KEB R6 -N power supply and regenerative unit Instruction Manual
Below you will find brief information for power supply and regenerative unit R6 R6-N. The COMBIVERT R6-N serves exclusively for the supply of frequency inverters with DC input and/or regeneration of excess energy into the supply system. The operation of other electrical consumers is prohibited and can lead to malfunctions or to the destruction of the units. The COMBIVERT R6-N is generally protected against overcurrent, ground fault and temperature. Appropriate dimensioned DC fuses protects the DC link circuit against short-circuit.
Advertisement
Advertisement
CO M B I V E RT
INSTRUCTION MANUAL
Type R6-N
Power Supply and Regenerative
Unit
Size 15/19
Original manual
Document
Part Version
20116581 GBR 01
Table of Contents
Table of Contents
4.4.1 Power supply and regenerative operation at inverter current ≤ current of one
4.4.2 Power supply and regenerative operation at inverter current ≤ current of one
3
Table of Contents
4.4.3 Power supply and regenerative operation at inverter currents ≤ current of one
4.4.5 Regenerative operation at parallel operation of up to two R6-N with decoupling diodes ....37
4
Table of Contents
List of figures
Dimensions and weights for the COMBIVERT R6-N ..............................................22
General description of input terminals at KEB inverter ...........................................29
Description of the input terminals of the COMBIVERT R6-N ..................................30
Power supply and regenerative operation at inverter current ≤ current of one
Power supply and regenerative operation at inverter currents ≤ inverter current ...33
Power supply and regenerative operation at inverter current ≥ inverter current .....33
Regenerative inverter currents ≤ inverter current (type A1/A2) ...............................35
Regenerative inverter currents ≤ inverter current (type B1/B2) ..............................36
Dimension of power supply and regenerative units ................................................51
5
Preface
1. Preface
The described hard and software are developments of the Karl E. Brinkmann GmbH. The enclosed documents correspond to conditions valid at printing. Misprint, mistakes and technical changes reserved.
1.1 Information on special measures
The used pictograms have following significance:
Danger
Is used, when death or serious bodily injury may be the consequence of non-observance of the measure.
Warning
Caution
Attention
Is used, when bodily injury and/or substantial property damage may be the consequence of non-observance of the measure.
Is used, when property damage may be the consequence of non-observance of the measure.
Is used, when noise sensitive or unrequested operation may be the consequence of non-observance of the measure.
Info
Is used, when a better or simpler result can be the consequence of the measure.
For a special case the instructions can be supplemented by additional pictograms and text.
1.2 Documentation
Attention
Step 1
Documentation via www.keb.de
Prior to performing any work on the unit, it is absolutely necessary to download and read the documentation, especially the safety precautions and instructions for use. Follow these steps to get the documentation:
Read the material number (Mat.No.) from nameplate
Input the material number at "www.keb.de => Service => Downloads" and click "search".
Downloads
Step 2
Suche nach Materialnummern
Bitte geben Sie eine vollständige (11-stellige) Materialnummer ein.
Suche nach:
xxxxxxx-xxxx suchen continued on the next page
6
Preface
Step 3
The entire documentation associated with the device will be displayed, including the instruction manuals in German and English. If available, other translations are also indicated. Make sure that the user understands the provided language.
Should you be unable to read or understand the documentation, do not take any further steps. Please inform our support network for further assistance.
Non-observance of the safety and operating instructions leads to the loss of any liability claims. The warnings and safety instructions in this manual work only supplementary. This list is not exhaustive.
1.3 Validity and liability
The use of our units in the target products is beyond of our control and therefore exclusively the responsibility of the machine manufacturer, system integrator or customer.
The information contained in the technical documentation, as well as any user-specific advice in spoken and written and through tests, are made to best of our knowledge and information about the application. However, they are considered for information only without responsibility. This also applies to any violation of industrial property rights of a third-party.
Selection of our units in view of their suitability for the intended use must be done generally by the user.
Tests can only be done within the application by the machine manufacturer. They must be repeated, even if only parts of hardware, software or the unit adjustment are modified.
Danger by tamper from unauthorized personnel
Unauthorised opening and tampering may lead to death, bodily injury, property damage and malfunctions. Modification or repair is permitted only by
KEB authorized personnel. Infringement will annul the liability for resulting consequences.
The suspension of liability is especially valid also for operation interruption loss, loss of profit, data loss or other damages. The disclaimer will void the warranty. This is also valid, if we referred first to the possibility of such damages.
If single regulations should be or become void, invalid or impracticable, the effectivity of all other regulations or agreements is not affected.
Through multitude applications not each possible case of installation, operation or maintenance can be considered. If you require further information or if special problems arise which are not treated in detail in the documentation, you can request the required information from the local agency of the company Karl E. Brinkmann GmbH.
1.4 Copyright
The customer may use the instruction manual as well as further documents or parts from it for internal purposes. Copyrights are with KEB and remain valid in its entirety.
7
Preface
KEB
®
, COMBIVERT
®
, KEB COMBICONTROL
®
and COMBIVIS
®
are registered trademarks of Karl E. Brinkmann GmbH.
Other wordmarks or/and logos are trademarks (™) or registered trademarks (®) of their respective owners and are listed in the footnote on the first occurrence.
When creating our documents we pay attention with the utmost care to the rights of third parties. Should we have not marked a trademark or breach a copyright, please inform us in order to have the possibility of remedy.
1.5 Specified application
The COMBIVERT R6-N serves exclusively for the supply of frequency inverters with DC input and/or regeneration of excess energy into the supply system. The operation of other electrical consumers is prohibited and can lead to malfunctions or to the destruction of the units.
The used semiconductors and components of the Karl E. Brinkmann GmbH are developed and dimensioned for the use in industrial products. If the KEB COMBIVERT F5 is used in machines, which work under exceptional conditions or if essential functions, life-supporting measures or an extraordinary safety step must be fulfilled, the necessary reliability and security must be ensured by the machine builder.
The operation of our products outside the indicated limit values of the technical data leads to the loss of any liability claims.
All output functions of the R6 are "one-channel according to ISO 13849, no diagnostic coverage and therefore not safe". If required, additional protective measures must be met by the user.
1.5.1 Standard operation
If the DC link voltage increases to a value above the peak value of the mains voltage (negative power), regeneration of the current into the mains occurs automatically. The regenerative level is defined with parameter CP.34 or cS.02. The mains voltage is analog measured. The regenerative current is equal to the feed-in, whereby the current flow periods correspond to the times of a B6 bridge circuit. Regeneration is completed if the regenerative and puls off level (CP.32 or cS.06) is fallen below.
8
Preface
1.5.2 Abnormal operation
When exceeding the permissible limit values for voltage, current or temperature the current flow between DC link and mains is blocked during regeneration. An appropriate error message is also displayed during supply. The unit must be disconnected from the supply system or the load must be switched off in case of overcurrent or overload. This can be done by opening the control release of the frequency inverter.
At factory setting the modulation is switched off in case of a net phase failure and error message E.nEt is displayed.
Special adjustments from KEB are necessary if the modulation and/or the standard operation should start again within a defined time in case of return of power supply.
1.6 Product description
This instruction manual describes the power supply and regenerative unit KEB COMBIVERT
R6-N. The COMBIVERT R6-N has the following features.
The supply unit
• converts a three-phase input voltage into DC voltage.
• supplies single KEB frequency inverter or via DC interconnection.
• can be parallel connected if higher power supply is required.
• increases the stability of the DC link voltage in the DC interconnection.
The regenerative unit
• feeds back the excess energy from generatoric operation into the supply system.
• reduces the energy demand.
• reduces the heat emission.
• is environmentally friendly and space-saving.
• replaces braking resistor and braking transistor.
• is cost-saving.
• has the same current flow (harmonic components) such as feed-in and rarely noise level
The COMBIVERT R6-N is generally protected against overcurrent, ground fault and temperature. Appropriate dimensioned DC fuses protects the DC link circuit against short-circuit. The following accessories are necessary for operation with the COMBIVERT R6-N:
• Mains choke
• EMC filter E6 (for observance of EMC standard) respectively voltage limitation
9
Preface
1.7 Part code
1 9 R 6 N 3 E - 9 0 0 A
Type
Design reserved
Voltage
Housing
Options
Control
Series
Inverter size
A: Standard
B: Flat rear
D: ext. fan power supply
E: Special fan
0: Standard
0: Standard
1: modified standard (increased overload)
9: 3-ph.; 180…550 V; AC
E
0: without 3: Precharging, DC-fuses
1: Precharging
N 1N.R6
R6
15 (13), 19 (16)
10
Safety Instructions
2. Safety Instructions
2.1 General instructions
Danger Electric Shock
COMBIVERT R6 power supply and regenerative units contain dangerous voltages which can cause death or serious injury.
COMBIVERT R6 can be adjusted by way that energy is regenerated into the supply system in case of power failure at regenerative operation. Therefore a dangerous high tension can exist in the unit after switching off the supply system.
Before working with the unit check the isolation from supply by measurements in the unit.
Care should be taken to ensure correct and safe operation to minimise risk to personnel and equipment.
Warning Only Qualified Electro-Personnel
All work from the transport, to installation and start-up as well as maintenance may only be done by qualified personnel (IEC 364 and/or CENELEC
HD 384 and IEC-Report 664 and note national safety regulations). According to this manual qualified staff means those who are able to recognise and judge the possible dangers based on their technical training and experience and those with knowledge of the relevant standards and who are familiar with the field of power transmission.
Attention Observe standards
The COMBIVERT must not be started until it is determined that the installation complies with the Machine directive (2006/42/EC) as well as the EMC-directive (2004/108/EC)(note EN 60204).
The COMBIVERT meets the requirements of the Low-Voltage Directive
2006/95/EC. The harmonized standard of the series EN 61800-5-1 (VDE
0160) is used.
This is a product of limited availability in accordance with IEC 61800-3. This product may cause radio interference in residential areas. In this case, the operator must take appropriate measures.
11
Safety Instructions
2.2 Transport, storage and installation
The storage of the COMBIVERT must be done in the original packing. It is to be protected against humidity and excessive cooling and thermal effect. A long-distance transport must be carried out in the original packing. It is to be secured against impact influence. Observe the marking on the final packing! After removing the final packing the COMBIVERT must be shut down on a stable base.
Warning Protect Against Accidental Contact
The COMBIVERT R6 must be protected against invalid loading. Components and covers must not be bent or moved as this may affect insulation distances. The units contain electrostatic sensitive devices which can be destroyed by inappropriate handling. For that reason the contact of electronic devices and contacts is to be avoided. The equipment must not be switched on if it is damaged as it may no longer comply with mandatory standards.
Make sure that during installation there is enough minimum clearance and enough cooling.
Climatic conditions must be observed in accordance with the instruction manual.
Warning Hot surface
Heat sinks can reach temperatures, which can cause burns when touching. If in case of structural measures a direct contact cannot be avoided, a warning notice "hot surface" must be mounted at the machine.
2.3 Electrical connection
Danger Observe capacitor discharge time
Before any installation and connection work, the system must be switched off and secured.
After clearing the DC link capacitors are still charged with high voltage for a short period of time. The unit can be worked on again, after it has been switched off for 5 minutes.
Caution Safe isolation
The terminals of the control terminal strip are securely isolated in accordance with EN 61800-
5-1. With existing or newly wired circuits the person installing the units or machines must ensure that the EN requirements are met. With frequency inverters that are not isolated from the supply circuit all control lines must be included in other protective measures (e.g. double insulation or shielded, earthed and insulated).
12
Safety Instructions
Danger Voltage with respect to ground
The connection of COMBIVERT R6 is allowed to: a) symmetrical mains with a voltage phase (L1, L2, L3) with respect to neutral conductor/ ground (N/PE) of maximum 305 V.
b) phase conductor grounded supply networks:
• the control system is no longer regarded as “safe isolated circuit”, further protection measures are required therefore (see "Safe isolation").
• with this type of power system, the max. voltage phase / earth must not exceed 528 V absolute
• appropriate, external DC fuses at the DC connections are necessary for the 400 V class.
Use the COMBIVERT R6-N without internal DC fuses.
• Contact KEB regarding EMC filter.
Attention Fixed connection
The COMBIVERT R6 is designed for fixed connection, since discharge currents of > 3.5 mA occur especially when using together with EMI filters. Therefore, the requirements or instructions from EN 60204-1 (VDE 0113) and EN 61800-5-1 (IEC 0160-5-1) must be observed.
Caution Insulation measurement
When doing an insulation or voltage measurement in accordance with in EN 60204-1 /
VDE 0113-1, the power semiconductor of the unit and existing radio interference filters must be disconnected because of the danger of destruction. This is permissible in compliance with the standard, since all inverters are given a high voltage test in the end control at KEB.
In the case of special requirements please contact KEB.
Caution Different earth potentials
When using components without isolated inputs/outputs, it is necessary that equipotential bonding exists between the components to be connected (e.g. through the equalizer). Disregard can cause destruction of the components by the equalizing currents.
13
Safety Instructions
14
Caution Prevent malfunctions
A trouble-free and safe operation of the COMBIVERT R6 is only guaranteed when the connection instructions below are strictly followed. Incorrect operation or damage may result from incorrect installation:
• Pay attention to mains voltage.
• Install power cables and control cables separately (>15 cm separation).
• Use shielded / twisted control lines. Lay shield at one side to COMBIVERT R6-N to PE !
• Only use suitable circuit elements to control the logic and analog inputs, whose contacts are rated for extra-low voltages.
• Housing of the COMBIVERT R6 must be well earthed. Screens of larger power cable must be directly and securely attached to both the inverter PE terminal and the motor ground terminal (remove paint).
• Ground the cabinet or the system earth star point with the shortest connection to mains earth. (avoid earth loops)
• Use exclusively the line commutation throttle specified by KEB.
• The average value of the supplied DC current may not exceed the maximum DC current.
• If several frequency inverters are connected to the COMBIVERT R6-N the max. permissible DC link capacities of all connected frequency inverters must be considered during supply operation (see technical data).
Warning Automatic restart
The COMBIVERT R6 can be adjusted by such way that the inverter restarts automatically after an error case (e.g. broken phase line). System design must take this into account, if appropriate, and additional monitoring or protective features added where necessary.
Caution Not short-circuit proof (supply)
The COMBIVERT R6 is not short-circuit proof at the mains input ! Conditional protection at the mains input is possible if the I
2 t-protection was adapted with a gR fuse. The short-circuit protection at DC output is ensured by internal or external aR respectively gR fuses.
Caution Conditionally short-circuit proof (regeneration)
The COMBIVERT R6 is conditionally short-circuit proof (EN 61800-5-1 / VDE 0160). The intended function is guaranteed after resetting the internal protection devices.
Exception:
• If earth- or short circuits often occurs at the output, this can lead to a defect in the unit.
Safety Instructions
Attention Cyclic activation and deactivation
With applications requiring the COMBIVERT R6 to be switched on and off cyclically, maintain an off-time of at least 5 min. If you require shorter cycle times please contact KEB.
Switching off during the initialization phase can cause undefined conditions.
Attention RCD (residual current operated circuit-breaker)
When using systems with RCD, the instructions or the requirements of VDE 0100 -T 530
(IEC 60364-5) must be observed. The recommended tripping current of the RCD type „B“ is
300 mA.
15
EMC instructions
2.4 EMC instructions
COMBIVERT R6-N represent electrical equipment designed for use in industrial and commercial units. In accordance with the EMC directive 2006/108/EC, it is not obligatory to mark these devices as they represent components to be further processed by the respective machine and unit manufacturer and are not operable independently according to the EMC directive. The person installing / operating the machine / unit is obliged to prove the protective measures demanded by the EMC directive are complied with. The prescribed ratings can usually be complied with when using the radio interference voltage filters specified by KEB, and when observing the following measures and installation guidelines.
2.5 EMC conform installation
The COMBIVERT R6 is designed to be used in the second environment as defined in EN
61800-3 (unit with its own supply transformer). Take additional filter measures when using it in the first environment (residential and commercial area connected to public low-voltage mains)!
• Install the control cabinet or system in an appropriate and correctly way (see chapter „EMC conform control cabinet installation“)
• To avoid coupled-in noise, separate supply lines, motor lines, control and data lines (low-voltage level < 48 V) and leave a space of at least 15 cm between them when installing.
• In order to maintain low-resistance high frequency connections, earthing and shielding, as well as other metallic connections (e.g. mounting plate, installed units) must be in metal-to-metal contact with the mounting plate, over as large an area as possible. Make ground connections with a surface as large as possible (earthing strips).
• Only use shielded cable with copper or tin-plated braid, since steel braid is not suitable for high frequency ranges. The screen must always be installed on the compensating rail and fastened with clips or guided through the wall of the housing. Do not elongate the screen end (pigtails) with individual conductors!
• If external interference suppression filters are used, then these must be installed as close as possible to (<30 cm from) the interference source and in metal-to-metal contact with the mounting plate, over as large an area as possible.
• Always equip inductive control elements (contactors, relays etc.) with suppressors such as varistors, RC-elements or damping diodes.
• All connections must be kept as short as possible and as close as possible to the earth, as free floating lines work as active and passive aerials.
• Keep connection cables straight (do not bundle). Install a non-assigned wire at one sides to the protective earth conductor.
• The flow and return circuit must be twisted when the lines are not shielded, in order to dampen common-mode noise.
• Further information can be found in the internet, see „www.keb.de“.
16
Technical Data
3. Technical Data
3.1 Standard unit size
Standard unit size
Housing size
Phases permitted mains forms
Rated voltage
Input voltage UL
Mains voltage range
Mains frequency
DC voltage range
Regenerative operation
Output rated power
Rated active power
Max. power output
Max. active power
Regenerative rated current
Regenerative DC current
Over load current (E.OL) 60 s
Max. regenerative DC current 60 s
Power supply operation
Input rated power
Rated active power
Max. input power
Max. active power
Rated supply current
DC supply current
Over load current (E.OL) 60 s
Max. DC supply current 60 s
Overload disconnection (E.OL)
Overvoltage switch-off (E.OP)
Output rated voltage
*)
*)
*)
[V]
[V]
[V]
[Hz]
[V
DC
Sn *) [kVA]
*) [ kW ]
*) [kVA]
*)
[ kW ]
[A]
[A
DC
1)
[A
[A]
DC
Sn *) [kVA]
*) [ kW ]
*) [kVA]
*)
2)
[ kW ]
[A]
[A
DC
[A
[A]
]
DC
[%]
[V
DC
]
[V
DC
[µF]
]
]
]
]
]
Max. permissible DC link capacity
4)
I
2 t Integral of the limiting load of the semiconduc-
*)
[A
2 s] tor
Max. permissible mains fuse type gR / aR
[A]
Permissible aR fuse Siemens Sitor / Bussmann (no delta power system)
Line fuse for UL type RK1 "fast acting" or "J fast acting"
Short-circuit factor at the connection point (S kn
Power loss at nominal operating
Max. heat sink temperature
" / S n
) or (S scp
/ S
[W]
[°C]
)
15 (13)
26
32
39
48
240/400/480
180…550 ±0 %
50 / 60 ±2
250…780 (UL: 340…680)
18 (10.5)
17 (10)
27 (15.5)
25.5 (15)
18 (10.5)
16 (10)
27 (15.5)
24 (14.5)
26
32
39
48
160
1200
E
3
TN, TT
5)
400 (230)
540 (310)
10000 (42000)
40 100
3NC2240 / FWP-40A22FA 3NC2240 / FWP-40A22FA
50A / 480V (50A / 250V)
200
70
20 < S kn
900
" / S
19 (16)
45 (26)
42 (23)
67.5 (39)
63 (34.5)
65
80
97.5
120
48.5 (28)
44.5 (25.5)
72.5 (42)
67 (38)
70
87
3)
105
130
160
10000 (42000)
4500
90A / 480V (90A / 250V) n
< 350
470
88
*)
1)
2)
3)
4)
5)
Bracket values obtain for operation at 230 V power supply. The unit is automatically adjusted by the software when switching on.
The overload current is specified for 1 minute. The overload cycle is 300 seconds. This corresponds to duty class 2
EN 60146-1-1.
The current data are based on a fundamental frequency component of g=0.95. The fundamental frequency component or the effective value of the input current is dependent on load and line supply conditions. At uncontrolled
B6 converters the phase angle cosφ1 can be set to one, so the value of the fundamental frequency components is equal to the value of the power factor.
If the DC infeed current > 85 A DC use two by two of the DC terminals (++ and --) to meet the requirements of the
UL standard. The connection cables are parallel connected.
Please contact KEB for higher values.
After consultation KEB IT and delta power system (see also safety instructions, voltage with respect to ground)
17
Technical Data
3.2 Special unit Peak Power
Inverter size
Housing size
Phases
*)
Approaved mains phases
Rated voltage
Input voltage UL
Mains voltage range
Mains frequency
DC voltage range
Regenerative operation
Output rated power
Rated active power
Max. power output
Max. active power
Regenerative rated current
Regenerative DC current
Overload current (E.OL) 10 s
Max. regenerative DC current 10 s
Power supply operation
Input rated power
Rated active power
Max. input power 10 s
Max. active power 10 s
Rated supply current
DC supply current
Overload current (E.OL) 10 s
Max. DC supply current 10 s
*)
*)
Sn *)
*)
*)
*)
Sn *)
*)
*)
1)
2)
[Hz]
[V
[V]
[V]
[V]
DC
[kVA]
[ kW ]
[kVA]
[ kW ]
[A]
[A
DC
]
[A]
[A
DC
]
[kVA]
*) [ kW ]
[kVA]
[ kW ]
[A]
[A
DC
]
]
Overload disconnection (E.OL)
Overvoltage switch-off (E.OP)
Rated output voltage
Max. permissible DC link capacity *)
I
2 t Integral of the limiting load of the semiconductor
Max. permissible mains fuse type gR / aR
Permissible aR fuse Siemens Sitor / Bussmann (no delta power system)
[A]
[A
DC
]
[%]
[V
DC
]
[V
DC
]
[µF]
[A
2 s]
[A]
Line fuse for UL type RK1 "fast acting" or "J fast acting"
Short-circuit factor at the connection point (S
Power dissipation at nominal operating
Max. heat sink temperature kn
" / S n
) or (S scp
/ S n
)
[W]
[°C]
*)
1)
2)
3)
Special unit Peak Power 19 (16)
E
3
TN, TT
3)
400 (230)
240/400/480
180…550 ±0 %
50 / 60 ±2
250…780 (UL: 340…680)
45 (26)
42 (23)
81 (46,6)
75 (42)
65
80
117
144
48.5 (28)
44.5 (25.5)
87 (50)
80 (46)
70
87
126
156
200
900
540 (310)
10000 (42000)
3058
100
3NC2240 / FWP-40A22FA
90A / 480V (90A / 250V)
20 < S kn
" / S n
< 350
430
88
Bracket values obtain for operation at 230 V power supply. The unit is automatically adjusted by the software when switching on.
The current data are based on a fundamental frequency component of g=0.95. The fundamental frequency component or the effective value of the input current is dependent on load and line supply conditions. At uncontrolled B6 converters the phase angle cosφ1 can be set to one, so the value of the fundamental frequency components is equal to the value of the power factor.
If the DC supply current > 85 A DC use two by two of the DC terminals (++ and --) to meet the requirements of the UL standard.
The connection cables are parallel connected.
After consultation KEB IT and delta power system (see also safety instructions, voltage with respect to ground)
18
Technical Data
Warning General instructions
•
•
•
Voltage stabilization must be activated at the frequency inverter if a harmonic filter is used.
•
The units are not short-circuit proof without corresponding dimensioned fuses.
•
Exceeding of the max. rechargeable DC link capacity can lead to a defect.
•
A load removal in the DC link circle may be done only after the message „ready“.
If the control release is set when switching off the mains, this can lead to an overcurrent error and the lifetime of the module can be reduced.
The unit must be disconnected from the supply system or the load must be switched off in case of overcurrent or overload.
3.3 Overload (OL) function
Standard:
Release time [s]
270
250
200
150
100
60
150
160
Load [%]
105 110 120 130
Figure 1: Overload (OL) function
Modified standard (increased overload):
Release time [s}
300
140
270
250
200
150
100
50
10
105 110 120 130 140 150
1. Depending on the line supply impedance
Figure 2: Overload (OL) function
160 180
①
200
Load [%]
19
Technical Data
3.4 Operating conditions
Definition acc.
Site altitude
Standard
EN 61800-2
EN 61800-5-1
Class Instructions
Inverter-product standard:
Rated specifications
Inverter-product standard:
General safety
max. 2000 m above sea level
With site altitudes over 1000 m a derating of 1 % per 100 m must be taken into consideration.
Ambient conditions during operation
Climate Temperature EN 60721-3-3
3K3
Mechanical
Contamination
Ambient conditions during transport
Tempera-
Climate
Humidity
Track
3K3
EN50155
Germ. Lloyd Part 7-3
Vibration
EN 60721-3-3 3M4 ture
Humidity
Gas
Solids
3C2
3S2
2K3
2K3
extended to -10…45 °C
(with temperature over 45°C to max. 55°C a derating of 5 % per 1 K must be taken into consideration)
5…85 % (without condensation) max. amplitude of a vibration 1 mm
(5…13 Hz) max. acceleration amplitude 7 m/s²
(13…200 Hz)
Mechanical
Vibration
EN 60721-3-2
2M1
(without condensation) max. vibration amplitude 3.5 mm
(2…9 Hz) max. acceleration amplitude 15 m/s²
(9…200 Hz) max. 100 m/s²; 11 ms
Contamination
Surge
Gas
Solids
Ambient conditions for the storage
Climate
Mechanical
Temperature
Humidity
Vibration
EN 60721-3-1
2M1
2C2
2S2
1K4
1K3
1M1
(without condensation) max. amplitude of a vibration 1 mm
(5…13 Hz) max. acceleration amplitude 7 m/s²
(13…200 Hz) max. 100 m/s²; 11 ms
Contamination
Surge
Type of protection
Environment
Definition acc.
EMC emitted interference
Cable-based interferences
Radiated interferences
Interference immunity
Gas
Solids
EN 60529
IEC 664-1
EN 61800-3
–
–
Static discharges
EN 61000-4-2
1M1
1C2
1S2
IP20
C2
EN 61800-3 with EMC filter and ferrite rings with EMC filter and ferrite rings
8 kV
Pollution degree 2
Inverter-product standard:
EMC
AD (air discharge) and CD (contact discharge) continued on the next page
20
Technical Data
Standard
Burst - control lines + bus EN 61000-4-4
Class
2 kV
Instructions
Burst - mains supply EN 61000-4-4 4 kV
Surge - mains supply EN 61000-4-5 1 / 2 kV Phase-phase / phase-ground
EN 61000-4-6 10 V 0.15-80 MHz Immunity to conducted disturbances, induced by radio-frequency fields
Electromagnetic fields EN 61000-4-3 10 V/m
Voltage variation / voltage drop EN 61000-2-1
Voltage unsymmetries / frequency changes EN 61000-2-4
+10 %, -15 %; 90 %
3 %; 2 %
3.5 Accessories
Inverter size
Rated voltage
Commutation reactor
Patch cable for parallel connection (length: 1 m)
Voltage limitation
15 (13) 19 (16)
1)
400 V
15Z1B04-1000 ED 100%
2)
19Z1B04-1000 ED 81% /
20Z1B04-1000 ED 100%
2)
00F50C3-1010
00R6940-2407 for illustration 19-21 with harmonic filter
3.6 Options
Inverter size
Mains filter
(see chapter connection power unit)
Harmonic filter
(no UL certification)
15 (13)
14E6T60-3000 ED 72% / 16E6T60-
19 (16)
18E6T60-3000 ED 86% / 20E6T60-
3000 ED 100%
2)
3000 ED 100%
2)
Limit class in accordance with EN 61800-3
C2 (only with ferrite rings)
C1 on consultation with KEB
15Z1C04-1000 max. overload 125% regenerative / 150% motoric
19Z1C04-1000 max. overload 140% regenerative / 150% motoric
Please contact KEB for further sizes and data to the THD value at regenerative operation in accordance with EN 61000-2-12.
17Z1C05-1000 21Z1C05-1000
3)
Harmonic filter (with UL certification)
DC fuses
(also see annex B.1.2)
Fuse holder for NH00 and
NH000 fuses
Operators
Bus operators
690 V / 50 A
(Part number 009025H-3459)
690 V / 125 A
(Part number 009025H-3559)
0090574-0001
Digital operator, interface operator
CAN, ProfiBus, InterBus, EtherCAT, EtherNet, Sercos, ModBus, PROFINET,
LCD-Operator, DeviceNet, HSP5
4)
1) The same assignment of filter, commutation reactors and harmonic filter is done for the modified unit
(Peak Power).
2) The ON time ED refers to R6-N.
3) Depending on the load, the following harmonic filters are also possible with the technical data given therein:
15Z1C04-1000, 16Z1C04-1000, 17Z1C04-1000, 18Z1C04-1000, 20Z1C04-1000
4) ProfiNet from operator firmware V3.4 of 30.01.2015
21
Dimensions and weights
3.7 Dimensions and weights
3.7.1 COMBIVERT R6-N
A C C1
H B
Ø F
Housing
E
C1 with operator
A
130
B
290
C
208
C1
14
Figure 3: Dimensions and weights for the COMBIVERT R6-N
F
7
3.7.2 Commutation reactor
H
275
Weight
5.6 kg
B
Ø
F
H1
H2
C
Part number
15Z1B04-1000
19Z1B04-1000
20Z1B04-1000
A
72.5
135
150
B
180
220
220
Figure 4: Commutation reactor
C
178
219
219
F
4.8
7
7
G
55
91
91
G
A
H1
113
136
136
H2
166
201
201
Weight
4.4 kg
12.0 kg
12.0kg
22
Dimensions and weights
3.7.3 Radio interference filter
B
H
D
A
Part number
14E6T60-3000
A
252
B
55
C
92
D
237
Figure 5: Radio interference filter 14E6T60-3000
E
25
F
F
7.5
G
5.5
H Weight
15 1.25 kg
B
H
D
A
Part number
16E6T60-3000
A
252
B
65
C
106
D
237
Figure 6: Radio interference filter 14E6T60-3000
E
30
F
F
7.5
G
5.5
H
15
Weight
1.8 kg
23
Dimensions and weights
B
E
G
Part number
18E6T60-3000
A
240
B
130
C
142
D
220
Figure 7: Radio interference filter 14E6T60-3000
E
100
F
8
G
9
H
88
Weight
3.9 kg
B
E
24
Part number
20E6T60-3000
A
240
B
160
C
142
D
220
Figure 8: Radio interference filter 14E6T60-3000
E
130
G
F
8
G
9
H
88
Weight
5.0 kg
Dimensions and weights
3.7.4 Voltage limitation
100
135
153
A
6
M6
9
R2,9
A (1 : 1)
49,5
R4,25
13
105,5
65,5
20
80 45,5
8
81
171
15
Part number Weight Terminal
00R6940-2407 0.65 kg PE
Connection
M6 stud for ring cable lug
L1.1, L2.1, L3.1 AWG16
Figure 9: Voltage limitation
-
Max. tightening torque
4,5 Nm 40 lb inch
25
Dimensions and weights
3.7.5 Fuse holder with cover
A
Dimensions:
4,96" 126 mm
B1 1,57" 40 mm
B2 1,34" 34 mm
C 0,5" 13 mm
D 0,75" 19 mm
E 3,15" 80 mm
F 0,12" 3 mm
G 1,81 " 46 mm
I
H 2,91" 74 mm
0,26" 6,5 mm
J
K
0,6" 15,5 mm
0,63" 16 mm
L
1
5,75" 146 mm
L2 6,5" 165 mm
M M8
N 0,98" 25 mm
Part number: 0090574-0001
Figure 10: Fuse holder
3.7.6 Ferrite rings
Ferrite rings are used to reduce the cable-fed and radiated disturbances. For a high damping they are placed as close as possible to the interference source, that means at the DC and motor output terminals of the inverter. The conductor are passed through the ferrite core for the use as current-compensated reactor. PE is passed outside the core. Further information is specified in the provided documentation. The ferrite ring to be used arises from the used cable cross-section.
Part number
0090396-2621
0090390-5241
0090395-3820
0090395-5222
0090395-5520
Nominal size in mm
R 42/26/18
R 56/32/18
R 63/38/25
R 87/54/30
R 102/66/15
Inside diameter in mm
24.9
29.5
36.0
54.5
64.5
26
Installation
4. Installation
4.1 EMC-compatible control cabinet installation
1
2
3
Main fuse
Main contactor
EMC side-mounted filter
(>=size 25 R-S or R6-N)
EMC sub-mounted filter
(<=size 19 R6-S)
4
5
If necessary, external voltage limitation / synchronisation
Commutation reactor / harmonic filter
COMBIVERT R6 6
7
8 if necessary, external DC fuses
Frequency inverter
9a DC lines with ferrite DC-
9b Motor line with ferrite
10a Equipotential bonding with the housing earth
10b Protective Earth (PE) on the mounting plate power circuit
10c Protective Earth (PE) on the mounting plate control circuit
11 Mains connection power circuit
11 A Mains connection control circuit
12 Control lines
12
11a
10a
2
1
11
150 mm
3
5
150 mm
Large area contact at the mounting plate
Figure 11: EMC-compatible control cabinet installation
4
150 mm
10b
6
10c
150 mm
7
8
9a 9b
30 mm
4.2 Installation instructions
Warning General installation instructions
• Stationary install and earth COMBIVERT.
• The device must not be permeated by mist or water.
• Allow for sufficient heat dissipation if installed in a dust-proof housing.
when operating it in explosion-endangered spaces.
• Protect COMBIVERT against conductive and aggressive gases and liquids.
• The lines of the R6-N commutation reactor must be limiting to 1m.
• The frequency inverter must be placed in the immediate environment of the R6-N.
27
Connection of the COMBIVERT R6-N
4.3 Connection of the COMBIVERT R6-N
4.3.1 General description of inverter input terminals
Caution Starting current limiting
When connecting inverters to a DC bus pay attention to the internal wiring of the DC voltage inputs !
Inverters that directly output the DC link bus to the DC terminals must be integrated into the DC bus by way that the supply unit(s) limit the starting current. The precharging must be completed within two seconds.
Caution Maximum DC link capacity
The maximum DC link capacity can be calculated by adding the DC link capacities of all inverters in the DC bus. A table for this can be found in the appendix. The supply source
(supply unit or inverter with AC input) must be suitable for this value.
Terminals
++, – –
+(PA), -
PA, PB
L1, L2, L3
Description of terminals at KEB inverters
DC voltage input with starting current limiting; usable as output only if all units supplied by the DC bus have a starting current limiting at the DC voltage input.
DC voltage output with starting current limiting; usable as input only if the starting current is limited by the supply source.
Connection for braking resistor; optionally only if a braking transistor is installed
Mains input 3-phase
28
Connection of the COMBIVERT R6-N
L1
L2
L3
Type A1: AC/DC inverter
+
++
--
L1
L2
L3
Type B1: AC inverter
+PA
+
or also type D1
+PA
L1
L2
L3
+
-
Type C1: DC inverter
+
++
--
L1
L2
L3
Type A2: AC/DC inverter
++
+
Type B2: AC inverter
+PA
Type C2: DC inverter
++
L1
L2
L3
+
+
--
--
-
This type can be supplied by mains and by DC circuit.
The starting current limitation is designed after the input terminals. When used as output parallel connected inverters must have an own starting current limiting at the DC voltage input. The maximum charging current is taken into account.
This type can be supplied by mains. The DC terminals can be used as output with regard to the maximum DC link capacity. When used as input ensure that the starting current is externally limited.
Figure 12: General description of input terminals at KEB inverter
This type is only a DC inverter with starting current limiting. The DC inverter can be combined with all other types in consideration of the maximum DC link capacity.
29
Connection of the COMBIVERT R6-N
4.3.2 Connection terminals of the R6-N power circuit
Info Input voltage
The COMBIVERT R6-N in E-housing is suitable for rated voltages of 230 V and 400 V. The regenerative unit checks the mains at the first switching on and adjusts the parameters accordingly (see parameter CP.31 if mains supply is changed).
Attention View of power supply and regenerative units
The terminals of a power supply and regenerative unit can be input or output dependent on the actual operating status (power supply or regeneration). For the standardization of the view the line side is always regarded as input and the DC voltage side is always regarded as output.
R6-N in E-housing
++
L1.2
L2.2
L3.2
+
--
Terminals
++, – –
Description of terminals at KEB inverters
DC voltage output with starting current limiting for loading the connected inverters; usable as input for regenerative operation. If inverters with mains supply of type A1 or A2 (see 4.3.1) are available in the DC bus, these may be switched to mains only after loading the DC bus. Note the maximum DC link capacity or decoupling diodes !
L1.2, L2.2, L3.2 Mains input 3-phase coming from the commutation reactor
Figure 13: Description of the input terminals of the COMBIVERT R6-N
30
Connection of the COMBIVERT R6-N
- - - -
Housing Size E
++
++ L12 L22 L32
Name
L12
L22
L32
++
- -
PE,
Figure 14: Terminals / earth handle
Strain relief, shielding
Tightening torque [Nm] permissible line cross section
Function
3-phase supply input of the commutation reactor
1.5…25 mm²
(AWG 16…4) max.
4
DC voltage output with starting current limiting
Connection for shielding/grounding occurs via provided copper bar by clamping yoke or ring cable lug. It must be mounted with four screws at the heat sink.
The strain relief and the shielding must be done by the customer e.g. with two clips.
–
-
3
3
4.3.3 Terminals commutation reactor/ harmonic filter
15 / 19Z1B04-1000 (commutation reactor)
15 / 19Z1C04-1000 (harmonic filter)
PE
L1.1
L.2.1 L3.1
L1.2
L2.2
L3.2
PE
Name
L1.1
L2.1
L3.1
L1.2
L2.2
L3.2
Tightening torque [Nm] permissible line cross section
Function
3-phase mains connection
Output to COMBIV-
ERT R6-N
PE
Connection for shielding/earthing
Figure 15: Terminals for commutation reactor / harmonic filter
Size 15
2.5...16 mm²
(AWG 20…6)
Size 19
2.5...35 mm²
(AWG 12…2)
–
Size 15
1.2…2
Size 19
2,5...5
6
31
Connection Power Unit R6-N
4.4 Connection Power Unit R6-N
4.4.1 Power supply and regenerative operation at inverter current ≤ current of one COMBIVERT R6-N
1 2 3 4 5 6 10 8 10 11
L1
L2
L3
PE
L1
L2
L3
L1’
L2’
L3’
L1.1
L2.1
L3.1
L1.2
L2.2
L3.2
L12
L22
L32
++
++
- -
- -
++/+PA
- - / -
PE
U
V
W
Figure 16: Power supply and regenerative operation at inverter current ≤ current of one
COMBIVERT R6-N
4.4.2 Power supply and regenerative operation at inverter current ≤ current of one COMBIVERT R6-N
1 2 3 4 5 6 7
L1
L2
L3
PE
L1
L2
L3
L1’
L2’
L3’
L1.1
L2.1
L3.1
L1.2
L2.2
L3.2
L12
L22
L32
++
++
- -
- -
10
- -/
-
8
++/
+PA
U V W
PE
10
- -/
-
9
++/
+PA
U V W
PE
10 10
11
11
1 Mains fuse type gR
2 Line contactor with protective wiring
5
6
COMBIVERT R6-N with DC fuses
DC fuses type aR/gR
1) 2)
3 Radio interference filter E6 7 DC fuses type aR/gR
2)
2)
4 Commutation reactor / harmonic filter
8 Frequency inverter with I
N(8)
≥ I
N(9)
(FI type A1…C2 possible)
9 Frequency inverter
(FI type A1…C2 possible)
10 Ferrite (optional)
11 Motor
1) The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise appropriate fuses in the DC bus (6) are required. The indicated maximum protection for the connected frequency inverter must be observed !
2) If R6 units without internal DC-fusing are used, fuses in accordance with annex B.1.2 must be used to be conform according to UL. The specified fuses there refer to a maximum fusing of the R6 units.
Smaller fuses according to the connected inverter can be done with fuses of the same type.
Connection clockwise rotating field required !
continued on the next page
32
Connection Power Unit R6-N
A load draw from the DC circuit may be done only if the ready signal is active
Figure 17: Power supply and regenerative operation at inverter currents ≤ inverter current
4.4.3 Power supply and regenerative operation at inverter currents ≤ current of one COM-
BIVERT R6-N
(Parallel operation of up to two units with an error at current sharing of the R6-N units of
≤ 10 %)
1 2
L1
L2
L3
3
L1’
L2’
L3’
L1.1
L2.1
L3.1
4
L1.2
L2.2
L3.2
X2D
L12
L22
L32
5a
++
++
- -
- -
6
A ≥ 25mm²
11
8
++
+PA
- -
-
10
PE
U
V
W
11 12
L1
L2
L3
PE
2
L1
L2
L3
3
L1’
L2’
L3’
L1.1
L2.1
L3.1
4
L1.2
L2.2
L3.2
X2D
L12
L22
L32
5b
++
++
- -
- -
7
7
11
++
+PA
- -
-
9
PE
U
V
W
11 12
1 Line contactor with protective wiring
5b COMBIVERT R6-N slave with
DC fuses
5)
2 Mains fuses type gR
4)
6 External terminal
1)
3 Radio interference filter E6 7 DC fuses type aR/gR
2) 4) 5)
10 Frequency inverter with
I
N(10)
> I
N(5)
1)
(FI type A1…C2 possible)
11 Ferrite (optional)
12 Motor
4 Commutation reactor/harmonic filter
3)
5a COMBIVERT R6-N master with DC fuses
5)
8 DC fuses type aR/gR
4) 5)
9 Frequency inverter with I
N(9)
<
I
N(5)
(FI type A1…C2 possible)
1) If the inverter current > current of the COMBIVERT R6-S it must be wired at an external terminal (6).
2) The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise appropriate fuses in the DC bus (7) are required. The indicated maximum protection for the connected frequency inverter must be observed !
3) In case of parallel connection of R6-N the total power can be lower up to 10 % caused by production tolerances of the commutation reactor.
4) Main and DC fuses must be monitored.
5) If R6 units without internal DC-fusing are used, fuses in accordance with annex B.1.2 must be used for compliance with UL. The specified fuses refer to a maximum fusing of the R6 units. Lower fuse protection according to the connected inverter can be done with fuses of the same type.
When connecting the units, absolutely pay attention to correct phasing !
Connection clockwise rotating field required !
A load draw from the DC circuit may be done only if the ready signal is active
Figure 18: Power supply and regenerative operation at inverter current ≥ inverter current
33
Connection Power Unit R6-N
4.4.4 Regenerative operation with decoupling diodes
Regenerative inverter currents ≤ current of one COMBIVERT R6-N (with mains-operated inverter of type A1 or A2 and max. power ratio from inverter to regenerative unit 1.7:1)
1 1a
L1
L2
L3
PE
2
L1
L2
L3
4
L1’
L2’
L3’
6 7
3
8
L12
L22
L32
PE
++
++
- -
- -
9 11
10
5
L1.1
L2.1
L3.1
14
- -
++
PE
12
U V W PE
14
- -
++
PE
13
U V W PE
L3 L2 L1
14 14
15
15
1 Line contactor with protective wiring
1A Contactor with protective wiring
4)
2 Main fuses
5
6
Voltage limitation 00R6940-2407 when using a harmonic filter
Mains choke / harmonic filter
6)
10 DC fuses type aR/gR
11 DC fuses type aR/gR
5)
3) 5)
3 Mains fuse type gR
7 Choke (xxZ1F04-1010)
6)
8 COMBIVERT R6-N with DC fuses
5)
12 Frequency inverter (type A1, A2,
C1, C2)
13 Frequency inverter (type A1, A2
-> 4.3.1)
4 Radio interference filter E6 9 Decoupling diodes (see annex) 14 Ferrite (optional)
15 Motor
3) The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise appropriate fuses in the DC bus (10) are required. The indicated maximum protection for the connected frequency inverter must be observed!
4) The contactor may only be connected if the precharging in the regenerative unit is completed. Note the permissible
DC link capacity of the charging circuit of the inverter!
5) If R6 units without internal DC-fusing are used, fuses in accordance with annex B.1.2 must be used to be conform according to UL. The specified fuses there refer to a maximum fusing of the R6 units.
Smaller fuses according to the connected inverter can be done with fuses of the same type.
6) Mains choke xxZ1B04-1000 or harmonic filter xxZ1C04-1000 must be sized for the power supply.
Connection clockwise rotating field required!
continued on the next page
34
Connection Power Unit R6-N
A load draw from the DC circuit may be done only if the ready signal is active (see page GB -
26).
In case of failure the contactors must disconnect the units from the supply system.
Figure 19: Regenerative inverter currents ≤ inverter current (type A1/A2)
Regenerative inverter currents ≤ current of one COMBIVERT R6-N (with mains-operated inverter of type B1 or B2 and max. power ratio from inverter to regenerative unit 1,7:1)
1
L1
L2
L3
PE
2
L1
L2
L3
4
L1’
L2’
L3’
6 7
1a
3
L12
L22
L32
PE
8
++
++
- -
- -
9 11
10
5
L1.1
L2.1
L3.1
14 xx xx
PE
12
U V W
PE
14
-
+PA
L3 L2 L1
PE
13
U V W
PE
14 14
15
15
1 Line contactor with protective wiring
1A Regenerative contractor with protective wiring
4)
2
3
Main fuses
Mains fuse type gR
5
6
Voltage limitation 00R6940-2407 when using a harmonic filter
Mains choke / harmonic filter
6)
10 DC fuses type aR/gR
5)
11 DC fuses type aR / gR
3) 5)
7 Choke (xxZ1F04-1010)
6)
8 COMBIVERT R6-N with DC fuses
5)
12 Frequency inverter (all types)
13 Frequency inverter (type B1, B2)
4 Radio interference filter E6 9 Decoupling diodes (see annex) 14 Ferrite (optional)
15 Motor
3) The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise appropriate fuses in the DC bus (10) are required. The indicated maximum protection for the connected frequency inverter must be observed!
4) The contactor may only be connected if the precharging in the regenerative unit is completed. Note the permissible DC link capacity of the charging circuit of the inverter!
continued on the next page
35
Connection Power Unit R6-N
5) If R6 units without internal DC-fusing are used, fuses in accordance with annex B.1.2 must be used to be conform according to UL. The specified fuses there refer to a maximum fusing of the R6 units.
Smaller fuses according to the connected inverter can be done with fuses of the same type.
6) Mains choke xxZ1B04-1000 or harmonic filter xxZ1C04-1000 must be sized for the power supply.
Connection clockwise rotating field required!
A load draw from the DC circuit may be done only if the ready signal is active.
In case of failure the line contactor must disconnect the units from the supply system.
Figure 20: Regenerative inverter currents ≤ inverter current (type B1/B2)
36
Connection Power Unit R6-N
4.4.5 Regenerative operation at parallel operation of up to two R6-N with decoupling diodes
(Parallel operation with an error at current sharing of the R6-N units of ≤10 % and max. power ratio from inverter to regenerative units 1.7:1)
8
3
X2D
L12
L22
L32
++
++
- -
- -
15
5
3
L1.1
L2.1
L3.1
X2D
L12
L22
L32
8
++
++
- -
- -
15 14
12
5
L1.1
L2.1
L3.1
2a
10
6 7
1
2
PE
L1
L2
L3
9
U V W PE
++
+PA
- -
-
12
L1
L2
L3
PE
L1
L2
L3
4
L1’
L2’
L3’
6 2a
10
11
10
7
PE
L1
L2
L3
9
U V W PE
++
+PA
- -
-
13
10
11
1 Line fuses
7)
2 Line contactor with protective wiring
2a Contactor with protective wiring
4)
3 Main fuses type gR
7)
4 Radio interference filter E6
6 Mains choke xxZ1B04-1000 harmonic filter xx-
10 Ferrite (optional)
Z1C04-1000
6) 8)
7 Choke (xxZ1F04-1010)
8)
11 Motor
8 Combivert R6-N with DC fuses
9 Frequency inverter (typ
A1/A2 or B1/B2) same type and size
12 DC fuses type aR/gR
13 DC fuses type aR/gR
2) 7)
7)
14 External terminal block
3)
5 Voltage limitation 00R6940-2407 when using a harmonic filter 15 Decoupling diodes (see annex)
2) The cable cross-section may not be smaller than 10 mm². It must be dimensioned for the DC rated current of the load. Otherwise there are fuses in the DC circuit (10) necessary The indicated maximum protection for the connected frequency inverter must be observed!
3) If the inverter current > current of the COMBIVERT R6-S it must be wired at an external terminal (12).
continued on the next page
37
Connection Power Unit R6-N
38
4) The contactor may only be connected if the precharging in the DC circuit is completed. Note the permissible DC link capacity of the charging circuit of the inverter!
6) In case of parallel connection of R6-N the total power can be lower up to 10 % caused by production tolerances of the commutation reactor /harmonic filter.
7) Main- and DC fuses must be monitored.
8) Mains choke / harmonic filter must be sized for the power supply.
When connecting the units absolutely pay attention to correct phasing!
Connection clockwise rotating field required!
A load draw from the DC circuit may be done only if the ready signal is active (see page GB - 26).
In case of failure the contactors must disconnect the units from the supply system.
Figure 21: Regenerative operation at parallel operation
Connection of the control release of the connected inverters
G1
X2A
24
25
26
S3
24V
STO
0V
G3
G2
X2A
24
25
26
S4
0V
STO
24V
G4
A load draw in the DC circuit may be done only when the message „ready“ is set. This can be guaranteed by a series connection of relay R1 of the R6-N units with the control release of the connected inverters.
G1, G2 Regenerative unit COMBIVERT R6
X2A Control terminal strip
24 Relay 1 / NO contact
25 Relay 1 / NC contact Ready for operation relay
26 Relay 1 / switching contact
G3, G4 Frequency inverter
X2A Control terminal strip
STO Control release
24V 24V output
0V Mass
S3, S4 Control release
General terminal assignment for frequency inverters
Connection of the control board version N
4.5 Connection of the control board version N
4.5.1 Assignment of the control terminal strip X2A
X2A
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
Core cross-section 0.14…1.5 mm², tightening torque 0.5 Nm
PIN Function
10 24V input
11 24V ground
12 Digital input 1
13 Digital input 2
14 Digital input 3
15 Digital input 4
16 Mass
17 24 V output
Name
Uin
COM
ST
I1
I2
I3
COM
Uout
Default Description
External supply of the control board
Reference potential: 24V input
Control release / reset
Set selection programmable
Set selection programmable
Ext. error programmable
Reference potential
Voltage supply for in and outputs
Specifications
21.6…26.4 V DC
/ 1 A
Ri: 4.4 kΩ approx. 24 V / max. 100 mA
18 Mass
19 Digital output 1
COM
O1
Reference potential
DC > 600V Transistor output (DC > I max
: 25 mA
20 Digital output 2 O2
CP.19)
Error message Transistor output (error mesI max
: 25 mA
21 Analog output
22 24 V output
23 Mass
24 Relay 1 / NO contact
ANOUT
Uout
COM
RLA
RLB
RLC
Ready for operation (no error) sage)
Difference to mains frequency (CP.18) see terminal 17
Reference potential
Relay output
0…±10 V / max.
5 mA
25 Relay 1 / NC contact
26 Relay 1 / switching contact
Ready signal ("Stb" or "rE-
GEn") max. 30 V DC *)
0.01…2 A DC
27 Relay 2 / NO contact
28 Relay 2 / NC contact
FLA
FLB
DC > 600V
29 Relay 2 / switching contact
FLC
Relay output
(DC > CP.19) max. 30 V DC *)
0.01…2 A DC
*) The relay outputs must be operated with max. 48 V DC protective separation voltage to guarantee the CE standard. After consultation with KEB, a current of max. 2 A AC is permissible for 120 V AC (depending on the switching capacity etc.).
39
Connection of the control board version N
4.5.2 Assignment of the sockets X2D
RJ45 socket for parallel operation of regenerative units No.
1
1 8
2
3
4
5
6
7
8
IGBT off
IGBT off
SLAVE active
IGBT on
IGBT on
SLAVE active nc nc
Name
→
→
→
→
→
→
High
Low
High
High
Low
Low
Attention at parallel connection
At parallel connection the regenerative units are connected with the KEB catch cable (see
Chapter Accessories) via the socket X2D.
40
Connection of the control board version N
4.5.3 Wiring example
Attention EMC
In order to prevent a malfunction caused by interference voltage supply on the control inputs, the following directions should be observed:
• Use shielded/drilled cables
• Lay shield on one side of the inverter onto earth potential max. 25 mA DC per digital output
Connection external
U
Analog output
0…±10 V DC / 5 mA
Power supply of the inverter inputs
Control release inverter max. 30 V DC
0.01…2 A max. 30 V DC
0.01…2 A
24
25
26
27
28
29
15
16
17
18
19
20
21
22
23
X2A
10 internal
11
12
13
14
Figure 22: Wiring example R6-N
41
Operation of the Unit
5. Operation of the Unit
5.1 Operation with PC and system software COMBIVIS
Instructions for the installation and operation of the system software COMBIVIS can be taken from the appropriate software instruction.
5.2 Switch-on procedure
The COMBIVERT R6-N is initialized after connection of the power supply. The power circuit identification is checked first. If an invalid power circuit is recognized, error „E.Puci” (Power unit code invalid) is released and displayed in the operator. This error cannot be reset, the power circuit must be checked.
The COMBIVERT R6-N changes into synchronisation phase if a valid power circuit is recognized.The following procedures take place one after another during this synchronisation phase:
• Testing the input phases -> error „E.nEt” is triggered if a net phase is missing.
• Testing the phase allocation -> error „E.SYn” is triggered if a phase allocation error occurs
(reverse rotation).
The actual mains frequency is determined and the correct connection of the COMBIVERT
R6-N is secured after successful synchronisation. If the control release (terminal ST) is set, the COMBIVERT R6-N starts independently with the specified operation. Depending whether regenerative requirement is available, the COMBIVERT R6-N is in status „rEGEn” or „Stb”.
Status „Stb“
COMBIVERT R6-N detects a typical voltage level in the DC link circuit of the connected frequency inverter (motor operation) and keeps the modulation signals of the regenerative unit deactivated.
Status „rEGEn”
If the DC voltage in the DC link (CP.09 or ru.19) exceeds the value of the regeneration level
(CP.34 or cs.02) referring to the reference value ru.18, the modulation signals are activated and the unit changes into regenerative operation. Further the regenerative unit is switched active, if regenerative operation is requested by an additional installed COMBIVERT R6-N in the system (master /slave operation).
42
Parameter summary
5.3 Parameter summary
The CP-Parameters are one of the parameter selection defined by KEB. You need an application manual in order to get access to the entire parameters.
Display
Parameter
CP.00 password input
CP.01 inverter state
CP.02 actual line frequency
CP.03 AC current L1
CP.04 AC current L2
CP.05 AC current L3
CP.06 act. DC utilization
CP.07 peak DC utilization
CP.08 DC output current
CP.09 DC voltage
CP.10 peak DC voltage
CP.11 power module temperature
CP.12 OL counter display
CP.13 actual power
CP.14 total regen
CP.15 total motor
CP.16 total net
CP.17 actual net
CP.18 ANOUT1 gain
CP.19 comparison level 0
CP.20 general fault reset
CP.21 last error
CP.22 last error -1
CP.23 last error -2
CP.24 last error -3
CP.25 last error -4
CP.26 last error -5
CP.27 last error -6
CP.28 last error -7
CP.29 software version
CP.30 software date
CP.31 power unit code
CP.32 puls off level
CP.33 operating mode
CP.34 regeneration level
Setting range
0…9999
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
±20.00
±30000.00 V
0…10
–
–
–
–
–
–
–
–
Resolution
1
–
0.1 Hz
0.1 A
0.1 A
0.1 A
1 %
1 %
0.1 A
Factory setting
–
–
–
–
–
–
–
–
–
1 V
1 V
1 °C
1 %
0.1 kW
0.1 kWh
0.1 kWh
0.1 kWh
0.1 kVA
0.01
0.01 V 600.00 V LE.00
1 3 Pn.15
–
–
–
–
In.21
In.21
–
–
–
–
– –
–
–
In.21
In.21
In.21
In.21
–
–
–
–
In.21
In.21
1.11
0801.7
–
–
250 –
0.0…-1000.0 kW 0.1 kW
0…3
100…120 %
1
1 %
–
–
–
–
–
–
–
–
–
1.00
1.11
0801.7
–
-0.8 kW
0
103 % ru.20
ru.38
ru.39
ru.81
ru.82
ru.83
ru.84
ru.85
An.33
In.06
In.07
Sy.03
cS.06
Pn.19
cS.02
based on
Ud.01
ru.00
ru.03
ru.08
ru.09
ru.10
ru.13
ru.14
ru.15
ru.19
43
Password input
5.4 Password input
No.
Name
CP.00
password input r/w Enter based on
– – Ud.01
Ex works the COMBIVERT R6-N is supplied without password protection, i.e. all changeable parameters can be adjusted. After parameterizing the inverter can be secured against unauthorized access (locking: 100 and release: 200). The adjusted mode is stored.
5.5 Monitoring and analysis parameters
The following parameters serve for the functional monitoring during operation.
No.
Name
CP.01
inverter state r/w Enter based on
– – ru.00
The status display shows the actual working condition of the COMBIVERT.
Status messages
rEGEn Regeneration active (regenerative operation) bbL Count down of the base-block time, R6-N released noP nEtoF
„no Operation“ control release not bridged, modulation switched off
Mains power failure; regenerative operation is further possible, if the disconnecting time E.nEt (Pn.14) > 0 s rinit
Stb
Re-initialisation
R6-N regenerative unit in stand-by operation (motor operation)
Error Messages
E.EF
External Fault, error message by an external unit
E.Frlr
E.LSF
Error "Fault reset level reached" is triggered when the adjusted value in parameter
Pn.15 is reached within one hour. The error can be reset.
Error! Charging circuit, load-shunt defective or wrong or input voltage too low. This message is displayed for a short time during the power-on phase (no error message follows).
E.nEt
„Error! net, one or more phases are missing
E.nOH No overheat, over-temperature error not present (E.OH), error can be reset.
E.nOL
No overload, cooling time after E.OL is up , error can be reset.
E.OC
„Error! Overcurrent“, output current too high or ground fault
E.OH
„Error! Overtemperature“, overheating at heat sink (see „Technical data“)
E.OHI
„Error! Interior temperature“, temperature in the interior > 95 °C
E.OL
„Error! Overload“, overload monitoring of the regenerative unit has responded
E.OP
„Error! Overvoltage“, DC link voltage too high
E.Pu
„Error in power unit“, power unit code is missing, load shunt relay defective continued on the next page
44
Monitoring and analysis parameters
No.
Name r/w Enter based on
CP.01
inverter state
E.Puci
Power unit identification invalid
E.Puch
– – ru.00
„Error! Power unit changed“, a configured unit for 400 V was connected to a 230 V mains (or reverse). Load factory setting with CP.31, so the unit can adapt itself to the changed supply system.
E.SYn
„Error! Synchronisation“ with wrong phase allocation (reverse rotation).
E.UP
„Error! Undervoltage“, DC link voltage too low
No.
Name
CP.02
actual line frequency r/w Enter based on
– – ru.03
After switching on, the actual mains frequency is determined during the initialization phase.
Slowly changes of the line frequency during the operation are recognized and displayed in CP.02. CP.02 displays the actual regenerative frequency, if the COMBIVERT R6-N is in
"netof" state.
Resolution
0.01 Hz
Meaning positive values = forward rotating field negative values = reverse rotating field (not permissible -> error E.SYn)
No.
CP.03
Name
AC current L1
CP.04
AC current L2
CP.05
AC current L3
Resolution
0.1 A
Meaning r/w Enter based on
– – ru.08
–
–
–
–
Display of the actual input current of the respective phase.
ru.09
ru.10
No.
Name
CP.06
act. DC utilization
Resolution
1 %
Meaning r/w Enter based on
– – ru.13
Independent whether power supply or regenerative operation, the display indicates the actual utilization of the COMBIVERT R6-N. 100 % correspond to the rated current of the COMBIVERT R6-N.
45
Monitoring and analysis parameters
No.
Name r/w Enter based on
CP.07
peak DC utilization
Resolution Meaning
1 %
– – ru.14
Parameter CP.07 enables to recognize short-term peak utilization within an operating cycle. For that the highest value of CP.06 is stored in
CP.07. The peak value memory can be cleared by pressing the UP and
DOWN key or via bus by writing any value you like to the address of
CP.07. Switching off COMBIVERT R6-N also clears the memory.
No.
Name
CP.08
DC current
Resolution
0.1 A r/w Enter based on
–
Meaning
Display of the actual DC output current in ampere.
– ru.15
No.
Name r/w Enter based on
CP.09
DC voltage
Resolution Meaning
1 V
– – ru.19
Display of actual DC link voltage in volt. The value is measured at the
DC output terminals of the COMBIVERT R6-N.
No.
Name
CP.10
peak DC voltage
Value range Meaning
0…1000 V r/w Enter based on
– – ru.20
Parameter CP.10 enables to recognize voltage peaks within an operating cycle. For that the highest value of CP.09 is stored in CP.10. The peak value memory can be cleared by pressing the UP and DOWN key or via bus by writing any value you like to the address of CP.10. Switching off COMBIVERT R6-N also clears the memory.
No.
Name
CP.11
power module temperature
Resolution
1 °C
Meaning r/w Enter based on
– – ru.38
Display of the actual power module temperature. On exceeding the maximum power module temperature (see "Technical data") the modulation is switched off and error E.OH is displayed. Message E.nOH is displayed after the cooling period. The error can be reset now.
46
Special adjustments
No.
Name r/w Enter based on
CP.12
OL counter display
Resolution Meaning
1 %
– – ru.39
The permanent load of the COMBIVERT R6-N can be evaluated with this parameter, in order to avoid an E.OL error (in-time load reduction).
Error E.OL is released, if the overload counter reaches 100 %.
No.
Name
CP.13
actual power
Resolution
0.1 kW r/w Enter based on
– – ru.81
Meaning
CP.13 displays the actual power of the COMBIVERT R6-N. Motor power is displayed with positive values, generatoric power is displayed with negative values.
No.
Name
CP.14
total regen
Resolution
1 kW r/w Enter based on
–
Meaning
Counter for the regeneratoric electric work to mains.
– ru.82
No.
Name
CP.15
total motor
Resolution
1 kW r/w Enter based on
– – ru.83
Meaning
Counter for the supplied electrical work from mains in kWh.
No.
Name
CP.16
total net
Resolution
1 kW r/w Enter based on
– – ru.84
Meaning
Display of the difference between supplied and regeneratoric work.
The result is displayed by right sign.
No.
Name
CP.17
Actual net
Resolution
0.01 kVA r/w Enter based on
– – ru.85
Meaning
Display of the current apparent power at the mains input.
5.6 Special adjustments
The power supply and regenerative unit can be adapted to the application with the following parameters.
47
Special adjustments
No.
Name
0…±20,00 r/w Enter based on
CP.18
ANOUT1 gain yes – An.33
The analog output displays the difference between actual supply frequency and set supply frequency. At factory setting of CP.18 this corresponds to 1 V per 0.1 Hz difference. The display occurs with right sign. The reference value of 50 or 60 Hz is determined during power on.
Setting range Setting Meaning
1.00
The amplification to the desired output voltage can be adapted with CP.18. Max. possible: ±10 V.
No.
Name
CP.19
DC switching level
0…3200.00 V 600.00 V r/w Enter based on yes – LE.00
This parameter determines the switching level for transistor output O1, as well as relay output 2.
Setting range Setting Meaning
The switching condition is fulfilled and the transistor output is set if the DC voltage level exceeds the adjusted value in CP.19. Relay output 2 is set, if the load shunt relay is additionally tightened.
No.
Name
CP.20
general fault reset r/w yes
Enter
– based on
Pn.15
A general fault reset can be activated with this parameter. Attention, the machine manufacturer must observe appropriate protective measures for operating personnel and machine.
Setting range
0
1…10
Setting Meaning
No general fault reset.
3
Maximum errors, which are reset within one hour. If the number of errors per hour exceeds the adjusted value in CP.20, only a manual reset via the terminal strip can be made.
48
Special adjustments
No.
CP.21
CP.22
CP.23
CP.24
CP.25
CP.26
CP.27
Name last error last error -1 last error -2 last error -3 last error -4 last error -5 last error -6
CP.28
last error -7 r/w Enter based on
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
In.24 set 0
In.24 set 1
In.24 set 2
In.24 set 3
In.24 set 4
In.24 set 5
In.24 set 6
In.24 set 7
Parameters CP.21…CP.28 display the last eight errors. With exception error "undervoltage
E.UP" is not stored. The oldest error is displayed in CP.28. A new error is stored in CP.21.
All other errors are shifted to the next parameter. The oldest error (CP.28) is not applicable.
The meaning of the error messages is described in parameter CP.01.
No.
Name
CP.29
software version
Value range Meaning
0.00…9.99
r/w Enter based on
– –
Display of the inverter software version number (e.g. 1,11).
In.06
No.
Name
CP.30
software date
Value range
0…6553.5
Meaning r/w Enter based on
– –
Display of the inverter software date in the format „ddmm.y“.
In.07
No.
Name
CP.31
power unit code r/w Enter based on
– – Sy.03
The COMBIVERT R6-N detects the connected supply system (230 V/400 V) at the first switching on. Depending on the supply system the COMBIVERT R6-S adjusts internally certain parameter values.
If the COMBIVERT R6-N is connected to another supply system, these stored parameter values are not valid any longer. Error message "power unit changed (E.Puch)" is displayed.
Value range Meaning
0…32767
If the displayed value is written, only the power unit dependent parameters are re-initialised.
No.
Name
CP.32
puls off level r/w Enter based on yes – cS.06
Value range
0.0…-1000.0 kW
Standard Meaning
-0.8 kW
If the adjusted regenerative power is decreased, the COM-
BIVERT R6-N switches the modulation off after turn-off delay and changes into standby mode (display: „Stb“).
49
Special adjustments
No.
Name
CP.33
operating mode r/w Enter based on yes yes Pn.19
This parameter determines the master or slave of regenerative units at parallel connection.
Further it is adjusted whether a harmonic filter or a commutation choke is series-connected.
Single units must be adjusted to master.
Value range
0
Meaning
Master with commutation reactor
3
4
1
2
5
Master with harmonic filter
Slave with commutation reactor
Slave with harmonic filter
Master-Slave with commutation reactor input selection
Master-Slave with harmonic filter input selection
No.
Name
CP.34
regeneration level
Value range
100…120 %
Meaning r/w Enter based on yes – cS.02
The regeneration level determines the starting value to energy regeneration. The adjusted value refers to the reference value of the DC voltage in percentage. The status changes from Standby „Stb“ to regeneration „rEGEn“.
50
Annex A
A. Annex A
A.1 Dimension of power supply and regenerative units
Dimensioning of the power supply and regenerative unit onlyregeneration ?
no
Acquire:
C
ZK_all
CZK_all > CZK_max no
Acquire:
P
M
, P
Mmax
, t1, T, η
M,
η
G,
η
FI yes
Bridge over ext. load-shunt with contactor (special unit) yes
Decoupling R6-N (see 4.4.3 to
4.4.5)
Calculate: ILM, ILMmax
Acquire:
PM, PMmax, t1, T, ηM, ηG, ηFI
Calculate:
ILG, ILGmax
IDCmax > ILGmax yes
T < 300 s no t1 > 60 s no select higher unit or parallel connection of R6-N
(n • IDC, n • IDCmax) no yes yes select higher unit or parallel connection of R6-N (n • IDC, n • IDCmax)
IDCmax > ILMmax no yes
T < 300 s no yes t1 > 60 s no yes
IDC > ILM yes no
Calculate: ILG, ILGmax select higher unit or parallel connection of R6-N (n • IDC, n • IDCmax)
IDCmax > ILGmax no
IDC > ILG no yes yes
IDC > ILG no
Regenerative unit capable yes
Power supply / regenerative unit capable t
N
PM
PMmax t1
Mechanical power η
M
Max. mechanical power ηG
Overload time
Load cycle
Number R6-N
ILM
ILMmax
Motor efficiency
Gearbox efficiency
ηFU Inverter efficiency
DC load mot. current
IDC DC output current R6-N
IDCmax Max. DC output current
ILG
ILGmax Max. DC load regen. current
Max. DC load mot. current CZK_all DC link capacity of all fre-
CZK_ max
R6-N
DC load regen. current quency inverters
Max. connecting capacity
R6-N
Figure 23: Dimension of power supply and regenerative units
51
Annex A
A.2 DC link capacities of KEB frequency inverters
Housing size
200 V units
05
13
14
15
16
17
07
09
10
12
18
19
20
21
Capacity
780 µF
880 µF (940 µF*)
1080 µF
1080 µF
2220 µF
3280 µF
4100 µF
4100 µF
5040 µF
9900 µF
13200 µF
15600 µF
16500 µF
19800 µF
Frequency inverter F5
Housing size
400 V units
05
07
09
10
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Capacity
180 µF
180 µF (300 µF*)
300 µF
345 µF
470 µF
580 µF
650 µF
940 µF
1290 µF
1640 µF
1875 µF
2700 µF
3900 µF
4950 µF
4950 µF
6350 µF
8400 µF
9900 µF
11700 µF
27
28(P)/28(W)
29(P)/(W)
30
31
32-35
36
14100 µF
16200 / 19800 µF
19800 / 23400 µF
28200 µF
32900 µF
39600 µF
59400 µF
* Special unit
52
Annex A
Housing Unit size
A
B
C
D
E
7
9
10
12
13
13
14
15
13
14
15
16
16
17
18
19
Frequency inverter G6
Capacity / µF Precharging circuit
135
195 Type A1
235
470
560
Type A1
680
Type A1
750
680
Type A1
840
1120
1035
1400
1985
Type B1
Housing Unit size
2
4
7
9
10
12
13
Frequency inverter S6
Capacity / µF Precharging circuit
195
195 Type A1
235
470
560
Type A1
Attention
Ferrites at the input and output are required in any case when using
G6/S6.
53
Annex A
A.3 Decoupling diodes
Use decoupling diodes when using the R6 as regenerative unit only, to avoid that the connected inverters cannot be supplied via the regenerative unit. Appropriate decoupling diodes are defined for the different sizes.
A.3.1 Assignment
R6-N Material number
15
19
25
29
0090147-3500
0090147-4101
0090147-6009
0090147-6009
Type
1600 V / 80 A
1600 V / 120 A
1600 V / 560 A
1600 V / 560 A
Volume
2
2
2
2 x 2
Ta [°C]
45
45
45
45
Legend
Ta: maximum ambient temperature
Th: maximum heat sink temperature
Rha: required thermal resistance of the heat sink at rated operation
(thermal value of the thermal compound ≥ 0.5 W/(m*K))
Th [°C] Rha [K/W]
90
90
90
90
1.50
0.84
0.19
0.09
A.3.2 Dimensions of the decoupling diodes
Material number Connection
0090147-3500 1 (anode)
2 (cathode) or
3 (anode)
1 (cathode)
Dimensions continued on the next page
54
Material number Connection
0090147-4101 1 (anode)
2 (cathode) or
3 (anode)
1 (cathode)
Dimensions
0090147-6009 3 (anode)
2 (cathode)
Annex A
Figure 24: Dimensions of the decoupling diodes
55
Annex B
B. Annex B
B.1 Certification
B.1.1 CE-Marking
CE marked power supply-/regenerative units were developed and manufactured to comply with the regulations of the Low-Voltage Directive 2006/95/EC.
The described units must not be started until it is determined that the installation complies with the Machine directive (2006/42/EC) as well as the EMC-directive (2004/108/EC)(note
EN 60204).
The power supply-/regenerative units meet the requirements of the Low-Voltage Directive 2006/95/EC. The harmonized standards of the series EN 61800-5-1 in connection with
EN 60439-1 and EN 60146 were used.
This is a product of limited availability in accordance with IEC 61800-3. This product may cause radio interference in residential areas. In this case the operator may need to take corresponding measures.
B.1.2 UL Certification
Acceptance according to UL is marked at KEB power supply and regenerative units with the adjacent logo on the type plate.
To be conform according to UL for the use on the North American Market the following instructions must be observed (original text of the UL file in English):
• Maximum Surrounding Air Temperature 45°C“
• Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000rms Symmetrical Amperes, 240 or 480 Volts Maximum“ and „When Protected by Fuses as listed below:
Feedback unit Cat.
No.
15R6 (240V)
Fuse
19R6 (240V)
15R6 (400/480V)
1) RK1 fast acting or J fast acting, rated 50A, min. 250V
2) Special purpose, type 3NC2240, rated 40A/690Vac, mfr. by
Siemens or type FWP-40A22FA, manufactured by Bussmann
1) RK1 fast acting or J fast acting, rated 90A, min. 250V
2) Special purpose, type 3NC2200, rated 100A/690Vac, mfr. by
Siemens or type FWP-40A22FA, manufactured by Bussmann
1) RK1 fast acting or J fast acting, rated 50A, min. 480V
2) Special purpose, type 3NC2240, rated 40A/690Vac, mfr. by
19R6 (400/480V)
Siemens or type FWP-40A22FA, manufactured by Bussmann
1) RK1 fast acting or J fast acting, rated 90A, min. 480V
2) Special purpose, type 3NC2200, rated 100A/690Vac, mfr. by
Siemens or type FWP-40A22FA, manufactured by Bussmann
• Use 75°C Copper Conductors Only“
• Use in a Pollution Degree 2 environment“
56
Annex B
• Following external DC fuses need to be installed in accordance with wiring diagrams in chapter 4.4 for following units without internal DC fuses:
15R6N1E-xxxx Rated 690 Vac / 700 Vdc 50 A (KEB No.: 009025H-3459):
R/C (JFHR2) - Type Sitor 3NE8-717-1, manufactured by Siemens or Type 170M1364-1, manufactured by Bussmann
Rated 690 Vac / 700 Vdc 125 A (KEB No.: 009025H-3559): 19R6N1E-xxxx
R/C (JFHR2) - Type Sitor 3NE8-722-1, manufactured by Siemens or Type 170M1368-1, manufactured by Bussmann
• For Feedback units 15R6N1E-xxxx and 19R6N1E-xxxx
In case of Semiconductor Fuses as specified in item 4 and 12 above, the marking shall also state that the Feedback unit and overcurrent protection device must be integrated within the same overall assembly (effective date: May 9, 2013)
• Only for 15R6N1E-xxxx and 19R6N1E-xxxx:
“Use max Wire Size: 8 AWG, strip wire insulation at 10 mm.”
“Use max Wire Size: 4 AWG, strip wire insulation at 16 mm.”
• Wiring terminals are marked to show a range of values or a nominal value of tightening torque in pound-inches to be applied to the clamping screws as shown below:
Mains Terminals AWG 8: 20.5 lb-in (2.3 Nm)
Mains Terminals AWG 4: 18.0 lb-in (2.0 Nm)
57
Notes
58
Notes
59
KEB Automation KG
Südstraße 38 • D-32683 Barntrup fon: +49 5263 401-0 • fax: +49 5263 401-116 net: www.keb.de
• mail: [email protected]
KEB worldwide…
KEB Antriebstechnik Austria GmbH
Ritzstraße 8 • A-4614 Marchtrenk fon: +43 7243 53586-0 • fax: +43 7243 53586-21 net: www.keb.at
• mail: [email protected]
KEB Antriebstechnik
Herenveld 2 • B-9500 Geraadsbergen fon: +32 5443 7860 • fax: +32 5443 7898 mail: [email protected]
KEB Power Transmission Technology (Shanghai) Co.,Ltd.
No. 435 Qianpu Road, Chedun Town, Songjiang District,
CHN-Shanghai 201611, P.R. China fon: +86 21 37746688 • fax: +86 21 37746600 net: www.keb.de
• mail: [email protected]
KEB Antriebstechnik Austria GmbH
Organizační složka
K. Weise 1675/5 • CZ-370 04 České Budějovice fon: +420 387 699 111 • fax: +420 387 699 119 mail: [email protected]
KEB Antriebstechnik GmbH
Wildbacher Str. 5 • D–08289 Schneeberg fon: +49 3772 67-0 • fax: +49 3772 67-281 mail: [email protected]
KEB España
C/ Mitjer, Nave 8 - Pol. Ind. LA MASIA
E-08798 Sant Cugat Sesgarrigues (Barcelona) fon: +34 93 897 0268 • fax: +34 93 899 2035 mail: [email protected]
Société Française KEB
Z.I. de la Croix St. Nicolas • 14, rue Gustave Eiffel
F-94510 LA QUEUE EN BRIE fon: +33 1 49620101 • fax: +33 1 45767495 net: www.keb.fr
• mail: [email protected]
KEB (UK) Ltd.
Morris Close, Park Farm Industrial Estate
GB-Wellingborough, NN8 6 XF fon: +44 1933 402220 • fax: +44 1933 400724 net: www.keb.co.uk
• mail: [email protected]
KEB Italia S.r.l.
Via Newton, 2 • I-20019 Settimo Milanese (Milano) fon: +39 02 3353531 • fax: +39 02 33500790 net: www.keb.de
• mail: [email protected]
KEB Japan Ltd.
15–16, 2–Chome, Takanawa Minato-ku
J-Tokyo 108-0074 fon: +81 33 445-8515 • fax: +81 33 445-8215 mail: [email protected]
KEB Korea Seoul
Room 1709, 415 Missy 2000
725 Su Seo Dong, Gang Nam Gu
ROK-135-757 Seoul/South Korea fon: +82 2 6253 6771 • fax: +82 2 6253 6770 mail: [email protected]
KEB RUS Ltd.
Lesnaya Str. House 30, Dzerzhinsky (MO)
RUS-140091 Moscow region fon: +7 495 632 0217 • fax: +7 495 632 0217 net: www.keb.ru
• mail: [email protected]
KEB America, Inc.
5100 Valley Industrial Blvd. South
USA-Shakopee, MN 55379 fon: +1 952 224-1400 • fax: +1 952 224-1499 net: www.kebamerica.com
• mail: [email protected]
More and latest addresses at http://www.keb.de
Document
© KEB
Part/Version GBR
Date
20116581
01
2016-10-07
Download
Advertisement
Key features
Converts AC to DC
Supplies KEB frequency inverters
Regenerates excess energy
Reduces energy demand
Reduces heat emission
Overcurrent, ground fault and temperature protected
DC fuses for short-circuit protection
Frequently asked questions
The COMBIVERT R6-N is a power supply and regenerative unit that serves exclusively for the supply of frequency inverters with DC input and/or regeneration of excess energy into the supply system. It is not intended for other electrical consumers.
The COMBIVERT R6-N converts AC to DC, supplies KEB frequency inverters, regenerates excess energy, reduces energy demand and heat emission, and is protected against overcurrent, ground fault and temperature. It also has DC fuses for short-circuit protection.
The regenerative unit feeds back the excess energy from generatoric operation into the supply system. This reduces the energy demand and heat emission, makes it environmentally friendly and space-saving, replaces braking resistor and braking transistor, and is cost-saving.
Before working with the unit, always ensure the system is switched off and secured. The DC link capacitors may still be charged with high voltage after switching off the supply system. It is recommended to wait at least 5 minutes before working with the unit after it has been switched off. Always check the isolation from the supply by measurements in the unit.