- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- LG
- L4UC608FA0
- Installation Guide
LG L4UC608FA0 Installation guide
Add to my manuals35 Pages
The LG L4UC608FA0 Multi Type Ceiling Duct Air Conditioner is a versatile and efficient cooling solution for a variety of indoor spaces. With its powerful performance and advanced features, this air conditioner delivers optimal comfort and energy savings.
advertisement
▼
Scroll to page 2
of 35
website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG LG Multi Type Air Conditioner INSTALLATION MANUAL IMPORTANT • Please read this installation manual completely before installing the product. • When the power cord is damaged, replacement work shall be performed by authorized personnel only. • Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Multi Type Ceiling Duct Air Conditioner Installation Manual TABLE OF CONTENTS Installation Requirements Required Tools Installation Parts Provided .........................................3 Safety Precautions ......................................................4 Installation of indoor, outdoor unit............................7 Connecting Pipes to the Indoor Unit.......................19 ❏ Level gauge ❏ Screw driver ❏ Electric drill ❏ Hole core drill (ø50mm) ❏ Horizontal meter Connecting Pipes to the Outdoor Unit....................24 Connection of the Cable...........................................25 ❏ Flaring tool set ❏ Specified torque wrenches 1.8kg.m, 4.2kg.m, 5.5kg.m, 6.6kg.m (different depending on model No.) ❏ Spanner .................Half union Air Purging of the Connecting Pipes and the Indoor Unit...........................................................27 ❏ A glass of water ❏ Screw driver Checking the Drainage and Forming the Piping ...................................................................24 Group Control............................................................28 Two Thermistor System ............................................28 E.S.P (External Static Pressure) Setting.................29 How to set E.S.P?......................................................30 Test Running..............................................................32 2 Multi type Air Conditioner ❏ Hexagonal wrench(4mm) ❏ Gas-leak detector ❏ Vacuum pump ❏ Gauge manifold ❏ Owner's manual ❏ Thermometer ❏ Holder Remote Control Installation Parts Provided Installation Parts Provided Standard Type Indoor Unit Air filters Air outlet vents Air intake vents Remote Controller Air intake vents Air outlet vents Remote Controller Outdoor Unit Air outlet vents (Rear) (Side) Air intake vents Control cover Connecting wire Piping Drain hose Installation Manual 3 Safety Precautions Safety Precautions To prevent injury to the user or other people and property damage, the following instructions must be followed. ■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications. WARNING This symbol indicates the possibility of death or serious injury. CAUTION This symbol indicates the possibility of injury or damage. ■ Meanings of symbols used in this manual are as shown below. Be sure not to do. Be sure to follow the instruction. WARNING Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit. • There is risk of fire or electric shock. Always ground the product. • There is risk of fire or electric shock. 4 Multi type Air Conditioner For electrical work, contact the dealer, seller, a qualified electrician or an Authorized Service Center. • Do not disassemble or repair the product. There is risk of fire or electric shock. Install the panel and the cover of control box securely. • There is risk of fire or electric shock. Safety Precautions Always intstall a dedicated circuit and breaker. • Improper wiring or installation may cause fire or electric shock. Do not modify or extend the power cable. • There is risk of fire or electric shock. For installation, always contact the dealer or an Authorized Service Center. Use the rated breaker or fuse correctly. • There is risk of fire or electric shock. Be cautious when unpacking and installing the product. • Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator. Do not install the product on a defective installation stand. • There is risk of fire, electric shock, explosion or • It may cause injury, accident or damage to the injury. product. Be sure the installation area does not deteriorate with age. Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open. • If the base collapses, the air • Moisture may condense and conditioner could fall with it, wet or damage furniture. causing property damage, product failure and personal injury. Do not store or use flammable gas or combustibles near the prodcut. • There is risk of fire or failure of product. Gasolin Installation Manual 5 Safety Precautions CAUTION Always check for gas (refrigerant) leakage after installation or repair of product. • Low refrigerant levels may cause failure of product. Keep level even when installing the product. • To avoid vibration or water leakage. 90° 6 Multi type Air Conditioner Install the drain hose to ensure that water is drained away properly. • A bad connection may cause water leakage. Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods. • It may cause a problem for your neighbors. Installation of Indoor, Outdoor Unit Installation of Indoor, Outdoor Unit Selection of the best location 1) Indoor unit • Do not have any heat or steam near the unit. • Select a place where there are no obstacles in front of the unit. • Make sure that condensation drainage can be conveniently routed away. • Do not install near a doorway. • Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. • Use a stud finder to locate studs to prevent unnecessary damage to the wall. Inspection hole (600X600) Control box Top view (unit: mm) 600 600 Front Front view H More than 5cm More than 5cm More than 5cm More than 2.3m 2) Outdoor unit • If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. • There should not be any animals or plants which could be affected by hot air discharged. • Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. 1000 Select location Install the air conditioner in the location that satisfies the following conditions. • The place shall easily bear a load exceeding four times the indoor unit’s weight. • The place shall be able to inspect the unit as the figure. • The place where the unit shall beleveled. • The place shall allow easy water drainage.(Suitable dimension “H” is necessary to get a slope to drain as figure.) • The place shall easily connect with the outdoor unit. • The place where the unit is not affected by an electrical noise. • The place where air circulation in the room will be good . • There should not be any heat source or steam near the unit Fence or obstacles More than 120cm More than 90cm Fe ob nce sta or cle s More than 90cm More than 90cm More than 90cm Installation Manual 7 Installation of Indoor, Outdoor Unit Piping length and elevation Distributor Type Capacity (Btu/h) 60K (m) Total Length With Distributor None Distributor Max Main Pipe Total Branch Length (A/B) Pipe Length Max Branch Max Elevation In - In Pipe Length (h1/h2) Elevation (h3) 50 A = 25 25 15 20 7.5 30 B = 30 - - 20 7.5 Distributor Branch Pipe A h3 B h1 h2 Main Pipe Distributor Type CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters. NOTICE When installing 36k Btu/h indoor unit, use the short tube connector. (not branch distributor type) 8 Multi type Air Conditioner Short tube connector (for A-UNIT) Installation of Indoor, Outdoor Unit Piping installation Case 1 Ø12.7/6.35 12,000 Btu/h Indoor Unit Distributor (3 room) Ø15.88/6.35 Circuit 1 (TPS Cycle) Ø12.7/6.35 Ø12.7/6.35 12,000 Btu/h Indoor Unit 12,000 Btu/h Indoor Unit Ø15.88/6.35 Circuit 2 (Single cycle) 24,000 Btu/h Indoor Unit Case 2 Ø15.88/6.35 Circuit 1 (TPS Cycle) Distributor (2 room) Ø12.7/6.35 18,000 Btu/h Indoor Unit or 24,000 Btu/h Indoor Unit Ø15.88/6.35 (at 24,000 Btu/h Indoor Unit) Ø12.7/6.35 18,000 Btu/h Indoor Unit or 12,000 Btu/h Indoor Unit Ø15.88/6.35 Circuit 2 (Single cycle) 24,000 Btu/h Indoor Unit Case 3 Ø15.88/6.35 Circuit 1 (TPS Cycle) 36,000 Btu/h Indoor Unit Ø15.88/6.35 Short tube Circuit 2 (Single cycle) 24,000 Btu/h Indoor Unit Installation Manual 9 Installation of Indoor, Outdoor Unit Indoor unit installation ■ Installation of Unit Install the unit above the ceiling correctly. A B CASE 1 C E POSITION OF SUSPENSION BOLT D • Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. • Apply a filter Accessory at air return hole. F (G) (Unit:mm) Dimension B C D E 18K BTU/h 948 880 355 45.5 450 24K BTU/h 30K BTU/h 1232 1180 315 45.5 450 36K BTU/h F (G) H I 30 87 750 163 30 87 830 186 H 1-3 mm A I Capacity Drainage hole CASE 2 • Install the unit leaning to a drainage hole side as a figure for easy water drainage. M10 Nut X4 (Local M10 SP. washer X 4 supply) M10 washer X4 POSITION OF CONSOLE BOLT • A place where the unit will be leveled and that can support the weight of the unit. • A place where the unit can withstand its vibration. • A place where service can be easily performed. 10 Multi type Air Conditioner M10 washer X4 (Local M10 SP. washer X 4 supply) M10 Nut X4 Installation of Indoor, Outdoor Unit • Select and mark the position for fixing bolts. • Drill the hole for set anchor on the face of ceiling. • Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. • Mount the suspension bolts to the set anchor firmly. • Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers. Old building New building 1 Set anchor 2 Plate washer 3 Spring washer 4 Nut CAUTION: Tighten the nut and bolt to prevent unit falling 5 Suspension bolts • Local supply Set anchor Plate washer Spring washer Nut Suspension bolt - M10 - M10 - W3/8 or M10 - W3/8 or M10 Installation Manual 11 Installation of Indoor, Outdoor Unit CAUTION 1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm. Front of view • The unit must be horizontal or declined to the drain hose connected when finished installation. 1~3mm Ceiling CORRECT INCORRECT Drainage hole CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING • Always lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part. • 5mm or thicker formed thermal insulator shall always be provided for the drain pipe. Drainage hole Lay the drain hose with a downward inclination so water will drain out. Thermal insulator (Local supply) Drainage pipe (Local supply) Unit Make sure to be closed. Drainage hole • Upward routing not allowed CORRECT INCORRECT Applied U-Trap Dimension • Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter. 12 Multi type Air Conditioner A ≥ 70mm B ≥ 2C C ≥ 2 x SP SP = External Pressure (mmAq) Ex) External Pressure = 10mmAq A ≥ 70mm B ≥ 40mm C ≥ 20mm B C U-Trap A Installation of Indoor, Outdoor Unit • Drill the piping hole with 70mm dia, hole core drill. • Piping hole should be slightly slant to the outdoor side. Indoor WALL Outdoor 5~7mm INSULATION, OTHERS THERMAL INSULATION Insulate the joint and tubes completely. All thermal insulation must comply with local requirement. INDOOR UNIT Union for liquid pipe Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply) Refrigerant pipe and thermal insulator(Local supply) Hose clip for thermal insulator (Local supply) Overlap with thermal insulator for piping. Hose clip for thermal insulator(Local supply) Make sure that there is no clearance here. Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe REFRIGERANT PIPE • Insulate and tape the gas piping. Power cable Tape Gas pipe Liquid pipe Thermal insulator TEST AND CHECK ■ After all workings are finished, check the working and operation. • Air distribution • Drain • Gas leakage • Wiring • Lock-bolt Is Is Is Is Is the the the the the air circulation good? drainage smooth and no sweating? piping connection correct? wiring connection correct? lock-bolt of compressor loosened? Installation Manual 13 Installation of Indoor, Outdoor Unit INSTALLATION OF REMOTE CONTROL BOX Install the remote control box and cord correctly. POINT OF REMOTE CONTROLLER INSTALLATION • Although the room temperature sensor is in the indoor unit, the remote control box should be installed in such places away from direct sunlight and high humidity. INSTALLATION OF THE REMOTE CONTROL BOX • Select places that is not splashed by water. • Select control position after receiving customer approval. • The room temperature sensor of the thermostat for temperature control is built in the indoor unit. • This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see. (The standard height is 1.2~1.5m high) ROUTING OF THE REMOTE CONTROL CORD • Keep the remote control cord away from the refrigerant piping and the drain piping. • To protect the remote control cord from electrical noise, place the cord at least 5cm away from other power cables. (Audio equipment, Television set, etc) • If the remote control cord is secured to a wall, provide a trap at the top of the cord to prevent water droplets from running. ELECTRICAL WIRING TO THE INDOOR UNIT Remote controller (Main board) CN REMO CN REMO Make sure that wire and terminal numbers are matched on unit side and remote controller side. The maximum length of the cord is 100m. If the length of the cord exceeds 50m, use a wire size greater than 0.5mm2. DISASSEMBLING OF THE REMOTE CONTROLLER Front case Th el ow er pa rt Lever carefully the box open using a screw driver, etc. Remote control box body WHEN THE REMOTE CONTROL BOX IS INSTALLED WITH THE CORD BURIED. PROCEDURE OF INSTALLATION 1. Fix the under plate on the switch box by screws(Local supply). In this case, fit the under plate on the wall, and be careful of deformation. 