F2000TSM-CO2-S110-02 User Manual V._61


Add to my manuals
3 Pages

advertisement

F2000TSM-CO2-S110-02 User Manual V._61 | Manualzz

H - G u a r d

T M

C O 2 T r a n s m i t t e r

Part #: 65-9080

User Manual

Specifications

Power supply 24VAC/24VDC±10%

Consumption

Gas sensor

CO

2

measuring range

Accuracy@25℃(77℉),2000ppm

Warm up time for each turning-on

Dry contact output

Analog output

Storage conditions

Operation conditions

Net weight/ Dimensions

Installment standard

Approval

Version

1.0 W Max

Carbon Dioxide: Non-Dispersive Infrared Detector (NDIR)

ABC Logic Self Calibration (default: effective)

0~2,000ppm

±40ppm +3% reading

48 hours (first time), 2 minutes (operation)

<240VAC/30VDC 2A switching current (resistance load),

Four CO2 levels selectable to control the relay by jumpers

4~20mA

-40~70℃(-40~158℉) , 0~95%RH, non condensing

0~50℃(32~122℉); 0~95%RH, non condensing

180g/100mm(H)×80mm(W)×24mm(D)

65mm×65mm(2 ”×4”) wire box, or hang on a nail

CE

F2000TSM-CO2-88_1A1R-9900_61

Mounting and Wire Connection

u Notice the supply power voltage of the detector: 24VAC. Do not install the detector on voltages higher than marked on the detector. u Following step 1 to 4 in figure. 1 to remove the cover. First, prepare a flat head screwdriver and put it deep inside of the hole on the top of the transmitter housing following step 1.

Then slant the screwdriver and open the cover gently following step 2. Do not mount it near diffuser or any steam source, in direct sunlight. u Mount the wall plate first, dimensions see fig. 2. there are two dimensions available.

If there is mounting box, please follow step 5 to 8 in fig. 3; if there

’s no mounting box,

5 5.00

3. 00 please follow step 5 to 8 in fig. 4.

4 5.0 0 u

Connect wires to terminal strips (see figure 5), or you can put in the power adaptor to the

1 socket of the indicator instead of connecting terminal 1, 2. make sure wiring connection correct and secure. Following step 4 to step 1 in figure 1 to close the cover.

Figure.5

Figure.1

<240VAC/30VDC/2A

L1

L2

Line

Voltage

2 3 Figure.3

4

24VAC

Transformer

Controled device

4-20mA mA

CO

2

Common

Transformer

60.0 0

Figure.2

1 2 3 4 5

1

4 .50

8.00

2 8.0 0

Figure.3

5

6

7

Figure.4

1mm

2

6

5

Select CO2 level to control the Relay

To open the controller ’s faceplate, Connection Terminal Function there are 2 jumpers (J4 and J5) on the 1 G+ Power (+) right bottom of the circuit board. We can select the CO2 level to control the

2

3

G0

OUT

Power ground (-)

Analog output (+) relay on /off by jumpers. 4

5 ventilator

Common

Relay output

7

IAQ lndicator/Controller

开/关/ 自动

8

8

Electrical Data

24VAC/24VDC +

24VAC/24VDC

4~20mA =0~2000ppm (CO2)

<240VAC/30VDC 2A switching current (resistance load)

Jumper CO2 level

J4-disconnect; J5-disconnect 800ppm

The relay turns on /turns off

CO2>800ppm,the relay on; CO2 <700ppm,the relay off

J4-connect; J5-disconnect 1000ppm

J4-disconnect; J5-connect

J4-connect; J5-connect

1200ppm (default)

1400ppm

CO2>1,000ppm, the relay on; CO2 <900ppm,the relay off

CO2>1,200ppm, the relay on; CO2 <1,100ppm,the relay off

CO2>1,400ppm, the relay on; CO2 <1,300ppm,the relay off

Important Instructions

1. Don ’t shake or hit the CO2 indicator/controller too much in shipment or in mounting to protect the internal infrared CO2 sensor from any damage and excursion of infrared receiver.

2. When a. First use CO2 transmitter, or b. Reuse CO2 transmitter after a long time unused or c. CO2 measurement is proved to be incorrect (by comparing with the measurement of other Tongdy ’s CO2 products, or put the transmitter outdoors and its measurement is away from the range of 350ppm~450ppm, which is the normal ambient CO2 level range.)

Then let ABC Logic

TM

Self Calibration System work as follows:

Keep the CO2 transmitter energized continuously for at least 2 days to let CO2 sensor ’s ABC Logic TM

self-calibration system operate properly. After more than 2 days ’ calibration, if the measurement (indicated by the analog output) of the

CO2 transmitter still exceeds over the accuracy, you need to let it self-calibrated for a longer time. Here ’s the typical

14-day calibration solution: During a 14-day period, place the CO2 transmitter twice in outdoors or unoccupied places

2

J1

J2

J3

S1

S2

where CO2 level is around 400ppm. Each time let it be there for more than 4 hours and then check the CO2 measurement via the analog output. If the CO2 measurement is in its accuracy limit, it indicates the measurement is right.

Notice: a. Use of cellular telephones or radio transceivers with two feet of the sensor during calibration process could cause sensor interference, calibration errors and affect sensor accuracy. Please refrain from using these devices during sensor calibration.

b. When checking the analog output, please avoid breath out directly to the CO2 transmitter. It

’s better to connect the output terminals with the Extending Wires with length of more than 1 meter. When the CO2 transmitter becomes stable after more than 10 minutes turning-on, check the analog output through the extending wires. That

’s because people ’s breath influences CO2 level.

Jumpers setup for 4-20mA output (Default)

CONNECTED

DISCONNECTED

DISCONNECTED

UPPER POSITION

UPPER POSITION

Jumpers setup for 0-10 output

DISCONNECTED

DISCONNECTED

DISCONNECTED

LOWER POSITION

LOWER POSITION

Contact Information

GasTech Australia Pty Ltd

24 Baretta Rd

Wangara Western Australia 6065

Tel 1800 999 902

Fax 1800 999 903 http://www.gastech.com.au

3

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement