Engineer Data
ED-FWW-VC-201607
Ceiling Concealed Chilled Water
Fan Coil Unit
Models: FWW200VC FWW300VC FWW400VC FWW500VC
FWW600VC FWW700VC FWW800VC FWW1000VC
FWW1200VC
Air Flow: 340-2380m
3
/h
FWW1400VC
Literature No.:
ED-FWW-VC-201607
Contents
Nomenclature …………………………………………………………………………………… 2
Valve Nomenclature …………………………………………………………………………… 3
Features ………………………………………………………………………………………… 4
Specifications …………………………………………………………………………………… 5
Sound Data ……………………………………………………………………………………… 6
Air Flow vs ESP Curve ………………………………………………………………………… 7
Operating Limits ………………………………………………………………………………… 8
Water Flow Rate/Pressure Drop Chart ……………………………………………………… 9
Outlines and Dimensions……………………………………………………………………… 10
Electrical Data …………………………………………………………………………………… 11
Wiring Diagrams ………………………………………………………………………………… 12
Installation ……………………………………………………………………………………… 13
NOTE: Installation and maintenance are to be performed only by qualified personnel who are
familiar with local codes and regulations, and experienced with this type of equipment.
Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.
Warning: Moving machinery and electrical power hazard. May cause severe personal injury or death. Disconnect and lock off power before servicing equipment.
1
Nomenclature
FWW 200 V C 3 R C X - A 0 A E
Sales Region:
Power Supply:
Other Feature Codes
Material of Drain Pan
E: Export
A: 220V~/50 Hz
Filter: X: no filter F: 8mm nylon filter
A: 8 mm aluminum filter
Return Air Plenum: C: without return air plenum
B: back return air plenum
D: bottom return air plenum
E: back return air plenum(5mm PE insulation)
F: bottom return air plenum(5mm PE insulation)
Pipe Connection: R: facing air flow right hand
L: facing air flow left hand
External Static Pressure: 1: 12 Pa
3: 30 Pa
5: 50 Pa
Coil Type: C: 3 rows
Unit Design SN
Rated Air Volume (CFM, 1 CFM = 1.7 m
3
/h)
DAIKIN Ceiling Concealed Horizontal Fan Coil Unit
2
Valve Nomenclature
FWW - 2V 4 Y B R A E
E-Export
U-Stick "Made In China"
Power Supply:
A-220-240V/1Ph/50Hz
K-208-230V/1Ph/60Hz
Pipe Connection
R-for Right hand unit
L-for Left hand unit
Valve Type
B-with Ball Valve
X-without Ball Valve
Strainer Type
Y-with Y-Strainer
X-without Y-Strainer
Union Size
Omitted-R3/4
4-R1
Valve model
2V:2-Way Valve Kit
3V:3-Way Valve Kit
FWW-DAIKIN FCU
(Only 2-pipe system is applicable)
3
Features
Compact
■ Light-weighted, good-looking appearance, and compact and solid structure.
■ 235 mm height, allowing installation on the ceiling with a limited space.
Low-noise
■ Low-noise motor for driving the low speed fan with a wide impeller; strictly tested before delivery.
■ Precise distance between the impeller inlet/outlet and the heat exchanger for more reasonable air flow distribution.
■ Highly efficient sound-absorbing and heat-preserving materials inside to minimize noises produced by the unit.
Reliable
■ Single-phase capacitor motor with the protection grade IP20 and insulation grade B to ensure operation safety.
■ Permanently lubricated and sealed ball bearing with high precision, which is provided by internationally famous brands and receives processing including hardening and tempering as well as chroming.
■ Motor power outlet wires protected by metal hoses to ensure its durability.
■ Working pressure up to 1.6 MPa and test pressure up to 2.0 MPa for the heat exchanger to endure high pressures and prevent leakage.
High Efficiency
■ Heat exchanger with the high-quality mechanically expanded copper pipe and hydrophilic aluminum fins to ensure high efficiency.
■ Intensified air supply using a large air flow fan with a wide impeller to maximize the heat transfer performance.
■ Precise matching of the fan and motor to guarantee the maximum cooling capacity but a low power input.
Flexible
■ Multiple external static pressures designed based on the unit’s cooling capacity, meeting the air supply requirements at different distances.
■ Optional bottom return air plenum or back return air plenum with support for onsite changes, featuring time saving.
■ Variable accessories for more options.
Anti-leakage
■ Delicate condensate-proof drain pan made of the cold-rolled steel through one-time impact molding, with coating on both sides and high-quality heat-preserving materials on the exterior.
■ Unique independent mounting bracket without soldering seams or joints, requiring no bolts for fixing to prevent damages to the drain pan heat-preserving layer or cold bridges.
■ Tilt structure for rapid condensate water drainage.
4
Specifications
General Data
MODEL
HIGH
Air
Flow
MEDIUM
LOW
EXTERNAL
STATIC PRESSURE Pa/in.wg
TOTAL COOLING
CAPACITY
SENSIBLE
COOLING
CAPACITY
TOTAL HEATING
CAPACITY
WATER FLOW
RATE
HEAD LOSS
(Cooling)
W
Btu/h
W
Btu/h
W
Btu/h m 3 /h
USGPM
Pa in.wg.
kg
UNIT WEIGHT
(Without plenum)
lb m 3 /h
CFM m
3
/h
CFM m 3 /h
CFM
FWW-VC
FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VCFWW1200VCFWW1400VC
340 510 680 850 1020 1170 1360 1700 2040 2380
200 300 400 500 600 688 800 1000 1200 1400
279
164
170
418
246
255
558
328
340
697
410
425
836
492
510
959
564
585
1115
656
680
1394
820
850
1673
984
1020
1952
1148
1190
100 150 200 250 300 344 400 500 600 700
2220
7575
1380
4709
3500
11942
0.37
1.6
25
0.1
10.3
22.7
3300
11260
2220
7575
5330
18187
0.58
2.6
21
0.1
12.4
27.3
4260
14536
2770
9452
6800
23203
0.72
3.2
30
0.1
12.8
28.2
5050
17231
3400
11601
8400
28662
0.88
3.9
30
0.1
15.1
33.3
12,30,50/0.05,0.12,0.20
5820
19859
4000
13649
9600
32757
1.02
4.5
32
0.1
16.7
36.8
6600
22520
4550
15525
11100
37875
1.14
5.0
35
0.1
17.6
38.8
8200
27980
5500
18767
13500
46064
1.41
6.2
32
0.1
25.2
55.6
9300
31733
6500
22179
15800
53912
1.67
7.4
40
0.2
28.6
63.1
11190
38182
7700
26273
18300
62442
1.95
8.6
35
0.2
31.0
68.3
13000
44358
9200
31392
21500
73361
2.29
10.1
50
0.2
33.5
73.9
UNIT GROSS
WEIGHT
(Without plenum)
Without
Return
Air Plenum
With Back
Return
Air Plenum
With Bottom
Return
Air Plenum
UNIT WEIGHT
(With plenum)
UNIT GROSS
WEIGHT
(With plenum)
CONDENSATE
DRAIN SIZE
kg lb mm mm mm kg lb kg lb
12.4
27.3
14.7
32.4
15.3
33.7
17.8
39.2
19.4
42.8
625×465×235 815×465×235 865×465×235 945×465×235 1045×465×235 1095×465×235 1425×465×235 1475×465×235 1675×465×235 1825×465×235
625×516×235 815×516×235 865×516×235 945×516×235 1045×516×235 1095×516×235 1425×516×235 1475×516×235 1675×516×235 1825×516×235
625×497×235 815×497×235 865×497×235 945×497×235 1045×497×235 1095×497×235 1425×497×235 1475×497×235 1675×497×235 1825×497×235
13.2
29.1
15.3
33.7
16.0
35.3
18.3
40.3
16.7
36.8
19.2
42.3
19.3
42.5
22.0
48.5
21.2
46.7
23.9
52.7
R3/4
20.4
45.0
22.4
49.4
25.2
55.6
28.9
63.7
31.3
69.0
35.0
77.2
32.4
71.4
34.8
76.7
38.6
85.1
35.4
78.0
38.0
83.8
42.4
93.5
38.5
84.9
41.5
91.5
46.5
102.5
NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONTITION:
• COOLING-27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C
• HEATING-21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.
3) SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT
IS 1m IN FRONT END
5
Components Data
FAN
MOTOR
COIL
AIR
FILTER
(Option)
TYPE
QUANTITY
MATERIAL
DRIVE
mm
DIAMETER
in mm
LENGTH
in
TYPE
QUANTITY
IP/INSULATION GRADE
MATERIAL
TUBE
DIAMETER
mm in mm
THICKNESS
in
FIN
MATERIAL
THICKNESS
mm in
FACE AREA
ROW
FIN PER INCH
m
2 ft
2
TYPE
mm in mm
SIZE
LENGTH
WIDTH
THICKNESS
in mm in
FWW-VC
FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VC FWW1200VC FWW1400VC
GALVANIZED STEEL DOUBLE STAGE IMPELLER CENTRIFUGAL (BLADE: FORWARD)
1 2 2 2 2 2 3 3 4 4
1
0.08
0.86
438
17.24
1
0.12
1.29
628
24.72
1
0.13
1.40
678
26.69
GALVANIZED STEEL
DIRECT DRIVE
150
5.904
150/200/240
5.91/7.87/9.45
SINGLE PHAZE BALL BEARING CAPACITOR RUNNING
1 1 1 2
IP20/B
0.15
1.61
758
29.83
COPPER
7
0.28
0.25
0.01
HYDROPHILIC ALUMINUM
0.11
0.0043
0.17
1.83
0.18
1.94
3
17
NYLON/ALUMINIUM FRAME
858 908
33.77 35.74
196
7.71
8
0.31
0.25
2.69
1238
48.73
2
0.26
2.80
1288
50.70
2
0.30
3.23
1488
58.57
2
0.34
3.66
1638
64.47
NOTES:
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Sound Data
Model
Sound
Pressure Level
(ESP: 12Pa)
High
dBA
Middle dBA
Low
dBA
High
dBA
Sound
Pressure Level
(ESP: 30 Pa)
Sound
Pressure Level
(ESP: 50 Pa)
Middle dBA
Low
dBA
High
Low
dBA
Middle dBA dBA
FWW-VC
FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VC FWW1200VC FWW1400VC
33.9
29.3
33.2
28.8
40.0
35.5
40.3
36.3
44.4
39
45.2
40.3
43.9
38.6
47.9
43.6
48.0
44.3
51.0
47.5
20.1
37.3
32.5
20.9
41.2
37.3
26.1
24.2
37.6
32.5
22.8
42.2
35.8
25.8
24.0
41.6
36.5
25.8
44.4
40.5
32.3
25.6
44.3
39.5
27.3
46.4
42.7
31.3
29.8
46.5
41.1
27.3
47.5
43.9
33.9
27.9
46.6
41.8
29.4
47.5
43.6
37.3
27.4
46.2
41.3
30.6
48.3
43.7
31.8
32.6
49.3
44.9
36.4
50.6
46.4
37.6
33.4
50.9
45.7
34.7
51.8
47.1
41.7
38.0
52.0
46.0
35.5
53.5
49.0
41.0
NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) SOUND PRESSURE LEVEL ARE ACCORDING TO MICROPHONE POSITION OF THE MEASUREMENT POINT IS 1m
IN FRONT AND 1m BELOW THE UNIT.
6
Air Flow vs ESP Curve
ESP, 12Pa
ESP, 30Pa
ESP, Pa
FWW1200
FWW1000
FWW800
FWW700
FWW600
FWW500
FWW400
FWW300
FWW200
FWW1200
FWW1000
FWW800
FWW700
FWW600
FWW500
FWW400
FWW300
FWW200
ESP, Pa
ESP, 50Pa
FWW1200
FWW1000
FWW800
FWW700
FWW600
FWW500
FWW400
FWW300
FWW200
ESP, Pa
7
Operating Limits
Operating Limits
Water Circuit
Max. Water side pressure
Min. Entering water temperature
Power supply
Operating voltage limits
Operating frequency limits
1.6MPa
3ºC (cooling)
±10% Volt
±2Hz
FWW-V
8
Water Flow Rate/Pressure Drop Chart
FWW-VC
WATER PRESSURE DROP CURVE(3 Rows)
65
60
55
50
45
40
35
30
FWW700VC
FWW500VC
FWW300VC
FWW400VC
FWW200VC
FWW600VC
25
20
15
10
5
FWW800VC
FWW1000VC
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1 1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
WATER FLOW m
3
/h
FWW1200VC
2 2.1
2.2
2.3
9
Outlines and Dimensions
WITHOUT PLENUM
D
B
40
MOUNTING HOLE 4-10×16
CONDENSATE DRAIN
R3/4″
AIR VENT
35
105
20
WATER SUPPLY
CONNECTION
Rc3/4″
WATER RETURN
CONNECTION
Rc3/4″
20°
131
242
262
465
MCW200V
Standard
625
A A
725
Long
B
402
815
625
815
915
965
FWW500V
FWW600V
FWW700V
FWW800V
FWW1000V
FWW1200V
865
945
1045
865
945
1045
1095
1425
1475
1675
FWW1400V 1825
1045
1145
1195
1525
1575
1775
1925
B
C
C
725
915
965
592
642
1045
1145
1195
1525
1575
1775
627
440
630
680
722 757 760
822 857 860
872 907 910
1202 1237 1240
1252 1287 1290
1452 1487 1490
1925 1602 1637 1640
Number
Of Fans
1
1
2
2
2
2
2
2
2
2
2
2
2
3
3 3
4
4
4
4
WITH BACK PLENUM
E
F
B
40
TERMINAL BOX
MOUNTING HOLE 4-10×16
CONDENSATE DRAIN
R3/4″
AIR VENT
35
WATER SUPPLY
CONNECTION
Rc3/4″
WATER RETURN
CONNECTION
Rc3/4″
5 15
131
242
262
516
WITH BOTTOM PLENUM
E
38
B
40
TERMINAL BOX
MOUNTING HOLE 4-10×16
CONDENSATE DRAIN
R3/4″
AIR VENT
35
WATER SUPPLY
CONNECTION
Rc3/4″
WATER RETURN
CONNECTION
Rc3/4″
5 15
105
131
242
262
497
Model
MCW200V
Standard Drain
Pan
625
A A
Long Drain
Pan
725
B
402
815
865
625
815
945
865
915
725
965
915
592
642
FWW600V
FWW700V
FWW800V
MCW1000V
1045
1095
1425
FWW1200V 1675
1575
1775
1252
1452
B
C
437
627
677
1287
1487
C
D
D
440
630
680
1290
1490
E
E
472
662
712
1322
1522
F
F
1045
1145
1195
1525
722
822
872
722 757 760 792 740
822 857 860 892 840
872 907 910 942 890
1202 1237 1240 1272
1602 1637 1640 1672 1620
Number
Of Fans
1
2
1
2
2
2
2
3
3
2
2
2
2
2
2
4
3
4
4
4
Standard
625
A
Long Drain
Pan
725
FWW200V 625
FWW300V 815
FWW400V 865
FWW500V
FWW600V
945
1045
FWW700V
FWW800V
MCW1000V
MCW1200V
1095
1425
FWW1200V 1675
FWW1400V 1825
B
B
402
592
642
C
C
627
440
630
680
472
662
712
G
G
441
581
681
1045 722 757 760 792 761
1145
1195
1525
822 857 860 892 861
872 907 910 942 911
1202 1237
910
861
911
1525 1202 1237 1240 1272 1241
1775
1252
1452
1287
1487
1240
1290
1490
1272
1322
1522
1241
1575 1252 1287 1290 1322 1291
1775 1452 1487 1490 1522 1491
1602 1637 1640 1672 1641
Number
Of Fans
1
1
2
2
2
2
2
2
2
3
3
2
2
2
2
3
4
4
4
4
䖛Ⓒ㔥ᣵᵓ
G
10
Electrical Data
FWW-VC
MODEL
INSULATION GRADE
12Pa
MOTOR
POWER
SOURCE
RATED INPUT
POWER
RATED
RUNNING
CURRENT
V/Ph/Hz
W
A
POLES
INSULATION GRADE
POWER
SOURCE
V/Ph/Hz
FWW200VC FWW300VC FWW400VC FWW500VC FWW600VC FWW700VC FWW800VC FWW1000VC FWW1200VC FWW1400VC
B
32
0.15
43
0.20
56
0.26
73
0.34
93
0.43
220~/1/50
4P
B
113
0.52
220~/1/50
133
0.61
152
0.70
188
0.86
228
1.12
30Pa
MOTOR
RATED INPUT
POWER
RATED
RUNNING
CURRENT
W
A
POLES
INSULATION GRADE
POWER
SOURCE
V/Ph/Hz
50Pa
MOTOR
RATED INPUT
POWER
RATED
RUNNING
CURRENT
POLES
W
A
39
0.18
46
0.21
53
0.24
62
0.28
72
0.33
80
0.37
83
0.38
95
0.44
107
0.49
112
0.51
4P
B
4P
122
0.56
220~/1/50
131
0.60
142
0.65
168
0.77
174
0.80
200
0.92
217
1.00
237
1.09
250
1.19
290
1.45
NOTES:
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL ELECTRIC DATA ARE BEING TESTED UNDER HIGH SPEED.
11
Wiring Diagrams
Molde: FWW 200-1400
H
M
L
FAN SPEED SWITCH
(220V~ /50Hz)
NOTE:
HF: FAN SPEED HIGH
MF: FAN SPEED MEDIUM
LF: FAN SPEED LOW
— — — — — FIELD WIRING
HF
MF
LF
L
N
YELLOW
BROWN
ORANGE
BLUE
BLACK
FAN
MOTOR
1
BLACK
MOTOR
CAPACITOR
YELLOW
BROWN
ORANGE
BLUE
BLACK
FAN
MOTOR
2 BLACK
MOTOR
CAPACITOR
Only unit 800~1200 have fan motor2
12
Installation
Receiving
All units leaving the DAIKIN plant have been inspected to ensure the shipment of high quality products and reasonable means are utilized to properly pack the fan coil units to protect them in transit.
Carefully inspect all shipments immediately upon delivery. When damage is visible, note this fact on the carrier’s freight bill and request that the carrier sends a representative to inspect the damage. This may be done by telephone or in person, but should always be confirmed in writing.
The shipment should be unpacked in the presence of the agent so that the damage or loss can be determined.
The carrier’s agent will make an inspection report and a copy will be given to the consignee for forwarding to the carrier with a formal claim.
Location
Before installation, please check the following:
There must be enough space for unit installation and maintenance. Please refer to the unit’s drawings and dimensions and fig.1 for the minimum distance between the unit and obstacle.
Please ensure enough space for piping connection and electrical wiring.
Please make sure that the hanging rods can support weight of the unit.
Installation
The unit is designed for concealed ceiling installation.
There are holes on the top of the unit for hanging. Please refer to Fig.1.Fig.2 and Fig.3.
Make sure that the top of the unit is level.
Insulation
1) Use proper insulation material only
2) Chilled water pipes and all parts on the pipes should be insulated
3) It is also necessary to insulated air ducted
4) Adhesive for insulation should work under range 0˚F(-18˚C) to 200˚F(93.3˚C).
Fig.1
OBSTACLE
OBSTACLE
B
CEILING
A≥200mm B≥400mm
13
C≥265mm
A
Fig.2 WITH AND WITHOUT PLENUM FORM:
A
Discharge air
Fig.3 DETAIL A:
NUT
FANCOIL
Terminal block
Ceiling access
Panel with air return
Return air
EXP ANSION SCREW
RECOMMENDED THE
DIAMETER IS 6-8MM
HANGING ROD
FLAT WASHER
Air Duct Connection
Circulatory air pressure drop should be within External Static Pressure
Galvanized steel air ducts are suitable
Make sure there is no leak of air.
Air duct should be fireproof, refer to concerned country national and local regulations.
Pipe Connection
Using suitable fittings as water pipe connections. Refer to the specification
The water inlet is on the bottom while outlet on top.
The connection must be concealed with rubberized fabric to avoid leakage.
Drainpipe can be PVC or steel.
The suggested slope of the drainpipe is at least 1:50.
Wiring
1
) Wiring connection must be done according to the wiring diagram on the unit.
2) The unit must be GROUNDED well.
3) An appropriate strain relief device must be used to attach the power wires to the terminal box.
4) A 7/8” knockout hole is designed on the terminal box for field installation of the strain relief device.
5) Field wiring must be complied with the national security regulations.
14
Valve Kit
The valve kit is applied for 2-pipe system.
The kit consists of (refer structure figure 0):
• 2/3 way valve body is made of brass, maximum working pressure 1.6MPa.
• Electric actuator has the following specifications:
-Power supply: 220V±10%/50/60Hz (±2Hz)
-Activation: ON/OFF
• Hydraulic kit for the installation of the valve on the heat exchanger, complete with 2 ball valves for adjusting the water flow and for closing the water circuit when perform maintenance to the unit.
• Y-strainer protects unit from impurity, increases the service life and insolating valves.
Figure 0
All parts of 2-way valve kit are indicated in the figure 1. ( For right pipe connection unit.)
F
E
A
B
Figure 1
A Ball valve
B Brass connector
C Y-strainer
D Water inlet pipe
E Water outlet pipe
F 2-way valve
D
C
All parts of 3-way valve kit are indicated in the figure 2. ( For right pipe connection unit.)
F
G
C
B
A
A Ball valve
B Brass connector
C Y-strainer
D Connector pipe
E Water inlet pipe
F 3-way valve
G Water outlet pipe
E
D
Figure 2
15
Installation
1. Install the 2-way valve kit as indicated in the pictures of figure 3. (For right pipe connection unit.) As shown as detail A, firstly take apart connector, then install ① to unit with necessary sealing material . Fix
② between ① and ③. At last tighten ③, make sure all of connectors are sealed.
2. Install the 3-way valve kit as indicated in the pictures of figure 4. (For right pipe connection unit.) Detail is as same as 2-way valve unit.
The valve kit has been pre-assembled for easy installation.
• Where needed the connections are pre-coated with sealing material.
• The connections are not tightened for easy adjustment.
• After determining the final position of the valve kit, tighten all connections to obtain water tightness.
209
65
WATER RETURN CONNECTION Rc3/4
WATER SUPPLY CONNECTION Rc3/4
Ĺ
A ķ ĸ
Detail A
218
153
Figure 3 2-Way Valve ķ ĸ
Detail A
Ĺ
A
WATER RETURN CONNECTION Rc3/4
WATER SUPPLY CONNECTION Rc3/4
0 21
16
Insulation
1. The insulation design and materials should be complying with local and national codes and regulations.
2. Chilled water pipes and all parts on the pipes should be insulated.
The flow resistance of the connecting valve/hydraulic kit assembly is obtained from the following formula:
△
P
W
= (Q
W
/100K v
)
2
P
W
is the flow resistance (Pa)
Q
W
is the water flow rate (m
3
/h)
K v
is the flow rate identified in the table
Valve Model
MC-FCV3335G
MC-FCV2334G
DN
20
20
Conncetion
Type
Rc3/4"
Rc3/4"
Valve Type
3-way Valve
2-way Valve
KV
3.4
3.0
Shut-off Pressure
Difference (MPa)
0.18
0.18
Pipe Connection
1. Using suitable fittings as water pipe connections with reference to the outline and dimensions.
2. The water inlet is on the bottom while outlet on top.
3. The connection must be concealed with rubberized fabric to avoid leakage.
4. Tightening torque should not be too high when connecting water pipes, in order to avoid brass deformation or water-leakage by torsion split.
Wiring
1. Refer to the wiring diagram of the appropriate controller.
2. For connection with the DAIKIN controller, position the water temperature probe into the appropriate position. Refer to the dedicated controller installation and operation manual.
17
Warning
● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
The air conditioners manufactured by Daikin Industries have received
ISO 9001 series certification for quality assurance.
Certificate Number. 9601019
The airconditioning factories of
Daikin Industries have received environmental management system standard ISO 14001 certification.
Certificate Number. EMS80362
Cautions on product corrosion
1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the unit close to the sea shore, contact your local distributor.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan http://www.daikin.com/global_ac/
© All rights reserved
Printed with soy ink.
Literature No.: ED-FWW-VC-201607