ICP PROFI-5060 User manual


Add to my manuals
45 Pages

advertisement

ICP PROFI-5060 User manual | Manualzz

PROFI-5000

User Manual

Warranty

All products manufactured by ICP DAS are warranted against defective materials for a period of one year from the date of delivery to the original purchaser.

Warning

ICP DAS assumes no liability for damages consequent to the use of this product. ICP DAS reserves the right to change this manual at any time without notice. The information furnished by ICP

DAS is believed to be accurate and reliable. However, no responsibility is assumed by ICP DAS for its use, or for any infringements of patents or other rights of third parties resulting from its use.

Copyright

Copyright 2009 by ICP DAS Co., LTD. All rights reserved worldwide.

Trademark

The names used for identification only may be registered trademarks of their respective companies.

Revision Note

Release

Add PROFI-5017/

PROFI-5017C/ PROFI-5024

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------1

Table of Content

4.

5.

1.

2.

3.

Introduction .............................................................................................................................. 3

1.1.

1.2.

Overview .................................................................................................................... 3

Product Information ............................................................................................... 3

1.3.

1.4.

Features ..................................................................................................................... 3

Specifications ........................................................................................................... 4

Hardware ...................................................................................................................................6

2.1.

2.2.

2.3.

2.4.

Bus Wiring ................................................................................................................. 6

PROFIBUS Cable and Transmission Distance ................................................ 7

Status Indicator ........................................................................................................ 8

Connector ................................................................................................................ 10

2.5.

2.6.

Node Address ......................................................................................................... 11

Baud rate support ................................................................................................. 13

2.7.

PROFIBUS DP System ......................................................................................................... 24

3.1.

3.2.

Pin assignment and I/O wiring

Power On / Reset ................................................................................................... 25

Wait Parameterization

.......................................................................... 14

.......................................................................................... 25

3.3.

3.4.

Wait Configuration ................................................................................................ 27

Data Exchange ....................................................................................................... 27

Establish connection with PROFI-5000 ........................................................... 34 3.5.

3.6. Diagnostic Message Report ............................................................................... 35

PROFI-5000 Guideline (for SIMATIC Step 7) .................................................................. 36

Appendix AFAQ ................................................................................................................. 45

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------2

1. Introduction

1.1. Overview

PROFIBUS is an open, digital communication system with a wide range of applications, particularly in the fields of factory automation and process automation. PROFIBUS is suitable for both fast, time-critical applications and complex communication tasks. PROFIBUS-DP is a famous protocol that enables simple, fast, cyclic and deterministic process data exchange between

Master and assigned Slave.

The PROFI-5000 Compact Remote I/O Module is specially designed for the slave device of PROFIBUS DP protocol. To setup PROFIBUS network, users can choose and configure I/O modules by using the GSD file without any other setting tools.

1.2. Product Information

Type

Digital Output

Digital Input

Digital Input and

Digital Output

Power Relay Output

Analog

Input

Voltage &

Current

Analog Output

Model Description

PROFI-5045 24-channel Isolated Digital Output

PROFI-5051 24-channel Isolated Digital Input

PROFI-5052 12-channel Isolated Digital Input

PROFI-5053 24-channels Dry Contact

Non-Isolated Digital Input

PROFI-5050 16-channel Non-Isolated Digital

Input and 8-channel Non-Isolated

Digital Output

PROFI-5055 8-channel Isolated Digital Input and

8-channel Isolated Digital Output

PROFI-5060 8-channel Isolated Digital Input and

4-channel Relay Output

PROFI-5017 8-Ch Isolated Analog Voltage Input

PROFI-5017C 8-Ch Isolated Analog Current Input

PROFI-5024 4-Ch Isolated Analog Voltage &

Current Output

1.3. Features

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------3

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

Protocol & Hierarchy

Supports Transmission Rate

(Kbps)

