AM✴✴✴✴XMDBC Series
AM✴✴✴✴XMKKC Series
Air Conditioner
installation manual
imagine the possibilities
Thank you for purchasing this Samsung product.
DVM S ECO_IM_EN_DB68-04650A-04.indd 1
2017-05-19 오후 5:26:15
Contents
Before installation
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Outdoor unit type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation combination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Deciding to where to install the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installing the product
Installation and base ground work for an outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigerant pipe installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting indoor unit option switch and key function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection and check operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Charging refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
13
33
38
39
44
47
48
Others
Checking lists after finishing installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Trial operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
ENGLISH-2
DVM S ECO_IM_EN_DB68-04650A-04.indd 2
2017-05-19 오후 5:26:16
Before installation
Safety precautions
Carefully follow the precautions listed below because they are essential to guarantee the safety of the equipment.
General information
ffCarefully read the content of this manual before installing the air conditioner and store the manual in a safe place in order
to be able to use it as reference after installation.
ffFor maximum safety, installers should always carefully read the following warnings.
ffStore the operation and installation manual in a safe location and remember to hand it over to the new owner if the air
conditioner is sold or transferred.
ffThis manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types
of units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be
responsible for damages arising from the use of non compliant units.
ffThe manufacturer shall not be responsible for damage originating from unauthorized changes or the improper
connection of electric and requirements set forth in the “Operating limits” table, included in the manual. Making such
changes or improper connections may damage the units and invalidate the warranty.
ffThe air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable
to be installed in areas used for laundry.
ffDo not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply.
ffIn order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact
SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
ffAlways remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations
should be performed by qualified personnel only.
ffThe unit contains moving parts, which should always be kept out of the reach of children.
ffDo not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may
cause electric shocks or fires.
ffDo not place containers with liquids or other objects on the unit.
ffAll the materials used for the manufacture and packaging of the air conditioner are recyclable.
ffThe packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with
current laws.
ffThe air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air
conditioner must be disposed of in authorized centers or returned to the retailer so that it can be disposed of correctly
and safely.
ffThis appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use
of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play
with the appliance.
ffWhen the product operates in heat mode during winter time, it operates protection mode when the outdoor
temperature drops below 0 °C. Therefore, supply the power during winter time. If the power is not supplied, compressor
protection mode will not operate and cause product malfunction.
01 Before installation
WARNING
• Always disconnect the air conditioner from the power supply before servicing it or
accessing its internal components.
• Verify that installation and testing operations are performed by qualified personnel.
• Verify that the air conditioner is not installed in an easily accessible area.
ENGLISH-3
DVM S ECO_IM_EN_DB68-04650A-04.indd 3
2017-05-19 오후 5:26:16
Safety precautions
Installing the unit
IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines. Always
disassemble the electric lines before the refrigerant tubes.
ffUpon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears
damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the
authorized technician has collected the material from the retailer.)
ffAfter completing the installation, always carry out a functional test and provide the instructions on how to operate the air
conditioner to the user.
ffDo not use the air conditioner in environments with hazardous substances or close to equipment that release free flames
to avoid the occurrence of fires, explosions or injuries.
ffOur units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from
both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible
and easy to disassemble without endangering people and objects.
ffFor this reason, when provisions of the installation manual are not complied with, the cost required to access and repair
the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaffolding or any other
elevation system will NOT be considered part of the warranty and will be charged to the end customer.
Power supply line, fuse or circuit breaker
ffAlways make sure that the power supply is compliant with current safety standards. Always install the air conditioner in
compliance with current local safety standards.
ffAlways verify that a suitable grounding connection is available.
ffVerify that the voltage and frequency of the power supply comply with the specifications and that the installed power is
sufficient to ensure the operation of any other domestic appliance connected to the same electric lines.
ffAlways verify that the cut-off and protection switches are suitably dimensioned.
ffVerify that the air conditioner is connected to the power supply in accordance with the instructions provided in the
wiring diagram included in the manual.
ffAlways verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric
specifications and with the instructions provided in the wiring scheme. Always verify that all connections comply with
the standards applicable to the installation of air conditioners.
ffDevices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
ENGLISH-4
DVM S ECO_IM_EN_DB68-04650A-04.indd 4
2017-05-19 오후 5:26:16
Outdoor unit type
Model
Cooling only
AM040✴XMDBC
AM050✴XMDBC
AM040✴XMKKC
AM050✴XMKKC
1phase
AM060✴XMDBC
AM060✴XMKKC
01 Before installation
Shape
Installation combination
ffYou must install the indoor unit that uses R-410A only.
ffIf sum capacity of the combined indoor units exceeds the capacity of an outdoor unit, the capacity of each indoor unit is
reduced below the rated capacity. Therefore, keeping the combination of indoor units within the capacity of an outdoor
unit is recommended.
Outdoor unit
Outdoor unit capacity (HP)
The maximum number of
connectable indoor units
Total capacity of the
connected indoor units
(Btu/h)
AM040✴XMDBC
AM040✴XMKKC
4
6
19,100~49,500
AM050✴XMDBC
AM050✴XMKKC
5
8
23,900~62,100
AM060✴XMDBC
AM060✴XMKKC
6
9
26,600~68,900
ENGLISH-5
DVM S ECO_IM_EN_DB68-04650A-04.indd 5
2017-05-19 오후 5:26:16
Deciding to where to install the outdoor unit
Decide the installation location based on the following condition and obtain the user’s approval.
ffAvoid a place that may disturb your neighbor. Noise may occur from the outdoor unit and the discharged air may run into
the neighborhood. (Be careful of the operation time in a residential area)
ffInstall the outdoor unit on a hard and even area that can support its weight.
ffChoose a flat place where rainwater does not settle or leak.
ffChoose a place that will avoid strong winds.
ffChoose a place that is well ventilated and allows enough space for repairs and service. (Discharge duct can be purchased
privately.)
ffChoose a place where the connection of refrigerant pipe between an indoor unit and outdoor unit is within allowed
distance.
ffMake sure that the condensed water dripping from the drain hose runs out properly and safely.
ffChoose a place where flammable gas does not leak.
ffChoose a place where the unit could not come into contact with snow and rain.
ffWhen installing the outdoor unit near sea shore, make sure it is not directly exposed to sea breeze.
-- When installing the outdoor unit near sea shore, consult the qualified installer since the places above require additional
measures for corrosion resistance. (You should remove salt and dust of a heat exchanger at least once a year.)
When installing an outdoor unit near sea shore
ffWhen installing an outdoor unit near sea shore, it should be placed behind a building or surrounded by wind protection
wall.
ffInstall the outdoor unit in a place where water can drain smoothly.
Outdoor unit
Sea breeze
Sea breeze
Outdoor unit
Sea
Sea
Protection wall
Outdoor unit
Sea breeze
Sea
❋❋ Protection wall should be constructed with a solid material such
as concrete to block the sea breeze and the height and the width
of the wall should be 1.5 times larger than the size of the outdoor
unit. (Also, allow over 700 mm space between the protection wall
and the outdoor unit for ventilation of exhaust air.)
❋❋ Corrosion registance model (AM***MXMKKC/EA) can be installed
in front of a structure, without a protection wall.
However, it must be installed where the water containing salt does
not contact the outdoor unit directly.
❋❋ As we cannot guarantee that the corrosion resistance model can
prevent corrosion completely, we recommend that you install a
protection wall, or install the outdoor unit behind a structure
(such as building) that can block see breeze.
ENGLISH-6
DVM S ECO_IM_EN_DB68-04650A-04.indd 6
2017-05-19 오후 5:26:16
CAUTION
Indoor Unit
01 Before installation
• Install the indoor unit away from any interfering sources such as radio, computer, stereo equipment and also
select a place where the electrical wiring work and an indoor unit installation are possible.
-- Especially keep the unit at least 3 m away from the electrical equipment in an area where weak
electromagnetic waves are generated and install the protection tube to protect the main power cable and
communication cable.
-- Make sure that there is no equipment that genetrates electromagnetic waves. If so, malfunction of the control
system may occur due to the effect of the electromagnetic wave. (For example: The remote control sensor of
the indoor unit may not have good reception in an area with fluorescent lamp style lighting.)
• Make sure the outdoor unit is installed in a safe place where it will not be obstructed by snowfall. The frame
should be installed in a place where the air inlet and heat exchanger of the unit are not buried in the snow.
• A ventilation system may be required when the outdoor unit is installed in a closed space or room, even though
R-410a is not poisonous or flammable.
• Install railing around the outdoor unit to prevent it falling when the unit is installed on a high place such as the
roof of the building.
• Avoid installing the units in places near an exhaust pipe and ventilating opening exposed to corrosive gas,
oxides of sulfur, ammonia gas or sulfur gas herbicides. (These places need additional anticorrosive treatments.
Please contact manufacture to avoid corroding copper pipes or soldered parts.)
• There shouldn’t be any inflammable material such as wood and oil around the indoor unit. Otherwise, external
fire may spread to the product.
• According to the condition of power supply, electric noise or unstable voltage can occur malfunction of electric
parts or control system. (At the ship or places using power supply from electric generator… etc)
Remote Control
1 m or more
1 m
or m
ore
Breaker
ore
1.5 m or m
Breaker
Stereo
ore
or m ore
m
1.5 or m
m
1.5
more
3 m or
Outdoor Unit
ffMake sure that the water dripping from the drain hose runs away correctly and safely.
ffYou should repaint or protect the damaged part so that the paint of the cabinet does not peel off and become rusty
during installation. When the cabinet becomes rusty, the life of an outdoor will be reduced.
