SAFETY PRECAUTIONS
(Always read these precautions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly.
The precautions given in this manual are concerned with this product.
In this manual, the safety precautions are ranked as "DANGER" and "CAUTION".
DANGER
CAUTION
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
Note that the caution level may lead to a serious accident according to the circumstances. Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
Some failures of the GOT or cable may keep the outputs on or off.
An external monitoring circuit should be provided to check for output signals which may lead to a serious accident.
Not doing so can cause an accident due to false output or malfunction.
If a communication error (including cable disconnection) occurs while monitoring on the GOT, communication between the GOT and PLC CPU is suspended, and the GOT becomes inoperative as described below:
(1) GT1155-QSBD, GT1150-QLBD: Become inoperative
(2) PLC CPU shuts down and the GOT becomes inoperative.
For the system configuration with GOT, assuming communication error ocurrs in the GOT, the switches for critical operation to the system should be set in the device other than GOT. False output or malfunciton may occur.
Do not use the GOT as the warning device that may cause a serious accident.
An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning.
Failure to observe this instruction may result in an accident due to incorrect output or malfunction.
A
- 1
[DESIGN PRECAUTIONS]
DANGER
Incorrect operation of the touch switch(s) may lead to a serious accident if the GOT backlight is gone out.
When the GOT backlight goes out, the POWER LED flickers (green/orange) and the display section turns black and causes the monitor screen to appear blank, while the input of the touch switch(s) remains active.
This may confuse an operator in thinking that the GOT is in "screensaver" mode, who then tries to release the GOT from this mode by touching the display section, which may cause a touch switch to operate.
Note that the following occurs on the GOT when the backlight goes out.
•The POWER LED flickers (green/orange) and the monitor screen appears blank
CAUTION
Do not bundle the control and communication cables with main-circuit, power or other wiring.
Run the above cables separately from such wiring and keep them a minimum of 100mm (3.94in.) apart. Not doing so noise can cause a malfunction.
[MOUNTING PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the option function board on to/from the GOT.
Not doing so can cause the unit to fail or malfunction.
When installing the option function board or battery, or operating the reset switch, wear an earth band etc. to avoid the static electricity.
The static electricity can cause the unit to fail or malfunction.
A
- 2
[MOUNTING PRECAUTIONS]
CAUTION
Use the GOT in the environment that satisfies the general specifications described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the
GOT.
Securely connect the option function board to the connector provided for the board.
When inserting/removing a CF card into/from the GOT, turn the CF card access switch off in advance.
Failure to do so may corrupt data within the CF card.
When inserting a CF card into the GOT, push it into the insertion slot until the CF card eject button will pop out.
Failure to do so may cause a malfunction due to poor contact.
When removing a CF card from the GOT, make sure to support the CF card by hand, as it may pop out.
Failure to do so may cause the CF card to drop from the GOT and break.
[WIRING PRECAUTIONS]
DANGER
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
Please make sure to ground FG terminal of the GOT power supply section by applying 100 or less which is used exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT.
Not doing so can cause a fire, failure or malfunction.
A
- 3
[WIRING PRECAUTIONS]
CAUTION
Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
Insert the bus cables for QnA, ACPU, and motion controller (A series) into the GOT's bus interface connectors until they click into the place.
Check for proper insertion to avoid malfunctions.
[TEST OPERATION PRECAUTIONS]
DANGER
Before performing the test operations of the user creation monitor screen (such as turning ON or
OFF bit device, changing the word device current value, changing the settings or current values of the timer or counter, and changing the buffer memory current value), read through the manual carefully and make yourself familiar with the operation method.
During test operation, never change the data of the devices which are used to perform significant operation for the system.
False output or malfunction can cause an accident.
[STARTUP/MAINTENANCE PRECAUTIONS]
DANGER
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Connect the battery correctly.
Do not discharge, disassemble, heat, short, solder or throw the battery into the fire.
Incorrect handling may cause the battery to generate heat, burst or take fire, resulting in injuries or fires.
Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases.
Not switching the power off in all phases can cause a unit failure or malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
A
- 4
[STARTUP/MAINTENANCE PRECAUTIONS]
CAUTION
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull the cable portion.
Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.
Do not drop or apply any impact to the battery.
If any impact has been applied, discard the battery and never use it.
The battery may be damaged by the drop or impact.
Before touching the unit, always touch grounded metal, etc. to discharge static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
[DISPOSAL PRECAUTIONS]
CAUTION
When disposing of the product, handle it as industrial waste.
[TRANSPORTATION PRECAUTIONS]
CAUTION
When transporting lithium batteries, make sure to treat them based on the transport regulations.
(Refer to Appendix 3 for details of the regulated units.)
Before transporting the GOT, turn the GOT power on and check that the battery voltage status is normal on the Time setting & display screen (utilities screen). In addition, confirm that the adequate battery life remains on the rating plate.
Transporting the GOT with the low battery voltage or the battery the reached battery life may unstabilize the backup data unstable during transportation.
Make sure to transport the GOT main unit and/or relevant unit(s) in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual, as they are precision devices.
Failure to do so may cause the unit to fail.
Check if the unit operates correctly after transportation.
A
- 5
REVISIONS
Print Date
Mar., 2005
Oct., 2005
Manual Number
JY997D17501
JY997D17501
The manual number is given on the bottom left of the back cover.
Ver.
A First edition
B
Partial correcting
Revision
ABOUT MANUALS, ABBREVIATIONS AND GENERIC TERMS IN THIS
MANUAL, Chapter 1, Section 2.2, 3.1, 3.2, 4.2, Chapter 6, 7, Section 8.1,
8.4, 8.5, 9.2, 9.3, Chapter 10, 11, 12, 13, Section 14.1, 14.3, 16.2, 16.3,
17.4, Chapter 18, Appendix2, Appendix 4
Additions
Section 13.6, 16.4
Nov., 2006 JY997D17501 C
Partial correcting
ABOUT MANUALS, ABBREVIATIONS AND GENERIC TERMS IN THIS
MANUAL, Section 2.2, 7.1, 9.2, 9.3, 10.1, Chapter 11, Section 13.1,
Chapter 14, Section 16.3, 16.4, Appendix1, Appendix2, Appendix 4
Additions
Section 7.2, 13.7, 14.8, 14.9
May. 2007 JY997D17501 D
Partial revisions
ABBREVIATIONS AND GENERIC TERMS IN THIS MANUAL, ABOUT
MANUALS, Section 4.1, Appendix 4
Additions
Section 1.1, 2.2, 2.2.1, 2.2.2, 3.2, 3.3, 3.4, 4.2, Chapter 5, Section 6.1, 6.5,
7.1, 8.1.2, 8.3, 10.1.3, 11.2.1, 13.1.3, 16.4, 18.3, Appendix 1, Appendix 2
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.
© 2005 MITSUBISHI ELECTRIC CORPORATION
A
- 6
INTRODUCTION
Thank you for choosing the Mitsubishi Graphic Operation Terminal.
Before using the equipment, please read this manual carefully to use the equipment to its optimum.
OUTLINE PRECAUTIONS
• This manual provides information for the use of the graphic operation terminal. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment using the product associated with this manual should be of a competent nature, trained and qualified to the local and national standards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely familiar with all associated documentation for the said product. All maintenance should be carried out in accordance with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and coordinated manner in compliance to established safety practices. The operators should also be familiar with documentation which is connected with the actual operation of the completed equipment.
Note: the term 'completed equipment' refers to a third party constructed device which contains or uses the product associated with this manual.
• This product has been manufactured as a general-purpose part for general industries, and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
• When using this product combining other products, please confirm the standard and the code, or regulation which a user should suit. Moreover, please confirm the compatibility of this product to the system, machine, and apparatus with which a user is used for user itself.
• If in doubt at any stage of the installation of the product always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use, please consult the nearest Mitsubishi Electric distributor.
• Since the example indicated by this manual, technical bulletin, the catalog, etc. is reference, please use it after confirming the function and safety of equipment and system when employing. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples.
• About this manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, you have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric distributor.
A - 7
CONTENTS
1. OVERVIEW..................................................................... 1-1
2. SYSTEM CONFIGURATION.......................................... 2-1
3. SPECIFICATIONS.......................................................... 3-1
4. PART NAME................................................................... 4-1
5. EMC DIRECTIVE............................................................ 5-1
5.3 Wiring Precautions the Part which Matches the EMC Directives ...............................5-5
A - 8
6. INSTALLATION.............................................................. 6-1
7. WIRING........................................................................... 7-1
8. OPTION .......................................................................... 8-1
9. UTILITY FUNCTION ....................................................... 9-1
A - 9
10. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING).................................. 10-1
11. DISPLAY AND OPERATION SETTINGS
(GOT SET UP)............................................................ 11-1
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY
(TIME SETTING AND DISPLAY) ............................... 12-1
(PROGRAM/DATA CONTROL) ................................. 13-1
A - 10
14. GOT SELF CHECK (DEBUG & SELF CHECK) ........ 14-1
A - 11
15. CLEANING OF DISPLAY SECTION
(CLEAN) ..................................................................... 15-1
16. INSTALLATION OF CoreOS, BOOTOS AND STANDARD
MONITOR OS............................................................. 16-1
16.1 BootOS and Standard Monitor OS Required for Installation ..................................16-2
16.2 Prior Preparations for Installing BootOS and Standard Monitor OS.......................16-3
16.3 BootOS and Standard Monitor OS Installation Using CF Card ..............................16-4
16.4 When Installing the Different Version of BootOS, Standard Monitor OS................16-8
17. MAINTENANCE AND INSPECTION.......................... 17-1
17.4 Battery Voltage Low Detection and Battery Replacement......................................17-4
18. ERROR MESSAGE AND SYSTEM ALARM ............. 18-1
A - 12
APPENDICES................................................................ App-1
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000
INDEX .........................................................................Index-1
A - 13
ABOUT MANUALS
The following manuals are also related to this product.
In necessary, order them by quoting the details in the tables below.
For the handy GOT (GT1155HS-QSBD, GT1150HS-QLBD), refer to the Handy GOT User’s Manual provided separately.
Related Manuals
Manual Name
GT Designer2 Version2 Basic Operation/Data Transfer Manual (For GOT1000 Series)
Describes methods of the GT Designer2 installation operation, basic operation for drawing and transmitting data to GOT1000 series
(Sold separately)
*1
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 1/3
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 2/3
GT Designer2 Version2 Screen Design Manual (For GOT1000 Series) 3/3
Describes specifications and settings of the object functions used in GT Designer2
(Sold separately)
*1
GOT1000 Series Connection Manual 1/3
GOT1000 Series Connection Manual 2/3
GOT1000 Series Connection Manual 3/3
Describes system configurations of the connection method applicable to GOT1000 series and cable creation method
(Sold separately)
*1
GOT1000 Series Extended/Option Functions Manual
Describes extended functions and option functions applicable to GOT1000 series.
(Sold separately)
*1
*1 The manual in PDF-format is included in the GT Works2 and GT Designer2 products.
Manual Number
(Model Code)
SH-080529ENG
(1D7M24)
SH-080530ENG
(1D7M25)
SH-080532ENG
(1D7M26)
SH-080544ENG
(1D7M32)
A - 14
ABBREVIATIONS AND GENERIC TERMS
Abbreviations and generic terms used in this manual are as follows:
GOT
Abbreviations and generic terms
GT SoftGOT1000
GT1595 GT1595-X
GT1585V-S
GT1585
GT1585-S
GT1575V-S
GT157
GT1575-S
GT1575-V
GT156
GT1575-VN
GT1572-VN
GT1565-V
GT1562-VN
GOT1000 Series
GT155
GT1555-V
GT1555-Q
GT1550-Q
GOT900 Series
GOT800 Series
Description
Abbreviation of GT SoftGOT1000
Abbreviation of GT1595-XTBA, GT1595-XTBD
Abbreviation of GT1585V-STBA
Abbreviation of GT1585-STBA, GT1585-STBD
Abbreviation of GT1575V-STBA
Abbreviation of GT1575-STBA, GT1575-STBD
Abbreviation of GT1575-VTBA, GT1575-VTBD
Abbreviation of GT1575-VNBA, GT1575-VNBD
Abbreviation of GT1572-VNBA, GT1572-VNBD
Abbreviation of GT1565-VTBA, GT1565-VTBD
Abbreviation of GT1562-VNBA, GT1562-VNBD
Abbreviation of GT1555-VTBD
Abbreviation of GT1555-QTBD, GT1555-QSBD
Abbreviation of GT1550-QLBD
GT15
GT115
GT1020
, GT15
GT1155-Q
Abbreviation of GT1595, GT1585, GT157 , GT156 , GT155
Abbreviation of GT1155-QTBDQ, GT1155-QSBDQ, GT1155-QTBDA, GT1155-QSBDA,
GT1155-QSBD
Abbreviation of GT1150-QLBDQ, GT1150-QLBDA, GT1150-QLBD
Handy
GOT
GT11
GT1030
GT1150-Q
GT1155HS-Q Abbreviation of GT1155HS-QSBD
GT1150HS-Q Abbreviation of GT1150HS-QLBD
, GT11
Abbreviation of GT1155-Q, GT1150-Q, GT11 Handy GOT
Abbreviation of GT1030-LBD, GT1030-LBD2, GT1030-LBDW, GT1030-LBDW2
Abbreviation of GT1020-LBD, GT1020-LBD2, GT1020-LBL, GT1020-LBDW,
GT1020-LBDW2, GT1020-LBLW
GT10 , GT10
Abbreviation of GT1030, GT1020
Abbreviation of GOT-A900 series, GOT-F900 series
Abbreviation of GOT-800 series
Communication unit
Abbreviations and generic terms
Bus connection unit
Serial communication unit
RS-422 conversion unit
Ethernet communication unit
MELSECNET/H communication unit
MELSECNET/10 communication unit
CC-Link communication unit
Interface converter unit
*1 A9GT-QJ71LP23 + GT15-75IF900 set
*2 A9GT-QJ71BR13 + GT15-75IF900 set
*3 A8GT-J61BT13 + GT15-75IF900 set
Description
GT15-QBUS,GT15-QBUS2,GT15-ABUS,GT15-ABUS2,
GT15-75QBUSL,GT15-75QBUS2L,GT15-75ABUSL,GT15-75ABUS2L
GT15-RS2-9P,GT15-RS4-9S,GT15-RS4-TE
GT15-RS2T4-9P,GT15-RS2T4-25P
GT15-J71E71-100
GT15-J71LP23-25,GT15-J71BR13
GT15-75J71LP23-Z
*1
,GT15-75J71BR13-Z
*2
GT15-J61BT13,GT15-75J61BT13-Z
*3
GT15-75IF900
A - 15
Option unit
Abbreviations and generic terms
Printer unit
Video input unit
Video/RGB unit
RGB input unit
Video/RGB input unit
RGB output unit
CF card unit
GT15-PRN
GT15V-75V4
GT15V-75R1
GT15V-75V4R1
GT15V-75ROUT
GT15-CFCD
CF card extension unit
*1
GT15-CFEX-C08SET
External I/O unit
Sound output unit
GT15-DIO
GT15-SOUT
*1 GT15-CFEX + GT15-CFEXIF + GT15-C08CF set.
Option
Abbreviations and generic terms
Memory card CF card
Memory card adaptor
Option function board
Battery
Protective Sheet
USB environmental protection cover
Stand
Attachment
Backlight
Multi-color display board
Connector conversion box
Emergency stop sw guard cover
Description
Description
GT05-MEM-16MC, GT05-MEM-32MC, GT05-MEM-64MC,
GT05-MEM-128MC, GT05-MEM-256MC
GT05-MEM-ADPC
GT15-FNB, GT15-QFNB,GT15-QFNB16M, GT15-QFNB32M, GT15-QFNB48M, GT11-50FNB
GT15-BAT, GT11-50BAT
GT15-90PSCB, GT15-90PSGB,GT15-90PSCW,GT15-90PSGW,
GT15-80PSCB, GT15-80PSGB,GT15-80PSCW,GT15-80PSGW,
GT15-70PSCB, GT15-70PSGB, GT15-70PSCW, GT15-70PSGW,
GT15-60PSCB, GT15-60PSGB, GT15-60PSCW, GT15-60PSGW,
GT15-50PSCB, GT15-50PSGB, GT15-50PSCW, GT15-50PSGW,
GT11-50PSCB, GT11-50PSGB, GT11-50PSCW, GT11-50PSGW,
GT11H-50PSC,
GT10-30PSCB, GT10-30PSGB, GT10-30PSCW, GT10-30PSGW,
GT10-20PSCB, GT10-20PSGB, GT10-20PSCW, GT10-20PSGW
GT15-UCOV, GT11-50UCOV
GT15-90STAND, GT15-80STAND, GT15-70STAND, A9GT-50STAND,
GT05-50STAND
GT15-60ATT-97, GT15-60ATT-96
GT15-90XLTT, GT15-80SLTT, GT15-70SLTT, GT15-70VLTT,GT15-70VLTN,GT15-60VLTT,
GT15-60VLTN
GT15-XHNB, GT15-VHNB
GT11H-CNB-37S
GT11H-50ESCOV
Software
Abbreviations and generic terms
GT Works2 Version
GT Designer2 Version
GT Designer2
GT Converter2
GT Simulator2
GT SoftGOT1000
GT SoftGOT2
GX Developer
Description
SW D5C-GTWK2-E, SW D5C-GTWK2-EV
SW D5C-GTD2-E, SW D5C-GTD2-EV
Abbreviation of screen drawing software GT Designer2 for GOT1000/GOT900 series
Abbreviation of data conversion software GT Converter2 for GOT1000/GOT900 series
Abbreviation of screen simulator GT Simulator 2 for GOT1000 / GOT900 series
Abbreviation of monitoring software GT SoftGOT1000
Abbreviation of monitoring software GT SoftGOT2
Abbreviation of SW D5C-GPPW-E(-EV)/SW D5F-GPPW-E type software package
A - 16
Abbreviations and generic terms
GX Simulator
Document Converter
PX Developer
Description
Abbreviation of SW D5C-LLT-E(-EV) type ladder logic test tool function software packages
(SW5D5C-LLT (-EV) or later versions)
Abbreviation of document data conversion software Document Converter for GOT1000 series
Abbreviation of SW D5C-FBDQ-E type FBD software package for process control
License key (for GT SoftGOT1000)
Abbreviations and generic terms
License GT15-SGTKEY-U, GT15-SGTKEY-P
Description
License key (for GT SoftGOT2)
Abbreviations and generic terms
License key
License key FD
Description
A9GTSOFT-LKEY-P (For DOS/V PC)
SW5D5F-SGLKEY-J (For PC CPU module)
Others
Abbreviations and generic terms
Omron PLC
KEYENCE PLC
Sharp PLC
JTEKT PLC
Toshiba PLC
HITACHI IES PLC
HITACHI PLC
FUJI FA PLC
Matsushita PLC
Yaskawa PLC
Yokogawa PLC
Allen-Bradley PLC
SIEMENS PLC
Temperature controller
OMRON temperature controller
SHINKO indicating controller
CHINO controller
FUJI SYS temperature controller
YAMATAKE temperature controller
YOKOGAWA temperature controller
RKC temperature controller
PC CPU module
GOT (server)
GOT (client)
Description
Abbreviation of PLC manufactured by OMRON Corporation
Abbreviation of PLC manufactured by KEYENCE
Abbreviation of PLC manufactured by SHARP Corporation
Abbreviation of PLC manufactured by JTEKT Corporation
Abbreviation of PLC manufactured by TOSHIBA CORPORATION
Abbreviation of PLC manufactured by Hitachi Industrial Equipment Systems Co., Ltd.
Abbreviation of PLC manufactured by Hitachi, Ltd.
Abbreviation of PLC manufactured by Fuji Electric FA Components & Systems Co., Ltd.
Abbreviation of PLC manufactured by Matsushita Electric Works, Ltd
Abbreviation of PLC manufactured by YASKAWA Electric Corporation
Abbreviation of PLC manufactured by Yokogawa Electric Corporation
Abbreviation of PLC manufactured by Allen-Bradley
Abbreviation of PLC manufactured by SIEMENS
Abbreviation of temperature controller manufactured by OMRON
Abbreviation of temperature controller manufactured by Shinko Technos Co., Ltd.
Abbreviation of temperature controller manufactured by CHINO CORPORATION
Abbreviation of temperature controller manufactured by Fuji Electric Systems Co., Ltd.
Abbreviation of temperature controller manufactured by YAMATAKE
Abbreviation of temperature controller manufactured by Yokogawa Electric Corporation
Abbreviation of temperature controller manufactured by RKC
Abbreviation of PC CPU Unit manufactured by CONTEC CO., LTD
Abbreviation of GOTs that use the server function
Abbreviation of GOTs that use the client function
Windows font
Intelligent function module
Abbreviation of TrueType font and OpenType font available for Windows
(Differs from the True Type fonts settable with GT Designer2)
Indicates the modules other than the PLC CPU, power supply module and I/O module that are mounted to the base unit.
A - 17
HOW TO READ THIS MANUAL
1
Functions
This manual describes functions available for the GT Designer2 Version 2.58L.
For the added functions by the product version upgrade, refer to the list of functions added by GT
Designer2 version upgrade in Appendices.
2
Symbols
Following symbols are used in this manual.
13.3.3 Memory check operation
Carries out write/read check of memory.
When drive is not displayed
When the drive (memory) to check is not displayed, confirm the mounting procedure or memory type with reference to the following.
• CF card inserting/removing method Section 7.1 CF Card
When no faults are found in mounting, etc, a memory failure may be arosen.
Replace the CF card or Flash memory.
For details of Flash memory, contact your nearest sales office or FA Center.
The following example explains about Memory Check using Flash memory.
For the CF card memory check, install the CF card before carrying out the same key operations as built-in flash memory.
1
Select [Flash Memory] in the Memory check setting screen, and touch the
Check
button.
If select the
OK
button, the numeric keyboard window is displayed.
If select the Cancel to the initial menu.
button, the screen returns
2
3
4
Touch
5 9 2 0
and then Enter .
(The password is fixed to 5920.)
Touching
Enter
executes read/write check for the flash memory.
Remark
Refers to the information required.
Refers to the supplementary explanations for reference.
Indicates the items in which the detailed explanation is described (manual, chapter, section, item of the manual).
. . . .
Indicates the operation steps.
Menu and items are differentiated with parentheses.
[ ]
: refers to the menu of GOT utility.
: refers to the button in the dialog
box of GOT utility.
13 - 4
13.3 Memory Check
13.3.3 Memory check operation
A - 18
1. OVERVIEW
1
About GOT
A GOT is installed on the panel surface of a control panel or operating panel and connects to the PLC within the control panel. The GOT carries out switch operation, lamp display, data display, message display, etc.
PLC
Connector for program
For the display screen, two kinds of screens are available : user screen and utility screen.
(1) User screen
The user screen is a screen drawn by GT Designer2.
GOT
The objects [Touch switch], [Lamp display], [Comment display], and [Numeric display] can be arditrarily arranged on the display.
A "horizontal format" or "vertical format" may be selected for displaying a user’s project.
Moreover, multiple screens created within GT Designer2 can be individually selected or overlapped for the display.
For details, refer to the following.
GT Designer2 Version Basic Operation/Data Transfer Manual
GT Designer2 Version Screen Design Manual
(2) Utility Screen
The utility screen is a factory drawn horizontal screen that cannot be edited.
Installing the BootOS or Standard monitor OS in the GOT from GT Designer2, the utility screen is displayed.
The utility screen has options for [Brightness/contrast] , [Memory check] , etc , and the format is horizontal only.
For details, refer to the following.
2
3
4
5
6
1
7
8
1 - 1
2
About Manual
The following manuals related to GOT 1000 series are available. Refer to each manual in accordance with the intended use.
(1) Installation of the software programs Drawing Data transfer
For operations from creating project data to transferring data to GOT, refer to the following manuals.
Purpose
Installing product on PC
GT Designer2 Version
Basic Operation/Data Transfer
Manual
*1
Detailed
GT Designer2 Version
Screen Design Manual
*1
Creating projects
Detailed
Creating screens
Detailed
Drawing figures
Detailed
Making Common Settings
Overview
Placing/Setting objects
Overview
Transferring data to GOT
Detailed
*1 Stored in the GT Works 2/GT Designer2 in PDF format.
Detailed
Detailed
1 - 2
(2) Installing a GOT connection to a PLC
For the operations from installing a GOT to communicating with a PLC CPU, refer to the following manuals.
1
Purpose
(Included)
GT15 General
Description
GT 11 General
Description
GT15 User's Manual
GT11 User's Manual
GOT1000 Series
Connection Manual
*1
2
Confirming part names and specifications of the GOT
Confirming the GOT installation method
Confirming the mounting method for communication units or option devices
Confirming the PLC connection method
Confirming the utility operation method
Overview
Overview
Detailed
Detailed
Detailed
Detailed
Overview
Detailed
3
4
5
Confirming error codes (system alarm) displayed on the GOT
Detailed
*1 Stored in the GT Works2/GT Designer2 in PDF format.
(3) Other manuals
The following manuals are also available.
The following manuals are stored in the GT Works2/GT Designer2 in PDF format.
(a) GOT1000 Series Extended/Option Functions Manual
Describes how to use the ladder monitoring function, system monitor function and list editor for
MELSEC-A.
(b) GOT1000 Series Gateway Functions Manual
Describes how to use the gateway function.
(c) GT Simulator 2 Version Operation Manual
Describes how to simulate the created project data with GT Simulator2.
(d) GT Converter2 Version Operating Manual
Describes how to use the GT Converter2.
6
7
8
1 - 3
1.1 Features
(1) Improved monitoring performance and connectivity to FA devices
• Multiple languages are displayed using the Unicode2.1-compatible fonts and beautiful characters are drawn using the TrueType and high quality fonts.
• Two types of display modes are provided: 256-color display and monochrome display.
In the monochrome display, 16 scales are used to improve the display.
• High-speed monitoring through high-speed serial communication at maximum tare of 115.2 kbps or through bus connection with the PLC.
• High speed display and high speed touch switch response.
(2) More efficient GOT operations including screen design, startup, adjustment, management and maintenance works
• The 3MB user memory is included as standard.
• CF card interface is included as standard.
• The USB connector is positioned on the GOT front. This enables the system startup to be performed more efficiently using FA device setup tool, and eliminates the indirect works (opening and closing the control panel, cable replacement, cable rewiring) in order to improve the working efficiency.
(3) Enhanced support of FA setup tools
• PLC program transfer and monitoring are possible via the personal computer that is connected to the GOT if connected directly to the A, QnA, Q, or FX series of the PLC CPU (FA transparent function).
1 - 4
1.1 Features
1.2 Rough Pre-operation Procedure
The outline procedure before operating GOT is shown.
Start
Install GT Designer2 in the PC.
Refer to GT Designer2 Version
Basic Operation/Data Transfer Manual.
Create project data.
Wire for the GOT power supply.
Refer to GT Designer2 Version
Screen Design Manual or Help functions of
GT Designer2.
Refer to Chapter 7 WIRING.
Attach the option function board.
(Only when necessary)
When transferring data via a cable
Refer to Chapter 8 OPTION.
When transferring data via the CF card
Connect GOT and PC with a USB cable or RS-232 cable.
Insert the CF card in the PC.
Install and download the OS program, project data installed in the PC to the GOT.
1) Install the standard monitor OS,
communication driver, extended
functions OS, option OS to GOT.
2) Download the project data created
by the PC.
Write the OS, project data installed in the PC in the CF card.
1) Write the standard monitor OS,
communication driver, extended function
OS, option OS in the CF card.
2) Write the project data created
by the PC in the CF card.
Install the CF card to GOT to install and download the standard monitor OS, communication driver, extended function OS, option OS, project data to the built-in flash memory.
Refer to GT Designer2 Version
Basic Operation/Data Transfer Manual.
Refer to 16. INSTALLATION OF
core OS, BOOTOS AND STANDARD
MONITOR OS in this manual for the
operations of GOT.
1
2
3
4
5
Check the communication settings.
Connect the cable to GOT and the destination connector.
Turn on the GOT power and the system of the connection destination.
Start the monitor. (Display each screen.)
End
Refer to GOT1000 Series Connection Manual.
6
7
8
1.2 Rough Pre-operation Procedure
1 - 5
2. SYSTEM CONFIGURATION
2.1 Overall Configuration
The overall configuration of GOT is as follows.
For the connection methods applicable to GOT1000 series and cable, refer to the following.
GOT1000 Series Connection Manual
Option function board Protective sheet
CF card
Personal computer
Commercially available
GOT
GRAPHIC OPERATION TERMINAL
GOT
1000
Memory card
MITSUBISHI
CF card
• GT11 does not connect a printer.
Memory card adaptor
Stand
Bar code reader
Commercially available
2 - 1
2.1 Overall Configuration
2.2 Component List
(1) Explanation of the GOT model name
G T 1 1 5 5
Communication interface
Power type
2 : Built-in RS-232
Q : Built-in Q bus
A : Built-in A bus
Blank : Built-in RS-422
A : 100 to 240VAC
D : 24VDC
L : 5VDC
1
2
Display device type
T : TFT color (High intensity, wide angle view)
N : TFT color
S : STN color
L : STN monochrome
Resolution
X : 1024 768 (XGA)
S : 800 600 (SVGA)
V : 640 480 (VCA)
Q : 320 240 (QVGA)
Blank: less than 320 240
Display color type
5 : 65535/256 colors*
1
2 : 16 colors
0 : Monochrome (black and white) 16 scales
Screen size type
9 : 15.0"
8 : 12.1"
7 : 10.4"
6 : 8.4"
5 : 5.7"
3 : 4.5"
2 : 3.7"
GOT 1000 series GT15/GT11/GT10
*1: For GT15 that can display 65536 colors, refer to following.
GT15 User's Manual
(2) Explanation of the option model name
G T
90 : 15.0"
80 : 12.1"
75 : Common for 10.4", 8.4"
70 : Dedicated for 10.4"
60 : Dedicated for 8.4"
50 : Dedicated for 5.7"
30 : Dedicated for 4.5"
20 : Dedicated for 3.7"
15 : Dedicated for GT15
11 : Dedicated for GT11
10 : Dedicated for GT10
09 :
05 :
01 :
Common for GT15/GT11
2.2 Component List
2 - 2
3
4
5
6
7
8
\
2.2.1
GOT (GT11)
1
Models with a built-in serial interface
GOT
GT1155-QSBD
GT1150-QLBD
5.7" [320 x 240 dots], STN color liquid crystal, 256 colors, 24VDC, memory size 3MB, builtin battery, built-in serial interface
5.7" [320 x 240 dots], STN monochrome liquid crystal, monochrome (black/white), 16 scales, 24VDC, memory size 3MB, built-in battery, built-in serial interface
2
Models with a built-in bus interface
GOT
GT1155-QTBDQ
GT1155-QTBDA
GT1155-QSBDQ
GT1155-QSBDA
GT1150-QLBDQ
GT1150-QLBDA
5.7" [320 x 240 dots], TFT color liquid crystal, 256 colors, 24VDC, memory size 3MB, builtin battery, built-in Q bus/serial interface
5.7" [320 x 240 dots], TFT color liquid crystal, 256 colors, 24VDC, memory size 3MB, builtin battery, built-in A bus/serial interface
5.7" [320 x 240 dots], STN color liquid crystal, 256 colors, 24VDC, memory size 3MB, builtin battery, built-in Q bus/serial interface
5.7" [320 x 240 dots], STN color liquid crystal, 256 colors, 24VDC, memory size 3MB, builtin battery, built-in A bus/serial interface
5.7" [320 x 240 dots], STN monochrome liquid crystal, monochrome (black/white), 16 scales, 24VDC, memory size 3MB, built-in battery, built-in Q bus/serial interface
5.7" [320 x 240 dots], STN monochrome liquid crystal, monochrome (black/white), 16 scales, 24VDC, memory size 3MB, built-in battery, built-in A bus/serial interface
2 - 3
2.2 Component List
2.2.1 GOT (GT11)
2.2.2
Option (Optional components for GT11)
PLC connection cable (Sold separately)
Product name Model name
FXCPU direct connection cable
FX expansion board connection cable
GT01-C10R4-8P
GT01-C30R4-8P
GT01-C100R4-8P
GT01-C200R4-8P
GT01-C300R4-8P
Cable length
1m
3m
10m
20m
30m
Contents
For connecting FXCPU (MINI DIN 8 pins) and
GOT.
For connecting FXCPU expansion board (MINI
DIN 8 pins) and GOT.
RS-422
Cable
RS-232
Cable
QnA/A/
FXCPU direct connection cable computer link connection cable
GT01-C30R4-25P
GT01-C100R4-25P
GT01-C200R4-25P
GT01-C300R4-25P
3m
10m
20m
30m
For connecting QnA/ACPU/Motion controller
CPU (A series) FXCPU (D-sub 25 pins) and
GOT.
For connecting FA-CNV CBL and GOT
For connecting serial communication unit
(AJ71QC24(N)-R4) and GOT
Computer link connection cable
GT09-C30R4-6C
GT09-C100R4-6C
GT09-C200R4-6C
GT09-C300R4-6C
3m
10m
20m
30m
For connecting computer link unit/serial communication unit and GOT
QCPU direct connection cable
FX expansion board connection,
FX special adaptor connection, data transfer cable
FX special adaptor connection
Computer link connection cable
GT01-C30R2-6P
GT01-C30R2-9S
GT01-C30R2-25P
GT09-C30R2-9P
GT09-C30R2-25P
3m
3m
3m
3m
3m
For connecting QCPU/Motion controller CPU (Q series) and GOT
For connecting FXCPU expansion board (D-sub
9pins), special adapter (D-sub 9 pins) and GOT.
For connecting personal computer (GT
Designer2) (D-sub 9 pins: female)
*1
(D-sub 9 pins: female)
*1
and GOT
For connecting FXCPU special adaptor (D-sub
25 pins) and GOT.
For connecting computer link unit/serial communication unit and GOT
*1: Description in parentheses indicates the cable side connector shape.
2.2 Component List
2.2.2 Option (Optional components for GT11)
2 - 4
1
2
3
4
5
6
7
8
Bus cable for connection to QCPU (Q mode) (Sold separately)
Product name
Q add-on cable
Inter-GOT connection cable
Long Q connection cable
Long inter-GOT connection cable
Model name
GT15-QC06B
GT15-QC12B
GT15-QC30B
GT15-QC50B
GT15-QC100B
GT15-QC150BS
GT15-QC200BS
GT15-QC250BS
GT15-QC300BS
GT15-QC350BS
Cable length 0.6m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 10m
Cable length 15m
Cable length 20m
Cable length 25m
Cable length 30m
Cable length 35m
Description
For connecting QCPU and GOT
For interconnecting GOTs
For connecting QCPU and GOT over a distance of 13.2 m or farther (Requires A9GT-
QCNB)
For interconnecting GOTs over a distance of
13.2 m or farther
Bus cable for connection to QnA/ACPU/motion controller (A series) (sold separately)
Product name
Small-CPU connection cable
Inter-GOT connection cable
Large-CPU connection cable
Model name
GT15-A1SC07B
GT15-A1SC12B
GT15-A1SC30B
GT15-A1SC50B
GT15-A1SC05NB
GT15-A1SC07NB
GT15-A1SC30NB
GT15-A1SC50NB
GT15-C12NB
GT15-C30NB
GT15-C50NB
GT15-AC06B
GT15-AC12B
GT15-AC30B
Cable length 0.7m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 0.45m
Cable length 0.7m
Cable length 3m
Cable length 5m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 0.6m
Cable length 1.2m
Cable length 3m
GT15-AC50B Cable length 5m
GT15-A370C12B-S1 Cable length 1.2m
GT15-A370C25B-S1 Cable length 2.5m
GT15-A370C12B Cable length 1.2m
GT15-A370C25B Cable length 2.5m
Description
For connecting QnAS/AnSCPU/motion controller CPU (A series) and GOT
For connecting QnAS/AnSCPU and GOT
For connecting QnAS/AnSCPU/motion controller CPU (A series) and A7GT-CNB
For connecting QnAS/AnSCPU and A7GT-CNB
For connecting QnA/ACPU/motion controller
CPU (A series/expanded base) and GOT
For connecting QnA/ACPU/motion controller
CPU (A series/expanded base) and A7GT-CNB
For connecting motion controller CPU (A series/ basic base) and GOT
For connecting motion controller CPU (A series/ basic base) and A7GT-CNB
Small-CPU long connection cable
GT15-C100EXSS-1
GT15-C200EXSS-1
GT15-C300EXSS-1
Cable length 10.6m
Cable length 20.6m
Cable length 30.6m
For QnAS/AnSCPU/motion controller CPU (A series) to GOT long distance connection
For A7GT-CNB to GOT long distance connection Combination of GT15-FXCNB and
GT15-C BS
2 - 5
2.2 Component List
2.2.2 Option (Optional components for GT11)
Product name
Long inter-GOT connection cable
A0J2HCPU connection cable
Buffer circuit cable
Model name
GT15-C07BS
GT15-C12BS
GT15-C30BS
GT15-C50BS
GT15-C100BS
GT15-C200BS
GT15-C300BS
GT15-J2C10B
GT15-EXCNB
Description
Cable length 0.7m
Cable length 1.2m
Cable length 3m
Cable length 5m
Cable length 10m
Cable length 20m
Cable length 30m
Cable length 1m
For interconnecting GOTs
Cable length 0.5m
For connecting the power supply unit (A0J2-
PW) to GOT
Can be used as a GT15-C EXSS-1 when used in combination with GT15-C BS
Connection cables for OMRON PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40101-9P Cable length 3m
GT09-C100R40101-9P Cable length 10m
GT09-C200R40101-9P Cable length 20m
GT09-C300R40101-9P Cable length 30m
GT09-C30R40102-9P Cable length 3m
GT09-C100R40102-9P Cable length 10m
GT09-C200R40102-9P Cable length 20m
GT09-C300R40102-9P Cable length 30m
For connecting GOT to OMRON PLC, serial communication module, serial communication board
For connecting GOT to OMRON rack type host link unit, communication board
GT09-C30R20101-9P Cable length 3m
For connecting GOT to OMRON PLC, serial communication module, communication board, serial communication board
GT09-C30R20102-25P Cable length 3m For connecting GOT to OMRON connection cable
GT09-C30R20103-25P Cable length 3m For connecting GOT to OMRON rack type host link unit
Connection cables for KEYENCE PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R41101-5T Cable length 3m
GT09-C100R41101-5T Cable length 10m
GT09-C200R41101-5T Cable length 20m
GT09-C300R41101-5T Cable length 30m
GT09-C30R21101-6P
GT09-C30R21102-9S
GT09-C30R21103-3T
For connecting GOT to KEYENCE multi-communication unit
Cable length 3m For connecting GOT to KEYENCE PLC
Cable length 3m For connecting GOT to KEYENCE multi-communication unit
Cable length 3m For connecting GOT to KEYENCE multi-communication unit
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option (Optional components for GT11)
2 - 6
Connection cables for JTEKT PLCs (Sold separately)
Product name
Model name
RS-422 cable
GT09-C30R41201-6C Cable length 3 m
GT09-C100R41201-6C Cable length 10 m
GT09-C200R41201-6C Cable length 20 m
GT09-C300R41201-6C Cable length 30 m
Description
For connecting GOT to JTEKT PLC
RS-232 cable
GT09-C30R21201-25P Cable length 3 m For connecting GOT to JTEKT PLC
Connection cables for SHARP PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40601-15P Cable length 3m
GT09-C100R40601-15P Cable length 10m
GT09-C200R40601-15P Cable length 20m
GT09-C300R40601-15P Cable length 30m
GT09-C30R40602-15P Cable length 3m
GT09-C100R40602-15P Cable length 10m
GT09-C200R40602-15P Cable length 20m
GT09-C300R40602-15P Cable length 30m
For connecting GOT to SHARP PLC
For connecting GOT to SHARP PLC
GT09-C30R40603-6T Cable length 3m
GT09-C100R40603-6T Cable length 10m
GT09-C200R40603-6T Cable length 20m
GT09-C300R40603-6T Cable length 30m
For connecting GOT to SHARP link unit
GT09-C30R20601-15P Cable length 3m For connecting GOT to SHARP PLC
GT09-C30R20602-15P Cable length 3m For connecting GOT to SHARP PLC
Connection cables for TOSHIBA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40501-15P Cable length 3m
GT09-C100R40501-15P Cable length 10m
GT09-C200R40501-15P Cable length 20m
GT09-C300R40501-15P Cable length 30m
GT09-C30R40502-6C Cable length 3m
GT09-C100R40502-6C Cable length 10m
GT09-C200R40502-6C Cable length 20m
GT09-C300R40502-6C Cable length 30m
For connecting GOT to TOSHIBA PLC
For connecting GOT to TOSHIBA PLC
GT09-C30R40503-15P Cable length 3m
GT09-C100R40503-15P Cable length 10m
GT09-C200R40503-15P Cable length 20m
GT09-C300R40503-15P Cable length 30m
For connecting GOT to TOSHIBA PLC
GT09-C30R20501-9P Cable length 3m For connecting GOT to TOSHIBA PLC
GT09-C30R20502-15P Cable length 3m For connecting GOT to TOSHIBA PLC
2 - 7
2.2 Component List
2.2.2 Option (Optional components for GT11)
Connection cables for HITACHI PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40401-7T Cable length 3m
GT09-C100R40401-7T Cable length 10m
GT09-C200R40401-7T Cable length 20m
GT09-C300R40401-7T Cable length 30m
GT09-C30R21101-6P
GT09-C30R21103-3T
For connecting GOT to HITACHI intelligent serial port module
Cable length 3m
For connecting GOT to HITACHI PLC, intelligent serial port module
Cable length 3m For connecting GOT to HITACHI PLC
Connection cables for MATSUSHITA PLCs (Sold separately)
Product name
Model name
RS-232 cable
GT09-C30R20901-25P Cable length 3m
GT09-C30R20902-9P
GT09-C30R20903-9P
GT09-C30R20904-3C
Cable length 3m
Cable length 3m
Cable length 3m
Description
For connecting GOT to MATSUSHITA RS422/232C conversion adapter
For connecting GOT to the tool port or RS232C port of
MATSUSHITA PLC, computer communication unit
For connecting GOT to the RS232C port of MATSUSHITA
PLC
For connecting GOT to the RS232C port of MATSUSHITA
PLC
Connection cables for YASKAWA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40201-9P Cable length 3m
GT09-C100R40201-9P Cable length 10m
GT09-C200R40201-9P Cable length 20m
GT09-C300R40201-9P Cable length 30m
GT09-C30R40202-14P Cable length 3m
GT09-C100R40202-14P Cable length 10m
GT09-C200R40202-14P Cable length 20m
For connecting GOT to YASKAWA MEMOBUS module
For connecting GOT to YASKAWA PLC
GT09-C300R40202-14P Cable length 30m
GT09-C30R20201-9P Cable length 3m
GT09-C30R20202-15P Cable length 3m
GT09-C30R20203-9P Cable length 3m
For connecting GOT to YASKAWA PLC
GT09-C30R20204-14P Cable length 3m
GT09-C30R20205-25P Cable length 3m For connecting GOT to YASKAWA MEMOBUS module
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option (Optional components for GT11)
2 - 8
Connection cables for YOKOGAWA PLCs (Sold separately)
Product name
Model name
RS-422 cable
RS-232 cable
Description
GT09-C30R40301-6T Cable length 3m
GT09-C100R40301-6T Cable length 10m
GT09-C200R40301-6T Cable length 20m
GT09-C300R40301-6T Cable length 30m
GT09-C30R40302-6T Cable length 3m
GT09-C100R40302-6T Cable length 10m
GT09-C200R40302-6T Cable length 20m
GT09-C300R40302-6T Cable length 30m
GT09-C30R20301-9P
GT09-C30R20302-9P
For connecting GOT to YOKOGAWA PC link module
Cable length 3m
For connecting GOT to YOKOGAWA CPU port/D-Sub 9-pin conversion cable
Cable length 3m For connecting GOT to YOKOGAWA PC link module
Connection cables for Allen-Bradley PLCs (Sold separately)
Product name
RS-232 cable
Model name
GT09-C30R20701-9S
Description
Cable length 3m For connecting GOT to Allen-Bradley PLC
Connection cables for SIEMENS PLCs (Sold separately)
Product name
RS-232 cable
Model name
GT09-C30R20801-9S
Description
Cable length 3m For connecting GOT to SIEMENS HMI Adapter
CF card (Sold separately)
Product name
CF card
Model name
GT05-MEM-32MC
GT05-MEM-64MC
GT05-MEM-128MC
GT05-MEM-256MC
-
Contents
Flash ROM 32MB
Flash ROM 64MB
Flash ROM 128MB
Flash ROM 256MB
Commercially-available CF card
*2
*2: Some models with the operations checked by our company are usable.
For the operation-checked models, refer to "List of valid devices applicable for GOT1000 series" (T10-0039) separately available.
The Technical News above is available as a reference at the information site for Mitsubishi industrial automation products MELFANSweb home page.
(MELFANSweb website: http://wwwf2.mitsubishielectric.co.jp/english/index.html)
Memory card adaptor (Sold separately)
Product name Model name
Memory card adaptor GT05-MEM-ADPC
Contents
CF card to memory card (Type II) conversion adaptor
2 - 9
2.2 Component List
2.2.2 Option (Optional components for GT11)
Option function board (Sold separately)
Product name Model name Contents
Option function board GT11-50FNB
Option function board
*3
*3: Necessity of mounting the option function board may offer depending on the hardware version. Refer to the following for detailes.
Section 8.3 Option Function Board
Stand (Sold separately)
Product name
Stand
Model name
GT05-50STAND
A9GT-50STAND
Stand for 5.7”
Stand (Common to A95 GOT)
Contents
Battery (Sold separately)
Product name
Battery
*4
Model name
GT11-50BAT
Contents
For storing clock data, alarm history and recipe data
*4: At GOT purchase, it is installed in the main unit.
Bus extension connector box (sold separately)
Product name
Bus extension connector box
Model name
A9GT-QCNB
Contents
Used for QCPU (Q mode)/motion controller CPU (Q series) bus connection when the cable is longer than 13.2 m
Bus connector adapter box (sold separately)
Product name Model name
Bus connector adapter box
A7GT-CNB
Contents
Used for QnA/ACPU/motion controller CPU (A series) bus connection when the cable is longer than 13.2 m (For changing a large connector to a small connector.)
Protective sheet (Sold separately)
Product name
Protective sheet
Model name
GT11-50PSCB
GT11-50PSGB
GT11-50PSCW
GT11-50PSGW
5.7
"
protective sheet
Contents
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: white) 5 sheets
Antiglare (Frame: white) 5 sheets
USB environmental protection cover (Sold separately)
Product name
USB environmental protection cover
*5
Model name
GT11-50UCOV
*5: At GOT purchase, it is installed in the main unit.
Contents
Replacement environmental protection cover for USB interface on the GOT main unit front side (For complying IP67)
1
2
3
4
5
6
7
8
2.2 Component List
2.2.2 Option (Optional components for GT11)
2 - 10
Drawing software (Sold separately)
Product name
GT Designer2
Model name Contents
SW D5C-GTD2-E
( indicates the version)
*6
Drawing software for GOT1000/GOT900 series
* 6: The is assigned with an integer 2 or more.
PC connection cable (Sold separately)
Product name Model name
GT01-C30R2-9S Cable length 3m
Project data transfer cable
GT01-C30R2-25P Cable length 3m
GT01-C20USB-5P
GT09-C30USB-5P
Cable length 2m
Cable length 3m
* 7: Connector shape on the cable is shown in ( ).
Contents
For connecting GOT (D sub 9-pin female) and PC (D sub 9-pin female)
*7
For connecting GOT (D sub 9-pin female) and PC (D sub 25-pin male)
*7
For connecting GOT (USB mini)
*7
and PC
(USB)
Bar code reader (Sold separately)
Product name Model name Contents
Bar code reader -
Commercially-available bar code reader
*8
*8: Some models with the operations checked by our company are usable.
For the operation-checked models, refer to "List of valid devices applicable for GOT1000 series" separately available (T10-0039).
The Technical News above is available as a reference at the Information site for Mitsubishi industrial automation products MELFANSweb home page.
(MELFANSweb home page: http://wwwf2.mitsubishielectric.co.jp/melfansweb/english/index_e.htm)
2 - 11
2.2 Component List
2.2.2 Option (Optional components for GT11)
3. SPECIFICATIONS
3.1 General Specifications
Operating ambient temperature
Item
Display section
Other than display section
0 to 50
Specifications
0 to 55 (when horizontally installed), 0 to 50 (when vertically installed)
Storage ambient temperature
-20 to 60
Operating ambient humidity
*1
Storage ambient humidity
*1
10 to 90% RH, non-condensing
10 to 90% RH, non-condensing
Vibrationresistance
Shock resistance
Operating atmosphere
Frequency Acceleration
Halfamplitude
3.5mm
Sweep Count
Compliant with JIS
B3502 and
IEC61131-2
Under intermittent vibration
Under continuous vibration
5 to 9Hz
9 to 150Hz
5 to 9Hz
9 to 150Hz
-
9.8m/s
-
4.9m/s
2
2
1.75mm
-
10 times each in X, Y and Z directions
Compliant with JIS B3502, IEC 61131-2 (147 m/s
2
, 3 times each in X, Y and Z directions)
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electroconductive dust particles.
Operating altitude
*2
Installation location
Overvoltage category
*3
2000 m (6562 ft) max.
Inside control panel
II or less
Pollution degree
*4
Cooling method
2 or less
Self-cooling
2
3
4
5
6
*1 : STN liquid crystal type to be stored at or below 39 WBT.
*2 : Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.). Failure to observe this instruction may cause a malfunction.
*3 : This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V.
*4 : This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
7
8
1
3.1 General Specifications
3 - 1
3.2 Performance Specifications
• GT1155-QSBD, GT1150-QLBD
Display section *1
Backlight
Touch panel
Memory
Battery
Item
Type
Screen size
Resolution
GT1155-QSBD
STN color liquid crystal
5.7"
Specifications
GT1150-QLBD
STN monochrome (white/black) liquid crystal
Display size
W115(4.53) H86(3.39)[mm](inch) (Horizontal format)
Display character
16-dot standard font: 20 characters 15 lines, 12-dot standard font: 26 characters 20 lines
(Horizontal format)
Display color
Display angle
256 colors
Left/Right: 50 degrees, Top: 50 degrees,
Bottom: 60 degrees (Horizontal format)
Contrast adjustment 16-level adjustment
Monochrome (white/black), 16 scales
Left/Right: 45 degrees, Top: 20 degrees,
Bottom: 40 degrees (Horizontal format)
Intensity of LCD only
350[cd/m
2
](Adjustable in 8 levels)
Intensity adjustment 8-level adjustment
Life
Life
*2
220[cd/m
2
](Adjustable in 8 levels)
Approx. 50,000h. (Time for display intensity to become 1/5 at operating ambient temperature of 25 ) Guaranteed: 1 year
Cold cathode fluorescent tube (irreplaceable by a user) backlight shutoff detection function is included.
Backlight off/screen saving time can be set.
Approx. 75,000h or longer. (Time for display intensity reaches 50% at the operating ambient temperature of 25 )
Guaranteed: 1 year
Approx. 54,000h or longer. (Time for display intensity reaches 50% at the operating ambient temperature of 25 )
Guaranteed: 1 year
Number of touch keys 300 keys/screen (Matrix structure of 15 lines
20 columns)
Key size
Number of points touched simultaneously
Life
C drive *3
Life (Number of write times)
D drive
Backup target
Minimum 16 16 dots (per key)
Maximum of 2 points
1 million times or more (operating force 0.98N max.)
Flash memory (Internal), for storing project data (3Mbytes) and OS
100,000 times
SRAM (Internal), 512kbyes (battery backup)
GT11-50BAT lithium battery
Clock data, alarm history and recipe data
Life
Buzzer output
Environmental protective structure
*4
External dimensions
Panel cutting dimensions
Weight
Compatible software package
Approx. 5 years (Operating ambient temperature of 25 ), Guaranteed: 1 year
Single tone (tone length adjustable)
Equivalent to IP67 (JEM1030) (front section) when the USB environmental protective cover is attached
W164(6.46) H135(5.32) D56(2.21)[mm](inch)(Excluding USB environmental protective cover) (Horizontal format)
W153 (6.03) H121(4.77)[mm] (inch) (Horizontal format)
0.7kg (Excluding mounting fixtures)
GT Designer2 Version2 or later
*1: Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements.
Flickers may be observed depending on the display color.
Please note that these dots appear due to its characteristic and are not caused by product defect.
*2: The GOT screen saving/backlight off function prevents images from becoming permanently etched on the display screen and increases the backlight life.
*3: ROM in which new data can be written without deleting the written data.
*4: Compliant with IP67 when the USB environmental protection cover is attached. Not compliant when a USB cable is connected. Note that this does not guarantee all user’s operation environment.
3 - 2
3.2 Performance Specifications
• GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA,
GT1155-QSBDA, GT1150-QLBDA
Display section
*1
Backlight
Screen size
Resolution
Life
Item
Type
Display size
Display character
Display color
GT1155-QTBDQ
GT1155-QTBDA
TFT color liquid crystal
256 colors
Specifications
GT1155-QSBDQ
GT1155-QSBDA
Color liquid crystal
GT1150-QLBDQ
GT1150-QLBDA
STN monochrome (black/ white) liquid crystal
5.7"
320 240 dots
W115(4.53) H86 (3.39)[mm](inch) (Horizontal format)
16-dot standard font: 20 characters 15 lines, 12-dot standard font: 26 characters
20 lines (Horizontal format)
Monochrome (black/white),
16 scales
Display angle
Left/right: 70 degrees, Top:
70 degrees, Bottom: 50
Left/right: 55 degrees, Top:
65 degrees, Bottom: 70
Left/right: 45 degrees, Top:
20 degrees, Bottom: 40
Contrast adjustment
Life
*2 degrees (Horizontal format)
-
Intensity of LCD
400[cd/m
2
] only
(Adjustable in 8 levels)
Intensity adjustment 8-level adjustment degrees (Horizontal format)
16-level adjustment
380[cd/m
2
]
(Adjustable in 8 levels) degrees (Horizontal format)
220[cd/m
2
]
(Adjustable in 8 levels)
Approx. 50,000 h (at operating ambient temperature of 25 )
Cold cathode fluorescent tube (irreplaceable by the user) backlight detection function is included
Backlight/screen saving time can be set.
Approx. 75,000 hours or longer. (The time takes to reduce to 50% of the backlight luminance at the operating
Approx. 54,000 hours or longer. (The time takes to reduce to 50% of the backlight luminance at the ambient temperature of 25 )
Guaranteed: 1 year operating ambient temperature of 25 )
Guaranteed: 1 year
Touch panel
Number of touch keys
Key size
Maximum simultaneous key
300 keys/screen (Matrix of 15 lines 20 columns)
Minimum 16 16 dots (per key)
Maximum of 2 points
Memory presses
Life
C drive
*3
Life (Number of write times)
D drive
1 million times or more (operating force 0.98N max.)
Flash memory (Internal), for storing project data (3Mbytes) and OS
100,000 times
Battery
Backup target
Life
SRAM (internal), 512kbytes (battery backup)
GT11-50BAT lithium battery
Clock data, alarm history and recipe data
Buzzer output
Environmental protective structure
*4
Approx. 5 years (Operating ambient temperature of 25 ), Guaranteed: 1 year
Single tone (tone length adjustable)
Equivalent to IP67f (JEM1030) (front section) when the USB environmental protective cover is attached (Horizontal format)
1
2
3
4
5
6
7
8
3.2 Performance Specifications
3 - 3
Item
External dimensions
GT1155-QTBDQ
GT1155-QTBDA
Specifications
GT1155-QSBDQ
GT1155-QSBDA
GT1150-QLBDQ
GT1150-QLBDA
W167(6.58) H135(5.32) D56(2.21)[mm](inch)(Excluding USB environmental protective cover) (Horizontal format)
Panel cutting dimensions
Weight
W153 (6.03) H121(4.77)[mm] (inch)(Horizontal format)
0.9kg(Excluding mounting fixtures)
Compatible software package GT Designer2 Version2 or later
*1: Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements.Flickers may be observed depending on the display color.Please note that these dots appear due to its characteristic and are not caused by product defect.
*2: The GOT screen saving/backlight off function prevents images from becoming permanently etched on the displayscreen and increases the backlight life.
*3: ROM in which new data can be written without deleting the written data.
*4: Compliant with IP67 when the USB environmental protection cover is attached. Not compliant when a USB cable is connected. Note that this does not guarantee all user’s operation environment.
3 - 4
3.2 Performance Specifications
3.3 Built-in Interface Specifications
• GT1155-QSBD, GT1150-QLBD
Built-in
Interface
Item
RS-422
RS-232
USB
CF card
Specifications
GT1155-QSBD
GT1150-QLBD
Serial interface, RS422-compliant, 1ch
Transmission speed :115,200/57,600/38,400/19,200/9,600/4,800bps
Connecter type
Use
: D-sub 9-pin (female)
: PLC communication
Serial interface, RS232-compliant, 1ch
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800bps
Connecter type
Use
: D-sub 9-pin (male)
: PLC communication, barcode reader connection, PC communication (project data upload/download, OS installation, transparent function)
Serial interface, USB-compliant (Full Speed 12Mbps), device, 1ch
Use : PC communication (project data upload/download, OS installation, transparent function)
PCMCIA-compliant, compact flash slot, 1ch
Connector type
Use
: For TYPE I only
: Data transmission and storage
Option function board
*1
For mounting the option function board 1ch
*1: Necessity of mounting the option function board may offer depending on the hardware version.
Refer to the following for details.
Section 8.3 Option Function Board
• GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA,
GT1155-QSBDA, GT1150-QLBDA
Built-in
Interface
Item
Bus
RS-232
USB
CF card
Specifications
GT1155-QTBDQ
GT1155-QSBDQ
GT1150-QLBDQ
QCPU (Q mode)/motion controller CPU (Q
GT1155-QTBDA
GT1155-QSBDA
GT1150-QLBDA series) , 1ch
Use : PLC communication
-
-
QnA/ACPU/motion controller CPU (A series) , 1ch
Use : PLC communication
Serial interface, RS232-compliant, 1ch
Transmission speed : 115,200/57,600/38,400/19,200/9,600/4,800bps
Connecter type
Use
: D-sub 9-pin (male)
: Barcode reader connection, PC communication (project data upload/download, OS installation, transparent function)
Serial interface, USB-compliant (Full Speed 12Mbps), device, 1ch
Use : PC communication (project data upload/download, OS installation, transparent function)
PCMCIA-compliant, compact flash slot, 1ch
Connector type
Use
: For TYPE I only
: Data transmission and storage
3.3 Built-in Interface Specifications
3 - 5
1
2
3
4
5
6
7
8
3.4 Power Supply Specifications
• GT1155-QSBD, GT1150-QLBD
Item
Specifications
GT1155-QSBD
24VDC (+10% -15%), ripple voltage 200mV or less Input power supply voltage
Fuse (built-in, not exchangeable)
Power consumption
At backlight off
Inrush current
Permissible instantaneous power failure time
1.0A
9.84W (410mA/24VDC) or less
4.32W (180mA/24VDC) or less
15A or less (26.4V) 2ms
Within 5ms
GT1150-QLBD
9.36W (390mA/24VDC) or less
Noise immunity
Dielectric withstand voltage
Noise voltage: 1000Vp-p, Noise width: 1 s (by noise simulator of 30 to 100Hz noise frequency)
500VAC for 1 minute (across power supply terminals and earth)
Insulation resistance
10M or larger by insulation resistance tester (across power supply terminals and earth)
0.75 to 2[mm 2 ] Applicable wire size
Applicable solderless terminal Solderless terminal for M3 screw RAV1.25-3, V2-N3A, FV2-N3A
Applicable tightening torque
(Terminal block terminal screw)
0.5 to 0.8[N•m]
3 - 6
3.4 Power Supply Specifications
• GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA,
GT1155-QSBDA, GT1150-QLBDA
Item
GT1155-QTBDQ
GT1155-QTBDA
Specifications
GT1155-QSBDQ
GT1155-QSBDA
Input power supply voltage DC24V(+10% -15%)ripple voltage 200mV or less
Fuse (built-in, irreplaceable)
1.0A
Power consumption
With backlight off
Inrush current
Permissible instantaneous power failure time
9.84W (410mA/24VDC) or less
4.32W (180mA/24VDC) or less
9.84W (410mA/24VDC) or less
15A or less (26.4V) 2ms
Within 10ms
GT1150-QLBDQ
GT1150-QLBDA
9.84W (410mA/24VDC) or less
Noise immunity
Noise voltage: 500Vp-p, Noise width: 1 s (by noise simulator of 25 to 60 Hz noise frequency)
Dielectric withstand voltage 500VAC for 1 minute (across power supply terminals and earth)
Insulation resistance
10M or larger as measured with the 500 VDC insulation resistance tester (across power supply terminals and earth)
0.75 to 2[mm 2 ] Applicable wire size
Applicable solderless terminal
Applicable tightening torque
(Terminal block terminal screw)
Solderless terminal for M3 screw RAV1.25-3, V2-N3A, FV2-N3A
0.5 to 0.8[N•m]
1
2
3
4
5
Remark
Operation at momentary power failure
The GOT continues to operate even when the instantaneous power failure occures within the permissible instantaneous power failure time.
The GOT stops operating if there is extended power failure or voltage drop, while it automatically resumes operation as soon as the power is restored.
6
7
8
3.4 Power Supply Specifications
3 - 7
4. PART NAME
4.1 Front Panel
GRAPHIC OPERATION TERMINAL
GOT
1000
1) 2)
5)
MITSUBISHI
3) 4)
No Name
1) Display screen
2) Touch key
3) USB interface
Specifications
Displays the utility screen and the user creation screen.
For operating the touch switches in the utility screen and the user creation screen
USB interface for connecting a personal computer
(OS installation, project data download, transparent)
4)
USB environmental protection cover
Opens/Closes when the UBS interface is used.
5) POWER LED
Lit in green
Lit in orange
Blinking in orange/green
Not lit
For the PC connection, refer to the following.
: Power is correctly supplied
: Screen saving
: Blown backlight bulb
: Power is not supplied
GT Designer2 Version Basic Operation/Data Transfer Manual
Section1.5 System Configuration
4 - 1
4.1 Front Panel
4.2 Back Panel
1
Remark
Connecting the back panel
For the connection to the controller (PLC, microcomputer board, bar code reader, etc) or PC, refer to the following.
GOT 1000 Series Connection Manual
1
GT1155-QSBD, GT1150-QLBD
1) 2) 3)
4) 5)
6) 3)
CF CARD
7) 14)
ACCESS OFF ON
CF CARD
15)
RS-232
Battery cover opened
RS-422
BATTERY
I/F
16)
Power supply terminal layout
INPUT
24V DC
+
(FG)
(FG)
INPUT
24V DC
+
12) 13) 3)
No.
Name
1) RS-232 interface
2) RS-422 interface
3) Hole for unit installation fitting
4) Rating plate (nameplate)
5) CF card access LED
6) CF card access switch
7) CF card cover
8) Option function board (option)
9) Option function board cover
10) Reset switch
11) Battery cover
12) Power terminal
13) Power terminal cover
14) CF card interface
15) CF card eject button
16) Battery
11)
RESET
10) 3) 8) 9)
CF card cover opened
Specifications
For communicating with controller (PLC, microcomputer board, bar code reader, etc) or personal computer (OS installation, project data download, transparent) (D-sub 9-pin male)
For communicating with controller (PLC, microcomputer board, etc)
(D-sub 9-pin female)
Hole for the inserting installation fittings (accessory) during the GOT installation to the panel (4 holes at top and bottom)
-
Lit: CF card accessed Not lit: CF card not accessed
Switch for prohibiting access to CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : No access to CF card (CF card removal possible)
Open or close when inserting or removing the CF card.
Connect when using optional functions.
Remove when using the option function board.
Hardware reset switch (Use an isolated rod to operate.)
Open or close when replacing the battery.
Power terminal and FG terminal (for power supply (24VDC) to GOT and grounding)
Open or close when connecting a power terminal. (Color: transparent)
Interface for installing the CF card to GOT
Button for removing the CF card
GT11-50BAT battery for storing clock data, alarm history and recipe data
(The project data is stored in the built-in flash memory.)
2
3
4
5
6
7
8
4.2 Back Panel
4 - 2
2
GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA,
GT1155-QSBDA, GT1150-QLBDA
1) 2)
3)
4)
5) 6) 3)
7)
10) 11)
Battery cover opened
12)
Power supply terminal layout
No.
9)
1) Bus interface
7) CF card cover
8) Battery cover
9) Power terminal
10) CF card interface
11) CF card eject button
12) Battery
3)
Name
2) RS-232 interface
3) Hole for unit installation fitting
4) Rating plate (nameplate)
5) CF card access LED
6) CF card access switch
8)
3)
CF card cover opened
Specifications
Compatible GOT : GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ
Use : For connection to QCPU (Q mode)/motion controller
CPU (Q series)
Compatible GOT : GT1155-QTBDA, GT1155-QSBDA, GT1150-QLBDA
Use : For connection to QnA/ACPU/motion controller CPU
(A series)
For communicating with controller (bar code) or personal computer (OS installation, project data download, transparent) (D-sub 9-pin male)
Hole for the inserting installation fittings (accessory) during the GOT installation to the panel (4 holes at top and bottom)
-
Lit: CF card accessed Not lit: CF card not accessed
Switch for prohibiting access to CF card before removing the CF card from the GOT
ON : CF card being accessed (CF card removal prohibited)
OFF : No access to CF card (CF card removal possible)
Open or close when inserting or removing the CF card.
Open or close when replacing the battery.
Power terminal and FG terminal (for power supply (24VDC) to GOT and grounding)
Interface for installing the CF card to GOT
Button for removing the CF card
GT11-50BAT battery for storing clock data, alarm history and recipe data
(The project data is stored in the built-in flash memory.)
4 - 3
4.2 Back Panel
5. EMC DIRECTIVE
For the products sold in European countries, the conformance to the EMC Directive, which is one of the
European Directives, has been a legal obligation since 1996. Also, conformance to the Low Voltage
Directive, another European Directives, has been a legal obligation since 1997.
Manufacturers who recognize their products must conform to the EMC and Low Voltage Directives required to declare that their products conform to these Directives and put a "CE mark" on their products.
Products that the EMC Directive applies to are marked with the CE mark logo.
2
5.1 Requirements for Conformance to EMC Directive
The EMC Directive specifies that products placed on the market must "be so constructed that they do not cause excessive electromagnetic interference (emissions) and are not unduly affected by electromagnetic interference (immunity)".
The applicable products are requested to meet these requirements.
The sections 5.1.1 through 5.3.2 summarize the precautions on conformance to the EMC Directive of the machinery constructed using the GOT.
The details of these precautions has been prepared based on the requirements and the applicable standards control. However, we will not assure that the overall machinery manufactured according to these details conforms to the above-mentioned directives. The method of conformance to the EMC Directive and the judgment on whether or not the machinery conforms to the EMC Directive must be determined finally by the manufacturer of the machinery.
5.1.1
Standards applicable to the EMC Directive
The following products have shown compliance through direct testing (to the identified standards) and design analysis (forming a technical construction file) to the European Directive for Electromagnetic
Compatibility (89/336/EEC) when used as directed by the appropriate documentation
Type : Programmable Controller (Open Type Equipment)
Models : MELSEC GOT series products, identified here, manufactured from April 1st, 2005
GT1155-QSBD and GT1150-QLBD (For this product see note under and over the page).
Standard
EN61131-2 : 2003
Programmable controllers
- Equipment, requirement and tests
EMI
EMS
Remark
Compliance with all relevant aspects of the standard.
(Radiated Emissions)
Compliance with all relevant aspects of the standard.
(ESD,RF electromagnetic field, EFTB, Surge, RF conducted disturbances and Power frequency magnetic field)
3
4
5
6
7
1
8
5.1 Requirements for Conformance to EMC Directive
5.1.1 Standards applicable to the EMC Directive
5 - 1
5.1.2
Control cabinet
The GOT is an open type device (device installed to another device) and must be installed in a conductive control panel or cabinet.
It not only assure the safety but also has a large effect to shut down the noise generated from GOT, on the control panel.
(1) Control cabinet
(a) Use a conductive control cabinet.
(b) When attaching the control cabinet's top plate or base plate, mask painting and weld so that good surface contact can be made between the cabinet and plate.
(c) To ensure good electrical contact with the control cabinet, mask the paint on the installation bolts of the inner plate in the control cabinet so that contact between surfaces can be ensured over the widest possible area.
(d) Earth the control cabinet with a thick wire so that a low impedance connection to ground can be ensured even at high frequencies. (22mm 2 wire or thicker is recommended.)
(e) Holes made in the control cabinet must be 10 cm (3.94inch) diameter or less. If the holes are
10cm (3.94inch) or larger, radio frequency noise may be emitted.
In addition, because radio waves leak through a clearance between the control panel door and the main unit, reduce the clearance as much as practicable.
The leakage of radio waves can be suppressed by the direct application of an EMI gasket on the paint surface.
(2) Connection of power and ground wires
Ground and power supply wires for the GOT must be connected as described below.
(a) Provide an earthing point near the GOT. Earth the power supply's FG terminal (FG: Frame
Ground) with the thickest and shortest wire possible. (The wire length must be 30cm
(11.18inch) or shorter.)
The FG terminal function is to pass the noise generated in the GOT to the ground, so an impedance that is as low as possible must be ensured. As the wires are used to relieve the noise, the wire itself carries a large noise content and thus short wiring means that the wire is prevented from acting as an antenna.
Note) A long conductor will become a more efficient antenna at high frequency.
(3) Electrical shock prevention
In order to such as the operators from electric shocks, the control box must have the following functions :
(a) The control cabinet must be equipped with a lock so that only skilled or qualified personnel.
(b) The control cabinet must be fitted with advice which automatically stops the power supply when the cabinet is opened.
(4) Dustproof and waterproof features
The control box also has the dustproof and waterproof functions. Insufficient dustproof and waterproof features lower the insulation withstand voltage, resulting in insulation destruction.
The insulation in our GOT is designed to cope with the pollution level 2, so use in an environment with pollution level 2 or better.
Pollution level 1: An environment where the air is dry and conductive dust does not exist.
Pollution level 2: An environment where conductive dust does not usually exist, but occasional temporary conductivity occurs due to the accumulated dust.
Generally, this is the level for inside the control box equivalent a control room
or on the floor of a typical factory.
5 - 2
5.1 Requirements for Conformance to EMC Directive
5.1.2 Control cabinet
Pollution level 3: An environment where conductive dust exits and conductivity may be generated due to the accumulated dust.
An environment for a typical factory floor.
Pollution level 4: Continuous conductivity may occur due to rain, snow, etc.
An outdoor environment.
5.1.3
Grounding
It is necessary to use the GOT grounding terminal only when it is in the grounded condition.
Be sure to ground the grounding for the safety reasons and EMC Directives.
Functional grounding : Improves the noise resistance.
Products that the EMC Directive applies to are marked with the CE mark logo.
1
2
3
4
5
6
7
8
5.1 Requirements for Conformance to EMC Directive
5.1.3 Grounding
5 - 3
5.2 System Configuration when EMC Directive is
Applicable
Connection conditions and models where the EMC Directive is applicable are shown below. (Available April,
2005)
5.2.1
About models applicable to the EMC Directive
The following table lists the modules compliant with the EMC Directive.
: Compliant with EMC Directive : Not compliant with EMC Directive
EMC Directive Item
GT1155-QSBD, GT1150-QLBD
GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ,
GT1155-QSBDA, GT1150-QLBDQ, GT1150-QLBDA
Hardware version
B
-
Please use the GOT whose hardware version is later than that described.
Confirm the hardware version with the products rating plate.
(Products that the EMC Directive applies to are marked with the CE mark logo.)
GRAPHIC OPERATION TERMINAL
MODEL
IN 20.4
GT1155-QSBD
26.4VDC POWER 9.84W MAX
SERIAL 540001 BC
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
JY550D26101A
80M1 IND. CONT. EQ
US LISTED
BC
Hardware version
5.2.2
Connection format
Connection conditions where the GT11 is applicable to the EMC Directive are shown below.
Connection format: CPU direct connection (RS-422)
If connecting to a PLC not from this company (MELSEC-FX
2N
series), refer to the manual of the connected device (PLC, microcomputer) for information about the applicability of the EMC Directive.