Transmission Rate Setting

Address Setting

Indicators

I/O modules Configuration

Network Isolation Protection

DC Isolation Protection

DP-V0 Slave

9.6, 19.2, 45.45, 93.75, 187.5, 500,

1500, 3000, 6000, 12000 detected automatically

0~99 set by Rotary switches

PWR and RUN LED

Configured by GSD file

High Speed iCoupler

3000VDC on PROFIBUS side

PROFI-5017/ PROFI-5017C/ PROFI-5024

Protocol & Hierarchy

Supports Transmission Rate

(Kbps)

DP-V0 Slave

9.6, 19.2, 45.45, 93.75, 187.5, 500,

1500, 3000, 6000, 12000

Transmission Rate Setting

Address Setting detected automatically

0~126 set by Rotary switches or

SAA-telegram

Indicators

I/O modules Configuration

Network Isolation Protection

DC Isolation Protection

PWR LED and RUN LED,ERR LED

Configured by GSD file

High Speed iCoupler

3000VDC on PROFIBUS side

1.4. Specifications

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

PROFIBUS Interface

PROFIBUS Controller

9-pin D-Sub(Female)

Profichip VPCLS2

PROFIBUS Transceiver ADI ADM2486 iCoupler Isolated transceiver

Transmission Rate

Power Requirement

Power Consumption

Operating Temp.

Up to 12Mbps

10V ~ 40V

1W

-25℃ ~ +75℃

Storage Temp.

Humidity

-30℃ ~ +85℃

5% ~ 95%(Non Condensing)

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------4

PROFI-5017/ PROFI-5017C

PROFIBUS Interface

PROFIBUS Controller

9-pin D-Sub(Female)

Siemens SPC3

PROFIBUS Transceiver ADI ADM2486 iCoupler Isolated transceiver

Transmission Rate

Power Requirement

Power Consumption

Operating Temp.

Up to 12Mbps

10V ~ 40V

3W

-25℃ ~ +75℃

Storage Temp.

Humidity

-30℃ ~ +85℃

5% ~ 95%(Non Condensing)

PROFI-5024

PROFIBUS Interface

PROFIBUS Controller

PROFIBUS Transceiver ADI ADM2486 iCoupler Isolated transceiver

Transmission Rate Up to 12Mbps

Power Requirement

Power Consumption

Operating Temp.

9-pin D-Sub(Female)

Siemens SPC3

10V ~ 40V

4W

-25℃ ~ +75℃

Storage Temp.

Humidity

-30℃ ~ +85℃

5% ~ 95%(Non Condensing)

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------5

2. Hardware

2.1. Bus Wiring

In order to minimize the reflection effect of the signal transmission,

PROFIBUS device has to fit with an active terminal resistor at both first node and last node, as shown below

However, the number of station in PROFIBUS network is also restricted.

According to PROFIBUS specification, it is up to 32 stations connected in a

PROFIBUS segment. If more than 32 stations are connected, the PROFIBUS repeater must be used to link the individual bus segments.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------6

2.2. PROFIBUS Cable and Transmission Distance

The PROFIBUS cable with following properties has different transmission distance with respect to different transmission rate, shown in the following table

1. Impedance :135~165Ω

2. Capacity : lower than 30 pF/m

3. Loop resistance : lower than 110Ω/Km

4. Wire diameter : larger than 0.65mm

5. Core cross-section : larger than 0.34mm

2

Transmission Rate(Kbps) Transmission Distance per Segment (meter)

9.6, 19.2, 45.45, 93.75 1200

187.5 1000

500 400

1500 200

3000, 6000, 12000 100

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------7

2.3. Status Indicator

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

It provides two status indicator, they are PWR LED (red) and RUN LED

(green). When the power is supplied to module, PWR LED will turn on; If

CHK_CFG procedure is finished, RUN LED will turn on. The table explains the relationship between them.

Status Indicator Meaning Recommend solution

PWR ON &

RUN OFF

Master not Ready, or

Address not Match or

Cfg Fault(Note 2.)

PWR ON &

RUN ON

Module is in clear mode or Operate mode*.

PROFI-5017/ PROFI-5017C/ PROFI-5024

1. Check the address setting of module and DP-master.

2. Sets the DP-Master to operation mode.

3. Make sure of the consistency of Module Selection.

N/A

It provides three types of status indicator, they are PWR LED (yellow),

ERR LED (red) and RUN LED (green). When the power is supplied to module,

PWR LED will turn on; If CHK_CFG procedure is finished, RUN LED will turn on and ERR LED will turn off. The table explains the relationship between

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------8

them.

Status Indicator

ERR ON &

RUN OFF

ERR Flash(10Hz)

ERR Flash(2Hz)

Meaning

Offline Mode

Stop Mode

Prm Fault

Recommend solution

Check the address setting of module and DP-master.

Check the DP-Master is ready to communicate with module.

Check the setting of module in the master interface and make sure of the consistency.

Same as above ERR Flash(1Hz) Cfg Fault

ERR ON & RUN ON Clear Mode

Sets the DP-Master from clear mode to operation mode

ERR OFF &

RUN ON

Operate Mode

PWR &

ERR Flash lnterlace(2Hz)

Diag Exist

(Diag. Msg. Request)

Check the Input/Output value that if exceed/under the limit

Note 1: “Prm Fault” is the abbreviation of “Parameter Fault”; It means that the number of parameter data which receive from DP-Master is not consistency with DP-Slave (PROFI-5017(C)), and it could due to the difference between module installation and master setting.

Note 2:“Cfg Fault” is the abbreviation of “Configuration Fault”, it means that the number of configuration data which receive from DP-Master is not consistency with DP-Slave (PROFI-5017(C)), and it could due to the wrong order of installation.

Note *: there are four kinds of state in PROFIBUS DP Master.

1. Offline mode: Master not active on the bus.

2. Stop mode: Master only transmit token on the bus, and PROFIBUS DP is not active.

3. Clear mode: DP Master active, but all output are zero or set to fail-safe state.

4. Operate mode: DP Master full active.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------9

2.4. Connector

The connector of PROFI-5000 is shown below

Pin No. Signal Meaning

3 B-Line Receive/Transmit data - plus

4 CNTR-P Repeater control signal, RTS signal

5

6

GND

VP

Power ground of active terminator

Power 5 volt of active terminator

8 A-Line Receive/Transmit data - minus

Note: The connector of PROFI-5000 has no terminators; users must use the connector with the terminator inside. The power of the terminator will provide by terminal device.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------10

2.5. Node Address

The figure shown above is the decimal rotary switch. It dominates the node (station) address of PROFI-5000. The switch is which labeled MSB is high nibble of address and the other one is low nibble of address.

According to PROFIBUS specification, the station address which from 0 to

126 is valid, and the address 126 is a special address that supports the remote setting SSA telegram from Class 2 DP-Master.

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

- It doesn’t support SSA service for setting node address.

PROFI-5017/ PROFI-5017C/ PROFI-5024

- Module applies the setting of rotary switch as its address if the address is valid. While the address is invalid, module loads the pre-saved value from EEPROM. Moreover, if the address is invalid (126) again, module awaits the SSA telegram and applies it. (Note: If you want to clear the setting stored at EEPROM, you just adjust rotary switch to FF before the power supplied).

SSA Telegram Rotary

Switch(dec)

0~125

126~254

Pre-saved address

(EEPROM)

Do not care No Accept

PROFI-5017(C)

Station Address

Rotary Switch address(EEPROM) with SSA Telegram and address 0~125 save address to

EEPROM

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------11

255 Clear to 126 Accept with address 0~125

SSA telegram and save address to

EEPROM

Note 1: Only one DP-Slave station with address 126 permitted in the bus.

Note 2: if you want to change the station address after data exchange,

PROFI-5017(C) should return to Wait-Prm state and wait for one second to apply the new address.

