Toshiba International Corporation
Uninterruptible Power Systems
1600 Series 18kVA 208/240V In - 208/240/120V Out Tower
Hardwire Solution - UE3G2L180C61T
Toshiba's 1600EP Series is an on-line uninterruptible power supply (UPS) systems
provide continuous computer-grade ac power in a compact, high performance, and
energy efficient unit. The UPS unit assures safe and reliable operation of critical
office equipment. This can range from word processors and personal computers to
mini-computers and local area networks. All units feature an audible alarm which
sounds if the battery voltage drops below standard during use. This is an additional
aid to help in retaining the valuable office data banks. All units allow for computer
interfacing. This model is a hardwire solution. Customers have the options to
choose from a range of different receptacles panels offers by Toshiba. Please refer
to the specification for different line cord and receptacles panels options.
Product Specifications
INPUT
OUTPUT
Voltage
Voltage Range
Frequency
Synchronization window
Power Factor
THD Current
Topology
Voltage
Capacity (VA)
Capacity (W)
Voltage Regulation
Voltage Distortion
Step Load
Rated Current
208/240Vac
168V~264V (+10% to -30%)
50/60 Hz Auto Sensing
± 3Hz
Greater than 0.95
Less than 5% at Full Load
True On-Line, Double Conversion, Input PF Correction
208/240/120Vac
18000
15300
± 3%
Less than 6% THD at Full Non-Linear Load. Less than 3% THD at full Linear Load.
± 8 % max from 100% to 0 % or from 0% to 100 % linear load
75A
UE3G2L180C61T
Toshiba International Corporation
Uninterruptible Power Systems
BATTERY
BATTERY
ENVIRONMENT
Max Peak Current
Overload Capacity
Crest Factor
Frequency
Frequency Regulation
Wave Form
Load Power Factor
Efficiency AC to AC
Common Mode Noise
DC Voltage
Backup Time
Battery type
Number of batteries Pack
Recharge time
Interface
Input
Output
Dimensions WxDxH (mm)
Ship Dimensions WxDxH (mm)
Dimensions W x D x H (inch)
Ship Dimensions WxDxH (inch)
Weight kg (lb)
Ship Weight kg (lb)
External Matching Battery
Cabinet
Network Interface Card
Environmental Monitoring
Device
Operating Ambient Temperature
225A
125% for 30 secs, 150% for 10 secs
3.0 at full load
50/60 Hz Auto Sensing
± 0.5Hz/± 1.0Hz/± 1.5Hz (authorized service center selectable only)
Sine wave, Zero Transfer Time
0.85
Greater than 83%
Less than 0.5 Vrms
288V
7 min (full load) 21 min (half load)
Enersys NPX-35 Flame retardant Lead Acid 9Ah/12V Part #: 51896
3 (Six batteries in each pack)
<12 hours to 90%
RS-232, Dry Contact Connectivity, External Battery Connectivity
Hardwire Input
Hardwire Output
889x457x990
990x610x1168
39x24x46
35x18x39
340 (750)
410 (904)
Single - 25 Mins, Double - 50 Mins. Max Two Cabinets. Part #: UE3-BC-1825
RemotEye II - Part #: RMTI-INT-R25
Part #: RMTI-EMD-HT
0 ~ 40oC (32 ~ 104oF)
+15oC ~ 25oC
Recommended Temperature
CONFORMANCE
Storage Temperature
Humidity
Audible Noise
Altitude
Regulatory Approvals
-20oC ~ 40oC
30-90%, Non-Condensing
50dB (A) maximum @ 1 meter from Front Panel
3300 ft (1,000 m) above sea level
UL, CUL, ISO 9001, NEMA/PEI-1993
UE3G2L180C61T
Toshiba International Corporation
Uninterruptible Power Systems
WARRANTY
Three years on electronics
Two years full replacement on battery (See Toshiba warranty policy for full details)
UE3G2L180C61T

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

advertisement