5 - 4
5.2 System Configuration when EMC Directive is Applicable
5.2.1 About models applicable to the EMC Directive
5.3 Wiring Precautions the Part which Matches the
EMC Directives
Connect and wire GOT equipment as instructed below.
If the GOT equipment is configured in a way that differs from the following instructions then the system will not comply with EMC directives.
5.3.1
About the cable used
Any device which utilizes a data communication function is susceptible to the wider effects of local EMC noise. Therefore, when installing any communication cables care should always be taken with the routing and location of those cables. The GOT units identified on the previous page are compliant with the EMC requirement when the following communication cables are used.
Existing Cables GOT Unit
GT1155-QSBD and
GT1150-QLBD
GT01-C30R4-8P modified as shown in EX.1
User Made Cables
Those cables need to be independently tested by the user to demonstrate EMC compatibility when they are used with Mitsubishi GOT unit and FX2N Programmable
Controllers.
1
2
3
(250mm)
GT01-C30R4-8P
F = Ferrite core
Ex. Tokin - ESD-R-17S or similar
100mm
4
Programmable controller
F F F
GOT units
140mm
Comes equipped
Added by user Added by user
5.3.2
Method to connect the power wire and ground wire
The GT1155-QSBD and GT1150-QLBD unit requires an additional ferrite filter to be attached to the 24V DC power supply cables. The filter should be attached in a similar manner as shown in the figure opposite, i.e. the power cables are wrapped around the filter. However, as with all EMC situations the more correctly applied precautions the better the systems Electro-magnetic Compatibility. The ferrite recommended is a
TDK ZCAT3035-1330 or similar. The ferrite should be placed as near to the 24V DC terminals of the
GT1155-QSBD and GT1150-QLBD as possible (which should be within 75mm of the GOT terminal).
5
6
INPUT
24V DC
+
7
Up to
75mm
8
5.3 Wiring Precautions the Part which Matches the EMC Directives
5.3.1 About the cable used
5 - 5
6. INSTALLATION
MOUNTING PRECAUTIONS
DANGER
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT to/from the panel.
Not doing so can cause the unit to fail or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the option function board on to/from the GOT.
Not doing so can cause the unit to fail or malfunction.
When installing the option function board or battery, or operating the reset switch, wear an earth band etc. to avoid the static electricity.
The static electricity can cause the unit to fail or malfunction.
MOUNTING PRECAUTIONS
CAUTION
Use the GOT in the environment that satisfies the general specifications described in this manual.
Not doing so can cause an electric shock, fire, malfunction or product damage or deterioration.
When mounting the GOT to the control panel, tighten the mounting screws in the specified torque range.
Undertightening can cause the GOT to drop, short circuit or malfunction.
Overtightening can cause a drop, short circuit or malfunction due to the damage of the screws or the
GOT.
Securely connect the option function board to the connector provided for the board.
When inserting/removing a CF card into/from the GOT, turn the CF card access switch off in advance.
Failure to do so may corrupt data within the CF card.
When inserting a CF card into the GOT, push it into the insertion slot until the CF card eject button will pop out.
Failure to do so may cause a malfunction due to poor contact.
When removing a CF card from the GOT, make sure to support the CF card by hand, as it may pop out.
Failure to do so may cause the CF card to drop from the GOT and break.
6 - 1
6.1 Control Panel Inside Dimensions for Mounting
GOT
Mount the GOT onto the control panel while considering the following control panel inside dimensions.
Vertical installation of the GOT requires a space with the same dimensions as the horizontal installation turned 90 degrees clockwise (seen from the display side).
Applicable cable
Some cables may need to be longer than the specified dimensions when connecting to the GOT.
Therefore, consider the connector dimensions and bending radius of the cable as well for installation.
1
GT1155-QSBD, GT1150-QLBD
30 (1.19")
152 (5.99")
CF CARD
ACCESS ON
CF CARD
RS-232
1)
RS-422
BATTERY
I/F
(FG)
INPUT
24V DC
+
1
2
3
4
5
Unit: mm (inch)
RESET
No
1) PLC connection cable/PC connection cable
Name
6
7
8
6.1 Control Panel Inside Dimensions for Mounting GOT
6 - 2
2
GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA, GT1155-
QSBDA, GT1150-QLBDA
A 152 (5.99")
1)
2)
Type
GT1155-QTBDQ
GT1155-QSBDQ
GT1150-QLBDQ
GT1155-QTBDA
GT1155-QSBDA
GT1150-QLBDA
A B
56(2.20) 40(1.57)
38(1.50) 40(1.57)
Unit: mm(inch)
B
No
1)
Bus cable
2) PC cable/barcode cable
Name
6 - 3
6.1 Control Panel Inside Dimensions for Mounting GOT
6.2 Panel Cutting Dimensions
Make holes in the panel according to the dimensions list below.
Also, ensure 10mm of space in upper and lower parts of the panel for mounting fixtures.
Horizontal format (If the vertical format is selected, the dimension must be rotated 90 degrees.)
153
+2
-0
+0.08"
(6.03" )
10 (0.4") or more
1
2
3
10 (0.4") or more
Unit: mm (inch)
6.3 Mounting Position
When mounting the GOT, the following clearances must be maintained from other structures and devices.
The below diagram represents a horizontal installation. (The same clearances must be maintained when rotating the GOT 90 degrees clockwise for a vertical installation.)
Installation Environment A,D B
In the presence of radiated-noise or heat-generating equipment nearby
50 mm (1.97") or more
80 mm (3.14") or more
*1
In the absence of radiated-noise or heat-generating equipment nearby
20 mm (0.79") or more
*1 Vertical Format....50 mm (1.97") or more (20 mm (0.79") or more)
*2 Horizontal Forma....80 mm (3.14") or more (20 mm (0.79") or more)
20 mm (0.79") or more
When the CF card is not used
50 mm (1.97") or more
*2
20 mm (0.79") or more
C
When the CF card is used
100 mm (3.93") or more
E
100 mm (3.93") or more
20 mm (0.79") or more
4
5
6
7
E
C D
8
Panel thickness: 2 to 4mm
(0.08 to 0.16inch)
6.2 Panel Cutting Dimensions
6 - 4
6.4 Control Panel Temperature and Mounting Angle
When mounting the main unit to a control panel or similar fixture, set the GOT display section as shown below.
1
Horizontal installation
When the temperature inside the control panel is 40 to 55 , the mounting angle should be in the range from 60 to 105 degrees.
GOT back panel
105°
GOT display section
Control panel, etc.
60°
• The GOT will have a longer lifetime if used within the mounting angles shown above.
Ideally, the temperature inside the control panel should not exceed 0 to 40
2
Vertical installation
When the temperature inside the control panel is 40 to 50
, the mounting angle should be in the range from 60 to 105 degrees.
GOT back panel
105°
GOT display section
Control panel, etc.
60°
• The GOT will have a longer lifetime if used within the mounting angles shown above.
Ideally, the temperature inside the control panel should not exceed 0 to 40 .
6 - 5
6.4 Control Panel Temperature and Mounting Angle
6.5 Installation Procedure
The GOT is designed to be embedded into a panel.
Mount the GOT by following the procedure below.
For panel cutting dimensions, refer to Section 6.2.
Note that the panel thickness should be within 5mm.
1
Installing the packing
(1) GT1155-QSBD and GT1150-QLBD
Install packing to the packing installation groove on the back panel of the GOT.
While referring to the cross sectional view of the packing shown right, push the thinner side into the packing groove.
(Right drawing is the example of lateral format.)
(2) GT1155-QTBDQ, GT1155^QSBDQ,
GT1150-QLBDQ, GT1155-QTBDA, GT1155-QSBDA, and GT1150-QLBDA
Units are shipped with the packing attached.
Packing
Magnified illustration
2
Inserting into the panel face
Insert the GOT from the front side of the panel.
1
2
3
Packing
Packing installation groove
Packing cross sectional view
Inserting direction
4
5
Mounting hole
6
7
8
6.5 Installation Procedure
6 - 6
3
Fixing the GOT
Engage the hook of the mounting fitting (accessory) to the unit fixing hole of the GOT and tighten the screw until the GOT is fixed with the mounting bolt (accessory).
The GOT will be fixed in 4 upper/lower parts.
Tighten the mounting screw with the specified torque.
(Failure to do so may distort the panel and make a surface waviness on the protective sheet.)
GOT
Tightening torque
GT1155-QSBD
GT1150-QLBD
0.3 to 0.5N•m
GT1155-QTBDQ
GT1155-QTBDA
GT1155-QSBDQ
GT1155-QSBDA
GT1150-QLBDQ
GT1150-QLBDA
0.36 to 0.48N•m
Enlarged view
Enlarged view
Mounting bracket
Mounting screw
Mounting bracket
Mounting screw
GT1155-QSBD ,GT1150-QLBD GT1155-QTBDQ, GT1155-QTBDA,
GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, GT1150-QLBDA
4
A protection film is attached on the display section of GOT prior to shipment.
Remove the film when the installation is completed.
6 - 7
6.5 Installation Procedure
7. WIRING
WIRING PRECAUTIONS
DANGER
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
Please make sure to ground FG terminal of the GOT power supply section by applying 100 or less which is used exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product.
Not doing so can cause a fire or failure.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT.
Not doing so can cause a fire, failure or malfunction.
WIRING PRECAUTIONS
CAUTION
Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
This chapter describes the wiring to the GOT power supply section.
(1) For the connection with a PLC, refer to the following.
GOT1000 Series Connection Manual
(2) For the dimensional drawing of connection cables, refer to the following.
Appendix 1 External Dimensions
Remark
General preventive measures against noise
There are two kinds of noises: Radiated noise that is transmitted into the air and
Conductive noise that is directly transmitted along connected lines.
Countermeasures must be taken considering both kinds of noises and referring to the following 3 points.
(1) Protecting against noise
(a) Keep signal lines away from noise sources such as a power cable or a highpower drive circuit.
(b) Shield the signal lines.
(2) Reducing generated noise
(a) Use a noise filter, etc. to reduce the level of the noise generated due to a source such as a high-power motor drive circuit.
(b) Attach surge killers to the terminals on the No Fuse Breaker (NFB), electromagnetic contactors, relays, solenoid valves, and generators to suppress noise interference.
(3) Releasing noise to the ground
(a) Make sure to connect the ground cable to the ground.
(b) Use a short and thick cable to lower its impedance.
(c) Ground the power system and the control system separately.
7 - 1
2
3
4
5
6
7
8
1
7.1 Power Supply Wiring
7.1.1
Wiring example
Connect the power supply to the power terminals on the back panel of the GOT.
Use 0.75mm
2
or thicker cables to avoid voltage drop and tighten the terminal screw with the specified torque securely.
1
GT1155-QSBD, GT1150-QLBD
CF CARD
INPUT
24V DC
+
PC and external device connection cables
INPUT
24V DC
+
Grounding
(100 or less)
24VDC power supply
2
GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA,
GT1155-QSBDA, GT1150-QLBDA
PLC connection cable
I/F
INPUT
24V DC
+
PC and barcode connection cable
Class D grounding
(class 3 grounding)
24VDC power supply
7 - 2
7.1 Power Supply Wiring
7.1.1 Wiring example
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible.
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
GOT
Other device
Grounding
(100 or less)
GOT
Other device
Grounding
(100 or less)
GOT
Other device
(1) Independent ground
...... Best condition
(2) Shared grounding
...... Good condition
(3) Common grounding
...... Not allowed
• Use the cable of 2mm
2
or more for grounding.
Set the grounding point closer to the GOT to make the grounding cable short as possible.
Recommended terminal shape
3.2
Terminal screw
Solderless terminal
Terminal screw
Solderless terminal
6.2mm or less
3.2
6.2mm or less
Cable size
Solderless terminal
Tightening torque
When wiring one cable to one terminal
When wiring two cables to one terminal
For power supply: 0.75mm
2
min. For grounding: 2mm
2
min.
M3 solderless terminal (applicable solderless terminal: RAV 1.25-3, V2-N3A and FV2-N3A)
0.5 to 0.8N•m
7.1.2
The cause of malfunctions related wiring/Remedy
Grounding of the GOT may cause electric potential difference and noise interference, which may result in
GOT malfunctions.
These problems may be resolved by taking the following measures.
1
Wiring path of the GOT's ground cable and power line
Bundling the GOT's ground cable and power line together can cause interference noise, which may result in malfunctions.
Keeping the GOT's ground cable and power line away from each other will help minimize noise interference.
GRAPHIC OPERATION TERMINAL GRAPHIC OPERATION TERMINAL GOT 1000
1
2
3
4
5
6
7
FG
MITSUBISHI
FG
MITSUBISHI
8
Power supply for power equipment Power supply for power equipment
Good : Wiring the ground cable away from the
power cable
Bad : Bundling the ground cable and
the power cable
7.1 Power Supply Wiring
7.1.2 The cause of malfunctions related wiring/Remedy
7 - 3
2
Connecting the ground cable from the panel that houses control equipment to the panel to which the GOT is grounded
When running a single ground cable from the panel that houses such piece of control equipment as a sequencer to the panel to which the GOT is grounded, the ground cable may have to be directly connected to the terminal on the GOT.
GRAPHIC OPERATION TERMINAL
GOT
1000
Connection cable
MITSUBISHI
FG
Ground cable from the panel that houses control equipment
If electric potential difference between the ground points created by it causes malfunctions, lowering the voltage as shown in Remedy 1 below may solve the problem.
7 - 4
7.1 Power Supply Wiring
7.1.2 The cause of malfunctions related wiring/Remedy
• Remedy 1 (Refer to the figures Remedy 1-1 and 1-2 below.)
If the electric potential difference between the ground cable and the panel that houses the GOT is creating problems, connect the ground cable to the panel also.
If the wiring method as shown in Remedy 1-1 is not feasible, follow Remedy 1-2.
GRAPHIC OPERATION TERMINAL GRAPHIC OPERATION TERMINAL GOT 1000
Connection cable
Ground cable from the panel that houses control equipment
Use the thickest cable possible.
FG
MITSUBISHI
Connection cable
Ground cable from the panel that houses control equipment
Use the thickest cable possible.
FG
MITSUBISHI
Panel grounding Panel grounding
Remedy 1-1 Remedy 1-2
If taking Remedy 1 worsens noise interference, taking Remedy 2 may alleviate it.
• Remedy 2 (Refer to the figures Remedy 2-1 and 2-2 below.)
Attach a ferrite core to the cable if noise from the GOT panel has adverse effects on the GOT when Remedy
1 is taken.
Wind the wire around the ferrite core several times (approx. 3 times), if a ferrite core is used.
If the wiring method as shown in Remedy 2-1 is not feasible, follow Remedy 2-2.
GRAPHIC OPERATION TERMINAL GOT 1000
Connection cable
MITSUBISHI
Ground cable from the panel that houses control equipment
Use the thickest cable possible.
FG
Remedy 2-1
Ferrite core
Panel grounding
GRAPHIC OPERATION TERMINAL GOT 1000
Connection cable
Ground cable from the panel that houses control equipment
Use the thickest cable possible.
FG
MITSUBISHI
Remedy 2-2
Ferrite core
Panel grounding
1
2
3
4
5
6
7
8
7.1 Power Supply Wiring
7.1.2 The cause of malfunctions related wiring/Remedy
7 - 5
7.2 Wiring inside and outside the panel
7.2.1
Wiring inside
Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other.
Noise interference that is generated by cables that cross each other may cause malfunctions.
Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers
(NFB), electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors.
Refer to the section to follow for surge killers.
Power cable
NFB
7.2.3 Attaching surge killers to control equipment
Uncrossed power lines and communication cables
Crossing power lines and communication cables
Power cable
PLC
GOT connection cable
NFB
PLC
GOT connection cable
PLC I/O wire
PLC
I/O wire
MC MC MC RA
Drive control wire
Terminal block
RA MC RA
Drive control wire
Terminal block
RA
7.2.2
Outside the panel
To pull the power line and communication cable out of the panel, make two pullout holes away from each other and pull the cables through.
Putting both cables through the same pullout hole will increase noise interference.
Power line
Power line
Connection cable
Connection cable
Pullout hole Pullout hole
Keep the power line and communication cable inside the duct at least 100 mm away from each other.
If that is not possible, the use of a metal separator inside the duct can reduce noise interference.
Power line
Wiring duct Separator
100mm or more
Signal line
Power line
Signal line
Wiring the power line and communication cable inside the duct
7 - 6
7.2 Wiring inside and outside the panel
7.2.1 Wiring inside
7.2.3
Attaching surge killers to control equipment
If communication errors happen in synch with the on/off signals from certain control equipment (referred to as "load" hereafter) such as no fuse breakers, electromagnetic contactors, relays, solenoid valves, and induction motors, surge noise interference is suspected.
If this problem happens, keep the ground cable and communication cable away from the load.
If that is not possible, an installation of a surge killer will help reduce noise interference.
Place the surge killer as close to the load as possible.
Remedy for AC inductive load
Keep the ground cable and communication cable away from each other.
Output
C
R
L:Load
AC
Output equipment such as PLC output unit
Remedy for DC inductive load
Keep the ground cable and communication cable away from each other.
Place the surge killer near the load.
1
2
3
4
Output
D
DC
Output equipment such as PLC output unit
L:Load
Place the surge killer near the load.
5
6
7
8
7.2 Wiring inside and outside the panel
7.2.3 Attaching surge killers to control equipment
7 - 7
7.2.4
Wiring the FG wire of the BUS cable
1
To connect the QCPU, motion controller CPU (Q series) and GOT
The cable for connection to the QCPU, motion controller CPU (Q series) does not have a FG wire that needs to be grounded.
2
To connect QnACPU, ACPU, motion controller CPU (A series) and GOT
When using GT15-C FXSS-1 or GT15-C BS, ground the FC wires as shown in the figure below.
(1) GT15-C EXSS-1
Leave unconnected
PLC
GOT
(GT15-C BS)
OUT IN
FG
LG
N
L
(GT15-EXCNB)
L N FG
2SQ wire to the FG terminals to be 28 cm or less
1
Ground the FG terminal of the power supply terminal block on the GOT.
2
FG wires on GT15-C BS must be 28 cm or less.
3
Leave the FG ground wire on GT15-EXCNB unconnected.
4
Connect the FG wire on GT15-C BS on the GOT side to the FG terminal of the power supply terminal block on the GOT.
5
Connect the FG wire on GT15-C BS on the PLC side to the FG terminal of the power supply terminal block on the PLC.
6
Connect the LG and FG terminals on the terminal block, and provide a single grounding point for them.
(2) GT15-C BS
For both GOTs, provide the same grounding as described in the section (1) above to both GOTs.
7 - 8
7.2 Wiring inside and outside the panel
7.2.4 Wiring the FG wire of the BUS cable
8. OPTION
8.1 CF Card
The CF card is used to transmit the OS or project data and to save the data of the alarm history function.
Refer to the following for details.
Chapter 13 FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
8.1.1
Applicable CF card
The following CF cards are applicable for GT15
Model
GT05-MEM-32MC
GT05-MEM-64MC
GT05-MEM-128MC
GT05-MEM-256MC
Flash ROM 32MB
Flash ROM 64MB
Flash ROM 128MB
Flash ROM 256MB
.
Description
1
2
3
4
The flash PC card of the GOT-A900 series
In the GT11 , the flash PC card for GOT-A900 series cannot be used.
Use the CF card which is described in the above.
5
6
7
8
8.1 CF Card
8.1.1 Applicable CF card
8 - 1
8.1.2
Installing and removing procedures of the CF card
Install/remove the CF card with the power supply of GOT is OFF or CF card access switch is "OFF".
1
Installing
1
Set the CF card access switch of the GOT to "OFF", and make sure that the CF card access LED turns off. (When the CF card access LED turns off, the CF card can be installed even during the GOT power on.)
CF card access LED
CF card access switch
CF card
I/F
INPUT
24V DC
CF card
2
To install the CF card to the GOT, insert the CF card into the CF card interface with its front side outside.
Push-in the CF card until the CF card eject button snaps.
GT1155-QSBD, GT1150-QLBD
CF card front face
CF card
3
Turn the CF card access switch on.
After the CF card access switch is turned on, the CF card can be used.
CF card front face
CF card eject button
8 - 2
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
2
Removing
1
Set the CF card access switch of the GOT to "OFF."
Make sure that the CF card access LED turns off.
When the CF card access LED turns off, the CF card can be installed or removed even during the GOT power on.
CF card access LED
CF card access switch
CF card
1
2
I/F
INPUT
24V DC
2
Push-in the CF card eject button of the GOT to eject the CF card, and then remove the CF card.
3
CF card
GT1155-QSBD, GT1150-QLBD
4
CF card eject button
Push.
5
Precautions for removing the CF card
(1) While the CF card access LED is on, do not install/remove the CF card or power off the GOT.
To do so may cause data corruption or malfunction.
(2) When ejecting the CF card, support it by hand since it may pop out.
Failure to do so may cause a fall of the CF card leading to failure or damage of the card.
6
7
8
8.1 CF Card
8.1.2 Installing and removing procedures of the CF card
8 - 3
8.2 Memory Card Adaptor
• The memory card adaptor is used to convert the CF card into the memory card (Type II).
Install the memory card adaptor to a PC equipped with a PCMCIA interface, to write the OS or project data on the CF card from the PC or load alarm history data from the CF card to the PC.
Refer to the following for the details related to CF card.
8.2.1
Applicable memory card adaptor
The following memory card adaptor is applicable.
Model
GT05-MEM-ADPC
Contents
Adaptor converting from CF card to memory card (Type II)
8.2.2
Installing procedure of the CF card into a memory card adaptor
Fit the CF card in the memory card adaptor.
CF card Memory card adaptor
8 - 4
8.2 Memory Card Adaptor
8.2.1 Applicable memory card adaptor
8.3 Option Function Board
1
GT1155-QSBD, GT1150-QLBD
To use the optional functions, the option function board is necessary.
For GT11 with hardware version C or later, option function can be used without mounting the option function board.
Refer to the following for the functions requiring the option function board.
GT Designer2 Version Screen Design Manual
Checking method of hardware version
Confim the hardware version with the products rating plate.
1
2
3
GRAPHIC OPERATION TERMINAL
MODEL
IN 20.4
GT1155-QSBD
26.4VDC POWER 9.84W MAX
SERIAL 540001 BC
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
JY550D26101A
80M1 IND. CONT. EQ
US LISTED
BC
Hardware version
4
2
GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, GT1150-QLBDA
The above models of GOTs have built-in option functions and do not require the option function board.
8.3.1
Applicable option function board
The table below shows the type of option function board that can be used with GT1155-QSBD and GT1150-
QLBD.
Model Contents
GT11-50FNB Option function board
8.3.2
Part names
Groove for reverse installation protection
Connector for connecting GOT
5
6
7
Lever for removal
Groove for reverse installation protection
8
8.3 Option Function Board
8.3.1 Applicable option function board
8 - 5
8.3.3
How to install or remove the option function board
1
Installing
1
Turn the GOT power off.
2
Rise the lever on the dummy cover with a fingernail as shown in the figure on the right.
3
Pinch the lever with fingers and pull-up it vertically to remove the dummy cover.
4
Install the option function board to the option function board connector on the back panel of the GOT.
Push-down the option function board by approximately
0.5mm with fingers along the groove for reverse installation protection.
Cross sectional view (with option function board installed)
*1
Push-down by approx. 0.5mm at four corners.
GOT main unit
*1:Option function
board
*1
Floated
*1
Inclined
Do not keep the option function board in a floated or inclined status.
Do not touch the circuit board in the GOT main unit during the option function board installation.
Dummy cover
Dummy cover
Option function board
Groove for reverse installation protection
8 - 6
8.3 Option Function Board
8.3.3 How to install or remove the option function board
2
Removing
1
Turn the GOT power off.
2
Rise the lever for removing the option function board with a fingernail as shown in the figure on the right.
3
Pinch the lever with fingers and pull-up it vertically to remove the option function board.
Option function board
1
2
Option function board
3
Groove for reverse installation protection
Precautions for installing/removing the option function board
(1) Do not twist the lever when removing the option function board. Otherwise the lever may be broken.
(2) Install the dummy cover when not using the option function board.
4
5
6
7
8
8.3 Option Function Board
8.3.3 How to install or remove the option function board
8 - 7
8.4 Battery
The battery backs up clock data, alarm history and recipe data.
A battery is installed to GT11 when the GT11 is shipped from the factory.
8.4.1
Applicable battery
The following battery is applicable for GT11
Model
GT11-50BAT
.
Contents
Battery for backup of clock data, alarm history and recipe data
8.4.2
Battery specifications
Item
Type
Initial voltage
Storage life
Application
Specifications
Magnesium manganese dioxide lithium primary battery
3.0V
Approx. 5 years (Operating ambient temperature of 25 )
For backup of clock data, alarm history and recipe data
8.4.3
Battery replacement procedure
Replace battery periodically at intervals of 4 to 5 years as reference.
1
Turn the GOT power off.
2
Open the back cover of the GOT.
3
Remove the old battery from the holder.
4
Disconnect the old battery connector and insert the new battery connector within 30s.
5
Insert the new battery into the holder and close the back cover.
6
Turn the GOT power on.
7
Check if the battery condition is normal with the utility.
Refer to the following for the details of battery status display.
Chapter 12 CLOCK SETTINGS AND BATTERY
STATUS DISPLAY (TIME SETTING AND DISPLAY)
Holder
Connector
Holder
Connector
Back cover
Back cover
8 - 8
8.4 Battery
8.4.1 Applicable battery
(1) Battery life
The battery life is approximately 5 years.
The production date of the optional replacement battery can be confirmed by the lot No. marked on the nameplate (label) affixed on the battery.
Nameplate
Model name
L OT.5 4
Year (example: 2005) last digit
Month
(example: Apr.)
1 (Jan.) to 9 (Sep.),
X (Oct.), Y (Nov.), Z (Dec.)
GT11-50BAT
LOT.54
Connector
The production date of the battery built in the purchased GOT can be confirmed by the production No. (serial No.) marked on the GOT main unit
(a) GT1155-QSBD, GT1150-QLBD.
1
2
3
24V DC
+
CF CARD
I/F
GRAPHIC OPERATION TERMINAL
MODEL
IN 20.4
GT1155-QSBD
26.4VDC POWER 9.84W MAX
SERIAL 540001 BC
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
JY550D26101A
80M1 IND. CONT. EQ
US LISTED
Year (example: 2005) last digit
5 4 0 0 0 1
Control number
Month (example: Apr.). 1 to 9: Jan. to Sep.,
X: Oct., Y: Nov., Z: Dec.
(b) GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ,
GT1155-QSBDA, GT1150-QLBDQ, GT1150-QLBDA
GRAPHIC OPERATION TERMINAL
MODEL
GT1155-QTBDQ
IN 24VDC
POWER MAX 00W
SERIAL 00007201DP00001-A
MITSUBISHI ELECTRIC
MADE IN JAPAN
4
5
6
Year (e.g., 2007) The last two digits of the Western calendar year
0
7
2
0
1
Date (e.g., 1st) 1 to 31=1st to 31st
Month
(e.g., February)
1 to 9=Jan. to Sept.,
X = Oct., Y = Nov., Z = Dec.
(2) Battery procurement
The battery is susceptible to natural discharge. Order one when necessary.
7
8
8.4 Battery
8.4.3 Battery replacement procedure
8 - 9
8.5 Protective Sheet
The protective sheet is used to protect the operation surface from damage or dirt when the touch key of GOT display section is operated.
8.5.1
Applicable protective sheet
The following protective sheets are applicable for GT11
Product name
Protective sheet
Model
GT11-50PSCB
GT11-50PSGB
GT11-50PSCW
GT11-50PSGW
.
Protective sheet for 5.7"
Contents
Clear 5 sheets
Antiglare 5 sheets
Clear (Frame: White) 5 sheets
Antiglare (Frame: White) 5 sheets
8.5.2
Installing procedure
1
If the protective sheet has been already attached to the GOT, remove the old one from the GOT display section holding the lower right corner.
If the protective sheet for transportation is attached to the GOT, remove it too.
2
Peel the release paper from the back of the new protective sheet, and attach its adhesive side to the GOT display section.
When attaching the protective sheet, make sure to fit it on the display section closely without leaving any clearance between them.
8 - 10
Remark
Replacement time of protective sheet
Check the status of the protection sheet visually by to the daily inspection.
The visibility becomes worse when there is too much dirt and cracks, causing malfunction. Proceeds replacement promptly.
8.5 Protective Sheet
8.5.1 Applicable protective sheet
8.6 USB Environmental Protection Cover
The USB environmental protection cover protects the USB connector on the front face of GOT from dust, water, and oil.
The GOT is installed with the USB environmental protection cover at factory shipment.
Replace when damage and deterioration are caused.
8.6.1
Applicable USB environmental protection cover
The following USB environmental protection cover is applicable for GT11
Product name
USB environmental protection cover
Model
GT11-50UCOV
.
Contents
Environmental protection cover for USB interface on the main unit front panel (conforming to IP67)
8.6.2
Installing procedure
1
Turn the GOT power off.
2
Disconnect the USB cable from the GOT if one is connected.
3
Open the USB environmental protection cover equipped with the GOT and remove the mounting screws.
Open.
4
Remove the old USB environmental protection cover from the GOT to replace it with the new USB environmental protection cover.
Mounting screw
5
Fix the new USB environmental protection cover while fitting its projection to the hole in the GOT, and mount the cover to the GOT, using the mounting screws.
USB environmental protection cover
Projection
Tightening torque 0.36 to 0.48N•m for both mounting screws A and B
1
2
3
4
5
6
Mounting screw B
Mounting screw A
M3 6 pan head screw
7
Precautions when the USB environmental protection cover is opened
Environmental protective structure of USB interface is "IP2X" when the USB environmental protection cover is opened.
8
8.6 USB Environmental Protection Cover
8.6.1 Applicable USB environmental protection cover
8 - 11
8.7 Stand
Stand is used to fix the GOT to standing status in order to debug the monitor screen data easily.
8.7.1
Applicable stand
The following stand is applicable for GT11 .
Product name
Stand
Model
GT05-50STAND
A9GT-50STAND
Stand for 5.7
"
Stand for 5.7
"
8.7.2
Installing procedure
Contents
1
Adjust the mounting angle of GOT with the angle adjusting fitting of the stand.
Adjust to
45 , 55 , 65 or 75 .
2
Put the GOT into the stand from the stand front side and fix it using the fixtures.
For how to mount the GOT, refer to the following.
Section 6.5 Installation Procedure
For details of the stand, refer to the following.
GT05-50STAND
GOT1000 series User's Manual
A9GT-50STAND
A9GT-50STAND User's Manual
GOT mounting face
Angle adjusting fitting
8 - 12
8.7 Stand
8.7.1 Applicable stand
9. UTILITY FUNCTION
9
Utility is a function, which carries out connection of GOT and PLC, screen display and operation method settings, program/data control and self-check etc.
Refer to the following for the utility function list.
Section 9.2 Utility Function List
10
9.1 Utility Execution
For utility execution, utility has to be displayed by installing BootOS and Standard monitor OS in the C drive
(Flash memory).
There are following three types for the installing Standard monitor OS methods.
11
1) GT Designer2 GOT
Via USB interface or
RS-232 interface
GOT • Installed directly from the GT Designer2
12
GT Designer2
BootOS or Standard monitor OS installation
2) GT Designer2 CF card GOT
OS file write
BootOS or Standard monitor OS installation
GOT
• When GOT is remote, installed easily
using the CF card
Install the CF card in GOT
CF card
GT Designer2
3) GOT CF card GOT
OS file upload
GOT
BootOS, Standard monitor OS installation
• Install OS from GOT to GOT using CF card
GOT
CF card
Install the CF card in GOT
Refer to the following for the installation which uses GT Designer2.
GT Designer2 Version Basic Operation/Data Transfer Manual
Chapter 8 TRANSFERRING DATA
Refer to the following for the installation which uses GOT.
Chapter 16 INSTALLATION OF CoreOS, BOOTOS AND STANDARD MONITOR OS
13
14
15
16
9.1 Utility Execution
9 - 1
9.2 Utility Function List
The items in the following list can be set/operated on the utility screens.
Item
Detail settings
Functions overview
Setting of channel number for the communication interface and assignment of communication driver
Setting of communication parameter.
Sequence program protection key word setting. (When FX series PLC is connected)
Sequence program protection key word deleting. (When FX series PLC is connected)
Sequence program protection status cancel. (When FX series PLC is connected)
Sequence program protection status reactivate. (When FX series PLC is connected)
Setting of opening screen time.
Setting of screen saving time.
Setting of screen saving back light ON/OFF.
Display
Switching message language. (Japanese/English/
Chinese (Simplified)/Korean/
German)
*2
Setting of battery alarm display ON/OFF
Setting of Invert colors ON/OFF
Operation
Time setting & display
Brightness, contrast
Liquid crystal intensity setting.
Liquid crystal contrast setting
Utility call key
Setting of buzzer volume.
Security setting
*3
Security level change. (security password input of each object)
Setting of the menu call key.
Key sensitivity setting Key sensitivity
Key reaction speed
Display of key reaction speed
Selection of base clock.
Display current time of clock.
Set current time of clock.
Display of battery status.
9 - 2
9.2 Utility Function List
System alarm display
GOT start time
Clean
Item
OS information
Project Information
Alarm information
Memory card format
Memory information
GOT data package acquisition
Debug
System monitor
A List editor
FX list editor
Self check
Memory check
Drawing check
Font check
Touch panel checking
I/O check
Functions overview
Installing OS.
Uploading OS.
Property display of OS. (Kind, version, and date)
Data check of system file. (OS)
Downloading project file.
Uploading project file.
Project file deleting.
Copying project file. (A drive A drive)
Property display of project file. (Date, version and screen title)
Data check of project file.
Deleting alarm log file.
Copying alarm log file.
Formatting of CF card and Internal SRAM
Display of free memory space in GOT
Copies the OS and project data to the memory card
Device monitor of PLC, Test function, Present value change of the buffer memory monitor and the buffer memory of intelligent module
Sequence program and parameter change of ACPU
Sequence program and parameter change of FX PLC
A drive memory check (Standard CF card)
C drive memory check (Built-in flash memory)
Missing bits, color, draw, display and overlap display check of liquid crystal
Installed fonts check
Touch panel operation check
Connected target confirmation
Self-loopback check
*4
Displaying GOT errors, CPU errors, network errors
Resetting GOT errors
Displaying GOT start date and time, current time, accumulated operating hours
Display the screen to clean the display section.
*1: Perform the following with the GT Designer2.
• Installing the communication driver
• Downloading the project data with communication settings (channel number and communication driver assignment)
*2: Selectable languages vary, depending on the standard fonts that are installed.
*3: It is necessary to set the security level with GT Designer2.
*4: It is necessary to install the RS-232 connector for test. (Section 14.7 I/O Check)
9
10
11
12
13
14
15
16
9.2 Utility Function List
9 - 3
9.3 Utility Display
To display setting screens for each utility, the main menu must displayed first.
(The utility screen is a factory installed horizontal format screen that cannot be edited.)
(1)
(1)
(2) (2)
(1) Main menu
The menu items that can be selected from the GOT utility are displayed.
Touching a menu item in the main menu will display the setting screen or following selection screen for the item.
(2) System message switch button
This button switches the language used for the utility screen and system alarms.
When touching the Language button, the Select Language screen is displayed.
1
Touch the button of a language to be displayed and then
OK
button, and the language is selected.
*1
9 - 4
9.3 Utility Display
2
Touching the button restarts the GOT and the language on the utility is switched to the selected one.
*1: Only selectable languages are displayed.
The selectable languages differ depending on the fonts installed in the GOT.
For details of the fonts, refer to the following manual.
GT Designer2 Version Screen Design Manual (2.3 Specifications of Applicable Characters)
9
When starting the GOT without selecting any language or the selected language and the installed fonts are not matched
The following screen will be displayed.
Touching the button of a desired language restarts the GOT and the language is switched to the selected one.
10
11
12
13
14
15
16
9.3 Utility Display
9 - 5
9.3.1
Display operation of main menu
The following three types of operation can display the main menu.
(Display the main menu after installing the Standard monitor OS from GT Designer2 to the GOT Flash memory (Internal).)
(1) When project data is undownloaded
After the GOT is turned on, a dialog box for notifying of absence of project data is displayed. After the dialog box is displayed, touch the
OK
button to display the main menu.
GOT power on
Touch the OK button.
(2) When touching menu call key
If you touch the menu call key while user-created screen is displayed, the main menu is displayed.
The menu call key can be set by the GOT utility or GT Designer2.
(At factory shipment, the GOT is set to "Simultaneous 2-point presses on GOT screen upper-right and upper-left corners".)
Menu call key Simultaneous 2-point touch
Horizonal format
Vertical format *
*: The utility screen is a factory installed horizontal format screen that cannot be edited.
(3) When touching special function switch (utility)
If you touch the special function switch (utility) while user-created screen is displayed, the main menu is displayed.
The special function switch (utility) can be set as a touch switch that is displayed on a user-created screen by GT Designer2.
9 - 6
Special function switch
(Utility)
For the details of the special function switch, refer to the following.
GT Designer2 Version Screen Design Manual
Section 6.2 Touch Switch
9.3 Utility Display
9.3.1 Display operation of main menu
Remark
Lock the utility display by password.
When a password is set on the GOT using GT Designer2, a password dialog box is displayed when trying to access the main menu of the utility display.
(The password setting option in GT Designer2 is located in the common menu.)
9
10
11
When the password is not matched, the following error message is displayed.
12
13
When touching
OK
, the screen returns to the monitor screen.
(1) Input operation of password
1) Input the password after touching
0
to
9
,
A
to
F
key.
2) Define the password by touching
Enter
key, after inputting password.
3) To correct the input character, touch
Del
key to delete the correcting character and then reinput/retype the new character.
(2) Password input cancel operation
When button is touched, the screen returns to the monitor screen.
Refer to the following for details on setting passwords.
GT Designer2 Version Screen Design Manual
Section 3.5 Password Setting
14
15
16
9.3 Utility Display
9.3.1 Display operation of main menu
9 - 7
9.3.2
Utility basic configuration
The basic configuration of the screen is as follows.
Title display Close/Return button
(1) Title display
Scroll key
Screen
Title display
The screen title name is displayed in title display part.
As the screen is composed of multiple layers, the title including these layers is displayed.
Title display
If the title overflows the title display area, the middle section is omitted and "..." is displayed at the section.
9 - 8
(2) Close/Return button
When a middle screen of the layers is displayed, if the of screen is touched, returns to the previous screen.
(Close/return) button in the right corner
If this button is touched when directly displayed from monitor screen, the screen is closed and returns to monitor screen.
(3) Scroll button
For screens in which the content does not fit on one screen page, there is a right or down scroll button on the screen.
Scroll one line/column
Scroll window
9.3 Utility Display
9.3.2 Utility basic configuration
9.3.3
Basic operation of settings change
1
Change of setting value
11
Setting item Select button Setting item Select button
1
Touch the select button (setting point) on the screen.
•
OK
Key: It is a key for selecting the setting value. Repeats with each touch
ON OFF
.
•
Numerical
Key: It is a key for inputting the numerical value. It displays the keyboard on the bottom of the screen when touched.
In the above mentioned screen example, there is no setting item which displays the keyboard. For the operation of keyboard refer to the next page.
12
Touching
Enter
confirms the numerical input.
When the setting range exists it repeats the numerical without displaying keyboard.
Example: 4800bps 9600bps 19200bps
•
Setting...
Key: It shifts to the setting screen of each setting item when touched.
13
14
2
Setting contents are reflected if
OK
button is touched.
3
If button is pressed without touching
OK are canceled, then the dialog box is closed.
button, the dialogue below is displayed and the changes
15
16
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button: The operation setting screen is displayed.
9.3 Utility Display
9.3.3 Basic operation of settings change
9 - 9
9
10
2
Keyboard operation
1
Touch the numerical value to be changed.
2
Keyboard for numerical input is displayed and cursor is displayed simultaneously.
The key board display position changes by the position of numerical value touched.
(At the time of numerical input, displayed in the position which will not interrupt the inputting.)
Cursor
Keyboard
3
Input numeric with keyboard.
•
•
•
•
•
•
0
Enter
Key
Cancel
Key
Key
Del
Key
*
to
9
Key : Input the numeric.
: Touching the
: Touching the
:
Del
Enter
Cancel
key completes numeric input and closes the keyboard.
key cancels numeric input and closes the keyboard.
: Moves the cursor left or right if there is an item that can be entered.
key is used when canceling the input by 1 character.
key and the key which is not mentioned do not function.
4
If
Enter
key is touched, numeric input is completed and keyboard is closed.
9 - 10
9.3 Utility Display
9.3.3 Basic operation of settings change
10. COMMUNICATION INTERFACE
SETTING (COMMUNICATION SETTING)
9
In [Communication Setting], the communication interface names and the related communication channel, communication driver names display and channel numbers are set.
Moreover, in [Communication Detail setting], the communication interface details are set. (Communication parameters setting)
10.1 Communication Setting
10.1.1 Communication setting functions
Function
Channel-Driver assign
Channel no. (Ch No.) setting
Communication parameters setting
Contents
Change the assignment of channel No. and communication driver name.
Set the channel numbers of the communication interface.
Set communication parameters of communication devices.
10
11
12
10.1.2 Communication setting display operation
Main menu
( Section 9.3 Utility Display)
Communication setting
Touch
[Communication setting].
13
14
15
16
10.1 Communication Setting
10.1.1 Communication setting functions
10 - 1
10.1.3 Description of communication setting screen
Name of setting item and display item columns for [Communication Setting]
(3)
(3)
(3)
(2)
(2)
(4)
(2)
(4)
(4)
(1)
(1) Channel - Driver assign (GT1155-QSBD and GT1150-QLBD only)
(a) Assigning channel No.
Channel No.s can be assigned to each of the communication drivers installed in the GOT.
Without setting [Communication Settings] in GT Designer2, communication with PLC CPU is only available after assigning a channel No. with this function.
(b) Changing communication driver
The communication driver assigned to the channel can be changed using the communication setting.
(To change the communication driver, it is required to pre-install the communication driver to be changed in the GOT.)
Section 10.1.4 Operation of communication setting
(2) Standard interface display box: Communication interface included as standard in GT11
(a) GT1155-QSBD ,GT1150-QLBD
The standard interface includes the following three types.
RS232 ....For communication with PC (GT Designer2), PLC, microcomputer, bar code reader and other equipment
RS422 ....For communication with PLC and microcomputer
USB........For communication with PC (GT Designer2)
[GOT front face]
USB interface (Standard interface) (mini)
10 - 2
10.1 Communication Setting
10.1.3 Description of communication setting screen
[GOT rear face]
RS-422 interface (Standard interface)
RS-232 interface (Standard interface)
(b) GT1155-QTBDQ, GT1155-QSBDQ, GT1150-QLBDQ, GT1155-QTBDA, GT1155-QSBDA,
GT1150-QLBDA
Standard interfaces have the following three types
BUS.........For communication with PLC
RS232 .....For communication with PC (GT Designer2) and barcode reader
USB.........For communication with PC (GT Designer2)
9
10
11
[GOT front face]
USB interface (Standard interface)
(mini)
[GOT rear face]
RS-232 interface (Standard interface)
BUS interface (Standard interface)
BUS for connection to QCPU (Q mode)/motion controller CPU (Q series), or BUS for connection to QnA/ACPU/motion controller CPU (A series)
12
13
14
15
16
10.1 Communication Setting
10.1.3 Description of communication setting screen
10 - 3
(3) Channel number specification menu BOX
0: Set when the communication interface is not used.
1: Set when connecting to PLC or microcomputer. (Only one can be set among arbitrary communication interfaces.)
8: Set when connecting to a bar code reader.
9: Set when connecting to PC (GT Designer2). (For USB and RS-232 interfaces, the simultaneous setting is possible. However, when either interface is communicating, the communication is not allowed for another interface.)
• Setting is not allowed for 2 to 7, *.
• Fixed to 9 for the USB interface.
• Fixed to 1 for the BUS interface.
(4) Driver display BOX
The name of the communication driver for which a channel number is assigned is displayed.
"None" is displayed in the driver display BOX in the following cases :
• The communication driver is not installed. (
• "0" is set in the channel number specification menu BOX.
When setting the channel number to "9", the communication driver "Host (PC)" is automatically assigned.
Precautions for communication between GOT and connected devices
(1) Installing [Communication driver] and downloading [Communication Settings]
To perform communication with the connected device, the following actions are necessary.
1) Installing [Communication driver] (Up to 4, OS installation)
2) Assigning channel number and communication driver to communication interface (Communication Setting)
3) Downloading [Communication Settings] (project data) assigned in step 2)
Perform 1), 2) and 3) with GT Designer2.
For [Communication Settings], refer to the following manual.
GT Designer 2 Version Screen Design Manual
Section 3.7 Communication Interface Setting (Communication settings).
For installation of [Communication driver] (OS) and download of project data, refer to the following manual.
GT Designer 2 Version Basic Operation/Data Transfer Manual
Chapter 8 TRANSFERRING DATA
10 - 4
10.1 Communication Setting
10.1.3 Description of communication setting screen
(2) When [Communication Settings] has not been downloaded using GT Designer2
(GT1155-QSBD and GT1155-QLBD only)
When [Communication Settings] has not been downloaded, the GOT automatically assigns the installed communication driver as the RS422 interface.
When multiple communication drivers are installed, the GOT automatically assigns the first-installed communication driver to the RS422 interface.
To assign the communication driver to the RS-232 interface or to change the already assigned communication driver, change the settings in the
[Communication Settings] of the utility screen or in the [Communication Settings] of GT Designer2.
On the unit that only allows a bus connection, the installed bus communication driver is assigned to the bus interface.
(a) After automatic assignment
If the
OK
button is clicked to store the settings in the GOT after automatic assignment, the automatic assignment will not be executed from the next startup.
(b) Priority of [Communication Settings] of GT Designer2
When [Communication Settings] is downloaded to the GOT from GT
Designer2 after automatic assignment, the GOT will operate according to the
[Communication Settings] of GT Designer2.
9
10
11
12
13
14
15
16
10.1 Communication Setting
10.1.3 Description of communication setting screen
10 - 5
10.1.4 Operation of communication setting
1
Channel and driver assignment operation (GT1155-QSBD and GT1150-QLBD only)
The operation method for the channel and communication driver assignment is described here.
In this section, the case for changing the computer link connection (Communication driver: [AJ71QC24,
MELDAS C6*]) to CPU direct connection (Communication driver: [A/QnA/QCPU, QJ71C24]) is described.
(In the present example, [Communication Settings] is not downloaded.)
Before starting operation
(1) Restarting the GOT
After Communication Setting is executed, the GOT automatically restarts.
If the project data is downloaded, GOT starts monitoring the communication device after restarting.
Before starting the operation, check for safe conditions.
(2) Setting retention
Once being established, [Channel-Driver assign] is retained until [Communication
Settings] is updated.
1
Install communication driver [A/QnA/
QCPU, QJ71C24] to the GOT
[Communication Settings] with
AJ71QC24, MELDAS C6*.
([Communication Settings] is not downloaded from GT Designer2.)
After installing the communication driver, touch the
CH-Driver assign
[Communication Settings].
button in
2
The screen shown on the left is displayed.
Touch the
Change
button.
3
Touch the communication driver installed to the GOT ([A/QnA/QCPU,
QJ71C24]).
10 - 6
10.1 Communication Setting
10.1.4 Operation of communication setting
4
The [Channel-Driver assign] screen is displayed again.
Touch the
OK
button.
5
Touch the button to return to the
[Communication Settings] screen.
9
10
6
Check that the selected communication driver ([A/QnA/QCPU, QJ71C24]) is assigned.
7
After checking, touch the
OK
button.
8
Touch the button. The GOT restarts.
11
12
Communication driver
(1) Multi-channel function
GT11 can install up to 4 communication drivers.
However, multiple communication drivers cannot be used at the same time.
(Multi-channel function cannot be used.)
(2) Display of communication driver
Communication drivers are displayed in the order of installation.
To change the assigned communication driver to one that is not listed, change the
[Communication Settings] of GT Designer2 and download to the GOT.
13
14
15
16
10.1 Communication Setting
10.1.4 Operation of communication setting
10 - 7
2
Channel number setting operation
1
Touch channel number specification menu BOX to be set.
Keyboard
2
The cursor for the channel number specification menu BOX is displayed.
Simultaneously the keyboard for a numerical input is displayed.
3
Enter the channel number from the keyboard and touch the
Enter
key to settle the entered value.
Setting the channel number to "1" displays the name of the communication driver for which CH No.1 is assigned with GT Designer2 in the driver display box.
3
Communication detail settings switching operation
1
If you touch the driver display BOX, the screen switches to the [Detailed setting] screen of the related communication device.
(
Section 10.2 Communication Detail Settings)
10 - 8
10.1 Communication Setting
10.1.4 Operation of communication setting
10.2 Communication Detail Settings
10.2.1 Communication detail settings functions
Function
Communication parameters setting
Keyword Register
Keyword Delete
Keyword Clear
Keyword Protect
Contents
Set various communication parameters of communication devices.
The settable parameters differ according to the communication device.
For the FX series PLCs, key word for protecting program in the PLC can be set.
For the FX series PLCs, key word for protecting program in the PLC can be deleted.
For the FX series PLCs, the program protection status in the PLC can be cancelled.
For the FX series PLCs with the 2nd keyword in use, the cancelled program protection in the
PLC can be reactivated.
9
10
11
10.2.2 Communication detail settings display operation
1
Touch the driver display BOX of the communication parameter to be set in the [Communication setting] screen.
12
13
2
The screen switches to the [Communication Detail setting] screen.
Set communication parameters from this screen.
Refer to the following for the setting change operation.
Section 9.3.3 Basic operation of settings change
Communication parameter
14
15
16
10.2 Communication Detail Settings
10.2.1 Communication detail settings functions
10 - 9
Communication parameter setting using GT Designer2
(1) Select [System Environment] [Communication Settings] from GT Designer2 to enter the communication parameters for each communication driver.
To change the communication parameter setting after downloading project data, change the setting at [Communication Detail Setting] (described in this section).
For [Communication Settings] using GT Designer 2, refer to the following manual.
GT Designer 2 Version Screen Design Manual
Section 3.7 Communication Interface Setting (Communication Settings)
10.2.3 Display contents of communication detail settings
Display items or setting items of communication detail settings depend on the type of communication driver installed in the GOT.
For the setting contents of each driver, refer to the following.
GT Designer2 Version Screen Design Manual (Section 3.7 Communication Interface
Setting (Communication Settings)
This section describes the items that can be set using only the utility screen.
Keyword settings of MELSEC-FX
On the communication detail setting screen of MELSEC-FX, registration, deletion, cancellation, or protection of the keyword for FX series PLC can be executed.
MELSEC FX
10 - 10
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
1
Regist
Keyword is registered.
1
Touching the
Regist
key pops up a keyboard for keyword input.
2
When the keyword is input and the
Enter
key is touched, registration is completed.
For the keyword, 8 digits from 0 to 9 or A to F must be set.
11
Target PLC
Settings
When keyword and 2nd keyword are registered When only keyword is registered
FX PLC compatible with 2nd keyword
*1
FX PLC not compatible with 2nd keyword
*1
Registration options can be selected.
-
Registration options
*2
cannot be selected.
*1: Refer to the manual for the PLC in use for the models that are compatible with the 2nd keyword.
Options can be selected among "Read/Write Protect", "Write Protect", or "All Protect".
For access restrictions of each setting, refer to the manual of the PLC to be used.
12
13
14
9
10
15
16
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
10 - 11
(1) Selection of keyword protection level
For the devices which can perform the online operation of FX PLC, 3 levels of protection can be set.
When the monitoring or setting change by online devices is needed, set the keyword taking the following into consideration.
(a) When only keyword is registered
Protection level is selected by the head character of keyword.
All operation prohibition: Set the keyword starting with one of A, D to F, or 0 to
9.
Read/incorrect write protection: Set the keyword starting with B.
Erroneous write prohibition: Set the keyword starting with C.
(b) When keyword and 2nd keyword are registered
Protection level is selected by "Registration options".
(2) Applicability of monitoring for each keyword protection level
The applicability of monitoring for each protection level is as follows.
Setting items
Device monitoring
Device change
T, C setting values and file register
(from D1000)
Other than the above
When only keyword is registered
All operation prohibition
Read/ incorrect write protection
Erroneous write prohibition
When keyword and 2nd keyword are registered
All Protect
Read/
Write prohibition
Write
Protect
Keyword unregistered/ protection cancelled
(3) Difference between "All Protect" and "All operation prohibition"
When "All Protect" is selected, both device display and input by the programming tool or GOT are prohibited.
When "All operation prohibition" is selected, device display and input are possible although operations by the programming tool are all prohibited.
10 - 12
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
2
Delete
Registered keyword is deleted.
1
Touching the
Delete
key pops up a keyboard for keyword input.
2
When the correct keyword is input and the
Enter
key is touched, the keyword is deleted.
Target PLC
FX PLC compatible with 2nd keyword
*1
FX PLC not compatible with 2nd keyword*
1
Settings
Input a keyword to be deleted.
Input a keyword to be deleted only into "keyword".
"2nd keyword" is ignored.
*1: Refer to the manual for the PLC in use for the models that are compatible with the 2nd keyword.
15
16
13
14
11
12
9
10
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
10 - 13
3
Clear
To access an FX PLC where a keyword has been registered, keyword protection is cancelled.
1
Touching the
Clear
key pops up a keyboard for keyword input.
2
When the correct keyword is input and the
Enter
key is touched, the protection is cancelled.
Target PLC
FX PLC compatible with 2nd keyword
*1
Settings
Input a keyword to cancel the protection.
FX PLC not compatible with 2nd keyword
*1
Input a keyword into "keyword" to cancel the protection.
"2nd keyword" is ignored.
*1: Refer to the manual for the PLC in use for the models that are compatible with the 2nd keyword.
4
Protect
A keyword with cancelled protection is reactivated for protection.
Keyword protection function is valid when the 2nd keyword is registered.
1
Touching the
Protect
key activates keyword protection.
10 - 14
10.2 Communication Detail Settings
10.2.3 Display contents of communication detail settings
11. DISPLAY AND OPERATION
SETTINGS (GOT SET UP)
Setting screen for display and setting screen for operation can be displayed from GOT setup.
In the setting screen for display and the setting screen for operation, the following settings can be set.
Screen Reference page
Setting screen for display
Setting screen for operation
Description
Opening screen time, screen save time, screen save backlight, language, battery alarm display, invert colors
Brightness, contrast
Buzzer volume, window move buzzer
Security setting
Utility call key
11.1 Display Settings
11.1.1 Display setting functions
Setting regarding display is possible.
The items which can be set are shown below.
Opening screen time
Screen save time
Items
Screen save backlight
Contents
The title display period at the main unit boot can be set.
The period from the user stops the touch panel operation till the screen save function starts can be set.
Whether turn ON or OFF the backlight simultaneously at the screen save function start can be specified.
Setting range
0 to 60 seconds
*1
<At factory shipment: 5 seconds >
0 to 60 minutes
<At factory shipment: 0 minutes>
When set to 0, the function becomes invalid.
ON/OFF
<At factory shipment: OFF>
Language
Battery alarm display
Brightness, Contrast
Japanese
English
Confirmation of the current language and switching language can be performed regarding with the language displayed by utility and dialogue.
Chinese (Simplified)
Korean
German
Factory setting: User-selected language
Whether to display system alarm when the voltage of the
GOT internal battery has dropped can be specified.
The brightness or contrast can be adjusted.
Section 11.2 Brightness, Contrast Adjustment
<At factory shipment: OFF>
Invert colors
*2
User creation screen and utility screen can be set to be highlighted or not.
ON/OFF
<At factory shipment: OFF>
*1 If setting 0, the title screen is not hidden.
The title screen is always displayed for 4 seconds or longer (which changes depending on the project data contents).
*2 Applicated to GT1150-QLBD only.(Standard monitor OS Ver.03.01.00 or later)
(BootOS Ver.03.01.**.M or later)
9
10
11
12
13
14
15
16
11.1 Display Settings
11.1.1 Display setting functions
11 - 1
(1) Display setting by GT Designer2
Set title display period, screen save time and screen save backlight at [GOT set up] in [System Environment] of GT Designer2.
When change a part of the setting after downloading the project data, change the setting by [Display] screen of the GOT.
GT Designer2 Version Screen Design Manual
(Section 3.8 Setting of the GOT display and operation (GOT setup) )
(2) Screen save and screen save backlight OFF function
When using the screen save and screen save back light OFF function, select valid/invalid by the system information reading device in [System Environment] of
GT Designer2.
For system information details, refer the following.
GT Designer2 Version Screen Design Manual
(Section 3.6 Setting System Information)
11 - 2
11.1 Display Settings
11.1.1 Display setting functions
11.1.2 Display operation of display setting
Main menu
( Section 9.3 Utility Display)
GOT setup
Touch [GOT setup].
Touch [Display].
Display
11
12
Touch an item to change settings.
13
Restart after setting change
If return the display to the GOT setup screen by touching the button after the setting of each item is changed and touch the button on the GOT setup screen, the GOT will restart.
After GOT restarts, it is displayed with the changed settings.
If restarted the GOT by powering OFF the GOT without the procedure above, the setting contents are canceled without reflected.
14
If touch , the GOT restarts and the changes are reflected.
15
16
9
10
11.1 Display Settings
11.1.2 Display operation of display setting
11 - 3
11.1.3 Display setting operations
1
Opening screen time, screen save time
1
If touching the setting time (numerical), keyboard is displayed. Input numeric with the keyboard.
2
Setting contents are defined if is touched.
OK
button
3
If button is touched without touching
OK
button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button:The display setting screen is displayed.
4
If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
11 - 4
11.1 Display Settings
11.1.3 Display setting operations
9
2
Screen save backlight, Battery alarm display
1
Setting item is changed if setting item is touched. (ON OFF)
2
Setting contents are defined if is touched
OK
button
10
3
If button is touched without touching
OK
button, the dialogue mentioned left is displayed.
OK
button: The change contents are canceled, and the screen is closed.
Cancel
button:The display setting screen is displayed.
4
If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
11
12
13
14
15
16
11.1 Display Settings
11.1.3 Display setting operations
11 - 5
3
Language
11 - 6
11.1 Display Settings
11.1.3 Display setting operations
1
Touch the setting items to display the
Select Language screen.
2
When touching the button of a desired language, the language is selected and the screen returns to the Display screen.
3
Setting contents are defined if
OK
button is touched. The language display does not change till is carried out.
4
If button is touched without touching
OK
button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button:The display setting screen is displayed.
5
If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
4
Brightness, Contrast
Refer to the following for brightness, contrast setting.
Section 11.2 Brightness, Contrast Adjustment
5
Invert colors
9
10
1
Setting item is changed if setting item is touched. (ON OFF)
2
Setting contents are defined if is touched
OK
button
11
12
3
If button is touched without touching
OK
button, the dialogue mentioned left is displayed.
OK
button: The change contents are canceled, and the screen is closed.
Cancel
button:The display setting screen is displayed.
4
If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
13
14
15
16
11.1 Display Settings
11.1.3 Display setting operations
11 - 7
11.2 Brightness, Contrast Adjustment
11.2.1 Brightness, contrast adjustment function
Brightness or contrast can be adjusted.
(GT1155-QSBD and GT1150-QLBD only)
Function
Brightness setting
Contrast setting
Contents
Brightness of display part can be adjusted by 8 levels.
Contrast of display part can be adjusted by 16 levels.
(GT1155-QTBDQ and GT1155-QTBDA excluded)
11.2.2 Display operation of brightness, contrast
Main menu
( Section 9.3 Utility Display)
GOT setup Display
Touch [Display].
Touch [GOT setup].
Touch
[Brightness, contrast]
Brightness/contrast
Touch [+]/[-] to adjust the brightness.
Touch [+]/[-] to adjust the contrast.
11 - 8
11.2 Brightness, Contrast Adjustment
11.2.1 Brightness, contrast adjustment function
11.2.3 Brightness adjustment operation
9
1
Brightness can be adjusted by touching
, key of brightness adjustment.
2
Contrast can be adjusted by touching ,
key of contrast adjustment.
3
Setting contents are defined if is touched
OK
button
10
11
4
If
OK
button is touched without touching
button, the dialogue box shown on the left displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button:The brightness/contrast adjustment screen is displayed.
5
If close the display setting and GOT setup screens after completing the setting of all items to change with button, GOT restarts and reflects the setting contents.
12
13
14
15
16
11.2 Brightness, Contrast Adjustment
11.2.3 Brightness adjustment operation
11 - 9
11.3 Operation Settings
11.3.1 Operation setting functions
Setting regarding GOT operation can be set.
The items which can be set are described below.
Function
Buzzer volume setting
Contents
Buzzer volume setting can be changed.
Window move buzzer volume setting
Whether turn ON/OFF buzzer when move window can be selected.
Setting range
OFF/SHORT/LONG
<At factory shipment:
SHORT>
ON/OFF
<At factory shipment:
ON>
Key sensitivity setting
Security level change screen can be displayed.
Security setting screen change
Utility call key screen change
Section 11.4 Security Level Change
Utility call key setting screen can be displayed.
Section 11.5 Utility Call Key Setting
The sensitivity of touch panel when GOT screen is touched can be set.
*1 Relationship between the "key sensitivity" setting and the "key reaction speed"
1 to 8
*1
The relationship between "key sensitivity" and "key reaction speed" is shown in the table below.
•Decreasing the "key sensitivity" value will speed up the key reaction speed.
•Increasing the "key sensitivity" value will slow down the key reaction speed.
"Key sensitivity" setting value
"Key reaction speed" [ms]
8
-20
7
-10
6
Standard(±0)
5
+10
4
+20
3
+40
2
+80
1
+120
When the GOT screen recognizes a single touch as two touches, decrease the "key sensitivity" (to slow down the key reaction speed).
Operation settings by GT Designer2
Set buzzer volume and window move buzzer volume by [GOT setup] in [System
Environment] of GT Designer2.
When change a part of the setting, change the setting by the GOT display setting after downloading the project data.
GT Designer2 Version Screen Design Manual
(Section 3.8 Setting of the GOT display and operation (GOT setup))
11 - 10
11.3 Operation Settings
11.3.1 Operation setting functions
11.3.2 Display operation of operation setting
Main menu
( Section 9.3 Utility Display)
GOT setup
Touch [GOT setup].
Touch [Operation].
Operation
9
10
11
Touch an item to change settings.
12
13
Restart after setting change
If return the display to the GOT setup screen by touching the button after the setting of each item (excluding the security setting) is changed and touch the button on the GOT setup screen, the GOT will restart.
After GOT restarts, it is displayed with the changed settings.
If restarted the GOT by powering OFF the GOT without the procedure above, the setting contents are canceled without reflected.
If touch , the GOT restarts and the changes are reflected.
14
15
16
11.3 Operation Settings
11.3.2 Display operation of operation setting
11 - 11
11.3.3 Setting operation of operation
1
Buzzer volume, window move buzzer
1
Setting items are changed if setting item is touched.
Buzzer volume :
SHORT LONG
Window move buzzer : OFF
OFF
ON
2
Security setting
Refer to the following for the security setting operation.
Section 11.4 Security Level Change
3
Utility call key
Refer to the following for the utility call key operation.
Section 11.5 Utility Call Key Setting
2
Setting contents are defined if is touched.
OK
button
3
If
OK
button is touched without touching
button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button:The operation setting screen is displayed.
4
If close the display setting and GOT setup screens with button after completing the setting of all items to change, GOT restarts and reflects the setting contents.
11 - 12
11.3 Operation Settings
11.3.3 Setting operation of operation
4
Key sensitivity setting
9
1
The keyboard is displayed if setting item is touched.
2
Enter the numerical value from the keyboard.
3
The key reaction speed according to the
"key sensitivity" setting is displayed.
4
Setting contents are defined if is touched.
OK
button
10
11
12
13
14
15
16
11.3 Operation Settings
11.3.3 Setting operation of operation
11 - 13
11.4 Security Level Change
11.4.1 Security level change functions
Changes the security level to the same security level set by each object or screen switch.
To change the security level, input the password of the security level which is set in GT Designer2.
Security level setting .....................
GT Designer2 Version Screen Design Manual
(Section 5.8 Security function)
Password setting...........................
GT Designer2 Version Screen Design Manual
(Section 3.5 Set Password)
Restrictions on screen display
The security level change screen cannot be displayed when project data do not exist in GOT. Change the security level after downloading the project data to GOT
11.4.2 Security change display operation
Main menu
( Section 9.3 Utility Display)
GOT setup
Operation settings
Touch [GOT setup].
Touch
[Operation].
Touch
[Security setting]
Security setting
Touch
[Security level change]
Security level change
Input the password of the security level which is set in GT
Designer2.
11 - 14
11.4 Security Level Change
11.4.1 Security level change functions
11.4.3 Security level change operation
1
Password input operation
9
1
By touching
0
to
9
,
A
to
F
key, the password of the changed security level is input.
2
When correcting the input character, touch
Del
key to delete the correcting character and input the password again.
10
11
3
After inputting password, touch the key.
Enter
When the password matches, a message notifying successful change of the security level is displayed.
When the password does not match, an error message is displayed.
4
If
OK
button is touched it returns to the password input screen again.
12
13
14
5
If button is touched it returns to security setting screen.
Remark
About forgetting to return to the original level after changing security level temporarily
When use GOT after temporarily changing the security level, do not forget to return the security level to the original level.
15
16
11.4 Security Level Change
11.4.3 Security level change operation
11 - 15
11.5 Utility Call Key Setting
11.5.1 Utility call key setting function
The key position for calling the main menu of the utility can be specified.
The key position can be specified by one point or two points of 4 corners on the screen.
When the key position is specified by one point, the time to switch to the utility when the key position is kept pressing can be set.
For default setting, the upper left and upper right corners are specified.
Operation settings by GT Designer2
Set the utility call key at [GOT set up] in [System Environment] of GT Designer2.
When change a part of the setting after downloading the project data, change the setting by [Display] screen of the GOT.
GT Designer2 Version Screen Design Manual
(Section 3.8 Setting of the GOT display and operation (GOT setup))
11.5.2 Utility call key display operation
Main menu
( Section 9.3 Utility Display)
GOT setup
Operation settings
Touch [GOT setup].
Touch
[Operation].
Touch
[Utility call key].
Menu call key
Touch buttons to set for the utility call key.
11 - 16
11.5 Utility Call Key Setting
11.5.1 Utility call key setting function
11.5.3 Utility call key setting operation
9
1
Touch or displayed on the four corners of the setting screen.
time it is pressed.
Change the part to be set as a key position to .
2
When the key position is specified by one point, the time to switch to the utility when the key position is kept pressing can be set.
Touch the time area.
3
The keyboard is displayed if the input area is touched.
Input a setting time from the keyboard.
4
Setting contents are defined by touching
OK
button.
5
If button is touched without touching
OK
button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button:The utility call key setting screen is displayed.
6
After finishing all the settings for items to be changed on the operation screen, closing "Operation" and "GOT setup" screens with button restarts GOT and reflects the setting contents.
10
11
12
13
14
15
16
11.5 Utility Call Key Setting
11.5.3 Utility call key setting operation
11 - 17
Setting another key position when there are two
Make the setting after changing either one of the key positions from to
Three of cannot be set at the same time.
Example: When changing the two positions from the upper left and upper right corners to the upper left and lower left corners
.
Change the upper right to . Change the lower left to .
11 - 18
11.5 Utility Call Key Setting
11.5.3 Utility call key setting operation
12. CLOCK SETTINGS AND BATTERY
STATUS DISPLAY
(TIME SETTING AND DISPLAY)
9
10
The clock display setting items and the time when displayed the setting screen are displayed.
The voltage status of the built-in battery is also displayed.
12.1 Time Setting and Display
12.1.1 Time setting and display functions
Time settings and displaying of the status of GOT built-in battery are possible.
Function Contents
Clock setting
Setup the method to adjust the time between GOT clock data and clock data of PLC CPU connected with GOT.
Carry out the display and setup of GOT clock data.
Clock display
GOT internal battery voltage status
Displays GOT internal battery voltage status.
Reference page
12.1.2 Display operation of clock display and setting
11
12
13
Main menu
( Section 9.3 Utility Display)
Time setting & display
14
Touch
[Time setting & display].
Set the Clock settings and Time settings.
15
16
12.1 Time Setting and Display
12.1.1 Time setting and display functions
12 - 1
12.1.3 Clock setting operations
1
Clock setting
Setup the method to adjust the time between GOT data and the clock data of PLC CPU connected with
GOT.
Setting Contents
Adjust the time of GOT clock data to the clock data of PLC CPU.
Adjust
Same as setting in [GOT setup] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual (Section 2.5 Clock Function)
Adjust the time of PLC CPU clock data to the clock data of GOT.
Broadcast
Same as setting in [GOT setup] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual (Section 2.5 Clock Function)
Adjust and Broadcast can be used appropriately.
12 - 2
Adjust/Broadcast
None
Same as setting in [GOT setup] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual (Section 2.5 Clock Function)
No adjustment of clock data.
1
If touch the setup item, the setup contents is changed.
(
Adjust Broadcast Adjust/Broadcast None
)
2
If touch reflected.
OK
button, the setup contents is
3
If touch button without touching
OK button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button: The time display and setting screen is displayed.
4
If touch button, GOT restarts. After restart, GOT operates with the changed settings.
12.1 Time Setting and Display
12.1.3 Clock setting operations
9
(1) When connecting with an external device which does not have clock function.
If set to [Adjust] or [Broadcast] for [Clock setting] while the GOT is connected with external devices (PLC or microcomputers) which do not have clock function, the clock data will not be adjusted.
Refer to the following for the list of PLC installed with clock function.
GT Designer2 Version Screen Design Manual
(Section 2.4.3 PLC CPUs with clock function)
(2) Clock setting and battery
If [Broadcast] or [None] is selected for [Clock setting], the battery status of the
GOT is required to be normal.
Refer to "GOT internal battery voltage status" to check the battery status.
(3) Operation setting by GT Designer2
Carry out the setting of clock setting in [GOT set up] in [System Environment] of
GT Designer2.
To change a part of the setting after downloading the project data, change the setting at the display setting of GOT.
GT Designer2 Version Screen Design Manual
(Section 3.8 Setting of the GOT display and operation (GOT setup))
10
11
12
13
14
15
16
12.1 Time Setting and Display
12.1.3 Clock setting operations
12 - 3
2
Clock display
Carry out the display and setting of GOT clock data.
When setting the clock data, change the clock data on the GOT and controller regardless of clock setting.
The setup methods of clock data are shown below.
1
If touch the clock display section, the keyboard for input is displayed and the clock update stops.
2
Input time with the keyboard by referring to the table below. Input the scheduled time when the operation of is to be carried out since the input time is reflected at the time of the operation of .
The day of the week is displayed automatically according to the input date.
Contents
0
to
9
Key
Input numeric value in cursor position.
/
Key
Key
Move the cursor.
Del
Key
Enter
Cancel
Key
Key
Move the cursor to the left by one character when month, day, time, minutes, seconds.
Del
Key is touched while inputting year,
Carry out nothing when touched other than when inputting the above.
Close the keyboard after the input time is displayed in clock display.
The update of the clock display does not restart even if the keyboard is closed.
The update of the clock display restarts with the operation of .
Cancel the input time and returns the time of clock display to the time at which the keyboard was displayed and close the keyboard.
The update of the clock display does not restart even if the keyboard is closed.
The update of the clock display restarts with the operation of .
12 - 4
12.1 Time Setting and Display
12.1.3 Clock setting operations
9
3
Touching the
OK
button reflects the settings and restarts updating the clock display.
Then, the settings are reflected to both clock data on the GOT and controller.
4
If touch button, the GOT restarts if the clock settings is changed, or the screen closes if clock settings is not changed.
If touch button without touching
OK button, the dialogue box shown on the left is displayed.
OK
button: The changed value is canceled, and the screen is closed.
Cancel
button: The time display and setting screen is displayed.
3
GOT internal battery voltage status
Displays battery voltage status.
Display
Normal
Low/None
Status
Normal
Low voltage
When the battery voltage is low, replace the battery immediately.
Refer to the following for battery replacement procedure.
10
11
12
13
14
15
16
12.1 Time Setting and Display
12.1.3 Clock setting operations
12 - 5
13. FILE DISPLAY AND COPY
(PROGRAM/DATA CONTROL)
The display of OS, project data or alarm data which is written in the GOT or CF card and the data transmission between GOT and CF card are possible.
The format of the CF card is also possible.