ENGLISH-7
DVM S ECO_IM_EN_DB68-04650A-04.indd 7
2017-05-19 오후 5:26:16
Installation location
ffMake a space for ventilation and service as seen in the picture.
ffWhen multiple outdoor units are combined for installation, allow enough space for ventilation against a wall. If the
ventilation space is not allowed, product malfunction may occur.
ffThe side with logo is the front side of the outdoor unit.
❋❋ Figure Description
Top view
Side view
Back side : Air intake
Front side : Air
outlet
Back side : Air
intake
Front side : Air outlet
•
,
Air flow direction.
When installing 1 outdoor unit
❋❋ When the air outlet is toward the wall
(Unit : mm)
1500 or more
300 or more
❋❋ When the air outlet is opposite the wall
2000 or more
150 or more
1500 or more
300 or more
❋❋ When 3 sides of the outdoor unit are blocked by the wall ❋❋ The upper part of the outdoor unit is blocked and the air
outlet is toward the wall
600 or more
300 or more
300 or more
1500 or more
500 or more
❋❋ The upper part of the outdoor unit is blocked and the air ❋❋ When the walls are blocking front and the rear of the
outlet is opposite the wall
outdoor unit
ENGLISH-8
DVM S ECO_IM_EN_DB68-04650A-04.indd 8
2017-05-19 오후 5:26:17
When installing more than 1 outdoor unit
(Unit : mm)
300 or more
600 or more
600 or more
600 or more
600 or more
600 or more
1500 or more
300 or more
❋❋ When the walls are blocking front and the rear of the outdoor units
01 Before installation
300 or more
❋❋ When 3 sides of the outdoor unit are blocked by the wall
❋❋ When front and rear side of the outdoor unit is toward the wall
1500 or more
600 or more
3000 or more
3000 or more
300 or more
• Should adopt bar type louver. Don’t use a type of rain resistance louver.
WARNING
[Bar type louver]
[Rain resistance louver]
• Louver specifications.
-- Angle criteria : less than 20˚
-- Opening ratio criteria : greater than 80%
ENGLISH-9
DVM S ECO_IM_EN_DB68-04650A-04.indd 9
2017-05-19 오후 5:26:17
Installation location
Moving the Outdoor Unit
ffSelect the moving route in advance.
ffBe sure that moving route is safe from the weight of the outdoor unit.
ffDo not slant the product more than 30˚ when carrying it. (Do not lay the product down sideways.)
ffThe surface of the heat exchanger is sharp. Be careful not to get injured while moving and installing.
When moving with a crane or wire rope
ffWhen moving an outdoor unit to a higher place such as the rooftop.
-- Fasten the wire rope as seen in the picture.
-- Move the outdoor unit with the product packed to prevent possible product
damage during the transportation.
Wire rope /
straps
Wood palette
When moving an outdoor unit with hands
ffMoving the outdoor unit by lifting up and carrying due to the short travel distance.
-- Two people should carry the outdoor unit by holding transportation handle.
-- Be careful not to damage the heat exchanger of the rear side of the outdoor unit during
transportation.
-- Be careful not to get hurt by the sharp surface of the heat exchanger.
ENGLISH-10
DVM S ECO_IM_EN_DB68-04650A-04.indd 10
2017-05-19 오후 5:26:17
Installing the product
Installation and base ground work for an outdoor unit
02
Installing the product
ffInstall the outdoor unit 150 mm higher than the base ground and install the drain hole to connect the pipe to the
drainage.
ffWhen the front fan of an outdoor unit is installed in a place where the average snowfall is more than 150 mm, the
discharge duct should be attached to the outdoor unit.
ffThe concrete foundation should be 1.5 times larger than bottom of the outdoor unit.
ffIt is necessary to install wire mesh or steel bar when outdoor units are installed on a soft foundation.
ffWhen installing multiple outdoor units at the same place, install the H beam on the base ground. (When installing a
number of outdoor units, you can install it on the base ground.)
ffInstall the H beam(150 mm x 150 mm x t10 : basic specification) or vibration absorption frame to jut out from the base
ground.
ffAfter installing the H beam, apply corrosion protection.
ffInstall a square pad(t=20 mm or more) to prevent vibration from the outdoor unit onto the base ground. Place the
outdoor unit on the H beam and fix it with the bolt, nut and washer. (Fix with M10 basic anchor bolt, nut and washer.)
Outdoor unit
Anchor bolt
20 mm
Nut, Spring washer
A
Square pad
H beam
75 mm or more
A+10~20 mm or more
ENGLISH-11
DVM S ECO_IM_EN_DB68-04650A-04.indd 11
2017-05-19 오후 5:26:18
Installation and base ground work for an outdoor unit
Base ground work
Drain hole
Install the outdoor unit
horizontally on the ground
150 mm or more
150 mm or more
< When installing on the roof >
< When installing on the ground >
ffThe outdoor unit should be supported within the range of measurement below for base ground work.
(Unit : mm)
360
384
330
Anchor bolt position
620
940
ffWhen the outdoor unit needs to be supported, fix it with wire as shown in the picture.
-- Slightly unwind the four screws on the cover top of the outdoor unit.
-- Wind wires round the four screws and fasten the screws again.
-- Fix the wires to the ground.
CAUTION
• If the outdoor unit is not fixed securely, product may fall and it might cause loss of life or property damage.
• Do not install the outdoor unit on a wood palette.
• Fix the outdoor unit securely to the base ground with anchor bolts.
• The manufacturer is not responsible for the damage occurred by not adhering to the standard of the installation.
• To protect the outdoor unit from external condition such as rain, install it on the base ground and connect the
drain pipe to the drainage.
ENGLISH-12
DVM S ECO_IM_EN_DB68-04650A-04.indd 12
2017-05-19 오후 5:26:18
Refrigerant pipe installation
Refrigerant pipe work
• When installing, make sure there is no leakage. When collecting the refrigerant, stop the compressor first before
removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works
with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle
abnormally high. It may cause explosion and injury.
Tool
Work
If compatible with conventional tool
Pipe cutter
Pipe cutting
Flaring tool
Pipe flaring
Refrigerant oil
Refrigerant pipe work
Apply refrigerant oil on
flared part
Pipe bender
Pipe bending
Nitrogen gas
Inhibition of oxidization
Manifold gauge
Refrigerant charging
hose
Vacuum pump
Air tightening test
Exclusive ether oil, ester oil, alkali benzene oil
or synthetic oil
Compatible
Pipe brazing
Need exclusive one to prevent mixture of R-22
refrigerant oil use and also the measurement is
not available due to the high pressure.
Air tightening test ~
additional refrigerant
charging
Vacuuming, charging and
checking operation
Vacuum drying
Compatible (Use products which contain the check valve to prevent the oil
from flowing backward into the outdoor unit.)
Use the one that can be vacuumed up to 100.7 kpa(5 Torr.-755 mmHg).
Scale for refrigerant
charging
Compatible
Gas leak detector
Gas leak test
Flare nut
Compatible
Connect flare nut with
pipe
Torque wrench
Brazing tool
Installing the product
WARNING
02
ffThe length of refrigerant pipe should be as short as possible and the height difference between an indoor unit and
outdoor unit should be minimized.
ffThe piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length, height
difference, and the allowable length after branching is done.
ffThe pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
ffAfter pipe installation, charge the refrigerant according to the length of the pipe and R-410A refrigerant should be used.
ffUse clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside pipe.
ffUse tools and accessories that fit on R-410A only.
Need exclusive one due to the refrigerant
leakage or inflow of impurities.
Need exclusive one
( The one for R-134a can be used)
You must use the flare nut equipped with product.
Refrigerant leakage may occur when the conventional flare nut for R-22 is used.
ENGLISH-13
DVM S ECO_IM_EN_DB68-04650A-04.indd 13
2017-05-19 오후 5:26:18
Refrigerant pipe installation
Selecting refrigerant pipe
Temper grade and minimum thickness of the refrigerant pipe
CAUTION
Outer diameter [mm]
Minimum thickness [mm]
ø6.35
0.7
ø9.52
0.7
ø12.70
0.8
ø15.88
1.0
ø19.05
0.9
ø22.23
0.9
Temper grade
Annealed
Drawn
• For pipes larger than Ø 19.05, drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used. If a
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause
personal injury.
Pipe installation between an outdoor unit and the first Y-joint
Outdoor unit capacity
[HP(Btu)]
Liquid pipe [mm]
Gas pipe [mm]
One step upgraded pipe
[mm]
4(37,500)
ø9.52
ø15.88
ø19.05
5(49,500)
ø9.52
ø15.88
ø19.05
6(54,600)
ø9.52
ø19.05
ø22.23
ffInstall the refrigerant pipe according to main pipe size of each outdoor unit capacity.
ffWhen the pipe length between an outdoor unit and the farthest indoor unit including elbow exceeds 90 m, the gas pipe
size should be upgraded one step among the main pipes from the outdoor unit to the first Y-joint. (The liquid pipe size
will be maintained.)
ffIf the capacity of the outdoor unit can decline due to the pipe length, upgrade the pipe size one step (gas pipe).
First Y-joint
Main pipe size up
ENGLISH-14
DVM S ECO_IM_EN_DB68-04650A-04.indd 14
2017-05-19 오후 5:26:18
Pipe installation between Y-joints
Pipe diameter (O•D•mm)
Indoor unit total capacity
[kW(Btu/h)]
Liquid pipe (mm)
X ≤ 15.0(51,200)
Gas pipe (mm)
ø15.88
ø9.52
ø19.05
02
15.0(51,200) < X ≤ 23.2(79,200)
Selecting the first Y-joint
Other Y-joints
Total indoor unit capacity
under the selected Y-joint
[kW(Btu/h)]
Y-joint model
Outdoor unit capacity
[HP(Btu)]
Y-joint model
4(37,500)
MXJ-YA1509✴
X ≤ 15.0(51,200)
MXJ-YA1509✴
5(49,500)
MXJ-YA1509✴
15.0(51,200) < X ≤ 40.6(138,500)
MXJ-YA2512✴
6(54,600)
MXJ-YA2512✴
Installing the product
Selecting Y-joint
ffSelect the first Y-joint according to main pipe size of each outdoor unit capacity.
ffSelect the other Y-joints according to the total indoor unit capacity under the selected Y-joint.
Keeping refrigerant pipe
To prevent foreign materials or water from entering the pipe, it is important to keep the refrigerant pipe clean and dry and to
seal it during installation.
Apply correct sealing method depending on the environment.
Exposure place
Outside exposure
Inside exposure
Exposure time
Sealing type
Longer than one month
Pipe pinch
Shorter than one month
Taping
-
Taping
ENGLISH-15
DVM S ECO_IM_EN_DB68-04650A-04.indd 15
2017-05-19 오후 5:26:18
Refrigerant pipe installation
Refrigerant pipe brazing and safety information
Important information for refrigerant pipe work
ffMake sure that there is no moisture inside the pipe.
ffMake sure that there are no foreign materials and impurities in the pipe.
ffMake sure that there is no leak.
ffMake sure to follow the instruction when brazing and keeping the pipe.
Nitrogen flushing brazing
ffUse Nitrogen gas when brazing the pipes as shown in the picture.
ffIf you do not perform nitrogen flushing when brazing the pipes, oxide may form inside the pipe. It can cause the damage
of the important parts such as compressor, valves.
ffAdjust the flow rate of the Nitrogen flushing with a pressure regulator to maintain 0.05 m3/h or less.
ø6.35 copper pipe
Brazing part
Shut-off valve
Nitrogen gas
Pressure regulator
Taping
Flow meter
High pressure hose
Direction of the pipe when brazing
ffBrazing the pipe should be done with the pipe headed downward or horizontally.
ffAvoid brazing with the pipe headed upward.
CAUTION
• The test liquid used to detect leakage after pipe brazing should be the designated one. The use of the test liquid
containing sulfur element may cause pipe corrosion.
ENGLISH-16
DVM S ECO_IM_EN_DB68-04650A-04.indd 16
2017-05-19 오후 5:26:18
Cutting or Flaring the pipes
ffMake sure that you prepared the required tools.
-- Pipe cutter, reamer, flaring tool and pipe holder, etc.
ffIf you want to shorten the pipe, cut it using a pipe cutter ensuring that the cut edge remains at 90° with the side of the pipe.
-- There are some examples of correctly and incorrectly cut edges below.
02
Pipe cutter
Oblique
Rough
Burr
Installing the product
90°
Pipe
ffTo prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.
ffCarry out flaring work using flaring tool as shown below.
[Flaring tool]
A
York
Flaring bar
Flaring bar
Clutch type
Wing nut type
Pipe
Pipe
Flare nut
A(mm)
Pipe diameter (mm)
Conventional flare tool
Flare tool for R-410A
clutch type
Clutch type
ø6.35
0~0.5
1.0~1.5
1.5~2.0
ø9.52
0~0.5
1.0~1.5
1.5~2.0
ø12.70
0~0.5
1.0~1.5
1.5~2.0
ø15.88
0~0.5
1.0~1.5
1.5~2.0
Wing nut type
ffCheck that you flared the pipe correctly.
-- There are some examples of incorrectly flared pipes below.
Correct
CAUTION
Inclined
Damaged Surface
Cracked
Uneven Thickness
• If foreign matters or BURRs are not removed after cutting pipe, refrigerant gas may leak.
• If foreign matters enter inside the pipe, the important interior parts of the unit may get damaged or product
efficiency will be reduced. So, the direction of pipe should be downward during pipe cutting or flaring.
ENGLISH-17
DVM S ECO_IM_EN_DB68-04650A-04.indd 17
2017-05-19 오후 5:26:19
Refrigerant pipe installation
Tightening flare connection area
ffCheck that the flaring is properly made.
ffAlign the center of the piping and sufficiently tighten the flare nut with fingers. Finally, tighten the flare nut with torque
wrench until the wrench clicks. When tightening the flare nut with torque wrench, ensure the direction for tightening
follows the arrow on the wrench.
ffMake sure to use ester oil to coat the flare connection section.
Pipe
CAUTION
Connection torque
Flare dimension (L, mm)
kgf•cm
N•m
ø6.35
140~180
14~18
8.70~9.10
ø9.52
350~430
34~42
12.80~13.20
ø12.70
500~620
49~61
16.20~16.60
ø15.88
690~830
68~82
19.30~19.70
Flare shape (mm)
45° ±2°
Outer diameter (D, mm)
Flare nut
90° ±2°
Flare connection section
L
R 0.4~0.8
D
• Blowing Nitrogen gas should be done when brazing the pipe.
• Make sure to use the provided flare nut.
• Make sure that there are no cracks on the bent pipe.
• Do not fasten the flare nut with excessive strength.
• Use ester oil to coat the flare connection area to prevent refrigerant leak. R-410A is a high pressure refrigerant.
Therefore, there is a risk of refrigerant leakage if the flare connection is not coated with ester oil.
ENGLISH-18
DVM S ECO_IM_EN_DB68-04650A-04.indd 18
2017-05-19 오후 5:26:19
Pipe installation for an outdoor unit
Pipe direction
The refrigerant pipe can be pulled out from front, flank, rear, and bottom side, so install it depending on the installation site
condition.
Installing the product
CAUTION
Caution for using knock-out hole
• Make sure not to damage the exterior of the outdoor unit.
• Remove all burrs at the edge of the knock-out hole and apply the paints it to prevent
rust.
• Use a cable tube and bushing to prevent a cable from being damaged when passing
through a knock-out hole.
• After installing pipes, block the unused knock hole to prevent small animal from
entering. However, the radiant heat hole (A) should be able to intake air.
02
CAUTION
Caution for connecting the pipe
• When brazing the pipe, the unit may get damaged by a brazing fire and a
flame. Use a flame proofing cloth to protect the unit from a brazing fire or
flame.
• The O-ring and Teflon packing inside service valve may get damaged by a
brazing fire. Wrap the bottom side of the service valve with a wet cloth and
braze it as shown above. Make sure not to interrupt the brazing with the
drips from the wet cloth.
High pressure (Liquid side)
• The connecting pipes of liquid side and gas side should not contact each
other nor should they contact to the product. Vibration may cause damage
Low pressure (Gas side)
to the pipes.
Outdoor unit refrigerant pipe connection
Classification
Working process
Front, flank, rear side of pipe connection
• First, remove the pipe cover from unit.
• Separate the knock-out hole to use. If
the hole is open, small animals such as
squirrels and rats may get into the unit
through the hole and the unit may be
damaged.
Bottom side of pipe connection
• Separate the knock-out hole at the bottom
side of the unit and install the  pipe.
• After installing and insulating the pipe,
close up the remaining gap. If the gap
remains open, small animals such as rats
and squirrels may get inside the unit and
cause damage to the unit.
ENGLISH-19
DVM S ECO_IM_EN_DB68-04650A-04.indd 19
2017-05-19 오후 5:26:19
Refrigerant pipe installation
Refrigerant pipe installation examples
Using a Y-joint
Using a Y-joint/EEV kit
Using a header joint
Using a header joint/ Y-joint
Allowable length of the refrigerant pipe and the installation examples
Connection by Y-joint
Outdoor unit
Connection by Y-joint/EEV kit
Outdoor unit
ENGLISH-20
DVM S ECO_IM_EN_DB68-04650A-04.indd 20
2017-05-19 오후 5:26:20
Classification
Y-joint connection
Actual Length
Ex) 6 indoor units
a+b+c+d+j ≤ 150 m(70 m)
Equivalent
length
The distance between an outdoor unit and the farthest indoor unit ≤
175 m(80 m)
Main pipe
length
The main pipe(a) from the outdoor unit to the first Y-joint should be less than
110 m.
Total length
The sum of the total length of pipes should be less then 300 m(150 m).
Height
H1: The difference of height between an outdoor unit and indoor unit <
50 m(30 m)
Outdoor unit
~ Indoor units
Maximum allowable length
after Y-joint
Ex) 8 indoor units
a+b+c+d+e+f+g+p≤ 150 m(70 m)
Height
Actual Length
H2: The difference of height between indoor units ≤ 15 m
The distance between the first Y-joint
and the farthest indoor unit ≤ 40 m
Ex) 8 indoor units
b+c+d+e+f+g+p≤ 40 m
EEV Kit
Allowable length between EEV kit and
an indoor unit ≤ 20 m
Ex) h, l, j ≤ 20 m
Model name
2 m or less
MEV-E24SA
MEV-E32SA
Installing the product
Maximum
allowable
height
Outdoor unit
~ Indoor units
The distance between the outdoor unit and the farthest indoor unit ≤
150 m(70 m)
02
Maximum
allowable
length of
pipe
Y-joint / EEV kit connection
Remarks
1 indoor
MXD-E24K132A
MXD-E24K200A
EEV Kit ~
Indoor units
Actual pipe lengh
2 indoor
MXD-E32K200A
20 m or less
MXD-E24K232A
MXD-E24K300A
MXD-E32K224A
Apply to products
without EEV (Wall
mounted & ceiling)
3 indoor
MXD-E32K300A
❋❋ When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90 m, upgrade the low
pressure pipe of the main pipe one step.
