)
Channel 1
Hysteresis (4 digits BCD)
0000 to 0999
0000 to 0999
+16
+17
Cooling hysteresis (4 digits BCD)
•
•
•
Channel 7
Hysteresis (4 digits BCD)
Channel 7
Cooling hysteresis (4 digits BCD)
0000 to 0999
0000 to 0999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Start Autotuning (Sequence No. 159 (Hex 009F))
Starts autotuning (AT).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
(Undefined)
Channel
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel (Channel) No. (1 digit BCD)
0003 (fixed)
00 to 0F
0 to 7
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Appendix I
531
E5ZE Temperature Controller Write Protocol
Cancel Autotuning (Sequence No. 160 (Hex 00A0))
Cancels Autotuning (AT) for all channels.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
Number of send data words
+1
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Write Setting Unit (Sequence No. 161 (Hex 00A1))
Writes the setting unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Write code (4 digits BCD)
0003 (fixed)
00 to 0F
0000: unit of 1
0001: unit of 0.1
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Input Shift Value (Sequence No. 162 (Hex 00A2))
Writes the input shift values.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
+5
+6
+7
+8
+9
+2
+3
+4
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Input shift value
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Appendix I
532
E5ZE Temperature Controller Write Protocol
Appendix I
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Input shift value (4 digits BCD)
+4
+8
+9
Input shift value (4 digits BCD)
Channel 2
Input shift value (4 digits BCD)
•
•
•
Channel 6
Input shift value (4 digits BCD)
Channel 7
Input shift value (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
000A (000A decimal) (fixed)
00 to 0F
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
Write Manual Reset Value (Sequence No. 163 (Hex 00A3))
Writes the manual reset values.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined) Unit No.
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Manual reset value
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Manual reset value
(4 digits BCD)
Data
000A (0010 decimal) (fixed)
00 to 0F
0000 to 1000
0000 to 1000
+4
+8
+9
Manual reset value
(4 digits BCD)
Channel 2
Manual reset value
(4 digits BCD)
•
•
•
Channel 6
Manual reset value
(4 digits BCD)
Channel 7
Manual reset value
(4 digits BCD)
0000 to 1000
0000 to 1000
0000 to 1000
533
E5ZE Temperature Controller Write Protocol
Appendix I
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Ramp Value (Sequence No. 164 (Hex 00A4))
Writes the ramp values.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
(Undefined)
(Undefined)
Time unit
(Undefined)
Time unit
+16
+17
Number of send data words
(Undefined)
Time unit
Unit No.
Ramp value
(Undefined)
Ramp value
(Undefined)
Ramp value
(Undefined)
~
Channel 0
Channel 1
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Ramp value (3 digits BCD)
Data
0012 (0018 decimal) (fixed)
00 to 0F
000 to 999
S: Seconds; M: Minutes; H: Hours
+4
Time unit (one ASCII character)
Channel 1
Ramp value (3 digits BCD)
000 to 999
S: Second M: Minute H: Hour
+16
+17
Time unit (one ASCII character)
•
•
•
Channel 7
Ramp value (3 digits BCD)
Channel 7
Time unit (one ASCII character)
000 to 999
S: Seconds; M: Minutes; H: Hours
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Manual Output Value (Sequence No. 165 (Hex 00A5))
Writes the manual output values for control output in manual operation.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
+16
+17
Number of send data words
(Undefined) Unit No.
Output value
Cooling output value
Output value
Cooling output value
Output value
Cooling output value
~
Channel 0
Channel 1
Channel 7
534
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Output value (4 digits BCD)
+4
Cooling output value
(4 digits BCD)
Channel 1
Output value (4 digits BCD)
+16
+17
Cooling output value
(4 digits BCD)
•
•
•
Channel 7
Output value (4 digits BCD)
Channel 7
Cooling output value
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
0012 (0018 decimal) (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Write Output Value Limit (Sequence No. 166 (Hex 00A6))
Writes the output value limits that restrict the values of the control outputs.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
~
Number of send data words
(Undefined) Unit No.
Output value lower limit
Output value upper limit
Cooling output value lower limit
Cooling output value upper limit
+30
+31
+32
+33
Output value lower limit
Output value upper limit
Cooling output value lower limit
Cooling output value upper limit
~
Channel 0
Channel 7
Appendix I
535
E5ZE Temperature Controller Write Protocol
Appendix I
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Output value lower limit
(4 digits BCD)
+4
+5
+32
+33
Output value upper limit
(4 digits BCD)
Channel 0
Cooling output value lower limit
(4 digits BCD)
Channel 0
Cooling output value upper limit
(4 digits BCD)
•
•
•
Channel 7
Cooling output value lower limit
(4 digits BCD)
Channel 7
Cooling output value upper limit
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
0022 (0034 decimal) (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Write Output Value Change Rate Limit (Sequence No. 167 (Hex
00A7))
Writes the output value change rate limits that restrict the rates of change in the control value output.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined) Unit No.
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Output change rate limit
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
536
E5ZE Temperature Controller Write Protocol
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Output change rate limit
(4 digits BCD)
+4
+8
+9
Output change rate limit
(4 digits BCD)
Channel 2
Output change rate limit
(4 digits BCD)
•
•
•
Channel 6
Output change rate limit
(4 digits BCD)
Channel 7
Output change rate limit
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
000A (0010 decimal) (fixed)
00 to 0F
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
0000 to 1000
Save Settings (Sequence No. 168 (Hex 00A8))
Saves the settings.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Initialize Settings (Sequence No. 169 (Hex 00A9))
Initializes all the settings to the factory defaults.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Appendix I
537
E5ZE Temperature Controller Write Protocol
Appendix I
Write HB and HS Alarm Valid Channels (Sequence No. 170 (Hex
00AA))
Writes the valid or invalid channels of HB alarm and HS alarm.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Unit No.
(Undefined) Write code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Write code (2 digits Hex)
0003 (fixed)
00 to 0F
00 to FF
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Heater Burnout and SSR Failure Detection Current
(Sequence No. 171 (Hex 00AB))
Writes the currents for detecting heater burnouts and SSR failures.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Number of send data words
(Undefined) Unit No.
Heater burnout detection current
SSR failure detection current
Heater burnout detection current
SSR failure detection current +5
~
+16
+17
+0
+1
+2
+3
+4
Heater burnout detection current
SSR failure detection current
~
Channel 0
Channel 1
Channel 7
538
E5ZE Temperature Controller Write Protocol
Appendix I
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Heater burnout detection current
(4 digits BCD)
+4
SSR failure detection current
(4 digits BCD)
Channel 1
Heater burnout detection current
(4 digits BCD)
+16
+17
SSR failure detection current
(4 digits BCD)
•
•
•
Channel 7
Heater burnout detection current
(4 digits BCD)
Channel 7
SSR failure detection current
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
0012 (0018 decimal) (fixed)
00 to 0F
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
0000 to 0500
Write Dead Band/Overlap Band (Sequence No. 172 (Hex 00AC))
Writes the dead bands or overlap bands for control outputs during heating/cooling control.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
(Undefined) Unit No.
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Dead band/overlap band
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
539
E5ZE Temperature Controller Write Protocol
Appendix I
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Dead band/overlap band
(4 digits BCD)
+4
+8
+9
Dead band/overlap band
(4 digits BCD)
Channel 2
Dead band/overlap band
(4 digits BCD)
•
•
•
Channel 6
Dead band/overlap band
(4 digits BCD)
Channel 7
Dead band/overlap band
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
000A (0010 decimal) (fixed)
00 to 0F
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
0000 to 0999
Write Cooling Coefficient (Sequence No. 173 (Hex 00AD))
Writes the cooling coefficients for the cooling proportional bands for heating/cooling control.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+5
+6
+7
+8
+9
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Cooling coefficient
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
Channel 0
Cooling coefficient (4 digits BCD)
Data
000A (0010 decimal) (fixed)
00 to 0F
0000 to 0100
0000 to 0100
+4
+8
+9
Cooling coefficient (4 digits BCD)
Channel 2
Cooling coefficient (4 digits BCD)
•
•
•
Channel 6
Cooling coefficient (4 digits BCD)
Channel 7
Cooling coefficient (4 digits BCD)
0000 to 0100
0000 to 0100
0000 to 0100
540
E5ZE Temperature Controller Write Protocol
Appendix I
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Start Control (Sequence No. 174 (Hex 00AE))
Starts temperature control for all channels in the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Stop Operation or Control (Sequence No. 175 (Hex 00AF))
Stops temperature control or manual operation for all channels of the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Start Manual Operation (Sequence No. 176 (Hex 00B0))
Starts manual operation based on the output values that were set for all channels of the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits Hex)
0002 (fixed)
00 to 0F
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
541
Appendix J
E5
@J Temperature Controller Protocol
The E5
@J Temperature Controller Protocol performs various settings and controls in remote mode for the Temperature Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The following table shows the structure of the E5
@J Temperature Controller Protocol.
Sequence
No.
Communications sequence name
Function
200 (00C8)
201 (00C9)
202 (00CA)
Select remote mode
Select local mode
Select backup mode
Switches the Controller to remote mode.
Switches the Controller to local mode.
Switches from set point write mode to backup mode.
203 (00CB) Select RAM write mode Switches from set point write mode to RAM write mode.
204 (00CC) Save set point
205 (00CD) Write parameters 1
Saves the set point.
Writes the set point, alarm value 1, alarm value 2, and heater burnout alarm value.
206 (00CE) Write parameters 2 Writes the proportional band, integral time, and derivative time.
207 (00CF) Write input shift value Writes the input shift value.
208 (00D0) Read parameters 1 Reads the set point, alarm value 1, alarm value 2, and heater burnout alarm value.
209 (00D1) Read parameters 2 Reads the proportional band, integral time, and derivative time.
210 (00D2) Read input shift value Reads the input shift value and writes it in
IOM.
211 (00D3) Read output value
212 (00D4) Read process value
213 (00D5)
214 (00D6)
Read set point limit
Read heater current
Reads the output value and stores it in IOM.
Reads the process value and stores it in
IOM.
Reads the set point limits and stores them in
IOM.
Reads the heater current and stores it in
IOM.
215 (00D7) Read initial status Reads the initial status and stores it in IOM.
216 (00D8) General-purpose write Writes the specified parameter by setting a header code.
217 (00D9) General-purpose read Reads the specified parameter by setting a header code.
Ladder interface
Send word allocation
Yes
Yes
Yes
Receive word allocation
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation:Set the constant 0000 for the 4th operand (D).
543
E5
@J Temperature Controller Protocol
Appendix J
Connections
The connections for using the E5
@J Temperature Controller Protocol are shown below.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
E5
#J
PLC PS
RS-232C
RS-232C port
Signal name
Signal ground or common return line
Send data
Receive data
Serial Communications
Unit/Board
RS-232C: D-sub
9-pin female
Signal
name
Pin
No.
FG
SG
SD
RD
RTS
CTS
DSR
DTR
5
7
8
3
4
1
9
2
Shield
SD
RD
→
RS-232C
Abbreviation
SG
Signal direction
---
Pin No.
25, 27
Output
Input
E5AJ
RS-232C:
Terminal Block
Terminal
Signal
name
25
27
SG
SG
26
28
SD
RD
MAX232C or equivalent
TX
RX
26
28
Note 1.
The connection configuration is a one-to-one configuration and the maximum cable length is 15 m.
2.
Use shielded twisted-pair cable.
544
E5
@J Temperature Controller Protocol
RS-422A/485 Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-422A/485 port
E5
#J
→
RS-422A/485
E5
#J
Appendix J
→
RS-422A/485
Up to 32 units can be connected.
E5
#J
→
RS-422A/485
• RS-422A 4-wire connections
Signal name
Send data A
Send data B
Receive data A
Receive data B
Signal ground
Serial Communications Board/Unit
RS-422A: D-sub
9-pin female
Signal name
Pin
No.
Shell
E5AJ
RS-422A:
Terminal Block
Terminal
Signal name
Terminating resistance
Abbreviation
SDA
SDB
RDA
RDB
SG
Signal direction
Output
Output
Input
Input
---
26
25
28
29
27
Pin No.
SN751177N or equivalent
Shield
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
Shield
Terminating resistance
240
Ω
E5AJ
RS-422A:
Terminal Block
Terminal
Signal name
Terminating resistance (240
Ω) is connected via the terminator switch.
Terminator switch
545
E5
@J Temperature Controller Protocol
Appendix J
• RS-485 2-wire Connections
Signal name
Terminal A
Terminal B
Signal ground
Serial Communications Board/Unit
RS-485: D-sub
9-pin female
Signal name
Pin
No.
SDA
SDB
Shell
E5AJ
RS-485:
Terminal Block
Terminating resistance
Terminal
Signal name
A
Abbreviation
B
SG
Signal direction
I/O
I/O
---
Pin No.
26, 28
25, 29
27
SN751177N or equivalent
Shield
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Terminator switch
Terminating resistance (240
Ω) is connected via the terminator switch.
Shield
E5AJ
RS-485:
Terminal Block
Terminal
Signal name
Note 1.
The connection configuration is a one-to-one or a one-to-N configuration. Using a one-to-N configuration, up to 32 units can be connected including the Serial Communications Boards Unit.
2.
The maximum cable length is 500 m. Use shielded twisted-pair cable.
3.
Connect terminating resistance to the devices only at both ends of the transmission path.
4.
The total terminating resistance at both ends must be at least 100
Ω for RS-422A or 54 Ω for RS-485.
Select Remote Mode (Sequence No. 200 (Hex 00C8))
Switches the Controller to remote mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
546
E5
@J Temperature Controller Protocol
Select Local Mode (Sequence No. 201 (Hex 00C9))
Switches the Controller to local mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Appendix J
Select Backup Mode (Sequence No. 202 (Hex 00CA))
Switches from the set point write mode to backup mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Select RAM Write Mode (Sequence No. 203 (Hex 00CB))
Switches from set point write mode to RAM write mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0002 (fixed)
00 to 31
547
E5
@J Temperature Controller Protocol
Save Set Point (Sequence No. 204 (Hex 00CC))
Saves the set point.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Appendix J
Write Parameters 1 (Sequence No. 205 (Hex 00CD))
Writes the set point, alarm value 1, alarm value 2, and a heater burnout alarm value to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+122
+123
+124
+125
+5
+6
~
+0
+1
+2
+3
+4
+126
Number of send data words
Number of units
(Undefined)
Set point
Unit No.
Alarm value 1
Alarm value 2
Heater burnout alarm value
(Undefined)
Set point
Unit No.
Alarm value 1
Alarm value 2
Heater burnout alarm value
~
1st unit
25th unit (max.)
548
E5
@J Temperature Controller Protocol
Appendix J
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+4
+5
+6
+7
+126
(max.)
Unit No. (2 digits BCD)
1st unit
Set point (4 digits BCD)
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
1st unit
Heater burnout alarm value 2
(4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Heater burnout alarm value 2
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Number of units
× 5 + 2
0001 to 0019 (1 to 25 decimal)
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
0000 to 9999
Write Parameters 2 (Sequence No. 206 (Hex 00CE))
Writes the proportional bands, integral times, and derivative times to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+122
+123
+124
+125
+0
+1
+2
+3
+4
+5
~
Number of send data words
Number of units
(Undefined) Unit No.
Proportional band
Integral time
Derivative time
(Undefined) Unit No.
Proportional band
Integral time
Derivative time
~
1st unit
31th unit (max.)
549
E5
@J Temperature Controller Protocol
Appendix J
Offset
+0
+1
+2
+3
+4
+5
+6
+125
(max.)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
1st unit Unit No. (2 digits BCD)
1st unit
Proportional band (4 digits BCD)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
31th unit
Derivative time (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Number of units
× 4 + 2
0001 to 001F (1 to 31 decimal)
00 to 31
0000 to 9999
0000 to 9999
0000 to 9999
00 to 31
0000 to 9999
Write Input Shift Value (Sequence No. 207 (Hex 00CF))
Writes the input shift value.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined) Unit No.
Input shift value
Data Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Input shift value (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0003 (fixed)
00 to 31
0000 to 9999
550
E5
@J Temperature Controller Protocol
Appendix J
Read Parameters 1 (Sequence No. 208 (Hex 00D0))
Reads the set points, alarm values 1, alarm values 2, and heater burnout alarm values for multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+26
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
~
(max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0019 (1 to 25 decimal)
00 to 31
+3
+26
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+97
+98
+99
+100
+0
+1
+2
+3
+4
~
Number of receive data words
Set point
Alarm value 1
Alarm value 2
Heater burnout alarm value
Set point
Alarm value 1
Alarm value 2
Heater burnout alarm value
~
1st unit
25th unit (max.)
551
E5
@J Temperature Controller Protocol
Appendix J
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Set point (4 digits BCD)
+2
+3
1st unit
Alarm value 1 (4 digits BCD)
1st unit
Alarm value 2 (4 digits BCD)
+4
+5
+100
(max.)
1st unit
Heater burnout alarm value
(4 digits BCD)
2nd unit
Set point (4 digits BCD)
•
•
•
25th unit
Heater burnout alarm value
(4 digits BCD)
Data
Number of units
× 4 + 1
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Parameters 2 (Sequence No. 209 (Hex 00D1))
Reads the proportional bands, integral times, and derivative times for multiple units and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+32
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
~
(max.)
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units (4 digits Hex) unit
Unit No. (2 digits BCD)
+3
+32
(max.)
2nd unit
Unit No. (2 digits BCD)
•
•
•
31th unit
Unit No. (2 digits BCD)
Number of units + 2
Data
0001 to 001F (1 to 31 decimal)
00 to 31
00 to 31
00 to 31
552
E5
@J Temperature Controller Protocol
Appendix J
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
~
+91
+92
+93
Number of receive data words
Proportional band
Integral time
Derivative time
Proportional band
Integral time
Derivative time
~
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Proportional band (4 digits BCD)
1st unit
31th unit (max.)
+2
+3
+4
+93
(max.)
1st unit
Integral time (4 digits BCD)
1st unit
Derivative time (4 digits BCD)
2nd unit
Proportional band (4 digits BCD)
•
•
•
31th unit
Derivative time (4 digits BCD)
Data
Number of units
× 3 + 1
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Input Shift Value (Sequence No. 210 (Hex 00D2))
Reads the input shift value and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Input shift value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Input shift value (4 digits BCD)
Data
0002
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
553
E5
@J Temperature Controller Protocol
Appendix J
Read Output Value (Sequence No. 211 (Hex 00D3))
Reads the output value and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Output value
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Output value
(4 digits BCD)
Data
Data
0002
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Process Value (Sequence No. 212 (Hex 00D4))
Reads the process value and status data and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Process value
Status data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Process value (4 digits BCD)
+2 Status data (4 digits Hex)
Data
0003
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
Read Set Point Limit (Sequence No. 213 (Hex 00D5))
Reads the set point limits and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
554
E5
@J Temperature Controller Protocol
Appendix J
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Set point lower limit
Set point upper limit
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Set point lower limit
(4 digits BCD)
+2 Set point upper limit
(4 digits BCD)
0002 (fixed)
00 to 31
Data
Data
0003
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Read Heater Current (Sequence No. 214 (Hex 00D6))
Reads the heater current and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
Heater current
Status data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Heater current
(4 digits BCD)
+2 Status data (4 digits Hex)
0002 (fixed)
00 to 31
Data
Data
0003
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
0000 to 0011
Read Initial Status (Sequence No. 215 (Hex 00D7))
Reads the initial status and stores the results in the specified word.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
555
E5
@J Temperature Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined)
+2 (Undefined)
Alarm 1 type Alarm 2 type
Status
Input type
Offset
+0
+1
+2
Contents (data format)
Number of receive data words
(4 digits Hex)
Status (2 digits Hex)
Alarm 1 type (1 digit Hex)
Alarm 2 type (1 digit Hex)
Input type (1 digit BCD)
0003
00 to 99
0 to 9
0 to 9
0 to 9
Data
Appendix J
General-purpose Write (Sequence No. 216 (Hex 00D8))
Writes the parameter specified by setting a header code.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
Header code (ASC)
(Undefined)
Send data
Data code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Header code (two ASCII characters)
+3
+4
Data code (2 digits BCD)
Write data (4 digits BCD)
0005 (fixed)
Data
00 to 31
Header codes that can be set
MB, WS, W%, WW, WB, WN, WV
01 to 02
0000 to 9999
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
General-purpose Read (Sequence No. 217 (Hex 00D9))
Reads the parameter specified by setting a header
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
Number of send data words
(Undefined) Unit No.
Header code (ASC)
(Undefined) Data code
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Header code (two ASCII characters)
+3 Data code (2 digits BCD)
0004 (fixed)
Data
00 to 31
Header codes that can be set
RS, R%, RW, RB, RN, RV, RO
01 to 02
556
E5
@J Temperature Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Receive data
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
Read data (4 digits BCD)
Appendix J
Data
0002
0000 to 9999
When the left digit is –1, A is set and when it is –, F is set.
Note The completion code is not included in the read data.
557
Appendix K
ES100
@ Digital Controller Protocol
The ES100
@ Digital Controller Protocol controls in remote mode and reads various settings from the Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The structure of the ES100
@ Digital Controller Protocol is shown below.
Sequence
No.
Transmission
sequence name
Function
250 (00FA)
251 (00FB)
Read event data
Read time signals
252 (00FC) Read error detection data
253 (00FD) Read heater burnout data
254 (00FE)
255 (00FF)
256 (0100)
257 (0101) Read control monitor
258 (0102) Read adjustment
259 (0103) Write adjustment
260 (0104) Read PID control
261 (0105)
262 (0106)
263 (0107)
264 (0108)
Read PV data
Read SP data
Read MV data parameters parameters parameters 1
Read PID control parameters 2
Write PID control parameters 1
Write PID control parameters 2
Read local SP
Reads events 1 to 10 in the variable area.
Reads time signals 1 to 10 in the variable area.
Reads error groups 1 to 15 in the variable area.
Reads the heater burnout alarm.
Reads PV data in the variable area.
Reads SP data in the variable area.
Reads the MV in the variable area.
Reads control monitor data (SP, PV, and MV) in the variable area.
Reads adjustment parameters in the parameter area.
Writes adjustment parameters in the parameter area.
Reads PID parameters No. 1 to 4 from the
PID control parameters in the parameter area.
Reads PID parameters No. 5 to 8 from the
PID control parameters in the parameter area.
Writes PID parameters No. 1 to 4 from PID control parameters in the parameter area.
Writes PID parameters No. 5 to 8 from PID control parameters in the parameter area.
Reads the local SP in the program parameter area.
265 (0109)
266 (010A)
Write local SP
Read program parameters
Writes local SP in the program parameter area.
Reads local SP, step time, PID No. wait code, and events 1 to 10 set values in the program parameter area.
267 (010B) Write program parameters
Writes the local SP, step time, PID No., wait code, and event 1 to 10 set values in the program parameter area.
268 (010C) Remote setting mode Switches the setting mode to remote setting.
269 (010D) Local setting mode Switches the setting mode to local setting.
270 (010E) External setting mode Switches the setting mode to external setting.
Ladder interface
Send word allocation
Yes
Yes
Receive word allocation
Yes
Yes
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
No
No
No
No
559
ES100
@ Digital Controller Protocol
Appendix K
Sequence
No.
Transmission
sequence name
Function
271 (010F) Run command
272 (0110) Reset (stop)
273 (0111) Auto mode
274 (0112) Manual mode
275 (0113) Execute A.T.
276 (0114) Cancel A.T.
277 (0115) Change pattern No.
278 (0116) Change bank No.
Starts control.
Stops control.
Switches the control mode to auto.
Switches the control mode to a manual.
Executes A.T.
Cancels A.T.
Changes the pattern No.
Changes the bank No.
279 (0117) Read controller status Reads the controller status.
280 (0118) General-purpose command
Sends specified data and stores the received data in the specified words.
Ladder interface
Send word allocation
Receive word allocation
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
Yes
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation:
Receive word allocation:
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
Connections
Connections for using the ES100
@ Digital Controller Protocol are shown below.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-232C
RS-232C port
ES100
#
Serial Communications Unit/Board
RS-232C: D-sub
9-pin female
Signal name
FG
SD
RD
RTS
CTS
DSR
DTR
SG
Pin No.
3
4
1
2
5
7
8
9
Shield
→
RS-232C
ES100
#-#01#
RS-232C:
Terminal Block
Terminal
17
16
15
Signal name
SD
RD
SG
560
ES100
@ Digital Controller Protocol
RS-422A/485 Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-422A/485 port
• RS-422A 4-wire Connections
Serial Communications Board/Unit
RS-422A: D-sub
9-pin female
Signal name
RDA
RDB
SDA
SDB
FG
Pin No.
6
8
1
2
Shield
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
• RS-485 2-wire Connections
Serial Communications Board/Unit
RS-485: D-sub
9-pin female
Signal name
SDA
SBA
Pin No.
1
2
Shield
FG
Hood
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Appendix K
ES100
#
→
RS-422A/485
ES100
#
→
RS-422A/485
Up to 32 units can be connected.
ES100
#
→
RS-422A/485
ES100
#-#04#
RS-422A
Terminal Block
Terminal
24
25
16
17
Signal name
SDA
SDB
RDA
RDB
24
25
16
17
SDA
SDB
RDA
RDB
Next
ES100
ES100
#-#04#
RS-485
Terminal Block
Terminal
16
17
Next
ES100
561
ES100
@ Digital Controller Protocol
Appendix K
Switch Settings
There are two switches located on the board on the left of the Unit. Set SW1 to the interface: RS-422A or RS-
485. Set SW2 to the same setting as SW1 on the terminating Units and to the center on all other Units.
422
←
•
→485
422
←
•
→485
Read Event Data (Sequence No. 250 (Hex 00FA))
Reads events 1 to 10 in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
~
+26
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
(Undefined) Unit No.
1st unit
~
2nd unit
25th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0019 (1 to 25 decimal)
00 to 31
+3
+26
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
562
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+121
+122
+123
+124
+125
+0
+1
+2
+3
+4
+5
~
Number of receive data words
Event 1
Event 3
Event 5
Event 7
Event 9
Event 2
Event 4
Event 6
Event 8
Event 10
Event 1
Event 3
Event 5
Event 7
Event 9
Event 2
Event 4
Event 6
Event 8
Event 10
~
1st unit
25th unit (max.)
Appendix K
Offset
+0
+1
+2
+3
+4
+5
+125
(max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Event data 1 (2 digits Hex)
Event data 2 (2 digits Hex)
1st unit
Event data 3 (2 digits Hex)
Event data 4 (2 digits Hex)
1st unit
Event data 5 (2 digits Hex)
Event data 6 (2 digits Hex)
1st unit
Event data 7 (2 digits Hex)
Event data 8 (2 digits Hex)
1st unit
Event data 9 (2 digits Hex)
Event data 10 (2 digits Hex)
•
•
•
25th unit
Event data 9 (2 digits Hex)
Event data 10 (2 digits Hex)
Data
Number of units x 5 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Read Time Signal (Sequence No. 251 (Hex 00FB))
Reads time signals from 1 to 10 in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined)
(Undefined)
Unit No.
Unit No.
+26
(Undefined)
Unit No.
1st unit
~
2nd unit
25th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0019 (1 to 25 decimal)
00 to 31
Unit No. (2 digits BCD)
563
ES100
@ Digital Controller Protocol
Offset
+3
+26
(max.)
Contents (data format)
2nd unit
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+5
~
+121
+122
+123
+124
+125
+0
+1
+2
+3
+4
Number of receive data words
Time signal 1 Time signal 2
Time signal 3
Time signal 5
Time signal 7
Time signal 9
Time signal 4
Time signal 6
Time signal 8
Time signal 10
Time signal 1
Time signal 3
Time signal 5
Time signal 7
Time signal 9
Time signal 2
Time signal 4
Time signal 6
Time signal 8
Time signal 10
~
00 to 31
00 to 31
1st unit
25th unit (max.)
Offset
+0
+1
+2
+3
+4
+5
+125
(max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Time signal 1 data (2 digits Hex)
Time signal 2 data (2 digits Hex)
1st unit
Time signal 3 data (2 digits Hex)
Time signal 4 data (2 digits Hex)
1st unit
Time signal 5 data (2 digits Hex)
Time signal 6 data (2 digits Hex)
1st unit
Time signal 7 data (2 digits Hex)
Time signal 8 data (2 digits Hex)
1st unit
Time signal 9 data (2 digits Hex)
Time signal 10 data (2 digits Hex)
•
•
•
25th unit
Time signal 9 data (2 digits Hex)
Time signal 10 data (2 digits Hex)
Data
Data
Number of units
× 5 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Appendix K
564
ES100
@ Digital Controller Protocol
Appendix K
Read Error Detection Data (Sequence No. 252 (Hex 00FC))
Reads error groups from 0 to 15 in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+17
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
16th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0010 (1 to 16 decimal)
00 to 31
+3
+17
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
16th unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
~
Number of receive data words
Error group 0 Error group 1
Error group 2
Error group 4
Error group 6
Error group 8
Error group 10
Error group 12
Error group 14
Error group 3
Error group 5
Error group 7
Error group 9
Error group 11
Error group 13
Error group 15
~
+128 Error group 14 Error group 15
1st unit
Offset
+0
+1
+2
+7
+8
+9
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Error group 0 data (2 digits Hex)
Error group 1 data (2 digits Hex)
1st unit
Error group 2 data (2 digits Hex)
Error group 3 data (2 digits Hex)
•
•
1st unit
Error group 12 data (2 digits Hex)
Error group 13 data (2 digits Hex)
1st unit
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
2nd unit
Error group 0 data (2 digits Hex)
Error group 1 data (2 digits Hex)
16th unit (max.)
Data
Number of units
× 8 + 1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
565
ES100
@ Digital Controller Protocol
Appendix K
Offset
+128
(max.)
Contents (data format)
•
•
16th unit
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
00 to FF
00 to FF
Data
Read Heater Burnout Data (Sequence No. 253 (Hex 00FD))
Reads the heater burnout alarm in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
+33 (Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+32
Number of receive data words
(Undefined)
Heater burnout alarm
(Undefined)
Heater burnout alarm
(Undefined)
Heater burnout alarm
(Undefined)
Heater burnout alarm
(Undefined)
Heater burnout alarm
1st unit
2nd unit
3rd unit
~
4th unit
32nd unit (max.)
Number of units +1
Data Offset
+0
+1
+2
+3
+4
+32
(max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Heater burnout alarm (2 digits Hex)
2nd unit
Heater burnout alarm (2 digits Hex)
3rd unit
Heater burnout alarm (2 digits Hex)
4th unit
Heater burnout alarm (2 digits Hex)
•
•
•
32nd unit
Heater burnout alarm (2 digits Hex)
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
566
ES100
@ Digital Controller Protocol
Appendix K
Read PV Data (Sequence No. 254 (Hex 00FE))
Reads the PV data for the variable type “analog data” in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+63
+64
Number of receive data words
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
~
1st unit
2nd unit
32nd unit
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
PV data (rightmost 4 digits)
(4 digits BCD)
1st unit
PV data (leftmost 4 digits)
(4 digits BCD)
2nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
2nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
PV data (rightmost 4 digits)
(4 digits BCD)
32nd unit
PV data (leftmost 4 digits)
(4 digits BCD)
Data
Number of units
× 2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
567
ES100
@ Digital Controller Protocol
Appendix K
Read SP Data (Sequence No. 255 (Hex 00FF))
Reads the SP data for the variable type “analog data” in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined) Unit No.
(Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+63
+64
Number of receive data words
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
~
1st unit
2nd unit
32nd unit
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
SP data (rightmost 4 digits)
(4 digits BCD)
1st unit
SP data (leftmost 4 digits)
(4 digits BCD)
2nd unit
SP data (rightmost 4 digits)
(4 digits BCD)
2nd unit
SP data (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
SP data (rightmost 4 digits)
(4 digits BCD)
32nd unit
SP data (leftmost 4 digits)
(4 digits BCD)
Data
Number of units
× 2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
568
ES100
@ Digital Controller Protocol
Appendix K
Read MV Data (Sequence No. 256 (Hex 0100))
Reads the MV for the variable type “analog data” in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
+33
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+63
+64
Number of receive data words
MV (rightmost 4 digits)
MV (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
~
1st unit
2nd unit
32nd unit
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
MV (rightmost 4 digits) (4 digits BCD)
1st unit
MV (leftmost 4 digits) (4 digits BCD)
2nd unit
MV (rightmost 4 digits) (4 digits BCD)
2nd unit
MV (leftmost 4 digits) (4 digits BCD)
•
•
•
32nd unit
MV (rightmost 4 digits) (4 digits BCD)
32nd unit
MV (leftmost 4 digits) (4 digits BCD)
Data
Number of units
× 2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
569
ES100
@ Digital Controller Protocol
Appendix K
Read Control Monitor Data (Sequence No. 257 (Hex 0101))
Reads the control monitor data (SP/PV/MV) in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+22
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
21st unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0015 (1 to 21 decimal)
00 to 31
+3
+22
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
21st unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
~
+121
+122
+123
+124
+125
+126
Number of receive data words
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
SP data (rightmost 4 digits)
SP data (leftmost 4 digits)
PV data (rightmost 4 digits)
PV data (leftmost 4 digits)
MV (rightmost 4 digits)
MV (leftmost 4 digits)
~
1st unit
21st unit
Offset
+0
+1
+2
+3
+4
+5
+6
Contents (data format)
1st unit
Number of receive data words (4 digits Hex)
1st unit
SP data (rightmost 4 digits) (4 digits BCD)
1st unit
SP data (leftmost 4 digits) (4 digits BCD)
1st unit
PV data (rightmost 4 digits) (4 digits BCD)
1st unit
PV data (leftmost 4 digits) (4 digits BCD)
1st unit
MV (rightmost 4 digits) (4 digits BCD)
1st unit
MV (leftmost 4 digits) (4 digits BCD)
Data
Number of units
× 6 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
F indicates a negative number.
