AP05 | User manual SIKONETZ5


Add to my manuals
56 Pages

advertisement

AP05 | User manual SIKONETZ5 | Manualzz

AP05

Absolute Position Indicator with RS485 /

SIKONETZ5 interface

User manual

269/17

Table of contents

1 General Information .................................................................................................. 6

1.1 Documentation ........................................................................................................6

1.2 Definitions ..............................................................................................................6

2 Intended use ............................................................................................................. 6

2.1 Switching on the supply voltage .................................................................................7

3 Display and control keys ............................................................................................ 7

3.1 General ...................................................................................................................7

3.2 LCD display ..............................................................................................................8

3.2.1 Extended display range ..........................................................................................8

3.3 LED display ..............................................................................................................8

3.4 Keys .......................................................................................................................8

4 Functional Description ............................................................................................... 9

4.1 Operating modes ......................................................................................................9

4.1.1 Position-bound operating modes ........................................................................... 10

4.1.1.1 Positioning ..................................................................................................... 10

4.1.1.2 Loop positioning ............................................................................................. 11

4.1.2 Alpha-numeric display operating mode ................................................................... 12

4.2 Battery buffering .................................................................................................... 13

4.3 Parameterization of the position indicator ................................................................. 13

4.3.1 Manual parameterization ...................................................................................... 13

4.3.1.1 Starting parameterization ................................................................................. 13

4.3.1.2 Value input ..................................................................................................... 14

4.3.1.3 Value selection ................................................................................................ 14

4.3.1.4 Overview of the operating menu ........................................................................ 15

4.3.1.5 "Changeable parameters" menu ......................................................................... 16

4.3.1.6 Interface parameters ........................................................................................ 16

4.3.1.7 Positioning ..................................................................................................... 16

4.3.1.8 Visualization ................................................................................................... 17

4.3.1.9 LED function ................................................................................................... 17

4.3.1.10 Device options ................................................................................................ 17

4.3.2 Parameterization via interface .............................................................................. 18

4.4 Calibration ............................................................................................................ 18

4.5 Additional system commands ................................................................................... 18

4.5.1 Device data ........................................................................................................ 18

4.5.2 Diagnosis ........................................................................................................... 18

4.5.2.1 Interface ........................................................................................................ 19

4.5.2.2 Reading the error memories .............................................................................. 20

4.5.2.3 Presentation ................................................................................................... 20

4.5.3 Restore factory settings ....................................................................................... 20

4.6 Warnings / Errors.................................................................................................... 21

4.6.1 Warnings ........................................................................................................... 21

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 2 of 56

4.6.2 Errors ................................................................................................................ 21

5 Overview of parameters ............................................................................................ 22

6 Communication via SIKONETZ 5 ................................................................................ 23

6.1 Interface ............................................................................................................... 23

6.2 Data exchange ....................................................................................................... 24

6.3 Telegram setup ....................................................................................................... 24

6.3.1 Command ........................................................................................................... 24

6.3.2 Node address ...................................................................................................... 24

6.3.3 Parameter address ............................................................................................... 25

6.3.4 Control word ...................................................................................................... 25

6.3.5 Status word ........................................................................................................ 26

6.3.6 Data .................................................................................................................. 26

6.3.7 Check sum .......................................................................................................... 27

6.4 Synchronization ..................................................................................................... 27

6.5 Error telegram ........................................................................................................ 27

6.5.1 SIKONETZ5 error codes ......................................................................................... 28

6.6 Communication errors ............................................................................................. 28

6.7 Communication monitoring ...................................................................................... 28

6.7.1 Bus-Timeout ....................................................................................................... 28

6.7.2 Programming interlock ......................................................................................... 29

6.8 Auto-ID ................................................................................................................. 29

6.9 Parameter description ............................................................................................. 30

6.9.1 00h: Note address ............................................................................................... 31

6.9.2 01h: Baud rate ................................................................................................... 31

6.9.3 02h: Bus Timeout ................................................................................................ 31

6.9.4 03h: Response parameter to a set point write access ................................................ 32

6.9.5 04h: Keys enable time: Parametrization start delay .................................................. 32

6.9.6 05h: Key function enable1: Calibration enable ......................................................... 32

6.9.7 06h: LED flashing ................................................................................................ 33

6.9.8 07h: LED3 (green right) ....................................................................................... 33

6.9.9 08h: LED2 (red left) ............................................................................................ 33

6.9.10 09h: LED1 (green left) ......................................................................................... 34

6.9.11 0Ah: Decimal places ............................................................................................ 34

6.9.12 0Bh: Display divisor (ADI) .................................................................................... 34

6.9.13 0Ch: Direction indicators (CW, CCW) ....................................................................... 35

6.9.14 0Dh: Display orientation ...................................................................................... 35

6.9.15 0Eh: Configuration programming mode ................................................................... 35

6.9.16 0Fh: PIN change ................................................................................................. 36

6.9.17 1Bh: Counting direction ....................................................................................... 36

6.9.18 1Ch: Resolution per revolution .............................................................................. 36

6.9.19 1Eh: Offset value ................................................................................................ 37

6.9.20 1Fh: Calibration value .......................................................................................... 37

6.9.21 20h: Target window1 (near field) .......................................................................... 37

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 3 of 56

6.9.22 21h: Positioning type (loop type) .......................................................................... 38

6.9.23 22h: Loop length ................................................................................................ 38

6.9.24 28h: Operating mode ........................................................................................... 39

6.9.25 30h: Display in the 2 nd

row ................................................................................... 39

6.9.26 31h: Target window2 (extended) ........................................................................... 39

6.9.27 32h: Target window2 visualization ......................................................................... 40

6.9.28 33h: Application of the display divisor (ADI application) .......................................... 40

6.9.29 34h: Formation of the differential value ................................................................. 41

6.9.30 35h: Key function enable2: Incremental measurement enable .................................... 41

6.9.31 39h: LED4 (red right)........................................................................................... 41

6.9.32 3Ah: LCD backlight flashing .................................................................................. 42

6.9.33 3Bh: LCD backlight white ..................................................................................... 42

6.9.34 3Ch: LCD backlight red ......................................................................................... 42

6.9.35 3Dh: Key function enable3: Parametrization enable via keyboard ............................... 43

6.9.36 3Eh: Acknowledgement settings ............................................................................ 43

6.9.37 3Fh: Display factor .............................................................................................. 43

6.9.38 40h: LED Bus ...................................................................................................... 44

6.9.39 63h: Battery voltage ............................................................................................ 45

6.9.40 65h: Device identification .................................................................................... 45

6.9.41 67h: Software version .......................................................................................... 45

6.9.42 80h: Number of errors .......................................................................................... 46

6.9.43 81h until 8Ah: Errors ........................................................................................... 46

6.9.44 96h: Input errors ................................................................................................ 46

6.9.45 A0h: System commands........................................................................................ 47

6.9.46 A7h: Calibration travel ......................................................................................... 47

6.9.47 A8h: Programming mode ...................................................................................... 48

6.9.48 AAh: Freeze actual value ...................................................................................... 48

6.9.49 C5h: ADC values of the sensor ............................................................................... 48

6.9.50 CAh: Bus protocol ............................................................................................... 49

6.9.51 CFh: Period counter ............................................................................................. 49

6.9.52 D0h: Response delay ............................................................................................ 49

6.9.53 D2h: Auto-ID assignment ..................................................................................... 50

6.9.54 FAh: Status word ................................................................................................. 50

6.9.55 FBh: Set point1 .................................................................................................. 50

6.9.56 FCh: Differential value ......................................................................................... 51

6.9.57 FDh: Error telegram ............................................................................................. 51

6.9.58 FEh: Position value .............................................................................................. 51

6.9.59 FFh: Set point2 ................................................................................................... 52

6.10 Examples of access ................................................................................................. 52

6.10.1 Example: Read parameter ..................................................................................... 52

6.10.2 Example: Write parameter ..................................................................................... 53

7 Communication via Service Standard Protocol ............................................................ 54

7.1 General ................................................................................................................. 54

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 4 of 56

7.2 Error number encoding ............................................................................................ 54

7.3 Service protocol commands list ................................................................................. 54

8 Text displays and their meaning ............................................................................... 55

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 5 of 56

General Information

1

1.1

1.2

2

General Information

Documentation

The following documents describe this product:

The data sheet describes the technical data, the dimensions, the pin assignments, the accessories and the order key.

The installation instructions describe the mechanical and electrical installation including all safety-relevant requirements and the associated technical specification.

The user manual for commissioning and integrating the position indicator into a fieldbus system.

These documents can also be downloaded at

http://www.siko-global.com/p/ap05

.

Additional information and guidance regarding this device can also be found there.

Definitions

If not explicitly stated otherwise, decimal values are given as figures without an extension (e. g. 1234), binary values are marked after the figure with a b (e. g. 1011b), hexadecimal values with an h (e. g. 280h).

Intended use

Absolute position indicator with hollow shaft suitable for direct shaft mounting. Actual and target values are indicated via the backlit two-row LC display. A direction indicator (arrow) is blended in if the actual value deviates from the target value including the adjustable target window. The direction of the arrow indicates the direction of shaft movement necessary to reach the target. Additionally, various visualization tasks can be realized by means of two bicolor LEDs (green and red).

The device parameters can be adjusted by means of 3 keys. You can change the set point, output the position value and adjust all device parameters via the integrated bus interface.

Scanning is magnetically-incremental. In the currentless state, scanning and saving of changes of the position value are battery-supported.

The state of charge of the replaceable battery is monitored and signified.

Display and interface are active with external power supply only.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 6 of 56

2.1

Display and control keys

Switching on the supply voltage

The AP05 will be initialized after switching on the supply voltage. A display test is executed during initialization, the LEDs are lighted consecutively and the parameters are loaded from the non-volatile memory into the RAM of the controller.

With the display still unconfigured all parameters are set to their default values. See to it that

the bus will be connected only after correct adjustment of baud rate and ID (see chapter 4.3

and chapter 6.8

). The AP05 functions with the data last parameterized.

AP05 is in the normal operating state. In this state, the display unit can be configured via keyboard/display or SIKONETZ5 interface as per the requirements of the application.

3 Display and control keys

3.1 General

The position indicator has a two-line display with special characters and three control keys.

The keys serve for position indicator parameterization and control. Two device status LEDs

(LED1) serve monitoring of positioning. One bus LED (LED2) indicates the status of bus communication.

LED1

LED2

Fig. 1: Control elements

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 7 of 56

3.2

Display and control keys

LCD display

The The display range is limited to -19999 … 99999. Values outside this range are displayed with "



".

With supply voltage applied to the position indicator with factory settings, the actual value will be displayed in the 1st row and the set point in the 2nd row. If there is no valid set point, "---" will be displayed in the 2nd row. The values displayed are determined by the operating mode.

Direction indicators (arrows) support positioning.

The battery symbol is shown with a critical or insufficient battery status. If battery voltage drops to a critical value, the battery symbol on the display will flash. If it falls below the minimum value, the symbol will glow permanently.

With incremental measurement function activated, the incremental measurement symbol

is shown.

Errors are signified by red characters.

3.2.1 Extended display range

Values up to -999999 can be displayed by means of the control word. If the relevant bit has been set and the value to be displayed is between -199999 and -999999, then the negative sign and the digit of the highest order will flash alternately. If the value range drops below -

99999, "



" will be displayed.

3.3 LED display

Device status LED (LED1):

In its basic state (factory setting) the LED display has different meanings depending on the

operating mode (see chapter 4.1

).

With the basic function of the LEDs inactivated, every LED can be controlled independently via

the control word (see chapters 6.9.8

to 6.9.10

and 6.9.31

: LEDs as well as chapter 6.3.4

).

Bus-LED (LED2)

After receiving a valid message, which addressed the device, the LED will shine yellow for the duration of 1 s.

3.4

AP05

Keys

Pressing the key enables or disables the incremental measurement function. With the

Auto-ID function, the new ID is adopted by actuating this key (see chapter 6.8

).

Pressing the key starts calibration (see chapter 4.4

) and acknowledges a pending error

(see chapter 4.6

). In the "Alphanumeric display" operating mode, the receipt of a set point is

acknowledged by this action.

Pressing the key starts the parameterization mode (see chapter 4.3

).

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 8 of 56

4

Functional Description

Functional Description

4.1 Operating modes

The following position-dependent operating modes are differentiated: Absolute position,

Differential value, Modulo and the position-independent operating mode Alpha-numeric

display.

Operating mode

Line 1

Line 2

Absolute position Differential value Modulo Alpha-numeric

Display

Actual position Actual position Actual position Set point1

Set point2 Differential value Set point2 Set point2

Table 1: Display with different operating modes

Absolute position:

Linear absolute position values are displayed.

Differential value display:

With factory setting: Differential value = actual position - set point2

Decimal places

0

1

2

3

4

Modulo display:

Position values ranging from 0° to 360° are displayed.

Using the parameter decimal places (see chapter 6.9.11

) the resolution and the modulo point

of the displayed values are set.

Display resolution

1/10°

1/100°

1/1000°

1/10000°

Value range

0°…360°

0.0°…360.0°

0.00°…360.00°

0.000°…360.000°

0.0000°…360.0000°

Table 2: Modulo display

Alphanumerische Anzeige:

Both rows can be written freely. Set point1 is received via the SIKONETZ5 parameter FBh "set point1", set point2 via parameter FFh "set point2". The data identifier must be correctly set in the relevant control word. The data identifier differentiates whether the data is interpreted

and displayed as figures or alpha-numeric characters (ASCII) (see chapter 6.3.4

).

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 9 of 56

4.1.1

Functional Description

Position-bound operating modes

The measured absolute position value is displayed, calculated depending on the APU ,

ADI ,

Decimal place

and Display factor parameters. Via the interface, the position value can be

provided to an upstream control and a set point can be specified.

4.1.1.1 Positioning

(see chapter 4.1.1.2

)

Arrows: (see parameter

0Ch: Direction indicators (CW, CCW) )

Arrows are displayed to support the user with positioning as long as the current actual

position value is outside (see parameter 20h: Target window1 (near field) ) target window1.

The direction of the arrow indicates the direction of shaft rotation in order to arrive at the set point2.

LED display: (see e. g. parameter

09h: LED1 (green left) )

With factory setting, the LED glows green as long as the actual position is within the programmed window1. When leaving target window1, the LED glows red. The shaft must be rotated in the direction of the glowing LED in order to arrive at the set point2. The red glowing LED on the right means: clockwise (cw) rotation required. Red glowing LED on the left: counter-clockwise (ccw) rotation required.

An additional target window (target window2) and an associated visualization can also be

configured (see parameter 31h: Target window2 (extended) ).

With factory settings, the LED display has the following meaning:

Operating state

There is no valid set point2.

There is no valid set point2.

LED

both

LED left

LED right

State

off off red green off red green

Meaning

Positioning disabled.

Target window not reached!

The shaft must be rotated clockwise (cw) in order to reach the target.

Target window not reached!

The shaft must be rotated counter-clockwise

(ccw) in order to reach the target.

Target window reached.

Target window not reached!

The shaft must be rotated counter-clockwise

(ccw) in order to reach the target.

Target window not reached!

The shaft must be rotated clockwise (cw) in order to reach the target.

Target window reached.

Table 3: LED display

Control word (see chapter

6.3.4

):

The set point is not displayed and positioning not monitored unless the set point2 is marked as valid in the control word.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 10 of 56

Functional Description

Status word (see chapter

6.3.5

):

Upon reaching target window1, the static and dynamic target-window-reached bits are set in the status word. The dynamic bit is deleted when leaving target window1. The user must acknowledge the static bit.

Example Position monitoring:

Parameterization:

Additionally:

Factory setting

Set point2 = 100

Positioning monitoring

LED left

LED right

95 105

-

100

+

Target window1

Fig. 2: Positioning monitoring

Example of position monitoring with additionally activated target window2 parameter:

Parameterization: Factory setting

Additionally: Target window2 = 15

Visualization target window2 = 1

Set point = 100

Positioning monitoring

LED left

LED right

Target window2

95 105

-

85

100

Target window1

Fig. 3: Positioning monitoring with target window2

115

+

4.1.1.2 Loop positioning

Target window1 is also applied to the loop length.

If the position indicator is operated on a spindle or an additional gear, the spindle or external gear backlash can be compensated by means of loop positioning. Therefore, movement towards the set point is always in the same direction. This direction of approach can be defined.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 11 of 56

Functional Description

Example:

The direction from which every target position shall be driven to is positive.

Case 1

the new position is greater than actual position:

Direct travel to the target position.

Case 2

the new position is smaller than actual position:

The position indicator's arrows show that the set point is to be overrun by the loop length.

Afterwards, the set point is approached in positive direction.

Loop length Positioning: loop +

Positioning in positive direction

Positioning in negative direction

-

Fig. 4: Positioning Loop+

Target window1

Set point

+

4.1.2 Alpha-numeric display operating mode

Two 5-digit set points can be displayed in this operating mode. With factory settings, the set

points are acknowledged by pressing the key (see chapter 3.4

and parameter 3Eh:

Acknowledgement settings ).

LCD display:

In the absence of a valid set point, the 1st row is displayed empty (blank). " --- " appears in the 2 nd

row.

A valid set point is displayed flashing until its receipt is acknowledged. If neither set point has been acknowledged, both values are acknowledged jointly by pressing the key.

LED display:

With factory settings, the LED display works according to the following table.

Operating state

There is no valid set point.

There is a valid set point.

LED1

both

State

off

LED left red green

LED right red green

Meaning

Set point1 not acknowledged

Set point1 acknowledged

Set point2 not acknowledged

Set point2 acknowledged

Table 4: LED display in the alpha-numeric display operating mode

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 12 of 56

4.2

Functional Description

Control word:

In the control word, the relevant type (number or character string) and the validity of the set point is transmitted to the display. As an additional option, the set point can be acknowledged via the control word.

Status word:

Type, validity and acknowledgement status of the set points are fed back in the status word.

Battery buffering

The battery makes possible the detection of currentless displacement. Battery life is approx. 8 years depending on the duration of battery operation (including storage) and frequency of currentless adjustments. Battery voltage is checked at intervals of approx. 5 min. If battery voltage drops below a specified value, the battery symbol will blink on the display. If the battery voltage continues to drop, will be displayed permanently. The battery should be replaced within approx. three months after the first appearance of the battery symbol. The battery can be replaced by the SIKO distribution partners or at the SIKO main factory. For battery replacement it is mandatory to follow the instructions of the installation instructions.

Status word:

The charge status of the battery is signified in the status word. Bit 11 is set when the charging voltage is critical and an error is signified with the additional bit 7 set when the battery is empty.

4.3 Parameterization of the position indicator

The position indicator can be fully parameterized via the bus interface. All parameters can also be set manually by means of the keyboard.

4.3.1 Manual parameterization

4.3.1.1 Starting parameterization

By actuating the key, the set node address and baud rate is displayed. Parameterization

starts if it is actuated for the duration of the enable time (see parameter 04h: Keys enable time: Parametrization start delay

and 3Dh: Key function enable3: Parametrization enable via keyboard ).

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 13 of 56

Functional Description

4.3.1.2 Value input

Enter values via the key and the key. Confirm values entered by pressing the key.

- decimal place selection key

- value input key

4.3.1.3 Value selection

For some parameters you can select values from a list.

Direct value input is not possible there.

Pressing the key, the value can be selected from the list. By pressing the key, the selection is confirmed.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 14 of 56

Functional Description

4.3.1.4 Overview of the operating menu

Start

Hold down the key no

Key enable time expired?

yes

Changeable parameter

chPAr

On the display:

Node address

Baud rate

1d 31

57

.6

Adjustable delay

(see chapter 6.9.5

)

PIN entry required

PIN correct?

yes

"Changeable parameters" menu

no

Device data

Read-only device data

ro

Diagnosis

DIAGn

Diagnosis

AP05

Quit

q1t

End

Fig. 5: Operating menu

All device parameters can be viewed and changed in the "Changeable parameters" ("chPAr")

submenu (see chapter 4.3.1.5

).

All fixed device data are displayed in the "Readable parameters" (Read Only = "ro") submenu

(see chapter 4.5.1

).

The "Diagnosis" ("dIAG") submenu provides various diagnostic options (see chapter 4.5.2

).

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 15 of 56

Functional Description

4.3.1.5 "Changeable parameters" menu

When choosing the "Changeable parameters" submenu, a PIN must be entered first. The factory-set PIN is "00000".

After confirming the correct PIN, you can choose among the following parameter menus.

Description

Interface parameters

Positioning

Visualization

LED function

Device options

Display



PI

11

d

PI

Table 5: "Changeable parameters" menu structure

4.3.1.6 Interface parameters

The following parameters can be set in the "Interface parameters" menu:

Description

Node address

Baud rate

Transmission protocol

Bus timeout

Reponse delay

Table 6: "Interface parameters" menu

Display

1D

d

Prtc

to

1nht

4.3.1.7 Positioning

The following parameters can be set in the "Positioning" menu:

Description

Display per revolution (APU)

Decimal plases

Display divisor (ADI)

Counting direction

Enter calibration value

Calibrate

Application Offset

Target window near field

Positioning type

Loop length

Target window far

Table 7: "Positioning" menu

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17

Display

AP

DP

ADI rott

1

1 no 

t tr1

PP

P

Page 16 of 56

Functional Description

4.3.1.8 Visualization

The following parameters can be set in the "Visualization" menu:

Description

Display orientation

Visualization target window far field

Direction indication

Display in the 2 nd row

White display backlight

Red display backlight

Display backlight blinking

Table 8: "Visualization" menu

4.3.1.9 LED function

The following parameters can be set in the "LED function" menu:

Description

LED1 green

LED1 red

LED2 green

LED2 red

LED blinking

LED3 bus

Table 9: "LED function" menu

Display

n 1 rd 1

n  rd 

A

 3

4.3.1.10 Device options

The following parameters can be set in the "Additional device options" menu:

Description

Key enable time / parameterization delay

Calibration enable

Incremental measurement enable

Type of difference calculation

Operating mode

Display factor

Application of the display divisor

Change the PIN

Load the factory setting

Display

DA

An

1nc

DI

PP

A

AD1

PI

ADP

Table 10: "Additional device options" menu

Display

D1P

1

1ndc

1



 rD

 

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 17 of 56

4.3.2

Functional Description

Parameterization via interface

The position indicator can be completely parameterized in the RS485-SIKONETZ5 interface

(see chapter 5 ).

4.4

4.5

Calibration

Two steps are required for executing calibration:

1. Write calibration value (see object 1Fh: Calibration value )

2. Execute calibration (reset) (see chapter 3.4

or object A0h: System commands with the data content 7 or object A7h: Calibration travel )

Since the measuring system is an absolute system, calibration is necessary only once with commissioning. With calibration, the calibration value is adopted for calculation of the position value. The following equation is applied in case of calibration:

Position value = 0 + calibration value + offset value

Calibration value (see object 1Fh: Calibration value )

Offset value (see object 1Eh: Offset value )

Additional system commands

4.5.1 Device data

The following values can be read in the "Device data" menu:

Description

Battery voltage

Firmware version number

Serial number

Table 11: "Device data" menu

Display

tt



ro

4.5.2 Diagnosis

The AP05 features various diagnostic options, which can be selected from the "Diagnosis" submenu. The following diagnostic options are differentiated:

Description

Interface

Reading the error memories

Presentation

Display

5

rror

Prnt

Table 12: "Diagnosis" menu

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 18 of 56

Functional Description

4.5.2.1 Interface

In interface diagnosis, bus communication can be checked in three different ways:

Scan ID

5



Setting the

ID to be checked

Display of the message received

Display of check sum

Display of the number of messages / s

00001 tP 0

00031 tP63

Subscriber with ID1 receives no massages

Red LED ON:

There is bus traffic with deviating ID.

Red LED OFF:

There is no recognizable bus traffic.

Subscriber with ID 31 receives

63 Telegrams Per Second

Geen LED: ON no

No message with this ID was heard.



.063

0

"FE." = Parameter address in hex (here FEh Actual value)

".0xx" = Read command

".x63" = Number of received telegrams per second

"0" = Data content of the request in dec.

The content of the message last heard is displayed.

Messages transmitted by the device itself cannot be displayed/ recorded.

0

00

.00

No CS errors were detected.

7

99 .99

"x" = Number of telegrams with check sum error

(here 7).

"Cxx.xx" = Ratio of faulty to the total of telegr. received (here 99.99 %)

Scan parameter

5 t

Setting the

ID to be checked

1d001

00001

Subscriber with ID 1

Setting the expected command cd 01

001

Command "01" = Write

Setting the parameter to be checked

PA

55

Parameter FFh = set point

Entry in decimal notation!

Display of the message

Scan value

Entry as before à

Additional setting of the value to be checked

5

A

Display of the message received

Fig. 6: Interface diagnosis

 .1 

500

"FF." = Parameter address in hex (here FFh set point)

".1xx" = Command (here 1 = Write)

".x 7" = Number of telegrams received (here Eh = 14d)

"500" = Data content of the telgram (decimal)

The content of the message last heard is display.

Messages transmitted by the device itself cannot be displayed/recorded.

LED OFF: no bus traffic, red: different telegr., green: telegram received.

A

00500

Value

 .1 

500

LED OFF: no bus traffic, red: different telegr., green: value received.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 19 of 56

Functional Description

4.5.2.2 Reading the error memories

Two different error histories can be output here.

The "AP05" list contains errors found by the device such as "Low battery voltage" or "Velocity exceeded".

The "bUS" list contains input or receipt errors on the interface.