❋❋ Values in ( ) are only applied for AM040/050✴XMDBC and AM040/050✴XMKKC.
ENGLISH-21
DVM S ECO_IM_EN_DB68-04650A-04.indd 21
2017-05-19 오후 5:26:20
Refrigerant pipe installation
Connection by header joint
Outdoor unit
Header joint
g
Indoor unit
Connection by Y-joint/header joint
Outdoor unit
Header joint
g
Y-joint
Indoor unit
Classification
Header joint connection
Actual Length
Maximum
allowable
length of
pipe
Outdoor
unit ~
Indoor units
Maximum
allowable
height
Outdoor
unit ~
Indoor units
Ex) 8 indoor units
a+g≤ 150 m(70 m)
Ex) 8 indoor units
a+b+c ≤ 150 m(70 m)
Equivalent
length
The distance between an outdoor unit and the farthest indoor unit ≤
175 m(90 m)
Main pipe
length
The main pipe(a) from the outdoor unit to the first Y-joint should be less than
110 m.
Total length
Maximum allowable
length after Y-joint
Y-joint / header joint connection
The distance between an outdoor unit and the farthest indoor unit ≤
150 m(70 m)
The sum of total length of pipes should be less then 300 m(150 m).
Height
H1: The difference in height between an outdoor unit and indoor unit <
50 m(30 m)
Height
H2: The difference in height between indoor units ≤ 15 m
Actual Length
The distance between the header joint
and the indoor unit ≤ 40 m
Ex) b, c ~ f, g ≤ 40 m
The distance between the first Y-joint
and the farthest indoor unit ≤ 40 m
Ex) 8 indoor units
b+c, d+g ≤ 40 m
❋❋ When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90 m, upgrade the low
pressure pipe of the main pipe one step.
❋❋ Values in ( ) are only applied for AM040/050✴XMDBC and AM040/050✴XMKKC.
ENGLISH-22
DVM S ECO_IM_EN_DB68-04650A-04.indd 22
2017-05-19 오후 5:26:20
Refrigerant pipe work
Refrigerant Y-joint installation
Install the Y-joint ‘horizontally’ or ‘vertically’.
ffInstall horizontally
02
Installing the product
ffInstall vertically
NOTE
• When using A~J type of Y-joint, connect the Y-joint to the pipe with the provided reducer.
• When using K~Z type of Y-joint, connect the Y-joint to the pipe by cutting the inlet of the Y-joint or provided
reducer properly.
10~15 mm or more
CAUTION
• Install the Y-joint within ±15° on the horizontal or on the vertical.
• Make sure that the pipe does not break at Y-joint and pipe connection.
• Keep a minimum straight line distance of 500 mm or more before connecting Y- joint.
Connect to other branch joint
or indoor unit
Rear
Reducer
Pipe
Front
Gas/liquid side Y-joint
Main pipe
±15°
Connect to
outdoor unit
Rear
Pipe connection
Reducer
Minimum straight line distance
(500 mm or more)
❋❋ Install the Y-joint within ±15° on the
horizontal or on the vertical.
ENGLISH-23
DVM S ECO_IM_EN_DB68-04650A-04.indd 23
2017-05-19 오후 5:26:21
Refrigerant pipe installation
Correct use
(The insertion depth of connecting pipe)
Incorrect use
(The insertion depth of connecting pipe)
Basic specification
Connecting pipe
Connecting pipe
Connecting pipe
Connecting pipe
When cutting
connection part
CAUTION
• When inserting connecting pipe into the Y-joint, please comply with the installation regulation.
Refrigerant header joint installation
ffSelect the reducer fitted on the diameter of the pipe.
Liquid side
Gas side
Supplied
Reducer
Pipe (Purchased
privately)
Pipe (Purchased
privately)
Reducer
Pipe (Purchased
privately)
Pipe (Purchased
privately)
To indoor unit
To outdoor unit
To indoor unit
Reducer
To outdoor unit
Reducer
ffBlock the unused pipes end with caps if the number of connected indoor unit is fewer than header joint ports.
Liquid side
Gas side
Brazing part
Connection in
order
Connection in
order
Supplied
Block the port of header joint
Reducer
Block the port of header joint
ENGLISH-24
DVM S ECO_IM_EN_DB68-04650A-04.indd 24
2017-05-19 오후 5:26:21
CAUTION
• When using A~J type of header joint, connect the header joint to the pipe with provided reducer.
• When using K~Z type of header joint, connect the header joint to the pipe by cutting the provided reducer
properly.
• Connect the header joint in order respecting the number of the indoor unit.
• Connect the indoor unit as the highest capacity comes first.
02
ffInstall the header joint horizontally.
-- Install the header joint horizontally so that it is not facing down.
Reducer
Header joint
Installing the product
10~15 mm or more
±10° or
less
Should be horizontal
Pipe
Liquid side
Should be horizontal
±15° or
less
Should be horizontal
Should be
horizontal
±15° or less
Should be horizontal
Gas side
±10° or less
ENGLISH-25
DVM S ECO_IM_EN_DB68-04650A-04.indd 25
2017-05-19 오후 5:26:21
Refrigerant pipe installation
Performing air tightening test
ffUse tools for R-410A only to prevent the inflow of foreign substances and to resist the internal pressure.
ffUse dry Nitrogen gas to do an airtight test as below.
Apply pressure to the liquid side pipe, gas
side pipe with Nitrogen gas of 4.1 MPa (gauge
pressure).
If you apply pressure more than 4.1 MPa (gauge pressure), the pipes
may be damaged. Apply pressure using pressure regulator.
Continue to apply pressure for minimum
24 hours to check if the pressure drops.
After applying Nitrogen gas, check the change of pressure using
pressure regulator.
If the pressure drops, check if there is a gas leak.
If the pressure is changed, apply soapy water to check the leak. Check
the pressure of the gas again.
Maintain 1.0 MPa (gauge pressure) of the
pressure before performing vacuum drying and
check for further gas leak.
After checking first gas leak, maintain 1.0 MPa (gauge pressure) to check
for further gas leaks.
Nitrogen gas
CAUTION
• If the joint of high pressure side is disconnected and the nitrogen gas come into contact with human body, injury
may occur. Tighten the joint connection firmly to prevent dangerous situation.
ENGLISH-26
DVM S ECO_IM_EN_DB68-04650A-04.indd 26
2017-05-19 오후 5:26:22
Vacuuming a pipe and an indoor unit
02
ffUse the tools for R-410A only to prevent the inflow of foreign substances and resist
against the internal pressure.
ffUse the vacuum pump with the check valve to prevent pump oil from flowing
backward while the vacuum pump is stopped suddenly.
ffUse the vacuum pump that can be vacuumed up to 666.6 Pa(5 mmHg).
ffClose the service valve of the liquid side pipe, gas side pipe completely when
performing air tightening test or vacuum drying.
Vacuum the liquid pipe and gas pipe
using the vacuum pump.
Make sure to install check valve to prevent pump oil from
flowing into the pipe.
Vacuum those pipes for more than 2 hours
and 30 minutes.
The time of vacuum drying may differ depending on the
length of the pipe or outdoor temperature.
Perform vacuum drying for at least 2 hours and 30 minutes.
Close the valve after checking the vacuum
gauge pressure has reached at -100.7 kPa
(gauge pressure).
Check the vacuum pressure using the vacuum gauge.
Vacuum
pump
Installing the product
Connect the manifold gauge to the liquid
pipe and gas pipe.
Check whether the pressure is maintained
as -100.7 kPa (gauge pressure), 5 torr. for
an hour.
Check the gas leak.
Pressure Increase
Yes
Vacuum destruction due to the
moisture inside the pipe
• Apply pressure with Nitrogen gas of
0.05 MPa (gauge pressure).
No
Charging additional refrigerant according
to piping length
Perform vacuum drying again up to
-100.7 kPa (gauge pressure), 5 torr (for
2 hours or longer) and evaluate the
vacuum
No
CAUTION
Pressure Increase
Yes
• If the pressure rises in an hour, either water remains inside the pipe, or there will be a leak.
ENGLISH-27
DVM S ECO_IM_EN_DB68-04650A-04.indd 27
2017-05-19 오후 5:26:22
Refrigerant pipe installation
Selecting additional refrigerant charging
ffBasic refrigerant
The basic amount of additional refrigerant charged at a factory
Model
Refrigerant
Factory charge(kg)
AM040✴XMDBC
AM040✴XMKKC
2.0
AM050✴XMDBC
AM050✴XMKKC
R-410A
2.0
AM060✴XMDBC
AM060✴XMKKC
2.8
ffCharging additional refrigerant
The amount of additional refrigerant charging
=
The amount of refrigerant charging for pipe +
the amount of refrigerant correction charging for an indoor unit.
1. The amount of additional refrigerant depending on the pipe size.
-- Amount of additional refrigerant has to be calculated based on the sum of all liquid pipe length.
Size of liquid pipe (mm)
6,35
9,52
12,7
15,88
Additional amount (kg/m)
0,02
0,06
0,125
0,18
Additional refrigerant charging calculation = The sum of total length of Ø 9.52 liquid pipe(m) x 60 g + the sum of
total length of Ø 6.35 liquid pipe(m) x 20 g
Ex) a(Ø 9.52)=40 m, b+c+d(Ø 9.52)=15 m, e+f+g(Ø 6.35)=15 m
The amount of additional refrigerant = 55 m x 60 g + 15 m x 20 g = 3600 g
2. The amount of additional refrigerant for each indoor unit
(Unit : kg)
Capacity [kW(Btu/h)]
Model
Slim 1way cassette (JSF) (AM✴✴✴FN1DCH)
2.2
2.8
3.6
4.5
5.6
6
7.1
9
11.2 12.8
14
(7,506) (9,553) (12,283) (15,354) (19,107) (20,472) (24,226) (30,709) (38,215) (43,675) (47,769)
0.25 0.25 0.25
2way cassette (AM✴✴✴FN2DCH)
0.31
0.31
Global 4way cassette (AM✴✴✴FN4DCH)
0.45 0.45
0.45 0.45 0.57 0.69 0.69
360 cassette (AM✴✴✴KN4DC✴)
0.45 0.45
0.45 0.45 0.69 0.69 0.69
Global mini 4way cassette (AM✴✴✴FNNDCH)
0.29 0.29 0.29 0.37 0.37 0.37
Slim duct (AM✴✴✴FNLDCH)
0.24 0.24 0.24 0.24 0.45
0.45 0.42 0.42 0.62 0.62
MSP duct-S (AM✴✴✴FNMDCH)
0.24 0.24 0.24 0.28 0.28
0.28 0.32 0.54 0.68 0.68
Ceiling (AM✴✴✴FNCDCH, AM✴✴✴JNCDCH)
0.39
0.39
0.24 0.24 0.24
0.36
0.36
Boracay (AM✴✴✴KNTDCH)
0.24 0.32 0.32
0.49 0.49 0.49
Boracay (with EEV) (AM✴✴✴KNQDCH)
0.24 0.32 0.32
0.49 0.49 0.49
Neo forte (AM✴✴✴FNTDCH)
HSP duct (AM✴✴✴FNHDCH)
0.56 0.56
0.68 0.68 0.68
Ex) When the indoor unit AM022FN1DEH and AM056FN4DEH are combinated
Additional refrigerant charging = 250 g + 450 g = 700 g
3. The total amount of additional refrigerant charging = the amount of refrigerant charging for pipe + the amount of
refrigerant for each indoor unit.
Ex) The amount of additional refrigerant charging = 3600 g + 700 g = 4300 g
ENGLISH-28
DVM S ECO_IM_EN_DB68-04650A-04.indd 28
2017-05-19 오후 5:26:22
Connecting the drain hose to the outdoor unit
50 mm
Installing the product
13 mm
02
When using the air conditioner in the heating mode, ice may accumulate . During de-icing (defrost operation), the
condensed water must be drained off safely. Consequently, you must install a drain hose on the outdoor unit, following the
instructions below.
ffLeave space of more than 50 mm between the bottom of the outdoor unit and the ground for installation of the drain
hose, as shown in figure.
ffInsert the drain plug into the hole on the underside of the outdoor unit.
ffConnect the drain hose to the drain plug.
ffEnsure that the drained water runs off correctly and safely.
ffBe sure to plug the rest of drain holes not connected with drain plugs using drain caps.
Drain cap
Drain plug
ENGLISH-29
DVM S ECO_IM_EN_DB68-04650A-04.indd 29
2017-05-19 오후 5:26:24
Refrigerant pipe installation
Insulating refrigerant pipe or Y-joint
ffYou must check if there is a gas leak before completing all the installation process. After you check that the gas does not
leak, you must insulate the pipe and hose.
ffUse EPDM insulation which meets the following condition.
Item
Unit
Standard
Density
g/cm3
0.048~0.096
Dimension change route by heat
%
-5 or less
Water absorption rate
g/cm
0.005 or less
Thermal conductivity
kcal/m·h·˚C
0.032 or less
Moisture transpiration factor
ng/(m ·s·Pa)
15 or less
Moisture transpiration grade
g/(m2·24h)
15 or less
Formaldehyde dispersion
mg/L
-
Oxygen rate
%
25 or more
3
2
Selecting the insulation of refrigerant pipe
ffInsulate the gas pipe and liquid pipe by referring to the thickness of insulator for each pipe size.
ffThe standard condition is 30 °C, with humidity less than 85 %. In the conditions of high humidity, use one grade thicker.
Insulation(Cooling, Heating)
Pipe
Pipe size (mm)
Standard
[30 °C, 85 %]
High humidity
[30 °C, 85 % or more]
Ø6.35~Ø9.52
9t
Ø12.70~Ø50.80
13t

Ø6.35
13t
19t
Remarks
EPDM, NBR
Liquid pipe

Ø9.52
Gas pipe
Heat resisting temperature is
more than 120 °C
Ø12.70
Ø15.88
19t
25t
Ø19.05
Ø22.23
ENGLISH-30
DVM S ECO_IM_EN_DB68-04650A-04.indd 30
2017-05-19 오후 5:26:24
Insulating refrigerant pipe
ffYou must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area.
ffIf you insulate the pipes, the condensed water does not fall from the pipes.
ffCheck if there are any insulation cracks on the bent pipe.
Clamp
Insulation
02
Insulation
Gas side pipe
Indoor unit
Liquid side pipe
Install the insulation to be
overlapped
Fix securely without any gap.
Pipe insulation
Pipe insulation after insulating EEV kit
Installing the product
Indoor unit
• The insulation of the gas and liquid pipes can be in contact
• When installing the gas side and liquid side pipes, leave
with each other but they should not press excessively
10 mm of space.
against each other.
• When contacting the gas side and liquid side pipe, use
• When contacting the gas side and liquid side pipe, use
thicker insulation.
thicker insulation.
10 mm
Insulation
10 mm
10 mm
Insulation
Liquid pipe
Gas pipe
CAUTION
Gas pipe
Liquid pipe
• Install the insulation not to be get wider and use adhesive on the connection part of it to prevent moisture
entering.
• Bind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When binding the pipe with
finishing tape, be careful not to reduce the thickness of the insulation.)
• Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.
• When the thickness of insulation is reduced, supplement the reduced thickness with additional insulation.
Hanger
Additional insulation
a
ax3
Insulation for refrigerant pipe
ENGLISH-31
DVM S ECO_IM_EN_DB68-04650A-04.indd 31
2017-05-19 오후 5:26:24
Refrigerant pipe installation
Insulating the header joint
ffFasten the header joint using a cable tie and cover the connected part.
ffInsulate the header joint and the brazing part and wrap the connected part with an
adhesive insulation tape to prevent dew formation.
Adhesive insulation tape
Insulation for the
header joint
Insulation
Insulation after brazing a stopper
Insulation for the
refrigerant pipe
Adhesive insulation tape
ffFix the header joint with a hanger after insulating it.
Insulating the Y-joint, liquid & gas side connecting pipe
ffAttach the insulation provided with the Y-joint to the insulation purchased privately without a gap. Wrap the connected
part with insulation (Purchased privately) of a thickness of at least 10 mm.
ffUse insulation that should be able to handle an interior temperature of over 120 °C. Wrap the Y- joint with insulation of a
thickness of at least 10 mm.
Pipe insulation
Provided insulation
(Purchased privately)
Fix securely without any gap.
Fix securely without
any gap.
150 mm
Y-joint
Insulation tape (Purchased privately)
Pipe insulation (Purchased
privately)
Thickness of the insulation (Purchased privately)
should be at least thicker than 10 mm.
Pipe
Pipe insulation (Purchased privately)
❋❋ Attach the adhesive insulation tape
to the pipe as shown in the picture
after insulating the pipe.
ENGLISH-32
DVM S ECO_IM_EN_DB68-04650A-04.indd 32
2017-05-19 오후 5:26:25
Wiring work
02
Installing the product
ffWiring work should be performed in accordance with related laws such as ‘Technical specification on electric installation’,
‘Wiring regulations’ or ‘Installation manual’.
ffCopper cable should be used for wiring work and all the wires or parts should be rated products.
ffWiring work should be performed by a company certified by an electric power company.
ffRefer to the circuit diagram attached to the outdoor unit for detailed wiring work.
ffWiring work should be performed after disconnecting main circuit breaker and Y-joint switch.
ffYou must perform grounding work .
(Grounding resistance value should be less than 100 Ω.)
When ELCB is installed, protective grounding resistance value can be applied.
(When the ELCB is 100 mA, 0.1sec, protective grounding resistance value should be less than 250 Ω at a place where
electric danger is high and should be less than 500 Ω at other places. )
ffElectric wiring circuit diagram displays outline only.
ffDo not connect a heater to an outdoor unit and do not install a duct which you arbitrarily remodeled.
-- Failure to do so may result in reduced capacity of an air conditioner, electric shock, and fire.
ffDo not connect the grounding wire to that of gas pipe, water pipe, lightning rod, or telephone.
-- Gas pipe: If the gas leaks, explosion or ignition may occur.
-- Water pipe: If rigid vinyl pipe is used, grounding effect will not work.
-- Grounding wire and lightning rod of telephone: The electric potential of grounding wire may rise abnormally in the
falling of a thunderbolt.
ffThe ELB for ground-fault protection only should be combined with MCCB or fuse equipped load breaker switch. In this
case, you should use the one that has at least the same or more capcity as fuse capacity or the rated current of MCCB.
ffUse the wires that comply with regulated specification and firmly connect to the terminal board. Then tighten it with the
screws provided so that the terminal board cannot be moved by external force. (The connecting cable and the grounding
terminal should be locally procured). When wiring, the connection cable shouldn’t be too tight.
ffApply silicon at the end of CD pipe so that rainwater does not enter.