570
ES100
@ Digital Controller Protocol
Appendix K
Offset
+125
+126
Contents (data format)
•
•
•
21st unit
MV (rightmost 4 digits) (4 digits BCD)
21st unit
MV (leftmost 4 digits) (4 digits BCD)
Data
00000000 to 09999000
F indicates a negative number.
Read Adjustment Parameters (Sequence No. 258 (Hex 0102))
Reads the adjustment parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
571
ES100
@ Digital Controller Protocol
+14
+15
+16
+17
+18
+10
+11
+12
+13
+7
+8
+9
+0
+1
+2
+3
+4
+5
+6
+19
+20
+21
+22
+23
+24
+25
+26
+27
+28
+29
+30
+31
+32
+33
+34
+35
+36
+37
+38
+39
+40
+41
+42
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
Fixed SP
Number of receive data words
Control output 1 pulse cycle
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Control output 2 pulse cycle
Fuzzy strength
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Cooling coefficient
Heater burnout alarm setting
Position-proportional dead band
Switching output hysteresis
ON/OFF count alarm setting
ON/OFF control hysteresis
Manual reset
SP setting lower limit
SP setting upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
SP rise rate limit
SP fall rate limit
MV rate-of-change limit
Secondary loop fixed SP
Secondary loop P
Secondary loop I
Secondary loop D
Secondary loop manual reset
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix K
572
ES100
@ Digital Controller Protocol
Appendix K
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+15 to 16
+17 to 18
+19 to 20
+21 to 22
+23 to 24
+25 to 26
+27 to 28
+29 to 30
+31 to 32
+33 to 34
+35 to 36
+37 to 38
+39 to 40
+41 to 42
Contents (data format)
Number of receive data words
(4 digits Hex)
Fixed SP (8 digits BCD)
Control output 1 pulse cycle
(8 digits BCD)
Control output 2 pulse cycle
(8 digits BCD)
Fuzzy strength (8 digits BCD)
Cooling coefficient (8 digits BCD)
Heater burnout alarm setting
(8 digits BCD)
Position-proportional dead band
(8 digits BCD)
Switching output hysteresis
(8 digits BCD)
ON/OFF count alarm setting
(8 digits BCD)
ON/OFF control hysteresis
(8 digits BCD)
Manual reset (8 digits BCD)
SP setting lower limit
(8 digits BCD)
SP setting upper limit
(8 digits BCD)
SP rise rate limit (8 digits BCD)
SP fall rate limit (8 digits BCD)
MV rate-of-change limit (8 digits BCD)
Secondary loop fixed SP
(8 digits BCD)
Secondary loop P (8 digits BCD)
Secondary loop I (8 digits BCD)
Secondary loop D (8 digits BCD)
Secondary loop manual reset
(8 digits BCD)
Data
002B (0043 decimal)
00000000 to 09999000
F indicates a negative number.
573
ES100
@ Digital Controller Protocol
Appendix K
Write Adjustment Parameters (Sequence No. 259 (Hex 0103))
Writes the adjust parameters in the parameter area.
+36
+37
+38
+39
+40
+41
+28
+29
+30
+31
+32
+33
+34
+35
+16
+17
+18
+19
+20
+21
+22
+23
+24
+25
+26
+27
+42
+43
+11
+12
+13
+14
+15
+7
+8
+9
+10
+0
+1
+2
+3
+4
+5
+6
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
Number of send data words
(Undefined)
Unit No.
Fixed SP
Control output 1 pulse cycle
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Control output 2 pulse cycle
Fuzzy strength
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Cooling coefficient
Heater burnout alarm setting
Position-proportional dead band
Switching output hysteresis
ON/OFF count alarm setting
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
ON/OFF control hysteresis
Manual reset
SP setting lower limit
SP setting upper limit
SP rise rate limit
SP fall rate limit
MV change rate limit
Secondary loop fixed SP
Secondary loop P
Secondary loop I
Secondary loop D
Secondary loop manual reset
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
574
ES100
@ Digital Controller Protocol
Appendix K
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+16 to 17
+18 to 19
+20 to 21
+22 to 23
+24 to 25
+26 to 27
+28 to 29
+30 to 31
+32 to 33
+34 to 35
+36 to 37
+38 to 39
+40 to 41
+42 to 43
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Fixed SP (8 digits BCD)
Control output 1 pulse cycle
(8 digits BCD)
Control output 2 pulse cycle
(8 digits BCD)
Fuzzy strength (8 digits BCD)
Cooling coefficient (8 digits BCD)
Heater burnout alarm setting
(8 digits BCD)
Position-proportional dead band
(8 digits BCD)
Switching output hysteresis
(8 digits BCD)
ON/OFF count alarm setting
(8 digits BCD) value
ON/OFF control hysteresis
(8 digits BCD)
Manual reset (8 digits BCD)
SP setting lower limit
(8 digits BCD)
SP setting upper limit
(8 digits BCD)
SP rise rate limit (8 digits BCD)
SP fall rate limit (8 digits BCD)
MV rate-of-change limit (8 digits BCD)
Secondary loop fixed SP
(8 digits BCD)
Secondary loop P (8 digits BCD)
Secondary loop I (8 digits BCD)
Secondary loop D (8 digits BCD)
Secondary loop manual reset
(8 digits BCD)
Data
002C (0044 decimal) (fixed)
00 to 31
00000000 to 09999000
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Read PID Control Parameters 1 (Sequence No. 260 (Hex 0104))
Reads PID parameters No. 1 to 4 from PID control parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
575
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+9
+10
+11
+12
+0
+5
+6
+7
+8
+1
+2
+3
+4
+13
+14
~
Number of receive data words
PID No. 1 P
PID No. 1 P
PID No. 1 I
PID No. 1 I
PID No. 1 D
PID No. 1 D
PID No. 1 MV lower limit
PID No. 1 MV lower limit
PID No. 1 MV upper limit
PID No. 1 MV upper limit
PID No. 1 PV bias value
PID No. 1 PV bias value
PID No. 1 Automatic selection range upper limit
PID No. 1 Automatic selection range upper limit
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
+51
+52
+53
+54
+55
+56
PID No. 4 MV upper limit
PID No. 4 MV upper limit
PID No. 4 PV bias value
PID No. 4 PV bias value
PID No. 4 Automatic selection range upper limit
PID No. 4 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
Appendix K
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+43 to 44
+45 to 46
+47 to 48
+49 to 50
+51 to 52
+53 to 54
+55 to 56
Contents (data format)
Number of receive data words
(4 digits Hex)
PID No. 1 P (8 digits BCD)
PID No. 1 I (8 digits BCD)
PID No. 1 D (8 digits BCD)
PID No. 1 MV lower limit (8 digits BCD)
PID No. 1 MV upper limit
(8 digits BCD)
PID No. 1 PV bias value (8 digits BCD)
PID No. 1 Automatic selection range upper limit (8 digits BCD)
•
•
•
PID No. 4 P (8 digits BCD)
PID No. 4 I (8 digits BCD)
PID No. 4 D (8 digits BCD)
PID No. 4 MV lower limit (8 digits BCD)
PID No. 4 MV upper limit
(8 digits BCD)
PID No. 4 PV bias value (8 digits BCD)
PID No. 4 Automatic selection range upper limit (8 digits BCD)
Data
0039 (0057 decimal)
00000000 to 09999000
576
ES100
@ Digital Controller Protocol
Appendix K
Read PID Control Parameters 2 (Sequence No. 261 (Hex 0105))
Reads PID parameters No. 5 to 8 from the PID control parameters in the parameter area and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 31
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+51
+52
+53
+54
+55
+56
+6
+7
+8
+9
+10
+11
+12
+13
+14
~
Number of receive data words
PID No. 5 P
PID No. 5 P
PID No. 5 I
PID No. 5 I
PID No. 5 D
PID No. 5 D
PID No. 5 MV lower limit
PID No. 5 MV lower limit
PID No. 5 MV upper limit
PID No. 5 MV upper limit
PID No. 5 PV bias value
PID No. 5 PV bias value
PID No. 5 Automatic selection range upper limit
PID No. 5 Automatic selection range upper limit
PID No. 8 MV upper limit
PID No. 8 MV upper limit
PID No. 8 PV bias value
PID No. 8 PV bias value
PID No. 8 Automatic selection range upper limit
PID No. 8 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
577
ES100
@ Digital Controller Protocol
Appendix K
+0
Offset
+1 to 2
+3 to 4
+5 to 6
+7 to 8
+9 to 10
+11 to 12
+13 to 14
+43 to 44
+45 to 46
+47 to 48
+49 to 50
+51 to 52
+53 to 54
+55 to 56
Contents (data format) Data
Number of receive data words
(4 digits Hex)
PID No. 5 P (8 digits BCD)
PID No. 5 I (8 digits BCD)
PID No. 5 D (8 digits BCD)
PID No. 5 MV lower limit (8 digits BCD)
PID No. 5 MV upper limit
(8 digits BCD)
PID No. 5 PV bias value (8 digits BCD)
PID No. 5 Automatic selection range upper limit (8 digits BCD)
•
•
•
PID No. 8 P (8 digits BCD)
PID No. 8 I (8 digits BCD)
PID No. 8 D (8 digits BCD)
PID No. 8 MV lower limit (8 digits BCD)
PID No. 8 MV upper limit
(8 digits BCD)
PID No. 8 PV bias value (8 digits BCD)
PID No. 8 Automatic selection range upper limit (8 digits BCD)
0039 (0057 decimal)
00000000 to 09999000
Write PID Control Parameters 1 (Sequence No. 262 (Hex 0106))
Writes PID parameters No. 1 to 4 to the PID control parameters in the parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+52
+53
+54
+55
+56
+57
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+0
+1
+2
+15
~
Number of send data words
(Undefined) Unit No.
PID No. 1 P
PID No. 1 P
PID No. 1 I
PID No. 1 I
PID No. 1 D
PID No. 1 D
PID No. 1 MV lower limit
PID No. 1 MV lower limit
PID No. 1 MV upper limit
PID No. 1 MV upper limit
PID No. 1 PV bias value
PID No. 1 PV bias value
PID No. 1 Automatic selection range upper limit
PID No. 1 Automatic selection range upper limit
PID No. 4 MV upper limit
PID No. 4 MV upper limit
PID No. 4 PV bias value
PID No. 4 PV bias value
PID No. 4 Automatic selection range upper limit
PID No. 4 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
~
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
578
ES100
@ Digital Controller Protocol
Appendix K
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+44 to 45
+46 to 47
+48 to 49
+50 to 51
+52 to 53
+54 to 55
+56 to 57
Contents (data format) Data
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
PID No. 1 P (8 digits BCD)
PID No. 1 I (8 digits BCD)
PID No. 1 D (8 digits BCD)
PID No. 1 MV lower limit (8 digits BCD)
PID No. 1 MV upper limit
(8 digits BCD)
PID No. 1 PV bias value
(8 digits BCD)
PID No. 1 Automatic selection range upper limit
(8 digits BCD)
•
•
•
PID No. 4 P (8 digits BCD)
PID No. 4 I (8 digits BCD)
PID No. 4 D (8 digits BCD)
PID No. 4 MV lower limit (8 digits BCD)
PID No. 4 MV upper limit
(8 digits BCD)
PID No. 4 PV bias value
(8 digits BCD)
PID No. 4 Automatic selection range upper limit
(8 digits BCD)
003A (0058 decimal) (fixed)
00 to 31
00000000 to 09999000
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
579
ES100
@ Digital Controller Protocol
Appendix K
Write PID Control Parameters 2 (Sequence No. 263 (Hex 0107))
Writes the PID parameters No. 5 to 8 to the PID control parameters in the parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+52
+53
+54
+55
+56
+57
+12
+13
+14
+15
~
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
Number of send data words
(Undefined)
Unit No.
PID No. 5 P
PID No. 5 P
PID No. 5 I
PID No. 5 I
PID No. 5 D
PID No. 5 D
PID No. 5 MV lower limit
PID No. 5 MV lower limit
PID No. 5 MV upper limit
PID No. 5 MV upper limit
PID No. 5 PV bias value
PID No. 5 PV bias value
PID No. 5 Automatic selection range upper limit
PID No. 5 Automatic selection range upper limit
PID No. 8 MV upper limit
PID No. 8 MV upper limit
PID No. 8 PV bias value
PID No. 8 PV bias value
PID No. 8 Automatic selection range upper limit
PID No. 8 Automatic selection range upper limit
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
~
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
(rightmost 4 digits)
(leftmost 4 digits)
580
ES100
@ Digital Controller Protocol
Appendix K
+0
Offset
+1
+2 to 3
+4 to 5
+6 to 7
+8 to 9
+10 to 11
+12 to 13
+14 to 15
+44 to 45
+46 to 47
+48 to 49
+50 to 51
+52 to 53
+54 to 55
+56 to 57
Contents (data format) Data
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
PID No. 5 P (8 digits BCD)
PID No. 5 I (8 digits BCD)
PID No. 5 D (8 digits BCD)
PID No. 5 MV lower limit (8 digits BCD)
PID No. 5 MV upper limit
(8 digits BCD)
PID No. 5 PV bias value
(8 digits BCD)
PID No. 5 Automatic selection range upper limit
(8 digits BCD)
•
•
•
PID No. 8 P (8 digits BCD)
PID No. 8 I (8 digits BCD)
PID No. 8 D (8 digits BCD)
PID No. 8 MV lower limit (8 digits BCD)
PID No. 8 MV upper limit
(8 digits BCD)
PID No. 8 PV bias value
(8 digits BCD)
PID No. 8 Automatic selection range upper limit
(8 digits BCD)
003A (0058 decimal) (fixed)
00 to 31
00000000 to 09999000
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Read Local SP (Sequence No. 264 (Hex 0108))
Reads the local SP in the program parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
Number of units
(Undefined) Unit No.
Step No.
Pattern No.
(Undefined)
Pattern No.
Unit No.
Step No.
+5
~
+64
+65
(Undefined)
Pattern No.
Unit No.
Step No.
~
1st unit
2nd unit
32nd unit
581
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
•
•
•
00 to 63
00 to 63
00 to 31
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
00 to 63
00 to 63
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
+4
~
+63
+64
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
~
Offset
+0
+1
+2
+3
+4
+63
+64
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
1st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
2nd unit
Local SP (rightmost 4 digits)
(4 digits BCD)
2nd unit
Local SP (leftmost 4 digits)
(4 digits BCD)
•
•
•
32nd unit
Local SP (rightmost 4 digits)
(4 digits BCD)
32nd unit
Local SP (leftmost 4 digits)
(4 digits BCD)
1st unit
2nd unit
32nd unit
Data
Number of units
× 2 + 1
00000000 to 09999000
F indicates a negative number.
00000000 to 09999000
00000000 to 09999000
582
ES100
@ Digital Controller Protocol
Write Local SP (Sequence No. 265 (Hex 0109))
Writes the local SP to the program parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+122
+123
+124
+125
+5
+6
+7
+8
+9
~
+0
+1
+2
+3
+4
Number of send data words
Number of units
(Undefined) Unit No.
Pattern No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
(Undefined)
Pattern No.
Unit No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
(Undefined)
Pattern No.
Unit No.
Step No.
Local SP (rightmost 4 digits)
Local SP (leftmost 4 digits)
~
1st unit
2nd unit
31st unit
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+4
+5
+122
+123
+124
+125
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
1st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
1st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
•
•
•
31st unit
Unit No. (2 digits BCD)
31st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
31st unit
Local SP (rightmost 4 digits)
(4 digits BCD)
31st unit
Local SP (leftmost 4 digits)
(4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Appendix K
Data
Number of units
× 4 + 2
0001 to 001F (1 to 31 decimal)
00 to 31
00 to 63
00 to 63
00000000 to 09999000
00 to 31
00 to 63
00 to 63
00000000 to 09999000
583
ES100
@ Digital Controller Protocol
Appendix K
Read Program Parameters (Sequence No. 266 (Hex 010A))
Reads the local SP, step time, PID set No., wait code, and events from 1 to 10 set values in the program parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
Number of units
(Undefined)
Pattern No.
Unit No.
Step No.
(Undefined)
Pattern No.
(Undefined)
Pattern No.
(Undefined)
Pattern No.
Unit No.
Step No.
Unit No.
Step No.
Unit No.
Step No.
1st unit
2nd unit
3rd unit
4th unit
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+8
+9
(max.)
Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
•
•
•
4th unit
Unit No. (2 digits BCD)
4th unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
Data
Number of units
× 2 + 2
0001 to 0004
00 to 31
00 to 63
00 to 63
00 to 31
00 to 63
00 to 63
584
ES100
@ Digital Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
~
+27
+28
~
+85
+86
+87
+88
+89
+90
+91
+92
+93
+94
~
+111
+112
Number of receive data words
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
Event 10 setting (rightmost)
Event 10 setting (leftmost)
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
Event 10 setting (rightmost)
Event 10 setting (leftmost)
~
~
~
1st unit
4th unit (max.)
Appendix K
585
ES100
@ Digital Controller Protocol
Offset Contents (data format)
+0
+1 to 2
+3 to 4
+5 to 6
Number of receive data words
(4 digits Hex)
1st unit
Local SP (8 digits BCD)
1st unit
Step time) (8 digits BCD)
1st unit
PID set No. (8 digits BCD)
+7 to 8
+9 to 10
1st unit
Wait code (8 digits BCD)
1st unit
Event 1 setting (8 digits BCD)
+11 to 12
+27 to 28
1st unit
Event 2 setting (8 digits BCD)
•
•
1st unit
Event 10 setting (8 digits BCD)
+29 to 30 1st unit
Local SP (8 digits BCD)
•
•
+109 to 110 4th unit
Event 9 setting (8 digits BCD)
+111 to 112
(max.)
4th unit
Event 10 setting (8 digits BCD)
Appendix K
Data
Number of units
× 28 + 1
00000000 to 09999000
F indicates a negative number.
586
ES100
@ Digital Controller Protocol
Appendix K
Write Program Parameters (Sequence No. 267 (Hex 010B))
Writes the local SP, step time, PID set No., wait code, and events from 1 to 10 settings in the program parameter area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
~
+30
+31
~
+92
+93
~
+120
+121
Number of send data words
Number of units
(Undefined) Unit No.
Pattern No.
Step No.
Local SP (rightmost)
Local SP (leftmost)
Step bank time (rightmost)
Step bank time (leftmost)
PID set No. (rightmost)
PID set No. (leftmost)
Wait code (rightmost)
Wait code (leftmost)
Event 1 setting (rightmost)
Event 1 setting (leftmost)
Event 10 setting (rightmost)
Event 10 setting (leftmost)
(Undefined)
Pattern No.
Unit No.
Step No.
Event 10 setting (rightmost)
Event 10 setting (leftmost)
~
~
~
1st unit
4th unit (max.)
587
ES100
@ Digital Controller Protocol
Appendix K
Offset Contents (data format)
+0
+1
+2
+3
Number of send data words
(4 digits Hex)
Number of units (4 digits BCD)
1st unit Unit No. (2 digits BCD)
1st unit
Pattern No. (2 digits BCD)
Step No. (2 digits BCD)
+4 to 5
+6 to 7
+8 to 9
+10 to 11
1st unit
Local SP (8 digits BCD)
1st unit
Step time (8 digits BCD)
1st unit
PID set No. (8 digits BCD)
1st unit
Wait code (8 digits BCD)
+12 to 13
+14 to 15
+30 to 31
1st unit
Event 1 setting (8 digits BCD)
1st unit
Event 2 setting (8 digits BCD)
•
•
1st unit
Event 10 setting (8 digits BCD)
+32 to 33 2nd unit
Unit No. (2 digits BCD)
•
•
+111 to 112 4th unit
Event 9 setting (8 digits BCD)
+120 to 121
(max.)
4th unit
Event 10 setting (8 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Number of units
× 30 + 2
0001 to 0004
00 to 31
00 to 63
00 to 63
00000000 to 09999000
Remote Setting Mode (Sequence No. 268 (Hex 010C))
Switches the setting mode to the remote setting mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
588
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
00 to 31
00 to 31
Local Setting Mode (Sequence No. 269 (Hex 010D))
Switches the setting mode to the local setting mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined)
Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
External Setting Mode (Sequence No. 270 (Hex 010E))
Switches the setting mode to the external setting mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+33
~
Number of send data words
Number of units
(Undefined)
Unit No.
(Undefined) Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
589
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
00 to 31
00 to 31
Run Command (Sequence No. 271 (Hex 010F))
Starts control.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined) Unit No.
Pattern No./Bank No.
+64
+65
(Undefined) Unit No.
Pattern No. Bank No.
~
1st unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
Unit No. (2 digits BCD)
1st unit
Pattern No./Bank No.
(4 digits BCD)
+24 2nd unit
Unit No. (2 digits BCD)
•
•
• unit
Unit No. (2 digits BCD)
+65
(max.)
32nd unit
Pattern No./Bank No.
(4 digits BCD)
0000 to 0063
00 to 31
00 to 31
0000 to 0063
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
590
ES100
@ Digital Controller Protocol
Appendix K
Reset (Stop) (Sequence No. 272 (Hex 0110))
Stops control.
Send Data Word Allocation (2nd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined)
Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Auto Mode (Sequence No. 273 (Hex 0111))
Switches the control mode to the auto mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
+33 (Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
591
ES100
@ Digital Controller Protocol
Appendix K
Manual Mode (Sequence No. 274 (Hex 0112))
Switches the control mode to the manual mode.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Execute A.T. (Sequence No. 275 (Hex 0113))
Executes A.T.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined)
PID set No.
Unit No.
+64
+65
(Undefined)
PID set No.
Unit No.
~
1st unit
32nd unit (max.)
592
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
+3
+4
Unit No. (2 digits BCD)
1st unit
PID set No. (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
PID set No. (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
Number of units
× 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
0000 to 0008
00 to 31
00 to 31
0000 to 0008
Cancel A.T. (Sequence No. 276 (Hex 0114))
Cancels A.T.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+33
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
(Undefined) Unit No.
1st unit
~
2nd unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+33
(max.)
Unit No. (2 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
32nd unit
Unit No. (2 digits BCD)
00 to 31
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
593
ES100
@ Digital Controller Protocol
Appendix K
Change Pattern No. (Sequence No. 277 (Hex 0115))
Changes the pattern number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+64
+65
Number of send data words
Number of units
(Undefined) Unit No.
Pattern No.
(Undefined)
Pattern No.
Unit No.
~
1st unit
32nd unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+4
+65
(max.)
Unit No. (2 digits BCD)
1st unit
Pattern No. (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
Unit No. (2 digits BCD)
32nd unit
Pattern No. (4 digits BCD)
0001 to 0063
00 to 31
00 to 31
0001 to 0063
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Change Bank No. (Sequence No. 278 (Hex 0116))
Changes the bank number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Number of units
(Undefined) Unit No.
Bank No.
~
1st unit
+64
+65
(Undefined)
Bank No.
Unit No.
32nd unit (max.)
594
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Data
Number of units
× 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
+3
+4
Unit No. (2 digits BCD)
1st unit
Bank No. (4 digits BCD)
2nd unit
Unit No. (2 digits BCD)
•
•
•
+65
(max.)
Unit No. (2 digits BCD)
32nd unit
Bank No. (4 digits BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0000 to 0007
00 to 31
00 to 31
0000 to 0007
Read Controller Status (Sequence No. 279 (Hex 0117))
Reads the Controller status.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+26
Number of send data words
Number of units
(Undefined) Unit No.
(Undefined) Unit No.
~
1st unit
25th unit (max.)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Number of units + 2
Data
0001 to 0019 (1 to 25 decimal)
00 to 31
+26
(max.)
Unit No. (2 digits BCD)
•
•
•
25th unit
Unit No. (2 digits BCD)
00 to 31
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+121
+122
+123
+124
+125
+0
+1
+2
+3
+4
+5
~
Number of receive data words
Operation status Hold
Auto/manual
Setting mode
A.T.
Wait
SP mode
Valid pattern No.
Valid PID set No.
Operation mode
~
Operation status
Auto/manual
Setting mode
A.T.
Wait
Hold
SP mode
Valid pattern No.
Valid PID set No.
Operation mode
1st unit
25th unit (max.)
595
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of receive data words
(4 digits Hex)
1st unit
Operation status (2 digits BCD)
Hold (2 digits BCD)
+2 1st unit
Auto/manual (2 digits BCD)
SP mode (2 digits BCD)
+3
+4
+5
1st unit
Setting mode (2 digits BCD)
Valid pattern No. (2 digits BCD)
1st unit
A.T. (2 digits BCD)
Valid PD set No. (2 digits Hex)
1st unit
Wait (2 digits BCD)
Operation mode (2 digits BCD)
Data
Number of units
× 5 + 1
00: Reset
01: Run
00: Not hold
01: Hold
00: Auto mode
01: Manual mode
00: Local SP mode
01: Remote SP mode
02: Fixed SP mode
00: Local setting mode
01: Remote setting mode
02: External setting mode
00 to 63
00: Not A.T.
01: A.T.
01 to 08
00: Not waiting
01: Waiting
02: Wait alarm output
00: Setting level 1 (without technical mode)
01: Setting level 1 (with technical mode)
02: Setting level 2 (without technical mode)
03: Setting level 2 (with technical mode)
+125
(max.)
25th unit
Wait (2 digits BCD)
•
•
•
Operation mode (2 digits BCD)
00: Not waiting
01: Waiting
02: Wait alarm output
00: Setting level 1 (without technical mode)
01: Setting level 1 (with technical mode)
02: Setting level 2 (without technical mode)
03: Setting level 2 (with technical mode)
General-purpose Command (Sequence No. 280 (Hex 0118))
Sends the specified data and stores the received data in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+249
Number of send data words
Number of send data bytes
Send data (ASCII)
Send data (ASCII)
Send data
~
(max. = 496 characters)
596
ES100
@ Digital Controller Protocol
Appendix K
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of send data bytes
(4 digits Hex)
+2 Send data (2 characters ASCII)
•
•
•
Send data (1 character ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The number of send bytes not including @, the FCS, or the terminator.
Refer to the manual for the ES100
@.
Use ASCII (Up to 496 characters total.)
+249
(max.)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+249
Number of receive data words
Receive data (ASCII)
Receive data (ASCII)
Receive data (Undefined)
~
(max. = 251 characters)
Offset
+0
+1
+249
(max.)
Contents (data format)
Number of receive data words
(4 digits Hex)
Receive data
(2 characters ASCII)
•
•
•
Receive data
(1 character ASCII)
Data
0001 to 00FA (1 to 250 decimal)
Refer to the manual for the ES100
@.
Returned as ASCII (Up to 498 characters total.)
Note 1.
At transmission, a header code “@” is attached before the data and the FCS and a terminator “*”CR are attached following the send data.
First word of send +0 data
+1
+2
+3
+4
+5
0006
0007
"AB"
"CD"
"EF"
"GH"
@ABCDEFG[FCS]*CR
2 bytes
2.
At reception, data excluding the header code “@” at the beginning of the receive data and the FCS and terminator “*”CR at the end of the data is stored in the receive data storage words.
@ABCDEFG[FCS]*CR
2 bytes
First word of send data
+0
+1
+2
+3
+4
+5
0006
0007
"AB"
"CD"
"EF"
"G"
3.
Refer to the manual for the ES100
@ for the contents of send data and receive data.
597
Appendix L
K3T
@ Intelligent Signal Processor Protocol
The K3T
@ Intelligent Signal Processor Protocol is used to make various settings or control remotely the Intelligent Signal Processor connected to the Serial Communications Unit/Board via RS-232C or RS-422/485 cable.
Protocol Configuration
The configuration of the K3T
@ Intelligent Signal Processor Protocol is shown as follows:
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
No 300 (012C) Reset (by unit number) Performs the same processing as when an input is received on the reset terminal.
301 (012D) Reset (continuous units) Performs the same processing as when an input is received on the reset terminal.
302 (012E)
303 (012F)
Write set value (by unit number)
Write set value HH (continuous units)
Writes the set value HH, H, L, or
LL.
Writes the set value HH.
304 (0130) Write set value H (continuous units)
Writes the set value H.
305 (0131) Write set value L (continuous units)
306 (0132) Write set value LL (continuous units)
307 (0133) Write set value with bank
(by unit number)
Writes the set value L.
Writes the set value LL.
308 (0134)
309 (0135)
312 (0138)
Write set value HH with bank (continuous units)
Write set value H with bank (continuous units)
310 (0136) Write set value L with bank (continuous units)
311 (0137) Write set value LL with bank (continuous units)
Write set value O5 with bank (continuous units)
Writes the set value to a bank which is not in use (K3TR: HH to
LL, K3TC: O1 to O5).
Writes the set value HH to a bank which is not in use.
Writes the set value H to a bank which is not in use.
Writes the set value L to a bank which is not in use.
Writes the set value LL to a bank which is not in use.
Writes the set value O5 to a bank which is not in use.
313 (0139) Write set value O4 with bank (continuous units)
314 (013A) Write set value O3 with bank (continuous units)
315 (013B) Write set value O2 with bank (continuous units)
316 (013C) Write set value O1 with bank (continuous units)
317 (013D) Read set value (by unit number)
318 (013E) Read set value HH (continuous units)
Writes the set value O4 to a bank which is not in use.
Writes the set value O3 to a bank which is not in use.
Writes the set value O2 to a bank which is not in use.
Writes the set value O1 to a bank which is not in use.
Reads the set value HH, H, L, or
LL.
Reads the set value HH.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
Notes
599
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Receive word allocation
Yes Yes 1
Notes
319 (013F) Read set value H (continuous units)
320 (0140) Read set value L (continuous units)
321 (0141) Read set value LL (continuous units)
322 (0142) Read set value with bank
(by unit number)
Reads the set value H.
Reads the set value L.
Reads the set value LL.
323 (0143) Read set value HH with
325 (0145)
326 (0146) bank (continuous units)
324 (0144) Read set value H with bank (continuous units)
Read set value L with bank (continuous units)
Read set value LL with bank (continuous units)
Reads set value of a bank which is not in use (K3TR: HH to LL, K3TC:
O1 to O5).
Reads the set value HH of a bank which is not in use.
Reads the set value H of a bank which is not in use.
Reads the set value L of a bank which is not in use.
Reads the set value LL of a bank which is not in use.
327 (0147)
328 (0148)
329 (0149)
330 (014A)
331 (014B)
332 (014C)
333 (014D)
Read set value O5 with bank (continuous units)
Read set value O4 with bank (continuous units)
Read set value O3 with bank (continuous units)
Read set value O2 with bank (continuous units)
Read set value O1 with bank (continuous units)
Read holding data (by unit number)
Read holding data PH
(continuous units)
334 (014E) Read holding data BH
(continuous units)
335 (014F) Read display value (PV)
(by unit number)
336 (0150) Read display value (PV)
(continuous units)
337 (0151) Read model (by unit number)
338 (0152) Read model (continuous units)
339 (0153) General-purpose command
Reads the set value O5 of a bank which is not in use.
Reads the set value O4 of a bank which is not in use.
Reads the set value O3 of a bank which is not in use.
Reads the set value O2 of a bank which is not in use.
Reads the set value O1 of a bank which is not in use.
Reads the peak/bottom data (maximum, minimum).
Reads the peak data (maximum).
Reads the bottom data (minimum).
Reads the display value (PV).
Reads the display value (PV).
Reads the model data.
Reads the model data.
Send specified data or receives specified data and writes it to the receive data words.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
1
1
2
1
1
1
1
1
1
1
1
1
3
3
3
Note 1.
Special specifications are required to use communications + comparison output.
2.
Special specifications are required to use communications + comparison output for the K3TR and
K3TC. The operands HH, H, L, and LL are for the K3TR, and the operands O5, O4, O3, O2, and O1 are for the K3TC.
3.
Not available for the K3TC.
4.
The hexadecimal equivalents of sequences numbers are given in parentheses.
600
K3T
@ Intelligent Signal Processor Protocol
5.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation:
Receive word allocation:
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
Appendix L
Connections
The connections used for the K3T
@ Intelligent Signal Processor Protocol are shown below.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
K3T
#
RS-232C
RS-232C port
RS-232C
Signal name
Protective ground or earth
Signal ground or common return line
Send data
Receive data
Request to send
Clear to send
Data set ready
Data terminal ready
Serial Communications Unit/Board
RS-232C: D-sub
9-pin female
Signal
Name
FG
SG
SD
RD
RTS
CTS
DSR
DTR
5
7
8
3
4
9
2
Pin
No.