PROFI-5000 series

EX 1 : MSB => 0, LSB => B,

0 < (0*16+11) = 11 < 125 => Station Address = 11

EX 2 : MSB =>7, LSB => 9,

0 < (7*16+9) = 121 < 125 => Station Address = 121

PROFI-5017/ PROFI-5017C/ PROFI-5024

EX 3 : MSB =>7, LSB => F, EEPROM => 15,

126 < (7*16+F) = 127 < 254

Station Address = Pre-saved address (EEPROM) = 15

EX 4 : MSB => 8, LSB => A, EEPROM => 126,

126 < (8*16+A) = 128 < 254

Station Address = SSA Telegram and save address to EEPROM

EX 5 : MSB =>F, LSB => F,

(F*16+F) = 255

Station Address = SSA Telegram and save address to EEPROM

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------12

2.6. Baud rate support

PROFI-5000 supports the entire baud rates of PROFIBUS. They are 9.6Kbps,

19.2Kbps, 45.45Kbps, 187.5Kbps, 500Kbps, 1.5Mbps, 3Mbps, 6Mbps, and

12Mbps. Because PROFI-5000 has a functionality of auto- detection for baud rates, users don’t need to set the baud rate manually.

Note: Many baud rates only are supported by the particular cable or speed.

For the detail, please refer to the above section “PROFIBUS Cable and

Transmission Distance”

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------13

2.7. Pin assignment and I/O wiring

 PROFI-5045

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------14

 PROFI-5050

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------15

 PROFI-5051

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------16

 PROFI-5052

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------17

 PROFI-5053

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------18

 PROFI-5055

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------19

 PROFI-5060

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------20

 PROFI-5017

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------21

 PROFI-5017C

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------22

 PROFI-5024

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------23

3. PROFIBUS DP System

The flow chart of the DP-slave

Power On / Reset

Invalid

Address

Valid Address /

SSA_Telegram

Wait Parameter

Slave Diagnosis

Get Configuration

Check

Configuration

Not Ok

Wait Configuration

Slave Diagnosis

Set Parameter OK

Get Configuration

Check

Configuration

Not Ok /

Set Parameter

Not Ok

Data Exchange

Data Exchange

Check Configuration OK

Set Parameter Ok

Read Input

Read Output

Get Configuration

Slave Diagnosis

Before DP-Slave changes to data exchange state, it employs some telegrams to initialize and establish the connection with DP-Master. These telegrams include Slave Diagnosis (Slave_Diag), Set Parameter (Set_Prm),

Check Configuration (Chk_Cfg), Slave Diagnosis, Data Exchange (Data_Exch) and optional global control (GC). The explanation is as follows:

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------24

3.1. Power On / Reset

While the power supplied, PROFI-5000 loads the value of rotary switches first and decides to apply it immediately. Be attention to duplicate address setting with others, it may occur any unpredictable accident.

3.2. Wait Parameterization

In order to establish the connection completely, the DP-Slave should obtain enough information from the DP-Master. The DP-Slave applies the parameterization data to the I/O module of DP-Slave. DP-master divided these parameters into two parts: one is master-related parameter, and another one is module-related parameter. Master-related parameters provide the common setting between DP-Master and DP-Slave (e.g. Byte-Order).

Module-related parameters provide the fundamental setting of the I/O modules in DP-Slave. If the parameters have been applied successfully, DP-state will switch to wait configuration, otherwise return to wait parameter.

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

- Module has no parameterization data.

PROFI-5017/ PROFI-5017C

System Parameters - Byte Order

Byte order is an important factor related to the memory allocation.

Big-endian byte order (Motorola format) allocates more significant byte in lower memory address. On the other hand, little-endian Byte order (Intel format) allocates more significant byte in higher memory address.

For example, the integer which value is 0x0400(hex) will allocates

0x40(hex) in the first byte of the memory allocated to the integer and 0x00(hex) in the second byte.

Module Parameters

PROFI-5017(C) is a standard analog input module; it requires the parameter of “Data Format”, “Data Range” and “Diag Enable” to establish the connection completely.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------25

“Data range” means the measurement type (voltage, current) and range.

1. Volt Inp. Range: +/- 10.0 V

2. Volt Inp. Range: +/- 5.0 V

3. Volt Inp. Range: +/- 2.5 V

4. Volt Inp. Range: +/- 1.25 V

5. Curr Inp. Range: 0 ~20000uA

“Data format” can be selected either engineer unit format or hexadecimal format.

“Diag Enable” is a flag that determines PROFI-5017(C) whether diagnostic message will report or not.

PROFI-5024

System data -- Byte Order

Byte order is an important factor related to the memory allocation.

Big-endian byte order (Motorola format) allocates more significant byte in lower memory address. On the other hand, little-endian Byte order (Intel format) allocates more significant byte in higher memory address.

For example, the integer which value is 0x0400(hex) will allocates

0x40(hex) in the first byte of the memory allocated to the integer and 0x00(hex) in the second byte.

I/O module data -- Module Parameters

PROFI-5024 is a standard analog output module; it requires the data of

“Data Format” and “Diag Enable” to establish the connection completely.

Data format can be selected either engineer unit format or hexadecimal format and output type (voltage, current).

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------26

“Diag Enable” is a flag that determines PROFI-5024 whether diagnostic message will report or not.

On the other hand, PROFI-5024 has the Safe Value output mechanism. It can output the Safe Value while PROFI-5024 has been changed to stop mode

(or offline mode). The safe value can make sure of the correctness of operating. There are three modes in safe value for users: Retain Last Value,

Clear Output and Switch to Substitute Value.

“Retain Last Value” is that PROFI-5024 retain the last valid output value for the corresponding channel.

“Clear Output” clear the corresponding channel to analog zero volt, analog zero ampere.

“Substitute Value” follows Safe mode selection in module parameter, it is setting by user, it must be obey the data range of corresponding data format and type-code.

3.3. Wait Configuration

Configuration data generates by configuration tools according to GSD file.

The users select the module he wants, and configuration data generate correspondingly.

If the module installed is not consistency with configuration, “configuration fault” diagnosis message will report by slave device.

3.4. Data Exchange

After the configuration procedure has been accomplished, PROFI-5000 exchanges I/O data with the DP-Master cyclically. In following section, we introduce the Numeric Notation and Byte Order briefly.

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

Byte Order

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------27

It support only little-endian Byte Order. The digital input or output module arrange its data as follow (for example: 4-Byte INPUT).

PROFI-5017/ PROFI-5017C

Byte Order

PROFI-5017(C) has 8 analog channels. Every channel has 2 bytes. For example, the following figure shows data arrangement of PROFI-5017(C).

Note : The order of I/O data is ranked by channel’s identifier, so the channel with lower ID has priority over the channel with higher ID.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------28

PROFI-5024

Byte Order

PROFI-5024 has 4 analog channels. Every channel has 2 bytes. For example, the following figure shows data arrangement of PROFI-5024.

Note: The order of I/O data is ranked by channel’s identifier, so the channel with lower ID has priority over the channel with higher ID.

3.4.1. Numeric Representation

PROFI-5017/ PROFI-5017C

+/- 10 V :

The range for Engineer-Unit: -10000~10000(mV)

The range for 2’s complement hexadecimal: 0000~1FFF (0v ~ 10v),

2000~3FFF (-10v~1.22mV)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------29

HexValue=

EngineerVa lue

× 8192-1 if 0≦EngineerValue≦10000

10000

HexValue=

EngineerVa lue

× 8192+16384 if -10000≦EngineerValue<0

10000

Measurement Value Decimal Hexadecimal

+10v(Engineer mode)

0v(Engineer mode)

-10v(Engineer mode)

+10v(Hex mode)

+5v(Hex mode)

0v(Hex mode)

-5v(Hex mode)

-10v(Hex mode)

10000

0

-10000

8191

4095

0

12288

8192

0x2710

0x0000

0xD8F0

0x1FFF

0x1000

0x0000

0x3000

0x2000

+/- 5 V :

The range for Engineer-Unit: -5000~5000(mV)

The range for 2’s complement hexadecimal: 0000~1FFF (0v ~ 5v),

2000~3FFF (-5v~0.61mV)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

HexValue=

EngineerVa lue

× 8192-1 if 0≦EngineerValue≦5000

5000

HexValue=

EngineerVa lue

× 8192+16384 if -5000≦EngineerValue<0

5000

Measurement Value Decimal Hexadecimal

+5v(Engineer mode)

0v(Engineer mode)

-5v(Engineer mode)

+5v(Hex mode)

+2.5v(Hex mode)

0v(Hex mode)

-2.5v(Hex mode)

-5v(Hex mode)

5000

0

-5000

8191

4095

0

12288

8192

0x1388

0x0000

0xEC78

0x1FFF

0x1000

0x0000

0x3000

0x2000

+/- 2.5 V :

The range for Engineer-Unit: -2500~2500(mV)

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------30

The range for 2’s complement hexadecimal: 0000~1FFF (0v ~ 2.5v),

2000~3FFF (-2.5v~0.3mV)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

HexValue=

EngineerVa lue

× 8192-1 if 0≦EngineerValue≦2500

2500

HexValue=

EngineerVa lue

× 8192+16384 if -2500≦EngineerValue<0

2500

Measurement Value Decimal Hexadecimal

+2.5v(Engineer mode) 2500

0v(Engineer mode) 0

-2.5v(Engineer mode) -2500

+2.5v(Hex mode) 8191

+1.25v(Hex mode)

0v(Hex mode)

-1.25v(Hex mode)

-2.5v(Hex mode)

4095

0

12288

8192

0x09C4

0x0000

0xF63C

0x1FFF

0x1000

0x0000

0x3000

0x2000

+/- 1.25 V :

The range for Engineer-Unit: -1250~1250(mV)

The range for 2’s complement hexadecimal: 0000~1FFF (0v ~ 1.25v),

2000~3FFF (-1.25v~0.15mV)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

HexValue=

EngineerVa lue

× 8192-1 if 0≦EngineerValue≦1250

1250

HexValue=

EngineerVa lue

× 8192+16384 if -1250≦EngineerValue<0

1250

Decimal Measurement Value

+1.25v(Engineer mode) 1250

0v(Engineer mode) 0

-1.25v(Engineer mode) -1250

+1.25v(Hex mode) 8191

+0.675v(Hex mode)

0v(Hex mode)

4095

0

-0.675v(Hex mode)

-1.25v(Hex mode)

12288

8192

Hexadecimal

0x04E2

0x0000

0xFB1E

0x1FFF

0x1000

0x0000

0x3000

0x2000

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------31

0 ~ 20 mA :

The range for Engineer-Unit: 0~20000(uA)

The range for 2’s complement hexadecimal: 0000~1FFF (0mA ~ 20mA)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

HexValue=

EngineerVa lue

× 8192-1 if 0≦EngineerValue≦20000

20000

Measurement Value

20mA(Engineer mode)

Decimal

20000

Hexadecimal

0x4E20

10mA(Engineer mode) 10000 0x2710

0mA(Engineer mode) 0 0x0000

20mA(Hex mode) 8191 0x1FFF

10mA(Hex mode) 4095 0x1000

0mA(Hex mode) 0 0x0000

PROFI-5024

+/-10V :

The range for Engineer-Unit: -10000~10000(mV)

The range for 2’s complement hexadecimal:

0000~7FFF (0v ~ 10v), 8000~FFFF (-10v~0.3mV)

Conversion from Engineer-Unit to two’s complement hexadecimal:

EngineerVa lue

HexValue= 10000 × 32768-1 if 0≦EngineerValue≦10000

EngineerVa lue

HexValue= 10000

Measurement Value

10v(Engineer mode)

0v(Engineer mode)

-10v(Engineer mode)

10v(Hex mode)

0v(Hex mode)

-10v(Hex mode)

× 32768+65536 if-10000≦EngineerValue<0

Decimal

10000

0

-10000

32767

0

-32768

+20mA :

The range for Engineer-Unit: -20000~20000(uA)

Hexadecimal

0x2710

0x0000

0xD8F0

0x7FFF

0x1000

0x8000

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------32

The range for 2’s complement hexadecimal: 0000~7FFF (0v ~ +20mA)

Conversion from Engineer-Unit to 2’s complement hexadecimal:

EngineerVa lue

HexValue= 20000

Measurement Value

20mA(Engineer mode)

0mA(Engineer mode)

20mA(Hex mode)

0mA(Hex mode)

× 32768-1

Decimal

20000

0

32767

0

Hexadecimal

0x4E20

0x0000

0x7FFF

0x0000

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------33

3.5. Establish connection with PROFI-5000

Before establish the connection between DP-Master and PROFI-5000, user should obey the following step first.

First, users must load the electronic device description file(GSD file) of the

PROFI-5000(IPDS0C47) into the DP-Master, and select the corresponding modules. Finally change your DP-master from Offline state to Operate state.

While DP-Master changes to operate mode, PROFI-5000 will initial the modules and wait for Chk_Cfg telegram in order. If there is no error occurs,

PROFI-5000 proceeds into data exchange state. Users can observe the status indicator LED to know the state of PROFI-5000. At the meantime, if there is any error occurs, PROFI-5000 will return to wait configuration.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------34

3.6. Diagnostic Message Report

The diagnostic messages report to DP-Master when the DP-Slave has errors or the unusual event occurs. Usually, It report diagnosis due to following standard channel-related event.

PROFI-5045/ PROFI-5050/ PROFI-5051/ PROFI-5052/ PROFI-5053/

PROFI-5055/ PROFI-5060

- It doesn’t support diagnostic message report.

PROFI-5017/ PROFI-5017C/ PROFI-5024

- It support error code “2”,”3”,”7” and ”8”.

Error Code Error Type

0 Reserved

2 Under-voltage

3 Over-voltage

4 Overload

5 Over-temperature

6

7

Line/wire Break (Sensor Only)

Upper Limit Value Exceeded (Current)

8 Lower Limit Value Exceeded(Current, Sensor)

9 Error

10~15 Reserved

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------35

4. PROFI-5000 Guideline (for SIMATIC Step 7)

In this example, we use Siemens S7-300 PLC (as a PROFIBUS master)、 a PROFI-5017 (as a PROFIBUS slave) to read voltage(9v) from channel

0~channel 7.

Step 1:Open “SIMATIC Manager” tool and select “New Project Wizard” to open a new project.

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------36

Step 2:Double Click “Hardware” to open “HW Config”

Step 3:Install GSD file a. Click “Install GSD File”

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------37

b. Select the directory of PROFI-5017’s GSD file(ipds0c47.gsd) and click

“OK” c. Click “Install” d. Click “”OK”

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------38

Step 4:Setup PROFI-5017 module a. Select PROFI-5000 module b. Add a “PROFI-5017(C) module”

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------39

Step 5:Setup the parameters of the PROFI-5017 a. Use the default setting

Step 6:Download the HW settings into SIMATIC PLC a. Click “Save and Compile”

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------40

b. Click “Download”

Step 7:Edit “OB1” a. Double click “OB1” b. Variables used in the example LAD Program

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------41

c. Program

Step 8:Download the settings into SIMATIC PLC

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------42

Step 9:Make sure the RUN LED of the PROFI-5017 is ON.

Step 10:read voltage from channel 0~channel 7

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------43

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------44

5. Appendix AFAQ

1. HOW to reads voltage(9v) from PROFI-5017 (for SIMATIC Step7)?

2. HOW to reads current(10mA) from PROFI-5017C (for SIMATIC Step7)?

3. HOW to sends voltage(9v) from PROFI-5024 (for SIMATIC Step7)?

4. HOW to sends current(10mA) from PROFI-5024 (for SIMATIC Step7)?

PROFI-5000 Remote I/O Module User Manual (Version 1.1, Jun/2012) -------------45