TECNOLOGIC TLK 96 S digital microprocessor-based controller Operating instructions
पीडीएफ
दस्तावेज़
विज्ञापन
विज्ञापन
TLK 96 S MICROPROCESSOR-BASED DIGITAL ELECTRONIC CONTROLLER INDEX 1 1.1 1.2 2 2.1 2.2 2.3 3 3.1 3.2 3.3 3.4 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5 6 6.1 6.2 6.3 7 7.1 7.2 7.3 OPERATING INSTRUCTIONS Vr. 01 (ENG) - 09/05 - cod.: ISTR 06874 TECNOLOGIC S.p.A. VIA INDIPENDENZA 56 27029 VIGEVANO (PV) ITALY TEL.: +39 0381 69871 FAX: +39 0381 698730 internet : http:\\www.tecnologic.it e-mail: [email protected] FOREWORD 7.4 7.5 7.6 INSTRUMENT DESCRIPTION GENERAL DESCRIPTION FRONT PANEL DESCRIPTION PROGRAMMING FAST PROGRAMMING OF SET POINTS PARAMETER PROGRAMMING PARAMETER PROTECTION USING THE PASSWORD AND PARAMETER PROGRAMMING LEVELS INFORMATION ON INSTALLATION AND USE PERMITTED USE MECHANICAL MOUNTING ELECTRICAL CONNECTIONS ELECTRICAL WIRING DIAGRAM FUNCTIONS MEASURING AND VISUALIZATION ON/OFF CONTROL NEUTRAL ZONE ON/OFF CONTROL PID CONTROL AUTOTUNING FUNCTION REACHING OF “SP1” SET POINT AT CONTROLLED SPEED (RAMP) DELAY OUTPUTS FUNCTIONS PROGRAMMABLE PARAMETERS TABLE PROBLEMS , MAINTENANCE AND GUARANTEE ERROR SIGNALLING CLEANING GUARANTEE AND REPAIRS TECHNICAL DATA ELECTRICAL DATA MECHANICAL DATA MECHANICAL DIMENSIONS, PANEL CUT-OUT AND MOUNTING FUNCTIONAL DATA MEASUREMENT RANGE TABLE INSTRUMENT ORDERING CODE 1 - INSTRUMENT DESCRIPTION 1.1 - GENERAL DESCRIPTION TLK 96 S is a digital microprocessor-based controller with ON/OFF, Neutral Zone ON/OFF, PID control and with AUTO-TUNING function for PID control. The process value is visualized on 4 red displays, while the output status is indicated by 2 LED displays. The instrument is equipped with a 3 LED programmable shift indexes and can have up to 2 outputs: relay type or can drive solid state relays type (SSR). Depending on the model required the input accept: C: Thermocouples temperature probes (J,K,S and TECNOLOGIC IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermoresistances PT100. E : Thermocouples temperature probes (J,K,S and TECNOLOGIC IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), Thermistors PTC and NTC. I : normalized analogue signals 0/4..20 mA V : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V This manual contains the information necessary for the product to be installed correctly and also instructions for its maintenance and use; we therefore recommend that the utmost attention is paid to the following instructions and to save it. This document is the exclusive property of TECNOLOGIC 1.2 - FRONT PANEL DESCRIPTION S.p.A. which forbids any reproduction and divulgation , even TLK 96 8 9 in part, of the document, unless expressly authorized. TECNOLOGIC S.p.A. reserves the right to make any formal or 10 functional changes at any moment and without any notice. Whenever a failure or a malfunction of the device may cause 7 11 OUT2 OUT1 dangerous situations for persons, thing or animals, please 5 6 remember that the plant has to be equipped with additional devices which will guarantee safety. 4 1 Tecnologic S.p.A. and its legal representatives do not assume any responsibility for any damage to people, things or animals 3 2 deriving from violation, wrong or improper use or in any case not in compliance with the instrument’s features. 1 - Key P : Used to access function programming parameters and to confirm selection. AT CNT SET TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 1 2 - Key DOWN : This is used to decrease the values to be set and to select the parameters. If the key is held down while programming parameters, the user exits the programming mode. 3 - Key UP :This is used to increase the values to be set and to select the parameters. If the key is held down, the user while programming parameters the user exits the programming mode. 4 - Key U : This can be used to activate Autotuning (see par. 4.5). When in programming mode, accessed by a password, it can be used to change the parameter programming level (see par. 2.3). 5 - Led OUT1 : indicates the state of output OUT1 6 - Led OUT2 : indicates the state of output OUT2 7 - Led SET : This shows the entry into quick setting mode and the parameter programming level in programming mode. 8 - Led AT : indicates that the Autotuning is in progress. 9 - Led v Shift index: indicates that the process value is lower than [SP1-AdE]. 10 - Led = Shift index: indicates that the process value is within the range [SP1+AdE ... SP1-AdE] 11 - Led ^ Shift index: indicates that the process value is higher than [SP1+AdE]. 2 - PROGRAMMAZIONE 2.1 - FAST PROGRAMMING OF SET POINTS Press the key P then release it and the display will show “SP 1” alternating with the set value. To change it, press the UP key to increase the value or the DOWN key to decrease it. These keys increase the value by one digit but if pressed down for more than one second, the value increase or decreases rapidly and after two seconds in the same condition, the speed increases further to all the value desired to be set quickly. The Set point “SP1" can be set at a value between the value set in par. “SP1L” and the value set in par. “SP1H”. If only Set Point 1 has been programmed, the unit will exit rapid setting mode by pressing the key P once the desired value has been set. If Set Point 2 can also be set by pressing and releasing key P again, the display will show “SP 2” alternating with the set value. To change it press the keys UP and DOWN. The Set point "SP2" can be set with a value included between the value set in par. “SP2L” and the value set in par. “SP2H”. Once the desired value has been set, the unit will exit rapid setting mode by pressing the key P. Pressing the key P allows the user to exit rapid setting mode, after visualising the last Set or automatically if no key is pressed for 15 seconds, after which time the display returns to the normal function mode. 2.2 - PARAMETERS PROGRAMMING To access the function parameters it is necessary to press key P and keep it pressed for about 3 seconds, after which time the led SET will light up, the display will show the code that identifies the first parameter and using the UP and DOWN keys it will be possible to select the parameter that the user wishes to change. Once the desired parameter has been selected by pressing the key P, the display will show the parameter code and its setting, alternately. The setting can be changed by using the UP or DOWN keys. Once the value has been set as desired, press key P again. The new value will be memorized and the display will show the abbreviation of the parameter only once more. By pressing the UP and DOWN keys, it is possible to select another parameter and to change it as described below. By pressing the UP and DOWN keys, it is therefore possible to select another parameter and change it as described To exit the programming mode, do not press any key for about 30 seconds, or keep the UP or DOWN key pressed until it exits the programming mode. If the user wishes to use this protection, he must set the password number chosen in the parameter “PASS" and exit the parameterprogramming mode. When the protection is active, in order to access the parameters press the key P and keep it pressed for about 3 seconds, after which the led SET will flash the display will show the parameter “r.PAS” and pressing the key P again, the display will show “0" . At this point, set the programmed password number using the keys UP and DOWN and press key P. If the password is correct, the display will show the code that identifies the first parameter and it will be possible to set the instrument's parameters in the same way described in the previous paragraph. The protection using passwords can be disabled by setting the par. “PASS" = OFF. The manufacturer's settings cause the password to protect all parameters. If the user desires after enabling the password using the “PASS", it is possible to make some parameters programmable without the password by using the following procedure. Access programming using the password and select the parameter you wish to make programmable without password. Once the parameter has been selected, if the led SET is turned off, it means that the parameter can be programmed using the password only (therefore it is protected) if instead it is lit up it means that the parameter can be programmed without the password too (not protected). To change the parameter visibility, press the key U and keep it pressed for about 1 sec. The led SET will change status showing the new accessibility level of the parameter (turned on =not protected; turned off = protected by a password). If the password is enabled and if some parameters have their protection removed, all the non-protected parameters will be shown when programming is accessed and the par. “r.PAS” will be shown which will allow the user to access the protected parameters. NOTE: If the password is lost, remove the instrument's power supply, press key P and reinsert power, keeping the key pressed for about 5 seconds. All parameters will be accessed in this way and it will therefore be possible to check and change the parameter “PASS". 3 - INFORMATION ON INSTALLATION AND USE 3.1 - PERMITTED USE The instrument has been projected and manufactured as a measuring and control device to be used according to EN61010-1 for the altitudes operation until 2000 ms. The use of the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures. The instrument CANNOT be used in dangerous environments (flammable or explosive) without adequate protection. The installer must ensure that EMC rules are respected, also after the instrument installation, if necessary using proper filters. Whenever a failure or a malfunction of the device may cause dangerous situations for persons, thing or animals, please remember that the plant has to be equipped with additional devices which will guarantee safety. 3.2 - MECHANICAL MOUNTING The instrument, in DIN case 96 x 96 mm, is designed for flush-in panel mounting. Make a hole 90 x 90 mm and insert the instrument, fixing it with the provided special brackets. We recommend that the gasket is mounted in order to obtain the front protection degree as declared. Avoid placing the instrument in environments with very high humidity levels or dirt that may create condensation or introduction of conductive substances into the instrument. Ensure adequate ventilation to the instrument and avoid installation 2.3 - PARAMETER PROTECTION USING THE PASSWORD AND in containers that house devices which may overheat or which may PARAMETER PROGRAMMING LEVELS cause the instrument to function at a higher temperature than the The instrument has a parameter protection function using a pass- one permitted and declared. word that can be personalized by using the par. “PASS”. TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 2 Connect the instrument as far away as possible from sources of - for normalised signals in current 0..20 mA (0.20) or 4..20 mA electromagnetic disturbances such as motors, power relays, relays, (4.20) solenoid valves, etc. - for normalised signals in tension 0..1 V (0.1), 0..5 V (0.5), 1..5 V (1.5), 0..10 V (0.10) or 2..10 V (2.10). - for normalised signals in tension 0..50 mV (0.50), 0..60 mV (0.60), 3.3 - ELECTRICAL CONNECTION Carry out the electrical wiring by connecting only one wire to each 12..60 mV (12.60). terminal, according to the following diagram, checking that the We recommend to switch on and off the instrument when these power supply is the same as that indicated on the instrument and parameters are modified, in order to obtain a correct measuring. that the load current absorption is no higher than the maximum For the instruments with input for temperature probes (tc, rtd) it’s possible to select, through par. “Unit”, the unit of measurement electricity current permitted. As the instrument is built-in equipment with permanent connection (°C, °F) and, through par. “dP” (Pt100, PTC and NTC only) the inside housing, it is not equipped with either switches or internal desired resolution (0=1°; 1=0,1°). devices to protect against overload of current: the installation will Instead, with regards to the instruments with normalised analogue include an overload protection and a two-phase circuit-breaker, input signals, it is first necessary to program the desired resolution placed as near as possible to the instrument, and located in a on par. “dP” (0=1; 1=0,1; 2=0,01; 3=0,001) and then, on par. position that can easily be reached by the user and marked as "SSC", the value that the instrument must visualise at the instrument disconnecting device which interrupts the power supply beginning of the scale (0/4 mA, 0/12 mV, 0/1 V o 0/2 V) and, on to the equipment. par. "FSC", the value that the instrument must visualise at the end It is also recommended that the supply of all the electrical circuits of the scale (20 mA, 50 mV, 60 mV, 5 V or 10 V). connected to the instrument must be protect properly, using The instrument allows for measuring calibration, which may be devices (ex. fuses) proportionate to the circulating currents. used to recalibrate the instrument according to application needs, It is strongly recommended that cables with proper insulation, by using par. “OFSt” and “rot”. according to the working voltages and temperatures, be used. Programming par. “rot”=1,000, in par. “OFSt” it is possible to set a Furthermore, the input cable of the probe has to be kept separate positive or negative offset that is simply added to the value read by from line voltage wiring. If the input cable of the probe is screened, the probe before visualisation, which remains constant for all the it has to be connected to the ground with only one side. measurements. We recommend that a check should be made that the parameters If instead, it is desired that the offset set should not be constant for are those desired and that the application functions correctly before all the measurements, it is possible to operate the calibration on connecting the outputs to the actuators so as to avoid any two points. malfunctioning that may cause irregularities in the plant that could In this case, in order to decide which values to program on par. cause damage to people, things or animals. “OFSt” and “rot”, the following formulae must be applied : “rot” = (D2-D1) / (M2-M1) “OFSt” = D2 - (“rot” x M2) 3.4 - ELECTRICAL WIRING DIAGRAM where: 0 .. .1 V 0 .. 5 0 / 6 0 m V M1 =measured value 1 0 / 2 ..1 0 V 0 / 1 .. 5 V D1 = visualisation value when the instrument measures M1 0 /4 .. 2 0 m A A C T IV E M2 =measured value 2 D2 = visualisation value when the instrument measures M2 4 .. 2 0 m A A C T IV E e x t. It then follows that the instrument will visualise : g en . DV = MV x “rot” + “OFSt” 4 . .2 0 m A where: DV = visualised value MV= measured value P A S S IV E ( 2 w ir e s ) Example 1: It is desired that the instrument visualises the value effectively measured at 20° but that, at 200°, it visualises a value P T C -N T C SUPPLY lower than 10° (190°). P t1 0 0 Therefore : M1=20 ; D1=20 ; M2=200 ; D2=190 TC “rot” = (190 - 20) / (200 - 20) = 0,944 1 2 3 4 5 6 “OFSt” = 190 - (0,944 x 200) = 1,2 Example 2: It is desired that the instrument visualises 10° whilst the TLK 96 value actually measured is 0°, but, at 500° it visualises a 50° higher value (550°). S S R :8 m A /8 V D C Therefore : M1=0 ; D1=10 ; M2=500 ; D2=550 R E L A Y S :8 A -A C 1 (3 A -A C 3 ) “rot” = (550 - 10) / (500 - 0) = 1,08 /2 5 0 V A C NO C NC NO C NC “OFSt” = 550 - (1,08 x 500) = 10 12 11 10 9 8 7 By using par. “FiL” it is possible to program time constant of the OUT1 O UT2 software filter for the input value measured, in order to reduce noise sensitivity (increasing the time of reading). 4 - FUNCTIONS If a measurement error is made, it is possible to make the outputs OUT1 and OUT2 continue to work in cycles, following the times set 4.1 - MEASURING AND VISUALIZATION in the par. “ton1” - “ton2” (activation times) and “toF1” - “toF2” Depending on the model required the input accept: (deactivation times). C: Thermocouples temperature probes (J,K,S and TECNOLOGIC If there is a probe error, the instrument activates the output for the IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), “ton" time and therefore deactivates it for the “toF" time and so on Thermoresistances PT100. as long as the error continues. E : Thermocouples temperature probes (J,K,S and TECNOLOGIC By programming “ton" = OFF the output exit in probe error status IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV), will remain turned off. Thermistors PTC and NTC. By programming “ton" to any value and “toF" = OFF the output in I : normalized analogue signals 0/4..20 mA probe error status will remain turned on. V : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V By using par. “AdE” it is possible to program the 3 led shift index Depending on the model, using par. “SEnS”, it’s possible to select functioning. the type of input probe, which can be : The lighting up of the green led = indicates that the process value - for thermocouples J (J), K (CrAL), S (S) or for infrared sensors is within the range [SP1+AdE ... SP1-AdE], the lighting up of the serie TECNOLOGIC IRTC1 with linearization J (Ir.J) or K (Ir.CA) led ^ indicates that the process value is lower than [SP1-AdE] and - for thermoresistances Pt100 IEC (Pt1) or thermistors PTC the lighting up of the led v indicates that the process value is higher KTY81-121 (Ptc) or NTC 103AT-2 (ntc) than [SP1+AdE]. OUT 12 VD C Max 20 mA TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 3 4.2 - ON/OFF CONTROL This regulation mode can be started by setting the parameter "Cont" = On.FA. and acts on the outputs OUT1 and OUT2 depending on the measurement, of the set points “SP1” and “SP2”, of the function mode “Fun1” and “Fun2”, and of the hystereses “HSE1” and “HSE2” programmed. The instrument starts up a ON/OFF regulation with asymmetric hysteresis. The regulators acts in the following way if they are inverted or if heated (“Fun"=HEAt), they deactivate the output when the process value reaches the value [SP]. To reactivate it when it goes below the value [SP - HSE]. Vice versa, in the event of direct action or cooling ("Fun"=CooL), they deactivate the output when the process value reaches the value [SP], to reactivate it when it rises above the value [SP + HSE]. The Set “SP2" can also be set as independent or dependent from the set “SP1", through the parameter "SP2C". If “SP2"is set as dependent (“SP2C" = di) the actual regulation setting of the output 2 will be [SP1+SP2]. The functioning of the outputs working in ON/OFF mode can be affected by delay functions that can be set on parameters “Ptd" and “PtS" described below. PV PV SP HSE HSE SP time time ON ON OUT off ON ON ON OUT off HSE2 HSE1 0N 0N tim e o ff 0N o ff o ff 4.4 - PID CONTROL The Single Action PID control can be obtained by programming par."Cont" = Pid and works on the output OUT1 depending on the 0N o ff tc r 1 tc r 1 0N 0N o ff o ff tc r1 tc r 1 0N 0N o ff o ff tc r 1 tc r1 0N t im e o ff tc r 1 In order to obtain good stability of the process variable, in the event of fast processes, the cycle time “tcr1” has to have a low value with a very frequent intervention of the control output. In this case use of a solid state relay (SSR) is recommended for driving the actuator. The Single Action PID control algorithm foresees the setting of the following parameters : "Pb" – Proportional Band "tcr1" – Cycle time of the output "Int" – Integral Time "rS" – Manual Reset (if “Int =0 only) "dEr" – Derivative Time “FuOC” - Fuzzy Overshoot Control This last parameter allows the variable overshoots at the start up of the process or at the changing of the Set Point to be avoided. Please remember that a low value on this parameter reduces the overshoot while a high value increase it. S P SP1 OUT 2 (co o lin g ) 0N O UT1 (H E a t) CooL - On.FA PV o ff SP1 P V 4.3 - NEUTRAL ZONE ON/OFF CONTROL The neutral zone function is used to control systems that have an element that causes positive increases (e.g. heating, humidifying etc) and an element that causes a negative increase (e.g. cooling, dehumidifying etc.). This function can be activated when there are 2 outputs and it can be obtained by programming the par. “Cont” = nr . Using this programming, the instrument excludes the parameters “SP2" , “Fun1" and “Fun2" from the function. The regulation function acts on the outputs depending on the measurement, of the Set point “SP1”, and the hystereses “HSE1” and “HSE2” that have been programmed. The regulator acts in the following way: it turns off the outputs when the process value reaches Set SP1 and activates the output OUT1 when the process value is less than [SP1-HSE1], or it turns on output OUT2 when the process value is greater than [SP1+HSE2]. Consequently the element that causes the positive increase is connected to output OUT1 while the negative increase element is connected to output OUT2. The functioning of the outputs working in neutral zone mode can be affected by delay functions that can be set on parameters “Ptd" and “PtS" described below. OUT 1 (h e a tin g ) PV off off HEAt - On.FA ON active Set Point “SP1”, on the functioning mode "Fun1” and on the instrument’s PID algorithm with two degree of freedom. In this mode, the output OUT2 works in ON/OFF mode. 2 1 3 t im e 1: Value “FuOC” OK 2: Value “FuOC” too high 3: Value “FuOC” too low 4.5 - AUTOTUNING FUNCTION The AUTOTUNING function foresees the calculation of the PID parameters through an OSCILLATING tuning cycle, which, when it ends, the parameters are memorized by the instrument and remain regular during regulation. The function calculate the following parameters automatically: “Pb” - Proportional ban “tcr1” - output cycle time “Int” - integral time “dEr” - derivative time “FuOC” - Fuzzy Overshoot Control To activate the AUTOTUNING function, proceed as follows: 1) Set the Set point “SP1" desired. 2) Set the parameter "Cont" =Pid. 3) Set the parameter "Fun1" depending on the process to be controlled by the output OUT1. 4) Set the parameter "Auto" as: = 1 - if the autotuning is to be started automatically each time the instrument is turned on. = 2 - if the autotuning is to be started automatically when the instrument is turned on the next time and, once tuning has been completed, the parameter “Auto"=OFF is set automatically. = 3 - if autotuning is started up manually, by the key U = 4 - if autotuning is to be started automatically each time the regulation set is changed. 5) Exit the parameter programming mode. 6) Connect the instrument to the controlled system. TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 4 7) Start up autotuning turning off and on the machine if “Auto" = 1 or 2, pressing the key U (suitably programmed) if “Auto" = 3, or by varying the Set value if “Auto" = 4. At this point, the Autotuning function is started up and is marked by the turning on of the led AT/CNT. The regulator starts up a series of operations on the connected system in order to calculate the most suitable PID regulation parameters. The autotuning cycle is limited to a maximum of 12 hours. If the process has not ended in 12 hours the instrument will show "noAt" . Instead, if a probe error should occur, the instrument will interrupt the cycle being carried out. The values calculated by Autotuning will be memorized automatically by the instrument at the end of the correct completion of the autotuning cycle in the parameters related to PID regulation. 4.6 - REACHING OF “SP1” SET POINT AT CONTROLLED SPEED (RAMP) It is possible to reach the set point SP1 in a predetermined time (in any case longer than the time the plant would naturally need). This could be useful in those processes (heating or chemical treatments, etc.) where the set point has to be reached gradually, in a predetermined time. The function is determined by the following parameter : "SLor" - Gradient of ramp expressed in unit/minute SV [ U n it] SP1 S Lor SLor SP1 change S P 1 V a lu e t im e [m in .] Example with start from values lower than SP 1 and with decreasing of SP 1. Note : In case of PID control, if Auto-tuning is desired whilst the ramp function is active, this will not be carried out until the tuning cycle has been completed. It is therefore recommended that Auto-tuning be started avoiding activating the ramp function and, once the tuning is finished, deactivate Auto-tuning (“Auto” = OFF), and program the desired ramp. 4.7 - DELAY IN OUTPUT ACTIVATION FUNCTION In ON/OFF type regulation modes it is possible to start up two timed controls on the output activation. The first control foresees a delay in the relative output activation according to what is set on the parameters “Ptd1” and “Ptd2”. The second control foresees an inhibition when the relative output is started up if the time set on the parameters “PtS1” has “PtS2” not been completed . These functions can be useful for avoiding frequent interventions of the outputs, especially when they control the compressors. If the regulator request is missing during the delay phase, the planned output activation is cancelled. The delay function are deactivated by programming the relative parameters = OFF. During the output switch-on delay phases, the led for the relative output involved flashes to shown the delay function is working. PV HSE SP ON ON OUT o ff P td o ff ON o ff P td Example “Ptd” with “Fun” = CooL tim e o ff P td PV HSE SP ON OUT ON o ff P tS ON o ff P tS t im e o ff P tS Example “PtS” with “Fun” = CooL In addition to these delays, it is possible to prevent the activation of all the outputs after turning on the instrument for the time set in parameter “od”.The function is deactivated for “od" = OFF. During the switch on delay phase the display shows the indication or alternates with the normal planned display screen. 5 - PROGRAMMABLE PARAMETERS TABLE Here following are described all the parameters available on the instrument. Some of them could be not present or because they are depending on the type of instrument or because they are automatically disabled as unnecessary. Par. Description Range Def. note 1 SP1L Low Set Point SP1 -1999 ÷ SP1H -1999 2 SP1H High Set Point SP1 SP1L ÷ 9999 9999 3 SP2L Low Set Point SP2 -1999 ÷ SP2H -1999 4 SP2H High Set Point SP2 SPL2 ÷ 9999 9999 in / di in 5 SP2C Set Point 2 connection: in= independent di = SP2 relative to SP1 6 SP1 Set Point SP1 SP1L ÷ SP1H 0 7 SP2 Set Point SP2 SP2L ÷ SP2H 0 input C : J 8 SEnS Probe type: J / CrAL / S / J= thermocoupled J Ir.J / Ir.CA / CrAL= termocoupled K Pt1 / 0.50 / S= thermocoupled S 0.60 / 12.60 Ir.J= Infrared Sen. IRS input E : J Ptc J / CrAL / S / Ir.CA= Infrared Sen. Ir.J / Ir.CA / IRS K Ptc / ntc / Pt1= thermoresistance 0.50 / 0.60 / Pt100 12.60 0.50= 0..50 mV input I : 0.60= 0..60 mV 4.20 0.20 / 4.20 12.60= 12..60 mV input V : 0.10 Ptc= thermistor PTC 0.1 /0.5 / 1.5 / KTY81-121 0.10 / 2.10 ntc= thermistor NTC 103-AT2 0.20= 0..20 mA 4.20= 4..20 mA 0.1= 0..1 V 0.5=0..5 V 1.5= 1..5 V 0.10= 0..10 V 2.10= 2..10 V 0 9 SSC Low scale limit in case -1999 ÷ FSC of input with V / I sign. 100 10 FSC High scale limit in case SSC ÷ 9999 of input with V / I sign. Pt1 / Ptc / ntc: 0 11 dP Number of decimal 0/1 figures norm sig.: 0÷3 °C / °F °C 12 Unit Temperature unit of measurement 13 FiL Input digital filter OFF ÷ 20.0 1.0 sec. 14 OFSt Measuring Offset -1999 ÷ 9999 0 of the 0.000 ÷ 2.000 1.000 15 rot Rotation measuring straight line 16 ton1 Activation time output OFF ÷ 99.59 OFF OUT1 for probe broken min.sec TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 5 17 toF1 Deactivation time output OUT1 for probe broken 18 ton2 Activation time output OUT2 for probe broken 19 toF2 Deactivation time output OUT2 for probe broken 20 Cont Control type: On.FA= ON/OFF nr= Neutral Zone ON/OFF Pid= PID (OUT1) 21 Fun1 Functioning mode OUT1: HEAt= Heating (reverse) CooL= Cooling (direct) 22 Fun2 Functioning mode OUT2: see “Fun1” 23 HSE1 Hysteresis OUT1 24 HSE2 Hysteresis OUT2 25 Ptd1 OUT1 delay 26 Ptd2 27 PtS1 28 PtS2 29 od 30 Auto 31 32 Pb Int 33 dEr 34 FuOc 35 tcr1 36 rS 37 SLor 38 AdE 39 PASS 40 r.PAS OFF ÷ 99.59 min.sec OFF noAt OFF ÷ 99.59 min.sec OFF ÷ 99.59 min.sec OFF ErEP On.FA / nr / Pid On.FA OFF HEAt / CooL HEAt HEAt / CooL HEAt OFF ÷ 9999 OFF ÷ 9999 OFF ÷ 99.59 min.sec OUT2 delay OFF ÷ 99.59 min.sec OUT1 delay after switch OFF ÷ 99.59 off min.sec OUT2 delay after switch OFF ÷ 99.59 off min.sec Outputs Delay at power OFF ÷ 99.59 on min.sec Autotuning Fast enable OFF / OFF = Not active 1/2/3/4 1 = Start each power on 2= Start at first power on 3= Start manually 4= Start after change Set Point Proportional band 0 ÷ 9999 Integral time OFF ÷ 9999 sec. Derivative time OFF÷ 9999 sec. Fuzzy overshoot control 0.00 ÷ 2.00 Cycle time 0.1 ÷ 130.0 sec. Manual reset -100.0÷100.0 % Gradient of SP1 ramp: 0.00 ÷ 99.99 / InF InF= Ramp not active unit/min. Shift value for the shift OFF...9999 index functioning Access Password to OFF ÷ 9999 parameter functions Access Password -1999 ÷ 9999 Request 1 1 OFF OFF OFF OFF OFF OFF 40 300 30 0.50 20.0 0.0 InF 5 OFF 6 - PROBLEMS, MAINTENANCE AND GUARANTEE 6.1 - ERROR SIGNALLING Error Reason Probe interrupted ---The measured variable uuuu is under the probe’s limits (under-range) The measured variable oooo is over the probe’s limits (over-range) Action Verify the correct connection between probe and instrument and then verify the correct functioning of the probe Auto-tuning not finished within 12 hours Possible anomaly of the EEPROM memory Check the functioning of probe and actuator and try to repeat the auto-tuning. Push key “P” 6.2 - CLEANING We recommend cleaning of the instrument with a slightly wet cloth using water and not abrasive cleaners or solvents which may damage the instrument. 6.3 - GUARANTEE AND REPAIRS The instrument is under warranty against manufacturing flaws or faulty material, that are found within 12 months from delivery date. The guarantee is limited to repairs or to the replacement of the instrument. The eventual opening of the housing, the violation of the instrument or the improper use and installation of the product will bring about the immediate withdrawal of the warranty’s effects. In the event of a faulty instrument, either within the period of warranty, or further to its expiry, please contact our sales department to obtain authorisation for sending the instrument to our company. The faulty product must be shipped to TECNOLOGIC with a detailed description of the faults found, without any fees or charge for Tecnologic, except in the event of alternative agreements. 7 - TECHNICAL DATA 7.1 - ELECTRICAL DATA Power supply: 24 VAC/VDC, 100.. 240 VAC +/- 10% Frequency AC: 50/60 Hz Power consumption: 5 VA approx. Input/s: 1 input for temperature probes: tc J,K,S ; infrared sensors TECNOLOGIC IRS J e K; RTD Pt 100 IEC; PTC KTY 81-121 (990 Ω @ 25 °C); NTC 103AT-2 (10KΩ @ 25 °C) or mV signals 0...50 mV, 0...60 mV, 12 ...60 mV or normalized signals 0/4...20 mA, 0..1 V, 0/1...5 V , 0/2...10 V. Normalized signals input impedance: 0/4..20 mA: 51 Ω; mV and V: 1 MΩ Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 250 VAC) ; or in tension to drive SSR (8mA/ 8VDC). Auxiliary supply output: 12 VDC / 20 mA Max. Electrical life for relay outputs: 100000 operat. Installation category: II Measurement category: I Protection class against electric shock: Class II for Front panel Insulation: Reinforced insulation between the low voltage part (Supply and relay outputs) and front panel; Reinforced insulation between the low voltage section (Supply and relay outputs) and the extra low voltage section (input, SSR outputs); Reinforced between power supply and relays; No insulation between input and SSR outputs. 7.2 - MECHANICAL DATA Housing: Self-extinguishing plastic, UL 94 V0 Dimensions: DIN 96 x 96 mm, depth 73 mm Weight: 250 g approx. Mounting: Flush in panel in 90 x 90 mm hole Connections: 2,5 mm 2 screw terminals block Degree of front panel protection : IP 54 mounted in panel with gasket Pollution situation: 2 Operating temperature: 0 ... 50 °C Operating humidity: 30 ... 95 RH% without condensation Storage temperature: -10 ... +60 °C TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 6 7.3 - MECHANICAL DIMENSIONS, PANEL CUT-OUT AND 7.5 - MEASURING RANGE TABLE MOUNTING [mm] INPUT “dP” = 0 9 60 12 96 0 ... 1000 °C tc J “SEnS” = J 32 ... 1832 °F 0 ... 1370 °C tc K TLK 96 “SEnS” = CrAl 32 ... 2498 °F 0 ... 1760 °C tc S OUT2 OUT1 “SEnS” = S 32 ... 3200 °F -200 ... 850 °C Pt100 (IEC) “SEnS” = Pt1 -328 ... 1562 °F -55 ... 150 °C PTC (KTY81-121) “SEnS” = Ptc -67 ... 302 °F -50 ... 110 °C NTC (103-AT2) “SEnS” = ntc -58 ... 230 °F min. 10 mm 0..20 mA “SEnS” = 0.20 4..20 mA 90 “SEnS” = 4.20 0 ... 50 mV “SEnS” = 0.50 0 ... 60 mV “SEnS” = 0.60 12 ... 60 mV “SEnS” = 12.60 -1999 ... 9999 min. 15 mm 0 ... 1 V “SEnS” = 0.1 0 ... 5 V “SEnS” = 0.5 1 ... 5 V “SEnS” = 1.5 0 ... 10 V “SEnS” = 0.10 2 ... 10 V “SEnS” = 2.10 “dP”= 1, 2, 3 ------- AT CNT ---- 88 -199.9 ... 850.0 °C -199.9 ... 999.9 °F -55.0 ... 150.0 °C -67.0 ...302.0 °F -50.0 ... 110.0 °C -58.0 ... 230.0 °F 90 55 96 SET -199.9 ... 999.9 -19.99 ... 99.99 -1.999 ... 9.999 RECOMMENDED PANEL CUTOUT PANEL + GASKET MAX 5 mm 7.6 - INSTRUMENT ORDERING CODE BRACKET TLK96 a b c d ee S a : POWER SUPPLY L = 24 VAC/VDC H = 100... 240 VAC b : INPUT C = thermocouples (J, K, S, I.R), mV, thermoresistances (Pt100) E = thermocouples (J, K, S, I.R.), mV, thermistors (PTC, NTC) I = normalized signals 0/4..20 mA V = normalized signals 0..1 V, 0/1..5 V, 0/2..10 V. BRACKET 7.4 - FUNCTIONAL FEATURES Control: ON/OFF, ON/OFF Neutral Zone, PID. Measurement range: according to the used probe (see range table) Display resolution: according to the probe used 1/0,1/0,01/0,001 Overall accuracy: +/- (0,5 % fs + 1 digit) ; tc S: +/- (1 % fs + 1 digit) Max cold junction compensation drift (in tc) : 0,1 °C/°C with operating temperature 0 ... 50 °C after warm-up of 20 min. Sampling rate: 130 ms. Sampling rate: 130 ms. Display: 4 Digit Red h 14 mm Compliance: ECC directive EMC 2004/108/CE (EN 61326), ECC directive LV 2006/95/CE (EN 61010-1) c : OUTPUT OUT1 R = Relay O = VDC for SSR d : OUTPUT OUT2 R = Relay O = VDC for SSR - = None ee : SPECIAL CODES TECNOLOGIC spa - TLK 96 S - OPERATING INSTRUCTIONS - Vr.01 - 09/05 - ISTR 06874 - PAG. 7 ">
/
डाउनलोड
बस एक दोस्ताना अनुस्मारक. आप दस्तावेज़ को यहीं देख सकते हैं. लेकिन सबसे महत्वपूर्ण बात, हमारे एआई ने इसे पहले ही पढ़ लिया है. यह जटिल चीजों को सरल शब्दों में समझा सकता है, किसी भी भाषा में आपके सवालों के जवाब दे सकता है और सबसे लंबे या सबसे जटिल दस्तावेजों को भी जल्दी से नेविगेट करने में आपकी मदद कर सकता है.
विज्ञापन