LYNX DM-IGSM Cellular Communicator Programming Guide
Annonce
Annonce
L Y N X D M
----
----
IIII
IIII G S M
D i i g i i t t a l l
C e l l l l u l l a r C o m m u n i i c a t t o r r
Programming Guide
K14541 9/07 Rev. A
Requires
Compass Version
1.5.8.54A
(or higher) for GSM
Downloading
Table of Contents
GENERAL INFORMATION ................................................................................................................................. 3
Using the AlarmNet Direct website .............................................................................................................................3
Using a 7720P Programming Tool ................................................................................................................................3
Programming Conventions.............................................................................................................................................4
PROGRAMMING ................................................................................................................................................... 4
ECP Mode Programming ................................................................................................................................... 4
ECP Status Codes.............................................................................................................................................................9
Exiting Programming Mode ............................................................................................................................ 10
Setting Factory Defaults...............................................................................................................................................10
REGISTRATION ..................................................................................................................................................11
Registering the LYNXDM-IGSM ....................................................................................................................11
Registering through AlarmNet Direct Website .......................................................................................................11
Using the Tamper Switch .............................................................................................................................................12
Using the Programming Tool.......................................................................................................................................12
Replacing an existing module using the programming tool..................................................................................12
Register by Phone...........................................................................................................................................................13
PROGRAMMER KEYBOARD COMMANDS ..................................................................................................14
Module Identification Displays ...................................................................................................................................14
GSM Status Displays.....................................................................................................................................................15
NETWORK DIAGNOSTICS ...............................................................................................................................16
Running Network Diagnostics on the LYNXDM-IGSM ................................................................................ 17
APPENDIX A.........................................................................................................................................................18
SUMMARY OF LED OPERATION ...................................................................................................................18
LYNXDM-IGSM Status Display Operation..............................................................................................................18
Network Connectivity Display.....................................................................................................................................19
Signal Strength (RSSI) / Mode and Status LEDs....................................................................................................19
Mode and Status Indicator Switch .............................................................................................................................19
CENTRAL STATION MESSAGES ....................................................................................................................20
IGSM DOWNLOADING ......................................................................................................................................20
General Information ......................................................................................................................................................20
GLOSSARY ............................................................................................................................................................21
- 2 -
GENERAL INFORMATION
The LYNXDM-IGSM is designed to deliver alarms via the Internet to an AlarmNet central station or via the
AlarmNet-G network, using GSM (Global System for Mobile) technology when the Internet is not available. The
LYNXDM-IGSM uses 256 bit AES (Rijndael) encryption which is required for certain government installations.
The LYNXDM-IGSM module requires an AlarmNet–i account. For new installations, please obtain the account information from the central station prior to programming this module.
The LYNXDM-IGSM can be programmed through the following methods:
• The AlarmNet Direct website
• Use of a 7720P Programming Tool
Using the AlarmNet Direct website
To program the module via the website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx
If you are not signed up for this service, click on “Dealer Sign-Up”. Log in and follow the on-screen prompts.
Please have the following information available when programming the module:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on the outside of box and on label inside module)
5. After programming is complete, you must transfer the data to the module and the module must be registered. Refer to the Registration section for further instructions.
Using a 7720P Programming Tool
Connect the 7720P Programming Tool as shown in Figure 1. The LYNXDM-IGSM powers the 7720P
Programming Tool via the programming jack, and automatically senses the presence of the 7720P when it is plugged in.
Xmit
Shift
BS / ESC
7720 PROGRAMMING TOOL
A
B C
1 2 3
/
N / Y
Shift
D
4
S
7
Space
E
5
T
8
0
F
6
X
9
Enter
#
7720P
PROGRAMMING
JACK
TB1
TAMPER
SWITCH
LEDs
INTERNAL
ANTENNA
RJ45
(FOR INTERNET
CONNECTION)
M1
M0
IBS
GP
MODE AND STATUS
INDICATOR SWITCH
RSSI / MODE AND
STATUS LEDs
09004-017-V0
Figure 1. Cable Connections
Each key of the 7720P has two possible functions: a normal function and a Shift function.
• To perform a normal key function, simply press the desired key.
• To perform a Shift function, press the [shift] key, and then press the appropriate key.
The prompts in this document reflect use of the 7720P Programming Tool. Table 1 lists each normal and shift key function.
- 3 -
Table 1. 7720P Normal and Shift Key (shift LED lit) Functions
1/A
2/B
3/C
4/D
5/E
6/F
7/S
8/T
9/X
SPACE
0
#/ENTER
KEY
BS/ESC
↓/↑
N/Y
SHIFT
NORMAL KEY FUNCTION
[BS]: Press to delete entry
SHIFT KEY FUNCTION
[ESC]: Press to quit program mode; also can reset programming defaults*
[↓]: Scroll down programming
[N]: Press for "NO" answer
[↑]: Scroll up programming
[Y]: Press SHIFT-Y for "YES" answer
Press before pressing a SHIFT key function. Will light SHIFT LED. LED goes out once a key is pressed. Press again for each SHIFT function desired.