13.1 Data Storage Location
13.1.1 Drive name allocation
For the Built-in CF card, Flash Memory (Internal) or Internal SRAM, the following drive names (A drive, C drive and D drive) are allocated.
Drive name Allocation
A drive
C drive
D drive
Built-in CF card
Flash Memory (Internal)
Internal SRAM
13.1.2 Data type and storage location
1
At system startup
The data storage location and transferring (write/read) route for each data type are shown below.
GOT main unit
(D drive)
Internal SRAM
Install/
Download
BootOS
OS
Project data
BootOS
OS
Project data
(C drive)
Flash Memory (Internal)
Upload
BootOS
OS
Project data
(A drive)
BootOS
OS
Project data
Install/
Download
Upload
Project data
PC
GT Designer2
Open a file
Project data
Write
BootOS
OS
Project data
BootOS
OS
Project data
Inserting/Removing
Built-in CF card
(when installed in PC)
13 - 1
Built-in CF card
(when installed in GOT)
13.1 Data Storage Location
13.1.1 Drive name allocation
9
2
At maintenance
GOT main unit
10
(D drive)
Recipe
Internal SRAM
Copy
Alarm
Alarm
(A drive)
Alarm
Recipe
Alarm
Recipe
(C drive)
Flash Memory (Internal)
Built-in CF card
(when installed in GOT)
Upload
PC
GT Designer2
Alarm
Recipe
Upload
Copy files on Windows
Inserting/Removing
Alarm
Recipe
Built-in CF card
(when installed in PC)
The data of the Flash Memory (Project data, etc.) can be saved even if the battery voltage becomes low.
Data type Storage location
BootOS
OS
Project data
BootOS
Standard monitor OS
Communication driver
Extended function OS
Option OS
Project data
(Including recipe setting, alarm conditions, time action, and GOT setup.)
Flash Memory (C drive)
Flash Memory (C drive)
*1
Alarm
Alarm data (Alarm log file)
*1
Recipe
Recipe data
The project data can be started only from the flash memory (C drive).
It cannot be started from the built-in CF card (A drive).
Internal SRAM (D drive)
11
12
13
14
15
Folder and file in memory card
Multiple folders and files will be created when OS or project data is transferred to the memory card.
Do not delete or edit these folders and files since the GOT uses them.
If the folders or files are deleted or edited, the GOT will not function normally.
16
13.1 Data Storage Location
13.1.2 Data type and storage location
13 - 2
13.1.3 OS version confirmation
Confirm the OS version carefully when install BootOS and Standard monitor OS.
When OS is installed, GOT checks and compares the OS version automatically.
(1) When install BootOS
When the BootOS to be installed has the older major version, GOT displays the installation disapproving message to cancel the installation so that the older version may not be written.
(Even when the version of the BootOS to be installed has the same or later version, the version information and the dialog for selecting continue/not continue will be displayed.)
When installing from the standard CF card, the dialog is displayed by the main unit.
When installing from GT Designer2 via USB or RS-232, the dialog is displayed by the GT
Designer2.
(2) When install Standard monitor OS, communication driver, Option OS
When Standard monitor OS, communication driver, or Option OS has already been installed, the version information of the OS which has been installed and the dialog for selecting continue/not continue will be displayed.
Moreover, when the different versions will coexist among all OSs (Standard monitor OS, communication driver, and Option OS) by installing OS, the installation disapproving dialog will be displayed and the installation process is canceled.
(3) When download project data
GOT automatically compares the version between the project data to be downloaded and the installed OS.
When the versions are different, the dialog confirming whether to install the OS together is displayed.
When downloading the project data from the CF card, storing the project data and OS beforehand is recommended.
The version of each OS can be confirmed by [Property] of [OS information] screen.
Explanation of OS version
01.00.00A
BootOS version
Appears only when the property of the BootOS is displayed.
Minor version
Major version
Refer to the following for details of the screen display operation.
13 - 3
13.1 Data Storage Location
13.1.3 OS version confirmation
9
Version confirmation of BootOS by rating plate
Confirm the version of BootOS installed in the GOT at product shipment by rating plate of GOT rear face.
(a) GT1155-QSBD ,GT1150-QLBD
GRAPHIC OPERATION TERMINAL
MODEL
GT1155-QSBD
IN 20.4 26.4VDC POWER 9.84W MAX
SERIAL 540001 BC
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
JY550D26101A
80M1 IND. CONT. EQ
US LISTED
BC
BootOS version
(b) GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, GT1150-QLBDA
GRAPHIC OPERATION TERMINAL
MODEL GT1155-QTBDQ
IN 24VDC
POWER MAX 00W
SERIAL
00007201DP00001-A
MITSUBISHI ELECTRIC
MADE IN JAPAN
D P
BootOS version
10
11
12
13
14
15
16
13.1 Data Storage Location
13.1.3 OS version confirmation
13 - 4
13.1.4 Display file
The files that can be displayed in each screen are as follows.
Contents
Display screen
Storage location
(Drive name/folder name)
Built-in flash memory C:\G1BOOT\
*3
BootOS
Standard monitor OS system screen data
Standard monitor OS system screen management information file
Standard monitor OS (monitor function)
*1
Standard monitor OS
6 8-dot font (ASCII characters)
12-dot numerical HQ font
16-dot numerical HQ font
TrueType numerical font
12-dot standard font
16-dot standard font
Extended function OS
Option OS
Communication driver
Project data
*2
User-created screen data
Comment data
12-dot HQ fonts (Mincho/Gothic)
16-dot HQ fonts (Mincho/Gothic)
TrueType (Mincho/Gothic)
OS information screen
Project information screen
Built-in flash memory C:\G1SYS\
*3
Built-in flash memory C:\PROJECT1\
*3*4
Resource data
Advanced alarm log file CSV file
Alarm information screen
Standard CF card A:\
With GT Designer2, any folder name or file name can be specified.
*1 The 6
8 dot font, 12-dot numerical HQ font, 16-dot numerical HQ font are displayed as Standard monitor OS.
*2 The user-created screen data, comment data, and font data are displayed as project data.
*3 Each folder is created automatically at installation, download and upload of each file.
*4 The folder name and file name can be set at [System Setting] in [System Environment] of GT Designer2.
GT Designer2 Version Screen Design Manual
Section 3.1 GOT/PLC Type Setting
13 - 5
13.1 Data Storage Location
13.1.4 Display file
13.2 OS Information
9
13.2.1 Function of OS information
Each file name/folder name of BootOS and OS (Standard monitor OS, PC communication driver and Option
OS) by which each drive (A: Built-in CF card, C: Flash memory) holds can be displayed in lists.
Installation and uploading of the files are also possible.
Function Contents
Information display of files and folders Displays the kind, name, data size, creation date and time of the file or folder.
Install
All files written in the A drive (Built-in CF card) can be installed in the C drive (Flash memory).
Upload
Property display
All files in the C drive (Flash memory) can be uploaded to the A drive (Built-in CF card).
Displays the property (file name, data size, type, version and creation date) of the file.
Data check Data check of files is possible.
Reference page
10
11
Notes on installing OS
If the Boot OS or the Standard monitor OS is installed, such data on the GOT as the project data will be deleted.
After installing the Boot OS or the Standard monitor OS, reinstall/download necessary data.
12
13
14
15
16
13.2 OS Information
13.2.1 Function of OS information
13 - 6
13.2.2 Display operation of OS information screen
Main menu
( Section 9.3 Utility Display)
Program/data control
Touch
[OS information].
Touch
[Program/data control].
OS information
Select a drive and operate BootOS and
OS files.
13 - 7
13.2 OS Information
13.2.2 Display operation of OS information screen
13.2.3 Display example of OS information
OS information screen
OS information screen: Storage file/folder display screen
9
10
(2) (3)
(4)
(7)
(5)
(8)
(6)
(9)
(1)
Number
(1)
Item
Select drive
(2) Kind
(3) Name
(4)
(5)
(6)
(7)
(8)
(9)
Path name
Size
Date and time
The size of drive
Operation switch
Number of files
11
Contents
The drive of which file or folder is displayed can be selected. When the CF card is not installed, [A: Built-in CF card] will not be displayed.
Indicates whether the displayed name is for file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
The file name or folder name which is stored in the selected drive or folder is displayed.
When the file name or folder name exceeds 20 characters, the exceeding characters (the 21th character or after) are not displayed.
The path name of the currently displayed drive/folder is displayed.
Displays the size of the file displayed in Name.
The date and time when each file was installed are displayed.
Displays the size in use size of the drive which is selected by drive selection.
Execution switch of each function (install, upload, etc.) which can be executed on the OS information screen.
Displays the total number of the displayed files.
12
13
14
Remark
Displayed folders and files
Refer to the following for the details of displayed folders and files.
15
16
13.2 OS Information
13.2.3 Display example of OS information
13 - 8
13.2.4 Operation of OS information
1
Display operation of OS information
OS information screen
OS information screen: Storage file/folder display screen
1
If touch a drive in [Select drive], the information of the first folder of the touched drive is displayed.
2
If touch a folder name, the information of the touched folder is displayed.
3
If touch a folder name of [ . . ], the information of the folder in one higher hierarchy is displayed.
4
If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5
If touch a file name, the touched file name is selected and inverted.
6
Refer to the following for operation of installation, upload, property, data check.
Installation...............
Upload.....................
Property ..................
Data check ..............
7
Touching button closes the screen.
13 - 9
13.2 OS Information
13.2.4 Operation of OS information
9
2
Installation operation
BootOS and OS which are written in the A drive (Built-in CF card) can be installed in GOT.
OS information screen
1
Install the CF card to which the BootOS or
OS to install is written to the GOT.
Refer to the following for inserting/ removing method of CF card.
2
Touch [A: Built-in CF Card] for drive selection.
3
Touching
Install
button starts the install.
2
10
11
12
OS information screen: Storage file/folder display screen
13
3
14
4
When the installation is completed, the dialog shown left is displayed.
GOT restarts if touch
OK
button.
15
16
13.2 OS Information
13.2.4 Operation of OS information
13 - 10
3
Upload operation
BootOS and OS in the C drive (Flash memory) can be uploaded to the A drive (Built-in CF card).
OS information screen
1
Install the CF card used as the uploading destination to GOT. Refer to the following for inserting/removing method of CF card.
2
Touch [A: Built-in CF Card] of [Select drive].
3
Touching
Upload
starts the uploading.
2
OS information screen: Storage file/folder display screen
3
4
When the upload is completed, the dialog shown left is displayed.
Touching
OK
closes the dialog.
13 - 11
13.2 OS Information
13.2.4 Operation of OS information
9
4
Property display operation
Displays the property of the file stored in the selected folder.
1
If touch
Property
button after selecting the property displaying target folder, the
[Property] screen shown left is displayed.
In the [Property] screen, the following information is displayed for each file selected by .
Item
Name
Kind
Version
Date, Time
Size
Contents
Displays the file name.
Displays the following items according to the file type.
Boot
Standard
: BootOS
: Standard monitor OS
Communication : Communication driver
Option : Option OS
Extend : Extended function OS
Displays the version of BootOS and
OS.
Displays the date and time of the file creation.
Displays the file size.
2
If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
3
Touching button returns the screen to the previous screen display.
10
11
12
13
14
15
16
13.2 OS Information
13.2.4 Operation of OS information
13 - 12
5
Data check operation
Carries out data check of the selected system file.
When data is normal.
When data is erroneous.
1
Touch
Data check
button after selecting a data check target file.
The dialog mentioned left will be displayed after executing data check.
2
Touching
OK
button closes the dialog.
3
If the data check fails, the target file may be broken.
Install the target file again.
4
For details of installation, refer to the following.
13 - 13
13.2 OS Information
13.2.4 Operation of OS information
13.3 Project Information
13.3.1 Function of project information
The project data files stored in each drive (A: Built-in CF card, C: Flash memory) can be displayed by lists.
In addition, the files can be downloaded, uploaded, deleted or copied, etc.
Contents Reference page Function
Information display of files and folders
Delete
Copy
Property display
Data check
Download
Upload
Displays the kind, name, data size, the creation date and time of the file or folder.
Deletes project data.
Copies project data. (Enabled to copy only from the A drive to the A drive)
Displays the project data creation date, author name and the version of GT Designer2. 13-19
Data check of the file can be executed.
Downloads the project data written in the A drive (Built-in CF card) to C drive (Flash memory).
Uploads the project data written in the C drive (Flash memory) to the A drive (Built-in
CF card).
9
10
11
12
13.3.2 Display operation of project information
Main menu
( Section 9.3 Utility Display)
Program/Data control
13
Touch
[Program/data control].
Touch
[Project information].
Project information
14
Select the drive and operate project data file.
15
16
13.3 Project Information
13.3.1 Function of project information
13 - 14
13.3.3 Display example of project information
Project information screen
Project information screen:
Storage file/folder display screen
(2)
(7)
(3) (4) (5)
(8)
(6)
(9)
Number
(1)
(2)
(3)
(1)
Select drive
Kind
Name
Item
(4)
(5)
(6)
(7)
(8)
(9)
Path name
Size
Date and time
Size of the drive
Operation switch
Number of files
Contents
The drive by which a file or folder is displayed can be selected.
When the CF card is not connected, [A: Built-in CF card] is not displayed.
Indicates the type of the displayed name (file or folder).
The file is indicated with an extension, while the folder is indicated with "DIR."
Displays the name of file or folder saved in the selected drive or contained in the selected folder.
When the file or folder name exceeds 18 characters, the 19th and later characters are not displayed.
If the displayed project data is a GOT monitoring target file, "%" mark precedes the file name.
If the displayed project data is currently selected to be displayed, asterisk "*" precedes the file name.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in [Name].
Displays the date and time when each file is installed.
Displays the size in use size of the drive selected in [Select drive].
Displays the execution switch of functions (download, upload, etc.) which can be carried out in [Project information].
Displays the total number of the displayed files.
Remark
Displayed folders and files
Refer to the following for the details of displayed folders and files.
13 - 15
13.3 Project Information
13.3.3 Display example of project information
13.3.4 Operation of project information
9
1
Display operation of project information
Project information screen
Project information screen: Storage file/folder display screen
1
Touch a drive in [Select drive], and the data in the first folder contained in the touched drive is displayed.
2
If touch a folder name, the data contained in the touched folder is displayed.
3
If touch the folder with name [ . . ], the data in the one-higher hierarchy folder is displayed.
4
Touching the button in the scroll bar scrolls up or down by 1 line.
Touching the down by 1 screen.
button scrolls up or
5
If touch a file name, the file is selected and the file name is highlighted.
6
Refer to the following for operation of delete, copy, property, data check, download, upload.
Delete .....................
Copy .......................
Property ..................
Data check ..............
Download................
Upload ....................
7
Touching button closes the screen.
10
11
12
13
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13 - 16
2
Delete operation
This operation deletes the selected file.
1
Touch and select the file to delete.
2
Screen mentioned left is displayed if
Del button is touched.
Confirm the deletion targeted file is specified correctly.
If touch
OK
button, the file is deleted.
If touch
Cancel
button, the deletion is canceled.
3
When the deletion completes, the dialog box shown left is displayed.
If touch
OK
button, the dialog is closed.
13 - 17
13.3 Project Information
13.3.4 Operation of project information
9
3
Copy operation
The file in the A drive is copied to another directory of the A drive.
Copy to/from C drive or D drive is disabled.
Dialog for selecting a copy destination drive
Dialog for selecting a copy destination folder
1
Install CF card in the PC, in which create a folder for the copy destination.
Set the same character with [System
Setting] of [System Environment] of GT
Designer2 for the folder name.
GT Designer2 Version Screen
Design Manual
(Section 3.1 GOT/PLC Type Setting)
2
Install the CF card mentioned above to
GOT.
Refer to the following for inserting/ removing method of CF card.
3
Open [Project information] and touch the drive of the file to be copied to select the drive, and then touch the
Next
button.
The dialog for selecting a copy destination folder as shown left is displayed.
10
11
12
13
4
Touch the folder display area to select a folder, and then touch the
Exec.
button.
The dialog shown left is displayed.
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13 - 18
5
Touch
If there is no file of the same name in the copy destination folder, starts to copy.
When there is a file of the same name in the copy destination folder, the dialog mentioned left is displayed without starting the copy.
If copy, in this case, the copied file is overwritten to the project data in the copy destination folder.
If touch
OK
button, starts to copy.
If touch
Cancel
button, cancels to copy.
6
When copying completes, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
4
Property display operation
Displays the property of the project data in the selected folder.
1
If touch
Property
button after selecting the project data to display the property, the property is displayed as shown left.
In property display, the following information is displayed.
Item
Date
Author
Drawing
S/W version
Contents
Displays the creation date of the file.
Displays the author of the project data.
Displays name and version of the drawing software by which the project data is created.
2
If touch button, the screen scrolls up/down line by line.
3
If touch button, the screen scrolls up/down by one screen.
4
If touch button, the property display is closed and returned to the previous screen.
13 - 19
13.3 Project Information
13.3.4 Operation of project information
9
5
Data check operation
Carrys out data check of the selected project file.
When data is normal.
1
Touch the
Data check
button after selecting the file for data check.
The data check is executed and the result is displayed by the dialog shown left.
2
If touch
OK
button, the dialog is closed.
10
When data is erroneous.
3
If [Data error] is displayed, the target file may be broken.
Download the target file again.
11
12
13
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13 - 20
6
Download
Transfers the project data from the A drive (Built-in CF card) to the C drive (Flash Memory).
1
Transfer the project data to be downloaded to the GOT to the CF card, using GT
Designer2 or another GOT.
2
Install the CF card mentioned by to
GOT. Refer to the following for inserting/ removing method of CF card.
3
Touch [A: Built-in CF card] in [Select drive].
4
If touching
Download
button, the screen mentioned left is displayed.
If touching executed.
OK
button, the download is
13 - 21
13.3 Project Information
13.3.4 Operation of project information
5
Touch
OK
button. If there is no project data of the same name in the C drive, starts the download.
If there is a project data of the same name in the C drive, the screen shown left is displayed without starting the download.
If touching
OK
button, an overwrite download is executed to a project data of the same name.
If touching
Cancel downloading.
button, cancels the
6
When the downloading is completed, the completion dialog mentioned left is displayed.
GOT is restarted if
OK
button is touched.
9
10
11
12
13
14
15
16
13.3 Project Information
13.3.4 Operation of project information
13 - 22
7
Upload
Transfers the project data from the C drive (Flash Memory) to the A drive (Built-in CF card).
1
Mount the CF card to GOT.
For the CF card installation/removal method, refer to the following.
2
Touch "A: Standard CF card" in the drive selection.
3
If touching
Upload
button, the screen shown on the left is displayed.
4
If touching executed.
OK
button, the upload is
5
If there is a project data of the same name in the A drive, the screen shown on the left is displayed without starting the upload.
If touching
OK
button, an overwrite upload is executed to the project data of the same name.
If touching
Cancel canceled.
button, the upload is
6
When the upload is completed, the dialogue box shown on the left is displayed.
If touching closed.
OK
button, the dialogue box is
13 - 23
13.3 Project Information
13.3.4 Operation of project information
13.4 Alarm Information
13.4.1 Function of alarm information
The alarm log file held by the D drive (Internal SRAM) is displayed.
The functions below can be carried out for files.
Contents Function
Information display of files and folders
Deletion
Copy
Displays name, data size, creation date and time of file or folder.
Deletes file.
Copys file.
13.4.2 The display operation of alarm information
Main menu
( Section 9.3 Utility Display)
Program/Data control
Touch
[Alarm information].
Touch
[Program/data control].
Alarm information
9
Reference page
10
11
12
13
Select a drive and operate alarm log file.
14
15
16
13.4 Alarm Information
13.4.1 Function of alarm information
13 - 24
13.4.3 The display example of alarm information
Alarm information screen Alarm information: Storage file/folder display screen
(2) (3)
(7)
(4)
(8)
(5) (6)
(9)
(1)
Number
(1)
Item
Select drive
(2) Kind
(3) Name
(4)
(5)
(6)
(7)
(8)
(9)
Path name
Size
Date and time
Drive size
Operation switch
Number of files
Contents
The drive of which file or folder is displayed can be selected. When the CF card is not installed, [A: Built-in CF card] is not displayed.
Indicates whether the displayed name is file or folder.
In case of file, displays the extension; in case of folder, displays "DIR".
Displays the file name or folder name held by the selected drive or folder.
When the file name or folder name exceeds 20 characters, the exceeding characters (the 21th character and after) are not displayed.
Displays the path name of drive/folder which is currently displayed.
Displays the size of the file displayed in Name.
Displays the date and time when each file has been created.
Displays the size in use and the entire size of the drive selected by "Select drive".
Displays the execution switch of each function (Delete, copy) which can be executed on the alarm information screen.
Displays the total number of the displayed files.
Display of creation date and time
The creation date and time display is not updated even if a file is created or updated while displaying the alarm information display screen.
If close the screen currently displayed (moving the screen to the folder of the upper hierarchy, etc.) and display the screen again, the updated contents are displayed.
Remark
Folders and files displayed
Refer to the following for the details of folders and files displayed.
13 - 25
13.4 Alarm Information
13.4.3 The display example of alarm information
13.4.4 Alarm information operation
9
1
The display operation of alarm information
Alarm information screen
Alarm information: Storage file/folder display screen
1
If touch a drive of [Select drive], the information in the first folder of the touched drive is displayed.
2
If touch a folder name, the information of the touched folder is displayed.
3
If touch a folder of [ . . ], the information of the folder of the one upper hierarchy is displayed.
4
If touch button of the scrollbar, the screen scrolls up/down by one line.
If touch button, the screen scrolls up/down by one screen.
5
If touch a file name, the touched file name is selected and inverted.
6
Refer to the following for delete, copy, operations.
Delete .....................
Copy .......................
7
If touch button, the screen is closed.
10
11
12
13
14
15
16
13.4 Alarm Information
13.4.4 Alarm information operation
13 - 26
2
Deletion operation
Deletes selected files.
1
Touch and select the file to delete.
2
If touch
Del
button, the dialog mentioned left is displayed.
Confirm deletion targeted file is specified correctly.
If touch
If touch canceled.
OK
button, the file is deleted.
Cancel
button, the deletion is
3
When the deletion is completed, the completion dialog is displayed.
If touch
OK
button, the dialog is closed.
13 - 27
13.4 Alarm Information
13.4.4 Alarm information operation
3
Copy operation
Copies the selected file.
Dialog for selecting a copy destination drive
Dialog for selecting a copy destination folder
9
1
Touch and select the file to copy.
2
If touch
Copy
button, the message
[Please select a destination.] is displayed in the left bottom of the screen.
3
Touch the drive name display area to select a drive, and then touch the
Next
button.
The dialog for selecting a copy destination folder is displayed as shown left.
10
11
12
13
4
Touch the folder display area to select a folder, and then touch the
Exec.
button.
The confirmation dialog shown left is displayed.
14
15
16
13.4 Alarm Information
13.4.4 Alarm information operation
13 - 28
13 - 29
13.4 Alarm Information
13.4.4 Alarm information operation
5
Touch
If there is no file of the same name in the copy destination folder, starts to copy.
If there is a file of the same name in the copy destination folder, the following dialog is displayed without starting the copy.
If copy, in this case, the copied file is overwritten to the project data in the copy destination folder.
If touch
If touch
OK
button, starts to copy.
Cancel
button, cancels to copy.
6
When the copy is completed, the dialog of completion is displayed.
If touch
OK
button, closes the dialog.
13.5 Memory Card Format
13.5.1 Format function of memory card
Formats the CF card or Internal SRAM.
13.5.2 Display operation of memory card format
Main menu
( Section 9.3 Utility Display)
Program/Data control Program/Data control
Touch
[Program/data control].
Touch
[Memory card format].
Touch [ ].
Memory card format
9
10
11
12
Select a drive and format it.
13
14
Formatting the D drive (Internal SRAM)
If the GOT is turned off and left in the status without a battery for 30s or longer, the data in the D drive (Internal SRAM) becomes indefinite, possibly disabling data writing. If the GOT is left in the status without a battery for 30s or longer, format the
D drive (Internal SRAM).
15
16
13.5 Memory Card Format
13.5.1 Format function of memory card
13 - 30
13.5.3 Format operation of memory card
1
To format the CF card, install the CF card to the GOT first.
For the CF card installation/removal method, refer to the following.
2
Touch and select the drive to format by
[Select Drive].
3
If touch
Format
button, the password input screen is displayed.
4
Type [1][1][1][1] and touch the
Enter
The dialog box shown on the left will
key. appear. (The password is fixed to 1111.)
Confirm the contents of the dialog.
When execute the CF card format, touch
OK
button.
When cancel the CF card format, touch
Cancel
button.
5
If touch
OK
button by , the dialog mentioned left is displayed for reconfirm.
6
Reconfirm whether to format the CF card.
If touch
OK
button, starts formatting.
If touch
Cancel
button, cancels formatting.
13 - 31
13.5 Memory Card Format
13.5.3 Format operation of memory card
7
When the formatting is completed, the completion dialog mentioned left is displayed.
8
If touch
OK
button, closes the dialog.
9
10
Remark
Restrictions on formatting
• When use an unformatted CF card in GOT, format the CF card by PC.
GOT cannot format the unformatted CF card.
• The formatting of GOT does not change the file system (Example: FAT16) of the CF card and inherits the file system before formatting.
13.6 Memory Information
11
12
13.6.1 Memory information function
The following shows the amount of the memory empty area size and boot Drive information empty area size which can be used by the user of each drive (A: Standard CF card, C: Built-in Flash Memory).
13.6.2 Memory information display operation
Main menu
( Section 9.3 Utility Display)
Program/data control
13
14
Touch
"Program/data control"
Touch
"Memory information"
Touch " "
Memory information
15
Select a drive and then format it.
16
13.6 Memory Information
13.6.1 Memory information function
13 - 32
13.6.3 Display example of memory information
(1)
No.
Setting items
(1) Flash memory empty area size
Description
Indicates the amount of memory empty area size for each drive in which a file or folder can be stored.
If CF card is not mounted, "A: Standard CF card" is not displayed.
13 - 33
13.6 Memory Information
13.6.3 Display example of memory information
13.7 GOT data package acquisition
9
13.7.1 The function of GOT data package acquisition
This function copies the following OSs that are installed on the GOT and the data to the memory card.
• OS (Boot OS, Standard monitor OS, Communication OS, Extended function OS, Option OS)
• Project data
Copied data can be used as a backup, or they can be installed on another GOT to create a GOT that has the same configuration.
Refer to the following section for the Installation function of the GOT.
Section 16.3 BootOS and Standard Monitor OS Installation Using CF Card
10
13.7.2 Operating the GOT data package acquisition function
11
Main menu
( Section 9.3 Utility Display)
Touch the
"Program/data control."
Program/data control
12
Touch " ."
GOT data package acquisition
Touch the "GOT data package acquisition."
13
14
15
16
13.7 GOT data package acquisition
13.7.1 The function of GOT data package acquisition
13 - 34
13.7.3 Display example of GOT data package acquisition
(1)
(2)
No.
(1) Drive selection
Setting items
(2) Copy
Description
Displays the drive to which the user can copy the OS and data.
[A: Standard CF Card] will not appear if a CF card is not inserted.
Copying begins when [Copy] is touched.
13 - 35
13.7 GOT data package acquisition
13.7.3 Display example of GOT data package acquisition
13.7.4 GOT data package acquisition operation
9
1
GOT data package acquisition operation on the display
Copy the following OS that is installed on the GOT and data to the CF card.
1
Touch [A: Standard CF Card] under Select drive to highlight it.
Touch the
Copy
button to begin copying.
10
11
2
Different dialogs appear, depending on the status of the copying destination. Follow the dialog that appears.
12
13
3
Upon completion of OS/Data copying, a dialog that indicates a completion of copying will appear.
Touch the
OK
button to close the dialog window.
14
15
16
13.7 GOT data package acquisition
13.7.4 GOT data package acquisition operation
13 - 36
2
Notes on copying operations
(1) Copying the OS/Project data to the GOT
When the OS or project data are copied to the memory card using the GOT data package acquisition function and then to the GOT, the utility settings will also be copied.
After copying the OS and project data to the GOT, check the utility settings and reconfigure the settings as necessary.
(2) Storage of other data on the CF card
When using the GOT data package acquisition function, do not store any other data to the memory card.
Other data on the memory card will become unusable.
13 - 37
13.7 GOT data package acquisition
13.7.4 GOT data package acquisition operation
14. GOT SELF CHECK (DEBUG & SELF CHECK)
The GOT can display the screen for debugging or self-checking.
The following describes the functions available as the debugging and self-checking function.
Items
Debug
Self check
System alarm display
GOT start time
Contents
System monitor, A list editor and FX list editor
Reference page
Memory check, Drawing check, Font check, Touch panel check and I/O check
GOT errors, CPU errors
Time when the GOT was started
14.1 Debug
This manual covers only an outline of the debugging function and operations until displaying the screen.
For display contents of each debugging function and operation method, refer to the following manual.
GOT1000 Series Extended/Option Functions Manual
14.1.1 Debug functions
The debug function includes functions for the PLC system status check and those for increasing the efficiency in troubleshooting.
The following items can be realized with the debug function.
Items
System monitor
A list editor
FX list editor
Contents
The device of PLC CPU or buffer memory of the intelligent function module can be monitored and tested.
The sequence program of ACPU can be list edited.
The sequence program of FX PLC can be list edited.
9
10
11
12
13
14
15
16
14.1 Debug
14.1.1 Debug functions
14 - 1
14.1.2 Display operation of debug
Main menu
( Section 9.3 Utility Display)
Debug & self check
Touch [Debug].
Touch [Debug & self check].
Display Debug
(Example of system monitor)
Debug
Self check
Touch a debug function to operate.
14 - 2
14.1 Debug
14.1.2 Display operation of debug
14.2 Self Check
14.2.1 Self check function
Carries out self-check for the GOT hardware or memory etc.
The items that can be self-checked are as follows.
Items
Memory check
Drawing Check
Font check
Touch panel Check
I/O check
Contents
Carries out write/read check of the Built-in CF card, Flash memory, and Internal
SRAM.
Password: "5920" (fixed)
Carries out missing bit check, color check and drawing check.
Displays the character data on the screen to check visually.
Checks whether there are no dead zone area in the Touch key minimum unit
(16 dots x 16 dots).
Carries out RS-422 and RS-232 connecting target confirmation (CPU communication check) and the RS-232 self-loopback check (hardware check of the RS-232 interface).
Reference page
9
10
11
12
15
16
13
14
14.2 Self Check
14.2.1 Self check function
14 - 3
14.3 Memory Check
14.3.1 Memory check function
The memory check function carries out the write/read check of the Standard CF card, Flash memory, and
Internal SRAM.
Function
A drive memory check
C drive memory check
D drive memory check
Contents
Checks whether the memory (Standard CF card) of the A drive can be read/written normally.
Checks whether the memory (Flash memory) of the C drive can be read/written normally.
Checks whether the memory (Internal SRAM) of the D drive can be read/written normally.
14.3.2 Display operation of memory check
Main menu
( Section 9.3 Utility Display)
Debug & self check Self check
Touch
[Memory check].
Touch [Self check].
Touch [Debug & self check].
Memory check
Select the memory to check and touch [Check].
14 - 4
14.3 Memory Check
14.3.1 Memory check function
14.3.3 Memory check operation
Carries out write/read check of memory.
9
When drive is not displayed
When the drive (memory) to check is not displayed, confirm the mounting procedure or memory type with reference to the following.
• CF card inserting/removing method
When no faults are found in mounting, etc, a memory failure may be arisen.
Replace the CF card or Flash memory (C drive).
For details of Flash memory, contact your nearest sales office or FA Center.
The following example explains about Memory Check using Flash memory (C drive).
For the standard CF card (A drive) memory check, install the CF card before carrying out the same key operations as Flash memory.
10
11
1
Select [Flash Memory] in the [Memory check] setting screen, and touch the
Check
button.
If select the
OK
button, the numeric keyboard window is displayed.
If select the
Cancel to the initial menu.
button, the screen returns
12
13
2
Touch
5 9 2 0
and then
Enter
3
(The password is fixed to 5920.)
.
4
Touching
Enter
executes read/write check for the flash memory.
14
15
16
14.3 Memory Check
14.3.3 Memory check operation
14 - 5
5
Touching the
OK
button returns to the
[Memory check] screen.
Remark
Password change
The password cannot be changed.
When input password error, the cancel dialog is displayed.
If touch
OK
, returns to the
[Memory check] screen.
14 - 6
14.3 Memory Check
14.3.3 Memory check operation
9
When error is found in the memory
When error is found by memory check, the dialog indicating the area in which the error occurred is displayed.
If an error is found in the D drive [Internal SRAM], format the internal SRAM.
For details of the formatting of the D drive [Internal SRAM], refer to the following.
Section 13.5 Memory Card Format
If an error is found in the C drive [Flash memory] or the D drive [Internal SRAM] right after formatting, contact your nearest sales office or FA Center.
10
If touch
OK
, the screen returns to the [Memory check] screen.
11
12
13
14
15
16
14.3 Memory Check
14.3.3 Memory check operation
14 - 7
14.4 Drawing Check
14.4.1 Drawing check function
The drawing check function carries out display checks as missing bit check, color check, basic figure display check, move check among screens.
14.4.2 Display operation of drawing check
Main menu
( Section 9.3 Utility Display)
Debug & self check Self check
Touch [Self check].
Touch
[Display check].
Touch [Debug & self check].
Display check
Touch
[Drawing check].
Starting drawing check
Touching [Drawing check] in the
Display check displays the screen describing the drawing check operation.
Touch the upper right of the description screen to start a drawing check.
14 - 8
Notes on drawing check
Missing bits is occurred in the following cases.
1. There are parts drawn in different color with the filled color.
2. There are parts of basic figure and drawing patterns which are not drawn
When missing bits occurs, contact your nearest sales office or FA Center.
Bright dots (always lit) and dark dots (unlit) may appear on a liquid crystal display panel. It is impossible to completely avoid this symptom, as the liquid crystal display comprises of a great number of display elements.
A flicker may be caused in some display colors. This is a characteristic of the LCD panel; it is not due to a fault or failure of the product.
14.4 Drawing Check
14.4.1 Drawing check function
14.4.3 Display and operation of drawing check
9
Touching [Drawing check] in the [Display check] displays the screen describing the drawing check operation.
Touch the upper right of the screen to start a drawing check.
1
Before execute drawing check
Upper-left touch position
Upper-right touch position
(1) Touching the upper right part of the screen proceeds to the next check in each step during the drawing check. Touching the upper left part of the screen returns to the [Display check] screen.
(2) For GT1155 (256 colors), color display (blue, black, red, purple, green, light blue, yellow and white) is available.
For GT1150 (monochrome 16 scales), the colors are reduced to the 16-scale monochrome.
This section describes with an example using
GT1155 (256 colors).
10
11
12
1
Missing bit, Color Check
By touching the upper-right part of the screen, the entire screen color changes in the following order: blue black red purple green light blue yellow white.
Check missing bit and color visually.
13
Blue Black Red Purple Green Light blue Yellow White
To Basic figure check screen
If touch the upper right part of the screen at the final color (white screen), the following Basic figure check screen is displayed.
14
15
16
14.4 Drawing Check
14.4.3 Display and operation of drawing check
14 - 9
2
Basic figure check
Check whether there is no shape transformation of basic figure or display losses.
The basic figure drawn has 4 types: 1. Filled circle, 2. Line, 3. Rectangle, 4. Ellipse.
To (a) Pattern 1 of
Move check among screens
14 - 10
14.4 Drawing Check
14.4.3 Display and operation of drawing check
9
3
Move check among screens
(a) Pattern 1: Shape transformation, color check
The drawn figures are displayed in order and at regular intervals.
If the shape and color (white, yellow, light blue, green, purple, red, blue, black) are displayed visually in order, it is normal.
For GT1150 (monochrome 16 scales), each color is subtracted to monochrome 16-scale.
10
To Pattern 2
11
12
Pattern 1
(b) Pattern 2: Shape transformation, color check
The drawn figures are displayed in order and at regular intervals.
If the shape and color (white, yellow, light blue, green, purple, red, blue, black) are displayed visually in order, it is normal.
For GT1150 (monochrome 16 scales), each color is subtracted to monochrome 16-scale.
13
To Pattern 3
14
Pattern 2
15
16
14.4 Drawing Check
14.4.3 Display and operation of drawing check
14 - 11
(c) Pattern 3: Shape transformation, color check
The overlaped shapes of pattern 1 and pattern 2 are displayed.
If the shape and color (white, yellow, light blue, green, purple, red, blue, black) are displayed visually in order, it is normal.
For GT1150 (monochrome 16 scales), each color is subtracted to monochrome 16-scale.
To Pattern 4
(d) Pattern 4: Shape Check
The drawn figures are displayed in order and at regular intervals.
If the shape and color are displayed visually in order, it is normal.
If touch the upper right part of the screen, returns to [Display check] screen.
To [Display check]
14 - 12
14.4 Drawing Check
14.4.3 Display and operation of drawing check
14.5 Font Check
9
14.5.1 Font check function
The font check is a function which confirms fonts installed in GOT. The character data of the font is displayed on the upper left part of the screen one by one.
14.5.2 Display operation of font check
10
Main menu
( Section 9.3 Utility Display)
Debug & self check Self check
11
Touch [Self check].
Touch
[Display clock].
Touch
[Debug & self check].
12
Display check
Touch [Font check].
Starting font check
Touch [Font check] in the Display check to display the screen describing the font check operation. Touch the upper right of the description screen to start the font check.
13
14
Notes on font check
Judged as normal if the following characters are correctly displayed. (UNICODE)
Alphabetic & etc.
: 0 x 0000 to 0 x 04F9 (From basic Latin to Krill)
Hangul
Chinese Characters
: 0 x AC00 to 0 x D7A3 (Hangul / Hangul auxiliary)
: 0 x 4E00 to 0 x 9FA5 (CJK integrated Kanjis)
If the characters above are not displayed correctly, the fonts may not be normally installed.
Install the Standard monitor OS again.
15
16
14.5 Font Check
14.5.1 Font check function
14 - 13
14.5.3 Font check operation
Touching [Font check] in the [Display check] menu displays the screen describing the font check operation.
Touching the upper right of the screen starts the font check.
The character data of the installed font (stored in the flash memory) can be displayed on the screen one by one to confirm the font drawings visually.
1
Before execute font check
Upper-left touch position
Upper-right touch position
Touching the upper right part of the screen proceeds to the next check in each step during
Font check.
Touching the upper left part of the screen returns to the [Display check] screen.
The installed font data is displayed by touching the upper right part of the screen.
Font data
14 - 14
14.5 Font Check
14.5.3 Font check operation
14.6 Touch Panel Check
9
14.6.1 Touch panel check function
Touch panel check is a function which checks whether there is no dead zone area in touch key minimum unit
(16 dots x 16 dots).
14.6.2 Display operation of touch panel check
10
Main menu
( Section 9.3 Utility Display)
Debug & self check Self check
11
Touch [Self check].
Touch
[Touch panel check].
Touch [Debug & Self check].
12
Starting the touch panel check
Touching [Touch panel check] in the [Self check] displays the screen describing the touch panel check operation. start the touch panel check.
13
14
Notes on Touch panel check
If the touched part is not filled with yellow color, there are the following two possible causes.
1. Display part failure
2. Touch panel failure
In that case, contact your nearest sales office or FA Center.
15
16
14.6 Touch Panel Check
14.6.1 Touch panel check function
14 - 15
14.6.3 Touch panel check operations
Touching [Touch panel check] of [Self check] displays the screen explaining the touch panel check operation.
Touch the
OK
button to start the touch panel check.
1
Touch a part of the screen.
The touched part becomes a yellow
*1
-filled display.
If not displayed in yellow even when touched, the display part may be faulty. In this case, contact your nearest sales office or FA Center.
*1: For a monochrome 16-scale GOT, the part is displayed with a subtracted yellow color.
Black-filled screen
Yellow
2
If touch the upper left part, returns to the [Selfcheck] screen.
Upper-left touch position
Remark
Checking the upper left part of the screen
Only the upper left part of the screen cannot be filled with yellow.
*1
If returnes to the [Self check] screen by touching the upper left part, judge that the upper left area operates normally.
*1: For a monochrome 16-scale GOT, the part is displayed with a subtracted yellow color.
14 - 16
14.6 Touch Panel Check
14.6.3 Touch panel check operations
14.7 I/O Check
9
14.7.1 I/O check function
The I/O check is a function which checks whether GOT and PLC can communicate with each other.
If I/O check ends normally, the communication interface and the connection cable hardwares are normal.
To execute I/O check, the PLC communication driver has to be installed in GOT in advance from GT
Designer2.
Refer to the following for the details related to the installation of the PLC communication driver.
GT Designer2 Version Basic Operation/Data Transfer Manual
Chapter 8 TRANSFERRING DATA
10
I/O check function
Controllers except MITSUBISHI PLC cannot be checked with the use of I/O check function.
When checking the communication between GOT and controller, follow "Preparatory
Procedures for Monitoring" in "GOT 1000 Series Connection Manual".
GOT 1000 Series Connection Manual.
14.7.2 Display operation of I/O check
11
12
Main menu
( Section 9.3 Utility Display)
Debug & self check Self check
13
Touch [Self check].
Touch [I/O check].
Touch [Debug & self check].
14
I/O check
GT1155-QSBD ,GT1150-QLBD
15
16
14.7 I/O Check
14.7.1 I/O check function
14 - 17
14.7.3 I/O check operation
1
Target confirmation
1
As a preparatory step for the CPU communication check, perform the following items.
• Installing [Communication driver]: Use GT
Designer2 to install.
• Setting [Communication settings]: Use GT
Designer2 to enter and download.
• Connecting connection device: Connect a PLC to the communication interface for which the CPU communication check is applied in order to start the communication.
(Check for the power is on or if any error occurred.)
2
If touch the
CPU
button, the CPU communication check is carried out.
3
After the CPU communication starts normally, the dialog mentioned left notifying that it is on checking, until the CPU communication check ends normally.
4
When the CPU communication check ends, its result is notified by dialog.
If the CPU communication check ends normally, the dialog notifying of the normal termination mentioned left is displayed. If touch the button in the dialog after confirming the result, returns to I/O check.
If the dialog mentioned left is displayed after selecting
CPU
or during CPU communication check, confirm the following.
• No misconnection with CPU
( GOT1000 Series Connection Manual)
• No hardware error
( GOT1000 Series Connection Manual)
• No missettings of parameter
(
Section 10.2 Communication Detail Settings)
If touch the
OK
button in the dialog after confirming the result, returns to I/O check.
14 - 18
14.7 I/O Check
14.7.3 I/O check operation
2
Self-loopback
4 3 2
Display unit (back)
RS-232
8 7 6
ON
CF CARD
CF CARD
(FG)
INPUT
24V DC
+
RS-422
BATTERY
I/F
RESET
9
1
For preparation for the self-loopback communication check, insert the connector for self-loopback check
(Customer purchased) shown in the diagram left in the RS-232 interface.
For this connector, short 2 and 3 pins, 7 and 8 pins, 4 and 6 pins, respectively.
2
If touch the
Self
button, the hardware check for the
RS-232 interface is carried out.
10
11
3
After selecting
Self
, the transferred data and received data are verified through the self-loopback connector. If data can not be received during data transmission, the dialog shown left is displayed, which notifies the self-loopback connector failure, self-loopback connector communication error or RS-
232 interface hardware failure.
12
4
During check, the dialog shown left is displayed.
13
5
When all checks end normally, the dialog shown left is displayed, and the GOT restarts.
14
15
6
If an error occurs the dialog is displayed at that point, notifying the GOT has terminated abnormally and which byte the error occurred, and then the GOT restarts.
If a verification error occurs, the RS-232 interface hardware may be faulty.
16
14.7 I/O Check
14.7.3 I/O check operation
14 - 19
14.8 System Alarm Display
14.8.1 System alarm display function
System alarm display is the function to display error code and error message when an error occurs in GOT, controller or network.
System alarms can be reset on the System alarm display screen.
For details of system alarm, refer to the following manual.
GT Designer2 Version Screen Design Manual (8. ALARM)
14.8.2 Displaying the system alarm display
(
Main menu
[Debug & self check]
Touch [System alarm display].
Touch [Debug & self check].
System alarm display
When touching Reset , the system alarm display on the
GOT is reset.
14 - 20
14.8 System Alarm Display
14.8.1 System alarm display function
14.8.3 Operating the system alarm display
1
System Alarm display resetting
9
1
Eliminate each cause of the system alarm being occurred.
Error causes can be identified by the error code, error message and channel No. displayed on the System alarm display screen.
(
10
11
Touch.
2
Touch the alarms.
Reset
button to reset system
12
13
(1) Before resetting System Alarm display
Eliminate each cause before resetting system alarms.
Without eliminating causes, System Alarm display cannot be reset even when touching the [Reset] button.
(2) Processings with reset operation
The following data in the system information are also reset.
• GOT error code (Write device)
• GOT error detection signal (System Signal 2-1.b13)
14
15
16
14.8 System Alarm Display
14.8.3 Operating the system alarm display
14 - 21
14.9 GOT Start Time
14.9.1 GOT start time function
GOT start time is the function to display the following date and time.
• Start time of GOT
• Current time of GOT
• Operating hours of GOT
14.9.2 Display operation of GOT start time
(
Main menu
[Debug & self check]
Touch [GOT start time].
Touch [Debug & self check].
GOT start time
14 - 22
14.9 GOT Start Time
14.9.1 GOT start time function
14.9.3 Display of GOT start time
11
Start Time
Item
Current Time
Operating hours
Description
Displays the time when the GOT was powered on or reset-restarted (OS installation, communication setting change).
Displays the current time.
Displays operating hours of the GOT.
The displayed operating hours is the accumulated time while GOT is powered on or resetrestarted (OS installation, communication setting change).
When powering off or reset-restarting the GOT, the operating hours is cleared.
12
13
To display correct time
Set the clock of GOT.( 12.1 Time Setting and Display)
When the clock has not been set, the correct time is not displayed at [Start Time] and [Current Time].
14
Remark
Time displayed at [Operating hours]
[Operating hours] is displayed irrespective of [Start Time] and [Current Time].
When changing the clock of the GOT, [Operating hours] does not match with the difference between [Current Time] and [Start Time]. ([Operating hours] is not the time calculated from [Current Time] and [Start Time].)
The time displayed at [Operating hours] is a reference for the accumulated time while GOT is powered on or reset-restarted (OS installation, communication setting change).
15
16
9
10
14.9 GOT Start Time
14.9.3 Display of GOT start time
14 - 23
15. CLEANING OF DISPLAY SECTION
(CLEAN)
In utility, the screen can be set as not to be effected by touching the screen when clean with clothes.
For cleaning method, refer to "Section 17.3 Cleaning Method".
15.1 Clean
15.1.1 Display operation of clean
Main menu
( 9.3 Utility Display)
Clean
Touch [Clean].
Even if touch points other than the upper left corner and upper right corner of the screen, the GOT does not operates.
15.1.2 Operation of clean
If touch the upper left and upper right corners of the screen at the same time, the screen returns to the previous screen display.
Upper-left touch position
Upper-right touch position
For details of cleaning method, refer to the following.
15 - 1
15.1 Clean
15.1.1 Display operation of clean
16. INSTALLATION OF CoreOS, BOOTOS
AND STANDARD MONITOR OS
To execute the GOT utility, BootOS or Standard monitor OS has to be installed in the C drive (Flash memory).
This chapter explains the installation using GOT.
GT Designer2 CF card GOT
Write OS file
BootOS or standard monitor OS installation
GRAPHIC OPERATION TERMINAL
GOT When GOT is remote, installed easily using the CF card
CF card
Install the
CF card in GOT
GT Designer2
MITSUBISHI
GOT CF card GOT
GRAPHIC OPERATION TERMINAL
Upload OS file
GOT
MITSUBISHI
BootOS or standard monitor OS installation
CF card
Install the
CF card in GOT
GRAPHIC OPERATION TERMINAL
GOT
MITSUBISHI
Install OS from GOT to GOT using the CF card
For details of the installation using GT Designer2, refer to the following.
GT Designer2 Version Basic Operation/Data Transmission Manual
(8. TRANSFERRING DATA)
CoreOS
Section 16.1 to 16.4 of this chapter describes BootOS and Standard monitor OS only.
For CoreOS, refer to the following.
9
10
11
12
13
14
15
16
16 - 1
16.1 BootOS and Standard Monitor OS
Required for Installation
Under-mentioned BootOS and Standard monitor OS are necessary to execute utility.
OS name
BootOS
Function overview
Required for the control of GOT and the communication between PC and GOT.
Installed at factory shipment.
(BootOS can be installed from GT Designer2 or the CF card. When installed from GT Designer2 or the CF card, GOT is initialized to be the factory shipment status.)
Storage location
Flash memory
C: G1BOOT
Standard monitor OS
Standard monitor
OS
System Screen Data
System Screen Information
TrueType numerical font
12-dot Standard Font (Gothic)
16-dot Standard Font (Mincho)
16-dot Standard Font (Gothic)
Required for display and operation of the user-created screen and utility screen.
Not installed in GOT at factory shipment.
Install it from GT Designer2 or the CF card.
At installation, select Mincho or
Gothic for the 16-dot standard font.
Flash memory
C:G1SYS
16 - 2
16.1 BootOS and Standard Monitor OS Required for Installation
16.2 Prior Preparations for Installing BootOS and Standard Monitor OS
For the installation using GOT, the CF card storing BootOS or Standard monitor OS is required.
For the method of writing BootOS and Standard monitor OS in the CF card, the following two methods are available.
(1) [To Memory Card] from GT Designer2
GT Designer2 Version Basic Operation/Data Transfer Manual
(8.8 Transferring Data Using a Memory Card)
(2) Uploading from other GOT (BootOS or Standard monitor OS has been installed)
Chapter 13 FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
9
10
11
Precautions on writing BootOS, Standard monitor OS in CF card
When writing BootOS, Standard monitor OS, etc. in the CF card, be sure to execute by the utility of other GOT or GT Designer2.
The installation is not executed properly with the CF card to which uploaded from the utility of GOT or copied by softwares other than GT Designer2.
Note the available capacity of the CF card.
The available capacity of BootOS and Standard monitor OS can be confirmed by [To
Memory Card] of GT Designer2.
12
13
Capacity of data of OS to be transferred
14
15
16
16.2 Prior Preparations for Installing BootOS and Standard Monitor OS
16 - 3
16.3 BootOS and Standard Monitor OS
Installation Using CF Card
There are the following two types for the BootOS, Standard monitor OS installation using CF card.
(1) Installation method when the GOT is turned on
When the GOT is turned on, all the OS and project data stored in the memory card are transferred to the GOT.
This installation method is valid for the following cases.
• When the utility of GOT cannot be displayed
• When the standard monitor OS is not installed
• To create a GOT with the same configuration as the copy source by using the GOT data package acquisition function
(2) Installation method using the program/data control function (Utility)
By the operation of the utility, the OS and project data stored in the memory card are selected and transferred to GOT.
16 - 4
Notes on installing the Boot OS and Standard monitor OS
(1) Installing both the Boot OS and Standard monitor OS
Install the Boot OS first, and then install the Standard monitor OS.
When the Boot OS is installed, the built-in flash memory on the GOT becomes initialized to the factory setting. (All OSs and project data will be deleted.)
The Boot OS comes factory installed. Installation of the Boot OS is not necessary unless upgrading the Boot OS version.
(2) Copying the project data using the CF card
Download the project data after installing the Boot OS, Standard monitor OS, and other OSs.
Make sure that the version of the Standard monitor OS on the GOT and that of the
Standard monitor OS that created the project data match.
(3) When the OS and project data are on the CF card (When GT Designer2 is in use)
When the 2-point press installation function is used, project data will be installed at the completion of the OS installation.
When installing the system using the utility screen, install the OS and download the project data on their respective operation screens.
(4) The installation cannot be interrupted.
The followings should not be performed during the installation of BootOS or standard monitor OS.
The installation may fail, and GOT may not operate.
• Turning OFF the GOT power
• Pressing the reset button of GOT
• Turning OFF the CF card access switch
• Removing the CF card
When GOT does not operate due to the failure of the installation, follow the procedures mentioned below.
• When the installation of BootOS is failed:
Install CoreOS.
Section 16.5.1 Installation method of CoreOS
• When the installation of standard monitor OS is failed:
Install BootOS.
Section 16.3.1 Installation method when the GOT is turned on
16.3 BootOS and Standard Monitor OS Installation Using CF Card
16.3.1 Installation method when the GOT is turned on
The displayed message is different depending on the installation condition of Standard monitor OS. When the screen requesting operation is displayed, operate the GOT according to the instructions on the screen.
1
Operation procedure
1
Power OFF GOT and CF card access switch. Insert the CF card in which
BootOS, Standard monitor OS or project data is stored in the CF card interface of
GOT.
2
Switch ON the CF card access switch of
GOT.
3
Power ON the GOT touching the upper and lower left corners of the GOT screen.
9
10
11
12
4
BootOS and Standard monitor OS are installed in the built-in Flash memory.
5
The CF card access LED is lit during installation.
Do not pull out the CF card or power off the
GOT while the CF card access LED is lit.
13
14
6
GOT restarts automatically after installation is completed.
(When Standard monitor OS is already installed, touch the
OK
button to reboot the GOT.)
7
After confirming that GOT restarted normally, switch OFF the CF card access switch of GOT.
8
Confirm the CF card access LED is extinguished, remove the CF card from the
CF interface of GOT.
15
16
16.3 BootOS and Standard Monitor OS Installation Using CF Card
16.3.1 Installation method when the GOT is turned on
16 - 5
16.3.2 Installation method using the program/data control function (Utility)
For details of program/data control function, refer to the following.
Chapter 13 FILE DISPLAY AND COPY (PROGRAM/DATA CONTROL)
Program/data control is a function to install OS files from the CF card to GOT by the Utility operation.
Precautions on executing program/data control function
When execute program/data control function, Standard monitor OS has to be installed in GOT in advance. Thus, this function cannot be used for the initial installation of Standard monitor OS after purchasing GOT.
Install Standard monitor OS by the following two methods.
(1) Method using GT Designer2
GT Designer2 Version Basic Operation/Data Transfer Manual
(2) Installation method when turning the GOT power on
Section 16.3.1 Installation method when the GOT is turned on
1
Operation procedure
1
Power OFF the GOT. After CF card access
LED is off, install the CF card in which
BootOS, Standard monitor OS or project data is stored in the CF card interface of
GOT.
2
Switch ON the CF card access switch of
GOT.
3
Display the program/data control function screen (Utility) on the GOT, and install
BootOS, Standard monitor OS from the CF card to GOT.
Touch [Install].
16 - 6
16.3 BootOS and Standard Monitor OS Installation Using CF Card
16.3.2 Installation method using the program/data control function (Utility)
4
The CF card access LED is lit during install execution.
5
Do not pull out the CF card, power OFF, or reset the GOT while the CF card access card is lit.
9
10
6
After the installation is finished, the dialog box shown on the left is displayed.
7
Touch the
OK
button to reboot the GOT.
8
After confirming that GOT restarted normally, switch OFF the CF card access switch of GOT.
9
Confirm the CF card access LED is extinguished, remove the CF card from the
CF card interface of GOT.
11
12
13
14
15
16
16.3 BootOS and Standard Monitor OS Installation Using CF Card
16.3.2 Installation method using the program/data control function (Utility)
16 - 7
16.4 When Installing the Different Version of
BootOS, Standard Monitor OS
(1) Boot OS installation
When the Boot OS is installed, the GOT compares the version of the current Boot OS and the version of the Boot OS to be installed.
When the major version of the Boot OS to be installed is older than that of the current Boot OS, the following warning dialogs will appear to prevent an accidental overwriting.
(When installing from GT Designer2, follow the messages that appear on the PC screen.)
(a) When only the Boot OS is stored on the CF card.
A message will appear to indicate that the installation cannot be proceeded.
Touch the
OK
button to cancel the installation.
Restart the GOT.
(b) When the Boot OS, Standard monitor OS, and other OSs are stored on the CF card.
The installation of the Boot OS will be skipped, and an installation of the Standard monitor OS and other OSs will take place.
The following message will appear if the Standard monitor OS is already installed on the GOT.
Touching the
OK
button will start the installation.
Touching the
Cancel
button will stop the installation.
16 - 8
16.4 When Installing the Different Version of BootOS, Standard Monitor
OS
Regardless of the types of data (as described in section (a) and (b) above) on the CF card, or whether the version of the OS to be installed is the same as the current one or newer, a window that has the version information and a message that asks whether to continue installation will appear.
9
10
<The GOT screen that appears when the Boot OS was installed from the CF card>
Touching the
OK
button will start the installation.
Touching the
Cancel
button will stop the installation.
(2) Standard monitor OS installation
Match the version of each OS file when installing Standard monitor OS.
Standard monitor OS cannot be installed if the version of each OS file does not match.
When the installation process is discontinued.
Standard monitor OS : 1.
O.
O
Communication driver :
Option OS :
2.
2.
O.
O.
O
O
When the installation process is normally executed.
Standard monitor OS : 2.
O.
O
Communication driver :
Option OS :
2.
2.
O.
O.
O
O
Please match the number.
11
12
13
Checking method of BootOS, Standard monitor OS version
1. Check the version of BootOS or Standard monitor OS installed in GOT at [OS information] of the utility.
Refer to the following for details.
2. Check the version of BootOS installed in GOT at product shipment on the rating plate on GOT rear face.
(a) GT1155-QSBD ,GT1150-QLBD
14
15
GRAPHIC OPERATION TERMINAL
MODEL
GT1155-QSBD
IN 20.4 26.4VDC POWER 9.84W MAX
SERIAL 540001 BC
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
JY550D26101A
80M1 IND. CONT. EQ
US LISTED
BC
BootOS version
16
16.4 When Installing the Different Version of BootOS, Standard Monitor OS
16.3.2 Installation method using the program/data control function (Utility)
16 - 9
(b) GT1155-QTBDQ, GT1155-QTBDA, GT1155-QSBDQ, GT1155-QSBDA,
GT1150-QLBDQ, GT1150-QLBDA
GRAPHIC OPERATION TERMINAL
MODEL GT1155-QTBDQ
IN 24VDC
POWER MAX 00W
SERIAL 00007201DP00001-A
MITSUBISHI ELECTRIC
MADE IN JAPAN
D P
BootOS version
16 - 10
16.4 When Installing the Different Version of BootOS, Standard Monitor
OS
16.5 CoreOS
Install CoreOS only if the GOT is not in its factory-shipped condition, even if BootOS is installed.
Normally, installation is not required.
Precautions when installing CoreOS.
The installation cannot be interrupted.
The followings should not be performed during the installation of CoreOS.
GOT may not operate.
• Turning OFF the GOT power
• Pressing the reset button of GOT
• Turning ON the CF card access switch
• Removing the CF card
If GOT does not operate, please consult your nearest sales office or FA Center.
If GOT does not recover after CoreOS is installed, there may be a hardware problem.
Please consult your nearest sales office or FA Center.
16.5.1 Installation method of CoreOS
1
Before installing CoreOS.
(1) Installation method
CoreOS can be installed only using the memory card.
The installation via USB, RS-232 or Ethernet is not available.
(2) CF card to be used
CF card of 32MB or more is required.
(3) BootOS
By installing CoreOS, BootOS is also installed with its latest version automatically.
(No operation is required to the user.)
9
10
11
12
13
14
15
16
16.5 CoreOS
16.5.1 Installation method of CoreOS
16 - 11
2
Installation method of CoreOS
1
Write CoreOS from GT Designer2 to the
CF card
For details on the operation method of GT
Designer2, refer to the following manual.
GT Designer2 Version Basic
Operation/Data Transfer Manual
(8. TRANSFERRING DATA)
2
Check that the power of GOT main unit is
OFF, and then mount the CF card to GOT.
After mounting it, turn ON the CF card access switch.
3
Turn ON the GOT power
After the power is turned on, CoreOS installation execution screen is automatically displayed after a brief interval.
4
After the CF card access switch is turned off, the installation of CoreOS is started.
16 - 12
16.5 CoreOS
16.5.1 Installation method of CoreOS
5
When the installation is completed, the dialogue box shown on the left is displayed.
Check that the message is displayed, and turn the GOT power OFF.
(When the installation is completed, the power LED blinks.)
6
Remove the CF card after turning the power OFF.
9
10
7
If the power is turned on again, the screen shown on the left is displayed.
(The GOT goes into its factory shipped condition.)
As necessary, install each OS (Standard monitor OS, communication driver, etc.) or download a project data.
For the installation method of each OS or the download method of project data, refer to the following manual.
GT Designer2 Version Basic
Operation/Data Transfer Manual
(8. TRANSFERRING DATA)
16.5.2 When CoreOS cannot be installed
When CoreOS cannot be installed, check the following contents.
When CoreOS cannot be installed even after the following contents are checked, there may be a hardware problem.
Please consult your nearest sales office or FA Center.
Description
The installation of CoreOS is not executed after the
CF card is insreted to GOT.
The following message is displayed on GOT.
"GOT error. Contact your local sales office."
The following message is displayed on GOT.
"CF card error. Installation will be canceled. Check whether the CF card can be used."
The following message is displayed on GOT.
Wrong operation system.
Action
• Check that the CF card access switch of GOT is ON.
If it is OFF, turn it ON.
• Memory card write from GT Designer2 may not be normally completed. Execute memory card write from GT Designer2 again.
GOT main unit is breakdown.
Please consult your nearest sales office or FA Center.
CF card is broken.
• Format the CF card and execute the installation again.
• Replace the CF card.
Either the wrong type of GOT was selected for the [Core OS write] setting of the GT
Designer2, or the data on the CF card are broken.
Make sure that the correct type of GOT is selected, and execute [Core OS write] again.
The following message is displayed on GOT.
The version of OS is not acceptable to this GOT.
Installation will be canceled.
Confirm the version of OS.
Install Core OS from the latest version of GT Designer2.
11
12
13
14
15
16
16.5 CoreOS
16.5.2 When CoreOS cannot be installed
16 - 13
17. MAINTENANCE AND INSPECTION
STARTUP AND MAINTENANCE
PRECAUTIONS
DANGER
When power is on, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Connect the battery correctly.
Do not discharge, disassemble, heat, short, solder or throw the battery into the fire.
Incorrect handling may cause the battery to generate heat, burst or take fire, resulting in injuries or fires.
Before starting cleaning or terminal screw retightening, always switch off the power externally in all phases.
Not switching the power off in all phases can cause a unit failure or malfunction.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
STARTUP AND MAINTENANCE
PRECAUTIONS
CAUTION
Do not disassemble or modify the unit.
Doing so can cause a failure, malfunction, injury or fire.
Do not touch the conductive and electronic parts of the unit directly.
Doing so can cause a unit malfunction or failure.
The cables connected to the unit must be run in ducts or clamped.
Not doing so can cause the unit or cable to be damaged due to the dangling, motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault.
When unplugging the cable connected to the unit, do not hold and pull the cable portion.
Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault.
Do not drop or apply any impact to the battery.
If any impact has been applied, discard the battery and never use it.
The battery may be damaged by the drop or impact.
Before touching the unit, always touch grounded metal, etc. to discharge static electricity from human body, etc.
Not doing so can cause the unit to fail or malfunction.
DISPOSAL PRECAUTIONS
CAUTION
When disposing of the product, handle it as industrial waste.
The GOT does not include consumable components that will cause the shorten life.
However, the battery, liquid crystal screen and backlight have each life length.
It is recommended to replace the battery periodically.
(For the replacement of the liquid crystal screen and backlight, please consult your nearest sales office or FA center.)
For the battery life, refer to the following.
Section 3.4 Power Supply Specifications
For the life of the LCD screen or backlight, refer to the following.
Section 3.2 Performance Specifications
17 - 1
17.1 Daily Inspection
Daily inspection items
No.
1
Inspection Item
GOT mounting status
Loose terminal screws
Inspection
Method
Check for loose mounting screws.
Retighten screws with screwdriver
Criterion
Securely mounted
Not loose
Action
Retighten screws within the specified torque range
Retighten terminal screws
2
Connection status
Proximate solderless terminals
Visual check Proper intervals Correct
Loose connectors Visual check Not loose
Retighten connector fixing screws
Replace with new one
3
Usage status
Dirt on protection sheet Visual check
Foreign material attachment
Visual check
Not outstanding
No foreign matter sticking
Remove clean
Refer to the following for the model names of the protection sheet or the replacement procedure.
17.2 Periodic Inspection
Yearly or half-yearly inspection items
The following inspection should also be performed when equipment has been moved or modified or the wiring changed.
No.
Inspection Item Inspection Method Action
1
Surrounding environment
Ambient temperature
Ambient humidity
Atmosphere
Make measurement with thermometer or hygrometer
Measure corrosive gas
Criterion
Display section 0 to 50°C
Other portions 0 to 55°C
10 to 90%RH
No corrosive gas
For use in control panel, temperature inside control panel is ambient temperature
2 Power supply voltage check
24VDC Measure voltage across terminals.
Move module
20.4 to 26.4VDC
Change supply power
3
4
Mounting status
Connection status
Looseness
Dirt, foreign matter
Loose terminal screws
Proximate solderless terminals
Loose connectors
Visual check
Retighten screws with screwdriver
Visual check
Visual check
Should be mounted firmly Retighten screws
No dirt, foreign matter sticking
Remove, clean
Not loose
Proper intervals
Not loose
Retighten terminal screws
Correct
Retighten connector fixing screws
5 Battery
Check the system alarm (error code:
500) report on the
Alarm Information
(Preventive maintenance)
Replace with new battery when the current battery has reached the specified life span, even if battery voltage is not displayed.
17
18
17.1 Daily Inspection
17 - 2
17.3 Cleaning Method
Use the GOT always in a clean condition.
To clean the GOT, wipe the dirty part with a soft cloth using neutral detergent.
For the display operation of the [Clean] screen, refer to the following.
Chapter 15 CLEANING OF DISPLAY SECTION (CLEAN)
Clean
GRAPHIC OPERATION TERMINAL
GOT
1000
MITSUBISHI
Precautions for cleaning
Do not use chemicals such as thinner, organic solvents and strong acids, since they may cause the protective sheet to be deformed or the dissolvable paint on the surface to peel off.
In addition, do not use spray solvents since they may cause the electrical failure of the GOT and peripheral devices.
17 - 3
17.3 Cleaning Method
17.4 Battery Voltage Low Detection and Battery
Replacement
17
The battery is used for backing up the clock data, alarm history or recipe data.
It is recommended that you replace battery periodically.
Refer to the following for the replacement procedure.
The battery voltage low detection can be confirmed by the utility screen and system alarm.
Refer to the following for details of the battery status display by the utility screen.
Chapter 12 CLOCK SETTINGS AND BATTERY STATUS DISPLAY (TIME SETTING
By using system alarm, the message that notifies the battery voltage has decreased can be displayed at the battery voltage low on the screen of the GOT.
System alarm
18
500 Warning! Built-in battery voltage is low.
Refer to the following for details of the system alarm display.
GT Designer2 Version Screen Design Manual (8. ALARM)
Battery replacement timing
When detecting voltage low, replace the battery immediately.
Data can be saved for approximately a month after the battery voltage low detection and cannot be saved after that.
If it exceeds a month from the voltage low detection to battery replacement, the clock data or D-drive (Internal SRAM) data may become indefinite.
Adjust the clock and format the D drive (Internal SRAM).
17.4 Battery Voltage Low Detection and Battery Replacement
17 - 4
Example of alarm output to external device (lamp, buzzer, etc.)
The following describes an example of outputting the battery voltage low signal from a FX series PLC to an external device with system information.
Condition: The Write Device is "D20" and all data is used (the
Select All
button is clicked on the setting screen of GT Designer2) for the system information assignment.
D36 b12: Battery voltage low (System Signal 2-2)
Turned on upon a battery voltage drop.
Used as shown below in the sequence program.
RUN monitor
M8000
MOV D36 K4M20
Battery voltage low
M32
Y***
Output to external device of PLC
Activated the output upon battery voltage low detection.
"*" indicates the output number at which the external device is connected.
For details of system information, refer to the following.
GT Designer2 Version Screen Design Manual
Section 3.6 System Information Setting
17 - 5
17.4 Battery Voltage Low Detection and Battery Replacement
17.5 Backlight Shutoff Detection
17
The backlight is built into GOT for the liquid crystal display.
When GOT detects backlight shutoff, the POWER LED blinks green/orange alternately.
The brightness of the backlight decreases with the lapse of usage period. When backlight shutoff is detected or the display becomes unclear, replace the backlight.
For replacement of the backlight, contact your nearest sales office or FA Center.
(1) Life of backlight
The usable duration of backlight can be extended by setting to "Screen saving backlight off" in the utility of GOT (GOT set up).
Refer to the following for details.
Chapter 11 DISPLAY AND OPERATION SETTINGS (GOT SET UP)
18
17.5.1 Backlight shutoff detection and external alarm
When the GOT detects a backlight shutoff, the system information set with GT Designer2 is turned on.
You can issue a backlight shutoff of the GOT from the PLC to external devices (such as the lamp or buzzer), using system information.
To avoid any screen touch operation by the user who misunderstands it is in screen saving mode, install an external alarm and interlock the loads that would cause danger.
For details of the system information, refer to the following.
GT Designer2 Version Screen Design Manual
Section 3.6 System Information Setting
Example of alarm output to external devices (such as lamp or buzzer)
The following provides an example of outputting the backlight shutoff detection signal from a FX Series PLC to an external device, using system information.
Condition: The Written Device is "D20" and all data is used (the
Select All
button is clicked on the setting screen of GT Designer2) for the system information assignment.
D36 b14: D36b14: Backlight shutoff detection (System Signal 2-2)
Turned on upon a backlight shutoff.
Used as shown below in the sequence program.
RUN monitor
M8000
MOV D36 K4M20
Backlight shutoff detection
M34
Y***
Output to external device of PLC
Activated the output upon battery shutoff detection.
"*" indicates the output number at which the external device is connected.
Precautions for the backlight shutoff status
In the backlight shutoff status, the touch key operates.
Early replacement of backlight is recommended.
17.5 Backlight Shutoff Detection
17.5.1 Backlight shutoff detection and external alarm
17 - 6
18. ERROR MESSAGE AND SYSTEM
ALARM
This chapter describes the error messages and system alarm displayed in the GOT.
As the error code and error message displaying functions when an error occurs at the GOT or Controller, the system alarm is available.
The error code can also be confirmed in the error code storage area of the system information.
For details of system alarm and system information, refer to the following.
GT Designer2 Version Screen Design Manual
18.1 Error Contents Display
This section describes how to identify the error code and system alarm displayed on the monitor screen by the system alarm display function and the reference material.
(1) Displaying format on monitor screen ... Displayed in user setting position
The system alarm is displayed together with an error code, its error message and occurrence time.
The displayed error code and error message are registered to the GOT in advance and need not to be prepared by the user.
335 Memory card battery voltage low. Replace battery. 16:40:30
104 Parameter error
400 Unable to communicate with CPU.
Up to 3 lines are displayed.
(1 line per error)
Error code Error message Time of occurrence
(Displayed only for errors related to GOT.)
Display priority
The alarm is displayed in the following priority if the displaying range is one or two lines.
(1) GOT error
(2) CPU error
:The error in the GOT is displayed as an alarm.
:The error in the PLC CPU is displayed as an alarm.
(3) Network error :The error in the network is displayed as an alarm.
Alarms with smaller priority cannot be displayed if system alarms overflow the displaying range.
As well, the error code, error message or time is not displayed if the displayed message overflows each line in the displaying range.
18 - 1
18.1 Error Contents Display
(2) Error code and reference manual
Error source Error code
0 to 99
(Value of D9008)
Contents
Error code of CPU (for ACPU)
Reference
User's manual of the ACPU connected with GOT
CPU
GOT
100 to 299
300 to 399
400 to 499
500 to 699
Error code of CPU
• FX PLC
*1
• Third party PLC
• Temperature controller
(OMRON temperature controller only)
Error code of the GOT main unit function
Error code of the GOT communication function
Error code of the GOT main unit function
Error code of CPU
(for QCPU, QnACPU)
User's manual of the FXCPU to which GOT is connected
If a third-party PLC is connected, take actions referring to the error message.
CPU
Servo amplifier
*2
1000 to 10000
(Value of SD0)
20016 to 20237 Error code of servo amplifier
User's manual of the QCPU and
QnACPU connected with GOT
User's manual of the servo amplifier connected to GOT
*1 The assigned error code for FXPLC is 100 to 109, which displays the status of M8060 to M8069.
(Example) When the error code (100) error occurs, correct the error according to the M8060 description.
*2 The error code displayed on GOT is calculated by changing the error code displayed on the servo amplifier to a decimal number and adding "20000" to it.
For this reason, to refer to the manual of the servo amplifier based on the error code displayed upon a system alarm caused to the GOT, subtract the error code by "20000" and convert the lower three digits into a hexadecimal.
(Example: If the system alarm displayed at GOT is "20144," the error code of the servo amplifier is: 20144 -
20000 = 144 (BIN) = 90 (HEX).
17
18
18.1 Error Contents Display
18 - 2
18.2 List of Error Message/System Alarm
The system alarm detected with GOT is shown below.
Error code
Error message
303
Set monitor points too large.
Decrease setting points.
Action
The number of objects of the screen to be displayed is too large and the system work area cannot be secured.
Decrease the number of objects from the displayed screen. For the number of maximum objects for 1 screen, refer to the following.
304
306
307 Monitor device not set
308
309
310
311
312
315
316
320
321
Set trigger points too large.
Decrease setting points.
No project data.
Download screen data.
No comment data.
Download comment.
Device reading error.
Correct device.
Project data does not exist or out of range.
No. of alarm has exceeded upper limit.
Delete restored alarm.
No. of sampling has exceeded upper limit.
Delete collected data.
Device writing error.
Correct device.
Cannot display or input operation value.
Review expression.
Specified object does not exist or out of range.
Station No. for monitor device is wrong
GT Designer2 Version Screen Design Manual
When cycle is / ON and when cycle is / OFF the number of objects used exceeds 100.
Decrease the number of objects.
The project data is not downloaded to the built-in flash memory.
Download the project data to the built-in flash memory.
The monitor device of the object is not set.
Set the monitor device of the object.
The comment file does not exist.
Create the comment file and download to GOT.
The error occurred when reading a continuous device.
Correct the device.
1. Specified base screen / window screen does not exist in the project data.
2. Specified base screen / window screen is out of the permissible area.
Specify the existing base screen / window screen.
The number of alarm histories that can be observed by the alarm history display function has exceeded the maximum points (1024 points).
Delete the restored history to decrease the number of alarm histories.
The collection frequency exceeded the upper limit when "Store Memory" and "Accumulate/Average" were set in the scatter graph.
1. Approve "Clear trigger" setup in the scatter graph.
2. Set the "Operation at frequency over time" and "initialize and continue" in scatter graph.
Error occurred while writing in the device.
Correct the device.
In indirect specification of comment/parts number, the data operation result exceeded the range in which device type can be expressed.
Review the data operational expression, in order not exceeding the range in which the device type can be expressed.
The part file does not exist.
Create the part file and download to GOT.
Check the monitor target station No. of the project data.
18 - 3
18.2 List of Error Message/System Alarm
Error code
Error message Action
322
330
331
Insufficient memory media capacity.
Confirm M-card capacity.
332 Memory media is not formatted.
334
345
351
Dedicated device is out of range.
Confirm device range.
Memory card not installed or M-
CARD switched OFF
Memory media error.
Replace memory media.
BCD/BIN conversion error.
Correct data
Recipe file error.
Confirm content of recipe file.
The monitored device No. is set out of the permissible range of the targeted PLC CPU, or the data length for a device dedicated to 32 bits is set other than 32 bits.
1. Set the device within the range that can be monitored by the monitored
PLC CPU and parameter settings.
2. AB: L device/ S7-200: HC device/ OMPON temperature controller: Set the data length of C0, C1 and C3 devices to 32 bits.
Available memory of the memory card is insufficient.
Check the available memory of the memory card on the Drive Information of GT Designer2.
GT Designer2 Version Basic Operation/Data Transfer Manual
Section8.4 Obtaining the Drive Information [GOT to PC]
The memory card is uninstalled or access switch is OFF in drive.
1. Install the memory card in the specified drive.
2. Turn ON the access switch.
Memory card is not formatted or formatted incorrectly.
Format the memory card.
Memory card is faulty.
Replace the memory card.
The BCD/BIN conversion disabled data is being displayed/input.
1. Change the device data to be displayed to the BCD value.
2. Correct the input value to the 4 digits integer.
The contents of the recipe file are not normal.
1. Confirm the contents of the recipe files in the memory card.
2. Reboot the GOT after deleting the recipe file in the memory card
(format).
352
Recipe file make error.
Reboot GOT after inserting memory card.
Failed to generate recipe file.
Reboot the GOT after installing the memory card.
353
Unable to write Recipe file.
Confirm memory card is inserted.
354 Recipe file write error
355 Recipe file read error
356
File system error occurred in
PLC.
Confirm file register.
Failed to write in the recipe file.
1. Confirm the contents of the memory card.
2. Do not pull out the memory card while recipe is operating.
Error occurred while writing in the recipe file.
Do not unplug the memory card while recipe is operating.
Error occurred while writing in the recipe file.
1. Do not unplug the memory card while recipe is operating.
2. Confirm the contents (device value) of the recipe file in the memory card.
Error occurred in the specified file register when executing the recipe function by specifying the file register name.
1. Execute the recipe function again after confirming the file register name.
2. Execute the recipe function again after formatting the PC memory in the specified PLC CPU drive with GX Developer.
17
18
18.2 List of Error Message/System Alarm
18 - 4
Error code
Error message Action
357
358
359
360
370
402
403
406
410
411
Error in specified PLC drive.
Confirm PLC drive.
PLC file access failure.
Confirm PLC drive.
Processing from another peripheral device.
Execute it after.
0 divisor division error.
Confirm operation expression.
Upper and lower limit value error.
Confirm value setting.
Communication timeout.
Confirm communication pathway or modules.
SIO status error.
Confirm communication pathway or modules.
Specified station access is out of range.
Confirm station no.
Cannot perform operation because of PLC run mode.
stop the PLC.
Memory cassette is writeprotected.
Check the memory cassette.
When executing the recipe function specifying the file register name, error occurred in PLC CPU drive.
1. Execute the recipe function again after confirming the specified PLC
CPU drive.
2. Execute the recipe function again after formatting the PC memory in the specified PLC CPU drive with GX Developer.
When the recipe function is executed specifying the file register name,
PLC CPU file register could not be accessed.
Execute the recipe function again after confirming the specified PLC CPU drive / file register name. (When you specify drive 0, execute the recipe function again after changing to other drives.)
When the recipe function is executed specifying the file register name, other peripherals carry out the process to the file register.
Wait until the processing of other peripherals end, and execute the recipe function again.
Division 0 was generated by the data operational expression.
Review the data operational expression so that the divisor should not become 0.
The setting of lower/upper limit value is [Upper limit < Lower limit].
Correct the setting so as to be "Upper limit Lower limit".
The time-out error occurred during communication.
1. Confirm the cable omission and PLC status.
2. Put COM instruction when A, QnA or QCPU is connected and the PLC scanning is long.
Either of the overrun error, parity bit error or flaming error was generated when the RS-422 / RS-232 communication was received.
Confirm the cable omission, status of the PLC, and the transmission speed of the computer link.
1. Station numbers other than master/local station are specified at the CC-
Link connection (via G4).
2. Accessed PLC CPUs other than QCPU.
Confirm the station number of the monitor screen data.
The operation, which could not be performed during RUN of PLC CPU, was performed.
Stop the PLC CPU.
The memory cassette installed in PLC CPU is in the state protected with
EPROM or E
2
PROM.
Confirm the memory cassette installed in PLC CPU.
412
Cannot read/write device protected by keyword.
Remove key word.
The key word is set in PLC CPU.
Cancel the key word.
448
PLC cannot handle as requested.
Correct devices.
The file register of QnACPU and the device beyond the outside range of buffer memory was specified.
Correct the monitor device by setting file register of PLC CPU.
18 - 5
18.2 List of Error Message/System Alarm
Error code
Error message Action
480
500
Warning! Built-in battery voltage is low.
510 Clock data input out of range
522
524
525
Unnecessary file deleted to create new file.
Device writing error.
Correct device.
Unable to read/write alarm log files under different projects.
535 Cannot open image file.
536
550 Invalid key code
570 Recipe device points too large.
571
Communication channel not set.
Set channel number on Utility.
Image file error or invalid file format.
Capacity shortage of user memory (RAM)
One or more channel for PLC and host (microcomputer) connection (Ch.1 to 5) is not allocated by GT Designer2 or utility.
Set the channel by GT Designer2 or utility.
The voltage of the GOT built-in battery is decreased.
Replace the GOT built-in battery.
The value that is input as clock data is out of the input enabled range.
In this case, the input value is not accepted.
Confirm the input range of the value to be input as clock data, and input the proper value again.
Cancelled the file of different contents and created a new file.
Note that the old file is cancelled and the new file is created if the file of the same name with different contents exists when creating files.
When writing in the device, error occurred.
Correct the device.
Unable to read the alarm log file saved by the different project.
Confirm where to store the alarm log file and alarm log file.
• No CF card is installed in the drive or the access switch is turned on.
1. Install a recording medium in the specified drive.
2. Turn the access switch on.
• The specified file is not found in the card.
3. Add the image file or change the image file name to a correct one.
There is an error in the image file data or the image file format is not supported.
Change to the correct image file.
The key code input execution trigger was ON with the non-target key code set in the key code storage device.
Confirm the key code supported by the object where error occurs.
The number of the set points of the recipe device exceeds the specified range.
Put the number of the set points of the recipe device within the specified range.
There is no empty area/space in D drive.
If the alarm log file located in the D drive needs to be backed up, copy it to the CF card with the utility and then format the D drive.
If the recipe function is used to read devices, format the D drive and then read again to create the recipe data.
17
18
18.2 List of Error Message/System Alarm
18 - 6
18.3 Troubleshooting in Bus Connection
When connect GOT and PLC CPU with bus connection, and the cause is not clear in "18.2 List of Error
Message/System Alarm", execute the following troubleshooting.
Refer to the following for details concerning the bus connection.
GOT1000 Series Connection Manual
18.3.1 Locating error positions
Explanation regarding the method of specifying the error part.
(Please refer to User's Manual of used PLC CPU for details related to the PLC CPU error and special register.)
(1) How to locate error positions:
(a) Use of peripheral devices
Using the peripheral devices such as GX Developer, check what type of the error occurs on the PLC CPU and, based on the error message on the PLC CPU, check each module and cable for installation and earthing statuses.
18 - 7
(2) Error timing
Check the timing of errors.
1)An error occurs when the power is turned on or immediately after the PLC is reset:
The error may be detected by the initial processing of the PLC CPU.
In this case, because the faulty module may not be identified, use only an END instruction for the sequence program and remove the modules one by one until the error does not occur.
When the error is eliminated after a specific module has been removed, the module may be causing the error.
2) An error occurs after a specific operation or several seconds:
The error may occur in the sequence program. Check the error step where the error may occur and the sequence program in that step.
The sequence program can be diagnosed throughout by merely using an END instruction for the sequence program.
3) An error occurs when a specific device operates:
The mis-operation may be caused by noise.
Check that any signal line such as bus cable is not laid out too close to the operating device.
If the line is too close to the device, separate the line 100 mm or more from the device.
(a) Locating the module where an error occurs:
Based on the PLC CPU error codes and special resister information, locate a specific module where an error occurs.
By the method stated above, correct the sequence program or replace the faulty module with a new one, and check whether the error occurs.
If the error continues to occur, it may have another cause.
Referring to 18.3.2 "Further locating error positions", locate the error position further.
18.3 Troubleshooting in Bus Connection
18.3.1 Locating error positions
18.3.2 Further locating error positions
17
If the function of the PLC cannot be recovered even when the module on which an error occurs is replaced with a new one, the error may be caused by the effect from another module.
Disconnect the extension cables and bus connection cables in order from the modules starting from the module located furthest from the operating position in the system, and check for the status of occurrence of the error each time the cables are disconnected until the error does not occur.
The module or extension cables/bus-connection cables disconnected immediately before the error does not occur are considered to cause the error.
Examples of the ways of further locating error positions are shown below. (When use the extension base unit
QnASCPU)
Example 1:
Example 2:
Turn off the power of the GOT.
Turn off the power of the GOT.
Turn off the power of the PLC.
Turn off the power of the PLC.
Disconnect the bus-connection cable
(IN side) from the final stage GOT.
Disconnect the bus-connection cable
(OUT side) from the GOT located one stage before the final stage.
Turn on the power of the PLC.
Turn on the power of the PLC.
Turn on the power of the GOT.
Turn on the power of the GOT.
If an error does not occur, the final stage GOT may be faulty.
If an error does not occur, the final stage GOT and the bus-connection cable before the final stage may be faulty.
Repeat the examples 1 and 2 above to locate error positions.
18
Notes on narrowing the error part range
1. When disconnecting the extension base units in order, use only an END instruction for the sequence program, and any error resulting from the sequence program will not occur, and the status of occurrence of errors will be obtained easily.
2. When the frequency of occurrence of an error is low, check the error by taking a rather long time with the modules disconnected.
The checks stated above are effective to locate a noise invading route when the mis-operation is caused by noise.
18.3 Troubleshooting in Bus Connection
18.3.2 Further locating error positions
18 - 8
18.3.3 Specific example of troubleshooting
Taking the following system as an example, troubleshooting is shown when PLC CPU error occurred. (When
QnASCPU and the extension base unit are used)
PLC
(main base unit)
GOT 1) GOT 2)
Extension cable
PLC
(extension base unit) Bus connection cable
Bus connection cable
Start
Check the error code/step appearing on the PLC CPU.
(Obtain the status of the error and the location where the error occurs.)
The SP. UNIT DOWN message appears on PLC CPU.
Turn off the power of the GOT.
Turn off the power of the PLC.
Replace the faulty PLC CPU with a new one.
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further (not on PLC CPU).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 2) at IN side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error occurs further
(not on the GOT 2) (bus connection unit).
Turn off the power of the GOT.
Turn off the power of the PLC.
Disconnect the bus-connection cable from the GOT 1) at OUT side
(to further locate the error positions).
Turn on the power of the PLC.
Turn on the power of the GOT.
The error will not occur.
The bus-connection cable connecting the GOT 1) to the GOT 2) is judged faulty.
Replace the faulty bus-connection cable with a new one.
End
18 - 9
18.3 Troubleshooting in Bus Connection
18.3.3 Specific example of troubleshooting
18.4 Troubleshooting for Monitoring
This section describes the countermeasures when GOT does not display the monitor screen.
GOT does not display the screen
POWER LED of GOT is off.
YES
Turn on the power supply of GOT
NO
GOT POWER LED is lit in orange
YES
Backlight OFF during screen saving is set.
The setting of screen saving can be set in the GOT utility menu. *1
NO
System Information function (System Signal 1) is set.
NO
YES
The bit of Forced Screen Saver Enable
Signal may be ON. Confirm the bit status.
When "ON", set the bit to "OFF". *2
GOT POWER LED blinks in orange/green
YES
Backlight bulb is blown.
To replace the backlight, contact your nearest sales office or FA Center.
NO
The possible cause is a GOT hardware fault.
Please consult your nearest sales office or FA Center, explaining a detailed description of the problem.
*1 For utility menu, refer to the following.
Chapter 11 DISPLAY AND OPERATION SETTINGS (GOT SET UP)
*2 For the details of the forced screen saver enable signal, refer to the following.
GT Designer2 Version Screen Design Manual
Section 3.6 System Information Setting
17
18
18.4 Troubleshooting for Monitoring
18.3.3 Specific example of troubleshooting
18 - 10
18.5 Starting GOT
18.5.1 Power-Off
Do not turn the GOT power OFF during the start-up right after turning the GOT power on or during the restart-up after transferring each OS or project data and changing the setting on the utility screen.
“When “Booting” or “Booting project data” is displayed on the screen, GOT is in start-up mode or restart-up mode.”
<When GOT standard monitor OS is V 01. 02. 01 or before>
When the GOT power in turned OFF, the setting may return to the factory-shipped default when the GOT power turned on next time.
If the power is turned off due to power failure or others, install the OS or download the project data again.
<When GOT standard monitor OS is V 01. 02. 02 or later>
Even if the power is turned off during the start-up, GOT operates in the condition that the OS and project data before the power OFF are stored when turning the GOT power on.
18.5.2 Communication from GT Designer2 to the GOT
GT Designer2 cannot communicate with the GOT while "Booting" is displayed on the GOT screen.
"Booting" is displayed on the GOT screen under the following conditions:
• Right after turning on the power to the GOT
• When rebooting after transferring OSs and project data
• When rebooting after changing the settings on the utility screen.
When the communication with GOT is attempted, communication errors will occur on GT Designer2.
Carry out the communication after "Booting project data" is displayed on the GOT screen.
It may take time to start the communication between the GOT and the controller depending on the type of controllers.
GOT starts the communication with GT Designer2 after the communication with the controller has been established.
18 - 11
18.5 Starting GOT
18.5.1 Power-Off
APPENDICES
Appendix 1 External Dimensions
External dimensional diagrams of GT1155-QSBD and GT1150-QLBD
22
(0.87")
164(6.46")
120(4.73")
23(0.91")
GRAPHIC OPERATION TERMINAL
GOT
1000
#4-40UNC
(Inch screw type)
M2.6
(Metric screw type)
22
(0.87")
120(4.73")
MITSUBISHI
4
(0.16")
5
(0.2")
Panel thickness: 5mm(0.2") or less
Unit: mm (inch)
152(5.99")
17
18
Appendix 1 External Dimensions
App - 1
External dimensional diagrams of GT1155-QTBDQ, GT1155-QSBDQ and GT1150-QLBDQ
28.5
(1.12")
21(0.83")
167(6.57")
110(4.33")
GRAPHIC OPERATION TERMINAL
GOT
1000
M2
(Metric screw type)
#4-40UNC
(Inch screw type)
MITSUBISHI
28.5
(1.12")
110(4.33")
4
5
(0.16") (0.2")
Panel board thickness to be 5 mm(0.2
"
) or less
Unit: mm(inch)
152
(5.99")
App - 2
Appendix 1 External Dimensions
External dimensional diagrams of GT1155-QTBDA, GT1155-QSBDA and GT1150-QLBDA
28.5
(1.12")
21(0.83")
167(6.57")
110(4.33")
GRAPHIC OPERATION TERMINAL
GOT
1000
28.5
(1.12")
110(4.33")
#4-40UNC
(Inch screw type)
MITSUBISHI
4
5
(0.16") (0.2")
Panel board thickness to be 5 mm(0.2
"
) or less
17
18
Unit: mm(inch)
152 (5.99")
Appendix 1 External Dimensions
App - 3
External dimensions of memory board
37.0(1.46")
6.1(0.25")
Unit: mm (inch)
External dimensions of stand
GT05-50STAND
For angle of 75
153(6.05")
220(8.67")
A9GT-50STAND
For angle of 75
156(6.15")
220(8.67")
260(10.24")
Unit: mm (inch)
262(10.32")
Unit: mm (inch)
App - 4
Appendix 1 External Dimensions
External dimensions of communication cable
GT01-C30R4-25P
16
(0.63")
50(1.97") 30000(1181.1")
7
(0.28")
M2.6
53(2.09")
M2.6
16
(0.63")
50(1.97") L
7
(0.28")
M2.6
Value of
100
200
300
53(2.09")
16
(0.63")
M2.6
Length L mm (inch)
10000 (393.7")
20000 (787.4")
30000 (1181.1")
16
(0.63")
Unit: mm (inch)
17
18
16
(0.63")
50(1.97") L
6
(0.24")
25 33
(0.99") (1.3")
40(1.58")
13
(0.52")
Value of
10
30
100
200
300
M2.6
Length L mm (inch)
1000 (39.37")
3000 (118.11")
10000 (393.7")
20000 (787.4")
30000 (1181.1")
Appendix 1 External Dimensions
App - 5
GT01-C30R2-25P
16
(0.63")
50(1.97") 30000(1181.1") 53(2.09")
16
(0.63")
GT01-C30R2-9S
16
(0.63")
50(1.97")
#4-40UNC
6
#4-40UNC
30000(1181.1")
6
M2.6
#4-40UNC
GT01-C30R2-6P
16
(0.63")
50(1.97")
50(1.97")
16
(0.63")
30000(1181.1")
20 28
(0.79") (1.11")
7
(0.28")
40(1.58")
#4-40UNC
13
(0.52")
App - 6
Appendix 1 External Dimensions
BUS connection cable specifications
Cable model
GT15-QC B
GT15-QC BS
GT15-C NB
GT15-AC B
GT15-A1SC B
GT15-A1SC NB
GT15-J2C B
GT15-370C B-S1
GT15-C EXSS-1
GT15-C BS
GT15-EXCNB
Cable length (m(ft.))
0.6(2),1.2(3.9),3(10),5(20),10(33)
15(49),20(66),25(82),30(98),35(120)
1.2(3.9),3(10),5(20)
0.6(2),1.2(3.9),3(10),5(20)
0.7(2),1.2(3.9),3(10)5(20)
0.45(1.5),1.2(3.9),3(10),5(20)
1(3)
1.2(3.9),2.5(8.2)
10.6(34.8),20.6(67.6),30.6(100)
10(33),20(66),30(98)
0.5(2)
Dimensions (mm) and shape of the connector
GOT side
Fig. 3
PLC side
Fig. 3
Fig. 3
Fig. 1
Fig. 2
Fig. 1
Fig. 4
Fig. 1
Fig. 4
Fig. 4
Fig. 4
Fig. 5
Fig. 3
Fig. 2
Fig. 2
Fig. 1
Fig. 2
Fig. 6
Fig. 4
Fig. 4
Fig. 4
Fig. 4
*1: The GT15-C EXSS/GT15-C BS cable has a grounding wire (1 m).
Be sure to connect the wire to control panels.
*2: The GT15-C EXSS-1 is the set product consisting of (GT15-EXCNB+GT15-C BS). (Refer to Fig. A)
Fig.A
Fig.4
PLC side
Fig.5
(GT15-EXCNB) buffer circuit cable
Fig.4
GOT side
Fig.4
(GT15-C BS) extension cable
33.0 (1.30)
11.5
(0.45)
Fig.1
Fig.2
60.0 (2.36)
20.0
(0.79)
17
18
Fig.3
35.0 (1.38)
10.0
(0.39)
Fig.4
33.0 (1.30)
12.4
(0.49)
Fig.5
75.0 (2.95)
20.5
(0.81)
Fig.6
55.3 (2.18)
6.0
(0.24)
5.0
(0.2)
2.2 (0.1)
Unit : mm (inch)
Appendix 1 External Dimensions
App - 7
Appendix 2 Usage Condition of Utility Function
The function which can be used differs according to the GOT type.
Moreover, there are the function which can be set with drawing software and the function which cannot be set.
: Applicable : Not Applicatble - : Not required
Setting items Function GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
Connection detail settings
Channel No. setting and communication driver assignment to communication interface
Communication parameter setting
Sequence program protection key word setting
(When connecting FX series PLC)
Sequence program protection key word deleting
(When connecting FX series PLC)
Sequence program protection status cancel (When connecting FX series PLC)
Opening screen time setting
Screen save time setting
Screen save backlight ON/OFF setting
Message language switching (Japanese/English/
Chinese (Simplified)/Chinese (Traditional)/Korean/
German)
Battery alarm display ON/OFF setting
Screen saving human sensor enable/disable setting
-
-
*2
V
Human sensor detect level setting
Display settings
V
Display of human sensor detect time
V
Human sensor OFF delay setting
V
Invert colors ON/OFF setting
Brightness
/contrast adjustment
Liquid crystal brightness setting
Liquid crystal contrast setting
(Continued to next page)
App - 8
Appendix 2 Usage Condition of Utility Function
Setting items
: Applicable : Not Applicatble - : Not required
Function GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
Operation
Security setting
Utility call key
Key sensitivity
*3
Buzzer volume setting
Security level change (Security password input for each object)
Utility call key setting
Key sensitivity setting
Key reaction speed Displaying key response speed
Touch panel adjustment
Correcting touch position reading error
-
-
-
17
18
Q/QnA ladder monitor setting
Transparent mode setting
Video Unit
Settings
Video Display
Settings
RGB Display
Settings
Time display and setting
*4
Setting of data holding destination for
MELSEC-Q/QnA ladder monitor function
Setting of communication target channel
No. when using FA transparent function
Setting of the video input signal and resolution
Setting of the captive area size for each video channel, the color tone, contrast, brightness, and color intensity
Setting of the RGB clock phase, horizontal screen position, and vertical screen position
Selecting base clock
Displaying the present time of the clock
Setting the present time of the clock
Displaying battery status
-
-
-
-
-
-
-
-
-
Appendix 2 Usage Condition of Utility Function
App - 9
Setting items
OS information
Project information
Alarm information
Function
: Applicable : Not Applicatble - : Not required
GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
Installing OS
Uploading OS
Displaying the properties of OS (Type, version, date)
System file (OS) data check
Downloading project file
Uploading project file
Deleting project file
Copying project file (A drive A drive)
Displaying the properties of project file
(Date, version, screen title)
Project file data check
Deleting alarm log file
Copying alarm log file
G1A CSV conversion (Conversion of alarm file from G1A to CSV)
G1A TXT conversion (Conversion of alarm file from G1A to TEXT)
Historical graph display
Total graph display
Historical graph display of alarm file
Total graph display of alarm file
Advanced recipe information
Advanced recipe record list
G1P CSV conversion (Conversion of advanced recipe file from G1P to CSV)
G1P TXT conversion (Conversion of advanced recipe file from G1P to CSV)
Deleting advanced recipe file or folder
Copying advanced recipe file
Moving advanced recipe file or folder
Changing advanced recipe folder name
Creating a new advanced recipe file or folder
Loading record value
Saving record value
Matching record value
Deleting device value
(Continued to next page)
App - 10
Appendix 2 Usage Condition of Utility Function
Setting items
Logging information
Operation log information
Function
: Applicable : Not Applicatble - : Not requireds
GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
G1L CSV conversion (Conversion of logging file from G1L to CSV)
G1L TXT conversion (Conversion of logging file from G1L to TXT)
Deleting logging file or folder
Copying logging file
Moving logging file
Changing logging file name
Creating a new logging folder or file
G1O CSV conversion (Conversion from G1L of operation log file to CSV)
G1O TXT conversion (Conversion from G1O of logging file to TXT)
Deletion of a operation log file or folder
Copying of an operation log file
Moving of an operation log file
Changing of an operation log file name
Creating of a new operation log folder
Displaying and searching of the list of operation logs
Deleting hard copy file
Copying hard copy file
Hard copy information
Memory card format
Memory information
Formatting memory card
Special data information
GOT data package acquisition
Displaying the memory free space of GOT
Displaying the name, data size and creating date of file or folder
Deleting special data file or folder
Special data file check
Downloading special data of A drive (Standard
CF card) to C drive (Built-in flash memory)
Copies OS, special data, and project data to the memory card
17
18
Appendix 2 Usage Condition of Utility Function
App - 11
Setting items
System monitor
Ladder monitor
A list editor
Function
: Applicable : Not Applicatble - : Not required
GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
Changing the present value of the device monitor of PLC, the buffer memory monitor of the test function and special memory, and the buffer memory
Displaying ladder monitor and executing hard copy
Changing PLC program of ACPU and parameters
FX list editor
List editing PLC program of FX PLC
Intelligent module monitor
Network monitor
Q motion monitor
Servo amplifier monitor
CNC monitor
Executing the monitor and data change for the buffer memory of intelligent function module on the dedicated screen
Or monitoring available to check the signal status of I/O module
Monitoring the network status of
MELSECNET/H, MELSECNET/10,
MELSECNET(II) and MELSECNET/B
Servo monitor and parameter settings of the motion controller CPU (Q series)
Executing each monitor function, parameter change, test operation and others of the servo amplifier
Executing the position display monitor equivalent to the display dedicated to
MELDAS, the alarm diagnosis monitor, the tool offset/parameter, the program monitor, etc.
App - 12
Appendix 2 Usage Condition of Utility Function
Setting items
Memory check
Drawing check
Function
: Applicable : Not Applicatble - : Not required
GT15
GT Soft
GOT 1000
GT11
Drawing
Setting
A drive memory check (Standard CF card)
C drive memory check (Built-in flash memory)
D drive memory check (Built-in SRAM)
Missing bits, color, draw, display and overlap display check of liquid crystal
Installed fonts check Font check
Touch panel check
Touch panel operation check
I/O check
NETWK unit status display
System alarm display
GOT start time
Screen cleaning
Maintenance report
*7
Integrated value reset
*7
Connected target confirmation
Self-loopback check
*5
Monitoring of the LED status display of the
MELSECNET/H communication unit and
CC-Link communication unit (GT15-
J61BT13)
Displaying GOT errors, CPU errors, network errors
Resetting GOT errors
Displaying GOT start date and time, current time, accumulated operating hours
Displaying the screen to clean the display section
Backlight maintenance notification time setting
Display section maintenance notification time setting
Touch key maintenance notification count setting
Built-in flash memory maintenance notification count setting
Function to reset the values of backlight maintenance notification time counted for maintenance time report, display section maintenance notification time, touch key maintenance notification count and built-in flash memory maintenance notification count
-
-
-
-
-
-
*1: It is necessary to perform the followings by GT Designer2.
• Installation of communication driver
• Assignment of channel No. and communication driver
*2: The following display and operations are not allowed with the GT11.
• Chinese (Traditional) cannot be displayed.
• Japanese and Chinese (Simplified) cannot be selected on the GOT screen.
(Japanese and Chinese (Simplified) fonts cannot be installed at the same time.)
*3: It is necessary to set the security level by GT Designer2.
*4: Mount a battery as necessary.
*5: It is necessary to mount a RS-232 connector for test. (
*6: GT11 will display only the GOT error and CPU error.
*7: It is necessary to mount the option function board and battery.
*6
Appendix 2 Usage Condition of Utility Function
App - 13
17
18
Appendix 3 Transportation Precautions
When transporting lithium batteries, make sure to treat them based on the transport regulations.
Appendix 3.1 Relevant models
The battery for the GOT1000 Series is classified as shown in the table below.
Product name
Battery for GOT1000 Series
Model
GT11-50BAT
Description
Lithium coin battery
Handled as
Non-dangerous goods
Appendix 3.2 Transport guidelines
Products are packed properly in compliance with the transportation regulations prior to shipment. When repacking any of the unpacked products to transport it to another location, make sure to observe the IATA
Dangerous Goods Regulations, IMDG Code and other local transportation regulations.
For details, please consult your transportation company.
App - 14
Appendix 3 Transportation Precautions
Appendix 4 List of Functions Added by GT Designer2
Version Upgrade (For GOT1000 Series)
17
The following describes the functions added by version upgrade of the GT Designer2 Version2.58L.
For function comparisons among GOTs, refer to the following.
GT Designer2 Version Basic Operation/Data Transfer Manual
(Appendix 3.2 List of Differences between the GOT1000 series and GOT-900 series
functions)
For using the following functions, use GT Designer2 or OS of the corresponding version or later.
(Applicable OS versions and communication drivers for GT15, GT SoftGOT1000, and GT11 are different from those for GT10. The added functions for GT10 are listed separately from those for GT15, GT
SoftGOT1000, and GT11.
How to use this table
provides the versions of GT Designer2 and OS required for each GOT or communication unit.
and the following provides description for the functions added with the version upgrade, and the versions of GT Designer2 and OS with which the function is compatible.
Regarding and the following, there may be a case where the function is not supported by a particular type of GOT even when the function is compatible with the version.
In such a case, check the version for the function and the version of the GOT, and use GT Designer2 or OS of the later version.
Appendix 4.1 GT15, GT SoftGOT1000, and GT11
18
1
Added GOT main unit /Communication unit
Target Models
GT1595-XTBA
GT1595-XTBD
GT1585-STBD
GT1585V-STBA, GT1585V-STBD
GT1575-STBD
GT1575V-STBA, GT1575V-STBD
GT1575-VTBD
GT1575-VNBA, GT1575-VNBD, GT1572-VNBA, GT1572-VNBD
GT1565-VTBD
GT1562-VNBA, GT1562-VNBD
GT1555-VTBD
GT1555-QTBD, GT1555-QSBD, GT1550-QLBD
GT1155-QTBDQ, GT1155-QSBDQ, GT1155-QTBDA, GT1155-QSBDA
GT1150-QLBDQ, GT1150-QLBDA
Version of GT
Designer2
2.18U
2.32J
2.18U
2.32J
2.18U
2.32J
2.18U
2.18U
2.18U
2.18U
2.58L
2.32J
2.58L
Version of OS
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.03.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.03.**]
(Continued to next page)
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 15
GT1155HS-QSBD to GT1150HS-QLBD
GT SoftGOT1000
Target Models
GT15-QBUS(2), GT15-ABUS(2), GT15-RS2-9P, GT15-RS4-9S, GT15-RS4-TE
GT15-CFCD
GT15-CFEX-C08SET
GT15-SOUT
GT15-DIO
Version of GT
Designer2
2.18U
Version of OS
Standard monitor OS [02.02.**]
2.27D
2.18U
2.43V
2.45X
2.58L
2.58L
-
Standard monitor OS [02.02.**]
Communication driver
For communication drivers used in
each connection, use [02.02.**] or
Standard monitor OS [03.01.**]
BootOS [03.01.**.M]
Standard monitor OS [03.02.**]
Extended function OS
Sound Output [03.03.**]
Extended function OS
External I/O / Operation Panel
[03.03.**]
2
Added connection types
Item
Bus connection
Description
Supporting connection to Q172HCPU,
Q173HCPU
Priority order of data load can be set.
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to FX3U series
Direct connection to CPU
Supporting automatic system switching for QCPU redundant system
Computer link connection
Supporting connection to BUS
Communication driver name has been changed.
Supporting connection to Q172HCPU,
Q173HCPU
Communication driver name has been changed.
Version of GT
Designer2
2.04E
2.58L
2.09K
2.43V
2.09K
2.18U
2.32J
2.43V
2.09K
2.43V
Version of OS
GT
15
GT Soft
GOT1000
GT
11
Communication driver
Bus(Q)[01.00.**]
Bus(A/QnA) [01.00.**]
GT15
Communication driver
Bus(Q) [03.03.**]
Bus(A/QnA) [03.03.**]
GT11
BootOS [03.03.**.P]
Standard monitor OS [03.03.**]
Communication driver
Bus(Q) [03.03.**]
Bus(A/QnA) [03.03.**]
Communication driver
Bus(Q) [01.02.**]
Communication driver
Bus connection Q [03.01.**]
Communication driver
A/QnA/QCPU,QJ71C24 [01.02.**]
Communication driver
MELSEC-FX[02.02.**]
Communication driver
A/QnA/QCPU, QJ71C24,
MELDAS C6* [03.00.**]
Communication driver
A/QnA/QCPU, QJ71C24
[03.01.**]
Communication driver
A/QnA/QCPU,QJ71C24 [01.02.**]
Communication driver
A/QnA/QCPU, QJ71C24 [03.01.**]
AJ71QC24, MELDAS C6* [03.01.**]
(Continued to next page)
App - 16
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Item Description
MELSECNET/H connection (PLC to PLC network)
MELSECNET/10 connection (PLC to PLC network)
CC-Link connection
(Intelligent device station)
Supporting connection to MELSECNET/H
(PLC to PLC network)
Supporting routing parameter setting with
GT Designer2.
Supporting connection to MELSECNET/
10 PLC to PLC connection)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting automatic system switching for QCPU redundant system
Supporting routing parameter setting with
GT Designer2.
Supporting connection to CC-Link
(Intelligence device station)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to CC-Link Ver.2
Version of GT
Designer2
2.25B
2.32J
2.43V
Version of OS
-
Communication driver
MELSECNET/H [03.00.**]
Communication driver
MELSECNET/H [03.01.**]
2.09K
2.32J
2.43V
2.09K
2.32J
Communication driver
MELSECNET/10 [01.02.**]
Communication driver
MELSECNET/10 [03.00.**]
Communication driver
MELSECNET/H [03.01.**]
Communication driver
CC-LINK(ID) [01.02.**]
Communication driver
CC-Link Ver2 (ID) [03.00.**]
CC-Link connection (Via
G4)
Ethernet connection
Supporting connection to CC-Link (Via
G4)
Supporting connection to Q172HCPU,
Q173HCPU
Supporting connection to the Ethernet
Supporting connection to Q172HCPU,
Q173HCPU
Supporting automatic system switching for QCPU redundant system
Supporting routing parameter setting with
GT Designer2.
