LG PQCSE342A0 Owner’s Manual


Add to my manuals
61 Pages

advertisement

LG PQCSE342A0 Owner’s Manual | Manualzz
ENGLISH
ITALIANO
ESPAÑOL
FRANCAIS
DEUTSCH
NEDERLANDS
РУССКИЙЯЗЫК
OWNER’S MANUAL
繁體中文
Please read this manual carefully before operating
your set and retain it for future reference.
TYPE : AC Smart II (Advanced Control Smart II)
Option function manual
P/NO :MFL62077720
www.lge.com
AC Smart II (Advanced Control Smart II)
Content
Introduction to AC Smart II option function .........................................................................3
Characteristics of option function .....................................................................................3
Components of option function.........................................................................................4
Activation of option function .................................................................................................5
Web schedule function .........................................................................................................11
Managing schedule group ..............................................................................................12
Creating schedule pattern ..............................................................................................21
Applying schedule ..........................................................................................................38
Checking schedule .........................................................................................................46
Running/Stopping schedule............................................................................................49
Power consumption statistics function ..............................................................................51
Accumulative power consumption...............................................................................................................52
Monthly power consumption ........................................................................................................................55
Setting power consumption view condition ................................................................................................57
Saving power consumption information......................................................................................................59
2
AC Smart II (Advanced Control Smart II)
Introduction to AC Smart II option function
AC Smart II additionally provides various convenient option functions for the users to sue. These
additional functions are provided in SD card format. When the user inserts the SD card to the main
unit of the AC Smart II, the option function can be activated and used.
Characteristics of option function
The characteristics of the option function of AC Smart II are as follows.
■ Web based schedule setting function
By using the web server function of AC SMART II, you can set and apply the schedule of AC SMART
II even from remote locations. The administrator can manage the schedule of AC SMART II through
the network free from where he or she is and reduce any unnecessary operations of the unit by using
the schedule functions.
■ Power consumption statistics function
You can view the power consumption information of the air conditioner. The power consumption is
provided in various methods including total usage, usage by period, monthly/daily usage etc. By using
the statistics information, the administrator can effectively analyze and manage the energy usage.
To use the power consumption statistics function, the PDI and watt-meter to measure the power
consumption must be connected to AC SMART II.
Reference: Type of option function sold
The option functions can be sold in 2 types.
- Web schedule + Power consumption statistics function (PQCSE342A0)
- Web schedule function (PQCSE341A0)
If you have purchased only the Web schedule function, you cannot use the Power
consumption statistics function.
Option function manual
3
ENGLISH
Introduction to AC Smart II option function
Introduction to AC Smart II option function
Components of option function
The following components are included in the packaged box of AC SMART II option function as
shown below. Open the box of AC SMART II and check whether the applicable components are
included.
Quick guide
4
Manual CD
AC Smart II (Advanced Control Smart II)
SD card (Option kit)
Activation of option function
To use the operation function from AC SMART II, use the SD card provided in the box to activate the
function.
To activate the option function, proceed as follows.
1. To use the option function, insert the provided SD card into the SD card slot located at the bottom
of the AC SMART II terminal.
Insert the card having the part with the product name facing up as shown below. Push the card in
until you hear the ʻClickʼ sound.
2. With the AC SMART II terminal turned on, press the keyboard button and the software keyboard
will be displayed on the screen.
Keyboard button
Software keyboard
Option function manual
5
ENGLISH
Activation of option function
Activation of option function
3. After pressing the ʻCtrlʼ key from the software keyboard, press the ʻEscʼ key to display the menu on
the left side of the screen.
When y o u pres s the
‘Ctrl ’ and ‘Es c’ key , the
menu wi l l be di s pl ay ed
4. Select ʻProgram (P)ʼ ➠ ʻWindows Explorerʼ from the menu.
Sel ect ‘Wi ndo ws
Ex pl o rer’ fro m the
menu.
6
AC Smart II (Advanced Control Smart II)
Activation of option function
ENGLISH
5. Windows Explorer will be displayed. Double click on the ʻSDMMC Cardʼ.
Do ubl e cl i ck o n
‘SDMMC Card’ fo l der.
6. Double click on the ʻACSmartActivator.exeʼ file located within the SDMMC Card folder to execute
the file.
Do ubl e cl i ck o n
‘ACSmartActi v ato r. ex e’ fi l e.
Option function manual
7
Activation of option function
7. ʻAC Smart Activatorʼ screen will displayed. Click on ʻActivate internal functionʼ button.
Cl i ck o n [Acti v ate
i nternal functi o n]
butto n.
Reference: Change language
When you select the language from the ʻLanguageʼ item, the text displayed on the AC Smart
Activator screen will change to the selected language.
8. ʻPassword inputʼ screen will be displayed. Use the software keyboard to enter the service
administrator password and click on the [OK] button.
The service administrator password is set to ʻdigital21ʼ.
After enteri ng the pas s wo rd,
cl i ck o n the [OK] butto n.
8
AC Smart II (Advanced Control Smart II)
Activation of option function
activatedʼ will be displayed. Click on the [OK] button.
When the mes s ag e i s
di s pl ay ed, cl i ck o n the
[OK] butto n.
Reference: Change language
When you select the language from the ʻLanguageʼ item, the text displayed on the AC Smart
Activator screen will change to the selected language.
10. Click on the [Close] button of AC Smart Activator and then click on [X] button on the Windows
Explorer to end the applicable program.
Cl i ck o n [Cl o s e] butto n and [X]
butto n to end the pro g ram.
Option function manual
9
ENGLISH
9. When you enter the password correctly, the message saying ʻFunction key has been successfully
Activation of option function
11. It will return to the screen of AC SMART II. Check whether the option function is activated. For
example, connect to the AC SMART II web server function to check whether the schedule menu
can be set.
Check whether the s chedul e
menu can be s et thro ug h the web
10
AC Smart II (Advanced Control Smart II)
Web schedule function
Schedule is the function to run the scheduled operation at specific time by presetting the operation of
the unit (Indoor unit, ventilator, On/Off unit, AWHP).
When the option function is added, the schedule control function and other function set on the main
unit of AC SMART II can be accessed through the web. Through this function, you can set and check
the schedule remotely.
After installing the option function, you can connect to the web server function of AC SMART II to add
the ʻScheduleʼ menu.
Schedul e menu thro ug h the
web
Reference: Limitation of web schedule function use
While setting the schedule function from the AC SMART II terminal, the schedule function through
the web cannot be used and the following message will be displayed.
“Schedule is in use from the terminal. Please use again later.”
In this case, the web schedule function can be used after ending the schedule function setting
through the terminal.
Option function manual
11
ENGLISH
Web schedule function
Web schedule function
Generally the web schedule can be set in accordance to the following order.
1. Edit schedule group
You can create or edit the schedule group through the group edit.
2. Edit schedule pattern
You can create or edit the weekly/daily schedule pattern through schedule pattern
wizard.
3. Set schedule through schedule wizard
You can apply the schedule pattern and operating period to the schedule group
through the schedule wizard.
4. Run and stop the schedule
You can run or stop the schedule applied to the schedule group.
This chapter describes the method of operating the AC SMART II function by using the web schedule.
Managing schedule group
Schedule group is a collection of units running the same operation. When you press the [Edit group]
button on the top right corner, the ʻEdit groupʼ screen will be displayed to create, edit or delete the
schedule group.
Yo u can create a s chedul e g ro up wi th
the s ame co nfi g urati o n as the g ro up
s et fro m the uni t manag ement menu.
Currentl y s el ected g ro up name
and l i s t o f uni ts i ncl uded i n the Yo u can i ncl ude o r ex cl ude
appl i cabl e g ro up are di s pl ay ed.
the uni t fro m a s peci fi c
g ro up.
Li s t o f currentl y
reg i s tered s chedul e
g ro up i s di s pl ay ed.
Yo u can create,
rename o r del ete the
s chedul e g ro up
dependi ng o n each
butto n.
Yo u can des i g nate
the s etti ng .
Yo u can cancel to s av e the s etti ng
and return to the prev i o us s creen.
12
AC Smart II (Advanced Control Smart II)
Li s t o f uni ts no t
i ncl uded i n the
g ro up i s di s pl ay ed.
Web schedule function
ENGLISH
■ Creating schedule group
To create a new schedule group, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To create the schedule group, click on the [Edit group] button.
Cl i ck o n [Edi t g ro up]
butto n
2. ʻEdit groupʼ screen will be displayed. To create a new schedule group, click on the [Add] button.
ʻAdd groupʼ screen will be displayed to enter the name of the schedule group to create.
When y o u cl i ck o n the [Add] butto n,
‘Add g ro up’ s creen wi l l be di s pl ay ed.
Option function manual
13
Web schedule function
3. After entering the name of the schedule group to create, click on the [OK] button.
After enteri ng the g ro up
name, cl i ck o n the [OK]
butto n.
4. Check whether the applicable schedule group is created in the ʻGroup nameʼ. At this time, select
the unit to include to the schedule group from the unregistered unit list and click on the [<] button to
move to the registered unit.
Check whether
s chedul e g ro up i s
created
Cl i ck o n [<] butto n to i ncl ude
the uni t to the reg i s tered uni t
14
AC Smart II (Advanced Control Smart II)
Web schedule function
screen will disappear.
Click on the [OK] button to
save the setting
Reference: Create schedule group on web server
The configuration of the schedule group and physical group created on the web server can be
different.
n Detail Guide
When use a AC Smart II Web Schedule function, have to check below caution.
installation
128 Units
10 Schedule Groups
Setting
Schedule
Spec.
AC Smart II
Schedule Gr.
10
4 weekly patterns For 1Month
Daily pattern
7
7 daily patterns for 1 week
Weekly pattern
4
24 events for 1 day
Event of day
24
[Guide a limitation]
If user set a specification for schedule over company guidance,
AC Smart II canʼt operate Web Schedule function.
Option function manual
15
ENGLISH
5. Click on the [OK] button to save the current setting. When the saving is completed, the group edit
Web schedule function
Information: Set schedule group using basic group setting button
When you click on the [Basic group setting] button located at the top right corner of the ʻEdit groupʼ
screen, same group as the basic control group set in control and monitoring of the ʻUnit
managementʼ menu of AC SMART II terminal will be created in the schedule group.
<Terminal unit screen>
When y o u cl i ck o n [Bas i c g ro up
s etti ng ] butto n, the s ame g ro up as
the g ro up co nfi g ured fro m the ‘Uni t
manag ement’ menu wi l l
auto mati cal l y be created i n the
s chedul e g ro up.
<Web server screen>
16
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
■ Renaming schedule group
To rename the schedule group, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To create the schedule group, click on the [Edit group] button.
Cl i ck o n [Edi t g ro up] butto n
2. ʻEdit groupʼ screen will be displayed. Select the schedule group to rename and click on the
[Rename] button.
After s el ecti ng the
s chedul e g ro up, cl i ck o n
the [Rename] butto n.
Option function manual
17
Web schedule function
3. ʻRename groupʼ screen will be displayed. After entering the name of the schedule group to
rename, click on the [OK] button.
After enteri ng the name o f
the s chedul e g ro up, cl i ck
o n the [OK] butto n.
4. Click on the [OK] button to save the current setting. When the saving is completed, the group edit
screen will disappear.
Cl i ck o n the [OK] butto n
to s av e the s etti ng
18
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
■ Deleting schedule group
To delete the schedule group, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To create the schedule group, click on the [Edit group] button.
Cl i ck o n [Edi t g ro up] butto n
2. ʻEdit groupʼ screen will be displayed. Select the schedule group to delete and click on the [Delete]
button. The applicable schedule group will be deleted.
After s el ecti ng the
s chedul e g ro up to del ete,
cl i ck o n the [Del ete]
butto n.
Option function manual
19
Web schedule function
3. Check whether the applicable schedule group is deleted and click on the [OK] button to save the
current setting. When the saving is completed, the group edit screen will disappear.
Check whether s chedul e
g ro up i s del eted
Click on the [OK] button
20
AC Smart II (Advanced Control Smart II)
Web schedule function
Schedule pattern refers to a certain operation of the unit (Indoor unit, ventilator, On/Off unit, AWHP)
repeated on a weekly or daily basis.
Schedule pattern wizard enables you to configure the operation of the unit on weekly or daily pattern.
The pattern created through the schedule pattern wizard is applied as the schedule to the group
through the schedule wizard to be described in the next chapter.
Schedule pattern wizard proceeds in total of 4 stages as shown below.
1
1. Select schedule pattern type
3
3. Enter schedule pattern name
2
2. Select to add/edit schedule pattern
4
4. Edit schedule pattern
Option function manual
21
ENGLISH
Creating schedule pattern
Web schedule function
■ Adding weekly schedule pattern
To add a weekly schedule pattern, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To create the schedule pattern, click on the [Short cut] button of the
schedule pattern wizard.
Cl i ck o n [Sho rt cut] butto n
o f s chedul e pattern wi zard
2. ʻSchedule pattern edit wizardʼ screen will be displayed. To create a new weekly schedule pattern,
select ʻAdd/Edit weekly schedule patternʼ and then click on the [Next] button.
After s el ecti ng ‘Add/ Edi t
weekl y s chedul e pattern’,
cl i ck o n the [Nex t] butto n.
22
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
3. Select ʻAdd patternʼ and then click on the [Next] button.
Sel ect ‘Add pattern’ and
then cl i ck o n the [Nex t]
butto n.
Reference: Edit weekly schedule pattern
When editing the weekly schedule pattern, select the weekly schedule pattern to edit from the list
and select ʻEdit schedule patternʼ. Everything is the same as the process of adding a weekly pattern
except for the fact that you cannot enter the pattern name at stage 3 of the schedule pattern edit
wizard.
Information: Rename and delete schedule pattern
In stage 2 of the schedule pattern edit wizard,
you can rename the existing schedule pattern
or delete the pattern that has been created.
To rename the schedule pattern, click on the
[Rename pattern] button and enter a new
name.
To delete the schedule pattern, select the
schedule pattern to delete, and click on the
[Delete pattern] button. After renaming and
deleting the schedule pattern, the wizard will
not proceed to the next stage.
Option function manual
23
Web schedule function
4. Enter the name of weekly schedule pattern and click on the [Next] button.
Enter the name o f weekl y s chedul e
pattern and cl i ck o n the [Nex t] butto n.
5. Select the time to operate the unit from ʻSelect timeʼ or ʻSchedule timeʼ. And then from the ʻControl
settingʼ, set the operation of the unit. Refer to the operation that can be set in the following table.
24
AC Smart II (Advanced Control Smart II)
Web schedule function
Set temperature
ENGLISH
Item
Description
You can set the desired indoor temperature you want to maintain.
Operation
You can set the unit (Indoor unit, ventilator, On/Off unit, AWHP) to run and stop.
• [Run]: This turns on the power of the unit.
• [Stop]: This turns off the power of the unit.
Mode
You can set the operating mode of the indoor unit.
• [Cooling]: This runs the unit in air conditioning mode. You can select the
desired temperature between 18°C and 30°C from the set temperature. When
the desired temperature is higher than the indoor temperature during the air
operation, the unit will run in the fan mode.
• [Heating]: This runs the unit in heating mode. You can select the desired
temperature between 18°C and 30°C from the set temperature.
• [Auto]: This judges the indoor condition and maintains at optimal condition
automatically.
Fan speed
Lock
This sets the Fan speed of the indoor unit.
• [Low]: This sets the Fan speed to low level.
• [Med]: This sets the Fan speed to medium level.
• [High]: This sets the Fan speed to high level.
This locks/unlocks the lock function so that the user cannot directly change the
setting of the unit (Indoor unit, ventilator, AWHP)
• [Lock]: This sets the lock function so that all the functions cannot be changed
individually.
• [Unlock]: This cancels the lock function so that all the function can be
changed individually.
Information: Delete schedule
If you want to delete all the existing schedules, click on
the [Delete all] button. If you want to delete the schedule
by day, press the time period of the day you want to
delete and then click on the [Delete daily event] button to
delete all the schedules of the applicable day.
Option function manual
25
Web schedule function
6. When you click on the [Modify] button, the schedule will be added to the table. If you have
additionally planned schedules, repeat the current process and continue to add the set event.
When all the schedules are set, click on the [End] button.
Cl i ck o n the [Mo di fy ] butto n
to add the s chedul e.
When al l the s chedul es are s et,
cl i ck o n the [End] butto n.
Information: Apply daily schedule pattern and apply daily
continuously
When creating or editing the weekly schedule pattern,
you can apply the daily schedule pattern. When you
click on the [Apply daily schedule pattern] button in the
4 stage process of schedule edit pattern wizard, you
can open the daily schedule pattern and apply to
specific days.
<Screen to apply daily schedule
pattern>
Also you can set specific schedule patterns to several
days continuously. When you select the schedule
pattern from the 4 stages of the schedule edit pattern
wizard, and click on the [Apply daily continuously], you
can apply the same pattern throughout several days.
<Screen to apply daily schedule
continuously>
26
AC Smart II (Advanced Control Smart II)
Web schedule function
edit.
Cl i ck o n the [OK] butto n to
end the wi zard.
Option function manual
27
ENGLISH
7. A message saying that the schedule pattern edit is completed. Press the [OK] button to end the
Web schedule function
■ Adding daily schedule pattern
To add a daily schedule pattern, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To create the schedule pattern, click on the [Short cut] button of the
schedule pattern wizard.
Cl i ck o n [Sho rt cut] butto n
o f s chedul e pattern wi zard
2. ʻSchedule pattern edit wizardʼ screen will be displayed. To create a new daily schedule pattern,
select ʻDaily pattern add/editʼ and then click on the [Next] button.
After s el ecti ng ‘Dai l y
pattern add/ edi t’, cl i ck o n
the [Nex t] butto n.
28
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
3. Select ʻAdd patternʼ and then click on the [Next] button.
Sel ect ‘Add pattern’ and
then cl i ck o n the [Nex t]
butto n.
Reference: Edit daily schedule pattern
When editing the daily schedule pattern, select the daily schedule pattern to edit from the list and
select ʻEdit schedule patternʼ. Everything is the same as the process of adding a daily pattern
except for the fact that you cannot enter the pattern name at stage 3 of the schedule pattern edit
wizard.
Information: Rename and delete schedule pattern
In stage 2 of the schedule pattern edit wizard,
you can rename the existing schedule pattern
or delete the pattern that has been created.
To rename the schedule pattern, click on the
[Rename pattern] button and enter a new
name.
To delete the schedule pattern, select the
schedule pattern to delete, and click on the
[Delete pattern] button. After renaming and
deleting the schedule pattern, the wizard will
not proceed to the next stage.
Option function manual
29
Web schedule function
4. Enter the name of daily schedule pattern and click on the [Next] button.
Enter the name o f dai l y
s chedul e pattern and cl i ck
o n the [Nex t] butto n.
5. Select the time to operate the unit from ʻSelect timeʼ or ʻSchedule timeʼ. And then from the ʻControl
settingʼ, set the operation of the unit. Refer to the operation that can be set in the following table.
30
AC Smart II (Advanced Control Smart II)
Web schedule function
Set temperature
ENGLISH
Item
Description
You can set the desired indoor temperature you want to maintain.
Operation
You can set the unit (Indoor unit, ventilator, On/Off unit, AWHP) to run and stop.
• [Run]: This turns on the power of the unit.
• [Stop]: This turns off the power of the unit.
Mode
You can set the operating mode of the indoor unit.
• [Cooling]: This runs the unit in air conditioning mode. You can select the
desired temperature between 18°C and 30°C from the set temperature. When
the desired temperature is higher than the indoor temperature during the air
conditioning operation, the unit will run in the fan mode.
• [Heating]: This runs the unit in heating mode. You can select the desired
temperature between 18°C and 30°C from the set temperature.
• [Auto]: This judges the indoor condition and maintains at optimal condition
automatically.
Fan speed
Lock
This sets the Fan speed of the indoor unit.
• [Low]: This sets the Fan speed to low level.
• [Med]: This sets the Fan speed to medium level.
• [High]: This sets the Fan speed to high level.
This locks/unlocks the lock function so that the user cannot directly change the
setting of the unit (Indoor unit, ventilator, AWHP)
• [Lock]: This sets the lock function so that all the functions cannot be changed
individually.
• [Unlock]: This cancels the lock function so that all the function can be
changed individually.
Information: Delete schedule
If you want to delete all the existing schedules, click on
the [Delete all] button. If you want to delete the schedule
by day, press the time period of the day you want to
delete and then click on the [Delete daily event] button to
delete all the schedules of the applicable day.
Option function manual
31
Web schedule function
6. When you click on the [Add event] button, the schedule will be added to the table. If you have
additionally planned schedules, repeat the current process and continue to add the set event.
When all the schedules are set, click on the [End] button.
Cl i ck o n the [Add ev ent]
butto n to add the s chedul e.
When al l the s chedul es are s et,
cl i ck o n the [End] butto n.
7. A message saying that the schedule pattern edit is completed. Press the [OK] button to end the
edit.
Cl i ck o n the [OK] butto n to
end the wi zard.
32
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
■ Setting detail schedule pattern
When you add or edit the weekly and daily schedule pattern, you can set the detail operation of each
unit through detail schedule.
1.In stage 4 of the weekly or daily schedule pattern wizard, click on the [Advanced] button.
Stag e 4 o f s chedul e pattern
wi zard
Cl i ck o n the [Adv anced]
butto n
2. ʻDetail schedule settingʼ screen to set the detail operation of the unit will be displayed. After setting
the schedule, click on the [Apply] button.
Refer to the following table for the operation you can select in ʻAdvancedʼ.
After s etti ng the s chedul e,
cl i ck o n the [Appl y ] butto n.
Option function manual
33
Web schedule function
[Indoor unit setting item]
Item
Set temperature
Operation
Mode
You can set the desired indoor temperature.
You can set the indoor unit to run and stop.
• [Run]: This turns on the power of the indoor unit.
• [Stop]: This turns off the power of the indoor unit.
You can set the operating mode of the indoor unit.
• [Cooling]: This runs the unit in air conditioning mode. You can select the
desired temperature between 18°C and 30°C from the set temperature. When
the desired temperature is higher than the indoor temperature during the air
conditioning operation, the unit will run in the fan mode.
• [Heating]: This runs the unit in heating mode. You can select the desired
temperature between 18°C and 30°C from the set temperature.
• [Auto]: This judges the indoor condition and maintains at optimal condition
automatically.
• [Dry]: This runs the unit in dehumidifier mode. During the rainy season or
when the humidity is high, you can effectively remove the humidity with this
mode. When you set the indoor unit to this mode, you cannot set a desired
temperature.
• [Fan]: This runs the unit in fan mode. Fresh air will be provided by running the
air purifier. It is good to use this just for air purification during the spring or fall.
When you set the indoor unit to this mode, you cannot set a desired
temperature.
Fan speed
This sets the fan level of the indoor unit. Adjust the fan level considering the
level of indoor contamination.
• [Low]: This sets the Fan speed to low level.
• [Med]: This sets the Fan speed to medium level.
• [High]: This sets the Fan speed to high level.
• [Auto]: This measures the level of indoor contamination automatically and
maintains the optimal condition.
Fan direction
Enable/Disable the lock function for the user to individually control the unit.
• [Set]: The fan direction automatically rotates.
• [Cancel]: The fan direction stays consistent.
Lock
34
Description
This sets the lock function so that the user cannot control the indoor unit.
• [Lock all]: This sets the lock function so that all the functions of the indoor unit
cannot be changed individually.
• [Unlock all]: This cancels the lock all function.
• [Mode lock]: This locks the operating mode of the indoor unit so that it cannot
be controlled individually.
• [Mode unlock]: This cancels the mode lock function.
• [Fan lock]: This locks the fan level so that it cannot be controlled individually.
• [Fan unlock]: This cancels the fan level lock function.
AC Smart II (Advanced Control Smart II)
Web schedule function
Lock
Set limit temperature
ENGLISH
Item
Description
• [Set temperature lock]: This locks the set temperature so that it cannot be
controlled individually.
• [Set temperature unlock]: This cancels the set temperature lock function.
You can limit the indoor temperature setting so that the indoor temperature is set
within a certain temperature range. In this case, the temperature outside of the
set temperature range cannot be controlled individually by the user.
[Ventilator schedule setting item]
Item
Operation
Mode
Fan speed
Lock
User mode
Description
You can set the ventilator to run and stop.
* [Run]: This turns on the power of the ventilator.
* [Stop]: This turns off the power of the ventilator.
You can set the operating mode of the ventilator.
• [Heating]: This runs both the inlet and outlet of the ventilator through the heat
exchanger. Use this mode during the summer and winter when the
temperature and humidity difference between indoors and outdoors is
significant.
• [Normal]: This runs only the inlet of the ventilator through the heat exchanger.
Use this mode during the spring and fall when the temperature and humidity
difference between indoors and outdoors is not significant.
• [Auto]: This measures the indoor and outdoor temperature and automatically
controls the inlet and outlet. Through this, optimal condition is maintained by
maintaining a consistent balance of the indoor air.
This sets the fan level of the ventilator. Adjust the fan level considering the level
of indoor contamination.
• [Low]: This sets the Fan speed to low level.
• [High]: This sets the Fan speed to high level.
• [Super high]: This sets the Fan speed to the maximum level.
• [Auto]: This measures the level of indoor contamination automatically and
maintains the optimal condition. Auto mode cannot be selected by the user and
when the power save mode or speed mode of the user mode are set, it is
automatically set.
This sets the lock function so that the user cannot control the ventilator.
• [Lock]: ]: This sets the lock function so that all the functions of the ventilator
cannot be changed individually.
• [Unlock]: This cancels the lock function.
This designates the additional operating method of the ventilator.
• [Humid on]: This sets the plasma function. Depending on the type of the
ventilator, the function may not be set. This function is currently not supported
and is expected to be supported in the future.
• [Humid off]: This cancels the plasma function.
Option function manual
35
Web schedule function
Item
Description
Reference: What is plasma?
This is the air cleaning function of providing refreshing air with
negative ion. This is the function that not only kills the
household virus or fungus but also the influenza virus, the
representative cold virus, to consider the health as well as the
environment.
User mode
• [Heater on]: This sets the heater function to warm the flowing air during the
cold winter. Depending on the type of the ventilator, the function may not be
set.
• [Heater off]: This cancels the heater function.
• [Power save on]: This operates the ventilator in the most efficient condition to
reduce the power consumption. When the fan level is set to low, high or super
high, this setting will automatically be canceled.
• [Power save off]: This cancels the power save function.
• [Quick operation on]: This sets the ventilator to operate a maximum
performance to prevent the contaminated indoor air and humidity from
spreading into other areas. It is good to use this function when the level of
indoor contamination is high. When the fan level is set to low, high or super
high, this setting will automatically be canceled.
• [Quick operation on]: This cancels the speed function.
[On/Off unit schedule setting item]
Item
Operation
36
Description
You can turn On or Off the device connected to AC SMART II.
• [Run]: This runs the On/Off unit.
• [Stop]: This stops the On/Off unit.
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
[AWHP schedule setting item]
Item
Room temperature
Description
This sets the indoor air temperature.
Water outlet temperature
This sets the water temperature passing through AWHP.
Water tank temperature
This sets the water temperature within the hot water tank.
Operation
You can set the AWHP to run and stop.
• [Run]: This turns on the power of AWHP.
• [Stop]: This turns off the power of AWHP.
You can set the operating mode of AWHP.
• [Cooling]: This runs AWHP in air conditioning mode.
Mode
• [Heating]: This runs AWHP in heating mode.
• [Auto]: This judges the indoor condition and maintains at optimal condition
automatically.
Lock
This sets the lock function so that the user cannot control AWHP individually.
• [Lock]: This sets the lock function so that all the functions of AWHP cannot be
changed individually.
• [Unlock]: : This cancels the lock all function.
Reference: Air temperature and water outlet temperature setting
Even though the air temperature and water outlet temperature item can simultaneously be set in
AC SMART II, actually the AWHP unit is controlled based on one of the two items. Applying criteria
(Air temperature, water outlet temperature) can be set by the remote controller.
Option function manual
37
Web schedule function
Applying schedule
Schedule refers to the process of adding the application period information to the schedule group and
schedule pattern previous set and designating the period for the unit (Indoor unit, ventilator, On/Off
unit, AWHP) to operate for the applicable period.
AC SMART II provides the schedule wizard to easily apply the schedule. The schedule wizard is
composed of total of 6 stages as shown below. But, the schedule copying between groups is done
through a separate 2 stage process.
1
2
1. Select to add/edit schedule
3
4
3. Select schedule start/end date
5
4. Apply set weekly schedule pattern
6
5. Check/edit schedule
38
2. Select to add/edit schedule
6. Set exception date not to apply
schedule
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
To apply the schedule, proceed as follows.
1. When you connect to web server of AC SMART II and select the ʻScheduleʼ menu, the following
screen will be displayed. To apply the schedule, click on the [Short cut] button of the schedule wizard.
Cl i ck o n [Sho rt cut] butto n
o f s chedul e wi zard
2. Schedule wizard screen will be displayed. Select ʻAdd/Edit scheduleʼ and select the schedule
group to apply the schedule. And then click on the [Next] button.
After s el ecti ng ‘Add/ Edi t s chedul e
and s el ecti ng the g ro up, cl i ck o n
the [Nex t] butto n.
Option function manual
39
Web schedule function
3. Select ʻAdd scheduleʼ, and click on the [Next] button.
Sel ect ‘Add s chedul e’ and
cl i ck o n the [Nex t]
butto n.
Information Edit schedule period and delete schedule
In the 2nd stage of the schedule wizard, you can
edit the period to apply the schedule and delete
the created schedule.
To edit the schedule period, press the [Edit
schedule period] button and set the new period.
To delete the schedule, select the schedule period
to delete and press the [Delete schedule] button.
After editing the schedule period and deleting the
schedule, you cannot proceed to the next stage of
the schedule wizard.
40
AC Smart II (Advanced Control Smart II)
Web schedule function
button, the calendar will be displayed. Use the calendar to select the period
(Start and end date) to apply the schedule. After entering the period, click on the [Next] button.
1 . Us e the cal endar to
enter the s tart and end date
2 . Cl i ck o n the [Nex t] butto n.
5. Set whether to apply the weekly schedule pattern. To apply the weekly schedule pattern, select the
ʻApplyʼ item and select the weekly schedule pattern to apply.
If you do not want to apply the weekly schedule pattern, select the ʻNot applyʼ item and directly
enter in 5th the stage. And then click on the [Next] button.
1 . Sel ect whether to appl y
the weekl y s chedul e pattern.
2 . Cl i ck o n the [Nex t] butto n.
Option function manual
41
ENGLISH
4. When you press the
Web schedule function
6. Check the current schedule setting information. Also you can add a new schedule or add/delete
the set schedule. After checking the schedule information, click on the [Next] button.
1 . Check and edi t the s chedul e i nfo rmati o n
2 . Cl i ck o n the [Nex t] butto n.
Reference: Edit schedule
When editing the schedule, the setting of the input item is the same as that of the schedule pattern
setting. For more detail on the setting item, refer to the ʻCreate schedule patternʼ section.
7. Lastly, designate the exception date. Exception date is to set the specific dates within the period to
apply the schedule to exclude the application of the schedule.
If there is a schedule to register as exception date, select the date to designate as exception date
from the calendar and click on the [Set exception day].
Sel ect the
ex cepti o n date and
cl i ck o n the [Set
ex cepti o n day ].
42
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
Reference: Set exception day
Setting the exception day is not a mandatory item. If you do not want to set the exception day, click
on the [End] button to end the schedule setting.
8. When the screen to enter the name of exception date is displayed, enter the name of the exception
day and click on the [OK] button.
After enteri ng the name
o f the ex cepti o n date,
cl i ck o n the [OK] butto n.
9. Check the content of exception day setting and click on the [End] button.
1 . Check the s etti ng
2 . Cl i ck o n the [End] butto n.
Option function manual
43
Web schedule function
Information: Rename and delete exception day
From the exception date edit screen, you can
rename or delete the name of the existing
exception day.
To rename the exception day, select the name of
the exception date and press the [Rename] button
to change the name.
To delete the exception day, select the exception
date and press the [Delete] button.
10. The screen to show that the schedule edit has been completed will be displayed. Click on the
[OK] button to close the schedule wizard screen and end the schedule setting.
Cl i ck o n the [OK]
butto n.
44
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
Information: Copy schedule
You can copy the schedule set to a specific schedule group to the schedule of another schedule
group.
1. From the starting screen of the schedule wizard, select the ʻCopy schedule among groupsʼ item,
and then click on the [Next] button.
Sel ect the ‘Co py
s chedul e amo ng g ro ups ’
i tem, and then cl i ck o n
the [Nex t] butto n.
2. Designate the original group and target group to copy the schedule from and to, and then select
the period to copy. And then click on the [End] button.
1 . Sel ect g ro up
and peri o d
2 . Pres s the
[End] butto n.
3. When you see the schedule wizard completion screen, click on the [OK] button.
Option function manual
45
Web schedule function
Checking schedule
Below screen is the first screen displayed when the user selects the schedule menu. In this screen,
you can check the details of the schedule applied to a specific schedule group. Also you can edit the
schedule directly.
Yo u can s el ect the s chedul e g ro up.
Yo u can s el ect the s chedul e s et i n 1 week
o r 1 mo nth uni t to v i ew the detai l s .
Yo u can s el ect the
s chedul e peri o d.
Yo u can create, edi t o r del ete the
s chedul e g ro up.
Yo u can
run/ s to p the
s et s chedul e.
Yo u can run
the s chedul e
wi zard s o that
the s chedul e
can be s et by
s tag e.
Yo u can v i ew the s chedul e detai l s fo r the week
by ti me zo ne. When y o u cl i ck o n the s et
s chedul e (Bl ue), y o u can check and edi t the
number o f s chedul e and o perati o n.
Yo u can run
the s chedul e
pattern
wi zard s o that
the
weekl y / dai l y
s chedul e
pattern can
be s et by
s tag e.
Reference: Set schedule group and schedule
From the schedule view, you can only check the schedule group and schedule that have been set
up. Therefore, if the schedule group and schedule are not set up, you must first set them up
through the process described in the previous section.
46
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
To check or edit the detail of the schedule, proceed as follows.
1.
When you select the schedule group and period of the schedule to check from the schedule menu,
you can check the set schedule.
When y o u s el ect the s chedul e g ro up and
peri o d, y o u can check the s chedul e.
2. When you click on the set schedule (Displayed in blue), you can check the schedule set in the
applicable time zone. To edit the applied schedule, press the [Edit] button.
When y o u cl i ck o n the s et s chedul e,
y o u can check and edi t the s chedul e.
Option function manual
47
Web schedule function
Information: View schedule detail
When you press the [Advanced] button, you
can see the ʻAdvancedʼ screen. In this
screen, you can view the details of the
schedule operation by unit.
3. The schedule wizard to edit the schedule will be run. When you edit the schedule and press the
[End] button, the editing will be completed.
1 . Check and edi t the
s chedul e i nfo rmati o n
2 . Cl i ck o n the [End] butto n
Reference: Edit schedule
The setting for the input item of editing the schedule is the same as the setting of the schedule
pattern. For more details on the setting item, refer to the ʻCreate schedule patternʼ section.
48
AC Smart II (Advanced Control Smart II)
Web schedule function
ENGLISH
Running/Stopping schedule
When you click on the [Run/Stop] button from the schedule menu, the ʻRun/Stopʼ screen will be
displayed. In this screen, you can run or stop the schedule applied to the group.
Yo u can s el ect to s to p
the s chedul e o f an
i ndi v i dual g ro up o r al l
g ro ups .
When s to ppi ng the
s chedul e by g ro up,
y o u can s el ect the
g ro up to s to p.
Yo u can appl y the
s chedul e run/ s to p s etti ng .
To run o r s to p the s chedul e,
pro ceed as fo l l o ws .
1. Click on the [Run/Stop] button from the schedule menu.
Cl i ck o n the [Run/ Sto p] butto n
Option function manual
49
Web schedule function
2. ʻRun/Stopʼ screen will be displayed.
When running the schedule by group, select the ʻRun schedule by groupʼ item and check the
schedule group to run.
On the other hand, if you want to stop all schedules, select the ʻStop all group scheduleʼ item.
Set whether the run the s chedul e
3. When you click on the [Apply] button, the setting will be completed and the ʻRun/Stopʼ screen will
disappear.
Cl i ck o n the [Appl y ] butto n.
50
AC Smart II (Advanced Control Smart II)
Power consumption statistics function
In AC SMART II, you can check the power consumption of the indoor unit by class, group and unit.
Reference: Before using the power consumption statistics function,
check the PDI connection
To use the power consumption statistics function, the PDI, device for measuring the power
consumption, and AC SMART II and outdoor/indoor unit must be connected. of the current siteʼ.
When you select the statistics menu after installing the option function to check the power
consumption, the statistical menu will include and display the 2 functional tabs shown below.
• Accumulative power consumption (By day): This provides the total power consumption information
during a specific period, daily power consumption information, current power consumption
information
• Monthly power consumption: This provides the power consumption information on a monthly basis
for a certain period of time (3 months, 6 months, 1 year).
Yo u can v i ew the po wer co ns umpti o n
o f the i ndo o r uni t and s tati s ti cal
v al ues fo r a s peci fi c peri o d o f ti me
Yo u can v i ew the mo nthl y
po wer co ns umpti o n by 3
mo nths , 6 mo nths and 1 y ear.
Reference: Statistical information
The statistical function provides the operating time information and power consumption information
during the period the indoor unit operates. The operation time information of the ventilator, On/Off
unit and AWHP is not provided.
Option function manual
51
ENGLISH
Power consumption statistics function
Power consumption statistics function
Accumulative power consumption
Accumulative power consumption is the function of calculating and providing the accumulative power
consumption of the indoor unit during a certain period of time the user selected.
When you press the accumulative power consumption tab, the following screen will be displayed.
Yo u can s et the v i ew co ndi ti o n and
targ et o f the accumul ati v e po wer
co ns umpti o n.
Yo u can s et the peri o d to v i ew
the accumul ati v e po wer
co ns umpti o n o f the i ndo o r uni t.
Yo u can s av e the accumul ati v e
po wer co ns umpti o n i nfo rmati o n
to a fi l e.
Yo u can res et the
accumul ati v e po wer
co ns umpti o n i nfo rmati o n.
Yo u can refres h and v i ew the
accumul ati v e po wer co ns umpti o n
to the l ates t i nfo rmati o n.
Yo u can v i ew the to tal accumul ati v e po wer
co ns umpti o n and s tati s ti cal i nfo rmati o n
fo r the peri o d y o u are v i ewi ng .
* [Reset] button will only be displayed when logged on with the installation expert access.
The accumulative power consumption is displayed in table format including the below information.
Item
Description
Unit Name
This displays the name of the target to view the accumulative operating time of.
Depending on the condition setting, the applicable class, group and indoor unit
is displayed.
Daily power consumption
When you click on the [View] button, the ʻDaily power consumptionʼ screen will
be displayed and you will be able to view the daily power consumption.
Power consumption per period
(KWh)
This displays the total power consumption within the set period of time.
Current power consumption
(W)
This displays the current power consumption of each unit. (Watt/Hour)
52
AC Smart II (Advanced Control Smart II)
Power consumption statistics function
ENGLISH
■ View accumulative power consumption
You can check the accumulative power consumption of the indoor unit for a specific period of time. To
check the accumulative power consumption, proceed as follows.
1. When you press the ʻAccumulative power consumptionʼ tab from the statistics menu, you can set
the period to view the accumulative power consumption from the ʻPeriodʼ item. When you press the
button, you can select the date. And then press the [Refresh] button.
Set the peri o d to v i ew the
accumul ati v e po wer co ns umpti o n
and pres s the [Refres h] butto n.
2. The following information for the accumulative power consumption is displayed on the screen.
Option function manual
53
Power consumption statistics function
Information: View daily power consumption
When you press the [View] button from the daily power consumption item, the ʻDaily power
consumptionʼ screen will be displayed. In this screen, the user can view the power consumption of
the indoor unit during the period set by the user on a daily basis.
When y o u pres s the [Vi ew]
butto n, the dai l y po wer
co ns umpti o n s creen i s di s pl ay ed.
54
AC Smart II (Advanced Control Smart II)
Power consumption statistics function
Monthly power consumption is the function of calculating and providing the monthly power
consumption of the indoor unit during a certain period of time (3 months, 6 months, 1 year) from the
specific month selected by the user.
When you press the monthly power consumption tab, the following screen will be displayed.
Yo u can res et the
mo nthl y po wer
co ns umpti o n
i nfo rmati o n.
Yo u can s et y ear and mo nth
to v i ew the mo nthl y po wer
co ns umpti o n o f the i ndo o r
uni t.
Yo u can s et the v i ew co ndi ti o n
and targ et o f the mo nthl y
po wer co ns umpti o n.
Yo u can v i ew the to tal po wer co ns umpti o n
and mo nthl y po wer co ns umpti o n o f the
i ndo o r uni t fo r the peri o d y o u are v i ewi ng .
Yo u can s av e the
mo nthl y po wer
co ns umpti o n
i nfo rmati o n to a fi l e.
Yo u can refres h and v i ew the
mo nthl y po wer co ns umpti o n
to the l ates t i nfo rmati o n.
Yo u can s et the v i ew co ndi ti o n and targ et
o f the mo nthl y po wer co ns umpti o n.
* [Reset] button will only be displayed when logged on with the installation expert access.
The monthly power consumption is displayed in table format including the below information.
Item
Description
Unit Name
This displays the name of the target to view the accumulative operating time of.
Depending on the condition setting, the applicable class, group and indoor unit
is displayed.
Power consumption per period
(KWh)
Monthly statistics
This displays the total power consumption within the set period of time.
The power consumption within the set period depending on the condition setting
is displayed on a monthly basis.
Option function manual
55
ENGLISH
Monthly power consumption
Power consumption statistics function
■ View monthly power consumption
You can check the monthly power consumption of the indoor unit for a certain period of time from the
specific month.
1. When you press the ʻMonthly power consumptionʼ tab from the statistics menu, you can set the
month as criteria to view the monthly power consumption from the ʻPeriodʼ item. When you press
the
button, you can select the year and month, and the period to view the power consumption
(3months, 6 months, 1 year). And then press the [Refresh] button.
Set the peri o d to v i ew the mo nthl y po wer
co ns umpti o n and pres s the [Refres h] butto n.
2. The following information for the monthly power consumption is displayed on the screen.
56
AC Smart II (Advanced Control Smart II)
Power consumption statistics function
You can set the view condition for the accumulative and monthly power consumption. To set the view
condition, proceed as follows. The description uses the accumulative power consumption as the
example from here on. The view condition setting for the monthly power consumption is the same.
1. Press the [Set option] button located on the ʻAccumulative power consumptionʼ tab. ʻCondition
settingʼ screen to set the viewing unit and target will be displayed.
When y o u pres s the [Set o pti o n] butto n, the
‘Co ndi ti o n s etti ng ’ s creen wi l l be di s pl ay ed.
2. Set the viewing unit and target, and press the [Apply] button.
For more detail on the setting item,
refer to the following table.
After s etti ng the co ndi ti o n, pres s the [OK] butto n.
Option function manual
57
ENGLISH
Setting power consumption view condition
Power consumption statistics function
Type
View option
Item
Set to display the usage information by zone.
Group view
Set to display the usage information by group.
Unit view
Target setup
Description
Zone view
Set to display the usage information by unit.
Select zone
Set the class to display the usage information.
Select group
Set the group within the class to display the usage information.
3. The message to check that the changed information is saved will be displayed. Press the [Yes]
button.
Pres s the [Yes ]
butto n.
4. The accumulative power consumption information that fist the set condition is displayed on the
screen.
58
AC Smart II (Advanced Control Smart II)
Power consumption statistics function
The accumulative and monthly power consumption that has been viewed can be saved in external
USB memory as Excel file format. To save the view result to the file, proceed as follows. The
description uses the accumulative power consumption as the example from here on. The file saving
method for the monthly power consumption is the same.
1. Connect the external USB memory to AC SMART II and view the accumulative power
consumption. When the results of the accumulative power consumption is displayed on the screen,
press the [Save] button.
After v i ewi ng the s tati s ti cs
i nfo rmati o n, pres s the
[Sav e] butto n.
2. ʻSave asʼ screen will be displayed. Enter the name of the Excel file to save and then press the [OK]
button.
After enteri ng the name,
pres s the [OK] butto n.
Option function manual
59
ENGLISH
Saving power consumption information
Power consumption statistics function
3. A message confirming that the file is saved will be displayed. When you press the [OK] button, the
file saving process will be completed. After that, you can disconnect the USB drive connected to
AC SMART II.
Pres s the [OK] butto n.
Information: Reset statistical information
When you have installed AC SMART II for the
first time or after an error has occurred, the
statistical information may not be displayed
correctly. In this case, press the [Initialize]
button to reset the previous statistical
information. The [Initialize] button will be
displayed only when logged on as installation
expert.
Information: Refresh to latest statistical information
While the statistical information is displayed
from the statistics menu, the units connected to
AC SMART II are still in operation. But the
statistical information is not immediately
reflected on the statistics screen.
To view the latest statistics information, press
the [Refresh] button located on the right side of
the accumulative and monthly power
consumption screen.
The statistics information displayed on the
screen will be refreshed to the latest
information.
60
AC Smart II (Advanced Control Smart II)

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals