R. STAHL EXLUX 6400 6400/5..., 6400/8... Explosion protected light fittings Operating instruction

Below you will find brief information for EXLUX 6400 6400/5..., EXLUX 6400 6400/8... . This explosion-proof and electrical equipment can be used in potentially explosive locations, providing illumination of shops and offices of a factory and storages in areas of zone 2, zone 21 and 22. The light fittings can be used inside or outside.

PDF
Document
EXLUX 6400 6400/5..., EXLUX 6400 6400/8... Operating instruction | Manualzz

Advertisement

Advertisement

/

Advertisement

Key features

  • Explosion protected

  • For fluorescent lamps

  • Zone 2, 21 and 22

  • Indoor and outdoor use

  • IP 66/67 protection rating

  • Electronic ballast

  • Various lamp power options

  • Cable entry options

Frequently asked questions

The ambient temperature range for this light fitting is -20°C to +55°C.

The maximum current rating for through wiring with a 2.5 mm² cross-section is 16A.

To open the light fitting, remove the cap from the central locking system. Turn the central lock half a revolution (180°) to the left with an M8 box spanner (size SW 13) until the stop is reached. Flap the lamp cover open. Closing is done in the reverse order. Check that the cover is resting properly on the edge of the gasket and that the point of the arrow on the hexagonal head of the central lock is pointing towards the mark "Light fitting closed."