Conduit leading into an outdoor unit
Silicone
ENGLISH-33
DVM S ECO_IM_EN_DB68-04650A-04.indd 33
2017-05-19 오후 5:26:25
Wiring work
Overall System Configuration
Connection of the power cable (1 phase 2 wires)
Distribution board
Outdoor unit
1 phase
2 wires
220 V-240 V~
ELCB
Or
MCCB +
ELB
Indoor unit
1 phase
2 wires
220 V-240 V~
Or
MCCB + ELCB
ELB
220 V
Earth
Communication
cable
Earth
Wired remote
controller
Connection of the power cable (1 phase 2 wires using EEV kit)
Distribution board
1 phase
2 wires
220 V-240 V~
Or
ELCB MCCB +
ELB
Earth
Outdoor unit
Indoor unit
1 phase
2 wires
220 V-240 V~
Or
MCCB + ELCB
ELB
Communication
cable
EEV kit
Wired remote
controller
ENGLISH-34
DVM S ECO_IM_EN_DB68-04650A-04.indd 34
2017-05-19 오후 5:26:25
CAUTION
ffPower supply cord is not supplied with air conditioner.
ffSelect the power supply cord in accordance with relevant local and national regulations.
ffWire size must comply with the applicable local and national code.
ffThe appliance shall be provided with a certified power supply cord and interconnection cord complying with the national
regulations of the countries in which the appliance is to be sold.
ffPower supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC : 60245 IEC 57 / CENELEC : H05RN-F)
Model
Voltage
AM040✴XMDBC
AM050✴XMDBC
MCA
MFA
22
32
24
32
AM060✴XMDBC
32
40
AM040✴XMKKC
22
32
24
32
32
40
AM050✴XMKKC
1phase, 220 V, 60 Hz
1phase, 220 ~ 240 V, 50/60 Hz
AM060✴XMKKC
Installing the product
Specification for circuit breaker and power supply cord
02
• You must install an earth leakage breaker.
-- ELCB(Earth Leakage Circuit Breaker)
-- MCCB(Molded Case Circuit Breaker)
-- ELB(Earth Leakage fuse breaker)
• Manufacturers are not responsible for fire caused by not installing ELCB or MCCB.
• Install the cabinet panel near the outdoor unit for service convenience and emergency operation switch off.
• You must install a circuit breaker that can prevent excess current and shut off the electric leakage on the
outdoorunit.
Ssc value (MVA)
(Note1)
(Note1)Equipment complying with IEC 61000-3-12.
Tightening power terminal
ffConnect the cables to the terminal board using the compressed ring terminal.
ffUse rated cables only.
ffConnect the cables with driver and wrench that can apply the rated torque to the screws.
ffMake sure that appropriate tightening torque is applied for cable connection. If the terminal is loose, arc heat may occur
and cause fire and if the terminal is connected too firmly, terminal may get damaged.
Tightening torque
M4
12.0~18.0 kgf•cm
1.2~1.8 N•m
Communication : F1, F2
M5
20.0~30.0 kgf•cm
2.0~3.0 N•m
1 phase AC power : L1, L2
ENGLISH-35
DVM S ECO_IM_EN_DB68-04650A-04.indd 35
2017-05-19 오후 5:26:25
Wiring work
Selecting compressed ring terminal
ffSelect a compressed ring terminal of a connecting power cable based on a nominal dimensions for cable.
ffCover a compressed ring terminal and a connector part of the power cable and then connect it.
Silver solder
Nominal dimensions for cable (mm2)
Nominal dimensions for screw (mm)
B
D
d1
Standard dimension (mm)
9.5
15
±0.2
16
25
8
8
8
15
16
12
±0.2
±0.2
35
8
8
16.5
16
±0.3
8
22
±0.3
50
70
8
8
22
24
±0.3
±0.4
5.6
7.1
9
11.5
13.3
13.5
17.5
Allowance (mm)
+0.3
-0.2
+0.3
-0.2
+0.3
-0.2
+0.5
-0.2
+0.5
-0.2
+0.5
-0.2
+0.5
-0.4
Standard dimension (mm)
3.4
4.5
5.8
7.7
9.4
11.4
13.3
Allowance (mm)
±0.2
±0.2
±0.2
±0.2
±0.2
±0.3
±0.4
7.9
9.5
12.5
17.5
18.5
9
13
15
13
14
20
34
Min.
Min.
t
8
10
Standard dimension (mm)
F
d2
4
Allowance (mm)
E
L
4/6
6
5
9
11
13
Max.
20
28.5
30
33
50
51
Standard dimension (mm)
4.3
8.4
8.4
8.4
8.4
8.4
8.4
8.4
Allowance (mm)
+ 0.2
0
+0.4
0
+0.4
0
+0.4
0
+0.4
0
+0.4
0
+0.4
0
+0.4
0
1.15
1.45
1.7
1.8
1.8
2.0
Min.
0.9
38
43
ENGLISH-36
DVM S ECO_IM_EN_DB68-04650A-04.indd 36
2017-05-19 오후 5:26:25
Installing grounding wire
ffGrounding must be done by a qualified installer for your safety.
ffUse the grounding wire by referring to the specification of the electric cable of the outdoor unit.
Grounding the power cable
High humidity
Voltage of lower than 150V
Low humidity
Perform the grounding work
3. Note 1)
Perform the grounding work 3 if
possible for your safety. Note 2)
Must perform the grounding work 3. Note 1)
(In case of installing circuit breaker as well)
Voltage of higher than 150V
NOTE
Average humidity
Installing the product
Installation place
Power condition
02
ffThe standard of grounding may vary according to the rated voltage and installation place of the air conditioner.
ffGround the power cable according to the following.
1. Grounding work 3
• Grounding must be done by your installation specialist.
• Check if the grounding resistance is lower than 100Ω. When installing a circuit breaker that can cut the electric
circuit within 0.5 second in case of a short circuit, the allowable grounding resistance should be 30~500Ω.
2. Grounding at dry place
• The grounding resistance is should be lower than 100Ω. (It should not be higher than 250Ω)
-- Use the rated grounding wire by referring to the specification of the electric cable of the outdoor unit.
Performing the grounding work
ffUse the grounding wire by referring to the specification of the electric cable for the outdoor unit.
When using the terminal for grounding only
When using grounding of the switch board
Switch Board
Earth terminal
ENGLISH-37
DVM S ECO_IM_EN_DB68-04650A-04.indd 37
2017-05-19 오후 5:26:26
Grounding work
If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, a ground
rod must be installed.
The corresponding accessories are not supplied with the air conditioner.
1. Select a grounding rod that complies with the specifications given in the illustration.
Copper wire
Carbon rod
Compressed ring terminal (Terminal M4)
PVC-insulated green/yellow wire
2. Select a proper place for the grounding rod installation.
-- In damp hard soil rather than loose sandy or gravel soil that has a higher grounding resistance.
-- Away from underground structures or facilities, such as gas pipes, water pipes, telephone lines and underground
cables.
-- At least two meters away from lightening(as in a storm) conductor.
50 cm
30 cm
CAUTION
• The grounding wire for the telephone line cannot be used to ground the air conditioner.
3. Install a green/yellow coloured grounding wire :
-- Refer to the ‘Wiring work’ for the specification of grounding wire.
-- When the grounding wire is too short, extend the grounding wire but bind the connection part with insulation tape.
(Do not bury the connection).
-- Secure the grounding wire in position with staples.
CAUTION
• When the grounding rod is installed in a place where many people pass by, you must fix it firmly.
4. Carefully check the installation, by measuring the grounding resistance with a ground resistance tester.
-- If the resistance is above required level, drive the grounding rod deeper into the ground or increase the number of
grounding rods.
5. Connect the grounding wire to the electrical component box inside of the outdoor unit.
ENGLISH-38
DVM S ECO_IM_EN_DB68-04650A-04.indd 38
2017-05-19 오후 5:26:26
Setting indoor unit option switch and key function
PBA shape
02
S/W for setting number of connecting indoor units
7-SEGMENT
(DISPLAY)
Installing the product
FLOW SWITCH
External Con
DIP S/W
(K5~K16)
Terminal blocks (R1, R2) for connection with the Upper Controller
(DMS, Touch, On/Off Controller, etc.)
Do not connect wires to these terminal blocks
Setting the number of connecting indoor units
Ex : When you connect 3 indoor units, set SW02 to 3
SW01
SW02
Unit digit
Unit digit
ENGLISH-39
DVM S ECO_IM_EN_DB68-04650A-04.indd 39
2017-05-19 오후 5:26:26
Setting indoor unit option switch and key function
S/W function
Tact switch
Heating KEY operation
Cooling KEY operation
K1
K2
K3
K4
Manual silent option
Snow prevention
Cooling target
evaporating
temperature
Cooling target
evaporating
temperature
K5
K6
K7
K8
Silent mode
Silent mode
Heating capacity
correction
Heating capacity
correction
K9
K10
K11
K12
Total electric current
option
Total electric current
option
Defrost correction
Defrost correction
K13
K14
K15
K16
DIP switch
Reset
View Mode
DIP S/W specification setting
TACT
switch
K1
K2
Number of
presses
Content
Press and hold
1 time
Check operation
1
Heating refrigerant charging
2
Heating trial operation
3
Heating pump out
4
Vacuum
5
Completion
1
Cooling refrigerant charging
2
Cooling trial operation
3
Cooling pump down
4
Checking the amount of refrigerant
5
Completion
K3
SEG1
SEG2
SEG3
SEG4
Remark
Reset
❋❋ If you perform Cooling refrigerant charging or Cooling pump down in high temperature environment,
E407 (High pressure protection control) error or high pressure protection switch may operate.
ENGLISH-40
DVM S ECO_IM_EN_DB68-04650A-04.indd 40
2017-05-19 오후 5:26:27
ffK4 input display order
(1) Current frequency  (2) Low pressure value  (3) Outdoor temperature  (4) Discharge temperature  (5) OLP
temperature  (6) COND temperature  (7) Double pipe out tube temperature  (8) High pressure value  (9) FAN
RPM  (10) ESC(EVI) EEV  (11) MAIN EEV  (12) Present running current  (13) Number of connected indoor units 
(14) Number of operating indoor units  (15) Sum of indoor unit capacity  (16) Mode Master indoor address
Display on segment
0 time
Main Micom version
Version (ex. 0912)
1 time
Inverter Micom version
Version (ex. 0912)
2 times
EEPROM version
Version (ex. 0912)
3 times
Automatically assigned address of the
units
4 times
Manually assigned address of the units
SEG1
SEG2
SEG3, 4
Indoor unit: “A”
Indoor unit: “0”
Address (ex: 05)
SEG1
SEG2
SEG3, 4
Indoor unit: “A”
Indoor unit: “0”
Address (ex: 01)
Installing the product
Displayed content
02
K4(Press and hold to
enter the setting) -> K4
press(Number of press)
ffK5 : Automatic / Manual Silent mode operation setting
Switch
Function (Silent mode operation control)
K5
ON
Automatic silent mode operation
OFF
Manual silent mode operation
❋❋ You can use the Manual silent mode operation, if you set the K5 DIP switch to ‘OFF’ and connect some external contact
switch to the ‘External Con’ port of MAIN PBA (shown in p.39)
ffK6: Snow prevention control option
Switch
Function (Snow prevention control)
K6
ON
Disuse snow prevention control (Default)
OFF
Use snow prevention control
❋❋ When you set the snow prevention control as ‘Use’, outdoor fan will operate for one minute every 30minutes in the
condition of Cooling/heating stop status at below 5 °C.
ffK7, K8: Changing cooling capacity correction table
Switch
K7
K8
Function (Target evaporating temperature)
ON
ON
7 ~ 9 °C (Factory default setting)
ON
OFF
5 ~ 7 °C
OFF
ON
9 ~ 11 °C
OFF
OFF
10 ~ 12 °C
❋❋ Upgrade the performance by referring to the cooling long pipe performance data of the technical data book.
❋❋ If you upgrade the performance at your discretion, low discharge air temperature of an indoor unit might cause
discomfort. This is the option for performance correction during long pipe installation only.
ENGLISH-41
DVM S ECO_IM_EN_DB68-04650A-04.indd 41
2017-05-19 오후 5:26:27
Setting indoor unit option switch and key function
ffK9, K10: Silent mode option. This reduces FAM RPM to operate the outdoor unit quietly during night operation.
Switch
K9
Function (Silent mode)
K10
ON
ON
Disuse Silent mode
ON
OFF
STEP - 1
OFF
ON
STEP - 2
OFF
OFF
STEP - 3
❋❋ Enables the silent mode for night-time in cooling mode.
(It operates automatically depending on the temperature.)
❋❋ However, if the external contact interface module (MIM-B14) is used, entering the silent mode is available with contact
signal in cooling and heating mode.
ffK11, K12: Changing heating capacity correction table
Switch
K11
Function
K12
ON
ON
Default
ON
OFF
Default -196 kPa
OFF
ON
Default - 98 kPa
OFF
OFF
Default + 98 kPa
❋❋ Heating operation increases frequency when current high pressure is higher than target high pressure; vice versa,
decreases frequency. When target high pressure is high, the discharge air temperature of an indoor unit will increase but
energy consumption will increase as well.
❋❋ Maintaining factory default status is recommended. However, if you want to reduce energy consumption or you are not
satisfied with heating performance, control the operation according to the surrounding environment. As you decrease the
target high pressure, energy consumption and noise may decrease but indoor air discharge temperature decreases as well.
ffK13, K14: Changing current limit option table
Switch
K13
Function
K14
4 HP
5 HP
6 HP
ON
ON
Default
Default
Default
ON
OFF
Default - 4(A)
Default - 2(A)
Default - 2(A)
OFF
ON
Default - 6(A)
Default - 4(A)
Default - 4(A)
OFF
OFF
Default - 8(A)
Default - 6(A)
Default - 6(A)
Classification
ø1
Model
Default
4HP
AM040✴XMDBC
AM040✴XMKKC
22A
5HP
AM050✴XMDBC
AM050✴XMKKC
24A
6HP
AM060✴XMDBC
AM060✴XMKKC
32A
ENGLISH-42
DVM S ECO_IM_EN_DB68-04650A-04.indd 42
2017-05-19 오후 5:26:27
ffK15, K16: Defrost Option  This is to control entering condition of defrost mode
Switch
Function
ON
ON
MID
ON
ON
LOW1
OFF
OFF
LOW2
❋❋ Defrost mode will start when the temperature difference between outdoor and outdoor heat exchanger has become
more than certain standard.
❋❋ Factory default status is MID. When the function changes to LOW with option control, defrost entering temperature
decreases. When defrost entering temperature decreases, the operation hour will be long but this means that the
operation hour with the reduced heating capacity increases. This option is used at places where humidity is high and the
defrost mode enters too frequently.
❋❋ Maintaining factory default status is recommended.
Setting the option
Installing the product
K16
02
K15
1. Press and hold K2 to enter the option setting. (Only available when the operation is stopped)
-- If you enter the option setting, display will show the following. (If you have set the ‘Emergency operation for
compressor malfunction’, 1 or 2 will be displayed on Seg 4.)
-- Seg 1 and Seg 2 will display the number for selected option.
-- Seg 3 and Seg 4 will display the number for set value of the selected option.
2. If you have entered option setting, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and select
the desired option. (Refer to pages 45~47 for the Seg number of the function for each option)
Example)

3. If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change
the function for the selected option. (Refer to pages 45~47 for the Seg number of the function for each option)
Example)

4. After selecting the function for options, press and hold the K2 switch for 2 seconds. Edited value of the option will be
saved when entire segments blinks and tracking mode begins.
CAUTION
• Edited option will not be saved if you do not end the option setting as explained in above instruction.
ENGLISH-43
DVM S ECO_IM_EN_DB68-04650A-04.indd 43
2017-05-19 오후 5:26:27
Setting indoor unit option switch and key function
❋❋ While you are setting the option, you may press and hold the K1 button to reset the value to previous setting.
❋❋ If you want to restore the setting to factory default, press and hold the K4 button while you are in the option setting
mode.
-- If you press and hold the K4 button, setting will be restored to factory default but it doesn’t mean that restored setting
is saved. Press and hold the K2 button. When the segments shows that tracking mode is in progress, setting will be
saved.
Optional
item
Channel
address
Input unit
Main
SEG1
0
SEG2 SEG3 SEG4
Function of the
option
A
Automatic setting
(Factory default)
U
0
0 ~ 15
Manual setting for
channel (0 ~ 15)
Remarks
Address for classifying the product from upper
level 0 ~ 15 controller (DMS, S-NET 3, etc.)
Inspection and check operation
CAUTION
Precautions before check operation
• When the outdoor temperature is low, turn on the main power 3 hours before beginning the operation.
-- If you start the operation immediately after turning on the main power, it may cause serious damage to the
part within the product.
• Do not touch the refrigerant pipe during or right after the operation.
-- Refrigerant pipe may be hot or cold during or right after the operation depending on the status of the
refrigerant which flows through the refrigerant pipe, compressor and other parts of the refrigerant cycle. If
you touch the refrigerant during or right after the operation, you may get burns or frostbite.
• Do not operate the product with its panel or protection nets off.
-- There is risk of personal injury from the parts that rotates, heated or with the high voltage.
• Do not turn off the main power immediately after stopping the operation.
-- Wait for at least 5 minutes before turning off the main power. If not, water leakage or other problems may
occur.
• Connect all the indoor units and the power supply for the outdoor unit and run auto or manual address setting.
Run auto or manual address setting after changing the indoor unit PCB.
ENGLISH-44
DVM S ECO_IM_EN_DB68-04650A-04.indd 44
2017-05-19 오후 5:26:27
Inspection before check operation
Check the power cable and communication cable of the indoor and outdoor unit.
Supply power to the outdoor unit 3 hours before check operation to pre-heat the crank case heater.
Before supplying the power, use a voltmeter and phase tester to check the voltage and the phase.
When the power is supplied, outdoor unit will execute tracking to check the indoor unit connection and other options.
Write down the installation report on the service history report paper attached on the front part of the control box.
• Supply power to the outdoor unit 3 hours before check operation to pre-heat the crank case heater.
Installing the product
CAUTION
6. Guaranteed range of check operation
For correct judgment, you must perform check operation in below indoor/outdoor temperature condition.
Outdoor temperature (°C)
50
40
30
20
02
1.
2.
3.
4.
5.
Cooling
Heating
10
0
-10
-20
5
10
15
20
25
30
35
40
45
Indoor temperature (°C)
-- Check operation selects and operates cooling/heating mode automatically.
-- In the temperature range marked with slashed pattern, system protection control may trigger during operation.(It may
be hard to judge the check operation correctly due to protection control operation.)
-- When the temperature is outside of guaranteed range, accuracy of judgment on check operation may decrease near
boarder line area. Inspection and check operation.
ENGLISH-45
DVM S ECO_IM_EN_DB68-04650A-04.indd 45
2017-05-19 오후 5:26:27
Inspection and check operation
Check operation
1. Use KEY MODE to run check operation.
-- When the check operation is not completed, UP (unprepared) will appear on the LED after the communication check
and restrict compressor from operating. (UP Mode will be cleared automatically when check operation is completed.)
-- Check operation may proceed from 30 minutes maximum 50 minutes depending on the operation status.
-- During check operation, noise can be generated due to valve inspection. (Check the product if abnormal noise occurs
continuously)
2. When error occurs during check operation, check the error code and take appropriate measures.
-- Refer to service manual if you need inspection or when other errors occur.
3. When check operation ends, use S-NET pro or S-CHECKER to issue a result report.
-- Refer to service manual for further actions if you have any items with “inspection required” sign on the result report.
-- After taking appropriate measure for the items with “inspection needed” sign, run the check operation again.
4. Check the following items by running (cooling/heating) trial operation.
-- Check if cooling/heating operation performs normally.
-- Individual indoor unit control: Check for air flow direction and fan speed.
-- Check for abnormal operation noise from the indoor and outdoor unit.
-- Check for proper draining from the indoor unit during cooling operation.
-- Use S-NET pro to check the detail operation status.
5. Explain to the user how to use the air conditioner according to the user’s manual.
6. Hand over the installation manual to the customer so they can keep it with them.
Automatic refrigerant amount detection function (Checking th amount of refrigerant)
ENGLISH-46
DVM S ECO_IM_EN_DB68-04650A-04.indd 46
2017-05-19 오후 5:26:27
Charging refrigerant
Gas side
Liquid side
R-410A (Inject
liquid refrigerant)
Manifold gage
Scale
Installing the product
Outdoor unit
02
ffThe R-410A refrigerant is blended refrigerant. Add only liquid refrigerant.
ffMeasure the quantity of the refrigerant according to the length of the liquid side pipe. Add quantity of the refrigerant
using a scale.
ffOpen the manifold gauge valve connected to the liquid side service valve and add the liquid refrigerant.
ffIf you cannot add the whole quantity of the refrigerant while the outdoor unit is stopped, open the gas side and liquid
side service valve. Then, add remaining refrigerant by pressing the refrigerant adding button of the outdoor PCB.
Service valve
Vacuum port
CAUTION
• Open the gas side and liquid side service valve completely after charging the refrigerant. (If you operate the air
conditioner with the service valve closed, the important parts may be damaged.)
• Put on safety equipment when charging refrigerant.
• Do not charge the refrigerant when you adjust or control other product such as indoor units or EEV kits.
• When the ambient temperature is low in winter time, do not heat the refrigerant container to speed up the
charging process. There is risk of explosion.
• Beware for possibility of refrigerant leakage when you connect the manifold gauge to the charging port for
heating.
• Close the valve of the refrigerant container immediately after charging the refrigerant. If not, there might be a
change in entire amount of refrigerant.
ENGLISH-47
DVM S ECO_IM_EN_DB68-04650A-04.indd 47
2017-05-19 오후 5:26:28
Pump Down
The object of pump down
ffYou can reduce as much refrigerant leakage as possible during product movement or repair by collecting the refrigerant
to the outdoor unit.
Caution for pump down procedure
ffThe amount of refrigerant that can be put into an outdoor unit is limited due to the slim shape of the outdoor unit.
ffBefore performing pump down, most of the refrigerant should be put into an empty container at first. The maximum
amount of refrigerant that can be put into the outdoor unit is 5 kg.
ffWhen the amount of system refrigerant exceeds the amount of maximum receptive capacity, compressor trip or damage
by fire might be caused.
Pump down procedure
ffBefore performing pump down, collect the refrigerant into the empty container.
ffTurn off the manifold gage.
ffTurn off the service valve of liquid pipe side.
ffPress K2 button on the outdoor unit PCB three times. (‘ ’ is displayed on outdoor PCB LED.)
ffWhen the compressor starts operating, observe low pressure using manifold gage.
ffWhen the low pressure goes below 0 kg/cm²,g, turn off the service valve at gas side and finish the pump down operation.
(To finish pump down operation, press K2 button one more time or press K3 button one time to be initiated.)
CAUTION
• When putting refrigerant into the refrigerant container, you must use the exclusive container that can be
recharged. When remodeling normal refrigerant container illegally, explosion might occur.
ENGLISH-48
DVM S ECO_IM_EN_DB68-04650A-04.indd 48
2017-05-19 오후 5:26:28
How to put the refrigerant into the refrigerant container before pump down operation
02
Installing the product
❋❋ When the amount of refrigerant charged in the system exceeds maximum receptive capacity, collect the refrigerant into
the refrigerant container at first and then perform the pump down.
ffPrepare the exclusive refrigerant container that can be recharged, scale, and manifold gage that can be recharged.
ffCheck the current amount of refrigerant within the system.
ffAfter connecting the refrigerant container to an outdoor unit, operate 50 % of all indoor units as cooling mode.
ffCheck the pressure of high pressure side for manifold gage after 10 minutes from cooling operation. When the pressure
of high pressure side is above 30 kg/cm²,g decrease the number of operating indoor unit and make the pressure below
30 kg/cm²,g.
ffAfter checking that the pressure of high pressure side went below 30 kg/cm²,g, open the manifold gage side valve(2) that
is connected to the liquid pipe and refrigerant container valve. Then run the refrigerant from liquid pipe to refrigerant
container.
ffCheck whether the proper amount of refrigerant are put into the container using a scale, turn off the valve and remove
the manifold gage.
ffThe amount of refrigerant that can be put into the refrigerant container should be about 50 % of all refrigerant of the
whole system.
ffDo not collect too much refrigerant in one refrigerant container.
Outdoor unit
Gas side
R-410A
Liquid side
Refrigerant
container valve
Valve(1)
Valve(2)
Scale
Manifold gage
Service valve
ENGLISH-49
DVM S ECO_IM_EN_DB68-04650A-04.indd 49
2017-05-19 오후 5:26:28
Others
Checking lists after finishing installation
ffBefore supplying power, measure the power terminal (L, N) and outdoor unit grounding using insulation-resistance
tester.
-- The measured value should be above 30 MΩ.
CAUTION
• You must not measure the communication terminal since the communication circuit may get damaged.
• Check the short circuit using a circuit tester.
Outdoor unit
Installation
Indoor unit
Refrigerant pipe work
• Have you secured air discharge profile at the bottom of service cover?
• Have you checked the external surface and the inside of the outdoor unit?
• Is there any possibility of short circuit due to the heat of an outdoor unit?
• Is the place well-ventilated and ensures space for service?
• Is the outdoor unit fixed securely?
• Have you checked the external surface and the inside of the indoor unit?
• Is the place well-ventilated and has enough space been allowed for service?
• Have you checked if the center of the indoor unit is ensured and it is installed
horizontally?
• Have you selected correct pipes?
• Are the liquid and gas valve open?
• Is the total number of connecting indoor units within the allowable range?
• Are the length and the height difference between the refrigerant pipes within
the allowable range?
• Is the refrigerant Y-joint properly installed?
• Has the connection of liquid and gas pipes been correctly performed?
• Have you chosen correct insulation for pipes and have you insulated them
correctly?
• Is the pipe or connection part properly insulated?
• Is the quantity of the additional refrigerant correctly weighed in? (You must
record the amount of additional refrigerant charging on the service record paper
placed outside the outdoor unit.)
Installing the drain pipe
• Have you checked whether the drain pipes of the indoor unit and outdoor unit
are connected together?
• Have you completed the drain test?
• Is the drain pipe properly insulated?
Wiring work
• Are the power cable and communication cable tightened firmly on the terminal
board within the range of rated tightening torque?
• Have you performed the earthing work 3 to the outdoor unit?
• Is 2-core cable used for the communication cable?
• Is the length of the wire is in the limited range?
• Is the wiring route correct?
Setting ADDRESS
Option
• Are the ADDRESSES of the indoor and outdoor units properly set?
• Are the ADDRESSES of the remote controller properly set?
(When using multiple remote controllers)
• Have you checked whether the vibration-resistance frame is correctly installed if
there is a possible vibration of the outdoor unit.
ENGLISH-50
DVM S ECO_IM_EN_DB68-04650A-04.indd 50
2017-05-19 오후 5:26:28
Trial operation
CAUTION
03Others
ffCheck the power supply between the outdoor unit and the cabinet panel.
-- 1 phase power supply : L, N
-- 3 phase power supply : R,S,T,N
ffCheck the indoor unit.
-- Check whether you have connected the power and communication cables correctly. (The communication cables
between an indoor unit and outdoor unit are F1, F2.)
-- Check the thermistor sensor, drain pump/hose, and display are connected correctly.
ffCheck with Key mode or S-Net Pro.
-- At first, operate all the indoor units with Key mode and operate the indoor units individually with S-Net Pro.
-- In the beginning of operation, check the compressor operation sound. If there is a boom sound, stop the trial operation.
ffCheck the operation status of indoor and outdoor unit.
-- Check whether the cooling operation is done correctly.
-- Check the individual indoor unit control, wind velocity, and wind flow direction.
-- Check whether you can hear abnormal sound from indoor unit and outdoor unit.
-- Check whether the drainage is done correctly in cooling.
-- Check S-net Pro for detailed operation.
ffExplain to the user the usage of the air conditioner by referring to the users manual.
• Turn on the outdoor unit 3 hours before the test operation to preheat the compressor.
• If the compressor is not preheated, ‘CH’ may appear on the outdoor unit PCB depending on the outdoor
temperature.
Writing and keeping installation checking card
ffInstallation checking card is enclosed with the installation manual.
-- Installer should fill out the front side of the card meticulously.
-- Write basic information such as date of installation, name of an installer, contact information, supervision company etc.
-- Write additional information such as the name of outdoor unit models, unusual, calculation of the additional amount of
refrigerant etc.
-- Write indoor unit related information such as indoor unit installation location, indoor unit model name etc.
ffKeep the installation checking card in a designated place and do not lose it.
Installation checking card
ENGLISH-51
DVM S ECO_IM_EN_DB68-04650A-04.indd 51
2017-05-19 오후 5:26:29
DVM S ECO_IM_EN_DB68-04650A-04.indd 52
2017-05-19 오후 5:26:29