With errors occurring, the error number and overall quantity are output on the upper line. The type of error appears in the lower line, with error number 1 containing the latest error. The oldest error is output with the highest error number. "noErr" appears if no errors have been detected so far.

4.5.2.3 Presentation

A fixed set point (850) is set and switched valid in the presentation mode. So, the mode of operation of the device can be presented without the need of specifying a set point via an interface.

4.5.3 Restore factory settings

There are various options for restoring the factory settings of the device:

Access

Manuell

SIKONETZ5

(see parameter A0h:

System commands )

Coding

Load

A0h

11100

Factory settings are restored

all parameters

11102 all except bus parameters

11105 only bus parameters

A

AD all parameters all except bus parameters (standard)



1

2

5 only bus parameters all parameters all except bus parameters only bus parameters

Table 13: Access to factory settings

The bus parameters are:

Display

ID

AD

Protc



Inht

Parameter address Parameter

00h Node-ID

01h Baud rate

-

02h

03h

0Eh

D0h

Protocol

Bus-Timeout

Response parameter to set point write access

Configuration programming mode

Response delay time

Table 14: Bus parameter

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 20 of 56

4.6

Functional Description

Warnings / Errors

4.6.1 Warnings

Warnings do not influence the acquisition of the absolute position value.

Warnings are deleted after removing the cause.

Possible warnings:

Battery voltage for absolute position detection is below limit

immediately exchange battery!

This warning is displayed with a blinking battery symbol . Via status word warning

messages are output via the interface (see chapter 6.3.5

and chapter 4.5.2

).

Display Bit assignment in the status word Error

flashing 11 Low battery voltage (critical)

Position value is still valid!

Table 15: Warnings

4.6.2 Errors

Error states are signalled via display (written in red or battery symbol) and interface.

To return to normal operation, the cause must be removed (see Table 17 ). Afterwards you can

acknowledge or delete the error message by pressing the key or via the interface

(see chapter 6.3.4

).

(For signaling see chapter 6.3.5

and chapter 4.5.2

)

Display

PD

Error code

SIKONETZ5

permanent 0006h

D

000Fh no

001Ah

0019h

 to

0080h

0081h

7

7

Bit assignment in the status word

11+7

12+7

12+7

12+7

Error

Low battery voltage (empty)

Tape-sensor gap exceeded

No sensor connected

Travel speed exceeded

Checksum SIKONETZ5

Timeout SIKONETZ5

Table 16: Error messages

Display

PD

Error

permanent Battery empty

Admissible speed exceeded (see installation instruction)

Possible effect

Position value not reliable

Position value not reliable

Corrective actions

Battery change + calibration travel

Reduce speed + calibration travel

Table 17: Corrective actions

A list of errors that occurred can be read in the Diagnosis/Error memory operating menu

(see chapter 4.5.2.2

).

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 21 of 56

5

Overview of parameters

Overview of parameters

Name Description

00h: Note address

01h: Baud rate

02h: Bus Timeout

03h: Response parameter to a set point write access

04h: Keys enable time:

Parametrization start delay

Node address

Baud rate of the RS485 interface

Indication of bus timeout in x100 ms

Defines the response to the command "Write set point".

Period of key actuation in order to start parametrization.

Enable calibration

32

05h: Key function enable1:

Calibration enable

06h: LED flashing

07h: LED3 (green right)

08h: LED2 (red left)

09h: LED1 (green left)

All LEDs flashing

LED green right (LED3)

LED red left (LED2)

LED green left (LED1)

32

0Ah: Decimal places

0Bh: Display divisor (ADI)

Number of decimal places.

ADI display divisor

0Ch: Direction indicators (CW, CCW) Visualization of direction indicators.

0Dh: Display orientation

0Eh: Configuration programming mode

0Fh: PIN change

Display orientation

Basic setting of programming interlock.

1Bh: Counting direction

1Ch: Resolution per revolution

PIN required for parameterization via keys and display.

Counting direction

Resolution of the measuring system.

36

1Eh: Offset value

1Fh: Calibration value

Offset value

Calibration value

20h: Target window1 (near field)

The set point has been reached when the actual value is within the target window1

21h: Positioning type (loop type)

22h: Loop length

Travel towards set point in this direction.

Loop length

28h: Operating mode

30h: Display in the 2 nd

row

Operating mode

Controls the display of the 2 display. nd

row of the

31h: Target window2 (extended)

Extended target window for easier positioning.

39

32h: Target window2 visualization

Visualization of target window2

40

ADI application

40 33h: Application of the display divisor (ADI application)

34h: Formation of the differential value

Formation of the differential value.

41

35h: Key function enable2:

Incremental measurement enable

39h: LED4 (red right)

Incremental measurement enable

LED red right (LED4)

41

41

38

38

39

39

36

36

37

37

37

34

34

35

35

35

33

33

33

34

see page

31

31

31

32

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 22 of 56

6

Communication via SIKONETZ 5

Name Description

3Ah: LCD backlight flashing

3Bh: LCD backlight white

3Ch: LCD backlight red

3Dh: Key function enable3:

Parametrization enable via keyboard

3Eh: Acknowledgement settings

Flashing LCD backlight

LCD backlight white

LCD backlight red

Parametrization enable

3Fh: Display factor

40h: LED Bus

63h: Battery voltage

65h: Device identification

67h: Software version

80h: Number of errors

81h until 8Ah: Errors

96h: Input errors

A0h: System commands

A7h: Calibration travel

A8h: Programming mode

AAh: Freeze actual value

C5h: ADC values of the sensor

CAh: Bus protocol

CFh: Period counter

D0h: Response delay

D2h: Auto-ID assignment

FAh: Status word

FBh: Set point1

FCh: Differential value

FDh: Error telegram

FEh: Position value

FFh: Set point2

Acknowledgment settings (alpha-numeric display)

Display factor (inch indication)

LED indicates valid bus traffic

Battery state of charge

43

43

44

45

SIKONETZ5 device identification (AP05 = 11)

45

Software version

45

Number of error incidents

46

Error list

Input error list

Various system commands

Starting calibration travel

Programming disable

Freeze position value

Hardware analysis

46

46

47

47

48

48

48

Setting of the communication protocol.

Hardware analysis

Delay until a SIKONETZ5 bus telegram is answered.

Automated node address assignment.

Device status

49

49

49

50

50

Set point1 (alpha-numeric display)

50

Deviation between actual and target positions.

51

Error telegram

51

Actual position

Target position

51

52

see page

42

42

42

43

Table 18: Parameter description

Communication via SIKONETZ 5

6.1

AP05

Interface

RS485 interface

Available baud rates: 19.2 kBit / 57.6 kBit (factory setting) / 115.2 kBit

No parity, 8 data bits, 1 stop bit, no handshake

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 23 of 56

6.2

Communication via SIKONETZ 5

Data exchange

The protocol functions according to the master – slave principle.

The position indicator acts as a slave. Every instance of communication must be initiated by the master. When the master has sent a command telegram, the slave sends a reply telegram.

Broadcast commands are an exception, they remain always unanswered by the slave.

The protocol is optimized for cyclical data exchange. The relevant data such as set point and actual value as well as control and status words can be transferred between master and slave by a single telegram exchange.

The parameter to be returned by the slave as a reply to the master's Write set point command can be defined via the "Write set point reply parameter".

6.3 Telegram setup

Control word (CW), status word (SW) and data are transferred in the Big-Endian format.

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address high Byte low Byte MSB

CW Data

LSB Check sum

Table 19: Command telegram (from master)

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address high Byte low Byte MSB

SW Data

LSB Check sum

Table 20: Reply telegram (from slave)

6.3.1 Command

The following access types are provided by SIKONETZ5.

Access code Meaning

00h read

01h

02h write broadcast

Description

The master requests the addressed slave to output the relevant value in a response telegram.

The master requests the addressed slave to accept the value transferred in the same telegram.

The master requests all connected slaves to execute the command transferred in the same telegram.

6.3.2 Node address

The device address can be freely set in the range of 0 to 127. The delivered devices are preset to node address 31 ex works and must be reset to the desired address to enable their

operation with multiple slaves on the SIKONETZ5 fieldbus (see parameter 00h: Note address

and chapter 6.8

).

Each address can be assigned in the fieldbus only once!

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 24 of 56

6.3.3

Communication via SIKONETZ 5

Parameter address

A distinct address is assigned to every parameter (e.g. calibration value) or functional value

(e. g. set point) (see chapter 6.9

).

6.3.4 Control word

The control word consists of 16 bits.

Control word

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

MSB High Byte Low Byte LSB

The following table lists the designations of the individual bits of the control word and their meanings.

Bit Meaning

0 reserved

1 reserved

2 Validity of set point1

3 Display range

4 Acknowledgment target window1 static

5 Error

6 With "Display" operating mode:

Acknowledgement of set point2

7 With "Display" operating mode:

Data identifier

8 reserved

9 Validity of set point2

10 With "Display" operating mode:

Acknowledgement of set point1

11 LED1 green left

12 LED3 green right

13 LED4 red right

14 LED2 red left

15 LED blinking

Value = 0

ever 0 ever 0

Value = 1

-

- invalid standard valid extended not acknowledged acknowledged not acknowledged acknowledged not acknowledged acknowledged number ever 0 invalid not acknowledged acknowledged

Off

Off

Off

Off

Off

ASCII

- valid

On

On

On

On

On

Table 21: Control word

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 25 of 56

6.3.5

Communication via SIKONETZ 5

Status word

The response to a set point write command contains a status word which was not updated yet.

The status word indicates the current status of AP05. It consists of 16 bits.

Status word

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

MSB High Byte Low Byte LSB

The following table lists the designations of the individual bits of the status word and their meanings.

Bit Meaning

0 Direction indication CW

Value= 0

Off

Value= 1

On

1

2

3

Direction indication CCW

Validity set point1

Target window2 dynamic

With "Display" operating mode:

Acknowledgement of set point2

4 Target window1 static

5 Target window1 dynamic

With "Display" operating mode:

Acknowledgement of set point2

6 Deviation

12 Sensor error

(Tape-Sensor or Lost-Sensor or Speed)

13

key

14

key

15

key

Off invalid not reached

On valid reached not acknowledged acknowledged never reached not reached reached not acknowledged acknowledged

7 General error actual position <= set point not present

8 Output of position value dynamic

9 Position value = incremental measurement Off

With "Display" operating mode:

Data identifier number

10 Validity set point2

11 Battery status (critical or empty) invalid alright not present not actuated not actuated not actuated reached actual position > set point is present freezed

On

ASCII-String valid critical or empty is present actuated actuated actuated

Table 22: Status word

6.3.6 Data

Range for data exchange. Size: 4 bytes.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 26 of 56

6.3.7

Communication via SIKONETZ 5

Check sum

For checking error-free data transfer, a check sum is formed at the end of the telegram. The check sum is the exclusive-OR-link of bytes 1 … 9:

Check sum [Byte10] =

[Byte1] XOR [Byte2] XOR [Byte3] XOR [Byte4] XOR [Byte5] XOR [Byte6] XOR [Byte7] XOR

[Byte8] XOR [Byte9]

The following applies for checking the telegram received:

[Byte1] XOR [Byte2] XOR [Byte3] XOR [Byte4] XOR [Byte5] XOR [Byte6] XOR [Byte7] XOR

[Byte8] XOR [Byte9] XOR [Byte 10] = 0

With a result unequal 0 a transmission error is to be assumed.

When a check sum error is detected, it is answered with an error telegram.

With three subsequent check sum errors, the check sum SIKONETZ5 error will be triggered.

6.4 Synchronization

Processing of the "Restore factory settings" system command may take up to 600 ms. Acknowledgment is reported only after proper updating of all parameters in the non-volatile memory.

Byte/telegram synchronization is via "Timeout". The intervals between the individual bytes of a telegram must not exceed the value of 10 ms. If an addressed device does not respond, the master must not send another telegram earlier than after 30 ms.

6.5

AP05

Error telegram

Illegal entries are replied with an error telegram.

An error telegram consists of parameter address FDh and an error code.

The error code is in the data section of the reply telegram. The error code is divided in two bytes. Code 1 describes the error proper, code 2 contains additional information if available.

In the following example an attempt was made at writing a value of 90 to the key enable time parameter address.

However, a maximum value of only 60 is admissible for this parameter.

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address

CW Data Check sum

01h 01h 04h 00h 00h 00h 00h 00h 5Ah 5Eh

Table 23: Telegram from master to slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node

01h address

01h

Parameter address

FDh 00h

SW

81h

- -

00h 00h

Data

Code 2 Code 1

02h

Check sum

82h FCh

Table 24: Reply telegram from slave

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 27 of 56

6.5.1

Communication via SIKONETZ 5

SIKONETZ5 error codes

Code 2

00h

00h

00h

01h

02h

00h

00h

01h

02h

00h

03h

Code 1 Description

80h Check sum SIKONETZ5

81h

82h

83h

84h

Timeout SIKONETZ5

Value rage exceeded / inadequate

Value < MIN

Value > MAX

Unknown parameter

Access is not supported

85h write attempt to read only read attempt to write only

Error due to device status

Programming locked

Table 25: SIKONETZ5 error codes

6.6

6.7

Communication errors

Error states of the slave are signified with the status word.7 = 1.

Every error must be acknowledged with control word.5 = 0/1 or by pressing the key. If the cause of the error has not been resolved at the time of acknowledgment, the error will not be reset or triggered anew, resp.

Errors that have not been acknowledged can be read via a read command on parameter Error

telegram (see chapter 6.9.57

). The error code will be output (see chapter 4.6

and 6.5.1

).

A list of errors occurring is output in Diagnosis (see chapter 4.5.2.2

).

Communication monitoring

6.7.1 Bus-Timeout

Bus timeout monitoring is activated by configuring a valid time value (>0) for timeout (see

parameter 02h: Bus Timeout ).

The first telegram received by the slave starts time monitoring.

Every new telegram recognized as valid by a slave (correct check sum) triggers time monitoring.

If timeout occurs, this will result in the Timeout SIKONETZ5 error.

After establishing cyclic communication between master and slave, this function can detect a broken cable of the connection line for instance and signal the defect.

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 28 of 56

6.7.2

Communication via SIKONETZ 5

Programming interlock

Programming interlock is controlled via parameter Configuration programming mode

(see chapter 6.9.15

). This parameter being enabled, the interlock must be canceled prior to

write access to a lockable parameter (see entry at the relevant parameter) by applying a write

access to parameter Programming mode (see chapter 6.9.47

). Correspondingly, the interlock

should be enabled again immediately after a write access.

This mechanism enhances protection against unintentional parameterization.

Write access to locked parameters is replied with "Error due to device state"

(see chapter 6.5.1

).

6.8 Auto-ID

This function facilitates first commissioning of the devices in the plant. The node numbers can be assigned by the superordinate control or by pressing the relevant button on the device

concerned. The functional principle is illustrated in Fig. 7 .

The Node ID 1Fh (31d) is factory-set. Now, the SIKONETZ5 master must send a write command

on parameter Auto-ID assignment (see chapter 6.9.53

) with the new Node ID to be set to the

bus subscriber(s) with the current Node-ID 1Fh and wait for an SIKONETZ5 response. A write command on devices with a node ID different from 1Fh is responded to with an error message.

"New ID" will be displayed on all devices that have the current Node-ID 1Fh.

The user must press the key on the device intended to adopt the new Node ID. Afterwards, this device sends a SIKONETZ5 response with the original Node-ID (1Fh) and the parameter

Auto-ID assignment. The new Node-ID is taken over and stored in the EEPROM. The initialization phase is finally repeated so that the new Node ID applies henceforth. All other devices do not react. Afterwards, the control unit can execute a read command on a parameter for the node with the node ID 1Fh for instance in order to detect any other devices with node

ID 1Fh present in the bus. If so, the procedure may be repeated until all devices have received the desired Node-ID. The Auto-ID function is aborted in the AP05 when an illegal value was sent for the new ID. Error messages will be returned in this case.

Use of this function is optional. The node numbers can also be set via parameterization

(see chapter 4.3

).

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 29 of 56

Communication via SIKONETZ 5

Fig. 7: Auto-ID function

6.9

AP05

Parameter description

Here, numbering follows the parameter address in SIKONETZ5.

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 30 of 56

6.9.1

Communication via SIKONETZ 5

00h: Note address

Setting of the SIKONETZ5 node address.

Changes become active only after restart of the device.

Parameter address

Description

00h node address

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

31

1 … 127

6.9.2 01h: Baud rate

Setting of the SIKONETZ5 baud rate.

Changes become active only after restart of the device.

Parameter address

Description

01h

Baud rate of the RS485 interface

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

57600 kBaud

0 = 19200

1 = 57600

2 = 115200

6.9.3 02h: Bus Timeout

See chapter 6.7.1

.

Parameter address

Description

Access

02h

Indication of bus timeout in x100 ms rw

EEPROM yes

Programming mode yes

Data type

Default

UNSIGNED 8

0

Data content 0 … 20

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 31 of 56

6.9.4

Communication via SIKONETZ 5

03h: Response parameter to a set point write access

Parameter address

Description

03h

This parameter defines the response to the command

"Write set point" rw Access

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = set point

1 = actual value

2 = differential value

6.9.5 04h: Keys enable time: Parametrization start delay

Parametrization start delay (key enable time) is set via parameter 04h.

Parameter address

Description

04h

Duration of key actuation to start parametrization.

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

5

1 … 60 s

6.9.6 05h: Key function enable1: Calibration enable

The parameter 05h indicates whether calibration of the position value is enabled via key actuation.

Parameter address

Description

Access

EEPROM

05h

Key enable rw yes

Programming mode yes

Data type UNSIGNED 8

Default 1

Data content 0: Calibration disabled

1: Calibration enabled

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 32 of 56

6.9.7

Communication via SIKONETZ 5

06h: LED flashing

Flashing of the LEDs can be set via parameter 06h (see chapter 3.3

). This setting applies to all

LEDs.

Parameter address

Description

06h

Flashing of all LEDs

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = no flashing

1 = any glowing LED is flashing

6.9.8 07h: LED3 (green right)

LED3 (green, right) can be set via parameter 07h (see chapter 3.3

). The control word can be

freely accessed only if the LED is switched off here.

Parameter address

Description

Access

EEPROM

07h

LED green right (LED3) rw yes

Programming mode yes

Data type UNSIGNED 8

Default 1

Data content 0 = Off

1 = position-dependent

6.9.9 08h: LED2 (red left)

LED2 (red, left) can be set via parameter 08h (see chapter 3.3

). The control word can be freely

accessed only if the LED is switched off here.

Parameter address

Description

08h

LED red left (LED2)

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

1

0 = Off

1 = position-dependent

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 33 of 56

Communication via SIKONETZ 5

6.9.10 09h: LED1 (green left)

ED1 (green, left) can be set via parameter 09h (see chapter 3.3

). The control word can be

freely accessed only if the LED is switched off here.

Parameter address

Description

09h

LED green left (LED1)

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

1

0 = Off

1 = position-dependent

6.9.11 0Ah: Decimal places

The parameter 0Ah indicates the number of decimal places.

Parameter address

Description

0Ah number of decimal places

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

0

0 … 4

6.9.12 0Bh: Display divisor (ADI)

The display divisor can be changed via parameter 0Bh.

Parameter address

Description

0Bh display divisor ADI

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: 1

1: 10

2: 100

3: 1000

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 34 of 56

Communication via SIKONETZ 5

6.9.13 0Ch: Direction indicators (CW, CCW)

The display of the direction arrows is set via parameter 0Ch.

Parameter address

Description

Access

0Ch

Representation of the direction indicators rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = On

1 = inverted

2 = Off

6.9.14 0Dh: Display orientation

Display orientation can be set via parameter 0Dh.

Parameter address

Description

0Dh

Display orientation

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

0

0 = 0°

1 = 180° rotated

6.9.15 0Eh: Configuration programming mode

Basic settings of programming interlock (see chapter 6.7.2

).

Parameter address

Description

0Eh

Configuration programming mode

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

0

0 = no active programming interlock

1 = active programming interlock

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 35 of 56

Communication via SIKONETZ 5

6.9.16 0Fh: PIN change

PIN required to be able to change parameters via keys and display (see chapter 4.3.1

).

Parameter address

Description

Access

0Fh

PIN rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 32

Default

Data content

0

0 … 99999

6.9.17 1Bh: Counting direction

The counting direction can be set via parameter 1Bh.

Parameter address

Description

Access

EEPROM

1Bh counting direction rw yes

Programming mode yes

Data type UNSIGNED 8

Default 0

Data content 0 = clockwise sense of rotation I (CW)

1 = counter-clockwise sense of rotation E (CCW)

I sense of rotation: ascending position values with clockwise shaft rotation (CW, view on the

display)

E sense of rotation: ascending position values with counter clockwise shaft rotation (CCW,

view on the display)

6.9.18 1Ch: Resolution per revolution

The number of measurement steps per revolution (display / revolution = APU) is defined via parameter 1Ch.

Parameter address

Description

1Ch

Number of measurement steps per revolution

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 16

720

1 … 65535

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 36 of 56

Communication via SIKONETZ 5

6.9.19 1Eh: Offset value

The offset value is determined via parameter 1Eh.

Parameter address

Description

Access

1Eh

Offset enables the shifting of a scaled value range. The offset value is added to the position value in the encoder. Both positive and negative values are allowed.

Position value = measured value + calibration value + offset value rw

EEPROM yes

Programming mode yes

Data type

Default

SIGNED 16

0

Data content -19999 … 19999

6.9.20 1Fh: Calibration value

Via parameter 1Fh, the encoder's position value can be set to a calibration value when calibrating.

To enable the execution of calibration, the "Calibration" system command must be executed

(see chapter 4.4

).

Parameter address

Description

Access

1Fh calibration value (position value = measured value + calibration value + offset value) rw

EEPROM yes

Programming mode yes

Data type SIGNED 32

Default

Data content

0

-19999 … 99999

6.9.21 20h: Target window1 (near field)

The parameter 20h indicates the window within which the set point is considered reached

(see chapter 4.1.1.1

).

Parameter address

Description

Access

EEPROM

20h

The set point is reached when the actual value is within the target window. rw yes

Programming mode yes

Data type UNSIGNED 16

Default 5

Data content 0 … 9999

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 37 of 56

Communication via SIKONETZ 5

6.9.22 21h: Positioning type (loop type)

The positioning type, loop type is indicated via parameter 21h, thereby selecting the direction

from which the set point shall be approached (see chapter 4.1.1.2

).

Parameter address

Description

21h

Set point is approached in this direction.

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: no loop

1: loop +

2: loop -

6.9.23 22h: Loop length

Parameter 22h specifies the loop length by which the set point shall be moved over with loop

travel (see chapter 4.1.1.2

).

Parameter address

Description

Access

22h loop length rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 16

Default

Data content

0

0 … 9999

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 38 of 56

Communication via SIKONETZ 5

6.9.24 28h: Operating mode

The operating mode can be set via parameter 28h.

Parameter address

Description

Access

28h operating mode rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: Absolute position

1: Difference

2: Modulo (360° angle display)

3: Alpha-numeric display

6.9.25 30h: Display in the 2

nd

row

Via parameter 30h the display of the 2 nd row of the display unit is controlled. The setting is not effective in the "Display" operating mode.

Parameter address

Description

Access

30h controls the display of the 2 nd

row of the display unit rw

EEPROM yes

Programming mode yes

Data type

Default

UNSIGNED 8

0

Data content 0: Set point or differential value (depending on mode,

see chapter 4.1.1

)

1: Off

6.9.26 31h: Target window2 (extended)

Via parameter 31h, the size of target window2 can be set (see chapter 4.1.1.2

and parameter

32h: Target window2 visualization ).

Parameter address

Description

31h

Extended target window to facilitate positioning at fast travel speed.

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 16

0

0 … 9999

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 39 of 56

Communication via SIKONETZ 5

6.9.27 32h: Target window2 visualization

Target window2 visualization can be set via parameter 32h (see chapter 4.1.1.1

and parameter

31h: Target window2 (extended) ).

Parameter address

Description

32h target window2 visualization

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = Off

1 = On

6.9.28 33h: Application of the display divisor (ADI application)

Via parameter 33h, the application oft he ADI can be adjusted for the position values ascertained (absolute position value, differential value, frozen position value). Target values are not offset against the ADI.

Parameter address

Description

Access

33h

ADI application rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: all values ascertained (absolute position value, differential value, frozen position value) are displayed after ofsetting against the ADI and transmitted via the interface this way.

1: all values ascertained are displayed after ofsetting against the

ADI and transmitted via the interface.

Examples:

Position value ascertained

12348

12348

12348

12348

12348

ADI

(0Bh)

0

1

1

3

3

ADIapplication x

0

1

0

1

Display Output interface

12348 12348

1235

1235

12

12

1235

12348

12

12348

Set point2 received

12348

1235

12348

12

12

Target attained yes yes no yes yes

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 40 of 56

Communication via SIKONETZ 5

6.9.29 34h: Formation of the differential value

Calculation of the differential value is set via parameter 34h.

Parameter address

Description

Access

34h formation of the differential value rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: DIFF = ACT – SET

1: DIFF = SET - ACT

6.9.30 35h: Key function enable2: Incremental measurement enable

The parameter 35h indicates whether setting of the position value as incremental measurement is enabled via key actuation.

Parameter address

Description

35h

Key enable

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

1

0: Incremental measurement disabled

1: Incremental measurement enabled

6.9.31 39h: LED4 (red right)

The LED4 (red, right) can be set via parameter 39h (see chapter 3.3

). Free access via the

control word is only enabled if the LED is switched off here.