2. Receive the remote control cord in the switch box. 3. Hook the remote control unit on the under plate. Face of wall Upper notch Under plate Remote control unit Screw (Local supply) Remote control cord Lower notch Switch box (Local supply) 14 Multi type Air Conditioner WHEN THE REMOTE CONTROL BOX IS INSTALLED WITH THE CORD EXPOSED. PROCEDURE OF INSTALLATION 1. Fix the under plate on the wall by self tapping screws (accessory). 2. Make a slit (Part A) at the top side of the remote control box by nipper. 3.Rout the cord as shown in the following figure. In this case, push the cord into the around of case(Part B). 4. Hook the remote control unit on the under plate. Remote control cord (Part A) Face of wall Upper notch Under plate Tapping screw (Local supply) Upper flange Push hand (Part B) Remote control unit Lower notch Cord clamp FIXING OF REMOTE CONTROL CORD 1. Fix the cord clamps on the wall by ø3 tapping screws(Local supply). 2. Fix the remote control cord. Installation of Indoor, Outdoor Unit WIRED REMOTE CONTROLLER INSTALLATION • Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature. Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature. Do not install the remote controller where it can be affected by: - Drafts, or dead spots behind doors and in corners. - Hot or cold air from ducts. - Radiant heat from sun or appliances. - Concealed pipes and chimneys. - Uncontrolled areas such as an outside wall behind the remote controller. - This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's, the remote controller should be installed properly as shown in Fig.1. (The standard height is 1.2~1.5 m from floor level.) AUTO SWING OPERATION SET TEMP Room Temp Operation unit 03 FAN SPEED HI MED LO Time Timer On Off Set no. Time 01 ZONE SUB FUNCTION AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4 Program set 05 07 09 11 13 15 17 19 21 23 yes AUTO SWING OPERATION SET TEMP Room Temp Operation unit 03 FAN SPEED HI MED LO Time Timer On Off Set no. Time 01 ZONE SUB FUNCTION AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4 Program set 05 07 09 11 13 15 17 19 21 23 no TEMP SET Temp Room ION FUNCT t SUB Preheafy D Heater Humidi door SPEE AUTO Defrost Out 4 FAN 3 HI JET Filter 2 1 MED 23 LO 21 ZONE ATION OPER G SWIN 19 17 Time set 15 13 Program11 AUTO 09 r Time Off Time Onno. Set 07 unit ion 05 Operat 03 01 5feet (1.5meters) no no Fig.1 Typical locations for remote controller Installation Manual 15 Installation of Indoor, Outdoor Unit Perform the work according to the Service Manual or Installation Guide. REFRIGERANT PIPING • Use two spanners when connecting the refrigerant pipe to the unit. • Make a bend with a radius as large as possible. • Perform air purge with R-22 or vacuum drying. • When piping work is finished, check all joints. Indoor Flared connection (Union) Use a seemliness tube Factory charged ■ Add refrigerant if piping over 7.5m(at 30g/m, non distributor type). ■ Add refrigerant if piping over 3m(main pipe), 4.5m(branch pipe) as shown below, distributor type. Pipe Liquid Gas Branch Pipe Main Pipe Additional 15.88 6.35 30g/m 12k Btu/h 12.7 6.35 20g/m 18k Btu/h 12.7 6.35 20g/m 24k Btu/h 15.88 6.35 30g/m INSTALLATION OF OUTDOOR UNIT Outdoor Flared connection (Service valve, Ball valve) Select a location that satisfies the following conditions. Install the unit firmly in place. ■ Select the following location • A place where the air conditioner can get good ventilation. • A place where it shall not annoy the neighbors. • A place where the unit shall be leveled and that can support the weight of unit and withstand its vibrations. ■ Keep a maintenance space * One side must be 90Cm for service. Above 90Cm Above 90Cm Above 90Cm *Above 90Cm 16 Multi type Air Conditioner Installation of Indoor, Outdoor Unit ELECTRICAL WIRING Perform the electrical wiring work according to the electrical wiring connection. • All wiring must comply with local requirements. • Select a power source that is capable of supplying the current required by the air conditioner. • Use a recognized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted. • Capacity of circuit breaker(at 3 Phase, 25A). Circuit Breaker Main power source Switch box Outdoor Indoor Control terminal board Control box A A view WIRING CONNECTION INDOOR UNIT • Remove the control box cover for electrical connection between the indoor and outdoor unit. (Remove screws ➀.) • Use the cord clamper to fix the cord. 1 1 Remote control cord Cord clamper Connection cord between the indoor unit and the outdoor unit Control box cover (On which the Electric Wiring Connection is put) OUTDOOR UNIT • Remove the control cover for wiring connection. • Use the cord clamper to fix the cord. • Earthing work Connect the cable of diameter 1.6mm2 or more to the earthing terminal provided in the control box and do earthing. Please check !! Terminal board Cover control Installation Manual 17 Installation of Indoor, Outdoor Unit How to fix installation plate The wall you select should be strong and solid enough to prevent vibration Installation Plate 1. Mount the installation plate on the wall with type "A" screws. If mounting the unit on a concrete wall, use anchor bolts. • Mount the installation plate horizontally by aligning the centerline using a level. (SR, ST) C Installation plate B D 2. Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely. Type "A" screw A Ø70mm Left rear piping CHASSIS (Grade) Ø70mm Right rear piping Distance (mm) SR(12k) A 0 B 40 C 20 D 40 ST(18k~24k) 105 0 210 0 18 Multi type Air Conditioner Connecting Pipes to the Indoor Unit Connecting Pipes to the Indoor Unit Preparation of Piping Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure. Copper tube Slanted Uneven Rough 90° 1) Cut the pipes and the cable. ■ Use the accessory piping kit or the pipes purchased locally. ■ Measure the distance between the indoor and the outdoor unit. ■ Cut the pipes a little longer than measured distance. ■ Cut the cable 1.5m longer than the pipe length. Pipe Reamer Point down 2) Burrs removal ■ Completely remove all burrs from the cut cross section of pipe/tube. ■ Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing. Flare nut Copper tube 3) Putting nut on ■ Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work) 4) Flaring work ■ Carry out flaring work using flaring tool as shown below. Outside Diameter 1/4" 3/8" 1/2" 5/8" 3/4" "A" 0~0.5 0.5~0.8 0.5~0.8 0.8~1.0 1.0~1.3 Handle Bar Bar "A" Yoke Cone Copper pipe Clamp handle Red arrow mark Smooth all round Inside is shining without scratches. Firmly hold copper tube in a bar(or die) as indicated dimension in the table above. = Improper flaring = 5) Check ■ Compare the flared work with figure. ■ If flare is noted to be defective, cut off the flared section and do flaring work again. Even length all round Inclined Surface Cracked Uneven damaged thickness Installation Manual 19 Connecting Pipes to the Indoor Unit 6) Pipe bending Annealed copper pipe with small diameter (ø6.35 or ø9.52) can be easily bent manually. In this case, secure large R(radius) for the bend section and gradually bend pipe. If annealed copper pipe is large in diameter (ø15.88 or ø19.05), bend pipe with bender. Use bender appropriate for the pipe diameter. 7) Brazing In refrigerant piping, bending (in particular, acute bending) must be minimized to reduce piping resistance. Bending is, however, necessary in some places by virtue of the installation position of devices auxiliary to the packaged air conditioner, or of the building structure, piping distance or finishing appearance. If a more acute bend is required than that attainable by pipe bender, perform brazing using ready-made elbow. Aside from this function, brazing also serves to connect straight pipes, generally using ready-made sockets. While brazing, protect piping against heat with wet cloth to avoid damaging valve packing or burning thermal insulator with burner heat. While brazing, blow inert gas (nitrogen gas or carbonic gas) to prevent formation of oxidation film in copper piping; otherwise, the refrigerant circuit will clog. The blowing of nitrogen gas (or carbonic gas) through 3-way valves is described in the following: 8) Refrigerant piping(Flare piping) When connecting piping, be sure to keep piping dry(keep piping away from water), clean (keep piping away from dust) and airtight (avoid refrigerant leakage). When connecting piping on rainy days or making a through-hole in wall, take due care to prevent water or plaster from entering piping. CAUTION: a. This procedure is designed to prevent formation of oxidation film by filling piping with inert gas. Note that excessive gas pressure will generate pinholes at brazed points. (Nitrogen gas: Supply pressure 0.05~0.1kg/cm2G) b. When supplying inert gas, be sure to open one end of piping. 20 Multi type Air Conditioner Water enters Plaster enters Connecting Pipes to the Indoor Unit Connection of piping - Indoor Preparing the indoor unit's piping and drain hose for installation through the wall. 1. Route the indoor tubing and the drain hose in the direction of rear left or right Drain hose 2. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit. Loop CAUTION: If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended. Connecting cable Drain hose Gas side piping Liquid side piping Indoor unit installation 1. Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right. Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound). Connecting cable Drain hose Installation Manual 21 Connecting Pipes to the Indoor Unit Connecting the pipings to the indoor unit and drain hose to drain pipe 1. Align the center of the pipings and sufficiently tighten the flare nut by hand. Indoor unit tubing Flare nut Pipings 2. Tighten the flare nut with a wrench. Outside diameter mm inch Ø6.35 1/4 Ø9.52 3/8 Ø12.7 1/2 Ø15.88 5/8 Torque kg.m 1.8 4.2 5.5 6.6 Spanner (fixed) Flare nut Torque wrench Connection pipe Indoor unit tubing 3. When extending the drain hose at the indoor unit, install the drain pipe. Drain pipe Indoor unit drain hose Adhesive Wrap the insulation material around the connecting portion. Vinyl tape(narrow) Plastic bands Insulation material 1. Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there is no gap. 2. Wrap the area which accommodates the rear piping housing section with vinyl tape. Indoor unit pipe Connection pipe Vinyl tape Wrap with vinyl tape (wide) Connecting cable Pipe Vinyl tape(narrow) 3. Bundle the piping and drain hose together by wrapping them with vinyl tape over the range within which they fit into the rear piping housing section. Wrap with vinyl tape Pipe Vinyl tape(wide) Drain hose 22 Multi type Air Conditioner Connecting Pipes to the Indoor Unit CAUTION: Installation Information (For right piping) For right piping, follow the instruction below. Good case • Press on the upper side of clamp and unfold the tubing to downward slowly. Bad case • Following bending type from left to right could cause problem of pipe damage. Installation Manual 23 Connecting Pipes to the Outdoor Unit Connecting Pipes to the Outdoor Unit 1) Connecting the pipes to the Outdoor unit 1. Align the center of the pipings and sufficiently tighten the flare nut with fingers. 2. Finally, tighten the flare nut with torque wrench until the wrench clicks. • When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow on the wrench. NOTICE Pipe size Torque 1/4" 1.8kg.m 3/8" 4.2kg.m 1/2" 5.5kg.m 5/8" 6.6kg.m : When installing 36K Btu/h Indoor Unit, use the short tube connector. (not branch distributor type) Outdoor unit Gas side piping Short tube connector (for A-UNIT) Liquid side piping Torque wrench Checking the Drainage and Forming the Piping 1) Checking the Drainage 1. Remove the Air Filter. 2. Check the drainage. • Spray one or two glasses of water upon the evaporator. • Ensure that water flows drain hose of indoor unit without any leakage. 24 Multi type Air Conditioner Checking the Drainage and Forming the Piping 2) Form the pipings 1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings) • If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.) Seal a small opening around the pipings with gum type sealer. Taping Drain hose Plastic band Pipings Connecting cable In case of the Outdoor unit being installed below position of the Indoor unit. Power supply cord 2. Tape the Pipings, drain hose and Connecting Cable from bottom to top. 3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent. • Trap is required to prevent water from entering into electrical parts. In case of the Outdoor Unit being installed above position of the Indoor Unit. Seal a small opening around the pipings with gum type sealer. 2. Tape the Pipings and Connecting cable from bottom to top. Trap 3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room. 4. Fix the pipings onto the wall by saddle or equivalent. Trap Connection of the Cable WARNING: Make sure that the screws of the terminal are free from looseness. 1) Clamping of cables 1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. Installation Manual 25 Checking the Drainage and Forming the Piping 2) Connection of the cable Outdoor Unit 1. Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following. 2. Secure the cable onto the control board with the holder (clamper). 3. Reflix the cover control to the original position with the screw. 4. Use a recongnized circuit breaker between the power source and the unit. A disconnection device to a adequately disconnect all supply lines must be fitted. Power cord Terminal on the OUTDOOR UNIT 1(L) 2(N) 3 1(L) 2(N) Terminal board R 3 S T N Cover control 5 6 7 Terminal on the INDOOR UNIT 3(L) 4(N) 5 6 7 Terminal on the INDOOR UNIT A-UNIT B-UNIT CAUTION: The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA). The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H07RN-F approved by HAR or SAA). ø8.5mm OTHER MODELS NORMAL CROSS-SECTIONAL AREA 2.5mm2 GN /YL ø7.5mm 3(L) 4(N) NORMAL CROSS-SECTIONAL AREA 0.75mm2 GN /YL 20 mm 20 mm CAUTION: After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. • Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. • Proper starting power is not given to the compressor. 26 Multi type Air Conditioner Air Purging of the Connecting Pipes and the Indoor Unit Air Purging of the Connecting Pipes and the Indoor Unit The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor. 1. Confirm that both the liquid side valve and the gas side valve are set to the closed position. 2. After connecting the piping, check the joints for gas leakage with gas leak detector. 3. Remove the service port nut, and connect the gauge manifold and the vacuum pump to the service port by the charge hose. 4. Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 76cmHg. 5. Remove the valve stem nuts, and fully open the stems of the 2-way and 3-way valves with a hexagon wrench. 6. Tighten the valve stem nuts of the 2-way valve and 3-way valve. 7. Disconnect the charge hose and fit the nut to the service port. (Tightening torque: 1.8kg.m) Indoor unit Liquid side Closed Outdoor unit 2-way valve/ 3-way valve Gas side 3-way valve Closed Vaccum pump OPEN CLOSE Installation Manual 27 Group Control Group Control It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent. Main PCB RED(12V) YL(SIGNAL) BR(GND) Indoor Unit 1 Indoor Unit 2 Terminal(Local Supply) Block Connector Terminal(Local Supply) Block Connector RED(12V) YL(SIGNAL) BR(GND) Main PCB #1 YL(SIGNAL) BR(GND) YL(SIGNAL) BR(GND) Indoor Unit 16 Terminal(Local Supply) Block Connector Main PCB #2 .... YL(SIGNAL) BR(GND) .... AUTO SWING OPERATION SET TEMP Room Temp Operation unit 03 FAN SPEED HI MED LO Time Timer On Off Set no. Time 01 ZONE YL(SIGNAL) BR(GND) Main PCB #16 Connecting Cable(Local Supply) SUB FUNCTION AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4 Program set 05 07 09 11 13 15 17 19 21 23 Wired Remote Controller (Standard) Single Group Slide Switch2 Remote Controller PCB Two Thermistor system • Open the rear cover of Remote Controller to set up the mode. Slide Switch1 Slide Switch2 Room Temp. Sensing Remo. Indoor Unit 2 TH(Remo.+Indoor) Single Group CAUTION • On installing, don't impact to the PCB and LCD display. • Don't remove the protection sheet. • Use the specified screw. • On installing, turn off the main power. 28 Multi type Air Conditioner • Selectable options are three as follows. - Remo: Sensing the room Temperature. - Indoor Unit: Sensing the intake air into indoor Unit. - 2 TH: Sensing the lower temperature of the two thermistors. • To set up the mode, adjust the slide switch to desired mode position on installing. E.S.P.(External Static Pressure) Setting E.S.P.(External Static Pressure) Setting (1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. ■ Without Zone System 1. Position V-H, F-H: • This position sets the maximum E.S.P as a default set. 2. Position V-L: • This position sets the minimum E.S.P as a default set. ■ With Zone System 1. Position V-H: • Maximum E.S.P setting & Fan speed is varied according to the state of dampers by micom. 2. Position F-H: • Maximum E.S.P setting & Fan speed doesn't vary according to the opening & Closing of dampers. 3. Position V-L: • Minimum E.S.P setting & Fan speed is varied according to the state of dampers by micom. *Maximum: 18K/24K-8mmAq Minimum: All-0mmAq (3) Move the slide switch to set position. TH R14H OP3 SW TH V-L R13H OP2 REMO MAIN 2TH CO1H OP1 R19H R11H OP5R16H OP4 R15H OP7 R18H R17H F-H OP6 LO STAND C070 V-H R12H R03S HI R04S HIGH R01S R02S SW Slide switch for ceiling height (4) Close the rear cover and check if it works normally. CAUTION: • Select the position after checking duct work and E.S.P of the unit. • Maunfactured in the position F-H. Installation Manual 29 How to Set E.S.P? How to Set E.S.P? Procedure of RPM change: Ex) External Static pressure is 4mmAq for Model Name "L2NC246BRA0" • To protect the unit, compressor is designed to be off during E.S.P. setting. 1 Push the "On/Off" button. The unit will start. AUTO SWING OPERATION SET TEMP FAN SPEED Room Temp AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4 Time Timer Operation unit On Off Set no. Time 01 2 03 Program set 05 07 09 11 13 15 AUTO SWING OPERATION SET TEMP Room Temp 19 21 FAN SPEED 23 Operation unit 03 SUB FUNCTION HI MED LO AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4 Time Timer On Off Set no. Time 01 Program set 05 07 09 11 13 15 17 19 21 23 Push the "Up" of "Down" button for E.S.P adjustment. And, adjust the number which you want.(In this example, the number is "190". Refer to the table 1 on the next page.) AUTO SWING OPERATION SET TEMP Room Temp FAN SPEED Operation unit 03 SUB FUNCTION HI MED LO AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4 Time Timer On Off Set no. Time 01 NOTICE 17 Push the "Timer" and "Wind" button simultaneously for more than 3 seconds. Timer 3 SUB FUNCTION HI MED LO Program set 05 07 09 11 13 15 17 19 21 23 : The range of selection is from 1~254. Since, the display is two Digit only. If the range selection is above 100 then the third digit will appear in the screen as shown. 4 Shift the fan speed mode by pressing the fan speed button. And then, Adjust numbers of next steps by repeating the stage 3. (In this example, the numbers are "220" and "235" respectly) 5 Push the "Timer" and "Wind" button simultaneously for more than 3 seconds. Then, Wind Data is memorized by the EEPROM of the main PCB. AUTO SWING OPERATION SET TEMP Room Temp AUTO Heater Preheat JET Defrost Humidify Filter Out door ZONE 1 2 3 4 Time Timer Operation unit 30 Multi type Air Conditioner 03 SUB FUNCTION HI MED LO Timer On Off Set no. Time 01 FAN SPEED Program set 05 07 09 11 13 15 17 19 21 23 How to Set E.S.P? [Table. 1] Static Pressure(mmAq) Capacity 18K Btu/h 24K Btu/h 30K Btu/h 36K Btu/h 0 2 4 16.5 CMM 235 230 225 215 180 14.5 CMM 245 238 235 230 215 13 CMM 254 252 248 245 240 18 CMM 220 205 190 50 1 16.5 CMM 235 230 220 200 100 Step(Hi/Med/Lo) 6 8 10 Setting Value 14 CMM 250 240 235 230 210 26.5 CMM 153 150 150 148 130 1 23 CMM 173 173 175 175 170 155 20 CMM 190 190 190 190 190 190 32 CMM 230 230 225 220 150 1 29 CMM 240 238 237 235 230 220 26.5 CMM 245 245 243 243 240 240 Note: 1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function. 2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies. Installation Manual 31 Test Running Test Running 1. Check that all tubing and wiring have been properly connected. 2. Check that the gas and liquid side service valves are fully open. Prepare remote control Remove the battery cover by pulling it according to the arrow direction. Insert new batteries making sure that the (+) and (–) of battery are installed correctly. Reattach the cover by pushing it back into position. NOTICE : • Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries. • Remove the batteries from the remote control if the system is not going to be used for a long time. Evaluation of the performance Operate unit for 15~20 minutes, then check the system refrigerant charge: 1. Measure the pressure of the gas side service valve. 2. Measure the temperature of the intake and discharge of air. 3. Ensure the difference between the intake temperature and the discharge is more than 8°C 4. For reference, the gas side pressure of optimum condition is as below.(Cooling) Outside ambient Refrigerant TEMP. R-22 35°C (95°F) The pressure of the gas side service valve. 4~5kg/cm2G(56.8~71.0 P.S.I.G.) NOTICE If the actual pressure are higher than shown, the system is most likely over-charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added. The air conditioner is now ready for use. 32 Multi type Air Conditioner Intake temperature Discharge air Discharge temperature Test Running PUMP DOWN This is performed when the unit is to be relocated or the refrigerant circuit is serviced. Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas. CAUTION: Be sure to perform Pump Down procedure with the unit cooling mode. Pump Down Procedure 1. Connect a low-pressure gauge manifold hose to the charge port on the gas side service valve. 2. Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas. 3. Close the liquid side service valve(all the way in). 4. Turn on the unit's operating switch and start the cooling operation. 5. When the low-pressure gauge reading becomes 1 to 0.5kg/cm2 G(14.2 to 7.1 P.S.I.G.), fully close the gas side valve stem and then quickly turn off the unit. At that time, Pump Down has been completed and all refrigerant gas will have been collected in the outdoor unit. Installation Manual 33 Memo 34 Multi type Air Conditioner P/No.: 3828A20433B
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project