[1]: For entering the number 1
[2]: For entering the number 2
[3]: For entering the number 3
[4]: For entering the number 4
[5]: For entering the number 5
[6]: For entering the number 6
[A]: For entering letter A
[B]: For entering letter B
[C]: For entering letter C
[D]: For entering letter D
[E]: For entering letter E
[F]: For entering letter F
[7]: For entering the number 7
[8]: For entering the number 8
[9]: For entering the number 9
[SPACE]: For scrolling option list
[0]: For entering the number 0
[#/ENTER]: Starts programming mode; Press to accept entries
[S]: For entering letter S
[T]: For entering letter T
[X]: For entering letter X
No SHIFT function
No SHIFT function
No SHIFT function
*Active only when the "Exit Programming Mode" prompt is displayed.
Programming Conventions
Programming is accomplished by answering a series of prompts (questions). Most prompts require only a [Y]es or [N]o response, while others require a numerical response (ID numbers, etc.).
The current value is displayed on the second line in parentheses ( ). A "?" indicates an invalid entry.
Use the [ENTER] key to accept the current entry and proceed to the next prompt. If the entered value is invalid, pressing [ENTER] re-displays the prompt; the next prompt is not displayed until a valid answer is entered.
Use the up/down arrow keys to scroll through the programming questions without changing any values. Press the [ESC] key to go to the end of the list of questions.
PROGRAMMING
ECP Mode Programming
The LYNXDM-IGSM supports ECP messaging to communicate with the control panel. LRR-enabled control panels send Contact ID format alarms to the LYNXDM-IGSM directly on the 4-wire console bus. Refer to Table
2 for LYNXDM-IGSM programming and follow the prompts.
Press the [ENTER] key to begin programming.
NOTE: The central station can remotely block access to local device programming. If this has been done, the following prompt appears:
Access to Prog
Mode Denied
- 4 -
Table 2: Programming the LYNXDM-IGSM.
NOTE: The default programming values are listed in the prompts below.
1
PROMPTS
Strt Prog Mode?
(Y/N)_
ENTRY OPTIONS
[Y], [N]
DESCRIPTION
Enters programming mode.
2
Enter Password
[0-9, A-F, N, S, T,
X, Y]
If a password has been previously assigned, this prompt appears.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
The next prompt appears.
3
Program Device?
(Y/N)_
[Y], [N]
4
5
Create Password?
(Y/N)_
Change Password?
(Y/N)_
[Y], [N]
[Y], [N]
To begin programming the module, press [Y] and go to
Prompt 9: "Device Mode."
To create a password if none has been assigned, press
[N] and go to Prompt 4: "Create Password?."
To change an existing password, press [N] and go to
Prompt 5: "Change Password?."
Passwords can be used to protect account and programming information.
If no password has been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt.
If a password is desired, press [Y] and go to Prompt 6:
"Enter Password."
If a password has already been assigned, this prompt appears after pressing [N] at the "Program Device?" prompt.
Press [Y] if you want to change the password.
NOTE: To clear an existing password, without entering a new one, answer [Y] to the "Change
Password?" prompt, then press the [Enter] key when prompted for the new password and its confirmation.
6
[0-9, A-F, N, S, T,
X, Y]
7
Enter Password
Verify Password
[0-9, A-F, N, S, T,
X, Y]
This prompt is displayed if [Y] was pressed in Prompt 4 or 5.
Enter a 4-digit password (0-9, A-F, N, S, T, X, Y).
Re-enter the password as confirmation.
If the password doesn't match the first entry, the following is displayed followed by the "Exit Prog.
Mode?" prompt:
Verify Not OK
PSWD not created
8
9
Exit Prog. Mode?
(Y/N)_
Device Mode
(ECP)_
[Y], [N]
[ESC]
• ECP
• Zone Trig.
• 4204 Sourced
• 2-4204 Sourced
Otherwise, the "Exit Prog. Mode?" prompt is displayed directly.
Exits program mode.
Press [N] to go back to Prompt 3.
Press [ESC] to load factory defaults.
Refer to the Exiting Programming Mode paragraph in this section.
Press the [space] key to scroll through the modes of operation . Press [ENTER] to select ECP mode.
Setting up the Multi-Mode Feature
Multi-Mode enables users to receive e-mail notification of system events. Since the communication device is emulating a 4204 or two 4204 modules, there is no additional hardware to install.
E-mail notification is intended as a convenience for the user, and does not replace Central Station reporting of critical events (alarms, troubles, etc.).
- 5 -
Configuring Multi-Mode
The communication device emulates one or two standard 4204 relay modules for purposes of triggering events for sending e-mail reports. If "4204 Sourced" is selected, you must enable Multi-Mode Address 6 or 7 in
Programming Field *86. If "2-4204 Sourced" is selected, you must enable both.
When "4204 Sourced" is selected, the user can be notified of up to four events, and when "2-4204 Sourced" is selected, the user can be notified of up to eight system events. The Multi-Mode Address must match the address of the e-mail trigger module enabled in the LYNXR-I/ReadyGuardR-I control panel in Field *86.