Extended device range monitored
(The setting of TIM or CNT up to 4095, etc.)
2.09K
2.09K
2.32J
2.43V
2.09K
Communication driver
CC-LINK(G4) [01.02.**]
OMRON PLC connection
KEYENCE PLC connection
SHARP PLC connection
TOSHIBA PLC connection
JTEKT PLC connection
Supporting delay time setting
Supporting the settings of Retry and
Timeout Time.
Supporting connection to KEYENCE PLC
Supporting connection to SHARP PLC
Supporting connection to TOSHIBA PLC
Supporting connection to JTEKT PLC
2.27D
2.43V
2.18U
2.09K
2.09K
2.32J
GT
15
GT Soft
GOT1000
GT
11
Communication driver
QJ71E71/AJ71(Q)E71
[01.02.**]
Communication driver
QJ71E71/AJ71(Q)E71 [03.00.**]
Communication driver
QJ71E71/AJ71(Q)E71 [03.01.**]
Communication driver
OMRON SYSMAC
[01.02.**]
Communication driver
OMRON SYSMAC
[02.04.**]
Communication driver
OMRON SYSMAC [03.01.**]
Communication driver
KEYENCE KV700/1000 [02.02.**]
Communication driver
SHARP JW [01.02.**]
Communication driver
TOSHIBA PROSEC T/V
[01.02.**]
Communication driver
JTEKT TOYOPUC-PC [03.00.**]
(Continued to next page)
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 17
Item
HITACHI IES PLC connection
HITACHI PLC connection
FUJI FA PLC connection
MATSUSHITA
PLC connection
Description
Supporting connection to HITACHI PLC
Supporting connection to HITACHI PLC
Supporting connection to FUJI FA PLC
Supporting connection to MATSUSHITA
PLC
Supporting connection to FP-
Σ
Version of GT
Designer2
2.09K
2.43V
2.43V
2.09K
2.18U
Version of OS
Communication driver
HITACHI HIDIC H [01.02.**]
HITACHI HIDIC H (Protocol 2)
[01.02.**]
Communication driver
HITACHI S10mini/S10V [03.01.**]
Communication driver
FUJI MICREX-F [03.01.**]
Communication driver
MATSUSHITA MEWNET-FP
[01.02.**]
Communication driver
MATSUSHITA MEWNET-FP
[02.02.**]
GT
15
GT Soft
GOT1000
GT
11
YASKAWA PLC connection
Supporting connection to FP-X
The device range applicable to monitoring is extended.
(Up to 991F for R and up to 911 for WR can be set.)
Supporting connection to MP2000 and
MP3000
2.58L
2.47Z
Communication driver
MATSUSHITA MEWNET-FP
[03.03.**]
Supporting the Ethernet connection
YOKOGAWA PLC connection
Supporting connection to STARDOM
Supporting the Ethernet connection
Can use L device by MicroLogix 1000/
1200/1500 series
Allen-Bradley PLC connection
Supporting connection to Control/
CompactLogix
SIEMENS PLC connection
Microcomputer connection
OMRON temperature controller connection
Supporting the Ethernet connection
Supporting connection to SIEMENS S7-
200 series
Supporting XON/XOFF control
Supporting interrupt extension
Supporting connection to OMRON temperature controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added.
2.47Z
2.32J
2.47Z
2.18U
2.58L
2.58L
2.18U
2.32J
2.18U
2.58L
Communication driver
YASKAWA GL/CP9200(SH/H)/
CP9300MS [03.02.**]
Communication driver
Ethernet(YASKAWA) [03.02.**]
Communication driver
YOKOGAWA FA500/FA-M3/
STARDOM [03.00.**]
Communication driver
Ethernet(YOKOGAWA) [03.02.**]
Communication driver
AB MicroLogix [02.02.**]
Communication driver
AB Control/CompactLogix
[03.03.**]
Communication driver
EtherNet/IP(AB) [03.03.**]
Communication driver
SIEMENS S7-200 [02.02.**]
Communication driver
Computer [03.00.**]
Communication driver
OMRON THERMAC / INPANEL
NEO [02.02.**]
Communication driver
OMRON THERMAC/INPANEL
NEO [03.03.**]
(Continued to next page)
App - 18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Item Description
SHINKO indicating controller connection
CHINO controller connection
FUJI SYS temperature controller connection
YAMATAKE temperature controller connection
Supporting connection to SHINKO indicating controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
Supporting connection to CHINO controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
Supporting connection to FUJI SYS temperature controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
Supporting connection to YAMATAKE temperature controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
YOKOGAWA temperature controller connection
Supporting connection to YOKOGAWA temperature controller
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
Supporting connection to RKC temperature controller
RKC temperature controller connection
Supporting connection to SRZ
The functions to automatically stop monitoring faulty stations and to disconnect communications with controllers are added
Supporting connection to inverter
Inverter connection
Setting range for Timeout Time has been changed.
(3 to 30 seconds 1 to 30 seconds)
Version of GT
Designer2
2.43V
Version of OS
Communication driver
Shinko Technos Controller [03.01.**]
GT
15
GT Soft
GOT1000
GT
11
2.58L
2.58L
2.32J
2.58L
2.18U
2.58L
2.43V
2.58L
2.18U
2.58L
2.18U
2.43V
Communication driver
Shinko Technos Controller [03.03.**]
Communication driver
CHINO Controllers(MODBUS)
[03.03.**]
Communication driver
FUJI PXR/PXG/PXH [03.00.**]
Communication driver
FUJI PXR/PXG/PXH [03.03.**]
Communication driver
YAMATAKE SDC/DMC [02.02.**]
Communication driver
YAMATAKE SDC/DMC [03.03.**]
Communication driver
YOKOGAWA GREEN/UT100/
UT2000 [03.01.**]
Communication driver
YOKOGAWA GREEN/UT100/
UT2000 [03.03.**]
Communication driver
RKC SR Mini HG(MODBUS)
[02.02.**]
Communication driver
RKC SR Mini HG(MODBUS)
[03.03.**]
Communication driver
FREQROL 500/700 [02.02.**]
Communication driver
FREQROL 500/700 [03.01.**]
(Continued to next page)
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 19
Item
CNC connection
Servo amplifier connection
Bar code reader connection
Printer connection
Description
Supporting connection to CNC
Communication driver name has been changed.
Supporting connection to servo amplifier
Supporting connection to MELSERVO-J3 series
Supporting writing to the E
2
PROM area in parameter writing
Supporting the point table setting for MR-
J2S-*CP
Supporting the test run mode
Supporting connection to barcode reader
Supporting connection to 2D-code reader
Supporting connection to printer
Supporting the FA transparent function via
USB
Version of GT
Designer2
2.18U
2.43V
2.09K
2.18U
2.32J
2.32J
2.32J
2.09K
2.27D
2.27D
2.09K
Version of OS
Communication driver
A/QnA/QCPU, QJ71C24, MELDAS
C6
*
[02.02.**]
A/QnAQJ71E71/AJ71(Q)E71
[02.02.**]
MELSECNET/10 [02.02.**]
CC-Link(ID) [02.02.**]
Communication driver
AJ71QC24, MELDAS C6* [03.01.**]
Communication driver
MELSERVO-J2S/M [01.02.**]
Communication driver
MELSERVO-J3,J2S/M [02.02.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Communication driver
MELSERVO-J3, J2S/M [03.00.**]
Extended function OS
Barcode [01.02.**]
Extended function OS
Barcode [02.04.**]
Extended function OS
Printer [02.04.**]
GT15
Standard monitor OS [01.02.**]
GT11
Standard monitor OS [01.02.**]
Boot OS [01.02.**.C]
FA transparent
MT Developer (via USB), MR Configurator and FR Configurator are added as compatible software.
GX Configuration and PX Developer are added as compatible software.
Connection with multiple GT11s
Multiple-GT11 connection
External I/O device connection
Supporting connection to external I/O devices
2.27D
2.32J
2.09K
2.58L
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [01.02.**]
Extended function OS
External I/O / Operation Panel
[03.03.**]
GT
15
GT Soft
GOT1000
GT
11
App - 20
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
17
3
Added GT Designer2 functions
Item Description
Ethernet download Downloading the project data via Ethernet
Basic comment, comment group
Copying comments in column unit on
Basic Comment or Comment Group, etc.
Improved library structure and added import function
Improved user library structure, expanded the user library registration capacity, copying the figure data to the user library, etc.
Library workspace
Project data matching
Copy ON
Copy OFF
Data View
Batch Edit
OFF
Import, Export
ON
Screen Preview
Wizard
Screen script, project script
Auxiliary setting
Expansion /
Reduction
Addition of fixed frame figure
Enables setting the background color of the figures in the Library Editor screen.
Enables sorting the figure data by subject or function and displaying differentshaped figures in the same color in the image list.
Matching project data stored in GOT and project data opened on GT Designer2
Enables copying of only characters in lamp display, touch switch and comment display.
Enables editing of the settings for advanced alarm observation (advanced user alarm), alarm history, advanced recipe function and recipe function in the
CSV file format and other format.
Enables printing of header and footer
Enables changing of the settings for the respective objects in grouped objects
Enables global replacement of channel
No.
Enables checking for security level switching and language switching in image after switching
Wizard for setting the GOT type, controller type and communication settings when creating a new project
Settings on the Script Edit dialog are available for screen script and project script.
Setting of maintaining screen numbers of the screens being displayed (System
Information) during screen switching is added.
Supports expansion/reduction when multiple objects and shapes are selected.
Version of GT
Designer2
2.09K
Version of OS
Standard monitor OS [01.02.**]
2.09K
2.09K
2.18U
2.18U
2.47Z
2.58L
2.09K
2.18U
2.18U
2.18U
2.18U
2.18U
2.18U
2.18U
2.27D
2.27D
2.32J
-
-
-
-
-
-
Standard monitor OS [01.02.**]
-
-
-
-
-
-
-
-
-
-
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 21
Zoom
Item
Screen capture
Communication
Description
Function for capturing the specified range and loading to GT Designer2
• Interval of magnification specification has been changed.
• +/- buttons have been added.
• Zoom in/zoom out operations using the
" Ctrl key" and "Mouse wheel" have been added.
Holds the previous downloaded drive.
• Enables updating BootOS without the standard monitor OS updated when only BootOS is already installed on the
GOT.
• Enables installing the standard monitor
OS with the communication driver at once when only BootOS is already installed on the GOT.
Version of GT
Designer2
2.43V
2.43V
2.47Z
2.58L
Version of OS
-
-
-
BootOS [03.03.**.P]
GT
15
GT Soft
GOT1000
GT
11
App - 22
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
17
Figure
4
Added common settings/object functions
Item Description
JPEG file reading enabled
Version of GT
Designer2
2.09K
Version of OS
Standard monitor OS [01.02.**]
Function to import IGES format data.
Enables adjusting image qualities for reading JPEG files.
2.43V
2.47Z
-
-
2.09K
Standard monitor OS [01.02.**]
Text
Standard font
Stroke font
KANJI Region
Windows fonts applicable
Stroke font applicable
Enables specifyng of background color.
• Japanese 12dot
• Japanese 16dot Gothic
• Japanese 16dot Mincho
• Japanese (supporting Europe) 12dot
• Japanese (supporting Europe) 16dot
Gothic
• Japanese (supporting Europe) 16dot
Mincho
• Chinese (Simplified) 12dot
• Chinese (Simplified) 16dot Mincho
• Chinese (Simplified) (supporting
Europe) 12dot
• Chinese (Simplified) (supporting
Europe) 16dot Mincho
Enables setting the KANJI region.
Supporting Thai
The following font name is changed.
• Stroke Standard Font(JPN)
The following fonts are added.
• Stroke Standard Font(China GB)
• Stroke Standard Font(China
GB)(supporting Hangul)
The following font is added.
• Stroke Font(JPN)
Supporting Chinese (Traditional)
2.43V
2.32J
2.04E
2.27D
2.47Z
2.47Z
2.58L
2.58L
2.18U
Standard monitor OS [03.01.**]
Standard monitor OS [03.00.**]
Standard monitor OS [01.01**]
Standard monitor OS [02.04.**]
Boot OS [G]
Standard monitor OS [03.02.**]
Standard monitor OS [03.02.**]
Extended function OS
Stroke Standard Font [03.03.**]
Option OS
Stroke Font(JPN) [03.03.**]
Standard monitor OS [02.02.**]
Option OS
Standard Font (China Big5)
[02.02.**]
GOT internal device
System alarm information, printer status information, and GT SoftGOT1000 end device are added.
2.27D
Standard monitor OS [02.04.**]
The devices for the trigger buffer of the
MES interface are added.
2.47Z
Standard monitor OS [03.02.**]
Option OS
MES Interface [03.02.**]
GOT Type
Supporting vertical installation type display
2.18U
Standard monitor OS [02.02.**]
Screen switching function
"ON" and "OFF" can be set.
2.43V
Standard monitor OS [03.01.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 23
Item Description
Station No.
Switching Function
Designation of the channel No. for which station No. is switched is possible.
Language
Switching Device
Language switching device can be used.
Password Setting
System information
Security
GOT Setup
Clock Setting
Startup Logo
Handy GOT
Setting
Dialog window
Password can be set for the connection of motion controller and servo amplifier.
System information of report function and print are added.
D drive automatic recovery status notification signal is added.
System information regarding B drive has been added.
The name [Password] is changed to
[Security] in the system environment.
Enables setting the operator authentication.
In clock management, both adjust and broadcast can be set.
Data save device of MELSEC-Q / QnA ladder monitor data can be set at GT
Designer2.
Automatic program read at the start of ladder monitor for MELSEC-Q/QnA/
Priority Level Comment can be set.
Time setting for call key ON until the start up of utility can be set (for 1-point pressing).
Alarm can be set to be displayed in system language switching or battery drops.
Enables the backup/restore setting.
Enables the setting for monitoring local devices.
Enables setting the drive for collectively reading comment data.
Designation of the channel No. used for adjusting and broadcasting is possible.
Function for setting any screen for the
GOT startup screen
Setting of the grip switch LED of handy
GOT
System messages to be displayed on
GOT can be customized or created by the user.
Version of GT
Designer2
2.18U
Version of OS
Standard monitor OS [02.02.**]
2.00A
2.18U
2.18U
2.27D
2.32J
2.43V
2.58L
2.58L
2.18U
2.18U
2.43V
2.18U
2.27D
2.58L
2.18U
2.09K
2.18U
2.27D
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.03.**]
Extended function OS
Operator authentication [03.03.**]
Standard monitor OS [02.02.**]
-
-
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
-
Standard monitor OS [02.02.**]
Standard monitor OS [01.02.**]
Boot OS [01.02.**.C]
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
App - 24
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Item
Operation log
Comment
Part
Key Window
Object rename
Lamp
Touch switch
Description
Function to save the GOT operation performed by the user as a history
Function for converting multiple files
The binary format file output can be converted to CSV/Unicode format file by external control.
Version of GT
Designer2
2.32J
2.43V
Version of OS
Standard monitor OS [03.00.**]
Option OS
Operation Log [03.00.**]
-
2.43V
Standard monitor OS [03.01.**]
Enables saving the operation log for the operator authentication.
Comment group can be used.
Enables setting the background color of the figures in the Parts Editor screen.
User defined key window display can be switched in synchronization with the language switching device.
In the user defined key window, input range (maximum value) and input range
(minimum value) are displayed.
Function to allow setting of object name
Windows fonts applicable
Stroke font applicable
Figure created as a part can be used to a lamp.
[Comment Group] can be used.
Enables specifying the transparent color of a figure when using an image file as a figure.
Windows fonts applicable
Stroke font applicable
Figure created as a part can be used to a touch switch.
Data change switch can be used.
[Comment Group] can be used.
[Adjust Text Size] setting is possible.
Auto repeat can be used.
The toutch switch on the ladder monitor with device search function can be used.
[PX Developer Function call] is added to
[Switch Action] of the special function switch.
2.58L
2.00A
2.18U
2.47Z
2.18U
2.18U
2.32J
2.09K
2.43V
2.43V
2.43V
2.47Z
2.09K
2.43V
2.43V
2.32J
2.43V
2.43V
2.43V
2.43V
2.47Z
Standard monitor OS [03.03.**]
Option OS
Operation Log [03.03.**]
Extended function OS
Operator authentication [03.03.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
-
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [01.02.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.02.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 25
Item Description
Touch switch
Numerical Display/
Numerical input
Enables specifying the transparent color of a figure when using an image file as a figure.
[FX List Monitor], [Operator Information
Management], [Log-in/Log-out (Operator
Authentication)], [Password Change
(Operator Authentication)], and [Backup/
Restore] are added to [Switch Action] of the special function switch.
The name [Password] is changed to
[Password (Security Level)] in [Switch
Action] of the special function switch.
Setting to display input value when entering the value at input target object position is possible.
Format String setting is possible.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Function to store NULL (0x00) at the end of input characters
Version of GT
Designer2
2.47Z
2.58L
2.32J
2.43V
2.43V
2.18U
2.18U
2.27D
Version of OS
Standard monitor OS [03.02.**]
Standard monitor OS[03.03.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Option OS
KANA KANJI (JP) [02.02.**]
Standard monitor OS [02.04.**]
Function to convert characters input in
Kana into Kanji
ASCII Display /
ASCII Input
Data List
Comment Display
User alarm
Alarm history
Alignment setting is added.
Setting for displaying an input value at the input target object position is possible.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Number of alarms settable for GT11 is extended to the same as GT15 (Up to
8192 alarms).
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Number of alarms settable for GT11 is extended to the same as GT15 (Up to
3072 alarms).
Function to save alarm history data to the
A drive (standard CF card) for GT11
Function to display the cursor by touching an alarm, and function to output the corresponding comment No. to a device
2.32J
2.43V
2.43V
2.43V
2.27D
2.43V
2.27D
2.27D
2.32J
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
App - 26
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Advanced Alarm
Parts Display/
Parts Movement
Panelmeter
Level
Item
Trend graph
Line graph
Bar graph
Statistics graph
Description
Function for detecting alarm even at the fall of bit device with Advanced User
Alarm
Function to display a cursor by touching an alarm and to output the corresponding comment No. to a device.
The binary format file output can be converted to CSV/Unicode format file by external control.
Function for using BMP/JPEG data in memory card as parts
Settings for BMP/JPEG file parts can be made on each object.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Enables specifying the transparent color of a figure when using an image file as a figure.
Windows fonts applicable
Stroke font applicable
Up to 101 points can be set for scale, value number.
Meter Attribute and Core can be set.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
When Bit Trigger is not met, whether to enable "Hold Display" can be selected.
Version of GT
Designer2
2.09K
2.43V
2.43V
2.09K
2.43V
2.43V
2.47Z
2.09K
2.43V
2.27D
2.43V
2.43V
2.27D
2.32J
2.27D
2.32J
2.43V
2.27D
2.32J
2.43V
2.27D
2.32J
2.43V
Version of OS
Standard monitor OS [01.02.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [01.02.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.02.**]
Standard monitor OS [01.02.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.01.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 27
Historical Trend
Graph
Item
Scatter graph
Time Action
Logging Function
Recipe function
Description
Up to 101 points can be set for scale, value number.
Function to collect data only when display trigger is met is added.
Function to display the data collected by the logging function in trend graph format
Second specification and external control are possible.
Version of GT
Designer2
2.27D
Version of OS
Standard monitor OS [02.04.**]
2.32J
2.18U
2.43V
Standard monitor OS [03.00.**]
Standard monitor OS [02.01.**]
Standard monitor OS [03.01.**]
Function to collect and accumulate device values
2.18U
2.43V
Standard monitor OS [02.02.**]
Option OS
Logging [02.02.**]
Function for converting multiple files
The binary/CSV/Unicode format files output can be stored to another folder by external control.
Number of devices settable for one recipe in GT11 is extended to the same as GT15
(Up to 8192 devices).
2.43V
2.27D
Standard monitor OS [03.01.**]
Function to save recipe data of GT11 in
CSV file format
Function to save recipe data to the A drive
(standard CF card) for GT11
The extended function of the existing recipe function
2.27D
2.27D
2.09K
2.43V
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [02.04.**]
Option OS
Recipe [02.04.**]
Standard monitor OS [01.02.**]
Option OS
Advanced recipe [01.02.**]
-
Advanced Recipe
Function for converting multiple files
The binary format file output can be converted to CSV/Unicode format file by external control.
2.43V
Standard monitor OS [03.01.**]
Report function
Hard copy function
Compatible with the printer output
Thumbnail Output can be set.
Operation panel function
Sound output function
The number of records that can be set is changed to 2000.
Function to print the colleted data
Enables setting the operation panel.
Enables setting the sound output.
2.58L
2.27D
2.27D
2.43V
2.58L
2.58L
GT
15
GT Soft
GOT1000
GT
11
Standard monitor OS [03.03.**]
Option OS
Advanced Recipe [03.03.**]
Standard monitor OS [02.04.**]
Extended function OS
Report [02.04.**]
Standard monitor OS [02.04.**]
Extended function OS
Printer [02.04.**]
Standard monitor OS [03.01.**]
Extended function OS
External I/O / Operation Panel
[03.03.**]
Extended function OS
Sound Output [03.03.**]
(Continued to next page)
App - 28
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Item
Barcode
Video display
Description
Function for loading the data read with bar cord reader to PLC CPU
Number of settable devices is extended from 32 to 1024 points.
Space (0x20) or NULL (0x00) can be selected for blank device.
Function to display an image taken by a video camera on the GOT
Version of GT
Designer2
2.09K
Version of OS
Standard monitor OS [01.00.**]
2.27D
2.27D
2.32J
2.32J
Standard monitor OS [02.04.**]
Standard monitor OS [02.04.**]
Standard monitor OS [03.00.**]
Extended function OS
Video/RGB [03.00.**]
Standard monitor OS [03.00.**]
Extended function OS
Video/RGB [03.00.**]
RGB display
Function to display the personal computer screen on the GOT
Set overlay screen
Test function
Number of screens that can be called on
GT11 is extended to the same as GT15
(Up to 2047 screens).
Screen calling setting with dragging is possible.
Specifying of placement position (Front/
Back) for the basic and called screens is possible.
[Disable background colors of overlay screen when setting an overlay screen] can be set.
Function for changing device value with displaying test window.
Project Script
Function to execute scripts in unit of project file
Screen Script
Object Script
2.27D
2.43V
2.43V
2.58L
2.09K
2.00A
2.18U
2.00A
2.18U
2.18U
Standard monitor OS [02.04.**]
-
Standard monitor OS [03.01.**]
Standard monitor OS [03.03.**]
Standard monitor OS [02.02.**]
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Standard monitor OS [01.00.**]
Standard monitor OS [02.02.**]
Option OS
Object Script [02.02.**]
Key Code
Function to execute scripts in unit of screen
Function to execute scripts in unit of object
Key codes for increment key and decrement key are added.
Key code for historical trend graph is added.
Key code used for Kana Kanji conversion is added.
Key codes for user ID ascending/ descending order movement of cursor are added.
2.18U
2.18U
2.18U
2.27D
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.02.**]
Standard monitor OS [02.04.**]
GT
15
GT Soft
GOT1000
GT
11
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 29
5
Other functions added
Item Description
Utility
Network unit status display
GOT data package acquisition
Displays details in OS information, project information, alarm information, hard copy information and advance recipe information properties.
Function to display the status of
MELSECNET/H communication unit and
CC-Link communication unit
Function for copying the installed OS or data in the GOT main unit to the memory card
Unlimited installation of extended function
OSs and option
OSs
Built-in option function board
Extended function OS and option OS can be installed unlimitedly.
(Conventionally, the limit was 10.)
GT15-FNB built in the GOT is enabled.
System monitoring function
Network monitor function
Function for monitoring/testing device of
PLC CPU or buffer memory of intelligent function module
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Function to monitor the network status of
MELSECNET/H, MELSECNET/10, etc.
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Version of GT
Designer2
2.18U
2.32J
2.43V
2.18U
2.58L
2.09K
2.27D
2.18U
2.27D
Version of OS
Standard monitor OS [02.02.**]
Standard monitor OS [03.00.**]
Standard monitor OS [03.01.**]
BootOS [03.01.**.M]
BootOS [02.02.**.E]
BootOS [03.03.**.P]
Standard monitor OS [03.03.**]
Extended function OS
System monitor [01.02.**]
Function for displaying sequence program loaded to CPU on GOT
Ladder monitoring function
Supporting display of Chinese (Simplified/
Traditional), German, Korean
Supporting language switching
(Japanese/Korean) for displaying file name and title of the sequence program
Supporting the read of programs/ comments
Supporting reading comments from CF cards
Supporting monitoring local devices
2.09K
2.27D
2.27D
2.43V
2.58L
2.58L
GT
15
GT Soft
GOT1000
GT
11
Extended function OS
System monitor [02.04.**]
Option OS
Network monitor [02.02.**]
Option OS
Network monitor [02.04.**]
Option OS
Ladder monitor for MELSEC-A
[01.02.**]
Ladder monitor for MELSEC-Q
/QnA [01.02.**]
Ladder monitor for MELSEC-FX
[01.02.**]
Option OS
Ladder monitor for MELSEC-Q
/QnA [02.04.**]
Ladder monitor for MELSEC-FX
[02.04.**]
Option OS
Ladder monitor for MELSEC-
Q/QnA [02.04.**]
Option OS
Ladder monitor for MELSEC-
Q/QnA [03.01.**]
Option OS
Ladder monitor for MELSEC-
Q/QnA [03.03.**]
(Continued to next page)
App - 30
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Item Description
Intelligent module monitor function
List editor for
MELSEC-A
Function to monitor and change the data of intelligent function module buffer memory using a dedicated screen
Function for displaying/editing sequence program saved from ACPU with list mode
Function to display / edit the sequence program read out from the FXCPU in the list mode
Version of GT
Designer2
2.18U
2.09K
2.18U
List editor for
MELSEC-FX
Supporting display of Chinese (Simplified)
Servo amplifier monitor function
Q motion monitor function
CNC monitor function
Backup/restore function
Supporting display of Chinese (Simplified/
Traditional), German and Korean
(GT11 supports display of Chinese
(Simplified/Traditional) and Korean)
Function to monitor the servo amplifier and also to change parameters, execute test run, etc.
Function to execute servo monitor and parameter setting for motion controller
CPU (Q series)
Parameter setting is enabled for
Q172HCPU/Q173HCPU.
Function to monitor the MELDAS that is connected to the GOT
Function to back up setting data for controllers and to restore the data to the controllers
2.27D
2.27D
2.18U
2.18U
2.32J
2.18U
2.58L
Option OS
Option OS
Version of OS
Option OS
Intelligent module monitor [02.02.**]
Option OS
List editor for MELSEC-A [01.02.**]
Option OS
List editor for MELSEC-FX
[02.02.**]
Extended function OS
List editor for MELSEC-FX
[02.04.**]
Extended function OS
List editor for MELSEC-FX
[02.04.**]
Servo amplifier monitor [02.02.**]
Q motion monitor [02.02.**]
Standard monitor OS [03.00.**]
Option OS
CNC monitor [02.02.**]
Extended function OS
Backup/Restore [03.03.**]
Multi-channel function
Gateway function
Document display function
Function to monitor multiple controllers with a single unit of GOT
Function for monitoring each controller from one GOT/PC or sending a mail from
GOT
Supporting the FTP server function
Enables transfer of binary data by the FTP server function.
Function to display document on the GOT
Image quality adjustment for documents is possible.
2.18U
2.09K
2.18U
2.32J
2.32J
2.43V
Standard monitor OS [02.02.**]
Communication driver
Use the communication driver,
[02.02.**] or later for each connection.
Option OS
Gateway function (Mail)
[01.02.**]
Gateway function (Server, Client)
[01.02.**]
Option OS
Gateway functionFTP [02.02.**]
Option OS
Gateway (FTP) [03.00.**]
Standard monitor OS [03.00.**]
Option OS
Document Display [03.00.**]
Standard monitor OS [03.01.**]
GT
15
GT Soft
GOT1000
GT
11
(Continued to next page)
17
18
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 31
Item
MES interface function
Description
Function to execute data linkage between the control and information systems
Oracle 8i, ACCESS2000, ACCESS2003, and MSDE2000 are added to the applicable database.
The trigger buffering function is added.
Enables setting [Do not sample] for the sampling setting in the device tag settings.
Industrial SQL Server 9.0 and Microsoft
SQL Server 2005 are added as an applicable database.
Version of GT
Designer2
2.43V
Version of OS
Standard monitor OS [03.01.**]
Option OS
MES Interface [03.01.**]
2.47Z
2.58L
Standard monitor OS [03.02.**]
Option OS
MES Interface [03.02.**]
Standard monitor OS [03.03.**]
Option OS
MES Interface [03.03.**]
GT
15
GT Soft
GOT1000
GT
11
App - 32
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
Appendix 4.2 For GT10
GT Designer2 Version 2.43V or later is applicable to GT1020.
GT Designer2 Version 2.58L or later is applicable to GT1030.
1
Added GOT main unit
Target Models
GT1020-LBD, GT1020-LBD2, GT1020-LBL
GT1020-LBDW, GT1020-LBDW2, GT1020-LBLW
GT1030-LBD, GT1030-LBD2, GT1030-LBDW, GT1030-LBDW2
Version of GT
Designer2
2.43V
2.58L
2.58L
Version of OS
-
-
-
2
Added connection types
Item
Microcomputer connection
OMRON PLC connection
Allen-Bradley
PLC connection
SIEMENS PLC connection
Description
Supporting the data formats of Format 1 and
Format 2.
Supporting connection to OMRON PLC
Supporting connection to MicroLogix 1000/1200/
1500 series.
Supporting connection to SLC500 series.
Supporting connection to SIEMENS S7-200 series.
: Applicable : N/A - : Applicable (from the first version)
Version of GT
Designer2
Version of OS GT1020 GT1030
2.47Z
2.47Z
2.58L
2.58L
2.58L
Standard monitor OS [01.02.**]
Communication driver
Computer
[01.02.**]
Standard monitor OS [01.02.**]
Communication driver
OMRON SYSMAC [01.02.**]
Standard monitor OS [01.04.**]
Communication driver
AB MicroLogix [01.00.**]
Standard monitor OS [01.04.**]
Communication driver
AB SLC 500 [01.00.**]
Standard monitor OS [01.04.**]
Communication driver
SIEMENS S7-200 [01.00.**]
-
-
17
18
3
Added GT Designer2 functions
Item
Library workspace
Description
Enables setting the background color of the figures in the Library Editor screen.
Version of GT
Designer2
2.47Z
Version of OS
-
4
Added common settings/object functions
Item
ASCII input
Graph
Description
The ASCII input can be set.
The statistics bar graph can be set.
The statistics pie graph can be set.
Version of GT
Designer2
2.58L
2.58L
2.58L
Version of OS
Standard monitor OS [01.03.**]
Standard monitor OS [01.03.**]
Standard monitor OS [01.03.**]
GT1020 GT1030
-
GT1020 GT1030
-
-
-
Appendix 4 List of Functions Added by GT Designer2 Version Upgrade (For GOT1000 Series)
App - 33
INDEX
[A]
A list editor........................................................... 14-1
[B]
Backlight shutoff detection................................... 17-6
Bar code ........................................................ 2-1,2-11
Battery ..................................................... 4-2,8-8,17-4
BootOS .................................................. 9-1,13-2,16-2
Brightness/contrast adjustment ........................... 11-8
Brightness/contrast adjustment of display ........... 11-8
Buzzer volume setting ....................................... 11-10
[M]
Message indicator................................................ 18-3
[O]
Operation setting ............................................... 11-11
Option .............................................................. 2-4,8-1
Option function board ...................................... 2-1,8-5
OS file list..................................................... 13-5,16-2
OS file storage location................................ 13-1,16-2
OS installation........................................9-1,13-1,16-2
Overall configuration.............................................. 2-1
[C]
...................................................2-9,8-1,9-1,13-2,16-1
Clean ................................................................... 15-1
Cleaning of display ...................................... 15-1,17-3
Clock settings ...................................................... 12-1
Communication settings screen .......................... 10-2
Component list....................................................... 2-2
[P]
Panel cutting dimensions....................................... 6-4
Part name .............................................................. 4-1
Password ............................................................... 9-7
PC connection cable............................................ 2-11
Performance specifications.................................... 3-2
Periodic inspection............................................... 17-2
Power supply specifications................................... 3-6
Program/data control ........................................... 13-1
Project data storage location ....................... 13-1,13-5
Protective sheet .....................................2-1,8-10,17-2
[D]
Daily inspection ................................................... 17-2
Debug & self check.............................................. 14-1
Display............................................................... 14-23
Display of OS information.................................... 13-6
Display of utility screen.......................................... 9-6
Display settings ................................................... 11-1
Displaying .......................................................... 14-20
[E]
Error list ............................................................... 18-3
Error message and solution................................. 18-3
External dimensions .......................................... App-1
[F]
Features ................................................................ 1-4
[G]
General specifications ........................................... 3-1
GOT data package acquisition .......................... 13-34
GOT set up .......................................................... 11-1
GOT Start Time ................................................. 14-22
[I]
Installation ............................................................. 6-1
Invert colors ......................................................... 11-7
[L]
List of error code and error massage .................. 18-3
[R]
Required device..................................................... 2-1
Rough pre-operation procedure............................. 1-5
[S]
Screen data transfer cable................................... 2-11
Security level change............................... 11-10,11-14
Self check ............................................................ 14-3
Set up .................................................................. 11-1
Specifications......................................................... 3-1
General specifications ........................................ 3-1
Performance specifications ................................ 3-2
Power supply specifications ............................... 3-6
Stand ............................................................. 2-1,8-12
Standard monitor OS .............................9-1,13-2,16-2
System............................................................... 14-20
System alarm............................................... 17-4,18-1
System Alarm Display........................................ 14-20
System configuration ............................................. 2-1
System monitor.................................................... 14-1
[T]
Third party PLC connection cable.......................... 2-2
Time setting and display ...................................... 12-1
Troubleshooting
Troubleshooting in bus connection .................. 18-7
Index-1
[U]
Utility function list................................................... 9-2
[W]
Wiring .................................................................... 7-1
Index-2
MEMO
Index-3
WARRANTY
Please confirm the following product warranty details before using this product.
1. Gratis Warranty Term and Gratis Warranty Range
If any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company.
However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module.
[Gratis Warranty Term]
The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place. Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs.
[Gratis Warranty Range]
(1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product.
(2) Even within the gratis warranty term, repairs shall be charged for in the following cases.
1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused by the user's hardware or software design.
2. Failure caused by unapproved modifications, etc., to the product by the user.
3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided.
4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced.
5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage.
6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.
7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.
2. Onerous repair term after discontinuation of production
(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.
Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.
(2) Product supply (including repair parts) is not available after production is discontinued.
3. Overseas service
Overseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ.
4. Exclusion of loss in opportunity and secondary loss from warranty liability
Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation of damages caused by any cause found not to be the responsibility of Mitsubishi, loss in opportunity, lost profits incurred to the user or third person by Failures of Mitsubishi products, special damages and secondary damages whether foreseeable or not , compensation for accidents, and compensation for damages to products other than Mitsubishi products, replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.
5. Changes in product specifications
The specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.
6. Product application
(1) In using the Mitsubishi graphic operation terminal, the usage conditions shall be that the application will not lead to a major accident even if any problem or fault should occur in the graphic operation terminal device, and that backup and fail-safe functions are systematically provided outside of the device for any problem or fault.
(2) The Mitsubishi graphic operation terminal has been designed and manufactured for applications in general industries, etc.
Thus, applications in which the public could be affected such as in nuclear power plants and other power plants operated by respective power companies, and applications in which a special quality assurance system is required, such as for Railway companies or Public service purposes shall be excluded from the graphic operation terminal applications. In addition, applications in which human life or property that could be greatly affected, such as in aircraft, medical applications, incineration and fuel devices, manned transportation, equipment for recreation and amusement, and safety devices, shall also be excluded from the graphic operation terminal range of applications. However, in certain cases, some applications may be possible, providing the user consults their local Mitsubishi representative outlining the special requirements of the project, and providing that all parties concerned agree to the special circumstances, solely at the users discretion.
Microsoft Windows, Windows NT are registered trademarks of Microsoft Corporation in the United States and other countries.
Ethernet is a trademark of Xerox Co., Ltd. in the United States.
Other company and product names herein may be either trademarks or registered trademarks of their respective owners.