Parameter address

Description

Access

39h

LED red right (LED4) rw

EEPROM yes

Programming mode yes

Data type

Default

UNSIGNED 8

1

Data content 0 = Off

1 = position-dependent

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 41 of 56

Communication via SIKONETZ 5

6.9.32 3Ah: LCD backlight flashing

Flashing of the LCD backlight can be set via parameter 3Ah. This setting applies to either color.

Parameter address

Description

3Ah

Flashing of the LCD backlight

Access

EEPROM rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = no flashing

1 = the current backlight is flashing.

6.9.33 3Bh: LCD backlight white

The white LCD backlight can be set via parameter 3Bh.

Parameter address

Description

3Bh

LCD backlight white

Access

EEPROM rw yes

Programming mode yes

Data type

Default

Data content

UNSIGNED 8

1

0 = Off

1 = On

6.9.34 3Ch: LCD backlight red

The red LCD backlight can be set via parameter 3Ch.

Parameter address

Description

Access

EEPROM

3Ch

LCD backlight red rw yes

Programming mode yes

Data type UNSIGNED 8

Default 1

Data content 0 = Off

1 = On

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 42 of 56

Communication via SIKONETZ 5

6.9.35 3Dh: Key function enable3: Parametrization enable via keyboard

Parameter 3Dh indicates whether parametrization via key actuation is enabled.

Parameter address

Description

Access

3Dh

Key enable rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

1

0: parametrization disabled

1: parametrization enabled

6.9.36 3Eh: Acknowledgement settings

Parameter 3Eh serves for determining the key to be used as acknowledgement key.

The setting is only relevant in the alpha-numeric display mode. A flashing set point is displayed until its receipt is acknowledged via keystroke.

Parameter address

Description

Access

EEPROM

3Eh acknowledgement settings rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0: key

2: and key

6.9.37 3Fh: Display factor

If a display factor> 0 is set, all values on the display are indicated in inch.

It should be noted that the transmission values from and to the interface are present in the metric system (depending on resolution and ADI). The control delivers target, calibration, and offset values as well as loop length and target window metrically as well. Device-internal position monitoring is metrical. Therefore, the superordinate control can only function in the metric system. The values for position, setpoint and the differential value if applicable are calculated by means of the following formula (for position value):

Display value = position value x calculation factor

Calculation factor

=

1

0.254

x 10

4-Display factor

9 different calculation factors can be set (see Table 26 ). The number of decimal places is

selected via parameter 0Ah: Decimal places .

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 43 of 56

Communication via SIKONETZ 5

Display factor

0

Calculation factor

1

Meaning

Metric indication after APU and ADI

Imperial indication (inch)

Examples of indication (APU = 400)

Position after 1 revolution = 400

400

1574803 1

2

3

4

5

6

7

8

10

3

0.254

10

2

0.254

10

1

0.254

10

0

0.254

10

-1

0.254

10

-2

0.254

10

-3

0.254

10

-4

0.254

Table 26: Value table of display factor

0

157480

15748

1575

158

16

2

Parameter address

Description

Access

EEPROM

3Fh

Display factor rw yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 … 8

6.9.38 40h: LED Bus

The function oft he LED bus can be set via parameter 40h (see chapter 3.3

). No access to this

LED via control word is supported.

Parameter address

Description

Access

EEPROM

40h

LED Bus rw yes

Programming mode yes

Data type UNSIGNED 8

Default 1

Data content 0 = Off

1 = Bus traffic-dependent (glows for 1 s when receiving a message)

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 44 of 56

Communication via SIKONETZ 5

6.9.39 63h: Battery voltage

Battery voltage can be read via parameter 63h. The voltage is indicated in 10 mV resolution.

Parameter address

Description

Access

63h battery voltage ro

EEPROM no

Programming mode no

Data type UNSIGNED 16

Default

Data content

0

0 … 310 (0 V … 3.10 V)

6.9.40 65h: Device identification

Parameter address

Description

65h

Device identification

Access

EEPROM ro no

Programming mode no

Data type

Default

Data content

UNSIGNED 8

11

11 = AP05

6.9.41 67h: Software version

Parameter address

Description

Access

EEPROM

67h

Software version number ro no

Programming mode no

Data type UNSIGNED 32

Default -

Data content 100 (= version 1.00) or higher

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 45 of 56

Communication via SIKONETZ 5

6.9.42 80h: Number of errors

See chapter 4.4

.

Parameter address

Description

Access

80h

Number of errors recorded ro

EEPROM yes

Programming mode no

Data type UNSIGNED 8

Default

Data content

0

0 … 10

6.9.43 81h until 8Ah: Errors

See chapter 4.6

. The oldest error is found under parameter address 81h, the most recent error

is found under the highest address.

Parameter address

Description

Access

81h until 8Ah error ro

EEPROM yes

Programming mode no

Data type UNSIGNED 16

Default

Data content

0

see Table 16

6.9.44 96h: Input errors

Output of a list (10 entries) of input errors (see chapter 6.5.1

). The list is deleted with

initialization of the device at program start (reset or power-on).

The error number must be transferred in data byte 3 of the telegram.

Data byte 3 with the request = 0

number of errors occurring is reported.

Data byte 3 with the request = 1

error number 1 (oldest error) is reported.

Example:

Telegram structure of master: oldest error (= no. 1) shall be read:

Command ID

00h 1Fh

Parameter ZSW

96h XX YY

Error number

01h

CS

00h 00h 00h NNh

Telegram structure of slave: oldest error (1) is output:

Command ID

00h 1Fh

Parameter ZSW

96h XX YY

Error number Error code

01h 00h 00h 83h

CS

NNh

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 46 of 56

Communication via SIKONETZ 5

Parameter address

Description

96h error

Access

EEPROM ro yes

Programming mode no

Data type

Default

Data content

UNSIGNED 16

0

see chapter 6.5.1

6.9.45 A0h: System commands

Various system commands can be executed via parameter A0h (see chapter 4.5

).

Parameter address

Description

Access

A0h

System commands wo, broadcast-compatible

EEPROM no

Programming mode yes

Data type UNSIGNED 32

Default

Data content

0

1: Reset all parameters to factory settings

2: Reset all parameters to factory settings, except the bus parameters

5: Reset only the bus parameters to factory settings

7: Calibrate

9: Software reset (warm start)

6.9.46 A7h: Calibration travel

Calibration travel or calibration, respectively, can be executed via parameter A7h.

Parameter address A7h

Description

Access

Execute calibration (see chapter 4.4

)

wo

EEPROM no

Programming mode no

Data type

Default

Data content

UNSIGNED 32

0

1

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 47 of 56

Communication via SIKONETZ 5

6.9.47 A8h: Programming mode

Programming interlock (see chapter 6.7.2

).

Parameter address

Description

Access

A8h

Programming mode wo, broadcast-compatible

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = parameter programming disabled

1 = parameter programming enabled

6.9.48 AAh: Freeze actual value

The actual position value can be freezed via this parameter. So, synchronized recording of all position values in the unit can be generated. The status word signifies whether the position

value treansmitted is updated or freezed (see chapter 6.3.5

). Updating of the position value

will be reenabled with the next readout operation.

Parameter address

Description

AAh

The current actual position value is cached (freezed) until the next readout operation of the actual position.

Access

EEPROM wo, broadcast-compatible no

Programming mode no

Data type

Default

Data content

UNSIGNED 8

0

1 = freeze actual position

6.9.49 C5h: ADC values of the sensor

The current ADC values of the sensor can be retrieved via parameter C5h.

Parameter address

Description

C5h

ADC values of the sensor

Access

EEPROM ro no

Programming mode no

Data type

Default

Data content

UNSIGNED 32

0

Byte 0

ADC_SIN

Byte 1 Byte 2

ADC_COS

Byte 3

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 48 of 56

Communication via SIKONETZ 5

6.9.50 CAh: Bus protocol

Changes become active only after restart of the device.

Parameter address

Description

Access

CAh

Protocol of the RS485 interface rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 = SIKONETZ5

1 = Service protocol

6.9.51 CFh: Period counter

The current values of the period counter can be retrieved via parameter CFh.

Parameter address

Description

Access

Default

Data content

CFh values of the period counter ro

EEPROM no

Programming mode no

Data type UNSIGNED 32

0

Byte 0

Quadrant

Byte 1

Period counter

Byte 2 Byte 3

6.9.52 D0h: Response delay

Number of internal program cycles deferred before responding to a SIKONETZ5 bus telegram.

The response to a telegram can be delayed until the master is ready to receive. The value 10 corresponds to a delay of approx. 5 ms.

Parameter address

Description

Access

D0h

Response delay rw

EEPROM yes

Programming mode yes

Data type UNSIGNED 8

Default

Data content

0

0 … 20

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 49 of 56

Communication via SIKONETZ 5

6.9.53 D2h: Auto-ID assignment

See chapter 6.8

.

Parameter address

Description

Access

D2h

Automated assignment of a node address wo

EEPROM yes, the node number is stored with its adoption

Programming mode no

Data type UNSIGNED 8

Default

Data content

-

1 … 31

6.9.54 FAh: Status word

The status word can be read via this parameter. Bit 4: "Target window1 static" is deleted in the status word with this operation. With this function, it can be detected whether the actual position was ever in the target window even if this is not the case at present

(see chapter 6.3.5

).

Parameter address

Description

Access

EEPROM

FAh

Read status word and delete "Target window1 static" ro no

Programming mode no

Data type UNSIGNED 16

Default -

Data content 0

6.9.55 FBh: Set point1

The current set point1 (alpha-numeric display operating mode) can be written and read via

address FBh (see chapter 4.1.2

).

Parameter address

Description

Access

EEPROM

FBh

Set point1 rw no

Programming mode no

Data type UNSIGNED 32

Default -

Data content 0h … FFFFFFFFh

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 50 of 56

Communication via SIKONETZ 5

6.9.56 FCh: Differential value

The differential value can be read via parameter FCh. Formation of the differential value is set

via parameter 34h: Formation of the differential value .

Parameter address

Description

FCh

Differential value: Deviation between actual and target positions

Access

EEPROM ro no

Programming mode no

Data type SIGNED 32

Default

Data content

-

-5242880 … 5242880

6.9.57 FDh: Error telegram

Illegal entries are answered with an error telegram.

An error telegram consists of the parameter address FDh and an error code (see chapter 6.5

).

Parameter address

Description

FDh

Error telegram

Access

EEPROM

- no

Programming mode no

Data type

Default

Data content

UNSIGNED 32

-

see chapter 6.5

6.9.58 FEh: Position value

The current position value of the device is output under FEh.

Parameter address

Description

FEh

Actual position (see chapter 4.1.1

)

Access

EEPROM ro no

Programming mode no

Data type SIGNED 32

Default

Data content

-

-5242880 … 5242880

Position value = measured value + calibration value + offset value

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 51 of 56

Communication via SIKONETZ 5

6.9.59 FFh: Set point2

The current set point2 can be written and read via address FFh.

Parameter address

Description

Access

FFh

Set point2 rw

EEPROM no

Programming mode no

Data type SIGNED / UNSIGNED 32 (depending on the operating mode)

Default

Data content

-

0h … FFFFFFFFh

6.10 Examples of access

6.10.1 Example: Read parameter

With read commands the data range shall be set to value 0.

Reading the parameter target window1 of node address 1:

Read command: 00h

Node address: 01h

Parameter address: 20h Target window1

Data: 00h 00h 00h 00h

Telegram from master to slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address

CW Data Check sum

00h 01h 20h 00h 00h 00h 00h 00h 00h 21h

Reply telegram from slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address

CW Data Check sum

00h 01h 20h 00h 01h 00h 00h 00h 05h 25h

The current value oft he target window1 parameter is in the response telegram.

Data: 00 00 00 05h

5 dec

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 52 of 56

Communication via SIKONETZ 5

6.10.2 Example: Write parameter

Set parameter offset value of node address 1 to value 500:

Write command: 01h

Node address: 01h

Parameter address: 1Eh Offset value

Data: 000001F4h

500 dec

Telegram from master to slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address

CW Data Check sum

01h 01h 1Eh 00h 00h 00h 00h 01h F4h EBh

Reply telegram from slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command

/ Reply

Node address

Parameter address

SW Data Check sum

01h 01h 1Eh 00h 01h 00h 00h 01h F4h EAh

Set set point value parameter of node address 1 to value 1234, switch set point2 to valid

Write command: 01h

Node address: 01h

Parameter address: FFh Sollwert2

Data: 000004D2h

1234 dec

Telegram from master to slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command Node address

Parameter address

CW Data Check sum

01h 01h FFh 02h 00h 00h 00h 04h D2h 43h

Reply telegram from slave

1

st

byte 2

nd

byte 3

rd

byte 4

th

byte 5

th

byte 6

th

byte 7

th

byte 8

th

byte 9

th

byte 10

th

byte

Command

/ Reply

Node address

Parameter address

SW Data Check sum

01h 01h FFh 04h 01h 00h 00h 04h D2h 44h

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 53 of 56

Communication via Service Standard Protocol

7

7.1

7.2

7.3

AP05

Communication via Service Standard Protocol

General

The service protocol enables the control of the position indicator via ASCII commands. No additional devices must be connected to the RS485 interface since this protocol is not buscompatible.

An ASCII terminal sends a letter and additional parameters if required (ASCII).

Subsequently, the position indicator sends a reply with a concluding <CR>.

Available baud rates: 19.2 kBit / 57.6 kBit (factory setting) / 115.2 kBit

Additional settings: No parity, 8 data bits, 1 stop bit, no handshake

Error number encoding

The following error messages are returned in case of wrong input.

Error number Description

?1

?2 input of illegal parameter number illegal value range

Table 27: Error number encoding

Service protocol commands list

Command Length Reply Description

Ay 2/17 "AP05 SN5 zW xxxx>" Device type / software version y=0: hardware version; z = H y=1: software version; z = S

L 1/2

Sxxxxx 6/2

">"

">"

Calibration (see chapter 4.4

)

System commands

U

Z

1/6

1/11

"xxyy>"

"±xxxxxxxx>" x=11100: all parameters into basic state

After restart, the factory settings will be active, this applies to bus protocol and baud rate as well. x=11101: reset all to factory settings, except bus parameters x=11102: only bus parameters into basic state x=11105: activate bootloader

Current SIN/COS values of the sensor unit x=SIN y=COS

Output actual position

Table 28: Service protocol commands list

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 54 of 56

8

Text displays and their meaning

Text displays and their meaning

Display Meaning

tnd

Standard

AD

Adjustment

D

Sensor-Band non

No Sensor

PA

Bus Passive



Bus Off

Ac

Battery critical

Ato

Battery low

Prtc

Protocol



Service

to

Bus-Time-Out

Inht

Inhibit



Checksum Bus to

Time-Out Bus

 o

Limit Low

 h

Limit high noPA

No Parameter rd

Read Only no rd

No Read noPG

No Programming

PIt

Positioning

II

Vision

PtI

Options

ro

Read Only

AP

APU

DP

Decimal Point

ADI

ADI rott

Rotation

I

Calibration



Offset tr1

Target1 tr

Target2

PP

Positioning Type

DIP

Display

I

Target2 Visualisation

Indc

Indicators

I

Line 2

Description

Adjustment

Sensor-magnetic strip gap

No sensor

Bus passive error state (CANopen)

Bus off error state (CANopen)

Critical battery status

Empty battery status

Bus protocol

Service Standard protocol (RS485)

Bus-Time-Out (Parameter)

Inhibit-Time

Bus telegram check sum

Bus time-out (fault)

Range limit undercut

Range limit exceeded

No known parameter

Read-only, no write access

Write-only, no read access

Not in the programming mode

Positioning

Visualization

Options

Device data

Display per revolution

Decimal place

Display divisor

Sense of rotation

Calibration value / Calibration

Offset

Target window1

Target window2

Type of positioning

Display orientation or

"alphanumeric display" mode

Visualization of target window2

Indicators

Lower line

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 55 of 56

Text displays and their meaning

Display Meaning



Backlight

 D

Backlight red

 

Backlight flash

A

Factor

rn 1

Green 1

D 1

Red 1

A

Flash

 3

Bus 3

DA

Config Delay

An

Calibration Enable

Inn

Increment Enable

nn

Configuration Enable

D

Difference

PP

Operation Type

A

U Battery

o

Serial Number

P

Positive

n

Negative

dr

Direct

nr

Invers trt

Target

PA

Position - Target tAP

Target - Position

Description

Display backlight

Red display backlight

Red display backlight

Display factor

LED green 1

LED red 1

LED flash

LED Bus 3

Configuration start delay

Calibration permitted

Incremental measurement permitted

Configuration permitted

Difference value calculation

Mode of operation

Battery voltage

Serial number

Positive

Negative

Direct

Inverted

Target

Position value – target value

Target value – position value

A

Absolut

An

Angle

Absolute

Angle display



Version (Firmware) version chPr

Changeable Parameter Changeable device parameters

DIAG

Diagnosis Diagnostic functions

PI

PIN

oADP

Load Parameter

ADI

ADI Use

tnd

Standard tG

Telegramm

Load default values of parameters

Use of ADI

P

Presentation

In

Invalid

Presentation mode

Invalid

AP05

Date: 04.09.2017 Art. No. 89246 Mod. status 269/17 Page 56 of 56

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement