LENNOX BALTIC BAC/BAH rooftop packaged unit Installation, operating and maintenance manual
Reklaam
Reklaam
INSTALLATION, OPERATING
AND MAINTENANCE
AIR COOLED AND WATER COOLED ROOFTOP PACKAGED UNITS
BALTIC
BAC/BAH
24 - 85 kW
BALTICIV-IOM-1711-E
www.lennoxemea.com
TABLE OF CONTENTS
BALTIC
Installation, operating and maintenance
Ref : BALTIC-IOM-1711-E
INSTALLATION MANUAL
SERVICE MANUAL
CERTIFICATES
3
38
84
Original version is the English one. Other versions are translations.
All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.
BALTIC-IOM-1711-E -1-
BALTIC-IOM-1711-E -2-
TABLE OF CONTENTS
BALTIC
INSTALLATION MANUAL
INTRODUCTION
TRANSPORT & HANDLING
Mandatory handling devices
Dimensions and weights
Minimum clearance around the unit installation
Fork lifting the unit
Removing the forklift protection located under the machine
LIFTING THE UNITS
Lifting the unit with a crane
Lifting the roof curbs
DELIVERY CHECKS
Rating plate
Storage
Maintenance key
Condensate drains
Preliminary checks
Installation requirements
Connections
INSTALLATION ON A ROOF MOUNTING FRAME
Roof opening dimensions
Sealing checks
Leveling adjustable roofcurbs
NON ADJUSTABLE NON ASSEMBLED ROOFCURB INSTALLATION
Frame parts packing
Installation
Assembly
Securing the frame
CURBING AND FLASHING
Sealing checks
Curbing and flashing
DUCT CONNECTIONS
ELECTRICAL CONNECTION
WATER COOLED UNITS
HEAT RECOVERY
General description
Plate heat recovery - Configurations
Plate heat recovery - Installation
Thermodynamic heat recovery - Configurations
Thermodynamic heat recovery - Installation
Thermodynamic heat recovery - Control
BALTIC-IOM-1711-E
4
12
13
17
17
17
22
22
23
24
25
20
21
21
21
29
30
31
33
34
36
-3-
14
14
14
15
15
15
15
8
9
10
10
10
INTRODUCTION
Safety codes & regulations
THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL SAFETY CODES AND REGULATIONS AND CAN ONLY BE
USED IN WELL VENTILLATED AREA.
PLEASE READ CAREFULLY THE MANUFACTURER’S INSTRUCTIONS BEFORE STARTING THIS UNIT.
INSPECTIONS AND REQUALIFICATION ACCORDING PRESSURE EQUIPMENT DIRECTIVE MUST FOLLOW THE LOCAL
REGULATIONS WHERE THE UNIT IS INSTALLED.
EMC DIRECTIVE COMPLIANCE
WARNING:
This equipment is a “B class” (or “A class“ if equipped with EBHO or ERVF option) according EMC Directive. The units meet the following hardest environments standards:
EN 61000-6-3: program for environment residential, commercial and light industry (or EN 61000-6-4 if equipped with EBHO or ERVF option)
EN 61000-6-2: immunity for industrial environments.
In emission devices having a rated current I < 75A:
- The short-circuit ratio Rsce is: 33 (EN 61000-3-12)
The maximum network impedance authorized Zmax is: 0.30 Ohms (EN 61000-3-11)
The differences between the various machines are only related to the power of the compressors and equipment that there are associated. For conducted and radiated emission and immunity, these differences do not alter the results.
Important note for unit fitted with gas burner:
THIS MANUAL IS ONLY VALID FOR UNITS DISPLAYING THE FOLLOWING CODES:
GB IR GR DA NO FI IS
In case these symbols are not displayed on the unit, please refer to the technical documentation which will eventually detail any modifications required to the installation of the unit in a particular country.
• If machine is including gas burner, minimum clearance around the unit must be at least 8 m to allow a proper gas flue dilution. If not possible, the fresh air intake must be ducted at least 8 m away from the gas burner exhaust.
• The gas burner air intake and exhaust chimney must not be modified or ducted.
• Before commissioning this type of unit, it’s mandatory to ensure that the gas distribution system is compatible with the adjustments and settings of the unit.
• Gas module can only be used for outdoor installations.
• Any work on gas module must be carried out by qualified engineer.
F-Gas REGULATION
Operators of refrigeration equipment’s must comply with the obligations defined in:
- EU Regulation No 517/2014 on fluorinated greenhouse gases
- EC 1005/2009 on substances that deplete the ozone layer
Non compliance with these requirements is an offence and liable of financial penalties.
Moreover, in case of problem it is mandatory to prove to the insurance company that the equipment complies with the F-gas
Regulation.
BALTIC-IOM-1711-E -4-
INTRODUCTION
WARRANTY
The warranty of the unit is subject to the warranty definitions as agreed upon in the order.
It is expected that the design and installation of the unit utilises good working practices.
The warranty will be legally null and void if:
• Service and maintenance have not been executed in accordance with the regulations; repairs have not been carried out
by LENNOX personnel or have been implemented without prior written permission by LENNOX.
• Modifications have been made to the equipment without prior written permission by LENNOX.
• Settings and protections have been modified without prior written permission by LENNOX.
• Non-original or other than the prescribed refrigerants or lubricants are used.
• The equipment has not been installed and/or connected in accordance with the installation instructions.
• The equipment is being used improperly, incorrectly, negligently or not in accordance with its nature and/or purpose.
• A flow protection device is not fitted.
In these circumstances LENNOX is indemnified from any product liability claims from third parties.
In the event of a warranty claim the machine serial number and LENNOX order number must be quoted.
WARNING - All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of LENNOX and must not be utilised (except in operation of this product),reproduced, issued to or made available to third parties without the prior written agreement of LENNOX. The technical information and specifications contained in this manual are for reference only. The manufacturer reserves the right to modify these without warning and without obligation to modify equipment already sold.
SAFETY
The safety information contained in this manual is provided as a guide for the safe handling of this installation. LENNOX does not vouch for the completeness of this information and can therefore not accept liability for any possible omissions.
In the roof tops, heat is being transported by a pressurised refrigerant, with changes in pressure and temperature. For air cooled roof tops, fans have been provided to discharge heat into the environment. The protection of operating and maintenance personnel was central in the design of the roof top. Safety features have been included to prevent excessive pressure in the system. Sheet metal parts have been fitted to prevent inadvertent contact with (hot) pipes. For air cooled roof tops, the fans are equipped with protective grids and the electrical control panel is completely touch-proof. This excludes some parts operating at a safe voltage (< 24 Volt). The service panels can only be opened using tools.
The electrical control panel is completely touch-proof. This excludes some parts operating at a safe voltage (< 50 Volt). The service panels can only be opened using tools.
Notwithstanding that the roof tops are equipped with extensive safety and protection features, the utmost care and attention is needed when carrying out operations on the machine. Furthermore, ear protection should be worn when working on or in the vicinity of the roof tops. Operations on the cooling circuit or electrical equipment should be carried out by authorised personnel.
It is essential to follow non exhaustive recommendations hereunder:
• Never work on a unit that is still energized.
• Any manipulation (opening or closing) of a shut-off valve must be carried out by a qualified and authorised engineer. These procedures must be carried out with the unit shut-down.
• Never work on any of the electrical components, until the general power supply to the unit has been cut. During any maintenance operations on the unit, lock the power supply circuit in the open position ahead of the machine. If the work is interrupted, check the lock before resuming the work.
WARNING: Even if the unit has been switched off, the power circuit remains energized, unless the unit or circuit disconnect switch is open. Refer to the wiring diagram for further details.
• For some units, a separate 220V power supply may exist, check the electrical wiring for more informations
• In case of maintenance operations on fans (grills replacement …) ensure that the power is shut off to avoid automatic restart.
• Before the opening of the refrigerant circuit, check the pressure with manometers or pressure sensors, and purge the circuits.
• Never leave a unit stopped with valves closed on the liquid line, refrigerant could be trapped and the pressure would rise.
• All installation parts must be maintained by the personnel in charge, in order to avoid material deterioration and injuries to people.
Faults and leaks must be repaired immediately. The authorized technician must have the responsibility to repair the fault immediately.
Each time repairs have been carried out to the unit, the operation of the safety devices must be re-checked.
• Follow guidance and recommendations given in safety and machine standards such as EN378, ISO5149, etc
• Do not use oxygen to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and other common substances.
• Never exceed the specified maximum operating pressures. Verify the allowable maximum high- and low-side test pressures by checking the instructions in this manual and the pressures given on the unit name plate.
• Do not use air for leak testing. Use only refrigerant or dry nitrogen.
• Do not unweld or flame cut the refrigerant lines or any refrigerant circuit component until all refrigerant (liquid and vapour) has been removed from roof top. Traces of vapour should be displaced with dry air nitrogen. Refrigerant in contact with an open flame produces toxic gases.
• Do not siphon refrigerant
• Avoid spilling liquid refrigerant on skin or splashing it into the eyes. Use safety goggles. Wash any spills from the skin with soap and water. If liquid refrigerant enters the eyes, immediately and abundantly flush the eyes with water and consult a doctor.
BALTIC-IOM-1711-E -5-
INTRODUCTION
Safety definition
The rooftops meet the following safety definitions, and is provided with CE markings if applicable (for further information see EU declaration).
-
EN 378-2016
- 2006/42/EC “Machine Directive”
- EN-60204-1
- 2014/30/EU “EMC Directive”
- Pressure Equipment Directive 2014/68/EU
- EU 517/2014 F-Gas
- Gas Equipment Directive 2009/142/EC
- 2014/35/EU Low Voltage Directive
- 2011/65/EU RoHS Directive
- 2012/19/EU WEEE
- 2009/125/EC Ecodesign (If applicable)
- EC 1005/2009
WARNING
Warning labels
The roof top is marked with the following warning labels to alert to potential hazards (on or near the potentially hazardous part).
High temperatures Electrical Voltage Rotating parts Sharp parts
Regularly check that the warning labels are still in the correct positions on the machine and replace them if necessary.
!
Warning
:
1.
Attention: The high-pressure safety switches are essential elements which guarantee the system remains within the admissible operating limits. Before switching on the installation, always ensure all electrical connections are correct on these elements which are used to isolate the electrical power supply to the compressor(s) they protect. Carry out a test to ensure the electrical power supply is effectively isolated when the pressure switch attains its set value.
2.
In case of installation in a seismic zone or in a zone which may be effected by violent natural occurrences such as storms, tornados, floods, tidal waves, etc…, the installer and/or operator will refer to valid standards and regulations in order to ensure the devices required are available as our units are not designed to operate under such conditions without prior precautions.
3.
The equipment is not designed to resist fire. The installation site will therefore have to respect valid standards with regard to protection against fire (emergency instructions, map…).
4.
In case of exposure to corrosive external atmospheres or products, the installer and/or operator shall take the necessary precautions to avoid damage to the equipment and will make sure the equipment provided has the necessary and sufficient anticorrosion protection.
5.
To respect a sufficient number of supports for the piping according to their size and weight under operating conditions and to design the piping to avoid a water hammer phenomenon
6.
For technical reasons, it is not possible to carry out hydrostatic tests on all our units so leak tests are carried out as a compensatory measure. (The entire circuit is checked using leak detectors). For machines charged with refrigerant, at the end of the test, an HP test is carried out in the factory to make sure the pressure switch is working properly.
7.
Before any work is carried out on the refrigeration circuit, the dry air or nitrogen pressure our units are supplied with must be released (For units not charged with refrigerant in the factory.)
8.
The emissions of refrigerant via the safety relief valves must be channeled to the exterior of the machine room. The outlet relief valve will have to be sized in compliance with EN13136.
9.
Installation and maintenance of these machines must be carried out by personnel qualified to work on refrigeration equipment.
10. All interventions must be carried out in conformity with valid safety regulations (e. g.: NF EN 378), as well as the recommendations indicated on the labels and handbooks provided with the machine. All actions shall be taken to avoid access of unauthorized persons.
11. It is essential that any pipework or other components of the refrigeration circuit hazardous to people because of their surface temperature are insulated or identified.
12. Ensure that the installation zone (room or area) of the machine has restricted access and ensure the good condition of the covering.
BALTIC-IOM-1711-E -6-
INTRODUCTION
The following note must be followed carefully
Main Safety Recommendations
All work on the unit must be carried out by a qualified and authorised employee.
Non-compliance with the following instructions may result in injury or serious accidents.
Work on the unit:
• The unit shall be isolated from the electrical supply by disconnection and locking using the main isolating switch.
• Workers shall wear the appropriate personal protective equipment (helmet, gloves, glasses, etc.).
Work on the electrical system:
• Work on electric components shall be performed with the power off (see below) by employees having valid electrical qualification and authorisation.
Work on the refrigerating circuit(s):
• Monitoring of the pressures, draining and filling of the system under pressure shall be carried out using connections provided for this purpose and suitable equipment.
• To prevent the risk of explosion due to spraying of coolant and oil, the relevant circuit shall be drained and at zero pressure before any disassembly or unbrazing of the refrigerating parts takes place.
• There is a residual risk of pressure build-up by degassing the oil or by heating the exchangers after the circuit has been drained.
Zero pressure shall be maintained by venting the drain connection to the atmosphere on the low pressure side.
• The brazing shall be carried out by a qualified brazier. The brazing shall comply with standard NF EN1044 AG107 (minimum 30% silver).
Replacing components:
• Replacement of components shall be carried out using spare parts, or using parts approved by LENNOX.
• Only the refrigerant shown on the manufacturer’s nameplate shall be used, to the exclusion of all other products (refrigerant blends, hydrocarbons, etc.).
Transport – Handling- Access:
• Never lift the unit without forklift protections
• Installation of the unit and accessibility must be compliant with the local regulations. Ensure that all access equipments allow maintenance operation in safety (electrical cabinet, main switch, panels, filter, refrigerant circuit…)
• It is strictly forbidden to walk or store equipment or material on top of the rooftop unit
• Equipment designed to withstand transport and handling according to the established protocol (for the handling protocol, please refer to the installation instructions for the relevant product range).
• All unloading operations must be carried out with suitable equipment (crane, forklift truck, etc.).
• When using a forklift truck, you must respect the positions and the direction of handling indicated on the products.
• The equipment must be handled with care to avoid damage to the bodywork, pipework, condenser, etc.
Rooftop installation in heavy wind locations
• The roofcurbs (vertical & horizontal) and rooftops installations are designed to withstand winds up to 80 km/h. Above this limit, it’s recommended to take appropriate actions to secure the installation.
• Ensure the fresh air inlet does not face prevailing wind direction.
Filters:
• Do the filters fire classification’s choice according to local regulations.
Fan compartment:
• Stop the power before accessing the fan compartment.
Warning: the unit is working under pressure. Never open the panels when the unit is working. Even after shutting down the unit, wait for 2 minutes until the fans are completely stopped before opening any panel.
CAUTION:
In the event of fire, refrigerating circuits can cause an explosion and spray coolant gas and oil.
Gas:
• Any work on gas module must be carried out by qualified personnel
• A unit with gas module must be installed in accordance with local safety codes and regulations and can only be used for outdoor installation.
Warning:
- The units are not designed to resist to a fire. The installation site must comply with the standards relating to fire protection.
- In case of installation of the units in an area recognized as being potentially at risk for natural phenomena (tornado, earthquake, tidal wave, lightning...), please follow the standards and regulations, and provide the necessary devices to prevent from these risks.
BALTIC-IOM-1711-E -7-
TRANSPORT & HANDLING
Mandatory handling devices
MANDATORY HANDLING DEVICES
Handling slings to guide the unit toward the roof curb
Vacuum lifting beam to position the unit
BALTIC-IOM-1711-E -8-
TRANSPORT & HANDLING
Dimensions and weights
Machine
C-box
D-box
Length
(mm)
2283+/-15
Width
(mm)
2250+/-15
E-box
2783+/-15
3663+/-15
2250+/-15
2250+/-15
Height
(mm)
1260+/-15
1260+/-15
1260+/-15
Width with hood
(mm)
2683+/-20
2683+/-20
2683+/-20
Transport lenght
(mm)
2310
2810
3690
Transport
Width
(mm)
2309
2309
2309
Transport
Height
(mm)
1260
1260
1260
BAH – Air cooled
Weight of basic units without any options.
24 30 38 42 45 52 57 65 75 85
598 600 650 655 847 851 904 914 1134 1136
All weights are given in kg (+/- 5%).
Individual weight of a given rooftop is indicated on the rating plate and on the sale’s offer
BALTIC-IOM-1711-E -9-
TRANSPORT & HANDLING
Minimum clearance around the unit installation
Figure below show the required clearances and service access around the unit.
IMPORTANT note for unit clearances
• Ensure the fresh air inlet does not face prevailing wind direction.
• If machine is including gas burner, minimum clearance around the unit must be at least 8 m to allow a proper gas flue dilution. If not possible, the fresh air intake must be ducted at least 8 m away from the gas burner exhaust.
• In case of extraction option, it is recommended to duct fresh air intake.
• An approach ramp must be installed if the unit’s installation requirements tell that it's necessary to reach the main switch, the electrical cabinet, the compressor and the ventilation compartment. This recommendation is valid for all type of installations.
• It is also important to respect a minimal clearance of 3 meters above of the unit, to allow a good operation of the outdoor fans.
3000
C Box
D Box
E Box
Drain pan clearance (A)
1150 mm
1650
mm
2150
mm
Fork lifting the unit
Do not lift the unit by the side (coil end side or drain pan outlet side). This will damage the unit.
Lift the unit on the long side using a forklift with dimensions according to the figure below.
Do not remove the unit plastic cover while lifting.
Plastic cover must not be removed before lifting
NO
DO NOT LIFT THIS SIDE
BALTIC-IOM-1711-E -10-
TRANSPORT & HANDLING
Removing the forklift protection located under the machine
Before installation, remove the forklift protection which is located under machine desk.
IMPORTANT note about forklift protection removal
Take care not to hurt anybody when removing the forklift rails .
Locate the machine on a safe area while removing the forklift rails from the machine.
BALTIC-IOM-1711-E -11-
LIFTING THE UNITS
Lifting the unit with a crane
Lifting shackles dimensions
Use lifting shackles on each lifting lug located on each angle of the unit. Maximum diameter of the ring shaft = 20 mm.
Lifting belts/straps length
The unit must be lifted using spacing beams to avoid the belts damages to the casing.
Spacing beams must have a length equal to the machine width – i.e 2250 mm.
5 m
Spacer Beam
BALTIC-IOM-1711-E -12-
LIFTING THE UNITS
Lifting the roof curbs
Ducting connection details
The supply and return air ducts can be secured to the 30 mm flanges at the bottom of the roofcurb
Any ducting weight above 100 kg must be fixed independently to other building frames.
Minimum distance: 30 mm
BALTIC-IOM-1711-E -13-
DELIVERY CHECKS
On receipt of new equipment please check the following points.
It is the customer’s responsibility to ensure that the products are in good working order:
• The exterior has not been damaged in any way.
• The lifting and handling equipment are suitable for the equipment and comply with the specifications of the handling instructions enclosed here-in.
• Accessories ordered for on site installation have been delivered and are in good working order.
• The equipment supplied corresponds to the order and matches the delivery note.
If the product is damaged, exact details must be confirmed in writing by registered post to the shipping company within 48 hours of delivery (working days). A copy of the letter must be addressed to LENNOX and the supplier or distributor for information purposes.
Failure to comply will invalidate any claim against the shipping company.
Rating plate
The rating plate provides a complete reference for the model and ensures that the unit corresponds to the model ordered. It states the electrical power consumption of the unit on start-up, its rated power and its supply voltage. The supply voltage must not deviate beyond +/-5 %. The start-up power is the maximum value likely to be achieved for the specified operational voltage. The customer must have a suitable electrical supply. It is therefore important to check whether the supply voltage stated on the unit's rating plate is compatible with that of the mains electrical supply.
The rating plate also states:
• year of manufacture
• weight of the unit
• type of refrigerant used + GWP : Global warming potential
• required charge for each circuit
• operating Pressure min/max
• operating Temperature min/max
CE marking : 3 possible cases
• CE
• CE0038
• Absence of CE marking
Storage
When units are delivered on site they are not always required immediately and are sometimes put into storage. In the event of medium to long-term storage, we recommend the following procedures:
• Ensure that there is no water in the hydraulic systems.
• Keep the heat exchanger covers in position.
• Keep protective plastic film in position.
• Ensure the electrical panels are closed.
• Keep all items and options supplied in a dry and clean place for future assembly before using the equipment.
• Store the unit on an appropriate place (flat surface).
• Storage temperature must be respected according to the information given on the rating plate
Maintenance key
On delivery we recommend that you keep the key which is attached to an eyebolt in a safe and accessible place. This allows you to open the panels for maintenance and installation work.
The locks are ¼ turn + then tighter.
After commissioning, all the panels must be closed and locked.
After any maintenance operation, all the panels must be closed and locked.
BALTIC-IOM-1711-E -14-
DELIVERY CHECKS
Condensate drains
The condensate drains are not assembled when delivered and are stored in the electrical panel with their clamping collars. To assemble them, insert them on the condensate tray outlets and use a screwdriver to tighten the collars. The drains must be installed in vertical position.
Preliminary checks
Before installing the equipment, the following points MUST be checked:
• Have the forklift protections been removed?
• Is there sufficient space for the equipment?
• Is the surface on which the equipment is to be installed sufficiently solid to withstand its weight? A detailed study of the frame must be made beforehand. The surface on which the equipment is to be installed must be flat. (See next paragraph)
• Do the supply and return ductwork openings excessively weaken the structure?
• Are there any obstructing items which could hinder the operation of the equipment?
• Does the electrical power available correspond to the equipment's electrical specifications?
• Is drainage provided for the condensate?
• Is there sufficient access for maintenance?
• Installation of the equipment could require different lifting methods which may vary with each installation (helicopter or crane). Have these been evaluated?
• Ensure that the unit is installed in accordance with the installation instructions and local applicable codes.
• Check to ensure that the refrigerant lines do not rub against the cabinet or against other refrigerant lines.
In general, make sure no obstacles (walls, trees or roof ledges) are obstructing the duct connections or hindering assembly and maintenance access.
Installation requirements
• The surface on which the equipment is to be installed must be clean and free of any obstacles which could hinder the flow of air to the condensers:
• Avoid installing two units side by side or close to each other as this may restrict the airflow to the condensers, and could limit the access for maintenance purposes.
• Uneven surfaces are prohibited. The surface must be flat and respect a maximal flatness of 0.5mm per linear meter (in both directions length and width).
• The surface must support continuously the entire area of the unit/curb (no rubber pad, no spring, no block…).
Before installing a packaged rooftop unit it is important to understand:
• The direction of prevailing winds
• The direction and position of air flows.
• The external dimensions of the unit and the dimensions of the supply and return air connections.
• The arrangement of the doors and the space required to open them to access the various components.
Connections
• Ensure that all the pipe-work crossing walls or roofs are secured, sealed and insulated.
• To avoid condensation problems, make sure that all pipes are insulated according to the temperatures of fluids and type of rooms.
NOTE: The packaging protection fitted on the finned surfaces must be removed prior to start up.
BALTIC-IOM-1711-E -15-
INSTALLATION ON A ROOF MOUNTING FRAME
Non adjustable roofcurb Adjustable roofcurb
Exhaust roofcurb Multidirectionnal roofcurb
WARNING : all multidirectionnal flowcurb and horizontal extraction flow curb must be secured to the ground using existing fixing holes on the frame.
WARNING : all the roofcurb must be strongly secured to the ground
The contact to the ground must be realized with the entire contact area of the roofcurb (no discontinuous contact).
BALTIC-IOM-1711-E -16-
INSTALLATION ON A ROOF MOUNTING FRAME
IMPORTANT NOTE:
all the curb must be strongly secured to the ground
The contact to the ground must be realized with the entire contact area of the curb (no discontinuous contact).
Roof opening dimensions
The roof opening dimensions & maximum slope are defined according mechanical drawings.
Sealing checks
IMPORTANT note: Prior to put the machine on the curbs make sure polyethylene foam is fitted on the curb upper flange side (must be delivered with the curb).
This gasket must be put only on the internal perimeter of the curb
Levelling adjustable roofcurbs
Above all, ensure that all the adjustable returns are facing outward. They could be turned inside-out for transport.
Transport position only
Correct position for installation
Place the roof mounting frame on the trimmer beam by first lining up the inlet and the outlet opening.
After levelling the frame, secure the adjustable returns on the trimmer.
BALTIC-IOM-1711-E -17-
INSTALLATION ON A ROOF MOUNTING FRAME
IMPORTANT NOTE: Securing the curb
When the roofcurb is correctly positioned, it is essential to secure the assembly with a disconnected stitched welded seam (20 to 30 mm every 200 mm) or self-taping screws (every 200mm) along the outside.
Example with welded seam
Example with screws
BALTIC-IOM-1711-E -18-
INSTALLATION ON A ROOF MOUNTING FRAME
Positioning the rooftop on adjustable roofcurbs
IMPORTANT note: Prior to put the machine, make sure to put a polyethylene gasket on the curb upper flange side (must be delivered in the curb package).
This gasket must be put only on the internal perimeter of the curb
BALTIC-IOM-1711-E -19-
NON ADJUSTABLE NON ASSEMBLED ROOFCURB INSTALLATION
Frame parts packing
Different parts are used in the assembly of this roof mounting frame. There are delivered stacked on a pallet.
BALTIC-IOM-1711-E
Water foam - 5680255T
-20-
NON ADJUSTABLE NON ASSEMBLIED ROOFCURB INSTALLATION
Installation
The roof mounting frame provides support when the units are installed in down-flow configurations.
The non adjustable, non assembled roof mounting frame can be installed directly on decks having adequate structural strength or on roof supports under deck. See drawing for frame dimensions, location of supply and return air opening
NOTE: frame assembly must be installed flat, levelled within 5mm per linear meter in any direction.
Assembly
The frame is supplied as a single package and shipped folded down for ease of transport and handling. It is easy field assembled as all parts required are supplied with the frame.
Unit support rail
Unit floor insulation + gasket
Air duct
Fixing flange
Roof curb
Securing the frame
To ensure proper mating with units, it is mandatory that the roof mounting frame be squared to roof structure as follows:
• With frame positioned levelled in the desired location on roof trusses, tack weld corner of frame.
• Measure frame diagonally from corner to corner as shown above. These Dimensions must be equal in order for the fame to be square.
• It is extremely important to sight frame from all corner to ensure it is not twisted across. Shim frame under any low side. The maximum slope tolerance is 5mm per linear meter in any direction.
• After the frame has been squared, straightened and shimmed, weld or secure the frame to the roof deck.
NOTE: It must be securely fastened to the roof as per local codes and regulations.
BALTIC-IOM-1711-E -21-
CURBING AND FLASHING
Sealing checks
IMPORTANT NOTE: After assembling the kit curb and prior to put the machine on it, make sure to put a poly- ethylene foam on the curb upper flange side (must be delivered in the curb package).
This gasket must be put only on the external perimeter of the curb
CURBING AND FLASHING
Check that the insulation is continuous, counter flash and seal around the frame as shown.
CAUTION: To be effective, the upstream must end below the drop edge. Where pipes and electrical conduits extend through the roof, flashing must conform to local codes of practice
Before installing the equipment, make sure that seals are not damaged and check that the unit is secured to the mounting frame. Once in position, the bottom of the equipment must be horizontal. The installer must comply with local authority standards and specifications.
Gasket
Rooftop
Sealing
Insulation
Roofcurb
* Check that the roofcurb height is enough to respect a sealing height of 150mm minimum (French DTU 43.3) considering the building specifications : geometry of the roof, material and thickness of the insulations and other protection layers, slope of the roof…).
BALTIC-IOM-1711-E -22-
DUCT CONNECTIONS
RECOMMENDATIONS FOR DUCTS CONNECTIONS
Some rules must be complied with for the connections between ducts and unit done on site.
Whatever the supply configuration is, respect a minimal duct’s length (D) of 2m before any elbow or any duct’s diameter change.
Directional vanes must be fitted inside any elbow fitted in return or supply ductwork closer than 5 meter to the machine connection flanges.
Horizontal supply
> 2m
< 2m
Vertical supply
> 2m
< 2m
BALTIC-IOM-1711-E -23-
ELECTRICAL CONNECTION
Accessibility for main switch connection on C-Box (size 24-30-38-42)
In case of full options control panel, the access to connect the power cable to the main switch can be limited. Therefore a removable hatch is available at the back of the control board (accessible from the ventilation panel). When the cable connection is finished, it’s important to put the hatch back in its initial position.
BALTIC-IOM-1711-E -24-
WATER COOLED UNITS
WATER SOURCE HEAT PUMP ONLY
Water connections
The water circulating pump will be preferably installed upstream so that the evaporator/condenser will be subjected to positive pres- sure. Inlet and Outlet water connections are indicated on the certified drawing sent with the unit or shown in the sales brochure.
The water pipes connected to the unit must not transmit any radial or axial force or any vibration to the heat exchangers.
It is important to follow non exhaustive recommendations hereunder:
•Comply with the water inlet and outlet connections shown on the unit.
• Install manual or automatic air purge valves at all high points in the circuit.
• Install a safety valve as well as an expansion tank to maintain the circuit pressure.
• Install thermometers in both the inlet and outlet water connections.
• Install drain connections at all low points to allow the whole circuit to be drained.
• Install stop valves, close to the inlet and outlet water connections and easily accessible for maintenance.
• Use flexible connections to reduce vibrations transmission.
• After testing for leaks, insulate all pipe work, to reduce thermal leaks and to prevent condensation.
•If the external water pipes are in an area, where the ambient temperature is likely to fall below 0°C, insulate the piping and add an electric heater.
• Ensure full earthling continuity
A drainage plug is located at the base of the evaporator. A drainage pipe may be connected to this to enable drainage of evaporator water for service operations or for seasonal shut down.
Connections at the inlet and outlet are Victaulic type.
Water analysis
The water must be analysed; the water circuit installed must include all items necessary for treatment of the water: filters, additives, intermediate exchangers, bleed valves, vents, isolating valves etc... depending on the results of the water analysis.
We do not advise operation of the units with open loops which can cause problems with oxygenation, or operation with untreated ground water.
!
Use of untreated or improperly treated water can cause deposits of scale, algae and sludge or cause corrosion and erosion. It is advisable to call in a qualified water treatment specialist to determine what kind of treatment will be necessary. The manufacturer cannot accept liability for damage caused by the use of untreated or improperly treated water, salt water or brine.
Here are our non exhaustive recommendations given as an indication:
• No NH4+ ammonium ions in the water, they are very detrimental for copper. <10mg/l
• Cl- Chloride ions are detrimental for copper with a risk of perforations by corrosion by puncture. < 10 mg/l.
• SO42- sulphate ions can cause perforating corrosion.< 30 mg/l.
• No fluoride ions (<0.1 mg/l).
• No Fe2+ and Fe3+ ions with dissolved oxygen. Dissolved iron < 5 mg/l with dissolved oxygen < 5 mg/l. Over those values, it means a corrosion of steel which may generate a corrosion of copper parts under deposite of Fe – this is mainly the case with shell and tube heat exchangers.
• Dissolved silicon: silicon is an acid element of water and can also lead to corrosion risks. Content < 1mg/l.
• Water hardness: TH >2.8 K. Values between 10 and 25 can be recommended. This will facilitate scale deposit that can limit corrosion of copper. TH values that are too high can cause piping blockage over time.
• TAC< 100.
• Dissolved oxygen: Any sudden change in water oxygenation conditions must be avoided. It is as detrimental to deoxygenate the water by mixing it with inert gas as it is to over-oxygenate it by mixing it with pure oxygen. The disturbance of the oxygenation conditions encourages destabilisation of copper hydroxides and enlargement of particles.
• Specific resistance – electric conductivity: the higher the specific resistance, the slower the corrosion tendency. Values above 3000
Ohm/cm are desirable. A neutral environment favours maximum specific resistance values. For electric conductivity values in the order of 200-6000 S/cm can be recommended.
• pH: pH neutral at 20°C (7 < pH < 8)
If the water circuit must be emptied for longer than one month, the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration.
BALTIC-IOM-1711-E -25-
WATER COOLED UNITS
Use of untreated or improperly treated water can cause deposits of scale, algae and sludge or cause corrosion and erosion. It is advisable to call in a qualified water treatment specialist to determine what kind of treatment will be necessary. The manufacturer cannot accept liability for damage caused by the use of untreated or improperly treated water, salt water or brine.
Here are our non exhaustive recommendations given as an indication:
• No NH4+ ammonium ions in the water, they are very detrimental for copper. <10mg/l
• Cl- Chloride ions are detrimental for copper with a risk of perforations by corrosion by puncture. < 10 mg/l.
• SO42- sulphate ions can cause perforating corrosion.< 30 mg/l.
• No fluoride ions (<0.1 mg/l).
• No Fe2+ and Fe3+ ions with dissolved oxygen. Dissolved iron < 5 mg/l with dissolved oxygen < 5 mg/l. Over those values, it means a corrosion of steel which may generate a corrosion of copper parts under deposite of Fe – this is mainly the case with shell and tube heat exchangers.
• Dissolved silicon: silicon is an acid element of water and can also lead to corrosion risks. Content < 1mg/l.
• Water hardness: TH >2.8 K. Values between 10 and 25 can be recommended. This will facilitate scale deposit that can limit corrosion of copper. TH values that are too high can cause piping blockage over time.
• TAC< 100.
• Dissolved oxygen: Any sudden change in water oxygenation conditions must be avoided. It is as detrimental to deoxygenate the water by mixing it with inert gas as it is to over-oxygenate it by mixing it with pure oxygen. The disturbance of the oxygenation conditions encourages destabilisation of copper hydroxides and enlargement of particles.
• Specific resistance – electric conductivity: the higher the specific resistance, the slower the corrosion tendency. Values above 3000
Ohm/cm are desirable. A neutral environment favours maximum specific resistance values. For electric conductivity values in the order of 200-6000 S/cm can be recommended.
• pH: pH neutral at 20°C (7 < pH < 8)
If the water circuit must be emptied for longer than one month, the complete circuit must be placed under nitrogen charge to avoid any risk of corrosion by differential aeration.
Antifreeze protection
Use glycol/water solution
!
ADDITION OF GLYCOL IS THE ONLY EFFICIENT WAY TO PROTECT AGAINST FREEZING
The glycol/water solution must be sufficiently concentrated to ensure proper protection and prevent formation of ice at the lowest outdoor air temperatures expected on an installation. Take precautions when using non-passivated MEG antifreeze solutions (Mono Ethylene Glycol or MPG Mono Propylene Glycol). Corrosion can occur with these antifreeze solutions with oxygen.
Drain the installation
!
It is important to make sure that manual or automatic air bleeders are installed at all the high points of the water circuit.
To enable drainage of the circuit, make sure that drain cocks are installed at all the low points of the circuit. To drain the circuit, the drain cocks must be opened and an air inlet ensured.
Note: air bleeders are not designed to admit air.
FREEZING OF A HEAT EXCHANGER DUE TO COLD WEATHER CONDITIONS IS NOT COVERED BY LENNOX WARRANTY.
Electrolytic corrosion
!
We would like to draw your attention to the problems of corrosion due to electrolytic corrosion caused by an imbalance between earthing points.
AN EXCHANGER THAT IS PUNCTURED BY ELECTROLYTIC CORROSION IS NOT COVERED BY THE UNIT
WARRANTY
BALTIC-IOM-1711-E -26-
WATER COOLED UNITS
Minimum water capacity
!
The minimum volume of the water circuit must be calculated with the formula here under. If necessary, install a buffer tank. Proper operation of regulating and safety devices can only be ensured if the volume of water is sufficient.
Vt → Minimum water content of the installation
Q → Chiller cooling capacity in kW
N → Number of control steps available in the unit
Dt
→ Maximum acceptable temperature rise (Dt = 6°c for an air conditioning application)
Vmini = 86 x Q / (N x Dt)
Water loop configuration
Figure below indicates all components used as standard :
• the victaulic type connections (1)
• the inlet water filter, (2)
• the automatic airvent, (3)
• the electronic water flow switch, (4)
• the pressure taps and drain valves, (5)
• the Plate Heat Exchanger (6)
3
2
1
6
5
4
BALTIC-IOM-1711-E -27-
WATER COOLED UNITS
Victaulic connection assembly instruction
Be careful not to roll or pinch the seal when installing the half-shells.
This would cause a leak.
1Install the bolts and tighten the nuts by hand on them.
2tighten bolts uniformly passing from one side to the other, until the pads for the bolts are in metal-metal contact. Make sure the shoulders are well engaged in the grooves.
It is imperative to tighten the nuts evenly to avoid pinching the gasket.
Water filter replacement
It is important that units are serviced regularly by a qualified technician, at least once every year or every 1000 hours of operation.
CAUTION: The water circuit may be pressurised. Observe the usual precautions when depressurising the circuit before opening it. Failure to observe these rules could lead to accidents and cause injury to service personal.
Access for cartridge cleaning
Pressure loss - Plate Heat Exchanger - Water Filter
BALTIC-IOM-1711-E
Unit size
45
52
57
65
75
85
Exchanger Curve
A
A
B
B
B
B
Filter Curve
F
F
F
F
F
F
-28-
HEAT RECOVERY - GENERAL DESCRIPTION
Heat recovery modules have following interests:
• in winter season and heating mode, the heat in the extract air is exchanged with the fresh air ;
• conversely, in summer season and cooling mode, the heat of the fresh air is transferred to the extract air.
HRMV and HRMH are two plates heat exchanger modules, that differ from each other by their horizontal or vertical configuration.
TRMO is a thermodynamic heat recovery module, included in the machine. Its main interests are:
• a variable fresh air rate from 25 to 100%,
• a high COP in winter when pre-heating the fresh air due to a favorable evaporating temperature, especially with high air flow rate;
• a high EER in summer when pre-cooling the fresh air due to a favorable condensing temperature, especially with high air flow rate.
For those reasons, TRMO will be more suitable than HRMV/HRMH in areas where the difference between indoor temperature and outdoor temperature is low. For example, in Mediterranean areas, where winter temperatures are not very cold or summer temperatures are not very high.
BALTIC-IOM-1711-E -29-
PLATE HEAT RECOVERY - CONFIGURATIONS
VERTICAL FLOW EXHAUST ROOFCURB + VERTICAL HEAT RECOVERY MODULE
VRHS
Fresh air
VRVS Return
HORIZONTAL EXTRACTION BOX + HORIZONTAL HEAT RECOVERY MODULE
Return
Return
Fresh air
HRHS
HRVS
VRHS
Vertical return - Horizontal supply
VRVS
Vertical return - Vertical supply
HRHS
Horizontal return - Horizontal supply
HRVS
Horizontal return - Vertical supply
BALTIC-IOM-1711-E -30-
PLATE HEAT RECOVERY - INSTALLATION (ERVF + HRMV)
2c x4
2a x2 x6
5 mm
2b
1. Install the flowcurb according to previous section.
2. Before installing the rooftop: a. Fix the brackets (5 pieces) on the curb by 24 screws (6x16 mm); b. ADJUST the position of the attachment bracket so that it is
5 mm above the support surface (without the foam); c. Install the foam (25x10 mm) on the upper part of the flowcurb.
3b
3. a. Fix the lower mounting bar of the heat recovery module using 4 screws (6x16 mm) and remove the side doors; b. Make sure that the foam is not damaged (20x15 mm).
4. Install the rooftop and remove the lifting covers.
3a
5
5. Place the two upper mounting bars through the two top slots.
6. Install the heat recovery module on the bracket by taking care to position properly the lower mounting bar.
Don't forget to remove the lifting covers from the module.
6
4
6
7
7. Slide the 'T' plate into the lifting lug and place the bolt through it. On the opposite side, place also the bolt (detail A).
8
8. Finally tighten the heat recovery module with the 4 bolts 8x60mm to compress the foam (2 bolts on the upper mounting bars (detail B) and the 2 bolts placed in step 7).
Detail B
7
Detail A
BALTIC-IOM-1711-E -31-
PLATE HEAT RECOVERY - INSTALLATION (EBHO + HRMH)
1. Make sure that the support surface enables to install the rooftop and the heat recovery module perfectly horizontal.
2.
a. Fix the lower mounting bar of the heat recovery module using 4 screws (6x16 mm) and remove the side doors; b. Make sure that the foam is not damaged (20x15 mm).
3. Install the rooftop and remove the lifting covers.
4. Place the two upper mounting bars through the two top slots.
2b
2a
6
5
5. Install the heat recovery module by taking care to position properly the lower mounting bar.
Don't forget to remove the lifting covers from the module.
5
6. Slide the 'T' plate into the lifting lug and place the bolt through it. On the opposite side, place also the bolt ( detail A).
7
7. Finally tighten the heat recovery module with the 4 bolts 8x60mm to compress the foam (2 bolts on the upper mounting bars ( detail B ) and the 2 bolts placed in step 6).
Detail B
6
Detail A
PLATE HEAT ELECTRICAL CONNECTIONS
Two components have to be connected in the space between the plate heat exchanger and the economizer:
• For the air pressostat, connect and tighten the 2 spade-tips on • For the actuator, assembly the two parts of the connector: terminal 1 and 3 (no polarity) :
BALTIC-IOM-1711-E -32-
THERMODYNAMIC HEAT RECOVERY - CONFIGURATIONS
VERTICAL FLOW EXHAUST ROOFCURB + THERMODYNAMIC HEAT RECOVERY MODULE
Fresh air
VRHS
VRVS
Return
HORIZONTAL EXTRACTION BOX + THERMODYNAMIC HEAT RECOVERY MODULE
Return
Return
HRHS
BALTIC-IOM-1711-E
HRVS
VRHS
Vertical return - Horizontal supply
VRVS
Vertical return - Vertical supply
HRHS
Horizontal return - Horizontal supply
HRVS
Horizontal return - Vertical supply
Fresh air
-33-
THERMODYNAMIC HEAT RECOVERY - INSTALLATION
1. REFRIGERATION CIRCUIT
Frigorific components access:
Compressor is located in the fix condenser part. Its access for electrical checking and pressure taps (HP and LP) is made through the screwed access door behind the hinged coil.
4-way valve, thermostatic expansion valve, dryer, and sensors are located on the e-
Drive™ supply compartment.
Electrical components:
• For D and E-box, specific TRMO components are located in the electrical box.
• For C-box, specific TRMO components are located on the back of the electrical box, and can be accessible from the supply e-Drive™ compartment.
2. COMMISSIONING
Electrical connections:
• All wire connections are factory made.
Starting up:
• CLIMATIC™ configuration:
- Power the unit
- Check the configuration of the CLIMATIC™ with the DS in expert mode.
• Flow rate settings:
Make sure that both supply and exhaust air flow are balanced. See section EBHO or ERVF. Balancing is correctly set if:
- with Test = 'B.Nom 100%': at 100% fresh air, set the exhaust Flow 3864 = supply flow 3333;
- then switch Test = 'B.Nom 0%':
1. reduce coefficient 3866 until the louvers are closed;
2. then if the flow (supply and exhaust) is far from the previous flow settings, set coefficient 3335;
3. finally, repeat step 1 and 2 to obtain a constant flow whatever the fresh air mode.
- same settings have to be realized for reduced flow - 3334 and 3865.
WARNING! During the settings, wait until the economizer is fully closed or opened, since it takes 1-2 minutes to switch.
• Start the TRMO circuit (circuit 3): switch Test='C3--Cool'
- check the sense of rotation of the circuit 3 compressor;
- check frigorific values (HP, LP, overheating and subcooling).
• Repeat the last operations with Test='C3--Heat'
BALTIC-IOM-1711-E -34-
THERMODYNAMIC HEAT RECOVERY - INSTALLATION
3. SERVICE DIAGNOSTIC
Refrigeration
Possible causes and symptoms Fault
Low LP and LP cut out
Alarm 317: main frigorific issue
Alarm 327: too low LP
Solution
Lack of charge, obstructed components
Freezing: wait that coil is defrosted by exhaust air;
Air flow too low on evaporating side (too low speed rate / fouled filter or coil).
HP problem and HP cut out
Incorrect airflow rates
Refrigerant charge too high
See also frigorific diagnostic of BALTIC™ section 'Refrigeration'.
Check fan (exhaust or supply) function of the mode (Amps) and also filter.
Check the refrigerant charge load according to the refrigerant load table.
Indoor or exhaust fan blower:
For both indoor supply fan and exhaust fan, same faults, causes and solutions are expected. See diagnostic of 'Indoor fan blower'.
BALTIC-IOM-1711-E -35-
THERMODYNAMIC HEAT RECOVERY - CONTROL
1. CONFIGURATION
Configuration of CLIMATIC™ with the DS in expert mode for TRMO (with a modulating exhaust fan):
3813 RECOV. = Comp. for TRMO
3815 EXHAUST = Modulate for both ERVF & EBHO
3816 KIT
3817 Motor
3818 Fan to be checked function of your need
2. USE
Protection:
• Operating envelop Protection: compressor stopped during 6 minutes.
- 328: min HP = 20.5°C condensation;
- 329: max HP = 62°C condensation;
- 319: min LP = between -24.5°C and 1.6°C (function of the condensation temperature) during 5 min => freezing or air flow on evaporator issue;
- 327: max LP = 26°C.
- 317: limit LP -27°C during 120 sec => frigorific failure (lack of refrigerant /closed components)
• Anti freezing Protection consist in defrosting the exhaust coil in heating mode with the extract air.
Control
• No specific parameters have to be set for TRMO control.
• Operation:
- TRMO runs if there is heating or cooling needs;
- above 50% fresh air, TRMO compressor has priority to start;
- under 15°C return or under 20% fresh air, TRMO compressor is not authorized to start.
BALTIC-IOM-1711-E -36-
BALTIC-IOM-1711-E -37-
TABLE OF CONTENTS
BALTIC
SERVICE MANUAL
COMMISSIONING
Operating limits
Before turning on the power
Wire connection tightness checks
Powering the unit
EDRIVE™ VENTILATION
FRESH AIR HOOD
FILTERS
REFRIGERATION CIRCUIT
HEATING OPTIONS
Hot water coils
Electric heater
Electrical preheater
GAS BURNERS
Preliminary checks before start-up
Starting up the gas burner
Standard start-up chronology
Burner safety checks
Gas module
RECOVERY WATER COIL
SERVICE DIAGNOSTIC
SPARE PART LIST
WARRANTY
MAINTENANCE PLAN
COMMISSIONING RECORD SHEET
REFRIGERANT TRANSACTIONS LOGBOOK
BALTIC-IOM-1711-E -38-
52
53
54
68
69
72
75
76
79
81
55
55
56
59
63
39
40
40
41
44
48
49
50
COMMISSIONING
!
The components are located inside the units or in a separate box and must be installed by a qualified engineer.
Note: In case of plate heat exchangers it is mandatory that a filter is installed at exchanger unit entrance.
These filters must remove all particles with a diameter greater than 1 mm.
OPERATING LIMITS
Prior to any operation, please checks the operation limits of the unit These tables will give you all necessary information concerning the operating envelop of the unit.
WARNING: It is very important ensure the units operate well inside these envelopes.
!
Air Cooled Baltic™
38 42 45 52 57 Size 24 30
Cooling Mode Operating Limits
Max. outdoor temp. at indoor 27°C DB/ 19°C WB °C 48 46
Max outdoor temp with unloading
Min. outdoor temp. at indoor 20°C DB
°C
°C no
-5
50
-5
Max. entering indoor coil temp. at outdoor 38°C DB °C 35 35
Min. entering indoor coil temp. at outdoor 35°C DB °C 18 18
46
50
-5
35
18
45 48
50 no
-5 -5
35 35
18 18
46
50
-5
35
18
46 46
50 50
-5 -5
35 35
18 18
65 75 85
48
50
-5
35
18
Heat Pump Mode Operating Limits
Min. outdoor temp. at indoor 20°C DB (8) °C -12 -12 -12 -12 -12 -12 -12 -12 -12 -12
Min. entering indoor coil temp. at outdoor 7°C DB °C 5 5 5 5 5 5 5 5 5 5
48
50
-5
35
18
Water Cooled Baltic™
45 52 57 65 75 85
Cooling Mode Operating Limits
Max. inlet water temp at indoor 27°C DB/ 19°C WB °C
Max. inlet water temp with unloading °C
Min. inlet water temp. at indoor 20°C DB °C
Max. inlet water temp 100% fresh air at outdoor 35°C °C
Heat Pump Mode Operating Limits
Min. inlet glycoled water temp. at indoor 20°C DB °C
Min outdoor temp with unloading °C
Min. entering indoor coil temp. at outdoor 7°C DB °°C
-15
-17
7
46
48
25
38
-15
-17
7
46
48
25
38
-15
-17
7
46
48
25
38
-15
-17
7
46
48
25
38
-15
-17
7
46
48
25
38
-15
-17
7
46
48
25
38
BALTIC-IOM-1711-E -39-
COMMISSIONING
!
WARNING: commissioning must only be carried out by trained refrigeration engineers whom qualification certificates are compliant with the local regulation
Before turning on the power
WARNING: ensure that the power supply includes 3 phases with no neutral
Ensure that the power supply between the building and the unit meets local authority standards and that the cable specification satisfies the start-up and operating conditions displayed on the name plate.
Wire connection tightness checks
WARNING: check the wire connection tightness
Check the following wire connections for tightness:
• Main switch connections,
• Mains wires linked to the contactors and circuit breakers
• Cables in the 24V control supply circuit.
WATER LOOP CHECK LIST BEFORE START-UP
Check that all drain and purge plugs are in place and well tightened prior to fill the installation with water or brine. Before proceeding with start-up, even for a test of short duration, check the following points, after having made sure that all the valves on the refrigeration circuit are fully open (discharge valves and liquid valves).
• The liquid pump(s) and other apparatus interlocked with the unit (coils, air handling units, dry coolers, cooling towers, terminals such as fan coil units, etc.) are in working order as required by the installation and according to their own specific requirements. Place all water valves and refrigerant valves in their operating positions and start the water circulating pumps.
• the condenser water circuit must be ready to operate, filled with water, pressure tested, bled, filter cleaned after 2 hours of operation of the water pump.
• start the pump(s) check the flow of liquid to be cooled through the heat exchangers: note the inlet and outlet water pressures, and, using the pressure drop curves, calculate liquid flow by applying the following formula:
Actual flow
Q = Q1 x
√(P2/P1)
Where
P2 = pressure drop measured on site
P1 = pressure drop published by LENNOX for a liquid fl ow of Q1
Q1 = nominal flow
Q = real flow
Adjust the condenser circuit water flows (via regulating valves, pump speed position..) to come close to the designed conditions
(LENNOX software).
OIL CHARGE
All units are delivered with a complete oil charge, and there is no need to add any oil before start up or afterwards. Overcharging with oil can cause serious problems on an installation, particularly for the compressors.
Oil Recommendation for LENNOX Roof Tops
Refrigerant Compressor type Brand Oil Type
R410a Scroll Lennox
ICI EMKARATE RL32-3MAF or for refill MOBIL
EAL Arctic 22CC
BALTIC-IOM-1711-E -40-
COMMISSIONING
Powering the unit
Power up the unit by closing the isolator switch (if fitted).
At this point the blower should start unless the CLIMATIC™ does not energise the contactor. Once the fan is running, check the rotation direction. Refer to the rotation arrow located on the fan.
The fans and compressors direction of rotation is checked during the end of line test. They should therefore all turn in either the right or wrong direction.
WARNING: a compressor rotating in the wrong direction will fail shortly.
If the fan turns in the wrong direction (the right direction is shown below), disconnect the main power supply to the machine at the building's mains switch, reverse two phases and repeat the above procedure.
Close all circuit breakers and power up the unit.
If now only one of the components rotates in the wrong direction, disconnect the power supply at the machine's isolator switch (if fitted) and reverse two of the component’s phases on the terminal within the electrical panel.
Check the current drawn against the rated values, in particular on the supply fan.
If the readings on the fan are outside the specified limits, this usually indicates excessive air flow which will affect the life expectancy. In this case reduce rpm using eDrive™.
While starting the unit, fill in the check list sheet of this manual to be sure that the unit correctly installed and ready to operate.
• Check the current values per phase on each fan motor.
• Check the current values per phase on each compressor motor.
• Check suction and discharge pressures and compressor suction temperature.
• Check chilled liquid entering and leaving temperatures if water cooled unit
• Check outdoor air temperature and indoor temperature
• Check liquid refrigerant temperature at the condenser outlet.
• Check if DAD is ON.
These verifications should be made as quickly as possible with a stable cooling load, i.e. the cooling load of the installation should be the same as the capacity developed by the unit. Measurements taken without heeding this condition will result in unusable and probably wrong values.
These verifications can only be made once the proper operation of all safety devices and unit controls has been established.
Check if the customer's air ducts are open to be sure the unit is not running with ducts closed. In addition it is needed to check if the airflow and available static pressure are in accordance with the unit.
BALTIC-IOM-1711-E -41-
COMMISSIONING
CLIMATIC™ configuration
Settings
1. Supply Air-flow adjustement (depending on customer requirements)
a. 3333 = nominal air flow / pressure b. 3334 = reduced air flow / pressure c. 3332 = Manual/Automatic d. 3331 = Nominal/DeadZone/PartLoad/Pressure
2. Exhaust Air-flow adjustement (optional)
a. 3864 = nominal air flow b. 3865 = reduced air flow
3. Scheduling (depending on customer requirements)
a. Zones & Modes (Night/Day/Day I/ DayII) b. Setpoints per mode
4. Regulation temperature probe selection
a. Select the regulation probe (DC, Return, Customer, etc.) in the Room Temp. Config screen
5. Regulation humidity sensor selection (optional)
a. Select the regulation sensor (Remote, Customer) in the Room Hum. Config screen
6. Outside temperature probe selection
a. Select the outdoor temp probe (Unit, Customer) in the Outside Temp. Config screen
7. Outside humidity sensor selection (optional)
a. Select the outdoor hum sensor (Unit, Customer) in the Outside Hum. Config screen
8. Air quality sensor selection (optional)
a. Select the air quality CO2 sensor (Remote, Customer) in the CO2 Config screen
9. Remote display configuration
a. 3151 = DC simple / DC full / DM
10. Minimum fresh air
a. 3121 = minimum opening %
BALTIC-IOM-1711-E -42-
COMMISSIONING
Check:
1. Air-flow Vs Damper
a. Test B.Nom100% : i. adjust the blower speed % (3333) to get the required air-flow ii. adjust the exhaust speed % (3864) to get the required air-flow b. Test B.Nom0%: i. adjust the damper compensation (3335) to maintain the required air-flow even with damper fully closed ii. adjust the damper compensation (3366) to maintain the required air-flow even with damper fully closed
2. Filter safety thresholds
a. Test B.Nom100% and Test B.Nom0% : read filter
ΔP (3442) and adjust the bigger measure multiplied by 2.5 at threshold 3345
3. Frigorific circuit tests
a. Cooling mode i. Test C---Cool: (if variable speed compressor option, set speed value)
1. Check circuit pressures and temperatures
2. Check electrical consumptions b. Heating mode i. Test C---Heat: (if variable speed compressor option, set speed value)
1. Check circuit pressures and temperatures
2. Check electrical consumptions
4. Unit option tests
a. Electrical Auxiliary heaters (Test H1-1 Full) i. Check supply temperature ii. Check electrical consumption b. Hot Water Auxiliary heaters (Test H1-1 Full) i. Check supply temperature ii. Check valve opening c. Gas burner heaters (Test H1-1 Full) i. Refer to gas burner chapter d. Electrical Fresh-air pre-heaters (Test H2-1 Full) i. Check supply temperature ii. Check electrical consumption e. Hot water eRecovery heaters (Test H2-1 Full) i. Check supply temperature ii. Check valve opening f. TRMO
i. Test C3---Cool:
1. Check circuit pressures and temperatures
2. Check electrical consumptions
ii. Test C3---Heat:
1. Check circuit pressures and temperatures
2. Check electrical consumptions
5. Advanced regulation optimization
WARNING! During the settings, wait until the economizer is fully closed or opened, since it takes 1-2 minutes to switch.
a. Compressor
ΔT i. Cooling.
1. T est C1c1 Cool: read │Mix-Supply| temp and adjust compressor stage ΔT at menu 3434 ii. Heating.
1. T est C1c1 Heat: read │Mix-Supply| temp and adjust compressor stage ΔT at menu 3444 b. Auxiliary Heaters
ΔT (Gas burner or electrical) i. Heating.
1. Test H1-
1: read │Mix-Supply| temp and adjust heaters stage ΔT at menu 3734 c. Staging sequence (compressor/electrical/water/burners) i. Aux Heaters Priority 3731= Never/ Always /OutTemp ii. Pre Heaters Priority 3736= First/Last d. Dynamic setpoint i. 3225=
ΔT between customer set point and outdoor temperature e. Fine temperature control i. Smooth 3231= No/ DeadZone/Comfort
6. Leak Detection
a. Cooling i. Test C1--Cool: read Subcooling and adjust 3437 ii. Test C2--Cool: read Subcooling and adjust 3438 b. Heating i. Test C1--Heat: read Subcooling and adjust 3447 ii. Test C2--Heat: read Subcooling and adjust 3448
Once all the settings have been adjusted, the list of parameters must be downloaded (Wizard tool), stored and signed by the customer.
BALTIC-IOM-1711-E -43-
eDrive™ VENTILATION
eDrive™ assembly instructions & specification (AC version)
The flexible elastomeric tire is removable without removing the plates The material is natural rubber
Temperature range from -42°C to + 82°C
Easy to assemble
BALTIC-IOM-1711-E -44-
eDrive™ VENTILATION
eDrive™ mounting (AC version)
eDrive™ assembly is designed to have no adjustment to be made inside the machine
In case of vertical misalignment one could use metallic washer located under the motor to adjust height
Max angular misalignment 4° Max radial misalignment 3mm Max axial range 8 mm Vibration absorbtion
eDrive™ coupling dimensions (AC version)
Machine size
Motor size kW
Motor shaft diameter mm
Fan shaft diameter mm
Coupling
Coupling reference
Coupling type
PP
Motor moteur
Fan taper bushing
Ref ref
C box
C box
C box
C box
C box
D box
D box
D box
D&E box
E box
5,5
2,2
3
4
5,5 to 7,5
9 to 11
1,5
2,2
3
4
25
30
30
30
25
25
25
25
30
40
38
28
28
28
24
28
28
28
38
38
PV60
PV50
PV50
PV50
PV40
PV40
PV40
PV40
PVP50
PV 60
2 x Taper lock bushing
2 x Taper lock bushing
2 x Taper lock bushing
2 x Taper lock bushing
2 x Taper lock bushing
1 Taper lock bushing + D30
1 Taper lock bushing + D30
1 Taper lock bushing + D30
1 Taper lock bushing + D38
2 x Taper lock bushing
28-20 al24 28-20 al25
28-20 al28 28-20 al25
28-20 al28 28-20 al25
28-20 al28 28-20 al25
40-25 a38 40-25 al25
30-25 al28 30-25 al30
30-25 al28 30-25 al30
30-25 al28 30-25 al30
30-25 al30
40-25 al 38 40-25 al 40
eDrive™ airflow reading
eDrive is controling the airflow within the operating range of each kit.
For AC fans airflow rate calculation inputs are rpm and power absorbed output read on the inverter variable bus, while on EC fans it’s based on supply pressure reading.
BALTIC-IOM-1711-E -45-
eDrive™ VENTILATION
eDrive™ is protecting the fan & motor against over-speed & over-amps (AC version)
eDrive™ is designed to keep motor and fan in its available operating range thanks to the kit configuration selected in CLIMATIC™ control. The CLIMATIC™ control is limiting rpm & absorbed power. The table below shows the operating ranges per box and kit size.
eDrive™ unit operating ranges (AC version)
Box Fan type
Motor kW
Efficiency Kit
C Box
BAH
BAC
D Box
BAH
BAC
E Box
BAH
BAC
AT 15-11 S
AT 15-11 S
AT 15-11 S
AT 15-11 S
AT 15-11 S
ADH 355 L
ADH 355 L
ADH 355 L
ADH 355 L
ADH 355 L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
5,5
7,5
9
9
3
4
5,5
7,5
11
1,5
2
3
4
5,5
2,2
0,85
0,85
0,87
0,88
0,87
0,88
0,88
0,88
0,89
0,80
0,83
0,85
0,85
0,87
0,83
K1
K2
K3
K4
K2
K3
K4
K5
K5
K1
K2
K3
K4
K5
K1
Comment
Fan shaft D30
Fan shaft D30
Fan shaft D40
Fan shaft D30
Fan shaft D40
rpm min rpm max
Qv min Qv max Imax
660
738
823
938
648
774
880
880
911
553
610
697
78
882
581
1208
1396
1439
1501
1302
1385
1378
1417
1417
962
1170
1330
1371
1417
939
3600
3750
4500
5550
7200
5500
5500
6100
7100
9500
8300
9700
11500
13100
10000 13500
10000 16000
10000 17750
10000 19000
10000 19000
4800
6000
7050
8250
8400
6900
6,6
8,4
12,2
16,3
12,2
16,3
17,6
17,6
23
3,6
4,9
6,6
8,4
12,2
4,9
Gas unit eDrive™ operating ranges (AC version)
Box Fan type
Motor kW
Efficiency Kit
C Box
BAH
BAC
D Box
BAH
BAC
E Box
BAH
BAC
AT 15-11 S
AT 15-11 S
AT 15-11 S
AT 15-11 S
AT 15-11 S
ADH 355 L
ADH 355 L
ADH 355 L
ADH 355 L
ADH 355 L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
AT 15-11 G2L
7,5
9
9
11
4
5,5
7,5
5,5
1,5
2
3
4
5,5
2,2
3
0,85
0,87
0,88
0,87
0,88
0,88
0,88
0,89
0,80
0,83
0,85
0,85
0,87
0,83
0,85
K2
K3
K4
K5
K3
K4
K5
K1
K1
K2
K3
K4
K5
K1
K2
Comment
ADHE 355
ADHE 355
ADHE 355
ADHE 355
ADHE 355
Axe D30
Axe D30
Axe D30
Axe D30
Axe D30
rpm min rpm max
Qv min Qv max Imax
826
930
1070
760
898
994
994
1072
592
690
788
907
1015
651
727
1409
1499
1578
1310
1431
1476
1476
1525
949
1155
1386
1449
1533
929
1206
3600
3750
4500
5400
6750
5500
5500
6100
7100
9300
11100
8700 13100
10000 13000
10000 15250
10000 17250
10000 17250
10000 19000
4650
5700
6900
7950
8400
6500
7900
8,4
12,2
16,3
12,2
16,3
17,6
17,6
23
3,6
4,9
6,6
8,4
12,2
4,9
6,6
BALTIC-IOM-1711-E -46-
eDrive™ VENTILATION
eDrive™ fan inverter configuration (AC version)
eDrive™ Inverter configuration is prepared in the factory to communicate with CLIMATIC™ & to be configured specifically for the customer machine.
eDrive™ Fan inverter parameters are configured via the CLIMATIC™ unit configuration.
This configuration is selecting the proper parameters to run eDrive™ in its operating range depending on fan type & motor size.
If ever, the Inverter loose fan control (No Fan or Wrong fan speed & Compressor or Heating stay on), one may check the Inverter configuration as below:
“0.0” will be displayed in this case on the Inverter instead of the regular “0” or “xxx” rpm
Switch to unlock mode:
F700 = 0
F732 = 0
On Inverter, set the TYP parameter to 3 value. (reinitialize the Inverter to the default values) then configure the following setpoints:
F800=1
F801=0
F802=11
F803=0
Then switch OFF the whole machine & then switch ON.
Then the CLIMATIC™ is going to send all the proper machine configuration to Inverter (motor size, fan type, Imax, safety parameters) .
BALTIC-IOM-1711-E -47-
FRESH AIR HOOD
Installing
The fresh air hood has to be opened and secured during commissioning.
The 3 parts of the fresh air hood have to be assembled thanks to self taping screws delivered in the spare part box
Check the proper position of the black seal on the top of the hood cover.
Wind direction
The prevailing wind has to be taken into account while choosing the machine position on the building roof.
It’s highly recommended to avoid putting the fresh air hood in the prevailing wind direction to avoid water ingress risks.
If this is not possible please contact us to require specific water droplet strainer in the hood section.
WARNING: the fresh air hood cover can hurt your head if you don’t pay attention while turning around the unit.
BALTIC-IOM-1711-E -48-
FILTERS
Filter replacement
After opening the filter access panel, lift the filter retaining log. The filters can then be removed and replaced easily by sliding the dirty filters out and clean ones in.
The CLIMATIC™ controller can monitor the pressure drop across the filter
The following set points can be adjusted depeding on the installation.
• “Airflow” in page 3343 = 25Pa by default
• “No filter “ in page 3344 = 50Pa by default
• “Dirty Filter” in page 3345 = 250Pa by default
The actual pressure drop measured accross the coil can be read on the CLIMATIC™ Display in menu 3342.
The following faults may be identified
• Fault code 001 AIRFLOW FAILURE, if measured ΔP across the filter and coil is below the value set in page 3343
• Fault code 004 DIRTY FILTERS, if measured ΔP across the filter and coil is above the value set in page 3344
• Fault code 005 MISSING FILTERS, if measured ΔP across the filter and coil is below the value set in page 3345.
BALTIC-IOM-1711-E -49-
REFRIGERATION CIRCUIT
Electronic expansion valve
2 electronic valves types are fitted on BALTIC™: E2V & E3V
Model designation
Reference
Cbox Dbox Ebox
24 30 38 42 45 52 57 65 75 85
E2V30 E2V30 E2V30 E3V45 E2V30 E2V30 E2V30 E2V30 E2V30 E3V45
EEV adjustments
EEV allows the control of superheat in biflow operation (see CLIMATIC™ sections).
E2V welding instructions
Electronic expansion valves are sensitive to dust – strainers must be used in case of replacing.
E3V welding instructions
BALTIC-IOM-1711-E -50-
REFRIGERATION CIRCUIT
Generic refrigerant sketch
Depending on the unit size or the selected options, the number of circuits and compressors can change.
Some connection valve (Schrader type) are available to load/unload the circuit.
Circuit 1
Circuit 2
BEV-
BS-
YP-
CA-
FD-
BCD-
B-
YV-
MG-
Indoor coil
Temperature sensor
Expansion valve
Check valve
Filter dryer
Outdoor coil
Low/High pressure switch
Cycle reversal valve
Compressor
BALTIC-IOM-1711-E -51-
HEATING OPTIONS
Hot water coils
The hot water coil is fitted with a three way proportional valve . Two spanners must be used to tighten the connections. One spanner must maintain the valve body when connecting the pipe- work to the main. Failure to do so may damage the pipes joints and invalidates the warranty.
Filling up and starting the system
• Adjust the control for Heating by reducing the simulated ambient temperature down to 10°C
• Check that the red indicators located under the valve actuator are moving correctly with the signal.(Arrow on the picture)
• Fill the hydraulic system and bleed the coil using the air vents. Check incoming hot water flow rate.
• Check the various connections for possible leaks
Maximum working pressure:
Maximum working temperature:
8 Bars
110 °C
Freeze protection
Check the hydraulic system contains glycol for protection against freezing. Glycol is the only effective protection against freezing. The antifreeze must protect the unit against freezing under winter conditions.
Warning: glycol based fluids may produce corrosive agents when mixed with air.
Drain the installation
You must ensure that the manual or automatic air vents have been installed on all high points in the system. In order to drain the system, check that all the drain valves have been installed on all low points of the system.
Heating hot water coils frozen due to low ambient conditions are not covered by the warranty.
Electrolytic corrosion
Attention is drawn to the corrosion problems resulting from electrolytic reaction created by unbalanced earth connections. Any coil damaged by electrolytic corrosion is not covered by the warranty.
BALTIC-IOM-1711-E -52-
HEATING OPTIONS
Electric heater
WARNING: electric heater is connected heater to mains power – risk of electrical shock – switch off the unit prior to open this section
The BALTIC™ electric heaters are stand alone options which are fitted in the heating section of the unit. As for the hot water coil or the gas burner this option slides into the heating compartment located under the supply fan.
In order to reduce the pressure drops the airflow is ducted around the shielded resistances. The resistances are made smooth stainless steel tubes with a capacity of 6W/cm 2 .
It is protected as standard, against overheat via a high temperature overload protection set at 98°C and located less than 150mm after the heater itself.
There are two sizes available for each size of unit:
S: Standard heat
H: High heat
The standard heat electric heaters are staged control with 50% or 100%. The high heat version is controlled through a fully modulating triac.
Module size (kW)
12
24
27
36
45
48
54
Current
(A)
16,3
32,6
36.7
48,9
61.1
65,2
73,4
380V
Cap (kW)
10,8
21,5
24.3
32,3
40.5
43,0
48,4
Current
(A)
17,0
34,0
38.3
51,1
63.8
68,1
76,6
400V
Cap (kW)
11,8
23,5
26.6
35,3
44.3
47,0
52,9
Current
(A)
17,8
35,6
40.1
53,3
66.8
71,1
80,0
415V
Cap (kW)
12,8
25,6
28.8
38,4
48.0
51,3
57,7
BALTIC-IOM-1711-E -53-
HEATING OPTIONS
Electrical preheater
WARNING: electric pre-heater is connected heater to main power – risk of electrical Shock – switch off the unit prior to open this section
Pre-heater is running only with high fresh air rate under low outdoor ambient temperature (see setpoint in CLIMATIC™ section).
A metallic filter is installed between air filter & electrical resistance to protect against heat radiations.
WARNING: electric pre-heater metallic filter must not be plugged by dust
Amps per model size
S 18 kW
S 24 kW
S 36 kW
H 36 kW
H 48 kW
H 72 kW
24
26
52 52
30
26
C BOX
38
26
42
26
52 52
69
45
35
52
D BOX
57
35 35
69 69
65
35
75
E BOX
85
52 52
69
104 104
BALTIC-IOM-1711-E -54-
GAS BURNERS
Preliminary checks before start-up
Note:
Any work on the gas system must be carried out by qualified personnel.
This unit must be installed in accordance with local safety codes and regulations and can only be used in planed installation conditions for outdoor.
Please read carefully the manufacturer’s instructions before starting a unit.
Before commissioning a unit with gas burner, it is mandatory to ensure that the gas distribution system (type of gas, available pressure…) is compatible with the adjustment and settings of the unit.
The gas module safety chain must be checked by a professional before start-up of the product.
Check access and clearance around the unit
• make sure one can move freely around the unit.
• a minimum one-meter clearance must be left in front of the burnt gas exhaust flue.
• combustion air inlet and burnt gas exhaust(s) must not be obstructed in any way.
Supply network pipe sizing
Male threaded connection for gas burner: 3/4”
Check that the gas supply line can provide the burners with the pressure and the gas flow rate necessary to provide the heating nominal output.
Number of male threaded connections (3/4”)
Unit size
S power
H power
24
1
1
30
1
1
38
1
1
42
1
1
45
1
1
52
1
1
57
1
1
65
1
1
75
1
2
85
1
2
Gas flow - m 3 /h (for G20 at 20 mbar and 15°C)
Unit size
S power
H power
24 30
1,9
4,5
38 42 45 52
3,2
5,7
57 65 75
5,7
11,5
85
For modulating gas we have just H power for C, D & E-box
• the gas supply of a rooftop gas unit must be realized according to sound engineering practice and the local safety codes and rules.
• in any case the diameter of pipe-work connected to each rooftop must not be smaller than the diameter of the connection on the rooftop unit.
• make sure that a shut-off isolation valve has been installed before each rooftop.
• check the supply voltage to the exit of the power supply's transformer t3 of the burner: it must be between 220 and 240v.
Starting up the gas burner
Purge the pipe-work near the connection on the ignition control valve for a few seconds.
• check that the unit's treatment “fan” blower is running.
• set the control to “on” this will priorities the gas burner.
• increase the set temperature (room set point temperature) to a temperature higher than the actual room temperature.
BALTIC-IOM-1711-E -55-
GAS BURNERS
Standard start-up chronology
Time in seconds
Control operation sequence
Extraction fan
Smoke extraction fan "ON"
30 to 45 seconds pre-ventilation
Fire-up spark electrode 4s
Opening of the gas valve
"high heat"
Flame propagation towards the ionisation probe
If ionisation within 5sec:normal running
Otherwise fault on gas ignition control block
After 5 minutes, fault reported on the CLIMATIC™ controller
If incorrect sequence, refer to the fault analysis table to identify the problem.
BALTIC-IOM-1711-E -56-
GAS BURNERS
Pressure adjustments on Honeywell pressure regulating valve type vk 4105 g
Pressure regulator adjustment with 300mbar gas supply:
• the burner must run in high heat mode for this check.
• place the tube of the “accurate” manometer on the inlet pressure port of the gas regulating valve after having loosened the screw by one turn
High heat injection pressure checks
• place the tube of the “accurate” manometer to the out port on the gas injector support bar after having loosened the screw by one turn.
Low heat adjustment
• Check and adjust if necessary the valve inlet pressure to 20 mbar
(G20) or 25 mbar for groningue (G25) or 37 mbar for propane
(G31). After gas burner ignition.
Check and adjust if necessary the valve outlet pressure to 8,4 mbar (G20) / 12,3 mbar for groningue (G25) & 31,4 mbar for propane (G31)
BALTIC-IOM-1711-E -57-
GAS BURNERS
Low heat injection pressure checks
• switch the control to low heat
• check and adjust if necessary the outlet pressure to 3,5 mbar
(G20) or 5 mbar for groningue(G25) & 14 mbar for propane (G31)
Valve electrical control
2,90 kΩ
• check these values with an ohmmeter.
1,69 kΩ
• after the adjustment of the low heat, re-verify the high heat
• re-position the stoppers and close the pressure ports
Pressure adjustments table for each type of gas (mbar)
Category
Supply Low heat High heat pressure injection min, injection
G20 20,0 +/- 1
G25 (groningue)
25,0 +/- 1,3
G31 (GPL)
37,0 +/- 1,9
BALTIC-IOM-1711-E
3,5 +/- 0,1
5,0 +/- 0,1
14,0 +/- 0,3
8,4 +/- 0,2
12,3 +/- 0,2
31,4 +/- 0,6
-58-
GAS BURNERS
Burner safety checks
Smoke extractor pressure switch test
• with the gas burner running, disconnect the flexible tube fitted to the pressure taping on the pressure switch.
• the flame must disappear and the extraction fan must carry on running.
• however, no fault will be displayed (gas ignition control block or CLIMATIC™).
Ionisation probe test
• with the gas burner running, disconnect the terminal plug coming from the ionisation probe to the gas ignition control box.
• after reconnecting of the tube, the burner will restart after a period of 30 to 45 seconds pre-ventilation.
• the flame disappears
• the fan is still running and attempting to restart the burner (restart cycle 30 to 45 seconds).
• if the ignition probe is not reconnected at the end of the ignition sequence the burner will stop completely.
• the fault light on the gas ignition control block is on.
• manually reset the gas ignition control block to eliminate the fault
Gas pressure switch test
• with the gas burner running, close the shut off valve located before the rooftop.
In case of problems refer to the start up sequence flowchart next page
• the burner stops completely.
• however, no fault light will be displayed on the gas ignition control block. After 6 minutes, the CLIMATIC™ will display a fault.
• reset the CLIMATIC™.
BALTIC-IOM-1711-E -59-
GAS BURNERS
Gas burner fire-up sequence
Operation from control
Thermostat GAS =Closed
Supply thermostat limit?
(Auto Reset)
YES
Gas low pressure switch?
YES
Gas ignition control block signal
Extraction fan ON
AIR pressure switch ON backfire thermostat ON?
YES
Pre-ventilation 30 seconds
Fire-up electrode 4s
Gas valve open
NO
Ionisation 1 second after the end of sparking?
YES
Gas valve remains open
Normal operation
Air press switch ON or backfire thermostat?
YES
Signal from ionisation probe still ON?
NO
BALTIC-IOM-1711-E
NO
NO
YES
NO
Gas control valve closes
BURNER STOPS
NO
Gas control valve closes
BURNER STOPS
Fault on gas control block
6 minutes delay
Fault on CLIMATIC™
-60-
GAS BURNERS
Gas burner troubleshouting
If faults reported on CLIMATIC™
• reset the CLIMATIC™.
• check voltage: 230V after circuit breaker.
• check gas isolation shut-off valves are open.
• check gas pressure at the inlet of the gas valves. It must be >20 mbar when the burners shut down.
• adjust the set points to priorities the burner. Increase the value of the room temperature set point to a temperature higher than actual room temperature.
Diagnostic table baltic gas burner
Stage Normal operation Possible fault Action Possible solution
Heating requested
L.e.d on
Green, yellow & red l.e.d. ON
Extraction fans are running
All l.e.d. OFF
→ fault on the blower thermostat
Check connections on the blower thermostat.
Replace thermostat
Yellow & red l.e.d. OFF
→ lack of gas supply
Check valve’s opening & supply pressure
Restore gas supply
Red l.e.d. OFF
→ fault on the superheat thermostat on the gas burner support bar
Check thermostat’s operation
Replace thermostat after manual reset
After 10 seconds safety shutdown by the ignition control block
Check connections of the control block on the gas valve
Check impedance of electro valve’s coils: (1) =
2.90kΩ; (2)
=
1.69kΩ repositioning of the control block on the valve
Replace valve
Nothing happens
Check the free movement of the fan wheel
Check electrical connection on the gas ignition control block and on ef connection board
Check the fan supply voltage
Replace fan
Replace ef connection board if necessary
Extraction fan is on
After 30 to 45 seconds: pre-ventilation the fire-up electrode should spark.
Check the fire-up electrode
Check the pressure drop at the pressure switch: it must
Continuous ventilation without sparks from fire-up electrode be higher than 165 pa
+check the good operation of the pressure switch using an ohmmeter and by artificially creating a depression in the tube.
Re-position the pressure switch tube.
Change the pressure switch.
Continuous ventilation and sparks from fire up electrode.
After 4 seconds the gas
After a few seconds the gas burner fires-up burner still not operating and safety shutdown by the ignition control block.
Within 4 seconds the gas burner fires-up but safety shutdown from the ignition control block.
Check injection pressure during start-up (value for high heat)
Remove the control box from the gas block.
Remove the air from the gas pipe-work
Adjust the injection pressure to high heat value.
Change the control box if the gas valve is ok.
Check the position and connection of the ionisation probe. It must not be earthed
(230v).
Check that r.c circuit of the gas burner’s transformer is well connected to the neutral polarity
Measure the ionisation current: it must be higher than
1.5 microamps.
Check the type of gas.
Check the whole electrical supply.
Adjust the supply and injection pressure if gas is different from natural gas g20
:( g25 gas of groningue for example).
BALTIC-IOM-1711-E -61-
GAS BURNERS
Disassembling the gas burner for maintenance purposes Disassembling the flue
• electrically disconnect the fan and remove the screws holding
Preliminary safety recommendations
it in place.
• take care not to loose any cage nuts in the smoke box.
• isolate the unit using the main isolator switch.
• close off the isolating gas valve located before the unit.
• disconnect the pipe-work. Do not discard the seals.
Attention: check the correct position of the pressure tube used by the extraction pressure switch.
Disassembling the gas «burner support bar»
• disconnect the electrical connector on the electric connection board BG50
• remove the two screws which hold the gas bar in place
• carefully remove the gas « burner support bar » avoiding any damages to the electrodes.
Required equipment list for maintenance adjustment and start-up
• an accurate manometer from 0 to 3500 pa (0 to 350 mbar):
0,1% full scale.
• a multimeter with ohmmeter and micro-amps scale
• an adjustable spanner
• tube spanner set: 8, 9, 10, and 13.
• flat screwdrivers diameter 3 and 4, fillips n°1
• vacuum cleaner
• paint brush
Gas burner support bar
BALTIC-IOM-1711-E -62-
GAS BURNERS
Gas module
4
5
6
10
9
12
1
2
3
1.
Circuit breaker
2.
Transformer 400/230V
Minimum gas pressure switch and inlet pressure plug
3.
4.
Gas valve and solenoid
Gas ignition control block and BG50 connection board
5.
6.
Ignition electrode
Ionisation probe
7.
8.
Gas inshot burner
Gas injectors support bar
9.
10.
Backfire thermostat
11.
Air pressure switch
12.
Outlet pressure plug
13.
Smoke exhaust chimney
14.
Supply safety thermostat
BALTIC-IOM-1711-E
11
14
13
7
8
-63-
MODULATING GAS BURNERS
Modulating gas (under patent inpi mai 2004)
The actuator
Bearing surface of the actuator’s screw
Minimum opening of the actuator
The actuator receives an information 0-10v from the regulation for the positioning of the air shutter; then the actuator transmits its position to the printed-board which will order the valve.
Check position and operation of the actuator
Disengaging for hand drive operation
Starting up the gas burner
Purge the pipe-work near the connection on the ignition control valve for a few seconds.
Manual rotation of the actuator
BALTIC-IOM-1711-E
• check that the unit's treatment fan blower is running.
• set the control to “on” this will priorities the gas burner.
• increase the set temperature (room set point temperature) to a temperature higher than the actual room temperature.
The start of the gas burner must be done at high heat injection.
-64-
MODULATING GAS BURNERS
Pressure adjustments on honeywell pressure regulating valve type vk 4105 g
Pressure regulator adjustment with 300 mbar gas supply:
• the burner must run in high heat mode for this check.
• place the tube of the “accurate” manometer on the inlet pressure port of the gas regulating valve after having loosened the screw by one turn
Low heat adjustment
Inlet pressure
High heat injection pressure checks
• place the tube of the “accurate” manometer to the out port on the gas injector support bar after having loosened the screw by one turn.
High heat adjustment underneath
• Check and adjust if necessary the valve inlet pressure to 20 mbar (G20) (or 25 mbar for G25) after gas burner ignition
Check and adjust if necessary the valve outlet pressure to 8,4 mbar
(G20) (or 12,3 mbar for G25)
BALTIC-IOM-1711-E -65-
MODULATING GAS BURNERS
Low heat injection pressure checks
• switch the control to low heat
• check and adjust if necessary the outlet pressure to 1,5 mbar minimum (G20) (or 2.25 mbar for G25)
• after the adjustment of the low heat, re-verify the high heat
• re-position the stoppers and close the pressure ports.
Pressure adjustments table for each type of gas (mbar)
Category
Supply pressure
Low heat injection mini.
High heat injection
G20
G25
G31
20,0 +/- 1
25,0 +/- 1,3
NA
1,5 +/- 0,03
2,25 +/- 0,05
NA
8,4 +/- 0,2
12,3 +/- 0,2
NA
Valve electrical control
• after the adjustment of the low heat, re-verify the high heat
• re-position the stoppers and close the pressure ports.
2,90 kΩ
• check these values with an ohmmeter.
1,69 kΩ
BALTIC-IOM-1711-E -66-
MODULATING GAS BURNERS
Burner safety checks
Idem non-modulating gas burner
Gas burner troubleshouting
Idem non-modulating gas burner.
If the valve’s flow is not correct, check the operation of the actuator and of the mechanical assembly.
→ Replace the actuator if necessary
Disassembling of gas burner for maintenance purposes
Idem non-modulating gas burner
Modulating gas
BALTIC-IOM-1711-E -67-
RECOVERY WATER COIL
Heat recovery water coil is delivered with a loose 3 ways valve inside carton to be assembled on site by installer.
The freeze protection is made via fresh damper safeties nevertheless for a full freezing protection has to be done using glycoled water
BALTIC-IOM-1711-E -68-
SERVICE DIAGNOSTIC
Refrigeration
Fault
LP problems and
LP cut outs
Possible cause and symptoms Solution
Refrigerant charge too low
Measure the superheat and sub-cooling:
Good if 5°c<sc<10°c and 5°c<sh<10°c
Bad if sc>10°c and sh too low
Check superheat adjustment and charge unit (a leak check must be carried out)
In heat pump mode the temperature difference between t outdoor and tevap. (dew) is too high
If too high check the coils are clean or check coil internal pressure drop between the liquid line and the suction line
5°c < delta t < 10°c excellent
10°c < delta t < 15°c acceptable
15°c < delta t < 25°c too high
Good if < 3bar
Too high if > 3bar (coil blocked)
Refrigeration circuit blocked in distribution
Stop the fan and create icing of the coil.
Check all circuits freeze evenly across the whole surface of the coil
If some parts of the coil do not freeze this could indicate a problem with the distribution
Liquid line drier blocked. High temperature difference between inlet and outlet of the drier
Change filter drier
Contaminant in the expansion valve
Expansion valve not adjusted properly
Ice plug in the expansion valve.
Attempt to free the valve adjusting element by freezing the valve and then heating the thermostatic element. Replace the valve if necessary
Adjust the expansion valve
Heat the main body of the valve. If the LP increases and then decreases gradually, empty the circuit and replace the drier.
Incorrect insulation of the thermostatic bulb of
Superheat too low: adjust superheat the expansion valve
Move the thermostatic element along the pipe
Insulate the thermostatic element of the valve
HP problems and HP cut outs
Low pressure switch cut out point too high
Check the cut out pressure of the low pressure switch: it must be 0,7+/- 0,2bar and must closes at 2,24 +/- 0,2 bar
LP cut out due to not enough defrost on heat pumps
Adjust the CLIMATIC™ settings to extend the defrost cycles or shorten the time between defrosts
Incorrect airflow rates
Heat pump mode: check the filter before the indoor coil measure and estimate the airflow rate increase the speed of the fan
Cooling mode: check the condenser fan (amps)
Moisture or contaminants in the system
Summer operation
Several hours after the unit has stopped, check the correspondence between the measured pressure and the outdoor temperature
BALTIC-IOM-1711-E -69-
SERVICE DIAGNOSTIC
Refrigeration
Fault
HP problems and HP cut outs
Strong variations of pressure
( 2 to 3 bar) expansion valve
"hunting"
Possible cause and symptoms
Moisture or contaminants in the system
Condenser coil is obstructed
Recycled hot air
Solution
If the circuit pressure is higher (<1 bar) than the saturated pressure corresponding to the measured outdoor temperature, there is possibility that some contaminants are present in the system.
Reclaim the refrigerant, and vacuum the circuit (ensure very low and slow vacuum for R410A)
Recharge the unit
Check the condenser coil and clean is necessary
Check clearance around the condenser
Incorrect adjustment of the expansion valve
Low refrigerant charge
Filter drier obstructed with gas bubbles at the expansion valve inlet
Moisture in the system
Refer to LP problems and LP cut out section
Very high discharge temperature,
High amps measured at compressor
Very high superheat, very hot compressor
Four way reversing valve possibly blocked, abnormal noise from the valve, low LP and increasing HP
Reduce the superheat on the electronic valve.
Check the pressure drop on the filter drier in the suction line
Check operation of the valve by going through cycle inversions. Change if necessary.
Refer to LP problems
Indoor fan blower
Fault
High amps on action fan motor
Possible cause and symptoms Solution
Pressure drop in the ducting installation too low.
Reduce the rotation speed of the fan
Read the airflow and pressure and compare with the specification from customer.
High amps on reaction fan motor
Pressure drop in the ducting installation too high.
Reduce the rotation speed of the fan
Read the airflow and pressure and compare with the specification from customer.
Unstable running and high vibration
Fan jumping from one operating point to the other
Change rotation speed of the fan.
Outdoor axial fan
Fault Possible cause and symptoms Solution
Heat pump mode: circuit breaker open
High amps due to a low voltage from the main Check the voltage drop when all components are running. supply Change the circuit breaker for one with a higher rating.
High amps due to freezing of the coil
Check the adjustable amps on the motor starter.
Adjust the defrost cycle set points.
FLEXY™: water ingress in the motor connection box.
Change the component
BALTIC-IOM-1711-E -70-
SERVICE DIAGNOSTIC
Electric heater
Fault
High temperature trip out on electric heater
Possible cause and symptoms
Low airflow rate
Incorrect position of the klixon
Solution
Measure and estimate the airflow and pressure and compare with the specification from customer.
Check that the klixon, is positioned in the airflow, relocate klixon if necessary
Check that there is no heat transfer from the klixon support.
Water leaks
Fault
Water found in the ventilation section
Water ingress in the filter compartment
Possible cause and symptoms Solution
Cooling mode: water carried away from the coil because of excessive airflow and speed on the coil.
Estimate the airflow rate and check the speed is lower than
2,8 m/s
Low air pressure in the compartment due to a high airflow rate or a high pressure drop before the fan
Check filter
Reduce airflow rate
Check seals around the ventilation section.
Check the door seal
Check for the presence of silicone seals in the corners of the door and at the bottom of the refrigeration section bulkhead.
Water ingress through a leaking fresh air hood Check the seals and flanges in the fresh air hood or when running 100% fresh air Reduce the airflow rate if necessary
CLIMATIC™ Displays
Fault Possible cause and symptoms
Nothing is written on the screen but it’s enlightened
Idem
Nothing occurs on the unit or an option disappeared
Possible problem of units' configuration
The message “no link” appears Problem of addresses’ recognition
All the units are extinct Problem main board plan addressing
BALTIC-IOM-1711-E
Solution
Press on the three right-hand side’s buttons at the same time during a few seconds then reconfigure display address setting at 32.
Check the instructions from 3811 to 3833 and reconfigure options if necessary.
Disconnect the DS from the unit and then reconnect it.
Disconnect then re-plug; disconnect each unit from the others then change all the plan addresses
-71-
SPARE PART LIST
Type
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Ventilation
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Coils
Type
Moteur
Moteur
Moteur
Moteur
Moteur
Moteur
Moteur
Moteur
Coils
Coils
Coils
Coils
Coils
BALTIC-IOM-1711-E
4310496R
4310501Y
4310505F
4310506H
4310507J
4310508K
4310509L
4310510M
4310511N
4310512P
4310513R
4350489H
4350492L
4350493M
4350499W
4940025V
4940026W
79102834
Code
4521802L
4521806R
4521807T
4521808V
4521809W
4521811Y
4521813A
4521822P
4310488F
4310490J
4310491K
4310494N
4310495P
Code
4910018R
4910022X
4910080H
4910090X
4910102R
4910104V
4921047L
4921121V
4921160A
4921161E
4921162F
4921170R
4921171T
4921172V
4950035P
4950040X
4950044E
4950046H
4950053R
4950054T
4950238N
4950266F
4950761J
4950762K
4950763L
4950764M
4950765N
4950766P
Designation
VENTILATEUR AT 15-11 SS D25
VENTILATEUR 230/1/50 HZ
VENTILATEUR AT 15-11 G2L D30
VENTILATEUR ADHE 355 L D30
VENTILATEUR PLUGFAN+VIROLE
VENTILATEUR PLUGFAN+VIROLE
VIROLE PLASTIQUE POUR EBM-450
MOTO VENTIL TRI 400V 2V. D=450
MOTO VENTIL TRI 400V 1V. D=630
MOTO VENTIL TRI 400V 1V. D=710
MOTO VENTIL TRI 400V 1V. D=800
MOTO VENTIL TRI 400V 2V. D=630
MOTO VENTIL TRI 400V 2V. D=710
MOTO VENTIL TRI 400V 2V. D=800
MOYEU FONTE 28-20 ALESAGE 25
MOYEU FONTE 28-20 ALESAGE 24
MOYEU FONTE 40-25 ALESAGE 25
MOYEU FONTE 40-25 ALESAGE 38
MOYEU FONTE 30-25 ALESAGE 25
MOYEU FONTE 30-25 ALESAGE 28
MOYEU FONTE 30-25 ALESAGE 30
MOYEU FONTE 40-25 ALESAGE 30
ROUE PNEUMABLOC PV40 H
ROUE PNEUMABLOC PV50 H
ROUE PNEUMABLOC PV60 H
PNEU PNEUMABLOC P40
PNEU PNEUMABLOC P50
PNEU PNEUMABLOC P60
Designation
MOT IP55 F.B3 1.5KW PTO 4P IE2
MOT IP55 F.B3 2.2KW PTO 4P IE2
MOT IP55 F.B3 3.0KW PTO 4P IE2
MOT IP55 F.B3 4.0KW PTO 4P IE2
MOT IP55 F.B3 5.5KW PTO 4P IE2
MOT IP55 F.B3 7.5KW PTO 4P IE2
MOT IP55 F.B3 9.2KW PTO 4P IE2
MOT IP55 F.B3 11.KW PTO 4P IE2
BAT 4N40T1000 1.81 20V C-BOX
BAT 4N40T1500 1.81 16+10V D-B
BAT 4N40T2000 1.81 2X13V E-BOX
BAT 2N40T0883 2.12 20V C-BOX
BAT 2N40T1383 2.12 20V D-BOX
BAT 2N40T1883 2.12 38V E-BOX
BAT 3N40T1000 1.81 12V C-BOX
BAT 3N24T0750 3.17 12V C-BOX
BAT 3N24T1225 3.17 18V D-BOX
BAT 4N24T1725 3.17 24V E-BOX
BAT 1N38T0970 2.12 4V TRMO-C.
BAT 1N38T1470 2.12 6V TRMO-D.
BAT 1N38T1970 2.12 4V TRMO-E.
BAT 3N20T0885 2.12 5V TRMO-C.
BAT 3N20T1385 2.12 5V TRMO-D.
BAT 3N20T1885 2.12 6V TRMO-E.
BAT 3N40T1818 1.58 10V C-D-BOX
BAT 3N40T2198 1.58 12V E-BOX
BAT 3N40T2198 1.58 12V E-BOX
BAT 2N40T1841 1.58 7V C-D-BOX
VOLET SURPRESSION 397X415 CONJ
VOLET SURPRESSION 750X415 CONJ
U FIXATION PLAQUE BATTERIE
-72-
SPARE PART LIST
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
4 way valve
Compressor
Compressor
Compressor
Compressor
Filter
Filter
Filter
Filter
Filter
Type
Liquid receiver
Liquid receiver
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
Refrigeration
4740100M
4740103R
4740146E
4740150L
4740151M
4740152N
4740165J
4740169N
4740170P
4740175X
4220449V
4220450X
4220452A
4220476K
4960128J
4960129K
4960130L
4960132N
4960134R
Code
4320047M
4320048N
4720001F
4720002H
4720905K
4720907M
4720931X
4720944R
4720945T
4720964W
4720965X
4720969E
4720971H
Designation
RESERVE LIQUIDE VERT. DE 2.4L
RESERVE LIQUIDE VERT. DE 3.0L
CLAPET DE RETENUE 1/2"
CLAPET DE RETENUE 5/8"
DESHYDRATEUR BI-FLOW 5/8"
DESHYDRATEUR A SOUDER 5/8"
CABLE CONNECTEUR 3M E2V-E3V U.
DETENDEUR ERZE-4-GA 3/8"X1/2"
DETENDEUR ERZE-6-GA 1/2"X5/8"
VANNE DET.ELECTRO - CORPS E2V
VANNE DET.ELECTRO - CORPS E3V
VANNE DET.ELECTRO - BOBINE E2V
VANNE DET.ELECTRO - BOBINE E3V
VANNE 4 VOIES 5/8"
BOBINE ELECTROVANNE 24V
VOLET 750X412 C-BOX BA3 EBHO
VOLET 750X891 C-BOX BA3
VOLET 1250X891 D-BOX BA3
VOLET 1750X891 E-BOX BA3
BOBINE ELECTROVANNE 24V
VANNE 4 VOIES 7/8" - 1"1/8
VOLET 1750X417 F-BOX FA1
VOLET 1250X417 D-BOX BA3 EBHO
COMPRESSEUR ZP72KCE TRI+BRASE
COMPRESSEUR ZP83KCE TRI+BRASE
AMORTISSEURS ZP54-72-83 TANDEM
COMPRESSEUR ZP54KSE TRI+BRASE
FILTRE 530X500X50 EU3 CAMPLANS
FILTRE 530X500X50 EU4 AR300
FILTRE 530X500X98 EU7 GP10
FILTRE METAL EP=10 850 X 455
FILTRE 530X500X50 EU4 RECHARG.
BALTIC-IOM-1711-E -73-
SPARE PART LIST
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Switch
Switch
Control
Control
Control
Control
Control
Control
Transformer
Transformer
Part
Plate HX
Plate HX
Switch
Switch
Switch
Switch
Switch
Type Code
Electrical components 4410650A
Electrical components 4410652F
Electrical components 4410653H
Electrical components 4410885X
Electrical components 4411010H
Electrical components 4411029K
Electrical components 4411030L
Electrical components 4411051R
Electrical components 4411059E
Electrical components 4411066N
Electrical components 4411067P
Electrical components 4411074Z
Electrical components 4411103T
Electrical components 4411105X
4770629J
4770633N
4770634P
4770643E
4770644L
4770692Z
4770703R
4770705V
4770715K
4770716L
4430125R
4430131Z
4880100V
4380416P
4380425E
4730050J
4730051K
4730093W
4730097A
4730184H
4730191P
4730192R
4770213W
4770217A
4770219F
4770609E
4770613K
4770623Y
Designation
CONTACTEUR 9A 1 F+1 O A VIS
CONTACTEUR 18A 1 F+1 O A VIS
CONTACTEUR 25A 1 F+1 O A VIS
CONTACTEUR K 9A 24V
CONTACT ADDITIF 2F - LC1K
CONTACTEUR 40A 1 F+1 O 24V
CONTACTEUR 50A 1 F+1 O 24V
RELAIS CONTROL RESEAUX TRI
TRANSFO INTENSITE TI400/5A
TRANSFO INTENSITE TI200/5A
TRANSFO INTENSITE TI250/5A
PEIGNE C60 TRI PAS 24
COMPTEUR ENERGIE IEM3250 (BUS)
FLASQUE PEIGNE ACTI9 3P
TRANSFORMATEUR 160VA 400V/230V
TRANSFORMATEUR 88VA PRIM:400V
PATIN DE GLISSEMENT BATT UF
ECHANG.A PLAQUES ACH230DQ054HG
ECHANG.A PLAQUES ACH230DQ082HG
CONTROLEUR DEBIT COMPACT
CONNECTEUR 5M POUR CONTROLEUR
THERMOSTAT SECURITE INCENDIE
PRESSOSTAT DIFF. AIR PROPORTI.
PRESSOSTAT HP 42.0 BARS OFF
CAPTEUR DIFF. AIR 0-30MBAR.
CAPTEUR DIFF. AIR 0-10MBAR.
CAPTR.PRESS. 4/20MA -1/20 BARS
CAPTR.PRESS. 4/20MA -1/45 BARS
CAPTR.PRESS. 0/5V -1/20 BARS
CABLE AFFICHEURS POUR CL50-60
SONDE D'AMBIANCE CLIMATIC 50
CONNECTEUR MULTI AFFICH DT50
INTERFACE ECHELON SANS PROGRAM
CARTE GAZ MODULANT
CARTE GAZ BG50
CARTE BACNET RS485
CARTE BACNET ETHERNET
CABLE AFFICHEURS POUR CL50-60
AFFICHEUR CLIENT DC60 24V T°
CARTE COMMUNICAT.RS485 CLIM 60
AFFICHEUR MAINTENANCE DS60
AFFICHEUR MULTI-ROOFTOP DM60
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Control
Type
Control
Control
Control
Control
Control
Control
Control
Control
Control
Designation
SONDE D'AMBIANCE CLIMATIC 50
CONNECTEUR MULTI AFFICH DT50
INTERFACE ECHELON SANS PROGRAM
CARTE GAZ MODULANT
CARTE GAZ BG50
CARTE BACNET RS485
CARTE BACNET ETHERNET
CABLE AFFICHEURS POUR CL50-60
AFFICHEUR CLIENT DC60 24V T°
CARTE COMMUNICAT.RS485 CLIM 60
AFFICHEUR MAINTENANCE DS60
AFFICHEUR MULTI-ROOFTOP DM60
SONDE NTC [-50+105]°C 3 METRE
SONDE NTC [-50+105]°C 7 METRE
SONDE HYGRO.-TEMP. DE GAINE
CARTE REGULATEUR E-CLI+MEDIUM
CONNECTEURS POUR E-CLI+MEDIUM
CARTE EXTENSION E-BE C.PCOE
CONNECTEURS POUR E-BE C.PCOE
INTERFACE DE COM.LENNOX ONEWEB
INSHOT GAS BURNER (BRULEUR)
THERMOSTAT ANTIGEL-30/+15 AUTO
VARIATEUR FREQUENCE 2.2KW
VARIATEUR FREQUENCE 4.0KW
VARIATEUR FREQUENCE 7.5KW
VARIATEUR FREQUENCE 11.KW
VARIATEUR FREQUENCE 5.5KW
THERMOSTAT SECURITE AUTO 98°C
THERMOSTAT SECU.REARM.MANUEL
VARIATEUR FREQUENCE 1.5KW
VARIATEUR FREQUENCE 3.0KW
SONDE HYGIENE AIR CO2 HUM.MBUS
SERVO-MOTEUR VANNE 0/10V 5833
VANNE 3V DN20 KVS 4
VANNE 3V DN25 KVS 10
VANNE 3V DN32 KVS 16
VANNE 3V DN40 KVS 25
RACCORD V3V DN25 FEMELLE
RACCORD V3V DN32 FEMELLE
RACCORD V3V DN40 FEMELLE
SERVO-MOTEUR 24V SM5 5NM
SERVO-MOTEUR 24V 0-10V 10NM
DETECTEUR DAD NON SECOURU
SOCLE DETECTEUR DE FUMEE
DETECTEUR OPTIQUE DE FUMEE
RELAIS STATIQUE 50A 400V
RELAIS STATIQUE 75A 400V
RELAIS STATIQUE 100A 400V
DISSIPATEUR THERMIQUE 0.7°/W
VANNE GAZ HONEYWELL 220/240V
BOITIER DE CONTROLE DE FLAMME
REGULATEUR HIGH-LOW 4-37 MBAR
PRESSOSTAT GAZ (GAZ NAT-PROP)
BRIDE DROITE AVEC JOINT ET VIS
BRIDE COUDEE AVEC JOINT ET VIS
COUVERCLE BOITIER CTRL FLAMME
DETENDEUR HONEYWELL 10-30 MBAR
AXE SERVO MOTEUR GAZ MODULANT
AXE BOISSEAU BIELLES GAZ MODUL
VANNE GAZ MODULANTE 220/240V
PRESSOSTAT AIR (BRULEUR GAZ)
CLIP FIX. PRESSOS.4781361T-62R
4781256L
4781257M
4781258N
4781277R
4781286T
4781290L
4781292N
4781293P
4781300Z
4781301A
4781302E
4780232F
4780415Y
4780417A
4780418E
4780419F
4780421J
4780425N
4780466Y
4780467Z
4780469E
4780470F
4780956V
4781250A
4781252F
4781253H
4781254J
4781255K
4781303F
4781305J
4781306M
4781307N
4781309R
4781311V
4781312W
4781313X
4781317F
4781337K
4781338L
4781360N
4781361P
4781363T
4770705V
4770715K
4770716L
4770720R
4770721T
4770725Y
4770728E
4770729F
4770730H
4770731J
4770738T
Code
4770613K
4770623Y
4770629J
4770633N
4770634P
4770643E
4770644L
4770692Z
4770703R
BALTIC-IOM-1711-E -74-
WARRANTY
Terms and conditions
In the absence of any other written agreement, the guarantee shall only apply to design faults which occur within a 12 month period
(warranty period).
The warranty period starts on the date of commissioning and at the latest six months after the delivery of the Rooftop.
Anti-corrosion warranty
10 year warranty terms and conditions for corrosion to the Rooftop casing:
LENNOX shall guarantee the casing of its Rooftop units manufactured against corrosion for 10 years commencing from the date of delivery of the material.
The warranty shall not apply in the following cases:
1. If the corrosion of the casing is caused by external damage to the protective layer such as scratches, projections, abrasion, impacts etc...
2. If the casing is not kept continually clean in the course of maintenance work or by a specialist company,
3. If the casing is not cleaned and maintained in accordance with regulations,
4. If the Rooftop units are installed on a site or in an environment which is known to be corrosive, unless a special protective coating has been applied by the owner for these applications, which has been recommended by a competent body not linked to the owner and after carrying out a study of the site.
5. Nevertheless the LENNOX coating is highly resistant to corrosion, the warranty will not be applied for rooftop installed at less than
1000 m away from the sea
Note: With the exception of the casing, the rest of the machine is covered by the warranty of our general terms of sale.
Do not confuse the warranty with maintenance
The warranty will only apply if a maintenance contract has been signed, starting from the date of commissioning, and if the maintenance contract has actually been performed
The maintenance contract must be made with a specialist, competent company.
The sole effect of any repair, modification or replacement of an item during the warranty period must be to extend the material's warranty period.
Maintenance must be carried out in accordance with regulations.
If a spare part is supplied after the expiry of the warranty period, it shall be guaranteed for a period equal to the initial warranty period and will be subject to the same conditions.
We recommend for a contract four inspections per year (every three months), before the start of each season, in order to check the operation of the equipment in the various operating modes.
Lifetime of the equipment
The refrigerating system is designed for a lifetime of at least 10 years if the safety and maintenance instructions are strictly respected.
The lifetime of the equipment may be renewed if the periodic requalification certificate is validated by the expert (authorized body or DREAL)
Disposal of the equipment
Equipment shut-down and recuperation of oil and coolant must be carried out by qualified personnel conform to the recommendations of standard NF EN 378.
All elements in the refrigeration system such as refrigerant, oil, coolant, filters, dryers and insulating materials must be recuperated, re-used and/or disposed of in a correct manner (see NF EN 378 part 4). No materials may be discarded into the environment.
BALTIC-IOM-1711-E -75-
MAINTENANCE PLAN
Rooftops are generally placed on the roof but can also be installed in technical rooms. These units are very robust but a minimum regular maintenance is required. Some moving parts in the units can suffer from wear and tear and must be checked regularly (belts).
Other parts can get clogged by dirt carried in the air (filters) and must be cleaned or replaced.
These units are designed to produce cooled or heated air through the use of a refrigeration vapour compression system, it is therefore imperative to monitor the refrigeration circuit operating pressures and check the pipe-work for leaks.
The table below, details a possible maintenance plan, including the operations to be carried out and the periodicity at which they must be accomplished. It is recommended to follow such a plan to keep a rooftop unit in good working order. Regular maintenance of your rooftop will extend its operating life and reduce operating faults
Symbols and Legend :
X Operation which can be carried out by on-site maintenance technicians.
◆
Operation which must be carried out by qualified refrigeration personnel, trained to operate on this type of equipment.
Note:
• Times are given for information purpose only and may vary depending on the unit size and type of installation.
• Coil cleaning must be carried out by qualified personnel using appropriate methods that won’t damage the fins or the tubes.
• It is recommended to keep a minimum stock of common replacement parts in order to be able to carry out regular maintenance operations (i.e. filters). You can contact your local LENNOX representative which can assist you in establishing a parts list for each type of equipment.
• The access ports to the refrigeration circuits MUST be leak checked every time gauges are connected to the service ports.
BALTIC-IOM-1711-E -76-
MAINTENANCE PLAN
Task
Clean or replace filters:
Disposable, or metal frame.
Replace filters with new ones if disposable. Vacuum clean or blow the dirt. Wash and dry carefully. Replace Filter if necessary by an original
Lennox filter.
Blocked filter will reduce the performance of the unit.
THE UNIT SHOULD NEVER BE OPERATED WITHOUT FILTERS
Visual check of the oil level
(applicable for units equipped with sight glass) and check the oil for acidity on the refrigerant circuits
Visually check the oil level through the sight glass on the side of the
Test the oil every 3 years and after each intervention on the refrigerant circuit
Clean condensate drain, indoor coils and outdoor coils (following local regulations)
Check condenser fans
Check for the Amps consumed
Check Smoke detector
It's mandatory to clean the external coils, according to the environment where the unit is located, the frequency of the cleaning varies from once in a month to minimum twice in a year.
The performance and the sustainability of the machine is based on the perfect heat exchange.
The use of a neutral pH cleaning product is mandatory.
(WARNING: Fins and copper tubes are very fragile! Any damage
WILL reduce the performances of the unit).
Check the rotation of the fan ( free rotation, detection of vibrations or bearing noises)
Check for the Amps consumed on all three phases; compare it with the nominal value given in the electrical wiring diagram.
Check the status of the fan blades and its protections.
Check for the Amps consumed on all three phases; compare with the nominal value given in the electrical wiring diagram.
Start the unit. Trigger the smoke detector with an aerosol tester.
Reset unit and control.
Check CLIMATIC™ control, set-points and variables
Check refrigeration system for proper functioning
Refer to the commissioning sheet; Check all set points are set according to this document.
Retrieve/Check the values of Overheating and subcooling
Check clock settings
Operating mode
Check the time and date of the control
Monthly + Quarterly
+ Half
Yearly
•
•
| |
|
|
|
|
|
•
|
Check the position and tightness of refrigeration components
Check three way valve on
HWC (If applicable)
Check systematically all connections and fixings on the refrigeration circuit. Check for oil traces, eventually a leak test should be conducted. Check operating pressures correspond to the ones, indicated on the commissioning sheet
Increase room set-point 10°C above the actual room temperature.
Check operation of the piston. It must move away from the valve head. Reset the control.
Check the position of the crankcase heaters (around the compressor) and the proper functioning of it
Check the well fixation of the crankcase heaters, if it is tight enough
And check the crankcase heaters overall working.
Check defrost cycle with 4way valve inversion.
Switch the unit to heat pump mode. Change the set point to obtain the standard defrost mode and reduce the cycle time to the min value. Check the operation of the defrost cycle.
Check overall working of the flow controller (only for rooftops with water condensation function)
Check the water flow ( only for rooftops with water condensation function )
Cut-off the compressors, stop the water circulation, then start the unit, wait for the water flow failing signal in the controller.
Measure the water flow and compare it to the initial value set in the command selection
Check the plug fans ( freewheel)
Check the axial extractor fan ( if the unit is equipped with )
Check the rotation of the fan (free rotation, detection of vibration or bearing noises)
Check for the Amps consumed on all three phases; compare with the nominal value given in the electrical wiring diagram.
Check the rotation of the fan (free rotation, detection of vibration or bearing noises)
Check for the Amps consumed on all three phases; compare with the nominal value given in the electrical wiring diagram.
Check the well working of the energy recovering wheels
Check the rotation of the wheel; Check the strap tension;
Replace the components in case of malfunctioning
Check Airflow rate safety switch (if equipped).
Shut down supply fan. The fault must be detected within 5 seconds.
|
|
•
|
|
|
•
|
|
•
BALTIC-IOM-1711-E -77-
MAINTENANCE PLAN
Task Operating mode
Check freeze protection on
HWC (if applicable)
Test antifreeze function (leakage rate, frost protection thermostat)
Check economizer actuator operation
Check tightness of all electrical connections
Check HP / LP safety switches
Check the value of the analog sensors
Check all fixings and transmission. Stop the unit using the control.
The fresh air damper must close. Start the unit, the fresh air damper should open.
Make a forced opening and closure of the motorized dampers.
Power down the unit and check and tighten all screws, terminal and electric connections (including the terminal boxes)
When turning on the unit, check the deterioration of the electrical components with a thermal camera, with the unit working at 100% of its power.
Install a pressure gauge HP / LP and check if the safety switches overall working.
Install the pressure gauge calibrated to check the analog sensors.
Install a thermometer calibrated to control the sensors.
Check the position of all sensors
Check the good positioning and the fixation of all sensors.
Check and clean if necessary all fresh air grids
Check electric heater element for excessive corrosion
Check anti-vibration mountings, for wear and tear.
Check Glycol concentration in the HWC circuit and/or in the water condenser circuits
Gas burner module check for corrosion
Check the fresh air grilles (if fitted). If dirty or damaged, remove them from unit and clean with high pressure water cleaner. Refit on unit once clean and dry.
Turn off the unit; Pull the electric heater out of the heater module box and check the resistances of traces of corrosion; Replace resistance as required;
Visually check anti-vibration mountings on compressors and centrifugal fan. Replace if damaged.
Check the glycol concentration in the pressurized water circuit. ( a concentration of 30% gives a protection down to approx.. -15°C) check the circuit pressure
Sweeping and cleaning the gas burner
Pull out the burner to access the tubes
(refer to Gas burner section in the IOM)
Clean the in-shot burners and the blower wheel lightly with a brush.
Sweep the flue and flue box. Wipe-off the dust from the housing of the motor. Clean combustion air inlet louvers Pull-out baffles from the tubes, sweep the tubes
CHECK FLUE BOX GASKET
Gas supply pressures
/ connections checks
Check the gas regulation valve settings
Refer to Gas burner section in the IOM for details
Refer to Gas burner section in the IOM for details
Check gas burner safety switches
Check the ignition electrode and the ionization probes
Check gas fume combustion levels
Refer to Gas burner section in the IOM for details
Refer to Gas burner section in the IOM for details
Do a combustion analysis.
Refer to local regulation if it exists
Check casing and equipment corrosion
To treat and neutralize eventual rust spots
Check the water tightness of the unit and it's accessories
Verify the gaskets, if cracked or ripped, repair them or replace them.
Check the doors gasket
Verify the gaskets; if cracked, ripped or discontinuous in these cases replace them.
Check the water tightness of the water circuit (only for
Rooftops with water condenser)
Check for water leaks and repair if it's needed.
Check and clean the water filter (only for Rooftops with water condenser)
ATTENTION: The water circuit can be under pressure. Follow the usual precautions when depressurizing the circuit before opening.
Ignoring these rules can lead to accidents and cause injury to the personal.
Monthly + Quarterly
+ Half
Yearly
|
|
|
|
|
|
|
|
|
•
•
|
•
|
•
•
•
•
|
|
|
|
BALTIC-IOM-171-E -78-
COMMISSIONING RECORD SHEET
Site details
Site
Unit Ref
Installer
(1) ROOF INSTALLATION
Sufficient Access OK
Yes No
(2) CONNECTIONS CHECK
Phase check
Yes No
Controller
Model
Serial No
Refrigerant
Condensate drain fitted
Yes No
Voltage between Phases
1/2
Roofcurb
OK
2/3
Not OK
1/3
(3) CLIMATIC™ CONFIGURATION CHECK
CLIMATIC™ Configured according to the options and specifications
Yes No
(4) SUPPLY BLOWER SECTION
Type
Power displayed on plate
Voltage displayed on plate
Current displayed on plate
Fan type
Displayed coupling ref
Alignment checked
Fan speed
Averaged measured amps
Shaft mechanical mower
(Refer to airflow balancing)
Operating point checked
Read airflow kW
V
A mm
Forward
Yes rpm
A
W m 3 /h
Yes
N°1
Backward
No
No
Forward
Yes
Yes
(5) AIRFLOW PRESSURE SENSOR CHECK
Measured pressure drop
Set points adjusted
Yes mBar
If yes enter new values
3410: 3411:
No
N°2
3412:
Backward
No
No
(6) EXTERNAL SENSOR CHECKS
Check electrical connections Yes
Supply temperature
Return temperature
Outdoor temperature
No
(7) MIXING AIR DAMPERS CHECKS
Dampers open & close freely
Yes No
% Minimum FA
%
BALTIC-IOM-1711-E
Check and record temp. in menu 2110
100% Fresh Air
°C
°C
°C
Yes No
100% return Air
°C
°C
°C
Yes
Power exhaust checked
No
Enthalpy sensor(s) checked
Yes No
-79-
COMMISSIONING RECORD SHEET
(8) REFRIGERATION SECTION
Outdoor fan motor current
Motor 1
Motor 2
Motor 3
L1:
L1:
L1:
Motor 4
Motor 5
L1:
L1:
Motor 6 L1:
Compressor amps - COOLING
Comp1
Comp2
Comp3
Comp4
Check Reversing valves
Comp1
Comp2
Comp3
Comp4
HP cut out:
Refrigerant charge
Phase 1
Compressor amps - HEATING
Phase 1
A
A
A
A
A
A
A
A
A L2:
A L2:
A L2:
A L2:
A L2:
A L2:
Phase 2
Valve 1:
Valve 2:
Phase 2
A L3:
A L3:
A L3:
A L3:
A L3:
A L3:
Check rotation
A Yes
A Yes
A Yes
No
No
No
A
A
A
Yes
Yes
Yes
Compressor voltage
Comp1:
No
No
Comp1:
Comp3:
No Comp4:
Pressures & temperatures
A
A
A
A
A
A
A
A
Phase 3
Yes
Yes
Phase 3
A
A
A
A
No
No
Temperatures
Suction Disch
°C
°C
°C
°C
Valve 3:
Valve 4:
°C
°C
°C
°C
Yes
Yes
LP
Pressures
HP
Bar
Bar
Bar
Bar
Bar
Bar
Bar
Bar
No
No
A
A
A
A
Suction
Pressures & temperatures
Temperatures Pressures
Disch LP HP
°C °C Bar
°C
°C
°C
Bar LP cut out:
C1: kg C2:
°C
°C
°C kg C3:
Bar
Bar
Bar kg C4:
Bar
Bar
Bar
Bar
Bar kg
V
V
V
V
(9) ELECTRIC HEATER SECTION
Type
AMPS 1 st stage (BALTIC™)
1 2
(10) HOT WATER COIL SECTION
Check Three Way Valve Movement
Yes No
3
Serial No
AMPS 2 nd stage (BALTIC™)
1 2 3
(11) GAS HEATING SECTION
Gas Burner N°1:
Size: Valve type:
Gas Burner N°2:
Size: Valve type:
Pipe size:
Line press:
Gas type:
G
Drop test
Yes
Check manifold pressure:
High fire Low fire
Pressure cut out airflow press switch
No
Pipe size:
Line press:
Gas type:
G
Drop test
Yes
Check manifold pressure:
High fire Low fire mBar/Pa Pressure cut out airflow press switch
No mBar/Pa
Motor amps:
A
Flue temp:
°C
CO
2
%:
(12 REMOTE CONTROL BMS CHECK
Type:
%
CO ppm:
Sensor type:
%
Motor amps:
A
Flue temp:
°C
CO
2
%:
Yes No
%
CO ppm:
Interconnect wiring checked:
%
BALTIC-IOM-1711-E -80-
REFRIGERANT TRANSACTIONS LOGBOOK
General information
Site name:
Site address:
Site operator:
Cooling load :
Refrigerant type:
Unit manufacturer
Refrigerant additions
Date Engineer
Serial Number:
Refrigerant quantity (kg)
Year of installation
Quantity (kg) Reason for addition
Refrigerant removal
Date Engineer Quantity (kg) Reason for removal
Leak tests (part 1)
Date Engineer Test Result Follow up action required
BALTIC-IOM-1711-E -81-
REFRIGERANT TRANSACTIONS LOGBOOK
Leak tests (part 2)
Date Engineer Test Result Follow up Action Required
Follow up actions
Date Engineer Related to test dated Action taken
Testing of automatic leak detection system (if fitted)
Date Engineer Test result Comments
BALTIC-IOM-1711-E -82-
BALTIC-IOM-1711-E -83-
TABLE OF CONTENTS
BALTIC
CERTIFICATES
CERTIGAZ
EU CONFORMITY DECLARATION TEMPLATE
ECODESIGN DATA SHEET TEMPLATE
85
86
87
BALTIC-IOM-1711-E
Certificates are given for information only.
To get the uptodate certificates, please contact your local LENNOX reprensentative.
-84-
CERTIGAZ
BALTIC-IOM-1711-E -85-
EU CONFORMITY DECLARATION TEMPLATE (If applicable)
BALTIC-IOM-1711-E -86-
ECODESIGN DATA SHEET TEMPLATE (If applicable)
BALTIC-IOM-1711-E -87-
SALES OFFICES :
BELGIUM AND LUXEMBOURG
FRANCE
GERMANY
ITALY
NETHERLANDS
+48 22 58 48 610
POLAND
PORTUGAL
SPAIN
UKRAINE
UNITED KINGDOM AND IRELAND
OTHER COUNTRIES :
LENNOX DISTRIBUTION
+33 4 72 23 20 20
Due to LENNOX EMEA ongoing commitment to quality, the specifi cations, ratings and dimensions are subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualifi ed installer and servicing agency.
www.lennoxemea.com
BALTICIV-IOM-1711-E