1
Shield
FG
SG
SD
RD
RS
CS
DR
ER
Abbreviation
---
---
Signal direction
Output
Input
Output
Input
Input
Output
Pin No.
4
5
2
3
1
7
6
20
Intelligent Signal
Processor
RS-232C:
Terminal block
7
2
3
Terminal
Signal
Name
1 FG
SG
SD
RD
4
5
RTS
CTS
6 DSR
20 DTR
MAX232C or equivalent
Note 1.
The connection configuration is a one-to-one configuration and the maximum cable length is 15 m.
2.
Use shielded twisted-pair cable.
601
K3T
@ Intelligent Signal Processor Protocol
RS-422/485 Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-422/485 port
Appendix L
RS-422/485
K3T
#
K3T
#
RS-422/485
Up to 32 units can be connected
K3T
#
RS-422/485
• RS-422 4-wire Connections
Signal name
Send data A
Send data B
Receive data A
Receive data B
Signal ground
Protective ground
Abbreviation
SDA
SDB
RDA
RDB
SG
FG
Signal direction Pin No.
Output 9
Output 5
Output
Input
---
---
6
1
3
7
Serial Communications
Board/Unit
RS-422: D-sub
9-pin female
Signal
Name
Pin
No.
FG
Hood
RDA
6
RDB
SDA
8
1
SDB
2
*1: Set the 2-/4-wire switch to the 4-wire setting.
*2: Turn ON the terminating resistance switch.
Shield
Intelligent Signal Processor
9
5
6
1
3
RS-422:
Terminal block
Terminal.
Signal
Name
SDA
SDB
RDA
RDB
SG
220
Ω
Terminal block SW
220
Ω
SN751177N or equivalent
6.8 V
Terminating resistance (approx. 220
Ω) is connected via the terminal block switch.
602
K3T
@ Intelligent Signal Processor Protocol
• RS-485 2-wire Connections
Signal name
Inverting output
Non-inverting output
Appendix L
–
Abbreviation Signal direction Terminal
Input or output 19
+ Input or output 18
Serial Communications
Board/Unit
RS-485: D-sub
9-pin female
Signal
Name
Pin
No.
FG
SDA
SDB
1
2
Intelligent Signal Processor
Turn ON the terminal block switch for terminators only.
5 V
51 k
Ω
RS-485:
Terminal block
Terminal block SW
220
Ω
Terminal.
Signal
Name
19
18
4.7 k
Ω
6.8 V
4.7 k
Ω
4.7 k
Ω
SN751177N or equivalent
TX
RX
Shield
*1: Set the 2-/4-wire switch to the 2-wire setting.
*2: Turn ON the terminating resistance switch.
Intelligent Signal Processor
Unit designated as terminator.
RS-485:
Terminal block
Terminal.
Signal
Name
18
19
220
Ω
Terminal block SW ON
The terminal block switch is turned ON.
Shield
Note 1.
The connection configuration is a one-to-one or a 1-to-N configuration. For 1-to-N connections, up to
32 units including the Serial Communications Boards/Units can be connected.
2.
The maximum cable length is 500 m. Use shielded twisted-pair cables (AWG28i or greater).
3.
Connect terminating resistance at both ends of the transmission path.
4.
Turn the terminal block switch ON at the terminators.
5.
Turn the terminal block switches OFF for units that are not terminators.
603
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Reset (by Unit Number) (Sequence No. 300 (Hex 012C))
This sequence performs the same processing as when an input is received on the reset terminal.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+33
Number of send data words
Number of units
(Undefined) Relevant unit No.
~
(Undefined) Relevant unit No.
Offset
+0
+1
+2
+33
Contents (data format)
Number of send data words
(4 digits BCD)
Number of units
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
Data
0003 to 0022 (3 to 34 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
00 to 99
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Reset Control (Continuous Units)
(Sequence No. 301 (Hex 012D))
This sequence performs reset control for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
0002
0001 to 0020 (1 to 32 decimal)
604
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Write Set Value (by Unit Number) (Sequence No. 302 (Hex 012E))
This sequence writes each set value (HH, H, L, LL).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+122
+123
~
+124
+125
Number of send data words
Number of units
(Undefined) Relevant unit No.
Operand
Set value
(Undefined)
(Undefined) Relevant unit No.
Operand
Set value
(Undefined)
~
Set value
Set value
Offset Contents (data format)
+0
+1
+2
+3
Number of send data words
(4 digits BCD)
Number of units
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
Operand
(ASCII 2 characters)
+4 to +5 Set value
(5 digits BCD)
Data
0006 to 007E (6 to 126 decimal)
0001 to 001F (1 to 31 decimal)
00 to 99
4848 (“HH”), 4C4C (“LL”)
4820 (“H”), 4C20 (“L”)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+4
+5
2345
0001
+4
+5
1234
000F
+124 to
+125
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Set Value HH (Continuous Units) (Sequence No. 303 (Hex
012F))
This sequence writes set value HH for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+64
+65
Number of send data words
Number of units
Set value
(Undefined)
Set value
(Undefined)
~
Set value
Set value
605
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
+1 Number of units
(4 digits Hex)
+2 to +3 Set value
(5 digits BCD)
Data
0004 to 0042 (4 to 66 decimal)
0001 to 0020 (1 to 32 decimal)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+2
+3
2345
0001
+2
+3
1234
000F
+64 to
+65
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Set Value H (Continuous Units) (Sequence No. 304 (Hex
0130))
This sequence writes set value H for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value L (Continuous Units) (Sequence No. 305 (Hex
0131))
This sequence writes set value L for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value LL (Continuous Units) (Sequence No. 306 (Hex
0132))
This sequence writes set value LL for continuous units. The word allocation is identical to that of sequence No.
303 (Write Set Value HH (Continuous Units)).
Write Set Value with Bank (by Unit Number) (Sequence No. 307
(Hex 0133))
This sequence writes set value of a bank which is not in use (K3TR: HH to LL, K3TC:O1 to O5).
606
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+122
~
+123
+124
+125
+126
Number of send data words
Number of units
(Undefined)
Relevant unit No.
(Undefined)
Bank No.
Operand
Set value
(Undefined)
(Undefined)
(Undefined)
(Undefined)
Relevant unit No.
Operand
Set value
Bank No.
~
Set value
Set value
Offset Contents (data format)
+0
+1
+2
+3
+4
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
Bank No.
(2 digits BCD)
Operand
(Two ASCII characters)
+5 to +6 Set value
(5 digits BCD)
Data
0007 to 007F (7 to 127 decimal)
0001 to 0019 (1 to 25 decimal)
00 to 99
01 to 04
4848 (“HH”), 4F31 (“O1”)
4820 (“H”), 4F32 (“O2”)
4C20 (“L”), 4F33 (“O3”)
4C4C (“LL”), 4F34 (“O4”)
4F35 (“O5”)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+5
+6
2345
0001
+5
+6
1234
000F
+125 to
+126
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
607
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Write Set Value HH with Bank (Continuous Units)
(Sequence No. 308 (Hex 0134))
This sequence writes set value HH of a bank not in use for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+95
~
+96
+97
Number of send data words
Number of units
(Undefined) Bank No.
Set value
(Undefined)
(Undefined)
Set value
Bank No.
(Undefined)
~
Set value
Set value
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
+2 Bank No.
(2 digits BCD)
+3 to +4 Set value
(5 digits BCD)
Data
0005 to 0062 (5 to 98 decimal)
0001 to 0020 (1 to 32 decimal)
01 to 04
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+2
+3
2345
0001
+2
+3
1234
000F
+96 to
+97
Set value
(5 digits BCD)
•
•
•
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Set Value H with Bank (Continuous Units)
(Sequence No. 309 (Hex 0135))
This sequence writes set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value L with Bank (Continuous Units)
(Sequence No. 310 (Hex 0136))
This sequence writes set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value LL with Bank (Continuous Units)
(Sequence No. 311 (Hex 0137))
This sequence writes set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
608
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Write Set Value O5 with Bank (Continuous Units)
(Sequence No. 312 (Hex 0138))
This sequence writes set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O4 with Bank (Continuous Units)
(Sequence No. 313 (Hex 0139))
This sequence writes set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O3 with Bank (Continuous Units)
(Sequence No. 314 (Hex 013A))
This sequence writes set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O2 with Bank (Continuous Units)
(Sequence No. 315 (Hex 013B))
This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O1 with Bank (Continuous Units)
(Sequence No. 316 (Hex 013C))
This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Read Set Value (by Unit Number) (Sequence No. 317 (Hex 013D))
Reads set value HH, H, L, or LL.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+64
+65
Number of send data words
Number of units
(Undefined) Relevant unit No.
Operand
~
(Undefined) Relevant unit No.
Operand
Offset Contents (data format)
+0
+1
+2
+3
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
Operand
(ASCII 2 characters)
Data
0004 to 0042 (4 to 66 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
4848 (“HH”), 4C4C (“LL”) 4F31 (“01”)
4820 (“H”), 4C20 (“L”) 4F35 (“05”)
609
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Offset Contents (data format)
•
•
•
+64 to
+65
Operand
(ASCII 2 characters)
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
Number of receive data words
(Undefined) End code
Set value
(Undefined)
+94
~
+95
+96
(Undefined)
Set value
(Undefined)
End code
~
Set value
Set value
Data
Offset Contents (data format)
+0 Number of receive data words
(4 digits Hex)
+1 End code (2 digits Hex)
+2 to +3 Set value
(5 digits BCD)
Data
0004 to 0061 (4 to 97 decimal)
00 to 22
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+2
+3
2345
0001
+2
+3
1234
000F
+95 to
+96
Set value
(5 digits BCD)
•
•
•
Same as above
Read Set Value HH (Continuous Units) (Sequence No. 318 (Hex
013E))
This sequence reads set value HH for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
0002
Data
0001 to 0020 (1 to 32 decimal)
Receive Data Word Allocation (4th Operand of PMCR(260))
This sequence is similar to sequence No. 317 (Read Set Value (by Unit Number)).
Read Set Value H (Continuous Units) (Sequence No. 319 (Hex
013F))
This sequence reads set value H for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
610
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Read Set Value L (Continuous Units) (Sequence No. 320 (Hex
0140))
This sequence reads set value L for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
Read Set Value LL (Continuous Units) (Sequence No. 321 (Hex
0141))
This sequence reads set value LL for continuous units. The word allocation is identical to that of sequence No.
318 (Read Set Value HH (Continuous Units)).
Read Set Value with Bank (by Unit Number) (Sequence No. 322
(Hex 0142))
Reads the set value of a bank which is not in use (K3TR: HH to LL, K3TC:01 to 05) and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
~
+95
+96
+97
Number of send data words
(Undefined)
(Undefined)
Number of units
Relevant unit No.
(Undefined)
Operand
Bank No.
~
(Undefined)
(Undefined)
Relevant unit No.
Bank No.
Operand
+1
+2
+3
+4
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Relevant unit No. (2 digits BCD)
Bank No. (2 digits BCD)
Operand (ASCII 2 characters)
Data
0005 to 0062 (5 to 98 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
01 to 04
4848 (“HH”),
4820 (“H”),
4C20 (“L”),
4C4C (“LL”),
4F31 (“O1”)
4F32 (“O2”)
4F33 (“O3”)
4F34 (“O4”)
4F35 (“O5”)
+ 97
•
•
•
Operand (ASCII 2 characters) Same as above
611
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Set value
(Undefined) +2
+63
~
+64
Set value
(Undefined)
~
Set value
Set value
Offset Contents (data format)
+0 Number of receive data words (4 digits Hex)
+1 to +2 Set value
(5 digits BCD)
Data
0003 to 0041 (3 to 65 decimal)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+1
+2
2345
0001
+1
+2
1234
000F
+63 to
+64
Set value
(5 digits BCD)
•
•
•
Same as above
Read Set Value HH with Bank (Continuous Units)
(Sequence No. 323 (Hex 0143))
This sequence reads set value HH of a bank not in use for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
`
First word of send data
+0
+1
+2
~
+33
Number of send data words
Number of units
(Undefined)
Bank No.
(Undefined)
Bank No.
~
Offset
+0
+1
+2
+ 33
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
Bank No. (2 digits BCD)
•
•
•
Bank No. (2 digits BCD)
Data
0003 to 0022 (3 to 34 decimal)
0001 to 0020 (1 to 32 decimal)
01 to 04
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)).
Read Set Value H with Bank (Continuous Units)
(Sequence No. 324 (Hex 0144))
This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
612
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Read Set Value L with Bank (Continuous Units)
(Sequence No. 325 (Hex 0145))
This sequence reads set value L of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value LL with Bank (Continuous Units)
(Sequence No. 326 (Hex 0146))
This sequence reads set value LL of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O5 with Bank (Continuous Units)
(Sequence No. 327 (Hex 0147))
This sequence reads set value O5 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O4 with Bank (Continuous Units)
(Sequence No. 328 (Hex 0148))
This sequence reads set value O4 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O3 with Bank (Continuous Units)
(Sequence No. 329 (Hex 0149))
This sequence reads set value O3 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O2 with Bank (Continuous Units)
(Sequence No. 330 (Hex 014A))
This sequence reads set value O2 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O1 with Bank (Continuous Units)
(Sequence No. 331 (Hex 014B))
This sequence reads set value O1 of a bank not in use for continuous units. The word allocation is identical to that of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Holding Data (Sequence No. 332 (Hex 014C))
Reads the peak/bottom data (maximum, minimum) and stores the results in the specified words.
613
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+64
+65
Number of send data words
Number of compared data
(Undefined)
Relevant unit No.
Operand
~
(Undefined) Relevant unit No.
Operand
Data
0004 to 0042 (4 to 66 decimal)
Offset
+0
+1
+2
+3
Contents (data format)
Number of send data words
(4 digits Hex)
Number of compared data
(4 digits Hex)
Relevant unit No. (2 digits BCD)
Operand (ASCII 2 characters)
+65
•
•
•
Operand (ASCII 2 characters)
0001 to 0020 (1 to 32 decimal)
00 to 99
5048 (“PH”)
4248 (“BH”)
Same as above
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+94
~
+95
+96
Number of receive data words
Peak/bottom data
(Undefined)
(Undefined)
Status
Peak/bottom data
(Undefined)
(Undefined)
Status
~
Peak/bottom data
Peak/bottom data
Offset Contents (data format)
+0 Number of receive data words (4 digits Hex)
+1 to +2 Peak/bottom data
(5 digits BCD)
Data
0004 to 0061 (4 to 97 decimal)
00000 to 99999
Negative sign: F (most significant digit)
Example 12345 Example –1234
+1
+2
2345
0001
+1
+2
1234
F000
614
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Offset Contents (data format)
+3 Status
(2 digits Hex)
Data
d0 bit:
If overflow:1 d1 bit:
If underflow:1 d4 bit:
Not used d5 bit:
During hold input:1
Others: 0
Others: 0 d2 bit:
Not used d3 bit:
During forced zero operation:1
(K3TH,K3TR: 0)
Others: 0 d6 bit:
Bank input 1:1
(K3TH, K3TX: 0) d7 bit:
Bank input 2:1
(K3TH, K3TX: 0)
Others: 0
Others: 0
Others: 0
•
•
•
+96 Status Same as above
Read Holding Data PH (Continuous Units) (Sequence No. 333
(Hex 014D))
This sequence reads peak holding data for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units (4 digits Hex)
0002
Data
0001 to 0020 (1 to 32 decimal)
Receive Data Word Allocation (4th Operand of PMCR(260))
The data allocation is similar to sequence No. 332 (Read Holding Data (by Unit Number)).
Read Holding Data BH (Continuous Units) (Sequence No. 334
(Hex 014E))
This sequence reads bottom holding data for continuous units. The word allocation is identical to that of sequence No. 333 (Read Holding Data PH (Continuous Units)).
Read Display Value (PV) (by Unit Number) (Sequence No. 335
(Hex 014F))
Reads the display value (PV) and stores the results in the specified words.
615
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+33
Number of send data words
Number of compared data
(Undefined) Relevant unit No.
~
(Undefined) Relevant unit No.
Offset
+0
+1
+2
+ 33
Contents
(data format)
Number of send data words
(4 digits Hex)
Number of compared data
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
Data
0003 to 0022 (3 to 34 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
00 to 99
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+94
~
+95
+96
Number of receive data words
Display value
(Undefined)
Status
Display value
(Undefined)
Status
~
Display value
Display value
Offset Contents (data format)
+0 Number of receive data words (4 digits Hex)
+1 to +2 Display value
(5 digits Hex)
Data
0004 to 0061 (4 to 97 decimal)
00000 to 99999
Negative sign: F (5th digit in BCD)
Example 12345 Example –1234
+1
+2
2345
0001
+1
+2
1234
000F
616
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Offset Contents (data format)
+3 Status (4 digits Hex)
Data
d0 bit:
If overflow:1 d1 bit:
If underflow:1
Others: 0
Others: 0 d2 bit:
Not used d3 bit:
During forced zero operation:1
(K3TH, K3TR, K3TC: 0) d4 bit:
In test mode: d5 bit:
While holding input:1
Others: 0
Others: 0
Others: 0 d6 bit:
Bank input 1:1
(K3TH, K3TX: 0) d7 bit:
Bank input 2:1
(K3TH, K3TX: 0)
Others: 0
Others: 0 d8 bit:
LL comparison output:1 Others: 0
OUT1 comparison output: 1 (K3TC) d9 bit:
L comparison output:1 Others: 0
OUT2 comparison output:1 (K3TC) d10 bit:
H comparison output:1 Others: 0
OUT4 comparison output:1 K3TC) d11 bit:
HH comparison output:1 Others: 0
OUT5 comparison output:1 (K3TC) d12 bit:
PASS comparison output:1 Others: 0
OUT3 comparison output:1 (K3TC) d13 bit: Not used d14 bit: Not used d15 bit: Not used
+96
•
•
•
Status (4 digits BIN) Same as above
617
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Read Display Value (PV) (Continuous Units) (Sequence No. 336
(Hex 0150))
This sequence reads display value (PV) for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
0002
Data
0001 to 0020 (1 to 32 decimal)
Receive Data Word Allocation (4th Operand of PMCR(260))
This sequence is similar to sequence No. 335 (Read Display Value (PV) (Continuous Units)).
Model Data Read (by Unit Number) (Sequence No. 337 (Hex
0151))
Reads model data and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+26
Number of send data words
Number of units
(Undefined) Relevant unit No.
~
(Undefined) Relevant unit No.
Offset Contents (data format)
+0
+1
+2
+ 26
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
Relevant unit No.
(2 digits BCD)
•
•
•
Relevant unit No.
(2 digits BCD)
Data
0003 to 001B (3 to 27 decimal)
0001 to 0019 (1 to 25 decimal)
00 to 99
Same as above
Note The number of Units can be up to 25 maximum.
618
K3T
@ Intelligent Signal Processor Protocol
Appendix L
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+121
+122
+123
+124
+125
+0
+1
+2
+3
+4
+5
~
Number of receive data words
Input specifications
Input specifications
Display specifications
Output specifications
Input contents
Operation mode
~
Input specifications
Input specifications
Display specifications
Output specifications
Input contents
Operation mode
Offset Contents (data format)
+0
+1 to
+ 2
+2
+3
+4
+5
Number of receive data words (4 digits Hex)
Input specifications (ASCII 3 characters)
Display specifications (ASCII
1 character)
Output specifications (ASCII
2 characters)
Input contents
(ASCII 2 characters)
Operation mode
(ASCII 2 characters)
Data
0006 to 007E (6 to 126 decimal)
544131 (“TA1”) (K3TH)
544231 (“TB1”) (K3TH)
564432 (“VD2”) (K3TX)
414432 (“AD2”) (K3TX)
564132 (“VA2”) (K3TX)
414132 (“AA2”) (K3TX)
524231 (“RB1”) (K3TR, K3TC)
41 (“A”) (common)
42 (“B”) (K3TH, K3TX)
43 (“C”) (K3TR, K3TC)
5331 (“S1”) (RS-232C)
5332 (“S2”) (RS-485)
5333 (“S3”) (RS-422)
5335 (“S5”) (RS-485 + comparison output)
5336 (“S6”) (RS-422 + comparison output)
Leftmost digit: 30 (“0”) to 31 (“1”)
Rightmost digit: 31 (“1”) to 45 (“E”)
3030 (“00”) (K3TH, K3TX)
3031 (“00”) to 3133 (“12”) (K3TR)
5542 (“UB”) (K3TC)
5543 (“UC”) (K3TC)
+125
•
•
•
Operation mode
(ASCII 2 characters)
Same as above
Model Data Read (Continuous Units) (Sequence No. 338 (Hex
0152))
This sequence reads model data for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
Number of units
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of units
(4 digits Hex)
0002
Data
0001 to 0019 (1 to 25 decimal)
Note The number of Units can be up to 25 maximum.
619
K3T
@ Intelligent Signal Processor Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)).
Appendix L
General-purpose Command (Sequence No. 339 (Hex 0153))
Sends the specified data and writes the receive data to the receive data words. The characters such as “@”,
FCS, terminators need not be set in the send and receive data words. These characters will be automatically added for transmission and automatically removed before saving data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+249
Number of send data words
Send data byte length
Send data
Send data
Send data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Send data byte length (4 digits BCD)
Data
0003 to 00FA (3 to 250 decimal)
+2 to
+249
Send data (ASCII)
0001 to 01F0 (1 to 496 decimal)
Number of bytes of send data not including
@, the FCS, and the terminator.
ASCII
Send data: 496 characters max.
Receive Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
~
+249
Number of receive data words
Receive data
Receive data
Receive data
Receive data
Offset
+0
+1 to
+249
Contents (data format)
Number of receive data words
(4 digits Hex)
Receive data (ASCII)
~
Data
0001 to 00FA (1 to 250 decimal)
ASCII
Receive data: 498 characters max.
620
Appendix M
V500/V520 Bar Code Reader Protocol
The V500/V520 Bar Code Reader Protocol is used to make various settings or control remotely the Bar Code
Reader connected the Serial Communications Unit/Board via RS-232C cable.
Protocol Configuration
The configuration of the V500/V520 Bar Code Reader Protocol is shown below.
Sequence
No.
Communications sequence name
Function
350 (015E) BCR read start
351 (015F) BCR read stop
352 (0160) Data read
353 (0161) Complete data read
354 (0162) BCR function write
(V500)
355 (0163) BCR function read
(V500)
356 (0164) Log data output request
(V500)
357 (0165) Preset data set (V500)
358 (0166) BCR connection confirmation (V500)
359 (0167) Log data clear (V500)
360 (0168) Continuous data read
(scan) (V500)
Instructs the Reader to start a BCR read.
Instructs the Reader to stop a BCR read.
Data read by the Reader is received and saved in the receive words.
Instructs the Reader to start a read. After the data read by the Reader is received and saved to the receive words, reading is stopped.
Writes the operation mode and read functions.
Reads the operation mode and read functions.
Requests output of log data sent to host.
Writes preset data.
Confirms if the Reader is correctly set.
Ladder interface
Send word allocation
Receive word allocation
No
No
No
No
No
Yes
No
Yes
No
Yes
Yes
No
No
No
Yes
No
Yes
Yes
No
No
No
Yes
361 (0169) Continuous data read
(interrupt) (V500)
362 (016A) BCR initialize
363 (016B) Continuous data read
(scan) (V520)
364 (016C) Continuous data read
(interrupt) (V520)
365 (016D) General-purpose command 1
366 (016E) General-purpose command 2
Clear log data.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt
No.100).
Clears the log, confirms BCR connection, and sets BCRs.
Performs the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the scan method.
Performing the following operations repeatedly: starts reading, receives data read by the Reader, saves the data to the receive words by the interrupt method (interrupt
No.100).
Used to send data of a specified data length, and receive only ACK as the receive data.
Used to send data of a specified data length, and receive ACK together with the return of other receive data. The frame format of the receive data, however, has to contain STX and ETX.
No
Yes
No
No
Yes
Yes
Yes
No
Yes
Yes
No
Yes
621
V500/V520 Bar Code Reader Protocol
Appendix M
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
3.
Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the
CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with the Serial Communications Unit.
Connections
The connections for using the V500/V520 Bar Code Reader Protocol are shown below.
V500 Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-232C port
100 VAC
V500-C11
ID Controller
V520-R12
#
Reader
Serial Communications Unit/Board:
D-sub 9 pin female
Signal
Name
FG
SD
RD
Pin No.
1
2
3
RTS
CTS
DSR
DTR
SG
4
5
7
8
9
V509-W040
Reader Cable
V500-C11:
D-sub 9 pin female
Pin No.
1
2
3
4
5
7
8
9
Signal
Name
FG
SD
RD
RTS
CTS
DSR
DTR
SG
622
V500/V520 Bar Code Reader Protocol
V520 Connections
Appendix M
V520-R121
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-232C port
Reader
V509-W011
Reader Cable
Serial Communications Unit/Board:
D-sub 9 pin female
Signal
Name
FG
SD
RD
RTS
CTS
DSR
DTR
SG
Pin No.
3
4
5
1
2
7
8
9
1
2
3
4
6
7
V520-R121:
D-sub 9 pin female
Pin No.
Signal
Name
SD
RD
RTS
CTS
DTR
SG
System Setting
Shown below are the system settings of the V500-C11 and V520-R121 when this protocol is used.
Note The portions enclosed by in boxes are used for this protocol.
V500-C11
• BCR Functions
Read trigger
"READ SIGNAL INPUT", "ONLINE READ COMMAND"
Read control method
"SINGLE READ", "CONTINUOUS READ"
• Host Interface
Prefix
Suffix
Bar code output
NONE, "STX"
"ETX" , "CR "
"OUTPUT" , "NO OUTPUT"
V520-R121
Start code
Stop code
Operation mode
Data output mode
NONE, "STX"
"ETX" , "CR"
External trigger, host trigger
1-shot, continuous
623
V500/V520 Bar Code Reader Protocol
Appendix M
BCR Read Start (Sequence No. 350 (Hex 015E))
This sequence instructs the Bar Code Reader to start reading.
Send Data Word Allocation 3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
BCR Read Stop (Sequence No. 351 (Hex 015F))
This sequence instructs the Bar Code Reader to stop reading.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data Read (Sequence No. 352 (Hex 0160))
This sequence receives read data and saves it to the receive data storage words.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
~
+15
+16
Number of receive data words
Read data
Read data
Read data
Read data
Read data
Read data
~
Offset Contents (data format)
+0
+1 to
+16
Number of receive data words (4 digits Hex)
Read data (ASCII)
Data
0002 to 0011 (2 to 17 decimal)
30 (‘0’) to 39 (‘9’), 41 (‘A’) to 5A (‘Z’), 3F (‘?’)
Up to 32 characters in ASCII
Note The reception wait time is not set for this sequence.
Complete Data Read (Sequence No. 353 (Hex 0161))
This sequence instructs the Bar Code Reader to start reading, receives the data read by the Bar Code Reader, stores the data in the receive data storage words, and then instructs the Reader to stop reading.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
It is similar to sequence No. 352 (Data read).
Note The reception wait time is not set for this sequence.
624
V500/V520 Bar Code Reader Protocol
Appendix M
BCR Function Write (V500) (Sequence No. 345 (Hex 0162))
This sequence sets the operation mode and read functions in the Bar Code Reader.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
Operation mode
Types of bar code
In-zone control
(Undefined)
(Undefined)
Number of digits
Modulus check
(Undefined)
(Undefined)
Buzzer
Number of matches
Multistep labels
Horizontal control
Offset Contents (data format)
+0 Number of send data words
(4 digits Hex)
0007 (fixed)
+2
+4
+5
(ASCII 1 character)
In-zone control
(ASCII 1 character)
Bar code type
(ASCII 1 character)
(2 digits BCD)
Modulus check
(ASCII 1 character)
Data
41 (‘A’): ONLINE
*42 (‘B’): ONLINE CONTROL
*41 (‘A’): ON
42 (‘B’): OFF
41 (‘A’): JAN
42 (‘B’): NW7 NORMAL
43 (‘C’): NW7 SMALL
44 (‘D’): NW7 HEX
45 (‘E’): CODE39 NORMAL
46 (‘F’): CODE39 ST/SP OUTPUT
47 (‘G’): 2 of 5 (ITF)
48 (‘H’): CODE128
49 (‘I’): CODE93
4A (‘J’): 2 of 5 (3BAR)
4B (‘K’): 2 of 5 (5BAR)
00 to 32
00: Any number of digits allowed.
41 (‘A’): No-check
42 (‘B’): Modulus 10 (all bar codes)
43 (‘C’): Modulus 11 (except JAN)
44 (‘D’): Modulus 16 (NW7 only)
45 (‘E’): Modulus 43 (CODE39 only)
46 (‘F’): Modulus 47 (CODE93 only)
47 (‘G’): Modulus 103 (CODE128 only)
1 to 5
+6
Number of matches
(1 digit BCD)
Multistep labels
(1 digit BCD)
Buzzer
(ASCII 1 character)
Horizontal control mode
(ASCII 1 character)
1 to 4
41 (‘A’): ON for normal read
42 (‘B’): ON for no-read
43 (‘C’): OFF
41 (‘A’): Normal (continuous rotating)
42 (‘B’): In-zone startup
Note Selecting the values marked with asterisks is required for this protocol.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
625
V500/V520 Bar Code Reader Protocol
Appendix M
BCR Function Read (V500) (Sequence No. 355 (Hex 0163))
This sequence reads the settings of functions in the Bar Code Reader.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
Operation mode
Types of bar code
In-zone control
(Undefined)
(Undefined)
Modulus check
Number of digits
(Undefined)
(Undefined)
Buzzer
Number of matches.
Multistep labels.
Horizontal control
Offset Contents (data format)
+0 Number of receive data words (4 digits Hex)
0007 (fixed)
+2
(ASCII 1 character)
In-zone control
(ASCII 1 character)
Bar code type
(ASCII 1 character)
Data
41 (‘A’): ONLINE
42 (‘B’): ONLINE CONTROL
41 (‘A’): ON
42 (‘B’): OFF
41 (‘A’): JAN
42 (‘B’): NW7 NORMAL
43 (‘C’): NW7 SMALL
44 (‘D’): NW7 HEX
45 (‘E’): CODE39 NORMAL
46 (‘F’): CODE39 ST/SP Output
47 (‘G’): 2 of 5 (ITF)
48 (‘H’): CODE128
49 (‘I’): CODE93
4A (‘J’): 2 of 5 (3BAR)
4B (‘K’): 2 of 5 (5BAR)
00 to 32
+4
(2 digits BCD)
Modulus check
(ASCII 1 character)
+5
41 (‘A’): No-check
42 (‘B’): Modulus 10 (all bar codes)
43 (‘C’): Modulus 11 (except JAN)
44 (‘D’): Modulus 16 (NW7 only)
45 (‘E’): Modulus 43 (CODE39 only)
46 (‘F’): Modulus 47 (CODE93 only)
47 (‘G’): Modulus 103 (CODE128 only)
1 to 5
+6
Number of matches
(1 digit BCD)
Multistep labels
(1 digit BCD)
Buzzer
(ASCII 1 character)
Horizontal control mode
(ASCII 1 character)
1 to 4
41 (‘A’): ON for normal read
42 (‘B’): ON for no-read
43 (‘C’): OFF
41 (‘A’): Normal (continuous rotating)
42 (‘B’): In-zone startup
626
V500/V520 Bar Code Reader Protocol
Appendix M
Log Data Output Request (V500) (Sequence No. 356 (Hex 0164))
This sequence requests output of the log data sent to host.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Number of units
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of units
(2 digits BCD)
0002 (fixed)
01 to 99
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+248
+249
Number of receive data words
Log data
Log data
Log data
Log data
~
Offset Contents (data format)
+0
+1 to
+249
Number of receive data words (4 digits Hex)
Log data (ASCII)
Data
0001 to 00FA (1 to 250 decimal)
Log data with the number of designated data is stored including the separator GS (1D).
If the log data (including separator) exceeds 498 bytes, only 498 bytes are stored.
Note No retries are performed for this sequence.
627
V500/V520 Bar Code Reader Protocol
Appendix M
Preset Data Set (V500) (Sequence No. 357 (Hex 0165))
This sequence sets preset data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+18
~
+19
Number of send data words
(Undefined)
(Undefined)
(Undefined)
Number of units
Preset data
Preset data
~
Preset data
Preset data
Number of presets
Preset data No.
~
+(18N+2)
+(18N+3)
+(18N+4)
+(18N+5)
+(18N+18)
~
+(18N+19)
~
(Undefined)
(Undefined)
Number of units
Preset data
Preset data
~
Preset data
Preset data
Preset data No.
Offset Contents (data format)
+0
+1
+2
+3
+4 to
+19
Number of send data words
(4 digits Hex)
Number of presets
(1 digit BCD)
Preset data No.
(1 digit BCD)
Data length
(2 digits BCD)
Preset data (ASCII)
+20 to
+91
Data
18N+2 (N is number of presets 1 to 5)
1 to 5
1 to 5
01 to 32
Combination of the following ASCII characters and up to 32 characters maximum:
30 (’0’) to 39 (’9’)
41 (’A’) to 5A (’Z’), 3F (’?’)
The area that is not used is undefined
Store repeatedly the contents of words with offsets +2 to +19 the same number of times as the number of presets (N)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
BCR Connection Confirmation (V500) (Sequence No. 358 (Hex
0166))
This sequence confirms whether the Bar Code Reader is connected correctly or not.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
628
V500/V520 Bar Code Reader Protocol
Appendix M
Log Data Clear (V500) (Sequence No. 359 (Hex 0167))
This sequence clears the log data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data Continuous Read (Scan) (V500) (Sequence No. 360 (Hex
0168))
This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data word allocation is similar to that of sequence No. 352 (Data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader still keeps reading. Execute sequence No. 351
(BCR read stop) to end the sequence.
Note The reception wait time is not set for this sequence.
Data Continuous Read (Interrupt) (V500) (Sequence No. 361
(Hex 0169))
This sequence performs the following operations repeatedly: Instruct the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation similar to that of sequence No. 352 (data read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Bar Code Reader keeps reading. Execute sequence No. 351 (BCR read stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
4.
Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the
CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications Unit.
BCR Initialize (V500) (Sequence No. 362 (Hex 016A))
This sequence clears the log data, confirms BCR connection and sets the BCR functions.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 354 (BCR Function Set).
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
629
V500/V520 Bar Code Reader Protocol
Appendix M
Data Continuous Read (Scan) (V520) (Sequence No. 363 (Hex
016B))
This sequence performs the following operations repeatedly: instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 352 (Data Read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR
Read Stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
Data Continuous Read (Interrupt) (V520) (Sequence No. 364
(Hex 016C))
This sequence performs the following operations repeatedly: Instructs the Bar Code Reader to start reading and receives the data read by the Bar Code Reader. The interrupt notification method is used for the receive data and the interrupt No. is 100.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 352 (Data Read).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the bar code still keeps reading. Execute sequence No. 351 (BCR
Read Stop) to end the sequence.
3.
The reception wait time is not set for this sequence.
4.
Sequences No. 361 and No. 364 (Continuous Data Read with Interrupt) are not supported by the
CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur is an attempt is made to execute either sequence with a Serial Communications Unit.
General-purpose Command 1 (Sequence No. 365 (Hex 016D))
This general-purpose command is used to send data with a specified data length, and receive back only ACK.
STX and ETX are automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+248
+249
Number of send data words
Send data byte length
Send data
Send data
Send data
Send data
~
630
V500/V520 Bar Code Reader Protocol
Appendix M
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Send data byte length
(4 digits Hex)
+2 to
+249
Send data (ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The byte length of the send data excluding STX and
ETX.
Inscribe send data up to 496 bytes (max.) by ASCII.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
General-purpose Command 2 (Sequence No. 366 (Hex 016E))
This general-purpose command is used to send data with a specified data length, and receive back ACK in addition to other receive data. The frame format of the receive data, however, has to contain STX and ETX.
STX and ETX are automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
+248
+249
Number of send data words
Send data byte length
Send data
Send data
Send data
Send data
~
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Send data byte length
(4 digits Hex)
+2 to
+128
Send data (ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The byte length of the send data excluding STX and
ETX.
Set send data up to 496 bytes (max.) by ASCII.
Receive Data Storage Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+126
+127
Number of receive data words
Receive data
Receive data
Receive data
Receive data
~
Offset Contents (data format)
+0
+1 to
+127
Number of receive data words (4 digits Hex)
Receive data (ASCII)
Data
0001 to 00FA (1 to 250 decimal)
Up to 498 bytes of ASCII receive data are stored.
Note Shown below is the receive data frame format. The reception data without ACK, STX, and ETX is stored.
Receive data (498 bytes max.)
ACK
STX ETX
631
Appendix N
3Z4L Laser Micrometer Protocol
The 3Z4L Laser Micrometer Protocol is used to make various settings or control remotely the Laser Micrometer connected to the Serial Communications Unit/Board via RS-232C cable.
Protocol Configuration
The configuration of the 3Z4L Laser Micrometer Protocol is shown below.
Sequence
No.
Communications sequence name
Function
400 (0190)
401 (0191)
402 (0192)
403 (0193)
404 (0194)
405 (0195)
3Z4L clear
Memory switch set mm unit set
E unit set
Calibration set
Calibration release
Resets errors, data, analog output, decision result and places the Laser
Micrometer into standby.
Sets memory switches and the area for the work position LED.
Sets the display unit to mm.
Sets the display unit to E.
Calibrates the Laser Micrometer.
Calibration setting release.
Releases the calibration of the Laser
Micrometer.
Switches the program number to a specified number.
Sets measurement conditions.
406 (0196) Program number set
(3000-series)
407 (0197) Measurement condition set
(3000-series)
408 (0198)
409 (0199)
410 (019A)
411 (019B)
Measurement condition release (3000-series)
Measurement condition list request (3000-series)
412 (019C) Continuous measurement start
(scan) (3000-series)
413 (019D) Continuous measurement start
(interrupt) (3000-series)
414 (019E)
415 (019F)
Single run measurement start
(3000-series)
Zero run measurement start
(3000-series)
Measurement termination
(3000-series)
Data request (3000-series)
Releases measurement conditions that have been set.
Requests the measurement conditions that have been set and other settings.
When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results.
If the sample measurement condition is zero, starts a zero run measurement.
Starts a continuous measurement.
The scan notification method is used for receive data.
Starts a continuous measurement.
The interrupt notification method is used for receive data.
Measurement termination (3000series)
Terminates a continuous measurement.
Requests display data in the idle measurement status or the latch data generated by the measurement command.
Ladder interface
Send word allocation
Receive word allocation
No No
Yes
No
No
Yes
No
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
No
Yes
Yes
No
*1
Yes
2
Notes
633
3Z4L Laser Micrometer Protocol
Appendix N
Sequence
No.
Communications sequence name
Function
416 (01A0) Statistic processing execution
(3000-series)
417 (01A1) Statistic processing non-execution (3000-series)
418 (01A2) All statistic memory clear
(3000-series)
419 (01A3) Statistic memory clear
(3000-series)
420 (01A4) Statistic result request
(3000-series)
421 (01A5) Memory switch set 1
(3000-series)
422 (01A6) Memory switch set 2
(3000-series)
423 (01A7) Simple AVG times set
(3000-series)
Lights the statistic processing LED and processes the statistics.
Turns OFF the statistic processing
LED. Statistics are not processed.
Clears statistic processing memories of all programs.
Clears statistic processing memories of program under display.
Requests statistic processing result.
Sets memory switches.
Sets memory switches.
424 (01A8)
425 (01A9)
426 (01AA)
427 (01AB)
430 (01AE)
AVG move interval set
(3000-series)
AVG move (H) times set
(3000-series)
AVG move (L) times set
(3000-series)
Automatic detection set
(3000-series)
428 (01AC) Automatic detection release
(3000-series)
429 (01AD) Automatic detection list request (3000-series)
3Z4L initialize (3000-series)
Taking the simple average as the averaging method, sets the averaging times per measurement interval 4.
Taking the average move as the averaging method, sets the measurement interval number.
Taking the average move and highspeed data output as the averaging method, sets the averaging times per measurement interval 4.
Taking the average move and lowspeed data output as the averaging method, sets the averaging times per measurement interval 4.
Sets work automatic detection function.
Releases the settings of work automatic detection function.
Requests the settings of work automatic detection function.
Clears the 3Z4L, sets the mm unit, sets the memory unit, does not processes statistics, and clears all statistic memory.
Sets measurement conditions.
431 (01AF) Measurement condition set
(4000-series)
432 (01B0)
433 (01B1)
434 (01B2)
Measurement condition release (4000-series)
Measurement condition list request (4000-series)
Single run measurement start
(4000-series)
Releases measurement conditions that have been set.
Requests the measurement conditions that have been set and other settings.
When the sample measurement condition is from 1 to 999, performs a single run measurement and requests the measurement results.
435 (01B3) Deflection measurement start
(4000-series)
436 (01B4) Continuous measurement start
(scan) (4000-series)
Starts a deflection measurement.
Starts a continuous measurement.
The scan notification method is used for receive data.
Ladder interface
Send word allocation
No
Receive word allocation
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
No
Yes
No
No
No
Yes
Yes
No
Yes
Notes
634
3Z4L Laser Micrometer Protocol
Appendix N
Sequence
No.
Communications sequence name
Function
437 (01B5) Continuous measurement start
(interrupt) (4000-series)
Starts a continuous measurement.
The interrupt notification method is used for receive data.
Terminates continuous measurement.
438 (01B6) Measurement termination
(4000-series)
439 (01B7) Data request (4000-series)
440 (01B8)
441 (01B9)
Forced positive zero
(4000-series)
Forced negative zero
(4000-series)
442 (01BA) Forced zero release
(4000-series)
443 (01BB) 3Z4L initialize (4000-series)
Requests measurement data in the idle measurement status or the latch data generated by the measurement command.
Sets the forced zero direction to positive (+).
Sets the forced zero direction to negative (–).
Releases the forced zero direction.
Clears the 3Z4L, sets the mm unit, and clears the memory unit settings.
444 (01BC) General-purpose command 1 Used to send data of a specified data length, and receive only OK as the receive data.
445 (01BD) General-purpose command 2 Used to send data of a specified data length, and receive data other than
OK.
446 (01BE) High calibration set
447 (01BF) Low calibration set
Sets the Laser Micrometer’s high calibration.
Sets the Laser Micrometer’s low calibration.
Ladder interface
Send word allocation
No
Receive word allocation
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
*1
Yes
No
No
No
No
No
Yes
No
No
Notes
2
*1 Depends on the measurement contents.
Note 1.
Sequences with interrupt notification are not supported by the CS1W-SCU21-V1 and CJ1W-SCU21/
41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
3.
The hexadecimal equivalents of sequences numbers are given in parentheses.
635
3Z4L Laser Micrometer Protocol
Connections
The connections for the 3Z4L Laser Micrometer Protocol are shown below.
RS-232C Connection
Sensor
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-232C Port
RS-232C
Controller
Appendix N
Signal cable
Serial Communications Unit/Board:
D-sub 9 pin (female)
Signal name
Pin No.
FG
SD
RD
RTS
CTS
DSR
DTR
SG
1
2
5
7
8
9
3
4
Controller: D-sub
25 pin (female)
Pin No.
Signal name
1
2
3
4
5
6
7
20
FG
TXD
RXD
RTS
CTS
DSR
SG
DTR
DIP Switch Settings
Shown below are the settings of 3Z4L-3000, 3Z4L-4000-series DIP switches required to use the system protocol sequences.
3Z4L-3000 Series
• DIP Switch 1
3
4
1
2
5
6
No.
Baud rate
Setting
Handshaking procedure
RS-232C interface use selection
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Status
• DIP Switch 2
3
4
5
1
2
6
7
No.
8
Setting
Selection for measurement section
Setting of minimum read value
Setting of transparent body measurement function
Setting of simultaneous measurement function
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Status
Set these settings according to the sensor connected.
Set these settings for
4 digits in the decimal portion.
636
3Z4L Laser Micrometer Protocol
• DIP Switch 3
3
4
5
1
2
No.
6
Setting
Setting of measurement function by 2 measurement instruments
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF Error data exclusion function
Multistep selection function
ON/OFF
Status
3Z4L-4000 Series
• DIP Switch 1
3
4
5
1
2
6
7
8
No.
Setting
Baud rate
Hand-shake procedure
Delimiter
RS-232C interface use selection
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
Status
• DIP Switch 2
3
4
5
1
2
6
7
8
No.
Setting
Selection for measurement section
ON/OFF
ON/OFF
ON/OFF
Setting of minimum read value
ON/OFF
ON/OFF
Display unit
ON/OFF
ON/OFF
External command setting ON/OFF
Status
Appendix N
This protocol does not support the error data exclusion function
Set these settings according to the sensor connected.
Set these settings for
4 digits in the decimal portion.
637
3Z4L Laser Micrometer Protocol
Appendix N
Delimiter Control Code Setting
3Z4L-4000 Series
The delimiter control codes must be set on DIP switch SW1 for the 3Z4L-4000 Series. Turn off pins 4 and 5, set the delimiter codes to CR+LF, and set the delimiter code control setting in the sequence to CR+LF. See the setting for CR+LF in the following diagram.
1 2 3 4 5 6 7 8
Turn OFF
Turn OFF (to use a general-purpose interface)
Turn ON (to use a general-purpose interface)
Delimiter Setting
Delimiter
CR+LF
Pin
Pin 4
OFF
Pin 5
OFF
CR
ON
OFF
LF
OFF
ON
Handshaking
ON: Control (recognize DRT input)
OFF: 3-wire method (non-protocol)
Baud Rate
Pin
Baud rate
1200 2400 4800 9600
Pin 1
Pin 2
OFF
ON OFF
OFF
OFF
ON
ON
ON
638
3Z4L Laser Micrometer Protocol
Appendix N
3Z4L-3000 Series
The delimiter control code does not need to be set on the DIP switch for the 3Z4L-3000 Series. Set the delimiter control codes in the sequence to CR+LF for the send code and to CR or CR+LF for the receive code. See the settings in the following diagram.
1 2 3 4 5 6
Turn OFF
Turn OFF (to use a general-purpose interface)
Turn ON (to use a general-purpose interface)
Handshaking
ON: Control (recognize DRT input)
OFF: 3-wire method (non-protocol)
Baud Rate
Pin
Baud rate
1200 2400
4800
9600
Pin 1
OFF
ON OFF
ON
Pin 2 OFF
OFF ON
ON
The High-speed 3Z4L-3000-series Meters must have the delimiter control codes set using the memory switches. Set both the send and receive codes to CR+LF.
Protocol Configuration
The configuration of the 3Z4L Laser Micrometer Protocol for the 5000 and 6000 Series is shown below.
Sequence
No.
400 (0190)
401 (0191)
402 (0192)
403 (0193)
404 (0194)
405 (0195)
406 (0196)
Communications sequence name
3Z4L clear
Memory switch set mm unit set
E unit set
Calibration set
Calibration release
Program number set (3000-series)
407 (0197) Measurement condition set (3000-series)
408 (0198)
409 (0199)
Measurement condition release (3000-series)
Measurement condition list request (3000-series)
410 (019A) Single run measurement start (3000-series)
411 (019B) Zero run measurement start (3000-series)
412 (019C) Continuous measurement start (scan) (3000-series)
413 (019D) Continuous measurement start (interrupt) (3000-series)
414 (019E) Measurement termination (3000-series)
415 (019F) Data request (3000-series)
Yes
No
*1
Yes
Yes
No
Yes
No
*1
No
No
No
No
No
No
No
No
Yes
5000 Series
Operation
6000 Series
Yes
No
*1
Yes
Yes
No
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
639
3Z4L Laser Micrometer Protocol
Appendix N
Sequence
No.
Communications sequence name
416 (01A0) Statistic processing execution (3000-series)
417 (01A1) Statistic processing non-execution (3000-series)
418 (01A2) All statistic memory clear (3000-series)
419 (01A3) Statistic memory clear (3000-series)
420 (01A4) Statistic result request (3000-series)
421 (01A5) Memory switch set 1 (3000-series)
422 (01A6) Memory switch set 2 (3000-series)
423 (01A7) Simple AVG times set (3000-series)
424 (01A8) AVG move interval set (3000-series)
425 (01A9) AVG move (H) times set (3000-series)
426 (01AA) AVG move (L) times set (3000-series)
427 (01AB) Automatic detection set (3000-series)
428 (01AC) Automatic detection release (3000-series)
429 (01AD) Automatic detection list request (3000-series)
430 (01AE) 3Z4L initialize (3000-series)
431 (01AF) Measurement condition set (4000-series)
432 (01B0) Measurement condition release (4000-series)
433 (01B1) Measurement condition list request (4000-series)
434 (01B2) Single run measurement start (4000-series)
435 (01B3) Deflection measurement start (4000-series)
436 (01B4) Continuous measurement start (scan) (4000-series)
437 (01B5) Continuous measurement start (interrupt) (4000-series)
438 (01B6) Measurement termination (4000-series)
439 (01B7) Data request (4000-series)
440 (01B8) Forced positive zero (4000-series)
441 (01B9) Forced negative zero (4000-series)
442 (01BA) Forced zero release (4000-series)
443 (01BB) 3Z4L initialize (4000-series)
444 (01BC) General-purpose command 1
445 (01BD) General-purpose command 2
446 (01BE) High calibration set
447 (01BF) Low calibration set
No
*1
No
*1
Yes
Yes
Yes
Yes*
2
No
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
*3
Yes
Yes
No
No
Yes
*3
No
No
No
Yes
Yes
*4
Yes
5000 Series
Operation
6000 Series
Yes
Yes
Yes
Yes
No
No
*1
No
*1
Yes
Yes
Yes
No
No
Yes
Yes
Yes
*3
No
No
No
No
No
Yes
Yes
Yes
*3
Yes
Yes
No
No
No
No
No
No
Yes
Note 1.
*Normal responses will be returned for these sequences for 5000-series and 6000-series Laser Micrometers, but no processing will be performed.
2.
*This sequence will be processed the same as sequence No. 425 AVG move (H) times set for 5000series Laser Micrometers.
3.
*Memory switch settings will be ignored for these sequences for 5000-series and 6000-series Laser
Micrometers.
4.
*This sequence will be processed the same as sequence No. 411 Zero run measurement start for
5000-series Laser Micrometers.
640
3Z4L Laser Micrometer Protocol
Appendix N
3Z4L Clear (Sequence No. 400 (Hex 0190))
This sequence resets errors, data, analog output, and decision result, and puts the Laser Micrometer into standby.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Memory Switch Set (Sequence No. 401 (Hex 0191))
This sequence sets memory switches and the area for the work position LED.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
Number of send data words
W X Y Z
(Undefined) V
Offset
+0
+1
Contents
(data format)
Number of send data words (4 digits Hex) w (1 digit BCD)
+2 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD) v (1 digit BCD)
3000-series
0003 (fixed)
Data
4000-series
0003 (fixed)
Using buzzer sound: 0 to 3
Automatic latch release time:
0 to 9
Using print timer, the setting for simultaneous measurement: 0 to 3 (high-speed), 0 to 1 (other)
Display of the comma for 1/
1000s digit, number of display digits: 0 to 5 (highspeed), 0 to 3 (other)
Measurement interval 4: 0 to
6
Number of digits for extinguishing indicator: 0 to 2
I/O IF RUN Input: 0 or 1
Display of Err–0: 0 or 1
Averaging method: 0 to 2
(high-speed), 0 (other)
Use of comma: 0 or 1
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
mm Unit Set (Sequence No. 402 (Hex 0192))
This sequence sets the display unit to mm.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
E Unit Set (Sequence No. 403 (Hex 0193))
This sequence sets the display unit to E.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
641
3Z4L Laser Micrometer Protocol
Appendix N
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
Calibration Set (Sequence No. 404 (Hex 0194))
This sequence calibrates the Laser Micrometer.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
Number of send data words
Decimal portion
(Undefined)
Sign
Decimal integer portion
(Undefined)
(Undefined)
Decimal portion
(Decimal integer portion)
Sign (Undefined)
High calibration gauge dimension
Low calibration gauge dimension
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
HC gauge dimension (Decimal portion)
(4 digits BCD)
0007 (fixed)
0000 to 9999
Data
Example –123.4567
+1
+2
+3
4 5 6 7
0 1 2 3
2 D 0 0
+2
+3
HC gauge dimension (integer portion)
(3 digits BCD)
HC gauge dimension (Sign)
(ASCII 1 character)
000 to 999 if +: 20(‘ ’) if –: 2D(‘–’)
+4 to +6 LC gauge dimensions
Example -123.4567
+1
+2
+3
4 5 6 7
0 1 2 3
2 D 0 0
Same as HC gauge dimensions
Note 1.
Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser
Micrometer. If this sequence (No. 404) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged.
2.
The HC gauge dimension and LC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Calibration Release (Sequence No. 405 (Hex 0195))
This sequence releases the calibration of the Laser Micrometer.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence releases both the high and low calibration.
642
3Z4L Laser Micrometer Protocol
Appendix N
Program Number Set (3000-series) (Sequence No. 406 (Hex
0196))
This sequence switches the program number to a specified number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined)
Program number (1 digit BCD)
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Program number (1 digit BCD)
0002 (fixed)
0 to 9
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Retry processing is not performed for this sequence.
Measurement Condition Set (3000-series) (Sequence No. 407
(Hex 0197))
This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags.
Send Data Word Allocation (3rd Operand of PMCR(260))
643
3Z4L Laser Micrometer Protocol
First word of send data
+0
+1
+2
+3
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
+18
+19
+20
+21
+4
+5
+6
+22
+23
+24
+25
+26
+27
+28
+29
Number of send data words
(Unused)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign (Undefined)
Appendix N
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
644
3Z4L Laser Micrometer Protocol
Appendix N
+30
+31
+32
+33
+34
+35
+36
+37
+38
+39
+40
+41
+42
+43
+44
+45
+46
+47
+48
+49
+50
+51
+52
+53
Decimal portion
(Undefined)
Sign
(Undefined)
Integer portion
(Undefined)
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
(Undefined) Schedule output timer
(Undefined) Sample measurement pulse
0
0
0
0
0
0
0
0
(Unused)
(Unused)
(Undefined)
Reference value (REF)
Analog output scale number (SCL)
Offset classification (OF)
Offset value
Data output conditions (PR)
(PRT)
(SMP)
Sample measurement classification
Setting Yes/No flags
Offset Contents (data format)
+9 to
+11
+12 to
+14
+15 to
+17
+18 to
+20
+21 to
+23
+24 to
+26
+0 Number of send data words
(4 digits Hex)
Unused +1
+2 to +4 Segment number
(ASCII 6 characters)
+5 Measurement interval number (1 digit BCD)
+6
+7
Lower limit value (decimal portion)
(4 digits BCD)
Lower limit value (Integer portion)
(3 digits BCD)
+8 Lower limit value (Sign)
(ASCII 1 character)
Upper limit value
+27 to
+29
+30 to
+32
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value
0054 (fixed)
1 to 4
0000 to 9999
000 to 999
Data
Undefined
Combination of 31(‘1’) to 36(‘6’), 20(‘ ’) if +: 20(‘ ’) if –: 2D(‘–’)
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Example –123.4567
+6
+7
+8
4 5 6 7
0 1 2 3
2 D 0 0
645
3Z4L Laser Micrometer Protocol
Appendix N
Offset Contents (data format)
+33
+34 to
+35
+36 to
+38
+39 0 to 6
Data
Analog output scale number
(1 digit BCD)
Offset classification (ASCII 3 characters)
Offset value
1 to 3
4F4620 (“OF”), 4F4D20 (“OM”)
Same as lower limit values
+40
+41
+42 to
+43
Data output conditions
(1 digit BCD)
Scheduled output timer
(3 digits BCD)
Sample measurement pulse
(3 digits BCD)
Sample measurement classification
(ASCII 3 characters)
Unused
000 to 999
000 to 999
415647 (“AVG”), 4D4158 (“MAX”)
4D494E (“MIN”), 524E47 (“RNG”)
Undefined +44 to
+45
+46
+47
+48
+49
+50
+51
+52
+53
Yes/No for segment setting
(1 digit BCD)
Don’t set: 0
Yes/No for measurement interval number setting
(1 digit BCD)
Yes/No for upper/lower limit value setting
(1 digit BCD)
Yes/No for multistep selection limit value
(1 digit BCD)
Yes/No for reference setting
(1 digit BCD)
Don’t set: 0
Don’t set: 0
Don’t set: 0
Yes/No for offset value setting (1 digit BCD)
Don’t set: 0
Set: 1 (OF or OM)
Don’t set: 0
Yes/No for data output condition setting
(1 digit BCD)
Yes/No for sample measurement pulse setting
(1 digit BCD)
Don’t set: 0
Set: 1 (SMP, MAX or MIN or RNG or AVG)
Don’t set: 0
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
This sequence cannot be used to set the error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
2.
The following settings must be made together with this sequence; they cannot be set separately.
Lower limit, upper limit
Multistep selection limit
Reference value, analog output scale number
Data output conditions, scheduled print timer
3.
The limit value, reference value, and offset value can be set to 3 digits for the integer portion and to
4 digits for the decimal portion.
646
3Z4L Laser Micrometer Protocol
Appendix N
Measurement Condition Release (3000-series)
(Sequence No. 408 (Hex 0198))
This sequence releases the measurement conditions that have been set.
Send Data Word Allocation (3rd Operand of PMCR(260))
Send data word allocation is similar to that of sequence No. 407 (Measurement Condition Set). However, only the setting Yes/No flags at +46 to +53 from the send data leading word can be used.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
The following conditions are used when the measurement conditions are released: Segment becomes 1, measurement interval becomes 1, the number of sample measurement pulses becomes 1.
2.
The following conditions cannot be released with this sequence: error lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
3.
The following settings cannot be released separately using this sequence.
Lower limit, Upper limit
Multistep selection limit
Reference value, analog output scale number
Data output conditions, scheduled print timer
Measurement Condition List Request (3000-series)
(Sequence No. 409 (Hex 0199))
This sequence requests the measurement condition settings that have been set and other settings.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
647
3Z4L Laser Micrometer Protocol
Appendix N
Receive Data Word Allocation (4th Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+17
+18
+19
+20
+21
+12
+13
+14
+15
+16
+4
+5
+6
+7
+8
+9
+10
+11
+22
+23
+24
+25
+26
+27
+28
+29
Number of receive data words
(Undefined)
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
Sign
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
(Undefined)
Sign
(Undefined)
Sign
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
(Undefined)
Integer portion
(Undefined)
+30
+31
+32
+33
+34
+35
+36
+37
+38
+39
+40
+41
+42
+43
+44
+45
(Undefined)
Sign
(Undefined)
(Undefined)
(Undefined)
Decimal portion
Integer portion
(Undefined)
Scheduled output timer
Sample measurement pulse
(Undefined)
(Undefined)
Program number (P)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value (REF)
Analog output scale number (SCL)
Offset classification (OF)
Offset value (LH)
Data output condition (PR)
(PRT)
(SMP)
Sample measurement classification
Statistical processing calculation classification
648
3Z4L Laser Micrometer Protocol
Appendix N
Offset Contents (data format)
+0 Number of receive data words (4 digits Hex)
+18 to
+20
+21 to
+23
+24 to
+26
+27 to
+29
+30 to
+32
+33
+1
+2 to +4 Segment number
(ASCII 6 characters)
+5 Measurement interval number (1 digit BCD)
+6 Lower limit value (Decimal portion)
(4 digits BCD)
+7
Program number
(1 digit BCD)
Lower limit value (Integer portion)
(3 digits BCD)
+8 Lower limit value (Sign)
(BIN)
Upper limit value +9 to
+11
+12 to
+14
+15 to
+17
Multistep selection limit value (L1)
Multistep selection limit value (L2)
Multistep selection limit value (L3)
Multistep selection limit value (L4)
Multistep selection limit value (L5)
Multistep selection limit value (L6)
Reference value
+34 to
+35
+36 to
+38
+39
Analog output scale number
(1 digit BCD)
Offset classification (ASCII 3 characters)
Offset value
+40
+41
+42 to
+43
+44 to
+45
Data output condition
(1 digit BCD)
Scheduled output timer
(3 digits BCD)
Sample measurement pulse
(3 digits BCD)
Sample measurement classification
(ASCII 3 characters)
Statistical processing calculation classification (ASCII 3 characters)
Data
002E (0046 decimal) (fixed)
0 to 9
Combination of 31(‘1’) to 36(‘6’), 20(‘ ’)
1 to 4
0000 to 9999
000 to 999
If +: 0
If – : F
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
Same as lower limit values
1 to 3
Same as lower limit values
0 to 6
000 to 999
000 to 999
Example –123.4567
+6
+7
+8
4F4620 (“OF”), 4F4D20 (“OM”)
415647 (“AVG”), 4D4158 (“MAX”)
4D494E (“MIN”), 524E47 (“RNG”)
535420 (“ST”), 4E5354 (“NST”)
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence cannot be used to request the lower limit (EL), error upper limit (EH), error exclusion counter (CNT) of the error data exclusion function (centerless grinder function).
649
3Z4L Laser Micrometer Protocol
Appendix N
Single Run Measurement Start (3000-series) (Sequence No. 410
(Hex 019A))
When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data stor age words
+3
+4
+5
+6
+7
+8
+0
+1
+2
Number of receive data words
(Undefined)
Decision result
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
Program number
Measurement value
Deviation value
Offset Contents (data format)
+0
+1
+2
Number of receive data words (4 digit Hex)
Program number
(1 digit BCD)
Decision result
(ASCII 2 characters)
Data
With no reference setting: 0006
With reference setting: 0009
0 to 9
+3
+4
+5
Measurement value (decimal portion)
(4 digits BCD)
Measurement value (integer portion) (3 digits BCD)
Measurement value (Sign)
(BIN)
000 to 999
+6 to +8 Deviation value
With no limit setting: 0000
With limit setting: 2B4E (“+N”), 4F4B (“OK”),
2D4E (“–N”)
0000 to 9999
Example –123.4567
+3
+4
+5
4 5 6 7
0 1 2 3
F 0 0 0
If +: 0
If –: F
Same as measurement value
*The deviation will be stored in this area only when reference setting is made.
Zero Run Measurement Start (3000-series) (Sequence No. 411
(Hex 019B))
If the sample measurement condition is zero, a zero run measurement is started.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note The zero run measurement keeps measuring until sequence No. 414 (Measurement Termination) is executed.
650
3Z4L Laser Micrometer Protocol
Appendix N
Continuous Measurement Start (Scan) (3000-series)
(Sequence No. 412 (Hex 019C))
A continuous measurement is started. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
414 (Measurement Termination) to end the sequence.
Continuous Measurement Start (Interrupt) (3000-series)
(Sequence No. 413 (Hex 019D))
A continuous measurement is started. The interrupt notification method is used for the receive data and the interrupt No. is 101.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
414 (Measurement Termination) to end the sequence.
3.
Sequences No. 413 and No. 437 (Continuous Measurement Start with Interrupt) not supported by the
CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
Measurement Termination (3000-series) (Sequence No. 414 (Hex
019E))
This sequence terminates a continuous measurement.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
For continuous measurement: Not available
For Zero Run Measurement
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Note This sequence may be aborted it is executed during continuous measurements. Measurements will be terminated even if the sequence is aborted. The sequence will be aborted if executed when the Laser
Micrometer is sending measurement results. The chances that the sequence will be aborted are higher if the scheduled data output value is set to a lower value.
651
3Z4L Laser Micrometer Protocol
Appendix N
Data Request (3000-series) (Sequence No. 415 (Hex 019F))
This sequence requests display data in the idle measurement status or the latch data generated by the measurement command.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 410 (Single Run Measurement Start).
Statistic Processing Execution (3000-series) (Sequence No. 416
(Hex 01A0))
This sequence lights the statistic processing LED and implements the statistic processing.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Statistic Processing Non-execution (3000-series)
(Sequence No. 417 (Hex 01A1))
This sequence turns the statistic processing LED off and does not carry out the statistic processing.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
All Statistic Memory Clear (3000-series) (Sequence No. 418 (Hex
01A2))
This sequence clears statistic processing memories of all programs.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Statistic Processing Memory Clear (3000-series)
(Sequence No. 419 (Hex 01A3))
This sequence clears statistic processing memories of the program under display.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
652
3Z4L Laser Micrometer Protocol
Appendix N
Statistic Result Request (3000-series) (Sequence No. 420 (Hex
01A4))
This sequence requests the statistic processing results.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
Number of receive data words
(Undefined)
+10
+11
+12
+13
+14
+15
+16
+17
+18
+3
+4
+5
+6
+7
+8
+9
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined) Integer portion
Sign
(Undefined)
Sign
(Undefined)
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Program number (P)
Number of statistic data (N)
Average value (AVG)
Maximum value (MAX)
Minimum value (MIN)
Range (R)
Standard deviation (SD)
Offset
Contents
(data format)
Data
+0
+1
+6
Number of receive data words (4 digits Hex)
Program number
(1 digit BCD)
+2 to +3 Number of statistic data
(6 digits BCD)
+4 Average value (decimal portion) (4 digits BCD)
+5
0013 (0019 decimal) (fixed)
0 to 9
000000 to 999999
0000 to 9999
Average value (integer portion) (4 digits BCD)
000 to 999
Average value (Sign) (BIN) If +: 0
If –: F
Example –123.4567
+4
+5
+6
4 5 6 7
0 1 2 3
F 0 0 0
+7 to +9 Maximum value Same as average value
+10 to
+12
+13 to
+15
+16 to
+18
Minimum value
Range
Standard deviation
Same as average value
Same as average value
Same as average value
Note The number of digits of the Decimal portion is fixed to 4 digits. If a deviation calculation results in a value with 5 decimal places, it will be stored with one digit overflowing into the integer portion.
Examples: The value -0.1234 is stored as follows:
Area of decimal portion: 1234; Area of integer portion: 0000; Sign area: F000
653
3Z4L Laser Micrometer Protocol
Appendix N
The value -0.12345 is stored as follows:
Area of decimal portion: 2345; Area of integer portion: 0001; Sign area: F000
Memory Switch Set 1 (3000-series, High-speed Type)
(Sequence No. 421 (Hex 01A5))
This sequence sets memory switches.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
W X
(Undefined)
Y Z
V
Offset
+0
Contents
(data format)
Number of send data words
(4 digits Hex) w (1 digits BCD)
0003 (fixed)
Data
+1
+2 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD) v (1 digit BCD)
0: For single run or zero run measurement start displaying ‘---.’
1: For single run or zero run measurement start displaying the previous measured value
0: Perform single run measurement to the RUN signal of I/O IF
1: Repeat measurement while the RUN signal of I/O IF is input
*0: RS-232C Delimiter CR+LF
1: RS-232C Delimiter CR
2: RS-232C Delimiter LF
0: RS-232C no parity check
1: RS-232C odd parity check
2: RS-232C even parity check
0: Displaying ‘Err-0’
1: Displaying ‘0’
Note Settings marked with asterisks are required for this protocol.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned
ON.
2.
The setting (y, z) of RS-232C takes effect when the power supply is turned back on.
654
3Z4L Laser Micrometer Protocol
Appendix N
Memory Switch Set 2 (3000-series, High-speed Type)
(Sequence No. 422 (Hex 01A6))
This sequence sets memory switches.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
Number of send data words
W X Y Z
(Undefined) V
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex) w (1 digit BCD)
0003 (fixed)
Data
0: Work automatic detection is not performed
1: Work automatic detection is performed
Diameter detection method (1 scan)
2: Work automatic detection is performed
Diameter detection method (8 scan)
3: Work automatic detection is performed
Position detection method (1 scan)
+2 x (1 digit BCD) y (1 digit BCD) z (1 digit BCD) v (1 digit BCD)
For expansion
0 (fixed)
For expansion
0 (fixed)
For expansion
0 (fixed)
*0: Error data exclusion function is not used
1: Error data exclusion function is used
Note Settings marked with asterisks are required for this protocol.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Memory switches cannot be set when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Simple AVG Times Set (3000-series, High-speed Type)
(Sequence No. 423 (Hex 01A7))
This sequence uses the simple average as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of averaging times
(4 digits BCD)
0002 (fixed)
1 to 2048
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
655
3Z4L Laser Micrometer Protocol
Appendix N
AVG Move Interval Set (3000-series, High-speed Type)
(Sequence No. 424 (Hex 01A8))
This sequence uses the average move as the averaging method and sets the measurement interval number.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
(Undefined) Measurement interval number
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Measurement interval number
(1 digit BCD)
0002 (fixed)
1 to 4
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
AVG Move (H) Times Set (3000-series, High-speed Type)
(Sequence No. 425 (Hex 01A9))
This sequence uses the average move and high-speed data output as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of averaging times
(4 digits BCD)
0002 (fixed)
Data
16 to 2048
(32 to 2048 for 5000/6000 Series)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
AVG Move (L) Times Set (3000-series, High-speed Type)
(Sequence No. 426 (Hex 01AA))
This sequence uses the average move and low-speed data output as the averaging method and sets the averaging times per measurement interval 4.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
Number of send data words
Number of averaging times
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Number of averaging times
(4 digits BCD)
0002 (fixed)
32 to 2048
Data
656
3Z4L Laser Micrometer Protocol
Appendix N
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
2.
This sequence will be processed the same as sequence No. 425 AVG move (H) times set for 5000series Laser Micrometers.
Automatic Detection Set (3000-series, High-speed Type)
(Sequence No. 427 (Hex 01AB))
This sequence sets the work automatic detection function.
Send Data Word Allocation (3rd Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
Number of send data words
(Undefined)
The number of measuring times
(Undefined)
Invalid time
Decimal portion
Integer portion
Sign
(Undefined)
(Undefined)
Decimal portion
Integer portion
Sign
(Undefined)
Detection lower limit
Detection upper limit
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of measurements
(3 digits BCD)
Invalid time (4 digits BCD) +2
+3
+4
+5
Detection lower limit (decimal portion)
(4 digits BCD)
Detection lower limit (integer portion)
(3 digits BCD)
Detection lower limit (Sign)
(ASCII 1 character)
+6 to +8 Detection upper limit
0009 (fixed)
001 to 999
0001 to 9999
0000 to 9999
Data
Example –123.4567
+3
000 to 999
+4
If +: 20 (‘ ’)
If –: 2D (‘–’)
Same as detection lower limit
+5
4 5 6 7
0 1 2 3
2 D 0 0
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
2.
The detection lower and upper limit must be set with 3 digits for the integer portion and 4 digits for the decimal portion.
Automatic Detection Release (3000-series, High-speed Type)
(Sequence No. 428 (Hex 01AC))
This sequence releases the setting of work automatic detection function.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
657
3Z4L Laser Micrometer Protocol
Appendix N
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
Automatic Detection List Request (3000-series, High-speed
Type) (Sequence No. 429 (Hex 01AD))
This sequence requests the settings of work automatic detection function.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+3
+4
+5
+6
+7
+8
+0
+1
+2
Number of receive data words
(Undefined) The number of measuring times
(Undefined)
Invalid time
Decimal portion
Integer portion
Sign
(Undefined)
Sign
(Undefined)
Decimal portion
Integer portion
(Undefined)
Detection lower limit
Detection upper limit
Offset Contents (data format) Data
+0
+1
+2
Number of receive data words (4 digits Hex)
The number of measuring times
(3 digits BCD)
Invalid time
(4 digits BCD)
+3 Detection lower limit (decimal portion)
(4 digits BCD)
+4
+5
Detection lower limit (integer portion)
(3 digits BCD)
Detection lower limit (Sign)
(BIN)
+6 to +8 Detection upper limit
0009 (fixed)
000 to 999
0001 to 9999
0000 to 9999
000 to 999
Example –123.4567
If +: 0
If –: F
Same as detection lower limit
+3
+4
+5
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence cannot be used when DIP switch SW3, pin 5 of the Laser Micrometer is not turned ON.
3Z4L Initialize (3000-series) (Sequence No. 430 (Hex 01AE))
This sequence clears the 3Z4L, sets the mm unit, sets memory switches, does not process statistics, and clears the statistic memory.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Memory switch settings will be ignored for this sequence for 5000-series and 6000-series Laser
Micrometers.
658
3Z4L Laser Micrometer Protocol
Appendix N
Measurement Condition Set (4000-series) (Sequence No. 431
(Hex 01AF))
This sequence sets measurement conditions. Conditions to be set can be selected by setting Yes/No flags.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+12
+13
+14
+15
+16
+8
+9
+10
+11
+0
+1
+2
+3
+4
+5
+6
+7
+17
+18
+19
+20
+21
+22
+23
+24
Number of send data words
(Undefined)
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
Decimal portion
(Undefined)
Sign
Integer portion
(Undefined)
(Undefined)
(Unused)
(Unused)
(Unused)
(Undefined)
(Undefined) Data output timer (BCD 3 digits)
(Undefined)
0
0
0
0
0
0
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Reference value (REF)
Analog output scale number (SCL)
Data output conditions (PR)
(PRT)
Number of seconds for latch timer (RLT)
Setting Yes/No flags
659
3Z4L Laser Micrometer Protocol
Appendix N
Offset Contents (data format)
+0
+1
+2
+3
Number of send data words
(4 digits Hex)
Segment number
(1 digit BCD)
Measurement interval number (1 digit BCD)
Lower limit value (Decimal portion)
(4 digits BCD)
+4
+5
Lower limit value (integer portion) (3 digits BCD)
Lower limit value (Sign)
(ASCII 1 character)
+6 to +8 Upper limit value
Data
0019 (0025 decimal) (fixed)
1 to 5
1 to 7
0000 to 9999
000 to 999
If +: 20 (‘ ’)
If –: 2D (‘–’)
Same as lower limit value
Example –123.4567
+3
+4
+5
4 5 6 7
0 1 2 3
2 D 0 0
+9 to
+11
+12
+17
+18
+19
+20
+21
+22
+23
+24
Reference value Same as lower limit value
+13 to
+15
+16
Analog output scale number
(1 digit BCD)
Unused
0 to 3
Data output conditions
(1 digit BCD)
Data output timer value
(3 digits BCD)
Number of seconds for latch timer
(2 digits BCD)
Yes/No for segment setting
(1 digit BCD)
0 to 6
000 to 999
00 to 99
Set: 1(SG)
Don’t set: 0
Yes/No for measurement interval number setting
(1 digit BCD)
Yes/No for upper/lower limit value setting
(1 digit BCD)
Yes/No for reference setting
(1 digit BCD)
Set: 1(M)
Don’t set: 0
Don’t set: 0
Don’t set: 0
Yes/No for data output condition setting
(1 digit BCD)
Yes/No for latch timer setting
(1 digit BCD)
Don’t set: 0
Set: 1(RLT)
Don’t set: 0
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
The following settings must be made together with this sequence; they cannot be set separately.
Lower limit, upper limit
Reference value, data output timer
Data output conditions, scheduled print timer
2.
The limit value and reference value can be set to 3 digits for the integer portion and to 4 digits for the decimal portion.
660
3Z4L Laser Micrometer Protocol
Appendix N
Measurement Condition Release (4000-series)
(Sequence No. 432 (Hex 01B0))
This sequence clears the measurement conditions that have been set.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 431 (Measurement Condition Setting). However, only the setting Yes/No flags at +19 to +24 from the send data leading word can be used.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
The following conditions are used when the measurement conditions are released: Segment becomes 1 and the measurement interval becomes 1.
2.
The following settings cannot be cleared separately using this sequence. They all must be cleared at the same time.
Lower limit, Upper limit
Data output conditions, Scheduled print timer
The scale (SCL) and data output timer (PRT) cannot be cleared.
3.
This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned
ON.
Measurement Condition List Request (4000-series)
(Sequence No. 433 (Hex 01B1))
This sequence requests the measurement condition settings that have been set and other settings.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+14
+15
+16
+17
+18
+8
+9
+10
+11
+12
+13
+0
+1
+2
+3
+4
+5
+6
+7
Number of receive data words
(Undefined)
(Undefined)
(Undefined)
Sign
Decimal portion
Integer portion
(Undefined)
(Undefined)
Decimal portion
Integer portion
(Undefined)
Sign
Decimal portion
(Undefined)
Sign
(Undefined)
Integer portion
(Undefined)
Segment number (SG)
Measurement interval number (M)
Lower limit value (LL)
Upper limit value (LH)
Reference value (REF)
Analog output scale number (SCL)
Forced zero number (ZERO+)
(Undefined)
(Undefined)
(Undefined)
Data output timer (BCD 3 digits)
(Undefined)
Data output condition (PR)
(PRT)
Number of seconds for latch timer (RLT)
661
3Z4L Laser Micrometer Protocol
Appendix N
Offset Contents (data format) Data
+0
+1
+2
+3
Number of receive data words (4 digits Hex)
Segment number
(1 digit BCD)
Measurement interval number (1 digit BCD)
Lower limit value (Decimal portion)
(4 digits BCD)
+4
+5
Lower limit value (Integer portion)
(3 digits BCD)
Lower limit value (Sign)
(BIN)
+6 to +8 Upper limit value
Reference value +9 to
+11
+12
+13 to
+15
Analog output scale number
(1 digit BCD)
Forced zero number (ASCII
5 characters)
+16
+17
+18
0013 (0019 decimal) (fixed)
1 to 5
1 to 7
0000 to 9999
000 to 999
If +: 0
If –: F
Same as lower limit value
Same as lower limit value
0 to 3
Data output condition
(1 digit BCD)
Data output timer value
(3 digits BCD)
Number of seconds for latch timer
(2 digits BCD)
5A45524F2B (“ZERO+”)
4E4F524D20 (“NORM ”)
5A45524F2D (“ZERO–”)
0 to 6
000 to 999
00 to 99
Example –123.4567
+3
+4
+5
4 5 6 7
0 1 2 3
F 0 0 0
Note This sequence can be used for the 3Z4L-4000 Series only when pin 8 on DIP switch SW2 is turned ON.
Single Run Measurement Start (4000-series) (Sequence No. 434
(Hex 01B2))
When the sample measurement condition is from 1 to 999, this sequence performs a single run measurement and requests the measurement results.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
Number of receive data words
Decision result
Decimal portion
(Undefined)
Sign
(Undefined)
Sign
Integer portion
(Undefined)
Decimal portion
Integer portion
(Undefined)
Measurement value
Deviation value
662
3Z4L Laser Micrometer Protocol
Appendix N
Offset Contents (data format) Data
+0
+1
Number of receive data words (4 digits Hex)
Decision result
(ASCII 2 characters)
With no reference setting: 0005
With reference setting: 0008
With no limit setting: 0000
With limit setting: 2B4E (“+N”), 4F4B (“OK”), 2D4E (“–
N”)
0000 to 9999
Example –123.4567
+2
+3
+4
Measurement value (decimal portion)
(4 digits BCD)
Measurement value (integer portion)
(3 digits BCD)
Measurement value (Sign)
(BIN)
+5 to +7 Deviation value
000 to 999
If +: 0
If –: F
+2
+3
+4
4 5 6 7
0 1 2 3
F 0 0 0
Same as measurement value
*The deviation will be stored in this area only when reference setting is made.
Deflection Measurement Start (4000-series) (Sequence No. 435
(Hex 01B3))
This sequence starts a deflection measurement.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
The deflection measurement keeps measuring until sequence No. 438 (Measurement Termination) is executed.
2.
This sequence will be processed the same as sequence No. 411 Zero run measurement start for
5000-series Laser Micrometers.
Continuous Measurement Start (Scan) (4000-series)
(Sequence No. 436 (Hex 01B4))
This sequence starts a continuous measurement. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
438 (Measurement Termination) to end the sequence.
Continuous Measurement Start (Interrupt) (4000-series)
(Sequence No. 437 (Hex 01B5))
This sequence starts a continuous measurement. The interrupt notification method is used for the receive data and the interrupt No. is 101.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
663
3Z4L Laser Micrometer Protocol
Appendix N
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Note 1.
Since this sequence repeats itself within the sequence, once it is executed, it remains in the execution state until cancelled.
2.
Even if execution is cancelled, the Laser Micrometer still keeps measuring. Execute sequence No.
438 (Measurement Termination) to end the sequence.
3.
Sequences No. 413 and No. 437 (Continuous Measurement Start with Interrupt) are not supported by the CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
Continuous Measurement Termination (4000-series)
(Sequence No. 438 (Hex 01B6))
This sequence terminates continuous measurement.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
For continuous measurement: None.
For Deflection Measurement
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Note This sequence may be aborted if it is executed during continuous measurements. Measurements will be terminated even if the sequence is aborted. The sequence will be aborted if executed when the Laser
Micrometer is sending measurement results. The chances that the sequence will be aborted are higher if the scheduled data output value is set to a lower value.
Data Request (4000-series) (Sequence No. 439 (Hex 01B7))
This sequence requests display data in the idle measurement status or latch data generated by the measurement command.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 434 (Single Run Measurement Start).
Forced Positive Zero (4000-series) (Sequence No. 440 (Hex
01B8))
This sequence sets the forced zero direction to positive (+)
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
664
3Z4L Laser Micrometer Protocol
Appendix N
Forced Negative Zero (4000-series) (Sequence No. 441 (Hex
01B9))
This sequence sets the forced zero direction to negative (–)
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Forced Zero Release (4000-series) (Sequence No. 442 (Hex
01BA))
This sequence releases the forced zero direction.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
3Z4L Initialize (4000-series) (Sequence No. 443 (Hex 01BB))
This sequence clears the 3Z4L, sets the mm unit, and sets memory switches.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 401 (Memory Switch Setting).
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Memory switch settings will be ignored for this sequence for 5000-series and 6000-series Laser
Micrometers.
General-purpose Command 1 (4000-series) (Sequence No. 444
(Hex 01BC))
This general-purpose command is used to send data with a specified data length, and receive back only OK.
The terminator (CR) is automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+248
+249
Number of send data words
Send data byte length
Send data
Send data
•
•
Send data
Send data CR
665
3Z4L Laser Micrometer Protocol
Appendix N
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Send data byte length (4 digits Hex)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The number of bytes of send data excluding the terminator (CR)
Send data up to 496 bytes maximum
Specify in ASCII.
+2 to
+249
Send data (ASCII)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
General-purpose Command 2 (4000-series) (Sequence No. 445
(Hex 01BD))
This general-purpose command is used to send data with a specified data length, and receive back receive data other than OK. The terminator (CR) is automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+128
+249
Number of send data words
Send data byte length
Send data
Send data
•
•
Send data
Send data CR
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Send data byte length
(4 digits Hex)
+2 to
+249
Send data (ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The number of bytes of send data excluding the terminator (CR)
Send data up to 496 bytes maximum
Specify in ASCII.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+126
+249
Number of receive data words
Receive data
Receive data
•
•
Receive data
Receive data
Offset
+0
+1 to
+249
Contents (data format)
Number of receive data words
(4 digits BCD)
Receive data (ASCII)
Data
0001 to 00FA (1 to 250 decimal)
When the receive data exceed 498 bytes, only 498 bytes are stored.
666
3Z4L Laser Micrometer Protocol
Appendix N
High Calibration Set (Sequence No. 446 (Hex 01BE))
This sequence sets the Laser Micrometer’s high calibration.
Send Data Word Allocation (3rd Operand of PMCR(260))
Allocations are the same as for sequence No. 404 (Calibration Set) except that the LC gauge dimension in words +4 to +5 are not used.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser
Micrometer. If sequence No. 404 (Calibration Set) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged.
2.
The HC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion.
Low Calibration Set (Sequence No. 447 (Hex 01BF))
This sequence sets the Laser Micrometer’s low calibration.
Send Data Word Allocation (3rd Operand of PMCR(260))
Allocations are the same as for sequence No. 404 (Calibration Set) except that the HC gauge dimension in words +1 to +3 are not used.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Use sequences No. 446 (High calibration set) and No. 447 (Low calibration set) to calibrate the Laser
Micrometer. If sequence No. 404 (Calibration Set) is used, both the high and low calibration gauges must be set, and the high calibration and low calibration gauges cannot be exchanged.
2.
The LC gauge dimension must be set with 3 digits for the integer portion and 4 digits for the decimal portion.
667
Appendix O
Visual Inspection System Protocol
The Visual Inspection System Protocol is used to make various settings or control remotely the Visual Recognition Device connected to the Serial Communications Unit/Board via RS-232C cable.
Protocol Configuration
The configuration of the Visual Inspection System Protocol is shown below.
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
No
Receive word allocation
Yes 450 (01C2) Measurement execution (F200)
451 (01C3) Continuous measure-
453 (01C5)
454 (01C6) ment execution (scan)
(F200)
452 (01C4) Continuous measurement execution (interrupt) (F200)
Reference object registration (group) (F200)
Reference object registration (reference position) (F200)
461 (01CD) Continuous measurement execution (scan)
(F300)
462 (01CE) Continuous measurement execution (interrupt) (F300)
463 (01CF) Reference object registration command 1 execution (F300)
464 (01D0) Reference object registration command 2 execution (F300)
465 (01D1) Illumination fluctuation follow execution (F300)
470 (01D6) Measurement execution and positioning
(F350)
Carries out one measurement one and stores the measurement results in the specified words.
Carries out continuously setting the
F200 and storing the measurement results in the specified words.
Carries out continuously setting the
F200 and storing the measurement results in the specified words.
Performs reference position registration and evaluation criterion registration at the same time.
Registers the reference position for measuring the amount of position displacement when a position displacement compensation is used.
Registers the reference value to discriminate the output format.
455 (01C7) Reference object registration (evaluation criterion) (F200)
456 (01C8) Evaluation condition change (F200)
457 (01C9) Arbitrary measurement value acquisition (F200)
460 (01CC) Measurement execution (F300)
Changes the upper and lower limit values of the evaluation condition of the designated output No.
Stores the measurement values of arbitrary measurement item regardless of output format in the specified words.
Carries out one measurement and stores the measurement results in the specified words.
Carries out continuously setting the
F300 and storing the measurement results in the specified words.
Carries out continuously setting the
F300 and storing the measurement results in the specified words.
Performs a measurement for the input image and updates the reference object data of the full window.
Performs a measurement for the input image and updates the reference object data of the full window
Executes an illumination fluctuation follow.
Carries out one measurement and stores the measurement results in the specified words.
No
No
No
No
No
Yes
Yes
No
No
No
No
Yes
No
No
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
Yes
Notes
3
3
669
Visual Inspection System Protocol
Appendix O
Sequence
No.
Communications sequence name
Function
471 (01D7) Camera designation and positioning (F350)
472 (01D8) Scene switching and positioning (F350)
473 (01D9) Inspection execution and character inspection (F350)
Designates the camera for measurement.
Switches to a designated scene No.
Carries out one inspection and outputs inspection results to the video monitor.
474 (01DA) Character string inspection and character inspection (F350)
480 (01E0) Camera change
(decrease by 1) (F200/
300)
481 (01E1) Camera change
(increase by 1) (F200/
300)
482 (01E2) Binary level modification
(F200/300)
Changes the inspection character string of a designated inspection area No. to a designated character string.
Decreases the display camera No. by 1.
Increases the display camera No. by 1.
Modifies the binary levels (upper limit and lower limit values) of a designated window number No.
483 (01E3) Reset (F200/300)
490 (01EA) Scene switch (decrease by 1)
Resets the F200/F300.
Decreases the scene No. by 1.
491 (01EB) Scene switch (increase by 1)
Increases the scene No. by 1.
492 (01EC) Scene switch (arbitrary) Switches to a designated scene No.
493 (01ED) Measurement, inspection termination
494 (01EE) General-purpose command (send)
495 (01EF) General-purpose command send/(receive)
Terminates the measurement and returns to the home menu.
Sets and executes commands that are otherwise not supported.
Sets and executes commands that are otherwise not supported.
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Notes
Yes
No
Yes
No
No
Yes
No
No
No
Yes
No
Yes
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation:
Receive word allocation:
Set the constant 0000 for the 3rd operand (S).
Set the constant 0000 for the 4th operand (D).
3.
Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications
Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
670
Visual Inspection System Protocol
Connections
The connections for using the Visual Inspection System Protocol are shown below.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
F200/300/350
RS-232C
RS-232C port
25
14
13
1
6
7
8
20
3
4
5
1
2
Pin No.
→
RS-232C Unit
Signal name
Protective ground or earth
Send data
Receive data
Request to send
Clear to send
Data set ready
Signal ground
Carrier detection (Data word receive)
Data terminal ready
Serial Communications Unit/
Board: D-sub 9 pin (female)
Signal Name
SD (TXD)
RD (RXD)
RTS
CTS
DSR
SG
DTR
FG
Pin No.
4
5
2
3
7
9
8
1
Appendix O
Abbreviation
FG (GND)
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
DR (DSR)
SG (GND)
CD (DCD)
ER (DTR)
Pin No.
2
3
4
5
6
7
8
20
F300-E:
D-sub 25 pin (female)
Signal Name
SD (TXD)
RD (RXD)
RTS
CTS
DSR
SG
CD (DCD)
DTR
• For RS/CS Flow Control
Serial Communications Unit/
Board: D-sub 9 pin (female)
Signal Name
SD (TXD)
RD (RXD)
RTS
CTS
DSR
SG
DTR
FG
Pin No.
9
8
1
5
7
2
3
4
F300-E:
D-sub 25 pin (female)
Pin No.
5
6
7
8
20
2
3
4
Signal Name
SD (TXD)
RD (RXD)
RTS
CTS
DSR
SG
CD (DCD)
DTR
671
Visual Inspection System Protocol
Appendix O
Measurement Execution (F200) (Sequence No. 450 (Hex 01C2))
This sequence carries out one measurement and stores the measurement results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined) Output No.
(Undefined)
Evaluation result
Decimal portion
Integer portion
Sign 0
Measurement value
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits Hex)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0006
00 to 07
0: OK
1: NG
Example
–123.456
Data
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
Note 1.
Only one output No. can be stored.
2.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
3.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
Continuous Measurement Execution (Scan) (F200)
(Sequence No. 451 (Hex 01C3))
This sequence carries out continuously the setting of the F200 and stores measurement results in the specified words. The scan notification method is used for the receive data.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined) Output No.
(Undefined)
Evaluation result
Decimal portion
Integer portion
Sign 0
Measurement value
672
Visual Inspection System Protocol
Appendix O
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits Hex)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0006
00 to 07
0: OK
1: NG
Example
–123.456
Data
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
Note 1.
Only one output No. can be designated.
2.
Turn ON the Abort Switch to end this sequences. Abort Switches for port 1 are CIO 190003 for the
Serial Communications Board and CIO 1500 + 25 x unit number, bit 03 for Serial Communications
Units. Abort Switches for port 2 are CIO 190011 for the Serial Communications Board and CIO 1500
+ 25 x unit number, bit 11 for Serial Communications Units.
3.
The ranges of measurement values are as follows:
For calibration OFF setting:–2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
4.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
Continuous Measurement Execution (Interrupt) (F200)
(Sequence No. 452 (Hex 01C4))
This sequence carries out continuously setting the F200 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
Number of receive data words
(Undefined) Output No.
(Undefined)
Evaluation result
Decimal portion
Integer portion
Sign 0
Measurement value
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits BCD)
Output No. (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0006
00 to 07
0: OK
1: NG
Example
–123.456
Data
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
673
Visual Inspection System Protocol
Appendix O
Note 1.
Only one output No. can be designated.
2.
Turn ON the Abort Switch to end this sequences. Abort Switches for port 1 are CIO 190003 for the
Serial Communications Board and CIO 1500 + 25 x unit number, bit 03 for Serial Communications
Units. Abort Switches for port 2 are CIO 190011 for the Serial Communications Board and CIO 1500
+ 25 x unit number, bit 11 for Serial Communications Units.
3.
The ranges of measurement values are as follows:
For calibration OFF setting:–2147483.648 to 2147483.647
For calibration ON setting:–9999999.999 to 9999999.999
4.
If a measurement value exceeds the range of measurement values when calibration is turned off, undefined data is stored in the specified words.
5.
Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications
Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
Reference Object Registration (Group) (F200)
(Sequence No. 453 (Hex 01C5))
This sequence performs reference position registration and criterion registration at the same time.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Reference Object Registration (Reference Position) (F200)
(Sequence No. 454 (Hex 01C6))
This sequence registers the reference position for measuring the amount of position displacement when a position displacement compensation is used.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Reference Object Registration (Criterion) (F200)
(Sequence No. 455 (Hex 01C7))
This sequence registers a reference value to discriminate the output format.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
674
Visual Inspection System Protocol
Appendix O
Evaluation Condition Change (F200) (Sequence No. 456 (Hex
01C8))
This sequence changes the upper and lower limit values of evaluation condition of the designated output No.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
Output No.
Decimal portion
+3
Integer portion
+4
(Undefined)
+5 Sign
+6
(Undefined)
+7
+8
(Undefined)
(Undefined)
Decimal portion
Integer portion
+9 Sign (Undefined)
Upper limit value
Lower limit value
Offset Content (data format)
+0 Number of send data words
(4 digits Hex)
Output No. (2 digits BCD) +1
+2 to +5 Upper limit value (decimal portion)
(3 digits BCD)
Upper limit value (integer portion)
(7 digits BCD)
Upper limit value (sign) (ASCII 2 digits)
Data
000A (0010 decimal)
00 to 07
Example
–123.456
+2 0567
1234
Example
+123.456
+2 0678
2345
+3
+4
+5
0000
2D00
+3
+4
+5
0001
3000
+6 to +9 Lower limit value (decimal portion)
(3 digits BCD)
Lower limit value (integer portion)
(7 digits BCD)
Lower limit value (sign) (ASCII 2 digits)
Same as upper limit.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Only one output No. can be designated.
2.
Enter values so that upper limit
≥ lower limit.
3.
Enter upper limit and lower limit values within the range –2147483.648 to 2147483.648.
Arbitrary Measurement Value Acquisition (F200)
(Sequence No. 457 (Hex 01C9))
This sequence stores measurement values of arbitrary measurement items regardless of output format in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
Data 1
(Undefined)
Data 2
675
Visual Inspection System Protocol
Appendix O
Offset
+0
+1
Content (data format)
Number of send data words
(4 digits Hex)
Data 1 (2 digits BCD)
+2 Data 2 (2 digits BCD)
Data
0003
00: Area
01: Center of gravity x
02: Center of gravity y
03: Main axis angle
04: Output format
05: Reference value of output format
06: X displacement
07: Y displacement
08: Angle displacement
09: X reference position
10: Y reference position
11: Angle reference position
When 00 to 03 is set to data 1
Window No.: 00 to 07
When 04 to 05 is set to data 1
Output No.: 00 to 07
When 06 to 11 is set to data 1
Camera No.: 00 to 01
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined)
Decimal portion
+2
+3 Sign
Integer portion
0
Measurement value
Offset Content (data format)
+0 Number of receive data words
(4 digits BCD)
+1 to +3 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0004
Example
–123.456
Data
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
Note 1.
Only one output No. can be designated.
2.
Measurement is not performed with this command. The measurement results of the last measurement will be stored in the specified words.
3.
This command can acquire only the measurement value of the window No. set by output format.
4.
For data 1 and 2, the receive data is compared with the send data. If the receive data is not the same as the send data, the following flags will be turned ON: The flags for port 1 are CIO 190914 for the
Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications
Units. The flags for port 2 are CIO 1919114 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units.
5.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.647
For calibration ON setting: –9999999.999 to 9999999.999
6.
If a measurement value exceeds the range of measurement values when calibration is turned off, unexpected data is stored in the specified words.
676
Visual Inspection System Protocol
Appendix O
Measurement Execution (F300) (Sequence No. 460 (Hex 01CC))
This sequence carries out one measurement and stores measurement results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
+10
+11
+12
+13
+14
+15
+16
+17
Number of receive data words
(Undefined)
(Undefined)
Window No.
Evaluation
result
Decimal portion
Sign
Sign
0
Integer portion
Decimal portion
Integer portion
0
Decimal portion
Sign
Sign
Sign
Integer portion
0
Decimal portion
Integer portion
0
Decimal portion
0
Integer portion
Data 1
Data 2
Data 3
Data 4
Data 5
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits Hex)
Window number (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0006:
0009:
000C:
000F:
0012:
00 to 07
0: OK
1: NG
Example
–123.456
Data
1 measurement item
2 measurement items
3 measurement items
4 measurement items
5 measurement items
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
+6 to +8 Same as +3 to +5.
+9 to
+11
+12 to
+14
Same as +3 to +5.
Same as +3 to +5.
+15 to
+17
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items is up to 5, but only one window number can be read.
3.
The ranges of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.648
For calibration ON setting: –9999999.999 to 9999999.999
677
Visual Inspection System Protocol
Appendix O
4.
The priority of measurement items being output are as follows:
1 Area
2 Center of gravity X
3 Center of gravity Y
4 Main axis angle
5 Edge angle
6 Center X
7 Center Y
8 Inclination
9 Intersecting point X
10 Intersecting point Y
Continuous Measurement Execution (Scan) (F300)
(Sequence No. 461 (Hex 01CD))
This sequence carries out continuously the settings of F300 and stores measurement results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+8
+9
+10
+11
+12
+4
+5
+6
+7
+0
+1
+2
+3
+13
+14
+15
+16
+17
Number of receive data words
(Undefined) Window No.
(Undefined)
Evaluation result
Decimal portion
Integer portion
Sign
Sign
0
Decimal portion
Integer portion
0
Decimal portion
Integer portion
Sign
Sign
Sign
0
Decimal portion
Integer portion
0
Decimal portion
Integer portion
0
Data 1
Data 2
Data 3
Data 4
Data 5
678
Visual Inspection System Protocol
Appendix O
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits Hex)
Window No. (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
+6 to +8 Same as +3 to +5.
+9 to
+11
Same as +3 to +5.
Same as +3 to +5.
+12 to
+14
+15 to
+17
Same as +3 to +5.
0006:
0009:
000C:
000F:
0012:
00 to 07
0: OK
1: NG
Example
–123.456
Data
1 measurement item
2 measurement items
3 measurement items
4 measurement items
5 measurement items
Example
+123.456
+3
+4
+5
3456
0012
F000
+3
+4
+5
3456
0012
0000
F is stored for negative values.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items are up to 5, but only one window number can be read.
3.
The range of measurement values are as follows:
For calibration OFF setting: –2147483.648 to 2147483.648
For calibration ON setting: –9999999.999 to 9999999.999
4.
The priority of measurement items being output are as follows:
1 Area
2 Center of gravity X
3 Center of gravity Y
4 Main axis angle
5 Edge angle
6 Center X
7 Center Y
8 Inclination
9 Intersecting point X
10 Intersecting point Y
679
Visual Inspection System Protocol
Appendix O
Continuous Measurement Execution (Interrupt) (F300)
(Sequence No. 462 (Hex 01CE))
This sequence carries out continuously setting the F300 and stores measurement results in the specified words. The interrupt notification method is used for the receive data. The interrupt No. is 102.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+11
+12
+13
+14
+7
+8
+9
+10
+15
+16
+17
+4
+5
+6
+0
+1
+2
+3
Number of receive data words
(Undefined)
(Undefined)
Window No.
Evaluation result
Decimal portion
Integer portion
Sign 0
Decimal portion
Integer portion
Sign
Sign
0
Decimal portion
Integer portion
0
Decimal portion
Integer portion
Sign
Sign
0
Decimal portion
Integer portion
0
Data 1
Data 2
Data 3
Data 4
Data 5
Offset
+0
+1
+2
Content (data format)
Number of receive data words
(4 digits Hex)
Window No. (2 digits BCD)
Evaluation result (1 digit BCD)
+3 to +5 Measurement value (decimal portion)
(3 digits BCD)
Measurement value (integer portion)
(7 digits BCD)
Measurement value (sign)
(1 digit)
0006:
0009:
000C:
000F:
0012:
00 to 07
0: OK
1: NG
Example
–123.456
Data
1 measurement item
2 measurement items
3 measurement items
4 measurement items
5 measurement items
Example
+123.456
+3
+4
3456
0012
+3
+4
3456
0012
+5
F000
+5
0000
F is stored for negative values.
+6 to +8 Same as +3 to +5.
+9 to
+11
+12 to
+14
Same as +3 to +5.
Same as +3 to +5.
+15 to
+17
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Same as +3 to +5.
Note 1.
Exponential expressions are used for numbers larger than 9999999.999 and smaller than –999999.9.
2.
The number of measurement items is up to 5, but only one window number can be read.
680
Visual Inspection System Protocol
Appendix O
3.
The ranges of measurement values are as follows:
For calibration OFF setting:–2147483.648 to 2147483.648
For calibration ON setting:–9999999.999 to 9999999.999
4.
The priority of measurement items being output are as follows:
1 Area
2 Center of gravity X
3 Center of gravity Y
4 Main axis angle
5 Edge angle
6 Center X
7 Center Y
8 Inclination
9 Intersecting point X
10 Intersecting point Y
5.
Sequences No. 452 and No. 462 (Continuous Measurement Execution with Interrupt) are not supported by the CS1W-SCU21-V1 and CJ1W-SCU21/41 Serial Communications Units. A protocol syntax error will occur if an attempt is made to execute either sequence with a Serial Communications
Unit.
Do not set an EM bank as the receive storage word for interrupt notification. A protocol syntax error will occur if an EM banks is set.
Reference Object Registration Command 1 Execution (F300)
(Sequence No. 463 (Hex 01CF))
This sequence performs a measurement for the input image and updates reference object data of the full window.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Reference Object Registration Command 2 Execution (F300)
(Sequence No. 464 (Hex 01D0))
This sequence performs a measurement for the input image and updates the reference object data of a designated window.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined) Window No.
Data Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Window No. (1 digit BCD)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
0002
0 to 7
681
Visual Inspection System Protocol
Appendix O
Illumination Fluctuation Follow Execution (F300)
(Sequence No. 465 (Hex 01D1))
This sequence executes an illumination fluctuation follow.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Measurement Execution and Positioning (F350)
(Sequence No. 470 (Hex 01D6))
This sequence carries out one measurement and stores the measurement results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
+3
+4
+5
+6
Number of receive data words
Decimal portion
Sign
Sign
Integer portion
Decimal portion
Integer portion
Sign
0
Decimal portion
Integer portion
X displacement
Y displacement
Correlation value
Offset Content (data format)
+0 Number of receive data words
(4 digits Hex)
+1 to +2 X displacement (decimal portion)
(3 digits BCD)
X displacement (integer portion)
(3 digits BCD)
X displacement (sign) (1 digit)
(.)
0007
Data
+3 to +4 Y displacement (decimal portion)
(3 digits BCD)
Y displacement (integer portion)
(3 digits BCD)
Y displacement (sign) (1 digit)
(.)
+5 to +6 Correlation value (decimal portion)
(3 digits BCD)
Correlation value (integer portion)
(3 digits BCD)
Correlation value (sign) (1 digit)
(.)
Example
–123.456
Example
+123.456
+1
+2
3456
F012
+1
+2
3456
0012
F is stored for negative values.
Example
–123.456
+1
+2
3456
F012
Example
+123.456
+1
+2
3456
0012
F is stored for negative values.
Example
–12.345
Example
+12.345
+1
+2
2345
F001
+1
+2
2345
0001
F is stored for negative values.
Note 1.
The number of models that can be stored in a designated word is 1.
2.
If a measurement is carried out without executing a camera designation, a measurement is executed for all cameras in which the measurement model is registered.
3.
When the correlation value is less than 70 and the measurement value overflows, the following flags will be turned ON. The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO
682
Visual Inspection System Protocol
Appendix O
1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO
1919114 for the Serial Communications Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial
Communications Units.
4.
Data to be output is within the range 999.999 (upper limit) to –999.999 (lower limit).
5.
Retry processing is not performed for this sequence.
6.
Turn the Abort Bit ON and then OFF to end this sequence.
Camera Designation and Positioning (F350) (Sequence No. 471
(Hex 01D7))
This sequence designates the cameras for measurement.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
Number of send data words
(Undefined)
(Undefined)
First camera
No.
Last camera
No.
Offset
+0
+1
+2
Content (data format)
Number of send data words
(4 digit Hex)
First camera No. (1 digit BCD)
Last camera No. (1 digit BCD)
0003
0 to 7
0 to 7
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Set values so that the first camera No.< last camera No.
2.
If a designated camera No. is abnormal, the following flags will be turned ON. The flags for port 1 are
CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for
Serial Communications Units. The flags for port 2 are CIO 191914 for the Serial Communications
Board and CIO 1500 + 25 x unit number +19, bit 14 for Serial Communications Units.
Scene Switching and Positioning (F350) (Sequence No. 472 (Hex
01D8))
This sequence switches to a designated scene No.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Scene No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Scene No. (2 digits BCD)
0002
00 to 15
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
If a scene No. is abnormal, the following flags will be turned ON. The flags for port 1 are CIO 190914 for the Serial Communications Board and CIO 1500 + 25 x unit number +9, bit 14 for Serial Communications Units. The flags for port 2 are CIO 191914 for the Serial Communications Board and CIO
1500 + 25 x unit number +19, bit 14 for Serial Communications Units.
2.
Retry processing is not performed for this sequence.
683
Visual Inspection System Protocol
Appendix O
3.
Turn ON the Abort Switch to end this sequence.
Inspection Execution and Character Inspection (F350)
(Sequence No. 473 (Hex 01D9))
This sequence carries out one inspection and outputs the inspection results to a video monitor.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Character String Inspection and Character Inspection (F350)
(Sequence No. 474 (Hex 01DA))
This sequence changes the inspection character string of a designated inspection area No. to a designated character string.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
~
Number of send data words
Inspection area No.
(Undefined) Number of designated character strings
Designated character string
~
Designated character string
Offset Contents (data format)
+0
+1
Number of send data words
(4 digits Hex)
Number of designated character strings (4 digits Hex) area
(1 digit BCD)
+3 to Number of designated character strings (ASCII)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Data
0004 to 000F (0004 to 0015 decimal)
0000 to 0018 (0000 to 0024 decimal)
0 to 7
Camera Change (Decrease by 1) (F200/300) (Sequence No. 480
(Hex 01E0))
This sequence decreases the display camera No. by 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Camera Change (Increase by 1) (F200/300) (Sequence No. 481
(Hex 01E1))
This sequence increases the display camera No. by 1.
684
Visual Inspection System Protocol
Appendix O
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Binary Level Modification (F200/300) (Sequence No. 482 (Hex
01E2))
This sequence modifies the binary levels (upper limit and lower limit values) of a designated output No. (F200) or window number No. (F300).
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
(Undefined)
(Undefined)
Number of send data words
(Undefined)
Upper limit value
Lower limit value
Window No.
or Output No.
+1
+2
+3
Offset
+0
Contents (data format)
Number of send data words
(4 digits Hex)
Window No. (1 digit BCD)
Upper limit value (3 digits BCD)
Lower limit value (3 digits BCD)
0004
0 to 7
000 to 255
000 to 255
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Enter values so that the upper limit
≥ lower limit.
Reset (F200/300) (Sequence No. 483 (Hex 01E3))
This sequence resets the F200/F300 (to starting status).
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Scene Switching (Decrease by 1) (Sequence No. 490 (Hex
01EA))
This sequence decreases the scene No. by 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Scene Switching (Increase by 1) (Sequence No. 491 (Hex 01EB))
This sequence increases the scene No. by 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
685
Visual Inspection System Protocol
Appendix O
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Scene Switching (Arbitrary) (Sequence No. 492 (Hex 01EC))
This sequence switches to a designated scene No.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
Number of send data words
(Undefined) Scene No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits BCD)
Scene No. (2 digits BCD)
0002
00 to 15
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Measurement, Inspection Termination (Sequence No. 493 (Hex
01ED))
This sequence terminates the measurement and returns to the home menu.
Send Data Word Allocation (3rd Operand of PMCR(260))
None.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
General-purpose Command (Send) (Sequence No. 494 (Hex
01EE))
This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
Number of send data words
Command length
Command (Undefined)
~
Offset
+0
+1
+2 to
Contents (data format)
Number of send data words
(4 digits Hex)
Command length (4 digits Hex)
Command (ASCII)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
The processing depends on the command.
2.
For a command with a response, use sequence #495.
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
Specify ASCII data.
686
Visual Inspection System Protocol
Appendix O
General-purpose Command (Send/Receive) (Sequence No. 495
(Hex 01EF))
This sequence can set and execute commands that are not otherwise supported. The delimiter (CR+LF) is automatically attached to the send data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
Number of send data words
Command length
Command (Undefined)
~
Offset
+0
+1
+2 to
Contents (data format)
Number of send data words
(4 digits Hex)
Command length (4 digits Hex)
Command (ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
Specify ASCII data.
Receive Data Word Allocation (4th Operand of PMCR(260))
The reception data is stored in the reception data words without the delimiter (CR+LF),
Receive data storage words
+0
+1
+2
~
Number of receive data words
Command length
Command (Undefined)
~
Offset
+0
+1
+2 to
Contents (data format)
Number of receive data words
(4 digits Hex)
Command length (4 digits Hex)
Command (ASCII)
Note 1.
The processing depends on the command.
2.
For a command without a response, use sequence #495.
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
ASCII data is returned.
687
Appendix P
V600/V620 ID Controller Protocol
The V600/V620 ID Controller Protocol is used to make various settings or control remotely the ID Controller
Connected to the Serial Communications Unit/Board via RS-232C or RS-422 cable.
Protocol Configuration
The configuration of the V600/V620 ID Controller Protocol is shown below.
Sequence
No.
Communications sequence name
Function
500 (01F4)
501 (01F5)
502 (01F6)
503 (01F7)
504 (01F8)
505 (01F9)
Read (ASCII/1)
Read (ASCII/2)
Read (ASCII/4)
Read (ASCII/8)
Read (Hex/1)
Read (Hex/2)
Used when the number of Heads to be read from the Carrier is 1.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
Used when the number of Heads to be read from the Carrier is 1.
Used when the number of Heads to be read from the Carrier is 2.
506 (01FA)
507 (01FB)
Read (Hex/4)
Read (Hex/8)
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
508 (01FC) Auto-read (ASCII/1) Used when the number of Heads to be read from the Carrier is 1.
509 (01FD) Auto-read (Hex/1) Used when the number of Heads to be read from the Carrier is 1.
510 (01FE) Polling Auto-read
(ASCII)
511 (01FF) Polling Auto-read
Subcommand
(ASCII/2)
512 (0200) Polling Auto-read
Subcommand
(ASCII/4)
513 (0201) Polling Auto-read
Subcommand
(ASCII/8)
Used when the number of Heads to be read from the Carrier is from 1 to 8.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
514 (0202) Polling Auto-read
(Hex)
515 (0203) Polling Auto-read
Subcommand (Hex/2)
516 (0204) Polling Auto-read
Subcommand (Hex/4)
517 (0205) Polling Auto-read
Subcommand (Hex/8)
Used when the number of Heads to be read from the Carrier is from 1 to 8.
Used when the number of Heads to be read from the Carrier is 2.
Used when the maximum number of Heads to be read from the Carrier is 4.
Used when the maximum number of Heads to be read from the Carrier is 8.
518 (0206) Write (ASCII/1) Used when the number of Heads to be written to the Carrier is 1.
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Ladder interface
Send word allocation
Yes
Receive word allocation
Yes
Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
No
Yes
Yes
Yes
No
689
V600/V620 ID Controller Protocol
Appendix P
Sequence
No.
Communications sequence name
Function
519 (0207)
520 (0208)
521 (0209)
522 (020A)
523 (020B)
524 (020C)
525 (020D)
Write (ASCII/2)
Write (ASCII/4)
Write (ASCII/8)
Write (Hex/1)
Write (Hex/2)
Write (Hex/4)
Write (Hex/8)
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the number of Heads to be written to the Carrier is 1.
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
526 (020E) Auto-write (ASCII/1) Used when the number of Heads to be written to the Carrier is 1.
527 (020F) Auto-write (Hex/1) Used when the number of Heads to be written to the Carrier is 1.
528 (0210) Polling Auto-write
(ASCII/2)
529 (0211) Polling Auto-write
Subcommand
(ASCII/2)
Used when the number of Heads to be written to the Carrier is 2.
Used when the number of Heads to be written to the Carrier is 2.
530 (0212) Polling Auto-write
(ASCII/4)
531 (0213) Polling Auto-write
Subcommand
(ASCII/4)
532 (0214) Polling Auto-write
(ASCII/8)
533 (0215) Polling Auto-write
Subcommand
(ASCII/8)
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 8.
Used when the maximum number of Heads to be written to the Carrier is 8.
534 (0216) Polling Auto-write
(Hex/2)
535 (0217) Polling Auto-write
Subcommand (Hex/2)
536 (0218) Polling Auto-write
(Hex/4)
537 (0219) Polling Auto-write
Subcommand (Hex/4)
Used when the number of Heads to be written to the Carrier is 2.
Used when the number of Heads to be written to the Carrier is 2.
Used when the maximum number of Heads to be written to the Carrier is 4.
Used when the maximum number of Heads to be written to the Carrier is 4.
538 (021A) Polling Auto-write
(Hex/8)
Used when the maximum number of Heads to be written to the Carrier is 8.
539 (021B)
540 (021C)
Polling Auto-write
Subcommand (Hex/8)
Data check
Used when the maximum number of Heads to be written to the Carrier is 8.
Writes and verify the CRC code for the check blocks designated by the user.
541 (021D) Control management Performs I/O or an I/O read.
542 (021E) Error information read Reads information from the latest error log.
543 (021F) Command processing cancel
Cancels command processing except polling command processing and returns to the command waiting status.
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
690
V600/V620 ID Controller Protocol
Appendix P
Sequence
No.
Communications sequence name
Function Ladder interface
Send word allocation
Yes
Receive word allocation
Yes 544 (0220) Polling auto-read command processing cancel
545 (0221) Polling auto-write command processing cancel
546 (0222) General-purpose command
Cancels polling auto-read processing.
Cancels polling auto-write processing.
Sends arbitrary data and stores receive data to receive data words.
Yes
Yes
Yes
Yes
Note 1.
The hexadecimal equivalents of sequences numbers are given in parentheses
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
3.
The Read/Write Head is abbreviated as R/W Head and the Data Carrier is abbreviated as simply Carrier in this appendix.
Connections
Connections when using the V600/V620 ID Controller Protocol are shown below.
RS-232C Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
Head
RS-232C
RS-232C port
ID Controller
Data Carrier
RS-232C
Serial Communications Unit/Board
D-sub 9 pin (female)
Signal
FG
SD
RD
RTS
CTS
SG
Pin No.
1
2
3
4
5
9
Shield
ID Controller (CD1D):
D-sub 9 pin (female)
Signal
Pin No.
1
2
3
4
5
9
GR
SD
RD
RTS
CTS
SG
691
V600/V620 ID Controller Protocol
ID Controller (CA1A):
D-sub 25 pin (female)
Serial Communications Unit/Board:
D-sub 9 pin (female)
Appendix P
Shield
RS-422 Connections
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
PLC PS
RS-422A/485 port
Head Data Carrier
ID Controller
RS-422
Head Data Carrier
ID Controller
RS-422
Serial Communications Board/Unit:
D-sub 9 pin (female)
Signal name
RDB
SDB
RDA
SDA
FG
Pin No.
8
2
6
1
Hood
Up to 16 units can be connected
ID Controller (CD1D):
D-sub 9 pin (female)
Pin No.
1
Signal name
RDB
3
5
SG
SDB
6
7
9
RDA
FG
SDA
Shield
Note 1.
Ground the cable shield at either the ID Controller or the Serial Communications Unit/Board to prevent malfunction.
2.
Turn ON the pin 6 on DIP switch SW6 to set the host communications procedure to the 1-to-N procedure for 1-to-N connections.
692
V600/V620 ID Controller Protocol
DIP Switch Settings
V600/620-CD1D DIP Switches
DIP Switch 1
1 2 3 4 5 6 7 8
Appendix P
Not used (Always keep it OFF.)
Local communications mode setting
Speed priority setting
Distance priority setting
• SW7 Setting
This setting is only valid if the EEPROM-type (batterylesstype) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (battery-type) DC. SW7 must be set to OFF when the V620 is used.
Baud rate
(bps)
2,400
4,800
9,600
19,200
Display mode
Error display mode
I/O display mode
Data length (bit)
7
8
8
8
8
7
7
7
STOP bits (bit)
1
2
1
1
1
2
2
1
Parity type
O
N
N
E
O
E
O
E
693
V600/V620 ID Controller Protocol
DIP Switch 2
1 2 3 4 5 6 7 8
Appendix P
Not used (Always keep it OFF.)
Communications protocol setting with host devices
1-to-N protocol
1-to-1 protocol
Note When selecting the "1-to-N" protocol, setting is limited to
N=1. In this case, the FCS check code may be added.
• ID Controller Unit Number Setting (Valid Only for 1-to-N Protocol)
Unit No.
No. 0
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
Note 1. Be careful not to set to the same unit number twice.
2. Set them to OFF for the 1-to-1 protocol.
Synchronous condition
OFF (LL level)
ON (HL level)
Trailing edge
Leading edge
694
V600/V620 ID Controller Protocol
V600-CA
@
A DIP Switches
DIP Switch 1
Mode 1
1 2 3 4 5 6 7 8
• Baud Rate
Setting
Baud rate
(bps)
1,200
2,400
4,800
9,600
19,200
1=ON, 0=OFF
Note Factory Setting: All OFF
SW7 and SW8: Be sure to set to OFF.
• Communications Format
Data length (bit)
8
8
7
8
8
7
7
7
1 = ON, 0 = OFF (See note 1)
Note 1. Data length setting
7 bits: ASCII
8 bits: JIS8 unit code
2. Parity setting
E: Even parity
O: Odd parity
N: No parity designation
STOP bit (bit)
1
1
1
2
1
2
2
1
DIP Switch 2
1 2 3 4 5 6 7 8
Appendix P
Parity type
O
N
N
E
O
E
O
E
(See note 2)
• SW8: Receive Side Terminating Resistance Setting (Valid Only for the V600-CA2A)
Connected (ID Controller send side)
Not connected
• SW7: Receive Side Terminating Resistance Setting (Valid Only for the V600-CA2A)
Connected (ID Controller receive side)
Not connected
• SW6: Communications Protocol Setting
1-to-N protocol
1-to-1 protocol
• ID Controller Unit Number Setting (Valid Only for the 1-to-N Protocol)
Unit No.
• Local Communications Mode Setting
Speed priority setting
Distance priority setting
No. 0
No. 1
No. 2
No. 3
No. 4
No. 5
• SW1 Setting
This setting is only valid if the EEPROM-type (batteryless-type) Data Carrier (DC) is accessed. The setting of SW7 does not work with the SRAM-type (batterytype) DC.
No. 6
No. 7
No. 8
No. 9
No. 10
No. 11
• SW6 Setting
When selecting the 1-to-N protocol for the
V600-CA1A/RS-232C interface, the setting is limited to N=1. In this case, the FCS check code may be added.
No. 12
No. 13
No. 14
No. 15
Note 1. Be careful not to set to the same unit number twice.
2. Set them to OFF for the 1-to-1 protocol.
695
V600/V620 ID Controller Protocol
Appendix P
Read (ASCII/1) (Sequence No. 500 (Hex 01F4))
This sequence is used when the number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
Number of send data words
(Undefined) Unit No.
(Undefined) Head CH No.
Leading address No.
(Undefined) Read bytes
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0005 (fixed)
+2
+3
R/W Head channel
(CH) No. (1 digit BCD)
Data
00 to 07 (CD1D)
00 to 15 (CA
@A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
+4
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
01 to F4 (1 to 244 bytes)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+122
Number of receive data words
Read data
Read data
Read data
~
+0
Offset
+1 to +122
Contents (data format)
Number of receive data words (4 digits Hex)
Read data (ASCII)
Data
0002 to 007B (2 to 123 decimal)
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words, as shown in the following diagram.
Data Carrier
+0
+1
+2
+3
+4
Example for 5 bytes
+0
+1
+2
Receive data storage words
Each byte (address) in the Data
Carrier contains the code for one
ASCII character.
696
V600/V620 ID Controller Protocol
Appendix P
Read (ASCII/2) (Sequence No. 501 (Hex 01F5))
This sequence is used when the number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
Number of send data words
Number of Heads
(Undefined)
Unit No.
+3
+4
+5
+6
+7
(Undefined)
Head CH No.
Leading address No.
(Undefined)
(Undefined)
Read bytes
Unit No.
+8
+9
(Undefined) Head CH No.
Leading address No.
(Undefined)
Read bytes
CH 1
CH 2
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 000A (6 to 10 decimal)
0001 to 0002
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
N: Number of Heads
01 to 76 (1 to 118 bytes)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+59
+60
+61
+119
~
Number of receive data words
Read data
Read data
Not used
Read data
Read data
~
~
CH 1
CH 2
Offset Contents (data format)
+0
+(60(N–1)+1) to
+(60(N–1)+59)
N: Number of Heads
Number of receive data words (4 digits Hex)
Read data (ASCII)
0002 to 0120
Data
Number of read bytes store in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
697
V600/V620 ID Controller Protocol
Appendix P
Read (ASCII/4) (Sequence No. 502 (Hex 01F6))
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
+14
~
+15
+16
+17
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 1
CH 2
4 CH
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 0012 (6 to 18 decimal)
0001 to 0004
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
N: Number of Heads
01 to 30 (1 to 48 bytes)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+24
+25
~
+48
Number of receive data words
Read data
Read data
Read data
Read data
~
~
~
~
CH 1
CH 2
Read data
+73
~
+96
Read data
~
4 CH
698
V600/V620 ID Controller Protocol
Appendix P
Offset Contents (data format)
+0
+(24(N–1)+1) to
+(24(N–1)+24)
N: Number of Heads
Number of receive data words (4 digits Hex)
Read data (ASCII)
0002 to 0097
Data
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
Read (ASCII/8) (Sequence No. 503 (Hex 01F7))
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
~
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
(Undefined)
Read bytes
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined) Read bytes
~
+30
+31
+32
+33
(Undefined) Unit No.
(Undefined) Head CH No.
Leading address No.
(Undefined)
Read bytes
CH 1
CH 2
8 CH
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 0022 (6 to 34 decimal)
0001 to 0008
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
N: Number of Heads
01 to 14 (1 to 20 bytes)
699
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
Number of receive data words
Read data
+10
+11
~
+20
Read data
Read data
Read data
~
~
~
~
CH 1
CH 2
+71
~
+80
Read data
~
CH 8
Read data
Offset Contents (data format)
+0
+(10(N–1)+1) to
+(10(N–1)+10)
N: Number of Heads
Number of receive data words (4 digits Hex)
Read data (ASCII)
0002 to 0081
Data
Number of read bytes stored in ASCII
Note Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
Read (Hex/1) (Sequence No. 504 (Hex 01F8))
This sequence is used when the number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
Number of send data words
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0005 (fixed)
+2
+3
R/W Head CH No. (1 digit BCD)
Data
00 to 07 (CD1D)
00 to 15 (CA
@A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
+4
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
01 to 7A (1 to 122 bytes)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
+2
~
+61
Number of receive data words
Read data
Read data
Read data
~
700
V600/V620 ID Controller Protocol
Appendix P
+0
Offset
+1 to +61
Contents (data format)
Number of receive data words (4 digits Hex)
Read data (Hex)
Data
0002 to 003E (6 to 62 decimal)
Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words, as shown in the following diagram.
Data Carrier
+0
+1
+2
Example for 6 bytes
Receive data storage words
+0
+1
Each byte (address) in the Data
Carrier contains 2 digits.
Read (Hex/2) (Sequence No. 505 (Hex 01F9))
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
+6
+7
+8
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
+9 (Undefined)
Read bytes
CH 1
CH 2
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 000A (6 to 10 decimal)
0001 to 0002
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4)
+(4(N–1)+5)
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
N: Number of Heads
01 to 3C (1 to 60 bytes)
701
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+30
+31
+60
~
+61
+90
~
Number of receive data words
Read data
Read data
Not used
Not used
Read data
Read data
~
~
~
CH 1
CH 2
Offset Contents (data format)
+0
+(60(N–1)+1) to
+(60(N–1)+30)
N: Number of Heads
Number of receive data words (4 digits Hex)
Read data (Hex)
Data
0002 to 005B (2 to 91 decimal)
Number of read bytes stored in hexadecimal code
Note Data for Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words.
Read (Hex/4) (Sequence No. 506 (Hex 01FA))
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
+2
+3
+4
+5
+6
+7
+8
+9
+14
~
+15
+16
+17
Number of send data words
Number of Heads
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
~
CH 1
CH 2
CH 4
702
V600/V620 ID Controller Protocol
Appendix P
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 0012 (6 to 18 decimal)
0001 to 0004
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hex)
+(4(N–1)+5) Read bytes
(2 digits Hex)
N: Number of Heads
01 to 18 (1 to 24 bytes)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+12
+13
~
+24
+25
~
Number of receive data words
Read data
Read data
(Not used)
(Not used)
Read data
Read data
+36
~
~
~
~
~
CH 1
CH 2
+73
~
+84
Read data
Read data
~
CH 4
+0
Offset
+(24(N–1)+1) to
+(24(N–1)+12)
Contents (data format)
Number of receive data words (4 digits Hex)
Read data (Hex)
Data
0002 to 0055 (2 to 85 decimal)
Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is received beginning with the largest offset from the receive data words.
703
V600/V620 ID Controller Protocol
Appendix P
Read (Hex/8) (Sequence No. 507 (Hex 01FB))
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
+30
+31
+32
+33
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
CH 1
CH 2
CH 8
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 0022 (6 to 34 decimal)
0001 to 0008
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(4(N–1)+4) Leading address No.
(4 digits Hex)
+(4(N–1)+5) Read bytes
(2 digits Hex)
N: Number of Heads
01 to 0A (1 to 10 bytes)
704
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+5
+6
~
+10
+11
~
+15
~
Number of receive data words
Read data
Read data
Not used
Not used
Read data
Read data
~
~
~
~
CH 1
CH 2
+71
~
+75
Read data
Read data
~
CH 8
Offset Contents (data format)
+0
+(10(N–1)+1) to
+(10(N–1)+5)
N: Number of Heads
Number of receive data words (4 digits Hex)
Read data (CH 1) (Hex)
Data
0002 to 004C (2 to 76 decimal)
Number of read bytes stored in hexadecimal data
Note Data for Data Carriers designated for hexadecimal is sent beginning with the largest offset from the receive data words.
Auto-read (ASCII/1) (Sequence No. 508 (Hex 01FC))
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 500 (Read (ASCII/1)).
Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Auto-read (Hex/1) (Sequence No. 509 (Hex 01FD))
This sequence is used when the maximum number of Heads to be read from the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 504 (Read (Hex/1)).
Note For auto-read (AR), a response is not returned if the number of Heads is not read by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
705
V600/V620 ID Controller Protocol
Appendix P
Polling Auto-read (ASCII) (Sequence No. 510 (Hex 01FE))
This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
~
+(4(N–1)+2)
+(4(N–1)+3)
+(4(N–1)+4)
+(4(N–1)+5)
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined)
Read bytes
~
CH 1
CH N
* N: Number of Heads
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
+(4(N–1)+4)
+(4(N–1)+5)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0006 to 0022 (6 to 34 decimal)
0001 to 0008
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
If number of Heads is 2 or less
01 to 76 (1 to 118 bytes)
If number of Heads is 4 or less
01 to 30 (1 to 48 bytes)
If number of Heads is 8 or less
01 to 20 (1 to 20 bytes)
N: Number of Heads
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 510 before executing Sequence No. 511, 512, 513.
2.
Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (ASCII/2) (Sequence No. 511
(Hex 01FF))
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 501 (Read (ASCII/2)).
706
V600/V620 ID Controller Protocol
Appendix P
Note 1.
Execute Sequence No. 510 before executing Sequence No. 511.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (ASCII/4) (Sequence No. 512
(Hex 0200))
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 502 (Read (ASCII/4)).
Note 1.
Execute Sequence No. 510 before executing Sequence No. 512.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (ASCII/8) (Sequence No. 513
(Hex 0201))
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #510.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 503 (Read (ASCII/8)).
Note 1.
Execute Sequence No. 510 before executing Sequence No. 513.
2.
Data from Data Carriers designated for ASCII is stored beginning with the smallest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
707
V600/V620 ID Controller Protocol
Appendix P
Polling Auto-read (Hex) (Sequence No. 514 (Hex 0202))
This sequence is used when the number of Heads to be read from the Carrier is from 1 to 8.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
~
+(4(N–1)+2)
+(4(N–1)+3)
+(4(N–1)+4)
+(4(N–1)+5)
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
(Undefined) Read bytes
~
CH 1
CH N
* N: Number of Heads
+0
+1
Offset
+(4(N–1)+2)
+(4(N–1)+3)
+(4(N–1)+4)
+(4(N–1)+5)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Leading address No.
(4 digits Hex)
Read bytes
(2 digits Hex)
Data
0006 to 0022 (6 to 34 decimal)
0001 to 0008
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
0000 to FFFF
If number of Heads is 2 or less
01 to 3C (1 to 60 bytes)
If number of Heads is 4 or less
01 to 18 (1 to 24 bytes)
If number of Heads is 8 or less
01 to 0A (1 to 10 bytes)
N: Number of Heads
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 514 before executing Sequence No. 515, 516, 517.
2.
Execute Sequence No. 544 (Polling Auto-read Command Processing Cancel) to cancel the polling auto-read.
Polling Auto-read Sub-command (Hex/2) (Sequence No. 515
(Hex 0203))
This sequence is used when the maximum number of Heads to be read from the Carrier is 2. Up to 60 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 505 (Read (Hex/2)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 505 (Read (Hex/2)).
Note 1.
Execute Sequence No. 514 before executing Sequence No. 515.
708
V600/V620 ID Controller Protocol
Appendix P
2.
Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
Polling Auto-read Sub-command (Hex/4) (Sequence No. 516
(Hex 0204))
This sequence is used when the maximum number of Heads to be read from the Carrier is 4. Up to 24 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 506 (Read (Hex/4)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 506 (Read (Hex/4)).
Note 1.
Execute Sequence No. 514 before executing Sequence No. 516.
2.
Data from Data Carrier designated for hexadecimal is stored beginning with the largest offset from the receive data words.
Polling Auto-read Sub-command (Hex/8) (Sequence No.517 (Hex
0205))
This sequence is used when the maximum number of Heads to be read from the Carrier is 8. Up to 10 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation 3rd Operand of PMCR(260))
The send data word allocation is similar to that of sequence No. 507 (Read (Hex/8)). However, the leading address No. and number of read bytes are not used and will be the value specified for sequence #514.
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of sequence No. 507 (Read (Hex/8)).
Note 1.
Execute sequence No. 514 before executing sequence No. 517.
2.
Data from Data Carriers designated for hexadecimal is stored beginning with the largest offset from the receive data words.
3.
Retry processing is not performed for this sequence.
709
V600/V620 ID Controller Protocol
Appendix P
Write (ASCII/1) (Sequence No.518 (Hex 0206))
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send +0 data
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Max
~
+249
Write data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Relevant Unit No. (2 digits BCD)
+2
+3
R/W Head CH No. (1 digit BCD)
Data
0006 to 00FA (6 to 250 decimal)
00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
+4
+5to
+249
Leading address No.
(4 digits Hex)
Number of write bytes
(4 digits Hex)
Write data (ASCII)
0001 to 01EA (1 to 490 decimal)
Input in ASCII
Up to 248 bytes (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words, as shown in the following diagram.
Receive data storage words
+0
+1
+2
Example for 5 bytes
+0
+1
+2
+3
+4
Data Carrier
Each byte (address) in the Data
Carrier contains the code for one
ASCII character.
710
V600/V620 ID Controller Protocol
Appendix P
Write (ASCII/2) (Sequence No. 519 (Hex 0207))
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
+6
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
~
CH 1
+64
+65
+66
+67
+68
+69
+70
~
+128
Write data
(Not used)
(Undefined) Unit No.
(Undefined) Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
CH 2
+0
+1
Offset
+(64(N–1)+2)
+(64(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 0081 (7 to 129 decimal)
0001 to 0002
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(64(N–1)+4)
+(64(N–1)+5)
+(64(N–1)+6) to
(64(N–1)+64)
N: Number of Heads
Leading address No.
(4 digits Hex)
Number of write bytes
(4 digits Hex)
Write data (ASCII)
0001 to 0076 (1 to 118 decimal)
Input in ASCII.
Up to 118 bytes (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words.
711
V600/V620 ID Controller Protocol
Appendix P
Write (ASCII/4) (Sequence No. 520 (Hex 0208))
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
+6
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
+29
+30
+31
+32
+33
+34
+57
~
Write data
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
~
CH 1
CH 2
~ ~
+86
+87
+88
+89
+90
~
+113
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
Write data
~
CH 4
+0
+1
Offset
+(28(N–1)+2)
+(28(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 0072 (7 to 114 decimal)
0001 to 0004
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(28(N–1)+4)
+(28(N–1)+5)
+(28(N–1)+6) to
(28(N–1)+29)
Leading address No.
(4 digits Hex)
Number of write bytes
(4 digits Hex)
Write data (ASCII)
N: Number of Heads
0001 to 0030 (1 to 48 decimal)
Input in ASCII.
Up to 48 bytes (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Write designated for ASCII is sent beginning with the smallest offset from the send data words.
712
V600/V620 ID Controller Protocol
Appendix P
Write (ASCII/8) (Sequence No. 521 (Hex 0209))
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 bytes of data can be read for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
~
+15
+16
+17
+18
+19
+20
+29
~
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
~
Write data
(Undefined)
Unit No.
(Undefined)
Head CH No.
Leading address No.
Number of write bytes
Write data
~
Write data
~
CH 1
CH 2
+100
+101
+102
+103
+104
+113
~
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write bytes
Write data
~
CH 8
Write data
+0
+1
Offset
+(14(N–1)+2)
+(14(N–1)+3)
Contents (data format)
Number of send data words(4 digits Hex)
Number of Heads
(4 digits BCD)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 0072 (7 to 114 decimal)
0001 to 0008
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(14(N–1)+4)
+(14(N–1)+5)
Leading address No.
(4 digits Hex)
Number of write bytes
(4 digits Hex)
+(14(N–1)+6) to
(14(N–1)+15)
Write data (ASCII)
N: Number of Heads
0001 to 0014 (1 to 20 decimal)
Input in ASCII
Up to 20 bytes (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note Write data designated for ASCII is sent beginning with the smallest offset from the send data words.
713
V600/V620 ID Controller Protocol
Appendix P
Write (Hex/1) (Sequence No. 522 (Hex 020A))
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
~ ~
Max +35
(Undefined) Write data
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Relevant Unit No. (2 digits BCD)
+2 R/W Head CH No. (1 digit BCD)
+3
+4
Leading address No.
(4 digits Hex)
Number of write digits
(4 digits Hex)
+5 to 35 Write data (Hex)
Data
0006 to 0024 (6 to 36 decimal)
00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF
0002 to 007A (2 to 122 decimal)
Input in hexadecimal
Up to 122 digits (max.)
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Data of which Data Carrier designated for hexadecimal is sent beginning with the largest offset from the send data words, as shown in the following diagram.
2.
Always set an even number of digits for the write data.
Data Carrier
Receive data storage words
+0
+1
Example for 6 bytes
+0
+1
+2
Each byte (address) in the Data
Carrier contains 2 digits.
714
V600/V620 ID Controller Protocol
Appendix P
Write (Hex/2) (Sequence No. 523 (Hex 020B))
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
+6
~
+19
+20
+65
~
+66
+67
+68
+69
+70
+83
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
(Not used)
(Not used)
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
~
~
~
CH 1
CH 2
+0
+1
Offset
+(64(N–1)+2)
+(64(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits Hex)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 0054 (7 to 84 decimal)
0002 to 0002
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(64(N–1)+4)
+(64(N–1)+5)
+(64(N–1)+6) to
(64(N–1)+19)
N: Number of Heads
Leading address No.
(4 digits Hex)
Number of write digits
(4 digits Hex)
Write data (Hex)
0002 to 0038 (2 to 56 decimal)
Input in hexadecimal
Up to 56 digits (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
715
V600/V620 ID Controller Protocol
Appendix P
Write (Hex/4) (Sequence No. 524 (Hex 020C))
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 24 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
~
+11
+12
~
+29
+30
+31
+32
+33
+34
~
+39
+86
~
+87
+88
+89
+90
~
+95
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
Not used
Not used
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
Write data
~
~
~
~
~
CH 1
CH 2
CH 4
+0
+1
Offset
+(28(N–1)+2)
+(28(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits Hex)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 0060 (7 to 96 decimal)
0001 to 0004
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(28(N–1)+4) Leading address No.
(4 digits Hex)
+(28(N–1)+5)
+(28(N–1)+6) to
(28(N–1)+11)
N: Number of Heads
Number of write digits
(4 digits Hex)
Write data (Hex)
0002 to 0018 (2 to 24 decimal)
Input in hexadecimal code
Up to 24 digits (max.) can be set
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
716
V600/V620 ID Controller Protocol
Appendix P
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
Write (Hex/8) (Sequence No. 525 (Hex 020D))
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
+3
+4
+5
+6
~
Number of send data words
Number of Heads
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
~
(Undefined)
Not used
Write data
+8
+9
~
+15
+16
+17
+18
+19
+20
~
+22
~
+100
+101
+102
+103
+104
~
+106
Not used
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
(Undefined)
(Undefined)
(Undefined)
Unit No.
Head CH No.
Leading address No.
Number of write digits
Write data
(Undefined)
Write data
Write data
~
~
~
~
CH 1
CH 2
CH 8
+0
+1
Offset
+(14(N–1)+2)
+(14(N–1)+3)
Contents (data format)
Number of send data words
(4 digits Hex)
Number of Heads
(4 digits Hex)
Unit No. (2 digits BCD)
R/W Head CH No.
(1 digit BCD)
Data
0007 to 006B (7 to 107 decimal)
0001 to 0004
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
0000 to FFFF +(14(N–1)+4)
+(14(N–1)+5)
Leading address No.
(4 digits Hex)
Number of write digits
(4 digits Hex)
+(14(N–1)+6) to
(14(N–1)+8)
Write data (Hex)
N: Number of Heads
0002 to 000A (2 to 10 decimal)
Input in hexadecimal code
Up to 10 digits (max.) can be set
717
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Write data designated for hexadecimal is sent beginning with the largest offset from the send data words.
2.
Always set an even number of digits for the write data.
Auto-write (ASCII/1) (Sequence No. 526 (Hex 020E))
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 518 (Write (ASCII/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 518 (Write (ASCII/1)).
Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Auto-write (Hex/1) (Sequence No. 527 (Hex 020F))
This sequence is used when the number of Heads to be written to the Carrier is 1.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 522 (Write (Hex/1)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 522 (Write (Hex/1)).
Note For auto-write (AW), a response is not returned if the number of Heads is not written by the Carrier, the
Abort Bit must be turned OFF to terminate the sequence.
Polling Auto-write (ASCII/2) (Sequence No. 528 (Hex 0210))
This sequence is used when the number of Heads to be written to the Carrier is 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (ASCII/2) (Sequence No. 529
(Hex 0211))
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 118 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 519 (Write (ASCII/2)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
718
V600/V620 ID Controller Protocol
Appendix P
Note 1.
Execute Sequence No. 528 before executing Sequence No. 529.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (ASCII/4) (Sequence No. 530 (Hex 0212))
This sequence is used when the number of Heads to be written to the Carrier is 4.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)).
Note Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling autowrite.
Polling Auto-write Subcommand (ASCII/4) (Sequence No. 531
(Hex 0213))
This sequence is used when the number of Heads to be written to the Carrier is 4. Up to 48 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 520 (Write (ASCII/4)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 530 before executing Sequence No. 531.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (ASCII/8) (Sequence No. 532 (Hex 0214))
This sequence is used when the number of Heads to be written to the Carrier is 8.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (ASCII/8) (Sequence No. 533
(Hex 0215))
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 20 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 521 (Write (ASCII/8)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
719
V600/V620 ID Controller Protocol
Appendix P
Note 1.
Execute Sequence No. 532 before executing Sequence No. 533.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hex/2) (Sequence No. 534 (Hex 0216))
This sequence is used when the number of Heads to be written to the Carrier is 2.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hex/2) (Sequence No. 535
(Hex 0217))
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 56 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 523 (Write (Hex/2)). However, the leading address No., number of write digits, and write data are not used and become undefined.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 534 before executing Sequence No. 535.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hex/4) (Sequence No. 536 (Hex 0218))
This sequence is used when the number of Heads to be written to the Carrier is 4.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hex/4) (Sequence No. 537
(Hex 0219))
This sequence is used when the number of Heads to be written to the Carrier is 2. Up to 24 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 524 (Write (Hex/4)). However, the leading address No., number of write, and write data are not used and become undefined.
720
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 536 before executing Sequence No. 537.
2.
Retry processing is not performed for this sequence.
Polling Auto-write (Hex/8) (Sequence No. 538 (Hex 021A))
This sequence is used when the number of Heads to be written to the Carrier is 8.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)).
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)).
Note 1.
Execute Sequence No. 545 (Polling Auto-write Command Processing Cancel) to cancel the polling auto-write.
2.
Retry processing is not performed for this sequence.
Polling Auto-write Subcommand (Hex/8) (Sequence No. 539
(Hex 021B))
This sequence is used when the number of Heads to be written to the Carrier is 8. Up to 10 digits of data can be written for each Read/Write Head.
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 525 (Write (Hex/8)). However, the leading address No., number of write, and write data are not used and become undefined.
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Note 1.
Execute Sequence No. 538 before executing Sequence No. 539.
2.
Retry processing is not performed for this sequence.
Data Check (Sequence No. 540 (Hex 021C))
This sequence writes and verifies the CRC code for check blocks designated by the user.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
+4
+5
Number of send data words
(Undefined)
Unit No.
(Undefined)
Head CH No.
Processing designation
(Undefined)
Leading address of check object
(Undefined)
Number of check block bytes
721
V600/V620 ID Controller Protocol
Appendix P
Offset Contents (data format)
+0
+1
+2
+3
+4
+5
Data
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0006 (fixed)
R/W Head CH No.
(1 digit BCD)
Processing designation
(2 digits Hex)
Leading address of check object
(4 digits Hex)
Number of check block bytes
(2 digits Hex)
00 to 07 (CD1D)
00 to 15 (CA2A)
R/W Head CH 1 designation:1
R/W Head CH 2 designation:2
The CD1D must be set to 1.
Verification: 43 (C)
Calculation: 4B (K)
Management of number of write times: 4C (L)
0000 to FFFF
(If management of number of write times is designated, H’
@@@0 to H’ @@@5 or H’ @@@8 to H’
@@@D)
If verification, calculation is designated:
03 to FF (set 00 for 256 bytes)
If management of number of write times is designated:
00 to FF
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Completion code
Offset Contents (data format)
+0
+1
Number of receive data words (4 digits Hex)
Completion code
(2 digits Hex)
0002 (fixed)
Data
(Verification, calculation designation)
00: Normal completion for calculation processing
75: Data in normal condition for verification processing
76: Error Data alarm for verification processing
(If management of number of write times is designated)
75: Number of write times is under those which is specified
76: alarm for number of write times is over those which is specified.
Note If L (management of number of write times) is designated by processing designation, management of number of write times for Data Carrier of EEPROM is performed.
Control (Sequence No. 541 (Hex 021D))
This sequence performs I/O operations or I/O reads.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined)
Unit No.
+2 (Undefined)
OUT1 operation OUT2 operation
Offset
+0
+1
+2
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
OUT1 operation (1 digit BCD)
OUT2 operation (1 digit BCD)
0003 (fixed)
00 to 07 (CD1D)
0: No operation
1: turned ON
2: turned OFF
0: No operation
1: turned ON
2: turned OFF
Data
722
V600/V620 ID Controller Protocol
Appendix P
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
Current input status
Output status after operation
+0
Offset
+1
Leftmost 1 byte
Contents (data format)
Number of receive data words
(4 digits Hex)
Current input status
Leftmost 4 bits: IN1 operation
Rightmost 4 bits: IN2 operation
Output status after operation
Leftmost 4 bits: OUT1 operation
Rightmost 4 bits: OUT2 operation
0002 (fixed)
1: ON status
0: OFF status
1: ON status
0: OFF status
Note 1.
The V600/620-CA
@A does not support this command.
2.
This sequence executes the equivalent of the CONTROL command.
Data
Error Information Read (Sequence No. 542 (Hex 021E))
This sequence reads information from the latest error log.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
Number of send data words
+1 (Undefined) Unit No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
00 to 07 (CD1D)
Data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+75
Number of receive data words
Error log
Error log
~
+0
Offset
+1 to +75
Contents (data format)
Number of receive data words
(4 digits Hex)
Error log (ASCII)
Data
0004 to 004C (4 to 76 decimal)
One item of data is stored with 5 characters of generated command, generated Head No., generated error code.
Note 1.
The V600/620-CA
@A does not support this command.
2.
Up to 30 error records can be stored.
3.
The most resent error records are stored first.
Command Processing Cancel (Sequence No. 543 (Hex 021F))
This sequence cancels command processing except for polling command processing. The command waiting status is entered.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
Number of send data words
(Undefined) Unit No.
723
V600/V620 ID Controller Protocol
Appendix P
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
0002 (fixed)
Data
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Unit No.
Offset Contents (data format)
+0
+1
Number of receive data words (4 digits Hex)
Completion code
(2 digits Hex)
0002 (fixed)
Data
00: Normal termination
14: Auto or communications command processing not executed
75: Cancelled before the end of expansion command receive or before sync input went active or before detection of the existence of Data Carrier
76: Cancelled during read/write processing for Data
Carrier
Polling Auto-read Command Processing Cancel
(Sequence No. 544 (Hex 0220))
This sequence cancels polling auto-read processing.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
+0 data
+1
+2
+3
Number of send data words
(Undefined)
(Not used)
Unit No.
(Undefined)
Head channel No.
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Unit No. (2 digits BCD)
Data
0004 (fixed)
Arbitrary (However, there is a limit for the maximum Unit No. depending on the model)
+2
+3
Not used
R/W Head CH No. (1 digit BCD) R/W Head CH 1 designation: 1
R/W Head CH 2 designation: 2
The CD1D must be set to 1.
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
Number of receive data words
(Undefined) Completion code
Offset Contents (data format)
+0
+1
Number of receive data words (4 digits Hex)
Completion code
(2 digits Hex)
0002 (fixed)
Data
75: Cancelled before communications processing with
Data Carrier
76: Cancelled after communications processing with
Data Carrier
724
V600/V620 ID Controller Protocol
Appendix P
Polling Auto-write Command Processing Cancel (Sequence
No. 545 (Hex 0221))
This sequence cancels polling auto-write processing
Send Data Word Allocation (3rd Operand of PMCR(260))
The send data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing
Cancel)
Receive Data Word Allocation (4th Operand of PMCR(260))
The receive data word allocation is similar to that of Sequence No. 544 (Polling Auto-read Command Processing Cancel)
General-purpose Command (Sequence No. 546 (Hex 0222))
This sequence transmits arbitrary data and stores receive data to the receive data words. The characters “@”,
FCS (terminator) are not required in the send data words and receive data words. These characters will be automatically added for transmission and automatically removed before saving data.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send data
+0
+1
+2
~
+249
Number of send data words
Send data byte length
Send data
Send data
~
Offset
+0
+1
Contents (data format)
Number of send data words
(4 digits Hex)
Send data byte length
(4 digits Hex)
+2 to
+249
Send data (ASCII)
Data
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
The number of bytes in the send data except for @, the FCS, and the terminator.
Input send data up to 496 characters (max.) in ASCII
Receive Data Storage Word Allocation (4th Operand of PMCR(260))
Receive data storage words
+0
+1
~
+249
Number of receive data words
Receive data
Receive data
~
Offset
+0
+1 to
+249
Contents (data format)
Number of receive data words
(4 digits Hex)
Receive data
(ASCII)
Data
0002 to 00FA (2 to 250 decimal)
Receive data is stored in ASCII.
Up to 498 characters (max.)
725
Appendix Q
Hayes Modem AT Command Protocol
The Hayes Modem AT Command Protocol is used to make various settings or control remotely a Hayes modem connected to the Serial Communications Unit/Board via RS-232C cable.
Protocol Configuration
The configuration of the Hayes Modem AT Command Protocol is shown below.
Sequence
No.
Communications sequence name
Function
550 (0226) Initialize modem
(general-purpose)
Ladder interface
Send word allocation
Yes
Receive word allocation
No
Initialize modem
(specialized)
Initializes the modem connected to the
Serial Communications Unit/Board. The initialization command is set in the words specified for the second operand of
PMCR(260).
Initializes certain OMRON Modems.
No No 560 (0230)
570 (023A)
580 (0244)
561 (0231)
571 (023B)
581 (0245)
Dial Yes No
552 (0228) Password
553 (0229) Data send/receive
(general purpose sequence)
554 (022A) Escape
555 (022B) Hang up
562 (0232)
572 (023C)
582 (0246)
Initialize and dial
590 (024E) Escape to hang up
Dials from the modem connected to the
Serial Communications Unit/Board. AT commands and telephone numbers are set set in the words specified for the 3rd operand of PMCR(260). This sequence can be used only for certain OMRON modems.
After the line is connected, the password sent from the other exchange is verified to confirm that the line is connected to the desired exchange. The normal value of a password is set in the words specified for the 3rd operand of PMCR(260).
Sends arbitrary data to the exchange which the line is connected. Send data is set in the words specified for the 2nd operand of
PMCR(260). Receive data is stored in the words specified for the fourth operand of
PMCR(260).
Shifts the modem to escape mode (the condition in which command input is available during data communications). The escape code is fixed to “+++”
After shifting to escape mode, the line is disconnected.
Executes continuously from initialization to dialling operations for certain OMRON
Modems.
Executes continuously from shifting to the escape mode to hanging up.
Yes
Yes
No
No
Yes*
1
No
No
Yes
No
No
No
No
Note 1.
Refer to sequences No. 561, No. 571, and No. 581 for dialing operations.
2.
Ladder Interface Settings
YES: User settings are required for the 3rd and 4th operands of PMCR(260).
NO:
Send word allocation: Set the constant 0000 for the 3rd operand (S).
Receive word allocation: Set the constant 0000 for the 4th operand (D).
3.
The hexadecimal equivalents of sequences numbers are given in parentheses.
727
Hayes Modem AT Command Protocol
Connections
The connections when using the Hayes Modem AT Command Protocol is shown below.
RS-232C Connection
Serial Communications Board
(CS Series only)
Serial Communications Unit
(CS/CJ Series)
Modem
Telephone line
Modem
Appendix Q
Modem: D-sub
25-pin (female)
FG
SD
RD
RTS
CTS
DSR
SG
CD
Serial Communications Board/Unit
D-sub 9-pin (female)
FG
SD
RD
RTS
CTS
5V
DSR
DTR
SG
1
5
6
9
ST2
RT
DTR
CI
ST1
Compatible Modems
Although most of the sequences in this protocol can be used regardless of modem, the sequences Initialize
Modem (specialized) and Dial sequences can be used only for the following Modems:
• MD24FB10V (OMRON Modem)
• MD144FB5V (OMRON Intelligent Modem)
• ME1414BIII, ME2814BII (OMRON FAX/DATA Modem)
For other modems, create a modem initialization sequence using the general-purpose Initialize Modem sequence and dial using the Data Communications Sequence (Sequence No. 553).
728
Hayes Modem AT Command Protocol
Appendix Q
Modem Settings
When this protocol is used, it is required that the modem connected to the Serial Communications Unit/Board be initialized to the following conditions:
Command echo
Result code display format
Speed display, busy/dialling tone detection at connection
Error correction data compression display
MNP setting
MNP class setting
V.42 compression, Error correction
Flow control between terminal modems
ER signal control
Escape code
No
Numeric format
Baud rate display enabled, busy and dialling tone detection enabled.
Error correction/data compression display enabled
Error correction provided (auto-reliable mode)
MNP class 4
Not enabled
Not enabled
Always ON
+
Note 1.
It is recommended that, in addition to the above settings, the abort timer should be set so that communications are cut off if a communications error happened due to incidents such as cable disconnection between the Serial Communications Unit/Board and modem. The abort timer is set to 10 minutes for the modem initialization (specialized) (Sequences No. 560, No. 570, No. 580: Initialize
Modem (Specialized)). Refer to modem’s manual for further information about abort timers.
2.
The data format of the modem (baud rate, data length, parity, stop bit) is set by AT commands issued from a device connected to the modem. Its settings should conform to communications conditions of the device which issues AT commands. Therefore when communications are made between the modem and Serial Communications Unit/Board, it is required that communications conditions should be set by issuing AT commands from the Serial Communications Unit/Board.
3.
Modem settings become invalid if the power supply is turned off and must be set again. However, a memory backup function can be used to protect settings so that even after the power supply to the modem is turned off, it can communicate with the previous setting conditions.
For Initialize Modem (specialized), the modem initialization command is built in as message data. However, for
Initialize Modem (general-purpose), the command must be specified in the send data for PMCR(260).
OPR 1
OPR 2
OPR 3
OPR 4
(Communications port settings)
#0226 (Sequence No. 550)
Address for first word containing initialization command character string S
None (Set #0000)
S+0
S+1
S+2
:
S+n
Number of words from address set for operand 2 to end of data 4 digits Hex
Number of bytes for send data (initialization command) 4 digits Hex
Send data (initialization command)
(Fill data to left for odd numbers of bytes)
ASCII
Setting Example for Modem Initialization Command
• MD24FB10V Using Sequence #550 (OMRON)
The following command is set in the words specified by the 3rd operand of PMCR(260).
ATE0V0X4\V2\N3%C0*C0\X1&M0S26=10
0012 0020
A T E 0 V 0 X 4 \ V 2 \ N 3 % C 0 * C 0 \ X 1 & M 0 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
Note Turn ON pin 4 of DIP switches SW3 on for this Modem (ER signal always ON).
729
Hayes Modem AT Command Protocol
Appendix Q
MD144FB5V (OMRON, No longer manufactured.)
The following command is set in the words specified by the second operand of PMCR(260).
ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10
0017 0029
A T E 0 V 0 X 4 \ V 2 \ N 3 % C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9 6 0 0 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
ME1414BIII/ME2814BII (OMRON)
The following command is set in the words specified by the second operand of PMCR(260).
AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10
0018 002C
A T \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 % C 0 & D 0 & E 0 \ X 1 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
Note Turn ON DIP switch SW3 on in the rear of the Modem.
Dialling (Sequences No. 561 (Hex 0231), No. 571 (Hex 023B), and
No. 581 (Hex 0245))
To dial a telephone numbers for the OMRON ME1414BIII/ME2814BII Modems using sequences No. 561, 571,
581, set the dialling command and telephone number in the words specified by the 3rd operand of PMCR(260).
However, for other Modems, make the following settings for the Data Communications sequence.
This is an example of telephone number settings for the above mentioned 4 OMRON Modems.
Operand and Send Data Word Settings of PMCR(260)
OPR 2
OPR 3
OPR 4
MD24FB10V #0231
MD144FB5V #023B
ME1414BIII/ME2814BII #0245
First address S of send data (dialling operation)
None (Set #0000)
S+0
S+1
S+2
:
S+n
Setting Example
If telephone number is 03-0123-4567
Number of words from address set for operand 2 to end of data 4 digits Hex
Number of bytes of send data (dialling operation) 4 digits Hex
Send data (dialling operation)
(Fill data to left for odd numbers of bytes)
ASCII
000A 0010 4154
A T
4454 3033 2D30 3132 332D 3435 3637
D T 0 3 – 0 1 2 3 – 4 5 6 7
Character string length of dialling operation sent to modem (bytes)
Code length of PMCR(260) when it is used (words)
Note 1.
This example uses a tone line. Change ATDT to ATDP for pulse lines.
2.
Fill the telephone number to the left in the words if the character string length of the dialling operation is an odd number of bytes.
730
Hayes Modem AT Command Protocol
Appendix Q
0008 000B 4154
A T
4454
D T
3031 2D32 3334 3500
0 1 – 2 3 4 5
#
Character string length of dialling operation sent to modem (bytes)
Code length of PMCR(260) when it is used (words)
Password Verification (Sequence No. 552 (Hex 0228))
A password can be verified by executing sequence No. 552 of this protocol. It is required to set in advance the value of the password in the words specified by the second operand of PMCR(260).
Operand and Send Data Word Settings of PMCR(260)
OPR 2
OPR 3
OPR4
#0228
Address of first word where the password is set S
None (Set #0000)
Setting Example
When password is OMRON-CO.
S+0
S+1
S+2
:
S+n
Number of words from address set for operand 3 to end of data 4 digits Hex
Number of bytes of comparison data (normal value of password)
4 digits Hex
Comparison value (password normal value)
(Fill data to left for odd numbers of bytes)
ASCII
0006 0008 4F4D 524F 4E2D 434F
O M R O N – C O
Character string length of password sent to modem (bytes)
Code length of PMCR(260) when it is used (words)
731
Hayes Modem AT Command Protocol
Password Verification Operation
The number of retries is 3 for password verification.
PLC
Password verification
(starting #552)
Appendix Q
Personal computer
(remote exchange)
Dispatching character string
(Retry up to 3 times)
Receiving password
Verifying password
"Password: "
Password
Receiving character string
Issuing password
Verification result
Terminating process
When Protocol Macro Execution Flag turns ON:
Port 1: CIO 190915 for the Serial Communications Board and CIO 1500 + 25 x unit number
+9, bit 15 for Serial Communications Units.
Port 2: CIO 191915 for the Serial Communications Board and CIO 1500 + 25 x unit number
+19, bit 15 for Serial Communications Units.
Data Send/Receive (Sequence No. 553 (Hex 0229))
Data Send/Receive can be executed using sequence No. 553. The send data sent to another exchange is set in the words specified by the 3rd operand of PMCR(260). Data received by the PLC is stored in the words specified by the 4th operand of PMCR(260).
Operand and Send/Receive Data Word Settings of PMCR(260)
OPR 2
OPR 3
OPR 4
#0229
First address C1 of the words where send data is set
First address C2 of the words where receive data is stored
C1+0
C1+1
C1+2
:
C1+n
• Send Data Words
Number of words from address set for operand 2 to end of data 4 digits Hex
Number of bytes of send data
Send data (dialling operation)
(Fill data to left for odd numbers of bytes)
4 digits Hex
ASCII
C2+0
C2+1
:
C2+n
• Receive Data Storage Words
Number of bytes of receive data
Receive data (dialling operation)
(Fill data to left for odd numbers of bytes)
4 digits Hex
ASCII
732
Hayes Modem AT Command Protocol
Appendix Q
Setting Example
When send data is THIS IS SAMPLE.
0009 000E 5448
T H
4953 2049 5320 5341 4D50 4C45
I S I S S A M P L E
Character string length of send data sent to modem (bytes)
Code length of PMCR(260) when it is used (words)
A maximum of 200 bytes (including the CR) can be received. When the received data is RETURN OK, the content stored in the receive words is as follows:
0006 5245
R E
5455 524E 204F 4B00
T U R N O K
Length of received character string (words)
Note An error will occur is the reception data is not received within 90 seconds after the data is sent.
Escape Mode (Sequence No. 554 (Hex 022A))
Shifting to the escape mode can be made using sequence No. 554. No setting is necessary for this sequence.
Note The character string to shift the online mode to the escape mode (i.e., the escape code) is ‘+’ for modem settings.
Hang Up Command (Sequence No. 555 (Hex 022B))
The hang up command (to disconnect the line) can be executed using sequence No. 555. No setting is necessary for this sequence.
Communication Errors
Three result codes are monitored after an AT command is sent to the modem. When a result code is returned, it will be checked. If the code is not the normal result code (“OK”, “CONNECT 9600/REL4”, “CONNECT 2400/
REL4”, in words), after a fixed time of waiting to send, the following retry processing will be repeated 2 times to send the AT command again and waiting for another result code.
The receive monitoring time and send wait time for each sequence are shown below.
Sequence name Sequence
No.
550 (0226)
560 (0230)
570 (023A)
580 (0244)
561 (0231)
571 (023B)
581 (0245)
552 (0228)
553 (0229)
554 (022A)
555 (022B)
562 (0232)
572 (023C)
582 (0246)
590 (024E)
Initialize modem (general-purpose)
Initialize modem (specialized)
Dial
Password
Data send/receive (general-purpose)
Escape
Hang up
Initialize and dial
Escape and hang up
Receive monitoring time
10 s
10 s
90 s
None
90 s
10 s
10 s
90s
10 s
Send wait time for retries
1 s
1 s
90 s
3 s
None
1.5 s (after first try)
1.5 s (after first try)
Initializing: 1 s
Dialling: 90 s
1.5 s (after first try)
Note The hexadecimal equivalents of sequences numbers are given in parentheses.
733
Appendix R
Changing Communications Port Settings
Using STUP(237)
The STUP(237) instruction can be used to change the serial communications mode, communications specifications, and other settings for each port of the Serial Communications Board/Unit during CPU Unit operation.
Executing the STUP(237) Instruction
Use the STUP(237) instruction to change the communications port settings. For example, the STUP(237) instruction can be used to switch the protocol to Host Link mode without leaving RUN mode and allow the user to monitor and program the CPU Unit from the host computer when the specified conditions are met while communications sequences for modem and line connections are being executed in protocol macro mode.
STUP(237) Instruction Specifications
Control data (serial port number, remote unit address)
First words of port settings
Control Data (C)
Serial port number Remote unit address
Set the following items.
Serial Port Number
Set the serial port number (physical port number) of the Serial Communications Board or Unit to which the remote node is connected. PORT1: 1 (hex)/PORT2: 2 (hex)
Remote Unit Address
Specify the unit address of the Serial Communications Board/Unit for which the serial port is to be changed.
Serial Communications Board: E1 (hex)
Serial Communications Unit: Unit number + 10 (hex)
Setting: 10 to 1F (hex)
Note The CPU Bus Unit number (0 to F) is set using the rotary switch on the front panel of the Unit.
First Word of Port Settings (S)
Set the address of the first word containing the serial port settings. The data is stored starting from word S in the say way as the port settings in the 10-word area allocated in the DM Area for each port. For details on the
Setup Area, see 2-3 I/O Memory Allocations or 4-2, 5-2, 6-2, and 7-2 Setup Area Allocations.
00
S
S+1
15
Serial port system setting
10 words per port
S+9
When the STUP(237) instruction is executed, the CPU Unit changes the contents of the relevant DM Area in the Unit, then automatically turns ON the Port Settings Change Bit (words A620 to A635) in the Auxiliary Area.
A620 + unit number
Port 1 Port Settings Change Bit: Bit 1
Port 2 Port Settings Change Bit: Bit 2
735
Changing Communications Port Settings Using STUP(237)
Appendix R
When the cyclic service finishes changing the communications port settings in the Serial Communications
Board or Unit, the Board or Unit automatically restarts the port and turns OFF the Port Settings Change Bit.
Data Contents
Area
CIO Area
Work Area
Holding Area
Auxiliary Area
Timer Area
Counter Area
Data Memory (DM) Area
Extended Data Memory (EM) Area
Extended Data Memory (EM) Area
(including bank specification)
Indirect DM/EM address, Binary
Indirect DM/EM address, BCD
Constants
Data Registers
Index Registers, Direct
Index Registers, Indirect
C
0000 to 6143
W000 to W511
H000 to H511
A000 to A959
T0000 to T4095
C0000 to C4095
D00000 to D32767
E00000 to D32767
En_00000 to En_32767 (n = 0 to C)
S
0000 to 6134
W000 to W502
H000 to H502
A000 to A950
T0000 to T4086
C0000 to C4086
D00000 to D32758
E00000 to E32758
En_00000 to En_32758 (n = 0 to C)
@D00000 to @D32767, @E00000 to @E32767, @En_00000 to @En_32767
*D00000 to *D32767, *E00000 to *E32767, *En_00000 to *En_32767
See Control Data (C).
DR0 to DR15
#0000 to FFFF (Binary data)
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047,IR15
DR0 to DR15 ,IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to ,–(– –)IR15
Error Flags (ER)
The Error Flag will turn ON in the following cases:
• The data specified in S is outside the allowable range.
• The Port Settings Change Bit is already ON when the instruction is executed.
Ladder Program Example
When CIO 000000 turns ON, the settings for port 2 for the Serial Communications Board will be changed to the values set in the 10 words from D00200 to D00209. In the following example, the protocol is changed to Host
Link mode.
Ladder Program
000000
@STUP
#02E1
D00200
736
Changing Communications Port Settings Using STUP(237)
Appendix R
Settings
S:
S+1:
S+2:
S+3:
S+9:
:
D00200 0500
D00201 0000
D00202 0000
D00203 0000
Port setting: Defaults
Protocol mode: 1 hex (Host Link)
Baud rate: Default (9,600 bps)
Transmission delay time: 0 ms
CTS control: None
Unit number: 00
D32010
D32011
D32012
D32013
Transmit
0500
0000
0000
0000
Settings for port 2 of Serial Communications Board
(D32010 to D32019)
D32019
Note STUP(237) transfers 10 words of data from the DM Area Setup Area. When using the Modbus-RTU slave mode, the Setup Area is expanded. Before executing STUP(237), use MOV(021) or other instructions to write the Modbus-RTU settings directly to the DM Area Setup Area for the Serial Communications Board/Unit. Doing so will allow STUP(237) to transfer all of the expanded DM Area Setup Area to the Serial Communications Board/Unit.
Serial
Communications
Board/Unit
3) STUP(237) writes the settings to the Board/Unit.
Setup in DM Area
2) Execute STUP(237).
Port 1 Settings
Port 1 setting data
Port 2 Settings
Port 1 Settings for Modbus-
RTU Slave
Port 1 Settings for Modbus-
RTU Slave
Port 1 setting data for Modbus-RTU slave
1) Move setting data using
MOV(021) or other instruction.
737
Numerics
1 1 NT Link
,
1 N NT Link
,
Auxiliary Area allocations
,
CIO Area allocations
,
commands
,
connecting Programmable Terminals
,
connection example
,
CPU Bus Unit Area allocations
,
errors
,
executing communications
,
Inner Board CIO Area allocations
,
Inner Board error information
,
overview
,
Setup Area allocations
,
Status Area allocations
,
2-wire and 4-wire connections, transmission circuits
,
2-wire or 4-wire switch
,
3Z4L Laser Micrometer
,
connections
,
protocols, sequences
,
A
Abort Flag
,
Abort Switch
,
Access Error Flag
,
Auxiliary Area allocations
1 N NT Link
,
Host Link
,
protocol macro
,
bits
,
B
B500-AL001-E Link Adapter
,
Backplanes applicable Backplanes
,
Bar Code Readers
,
baud rate
Host Link
,
protocol macro
,
Board/Unit Watchdog Timer Error Flags
,
Index
C
C200H Communications Boards
,
C200H Host Link Units
,
C200HX/HG/HE Communications Board changes in communications specifications
,
cables preparation
,
CIO Area
,
allocations
,
1 N NT Link
,
Host Link
,
loopback test
,
protocol macro
,
Serial Communications Boards
,
Serial Communications Units
,
CPU Bus Unit Area allocations
1 N NT Link
,
Host Link
,
protocol macro
,
Inner Board Area allocations
1 N NT Link
,
Host Link
,
protocol macro
,
Status Area allocations
1 N NT Link
,
Host Link
,
protocol macro
,
cleaning
,
CMND(490) instruction
,
C-mode commands
,
commands
CONTROLLER DATA READ 05 01
,
,
,
communications distance
Host Link
,
protocol macro
,
communications modes
,
1 communications modes. See 1 N NT Link Host Link Loop-
back Test protocol macro serial communications modes
Communications Port Completion Codes
,
Communications Port Enabled Flags
,
Communications Port Error Flags
,
Communications Sequence No.
,
communications sequences
,
communications timing
,
commands addressed to host computer
,
comparison
739
740
previous products
,
CompoWay/F Master command and response formats
,
communications specifications
,
connections
,
message frames
,
protocols
,
sequences
,
transmission procedure
,
CompoWay/F protocol
,
connectors connector hoods
,
cover dimensions
,
pin layout
RS-232C ports
,
RS-422A/485 ports
,
wiring
,
CONTROLLER DATA READ 05 01
,
CPU Bus Unit Area allocations
,
1 N NT Link
,
Host Link
,
protocol macro
,
CPU Bus Unit DM Area
,
CPU Units supporting CPU Units
,
CS1 CPU Bus Unit Restart Bits
,
CS1 CPU Bus Units
,
CS1 Expansion Racks
,
CS1W-SCB21 Serial Communications Board
,
specifications
,
CS1W-SCB41 Serial Communication Board
,
specifications
,
CS1W-SCU21 Serial Communications Unit
,
specifications
,
C-series Host Link Units changes in communications specifications
,
C-series Units changes in communications specifications
,
CTS control
,
current consumption
,
CVM1 Units changes in communications specifications
,
CV-series Units changes in communications specifications
,
CX-Protocol
,
Index
D
dimensions
Serial Communications Boards
,
Serial Communications Units
,
DM Area allocations
,
Serial Communications Boards
,
Serial Communications Units
,
E
E5_J Temperature Controller
,
connections
,
protocols sequences
,
E5_K Digital Controller
,
connections read
,
write
,
read protocols sequences
,
E5ZE Temperature Controller
,
connections read
,
write
,
read protocols sequences
,
write protocols sequences
,
EC Directives
,
EMC Directives
,
EMI measures
,
error check codes
Host Link
,
error codes
,
troubleshooting
,
Error Flag
,
error log specifications
,
table configuration
,
EEPROM
,
RAM
,
reading and clearing
,
,
,
error responses
,
errors
1 N NT Link
,
framing error
,
Host Link
,
overrun error
,
parity error
,
protocol macro
,
troubleshooting
,
ES100 Digital Controller connections
,
ES100_ Digital Controller
,
protocols sequences
,
Executed Reception Case No. (code)
,
Executed Reception Case No. Flag
,
Executed Step No. (code)
,
Executed Step No. Flag
,
external dimensions connector cover
,
F
F200/F300/F350 Visual Inspection Unit
,
ferrite cores
,
FINS commands
,
framing errors
,
H
Hayes Modem AT Command
,
compatible modems
,
connections
,
protocols sequences
,
heat-shrinking tubes
,
Host Link
,
Auxiliary Area allocations
,
CIO Area allocations
,
commands
,
communications timing
,
connection example
,
CPU Bus Unit Area allocations
,
error responses
,
errors
,
executing communications
,
host-initiated communications
,
Inner Board CIO Area allocations
,
Inner Board error information
,
PLC-initiated communications
,
ports
,
Index
connections
,
reception buffers
,
Setup Area allocations
,
system configuration
,
unit numbers
,
Host Link Units changes in communications specifications
,
I
I/O memory allocations
,
I/O tables
,
indicators
CPU Unit
,
error displays
Serial Communications Boards
,
Serial Communications Units
,
loopback test
,
Serial Communications Boards
,
Serial Communications Units
,
Inner Board CIO Area allocations
,
1 N NT Link
,
Host Link
,
protocol macro
,
Inner Board DM Area
,
Inner Board Restart Bit
,
Inner Boards
,
error information
,
1 N NT Link
,
Host Link
,
protocol macro
,
Inner Bus Error Flag
,
inspection
,
installation
Serial Communications Boards
,
Serial Communications Units
,
Intelligent Signal Processors
,
K
K3T_ Intelligent Signal Processor
,
connections
,
protocols sequences
,
L
ladder programs
741
742
protocol macro
,
Link Adapters
,
loopback test
,
CIO Area allocations
,
connections
,
executing
,
indicators
,
port connections
,
procedure
,
protocol status
,
Setup Area allocations
,
Low Voltage Directive
,
M
maintenance cleaning
,
inspection
,
modem compatibility
,
settings
,
mounting height
,
N
noise reduction
,
NT Link ports
,
protocol status
,
NT Link commands
,
NT-AL001-E Link Adapter
,
DIP switch settings
,
O
operating environment precautions
,
overrun errors
,
P
parameters sequence
,
step
,
parity errors
,
PMCR(260) instruction
,
operand settings
,
specifications
,
Index
Port Settings Change Bits
,
1 N NT Link
,
Host Link
,
protocol macro
,
Serial Communications Boards
,
Serial Communications Units
,
Port Settings Changing Flag
,
precautions applications
,
general
,
installation
,
installing Serial Communications Boards
,
installing Serial Communications Units
,
noise reduction
,
operating environment
,
replacement
,
safety
,
system configuration
,
wiring
,
previous products comparison
,
Programmable Terminals
,
1 N NT Link connections
,
RS-232C port connections
,
Programming Console
,
Programming Devices
,
CX-Programmer
,
Programming Console
,
protocol macro
,
applications
,
Auxiliary Area allocations
,
CIO Area allocations
,
CPU Bus Unit Area allocations
,
errors
,
executing communications
,
functions
,
Inner Board CIO Area allocations
,
Inner Board error information
,
ladder programs
,
ports
,
protocol status
,
Setup Area allocations
,
Software Switches
,
specifications
,
standard system protocols
,
Status Area allocations
,
system configuration
,
time lag
,
Protocol Macro Error Code
,
Protocol Macro Executing Flag
,
Protocol Macro Execution Error Flag
,
protocol specifications
,
protocol status loopback test
,
NT Link
,
protocol macro
,
protocols
,
3Z4L Laser Micrometer sequences
,
CompoWay/F sequences
,
creating
,
E5_J Temperature Controller sequences
,
E5_K Digital Controller read sequences
,
E5ZE Temperature Controller read sequences
,
E5ZE Temperature Controller write sequences
,
ES100_ Digital Controller sequences
,
Hayes Modem AT Command sequences
,
K3T_ Intelligent Signal Processor sequences
,
Protocol Support Software list
,
structure
,
V500/V520 Bar Code Reader sequences
,
V600/V620 ID Controller sequences
,
Visual Inspection System sequences
,
PT Communications Execution Flag
,
PT Priority Registered Flag
,
PTs. See Programmable Terminals
,
R
reception buffers
,
reception case number
,
reception matrixes
,
RECV(098) instruction
,
Repeat Counter Setting Value
,
Reset Counter Present Value
,
Restart Bit
Serial Communications Boards
,
Index
Serial Communications Units
,
RS-232C connections
,
RS-232C ports
1 1 connections
,
1 N connections
,
changes from previous products
,
connector pin layout
,
direct connections
1 N NT Link
,
Programmable Terminals
,
host computer connections
,
Programmable Terminal connections
,
specifications
,
wiring
,
RS-422 connections
,
RS-422A/485 ports
1 1 connections
,
1 N connections
,
changes from previous products
,
connector pin layout
,
host computer connections
,
Programmable Terminal connections
,
specifications
,
wiring
,
RS-485 connections
,
S
send delay
,
SEND(090) instruction
,
Sequence Abort Completion Flag
,
Sequence End Completion Flag
,
sequence parameters
,
Sequence Wait Flag
,
sequences
CompoWay/F Master
Broadcast with ASCII Conversion, No Response
,
Broadcast with No Conversion and No Response
,
General-purpose Broadcast with No Conversion and
No Response
,
General-purpose Send with No Conversion and with
Response
,
Send with ASCII Conversion, with Response
,
Send with No Conversion and with Response
,
sequences, 3Z4L Laser Micrometer
3Z4L Clear
,
3Z4L Initialize (3000-series)
,
3Z4L Initialize (4000-series)
,
All Statistic Memory Clear (3000-series)
,
Automatic Detection List Request (3000-series)
,
743
744
Automatic Detection Release (3000-series)
,
Automatic Detection Set (3000-series)
,
AVG Move (H) Times Set (3000-series)
,
AVG Move (L) Times Set (3000-series)
,
AVG Move Interval Set (3000-series)
,
Calibration Release
,
Calibration Set
,
Continuous Measurement Start (Interrupt) (3000-series)
,
Continuous Measurement Start (Interrupt) (4000-series)
,
Continuous Measurement Start (Scan) (3000-series)
,
Continuous Measurement Start (Scan) (4000-series)
,
Continuous Measurement Termination (4000-series)
,
Data Request (3000-series)
,
Data Request (4000-series)
,
Deflection Measurement Start (4000-series)
,
E Unit Set
,
Forced Negative Zero (4000-series)
,
Forced Positive Zero (4000-series)
,
Forced Zero Release (4000-series)
,
Genera- purpose Command 2 (4000-series)
,
Genera-purpose Command 1 (4000-series)
,
Measurement Condition List Request (3000-series)
,
Measurement Condition List Request (4000-series)
,
Measurement Condition Release (3000-series)
,
Measurement Condition Release (4000-series)
,
Measurement Condition Set (3000-series)
,
Measurement Condition Set (4000-series)
,
Measurement Termination (3000-series)
,
Memory Switch Set
,
Memory Switch Set 1 (3000-series)
,
Memory Switch Set 2 (3000-series)
,
mm Unit Set
,
Program Number Set (3000-series)
,
Settings
,
Simple AVG Times Set (3000-series)
,
Single Run Measurement Start (3000-series)
,
Single Run Measurement Start (4000-series)
,
Statistic Processing Calculation Non-execution (3000-series)
,
Statistic Processing Execution (3000-series)
,
Statistic Processing Memory Clear (3000-series)
,
Statistic Result Request (3000-series)
,
Zero Run Measurement Start (3000-series)
,
sequences, E5_J Temperature Controller
General-purpose Read
,
General-purpose Write
,
Read Heater Current
,
Read Initial Status
,
Read Input Shift Value
,
Read Output Value
,
Index
Read Parameters 1
,
Read Parameters 2
,
Read Process Value
,
Read Set Point Limit
,
Save Set Point
,
Select Backup Mode
,
Select Local Mode
,
Select RAM Write Mode
,
Select Remote Mode
,
Write Input Shift Value
,
Write Parameters 1
,
Write Parameters 2
,
sequences, E5_K Digital Controller
Execute/Cancel AT
,
General-purpose Write
,
Genera-purpose Read
,
Read Alarm Hysteresis
,
Read Alarm Value
,
Read Control Period
,
Read Cooling Coefficient
,
Read Dead Band
,
Read Hysteresis
,
Read Input Digital Filter
,
Read Input Shift Limits
,
Read LBA Detection Time
,
Read Level 0 Parameters
,
Read Level 1 Parameters 1
,
Read Level 1 Parameters 2
,
Read Level 2 Parameters 1
,
Read Level 2 Parameters 2
,
Read Manual Reset Value
,
Read MV
,
Read MV at Stop Time and at PV Error
,
Read MV Limits
,
Read Process Value
,
Read Proportional Band, Integral Time, and Derivative
Time
,
Read Set Point
,
Read Set Point during SP Ramp
,
Read SP Ramp Time Unit and Set Value
,
Remote/Local
,
Run/Stop
,
Software Reset
,
Switch to Level 0 (Software Reset)
,
Switch to Level 1
,
Write Alarm Hysteresis
,
Write Alarm Value
,
Write Control Period
,
Write Cooling Coefficient
,
Write Dead Band
,
Write Hysteresis
,
Write Input Digital Filter
,
Index
Write Input Shift Value
,
Write LBA Detection Time
,
Write Level 0 Parameters
,
Write Level 1 Parameter 2
,
Write Level 1 Parameters 1
,
Write Level 2 Parameters 1
,
Write Level 2 Parameters 2
,
Write Manual Reset Value
,
Write MV at Stop Time and at PV Error
,
Write MV Limits
,
Write Proportional Band, Integral Time, and Derivative
Time
,
Write Set Point
,
Write SP Ramp Time Unit and Set Value
,
sequences, E5ZE Temperature Controller
Cancel Autotuning
,
Initialize Settings
,
Read Alarm Mode
,
Read Alarm Temperatures
,
Read Control Period
,
Read Cooling Coefficient
,
Read Dead Band/Overlap Band
,
Read Error Status
,
Read HB Alarm and HS Alarm Valid Channels
,
Read Heater Burnout and SSR Failure Detection Currents
,
Read Heater Current and SSR Leakage Current
,
Read Hysteresis
,
Read Input Shift Value
,
Read Manual Reset Value
,
Read Operation Status
,
Read Output Mode
,
Read Output Value Change Rate Limit
,
Read Output Value Limit
,
Read Output Values
,
Read Present Set Point
,
Read Process Value
,
Read Proportional Band, Integral Time, and Derivative
Time
,
Read Ramp Value
,
Read Set Point
,
Read Set Point, Process Value, and Output Value
,
Read Setting Unit
,
Save Settings
,
Start Autotuning
,
Start Control
,
Start Manual Operation
,
Stop Operation or Control
,
Write Alarm Mode
,
Write Alarm Temperature (Setting Unit 0.1)
,
Write Alarm Temperature (Setting Unit 1)
,
Write Control Period
,
Write Cooling Coefficient
,
Write Dead Band/Overlap Band
,
Write HB and HS Alarm Valid Channels
,
Write Heater Burnout and SSR Failure Detection Current
,
Write Hysteresis
,
Write Input Shift Value
,
Write Manual Output Value
,
Write Manual Reset Value
,
Write Output Mode
,
Write Output Value Change Rate Limit
,
Write Output Value Limit
,
Write Proportional Band, Integral Time, and Derivative
Time
,
Write Ramp Value
,
Write Set Point (Setting Unit 0.1)
,
Write Set Point (Setting Unit 1)
,
Write Setting Unit
,
sequences, ES100_ Digital Controller
Auto Mode
,
Cancel A.T.
,
Change Bank No.
,
Change Pattern No.
,
Execute A.T.
,
External Setting Mode
,
General-purpose Command
,
Local Setting Mode
,
Manual Mode
,
Read Adjustment Parameters
,
Read Control Monitor Data
,
Read Controller Status
,
Read Error Detection Data
,
Read Event Data
,
Read Heater Burnout Data
,
Read Local SP
,
Read MV Data
,
Read PID Control Parameters 1
,
Read PID Control Parameters 2
,
Read Program Parameters
,
Read PV Data
,
Read SP Data
,
Read Time Signal
,
Remote Setting Mode
,
Reset (Stop)
,
Run Command
,
Write Adjustment Parameters
,
Write Local SP
,
Write PID Control Parameters 1
,
Write PID Control Parameters 2
,
Write Program Parameters
,
sequences, Hayes Modem AT Command
Data Send/Receive (General-purpose)
,
745
746
Dial
,
Escape
,
Escape to Hang Up
,
Hang Up
,
Initialize and Dial
,
Initialize Modem (Specialized)
,
Password
,
Set Modem (General-purpose)
,
sequences, K3T_ Intelligent Signal Processor
General-purpose Command
,
Model Data Read (by Unit Number)
,
Model Data Read (Continuous Units)
,
Read Display Value (PV) (by Unit Number)
,
Read Display Value (PV) (Continuous Units)
,
Read Holding Data
,
Read Holding Data BH (Continuous Units)
,
Read Holding Data PH (Continuous Units)
,
Read Set Value (by Unit Number)
,
Read Set Value H (Continuous Units)
,
Read Set Value H with Bank (Continuous Units)
,
Read Set Value HH (Continuous Units)
,
Read Set Value HH with Bank (Continuous Units)
,
Read Set Value L (Continuous Units)
,
Read Set Value L with Bank (Continuous Units)
,
Read Set Value LL (Continuous Units)
,
Read Set Value LL with Bank (Continuous Units)
,
Read Set Value O1 with Bank (Continuous Units)
,
Read Set Value O2 with Bank (Continuous Units)
,
Read Set Value O3 with Bank (Continuous Units)
,
Read Set Value O4 with Bank (Continuous Units)
,
Read Set Value O5 with Bank (Continuous Units)
,
Read Set Value with Bank (by Unit Number)
,
Reset (by Unit Number)
,
Reset Control (Continuous Units)
,
Write Set Value (by Unit Number)
,
Write Set Value H (Continuous Units)
,
Write Set Value H with Bank (Continuous Units)
,
Write Set Value HH (Continuous Units)
,
Write Set Value HH with Bank (Continuous Units)
,
Write Set Value L (Continuous Units)
,
Write Set Value L with Bank (Continuous Units)
,
Write Set Value LL (Continuous Units)
,
Write Set Value LL with Bank (Continuous Units)
,
Write Set Value O1 with Bank (Continuous Units)
,
Write Set Value O2 with Bank (Continuous Units)
,
Write Set Value O3 with Bank (Continuous Units)
,
Write Set Value O4 with Bank (Continuous Units)
,
Write Set Value O5 with Bank (Continuous Units)
,
Write Set Value with Bank (by Unit Number)
,
sequences, V500/V520 Bar Code Reader
BCR Connection Confirmation (V500)
,
Index
BCR Function Read (V500)
,
BCR Initialize (V500)
,
BCR Read Start
,
BCR Read Stop
,
Complete Data Read
,
Data Continuous Read (Interrupt) (V500)
,
Data Continuous Read (Interrupt) (V520)
,
Data Continuous Read (Scan) (V500)
,
Data Continuous Read (Scan) (V520)
,
Data Read
,
Log Data Clear (V500)
,
Log Data Output Request (V500)
,
Preset Data Set (V500)
,
System Setting
,
sequences, V600/V620 ID Controller
Auto-read (ASCII/1)
,
Auto-read (Hexadecimal/1)
,
Auto-write (ASCII/1)
,
Auto-write (Hexadecimal/1)
,
Command Processing Cancel
,
Control
,
Data Check
,
Error Information Read
,
General-purpose Command
,
Polling Auto-read (ASCII)
,
Polling Auto-read (ASCII/2)
,
Polling Auto-read (ASCII/4)
,
Polling Auto-read (Hexadecimal)
,
Polling Auto-read (Hexadecimal/2)
,
Polling Auto-read (Hexadecimal/4)
,
Polling Auto-read (Hexadecimal/8)
,
Polling Auto-read Command Processing Cancel
,
Polling Auto-write (ASCII/2)
,
Polling Auto-write (ASCII/4)
,
Polling Auto-write (ASCII/8)
,
Polling Auto-write (Hexadecimal/2)
,
Polling Auto-write (Hexadecimal/4)
,
Polling Auto-write (Hexadecimal/8)
,
Polling Auto-write Command Processing Cancel
,
Polling Auto-write Subcommand (ASCII/2)
,
Polling Auto-write Subcommand (ASCII/4)
,
Polling Auto-write Subcommand (ASCII/8)
,
Polling Auto-write Subcommand (Hexadecimal/2)
,
Polling Auto-write Subcommand (Hexadecimal/4)
,
Polling Auto-write Subcommand (Hexadecimal/8)
,
Read (ASCII/1)
,
Read (ASCII/2)
,
Read (ASCII/4)
,
Read (ASCII/8)
,
Read (Hexadecimal/1)
,
Index
Read (Hexadecimal/2)
,
Read (Hexadecimal/4)
,
Read (Hexadecimal/8)
,
Write (ASCII/1)
,
Write (ASCII/2)
,
Write (ASCII/4)
,
Write (ASCII/8)
,
Write (Hexadecimal/1)
,
Write (Hexadecimal/2)
,
Write (Hexadecimal/4)
,
Write (Hexadecimal/8)
,
sequences, Visual Inspection System
Arbitrary Measurement Value Acquisition (F200)
,
Binary Level Modification (F200/300)
,
Camera Change (Decrease by 1) (F200/300)
,
Camera Change (Increase by 1) (F200/300)
,
Camera Designation and Positioning (F350)
,
Character String Inspection and Character Inspection
(F350)
,
Continuous Measurement Execution (Interrupt) (F200)
,
Continuous Measurement Execution (Interrupt) (F300)
,
Continuous Measurement Execution (Scan) (F200)
,
Continuous Measurement Execution (Scan) (F300)
,
Evaluation Condition Change (F200)
,
General-purpose Command (Send)
,
General-purpose Command (Send/Receive)
,
Illumination Fluctuation Follow Execution (F300)
,
Inspection Execution and Character Inspection (F350)
,
Measurement Execution (F200)
,
Measurement Execution (F300)
,
Measurement Execution and Positioning (F350)
,
Measurement, Inspection Termination
,
Reference Object Registration (Criterion) (F200)
,
Reference Object Registration (Group) (F200)
,
Reference Object Registration (Reference Position)
(F200)
,
Reference Object Registration Command 1 Execution
(F300)
,
Reference Object Registration Command 2 Execution
(F300)
,
,
Scene Switching (Arbitrary)
,
Scene Switching (Decrease by 1)
,
Scene Switching (Increase by 1)
,
Scene Switching and Positioning (F350)
,
Serial Communications Boards
,
CIO Area allocations
,
component names
,
data exchange
,
DM Area allocations
,
error information
,
indicator error displays
,
installation
,
replacement
,
specifications
,
serial communications modes
,
1 1 NT Link
,
1 N NT Link
,
Host Link
,
loopback test
,
protocol macro
,
See also 1 N NT Link Host Link Loopback Test protocol
macro selection
,
Serial Communications Units
,
CIO Area allocations
,
component names
,
data exchange
,
DM Area allocations
,
indicator error displays
,
installation
,
precautions
,
replacement
,
specifications
,
Setup Area
,
allocations
,
1 N NT Link
,
Host Link
,
loopback test
,
protocol macro
,
Software Switches
,
soldering
,
specifications protocol
,
Serial Communications Boards
,
Serial Communications Units
,
standard system protocol
,
communications problems
,
DM Area settings
,
examples
,
modifying
,
Status Area
,
allocations
1 N NT Link
,
Host Link
,
protocol macro
,
error information
,
Step Error Processing Flag
,
step number
,
step parameters
,
747
748
STUP(237) instruction
,
executing
,
specifications
,
system configuration
Host Link
,
precautions
,
protocol macro
,
T
terminating resistance switch
,
trace function protocol macro
,
Tracing Flag
,
troubleshooting
,
1 N NT Link errors
,
error codes
,
Host Link errors
,
protocol macro errors
,
U
unit number switch
,
V
V500/V520 Bar Code Reader
,
connections
,
protocols sequences
,
V600/V620 ID Controller
,
connections
,
protocols sequences
,
Visual Inspection System connections
,
protocols sequences
,
Visual Inspection Units
,
W
weight
,
wiring connectors
,
precautions
,
RS-232C ports
,
RS-422A/485 ports
,
Index
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W336-E1-07
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1
2
3
04
05
Date
February 1999
April 2000
May 2001
April 2002
June 2003
Revised content
Original production
Changes were made on the following pages.
Page 4: “Boards” corrected to “Unit” in “Connectable Devices.”
Pages 23-24: Information on 1: N NT link added.
Page 29: “1694” corrected to “1699” in “Unit No. 7” row of table on right.
Page 31: “RS-422” changed to “RS-422A” in “Connections.”
Page 33: Information on NT link changed.
Pages 41-42: Information about high-speed NT link added.
Page 50: Information on NT link removed from “Note 4.”
Page 97: “1694” corrected to “1699” in “Unit No. 7” row.
Page 118: “Note 3” removed from bottom right box in table. Information on RS/CS flow added.
Page 138: Note added.
Page 151: Information on D32001 added. Information on high-speed NT link added.
Page 154: Information on baud rate and note added.
Page 163: “Execution error” changed to “syntax error” in table.
Page 171: Information added to “cause” column.
Page 347, 348, 349, 350, 352, 353, 358: “Negative sign” information changed.
CJ1W-SCU41 Serial Communications Unit added, “CS1” changed to “CS” or CS/CJ” according to context, and “CS Series only” added to distinguish functions for Serial Communications Boards.
Page xiv: Added terminal block precaution, section name changed to “this manual,” change precaution on locking devices, and precaution added on terminal blocks.
Pages 105 and 114: Note added on retry processing.
Pages 171 and 181: Information added on retry processing.
CJ1W-SCU21 Serial Communications Unit and information on the Simple Backup Function added. The CS1W-SCB21-V1, CS1W-SCB41-V1, CS1W-SCU21-V1, and CJ1W-
SCB21/41 support this function.
Page xix: “EMC” changed to “EMS.”
Page 5: Overview of the “-V1” upgrades.
Pages 21 and 22: Added CS1-H CPU Units, CJ1-H CPU Units, and Simple Backup Function to Specifications.
Page 32: Simple Backup Function added to table.
Page 149: Modified the Error Flag’s ON conditions.
Pages 158 to 161: Simple Backup Function description added.
Pages 177 and 179: Added Indicator Displays related to the protocol data restore operation.
Pages 205 to 207: Added Board/Unit replacement procedure that uses the Simple
Backup Function to restore protocol data in the new Board/Unit.
Front cover: “21” inserted in model number.
Page 142: Minor changes made to first table.
Page 144: Changes made to first table row in several places.
Page 152: Line added before notes.
749
Revision code
06
07
Revision History
Date
June 2004
November 2005
Revised content
Additions made throughout the manual to include information on the upgrade to version
1.2, including two new sections on Serial Gateway and no-protocol modes and three new appendices. The following changes were also made.
Front cover: “-V1” suffix added to CJ-series Serial Communications Unit model numbers.
Page xvii: Application precautions added.
Page xx: Information on unit versions and summary of upgraded functions added.
Pages 3 and 5: Connection diagram for version 1.2 or later added.
Page 6: Protocol overview for version 1.2 or later added.
Page 7: Information on version 1.2 or later added.
Page 8: Information on protocol macros used with version 1.2 or later added.
Page 9: Information including diagrams on Serial Gateway and no-protocol mode added.
Pages 22 and 23: Information added to table and model numbers changed.
Pages 25 and 26: Note added to table.
Page 29: Table on Serial Gateway and no-protocol mode specifications added.
Page 30: Table changed.
Page 32: Note and table changed.
Page 35: Information added to table.
Page 41: Information on 1:1 Host Link communications added.
Page 42: Table changed and new tables on other communications modes added.
Page 47: Information on Serial Gateway mode added.
Pages 63 and 65: Tables changed.
Page 67: Table changed, Note 5 removed, and new notes added.
Pages 68 and 69: Tables changed.
Page 70: Table changed, note added, and new table added.
Page 71: Table added.
Page 79: Tables changed.
Page 122: Note changed and 4-6 Host Link Function for Replacing Existing PLCs added.
Page 132: Table changed and information on new settings added.
Page 134: Information on new settings added.
Page 139: Table changed.
Page 140: Diagram and table changed.
Pages 142 and 145: Tables changed.
Page 146: Diagram changed.
Page 148: Table changed.
Page 158: “FAL(06)00” and “FAL(06)01” corrected respectively to “FAL(06)01” and
“FAL(06)02.”
Page 163: Table changed.
Page 166: 5-6 Enhanced Protocol Macro Functions, SECTION 6 Serial Gateway, and
SECTION 7 No-protocol Mode added.
Page 171:Table changed.
Page 183: Table changed.
Page 192: 11-3-2 Serial Gateway (Serial Gateway or Protocol Macro Mode) and 11-3-3
Page 204: Table changed.
Page 214: Table changed.
Page 220: Table changed.
Page 221: Information including table added on ASCII conversion.
Page 222: Notes changed.
Page 230: Information on new communications sequences added.
Page 231: Appendix C C-mode (Host Link) Command Master, Appendix D Host Link
FINS Command Master, and Appendix E Mitsubishi Computer Link Master (A-compatible
“PC” was changed to “PLC” throughout the manual and the “-V1” suffix was added to
CJ1W-SCU21/41. Changes were also made to update to unit version 1.3. Other minor changes and corrections were made, including the following changes.
Page v: Changed and added information.
Page xi: Changed information in table.
Page xii: Added warranty and liability information.
Page xvi: Changed precaution on ground terminal.
Page xvii: Added precaution information.
Page xix: Changed Common Emission Standard EN50081-2 to EN61000-6-4.
Page xxii: Changed diagram.
Page 79: Removed error code 5 from table.
Pages 127 and 264: Changed layout of information on hardware settings in table.
Page 150: Added information to table.
Page 156: Changed information for bit 10 in table.
Page 247: Changed values in table for Serial Communications Boards.
Page 251: Joined tables together.
Page 254: Changed “A35607” to “A35606” for the Reception Completed Flag bit.
Page 311: Changed “No” to “Yes” for 0601 and 0602 hex.
Page 317: Removed step 2 from procedure for using the simple backup function.
Pages 640, 641, and 643: Changed information in note 4.
750
W336-E1-07
Download
Advertisement
Key features
Supports RS-232C, RS-422A, and RS-485 interfaces
Provides a simple and reliable way to connect to external devices
Supports various standard protocols for communicating with devices
Provides data exchange with the CPU unit
Offers various communications modes
Offers loopback test for testing serial ports
Includes troubleshooting and maintenance procedures
Allows for easy replacement of existing PLCs
Frequently asked questions
The Serial Communications Boards and Units support RS-232C, RS-422A, and RS-485 interfaces.
The Units and Boards support various standard protocols for communicating with devices, including Host Link, Protocol Macros, Serial Gateway, and No-protocol mode.
The manual provides troubleshooting procedures and guidelines for diagnosing and resolving issues with the Serial Communications Boards and Units.
The manual details the steps for replacing existing PLCs using the Serial Communications Boards and Units, including setting up the Host Link function and Modbus-RTU Slave mode.