Events used to send e-mail messages are defined on the Honeywell Total Connect website, and must correspond to (e-mail) event triggers programmed in the control panel as events 09-16 in field *80 Device Programming
Menu Mode.
10
11
PROMPTS
Multi Mode
(Disabled)_
Multi Mode Addr
(12)
ENTRY OPTIONS
• Disabled
• 4204 Sourced
• 2-4204 Sourced
[01-30]
DESCRIPTION
Enable if you want system events sent by e-mail to the user. Select "4204 Sourced" to send up to four events, or
"2-4204 Sourced" to send eight events.
Disable for normal alarm processing and go to Prompt
12 "Primary City ID" prompt.
This address must be programmed if using the Multi-
Mode (e-mail notification) feature. The device address must be unique from the normal LRR Device Address and the Keypad Address used for Remote Access.
Multi-Mode uses address(es) 6 and/or 7, which must also be enabled in the control panel.
1. Account information is provided by the central station administrator.
2. The LYNXR-I Series Controls do not support second account reporting.
12
13
14
15
16
Primary City ID
(??)_
Primary CS ID
(???)
Primary Sub ID
(????)
En. 2 nd
(N)_
CS Y/N
Device Address
(03)_
[01-99]
[01-FE]
[0001-9999]
[Y], [N]
[01-30]
Enter the 2-digit primary city ID, 01-99 (decimal).
Enter the 2-digit primary central station ID number,
01-FE (HEX).
Enter the 4-digit subscriber account number, 0001-
9999 (decimal).
Not used with LYNXR-I Series Controls. Select [N]
The LYNXDM-IGSM communicates with the panel as a
Long Range Radio (LRR) device. Enter ECP device address 03.
NOTE: When programming the control, enable the LRR output.
Setting up the Remote Access Feature
Remote Access enables the user to remotely control the security system using a standard web browser.
To Enable Remote Access:
• Remote Access must be enabled during account programming on the AlarmNet Direct website by selecting
"Enabled" at the Remote Access prompt.
• A keypad address of "1" must be enabled in the communication device in order for the communication device to talk to the control panel.
To Select the User Interface:
This option is selected during account programming from the Alarmnet Direct website and follows the "Keypad
Address" prompt. Select “LYNX Keypad”.
- 6 -
17
PROMPTS
Remote Access Y/N
(N)_
18
19
Keypad Address
(28)_
Supervision
(24 Hours)_
20
GSM Rollover Y/N
(Y)_
21
GSM 24Hr Tst Y/N
(N)_
22
Old Alarm Time
(10 Minutes)_
23
IP Flt Time
(60 mins)_
24
GSM Flt Time
(60 mins)_
25
Notify Panel Of_
(Neither Fault)
ENTRY OPTIONS
[Y], [N]
[01-30]
• 30 Day
• 24 Hour
• None
[Y] , [N]
[Y], [N]
DESCRIPTION
Press [Y] to allow the end user to access their system via a website. Availability of this service is controlled by the dealer via the web-based programming tool on the AlarmNet Direct website.
Must be programmed if using the Remote Access feature.
Enter the appropriate device address.
NOTE: This address must be set to “1”.
The AlarmNet network must hear at least one supervisory message from the module during this supervision period; otherwise, AlarmNet notifies the central station that a communication failure has occurred. (If the supervision period is changed after registration, you must re-register the module.)
Press the [space] key to scroll through choices.
UL NOTE: Must be set to 24 hour.
If enabled, all messages (including AlarmNet network supervisory messages) are sent over the GSM network in the event of an Internet failure.
If disabled, all messages (except AlarmNet network supervisory messages) are sent automatically over the
GSM network in the event of an Internet failure.
If enabled, the LYNXDM-IGSM sends a message once a day to verify radio operation. A "secondary communication path loss" message is generated if the message is not successfully delivered.
UL NOTE: Must be set to Y.
Sets how long an undeliverable alarm is retried for delivery to the central station. If the message is not validated, it is retried until the old alarm time is reached or the message is validated.
Press the [space] key to scroll through choices.
UL NOTE: Must be 10 minutes.
• 10 Minutes
• 15 Minutes
• 30 Minutes
• 1 Hour
• 2 Hours
• 4 Hours
• 8 Hours
• 12 Hours
• 24 Hours
[01-99]
[01-99]
In the event there is a loss of contact with the network over the Ethernet connection, enter the time delay (in minutes) before the LYNXDM-IGSM notifies the central station. IP failure will always be sent to the central station as Primary Communication Path
Failure.
UL NOTE: Must be one (01) minute.
In the event that the module detects a communication path failure, enter the time delay (in minutes) before the LYNXDM-IGSM notifies the central station. A
GSM failure will always be sent to the central station as a Secondary Communication Path Failure.
UL NOTE: Must be one (01) minute. fault] only notify the control panel if both communication
[Both IP and paths fail, but will always send notification of either
GSM Faults] failure to the central station.
NOTE: The fault relay output will be triggered only if "Both IP and GSM Faults" is selected.
Press the [space] key to scroll through choices.
UL NOTE: Must be set to “Both IP and GSM Faults”.
- 7 -
26
27
28
29
30
31
PROMPTS
Flt Rel ON Y/N
(N)_
Enable Zn6 Y/N
(N)_
Enable Zn7 Y/N
(N)_
Use DHCP Y/N
(Y)_
NIC IP Address:
255.255.255.255_
Subnet Mask:
255.255.255.255_
32
Gateway IP Addr:
255.255.255.255_
33
DNS Serv IP Addr:
255.255.255.255_
34
Enable Pwr Save
(Y)_
35
Review? Y/N
ENTRY OPTIONS
[Y], [N]
[Y], [N]
[Y], [N]
DESCRIPTION
Not used with LYNXR-I Series Controls Select [N].
Not used with LYNXR-I Series Controls Select [N].
Not used with LYNXR-I Series Controls Select [N].
[Y], [N]
12 digit: xxx.xxx.xxx.xxx
12 digit: xxx.xxx.xxx.xxx
12 digit: xxx.xxx.xxx.xxx
[0.0.0.0.] = not used
12 digit: xxx.xxx.xxx.xxx
[0.0.0.0.] = not used
[Y], [N]
Dynamically allocates the IP addresses (recommended); then skip to Prompt 34: "Enable Pwr Save"
If [N], uses fixed IP addresses.
Enter the 4-part address for this device. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
Enter the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
Enter the 4-part address assigned to the Gateway. The
4 parts of the address must be separated by spaces
(displayed as periods in Review mode).
[Y] = review
[N] = exit
Enter the 4-part IP address assigned to the DNS
(Domain Name System) server. The 4 parts of the address must be separated by spaces (displayed as periods in Review mode).
For 24 hour UL Battery Backup requirement, this feature must be enabled, or the unit must be powered by an appropriate UL listed UPS. If connectivity problems occur with certain routers or switches disable this option.
This option is forced to [N] when Private LAN is enabled.
Reviewing Programming Mode Entries
To review the programming options (to ensure that the correct entries have been made), press [Y]. The programming prompts are displayed again. Use the up/down arrow keys to scroll through the program fields without changing any of the values. If a value requires change, simply type in the correct value. When the last field is displayed, the “Review?” prompt again appears.
To exit the programming mode, press [N] in response to the "Review?" prompt, and refer to Exiting
Programming Mode paragraph at the end of this section.
- 8 -
ECP Status Codes
The LYNXDM-IGSM sends status messages to the control panels for power and network connectivity failures.
The LYNXR-I will display “FAULT 103” if any of the events listed below should occur. In addition, the Contact
ID codes (listed in Appendix A) for these conditions are sent to the central station by the module.
• Control panel loses communication with LYNXDM-IGSM.
• LYNXDM-IGSM lost contact with AlarmNet.
• LYNXDM-IGSM is not registered; account not activated.
• LYNXDM-IGSM shutdown.
- 9 -
Exiting Programming Mode
To exit the programming mode, press [N] in response to the "REVIEW?" question. Then press [Y] to the "Exit
Prog Mode?" question. Upon exiting, the message “checking Root File TX Path” will be displayed, and the configuration file at the server is updated to log the changes made. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded.
If critical configuration changes were made, such as the mode of operation, the LYNXDM-IGSM will reset to ensure that the programming features are enabled.
If the file is not successfully uploaded, one of the following prompts will be displayed. Follow these steps until the upload is successful.
Display
Cannot Upload
Try Again? Y/N_
Failed to Update
Root File!
Description
GSM radio not yet initialized
AND there is no Ethernet connection.
Network problem, or you answered "N" to "Cannot Upload
Try Again?" prompt.
What to do
Wait for RSSI LEDs to be lit.
Press [Y].
Initiate the Force Server Update command by pressing the [0] key; refer to the Programmer Keyboard Commands section
.
Setting Factory Defaults
To reset the programming options to factory-default values, press [ESC] at the "Exit Prog Mode?" prompt.
Set Default?
Y/N_
Press [Y] to reset factory default values.
Press [N] to cancel this function.
If you press [Y], all programmed values are reset to the original factory settings.
PLEASE NOTE THAT THIS WILL ERASE ANY PASSWORD THAT MAY HAVE BEEN ENTERED. After pressing [Y], the Create Password prompt appears (see Programming step 4).
- 10 -
REGISTRATION
Registering the LYNXDM-IGSM
Once you have initialized and programmed the LYNXDM-IGSM, it must be registered to enable the account. An unregistered LYNXDM-IGSM is indicated on the Status Display as: Status lit, Message slow blinking, and Fault not lit.
STATUS, GREEN
MESSAGE, YELLOW
FAULT, RED
Figure 2. Unregistered LYNXDM-IGSM Status Display In Normal Operation
Throughout this document, the following key is used to describe LED state:
ON OFF FAST BLINK SLOW BLINK
7845i-GSM-014-V0
Figure 3. LED Key
Upon completion of the registration process, a LYNXDM-IGSM transmits a registration message and receives a registration validation indicating that the account is now enabled. Wait for the "Registration Success" message to appear.
The “Registration Success” message is only displayed when the 7720P Programming Tool is used for registration.
You can register the LYNXDM-IGSM by one of the following methods:
• Through the AlarmNet Direct website
• Through the use of the Tamper Switch
• Through the use of a 7720P Programming Tool
• By phone
Registering through AlarmNet Direct Website
Register the module via the website (if you are already signed up for this service), go to: https://services.alarmnet.com/AlarmNetDirect/userlogin.aspx.
Log in and follow the on-screen prompts.
If you are not signed up for this service, click on “Dealer Signup” from the login screen to gain access to the
Honeywell web-based programming.
Dealer Sign-Up Direct Link: https://services.alarmnet.com/AlarmNetDirectP_Sign-Up.
You will be instructed how to proceed upon completing the sign-up form. Only one sign-up per dealer is required.
Once an initial user is established, additional logins may be created by that user.
NOTE: Central Stations sign up by contacting AlarmNet Administration at 800-222-6525 option 3.
Please have the following information available when programming the device:
1. Primary City ID (two-digit number)
2. Primary Central Station ID (two-digit hexadecimal number)
3. Primary Subscriber ID (four-digit number)
4. MAC ID and MAC CRC number (located on outside of box and on label inside module) or MIN number of the device you are replacing.
Once module is registered, you may log out of the AlarmNet Direct website.
- 11 -
Using the Tamper Switch
Initiate the registration sequence by clicking the Tamper Switch three times.
You can monitor the registration process by viewing the Status Display. The Message (yellow) LED and the
Status (green) LED will blink slowly in unison while registration is in progress.
Once the registration has been completed successfully, the LYNXDM-IGSM enters normal operating mode; the
Status (green) LED goes out and the Message (yellow) LED is lit to indicate that the power-on / reset message is waiting to be sent. This message will appear at the receiving station as “E339 803”. The description may read
“Trouble – Exp. Mod. Reset”. If registration is not validated within 90 seconds, the LYNXDM-IGSM times out, and the (green) LED will be lit (solid).
Using the Programming Tool
The interactive registration feature allows the installer to register the LYNXDM-IGSM through a series of keyboard commands on the 7720P Programming Tool. This method of registration lets the installer monitor the registration process.
Registering …
Registration
SUCCESS
Once the installation is complete, press the [
↑↑↑↑] key on the 7720P. The registration message is sent and the unit waits for the acknowledgment.
If this is a new installation and the city, central station, and customer numbers have been correctly entered, the LYNXDM-IGSM is registered and this message is displayed. The
LYNXDM-IGSM is now in full service and available for alarm reporting to the central station.
Possible Errors
Registration BAD
Timed Out
Registration BAD
Pri Sub ID BAD
Displayed if no response to the registration request is received.
Registration BAD
2nd Sub ID BAD
Indicates the city, central station, or customer number for the labeled account(s) is not accepted. The ID information was either entered in error, or the central station failed to preauthorize programmed ID numbers with AlarmNet customer service.
Indicates the city, central station, or customer number for the Secondary account is not accepted. The ID information was either entered in error, or the central station failed to preauthorize programmed ID numbers with AlarmNet customer service.
Displayed when both primary and secondary subscriber IDs are invalid.
Registration BAD
Pri&Sec – IDs BAD
Registration BAD
Pri ID – Need PIN
Registration BAD
2nd ID – Need PIN
Registration BAD
Pri&2nd – Need PIN
Displayed if this is a repair/replacement, or an error was made in programming the Primary account information of LYNXDM-IGSM for an existing account. This prompt appears for 2 seconds. See the Replacing an existing module section below for further displays.
This prompt is displayed if this is a repair/replacement, or an error was made in programming the Secondary account information of LYNXDM-IGSM for an existing account. This prompt appears for 2 seconds. See the Replacing an existing module section below for further displays.
This prompt is displayed if this is a repair/replacement, or an error was made in programming
BOTH the Primary and Secondary account information of
LYNXDM-IGSM for an existing account. This prompt appears for 2 seconds. See the
Replacing an existing module section below for further displays.
Replacing an existing module using the programming tool
Enter PIN#
This prompt appears after pressing the down arrow [
↓↓↓↓] on the 7720P. Enter a 4-digit alphanumeric PIN number provided by your central station, your dealer or an authorized
AlarmNet representative.
NOTE: If you are replacing an existing "C Series" radio, you can enter the last four-digits of the "C Series" MIN number.
Press the [ENTER] key.
Registering …
Registration
SUCCESS
The registration message is sent and the unit waits for acknowledgement.
If the PIN is valid, the new LYNXDM-IGSM is registered and the old unit unregistered.
Additionally, AlarmNet sends a substitution alarm to the central station.
- 12 -
Registration BAD
Register by Phone
You can register the module by calling the AlarmNet Technical Assistance Center (TAC) at 1-800-222-6525.
You will need the following information:
• MAC number (found on the label).
• Subscriber information (provided by the central station), including a city code, CSID, and subscriber ID.
• When instructed to do so, triple-click the tamper switch to complete the registration.
If you entered an invalid PIN, the appropriate message is displayed depending on which account number is being replaced (see above for exact wording). The registration process is repeated.
NOTE: Each attempt causes a substitution alarm to be sent to the central station.
The Total Connect Website
Users will be able to access their systems via Honeywell's Total Connect website, once the dealer has enabled them to do so from the Alarmnet Direct website. Users can control their security system and see system status, as well as view/define other users (if using the master code), and modify e-mail notification text.
The dealer will have to initially set up the user's options on the Total Connect website to define the e-mail reports the user will receive. The events that are defined must match output (relay) triggering events programmed in the control panel. The end user will be able to add additional cell phones and PDA devices to be notified of system events by e-mail or SMS, and customize names of events to be received.
Once the dealer assigns a login name and password for the user, the user will receive a "Welcome" message with their login name and password, along with some helpful information. The customer will then be able to access the system remotely over wired Internet communicators or wireless communicators that use the GSM/GPRS channel.
For the Alarmnet Direct dealer website, go to: https://services.alarmnet.com/AlarmNetDirect
For the Honeywell Total Connect end-user website, go to: https://services.alarmnet.com/TotalConnect
- 13 -
PROGRAMMER KEYBOARD COMMANDS
Programmer keyboard commands can be used to quickly view your connectivity settings and options. Most commands require you to press the [shift] key and then the designated command key. (See the keys designated in red on the 7720P Programming Tool.)
[A]
7845IGSM x.x.xx mm/dd/yy
Software Revision
"x.x.xx" indicates the installed software Revision.
Mm/dd/yy indicates month, day and year of the revision.
Module Identification Displays
[B]
MAC xxxxxxxxxxxx
MAC CRC yyyy
[C]
[D]
SCID xxxxx xxxxx
xxxxx xxxxx
IMEI xxxxxxxx
xxxxxx x
Mon 01 Jan 2001
05:48:39 am
Physical Link
Good/Bad
NIC IP Address xxx.xxx.xxx.xxx
Subnet Mask xxx.xxx.xxx.xxx
Gateway IP Addr xxx.xxx.xxx.xxx
DNS Serv IP xxx.xxx.xxx.xxx
Encryption Test
AES Passed!
DHCP
OK
MAC Address
“xxxxxxxxxxxx” indicates the LYNXDM-IGSM's unique identification number.
"yyyy" indicates the MAC CRC number. This number is also found on the label on the module, as well as the label on the box.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the IMEI display.
SCID Display
Displays the identification number assigned to the SIM card (SCID) in this device.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
IMEI Display
Displays the identification number assigned to the GSM module in this device.
Press the [space] key to get the MAC Address.
Press the [backspace] key to go to the previous field.
Time
Retrieves the current date and time from the AlarmNet network in Greenwich
Mean Time (GMT). This display confirms that the module is in sync with network.
Network Diagnostics Display
Indicates whether the device has detected a physical connection to the internet.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the DHCP display.
IP Information Display
Displays the IP address assigned to this device.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Displays the 32-bit address mask used to indicate the portion (bits) of the IP address that is being used for the subnet address.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Displays the IP address assigned to the Gateway.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Displays the IP address assigned to the DNS (Domain Name System) server.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
Performs a self-test of the AES encryption algorithm.
Press the [space] key to go to the next field.
Press the [backspace] key to go to the previous field.
DHCP (Dynamic Host Configuration Protocol) indicates server is performing satisfactorily.
Press the [space] key to go to the Physical Link display.
Press the [backspace] key to go to the previous field.
- 14 -
GSM Status Displays
[E]
PriRSSI GPRS REG
-xxxdbm x x
Cntry Netw LAC xxx xxx xxxxx
Cell BaseSt Chan xxxxx x xxx
Second Site RSSI
-xxxdbm
[F]
[S]
[T]
Testing Gateway
Redir 1
ECP 67 Flt
xx OK
Test Msg Sent
[X]
Reset CPU Y/N
[↑↑↑↑]
(UP arrow)
[↓↓↓↓]
(DN arrow)
Registering …
Enter PIN#
GSM Status Display Screen 1
PriRSSI – Primary Site RSSI level in dbm
GPRS – GPRS Service availability where “x” can be:
“Y” if GPRS is available
“N” if GPRS is Not available
REG – Registration status from radio module where
“x” can be:
N – Not Registered
H – Registered Home
S – Searching
D – Registration Denied
R – Registered Roaming
? – Unknown Registration State
Press the [space] key to go to the next screen.
Press the [backspace] key to go to the last screen.
GSM Status Display Screen 2
Cntry – Country Code
Netw – Network Code
LAC – Local area code
Press the [space] key to get to the next screen.
Press the [backspace] key to go to the previous field.
GSM Status Display Screen 3
Cell – Base Station ID
BaseSt – Base Station Antenna Sector
Chan – Control Channel in use
Press the [space] key to go to the next screen.
Press the [backspace] key to go to the previous field.
GSM Status Display Screen 4
Secondary GSM Site RSSI level in dbm.
Press the [space] key to go to the GSM Status Display Screen 1.
Press the [backspace] key to go to the previous field.
Run Network Diagnostic Test
Performs a set of network diagnostics that tests the integrity of the links between the 7845i-GSM and the various connection points (Redirs) to AlarmNet.
Refer to: Network Diagnostics section.
System Status Displays
Displays the zone and system fault status.
Test Alarm
Sends a Test alarm to AlarmNet. Functional for a registered LYNXDM-IGSM only. If the device is not registered, a message is displayed indicating that the command cannot be executed.
Reset the LYNXDM-IGSM.
Pressing [N] returns to normal mode.
Pressing [Y] resets the device.
Registration
Registers a programmed LYNXDM-IGSM with AlarmNet
.
Registration with PIN for Replacement Module
Registers a replacement LYNXDM-IGSM with AlarmNet, once programmed, using the existing PIN #.
- 15 -
[0]
Force Server Update?
Y/N
[ENTER]
Strt Prog Mode?
Y/N_
Force Upload of Configuration File to Server
Pressing [Y] will force the device to upload its entire configuration file to the server.
Pressing [N] cancels the operation.
NOTE: If the GSM module is not initialized when you enter this command, the following screen will be displayed:
Cannot Upload
Try Later! _
Wait for the RSSI LEDs to light, indicating the GSM module has completed its initialization, and try again.
Enter Program Mode
Press [Y] to enter program mode; otherwise, press [N].
- 16 -
NETWORK DIAGNOSTICS
Running Network Diagnostics on the LYNXDM-IGSM
The network diagnostic process tests the integrity of the links between the LYNXDM-IGSM and the various connection points of AlarmNet Control that are known as "Redirs".
To initiate the network diagnostics, press the [F] key on the 7720P Programming Tool.
NOTE: The test is performed ONLY if a physical link is detected. If no physical link is detected, the test is aborted and the following is displayed:
NO PHYSICAL LINK
If a physical link is detected, the diagnostics are performed. The following shows the progression of the test:
Testing Redir 1
Testing Redir 2
Reached Gateway
Redir 1
Service OK
Testing Redir 2
Redir 2
Service OK
Testing Redir 3
Redir 3
Service OK
RDR1 RDR2 RDR3
OK OK OK
The first step of the test traces the connection to Redir 1 at AlarmNet Control.
A successful trace to Redir 1 is indicated here. See below for possible errors that may occur at this stage of testing.
The service at AlarmNet Control on Redir 1 is functioning. See below for possible errors that may occur at this stage of testing.
The first step of the test traces the connection to Redir 2 at AlarmNet Control.
The service at AlarmNet Control on Redir 2 is functioning. See below for possible errors that may occur at this stage of testing.
The first step of the test traces the connection to Redir 3 at AlarmNet Control.
The service at AlarmNet Control on Redir 3 is functioning. See below for possible errors that may occur at this stage of testing.
A summary of the tests is displayed after Redir 3 is tested. The example shows that the tests of all three connection points, or Redirs, were successful. If an error occurred at any point, the summary will display "FAIL" under the faulty Redir.
- 17 -
APPENDIX A
SUMMARY OF LED OPERATION
LYNXDM-IGSM Status Display Operation
The LYNXDM-IGSM Status Display has three LEDs used to indicate message and device status:
• STATUS, green
• MESSAGE, yellow
• FAULT, red
Each LED can have four different states - ON, OFF, FAST BLINK and SLOW BLINK.
Throughout this document, the following key is used to describe LED state:
LED COLOR
GREEN
YELLOW
RED
ALL
LED
STATUS
MESSAGE
FAULT
ON OFF FAST BLINK SLOW BLINK
7845i-GSM-014-V0
Figure 4. LED Key
Table 3. Status Display Operation
DESCRIPTION
ON – LYNXDM-IGSM is NOT registered with AlarmNet.
OFF – LYNXDM-IGSM is registered with AlarmNet.
FAST BLINK – Download session with Compass in progress.
SLOW BLINK – In unison with yellow LED – Registration in progress.
ON – Message transmission pending.
QUICK PERIODIC BLINK - Normal
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – In unison with green LED – Registration in progress.
ON – No contact with network.
OFF– Normal.
SLOW BLINK – Loss of communication with the panel (ECP fault).
FAST BLINK – No network contact AND loss of communication with the panel.
FAST BLINK – In unison with the RSSI Bar Graph LEDs – Hardware Error.
Call the AlarmNet Technical Assistance Center.
A B
STATUS, GREEN STATUS, GREEN
MESSAGE, YELLOW MESSAGE, YELLOW
FAULT, RED FAULT, RED
7845i-ENTV2-013-V0
Figure 5. A Registered LYNXDM-IGSM Status Display (A) and an Unregistered LYNXDM-IGSM Status Display in Normal Operating State (B)
1 2 3 4
STATUS, GREEN
MESSAGE, YELLOW
FAULT, RED
INTERNET LINK, YELLOW
7845GSM-018-V0
Figure 6. LED Sequence for a Registered LYNXDM-IGSM Message Transmission
- 18 -
Network Connectivity Display
The Network Connectivity LED display can only be viewed with the cover removed. It is used as a visual indication of LYNXDM-IGSM network activity. Every 15-20 seconds the LEDs turn on to indicate status. The
Network Connectivity Display consists of three LEDs that function as shown in Table 4:
LED COLOR
Table 4. Network Connectivity Display
LED LABEL
DESCRIPTION
YELLOW NETWORK
TRAFFIC
OFF – No network traffic.
1 st GREEN LINK SPEED ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.
2 nd
GREEN ETHERNET LINK ON – Ethernet link detected.
OFF – No Ethernet link detected.
FAST BLINK – Transmitting/Receiving Data.
Signal Strength (RSSI) / Mode and Status LEDs
The Signal Strength (RSSI) / Mode and Status LEDs normally display the module’s signal strength. LED 1 (red
LED on the left) will be lit to indicate that the display is in RSSI mode, and the other LEDs indicate signal strength (lowest to highest, from left to right) between the module and the receiving tower. Signal strength should be within 3-5 bars.
Mode and Status Indicator Switch
Press and hold the Mode and Status Indicator Switch to change the LED functions in order to view the mode of operation and network carrier status. When the switch is held down, LED 1 (red LED on the left) will be off, and the LEDs from left to right have the following meanings:
Table 5. LED Functions with Mode and Status Indicator Switch Depressed
Operation Modes (Table 5a) Status Indications (Table 5b)
LED 1
(red)
Off=Mode and Status indicator
LED 2
(yellow)
Operation
Mode (in combination with LED 3)
LED 3
(yellow)
Operation
Mode (in combination with LED 2)
LED 4
(green)
Not Used
(see below for specific modes and status indications)
LED 5
(green)
GPRS Service
LED 6
(green)
IGSM Module
Registration with Network
Carrier
STATUS
SLOW BLINK
NORMAL BLINK
FAST BLINK
Table 5a. Operation Modes
OPERATION
MODE
ECP
(1 st
LED 2
yellow) (2
LED 3 nd yellow)
OFF OFF
Table 5b. Status Indications
(1
LED 4 st green) (2
LED 5 nd green)
–
–
–
–
–
GPRS in use by device
(3
LED 6 rd green)
IGSM module not registered with network carrier
IGSM module registered—second site available–low signal strength
IGSM module registered—second site available–acceptable signal strength
IGSM module registered—second site available–excellent signal strength
IGSM module registered—no second site available
- 19 -
CENTRAL STATION MESSAGES
The following messages are sent to the Central Station by the LYNXDM-IGSM module for the conditions listed below.
Table 6. LYNXDM-IGSM Central Station Messages
Alarm Condition
Power On Reset
ECP Supervision
Primary Communication Path Supervision
Secondary Communication Path Supervision
Test
ECP Mode
Alarm Code
E339 C0803
E355 C0000
R350 C0951
R350 C0952
5555 5555 9
ECP Mode
Restore Code
R355 C0000
R350 C0951
R350 C0952
The control panel sends its own general code (E353) for a trouble condition.
IGSM DOWNLOADING
General Information
The LYNXDM-IGSM can be used to provide high-speed up/downloading to LYNXR-I Series control panels over the GPRS network via ECP downloading. This allows site maintenance independent of central station monitoring, and modification to sites globally.
U
Downloading may only be performed if a technician is at the site.
- 20 -
GLOSSARY
AES – Advanced Encryption Standard
DHCP – Dynamic Host Configuration Protocol, which provides a mechanism for allocating IP addresses dynamically so that addresses can be reused when hosts no longer need them.
DNS – Domain Name System, which is a distributed hierarchical naming system used to resolve domain names
(e.g., www.yahoo.com) into numerical IP addresses (e.g., 204.17.25.1.).
DSL – Digital Subscriber Line
ECP – Enhanced Console Protocol, which is a proprietary communications bus used in Honeywell control panels for wiring additional keypads and peripheral devices; consists of a four-wire data bus (power+/-, data in/out).
Gateway IP Address - A gateway (sometimes called a router) is a computer and/or software used to connect two or more networks (including incompatible networks) and translates information from one network to the other.
The Gateway IP address is the IP address for the gateway.
GPRS – (General Packet Radio Service)
GSM – Global System for Mobile communications, which is an international standard for digital mobile phone systems used for cellular communication.
IMEI – International Mobile Equipment Identity number
IP – Internet Protocol
IP Address – A unique number consisting of four parts separated by periods, sometimes called a "dotted quad.," for example: 204.17.29.11, assigned to every computer/workstation connected to the Internet. IP numbers can be
"static" (assigned and unchanging) or "dynamic," assigned via DHCP at each and every startup.
ISDN – Integrated Services Digital Network
ISP – Internet Service Provider
LAN – Local Area Network
MAC Address – Media Access Code; located on the module label.
PPPoE – Point-to-Point Protocol over Ethernet
Subnet Mask - A Subnet is a portion of a network that shares a network address with other portions of the network, and is distinguished by a subnet number. The Subnet Mask is a 32-bit address mask used in IP to indicate the bits of an IP address that are being used for the subnet address.
TCP/IP – Transmission Control Protocol / Internet protocol.
- 21 -